Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:45:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11319.84 | 997.76 | 997.76 |
Net Site Energy | 11319.84 | 997.76 | 997.76 |
Total Source Energy | 22700.52 | 2000.88 | 2000.88 |
Net Source Energy | 22700.52 | 2000.88 | 2000.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1309.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 765.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 581.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 69.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 163.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3214.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5007.11 | 6312.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1309.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 765.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 581.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 69.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 163.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3214.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1309.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 765.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 581.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 69.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 163.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3214.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.88 | 398.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 222.47 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.34 | 556.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.88 | 398.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 222.47 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.34 | 556.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5007.112 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5007.112 | 100.00 |
Total On-Site and Utility Electric Sources | 5007.112 | 100.00 |
Total Electricity End Uses | 5007.112 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 65.49 | 1.90 |
Air to Air Heat Recovery for Heating | 3380.07 | 98.10 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3445.56 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.00 |
Time Setpoint Not Met During Occupied Cooling | 467.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7663.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 21-DEC-19:30 | - | - | - | - | - | - | - | - | - | - | 19-APR-20:49 |
Heating | 0.00 | 286285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 139019.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31552.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42689.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3946.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4047.07 | 268207.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2354.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 396959.82 | 642113.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 286285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 139019.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42689.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3946.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4047.07 | 268207.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1056.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1057.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1419.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2425.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2475.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1840.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 518.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.39 | 3484.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15857.52 | 6843.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 125.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 45.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 307.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1397.72 | 603.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 125.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 45.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 307.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1397.72 | 603.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.96 | 0.509119 | 0.431000 | 1.28 | 1.00 | 0.500000 | 0.000748 | 0.000048 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.449090 | 0.113804 | 0.431000 | 0.193558 | 0.431000 | 0.500000 | 0.003348 | 0.000036 | 0.193558 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.278163 | 0.212766 | 0.431000 | 0.119888 | 0.567377 | 0.500000 | 0.001791 | 0.000014 | 0.119888 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.223554 | 0.559834 | 0.431000 | 0.096352 | 1.00 | 0.500000 | 0.000681 | 0.000021 | 0.101592 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.133189 | 0.542134 | 0.431000 | 0.057405 | 1.00 | 0.500000 | 0.000703 | 0.000014 | 0.067412 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.01 | 0.014831 | 0.431000 | 1.73 | 0.431000 | 0.500000 | 0.025689 | 0.000087 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.88 | 0.076508 | 0.431000 | 0.810717 | 0.431000 | 0.500000 | 0.004980 | 0.000103 | 0.810717 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.95 | 0.167462 | 0.431000 | 2.57 | 0.446566 | 0.500000 | 0.002275 | 0.000261 | 2.57 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.89 | 0.627921 | 0.431000 | 0.814682 | 1.00 | 0.500000 | 0.000607 | 0.000129 | 0.814682 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.68 | 0.094190 | 0.431000 | 1.16 | 0.431000 | 0.500000 | 0.004045 | 0.000107 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.81 | 0.089915 | 0.431000 | 1.21 | 0.431000 | 0.500000 | 0.004237 | 0.000111 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.79 | 0.050799 | 0.431000 | 1.20 | 0.431000 | 0.500000 | 0.013490 | 0.000070 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.985388 | 0.318696 | 0.431000 | 0.424702 | 0.849855 | 0.500000 | 0.001195 | 0.000083 | 0.424702 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5470.87 | 0.000048 | 114.09 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4097.34 | 0.000036 | 108.09 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1553.03 | 0.000014 | 36.23 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2358.80 | 0.000021 | 64.37 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1565.23 | 0.000014 | 42.72 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9957.42 | 0.000087 | 211.43 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11725.41 | 0.000103 | 279.40 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29870.87 | 0.000261 | 684.38 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 7206.30 | 0.000063 | 205.93 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 7211.17 | 0.000063 | 206.07 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 41162.50 | 0.000360 | 1176.25 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 41270.21 | 0.000361 | 1179.33 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7206.30 | 0.000063 | 205.93 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 7211.17 | 0.000063 | 206.07 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14778.79 | 0.000129 | 371.76 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2202.89 | 0.000019 | 62.95 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2202.78 | 0.000019 | 62.94 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10571.45 | 0.000092 | 302.08 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12263.01 | 0.000107 | 277.06 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12648.92 | 0.000111 | 285.16 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7984.01 | 0.000070 | 171.40 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9498.33 | 0.000083 | 255.53 |
VAV WITH REHEAT HEATING COIL | 274186.14 | 0.002399 | 4253.48 |
FLR_3_DOAS HEATING COIL | 20913.38 | 0.000183 | 324.43 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.47 | 0.000063 | 0.000380 |
ROOM_2_FLR_3 FAN COIL | 1.43 | 0.000063 | 0.000371 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.38 | 0.000360 | 0.002156 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.59 | 0.000361 | 0.002050 |
ROOM_5_FLR_3 FAN COIL | 1.29 | 0.000063 | 0.000333 |
ROOM_6_FLR_3 FAN COIL | 1.26 | 0.000063 | 0.000325 |
ROOM_1_FLR_6 FAN COIL | 0.389700 | 0.000019 | 0.000101 |
ROOM_2_FLR_6 FAN COIL | 0.380050 | 0.000019 | 0.000098 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.71 | 0.000092 | 0.000448 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.47 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.43 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.38 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.59 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.29 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.26 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.389700 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.380050 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.71 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000380 | 1.47 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000371 | 1.43 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008459 | 12.80 | 0.008459 | 0.002156 | 8.38 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008680 | 12.80 | 0.008500 | 0.002050 | 7.59 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000333 | 1.29 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000325 | 1.26 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000101 | 0.389700 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000098 | 0.380050 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008575 | 12.80 | 0.008500 | 0.000448 | 1.71 | |
VAV WITH REHEAT COOLING COIL | 28.29 | 6.70 | 0.007820 | 10.55 | 0.007820 | 0.013592 | 26.89 | 475263.29 |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.005475 | 11.72 | 0.005475 | 0.001291 | 2.05 | 45136.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.52 | 11.66 | 27.05 | 11.66 | 26.89 | 26.89 | 0.300000 | 0.433429 | 26.89 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.89 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.89 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013592 | 0.000035 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002399 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001291 | 0.000369 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000183 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.021144 | 3452.11 | |
HEATSYS1 PUMP | 0.004769 | 1436.19 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004769 | 0.572270 |
COOLSYS1 | 0.021144 | 2.54 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 545116.30 | 545116.30 | 0.004769 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.021144 | 2390.01 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.021144 | 739291.66 | 740001.03 | 84.36 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.38_SHGC_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1527 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.9324E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1717 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.9683E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1091 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2955E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3971E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4607E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1739 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.5745E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1963 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1080 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1208 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3719E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.9373E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9973E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7455E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1621E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8716E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6274E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7733E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1091E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3283E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5348E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7455E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1621E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8716E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6274E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7733E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1091E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3283E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5348E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33087.20211 | 33087.20211 | 2.96172 | 2.96172 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 27.04267 | 5.46480E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5016.74229 | 5016.74229 | 0.44909 | 0.44909 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3268.64566 | 3268.64566 | 0.17259 | 0.17259 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3107.18566 | 3107.18566 | 0.27816 | 0.27816 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.16000 | 5.47412E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1039.74147 | 1039.74147 | 5.49024E-002 | 9.17347E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2497.79450 | 2497.79450 | 0.22355 | 0.22355 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 32.81467 | 5.47359E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1923.95756 | 1923.95756 | 0.10159 | 0.10159 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1488.12338 | 1488.12338 | 0.13319 | 0.13319 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1276.64495 | 1276.64495 | 6.74116E-002 | 6.74116E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44795.34178 | 44795.34178 | 4.00956 | 4.00956 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2561.93058 | 2561.93058 | 0.13527 | 0.13527 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20993.49558 | 20993.49558 | 1.88101 | 1.88101 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8253.95369 | 8253.95369 | 0.43583 | 0.67639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66472.44216 | 66472.44216 | 5.95261 | 5.95261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 18885.70935 | 18885.70935 | 0.99724 | 1.89399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12173.47048 | 12173.47048 | 1.46827 | 1.46827 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7206.47952 | 7206.47952 | 0.38274 | 0.38274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11892.68393 | 11892.68393 | 1.43440 | 1.43440 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7211.35252 | 7211.35252 | 0.38300 | 0.38300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 69480.57723 | 69480.57723 | 8.37994 | 8.37994 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 41163.02834 | 41163.02834 | 2.18631 | 2.18631 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 62924.48302 | 62924.48302 | 7.58986 | 7.58986 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 41270.73483 | 41270.73483 | 2.19203 | 2.19203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10669.15095 | 10669.15095 | 1.28683 | 1.28683 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.43733 | 5.46540E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7206.47952 | 7206.47952 | 0.38274 | 0.38274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10425.27500 | 10425.27500 | 1.25741 | 1.25741 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7211.35252 | 7211.35252 | 0.38300 | 0.38300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21117.49198 | 21117.49198 | 1.89021 | 1.89021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90000 | 5.47527E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11289.65079 | 11289.65079 | 0.59615 | 0.59615 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3231.01989 | 3231.01989 | 0.38970 | 0.38970 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2202.94064 | 2202.94064 | 0.11700 | 0.11700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3151.01728 | 3151.01728 | 0.38005 | 0.38005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2202.83713 | 2202.83713 | 0.11699 | 0.11699 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14149.29770 | 14149.29770 | 1.70663 | 1.70663 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 10571.65365 | 10571.65365 | 0.56148 | 0.56148 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29935.29875 | 29935.29875 | 2.68312 | 2.68312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7309.81091 | 7309.81091 | 0.38599 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31359.14726 | 31359.14726 | 2.81069 | 2.81069 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7460.16630 | 7460.16630 | 0.39393 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31051.32794 | 31051.32794 | 2.78716 | 2.78716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2847.63130 | 2847.63130 | 0.15035 | 0.36735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11008.90844 | 11008.90844 | 0.98539 | 0.98539 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.47527E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7679.03298 | 7679.03298 | 0.40549 | 0.40549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 408990.79 | 26.89392 | 26.89392 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 262966.05 | 7.73802 | 7.73802 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42510.28 | 22.42710 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69708.81 | 6.70531 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.96172 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50912 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.27650 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.48352E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.78616E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.27650 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5470.87205 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.78616E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 114.08561 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44909 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11380 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19356 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34785E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.58453E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19356 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4097.33554 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.58453E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 108.08564 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27816 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21277 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11989 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56738 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79070E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35866E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11989 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1553.03016 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35866E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.22877 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22355 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55983 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.63520E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.80559E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06358E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10159 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2358.80407 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06358E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 64.37285 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13319 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54213 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.74046E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.02778E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36933E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.74116E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1565.22944 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36933E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.71626 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.00956 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.48311E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72812 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56893E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.71118E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72812 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9957.41649 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.71118E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.42562 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.88101 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.65081E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81072 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.97987E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02579E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81072 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11725.40925 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02579E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 279.40449 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.95261 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16746 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56557 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44657 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27514E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61323E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56557 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29870.86727 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61323E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 684.38163 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.46827 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.46827 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.30438E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.79501E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51727E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.79501E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.46827 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7206.29596 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.30438E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 205.92800 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.43440 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.43440 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.30865E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.70783E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51762E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.70783E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.43440 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7211.16886 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.30865E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 206.06721 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.37994 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.37994 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.60108E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.15558E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81651 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45928E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45928E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.15558E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.37994 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 41162.50169 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60108E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1176.25268 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.58986 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.58986 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.61050E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.04952E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81553 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68032E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04952E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.58986 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 41270.20696 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61050E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1179.32981 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.28683 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.28683 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.30438E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.32727E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51861E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.32727E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.28683 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7206.29596 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.30438E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 205.92800 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25741 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25741 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.30865E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.25145E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51888E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25145E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25741 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7211.16886 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.30865E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 206.06721 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.89021 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62792 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81468 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.06764E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29291E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81468 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14778.78894 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29291E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 371.76112 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38970 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.38970 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.92718E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.00698E-004 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51629E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.00698E-004 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.38970 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2202.88759 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92718E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 62.94713 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38005 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.38005 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.92709E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.82149E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51667E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.82149E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.38005 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2202.78408 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92709E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 62.94417 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.70663 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.70663 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.24836E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.48107E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81583 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57512E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.48107E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.70663 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 10571.44884 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.24836E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 302.07559 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.68312 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.41901E-002 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15642 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04501E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07282E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15642 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12263.01335 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07282E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.05970 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81069 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.99151E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21141 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23733E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10658E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21141 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12648.92350 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10658E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.15935 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.78716 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.07987E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20127 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34900E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.98476E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20127 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7984.00754 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.98476E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.40078 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98539 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31870 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42470 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84986 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19550E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.30955E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42470 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9498.32912 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30955E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 255.52838 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.52273 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65660 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 27.04547 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65660 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.89392 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.89392 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43343 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.89392 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.89392 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.28724 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.55121 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81981E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81981E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 475263.29231 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.35925E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.89392 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 274186.13777 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39870E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4253.47875 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.89392 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.35925E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.50334E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39870E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.72145 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45136.60304 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29090E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20913.37763 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82959E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.43145 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29090E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.68882E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82959E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.11436E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3452.11162 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.76892E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.57227 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.76892E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1436.18783 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 545116.30092 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 545116.30000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.76892E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.11436E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.53724 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.11436E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2390.01331 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.11436E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 739291.65985 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 740001.03000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 84.36012 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5499.65 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4115.41 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1560.58 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2369.02 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1572.01 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10009.25 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11781.83 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 30017.61 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7765.24 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7770.49 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 44355.25 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 44471.29 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7765.24 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7770.49 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14846.69 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2373.69 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2373.58 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11391.10 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12323.76 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12711.67 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8025.32 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9539.76 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 180531.30 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 13769.91 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15447.10 | 11965.73 | 3481.37 | 0.77 | 1336.03 | 13.55 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15092.07 | 11690.48 | 3401.58 | 0.77 | 1305.34 | 13.24 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 93479.88 | 73387.63 | 20092.25 | 0.79 | 8989.08 | 91.17 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 82939.94 | 63678.43 | 19261.50 | 0.77 | 7216.76 | 73.20 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13542.57 | 10489.65 | 3052.92 | 0.77 | 1171.36 | 11.88 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13233.86 | 10250.38 | 2983.48 | 0.77 | 1144.67 | 11.61 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4098.93 | 3175.31 | 923.62 | 0.77 | 354.51 | 3.60 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3997.80 | 3096.90 | 900.90 | 0.77 | 345.76 | 3.51 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18202.25 | 14055.22 | 4147.03 | 0.77 | 1577.68 | 16.00 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 486357.98 | 324435.40 | 161922.58 | 0.67 | 47944.28 | 486.28 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 44280.81 | 27957.13 | 16323.69 | 0.63 | 4887.02 | 49.57 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1770838825E-002 | 2.2619268789E-002 | Pass | Pass | 1.1107118300E-002 | 2.9504644792E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7389510751E-002 | 9.7762407613E-002 | Pass | Pass | 3.9688923374E-002 | 4.5620909144E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7708801996E-002 | 2.9702981690E-002 | Pass | Pass | 7.5905702825E-003 | 1.8994043337E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4133301408E-002 | 1.4422726616E-002 | Pass | Pass | 8.5696750294E-003 | 2.4748908093E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6433040238E-003 | 1.1086321526E-002 | Pass | Pass | 1.6959537543E-002 | 3.0853691678E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1383162465E-002 | 9.9453565962E-002 | Pass | Pass | 2.0020404636E-002 | 5.5592278127E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3906324034E-002 | 7.7144329690E-002 | Pass | Pass | 1.8290218517E-002 | 2.5347948272E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6743704734E-002 | 4.0043220654E-002 | Pass | Pass | 1.1388629805E-002 | 2.2697997416E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5203352529E-002 | 0.1890756396 | Pass | Pass | 0.1481122398 | 0.2848694337 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.1656708264E-002 | 0.2201992224 | Pass | Pass | 0.1442317192 | 0.5377825528 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6929732612E-002 | 3.5057525214E-002 | Pass | Pass | 0.1197935909 | 0.6593994104 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5614608443E-002 | 8.2184825923E-002 | Pass | Pass | 0.3588800519 | 2.1070854539 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3263994837E-002 | 0.2575406956 | Pass | Pass | 0.1971055890 | 0.4824166267 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4473542195E-002 | 0.2084204017 | Pass | Pass | 8.9233915251E-002 | 0.2718558217 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5374459796E-002 | 1.4983462645E-002 | Pass | Pass | 8.4365415587E-003 | 2.2362788936E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.4415034944E-002 | 0.1917289701 | Pass | Pass | 0.1355588314 | 0.3569670777 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1019315448 | 0.2865998954 | Pass | Pass | 8.9005026876E-002 | 0.2883389508 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3691752472E-002 | 0.2932993034 | Pass | Pass | 1.0932265318 | 10.3375577295 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1558503059E-002 | 5.5277846401E-002 | Pass | Pass | 1.6638257111E-002 | 4.8884413743E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3532958387E-002 | 4.0670649999E-002 | Pass | Pass | 1.6179336083E-002 | 4.6133770899E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.5752432934E-002 | 4.6342598733E-002 | Pass | Pass | 2.2232771455E-002 | 4.4076800590E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0528370907E-002 | 2.5687495396E-002 | Pass | Pass | 2.7434480123E-002 | 3.7720624590E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4754.29 | 135.03 | 1642.49 | 7998.24 | 3746.83 | 18276.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.381 | 0.420 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.381 | 0.420 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.381 | 0.420 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.381 | 0.420 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.52 | 0.0000 | Y | 14.03 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.54 | 0.0000 | Y | 109.80 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.34 | 0.0000 | Y | 30.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.34 | 0.0000 | Y | 30.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.00 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.67 | 83.67 | 193.79 | |
Exterior Lighting Total | 12338.45 | 193.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 545116.30 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 740001.03 | 2.96 | 740131.10 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13269.57 | 15447.10 | 11965.73 | 3481.37 | 0.77 | - | 1336.03 | 13.55 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12964.74 | 15092.07 | 11690.48 | 3401.58 | 0.77 | - | 1305.34 | 13.24 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75371.84 | 93479.88 | 73387.63 | 20092.25 | 0.79 | - | 8989.08 | 91.17 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 71663.05 | 82939.94 | 63678.43 | 19261.50 | 0.77 | - | 7216.76 | 73.20 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11634.07 | 13542.57 | 10489.65 | 3052.92 | 0.77 | - | 1171.36 | 11.88 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11368.98 | 13233.86 | 10250.38 | 2983.48 | 0.77 | - | 1144.67 | 11.61 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3520.99 | 4098.93 | 3175.31 | 923.62 | 0.77 | - | 354.51 | 3.60 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3434.17 | 3997.80 | 3096.90 | 900.90 | 0.77 | - | 345.76 | 3.51 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15668.45 | 18202.25 | 14055.22 | 4147.03 | 0.77 | - | 1577.68 | 16.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 475263.29 | 486357.98 | 324435.40 | 161922.58 | 0.67 | - | 47944.28 | 486.28 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45136.60 | 44280.81 | 27957.13 | 16323.69 | 0.63 | - | 4887.02 | 49.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5470.87 | 5499.65 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4097.34 | 4115.41 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1553.03 | 1560.58 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2358.80 | 2369.02 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1565.23 | 1572.01 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9957.42 | 10009.25 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11725.41 | 11781.83 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29870.87 | 30017.61 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7206.30 | 7765.24 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7211.17 | 7770.49 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 41162.50 | 44355.25 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 41270.21 | 44471.29 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7206.30 | 7765.24 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7211.17 | 7770.49 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14778.79 | 14846.69 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2202.89 | 2373.69 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2202.78 | 2373.58 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 10571.45 | 11391.10 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12263.01 | 12323.76 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12648.92 | 12711.67 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7984.01 | 8025.32 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9498.33 | 9539.76 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 274186.14 | 180531.30 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20913.38 | 13769.91 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.47 | 1033.13 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.43 | 1009.30 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.38 | 5896.43 | 703.64 | 1.00 | 0.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.59 | 5340.50 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.29 | 905.46 | 703.64 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.26 | 884.76 | 703.64 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.39 | 274.21 | 703.64 | 1.00 | 1.55 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.38 | 267.42 | 703.64 | 1.00 | 1.56 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.71 | 1200.85 | 703.64 | 1.00 | 1.09 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.89 | 60259.56 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.021144 | 3452.11 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004769 | 1436.19 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.021144 | 2390.01 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33087.20 | 33087.20 | 16.72 | 2.962 | 2.962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00923 | 27.04 | 0.00546 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5016.74 | 5016.74 | 74.80 | 0.449 | 0.449 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00892 | 33.41 | 0.00547 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3107.19 | 3107.19 | 40.01 | 0.278 | 0.278 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00936 | 33.16 | 0.00547 | 0.092 | 0.00 |
MECH_FLR_1 | 2497.79 | 2497.79 | 15.21 | 0.224 | 0.224 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00862 | 32.81 | 0.00547 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1488.12 | 1488.12 | 15.70 | 0.133 | 0.133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00869 | 33.75 | 0.00548 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44795.34 | 44795.34 | 574.01 | 4.010 | 4.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00853 | 33.90 | 0.00548 | 0.000 | 0.00 |
CAFE_FLR_1 | 20993.50 | 20993.50 | 111.16 | 1.881 | 1.881 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.00998 | 33.41 | 0.00547 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66472.44 | 66472.44 | 50.81 | 5.953 | 5.953 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00989 | 33.53 | 0.00547 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12173.47 | 12173.47 | 311.96 | 1.468 | 1.468 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11892.68 | 11892.68 | 304.80 | 1.434 | 1.434 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00547 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 69480.58 | 69480.58 | 2833.18 | 8.380 | 8.380 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00846 | 33.53 | 0.00547 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 62924.48 | 62924.48 | 2565.15 | 7.590 | 7.590 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00868 | 33.75 | 0.00548 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10669.15 | 10669.15 | 273.41 | 1.287 | 1.287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00852 | 27.44 | 0.00547 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10425.28 | 10425.28 | 267.20 | 1.257 | 1.257 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00852 | 26.60 | 0.00546 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21117.49 | 21117.49 | 54.23 | 1.890 | 1.890 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00935 | 33.90 | 0.00548 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3231.02 | 3231.02 | 82.80 | 0.390 | 0.390 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3151.02 | 3151.02 | 80.76 | 0.380 | 0.380 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14149.30 | 14149.30 | 576.80 | 1.707 | 1.707 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00858 | 33.53 | 0.00547 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29935.30 | 29935.30 | 90.26 | 2.683 | 2.683 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01036 | 33.90 | 0.00548 | 1.188 | 0.00 |
DINING_FLR_6 | 31359.15 | 31359.15 | 94.55 | 2.811 | 2.811 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01028 | 33.90 | 0.00548 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31051.33 | 31051.33 | 300.58 | 2.787 | 2.787 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01005 | 32.57 | 0.00547 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11008.91 | 11008.91 | 26.71 | 0.985 | 0.985 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00892 | 33.90 | 0.00548 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.36 | 0.00096 | -17.90 | 0.00096 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3268.65 | 3268.65 | 48.73 | 0.173 | 0.173 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00757 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1039.74 | 1039.74 | 13.39 | 0.055 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00748 | -17.90 | 0.00096 | 0.092 | 0.00 |
MECH_FLR_1 | 1923.96 | 1923.96 | 11.71 | 0.102 | 0.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00735 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1276.64 | 1276.64 | 13.47 | 0.067 | 0.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00743 | -17.90 | 0.00096 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2561.93 | 2561.93 | 32.83 | 0.135 | 0.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00734 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 8253.95 | 8253.95 | 43.70 | 0.436 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00762 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 18885.71 | 18885.71 | 14.44 | 0.997 | 1.894 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00753 | -17.90 | 0.00096 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7206.48 | 7206.48 | 184.68 | 0.383 | 0.383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7211.35 | 7211.35 | 184.82 | 0.383 | 0.383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 41163.03 | 41163.03 | 1678.49 | 2.186 | 2.186 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 41270.73 | 41270.73 | 1682.42 | 2.192 | 2.192 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7206.48 | 7206.48 | 184.68 | 0.383 | 0.383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7211.35 | 7211.35 | 184.82 | 0.383 | 0.383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | -17.90 | 0.00096 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 11289.65 | 11289.65 | 28.99 | 0.596 | 0.596 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -17.90 | 0.00096 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2202.94 | 2202.94 | 56.45 | 0.117 | 0.117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00763 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2202.84 | 2202.84 | 56.46 | 0.117 | 0.117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00763 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10571.65 | 10571.65 | 430.96 | 0.561 | 0.561 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00764 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7309.81 | 7309.81 | 22.04 | 0.386 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00772 | -17.90 | 0.00096 | 1.188 | 0.00 |
DINING_FLR_6 | 7460.17 | 7460.17 | 22.49 | 0.394 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00773 | -17.90 | 0.00096 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2847.63 | 2847.63 | 27.57 | 0.150 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00708 | -17.90 | 0.00096 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7679.03 | 7679.03 | 18.63 | 0.405 | 0.405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.89 | 26.89 | 7.74 | 7.74 | 26.8939 | 11.6566 | 26.8939 | 0.4334 | 0.3000 |
FLR_3_DOAS | 22.43 | 2.05 | 6.71 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5470.872 | 5470.872 | 1.276503 | 0.00004786 | 114.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5470.87 | 5470.87 | 1.276503 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5501.62 | 5501.62 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4097.336 | 4097.336 | 0.193558 | 0.00003585 | 108.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4097.34 | 4097.34 | 0.193558 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00756923 | 39.7491 | 3268.65 | 0.00 | 4117.85 | 4117.85 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1553.030 | 1553.030 | 0.119888 | 0.00001359 | 36.229 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1553.03 | 1553.03 | 0.119888 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00748395 | 39.3049 | 1039.74 | 0.00 | 1561.32 | 1561.32 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2358.804 | 2358.804 | 0.101592 | 0.00002064 | 64.373 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2358.80 | 2358.80 | 0.101592 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00735398 | 38.6304 | 1923.96 | 0.00 | 2370.50 | 2370.50 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1565.229 | 1565.229 | 0.067412 | 0.00001369 | 42.716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1565.23 | 1565.23 | 0.067412 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00743152 | 39.0329 | 1276.64 | 0.00 | 1572.99 | 1572.99 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9957.416 | 9957.416 | 1.728122 | 0.00008711 | 211.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9957.42 | 9957.42 | 1.728122 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00733917 | 38.5552 | 2561.93 | 0.00 | 10013.03 | 10013.03 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11725.409 | 11725.409 | 0.810717 | 0.00010258 | 279.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11725.41 | 11725.41 | 0.810717 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00762001 | 40.0120 | 8253.95 | 0.00 | 11787.66 | 11787.66 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29870.867 | 29870.867 | 2.565574 | 0.00026132 | 684.382 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 29870.87 | 29870.87 | 2.565574 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00753173 | 39.5528 | 18885.71 | 0.00 | 30031.29 | 30031.29 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13269.565 | -999.000 | 1.468267 | 0.00037950 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13269.57 | 13226.90 | 1.468267 | 21.82 | 13.52 | 0.00851727 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851727 | 44.3541 | 12173.47 | 0.00 | 9971.09 | 9971.09 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7206.296 | 7206.296 | 0.382743 | 0.00006304 | 205.928 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7206.30 | 7206.30 | 0.382743 | 21.11 | 12.45 | 0.00755030 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00755030 | 39.3818 | 7206.48 | 0.00 | 7768.48 | 7768.48 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12964.740 | -999.000 | 1.434400 | 0.00037078 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12964.74 | 12922.21 | 1.434400 | 21.82 | 13.52 | 0.00851762 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00851762 | 44.3559 | 11892.68 | 0.00 | 9742.23 | 9742.23 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7211.169 | 7211.169 | 0.383001 | 0.00006309 | 206.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7211.17 | 7211.17 | 0.383001 | 21.11 | 12.45 | 0.00755062 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00755062 | 39.3835 | 7211.35 | 0.00 | 7773.73 | 7773.73 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75371.844 | -999.000 | 8.379940 | 0.00215558 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 75371.84 | 75371.84 | 8.379940 | 21.82 | 13.48 | 0.00845928 | 12.80 | 10.18 | 0.00845928 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00845928 | 44.0555 | 69480.58 | 0.00 | 60360.69 | 60360.69 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 41162.502 | 41162.502 | 2.186313 | 0.00036011 | 1176.253 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 41162.50 | 41162.50 | 2.186313 | 21.11 | 12.48 | 0.00758072 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00758072 | 39.5369 | 41163.03 | 0.00 | 44374.21 | 44374.21 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 71663.053 | -999.000 | 7.589857 | 0.00204952 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 71663.05 | 69328.06 | 7.589857 | 21.82 | 13.66 | 0.00868032 | 12.80 | 10.21 | 0.00850000 | 33.75 | 0.00547504 | 15.02 | 0.0000 | 21.11 | 0.00868032 | 45.1928 | 62924.48 | 0.00 | 54326.95 | 54326.95 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 41270.207 | 41270.207 | 2.192034 | 0.00036105 | 1179.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 41270.21 | 41270.21 | 2.192034 | 21.11 | 12.48 | 0.00758164 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00758164 | 39.5417 | 41270.73 | 0.00 | 44490.32 | 44490.32 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11634.069 | -999.000 | 1.286826 | 0.00033273 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11634.07 | 11593.77 | 1.286826 | 21.82 | 13.53 | 0.00851861 | 12.80 | 10.21 | 0.00850000 | 27.44 | 0.00546540 | 12.88 | 0.0000 | 21.11 | 0.00851861 | 44.3610 | 10669.15 | 0.00 | 8742.78 | 8742.78 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7206.296 | 7206.296 | 0.382743 | 0.00006304 | 205.928 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7206.30 | 7206.30 | 0.382743 | 21.11 | 12.45 | 0.00755030 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00755030 | 39.3818 | 7206.48 | 0.00 | 7768.48 | 7768.48 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11368.976 | -999.000 | 1.257412 | 0.00032515 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 11368.98 | 11329.03 | 1.257412 | 21.82 | 13.53 | 0.00851888 | 12.80 | 10.21 | 0.00850000 | 26.60 | 0.00546414 | 12.59 | 0.0000 | 21.11 | 0.00851888 | 44.3624 | 10425.28 | 0.00 | 8543.70 | 8543.70 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7211.169 | 7211.169 | 0.383001 | 0.00006309 | 206.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7211.17 | 7211.17 | 0.383001 | 21.11 | 12.45 | 0.00755062 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00755062 | 39.3835 | 7211.35 | 0.00 | 7773.73 | 7773.73 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14778.789 | 14778.789 | 0.814682 | 0.00012929 | 371.761 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14778.79 | 14778.79 | 0.814682 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00764577 | 40.1440 | 11289.65 | 0.00 | 14854.83 | 14854.83 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3520.992 | -999.000 | 0.389700 | 0.00010070 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3520.99 | 3510.31 | 0.389700 | 21.82 | 13.52 | 0.00851629 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851629 | 44.3491 | 3231.02 | 0.00 | 2645.62 | 2645.62 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2202.888 | 2202.888 | 0.117000 | 0.00001927 | 62.947 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2202.89 | 2202.89 | 0.117000 | 21.11 | 12.52 | 0.00762782 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00762782 | 39.7812 | 2202.94 | 0.00 | 2374.74 | 2374.74 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3434.167 | -999.000 | 0.380050 | 0.00009821 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3434.17 | 3423.51 | 0.380050 | 21.82 | 13.52 | 0.00851667 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851667 | 44.3510 | 3151.02 | 0.00 | 2580.44 | 2580.44 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2202.784 | 2202.784 | 0.116995 | 0.00001927 | 62.944 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2202.78 | 2202.78 | 0.116995 | 21.11 | 12.52 | 0.00762783 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00762783 | 39.7813 | 2202.84 | 0.00 | 2374.63 | 2374.63 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15668.445 | -999.000 | 1.706634 | 0.00044811 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 15668.45 | 15451.66 | 1.706634 | 21.82 | 13.57 | 0.00857512 | 12.80 | 10.21 | 0.00850000 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00857512 | 44.6520 | 14149.30 | 0.00 | 11811.00 | 11811.00 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 10571.449 | 10571.449 | 0.561481 | 0.00009248 | 302.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10571.45 | 10571.45 | 0.561481 | 21.11 | 12.53 | 0.00764212 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00764212 | 39.8543 | 10571.65 | 0.00 | 11396.21 | 11396.21 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12263.013 | 12263.013 | 1.156423 | 0.00010728 | 277.060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12263.01 | 12263.01 | 1.156423 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00772069 | 40.5330 | 7309.81 | 0.00 | 12329.20 | 12329.20 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12648.923 | 12648.923 | 1.211405 | 0.00011066 | 285.159 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12648.92 | 12648.92 | 1.211405 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00772610 | 40.5611 | 7460.17 | 0.00 | 12717.25 | 12717.25 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7984.008 | 7984.008 | 1.201266 | 0.00006985 | 171.401 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7984.01 | 7984.01 | 1.201266 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00707728 | 37.1987 | 2847.63 | 0.00 | 8028.44 | 8028.44 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9498.329 | 9498.329 | 0.424702 | 0.00008310 | 255.528 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9498.33 | 9498.33 | 0.424702 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776549 | 40.7650 | 7679.03 | 0.00 | 9545.60 | 9545.60 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 475263.292 | -999.000 | 26.893922 | 0.01359247 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 475263.29 | 475263.29 | 26.893922 | 28.29 | 15.11 | 0.00781981 | 10.55 | 8.65 | 0.00781981 | 33.90 | 0.00547527 | 15.07 | 43.3609 | 23.99 | 0.00956931 | 41.7624 | 300166.87 | 0.00 | 376533.21 | 376533.21 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 274186.138 | 274186.138 | 8.068177 | 0.00239870 | 4253.479 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 274186.14 | 274186.14 | 8.068177 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 144.5365 | 21.19 | 0.00670109 | 34.8201 | 73369.74 | 0.00 | 218169.57 | 218169.57 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45136.603 | -999.000 | 2.051317 | 0.00129090 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 45136.60 | 45136.60 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 11.72 | 6.72 | 0.00547527 | 33.90 | 0.00547527 | 15.07 | 99.9965 | 21.11 | 0.00856483 | 44.5987 | 185942.29 | 0.00 | 45178.78 | 45178.78 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 20913.38 | 20913.38 | 0.615395 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3216 | 21.11 | 0.00758156 | 39.5413 | 126246.86 | 0.00 | 16640.75 | 16640.75 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5470.872 | 5470.872 | 1.276503 | 0.00004786 | 114.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.9838 | 1.003616 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5470.87 | 5470.87 | 1.0000 | 1.24770163 | 1.276503 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.04785669 | 60.00 | 32.22 | 27.78 | 0.000 | 5470.87 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5501.62 | 5501.62 | 1.24770163 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4097.336 | 4097.336 | 0.193558 | 0.00003585 | 108.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.7368 | 0.751644 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 4097.34 | 4097.34 | 1.0000 | 0.18919067 | 0.193558 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.03584162 | 60.00 | 32.22 | 27.78 | 0.000 | 4097.34 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00756923 | 21.00 | 0.00756923 | 39.7491 | 3268.65 | 0.00 | 4117.85 | 4117.85 | 0.18919067 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.94 | 20.57 | 0.00800000 | 58700.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1553.030 | 1553.030 | 0.119888 | 0.00001359 | 36.229 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.2793 | 0.284899 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1553.03 | 1553.03 | 1.0000 | 0.11718331 | 0.119888 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01358520 | 60.00 | 32.22 | 27.78 | 0.000 | 1553.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00748395 | 21.00 | 0.00748395 | 39.3049 | 1039.74 | 0.00 | 1561.32 | 1561.32 | 0.11718331 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.67 | 17.93 | 0.00800000 | 50258.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2358.804 | 2358.804 | 0.101592 | 0.00002064 | 64.373 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.4242 | 0.432716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2358.80 | 2358.80 | 1.0000 | 0.09929989 | 0.101592 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.02063374 | 60.00 | 32.22 | 27.78 | 0.000 | 2358.80 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00735398 | 21.00 | 0.00735398 | 38.6304 | 1923.96 | 0.00 | 2370.50 | 2370.50 | 0.09929989 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1565.229 | 1565.229 | 0.067412 | 0.00001369 | 42.716 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.2815 | 0.287137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1565.23 | 1565.23 | 1.0000 | 0.06589064 | 0.067412 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01369191 | 60.00 | 32.22 | 27.78 | 0.000 | 1565.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00743152 | 21.00 | 0.00743152 | 39.0329 | 1276.64 | 0.00 | 1572.99 | 1572.99 | 0.06589064 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9957.416 | 9957.416 | 1.728122 | 0.00008711 | 211.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.7906 | 1.826659 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9957.42 | 9957.42 | 1.0000 | 1.68913162 | 1.728122 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08710294 | 60.00 | 32.22 | 27.78 | 0.000 | 9957.42 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00733917 | 21.00 | 0.00733917 | 38.5552 | 2561.93 | 0.00 | 10013.03 | 10013.03 | 1.68913162 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.41 | 15.38 | 0.00800000 | 42862.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11725.409 | 11725.409 | 0.810717 | 0.00010258 | 279.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 2.1086 | 2.150992 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11725.41 | 11725.41 | 1.0000 | 0.79242517 | 0.810717 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10256853 | 60.00 | 32.22 | 27.78 | 0.000 | 11725.41 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00762001 | 21.00 | 0.00762001 | 40.0120 | 8253.95 | 0.00 | 11787.66 | 11787.66 | 0.79242517 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.19 | 18.43 | 0.00800000 | 51810.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29870.867 | 29870.867 | 2.565574 | 0.00026132 | 684.382 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 5.3716 | 5.479724 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 29870.87 | 29870.87 | 1.0000 | 2.50768816 | 2.565574 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.26129672 | 60.00 | 32.22 | 27.78 | 0.000 | 29870.87 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00753173 | 21.00 | 0.00753173 | 39.5528 | 18885.71 | 0.00 | 30031.29 | 30031.29 | 2.50768816 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.34 | 17.48 | 0.00800000 | 48910.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13269.565 | -999.000 | 1.468267 | 0.00037950 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6732 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.468267 | 1.43513899 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 1.7949 | 1.794869 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13269.57 | 13226.90 | 1.0000 | 1.43513899 | 1.468267 | 21.82 | 13.52 | 0.00851727 | 43568.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.37946208 | 6.70 | 15.03 | 8.33 | 0.000 | 13269.57 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851727 | 21.11 | 0.00851727 | 44.3541 | 12173.47 | 0.00 | 9971.09 | 9971.09 | 1.43513899 | 21.82 | 15.62 | 0.00851727 | 43568.4 | 15.01 | 13.02 | 0.00851727 | 36620.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7206.296 | 7206.296 | 0.382743 | 0.00006304 | 205.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.468267 | 1.43513899 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.2959 | 1.321974 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7206.30 | 7206.30 | 1.0000 | 0.37410697 | 0.382743 | 21.11 | 12.45 | 0.00755030 | 40391.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06303739 | 60.00 | 32.22 | 27.78 | 0.000 | 7206.30 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00755030 | 21.11 | 0.00755030 | 39.3818 | 7206.48 | 0.00 | 7768.48 | 7768.48 | 0.37410697 | 16.60 | 12.71 | 0.00755030 | 35796.2 | 36.98 | 19.93 | 0.00755030 | 56561.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12964.740 | -999.000 | 1.434400 | 0.00037078 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6738 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.434400 | 1.40203693 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 1.7537 | 1.753638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12964.74 | 12922.21 | 1.0000 | 1.40203693 | 1.434400 | 21.82 | 13.52 | 0.00851762 | 43569.3 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.37074518 | 6.70 | 15.03 | 8.33 | 0.000 | 12964.74 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00851762 | 21.11 | 0.00851762 | 44.3559 | 11892.68 | 0.00 | 9742.23 | 9742.23 | 1.40203693 | 21.82 | 15.62 | 0.00851762 | 43569.3 | 15.01 | 13.02 | 0.00851762 | 36620.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7211.169 | 7211.169 | 0.383001 | 0.00006309 | 206.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.434400 | 1.40203693 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.2968 | 1.322868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7211.17 | 7211.17 | 1.0000 | 0.37435994 | 0.383001 | 21.11 | 12.45 | 0.00755062 | 40391.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06308002 | 60.00 | 32.22 | 27.78 | 0.000 | 7211.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00755062 | 21.11 | 0.00755062 | 39.3835 | 7211.35 | 0.00 | 7773.73 | 7773.73 | 0.37435994 | 16.60 | 12.71 | 0.00755062 | 35797.0 | 36.98 | 19.93 | 0.00755062 | 56562.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75371.844 | -999.000 | 8.379940 | 0.00215558 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5654 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.379940 | 8.19086838 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 10.1951 | 10.194953 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 75371.84 | 75371.84 | 1.0000 | 8.19086838 | 8.379940 | 21.82 | 13.48 | 0.00845928 | 43421.3 | 12.80 | 10.18 | 0.00845928 | 34219.4 | 2.15536505 | 6.70 | 15.03 | 8.33 | 0.000 | 75371.84 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00845928 | 21.11 | 0.00845928 | 44.0555 | 69480.58 | 0.00 | 60360.69 | 60360.69 | 8.19086838 | 21.82 | 15.57 | 0.00845928 | 43421.3 | 14.60 | 12.79 | 0.00845928 | 36052.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41162.502 | 41162.502 | 2.186313 | 0.00036011 | 1176.253 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.379940 | 8.19086838 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 7.4022 | 7.551141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 41162.50 | 41162.50 | 1.0000 | 2.13698497 | 2.186313 | 21.11 | 12.48 | 0.00758072 | 40469.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.36007079 | 60.00 | 32.22 | 27.78 | 0.000 | 41162.50 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758072 | 21.11 | 0.00758072 | 39.5369 | 41163.03 | 0.00 | 44374.21 | 44374.21 | 2.13698497 | 16.60 | 12.74 | 0.00758072 | 35873.2 | 36.98 | 19.96 | 0.00758072 | 56638.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 71663.053 | -999.000 | 7.589857 | 0.00204952 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9763 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.589857 | 7.41861183 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 9.6935 | 9.693294 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 71663.05 | 69328.06 | 1.0000 | 7.41861183 | 7.589857 | 21.82 | 13.66 | 0.00868032 | 43982.1 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 2.04930690 | 6.70 | 15.03 | 8.33 | 0.000 | 71663.05 | 33.75 | 0.00547504 | 15.02 | 0.00000000 | 0.0000 | 21.11 | 0.00868032 | 21.11 | 0.00868032 | 45.1928 | 62924.48 | 0.00 | 54326.95 | 54326.95 | 7.41861183 | 21.82 | 15.76 | 0.00868032 | 43982.1 | 14.64 | 13.03 | 0.00868032 | 36659.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41270.207 | 41270.207 | 2.192034 | 0.00036105 | 1179.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.589857 | 7.41861183 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 7.4215 | 7.570899 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 41270.21 | 41270.21 | 1.0000 | 2.14257658 | 2.192034 | 21.11 | 12.48 | 0.00758164 | 40471.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.36101294 | 60.00 | 32.22 | 27.78 | 0.000 | 41270.21 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758164 | 21.11 | 0.00758164 | 39.5417 | 41270.73 | 0.00 | 44490.32 | 44490.32 | 2.14257658 | 16.60 | 12.74 | 0.00758164 | 35875.5 | 36.98 | 19.96 | 0.00758164 | 56640.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11634.069 | -999.000 | 1.286826 | 0.00033273 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6757 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.286826 | 1.25779260 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 1.5737 | 1.573648 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11634.07 | 11593.77 | 1.0000 | 1.25779260 | 1.286826 | 21.82 | 13.53 | 0.00851861 | 43571.8 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.33269275 | 6.70 | 15.03 | 8.33 | 0.000 | 11634.07 | 27.44 | 0.00546540 | 12.88 | 0.00000000 | 0.0000 | 21.11 | 0.00851861 | 21.11 | 0.00851861 | 44.3610 | 10669.15 | 0.00 | 8742.78 | 8742.78 | 1.25779260 | 21.82 | 15.62 | 0.00851861 | 43571.8 | 15.01 | 13.02 | 0.00851861 | 36620.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7206.296 | 7206.296 | 0.382743 | 0.00006304 | 205.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.286826 | 1.25779260 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.2959 | 1.321974 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7206.30 | 7206.30 | 1.0000 | 0.37410697 | 0.382743 | 21.11 | 12.45 | 0.00755030 | 40391.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06303739 | 60.00 | 32.22 | 27.78 | 0.000 | 7206.30 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00755030 | 21.11 | 0.00755030 | 39.3818 | 7206.48 | 0.00 | 7768.48 | 7768.48 | 0.37410697 | 16.60 | 12.71 | 0.00755030 | 35796.2 | 36.98 | 19.93 | 0.00755030 | 56561.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11368.976 | -999.000 | 1.257412 | 0.00032515 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6762 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.257412 | 1.22904181 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 1.5378 | 1.537791 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 11368.98 | 11329.03 | 1.0000 | 1.22904181 | 1.257412 | 21.82 | 13.53 | 0.00851888 | 43572.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.32511203 | 6.70 | 15.03 | 8.33 | 0.000 | 11368.98 | 26.60 | 0.00546414 | 12.59 | 0.00000000 | 0.0000 | 21.11 | 0.00851888 | 21.11 | 0.00851888 | 44.3624 | 10425.28 | 0.00 | 8543.70 | 8543.70 | 1.22904181 | 21.82 | 15.62 | 0.00851888 | 43572.5 | 15.01 | 13.02 | 0.00851888 | 36621.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7211.169 | 7211.169 | 0.383001 | 0.00006309 | 206.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.257412 | 1.22904181 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.2968 | 1.322868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7211.17 | 7211.17 | 1.0000 | 0.37435994 | 0.383001 | 21.11 | 12.45 | 0.00755062 | 40391.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06308002 | 60.00 | 32.22 | 27.78 | 0.000 | 7211.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00755062 | 21.11 | 0.00755062 | 39.3835 | 7211.35 | 0.00 | 7773.73 | 7773.73 | 0.37435994 | 16.60 | 12.71 | 0.00755062 | 35797.0 | 36.98 | 19.93 | 0.00755062 | 56562.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14778.789 | 14778.789 | 0.814682 | 0.00012929 | 371.761 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 2.6576 | 2.711126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14778.79 | 14778.79 | 1.0000 | 0.79630126 | 0.814682 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.12927810 | 60.00 | 32.22 | 27.78 | 0.000 | 14778.79 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00764577 | 21.00 | 0.00764577 | 40.1440 | 11289.65 | 0.00 | 14854.83 | 14854.83 | 0.79630126 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.89 | 19.62 | 0.00800000 | 55589.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3520.992 | -999.000 | 0.389700 | 0.00010070 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6714 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.389700 | 0.38090714 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 0.4763 | 0.476257 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3520.99 | 3510.31 | 1.0000 | 0.38090714 | 0.389700 | 21.82 | 13.52 | 0.00851629 | 43565.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.10068777 | 6.70 | 15.03 | 8.33 | 0.000 | 3520.99 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851629 | 21.11 | 0.00851629 | 44.3491 | 3231.02 | 0.00 | 2645.62 | 2645.62 | 0.38090714 | 21.82 | 15.62 | 0.00851629 | 43565.9 | 15.01 | 13.02 | 0.00851629 | 36620.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2202.888 | 2202.888 | 0.117000 | 0.00001927 | 62.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.389700 | 0.38090714 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.3961 | 0.404113 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2202.89 | 2202.89 | 1.0000 | 0.11436063 | 0.117000 | 21.11 | 12.52 | 0.00762782 | 40587.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01926986 | 60.00 | 32.22 | 27.78 | 0.000 | 2202.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00762782 | 21.11 | 0.00762782 | 39.7812 | 2202.94 | 0.00 | 2374.74 | 2374.74 | 0.11436063 | 16.60 | 12.79 | 0.00762782 | 35992.4 | 36.98 | 19.99 | 0.00762782 | 56757.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3434.167 | -999.000 | 0.380050 | 0.00009821 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6721 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.380050 | 0.37147563 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 0.4645 | 0.464513 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3434.17 | 3423.51 | 1.0000 | 0.37147563 | 0.380050 | 21.82 | 13.52 | 0.00851667 | 43566.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.09820490 | 6.70 | 15.03 | 8.33 | 0.000 | 3434.17 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851667 | 21.11 | 0.00851667 | 44.3510 | 3151.02 | 0.00 | 2580.44 | 2580.44 | 0.37147563 | 21.82 | 15.62 | 0.00851667 | 43566.9 | 15.01 | 13.02 | 0.00851667 | 36620.4 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2202.784 | 2202.784 | 0.116995 | 0.00001927 | 62.944 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.380050 | 0.37147563 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 0.3961 | 0.404094 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2202.78 | 2202.78 | 1.0000 | 0.11435525 | 0.116995 | 21.11 | 12.52 | 0.00762783 | 40588.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01926895 | 60.00 | 32.22 | 27.78 | 0.000 | 2202.78 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00762783 | 21.11 | 0.00762783 | 39.7813 | 2202.84 | 0.00 | 2374.63 | 2374.63 | 0.11435525 | 16.60 | 12.79 | 0.00762783 | 35992.5 | 36.98 | 19.99 | 0.00762783 | 56757.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15668.445 | -999.000 | 1.706634 | 0.00044811 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7807 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.706634 | 1.66812821 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 2.1194 | 2.119347 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 15668.45 | 15451.66 | 1.0000 | 1.66812821 | 1.706634 | 21.82 | 13.57 | 0.00857512 | 43715.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.44806148 | 6.70 | 15.03 | 8.33 | 0.000 | 15668.45 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00857512 | 21.11 | 0.00857512 | 44.6520 | 14149.30 | 0.00 | 11811.00 | 11811.00 | 1.66812821 | 21.82 | 15.67 | 0.00857512 | 43715.0 | 14.88 | 13.02 | 0.00857512 | 36634.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10571.449 | 10571.449 | 0.561481 | 0.00009248 | 302.076 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.706634 | 1.66812821 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.9010 | 1.939302 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 10571.45 | 10571.45 | 1.0000 | 0.54881306 | 0.561481 | 21.11 | 12.53 | 0.00764212 | 40624.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09247421 | 60.00 | 32.22 | 27.78 | 0.000 | 10571.45 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00764212 | 21.11 | 0.00764212 | 39.8543 | 10571.65 | 0.00 | 11396.21 | 11396.21 | 0.54881306 | 16.60 | 12.80 | 0.00764212 | 36028.6 | 36.98 | 20.00 | 0.00764212 | 56793.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12263.013 | 12263.013 | 1.156423 | 0.00010728 | 277.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 2.2052 | 2.249614 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12263.01 | 12263.01 | 1.0000 | 1.13033096 | 1.156423 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10727125 | 60.00 | 32.22 | 27.78 | 0.000 | 12263.01 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772069 | 21.00 | 0.00772069 | 40.5330 | 7309.81 | 0.00 | 12329.20 | 12329.20 | 1.13033096 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.30 | 17.12 | 0.00800000 | 47842.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12648.923 | 12648.923 | 1.211405 | 0.00011066 | 285.159 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 2.2746 | 2.320408 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12648.92 | 12648.92 | 1.0000 | 1.18407317 | 1.211405 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11064701 | 60.00 | 32.22 | 27.78 | 0.000 | 12648.92 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772610 | 21.00 | 0.00772610 | 40.5611 | 7460.17 | 0.00 | 12717.25 | 12717.25 | 1.18407317 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.13 | 17.06 | 0.00800000 | 47675.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7984.008 | 7984.008 | 1.201266 | 0.00006985 | 171.401 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.4357 | 1.464643 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7984.01 | 7984.01 | 1.0000 | 1.17416301 | 1.201266 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06984046 | 60.00 | 32.22 | 27.78 | 0.000 | 7984.01 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.64 | 0.00707728 | 21.00 | 0.00707728 | 37.1987 | 2847.63 | 0.00 | 8028.44 | 8028.44 | 1.17416301 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.31 | 15.70 | 0.00800000 | 43772.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9498.329 | 9498.329 | 0.424702 | 0.00008310 | 255.528 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 1.7081 | 1.742441 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9498.33 | 9498.33 | 1.0000 | 0.41512006 | 0.424702 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08308705 | 60.00 | 32.22 | 27.78 | 0.000 | 9498.33 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00776549 | 21.00 | 0.00776549 | 40.7650 | 7679.03 | 0.00 | 9545.60 | 9545.60 | 0.41512006 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.15 | 20.93 | 0.00800000 | 59929.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 475263.292 | -999.000 | 26.893922 | 0.01359247 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3766 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.893922 | 26.28713112 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 64.2863 | 64.286305 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 475263.29 | 475263.29 | 1.0000 | 26.28713112 | 26.893922 | 28.29 | 15.11 | 0.00781981 | 48392.2 | 10.55 | 8.65 | 0.00781981 | 30312.5 | 13.59108343 | 6.70 | 15.03 | 8.33 | 60259.560 | 415003.73 | 33.90 | 0.00547527 | 15.07 | 11.66146000 | 43.3609 | 23.99 | 0.00961551 | 23.99 | 0.00956931 | 41.7624 | 300166.87 | 0.00 | 376533.21 | 376533.21 | 26.28713112 | 28.29 | 17.31 | 0.00781981 | 48392.2 | 14.24 | 12.01 | 0.00781981 | 34068.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 274186.138 | 274186.138 | 8.068177 | 0.00239870 | 4253.479 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.893922 | 26.28713112 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 49.3063 | 50.298650 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 274186.14 | 274186.14 | 1.0000 | 7.88613934 | 8.068177 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 2.39845525 | 60.00 | 32.22 | 27.78 | 0.000 | 274186.14 | -17.90 | 0.00095524 | -17.90 | 11.66146000 | 144.5365 | 18.66 | 0.00686483 | 21.19 | 0.00670109 | 34.8201 | 73369.74 | 0.00 | 218169.57 | 218169.57 | 7.88613934 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45136.603 | -999.000 | 2.051317 | 0.00129090 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.0183 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 21.14149102 | 15.03 | 6.70 | 8.33 | 739291.66 | 6.1054 | 6.105385 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 45136.60 | 45136.60 | 1.0000 | 2.00503462 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 48102.5 | 11.72 | 6.72 | 0.00547527 | 25590.8 | 1.29076945 | 6.70 | 15.03 | 8.33 | 2195.006 | 42941.60 | 33.90 | 0.00547527 | 15.07 | 2.05124512 | 99.9965 | 21.11 | 0.00855666 | 21.11 | 0.00856483 | 44.5987 | 185942.29 | 0.00 | 45178.78 | 45178.78 | 2.00503462 | 33.90 | 17.27 | 0.00547527 | 48102.5 | 11.70 | 8.38 | 0.00547527 | 25569.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 4.76842872 | 54.44 | 82.22 | 27.78 | 556086.98 | 3.7608 | 3.836498 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 20913.38 | 20913.38 | 1.0000 | 0.60151039 | 0.615395 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 0.18294069 | 60.00 | 32.22 | 27.78 | 0.000 | 20913.38 | -17.90 | 0.00095524 | -17.90 | 2.05124512 | 333.3216 | 21.11 | 0.00758089 | 21.11 | 0.00758156 | 39.5413 | 126246.86 | 0.00 | 16640.75 | 16640.75 | 0.60151039 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 26.89 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 597.33 | 6512.83 | 306.17 |
RETAIL_1_FLR_1 | 2732.50 | 6064.17 | 1057.00 |
RETAIL_2_FLR_1 | 1223.17 | 5995.17 | 390.00 |
MECH_FLR_1 | 950.00 | 7331.33 | 586.17 |
STORAGE_FLR_1 | 926.83 | 7756.50 | 716.50 |
LAUNDRY_FLR_1 | 7965.17 | 3175.67 | 2941.33 |
CAFE_FLR_1 | 3867.33 | 3798.00 | 725.00 |
LOBBY_FLR_1 | 1947.83 | 3848.00 | 480.50 |
ROOM_1_FLR_3 | 1638.33 | 8036.67 | 1444.33 |
ROOM_2_FLR_3 | 2656.33 | 7853.50 | 2278.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1379.83 | 8708.67 | 1362.17 |
ROOM_5_FLR_3 | 1670.67 | 7953.67 | 1437.33 |
ROOM_6_FLR_3 | 2752.67 | 7763.83 | 2328.00 |
CORRIDOR_FLR_3 | 863.67 | 7641.00 | 665.83 |
ROOM_1_FLR_6 | 2440.00 | 7904.33 | 2122.17 |
ROOM_2_FLR_6 | 3603.67 | 7749.00 | 3120.00 |
ROOM_3_MULT9_FLR_6 | 1391.83 | 7641.33 | 1032.33 |
BANQUET_FLR_6 | 3388.00 | 2466.17 | 485.50 |
DINING_FLR_6 | 4208.33 | 1399.00 | 468.17 |
KITCHEN_FLR_6 | 8533.67 | 6245.17 | 6182.33 |
CORRIDOR_FLR_6 | 1220.17 | 7044.33 | 735.00 |
Facility | 8760.00 | 8760.00 | 7663.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 1.33 | 0.00 | 1.33 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 6.00 | 0.00 | 6.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.83 | 122.33 | 0.83 | 122.33 |
ROOM_2_FLR_3 | 2.33 | 132.50 | 2.33 | 132.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 5.67 | 131.50 | 5.67 | 131.50 |
ROOM_5_FLR_3 | 2.50 | 158.00 | 2.50 | 158.00 |
ROOM_6_FLR_3 | 3.67 | 174.50 | 3.67 | 174.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 2.00 | 142.83 | 2.00 | 142.83 |
ROOM_2_FLR_6 | 3.50 | 148.00 | 3.50 | 148.00 |
ROOM_3_MULT9_FLR_6 | 1.50 | 146.67 | 1.50 | 146.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 7.00 | 0.00 | 7.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 8.00 | 467.33 | 8.00 | 467.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.090 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.938 | 0.139 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.525 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.553 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.557 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 26.161 | 0.149 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.518 | 0.110 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 2.017 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.053 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.180 | 0.000 | 0.050 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.080 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.053 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.180 | 0.000 | 0.052 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.628 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.063 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.354 | 0.180 | 0.000 | 0.056 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.147 | 0.000 | 0.101 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.622 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 6.115 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.300 | 0.150 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.257 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.463 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.459 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.994 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.428 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.391 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 14.196 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.488 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.285 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.408 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.311 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.469 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.101 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.756 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 45354693.44 | 0.00 | 45354693.44 | 0.00 | 45354693.44 | 26946214.98 | 32.22 | 4.72 | 8723.06 | 0.00 |
RETAIL_1_FLR_1 | 6764899.49 | 0.00 | 6764899.49 | 319936.80 | 7084836.29 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4049508.96 | 0.00 | 4049508.96 | 123496.01 | 4173004.97 | 2892943.94 | 3.17 | 0.67 | 8756.17 | 0.00 |
MECH_FLR_1 | 3118013.28 | 0.00 | 3118013.28 | 291871.20 | 3409884.48 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1812961.99 | 0.00 | 1812961.99 | 168393.60 | 1981355.60 | 1821682.01 | 537.00 | 7969.08 | 253.92 | 0.00 |
LAUNDRY_FLR_1 | 69824476.03 | 0.00 | 69824476.03 | 398535.21 | 70223011.25 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29151700.57 | 0.00 | 29151700.57 | 707238.41 | 29858938.97 | 21330615.53 | 63.18 | 5.12 | 8691.69 | 0.00 |
LOBBY_FLR_1 | 90048690.74 | 0.00 | 90048690.74 | 2020741.67 | 92069432.41 | 59728886.00 | 0.83 | 1.33 | 8757.83 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 55062.91 | 1515219.62 | 185701.25 | 1700920.88 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 51968.37 | 1511954.01 | 185687.09 | 1697641.09 | 1946647.51 | 2190.00 | 6048.22 | 521.78 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 327.01 | 1100238.98 | 51812.73 | 1152051.71 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 368.50 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 56314.01 | 19860143.31 | 51826.90 | 19911970.21 | 26405105.73 | 2190.00 | 5994.82 | 575.18 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 55166.02 | 1515322.74 | 185701.25 | 1701023.99 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 53381.30 | 1513366.94 | 185687.09 | 1699054.02 | 1946647.51 | 2190.00 | 6007.00 | 563.00 | 0.00 |
CORRIDOR_FLR_3 | 25791884.56 | 0.00 | 25791884.56 | 224550.18 | 26016434.74 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 65703.04 | 430742.22 | 185740.37 | 616482.59 | 486718.90 | 2038.95 | 5990.80 | 730.25 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 57894.65 | 422891.06 | 185726.20 | 608617.25 | 486661.88 | 2064.32 | 6072.29 | 623.39 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 65711.45 | 2410901.76 | 95031.27 | 2505933.04 | 3126920.42 | 2190.00 | 5989.50 | 580.50 | 0.00 |
BANQUET_FLR_6 | 48891075.10 | 0.00 | 48891075.10 | 453531.30 | 49344606.39 | 37458366.31 | 1949.69 | 149.51 | 6660.80 | 0.00 |
DINING_FLR_6 | 53180962.77 | 0.00 | 53180962.77 | 453531.30 | 53634494.07 | 37458366.31 | 9.17 | 4.58 | 8746.25 | 0.00 |
KITCHEN_FLR_6 | 71325542.66 | 0.00 | 71325542.66 | 406015.66 | 71731558.32 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13684221.51 | 0.00 | 13684221.51 | 397385.47 | 14081606.98 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.22E+10 | 5882032.58 | 0.22E+10 | 18713344.22 | 0.22E+10 | 0.43E+10 | 8760.00 | 8640.47 | 8760.00 | 368.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4382 | 0.0000 | 1.4382 | 0.0000 | 1.4382 | 0.8545 | 32.22 | 4.72 | 8723.06 |
RETAIL_1_FLR_1 | 0.2145 | 0.0000 | 0.2145 | 0.0101 | 0.2247 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1284 | 0.0000 | 0.1284 | 0.0039 | 0.1323 | 0.0917 | 3.17 | 0.67 | 8756.17 |
MECH_FLR_1 | 0.0989 | 0.0000 | 0.0989 | 0.0093 | 0.1081 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0575 | 0.0000 | 0.0575 | 0.0053 | 0.0628 | 0.0578 | 537.00 | 7969.08 | 253.92 |
LAUNDRY_FLR_1 | 2.2141 | 0.0000 | 2.2141 | 0.0126 | 2.2268 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9244 | 0.0000 | 0.9244 | 0.0224 | 0.9468 | 0.6764 | 63.18 | 5.12 | 8691.69 |
LOBBY_FLR_1 | 2.8554 | 0.0000 | 2.8554 | 0.0641 | 2.9195 | 1.8940 | 0.83 | 1.33 | 8757.83 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0059 | 0.0539 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0059 | 0.0538 | 0.0617 | 2190.00 | 6048.22 | 521.78 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0016 | 0.6314 | 0.8373 | 2190.00 | 5994.82 | 575.18 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0481 | 0.0059 | 0.0539 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0059 | 0.0539 | 0.0617 | 2190.00 | 6007.00 | 563.00 |
CORRIDOR_FLR_3 | 0.8179 | 0.0000 | 0.8179 | 0.0071 | 0.8250 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0059 | 0.0195 | 0.0154 | 2038.95 | 5990.80 | 730.25 |
ROOM_2_FLR_6 | 0.0116 | 0.0018 | 0.0134 | 0.0059 | 0.0193 | 0.0154 | 2064.32 | 6072.29 | 623.39 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0764 | 0.0030 | 0.0795 | 0.0992 | 2190.00 | 5989.50 | 580.50 |
BANQUET_FLR_6 | 1.5503 | 0.0000 | 1.5503 | 0.0144 | 1.5647 | 1.1878 | 1949.69 | 149.51 | 6660.80 |
DINING_FLR_6 | 1.6864 | 0.0000 | 1.6864 | 0.0144 | 1.7007 | 1.1878 | 9.17 | 4.58 | 8746.25 |
KITCHEN_FLR_6 | 2.2617 | 0.0000 | 2.2617 | 0.0129 | 2.2746 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4339 | 0.0000 | 0.4339 | 0.0126 | 0.4465 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 66.2945 | 0.1857 | 66.4802 | 0.4685 | 66.9488 | 73.9670 | 8760.00 | 8640.47 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 28488844.65 | 461528.77 | 28950373.41 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.0266 | 0.0000 | 14.0266 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 0.9034 | 0.0146 | 0.9180 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4069.83 | 0.00 | 0.00 | 0.00 | 4690.17 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.5563 | 0.0000 | 0.0000 | 0.0000 | 13.5699 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
Electricity:Building | 2447.03 | 31112.40 | 27-MAY-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.94 | 30971.25 | 27-MAY-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.37 | 318.54 | 20-MAY-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.81 | 3118.22 | 27-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.81 | 1006.80 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.81 | 1006.80 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.60 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.60 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.34 | 1114.44 | 15-JUL-22:30 | 3259.79 | 28-JUL-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 980.57 | 2638.36 | 12-APR-00:50 | 167917.54 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.43 | 0.00 | 01-JAN-11:10 | 1893.82 | 05-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.81 | 947.97 | 22-DEC-04:10 | 1197.22 | 28-JUL-13:10 |
Fans:Electricity | 581.24 | 10638.51 | 30-OCT-10:10 | 61239.06 | 17-JUL-18:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 766.69 | 11230.15 | 30-APR-14:00 | 72225.97 | 17-JUL-18:40 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.98 | 10-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
General:Cogeneration:ElectricityPurchased | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
ElectricityNet:Plant | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
General:Cogeneration:ElectricityNet | 5007.11 | 70274.70 | 27-APR-01:50 | 396959.82 | 26-JUN-19:30 |
General:Fans:Electricity | 581.24 | 10638.51 | 30-OCT-10:10 | 61239.06 | 17-JUL-18:40 |
ExteriorLights:Electricity | 193.79 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.79 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 163.69 | 0.00 | 01-JAN-11:40 | 9938.94 | 14-JUN-07:00 |
General:HeatRecovery:Electricity | 163.69 | 0.00 | 01-JAN-11:40 | 9938.94 | 14-JUN-07:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 11-JUL-00:10 | 4738.73 | 14-SEP-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 11-JUL-00:10 | 4738.73 | 14-SEP-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 765.98 | 0.00 | 01-JAN-00:10 | 156777.56 | 26-JUN-18:10 |
General:Cooling:Electricity | 765.98 | 0.00 | 01-JAN-00:10 | 156777.56 | 26-JUN-18:10 |
Pumps:Electricity | 69.59 | 47.91 | 29-JAN-11:30 | 5590.76 | 10-AUG-19:10 |
General:Pumps:Electricity | 69.59 | 47.91 | 29-JAN-11:30 | 5590.76 | 10-AUG-19:10 |
WIRED_LTG_ELECTRICITY | 27.52 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6312.73 | 29270.80 | 11-MAY-01:10 | 642113.20 | 21-DEC-19:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4523.89 | 15908.90 | 13-MAR-15:20 | 554493.42 | 21-DEC-19:30 |
WaterSystems:NaturalGas | 3214.61 | 15908.90 | 09-JAN-16:10 | 293470.52 | 13-FEB-21:50 |
Water Heater:WaterSystems:NaturalGas | 3214.61 | 15908.90 | 09-JAN-16:10 | 293470.52 | 13-FEB-21:50 |
Heating:NaturalGas | 1309.28 | 0.00 | 01-JAN-11:10 | 307078.75 | 21-DEC-09:20 |
Boiler:Heating:NaturalGas | 1309.28 | 0.00 | 01-JAN-11:10 | 307078.75 | 21-DEC-09:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2313.99 | 0.00 | 01-JAN-00:10 | 424760.69 | 26-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 2313.99 | 0.00 | 01-JAN-00:10 | 424760.69 | 26-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2313.99 | 0.00 | 01-JAN-00:10 | 424760.69 | 26-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19004.61 | 137726.11 | 01-MAY-14:50 | 1854746.61 | 26-JUN-18:10 |
EnergyTransfer:Building | 5090.39 | 76046.62 | 06-FEB-11:10 | 334672.11 | 11-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 718.35 | 9204.52 | 22-DEC-04:00 | 36675.05 | 05-AUG-10:50 |
Refrigeration:EnergyTransfer | 179.67 | 4016.15 | 15-JUL-22:30 | 10348.63 | 28-JUL-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.83 | 2008.08 | 15-JUL-22:30 | 5174.32 | 28-JUL-06:20 |
General:Refrigeration:EnergyTransfer | 89.83 | 2008.08 | 15-JUL-22:30 | 5174.32 | 28-JUL-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.83 | 2008.08 | 15-JUL-22:30 | 5174.32 | 28-JUL-06:20 |
EnergyTransfer:Plant | 7262.00 | 16427.16 | 13-OCT-00:20 | 1047705.75 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.51 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.33 | 1793.91 | 22-DEC-04:10 | 2541.65 | 28-JUL-13:10 |
EnergyTransfer:Zone:BASEMENT | 387.53 | 9119.67 | 26-MAR-15:00 | 22633.95 | 20-OCT-21:00 |
Heating:EnergyTransfer | 161.16 | 0.00 | 01-JAN-08:10 | 96240.82 | 21-DEC-09:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 161.16 | 0.00 | 01-JAN-08:10 | 96240.82 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4839.39 | 59506.44 | 20-DEC-15:00 | 332154.34 | 11-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 387.53 | 9119.67 | 26-MAR-15:00 | 22633.95 | 20-OCT-21:00 |
General:Cooling:EnergyTransfer | 4839.39 | 59506.44 | 20-DEC-15:00 | 332154.34 | 11-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 387.53 | 9119.67 | 26-MAR-15:00 | 22633.95 | 20-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.81 | 0.01 | 09-DEC-05:50 | 5019.27 | 07-NOV-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.59 | 0.00 | 01-JAN-00:10 | 1851.12 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.59 | 0.00 | 01-JAN-00:10 | 1851.12 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.22 | 0.00 | 03-JAN-04:30 | 5019.27 | 07-NOV-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.22 | 0.00 | 03-JAN-04:30 | 5019.27 | 07-NOV-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.92 | 60.96 | 21-DEC-10:10 | 2226.34 | 26-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.92 | 60.96 | 21-DEC-10:10 | 2226.34 | 26-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.92 | 60.96 | 21-DEC-10:10 | 2226.34 | 26-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.95 | 0.14 | 30-NOV-09:50 | 1890.10 | 17-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.33 | 0.00 | 01-JAN-00:10 | 873.32 | 22-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.33 | 0.00 | 01-JAN-00:10 | 873.32 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.62 | 0.00 | 04-JAN-16:00 | 1890.10 | 17-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.62 | 0.00 | 04-JAN-16:00 | 1890.10 | 17-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.05 | 0.01 | 17-APR-00:50 | 916.92 | 26-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.44 | 0.00 | 01-JAN-00:10 | 667.13 | 23-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.44 | 0.00 | 01-JAN-00:10 | 667.13 | 23-DEC-07:50 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.61 | 0.00 | 04-JAN-10:50 | 916.92 | 26-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.61 | 0.00 | 04-JAN-10:50 | 916.92 | 26-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.18 | 8601.80 | 22-DEC-05:00 | 39299.76 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.18 | 8601.80 | 22-DEC-05:00 | 39299.76 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 593.18 | 8601.80 | 22-DEC-05:00 | 39299.76 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 237.37 | 0.42 | 30-OCT-09:10 | 17836.82 | 18-FEB-13:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 3033.92 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 3033.92 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.29 | 0.00 | 05-JAN-09:10 | 17836.82 | 18-FEB-13:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.29 | 0.00 | 05-JAN-09:10 | 17836.82 | 18-FEB-13:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 758.28 | 5548.71 | 21-DEC-09:30 | 42655.13 | 16-AUG-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 758.28 | 5548.71 | 21-DEC-09:30 | 42655.13 | 16-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 758.28 | 5548.71 | 21-DEC-09:30 | 42655.13 | 16-AUG-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.57 | 0.00 | 01-JAN-08:10 | 10544.00 | 16-AUG-16:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 15.49 | 0.00 | 01-JAN-08:10 | 7295.15 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 15.49 | 0.00 | 01-JAN-08:10 | 7295.15 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 54.07 | 0.00 | 01-JAN-00:10 | 10544.00 | 16-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 54.07 | 0.00 | 01-JAN-00:10 | 10544.00 | 16-AUG-16:30 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 58.03 | 0.00 | 01-JAN-08:10 | 10284.47 | 27-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.21 | 0.00 | 01-JAN-08:10 | 7270.23 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.21 | 0.00 | 01-JAN-08:10 | 7270.23 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 36.82 | 0.00 | 01-JAN-00:10 | 10284.47 | 27-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 36.82 | 0.00 | 01-JAN-00:10 | 10284.47 | 27-JUN-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 359.98 | 0.00 | 01-JAN-00:10 | 64552.33 | 20-JAN-12:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 359.98 | 0.00 | 01-JAN-00:10 | 64552.33 | 20-JAN-12:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 359.98 | 0.00 | 01-JAN-00:10 | 64552.33 | 20-JAN-12:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 354.96 | 0.00 | 01-JAN-08:10 | 61828.63 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 52.08 | 0.00 | 01-JAN-08:10 | 39712.69 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 52.08 | 0.00 | 01-JAN-08:10 | 39712.69 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 302.88 | 0.00 | 01-JAN-00:10 | 61828.63 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 302.88 | 0.00 | 01-JAN-00:10 | 61828.63 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.55 | 0.00 | 01-JAN-08:10 | 9402.93 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 15.86 | 0.00 | 01-JAN-08:00 | 7067.02 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 15.86 | 0.00 | 01-JAN-08:00 | 7067.02 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.69 | 0.00 | 01-JAN-00:10 | 9402.93 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.69 | 0.00 | 01-JAN-00:10 | 9402.93 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 61.66 | 0.00 | 01-JAN-08:10 | 10195.67 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 21.55 | 0.00 | 01-JAN-08:10 | 7158.26 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 21.55 | 0.00 | 01-JAN-08:10 | 7158.26 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.11 | 0.00 | 01-JAN-00:10 | 10195.67 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.11 | 0.00 | 01-JAN-00:10 | 10195.67 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 177.06 | 2.15 | 30-NOV-04:20 | 13353.58 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.20 | 0.00 | 01-JAN-00:10 | 5369.97 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.20 | 0.00 | 01-JAN-00:10 | 5369.97 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 175.86 | 0.00 | 04-JAN-13:10 | 13353.58 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 175.86 | 0.00 | 04-JAN-13:10 | 13353.58 | 26-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.34 | 0.00 | 01-JAN-08:10 | 2846.39 | 16-AUG-16:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.13 | 0.00 | 01-JAN-08:10 | 2188.20 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.13 | 0.00 | 01-JAN-08:10 | 2188.20 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.20 | 0.00 | 01-JAN-00:10 | 2846.39 | 16-AUG-16:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.20 | 0.00 | 01-JAN-00:10 | 2846.39 | 16-AUG-16:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.19 | 0.00 | 01-JAN-08:10 | 2755.08 | 27-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.07 | 0.00 | 01-JAN-08:10 | 2180.52 | 22-DEC-03:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.07 | 0.00 | 01-JAN-08:10 | 2180.52 | 22-DEC-03:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.12 | 0.00 | 01-JAN-00:10 | 2755.08 | 27-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.12 | 0.00 | 01-JAN-00:10 | 2755.08 | 27-JUN-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 111.69 | 0.00 | 01-JAN-08:10 | 13589.10 | 20-JAN-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 15.14 | 0.00 | 01-JAN-00:10 | 10083.52 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 15.14 | 0.00 | 01-JAN-00:10 | 10083.52 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 96.55 | 0.00 | 01-JAN-01:40 | 13589.10 | 20-JAN-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 96.55 | 0.00 | 01-JAN-01:40 | 13589.10 | 20-JAN-13:30 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 424.93 | 6575.45 | 20-DEC-15:00 | 23375.69 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 424.93 | 6575.45 | 20-DEC-15:00 | 23375.69 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 424.93 | 6575.45 | 20-DEC-15:00 | 23375.69 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 464.66 | 7461.12 | 20-DEC-15:00 | 24571.78 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 464.66 | 7461.12 | 20-DEC-15:00 | 24571.78 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 464.66 | 7461.12 | 20-DEC-15:00 | 24571.78 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 628.52 | 7168.67 | 22-DEC-04:00 | 31631.81 | 05-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 628.52 | 7168.67 | 22-DEC-04:00 | 31631.81 | 05-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.33 | 0.01 | 25-OCT-05:20 | 7263.17 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.00 | 0.00 | 01-JAN-00:10 | 3817.18 | 23-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.00 | 0.00 | 01-JAN-00:10 | 3817.18 | 23-DEC-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 88.33 | 0.00 | 03-JAN-06:10 | 7263.17 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 88.33 | 0.00 | 03-JAN-06:10 | 7263.17 | 16-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1678.69 | 9320.29 | 12-AUG-02:40 | 283401.45 | 21-DEC-09:10 |
PlantLoopHeatingDemand:Plant | 786.02 | 9320.29 | 12-AUG-02:40 | 58325.44 | 16-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 786.02 | 9320.29 | 12-AUG-02:40 | 58325.44 | 16-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 786.02 | 9320.29 | 12-AUG-02:40 | 58325.44 | 16-FEB-07:10 |
EnergyTransfer:HVAC | 6652.22 | 248.11 | 28-APR-10:40 | 736653.65 | 21-DEC-20:00 |
HeatingCoils:EnergyTransfer | 892.67 | 0.00 | 01-JAN-11:10 | 251176.99 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 892.67 | 0.00 | 01-JAN-11:10 | 251176.99 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 892.67 | 0.00 | 01-JAN-11:10 | 251176.99 | 21-DEC-09:10 |
CoolingCoils:EnergyTransfer | 2313.99 | 0.00 | 01-JAN-00:10 | 424760.69 | 26-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 3380.07 | 0.00 | 01-JAN-11:40 | 514198.17 | 21-DEC-20:10 |
HeatRecoveryForCooling:EnergyTransfer | 65.49 | 0.00 | 01-JAN-00:10 | 145260.42 | 16-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 786.02 | 9320.29 | 12-AUG-02:40 | 58325.44 | 16-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 786.02 | 9320.29 | 12-AUG-02:40 | 58325.44 | 16-FEB-07:10 |
Boilers:EnergyTransfer | 885.42 | 0.00 | 01-JAN-11:10 | 248401.35 | 21-DEC-09:20 |
Chillers:EnergyTransfer | 2367.37 | 0.00 | 01-JAN-00:10 | 428070.75 | 26-JUN-18:10 |
HeatRejection:EnergyTransfer | 3133.36 | 0.00 | 01-JAN-00:10 | 584848.31 | 26-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 3133.36 | 0.00 | 01-JAN-00:10 | 584848.31 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -387.536 | 0.000 | 0.000 | 135.360 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.223 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.589 | -44.219 | 0.000 | 0.000 | 15.132 | 7.307 | 10.186 | 34.457 | 0.000 | 0.160 | 0.001 | 0.000 | -13.044 | 0.000 | -4.215 | -7.354 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.918 | 0.000 | 0.000 | 16.372 | 8.462 | 11.795 | 0.000 | 0.000 | 0.062 | 0.000 | 0.000 | 0.000 | 0.000 | -1.733 | -2.040 |
MECH_FLR_1 | 0.000 | 0.000 | 0.325 | -21.624 | 0.000 | 0.000 | 3.639 | 8.366 | 12.471 | 0.000 | 0.000 | 0.149 | 0.542 | 0.000 | 0.000 | 0.000 | -3.869 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.442 | -11.606 | 0.000 | 0.000 | 2.833 | 3.079 | 3.598 | 0.000 | 0.000 | 0.088 | 3.768 | 0.000 | 0.000 | 0.000 | -2.202 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -593.184 | 0.000 | 0.000 | 10.897 | 3.975 | 658.131 | 0.000 | 0.000 | 0.204 | 0.000 | 0.000 | 0.000 | 0.000 | -5.721 | -74.302 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.077 | -237.295 | 0.000 | 0.000 | 185.499 | 14.027 | 14.341 | 95.955 | 0.000 | 0.351 | 0.000 | 0.000 | -38.888 | 0.000 | -9.963 | -24.104 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -758.287 | 0.000 | 0.000 | 541.204 | 109.807 | 148.998 | 126.885 | 0.000 | 1.012 | 0.000 | 0.000 | -52.146 | 0.000 | -28.962 | -88.512 |
ROOM_1_FLR_3 | 18.555 | -47.977 | 0.000 | -9.153 | 0.000 | 0.000 | 9.688 | 9.244 | 10.478 | 61.118 | 0.000 | 0.572 | 0.000 | 0.000 | -28.786 | 0.000 | -9.818 | -13.920 |
ROOM_2_FLR_3 | 24.859 | -30.893 | 0.000 | -9.571 | 0.000 | 0.000 | 9.572 | 9.243 | 10.477 | 40.088 | 0.000 | 0.496 | 0.000 | 0.000 | -29.779 | 0.000 | -10.228 | -14.263 |
ROOM_3_MULT19_FLR_3 | 0.000 | -347.396 | 0.000 | -12.577 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 396.428 | 0.000 | 0.965 | 0.041 | 0.000 | -196.618 | 0.000 | -63.903 | -82.281 |
ROOM_4_MULT19_FLR_3 | 86.732 | -210.359 | 0.000 | -127.180 | 0.000 | 0.000 | 182.954 | 110.415 | 195.050 | 97.181 | 0.000 | 2.902 | 0.000 | 0.000 | -164.619 | 0.000 | -64.056 | -109.019 |
ROOM_5_FLR_3 | 18.906 | -51.575 | 0.000 | -9.163 | 0.000 | 0.000 | 9.682 | 9.244 | 10.478 | 64.107 | 0.000 | 0.573 | 0.000 | 0.000 | -28.351 | 0.000 | -9.854 | -14.047 |
ROOM_6_FLR_3 | 25.119 | -34.086 | 0.000 | -9.587 | 0.000 | 0.000 | 9.575 | 9.243 | 10.477 | 42.777 | 0.000 | 0.491 | 0.000 | 0.000 | -29.084 | 0.000 | -10.284 | -14.641 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 1.198 | -175.866 | 0.000 | 0.000 | 115.651 | 91.336 | 0.000 | 57.153 | 0.000 | 0.455 | 0.000 | 0.000 | -37.581 | 0.000 | -11.878 | -40.468 |
ROOM_1_FLR_6 | 7.025 | -11.805 | 0.000 | -2.289 | 0.000 | 0.000 | 2.424 | 2.311 | 2.620 | 15.203 | 0.000 | 0.143 | 0.000 | 0.000 | -7.148 | 0.000 | -2.480 | -6.005 |
ROOM_2_FLR_6 | 9.062 | -7.722 | 0.000 | -2.394 | 0.000 | 0.000 | 2.394 | 2.311 | 2.619 | 9.975 | 0.000 | 0.122 | 0.000 | 0.000 | -7.398 | 0.000 | -2.576 | -6.393 |
ROOM_3_MULT9_FLR_6 | 18.881 | -85.540 | 0.000 | -14.754 | 0.000 | 0.000 | 21.747 | 13.076 | 23.098 | 90.441 | 0.000 | 0.745 | 0.002 | 0.000 | -33.567 | 0.000 | -12.242 | -21.886 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -424.934 | 0.000 | 0.000 | 315.240 | 30.748 | 175.857 | 9.853 | 0.000 | 0.217 | 0.000 | 0.000 | -22.242 | 0.000 | -6.661 | -78.077 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -464.666 | 0.000 | 0.000 | 314.560 | 30.748 | 175.857 | 9.681 | 0.000 | 0.217 | 0.000 | 0.000 | -22.730 | 0.000 | -6.692 | -36.975 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -628.506 | 0.000 | 0.000 | 28.086 | 12.972 | 550.372 | 29.011 | 0.000 | 0.194 | 29.180 | 0.000 | -15.316 | 0.000 | -5.993 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.995 | -88.335 | 0.000 | 0.000 | 30.857 | 24.166 | 0.000 | 28.489 | 0.000 | 0.192 | 24.631 | 0.000 | -16.758 | 0.000 | -5.239 | -0.001 |
Total Facility | 209.138 | -827.353 | 5.625 | -4065.645 | 0.000 | 0.000 | 1963.367 | 781.761 | 2365.005 | 1208.803 | 0.000 | 10.312 | 58.167 | 0.000 | -744.055 | 0.000 | -278.571 | -686.512 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-OCT-21:00 | 0.00 | 0.00 | 0.00 | -22633.72 | 0.00 | 0.00 | 5924.48 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4140.97 |
RETAIL_1_FLR_1 | 07-NOV-12:40 | 0.00 | 0.00 | 0.00 | -5018.45 | 0.00 | 0.00 | 149.39 | 166.00 | 252.59 | 7610.19 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -40.36 | -3119.35 |
RETAIL_2_FLR_1 | 26-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2226.60 | 0.00 | 0.00 | 697.60 | 615.12 | 752.15 | 0.00 | 0.00 | 29.08 | 132.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 17-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1890.41 | 0.00 | 0.00 | 128.89 | 684.18 | 839.45 | 0.00 | 0.00 | 51.71 | 186.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 26-JUN-19:10 | 0.00 | 0.00 | 0.00 | -917.03 | 0.00 | 0.00 | 99.29 | 251.84 | 242.16 | 0.00 | 0.00 | 53.89 | 269.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39303.00 | 0.00 | 0.00 | 408.85 | 325.08 | 44299.38 | 0.00 | 0.00 | 101.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5831.54 |
CAFE_FLR_1 | 18-FEB-13:10 | 0.00 | 0.00 | 0.00 | -17836.91 | 0.00 | 0.00 | 2968.78 | 103.98 | 355.63 | 20997.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -86.18 | -6502.32 |
LOBBY_FLR_1 | 16-AUG-20:10 | 0.00 | 0.00 | 0.00 | -42651.86 | 0.00 | 0.00 | 23502.71 | 8448.71 | 9501.36 | 291.56 | 0.00 | 268.90 | 638.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 16-AUG-15:02 | 0.00 | -10219.29 | 0.00 | -629.93 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 11991.39 | 0.00 | 280.88 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2057.73 |
ROOM_2_FLR_3 | 08-APR-18:01 | 0.00 | -11058.80 | 0.00 | -587.40 | 0.00 | 0.00 | 236.32 | 711.45 | 484.60 | 1949.15 | 0.00 | 0.00 | 8531.80 | 0.00 | -0.00 | 0.00 | -267.11 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-JAN-12:40 | 0.00 | -64551.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 96507.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -723.57 | -35964.94 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -60027.91 | 0.00 | -9746.42 | 0.00 | 0.00 | 2222.09 | 4759.18 | 12159.85 | 9144.01 | 0.00 | 163.88 | 41325.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 19-APR-08:51 | 0.00 | -10164.15 | 0.00 | -682.32 | 0.00 | 0.00 | 71.66 | 313.07 | 453.05 | 10837.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -169.99 | -658.48 |
ROOM_6_FLR_3 | 27-JUN-08:32 | 0.00 | -10702.34 | 0.00 | -872.12 | 0.00 | 0.00 | 58.86 | 313.04 | 452.99 | 9517.19 | 0.00 | 0.00 | 1287.41 | 0.00 | -0.00 | 0.00 | -55.03 | 0.00 |
CORRIDOR_FLR_3 | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -13354.48 | 0.00 | 0.00 | 4080.25 | 6639.35 | 0.00 | 3469.77 | 0.00 | 325.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1160.68 |
ROOM_1_FLR_6 | 16-AUG-15:02 | 0.00 | -2735.74 | 0.00 | -158.45 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 2983.11 | 0.00 | 69.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -317.17 |
ROOM_2_FLR_6 | 08-APR-18:01 | 0.00 | -2970.32 | 0.00 | -149.87 | 0.00 | 0.00 | 58.22 | 177.86 | 121.15 | 464.60 | 0.00 | 0.00 | 2366.63 | 0.00 | -0.00 | 0.00 | -68.27 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16-NOV-13:33 | 0.00 | -12937.45 | 0.00 | -892.18 | 0.00 | 0.00 | 178.49 | 281.79 | 278.71 | 17299.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -221.18 | -3987.52 |
BANQUET_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23377.89 | 0.00 | 0.00 | 15609.53 | 1992.02 | 6747.90 | 1.28 | 0.00 | 46.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1018.84 |
DINING_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24574.23 | 0.00 | 0.00 | 15599.07 | 1992.02 | 6747.90 | 0.00 | 0.00 | 45.95 | 200.31 | 0.00 | -11.03 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 05-AUG-10:50 | 0.00 | 0.00 | 0.00 | -31634.01 | 0.00 | 0.00 | 460.35 | 294.67 | 24259.91 | 3564.00 | 0.00 | 63.81 | 2991.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 | -7268.21 | 0.00 | 0.00 | 771.11 | 548.96 | 0.00 | 2361.76 | 0.00 | 138.68 | 3447.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-18:02 | 0.00 | -135720.74 | 0.00 | -207296.73 | 0.00 | 0.00 | 73664.69 | 54326.11 | 120482.43 | 44990.76 | 0.00 | 3601.05 | 45952.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 21-DEC-08:10 | 0.00 | 0.00 | 1858.73 | 0.00 | 0.00 | 0.00 | 369.39 | 265.60 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1974.35 | 0.00 | -447.13 | -433.08 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 22-DEC-05:00 | 0.00 | 0.00 | 873.35 | 0.00 | 0.00 | 0.00 | 197.29 | 76.02 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -428.79 | -894.59 |
STORAGE_FLR_1 | 21-DEC-18:02 | 0.00 | 0.00 | 670.47 | 0.00 | 0.00 | 0.00 | 84.42 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -252.89 | -848.32 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-09:25 | 0.00 | 0.00 | 3034.46 | 0.00 | 0.00 | 0.00 | 2352.28 | 264.68 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3963.32 | 0.00 | -1009.72 | -1186.43 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-DEC-09:13 | 7512.73 | 294.39 | 0.00 | -294.39 | 0.00 | 0.00 | 99.81 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3277.46 | 0.00 | -1043.58 | -4057.62 |
ROOM_2_FLR_3 | 20-DEC-16:13 | 7480.97 | 293.91 | 0.00 | -293.91 | 0.00 | 0.00 | 269.17 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3276.94 | 0.00 | -961.76 | -3910.81 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:13 | 40563.65 | 3714.83 | 0.00 | -3714.83 | 0.00 | 0.00 | 5187.63 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19049.49 | 0.00 | -5304.33 | -27503.46 |
ROOM_5_FLR_3 | 21-DEC-09:13 | 7256.40 | 288.96 | 0.00 | -288.96 | 0.00 | 0.00 | 100.36 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3268.14 | 0.00 | -1041.28 | -3813.45 |
ROOM_6_FLR_3 | 21-DEC-16:13 | 7271.98 | 281.46 | 0.00 | -281.46 | 0.00 | 0.00 | 272.37 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3518.75 | 0.00 | -1003.43 | -3421.53 |
CORRIDOR_FLR_3 | 21-DEC-09:30 | 0.00 | 0.00 | 5371.41 | 0.00 | 0.00 | 0.00 | 1387.16 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4143.90 | 0.00 | -1282.95 | -4651.40 |
ROOM_1_FLR_6 | 21-DEC-09:13 | 2237.75 | 71.18 | 0.00 | -71.18 | 0.00 | 0.00 | 25.23 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -817.37 | 0.00 | -260.32 | -1376.82 |
ROOM_2_FLR_6 | 20-DEC-16:13 | 2227.28 | 70.34 | 0.00 | -70.34 | 0.00 | 0.00 | 68.29 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -816.70 | 0.00 | -239.56 | -1339.15 |
ROOM_3_MULT9_FLR_6 | 20-DEC-16:13 | 10334.27 | 466.57 | 0.00 | -466.57 | 0.00 | 0.00 | 606.99 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3849.99 | 0.00 | -1107.45 | -6706.90 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 23-DEC-07:20 | 0.00 | 0.00 | 3816.52 | 0.00 | 0.00 | 0.00 | 916.56 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2367.13 | 0.00 | -603.35 | -2421.36 |
Total Facility | 21-DEC-09:13 | 18813.61 | 70554.42 | 15299.34 | -70554.42 | 0.00 | 0.00 | 23908.64 | 27037.32 | 88178.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76064.27 | 0.00 | -26093.54 | -71080.01 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 27.0455 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.8939 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.5227 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6566 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9617 | 2.9617 | 1.2765 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4491 | 0.4491 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2782 | 0.2782 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2236 | 0.2236 | 0.0964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1332 | 0.1332 | 0.0574 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0096 | 4.0096 | 1.7281 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8810 | 1.8810 | 0.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9526 | 5.9526 | 2.5656 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8902 | 1.8902 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6831 | 2.6831 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8107 | 2.8107 | 1.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7872 | 2.7872 | 1.2013 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9854 | 0.9854 | 0.4247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 27.0455 | 26.8939 | 27.0455 | 11.6566 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4809 | 1.4809 | 1.2765 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2245 | 0.2245 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1391 | 0.1391 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1118 | 0.1118 | 0.0964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0666 | 0.0666 | 0.0574 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0048 | 2.0048 | 1.7281 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9405 | 0.9405 | 0.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9763 | 2.9763 | 2.5656 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9451 | 0.9451 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3416 | 1.3416 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4053 | 1.4053 | 1.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3936 | 1.3936 | 1.2013 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4927 | 0.4927 | 0.4247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.5227 | 11.6566 | 11.6566 | 11.6566 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 8.00 |
Number of hours cooling loads not met | 467.33 |
Number of hours not met | 475.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1309.28 | 307078.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 765.98 | 156777.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.76 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.79 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 581.24 | 61239.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 69.59 | 5590.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 163.69 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.73 | 3214.61 | 293470.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.43 | 1893.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.81 | 1197.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.52 | 5007.11 |
Natural Gas | 1788.84 | 6312.73 |
Additional | 0.00 | 0.00 |
Total | 3508.36 | 11319.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.91 |
Space Heating | 0.00 |
Space Cooling | 67.52 |
Fans (All) | 51.23 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 441.34 |
Subtotal | 441.34 |
Natural Gas [MJ/m2] | |
Space Heating | 115.40 |
Service Water Heating | 283.34 |
Miscellaneous (All) | 556.42 |
Subtotal | 556.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.91 |
Space Heating | 11.57 |
Space Cooling | 6.77 |
Fans (All) | 5.13 |
Service Water Heating | 29.20 |
Receptacle Equipment | 30.45 |
Miscellaneous | 9.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8535.83 | 224.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8708.67 | 51.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8535.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 224.17 | 0.00 | 0.00 | 0.00 |
Average | 8745.29 | 14.71 | 0.00 | 0.00 | 0.00 |
Sum | 192396.33 | 323.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4146.50 | 7.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 7.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.61 | 0.44 | 0.00 | 0.00 | 0.00 |
Sum | 6355505.33 | 9.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8686.83 | 73.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8436.33 | 323.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8692.33 | 67.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8713.50 | 46.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8436.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 323.67 | 0.00 | 0.00 | 0.00 |
Average | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Sum | 192052.67 | 667.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59148.67 | 7.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 701492.67 | 8924.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2100599.33 | 14829.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4142.67 | 11.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4147.17 | 6.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4133.67 | 20.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1235686.33 | 10028.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1238241.33 | 7473.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2100599.33 | 14829.67 | 0.00 | 0.00 | 0.00 |
Average | 287009.67 | 1877.38 | 0.00 | 0.00 | 0.00 |
Sum | 6314212.67 | 41302.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308850E+11 | 17991.44 | 26-JAN-22:00 | 4.00 | 2.09 | 0.815675E+10 | 4837.05 | 18-JAN-22:19 | 4.00 | 2.09 |
February | 0.261124E+11 | 16396.92 | 01-FEB-22:00 | -8.0 | -8.0 | 0.727481E+10 | 4836.97 | 22-FEB-22:19 | 2.67 | 2.34 |
March | 0.275863E+11 | 15069.68 | 01-MAR-22:00 | -4.0 | -4.0 | 0.791760E+10 | 4837.07 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.269432E+11 | 14074.66 | 14-APR-21:00 | 1.00 | -0.9 | 0.768153E+10 | 4837.02 | 07-APR-21:10 | 1.00 | -0.9 |
May | 0.282147E+11 | 13533.86 | 19-MAY-21:00 | 10.00 | 6.74 | 0.791409E+10 | 4837.12 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.298479E+11 | 16468.94 | 16-JUN-21:00 | 21.60 | 14.78 | 0.783151E+10 | 4837.45 | 07-JUN-21:10 | 21.60 | 14.78 |
July | 0.314645E+11 | 17215.06 | 28-JUL-21:00 | 16.00 | 15.35 | 0.811002E+10 | 4837.13 | 15-JUL-00:10 | 16.00 | 15.35 |
August | 0.352897E+11 | 19894.17 | 18-AUG-21:00 | 19.00 | 9.02 | 0.822651E+10 | 4837.47 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.383099E+11 | 22574.97 | 15-SEP-21:00 | 12.20 | 6.07 | 0.797141E+10 | 4837.69 | 01-SEP-01:10 | 12.20 | 6.07 |
October | 0.393293E+11 | 22633.95 | 20-OCT-21:00 | 10.00 | 1.41 | 0.823327E+10 | 4837.21 | 27-OCT-01:10 | 5.00 | 5.00 |
November | 0.372822E+11 | 22330.53 | 09-NOV-22:00 | 8.00 | 6.33 | 0.796021E+10 | 4837.11 | 09-NOV-02:20 | 8.00 | 6.33 |
December | 0.362684E+11 | 21394.92 | 05-DEC-22:00 | -4.0 | -4.0 | 0.822374E+10 | 4837.08 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.387534E+12 | 0.955015E+11 | ||||||||
Minimum of Months | 0.261124E+11 | 13533.86 | -8.0 | -8.0 | 0.727481E+10 | 4836.97 | 1.00 | -2.3 | ||
Maximum of Months | 0.393293E+11 | 22633.95 | 21.60 | 15.35 | 0.823327E+10 | 4837.69 | 21.60 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335722E+10 | 4991.97 | 20-JAN-13:10 | 21.00 | 6.97 | 0.665057E+09 | 453.44 | 20-JAN-22:19 | 7.67 | 1.92 |
February | 0.276714E+10 | 4973.06 | 18-FEB-13:20 | 20.00 | 7.74 | 0.600958E+09 | 441.47 | 17-FEB-22:19 | 20.00 | 7.74 |
March | 0.299972E+10 | 4616.48 | 14-MAR-12:40 | 23.33 | 7.71 | 0.678105E+09 | 481.85 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.231635E+10 | 3255.08 | 07-APR-12:30 | 20.50 | 8.13 | 0.636096E+09 | 458.32 | 07-APR-21:30 | 11.50 | 6.33 |
May | 0.351933E+10 | 2380.20 | 05-MAY-13:00 | 22.00 | 10.96 | 0.692628E+09 | 470.50 | 31-MAY-21:30 | 17.65 | 11.72 |
June | 0.452240E+10 | 3059.58 | 26-JUN-12:40 | 36.43 | 15.33 | 0.756196E+09 | 491.88 | 07-JUN-21:10 | 36.43 | 15.33 |
July | 0.473095E+10 | 3303.56 | 23-JUL-12:00 | 32.00 | 15.97 | 0.781653E+09 | 491.84 | 12-JUL-22:10 | 32.00 | 15.97 |
August | 0.509060E+10 | 4020.40 | 31-AUG-12:40 | 30.00 | 12.25 | 0.785648E+09 | 491.87 | 25-AUG-22:10 | 30.00 | 12.25 |
September | 0.492992E+10 | 4901.24 | 28-SEP-12:50 | 30.42 | 11.32 | 0.744898E+09 | 491.84 | 08-SEP-22:10 | 30.42 | 11.32 |
October | 0.384454E+10 | 4942.20 | 10-OCT-12:30 | 23.50 | 7.91 | 0.696847E+09 | 490.14 | 10-OCT-21:19 | 13.67 | 4.16 |
November | 0.343775E+10 | 5019.27 | 07-NOV-12:40 | 20.00 | 7.20 | 0.651856E+09 | 455.88 | 07-NOV-22:19 | 7.00 | 2.01 |
December | 0.270310E+10 | 4654.61 | 17-DEC-13:00 | 18.00 | 5.78 | 0.652338E+09 | 422.01 | 04-DEC-22:30 | 18.00 | 5.78 |
Annual Sum or Average | 0.442190E+11 | 0.834228E+10 | ||||||||
Minimum of Months | 0.231635E+10 | 2380.20 | 18.00 | 5.78 | 0.600958E+09 | 422.01 | 7.00 | 1.92 | ||
Maximum of Months | 0.509060E+10 | 5019.27 | 36.43 | 15.97 | 0.785648E+09 | 491.88 | 36.43 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242595E+10 | 1533.37 | 20-JAN-22:00 | 8.00 | 2.08 | 0.888686E+09 | 569.52 | 25-JAN-23:30 | 1.00 | -0.7 |
February | 0.211337E+10 | 1428.61 | 27-FEB-21:10 | 3.67 | 0.22 | 0.789185E+09 | 569.52 | 22-FEB-22:19 | 3.67 | 0.22 |
March | 0.249930E+10 | 1816.20 | 15-MAR-21:00 | 13.00 | 3.08 | 0.892398E+09 | 569.55 | 14-MAR-21:10 | 13.00 | 3.08 |
April | 0.235263E+10 | 1595.84 | 07-APR-21:00 | 12.00 | 6.33 | 0.858109E+09 | 569.53 | 12-APR-23:10 | 7.17 | 2.91 |
May | 0.277751E+10 | 1784.80 | 31-MAY-21:00 | 18.00 | 12.50 | 0.936729E+09 | 569.55 | 30-MAY-21:10 | 18.00 | 12.50 |
June | 0.334315E+10 | 2226.34 | 26-JUN-20:10 | 32.05 | 13.25 | 0.937552E+09 | 569.60 | 07-JUN-21:10 | 32.05 | 13.25 |
July | 0.343368E+10 | 2134.31 | 17-JUL-21:00 | 29.00 | 13.54 | 0.965599E+09 | 569.55 | 12-JUL-22:10 | 29.00 | 13.54 |
August | 0.344939E+10 | 2216.47 | 16-AUG-20:10 | 28.50 | 11.68 | 0.969883E+09 | 569.59 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.318301E+10 | 2087.10 | 12-SEP-20:03 | 23.72 | 13.29 | 0.932465E+09 | 569.63 | 01-SEP-01:10 | 23.72 | 13.29 |
October | 0.269172E+10 | 1877.04 | 11-OCT-20:10 | 10.83 | 5.03 | 0.917631E+09 | 569.53 | 11-OCT-00:20 | 10.83 | 5.03 |
November | 0.241034E+10 | 1636.46 | 07-NOV-21:10 | 7.00 | 1.69 | 0.866049E+09 | 569.52 | 17-NOV-23:49 | 6.00 | 3.31 |
December | 0.223755E+10 | 1380.75 | 04-DEC-22:00 | 7.00 | 0.68 | 0.857104E+09 | 569.51 | 04-DEC-22:19 | 7.33 | 0.76 |
Annual Sum or Average | 0.329176E+11 | 0.108114E+11 | ||||||||
Minimum of Months | 0.211337E+10 | 1380.75 | 3.67 | 0.22 | 0.789185E+09 | 569.51 | 1.00 | -0.7 | ||
Maximum of Months | 0.344939E+10 | 2226.34 | 32.05 | 13.54 | 0.969883E+09 | 569.63 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137733E+10 | 867.26 | 20-JAN-13:40 | 21.00 | 6.96 | 0.161235E+09 | 107.78 | 24-JAN-22:10 | 3.00 | 0.25 |
February | 0.102832E+10 | 859.83 | 18-FEB-13:30 | 20.00 | 7.73 | 0.144134E+09 | 108.05 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.150739E+10 | 930.51 | 15-MAR-10:33 | 15.67 | 4.43 | 0.166250E+09 | 116.77 | 15-MAR-21:19 | 12.67 | 3.04 |
April | 0.151380E+10 | 882.62 | 21-APR-10:33 | 13.33 | 5.84 | 0.161503E+09 | 112.46 | 20-APR-21:19 | 13.33 | 5.84 |
May | 0.197694E+10 | 1067.24 | 17-MAY-21:00 | 17.00 | 8.20 | 0.186373E+09 | 120.45 | 17-MAY-21:00 | 18.00 | 9.24 |
June | 0.251509E+10 | 1866.83 | 26-JUN-20:00 | 32.70 | 13.66 | 0.196860E+09 | 120.46 | 07-JUN-21:10 | 32.70 | 13.66 |
July | 0.265972E+10 | 1890.10 | 17-JUL-20:00 | 30.00 | 13.88 | 0.203510E+09 | 120.46 | 15-JUL-00:10 | 30.00 | 13.88 |
August | 0.251038E+10 | 1735.13 | 16-AUG-20:00 | 29.00 | 11.91 | 0.203447E+09 | 120.46 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.222550E+10 | 1564.41 | 12-SEP-20:00 | 23.80 | 13.35 | 0.191990E+09 | 120.46 | 20-SEP-21:10 | 15.32 | 11.76 |
October | 0.173334E+10 | 962.30 | 01-OCT-10:35 | 14.67 | 8.01 | 0.176143E+09 | 119.30 | 11-OCT-21:10 | 9.67 | 4.56 |
November | 0.143440E+10 | 906.02 | 07-NOV-13:30 | 21.00 | 7.19 | 0.159491E+09 | 113.58 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 0.114184E+10 | 795.15 | 03-DEC-13:00 | 17.20 | 6.28 | 0.158768E+09 | 108.16 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.216241E+11 | 0.210970E+10 | ||||||||
Minimum of Months | 0.102832E+10 | 795.15 | 13.33 | 4.43 | 0.144134E+09 | 107.78 | 2.00 | -0.8 | ||
Maximum of Months | 0.265972E+10 | 1890.10 | 32.70 | 13.88 | 0.203510E+09 | 120.46 | 32.70 | 13.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.707693E+09 | 514.67 | 20-JAN-13:40 | 21.00 | 6.96 | 0.121217E+09 | 79.12 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.505108E+09 | 511.82 | 18-FEB-13:30 | 20.00 | 7.73 | 0.108938E+09 | 78.87 | 27-FEB-22:30 | 2.00 | -0.8 |
March | 0.774621E+09 | 542.63 | 15-MAR-10:33 | 15.67 | 4.43 | 0.124858E+09 | 85.78 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.807705E+09 | 514.33 | 21-APR-10:33 | 13.33 | 5.84 | 0.120943E+09 | 83.16 | 20-APR-22:10 | 13.33 | 5.84 |
May | 0.113394E+10 | 571.84 | 18-MAY-10:33 | 22.00 | 11.41 | 0.139052E+09 | 90.20 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.135892E+10 | 916.92 | 26-JUN-19:10 | 35.03 | 14.34 | 0.149538E+09 | 92.66 | 07-JUN-21:10 | 35.03 | 14.34 |
July | 0.142584E+10 | 886.87 | 17-JUL-20:00 | 30.00 | 13.88 | 0.154998E+09 | 92.66 | 15-JUL-00:10 | 30.00 | 13.88 |
August | 0.136232E+10 | 801.30 | 16-AUG-20:00 | 29.00 | 11.91 | 0.154341E+09 | 92.66 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.123412E+10 | 676.07 | 12-SEP-21:00 | 23.30 | 12.99 | 0.144508E+09 | 92.66 | 08-SEP-21:00 | 23.30 | 12.99 |
October | 0.953094E+09 | 565.39 | 11-OCT-12:50 | 25.83 | 9.40 | 0.131509E+09 | 87.43 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.772408E+09 | 535.77 | 07-NOV-13:30 | 21.00 | 7.19 | 0.119494E+09 | 83.22 | 09-NOV-22:30 | 8.00 | 6.60 |
December | 0.570113E+09 | 468.01 | 03-DEC-13:00 | 17.20 | 6.28 | 0.119933E+09 | 79.38 | 04-DEC-23:10 | 7.83 | 0.81 |
Annual Sum or Average | 0.116059E+11 | 0.158933E+10 | ||||||||
Minimum of Months | 0.505108E+09 | 468.01 | 13.33 | 4.43 | 0.108938E+09 | 78.87 | 2.00 | -0.8 | ||
Maximum of Months | 0.142584E+10 | 916.92 | 35.03 | 14.34 | 0.154998E+09 | 92.66 | 35.03 | 14.34 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486288E+11 | 37685.65 | 20-JAN-21:00 | 7.00 | 1.60 | 0.615780E+09 | 381.77 | 18-JAN-22:10 | 7.00 | 1.60 |
February | 0.436661E+11 | 37660.65 | 27-FEB-21:00 | 4.00 | 0.39 | 0.555106E+09 | 381.74 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.493718E+11 | 38311.04 | 14-MAR-20:00 | 16.00 | 5.00 | 0.619189E+09 | 381.79 | 16-MAR-21:10 | 10.00 | 4.14 |
April | 0.476992E+11 | 38320.58 | 20-APR-19:55 | 15.00 | 7.97 | 0.598810E+09 | 381.80 | 07-APR-21:10 | 15.00 | 7.97 |
May | 0.511431E+11 | 38648.60 | 16-MAY-20:00 | 19.00 | 9.69 | 0.623660E+09 | 381.83 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.513421E+11 | 39299.76 | 26-JUN-20:00 | 32.70 | 13.66 | 0.608794E+09 | 394.58 | 14-JUN-21:10 | 32.70 | 13.66 |
July | 0.528335E+11 | 39319.26 | 07-JUL-19:40 | 24.00 | 12.33 | 0.627581E+09 | 387.86 | 17-JUL-21:10 | 28.50 | 13.44 |
August | 0.529391E+11 | 39203.89 | 16-AUG-20:00 | 29.00 | 11.91 | 0.628390E+09 | 382.02 | 25-AUG-21:10 | 24.00 | 14.43 |
September | 0.504218E+11 | 38878.02 | 12-SEP-20:00 | 23.80 | 13.35 | 0.605910E+09 | 381.89 | 08-SEP-21:10 | 23.80 | 13.35 |
October | 0.498456E+11 | 38218.10 | 11-OCT-20:00 | 11.00 | 5.10 | 0.619195E+09 | 381.84 | 04-OCT-21:10 | 11.00 | 5.10 |
November | 0.474808E+11 | 37875.29 | 09-NOV-21:00 | 9.00 | 7.27 | 0.596437E+09 | 381.80 | 07-NOV-22:10 | 9.00 | 7.27 |
December | 0.478091E+11 | 37488.67 | 04-DEC-21:00 | 7.00 | 0.68 | 0.612876E+09 | 381.75 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.593181E+12 | 0.731173E+10 | ||||||||
Minimum of Months | 0.436661E+11 | 37488.67 | 4.00 | 0.39 | 0.555106E+09 | 381.74 | 2.00 | -0.8 | ||
Maximum of Months | 0.529391E+11 | 39319.26 | 32.70 | 13.66 | 0.628390E+09 | 394.58 | 32.70 | 14.43 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194762E+11 | 17412.87 | 20-JAN-13:00 | 21.00 | 6.97 | 0.102063E+11 | 6461.80 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.167323E+11 | 17836.82 | 18-FEB-13:10 | 20.00 | 7.74 | 0.907589E+10 | 6461.77 | 18-FEB-02:20 | 20.00 | 7.74 |
March | 0.183975E+11 | 16379.36 | 11-MAR-13:00 | 17.00 | 5.47 | 0.101539E+11 | 6462.53 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.158416E+11 | 12161.64 | 07-APR-12:30 | 20.50 | 8.13 | 0.968375E+10 | 6461.92 | 01-APR-01:19 | 20.50 | 8.13 |
May | 0.186116E+11 | 10031.93 | 10-MAY-21:10 | 20.33 | 7.92 | 0.106332E+11 | 6462.64 | 15-MAY-21:40 | 13.33 | 9.13 |
June | 0.215831E+11 | 11766.17 | 26-JUN-21:10 | 28.17 | 11.17 | 0.106085E+11 | 6462.72 | 06-JUN-22:10 | 28.17 | 11.17 |
July | 0.225430E+11 | 11851.48 | 17-JUL-21:10 | 28.50 | 13.44 | 0.109263E+11 | 6462.65 | 03-JUL-22:10 | 28.50 | 13.44 |
August | 0.238137E+11 | 13798.66 | 26-AUG-12:40 | 31.67 | 13.33 | 0.109811E+11 | 6462.68 | 11-AUG-22:10 | 31.67 | 13.33 |
September | 0.230997E+11 | 16132.22 | 28-SEP-12:50 | 30.42 | 11.32 | 0.105547E+11 | 6462.71 | 01-SEP-00:49 | 30.42 | 11.32 |
October | 0.204031E+11 | 16473.27 | 07-OCT-12:20 | 23.00 | 9.55 | 0.103863E+11 | 6462.06 | 06-OCT-04:19 | 23.00 | 9.55 |
November | 0.193222E+11 | 17784.92 | 05-NOV-12:00 | 20.00 | 5.63 | 0.990886E+10 | 6462.06 | 06-NOV-05:19 | 6.00 | -0.7 |
December | 0.174692E+11 | 17099.79 | 17-DEC-13:00 | 18.00 | 5.78 | 0.985007E+10 | 6461.43 | 02-DEC-02:20 | 18.00 | 5.78 |
Annual Sum or Average | 0.237293E+12 | 0.122969E+12 | ||||||||
Minimum of Months | 0.158416E+11 | 10031.93 | 17.00 | 5.47 | 0.907589E+10 | 6461.43 | 6.00 | -0.7 | ||
Maximum of Months | 0.238137E+11 | 17836.82 | 31.67 | 13.44 | 0.109811E+11 | 6462.72 | 31.67 | 13.44 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578017E+11 | 34808.59 | 20-JAN-22:10 | 7.83 | 2.00 | 0.314785E+11 | 19184.96 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.505038E+11 | 33154.73 | 17-FEB-22:10 | 7.00 | 3.16 | 0.280095E+11 | 19185.01 | 25-FEB-02:20 | -0.3 | -1.6 |
March | 0.585476E+11 | 37345.03 | 15-MAR-21:10 | 12.83 | 3.06 | 0.313320E+11 | 19185.90 | 14-MAR-21:10 | 12.83 | 3.06 |
April | 0.545702E+11 | 34407.50 | 20-APR-21:10 | 14.00 | 7.96 | 0.301423E+11 | 19185.42 | 13-APR-04:19 | 14.00 | 7.96 |
May | 0.641241E+11 | 36892.88 | 17-MAY-21:10 | 17.17 | 8.37 | 0.322107E+11 | 19186.06 | 15-MAY-21:40 | 17.17 | 8.37 |
June | 0.728808E+11 | 42510.93 | 26-JUN-20:10 | 32.05 | 13.25 | 0.316029E+11 | 19186.52 | 01-JUN-01:10 | 32.05 | 13.25 |
July | 0.757277E+11 | 42387.26 | 17-JUL-21:10 | 28.50 | 13.44 | 0.325554E+11 | 19186.15 | 12-JUL-22:10 | 28.50 | 13.44 |
August | 0.766880E+11 | 42655.13 | 16-AUG-20:10 | 28.50 | 11.68 | 0.327144E+11 | 19186.65 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.722508E+11 | 41304.92 | 12-SEP-21:10 | 22.93 | 12.81 | 0.315538E+11 | 19188.11 | 01-SEP-01:10 | 22.93 | 12.81 |
October | 0.634080E+11 | 38255.75 | 10-OCT-21:10 | 13.83 | 4.11 | 0.318140E+11 | 19185.38 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.575447E+11 | 35456.51 | 07-NOV-22:10 | 7.00 | 2.01 | 0.305188E+11 | 19185.36 | 06-NOV-05:19 | 7.00 | 2.01 |
December | 0.542318E+11 | 32555.06 | 04-DEC-22:10 | 7.17 | 0.72 | 0.305897E+11 | 19185.37 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.758279E+12 | 0.374522E+12 | ||||||||
Minimum of Months | 0.505038E+11 | 32555.06 | 7.00 | 0.72 | 0.280095E+11 | 19184.96 | -0.3 | -2.3 | ||
Maximum of Months | 0.766880E+11 | 42655.13 | 32.05 | 13.44 | 0.327144E+11 | 19188.11 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327253E+09 | 2562.51 | 23-JAN-16:02 | 18.17 | 6.14 | 96628612.91 | 56.69 | 06-JAN-05:19 | 18.17 | 6.14 |
February | 0.344955E+09 | 2562.26 | 25-FEB-16:02 | 12.00 | 3.90 | 86954540.16 | 56.69 | 08-FEB-05:19 | 12.00 | 3.90 |
March | 0.672764E+09 | 2672.85 | 13-MAR-15:02 | 23.00 | 6.97 | 96658048.59 | 56.69 | 13-MAR-21:19 | 10.67 | 1.98 |
April | 0.466126E+09 | 2624.02 | 07-APR-15:02 | 21.00 | 7.80 | 93355134.17 | 56.69 | 20-APR-22:19 | 13.67 | 7.86 |
May | 0.114426E+10 | 2598.27 | 09-MAY-15:02 | 21.17 | 8.58 | 98633633.49 | 56.69 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.237854E+10 | 2685.26 | 30-JUN-17:04 | 32.80 | 13.10 | 96519271.50 | 56.71 | 26-JUN-21:10 | 32.80 | 13.10 |
July | 0.232068E+10 | 2706.11 | 15-JUL-17:04 | 33.83 | 13.38 | 99355341.70 | 56.70 | 24-JUL-21:10 | 23.33 | 16.45 |
August | 0.233818E+10 | 2712.29 | 16-AUG-15:02 | 36.17 | 16.19 | 99650359.34 | 56.70 | 16-AUG-21:49 | 24.33 | 13.24 |
September | 0.193563E+10 | 2710.46 | 28-SEP-15:02 | 29.50 | 11.04 | 95886656.87 | 56.69 | 01-SEP-21:30 | 29.50 | 11.04 |
October | 0.926900E+09 | 2694.81 | 11-OCT-15:02 | 25.67 | 9.32 | 97238756.93 | 56.69 | 10-OCT-21:30 | 25.67 | 9.32 |
November | 0.450719E+09 | 2625.52 | 05-NOV-15:02 | 20.67 | 6.59 | 93739289.02 | 56.69 | 08-NOV-22:19 | 7.00 | 3.91 |
December | 0.211694E+09 | 2512.57 | 02-DEC-16:01 | 17.33 | 5.85 | 95587619.73 | 56.69 | 22-DEC-05:19 | -21.0 | -21.0 |
Annual Sum or Average | 0.135177E+11 | 0.115021E+10 | ||||||||
Minimum of Months | 0.211694E+09 | 2512.57 | 12.00 | 3.90 | 86954540.16 | 56.69 | -21.0 | -21.0 | ||
Maximum of Months | 0.237854E+10 | 2712.29 | 36.17 | 16.19 | 99650359.34 | 56.71 | 32.80 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63004743.19 | 2423.74 | 23-JAN-16:02 | 18.17 | 6.14 | 94658142.95 | 56.69 | 06-JAN-05:19 | 18.17 | 6.14 |
February | 88620604.81 | 2421.75 | 26-FEB-16:02 | 17.67 | 5.08 | 85489573.21 | 56.69 | 08-FEB-05:19 | 17.67 | 5.08 |
March | 0.294234E+09 | 2818.78 | 15-MAR-18:31 | 13.00 | 3.03 | 97358721.07 | 74.91 | 13-MAR-18:10 | 13.00 | 3.03 |
April | 0.257044E+09 | 2911.56 | 08-APR-18:01 | 13.50 | 4.30 | 94274972.35 | 78.55 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.839939E+09 | 2840.60 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103384E+09 | 81.99 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.206799E+10 | 2809.81 | 18-JUN-21:51 | 18.80 | 12.91 | 0.103599E+09 | 83.41 | 29-JUN-21:30 | 20.80 | 11.76 |
July | 0.195685E+10 | 2907.22 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106719E+09 | 87.42 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.182267E+10 | 2785.69 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106774E+09 | 82.41 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.128125E+10 | 2669.29 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102543E+09 | 79.52 | 12-SEP-21:10 | 12.70 | 6.10 |
October | 0.395716E+09 | 2773.80 | 14-OCT-16:11 | 14.00 | 3.81 | 98187307.32 | 64.07 | 10-OCT-20:40 | 14.00 | 3.81 |
November | 0.104860E+09 | 2469.44 | 07-NOV-16:02 | 20.00 | 7.03 | 92325967.11 | 56.69 | 01-NOV-04:19 | 20.00 | 7.03 |
December | 32401517.04 | 2402.29 | 02-DEC-16:01 | 17.33 | 5.85 | 94025806.44 | 56.69 | 24-DEC-02:20 | -21.0 | -21.2 |
Annual Sum or Average | 0.920458E+10 | 0.117934E+10 | ||||||||
Minimum of Months | 32401517.04 | 2402.29 | 12.70 | 3.03 | 85489573.21 | 56.69 | -21.0 | -21.2 | ||
Maximum of Months | 0.206799E+10 | 2911.56 | 26.00 | 12.91 | 0.106774E+09 | 87.42 | 20.80 | 11.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386892E+09 | 849.37 | 20-JAN-12:40 | 20.67 | 7.18 | 0.00 | 0.00 | 01-JAN-00:10 | 20.67 | 7.18 |
February | 0.268605E+09 | 806.39 | 18-FEB-13:00 | 20.00 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.74 |
March | 0.283304E+09 | 733.84 | 14-MAR-12:40 | 23.33 | 7.71 | 0.00 | 0.00 | 01-MAR-00:10 | 23.33 | 7.71 |
April | 99732603.49 | 425.93 | 12-APR-13:30 | 21.00 | 7.78 | 0.00 | 0.00 | 01-APR-00:10 | 21.00 | 7.78 |
May | 0.259752E+09 | 340.73 | 16-MAY-13:20 | 27.33 | 12.20 | 0.00 | 0.00 | 01-MAY-00:10 | 27.33 | 12.20 |
June | 0.519318E+09 | 428.42 | 14-JUN-13:30 | 34.95 | 13.21 | 0.00 | 0.00 | 01-JUN-00:10 | 34.95 | 13.21 |
July | 0.567304E+09 | 463.58 | 23-JUL-13:10 | 34.17 | 16.17 | 0.00 | 0.00 | 01-JUL-00:10 | 34.17 | 16.17 |
August | 0.643718E+09 | 592.77 | 31-AUG-12:40 | 30.00 | 12.25 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 12.25 |
September | 0.646824E+09 | 765.04 | 28-SEP-13:00 | 30.50 | 11.31 | 0.00 | 0.00 | 01-SEP-00:10 | 30.50 | 11.31 |
October | 0.460217E+09 | 790.79 | 10-OCT-12:30 | 23.50 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 23.50 | 7.91 |
November | 0.367644E+09 | 841.51 | 07-NOV-12:10 | 20.00 | 7.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.48 |
December | 0.233244E+09 | 755.72 | 17-DEC-13:00 | 18.00 | 5.78 | 0.00 | 0.00 | 01-DEC-00:10 | 18.00 | 5.78 |
Annual Sum or Average | 0.473655E+10 | 0.00 | ||||||||
Minimum of Months | 99732603.49 | 340.73 | 18.00 | 5.78 | 0.00 | 0.00 | 18.00 | 5.78 | ||
Maximum of Months | 0.646824E+09 | 849.37 | 34.95 | 16.17 | 0.00 | 0.00 | 34.95 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50465591.06 | 726.52 | 21-JAN-09:02 | 13.00 | 3.75 | 94971103.06 | 56.69 | 26-JAN-22:10 | 4.00 | 2.01 |
February | 43249267.20 | 731.47 | 19-FEB-09:01 | 5.17 | 2.82 | 85687528.93 | 56.69 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.140960E+09 | 793.65 | 14-MAR-20:51 | 13.00 | 3.78 | 96324856.03 | 63.79 | 14-MAR-20:49 | 13.00 | 3.78 |
April | 0.188565E+09 | 814.68 | 20-APR-20:31 | 14.33 | 7.97 | 93700742.47 | 64.85 | 20-APR-20:40 | 14.33 | 7.97 |
May | 0.468351E+09 | 838.65 | 17-MAY-21:51 | 18.00 | 9.24 | 0.101033E+09 | 75.74 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.763352E+09 | 876.28 | 12-JUN-08:61 | 26.97 | 12.63 | 0.101139E+09 | 79.13 | 22-JUN-21:49 | 16.52 | 14.01 |
July | 0.784809E+09 | 918.10 | 01-JUL-08:61 | 26.00 | 9.47 | 0.104852E+09 | 80.64 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.693463E+09 | 879.01 | 01-AUG-21:51 | 21.00 | 10.09 | 0.103967E+09 | 78.47 | 03-AUG-21:19 | 21.33 | 15.95 |
September | 0.528611E+09 | 852.04 | 09-SEP-21:51 | 21.60 | 11.20 | 99547862.79 | 75.91 | 13-SEP-21:30 | 14.95 | 10.84 |
October | 0.206476E+09 | 807.58 | 11-OCT-15:02 | 25.67 | 9.32 | 96787209.36 | 62.91 | 10-OCT-20:40 | 25.67 | 9.32 |
November | 78514107.37 | 739.58 | 06-NOV-19:01 | 13.33 | 3.91 | 92379615.25 | 56.69 | 06-NOV-22:10 | 7.83 | 1.71 |
December | 38512953.42 | 713.28 | 03-DEC-09:02 | 9.50 | 2.25 | 94558463.08 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.398533E+10 | 0.116495E+10 | ||||||||
Minimum of Months | 38512953.42 | 713.28 | 5.17 | 2.25 | 85687528.93 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.784809E+09 | 918.10 | 26.97 | 12.63 | 0.104852E+09 | 80.64 | 25.67 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319229E+09 | 2239.87 | 20-JAN-09:02 | 10.67 | 3.20 | 96843262.48 | 56.69 | 06-JAN-05:19 | 10.67 | 3.20 |
February | 0.380996E+09 | 2281.59 | 18-FEB-09:02 | 11.67 | 4.30 | 87210155.66 | 56.69 | 07-FEB-04:19 | 11.67 | 4.30 |
March | 0.712415E+09 | 2308.00 | 11-MAR-09:02 | 13.17 | 4.41 | 96980089.75 | 56.69 | 14-MAR-21:00 | 13.00 | 4.05 |
April | 0.545737E+09 | 2711.62 | 19-APR-08:51 | 18.00 | 8.66 | 93713174.44 | 56.69 | 19-APR-21:10 | 13.67 | 6.76 |
May | 0.123782E+10 | 2331.90 | 17-MAY-08:62 | 22.50 | 11.08 | 98911634.50 | 56.69 | 16-MAY-23:19 | 22.50 | 11.08 |
June | 0.251598E+10 | 2378.20 | 27-JUN-08:62 | 24.00 | 9.68 | 96266748.08 | 56.69 | 27-JUN-22:49 | 21.18 | 11.18 |
July | 0.256908E+10 | 2438.51 | 01-JUL-08:61 | 26.00 | 9.47 | 99415319.11 | 56.70 | 23-JUL-23:40 | 18.67 | 16.23 |
August | 0.257058E+10 | 2398.79 | 05-AUG-08:62 | 22.33 | 16.17 | 99468635.07 | 56.70 | 10-AUG-21:00 | 24.00 | 15.55 |
September | 0.202971E+10 | 2351.62 | 28-SEP-08:62 | 20.78 | 8.57 | 95991710.20 | 56.69 | 07-SEP-21:19 | 20.78 | 8.57 |
October | 0.890303E+09 | 2307.88 | 11-OCT-15:02 | 25.67 | 9.32 | 97455150.60 | 56.69 | 10-OCT-21:00 | 25.67 | 9.32 |
November | 0.434329E+09 | 2288.15 | 07-NOV-09:02 | 14.00 | 4.09 | 93792586.36 | 56.69 | 06-NOV-22:30 | 14.00 | 4.09 |
December | 0.216475E+09 | 2213.96 | 15-DEC-09:01 | 2.50 | -1.3 | 95711219.53 | 56.69 | 19-DEC-04:19 | -16.1 | -16.3 |
Annual Sum or Average | 0.144226E+11 | 0.115176E+10 | ||||||||
Minimum of Months | 0.216475E+09 | 2213.96 | 2.50 | -1.3 | 87210155.66 | 56.69 | -16.1 | -16.3 | ||
Maximum of Months | 0.257058E+10 | 2711.62 | 26.00 | 16.17 | 99468635.07 | 56.70 | 25.67 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68741456.04 | 2129.63 | 20-JAN-09:02 | 10.67 | 3.20 | 94422798.04 | 56.69 | 06-JAN-04:19 | 10.67 | 3.20 |
February | 0.120403E+09 | 2179.28 | 27-FEB-09:02 | 9.17 | 2.67 | 85596504.03 | 56.69 | 10-FEB-05:19 | 9.17 | 2.67 |
March | 0.348381E+09 | 2234.33 | 15-MAR-18:31 | 13.00 | 3.03 | 96833004.11 | 65.03 | 14-MAR-20:40 | 13.00 | 3.03 |
April | 0.353333E+09 | 2621.74 | 19-APR-08:51 | 18.00 | 8.66 | 94030206.55 | 64.74 | 20-APR-20:30 | 14.50 | 7.98 |
May | 0.957876E+09 | 2669.45 | 10-MAY-08:51 | 20.00 | 9.05 | 0.102671E+09 | 76.23 | 16-MAY-21:40 | 16.33 | 9.88 |
June | 0.212495E+10 | 2893.63 | 27-JUN-08:32 | 24.60 | 10.38 | 0.104466E+09 | 82.12 | 29-JUN-21:30 | 20.80 | 11.76 |
July | 0.213421E+10 | 2802.27 | 01-JUL-07:32 | 25.00 | 9.48 | 0.107810E+09 | 82.52 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.198845E+10 | 2830.77 | 08-AUG-08:32 | 23.67 | 14.89 | 0.107306E+09 | 82.09 | 31-AUG-21:10 | 23.70 | 11.86 |
September | 0.137789E+10 | 2674.48 | 18-SEP-08:51 | 22.70 | 10.68 | 0.101925E+09 | 78.46 | 08-SEP-21:19 | 22.70 | 10.68 |
October | 0.391657E+09 | 2599.67 | 11-OCT-08:51 | 20.20 | 7.65 | 97585658.57 | 62.91 | 10-OCT-20:40 | 20.20 | 7.65 |
November | 0.118766E+09 | 2174.65 | 07-NOV-09:02 | 14.00 | 4.09 | 92022752.22 | 56.69 | 30-NOV-05:19 | -12.7 | -13.3 |
December | 42248611.36 | 2091.71 | 02-DEC-09:02 | 11.75 | 4.10 | 93812540.51 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.100269E+11 | 0.117848E+10 | ||||||||
Minimum of Months | 42248611.36 | 2091.71 | 9.17 | 2.67 | 85596504.03 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.213421E+10 | 2893.63 | 25.00 | 14.89 | 0.107810E+09 | 82.52 | 23.70 | 11.86 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300295E+10 | 1862.29 | 20-JAN-13:40 | 21.00 | 6.96 | 0.126629E+10 | 826.76 | 24-JAN-22:40 | 3.00 | 0.25 |
February | 0.233263E+10 | 1912.73 | 18-FEB-13:30 | 20.00 | 7.73 | 0.113959E+10 | 826.78 | 27-FEB-22:40 | 2.00 | -0.8 |
March | 0.314872E+10 | 2025.60 | 15-MAR-10:33 | 15.67 | 4.43 | 0.131047E+10 | 918.61 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.304874E+10 | 1817.59 | 21-APR-10:33 | 13.33 | 5.84 | 0.124615E+10 | 838.55 | 20-APR-21:40 | 13.33 | 5.84 |
May | 0.401288E+10 | 2009.50 | 18-MAY-10:33 | 22.00 | 11.41 | 0.142495E+10 | 913.39 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.484466E+10 | 3338.39 | 26-JUN-18:30 | 36.60 | 14.84 | 0.154041E+10 | 951.90 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.508371E+10 | 2960.47 | 15-JUL-18:30 | 32.50 | 12.97 | 0.160017E+10 | 951.86 | 15-JUL-00:10 | 32.50 | 12.97 |
August | 0.499435E+10 | 2991.70 | 16-AUG-18:13 | 33.00 | 14.57 | 0.160236E+10 | 951.88 | 10-AUG-21:19 | 33.00 | 14.57 |
September | 0.456010E+10 | 2710.55 | 12-SEP-18:04 | 27.33 | 13.46 | 0.151620E+10 | 951.85 | 08-SEP-22:10 | 27.33 | 13.46 |
October | 0.362234E+10 | 2109.58 | 11-OCT-12:50 | 25.83 | 9.40 | 0.139189E+10 | 925.53 | 11-OCT-21:40 | 8.67 | 4.30 |
November | 0.300061E+10 | 1967.76 | 07-NOV-13:30 | 21.00 | 7.19 | 0.124496E+10 | 854.13 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.231444E+10 | 1715.90 | 17-DEC-13:00 | 18.00 | 5.78 | 0.123305E+10 | 797.70 | 04-DEC-23:10 | 18.00 | 5.78 |
Annual Sum or Average | 0.439661E+11 | 0.165165E+11 | ||||||||
Minimum of Months | 0.231444E+10 | 1715.90 | 13.33 | 4.43 | 0.113959E+10 | 797.70 | 2.00 | -0.8 | ||
Maximum of Months | 0.508371E+10 | 3338.39 | 36.60 | 14.84 | 0.160236E+10 | 951.90 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296915E+09 | 2718.60 | 20-JAN-16:02 | 17.00 | 7.18 | 96157782.06 | 56.69 | 06-JAN-04:19 | 17.00 | 7.18 |
February | 0.325069E+09 | 2719.02 | 17-FEB-16:02 | 13.83 | 6.79 | 86649491.72 | 56.69 | 09-FEB-05:19 | 13.83 | 6.79 |
March | 0.652851E+09 | 2837.21 | 13-MAR-15:02 | 23.00 | 6.97 | 96368155.80 | 56.69 | 14-MAR-22:10 | 12.83 | 3.96 |
April | 0.470330E+09 | 2776.41 | 07-APR-15:02 | 21.00 | 7.80 | 93073922.35 | 58.62 | 18-APR-18:10 | 17.17 | 7.62 |
May | 0.110466E+10 | 2757.84 | 09-MAY-15:02 | 21.17 | 8.58 | 98519806.26 | 56.69 | 31-MAY-21:30 | 17.65 | 11.72 |
June | 0.241049E+10 | 2889.54 | 24-JUN-17:03 | 31.42 | 12.74 | 96639344.94 | 58.77 | 26-JUN-18:10 | 37.33 | 15.09 |
July | 0.230734E+10 | 2859.11 | 01-JUL-18:02 | 27.67 | 10.47 | 99397639.23 | 56.70 | 21-JUL-21:00 | 23.00 | 15.78 |
August | 0.233277E+10 | 2894.17 | 16-AUG-15:02 | 36.17 | 16.19 | 99730876.55 | 56.74 | 10-AUG-18:10 | 36.17 | 16.19 |
September | 0.184409E+10 | 2877.23 | 28-SEP-15:02 | 29.50 | 11.04 | 95789808.28 | 56.70 | 27-SEP-04:49 | 29.50 | 11.04 |
October | 0.850162E+09 | 2853.62 | 11-OCT-15:02 | 25.67 | 9.32 | 96959004.00 | 56.69 | 11-OCT-21:40 | 8.67 | 4.30 |
November | 0.415298E+09 | 2790.25 | 05-NOV-15:02 | 20.67 | 6.59 | 93392432.87 | 56.69 | 02-NOV-04:19 | 20.67 | 6.59 |
December | 0.192067E+09 | 2666.80 | 02-DEC-16:01 | 17.33 | 5.85 | 95129191.44 | 56.69 | 20-DEC-05:19 | -19.0 | -19.2 |
Annual Sum or Average | 0.132020E+11 | 0.114781E+10 | ||||||||
Minimum of Months | 0.192067E+09 | 2666.80 | 13.83 | 5.85 | 86649491.72 | 56.69 | -19.0 | -19.2 | ||
Maximum of Months | 0.241049E+10 | 2894.17 | 36.17 | 16.19 | 99730876.55 | 58.77 | 37.33 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49817573.86 | 2544.80 | 23-JAN-16:02 | 18.17 | 6.14 | 94121663.12 | 56.69 | 06-JAN-04:19 | 18.17 | 6.14 |
February | 77197864.45 | 2544.23 | 25-FEB-16:02 | 12.00 | 3.90 | 85170425.09 | 56.69 | 10-FEB-04:19 | 12.00 | 3.90 |
March | 0.271571E+09 | 3048.38 | 08-MAR-17:11 | 14.33 | 3.92 | 97288162.90 | 82.50 | 31-MAR-18:10 | 14.33 | 7.61 |
April | 0.253360E+09 | 3120.21 | 08-APR-18:01 | 13.50 | 4.30 | 94265077.87 | 86.19 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.803851E+09 | 3041.01 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103860E+09 | 89.31 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.214599E+10 | 3043.99 | 18-JUN-21:51 | 18.80 | 12.91 | 0.103849E+09 | 88.62 | 22-JUN-21:10 | 16.18 | 13.70 |
July | 0.199638E+10 | 3030.13 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106764E+09 | 91.78 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.185862E+10 | 2926.35 | 05-AUG-21:51 | 18.00 | 13.60 | 0.106919E+09 | 86.73 | 03-AUG-21:10 | 18.00 | 13.60 |
September | 0.121992E+10 | 2865.96 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102503E+09 | 78.83 | 15-SEP-18:10 | 12.70 | 6.10 |
October | 0.330465E+09 | 2976.83 | 08-OCT-18:11 | 13.33 | 7.54 | 98077536.62 | 65.78 | 05-OCT-18:10 | 13.33 | 7.54 |
November | 89472342.05 | 2607.14 | 07-NOV-16:02 | 20.00 | 7.03 | 91915288.07 | 56.69 | 30-NOV-05:19 | -12.7 | -13.3 |
December | 26762827.39 | 2529.14 | 02-DEC-16:01 | 17.33 | 5.85 | 93587709.10 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.912340E+10 | 0.117832E+10 | ||||||||
Minimum of Months | 26762827.39 | 2529.14 | 12.00 | 3.90 | 85170425.09 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.214599E+10 | 3120.21 | 26.00 | 13.60 | 0.106919E+09 | 91.78 | 18.17 | 13.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.784527E+09 | 1511.09 | 20-JAN-13:15 | 21.00 | 6.97 | 98008007.90 | 56.69 | 20-JAN-22:49 | 7.17 | 1.68 |
February | 0.638476E+09 | 1411.95 | 17-FEB-16:02 | 13.83 | 6.79 | 88038188.01 | 56.69 | 21-FEB-22:19 | 2.33 | 2.33 |
March | 0.676239E+09 | 1466.05 | 13-MAR-15:02 | 23.00 | 6.97 | 97211941.13 | 56.69 | 15-MAR-22:49 | 11.17 | 2.61 |
April | 0.370664E+09 | 1406.44 | 07-APR-15:02 | 21.00 | 7.80 | 93634885.09 | 56.69 | 07-APR-21:30 | 11.50 | 6.33 |
May | 0.658183E+09 | 1396.79 | 04-MAY-15:02 | 24.83 | 10.09 | 98539753.16 | 56.69 | 15-MAY-21:30 | 13.50 | 9.22 |
June | 0.121008E+10 | 1404.06 | 14-JUN-15:02 | 36.00 | 13.52 | 96012571.69 | 56.70 | 19-JUN-21:00 | 17.70 | 14.11 |
July | 0.129265E+10 | 1403.16 | 01-JUL-08:61 | 26.00 | 9.47 | 99150123.83 | 56.70 | 25-JUL-21:49 | 20.00 | 15.92 |
August | 0.141847E+10 | 1429.78 | 17-AUG-15:02 | 31.00 | 12.21 | 99286899.02 | 56.70 | 26-AUG-00:20 | 21.67 | 15.93 |
September | 0.134435E+10 | 1469.52 | 28-SEP-15:02 | 29.50 | 11.04 | 95979074.57 | 56.70 | 08-SEP-21:49 | 29.50 | 11.04 |
October | 0.936573E+09 | 1486.88 | 08-OCT-12:35 | 21.00 | 8.62 | 97736028.57 | 56.69 | 10-OCT-21:49 | 13.17 | 4.31 |
November | 0.818970E+09 | 1536.69 | 16-NOV-13:33 | 16.00 | 6.40 | 94997999.75 | 56.69 | 06-NOV-22:49 | 16.00 | 6.40 |
December | 0.578953E+09 | 1400.91 | 17-DEC-16:01 | 15.50 | 4.73 | 97256285.87 | 56.69 | 01-DEC-22:40 | 15.50 | 4.73 |
Annual Sum or Average | 0.107281E+11 | 0.115585E+10 | ||||||||
Minimum of Months | 0.370664E+09 | 1396.79 | 13.83 | 4.73 | 88038188.01 | 56.69 | 2.33 | 1.68 | ||
Maximum of Months | 0.141847E+10 | 1536.69 | 36.00 | 13.52 | 99286899.02 | 56.70 | 29.50 | 15.93 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303994E+11 | 18407.72 | 20-JAN-22:10 | 7.83 | 2.00 | 0.191001E+11 | 11347.48 | 06-JAN-04:19 | 7.83 | 2.00 |
February | 0.272373E+11 | 18109.60 | 27-FEB-22:10 | 2.00 | -0.8 | 0.172534E+11 | 11347.50 | 07-FEB-04:19 | 2.00 | -0.8 |
March | 0.328892E+11 | 20271.98 | 14-MAR-21:03 | 13.00 | 3.83 | 0.192676E+11 | 11348.61 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.325286E+11 | 20364.20 | 20-APR-21:10 | 14.00 | 7.96 | 0.186332E+11 | 11347.63 | 13-APR-04:19 | 14.00 | 7.96 |
May | 0.386768E+11 | 21503.09 | 31-MAY-21:10 | 17.88 | 12.24 | 0.193421E+11 | 11348.90 | 15-MAY-21:40 | 17.88 | 12.24 |
June | 0.426779E+11 | 23375.69 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187619E+11 | 11397.89 | 29-JUN-21:19 | 20.70 | 11.71 |
July | 0.439896E+11 | 23238.37 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193107E+11 | 11395.95 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.432296E+11 | 23130.94 | 16-AUG-21:50 | 24.33 | 13.24 | 0.193919E+11 | 11471.38 | 16-AUG-21:49 | 24.33 | 13.24 |
September | 0.394125E+11 | 22232.50 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187073E+11 | 11383.37 | 12-SEP-21:19 | 22.57 | 12.63 |
October | 0.342280E+11 | 20339.43 | 10-OCT-21:10 | 13.83 | 4.11 | 0.192221E+11 | 11347.62 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.305123E+11 | 19275.00 | 09-NOV-23:00 | 8.00 | 6.87 | 0.185313E+11 | 11347.58 | 06-NOV-05:19 | 8.00 | 6.87 |
December | 0.291485E+11 | 18419.40 | 04-DEC-23:00 | 8.00 | 0.89 | 0.189464E+11 | 11347.53 | 19-DEC-04:19 | -16.1 | -16.3 |
Annual Sum or Average | 0.424930E+12 | 0.226468E+12 | ||||||||
Minimum of Months | 0.272373E+11 | 18109.60 | 2.00 | -0.8 | 0.172534E+11 | 11347.48 | -16.1 | -16.3 | ||
Maximum of Months | 0.439896E+11 | 23375.69 | 28.00 | 13.33 | 0.193919E+11 | 11471.38 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340309E+11 | 20054.82 | 20-JAN-22:10 | 7.83 | 2.00 | 0.192188E+11 | 11347.56 | 06-JAN-04:19 | 7.83 | 2.00 |
February | 0.305185E+11 | 19718.29 | 27-FEB-22:10 | 2.00 | -0.8 | 0.173623E+11 | 11347.51 | 07-FEB-04:19 | 2.00 | -0.8 |
March | 0.365637E+11 | 21597.51 | 14-MAR-21:03 | 13.00 | 3.83 | 0.193489E+11 | 11348.62 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.362485E+11 | 21865.52 | 20-APR-21:10 | 14.00 | 7.96 | 0.186918E+11 | 11347.72 | 13-APR-04:19 | 14.00 | 7.96 |
May | 0.421908E+11 | 22816.07 | 31-MAY-21:10 | 17.88 | 12.24 | 0.193495E+11 | 11348.90 | 15-MAY-21:40 | 17.88 | 12.24 |
June | 0.454892E+11 | 24571.78 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187625E+11 | 11414.15 | 06-JUN-21:19 | 27.53 | 11.08 |
July | 0.468506E+11 | 24483.34 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193112E+11 | 11411.57 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.460892E+11 | 24283.36 | 16-AUG-21:50 | 24.33 | 13.24 | 0.193925E+11 | 11485.54 | 16-AUG-21:49 | 24.33 | 13.24 |
September | 0.422979E+11 | 23416.01 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187102E+11 | 11399.96 | 08-SEP-21:19 | 22.57 | 12.63 |
October | 0.376456E+11 | 21633.77 | 10-OCT-21:10 | 13.83 | 4.11 | 0.192744E+11 | 11347.69 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.340217E+11 | 20722.02 | 09-NOV-22:10 | 8.00 | 6.42 | 0.186120E+11 | 11347.67 | 06-NOV-05:19 | 8.00 | 6.42 |
December | 0.327142E+11 | 20086.74 | 04-DEC-23:00 | 8.00 | 0.89 | 0.191140E+11 | 11347.54 | 19-DEC-04:19 | -16.1 | -16.3 |
Annual Sum or Average | 0.464661E+12 | 0.227148E+12 | ||||||||
Minimum of Months | 0.305185E+11 | 19718.29 | 2.00 | -0.8 | 0.173623E+11 | 11347.51 | -16.1 | -16.3 | ||
Maximum of Months | 0.468506E+11 | 24571.78 | 28.00 | 13.33 | 0.193925E+11 | 11485.54 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497151E+11 | 28578.14 | 20-JAN-11:40 | 19.33 | 7.26 | 0.188454E+11 | 11319.56 | 07-JAN-18:19 | 19.33 | 7.26 |
February | 0.447697E+11 | 29032.85 | 18-FEB-11:40 | 17.67 | 6.73 | 0.170188E+11 | 11319.68 | 25-FEB-18:19 | 7.67 | 3.07 |
March | 0.513801E+11 | 30166.59 | 14-MAR-10:33 | 21.00 | 7.01 | 0.188599E+11 | 11319.60 | 04-MAR-18:19 | 21.00 | 7.01 |
April | 0.499777E+11 | 29867.93 | 20-APR-10:33 | 19.33 | 8.37 | 0.182497E+11 | 11319.65 | 08-APR-17:19 | 19.33 | 8.37 |
May | 0.550233E+11 | 30463.19 | 16-MAY-10:33 | 24.67 | 11.32 | 0.188687E+11 | 11319.64 | 06-MAY-17:19 | 24.67 | 11.32 |
June | 0.568776E+11 | 31337.99 | 26-JUN-10:40 | 32.70 | 15.62 | 0.182669E+11 | 11319.64 | 17-JUN-17:19 | 32.70 | 15.62 |
July | 0.585553E+11 | 31547.31 | 23-JUL-10:50 | 29.83 | 15.95 | 0.188697E+11 | 11319.64 | 22-JUL-17:19 | 29.83 | 15.95 |
August | 0.584140E+11 | 31631.81 | 05-AUG-10:50 | 29.50 | 17.78 | 0.188760E+11 | 11319.65 | 05-AUG-17:19 | 21.33 | 16.54 |
September | 0.547659E+11 | 31076.42 | 04-SEP-10:40 | 26.83 | 13.23 | 0.182607E+11 | 11319.64 | 16-SEP-17:19 | 21.97 | 10.13 |
October | 0.520233E+11 | 30142.43 | 07-OCT-10:33 | 20.33 | 9.02 | 0.188584E+11 | 11319.68 | 21-OCT-17:10 | 11.67 | 4.94 |
November | 0.487354E+11 | 29355.55 | 05-NOV-10:40 | 18.00 | 5.62 | 0.182396E+11 | 11319.51 | 04-NOV-17:19 | 18.00 | 5.62 |
December | 0.482838E+11 | 28316.92 | 02-DEC-11:50 | 19.50 | 6.90 | 0.188355E+11 | 11319.67 | 23-DEC-18:19 | -17.0 | -17.3 |
Annual Sum or Average | 0.628521E+12 | 0.222049E+12 | ||||||||
Minimum of Months | 0.447697E+11 | 28316.92 | 17.67 | 5.62 | 0.170188E+11 | 11319.51 | -17.0 | -17.3 | ||
Maximum of Months | 0.585553E+11 | 31631.81 | 32.70 | 17.78 | 0.188760E+11 | 11319.68 | 32.70 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517137E+10 | 4243.22 | 20-JAN-13:40 | 21.00 | 6.96 | 0.131048E+10 | 857.30 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.419283E+10 | 4291.20 | 18-FEB-13:30 | 20.00 | 7.73 | 0.118752E+10 | 839.46 | 27-FEB-22:30 | 2.00 | -0.8 |
March | 0.579511E+10 | 4921.08 | 15-MAR-14:10 | 20.83 | 6.19 | 0.136794E+10 | 956.44 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.589713E+10 | 4026.79 | 21-APR-10:33 | 13.33 | 5.84 | 0.131201E+10 | 911.16 | 20-APR-21:40 | 13.33 | 5.84 |
May | 0.838831E+10 | 4355.05 | 18-MAY-10:33 | 22.00 | 11.41 | 0.150257E+10 | 974.29 | 17-MAY-21:30 | 22.00 | 11.41 |
June | 0.106972E+11 | 7018.18 | 26-JUN-14:10 | 37.98 | 15.29 | 0.162008E+10 | 1007.48 | 07-JUN-21:10 | 37.98 | 15.29 |
July | 0.110904E+11 | 6962.87 | 23-JUL-13:00 | 34.00 | 16.01 | 0.167355E+10 | 1007.41 | 14-JUL-23:40 | 34.00 | 16.01 |
August | 0.110094E+11 | 7268.13 | 16-AUG-15:02 | 36.17 | 16.19 | 0.167239E+10 | 1007.45 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.959902E+10 | 6864.72 | 09-SEP-12:50 | 32.62 | 13.01 | 0.156341E+10 | 1007.41 | 08-SEP-21:00 | 32.62 | 13.01 |
October | 0.689784E+10 | 5084.96 | 11-OCT-14:10 | 26.83 | 9.68 | 0.142436E+10 | 963.40 | 10-OCT-21:30 | 26.83 | 9.68 |
November | 0.554916E+10 | 4440.19 | 07-NOV-13:30 | 21.00 | 7.19 | 0.129331E+10 | 890.47 | 09-NOV-22:30 | 8.00 | 6.60 |
December | 0.404633E+10 | 3763.53 | 03-DEC-13:00 | 17.20 | 6.28 | 0.129521E+10 | 830.09 | 04-DEC-22:40 | 7.67 | 0.83 |
Annual Sum or Average | 0.883342E+11 | 0.172228E+11 | ||||||||
Minimum of Months | 0.404633E+10 | 3763.53 | 13.33 | 5.84 | 0.118752E+10 | 830.09 | 2.00 | -0.8 | ||
Maximum of Months | 0.110904E+11 | 7268.13 | 37.98 | 16.19 | 0.167355E+10 | 1007.48 | 37.98 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148463E+09 | 1454.58 | 05-JAN-09:04 | -17.0 |
February | 0.319371E+09 | 1222.11 | 05-FEB-17:00 | -7.0 |
March | 0.183123E+09 | 1379.55 | 19-MAR-08:06 | -13.0 |
April | 0.130658E+09 | 829.44 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.187961E+09 | 1142.55 | 31-OCT-15:00 | -8.0 |
November | 0.140341E+09 | 1092.78 | 30-NOV-07:05 | -11.3 |
December | 0.478818E+09 | 1858.78 | 21-DEC-08:10 | -20.0 |
Annual Sum or Average | 0.158873E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.478818E+09 | 1858.78 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28786458.67 | 433.01 | 05-JAN-13:50 | -16.0 |
February | 46264159.76 | 324.05 | 06-FEB-14:00 | -3.0 |
March | 2010947.31 | 132.84 | 19-MAR-14:50 | 0.00 |
April | 618171.34 | 64.25 | 03-APR-11:30 | -1.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 11008559.04 | 278.65 | 31-OCT-14:00 | -7.0 |
November | 11624945.69 | 285.00 | 30-NOV-05:00 | -13.0 |
December | 0.224724E+09 | 873.32 | 22-DEC-05:00 | -21.0 |
Annual Sum or Average | 0.325037E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.224724E+09 | 873.32 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47621123.12 | 431.27 | 05-JAN-18:00 | -18.0 |
February | 85311282.22 | 336.15 | 06-FEB-18:00 | -7.0 |
March | 14521502.64 | 197.69 | 19-MAR-09:00 | -13.3 |
April | 7972392.87 | 141.71 | 03-APR-09:30 | -3.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 23370299.30 | 319.41 | 31-OCT-15:00 | -8.0 |
November | 33729409.33 | 282.40 | 30-NOV-05:00 | -13.0 |
December | 0.229266E+09 | 670.47 | 21-DEC-18:02 | -21.7 |
Annual Sum or Average | 0.441792E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.229266E+09 | 670.47 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2232838.86 | 1135.54 | 05-JAN-09:10 | -17.0 |
February | 12263414.89 | 759.26 | 05-FEB-16:00 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 9898873.75 | 680.11 | 31-OCT-14:00 | -7.0 |
November | 7923.02 | 21.71 | 29-NOV-09:03 | -9.0 |
December | 52527881.17 | 3034.63 | 21-DEC-09:25 | -20.0 |
Annual Sum or Average | 76930931.70 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 52527881.17 | 3034.63 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541866E+09 | 1823.25 | 05-JAN-09:13 | -17.0 |
February | 0.647094E+09 | 1818.03 | 05-FEB-16:13 | -6.3 |
March | 0.487497E+09 | 1773.91 | 19-MAR-08:62 | -13.0 |
April | 0.390810E+09 | 1759.90 | 03-APR-08:62 | -4.8 |
May | 30631298.72 | 1624.85 | 02-MAY-08:62 | 3.35 |
June | 425842.93 | 500.84 | 21-JUN-08:05 | 19.68 |
July | 346792.23 | 448.13 | 03-JUL-08:05 | 13.33 |
August | 631504.16 | 544.17 | 24-AUG-08:05 | 15.00 |
September | 11666992.11 | 1661.27 | 22-SEP-08:62 | 2.57 |
October | 0.341388E+09 | 1824.72 | 31-OCT-15:13 | -8.0 |
November | 0.459897E+09 | 1787.10 | 28-NOV-16:13 | -7.3 |
December | 0.961474E+09 | 1878.22 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.387373E+10 | |||
Minimum of Months | 346792.23 | 448.13 | -20.0 | |
Maximum of Months | 0.961474E+09 | 1878.22 | 19.68 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.894297E+09 | 1823.55 | 05-JAN-19:13 | -18.3 |
February | 0.907596E+09 | 1812.47 | 05-FEB-16:13 | -6.3 |
March | 0.593883E+09 | 1767.44 | 19-MAR-08:62 | -13.0 |
April | 0.425291E+09 | 1753.38 | 02-APR-15:02 | -4.0 |
May | 33138701.26 | 1623.60 | 02-MAY-08:62 | 3.35 |
June | 60986.27 | 260.70 | 06-JUN-08:26 | 26.10 |
July | 54033.18 | 307.05 | 03-JUL-08:05 | 13.33 |
August | 236489.57 | 558.89 | 24-AUG-08:05 | 15.00 |
September | 13875814.46 | 1660.27 | 22-SEP-08:62 | 2.57 |
October | 0.403267E+09 | 1817.07 | 31-OCT-15:13 | -8.0 |
November | 0.698244E+09 | 1793.35 | 28-NOV-16:13 | -7.3 |
December | 0.133314E+10 | 1870.25 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.530309E+10 | |||
Minimum of Months | 54033.18 | 260.70 | -18.3 | |
Maximum of Months | 0.133314E+10 | 1870.25 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129494E+09 | 527.61 | 05-JAN-16:02 | -15.2 |
February | 0.145364E+09 | 524.23 | 12-FEB-16:02 | -6.2 |
March | 52754838.99 | 509.97 | 04-MAR-16:02 | -9.0 |
April | 22656166.63 | 502.13 | 02-APR-15:02 | -4.0 |
May | 142476.55 | 276.01 | 02-MAY-08:04 | 3.35 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 101636.42 | 295.47 | 22-SEP-08:03 | 2.57 |
October | 34779974.67 | 517.62 | 31-OCT-15:02 | -8.0 |
November | 81063289.39 | 522.32 | 29-NOV-16:02 | -9.3 |
December | 0.218849E+09 | 533.73 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.685205E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.218849E+09 | 533.73 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572719E+09 | 1768.35 | 05-JAN-19:13 | -18.3 |
February | 0.681374E+09 | 1760.88 | 05-FEB-16:13 | -6.3 |
March | 0.479686E+09 | 1727.14 | 19-MAR-08:62 | -13.0 |
April | 0.378729E+09 | 1714.98 | 02-APR-15:02 | -4.0 |
May | 28890551.13 | 703.39 | 02-MAY-18:03 | 6.83 |
June | 29248.31 | 292.48 | 17-JUN-08:05 | 17.28 |
July | 21906.61 | 182.56 | 28-JUL-08:06 | 18.00 |
August | 37757.78 | 316.12 | 27-AUG-08:05 | 17.17 |
September | 10355207.31 | 1112.16 | 22-SEP-08:62 | 2.57 |
October | 0.344562E+09 | 1764.81 | 31-OCT-15:13 | -8.0 |
November | 0.490203E+09 | 1735.22 | 28-NOV-16:02 | -7.2 |
December | 0.977850E+09 | 1814.13 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.396446E+10 | |||
Minimum of Months | 21906.61 | 182.56 | -20.0 | |
Maximum of Months | 0.977850E+09 | 1814.13 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.924182E+09 | 1782.47 | 05-JAN-16:13 | -15.3 |
February | 0.933048E+09 | 1754.47 | 05-FEB-16:13 | -6.3 |
March | 0.574761E+09 | 1720.06 | 19-MAR-08:62 | -13.0 |
April | 0.418338E+09 | 1707.72 | 02-APR-15:02 | -4.0 |
May | 31094800.17 | 635.91 | 03-MAY-15:05 | 16.17 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 1294.23 | 15.10 | 22-AUG-20:36 | 15.00 |
September | 12803853.04 | 1320.06 | 22-SEP-08:62 | 2.57 |
October | 0.411341E+09 | 1756.52 | 31-OCT-15:13 | -8.0 |
November | 0.742082E+09 | 1749.14 | 29-NOV-16:13 | -9.7 |
December | 0.134038E+10 | 1818.01 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.538803E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.134038E+10 | 1818.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16974216.89 | 734.78 | 05-JAN-09:04 | -17.0 |
February | 72755447.03 | 847.93 | 05-FEB-16:00 | -6.0 |
March | 260372.62 | 52.81 | 19-MAR-15:00 | 0.00 |
April | 3114135.85 | 290.85 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 37252969.51 | 808.32 | 31-OCT-14:00 | -7.0 |
November | 15692092.06 | 553.30 | 29-NOV-09:03 | -9.0 |
December | 0.153429E+09 | 1343.01 | 21-DEC-09:30 | -20.0 |
Annual Sum or Average | 0.299478E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.153429E+09 | 1343.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.899387E+09 | 2184.96 | 05-JAN-09:13 | -17.0 |
February | 0.984623E+09 | 2172.44 | 05-FEB-16:13 | -6.3 |
March | 0.763944E+09 | 2116.14 | 19-MAR-08:15 | -13.0 |
April | 0.628158E+09 | 2086.64 | 02-APR-15:02 | -4.0 |
May | 75954734.42 | 1926.70 | 02-MAY-08:62 | 3.35 |
June | 611556.59 | 452.99 | 24-JUN-08:05 | 22.25 |
July | 440396.24 | 423.08 | 21-JUL-08:05 | 23.17 |
August | 841396.05 | 456.42 | 15-AUG-08:05 | 14.17 |
September | 31478635.64 | 1992.15 | 22-SEP-08:62 | 2.57 |
October | 0.573286E+09 | 2179.00 | 31-OCT-15:13 | -8.0 |
November | 0.755103E+09 | 2141.98 | 28-NOV-16:13 | -7.3 |
December | 0.142006E+10 | 2237.79 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.613389E+10 | |||
Minimum of Months | 440396.24 | 423.08 | -20.0 | |
Maximum of Months | 0.142006E+10 | 2237.79 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137411E+10 | 2185.58 | 05-JAN-19:13 | -18.3 |
February | 0.132879E+10 | 2162.67 | 05-FEB-16:13 | -6.3 |
March | 0.909203E+09 | 2106.85 | 19-MAR-08:15 | -13.0 |
April | 0.673245E+09 | 2077.23 | 02-APR-15:02 | -4.0 |
May | 74454092.47 | 1933.66 | 03-MAY-08:62 | 6.33 |
June | 106807.88 | 439.25 | 16-JUN-08:05 | 15.78 |
July | 113185.34 | 396.68 | 03-JUL-08:05 | 13.33 |
August | 293058.10 | 474.93 | 15-AUG-08:05 | 14.17 |
September | 35820868.28 | 1988.59 | 22-SEP-08:62 | 2.57 |
October | 0.682977E+09 | 2167.22 | 31-OCT-15:13 | -8.0 |
November | 0.109704E+10 | 2144.27 | 28-NOV-16:13 | -7.3 |
December | 0.189212E+10 | 2227.29 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.806828E+10 | |||
Minimum of Months | 106807.88 | 396.68 | -18.3 | |
Maximum of Months | 0.189212E+10 | 2227.29 | 15.78 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180751E+09 | 1116.30 | 05-JAN-09:13 | -17.0 |
February | 0.282325E+09 | 1123.55 | 05-FEB-16:13 | -6.3 |
March | 0.248024E+09 | 1093.85 | 19-MAR-15:02 | 0.00 |
April | 0.214934E+09 | 1085.55 | 02-APR-15:02 | -4.0 |
May | 17949165.11 | 865.60 | 02-MAY-08:62 | 3.35 |
June | 262030.31 | 201.97 | 21-JUN-08:05 | 19.68 |
July | 74829.37 | 189.32 | 03-JUL-08:05 | 13.33 |
August | 92995.07 | 180.37 | 02-AUG-08:05 | 20.00 |
September | 5815413.74 | 973.08 | 22-SEP-08:62 | 2.57 |
October | 0.179636E+09 | 1127.53 | 31-OCT-15:13 | -8.0 |
November | 0.174749E+09 | 1098.16 | 28-NOV-16:13 | -7.3 |
December | 0.377398E+09 | 1148.25 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.168201E+10 | |||
Minimum of Months | 74829.37 | 180.37 | -17.3 | |
Maximum of Months | 0.377398E+09 | 1148.25 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255659E+09 | 2521.83 | 05-JAN-09:06 | -17.0 |
February | 0.365373E+09 | 2293.47 | 12-FEB-05:40 | -19.3 |
March | 67784293.25 | 1317.61 | 05-MAR-06:00 | -12.0 |
April | 30662501.90 | 903.88 | 03-APR-06:10 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.138826E+09 | 1539.11 | 31-OCT-14:00 | -7.0 |
November | 0.149888E+09 | 1897.69 | 30-NOV-07:10 | -11.3 |
December | 0.986815E+09 | 3817.18 | 23-DEC-07:20 | -22.2 |
Annual Sum or Average | 0.199501E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.986815E+09 | 3817.18 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133720E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.117038E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122572E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.111406E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.104558E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.955454E+09 | 1701.53 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.100549E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.110602E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.114071E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.129645E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.128057E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.134932E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.140270E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.955454E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.134932E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.944630E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.849836E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.938141E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.898075E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.920653E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.887437E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.913916E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.927475E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.900291E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.941533E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.914999E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.943694E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109807E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.849836E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.944630E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280433E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247269E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265069E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247185E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244435E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.229353E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.238660E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250716E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.251260E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271903E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268606E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279887E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.307478E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.229353E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280433E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280433E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247269E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265069E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247185E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244435E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.229353E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.238660E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250716E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.251260E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271903E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268606E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279887E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.307478E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.229353E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280433E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587448E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561116E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472159E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413148E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3230216.87 | 0.230795E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47091437.91 | 79378622.87 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50021083.89 | 69925544.15 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39845815.26 | 85431198.24 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19549844.36 | 0.142697E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395884.89 | 0.417836E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509964E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645051E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160134E+09 | 0.421495E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69925544.15 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50021083.89 | 0.645051E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237226E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224355E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.77 | 0.191994E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171606E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1375322.82 | 0.102536E+09 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18232942.11 | 36278554.09 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19354115.58 | 32527313.16 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15602365.84 | 38561687.12 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7728400.28 | 61592382.67 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176505.39 | 0.171819E+09 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206675E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258005E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62471550.79 | 0.173318E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32527313.16 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19354115.58 | 0.258005E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524461E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499591E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59419.53 | 0.424725E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807.52 | 0.380537E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4069084.40 | 0.229543E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43018640.76 | 84549750.20 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45239686.90 | 76154336.29 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37106771.11 | 89744278.07 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19239044.17 | 0.140071E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 684828.30 | 0.383516E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456908E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15543.88 | 0.579459E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149434E+09 | 0.386926E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76154336.29 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45239686.90 | 0.579459E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299822E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286370E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41964.73 | 0.242208E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.75 | 0.216347E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2484708.86 | 0.128614E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25224517.45 | 47413182.46 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26412385.97 | 42793790.55 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21845518.05 | 50144553.63 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11442707.32 | 78208592.36 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 421565.83 | 0.217458E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260457E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7362.72 | 0.332180E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87881803.67 | 0.220202E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42793790.55 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26412385.97 | 0.332180E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785587E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747611E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 22781.70 | 0.641276E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577377E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3687505.98 | 0.335839E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 59169075.39 | 0.110830E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 63090557.70 | 98641774.48 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 51094650.06 | 0.117482E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 26151633.76 | 0.193618E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 851626.93 | 0.564884E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683794E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864513E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.204068E+09 | 0.572145E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98641774.48 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 63090557.70 | 0.864513E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.133720E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137188E+10 |
February | 0.236489E+11 | 0.117038E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129885E+10 |
March | 0.262800E+11 | 0.122572E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110373E+10 |
April | 0.253579E+11 | 0.111406E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978842E+09 |
May | 0.262123E+11 | 0.104558E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6246170.45 | 0.585480E+09 |
June | 0.254132E+11 | 0.955454E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103303E+09 | 0.204476E+09 |
July | 0.261570E+11 | 0.100549E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110000E+09 | 0.183296E+09 |
August | 0.262677E+11 | 0.110602E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87463539.27 | 0.217925E+09 |
September | 0.253456E+11 | 0.114071E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43115191.57 | 0.350783E+09 |
October | 0.261693E+11 | 0.129645E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876794.77 | 0.982715E+09 |
November | 0.253025E+11 | 0.128057E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119346E+10 |
December | 0.261570E+11 | 0.134932E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149163E+10 |
Annual Sum or Average | 0.308468E+12 | 0.140270E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351005E+09 | 0.996307E+10 |
Minimum of Months | 0.236489E+11 | 0.955454E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183296E+09 |
Maximum of Months | 0.262800E+11 | 0.134932E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110000E+09 | 0.149163E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.944630E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397552E+10 |
February | 0.702046E+11 | 0.849836E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375782E+10 |
March | 0.780153E+11 | 0.938141E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321411E+10 |
April | 0.752779E+11 | 0.898075E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287540E+10 |
May | 0.778146E+11 | 0.920653E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20243432.87 | 0.171197E+10 |
June | 0.754422E+11 | 0.887437E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297758E+09 | 0.594005E+09 |
July | 0.776503E+11 | 0.913916E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315739E+09 | 0.533245E+09 |
August | 0.779788E+11 | 0.927475E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251881E+09 | 0.632188E+09 |
September | 0.752414E+11 | 0.900291E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124095E+09 | 0.101637E+10 |
October | 0.776868E+11 | 0.941533E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2503790.85 | 0.286387E+10 |
November | 0.751137E+11 | 0.914999E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346331E+10 |
December | 0.776503E+11 | 0.943694E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432405E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109807E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101222E+10 | 0.289619E+11 |
Minimum of Months | 0.702046E+11 | 0.849836E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533245E+09 |
Maximum of Months | 0.780153E+11 | 0.944630E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315739E+09 | 0.432405E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331554E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316281E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80362.47 | 0.263676E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234470E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3199990.21 | 0.127725E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36210025.39 | 33287325.48 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39243257.41 | 27342177.68 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31628276.19 | 34582761.98 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16730029.75 | 66647411.20 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 550734.58 | 0.229624E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285606E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365507E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127643E+09 | 0.231630E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27342177.68 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39243257.41 | 0.365507E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324982E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311164E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15968.06 | 0.262872E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234707E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2926580.67 | 0.133502E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34276793.65 | 40399521.53 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37319107.10 | 35292605.34 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30234088.87 | 42366359.96 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15865617.79 | 74044776.80 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 527853.68 | 0.229757E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280878E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360316E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121166E+09 | 0.233028E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35292605.34 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37319107.10 | 0.360316E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112873E+09 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101689E+09 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87757562.34 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80962689.01 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64420.51 | 55342746.75 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4055526.02 | 23042169.98 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4212520.53 | 21497455.69 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3157924.58 | 24580004.52 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1211249.70 | 35361868.80 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485.59 | 82910440.02 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97757647.26 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114937E+09 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12702126.93 | 0.838711E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21497455.69 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4212520.53 | 0.114937E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90871845.87 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86951827.64 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22849.74 | 73112764.24 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65517130.21 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 883711.17 | 36344728.21 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9803882.92 | 10604247.90 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10472010.41 | 9193846.87 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8701061.25 | 10988126.79 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4615158.10 | 19620488.08 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191258.35 | 63569788.07 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3578.34 | 78379996.87 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7120.05 | 0.100912E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34700630.33 | 0.646067E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9193846.87 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10472010.41 | 0.100912E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332054E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316957E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96084.91 | 0.264872E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235846E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3190278.72 | 0.128636E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36446669.84 | 33701578.58 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38866066.83 | 27545922.58 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31811019.04 | 35020656.52 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16767703.76 | 67239592.75 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 583481.92 | 0.230326E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285764E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365721E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127761E+09 | 0.232368E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27545922.58 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38866066.83 | 0.365721E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324322E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311476E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17152.24 | 0.263247E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235624E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2846427.77 | 0.133575E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34191063.09 | 43404338.19 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36480524.54 | 37527643.35 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30067827.70 | 44796126.97 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15681009.07 | 74286237.94 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526487.79 | 0.229696E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280056E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12160.24 | 0.359595E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119823E+09 | 0.233761E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37527643.35 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36480524.54 | 0.359595E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403988E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385836E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9070.75 | 0.327721E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 | 0.289830E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3336870.89 | 0.171798E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33185705.87 | 63999028.45 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34640482.51 | 58189849.43 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28049573.42 | 68755411.72 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14161283.05 | 0.108099E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387943.88 | 0.296295E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350873E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3512.77 | 0.444177E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113775E+09 | 0.296956E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58189849.43 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34640482.51 | 0.444177E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331313E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316358E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68772.43 | 0.263814E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234589E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3087954.27 | 0.128277E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35574542.52 | 33675951.91 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38671451.60 | 27711106.61 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31042567.82 | 34978968.48 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16415588.23 | 66985612.76 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 519377.77 | 0.229821E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285648E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365230E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125380E+09 | 0.231840E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27711106.61 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38671451.60 | 0.365230E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324357E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311104E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14196.94 | 0.263215E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235184E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2824777.78 | 0.134764E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33693739.76 | 40856490.46 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36834326.34 | 35573749.50 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29717850.11 | 42738819.42 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15639491.11 | 74384157.25 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 514446.06 | 0.230033E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280647E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359996E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119239E+09 | 0.233285E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35573749.50 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36834326.34 | 0.359996E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171992E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163797E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29431.56 | 0.136287E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121030E+09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602228.12 | 65806694.65 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18661516.28 | 17204038.82 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19968904.23 | 14167779.33 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16201623.90 | 17901369.54 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8359257.57 | 34498363.73 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 239944.39 | 0.118602E+09 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148457E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190062E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65062906.05 | 0.119981E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14167779.33 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19968904.23 | 0.190062E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905636E+09 |
February | 0.415303E+11 | 0.247269E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861651E+09 |
March | 0.461508E+11 | 0.265069E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744279E+09 |
April | 0.445315E+11 | 0.247185E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672286E+09 |
May | 0.460320E+11 | 0.244435E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3542345.91 | 0.398211E+09 |
June | 0.446286E+11 | 0.229353E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63678754.73 | 0.137062E+09 |
July | 0.459349E+11 | 0.238660E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67753648.32 | 0.122949E+09 |
August | 0.461292E+11 | 0.250716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54462145.13 | 0.145587E+09 |
September | 0.445099E+11 | 0.251260E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26835289.15 | 0.232537E+09 |
October | 0.459565E+11 | 0.271903E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 560285.33 | 0.657461E+09 |
November | 0.444343E+11 | 0.268606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791189E+09 |
December | 0.459349E+11 | 0.279887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992331E+09 |
Annual Sum or Average | 0.541708E+12 | 0.307478E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216832E+09 | 0.666118E+10 |
Minimum of Months | 0.415303E+11 | 0.229353E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122949E+09 |
Maximum of Months | 0.461508E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67753648.32 | 0.992331E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910848E+09 |
February | 0.415303E+11 | 0.247269E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866490E+09 |
March | 0.461508E+11 | 0.265069E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748078E+09 |
April | 0.445315E+11 | 0.247185E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675188E+09 |
May | 0.460320E+11 | 0.244435E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3538225.10 | 0.398632E+09 |
June | 0.446286E+11 | 0.229353E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63674777.70 | 0.137070E+09 |
July | 0.459349E+11 | 0.238660E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67750107.54 | 0.122958E+09 |
August | 0.461292E+11 | 0.250716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54454474.58 | 0.145600E+09 |
September | 0.445099E+11 | 0.251260E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26817492.34 | 0.232677E+09 |
October | 0.459565E+11 | 0.271903E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 528181.64 | 0.660076E+09 |
November | 0.444343E+11 | 0.268606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795087E+09 |
December | 0.459349E+11 | 0.279887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998840E+09 |
Annual Sum or Average | 0.541708E+12 | 0.307478E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216763E+09 | 0.669154E+10 |
Minimum of Months | 0.415303E+11 | 0.229353E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122958E+09 |
Maximum of Months | 0.461508E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67750107.54 | 0.998840E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815966E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775994E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669456E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603733E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3184033.90 | 0.356362E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 57004331.06 | 0.122670E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60530946.22 | 0.110036E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48762783.35 | 0.130293E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24055722.02 | 0.208116E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 468945.68 | 0.591442E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712115E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896805E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.194007E+09 | 0.599299E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110036E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60530946.22 | 0.896805E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712562E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682588E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580098E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515254E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4012920.88 | 0.305823E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56167118.06 | 0.112353E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59697766.90 | 0.100712E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48026796.00 | 0.118883E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23873648.01 | 0.185352E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474570.60 | 0.517867E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620027E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787551E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192253E+09 | 0.523907E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100712E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59697766.90 | 0.787551E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 439.29 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 458.75 | 12-FEB-05:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 400.63 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 311.36 | 17-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 17-MAY-13:00 | 229.12 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 26-JUN-15:00 | 155.55 | 09-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 | 16-JUL-13:00 | 131.20 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.11 | 16-AUG-16:00 | 119.65 | 12-AUG-23:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 | 09-SEP-13:00 | 238.74 | 22-SEP-05:30 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 11-OCT-14:00 | 334.19 | 30-OCT-06:40 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 392.16 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 494.59 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.65 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 494.59 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 171.20 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 181.00 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 14-MAR-13:00 | 157.85 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 123.89 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 17-MAY-13:00 | 96.22 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 | 26-JUN-15:00 | 68.56 | 09-JUN-04:10 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.75 | 16-JUL-13:00 | 58.44 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 16-AUG-16:00 | 50.57 | 12-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 10-SEP-13:00 | 101.12 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 11-OCT-14:00 | 133.45 | 30-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 157.39 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 191.58 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.57 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 | 191.58 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 400.73 | 05-JAN-19:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.45 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 14-MAR-13:00 | 365.42 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 19-APR-13:00 | 284.06 | 17-APR-03:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.03 | 17-MAY-13:00 | 214.91 | 03-MAY-02:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 26-JUN-15:00 | 158.92 | 09-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.18 | 16-JUL-13:00 | 136.98 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.57 | 16-AUG-14:00 | 119.44 | 12-AUG-23:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 | 09-SEP-13:00 | 232.94 | 22-SEP-05:40 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.40 | 11-OCT-14:00 | 304.84 | 30-OCT-06:20 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 357.73 | 29-NOV-21:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 | 01-DEC-14:00 | 452.77 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.44 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 452.77 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 231.20 | 05-JAN-19:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 241.43 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 | 14-MAR-13:00 | 210.83 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 19-APR-13:00 | 163.88 | 17-APR-03:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 17-MAY-13:00 | 122.34 | 03-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 26-JUN-15:00 | 90.20 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.57 | 16-JUL-13:00 | 77.73 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.21 | 16-AUG-14:00 | 67.35 | 12-AUG-23:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.54 | 09-SEP-13:00 | 131.83 | 22-SEP-05:30 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 11-OCT-14:00 | 175.88 | 30-OCT-06:20 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 206.39 | 29-NOV-21:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 01-DEC-14:00 | 261.21 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 261.21 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 588.20 | 05-JAN-19:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 612.30 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 10.96 | 14-MAR-13:00 | 539.84 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 427.92 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 58.92 | 17-MAY-13:00 | 307.33 | 02-MAY-24:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 177.60 | 26-JUN-15:20 | 213.59 | 09-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 156.75 | 16-JUL-13:00 | 185.61 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 155.71 | 16-AUG-16:00 | 163.22 | 12-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 109.87 | 10-SEP-13:00 | 336.55 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 47.01 | 11-OCT-14:00 | 456.51 | 30-OCT-07:20 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 529.15 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 644.56 | 23-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 177.60 | 644.56 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 971.08 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1014.10 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 885.52 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 707.81 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 17-MAY-13:00 | 553.90 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 26-JUN-15:00 | 392.59 | 09-JUN-04:07 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.99 | 16-JUL-13:00 | 325.93 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.56 | 16-AUG-16:00 | 289.57 | 12-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.53 | 10-SEP-13:00 | 575.80 | 22-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 11-OCT-14:00 | 759.01 | 30-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 876.64 | 29-NOV-21:10 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1097.21 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.57 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 1097.21 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2830.51 | 05-JAN-19:10 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2999.35 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2625.42 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2090.85 | 17-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.93 | 17-MAY-13:00 | 1625.33 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 892.49 | 26-JUN-15:00 | 1121.79 | 09-JUN-04:07 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 770.54 | 16-JUL-13:00 | 956.25 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 758.66 | 16-AUG-16:00 | 827.48 | 12-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.80 | 10-SEP-13:00 | 1703.54 | 22-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.34 | 11-OCT-14:00 | 2245.24 | 30-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2607.84 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3195.52 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.48 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 892.49 | 3195.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.54 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.24 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 14-MAR-15:10 | 233.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 | 31-MAY-16:00 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 26-JUN-15:10 | 86.23 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.65 | 16-JUL-15:10 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 16-AUG-16:00 | 59.41 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 | 10-OCT-16:30 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 289.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 289.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.52 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.22 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:10 | 233.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 31-MAY-16:00 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.93 | 26-JUN-15:10 | 86.23 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 16-JUL-13:00 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 16-AUG-16:00 | 63.95 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 11-OCT-15:10 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.55 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 289.06 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.93 | 289.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 73.80 | 14-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 75.73 | 12-FEB-05:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 65.73 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 51.15 | 11-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 17-MAY-13:00 | 42.27 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 26-JUN-15:00 | 32.83 | 09-JUN-04:20 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.48 | 16-JUL-13:00 | 28.89 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 | 16-AUG-14:00 | 25.64 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 10-SEP-13:00 | 46.12 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 11-OCT-14:00 | 57.41 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.57 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 74.93 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 75.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 70.76 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 74.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 14-MAR-13:00 | 65.16 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 50.71 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 31-MAY-15:10 | 37.37 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 26-JUN-15:10 | 24.07 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 16-JUL-13:00 | 19.87 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 16-AUG-16:00 | 16.58 | 12-AUG-23:50 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 10-SEP-16:00 | 38.93 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 11-OCT-15:10 | 54.40 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 07-NOV-14:00 | 63.79 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 01-DEC-14:00 | 80.68 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 80.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.54 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.24 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-16:00 | 233.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.35 | 26-JUN-15:40 | 86.23 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.47 | 16-JUL-13:00 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.20 | 16-AUG-16:00 | 63.31 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 | 11-OCT-15:10 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 289.09 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 91.35 | 289.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.51 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.22 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:10 | 233.45 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 26-JUN-15:10 | 86.23 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 16-JUL-13:00 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.20 | 16-AUG-16:00 | 63.33 | 12-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.56 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 01-DEC-14:00 | 289.07 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.33 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 289.07 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 308.64 | 05-JAN-19:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 322.28 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 14-MAR-13:00 | 281.47 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 19-APR-13:00 | 218.87 | 17-APR-03:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 17-MAY-13:00 | 163.51 | 03-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 26-JUN-15:00 | 121.97 | 09-JUN-04:03 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 16-JUL-13:00 | 104.27 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 16-AUG-16:00 | 91.30 | 12-AUG-23:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 10-SEP-13:00 | 179.59 | 22-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 11-OCT-14:00 | 234.86 | 30-OCT-06:20 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 275.55 | 29-NOV-21:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 01-DEC-14:00 | 348.69 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 348.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.98 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.69 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 14-MAR-15:10 | 233.90 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.09 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.22 | 31-MAY-16:00 | 134.29 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.10 | 26-JUN-15:10 | 86.60 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 | 16-JUL-13:00 | 71.58 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.85 | 16-AUG-16:00 | 59.76 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 | 10-SEP-16:00 | 139.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 10-OCT-16:30 | 195.32 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 229.00 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 289.54 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 85.10 | 289.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.95 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 267.66 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 13-MAR-15:10 | 233.89 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.08 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 31-MAY-16:00 | 134.28 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 | 26-JUN-15:10 | 86.60 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 | 16-JUL-13:00 | 71.57 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.77 | 16-AUG-16:00 | 66.38 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.36 | 10-SEP-16:00 | 139.88 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 | 11-OCT-15:10 | 195.30 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.98 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 289.52 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 | 289.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 129.95 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 136.95 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 14-MAR-15:10 | 119.67 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 93.17 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 31-MAY-15:50 | 68.71 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 | 26-JUN-15:10 | 44.31 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 16-JUL-15:10 | 36.62 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.34 | 16-AUG-16:00 | 30.58 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 10-SEP-16:00 | 71.57 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 10-OCT-17:00 | 99.93 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 117.17 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 148.14 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 | 148.14 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 664.16 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 695.44 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 615.87 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 488.50 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.65 | 17-MAY-13:00 | 370.45 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 26-JUN-15:00 | 253.23 | 09-JUN-04:07 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 | 16-JUL-13:00 | 216.04 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 16-AUG-16:00 | 187.13 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.42 | 10-SEP-13:00 | 384.57 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 11-OCT-14:00 | 520.98 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 603.68 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 746.32 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.13 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 746.32 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 665.06 | 05-JAN-19:08 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 699.34 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 615.87 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 488.50 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.65 | 17-MAY-13:00 | 370.45 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 26-JUN-15:00 | 253.23 | 09-JUN-04:07 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 | 16-JUL-13:00 | 216.04 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 16-AUG-16:00 | 187.14 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.42 | 10-SEP-13:00 | 384.57 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 | 11-OCT-14:00 | 520.99 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 603.69 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 750.52 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.14 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 750.52 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 600.47 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 626.00 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 551.25 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 437.25 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 58.91 | 17-MAY-13:00 | 323.88 | 03-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 178.26 | 26-JUN-15:00 | 226.70 | 09-JUN-04:03 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 152.20 | 16-JUL-13:00 | 193.39 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 151.42 | 16-AUG-16:00 | 167.54 | 12-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 102.57 | 10-SEP-13:00 | 344.26 | 22-SEP-05:05 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 34.96 | 11-OCT-14:00 | 466.42 | 30-OCT-07:07 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 540.33 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 660.62 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 167.54 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 178.26 | 660.62 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 547.05 | 05-JAN-19:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 571.18 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 498.96 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 388.13 | 17-APR-03:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.02 | 17-MAY-13:00 | 285.89 | 03-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 | 26-JUN-15:00 | 209.46 | 09-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.83 | 16-JUL-13:00 | 177.80 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 16-AUG-16:00 | 158.36 | 12-AUG-23:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.24 | 10-SEP-13:00 | 302.74 | 22-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 11-OCT-14:00 | 416.44 | 30-OCT-06:40 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 488.45 | 29-NOV-21:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 617.96 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.36 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 | 617.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17991.44 | 26-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16396.92 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15069.68 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14074.66 | 14-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13533.86 | 19-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16468.94 | 16-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17215.06 | 28-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19894.17 | 18-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22574.97 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22633.95 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22330.53 | 09-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21394.92 | 05-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13533.86 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22633.95 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4991.97 | 20-JAN-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
February | 4973.06 | 18-FEB-13:20 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 |
March | 4616.48 | 14-MAR-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
April | 3255.08 | 07-APR-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.99 |
May | 2380.20 | 05-MAY-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
June | 3059.58 | 26-JUN-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
July | 3303.56 | 23-JUL-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 | 0.00 |
August | 4020.40 | 31-AUG-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 0.00 |
September | 4901.24 | 28-SEP-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 | 0.00 |
October | 4942.20 | 10-OCT-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
November | 5019.27 | 07-NOV-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 |
December | 4654.61 | 17-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2380.20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5019.27 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 58.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1533.37 | 20-JAN-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 |
February | 1428.61 | 27-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 |
March | 1816.20 | 15-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 |
April | 1595.84 | 07-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 |
May | 1784.80 | 31-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 |
June | 2226.34 | 26-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 0.00 |
July | 2134.31 | 17-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 0.00 |
August | 2216.47 | 16-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
September | 2087.10 | 12-SEP-20:03 | 7223.04 | 3690.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 1877.04 | 11-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
November | 1636.46 | 07-NOV-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.62 |
December | 1380.75 | 04-DEC-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1380.75 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2226.34 | 7223.04 | 3690.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 79.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 867.26 | 20-JAN-13:40 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
February | 859.83 | 18-FEB-13:30 | 95.47 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
March | 930.51 | 15-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.07 |
April | 882.62 | 21-APR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.69 |
May | 1067.24 | 17-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 |
June | 1866.83 | 26-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 0.00 |
July | 1890.10 | 17-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 0.00 |
August | 1735.13 | 16-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 0.00 |
September | 1564.41 | 12-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 962.30 | 01-OCT-10:35 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.94 |
November | 906.02 | 07-NOV-13:30 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 |
December | 795.15 | 03-DEC-13:00 | 95.47 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 795.15 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1890.10 | 254.59 | 684.18 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 81.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 514.67 | 20-JAN-13:40 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
February | 511.82 | 18-FEB-13:30 | 73.44 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 |
March | 542.63 | 15-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 |
April | 514.33 | 21-APR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 |
May | 571.84 | 18-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 |
June | 916.92 | 26-JUN-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 | 0.00 |
July | 886.87 | 17-JUL-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 0.00 |
August | 801.30 | 16-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
September | 676.07 | 12-SEP-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
October | 565.39 | 11-OCT-12:50 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
November | 535.77 | 07-NOV-13:30 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
December | 468.01 | 03-DEC-13:00 | 73.44 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 468.01 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 916.92 | 195.84 | 251.84 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 | 46.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37685.65 | 20-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 213.69 |
February | 37660.65 | 27-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 252.92 |
March | 38311.04 | 14-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 |
April | 38320.58 | 20-APR-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 109.82 |
May | 38648.60 | 16-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 |
June | 39299.76 | 26-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 101.23 | 0.00 |
July | 39319.26 | 07-JUL-19:40 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
August | 39203.89 | 16-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 58.82 | 0.00 |
September | 38878.02 | 12-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
October | 38218.10 | 11-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 162.15 |
November | 37875.29 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 186.08 |
December | 37488.67 | 04-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 211.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37488.67 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39319.26 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 101.23 | 252.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17412.87 | 20-JAN-13:00 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.42 |
February | 17836.82 | 18-FEB-13:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.18 |
March | 16379.36 | 11-MAR-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.92 |
April | 12161.64 | 07-APR-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
May | 10031.93 | 10-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
June | 11766.17 | 26-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 0.00 |
July | 11851.48 | 17-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.50 | 0.00 |
August | 13798.66 | 26-AUG-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.66 | 0.00 |
September | 16132.22 | 28-SEP-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 0.00 |
October | 16473.27 | 07-OCT-12:20 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 |
November | 17784.92 | 05-NOV-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 |
December | 17099.79 | 17-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10031.93 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17836.82 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.66 | 150.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34808.59 | 20-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1025.57 |
February | 33154.73 | 17-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.34 |
March | 37345.03 | 15-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.41 |
April | 34407.50 | 20-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.80 |
May | 36892.88 | 17-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.04 |
June | 42510.93 | 26-JUN-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 475.87 | 0.00 |
July | 42387.26 | 17-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 269.86 | 0.00 |
August | 42655.13 | 16-AUG-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 268.90 | 0.00 |
September | 41304.92 | 12-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.03 |
October | 38255.75 | 10-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.59 |
November | 35456.51 | 07-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.07 |
December | 32555.06 | 04-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32555.06 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42655.13 | 45622.98 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 475.87 | 1095.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2562.51 | 23-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.11 |
February | 2562.26 | 25-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 |
March | 2672.85 | 13-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
April | 2624.02 | 07-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
May | 2598.27 | 09-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 |
June | 2685.26 | 30-JUN-17:04 | 777.60 | 953.45 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 0.00 |
July | 2706.11 | 15-JUL-17:04 | 777.60 | 1209.60 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 56.32 | 0.00 |
August | 2712.29 | 16-AUG-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 | 0.00 |
September | 2710.46 | 28-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 | 0.00 |
October | 2694.81 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
November | 2625.52 | 05-NOV-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
December | 2512.57 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2512.57 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2712.29 | 777.60 | 1209.60 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 | 62.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2423.74 | 23-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 |
February | 2421.75 | 26-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
March | 2818.78 | 15-MAR-18:31 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.77 |
April | 2911.56 | 08-APR-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 |
May | 2840.60 | 27-MAY-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 |
June | 2809.81 | 18-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
July | 2907.22 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 0.00 |
August | 2785.69 | 13-AUG-21:51 | 1247.40 | 1360.64 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.67 |
September | 2669.29 | 15-SEP-19:51 | 1247.40 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.97 |
October | 2773.80 | 14-OCT-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
November | 2469.44 | 07-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
December | 2402.29 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2402.29 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2911.56 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 66.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 849.37 | 20-JAN-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
February | 806.39 | 18-FEB-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
March | 733.84 | 14-MAR-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
April | 425.93 | 12-APR-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
May | 340.73 | 16-MAY-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
June | 428.42 | 14-JUN-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 0.00 |
July | 463.58 | 23-JUL-13:10 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 0.00 |
August | 592.77 | 31-AUG-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
September | 765.04 | 28-SEP-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
October | 790.79 | 10-OCT-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
November | 841.51 | 07-NOV-12:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 |
December | 755.72 | 17-DEC-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 340.73 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 849.37 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 13.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 726.52 | 21-JAN-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 |
February | 731.47 | 19-FEB-09:01 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
March | 793.65 | 14-MAR-20:51 | 1121.40 | 696.66 | 1246.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 |
April | 814.68 | 20-APR-20:31 | 1441.80 | 895.70 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 |
May | 838.65 | 17-MAY-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
June | 876.28 | 12-JUN-08:61 | 288.00 | 393.62 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 0.00 |
July | 918.10 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
August | 879.01 | 01-AUG-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 |
September | 852.04 | 09-SEP-21:51 | 970.20 | 665.35 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
October | 807.58 | 11-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
November | 739.58 | 06-NOV-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
December | 713.28 | 03-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 713.28 | 288.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 918.10 | 1441.80 | 895.70 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 27.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2239.87 | 20-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 |
February | 2281.59 | 18-FEB-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.22 |
March | 2308.00 | 11-MAR-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.18 |
April | 2711.62 | 19-APR-08:51 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 |
May | 2331.90 | 17-MAY-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
June | 2378.20 | 27-JUN-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 | 0.00 |
July | 2438.51 | 01-JUL-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
August | 2398.79 | 05-AUG-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
September | 2351.62 | 28-SEP-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 |
October | 2307.88 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 0.00 |
November | 2288.15 | 07-NOV-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
December | 2213.96 | 15-DEC-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2213.96 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2711.62 | 583.20 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 122.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2129.63 | 20-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.29 |
February | 2179.28 | 27-FEB-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 |
March | 2234.33 | 15-MAR-18:31 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 |
April | 2621.74 | 19-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 |
May | 2669.45 | 10-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 |
June | 2893.63 | 27-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
July | 2802.27 | 01-JUL-07:32 | 477.00 | 498.01 | 1185.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 |
August | 2830.77 | 08-AUG-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 |
September | 2674.48 | 18-SEP-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
October | 2599.67 | 11-OCT-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
November | 2174.65 | 07-NOV-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 |
December | 2091.71 | 02-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2091.71 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | |
Maximum of Months | 2893.63 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1862.29 | 20-JAN-13:40 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
February | 1912.73 | 18-FEB-13:30 | 754.45 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 |
March | 2025.60 | 15-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 |
April | 1817.59 | 21-APR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 |
May | 2009.50 | 18-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 |
June | 3338.39 | 26-JUN-18:30 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 0.00 |
July | 2960.47 | 15-JUL-18:30 | 1508.90 | 1452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.98 | 0.00 |
August | 2991.70 | 16-AUG-18:13 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 | 0.00 |
September | 2710.55 | 12-SEP-18:04 | 8801.94 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 | 0.00 |
October | 2109.58 | 11-OCT-12:50 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
November | 1967.76 | 07-NOV-13:30 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
December | 1715.90 | 17-DEC-13:00 | 754.45 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1715.90 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3338.39 | 8801.94 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 61.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2718.60 | 20-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 |
February | 2719.02 | 17-FEB-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 |
March | 2837.21 | 13-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 2776.41 | 07-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
May | 2757.84 | 09-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 |
June | 2889.54 | 24-JUN-17:03 | 680.40 | 1058.40 | 885.02 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 | 0.00 |
July | 2859.11 | 01-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 | 0.00 |
August | 2894.17 | 16-AUG-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 69.58 | 0.00 |
September | 2877.23 | 28-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 | 0.00 |
October | 2853.62 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 0.00 |
November | 2790.25 | 05-NOV-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
December | 2666.80 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2666.80 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2894.17 | 702.00 | 1067.29 | 885.02 | 0.00 | 0.00 | 0.00 | 0.00 | 69.58 | 52.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2544.80 | 23-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 |
February | 2544.23 | 25-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.41 |
March | 3048.38 | 08-MAR-17:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.01 |
April | 3120.21 | 08-APR-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.27 |
May | 3041.01 | 27-MAY-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 |
June | 3043.99 | 18-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 |
July | 3030.13 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 0.00 |
August | 2926.35 | 05-AUG-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 |
September | 2865.96 | 15-SEP-19:51 | 1247.40 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 |
October | 2976.83 | 08-OCT-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.12 |
November | 2607.14 | 07-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
December | 2529.14 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2529.14 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3120.21 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 68.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1511.09 | 20-JAN-13:15 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
February | 1411.95 | 17-FEB-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
March | 1466.05 | 13-MAR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 1406.44 | 07-APR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 |
May | 1396.79 | 04-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 0.00 |
June | 1404.06 | 14-JUN-15:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 0.00 |
July | 1403.16 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
August | 1429.78 | 17-AUG-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 | 0.00 |
September | 1469.52 | 28-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
October | 1486.88 | 08-OCT-12:35 | 108.00 | 73.80 | 67.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
November | 1536.69 | 16-NOV-13:33 | 108.00 | 93.93 | 92.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 |
December | 1400.91 | 17-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1396.79 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1536.69 | 583.20 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 27.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18407.72 | 20-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.57 |
February | 18109.60 | 27-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.43 |
March | 20271.98 | 14-MAR-21:03 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 |
April | 20364.20 | 20-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.47 |
May | 21503.09 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 |
June | 23375.69 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 0.00 |
July | 23238.37 | 17-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 0.00 |
August | 23130.94 | 16-AUG-21:50 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 0.00 |
September | 22232.50 | 12-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
October | 20339.43 | 10-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.80 |
November | 19275.00 | 09-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.99 |
December | 18419.40 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18109.60 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23375.69 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 319.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20054.82 | 20-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.58 |
February | 19718.29 | 27-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.43 |
March | 21597.51 | 14-MAR-21:03 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 |
April | 21865.52 | 20-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.48 |
May | 22816.07 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.40 |
June | 24571.78 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 0.00 |
July | 24483.34 | 17-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.48 | 0.00 |
August | 24283.36 | 16-AUG-21:50 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
September | 23416.01 | 12-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 |
October | 21633.77 | 10-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.80 |
November | 20722.02 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.97 |
December | 20086.74 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19718.29 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24571.78 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 52.48 | 319.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28578.14 | 20-JAN-11:40 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 58.92 |
February | 29032.85 | 18-FEB-11:40 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 80.12 |
March | 30166.59 | 14-MAR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 |
April | 29867.93 | 20-APR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 |
May | 30463.19 | 16-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
June | 31337.99 | 26-JUN-10:40 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 101.69 | 0.00 |
July | 31547.31 | 23-JUL-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 67.83 | 0.00 |
August | 31631.81 | 05-AUG-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 63.81 | 0.00 |
September | 31076.42 | 04-SEP-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 33.32 | 0.00 |
October | 30142.43 | 07-OCT-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 |
November | 29355.55 | 05-NOV-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 |
December | 28316.92 | 02-DEC-11:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28316.92 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31631.81 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 101.69 | 80.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4243.22 | 20-JAN-13:40 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 |
February | 4291.20 | 18-FEB-13:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.85 |
March | 4921.08 | 15-MAR-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 |
April | 4026.79 | 21-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.47 |
May | 4355.05 | 18-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 |
June | 7018.18 | 26-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.91 | 0.00 |
July | 6962.87 | 23-JUL-13:00 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 | 0.00 |
August | 7268.13 | 16-AUG-15:02 | 6654.00 | 2744.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 0.00 |
September | 6864.72 | 09-SEP-12:50 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.28 | 0.00 |
October | 5084.96 | 11-OCT-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 0.00 |
November | 4440.19 | 07-NOV-13:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 |
December | 3763.53 | 03-DEC-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3763.53 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7268.13 | 6654.00 | 2744.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.91 | 116.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.380057E+12 | 250111.53 | 24-JAN-20:19 | 0.614372E+12 | 617423.89 | 05-JAN-19:10 |
February | 0.338699E+12 | 248267.07 | 27-FEB-20:10 | 0.579703E+12 | 599541.38 | 22-FEB-18:19 |
March | 0.376481E+12 | 268609.46 | 13-MAR-19:30 | 0.597750E+12 | 597180.32 | 02-MAR-18:00 |
April | 0.355303E+12 | 259487.84 | 20-APR-20:40 | 0.563371E+12 | 572841.44 | 04-APR-17:19 |
May | 0.404253E+12 | 307662.49 | 31-MAY-18:19 | 0.532493E+12 | 541031.86 | 02-MAY-18:10 |
June | 0.501502E+12 | 396959.82 | 26-JUN-19:30 | 0.407495E+12 | 351414.98 | 02-JUN-17:19 |
July | 0.529506E+12 | 393812.69 | 17-JUL-19:30 | 0.412012E+12 | 349792.85 | 03-JUL-17:19 |
August | 0.517258E+12 | 390449.51 | 10-AUG-19:10 | 0.409958E+12 | 349052.45 | 30-AUG-17:19 |
September | 0.462912E+12 | 359790.08 | 12-SEP-18:30 | 0.432927E+12 | 467200.88 | 22-SEP-20:00 |
October | 0.394148E+12 | 280299.84 | 10-OCT-19:10 | 0.542910E+12 | 547643.29 | 02-OCT-16:49 |
November | 0.371219E+12 | 256872.79 | 07-NOV-20:10 | 0.549041E+12 | 559299.43 | 25-NOV-18:40 |
December | 0.375774E+12 | 247864.73 | 04-DEC-20:00 | 0.670697E+12 | 642113.20 | 21-DEC-19:30 |
Annual Sum or Average | 0.500711E+13 | 0.631273E+13 | ||||
Minimum of Months | 0.338699E+12 | 247864.73 | 0.407495E+12 | 349052.45 | ||
Maximum of Months | 0.529506E+12 | 396959.82 | 0.670697E+12 | 642113.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670763E+11 | 0.199069E+11 | 0.140828E+12 | 0.544239E+11 | 0.434069E+11 | 0.488566E+10 | 0.00 | 0.162971E+11 | 0.00 | 0.00 | 0.203410E+11 | 0.770454E+10 | 0.00 |
February | 0.603817E+11 | 0.167606E+11 | 0.127191E+12 | 0.491570E+11 | 0.385972E+11 | 0.411821E+10 | 0.00 | 0.120940E+11 | 0.00 | 0.00 | 0.187634E+11 | 0.696213E+10 | 0.00 |
March | 0.664904E+11 | 0.168346E+11 | 0.140882E+12 | 0.544261E+11 | 0.432668E+11 | 0.487139E+10 | 0.00 | 0.210720E+11 | 0.00 | 0.00 | 0.157521E+11 | 0.770302E+10 | 0.00 |
April | 0.640698E+11 | 0.145470E+11 | 0.136245E+12 | 0.526675E+11 | 0.400324E+11 | 0.469320E+10 | 0.00 | 0.165252E+11 | 0.00 | 0.00 | 0.140346E+11 | 0.746509E+10 | 0.00 |
May | 0.657791E+11 | 0.135180E+11 | 0.140860E+12 | 0.544244E+11 | 0.469337E+11 | 0.697750E+10 | 0.00 | 0.570002E+11 | 0.00 | 0.00 | 0.583279E+10 | 0.770429E+10 | 0.00 |
June | 0.633888E+11 | 0.122817E+11 | 0.136336E+12 | 0.526695E+11 | 0.573087E+11 | 0.729832E+10 | 0.00 | 0.149941E+12 | 0.00 | 0.00 | 0.972313E+10 | 0.745688E+10 | 0.00 |
July | 0.656186E+11 | 0.130516E+11 | 0.140770E+12 | 0.544218E+11 | 0.594380E+11 | 0.768684E+10 | 0.00 | 0.165207E+12 | 0.00 | 0.00 | 0.103484E+11 | 0.771239E+10 | 0.00 |
August | 0.659875E+11 | 0.143620E+11 | 0.140892E+12 | 0.544258E+11 | 0.597892E+11 | 0.762512E+10 | 0.00 | 0.152227E+12 | 0.00 | 0.00 | 0.897072E+10 | 0.770434E+10 | 0.00 |
September | 0.642168E+11 | 0.155316E+11 | 0.136256E+12 | 0.526677E+11 | 0.558875E+11 | 0.702646E+10 | 0.00 | 0.111734E+12 | 0.00 | 0.00 | 0.706971E+10 | 0.746627E+10 | 0.00 |
October | 0.668205E+11 | 0.178488E+11 | 0.140818E+12 | 0.544237E+11 | 0.483004E+11 | 0.538962E+10 | 0.00 | 0.334747E+11 | 0.00 | 0.00 | 0.141753E+11 | 0.770297E+10 | 0.00 |
November | 0.648437E+11 | 0.188112E+11 | 0.136330E+12 | 0.526689E+11 | 0.441250E+11 | 0.486206E+10 | 0.00 | 0.186330E+11 | 0.00 | 0.00 | 0.184775E+11 | 0.744904E+10 | 0.00 |
December | 0.670878E+11 | 0.203362E+11 | 0.140770E+12 | 0.544227E+11 | 0.441525E+11 | 0.415481E+10 | 0.00 | 0.117792E+11 | 0.00 | 0.00 | 0.201981E+11 | 0.771272E+10 | 0.00 |
Annual Sum or Average | 0.781761E+12 | 0.193790E+12 | 0.165818E+13 | 0.640799E+12 | 0.581238E+12 | 0.695892E+11 | 0.00 | 0.765985E+12 | 0.00 | 0.00 | 0.163687E+12 | 0.907437E+11 | 0.00 |
Minimum of Months | 0.603817E+11 | 0.122817E+11 | 0.127191E+12 | 0.491570E+11 | 0.385972E+11 | 0.411821E+10 | 0.00 | 0.117792E+11 | 0.00 | 0.00 | 0.583279E+10 | 0.696213E+10 | 0.00 |
Maximum of Months | 0.670878E+11 | 0.203362E+11 | 0.140892E+12 | 0.544261E+11 | 0.597892E+11 | 0.768684E+10 | 0.00 | 0.165207E+12 | 0.00 | 0.00 | 0.203410E+11 | 0.771272E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.170630E+12 | 0.00 | 0.291823E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.176527E+12 | 0.00 | 0.265971E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.154290E+12 | 0.00 | 0.291436E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.142102E+12 | 0.00 | 0.274313E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.107743E+12 | 0.00 | 0.272772E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.662548E+10 | 0.00 | 0.253755E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.571732E+10 | 0.00 | 0.254475E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.605447E+10 | 0.00 | 0.251865E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.393011E+11 | 0.00 | 0.246655E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.128205E+12 | 0.00 | 0.262802E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.137275E+12 | 0.00 | 0.264675E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.234811E+12 | 0.00 | 0.284065E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.130928E+13 | 0.00 | 0.321461E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.571732E+10 | 0.00 | 0.246655E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.234811E+12 | 0.00 | 0.291823E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 32139.91 | 20-JAN-22:10 | 3394.17 | 01-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 29233.93 | 17-FEB-22:10 | 3382.80 | 14-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 37094.81 | 14-MAR-21:10 | 3340.32 | 05-MAR-16:30 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.68 | 03-APR-06:19 | 35093.10 | 20-APR-21:10 | 3242.79 | 06-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39168.28 | 19-MAY-06:19 | 37833.81 | 16-MAY-21:00 | 4187.24 | 31-MAY-18:49 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.39 | 16-JUN-06:19 | 60704.86 | 27-JUN-19:10 | 5421.85 | 15-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.39 | 28-JUL-06:19 | 61239.06 | 17-JUL-18:40 | 5535.57 | 12-JUL-19:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39168.49 | 18-AUG-06:19 | 58662.11 | 10-AUG-19:10 | 5590.76 | 10-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.47 | 19-SEP-06:19 | 52366.86 | 12-SEP-18:30 | 5488.92 | 12-SEP-18:30 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 43118.20 | 10-OCT-21:10 | 3317.50 | 25-OCT-08:30 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 35151.84 | 07-NOV-22:10 | 3350.28 | 12-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 31376.12 | 04-DEC-22:10 | 3414.80 | 22-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.28 | 29233.93 | 3242.79 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 61239.06 | 5590.76 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 64502.57 | 20-JAN-13:20 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.31 | 30-JAN-07:10 | 0.00 |
February | 60314.47 | 18-FEB-13:30 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.40 | 13-FEB-19:10 | 0.00 |
March | 81621.02 | 13-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.44 | 31-MAR-18:49 | 0.00 |
April | 64171.46 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.17 | 03-APR-18:10 | 0.00 |
May | 92876.49 | 31-MAY-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAY-05:19 | 4738.71 | 11-MAY-18:10 | 0.00 |
June | 156777.56 | 26-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-12:09 | 4738.67 | 08-JUN-18:10 | 0.00 |
July | 125580.47 | 15-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:09 | 4738.60 | 27-JUL-18:10 | 0.00 |
August | 148511.78 | 16-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 02-AUG-09:00 | 4738.62 | 24-AUG-18:10 | 0.00 |
September | 115372.69 | 10-SEP-15:39 | 0.00 | 0.00 | 9938.94 | 02-SEP-12:09 | 4738.73 | 14-SEP-18:10 | 0.00 |
October | 96947.50 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-20:10 | 4738.39 | 16-OCT-18:10 | 0.00 |
November | 67482.41 | 07-NOV-13:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.53 | 08-NOV-19:10 | 0.00 |
December | 59651.11 | 02-DEC-13:20 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.29 | 18-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 59651.11 | 0.00 | 0.00 | 9938.94 | 4738.17 | 0.00 | |||
Maximum of Months | 156777.56 | 0.00 | 0.00 | 9938.94 | 4738.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 250111.53 | 24-JAN-20:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 25457.30 | 2489.12 | 0.00 | 11503.79 | 0.00 |
February | 248267.07 | 27-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 24780.29 | 2477.65 | 0.00 | 9887.24 | 0.00 |
March | 268609.46 | 13-MAR-19:30 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 31107.04 | 2571.59 | 0.00 | 32508.13 | 0.00 |
April | 259487.84 | 20-APR-20:40 | 57474.69 | 88218.55 | 12338.45 | 24013.36 | 32852.70 | 2566.46 | 0.00 | 34411.86 | 0.00 |
May | 307662.49 | 31-MAY-18:19 | 53381.59 | 77573.37 | 0.00 | 31351.44 | 32292.33 | 3974.98 | 0.00 | 92019.37 | 0.00 |
June | 396959.82 | 26-JUN-19:30 | 64632.59 | 86439.81 | 12338.45 | 31552.79 | 42689.25 | 3946.01 | 0.00 | 139019.95 | 0.00 |
July | 393812.69 | 17-JUL-19:30 | 64632.59 | 86439.81 | 12338.45 | 31552.79 | 56296.47 | 5334.47 | 0.00 | 120766.79 | 0.00 |
August | 390449.51 | 10-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 58662.11 | 5590.76 | 0.00 | 115117.35 | 0.00 |
September | 359790.08 | 12-SEP-18:30 | 57474.69 | 77573.37 | 12338.45 | 31354.49 | 52366.86 | 5488.92 | 0.00 | 106695.13 | 0.00 |
October | 280299.84 | 10-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 30883.32 | 2571.40 | 0.00 | 46460.57 | 0.00 |
November | 256872.79 | 07-NOV-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 28634.46 | 2505.91 | 0.00 | 15344.63 | 0.00 |
December | 247864.73 | 04-DEC-20:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 25784.87 | 2484.02 | 0.00 | 8812.55 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 247864.73 | 53381.59 | 77573.37 | 0.00 | 24013.36 | 24780.29 | 2477.65 | 0.00 | 8812.55 | 0.00 | |
Maximum of Months | 396959.82 | 64632.59 | 88218.55 | 12338.45 | 31553.12 | 58662.11 | 5590.76 | 0.00 | 139019.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 261201.94 | 05-JAN-19:10 | 0.00 | 293023.89 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 246897.93 | 12-FEB-07:10 | 0.00 | 293470.52 | 13-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 238508.83 | 27-MAR-10:39 | 0.00 | 292366.15 | 07-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 213657.29 | 17-APR-10:39 | 0.00 | 287973.29 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 208641.56 | 01-MAY-00:10 | 0.00 | 279769.41 | 04-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 179357.95 | 09-JUN-03:49 | 0.00 | 249171.81 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 94701.86 | 02-JUL-04:00 | 0.00 | 246235.96 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 85021.07 | 23-AUG-04:00 | 0.00 | 245409.76 | 22-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 214073.67 | 21-SEP-14:20 | 0.00 | 246339.29 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 221605.77 | 09-OCT-05:10 | 0.00 | 250164.99 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 230299.56 | 02-NOV-10:50 | 0.00 | 279636.06 | 24-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 307078.75 | 21-DEC-09:20 | 0.00 | 288730.56 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 85021.07 | 0.00 | 245409.76 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 307078.75 | 0.00 | 293470.52 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.37 | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 1.33 | 20.37 | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.37 | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.27 | 2.33 | 25.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.08 | 3.00 | 25.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.88 | 0.67 | 24.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 25.13 | 6.00 | 25.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.27 | 3.00 | 25.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.97 | 0.17 | 21.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.90 | 3.67 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 22.22 | 39.83 | 22.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 22.15 | 24.17 | 22.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 22.43 | 32.83 | 22.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 22.31 | 15.00 | 22.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.93 | 4.00 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
December | 0.83 | 20.35 | 0.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 0.83 | 20.35 | 0.83 | 20.35 | 122.33 | 22.22 | 122.33 | 22.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.35 | 0.83 | 20.35 | 39.83 | 22.43 | 39.83 | 22.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.89 | 0.50 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.85 | 4.67 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 22.25 | 50.17 | 22.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 22.18 | 32.33 | 22.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 22.30 | 32.33 | 22.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 22.13 | 11.50 | 22.13 |
October | 0.17 | 20.55 | 0.17 | 20.55 | 0.50 | 21.28 | 0.50 | 21.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 20.38 | 1.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 2.33 | 20.42 | 2.33 | 20.42 | 132.50 | 22.15 | 132.50 | 22.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.55 | 1.83 | 20.55 | 50.17 | 22.30 | 50.17 | 22.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.43 | 0.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.91 | 7.67 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 21.96 | 41.67 | 21.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 21.96 | 49.17 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 21.90 | 20.50 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 21.90 | 11.83 | 21.90 |
October | 0.33 | 20.34 | 0.33 | 20.34 | 0.17 | 20.63 | 0.17 | 20.82 |
November | 0.33 | 20.39 | 0.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
December | 3.50 | 20.26 | 3.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
Annual Sum or Average | 5.67 | 20.31 | 5.67 | 20.31 | 131.50 | 21.81 | 131.50 | 21.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 0.00 | 20.26 |
Maximum of Months | 3.50 | 20.43 | 3.50 | 20.43 | 49.17 | 21.96 | 49.17 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.55 | 0.33 | 20.55 | 0.33 | 20.96 | 0.33 | 21.17 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 1.33 | 21.60 | 1.33 | 21.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.01 | 3.67 | 22.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.97 | 4.50 | 21.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 22.11 | 36.00 | 22.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 22.14 | 38.33 | 22.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 22.04 | 38.17 | 22.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.09 | 23.83 | 22.09 |
October | 0.17 | 20.53 | 0.17 | 20.53 | 8.83 | 21.93 | 8.83 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
December | 1.83 | 20.41 | 1.83 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Annual Sum or Average | 2.50 | 20.45 | 2.50 | 20.45 | 158.00 | 22.03 | 158.00 | 22.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 0.00 | 20.41 |
Maximum of Months | 1.83 | 20.55 | 1.83 | 20.55 | 38.33 | 22.14 | 38.33 | 22.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.46 | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.17 | 20.53 | 0.17 | 20.53 | 0.17 | 20.91 | 0.17 | 21.10 |
March | 0.17 | 20.55 | 0.17 | 20.55 | 0.17 | 20.95 | 0.17 | 21.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.03 | 2.33 | 22.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.27 | 6.17 | 22.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 22.42 | 51.83 | 22.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 22.46 | 56.17 | 22.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 22.47 | 35.67 | 22.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 22.29 | 20.33 | 22.29 |
October | 0.17 | 20.52 | 0.17 | 20.52 | 1.50 | 21.69 | 1.50 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
December | 2.67 | 20.30 | 2.67 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 3.67 | 20.35 | 3.67 | 20.35 | 174.50 | 22.33 | 174.50 | 22.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 0.00 | 20.30 |
Maximum of Months | 2.67 | 20.55 | 2.67 | 20.55 | 56.17 | 22.47 | 56.17 | 22.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.51 | 0.17 | 20.51 | 0.33 | 21.17 | 0.33 | 21.38 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.87 | 2.33 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.99 | 5.50 | 21.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 22.38 | 46.33 | 22.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 22.26 | 28.33 | 22.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 22.64 | 37.33 | 22.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 22.39 | 16.67 | 22.39 |
October | 0.17 | 20.53 | 0.17 | 20.53 | 4.67 | 21.86 | 4.67 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.85 | 1.00 | 21.85 |
December | 1.50 | 20.35 | 1.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 2.00 | 20.39 | 2.00 | 20.39 | 142.83 | 22.33 | 142.83 | 22.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 0.00 | 20.35 |
Maximum of Months | 1.50 | 20.55 | 1.50 | 20.55 | 46.33 | 22.64 | 46.33 | 22.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.98 | 0.67 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.99 | 5.67 | 21.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 22.38 | 56.83 | 22.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 22.28 | 36.33 | 22.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 22.49 | 35.17 | 22.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 22.25 | 11.67 | 22.25 |
October | 0.17 | 20.52 | 0.17 | 20.52 | 0.67 | 21.43 | 0.67 | 21.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 20.33 | 2.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 3.50 | 20.36 | 3.50 | 20.36 | 148.00 | 22.26 | 148.00 | 22.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.53 | 2.83 | 20.53 | 56.83 | 22.49 | 56.83 | 22.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 22.49 | 13.50 | 22.49 |
February | 0.33 | 20.53 | 0.33 | 20.53 | 5.17 | 21.77 | 5.17 | 21.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.04 | 4.33 | 22.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.94 | 1.83 | 21.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 21.95 | 15.00 | 21.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 21.95 | 15.83 | 21.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 22.14 | 18.83 | 22.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.17 | 21.83 | 22.17 |
October | 0.17 | 20.50 | 0.17 | 20.50 | 18.17 | 22.70 | 18.17 | 22.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 22.63 | 30.33 | 22.63 |
December | 1.00 | 20.40 | 1.00 | 20.40 | 1.50 | 21.00 | 1.50 | 21.24 |
Annual Sum or Average | 1.50 | 20.44 | 1.50 | 20.44 | 146.67 | 22.26 | 146.67 | 22.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.00 | 0.33 | 21.24 |
Maximum of Months | 1.00 | 20.53 | 1.00 | 20.53 | 30.33 | 22.70 | 30.33 | 22.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.06 | 2.17 | 25.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.17 | 3.50 | 25.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.91 | 1.00 | 24.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 24.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.00 | 25.07 | 7.00 | 25.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.17 | 3.50 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 626.17 | 23.81 | 0.00 | 23.81 | 0.00 | 23.81 |
February | 657.50 | 23.66 | 0.00 | 23.66 | 0.00 | 23.66 |
March | 740.83 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
April | 702.50 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
May | 702.67 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
June | 489.17 | 23.60 | 111.67 | 23.65 | 66.00 | 23.67 |
July | 487.50 | 23.69 | 199.17 | 23.74 | 149.17 | 23.76 |
August | 319.67 | 23.85 | 248.67 | 23.90 | 91.00 | 23.91 |
September | 292.67 | 23.97 | 37.83 | 23.98 | 0.00 | 23.98 |
October | 441.00 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
November | 364.17 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
December | 689.00 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 6512.83 | 23.70 | 597.33 | 23.72 | 306.17 | 23.72 |
Minimum of Months | 292.67 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
Maximum of Months | 740.83 | 23.98 | 248.67 | 23.98 | 149.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 582.00 | 21.45 | 185.17 | 21.75 | 80.33 | 21.68 |
February | 532.33 | 21.46 | 226.00 | 21.62 | 152.00 | 21.51 |
March | 614.67 | 21.60 | 150.00 | 21.69 | 96.83 | 21.61 |
April | 659.83 | 21.47 | 123.00 | 21.44 | 110.00 | 21.39 |
May | 652.33 | 21.97 | 29.67 | 22.02 | 9.00 | 22.00 |
June | 309.00 | 22.70 | 318.17 | 23.24 | 42.50 | 23.23 |
July | 328.17 | 22.80 | 405.83 | 23.26 | 114.17 | 23.21 |
August | 301.50 | 22.75 | 398.50 | 23.30 | 77.17 | 23.27 |
September | 340.50 | 22.51 | 228.33 | 23.10 | 0.83 | 23.10 |
October | 551.83 | 21.72 | 212.33 | 21.99 | 93.00 | 21.88 |
November | 559.50 | 21.56 | 177.67 | 21.88 | 66.33 | 21.81 |
December | 632.50 | 21.37 | 277.83 | 21.46 | 214.83 | 21.37 |
Annual Sum or Average | 6064.17 | 21.81 | 2732.50 | 22.17 | 1057.00 | 22.09 |
Minimum of Months | 301.50 | 21.37 | 29.67 | 21.44 | 0.83 | 21.37 |
Maximum of Months | 659.83 | 22.80 | 405.83 | 23.30 | 214.83 | 23.27 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 702.00 | 22.91 | 2.67 | 22.90 | 2.67 | 22.90 |
February | 638.17 | 22.71 | 11.00 | 22.68 | 11.00 | 22.66 |
March | 720.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
April | 669.33 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
May | 514.67 | 23.28 | 34.33 | 23.32 | 0.00 | 23.32 |
June | 150.00 | 23.80 | 287.50 | 23.89 | 77.67 | 23.90 |
July | 207.50 | 23.83 | 345.83 | 23.88 | 157.00 | 23.88 |
August | 163.50 | 23.85 | 392.33 | 23.93 | 107.17 | 23.93 |
September | 205.83 | 23.65 | 115.00 | 23.77 | 1.67 | 23.77 |
October | 624.00 | 23.16 | 1.17 | 23.16 | 0.00 | 23.16 |
November | 659.50 | 22.96 | 0.50 | 22.97 | 0.00 | 22.97 |
December | 739.83 | 22.59 | 32.83 | 22.52 | 32.83 | 22.46 |
Annual Sum or Average | 5995.17 | 23.00 | 1223.17 | 23.14 | 390.00 | 23.16 |
Minimum of Months | 150.00 | 22.59 | 0.00 | 22.52 | 0.00 | 22.46 |
Maximum of Months | 739.83 | 23.85 | 392.33 | 23.93 | 157.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.53 | 48.83 | 21.50 | 48.83 | 21.47 |
February | 672.00 | 21.44 | 119.17 | 21.37 | 119.17 | 21.32 |
March | 744.00 | 21.76 | 18.50 | 21.74 | 18.50 | 21.72 |
April | 720.00 | 21.81 | 7.67 | 21.80 | 7.67 | 21.80 |
May | 740.83 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
June | 342.50 | 23.78 | 122.33 | 23.81 | 15.00 | 23.81 |
July | 299.50 | 23.84 | 214.50 | 23.85 | 85.67 | 23.84 |
August | 311.50 | 23.78 | 169.00 | 23.83 | 41.33 | 23.83 |
September | 549.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
October | 744.00 | 22.37 | 18.33 | 22.33 | 18.33 | 22.30 |
November | 720.00 | 21.74 | 35.50 | 21.71 | 35.50 | 21.68 |
December | 744.00 | 21.40 | 196.17 | 21.31 | 196.17 | 21.26 |
Annual Sum or Average | 7331.33 | 22.25 | 950.00 | 22.28 | 586.17 | 22.24 |
Minimum of Months | 299.50 | 21.40 | 0.00 | 21.31 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 23.84 | 214.50 | 23.85 | 196.17 | 23.84 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.34 | 64.83 | 21.31 | 64.83 | 21.29 |
February | 672.00 | 21.29 | 145.17 | 21.24 | 145.17 | 21.20 |
March | 744.00 | 21.56 | 31.67 | 21.53 | 31.67 | 21.51 |
April | 720.00 | 21.58 | 18.00 | 21.57 | 18.00 | 21.55 |
May | 744.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
June | 444.17 | 23.66 | 75.17 | 23.68 | 21.67 | 23.68 |
July | 390.50 | 23.71 | 186.17 | 23.72 | 94.17 | 23.69 |
August | 440.00 | 23.63 | 116.67 | 23.66 | 51.83 | 23.66 |
September | 649.83 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
October | 744.00 | 22.10 | 27.17 | 22.06 | 27.17 | 22.02 |
November | 720.00 | 21.52 | 46.67 | 21.49 | 46.67 | 21.46 |
December | 744.00 | 21.25 | 215.33 | 21.19 | 215.33 | 21.16 |
Annual Sum or Average | 7756.50 | 22.13 | 926.83 | 22.13 | 716.50 | 22.09 |
Minimum of Months | 390.50 | 21.25 | 0.00 | 21.19 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 23.71 | 215.33 | 23.72 | 215.33 | 23.69 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.17 | 23.60 | 649.67 | 23.73 | 170.50 | 23.78 |
February | 189.17 | 23.47 | 574.83 | 23.71 | 148.17 | 23.76 |
March | 197.17 | 23.66 | 644.00 | 23.76 | 169.00 | 23.80 |
April | 206.00 | 23.77 | 639.00 | 23.77 | 186.83 | 23.81 |
May | 268.67 | 23.95 | 696.00 | 23.81 | 262.50 | 23.85 |
June | 370.67 | 23.98 | 711.17 | 23.80 | 370.67 | 23.85 |
July | 421.00 | 23.94 | 740.50 | 23.79 | 421.00 | 23.83 |
August | 410.83 | 23.93 | 734.00 | 23.78 | 410.83 | 23.82 |
September | 282.67 | 23.98 | 686.17 | 23.82 | 280.33 | 23.86 |
October | 215.67 | 23.82 | 669.00 | 23.77 | 199.67 | 23.81 |
November | 205.67 | 23.66 | 635.50 | 23.74 | 176.67 | 23.79 |
December | 204.00 | 23.30 | 585.33 | 23.69 | 145.17 | 23.74 |
Annual Sum or Average | 3175.67 | 23.80 | 7965.17 | 23.77 | 2941.33 | 23.81 |
Minimum of Months | 189.17 | 23.30 | 574.83 | 23.69 | 145.17 | 23.74 |
Maximum of Months | 421.00 | 23.98 | 740.50 | 23.82 | 421.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.50 | 22.63 | 187.83 | 22.98 | 15.67 | 22.93 |
February | 392.50 | 22.39 | 193.17 | 22.69 | 44.00 | 22.57 |
March | 439.83 | 22.34 | 130.17 | 22.66 | 11.83 | 22.62 |
April | 484.33 | 22.28 | 97.50 | 22.52 | 8.17 | 22.50 |
May | 263.17 | 22.93 | 218.17 | 23.38 | 10.83 | 23.39 |
June | 158.33 | 23.86 | 616.50 | 23.89 | 150.17 | 23.89 |
July | 200.67 | 23.81 | 667.00 | 23.89 | 193.00 | 23.88 |
August | 180.67 | 23.88 | 649.33 | 23.92 | 173.33 | 23.92 |
September | 73.17 | 23.13 | 483.83 | 23.86 | 4.33 | 23.86 |
October | 305.17 | 22.31 | 240.00 | 22.91 | 25.67 | 22.82 |
November | 353.33 | 22.50 | 195.83 | 22.99 | 8.83 | 22.95 |
December | 525.33 | 22.37 | 188.00 | 22.47 | 79.17 | 22.32 |
Annual Sum or Average | 3798.00 | 22.66 | 3867.33 | 23.23 | 725.00 | 23.22 |
Minimum of Months | 73.17 | 22.28 | 97.50 | 22.47 | 4.33 | 22.32 |
Maximum of Months | 525.33 | 23.88 | 667.00 | 23.92 | 193.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.50 | 23.17 | 4.00 | 23.18 | 0.00 | 23.18 |
February | 428.50 | 22.97 | 0.33 | 22.97 | 0.00 | 22.97 |
March | 514.17 | 23.06 | 1.83 | 23.06 | 0.00 | 23.06 |
April | 511.83 | 22.98 | 30.00 | 23.04 | 0.00 | 23.04 |
May | 270.33 | 23.32 | 146.00 | 23.55 | 4.83 | 23.55 |
June | 138.17 | 23.91 | 436.50 | 23.93 | 129.67 | 23.93 |
July | 182.17 | 23.91 | 499.33 | 23.94 | 181.83 | 23.93 |
August | 159.00 | 23.96 | 520.00 | 23.95 | 152.67 | 23.96 |
September | 38.17 | 23.48 | 255.67 | 23.91 | 2.50 | 23.91 |
October | 261.83 | 22.91 | 31.50 | 23.03 | 0.00 | 23.03 |
November | 347.67 | 23.08 | 13.67 | 23.12 | 0.00 | 23.12 |
December | 573.67 | 22.94 | 9.00 | 22.91 | 9.00 | 22.88 |
Annual Sum or Average | 3848.00 | 23.16 | 1947.83 | 23.42 | 480.50 | 23.45 |
Minimum of Months | 38.17 | 22.91 | 0.33 | 22.91 | 0.00 | 22.88 |
Maximum of Months | 573.67 | 23.96 | 520.00 | 23.95 | 181.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.67 | 21.32 | 158.67 | 21.22 | 158.67 | 21.16 |
February | 657.83 | 21.24 | 238.33 | 21.11 | 238.33 | 21.03 |
March | 729.00 | 21.25 | 185.83 | 21.11 | 185.83 | 21.02 |
April | 714.67 | 21.26 | 155.50 | 21.13 | 155.50 | 21.05 |
May | 710.50 | 21.57 | 9.83 | 21.57 | 7.33 | 21.57 |
June | 566.33 | 21.43 | 61.17 | 21.59 | 5.83 | 21.60 |
July | 598.17 | 21.41 | 85.00 | 21.56 | 37.83 | 21.57 |
August | 577.17 | 21.38 | 72.83 | 21.56 | 13.17 | 21.56 |
September | 614.83 | 21.48 | 26.33 | 21.55 | 0.83 | 21.54 |
October | 703.83 | 21.30 | 115.00 | 21.19 | 111.17 | 21.10 |
November | 694.33 | 21.30 | 150.50 | 21.19 | 150.50 | 21.12 |
December | 740.33 | 21.15 | 379.33 | 21.01 | 379.33 | 20.95 |
Annual Sum or Average | 8036.67 | 21.34 | 1638.33 | 21.28 | 1444.33 | 21.21 |
Minimum of Months | 566.33 | 21.15 | 9.83 | 21.01 | 0.83 | 20.95 |
Maximum of Months | 740.33 | 21.57 | 379.33 | 21.59 | 379.33 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 351.50 | 20.83 | 351.50 | 20.77 |
February | 672.00 | 20.93 | 355.67 | 20.82 | 355.67 | 20.76 |
March | 722.50 | 21.12 | 285.00 | 21.04 | 272.33 | 20.94 |
April | 707.00 | 21.21 | 187.33 | 21.13 | 177.50 | 21.02 |
May | 661.50 | 21.77 | 41.67 | 21.92 | 9.17 | 21.93 |
June | 494.33 | 21.85 | 140.00 | 22.35 | 36.83 | 22.45 |
July | 543.00 | 21.95 | 162.17 | 22.41 | 80.00 | 22.57 |
August | 542.17 | 21.92 | 119.17 | 22.34 | 44.00 | 22.47 |
September | 589.33 | 21.89 | 54.00 | 22.14 | 1.50 | 22.15 |
October | 713.83 | 21.28 | 139.67 | 21.20 | 130.00 | 21.10 |
November | 719.83 | 21.07 | 253.00 | 20.94 | 253.00 | 20.87 |
December | 744.00 | 20.84 | 567.17 | 20.76 | 567.17 | 20.73 |
Annual Sum or Average | 7853.50 | 21.35 | 2656.33 | 21.35 | 2278.67 | 21.26 |
Minimum of Months | 494.33 | 20.84 | 41.67 | 20.76 | 1.50 | 20.73 |
Maximum of Months | 744.00 | 21.95 | 567.17 | 22.41 | 567.17 | 22.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 232.83 | 20.90 | 232.83 | 20.86 |
February | 672.00 | 20.95 | 307.67 | 20.88 | 307.67 | 20.84 |
March | 744.00 | 21.18 | 101.50 | 21.12 | 101.50 | 21.08 |
April | 720.00 | 21.29 | 29.00 | 21.26 | 29.00 | 21.23 |
May | 743.83 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
June | 699.83 | 22.14 | 30.83 | 22.20 | 24.17 | 22.24 |
July | 725.67 | 22.21 | 65.17 | 22.31 | 61.00 | 22.39 |
August | 731.50 | 22.10 | 34.33 | 22.16 | 27.50 | 22.20 |
September | 719.83 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
October | 744.00 | 21.28 | 60.67 | 21.22 | 60.67 | 21.17 |
November | 720.00 | 21.06 | 127.17 | 20.99 | 127.17 | 20.94 |
December | 744.00 | 20.91 | 390.67 | 20.84 | 390.67 | 20.80 |
Annual Sum or Average | 8708.67 | 21.49 | 1379.83 | 21.42 | 1362.17 | 21.35 |
Minimum of Months | 672.00 | 20.91 | 0.00 | 20.84 | 0.00 | 20.80 |
Maximum of Months | 744.00 | 22.21 | 390.67 | 22.31 | 390.67 | 22.39 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 167.17 | 21.28 | 167.17 | 21.21 |
February | 669.33 | 21.32 | 250.83 | 21.17 | 250.83 | 21.09 |
March | 734.33 | 21.34 | 186.83 | 21.19 | 186.83 | 21.09 |
April | 711.33 | 21.34 | 151.00 | 21.22 | 149.83 | 21.12 |
May | 711.67 | 21.64 | 6.00 | 21.63 | 6.00 | 21.63 |
June | 532.67 | 21.30 | 58.17 | 21.50 | 1.50 | 21.50 |
July | 549.83 | 21.30 | 97.33 | 21.54 | 25.67 | 21.55 |
August | 540.00 | 21.28 | 92.33 | 21.56 | 3.67 | 21.56 |
September | 590.17 | 21.44 | 14.17 | 21.48 | 0.00 | 21.48 |
October | 709.17 | 21.36 | 111.00 | 21.24 | 110.00 | 21.15 |
November | 717.17 | 21.38 | 150.67 | 21.26 | 150.67 | 21.18 |
December | 744.00 | 21.18 | 385.17 | 21.04 | 385.17 | 20.97 |
Annual Sum or Average | 7953.67 | 21.36 | 1670.67 | 21.31 | 1437.33 | 21.23 |
Minimum of Months | 532.67 | 21.18 | 6.00 | 21.04 | 0.00 | 20.97 |
Maximum of Months | 744.00 | 21.64 | 385.17 | 21.63 | 385.17 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 373.33 | 20.81 | 373.33 | 20.76 |
February | 672.00 | 20.95 | 349.17 | 20.84 | 349.17 | 20.78 |
March | 744.00 | 21.27 | 250.33 | 21.12 | 250.33 | 21.03 |
April | 716.00 | 21.34 | 181.67 | 21.20 | 180.67 | 21.10 |
May | 694.50 | 21.92 | 19.33 | 21.97 | 9.50 | 21.97 |
June | 455.00 | 21.97 | 180.83 | 22.74 | 56.50 | 22.99 |
July | 472.00 | 21.97 | 228.50 | 22.73 | 84.50 | 22.93 |
August | 479.67 | 21.92 | 161.67 | 22.58 | 52.00 | 22.80 |
September | 580.83 | 21.95 | 36.33 | 22.13 | 1.17 | 22.14 |
October | 741.83 | 21.41 | 128.67 | 21.28 | 128.00 | 21.18 |
November | 720.00 | 21.01 | 278.17 | 20.90 | 278.17 | 20.83 |
December | 744.00 | 20.79 | 564.67 | 20.73 | 564.67 | 20.71 |
Annual Sum or Average | 7763.83 | 21.39 | 2752.67 | 21.42 | 2328.00 | 21.35 |
Minimum of Months | 455.00 | 20.79 | 19.33 | 20.73 | 1.17 | 20.71 |
Maximum of Months | 744.00 | 21.97 | 564.67 | 22.74 | 564.67 | 22.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.51 | 28.33 | 21.49 | 28.33 | 21.48 |
February | 672.00 | 21.48 | 62.00 | 21.44 | 62.00 | 21.40 |
March | 744.00 | 21.77 | 1.50 | 21.77 | 1.50 | 21.76 |
April | 720.00 | 21.61 | 3.67 | 21.61 | 3.67 | 21.60 |
May | 744.00 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
June | 470.67 | 23.67 | 128.33 | 23.70 | 88.00 | 23.70 |
July | 420.83 | 23.79 | 244.50 | 23.79 | 157.00 | 23.78 |
August | 371.17 | 23.78 | 178.00 | 23.79 | 109.83 | 23.79 |
September | 546.33 | 23.52 | 1.83 | 23.52 | 0.00 | 23.52 |
October | 744.00 | 22.40 | 22.50 | 22.36 | 22.50 | 22.32 |
November | 720.00 | 21.67 | 21.00 | 21.65 | 21.00 | 21.63 |
December | 744.00 | 21.27 | 172.00 | 21.22 | 172.00 | 21.18 |
Annual Sum or Average | 7641.00 | 22.24 | 863.67 | 22.30 | 665.83 | 22.31 |
Minimum of Months | 371.17 | 21.27 | 0.00 | 21.22 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.79 | 244.50 | 23.79 | 172.00 | 23.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 727.00 | 21.23 | 284.33 | 21.11 | 284.33 | 21.05 |
February | 655.17 | 21.17 | 302.67 | 21.04 | 302.67 | 20.98 |
March | 720.50 | 21.17 | 292.17 | 21.04 | 291.67 | 20.96 |
April | 705.67 | 21.17 | 220.50 | 21.02 | 220.50 | 20.93 |
May | 692.50 | 21.51 | 29.33 | 21.51 | 22.83 | 21.50 |
June | 537.50 | 21.36 | 108.00 | 21.63 | 18.50 | 21.62 |
July | 579.50 | 21.37 | 134.17 | 21.58 | 59.33 | 21.58 |
August | 560.50 | 21.33 | 140.83 | 21.60 | 43.83 | 21.58 |
September | 601.00 | 21.42 | 49.33 | 21.53 | 9.17 | 21.52 |
October | 698.17 | 21.23 | 166.67 | 21.12 | 157.33 | 21.02 |
November | 689.50 | 21.23 | 230.67 | 21.10 | 230.67 | 21.02 |
December | 737.33 | 21.06 | 481.33 | 20.93 | 481.33 | 20.88 |
Annual Sum or Average | 7904.33 | 21.26 | 2440.00 | 21.22 | 2122.17 | 21.14 |
Minimum of Months | 537.50 | 21.06 | 29.33 | 20.93 | 9.17 | 20.88 |
Maximum of Months | 737.33 | 21.51 | 481.33 | 21.63 | 481.33 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 510.33 | 20.75 | 510.33 | 20.71 |
February | 672.00 | 20.86 | 458.00 | 20.77 | 458.00 | 20.72 |
March | 721.67 | 21.07 | 403.00 | 21.00 | 388.83 | 20.92 |
April | 705.17 | 21.17 | 262.17 | 21.08 | 252.50 | 20.98 |
May | 637.00 | 21.72 | 78.33 | 21.95 | 29.83 | 21.95 |
June | 465.50 | 21.81 | 176.00 | 22.39 | 42.17 | 22.51 |
July | 529.67 | 21.94 | 201.67 | 22.42 | 100.83 | 22.56 |
August | 521.83 | 21.89 | 172.50 | 22.36 | 70.17 | 22.48 |
September | 582.67 | 21.85 | 75.50 | 22.14 | 16.17 | 22.14 |
October | 706.33 | 21.19 | 228.17 | 21.12 | 213.17 | 21.01 |
November | 719.17 | 20.98 | 389.33 | 20.86 | 389.33 | 20.80 |
December | 744.00 | 20.75 | 648.67 | 20.70 | 648.67 | 20.68 |
Annual Sum or Average | 7749.00 | 21.28 | 3603.67 | 21.29 | 3120.00 | 21.20 |
Minimum of Months | 465.50 | 20.75 | 75.50 | 20.70 | 16.17 | 20.68 |
Maximum of Months | 744.00 | 21.94 | 648.67 | 22.42 | 648.67 | 22.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 638.67 | 21.29 | 126.17 | 21.34 | 86.83 | 21.28 |
February | 587.00 | 21.22 | 180.50 | 21.17 | 161.33 | 21.09 |
March | 680.17 | 21.22 | 144.50 | 21.10 | 141.50 | 21.01 |
April | 691.50 | 21.27 | 151.00 | 21.15 | 151.00 | 21.07 |
May | 706.67 | 21.56 | 8.17 | 21.56 | 8.17 | 21.55 |
June | 606.50 | 21.45 | 25.67 | 21.50 | 10.17 | 21.50 |
July | 615.00 | 21.42 | 77.33 | 21.52 | 46.83 | 21.53 |
August | 594.50 | 21.37 | 100.83 | 21.59 | 22.00 | 21.58 |
September | 593.00 | 21.42 | 56.83 | 21.59 | 0.83 | 21.59 |
October | 640.17 | 21.19 | 148.83 | 21.22 | 103.67 | 21.13 |
November | 612.67 | 21.30 | 138.00 | 21.38 | 86.50 | 21.31 |
December | 675.50 | 21.28 | 234.00 | 21.23 | 213.50 | 21.16 |
Annual Sum or Average | 7641.33 | 21.33 | 1391.83 | 21.35 | 1032.33 | 21.29 |
Minimum of Months | 587.00 | 21.19 | 8.17 | 21.10 | 0.83 | 21.01 |
Maximum of Months | 706.67 | 21.56 | 234.00 | 21.59 | 213.50 | 21.59 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.00 | 23.49 | 26.33 | 23.52 | 0.00 | 23.52 |
February | 350.00 | 23.49 | 21.33 | 23.52 | 0.00 | 23.52 |
March | 230.50 | 23.49 | 30.83 | 23.55 | 0.00 | 23.55 |
April | 156.17 | 23.52 | 149.83 | 23.75 | 0.00 | 23.75 |
May | 18.83 | 23.64 | 463.33 | 23.98 | 2.83 | 23.98 |
June | 132.33 | 24.00 | 679.67 | 24.00 | 132.33 | 24.00 |
July | 189.33 | 24.00 | 724.50 | 24.00 | 189.33 | 24.00 |
August | 158.17 | 24.00 | 702.33 | 24.00 | 158.17 | 24.00 |
September | 8.17 | 23.71 | 440.50 | 23.99 | 2.83 | 23.99 |
October | 142.17 | 23.40 | 112.17 | 23.66 | 0.00 | 23.66 |
November | 241.50 | 23.43 | 37.17 | 23.50 | 0.00 | 23.50 |
December | 479.00 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
Annual Sum or Average | 2466.17 | 23.56 | 3388.00 | 23.81 | 485.50 | 23.83 |
Minimum of Months | 8.17 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
Maximum of Months | 479.00 | 24.00 | 724.50 | 24.00 | 189.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.83 | 23.58 | 132.00 | 23.76 | 0.00 | 23.76 |
February | 181.50 | 23.54 | 77.50 | 23.68 | 0.00 | 23.68 |
March | 97.00 | 23.59 | 104.67 | 23.80 | 0.00 | 23.80 |
April | 39.50 | 23.51 | 263.00 | 23.93 | 0.00 | 23.93 |
May | 3.00 | 23.93 | 546.50 | 24.00 | 2.50 | 24.00 |
June | 127.67 | 24.00 | 706.00 | 24.00 | 127.67 | 24.00 |
July | 183.83 | 24.00 | 732.33 | 24.00 | 183.83 | 24.00 |
August | 151.33 | 24.00 | 729.33 | 24.00 | 151.33 | 24.00 |
September | 2.83 | 23.99 | 540.00 | 24.00 | 2.83 | 24.00 |
October | 49.50 | 23.28 | 226.00 | 23.86 | 0.00 | 23.86 |
November | 95.00 | 23.45 | 149.50 | 23.78 | 0.00 | 23.78 |
December | 295.00 | 23.46 | 1.50 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 1399.00 | 23.67 | 4208.33 | 23.91 | 468.17 | 23.92 |
Minimum of Months | 2.83 | 23.28 | 1.50 | 23.46 | 0.00 | 23.46 |
Maximum of Months | 295.00 | 24.00 | 732.33 | 24.00 | 183.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 23.96 | 707.17 | 23.95 | 489.33 | 23.96 |
February | 445.17 | 23.95 | 623.50 | 23.95 | 433.83 | 23.96 |
March | 502.33 | 23.98 | 724.00 | 23.96 | 497.83 | 23.97 |
April | 494.50 | 23.99 | 705.50 | 23.97 | 494.50 | 23.97 |
May | 539.17 | 23.99 | 743.83 | 23.98 | 539.17 | 23.99 |
June | 560.67 | 24.00 | 720.00 | 24.00 | 560.67 | 24.00 |
July | 603.50 | 24.00 | 744.00 | 24.00 | 603.50 | 24.00 |
August | 606.83 | 23.99 | 744.00 | 23.99 | 606.83 | 23.99 |
September | 522.67 | 23.99 | 720.00 | 23.99 | 522.67 | 23.99 |
October | 504.17 | 23.99 | 734.83 | 23.97 | 503.00 | 23.98 |
November | 488.67 | 23.97 | 695.17 | 23.95 | 483.50 | 23.96 |
December | 477.83 | 23.89 | 671.67 | 23.93 | 447.50 | 23.94 |
Annual Sum or Average | 6245.17 | 23.98 | 8533.67 | 23.97 | 6182.33 | 23.98 |
Minimum of Months | 445.17 | 23.89 | 623.50 | 23.93 | 433.83 | 23.94 |
Maximum of Months | 606.83 | 24.00 | 744.00 | 24.00 | 606.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 67.83 | 21.35 | 67.83 | 21.33 |
February | 672.00 | 21.41 | 108.00 | 21.35 | 108.00 | 21.31 |
March | 744.00 | 21.72 | 32.33 | 21.69 | 32.33 | 21.66 |
April | 720.00 | 21.63 | 11.50 | 21.62 | 11.50 | 21.61 |
May | 725.17 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
June | 241.50 | 23.44 | 168.33 | 23.61 | 37.50 | 23.61 |
July | 262.83 | 23.50 | 287.83 | 23.64 | 112.67 | 23.62 |
August | 265.17 | 23.44 | 239.50 | 23.62 | 76.00 | 23.61 |
September | 469.67 | 23.14 | 15.67 | 23.16 | 0.00 | 23.16 |
October | 736.00 | 22.14 | 37.50 | 22.08 | 37.50 | 22.03 |
November | 720.00 | 21.58 | 44.00 | 21.55 | 44.00 | 21.52 |
December | 744.00 | 21.25 | 207.67 | 21.20 | 207.67 | 21.16 |
Annual Sum or Average | 7044.33 | 22.00 | 1220.17 | 22.10 | 735.00 | 22.07 |
Minimum of Months | 241.50 | 21.25 | 0.00 | 21.20 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 23.50 | 287.83 | 23.64 | 207.67 | 23.62 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.83706 | 23.87556 | 0.17510 | 5.73931 |
February | 672.00000 | 23.67072 | 22.56941 | 0.12008 | 5.44230 |
March | 744.00000 | 23.42889 | 22.14738 | 0.05491 | 5.23263 |
April | 720.00000 | 23.49403 | 26.18016 | 0.09727 | 5.38469 |
May | 744.00000 | 23.45264 | 30.21004 | -0.8578 | 20.78825 |
June | 720.00000 | 23.67811 | 37.76776 | -0.7183 | 16.15631 |
July | 744.00000 | 23.75356 | 40.09861 | -0.6734 | 14.82603 |
August | 744.00000 | 23.89715 | 39.06246 | -0.6138 | 13.12625 |
September | 720.00000 | 23.98254 | 27.90980 | -0.6420 | 13.76002 |
October | 744.00000 | 23.99003 | 23.18118 | 0.23346 | 6.18739 |
November | 720.00000 | 23.98799 | 24.13538 | 0.23722 | 6.21755 |
December | 744.00000 | 23.97320 | 18.05842 | 0.18499 | 5.75066 |
Annual Sum or Average | 8760.00000 | 23.76265 | 27.96542 | -0.2022 | 9.91536 |
Minimum of Months | 672.00000 | 23.42889 | 18.05842 | -0.8578 | 5.23263 |
Maximum of Months | 744.00000 | 23.99003 | 40.09861 | 0.23722 | 20.78825 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.99566 | 24.66093 | -0.1885 | 8.92951 |
February | 672.00000 | 21.98151 | 22.81504 | -0.2275 | 9.50612 |
March | 744.00000 | 22.00895 | 22.23823 | -0.2240 | 8.86264 |
April | 720.00000 | 21.67123 | 27.13457 | -0.2979 | 8.73838 |
May | 744.00000 | 22.18773 | 30.69327 | -1.1403 | 34.32988 |
June | 720.00000 | 23.33302 | 37.04582 | -0.6431 | 15.18900 |
July | 744.00000 | 23.37477 | 39.61990 | -0.6087 | 14.23367 |
August | 744.00000 | 23.38930 | 39.06362 | -0.5881 | 13.93185 |
September | 720.00000 | 23.24457 | 28.31458 | -0.7074 | 18.51239 |
October | 744.00000 | 22.29924 | 24.70596 | -0.1011 | 8.48683 |
November | 720.00000 | 22.09953 | 25.88508 | -0.1499 | 8.70222 |
December | 744.00000 | 21.76162 | 19.05385 | -0.3225 | 10.34807 |
Annual Sum or Average | 8760.00000 | 22.44786 | 28.46940 | -0.4348 | 13.35131 |
Minimum of Months | 672.00000 | 21.67123 | 19.05385 | -1.1403 | 8.48683 |
Maximum of Months | 744.00000 | 23.38930 | 39.61990 | -0.1011 | 34.32988 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.96999 | 25.76085 | 0.00193 | 5.60410 |
February | 672.00000 | 22.77739 | 24.20670 | -0.0583 | 6.03521 |
March | 744.00000 | 22.92558 | 23.46830 | -0.0238 | 5.73225 |
April | 720.00000 | 22.85811 | 27.71684 | -0.0162 | 5.78053 |
May | 744.00000 | 23.47060 | 30.81507 | -0.7851 | 18.63116 |
June | 720.00000 | 23.89836 | 37.50315 | -0.5543 | 11.62447 |
July | 744.00000 | 23.91289 | 40.04139 | -0.5330 | 11.11850 |
August | 744.00000 | 23.91333 | 39.64804 | -0.5344 | 11.17799 |
September | 720.00000 | 23.87519 | 29.27007 | -0.6257 | 13.53006 |
October | 744.00000 | 23.28795 | 25.66463 | 0.08807 | 5.93541 |
November | 720.00000 | 23.04882 | 26.94749 | 0.03072 | 5.71577 |
December | 744.00000 | 22.59669 | 20.64576 | -0.1286 | 6.41311 |
Annual Sum or Average | 8760.00000 | 23.29745 | 29.33775 | -0.2629 | 8.96301 |
Minimum of Months | 672.00000 | 22.59669 | 20.64576 | -0.7851 | 5.60410 |
Maximum of Months | 744.00000 | 23.91333 | 40.04139 | 0.08807 | 18.63116 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54840 | 20.56732 | 0.70967 | 17.38541 |
February | 672.00000 | 23.52592 | 18.91953 | 0.68680 | 16.81870 |
March | 744.00000 | 23.55648 | 18.09427 | 0.70812 | 17.28519 |
April | 720.00000 | 23.57343 | 22.20471 | 0.73862 | 18.27214 |
May | 744.00000 | 23.64609 | 25.97019 | 0.15632 | 8.82898 |
June | 720.00000 | 23.69142 | 33.86878 | 0.28229 | 9.83965 |
July | 744.00000 | 23.69996 | 36.48103 | 0.29879 | 9.90545 |
August | 744.00000 | 23.67826 | 36.02613 | 0.28822 | 9.81787 |
September | 720.00000 | 23.67537 | 25.39418 | 0.19411 | 8.89718 |
October | 744.00000 | 23.57745 | 20.71902 | 0.74319 | 18.29752 |
November | 720.00000 | 23.55103 | 21.76346 | 0.72647 | 17.89897 |
December | 744.00000 | 23.49947 | 15.36032 | 0.64493 | 15.71148 |
Annual Sum or Average | 8760.00000 | 23.60234 | 24.64780 | 0.51370 | 14.06123 |
Minimum of Months | 672.00000 | 23.49947 | 15.36032 | 0.15632 | 8.82898 |
Maximum of Months | 744.00000 | 23.69996 | 36.48103 | 0.74319 | 18.29752 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.19508 | 28.57901 | 0.16857 | 7.67340 |
February | 672.00000 | 23.03411 | 27.05441 | 0.10018 | 8.10426 |
March | 744.00000 | 23.00080 | 26.51599 | 0.08577 | 7.44497 |
April | 720.00000 | 22.79896 | 31.13840 | 0.03724 | 6.98489 |
May | 744.00000 | 23.47172 | 34.21864 | -0.6510 | 14.99879 |
June | 720.00000 | 23.86061 | 40.72625 | -0.3868 | 8.48545 |
July | 744.00000 | 23.87675 | 43.21068 | -0.3583 | 8.07650 |
August | 744.00000 | 23.89710 | 42.48789 | -0.3314 | 7.78531 |
September | 720.00000 | 23.86327 | 32.13845 | -0.4151 | 9.67491 |
October | 744.00000 | 23.27608 | 28.62825 | 0.20138 | 8.31864 |
November | 720.00000 | 23.22161 | 29.75167 | 0.18909 | 7.95246 |
December | 744.00000 | 22.83127 | 23.60105 | 0.01155 | 7.89707 |
Annual Sum or Average | 8760.00000 | 23.36247 | 32.36891 | -0.1138 | 8.62434 |
Minimum of Months | 672.00000 | 22.79896 | 23.60105 | -0.6510 | 6.98489 |
Maximum of Months | 744.00000 | 23.89710 | 43.21068 | 0.20138 | 14.99879 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50837 | 27.84577 | 0.17039 | 6.16726 |
February | 672.00000 | 23.32291 | 26.38539 | 0.10868 | 6.19205 |
March | 744.00000 | 23.34489 | 25.62606 | 0.11372 | 5.91813 |
April | 720.00000 | 23.26242 | 29.89530 | 0.11484 | 5.97892 |
May | 744.00000 | 23.68641 | 32.87173 | -0.6556 | 14.48088 |
June | 720.00000 | 23.90447 | 39.63871 | -0.4877 | 10.13241 |
July | 744.00000 | 23.92480 | 42.11569 | -0.4614 | 9.60957 |
August | 744.00000 | 23.94177 | 41.62150 | -0.4551 | 9.47304 |
September | 720.00000 | 23.94252 | 31.26649 | -0.5323 | 11.13067 |
October | 744.00000 | 23.59411 | 27.68522 | 0.20601 | 6.60903 |
November | 720.00000 | 23.53309 | 28.95458 | 0.18814 | 6.32597 |
December | 744.00000 | 23.17689 | 22.93518 | 0.04544 | 6.16459 |
Annual Sum or Average | 8760.00000 | 23.59674 | 31.43337 | -0.1386 | 8.19593 |
Minimum of Months | 672.00000 | 23.17689 | 22.93518 | -0.6556 | 5.91813 |
Maximum of Months | 744.00000 | 23.94252 | 42.11569 | 0.20601 | 14.48088 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35808 | 33.22257 | -0.4187 | 10.01757 |
February | 672.00000 | 21.28434 | 31.25759 | -0.4561 | 10.99480 |
March | 744.00000 | 21.29379 | 31.19775 | -0.4188 | 10.13162 |
April | 720.00000 | 21.27346 | 35.80336 | -0.4069 | 9.78469 |
May | 744.00000 | 21.65048 | 39.52004 | -1.3240 | 42.71929 |
June | 720.00000 | 21.80361 | 44.56458 | -1.1036 | 32.61034 |
July | 744.00000 | 21.77679 | 46.25346 | -1.1154 | 32.99486 |
August | 744.00000 | 21.79296 | 46.41207 | -1.1072 | 32.82831 |
September | 720.00000 | 21.73790 | 37.64120 | -1.2114 | 37.69341 |
October | 744.00000 | 21.40823 | 34.37749 | -0.3373 | 9.20614 |
November | 720.00000 | 21.37493 | 35.03272 | -0.3883 | 9.66527 |
December | 744.00000 | 21.16324 | 27.71687 | -0.5397 | 12.64001 |
Annual Sum or Average | 8760.00000 | 21.49427 | 36.94843 | -0.7375 | 21.00586 |
Minimum of Months | 672.00000 | 21.16324 | 27.71687 | -1.3240 | 9.20614 |
Maximum of Months | 744.00000 | 21.80361 | 46.41207 | -0.3373 | 42.71929 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94399 | 33.94347 | -0.5748 | 12.66414 |
February | 672.00000 | 20.93142 | 31.77479 | -0.5921 | 13.33771 |
March | 744.00000 | 21.25279 | 31.31787 | -0.4716 | 11.34630 |
April | 720.00000 | 21.29325 | 35.85478 | -0.4247 | 10.32353 |
May | 744.00000 | 22.04886 | 38.77372 | -1.2280 | 39.09311 |
June | 720.00000 | 22.42117 | 43.50763 | -0.9354 | 26.61778 |
July | 744.00000 | 22.42723 | 45.47378 | -0.9393 | 26.80444 |
August | 744.00000 | 22.39719 | 45.61933 | -0.9632 | 27.83980 |
September | 720.00000 | 22.29919 | 36.74480 | -1.1034 | 33.61233 |
October | 744.00000 | 21.42244 | 34.21608 | -0.3860 | 9.91150 |
November | 720.00000 | 21.06698 | 35.52232 | -0.5189 | 11.54823 |
December | 744.00000 | 20.83816 | 28.19830 | -0.6679 | 15.25050 |
Annual Sum or Average | 8760.00000 | 21.61575 | 36.77370 | -0.7348 | 19.90881 |
Minimum of Months | 672.00000 | 20.83816 | 28.19830 | -1.2280 | 9.91150 |
Maximum of Months | 744.00000 | 22.42723 | 45.61933 | -0.3860 | 39.09311 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97763 | 32.90590 | -0.5450 | 11.44679 |
February | 672.00000 | 20.95290 | 30.92156 | -0.5653 | 11.97510 |
March | 744.00000 | 21.18070 | 30.03071 | -0.4878 | 10.16683 |
April | 720.00000 | 21.28671 | 34.62913 | -0.4213 | 9.01612 |
May | 744.00000 | 21.81675 | 37.55024 | -1.3588 | 43.92549 |
June | 720.00000 | 22.19742 | 43.12620 | -1.1392 | 33.64942 |
July | 744.00000 | 22.25871 | 44.91457 | -1.1072 | 32.31795 |
August | 744.00000 | 22.13597 | 45.12979 | -1.1662 | 34.79324 |
September | 720.00000 | 21.99810 | 35.60799 | -1.2974 | 40.95728 |
October | 744.00000 | 21.27573 | 33.11772 | -0.4325 | 9.21669 |
November | 720.00000 | 21.05727 | 34.52545 | -0.5062 | 10.56455 |
December | 744.00000 | 20.91012 | 27.16358 | -0.6057 | 13.05067 |
Annual Sum or Average | 8760.00000 | 21.50710 | 35.82919 | -0.8042 | 21.81746 |
Minimum of Months | 672.00000 | 20.91012 | 27.16358 | -1.3588 | 9.01612 |
Maximum of Months | 744.00000 | 22.25871 | 45.12979 | -0.4213 | 43.92549 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38917 | 33.26524 | -0.4144 | 9.90937 |
February | 672.00000 | 21.33112 | 31.27636 | -0.4438 | 10.90927 |
March | 744.00000 | 21.36762 | 31.20669 | -0.3956 | 9.90555 |
April | 720.00000 | 21.36367 | 35.73068 | -0.3759 | 9.51781 |
May | 744.00000 | 21.70972 | 39.37890 | -1.2913 | 41.17609 |
June | 720.00000 | 21.81449 | 44.61028 | -1.0826 | 31.67270 |
July | 744.00000 | 21.81534 | 46.07959 | -1.0767 | 31.44227 |
August | 744.00000 | 21.80855 | 46.27890 | -1.0772 | 31.59829 |
September | 720.00000 | 21.77468 | 37.60357 | -1.1875 | 36.62066 |
October | 744.00000 | 21.45056 | 34.37646 | -0.3287 | 9.17372 |
November | 720.00000 | 21.38519 | 35.08803 | -0.3899 | 9.66340 |
December | 744.00000 | 21.17641 | 27.73689 | -0.5371 | 12.52291 |
Annual Sum or Average | 8760.00000 | 21.53329 | 36.91704 | -0.7185 | 20.40348 |
Minimum of Months | 672.00000 | 21.17641 | 27.73689 | -1.2913 | 9.17372 |
Maximum of Months | 744.00000 | 21.81534 | 46.27890 | -0.3287 | 41.17609 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90049 | 33.99472 | -0.5863 | 12.80008 |
February | 672.00000 | 20.95270 | 31.71338 | -0.5847 | 13.22730 |
March | 744.00000 | 21.27296 | 31.21940 | -0.4591 | 10.63859 |
April | 720.00000 | 21.35195 | 35.72277 | -0.4008 | 9.78764 |
May | 744.00000 | 22.05798 | 38.73016 | -1.2100 | 37.77457 |
June | 720.00000 | 22.63130 | 43.45963 | -0.8551 | 25.66744 |
July | 744.00000 | 22.63121 | 45.09568 | -0.8515 | 24.91991 |
August | 744.00000 | 22.56721 | 45.18592 | -0.8871 | 26.38779 |
September | 720.00000 | 22.32805 | 36.68181 | -1.0803 | 32.49021 |
October | 744.00000 | 21.41633 | 34.21917 | -0.3881 | 9.56853 |
November | 720.00000 | 21.01178 | 35.62158 | -0.5340 | 11.76872 |
December | 744.00000 | 20.79010 | 28.20895 | -0.6780 | 15.40303 |
Annual Sum or Average | 8760.00000 | 21.66327 | 36.68170 | -0.7105 | 19.24398 |
Minimum of Months | 672.00000 | 20.79010 | 28.20895 | -1.2100 | 9.56853 |
Maximum of Months | 744.00000 | 22.63130 | 45.18592 | -0.3881 | 37.77457 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.27884 | 33.74190 | -0.4723 | 11.24144 |
February | 672.00000 | 21.22543 | 31.71348 | -0.5035 | 12.19561 |
March | 744.00000 | 21.24045 | 31.69020 | -0.4575 | 11.15392 |
April | 720.00000 | 21.21911 | 36.40999 | -0.4404 | 10.74922 |
May | 744.00000 | 21.63248 | 39.97046 | -1.3432 | 43.92230 |
June | 720.00000 | 21.81502 | 44.93916 | -1.0953 | 32.69731 |
July | 744.00000 | 21.78022 | 46.73282 | -1.1140 | 33.27447 |
August | 744.00000 | 21.79895 | 47.10991 | -1.1034 | 33.11695 |
September | 720.00000 | 21.72238 | 37.92009 | -1.2323 | 39.03279 |
October | 744.00000 | 21.36055 | 34.89577 | -0.3771 | 10.15509 |
November | 720.00000 | 21.31437 | 35.58663 | -0.4333 | 10.73103 |
December | 744.00000 | 21.08122 | 28.10488 | -0.5978 | 14.24982 |
Annual Sum or Average | 8760.00000 | 21.45697 | 37.43364 | -0.7659 | 21.94061 |
Minimum of Months | 672.00000 | 21.08122 | 28.10488 | -1.3432 | 10.15509 |
Maximum of Months | 744.00000 | 21.81502 | 47.10991 | -0.3771 | 43.92230 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83970 | 34.56337 | -0.6385 | 14.37830 |
February | 672.00000 | 20.86243 | 32.29652 | -0.6459 | 14.82288 |
March | 744.00000 | 21.21242 | 31.81875 | -0.5093 | 12.60856 |
April | 720.00000 | 21.26324 | 36.46176 | -0.4534 | 11.38356 |
May | 744.00000 | 22.07659 | 39.15255 | -1.2294 | 39.90860 |
June | 720.00000 | 22.43355 | 43.73232 | -0.9213 | 26.69974 |
July | 744.00000 | 22.41887 | 45.77052 | -0.9363 | 27.24562 |
August | 744.00000 | 22.39702 | 46.19594 | -0.9563 | 28.28058 |
September | 720.00000 | 22.27746 | 37.04759 | -1.1220 | 35.02897 |
October | 744.00000 | 21.37885 | 34.80443 | -0.4276 | 11.07512 |
November | 720.00000 | 20.98817 | 36.15677 | -0.5728 | 12.92867 |
December | 744.00000 | 20.75235 | 28.63876 | -0.7300 | 17.16506 |
Annual Sum or Average | 8760.00000 | 21.57910 | 37.24803 | -0.7628 | 21.00489 |
Minimum of Months | 672.00000 | 20.75235 | 28.63876 | -1.2294 | 11.07512 |
Maximum of Months | 744.00000 | 22.43355 | 46.19594 | -0.4276 | 39.90860 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.58290 | 34.90920 | -0.2826 | 8.95516 |
February | 672.00000 | 21.48555 | 33.17943 | -0.3412 | 9.96479 |
March | 744.00000 | 21.40239 | 32.74239 | -0.3651 | 9.77247 |
April | 720.00000 | 21.34725 | 36.97651 | -0.3864 | 9.65043 |
May | 744.00000 | 21.65148 | 40.37517 | -1.3596 | 44.57957 |
June | 720.00000 | 21.74815 | 45.77653 | -1.1923 | 36.52050 |
July | 744.00000 | 21.75460 | 47.23162 | -1.1746 | 35.74141 |
August | 744.00000 | 21.75706 | 47.43373 | -1.1528 | 35.03167 |
September | 720.00000 | 21.75707 | 38.49925 | -1.2127 | 38.14959 |
October | 744.00000 | 21.49038 | 35.76330 | -0.2856 | 9.14860 |
November | 720.00000 | 21.60725 | 36.56872 | -0.2610 | 8.85061 |
December | 744.00000 | 21.46579 | 29.64913 | -0.3890 | 10.47481 |
Annual Sum or Average | 8760.00000 | 21.58803 | 38.28739 | -0.7025 | 21.47661 |
Minimum of Months | 672.00000 | 21.34725 | 29.64913 | -1.3596 | 8.85061 |
Maximum of Months | 744.00000 | 21.75707 | 47.43373 | -0.2610 | 44.57957 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.74223 | 28.76039 | 0.21920 | 6.31643 |
February | 672.00000 | 23.72674 | 27.19579 | 0.20210 | 6.22511 |
March | 744.00000 | 23.82969 | 25.82194 | 0.25074 | 6.50329 |
April | 720.00000 | 23.87822 | 29.66325 | 0.29812 | 7.07936 |
May | 744.00000 | 23.98318 | 32.51301 | -0.4580 | 9.55226 |
June | 720.00000 | 23.99672 | 39.61306 | -0.3208 | 7.26810 |
July | 744.00000 | 23.99651 | 42.17569 | -0.3041 | 7.06215 |
August | 744.00000 | 23.99614 | 41.80445 | -0.3193 | 7.25134 |
September | 720.00000 | 23.99071 | 31.75097 | -0.4283 | 9.00967 |
October | 744.00000 | 23.86550 | 28.16129 | 0.29316 | 7.04683 |
November | 720.00000 | 23.79310 | 29.70805 | 0.25277 | 6.60804 |
December | 744.00000 | 23.61390 | 23.96471 | 0.13877 | 6.03144 |
Annual Sum or Average | 8760.00000 | 23.86836 | 31.78846 | -0.0160 | 7.16694 |
Minimum of Months | 672.00000 | 23.61390 | 23.96471 | -0.4580 | 6.03144 |
Maximum of Months | 744.00000 | 23.99672 | 42.17569 | 0.29812 | 9.55226 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.87589 | 27.79752 | 0.29150 | 6.95692 |
February | 672.00000 | 23.86275 | 26.23759 | 0.27524 | 6.79290 |
March | 744.00000 | 23.92758 | 24.95624 | 0.31322 | 7.14053 |
April | 720.00000 | 23.95549 | 28.80494 | 0.35670 | 7.79395 |
May | 744.00000 | 23.99441 | 31.92118 | -0.4042 | 8.54233 |
June | 720.00000 | 23.99707 | 39.22726 | -0.2819 | 6.78449 |
July | 744.00000 | 23.99686 | 41.79483 | -0.2657 | 6.61288 |
August | 744.00000 | 23.99672 | 41.40552 | -0.2806 | 6.76860 |
September | 720.00000 | 23.99499 | 31.28303 | -0.3856 | 8.26130 |
October | 744.00000 | 23.93334 | 27.40044 | 0.34467 | 7.63175 |
November | 720.00000 | 23.89660 | 28.78473 | 0.31676 | 7.24932 |
December | 744.00000 | 23.77706 | 23.02976 | 0.21902 | 6.41676 |
Annual Sum or Average | 8760.00000 | 23.93435 | 31.08253 | 0.04012 | 7.24667 |
Minimum of Months | 672.00000 | 23.77706 | 23.02976 | -0.4042 | 6.41676 |
Maximum of Months | 744.00000 | 23.99707 | 41.79483 | 0.35670 | 8.54233 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.89297 | 26.41358 | 0.94654 | 25.89177 |
February | 672.00000 | 23.87354 | 24.85818 | 0.92822 | 25.31492 |
March | 744.00000 | 23.92130 | 23.91695 | 0.97052 | 26.73738 |
April | 720.00000 | 23.93462 | 27.83437 | 1.00499 | 28.12955 |
May | 744.00000 | 23.97916 | 31.36904 | 0.55045 | 15.27864 |
June | 720.00000 | 23.99580 | 38.95098 | 0.71236 | 19.55744 |
July | 744.00000 | 23.99943 | 41.43733 | 0.72514 | 19.92086 |
August | 744.00000 | 23.99471 | 40.95843 | 0.71433 | 19.42204 |
September | 720.00000 | 23.98794 | 30.89310 | 0.59508 | 16.36417 |
October | 744.00000 | 23.94767 | 26.46569 | 1.00716 | 28.11466 |
November | 720.00000 | 23.90747 | 27.54864 | 0.97124 | 26.81121 |
December | 744.00000 | 23.85008 | 21.64460 | 0.87368 | 23.38837 |
Annual Sum or Average | 8760.00000 | 23.94076 | 30.22251 | 0.83266 | 22.89330 |
Minimum of Months | 672.00000 | 23.85008 | 21.64460 | 0.55045 | 15.27864 |
Maximum of Months | 744.00000 | 23.99943 | 41.43733 | 1.00716 | 28.12955 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33880 | 24.28684 | -0.4267 | 9.06243 |
February | 672.00000 | 21.29230 | 22.36060 | -0.4579 | 9.66132 |
March | 744.00000 | 21.55648 | 21.53439 | -0.3905 | 8.60203 |
April | 720.00000 | 21.58141 | 25.99834 | -0.3562 | 8.05459 |
May | 744.00000 | 22.63130 | 28.81912 | -1.1227 | 32.04073 |
June | 720.00000 | 23.71797 | 35.19268 | -0.7017 | 15.52687 |
July | 744.00000 | 23.79944 | 37.56584 | -0.6565 | 14.20668 |
August | 744.00000 | 23.69572 | 37.47543 | -0.6958 | 15.38217 |
September | 720.00000 | 23.38091 | 27.07302 | -0.8743 | 21.81918 |
October | 744.00000 | 22.09822 | 23.85041 | -0.2408 | 6.74488 |
November | 720.00000 | 21.51905 | 25.49742 | -0.3736 | 8.25300 |
December | 744.00000 | 21.24867 | 18.37218 | -0.4968 | 10.41834 |
Annual Sum or Average | 8760.00000 | 22.32765 | 27.36430 | -0.5669 | 13.34329 |
Minimum of Months | 672.00000 | 21.24867 | 18.37218 | -1.1227 | 6.74488 |
Maximum of Months | 744.00000 | 23.79944 | 37.56584 | -0.2408 | 32.04073 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51316 | 27.42784 | -0.3788 | 8.29169 |
February | 672.00000 | 21.47784 | 25.54659 | -0.4054 | 8.82871 |
March | 744.00000 | 21.76692 | 24.69874 | -0.3351 | 7.93548 |
April | 720.00000 | 21.61094 | 29.29352 | -0.3455 | 7.85614 |
May | 744.00000 | 22.60295 | 32.14463 | -1.1341 | 32.59972 |
June | 720.00000 | 23.74458 | 38.48589 | -0.6908 | 15.22482 |
July | 744.00000 | 23.84995 | 40.74556 | -0.6380 | 13.66681 |
August | 744.00000 | 23.81560 | 40.58337 | -0.6522 | 14.07321 |
September | 720.00000 | 23.61216 | 30.14539 | -0.7943 | 18.82602 |
October | 744.00000 | 22.39865 | 26.89916 | -0.1653 | 6.36664 |
November | 720.00000 | 21.66844 | 28.65048 | -0.3342 | 7.72662 |
December | 744.00000 | 21.26870 | 21.73690 | -0.4814 | 10.05505 |
Annual Sum or Average | 8760.00000 | 22.44975 | 30.55859 | -0.5305 | 12.65441 |
Minimum of Months | 672.00000 | 21.26870 | 21.73690 | -1.1341 | 6.36664 |
Maximum of Months | 744.00000 | 23.84995 | 40.74556 | -0.1653 | 32.59972 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38602 | 25.42002 | -0.4043 | 8.81442 |
February | 672.00000 | 21.41174 | 23.44727 | -0.4169 | 9.12515 |
March | 744.00000 | 21.71504 | 22.49541 | -0.3368 | 8.16257 |
April | 720.00000 | 21.62844 | 27.04402 | -0.3270 | 7.82953 |
May | 744.00000 | 22.66036 | 29.73597 | -1.0692 | 29.99805 |
June | 720.00000 | 23.74095 | 36.02073 | -0.6269 | 13.59103 |
July | 744.00000 | 23.77245 | 38.52642 | -0.5988 | 12.82987 |
August | 744.00000 | 23.72247 | 38.22064 | -0.6192 | 13.38621 |
September | 720.00000 | 23.40782 | 27.99261 | -0.8076 | 19.87778 |
October | 744.00000 | 22.15796 | 24.87232 | -0.2062 | 6.88040 |
November | 720.00000 | 21.58494 | 26.58004 | -0.3438 | 8.06284 |
December | 744.00000 | 21.25448 | 19.54899 | -0.4889 | 10.37197 |
Annual Sum or Average | 8760.00000 | 22.37569 | 28.35358 | -0.5213 | 12.43860 |
Minimum of Months | 672.00000 | 21.25448 | 19.54899 | -1.0692 | 6.88040 |
Maximum of Months | 744.00000 | 23.77245 | 38.52642 | -0.2062 | 29.99805 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53000 | 23.66034 | -0.3835 | 8.43966 |
February | 672.00000 | 21.43525 | 21.81149 | -0.4237 | 9.15215 |
March | 744.00000 | 21.75532 | 20.96042 | -0.3458 | 8.01475 |
April | 720.00000 | 21.81273 | 25.30033 | -0.3054 | 7.44347 |
May | 744.00000 | 22.91257 | 28.00720 | -1.0369 | 28.31582 |
June | 720.00000 | 23.85090 | 34.50360 | -0.6570 | 14.22566 |
July | 744.00000 | 23.90476 | 36.90743 | -0.6202 | 13.20858 |
August | 744.00000 | 23.84569 | 36.79663 | -0.6461 | 13.96173 |
September | 720.00000 | 23.59903 | 26.36491 | -0.8053 | 19.29835 |
October | 744.00000 | 22.36634 | 23.13700 | -0.1818 | 6.31968 |
November | 720.00000 | 21.74469 | 24.80746 | -0.3238 | 7.61986 |
December | 744.00000 | 21.39556 | 17.85948 | -0.4612 | 9.81060 |
Annual Sum or Average | 8760.00000 | 22.51897 | 26.70464 | -0.5166 | 12.17555 |
Minimum of Months | 672.00000 | 21.39556 | 17.85948 | -1.0369 | 6.31968 |
Maximum of Months | 744.00000 | 23.90476 | 36.90743 | -0.1818 | 28.31582 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.162971E+11 | 64530.89 | 20-JAN-13:15 | 438.85 | 0.504771E+11 | 0.00 | 0.667743E+11 | 1.83 | 3.63 | 20-JAN-16:02 | 0.00 | 0.00 |
February | 0.120940E+11 | 60314.47 | 18-FEB-13:30 | 350.80 | 0.374544E+11 | 0.00 | 0.495484E+11 | 1.62 | 3.43 | 18-FEB-13:30 | 0.00 | 0.00 |
March | 0.210720E+11 | 88352.93 | 13-MAR-15:03 | 448.35 | 0.648538E+11 | 0.00 | 0.859258E+11 | 1.87 | 3.84 | 15-MAR-15:03 | 0.00 | 0.00 |
April | 0.165252E+11 | 71040.86 | 07-APR-15:03 | 441.24 | 0.487063E+11 | 0.00 | 0.652315E+11 | 1.88 | 3.67 | 07-APR-15:03 | 0.00 | 0.00 |
May | 0.570002E+11 | 97012.87 | 31-MAY-18:03 | 715.22 | 0.169956E+12 | 0.00 | 0.226956E+12 | 2.91 | 3.74 | 17-MAY-18:03 | 0.00 | 0.00 |
June | 0.149941E+12 | 157337.20 | 26-JUN-18:03 | 720.00 | 0.461066E+12 | 0.00 | 0.611007E+12 | 3.05 | 3.85 | 18-JUN-08:53 | 0.00 | 0.00 |
July | 0.165207E+12 | 131859.41 | 17-JUL-18:32 | 744.00 | 0.514949E+12 | 0.00 | 0.680156E+12 | 3.08 | 4.15 | 30-JUL-21:53 | 0.00 | 0.00 |
August | 0.152227E+12 | 149529.25 | 16-AUG-15:04 | 744.00 | 0.474683E+12 | 0.00 | 0.626910E+12 | 3.08 | 4.04 | 05-AUG-15:03 | 0.00 | 0.00 |
September | 0.111734E+12 | 118385.87 | 28-SEP-15:03 | 711.51 | 0.347544E+12 | 0.00 | 0.459278E+12 | 3.04 | 3.80 | 08-SEP-21:52 | 0.00 | 0.00 |
October | 0.334747E+11 | 102179.10 | 11-OCT-15:03 | 522.68 | 0.104027E+12 | 0.00 | 0.137501E+12 | 2.18 | 3.79 | 18-OCT-15:03 | 0.00 | 0.00 |
November | 0.186330E+11 | 70722.90 | 05-NOV-15:02 | 455.25 | 0.578266E+11 | 0.00 | 0.764597E+11 | 1.96 | 3.70 | 05-NOV-15:02 | 0.00 | 0.00 |
December | 0.117792E+11 | 59667.00 | 02-DEC-13:15 | 326.54 | 0.358313E+11 | 0.00 | 0.476105E+11 | 1.36 | 3.35 | 02-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.765985E+12 | 6618.42 | 0.236737E+13 | 0.00 | 0.313336E+13 | 2.33 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117792E+11 | 59667.00 | 326.54 | 0.358313E+11 | 0.00 | 0.476105E+11 | 1.36 | 3.35 | 0.00 | 0.00 | ||
Maximum of Months | 0.165207E+12 | 157337.20 | 744.00 | 0.514949E+12 | 0.00 | 0.680156E+12 | 3.08 | 4.15 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.113830E+12 | 0.00 | 697.08 | 217953.64 | 05-JAN-19:05 | 0.00 | 39.67 | 58.56 | 0.46 | 0.00 | 0.08 | 0.40 | 05-JAN-19:05 |
February | 0.118386E+12 | 0.00 | 638.55 | 201898.32 | 07-FEB-16:03 | 0.00 | 38.77 | 58.76 | 0.51 | 0.00 | 0.09 | 0.37 | 07-FEB-16:03 |
March | 0.101898E+12 | 0.00 | 640.64 | 202871.37 | 21-MAR-15:02 | 0.00 | 36.30 | 55.43 | 0.39 | 0.00 | 0.07 | 0.37 | 21-MAR-15:02 |
April | 0.930019E+11 | 0.00 | 607.78 | 139895.80 | 30-APR-08:07 | 0.00 | 35.75 | 54.94 | 0.35 | 0.00 | 0.07 | 0.26 | 30-APR-08:07 |
May | 0.745628E+11 | 0.00 | 432.38 | 133719.27 | 02-MAY-18:04 | 0.00 | 28.15 | 45.54 | 0.23 | 0.00 | 0.05 | 0.25 | 02-MAY-18:04 |
June | 0.521598E+10 | 0.00 | 61.68 | 115452.88 | 09-JUN-05:10 | 0.00 | 24.15 | 27.16 | 0.01 | 0.00 | 0.00 | 0.21 | 09-JUN-05:10 |
July | 0.455166E+10 | 0.00 | 43.14 | 75761.49 | 02-JUL-05:00 | 0.00 | 25.70 | 27.70 | 0.01 | 0.00 | 0.00 | 0.14 | 02-JUL-05:00 |
August | 0.465405E+10 | 0.00 | 57.10 | 56796.47 | 12-AUG-23:00 | 0.00 | 26.39 | 29.07 | 0.01 | 0.00 | 0.00 | 0.10 | 12-AUG-23:00 |
September | 0.283773E+11 | 0.00 | 197.51 | 133271.63 | 21-SEP-14:20 | 0.00 | 26.08 | 34.76 | 0.09 | 0.00 | 0.02 | 0.24 | 21-SEP-14:20 |
October | 0.861929E+11 | 0.00 | 570.22 | 166441.83 | 30-OCT-08:03 | 0.00 | 34.74 | 52.44 | 0.31 | 0.00 | 0.06 | 0.31 | 30-OCT-08:03 |
November | 0.904785E+11 | 0.00 | 639.66 | 182384.24 | 24-NOV-16:03 | 0.00 | 39.24 | 57.03 | 0.38 | 0.00 | 0.06 | 0.33 | 24-NOV-16:03 |
December | 0.164268E+12 | 0.00 | 698.33 | 249043.17 | 21-DEC-09:08 | 0.00 | 38.82 | 58.71 | 0.63 | 0.00 | 0.11 | 0.46 | 21-DEC-09:08 |
Annual Sum or Average | 0.885417E+12 | 0.00 | 5284.06 | 0.00 | 32.78 | 46.61 | 0.28 | 0.00 | 0.05 | ||||
Minimum of Months | 0.455166E+10 | 0.00 | 43.14 | 56796.47 | 0.00 | 24.15 | 27.16 | 0.01 | 0.00 | 0.00 | 0.10 | ||
Maximum of Months | 0.164268E+12 | 0.00 | 698.33 | 249043.17 | 0.00 | 39.67 | 58.76 | 0.63 | 0.00 | 0.11 | 0.46 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.508402E+10 | 0.00 | 45.09 | 0.508402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123391.13 | 20-JAN-13:00 | 123391.13 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.284855E+10 | 0.00 | 19.00 | 0.284855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112295.13 | 18-FEB-13:00 | 112295.13 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.178962E+11 | 0.00 | 119.01 | 0.178962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152508.15 | 14-MAR-13:00 | 152508.15 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.188813E+11 | 0.00 | 120.38 | 0.188813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107926.08 | 20-APR-13:00 | 107926.08 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.885542E+11 | 0.00 | 306.33 | 0.885542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202653.06 | 31-MAY-18:07 | 202653.06 | 31-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.291935E+12 | 0.00 | 659.00 | 0.287189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279965.75 | 26-JUN-18:20 | 279965.75 | 26-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.335840E+12 | 0.00 | 703.17 | 0.316635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283317.20 | 30-JUL-10:40 | 266068.55 | 17-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.299728E+12 | 0.00 | 688.44 | 0.292387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268634.84 | 16-AUG-18:05 | 268634.84 | 16-AUG-18:05 | 0.00 | 0.00 | 0.00 |
September | 0.206446E+12 | 0.00 | 523.33 | 0.206446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242015.02 | 12-SEP-18:30 | 242015.02 | 12-SEP-18:30 | 0.00 | 0.00 | 0.00 |
October | 0.333491E+11 | 0.00 | 146.56 | 0.333491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180057.39 | 11-OCT-15:10 | 180057.39 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.104961E+11 | 0.00 | 66.32 | 0.104961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135408.69 | 06-NOV-13:00 | 135408.69 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.696639E+10 | 0.00 | 42.92 | 0.696639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114594.23 | 02-DEC-13:00 | 114594.23 | 02-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131802E+13 | 0.00 | 3439.55 | 0.128673E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.284855E+10 | 0.00 | 19.00 | 0.284855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107926.08 | 107926.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.335840E+12 | 0.00 | 703.17 | 0.316635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283317.20 | 279965.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.192283E+09 | 0.00 | 14.67 | 0.192283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11112.29 | 20-JAN-14:00 | 11112.29 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.67 | 18-FEB-14:00 | 9344.67 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.893958E+09 | 0.00 | 49.33 | 0.893958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13429.57 | 13-MAR-15:02 | 13429.57 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.105767E+10 | 0.00 | 59.33 | 0.105767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12344.03 | 20-APR-13:00 | 12344.03 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.512456E+10 | 0.00 | 201.17 | 0.512456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15637.39 | 17-MAY-13:00 | 15637.39 | 17-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.173122E+11 | 0.00 | 514.67 | 0.168055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21623.04 | 18-JUN-12:05 | 18833.04 | 26-JUN-15:03 | 0.00 | 0.00 | 0.00 |
July | 0.210669E+11 | 0.00 | 551.83 | 0.191640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25905.81 | 30-JUL-15:37 | 18123.25 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.182535E+11 | 0.00 | 538.50 | 0.171964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21036.31 | 05-AUG-15:10 | 17891.04 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.117385E+11 | 0.00 | 387.83 | 0.117385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16823.41 | 10-SEP-13:00 | 16823.41 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.173199E+10 | 0.00 | 82.00 | 0.173199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14653.49 | 11-OCT-15:02 | 14653.49 | 11-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.497100E+09 | 0.00 | 28.33 | 0.497100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12313.09 | 06-NOV-13:50 | 12313.09 | 06-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.275045E+09 | 0.00 | 17.83 | 0.275045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11644.27 | 01-DEC-14:00 | 11644.27 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.782673E+11 | 0.00 | 2454.83 | 0.748005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.67 | 9344.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210669E+11 | 0.00 | 551.83 | 0.191640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25905.81 | 18833.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122329E+10 | 0.00 | 187.83 | 0.115912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11662.07 | 12-JAN-16:02 | 11662.07 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.131291E+10 | 0.00 | 173.89 | 0.127747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11664.13 | 23-FEB-16:02 | 11664.13 | 23-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.262611E+10 | 0.00 | 278.48 | 0.261466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11661.24 | 26-MAR-15:02 | 11661.24 | 26-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.174293E+10 | 0.00 | 240.63 | 0.163655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11662.53 | 27-APR-15:02 | 11662.53 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.435784E+10 | 0.00 | 563.92 | 0.360414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11914.07 | 22-MAY-08:62 | 11664.11 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.981808E+10 | 0.00 | 687.71 | 0.814414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13179.46 | 18-JUN-08:62 | 11663.58 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.962442E+10 | 0.00 | 712.43 | 0.753178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13468.98 | 28-JUL-18:02 | 11664.43 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.965773E+10 | 0.00 | 709.71 | 0.768084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13174.03 | 05-AUG-08:62 | 11703.97 | 21-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.769549E+10 | 0.00 | 649.08 | 0.687345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11663.99 | 07-SEP-18:02 | 11663.99 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.363137E+10 | 0.00 | 384.12 | 0.345909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11663.41 | 01-OCT-18:01 | 11663.41 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.170367E+10 | 0.00 | 238.27 | 0.155372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11663.73 | 23-NOV-16:01 | 11663.73 | 23-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.778990E+09 | 0.00 | 128.58 | 0.778990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11659.09 | 29-DEC-16:01 | 11659.09 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541728E+11 | 0.00 | 4954.65 | 0.463140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.778990E+09 | 0.00 | 128.58 | 0.778990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11659.09 | 11659.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.981808E+10 | 0.00 | 712.43 | 0.814414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13468.98 | 11703.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.191684E+09 | 0.00 | 42.58 | 0.184704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11391.63 | 19-JAN-16:02 | 11391.63 | 19-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.294485E+09 | 0.00 | 53.38 | 0.293780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11395.64 | 23-FEB-16:02 | 11395.64 | 23-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.101249E+10 | 0.00 | 164.57 | 0.100869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12798.25 | 15-MAR-18:31 | 12798.25 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.841518E+09 | 0.00 | 158.04 | 0.753681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14290.01 | 08-APR-17:42 | 14290.01 | 08-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.294323E+10 | 0.00 | 441.41 | 0.229107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12838.33 | 27-MAY-16:11 | 12838.33 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.833572E+10 | 0.00 | 544.03 | 0.706286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14001.98 | 20-JUN-21:51 | 12580.64 | 18-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.783636E+10 | 0.00 | 545.70 | 0.628063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14319.73 | 31-JUL-21:51 | 12998.52 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.724387E+10 | 0.00 | 544.20 | 0.574078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13768.31 | 05-AUG-08:51 | 12686.14 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.474744E+10 | 0.00 | 472.11 | 0.408461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12225.36 | 15-SEP-19:51 | 12225.36 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.135763E+10 | 0.00 | 218.91 | 0.127186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12550.49 | 14-OCT-16:11 | 12550.49 | 14-OCT-16:11 | 0.00 | 0.00 | 0.00 |
November | 0.332695E+09 | 0.00 | 74.93 | 0.312620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11393.09 | 15-NOV-16:02 | 11393.09 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 87545814.53 | 0.00 | 24.04 | 87545814.53 | 0.00 | 0.00 | 0.00 | 0.00 | 11388.16 | 03-DEC-16:01 | 11388.16 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352247E+11 | 0.00 | 3283.90 | 0.293728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 87545814.53 | 0.00 | 24.04 | 87545814.53 | 0.00 | 0.00 | 0.00 | 0.00 | 11388.16 | 11388.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.833572E+10 | 0.00 | 545.70 | 0.706286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14319.73 | 14290.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.302543E+11 | 0.00 | 366.99 | 0.302543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69602.44 | 20-JAN-12:40 | 69602.44 | 20-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.208767E+11 | 0.00 | 268.12 | 0.208767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65069.32 | 18-FEB-13:00 | 65069.32 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.219621E+11 | 0.00 | 287.51 | 0.219621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59312.23 | 14-MAR-12:40 | 59312.23 | 14-MAR-12:40 | 0.00 | 0.00 | 0.00 |
April | 0.714566E+10 | 0.00 | 170.34 | 0.705764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34062.19 | 12-APR-13:30 | 34062.19 | 12-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.199405E+11 | 0.00 | 497.37 | 0.167277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27335.57 | 16-MAY-13:20 | 27335.57 | 16-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.408399E+11 | 0.00 | 706.08 | 0.318108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34255.90 | 14-JUN-13:30 | 34255.90 | 14-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.448703E+11 | 0.00 | 737.29 | 0.347375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37603.20 | 23-JUL-12:40 | 34670.29 | 18-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.510341E+11 | 0.00 | 739.42 | 0.390443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48569.39 | 31-AUG-12:50 | 44011.88 | 31-AUG-12:50 | 0.00 | 0.00 | 0.00 |
September | 0.510439E+11 | 0.00 | 678.87 | 0.468701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61788.24 | 28-SEP-13:00 | 61788.24 | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.361213E+11 | 0.00 | 423.87 | 0.361199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63828.99 | 10-OCT-12:30 | 63828.99 | 10-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.287344E+11 | 0.00 | 352.81 | 0.287344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68973.44 | 07-NOV-12:10 | 68973.44 | 07-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.179622E+11 | 0.00 | 227.94 | 0.179622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61048.37 | 17-DEC-13:00 | 61048.37 | 17-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370785E+12 | 0.00 | 5456.60 | 0.332158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.714566E+10 | 0.00 | 170.34 | 0.705764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27335.57 | 27335.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.510439E+11 | 0.00 | 739.42 | 0.468701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69602.44 | 69602.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.124434E+10 | 0.00 | 79.99 | 0.112255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59065.62 | 21-JAN-09:02 | 59065.62 | 21-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.119511E+10 | 0.00 | 70.81 | 0.109947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58988.44 | 19-FEB-09:01 | 58988.44 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.602611E+10 | 0.00 | 200.18 | 0.584923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62535.16 | 14-MAR-20:51 | 62535.16 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.853365E+10 | 0.00 | 269.71 | 0.721134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63328.49 | 20-APR-20:31 | 63328.49 | 20-APR-20:31 | 0.00 | 0.00 | 0.00 |
May | 0.279783E+11 | 0.00 | 446.94 | 0.242197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64469.44 | 07-MAY-19:31 | 64469.44 | 07-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.522518E+11 | 0.00 | 508.28 | 0.462486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75409.23 | 20-JUN-21:51 | 67090.45 | 30-JUN-07:42 | 0.00 | 0.00 | 0.00 |
July | 0.537838E+11 | 0.00 | 518.65 | 0.466163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77167.48 | 31-JUL-21:51 | 68335.94 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.465018E+11 | 0.00 | 494.39 | 0.389453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73505.78 | 29-AUG-21:51 | 65923.50 | 01-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.317979E+11 | 0.00 | 431.37 | 0.290171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64528.27 | 09-SEP-21:51 | 64528.27 | 09-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.930298E+10 | 0.00 | 289.56 | 0.841795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62367.46 | 01-OCT-18:01 | 62367.46 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.256896E+10 | 0.00 | 127.72 | 0.221590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59642.95 | 09-NOV-19:02 | 59642.95 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.888803E+09 | 0.00 | 55.59 | 0.888803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58151.84 | 03-DEC-09:02 | 58151.84 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242074E+12 | 0.00 | 3493.19 | 0.211852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.888803E+09 | 0.00 | 55.59 | 0.888803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58151.84 | 58151.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.537838E+11 | 0.00 | 518.65 | 0.466163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77167.48 | 68335.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.120231E+10 | 0.00 | 176.53 | 0.114400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10225.34 | 01-JAN-09:01 | 10225.34 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.147318E+10 | 0.00 | 191.68 | 0.142817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10225.11 | 18-FEB-09:02 | 10225.11 | 18-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.278752E+10 | 0.00 | 300.47 | 0.277526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10225.41 | 01-MAR-09:01 | 10225.41 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.207621E+10 | 0.00 | 268.51 | 0.194561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11855.46 | 19-APR-08:51 | 11855.46 | 19-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.476430E+10 | 0.00 | 596.77 | 0.401697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10237.88 | 22-MAY-08:62 | 10237.88 | 22-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.104328E+11 | 0.00 | 708.15 | 0.889543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11245.07 | 17-JUN-08:62 | 10260.56 | 16-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.107577E+11 | 0.00 | 729.75 | 0.892230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11892.55 | 28-JUL-18:02 | 10241.67 | 30-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.107081E+11 | 0.00 | 728.98 | 0.892939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10632.76 | 21-AUG-18:02 | 10258.62 | 05-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.811563E+10 | 0.00 | 669.84 | 0.741380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10225.64 | 16-SEP-15:02 | 10225.64 | 16-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.348800E+10 | 0.00 | 383.92 | 0.332699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10225.49 | 04-OCT-15:01 | 10225.49 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.165390E+10 | 0.00 | 229.35 | 0.151987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10224.12 | 05-NOV-08:62 | 10224.12 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.797561E+09 | 0.00 | 134.59 | 0.797561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10224.70 | 16-DEC-09:02 | 10224.70 | 16-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.582572E+11 | 0.00 | 5118.54 | 0.511153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.797561E+09 | 0.00 | 134.59 | 0.797561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10224.12 | 10224.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107577E+11 | 0.00 | 729.75 | 0.892939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11892.55 | 11855.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.206441E+09 | 0.00 | 41.00 | 0.187575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9989.58 | 20-JAN-09:02 | 9989.58 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.414601E+09 | 0.00 | 66.07 | 0.387171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9991.84 | 18-FEB-09:02 | 9991.84 | 18-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.124737E+10 | 0.00 | 187.41 | 0.123751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10107.03 | 14-MAR-20:51 | 10107.03 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.125908E+10 | 0.00 | 196.45 | 0.114804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11492.47 | 19-APR-08:51 | 11492.47 | 19-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.348148E+10 | 0.00 | 482.08 | 0.283475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11585.74 | 10-MAY-08:51 | 11585.74 | 10-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.859821E+10 | 0.00 | 561.99 | 0.741971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13571.63 | 21-JUN-08:32 | 12797.41 | 28-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.865461E+10 | 0.00 | 561.58 | 0.732017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13707.89 | 01-JUL-07:32 | 13707.89 | 01-JUL-07:32 | 0.00 | 0.00 | 0.00 |
August | 0.800273E+10 | 0.00 | 565.73 | 0.657889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13986.88 | 04-AUG-08:32 | 12682.10 | 19-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.518991E+10 | 0.00 | 502.15 | 0.455449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11584.79 | 07-SEP-08:51 | 11584.79 | 07-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.136664E+10 | 0.00 | 223.70 | 0.125940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11354.89 | 11-OCT-08:51 | 11354.89 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.379684E+09 | 0.00 | 67.66 | 0.328196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9990.77 | 05-NOV-08:62 | 9990.77 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.120612E+09 | 0.00 | 24.68 | 0.120612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9955.05 | 02-DEC-09:02 | 9955.05 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389214E+11 | 0.00 | 3480.50 | 0.333765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120612E+09 | 0.00 | 24.68 | 0.120612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9955.05 | 9955.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.865461E+10 | 0.00 | 565.73 | 0.741971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13986.88 | 13707.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.286879E+09 | 0.00 | 145.74 | 0.273686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.67 | 12-JAN-16:02 | 3094.67 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.318021E+09 | 0.00 | 140.46 | 0.312815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.21 | 23-FEB-16:02 | 3095.21 | 23-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.650394E+09 | 0.00 | 232.16 | 0.647930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.55 | 26-MAR-15:02 | 3094.55 | 26-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.453519E+09 | 0.00 | 206.89 | 0.429427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3137.38 | 18-APR-19:11 | 3137.38 | 18-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.106928E+10 | 0.00 | 484.86 | 0.902200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3292.85 | 22-MAY-08:62 | 3095.14 | 27-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.248757E+10 | 0.00 | 684.79 | 0.207141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.11 | 18-JUN-08:62 | 3129.45 | 24-JUN-16:43 | 0.00 | 0.00 | 0.00 |
July | 0.238970E+10 | 0.00 | 708.96 | 0.187199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.60 | 30-JUL-08:62 | 3095.12 | 17-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.240262E+10 | 0.00 | 701.49 | 0.192025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3614.02 | 05-AUG-08:62 | 3095.03 | 12-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.183211E+10 | 0.00 | 627.47 | 0.162960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.10 | 10-SEP-15:37 | 3123.10 | 10-SEP-15:37 | 0.00 | 0.00 | 0.00 |
October | 0.848871E+09 | 0.00 | 314.75 | 0.813509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.99 | 01-OCT-18:01 | 3094.99 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.404608E+09 | 0.00 | 187.20 | 0.374584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.16 | 23-NOV-16:01 | 3095.16 | 23-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.180797E+09 | 0.00 | 106.47 | 0.180788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.81 | 16-DEC-16:02 | 3093.81 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133244E+11 | 0.00 | 4541.25 | 0.114282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.180797E+09 | 0.00 | 106.47 | 0.180788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.81 | 3093.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.248757E+10 | 0.00 | 708.96 | 0.207141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.60 | 3137.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 39710770.99 | 0.00 | 29.33 | 38205125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3017.76 | 19-JAN-16:02 | 3017.76 | 19-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 67575443.71 | 0.00 | 40.64 | 67422041.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3018.75 | 23-FEB-16:02 | 3018.75 | 23-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.239307E+09 | 0.00 | 133.93 | 0.238572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3466.16 | 08-MAR-17:11 | 3466.16 | 08-MAR-17:11 | 0.00 | 0.00 | 0.00 |
April | 0.216063E+09 | 0.00 | 134.80 | 0.197399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3861.15 | 08-APR-17:42 | 3861.15 | 08-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.712446E+09 | 0.00 | 391.79 | 0.565849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3456.39 | 27-MAY-16:11 | 3456.39 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.216837E+10 | 0.00 | 544.63 | 0.184040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3832.83 | 22-JUN-21:51 | 3425.41 | 18-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.200291E+10 | 0.00 | 547.05 | 0.160347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3879.99 | 31-JUL-21:51 | 3418.85 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.184728E+10 | 0.00 | 541.83 | 0.146741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3694.28 | 05-AUG-21:51 | 3302.77 | 05-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.112541E+10 | 0.00 | 457.57 | 0.961080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3302.94 | 15-SEP-19:51 | 3302.94 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.287604E+09 | 0.00 | 163.15 | 0.272916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3395.80 | 08-OCT-18:11 | 3395.80 | 08-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 73536650.70 | 0.00 | 57.53 | 69945533.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3018.05 | 15-NOV-16:02 | 3018.05 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 20097199.49 | 0.00 | 17.23 | 20097199.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.74 | 03-DEC-16:01 | 3016.74 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.880031E+10 | 0.00 | 3059.50 | 0.734276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 20097199.49 | 0.00 | 17.23 | 20097199.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.74 | 3016.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.216837E+10 | 0.00 | 547.05 | 0.184040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3879.99 | 3861.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.713691E+10 | 0.00 | 373.23 | 0.696659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14487.18 | 19-JAN-13:53 | 14487.18 | 19-JAN-13:53 | 0.00 | 0.00 | 0.00 |
February | 0.579534E+10 | 0.00 | 318.83 | 0.566097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13725.77 | 18-FEB-09:02 | 13725.77 | 18-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.601129E+10 | 0.00 | 365.32 | 0.597435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13725.26 | 26-MAR-15:02 | 13725.26 | 26-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.305968E+10 | 0.00 | 286.51 | 0.286924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13868.25 | 18-APR-19:11 | 13868.25 | 18-APR-19:11 | 0.00 | 0.00 | 0.00 |
May | 0.539147E+10 | 0.00 | 555.65 | 0.446462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14277.37 | 22-MAY-15:02 | 13724.68 | 06-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.108625E+11 | 0.00 | 680.27 | 0.874346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15601.51 | 18-JUN-08:62 | 13725.58 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.117967E+11 | 0.00 | 705.53 | 0.917946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16221.58 | 31-JUL-18:02 | 13724.35 | 13-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.129806E+11 | 0.00 | 706.56 | 0.105019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15410.87 | 04-AUG-08:62 | 13746.16 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.120189E+11 | 0.00 | 658.06 | 0.110087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13724.95 | 18-SEP-18:02 | 13724.95 | 18-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.844401E+10 | 0.00 | 454.64 | 0.819332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14340.90 | 08-OCT-12:35 | 14340.90 | 08-OCT-12:35 | 0.00 | 0.00 | 0.00 |
November | 0.743434E+10 | 0.00 | 406.35 | 0.705291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14860.75 | 16-NOV-13:33 | 14860.75 | 16-NOV-13:33 | 0.00 | 0.00 | 0.00 |
December | 0.521155E+10 | 0.00 | 285.86 | 0.521155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13724.76 | 30-DEC-16:02 | 13724.76 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.961431E+11 | 0.00 | 5796.80 | 0.858271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.305968E+10 | 0.00 | 285.86 | 0.286924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13724.76 | 13724.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129806E+11 | 0.00 | 706.56 | 0.110087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16221.58 | 14860.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1327.33 | 1092.65 | 234.67 | 1516.03 | 622.11 | 0.00 | 0.00 | 0.00 |
February | 1255.98 | 998.64 | 257.34 | 1421.30 | 652.09 | 0.00 | 0.00 | 0.00 |
March | 943.45 | 623.53 | 319.92 | 1080.04 | 518.45 | 0.00 | 0.00 | 0.00 |
April | 617.77 | 255.57 | 362.20 | 648.68 | 463.80 | 0.00 | 0.00 | 0.00 |
May | 561.37 | 107.95 | 453.41 | 656.00 | 267.02 | 0.00 | 0.00 | 0.00 |
June | 510.38 | 92.13 | 418.25 | 743.28 | 144.17 | 0.00 | 0.00 | 0.00 |
July | 527.16 | 89.81 | 437.35 | 771.41 | 128.77 | 0.00 | 0.00 | 0.00 |
August | 670.74 | 275.95 | 394.79 | 980.09 | 150.59 | 0.00 | 0.00 | 0.00 |
September | 881.07 | 495.25 | 385.82 | 1201.43 | 236.64 | 0.00 | 0.00 | 0.00 |
October | 1040.04 | 736.90 | 303.14 | 1261.09 | 503.19 | 0.00 | 0.00 | 0.00 |
November | 1274.79 | 1016.81 | 257.98 | 1495.37 | 583.35 | 0.00 | 0.00 | 0.00 |
December | 1216.57 | 984.85 | 231.72 | 1359.61 | 708.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 900.20 | 561.69 | 338.52 | 1092.63 | 413.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.38 | 89.81 | 231.72 | 648.68 | 128.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1327.33 | 1092.65 | 453.41 | 1516.03 | 708.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3737.67 | 3076.84 | 660.83 | 4230.25 | 1849.40 | 0.00 | 0.00 | 0.00 |
February | 3536.75 | 2812.11 | 724.64 | 3964.79 | 1923.89 | 0.00 | 0.00 | 0.00 |
March | 2656.69 | 1755.81 | 900.88 | 3007.51 | 1542.80 | 0.00 | 0.00 | 0.00 |
April | 1739.60 | 719.67 | 1019.93 | 1791.71 | 1401.55 | 0.00 | 0.00 | 0.00 |
May | 1580.77 | 303.98 | 1276.78 | 1794.70 | 832.61 | 0.00 | 0.00 | 0.00 |
June | 1437.19 | 259.44 | 1177.75 | 2065.28 | 430.29 | 0.00 | 0.00 | 0.00 |
July | 1484.44 | 252.89 | 1231.56 | 2144.75 | 386.78 | 0.00 | 0.00 | 0.00 |
August | 1888.76 | 777.06 | 1111.70 | 2732.48 | 450.33 | 0.00 | 0.00 | 0.00 |
September | 2481.05 | 1394.59 | 1086.46 | 3355.33 | 704.48 | 0.00 | 0.00 | 0.00 |
October | 2928.68 | 2075.07 | 853.61 | 3521.79 | 1496.49 | 0.00 | 0.00 | 0.00 |
November | 3589.72 | 2863.26 | 726.46 | 4175.63 | 1734.81 | 0.00 | 0.00 | 0.00 |
December | 3425.79 | 2773.28 | 652.52 | 3792.38 | 2089.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2534.91 | 1581.67 | 953.24 | 3042.72 | 1233.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1437.19 | 252.89 | 652.52 | 1791.71 | 386.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3737.67 | 3076.84 | 1276.78 | 4230.25 | 2089.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4855.45 | 3996.99 | 858.45 | 5578.17 | 2471.74 | 0.00 | 0.00 | 0.00 |
February | 4594.44 | 3653.09 | 941.35 | 5236.53 | 2579.94 | 0.00 | 0.00 | 0.00 |
March | 3451.19 | 2280.90 | 1170.29 | 3974.72 | 2087.01 | 0.00 | 0.00 | 0.00 |
April | 2259.84 | 934.90 | 1324.95 | 2368.55 | 1917.68 | 0.00 | 0.00 | 0.00 |
May | 2053.51 | 394.89 | 1658.62 | 2377.90 | 1119.44 | 0.00 | 0.00 | 0.00 |
June | 1866.99 | 337.03 | 1529.97 | 2750.99 | 567.10 | 0.00 | 0.00 | 0.00 |
July | 1928.38 | 328.51 | 1599.86 | 2854.68 | 508.87 | 0.00 | 0.00 | 0.00 |
August | 2453.61 | 1009.44 | 1444.17 | 3627.70 | 588.03 | 0.00 | 0.00 | 0.00 |
September | 3223.02 | 1811.65 | 1411.37 | 4441.76 | 924.30 | 0.00 | 0.00 | 0.00 |
October | 3804.52 | 2695.63 | 1108.89 | 4647.24 | 2010.42 | 0.00 | 0.00 | 0.00 |
November | 4663.25 | 3719.54 | 943.71 | 5508.17 | 2324.07 | 0.00 | 0.00 | 0.00 |
December | 4450.30 | 3602.64 | 847.66 | 5000.00 | 2805.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3292.99 | 2054.68 | 1238.31 | 4023.51 | 1653.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1866.99 | 328.51 | 847.66 | 2368.55 | 508.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4855.45 | 3996.99 | 1658.62 | 5578.17 | 2805.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 304.42 | 121.85 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 284.26 | 129.50 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 215.92 | 102.29 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 129.16 | 92.71 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 130.92 | 51.59 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 152.39 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.88 | 19.48 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 199.35 | 23.25 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 242.76 | 40.36 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 252.93 | 97.34 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 300.02 | 114.09 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 271.70 | 141.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 219.85 | 79.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 129.16 | 19.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 304.42 | 141.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 158.33 | 251.41 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 188.83 | 258.72 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 238.49 | 194.00 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 216.59 | 169.15 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 321.82 | 93.66 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 473.54 | 42.52 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 390.95 | 36.22 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 398.54 | 42.83 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 336.91 | 75.94 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 232.33 | 186.88 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 169.60 | 226.27 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 119.17 | 287.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 270.78 | 154.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 119.17 | 36.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 473.54 | 287.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.58 | 139.22 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 6.60 | 144.04 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 21.25 | 107.90 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 32.66 | 91.93 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 75.40 | 48.96 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 122.79 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 119.01 | 20.12 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 90.11 | 24.34 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.57 | 42.98 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 22.99 | 101.39 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.92 | 124.14 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.62 | 160.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 48.28 | 85.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.62 | 20.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 122.79 | 160.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 165.08 | 245.54 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 195.78 | 253.79 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 242.66 | 192.27 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 218.59 | 168.71 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 320.27 | 95.73 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 470.31 | 45.96 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 387.26 | 39.41 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 397.19 | 46.22 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 337.65 | 79.24 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 236.24 | 185.23 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 176.12 | 221.57 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 124.82 | 282.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 272.99 | 154.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 124.82 | 39.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 470.31 | 282.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.91 | 172.79 | 37.11 | 232.00 | 121.09 | 0.00 | 0.00 | 0.00 |
February | 198.62 | 157.93 | 40.70 | 217.84 | 121.07 | 0.00 | 0.00 | 0.00 |
March | 149.20 | 98.61 | 50.59 | 164.79 | 98.28 | 0.00 | 0.00 | 0.00 |
April | 97.70 | 40.42 | 57.28 | 96.07 | 93.88 | 0.00 | 0.00 | 0.00 |
May | 88.78 | 17.07 | 71.70 | 92.80 | 59.55 | 0.00 | 0.00 | 0.00 |
June | 80.71 | 14.57 | 66.14 | 109.07 | 33.05 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 14.20 | 69.16 | 113.55 | 30.57 | 0.00 | 0.00 | 0.00 |
August | 106.07 | 43.64 | 62.43 | 147.15 | 34.79 | 0.00 | 0.00 | 0.00 |
September | 139.34 | 78.32 | 61.02 | 182.36 | 50.94 | 0.00 | 0.00 | 0.00 |
October | 164.47 | 116.54 | 47.94 | 193.13 | 99.81 | 0.00 | 0.00 | 0.00 |
November | 201.60 | 160.80 | 40.80 | 230.35 | 113.50 | 0.00 | 0.00 | 0.00 |
December | 192.39 | 155.75 | 36.65 | 209.39 | 130.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 142.36 | 88.83 | 53.53 | 165.40 | 82.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.71 | 14.20 | 36.65 | 92.80 | 30.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.91 | 172.79 | 71.70 | 232.00 | 130.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.83 | 0.00 | 21.83 | 4.38 | 113.86 | 0.00 | 0.00 | 0.00 |
February | 27.44 | 0.00 | 27.44 | 5.43 | 117.26 | 0.00 | 0.00 | 0.00 |
March | 37.34 | 0.00 | 37.34 | 17.91 | 86.99 | 0.00 | 0.00 | 0.00 |
April | 46.94 | 0.31 | 46.64 | 27.08 | 74.76 | 0.00 | 0.00 | 0.00 |
May | 64.13 | 2.15 | 61.98 | 63.28 | 38.54 | 0.00 | 0.00 | 0.00 |
June | 70.31 | 7.86 | 62.45 | 103.06 | 16.71 | 0.00 | 0.00 | 0.00 |
July | 66.69 | 4.55 | 62.14 | 99.31 | 14.82 | 0.00 | 0.00 | 0.00 |
August | 53.10 | 1.44 | 51.66 | 76.46 | 17.67 | 0.00 | 0.00 | 0.00 |
September | 44.46 | 0.04 | 44.42 | 56.67 | 32.29 | 0.00 | 0.00 | 0.00 |
October | 31.81 | 0.00 | 31.81 | 19.81 | 81.27 | 0.00 | 0.00 | 0.00 |
November | 24.15 | 0.00 | 24.15 | 7.28 | 101.14 | 0.00 | 0.00 | 0.00 |
December | 20.42 | 0.00 | 20.42 | 3.53 | 132.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.46 | 1.37 | 41.10 | 40.55 | 68.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.42 | 0.00 | 20.42 | 3.53 | 14.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.31 | 7.86 | 62.45 | 103.06 | 132.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 138.55 | 247.13 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 197.71 | 257.67 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 258.11 | 190.32 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 260.83 | 165.45 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 357.31 | 88.26 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 519.95 | 38.65 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 478.25 | 34.10 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 475.60 | 41.26 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 373.78 | 71.88 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 218.40 | 183.12 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 148.41 | 224.76 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 114.10 | 286.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 295.55 | 151.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 114.10 | 34.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 519.95 | 286.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 303.88 | 121.34 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 283.25 | 128.92 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 214.43 | 101.78 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 127.60 | 92.55 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 129.66 | 51.40 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.17 | 22.43 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 157.28 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 197.95 | 23.06 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 241.68 | 40.08 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 252.25 | 96.87 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 299.66 | 113.50 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 271.22 | 140.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 218.80 | 79.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 127.60 | 19.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 303.88 | 140.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.26 | 138.59 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 5.82 | 143.65 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 20.02 | 107.41 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 31.19 | 91.68 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 74.12 | 48.48 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 120.15 | 22.42 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 116.21 | 19.99 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 87.52 | 24.06 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 65.07 | 42.35 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 22.14 | 100.43 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.34 | 123.22 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.28 | 159.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 46.91 | 84.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.28 | 19.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 120.15 | 159.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 143.19 | 238.21 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 202.42 | 250.17 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 262.30 | 187.85 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 263.04 | 164.64 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 356.34 | 90.12 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 513.90 | 42.21 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 472.25 | 37.43 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 472.05 | 44.72 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 373.91 | 74.59 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 222.64 | 180.83 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 153.28 | 217.69 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 118.14 | 278.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 296.56 | 150.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 118.14 | 37.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 513.90 | 278.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 5.66 | 190.19 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 6.79 | 194.77 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 25.75 | 145.37 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 41.64 | 123.29 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 97.14 | 66.63 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 155.38 | 33.64 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 149.39 | 31.22 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 113.01 | 37.26 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 82.81 | 62.21 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 27.36 | 140.09 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 9.60 | 169.59 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 4.71 | 217.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 60.24 | 117.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 4.71 | 31.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 155.38 | 217.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.74 | 0.00 | 12.74 | 2.09 | 70.11 | 0.00 | 0.00 | 0.00 |
February | 16.01 | 0.00 | 16.01 | 2.50 | 71.80 | 0.00 | 0.00 | 0.00 |
March | 21.79 | 0.00 | 21.79 | 9.49 | 53.59 | 0.00 | 0.00 | 0.00 |
April | 27.39 | 0.18 | 27.21 | 15.35 | 45.45 | 0.00 | 0.00 | 0.00 |
May | 37.42 | 1.25 | 36.16 | 35.81 | 24.56 | 0.00 | 0.00 | 0.00 |
June | 41.03 | 4.59 | 36.44 | 57.28 | 12.40 | 0.00 | 0.00 | 0.00 |
July | 38.91 | 2.66 | 36.26 | 55.07 | 11.51 | 0.00 | 0.00 | 0.00 |
August | 30.98 | 0.84 | 30.14 | 41.66 | 13.73 | 0.00 | 0.00 | 0.00 |
September | 25.94 | 0.02 | 25.92 | 30.53 | 22.93 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 10.09 | 51.64 | 0.00 | 0.00 | 0.00 |
November | 14.09 | 0.00 | 14.09 | 3.54 | 62.52 | 0.00 | 0.00 | 0.00 |
December | 11.92 | 0.00 | 11.92 | 1.74 | 80.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.78 | 0.80 | 23.98 | 22.21 | 43.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.92 | 0.00 | 11.92 | 1.74 | 11.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.03 | 4.59 | 36.44 | 57.28 | 80.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.45 | 100.80 | 21.65 | 142.83 | 59.13 | 0.00 | 0.00 | 0.00 |
February | 115.87 | 92.13 | 23.74 | 133.48 | 62.95 | 0.00 | 0.00 | 0.00 |
March | 87.04 | 57.52 | 29.51 | 101.33 | 50.45 | 0.00 | 0.00 | 0.00 |
April | 56.99 | 23.58 | 33.41 | 60.83 | 45.66 | 0.00 | 0.00 | 0.00 |
May | 51.79 | 9.96 | 41.83 | 61.51 | 26.53 | 0.00 | 0.00 | 0.00 |
June | 47.08 | 8.50 | 38.59 | 70.47 | 13.64 | 0.00 | 0.00 | 0.00 |
July | 48.63 | 8.28 | 40.35 | 72.92 | 12.31 | 0.00 | 0.00 | 0.00 |
August | 61.88 | 25.46 | 36.42 | 92.32 | 14.24 | 0.00 | 0.00 | 0.00 |
September | 81.28 | 45.69 | 35.59 | 112.80 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 95.95 | 67.98 | 27.97 | 118.31 | 49.13 | 0.00 | 0.00 | 0.00 |
November | 117.60 | 93.80 | 23.80 | 140.82 | 55.76 | 0.00 | 0.00 | 0.00 |
December | 112.23 | 90.86 | 21.38 | 127.24 | 68.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 51.82 | 31.23 | 102.73 | 39.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.08 | 8.28 | 21.38 | 60.83 | 12.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.45 | 100.80 | 41.83 | 142.83 | 68.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 332.36 | 273.60 | 58.76 | 387.67 | 160.50 | 0.00 | 0.00 | 0.00 |
February | 314.49 | 250.06 | 64.44 | 362.29 | 170.85 | 0.00 | 0.00 | 0.00 |
March | 236.24 | 156.13 | 80.11 | 275.04 | 136.94 | 0.00 | 0.00 | 0.00 |
April | 154.69 | 63.99 | 90.69 | 165.10 | 123.94 | 0.00 | 0.00 | 0.00 |
May | 140.56 | 27.03 | 113.53 | 166.95 | 72.01 | 0.00 | 0.00 | 0.00 |
June | 127.80 | 23.07 | 104.73 | 191.28 | 37.03 | 0.00 | 0.00 | 0.00 |
July | 132.00 | 22.49 | 109.51 | 197.92 | 33.42 | 0.00 | 0.00 | 0.00 |
August | 167.95 | 69.10 | 98.86 | 250.56 | 38.64 | 0.00 | 0.00 | 0.00 |
September | 220.62 | 124.01 | 96.61 | 306.18 | 61.23 | 0.00 | 0.00 | 0.00 |
October | 260.42 | 184.52 | 75.90 | 321.12 | 133.34 | 0.00 | 0.00 | 0.00 |
November | 319.20 | 254.60 | 64.60 | 382.22 | 151.35 | 0.00 | 0.00 | 0.00 |
December | 304.63 | 246.60 | 58.02 | 345.37 | 185.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.41 | 140.64 | 84.76 | 278.82 | 108.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.80 | 22.49 | 58.02 | 165.10 | 33.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.36 | 273.60 | 113.53 | 387.67 | 185.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 303.66 | 121.16 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 282.84 | 129.41 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 214.74 | 101.91 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 128.23 | 92.38 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 129.92 | 51.29 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.34 | 22.37 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.05 | 18.89 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 198.12 | 22.66 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 241.67 | 39.55 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 251.97 | 96.60 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 298.91 | 113.57 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 270.62 | 140.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 218.80 | 78.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 128.23 | 18.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 303.66 | 140.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 157.68 | 249.36 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 187.54 | 258.06 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 236.93 | 193.02 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 214.94 | 168.33 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 319.57 | 92.95 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 470.98 | 41.56 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 389.05 | 35.13 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 396.36 | 41.74 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 335.51 | 74.37 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 231.21 | 185.20 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 168.64 | 224.86 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 118.64 | 286.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 269.28 | 153.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 118.64 | 35.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 470.98 | 286.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.81 | 137.79 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 6.67 | 143.41 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 21.19 | 107.50 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 32.27 | 91.70 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 74.45 | 49.01 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 121.93 | 22.77 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 118.42 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 89.48 | 24.08 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.50 | 42.46 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 23.11 | 100.68 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 9.05 | 123.07 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.80 | 159.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 48.04 | 84.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.80 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 121.93 | 159.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 165.30 | 243.32 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 195.19 | 253.01 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 241.36 | 191.44 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 216.91 | 168.13 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 317.58 | 95.66 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 467.60 | 45.55 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 385.31 | 38.76 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 394.98 | 45.60 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 336.41 | 78.14 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 235.54 | 183.62 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 175.87 | 219.89 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 124.86 | 281.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 271.73 | 153.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 124.86 | 38.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 467.60 | 281.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.89 | 316.84 | 68.05 | 437.70 | 184.11 | 0.00 | 0.00 | 0.00 |
February | 364.20 | 289.58 | 74.62 | 408.26 | 195.52 | 0.00 | 0.00 | 0.00 |
March | 273.57 | 180.80 | 92.77 | 311.21 | 152.58 | 0.00 | 0.00 | 0.00 |
April | 179.14 | 74.11 | 105.03 | 186.17 | 137.53 | 0.00 | 0.00 | 0.00 |
May | 162.78 | 31.30 | 131.48 | 191.51 | 74.79 | 0.00 | 0.00 | 0.00 |
June | 148.00 | 26.72 | 121.28 | 226.52 | 30.97 | 0.00 | 0.00 | 0.00 |
July | 152.86 | 26.04 | 126.82 | 234.93 | 26.51 | 0.00 | 0.00 | 0.00 |
August | 194.50 | 80.02 | 114.48 | 292.88 | 32.05 | 0.00 | 0.00 | 0.00 |
September | 255.49 | 143.61 | 111.88 | 353.97 | 57.90 | 0.00 | 0.00 | 0.00 |
October | 301.58 | 213.68 | 87.90 | 366.25 | 145.21 | 0.00 | 0.00 | 0.00 |
November | 369.65 | 294.84 | 74.81 | 431.72 | 172.61 | 0.00 | 0.00 | 0.00 |
December | 352.77 | 285.58 | 67.19 | 388.93 | 214.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.03 | 162.87 | 98.16 | 318.65 | 118.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.00 | 26.04 | 67.19 | 186.17 | 26.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.89 | 316.84 | 131.48 | 437.70 | 214.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 22.24 | 1141.48 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 27.30 | 1179.57 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 116.36 | 889.98 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 189.45 | 773.99 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 484.62 | 404.50 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 836.34 | 192.18 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 808.12 | 177.76 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 608.85 | 210.48 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 443.02 | 352.82 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 134.33 | 831.74 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 41.55 | 1027.10 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 18.01 | 1312.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 312.45 | 705.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 18.01 | 177.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 836.34 | 1312.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 19.49 | 1166.20 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 24.82 | 1205.60 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 110.24 | 909.53 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 181.81 | 791.32 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 475.59 | 412.49 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 828.89 | 196.93 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 800.90 | 182.67 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 602.26 | 216.12 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 437.02 | 360.38 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 129.10 | 847.88 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 38.72 | 1049.57 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 16.09 | 1341.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 306.99 | 720.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 16.09 | 182.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 828.89 | 1341.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 7.26 | 142.32 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 8.03 | 150.25 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 25.33 | 114.15 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 38.29 | 100.01 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 91.54 | 54.85 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 146.14 | 27.29 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 141.83 | 25.16 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 111.88 | 28.42 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 83.95 | 45.39 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 29.50 | 105.32 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 11.61 | 128.02 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 5.43 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 58.69 | 90.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 5.43 | 25.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 146.14 | 167.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.98 | 194.49 | 123.49 | 301.49 | 494.67 | 0.00 | 0.00 | 0.00 |
February | 426.28 | 269.79 | 156.49 | 419.26 | 529.63 | 0.00 | 0.00 | 0.00 |
March | 513.51 | 299.74 | 213.77 | 550.56 | 404.29 | 0.00 | 0.00 | 0.00 |
April | 524.20 | 255.31 | 268.89 | 555.59 | 363.29 | 0.00 | 0.00 | 0.00 |
May | 614.54 | 257.27 | 357.27 | 778.02 | 203.67 | 0.00 | 0.00 | 0.00 |
June | 747.77 | 392.46 | 355.32 | 1124.04 | 102.25 | 0.00 | 0.00 | 0.00 |
July | 678.74 | 322.53 | 356.21 | 1040.07 | 94.29 | 0.00 | 0.00 | 0.00 |
August | 686.30 | 378.12 | 308.19 | 1035.71 | 105.89 | 0.00 | 0.00 | 0.00 |
September | 571.97 | 310.91 | 261.06 | 822.55 | 163.98 | 0.00 | 0.00 | 0.00 |
October | 413.90 | 227.00 | 186.90 | 478.74 | 382.88 | 0.00 | 0.00 | 0.00 |
November | 321.19 | 181.00 | 140.18 | 324.18 | 456.50 | 0.00 | 0.00 | 0.00 |
December | 278.56 | 160.52 | 118.04 | 244.91 | 591.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 508.22 | 270.61 | 237.60 | 640.67 | 323.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.56 | 160.52 | 118.04 | 244.91 | 94.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 747.77 | 392.46 | 357.27 | 1124.04 | 591.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 315.28 | 124.30 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 293.22 | 134.94 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 225.05 | 108.56 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 136.88 | 100.63 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 146.72 | 58.46 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 173.79 | 29.30 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 179.64 | 26.34 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 220.48 | 29.08 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 261.58 | 45.25 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 265.08 | 101.52 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 310.67 | 117.21 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 278.46 | 146.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 233.56 | 84.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 136.88 | 26.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 315.28 | 146.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 4.89 | 191.80 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 5.71 | 197.57 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 23.37 | 146.95 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 38.73 | 125.38 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 92.86 | 68.09 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 151.45 | 34.70 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 146.11 | 32.10 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 109.83 | 38.09 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 80.42 | 62.17 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 25.48 | 140.23 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 8.26 | 171.66 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 3.93 | 220.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 57.88 | 118.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 3.93 | 32.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 151.45 | 220.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.91 | 0.00 | 30.91 | 4.38 | 171.58 | 0.00 | 0.00 | 0.00 |
February | 38.86 | 0.00 | 38.86 | 5.11 | 176.77 | 0.00 | 0.00 | 0.00 |
March | 52.89 | 0.00 | 52.88 | 20.91 | 131.47 | 0.00 | 0.00 | 0.00 |
April | 66.48 | 0.44 | 66.05 | 34.65 | 112.18 | 0.00 | 0.00 | 0.00 |
May | 90.82 | 3.05 | 87.77 | 83.08 | 60.92 | 0.00 | 0.00 | 0.00 |
June | 99.57 | 11.13 | 88.44 | 135.50 | 31.05 | 0.00 | 0.00 | 0.00 |
July | 94.44 | 6.45 | 87.99 | 130.73 | 28.72 | 0.00 | 0.00 | 0.00 |
August | 75.19 | 2.03 | 73.16 | 98.27 | 34.08 | 0.00 | 0.00 | 0.00 |
September | 62.96 | 0.05 | 62.91 | 71.95 | 55.63 | 0.00 | 0.00 | 0.00 |
October | 45.04 | 0.00 | 45.04 | 22.79 | 125.46 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 0.00 | 34.19 | 7.39 | 153.58 | 0.00 | 0.00 | 0.00 |
December | 28.92 | 0.00 | 28.92 | 3.52 | 197.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.13 | 1.93 | 58.20 | 51.79 | 106.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.92 | 0.00 | 28.92 | 3.52 | 28.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.57 | 11.13 | 88.44 | 135.50 | 197.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 979.75 | 806.53 | 173.22 | 1132.23 | 474.80 | 0.00 | 0.00 | 0.00 |
February | 927.09 | 737.13 | 189.95 | 1055.07 | 509.01 | 0.00 | 0.00 | 0.00 |
March | 696.40 | 460.25 | 236.15 | 798.81 | 408.09 | 0.00 | 0.00 | 0.00 |
April | 456.00 | 188.65 | 267.36 | 475.77 | 372.30 | 0.00 | 0.00 | 0.00 |
May | 414.37 | 79.68 | 334.68 | 478.80 | 217.64 | 0.00 | 0.00 | 0.00 |
June | 376.73 | 68.01 | 308.73 | 551.65 | 112.69 | 0.00 | 0.00 | 0.00 |
July | 389.12 | 66.29 | 322.83 | 572.97 | 101.35 | 0.00 | 0.00 | 0.00 |
August | 495.10 | 203.69 | 291.41 | 727.28 | 116.57 | 0.00 | 0.00 | 0.00 |
September | 650.36 | 365.56 | 284.79 | 892.42 | 180.89 | 0.00 | 0.00 | 0.00 |
October | 767.69 | 543.93 | 223.76 | 937.47 | 393.54 | 0.00 | 0.00 | 0.00 |
November | 940.97 | 750.54 | 190.43 | 1114.79 | 449.82 | 0.00 | 0.00 | 0.00 |
December | 898.00 | 726.96 | 171.04 | 1006.21 | 555.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.48 | 414.60 | 249.87 | 810.54 | 323.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.73 | 66.29 | 171.04 | 475.77 | 101.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 979.75 | 806.53 | 334.68 | 1132.23 | 555.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.406052E+10 | 0.166626E+10 |
February | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.343840E+10 | 0.157755E+10 |
March | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.289278E+10 | 0.138861E+10 |
April | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.168137E+10 | 0.120216E+10 |
May | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.175703E+10 | 0.715193E+09 |
June | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.192657E+10 | 0.373677E+09 |
July | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.206613E+10 | 0.344896E+09 |
August | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.262508E+10 | 0.403336E+09 |
September | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.311410E+10 | 0.613379E+09 |
October | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.337770E+10 | 0.134776E+10 |
November | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.387599E+10 | 0.151204E+10 |
December | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.364158E+10 | 0.189877E+10 |
Annual Sum or Average | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.344573E+11 | 0.130436E+11 |
Minimum of Months | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.168137E+10 | 0.344896E+09 |
Maximum of Months | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.406052E+10 | 0.189877E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.113303E+11 | 0.495344E+10 |
February | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.959162E+10 | 0.465427E+10 |
March | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.805531E+10 | 0.413224E+10 |
April | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.464412E+10 | 0.363281E+10 |
May | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.480693E+10 | 0.223007E+10 |
June | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.535320E+10 | 0.111531E+10 |
July | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.574451E+10 | 0.103596E+10 |
August | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.731866E+10 | 0.120617E+10 |
September | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.869702E+10 | 0.182602E+10 |
October | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.943275E+10 | 0.400820E+10 |
November | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.108232E+11 | 0.449662E+10 |
December | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.101575E+11 | 0.559684E+10 |
Annual Sum or Average | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.959552E+11 | 0.388879E+11 |
Minimum of Months | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.464412E+10 | 0.103596E+10 |
Maximum of Months | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.113303E+11 | 0.559684E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.149406E+11 | 0.662030E+10 |
February | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.126682E+11 | 0.624139E+10 |
March | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.106459E+11 | 0.558985E+10 |
April | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.613929E+10 | 0.497063E+10 |
May | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.636896E+10 | 0.299831E+10 |
June | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.713058E+10 | 0.146991E+10 |
July | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.764598E+10 | 0.136295E+10 |
August | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.971644E+10 | 0.157498E+10 |
September | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.115130E+11 | 0.239579E+10 |
October | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.124472E+11 | 0.538471E+10 |
November | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.142772E+11 | 0.602399E+10 |
December | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.133920E+11 | 0.751333E+10 |
Annual Sum or Average | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.126885E+12 | 0.521461E+11 |
Minimum of Months | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.613929E+10 | 0.136295E+10 |
Maximum of Months | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.149406E+11 | 0.751333E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.815364E+09 | 0.326368E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.687672E+09 | 0.313284E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.578320E+09 | 0.273979E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.334792E+09 | 0.240292E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.350650E+09 | 0.138173E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.394985E+09 | 59354268.85 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.425536E+09 | 52170262.68 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.533926E+09 | 62262568.68 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.629233E+09 | 0.104601E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.677454E+09 | 0.260709E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.777663E+09 | 0.295713E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.727734E+09 | 0.377955E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.693333E+10 | 0.250486E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.334792E+09 | 52170262.68 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.815364E+09 | 0.377955E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.424074E+09 | 0.673378E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.456816E+09 | 0.625890E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.638775E+09 | 0.519622E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.561393E+09 | 0.438434E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.861967E+09 | 0.250866E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122741E+10 | 0.110215E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104711E+10 | 97022513.18 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106744E+10 | 0.114716E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.873258E+09 | 0.196842E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.622273E+09 | 0.500548E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.439614E+09 | 0.586503E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.319176E+09 | 0.770882E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.853930E+10 | 0.488492E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.319176E+09 | 97022513.18 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122741E+10 | 0.770882E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 14948739.02 | 0.372896E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 15971538.27 | 0.348471E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 56910890.24 | 0.289004E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 84653293.63 | 0.238276E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.201939E+09 | 0.131142E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.318277E+09 | 59351298.95 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.318755E+09 | 53891030.72 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.241347E+09 | 65182340.68 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.172552E+09 | 0.111415E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 61569368.01 | 0.271556E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 23123665.28 | 0.321763E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 12368094.62 | 0.429331E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.152242E+10 | 0.269228E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 12368094.62 | 53891030.72 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.318755E+09 | 0.429331E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.442162E+09 | 0.657661E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.473624E+09 | 0.613967E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.649928E+09 | 0.514976E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.566582E+09 | 0.437306E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.857823E+09 | 0.256393E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.121903E+10 | 0.119118E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103725E+10 | 0.105542E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106384E+10 | 0.123799E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.875202E+09 | 0.205386E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.632740E+09 | 0.496125E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.456513E+09 | 0.574306E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.334320E+09 | 0.757285E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.860901E+10 | 0.486186E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.334320E+09 | 0.105542E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.121903E+10 | 0.757285E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.621398E+09 | 0.324335E+09 |
February | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.527001E+09 | 0.292901E+09 |
March | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.441383E+09 | 0.263225E+09 |
April | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.249001E+09 | 0.243330E+09 |
May | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.248546E+09 | 0.159490E+09 |
June | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.282698E+09 | 85676629.00 |
July | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.304143E+09 | 81888900.13 |
August | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.394127E+09 | 93185784.33 |
September | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.472667E+09 | 0.132033E+09 |
October | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.517292E+09 | 0.267343E+09 |
November | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.597065E+09 | 0.294181E+09 |
December | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.560836E+09 | 0.349492E+09 |
Annual Sum or Average | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.521616E+10 | 0.258708E+10 |
Minimum of Months | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.248546E+09 | 81888900.13 |
Maximum of Months | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.621398E+09 | 0.349492E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58468616.74 | 0.00 | 58468616.74 | 11722159.59 | 0.304975E+09 |
February | 66376345.10 | 0.00 | 66376345.10 | 13147913.94 | 0.283685E+09 |
March | 0.100024E+09 | 5161.40 | 0.100019E+09 | 47959519.85 | 0.232989E+09 |
April | 0.121681E+09 | 797247.66 | 0.120884E+09 | 70194011.63 | 0.193767E+09 |
May | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.169482E+09 | 0.103214E+09 |
June | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.267135E+09 | 43324558.72 |
July | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.265982E+09 | 39685942.58 |
August | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.204804E+09 | 47327781.60 |
September | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.146882E+09 | 83687990.19 |
October | 85190674.52 | 0.00 | 85190674.52 | 53068495.99 | 0.217669E+09 |
November | 62584379.74 | 0.00 | 62584379.74 | 18859144.13 | 0.262167E+09 |
December | 54704647.81 | 0.00 | 54704647.81 | 9464312.86 | 0.353555E+09 |
Annual Sum or Average | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.127870E+10 | 0.216605E+10 |
Minimum of Months | 54704647.81 | 0.00 | 54704647.81 | 9464312.86 | 39685942.58 |
Maximum of Months | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.267135E+09 | 0.353555E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.371105E+09 | 0.661909E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.478303E+09 | 0.623345E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.691315E+09 | 0.509743E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.676062E+09 | 0.428855E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.957028E+09 | 0.236396E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.134770E+10 | 0.100181E+09 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.128093E+10 | 91338253.61 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.127384E+10 | 0.110512E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.968841E+09 | 0.186319E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.584965E+09 | 0.490480E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.384677E+09 | 0.582574E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.305597E+09 | 0.766631E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.932036E+10 | 0.478828E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.305597E+09 | 91338253.61 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.134770E+10 | 0.766631E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.813906E+09 | 0.324987E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.685234E+09 | 0.311884E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.574340E+09 | 0.272621E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.330736E+09 | 0.239899E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.347291E+09 | 0.137666E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.391820E+09 | 58140469.93 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.421257E+09 | 51766037.26 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.530200E+09 | 61774937.49 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.626440E+09 | 0.103875E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.675621E+09 | 0.259448E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.776710E+09 | 0.294195E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.726428E+09 | 0.376812E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.689998E+10 | 0.249307E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.330736E+09 | 51766037.26 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.813906E+09 | 0.376812E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 14089420.33 | 0.371197E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 14080559.82 | 0.347519E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 53614042.04 | 0.287687E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 80840516.23 | 0.237644E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.198525E+09 | 0.129845E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.311441E+09 | 58116597.88 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.311269E+09 | 53539589.46 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.234416E+09 | 64437453.37 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.168666E+09 | 0.109773E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 59304431.28 | 0.268980E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 21626465.58 | 0.319386E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 11457595.75 | 0.427742E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.147933E+10 | 0.267587E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 11457595.75 | 53539589.46 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.311441E+09 | 0.427742E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.383509E+09 | 0.638030E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.489686E+09 | 0.605222E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.702549E+09 | 0.503129E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.681797E+09 | 0.426740E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.954408E+09 | 0.241366E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.133203E+10 | 0.109412E+09 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.126487E+10 | 0.100253E+09 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.126434E+10 | 0.119785E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.969184E+09 | 0.193332E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.596316E+09 | 0.484347E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.397302E+09 | 0.564248E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.316434E+09 | 0.746604E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.935243E+10 | 0.473247E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.316434E+09 | 0.100253E+09 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.133203E+10 | 0.746604E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 15150641.62 | 0.509392E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 16424475.06 | 0.471179E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 68967457.80 | 0.389369E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.107941E+09 | 0.319561E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.260188E+09 | 0.178468E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.402757E+09 | 87184908.60 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.400138E+09 | 83628266.54 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.302693E+09 | 99791098.72 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.214634E+09 | 0.161254E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 73275959.35 | 0.375216E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 24873593.16 | 0.439578E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 12623440.83 | 0.582765E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.189967E+10 | 0.369739E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 12623440.83 | 83628266.54 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.402757E+09 | 0.582765E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34116379.75 | 0.00 | 34116379.75 | 5585153.84 | 0.187783E+09 |
February | 38730531.38 | 0.00 | 38730531.38 | 6054741.59 | 0.173697E+09 |
March | 58364136.20 | 3011.67 | 58361124.52 | 25424260.66 | 0.143538E+09 |
April | 71000608.82 | 465193.22 | 70535415.60 | 39791703.25 | 0.117803E+09 |
May | 0.100224E+09 | 3361308.60 | 96862221.74 | 95916050.16 | 65790632.46 |
June | 0.106339E+09 | 11891705.58 | 94447236.21 | 0.148473E+09 | 32139967.35 |
July | 0.104222E+09 | 7114228.39 | 97107710.86 | 0.147508E+09 | 30828841.82 |
August | 82980016.94 | 2245617.48 | 80734399.46 | 0.111585E+09 | 36787131.01 |
September | 67238296.50 | 53699.58 | 67184596.92 | 79122958.76 | 59445030.93 |
October | 49708673.90 | 0.00 | 49708673.90 | 27012552.74 | 0.138320E+09 |
November | 36517923.36 | 0.00 | 36517923.36 | 9169436.37 | 0.162046E+09 |
December | 31920107.62 | 0.00 | 31920107.62 | 4653522.99 | 0.214831E+09 |
Annual Sum or Average | 0.781361E+09 | 25134764.53 | 0.756226E+09 | 0.700296E+09 | 0.136301E+10 |
Minimum of Months | 31920107.62 | 0.00 | 31920107.62 | 4653522.99 | 30828841.82 |
Maximum of Months | 0.106339E+09 | 11891705.58 | 97107710.86 | 0.148473E+09 | 0.214831E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327974E+09 | 0.269987E+09 | 57987003.41 | 0.382552E+09 | 0.158382E+09 |
February | 0.280311E+09 | 0.222878E+09 | 57433344.00 | 0.322910E+09 | 0.152277E+09 |
March | 0.233121E+09 | 0.154069E+09 | 79051433.12 | 0.271411E+09 | 0.135132E+09 |
April | 0.147724E+09 | 61112968.53 | 86610767.13 | 0.157668E+09 | 0.118358E+09 |
May | 0.138711E+09 | 26674072.02 | 0.112037E+09 | 0.164747E+09 | 71058964.81 |
June | 0.122044E+09 | 22030990.58 | 0.100013E+09 | 0.182666E+09 | 35366030.07 |
July | 0.130258E+09 | 22190312.50 | 0.108068E+09 | 0.195313E+09 | 32980406.98 |
August | 0.165737E+09 | 68185376.53 | 97551239.88 | 0.247258E+09 | 38134035.07 |
September | 0.210685E+09 | 0.118425E+09 | 92260125.35 | 0.292390E+09 | 58472241.73 |
October | 0.256987E+09 | 0.182083E+09 | 74903651.52 | 0.316883E+09 | 0.131577E+09 |
November | 0.304831E+09 | 0.243141E+09 | 61689551.46 | 0.365009E+09 | 0.144539E+09 |
December | 0.300608E+09 | 0.243350E+09 | 57257659.68 | 0.340810E+09 | 0.183531E+09 |
Annual Sum or Average | 0.261899E+10 | 0.163413E+10 | 0.984863E+09 | 0.323962E+10 | 0.125981E+10 |
Minimum of Months | 0.122044E+09 | 22030990.58 | 57257659.68 | 0.157668E+09 | 32980406.98 |
Maximum of Months | 0.327974E+09 | 0.269987E+09 | 0.112037E+09 | 0.382552E+09 | 0.183531E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.890190E+09 | 0.732801E+09 | 0.157389E+09 | 0.103832E+10 | 0.429880E+09 |
February | 0.760821E+09 | 0.604935E+09 | 0.155886E+09 | 0.876443E+09 | 0.413310E+09 |
March | 0.632738E+09 | 0.418176E+09 | 0.214562E+09 | 0.736664E+09 | 0.366776E+09 |
April | 0.400952E+09 | 0.165873E+09 | 0.235079E+09 | 0.427943E+09 | 0.321247E+09 |
May | 0.376489E+09 | 72398887.53 | 0.304090E+09 | 0.447156E+09 | 0.192869E+09 |
June | 0.331253E+09 | 59796614.77 | 0.271456E+09 | 0.495793E+09 | 95990639.56 |
July | 0.353548E+09 | 60229047.04 | 0.293319E+09 | 0.530119E+09 | 89515570.53 |
August | 0.449843E+09 | 0.185069E+09 | 0.264774E+09 | 0.671110E+09 | 0.103504E+09 |
September | 0.571844E+09 | 0.321431E+09 | 0.250413E+09 | 0.793606E+09 | 0.158706E+09 |
October | 0.697515E+09 | 0.494211E+09 | 0.203304E+09 | 0.860084E+09 | 0.357126E+09 |
November | 0.827373E+09 | 0.659935E+09 | 0.167438E+09 | 0.990709E+09 | 0.392309E+09 |
December | 0.815911E+09 | 0.660502E+09 | 0.155409E+09 | 0.925027E+09 | 0.498140E+09 |
Annual Sum or Average | 0.710848E+10 | 0.443536E+10 | 0.267312E+10 | 0.879298E+10 | 0.341937E+10 |
Minimum of Months | 0.331253E+09 | 59796614.77 | 0.155409E+09 | 0.427943E+09 | 89515570.53 |
Maximum of Months | 0.890190E+09 | 0.732801E+09 | 0.304090E+09 | 0.103832E+10 | 0.498140E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.813322E+09 | 0.324504E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.684244E+09 | 0.313078E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.575161E+09 | 0.272946E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.332360E+09 | 0.239437E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.347976E+09 | 0.137377E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.392284E+09 | 57988827.14 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.423318E+09 | 50584561.35 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.530651E+09 | 60683329.31 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.626402E+09 | 0.102523E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.674884E+09 | 0.258738E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.774772E+09 | 0.294374E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.724817E+09 | 0.377466E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.690019E+10 | 0.248970E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.332360E+09 | 50584561.35 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.813322E+09 | 0.377466E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.422334E+09 | 0.667893E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.453701E+09 | 0.624291E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.634592E+09 | 0.516989E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.557123E+09 | 0.436320E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.855935E+09 | 0.248968E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122077E+10 | 0.107729E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104203E+10 | 94094527.55 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106160E+10 | 0.111792E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.869653E+09 | 0.192776E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.619260E+09 | 0.496044E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.437108E+09 | 0.582825E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.317762E+09 | 0.768147E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.849187E+10 | 0.484787E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.317762E+09 | 94094527.55 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122077E+10 | 0.768147E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 15572347.04 | 0.369048E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 16146964.79 | 0.346942E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 56756108.80 | 0.287938E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 83635299.81 | 0.237687E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.199406E+09 | 0.131275E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.316042E+09 | 59031050.10 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.317182E+09 | 53266470.01 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.239666E+09 | 64494648.45 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.172367E+09 | 0.110067E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 61890568.44 | 0.269655E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 23466660.87 | 0.318993E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 12858537.26 | 0.427123E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.151499E+10 | 0.267552E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 12858537.26 | 53266470.01 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.317182E+09 | 0.427123E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.442752E+09 | 0.651708E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.472198E+09 | 0.612093E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.646466E+09 | 0.512760E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.562241E+09 | 0.435785E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.850613E+09 | 0.256227E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.121202E+10 | 0.118055E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103200E+10 | 0.103823E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.105791E+10 | 0.122147E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.871966E+09 | 0.202548E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.630880E+09 | 0.491814E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.455853E+09 | 0.569945E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.334423E+09 | 0.754310E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.856933E+10 | 0.483121E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.334423E+09 | 0.103823E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.121202E+10 | 0.754310E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.117232E+10 | 0.493123E+09 |
February | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.987666E+09 | 0.472992E+09 |
March | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.833548E+09 | 0.408672E+09 |
April | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.482558E+09 | 0.356469E+09 |
May | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.512932E+09 | 0.200315E+09 |
June | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.587138E+09 | 80277714.71 |
July | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.629231E+09 | 70998533.07 |
August | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.784463E+09 | 85835123.19 |
September | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.917484E+09 | 0.150089E+09 |
October | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.980961E+09 | 0.388924E+09 |
November | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.111901E+10 | 0.447409E+09 |
December | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.104172E+10 | 0.574526E+09 |
Annual Sum or Average | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.100490E+11 | 0.372963E+10 |
Minimum of Months | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.482558E+09 | 70998533.07 |
Maximum of Months | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.117232E+10 | 0.574526E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 59565375.61 | 0.305734E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 66048798.42 | 0.285361E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.311660E+09 | 0.238372E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.491067E+09 | 0.200619E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.129801E+10 | 0.108341E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.216779E+10 | 0.498128E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.216447E+10 | 0.476102E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.163075E+10 | 0.563745E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.114830E+10 | 0.914502E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.359800E+09 | 0.222774E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.107710E+09 | 0.266224E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 48246363.49 | 0.351572E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.985342E+10 | 0.222424E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 48246363.49 | 0.476102E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.216779E+10 | 0.351572E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 52214887.82 | 0.312355E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 60038404.92 | 0.291660E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.295272E+09 | 0.243608E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.471252E+09 | 0.205111E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.127383E+10 | 0.110483E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.214847E+10 | 0.510455E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.214514E+10 | 0.489262E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.161311E+10 | 0.578867E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.113275E+10 | 0.934111E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.345775E+09 | 0.227096E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.100364E+09 | 0.272048E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 43093722.43 | 0.359348E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.968131E+10 | 0.227298E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 43093722.43 | 0.489262E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.214847E+10 | 0.359348E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 19435984.00 | 0.381179E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 19416953.99 | 0.363479E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 67839329.76 | 0.305730E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 99242997.08 | 0.259216E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.245180E+09 | 0.146908E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.378802E+09 | 70739948.13 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.379879E+09 | 67391694.33 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.299665E+09 | 76131209.33 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.217593E+09 | 0.117659E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 79022817.44 | 0.282093E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 30089913.54 | 0.331815E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 14536383.31 | 0.449521E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.185070E+10 | 0.285186E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 14536383.31 | 67391694.33 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.379879E+09 | 0.449521E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851689E+09 | 0.520925E+09 | 0.330764E+09 | 0.807523E+09 | 0.132492E+10 |
February | 0.103127E+10 | 0.652680E+09 | 0.378585E+09 | 0.101426E+10 | 0.128128E+10 |
March | 0.137538E+10 | 0.802812E+09 | 0.572564E+09 | 0.147463E+10 | 0.108284E+10 |
April | 0.135873E+10 | 0.661766E+09 | 0.696961E+09 | 0.144010E+10 | 0.941657E+09 |
May | 0.164598E+10 | 0.689069E+09 | 0.956909E+09 | 0.208386E+10 | 0.545499E+09 |
June | 0.193823E+10 | 0.101725E+10 | 0.920982E+09 | 0.291350E+10 | 0.265028E+09 |
July | 0.181794E+10 | 0.863862E+09 | 0.954079E+09 | 0.278573E+10 | 0.252551E+09 |
August | 0.183819E+10 | 0.101275E+10 | 0.825447E+09 | 0.277403E+10 | 0.283616E+09 |
September | 0.148255E+10 | 0.805873E+09 | 0.676677E+09 | 0.213204E+10 | 0.425043E+09 |
October | 0.110859E+10 | 0.607994E+09 | 0.500598E+09 | 0.128227E+10 | 0.102551E+10 |
November | 0.832518E+09 | 0.469164E+09 | 0.363353E+09 | 0.840266E+09 | 0.118325E+10 |
December | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.655980E+09 | 0.158467E+10 |
Annual Sum or Average | 0.160272E+11 | 0.853408E+10 | 0.749308E+10 | 0.202042E+11 | 0.101959E+11 |
Minimum of Months | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.655980E+09 | 0.252551E+09 |
Maximum of Months | 0.193823E+10 | 0.101725E+10 | 0.956909E+09 | 0.291350E+10 | 0.158467E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.844445E+09 | 0.332918E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.709349E+09 | 0.326445E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.602766E+09 | 0.290756E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.354784E+09 | 0.260837E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.392981E+09 | 0.156585E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.450463E+09 | 75944471.02 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.481156E+09 | 70545658.79 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.590537E+09 | 77895377.03 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.678011E+09 | 0.117279E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.709999E+09 | 0.271902E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.805252E+09 | 0.303814E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.745839E+09 | 0.393543E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.736558E+10 | 0.267846E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.354784E+09 | 70545658.79 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.844445E+09 | 0.393543E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 13099538.31 | 0.513716E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 13809707.87 | 0.477959E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 62605222.11 | 0.393583E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.100391E+09 | 0.324986E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.248707E+09 | 0.182362E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.392549E+09 | 89940344.59 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.391347E+09 | 85981999.90 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.294176E+09 | 0.102008E+09 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.208454E+09 | 0.161150E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 68235358.47 | 0.375591E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 21400798.53 | 0.444941E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 10526612.27 | 0.591426E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.182530E+10 | 0.374364E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 10526612.27 | 85981999.90 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.392549E+09 | 0.591426E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82801480.44 | 0.00 | 82801480.44 | 11720206.56 | 0.459550E+09 |
February | 94000165.32 | 0.00 | 94000165.32 | 12355597.96 | 0.427637E+09 |
March | 0.141652E+09 | 7309.43 | 0.141644E+09 | 56013129.44 | 0.352140E+09 |
April | 0.172321E+09 | 1129037.94 | 0.171192E+09 | 89820164.51 | 0.290766E+09 |
May | 0.243246E+09 | 8157997.15 | 0.235088E+09 | 0.222519E+09 | 0.163160E+09 |
June | 0.258088E+09 | 28861527.34 | 0.229226E+09 | 0.351215E+09 | 80469967.09 |
July | 0.252950E+09 | 17266446.42 | 0.235683E+09 | 0.350140E+09 | 76928421.09 |
August | 0.201395E+09 | 5450181.22 | 0.195945E+09 | 0.263201E+09 | 91267067.00 |
September | 0.163189E+09 | 130330.49 | 0.163059E+09 | 0.186505E+09 | 0.144182E+09 |
October | 0.120644E+09 | 0.00 | 0.120644E+09 | 61050433.77 | 0.336043E+09 |
November | 88630099.07 | 0.00 | 88630099.07 | 19147375.53 | 0.398080E+09 |
December | 77471061.88 | 0.00 | 77471061.88 | 9418199.88 | 0.529108E+09 |
Annual Sum or Average | 0.189639E+10 | 61002829.99 | 0.183538E+10 | 0.163310E+10 | 0.334933E+10 |
Minimum of Months | 77471061.88 | 0.00 | 77471061.88 | 9418199.88 | 76928421.09 |
Maximum of Months | 0.258088E+09 | 28861527.34 | 0.235683E+09 | 0.351215E+09 | 0.529108E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262417E+10 | 0.216021E+10 | 0.463962E+09 | 0.303256E+10 | 0.127170E+10 |
February | 0.224281E+10 | 0.178327E+10 | 0.459532E+09 | 0.255243E+10 | 0.123140E+10 |
March | 0.186523E+10 | 0.123273E+10 | 0.632501E+09 | 0.213954E+10 | 0.109302E+10 |
April | 0.118196E+10 | 0.488973E+09 | 0.692985E+09 | 0.123320E+10 | 0.965007E+09 |
May | 0.110984E+10 | 0.213423E+09 | 0.896420E+09 | 0.128241E+10 | 0.582922E+09 |
June | 0.976492E+09 | 0.176273E+09 | 0.800219E+09 | 0.142988E+10 | 0.292087E+09 |
July | 0.104221E+10 | 0.177548E+09 | 0.864667E+09 | 0.153465E+10 | 0.271449E+09 |
August | 0.132608E+10 | 0.545560E+09 | 0.780521E+09 | 0.194795E+10 | 0.312234E+09 |
September | 0.168572E+10 | 0.947538E+09 | 0.738186E+09 | 0.231316E+10 | 0.468880E+09 |
October | 0.205619E+10 | 0.145687E+10 | 0.599314E+09 | 0.251091E+10 | 0.105404E+10 |
November | 0.243899E+10 | 0.194541E+10 | 0.493587E+09 | 0.288953E+10 | 0.116593E+10 |
December | 0.240520E+10 | 0.194708E+10 | 0.458126E+09 | 0.269503E+10 | 0.148668E+10 |
Annual Sum or Average | 0.209549E+11 | 0.130749E+11 | 0.788002E+10 | 0.255612E+11 | 0.101954E+11 |
Minimum of Months | 0.976492E+09 | 0.176273E+09 | 0.458126E+09 | 0.123320E+10 | 0.271449E+09 |
Maximum of Months | 0.262417E+10 | 0.216021E+10 | 0.896420E+09 | 0.303256E+10 | 0.148668E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1516.03 | 622.11 | 1327.33 | 1092.65 | 234.67 | 0.00 | 0.00 |
February | 1421.30 | 652.09 | 1255.98 | 998.64 | 257.34 | 0.00 | 0.00 |
March | 1080.04 | 518.45 | 943.45 | 623.53 | 319.92 | 0.00 | 0.00 |
April | 648.68 | 463.80 | 617.77 | 255.57 | 362.20 | 0.00 | 0.00 |
May | 656.00 | 267.02 | 561.37 | 107.95 | 453.41 | 0.00 | 0.00 |
June | 743.28 | 144.17 | 510.38 | 92.13 | 418.25 | 0.00 | 0.00 |
July | 771.41 | 128.77 | 527.16 | 89.81 | 437.35 | 0.00 | 0.00 |
August | 980.09 | 150.59 | 670.74 | 275.95 | 394.79 | 0.00 | 0.00 |
September | 1201.43 | 236.64 | 881.07 | 495.25 | 385.82 | 0.00 | 0.00 |
October | 1261.09 | 503.19 | 1040.04 | 736.90 | 303.14 | 0.00 | 0.00 |
November | 1495.37 | 583.35 | 1274.79 | 1016.81 | 257.98 | 0.00 | 0.00 |
December | 1359.61 | 708.92 | 1216.57 | 984.85 | 231.72 | 0.00 | 0.00 |
Annual Sum or Average | 1092.63 | 413.61 | 900.20 | 561.69 | 338.52 | 0.00 | 0.00 |
Minimum of Months | 648.68 | 128.77 | 510.38 | 89.81 | 231.72 | 0.00 | 0.00 |
Maximum of Months | 1516.03 | 708.92 | 1327.33 | 1092.65 | 453.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4230.25 | 1849.40 | 3737.67 | 3076.84 | 660.83 | 0.00 | 0.00 |
February | 3964.79 | 1923.89 | 3536.75 | 2812.11 | 724.64 | 0.00 | 0.00 |
March | 3007.51 | 1542.80 | 2656.69 | 1755.81 | 900.88 | 0.00 | 0.00 |
April | 1791.71 | 1401.55 | 1739.60 | 719.67 | 1019.93 | 0.00 | 0.00 |
May | 1794.70 | 832.61 | 1580.77 | 303.98 | 1276.78 | 0.00 | 0.00 |
June | 2065.28 | 430.29 | 1437.19 | 259.44 | 1177.75 | 0.00 | 0.00 |
July | 2144.75 | 386.78 | 1484.44 | 252.89 | 1231.56 | 0.00 | 0.00 |
August | 2732.48 | 450.33 | 1888.76 | 777.06 | 1111.70 | 0.00 | 0.00 |
September | 3355.33 | 704.48 | 2481.05 | 1394.59 | 1086.46 | 0.00 | 0.00 |
October | 3521.79 | 1496.49 | 2928.68 | 2075.07 | 853.61 | 0.00 | 0.00 |
November | 4175.63 | 1734.81 | 3589.72 | 2863.26 | 726.46 | 0.00 | 0.00 |
December | 3792.38 | 2089.62 | 3425.79 | 2773.28 | 652.52 | 0.00 | 0.00 |
Annual Sum or Average | 3042.72 | 1233.13 | 2534.91 | 1581.67 | 953.24 | 0.00 | 0.00 |
Minimum of Months | 1791.71 | 386.78 | 1437.19 | 252.89 | 652.52 | 0.00 | 0.00 |
Maximum of Months | 4230.25 | 2089.62 | 3737.67 | 3076.84 | 1276.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5578.17 | 2471.74 | 4855.45 | 3996.99 | 858.45 | 0.00 | 0.00 |
February | 5236.53 | 2579.94 | 4594.44 | 3653.09 | 941.35 | 0.00 | 0.00 |
March | 3974.72 | 2087.01 | 3451.19 | 2280.90 | 1170.29 | 0.00 | 0.00 |
April | 2368.55 | 1917.68 | 2259.84 | 934.90 | 1324.95 | 0.00 | 0.00 |
May | 2377.90 | 1119.44 | 2053.51 | 394.89 | 1658.62 | 0.00 | 0.00 |
June | 2750.99 | 567.10 | 1866.99 | 337.03 | 1529.97 | 0.00 | 0.00 |
July | 2854.68 | 508.87 | 1928.38 | 328.51 | 1599.86 | 0.00 | 0.00 |
August | 3627.70 | 588.03 | 2453.61 | 1009.44 | 1444.17 | 0.00 | 0.00 |
September | 4441.76 | 924.30 | 3223.02 | 1811.65 | 1411.37 | 0.00 | 0.00 |
October | 4647.24 | 2010.42 | 3804.52 | 2695.63 | 1108.89 | 0.00 | 0.00 |
November | 5508.17 | 2324.07 | 4663.25 | 3719.54 | 943.71 | 0.00 | 0.00 |
December | 5000.00 | 2805.16 | 4450.30 | 3602.64 | 847.66 | 0.00 | 0.00 |
Annual Sum or Average | 4023.51 | 1653.54 | 3292.99 | 2054.68 | 1238.31 | 0.00 | 0.00 |
Minimum of Months | 2368.55 | 508.87 | 1866.99 | 328.51 | 847.66 | 0.00 | 0.00 |
Maximum of Months | 5578.17 | 2805.16 | 4855.45 | 3996.99 | 1658.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.75 | 355.26 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 459.20 | 374.33 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 448.70 | 290.59 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 343.04 | 259.15 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 451.66 | 144.18 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 625.77 | 65.27 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 549.72 | 55.60 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 597.55 | 65.75 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 578.95 | 115.58 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 482.13 | 281.09 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 460.01 | 330.74 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 372.39 | 410.44 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 484.51 | 228.20 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 343.04 | 55.60 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 625.77 | 410.44 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.17 | 377.27 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 194.41 | 389.87 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 259.73 | 296.00 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 249.16 | 258.55 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 394.10 | 143.12 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 591.11 | 66.86 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 504.99 | 58.24 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 486.73 | 69.99 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 403.60 | 121.60 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 257.18 | 284.57 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 180.05 | 340.71 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 122.30 | 435.89 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 317.79 | 236.07 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 122.30 | 58.24 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 591.11 | 435.89 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 232.00 | 121.09 | 209.91 | 172.79 | 37.11 | 0.00 | 0.00 |
February | 217.84 | 121.07 | 198.62 | 157.93 | 40.70 | 0.00 | 0.00 |
March | 164.79 | 98.28 | 149.20 | 98.61 | 50.59 | 0.00 | 0.00 |
April | 96.07 | 93.88 | 97.70 | 40.42 | 57.28 | 0.00 | 0.00 |
May | 92.80 | 59.55 | 88.78 | 17.07 | 71.70 | 0.00 | 0.00 |
June | 109.07 | 33.05 | 80.71 | 14.57 | 66.14 | 0.00 | 0.00 |
July | 113.55 | 30.57 | 83.37 | 14.20 | 69.16 | 0.00 | 0.00 |
August | 147.15 | 34.79 | 106.07 | 43.64 | 62.43 | 0.00 | 0.00 |
September | 182.36 | 50.94 | 139.34 | 78.32 | 61.02 | 0.00 | 0.00 |
October | 193.13 | 99.81 | 164.47 | 116.54 | 47.94 | 0.00 | 0.00 |
November | 230.35 | 113.50 | 201.60 | 160.80 | 40.80 | 0.00 | 0.00 |
December | 209.39 | 130.49 | 192.39 | 155.75 | 36.65 | 0.00 | 0.00 |
Annual Sum or Average | 165.40 | 82.04 | 142.36 | 88.83 | 53.53 | 0.00 | 0.00 |
Minimum of Months | 92.80 | 30.57 | 80.71 | 14.20 | 36.65 | 0.00 | 0.00 |
Maximum of Months | 232.00 | 130.49 | 209.91 | 172.79 | 71.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.38 | 113.86 | 21.83 | 0.00 | 21.83 | 0.00 | 0.00 |
February | 5.43 | 117.26 | 27.44 | 0.00 | 27.44 | 0.00 | 0.00 |
March | 17.91 | 86.99 | 37.34 | 0.00 | 37.34 | 0.00 | 0.00 |
April | 27.08 | 74.76 | 46.94 | 0.31 | 46.64 | 0.00 | 0.00 |
May | 63.28 | 38.54 | 64.13 | 2.15 | 61.98 | 0.00 | 0.00 |
June | 103.06 | 16.71 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
July | 99.31 | 14.82 | 66.69 | 4.55 | 62.14 | 0.00 | 0.00 |
August | 76.46 | 17.67 | 53.10 | 1.44 | 51.66 | 0.00 | 0.00 |
September | 56.67 | 32.29 | 44.46 | 0.04 | 44.42 | 0.00 | 0.00 |
October | 19.81 | 81.27 | 31.81 | 0.00 | 31.81 | 0.00 | 0.00 |
November | 7.28 | 101.14 | 24.15 | 0.00 | 24.15 | 0.00 | 0.00 |
December | 3.53 | 132.00 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Annual Sum or Average | 40.55 | 68.68 | 42.46 | 1.37 | 41.10 | 0.00 | 0.00 |
Minimum of Months | 3.53 | 14.82 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Maximum of Months | 103.06 | 132.00 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 425.55 | 351.58 | 421.44 | 313.29 | 108.15 | 0.00 | 0.00 |
February | 467.30 | 372.93 | 461.49 | 332.35 | 129.13 | 0.00 | 0.00 |
March | 468.90 | 288.46 | 443.31 | 273.16 | 170.15 | 0.00 | 0.00 |
April | 384.65 | 254.23 | 384.26 | 178.20 | 206.07 | 0.00 | 0.00 |
May | 483.44 | 136.12 | 418.28 | 149.99 | 268.30 | 0.00 | 0.00 |
June | 669.44 | 59.41 | 474.83 | 214.46 | 260.37 | 0.00 | 0.00 |
July | 634.51 | 52.41 | 443.62 | 179.03 | 264.59 | 0.00 | 0.00 |
August | 672.59 | 63.37 | 475.79 | 243.63 | 232.16 | 0.00 | 0.00 |
September | 613.93 | 110.42 | 460.21 | 253.38 | 206.83 | 0.00 | 0.00 |
October | 468.77 | 278.11 | 412.60 | 259.21 | 153.39 | 0.00 | 0.00 |
November | 438.41 | 328.60 | 412.65 | 291.55 | 121.10 | 0.00 | 0.00 |
December | 369.38 | 410.97 | 379.83 | 274.99 | 104.84 | 0.00 | 0.00 |
Annual Sum or Average | 508.20 | 224.75 | 432.11 | 246.37 | 185.74 | 0.00 | 0.00 |
Minimum of Months | 369.38 | 52.41 | 379.83 | 149.99 | 104.84 | 0.00 | 0.00 |
Maximum of Months | 672.59 | 410.97 | 475.79 | 332.35 | 268.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 138.20 | 366.56 | 186.29 | 97.25 | 89.03 | 0.00 | 0.00 |
February | 198.85 | 384.44 | 247.45 | 134.91 | 112.54 | 0.00 | 0.00 |
March | 276.06 | 289.00 | 303.45 | 149.88 | 153.57 | 0.00 | 0.00 |
April | 290.72 | 252.81 | 320.79 | 128.05 | 192.74 | 0.00 | 0.00 |
May | 429.32 | 137.46 | 387.44 | 131.33 | 256.11 | 0.00 | 0.00 |
June | 633.77 | 64.35 | 461.79 | 206.07 | 255.72 | 0.00 | 0.00 |
July | 588.29 | 57.25 | 422.74 | 166.97 | 255.78 | 0.00 | 0.00 |
August | 559.12 | 68.33 | 409.54 | 190.87 | 218.67 | 0.00 | 0.00 |
September | 436.87 | 114.82 | 341.57 | 155.51 | 186.06 | 0.00 | 0.00 |
October | 241.37 | 277.85 | 246.72 | 113.51 | 133.21 | 0.00 | 0.00 |
November | 155.54 | 334.83 | 190.78 | 90.51 | 100.27 | 0.00 | 0.00 |
December | 112.87 | 428.90 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Annual Sum or Average | 339.11 | 230.56 | 307.20 | 137.02 | 170.17 | 0.00 | 0.00 |
Minimum of Months | 112.87 | 57.25 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Maximum of Months | 633.77 | 428.90 | 461.79 | 206.07 | 256.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 504.49 | 446.18 | 502.10 | 374.40 | 127.70 | 0.00 | 0.00 |
February | 479.49 | 474.79 | 489.80 | 342.18 | 147.62 | 0.00 | 0.00 |
March | 405.92 | 380.67 | 404.18 | 213.66 | 190.52 | 0.00 | 0.00 |
April | 282.48 | 337.89 | 313.38 | 88.24 | 225.14 | 0.00 | 0.00 |
May | 359.55 | 187.87 | 331.28 | 41.65 | 289.63 | 0.00 | 0.00 |
June | 471.32 | 93.61 | 327.20 | 48.60 | 278.60 | 0.00 | 0.00 |
July | 473.33 | 86.49 | 325.10 | 40.63 | 284.47 | 0.00 | 0.00 |
August | 496.94 | 103.26 | 344.85 | 97.67 | 247.19 | 0.00 | 0.00 |
September | 531.75 | 168.37 | 398.21 | 169.77 | 228.44 | 0.00 | 0.00 |
October | 471.82 | 369.14 | 425.27 | 252.50 | 172.77 | 0.00 | 0.00 |
November | 516.84 | 419.89 | 489.11 | 348.41 | 140.70 | 0.00 | 0.00 |
December | 445.20 | 518.44 | 461.11 | 337.46 | 123.65 | 0.00 | 0.00 |
Annual Sum or Average | 453.08 | 297.92 | 400.44 | 195.42 | 205.02 | 0.00 | 0.00 |
Minimum of Months | 282.48 | 86.49 | 313.38 | 40.63 | 123.65 | 0.00 | 0.00 |
Maximum of Months | 531.75 | 518.44 | 502.10 | 374.40 | 289.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 443.87 | 353.05 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 456.74 | 373.83 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 446.01 | 289.26 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 340.41 | 257.96 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 448.38 | 143.14 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 622.16 | 63.78 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 546.99 | 53.91 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 594.14 | 64.05 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 576.49 | 113.23 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 480.22 | 278.85 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 458.16 | 329.04 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 371.11 | 409.58 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 482.08 | 226.67 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 340.41 | 53.91 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 622.16 | 409.58 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.80 | 373.79 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 193.91 | 388.47 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 258.26 | 294.65 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 247.00 | 257.64 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 390.41 | 143.06 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 587.61 | 66.40 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 502.50 | 57.43 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 483.90 | 69.12 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 402.23 | 119.93 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 256.53 | 282.18 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 179.98 | 338.01 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 122.68 | 434.12 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 316.31 | 234.58 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 122.68 | 57.43 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 587.61 | 434.12 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.70 | 184.11 | 384.89 | 316.84 | 68.05 | 0.00 | 0.00 |
February | 408.26 | 195.52 | 364.20 | 289.58 | 74.62 | 0.00 | 0.00 |
March | 311.21 | 152.58 | 273.57 | 180.80 | 92.77 | 0.00 | 0.00 |
April | 186.17 | 137.53 | 179.14 | 74.11 | 105.03 | 0.00 | 0.00 |
May | 191.51 | 74.79 | 162.78 | 31.30 | 131.48 | 0.00 | 0.00 |
June | 226.52 | 30.97 | 148.00 | 26.72 | 121.28 | 0.00 | 0.00 |
July | 234.93 | 26.51 | 152.86 | 26.04 | 126.82 | 0.00 | 0.00 |
August | 292.88 | 32.05 | 194.50 | 80.02 | 114.48 | 0.00 | 0.00 |
September | 353.97 | 57.90 | 255.49 | 143.61 | 111.88 | 0.00 | 0.00 |
October | 366.25 | 145.21 | 301.58 | 213.68 | 87.90 | 0.00 | 0.00 |
November | 431.72 | 172.61 | 369.65 | 294.84 | 74.81 | 0.00 | 0.00 |
December | 388.93 | 214.50 | 352.77 | 285.58 | 67.19 | 0.00 | 0.00 |
Annual Sum or Average | 318.65 | 118.27 | 261.03 | 162.87 | 98.16 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 26.51 | 148.00 | 26.04 | 67.19 | 0.00 | 0.00 |
Maximum of Months | 437.70 | 214.50 | 384.89 | 316.84 | 131.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.24 | 1141.48 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 27.30 | 1179.57 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 116.36 | 889.98 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 189.45 | 773.99 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 484.62 | 404.50 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 836.34 | 192.18 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 808.12 | 177.76 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 608.85 | 210.48 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 443.02 | 352.82 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 134.33 | 831.74 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 41.55 | 1027.10 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 18.01 | 1312.62 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 312.45 | 705.30 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 18.01 | 177.76 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 836.34 | 1312.62 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.49 | 1166.20 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 24.82 | 1205.60 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 110.24 | 909.53 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 181.81 | 791.32 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 475.59 | 412.49 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 828.89 | 196.93 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 800.90 | 182.67 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 602.26 | 216.12 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 437.02 | 360.38 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 129.10 | 847.88 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 38.72 | 1049.57 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 16.09 | 1341.65 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 306.99 | 720.76 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 16.09 | 182.67 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 828.89 | 1341.65 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 587.65 | 724.90 | 607.70 | 410.53 | 197.18 | 0.00 | 0.00 |
February | 690.04 | 784.36 | 708.90 | 467.24 | 241.66 | 0.00 | 0.00 |
March | 791.94 | 617.99 | 746.72 | 423.02 | 323.70 | 0.00 | 0.00 |
April | 724.21 | 557.38 | 705.02 | 306.23 | 398.79 | 0.00 | 0.00 |
May | 1011.95 | 312.64 | 805.68 | 281.30 | 524.38 | 0.00 | 0.00 |
June | 1441.89 | 156.76 | 936.56 | 420.50 | 516.06 | 0.00 | 0.00 |
July | 1360.36 | 144.60 | 866.32 | 345.97 | 520.34 | 0.00 | 0.00 |
August | 1366.95 | 162.28 | 885.28 | 434.47 | 450.81 | 0.00 | 0.00 |
September | 1165.32 | 251.86 | 801.74 | 408.87 | 392.87 | 0.00 | 0.00 |
October | 768.93 | 585.32 | 659.29 | 372.70 | 286.59 | 0.00 | 0.00 |
November | 626.69 | 681.96 | 603.41 | 382.04 | 221.37 | 0.00 | 0.00 |
December | 489.86 | 867.47 | 544.63 | 355.24 | 189.38 | 0.00 | 0.00 |
Annual Sum or Average | 919.92 | 485.68 | 739.28 | 383.38 | 355.90 | 0.00 | 0.00 |
Minimum of Months | 489.86 | 144.60 | 544.63 | 281.30 | 189.38 | 0.00 | 0.00 |
Maximum of Months | 1441.89 | 867.47 | 936.56 | 467.24 | 524.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1090.81 | 787.49 | 1045.22 | 806.53 | 238.69 | 0.00 | 0.00 |
February | 1026.51 | 843.97 | 1009.37 | 737.13 | 272.24 | 0.00 | 0.00 |
March | 834.09 | 677.50 | 808.39 | 460.25 | 348.14 | 0.00 | 0.00 |
April | 548.42 | 609.12 | 596.79 | 189.57 | 407.22 | 0.00 | 0.00 |
May | 651.64 | 343.55 | 606.69 | 86.13 | 520.56 | 0.00 | 0.00 |
June | 832.58 | 172.42 | 587.59 | 91.59 | 496.01 | 0.00 | 0.00 |
July | 846.01 | 158.37 | 589.11 | 79.94 | 509.17 | 0.00 | 0.00 |
August | 934.22 | 187.58 | 654.34 | 208.00 | 446.34 | 0.00 | 0.00 |
September | 1043.98 | 297.88 | 783.68 | 365.67 | 418.01 | 0.00 | 0.00 |
October | 978.14 | 651.64 | 863.08 | 543.93 | 319.15 | 0.00 | 0.00 |
November | 1100.55 | 745.18 | 1013.38 | 750.54 | 262.84 | 0.00 | 0.00 |
December | 962.68 | 922.45 | 959.25 | 726.96 | 232.30 | 0.00 | 0.00 |
Annual Sum or Average | 903.38 | 531.38 | 791.82 | 418.70 | 373.12 | 0.00 | 0.00 |
Minimum of Months | 548.42 | 158.37 | 587.59 | 79.94 | 232.30 | 0.00 | 0.00 |
Maximum of Months | 1100.55 | 922.45 | 1045.22 | 806.53 | 520.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.406052E+10 | 0.166626E+10 | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.00 | 0.00 |
February | 0.343840E+10 | 0.157755E+10 | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.00 | 0.00 |
March | 0.289278E+10 | 0.138861E+10 | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.00 | 0.00 |
April | 0.168137E+10 | 0.120216E+10 | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.00 | 0.00 |
May | 0.175703E+10 | 0.715193E+09 | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.00 | 0.00 |
June | 0.192657E+10 | 0.373677E+09 | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.00 | 0.00 |
July | 0.206613E+10 | 0.344896E+09 | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.00 | 0.00 |
August | 0.262508E+10 | 0.403336E+09 | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.00 | 0.00 |
September | 0.311410E+10 | 0.613379E+09 | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.00 | 0.00 |
October | 0.337770E+10 | 0.134776E+10 | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.00 | 0.00 |
November | 0.387599E+10 | 0.151204E+10 | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.00 | 0.00 |
December | 0.364158E+10 | 0.189877E+10 | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344573E+11 | 0.130436E+11 | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168137E+10 | 0.344896E+09 | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.406052E+10 | 0.189877E+10 | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113303E+11 | 0.495344E+10 | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.00 | 0.00 |
February | 0.959162E+10 | 0.465427E+10 | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.00 | 0.00 |
March | 0.805531E+10 | 0.413224E+10 | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.00 | 0.00 |
April | 0.464412E+10 | 0.363281E+10 | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.00 | 0.00 |
May | 0.480693E+10 | 0.223007E+10 | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.00 | 0.00 |
June | 0.535320E+10 | 0.111531E+10 | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.00 | 0.00 |
July | 0.574451E+10 | 0.103596E+10 | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.00 | 0.00 |
August | 0.731866E+10 | 0.120617E+10 | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.00 | 0.00 |
September | 0.869702E+10 | 0.182602E+10 | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.00 | 0.00 |
October | 0.943275E+10 | 0.400820E+10 | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.00 | 0.00 |
November | 0.108232E+11 | 0.449662E+10 | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.00 | 0.00 |
December | 0.101575E+11 | 0.559684E+10 | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.959552E+11 | 0.388879E+11 | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.00 | 0.00 |
Minimum of Months | 0.464412E+10 | 0.103596E+10 | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113303E+11 | 0.559684E+10 | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149406E+11 | 0.662030E+10 | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.00 | 0.00 |
February | 0.126682E+11 | 0.624139E+10 | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.00 | 0.00 |
March | 0.106459E+11 | 0.558985E+10 | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.00 | 0.00 |
April | 0.613929E+10 | 0.497063E+10 | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.00 | 0.00 |
May | 0.636896E+10 | 0.299831E+10 | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.00 | 0.00 |
June | 0.713058E+10 | 0.146991E+10 | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.00 | 0.00 |
July | 0.764598E+10 | 0.136295E+10 | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.00 | 0.00 |
August | 0.971644E+10 | 0.157498E+10 | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.00 | 0.00 |
September | 0.115130E+11 | 0.239579E+10 | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.00 | 0.00 |
October | 0.124472E+11 | 0.538471E+10 | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.00 | 0.00 |
November | 0.142772E+11 | 0.602399E+10 | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.00 | 0.00 |
December | 0.133920E+11 | 0.751333E+10 | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126885E+12 | 0.521461E+11 | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.613929E+10 | 0.136295E+10 | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149406E+11 | 0.751333E+10 | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119121E+10 | 0.951523E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.111090E+10 | 0.905584E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.120180E+10 | 0.778307E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.889164E+09 | 0.671705E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.120974E+10 | 0.386159E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.162201E+10 | 0.169187E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.147238E+10 | 0.148924E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.160048E+10 | 0.176096E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.150064E+10 | 0.299596E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.129135E+10 | 0.752877E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.119234E+10 | 0.857278E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.997402E+09 | 0.109933E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152794E+11 | 0.719657E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.889164E+09 | 0.148924E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162201E+10 | 0.109933E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.437022E+09 | 0.101047E+10 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.470321E+09 | 0.943164E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.695653E+09 | 0.792794E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.645817E+09 | 0.670164E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.105555E+10 | 0.383320E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.153215E+10 | 0.173313E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.135257E+10 | 0.156002E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.130367E+10 | 0.187461E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104613E+10 | 0.315181E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.688833E+09 | 0.762205E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.466684E+09 | 0.883118E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.327565E+09 | 0.116749E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100220E+11 | 0.744468E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327565E+09 | 0.156002E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153215E+10 | 0.116749E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.621398E+09 | 0.324335E+09 | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.00 | 0.00 |
February | 0.527001E+09 | 0.292901E+09 | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.00 | 0.00 |
March | 0.441383E+09 | 0.263225E+09 | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.00 | 0.00 |
April | 0.249001E+09 | 0.243330E+09 | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.00 | 0.00 |
May | 0.248546E+09 | 0.159490E+09 | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.00 | 0.00 |
June | 0.282698E+09 | 85676629.00 | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.00 | 0.00 |
July | 0.304143E+09 | 81888900.13 | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.00 | 0.00 |
August | 0.394127E+09 | 93185784.33 | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.00 | 0.00 |
September | 0.472667E+09 | 0.132033E+09 | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.00 | 0.00 |
October | 0.517292E+09 | 0.267343E+09 | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.00 | 0.00 |
November | 0.597065E+09 | 0.294181E+09 | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.00 | 0.00 |
December | 0.560836E+09 | 0.349492E+09 | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.521616E+10 | 0.258708E+10 | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.00 | 0.00 |
Minimum of Months | 0.248546E+09 | 81888900.13 | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.00 | 0.00 |
Maximum of Months | 0.621398E+09 | 0.349492E+09 | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11722159.59 | 0.304975E+09 | 58468616.74 | 0.00 | 58468616.74 | 0.00 | 0.00 |
February | 13147913.94 | 0.283685E+09 | 66376345.10 | 0.00 | 66376345.10 | 0.00 | 0.00 |
March | 47959519.85 | 0.232989E+09 | 0.100024E+09 | 5161.40 | 0.100019E+09 | 0.00 | 0.00 |
April | 70194011.63 | 0.193767E+09 | 0.121681E+09 | 797247.66 | 0.120884E+09 | 0.00 | 0.00 |
May | 0.169482E+09 | 0.103214E+09 | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.00 | 0.00 |
June | 0.267135E+09 | 43324558.72 | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.00 | 0.00 |
July | 0.265982E+09 | 39685942.58 | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.00 | 0.00 |
August | 0.204804E+09 | 47327781.60 | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.00 | 0.00 |
September | 0.146882E+09 | 83687990.19 | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.00 | 0.00 |
October | 53068495.99 | 0.217669E+09 | 85190674.52 | 0.00 | 85190674.52 | 0.00 | 0.00 |
November | 18859144.13 | 0.262167E+09 | 62584379.74 | 0.00 | 62584379.74 | 0.00 | 0.00 |
December | 9464312.86 | 0.353555E+09 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.127870E+10 | 0.216605E+10 | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.00 | 0.00 |
Minimum of Months | 9464312.86 | 39685942.58 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Maximum of Months | 0.267135E+09 | 0.353555E+09 | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113978E+10 | 0.941666E+09 | 0.112878E+10 | 0.839113E+09 | 0.289670E+09 | 0.00 | 0.00 |
February | 0.113050E+10 | 0.902196E+09 | 0.111643E+10 | 0.804030E+09 | 0.312396E+09 | 0.00 | 0.00 |
March | 0.125590E+10 | 0.772604E+09 | 0.118736E+10 | 0.731633E+09 | 0.455724E+09 | 0.00 | 0.00 |
April | 0.997016E+09 | 0.658972E+09 | 0.996011E+09 | 0.461883E+09 | 0.534128E+09 | 0.00 | 0.00 |
May | 0.129484E+10 | 0.364580E+09 | 0.112033E+10 | 0.401726E+09 | 0.718603E+09 | 0.00 | 0.00 |
June | 0.173518E+10 | 0.153984E+09 | 0.123075E+10 | 0.555877E+09 | 0.674870E+09 | 0.00 | 0.00 |
July | 0.169947E+10 | 0.140380E+09 | 0.118820E+10 | 0.479520E+09 | 0.708683E+09 | 0.00 | 0.00 |
August | 0.180148E+10 | 0.169724E+09 | 0.127437E+10 | 0.652543E+09 | 0.621823E+09 | 0.00 | 0.00 |
September | 0.159131E+10 | 0.286220E+09 | 0.119287E+10 | 0.656772E+09 | 0.536093E+09 | 0.00 | 0.00 |
October | 0.125555E+10 | 0.744892E+09 | 0.110511E+10 | 0.694257E+09 | 0.410849E+09 | 0.00 | 0.00 |
November | 0.113636E+10 | 0.851740E+09 | 0.106960E+10 | 0.755695E+09 | 0.313902E+09 | 0.00 | 0.00 |
December | 0.989337E+09 | 0.110075E+10 | 0.101733E+10 | 0.736528E+09 | 0.280804E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.160267E+11 | 0.708771E+10 | 0.136271E+11 | 0.776958E+10 | 0.585754E+10 | 0.00 | 0.00 |
Minimum of Months | 0.989337E+09 | 0.140380E+09 | 0.996011E+09 | 0.401726E+09 | 0.280804E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180148E+10 | 0.110075E+10 | 0.127437E+10 | 0.839113E+09 | 0.718603E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.370158E+09 | 0.981787E+09 | 0.498951E+09 | 0.260481E+09 | 0.238470E+09 | 0.00 | 0.00 |
February | 0.481056E+09 | 0.930031E+09 | 0.598629E+09 | 0.326363E+09 | 0.272266E+09 | 0.00 | 0.00 |
March | 0.739393E+09 | 0.774046E+09 | 0.812750E+09 | 0.401441E+09 | 0.411310E+09 | 0.00 | 0.00 |
April | 0.753540E+09 | 0.655287E+09 | 0.831493E+09 | 0.331903E+09 | 0.499590E+09 | 0.00 | 0.00 |
May | 0.114989E+10 | 0.368171E+09 | 0.103772E+10 | 0.351759E+09 | 0.685964E+09 | 0.00 | 0.00 |
June | 0.164274E+10 | 0.166799E+09 | 0.119696E+10 | 0.534132E+09 | 0.662827E+09 | 0.00 | 0.00 |
July | 0.157568E+10 | 0.153329E+09 | 0.113227E+10 | 0.447200E+09 | 0.685075E+09 | 0.00 | 0.00 |
August | 0.149754E+10 | 0.183005E+09 | 0.109690E+10 | 0.511220E+09 | 0.585683E+09 | 0.00 | 0.00 |
September | 0.113236E+10 | 0.297617E+09 | 0.885350E+09 | 0.403080E+09 | 0.482270E+09 | 0.00 | 0.00 |
October | 0.646491E+09 | 0.744198E+09 | 0.660810E+09 | 0.304019E+09 | 0.356791E+09 | 0.00 | 0.00 |
November | 0.403163E+09 | 0.867869E+09 | 0.494509E+09 | 0.234599E+09 | 0.259910E+09 | 0.00 | 0.00 |
December | 0.302311E+09 | 0.114877E+10 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106943E+11 | 0.727090E+10 | 0.968780E+10 | 0.432118E+10 | 0.536662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.302311E+09 | 0.153329E+09 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164274E+10 | 0.114877E+10 | 0.119696E+10 | 0.534132E+09 | 0.685964E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135123E+10 | 0.119505E+10 | 0.134483E+10 | 0.100279E+10 | 0.342038E+09 | 0.00 | 0.00 |
February | 0.115998E+10 | 0.114861E+10 | 0.118493E+10 | 0.827813E+09 | 0.357113E+09 | 0.00 | 0.00 |
March | 0.108723E+10 | 0.101958E+10 | 0.108254E+10 | 0.572256E+09 | 0.510288E+09 | 0.00 | 0.00 |
April | 0.732198E+09 | 0.875821E+09 | 0.812278E+09 | 0.228713E+09 | 0.583564E+09 | 0.00 | 0.00 |
May | 0.963021E+09 | 0.503200E+09 | 0.887296E+09 | 0.111552E+09 | 0.775744E+09 | 0.00 | 0.00 |
June | 0.122165E+10 | 0.242647E+09 | 0.848098E+09 | 0.125978E+09 | 0.722120E+09 | 0.00 | 0.00 |
July | 0.126777E+10 | 0.231643E+09 | 0.870747E+09 | 0.108832E+09 | 0.761915E+09 | 0.00 | 0.00 |
August | 0.133101E+10 | 0.276578E+09 | 0.923657E+09 | 0.261592E+09 | 0.662065E+09 | 0.00 | 0.00 |
September | 0.137830E+10 | 0.436427E+09 | 0.103216E+10 | 0.440055E+09 | 0.592107E+09 | 0.00 | 0.00 |
October | 0.126373E+10 | 0.988717E+09 | 0.113905E+10 | 0.676295E+09 | 0.462759E+09 | 0.00 | 0.00 |
November | 0.133965E+10 | 0.108836E+10 | 0.126778E+10 | 0.903077E+09 | 0.364706E+09 | 0.00 | 0.00 |
December | 0.119243E+10 | 0.138859E+10 | 0.123503E+10 | 0.903852E+09 | 0.331175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142882E+11 | 0.939522E+10 | 0.126284E+11 | 0.616280E+10 | 0.646559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.732198E+09 | 0.231643E+09 | 0.812278E+09 | 0.108832E+09 | 0.331175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137830E+10 | 0.138859E+10 | 0.134483E+10 | 0.100279E+10 | 0.775744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118886E+10 | 0.945603E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.110494E+10 | 0.904366E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.119458E+10 | 0.774763E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.882347E+09 | 0.668620E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.120095E+10 | 0.383383E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.161265E+10 | 0.165315E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.146507E+10 | 0.144396E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.159134E+10 | 0.171565E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.149426E+10 | 0.293501E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.128623E+10 | 0.746865E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.118755E+10 | 0.852871E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.993983E+09 | 0.109702E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152028E+11 | 0.714827E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.882347E+09 | 0.144396E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161265E+10 | 0.109702E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438726E+09 | 0.100116E+10 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.469096E+09 | 0.939785E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.691719E+09 | 0.789195E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.640213E+09 | 0.667808E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.104568E+10 | 0.383167E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.152309E+10 | 0.172110E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.134590E+10 | 0.153809E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.129607E+10 | 0.185133E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104258E+10 | 0.310858E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.687085E+09 | 0.755783E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.466510E+09 | 0.876128E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.328599E+09 | 0.116275E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.997527E+10 | 0.739769E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.328599E+09 | 0.153809E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152309E+10 | 0.116275E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117232E+10 | 0.493123E+09 | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.00 | 0.00 |
February | 0.987666E+09 | 0.472992E+09 | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.00 | 0.00 |
March | 0.833548E+09 | 0.408672E+09 | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.00 | 0.00 |
April | 0.482558E+09 | 0.356469E+09 | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.00 | 0.00 |
May | 0.512932E+09 | 0.200315E+09 | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.00 | 0.00 |
June | 0.587138E+09 | 80277714.71 | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.00 | 0.00 |
July | 0.629231E+09 | 70998533.07 | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.00 | 0.00 |
August | 0.784463E+09 | 85835123.19 | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.00 | 0.00 |
September | 0.917484E+09 | 0.150089E+09 | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.00 | 0.00 |
October | 0.980961E+09 | 0.388924E+09 | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.00 | 0.00 |
November | 0.111901E+10 | 0.447409E+09 | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.00 | 0.00 |
December | 0.104172E+10 | 0.574526E+09 | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100490E+11 | 0.372963E+10 | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.00 | 0.00 |
Minimum of Months | 0.482558E+09 | 70998533.07 | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117232E+10 | 0.574526E+09 | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59565375.61 | 0.305734E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 66048798.42 | 0.285361E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.311660E+09 | 0.238372E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.491067E+09 | 0.200619E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.129801E+10 | 0.108341E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.216779E+10 | 0.498128E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.216447E+10 | 0.476102E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.163075E+10 | 0.563745E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.114830E+10 | 0.914502E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.359800E+09 | 0.222774E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.107710E+09 | 0.266224E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 48246363.49 | 0.351572E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.985342E+10 | 0.222424E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 48246363.49 | 0.476102E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216779E+10 | 0.351572E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 52214887.82 | 0.312355E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 60038404.92 | 0.291660E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.295272E+09 | 0.243608E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.471252E+09 | 0.205111E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.127383E+10 | 0.110483E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.214847E+10 | 0.510455E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.214514E+10 | 0.489262E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.161311E+10 | 0.578867E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.113275E+10 | 0.934111E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.345775E+09 | 0.227096E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.100364E+09 | 0.272048E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 43093722.43 | 0.359348E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968131E+10 | 0.227298E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 43093722.43 | 0.489262E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.214847E+10 | 0.359348E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157396E+10 | 0.194157E+10 | 0.162767E+10 | 0.109956E+10 | 0.528117E+09 | 0.00 | 0.00 |
February | 0.166934E+10 | 0.189752E+10 | 0.171498E+10 | 0.113035E+10 | 0.584635E+09 | 0.00 | 0.00 |
March | 0.212114E+10 | 0.165522E+10 | 0.200001E+10 | 0.113302E+10 | 0.866993E+09 | 0.00 | 0.00 |
April | 0.187714E+10 | 0.144473E+10 | 0.182741E+10 | 0.793739E+09 | 0.103367E+10 | 0.00 | 0.00 |
May | 0.271041E+10 | 0.837382E+09 | 0.215794E+10 | 0.753436E+09 | 0.140450E+10 | 0.00 | 0.00 |
June | 0.373738E+10 | 0.406320E+09 | 0.242757E+10 | 0.108994E+10 | 0.133763E+10 | 0.00 | 0.00 |
July | 0.364359E+10 | 0.387309E+09 | 0.232035E+10 | 0.926658E+09 | 0.139369E+10 | 0.00 | 0.00 |
August | 0.366123E+10 | 0.434641E+09 | 0.237114E+10 | 0.116369E+10 | 0.120745E+10 | 0.00 | 0.00 |
September | 0.302050E+10 | 0.652829E+09 | 0.207811E+10 | 0.105980E+10 | 0.101831E+10 | 0.00 | 0.00 |
October | 0.205951E+10 | 0.156772E+10 | 0.176584E+10 | 0.998232E+09 | 0.767605E+09 | 0.00 | 0.00 |
November | 0.162438E+10 | 0.176765E+10 | 0.156405E+10 | 0.990260E+09 | 0.573786E+09 | 0.00 | 0.00 |
December | 0.131205E+10 | 0.232343E+10 | 0.145873E+10 | 0.951482E+09 | 0.507244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290106E+11 | 0.153163E+11 | 0.233138E+11 | 0.120902E+11 | 0.112236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131205E+10 | 0.387309E+09 | 0.145873E+10 | 0.753436E+09 | 0.507244E+09 | 0.00 | 0.00 |
Maximum of Months | 0.373738E+10 | 0.232343E+10 | 0.242757E+10 | 0.116369E+10 | 0.140450E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.292162E+10 | 0.210921E+10 | 0.279952E+10 | 0.216021E+10 | 0.639310E+09 | 0.00 | 0.00 |
February | 0.248335E+10 | 0.204174E+10 | 0.244187E+10 | 0.178327E+10 | 0.658595E+09 | 0.00 | 0.00 |
March | 0.223403E+10 | 0.181461E+10 | 0.216521E+10 | 0.123275E+10 | 0.932460E+09 | 0.00 | 0.00 |
April | 0.142150E+10 | 0.157885E+10 | 0.154688E+10 | 0.491364E+09 | 0.105551E+10 | 0.00 | 0.00 |
May | 0.174535E+10 | 0.920156E+09 | 0.162496E+10 | 0.230699E+09 | 0.139426E+10 | 0.00 | 0.00 |
June | 0.215806E+10 | 0.446905E+09 | 0.152304E+10 | 0.237393E+09 | 0.128565E+10 | 0.00 | 0.00 |
July | 0.226596E+10 | 0.424180E+09 | 0.157788E+10 | 0.214113E+09 | 0.136377E+10 | 0.00 | 0.00 |
August | 0.250223E+10 | 0.502412E+09 | 0.175257E+10 | 0.557102E+09 | 0.119547E+10 | 0.00 | 0.00 |
September | 0.270599E+10 | 0.772093E+09 | 0.203131E+10 | 0.947814E+09 | 0.108349E+10 | 0.00 | 0.00 |
October | 0.261986E+10 | 0.174534E+10 | 0.231168E+10 | 0.145687E+10 | 0.854802E+09 | 0.00 | 0.00 |
November | 0.285264E+10 | 0.193151E+10 | 0.262668E+10 | 0.194541E+10 | 0.681277E+09 | 0.00 | 0.00 |
December | 0.257845E+10 | 0.247069E+10 | 0.256926E+10 | 0.194708E+10 | 0.622186E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284890E+11 | 0.167577E+11 | 0.249709E+11 | 0.132041E+11 | 0.117668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142150E+10 | 0.424180E+09 | 0.152304E+10 | 0.214113E+09 | 0.622186E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292162E+10 | 0.247069E+10 | 0.279952E+10 | 0.216021E+10 | 0.139426E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770446E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161683336.8 | 81.21 | 0.00 | 0.00 |
February | 0.696205E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146084730.1 | 81.21 | 0.00 | 0.00 |
March | 0.770306E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161605646.8 | 81.21 | 0.00 | 0.00 |
April | 0.746494E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156357201.1 | 81.21 | 0.00 | 0.00 |
May | 0.770424E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161446902.1 | 81.21 | 0.00 | 0.00 |
June | 0.745673E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156193308.7 | 81.21 | 0.00 | 0.00 |
July | 0.771224E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161387856.1 | 81.21 | 0.00 | 0.00 |
August | 0.770421E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161402842.0 | 81.21 | 0.00 | 0.00 |
September | 0.746615E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156214891.5 | 81.21 | 0.00 | 0.00 |
October | 0.770296E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161532668.2 | 81.21 | 0.00 | 0.00 |
November | 0.744887E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156429172.5 | 81.21 | 0.00 | 0.00 |
December | 0.771266E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161803267.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907426E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190214E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696205E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161803267.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771266E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146084730.1 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.125054E+12 | -0.123322E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173171E+10 | 81.29 | 0.00 | 0.00 |
February | 0.113996E+12 | -0.112427E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156905E+10 | 81.30 | 0.00 | 0.00 |
March | 0.124839E+12 | -0.123095E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174400E+10 | 81.29 | 0.00 | 0.00 |
April | 0.117445E+12 | -0.115760E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168521E+10 | 81.27 | 0.00 | 0.00 |
May | 0.116736E+12 | -0.114994E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174233E+10 | 81.26 | 0.00 | 0.00 |
June | 0.108538E+12 | -0.106859E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167938E+10 | 81.25 | 0.00 | 0.00 |
July | 0.108851E+12 | -0.107118E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173315E+10 | 81.25 | 0.00 | 0.00 |
August | 0.107687E+12 | -0.105958E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172877E+10 | 81.25 | 0.00 | 0.00 |
September | 0.105497E+12 | -0.103827E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167047E+10 | 81.25 | 0.00 | 0.00 |
October | 0.112452E+12 | -0.110726E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172605E+10 | 81.25 | 0.00 | 0.00 |
November | 0.113292E+12 | -0.111621E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167053E+10 | 81.26 | 0.00 | 0.00 |
December | 0.121646E+12 | -0.119919E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172689E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.137603E+13 | -0.135563E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204075E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.105497E+12 | -0.123322E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.174400E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.125054E+12 | -0.103827E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156905E+10 | 81.30 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.752025E+11 | -0.737339E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146860E+10 | 58.98 | 0.00 | 0.00 |
February | 0.687712E+11 | -0.674384E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.133276E+10 | 58.98 | 0.00 | 0.00 |
March | 0.751001E+11 | -0.736144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148565E+10 | 58.98 | 0.00 | 0.00 |
April | 0.698208E+11 | -0.683857E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143505E+10 | 58.98 | 0.00 | 0.00 |
May | 0.682054E+11 | -0.667208E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148459E+10 | 58.98 | 0.00 | 0.00 |
June | 0.622141E+11 | -0.607865E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142759E+10 | 58.98 | 0.00 | 0.00 |
July | 0.613806E+11 | -0.599086E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147199E+10 | 58.98 | 0.00 | 0.00 |
August | 0.604362E+11 | -0.589702E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146598E+10 | 58.98 | 0.00 | 0.00 |
September | 0.595605E+11 | -0.581453E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141528E+10 | 58.98 | 0.00 | 0.00 |
October | 0.644774E+11 | -0.630153E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146215E+10 | 58.98 | 0.00 | 0.00 |
November | 0.662370E+11 | -0.648219E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141511E+10 | 58.98 | 0.00 | 0.00 |
December | 0.723534E+11 | -0.708905E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146292E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.803759E+12 | -0.786432E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.173277E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.595605E+11 | -0.737339E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.148565E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.752025E+11 | -0.581453E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.133276E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.87 | 0.86 | 01-JAN-07:49 | 9411.76 | 39.82 | 274.00 | 270.83 | 3585.01 | 33.84 | 232.83 | 260.17 |
February | 245.50 | 0.86 | 0.86 | 01-FEB-10:39 | 12828.02 | 39.21 | 238.17 | 266.17 | 1087.62 | 26.11 | 174.83 | 234.00 |
March | 296.17 | 0.87 | 0.86 | 01-MAR-06:00 | 4576.51 | 25.81 | 135.17 | 332.33 | 660.30 | 22.47 | 239.83 | 275.83 |
April | 296.67 | 0.87 | 0.86 | 03-APR-09:39 | 1458.46 | 20.50 | 95.33 | 344.83 | 585.86 | 22.21 | 220.17 | 280.33 |
May | 415.33 | 0.87 | 0.86 | 01-MAY-06:30 | 1377.33 | 20.13 | 131.50 | 396.00 | 539.74 | 21.85 | 296.33 | 338.83 |
June | 421.50 | 0.87 | 0.86 | 01-JUN-06:10 | 1061.34 | 20.19 | 63.83 | 396.00 | 446.53 | 21.95 | 311.00 | 326.33 |
July | 430.33 | 0.88 | 0.86 | 01-JUL-08:30 | 1233.07 | 20.02 | 104.50 | 401.83 | 492.88 | 21.76 | 290.00 | 334.17 |
August | 394.50 | 0.87 | 0.86 | 01-AUG-06:30 | 1230.92 | 20.26 | 99.83 | 374.33 | 513.94 | 22.00 | 296.33 | 320.33 |
September | 354.00 | 0.87 | 0.86 | 01-SEP-07:10 | 1525.41 | 20.51 | 102.00 | 336.67 | 627.01 | 22.29 | 275.50 | 291.67 |
October | 262.67 | 0.87 | 0.86 | 01-OCT-06:49 | 10055.37 | 35.15 | 226.00 | 302.50 | 839.89 | 24.13 | 237.67 | 258.00 |
November | 257.67 | 0.87 | 0.86 | 01-NOV-08:39 | 10866.39 | 39.70 | 254.00 | 267.83 | 1980.07 | 30.31 | 213.50 | 240.17 |
December | 251.17 | 0.86 | 0.86 | 01-DEC-07:40 | 8723.34 | 40.23 | 250.83 | 260.17 | 5340.79 | 38.34 | 239.50 | 244.17 |
Annual Sum or Average | 3902.00 | 0.87 | 4548.30 | 26.83 | 1975.17 | 3949.50 | 1217.08 | 24.87 | 3027.50 | 3404.00 | ||
Minimum of Months | 245.50 | 0.86 | 0.86 | 1061.34 | 20.02 | 63.83 | 260.17 | 446.53 | 21.76 | 174.83 | 234.00 | |
Maximum of Months | 430.33 | 0.88 | 0.86 | 12828.02 | 40.23 | 274.00 | 401.83 | 5340.79 | 38.34 | 311.00 | 338.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.25 | 0.22 | 01-JAN-07:40 | 10066.27 | 39.88 | 274.17 | 276.83 | 4238.88 | 33.43 | 225.33 | 268.50 |
February | 245.50 | 0.24 | 0.22 | 01-FEB-10:39 | 13482.96 | 39.28 | 238.17 | 272.67 | 1741.22 | 25.34 | 128.83 | 257.00 |
March | 296.17 | 0.25 | 0.22 | 01-MAR-06:00 | 5049.29 | 25.80 | 138.00 | 340.83 | 1131.61 | 22.21 | 185.83 | 312.17 |
April | 296.67 | 0.26 | 0.22 | 03-APR-09:39 | 1771.78 | 20.81 | 110.50 | 355.17 | 898.25 | 22.36 | 221.83 | 323.67 |
May | 415.33 | 0.27 | 0.22 | 01-MAY-05:00 | 1609.16 | 20.70 | 185.00 | 406.17 | 770.74 | 22.23 | 322.50 | 378.17 |
June | 421.50 | 0.27 | 0.22 | 01-JUN-05:40 | 1270.76 | 20.76 | 144.50 | 412.00 | 655.35 | 22.33 | 332.17 | 376.00 |
July | 430.33 | 0.27 | 0.22 | 01-JUL-06:10 | 1448.41 | 20.62 | 171.67 | 417.83 | 707.48 | 22.17 | 327.50 | 379.50 |
August | 394.50 | 0.27 | 0.22 | 01-AUG-06:10 | 1515.31 | 20.61 | 124.33 | 383.50 | 797.61 | 22.18 | 295.17 | 356.67 |
September | 354.00 | 0.26 | 0.22 | 01-SEP-06:19 | 1906.43 | 20.61 | 122.17 | 347.00 | 1007.06 | 22.25 | 251.17 | 321.33 |
October | 262.67 | 0.24 | 0.22 | 01-OCT-06:40 | 10632.89 | 35.12 | 219.00 | 311.83 | 1415.64 | 23.67 | 184.00 | 289.17 |
November | 257.67 | 0.25 | 0.22 | 01-NOV-08:39 | 11539.98 | 39.76 | 254.00 | 274.83 | 2651.00 | 29.65 | 176.83 | 258.83 |
December | 251.17 | 0.24 | 0.22 | 01-DEC-07:40 | 9384.62 | 40.28 | 250.83 | 264.17 | 6000.30 | 38.20 | 231.83 | 257.33 |
Annual Sum or Average | 3902.00 | 0.26 | 4955.88 | 27.09 | 2232.33 | 4062.83 | 1623.55 | 24.84 | 2883.00 | 3778.33 | ||
Minimum of Months | 245.50 | 0.24 | 0.22 | 1270.76 | 20.61 | 110.50 | 264.17 | 655.35 | 22.17 | 128.83 | 257.00 | |
Maximum of Months | 430.33 | 0.27 | 0.22 | 13482.96 | 40.28 | 274.17 | 417.83 | 6000.30 | 38.20 | 332.17 | 379.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.70 | 0.60 | 01-JAN-10:30 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 91.50 |
February | 245.50 | 0.66 | 0.60 | 01-FEB-10:50 | 394.86 | 15.63 | 0.00 | 252.00 | 213.84 | 19.23 | 1.67 | 118.67 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 544.95 | 16.88 | 0.00 | 328.33 | 272.52 | 20.23 | 25.83 | 263.33 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 771.22 | 18.01 | 0.00 | 355.50 | 351.23 | 21.19 | 115.83 | 304.50 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-06:10 | 983.57 | 18.34 | 0.00 | 413.83 | 415.77 | 21.99 | 260.83 | 386.33 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1044.39 | 19.03 | 11.00 | 422.33 | 447.39 | 24.27 | 294.00 | 409.17 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1015.92 | 18.49 | 1.83 | 427.83 | 428.61 | 22.86 | 280.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 764.19 | 18.01 | 0.00 | 389.83 | 346.53 | 21.25 | 166.17 | 351.00 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 611.02 | 17.28 | 0.00 | 339.33 | 297.57 | 20.56 | 61.50 | 282.33 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 495.96 | 16.66 | 0.00 | 293.50 | 264.36 | 20.11 | 4.00 | 212.33 |
November | 257.67 | 0.68 | 0.60 | 01-NOV-08:00 | 385.02 | 15.09 | 0.00 | 244.00 | 209.50 | 18.74 | 0.17 | 112.17 |
December | 251.17 | 0.69 | 0.60 | 01-DEC-08:00 | 365.96 | 14.71 | 0.00 | 229.17 | 195.18 | 18.40 | 0.00 | 90.83 |
Annual Sum or Average | 3902.00 | 0.64 | 694.20 | 17.15 | 12.83 | 3921.00 | 319.97 | 20.90 | 1210.83 | 3023.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 90.83 | |
Maximum of Months | 430.33 | 0.70 | 0.60 | 1044.39 | 19.03 | 11.00 | 427.83 | 447.39 | 24.27 | 294.00 | 409.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.70 | 0.60 | 01-JAN-10:30 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 91.50 |
February | 245.50 | 0.66 | 0.60 | 01-FEB-10:50 | 394.86 | 15.63 | 0.00 | 252.00 | 213.84 | 19.23 | 1.67 | 118.67 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 544.95 | 16.88 | 0.00 | 328.33 | 272.52 | 20.23 | 25.83 | 263.33 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 771.22 | 18.01 | 0.00 | 355.50 | 351.23 | 21.19 | 115.83 | 304.50 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-06:10 | 983.57 | 18.34 | 0.00 | 413.83 | 415.77 | 21.99 | 260.83 | 386.33 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1044.39 | 19.03 | 11.00 | 422.33 | 447.39 | 24.27 | 294.00 | 409.17 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1015.92 | 18.49 | 1.83 | 427.83 | 428.61 | 22.86 | 280.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 764.19 | 18.01 | 0.00 | 389.83 | 346.53 | 21.25 | 166.17 | 351.00 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 611.02 | 17.28 | 0.00 | 339.33 | 297.57 | 20.56 | 61.50 | 282.33 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 495.96 | 16.66 | 0.00 | 293.50 | 264.36 | 20.11 | 4.00 | 212.33 |
November | 257.67 | 0.68 | 0.60 | 01-NOV-08:00 | 385.02 | 15.09 | 0.00 | 244.00 | 209.50 | 18.74 | 0.17 | 112.17 |
December | 251.17 | 0.69 | 0.60 | 01-DEC-08:00 | 365.96 | 14.71 | 0.00 | 229.17 | 195.18 | 18.40 | 0.00 | 90.83 |
Annual Sum or Average | 3902.00 | 0.64 | 694.20 | 17.15 | 12.83 | 3921.00 | 319.97 | 20.90 | 1210.83 | 3023.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 90.83 | |
Maximum of Months | 430.33 | 0.70 | 0.60 | 1044.39 | 19.03 | 11.00 | 427.83 | 447.39 | 24.27 | 294.00 | 409.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.765798E+11 | 144089.80 | 13-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754920E+11 | 141629.65 | 17-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762438E+11 | 153240.10 | 27-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.750084E+11 | 133363.71 | 17-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736060E+11 | 127021.46 | 19-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.524542E+10 | 116114.99 | 09-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.456579E+10 | 75886.88 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.468682E+10 | 56779.67 | 12-AUG-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280518E+11 | 132804.42 | 21-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683367E+11 | 137669.45 | 22-OCT-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617031E+11 | 150501.89 | 02-NOV-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103929E+12 | 151095.68 | 25-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.653449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.456579E+10 | 56779.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103929E+12 | 153240.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.853003E+09 | 2484.31 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115200E+10 | 2255.00 | 05-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110400E+10 | 2410.47 | 19-MAR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104755E+10 | 1862.38 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112371E+09 | 898.38 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28853650.60 | 889.92 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.773372E+09 | 2173.98 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790519E+09 | 2123.88 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154214E+10 | 2889.27 | 20-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154214E+10 | 2889.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2981726.16 | 213.06 | 05-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19674797.15 | 365.28 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5205672.88 | 248.13 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 675106.45 | 123.42 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8301449.36 | 319.99 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 510553.83 | 130.12 | 01-NOV-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39547559.07 | 576.96 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76896864.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39547559.07 | 576.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206912E+09 | 945.68 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399227E+09 | 838.00 | 06-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131972E+09 | 648.79 | 19-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82787353.39 | 625.51 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86213343.96 | 792.62 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149026E+09 | 799.89 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593400E+09 | 1387.66 | 22-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.593400E+09 | 1387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237540E+09 | 736.78 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383488E+09 | 642.66 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185203E+09 | 503.44 | 19-MAR-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117049E+09 | 460.58 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107006E+09 | 625.47 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164532E+09 | 589.14 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537972E+09 | 1020.86 | 21-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537972E+09 | 1020.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6698904.42 | 611.65 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6698904.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6698904.42 | 611.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209092E+09 | 5450.08 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.534041E+09 | 5087.84 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.487211E+09 | 4116.34 | 19-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360656E+09 | 3977.89 | 03-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 632039.71 | 1136.16 | 02-MAY-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.502696E+09 | 5005.41 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211492E+09 | 4347.40 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624647E+09 | 7346.29 | 21-DEC-09:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.624647E+09 | 7346.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2773029.31 | 2026.67 | 05-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193770E+09 | 5389.16 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23028427.28 | 2865.87 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80068160.85 | 4748.10 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183165E+09 | 8117.45 | 21-DEC-09:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193770E+09 | 8117.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118690E+10 | 7269.37 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273459E+10 | 7736.20 | 05-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129195E+10 | 4828.45 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.904671E+09 | 5510.92 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 194220.17 | 323.70 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104063E+10 | 7577.33 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120611E+10 | 6553.60 | 29-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386662E+10 | 10368.15 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386662E+10 | 10368.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177944E+10 | 4780.31 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223809E+10 | 4556.51 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145636E+10 | 3585.15 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.969119E+09 | 3174.74 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38748243.26 | 871.45 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.993921E+09 | 3804.60 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135613E+10 | 4159.69 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344044E+10 | 6071.06 | 22-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344044E+10 | 6071.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164885E+10 | 8472.13 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177323E+10 | 6762.83 | 12-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.709553E+09 | 5668.06 | 04-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322736E+09 | 2457.27 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16045.21 | 0.44 | 24-MAY-19:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31903.86 | 0.45 | 21-JUN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42012.19 | 0.45 | 08-JUL-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33741.78 | 0.45 | 12-AUG-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 934149.07 | 186.24 | 22-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.512380E+09 | 5283.88 | 30-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.825086E+09 | 5680.76 | 29-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310727E+10 | 8840.77 | 20-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16045.21 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310727E+10 | 8840.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241838E+10 | 7172.28 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277570E+10 | 7171.18 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213749E+10 | 7172.69 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177471E+10 | 7170.98 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183755E+09 | 6953.27 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2145279.33 | 2238.88 | 21-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1867634.43 | 2069.30 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3279737.79 | 2285.08 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64408931.69 | 6942.07 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150686E+10 | 7171.98 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205476E+10 | 7171.72 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399393E+10 | 7169.66 | 25-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1867634.43 | 2069.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.399393E+10 | 7172.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382900E+10 | 7142.99 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382922E+10 | 7142.45 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258647E+10 | 7143.40 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192955E+10 | 7141.67 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189153E+09 | 6935.04 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 371953.50 | 1388.51 | 06-JUN-08:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 479221.90 | 1379.46 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1377657.86 | 2343.13 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76771395.27 | 6929.77 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180636E+10 | 7142.71 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305768E+10 | 7142.77 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543762E+10 | 7141.62 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 371953.50 | 1379.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.543762E+10 | 7143.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150287E+11 | 40206.92 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158168E+11 | 40196.71 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747664E+10 | 39630.85 | 04-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391967E+10 | 39293.72 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138337E+09 | 23899.77 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42188.10 | 421.88 | 02-JUN-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50828.74 | 840.57 | 25-JUL-08:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1083578.94 | 4452.63 | 22-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61608620.62 | 25344.97 | 22-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454945E+10 | 40204.92 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105434E+11 | 40185.49 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216601E+11 | 40200.42 | 24-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.791959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 42188.10 | 421.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216601E+11 | 40206.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255080E+10 | 6978.97 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291014E+10 | 6977.78 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211689E+10 | 6979.46 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173206E+10 | 6977.57 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174107E+09 | 2913.64 | 02-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 139375.21 | 1393.75 | 17-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 123318.89 | 1027.66 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 235991.12 | 1489.78 | 27-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59664685.35 | 4619.05 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154626E+10 | 6978.65 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218764E+10 | 6978.42 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406771E+10 | 6976.84 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 123318.89 | 1027.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406771E+10 | 6979.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396127E+10 | 6947.24 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392278E+10 | 6946.03 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252206E+10 | 6947.77 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190726E+10 | 6946.24 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181304E+09 | 2676.69 | 03-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8417.73 | 112.24 | 10-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74812.85 | 340.99 | 22-AUG-20:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72337729.44 | 5497.22 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185312E+10 | 6946.94 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322942E+10 | 6947.00 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.548465E+10 | 6945.83 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548465E+10 | 6947.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.951021E+09 | 2129.24 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101971E+10 | 2128.85 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807350E+09 | 2129.34 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.678753E+09 | 2129.49 | 30-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105937E+09 | 2092.08 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 928688.64 | 524.31 | 24-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 740536.45 | 497.69 | 21-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1551230.03 | 517.51 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39049433.28 | 2106.83 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614316E+09 | 2129.00 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.805085E+09 | 2129.15 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143220E+10 | 2128.59 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 740536.45 | 497.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143220E+10 | 2129.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141578E+10 | 2117.38 | 11-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135790E+10 | 2116.98 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.953139E+09 | 2117.47 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725487E+09 | 2117.63 | 30-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99310309.78 | 2083.39 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 166869.90 | 476.90 | 16-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 193063.64 | 436.65 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 729358.23 | 508.33 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43135460.40 | 2099.54 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730189E+09 | 2117.20 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114579E+10 | 2117.31 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188341E+10 | 2117.05 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 166869.90 | 436.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188341E+10 | 2117.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196503E+10 | 10003.30 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283070E+10 | 10004.95 | 04-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254030E+10 | 10006.59 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229136E+10 | 10004.69 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282503E+09 | 8296.73 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4568944.81 | 2344.35 | 21-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2396957.44 | 2100.51 | 13-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1616240.35 | 2175.99 | 02-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79270622.34 | 9190.32 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182753E+10 | 10006.34 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184823E+10 | 10005.93 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371283E+10 | 10002.00 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1616240.35 | 2100.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371283E+10 | 10006.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.508402E+10 | 0.508402E+10 | 123391.13 | 20-JAN-13:00 | 123391.13 | 0.00 |
February | 0.00 | 0.00 | 0.284855E+10 | 0.284855E+10 | 112295.13 | 18-FEB-13:00 | 112295.13 | 0.00 |
March | 0.00 | 0.00 | 0.178962E+11 | 0.178962E+11 | 152508.15 | 14-MAR-13:00 | 152508.15 | 0.00 |
April | 0.00 | 0.00 | 0.188813E+11 | 0.188813E+11 | 107926.08 | 20-APR-13:00 | 107926.08 | 0.01 |
May | 0.00 | 0.00 | 0.885542E+11 | 0.885542E+11 | 202653.06 | 31-MAY-18:07 | 202653.06 | 0.08 |
June | 0.00 | 0.00 | 0.291935E+12 | 0.287189E+12 | 279965.75 | 26-JUN-18:20 | 279965.75 | 0.42 |
July | 0.00 | 0.00 | 0.335840E+12 | 0.316635E+12 | 283317.20 | 30-JUL-10:40 | 156994.38 | 0.49 |
August | 0.00 | 0.00 | 0.299728E+12 | 0.292387E+12 | 268634.84 | 16-AUG-18:05 | 268634.84 | 0.55 |
September | 0.00 | 0.00 | 0.206446E+12 | 0.206446E+12 | 242015.02 | 12-SEP-18:30 | 242015.02 | 0.14 |
October | 0.00 | 0.00 | 0.333491E+11 | 0.333491E+11 | 180057.39 | 11-OCT-15:10 | 180057.39 | 0.00 |
November | 0.00 | 0.00 | 0.104961E+11 | 0.104961E+11 | 135408.69 | 06-NOV-13:00 | 135408.69 | 0.00 |
December | 0.00 | 0.00 | 0.696639E+10 | 0.696639E+10 | 114594.23 | 02-DEC-13:00 | 114594.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131802E+13 | 0.128673E+13 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.284855E+10 | 0.284855E+10 | 107926.08 | 107926.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.335840E+12 | 0.316635E+12 | 283317.20 | 279965.75 | 0.55 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192283E+09 | 0.192283E+09 | 11112.29 | 20-JAN-14:00 | 11112.29 | 0.00 |
February | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.67 | 18-FEB-14:00 | 9344.67 | 0.00 |
March | 0.00 | 0.00 | 0.893958E+09 | 0.893958E+09 | 13429.57 | 13-MAR-15:02 | 13429.57 | 0.00 |
April | 0.00 | 0.00 | 0.105767E+10 | 0.105767E+10 | 12344.03 | 20-APR-13:00 | 12344.03 | 0.00 |
May | 0.00 | 0.00 | 0.512456E+10 | 0.512456E+10 | 15637.39 | 17-MAY-13:00 | 15637.39 | 0.06 |
June | 0.00 | 0.00 | 0.173122E+11 | 0.168055E+11 | 21623.04 | 18-JUN-12:05 | 15867.09 | 0.35 |
July | 0.00 | 0.00 | 0.210669E+11 | 0.191640E+11 | 25905.81 | 30-JUL-15:37 | 13391.04 | 0.41 |
August | 0.00 | 0.00 | 0.182535E+11 | 0.171964E+11 | 21036.31 | 05-AUG-15:10 | 9826.56 | 0.48 |
September | 0.00 | 0.00 | 0.117385E+11 | 0.117385E+11 | 16823.41 | 10-SEP-13:00 | 16823.41 | 0.13 |
October | 0.00 | 0.00 | 0.173199E+10 | 0.173199E+10 | 14653.49 | 11-OCT-15:02 | 14653.49 | 0.00 |
November | 0.00 | 0.00 | 0.497100E+09 | 0.497100E+09 | 12313.09 | 06-NOV-13:50 | 12313.09 | 0.00 |
December | 0.00 | 0.00 | 0.275045E+09 | 0.275045E+09 | 11644.27 | 01-DEC-14:00 | 11644.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.782673E+11 | 0.748005E+11 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.67 | 9344.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210669E+11 | 0.191640E+11 | 25905.81 | 16823.41 | 0.48 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122329E+10 | 0.115912E+10 | 11662.07 | 12-JAN-16:02 | 11662.07 | 0.05 |
February | 0.00 | 0.00 | 0.131291E+10 | 0.127747E+10 | 11664.13 | 23-FEB-16:02 | 11664.13 | 0.03 |
March | 0.00 | 0.00 | 0.262611E+10 | 0.261466E+10 | 11661.24 | 26-MAR-15:02 | 11661.24 | 0.01 |
April | 0.00 | 0.00 | 0.174293E+10 | 0.163655E+10 | 11662.53 | 27-APR-15:02 | 11662.53 | 0.07 |
May | 0.00 | 0.00 | 0.435784E+10 | 0.360414E+10 | 11914.07 | 22-MAY-08:62 | 10541.24 | 0.43 |
June | 0.00 | 0.00 | 0.981808E+10 | 0.814414E+10 | 13179.46 | 18-JUN-08:62 | 10573.92 | 0.73 |
July | 0.00 | 0.00 | 0.962442E+10 | 0.753178E+10 | 13468.98 | 28-JUL-18:02 | 10381.44 | 0.83 |
August | 0.00 | 0.00 | 0.965773E+10 | 0.768084E+10 | 13174.03 | 05-AUG-08:62 | 10578.24 | 0.76 |
September | 0.00 | 0.00 | 0.769549E+10 | 0.687345E+10 | 11663.99 | 07-SEP-18:02 | 11663.99 | 0.41 |
October | 0.00 | 0.00 | 0.363137E+10 | 0.345909E+10 | 11663.41 | 01-OCT-18:01 | 11663.41 | 0.11 |
November | 0.00 | 0.00 | 0.170367E+10 | 0.155372E+10 | 11663.73 | 23-NOV-16:01 | 11663.73 | 0.11 |
December | 0.00 | 0.00 | 0.778990E+09 | 0.778990E+09 | 11659.09 | 29-DEC-16:01 | 11659.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.541728E+11 | 0.463140E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.778990E+09 | 0.778990E+09 | 11659.09 | 10381.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.981808E+10 | 0.814414E+10 | 13468.98 | 11664.13 | 0.83 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.191684E+09 | 0.184704E+09 | 11391.63 | 19-JAN-16:02 | 11391.63 | 0.01 |
February | 0.00 | 0.00 | 0.294485E+09 | 0.293780E+09 | 11395.64 | 23-FEB-16:02 | 11395.64 | 0.00 |
March | 0.00 | 0.00 | 0.101249E+10 | 0.100869E+10 | 12798.25 | 15-MAR-18:31 | 12798.25 | 0.00 |
April | 0.00 | 0.00 | 0.841518E+09 | 0.753681E+09 | 14290.01 | 08-APR-17:42 | 14290.01 | 0.07 |
May | 0.00 | 0.00 | 0.294323E+10 | 0.229107E+10 | 12838.33 | 27-MAY-16:11 | 12838.33 | 0.36 |
June | 0.00 | 0.00 | 0.833572E+10 | 0.706286E+10 | 14001.98 | 20-JUN-21:51 | 10489.92 | 0.57 |
July | 0.00 | 0.00 | 0.783636E+10 | 0.628063E+10 | 14319.73 | 31-JUL-21:51 | 10268.83 | 0.64 |
August | 0.00 | 0.00 | 0.724387E+10 | 0.574078E+10 | 13768.31 | 05-AUG-08:51 | 10707.67 | 0.59 |
September | 0.00 | 0.00 | 0.474744E+10 | 0.408461E+10 | 12225.36 | 15-SEP-19:51 | 12225.36 | 0.33 |
October | 0.00 | 0.00 | 0.135763E+10 | 0.127186E+10 | 12550.49 | 14-OCT-16:11 | 12550.49 | 0.06 |
November | 0.00 | 0.00 | 0.332695E+09 | 0.312620E+09 | 11393.09 | 15-NOV-16:02 | 11393.09 | 0.02 |
December | 0.00 | 0.00 | 87545814.53 | 87545814.53 | 11388.16 | 03-DEC-16:01 | 11388.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.352247E+11 | 0.293728E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 87545814.53 | 87545814.53 | 11388.16 | 10268.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.833572E+10 | 0.706286E+10 | 14319.73 | 14290.01 | 0.64 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.302543E+11 | 0.302543E+11 | 69602.44 | 20-JAN-12:40 | 69602.44 | 0.00 |
February | 0.00 | 0.00 | 0.208767E+11 | 0.208767E+11 | 65069.32 | 18-FEB-13:00 | 65069.32 | 0.00 |
March | 0.00 | 0.00 | 0.219621E+11 | 0.219621E+11 | 59312.23 | 14-MAR-12:40 | 59312.23 | 0.00 |
April | 0.00 | 0.00 | 0.714566E+10 | 0.705764E+10 | 34062.19 | 12-APR-13:30 | 34062.19 | 0.01 |
May | 0.00 | 0.00 | 0.199405E+11 | 0.167277E+11 | 27335.57 | 16-MAY-13:20 | 27335.57 | 0.21 |
June | 0.00 | 0.00 | 0.408399E+11 | 0.318108E+11 | 34255.90 | 14-JUN-13:30 | 34255.90 | 0.54 |
July | 0.00 | 0.00 | 0.448703E+11 | 0.347375E+11 | 37603.20 | 23-JUL-12:40 | 33788.03 | 0.56 |
August | 0.00 | 0.00 | 0.510341E+11 | 0.390443E+11 | 48569.39 | 31-AUG-12:50 | 44011.88 | 0.72 |
September | 0.00 | 0.00 | 0.510439E+11 | 0.468701E+11 | 61788.24 | 28-SEP-13:00 | 61788.24 | 0.29 |
October | 0.00 | 0.00 | 0.361213E+11 | 0.361199E+11 | 63828.99 | 10-OCT-12:30 | 63828.99 | 0.00 |
November | 0.00 | 0.00 | 0.287344E+11 | 0.287344E+11 | 68973.44 | 07-NOV-12:10 | 68973.44 | 0.00 |
December | 0.00 | 0.00 | 0.179622E+11 | 0.179622E+11 | 61048.37 | 17-DEC-13:00 | 61048.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.370785E+12 | 0.332158E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.714566E+10 | 0.705764E+10 | 27335.57 | 27335.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.510439E+11 | 0.468701E+11 | 69602.44 | 69602.44 | 0.72 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.124434E+10 | 0.112255E+10 | 59065.62 | 21-JAN-09:02 | 59065.62 | 0.03 |
February | 0.00 | 0.00 | 0.119511E+10 | 0.109947E+10 | 58988.44 | 19-FEB-09:01 | 58988.44 | 0.02 |
March | 0.00 | 0.00 | 0.602611E+10 | 0.584923E+10 | 62535.16 | 14-MAR-20:51 | 62535.16 | 0.03 |
April | 0.00 | 0.00 | 0.853365E+10 | 0.721134E+10 | 63328.49 | 20-APR-20:31 | 63328.49 | 0.15 |
May | 0.00 | 0.00 | 0.279783E+11 | 0.242197E+11 | 64469.44 | 07-MAY-19:31 | 64469.44 | 0.33 |
June | 0.00 | 0.00 | 0.522518E+11 | 0.462486E+11 | 75409.23 | 20-JUN-21:51 | 57788.46 | 0.50 |
July | 0.00 | 0.00 | 0.537838E+11 | 0.466163E+11 | 77167.48 | 31-JUL-21:51 | 56819.87 | 0.57 |
August | 0.00 | 0.00 | 0.465018E+11 | 0.389453E+11 | 73505.78 | 29-AUG-21:51 | 56699.59 | 0.52 |
September | 0.00 | 0.00 | 0.317979E+11 | 0.290171E+11 | 64528.27 | 09-SEP-21:51 | 64528.27 | 0.29 |
October | 0.00 | 0.00 | 0.930298E+10 | 0.841795E+10 | 62367.46 | 01-OCT-18:01 | 62367.46 | 0.11 |
November | 0.00 | 0.00 | 0.256896E+10 | 0.221590E+10 | 59642.95 | 09-NOV-19:02 | 59642.95 | 0.06 |
December | 0.00 | 0.00 | 0.888803E+09 | 0.888803E+09 | 58151.84 | 03-DEC-09:02 | 58151.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242074E+12 | 0.211852E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.888803E+09 | 0.888803E+09 | 58151.84 | 56699.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.537838E+11 | 0.466163E+11 | 77167.48 | 64528.27 | 0.57 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.120231E+10 | 0.114400E+10 | 10225.34 | 01-JAN-09:01 | 10225.34 | 0.05 |
February | 0.00 | 0.00 | 0.147318E+10 | 0.142817E+10 | 10225.11 | 18-FEB-09:02 | 10225.11 | 0.05 |
March | 0.00 | 0.00 | 0.278752E+10 | 0.277526E+10 | 10225.41 | 01-MAR-09:01 | 10225.41 | 0.01 |
April | 0.00 | 0.00 | 0.207621E+10 | 0.194561E+10 | 11855.46 | 19-APR-08:51 | 11855.46 | 0.11 |
May | 0.00 | 0.00 | 0.476430E+10 | 0.401697E+10 | 10237.88 | 22-MAY-08:62 | 10237.88 | 0.46 |
June | 0.00 | 0.00 | 0.104328E+11 | 0.889543E+10 | 11245.07 | 17-JUN-08:62 | 9389.63 | 0.76 |
July | 0.00 | 0.00 | 0.107577E+11 | 0.892230E+10 | 11892.55 | 28-JUL-18:02 | 9044.41 | 0.86 |
August | 0.00 | 0.00 | 0.107081E+11 | 0.892939E+10 | 10632.76 | 21-AUG-18:02 | 9874.96 | 0.79 |
September | 0.00 | 0.00 | 0.811563E+10 | 0.741380E+10 | 10225.64 | 16-SEP-15:02 | 10225.64 | 0.44 |
October | 0.00 | 0.00 | 0.348800E+10 | 0.332699E+10 | 10225.49 | 04-OCT-15:01 | 10225.49 | 0.13 |
November | 0.00 | 0.00 | 0.165390E+10 | 0.151987E+10 | 10224.12 | 05-NOV-08:62 | 10224.12 | 0.12 |
December | 0.00 | 0.00 | 0.797561E+09 | 0.797561E+09 | 10224.70 | 16-DEC-09:02 | 10224.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.582572E+11 | 0.511153E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.797561E+09 | 0.797561E+09 | 10224.12 | 9044.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107577E+11 | 0.892939E+10 | 11892.55 | 11855.46 | 0.86 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206441E+09 | 0.187575E+09 | 9989.58 | 20-JAN-09:02 | 9989.58 | 0.01 |
February | 0.00 | 0.00 | 0.414601E+09 | 0.387171E+09 | 9991.84 | 18-FEB-09:02 | 9991.84 | 0.02 |
March | 0.00 | 0.00 | 0.124737E+10 | 0.123751E+10 | 10107.03 | 14-MAR-20:51 | 10107.03 | 0.01 |
April | 0.00 | 0.00 | 0.125908E+10 | 0.114804E+10 | 11492.47 | 19-APR-08:51 | 11492.47 | 0.09 |
May | 0.00 | 0.00 | 0.348148E+10 | 0.283475E+10 | 11585.74 | 10-MAY-08:51 | 11585.74 | 0.40 |
June | 0.00 | 0.00 | 0.859821E+10 | 0.741971E+10 | 13571.63 | 21-JUN-08:32 | 11642.08 | 0.61 |
July | 0.00 | 0.00 | 0.865461E+10 | 0.732017E+10 | 13707.89 | 01-JUL-07:32 | 13707.89 | 0.68 |
August | 0.00 | 0.00 | 0.800273E+10 | 0.657889E+10 | 13986.88 | 04-AUG-08:32 | 11850.16 | 0.62 |
September | 0.00 | 0.00 | 0.518991E+10 | 0.455449E+10 | 11584.79 | 07-SEP-08:51 | 11584.79 | 0.37 |
October | 0.00 | 0.00 | 0.136664E+10 | 0.125940E+10 | 11354.89 | 11-OCT-08:51 | 11354.89 | 0.09 |
November | 0.00 | 0.00 | 0.379684E+09 | 0.328196E+09 | 9990.77 | 05-NOV-08:62 | 9990.77 | 0.04 |
December | 0.00 | 0.00 | 0.120612E+09 | 0.120612E+09 | 9955.05 | 02-DEC-09:02 | 9955.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.389214E+11 | 0.333765E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.120612E+09 | 0.120612E+09 | 9955.05 | 9955.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.865461E+10 | 0.741971E+10 | 13986.88 | 13707.89 | 0.68 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.286879E+09 | 0.273686E+09 | 3094.67 | 12-JAN-16:02 | 3094.67 | 0.04 |
February | 0.00 | 0.00 | 0.318021E+09 | 0.312815E+09 | 3095.21 | 23-FEB-16:02 | 3095.21 | 0.02 |
March | 0.00 | 0.00 | 0.650394E+09 | 0.647930E+09 | 3094.55 | 26-MAR-15:02 | 3094.55 | 0.01 |
April | 0.00 | 0.00 | 0.453519E+09 | 0.429427E+09 | 3137.38 | 18-APR-19:11 | 3137.38 | 0.07 |
May | 0.00 | 0.00 | 0.106928E+10 | 0.902200E+09 | 3292.85 | 22-MAY-08:62 | 2598.68 | 0.36 |
June | 0.00 | 0.00 | 0.248757E+10 | 0.207141E+10 | 3585.11 | 18-JUN-08:62 | 2747.32 | 0.73 |
July | 0.00 | 0.00 | 0.238970E+10 | 0.187199E+10 | 3651.60 | 30-JUL-08:62 | 2702.96 | 0.82 |
August | 0.00 | 0.00 | 0.240262E+10 | 0.192025E+10 | 3614.02 | 05-AUG-08:62 | 2728.12 | 0.75 |
September | 0.00 | 0.00 | 0.183211E+10 | 0.162960E+10 | 3123.10 | 10-SEP-15:37 | 3123.10 | 0.41 |
October | 0.00 | 0.00 | 0.848871E+09 | 0.813509E+09 | 3094.99 | 01-OCT-18:01 | 3094.99 | 0.08 |
November | 0.00 | 0.00 | 0.404608E+09 | 0.374584E+09 | 3095.16 | 23-NOV-16:01 | 3095.16 | 0.08 |
December | 0.00 | 0.00 | 0.180797E+09 | 0.180788E+09 | 3093.81 | 16-DEC-16:02 | 3093.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133244E+11 | 0.114282E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.180797E+09 | 0.180788E+09 | 3093.81 | 2598.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.248757E+10 | 0.207141E+10 | 3651.60 | 3137.38 | 0.82 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 39710770.99 | 38205125.18 | 3017.76 | 19-JAN-16:02 | 3017.76 | 0.00 |
February | 0.00 | 0.00 | 67575443.71 | 67422041.46 | 3018.75 | 23-FEB-16:02 | 3018.75 | 0.00 |
March | 0.00 | 0.00 | 0.239307E+09 | 0.238572E+09 | 3466.16 | 08-MAR-17:11 | 3466.16 | 0.00 |
April | 0.00 | 0.00 | 0.216063E+09 | 0.197399E+09 | 3861.15 | 08-APR-17:42 | 3861.15 | 0.06 |
May | 0.00 | 0.00 | 0.712446E+09 | 0.565849E+09 | 3456.39 | 27-MAY-16:11 | 3456.39 | 0.32 |
June | 0.00 | 0.00 | 0.216837E+10 | 0.184040E+10 | 3832.83 | 22-JUN-21:51 | 3017.22 | 0.57 |
July | 0.00 | 0.00 | 0.200291E+10 | 0.160347E+10 | 3879.99 | 31-JUL-21:51 | 2710.62 | 0.64 |
August | 0.00 | 0.00 | 0.184728E+10 | 0.146741E+10 | 3694.28 | 05-AUG-21:51 | 3302.77 | 0.59 |
September | 0.00 | 0.00 | 0.112541E+10 | 0.961080E+09 | 3302.94 | 15-SEP-19:51 | 3302.94 | 0.33 |
October | 0.00 | 0.00 | 0.287604E+09 | 0.272916E+09 | 3395.80 | 08-OCT-18:11 | 3395.80 | 0.04 |
November | 0.00 | 0.00 | 73536650.70 | 69945533.71 | 3018.05 | 15-NOV-16:02 | 3018.05 | 0.01 |
December | 0.00 | 0.00 | 20097199.49 | 20097199.49 | 3016.74 | 03-DEC-16:01 | 3016.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.880031E+10 | 0.734276E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 20097199.49 | 20097199.49 | 3016.74 | 2710.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216837E+10 | 0.184040E+10 | 3879.99 | 3861.15 | 0.64 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.713691E+10 | 0.696659E+10 | 14487.18 | 19-JAN-13:53 | 14487.18 | 0.14 |
February | 0.00 | 0.00 | 0.579534E+10 | 0.566097E+10 | 13725.77 | 18-FEB-09:02 | 13725.77 | 0.10 |
March | 0.00 | 0.00 | 0.601129E+10 | 0.597435E+10 | 13725.26 | 26-MAR-15:02 | 13725.26 | 0.02 |
April | 0.00 | 0.00 | 0.305968E+10 | 0.286924E+10 | 13868.25 | 18-APR-19:11 | 13868.25 | 0.11 |
May | 0.00 | 0.00 | 0.539147E+10 | 0.446462E+10 | 14277.37 | 22-MAY-15:02 | 13233.53 | 0.44 |
June | 0.00 | 0.00 | 0.108625E+11 | 0.874346E+10 | 15601.51 | 18-JUN-08:62 | 12301.33 | 0.77 |
July | 0.00 | 0.00 | 0.117967E+11 | 0.917946E+10 | 16221.58 | 31-JUL-18:02 | 11962.04 | 0.85 |
August | 0.00 | 0.00 | 0.129806E+11 | 0.105019E+11 | 15410.87 | 04-AUG-08:62 | 12498.76 | 0.78 |
September | 0.00 | 0.00 | 0.120189E+11 | 0.110087E+11 | 13724.95 | 18-SEP-18:02 | 13724.95 | 0.48 |
October | 0.00 | 0.00 | 0.844401E+10 | 0.819332E+10 | 14340.90 | 08-OCT-12:35 | 14340.90 | 0.17 |
November | 0.00 | 0.00 | 0.743434E+10 | 0.705291E+10 | 14860.75 | 16-NOV-13:33 | 14860.75 | 0.28 |
December | 0.00 | 0.00 | 0.521155E+10 | 0.521155E+10 | 13724.76 | 30-DEC-16:02 | 13724.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.961431E+11 | 0.858271E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.305968E+10 | 0.286924E+10 | 13724.76 | 11962.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129806E+11 | 0.110087E+11 | 16221.58 | 14860.75 | 0.85 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 42499.22 | 217953.64 | 05-JAN-19:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 48936.08 | 201898.32 | 07-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 38044.27 | 202871.37 | 21-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 35880.35 | 139895.80 | 30-APR-08:07 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27838.55 | 133719.27 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2012.35 | 115452.88 | 09-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1699.40 | 75761.49 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1737.63 | 56796.47 | 12-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10948.03 | 133271.63 | 21-SEP-14:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32180.76 | 166441.83 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 34906.85 | 182384.24 | 24-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 61330.79 | 249043.17 | 21-DEC-09:08 |
Annual Sum or Average | 0.00 | 28076.40 | ||||
Minimum of Months | 0.00 | 0.00 | 1699.40 | 56796.47 | ||
Maximum of Months | 0.00 | 0.00 | 61330.79 | 249043.17 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18846.00 | 224362.67 | 20-JAN-13:15 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15482.12 | 206861.01 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24213.65 | 334971.18 | 13-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18791.01 | 261065.38 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 63454.39 | 350771.24 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 177880.22 | 435985.06 | 27-JUN-18:53 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 192259.94 | 424879.84 | 17-JUL-18:32 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 177226.32 | 428988.86 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 134083.29 | 406293.37 | 13-SEP-15:06 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38839.12 | 372882.04 | 11-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22309.66 | 261938.53 | 05-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 13377.87 | 196385.08 | 02-DEC-13:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 75068.93 | 0.00 | ||||
Minimum of Months | 13377.87 | 196385.08 | 0.00 | 0.00 | ||
Maximum of Months | 192259.94 | 435985.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 29092.59 | 59645.53 | 31-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29438.54 | 59811.96 | 13-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29047.29 | 59557.31 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27948.82 | 57710.32 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26479.40 | 55121.98 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25023.56 | 51970.69 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23941.75 | 48992.54 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23592.59 | 47680.30 | 31-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24006.89 | 49268.61 | 29-SEP-06:47 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25099.23 | 52111.35 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26576.97 | 55306.34 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28033.12 | 57944.83 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 26506.39 | ||||
Minimum of Months | 0.00 | 0.00 | 23592.59 | 47680.30 | ||
Maximum of Months | 0.00 | 0.00 | 29438.54 | 59811.96 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.85 | 1299.30 | 01-JAN-16:35 | 1.08 |
February | 0.244774E+10 | 0.86 | 1299.30 | 02-FEB-09:06 | 1.08 |
March | 0.271000E+10 | 0.86 | 1299.30 | 07-MAR-09:02 | 1.08 |
April | 0.262258E+10 | 0.85 | 1299.30 | 07-APR-19:16 | 1.08 |
May | 0.271000E+10 | 0.85 | 1299.30 | 05-MAY-21:27 | 1.08 |
June | 0.262258E+10 | 0.85 | 1299.30 | 06-JUN-22:30 | 1.08 |
July | 0.271000E+10 | 0.85 | 1299.30 | 06-JUL-09:30 | 1.08 |
August | 0.271000E+10 | 0.85 | 1299.30 | 02-AUG-20:20 | 1.07 |
September | 0.262258E+10 | 0.85 | 1299.30 | 04-SEP-18:50 | 1.07 |
October | 0.271000E+10 | 0.85 | 1299.30 | 02-OCT-06:40 | 1.07 |
November | 0.262258E+10 | 0.85 | 1299.30 | 28-NOV-16:08 | 1.08 |
December | 0.271000E+10 | 0.86 | 1299.30 | 20-DEC-17:20 | 1.08 |
Annual Sum or Average | 0.319080E+11 | 0.85 | |||
Minimum of Months | 0.244774E+10 | 0.85 | 1299.30 | 1.07 | |
Maximum of Months | 0.271000E+10 | 0.86 | 1299.30 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333735E+11 | 0.88 | 27776.23 | 20-JAN-22:10 | 1.40 |
February | 0.295882E+11 | 0.87 | 25392.76 | 17-FEB-22:10 | 1.32 |
March | 0.340077E+11 | 0.89 | 29862.95 | 15-MAR-21:10 | 1.46 |
April | 0.324503E+11 | 0.88 | 28111.54 | 20-APR-21:10 | 1.40 |
May | 0.367212E+11 | 0.92 | 30888.19 | 17-MAY-21:10 | 1.49 |
June | 0.413885E+11 | 1.00 | 46633.71 | 27-JUN-19:05 | 1.91 |
July | 0.430149E+11 | 1.00 | 50026.72 | 17-JUL-18:33 | 2.00 |
August | 0.440940E+11 | 1.01 | 45808.28 | 10-AUG-19:04 | 1.89 |
September | 0.422247E+11 | 1.01 | 42866.55 | 12-SEP-21:10 | 1.81 |
October | 0.379826E+11 | 0.94 | 35821.50 | 10-OCT-21:10 | 1.64 |
November | 0.346437E+11 | 0.91 | 30527.66 | 07-NOV-22:10 | 1.48 |
December | 0.335295E+11 | 0.89 | 27527.01 | 04-DEC-22:10 | 1.39 |
Annual Sum or Average | 0.443019E+12 | 0.94 | |||
Minimum of Months | 0.295882E+11 | 0.87 | 25392.76 | 1.32 | |
Maximum of Months | 0.440940E+11 | 1.01 | 50026.72 | 2.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:10 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:10 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:10 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:10 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:05 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:10 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:10 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:10 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:05 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:10 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.33 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.33 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.33 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.33 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.33 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:03 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.33 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.33 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:10 | 0.33 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358064E+09 | 0.58 | 1033.13 | 01-JAN-16:02 | 0.71 |
February | 0.374545E+09 | 0.59 | 1033.13 | 01-FEB-09:02 | 0.71 |
March | 0.443505E+09 | 0.60 | 1033.13 | 01-MAR-19:02 | 0.71 |
April | 0.346183E+09 | 0.57 | 1033.13 | 01-APR-15:02 | 0.71 |
May | 0.439059E+09 | 0.62 | 1033.13 | 01-MAY-15:02 | 0.71 |
June | 0.877890E+09 | 0.67 | 1033.13 | 01-JUN-08:62 | 0.70 |
July | 0.837805E+09 | 0.68 | 1033.13 | 01-JUL-08:61 | 0.71 |
August | 0.831290E+09 | 0.67 | 1033.13 | 01-AUG-08:62 | 0.71 |
September | 0.691790E+09 | 0.66 | 1033.13 | 01-SEP-08:62 | 0.70 |
October | 0.484503E+09 | 0.63 | 1033.13 | 01-OCT-08:62 | 0.71 |
November | 0.359587E+09 | 0.59 | 1033.13 | 01-NOV-08:62 | 0.71 |
December | 0.483785E+09 | 0.58 | 1033.13 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.652801E+10 | 0.62 | |||
Minimum of Months | 0.346183E+09 | 0.57 | 1033.13 | 0.70 | |
Maximum of Months | 0.877890E+09 | 0.68 | 1033.13 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.382778E+09 | 0.53 | 1009.30 | 01-JAN-09:01 | 0.71 |
February | 0.369328E+09 | 0.56 | 1009.30 | 01-FEB-09:02 | 0.71 |
March | 0.338399E+09 | 0.53 | 1009.30 | 01-MAR-09:01 | 0.71 |
April | 0.276799E+09 | 0.51 | 1009.30 | 01-APR-15:02 | 0.71 |
May | 0.305569E+09 | 0.50 | 1009.30 | 01-MAY-15:02 | 0.71 |
June | 0.752242E+09 | 0.53 | 1009.30 | 01-JUN-08:51 | 0.70 |
July | 0.699165E+09 | 0.52 | 1009.30 | 01-JUL-08:61 | 0.71 |
August | 0.631312E+09 | 0.52 | 1009.30 | 01-AUG-08:52 | 0.71 |
September | 0.442319E+09 | 0.49 | 1009.30 | 01-SEP-08:51 | 0.70 |
October | 0.310215E+09 | 0.53 | 1009.30 | 01-OCT-08:62 | 0.71 |
November | 0.327061E+09 | 0.54 | 1009.30 | 01-NOV-08:62 | 0.71 |
December | 0.554306E+09 | 0.57 | 1009.30 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.538949E+10 | 0.53 | |||
Minimum of Months | 0.276799E+09 | 0.49 | 1009.30 | 0.70 | |
Maximum of Months | 0.752242E+09 | 0.57 | 1009.30 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185256E+10 | 0.35 | 5049.92 | 20-JAN-12:40 | 0.71 |
February | 0.126810E+10 | 0.28 | 3783.71 | 18-FEB-13:00 | 0.71 |
March | 0.132251E+10 | 0.27 | 3540.10 | 14-MAR-12:40 | 0.71 |
April | 0.469789E+09 | 0.17 | 1691.77 | 12-APR-13:30 | 0.71 |
May | 0.136316E+10 | 0.47 | 1580.37 | 16-MAY-12:00 | 0.71 |
June | 0.243597E+10 | 0.69 | 1846.05 | 26-JUN-12:50 | 0.71 |
July | 0.262762E+10 | 0.70 | 1877.11 | 15-JUL-13:30 | 0.71 |
August | 0.299903E+10 | 0.70 | 3616.56 | 16-AUG-13:20 | 0.71 |
September | 0.308345E+10 | 0.67 | 5432.15 | 12-SEP-13:30 | 0.71 |
October | 0.215517E+10 | 0.40 | 3729.54 | 10-OCT-12:30 | 0.71 |
November | 0.175516E+10 | 0.35 | 5018.38 | 07-NOV-12:10 | 0.71 |
December | 0.109833E+10 | 0.22 | 3613.87 | 17-DEC-13:00 | 0.71 |
Annual Sum or Average | 0.224308E+11 | 0.44 | |||
Minimum of Months | 0.469789E+09 | 0.17 | 1580.37 | 0.71 | |
Maximum of Months | 0.308345E+10 | 0.70 | 5432.15 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155648E+10 | 0.50 | 5340.50 | 01-JAN-16:02 | 0.71 |
February | 0.155718E+10 | 0.50 | 5340.50 | 01-FEB-09:02 | 0.71 |
March | 0.133790E+10 | 0.48 | 5340.50 | 01-MAR-16:02 | 0.71 |
April | 0.124509E+10 | 0.47 | 5340.50 | 01-APR-08:62 | 0.71 |
May | 0.250135E+10 | 0.44 | 5340.50 | 01-MAY-08:62 | 0.71 |
June | 0.482126E+10 | 0.50 | 5340.50 | 01-JUN-08:51 | 0.70 |
July | 0.502730E+10 | 0.49 | 5340.50 | 01-JUL-08:61 | 0.71 |
August | 0.405817E+10 | 0.47 | 5340.50 | 01-AUG-08:52 | 0.71 |
September | 0.287629E+10 | 0.43 | 5340.50 | 01-SEP-08:51 | 0.70 |
October | 0.135974E+10 | 0.47 | 5340.50 | 01-OCT-08:62 | 0.71 |
November | 0.131525E+10 | 0.49 | 5340.50 | 01-NOV-08:62 | 0.71 |
December | 0.227679E+10 | 0.52 | 5340.50 | 02-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.299328E+11 | 0.48 | |||
Minimum of Months | 0.124509E+10 | 0.43 | 5340.50 | 0.70 | |
Maximum of Months | 0.502730E+10 | 0.52 | 5340.50 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358471E+09 | 0.57 | 905.46 | 01-JAN-09:01 | 0.71 |
February | 0.389930E+09 | 0.60 | 905.46 | 01-FEB-09:02 | 0.71 |
March | 0.434253E+09 | 0.61 | 905.46 | 01-MAR-09:01 | 0.71 |
April | 0.352668E+09 | 0.59 | 905.46 | 01-APR-15:02 | 0.71 |
May | 0.463080E+09 | 0.65 | 905.46 | 02-MAY-15:02 | 0.71 |
June | 0.940019E+09 | 0.69 | 905.46 | 01-JUN-08:62 | 0.70 |
July | 0.965560E+09 | 0.69 | 905.46 | 01-JUL-06:35 | 0.71 |
August | 0.929005E+09 | 0.69 | 905.46 | 01-AUG-08:62 | 0.71 |
September | 0.736177E+09 | 0.68 | 905.46 | 01-SEP-08:62 | 0.70 |
October | 0.462306E+09 | 0.64 | 905.46 | 01-OCT-08:62 | 0.71 |
November | 0.363314E+09 | 0.59 | 905.46 | 01-NOV-08:62 | 0.71 |
December | 0.472460E+09 | 0.58 | 905.46 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.686724E+10 | 0.63 | |||
Minimum of Months | 0.352668E+09 | 0.57 | 905.46 | 0.70 | |
Maximum of Months | 0.965560E+09 | 0.69 | 905.46 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360622E+09 | 0.52 | 884.76 | 01-JAN-09:01 | 0.71 |
February | 0.368189E+09 | 0.56 | 884.76 | 01-FEB-09:02 | 0.71 |
March | 0.336141E+09 | 0.55 | 884.76 | 01-MAR-09:01 | 0.71 |
April | 0.296589E+09 | 0.54 | 884.76 | 01-APR-15:02 | 0.71 |
May | 0.350800E+09 | 0.54 | 884.76 | 02-MAY-15:02 | 0.71 |
June | 0.772058E+09 | 0.55 | 884.76 | 01-JUN-08:51 | 0.70 |
July | 0.775022E+09 | 0.53 | 884.76 | 01-JUL-07:32 | 0.71 |
August | 0.679799E+09 | 0.54 | 884.76 | 01-AUG-08:52 | 0.71 |
September | 0.484324E+09 | 0.52 | 884.76 | 01-SEP-08:51 | 0.70 |
October | 0.307086E+09 | 0.54 | 884.76 | 01-OCT-08:62 | 0.71 |
November | 0.319278E+09 | 0.53 | 884.76 | 01-NOV-08:62 | 0.71 |
December | 0.526616E+09 | 0.56 | 884.76 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.557652E+10 | 0.54 | |||
Minimum of Months | 0.296589E+09 | 0.52 | 884.76 | 0.70 | |
Maximum of Months | 0.775022E+09 | 0.56 | 884.76 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112664E+09 | 0.58 | 274.21 | 01-JAN-16:02 | 0.71 |
February | 0.115572E+09 | 0.59 | 274.21 | 01-FEB-09:02 | 0.71 |
March | 0.128424E+09 | 0.61 | 274.21 | 01-MAR-09:01 | 0.71 |
April | 0.102719E+09 | 0.59 | 274.21 | 01-APR-15:02 | 0.71 |
May | 0.114704E+09 | 0.62 | 274.21 | 01-MAY-15:02 | 0.71 |
June | 0.226300E+09 | 0.67 | 274.21 | 01-JUN-08:62 | 0.70 |
July | 0.212215E+09 | 0.67 | 274.21 | 01-JUL-08:61 | 0.71 |
August | 0.210595E+09 | 0.67 | 274.21 | 01-AUG-08:62 | 0.71 |
September | 0.171317E+09 | 0.66 | 274.21 | 01-SEP-08:62 | 0.70 |
October | 0.133970E+09 | 0.63 | 274.21 | 01-OCT-08:62 | 0.71 |
November | 0.108601E+09 | 0.60 | 274.21 | 01-NOV-08:62 | 0.71 |
December | 0.152394E+09 | 0.59 | 274.21 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.178947E+10 | 0.62 | |||
Minimum of Months | 0.102719E+09 | 0.58 | 274.21 | 0.70 | |
Maximum of Months | 0.226300E+09 | 0.67 | 274.21 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122761E+09 | 0.56 | 267.42 | 01-JAN-09:01 | 0.71 |
February | 0.118933E+09 | 0.57 | 267.42 | 01-FEB-09:02 | 0.71 |
March | 0.102923E+09 | 0.55 | 267.42 | 01-MAR-09:01 | 0.71 |
April | 84358142.56 | 0.53 | 267.42 | 01-APR-15:02 | 0.71 |
May | 79351200.91 | 0.50 | 267.42 | 01-MAY-18:02 | 0.71 |
June | 0.198214E+09 | 0.53 | 267.42 | 01-JUN-08:51 | 0.70 |
July | 0.181629E+09 | 0.52 | 267.42 | 01-JUL-08:61 | 0.71 |
August | 0.164291E+09 | 0.52 | 267.42 | 01-AUG-08:52 | 0.71 |
September | 0.109809E+09 | 0.49 | 267.42 | 01-SEP-08:51 | 0.70 |
October | 92925005.61 | 0.54 | 267.42 | 01-OCT-15:02 | 0.71 |
November | 0.105676E+09 | 0.55 | 267.42 | 01-NOV-08:62 | 0.71 |
December | 0.178391E+09 | 0.59 | 267.42 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.153926E+10 | 0.54 | |||
Minimum of Months | 79351200.91 | 0.49 | 267.42 | 0.70 | |
Maximum of Months | 0.198214E+09 | 0.59 | 267.42 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.851002E+09 | 0.63 | 1200.85 | 01-JAN-09:01 | 0.71 |
February | 0.763856E+09 | 0.64 | 1200.85 | 01-FEB-09:02 | 0.71 |
March | 0.737007E+09 | 0.63 | 1200.85 | 01-MAR-09:01 | 0.71 |
April | 0.461392E+09 | 0.59 | 1200.85 | 01-APR-15:02 | 0.71 |
May | 0.517401E+09 | 0.62 | 1200.85 | 01-MAY-15:02 | 0.71 |
June | 0.949741E+09 | 0.67 | 1200.85 | 01-JUN-08:62 | 0.70 |
July | 0.101873E+10 | 0.67 | 1200.85 | 01-JUL-08:61 | 0.71 |
August | 0.111373E+10 | 0.67 | 1200.85 | 01-AUG-08:62 | 0.71 |
September | 0.112086E+10 | 0.67 | 1200.85 | 01-SEP-08:62 | 0.70 |
October | 0.933879E+09 | 0.64 | 1200.85 | 01-OCT-08:62 | 0.71 |
November | 0.880917E+09 | 0.64 | 1200.85 | 01-NOV-08:62 | 0.71 |
December | 0.801902E+09 | 0.62 | 1200.85 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.101504E+11 | 0.64 | |||
Minimum of Months | 0.461392E+09 | 0.59 | 1200.85 | 0.70 | |
Maximum of Months | 0.112086E+10 | 0.67 | 1200.85 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.948306E+09 | 0.853475E+09 | 1017.90 | 05-JAN-19:02 | 916.11 | 916.11 | 34.18 | 1.94 |
February | 0.958002E+09 | 0.862202E+09 | 1006.39 | 12-FEB-07:10 | 905.75 | 905.75 | 35.99 | 1.89 |
March | 0.825329E+09 | 0.742796E+09 | 983.35 | 21-MAR-15:02 | 885.02 | 885.02 | 32.74 | 1.78 |
April | 0.734215E+09 | 0.660793E+09 | 846.66 | 30-APR-23:40 | 761.99 | 761.99 | 40.22 | 1.31 |
May | 0.491011E+09 | 0.441910E+09 | 843.37 | 01-MAY-00:10 | 759.03 | 759.03 | 36.16 | 1.30 |
June | 32965745.99 | 29669171.39 | 712.98 | 09-JUN-05:10 | 641.68 | 641.68 | 32.28 | 1.00 |
July | 28978030.13 | 26080227.12 | 484.60 | 02-JUL-05:00 | 436.14 | 436.14 | 29.53 | 0.59 |
August | 29575395.31 | 26617855.77 | 358.38 | 12-AUG-23:00 | 322.54 | 322.54 | 27.30 | 0.42 |
September | 0.186214E+09 | 0.167593E+09 | 831.81 | 22-SEP-09:20 | 748.63 | 748.63 | 40.24 | 1.27 |
October | 0.657451E+09 | 0.591706E+09 | 899.30 | 27-OCT-10:00 | 809.37 | 809.37 | 36.93 | 1.47 |
November | 0.775643E+09 | 0.698078E+09 | 961.31 | 24-NOV-16:03 | 865.18 | 865.18 | 34.15 | 1.69 |
December | 0.119376E+10 | 0.107438E+10 | 1081.80 | 21-DEC-09:02 | 973.62 | 973.62 | 35.44 | 2.36 |
Annual Sum or Average | 0.686145E+10 | 0.617531E+10 | ||||||
Minimum of Months | 28978030.13 | 26080227.12 | 358.38 | 322.54 | 322.54 | 27.30 | 0.42 | |
Maximum of Months | 0.119376E+10 | 0.107438E+10 | 1081.80 | 973.62 | 973.62 | 40.24 | 2.36 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 33196023.65 | 29876421.29 | 285.67 | 20-JAN-13:40 | 257.10 | 257.10 | 6.72 | 7.43 |
February | 26051041.19 | 23445937.07 | 277.52 | 18-FEB-16:01 | 249.76 | 249.76 | 6.72 | 7.33 |
March | 60152653.06 | 54137387.76 | 570.04 | 13-MAR-15:03 | 513.03 | 513.03 | 6.72 | 10.07 |
April | 38396122.35 | 34556510.11 | 382.39 | 07-APR-15:03 | 344.15 | 344.15 | 6.72 | 8.46 |
May | 0.204415E+09 | 0.183974E+09 | 1749.32 | 31-MAY-18:50 | 1574.39 | 1574.39 | 6.72 | 16.09 |
June | 0.946268E+09 | 0.851642E+09 | 3011.79 | 15-JUN-18:02 | 2710.61 | 2710.61 | 6.72 | 19.99 |
July | 0.112814E+10 | 0.101532E+10 | 3114.45 | 10-JUL-18:06 | 2803.00 | 2803.00 | 6.72 | 20.26 |
August | 0.106582E+10 | 0.959238E+09 | 3158.94 | 10-AUG-19:02 | 2843.04 | 2843.04 | 6.72 | 20.37 |
September | 0.594194E+09 | 0.534775E+09 | 3063.85 | 12-SEP-18:23 | 2757.47 | 2757.47 | 6.72 | 20.13 |
October | 0.106703E+09 | 96032447.12 | 682.11 | 11-OCT-15:03 | 613.90 | 613.90 | 6.72 | 10.88 |
November | 45267600.38 | 40740840.34 | 381.31 | 06-NOV-16:02 | 343.18 | 343.18 | 6.72 | 8.45 |
December | 23150546.33 | 20835491.69 | 239.42 | 02-DEC-16:01 | 215.48 | 215.48 | 6.72 | 6.85 |
Annual Sum or Average | 0.427175E+10 | 0.384458E+10 | ||||||
Minimum of Months | 23150546.33 | 20835491.69 | 239.42 | 215.48 | 215.48 | 6.72 | 6.85 | |
Maximum of Months | 0.112814E+10 | 0.101532E+10 | 3158.94 | 2843.04 | 2843.04 | 6.72 | 20.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.377585E+10 | 0.339826E+10 | 2390.01 | 01-JAN-01:20 | 2151.01 | 2151.01 | 6.72 | 21.14 |
February | 0.301826E+10 | 0.271644E+10 | 2390.01 | 01-FEB-09:05 | 2151.01 | 2151.01 | 6.79 | 21.14 |
March | 0.385760E+10 | 0.347184E+10 | 2390.01 | 01-MAR-07:20 | 2151.01 | 2151.01 | 6.73 | 21.14 |
April | 0.379641E+10 | 0.341677E+10 | 2390.01 | 01-APR-00:10 | 2151.01 | 2151.01 | 6.79 | 21.14 |
May | 0.615376E+10 | 0.553838E+10 | 2390.01 | 01-MAY-05:05 | 2151.01 | 2151.01 | 6.76 | 21.14 |
June | 0.619491E+10 | 0.557542E+10 | 2390.01 | 01-JUN-00:05 | 2151.01 | 2151.01 | 7.44 | 21.14 |
July | 0.640141E+10 | 0.576127E+10 | 2390.01 | 01-JUL-00:10 | 2151.01 | 2151.01 | 8.96 | 21.14 |
August | 0.640141E+10 | 0.576127E+10 | 2390.01 | 01-AUG-00:05 | 2151.01 | 2151.01 | 8.25 | 21.14 |
September | 0.612188E+10 | 0.550969E+10 | 2390.01 | 01-SEP-00:10 | 2151.01 | 2151.01 | 8.11 | 21.14 |
October | 0.449715E+10 | 0.404744E+10 | 2390.01 | 01-OCT-00:10 | 2151.01 | 2151.01 | 6.96 | 21.14 |
November | 0.391698E+10 | 0.352528E+10 | 2390.01 | 01-NOV-03:05 | 2151.01 | 2151.01 | 6.72 | 21.14 |
December | 0.280958E+10 | 0.252862E+10 | 2390.01 | 01-DEC-07:50 | 2151.01 | 2151.01 | 6.74 | 21.14 |
Annual Sum or Average | 0.569452E+11 | 0.512507E+11 | ||||||
Minimum of Months | 0.280958E+10 | 0.252862E+10 | 2390.01 | 2151.01 | 2151.01 | 6.72 | 21.14 | |
Maximum of Months | 0.640141E+10 | 0.576127E+10 | 2390.01 | 2151.01 | 2151.01 | 8.96 | 21.14 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.05 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 48.33 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 48.76 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.93 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.69 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 51.70 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.38 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.46 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.04 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.69 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.50 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 49.12 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.05 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.04 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 45.79 | 60.00 | 42499.22 | 217953.64 | 05-JAN-19:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40.71 | 60.00 | 48936.08 | 201898.32 | 07-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 45.85 | 60.00 | 38044.27 | 202871.37 | 21-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.39 | 60.00 | 35880.35 | 139895.80 | 30-APR-08:07 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 36.15 | 60.00 | 27838.55 | 133719.27 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.83 | 24.83 | 2012.35 | 115452.88 | 09-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.71 | 23.71 | 1699.40 | 75761.49 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.82 | 33.82 | 1737.63 | 56796.47 | 12-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.62 | 25.62 | 10948.03 | 133271.63 | 21-SEP-14:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.25 | 60.00 | 32180.76 | 166441.83 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 40.57 | 60.00 | 34906.85 | 182384.24 | 24-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46.17 | 60.00 | 61330.79 | 249043.17 | 21-DEC-09:08 |
Annual Sum or Average | 0.00 | 28076.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.71 | 23.71 | 1699.40 | 56796.47 | ||
Maximum of Months | 0.00 | 0.00 | 46.17 | 60.00 | 61330.79 | 249043.17 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18846.00 | 224362.67 | 20-JAN-13:15 | 9.23 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15482.12 | 206861.01 | 18-FEB-13:30 | 9.03 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24213.65 | 334971.18 | 13-MAR-15:03 | 10.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18791.01 | 261065.38 | 07-APR-15:03 | 9.65 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 63454.39 | 350771.24 | 31-MAY-18:03 | 10.66 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 177880.22 | 435985.06 | 27-JUN-18:53 | 11.62 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 192259.94 | 424879.84 | 17-JUL-18:32 | 11.50 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 177226.32 | 428988.86 | 14-AUG-18:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 134083.29 | 406293.37 | 13-SEP-15:06 | 11.29 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38839.12 | 372882.04 | 11-OCT-15:03 | 10.91 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22309.66 | 261938.53 | 05-NOV-15:02 | 9.66 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 13377.87 | 196385.08 | 02-DEC-13:15 | 8.92 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 75068.93 | 0.00 | ||||||
Minimum of Months | 13377.87 | 196385.08 | 8.92 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 192259.94 | 435985.06 | 11.62 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.05 | 59.40 | 29092.59 | 59645.53 | 31-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 48.33 | 58.59 | 29438.54 | 59811.96 | 13-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 48.76 | 59.39 | 29047.29 | 59557.31 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.93 | 58.36 | 27948.82 | 57710.32 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.69 | 59.43 | 26479.40 | 55121.98 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 51.70 | 58.50 | 25023.56 | 51970.69 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.38 | 58.69 | 23941.75 | 48992.54 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.46 | 58.70 | 23592.59 | 47680.30 | 31-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.04 | 59.53 | 24006.89 | 49268.61 | 29-SEP-06:47 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.69 | 58.87 | 25099.23 | 52111.35 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.50 | 58.31 | 26576.97 | 55306.34 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49.12 | 58.64 | 28033.12 | 57944.83 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 26506.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.05 | 58.31 | 23592.59 | 47680.30 | ||
Maximum of Months | 0.00 | 0.00 | 53.04 | 59.53 | 29438.54 | 59811.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.810584E+11 | 0.00 | 0.508402E+10 | 0.333735E+11 | 0.00 | 0.00 |
February | 0.831469E+11 | 0.00 | 0.284855E+10 | 0.295882E+11 | 0.00 | 0.00 |
March | 0.809287E+11 | 0.00 | 0.178962E+11 | 0.340077E+11 | 0.00 | 0.00 |
April | 0.784909E+11 | 0.00 | 0.188813E+11 | 0.324503E+11 | 0.00 | 0.00 |
May | 0.737580E+11 | 0.00 | 0.885542E+11 | 0.367212E+11 | 0.00 | 0.00 |
June | 0.524542E+10 | 0.00 | 0.291935E+12 | 0.413885E+11 | 0.00 | 0.00 |
July | 0.456579E+10 | 0.00 | 0.335840E+12 | 0.430149E+11 | 0.00 | 0.00 |
August | 0.468682E+10 | 0.00 | 0.299728E+12 | 0.440940E+11 | 0.00 | 0.00 |
September | 0.280807E+11 | 0.00 | 0.206446E+12 | 0.422247E+11 | 0.00 | 0.00 |
October | 0.719289E+11 | 0.00 | 0.333491E+11 | 0.379826E+11 | 0.00 | 0.00 |
November | 0.655814E+11 | 0.00 | 0.104961E+11 | 0.346437E+11 | 0.00 | 0.00 |
December | 0.114764E+12 | 0.00 | 0.696639E+10 | 0.335295E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.692235E+12 | 0.00 | 0.131802E+13 | 0.443019E+12 | 0.00 | 0.00 |
Minimum of Months | 0.456579E+10 | 0.00 | 0.284855E+10 | 0.295882E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114764E+12 | 0.00 | 0.335840E+12 | 0.440940E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.164885E+10 | 0.00 | 0.192283E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.177323E+10 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.709553E+09 | 0.00 | 0.893958E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.322736E+09 | 0.00 | 0.105767E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 16045.21 | 0.00 | 0.512456E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 31903.86 | 0.00 | 0.173122E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 42012.19 | 0.00 | 0.210669E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 33741.78 | 0.00 | 0.182535E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 934149.07 | 0.00 | 0.117385E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.512380E+09 | 0.00 | 0.173199E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.825086E+09 | 0.00 | 0.497100E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.310727E+10 | 0.00 | 0.275045E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.890017E+10 | 0.00 | 0.782673E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 16045.21 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.310727E+10 | 0.00 | 0.210669E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333735E+11 | 0.508402E+10 | 0.810584E+11 | 0.525258E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295882E+11 | 0.284855E+10 | 0.831469E+11 | 0.502154E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340077E+11 | 0.178962E+11 | 0.809287E+11 | 0.360870E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324503E+11 | 0.188813E+11 | 0.784909E+11 | 0.298035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367212E+11 | 0.885542E+11 | 0.737580E+11 | 0.489532E+11 | 0.435471E+09 | 0.00 | 0.00 | 0.00 |
June | 0.413885E+11 | 0.291935E+12 | 0.524542E+10 | 0.668987E+10 | 0.189774E+11 | 0.00 | 0.00 | 0.00 |
July | 0.430149E+11 | 0.335840E+12 | 0.456579E+10 | 0.646360E+10 | 0.204411E+11 | 0.00 | 0.00 | 0.00 |
August | 0.440940E+11 | 0.299728E+12 | 0.468682E+10 | 0.619208E+10 | 0.159079E+11 | 0.00 | 0.00 | 0.00 |
September | 0.422247E+11 | 0.206446E+12 | 0.280807E+11 | 0.234224E+11 | 0.604188E+10 | 0.00 | 0.00 | 0.00 |
October | 0.379826E+11 | 0.333491E+11 | 0.719289E+11 | 0.297365E+12 | 13035706.55 | 0.00 | 0.00 | 0.00 |
November | 0.346437E+11 | 0.104961E+11 | 0.655814E+11 | 0.451443E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335295E+11 | 0.696639E+10 | 0.114764E+12 | 0.566351E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443019E+12 | 0.131802E+13 | 0.692235E+12 | 0.309320E+13 | 0.618168E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.295882E+11 | 0.284855E+10 | 0.456579E+10 | 0.619208E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440940E+11 | 0.335840E+12 | 0.114764E+12 | 0.566351E+12 | 0.204411E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.192283E+09 | 0.164885E+10 | 0.447751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.123483E+09 | 0.177323E+10 | 0.427676E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.893958E+09 | 0.709553E+09 | 0.343136E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.105767E+10 | 0.322736E+09 | 0.300114E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.512456E+10 | 16045.21 | 0.120859E+11 | 18431367.34 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.173122E+11 | 31903.86 | 0.131892E+10 | 0.119805E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.210669E+11 | 42012.19 | 0.103001E+10 | 0.136095E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.182535E+11 | 33741.78 | 0.112513E+10 | 0.825500E+09 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.117385E+11 | 934149.07 | 0.488631E+10 | 0.269066E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.173199E+10 | 0.512380E+09 | 0.282380E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.497100E+09 | 0.825086E+09 | 0.383823E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.275045E+09 | 0.310727E+10 | 0.479347E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.782673E+11 | 0.890017E+10 | 0.286869E+12 | 0.367200E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.123483E+09 | 16045.21 | 0.103001E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.210669E+11 | 0.310727E+10 | 0.479347E+11 | 0.136095E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.333735E+11 | 0.810584E+11 | 0.508402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295882E+11 | 0.831469E+11 | 0.284855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340077E+11 | 0.809287E+11 | 0.178962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324503E+11 | 0.784909E+11 | 0.188813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367212E+11 | 0.737580E+11 | 0.885542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413885E+11 | 0.524542E+10 | 0.291935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.430149E+11 | 0.456579E+10 | 0.335840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.440940E+11 | 0.468682E+10 | 0.299728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.422247E+11 | 0.280807E+11 | 0.206446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.379826E+11 | 0.719289E+11 | 0.333491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346437E+11 | 0.655814E+11 | 0.104961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335295E+11 | 0.114764E+12 | 0.696639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443019E+12 | 0.692235E+12 | 0.131802E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.295882E+11 | 0.456579E+10 | 0.284855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440940E+11 | 0.114764E+12 | 0.335840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.164885E+10 | 0.192283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.177323E+10 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.709553E+09 | 0.893958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.322736E+09 | 0.105767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 16045.21 | 0.512456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 31903.86 | 0.173122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 42012.19 | 0.210669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 33741.78 | 0.182535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 934149.07 | 0.117385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.512380E+09 | 0.173199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.825086E+09 | 0.497100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.310727E+10 | 0.275045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.890017E+10 | 0.782673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 16045.21 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.310727E+10 | 0.210669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.762903E+10 | 0.00 | 0.00 | 42129611.47 | 0.00 | 0.00 | 0.428576E+11 | 0.00 | 1.05 |
February | 0.170031E+11 | 0.00 | 0.00 | 19348171.70 | 0.00 | 0.00 | 0.271008E+11 | 0.00 | 1.00 |
March | 0.302741E+11 | 0.00 | 0.00 | 9285730.49 | 0.00 | 0.00 | 0.157064E+11 | 0.00 | 0.98 |
April | 0.254314E+11 | 0.00 | 0.00 | 10902105.75 | 0.00 | 0.00 | 0.189352E+11 | 0.00 | 0.98 |
May | 0.239644E+11 | 0.00 | 0.00 | 10846243.97 | 3274342.76 | 0.00 | 0.169676E+11 | 0.00 | 0.97 |
June | 0.280668E+10 | 14749196.20 | 0.00 | 31750715.33 | 0.437117E+09 | 0.00 | 0.170846E+11 | 0.00 | 0.97 |
July | 0.113003E+10 | 46880940.86 | 0.00 | 39238874.40 | 0.559634E+09 | 0.00 | 0.168159E+11 | 0.00 | 0.98 |
August | 0.502328E+09 | 0.321752E+09 | 0.00 | 70403503.18 | 37718750.98 | 0.00 | 0.236656E+11 | 0.00 | 1.10 |
September | 12451719.06 | 79668972.83 | 0.00 | 95178138.62 | 7220.10 | 0.00 | 0.379768E+11 | 0.00 | 1.26 |
October | 1560951.65 | 0.00 | 0.00 | 91186071.92 | 0.00 | 0.00 | 0.599438E+11 | 0.00 | 1.29 |
November | 21509019.94 | 0.00 | 0.00 | 83090549.60 | 0.00 | 0.00 | 0.577119E+11 | 0.00 | 1.28 |
December | 0.122863E+09 | 0.00 | 0.00 | 78425435.84 | 0.00 | 0.00 | 0.608453E+11 | 0.00 | 1.22 |
Annual Sum or Average | 0.108900E+12 | 0.463052E+09 | 0.00 | 0.581785E+09 | 0.103775E+10 | 0.00 | 0.395612E+12 | 0.00 | 1.09 |
Minimum of Months | 1560951.65 | 0.00 | 0.00 | 9285730.49 | 0.00 | 0.00 | 0.157064E+11 | 0.00 | 0.97 |
Maximum of Months | 0.302741E+11 | 0.321752E+09 | 0.00 | 95178138.62 | 0.559634E+09 | 0.00 | 0.608453E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456224E+10 | 0.00 | 0.00 | 3967386.73 | 0.00 | 0.882453E+09 | 0.260272E+10 | 0.00 | 3.07 |
February | 0.344186E+10 | 0.00 | 0.00 | 3468997.53 | 0.00 | 0.145514E+10 | 0.248090E+10 | 0.00 | 3.02 |
March | 0.413508E+10 | 0.00 | 0.00 | 3711517.04 | 0.00 | 0.126542E+10 | 0.201646E+10 | 0.00 | 2.94 |
April | 0.509236E+10 | 0.00 | 0.00 | 1049994.74 | 0.00 | 0.100150E+10 | 0.657501E+09 | 0.00 | 2.71 |
May | 0.565496E+10 | 574179.64 | 0.00 | 1046801.09 | 0.00 | 0.00 | 0.516449E+09 | 0.00 | 2.67 |
June | 0.189166E+10 | 94882043.85 | 0.00 | 4173824.30 | 308304.02 | 0.00 | 0.104106E+10 | 0.00 | 2.75 |
July | 0.163037E+10 | 0.116477E+09 | 0.00 | 4166427.33 | 3510873.58 | 0.00 | 0.977148E+09 | 0.00 | 2.76 |
August | 0.183752E+10 | 88199798.05 | 0.00 | 6187881.74 | 0.00 | 0.00 | 0.131191E+10 | 0.00 | 3.02 |
September | 0.259210E+10 | 22037802.91 | 0.00 | 7676002.23 | 0.00 | 0.00 | 0.170166E+10 | 0.00 | 3.14 |
October | 0.388160E+10 | 0.00 | 0.00 | 5576848.32 | 0.00 | 0.925784E+09 | 0.265666E+10 | 0.00 | 3.11 |
November | 0.411883E+10 | 0.00 | 0.00 | 4318595.18 | 0.00 | 0.784570E+09 | 0.271400E+10 | 0.00 | 3.10 |
December | 0.442239E+10 | 0.00 | 0.00 | 2980167.17 | 0.00 | 0.182988E+10 | 0.182177E+10 | 0.00 | 2.96 |
Annual Sum or Average | 0.432610E+11 | 0.322170E+09 | 0.00 | 48324443.41 | 3819177.60 | 0.814474E+10 | 0.204982E+11 | 0.00 | 2.94 |
Minimum of Months | 0.163037E+10 | 0.00 | 0.00 | 1046801.09 | 0.00 | 0.00 | 0.516449E+09 | 0.00 | 2.67 |
Maximum of Months | 0.565496E+10 | 0.116477E+09 | 0.00 | 7676002.23 | 3510873.58 | 0.182988E+10 | 0.271400E+10 | 0.00 | 3.14 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322225E+10 | 0.00 | 0.00 | 760644.21 | 0.00 | 0.00 | 0.121240E+10 | 0.00 | 1.44 |
February | 0.298787E+10 | 0.00 | 0.00 | 652733.45 | 0.00 | 0.00 | 0.105922E+10 | 0.00 | 1.44 |
March | 0.272924E+10 | 0.00 | 0.00 | 1675384.77 | 0.00 | 0.00 | 0.170968E+10 | 0.00 | 1.47 |
April | 0.287499E+10 | 0.00 | 0.00 | 929633.48 | 0.00 | 0.00 | 0.132053E+10 | 0.00 | 1.45 |
May | 0.132615E+10 | 307524.10 | 0.00 | 2567649.74 | 0.00 | 0.00 | 0.267461E+10 | 0.00 | 1.49 |
June | 58563386.18 | 44177072.85 | 0.00 | 6623204.03 | 528011.14 | 0.00 | 0.215179E+10 | 0.00 | 1.65 |
July | 24809507.92 | 54005998.42 | 0.00 | 6730740.54 | 4265921.07 | 0.00 | 0.194478E+10 | 0.00 | 1.63 |
August | 70600592.40 | 36446534.55 | 0.00 | 6930196.52 | 144811.15 | 0.00 | 0.222964E+10 | 0.00 | 1.68 |
September | 0.239443E+09 | 7791236.34 | 0.00 | 6406792.16 | 0.00 | 0.00 | 0.276433E+10 | 0.00 | 1.65 |
October | 0.185209E+10 | 0.00 | 0.00 | 2682090.29 | 0.00 | 0.00 | 0.253220E+10 | 0.00 | 1.50 |
November | 0.264241E+10 | 0.00 | 0.00 | 1089885.27 | 0.00 | 0.00 | 0.152992E+10 | 0.00 | 1.45 |
December | 0.374589E+10 | 0.00 | 0.00 | 460002.94 | 0.00 | 0.00 | 0.820027E+09 | 0.00 | 1.42 |
Annual Sum or Average | 0.217743E+11 | 0.142728E+09 | 0.00 | 37508957.39 | 4938743.36 | 0.00 | 0.219491E+11 | 0.00 | 1.52 |
Minimum of Months | 24809507.92 | 0.00 | 0.00 | 460002.94 | 0.00 | 0.00 | 0.820027E+09 | 0.00 | 1.42 |
Maximum of Months | 0.374589E+10 | 54005998.42 | 0.00 | 6930196.52 | 4265921.07 | 0.00 | 0.276433E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201225E+09 | 0.00 | 0.00 | 0.54 |
February | 0.279435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426901E+09 | 0.00 | 0.00 | 0.54 |
March | 0.342509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24156075.38 | 0.00 | 0.00 | 0.54 |
April | 0.330272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17521808.96 | 0.00 | 0.00 | 0.54 |
May | 0.299526E+10 | 0.00 | 0.00 | 78486.72 | 247151.42 | 0.00 | 76150989.91 | 0.00 | 0.54 |
June | 0.449834E+09 | 35712482.68 | 0.00 | 3655297.17 | 1397772.43 | 0.00 | 0.114886E+10 | 0.00 | 0.59 |
July | 0.224895E+09 | 36142060.22 | 0.00 | 4523823.52 | 12224366.07 | 0.00 | 0.123087E+10 | 0.00 | 0.60 |
August | 0.487026E+09 | 25383491.71 | 0.00 | 3310266.71 | 2493536.42 | 0.00 | 0.116171E+10 | 0.00 | 0.58 |
September | 0.127597E+10 | 4437589.97 | 0.00 | 1922078.15 | 1525733.26 | 0.00 | 0.857155E+09 | 0.00 | 0.56 |
October | 0.320226E+10 | 0.00 | 0.00 | 9727.61 | 0.00 | 0.106725E+09 | 30193729.07 | 0.00 | 0.54 |
November | 0.312760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166387E+09 | 0.00 | 0.00 | 0.54 |
December | 0.284640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808653E+09 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.274571E+11 | 0.101676E+09 | 0.00 | 13499679.88 | 17888559.61 | 0.175157E+10 | 0.450494E+10 | 0.00 | 0.55 |
Minimum of Months | 0.224895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.342509E+10 | 36142060.22 | 0.00 | 4523823.52 | 12224366.07 | 0.808653E+09 | 0.123087E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261006E+09 | 0.00 | 0.00 | 0.56 |
February | 0.144560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473557E+09 | 0.00 | 0.00 | 0.55 |
March | 0.192945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125539E+09 | 0.00 | 0.00 | 0.56 |
April | 0.188109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97041533.66 | 0.00 | 0.00 | 0.56 |
May | 0.182871E+10 | 0.00 | 0.00 | 0.00 | 147248.00 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.536034E+09 | 19646913.87 | 0.00 | 1043212.35 | 1989430.42 | 0.00 | 0.347462E+09 | 0.00 | 0.56 |
July | 0.360967E+09 | 20290920.37 | 0.00 | 1358247.23 | 8303713.70 | 0.00 | 0.431266E+09 | 0.00 | 0.56 |
August | 0.618882E+09 | 13532506.08 | 0.00 | 712651.49 | 2728706.68 | 0.00 | 0.303595E+09 | 0.00 | 0.56 |
September | 0.105905E+10 | 2414959.58 | 0.00 | 314302.94 | 1123238.60 | 0.00 | 0.168086E+09 | 0.00 | 0.56 |
October | 0.186285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126573E+09 | 0.00 | 0.00 | 0.55 |
November | 0.174942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213068E+09 | 0.00 | 0.00 | 0.56 |
December | 0.158250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599521E+09 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.166948E+11 | 55885299.90 | 0.00 | 3428414.01 | 14292337.41 | 0.189630E+10 | 0.125041E+10 | 0.00 | 0.56 |
Minimum of Months | 0.360967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.192945E+10 | 20290920.37 | 0.00 | 1358247.23 | 8303713.70 | 0.599521E+09 | 0.431266E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17906629.88 | 0.00 | 0.00 | 0.107954E+09 | 0.00 | 0.00 | 0.814169E+11 | 0.00 | 26.41 |
February | 13719853.00 | 0.00 | 0.00 | 96277609.09 | 0.00 | 0.00 | 0.739330E+11 | 0.00 | 26.25 |
March | 0.00 | 0.00 | 0.00 | 0.112457E+09 | 0.00 | 0.00 | 0.802544E+11 | 0.00 | 26.45 |
April | 0.00 | 0.00 | 0.00 | 0.106085E+09 | 0.00 | 0.00 | 0.767066E+11 | 0.00 | 26.36 |
May | 0.00 | 4646798.70 | 0.00 | 0.127440E+09 | 0.00 | 0.00 | 0.720085E+11 | 0.00 | 26.48 |
June | 0.00 | 0.642541E+09 | 0.00 | 0.133717E+09 | 0.00 | 0.00 | 0.330425E+11 | 0.00 | 25.49 |
July | 0.00 | 0.864661E+09 | 0.00 | 0.126824E+09 | 0.00 | 0.00 | 0.293760E+11 | 0.00 | 25.21 |
August | 0.00 | 0.510799E+09 | 0.00 | 0.137702E+09 | 0.00 | 0.00 | 0.352711E+11 | 0.00 | 26.05 |
September | 0.00 | 0.110346E+09 | 0.00 | 0.132058E+09 | 0.00 | 0.00 | 0.483864E+11 | 0.00 | 26.36 |
October | 14041256.70 | 0.00 | 0.00 | 0.115620E+09 | 0.00 | 0.00 | 0.781533E+11 | 0.00 | 26.36 |
November | 0.00 | 0.00 | 0.00 | 0.105256E+09 | 0.00 | 0.00 | 0.761507E+11 | 0.00 | 26.43 |
December | 39123913.59 | 0.00 | 0.00 | 0.106490E+09 | 0.00 | 0.00 | 0.838612E+11 | 0.00 | 26.10 |
Annual Sum or Average | 84791653.17 | 0.213299E+10 | 0.00 | 0.140788E+10 | 0.00 | 0.00 | 0.768561E+12 | 0.00 | 26.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 96277609.09 | 0.00 | 0.00 | 0.293760E+11 | 0.00 | 25.21 |
Maximum of Months | 39123913.59 | 0.864661E+09 | 0.00 | 0.137702E+09 | 0.00 | 0.00 | 0.838612E+11 | 0.00 | 26.48 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.717980E+10 | 0.00 | 0.00 | 30039169.01 | 0.00 | 36591228.32 | 0.267204E+11 | 0.00 | 4.61 |
February | 0.806238E+10 | 0.00 | 0.00 | 25438581.62 | 0.00 | 0.343183E+09 | 0.226965E+11 | 0.00 | 4.54 |
March | 0.867820E+10 | 0.00 | 0.00 | 29035645.07 | 0.00 | 0.00 | 0.231997E+11 | 0.00 | 4.46 |
April | 0.108756E+11 | 0.00 | 0.00 | 18085585.68 | 0.00 | 0.00 | 0.178381E+11 | 0.00 | 4.11 |
May | 0.364726E+10 | 2397784.07 | 0.00 | 27779819.80 | 0.00 | 0.00 | 0.229802E+11 | 0.00 | 4.11 |
June | 0.504241E+09 | 0.350990E+09 | 0.00 | 40592905.64 | 154061.91 | 0.00 | 0.136767E+11 | 0.00 | 4.44 |
July | 0.234141E+09 | 0.455831E+09 | 0.00 | 40925270.09 | 986330.31 | 0.00 | 0.125015E+11 | 0.00 | 4.45 |
August | 0.450198E+09 | 0.322199E+09 | 0.00 | 48245708.09 | 0.00 | 0.00 | 0.147228E+11 | 0.00 | 4.80 |
September | 0.763119E+09 | 77414731.04 | 0.00 | 52055582.69 | 0.00 | 0.00 | 0.194523E+11 | 0.00 | 4.92 |
October | 0.663512E+10 | 0.00 | 0.00 | 38935497.01 | 0.00 | 0.296554E+09 | 0.252116E+11 | 0.00 | 4.70 |
November | 0.654440E+10 | 0.00 | 0.00 | 31681073.63 | 0.00 | 1251196.86 | 0.256693E+11 | 0.00 | 4.65 |
December | 0.118190E+11 | 0.00 | 0.00 | 22825898.31 | 0.00 | 0.569958E+09 | 0.213621E+11 | 0.00 | 4.41 |
Annual Sum or Average | 0.653935E+11 | 0.120883E+10 | 0.00 | 0.405641E+09 | 1140392.22 | 0.124754E+10 | 0.246031E+12 | 0.00 | 4.52 |
Minimum of Months | 0.234141E+09 | 0.00 | 0.00 | 18085585.68 | 0.00 | 0.00 | 0.125015E+11 | 0.00 | 4.11 |
Maximum of Months | 0.118190E+11 | 0.455831E+09 | 0.00 | 52055582.69 | 986330.31 | 0.569958E+09 | 0.267204E+11 | 0.00 | 4.92 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267937E+11 | 0.00 | 0.00 | 70373438.66 | 0.00 | 0.00 | 0.712266E+11 | 0.00 | 1.90 |
February | 0.304498E+11 | 0.00 | 0.00 | 54763591.60 | 0.00 | 0.00 | 0.586823E+11 | 0.00 | 1.89 |
March | 0.324369E+11 | 0.00 | 0.00 | 73585466.38 | 0.00 | 0.00 | 0.659190E+11 | 0.00 | 1.94 |
April | 0.350840E+11 | 0.00 | 0.00 | 50576565.25 | 0.00 | 0.00 | 0.573654E+11 | 0.00 | 1.89 |
May | 0.129366E+11 | 6580924.79 | 0.00 | 93838006.92 | 0.00 | 0.00 | 0.785525E+11 | 0.00 | 2.00 |
June | 0.954978E+09 | 0.942016E+09 | 0.00 | 0.148501E+09 | 7205517.39 | 0.00 | 0.498128E+11 | 0.00 | 2.16 |
July | 0.384193E+09 | 0.122981E+10 | 0.00 | 0.151712E+09 | 26625351.12 | 0.00 | 0.452850E+11 | 0.00 | 2.15 |
August | 0.768860E+09 | 0.804534E+09 | 0.00 | 0.161637E+09 | 1018195.95 | 0.00 | 0.522804E+11 | 0.00 | 2.23 |
September | 0.169100E+10 | 0.179699E+09 | 0.00 | 0.164740E+09 | 0.00 | 0.00 | 0.675103E+11 | 0.00 | 2.22 |
October | 0.195602E+11 | 0.00 | 0.00 | 0.109868E+09 | 0.00 | 0.00 | 0.794196E+11 | 0.00 | 2.02 |
November | 0.221079E+11 | 0.00 | 0.00 | 79678334.16 | 0.00 | 0.00 | 0.713236E+11 | 0.00 | 1.93 |
December | 0.448216E+11 | 0.00 | 0.00 | 51782579.88 | 0.00 | 0.00 | 0.553276E+11 | 0.00 | 1.87 |
Annual Sum or Average | 0.227990E+12 | 0.316264E+10 | 0.00 | 0.121106E+10 | 34849064.46 | 0.00 | 0.752705E+12 | 0.00 | 2.02 |
Minimum of Months | 0.384193E+09 | 0.00 | 0.00 | 50576565.25 | 0.00 | 0.00 | 0.452850E+11 | 0.00 | 1.87 |
Maximum of Months | 0.448216E+11 | 0.122981E+10 | 0.00 | 0.164740E+09 | 26625351.12 | 0.00 | 0.794196E+11 | 0.00 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26138929.80 | 0.00 | 0.00 | 3573905.03 | 0.00 | 0.932393E+09 | 0.362181E+09 | 0.00 | 0.36 |
February | 21684474.59 | 0.00 | 0.00 | 3555119.22 | 0.00 | 0.838012E+09 | 0.339516E+09 | 0.00 | 0.35 |
March | 27072718.80 | 0.00 | 0.00 | 7988367.71 | 0.00 | 0.709934E+09 | 0.528499E+09 | 0.00 | 0.36 |
April | 41591464.05 | 0.00 | 0.00 | 5630933.12 | 0.00 | 0.668322E+09 | 0.488284E+09 | 0.00 | 0.36 |
May | 19779584.12 | 0.00 | 0.00 | 13477919.82 | 0.00 | 0.121070E+09 | 0.969589E+09 | 0.00 | 0.35 |
June | 0.00 | 7269287.16 | 0.00 | 20496991.96 | 0.00 | 443217.75 | 0.582028E+09 | 0.00 | 0.35 |
July | 0.00 | 17569971.51 | 0.00 | 18130129.91 | 0.00 | 401232.64 | 0.468268E+09 | 417.36 | 0.35 |
August | 0.00 | 24217956.92 | 0.00 | 20866562.52 | 0.00 | 1005501.62 | 0.547815E+09 | 0.00 | 0.35 |
September | 4511672.05 | 982599.98 | 0.00 | 19282387.20 | 0.00 | 40232711.51 | 0.784547E+09 | 0.00 | 0.35 |
October | 10922272.11 | 0.00 | 0.00 | 10813377.35 | 0.00 | 0.485059E+09 | 0.737258E+09 | 0.00 | 0.35 |
November | 18275040.39 | 0.00 | 0.00 | 4662763.94 | 0.00 | 0.746166E+09 | 0.473375E+09 | 0.00 | 0.36 |
December | 33424597.55 | 0.00 | 0.00 | 2078290.84 | 0.00 | 0.111461E+10 | 0.237423E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.203401E+09 | 50039815.57 | 0.00 | 0.130557E+09 | 0.00 | 0.565765E+10 | 0.651878E+10 | 417.36 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2078290.84 | 0.00 | 401232.64 | 0.237423E+09 | 0.00 | 0.35 |
Maximum of Months | 41591464.05 | 24217956.92 | 0.00 | 20866562.52 | 0.00 | 0.111461E+10 | 0.969589E+09 | 417.36 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66086178.09 | 0.00 | 0.00 | 1057219.84 | 0.00 | 0.116165E+10 | 95339304.80 | 0.00 | 0.36 |
February | 55685489.35 | 0.00 | 0.00 | 1282329.12 | 0.00 | 0.101957E+10 | 0.126085E+09 | 0.00 | 0.35 |
March | 89842479.16 | 0.00 | 0.00 | 3955787.63 | 0.00 | 0.822877E+09 | 0.356670E+09 | 0.00 | 0.36 |
April | 0.103864E+09 | 0.00 | 0.00 | 3552194.61 | 0.00 | 0.726338E+09 | 0.369933E+09 | 0.00 | 0.36 |
May | 0.176318E+09 | 0.00 | 0.00 | 9653606.28 | 0.00 | 0.122719E+09 | 0.815095E+09 | 0.00 | 0.35 |
June | 0.140581E+09 | 6659363.09 | 0.00 | 17221702.27 | 608957.44 | 63393.75 | 0.445032E+09 | 114.93 | 0.35 |
July | 0.139070E+09 | 13737352.97 | 211.36 | 14291582.63 | 3830736.55 | 128045.96 | 0.333253E+09 | 29.37 | 0.35 |
August | 0.158871E+09 | 22410955.83 | 9599.36 | 15478077.41 | 1794408.42 | 312502.26 | 0.394958E+09 | 155.82 | 0.35 |
September | 0.187459E+09 | 840681.36 | 0.00 | 12582940.55 | 141803.49 | 45509464.65 | 0.602923E+09 | 0.00 | 0.35 |
October | 0.114398E+09 | 0.00 | 0.00 | 4854171.69 | 0.00 | 0.628251E+09 | 0.496404E+09 | 0.00 | 0.35 |
November | 66959081.90 | 0.00 | 0.00 | 1473222.24 | 0.00 | 0.100344E+10 | 0.170463E+09 | 0.00 | 0.36 |
December | 50327023.97 | 0.00 | 0.00 | 560003.97 | 0.00 | 0.128052E+10 | 55967414.85 | 0.00 | 0.35 |
Annual Sum or Average | 0.134946E+10 | 43648353.24 | 9810.72 | 85962838.23 | 6375905.90 | 0.681138E+10 | 0.426212E+10 | 300.13 | 0.35 |
Minimum of Months | 50327023.97 | 0.00 | 0.00 | 560003.97 | 0.00 | 63393.75 | 55967414.85 | 0.00 | 0.35 |
Maximum of Months | 0.187459E+09 | 22410955.83 | 9599.36 | 17221702.27 | 3830736.55 | 0.128052E+10 | 0.815095E+09 | 155.82 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225828E+09 | 0.00 | 0.00 | 5157132.83 | 0.00 | 0.00 | 0.995556E+09 | 0.00 | 0.02 |
February | 0.282963E+09 | 0.00 | 0.00 | 3205992.57 | 0.00 | 0.00 | 0.745175E+09 | 0.00 | 0.02 |
March | 0.383547E+09 | 0.00 | 0.00 | 3223131.08 | 0.00 | 0.00 | 0.654937E+09 | 0.00 | 0.02 |
April | 0.574933E+09 | 0.00 | 0.00 | 1086648.01 | 0.00 | 0.00 | 0.424966E+09 | 0.00 | 0.02 |
May | 0.124192E+09 | 0.00 | 0.00 | 2515078.75 | 0.00 | 0.00 | 0.765713E+09 | 0.00 | 0.02 |
June | 0.00 | 5082828.98 | 0.00 | 3610668.28 | 0.00 | 0.00 | 0.208619E+09 | 0.00 | 0.02 |
July | 0.00 | 38973408.72 | 0.00 | 3324494.61 | 0.00 | 0.00 | 0.122551E+09 | 0.00 | 0.02 |
August | 0.00 | 38355537.69 | 0.00 | 4242992.13 | 0.00 | 0.00 | 0.246116E+09 | 0.00 | 0.02 |
September | 23510259.31 | 1456653.68 | 0.00 | 6060262.23 | 0.00 | 0.00 | 0.428275E+09 | 0.00 | 0.02 |
October | 0.291637E+09 | 0.00 | 0.00 | 5470825.27 | 0.00 | 0.00 | 0.830859E+09 | 0.00 | 0.02 |
November | 0.238226E+09 | 0.00 | 0.00 | 4017922.11 | 0.00 | 0.00 | 0.902097E+09 | 0.00 | 0.02 |
December | 0.399358E+09 | 0.00 | 0.00 | 3180300.01 | 0.00 | 0.00 | 0.720110E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.254419E+10 | 83868429.06 | 0.00 | 45095447.90 | 0.00 | 0.00 | 0.704497E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1086648.01 | 0.00 | 0.00 | 0.122551E+09 | 0.00 | 0.02 |
Maximum of Months | 0.574933E+09 | 38973408.72 | 0.00 | 6060262.23 | 0.00 | 0.00 | 0.995556E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.943960E+09 | 0.00 | 0.00 | 8813500.85 | 0.00 | 0.110505E+11 | 0.595777E+10 | 0.00 | 0.40 |
February | 0.913771E+09 | 0.00 | 0.00 | 7909981.12 | 0.00 | 0.108887E+11 | 0.450251E+10 | 0.00 | 0.40 |
March | 0.142680E+10 | 0.00 | 0.00 | 31447223.69 | 0.00 | 0.637304E+10 | 0.944088E+10 | 0.00 | 0.40 |
April | 0.151101E+10 | 0.00 | 0.00 | 42693995.37 | 0.00 | 0.350996E+10 | 0.112636E+11 | 0.00 | 0.40 |
May | 0.269356E+10 | 0.00 | 0.00 | 0.126812E+09 | 0.00 | 12321250.59 | 0.124108E+11 | 0.00 | 0.40 |
June | 0.193310E+10 | 90011578.78 | 0.00 | 0.181569E+09 | 8580387.84 | 0.00 | 0.606328E+10 | 0.00 | 0.40 |
July | 0.190831E+10 | 0.175157E+09 | 0.00 | 0.160075E+09 | 63146763.61 | 0.00 | 0.453399E+10 | 0.00 | 0.40 |
August | 0.227106E+10 | 0.304045E+09 | 0.00 | 0.154469E+09 | 24418148.78 | 0.00 | 0.530103E+10 | 0.00 | 0.40 |
September | 0.268471E+10 | 10999840.74 | 394535.20 | 0.133143E+09 | 1923479.29 | 8924718.88 | 0.868227E+10 | 8962.41 | 0.40 |
October | 0.177257E+10 | 0.00 | 0.00 | 45851464.87 | 0.00 | 0.322505E+10 | 0.118294E+11 | 0.00 | 0.40 |
November | 0.108306E+10 | 0.00 | 0.00 | 15315551.75 | 0.00 | 0.836483E+10 | 0.738829E+10 | 0.00 | 0.40 |
December | 0.827069E+09 | 0.00 | 0.00 | 6546985.48 | 0.00 | 0.132623E+11 | 0.472303E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.199690E+11 | 0.580214E+09 | 394535.20 | 0.914647E+09 | 98068779.52 | 0.566956E+11 | 0.920968E+11 | 8962.41 | 0.40 |
Minimum of Months | 0.827069E+09 | 0.00 | 0.00 | 6546985.48 | 0.00 | 0.00 | 0.450251E+10 | 0.00 | 0.40 |
Maximum of Months | 0.269356E+10 | 0.304045E+09 | 394535.20 | 0.181569E+09 | 63146763.61 | 0.132623E+11 | 0.124108E+11 | 8962.41 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31530580.40 | 0.00 | 0.00 | 3968993.15 | 0.00 | 0.938494E+09 | 0.350294E+09 | 0.00 | 0.36 |
February | 23351773.88 | 0.00 | 0.00 | 4355851.12 | 0.00 | 0.823482E+09 | 0.351578E+09 | 0.00 | 0.36 |
March | 24306412.06 | 0.00 | 0.00 | 7847858.47 | 0.00 | 0.695981E+09 | 0.545359E+09 | 0.00 | 0.36 |
April | 36760679.79 | 0.00 | 0.00 | 6342706.35 | 0.00 | 0.645222E+09 | 0.515503E+09 | 0.00 | 0.36 |
May | 9667847.01 | 0.00 | 0.00 | 14375530.08 | 0.00 | 0.105863E+09 | 0.994010E+09 | 0.00 | 0.35 |
June | 0.00 | 7269287.16 | 0.00 | 24188058.65 | 0.00 | 34251.40 | 0.578746E+09 | 0.00 | 0.35 |
July | 0.00 | 17570388.88 | 0.00 | 21009132.90 | 0.00 | 32294.83 | 0.465758E+09 | 0.00 | 0.35 |
August | 0.00 | 24217956.92 | 0.00 | 25029374.32 | 0.00 | 72734.09 | 0.544585E+09 | 0.00 | 0.35 |
September | 2683939.85 | 982599.98 | 0.00 | 20862363.79 | 0.00 | 41492991.30 | 0.783534E+09 | 0.00 | 0.35 |
October | 8645126.00 | 0.00 | 0.00 | 10032774.11 | 0.00 | 0.517611E+09 | 0.707764E+09 | 0.00 | 0.35 |
November | 23219432.55 | 0.00 | 0.00 | 5016017.62 | 0.00 | 0.753795E+09 | 0.460447E+09 | 0.00 | 0.36 |
December | 32004631.95 | 0.00 | 0.00 | 2536226.42 | 0.00 | 0.110466E+10 | 0.248336E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.192170E+09 | 50040232.93 | 0.00 | 0.145565E+09 | 0.00 | 0.562674E+10 | 0.654592E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2536226.42 | 0.00 | 32294.83 | 0.248336E+09 | 0.00 | 0.35 |
Maximum of Months | 36760679.79 | 24217956.92 | 0.00 | 25029374.32 | 0.00 | 0.110466E+10 | 0.994010E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63821154.34 | 0.00 | 0.00 | 959149.81 | 0.00 | 0.112861E+10 | 0.130747E+09 | 0.00 | 0.36 |
February | 49718808.25 | 0.00 | 0.00 | 1633550.10 | 0.00 | 0.974865E+09 | 0.176410E+09 | 0.00 | 0.35 |
March | 83077775.34 | 0.00 | 0.00 | 4200827.57 | 0.00 | 0.789840E+09 | 0.396226E+09 | 0.00 | 0.36 |
April | 91534428.00 | 0.00 | 0.00 | 4458785.21 | 0.00 | 0.710901E+09 | 0.396793E+09 | 0.00 | 0.36 |
May | 0.162482E+09 | 0.00 | 0.00 | 11113048.48 | 0.00 | 0.108585E+09 | 0.841605E+09 | 0.00 | 0.35 |
June | 0.134247E+09 | 6663488.86 | 0.00 | 19130811.49 | 604946.59 | 0.00 | 0.449520E+09 | 0.00 | 0.35 |
July | 0.136147E+09 | 13737593.70 | 0.00 | 15693761.09 | 3830736.55 | 0.00 | 0.334901E+09 | 0.00 | 0.35 |
August | 0.150892E+09 | 22420711.01 | 0.00 | 18506968.08 | 1794408.42 | 56288.17 | 0.400164E+09 | 0.00 | 0.35 |
September | 0.181352E+09 | 840681.36 | 0.00 | 14112100.95 | 141803.49 | 49715186.41 | 0.603295E+09 | 0.00 | 0.35 |
October | 0.108191E+09 | 0.00 | 0.00 | 5063035.06 | 0.00 | 0.644439E+09 | 0.486214E+09 | 0.00 | 0.35 |
November | 69962068.31 | 0.00 | 0.00 | 1668332.56 | 0.00 | 0.969950E+09 | 0.200752E+09 | 0.00 | 0.36 |
December | 48296712.25 | 0.00 | 0.00 | 566207.72 | 0.00 | 0.125663E+10 | 81877412.92 | 0.00 | 0.35 |
Annual Sum or Average | 0.127972E+10 | 43662474.94 | 0.00 | 97106578.11 | 6371895.05 | 0.663359E+10 | 0.449851E+10 | 0.00 | 0.35 |
Minimum of Months | 48296712.25 | 0.00 | 0.00 | 566207.72 | 0.00 | 0.00 | 81877412.92 | 0.00 | 0.35 |
Maximum of Months | 0.181352E+09 | 22420711.01 | 0.00 | 19130811.49 | 3830736.55 | 0.125663E+10 | 0.841605E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929326E+09 | 0.00 | 0.00 | 0.63 |
February | 0.246775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255907E+10 | 0.00 | 0.00 | 0.62 |
March | 0.290465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117836E+09 | 0.00 | 0.00 | 0.63 |
April | 0.277774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296082E+09 | 0.00 | 0.00 | 0.63 |
May | 0.259529E+11 | 0.00 | 0.00 | 0.00 | 2089733.01 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 0.609033E+10 | 0.293178E+09 | 0.00 | 15904675.97 | 17233811.33 | 0.00 | 0.648170E+10 | 0.00 | 0.63 |
July | 0.350083E+10 | 0.300341E+09 | 0.00 | 21250043.69 | 0.107094E+09 | 0.00 | 0.776072E+10 | 0.00 | 0.63 |
August | 0.570574E+10 | 0.242180E+09 | 0.00 | 17874577.98 | 6742018.26 | 0.00 | 0.749838E+10 | 0.00 | 0.64 |
September | 0.114145E+11 | 50734486.06 | 0.00 | 12374489.85 | 3818679.15 | 0.00 | 0.610023E+10 | 0.00 | 0.63 |
October | 0.271972E+11 | 0.00 | 0.00 | 4290.74 | 0.00 | 0.102988E+10 | 6624490.14 | 0.00 | 0.62 |
November | 0.269747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876844E+09 | 0.00 | 0.00 | 0.62 |
December | 0.256843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522644E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.242914E+12 | 0.886433E+09 | 0.00 | 67408078.22 | 0.136978E+09 | 0.110355E+11 | 0.278477E+11 | 0.00 | 0.63 |
Minimum of Months | 0.350083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.290465E+11 | 0.300341E+09 | 0.00 | 21250043.69 | 0.107094E+09 | 0.522644E+10 | 0.776072E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7758416.36 | 0.00 | 0.00 | 831051.34 | 0.00 | 0.260743E+09 | 61739216.11 | 0.00 | 0.36 |
February | 5285829.20 | 0.00 | 0.00 | 832062.25 | 0.00 | 0.232244E+09 | 62330389.15 | 0.00 | 0.36 |
March | 6241988.23 | 0.00 | 0.00 | 1980754.78 | 0.00 | 0.203752E+09 | 0.106399E+09 | 0.00 | 0.36 |
April | 8900989.21 | 0.00 | 0.00 | 1423916.58 | 0.00 | 0.195026E+09 | 95606568.86 | 0.00 | 0.36 |
May | 4683722.21 | 0.00 | 0.00 | 3269051.59 | 0.00 | 64462867.55 | 0.208563E+09 | 0.00 | 0.35 |
June | 0.00 | 1817321.79 | 0.00 | 5004902.68 | 0.00 | 386598.11 | 0.145351E+09 | 0.00 | 0.35 |
July | 0.00 | 4392492.88 | 0.00 | 4336624.07 | 0.00 | 111979.88 | 0.117251E+09 | 104.34 | 0.35 |
August | 0.00 | 6054489.23 | 0.00 | 5093832.66 | 0.00 | 691941.79 | 0.136636E+09 | 0.00 | 0.35 |
September | 1127918.01 | 245649.99 | 0.00 | 4557432.93 | 0.00 | 19010012.42 | 0.187448E+09 | 0.00 | 0.35 |
October | 2868814.75 | 0.00 | 0.00 | 2552962.94 | 0.00 | 0.167052E+09 | 0.138539E+09 | 0.00 | 0.35 |
November | 3789091.97 | 0.00 | 0.00 | 1064218.09 | 0.00 | 0.221245E+09 | 84521534.36 | 0.00 | 0.36 |
December | 6188593.70 | 0.00 | 0.00 | 472271.97 | 0.00 | 0.296035E+09 | 44188425.87 | 0.00 | 0.35 |
Annual Sum or Average | 46845363.65 | 12509953.89 | 0.00 | 31419081.88 | 0.00 | 0.166076E+10 | 0.138857E+10 | 104.34 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 472271.97 | 0.00 | 111979.88 | 44188425.87 | 0.00 | 0.35 |
Maximum of Months | 8900989.21 | 6054489.23 | 0.00 | 5093832.66 | 0.00 | 0.296035E+09 | 0.208563E+09 | 104.34 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14923115.31 | 0.00 | 0.00 | 215896.43 | 0.00 | 0.301834E+09 | 14059558.17 | 0.00 | 0.36 |
February | 12115642.88 | 0.00 | 0.00 | 288799.43 | 0.00 | 0.268544E+09 | 19707835.39 | 0.00 | 0.35 |
March | 20838778.21 | 0.00 | 0.00 | 962915.96 | 0.00 | 0.225429E+09 | 71105702.03 | 0.00 | 0.36 |
April | 23347662.57 | 0.00 | 0.00 | 908645.83 | 0.00 | 0.203856E+09 | 72809097.69 | 0.00 | 0.36 |
May | 43293094.19 | 0.00 | 0.00 | 2325747.21 | 0.00 | 57967306.77 | 0.177360E+09 | 0.00 | 0.35 |
June | 35008843.30 | 1664869.50 | 0.00 | 4316549.53 | 152239.36 | 74162.49 | 0.111325E+09 | 0.00 | 0.35 |
July | 34767542.18 | 3434338.24 | 0.00 | 3502931.93 | 957684.14 | 51073.70 | 83364073.20 | 60.18 | 0.35 |
August | 39390663.92 | 5605177.75 | 0.00 | 3872354.91 | 448602.11 | 319601.73 | 98822355.65 | 0.00 | 0.35 |
September | 46736521.52 | 210077.09 | 0.00 | 2951124.17 | 35450.87 | 18717193.39 | 0.143714E+09 | 93.25 | 0.35 |
October | 28390065.18 | 0.00 | 0.00 | 1084750.13 | 0.00 | 0.197988E+09 | 83513876.17 | 0.00 | 0.35 |
November | 15545602.59 | 0.00 | 0.00 | 325398.41 | 0.00 | 0.268207E+09 | 26505262.64 | 0.00 | 0.36 |
December | 10926143.32 | 0.00 | 0.00 | 124593.71 | 0.00 | 0.329594E+09 | 6199081.36 | 0.00 | 0.35 |
Annual Sum or Average | 0.325284E+09 | 10914462.59 | 0.00 | 20879707.66 | 1593976.47 | 0.187258E+10 | 0.908486E+09 | 153.44 | 0.35 |
Minimum of Months | 10926143.32 | 0.00 | 0.00 | 124593.71 | 0.00 | 51073.70 | 6199081.36 | 0.00 | 0.35 |
Maximum of Months | 46736521.52 | 5605177.75 | 0.00 | 4316549.53 | 957684.14 | 0.329594E+09 | 0.177360E+09 | 93.25 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9059443.66 | 0.00 | 0.00 | 15520451.30 | 0.00 | 0.971801E+09 | 0.113059E+10 | 0.00 | 0.40 |
February | 5712234.01 | 0.00 | 0.00 | 12046337.29 | 0.00 | 0.102359E+10 | 0.890441E+09 | 0.00 | 0.40 |
March | 18305681.72 | 0.00 | 0.00 | 15212164.80 | 0.00 | 0.933340E+09 | 0.107853E+10 | 0.00 | 0.40 |
April | 46422823.55 | 0.00 | 0.00 | 8624806.25 | 0.00 | 0.940624E+09 | 0.937824E+09 | 0.00 | 0.40 |
May | 12099318.88 | 0.00 | 0.00 | 17028954.46 | 0.00 | 0.194692E+09 | 0.158133E+10 | 0.00 | 0.40 |
June | 0.00 | 11675364.47 | 0.00 | 23869150.00 | 0.00 | 2687425.47 | 0.941885E+09 | 0.00 | 0.40 |
July | 0.00 | 28220194.02 | 0.00 | 22852644.54 | 0.00 | 482357.69 | 0.758525E+09 | 0.00 | 0.40 |
August | 0.00 | 38897001.53 | 0.00 | 27592291.79 | 0.00 | 913146.52 | 0.886481E+09 | 0.00 | 0.40 |
September | 2241257.79 | 1578175.77 | 0.00 | 29653647.52 | 0.00 | 54492442.99 | 0.127653E+10 | 0.00 | 0.40 |
October | 13030195.67 | 0.00 | 0.00 | 22370735.37 | 0.00 | 0.615704E+09 | 0.134700E+10 | 0.00 | 0.40 |
November | 15663130.43 | 0.00 | 0.00 | 17155590.20 | 0.00 | 0.770004E+09 | 0.119275E+10 | 0.00 | 0.40 |
December | 32199995.05 | 0.00 | 0.00 | 10312863.54 | 0.00 | 0.133426E+10 | 0.851784E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.154734E+09 | 80370735.79 | 0.00 | 0.222240E+09 | 0.00 | 0.684259E+10 | 0.128737E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8624806.25 | 0.00 | 482357.69 | 0.758525E+09 | 0.00 | 0.40 |
Maximum of Months | 46422823.55 | 38897001.53 | 0.00 | 29653647.52 | 0.00 | 0.133426E+10 | 0.158133E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176648E+10 | 0.00 | 0.00 | 56127223.02 | 0.00 | 0.00 | 0.482721E+11 | 0.00 | 4.99 |
February | 0.179307E+10 | 0.00 | 0.00 | 49482877.42 | 0.00 | 0.00 | 0.436955E+11 | 0.00 | 4.94 |
March | 0.634406E+09 | 0.00 | 0.00 | 68215892.39 | 0.00 | 0.00 | 0.518282E+11 | 0.00 | 5.29 |
April | 0.235604E+09 | 0.00 | 0.00 | 68064917.10 | 0.00 | 0.00 | 0.514081E+11 | 0.00 | 5.38 |
May | 2928376.42 | 4061685.03 | 0.00 | 95305912.65 | 0.00 | 0.00 | 0.541711E+11 | 0.00 | 5.99 |
June | 0.00 | 0.576065E+09 | 0.00 | 0.105759E+09 | 0.00 | 0.00 | 0.294957E+11 | 0.00 | 6.44 |
July | 0.00 | 0.747531E+09 | 0.00 | 0.101543E+09 | 0.00 | 0.00 | 0.263472E+11 | 0.00 | 6.39 |
August | 0.00 | 0.457705E+09 | 0.00 | 0.107568E+09 | 0.00 | 0.00 | 0.300697E+11 | 0.00 | 6.43 |
September | 3642004.00 | 94174498.59 | 0.00 | 99645948.82 | 0.00 | 0.00 | 0.384349E+11 | 0.00 | 6.20 |
October | 0.101338E+10 | 0.00 | 0.00 | 74556906.24 | 0.00 | 0.00 | 0.513242E+11 | 0.00 | 5.42 |
November | 0.138991E+10 | 0.00 | 0.00 | 59052650.71 | 0.00 | 0.00 | 0.467186E+11 | 0.00 | 5.11 |
December | 0.465540E+10 | 0.00 | 0.00 | 50078343.40 | 0.00 | 0.00 | 0.458321E+11 | 0.00 | 4.85 |
Annual Sum or Average | 0.114948E+11 | 0.187954E+10 | 0.00 | 0.935401E+09 | 0.00 | 0.00 | 0.517597E+12 | 0.00 | 5.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 49482877.42 | 0.00 | 0.00 | 0.263472E+11 | 0.00 | 4.85 |
Maximum of Months | 0.465540E+10 | 0.747531E+09 | 0.00 | 0.107568E+09 | 0.00 | 0.00 | 0.541711E+11 | 0.00 | 6.44 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.530110E+09 | 0.00 | 0.00 | 70642069.27 | 0.00 | 0.00 | 0.547427E+11 | 0.00 | 5.51 |
February | 0.340190E+09 | 0.00 | 0.00 | 62321987.79 | 0.00 | 0.00 | 0.498713E+11 | 0.00 | 5.46 |
March | 79949754.70 | 0.00 | 0.00 | 81551740.58 | 0.00 | 0.00 | 0.576674E+11 | 0.00 | 5.82 |
April | 49696717.90 | 0.00 | 0.00 | 80443215.12 | 0.00 | 0.00 | 0.570015E+11 | 0.00 | 5.95 |
May | 0.00 | 4428251.75 | 0.00 | 0.104817E+09 | 0.00 | 0.00 | 0.588365E+11 | 0.00 | 6.53 |
June | 0.00 | 0.619006E+09 | 0.00 | 0.112929E+09 | 0.00 | 0.00 | 0.312182E+11 | 0.00 | 6.86 |
July | 0.00 | 0.805952E+09 | 0.00 | 0.108259E+09 | 0.00 | 0.00 | 0.278393E+11 | 0.00 | 6.80 |
August | 0.00 | 0.491232E+09 | 0.00 | 0.115039E+09 | 0.00 | 0.00 | 0.318758E+11 | 0.00 | 6.85 |
September | 0.00 | 0.101469E+09 | 0.00 | 0.107508E+09 | 0.00 | 0.00 | 0.410936E+11 | 0.00 | 6.64 |
October | 0.147029E+09 | 0.00 | 0.00 | 86121700.01 | 0.00 | 0.00 | 0.570189E+11 | 0.00 | 5.93 |
November | 0.294135E+09 | 0.00 | 0.00 | 71795423.96 | 0.00 | 0.00 | 0.527817E+11 | 0.00 | 5.64 |
December | 0.259371E+10 | 0.00 | 0.00 | 64172539.64 | 0.00 | 0.00 | 0.530037E+11 | 0.00 | 5.35 |
Annual Sum or Average | 0.403482E+10 | 0.202209E+10 | 0.00 | 0.106560E+10 | 0.00 | 0.00 | 0.572951E+12 | 0.00 | 6.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 62321987.79 | 0.00 | 0.00 | 0.278393E+11 | 0.00 | 5.35 |
Maximum of Months | 0.259371E+10 | 0.805952E+09 | 0.00 | 0.115039E+09 | 0.00 | 0.00 | 0.588365E+11 | 0.00 | 6.86 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.119679E+09 | 0.00 | 0.00 | 0.800943E+11 | 0.00 | 25.64 |
February | 0.00 | 0.00 | 0.00 | 0.107441E+09 | 0.00 | 0.00 | 0.731585E+11 | 0.00 | 25.52 |
March | 0.00 | 0.00 | 0.00 | 0.126570E+09 | 0.00 | 0.00 | 0.784575E+11 | 0.00 | 26.06 |
April | 0.00 | 0.00 | 0.00 | 0.119483E+09 | 0.00 | 0.00 | 0.752705E+11 | 0.00 | 26.19 |
May | 0.00 | 7139138.45 | 0.00 | 0.145076E+09 | 0.00 | 0.00 | 0.685154E+11 | 0.00 | 27.08 |
June | 0.00 | 0.984876E+09 | 0.00 | 0.145846E+09 | 0.00 | 0.00 | 0.305244E+11 | 0.00 | 27.04 |
July | 0.00 | 0.132082E+10 | 0.00 | 0.137796E+09 | 0.00 | 0.00 | 0.266193E+11 | 0.00 | 26.76 |
August | 0.00 | 0.777378E+09 | 0.00 | 0.153763E+09 | 0.00 | 0.00 | 0.330602E+11 | 0.00 | 27.40 |
September | 0.00 | 0.168250E+09 | 0.00 | 0.147809E+09 | 0.00 | 0.00 | 0.444304E+11 | 0.00 | 27.20 |
October | 0.00 | 0.00 | 0.00 | 0.131336E+09 | 0.00 | 0.00 | 0.759608E+11 | 0.00 | 26.01 |
November | 0.00 | 0.00 | 0.00 | 0.117367E+09 | 0.00 | 0.00 | 0.747539E+11 | 0.00 | 25.71 |
December | 3189768.90 | 0.00 | 0.00 | 0.116832E+09 | 0.00 | 0.00 | 0.808540E+11 | 0.00 | 24.96 |
Annual Sum or Average | 3189768.90 | 0.325846E+10 | 0.00 | 0.156900E+10 | 0.00 | 0.00 | 0.741699E+12 | 0.00 | 26.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107441E+09 | 0.00 | 0.00 | 0.266193E+11 | 0.00 | 24.96 |
Maximum of Months | 3189768.90 | 0.132082E+10 | 0.00 | 0.153763E+09 | 0.00 | 0.00 | 0.808540E+11 | 0.00 | 27.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188573E+10 | 0.00 | 0.00 | 1.23 |
February | 0.113915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280724E+10 | 0.00 | 0.00 | 1.23 |
March | 0.141717E+11 | 0.00 | 0.00 | 624388.84 | 0.00 | 0.762925E+09 | 0.273355E+09 | 0.00 | 1.23 |
April | 0.141360E+11 | 0.00 | 0.00 | 1612.88 | 0.00 | 0.483638E+09 | 15340967.56 | 0.00 | 1.23 |
May | 0.132416E+11 | 1089399.38 | 0.00 | 562753.64 | 0.00 | 0.00 | 0.287859E+09 | 0.00 | 1.23 |
June | 0.329091E+10 | 0.219864E+09 | 0.00 | 12715887.64 | 237749.42 | 0.00 | 0.319684E+10 | 0.00 | 1.31 |
July | 0.254254E+10 | 0.264076E+09 | 0.00 | 12577896.69 | 3604327.36 | 0.00 | 0.322938E+10 | 0.00 | 1.31 |
August | 0.354583E+10 | 0.177544E+09 | 0.00 | 13241133.32 | 0.00 | 0.00 | 0.329782E+10 | 0.00 | 1.34 |
September | 0.658295E+10 | 37470254.08 | 0.00 | 8477732.74 | 0.00 | 0.00 | 0.250637E+10 | 0.00 | 1.28 |
October | 0.131202E+11 | 0.00 | 0.00 | 896371.98 | 0.00 | 0.109967E+10 | 0.500231E+09 | 0.00 | 1.23 |
November | 0.132561E+11 | 0.00 | 0.00 | 15410.52 | 0.00 | 0.121506E+10 | 48095939.03 | 0.00 | 1.23 |
December | 0.119370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417386E+10 | 0.00 | 0.00 | 1.22 |
Annual Sum or Average | 0.120877E+12 | 0.700044E+09 | 0.00 | 49113188.26 | 3842076.78 | 0.124281E+11 | 0.133553E+11 | 0.00 | 1.26 |
Minimum of Months | 0.254254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
Maximum of Months | 0.141717E+11 | 0.264076E+09 | 0.00 | 13241133.32 | 3604327.36 | 0.417386E+10 | 0.329782E+10 | 0.00 | 1.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:45:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.230276E+12 | 0.177465E+11 | 0.223089E+12 | 0.103068E+13 | 0.138489E+12 |
February | 0.315418E+12 | 0.168049E+11 | 0.209545E+12 | 0.960533E+12 | 0.121110E+12 |
March | 0.421159E+12 | 0.147362E+11 | 0.185032E+12 | 0.864103E+12 | 0.153368E+12 |
April | 0.472296E+12 | 0.133407E+11 | 0.167763E+12 | 0.780278E+12 | 0.128583E+12 |
May | 0.531246E+12 | 0.864015E+10 | 0.988774E+11 | 0.518666E+12 | 0.276259E+12 |
June | 0.575764E+12 | 0.344981E+10 | 0.327514E+11 | 0.220326E+12 | 0.630593E+12 |
July | 0.549919E+12 | 0.295618E+10 | 0.276604E+11 | 0.189467E+12 | 0.699285E+12 |
August | 0.512299E+12 | 0.371340E+10 | 0.386639E+11 | 0.236506E+12 | 0.646676E+12 |
September | 0.384204E+12 | 0.570068E+10 | 0.612679E+11 | 0.356244E+12 | 0.486857E+12 |
October | 0.315087E+12 | 0.132483E+11 | 0.163011E+12 | 0.810730E+12 | 0.194844E+12 |
November | 0.248595E+12 | 0.156146E+11 | 0.196678E+12 | 0.941364E+12 | 0.137638E+12 |
December | 0.198026E+12 | 0.190750E+11 | 0.238149E+12 | 0.108910E+13 | 0.133116E+12 |
Annual Sum or Average | 0.475429E+13 | 0.135026E+12 | 0.164249E+13 | 0.799799E+13 | 0.374682E+13 |
Minimum of Months | 0.198026E+12 | 0.295618E+10 | 0.276604E+11 | 0.189467E+12 | 0.121110E+12 |
Maximum of Months | 0.575764E+12 | 0.190750E+11 | 0.238149E+12 | 0.108910E+13 | 0.699285E+12 |