Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:45:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11058.04 | 974.68 | 974.68 |
Net Site Energy | 11058.04 | 974.68 | 974.68 |
Total Source Energy | 23732.81 | 2091.87 | 2091.87 |
Net Source Energy | 23732.81 | 2091.87 | 2091.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 786.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1392.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 599.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 83.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 133.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2844.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5638.93 | 5419.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 786.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1392.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 599.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 83.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 133.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2844.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 786.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1392.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 599.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 83.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 133.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2844.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 191.01 | 319.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 219.89 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 497.03 | 477.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 191.01 | 319.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 219.89 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 497.03 | 477.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5638.934 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5638.934 | 100.00 |
Total On-Site and Utility Electric Sources | 5638.934 | 100.00 |
Total Electricity End Uses | 5638.934 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 243.48 | 23.98 |
Air to Air Heat Recovery for Heating | 772.03 | 76.02 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1015.50 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 522.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7790.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-JUL-19:10 | 01-FEB-18:49 | - | - | - | - | - | - | - | - | - | - | 07-FEB-21:49 |
Heating | 0.00 | 194233.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150311.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31546.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40536.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3688.60 | 247062.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1871.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 404811.92 | 545543.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 194233.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 150311.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1242.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 40536.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3688.60 | 247062.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 852.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4411.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1898.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 265.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 424.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3083.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17858.50 | 5874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 388.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 37.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1574.09 | 517.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 388.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 37.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1574.09 | 517.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.89 | 0.522197 | 0.466000 | 1.35 | 1.00 | 0.500000 | 0.000730 | 0.000054 | 1.35 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.363162 | 0.140732 | 0.466000 | 0.169233 | 0.466000 | 0.500000 | 0.002707 | 0.000030 | 0.169233 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.268032 | 0.220808 | 0.466000 | 0.124903 | 0.588822 | 0.500000 | 0.001725 | 0.000012 | 0.124903 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.236750 | 0.528630 | 0.466000 | 0.110326 | 1.00 | 0.500000 | 0.000721 | 0.000018 | 0.110326 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.140431 | 0.514180 | 0.466000 | 0.065441 | 1.00 | 0.500000 | 0.000741 | 0.000011 | 0.065441 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.76 | 0.015796 | 0.466000 | 1.75 | 0.466000 | 0.500000 | 0.024120 | 0.000088 | 1.75 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.57 | 0.091470 | 0.466000 | 0.733170 | 0.466000 | 0.500000 | 0.004165 | 0.000087 | 0.733170 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.42 | 0.183966 | 0.466000 | 2.53 | 0.490575 | 0.500000 | 0.002071 | 0.000232 | 2.53 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.74 | 0.682260 | 0.466000 | 0.810685 | 1.00 | 0.500000 | 0.000558 | 0.000112 | 0.810685 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.53 | 0.099919 | 0.466000 | 1.18 | 0.466000 | 0.500000 | 0.003813 | 0.000099 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.65 | 0.095414 | 0.466000 | 1.23 | 0.466000 | 0.500000 | 0.003993 | 0.000102 | 1.23 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.58 | 0.054879 | 0.466000 | 1.20 | 0.466000 | 0.500000 | 0.012487 | 0.000064 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.886029 | 0.354434 | 0.466000 | 0.412890 | 0.945158 | 0.500000 | 0.001075 | 0.000072 | 0.412890 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6161.68 | 0.000054 | 128.49 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3380.82 | 0.000030 | 85.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1399.33 | 0.000012 | 31.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2048.01 | 0.000018 | 50.92 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1277.97 | 0.000011 | 32.21 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10095.54 | 0.000088 | 213.37 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9909.40 | 0.000087 | 230.19 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26556.54 | 0.000232 | 593.97 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5784.93 | 0.000051 | 165.31 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5778.77 | 0.000051 | 165.13 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33357.80 | 0.000292 | 953.21 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33258.71 | 0.000291 | 950.38 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5773.28 | 0.000051 | 164.98 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5767.12 | 0.000050 | 164.80 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12798.32 | 0.000112 | 306.31 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1777.96 | 0.000016 | 50.80 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1777.21 | 0.000016 | 50.78 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8570.91 | 0.000075 | 244.91 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11327.11 | 0.000099 | 250.55 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11705.83 | 0.000102 | 258.53 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7360.85 | 0.000064 | 156.23 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8181.41 | 0.000072 | 207.09 |
VAV WITH REHEAT HEATING COIL | 171732.54 | 0.001502 | 2915.34 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.19 | 0.000051 | 0.000329 |
ROOM_2_FLR_3 FAN COIL | 1.18 | 0.000051 | 0.000327 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.04 | 0.000292 | 0.001926 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.63 | 0.000291 | 0.002195 |
ROOM_5_FLR_3 FAN COIL | 1.05 | 0.000051 | 0.000290 |
ROOM_6_FLR_3 FAN COIL | 1.04 | 0.000050 | 0.000288 |
ROOM_1_FLR_6 FAN COIL | 0.315419 | 0.000016 | 0.000087 |
ROOM_2_FLR_6 FAN COIL | 0.312975 | 0.000016 | 0.000087 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.41 | 0.000075 | 0.000397 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.19 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.18 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.04 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.63 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.04 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.315419 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.312975 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.41 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000329 | 1.19 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000327 | 1.18 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008474 | 12.80 | 0.008474 | 0.001926 | 7.04 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008686 | 12.80 | 0.008500 | 0.002195 | 7.63 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008547 | 12.80 | 0.008500 | 0.000290 | 1.05 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008547 | 12.80 | 0.008500 | 0.000288 | 1.04 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008540 | 12.80 | 0.008500 | 0.000087 | 0.315419 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008540 | 12.80 | 0.008500 | 0.000087 | 0.312975 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000397 | 1.41 | |
VAV WITH REHEAT COOLING COIL | 30.60 | 6.70 | 0.008341 | 10.70 | 0.008341 | 0.015104 | 24.91 | 528127.03 |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.001640 | 2.05 | 57348.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.52 | 11.67 | 25.04 | 11.67 | 24.91 | 24.91 | 0.300000 | 0.468390 | 24.91 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.91 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.91 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.015104 | 0.000032 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001502 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001640 | 0.000290 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.022669 | 3701.16 | |
HEATSYS1 PUMP | 0.003499 | 1053.66 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003499 | 0.419846 |
COOLSYS1 | 0.022669 | 2.72 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 399925.06 | 399925.06 | 0.003499 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.022669 | 2562.44 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.022669 | 792626.21 | 793296.81 | 90.44 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.3945E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1877E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1040 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5473E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1944E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6614E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1062 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1341E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1179 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.5711E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9683E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3635E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3060E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3169E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7765E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9456E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6976E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.7808E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3060E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3169E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7765E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9456E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6976E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.7808E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34466.48362 | 34466.48362 | 2.88755 | 2.88755 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 30.82000 | 6.85992E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4334.44500 | 4334.44500 | 0.36316 | 0.36316 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2606.53738 | 2606.53738 | 0.12882 | 0.12882 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3198.94274 | 3198.94274 | 0.26803 | 0.26803 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63000 | 6.86752E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 827.89785 | 827.89785 | 4.09166E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2826.25390 | 2826.25390 | 0.23675 | 0.23675 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 33.68000 | 6.86443E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1543.37718 | 1543.37718 | 7.62771E-002 | 7.62771E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1676.40342 | 1676.40342 | 0.14043 | 0.14043 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 35.84667 | 6.86787E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 978.61282 | 978.61282 | 4.83652E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44936.16811 | 44936.16811 | 3.76456 | 3.76456 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2072.20029 | 2072.20029 | 0.10241 | 0.10241 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18761.31866 | 18761.31866 | 1.57333 | 1.57333 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6554.60374 | 6554.60374 | 0.32394 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64651.47085 | 64651.47085 | 5.41861 | 5.41861 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15003.49674 | 15003.49674 | 0.74151 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10530.26067 | 10530.26067 | 1.18874 | 1.18874 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5785.05496 | 5785.05496 | 0.28758 | 0.28758 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10459.45936 | 10459.45936 | 1.18075 | 1.18075 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5778.89509 | 5778.89509 | 0.28727 | 0.28727 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 62389.55917 | 62389.55917 | 7.04276 | 7.04276 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33358.13548 | 33358.13548 | 1.65831 | 1.65831 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 67610.25015 | 67610.25015 | 7.63271 | 7.63271 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33259.04654 | 33259.04654 | 1.65338 | 1.65338 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9267.78885 | 9267.78885 | 1.04622 | 1.04622 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5773.40437 | 5773.40437 | 0.28700 | 0.28700 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9197.35534 | 9197.35534 | 1.03827 | 1.03827 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5767.24281 | 5767.24281 | 0.28669 | 0.28669 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20765.74049 | 20765.74049 | 1.73967 | 1.73967 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9088.35837 | 9088.35837 | 0.44917 | 0.47476 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2794.09131 | 2794.09131 | 0.31542 | 0.31542 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1777.99997 | 1777.99997 | 8.83860E-002 | 8.83860E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2772.43714 | 2772.43714 | 0.31297 | 0.31297 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1777.24514 | 1777.24514 | 8.83484E-002 | 8.83484E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12488.33105 | 12488.33105 | 1.40983 | 1.40983 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8571.05205 | 8571.05205 | 0.42608 | 0.42608 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30151.65525 | 30151.65525 | 2.52929 | 2.52929 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5932.68574 | 5932.68574 | 0.29321 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31575.65778 | 31575.65778 | 2.64870 | 2.64870 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6056.73493 | 6056.73493 | 0.29934 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30711.15279 | 30711.15279 | 2.57991 | 2.57991 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1873.47905 | 1873.47905 | 9.25788E-002 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10576.30727 | 10576.30727 | 0.88603 | 0.88603 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6291.54149 | 6291.54149 | 0.31094 | 0.31094 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 465147.43 | 24.90828 | 24.90828 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 170307.32 | 7.41047 | 7.41047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 20.68143 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 5.06306 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88755 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52220 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.34560 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.29610E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.39051E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.34560 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6161.68157 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.39051E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 128.49125 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36316 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14073 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16923 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70728E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.95769E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16923 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3380.82284 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.95769E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.77549 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26803 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22081 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12490 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58882 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72548E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22419E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12490 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1399.32603 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22419E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.56518 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23675 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52863 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11033 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.20731E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79169E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11033 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2048.00798 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79169E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 50.92266 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14043 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51418 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.54407E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.40986E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11802E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.54407E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1277.96510 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11802E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.21478 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.76456 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.57963E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.75429 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41196E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.83202E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.75429 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10095.54243 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.83202E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 213.36768 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57333 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.14703E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73317 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16528E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.66917E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73317 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9909.39949 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.66917E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.19274 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.41861 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18397 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52507 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49057 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07104E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32328E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52507 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26556.53719 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32328E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 593.97087 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18874 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.18874 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.06091E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.28859E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54190E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.28859E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18874 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5784.93444 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.06091E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.30851 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18075 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.18075 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.05552E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.26673E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54218E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.26673E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18075 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5778.77469 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.05552E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 165.13253 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.04276 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.04276 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.91829E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.92594E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77125 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47442E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47442E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.92594E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.04276 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33357.79509 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.91829E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 953.20854 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.63271 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.63271 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.90962E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.19489E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77032 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68596E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.19489E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.63271 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33258.70705 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.90962E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 950.37772 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04622 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04622 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.05072E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.89830E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54691E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.89830E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04622 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5773.28407 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.05072E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 164.97567 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03827 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.03827 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.04533E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.87651E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54721E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.87651E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.03827 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5767.12262 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.04533E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 164.79964 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.73967 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68226 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81068 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.58438E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11965E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81068 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12798.32257 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11965E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.30739 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31542 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31542 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55544E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.72028E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53954E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.72028E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31542 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1777.96441 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55544E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.80442 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31297 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31297 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55478E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.65334E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53981E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.65334E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31297 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1777.20959 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55478E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.78285 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.40983 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.40983 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.49821E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.96897E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77052 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60628E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.96897E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.40983 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8570.91465 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.49821E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 244.90775 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.52929 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.99186E-002 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17865 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81310E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.90945E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17865 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11327.11403 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.90945E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 250.54643 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64870 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.54141E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23429 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99312E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02408E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23429 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11705.82919 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02408E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.52577 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57991 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.48794E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20224 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24869E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.43959E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20224 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7360.84873 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.43959E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 156.23180 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88603 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35443 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41289 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94516 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07495E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.15746E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41289 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8181.41245 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15746E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 207.08663 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.51801 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66679 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.03602 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66679 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.90828 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.90828 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46839 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.90828 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.90828 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.59522 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69726 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34132E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34132E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 528127.03095 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.51044E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.90828 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 171732.54110 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50239E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2915.33717 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.90828 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.51044E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.15267E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.50239E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64017E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.64017E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.90331E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.26690E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3701.15651 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.49872E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.41985 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.49872E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1053.66048 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 399925.05992 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 399925.06000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.49872E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.26690E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.72028 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.26690E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2562.43549 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.26690E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 792626.20796 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 793296.81000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 90.43584 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6193.89 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3395.77 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1406.15 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2057.19 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1283.64 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10147.82 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9956.71 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26686.88 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6232.61 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6225.97 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 35939.06 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 35832.32 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6220.06 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6213.42 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12857.38 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1915.51 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1914.69 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9233.93 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11383.19 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11763.85 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7398.85 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8217.64 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129336.20 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 12837.19 | 10173.69 | 2663.49 | 0.79 | 1084.03 | 10.99 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 12751.73 | 10105.82 | 2645.90 | 0.79 | 1076.83 | 10.92 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 82596.83 | 66689.25 | 15907.58 | 0.81 | 8058.83 | 81.74 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 85222.33 | 67065.14 | 18157.19 | 0.79 | 7236.38 | 73.40 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 11311.57 | 8962.39 | 2349.18 | 0.79 | 955.38 | 9.69 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 11226.39 | 8894.77 | 2331.62 | 0.79 | 948.20 | 9.62 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3404.31 | 2698.29 | 706.02 | 0.79 | 287.45 | 2.92 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3378.14 | 2677.51 | 700.63 | 0.79 | 285.24 | 2.89 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 15456.25 | 12210.58 | 3245.67 | 0.79 | 1308.42 | 13.27 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 652321.10 | 408925.60 | 243395.50 | 0.63 | 136793.86 | 1387.44 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49472.21 | 31519.61 | 17952.61 | 0.64 | 5383.03 | 54.60 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.4980828133E-002 | 2.3313165965E-002 | Pass | Pass | 8.7010890394E-003 | 2.2165878530E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7360122122E-002 | 7.9956602898E-002 | Pass | Pass | 2.1068830556E-002 | 2.3288480777E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5818853126E-002 | 2.8635114799E-002 | Pass | Pass | 7.2759980800E-003 | 1.9019908603E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3020923845E-002 | 1.3873307053E-002 | Pass | Pass | 7.8743322053E-003 | 2.3168847898E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0112371240E-002 | 9.4391734926E-003 | Pass | Pass | 7.8470735057E-003 | 2.3459330511E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1761085804E-002 | 0.1672402062 | Pass | Pass | 1.9665548739E-002 | 5.3040036650E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8017166650E-002 | 7.0485906678E-002 | Pass | Pass | 1.6320343076E-002 | 2.3206051805E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1817528558E-002 | 4.1150707686E-002 | Pass | Pass | 9.4167752742E-003 | 2.0679106368E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.6854158137E-002 | 0.1939331262 | Pass | Pass | 0.1747592759 | 0.3831820553 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.9166687815E-002 | 0.1680539168 | Pass | Pass | 0.1825919254 | 0.4721046307 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0329652942E-002 | 2.2637508080E-002 | Pass | Pass | 6.7404746354E-002 | 0.1787018177 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.9997444177E-002 | 0.1208894135 | Pass | Pass | 6.2092212598 | 72.6345778651 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9977066356E-002 | 0.2100970225 | Pass | Pass | 0.1820946350 | 0.4785989022 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1620709084E-002 | 5.6538378495E-002 | Pass | Pass | 0.2216562336 | 0.8915531421 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2534691100E-002 | 1.1575311572E-002 | Pass | Pass | 7.9428234960E-003 | 2.2391246994E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.7607819810E-002 | 0.1799196201 | Pass | Pass | 0.1559221303 | 0.4231943245 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9876558561E-002 | 0.1874875648 | Pass | Pass | 0.1128095445 | 0.2872918976 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.0684283940E-002 | 0.2636375063 | Pass | Pass | 0.2829047568 | 1.1046904774 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8836918037E-002 | 5.3322522046E-002 | Pass | Pass | 1.5337893758E-002 | 4.4986391447E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1648841462E-002 | 3.8704774602E-002 | Pass | Pass | 1.4989688221E-002 | 4.2689640647E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.4935622159E-002 | 4.4100809121E-002 | Pass | Pass | 2.1235823333E-002 | 4.2958290576E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1218409063E-002 | 2.1108519062E-002 | Pass | Pass | 1.1298173411E-002 | 2.2826917005E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3229.43 | 70.63 | 860.40 | 3863.78 | 6140.19 | 14164.44 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.22 | 0.0000 | Y | 14.27 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.17 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 31.15 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 31.15 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.42 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.01 | |
Exterior Lighting Total | 12338.45 | 194.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 399925.06 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 793296.81 | 2.96 | 793436.25 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11498.82 | 12837.19 | 10173.69 | 2663.49 | 0.79 | - | 1084.03 | 10.99 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11422.39 | 12751.73 | 10105.82 | 2645.90 | 0.79 | - | 1076.83 | 10.92 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 67342.19 | 82596.83 | 66689.25 | 15907.58 | 0.81 | - | 8058.83 | 81.74 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 76746.16 | 85222.33 | 67065.14 | 18157.19 | 0.79 | - | 7236.38 | 73.40 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10134.14 | 11311.57 | 8962.39 | 2349.18 | 0.79 | - | 955.38 | 9.69 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10057.95 | 11226.39 | 8894.77 | 2331.62 | 0.79 | - | 948.20 | 9.62 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3049.12 | 3404.31 | 2698.29 | 706.02 | 0.79 | - | 287.45 | 2.92 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3025.71 | 3378.14 | 2677.51 | 700.63 | 0.79 | - | 285.24 | 2.89 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13877.83 | 15456.25 | 12210.58 | 3245.67 | 0.79 | - | 1308.42 | 13.27 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 528127.03 | 652321.10 | 408925.60 | 243395.50 | 0.63 | - | 136793.86 | 1387.44 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 49472.21 | 31519.61 | 17952.61 | 0.64 | - | 5383.03 | 54.60 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6161.68 | 6193.89 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3380.82 | 3395.77 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1399.33 | 1406.15 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2048.01 | 2057.19 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1277.97 | 1283.64 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10095.54 | 10147.82 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9909.40 | 9956.71 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26556.54 | 26686.88 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5784.93 | 6232.61 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5778.77 | 6225.97 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33357.80 | 35939.06 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33258.71 | 35832.32 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5773.28 | 6220.06 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5767.12 | 6213.42 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12798.32 | 12857.38 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1777.96 | 1915.51 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1777.21 | 1914.69 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8570.91 | 9233.93 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11327.11 | 11383.19 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11705.83 | 11763.85 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7360.85 | 7398.85 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8181.41 | 8217.64 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 171732.54 | 129336.20 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 836.44 | 703.64 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 830.82 | 703.64 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.04 | 4955.54 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.63 | 5370.65 | 703.64 | 1.00 | 0.94 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 736.16 | 703.64 | 1.00 | 1.19 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.04 | 730.56 | 703.64 | 1.00 | 1.19 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 221.94 | 703.64 | 1.00 | 1.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 220.22 | 703.64 | 1.00 | 1.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.41 | 992.00 | 703.64 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.91 | 55810.46 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.022669 | 3701.16 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003499 | 1053.66 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.022669 | 2562.44 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34466.48 | 34466.48 | 17.42 | 2.888 | 2.888 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 24.00 | 24.00 | 0.00920 | 30.82 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4334.45 | 4334.45 | 64.62 | 0.363 | 0.363 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00901 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3198.94 | 3198.94 | 41.19 | 0.268 | 0.268 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00935 | 35.63 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 2826.25 | 2826.25 | 17.21 | 0.237 | 0.237 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 24.00 | 24.00 | 0.00865 | 33.68 | 0.00686 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1676.40 | 1676.40 | 17.69 | 0.140 | 0.140 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00871 | 35.85 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44936.17 | 44936.17 | 575.81 | 3.765 | 3.765 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00854 | 37.15 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 18761.32 | 18761.32 | 99.34 | 1.573 | 1.573 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01017 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64651.47 | 64651.47 | 49.42 | 5.419 | 5.419 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00995 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10530.26 | 10530.26 | 269.85 | 1.189 | 1.189 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10459.46 | 10459.46 | 268.07 | 1.181 | 1.181 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00854 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 62389.56 | 62389.56 | 2544.04 | 7.043 | 7.043 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00847 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 67610.25 | 67610.25 | 2756.17 | 7.633 | 7.633 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00869 | 37.71 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9267.79 | 9267.79 | 237.50 | 1.046 | 1.046 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00855 | 33.48 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9197.36 | 9197.36 | 235.72 | 1.038 | 1.038 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00855 | 33.16 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20765.74 | 20765.74 | 53.33 | 1.740 | 1.740 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00938 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2794.09 | 2794.09 | 71.60 | 0.315 | 0.315 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2772.44 | 2772.44 | 71.06 | 0.313 | 0.313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12488.33 | 12488.33 | 509.09 | 1.410 | 1.410 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00861 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30151.66 | 30151.66 | 90.91 | 2.529 | 2.529 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01035 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 31575.66 | 31575.66 | 95.21 | 2.649 | 2.649 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01027 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30711.15 | 30711.15 | 297.29 | 2.580 | 2.580 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10576.31 | 10576.31 | 25.66 | 0.886 | 0.886 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00895 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.95 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2606.54 | 2606.54 | 38.86 | 0.129 | 0.129 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 827.90 | 827.90 | 10.66 | 0.041 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1543.38 | 1543.38 | 9.40 | 0.076 | 0.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00741 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 978.61 | 978.61 | 10.33 | 0.048 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2072.20 | 2072.20 | 26.55 | 0.102 | 0.102 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 6554.60 | 6554.60 | 34.71 | 0.324 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15003.50 | 15003.50 | 11.47 | 0.742 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00757 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5785.05 | 5785.05 | 148.25 | 0.288 | 0.288 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5778.90 | 5778.90 | 148.11 | 0.287 | 0.287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33358.14 | 33358.14 | 1360.23 | 1.658 | 1.658 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33259.05 | 33259.05 | 1355.82 | 1.653 | 1.653 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5773.40 | 5773.40 | 147.95 | 0.287 | 0.287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5767.24 | 5767.24 | 147.81 | 0.287 | 0.287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9088.36 | 9088.36 | 23.34 | 0.449 | 0.475 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1778.00 | 1778.00 | 45.56 | 0.088 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1777.25 | 1777.25 | 45.55 | 0.088 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8571.05 | 8571.05 | 349.40 | 0.426 | 0.426 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5932.69 | 5932.69 | 17.89 | 0.293 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 6056.73 | 6056.73 | 18.26 | 0.299 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1873.48 | 1873.48 | 18.14 | 0.093 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00660 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6291.54 | 6291.54 | 15.27 | 0.311 | 0.311 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.91 | 24.91 | 7.41 | 7.41 | 24.9083 | 11.6668 | 24.9083 | 0.4684 | 0.3000 |
FLR_3_DOAS | 20.68 | 2.05 | 5.06 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6161.682 | 6161.682 | 1.345597 | 0.00005391 | 128.491 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6161.68 | 6161.68 | 1.345597 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6196.31 | 6196.31 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3380.823 | 3380.823 | 0.169233 | 0.00002958 | 85.775 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3380.82 | 3380.82 | 0.169233 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00760265 | 42.6532 | 2606.54 | 0.00 | 3398.18 | 3398.18 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1399.326 | 1399.326 | 0.124903 | 0.00001224 | 31.565 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1399.33 | 1399.33 | 0.124903 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00752486 | 42.2211 | 827.90 | 0.00 | 1406.88 | 1406.88 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2048.008 | 2048.008 | 0.110326 | 0.00001792 | 50.923 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2048.01 | 2048.01 | 0.110326 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00741199 | 41.5953 | 1543.38 | 0.00 | 2058.58 | 2058.58 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1277.965 | 1277.965 | 0.065441 | 0.00001118 | 32.215 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1277.97 | 1277.97 | 0.065441 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00745948 | 41.8586 | 978.61 | 0.00 | 1284.54 | 1284.54 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10095.542 | 10095.542 | 1.754286 | 0.00008832 | 213.368 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10095.54 | 10095.54 | 1.754286 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00740325 | 41.5477 | 2072.20 | 0.00 | 10152.01 | 10152.01 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9909.399 | 9909.399 | 0.733170 | 0.00008669 | 230.193 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9909.40 | 9909.40 | 0.733170 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00764744 | 42.9012 | 6554.60 | 0.00 | 9962.38 | 9962.38 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26556.537 | 26556.537 | 2.525074 | 0.00023233 | 593.971 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26556.54 | 26556.54 | 2.525074 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00756716 | 42.4555 | 15003.50 | 0.00 | 26700.43 | 26700.43 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11498.819 | -999.000 | 1.188739 | 0.00032886 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 11498.82 | 11402.17 | 1.188739 | 21.77 | 14.20 | 0.00854190 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00854190 | 47.5251 | 10530.26 | 0.00 | 8394.21 | 8394.21 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5784.934 | 5784.934 | 0.287580 | 0.00005061 | 165.309 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5784.93 | 5784.93 | 0.287580 | 21.11 | 13.13 | 0.00758802 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00758802 | 42.2831 | 5785.05 | 0.00 | 6236.30 | 6236.30 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11422.389 | -999.000 | 1.180747 | 0.00032667 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11422.39 | 11325.74 | 1.180747 | 21.77 | 14.20 | 0.00854218 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00854218 | 47.5267 | 10459.46 | 0.00 | 8338.55 | 8338.55 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5778.775 | 5778.775 | 0.287274 | 0.00005056 | 165.133 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5778.77 | 5778.77 | 0.287274 | 21.11 | 13.13 | 0.00758765 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00758765 | 42.2810 | 5778.90 | 0.00 | 6229.66 | 6229.66 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 67342.194 | -999.000 | 7.042764 | 0.00192594 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 67342.19 | 67342.19 | 7.042764 | 21.77 | 14.14 | 0.00847442 | 12.80 | 10.79 | 0.00847442 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00847442 | 47.1538 | 62389.56 | 0.00 | 54010.30 | 54010.30 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33357.795 | 33357.795 | 1.658310 | 0.00029183 | 953.209 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33357.80 | 33357.80 | 1.658310 | 21.11 | 13.16 | 0.00761880 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00761880 | 42.4516 | 33358.14 | 0.00 | 35960.72 | 35960.72 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 76746.159 | -999.000 | 7.632713 | 0.00219489 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 76746.16 | 73963.27 | 7.632713 | 21.77 | 14.32 | 0.00868596 | 12.80 | 10.82 | 0.00850000 | 37.71 | 0.00687086 | 18.05 | 0.0000 | 21.11 | 0.00868596 | 48.3167 | 67610.25 | 0.00 | 56472.19 | 55550.12 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33258.707 | 33258.707 | 1.653384 | 0.00029096 | 950.378 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 33258.71 | 33258.71 | 1.653384 | 21.11 | 13.16 | 0.00761765 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00761765 | 42.4453 | 33259.05 | 0.00 | 35853.90 | 35853.90 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10134.145 | -999.000 | 1.046221 | 0.00028983 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 10134.14 | 10038.86 | 1.046221 | 21.77 | 14.20 | 0.00854691 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00854691 | 47.5527 | 9267.79 | 0.00 | 7400.06 | 7400.06 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5773.284 | 5773.284 | 0.287001 | 0.00005051 | 164.976 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5773.28 | 5773.28 | 0.287001 | 21.11 | 13.13 | 0.00758726 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00758726 | 42.2789 | 5773.40 | 0.00 | 6223.74 | 6223.74 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10057.949 | -999.000 | 1.038270 | 0.00028765 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 10057.95 | 9962.79 | 1.038270 | 21.77 | 14.20 | 0.00854721 | 12.80 | 10.82 | 0.00850000 | 33.16 | 0.00686360 | 16.64 | 0.0000 | 21.11 | 0.00854721 | 47.5543 | 9197.36 | 0.00 | 7344.55 | 7344.55 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5767.123 | 5767.123 | 0.286694 | 0.00005045 | 164.800 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5767.12 | 5767.12 | 0.286694 | 21.11 | 13.13 | 0.00758688 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00758688 | 42.2768 | 5767.24 | 0.00 | 6217.10 | 6217.10 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12798.323 | 12798.323 | 0.810685 | 0.00011197 | 306.307 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12798.32 | 12798.32 | 0.810685 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00767513 | 43.0537 | 9088.36 | 0.00 | 12865.31 | 12865.31 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3049.120 | -999.000 | 0.315419 | 0.00008720 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3049.12 | 3024.92 | 0.315419 | 21.77 | 14.20 | 0.00853954 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00853954 | 47.5122 | 2794.09 | 0.00 | 2225.58 | 2225.58 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1777.964 | 1777.964 | 0.088386 | 0.00001555 | 50.804 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1777.96 | 1777.96 | 0.088386 | 21.11 | 13.20 | 0.00765979 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00765979 | 42.6781 | 1778.00 | 0.00 | 1916.69 | 1916.69 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3025.714 | -999.000 | 0.312975 | 0.00008653 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3025.71 | 3001.54 | 0.312975 | 21.77 | 14.20 | 0.00853981 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00853981 | 47.5137 | 2772.44 | 0.00 | 2208.53 | 2208.53 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1777.210 | 1777.210 | 0.088348 | 0.00001555 | 50.783 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1777.21 | 1777.21 | 0.088348 | 21.11 | 13.20 | 0.00765968 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00765968 | 42.6775 | 1777.25 | 0.00 | 1915.88 | 1915.88 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13877.834 | -999.000 | 1.409826 | 0.00039690 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 13877.83 | 13585.68 | 1.409826 | 21.77 | 14.25 | 0.00860628 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00860628 | 47.8792 | 12488.33 | 0.00 | 10167.24 | 10167.24 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8570.915 | 8570.915 | 0.426079 | 0.00007498 | 244.908 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8570.91 | 8570.91 | 0.426079 | 21.11 | 13.21 | 0.00767407 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00767407 | 42.7564 | 8571.05 | 0.00 | 9239.67 | 9239.67 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11327.114 | 11327.114 | 1.178648 | 0.00009909 | 250.546 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11327.11 | 11327.11 | 1.178648 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00774517 | 43.4420 | 5932.69 | 0.00 | 11388.76 | 11388.76 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11705.829 | 11705.829 | 1.234293 | 0.00010241 | 258.526 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11705.83 | 11705.83 | 1.234293 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775014 | 43.4697 | 6056.73 | 0.00 | 11769.57 | 11769.57 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7360.849 | 7360.849 | 1.202240 | 0.00006440 | 156.232 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7360.85 | 7360.85 | 1.202240 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00660274 | 37.1080 | 1873.48 | 0.00 | 7401.97 | 7401.97 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8181.412 | 8181.412 | 0.412890 | 0.00007157 | 207.087 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 8181.41 | 8181.41 | 0.412890 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778764 | 43.6773 | 6291.54 | 0.00 | 8223.44 | 8223.44 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 528127.031 | -999.000 | 24.908284 | 0.01510437 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 528127.03 | 528127.02 | 24.908284 | 30.60 | 16.97 | 0.00834132 | 10.70 | 9.81 | 0.00834132 | 38.10 | 0.00687148 | 18.17 | 46.8176 | 23.99 | 0.00959191 | 44.7238 | 297111.33 | 0.00 | 585323.26 | 542630.66 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 171732.541 | 171732.541 | 7.472485 | 0.00150239 | 2915.337 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 171732.54 | 171732.54 | 7.472485 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 156.0587 | 21.36 | 0.00679257 | 37.3331 | 58296.11 | 0.00 | 156394.26 | 156394.26 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00164017 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00858455 | 47.7594 | 182975.40 | 0.00 | 50441.98 | 50441.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00761854 | 42.4501 | 101848.08 | 0.00 | 12879.82 | 12879.82 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6161.682 | 6161.682 | 1.345597 | 0.00005391 | 128.491 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.5103 | 1.540709 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6161.68 | 6161.68 | 1.0000 | 1.40524949 | 1.345597 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05389958 | 60.00 | 32.22 | 27.78 | 0.000 | 6161.68 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6196.31 | 6196.31 | 1.40524949 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3380.823 | 3380.823 | 0.169233 | 0.00002958 | 85.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.8287 | 0.845364 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3380.82 | 3380.82 | 1.0000 | 0.17673576 | 0.169233 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.02957390 | 60.00 | 32.22 | 27.78 | 0.000 | 3380.82 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760265 | 21.00 | 0.00760265 | 42.6532 | 2606.54 | 0.00 | 3398.18 | 3398.18 | 0.17673576 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.46 | 19.80 | 0.00800000 | 56162.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1399.326 | 1399.326 | 0.124903 | 0.00001224 | 31.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.3430 | 0.349897 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1399.33 | 1399.33 | 1.0000 | 0.13044015 | 0.124903 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01224067 | 60.00 | 32.22 | 27.78 | 0.000 | 1399.33 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00752486 | 21.00 | 0.00752486 | 42.2211 | 827.90 | 0.00 | 1406.88 | 1406.88 | 0.13044015 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.18 | 17.08 | 0.00800000 | 47720.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2048.008 | 2048.008 | 0.110326 | 0.00001792 | 50.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.5020 | 0.512098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2048.01 | 2048.01 | 1.0000 | 0.11521659 | 0.110326 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01791504 | 60.00 | 32.22 | 27.78 | 0.000 | 2048.01 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741199 | 21.00 | 0.00741199 | 41.5953 | 1543.38 | 0.00 | 2058.58 | 2058.58 | 0.11521659 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.12 | 19.38 | 0.00800000 | 54801.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1277.965 | 1277.965 | 0.065441 | 0.00001118 | 32.215 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.3132 | 0.319551 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1277.97 | 1277.97 | 1.0000 | 0.06834176 | 0.065441 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01117906 | 60.00 | 32.22 | 27.78 | 0.000 | 1277.97 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00745948 | 21.00 | 0.00745948 | 41.8586 | 978.61 | 0.00 | 1284.54 | 1284.54 | 0.06834176 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.03 | 19.67 | 0.00800000 | 55730.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10095.542 | 10095.542 | 1.754286 | 0.00008832 | 213.368 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.4746 | 2.524359 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10095.54 | 10095.54 | 1.0000 | 1.83205704 | 1.754286 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08831120 | 60.00 | 32.22 | 27.78 | 0.000 | 10095.54 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00740325 | 21.00 | 0.00740325 | 41.5477 | 2072.20 | 0.00 | 10152.01 | 10152.01 | 1.83205704 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.03 | 15.24 | 0.00800000 | 42476.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9909.399 | 9909.399 | 0.733170 | 0.00008669 | 230.193 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.4289 | 2.477814 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9909.40 | 9909.40 | 1.0000 | 0.76567315 | 0.733170 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08668291 | 60.00 | 32.22 | 27.78 | 0.000 | 9909.40 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00764744 | 21.00 | 0.00764744 | 42.9012 | 6554.60 | 0.00 | 9962.38 | 9962.38 | 0.76567315 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.36 | 17.82 | 0.00800000 | 49946.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26556.537 | 26556.537 | 2.525074 | 0.00023233 | 593.971 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 6.5094 | 6.640378 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26556.54 | 26556.54 | 1.0000 | 2.63701444 | 2.525074 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.23230447 | 60.00 | 32.22 | 27.78 | 0.000 | 26556.54 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00756716 | 21.00 | 0.00756716 | 42.4555 | 15003.50 | 0.00 | 26700.43 | 26700.43 | 2.63701444 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.53 | 16.85 | 0.00800000 | 47060.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11498.819 | -999.000 | 1.188739 | 0.00032886 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7190 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.188739 | 1.24143805 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 1.4507 | 1.450697 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 11498.82 | 11402.17 | 1.0000 | 1.24143805 | 1.188739 | 21.77 | 14.20 | 0.00854190 | 43584.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.32882509 | 6.70 | 15.03 | 8.33 | 0.000 | 11498.82 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00854190 | 21.11 | 0.00854190 | 47.5251 | 10530.26 | 0.00 | 8394.21 | 8394.21 | 1.24143805 | 21.77 | 15.62 | 0.00854190 | 43584.7 | 15.15 | 13.09 | 0.00854190 | 36823.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5784.934 | 5784.934 | 0.287580 | 0.00005061 | 165.309 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.188739 | 1.24143805 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.4180 | 1.446505 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5784.93 | 5784.93 | 1.0000 | 0.30032887 | 0.287580 | 21.11 | 13.13 | 0.00758802 | 40487.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05060397 | 60.00 | 32.22 | 27.78 | 0.000 | 5784.93 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758802 | 21.11 | 0.00758802 | 42.2831 | 5785.05 | 0.00 | 6236.30 | 6236.30 | 0.30032887 | 16.60 | 12.75 | 0.00758802 | 35891.7 | 36.98 | 19.96 | 0.00758802 | 56656.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11422.389 | -999.000 | 1.180747 | 0.00032667 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7195 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.180747 | 1.23309111 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 1.4411 | 1.441054 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11422.39 | 11325.74 | 1.0000 | 1.23309111 | 1.180747 | 21.77 | 14.20 | 0.00854218 | 43585.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.32663945 | 6.70 | 15.03 | 8.33 | 0.000 | 11422.39 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00854218 | 21.11 | 0.00854218 | 47.5267 | 10459.46 | 0.00 | 8338.55 | 8338.55 | 1.23309111 | 21.77 | 15.62 | 0.00854218 | 43585.4 | 15.15 | 13.09 | 0.00854218 | 36823.1 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5778.775 | 5778.775 | 0.287274 | 0.00005056 | 165.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.180747 | 1.23309111 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.4165 | 1.444964 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5778.77 | 5778.77 | 1.0000 | 0.30000908 | 0.287274 | 21.11 | 13.13 | 0.00758765 | 40486.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05055008 | 60.00 | 32.22 | 27.78 | 0.000 | 5778.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758765 | 21.11 | 0.00758765 | 42.2810 | 5778.90 | 0.00 | 6229.66 | 6229.66 | 0.30000908 | 16.60 | 12.75 | 0.00758765 | 35890.7 | 36.98 | 19.96 | 0.00758765 | 56655.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 67342.194 | -999.000 | 7.042764 | 0.00192594 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5935 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.042764 | 7.35498211 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 8.4961 | 8.495926 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 67342.19 | 67342.19 | 1.0000 | 7.35498211 | 7.042764 | 21.77 | 14.14 | 0.00847442 | 43413.6 | 12.80 | 10.79 | 0.00847442 | 34257.6 | 1.92574579 | 6.70 | 15.03 | 8.33 | 0.000 | 67342.19 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00847442 | 21.11 | 0.00847442 | 47.1538 | 62389.56 | 0.00 | 54010.30 | 54010.30 | 7.35498211 | 21.77 | 15.56 | 0.00847442 | 43413.6 | 14.58 | 12.80 | 0.00847442 | 36070.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33357.795 | 33357.795 | 1.658310 | 0.00029183 | 953.209 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.042764 | 7.35498211 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 8.1765 | 8.341011 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33357.80 | 33357.80 | 1.0000 | 1.73182530 | 1.658310 | 21.11 | 13.16 | 0.00761880 | 40566.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.29179877 | 60.00 | 32.22 | 27.78 | 0.000 | 33357.80 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00761880 | 21.11 | 0.00761880 | 42.4516 | 33358.14 | 0.00 | 35960.72 | 35960.72 | 1.73182530 | 16.60 | 12.78 | 0.00761880 | 35969.6 | 36.98 | 19.98 | 0.00761880 | 56734.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 76746.159 | -999.000 | 7.632713 | 0.00219489 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9868 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.632713 | 7.97108481 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 9.6825 | 9.682335 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 76746.16 | 73963.27 | 1.0000 | 7.97108481 | 7.632713 | 21.77 | 14.32 | 0.00868596 | 43950.3 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 2.19466555 | 6.70 | 15.03 | 8.33 | 0.000 | 76746.16 | 37.71 | 0.00687086 | 18.05 | 0.00000000 | 0.0000 | 21.11 | 0.00868596 | 21.11 | 0.00868596 | 48.3167 | 67610.25 | 0.00 | 56472.19 | 55550.12 | 7.97108481 | 21.77 | 15.75 | 0.00868596 | 43950.3 | 14.94 | 13.11 | 0.00864021 | 36865.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33258.707 | 33258.707 | 1.653384 | 0.00029096 | 950.378 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.632713 | 7.97108481 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 8.1522 | 8.316235 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 33258.71 | 33258.71 | 1.0000 | 1.72668098 | 1.653384 | 21.11 | 13.16 | 0.00761765 | 40563.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.29093200 | 60.00 | 32.22 | 27.78 | 0.000 | 33258.71 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00761765 | 21.11 | 0.00761765 | 42.4453 | 33259.05 | 0.00 | 35853.90 | 35853.90 | 1.72668098 | 16.60 | 12.78 | 0.00761765 | 35966.7 | 36.98 | 19.98 | 0.00761765 | 56731.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10134.145 | -999.000 | 1.046221 | 0.00028983 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7283 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.046221 | 1.09260213 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 1.2786 | 1.278529 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 10134.14 | 10038.86 | 1.0000 | 1.09260213 | 1.046221 | 21.77 | 14.20 | 0.00854691 | 43597.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.28980027 | 6.70 | 15.03 | 8.33 | 0.000 | 10134.14 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00854691 | 21.11 | 0.00854691 | 47.5527 | 9267.79 | 0.00 | 7400.06 | 7400.06 | 1.09260213 | 21.77 | 15.63 | 0.00854691 | 43597.4 | 15.14 | 13.09 | 0.00854691 | 36824.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5773.284 | 5773.284 | 0.287001 | 0.00005051 | 164.976 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.046221 | 1.09260213 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.4151 | 1.443591 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5773.28 | 5773.28 | 1.0000 | 0.29972403 | 0.287001 | 21.11 | 13.13 | 0.00758726 | 40485.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05050206 | 60.00 | 32.22 | 27.78 | 0.000 | 5773.28 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758726 | 21.11 | 0.00758726 | 42.2789 | 5773.40 | 0.00 | 6223.74 | 6223.74 | 0.29972403 | 16.60 | 12.75 | 0.00758726 | 35889.7 | 36.98 | 19.96 | 0.00758726 | 56654.7 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10057.949 | -999.000 | 1.038270 | 0.00028765 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7288 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.038270 | 1.08429856 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 1.2689 | 1.268916 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 10057.95 | 9962.79 | 1.0000 | 1.08429856 | 1.038270 | 21.77 | 14.20 | 0.00854721 | 43598.2 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.28762134 | 6.70 | 15.03 | 8.33 | 0.000 | 10057.95 | 33.16 | 0.00686360 | 16.64 | 0.00000000 | 0.0000 | 21.11 | 0.00854721 | 21.11 | 0.00854721 | 47.5543 | 9197.36 | 0.00 | 7344.55 | 7344.55 | 1.08429856 | 21.77 | 15.63 | 0.00854721 | 43598.2 | 15.13 | 13.09 | 0.00854721 | 36824.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5767.123 | 5767.123 | 0.286694 | 0.00005045 | 164.800 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.038270 | 1.08429856 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.4136 | 1.442051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5767.12 | 5767.12 | 1.0000 | 0.29940416 | 0.286694 | 21.11 | 13.13 | 0.00758688 | 40484.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05044816 | 60.00 | 32.22 | 27.78 | 0.000 | 5767.12 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758688 | 21.11 | 0.00758688 | 42.2768 | 5767.24 | 0.00 | 6217.10 | 6217.10 | 0.29940416 | 16.60 | 12.75 | 0.00758688 | 35888.8 | 36.98 | 19.96 | 0.00758688 | 56653.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12798.323 | 12798.323 | 0.810685 | 0.00011197 | 306.307 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 3.1370 | 3.200180 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12798.32 | 12798.32 | 1.0000 | 0.84662358 | 0.810685 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11195389 | 60.00 | 32.22 | 27.78 | 0.000 | 12798.32 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00767513 | 21.00 | 0.00767513 | 43.0537 | 9088.36 | 0.00 | 12865.31 | 12865.31 | 0.84662358 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.50 | 18.53 | 0.00800000 | 52130.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3049.120 | -999.000 | 0.315419 | 0.00008720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7146 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.315419 | 0.32940212 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 0.3847 | 0.384679 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3049.12 | 3024.92 | 1.0000 | 0.32940212 | 0.315419 | 21.77 | 14.20 | 0.00853954 | 43578.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.08719391 | 6.70 | 15.03 | 8.33 | 0.000 | 3049.12 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00853954 | 21.11 | 0.00853954 | 47.5122 | 2794.09 | 0.00 | 2225.58 | 2225.58 | 0.32940212 | 21.77 | 15.62 | 0.00853954 | 43578.7 | 15.15 | 13.09 | 0.00853954 | 36822.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1777.964 | 1777.964 | 0.088386 | 0.00001555 | 50.804 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.315419 | 0.32940212 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.4358 | 0.444574 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1777.96 | 1777.96 | 1.0000 | 0.09230426 | 0.088386 | 21.11 | 13.20 | 0.00765979 | 40669.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01555282 | 60.00 | 32.22 | 27.78 | 0.000 | 1777.96 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00765979 | 21.11 | 0.00765979 | 42.6781 | 1778.00 | 0.00 | 1916.69 | 1916.69 | 0.09230426 | 16.60 | 12.82 | 0.00765979 | 36073.4 | 36.98 | 20.02 | 0.00765979 | 56838.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3025.714 | -999.000 | 0.312975 | 0.00008653 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7151 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.312975 | 0.32684929 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 0.3817 | 0.381726 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3025.71 | 3001.54 | 1.0000 | 0.32684929 | 0.312975 | 21.77 | 14.20 | 0.00853981 | 43579.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.08652460 | 6.70 | 15.03 | 8.33 | 0.000 | 3025.71 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00853981 | 21.11 | 0.00853981 | 47.5137 | 2772.44 | 0.00 | 2208.53 | 2208.53 | 0.32684929 | 21.77 | 15.62 | 0.00853981 | 43579.4 | 15.15 | 13.09 | 0.00853981 | 36822.4 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1777.210 | 1777.210 | 0.088348 | 0.00001555 | 50.783 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.312975 | 0.32684929 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 0.4356 | 0.444386 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1777.21 | 1777.21 | 1.0000 | 0.09226508 | 0.088348 | 21.11 | 13.20 | 0.00765968 | 40669.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01554622 | 60.00 | 32.22 | 27.78 | 0.000 | 1777.21 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00765968 | 21.11 | 0.00765968 | 42.6775 | 1777.25 | 0.00 | 1915.88 | 1915.88 | 0.09226508 | 16.60 | 12.82 | 0.00765968 | 36073.1 | 36.98 | 20.02 | 0.00765968 | 56838.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13877.834 | -999.000 | 1.409826 | 0.00039690 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8386 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.409826 | 1.47232579 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 1.7509 | 1.750835 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 13877.83 | 13585.68 | 1.0000 | 1.47232579 | 1.409826 | 21.77 | 14.25 | 0.00860628 | 43748.0 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.39685640 | 6.70 | 15.03 | 8.33 | 0.000 | 13877.83 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00860628 | 21.11 | 0.00860628 | 47.8792 | 12488.33 | 0.00 | 10167.24 | 10167.24 | 1.47232579 | 21.77 | 15.68 | 0.00860628 | 43748.0 | 15.01 | 13.10 | 0.00860628 | 36842.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8570.915 | 8570.915 | 0.426079 | 0.00007498 | 244.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.409826 | 1.47232579 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.1008 | 2.143130 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8570.91 | 8570.91 | 1.0000 | 0.44496792 | 0.426079 | 21.11 | 13.21 | 0.00767407 | 40706.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07497445 | 60.00 | 32.22 | 27.78 | 0.000 | 8570.91 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00767407 | 21.11 | 0.00767407 | 42.7564 | 8571.05 | 0.00 | 9239.67 | 9239.67 | 0.44496792 | 16.60 | 12.83 | 0.00767407 | 36109.5 | 36.98 | 20.03 | 0.00767407 | 56874.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11327.114 | 11327.114 | 1.178648 | 0.00009909 | 250.546 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.7764 | 2.832309 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11327.11 | 11327.11 | 1.0000 | 1.23089992 | 1.178648 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09908443 | 60.00 | 32.22 | 27.78 | 0.000 | 11327.11 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00774517 | 21.00 | 0.00774517 | 43.4420 | 5932.69 | 0.00 | 11388.76 | 11388.76 | 1.23089992 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.67 | 16.55 | 0.00800000 | 46187.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11705.829 | 11705.829 | 1.234293 | 0.00010241 | 258.526 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.8693 | 2.927006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11705.83 | 11705.83 | 1.0000 | 1.28901134 | 1.234293 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10239725 | 60.00 | 32.22 | 27.78 | 0.000 | 11705.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775014 | 21.00 | 0.00775014 | 43.4697 | 6056.73 | 0.00 | 11769.57 | 11769.57 | 1.28901134 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.55 | 16.51 | 0.00800000 | 46065.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7360.849 | 7360.849 | 1.202240 | 0.00006440 | 156.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 1.8042 | 1.840557 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7360.85 | 7360.85 | 1.0000 | 1.25553767 | 1.202240 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06438935 | 60.00 | 32.22 | 27.78 | 0.000 | 7360.85 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.45 | 0.00660274 | 21.00 | 0.00660274 | 37.1080 | 1873.48 | 0.00 | 7401.97 | 7401.97 | 1.25553767 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.38 | 15.37 | 0.00800000 | 42830.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8181.412 | 8181.412 | 0.412890 | 0.00007157 | 207.087 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 2.0054 | 2.045736 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 8181.41 | 8181.41 | 1.0000 | 0.43119375 | 0.412890 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07156726 | 60.00 | 32.22 | 27.78 | 0.000 | 8181.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00778764 | 21.00 | 0.00778764 | 43.6773 | 6291.54 | 0.00 | 8223.44 | 8223.44 | 0.43119375 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.30 | 19.75 | 0.00800000 | 56006.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 528127.031 | -999.000 | 24.908284 | 0.01510437 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3461 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.908284 | 26.01251103 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 66.6300 | 66.630024 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 528127.03 | 528127.02 | 1.0000 | 26.01251103 | 24.908284 | 30.60 | 16.97 | 0.00834132 | 52078.9 | 10.70 | 9.81 | 0.00834132 | 31776.0 | 15.10282543 | 6.70 | 15.03 | 8.33 | 55810.462 | 472316.57 | 38.10 | 0.00687148 | 18.17 | 11.66146000 | 46.8176 | 23.99 | 0.00963525 | 23.99 | 0.00959191 | 44.7238 | 297111.33 | 0.00 | 585323.26 | 542630.66 | 26.01251103 | 30.60 | 18.51 | 0.00834132 | 52078.9 | 10.15 | 10.13 | 0.00768999 | 29577.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 171732.541 | 171732.541 | 7.472485 | 0.00150239 | 2915.337 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.908284 | 26.01251103 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 42.0940 | 42.941180 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | Sensible | 171732.54 | 171732.54 | 1.0000 | 7.80375331 | 7.472485 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.50223793 | 60.00 | 32.22 | 27.78 | 0.000 | 171732.54 | -5.20 | 0.00280840 | -5.20 | 11.66146000 | 156.0587 | 18.55 | 0.00704714 | 21.36 | 0.00679257 | 37.3331 | 58296.11 | 0.00 | 156394.26 | 156394.26 | 7.80375331 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00164017 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 22.66669674 | 15.03 | 6.70 | 8.33 | 792626.21 | 7.2353 | 7.235280 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 1.63999890 | 6.70 | 15.03 | 8.33 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00857806 | 21.11 | 0.00858455 | 47.7594 | 182975.40 | 0.00 | 50441.98 | 50441.98 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.96 | 11.35 | 0.00687148 | 32410.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 3.49836198 | 54.44 | 82.22 | 27.78 | 407973.71 | 3.4666 | 3.536413 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00761739 | 21.11 | 0.00761854 | 42.4501 | 101848.08 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.91 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2007.33 | 6376.83 | 966.17 |
RETAIL_1_FLR_1 | 3232.17 | 5425.50 | 1015.33 |
RETAIL_2_FLR_1 | 2794.67 | 5765.83 | 1124.67 |
MECH_FLR_1 | 2018.83 | 6381.33 | 629.83 |
STORAGE_FLR_1 | 1813.33 | 6650.83 | 722.33 |
LAUNDRY_FLR_1 | 8015.83 | 3799.00 | 3494.67 |
CAFE_FLR_1 | 4456.00 | 4492.83 | 1869.33 |
LOBBY_FLR_1 | 3393.17 | 5354.17 | 1691.00 |
ROOM_1_FLR_3 | 805.50 | 7914.00 | 539.33 |
ROOM_2_FLR_3 | 1740.33 | 7778.83 | 1431.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 660.50 | 8732.17 | 657.00 |
ROOM_5_FLR_3 | 720.50 | 7845.00 | 540.33 |
ROOM_6_FLR_3 | 1767.50 | 7667.33 | 1396.67 |
CORRIDOR_FLR_3 | 1959.00 | 7287.33 | 1326.00 |
ROOM_1_FLR_6 | 1712.67 | 7737.33 | 1241.67 |
ROOM_2_FLR_6 | 2746.83 | 7650.00 | 2251.83 |
ROOM_3_MULT9_FLR_6 | 461.00 | 7906.00 | 289.33 |
BANQUET_FLR_6 | 4406.50 | 3429.83 | 1801.50 |
DINING_FLR_6 | 4826.67 | 2284.83 | 1700.17 |
KITCHEN_FLR_6 | 8533.67 | 6690.00 | 6684.83 |
CORRIDOR_FLR_6 | 2523.83 | 6301.00 | 899.83 |
Facility | 8759.00 | 8760.00 | 7790.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 234.50 | 0.00 | 234.50 |
ROOM_2_FLR_3 | 0.00 | 231.00 | 0.00 | 231.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 89.33 | 0.00 | 89.33 |
ROOM_5_FLR_3 | 0.00 | 160.17 | 0.00 | 160.17 |
ROOM_6_FLR_3 | 0.00 | 243.17 | 0.00 | 243.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 268.17 | 0.00 | 268.17 |
ROOM_2_FLR_6 | 0.00 | 256.17 | 0.00 | 256.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 148.33 | 0.00 | 148.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 522.67 | 0.00 | 522.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.034 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.286 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.466 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.583 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.586 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.148 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.727 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.814 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.175 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.059 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.078 | 0.000 | 0.090 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.175 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.573 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.175 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.142 | 0.000 | 0.105 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.109 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.511 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 23.086 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.133 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.491 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.422 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.999 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.474 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.418 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 11.379 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.588 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.170 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.336 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.652 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.840 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 9.970 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.744 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42947704.65 | 0.00 | 42947704.65 | 0.00 | 42947704.65 | 26946214.98 | 138.72 | 22.51 | 8598.77 | 0.00 |
RETAIL_1_FLR_1 | 5236249.87 | 0.00 | 5236249.87 | 309826.10 | 5546075.97 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3878589.52 | 0.00 | 3878589.52 | 119593.27 | 3998182.78 | 2892943.94 | 9.50 | 4.37 | 8746.13 | 0.00 |
MECH_FLR_1 | 3275464.37 | 0.00 | 3275464.37 | 282647.43 | 3558111.81 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1900376.76 | 0.00 | 1900376.76 | 163072.00 | 2063448.76 | 1821682.01 | 2438.04 | 1129.05 | 5192.91 | 0.00 |
LAUNDRY_FLR_1 | 61629304.54 | 0.00 | 61629304.54 | 385940.64 | 62015245.17 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23937838.94 | 0.00 | 23937838.94 | 684888.14 | 24622727.08 | 21330615.53 | 2983.28 | 213.25 | 5563.47 | 0.00 |
LOBBY_FLR_1 | 80692297.65 | 0.00 | 80692297.65 | 1956881.84 | 82649179.49 | 59728886.00 | 16.84 | 8.46 | 8734.69 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 57030.95 | 1517187.67 | 179831.92 | 1697019.59 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 59973.20 | 1519958.83 | 179818.20 | 1699777.03 | 1946647.51 | 2190.00 | 5879.17 | 690.83 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 351.62 | 1100263.59 | 50175.12 | 1150438.71 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 368.67 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 57973.57 | 19861802.86 | 50188.84 | 19911991.71 | 26405105.73 | 2190.00 | 5929.28 | 640.72 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 57178.91 | 1517335.62 | 179831.92 | 1697167.55 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 57499.54 | 1517485.18 | 179818.20 | 1697303.38 | 1946647.51 | 2190.00 | 5880.33 | 689.67 | 0.00 |
CORRIDOR_FLR_3 | 23454058.25 | 0.00 | 23454058.25 | 217452.98 | 23671511.22 | 14972100.18 | 8.67 | 9.33 | 8742.01 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 67664.60 | 432703.78 | 179868.73 | 612572.51 | 486718.90 | 2055.18 | 5876.89 | 827.93 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 69401.86 | 434398.26 | 179855.01 | 614253.27 | 486661.88 | 2054.28 | 5881.13 | 824.59 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 67711.40 | 2412901.71 | 92027.14 | 2504928.85 | 3126920.42 | 2190.00 | 5874.08 | 695.92 | 0.00 |
BANQUET_FLR_6 | 44274665.35 | 0.00 | 44274665.35 | 439194.23 | 44713859.58 | 37458366.31 | 810.49 | 2237.94 | 5711.57 | 0.00 |
DINING_FLR_6 | 47758998.59 | 0.00 | 47758998.59 | 439194.23 | 48198192.82 | 37458366.31 | 82.48 | 44.28 | 8633.24 | 0.00 |
KITCHEN_FLR_6 | 62381683.12 | 0.00 | 62381683.12 | 393180.66 | 62774863.79 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12278339.17 | 0.00 | 12278339.17 | 384823.29 | 12663162.46 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6105913.44 | 0.21E+10 | 18121884.23 | 0.21E+10 | 0.43E+10 | 8760.00 | 7540.81 | 8760.00 | 368.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3619 | 0.0000 | 1.3619 | 0.0000 | 1.3619 | 0.8545 | 138.72 | 22.51 | 8598.77 |
RETAIL_1_FLR_1 | 0.1660 | 0.0000 | 0.1660 | 0.0098 | 0.1759 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1230 | 0.0000 | 0.1230 | 0.0038 | 0.1268 | 0.0917 | 9.50 | 4.37 | 8746.13 |
MECH_FLR_1 | 0.1039 | 0.0000 | 0.1039 | 0.0090 | 0.1128 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0603 | 0.0000 | 0.0603 | 0.0052 | 0.0654 | 0.0578 | 2438.04 | 1129.05 | 5192.91 |
LAUNDRY_FLR_1 | 1.9543 | 0.0000 | 1.9543 | 0.0122 | 1.9665 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7591 | 0.0000 | 0.7591 | 0.0217 | 0.7808 | 0.6764 | 2983.28 | 213.25 | 5563.47 |
LOBBY_FLR_1 | 2.5587 | 0.0000 | 2.5587 | 0.0621 | 2.6208 | 1.8940 | 16.84 | 8.46 | 8734.69 |
ROOM_1_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0057 | 0.0538 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0057 | 0.0539 | 0.0617 | 2190.00 | 5879.17 | 690.83 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0016 | 0.6314 | 0.8373 | 2190.00 | 5929.28 | 640.72 |
ROOM_5_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0057 | 0.0538 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0057 | 0.0538 | 0.0617 | 2190.00 | 5880.33 | 689.67 |
CORRIDOR_FLR_3 | 0.7437 | 0.0000 | 0.7437 | 0.0069 | 0.7506 | 0.4748 | 8.67 | 9.33 | 8742.01 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0057 | 0.0194 | 0.0154 | 2055.18 | 5876.89 | 827.93 |
ROOM_2_FLR_6 | 0.0116 | 0.0022 | 0.0138 | 0.0057 | 0.0195 | 0.0154 | 2054.28 | 5881.13 | 824.59 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0765 | 0.0029 | 0.0794 | 0.0992 | 2190.00 | 5874.08 | 695.92 |
BANQUET_FLR_6 | 1.4039 | 0.0000 | 1.4039 | 0.0139 | 1.4179 | 1.1878 | 810.49 | 2237.94 | 5711.57 |
DINING_FLR_6 | 1.5144 | 0.0000 | 1.5144 | 0.0139 | 1.5284 | 1.1878 | 82.48 | 44.28 | 8633.24 |
KITCHEN_FLR_6 | 1.9781 | 0.0000 | 1.9781 | 0.0125 | 1.9906 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3893 | 0.0000 | 0.3893 | 0.0122 | 0.4015 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.5071 | 0.1928 | 64.6999 | 0.4537 | 65.1536 | 73.9670 | 8760.00 | 7540.81 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.45E+09 | 0.00 | 0.45E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 32521733.86 | 494785.64 | 33016519.50 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.3054 | 0.0000 | 14.3054 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.0313 | 0.0157 | 1.0469 | 2.0513 | 8759.83 | 0.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 5098.75 | 0.00 | 0.00 | 0.00 | 3661.25 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 15.0697 | 0.0000 | 0.0000 | 0.0000 | 13.2449 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.3026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
Electricity:Building | 2448.45 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.36 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.61 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.17 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.75 | 1114.41 | 21-APR-22:30 | 3261.55 | 15-AUG-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1622.20 | 2700.45 | 21-NOV-02:30 | 167553.15 | 26-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.47 | 0.00 | 01-JAN-11:10 | 1891.81 | 02-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.18 | 976.25 | 20-DEC-03:50 | 1201.31 | 16-OCT-13:10 |
Fans:Electricity | 599.50 | 11199.42 | 26-NOV-15:00 | 50793.89 | 07-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 755.23 | 11738.67 | 26-NOV-15:00 | 61574.64 | 07-AUG-21:10 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
ElectricityPurchased:Plant | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
Cogeneration:ElectricityPurchased | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
General:Cogeneration:ElectricityPurchased | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
ElectricityNet:Plant | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
Cogeneration:ElectricityNet | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
General:Cogeneration:ElectricityNet | 5638.93 | 70048.61 | 28-MAR-02:10 | 404811.92 | 25-JUL-19:10 |
General:Fans:Electricity | 599.50 | 11199.42 | 26-NOV-15:00 | 50793.89 | 07-AUG-21:10 |
ExteriorLights:Electricity | 194.01 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.01 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 133.96 | 0.00 | 01-JAN-08:10 | 9938.94 | 02-JUN-08:20 |
General:HeatRecovery:Electricity | 133.96 | 0.00 | 01-JAN-08:10 | 9938.94 | 02-JUN-08:20 |
WaterSystems:Electricity | 90.74 | 1086.56 | 22-JUN-01:00 | 4738.73 | 06-APR-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 22-JUN-01:00 | 4738.73 | 06-APR-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1392.86 | 0.00 | 01-JAN-03:20 | 157627.30 | 14-JUN-18:10 |
General:Cooling:Electricity | 1392.86 | 0.00 | 01-JAN-03:20 | 157627.30 | 14-JUN-18:10 |
Pumps:Electricity | 83.94 | 47.91 | 15-FEB-08:30 | 4108.86 | 05-JUN-19:10 |
General:Pumps:Electricity | 83.94 | 47.91 | 15-FEB-08:30 | 4108.86 | 05-JUN-19:10 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5419.10 | 29270.80 | 16-MAR-01:20 | 545543.43 | 01-FEB-18:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3630.27 | 15908.90 | 09-MAY-10:10 | 441295.11 | 01-FEB-18:50 |
WaterSystems:NaturalGas | 2844.13 | 15908.90 | 22-FEB-16:10 | 248619.64 | 23-JAN-22:00 |
Water Heater:WaterSystems:NaturalGas | 2844.13 | 15908.90 | 22-FEB-16:10 | 248619.64 | 23-JAN-22:00 |
Heating:NaturalGas | 786.14 | 0.00 | 01-JAN-11:40 | 210090.42 | 25-DEC-00:10 |
Boiler:Heating:NaturalGas | 786.14 | 0.00 | 01-JAN-11:40 | 210090.42 | 25-DEC-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4208.49 | 0.00 | 01-JAN-03:20 | 607489.03 | 21-JUL-21:00 |
PlantLoopCoolingDemand:HVAC | 4208.49 | 0.00 | 01-JAN-03:20 | 607489.03 | 21-JUL-21:00 |
CoolingCoils:PlantLoopCoolingDemand | 4208.49 | 0.00 | 01-JAN-03:20 | 607489.03 | 21-JUL-21:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22371.74 | 118830.05 | 25-DEC-14:40 | 2309914.11 | 21-JUL-21:00 |
EnergyTransfer:Building | 5449.89 | 85428.18 | 26-DEC-11:10 | 341539.19 | 07-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 735.58 | 10857.38 | 19-DEC-04:00 | 36216.27 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 181.99 | 4015.98 | 21-APR-22:30 | 10359.09 | 15-AUG-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.99 | 2007.99 | 21-APR-22:30 | 5179.55 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer | 90.99 | 2007.99 | 21-APR-22:30 | 5179.55 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.99 | 2007.99 | 21-APR-22:30 | 5179.55 | 15-AUG-06:20 |
EnergyTransfer:Plant | 11188.89 | 19454.83 | 29-MAR-00:20 | 1395085.03 | 21-JUL-21:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.43 | 1878.76 | 20-DEC-03:50 | 2553.93 | 16-OCT-13:10 |
EnergyTransfer:Zone:BASEMENT | 413.21 | 8609.37 | 26-MAR-15:00 | 24598.19 | 22-SEP-21:00 |
Heating:EnergyTransfer | 41.35 | 0.00 | 01-JAN-08:10 | 42962.84 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 41.35 | 0.00 | 01-JAN-08:10 | 42962.84 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5317.54 | 81382.47 | 26-DEC-15:00 | 337936.76 | 07-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 413.21 | 8609.37 | 26-MAR-15:00 | 24598.19 | 22-SEP-21:00 |
General:Cooling:EnergyTransfer | 5317.54 | 81382.47 | 26-DEC-15:00 | 337936.76 | 07-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 413.21 | 8609.37 | 26-MAR-15:00 | 24598.19 | 22-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.02 | 0.10 | 04-DEC-07:00 | 3613.32 | 18-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 733.75 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 733.75 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.99 | 0.00 | 07-JAN-07:10 | 3613.32 | 18-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.99 | 0.00 | 07-JAN-07:10 | 3613.32 | 18-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.94 | 748.03 | 26-DEC-15:00 | 2348.67 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.94 | 748.03 | 26-DEC-15:00 | 2348.67 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.94 | 748.03 | 26-DEC-15:00 | 2348.67 | 15-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 29.33 | 180.88 | 27-DEC-05:00 | 2140.36 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.33 | 180.88 | 27-DEC-05:00 | 2140.36 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.33 | 180.88 | 27-DEC-05:00 | 2140.36 | 15-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 16.34 | 15.59 | 27-DEC-05:00 | 1036.18 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 16.34 | 15.59 | 27-DEC-05:00 | 1036.18 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 16.34 | 15.59 | 27-DEC-05:00 | 1036.18 | 15-JUN-18:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.95 | 9882.67 | 27-DEC-05:00 | 39420.49 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.95 | 9882.67 | 27-DEC-05:00 | 39420.49 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.95 | 9882.67 | 27-DEC-05:00 | 39420.49 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 238.15 | 2284.44 | 26-DEC-11:30 | 12792.01 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 238.15 | 2284.44 | 26-DEC-11:30 | 12792.01 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 238.15 | 2284.44 | 26-DEC-11:30 | 12792.01 | 18-OCT-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 806.12 | 15587.45 | 26-DEC-15:00 | 43867.01 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 806.12 | 15587.45 | 26-DEC-15:00 | 43867.01 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 806.12 | 15587.45 | 26-DEC-15:00 | 43867.01 | 07-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.43 | 0.00 | 01-JAN-08:10 | 8937.78 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.52 | 0.00 | 01-JAN-00:10 | 4054.75 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.52 | 0.00 | 01-JAN-00:10 | 4054.75 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.91 | 0.00 | 01-JAN-00:20 | 8937.78 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.91 | 0.00 | 01-JAN-00:20 | 8937.78 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.75 | 0.00 | 01-JAN-08:10 | 8974.20 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 7.57 | 0.00 | 01-JAN-08:10 | 4263.24 | 27-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 7.57 | 0.00 | 01-JAN-08:10 | 4263.24 | 27-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.18 | 0.00 | 01-JAN-00:10 | 8974.20 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.18 | 0.00 | 01-JAN-00:10 | 8974.20 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 377.40 | 0.00 | 01-JAN-00:10 | 43976.35 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 377.40 | 0.00 | 01-JAN-00:10 | 43976.35 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 377.40 | 0.00 | 01-JAN-00:10 | 43976.35 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 457.15 | 0.00 | 01-JAN-08:10 | 60723.15 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 8.23 | 0.00 | 01-JAN-00:10 | 19750.99 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 8.23 | 0.00 | 01-JAN-00:10 | 19750.99 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 448.92 | 0.00 | 01-JAN-08:10 | 60723.15 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 448.92 | 0.00 | 01-JAN-08:10 | 60723.15 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 75.71 | 0.00 | 01-JAN-08:10 | 7829.71 | 15-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.64 | 0.00 | 01-JAN-08:10 | 4053.41 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.64 | 0.00 | 01-JAN-08:10 | 4053.41 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 71.07 | 0.00 | 01-JAN-00:10 | 7829.71 | 15-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 71.07 | 0.00 | 01-JAN-00:10 | 7829.71 | 15-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.03 | 0.00 | 01-JAN-08:10 | 8445.50 | 14-JUN-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 7.50 | 0.00 | 01-JAN-08:10 | 4131.00 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 7.50 | 0.00 | 01-JAN-08:10 | 4131.00 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 56.54 | 0.00 | 01-JAN-00:10 | 8445.50 | 14-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 56.54 | 0.00 | 01-JAN-00:10 | 8445.50 | 14-JUN-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.75 | 53.74 | 27-DEC-07:40 | 12545.52 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 194.45 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 194.45 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.75 | 0.00 | 27-DEC-07:10 | 12545.52 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.75 | 0.00 | 27-DEC-07:10 | 12545.52 | 15-JUN-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.42 | 0.00 | 01-JAN-08:10 | 2389.34 | 15-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.26 | 0.00 | 01-JAN-08:10 | 1211.20 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.26 | 0.00 | 01-JAN-08:10 | 1211.20 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.16 | 0.00 | 01-JAN-00:10 | 2389.34 | 15-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.16 | 0.00 | 01-JAN-00:10 | 2389.34 | 15-JUN-16:30 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.41 | 0.00 | 01-JAN-08:10 | 2395.13 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.37 | 0.00 | 01-JAN-08:10 | 1319.95 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.37 | 0.00 | 01-JAN-08:10 | 1319.95 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.04 | 0.00 | 01-JAN-00:10 | 2395.13 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.04 | 0.00 | 01-JAN-00:10 | 2395.13 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 108.99 | 0.00 | 01-JAN-08:10 | 11025.63 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.19 | 0.00 | 01-JAN-00:10 | 4631.17 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.19 | 0.00 | 01-JAN-00:10 | 4631.17 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 105.80 | 0.00 | 01-JAN-05:40 | 11025.63 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 105.80 | 0.00 | 01-JAN-05:40 | 11025.63 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 456.24 | 8446.55 | 26-DEC-12:00 | 23859.79 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 456.24 | 8446.55 | 26-DEC-12:00 | 23859.79 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 456.24 | 8446.55 | 26-DEC-12:00 | 23859.79 | 15-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 494.29 | 9425.47 | 26-DEC-15:00 | 25044.27 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 494.29 | 9425.47 | 26-DEC-15:00 | 25044.27 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 494.29 | 9425.47 | 26-DEC-15:00 | 25044.27 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 644.59 | 8729.57 | 19-DEC-04:00 | 31130.42 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 644.59 | 8729.57 | 19-DEC-04:00 | 31130.42 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.67 | 0.16 | 19-DEC-04:50 | 6949.09 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 1002.29 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 1002.29 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.63 | 0.00 | 07-JAN-07:10 | 6949.09 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.63 | 0.00 | 07-JAN-07:10 | 6949.09 | 03-JUL-12:50 |
PlantLoopHeatingDemand:Facility | 1157.47 | 7205.96 | 28-JUL-01:20 | 175358.97 | 13-MAR-06:10 |
PlantLoopHeatingDemand:Plant | 648.50 | 7205.96 | 28-JUL-01:20 | 50242.18 | 27-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 648.50 | 7205.96 | 28-JUL-01:20 | 50242.18 | 27-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 648.50 | 7205.96 | 28-JUL-01:20 | 50242.18 | 27-JAN-07:10 |
EnergyTransfer:HVAC | 5732.96 | 31.91 | 28-FEB-18:10 | 664643.63 | 21-JUL-18:10 |
HeatingCoils:EnergyTransfer | 508.96 | 0.00 | 01-JAN-11:40 | 143154.89 | 27-DEC-17:40 |
PlantLoopHeatingDemand:HVAC | 508.96 | 0.00 | 01-JAN-11:40 | 143154.89 | 27-DEC-17:40 |
HeatingCoils:PlantLoopHeatingDemand | 508.96 | 0.00 | 01-JAN-11:40 | 143154.89 | 27-DEC-17:40 |
CoolingCoils:EnergyTransfer | 4208.49 | 0.00 | 01-JAN-03:20 | 607489.03 | 21-JUL-21:00 |
HeatRecoveryForHeating:EnergyTransfer | 772.03 | 0.00 | 01-JAN-08:10 | 366937.29 | 03-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 243.48 | 0.00 | 01-JAN-00:10 | 145684.59 | 21-JUL-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 648.50 | 7205.96 | 28-JUL-01:20 | 50242.18 | 27-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 648.50 | 7205.96 | 28-JUL-01:20 | 50242.18 | 27-JAN-07:10 |
Boilers:EnergyTransfer | 505.13 | 0.00 | 01-JAN-11:40 | 142856.97 | 27-DEC-17:40 |
Chillers:EnergyTransfer | 4275.70 | 0.00 | 01-JAN-03:20 | 606899.73 | 21-JUL-21:00 |
HeatRejection:EnergyTransfer | 5668.57 | 0.00 | 01-JAN-03:20 | 757120.88 | 21-JUL-21:00 |
General:HeatRejection:EnergyTransfer | 5668.57 | 0.00 | 01-JAN-03:20 | 757120.88 | 21-JUL-21:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -413.213 | 0.000 | 0.000 | 138.691 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -29.878 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.037 | -45.988 | 0.000 | 0.000 | 14.699 | 7.307 | 10.186 | 23.608 | 0.000 | 0.462 | 0.253 | 0.000 | -8.407 | 0.000 | -2.158 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.939 | 0.000 | 0.000 | 16.212 | 8.462 | 11.795 | 0.000 | 0.000 | 0.181 | 2.198 | 0.000 | 0.000 | 0.000 | -0.910 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -29.326 | 0.000 | 0.000 | 3.582 | 8.366 | 12.471 | 0.000 | 0.000 | 0.437 | 6.427 | 0.000 | 0.000 | 0.000 | -1.957 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -16.342 | 0.000 | 0.000 | 2.784 | 3.079 | 3.598 | 0.000 | 0.000 | 0.257 | 7.728 | 0.000 | 0.000 | 0.000 | -1.104 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -607.953 | 0.000 | 0.000 | 10.998 | 3.975 | 658.131 | 0.000 | 0.000 | 0.616 | 0.000 | 0.000 | 0.000 | 0.000 | -2.968 | -62.800 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -238.155 | 0.000 | 0.000 | 182.228 | 14.273 | 14.341 | 65.490 | 0.000 | 1.022 | 0.001 | 0.000 | -25.669 | 0.000 | -5.328 | -8.201 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -806.126 | 0.000 | 0.000 | 538.455 | 110.171 | 148.998 | 87.252 | 0.000 | 2.970 | 0.000 | 0.000 | -34.004 | 0.000 | -15.347 | -32.370 |
ROOM_1_FLR_3 | 6.495 | -60.957 | 0.000 | -10.926 | 0.000 | 0.000 | 9.652 | 9.244 | 10.478 | 50.839 | 0.000 | 1.638 | 7.309 | 0.000 | -18.694 | 0.000 | -5.078 | -0.001 |
ROOM_2_FLR_3 | 10.078 | -47.392 | 0.000 | -11.294 | 0.000 | 0.000 | 9.566 | 9.243 | 10.477 | 38.200 | 0.000 | 1.503 | 4.715 | 0.000 | -19.665 | 0.000 | -5.430 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -362.438 | 0.000 | -14.956 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 256.794 | 0.000 | 2.970 | 1.980 | 0.000 | -150.835 | 0.000 | -38.896 | -0.001 |
ROOM_4_MULT19_FLR_3 | 25.377 | -315.457 | 0.000 | -150.601 | 0.000 | 0.000 | 182.663 | 110.415 | 195.050 | 101.279 | 0.000 | 8.749 | 0.002 | 0.000 | -106.562 | 0.000 | -36.487 | -14.425 |
ROOM_5_FLR_3 | 6.564 | -62.076 | 0.000 | -10.914 | 0.000 | 0.000 | 9.650 | 9.244 | 10.478 | 50.892 | 0.000 | 1.644 | 7.587 | 0.000 | -17.956 | 0.000 | -5.112 | -0.000 |
ROOM_6_FLR_3 | 9.944 | -47.652 | 0.000 | -11.326 | 0.000 | 0.000 | 9.562 | 9.243 | 10.477 | 37.461 | 0.000 | 1.501 | 4.455 | 0.000 | -18.261 | 0.000 | -5.404 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -204.753 | 0.000 | 0.000 | 113.811 | 91.336 | 0.000 | 42.971 | 0.000 | 1.352 | 0.003 | 0.000 | -23.255 | 0.000 | -5.996 | -15.466 |
ROOM_1_FLR_6 | 2.890 | -15.065 | 0.000 | -2.732 | 0.000 | 0.000 | 2.415 | 2.311 | 2.620 | 12.630 | 0.000 | 0.409 | 0.405 | 0.000 | -4.592 | 0.000 | -1.290 | -0.000 |
ROOM_2_FLR_6 | 4.101 | -11.952 | 0.000 | -2.815 | 0.000 | 0.000 | 2.396 | 2.311 | 2.619 | 9.506 | 0.000 | 0.373 | 0.000 | 0.000 | -4.822 | 0.000 | -1.375 | -0.342 |
ROOM_3_MULT9_FLR_6 | 5.356 | -90.396 | 0.000 | -17.563 | 0.000 | 0.000 | 21.686 | 13.076 | 23.098 | 63.776 | 0.000 | 2.032 | 6.979 | 0.000 | -21.326 | 0.000 | -6.717 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -456.248 | 0.000 | 0.000 | 314.932 | 31.154 | 175.857 | 9.542 | 0.000 | 0.625 | 0.000 | 0.000 | -14.689 | 0.000 | -3.563 | -57.609 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -494.290 | 0.000 | 0.000 | 314.388 | 31.154 | 175.857 | 9.317 | 0.000 | 0.625 | 0.000 | 0.000 | -15.138 | 0.000 | -3.589 | -18.324 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -644.570 | 0.000 | 0.000 | 28.078 | 12.972 | 550.372 | 23.545 | 0.000 | 0.560 | 42.619 | 0.000 | -10.365 | 0.000 | -3.212 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.033 | -105.635 | 0.000 | 0.000 | 30.258 | 24.166 | 0.000 | 20.695 | 0.000 | 0.563 | 42.951 | 0.000 | -10.401 | 0.000 | -2.631 | 0.000 |
Total Facility | 70.804 | -1013.386 | 0.070 | -4333.666 | 0.000 | 0.000 | 1956.707 | 783.183 | 2365.005 | 903.796 | 0.000 | 30.489 | 135.614 | 0.000 | -504.639 | 0.000 | -154.553 | -239.421 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-SEP-21:00 | 0.00 | 0.00 | 0.00 | -24598.54 | 0.00 | 0.00 | 5924.44 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2176.12 |
RETAIL_1_FLR_1 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | -3613.19 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4410.09 | 0.00 | 38.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1404.47 |
RETAIL_2_FLR_1 | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2348.79 | 0.00 | 0.00 | 697.61 | 615.12 | 752.15 | 0.00 | 0.00 | 35.40 | 248.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2140.54 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 88.47 | 399.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 15-JUN-18:40 | 0.00 | 0.00 | 0.00 | -1036.27 | 0.00 | 0.00 | 99.29 | 223.85 | 229.41 | 0.00 | 0.00 | 58.55 | 425.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39421.56 | 0.00 | 0.00 | 408.85 | 325.08 | 44299.38 | 0.00 | 0.00 | 120.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5732.56 |
CAFE_FLR_1 | 18-OCT-15:03 | 0.00 | 0.00 | 0.00 | -12805.43 | 0.00 | 0.00 | 4948.03 | 103.98 | 355.63 | 7539.62 | 0.00 | 108.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -250.69 |
LOBBY_FLR_1 | 07-AUG-21:10 | 0.00 | 0.00 | 0.00 | -43872.36 | 0.00 | 0.00 | 26439.97 | 6336.53 | 7389.94 | 828.72 | 0.00 | 456.68 | 2420.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 15-JUN-15:02 | 0.00 | -8532.26 | 0.00 | -671.53 | 0.00 | 0.00 | 235.27 | 199.23 | 200.18 | 8146.84 | 0.00 | 341.27 | 81.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 19-JUN-18:51 | 0.00 | -9329.39 | 0.00 | -819.07 | 0.00 | 0.00 | 280.69 | 633.19 | 484.60 | 1353.25 | 0.00 | 46.21 | 7350.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:15 | 0.00 | -43976.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.75 | 2548.95 | 50904.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -92.98 | -12187.70 |
ROOM_4_MULT19_FLR_3 | 14-JUN-08:11 | 0.00 | -59613.79 | 0.00 | -9787.77 | 0.00 | 0.00 | 1589.32 | 3739.35 | 8433.45 | 9586.98 | 0.00 | 501.58 | 45550.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 11-JUL-08:62 | 0.00 | -7528.94 | 0.00 | -673.55 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 7305.98 | 0.00 | 104.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -61.47 |
ROOM_6_FLR_3 | 20-MAY-08:32 | 0.00 | -8758.60 | 0.00 | -892.16 | 0.00 | 0.00 | 93.79 | 398.41 | 653.15 | 6951.94 | 0.00 | 0.00 | 1569.84 | 0.00 | -0.00 | 0.00 | -16.38 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:40 | 0.00 | 0.00 | 0.00 | -12546.98 | 0.00 | 0.00 | 4080.28 | 6639.35 | 0.00 | 2510.77 | 0.00 | 311.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -994.58 |
ROOM_1_FLR_6 | 15-JUN-15:02 | 0.00 | -2275.37 | 0.00 | -168.53 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 2020.71 | 0.00 | 84.79 | 179.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 19-JUN-18:51 | 0.00 | -2478.74 | 0.00 | -207.45 | 0.00 | 0.00 | 69.01 | 158.30 | 121.15 | 328.99 | 0.00 | 10.25 | 1998.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:02 | 0.00 | -10277.46 | 0.00 | -1097.39 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 7101.85 | 0.00 | 151.93 | 2868.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23863.20 | 0.00 | 0.00 | 15615.85 | 1992.02 | 6747.90 | 253.63 | 0.00 | 108.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -854.71 |
DINING_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -25047.95 | 0.00 | 0.00 | 15608.50 | 1992.02 | 6747.90 | 240.20 | 0.00 | 108.46 | 350.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31133.44 | 0.00 | 0.00 | 464.23 | 353.60 | 24259.91 | 2635.31 | 0.00 | 101.78 | 3318.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-12:50 | 0.00 | 0.00 | 0.00 | -6948.08 | 0.00 | 0.00 | 308.46 | 548.96 | 0.00 | 1960.11 | 0.00 | 151.15 | 3979.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-18:02 | 0.00 | -126220.85 | 0.00 | -216300.51 | 0.00 | 0.00 | 73662.93 | 54680.24 | 120482.43 | 43147.27 | 0.00 | 5668.43 | 44880.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-DEC-07:30 | 0.00 | 0.00 | 733.50 | 0.00 | 0.00 | 0.00 | 358.00 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1207.22 | 0.00 | -284.36 | -364.92 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-DEC-16:02 | 5768.19 | 255.84 | 0.00 | -255.84 | 0.00 | 0.00 | 293.98 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1580.70 | 0.00 | -445.23 | -4435.64 |
ROOM_2_FLR_3 | 27-DEC-09:02 | 5795.53 | 254.19 | 0.00 | -254.19 | 0.00 | 0.00 | 108.88 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1300.87 | 0.00 | -523.41 | -4846.17 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 09-DEC-16:03 | 32767.67 | 5363.30 | 0.00 | -5363.30 | 0.00 | 0.00 | 2740.76 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2403.03 | 0.00 | -10980.35 | -29048.22 |
ROOM_5_FLR_3 | 26-DEC-16:02 | 5616.50 | 254.55 | 0.00 | -254.55 | 0.00 | 0.00 | 293.98 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.50 | 0.00 | -444.73 | -4168.66 |
ROOM_6_FLR_3 | 26-DEC-16:02 | 5629.36 | 252.95 | 0.00 | -252.95 | 0.00 | 0.00 | 293.99 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1719.79 | 0.00 | -444.08 | -4158.84 |
CORRIDOR_FLR_3 | 27-DEC-07:30 | 0.00 | 0.00 | 194.41 | 0.00 | 0.00 | 0.00 | 2771.54 | 4149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3543.48 | 0.00 | -799.67 | -2772.40 |
ROOM_1_FLR_6 | 26-DEC-16:02 | 1717.20 | 64.50 | 0.00 | -64.50 | 0.00 | 0.00 | 73.50 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -389.74 | 0.00 | -111.92 | -1388.88 |
ROOM_2_FLR_6 | 27-DEC-09:02 | 1726.81 | 63.99 | 0.00 | -63.99 | 0.00 | 0.00 | 27.22 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -314.61 | 0.00 | -131.43 | -1499.50 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:02 | 7884.21 | 468.81 | 0.00 | -468.81 | 0.00 | 0.00 | 647.47 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1986.82 | 0.00 | -530.59 | -6737.34 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-DEC-07:10 | 0.00 | 0.00 | 1002.49 | 0.00 | 0.00 | 0.00 | 733.32 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1575.69 | 0.00 | -357.05 | -900.99 |
Total Facility | 26-DEC-16:02 | -21481.21 | 93681.90 | 48.98 | -93681.90 | 0.00 | 0.00 | 59148.26 | 17287.14 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43430.76 | 0.00 | -12502.89 | -72982.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.0360 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.9083 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.5180 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8875 | 2.8875 | 1.3456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3632 | 0.3632 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2680 | 0.2680 | 0.1249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2368 | 0.2368 | 0.1103 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1404 | 0.1404 | 0.0654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7646 | 3.7646 | 1.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5733 | 1.5733 | 0.7332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4186 | 5.4186 | 2.5251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7397 | 1.7397 | 0.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5293 | 2.5293 | 1.1786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6487 | 2.6487 | 1.2343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5799 | 2.5799 | 1.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8860 | 0.8860 | 0.4129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.0360 | 24.9083 | 25.0360 | 11.6668 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4438 | 1.4438 | 1.3456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1816 | 0.1816 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1340 | 0.1340 | 0.1249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1184 | 0.1184 | 0.1103 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0702 | 0.0702 | 0.0654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8823 | 1.8823 | 1.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7867 | 0.7867 | 0.7332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7093 | 2.7093 | 2.5251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8698 | 0.8698 | 0.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2646 | 1.2646 | 1.1786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3243 | 1.3243 | 1.2343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2900 | 1.2900 | 1.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4430 | 0.4430 | 0.4129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.5180 | 11.6668 | 11.6668 | 11.6668 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 522.67 |
Number of hours not met | 522.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 786.14 | 210090.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1392.86 | 157627.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.18 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.01 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 599.50 | 50793.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 83.94 | 4108.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 133.96 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.73 | 2844.13 | 248619.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.47 | 1891.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.18 | 1201.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.92 | 5638.93 |
Natural Gas | 1788.84 | 5419.10 |
Additional | 0.00 | 0.00 |
Total | 3508.76 | 11058.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.03 |
Space Heating | 0.00 |
Space Cooling | 122.77 |
Fans (All) | 52.84 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 497.03 |
Subtotal | 497.03 |
Natural Gas [MJ/m2] | |
Space Heating | 69.29 |
Service Water Heating | 250.69 |
Miscellaneous (All) | 477.65 |
Subtotal | 477.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.08 |
Space Heating | 7.11 |
Space Cooling | 12.60 |
Fans (All) | 5.42 |
Service Water Heating | 26.54 |
Receptacle Equipment | 31.17 |
Miscellaneous | 10.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7848.00 | 912.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7848.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 912.00 | 0.00 | 0.00 | 0.00 |
Average | 8716.78 | 43.22 | 0.00 | 0.00 | 0.00 |
Sum | 191769.17 | 950.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8161.00 | 599.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8312.33 | 447.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7518.00 | 1242.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8629.00 | 131.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8711.67 | 48.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8289.33 | 470.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8323.00 | 437.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7518.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1242.00 | 0.00 | 0.00 | 0.00 |
Average | 8602.11 | 157.89 | 0.00 | 0.00 | 0.00 |
Sum | 189246.50 | 3473.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58789.00 | 367.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 639974.83 | 70442.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1957906.17 | 157522.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4151.50 | 2.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4148.67 | 5.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1147131.50 | 98583.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1153422.83 | 92292.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108235.00 | 34.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1957906.17 | 157522.83 | 0.00 | 0.00 | 0.00 |
Average | 269830.09 | 19056.95 | 0.00 | 0.00 | 0.00 |
Sum | 5936262.00 | 419253.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331764E+11 | 18256.23 | 05-JAN-22:00 | 5.60 | -2.2 | 0.810199E+10 | 4837.09 | 25-JAN-23:19 | 5.77 | 3.79 |
February | 0.260886E+11 | 15270.92 | 01-FEB-22:00 | 1.70 | -2.7 | 0.681504E+10 | 4836.99 | 02-FEB-22:10 | 4.03 | -2.0 |
March | 0.262845E+11 | 12080.10 | 01-MAR-21:00 | 1.70 | -3.0 | 0.704121E+10 | 4542.32 | 01-MAR-22:10 | 1.02 | -3.3 |
April | 0.265031E+11 | 13003.62 | 30-APR-10:33 | 24.07 | 13.08 | 0.686793E+10 | 4428.95 | 07-APR-22:10 | 24.07 | 13.08 |
May | 0.291438E+11 | 13595.30 | 21-MAY-10:33 | 29.47 | 14.38 | 0.732081E+10 | 4562.35 | 12-MAY-22:10 | 29.47 | 14.38 |
June | 0.300115E+11 | 14313.13 | 15-JUN-18:10 | 35.92 | 14.47 | 0.731773E+10 | 4708.43 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.354402E+11 | 18929.20 | 19-JUL-21:00 | 23.90 | 20.39 | 0.808519E+10 | 4837.16 | 05-JUL-22:10 | 23.90 | 20.39 |
August | 0.403385E+11 | 22181.42 | 24-AUG-21:00 | 26.70 | 16.71 | 0.823599E+10 | 4837.25 | 22-AUG-00:10 | 26.70 | 16.71 |
September | 0.433066E+11 | 24598.19 | 22-SEP-21:00 | 25.00 | 17.90 | 0.797363E+10 | 4837.39 | 19-SEP-04:10 | 25.00 | 17.90 |
October | 0.440540E+11 | 24391.06 | 05-OCT-21:00 | 23.30 | 16.16 | 0.823433E+10 | 4837.31 | 10-OCT-21:19 | 13.87 | 9.12 |
November | 0.407727E+11 | 23793.71 | 10-NOV-22:00 | 15.60 | 8.38 | 0.796130E+10 | 4837.46 | 01-NOV-01:10 | 15.60 | 8.38 |
December | 0.380905E+11 | 22070.18 | 01-DEC-22:00 | 7.20 | 2.26 | 0.821483E+10 | 4837.20 | 13-DEC-00:10 | 6.47 | 5.55 |
Annual Sum or Average | 0.413210E+12 | 0.921700E+11 | ||||||||
Minimum of Months | 0.260886E+11 | 12080.10 | 1.70 | -3.0 | 0.681504E+10 | 4428.95 | 1.02 | -3.3 | ||
Maximum of Months | 0.440540E+11 | 24598.19 | 35.92 | 20.39 | 0.823599E+10 | 4837.46 | 29.47 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279134E+10 | 2799.51 | 12-JAN-13:50 | 18.03 | 9.58 | 0.666560E+09 | 442.84 | 12-JAN-22:19 | 9.47 | 5.03 |
February | 0.276311E+10 | 2851.69 | 07-FEB-13:30 | 20.30 | 9.54 | 0.611589E+09 | 466.65 | 06-FEB-22:30 | 20.30 | 9.54 |
March | 0.309067E+10 | 2228.87 | 16-MAR-13:20 | 22.40 | 9.11 | 0.687661E+09 | 468.81 | 16-MAR-21:19 | 16.83 | 5.98 |
April | 0.361471E+10 | 2346.07 | 03-APR-14:10 | 26.70 | 11.67 | 0.719068E+09 | 491.84 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.411320E+10 | 2333.00 | 31-MAY-18:04 | 30.92 | 15.25 | 0.785001E+09 | 491.84 | 17-MAY-22:10 | 30.92 | 15.25 |
June | 0.460300E+10 | 2725.09 | 15-JUN-18:17 | 35.73 | 14.50 | 0.792712E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.478593E+10 | 2709.08 | 26-JUL-18:04 | 33.77 | 19.75 | 0.817459E+09 | 491.84 | 05-JUL-22:10 | 33.77 | 19.75 |
August | 0.484163E+10 | 2877.87 | 27-AUG-12:00 | 33.30 | 15.93 | 0.815007E+09 | 491.86 | 22-AUG-00:10 | 33.30 | 15.93 |
September | 0.486750E+10 | 3496.90 | 20-SEP-12:50 | 32.12 | 17.95 | 0.779899E+09 | 491.84 | 19-SEP-23:10 | 32.12 | 17.95 |
October | 0.452030E+10 | 3613.32 | 18-OCT-13:00 | 27.80 | 18.14 | 0.765066E+09 | 491.85 | 05-OCT-23:49 | 27.80 | 18.14 |
November | 0.346183E+10 | 3375.30 | 10-NOV-12:00 | 21.10 | 12.09 | 0.678024E+09 | 491.75 | 09-NOV-22:19 | 21.10 | 12.09 |
December | 0.253421E+10 | 2520.78 | 16-DEC-13:30 | 14.45 | 3.99 | 0.657238E+09 | 429.57 | 15-DEC-22:30 | 14.45 | 3.99 |
Annual Sum or Average | 0.459874E+11 | 0.877528E+10 | ||||||||
Minimum of Months | 0.253421E+10 | 2228.87 | 14.45 | 3.99 | 0.611589E+09 | 429.57 | 9.47 | 3.99 | ||
Maximum of Months | 0.486750E+10 | 3613.32 | 35.73 | 19.75 | 0.817459E+09 | 491.86 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261608E+10 | 1374.91 | 12-JAN-22:00 | 10.60 | 5.73 | 0.879951E+09 | 569.52 | 04-JAN-22:30 | 10.60 | 5.73 |
February | 0.243068E+10 | 1538.40 | 21-FEB-22:00 | 14.40 | 4.35 | 0.805743E+09 | 569.54 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.276301E+10 | 1607.72 | 16-MAR-21:00 | 17.20 | 5.94 | 0.906705E+09 | 569.55 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.303213E+10 | 1944.93 | 28-APR-20:55 | 22.80 | 12.84 | 0.911325E+09 | 569.66 | 17-APR-01:10 | 22.80 | 12.84 |
May | 0.348630E+10 | 2137.56 | 19-MAY-21:00 | 30.00 | 13.65 | 0.959103E+09 | 569.58 | 18-MAY-00:10 | 30.00 | 13.65 |
June | 0.374114E+10 | 2348.67 | 15-JUN-21:00 | 33.30 | 13.72 | 0.937155E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.386524E+10 | 2302.18 | 26-JUL-21:00 | 28.90 | 18.16 | 0.965124E+09 | 569.55 | 05-JUL-22:10 | 28.90 | 18.16 |
August | 0.380827E+10 | 2338.14 | 07-AUG-21:00 | 31.70 | 16.85 | 0.968299E+09 | 569.57 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.359647E+10 | 2218.01 | 20-SEP-20:10 | 25.40 | 15.25 | 0.934777E+09 | 569.58 | 19-SEP-04:10 | 25.40 | 15.25 |
October | 0.329043E+10 | 2143.20 | 05-OCT-20:10 | 23.80 | 16.56 | 0.951315E+09 | 569.56 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.275467E+10 | 1804.36 | 09-NOV-22:00 | 18.90 | 11.06 | 0.884121E+09 | 569.55 | 08-NOV-23:10 | 18.90 | 11.06 |
December | 0.255410E+10 | 1215.61 | 07-DEC-21:00 | 9.40 | 3.58 | 0.867309E+09 | 569.51 | 07-DEC-22:19 | 5.73 | 1.70 |
Annual Sum or Average | 0.379385E+11 | 0.109709E+11 | ||||||||
Minimum of Months | 0.243068E+10 | 1215.61 | 9.40 | 3.58 | 0.805743E+09 | 569.51 | 5.73 | 1.70 | ||
Maximum of Months | 0.386524E+10 | 2348.67 | 33.30 | 18.16 | 0.968299E+09 | 569.66 | 30.00 | 18.16 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185457E+10 | 908.94 | 03-JAN-21:00 | 14.40 | 6.79 | 0.160230E+09 | 104.03 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.175426E+10 | 966.64 | 20-FEB-11:33 | 20.37 | 8.19 | 0.148061E+09 | 107.18 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.204847E+10 | 1007.26 | 16-MAR-18:10 | 19.82 | 7.14 | 0.169145E+09 | 110.39 | 16-MAR-21:10 | 17.02 | 5.96 |
April | 0.231323E+10 | 1193.80 | 30-APR-10:33 | 24.07 | 13.08 | 0.178611E+09 | 120.45 | 21-APR-21:19 | 24.07 | 13.08 |
May | 0.275129E+10 | 1766.05 | 31-MAY-20:00 | 29.40 | 14.60 | 0.198022E+09 | 120.45 | 24-MAY-21:00 | 29.40 | 14.60 |
June | 0.317267E+10 | 2140.36 | 15-JUN-20:00 | 33.90 | 14.00 | 0.198151E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.330712E+10 | 2097.30 | 03-JUL-20:00 | 28.30 | 19.12 | 0.204179E+09 | 120.46 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.312319E+10 | 2065.22 | 07-AUG-20:00 | 31.70 | 17.36 | 0.203839E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.276360E+10 | 1738.16 | 22-SEP-20:00 | 26.10 | 18.64 | 0.194207E+09 | 120.46 | 20-SEP-22:10 | 26.10 | 18.64 |
October | 0.248519E+10 | 1528.84 | 05-OCT-20:00 | 23.90 | 16.65 | 0.188855E+09 | 120.45 | 04-OCT-21:19 | 23.90 | 16.65 |
November | 0.202065E+10 | 1065.86 | 10-NOV-11:33 | 20.93 | 12.02 | 0.165585E+09 | 113.87 | 10-NOV-22:10 | 15.50 | 8.35 |
December | 0.173201E+10 | 891.68 | 10-DEC-11:35 | 15.93 | 7.48 | 0.158188E+09 | 101.54 | 15-DEC-22:10 | 14.32 | 4.61 |
Annual Sum or Average | 0.293263E+11 | 0.216707E+10 | ||||||||
Minimum of Months | 0.173201E+10 | 891.68 | 14.40 | 6.79 | 0.148061E+09 | 101.54 | 11.93 | 4.61 | ||
Maximum of Months | 0.330712E+10 | 2140.36 | 33.90 | 19.12 | 0.204179E+09 | 120.46 | 29.40 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103777E+10 | 525.16 | 01-JAN-11:35 | 13.87 | 8.54 | 0.120533E+09 | 77.03 | 03-JAN-22:30 | 11.70 | 5.76 |
February | 0.992650E+09 | 567.98 | 20-FEB-11:33 | 20.37 | 8.19 | 0.111377E+09 | 79.59 | 07-FEB-23:10 | 20.37 | 8.19 |
March | 0.116925E+10 | 586.91 | 16-MAR-10:33 | 20.03 | 8.28 | 0.126990E+09 | 81.82 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.133299E+10 | 696.20 | 30-APR-10:33 | 24.07 | 13.08 | 0.134171E+09 | 89.62 | 21-APR-22:10 | 24.07 | 13.08 |
May | 0.155105E+10 | 794.85 | 31-MAY-21:00 | 28.30 | 13.66 | 0.149406E+09 | 92.66 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.171859E+10 | 1036.18 | 15-JUN-18:40 | 35.37 | 14.55 | 0.151487E+09 | 92.66 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.178410E+10 | 1028.75 | 03-JUL-18:30 | 34.45 | 19.49 | 0.156246E+09 | 92.66 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.170572E+10 | 1003.88 | 07-AUG-21:00 | 31.70 | 16.85 | 0.155320E+09 | 92.66 | 21-AUG-23:49 | 25.23 | 16.56 |
September | 0.154622E+10 | 769.12 | 22-SEP-21:00 | 25.00 | 17.90 | 0.146794E+09 | 92.66 | 20-SEP-22:10 | 25.00 | 17.90 |
October | 0.142382E+10 | 726.12 | 05-OCT-10:33 | 27.60 | 18.63 | 0.141925E+09 | 92.66 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.114926E+10 | 623.42 | 10-NOV-11:33 | 20.93 | 12.02 | 0.124287E+09 | 84.38 | 09-NOV-22:30 | 20.93 | 12.02 |
December | 0.930462E+09 | 521.17 | 10-DEC-11:35 | 15.93 | 7.48 | 0.119372E+09 | 75.42 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.163419E+11 | 0.163791E+10 | ||||||||
Minimum of Months | 0.930462E+09 | 521.17 | 13.87 | 7.48 | 0.111377E+09 | 75.42 | 11.70 | 4.57 | ||
Maximum of Months | 0.178410E+10 | 1036.18 | 35.37 | 19.49 | 0.156246E+09 | 92.66 | 28.43 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490988E+11 | 37438.29 | 12-JAN-21:00 | 12.80 | 7.31 | 0.605064E+09 | 381.75 | 03-JAN-22:10 | 12.80 | 7.31 |
February | 0.448877E+11 | 37785.75 | 21-FEB-20:55 | 15.00 | 4.44 | 0.548395E+09 | 381.73 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.503950E+11 | 37928.62 | 16-MAR-20:00 | 17.20 | 5.94 | 0.610192E+09 | 381.73 | 17-MAR-21:10 | 5.37 | -0.8 |
April | 0.501924E+11 | 38706.67 | 28-APR-20:00 | 25.00 | 12.84 | 0.594253E+09 | 381.72 | 18-APR-21:10 | 25.00 | 12.84 |
May | 0.530501E+11 | 39027.30 | 30-MAY-20:00 | 28.90 | 14.28 | 0.616966E+09 | 381.76 | 19-MAY-21:10 | 28.90 | 14.28 |
June | 0.523598E+11 | 39420.49 | 15-JUN-20:00 | 33.90 | 14.00 | 0.599537E+09 | 381.84 | 27-JUN-21:10 | 28.62 | 16.18 |
July | 0.538440E+11 | 39357.69 | 03-JUL-20:00 | 28.30 | 19.12 | 0.617183E+09 | 381.83 | 28-JUL-21:10 | 29.03 | 16.95 |
August | 0.537544E+11 | 39295.16 | 04-AUG-20:00 | 33.30 | 17.89 | 0.618093E+09 | 381.85 | 22-AUG-21:10 | 29.22 | 13.60 |
September | 0.514534E+11 | 38965.51 | 20-SEP-20:00 | 25.60 | 15.27 | 0.595841E+09 | 381.87 | 12-SEP-21:10 | 25.60 | 15.27 |
October | 0.516907E+11 | 38739.25 | 05-OCT-20:00 | 23.90 | 16.65 | 0.612622E+09 | 381.82 | 31-OCT-21:10 | 10.60 | 4.71 |
November | 0.484825E+11 | 38077.98 | 09-NOV-21:00 | 20.00 | 11.27 | 0.588590E+09 | 381.79 | 09-NOV-22:10 | 18.53 | 10.92 |
December | 0.487410E+11 | 37236.48 | 15-DEC-21:00 | 14.40 | 4.76 | 0.603907E+09 | 381.74 | 29-DEC-22:10 | 2.80 | -0.7 |
Annual Sum or Average | 0.607950E+12 | 0.721064E+10 | ||||||||
Minimum of Months | 0.448877E+11 | 37236.48 | 12.80 | 4.44 | 0.548395E+09 | 381.72 | 2.80 | -0.8 | ||
Maximum of Months | 0.538440E+11 | 39420.49 | 33.90 | 19.12 | 0.618093E+09 | 381.87 | 29.22 | 16.95 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172864E+11 | 11279.27 | 01-JAN-11:00 | 12.80 | 8.11 | 0.103671E+11 | 6461.80 | 14-JAN-02:20 | 8.50 | 3.32 |
February | 0.160969E+11 | 11297.62 | 20-FEB-13:00 | 21.10 | 8.39 | 0.947785E+10 | 6462.31 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.175555E+11 | 10186.82 | 14-MAR-15:03 | 23.98 | 9.90 | 0.105889E+11 | 6462.44 | 15-MAR-22:10 | 19.32 | 7.27 |
April | 0.187398E+11 | 11125.73 | 19-APR-21:10 | 28.12 | 12.29 | 0.104404E+11 | 6463.25 | 17-APR-01:10 | 28.12 | 12.29 |
May | 0.205791E+11 | 11479.64 | 19-MAY-21:10 | 29.90 | 13.55 | 0.108852E+11 | 6462.63 | 17-MAY-22:10 | 29.90 | 13.55 |
June | 0.218875E+11 | 12083.12 | 15-JUN-21:10 | 32.57 | 13.55 | 0.106148E+11 | 6462.62 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.227431E+11 | 12005.19 | 25-JUL-21:10 | 31.42 | 17.57 | 0.109352E+11 | 6462.52 | 21-JUL-22:10 | 31.42 | 17.57 |
August | 0.230000E+11 | 12428.58 | 07-AUG-21:10 | 31.25 | 17.07 | 0.109770E+11 | 6462.62 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.227376E+11 | 12257.79 | 19-SEP-15:04 | 33.40 | 16.39 | 0.106115E+11 | 6462.69 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.220248E+11 | 12804.85 | 18-OCT-15:03 | 28.90 | 17.08 | 0.108687E+11 | 6462.63 | 05-OCT-22:10 | 28.90 | 17.08 |
November | 0.187473E+11 | 12653.76 | 11-NOV-11:00 | 16.10 | 7.51 | 0.102430E+11 | 6462.35 | 08-NOV-23:10 | 16.10 | 7.51 |
December | 0.167543E+11 | 10935.50 | 16-DEC-13:30 | 14.45 | 3.99 | 0.102308E+11 | 6461.79 | 16-DEC-02:20 | 14.45 | 3.99 |
Annual Sum or Average | 0.238152E+12 | 0.126240E+12 | ||||||||
Minimum of Months | 0.160969E+11 | 10186.82 | 12.80 | 3.99 | 0.947785E+10 | 6461.79 | 8.50 | 3.32 | ||
Maximum of Months | 0.230000E+11 | 12804.85 | 33.40 | 17.57 | 0.109770E+11 | 6463.25 | 31.42 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577892E+11 | 31771.73 | 03-JAN-22:10 | 12.43 | 6.06 | 0.312569E+11 | 19184.95 | 14-JAN-02:20 | 8.50 | 3.32 |
February | 0.534594E+11 | 33210.59 | 07-FEB-22:10 | 15.10 | 7.63 | 0.284666E+11 | 19185.64 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.601762E+11 | 34010.32 | 16-MAR-21:10 | 17.02 | 5.96 | 0.317251E+11 | 19185.76 | 15-MAR-22:10 | 17.02 | 5.96 |
April | 0.646698E+11 | 37980.93 | 21-APR-21:10 | 24.90 | 9.61 | 0.311020E+11 | 19189.54 | 17-APR-01:10 | 24.90 | 9.61 |
May | 0.726460E+11 | 40950.48 | 31-MAY-21:10 | 28.13 | 13.59 | 0.323464E+11 | 19186.04 | 17-MAY-22:10 | 28.13 | 13.59 |
June | 0.762981E+11 | 43451.00 | 15-JUN-21:10 | 32.57 | 13.55 | 0.315172E+11 | 19186.01 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.792041E+11 | 43102.40 | 26-JUL-21:10 | 28.62 | 18.19 | 0.324684E+11 | 19185.92 | 19-JUL-22:10 | 28.62 | 18.19 |
August | 0.786320E+11 | 43867.01 | 07-AUG-21:10 | 31.25 | 17.07 | 0.326149E+11 | 19186.03 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.748512E+11 | 41985.93 | 21-SEP-21:10 | 26.10 | 17.46 | 0.315255E+11 | 19186.12 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.712067E+11 | 41263.54 | 05-OCT-21:10 | 23.22 | 16.17 | 0.324061E+11 | 19186.05 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.606808E+11 | 37530.55 | 09-NOV-22:10 | 18.53 | 10.92 | 0.308457E+11 | 19185.94 | 01-NOV-01:10 | 18.53 | 10.92 |
December | 0.565052E+11 | 30112.27 | 15-DEC-22:10 | 14.32 | 4.61 | 0.309960E+11 | 19184.92 | 16-DEC-02:20 | 10.60 | 3.59 |
Annual Sum or Average | 0.806119E+12 | 0.377271E+12 | ||||||||
Minimum of Months | 0.534594E+11 | 30112.27 | 12.43 | 4.61 | 0.284666E+11 | 19184.92 | 8.50 | 3.32 | ||
Maximum of Months | 0.792041E+11 | 43867.01 | 32.57 | 18.19 | 0.326149E+11 | 19189.54 | 28.62 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239894E+09 | 2156.47 | 12-JAN-16:02 | 18.72 | 10.12 | 96588660.68 | 56.69 | 01-JAN-05:19 | 18.72 | 10.12 |
February | 0.369314E+09 | 2237.97 | 20-FEB-16:02 | 23.12 | 8.59 | 87800840.01 | 56.69 | 06-FEB-22:40 | 23.12 | 8.59 |
March | 0.671185E+09 | 2231.18 | 16-MAR-15:02 | 22.70 | 8.66 | 97928253.31 | 56.69 | 16-MAR-21:19 | 16.83 | 5.98 |
April | 0.147507E+10 | 2263.48 | 16-APR-15:02 | 29.50 | 11.50 | 95616666.82 | 56.69 | 17-APR-03:20 | 15.73 | 11.53 |
May | 0.218261E+10 | 2268.08 | 08-MAY-15:02 | 32.20 | 16.28 | 99453379.70 | 56.70 | 21-MAY-23:40 | 21.30 | 15.38 |
June | 0.267273E+10 | 2300.96 | 15-JUN-15:02 | 38.22 | 15.87 | 96765710.20 | 59.75 | 16-JUN-21:10 | 32.52 | 14.90 |
July | 0.267792E+10 | 2262.32 | 27-JUL-18:02 | 32.52 | 19.86 | 99478472.54 | 56.70 | 10-JUL-22:40 | 32.52 | 19.86 |
August | 0.252058E+10 | 2260.14 | 28-AUG-18:02 | 29.03 | 17.18 | 99602136.13 | 56.70 | 05-AUG-00:49 | 29.03 | 17.18 |
September | 0.229209E+10 | 2267.09 | 01-SEP-18:02 | 31.13 | 18.07 | 96254344.71 | 56.70 | 12-SEP-21:49 | 25.78 | 17.09 |
October | 0.158406E+10 | 2252.17 | 31-OCT-15:02 | 21.60 | 7.74 | 98913255.00 | 56.70 | 05-OCT-21:49 | 21.60 | 7.74 |
November | 0.637916E+09 | 2238.38 | 09-NOV-16:02 | 23.22 | 12.98 | 94518442.27 | 56.69 | 01-NOV-01:10 | 23.22 | 12.98 |
December | 0.154077E+09 | 2129.84 | 16-DEC-16:02 | 14.72 | 4.08 | 96308480.80 | 56.69 | 13-DEC-01:19 | 14.72 | 4.08 |
Annual Sum or Average | 0.174774E+11 | 0.115923E+10 | ||||||||
Minimum of Months | 0.154077E+09 | 2129.84 | 14.72 | 4.08 | 87800840.01 | 56.69 | 14.72 | 4.08 | ||
Maximum of Months | 0.267792E+10 | 2300.96 | 38.22 | 19.86 | 99602136.13 | 59.75 | 32.52 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58008006.31 | 2089.20 | 12-JAN-16:02 | 18.72 | 10.12 | 94977786.25 | 56.69 | 06-JAN-04:19 | 18.72 | 10.12 |
February | 0.110521E+09 | 2177.64 | 20-FEB-16:02 | 23.12 | 8.59 | 87350193.20 | 63.25 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.299811E+09 | 2180.15 | 16-MAR-15:02 | 22.70 | 8.66 | 99890768.64 | 69.08 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.115288E+10 | 2419.25 | 06-APR-18:11 | 14.63 | 6.39 | 99203883.76 | 75.67 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.200754E+10 | 2393.19 | 20-MAY-08:51 | 26.70 | 12.19 | 0.102558E+09 | 79.51 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.258505E+10 | 2537.13 | 19-JUN-18:51 | 27.20 | 19.20 | 99202369.52 | 79.56 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.255885E+10 | 2253.90 | 12-JUL-08:11 | 26.33 | 18.31 | 0.102060E+09 | 76.27 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.227692E+10 | 2331.34 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102489E+09 | 80.26 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.181368E+10 | 2261.66 | 29-SEP-21:51 | 19.40 | 9.20 | 0.100216E+09 | 78.83 | 13-SEP-21:10 | 19.40 | 9.20 |
October | 0.944443E+09 | 2230.57 | 05-OCT-21:51 | 22.80 | 16.23 | 0.103854E+09 | 80.81 | 05-OCT-21:10 | 22.80 | 16.23 |
November | 0.206661E+09 | 2144.30 | 07-NOV-16:02 | 21.52 | 10.29 | 94468693.77 | 68.53 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 30305811.91 | 2066.90 | 16-DEC-16:02 | 14.72 | 4.08 | 94467969.21 | 56.69 | 21-DEC-05:19 | 1.13 | -2.2 |
Annual Sum or Average | 0.140447E+11 | 0.118074E+10 | ||||||||
Minimum of Months | 30305811.91 | 2066.90 | 14.63 | 4.08 | 87350193.20 | 56.69 | 1.13 | -2.2 | ||
Maximum of Months | 0.258505E+10 | 2537.13 | 27.20 | 19.20 | 0.103854E+09 | 80.81 | 27.07 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232867E+09 | 489.13 | 12-JAN-14:25 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.243021E+09 | 464.77 | 07-FEB-13:40 | 20.20 | 9.50 | 0.00 | 0.00 | 01-FEB-00:10 | 20.20 | 9.50 |
March | 0.226574E+09 | 364.40 | 16-MAR-12:50 | 22.02 | 8.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.02 | 8.91 |
April | 0.341563E+09 | 348.40 | 04-APR-13:30 | 26.95 | 10.78 | 0.00 | 0.00 | 01-APR-00:10 | 26.95 | 10.78 |
May | 0.431288E+09 | 335.72 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.545288E+09 | 380.10 | 15-JUN-20:20 | 33.70 | 13.91 | 0.00 | 0.00 | 01-JUN-00:10 | 33.70 | 13.91 |
July | 0.573455E+09 | 382.47 | 02-JUL-20:30 | 33.35 | 16.67 | 0.00 | 0.00 | 01-JUL-00:10 | 33.35 | 16.67 |
August | 0.591601E+09 | 406.38 | 27-AUG-13:40 | 34.40 | 16.46 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.46 |
September | 0.639769E+09 | 513.66 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.565057E+09 | 578.65 | 22-OCT-13:15 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.386327E+09 | 540.08 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.188950E+09 | 407.54 | 16-DEC-13:40 | 14.63 | 4.10 | 0.00 | 0.00 | 01-DEC-00:10 | 14.63 | 4.10 |
Annual Sum or Average | 0.496576E+10 | 0.00 | ||||||||
Minimum of Months | 0.188950E+09 | 335.72 | 14.63 | 4.10 | 0.00 | 0.00 | 14.63 | 4.10 | ||
Maximum of Months | 0.639769E+09 | 578.65 | 34.40 | 16.80 | 0.00 | 0.00 | 34.40 | 16.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93178365.77 | 731.23 | 13-JAN-19:02 | 13.12 | 6.39 | 95565782.82 | 56.69 | 03-JAN-22:40 | 13.12 | 6.39 |
February | 0.145719E+09 | 793.17 | 22-FEB-16:01 | 22.62 | 8.47 | 87175706.02 | 67.75 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.255283E+09 | 824.48 | 15-MAR-21:52 | 19.40 | 7.29 | 98265109.59 | 70.51 | 09-MAR-22:10 | 19.40 | 7.29 |
April | 0.511556E+09 | 847.98 | 21-APR-18:02 | 29.95 | 11.64 | 97316106.51 | 72.66 | 25-APR-21:49 | 18.22 | 11.64 |
May | 0.765302E+09 | 893.16 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101159E+09 | 75.07 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.944938E+09 | 913.18 | 14-JUN-08:11 | 27.93 | 12.20 | 97934302.19 | 75.32 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.959753E+09 | 877.44 | 06-JUL-08:61 | 26.38 | 18.59 | 0.101064E+09 | 71.75 | 18-JUL-21:00 | 19.40 | 19.40 |
August | 0.851762E+09 | 867.60 | 29-AUG-21:51 | 22.20 | 14.62 | 0.101359E+09 | 77.33 | 14-AUG-21:10 | 22.20 | 14.62 |
September | 0.669816E+09 | 852.08 | 20-SEP-15:02 | 33.30 | 17.34 | 98641692.19 | 74.02 | 13-SEP-21:10 | 33.30 | 17.34 |
October | 0.461171E+09 | 850.99 | 04-OCT-18:02 | 28.22 | 19.05 | 0.101393E+09 | 75.09 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.179697E+09 | 805.35 | 09-NOV-16:02 | 23.22 | 12.98 | 93613894.77 | 68.60 | 09-NOV-22:49 | 17.07 | 10.34 |
December | 68675902.85 | 735.63 | 16-DEC-09:02 | 8.48 | 2.42 | 95293070.55 | 56.69 | 13-DEC-00:20 | 8.48 | 2.42 |
Annual Sum or Average | 0.590685E+10 | 0.116878E+10 | ||||||||
Minimum of Months | 68675902.85 | 731.23 | 8.48 | 2.42 | 87175706.02 | 56.69 | 8.48 | 2.42 | ||
Maximum of Months | 0.959753E+09 | 913.18 | 33.30 | 19.05 | 0.101393E+09 | 77.33 | 33.30 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219194E+09 | 1894.25 | 03-JAN-16:02 | 20.10 | 7.84 | 96799747.32 | 56.69 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.413712E+09 | 1953.88 | 20-FEB-16:02 | 23.12 | 8.59 | 88226846.09 | 56.69 | 06-FEB-22:00 | 23.12 | 8.59 |
March | 0.685361E+09 | 1955.98 | 16-MAR-15:02 | 22.70 | 8.66 | 98329777.31 | 56.69 | 15-MAR-21:19 | 22.70 | 8.66 |
April | 0.154456E+10 | 1995.71 | 21-APR-15:02 | 32.02 | 15.38 | 95871655.62 | 56.69 | 17-APR-02:00 | 32.02 | 15.38 |
May | 0.223528E+10 | 2031.62 | 20-MAY-08:62 | 24.37 | 10.75 | 99338966.15 | 56.69 | 24-MAY-22:40 | 19.80 | 15.99 |
June | 0.275280E+10 | 2047.95 | 15-JUN-08:62 | 29.78 | 13.66 | 96452413.37 | 59.00 | 16-JUN-21:10 | 32.52 | 14.90 |
July | 0.274868E+10 | 2050.72 | 11-JUL-08:62 | 27.48 | 17.81 | 99312013.11 | 56.70 | 10-JUL-23:30 | 27.48 | 17.81 |
August | 0.258435E+10 | 2042.55 | 06-AUG-08:62 | 26.97 | 17.40 | 99368393.56 | 56.70 | 07-AUG-22:30 | 27.55 | 18.81 |
September | 0.231340E+10 | 2030.95 | 05-SEP-08:62 | 21.38 | 16.86 | 96075069.11 | 56.70 | 20-SEP-22:00 | 25.60 | 16.61 |
October | 0.149460E+10 | 2012.38 | 05-OCT-08:62 | 23.17 | 17.04 | 98846788.71 | 56.70 | 05-OCT-21:00 | 22.80 | 16.23 |
November | 0.609889E+09 | 1962.01 | 09-NOV-16:02 | 23.22 | 12.98 | 94745574.72 | 56.69 | 01-NOV-01:10 | 23.22 | 12.98 |
December | 0.165725E+09 | 1896.00 | 16-DEC-09:02 | 8.48 | 2.42 | 96492278.88 | 56.69 | 28-DEC-05:19 | -3.2 | -3.9 |
Annual Sum or Average | 0.177675E+11 | 0.115986E+10 | ||||||||
Minimum of Months | 0.165725E+09 | 1894.25 | 8.48 | 2.42 | 88226846.09 | 56.69 | -3.2 | -3.9 | ||
Maximum of Months | 0.275280E+10 | 2050.72 | 32.02 | 17.81 | 99368393.56 | 59.00 | 32.52 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45192247.98 | 1762.98 | 31-JAN-09:02 | 10.78 | 4.13 | 94781927.88 | 56.69 | 01-JAN-05:19 | 10.78 | 4.13 |
February | 0.156307E+09 | 1921.29 | 22-FEB-16:01 | 22.62 | 8.47 | 87310983.01 | 64.75 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.359458E+09 | 1915.19 | 22-MAR-15:02 | 23.90 | 8.87 | 99287906.97 | 67.99 | 15-MAR-21:30 | 23.90 | 8.87 |
April | 0.121282E+10 | 2332.81 | 27-APR-08:51 | 20.60 | 11.74 | 99191598.28 | 74.07 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.199207E+10 | 2412.67 | 20-MAY-08:32 | 25.77 | 11.62 | 0.103382E+09 | 75.67 | 17-MAY-21:19 | 25.77 | 11.62 |
June | 0.260314E+10 | 2410.55 | 20-JUN-08:62 | 25.28 | 16.80 | 99969671.28 | 78.62 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.257603E+10 | 2330.80 | 04-JUL-08:62 | 25.18 | 18.51 | 0.102822E+09 | 74.68 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.228325E+10 | 2342.43 | 30-AUG-08:51 | 23.30 | 15.51 | 0.103117E+09 | 80.38 | 11-AUG-21:10 | 23.30 | 15.51 |
September | 0.176860E+10 | 2301.86 | 19-SEP-08:51 | 26.10 | 16.81 | 0.100899E+09 | 77.40 | 06-SEP-21:10 | 26.10 | 16.81 |
October | 0.891865E+09 | 2239.14 | 03-OCT-08:51 | 23.30 | 15.83 | 0.102606E+09 | 78.73 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.212292E+09 | 2059.18 | 09-NOV-09:51 | 18.30 | 8.77 | 94006867.14 | 67.56 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 32738744.90 | 1792.61 | 16-DEC-09:02 | 8.48 | 2.42 | 94391375.15 | 56.69 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.141338E+11 | 0.118177E+10 | ||||||||
Minimum of Months | 32738744.90 | 1762.98 | 8.48 | 2.42 | 87310983.01 | 56.69 | -3.9 | -7.3 | ||
Maximum of Months | 0.260314E+10 | 2412.67 | 26.10 | 18.51 | 0.103382E+09 | 80.38 | 26.10 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327389E+10 | 1696.80 | 01-JAN-11:35 | 13.87 | 8.54 | 0.124927E+10 | 800.79 | 03-JAN-22:40 | 11.33 | 5.60 |
February | 0.321633E+10 | 1800.16 | 20-FEB-11:33 | 20.37 | 8.19 | 0.116253E+10 | 828.18 | 22-FEB-23:10 | 14.03 | 4.88 |
March | 0.377590E+10 | 1848.96 | 16-MAR-10:33 | 20.03 | 8.28 | 0.133522E+10 | 853.22 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.422124E+10 | 2166.13 | 30-APR-10:33 | 24.07 | 13.08 | 0.139997E+10 | 912.99 | 21-APR-21:49 | 24.07 | 13.08 |
May | 0.483115E+10 | 2290.00 | 20-MAY-10:33 | 28.30 | 13.16 | 0.154216E+10 | 951.83 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.522566E+10 | 3136.38 | 15-JUN-18:40 | 35.37 | 14.55 | 0.155519E+10 | 951.87 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.529175E+10 | 2855.90 | 26-JUL-18:25 | 32.50 | 19.69 | 0.159567E+10 | 951.86 | 05-JUL-22:10 | 32.50 | 19.69 |
August | 0.519031E+10 | 2903.80 | 07-AUG-18:25 | 33.05 | 18.14 | 0.159215E+10 | 951.85 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.488571E+10 | 2600.31 | 20-SEP-18:06 | 31.05 | 16.15 | 0.152580E+10 | 951.85 | 20-SEP-22:10 | 26.52 | 16.85 |
October | 0.452241E+10 | 2275.28 | 05-OCT-10:33 | 27.60 | 18.63 | 0.148417E+10 | 951.85 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.370242E+10 | 1962.58 | 10-NOV-11:33 | 20.93 | 12.02 | 0.130758E+10 | 875.59 | 01-NOV-00:10 | 20.93 | 12.02 |
December | 0.305122E+10 | 1624.26 | 10-DEC-11:35 | 15.93 | 7.48 | 0.122684E+10 | 759.45 | 15-DEC-22:49 | 13.98 | 4.58 |
Annual Sum or Average | 0.511880E+11 | 0.169765E+11 | ||||||||
Minimum of Months | 0.305122E+10 | 1624.26 | 13.87 | 7.48 | 0.116253E+10 | 759.45 | 11.33 | 4.58 | ||
Maximum of Months | 0.529175E+10 | 3136.38 | 35.37 | 19.69 | 0.159567E+10 | 951.87 | 32.50 | 19.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193592E+09 | 2278.93 | 12-JAN-16:02 | 18.72 | 10.12 | 96077822.59 | 56.69 | 03-JAN-22:10 | 18.72 | 10.12 |
February | 0.316399E+09 | 2363.88 | 20-FEB-16:02 | 23.12 | 8.59 | 87434781.71 | 56.69 | 06-FEB-22:00 | 23.12 | 8.59 |
March | 0.598750E+09 | 2360.01 | 14-MAR-15:02 | 23.98 | 9.90 | 97616507.30 | 56.70 | 25-MAR-23:30 | 13.35 | 4.70 |
April | 0.143071E+10 | 2403.91 | 16-APR-15:02 | 29.50 | 11.50 | 95536024.31 | 56.69 | 09-APR-02:39 | 29.50 | 11.50 |
May | 0.217639E+10 | 2403.43 | 17-MAY-15:02 | 29.40 | 13.34 | 99480592.67 | 56.69 | 22-MAY-22:10 | 23.22 | 14.22 |
June | 0.275687E+10 | 2443.92 | 15-JUN-15:02 | 38.22 | 15.87 | 96942091.89 | 59.82 | 16-JUN-21:10 | 32.52 | 14.90 |
July | 0.276188E+10 | 2398.06 | 27-JUL-18:02 | 32.52 | 19.86 | 99595156.71 | 56.70 | 26-JUL-22:49 | 32.52 | 19.86 |
August | 0.256538E+10 | 2387.03 | 28-AUG-18:02 | 29.03 | 17.18 | 99664158.36 | 56.70 | 07-AUG-00:10 | 29.03 | 17.18 |
September | 0.226306E+10 | 2391.41 | 14-SEP-18:02 | 29.45 | 17.02 | 96267193.85 | 56.70 | 20-SEP-21:00 | 26.70 | 16.89 |
October | 0.145057E+10 | 2371.67 | 31-OCT-15:02 | 21.60 | 7.74 | 98741040.95 | 56.70 | 04-OCT-22:49 | 21.60 | 7.74 |
November | 0.526488E+09 | 2363.63 | 09-NOV-16:02 | 23.22 | 12.98 | 94113409.73 | 56.70 | 24-NOV-22:49 | 7.30 | 2.12 |
December | 0.123185E+09 | 2246.94 | 16-DEC-16:02 | 14.72 | 4.08 | 95800590.34 | 56.69 | 28-DEC-05:19 | -3.2 | -3.9 |
Annual Sum or Average | 0.171633E+11 | 0.115727E+10 | ||||||||
Minimum of Months | 0.123185E+09 | 2246.94 | 14.72 | 4.08 | 87434781.71 | 56.69 | -3.2 | -3.9 | ||
Maximum of Months | 0.276188E+10 | 2443.92 | 38.22 | 19.86 | 99664158.36 | 59.82 | 32.52 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41866164.22 | 2193.67 | 12-JAN-16:02 | 18.72 | 10.12 | 94303149.54 | 56.69 | 27-JAN-05:19 | 0.93 | -2.8 |
February | 82255558.37 | 2291.58 | 20-FEB-16:02 | 23.12 | 8.59 | 86831069.32 | 60.84 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.239486E+09 | 2289.77 | 16-MAR-15:02 | 22.70 | 8.66 | 99565782.43 | 68.41 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.112427E+10 | 2556.12 | 06-APR-18:11 | 14.63 | 6.39 | 99068796.78 | 75.66 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.203210E+10 | 2517.09 | 20-MAY-08:51 | 26.70 | 12.19 | 0.102325E+09 | 79.05 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.269892E+10 | 2686.20 | 19-JUN-18:51 | 27.20 | 19.20 | 99153033.52 | 78.98 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.267153E+10 | 2431.98 | 25-JUL-18:02 | 34.32 | 19.47 | 0.101967E+09 | 75.78 | 21-JUL-21:00 | 34.32 | 19.47 |
August | 0.234945E+10 | 2445.81 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102267E+09 | 79.89 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.181367E+10 | 2373.04 | 01-SEP-18:02 | 31.13 | 18.07 | 99779735.77 | 78.11 | 13-SEP-21:10 | 21.70 | 17.29 |
October | 0.825463E+09 | 2318.31 | 05-OCT-21:51 | 22.80 | 16.23 | 0.103514E+09 | 80.31 | 05-OCT-21:10 | 22.80 | 16.23 |
November | 0.137122E+09 | 2249.31 | 07-NOV-16:02 | 21.52 | 10.29 | 93835206.36 | 67.20 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 22536475.32 | 2139.49 | 16-DEC-16:02 | 14.72 | 4.08 | 93826745.45 | 56.69 | 04-DEC-05:19 | 14.72 | 4.08 |
Annual Sum or Average | 0.140387E+11 | 0.117644E+10 | ||||||||
Minimum of Months | 22536475.32 | 2139.49 | 14.63 | 4.08 | 86831069.32 | 56.69 | 0.93 | -2.8 | ||
Maximum of Months | 0.269892E+10 | 2686.20 | 34.32 | 19.47 | 0.103514E+09 | 80.31 | 34.32 | 19.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530043E+09 | 1210.39 | 03-JAN-16:02 | 20.10 | 7.84 | 97948278.69 | 56.69 | 12-JAN-22:30 | 8.90 | 4.67 |
February | 0.543431E+09 | 1246.78 | 20-FEB-16:02 | 23.12 | 8.59 | 88720071.83 | 56.69 | 06-FEB-23:30 | 23.12 | 8.59 |
March | 0.560746E+09 | 1247.90 | 14-MAR-15:02 | 23.98 | 9.90 | 98308951.93 | 56.69 | 14-MAR-21:10 | 13.62 | 5.68 |
April | 0.852168E+09 | 1241.76 | 03-APR-15:02 | 26.88 | 11.50 | 95494220.08 | 56.69 | 17-APR-02:39 | 16.67 | 12.47 |
May | 0.110072E+10 | 1225.88 | 17-MAY-15:02 | 29.40 | 13.34 | 99052567.20 | 56.69 | 22-MAY-22:00 | 22.80 | 14.76 |
June | 0.137559E+10 | 1232.81 | 14-JUN-15:02 | 37.88 | 15.65 | 96311917.03 | 59.80 | 15-JUN-21:10 | 32.57 | 13.55 |
July | 0.143780E+10 | 1239.69 | 26-JUL-15:02 | 36.60 | 20.09 | 99164302.21 | 56.70 | 26-JUL-23:10 | 26.70 | 17.47 |
August | 0.143513E+10 | 1244.19 | 30-AUG-15:02 | 31.10 | 17.81 | 99261781.63 | 56.69 | 05-AUG-00:20 | 31.10 | 17.81 |
September | 0.143807E+10 | 1254.22 | 06-SEP-15:02 | 27.43 | 17.91 | 96107451.55 | 56.70 | 06-SEP-21:00 | 22.80 | 16.86 |
October | 0.121529E+10 | 1263.90 | 18-OCT-15:02 | 28.90 | 17.08 | 99160851.84 | 56.70 | 17-OCT-21:30 | 28.90 | 17.08 |
November | 0.784708E+09 | 1240.97 | 07-NOV-16:02 | 21.52 | 10.29 | 95241294.03 | 56.69 | 01-NOV-01:30 | 21.52 | 10.29 |
December | 0.481883E+09 | 1204.99 | 16-DEC-16:02 | 14.72 | 4.08 | 97892028.11 | 56.69 | 05-DEC-22:30 | 14.72 | 4.08 |
Annual Sum or Average | 0.117556E+11 | 0.116266E+10 | ||||||||
Minimum of Months | 0.481883E+09 | 1204.99 | 14.72 | 4.08 | 88720071.83 | 56.69 | 8.90 | 4.08 | ||
Maximum of Months | 0.143807E+10 | 1263.90 | 37.88 | 20.09 | 99261781.63 | 59.80 | 32.57 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318700E+11 | 18278.30 | 03-JAN-22:10 | 12.43 | 6.06 | 0.190855E+11 | 11347.14 | 20-JAN-04:19 | 3.30 | 2.24 |
February | 0.299776E+11 | 19374.90 | 07-FEB-23:00 | 15.60 | 8.35 | 0.173177E+11 | 11348.13 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.349397E+11 | 20264.81 | 15-MAR-21:53 | 19.40 | 7.29 | 0.192953E+11 | 11348.44 | 15-MAR-22:10 | 19.32 | 7.27 |
April | 0.380773E+11 | 22231.54 | 19-APR-22:00 | 27.20 | 11.76 | 0.186943E+11 | 11349.86 | 17-APR-01:10 | 27.20 | 11.76 |
May | 0.428557E+11 | 23230.89 | 31-MAY-21:20 | 27.97 | 13.53 | 0.193450E+11 | 11353.86 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.444681E+11 | 23859.79 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187604E+11 | 11372.91 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.456723E+11 | 23646.39 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193094E+11 | 11362.06 | 25-JUL-22:00 | 30.00 | 16.46 |
August | 0.446207E+11 | 23802.87 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193897E+11 | 11364.29 | 04-AUG-22:00 | 30.80 | 17.26 |
September | 0.412449E+11 | 22615.81 | 22-SEP-22:00 | 25.00 | 17.90 | 0.187064E+11 | 11348.98 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.387341E+11 | 22097.16 | 04-OCT-21:10 | 25.32 | 17.67 | 0.192873E+11 | 11348.86 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.327291E+11 | 20224.37 | 09-NOV-22:10 | 18.53 | 10.92 | 0.185477E+11 | 11348.20 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.310541E+11 | 18220.97 | 15-DEC-23:00 | 13.90 | 4.56 | 0.190374E+11 | 11347.75 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.456244E+12 | 0.226776E+12 | ||||||||
Minimum of Months | 0.299776E+11 | 18220.97 | 12.43 | 4.56 | 0.173177E+11 | 11347.14 | -3.9 | -7.3 | ||
Maximum of Months | 0.456723E+11 | 23859.79 | 31.83 | 17.90 | 0.193897E+11 | 11372.91 | 31.83 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355543E+11 | 20080.98 | 03-JAN-22:10 | 12.43 | 6.06 | 0.192073E+11 | 11347.22 | 20-JAN-04:19 | 3.30 | 2.24 |
February | 0.333071E+11 | 21077.90 | 06-FEB-22:10 | 18.62 | 6.93 | 0.173979E+11 | 11348.16 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.386247E+11 | 21843.37 | 15-MAR-21:53 | 19.40 | 7.29 | 0.193612E+11 | 11348.45 | 15-MAR-22:10 | 19.32 | 7.27 |
April | 0.413060E+11 | 23601.55 | 19-APR-21:10 | 28.12 | 12.29 | 0.187121E+11 | 11350.06 | 17-APR-01:10 | 28.12 | 12.29 |
May | 0.458229E+11 | 24433.66 | 19-MAY-21:20 | 29.80 | 13.44 | 0.193494E+11 | 11364.00 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.471528E+11 | 25044.27 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187614E+11 | 11380.27 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.484373E+11 | 24807.20 | 25-JUL-21:20 | 31.13 | 17.50 | 0.193102E+11 | 11362.78 | 06-JUL-22:00 | 31.13 | 17.50 |
August | 0.474084E+11 | 24969.94 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193912E+11 | 11366.89 | 07-AUG-21:19 | 30.80 | 17.26 |
September | 0.439807E+11 | 23742.19 | 22-SEP-21:20 | 25.00 | 17.90 | 0.187098E+11 | 11348.98 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.418619E+11 | 23261.38 | 04-OCT-21:10 | 25.32 | 17.67 | 0.193084E+11 | 11348.86 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.361160E+11 | 21719.25 | 09-NOV-22:10 | 18.53 | 10.92 | 0.186259E+11 | 11348.22 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.347132E+11 | 20061.87 | 15-DEC-23:00 | 13.90 | 4.56 | 0.191847E+11 | 11347.76 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.494285E+12 | 0.227320E+12 | ||||||||
Minimum of Months | 0.333071E+11 | 20061.87 | 12.43 | 4.56 | 0.173979E+11 | 11347.22 | -3.9 | -7.3 | ||
Maximum of Months | 0.484373E+11 | 25044.27 | 31.83 | 17.90 | 0.193912E+11 | 11380.27 | 31.83 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500070E+11 | 27401.03 | 01-JAN-11:50 | 14.13 | 8.64 | 0.188394E+11 | 11319.53 | 07-JAN-18:19 | 12.07 | 5.16 |
February | 0.461859E+11 | 28441.40 | 20-FEB-11:45 | 20.73 | 8.30 | 0.170221E+11 | 11319.48 | 04-FEB-18:19 | 20.73 | 8.30 |
March | 0.522776E+11 | 28657.86 | 19-MAR-10:33 | 18.67 | 7.01 | 0.188588E+11 | 11319.58 | 25-MAR-17:19 | 21.10 | 8.62 |
April | 0.534757E+11 | 30299.20 | 30-APR-10:50 | 24.53 | 12.98 | 0.182575E+11 | 11319.65 | 15-APR-17:19 | 24.53 | 12.98 |
May | 0.573503E+11 | 30471.53 | 21-MAY-10:33 | 29.47 | 14.38 | 0.188709E+11 | 11319.65 | 06-MAY-17:19 | 29.47 | 14.38 |
June | 0.574084E+11 | 30976.30 | 18-JUN-10:50 | 32.62 | 16.28 | 0.182662E+11 | 11319.64 | 24-JUN-17:19 | 31.67 | 16.29 |
July | 0.592536E+11 | 31144.57 | 02-JUL-10:37 | 32.23 | 20.13 | 0.188684E+11 | 11319.66 | 22-JUL-17:19 | 30.60 | 19.89 |
August | 0.586406E+11 | 31042.81 | 06-AUG-10:50 | 31.93 | 18.13 | 0.188756E+11 | 11319.63 | 12-AUG-17:19 | 33.70 | 18.99 |
September | 0.558490E+11 | 30711.22 | 17-SEP-10:33 | 29.47 | 15.71 | 0.182612E+11 | 11319.65 | 02-SEP-17:19 | 29.47 | 15.71 |
October | 0.548128E+11 | 30136.16 | 05-OCT-10:33 | 27.60 | 18.63 | 0.188641E+11 | 11319.63 | 28-OCT-17:19 | 22.23 | 13.64 |
November | 0.498186E+11 | 28257.94 | 10-NOV-11:50 | 21.02 | 12.06 | 0.182386E+11 | 11319.49 | 18-NOV-18:19 | 13.90 | 3.79 |
December | 0.495076E+11 | 27350.69 | 10-DEC-11:50 | 16.32 | 7.64 | 0.188344E+11 | 11319.62 | 30-DEC-18:19 | 7.97 | 2.46 |
Annual Sum or Average | 0.644587E+12 | 0.222057E+12 | ||||||||
Minimum of Months | 0.461859E+11 | 27350.69 | 14.13 | 7.01 | 0.170221E+11 | 11319.48 | 7.97 | 2.46 | ||
Maximum of Months | 0.592536E+11 | 31144.57 | 32.62 | 20.13 | 0.188756E+11 | 11319.66 | 33.70 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590273E+10 | 3475.90 | 01-JAN-11:35 | 13.87 | 8.54 | 0.130063E+10 | 829.77 | 12-JAN-22:30 | 8.90 | 4.67 |
February | 0.605502E+10 | 3810.02 | 20-FEB-11:33 | 20.37 | 8.19 | 0.120720E+10 | 865.87 | 07-FEB-22:40 | 20.37 | 8.19 |
March | 0.735635E+10 | 3834.20 | 16-MAR-10:33 | 20.03 | 8.28 | 0.138242E+10 | 901.72 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.866851E+10 | 4617.81 | 30-APR-10:33 | 24.07 | 13.08 | 0.148131E+10 | 999.94 | 21-APR-21:40 | 24.07 | 13.08 |
May | 0.102332E+11 | 5718.86 | 30-MAY-15:02 | 34.32 | 17.72 | 0.164357E+10 | 1007.39 | 17-MAY-22:10 | 34.32 | 17.72 |
June | 0.118202E+11 | 6601.74 | 17-JUN-17:15 | 36.10 | 16.68 | 0.164871E+10 | 1007.44 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.121231E+11 | 6949.09 | 03-JUL-12:50 | 36.52 | 18.58 | 0.169714E+10 | 1007.42 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.116311E+11 | 6793.76 | 07-AUG-15:04 | 35.37 | 18.63 | 0.169155E+10 | 1007.44 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.105148E+11 | 6282.62 | 21-SEP-14:10 | 31.78 | 18.05 | 0.160584E+10 | 1007.41 | 20-SEP-22:10 | 31.78 | 18.05 |
October | 0.918224E+10 | 5818.93 | 05-OCT-15:03 | 30.68 | 17.34 | 0.154629E+10 | 1007.40 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.695244E+10 | 4141.86 | 10-NOV-11:33 | 20.93 | 12.02 | 0.133032E+10 | 920.76 | 09-NOV-22:30 | 20.93 | 12.02 |
December | 0.519461E+10 | 3381.33 | 10-DEC-11:35 | 15.93 | 7.48 | 0.128696E+10 | 807.16 | 15-DEC-22:40 | 14.07 | 4.59 |
Annual Sum or Average | 0.105634E+12 | 0.178219E+11 | ||||||||
Minimum of Months | 0.519461E+10 | 3381.33 | 13.87 | 7.48 | 0.120720E+10 | 807.16 | 8.90 | 4.59 | ||
Maximum of Months | 0.121231E+11 | 6949.09 | 36.52 | 18.63 | 0.169714E+10 | 1007.44 | 34.32 | 18.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3003079.04 | 313.86 | 27-JAN-07:30 | -4.2 |
February | 1769044.27 | 269.31 | 03-FEB-07:05 | -5.1 |
March | 2238625.17 | 200.19 | 02-MAR-07:10 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 2767304.96 | 236.49 | 28-NOV-05:00 | -0.6 |
December | 27110731.49 | 733.75 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 36888784.92 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 27110731.49 | 733.75 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301659E+09 | 1397.25 | 15-JAN-16:02 | 10.00 |
February | 0.179059E+09 | 1385.47 | 02-FEB-09:02 | 1.38 |
March | 86425740.26 | 1400.13 | 02-MAR-09:02 | 0.47 |
April | 5343589.14 | 592.71 | 11-APR-08:62 | 6.88 |
May | 360288.26 | 558.60 | 08-MAY-08:05 | 20.23 |
June | 46663.48 | 466.63 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 169728.09 | 398.73 | 15-AUG-08:05 | 19.50 |
September | 149993.73 | 528.93 | 28-SEP-08:05 | 18.68 |
October | 979909.57 | 642.24 | 07-OCT-08:04 | 11.28 |
November | 0.133857E+09 | 1405.09 | 27-NOV-09:02 | 3.98 |
December | 0.421974E+09 | 1442.05 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.113003E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.421974E+09 | 1442.05 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525716E+09 | 1445.24 | 27-JAN-09:02 | -1.2 |
February | 0.305751E+09 | 1435.17 | 02-FEB-09:02 | 1.38 |
March | 0.127517E+09 | 1420.63 | 02-MAR-09:02 | 0.47 |
April | 5855765.89 | 761.80 | 11-APR-08:62 | 6.88 |
May | 220262.62 | 659.41 | 05-MAY-08:53 | 17.80 |
June | 11182.05 | 114.25 | 26-JUN-08:36 | 25.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 6073.74 | 36.11 | 17-AUG-08:56 | 19.40 |
September | 75007.39 | 328.44 | 27-SEP-08:54 | 21.10 |
October | 1031443.17 | 627.92 | 07-OCT-08:04 | 11.28 |
November | 0.219988E+09 | 1415.99 | 28-NOV-09:02 | 4.18 |
December | 0.705974E+09 | 1448.91 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.189215E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.2 | |
Maximum of Months | 0.705974E+09 | 1448.91 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26645962.32 | 419.64 | 27-JAN-16:02 | 9.50 |
February | 16901249.95 | 416.58 | 02-FEB-16:02 | 10.60 |
March | 3537005.92 | 405.91 | 29-MAR-15:03 | 16.28 |
April | 219187.98 | 383.71 | 11-APR-15:04 | 16.78 |
May | 30559.16 | 129.36 | 01-MAY-08:54 | 17.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 4054.41 | 54.06 | 20-SEP-08:56 | 26.10 |
October | 137647.00 | 260.10 | 24-OCT-15:05 | 17.88 |
November | 6397243.34 | 412.16 | 27-NOV-16:02 | 8.22 |
December | 54397357.71 | 431.22 | 09-DEC-16:03 | 16.42 |
Annual Sum or Average | 0.108270E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.22 | |
Maximum of Months | 54397357.71 | 431.22 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319172E+09 | 1364.92 | 15-JAN-16:02 | 10.00 |
February | 0.169943E+09 | 1293.95 | 13-FEB-16:02 | 12.30 |
March | 90280677.36 | 1330.06 | 02-MAR-09:02 | 0.47 |
April | 4831286.43 | 324.99 | 22-APR-18:05 | 18.03 |
May | 6132.54 | 51.10 | 03-MAY-08:06 | 19.18 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 10727.42 | 107.27 | 19-JUL-08:07 | 20.78 |
August | 41779.19 | 348.16 | 14-AUG-08:06 | 18.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 1031514.84 | 466.02 | 15-OCT-18:05 | 18.72 |
November | 0.146289E+09 | 1360.48 | 27-NOV-09:02 | 3.98 |
December | 0.429111E+09 | 1404.13 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.116072E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.429111E+09 | 1404.13 | 25.03 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533940E+09 | 1369.33 | 14-JAN-16:02 | 7.88 |
February | 0.274078E+09 | 1350.74 | 02-FEB-16:02 | 10.60 |
March | 0.133137E+09 | 1349.38 | 02-MAR-09:02 | 0.47 |
April | 5918322.46 | 876.98 | 11-APR-15:04 | 16.78 |
May | 7405.29 | 30.05 | 04-MAY-21:56 | 20.60 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 8972.42 | 104.68 | 19-JUL-21:56 | 22.20 |
August | 7848.41 | 65.40 | 17-AUG-08:56 | 19.40 |
September | 16634.86 | 138.62 | 29-SEP-06:26 | 15.80 |
October | 2641918.65 | 552.92 | 14-OCT-08:04 | 14.50 |
November | 0.232168E+09 | 1379.70 | 27-NOV-16:02 | 8.22 |
December | 0.692938E+09 | 1407.35 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.187486E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.692938E+09 | 1407.35 | 25.03 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 94229.58 | 48.61 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 94229.58 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 94229.58 | 48.61 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575680E+09 | 1685.67 | 14-JAN-16:02 | 7.88 |
February | 0.371314E+09 | 1675.56 | 02-FEB-09:02 | 1.38 |
March | 0.222247E+09 | 1686.99 | 02-MAR-09:02 | 0.47 |
April | 28885642.98 | 1613.10 | 11-APR-08:62 | 6.88 |
May | 811515.12 | 633.70 | 02-MAY-08:03 | 14.68 |
June | 121908.65 | 452.34 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 373535.93 | 468.44 | 16-AUG-08:05 | 20.60 |
September | 294685.77 | 454.92 | 26-SEP-08:05 | 20.78 |
October | 9154264.37 | 601.95 | 10-OCT-08:03 | 14.87 |
November | 0.300663E+09 | 1692.19 | 27-NOV-09:02 | 3.98 |
December | 0.745565E+09 | 1717.21 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.225511E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.745565E+09 | 1717.21 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.894094E+09 | 1720.85 | 27-JAN-09:02 | -1.2 |
February | 0.560484E+09 | 1709.66 | 02-FEB-09:02 | 1.38 |
March | 0.287373E+09 | 1701.41 | 02-MAR-09:02 | 0.47 |
April | 29194314.12 | 1614.28 | 11-APR-08:62 | 6.88 |
May | 345553.69 | 653.89 | 06-MAY-08:53 | 18.90 |
June | 6970.88 | 104.56 | 11-JUN-08:36 | 25.53 |
July | 5127.35 | 68.36 | 29-JUL-06:55 | 25.00 |
August | 50239.02 | 147.53 | 30-AUG-08:54 | 23.30 |
September | 263679.40 | 524.24 | 29-SEP-06:24 | 15.80 |
October | 12740878.14 | 1120.14 | 25-OCT-08:62 | 11.15 |
November | 0.461645E+09 | 1697.27 | 28-NOV-09:02 | 4.18 |
December | 0.112622E+10 | 1726.85 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.337242E+10 | |||
Minimum of Months | 5127.35 | 68.36 | -1.2 | |
Maximum of Months | 0.112622E+10 | 1726.85 | 25.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84217757.16 | 863.70 | 15-JAN-16:02 | 10.00 |
February | 54329908.29 | 416.63 | 13-FEB-16:02 | 12.30 |
March | 36850114.66 | 849.97 | 02-MAR-09:02 | 0.47 |
April | 4266003.87 | 304.44 | 18-APR-08:03 | 10.18 |
May | 260077.66 | 224.86 | 10-MAY-08:05 | 20.78 |
June | 47278.98 | 245.30 | 28-JUN-08:05 | 19.18 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 34571.91 | 180.43 | 15-AUG-08:05 | 19.50 |
September | 42163.89 | 133.34 | 08-SEP-08:05 | 19.78 |
October | 149941.59 | 266.32 | 07-OCT-18:05 | 17.62 |
November | 46097135.19 | 858.84 | 27-NOV-09:02 | 3.98 |
December | 0.128615E+09 | 876.03 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.354910E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.128615E+09 | 876.03 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3757835.48 | 516.49 | 27-JAN-07:30 | -4.2 |
February | 4504947.34 | 644.15 | 03-FEB-07:10 | -5.1 |
March | 710486.01 | 234.31 | 02-MAR-07:10 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 23933118.52 | 1002.64 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 32906387.34 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 23933118.52 | 1002.64 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132566E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.115622E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123068E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.112060E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.112432E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.105682E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.109484E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.116397E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.115946E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128391E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.124152E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.131487E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142729E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.105682E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.132566E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.943854E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.848695E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939774E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899513E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929943E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.899697E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.925861E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.934824E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.904139E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.939822E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.910852E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.940104E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110171E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.848695E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.943854E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280761E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248271E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269049E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248234E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250357E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.238414E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.245742E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.256390E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256111E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.274401E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268836E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278826E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311539E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.238414E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280761E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280761E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248271E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269049E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248234E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250357E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.238414E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.245742E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.256390E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256104E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.274401E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268836E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278826E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311538E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.238414E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280761E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400623E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308416E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 229478.16 | 0.274719E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22153734.91 | 0.121339E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61092015.78 | 48940335.07 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119546E+09 | 14230626.06 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110013E+09 | 9068931.66 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88713655.41 | 20023266.10 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48816197.10 | 57930161.85 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11617758.36 | 0.149235E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313777E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439902E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462181E+09 | 0.215821E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9068931.66 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119546E+09 | 0.439902E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164416E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1955.37 | 0.127908E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254466.08 | 0.116744E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9368296.95 | 55167319.63 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23837896.09 | 23845761.62 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46358417.97 | 7315188.43 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42485009.08 | 5059622.11 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34572571.70 | 10222201.48 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19597710.50 | 25799411.95 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4900602.24 | 64026654.05 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7265.70 | 0.130209E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179435E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181384E+09 | 0.910148E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5059622.11 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46358417.97 | 0.179435E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352442E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 362209.68 | 0.271927E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1934874.79 | 0.247563E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26284015.73 | 0.117043E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57580976.96 | 52375360.62 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108334E+09 | 16932022.52 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99111569.04 | 11691731.06 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81327919.81 | 23316875.74 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47928648.51 | 58214268.15 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13884975.06 | 0.137780E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257170.62 | 0.278827E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388407E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437007E+09 | 0.195652E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11691731.06 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108334E+09 | 0.388407E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200491E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 217026.98 | 0.154321E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1173859.49 | 0.139716E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15818870.86 | 65080846.57 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34392137.25 | 28600683.98 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62995618.53 | 9261559.14 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57682776.36 | 6361158.58 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47576540.50 | 12584168.86 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28467206.14 | 31894794.46 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8376847.21 | 76593277.82 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163369.74 | 0.157743E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221716E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256864E+09 | 0.110436E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6361158.58 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62995618.53 | 0.221716E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549328E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 13571.97 | 0.426193E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 519852.71 | 0.388034E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 29528625.30 | 0.175387E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 78925176.25 | 70057107.84 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.156842E+09 | 18397601.32 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.145961E+09 | 11678223.02 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.118843E+09 | 26740431.14 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 67792460.33 | 73979400.10 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 18007642.17 | 0.200454E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 22375.22 | 0.425807E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602300E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.616456E+09 | 0.296836E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11678223.02 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.156842E+09 | 0.602300E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.132566E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971002E+09 |
February | 0.236489E+11 | 0.115622E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758155E+09 |
March | 0.262800E+11 | 0.123068E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 319546.65 | 0.688597E+09 |
April | 0.253579E+11 | 0.112060E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47029670.09 | 0.316409E+09 |
May | 0.262123E+11 | 0.112432E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134027E+09 | 0.133183E+09 |
June | 0.254132E+11 | 0.105682E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266103E+09 | 40079327.30 |
July | 0.261570E+11 | 0.109484E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243931E+09 | 27590489.13 |
August | 0.262677E+11 | 0.116397E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196472E+09 | 55733731.92 |
September | 0.253456E+11 | 0.115946E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108386E+09 | 0.145561E+09 |
October | 0.261693E+11 | 0.128391E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25562924.85 | 0.370810E+09 |
November | 0.253025E+11 | 0.124152E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762211E+09 |
December | 0.261570E+11 | 0.131487E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105910E+10 |
Annual Sum or Average | 0.308468E+12 | 0.142729E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102183E+10 | 0.532843E+10 |
Minimum of Months | 0.236489E+11 | 0.105682E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27590489.13 |
Maximum of Months | 0.262800E+11 | 0.132566E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266103E+09 | 0.105910E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.943854E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278716E+10 |
February | 0.702046E+11 | 0.848695E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217155E+10 |
March | 0.780153E+11 | 0.939774E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2730609.45 | 0.197609E+10 |
April | 0.752779E+11 | 0.899513E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149241E+09 | 0.920813E+09 |
May | 0.778146E+11 | 0.929943E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392667E+09 | 0.391982E+09 |
June | 0.754422E+11 | 0.899697E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764642E+09 | 0.118925E+09 |
July | 0.776503E+11 | 0.925861E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700544E+09 | 82326810.00 |
August | 0.779788E+11 | 0.934824E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567311E+09 | 0.166823E+09 |
September | 0.752414E+11 | 0.904139E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317230E+09 | 0.422313E+09 |
October | 0.776868E+11 | 0.939822E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75649838.94 | 0.106874E+10 |
November | 0.751137E+11 | 0.910852E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8982.59 | 0.219712E+10 |
December | 0.776503E+11 | 0.940104E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304326E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110171E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297003E+10 | 0.153471E+11 |
Minimum of Months | 0.702046E+11 | 0.848695E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82326810.00 |
Maximum of Months | 0.780153E+11 | 0.943854E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764642E+09 | 0.304326E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222904E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139155.20 | 0.170169E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836660.89 | 0.151338E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19892136.27 | 60782845.56 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50390589.13 | 19593554.80 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92493001.27 | 3219244.52 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89879622.21 | 1029579.80 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74096482.14 | 5081934.12 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42432774.55 | 19907577.13 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11998377.09 | 69355678.95 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179984.48 | 0.168587E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246956E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382339E+09 | 0.113892E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1029579.80 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92493001.27 | 0.246956E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217220E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30195.56 | 0.167215E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 509590.17 | 0.152350E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19007893.74 | 64429321.56 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48768701.10 | 22922662.41 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90162489.78 | 5265905.37 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87022087.87 | 2779413.77 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72055560.06 | 7842123.39 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40950515.66 | 24194348.47 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11049411.72 | 74435161.54 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31257.11 | 0.166577E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240629E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369588E+09 | 0.114586E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779413.77 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90162489.78 | 0.240629E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84500568.57 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67934153.70 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64281807.39 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1043521.71 | 33835339.14 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4354407.30 | 17400028.46 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11752972.80 | 7329394.93 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9925880.77 | 6573318.25 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7719333.26 | 9981058.21 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3626672.54 | 18328948.88 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 656759.93 | 39019167.47 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68438077.83 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91043344.94 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39079548.31 | 0.508665E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6573318.25 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11752972.80 | 91043344.94 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61095229.65 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54523.54 | 46654341.65 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 257297.44 | 41873200.99 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5609060.00 | 17358807.11 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13987086.07 | 6058485.75 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25601730.57 | 1280472.50 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24602274.98 | 587192.62 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20479908.33 | 1955140.52 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11813832.61 | 6366104.00 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3408426.44 | 19898042.13 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70350.38 | 45992657.00 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67793904.45 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105884E+09 | 0.316914E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587192.62 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25601730.57 | 67793904.45 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223614E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 142488.91 | 0.171458E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 850105.19 | 0.152813E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20074237.95 | 61885525.58 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50621218.91 | 20029594.14 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92601215.41 | 3297614.61 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89814311.47 | 1059112.22 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74272147.41 | 5178739.68 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42721832.08 | 20193386.08 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12291439.15 | 69721484.29 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187188.85 | 0.169215E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247459E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383576E+09 | 0.114592E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059112.22 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92601215.41 | 0.247459E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216926E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41548.20 | 0.167677E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 524038.94 | 0.152712E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19082908.30 | 65921900.73 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48699344.39 | 25678811.50 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89703417.83 | 7134557.06 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86443730.72 | 4313045.13 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71714713.11 | 9536858.12 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40727372.87 | 26450694.54 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11197591.04 | 73536337.73 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67056.49 | 0.165905E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240419E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368202E+09 | 0.115621E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4313045.13 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89703417.83 | 0.240419E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270041E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173648.28 | 0.209291E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113727.66 | 0.191166E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20059964.02 | 89536310.20 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45095399.01 | 39078228.46 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83762046.19 | 12534807.28 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77564092.73 | 8335201.28 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63435275.90 | 16932686.82 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36397488.44 | 44104039.36 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10200918.66 | 0.105592E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139255.21 | 0.215741E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296708E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337942E+09 | 0.149906E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8335201.28 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83762046.19 | 0.296708E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222405E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129208.96 | 0.170029E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 799457.08 | 0.151403E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19463617.20 | 61037620.10 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49647757.32 | 19798316.08 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91433201.33 | 3304828.11 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88825025.16 | 1078062.67 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73188857.26 | 5187554.25 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41747595.98 | 20129568.12 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11721154.74 | 69587937.62 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166846.46 | 0.168453E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246509E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377123E+09 | 0.113892E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078062.67 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91433201.33 | 0.246509E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216177E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29639.93 | 0.166675E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485173.39 | 0.152300E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18612619.39 | 64566374.31 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48079852.14 | 22682231.27 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89171496.47 | 5028960.99 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86053833.64 | 2565160.57 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71239861.72 | 7535895.79 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40400561.06 | 23754201.96 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10846453.77 | 74413448.14 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27690.32 | 0.165834E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239692E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364947E+09 | 0.114122E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2565160.57 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89171496.47 | 0.239692E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116616E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57726.70 | 88935574.41 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 400493.19 | 78685280.94 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10100906.25 | 31461701.72 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25769146.95 | 10128090.83 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47311461.26 | 1682237.13 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45819274.97 | 551425.46 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37798809.54 | 2660844.22 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21527170.94 | 10353227.41 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5877746.48 | 36034274.74 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62311.33 | 87714321.73 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129304E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194725E+09 | 0.594127E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551425.46 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47311461.26 | 0.129304E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644261E+09 |
February | 0.415303E+11 | 0.248271E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503945E+09 |
March | 0.461508E+11 | 0.269049E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190237.56 | 0.463786E+09 |
April | 0.445315E+11 | 0.248234E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28002753.27 | 0.216782E+09 |
May | 0.460320E+11 | 0.250357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79336889.36 | 92405987.87 |
June | 0.446286E+11 | 0.238414E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163709E+09 | 28279643.81 |
July | 0.459349E+11 | 0.245742E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149627E+09 | 19867077.37 |
August | 0.461292E+11 | 0.256390E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121238E+09 | 40157207.33 |
September | 0.445099E+11 | 0.256111E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67412201.15 | 97725512.33 |
October | 0.459565E+11 | 0.274401E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15815461.22 | 0.247291E+09 |
November | 0.444343E+11 | 0.268836E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178.12 | 0.504735E+09 |
December | 0.459349E+11 | 0.278826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703754E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311539E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625332E+09 | 0.356299E+10 |
Minimum of Months | 0.415303E+11 | 0.238414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19867077.37 |
Maximum of Months | 0.461508E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163709E+09 | 0.703754E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650028E+09 |
February | 0.415303E+11 | 0.248271E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507973E+09 |
March | 0.461508E+11 | 0.269049E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160966.78 | 0.467315E+09 |
April | 0.445315E+11 | 0.248234E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27891346.64 | 0.217713E+09 |
May | 0.460320E+11 | 0.250357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79280216.89 | 92608650.28 |
June | 0.446286E+11 | 0.238414E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163675E+09 | 28285591.15 |
July | 0.459349E+11 | 0.245742E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149593E+09 | 19870667.83 |
August | 0.461292E+11 | 0.256390E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121200E+09 | 40198518.26 |
September | 0.445099E+11 | 0.256104E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67325164.29 | 97833587.77 |
October | 0.459565E+11 | 0.274401E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15769989.07 | 0.248498E+09 |
November | 0.444343E+11 | 0.268836E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508667E+09 |
December | 0.459349E+11 | 0.278826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710208E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311538E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624896E+09 | 0.358920E+10 |
Minimum of Months | 0.415303E+11 | 0.238414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19870667.83 |
Maximum of Months | 0.461508E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163675E+09 | 0.710208E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582456E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454351E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 145807.41 | 0.417653E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 25014994.86 | 0.194488E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 71045985.07 | 82783133.12 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.146643E+09 | 25310561.79 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.134012E+09 | 17779583.38 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108568E+09 | 35967985.78 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 60319064.47 | 87501755.81 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 14133965.91 | 0.222177E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454810E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636360E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.559883E+09 | 0.321164E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17779583.38 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.146643E+09 | 0.636360E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476961E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39906.64 | 0.368681E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1273198.23 | 0.334531E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30177562.38 | 0.156941E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73003349.52 | 68721786.55 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143943E+09 | 21906605.49 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132028E+09 | 14886106.13 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107237E+09 | 29875747.41 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60233180.32 | 75671061.91 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15233274.86 | 0.182715E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84017.24 | 0.373291E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526497E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563252E+09 | 0.263068E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14886106.13 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143943E+09 | 0.526497E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 286.20 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 300.77 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 21-MAR-16:00 | 282.97 | 02-MAR-05:40 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 21-APR-14:00 | 192.61 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 21-MAY-14:00 | 128.67 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 02-JUN-16:00 | 83.19 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 | 02-JUL-16:00 | 50.64 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 | 07-AUG-16:00 | 65.23 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 | 19-SEP-14:00 | 146.93 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 01-OCT-15:00 | 158.35 | 11-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 242.60 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 287.27 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 300.77 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 116.80 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 20-FEB-15:00 | 122.82 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 22-MAR-13:00 | 115.52 | 02-MAR-05:50 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 | 21-APR-14:00 | 83.36 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 19-MAY-14:00 | 58.77 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 02-JUN-16:00 | 36.47 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 02-JUL-16:00 | 24.95 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 07-AUG-16:00 | 29.64 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 19-SEP-14:00 | 64.68 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 01-OCT-15:00 | 70.79 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 03-NOV-15:55 | 101.77 | 17-NOV-04:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 116.59 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 122.82 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 261.10 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 20-FEB-15:00 | 274.38 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | 21-MAR-16:00 | 258.11 | 02-MAR-05:20 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.11 | 21-APR-14:00 | 186.51 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 | 19-MAY-16:00 | 132.14 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.40 | 02-JUN-16:00 | 85.41 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.40 | 02-JUL-16:00 | 57.44 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.75 | 07-AUG-16:00 | 68.49 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 | 19-SEP-14:00 | 147.03 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 | 01-OCT-15:00 | 158.60 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 08-NOV-15:00 | 225.87 | 17-NOV-04:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 262.07 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 132.40 | 274.38 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 150.64 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 | 20-FEB-15:00 | 158.30 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 21-MAR-16:00 | 148.92 | 02-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 | 21-APR-14:00 | 105.74 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.16 | 19-MAY-14:00 | 74.50 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 02-JUN-16:00 | 48.02 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.47 | 02-JUL-16:00 | 32.00 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 07-AUG-16:00 | 38.00 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 | 19-SEP-16:00 | 82.97 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 01-OCT-15:00 | 89.59 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 03-NOV-16:00 | 129.04 | 17-NOV-04:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 151.20 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 158.30 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 398.54 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 2.85 | 20-FEB-16:00 | 416.82 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 23.84 | 21-MAR-16:00 | 388.00 | 02-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 105.32 | 21-APR-15:20 | 280.56 | 12-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 148.67 | 21-MAY-16:00 | 193.61 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 193.77 | 02-JUN-16:30 | 113.24 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 194.80 | 02-JUL-16:00 | 80.52 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 173.45 | 07-AUG-16:00 | 95.63 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 133.59 | 19-SEP-16:00 | 209.88 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:20 | 234.20 | 25-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 10.25 | 03-NOV-16:00 | 338.23 | 17-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 400.03 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 194.80 | 416.82 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 661.40 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 693.48 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 21-MAR-16:00 | 667.72 | 02-MAR-05:10 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.86 | 21-APR-14:00 | 469.47 | 12-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.51 | 21-MAY-14:00 | 330.47 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.80 | 02-JUN-16:00 | 208.80 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.11 | 02-JUL-16:00 | 142.83 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.40 | 07-AUG-16:00 | 169.68 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.81 | 19-SEP-14:00 | 363.91 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.91 | 01-OCT-15:00 | 401.33 | 25-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 590.84 | 17-NOV-04:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 674.12 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.83 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 319.80 | 693.48 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1955.88 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2048.66 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.98 | 22-MAR-13:00 | 1951.35 | 02-MAR-05:50 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.64 | 21-APR-14:00 | 1395.42 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.89 | 19-MAY-14:00 | 982.12 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 914.80 | 02-JUN-16:00 | 596.75 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 904.25 | 02-JUL-16:00 | 408.22 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.33 | 07-AUG-16:00 | 484.95 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.58 | 19-SEP-14:00 | 1065.56 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.17 | 01-OCT-15:00 | 1183.30 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 08-NOV-15:00 | 1713.32 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1965.74 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.22 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 914.80 | 2048.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 20-FEB-16:10 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.22 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.60 | 02-JUN-16:30 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.76 | 03-JUL-16:00 | 20.31 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.06 | 07-AUG-16:00 | 28.96 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 | 01-OCT-16:30 | 91.19 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 03-NOV-16:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.60 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:10 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.11 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.02 | 19-MAY-16:00 | 72.66 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 02-JUN-16:30 | 38.88 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.76 | 03-JUL-16:00 | 28.02 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 | 07-AUG-16:00 | 33.80 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.48 | 01-OCT-15:10 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:10 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.73 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 175.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 53.23 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 55.98 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 51.67 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 21-APR-14:00 | 39.59 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 | 21-MAY-14:00 | 29.86 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 02-JUN-16:00 | 19.91 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 02-JUL-16:00 | 15.04 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 07-AUG-16:00 | 17.05 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 19-SEP-14:00 | 32.04 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 01-OCT-15:00 | 35.21 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 47.38 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 53.12 | 19-DEC-04:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 55.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.64 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 20-FEB-16:10 | 49.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 21-MAR-16:00 | 46.11 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 21-APR-15:10 | 31.47 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 19-MAY-16:00 | 20.28 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 02-JUN-16:00 | 10.47 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 02-JUL-16:00 | 7.47 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 07-AUG-16:00 | 9.77 | 16-AUG-21:40 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 19-SEP-16:00 | 22.38 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 01-OCT-15:10 | 25.45 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 03-NOV-15:08 | 39.57 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46.82 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 49.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:10 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 | 21-APR-15:10 | 112.77 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.57 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.46 | 01-JUL-17:00 | 21.13 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 | 07-AUG-16:00 | 30.51 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 01-OCT-15:10 | 91.19 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 03-NOV-16:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.74 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:08 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.53 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.13 | 02-JUN-17:00 | 41.03 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.45 | 01-JUL-17:00 | 33.78 | 05-JUL-06:40 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.73 | 07-AUG-16:00 | 37.16 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.73 | 01-OCT-15:10 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 03-NOV-15:08 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.73 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.13 | 175.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 201.22 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 20-FEB-16:00 | 211.43 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 | 21-MAR-16:00 | 198.93 | 02-MAR-05:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 | 21-APR-14:00 | 144.01 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 19-MAY-14:00 | 101.09 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.12 | 02-JUN-16:00 | 64.81 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.91 | 02-JUL-16:00 | 43.19 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 07-AUG-16:00 | 51.25 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.78 | 19-SEP-14:00 | 112.66 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.81 | 01-OCT-15:00 | 121.42 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 08-NOV-15:00 | 176.26 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 201.98 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.19 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.12 | 211.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.55 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 20-FEB-16:10 | 176.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.66 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 21-APR-15:10 | 113.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.12 | 02-JUN-16:40 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 03-JUL-16:00 | 20.67 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 07-AUG-16:00 | 27.57 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.29 | 02-SEP-16:00 | 80.57 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 | 01-OCT-16:40 | 91.58 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 03-NOV-16:00 | 142.21 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.18 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.12 | 176.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.53 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-FEB-16:10 | 175.99 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.65 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 | 21-APR-15:10 | 113.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.78 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 02-JUN-16:50 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 03-JUL-16:00 | 26.80 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.81 | 07-AUG-16:00 | 31.96 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 | 19-SEP-16:00 | 80.56 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 | 01-OCT-15:10 | 91.57 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 03-NOV-15:10 | 142.19 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.16 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 175.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 85.72 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 22-FEB-16:09 | 90.05 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 21-MAR-16:00 | 84.76 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 21-APR-15:10 | 57.90 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 19-MAY-16:00 | 37.38 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 02-JUN-16:00 | 19.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 | 01-JUL-17:00 | 10.58 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 | 07-AUG-16:00 | 14.11 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 19-SEP-16:00 | 41.22 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 01-OCT-15:10 | 46.86 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 03-NOV-16:00 | 72.76 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 86.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 90.05 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 455.16 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.97 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 22-MAR-13:00 | 450.99 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 320.81 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 221.92 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 02-JUN-16:00 | 135.39 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.17 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.97 | 19-SEP-14:00 | 240.66 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 268.06 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 08-NOV-15:00 | 393.12 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.87 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 475.97 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 455.17 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.98 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 21-MAR-16:00 | 450.99 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 320.81 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 221.92 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 02-JUN-16:00 | 135.40 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.17 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.97 | 19-SEP-14:00 | 240.66 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 268.06 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 393.13 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.87 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 475.98 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 407.41 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 426.04 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11.67 | 21-MAR-16:00 | 397.73 | 02-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 101.50 | 21-APR-14:00 | 287.13 | 12-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 136.32 | 21-MAY-14:00 | 198.61 | 02-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 182.51 | 02-JUN-16:00 | 121.20 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 175.79 | 02-JUL-16:00 | 83.30 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 162.76 | 07-AUG-16:00 | 98.71 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 122.73 | 19-SEP-14:00 | 215.38 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 109.59 | 01-OCT-15:00 | 239.91 | 25-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 351.94 | 28-NOV-05:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 408.93 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 182.51 | 426.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 356.92 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 20-FEB-16:00 | 375.01 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 21-MAR-16:00 | 352.89 | 02-MAR-05:40 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.79 | 21-APR-15:00 | 243.50 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 21-MAY-14:00 | 172.65 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 02-JUN-16:00 | 111.52 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 02-JUL-16:00 | 72.80 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 07-AUG-16:00 | 87.44 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.99 | 19-SEP-14:00 | 191.73 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | 01-OCT-15:00 | 204.92 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 08-NOV-15:00 | 302.72 | 28-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 358.26 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.80 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 375.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18256.23 | 05-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15270.92 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12080.10 | 01-MAR-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13003.62 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13595.30 | 21-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14313.13 | 15-JUN-18:10 | 35783.66 | 46898.65 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18929.20 | 19-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22181.42 | 24-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24598.19 | 22-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24391.06 | 05-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23793.71 | 10-NOV-22:00 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22070.18 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12080.10 | 8945.92 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24598.19 | 35783.66 | 46898.65 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2799.51 | 12-JAN-13:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 |
February | 2851.69 | 07-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
March | 2228.87 | 16-MAR-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
April | 2346.07 | 03-APR-14:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 0.00 |
May | 2333.00 | 31-MAY-18:04 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 0.00 |
June | 2725.09 | 15-JUN-18:17 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 0.00 |
July | 2709.08 | 26-JUL-18:04 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 0.00 |
August | 2877.87 | 27-AUG-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 | 0.00 |
September | 3496.90 | 20-SEP-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 | 0.00 |
October | 3613.32 | 18-OCT-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 0.00 |
November | 3375.30 | 10-NOV-12:00 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 |
December | 2520.78 | 16-DEC-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2228.87 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3613.32 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 101.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1374.91 | 12-JAN-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 |
February | 1538.40 | 21-FEB-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 |
March | 1607.72 | 16-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 |
April | 1944.93 | 28-APR-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 |
May | 2137.56 | 19-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
June | 2348.67 | 15-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 0.00 |
July | 2302.18 | 26-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 0.00 |
August | 2338.14 | 07-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 0.00 |
September | 2218.01 | 20-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
October | 2143.20 | 05-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
November | 1804.36 | 09-NOV-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 |
December | 1215.61 | 07-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1215.61 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2348.67 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 59.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 908.94 | 03-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.54 |
February | 966.64 | 20-FEB-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 |
March | 1007.26 | 16-MAR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
April | 1193.80 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 |
May | 1766.05 | 31-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
June | 2140.36 | 15-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 0.00 |
July | 2097.30 | 03-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 0.00 |
August | 2065.22 | 07-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 0.00 |
September | 1738.16 | 22-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
October | 1528.84 | 05-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 1065.86 | 10-NOV-11:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 |
December | 891.68 | 10-DEC-11:35 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 891.68 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2140.36 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 76.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 525.16 | 01-JAN-11:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 |
February | 567.98 | 20-FEB-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
March | 586.91 | 16-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
April | 696.20 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 0.00 |
May | 794.85 | 31-MAY-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
June | 1036.18 | 15-JUN-18:40 | 171.36 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 | 0.00 |
July | 1028.75 | 03-JUL-18:30 | 342.72 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 | 0.00 |
August | 1003.88 | 07-AUG-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | 0.00 |
September | 769.12 | 22-SEP-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
October | 726.12 | 05-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 |
November | 623.42 | 10-NOV-11:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
December | 521.17 | 10-DEC-11:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 521.17 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1036.18 | 342.72 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 | 43.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37438.29 | 12-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.91 |
February | 37785.75 | 21-FEB-20:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 |
March | 37928.62 | 16-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 88.01 |
April | 38706.67 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 12.61 | 0.00 |
May | 39027.30 | 30-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 61.20 | 0.00 |
June | 39420.49 | 15-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.81 | 0.00 |
July | 39357.69 | 03-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 53.78 | 0.00 |
August | 39295.16 | 04-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 114.36 | 0.00 |
September | 38965.51 | 20-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 20.15 | 0.00 |
October | 38739.25 | 05-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
November | 38077.98 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
December | 37236.48 | 15-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 125.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37236.48 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39420.49 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 120.81 | 148.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11279.27 | 01-JAN-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.24 |
February | 11297.62 | 20-FEB-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.40 |
March | 10186.82 | 14-MAR-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 11125.73 | 19-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 91.34 | 0.00 |
May | 11479.64 | 19-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 130.00 | 0.00 |
June | 12083.12 | 15-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.22 | 0.00 |
July | 12005.19 | 25-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 163.86 | 0.00 |
August | 12428.58 | 07-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.88 | 0.00 |
September | 12257.79 | 19-SEP-15:04 | 42690.00 | 519.91 | 1778.13 | 0.00 | 0.00 | 0.00 | 0.00 | 204.98 | 0.00 |
October | 12804.85 | 18-OCT-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 108.85 | 0.00 |
November | 12653.76 | 11-NOV-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.12 |
December | 10935.50 | 16-DEC-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10186.82 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12804.85 | 51228.00 | 1134.35 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 204.98 | 264.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31771.73 | 03-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.80 |
February | 33210.59 | 07-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.99 |
March | 34010.32 | 16-MAR-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.09 |
April | 37980.93 | 21-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 57.20 | 0.00 |
May | 40950.48 | 31-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 262.55 | 0.00 |
June | 43451.00 | 15-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 0.00 |
July | 43102.40 | 26-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 293.47 | 0.00 |
August | 43867.01 | 07-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 456.68 | 0.00 |
September | 41985.93 | 21-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 | 0.00 |
October | 41263.54 | 05-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 |
November | 37530.55 | 09-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.23 |
December | 30112.27 | 15-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30112.27 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43867.01 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 770.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2156.47 | 12-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
February | 2237.97 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
March | 2231.18 | 16-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
April | 2263.48 | 16-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 0.00 |
May | 2268.08 | 08-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 | 0.00 |
June | 2300.96 | 15-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 | 0.00 |
July | 2262.32 | 27-JUL-18:02 | 693.00 | 791.58 | 605.82 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 0.00 |
August | 2260.14 | 28-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 | 0.00 |
September | 2267.09 | 01-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 | 0.00 |
October | 2252.17 | 31-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
November | 2238.38 | 09-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
December | 2129.84 | 16-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2129.84 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2300.96 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 | 49.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2089.20 | 12-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
February | 2177.64 | 20-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
March | 2180.15 | 16-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
April | 2419.25 | 06-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.18 |
May | 2393.19 | 20-MAY-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 | 0.00 |
June | 2537.13 | 19-JUN-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
July | 2253.90 | 12-JUL-08:11 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 0.00 |
August | 2331.34 | 26-AUG-08:11 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
September | 2261.66 | 29-SEP-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 |
October | 2230.57 | 05-OCT-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
November | 2144.30 | 07-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
December | 2066.90 | 16-DEC-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2066.90 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2537.13 | 1440.00 | 1582.97 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 60.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 489.13 | 12-JAN-14:25 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 |
February | 464.77 | 07-FEB-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
March | 364.40 | 16-MAR-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
April | 348.40 | 04-APR-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
May | 335.72 | 19-MAY-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
June | 380.10 | 15-JUN-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 0.00 |
July | 382.47 | 02-JUL-20:30 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 | 0.00 |
August | 406.38 | 27-AUG-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
September | 513.66 | 19-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
October | 578.65 | 22-OCT-13:15 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 540.08 | 09-NOV-13:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
December | 407.54 | 16-DEC-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 335.72 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 578.65 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 20.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 731.23 | 13-JAN-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 |
February | 793.17 | 22-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
March | 824.48 | 15-MAR-21:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
April | 847.98 | 21-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 0.00 |
May | 893.16 | 20-MAY-08:51 | 486.00 | 563.59 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 0.00 |
June | 913.18 | 14-JUN-08:11 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 0.00 |
July | 877.44 | 06-JUL-08:61 | 324.00 | 442.82 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 0.00 |
August | 867.60 | 29-AUG-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
September | 852.08 | 20-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 0.00 |
October | 850.99 | 04-OCT-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 |
November | 805.35 | 09-NOV-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 0.00 |
December | 735.63 | 16-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 731.23 | 324.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 913.18 | 1440.00 | 599.37 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 23.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1894.25 | 03-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 |
February | 1953.88 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
March | 1955.98 | 16-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 1995.71 | 21-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 | 0.00 |
May | 2031.62 | 20-MAY-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 | 0.00 |
June | 2047.95 | 15-JUN-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 | 0.00 |
July | 2050.72 | 11-JUL-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 | 0.00 |
August | 2042.55 | 06-AUG-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 0.00 |
September | 2030.95 | 05-SEP-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 |
October | 2012.38 | 05-OCT-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
November | 1962.01 | 09-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 0.00 |
December | 1896.00 | 16-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1894.25 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2050.72 | 583.20 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 | 89.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1762.98 | 31-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.53 |
February | 1921.29 | 22-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 1915.19 | 22-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 0.00 |
April | 2332.81 | 27-APR-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.30 |
May | 2412.67 | 20-MAY-08:32 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 |
June | 2410.55 | 20-JUN-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
July | 2330.80 | 04-JUL-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
August | 2342.43 | 30-AUG-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 |
September | 2301.86 | 19-SEP-08:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
October | 2239.14 | 03-OCT-08:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
November | 2059.18 | 09-NOV-09:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
December | 1792.61 | 16-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1762.98 | 216.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2412.67 | 680.40 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 86.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1696.80 | 01-JAN-11:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
February | 1800.16 | 20-FEB-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 |
March | 1848.96 | 16-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
April | 2166.13 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 0.00 |
May | 2290.00 | 20-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.92 | 0.00 |
June | 3136.38 | 15-JUN-18:40 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.79 | 0.00 |
July | 2855.90 | 26-JUL-18:25 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.99 | 0.00 |
August | 2903.80 | 07-AUG-18:25 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 0.00 |
September | 2600.31 | 20-SEP-18:06 | 8801.94 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | 0.00 |
October | 2275.28 | 05-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 0.00 |
November | 1962.58 | 10-NOV-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
December | 1624.26 | 10-DEC-11:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1624.26 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3136.38 | 8801.94 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.79 | 60.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2278.93 | 12-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
February | 2363.88 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
March | 2360.01 | 14-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
April | 2403.91 | 16-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 0.00 |
May | 2403.43 | 17-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 | 0.00 |
June | 2443.92 | 15-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 | 0.00 |
July | 2398.06 | 27-JUL-18:02 | 693.00 | 791.58 | 605.82 | 0.00 | 0.00 | 0.00 | 0.00 | 54.39 | 0.00 |
August | 2387.03 | 28-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 | 0.00 |
September | 2391.41 | 14-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 0.00 |
October | 2371.67 | 31-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 |
November | 2363.63 | 09-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
December | 2246.94 | 16-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2246.94 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2443.92 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 | 49.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2193.67 | 12-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.41 |
February | 2291.58 | 20-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
March | 2289.77 | 16-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 2556.12 | 06-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 |
May | 2517.09 | 20-MAY-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 |
June | 2686.20 | 19-JUN-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
July | 2431.98 | 25-JUL-18:02 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 | 0.00 |
August | 2445.81 | 26-AUG-08:11 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 |
September | 2373.04 | 01-SEP-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 0.00 |
October | 2318.31 | 05-OCT-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
November | 2249.31 | 07-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
December | 2139.49 | 16-DEC-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2139.49 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2686.20 | 1440.00 | 1582.97 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 | 60.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1210.39 | 03-JAN-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
February | 1246.78 | 20-FEB-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
March | 1247.90 | 14-MAR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
April | 1241.76 | 03-APR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
May | 1225.88 | 17-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 |
June | 1232.81 | 14-JUN-15:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 43.10 | 0.00 |
July | 1239.69 | 26-JUL-15:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 | 0.00 |
August | 1244.19 | 30-AUG-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 0.00 |
September | 1254.22 | 06-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 0.00 |
October | 1263.90 | 18-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 0.00 |
November | 1240.97 | 07-NOV-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
December | 1204.99 | 16-DEC-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1204.99 | 324.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1263.90 | 583.20 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 43.10 | 26.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18278.30 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.46 |
February | 19374.90 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.17 |
March | 20264.81 | 15-MAR-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 |
April | 22231.54 | 19-APR-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.24 | 0.00 |
May | 23230.89 | 31-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 0.00 |
June | 23859.79 | 15-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 108.49 | 0.00 |
July | 23646.39 | 25-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 | 0.00 |
August | 23802.87 | 07-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 0.00 |
September | 22615.81 | 22-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
October | 22097.16 | 04-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
November | 20224.37 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 |
December | 18220.97 | 15-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18220.97 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23859.79 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 108.49 | 174.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20080.98 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.47 |
February | 21077.90 | 06-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.30 |
March | 21843.37 | 15-MAR-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 |
April | 23601.55 | 19-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 0.00 |
May | 24433.66 | 19-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.47 | 0.00 |
June | 25044.27 | 15-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 0.00 |
July | 24807.20 | 25-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.69 | 0.00 |
August | 24969.94 | 07-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.79 | 0.00 |
September | 23742.19 | 22-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
October | 23261.38 | 04-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
November | 21719.25 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.62 |
December | 20061.87 | 15-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20061.87 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25044.27 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 174.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27401.03 | 01-JAN-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 134.11 |
February | 28441.40 | 20-FEB-11:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 |
March | 28657.86 | 19-MAR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 |
April | 30299.20 | 30-APR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 5.74 | 0.00 |
May | 30471.53 | 21-MAY-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 68.27 | 0.00 |
June | 30976.30 | 18-JUN-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 107.11 | 0.00 |
July | 31144.57 | 02-JUL-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 101.91 | 0.00 |
August | 31042.81 | 06-AUG-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.69 | 0.00 |
September | 30711.22 | 17-SEP-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
October | 30136.16 | 05-OCT-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 44.93 | 0.00 |
November | 28257.94 | 10-NOV-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 40.08 |
December | 27350.69 | 10-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27350.69 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31144.57 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 107.11 | 134.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3475.90 | 01-JAN-11:35 | 1596.96 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.93 |
February | 3810.02 | 20-FEB-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.42 |
March | 3834.20 | 16-MAR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 |
April | 4617.81 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
May | 5718.86 | 30-MAY-15:02 | 5323.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.38 | 0.00 |
June | 6601.74 | 17-JUN-17:15 | 3193.92 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.91 | 0.00 |
July | 6949.09 | 03-JUL-12:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.15 | 0.00 |
August | 6793.76 | 07-AUG-15:04 | 6654.00 | 2744.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.67 | 0.00 |
September | 6282.62 | 21-SEP-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.77 | 0.00 |
October | 5818.93 | 05-OCT-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.57 | 0.00 |
November | 4141.86 | 10-NOV-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 |
December | 3381.33 | 10-DEC-11:35 | 1596.96 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3381.33 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6949.09 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.15 | 107.93 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.362092E+12 | 252045.91 | 03-JAN-20:40 | 0.618873E+12 | 522309.66 | 26-JAN-17:00 |
February | 0.338508E+12 | 268530.79 | 06-FEB-20:10 | 0.503621E+12 | 545543.43 | 01-FEB-18:49 |
March | 0.386272E+12 | 283994.29 | 15-MAR-19:10 | 0.517868E+12 | 509690.93 | 01-MAR-17:40 |
April | 0.448990E+12 | 352160.22 | 19-APR-19:10 | 0.418143E+12 | 400965.65 | 10-APR-20:00 |
May | 0.535438E+12 | 378479.56 | 19-MAY-19:10 | 0.388685E+12 | 346675.21 | 01-MAY-17:40 |
June | 0.588071E+12 | 403191.86 | 05-JUN-19:10 | 0.364081E+12 | 319634.09 | 08-JUN-17:19 |
July | 0.637742E+12 | 404811.92 | 25-JUL-19:10 | 0.369469E+12 | 316288.76 | 10-JUL-17:10 |
August | 0.600238E+12 | 399312.60 | 04-AUG-19:19 | 0.369782E+12 | 316774.43 | 31-AUG-17:30 |
September | 0.541309E+12 | 373902.82 | 22-SEP-19:30 | 0.365863E+12 | 319459.68 | 29-SEP-17:19 |
October | 0.462965E+12 | 369301.99 | 04-OCT-19:10 | 0.406611E+12 | 347099.05 | 31-OCT-17:40 |
November | 0.373829E+12 | 291334.97 | 09-NOV-20:19 | 0.510160E+12 | 516281.38 | 27-NOV-17:40 |
December | 0.363480E+12 | 242787.08 | 15-DEC-20:10 | 0.585949E+12 | 540451.46 | 03-DEC-18:00 |
Annual Sum or Average | 0.563893E+13 | 0.541910E+13 | ||||
Minimum of Months | 0.338508E+12 | 242787.08 | 0.364081E+12 | 316288.76 | ||
Maximum of Months | 0.637742E+12 | 404811.92 | 0.618873E+12 | 545543.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670636E+11 | 0.190555E+11 | 0.140828E+12 | 0.544239E+11 | 0.409948E+11 | 0.589304E+10 | 0.00 | 0.123852E+11 | 0.00 | 0.00 | 0.855685E+10 | 0.770459E+10 | 0.00 |
February | 0.603762E+11 | 0.163016E+11 | 0.127191E+12 | 0.491570E+11 | 0.373478E+11 | 0.573533E+10 | 0.00 | 0.244394E+11 | 0.00 | 0.00 | 0.632387E+10 | 0.696209E+10 | 0.00 |
March | 0.665913E+11 | 0.167531E+11 | 0.140882E+12 | 0.544262E+11 | 0.421063E+11 | 0.682803E+10 | 0.00 | 0.405335E+11 | 0.00 | 0.00 | 0.527543E+10 | 0.770305E+10 | 0.00 |
April | 0.641117E+11 | 0.149098E+11 | 0.136245E+12 | 0.526676E+11 | 0.469163E+11 | 0.713116E+10 | 0.00 | 0.106538E+12 | 0.00 | 0.00 | 0.798384E+10 | 0.746497E+10 | 0.00 |
May | 0.660692E+11 | 0.142879E+11 | 0.140860E+12 | 0.544246E+11 | 0.546562E+11 | 0.762476E+10 | 0.00 | 0.170668E+12 | 0.00 | 0.00 | 0.138944E+11 | 0.770426E+10 | 0.00 |
June | 0.637940E+11 | 0.132663E+11 | 0.136336E+12 | 0.526698E+11 | 0.596244E+11 | 0.773714E+10 | 0.00 | 0.223300E+12 | 0.00 | 0.00 | 0.187611E+11 | 0.745688E+10 | 0.00 |
July | 0.659690E+11 | 0.139548E+11 | 0.140770E+12 | 0.544220E+11 | 0.611761E+11 | 0.813867E+10 | 0.00 | 0.259516E+12 | 0.00 | 0.00 | 0.207458E+11 | 0.771234E+10 | 0.00 |
August | 0.662325E+11 | 0.149098E+11 | 0.140892E+12 | 0.544260E+11 | 0.608428E+11 | 0.799802E+10 | 0.00 | 0.224795E+12 | 0.00 | 0.00 | 0.170911E+11 | 0.770439E+10 | 0.00 |
September | 0.643709E+11 | 0.156353E+11 | 0.136256E+12 | 0.526678E+11 | 0.573362E+11 | 0.756448E+10 | 0.00 | 0.183053E+12 | 0.00 | 0.00 | 0.117984E+11 | 0.746629E+10 | 0.00 |
October | 0.668408E+11 | 0.175157E+11 | 0.140818E+12 | 0.544237E+11 | 0.527921E+11 | 0.741636E+10 | 0.00 | 0.104843E+12 | 0.00 | 0.00 | 0.533240E+10 | 0.770291E+10 | 0.00 |
November | 0.647677E+11 | 0.180857E+11 | 0.136330E+12 | 0.526689E+11 | 0.441708E+11 | 0.617181E+10 | 0.00 | 0.332710E+11 | 0.00 | 0.00 | 0.589622E+10 | 0.744904E+10 | 0.00 |
December | 0.669963E+11 | 0.193368E+11 | 0.140770E+12 | 0.544227E+11 | 0.415375E+11 | 0.570414E+10 | 0.00 | 0.952320E+10 | 0.00 | 0.00 | 0.123025E+11 | 0.771270E+10 | 0.00 |
Annual Sum or Average | 0.783183E+12 | 0.194012E+12 | 0.165818E+13 | 0.640800E+12 | 0.599501E+12 | 0.839429E+11 | 0.00 | 0.139286E+13 | 0.00 | 0.00 | 0.133962E+12 | 0.907435E+11 | 0.00 |
Minimum of Months | 0.603762E+11 | 0.132663E+11 | 0.127191E+12 | 0.491570E+11 | 0.373478E+11 | 0.570414E+10 | 0.00 | 0.952320E+10 | 0.00 | 0.00 | 0.527543E+10 | 0.696209E+10 | 0.00 |
Maximum of Months | 0.670636E+11 | 0.193368E+11 | 0.140892E+12 | 0.544262E+11 | 0.611761E+11 | 0.813867E+10 | 0.00 | 0.259516E+12 | 0.00 | 0.00 | 0.207458E+11 | 0.771270E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.201447E+12 | 0.00 | 0.265508E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.126640E+12 | 0.00 | 0.239777E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.106558E+12 | 0.00 | 0.259287E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.310103E+11 | 0.00 | 0.240177E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.139145E+10 | 0.00 | 0.235316E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 9744076.80 | 0.00 | 0.216957E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 3922199.84 | 0.00 | 0.217644E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 10405943.27 | 0.00 | 0.217733E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.190105E+10 | 0.00 | 0.216991E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.193641E+11 | 0.00 | 0.235344E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.122887E+12 | 0.00 | 0.240181E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.174913E+12 | 0.00 | 0.259215E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.786136E+12 | 0.00 | 0.284413E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 3922199.84 | 0.00 | 0.216957E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.201447E+12 | 0.00 | 0.265508E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 28644.87 | 03-JAN-22:10 | 3386.76 | 06-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 30733.42 | 22-FEB-22:10 | 3366.62 | 05-FEB-01:10 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 31805.62 | 15-MAR-21:00 | 3352.79 | 15-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.86 | 04-APR-06:19 | 38851.40 | 19-APR-21:10 | 3672.47 | 28-APR-18:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.68 | 03-MAY-06:19 | 42189.97 | 31-MAY-21:10 | 3931.93 | 19-MAY-19:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.30 | 28-JUN-06:19 | 48928.11 | 16-JUN-21:10 | 4108.86 | 05-JUN-19:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:19 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.59 | 18-JUL-06:19 | 47730.57 | 26-JUL-21:10 | 3947.80 | 21-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.86 | 14-AUG-06:19 | 50793.89 | 07-AUG-21:10 | 4033.91 | 22-AUG-19:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 25-SEP-06:19 | 48795.69 | 22-SEP-21:10 | 3782.73 | 17-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 45795.70 | 05-OCT-21:00 | 3824.69 | 01-OCT-19:10 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 38711.04 | 09-NOV-22:00 | 3394.57 | 25-NOV-09:20 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 11-DEC-07:19 | 29052.69 | 15-DEC-22:10 | 3384.95 | 27-DEC-17:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.30 | 28644.87 | 3352.79 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 50793.89 | 4108.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 51735.33 | 03-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 02-JAN-01:49 | 4738.31 | 25-JAN-07:10 | 0.00 |
February | 73047.44 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-01:39 | 4738.33 | 13-FEB-07:10 | 0.00 |
March | 76777.09 | 22-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-02:39 | 4738.62 | 23-MAR-18:10 | 0.00 |
April | 111084.97 | 21-APR-15:20 | 0.00 | 0.00 | 9938.94 | 01-APR-12:09 | 4738.73 | 06-APR-18:10 | 0.00 |
May | 132693.67 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 02-MAY-15:20 | 4738.73 | 11-MAY-18:10 | 0.00 |
June | 157627.30 | 14-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.49 | 22-JUN-18:10 | 0.00 |
July | 157409.69 | 26-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.64 | 20-JUL-18:10 | 0.00 |
August | 150092.91 | 04-AUG-18:19 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.60 | 31-AUG-18:10 | 0.00 |
September | 129577.12 | 20-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-08:30 | 4738.68 | 28-SEP-18:10 | 0.00 |
October | 127403.76 | 04-OCT-18:19 | 0.00 | 0.00 | 9938.94 | 01-OCT-09:50 | 4738.63 | 05-OCT-18:10 | 0.00 |
November | 77316.94 | 09-NOV-16:10 | 0.00 | 0.00 | 9938.94 | 03-NOV-15:50 | 4738.23 | 29-NOV-07:10 | 0.00 |
December | 29033.45 | 23-DEC-14:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-05:19 | 4738.32 | 08-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 29033.45 | 0.00 | 0.00 | 9938.94 | 4738.23 | 0.00 | |||
Maximum of Months | 157627.30 | 0.00 | 0.00 | 9938.94 | 4738.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 252045.91 | 03-JAN-20:40 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 25616.22 | 2724.01 | 0.00 | 23064.95 | 0.00 |
February | 268530.79 | 06-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23128.99 | 2678.07 | 0.00 | 41538.46 | 0.00 |
March | 283994.29 | 15-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23249.68 | 2715.69 | 0.00 | 57162.68 | 0.00 |
April | 352160.22 | 19-APR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 32302.10 | 3061.49 | 0.00 | 105707.41 | 0.00 |
May | 378479.56 | 19-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 37287.47 | 3931.93 | 0.00 | 126949.39 | 0.00 |
June | 403191.86 | 05-JUN-19:10 | 64632.59 | 86439.81 | 12338.45 | 31546.78 | 37678.34 | 4108.86 | 0.00 | 150093.13 | 0.00 |
July | 404811.92 | 25-JUL-19:10 | 64632.59 | 86439.81 | 12338.45 | 31546.49 | 40536.57 | 3507.15 | 0.00 | 150311.91 | 0.00 |
August | 399312.60 | 04-AUG-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 43044.25 | 3405.95 | 0.00 | 142136.94 | 0.00 |
September | 373902.82 | 22-SEP-19:30 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 39141.73 | 3492.21 | 0.00 | 120818.50 | 0.00 |
October | 369301.99 | 04-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 35133.41 | 3443.35 | 0.00 | 119710.33 | 0.00 |
November | 291334.97 | 09-NOV-20:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 29804.57 | 2733.02 | 0.00 | 57484.20 | 0.00 |
December | 242787.08 | 15-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23843.55 | 2663.71 | 0.00 | 15639.61 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 242787.08 | 64632.59 | 86439.81 | 12338.45 | 31546.49 | 23128.99 | 2663.71 | 0.00 | 15639.61 | 0.00 | |
Maximum of Months | 404811.92 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 43044.25 | 4108.86 | 0.00 | 150311.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 207861.88 | 22-JAN-01:10 | 0.00 | 248619.64 | 23-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 207436.51 | 05-FEB-01:10 | 0.00 | 247902.28 | 07-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 206550.96 | 15-MAR-06:10 | 0.00 | 247287.16 | 01-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 203030.94 | 07-APR-06:10 | 0.00 | 245568.22 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 83831.24 | 02-MAY-05:00 | 0.00 | 243236.39 | 04-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 2960.97 | 29-JUN-08:09 | 0.00 | 218938.66 | 01-JUN-19:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1399.12 | 19-JUL-08:09 | 0.00 | 212823.02 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 3326.71 | 14-AUG-08:09 | 0.00 | 212991.26 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 107761.98 | 30-SEP-05:00 | 0.00 | 220765.90 | 30-SEP-21:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 190310.99 | 25-OCT-06:10 | 0.00 | 243495.87 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 201597.41 | 25-NOV-09:20 | 0.00 | 245680.34 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 210090.42 | 25-DEC-00:10 | 0.00 | 247223.93 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1399.12 | 0.00 | 212823.02 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 210090.42 | 0.00 | 248619.64 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 22.02 | 15.17 | 22.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 22.13 | 32.67 | 22.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 22.14 | 57.33 | 22.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 21.93 | 36.50 | 21.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 22.07 | 38.67 | 22.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 22.13 | 33.17 | 22.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 22.10 | 19.17 | 22.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.89 | 0.83 | 21.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 234.50 | 22.08 | 234.50 | 22.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 22.14 | 57.33 | 22.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 21.97 | 14.33 | 21.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 22.14 | 36.50 | 22.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 22.18 | 65.67 | 22.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 21.96 | 43.83 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 22.02 | 39.33 | 22.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.00 | 25.83 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.93 | 5.33 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.05 | 0.17 | 22.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 231.00 | 22.06 | 231.00 | 22.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 22.18 | 65.67 | 22.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.79 | 4.00 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 21.83 | 13.67 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 21.90 | 22.17 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 21.85 | 18.67 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 21.81 | 14.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 21.75 | 12.33 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.73 | 4.33 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 89.33 | 21.83 | 89.33 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 21.90 | 22.17 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.90 | 6.83 | 21.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 21.98 | 22.17 | 21.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 21.96 | 45.67 | 21.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 21.92 | 27.67 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 21.93 | 24.83 | 21.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 21.91 | 21.67 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 21.87 | 9.33 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.86 | 1.33 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Annual Sum or Average | 0.00 | 0.00 | 160.17 | 21.94 | 160.17 | 21.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 21.98 | 45.67 | 21.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.15 | 9.33 | 22.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 22.21 | 35.83 | 22.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 22.18 | 76.00 | 22.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 22.18 | 51.33 | 22.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 | 22.22 | 38.83 | 22.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 22.26 | 26.33 | 22.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.06 | 5.17 | 22.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.04 | 0.33 | 22.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 243.17 | 22.20 | 243.17 | 22.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 22.26 | 76.00 | 22.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 22.17 | 16.33 | 22.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 22.20 | 36.33 | 22.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 22.27 | 63.17 | 22.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 22.03 | 44.50 | 22.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 22.14 | 44.50 | 22.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 22.18 | 39.50 | 22.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.13 | 21.83 | 22.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.93 | 0.83 | 21.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 268.17 | 22.17 | 268.17 | 22.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 22.27 | 63.17 | 22.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 22.14 | 15.50 | 22.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 22.22 | 39.50 | 22.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 22.32 | 70.00 | 22.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 22.07 | 51.50 | 22.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 22.09 | 45.67 | 22.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 22.06 | 28.00 | 22.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.95 | 5.83 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.01 | 0.17 | 22.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 256.17 | 22.17 | 256.17 | 22.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 22.32 | 70.00 | 22.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.96 | 5.50 | 21.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.91 | 1.67 | 21.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.88 | 5.67 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 21.91 | 11.50 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 21.97 | 25.00 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 21.89 | 12.17 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 21.93 | 15.00 | 21.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 22.03 | 26.00 | 22.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 22.18 | 31.50 | 22.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.97 | 10.00 | 21.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
Annual Sum or Average | 0.00 | 0.00 | 148.33 | 22.00 | 148.33 | 22.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.80 | 1.67 | 21.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 22.18 | 31.50 | 22.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 705.67 | 23.75 | 0.00 | 23.75 | 0.00 | 23.75 |
February | 672.00 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
March | 744.00 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
April | 720.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
May | 744.00 | 22.64 | 10.67 | 22.64 | 10.67 | 22.65 |
June | 707.17 | 22.94 | 64.67 | 22.95 | 64.67 | 22.97 |
July | 427.00 | 23.78 | 515.17 | 23.82 | 384.67 | 23.83 |
August | 240.33 | 23.98 | 607.17 | 23.95 | 236.17 | 23.96 |
September | 221.00 | 24.00 | 495.33 | 23.99 | 220.50 | 23.99 |
October | 117.33 | 23.99 | 299.33 | 23.99 | 49.50 | 23.99 |
November | 458.67 | 23.99 | 15.00 | 23.99 | 0.00 | 23.99 |
December | 619.67 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 6376.83 | 23.17 | 2007.33 | 23.35 | 966.17 | 23.40 |
Minimum of Months | 117.33 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
Maximum of Months | 744.00 | 24.00 | 607.17 | 23.99 | 384.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 641.67 | 21.64 | 43.83 | 21.70 | 21.17 | 21.68 |
February | 580.17 | 21.79 | 15.50 | 21.79 | 12.00 | 21.77 |
March | 669.17 | 21.91 | 21.00 | 21.88 | 21.00 | 21.86 |
April | 543.00 | 22.47 | 33.50 | 22.55 | 0.67 | 22.55 |
May | 371.83 | 22.82 | 205.00 | 23.19 | 9.33 | 23.19 |
June | 114.50 | 23.23 | 508.67 | 23.73 | 42.83 | 23.71 |
July | 366.17 | 23.59 | 740.00 | 23.70 | 365.67 | 23.67 |
August | 245.17 | 23.36 | 661.50 | 23.64 | 211.50 | 23.60 |
September | 301.17 | 23.23 | 578.33 | 23.58 | 212.83 | 23.54 |
October | 394.00 | 22.48 | 290.50 | 23.07 | 47.00 | 23.09 |
November | 541.33 | 21.90 | 78.33 | 22.09 | 15.33 | 22.07 |
December | 657.33 | 21.56 | 56.00 | 21.52 | 56.00 | 21.48 |
Annual Sum or Average | 5425.50 | 22.26 | 3232.17 | 22.79 | 1015.33 | 22.83 |
Minimum of Months | 114.50 | 21.56 | 15.50 | 21.52 | 0.67 | 21.48 |
Maximum of Months | 669.17 | 23.59 | 740.00 | 23.73 | 365.67 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.33 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
February | 666.83 | 22.95 | 0.00 | 22.95 | 0.00 | 22.95 |
March | 739.50 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
April | 558.33 | 23.40 | 11.50 | 23.41 | 0.00 | 23.41 |
May | 282.33 | 23.54 | 175.17 | 23.68 | 22.50 | 23.69 |
June | 132.17 | 23.85 | 424.67 | 23.92 | 71.00 | 23.92 |
July | 415.50 | 23.95 | 732.83 | 23.92 | 415.50 | 23.93 |
August | 281.50 | 23.90 | 676.67 | 23.90 | 279.67 | 23.90 |
September | 279.17 | 23.91 | 532.50 | 23.91 | 254.83 | 23.92 |
October | 298.17 | 23.47 | 237.33 | 23.64 | 81.17 | 23.66 |
November | 632.00 | 23.15 | 4.00 | 23.16 | 0.00 | 23.16 |
December | 744.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
Annual Sum or Average | 5765.83 | 23.22 | 2794.67 | 23.44 | 1124.67 | 23.50 |
Minimum of Months | 132.17 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 744.00 | 23.95 | 732.83 | 23.92 | 415.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 21.17 | 21.44 | 21.17 | 21.43 |
February | 672.00 | 21.66 | 15.00 | 21.65 | 15.00 | 21.63 |
March | 744.00 | 21.91 | 6.83 | 21.90 | 6.83 | 21.90 |
April | 720.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
May | 525.00 | 23.43 | 43.17 | 23.47 | 0.83 | 23.47 |
June | 136.00 | 23.89 | 240.83 | 23.93 | 11.67 | 23.92 |
July | 261.50 | 23.92 | 723.83 | 23.94 | 261.50 | 23.93 |
August | 138.83 | 23.76 | 506.83 | 23.87 | 128.83 | 23.86 |
September | 335.50 | 23.60 | 380.00 | 23.72 | 148.33 | 23.73 |
October | 640.50 | 22.96 | 57.50 | 23.03 | 12.00 | 23.04 |
November | 720.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
December | 744.00 | 21.34 | 23.67 | 21.33 | 23.67 | 21.32 |
Annual Sum or Average | 6381.33 | 22.37 | 2018.83 | 22.72 | 629.83 | 22.77 |
Minimum of Months | 136.00 | 21.34 | 0.00 | 21.33 | 0.00 | 21.32 |
Maximum of Months | 744.00 | 23.92 | 723.83 | 23.94 | 261.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 25.67 | 21.26 | 25.67 | 21.25 |
February | 672.00 | 21.47 | 24.33 | 21.46 | 24.33 | 21.44 |
March | 744.00 | 21.70 | 9.17 | 21.69 | 9.17 | 21.68 |
April | 720.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
May | 608.50 | 23.28 | 17.00 | 23.29 | 1.83 | 23.29 |
June | 162.00 | 23.76 | 185.67 | 23.84 | 14.50 | 23.83 |
July | 289.17 | 23.83 | 716.83 | 23.87 | 289.17 | 23.86 |
August | 190.33 | 23.62 | 455.83 | 23.76 | 142.83 | 23.74 |
September | 392.67 | 23.42 | 306.67 | 23.53 | 165.33 | 23.54 |
October | 664.17 | 22.76 | 37.83 | 22.81 | 15.17 | 22.82 |
November | 720.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
December | 744.00 | 21.19 | 34.33 | 21.18 | 34.33 | 21.18 |
Annual Sum or Average | 6650.83 | 22.24 | 1813.33 | 22.55 | 722.33 | 22.61 |
Minimum of Months | 162.00 | 21.19 | 0.00 | 21.18 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.83 | 716.83 | 23.87 | 289.17 | 23.86 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 218.33 | 23.27 | 630.50 | 23.54 | 156.67 | 23.61 |
February | 191.50 | 23.34 | 568.00 | 23.58 | 142.33 | 23.65 |
March | 212.50 | 23.37 | 628.17 | 23.59 | 158.50 | 23.66 |
April | 226.50 | 23.78 | 639.33 | 23.68 | 205.00 | 23.74 |
May | 298.50 | 23.95 | 696.33 | 23.70 | 293.83 | 23.76 |
June | 365.67 | 23.93 | 708.17 | 23.66 | 365.67 | 23.73 |
July | 573.50 | 23.66 | 744.00 | 23.57 | 573.50 | 23.59 |
August | 492.00 | 23.75 | 744.00 | 23.59 | 492.00 | 23.63 |
September | 460.17 | 23.75 | 712.50 | 23.59 | 460.17 | 23.63 |
October | 332.17 | 23.93 | 706.83 | 23.66 | 330.00 | 23.73 |
November | 215.83 | 23.49 | 620.83 | 23.61 | 171.83 | 23.68 |
December | 212.33 | 23.17 | 617.17 | 23.52 | 145.17 | 23.60 |
Annual Sum or Average | 3799.00 | 23.67 | 8015.83 | 23.61 | 3494.67 | 23.67 |
Minimum of Months | 191.50 | 23.17 | 568.00 | 23.52 | 142.33 | 23.59 |
Maximum of Months | 573.50 | 23.95 | 744.00 | 23.70 | 573.50 | 23.76 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.67 | 22.95 | 86.67 | 23.11 | 0.00 | 23.11 |
February | 415.17 | 23.10 | 64.33 | 23.22 | 1.33 | 23.22 |
March | 447.67 | 23.07 | 52.33 | 23.17 | 0.33 | 23.17 |
April | 251.67 | 23.18 | 183.83 | 23.51 | 0.00 | 23.51 |
May | 185.50 | 23.47 | 425.67 | 23.75 | 86.67 | 23.76 |
June | 188.83 | 23.85 | 640.33 | 23.86 | 180.00 | 23.86 |
July | 603.17 | 23.88 | 743.67 | 23.87 | 603.17 | 23.87 |
August | 449.83 | 23.83 | 740.83 | 23.85 | 449.67 | 23.85 |
September | 382.00 | 23.90 | 687.33 | 23.93 | 376.67 | 23.92 |
October | 227.50 | 23.57 | 554.50 | 23.82 | 169.33 | 23.83 |
November | 310.83 | 22.95 | 207.50 | 23.36 | 2.17 | 23.37 |
December | 546.00 | 22.92 | 69.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 4492.83 | 23.37 | 4456.00 | 23.63 | 1869.33 | 23.68 |
Minimum of Months | 185.50 | 22.92 | 52.33 | 23.04 | 0.00 | 23.04 |
Maximum of Months | 603.17 | 23.90 | 743.67 | 23.93 | 603.17 | 23.92 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 637.50 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
February | 593.17 | 23.38 | 4.00 | 23.38 | 0.00 | 23.38 |
March | 641.17 | 23.34 | 9.33 | 23.35 | 0.00 | 23.35 |
April | 420.67 | 23.45 | 56.83 | 23.51 | 0.00 | 23.51 |
May | 226.17 | 23.51 | 247.50 | 23.71 | 64.00 | 23.73 |
June | 166.67 | 23.83 | 505.50 | 23.89 | 140.67 | 23.89 |
July | 554.83 | 23.91 | 739.67 | 23.88 | 554.83 | 23.89 |
August | 420.50 | 23.89 | 733.17 | 23.88 | 420.50 | 23.88 |
September | 368.67 | 23.93 | 643.00 | 23.93 | 368.50 | 23.93 |
October | 200.50 | 23.72 | 412.50 | 23.86 | 142.50 | 23.87 |
November | 417.67 | 23.40 | 41.67 | 23.46 | 0.00 | 23.46 |
December | 706.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
Annual Sum or Average | 5354.17 | 23.51 | 3393.17 | 23.66 | 1691.00 | 23.70 |
Minimum of Months | 166.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
Maximum of Months | 706.67 | 23.93 | 739.67 | 23.93 | 554.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 117.50 | 21.27 | 117.50 | 21.22 |
February | 671.67 | 21.44 | 83.67 | 21.39 | 83.67 | 21.36 |
March | 744.00 | 21.53 | 44.67 | 21.50 | 44.67 | 21.47 |
April | 695.83 | 21.63 | 0.17 | 21.63 | 0.00 | 21.63 |
May | 660.50 | 21.59 | 9.17 | 21.61 | 0.00 | 21.61 |
June | 575.83 | 21.49 | 34.83 | 21.60 | 0.00 | 21.60 |
July | 571.33 | 21.36 | 81.83 | 21.60 | 9.67 | 21.62 |
August | 572.33 | 21.38 | 66.17 | 21.57 | 5.17 | 21.57 |
September | 558.67 | 21.37 | 75.00 | 21.60 | 7.00 | 21.61 |
October | 665.50 | 21.52 | 28.50 | 21.58 | 7.67 | 21.58 |
November | 710.33 | 21.48 | 52.00 | 21.43 | 52.00 | 21.39 |
December | 744.00 | 21.29 | 212.00 | 21.21 | 212.00 | 21.16 |
Annual Sum or Average | 7914.00 | 21.45 | 805.50 | 21.48 | 539.33 | 21.45 |
Minimum of Months | 558.67 | 21.29 | 0.17 | 21.21 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.63 | 212.00 | 21.63 | 212.00 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 298.67 | 20.91 | 298.67 | 20.86 |
February | 672.00 | 21.25 | 220.83 | 21.16 | 220.83 | 21.10 |
March | 734.50 | 21.57 | 80.83 | 21.51 | 80.17 | 21.45 |
April | 687.00 | 21.87 | 7.00 | 21.91 | 0.00 | 21.91 |
May | 630.50 | 21.82 | 26.50 | 21.91 | 3.00 | 21.92 |
June | 512.50 | 21.59 | 74.50 | 21.87 | 7.00 | 21.89 |
July | 545.00 | 21.65 | 149.50 | 22.06 | 69.33 | 22.22 |
August | 557.00 | 21.68 | 110.33 | 21.99 | 48.83 | 22.10 |
September | 571.17 | 21.83 | 115.33 | 22.10 | 69.83 | 22.21 |
October | 663.67 | 21.86 | 48.50 | 21.96 | 26.50 | 21.98 |
November | 717.50 | 21.38 | 125.17 | 21.30 | 124.17 | 21.24 |
December | 744.00 | 20.92 | 483.17 | 20.85 | 483.17 | 20.83 |
Annual Sum or Average | 7778.83 | 21.51 | 1740.33 | 21.54 | 1431.50 | 21.49 |
Minimum of Months | 512.50 | 20.92 | 7.00 | 20.85 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 21.87 | 483.17 | 22.10 | 483.17 | 22.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 161.50 | 21.06 | 161.50 | 21.04 |
February | 672.00 | 21.23 | 115.83 | 21.18 | 115.83 | 21.15 |
March | 744.00 | 21.44 | 24.83 | 21.42 | 24.83 | 21.41 |
April | 720.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
May | 742.50 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
June | 709.00 | 21.93 | 1.00 | 21.94 | 0.00 | 21.94 |
July | 735.83 | 21.94 | 52.00 | 22.03 | 49.67 | 22.11 |
August | 738.33 | 21.94 | 29.00 | 21.99 | 28.83 | 22.03 |
September | 719.17 | 21.98 | 48.17 | 22.04 | 48.17 | 22.10 |
October | 743.33 | 21.81 | 9.17 | 21.82 | 9.17 | 21.84 |
November | 720.00 | 21.26 | 21.17 | 21.25 | 21.17 | 21.23 |
December | 744.00 | 21.05 | 197.83 | 21.00 | 197.83 | 20.97 |
Annual Sum or Average | 8732.17 | 21.61 | 660.50 | 21.60 | 657.00 | 21.58 |
Minimum of Months | 672.00 | 21.05 | 0.00 | 21.00 | 0.00 | 20.97 |
Maximum of Months | 744.00 | 21.98 | 197.83 | 22.04 | 197.83 | 22.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.38 | 116.00 | 21.32 | 116.00 | 21.27 |
February | 672.00 | 21.52 | 78.50 | 21.48 | 78.50 | 21.44 |
March | 744.00 | 21.61 | 43.33 | 21.58 | 43.33 | 21.56 |
April | 697.67 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 659.17 | 21.58 | 1.50 | 21.59 | 0.00 | 21.59 |
June | 552.17 | 21.38 | 22.33 | 21.46 | 0.00 | 21.46 |
July | 547.17 | 21.26 | 67.00 | 21.48 | 6.67 | 21.49 |
August | 559.83 | 21.28 | 47.50 | 21.43 | 4.67 | 21.43 |
September | 541.33 | 21.28 | 50.33 | 21.46 | 1.83 | 21.46 |
October | 666.00 | 21.52 | 17.67 | 21.53 | 13.00 | 21.53 |
November | 717.67 | 21.54 | 62.00 | 21.48 | 62.00 | 21.44 |
December | 744.00 | 21.32 | 214.33 | 21.25 | 214.33 | 21.20 |
Annual Sum or Average | 7845.00 | 21.46 | 720.50 | 21.47 | 540.33 | 21.44 |
Minimum of Months | 541.33 | 21.26 | 0.00 | 21.25 | 0.00 | 21.20 |
Maximum of Months | 744.00 | 21.69 | 214.33 | 21.69 | 214.33 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 296.00 | 20.92 | 296.00 | 20.89 |
February | 672.00 | 21.28 | 183.83 | 21.21 | 183.83 | 21.16 |
March | 744.00 | 21.63 | 75.50 | 21.57 | 75.50 | 21.52 |
April | 682.67 | 21.94 | 15.83 | 22.01 | 1.83 | 22.01 |
May | 584.50 | 21.77 | 57.83 | 22.10 | 5.17 | 22.14 |
June | 479.67 | 21.56 | 98.83 | 22.09 | 13.67 | 22.19 |
July | 527.83 | 21.75 | 168.50 | 22.30 | 70.17 | 22.52 |
August | 521.17 | 21.65 | 122.17 | 22.14 | 50.33 | 22.30 |
September | 548.17 | 21.93 | 108.17 | 22.33 | 71.00 | 22.53 |
October | 701.00 | 21.91 | 42.00 | 21.97 | 31.17 | 21.98 |
November | 718.33 | 21.34 | 131.00 | 21.27 | 130.17 | 21.21 |
December | 744.00 | 20.90 | 467.83 | 20.86 | 467.83 | 20.84 |
Annual Sum or Average | 7667.33 | 21.53 | 1767.50 | 21.62 | 1396.67 | 21.60 |
Minimum of Months | 479.67 | 20.90 | 15.83 | 20.86 | 1.83 | 20.84 |
Maximum of Months | 744.00 | 21.94 | 467.83 | 22.33 | 467.83 | 22.53 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 18.33 | 21.35 | 18.33 | 21.34 |
February | 672.00 | 21.63 | 2.00 | 21.63 | 2.00 | 21.62 |
March | 744.00 | 21.92 | 1.00 | 21.92 | 1.00 | 21.92 |
April | 720.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
May | 627.50 | 23.34 | 37.33 | 23.36 | 27.83 | 23.37 |
June | 254.33 | 23.77 | 210.67 | 23.81 | 78.83 | 23.80 |
July | 475.67 | 23.78 | 664.67 | 23.79 | 475.67 | 23.79 |
August | 405.00 | 23.65 | 496.00 | 23.70 | 325.83 | 23.70 |
September | 490.17 | 23.60 | 404.83 | 23.66 | 291.17 | 23.66 |
October | 690.67 | 22.98 | 97.33 | 23.03 | 78.50 | 23.05 |
November | 720.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
December | 744.00 | 21.20 | 26.83 | 21.19 | 26.83 | 21.19 |
Annual Sum or Average | 7287.33 | 22.48 | 1959.00 | 22.74 | 1326.00 | 22.84 |
Minimum of Months | 254.33 | 21.20 | 0.00 | 21.19 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 23.78 | 664.67 | 23.81 | 475.67 | 23.80 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 21.24 | 252.33 | 21.14 | 252.33 | 21.08 |
February | 670.33 | 21.36 | 197.50 | 21.27 | 197.50 | 21.22 |
March | 743.33 | 21.47 | 133.67 | 21.39 | 133.67 | 21.34 |
April | 678.83 | 21.58 | 31.83 | 21.57 | 26.33 | 21.56 |
May | 633.67 | 21.52 | 31.50 | 21.60 | 1.00 | 21.61 |
June | 534.50 | 21.41 | 74.33 | 21.63 | 1.00 | 21.63 |
July | 540.17 | 21.32 | 137.33 | 21.68 | 21.00 | 21.69 |
August | 550.83 | 21.34 | 125.00 | 21.64 | 20.67 | 21.65 |
September | 537.50 | 21.33 | 139.83 | 21.66 | 33.00 | 21.67 |
October | 652.83 | 21.46 | 66.67 | 21.55 | 33.50 | 21.55 |
November | 708.00 | 21.41 | 150.17 | 21.32 | 149.17 | 21.25 |
December | 744.00 | 21.21 | 372.50 | 21.11 | 372.50 | 21.06 |
Annual Sum or Average | 7737.33 | 21.39 | 1712.67 | 21.43 | 1241.67 | 21.38 |
Minimum of Months | 534.50 | 21.21 | 31.50 | 21.11 | 1.00 | 21.06 |
Maximum of Months | 744.00 | 21.58 | 372.50 | 21.68 | 372.50 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.87 | 486.67 | 20.80 | 486.67 | 20.77 |
February | 671.17 | 21.15 | 352.67 | 21.03 | 352.67 | 20.98 |
March | 732.00 | 21.49 | 186.50 | 21.38 | 185.50 | 21.30 |
April | 673.17 | 21.81 | 38.83 | 21.84 | 26.67 | 21.81 |
May | 609.83 | 21.76 | 47.67 | 21.89 | 5.17 | 21.90 |
June | 487.33 | 21.54 | 114.33 | 21.90 | 10.50 | 21.93 |
July | 520.17 | 21.62 | 201.50 | 22.10 | 75.00 | 22.24 |
August | 539.50 | 21.64 | 162.33 | 22.02 | 65.17 | 22.12 |
September | 555.17 | 21.76 | 162.00 | 22.06 | 86.17 | 22.14 |
October | 656.67 | 21.78 | 95.83 | 21.92 | 60.83 | 21.93 |
November | 717.00 | 21.27 | 259.50 | 21.16 | 258.50 | 21.09 |
December | 744.00 | 20.80 | 639.00 | 20.76 | 639.00 | 20.75 |
Annual Sum or Average | 7650.00 | 21.43 | 2746.83 | 21.45 | 2251.83 | 21.38 |
Minimum of Months | 487.33 | 20.80 | 38.83 | 20.76 | 5.17 | 20.75 |
Maximum of Months | 744.00 | 21.81 | 639.00 | 22.10 | 639.00 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 711.83 | 21.49 | 54.00 | 21.46 | 54.00 | 21.42 |
February | 648.67 | 21.56 | 30.00 | 21.54 | 30.00 | 21.52 |
March | 743.00 | 21.61 | 29.67 | 21.59 | 29.67 | 21.57 |
April | 701.67 | 21.64 | 4.67 | 21.64 | 4.67 | 21.63 |
May | 703.83 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 631.50 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
July | 604.67 | 21.39 | 22.83 | 21.43 | 18.00 | 21.46 |
August | 605.33 | 21.39 | 36.83 | 21.48 | 10.00 | 21.48 |
September | 563.83 | 21.35 | 100.17 | 21.62 | 15.67 | 21.64 |
October | 618.33 | 21.43 | 59.50 | 21.57 | 8.50 | 21.58 |
November | 644.83 | 21.43 | 31.83 | 21.42 | 27.33 | 21.40 |
December | 728.50 | 21.54 | 91.50 | 21.48 | 91.50 | 21.43 |
Annual Sum or Average | 7906.00 | 21.51 | 461.00 | 21.54 | 289.33 | 21.52 |
Minimum of Months | 563.83 | 21.35 | 0.00 | 21.42 | 0.00 | 21.40 |
Maximum of Months | 743.00 | 21.64 | 100.17 | 21.64 | 91.50 | 21.64 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 387.17 | 23.47 | 27.17 | 23.50 | 0.00 | 23.50 |
February | 303.83 | 23.56 | 38.00 | 23.61 | 0.00 | 23.61 |
March | 206.83 | 23.52 | 20.67 | 23.56 | 0.00 | 23.56 |
April | 33.50 | 23.60 | 217.00 | 23.94 | 0.00 | 23.94 |
May | 73.33 | 23.99 | 537.33 | 23.99 | 72.83 | 23.99 |
June | 154.33 | 24.00 | 679.17 | 24.00 | 154.33 | 24.00 |
July | 579.50 | 24.00 | 744.00 | 24.00 | 579.50 | 24.00 |
August | 441.50 | 23.99 | 744.00 | 23.99 | 441.50 | 23.99 |
September | 388.83 | 24.00 | 712.83 | 23.99 | 388.83 | 23.99 |
October | 171.67 | 23.96 | 588.33 | 23.97 | 164.50 | 23.97 |
November | 225.00 | 23.52 | 98.00 | 23.66 | 0.00 | 23.66 |
December | 464.33 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 3429.83 | 23.76 | 4406.50 | 23.89 | 1801.50 | 23.91 |
Minimum of Months | 33.50 | 23.47 | 0.00 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 579.50 | 24.00 | 744.00 | 24.00 | 579.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 163.33 | 23.48 | 98.00 | 23.67 | 0.00 | 23.67 |
February | 80.67 | 23.48 | 60.33 | 23.70 | 0.00 | 23.70 |
March | 61.50 | 23.51 | 45.17 | 23.72 | 0.00 | 23.72 |
April | 6.33 | 23.60 | 306.33 | 23.98 | 0.00 | 23.98 |
May | 64.50 | 24.00 | 592.17 | 24.00 | 64.50 | 24.00 |
June | 143.00 | 24.00 | 691.00 | 24.00 | 143.00 | 24.00 |
July | 548.00 | 24.00 | 744.00 | 24.00 | 548.00 | 24.00 |
August | 419.17 | 24.00 | 744.00 | 24.00 | 419.17 | 24.00 |
September | 374.50 | 24.00 | 720.00 | 23.99 | 374.50 | 24.00 |
October | 151.17 | 23.99 | 649.83 | 23.99 | 151.00 | 23.99 |
November | 60.50 | 23.45 | 153.33 | 23.82 | 0.00 | 23.82 |
December | 212.17 | 23.46 | 22.50 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 2284.83 | 23.86 | 4826.67 | 23.95 | 1700.17 | 23.96 |
Minimum of Months | 6.33 | 23.45 | 22.50 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 548.00 | 24.00 | 744.00 | 24.00 | 548.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.33 | 23.99 | 696.00 | 23.95 | 486.83 | 23.96 |
February | 449.50 | 23.98 | 631.67 | 23.96 | 448.17 | 23.97 |
March | 499.17 | 23.99 | 714.00 | 23.96 | 498.50 | 23.97 |
April | 508.50 | 23.99 | 715.00 | 23.98 | 508.50 | 23.98 |
May | 551.50 | 23.99 | 744.00 | 23.99 | 551.50 | 23.99 |
June | 592.17 | 23.99 | 720.00 | 23.99 | 592.17 | 23.99 |
July | 740.17 | 23.99 | 744.00 | 23.99 | 740.17 | 23.99 |
August | 680.50 | 23.99 | 744.00 | 23.99 | 680.50 | 23.99 |
September | 646.67 | 23.99 | 720.00 | 23.99 | 646.67 | 23.99 |
October | 564.00 | 23.99 | 744.00 | 23.98 | 564.00 | 23.98 |
November | 489.67 | 23.99 | 688.50 | 23.96 | 489.67 | 23.97 |
December | 480.83 | 23.98 | 672.50 | 23.95 | 478.17 | 23.96 |
Annual Sum or Average | 6690.00 | 23.99 | 8533.67 | 23.98 | 6684.83 | 23.98 |
Minimum of Months | 449.50 | 23.98 | 631.67 | 23.95 | 448.17 | 23.96 |
Maximum of Months | 740.17 | 23.99 | 744.00 | 23.99 | 740.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 23.67 | 21.26 | 23.67 | 21.26 |
February | 672.00 | 21.53 | 4.50 | 21.52 | 4.50 | 21.52 |
March | 744.00 | 21.78 | 9.00 | 21.77 | 9.00 | 21.77 |
April | 687.33 | 22.76 | 0.83 | 22.76 | 0.00 | 22.76 |
May | 392.17 | 23.22 | 119.00 | 23.37 | 6.83 | 23.38 |
June | 91.67 | 23.65 | 390.17 | 23.87 | 35.50 | 23.86 |
July | 342.50 | 23.80 | 741.50 | 23.87 | 342.50 | 23.85 |
August | 212.33 | 23.64 | 610.67 | 23.79 | 190.67 | 23.76 |
September | 342.83 | 23.40 | 474.67 | 23.61 | 203.50 | 23.60 |
October | 608.17 | 22.75 | 106.50 | 22.89 | 40.33 | 22.91 |
November | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
December | 744.00 | 21.18 | 43.33 | 21.17 | 43.33 | 21.16 |
Annual Sum or Average | 6301.00 | 22.21 | 2523.83 | 22.65 | 899.83 | 22.72 |
Minimum of Months | 91.67 | 21.18 | 0.00 | 21.17 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 23.80 | 741.50 | 23.87 | 342.50 | 23.86 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.75646 | 23.72346 | 0.16199 | 5.65512 |
February | 672.00000 | 22.96834 | 21.93141 | -0.0523 | 5.24130 |
March | 744.00000 | 22.22742 | 21.21507 | -0.2407 | 6.35647 |
April | 720.00000 | 22.33532 | 25.12806 | -0.1886 | 5.92932 |
May | 744.00000 | 22.64032 | 35.93527 | -1.0911 | 30.39880 |
June | 720.00000 | 22.94864 | 44.93563 | -0.9197 | 23.24234 |
July | 744.00000 | 23.72146 | 57.33151 | -0.5490 | 11.53880 |
August | 744.00000 | 23.92215 | 52.75280 | -0.4897 | 10.09663 |
September | 720.00000 | 23.98984 | 49.09164 | -0.4743 | 9.81801 |
October | 744.00000 | 23.99385 | 39.69705 | 0.36168 | 7.85837 |
November | 720.00000 | 23.99243 | 23.64605 | 0.24486 | 6.31180 |
December | 744.00000 | 23.95174 | 21.16572 | 0.20674 | 5.94375 |
Annual Sum or Average | 8760.00000 | 23.37456 | 34.80704 | -0.2533 | 10.73722 |
Minimum of Months | 672.00000 | 22.22742 | 21.16572 | -1.0911 | 5.24130 |
Maximum of Months | 744.00000 | 23.99385 | 57.33151 | 0.36168 | 30.39880 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.95698 | 25.03121 | -0.2145 | 7.85220 |
February | 672.00000 | 22.08644 | 21.95436 | -0.1901 | 7.48806 |
March | 744.00000 | 22.11229 | 20.42064 | -0.1904 | 7.22987 |
April | 720.00000 | 22.80869 | 23.43784 | 0.02283 | 6.41284 |
May | 744.00000 | 23.31485 | 33.50077 | -0.7087 | 17.19221 |
June | 720.00000 | 23.72820 | 41.84408 | -0.4748 | 10.29393 |
July | 744.00000 | 23.75384 | 56.48998 | -0.3632 | 8.14565 |
August | 744.00000 | 23.67871 | 52.90237 | -0.4112 | 9.28413 |
September | 720.00000 | 23.63536 | 49.84682 | -0.4341 | 10.24184 |
October | 744.00000 | 23.14308 | 41.52359 | 0.25472 | 7.85649 |
November | 720.00000 | 22.41041 | 25.49526 | -0.0677 | 7.44965 |
December | 744.00000 | 21.83974 | 22.94629 | -0.2677 | 8.28688 |
Annual Sum or Average | 8760.00000 | 22.87585 | 34.71425 | -0.2544 | 8.99420 |
Minimum of Months | 672.00000 | 21.83974 | 20.42064 | -0.7087 | 6.41284 |
Maximum of Months | 744.00000 | 23.75384 | 56.48998 | 0.25472 | 17.19221 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.82431 | 25.77896 | -0.0273 | 5.33776 |
February | 672.00000 | 22.96025 | 22.80923 | -0.0108 | 5.29395 |
March | 744.00000 | 23.05864 | 21.32397 | 0.00656 | 5.34189 |
April | 720.00000 | 23.51734 | 24.37443 | 0.15158 | 5.83100 |
May | 744.00000 | 23.75100 | 34.24565 | -0.6257 | 13.67095 |
June | 720.00000 | 23.88183 | 42.77264 | -0.5019 | 10.50798 |
July | 744.00000 | 23.89671 | 57.11410 | -0.3973 | 8.39992 |
August | 744.00000 | 23.87898 | 53.56809 | -0.4311 | 9.02722 |
September | 720.00000 | 23.88955 | 50.50100 | -0.4506 | 9.46700 |
October | 744.00000 | 23.68820 | 41.88654 | 0.32043 | 7.40599 |
November | 720.00000 | 23.24469 | 26.25900 | 0.08818 | 5.59610 |
December | 744.00000 | 22.68815 | 23.86177 | -0.0751 | 5.40591 |
Annual Sum or Average | 8760.00000 | 23.44179 | 35.47129 | -0.1638 | 7.62349 |
Minimum of Months | 672.00000 | 22.68815 | 21.32397 | -0.6257 | 5.29395 |
Maximum of Months | 744.00000 | 23.89671 | 57.11410 | 0.32043 | 13.67095 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.34902 | 20.61159 | 0.66861 | 16.41973 |
February | 672.00000 | 23.37854 | 17.81698 | 0.67031 | 16.39431 |
March | 744.00000 | 23.39021 | 16.44294 | 0.67779 | 16.62342 |
April | 720.00000 | 23.46112 | 20.09286 | 0.75162 | 18.77357 |
May | 744.00000 | 23.49181 | 30.73087 | 0.19151 | 9.58461 |
June | 720.00000 | 23.50121 | 39.97229 | 0.28752 | 10.28810 |
July | 744.00000 | 23.49798 | 54.48778 | 0.37906 | 11.26094 |
August | 744.00000 | 23.48143 | 50.90697 | 0.34313 | 10.94056 |
September | 720.00000 | 23.47286 | 47.70993 | 0.30618 | 10.46885 |
October | 744.00000 | 23.44818 | 38.15598 | 0.86614 | 22.61267 |
November | 720.00000 | 23.40666 | 21.54196 | 0.71028 | 17.59697 |
December | 744.00000 | 23.33179 | 18.64862 | 0.64488 | 15.77084 |
Annual Sum or Average | 8760.00000 | 23.43440 | 31.52853 | 0.54066 | 14.71907 |
Minimum of Months | 672.00000 | 23.33179 | 16.44294 | 0.19151 | 9.58461 |
Maximum of Months | 744.00000 | 23.50121 | 54.48778 | 0.86614 | 22.61267 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.28844 | 29.59682 | 0.16569 | 6.52145 |
February | 672.00000 | 23.41262 | 26.65970 | 0.18633 | 6.40745 |
March | 744.00000 | 23.40239 | 25.30234 | 0.17270 | 6.30487 |
April | 720.00000 | 23.64081 | 28.21614 | 0.28174 | 7.18673 |
May | 744.00000 | 23.73838 | 38.16028 | -0.4882 | 10.61518 |
June | 720.00000 | 23.84122 | 46.45544 | -0.3497 | 7.86555 |
July | 744.00000 | 23.86436 | 60.68221 | -0.2390 | 6.37934 |
August | 744.00000 | 23.85920 | 57.03178 | -0.2623 | 6.74531 |
September | 720.00000 | 23.91970 | 53.76004 | -0.2524 | 6.80871 |
October | 744.00000 | 23.79815 | 45.14327 | 0.47748 | 10.31680 |
November | 720.00000 | 23.51846 | 29.92873 | 0.25919 | 7.50675 |
December | 744.00000 | 23.18338 | 27.70964 | 0.11810 | 6.27440 |
Annual Sum or Average | 8760.00000 | 23.62280 | 39.14986 | 0.00454 | 7.42005 |
Minimum of Months | 672.00000 | 23.18338 | 25.30234 | -0.4882 | 6.27440 |
Maximum of Months | 744.00000 | 23.91970 | 60.68221 | 0.47748 | 10.61518 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.35473 | 28.31449 | 0.13198 | 5.65957 |
February | 672.00000 | 23.44004 | 25.43938 | 0.13786 | 5.64617 |
March | 744.00000 | 23.43270 | 24.02854 | 0.12978 | 5.64922 |
April | 720.00000 | 23.64668 | 27.00975 | 0.22172 | 6.30230 |
May | 744.00000 | 23.74575 | 36.84216 | -0.5747 | 12.33430 |
June | 720.00000 | 23.83998 | 45.33557 | -0.4590 | 9.67778 |
July | 744.00000 | 23.86249 | 59.60326 | -0.3506 | 7.68781 |
August | 744.00000 | 23.86704 | 56.00733 | -0.3765 | 8.09329 |
September | 720.00000 | 23.91147 | 52.87498 | -0.3850 | 8.26850 |
October | 744.00000 | 23.83347 | 44.08362 | 0.39973 | 8.54741 |
November | 720.00000 | 23.62397 | 28.73528 | 0.21685 | 6.31304 |
December | 744.00000 | 23.27110 | 26.46729 | 0.09525 | 5.48903 |
Annual Sum or Average | 8760.00000 | 23.65307 | 37.99101 | -0.0690 | 7.48554 |
Minimum of Months | 672.00000 | 23.27110 | 24.02854 | -0.5747 | 5.48903 |
Maximum of Months | 744.00000 | 23.91147 | 59.60326 | 0.39973 | 12.33430 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33425 | 34.53003 | -0.4152 | 9.31517 |
February | 672.00000 | 21.43747 | 30.46525 | -0.3887 | 8.93209 |
March | 744.00000 | 21.52545 | 28.44158 | -0.3458 | 8.32827 |
April | 720.00000 | 21.68717 | 31.42512 | -0.2171 | 7.09315 |
May | 744.00000 | 21.77183 | 39.93782 | -1.1753 | 35.61678 |
June | 720.00000 | 21.83203 | 46.25229 | -1.0624 | 30.48362 |
July | 744.00000 | 21.79141 | 54.57922 | -1.0334 | 29.17138 |
August | 744.00000 | 21.79268 | 53.34454 | -1.0547 | 30.15820 |
September | 720.00000 | 21.78791 | 52.08814 | -1.0738 | 31.18076 |
October | 744.00000 | 21.70531 | 47.97515 | -0.1054 | 6.26118 |
November | 720.00000 | 21.50595 | 34.44646 | -0.3196 | 8.21570 |
December | 744.00000 | 21.29486 | 31.82892 | -0.4578 | 10.05287 |
Annual Sum or Average | 8760.00000 | 21.62282 | 40.51820 | -0.6391 | 17.95977 |
Minimum of Months | 672.00000 | 21.29486 | 28.44158 | -1.1753 | 6.26118 |
Maximum of Months | 744.00000 | 21.83203 | 54.57922 | -0.1054 | 35.61678 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99243 | 35.14203 | -0.5377 | 11.40970 |
February | 672.00000 | 21.24884 | 30.72767 | -0.4764 | 10.35761 |
March | 744.00000 | 21.61262 | 28.32312 | -0.3632 | 8.72744 |
April | 720.00000 | 21.97907 | 31.02647 | -0.1770 | 6.96485 |
May | 744.00000 | 22.08174 | 39.52459 | -1.0942 | 32.10813 |
June | 720.00000 | 22.11559 | 46.22319 | -0.9790 | 27.23569 |
July | 744.00000 | 22.07948 | 55.06436 | -0.9471 | 25.99246 |
August | 744.00000 | 22.09160 | 53.62811 | -0.9795 | 27.17496 |
September | 720.00000 | 22.15905 | 52.36844 | -1.0006 | 28.06457 |
October | 744.00000 | 22.08031 | 47.85115 | -0.0668 | 6.29504 |
November | 720.00000 | 21.39203 | 34.55514 | -0.3978 | 9.15325 |
December | 744.00000 | 20.91576 | 32.47591 | -0.5889 | 12.56559 |
Annual Sum or Average | 8760.00000 | 21.73099 | 40.65167 | -0.6353 | 17.21928 |
Minimum of Months | 672.00000 | 20.91576 | 28.32312 | -1.0942 | 6.29504 |
Maximum of Months | 744.00000 | 22.15905 | 55.06436 | -0.0668 | 32.10813 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09091 | 33.53632 | -0.4968 | 10.28442 |
February | 672.00000 | 21.22917 | 29.19980 | -0.4739 | 9.87299 |
March | 744.00000 | 21.43863 | 26.82452 | -0.4186 | 8.87179 |
April | 720.00000 | 21.76381 | 29.65942 | -0.2891 | 7.32962 |
May | 744.00000 | 21.91940 | 38.93381 | -1.2693 | 39.53859 |
June | 720.00000 | 21.96708 | 46.46373 | -1.1744 | 35.06979 |
July | 744.00000 | 21.96503 | 56.16140 | -1.1184 | 32.62792 |
August | 744.00000 | 21.95463 | 54.41829 | -1.1506 | 33.96003 |
September | 720.00000 | 21.97881 | 52.80221 | -1.1772 | 35.14491 |
October | 744.00000 | 21.81138 | 46.72031 | -0.1824 | 6.21940 |
November | 720.00000 | 21.26070 | 33.15540 | -0.4375 | 9.20191 |
December | 744.00000 | 21.04892 | 30.98334 | -0.5296 | 10.96860 |
Annual Sum or Average | 8760.00000 | 21.62089 | 39.98612 | -0.7281 | 19.98746 |
Minimum of Months | 672.00000 | 21.04892 | 26.82452 | -1.2693 | 6.21940 |
Maximum of Months | 744.00000 | 21.97881 | 56.16140 | -0.1824 | 39.53859 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37601 | 34.48724 | -0.4090 | 9.16449 |
February | 672.00000 | 21.52240 | 30.38385 | -0.3617 | 8.59793 |
March | 744.00000 | 21.61358 | 28.40412 | -0.3219 | 8.13186 |
April | 720.00000 | 21.74475 | 31.36701 | -0.1948 | 6.95989 |
May | 744.00000 | 21.78348 | 39.95209 | -1.1629 | 34.99535 |
June | 720.00000 | 21.82873 | 46.41179 | -1.0524 | 30.04006 |
July | 744.00000 | 21.79664 | 54.55300 | -1.0232 | 28.77523 |
August | 744.00000 | 21.78657 | 53.24528 | -1.0495 | 29.92238 |
September | 720.00000 | 21.78638 | 51.86945 | -1.0715 | 31.04740 |
October | 744.00000 | 21.70894 | 48.19605 | -0.1098 | 6.29803 |
November | 720.00000 | 21.54415 | 34.42082 | -0.3139 | 8.15028 |
December | 744.00000 | 21.32408 | 31.80368 | -0.4499 | 9.84369 |
Annual Sum or Average | 8760.00000 | 21.65155 | 40.50056 | -0.6285 | 17.71982 |
Minimum of Months | 672.00000 | 21.32408 | 28.40412 | -1.1629 | 6.29803 |
Maximum of Months | 744.00000 | 21.82873 | 54.55300 | -0.1098 | 34.99535 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97278 | 35.08409 | -0.5441 | 11.41912 |
February | 672.00000 | 21.27636 | 30.65588 | -0.4603 | 9.93918 |
March | 744.00000 | 21.63088 | 28.34049 | -0.3538 | 8.37533 |
April | 720.00000 | 22.06857 | 30.89416 | -0.1488 | 6.88012 |
May | 744.00000 | 22.25724 | 39.32851 | -1.0349 | 30.84615 |
June | 720.00000 | 22.26568 | 45.87708 | -0.9259 | 26.56206 |
July | 744.00000 | 22.21128 | 54.56266 | -0.9012 | 25.51060 |
August | 744.00000 | 22.21813 | 53.03981 | -0.9370 | 26.68045 |
September | 720.00000 | 22.31820 | 51.71252 | -0.9523 | 27.43636 |
October | 744.00000 | 22.01475 | 48.07779 | -0.0861 | 6.21921 |
November | 720.00000 | 21.34554 | 34.63714 | -0.4097 | 9.17594 |
December | 744.00000 | 20.90143 | 32.40881 | -0.5893 | 12.55020 |
Annual Sum or Average | 8760.00000 | 21.79200 | 40.46054 | -0.6132 | 16.84812 |
Minimum of Months | 672.00000 | 20.90143 | 28.34049 | -1.0349 | 6.21921 |
Maximum of Months | 744.00000 | 22.31820 | 54.56266 | -0.0861 | 30.84615 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.24180 | 35.15969 | -0.4673 | 10.41156 |
February | 672.00000 | 21.36703 | 30.93469 | -0.4326 | 9.85615 |
March | 744.00000 | 21.47058 | 28.75408 | -0.3813 | 9.05332 |
April | 720.00000 | 21.67158 | 31.54957 | -0.2290 | 7.46934 |
May | 744.00000 | 21.77299 | 40.12632 | -1.1756 | 35.94597 |
June | 720.00000 | 21.84979 | 46.56315 | -1.0442 | 30.08884 |
July | 744.00000 | 21.80350 | 55.03181 | -1.0166 | 28.78291 |
August | 744.00000 | 21.79858 | 54.02581 | -1.0436 | 30.01834 |
September | 720.00000 | 21.78811 | 52.95229 | -1.0736 | 31.56309 |
October | 744.00000 | 21.67714 | 48.94185 | -0.1224 | 6.54968 |
November | 720.00000 | 21.43707 | 34.97790 | -0.3649 | 9.08292 |
December | 744.00000 | 21.20530 | 32.35343 | -0.5114 | 11.26569 |
Annual Sum or Average | 8760.00000 | 21.59107 | 41.02367 | -0.6568 | 18.39712 |
Minimum of Months | 672.00000 | 21.20530 | 28.75408 | -1.1756 | 6.54968 |
Maximum of Months | 744.00000 | 21.84979 | 55.03181 | -0.1224 | 35.94597 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86668 | 35.86603 | -0.5994 | 12.95736 |
February | 672.00000 | 21.15056 | 31.26288 | -0.5283 | 11.61582 |
March | 744.00000 | 21.54995 | 28.67873 | -0.4006 | 9.57361 |
April | 720.00000 | 21.95378 | 31.17002 | -0.1892 | 7.34950 |
May | 744.00000 | 22.05178 | 39.69486 | -1.1012 | 32.67659 |
June | 720.00000 | 22.10810 | 46.46245 | -0.9666 | 27.01464 |
July | 744.00000 | 22.06978 | 55.38444 | -0.9355 | 25.73264 |
August | 744.00000 | 22.06618 | 54.20421 | -0.9763 | 27.26536 |
September | 720.00000 | 22.10789 | 53.22770 | -1.0140 | 28.82817 |
October | 744.00000 | 22.03180 | 48.79942 | -0.0879 | 6.58396 |
November | 720.00000 | 21.28398 | 35.20894 | -0.4552 | 10.33190 |
December | 744.00000 | 20.79623 | 33.08256 | -0.6511 | 14.25172 |
Annual Sum or Average | 8760.00000 | 21.67187 | 41.16288 | -0.6599 | 17.89383 |
Minimum of Months | 672.00000 | 20.79623 | 28.67873 | -1.1012 | 6.58396 |
Maximum of Months | 744.00000 | 22.10810 | 55.38444 | -0.0879 | 32.67659 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57331 | 35.77879 | -0.3018 | 8.22331 |
February | 672.00000 | 21.62116 | 31.60758 | -0.3011 | 8.17146 |
March | 744.00000 | 21.61635 | 29.40015 | -0.3170 | 8.23845 |
April | 720.00000 | 21.68189 | 32.62385 | -0.2414 | 7.42086 |
May | 744.00000 | 21.72637 | 41.38562 | -1.2560 | 39.32532 |
June | 720.00000 | 21.77875 | 47.55494 | -1.1520 | 34.31935 |
July | 744.00000 | 21.75613 | 55.50572 | -1.1090 | 32.38900 |
August | 744.00000 | 21.75461 | 54.29561 | -1.1162 | 32.84196 |
September | 720.00000 | 21.77297 | 53.15807 | -1.1054 | 32.79420 |
October | 744.00000 | 21.74317 | 48.29243 | -0.0922 | 6.50357 |
November | 720.00000 | 21.62536 | 35.46303 | -0.2513 | 7.80131 |
December | 744.00000 | 21.57644 | 33.30331 | -0.3257 | 8.56096 |
Annual Sum or Average | 8760.00000 | 21.68575 | 41.60499 | -0.6329 | 18.95187 |
Minimum of Months | 672.00000 | 21.57331 | 29.40015 | -1.2560 | 6.50357 |
Maximum of Months | 744.00000 | 21.77875 | 55.50572 | -0.0922 | 39.32532 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.71031 | 28.81954 | 0.22856 | 6.37020 |
February | 672.00000 | 23.79017 | 25.83056 | 0.24435 | 6.46016 |
March | 744.00000 | 23.84774 | 24.13813 | 0.26805 | 6.64731 |
April | 720.00000 | 23.95637 | 26.91837 | 0.36481 | 7.95091 |
May | 744.00000 | 23.98730 | 36.68527 | -0.3648 | 8.04659 |
June | 720.00000 | 23.99520 | 45.26425 | -0.2571 | 6.53140 |
July | 744.00000 | 23.99502 | 59.35260 | -0.1621 | 5.56625 |
August | 744.00000 | 23.99320 | 55.96068 | -0.2031 | 5.92077 |
September | 720.00000 | 23.98899 | 53.13580 | -0.2524 | 6.50452 |
October | 744.00000 | 23.94817 | 44.43756 | 0.47824 | 10.00542 |
November | 720.00000 | 23.81561 | 29.36609 | 0.28284 | 6.88371 |
December | 744.00000 | 23.67064 | 27.11644 | 0.19637 | 6.08505 |
Annual Sum or Average | 8760.00000 | 23.89187 | 38.17975 | 0.06757 | 6.91751 |
Minimum of Months | 672.00000 | 23.67064 | 24.13813 | -0.3648 | 5.56625 |
Maximum of Months | 744.00000 | 23.99520 | 59.35260 | 0.47824 | 10.00542 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.85216 | 27.84846 | 0.30219 | 7.07306 |
February | 672.00000 | 23.90073 | 24.93340 | 0.30928 | 7.12583 |
March | 744.00000 | 23.93679 | 23.32609 | 0.32664 | 7.30824 |
April | 720.00000 | 23.98360 | 26.32466 | 0.40349 | 8.55121 |
May | 744.00000 | 23.99397 | 36.24704 | -0.3224 | 7.42301 |
June | 720.00000 | 23.99628 | 44.90286 | -0.2203 | 6.16946 |
July | 744.00000 | 23.99600 | 58.98318 | -0.1255 | 5.34939 |
August | 744.00000 | 23.99524 | 55.57253 | -0.1654 | 5.63292 |
September | 720.00000 | 23.99419 | 52.70103 | -0.2125 | 6.10713 |
October | 744.00000 | 23.97981 | 43.82983 | 0.51587 | 10.76598 |
November | 720.00000 | 23.91624 | 28.51058 | 0.34304 | 7.59259 |
December | 744.00000 | 23.82833 | 26.13738 | 0.27451 | 6.72948 |
Annual Sum or Average | 8760.00000 | 23.94789 | 37.53860 | 0.11796 | 7.15310 |
Minimum of Months | 672.00000 | 23.82833 | 23.32609 | -0.3224 | 5.34939 |
Maximum of Months | 744.00000 | 23.99628 | 58.98318 | 0.51587 | 10.76598 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86908 | 26.60566 | 0.94544 | 25.82207 |
February | 672.00000 | 23.89033 | 23.86618 | 0.95608 | 26.19189 |
March | 744.00000 | 23.91866 | 22.54174 | 0.97788 | 27.05428 |
April | 720.00000 | 23.97041 | 25.95830 | 1.07350 | 31.07847 |
May | 744.00000 | 23.98839 | 35.99429 | 0.64670 | 17.81400 |
June | 720.00000 | 23.99238 | 44.59604 | 0.75917 | 20.59707 |
July | 744.00000 | 23.99303 | 58.29581 | 0.84768 | 23.25195 |
August | 744.00000 | 23.99276 | 54.90108 | 0.80622 | 21.97990 |
September | 720.00000 | 23.99037 | 51.92942 | 0.76022 | 20.70620 |
October | 744.00000 | 23.97158 | 42.97996 | 1.17684 | 35.51235 |
November | 720.00000 | 23.90187 | 27.47126 | 0.99045 | 27.62590 |
December | 744.00000 | 23.84635 | 24.80412 | 0.91757 | 24.79342 |
Annual Sum or Average | 8760.00000 | 23.94399 | 36.75810 | 0.90449 | 25.19635 |
Minimum of Months | 672.00000 | 23.84635 | 22.54174 | 0.64670 | 17.81400 |
Maximum of Months | 744.00000 | 23.99303 | 58.29581 | 1.17684 | 35.51235 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26521 | 24.29161 | -0.4317 | 9.01169 |
February | 672.00000 | 21.47066 | 20.93525 | -0.4014 | 8.53509 |
March | 744.00000 | 21.69999 | 19.23379 | -0.3553 | 7.80882 |
April | 720.00000 | 22.58692 | 22.17165 | -0.1214 | 5.64362 |
May | 744.00000 | 23.34979 | 31.81644 | -0.8412 | 20.53128 |
June | 720.00000 | 23.84756 | 40.09040 | -0.6061 | 12.86298 |
July | 744.00000 | 23.87754 | 54.81462 | -0.4935 | 10.13713 |
August | 744.00000 | 23.75583 | 51.28727 | -0.5637 | 11.80869 |
September | 720.00000 | 23.53102 | 48.82917 | -0.6609 | 14.55247 |
October | 744.00000 | 22.84689 | 40.65566 | 0.06363 | 5.46441 |
November | 720.00000 | 21.87889 | 24.57442 | -0.2788 | 6.97250 |
December | 744.00000 | 21.18787 | 22.08434 | -0.4667 | 9.62180 |
Annual Sum or Average | 8760.00000 | 22.61366 | 33.49548 | -0.4301 | 10.26254 |
Minimum of Months | 672.00000 | 21.18787 | 19.23379 | -0.8412 | 5.46441 |
Maximum of Months | 744.00000 | 23.87754 | 54.81462 | 0.06363 | 20.53128 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35553 | 27.59281 | -0.4138 | 8.69619 |
February | 672.00000 | 21.62786 | 24.21767 | -0.3660 | 7.92516 |
March | 744.00000 | 21.92496 | 22.46487 | -0.3037 | 7.08068 |
April | 720.00000 | 22.74447 | 25.55398 | -0.0842 | 5.40387 |
May | 744.00000 | 23.39600 | 35.42664 | -0.8330 | 20.14440 |
June | 720.00000 | 23.82795 | 43.77773 | -0.6214 | 13.26123 |
July | 744.00000 | 23.79323 | 58.39743 | -0.5347 | 11.03814 |
August | 744.00000 | 23.72137 | 54.92804 | -0.5851 | 12.33179 |
September | 720.00000 | 23.65714 | 52.01554 | -0.6270 | 13.50826 |
October | 744.00000 | 23.03008 | 43.81281 | 0.10644 | 5.53308 |
November | 720.00000 | 22.11790 | 27.75576 | -0.2240 | 6.42534 |
December | 744.00000 | 21.19690 | 25.51984 | -0.4662 | 9.58388 |
Annual Sum or Average | 8760.00000 | 22.70401 | 36.88658 | -0.4134 | 10.10005 |
Minimum of Months | 672.00000 | 21.19690 | 22.46487 | -0.8330 | 5.40387 |
Maximum of Months | 744.00000 | 23.82795 | 58.39743 | 0.10644 | 20.14440 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.27237 | 25.46800 | -0.4226 | 8.90153 |
February | 672.00000 | 21.52787 | 22.10723 | -0.3738 | 8.18256 |
March | 744.00000 | 21.78352 | 20.33491 | -0.3168 | 7.41423 |
April | 720.00000 | 22.80655 | 23.08629 | -0.0401 | 5.67828 |
May | 744.00000 | 23.52837 | 32.78248 | -0.7318 | 17.15938 |
June | 720.00000 | 23.89359 | 41.12781 | -0.5257 | 11.01792 |
July | 744.00000 | 23.89438 | 55.51871 | -0.4273 | 8.88759 |
August | 744.00000 | 23.80960 | 52.15455 | -0.4866 | 10.17644 |
September | 720.00000 | 23.65643 | 49.49563 | -0.5664 | 12.33832 |
October | 744.00000 | 22.93805 | 41.62032 | 0.11416 | 5.92642 |
November | 720.00000 | 21.82096 | 25.85155 | -0.2762 | 7.16200 |
December | 744.00000 | 21.17805 | 23.31784 | -0.4651 | 9.61250 |
Annual Sum or Average | 8760.00000 | 22.68121 | 34.50121 | -0.3768 | 9.38473 |
Minimum of Months | 672.00000 | 21.17805 | 20.33491 | -0.7318 | 5.67828 |
Maximum of Months | 744.00000 | 23.89438 | 55.51871 | 0.11416 | 17.15938 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45250 | 23.72411 | -0.3921 | 8.37197 |
February | 672.00000 | 21.65927 | 20.40392 | -0.3620 | 7.94819 |
March | 744.00000 | 21.91171 | 18.69878 | -0.3108 | 7.22777 |
April | 720.00000 | 22.80539 | 21.58367 | -0.0750 | 5.48092 |
May | 744.00000 | 23.54314 | 31.10956 | -0.7798 | 18.40852 |
June | 720.00000 | 23.91952 | 39.58034 | -0.5787 | 12.16412 |
July | 744.00000 | 23.93912 | 54.25731 | -0.4691 | 9.63322 |
August | 744.00000 | 23.86129 | 50.62607 | -0.5269 | 10.92459 |
September | 720.00000 | 23.70966 | 47.99956 | -0.6029 | 12.97067 |
October | 744.00000 | 23.06811 | 39.82689 | 0.11109 | 5.63622 |
November | 720.00000 | 22.09337 | 23.96025 | -0.2334 | 6.53206 |
December | 744.00000 | 21.34315 | 21.59249 | -0.4331 | 9.03199 |
Annual Sum or Average | 8760.00000 | 22.78079 | 32.87648 | -0.3881 | 9.54314 |
Minimum of Months | 672.00000 | 21.34315 | 18.69878 | -0.7798 | 5.48092 |
Maximum of Months | 744.00000 | 23.93912 | 54.25731 | 0.11109 | 18.40852 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.123852E+11 | 65342.60 | 03-JAN-16:02 | 524.22 | 0.374977E+11 | 0.00 | 0.498829E+11 | 2.18 | 3.44 | 03-JAN-16:02 | 0.00 | 0.00 |
February | 0.244394E+11 | 83691.35 | 22-FEB-16:01 | 541.51 | 0.708965E+11 | 0.00 | 0.953359E+11 | 2.45 | 3.66 | 22-FEB-16:01 | 0.00 | 0.00 |
March | 0.405335E+11 | 87098.09 | 14-MAR-15:02 | 667.71 | 0.116327E+12 | 0.00 | 0.156860E+12 | 2.70 | 3.61 | 06-MAR-16:02 | 0.00 | 0.00 |
April | 0.106538E+12 | 116245.95 | 28-APR-18:04 | 714.17 | 0.315532E+12 | 0.00 | 0.422070E+12 | 2.94 | 3.90 | 28-APR-21:51 | 0.00 | 0.00 |
May | 0.170668E+12 | 134382.59 | 19-MAY-18:04 | 744.00 | 0.509348E+12 | 0.00 | 0.680016E+12 | 2.96 | 3.71 | 17-MAY-21:51 | 0.00 | 0.00 |
June | 0.223300E+12 | 159253.68 | 14-JUN-18:05 | 720.00 | 0.657597E+12 | 0.00 | 0.880897E+12 | 2.95 | 3.72 | 19-JUN-18:05 | 0.00 | 0.00 |
July | 0.259516E+12 | 158976.16 | 26-JUL-18:04 | 744.00 | 0.836776E+12 | 0.00 | 0.109629E+13 | 3.23 | 4.42 | 18-JUL-21:51 | 0.00 | 0.00 |
August | 0.224795E+12 | 152198.34 | 04-AUG-18:06 | 744.00 | 0.698682E+12 | 0.00 | 0.923477E+12 | 3.09 | 4.15 | 01-AUG-21:51 | 0.00 | 0.00 |
September | 0.183053E+12 | 132143.40 | 01-SEP-18:03 | 720.00 | 0.585095E+12 | 0.00 | 0.768148E+12 | 3.15 | 4.27 | 03-SEP-21:51 | 0.00 | 0.00 |
October | 0.104843E+12 | 132965.05 | 04-OCT-18:03 | 744.00 | 0.321122E+12 | 0.00 | 0.425964E+12 | 3.03 | 4.22 | 03-OCT-21:52 | 0.00 | 0.00 |
November | 0.332710E+11 | 83909.70 | 09-NOV-16:02 | 588.43 | 0.977062E+11 | 0.00 | 0.130977E+12 | 2.48 | 3.60 | 08-NOV-16:02 | 0.00 | 0.00 |
December | 0.952320E+10 | 51984.06 | 10-DEC-16:02 | 510.65 | 0.291233E+11 | 0.00 | 0.386465E+11 | 2.12 | 3.12 | 06-DEC-11:33 | 0.00 | 0.00 |
Annual Sum or Average | 0.139286E+13 | 7962.70 | 0.427570E+13 | 0.00 | 0.566857E+13 | 2.77 | 0.00 | 0.00 | ||||
Minimum of Months | 0.952320E+10 | 51984.06 | 510.65 | 0.291233E+11 | 0.00 | 0.386465E+11 | 2.12 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.259516E+12 | 159253.68 | 744.00 | 0.836776E+12 | 0.00 | 0.109629E+13 | 3.23 | 4.42 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.128991E+12 | 0.00 | 686.08 | 159844.92 | 14-JAN-16:02 | 0.00 | 35.88 | 57.78 | 0.48 | 0.00 | 0.12 | 0.40 | 14-JAN-16:02 |
February | 0.810699E+11 | 0.00 | 521.75 | 150227.99 | 01-FEB-19:02 | 0.00 | 34.95 | 53.97 | 0.33 | 0.00 | 0.08 | 0.38 | 01-FEB-19:02 |
March | 0.681158E+11 | 0.00 | 440.49 | 141271.67 | 24-MAR-08:04 | 0.00 | 32.61 | 48.06 | 0.24 | 0.00 | 0.06 | 0.35 | 24-MAR-08:04 |
April | 0.203267E+11 | 0.00 | 141.52 | 131357.37 | 11-APR-08:05 | 0.00 | 27.91 | 33.89 | 0.07 | 0.00 | 0.02 | 0.33 | 11-APR-08:05 |
May | 0.930899E+09 | 0.00 | 17.78 | 52189.17 | 02-MAY-06:00 | 0.00 | 27.54 | 28.31 | 0.00 | 0.00 | 0.00 | 0.13 | 02-MAY-06:00 |
June | 6066178.04 | 0.00 | 0.62 | 11060.13 | 29-JUN-08:05 | 0.00 | 28.91 | 28.93 | 0.00 | 0.00 | 0.00 | 0.03 | 29-JUN-08:05 |
July | 2441766.73 | 0.00 | 0.57 | 5226.13 | 19-JUL-08:07 | 0.00 | 32.83 | 32.85 | 0.00 | 0.00 | 0.00 | 0.01 | 19-JUL-08:07 |
August | 6478223.22 | 0.00 | 0.92 | 10355.23 | 14-AUG-08:06 | 0.00 | 35.81 | 35.84 | 0.00 | 0.00 | 0.00 | 0.03 | 14-AUG-08:06 |
September | 0.130345E+10 | 0.00 | 18.58 | 67087.26 | 30-SEP-06:00 | 0.00 | 36.65 | 37.50 | 0.00 | 0.00 | 0.00 | 0.17 | 30-SEP-06:00 |
October | 0.127166E+11 | 0.00 | 153.67 | 120641.91 | 25-OCT-06:05 | 0.00 | 28.54 | 34.95 | 0.04 | 0.00 | 0.01 | 0.30 | 25-OCT-06:05 |
November | 0.789021E+11 | 0.00 | 502.49 | 173770.29 | 27-NOV-19:02 | 0.00 | 35.50 | 52.62 | 0.30 | 0.00 | 0.08 | 0.43 | 27-NOV-19:02 |
December | 0.112755E+12 | 0.00 | 702.00 | 179898.32 | 28-DEC-19:02 | 0.00 | 37.22 | 58.42 | 0.44 | 0.00 | 0.11 | 0.45 | 28-DEC-19:02 |
Annual Sum or Average | 0.505127E+12 | 0.00 | 3186.48 | 0.00 | 32.85 | 41.87 | 0.16 | 0.00 | 0.04 | ||||
Minimum of Months | 2441766.73 | 0.00 | 0.57 | 5226.13 | 0.00 | 27.54 | 28.31 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.128991E+12 | 0.00 | 702.00 | 179898.32 | 0.00 | 37.22 | 58.42 | 0.48 | 0.00 | 0.12 | 0.45 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.634906E+10 | 0.00 | 144.33 | 0.634906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89892.32 | 03-JAN-17:00 | 89892.32 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.327740E+11 | 0.00 | 220.43 | 0.327740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124604.07 | 21-FEB-16:13 | 124604.07 | 21-FEB-16:13 | 0.00 | 0.00 | 0.00 |
March | 0.669580E+11 | 0.00 | 329.79 | 0.669580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160086.38 | 14-MAR-18:10 | 160086.38 | 14-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.210536E+12 | 0.00 | 550.67 | 0.210536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232451.98 | 19-APR-21:00 | 232451.98 | 19-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.349646E+12 | 0.00 | 711.00 | 0.348107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256574.42 | 19-MAY-19:10 | 256574.42 | 19-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.452127E+12 | 0.00 | 720.00 | 0.447200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 302481.53 | 19-JUN-18:02 | 277928.43 | 15-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.604956E+12 | 0.00 | 744.00 | 0.468638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478794.26 | 21-JUL-21:00 | 275438.54 | 25-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.491102E+12 | 0.00 | 744.00 | 0.438975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 453910.00 | 01-AUG-20:50 | 283277.97 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.400819E+12 | 0.00 | 692.17 | 0.345211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 336972.62 | 09-SEP-20:00 | 261180.52 | 19-SEP-18:17 | 0.00 | 0.00 | 0.00 |
October | 0.197980E+12 | 0.00 | 533.50 | 0.189585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 383831.25 | 03-OCT-19:55 | 243111.60 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.407680E+11 | 0.00 | 270.79 | 0.407680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148848.45 | 03-NOV-15:55 | 148848.45 | 03-NOV-15:55 | 0.00 | 0.00 | 0.00 |
December | 0.370344E+10 | 0.00 | 164.64 | 0.370344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48738.53 | 23-DEC-15:00 | 48738.53 | 23-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285772E+13 | 0.00 | 5825.32 | 0.259880E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.370344E+10 | 0.00 | 144.33 | 0.370344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48738.53 | 48738.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.604956E+12 | 0.00 | 744.00 | 0.468638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478794.26 | 283277.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424271E+09 | 0.00 | 40.67 | 0.424271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11015.35 | 03-JAN-17:00 | 11015.35 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.213329E+10 | 0.00 | 104.33 | 0.213329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14187.69 | 20-FEB-16:02 | 14187.69 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.440325E+10 | 0.00 | 187.50 | 0.440325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14760.49 | 22-MAR-15:02 | 14760.49 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.144427E+11 | 0.00 | 416.17 | 0.144427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17660.73 | 21-APR-15:02 | 17660.73 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.238606E+11 | 0.00 | 559.50 | 0.233116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21816.91 | 24-MAY-13:00 | 18542.20 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.297804E+11 | 0.00 | 570.00 | 0.285424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24534.76 | 27-JUN-24:00 | 19641.84 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.421110E+11 | 0.00 | 589.00 | 0.300770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39037.79 | 21-JUL-08:03 | 19655.90 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.344471E+11 | 0.00 | 589.00 | 0.282819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33560.00 | 01-AUG-21:51 | 19087.05 | 06-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.289207E+11 | 0.00 | 543.50 | 0.220951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31964.14 | 22-SEP-08:03 | 18184.23 | 19-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.137054E+11 | 0.00 | 400.67 | 0.123357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27787.53 | 03-OCT-20:20 | 17904.33 | 01-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.268538E+10 | 0.00 | 138.17 | 0.268538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14427.26 | 09-NOV-16:02 | 14427.26 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.217498E+09 | 0.00 | 33.00 | 0.217498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 10-DEC-14:00 | 5697.71 | 10-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197132E+12 | 0.00 | 4171.50 | 0.168950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.217498E+09 | 0.00 | 33.00 | 0.217498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 5697.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.421110E+11 | 0.00 | 589.00 | 0.300770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39037.79 | 19655.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.791304E+09 | 0.00 | 175.17 | 0.744796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9735.11 | 22-JAN-16:02 | 9735.11 | 22-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.125782E+10 | 0.00 | 231.61 | 0.124653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9732.84 | 18-FEB-16:02 | 9732.84 | 18-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.238410E+10 | 0.00 | 375.65 | 0.236308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9734.54 | 12-MAR-15:02 | 9734.54 | 12-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.557417E+10 | 0.00 | 601.60 | 0.525322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9735.41 | 21-APR-18:02 | 9735.41 | 21-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.865679E+10 | 0.00 | 698.66 | 0.769104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10775.12 | 28-MAY-08:62 | 9735.75 | 15-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.109694E+11 | 0.00 | 694.75 | 0.939593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10657.11 | 28-JUN-08:62 | 9743.59 | 29-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.116809E+11 | 0.00 | 717.91 | 0.875618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12478.13 | 19-JUL-08:62 | 9807.11 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.106826E+11 | 0.00 | 710.42 | 0.810155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11235.39 | 14-AUG-08:62 | 9779.36 | 08-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.972614E+10 | 0.00 | 687.00 | 0.730791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11611.83 | 09-SEP-08:62 | 9761.92 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.629859E+10 | 0.00 | 655.15 | 0.478345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11157.04 | 15-OCT-08:62 | 9820.24 | 17-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.230023E+10 | 0.00 | 362.38 | 0.213438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9735.54 | 09-NOV-16:02 | 9735.54 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.468804E+09 | 0.00 | 128.45 | 0.457746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9733.57 | 13-DEC-16:02 | 9733.57 | 13-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707908E+11 | 0.00 | 6038.76 | 0.582358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.468804E+09 | 0.00 | 128.45 | 0.457746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9732.84 | 9732.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116809E+11 | 0.00 | 717.91 | 0.939593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12478.13 | 9820.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.134507E+09 | 0.00 | 34.41 | 0.129199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9670.13 | 12-JAN-16:02 | 9670.13 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.227648E+09 | 0.00 | 72.78 | 0.225200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9667.72 | 18-FEB-16:02 | 9667.72 | 18-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.782981E+09 | 0.00 | 194.21 | 0.767508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9669.69 | 12-MAR-15:02 | 9669.69 | 12-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.411494E+10 | 0.00 | 476.77 | 0.385410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10678.21 | 06-APR-18:11 | 10678.21 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.783043E+10 | 0.00 | 591.19 | 0.701417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11335.91 | 28-MAY-08:51 | 10439.74 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.105158E+11 | 0.00 | 620.04 | 0.911159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11486.19 | 04-JUN-08:51 | 10917.71 | 19-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.110327E+11 | 0.00 | 636.25 | 0.840950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13353.11 | 22-JUL-08:31 | 10376.65 | 11-JUL-07:52 | 0.00 | 0.00 | 0.00 |
August | 0.948157E+10 | 0.00 | 609.05 | 0.726182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12842.21 | 03-AUG-08:61 | 10329.98 | 11-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.744938E+10 | 0.00 | 545.51 | 0.556205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12409.61 | 03-SEP-08:51 | 10477.11 | 09-SEP-17:52 | 0.00 | 0.00 | 0.00 |
October | 0.333266E+10 | 0.00 | 453.49 | 0.228746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11709.27 | 03-OCT-21:52 | 9825.02 | 05-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.527854E+09 | 0.00 | 157.19 | 0.446107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9669.20 | 13-NOV-16:02 | 9669.20 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 55150681.86 | 0.00 | 14.22 | 53822204.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9661.89 | 16-DEC-16:02 | 9661.89 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554856E+11 | 0.00 | 4405.10 | 0.451225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 55150681.86 | 0.00 | 14.22 | 53822204.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9661.89 | 9661.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110327E+11 | 0.00 | 636.25 | 0.911159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13353.11 | 10917.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176245E+11 | 0.00 | 360.78 | 0.176245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39587.94 | 12-JAN-14:25 | 39587.94 | 12-JAN-14:25 | 0.00 | 0.00 | 0.00 |
February | 0.184525E+11 | 0.00 | 381.14 | 0.182800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37655.20 | 07-FEB-13:40 | 37655.20 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.170120E+11 | 0.00 | 432.57 | 0.168659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29067.78 | 16-MAR-12:50 | 29067.78 | 16-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.262409E+11 | 0.00 | 598.28 | 0.249767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27807.73 | 04-APR-13:30 | 27807.73 | 04-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.334245E+11 | 0.00 | 715.56 | 0.277741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26874.52 | 19-MAY-20:20 | 26367.79 | 31-MAY-20:50 | 0.00 | 0.00 | 0.00 |
June | 0.425824E+11 | 0.00 | 719.17 | 0.316128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30303.13 | 15-JUN-20:20 | 30303.13 | 15-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.468014E+11 | 0.00 | 743.14 | 0.264147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31428.65 | 26-JUL-17:20 | 26286.30 | 02-JUL-20:40 | 0.00 | 0.00 | 0.00 |
August | 0.472417E+11 | 0.00 | 740.00 | 0.290099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33055.46 | 29-AUG-13:00 | 31274.53 | 27-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.515260E+11 | 0.00 | 716.55 | 0.354094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41767.30 | 19-SEP-13:30 | 36254.01 | 29-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.445738E+11 | 0.00 | 673.02 | 0.356723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47214.46 | 22-OCT-13:15 | 46742.76 | 22-OCT-13:15 | 0.00 | 0.00 | 0.00 |
November | 0.298884E+11 | 0.00 | 452.75 | 0.286825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43632.52 | 09-NOV-13:50 | 43632.52 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.141262E+11 | 0.00 | 335.68 | 0.141262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32463.13 | 16-DEC-13:40 | 32463.13 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389494E+12 | 0.00 | 6868.63 | 0.306449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.141262E+11 | 0.00 | 335.68 | 0.141262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26874.52 | 26286.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.515260E+11 | 0.00 | 743.14 | 0.356723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47214.46 | 46742.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.235701E+10 | 0.00 | 141.75 | 0.205514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59922.81 | 01-JAN-09:02 | 59922.81 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.490155E+10 | 0.00 | 206.31 | 0.451307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62544.06 | 21-FEB-21:32 | 62544.06 | 21-FEB-21:32 | 0.00 | 0.00 | 0.00 |
March | 0.106002E+11 | 0.00 | 323.33 | 0.101947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63723.64 | 15-MAR-21:52 | 63723.64 | 15-MAR-21:52 | 0.00 | 0.00 | 0.00 |
April | 0.290798E+11 | 0.00 | 447.41 | 0.275831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65178.99 | 05-APR-21:52 | 65178.99 | 05-APR-21:52 | 0.00 | 0.00 | 0.00 |
May | 0.494486E+11 | 0.00 | 530.23 | 0.444557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70941.14 | 23-MAY-21:51 | 66475.34 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.655481E+11 | 0.00 | 583.68 | 0.566210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71033.92 | 19-JUN-18:51 | 68513.16 | 21-JUN-07:42 | 0.00 | 0.00 | 0.00 |
July | 0.709912E+11 | 0.00 | 596.58 | 0.538061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83528.23 | 21-JUL-08:51 | 67781.12 | 10-JUL-07:21 | 0.00 | 0.00 | 0.00 |
August | 0.601546E+11 | 0.00 | 554.10 | 0.455133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78289.67 | 16-AUG-21:52 | 67166.24 | 11-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.455275E+11 | 0.00 | 481.26 | 0.334635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78602.08 | 23-SEP-21:51 | 64859.80 | 03-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.268092E+11 | 0.00 | 407.18 | 0.192301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76645.72 | 03-OCT-21:52 | 64722.27 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.651981E+10 | 0.00 | 255.08 | 0.548230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62166.16 | 08-NOV-22:52 | 62166.16 | 08-NOV-22:52 | 0.00 | 0.00 | 0.00 |
December | 0.159089E+10 | 0.00 | 101.98 | 0.151895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60262.14 | 09-DEC-09:02 | 60262.14 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373528E+12 | 0.00 | 4628.89 | 0.304437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.159089E+10 | 0.00 | 101.98 | 0.151895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59922.81 | 59922.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.709912E+11 | 0.00 | 596.58 | 0.566210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83528.23 | 68513.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.693705E+09 | 0.00 | 159.73 | 0.641638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8575.51 | 31-JAN-09:02 | 8575.51 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.141671E+10 | 0.00 | 271.06 | 0.139195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8577.27 | 19-FEB-09:02 | 8577.27 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.242760E+10 | 0.00 | 418.28 | 0.240560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8577.57 | 25-MAR-08:62 | 8577.57 | 25-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.587336E+10 | 0.00 | 646.29 | 0.556771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8577.48 | 21-APR-18:02 | 8577.48 | 21-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.888281E+10 | 0.00 | 726.16 | 0.799691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8963.04 | 28-MAY-08:62 | 8616.58 | 23-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.113332E+11 | 0.00 | 708.59 | 0.996102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9266.79 | 29-JUN-08:62 | 8637.01 | 19-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.120168E+11 | 0.00 | 729.76 | 0.934943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11013.65 | 19-JUL-08:62 | 8638.57 | 11-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.109910E+11 | 0.00 | 724.92 | 0.871880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9900.65 | 14-AUG-08:62 | 8643.58 | 22-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.984990E+10 | 0.00 | 703.55 | 0.766791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10250.61 | 23-SEP-18:02 | 8630.34 | 05-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.590295E+10 | 0.00 | 652.42 | 0.454444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10102.32 | 15-OCT-08:62 | 8576.52 | 05-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.219010E+10 | 0.00 | 378.39 | 0.204482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8706.52 | 03-NOV-08:62 | 8577.54 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.496275E+09 | 0.00 | 123.98 | 0.470319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8575.61 | 10-DEC-09:02 | 8575.61 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720744E+11 | 0.00 | 6243.12 | 0.607606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.496275E+09 | 0.00 | 123.98 | 0.470319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8575.51 | 8575.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120168E+11 | 0.00 | 729.76 | 0.996102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11013.65 | 8643.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 78029302.90 | 0.00 | 31.32 | 58496264.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8145.06 | 31-JAN-09:02 | 8145.06 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.388124E+09 | 0.00 | 94.17 | 0.369513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8512.70 | 19-FEB-09:02 | 8512.70 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.102075E+10 | 0.00 | 231.76 | 0.100481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8512.28 | 25-MAR-08:62 | 8512.28 | 25-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.438011E+10 | 0.00 | 519.53 | 0.412810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9876.02 | 27-APR-08:51 | 9876.02 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.776751E+10 | 0.00 | 614.81 | 0.704084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10809.76 | 28-MAY-08:51 | 10616.43 | 20-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.106247E+11 | 0.00 | 633.10 | 0.942395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11359.07 | 20-JUN-08:62 | 10895.80 | 14-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.111372E+11 | 0.00 | 646.35 | 0.876527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12321.09 | 21-JUL-08:51 | 10088.92 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.955543E+10 | 0.00 | 622.82 | 0.759373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11913.00 | 03-AUG-07:42 | 10169.91 | 04-AUG-07:42 | 0.00 | 0.00 | 0.00 |
September | 0.729327E+10 | 0.00 | 562.43 | 0.546943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11540.73 | 03-SEP-08:51 | 9751.29 | 19-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.314424E+10 | 0.00 | 456.29 | 0.219721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10508.90 | 05-OCT-08:51 | 9570.90 | 03-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.553846E+09 | 0.00 | 132.02 | 0.491668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8996.05 | 09-NOV-09:51 | 8996.05 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 55398425.73 | 0.00 | 19.52 | 48419723.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8267.98 | 16-DEC-09:02 | 8267.98 | 16-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559986E+11 | 0.00 | 4564.12 | 0.465914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 55398425.73 | 0.00 | 19.52 | 48419723.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8145.06 | 8145.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.111372E+11 | 0.00 | 646.35 | 0.942395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12321.09 | 10895.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.166267E+09 | 0.00 | 117.58 | 0.159263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.83 | 22-JAN-16:02 | 2581.83 | 22-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.280492E+09 | 0.00 | 173.35 | 0.279032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.21 | 07-FEB-16:01 | 2581.21 | 07-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.546133E+09 | 0.00 | 298.58 | 0.543407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.70 | 12-MAR-15:02 | 2581.70 | 12-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.135936E+10 | 0.00 | 559.82 | 0.127971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.80 | 21-APR-18:02 | 2581.80 | 21-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.215981E+10 | 0.00 | 690.02 | 0.190607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.01 | 28-MAY-08:62 | 2581.98 | 11-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.283381E+10 | 0.00 | 694.93 | 0.241179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2911.61 | 28-JUN-08:62 | 2581.82 | 02-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.301997E+10 | 0.00 | 717.51 | 0.224590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3467.74 | 19-JUL-08:62 | 2601.72 | 17-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.272014E+10 | 0.00 | 710.51 | 0.204571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3092.94 | 14-AUG-08:62 | 2602.55 | 28-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.239690E+10 | 0.00 | 679.56 | 0.178359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3214.14 | 09-SEP-08:62 | 2602.00 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.144357E+10 | 0.00 | 580.59 | 0.109693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3077.02 | 09-OCT-08:62 | 2581.16 | 27-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.479512E+09 | 0.00 | 282.90 | 0.448907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.83 | 09-NOV-16:02 | 2581.83 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.100317E+09 | 0.00 | 84.38 | 98205950.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.43 | 13-DEC-16:02 | 2581.43 | 13-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175063E+11 | 0.00 | 5589.73 | 0.142985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100317E+09 | 0.00 | 84.38 | 98205950.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.21 | 2581.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.301997E+10 | 0.00 | 717.51 | 0.241179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3467.74 | 2602.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 23466800.61 | 0.00 | 22.58 | 22490346.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.93 | 12-JAN-16:02 | 2561.93 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 39333324.40 | 0.00 | 44.44 | 39087067.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.29 | 18-FEB-16:02 | 2561.29 | 18-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.153496E+09 | 0.00 | 133.21 | 0.151810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.83 | 12-MAR-15:02 | 2561.83 | 12-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.101126E+10 | 0.00 | 445.18 | 0.947049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2839.11 | 06-APR-18:11 | 2839.11 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.198717E+10 | 0.00 | 589.58 | 0.176890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3008.83 | 28-MAY-08:51 | 2767.78 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.275535E+10 | 0.00 | 621.91 | 0.237750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3065.49 | 04-JUN-08:51 | 2911.39 | 19-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.289137E+10 | 0.00 | 637.77 | 0.219922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.48 | 22-JUL-08:31 | 2718.95 | 11-JUL-07:52 | 0.00 | 0.00 | 0.00 |
August | 0.245221E+10 | 0.00 | 610.70 | 0.186623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3451.18 | 03-AUG-08:61 | 2694.61 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.185977E+10 | 0.00 | 541.42 | 0.137458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.10 | 03-SEP-08:51 | 2770.59 | 09-SEP-17:52 | 0.00 | 0.00 | 0.00 |
October | 0.719436E+09 | 0.00 | 377.44 | 0.501623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3154.41 | 03-OCT-21:52 | 2581.94 | 03-OCT-18:21 | 0.00 | 0.00 | 0.00 |
November | 84286383.11 | 0.00 | 85.33 | 70676483.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.68 | 13-NOV-16:02 | 2561.68 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 9213279.51 | 0.00 | 9.62 | 8912921.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2526.71 | 16-DEC-16:02 | 2526.71 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139864E+11 | 0.00 | 4119.19 | 0.113281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9213279.51 | 0.00 | 9.62 | 8912921.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2526.71 | 2526.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.289137E+10 | 0.00 | 637.77 | 0.237750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.48 | 2911.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.448859E+10 | 0.00 | 376.02 | 0.424406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11706.08 | 03-JAN-16:02 | 11706.08 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.451339E+10 | 0.00 | 398.20 | 0.444036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11706.21 | 18-FEB-16:02 | 11706.21 | 18-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.447557E+10 | 0.00 | 465.47 | 0.442150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11705.92 | 05-MAR-16:02 | 11705.92 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.695170E+10 | 0.00 | 603.72 | 0.652701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11918.28 | 18-APR-18:02 | 11706.19 | 16-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.935264E+10 | 0.00 | 689.02 | 0.795177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12933.22 | 28-MAY-08:62 | 11745.83 | 24-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.123133E+11 | 0.00 | 688.40 | 0.102390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12724.04 | 28-JUN-08:62 | 11773.00 | 21-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.138751E+11 | 0.00 | 711.33 | 0.100793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15696.14 | 19-JUL-08:62 | 11776.58 | 03-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.134586E+11 | 0.00 | 706.07 | 0.100984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13799.30 | 02-AUG-08:62 | 11767.01 | 05-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.135676E+11 | 0.00 | 687.76 | 0.104907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14568.96 | 23-SEP-18:02 | 11784.94 | 09-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.109395E+11 | 0.00 | 663.18 | 0.903120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13462.56 | 04-OCT-08:62 | 11786.45 | 02-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.679141E+10 | 0.00 | 466.59 | 0.650022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11706.37 | 09-NOV-19:02 | 11706.37 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.405188E+10 | 0.00 | 354.10 | 0.394078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11705.76 | 10-DEC-16:02 | 11705.76 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104779E+12 | 0.00 | 6809.84 | 0.879642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.405188E+10 | 0.00 | 354.10 | 0.394078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11705.76 | 11705.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.138751E+11 | 0.00 | 711.33 | 0.104907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15696.14 | 11786.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 946.86 | 496.33 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 910.16 | 438.97 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 736.55 | 381.87 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 583.62 | 227.12 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 465.13 | 129.21 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 487.30 | 61.32 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 495.07 | 46.02 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 582.24 | 69.98 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 829.45 | 153.16 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 972.35 | 250.52 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1035.18 | 420.41 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 953.04 | 534.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 748.60 | 266.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 465.13 | 46.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1035.18 | 534.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2619.86 | 1525.09 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2512.90 | 1356.40 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 2023.17 | 1185.34 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1607.03 | 703.86 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1287.84 | 392.24 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1365.35 | 178.91 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1385.98 | 134.99 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1627.58 | 208.36 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2317.37 | 446.79 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2707.61 | 757.06 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2871.12 | 1281.31 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2631.85 | 1628.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2076.68 | 813.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1287.84 | 134.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2871.12 | 1628.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3476.99 | 2032.47 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3339.84 | 1801.00 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2695.16 | 1575.73 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2150.67 | 930.63 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1728.82 | 516.01 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1838.90 | 232.77 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1864.93 | 174.41 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2181.70 | 269.57 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3087.99 | 578.47 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3591.90 | 991.80 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3802.17 | 1701.97 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3491.43 | 2176.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2766.76 | 1078.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1728.82 | 174.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3802.17 | 2176.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.36 | 102.42 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 181.17 | 90.02 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 145.25 | 78.33 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 118.38 | 41.76 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.97 | 19.69 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.94 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.46 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 128.12 | 7.77 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.53 | 22.85 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.31 | 44.87 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.26 | 84.14 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 190.40 | 110.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.32 | 50.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.97 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.26 | 110.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 113.14 | 212.17 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 138.27 | 186.08 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 211.74 | 151.99 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 293.80 | 77.12 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 361.70 | 36.43 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 409.30 | 12.79 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 369.89 | 7.00 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 339.81 | 14.39 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 318.51 | 43.26 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 233.27 | 88.09 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 153.13 | 174.55 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 101.13 | 233.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.15 | 102.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 101.13 | 7.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 409.30 | 233.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.12 | 114.70 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.46 | 100.67 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.13 | 83.76 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.27 | 42.17 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 82.20 | 19.09 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 116.63 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.17 | 3.99 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 85.54 | 8.06 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.29 | 24.31 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.84 | 49.44 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.21 | 95.04 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.94 | 126.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.93 | 56.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.94 | 3.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 116.63 | 126.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.57 | 205.84 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 143.98 | 181.93 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 214.78 | 151.52 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.02 | 79.19 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.63 | 38.17 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 406.03 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 366.83 | 7.66 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 338.40 | 15.55 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 319.34 | 45.38 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 235.59 | 90.39 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.56 | 170.84 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.52 | 226.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 255.84 | 101.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.52 | 7.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 406.03 | 226.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 136.29 | 112.00 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 130.12 | 101.40 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 101.40 | 89.22 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 80.21 | 56.59 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 63.14 | 34.05 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 68.78 | 17.71 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 69.45 | 15.08 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 83.39 | 21.01 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 123.39 | 37.86 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 143.02 | 59.95 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 151.36 | 94.93 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 137.24 | 117.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 107.14 | 62.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 63.14 | 15.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 151.36 | 117.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.07 | 94.32 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 9.54 | 81.78 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 20.01 | 66.44 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 42.18 | 31.94 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 71.06 | 13.77 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 100.10 | 4.49 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 93.63 | 2.36 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 74.28 | 5.34 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 53.58 | 17.31 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 28.18 | 37.31 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 7.28 | 75.88 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.10 | 104.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 42.26 | 44.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.10 | 2.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 100.10 | 104.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 93.89 | 201.34 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 151.42 | 172.93 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 207.17 | 139.76 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 309.96 | 69.56 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 368.67 | 33.01 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 427.37 | 11.88 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 389.26 | 6.73 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 354.30 | 13.48 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 317.91 | 39.39 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 200.71 | 82.27 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 132.72 | 162.42 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 89.73 | 220.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 253.96 | 95.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 89.73 | 6.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 427.37 | 220.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.64 | 101.87 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.54 | 89.81 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 143.64 | 77.86 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.06 | 41.65 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.23 | 19.47 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.30 | 6.69 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.86 | 3.72 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.76 | 7.61 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.09 | 22.50 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.02 | 44.06 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 206.48 | 83.49 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.66 | 110.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.50 | 50.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.23 | 3.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 206.48 | 110.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.83 | 114.26 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 10.70 | 100.87 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 22.13 | 83.32 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 46.51 | 41.85 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 80.05 | 18.76 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 114.79 | 6.72 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 107.58 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 84.11 | 7.90 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 59.79 | 24.19 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.34 | 47.95 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 7.73 | 94.03 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.64 | 126.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 47.80 | 55.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.64 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 114.79 | 126.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 98.89 | 192.84 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 156.82 | 167.64 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 210.78 | 138.47 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 309.44 | 71.30 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 363.42 | 34.53 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 421.01 | 12.42 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 383.71 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 350.11 | 14.41 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 315.48 | 41.17 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 203.25 | 83.57 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 137.99 | 157.17 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 93.85 | 211.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 254.06 | 94.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 93.85 | 7.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 421.01 | 211.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 4.67 | 145.63 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 14.50 | 127.42 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 31.08 | 104.38 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 62.78 | 55.05 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 102.63 | 28.34 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 140.78 | 12.85 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 130.56 | 9.02 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 102.17 | 14.84 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 74.95 | 36.54 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 39.30 | 65.70 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 9.64 | 123.27 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 3.24 | 160.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 59.93 | 73.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 3.24 | 9.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 140.78 | 160.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.72 | 53.68 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 5.34 | 46.97 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 11.46 | 38.48 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 23.14 | 20.29 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 37.83 | 10.45 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 51.90 | 4.74 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 48.13 | 3.32 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 37.66 | 5.47 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 27.63 | 13.47 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 14.49 | 24.22 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 3.56 | 45.44 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 1.20 | 58.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 22.09 | 27.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 1.20 | 3.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 51.90 | 58.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 89.42 | 46.64 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 86.00 | 41.26 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 69.28 | 36.13 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 55.86 | 20.73 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 45.58 | 11.24 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 48.86 | 4.96 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 49.32 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 57.00 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 79.16 | 13.30 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 91.91 | 22.77 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 97.64 | 39.53 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 90.37 | 50.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 71.60 | 24.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 45.58 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 97.64 | 50.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 242.70 | 126.60 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 233.42 | 111.99 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 188.04 | 98.07 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 151.63 | 56.25 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 123.71 | 30.50 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 132.61 | 13.47 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 133.87 | 9.50 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 154.72 | 15.44 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 214.85 | 36.11 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 249.47 | 61.80 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 265.02 | 107.29 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 245.28 | 136.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 194.33 | 66.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 123.71 | 9.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 265.02 | 136.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.26 | 101.34 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.99 | 88.93 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 143.92 | 77.34 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.18 | 40.83 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.46 | 18.86 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.78 | 6.41 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.02 | 3.55 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.43 | 7.28 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 171.18 | 22.05 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 195.90 | 43.93 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 206.23 | 82.83 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.73 | 109.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.40 | 50.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.46 | 3.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 206.23 | 109.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 112.15 | 209.53 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 136.96 | 183.43 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 209.54 | 149.69 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.12 | 75.28 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.02 | 34.85 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 407.14 | 11.98 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 367.77 | 6.43 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 337.78 | 13.51 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 316.17 | 41.71 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 231.57 | 85.96 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 152.02 | 171.35 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 100.62 | 230.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 252.33 | 100.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 100.62 | 6.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 407.14 | 230.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.42 | 113.04 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.73 | 99.08 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.25 | 82.68 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 47.95 | 41.39 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 81.98 | 18.37 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 116.29 | 6.46 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 108.70 | 3.69 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 85.36 | 7.59 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.01 | 23.42 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.86 | 48.46 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.62 | 93.16 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.20 | 124.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.89 | 54.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.20 | 3.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 116.29 | 124.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.45 | 202.91 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 143.42 | 179.05 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 212.98 | 149.35 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.43 | 77.58 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 357.07 | 36.62 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 403.91 | 12.60 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 364.72 | 7.05 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 336.50 | 14.61 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 317.36 | 43.67 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 234.27 | 88.41 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.40 | 167.16 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.85 | 223.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.43 | 99.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.85 | 7.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 403.91 | 223.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 267.00 | 155.65 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 257.65 | 135.76 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 207.63 | 115.28 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 173.42 | 58.82 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 151.56 | 26.13 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 171.90 | 8.37 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 172.68 | 4.44 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 192.24 | 9.84 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 253.19 | 31.26 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 285.57 | 65.18 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 297.01 | 126.09 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 269.68 | 168.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 224.70 | 75.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 151.56 | 4.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 297.01 | 168.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 11.04 | 940.11 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 53.53 | 817.32 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 129.38 | 667.33 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 298.95 | 351.92 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 524.70 | 178.66 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 748.95 | 81.44 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 690.02 | 61.39 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 535.40 | 96.08 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 391.52 | 216.67 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 188.98 | 404.87 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 34.88 | 769.85 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 7.86 | 1023.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 302.57 | 465.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 7.86 | 61.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 748.95 | 1023.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 8.18 | 969.73 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 47.54 | 840.92 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 119.75 | 685.43 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 289.71 | 362.22 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 515.54 | 184.74 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 739.63 | 85.02 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 680.79 | 64.95 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 526.66 | 100.60 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 384.72 | 223.64 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 181.70 | 416.27 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 29.72 | 792.01 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 5.95 | 1054.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 295.45 | 480.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 5.95 | 64.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 739.63 | 1054.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.62 | 123.76 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.46 | 108.50 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.85 | 90.39 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 56.74 | 49.23 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 93.06 | 27.35 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 127.99 | 13.87 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 120.32 | 11.01 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 97.28 | 15.49 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 74.66 | 29.82 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 39.25 | 53.96 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.78 | 100.97 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.65 | 133.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 55.52 | 62.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.65 | 11.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 127.99 | 133.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 199.88 | 422.60 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 325.25 | 367.90 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 441.87 | 306.67 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 659.05 | 172.83 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 774.17 | 101.35 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 887.71 | 51.88 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 810.91 | 41.67 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 746.99 | 57.97 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 687.86 | 107.13 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 438.14 | 192.40 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 287.69 | 342.85 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 192.04 | 454.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 538.36 | 217.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 192.04 | 41.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 887.71 | 454.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 193.56 | 108.81 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 186.95 | 96.65 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 151.19 | 84.99 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 126.53 | 49.98 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 108.55 | 28.70 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 120.85 | 14.10 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 122.41 | 11.21 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 138.65 | 15.77 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 185.60 | 29.67 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 207.09 | 51.51 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 214.76 | 89.30 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 196.08 | 115.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 162.49 | 57.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 108.55 | 11.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 214.76 | 115.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 3.67 | 147.97 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 12.82 | 128.78 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 28.89 | 104.87 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 58.93 | 56.38 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 97.81 | 29.80 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 135.87 | 13.93 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 125.07 | 10.35 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 97.29 | 16.26 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 71.29 | 37.84 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 36.48 | 66.50 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 8.43 | 122.70 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.60 | 162.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 56.82 | 74.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.60 | 10.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 135.87 | 162.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 3.28 | 132.39 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 11.47 | 115.22 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 25.85 | 93.83 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 52.72 | 50.45 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 87.51 | 26.66 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 121.56 | 12.46 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 111.90 | 9.26 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 87.05 | 14.55 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 63.78 | 33.86 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 32.64 | 59.50 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 7.54 | 109.78 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 2.33 | 145.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 50.84 | 66.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 2.33 | 9.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 121.56 | 145.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 703.72 | 376.78 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 676.17 | 332.80 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 542.34 | 290.38 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 432.56 | 170.10 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 349.84 | 94.57 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 376.99 | 42.95 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 378.55 | 32.21 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 440.45 | 50.00 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 619.69 | 110.46 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 722.48 | 184.58 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 772.31 | 314.07 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 711.98 | 404.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 559.75 | 199.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 349.84 | 32.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 772.31 | 404.94 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.253607E+10 | 0.132938E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.220187E+10 | 0.106196E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.197279E+10 | 0.102279E+10 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.151275E+10 | 0.588704E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.124581E+10 | 0.346086E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.126307E+10 | 0.158950E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.132598E+10 | 0.123250E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.155948E+10 | 0.187444E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.214993E+10 | 0.396990E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.260433E+10 | 0.670997E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.268319E+10 | 0.108970E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.255262E+10 | 0.143034E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.236079E+11 | 0.840660E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.124581E+10 | 0.123250E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.268319E+10 | 0.143034E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.701703E+10 | 0.408481E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.607920E+10 | 0.328141E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.541887E+10 | 0.317482E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.416541E+10 | 0.182441E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.344935E+10 | 0.105057E+10 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.353900E+10 | 0.463723E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.371222E+10 | 0.361569E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.435932E+10 | 0.558075E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.600663E+10 | 0.115809E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.725206E+10 | 0.202770E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.744193E+10 | 0.332117E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.704915E+10 | 0.436227E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.654902E+11 | 0.256686E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.344935E+10 | 0.361569E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.744193E+10 | 0.436227E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.931277E+10 | 0.544377E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.807973E+10 | 0.435698E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.721872E+10 | 0.422043E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.557454E+10 | 0.241219E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.463047E+10 | 0.138207E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.476643E+10 | 0.603338E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.499502E+10 | 0.467132E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.584346E+10 | 0.722025E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.800407E+10 | 0.149938E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.962054E+10 | 0.265643E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.985523E+10 | 0.441152E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.935145E+10 | 0.582823E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.872524E+11 | 0.340035E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.463047E+10 | 0.467132E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.985523E+10 | 0.582823E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.504492E+09 | 0.274332E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.438291E+09 | 0.217774E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.389049E+09 | 0.209794E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.306844E+09 | 0.108237E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.267755E+09 | 52733418.32 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.290151E+09 | 17835174.64 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.303878E+09 | 10356102.10 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.343164E+09 | 20801756.32 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.447207E+09 | 59235008.87 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.528478E+09 | 0.120169E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.537226E+09 | 0.218092E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.509979E+09 | 0.296696E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.486651E+10 | 0.160606E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.267755E+09 | 10356102.10 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.537226E+09 | 0.296696E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.303045E+09 | 0.568266E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.334507E+09 | 0.450167E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.567122E+09 | 0.407103E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.761523E+09 | 0.199896E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.968770E+09 | 97580731.75 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106091E+10 | 33149012.60 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.990721E+09 | 18761720.81 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.910159E+09 | 38548280.44 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.825582E+09 | 0.112118E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.624778E+09 | 0.235941E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.396914E+09 | 0.452440E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.270871E+09 | 0.625181E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.801490E+10 | 0.323915E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.270871E+09 | 18761720.81 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106091E+10 | 0.625181E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11038698.04 | 0.307219E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 27724791.36 | 0.243533E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 61962779.79 | 0.224345E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.125108E+09 | 0.109304E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.220170E+09 | 51131326.58 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.302307E+09 | 17825677.60 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.292397E+09 | 10675626.56 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.229123E+09 | 21580996.95 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.158872E+09 | 63005871.66 |
October | 71778804.06 | 0.00 | 71778804.06 | 85277387.79 | 0.132421E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 21272856.37 | 0.246343E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7865226.88 | 0.338975E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.154312E+10 | 0.176636E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7865226.88 | 10675626.56 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.302307E+09 | 0.338975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.320254E+09 | 0.551315E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.348322E+09 | 0.440125E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.575270E+09 | 0.405834E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.762109E+09 | 0.205263E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.963220E+09 | 0.102244E+09 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105244E+10 | 34879347.60 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.982528E+09 | 20519004.44 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.906358E+09 | 41659558.67 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.827738E+09 | 0.117612E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.631009E+09 | 0.242103E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.410989E+09 | 0.442806E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.287968E+09 | 0.606958E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.806821E+10 | 0.321132E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.287968E+09 | 20519004.44 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105244E+10 | 0.606958E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.365045E+09 | 0.299975E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.314790E+09 | 0.245316E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.271578E+09 | 0.238978E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.207900E+09 | 0.146682E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.169105E+09 | 91192048.80 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.178280E+09 | 45904045.26 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.186005E+09 | 40381565.88 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.223363E+09 | 56263948.56 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.319836E+09 | 98122718.94 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.383052E+09 | 0.160558E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.392327E+09 | 0.246052E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.367583E+09 | 0.315250E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.337886E+10 | 0.198467E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.169105E+09 | 40381565.88 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.392327E+09 | 0.315250E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 8225849.72 | 0.252630E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 23070243.06 | 0.197831E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 53594234.36 | 0.177952E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.109334E+09 | 82783238.49 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.190337E+09 | 36870863.08 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.259470E+09 | 11645251.87 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.250789E+09 | 6319057.77 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.198950E+09 | 14301740.86 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.138881E+09 | 44856466.31 |
October | 57430655.00 | 0.00 | 57430655.00 | 75479189.75 | 99943959.41 |
November | 44867884.08 | 0.00 | 44867884.08 | 18874413.26 | 0.196691E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 5612461.95 | 0.280311E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.133262E+10 | 0.140214E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 5612461.95 | 6319057.77 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.259470E+09 | 0.280311E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.251482E+09 | 0.539257E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.366322E+09 | 0.418348E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.554882E+09 | 0.374344E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.803410E+09 | 0.180300E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.987447E+09 | 88402315.40 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110774E+10 | 30796036.65 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.104260E+10 | 18029936.13 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.948956E+09 | 36103972.06 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.824028E+09 | 0.102096E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.537577E+09 | 0.220346E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.344021E+09 | 0.420996E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.240333E+09 | 0.591863E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.800880E+10 | 0.302088E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.240333E+09 | 18029936.13 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110774E+10 | 0.591863E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.502579E+09 | 0.272836E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.434355E+09 | 0.217258E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.384724E+09 | 0.208537E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.303413E+09 | 0.107966E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.265776E+09 | 52143367.89 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.288498E+09 | 17330069.19 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302289E+09 | 9960880.63 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.342201E+09 | 20384791.18 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.446056E+09 | 58319742.75 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.527694E+09 | 0.118017E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.535207E+09 | 0.216410E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.507982E+09 | 0.295692E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.484078E+10 | 0.159485E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.265776E+09 | 9960880.63 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.535207E+09 | 0.295692E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 10263597.50 | 0.306023E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 25876816.75 | 0.244020E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 59283074.66 | 0.223152E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.120564E+09 | 0.108486E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.214400E+09 | 50233497.90 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.297538E+09 | 17417894.97 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.288146E+09 | 10360330.91 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.225275E+09 | 21160987.18 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.154988E+09 | 62694819.71 |
October | 71778804.06 | 0.00 | 71778804.06 | 83948084.37 | 0.128427E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 20032230.53 | 0.243724E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7058423.26 | 0.338739E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.150737E+10 | 0.175444E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7058423.26 | 10360330.91 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.297538E+09 | 0.338739E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.264877E+09 | 0.516490E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.379390E+09 | 0.405561E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.564548E+09 | 0.370882E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.802073E+09 | 0.184805E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.973380E+09 | 92490101.73 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.109125E+10 | 32197343.31 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.102773E+10 | 19603657.17 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.937737E+09 | 38594089.49 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.817725E+09 | 0.106715E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.544380E+09 | 0.223826E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.357681E+09 | 0.407387E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.251374E+09 | 0.566458E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.801215E+10 | 0.296501E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.251374E+09 | 19603657.17 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.109125E+10 | 0.566458E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 12514757.87 | 0.390049E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 35070231.33 | 0.308259E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 83243127.04 | 0.279565E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.162727E+09 | 0.142695E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.274871E+09 | 75905093.90 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.364900E+09 | 33310587.79 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.349687E+09 | 24156751.25 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.273646E+09 | 39748872.35 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.194261E+09 | 94714487.90 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.105274E+09 | 0.175967E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 24996292.76 | 0.319507E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 8685175.78 | 0.428586E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.188988E+10 | 0.231246E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 8685175.78 | 24156751.25 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.364900E+09 | 0.428586E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 4613457.95 | 0.143788E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 12928339.41 | 0.113637E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 30686863.45 | 0.103059E+09 |
April | 45815375.73 | 583662.08 | 45231713.65 | 59987983.33 | 52603370.84 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 0.101329E+09 | 27981760.59 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.134517E+09 | 12279661.94 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.128909E+09 | 8905178.76 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 0.100877E+09 | 14653080.22 |
September | 39123254.53 | 49445.13 | 39073809.41 | 71612675.45 | 34915682.06 |
October | 33510730.10 | 0.00 | 33510730.10 | 38808434.06 | 64868645.20 |
November | 26180365.76 | 0.00 | 26180365.76 | 9214668.53 | 0.117783E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 3201715.42 | 0.157995E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.696687E+09 | 0.852469E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 3201715.42 | 8905178.76 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.134517E+09 | 0.157995E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.239501E+09 | 0.124931E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.208049E+09 | 99817338.01 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.185563E+09 | 96775850.97 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.144801E+09 | 53721483.99 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.122075E+09 | 30094834.51 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.126641E+09 | 12860527.96 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.132103E+09 | 9371976.12 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.152678E+09 | 15234271.28 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.205177E+09 | 34483813.18 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.246180E+09 | 60980683.67 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.253083E+09 | 0.102458E+09 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.242042E+09 | 0.134355E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.225789E+10 | 0.775085E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.122075E+09 | 9371976.12 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.253083E+09 | 0.134355E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.650055E+09 | 0.339088E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.564687E+09 | 0.270925E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.503657E+09 | 0.262669E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.393019E+09 | 0.145811E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.331336E+09 | 81683536.63 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.343730E+09 | 34906103.44 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.358553E+09 | 25437460.18 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.414399E+09 | 41348928.35 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.556892E+09 | 93596122.47 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.668184E+09 | 0.165514E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.686920E+09 | 0.278093E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.656951E+09 | 0.364667E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.612838E+10 | 0.210374E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.331336E+09 | 25437460.18 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.686920E+09 | 0.364667E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.501544E+09 | 0.271428E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.435440E+09 | 0.215145E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.385488E+09 | 0.207155E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.303724E+09 | 0.105829E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.266389E+09 | 50509143.33 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289737E+09 | 16622991.91 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302709E+09 | 9515114.15 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.341311E+09 | 19502256.97 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.443702E+09 | 57146741.62 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.524710E+09 | 0.117654E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.534537E+09 | 0.214699E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.508184E+09 | 0.293482E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.483748E+10 | 0.157869E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.266389E+09 | 9515114.15 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.534537E+09 | 0.293482E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.300375E+09 | 0.561210E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.331324E+09 | 0.443758E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.561239E+09 | 0.400934E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.754572E+09 | 0.195113E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.961605E+09 | 93348500.26 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105530E+10 | 31041455.71 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.985033E+09 | 17219619.14 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.904718E+09 | 36178313.39 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.819503E+09 | 0.108104E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.620226E+09 | 0.230226E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.394041E+09 | 0.444142E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269511E+09 | 0.616693E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.795745E+10 | 0.317797E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269511E+09 | 17219619.14 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105530E+10 | 0.616693E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11833185.16 | 0.302771E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 28367979.55 | 0.239697E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 62280785.03 | 0.221462E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.124292E+09 | 0.107273E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.219572E+09 | 49200098.41 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.301419E+09 | 16755632.36 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.291138E+09 | 9889243.86 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.228641E+09 | 20338666.07 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.158132E+09 | 60699730.43 |
October | 71778804.06 | 0.00 | 71778804.06 | 85342240.59 | 0.129801E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 22330596.84 | 0.241458E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8565135.67 | 0.333893E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.154191E+10 | 0.173324E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8565135.67 | 9889243.86 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.301419E+09 | 0.333893E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.319927E+09 | 0.543486E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.346950E+09 | 0.433151E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.570438E+09 | 0.400019E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.755374E+09 | 0.201083E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.956369E+09 | 98075370.05 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.104694E+10 | 32661019.60 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.976858E+09 | 18892142.12 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.901291E+09 | 39142073.63 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.822605E+09 | 0.113186E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.627466E+09 | 0.236797E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.410574E+09 | 0.433283E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.288861E+09 | 0.598044E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.802366E+10 | 0.314782E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.288861E+09 | 18892142.12 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.104694E+10 | 0.598044E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.715121E+09 | 0.416901E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.623300E+09 | 0.328420E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.556117E+09 | 0.308767E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.449508E+09 | 0.152471E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.405926E+09 | 69991387.56 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.445564E+09 | 21698727.65 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.462511E+09 | 11898144.37 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.514884E+09 | 26344732.70 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.656266E+09 | 81037220.31 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.764859E+09 | 0.174570E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.769837E+09 | 0.326834E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.722324E+09 | 0.450586E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.708622E+10 | 0.236952E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.405926E+09 | 11898144.37 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.769837E+09 | 0.450586E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 29573868.28 | 0.251800E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.129496E+09 | 0.197727E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.346545E+09 | 0.178737E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.774873E+09 | 0.912183E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.140535E+10 | 0.478522E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.194128E+10 | 0.211094E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.184815E+10 | 0.164431E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.143401E+10 | 0.257339E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.101483E+10 | 0.561616E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.506171E+09 | 0.108441E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 90398066.51 | 0.199545E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 21039220.31 | 0.274112E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.954172E+10 | 0.146888E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 21039220.31 | 0.164431E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.194128E+10 | 0.274112E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 21903108.31 | 0.259732E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.115010E+09 | 0.203436E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.320741E+09 | 0.183585E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.750940E+09 | 0.938874E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.138083E+10 | 0.494803E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.191711E+10 | 0.220362E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.182342E+10 | 0.173956E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.141061E+10 | 0.269455E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.997188E+09 | 0.579664E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.486655E+09 | 0.111495E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 77039802.84 | 0.205288E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 15937671.77 | 0.282568E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.931739E+10 | 0.151381E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 15937671.77 | 0.173956E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.191711E+10 | 0.282568E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 9701640.02 | 0.331477E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 30133132.92 | 0.262493E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 69224725.62 | 0.242100E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.147061E+09 | 0.127609E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.249248E+09 | 73255214.23 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.331738E+09 | 35962711.18 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.322258E+09 | 29480433.11 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.260549E+09 | 41487662.68 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.193518E+09 | 77305889.94 |
October | 71778804.06 | 0.00 | 71778804.06 | 0.105133E+09 | 0.144514E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 25343025.21 | 0.261708E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7095044.46 | 0.358486E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.175100E+10 | 0.198588E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7095044.46 | 29480433.11 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.331738E+09 | 0.358486E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.535350E+09 | 0.113188E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.786847E+09 | 0.890022E+09 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.118351E+10 | 0.821387E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.170827E+10 | 0.447988E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.207353E+10 | 0.271463E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.230094E+10 | 0.134482E+09 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.217194E+10 | 0.111619E+09 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.200073E+10 | 0.155277E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.178294E+10 | 0.277679E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.117352E+10 | 0.515312E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.745681E+09 | 0.888672E+09 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.514347E+09 | 0.121760E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.169776E+11 | 0.686338E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.514347E+09 | 0.111619E+09 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.230094E+10 | 0.121760E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.518435E+09 | 0.291444E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.452264E+09 | 0.233817E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.404939E+09 | 0.227633E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.327953E+09 | 0.129537E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.290742E+09 | 76879604.65 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.313243E+09 | 36556962.18 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.327862E+09 | 30011777.69 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.371360E+09 | 42251671.77 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.481069E+09 | 76908963.17 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.554676E+09 | 0.137958E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.556669E+09 | 0.231471E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.525192E+09 | 0.309406E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.512440E+10 | 0.182387E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.290742E+09 | 30011777.69 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.556669E+09 | 0.309406E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 9824662.96 | 0.396311E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 31002755.43 | 0.311539E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 77391910.00 | 0.280888E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.152743E+09 | 0.146142E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.261979E+09 | 79821913.59 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.352175E+09 | 36093837.23 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.334988E+09 | 27717586.63 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.260585E+09 | 43543248.78 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.184773E+09 | 98079755.72 |
October | 90903326.35 | 0.00 | 90903326.35 | 97720712.64 | 0.178108E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 21850172.19 | 0.318036E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 6971459.61 | 0.435948E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.179201E+10 | 0.235223E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 6971459.61 | 27717586.63 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.352175E+09 | 0.435948E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 8790163.18 | 0.354581E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 27738282.75 | 0.278735E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 69242835.11 | 0.251311E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.136659E+09 | 0.130754E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.234393E+09 | 71416968.53 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.315092E+09 | 32293292.93 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.299715E+09 | 24799029.78 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.233147E+09 | 38958309.67 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.165318E+09 | 87752329.07 |
October | 81331550.52 | 0.00 | 81331550.52 | 87431091.86 | 0.159354E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 19549431.85 | 0.284548E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 6237391.33 | 0.390028E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.160331E+10 | 0.210453E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 6237391.33 | 24799029.78 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.315092E+09 | 0.390028E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.188486E+10 | 0.100916E+10 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.163578E+10 | 0.805111E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.145261E+10 | 0.777742E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.112121E+10 | 0.440910E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.937022E+09 | 0.253305E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.977162E+09 | 0.111318E+09 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.101391E+10 | 86281518.00 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.117971E+10 | 0.133909E+09 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.160622E+10 | 0.286306E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.193508E+10 | 0.494385E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.200183E+10 | 0.814062E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.190697E+10 | 0.108459E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.176524E+11 | 0.629708E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.937022E+09 | 86281518.00 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.200183E+10 | 0.108459E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 946.86 | 496.33 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 910.16 | 438.97 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 736.55 | 381.87 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 583.62 | 227.12 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 465.13 | 129.21 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 487.30 | 61.32 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 495.07 | 46.02 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 582.24 | 69.98 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 829.45 | 153.16 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 972.35 | 250.52 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1035.18 | 420.41 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 953.04 | 534.03 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 748.60 | 266.57 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 465.13 | 46.02 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1035.18 | 534.03 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2619.86 | 1525.09 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2512.90 | 1356.40 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 2023.17 | 1185.34 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1607.03 | 703.86 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1287.84 | 392.24 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1365.35 | 178.91 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1385.98 | 134.99 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1627.58 | 208.36 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2317.37 | 446.79 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2707.61 | 757.06 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2871.12 | 1281.31 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2631.85 | 1628.68 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2076.68 | 813.95 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1287.84 | 134.99 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2871.12 | 1628.68 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3476.99 | 2032.47 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3339.84 | 1801.00 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2695.16 | 1575.73 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2150.67 | 930.63 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1728.82 | 516.01 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1838.90 | 232.77 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1864.93 | 174.41 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2181.70 | 269.57 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3087.99 | 578.47 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3591.90 | 991.80 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3802.17 | 1701.97 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3491.43 | 2176.01 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2766.76 | 1078.24 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1728.82 | 174.41 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3802.17 | 2176.01 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.16 | 299.25 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 307.78 | 264.44 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 352.17 | 225.50 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 411.14 | 117.84 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 461.59 | 56.04 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 521.24 | 19.67 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 483.28 | 10.80 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 467.89 | 22.11 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 490.81 | 65.87 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 428.21 | 130.59 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 349.22 | 247.52 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 272.72 | 325.37 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 403.02 | 148.19 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 272.72 | 10.80 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 521.24 | 325.37 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.13 | 315.98 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 151.91 | 279.06 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 235.15 | 232.52 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 341.35 | 120.42 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 441.03 | 56.47 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 522.27 | 19.94 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 475.74 | 11.39 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 423.73 | 23.40 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 380.58 | 69.63 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 266.45 | 138.85 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 163.22 | 262.33 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 105.07 | 347.79 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 302.83 | 155.89 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 105.07 | 11.39 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 522.27 | 347.79 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.29 | 112.00 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 130.12 | 101.40 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 101.40 | 89.22 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 80.21 | 56.59 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 63.14 | 34.05 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 68.78 | 17.71 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 69.45 | 15.08 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 83.39 | 21.01 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 123.39 | 37.86 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 143.02 | 59.95 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 151.36 | 94.93 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 137.24 | 117.70 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 107.14 | 62.93 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 63.14 | 15.08 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 151.36 | 117.70 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.07 | 94.32 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 9.54 | 81.78 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 20.01 | 66.44 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 42.18 | 31.94 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 71.06 | 13.77 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 100.10 | 4.49 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 93.63 | 2.36 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 74.28 | 5.34 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 53.58 | 17.31 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 28.18 | 37.31 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 7.28 | 75.88 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.10 | 104.66 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 42.26 | 44.46 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.10 | 2.36 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 100.10 | 104.66 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.10 | 293.77 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 324.92 | 256.68 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 345.73 | 212.54 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 422.70 | 106.90 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 466.07 | 50.64 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 538.36 | 18.26 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 502.00 | 10.32 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 481.67 | 20.69 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 488.57 | 60.45 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 396.75 | 125.35 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 333.46 | 240.16 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 266.82 | 318.81 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 403.44 | 142.35 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 266.82 | 10.32 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 538.36 | 318.81 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.88 | 297.25 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 156.98 | 257.97 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 224.56 | 213.44 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 352.21 | 109.41 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 443.07 | 52.89 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 535.78 | 19.12 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 491.24 | 11.13 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 434.06 | 22.15 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 373.19 | 63.28 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 231.48 | 128.41 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 136.77 | 242.25 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 84.69 | 326.17 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 296.97 | 144.76 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 84.69 | 11.13 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 535.78 | 326.17 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 317.99 | 352.03 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 324.44 | 312.83 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 295.37 | 272.57 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 292.98 | 151.89 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 308.68 | 79.46 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 373.59 | 35.46 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 361.37 | 24.84 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 351.27 | 41.15 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 396.28 | 99.13 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 392.17 | 171.47 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 360.23 | 299.90 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 313.81 | 379.04 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 340.65 | 184.35 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 292.98 | 24.84 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 396.28 | 379.04 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.60 | 296.07 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 305.72 | 261.13 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 348.78 | 222.35 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 407.26 | 115.07 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 458.40 | 53.63 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 518.92 | 18.39 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 480.71 | 9.91 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 465.16 | 20.74 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 487.14 | 63.54 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 425.31 | 127.73 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 347.59 | 243.53 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 272.22 | 321.69 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 400.49 | 145.60 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 272.22 | 9.91 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 518.92 | 321.69 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.54 | 311.63 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 151.73 | 274.72 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 233.44 | 229.25 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 338.41 | 118.00 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 438.28 | 54.22 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 519.85 | 18.71 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 473.20 | 10.53 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 421.68 | 22.02 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 378.31 | 67.03 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 265.12 | 135.86 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 163.59 | 256.89 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 105.99 | 342.89 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 301.45 | 152.90 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 105.99 | 10.53 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 519.85 | 342.89 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 267.00 | 155.65 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 257.65 | 135.76 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 207.63 | 115.28 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 173.42 | 58.82 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 151.56 | 26.13 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 171.90 | 8.37 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 172.68 | 4.44 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 192.24 | 9.84 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 253.19 | 31.26 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 285.57 | 65.18 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 297.01 | 126.09 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 269.68 | 168.23 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 224.70 | 75.14 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 151.56 | 4.44 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 297.01 | 168.23 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.04 | 940.11 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 53.53 | 817.32 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 129.38 | 667.33 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 298.95 | 351.92 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 524.70 | 178.66 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 748.95 | 81.44 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 690.02 | 61.39 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 535.40 | 96.08 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 391.52 | 216.67 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 188.98 | 404.87 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 34.88 | 769.85 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 7.86 | 1023.42 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 302.57 | 465.78 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 7.86 | 61.39 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 748.95 | 1023.42 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.18 | 969.73 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 47.54 | 840.92 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 119.75 | 685.43 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 289.71 | 362.22 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 515.54 | 184.74 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 739.63 | 85.02 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 680.79 | 64.95 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 526.66 | 100.60 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 384.72 | 223.64 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 181.70 | 416.27 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 29.72 | 792.01 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 5.95 | 1054.99 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 295.45 | 480.03 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 5.95 | 64.95 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 739.63 | 1054.99 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.78 | 630.88 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 506.29 | 554.69 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 606.45 | 469.59 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 835.72 | 265.45 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 973.71 | 155.34 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1136.21 | 79.53 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1053.47 | 63.72 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 982.48 | 88.81 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 945.83 | 164.34 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 681.13 | 294.50 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 496.82 | 517.72 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 358.98 | 672.18 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 746.61 | 328.68 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 358.98 | 63.72 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1136.21 | 672.18 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 679.26 | 625.71 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 677.86 | 554.21 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 590.04 | 482.02 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 543.55 | 276.26 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 533.30 | 149.17 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 633.29 | 68.20 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 614.51 | 50.81 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 624.24 | 80.25 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 754.32 | 181.72 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 786.99 | 305.96 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 765.11 | 523.38 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 676.59 | 673.00 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 656.22 | 329.81 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 533.30 | 50.81 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 786.99 | 673.00 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253607E+10 | 0.132938E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.220187E+10 | 0.106196E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.197279E+10 | 0.102279E+10 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.151275E+10 | 0.588704E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.124581E+10 | 0.346086E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.126307E+10 | 0.158950E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.132598E+10 | 0.123250E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.155948E+10 | 0.187444E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.214993E+10 | 0.396990E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.260433E+10 | 0.670997E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.268319E+10 | 0.108970E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.255262E+10 | 0.143034E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236079E+11 | 0.840660E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124581E+10 | 0.123250E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268319E+10 | 0.143034E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.701703E+10 | 0.408481E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.607920E+10 | 0.328141E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.541887E+10 | 0.317482E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.416541E+10 | 0.182441E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.344935E+10 | 0.105057E+10 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.353900E+10 | 0.463723E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.371222E+10 | 0.361569E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.435932E+10 | 0.558075E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.600663E+10 | 0.115809E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.725206E+10 | 0.202770E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.744193E+10 | 0.332117E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.704915E+10 | 0.436227E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654902E+11 | 0.256686E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.344935E+10 | 0.361569E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.744193E+10 | 0.436227E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.931277E+10 | 0.544377E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.807973E+10 | 0.435698E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.721872E+10 | 0.422043E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.557454E+10 | 0.241219E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.463047E+10 | 0.138207E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.476643E+10 | 0.603338E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.499502E+10 | 0.467132E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.584346E+10 | 0.722025E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.800407E+10 | 0.149938E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.962054E+10 | 0.265643E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.985523E+10 | 0.441152E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.935145E+10 | 0.582823E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.872524E+11 | 0.340035E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463047E+10 | 0.467132E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.985523E+10 | 0.582823E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766455E+09 | 0.801515E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.744581E+09 | 0.639723E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.943257E+09 | 0.603983E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106567E+10 | 0.305439E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.123631E+10 | 0.150100E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.135106E+10 | 50980785.57 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.129441E+10 | 28931569.74 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.125319E+10 | 59219561.42 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.127218E+10 | 0.170746E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114692E+10 | 0.349770E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.905187E+09 | 0.641580E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.730447E+09 | 0.871474E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127097E+11 | 0.467346E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.730447E+09 | 28931569.74 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135106E+10 | 0.871474E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319090E+09 | 0.846332E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.367489E+09 | 0.675101E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.629823E+09 | 0.622770E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.884778E+09 | 0.312128E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.118126E+10 | 0.151247E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.135372E+10 | 51680531.62 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.127423E+10 | 30495801.24 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.113491E+10 | 62667333.99 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.986471E+09 | 0.180479E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.713650E+09 | 0.371887E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.423061E+09 | 0.679947E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.281414E+09 | 0.931513E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.954990E+10 | 0.491625E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.281414E+09 | 30495801.24 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135372E+10 | 0.931513E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.365045E+09 | 0.299975E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.314790E+09 | 0.245316E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.271578E+09 | 0.238978E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.207900E+09 | 0.146682E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.169105E+09 | 91192048.80 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.178280E+09 | 45904045.26 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.186005E+09 | 40381565.88 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.223363E+09 | 56263948.56 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.319836E+09 | 98122718.94 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.383052E+09 | 0.160558E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.392327E+09 | 0.246052E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.367583E+09 | 0.315250E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.337886E+10 | 0.198467E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.169105E+09 | 40381565.88 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.392327E+09 | 0.315250E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8225849.72 | 0.252630E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 23070243.06 | 0.197831E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 53594234.36 | 0.177952E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.109334E+09 | 82783238.49 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.190337E+09 | 36870863.08 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.259470E+09 | 11645251.87 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.250789E+09 | 6319057.77 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.198950E+09 | 14301740.86 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.138881E+09 | 44856466.31 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 75479189.75 | 99943959.41 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 18874413.26 | 0.196691E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 5612461.95 | 0.280311E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.133262E+10 | 0.140214E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 5612461.95 | 6319057.77 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.259470E+09 | 0.280311E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.728801E+09 | 0.786833E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.786037E+09 | 0.620966E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.926005E+09 | 0.569279E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.109565E+10 | 0.277094E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.124832E+10 | 0.135642E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.139543E+10 | 47317979.57 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.134455E+10 | 27651752.98 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.129009E+10 | 55424177.50 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.126636E+10 | 0.156696E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.106266E+10 | 0.335746E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.864320E+09 | 0.622498E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.714649E+09 | 0.853888E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127229E+11 | 0.448904E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.714649E+09 | 27651752.98 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139543E+10 | 0.853888E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248780E+09 | 0.796153E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.379760E+09 | 0.624075E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.601470E+09 | 0.571673E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.912930E+09 | 0.283585E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.118671E+10 | 0.141658E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.138873E+10 | 49553412.61 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.131573E+10 | 29823859.96 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.116258E+10 | 59322627.64 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.967312E+09 | 0.164009E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.619999E+09 | 0.343924E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.354507E+09 | 0.627904E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.226847E+09 | 0.873611E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.936536E+10 | 0.456529E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.226847E+09 | 29823859.96 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138873E+10 | 0.873611E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851695E+09 | 0.942866E+09 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.784895E+09 | 0.756799E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.791131E+09 | 0.730050E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.759398E+09 | 0.393694E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.826758E+09 | 0.212812E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.968337E+09 | 91904577.41 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.967906E+09 | 66525210.85 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.940839E+09 | 0.110225E+09 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.102717E+10 | 0.256937E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.105039E+10 | 0.459270E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.933704E+09 | 0.777332E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.840497E+09 | 0.101522E+10 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107427E+11 | 0.581363E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.759398E+09 | 66525210.85 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105039E+10 | 0.101522E+10 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.762279E+09 | 0.792998E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.739587E+09 | 0.631726E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.934178E+09 | 0.595541E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.105562E+10 | 0.298269E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122777E+10 | 0.143633E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.134503E+10 | 47658314.17 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.128755E+10 | 26538876.80 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.124589E+10 | 55545299.48 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.126266E+10 | 0.164707E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.113916E+10 | 0.342105E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.900965E+09 | 0.631227E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.729125E+09 | 0.861605E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126298E+11 | 0.459155E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.729125E+09 | 26538876.80 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134503E+10 | 0.861605E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320169E+09 | 0.834665E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.367064E+09 | 0.664594E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.625252E+09 | 0.614014E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.877158E+09 | 0.305847E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.117389E+10 | 0.145227E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.134745E+10 | 48507781.52 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.126741E+10 | 28196313.91 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.112942E+10 | 58967072.17 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.980590E+09 | 0.173739E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.710102E+09 | 0.363891E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.424021E+09 | 0.665858E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.283880E+09 | 0.918390E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950641E+10 | 0.482190E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.283880E+09 | 28196313.91 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134745E+10 | 0.918390E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.715121E+09 | 0.416901E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.623300E+09 | 0.328420E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.556117E+09 | 0.308767E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.449508E+09 | 0.152471E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.405926E+09 | 69991387.56 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.445564E+09 | 21698727.65 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.462511E+09 | 11898144.37 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.514884E+09 | 26344732.70 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.656266E+09 | 81037220.31 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.764859E+09 | 0.174570E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.769837E+09 | 0.326834E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.722324E+09 | 0.450586E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.708622E+10 | 0.236952E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.405926E+09 | 11898144.37 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.769837E+09 | 0.450586E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29573868.28 | 0.251800E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.129496E+09 | 0.197727E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.346545E+09 | 0.178737E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.774873E+09 | 0.912183E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.140535E+10 | 0.478522E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.194128E+10 | 0.211094E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.184815E+10 | 0.164431E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.143401E+10 | 0.257339E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.101483E+10 | 0.561616E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.506171E+09 | 0.108441E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 90398066.51 | 0.199545E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 21039220.31 | 0.274112E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.954172E+10 | 0.146888E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 21039220.31 | 0.164431E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194128E+10 | 0.274112E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21903108.31 | 0.259732E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.115010E+09 | 0.203436E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.320741E+09 | 0.183585E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.750940E+09 | 0.938874E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.138083E+10 | 0.494803E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.191711E+10 | 0.220362E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.182342E+10 | 0.173956E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.141061E+10 | 0.269455E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.997188E+09 | 0.579664E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.486655E+09 | 0.111495E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 77039802.84 | 0.205288E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 15937671.77 | 0.282568E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931739E+10 | 0.151381E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 15937671.77 | 0.173956E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.191711E+10 | 0.282568E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998443E+09 | 0.168976E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.122481E+10 | 0.134189E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.162431E+10 | 0.125776E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.216620E+10 | 0.688045E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.260799E+10 | 0.416069E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.294506E+10 | 0.206143E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.282163E+10 | 0.170673E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.263149E+10 | 0.237868E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.245160E+10 | 0.425968E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.182435E+10 | 0.788800E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.128777E+10 | 0.134192E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.961496E+09 | 0.180036E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235451E+11 | 0.103653E+11 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.961496E+09 | 0.170673E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.294506E+10 | 0.180036E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181933E+10 | 0.167591E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.163988E+10 | 0.134074E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.158035E+10 | 0.129105E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.140887E+10 | 0.716073E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.142839E+10 | 0.399542E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.164149E+10 | 0.176762E+09 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.164590E+10 | 0.136086E+09 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.167197E+10 | 0.214939E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.195519E+10 | 0.471009E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.210787E+10 | 0.819485E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.198318E+10 | 0.135659E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.181218E+10 | 0.180257E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206946E+11 | 0.104008E+11 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.140887E+10 | 0.136086E+09 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210787E+10 | 0.180257E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770453E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161748621.6 | 81.21 | 0.00 | 0.00 |
February | 0.696200E+10 | -0.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146042540.9 | 81.21 | 0.00 | 0.00 |
March | 0.770307E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161612008.3 | 81.21 | 0.00 | 0.00 |
April | 0.746485E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156262167.8 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161421340.7 | 81.21 | 0.00 | 0.00 |
June | 0.745673E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203434.2 | 81.21 | 0.00 | 0.00 |
July | 0.771225E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408254.0 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161409105.6 | 81.21 | 0.00 | 0.00 |
September | 0.746615E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156208801.3 | 81.21 | 0.00 | 0.00 |
October | 0.770290E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161467740.0 | 81.21 | 0.00 | 0.00 |
November | 0.744887E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156443741.9 | 81.21 | 0.00 | 0.00 |
December | 0.771266E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161811341.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907424E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190204E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696200E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161811341.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771266E+10 | -0.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146042540.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.113625E+12 | -0.111892E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173311E+10 | 81.25 | 0.00 | 0.00 |
February | 0.102584E+12 | -0.100997E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158692E+10 | 81.26 | 0.00 | 0.00 |
March | 0.110885E+12 | -0.109106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177932E+10 | 81.26 | 0.00 | 0.00 |
April | 0.102683E+12 | -0.100964E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171870E+10 | 81.25 | 0.00 | 0.00 |
May | 0.100564E+12 | -0.987969E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176663E+10 | 81.25 | 0.00 | 0.00 |
June | 0.926643E+11 | -0.909638E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170051E+10 | 81.24 | 0.00 | 0.00 |
July | 0.929640E+11 | -0.912302E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173387E+10 | 81.24 | 0.00 | 0.00 |
August | 0.929813E+11 | -0.912535E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172777E+10 | 81.24 | 0.00 | 0.00 |
September | 0.926947E+11 | -0.910247E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167007E+10 | 81.24 | 0.00 | 0.00 |
October | 0.100608E+12 | -0.988824E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172567E+10 | 81.24 | 0.00 | 0.00 |
November | 0.102716E+12 | -0.101046E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167016E+10 | 81.25 | 0.00 | 0.00 |
December | 0.110895E+12 | -0.109168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172701E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.121586E+13 | -0.119532E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205397E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.926643E+11 | -0.111892E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.177932E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.113625E+12 | -0.909638E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158692E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.654960E+11 | -0.640241E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147187E+10 | 58.98 | 0.00 | 0.00 |
February | 0.591418E+11 | -0.577826E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.135918E+10 | 58.98 | 0.00 | 0.00 |
March | 0.632154E+11 | -0.616797E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153573E+10 | 58.98 | 0.00 | 0.00 |
April | 0.571541E+11 | -0.556723E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148181E+10 | 58.98 | 0.00 | 0.00 |
May | 0.542817E+11 | -0.527633E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151843E+10 | 58.98 | 0.00 | 0.00 |
June | 0.485249E+11 | -0.470680E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145692E+10 | 58.98 | 0.00 | 0.00 |
July | 0.476774E+11 | -0.462043E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147313E+10 | 58.98 | 0.00 | 0.00 |
August | 0.477362E+11 | -0.462715E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146476E+10 | 58.98 | 0.00 | 0.00 |
September | 0.485132E+11 | -0.470984E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141481E+10 | 58.98 | 0.00 | 0.00 |
October | 0.542684E+11 | -0.528065E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146189E+10 | 58.98 | 0.00 | 0.00 |
November | 0.571351E+11 | -0.557203E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141484E+10 | 58.98 | 0.00 | 0.00 |
December | 0.631367E+11 | -0.616729E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146372E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.666281E+12 | -0.648764E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.175171E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.476774E+11 | -0.640241E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.153573E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.654960E+11 | -0.462043E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135918E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.87 | 0.86 | 01-JAN-08:20 | 7927.13 | 38.53 | 274.50 | 280.33 | 1044.76 | 27.15 | 179.17 | 259.00 |
February | 268.33 | 0.87 | 0.86 | 01-FEB-07:49 | 6427.24 | 33.89 | 210.83 | 272.17 | 656.61 | 24.04 | 167.33 | 241.17 |
March | 351.83 | 0.88 | 0.86 | 01-MAR-07:10 | 1135.36 | 19.90 | 12.33 | 323.17 | 437.93 | 21.23 | 148.67 | 256.17 |
April | 373.83 | 0.88 | 0.86 | 01-APR-07:19 | 820.80 | 19.43 | 0.33 | 339.67 | 348.43 | 21.18 | 161.00 | 260.67 |
May | 408.83 | 0.88 | 0.86 | 01-MAY-07:19 | 686.59 | 19.07 | 0.00 | 364.17 | 296.17 | 20.82 | 134.83 | 266.50 |
June | 398.00 | 0.88 | 0.86 | 01-JUN-08:09 | 602.04 | 19.00 | 0.00 | 356.50 | 266.86 | 20.80 | 76.00 | 223.50 |
July | 400.17 | 0.88 | 0.86 | 01-JUL-08:09 | 659.82 | 18.87 | 0.00 | 362.50 | 282.78 | 20.64 | 116.83 | 217.67 |
August | 377.83 | 0.88 | 0.86 | 01-AUG-07:00 | 772.66 | 19.19 | 0.00 | 351.00 | 326.71 | 20.93 | 162.83 | 259.00 |
September | 365.83 | 0.88 | 0.86 | 01-SEP-09:39 | 887.54 | 19.30 | 0.33 | 321.17 | 375.39 | 21.09 | 153.33 | 240.67 |
October | 318.83 | 0.87 | 0.86 | 01-OCT-07:19 | 3201.31 | 26.33 | 125.67 | 314.33 | 513.35 | 22.14 | 150.50 | 279.33 |
November | 295.83 | 0.87 | 0.86 | 01-NOV-12:39 | 8202.96 | 37.69 | 288.50 | 289.67 | 800.11 | 26.02 | 160.17 | 270.67 |
December | 289.50 | 0.87 | 0.86 | 01-DEC-07:19 | 7147.65 | 38.04 | 284.67 | 278.33 | 1166.43 | 27.77 | 199.50 | 268.83 |
Annual Sum or Average | 4125.67 | 0.87 | 2797.86 | 24.68 | 1197.17 | 3853.00 | 506.35 | 22.50 | 1810.17 | 3043.17 | ||
Minimum of Months | 268.33 | 0.87 | 0.86 | 602.04 | 18.87 | 0.00 | 272.17 | 266.86 | 20.64 | 76.00 | 217.67 | |
Maximum of Months | 408.83 | 0.88 | 0.86 | 8202.96 | 38.53 | 288.50 | 364.17 | 1166.43 | 27.77 | 199.50 | 279.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.24 | 0.22 | 01-JAN-08:09 | 8370.79 | 38.58 | 274.50 | 287.17 | 1487.42 | 26.73 | 164.67 | 273.33 |
February | 268.33 | 0.25 | 0.22 | 01-FEB-07:49 | 6825.17 | 33.88 | 211.17 | 281.67 | 1054.06 | 23.76 | 150.17 | 260.50 |
March | 351.83 | 0.27 | 0.22 | 01-MAR-06:00 | 1414.38 | 20.17 | 32.83 | 337.50 | 716.34 | 21.36 | 163.67 | 308.33 |
April | 373.83 | 0.27 | 0.22 | 01-APR-06:49 | 1012.58 | 20.00 | 33.00 | 355.00 | 539.73 | 21.54 | 213.00 | 320.83 |
May | 408.83 | 0.28 | 0.22 | 01-MAY-06:19 | 827.26 | 19.84 | 2.33 | 377.50 | 436.44 | 21.37 | 287.00 | 348.67 |
June | 398.00 | 0.27 | 0.22 | 01-JUN-06:19 | 727.88 | 19.85 | 0.17 | 372.67 | 392.34 | 21.42 | 245.83 | 340.00 |
July | 400.17 | 0.28 | 0.22 | 01-JUL-06:30 | 787.61 | 19.70 | 1.00 | 381.50 | 410.18 | 21.24 | 228.00 | 337.17 |
August | 377.83 | 0.28 | 0.22 | 01-AUG-06:30 | 932.54 | 19.90 | 18.83 | 365.17 | 486.15 | 21.42 | 236.50 | 328.50 |
September | 365.83 | 0.28 | 0.22 | 01-SEP-07:19 | 1119.40 | 19.73 | 19.50 | 337.33 | 606.74 | 21.33 | 166.50 | 303.50 |
October | 318.83 | 0.26 | 0.22 | 01-OCT-06:00 | 3552.33 | 26.35 | 131.33 | 318.00 | 863.29 | 22.04 | 151.17 | 302.67 |
November | 295.83 | 0.25 | 0.22 | 01-NOV-12:39 | 8617.22 | 37.76 | 288.67 | 295.33 | 1214.76 | 25.60 | 138.67 | 283.00 |
December | 289.50 | 0.24 | 0.22 | 01-DEC-07:10 | 7575.86 | 38.11 | 284.67 | 283.83 | 1596.63 | 27.43 | 181.33 | 276.67 |
Annual Sum or Average | 4125.67 | 0.27 | 3055.24 | 25.11 | 1298.00 | 3992.67 | 763.42 | 22.67 | 2326.50 | 3683.17 | ||
Minimum of Months | 268.33 | 0.24 | 0.22 | 727.88 | 19.70 | 0.17 | 281.67 | 392.34 | 21.24 | 138.67 | 260.50 | |
Maximum of Months | 408.83 | 0.28 | 0.22 | 8617.22 | 38.58 | 288.67 | 381.50 | 1596.63 | 27.43 | 287.00 | 348.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110785E+12 | 123727.98 | 21-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.707187E+11 | 134250.79 | 01-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632004E+11 | 124431.04 | 15-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199946E+11 | 122177.62 | 07-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.917604E+09 | 52340.66 | 02-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131520E+10 | 66775.38 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126267E+11 | 114296.99 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708229E+11 | 141045.85 | 27-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869386E+11 | 135673.62 | 28-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110785E+12 | 141045.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465963E+09 | 1277.07 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277082E+09 | 1234.66 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208130E+09 | 1165.26 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20887883.54 | 544.77 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 236000.14 | 250.58 | 14-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227451E+09 | 1205.69 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.630343E+09 | 1698.69 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.630343E+09 | 1698.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19626889.00 | 350.36 | 27-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11112969.55 | 337.77 | 03-FEB-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5863859.61 | 333.11 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7598947.73 | 303.71 | 28-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100574E+09 | 524.11 | 27-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100574E+09 | 524.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39278598.77 | 299.67 | 28-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23030504.77 | 253.10 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10208837.46 | 253.08 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15419269.26 | 228.64 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127858E+09 | 358.83 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127858E+09 | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 292489.73 | 180.26 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292489.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 292489.73 | 180.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33343028.65 | 1581.51 | 15-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4697849.12 | 633.93 | 13-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 348178.39 | 444.16 | 24-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24477714.12 | 2118.06 | 27-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32170542.75 | 2118.12 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95037313.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33343028.65 | 2118.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468895E+09 | 3652.88 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57408765.58 | 3007.73 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41411709.60 | 2282.79 | 02-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167782E+09 | 2656.18 | 28-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.940545E+09 | 4820.86 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.940545E+09 | 4820.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.906512E+09 | 2866.61 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419894E+09 | 2997.76 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186058E+09 | 2588.74 | 02-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332677E+09 | 2242.16 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149657E+10 | 3359.21 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149657E+10 | 3359.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28357528.95 | 1320.19 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49689209.94 | 1782.63 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15177635.67 | 1128.42 | 02-MAR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24546.10 | 0.37 | 06-APR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33999.62 | 0.37 | 26-MAY-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22212.33 | 0.37 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21539.25 | 0.38 | 22-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19041.10 | 0.38 | 24-AUG-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21356.19 | 0.38 | 21-SEP-01:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19398.24 | 0.37 | 01-OCT-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6591.78 | 0.33 | 08-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91442290.30 | 1326.08 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6591.78 | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91442290.30 | 1782.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154075E+10 | 5753.85 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962760E+09 | 5706.38 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539158E+09 | 5749.44 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53605299.44 | 2604.16 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1931273.35 | 2525.00 | 08-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 220645.30 | 2111.96 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57174.30 | 452.49 | 19-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 945458.46 | 1882.68 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 863773.59 | 2370.44 | 28-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9468580.98 | 2685.33 | 07-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732774E+09 | 5759.00 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203470E+10 | 5844.85 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 57174.30 | 452.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203470E+10 | 5844.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249214E+10 | 5833.30 | 26-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152773E+10 | 5832.58 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744077E+09 | 5800.10 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55405368.00 | 3282.14 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1365156.19 | 2839.48 | 05-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 171277.33 | 890.99 | 26-JUN-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15140.04 | 176.63 | 16-JUL-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 210119.61 | 560.25 | 17-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 644207.84 | 1686.91 | 27-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13791589.40 | 2635.44 | 07-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115810E+10 | 5794.19 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320289E+10 | 5833.48 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15140.04 | 176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.320289E+10 | 5833.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.622653E+10 | 33226.43 | 27-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350732E+10 | 33114.15 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116034E+10 | 30759.74 | 29-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38686932.98 | 29584.96 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6433102.23 | 14250.93 | 01-MAY-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 790251.22 | 2722.72 | 29-JUN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 217087.34 | 2082.12 | 24-AUG-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3280235.63 | 10490.77 | 20-SEP-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27746013.11 | 23928.63 | 24-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243511E+10 | 32936.83 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.920638E+10 | 33389.21 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.920638E+10 | 33389.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161607E+10 | 5620.14 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.908797E+09 | 5493.67 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.548934E+09 | 5519.38 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51223648.64 | 1588.78 | 22-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73209.47 | 610.08 | 03-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2811.15 | 28.11 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87265.90 | 872.66 | 19-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 248695.91 | 1687.31 | 14-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21442460.13 | 2159.83 | 15-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790655E+09 | 5596.84 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206034E+10 | 5691.68 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.599787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206034E+10 | 5691.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254200E+10 | 5628.96 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138424E+10 | 5569.06 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747731E+09 | 5566.99 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58219340.71 | 3650.61 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 209210.63 | 570.95 | 04-MAY-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74036.72 | 862.46 | 19-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80766.66 | 673.06 | 17-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 121221.08 | 825.76 | 29-SEP-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39098774.48 | 2386.67 | 15-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120881E+10 | 5654.08 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316779E+10 | 5678.39 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316779E+10 | 5678.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660681E+09 | 1746.26 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441770E+09 | 1739.31 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286209E+09 | 1745.17 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45295366.69 | 1691.35 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2101586.07 | 668.22 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 195638.63 | 521.96 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2218.95 | 20.33 | 21-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 475183.19 | 550.67 | 16-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 981769.01 | 540.40 | 26-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24985033.70 | 638.09 | 10-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361667E+09 | 1745.61 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.829720E+09 | 1745.54 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2218.95 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.829720E+09 | 1746.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.979633E+09 | 1742.84 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.634303E+09 | 1742.14 | 17-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356171E+09 | 1741.75 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44861887.32 | 1690.79 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 709635.39 | 713.01 | 06-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36818.60 | 213.16 | 11-JUN-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31387.20 | 178.59 | 29-JUL-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 130216.99 | 255.70 | 30-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 905586.39 | 564.89 | 29-SEP-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30869438.77 | 1171.14 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540889E+09 | 1742.20 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120383E+10 | 1742.34 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31387.20 | 178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120383E+10 | 1742.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115926E+10 | 8113.32 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764592E+09 | 4207.71 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580499E+09 | 8012.21 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107813E+09 | 3085.83 | 18-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5622742.66 | 2654.93 | 10-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 579858.71 | 2755.29 | 28-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 378104.51 | 618.21 | 18-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 600934.60 | 2212.05 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 882359.34 | 1822.54 | 08-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13934638.19 | 2869.61 | 07-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662216E+09 | 8048.71 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158034E+10 | 8174.19 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 378104.51 | 618.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158034E+10 | 8174.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.634906E+10 | 0.634906E+10 | 89892.32 | 03-JAN-17:00 | 89892.32 | 0.00 |
February | 0.00 | 0.00 | 0.327740E+11 | 0.327740E+11 | 124604.07 | 21-FEB-16:13 | 124604.07 | 0.00 |
March | 0.00 | 0.00 | 0.669580E+11 | 0.669580E+11 | 160086.38 | 14-MAR-18:10 | 160086.38 | 0.00 |
April | 0.00 | 0.00 | 0.210536E+12 | 0.210536E+12 | 232451.98 | 19-APR-21:00 | 232451.98 | 0.10 |
May | 0.00 | 0.00 | 0.349646E+12 | 0.348107E+12 | 256574.42 | 19-MAY-19:10 | 256574.42 | 0.36 |
June | 0.00 | 0.00 | 0.452127E+12 | 0.447200E+12 | 302481.53 | 19-JUN-18:02 | 203615.78 | 0.69 |
July | 0.00 | 0.00 | 0.604956E+12 | 0.468638E+12 | 478794.26 | 21-JUL-21:00 | 220550.00 | 1.00 |
August | 0.00 | 0.00 | 0.491102E+12 | 0.438975E+12 | 453910.00 | 01-AUG-20:50 | 212306.91 | 0.98 |
September | 0.00 | 0.00 | 0.400819E+12 | 0.345211E+12 | 336972.62 | 09-SEP-20:00 | 185995.07 | 0.85 |
October | 0.00 | 0.00 | 0.197980E+12 | 0.189585E+12 | 383831.25 | 03-OCT-19:55 | 210012.63 | 0.43 |
November | 0.00 | 0.00 | 0.407680E+11 | 0.407680E+11 | 148848.45 | 03-NOV-15:55 | 148848.45 | 0.03 |
December | 0.00 | 0.00 | 0.370344E+10 | 0.370344E+10 | 48738.53 | 23-DEC-15:00 | 48738.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.285772E+13 | 0.259880E+13 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.370344E+10 | 0.370344E+10 | 48738.53 | 48738.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.604956E+12 | 0.468638E+12 | 478794.26 | 256574.42 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424271E+09 | 0.424271E+09 | 11015.35 | 03-JAN-17:00 | 11015.35 | 0.00 |
February | 0.00 | 0.00 | 0.213329E+10 | 0.213329E+10 | 14187.69 | 20-FEB-16:02 | 14187.69 | 0.00 |
March | 0.00 | 0.00 | 0.440325E+10 | 0.440325E+10 | 14760.49 | 22-MAR-15:02 | 14760.49 | 0.00 |
April | 0.00 | 0.00 | 0.144427E+11 | 0.144427E+11 | 17660.73 | 21-APR-15:02 | 17660.73 | 0.08 |
May | 0.00 | 0.00 | 0.238606E+11 | 0.233116E+11 | 21816.91 | 24-MAY-13:00 | 16245.16 | 0.28 |
June | 0.00 | 0.00 | 0.297804E+11 | 0.285424E+11 | 24534.76 | 27-JUN-24:00 | 12151.89 | 0.56 |
July | 0.00 | 0.00 | 0.421110E+11 | 0.300770E+11 | 39037.79 | 21-JUL-08:03 | 13821.47 | 0.79 |
August | 0.00 | 0.00 | 0.344471E+11 | 0.282819E+11 | 33560.00 | 01-AUG-21:51 | 14428.59 | 0.79 |
September | 0.00 | 0.00 | 0.289207E+11 | 0.220951E+11 | 31964.14 | 22-SEP-08:03 | 14826.78 | 0.67 |
October | 0.00 | 0.00 | 0.137054E+11 | 0.123357E+11 | 27787.53 | 03-OCT-20:20 | 14079.21 | 0.34 |
November | 0.00 | 0.00 | 0.268538E+10 | 0.268538E+10 | 14427.26 | 09-NOV-16:02 | 14427.26 | 0.02 |
December | 0.00 | 0.00 | 0.217498E+09 | 0.217498E+09 | 5697.71 | 10-DEC-14:00 | 5697.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197132E+12 | 0.168950E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.217498E+09 | 0.217498E+09 | 5697.71 | 5697.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.421110E+11 | 0.300770E+11 | 39037.79 | 17660.73 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.791304E+09 | 0.744796E+09 | 9735.11 | 22-JAN-16:02 | 9735.11 | 0.04 |
February | 0.00 | 0.00 | 0.125782E+10 | 0.124653E+10 | 9732.84 | 18-FEB-16:02 | 9732.84 | 0.01 |
March | 0.00 | 0.00 | 0.238410E+10 | 0.236308E+10 | 9734.54 | 12-MAR-15:02 | 9734.54 | 0.02 |
April | 0.00 | 0.00 | 0.557417E+10 | 0.525322E+10 | 9735.41 | 21-APR-18:02 | 9735.41 | 0.22 |
May | 0.00 | 0.00 | 0.865679E+10 | 0.769104E+10 | 10775.12 | 28-MAY-08:62 | 9059.14 | 0.52 |
June | 0.00 | 0.00 | 0.109694E+11 | 0.939593E+10 | 10657.11 | 28-JUN-08:62 | 9090.23 | 0.75 |
July | 0.00 | 0.00 | 0.116809E+11 | 0.875618E+10 | 12478.13 | 19-JUL-08:62 | 7926.09 | 0.96 |
August | 0.00 | 0.00 | 0.106826E+11 | 0.810155E+10 | 11235.39 | 14-AUG-08:62 | 8456.80 | 0.95 |
September | 0.00 | 0.00 | 0.972614E+10 | 0.730791E+10 | 11611.83 | 09-SEP-08:62 | 8509.09 | 0.94 |
October | 0.00 | 0.00 | 0.629859E+10 | 0.478345E+10 | 11157.04 | 15-OCT-08:62 | 8013.02 | 0.74 |
November | 0.00 | 0.00 | 0.230023E+10 | 0.213438E+10 | 9735.54 | 09-NOV-16:02 | 9735.54 | 0.12 |
December | 0.00 | 0.00 | 0.468804E+09 | 0.457746E+09 | 9733.57 | 13-DEC-16:02 | 9733.57 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.707908E+11 | 0.582358E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.468804E+09 | 0.457746E+09 | 9732.84 | 7926.09 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.116809E+11 | 0.939593E+10 | 12478.13 | 9735.54 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134507E+09 | 0.129199E+09 | 9670.13 | 12-JAN-16:02 | 9670.13 | 0.01 |
February | 0.00 | 0.00 | 0.227648E+09 | 0.225200E+09 | 9667.72 | 18-FEB-16:02 | 9667.72 | 0.00 |
March | 0.00 | 0.00 | 0.782981E+09 | 0.767508E+09 | 9669.69 | 12-MAR-15:02 | 9669.69 | 0.01 |
April | 0.00 | 0.00 | 0.411494E+10 | 0.385410E+10 | 10678.21 | 06-APR-18:11 | 10678.21 | 0.18 |
May | 0.00 | 0.00 | 0.783043E+10 | 0.701417E+10 | 11335.91 | 28-MAY-08:51 | 9194.54 | 0.45 |
June | 0.00 | 0.00 | 0.105158E+11 | 0.911159E+10 | 11486.19 | 04-JUN-08:51 | 9444.90 | 0.67 |
July | 0.00 | 0.00 | 0.110327E+11 | 0.840950E+10 | 13353.11 | 22-JUL-08:31 | 8454.29 | 0.86 |
August | 0.00 | 0.00 | 0.948157E+10 | 0.726182E+10 | 12842.21 | 03-AUG-08:61 | 8993.46 | 0.82 |
September | 0.00 | 0.00 | 0.744938E+10 | 0.556205E+10 | 12409.61 | 03-SEP-08:51 | 8725.74 | 0.75 |
October | 0.00 | 0.00 | 0.333266E+10 | 0.228746E+10 | 11709.27 | 03-OCT-21:52 | 8672.83 | 0.53 |
November | 0.00 | 0.00 | 0.527854E+09 | 0.446107E+09 | 9669.20 | 13-NOV-16:02 | 9669.20 | 0.07 |
December | 0.00 | 0.00 | 55150681.86 | 53822204.81 | 9661.89 | 16-DEC-16:02 | 9661.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554856E+11 | 0.451225E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 55150681.86 | 53822204.81 | 9661.89 | 8454.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110327E+11 | 0.911159E+10 | 13353.11 | 10678.21 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176245E+11 | 0.176245E+11 | 39587.94 | 12-JAN-14:25 | 39587.94 | 0.00 |
February | 0.00 | 0.00 | 0.184525E+11 | 0.182800E+11 | 37655.20 | 07-FEB-13:40 | 37655.20 | 0.02 |
March | 0.00 | 0.00 | 0.170120E+11 | 0.168659E+11 | 29067.78 | 16-MAR-12:50 | 29067.78 | 0.02 |
April | 0.00 | 0.00 | 0.262409E+11 | 0.249767E+11 | 27807.73 | 04-APR-13:30 | 27807.73 | 0.10 |
May | 0.00 | 0.00 | 0.334245E+11 | 0.277741E+11 | 26874.52 | 19-MAY-20:20 | 22350.22 | 0.36 |
June | 0.00 | 0.00 | 0.425824E+11 | 0.316128E+11 | 30303.13 | 15-JUN-20:20 | 30303.13 | 0.67 |
July | 0.00 | 0.00 | 0.468014E+11 | 0.264147E+11 | 31428.65 | 26-JUL-17:20 | 25634.92 | 1.00 |
August | 0.00 | 0.00 | 0.472417E+11 | 0.290099E+11 | 33055.46 | 29-AUG-13:00 | 26156.55 | 0.99 |
September | 0.00 | 0.00 | 0.515260E+11 | 0.354094E+11 | 41767.30 | 19-SEP-13:30 | 34853.88 | 0.98 |
October | 0.00 | 0.00 | 0.445738E+11 | 0.356723E+11 | 47214.46 | 22-OCT-13:15 | 46742.76 | 0.59 |
November | 0.00 | 0.00 | 0.298884E+11 | 0.286825E+11 | 43632.52 | 09-NOV-13:50 | 43632.52 | 0.10 |
December | 0.00 | 0.00 | 0.141262E+11 | 0.141262E+11 | 32463.13 | 16-DEC-13:40 | 32463.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.389494E+12 | 0.306449E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.141262E+11 | 0.141262E+11 | 26874.52 | 22350.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.515260E+11 | 0.356723E+11 | 47214.46 | 46742.76 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.235701E+10 | 0.205514E+10 | 59922.81 | 01-JAN-09:02 | 59922.81 | 0.05 |
February | 0.00 | 0.00 | 0.490155E+10 | 0.451307E+10 | 62544.06 | 21-FEB-21:32 | 62544.06 | 0.05 |
March | 0.00 | 0.00 | 0.106002E+11 | 0.101947E+11 | 63723.64 | 15-MAR-21:52 | 63723.64 | 0.04 |
April | 0.00 | 0.00 | 0.290798E+11 | 0.275831E+11 | 65178.99 | 05-APR-21:52 | 65178.99 | 0.16 |
May | 0.00 | 0.00 | 0.494486E+11 | 0.444557E+11 | 70941.14 | 23-MAY-21:51 | 62880.20 | 0.40 |
June | 0.00 | 0.00 | 0.655481E+11 | 0.566210E+11 | 71033.92 | 19-JUN-18:51 | 65250.88 | 0.63 |
July | 0.00 | 0.00 | 0.709912E+11 | 0.538061E+11 | 83528.23 | 21-JUL-08:51 | 51926.99 | 0.80 |
August | 0.00 | 0.00 | 0.601546E+11 | 0.455133E+11 | 78289.67 | 16-AUG-21:52 | 56377.50 | 0.74 |
September | 0.00 | 0.00 | 0.455275E+11 | 0.334635E+11 | 78602.08 | 23-SEP-21:51 | 57437.98 | 0.65 |
October | 0.00 | 0.00 | 0.268092E+11 | 0.192301E+11 | 76645.72 | 03-OCT-21:52 | 57687.93 | 0.47 |
November | 0.00 | 0.00 | 0.651981E+10 | 0.548230E+10 | 62166.16 | 08-NOV-22:52 | 62166.16 | 0.12 |
December | 0.00 | 0.00 | 0.159089E+10 | 0.151895E+10 | 60262.14 | 09-DEC-09:02 | 60262.14 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.373528E+12 | 0.304437E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.159089E+10 | 0.151895E+10 | 59922.81 | 51926.99 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.709912E+11 | 0.566210E+11 | 83528.23 | 65250.88 | 0.80 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.693705E+09 | 0.641638E+09 | 8575.51 | 31-JAN-09:02 | 8575.51 | 0.05 |
February | 0.00 | 0.00 | 0.141671E+10 | 0.139195E+10 | 8577.27 | 19-FEB-09:02 | 8577.27 | 0.02 |
March | 0.00 | 0.00 | 0.242760E+10 | 0.240560E+10 | 8577.57 | 25-MAR-08:62 | 8577.57 | 0.02 |
April | 0.00 | 0.00 | 0.587336E+10 | 0.556771E+10 | 8577.48 | 21-APR-18:02 | 8577.48 | 0.23 |
May | 0.00 | 0.00 | 0.888281E+10 | 0.799691E+10 | 8963.04 | 28-MAY-08:62 | 8324.16 | 0.53 |
June | 0.00 | 0.00 | 0.113332E+11 | 0.996102E+10 | 9266.79 | 29-JUN-08:62 | 7939.82 | 0.77 |
July | 0.00 | 0.00 | 0.120168E+11 | 0.934943E+10 | 11013.65 | 19-JUL-08:62 | 6970.66 | 0.98 |
August | 0.00 | 0.00 | 0.109910E+11 | 0.871880E+10 | 9900.65 | 14-AUG-08:62 | 7435.35 | 0.97 |
September | 0.00 | 0.00 | 0.984990E+10 | 0.766791E+10 | 10250.61 | 23-SEP-18:02 | 7483.19 | 0.96 |
October | 0.00 | 0.00 | 0.590295E+10 | 0.454444E+10 | 10102.32 | 15-OCT-08:62 | 7581.88 | 0.74 |
November | 0.00 | 0.00 | 0.219010E+10 | 0.204482E+10 | 8706.52 | 03-NOV-08:62 | 8486.17 | 0.12 |
December | 0.00 | 0.00 | 0.496275E+09 | 0.470319E+09 | 8575.61 | 10-DEC-09:02 | 8575.61 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.720744E+11 | 0.607606E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.496275E+09 | 0.470319E+09 | 8575.51 | 6970.66 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.120168E+11 | 0.996102E+10 | 11013.65 | 8577.57 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 78029302.90 | 58496264.46 | 8145.06 | 31-JAN-09:02 | 8145.06 | 0.02 |
February | 0.00 | 0.00 | 0.388124E+09 | 0.369513E+09 | 8512.70 | 19-FEB-09:02 | 8512.70 | 0.02 |
March | 0.00 | 0.00 | 0.102075E+10 | 0.100481E+10 | 8512.28 | 25-MAR-08:62 | 8512.28 | 0.02 |
April | 0.00 | 0.00 | 0.438011E+10 | 0.412810E+10 | 9876.02 | 27-APR-08:51 | 9876.02 | 0.19 |
May | 0.00 | 0.00 | 0.776751E+10 | 0.704084E+10 | 10809.76 | 28-MAY-08:51 | 9233.21 | 0.47 |
June | 0.00 | 0.00 | 0.106247E+11 | 0.942395E+10 | 11359.07 | 20-JUN-08:62 | 10486.66 | 0.69 |
July | 0.00 | 0.00 | 0.111372E+11 | 0.876527E+10 | 12321.09 | 21-JUL-08:51 | 7916.95 | 0.87 |
August | 0.00 | 0.00 | 0.955543E+10 | 0.759373E+10 | 11913.00 | 03-AUG-07:42 | 9170.28 | 0.84 |
September | 0.00 | 0.00 | 0.729327E+10 | 0.546943E+10 | 11540.73 | 03-SEP-08:51 | 8745.67 | 0.77 |
October | 0.00 | 0.00 | 0.314424E+10 | 0.219721E+10 | 10508.90 | 05-OCT-08:51 | 9439.92 | 0.54 |
November | 0.00 | 0.00 | 0.553846E+09 | 0.491668E+09 | 8996.05 | 09-NOV-09:51 | 8996.05 | 0.05 |
December | 0.00 | 0.00 | 55398425.73 | 48419723.92 | 8267.98 | 16-DEC-09:02 | 8267.98 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.559986E+11 | 0.465914E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 55398425.73 | 48419723.92 | 8145.06 | 7916.95 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.111372E+11 | 0.942395E+10 | 12321.09 | 10486.66 | 0.87 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.166267E+09 | 0.159263E+09 | 2581.83 | 22-JAN-16:02 | 2581.83 | 0.02 |
February | 0.00 | 0.00 | 0.280492E+09 | 0.279032E+09 | 2581.21 | 07-FEB-16:01 | 2581.21 | 0.01 |
March | 0.00 | 0.00 | 0.546133E+09 | 0.543407E+09 | 2581.70 | 12-MAR-15:02 | 2581.70 | 0.01 |
April | 0.00 | 0.00 | 0.135936E+10 | 0.127971E+10 | 2581.80 | 21-APR-18:02 | 2581.80 | 0.21 |
May | 0.00 | 0.00 | 0.215981E+10 | 0.190607E+10 | 2928.01 | 28-MAY-08:62 | 2356.64 | 0.52 |
June | 0.00 | 0.00 | 0.283381E+10 | 0.241179E+10 | 2911.61 | 28-JUN-08:62 | 2286.85 | 0.76 |
July | 0.00 | 0.00 | 0.301997E+10 | 0.224590E+10 | 3467.74 | 19-JUL-08:62 | 1948.39 | 0.96 |
August | 0.00 | 0.00 | 0.272014E+10 | 0.204571E+10 | 3092.94 | 14-AUG-08:62 | 2086.82 | 0.95 |
September | 0.00 | 0.00 | 0.239690E+10 | 0.178359E+10 | 3214.14 | 09-SEP-08:62 | 2166.80 | 0.93 |
October | 0.00 | 0.00 | 0.144357E+10 | 0.109693E+10 | 3077.02 | 09-OCT-08:62 | 2050.71 | 0.66 |
November | 0.00 | 0.00 | 0.479512E+09 | 0.448907E+09 | 2581.83 | 09-NOV-16:02 | 2581.83 | 0.09 |
December | 0.00 | 0.00 | 0.100317E+09 | 98205950.92 | 2581.43 | 13-DEC-16:02 | 2581.43 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.175063E+11 | 0.142985E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.100317E+09 | 98205950.92 | 2581.21 | 1948.39 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.301997E+10 | 0.241179E+10 | 3467.74 | 2581.83 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 23466800.61 | 22490346.47 | 2561.93 | 12-JAN-16:02 | 2561.93 | 0.00 |
February | 0.00 | 0.00 | 39333324.40 | 39087067.47 | 2561.29 | 18-FEB-16:02 | 2561.29 | 0.00 |
March | 0.00 | 0.00 | 0.153496E+09 | 0.151810E+09 | 2561.83 | 12-MAR-15:02 | 2561.83 | 0.01 |
April | 0.00 | 0.00 | 0.101126E+10 | 0.947049E+09 | 2839.11 | 06-APR-18:11 | 2839.11 | 0.18 |
May | 0.00 | 0.00 | 0.198717E+10 | 0.176890E+10 | 3008.83 | 28-MAY-08:51 | 2405.43 | 0.46 |
June | 0.00 | 0.00 | 0.275535E+10 | 0.237750E+10 | 3065.49 | 04-JUN-08:51 | 2488.19 | 0.68 |
July | 0.00 | 0.00 | 0.289137E+10 | 0.219922E+10 | 3603.48 | 22-JUL-08:31 | 2196.08 | 0.86 |
August | 0.00 | 0.00 | 0.245221E+10 | 0.186623E+10 | 3451.18 | 03-AUG-08:61 | 2309.51 | 0.82 |
September | 0.00 | 0.00 | 0.185977E+10 | 0.137458E+10 | 3349.10 | 03-SEP-08:51 | 2245.32 | 0.74 |
October | 0.00 | 0.00 | 0.719436E+09 | 0.501623E+09 | 3154.41 | 03-OCT-21:52 | 2224.00 | 0.44 |
November | 0.00 | 0.00 | 84286383.11 | 70676483.23 | 2561.68 | 13-NOV-16:02 | 2561.68 | 0.04 |
December | 0.00 | 0.00 | 9213279.51 | 8912921.83 | 2526.71 | 16-DEC-16:02 | 2526.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139864E+11 | 0.113281E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 9213279.51 | 8912921.83 | 2526.71 | 2196.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.289137E+10 | 0.237750E+10 | 3603.48 | 2839.11 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.448859E+10 | 0.424406E+10 | 11706.08 | 03-JAN-16:02 | 11706.08 | 0.17 |
February | 0.00 | 0.00 | 0.451339E+10 | 0.444036E+10 | 11706.21 | 18-FEB-16:02 | 11706.21 | 0.05 |
March | 0.00 | 0.00 | 0.447557E+10 | 0.442150E+10 | 11705.92 | 05-MAR-16:02 | 11705.92 | 0.03 |
April | 0.00 | 0.00 | 0.695170E+10 | 0.652701E+10 | 11918.28 | 18-APR-18:02 | 11543.72 | 0.24 |
May | 0.00 | 0.00 | 0.935264E+10 | 0.795177E+10 | 12933.22 | 28-MAY-08:62 | 10897.09 | 0.60 |
June | 0.00 | 0.00 | 0.123133E+11 | 0.102390E+11 | 12724.04 | 28-JUN-08:62 | 10303.53 | 0.80 |
July | 0.00 | 0.00 | 0.138751E+11 | 0.100793E+11 | 15696.14 | 19-JUL-08:62 | 8811.19 | 0.96 |
August | 0.00 | 0.00 | 0.134586E+11 | 0.100984E+11 | 13799.30 | 02-AUG-08:62 | 10334.10 | 0.95 |
September | 0.00 | 0.00 | 0.135676E+11 | 0.104907E+11 | 14568.96 | 23-SEP-18:02 | 9825.32 | 0.94 |
October | 0.00 | 0.00 | 0.109395E+11 | 0.903120E+10 | 13462.56 | 04-OCT-08:62 | 10488.11 | 0.77 |
November | 0.00 | 0.00 | 0.679141E+10 | 0.650022E+10 | 11706.37 | 09-NOV-19:02 | 11706.37 | 0.18 |
December | 0.00 | 0.00 | 0.405188E+10 | 0.394078E+10 | 11705.76 | 10-DEC-16:02 | 11705.76 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.104779E+12 | 0.879642E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.405188E+10 | 0.394078E+10 | 11705.76 | 8811.19 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.138751E+11 | 0.104907E+11 | 15696.14 | 11706.37 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48159.68 | 159844.92 | 14-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33511.04 | 150227.99 | 01-FEB-19:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25431.53 | 141271.67 | 24-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7842.09 | 131357.37 | 11-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 347.57 | 52189.17 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2.35 | 11060.13 | 29-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.92 | 5226.13 | 19-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 2.42 | 10355.23 | 14-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 502.88 | 67087.26 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4747.83 | 120641.91 | 25-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 30440.61 | 173770.29 | 27-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 42097.99 | 179898.32 | 28-DEC-19:02 |
Annual Sum or Average | 0.00 | 16017.46 | ||||
Minimum of Months | 0.00 | 0.00 | 0.92 | 5226.13 | ||
Maximum of Months | 0.00 | 0.00 | 48159.68 | 179898.32 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14000.04 | 225072.62 | 03-JAN-16:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29305.77 | 306023.74 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43431.41 | 310229.49 | 14-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 121732.91 | 399745.33 | 28-APR-18:04 | 0.00 | 0.00 | 01-APR-00:10 |
May | 190168.63 | 416939.90 | 12-MAY-18:06 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 253702.60 | 465934.34 | 19-JUN-18:51 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 312416.49 | 616880.70 | 20-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 260858.06 | 605691.15 | 01-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 225730.99 | 460493.02 | 03-SEP-21:51 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 119893.07 | 479056.27 | 03-OCT-19:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 37695.31 | 302092.14 | 08-NOV-16:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 10873.40 | 160772.12 | 10-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 135581.62 | 0.00 | ||||
Minimum of Months | 10873.40 | 160772.12 | 0.00 | 0.00 | ||
Maximum of Months | 312416.49 | 616880.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25475.11 | 51764.58 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 25455.69 | 51745.20 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24601.43 | 50760.20 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23055.09 | 47881.87 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 21280.55 | 44485.00 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 19743.88 | 40790.73 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18838.89 | 38050.38 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18863.67 | 38280.86 | 31-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19756.97 | 40875.49 | 29-SEP-06:24 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21296.52 | 44584.06 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23073.62 | 48126.50 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24599.36 | 50697.14 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 22151.42 | ||||
Minimum of Months | 0.00 | 0.00 | 18838.89 | 38050.38 | ||
Maximum of Months | 0.00 | 0.00 | 25475.11 | 51764.58 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.80 | 1299.30 | 03-JAN-16:02 | 1.01 |
February | 0.244774E+10 | 0.80 | 1299.30 | 11-FEB-16:02 | 1.02 |
March | 0.271000E+10 | 0.80 | 1299.30 | 29-MAR-15:02 | 1.02 |
April | 0.262258E+10 | 0.80 | 1299.30 | 15-APR-08:15 | 1.02 |
May | 0.271000E+10 | 0.80 | 1299.30 | 08-MAY-19:50 | 1.01 |
June | 0.262258E+10 | 0.80 | 1299.30 | 01-JUN-20:00 | 1.01 |
July | 0.271000E+10 | 0.79 | 1299.30 | 02-JUL-08:40 | 1.00 |
August | 0.271000E+10 | 0.79 | 1299.30 | 01-AUG-08:30 | 1.00 |
September | 0.262258E+10 | 0.79 | 1299.30 | 01-SEP-08:56 | 1.00 |
October | 0.271000E+10 | 0.80 | 1299.30 | 03-OCT-18:50 | 1.00 |
November | 0.262258E+10 | 0.80 | 1299.30 | 10-NOV-16:13 | 1.01 |
December | 0.271000E+10 | 0.80 | 1299.30 | 10-DEC-16:02 | 1.01 |
Annual Sum or Average | 0.319080E+11 | 0.80 | |||
Minimum of Months | 0.244774E+10 | 0.79 | 1299.30 | 1.00 | |
Maximum of Months | 0.271000E+10 | 0.80 | 1299.30 | 1.02 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332594E+11 | 0.86 | 24762.42 | 03-JAN-22:10 | 1.28 |
February | 0.303257E+11 | 0.86 | 25352.21 | 06-FEB-22:10 | 1.30 |
March | 0.343761E+11 | 0.87 | 26211.13 | 15-MAR-21:10 | 1.32 |
April | 0.362282E+11 | 0.91 | 30478.72 | 21-APR-21:10 | 1.45 |
May | 0.402475E+11 | 0.95 | 32970.61 | 31-MAY-21:10 | 1.51 |
June | 0.424183E+11 | 0.99 | 35920.78 | 15-JUN-21:10 | 1.60 |
July | 0.440025E+11 | 0.98 | 37466.12 | 26-JUL-21:10 | 1.63 |
August | 0.449200E+11 | 1.00 | 39989.11 | 07-AUG-21:10 | 1.69 |
September | 0.431926E+11 | 0.99 | 40305.38 | 22-SEP-21:10 | 1.70 |
October | 0.413824E+11 | 0.96 | 39208.32 | 05-OCT-21:10 | 1.67 |
November | 0.358806E+11 | 0.91 | 33296.71 | 09-NOV-22:10 | 1.52 |
December | 0.337042E+11 | 0.86 | 25394.33 | 15-DEC-22:10 | 1.30 |
Annual Sum or Average | 0.459937E+12 | 0.93 | |||
Minimum of Months | 0.303257E+11 | 0.86 | 24762.42 | 1.28 | |
Maximum of Months | 0.449200E+11 | 1.00 | 40305.38 | 1.70 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:10 | 0.31 |
February | 0.185347E+09 | 0.31 | 76.61 | 01-FEB-00:10 | 0.31 |
March | 0.205205E+09 | 0.31 | 76.61 | 01-MAR-00:10 | 0.31 |
April | 0.198586E+09 | 0.31 | 76.61 | 01-APR-00:10 | 0.31 |
May | 0.205205E+09 | 0.31 | 76.61 | 01-MAY-00:05 | 0.31 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:05 | 0.31 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:05 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:05 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.31 |
November | 0.198586E+09 | 0.31 | 76.61 | 01-NOV-00:05 | 0.31 |
December | 0.205205E+09 | 0.31 | 76.61 | 01-DEC-00:10 | 0.31 |
Annual Sum or Average | 0.241613E+10 | 0.31 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:10 | 0.31 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:05 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.31 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.31 |
May | 0.116283E+10 | 0.22 | 612.92 | 01-MAY-06:05 | 0.31 |
June | 0.112532E+10 | 0.22 | 612.92 | 01-JUN-06:05 | 0.31 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:10 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.22 | 612.92 | 01-OCT-06:10 | 0.31 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:05 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:05 | 0.31 |
Annual Sum or Average | 0.136914E+11 | 0.22 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238788E+09 | 0.51 | 836.44 | 01-JAN-16:02 | 0.66 |
February | 0.221448E+09 | 0.52 | 836.44 | 01-FEB-09:02 | 0.66 |
March | 0.284509E+09 | 0.54 | 836.44 | 01-MAR-09:02 | 0.66 |
April | 0.506693E+09 | 0.59 | 836.44 | 01-APR-08:62 | 0.66 |
May | 0.752868E+09 | 0.62 | 836.44 | 01-MAY-08:62 | 0.67 |
June | 0.925987E+09 | 0.64 | 836.44 | 01-JUN-08:62 | 0.66 |
July | 0.900959E+09 | 0.64 | 836.44 | 01-JUL-08:62 | 0.66 |
August | 0.836162E+09 | 0.63 | 836.44 | 01-AUG-08:62 | 0.66 |
September | 0.765475E+09 | 0.63 | 836.44 | 01-SEP-08:62 | 0.66 |
October | 0.536854E+09 | 0.59 | 836.44 | 01-OCT-08:62 | 0.66 |
November | 0.285869E+09 | 0.55 | 836.44 | 02-NOV-15:02 | 0.66 |
December | 0.246501E+09 | 0.50 | 836.44 | 01-DEC-16:02 | 0.66 |
Annual Sum or Average | 0.650211E+10 | 0.58 | |||
Minimum of Months | 0.221448E+09 | 0.50 | 836.44 | 0.66 | |
Maximum of Months | 0.925987E+09 | 0.64 | 836.44 | 0.67 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.253113E+09 | 0.46 | 830.82 | 01-JAN-16:02 | 0.66 |
February | 0.178886E+09 | 0.43 | 830.82 | 01-FEB-09:02 | 0.66 |
March | 0.165630E+09 | 0.42 | 830.82 | 01-MAR-09:02 | 0.66 |
April | 0.383486E+09 | 0.48 | 830.82 | 01-APR-08:51 | 0.66 |
May | 0.689392E+09 | 0.53 | 830.82 | 01-MAY-08:51 | 0.67 |
June | 0.903154E+09 | 0.57 | 830.82 | 01-JUN-08:31 | 0.66 |
July | 0.867999E+09 | 0.56 | 830.82 | 01-JUL-08:62 | 0.66 |
August | 0.752520E+09 | 0.54 | 830.82 | 01-AUG-07:51 | 0.66 |
September | 0.591422E+09 | 0.50 | 830.82 | 01-SEP-08:51 | 0.65 |
October | 0.290396E+09 | 0.42 | 830.82 | 01-OCT-08:51 | 0.66 |
November | 0.179243E+09 | 0.45 | 830.82 | 02-NOV-15:02 | 0.66 |
December | 0.294098E+09 | 0.47 | 830.82 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.554934E+10 | 0.49 | |||
Minimum of Months | 0.165630E+09 | 0.42 | 830.82 | 0.65 | |
Maximum of Months | 0.903154E+09 | 0.57 | 830.82 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100932E+10 | 0.32 | 2415.34 | 12-JAN-14:25 | 0.66 |
February | 0.105157E+10 | 0.38 | 2332.73 | 07-FEB-13:40 | 0.67 |
March | 0.103980E+10 | 0.39 | 1373.30 | 16-MAR-12:50 | 0.67 |
April | 0.156577E+10 | 0.55 | 1370.39 | 19-APR-20:10 | 0.66 |
May | 0.195037E+10 | 0.64 | 1467.54 | 31-MAY-20:20 | 0.66 |
June | 0.231913E+10 | 0.66 | 1577.77 | 07-JUN-17:15 | 0.66 |
July | 0.230654E+10 | 0.66 | 1411.24 | 02-JUL-20:50 | 0.66 |
August | 0.239950E+10 | 0.66 | 1576.29 | 27-AUG-13:50 | 0.66 |
September | 0.262749E+10 | 0.66 | 2863.70 | 30-SEP-13:20 | 0.66 |
October | 0.250821E+10 | 0.60 | 3237.98 | 22-OCT-13:15 | 0.66 |
November | 0.166132E+10 | 0.42 | 3106.78 | 10-NOV-12:00 | 0.66 |
December | 0.838050E+09 | 0.30 | 1489.75 | 16-DEC-13:40 | 0.67 |
Annual Sum or Average | 0.212771E+11 | 0.52 | |||
Minimum of Months | 0.838050E+09 | 0.30 | 1370.39 | 0.66 | |
Maximum of Months | 0.262749E+10 | 0.66 | 3237.98 | 0.67 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105205E+10 | 0.46 | 5370.65 | 01-JAN-09:02 | 0.66 |
February | 0.930475E+09 | 0.42 | 5370.65 | 01-FEB-16:02 | 0.67 |
March | 0.114454E+10 | 0.39 | 5370.65 | 03-MAR-16:02 | 0.66 |
April | 0.252009E+10 | 0.42 | 5370.65 | 01-APR-08:51 | 0.67 |
May | 0.430887E+10 | 0.47 | 5370.65 | 01-MAY-08:51 | 0.67 |
June | 0.571979E+10 | 0.54 | 5370.65 | 01-JUN-08:31 | 0.66 |
July | 0.568254E+10 | 0.53 | 5370.65 | 01-JUL-08:62 | 0.66 |
August | 0.477791E+10 | 0.49 | 5370.65 | 01-AUG-07:51 | 0.66 |
September | 0.346133E+10 | 0.44 | 5370.65 | 01-SEP-08:51 | 0.66 |
October | 0.207716E+10 | 0.36 | 5370.65 | 01-OCT-08:51 | 0.66 |
November | 0.983179E+09 | 0.42 | 5370.65 | 01-NOV-08:62 | 0.66 |
December | 0.123386E+10 | 0.46 | 5370.65 | 01-DEC-19:02 | 0.66 |
Annual Sum or Average | 0.338918E+11 | 0.45 | |||
Minimum of Months | 0.930475E+09 | 0.36 | 5370.65 | 0.66 | |
Maximum of Months | 0.571979E+10 | 0.54 | 5370.65 | 0.67 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217861E+09 | 0.49 | 736.16 | 01-JAN-09:02 | 0.66 |
February | 0.218221E+09 | 0.53 | 736.16 | 01-FEB-09:02 | 0.66 |
March | 0.278388E+09 | 0.57 | 736.16 | 01-MAR-09:02 | 0.66 |
April | 0.524897E+09 | 0.63 | 736.16 | 01-APR-08:62 | 0.66 |
May | 0.769500E+09 | 0.65 | 736.16 | 01-MAY-08:62 | 0.67 |
June | 0.973627E+09 | 0.65 | 736.16 | 01-JUN-08:62 | 0.66 |
July | 0.949248E+09 | 0.65 | 736.16 | 01-JUL-08:62 | 0.66 |
August | 0.875828E+09 | 0.64 | 736.16 | 01-AUG-08:62 | 0.66 |
September | 0.779205E+09 | 0.64 | 736.16 | 01-SEP-08:62 | 0.66 |
October | 0.506868E+09 | 0.61 | 736.16 | 01-OCT-08:62 | 0.66 |
November | 0.279358E+09 | 0.57 | 736.16 | 02-NOV-15:02 | 0.66 |
December | 0.228380E+09 | 0.48 | 736.16 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.660138E+10 | 0.59 | |||
Minimum of Months | 0.217861E+09 | 0.48 | 736.16 | 0.66 | |
Maximum of Months | 0.973627E+09 | 0.65 | 736.16 | 0.67 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.228777E+09 | 0.46 | 730.56 | 02-JAN-09:02 | 0.66 |
February | 0.164422E+09 | 0.43 | 730.56 | 01-FEB-16:02 | 0.67 |
March | 0.172062E+09 | 0.42 | 730.56 | 01-MAR-09:02 | 0.66 |
April | 0.400092E+09 | 0.51 | 730.56 | 01-APR-08:51 | 0.66 |
May | 0.675277E+09 | 0.55 | 730.56 | 01-MAY-08:51 | 0.67 |
June | 0.918189E+09 | 0.58 | 730.56 | 01-JUN-08:12 | 0.66 |
July | 0.884353E+09 | 0.57 | 730.56 | 01-JUL-08:62 | 0.66 |
August | 0.756171E+09 | 0.55 | 730.56 | 01-AUG-07:51 | 0.66 |
September | 0.563055E+09 | 0.51 | 730.56 | 01-SEP-08:51 | 0.65 |
October | 0.275042E+09 | 0.45 | 730.56 | 01-OCT-08:51 | 0.66 |
November | 0.168971E+09 | 0.42 | 730.56 | 02-NOV-15:02 | 0.66 |
December | 0.264340E+09 | 0.47 | 730.56 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.547075E+10 | 0.49 | |||
Minimum of Months | 0.164422E+09 | 0.42 | 730.56 | 0.65 | |
Maximum of Months | 0.918189E+09 | 0.58 | 730.56 | 0.67 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 73450253.84 | 0.50 | 221.94 | 01-JAN-16:02 | 0.66 |
February | 65745537.09 | 0.52 | 221.94 | 01-FEB-09:02 | 0.66 |
March | 78286057.45 | 0.54 | 221.94 | 01-MAR-09:02 | 0.66 |
April | 0.128653E+09 | 0.59 | 221.94 | 01-APR-15:02 | 0.66 |
May | 0.190455E+09 | 0.62 | 221.94 | 01-MAY-15:02 | 0.66 |
June | 0.239432E+09 | 0.64 | 221.94 | 01-JUN-08:62 | 0.66 |
July | 0.232838E+09 | 0.63 | 221.94 | 01-JUL-08:62 | 0.66 |
August | 0.213196E+09 | 0.63 | 221.94 | 01-AUG-08:62 | 0.66 |
September | 0.190307E+09 | 0.63 | 221.94 | 01-SEP-08:62 | 0.66 |
October | 0.127797E+09 | 0.59 | 221.94 | 01-OCT-08:62 | 0.66 |
November | 76349966.48 | 0.55 | 221.94 | 02-NOV-15:02 | 0.66 |
December | 78644503.99 | 0.50 | 221.94 | 01-DEC-16:02 | 0.66 |
Annual Sum or Average | 0.169516E+10 | 0.58 | |||
Minimum of Months | 65745537.09 | 0.50 | 221.94 | 0.66 | |
Maximum of Months | 0.239432E+09 | 0.64 | 221.94 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 81761717.61 | 0.47 | 220.22 | 01-JAN-09:02 | 0.66 |
February | 57953771.83 | 0.44 | 220.22 | 01-FEB-09:02 | 0.66 |
March | 49328413.38 | 0.42 | 220.22 | 01-MAR-09:02 | 0.66 |
April | 98745983.72 | 0.48 | 220.22 | 01-APR-15:02 | 0.66 |
May | 0.176918E+09 | 0.53 | 220.22 | 01-MAY-08:51 | 0.67 |
June | 0.236709E+09 | 0.57 | 220.22 | 01-JUN-08:31 | 0.66 |
July | 0.226895E+09 | 0.56 | 220.22 | 01-JUL-08:62 | 0.66 |
August | 0.194875E+09 | 0.54 | 220.22 | 01-AUG-07:51 | 0.66 |
September | 0.149914E+09 | 0.50 | 220.22 | 01-SEP-08:51 | 0.65 |
October | 67577890.43 | 0.42 | 220.22 | 01-OCT-08:51 | 0.66 |
November | 57030737.30 | 0.45 | 220.22 | 02-NOV-08:62 | 0.66 |
December | 94463054.59 | 0.48 | 220.22 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.149217E+10 | 0.49 | |||
Minimum of Months | 49328413.38 | 0.42 | 220.22 | 0.65 | |
Maximum of Months | 0.236709E+09 | 0.57 | 220.22 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.502277E+09 | 0.57 | 992.00 | 01-JAN-09:02 | 0.66 |
February | 0.450018E+09 | 0.58 | 992.00 | 01-FEB-16:02 | 0.66 |
March | 0.439631E+09 | 0.58 | 992.00 | 01-MAR-16:02 | 0.66 |
April | 0.613236E+09 | 0.60 | 992.00 | 01-APR-08:62 | 0.66 |
May | 0.817013E+09 | 0.62 | 992.00 | 01-MAY-15:02 | 0.66 |
June | 0.102355E+10 | 0.63 | 992.00 | 01-JUN-08:62 | 0.66 |
July | 0.104417E+10 | 0.63 | 992.00 | 01-JUL-08:62 | 0.66 |
August | 0.103869E+10 | 0.62 | 992.00 | 01-AUG-08:62 | 0.66 |
September | 0.106887E+10 | 0.63 | 992.00 | 01-SEP-08:62 | 0.66 |
October | 0.941839E+09 | 0.61 | 992.00 | 01-OCT-08:62 | 0.66 |
November | 0.652422E+09 | 0.59 | 992.00 | 01-NOV-15:02 | 0.66 |
December | 0.476877E+09 | 0.57 | 992.00 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.906859E+10 | 0.60 | |||
Minimum of Months | 0.439631E+09 | 0.57 | 992.00 | 0.66 | |
Maximum of Months | 0.106887E+10 | 0.63 | 992.00 | 0.66 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.907593E+09 | 0.816833E+09 | 774.02 | 29-JAN-06:03 | 696.62 | 696.62 | 39.06 | 1.58 |
February | 0.582314E+09 | 0.524082E+09 | 770.72 | 01-FEB-19:02 | 693.65 | 693.65 | 37.01 | 1.56 |
March | 0.471332E+09 | 0.424198E+09 | 769.47 | 24-MAR-08:04 | 692.52 | 692.52 | 38.26 | 1.55 |
April | 0.131837E+09 | 0.118653E+09 | 728.05 | 11-APR-08:05 | 655.25 | 655.25 | 36.45 | 1.33 |
May | 6092001.76 | 5482801.58 | 329.74 | 02-MAY-06:00 | 296.77 | 296.77 | 28.63 | 0.40 |
June | 46092.50 | 41483.25 | 84.55 | 29-JUN-08:05 | 76.10 | 76.10 | 30.38 | 0.09 |
July | 21187.62 | 19068.85 | 44.78 | 19-JUL-08:07 | 40.31 | 40.31 | 33.07 | 0.05 |
August | 62644.38 | 56379.94 | 92.74 | 14-AUG-08:06 | 83.47 | 83.47 | 34.78 | 0.10 |
September | 8343965.55 | 7509568.99 | 420.64 | 30-SEP-06:00 | 378.57 | 378.57 | 30.30 | 0.54 |
October | 82778387.76 | 74500548.99 | 689.01 | 25-OCT-06:10 | 620.10 | 620.10 | 36.34 | 1.18 |
November | 0.551816E+09 | 0.496634E+09 | 797.26 | 27-NOV-19:02 | 717.53 | 717.53 | 36.35 | 1.76 |
December | 0.849991E+09 | 0.764992E+09 | 808.59 | 28-DEC-19:02 | 727.73 | 727.73 | 36.86 | 1.86 |
Annual Sum or Average | 0.359223E+10 | 0.323300E+10 | ||||||
Minimum of Months | 21187.62 | 19068.85 | 44.78 | 40.31 | 40.31 | 28.63 | 0.05 | |
Maximum of Months | 0.907593E+09 | 0.816833E+09 | 808.59 | 727.73 | 727.73 | 39.06 | 1.86 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 21352012.37 | 19216811.14 | 221.64 | 03-JAN-16:02 | 199.47 | 199.47 | 6.72 | 6.87 |
February | 41778432.72 | 37600589.45 | 314.23 | 20-FEB-16:03 | 282.80 | 282.80 | 6.72 | 8.05 |
March | 68909382.06 | 62018443.86 | 325.88 | 14-MAR-15:02 | 293.29 | 293.29 | 6.72 | 8.19 |
April | 0.287047E+09 | 0.258343E+09 | 1123.32 | 28-APR-18:06 | 1010.99 | 1010.99 | 6.72 | 13.98 |
May | 0.627123E+09 | 0.564411E+09 | 1321.58 | 19-MAY-19:10 | 1189.43 | 1189.43 | 6.72 | 14.95 |
June | 0.971088E+09 | 0.873979E+09 | 1512.70 | 05-JUN-18:05 | 1361.43 | 1361.43 | 6.72 | 15.80 |
July | 0.114711E+10 | 0.103240E+10 | 1337.46 | 21-JUL-21:00 | 1203.71 | 1203.71 | 6.72 | 15.02 |
August | 0.100642E+10 | 0.905775E+09 | 1423.57 | 22-AUG-20:00 | 1281.21 | 1281.21 | 6.72 | 15.42 |
September | 0.790134E+09 | 0.711120E+09 | 1249.19 | 17-SEP-18:04 | 1124.27 | 1124.27 | 6.72 | 14.61 |
October | 0.342040E+09 | 0.307836E+09 | 1214.35 | 01-OCT-19:10 | 1092.92 | 1092.92 | 6.72 | 14.44 |
November | 67711674.52 | 60940507.06 | 650.90 | 03-NOV-15:02 | 585.81 | 585.81 | 6.72 | 11.10 |
December | 15186167.97 | 13667551.17 | 135.61 | 09-DEC-16:02 | 122.05 | 122.05 | 6.72 | 5.45 |
Annual Sum or Average | 0.538589E+10 | 0.484731E+10 | ||||||
Minimum of Months | 15186167.97 | 13667551.17 | 135.61 | 122.05 | 122.05 | 6.72 | 5.45 | |
Maximum of Months | 0.114711E+10 | 0.103240E+10 | 1512.70 | 1361.43 | 1361.43 | 6.72 | 15.80 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.483578E+10 | 0.435220E+10 | 2562.44 | 01-JAN-00:10 | 2306.19 | 2306.19 | 6.73 | 22.67 |
February | 0.499534E+10 | 0.449581E+10 | 2562.44 | 01-FEB-01:40 | 2306.19 | 2306.19 | 6.72 | 22.67 |
March | 0.615948E+10 | 0.554353E+10 | 2562.44 | 01-MAR-00:10 | 2306.19 | 2306.19 | 6.74 | 22.67 |
April | 0.658810E+10 | 0.592929E+10 | 2562.44 | 01-APR-00:10 | 2306.19 | 2306.19 | 6.78 | 22.67 |
May | 0.686323E+10 | 0.617690E+10 | 2562.44 | 01-MAY-00:05 | 2306.19 | 2306.19 | 8.19 | 22.67 |
June | 0.664183E+10 | 0.597765E+10 | 2562.44 | 01-JUN-00:05 | 2306.19 | 2306.19 | 9.17 | 22.67 |
July | 0.686323E+10 | 0.617690E+10 | 2562.44 | 01-JUL-00:10 | 2306.19 | 2306.19 | 9.28 | 22.67 |
August | 0.686323E+10 | 0.617690E+10 | 2562.44 | 01-AUG-00:05 | 2306.19 | 2306.19 | 9.76 | 22.67 |
September | 0.664183E+10 | 0.597765E+10 | 2562.44 | 01-SEP-00:05 | 2306.19 | 2306.19 | 8.87 | 22.67 |
October | 0.686323E+10 | 0.617690E+10 | 2562.44 | 01-OCT-00:10 | 2306.19 | 2306.19 | 7.37 | 22.67 |
November | 0.542811E+10 | 0.488530E+10 | 2562.44 | 01-NOV-00:05 | 2306.19 | 2306.19 | 6.89 | 22.67 |
December | 0.471065E+10 | 0.423959E+10 | 2562.44 | 01-DEC-00:10 | 2306.19 | 2306.19 | 6.73 | 22.67 |
Annual Sum or Average | 0.734540E+11 | 0.661086E+11 | ||||||
Minimum of Months | 0.471065E+10 | 0.423959E+10 | 2562.44 | 2306.19 | 2306.19 | 6.72 | 22.67 | |
Maximum of Months | 0.686323E+10 | 0.617690E+10 | 2562.44 | 2306.19 | 2306.19 | 9.76 | 22.67 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.45 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.16 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.00 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.42 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.21 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.30 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.92 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.13 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.51 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.32 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.44 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 50.26 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.45 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.13 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 35.14 | 60.00 | 48159.68 | 159844.92 | 14-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35.37 | 60.00 | 33511.04 | 150227.99 | 01-FEB-19:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 34.26 | 60.00 | 25431.53 | 141271.67 | 24-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.54 | 60.00 | 7842.09 | 131357.37 | 11-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25.50 | 25.50 | 347.57 | 52189.17 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 27.26 | 27.26 | 2.35 | 11060.13 | 29-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.93 | 31.93 | 0.92 | 5226.13 | 19-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.99 | 33.99 | 2.42 | 10355.23 | 14-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 38.11 | 38.11 | 502.88 | 67087.26 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.46 | 26.46 | 4747.83 | 120641.91 | 25-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.49 | 60.00 | 30440.61 | 173770.29 | 27-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.58 | 60.00 | 42097.99 | 179898.32 | 28-DEC-19:02 |
Annual Sum or Average | 0.00 | 16017.46 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.49 | 25.50 | 0.92 | 5226.13 | ||
Maximum of Months | 0.00 | 0.00 | 38.11 | 60.00 | 48159.68 | 179898.32 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14000.04 | 225072.62 | 03-JAN-16:02 | 9.07 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29305.77 | 306023.74 | 22-FEB-16:01 | 9.92 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43431.41 | 310229.49 | 14-MAR-15:02 | 9.97 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 121732.91 | 399745.33 | 28-APR-18:04 | 10.91 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 190168.63 | 416939.90 | 12-MAY-18:06 | 11.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 253702.60 | 465934.34 | 19-JUN-18:51 | 11.61 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 312416.49 | 616880.70 | 20-JUL-21:52 | 13.20 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 260858.06 | 605691.15 | 01-AUG-21:51 | 13.08 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 225730.99 | 460493.02 | 03-SEP-21:51 | 11.55 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 119893.07 | 479056.27 | 03-OCT-19:30 | 11.75 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 37695.31 | 302092.14 | 08-NOV-16:02 | 9.88 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 10873.40 | 160772.12 | 10-DEC-16:02 | 8.39 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 135581.62 | 0.00 | ||||||
Minimum of Months | 10873.40 | 160772.12 | 8.39 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 312416.49 | 616880.70 | 13.20 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.45 | 59.47 | 25475.11 | 51764.58 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.16 | 59.37 | 25455.69 | 51745.20 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.00 | 58.77 | 24601.43 | 50760.20 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.42 | 58.66 | 23055.09 | 47881.87 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.21 | 59.36 | 21280.55 | 44485.00 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.30 | 58.60 | 19743.88 | 40790.73 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.92 | 58.78 | 18838.89 | 38050.38 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.13 | 59.02 | 18863.67 | 38280.86 | 31-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.51 | 58.42 | 19756.97 | 40875.49 | 29-SEP-06:24 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.32 | 59.57 | 21296.52 | 44584.06 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.44 | 58.19 | 23073.62 | 48126.50 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.26 | 58.41 | 24599.36 | 50697.14 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 22151.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.45 | 58.19 | 18838.89 | 38050.38 | ||
Maximum of Months | 0.00 | 0.00 | 54.13 | 59.57 | 25475.11 | 51764.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.112719E+12 | 0.00 | 0.634906E+10 | 0.332594E+11 | 0.00 | 0.00 |
February | 0.715119E+11 | 0.00 | 0.327740E+11 | 0.303257E+11 | 0.00 | 0.00 |
March | 0.636524E+11 | 0.00 | 0.669580E+11 | 0.343761E+11 | 0.00 | 0.00 |
April | 0.200155E+11 | 0.00 | 0.210536E+12 | 0.362282E+11 | 0.00 | 0.00 |
May | 0.917604E+09 | 0.00 | 0.349646E+12 | 0.402475E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.452127E+12 | 0.424183E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.604956E+12 | 0.440025E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.491102E+12 | 0.449200E+11 | 0.00 | 0.00 |
September | 0.131520E+10 | 0.00 | 0.400819E+12 | 0.431926E+11 | 0.00 | 0.00 |
October | 0.126269E+11 | 0.00 | 0.197980E+12 | 0.413824E+11 | 0.00 | 0.00 |
November | 0.715983E+11 | 0.00 | 0.407680E+11 | 0.358806E+11 | 0.00 | 0.00 |
December | 0.902670E+11 | 0.00 | 0.370344E+10 | 0.337042E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.444624E+12 | 0.00 | 0.285772E+13 | 0.459937E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.370344E+10 | 0.303257E+11 | 0.00 | 0.00 |
Maximum of Months | 0.112719E+12 | 0.00 | 0.604956E+12 | 0.449200E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 28357528.95 | 0.00 | 0.424271E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 49689209.94 | 0.00 | 0.213329E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 15177635.67 | 0.00 | 0.440325E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 24546.10 | 0.00 | 0.144427E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 33999.62 | 0.00 | 0.238606E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 22212.33 | 0.00 | 0.297804E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 21539.25 | 0.00 | 0.421110E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 19041.10 | 0.00 | 0.344471E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 21356.19 | 0.00 | 0.289207E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 19398.24 | 0.00 | 0.137054E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 6591.78 | 0.00 | 0.268538E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 91442290.30 | 0.00 | 0.217498E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.184835E+09 | 0.00 | 0.197132E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 6591.78 | 0.00 | 0.217498E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 91442290.30 | 0.00 | 0.421110E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.332594E+11 | 0.634906E+10 | 0.112719E+12 | 0.125304E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303257E+11 | 0.327740E+11 | 0.715119E+11 | 0.932051E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343761E+11 | 0.669580E+11 | 0.636524E+11 | 0.559534E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362282E+11 | 0.210536E+12 | 0.200155E+11 | 0.108464E+11 | 0.440139E+10 | 0.00 | 0.00 | 0.00 |
May | 0.402475E+11 | 0.349646E+12 | 0.917604E+09 | 0.184005E+11 | 0.190162E+11 | 0.00 | 0.00 | 0.00 |
June | 0.424183E+11 | 0.452127E+12 | 0.00 | 0.240418E+11 | 0.440209E+11 | 0.00 | 0.00 | 0.00 |
July | 0.440025E+11 | 0.604956E+12 | 0.00 | 0.945781E+10 | 0.751711E+11 | 0.00 | 0.00 | 0.00 |
August | 0.449200E+11 | 0.491102E+12 | 0.00 | 0.113637E+11 | 0.365082E+11 | 0.00 | 0.00 | 0.00 |
September | 0.431926E+11 | 0.400819E+12 | 0.131520E+10 | 0.684502E+10 | 0.210052E+11 | 0.00 | 0.00 | 0.00 |
October | 0.413824E+11 | 0.197980E+12 | 0.126269E+11 | 0.494466E+10 | 0.383153E+10 | 0.00 | 0.00 | 0.00 |
November | 0.358806E+11 | 0.407680E+11 | 0.715983E+11 | 0.730871E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337042E+11 | 0.370344E+10 | 0.902670E+11 | 0.219384E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459937E+12 | 0.285772E+13 | 0.444624E+12 | 0.652834E+12 | 0.203955E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303257E+11 | 0.370344E+10 | 0.00 | 0.494466E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449200E+11 | 0.604956E+12 | 0.112719E+12 | 0.219384E+12 | 0.751711E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.424271E+09 | 28357528.95 | 0.261147E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.213329E+10 | 49689209.94 | 0.186652E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.440325E+10 | 15177635.67 | 0.149152E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.144427E+11 | 24546.10 | 0.463563E+10 | 0.415965E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.238606E+11 | 33999.62 | 0.190152E+10 | 0.241445E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.297804E+11 | 22212.33 | 0.710144E+09 | 0.583193E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.421110E+11 | 21539.25 | 597262.92 | 0.161852E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.344471E+11 | 19041.10 | 0.175363E+09 | 0.900863E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.289207E+11 | 21356.19 | 0.818347E+09 | 0.467089E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.137054E+11 | 19398.24 | 0.332330E+10 | 0.991096E+09 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.268538E+10 | 6591.78 | 0.173568E+11 | 5839808.45 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.217498E+09 | 91442290.30 | 0.305752E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.197132E+12 | 0.184835E+09 | 0.119192E+12 | 0.395240E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.217498E+09 | 6591.78 | 597262.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.421110E+11 | 91442290.30 | 0.305752E+11 | 0.161852E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.332594E+11 | 0.112719E+12 | 0.634906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303257E+11 | 0.715119E+11 | 0.327740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343761E+11 | 0.636524E+11 | 0.669580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362282E+11 | 0.200155E+11 | 0.210536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.402475E+11 | 0.917604E+09 | 0.349646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.424183E+11 | 0.00 | 0.452127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.440025E+11 | 0.00 | 0.604956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.449200E+11 | 0.00 | 0.491102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431926E+11 | 0.131520E+10 | 0.400819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.413824E+11 | 0.126269E+11 | 0.197980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358806E+11 | 0.715983E+11 | 0.407680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337042E+11 | 0.902670E+11 | 0.370344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459937E+12 | 0.444624E+12 | 0.285772E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303257E+11 | 0.00 | 0.370344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449200E+11 | 0.112719E+12 | 0.604956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 28357528.95 | 0.424271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 49689209.94 | 0.213329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 15177635.67 | 0.440325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 24546.10 | 0.144427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 33999.62 | 0.238606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 22212.33 | 0.297804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 21539.25 | 0.421110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 19041.10 | 0.344471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 21356.19 | 0.289207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 19398.24 | 0.137054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 6591.78 | 0.268538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 91442290.30 | 0.217498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.184835E+09 | 0.197132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 6591.78 | 0.217498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 91442290.30 | 0.421110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132959E+11 | 0.00 | 0.00 | 33623482.72 | 0.00 | 0.00 | 0.440453E+11 | 0.00 | 1.00 |
February | 0.400851E+11 | 0.00 | 0.00 | 1641406.22 | 0.00 | 0.00 | 0.408347E+10 | 0.00 | 0.96 |
March | 0.445066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
April | 0.272061E+11 | 0.00 | 0.00 | 0.00 | 97240817.54 | 0.00 | 0.00 | 0.00 | 0.96 |
May | 0.159480E+11 | 0.00 | 0.00 | 0.00 | 0.545427E+09 | 0.00 | 0.00 | 0.00 | 0.94 |
June | 0.796686E+10 | 4146754.77 | 0.00 | 706241.51 | 0.155753E+10 | 0.00 | 0.288764E+09 | 0.00 | 0.85 |
July | 0.206517E+09 | 0.457106E+10 | 0.00 | 16680180.69 | 0.269809E+10 | 0.00 | 0.199954E+10 | 0.00 | 0.87 |
August | 11254753.41 | 0.198423E+10 | 0.00 | 59521799.06 | 0.139017E+09 | 0.00 | 0.880087E+10 | 0.00 | 1.02 |
September | 25265.49 | 0.143263E+10 | 0.00 | 85808037.55 | 4294360.20 | 0.00 | 0.179012E+11 | 0.00 | 1.23 |
October | 0.00 | 0.237069E+09 | 0.00 | 0.102827E+09 | 0.00 | 0.00 | 0.416746E+11 | 0.00 | 1.27 |
November | 0.00 | 0.00 | 0.00 | 91695573.30 | 0.00 | 0.00 | 0.612411E+11 | 0.00 | 1.22 |
December | 0.353805E+09 | 0.00 | 0.00 | 73937631.75 | 0.00 | 0.00 | 0.613265E+11 | 0.00 | 1.12 |
Annual Sum or Average | 0.149580E+12 | 0.822913E+10 | 0.00 | 0.466441E+09 | 0.504159E+10 | 0.00 | 0.241361E+12 | 0.00 | 1.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.445066E+11 | 0.457106E+10 | 0.00 | 0.102827E+09 | 0.269809E+10 | 0.00 | 0.613265E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.575310E+10 | 0.00 | 0.00 | 1607753.61 | 0.00 | 62280966.98 | 0.125337E+10 | 0.00 | 2.25 |
February | 0.469392E+10 | 0.00 | 0.00 | 1703473.10 | 0.00 | 40456568.29 | 0.911970E+09 | 0.00 | 2.27 |
March | 0.500632E+10 | 0.00 | 0.00 | 1175208.59 | 0.00 | 44458979.00 | 0.566321E+09 | 0.00 | 2.22 |
April | 0.288110E+10 | 14576733.36 | 0.00 | 2218675.13 | 70665.32 | 0.00 | 0.544100E+09 | 0.00 | 2.23 |
May | 0.136597E+10 | 73585077.35 | 0.00 | 2888058.97 | 2335528.91 | 0.00 | 0.649658E+09 | 0.00 | 2.20 |
June | 0.364927E+09 | 0.239960E+09 | 0.00 | 3551854.36 | 1481165.77 | 0.00 | 0.692696E+09 | 0.00 | 2.12 |
July | 61334645.67 | 0.804856E+09 | 0.00 | 1725183.79 | 0.151096E+09 | 0.00 | 0.218248E+09 | 0.00 | 2.11 |
August | 0.383347E+09 | 0.270522E+09 | 0.00 | 3996532.51 | 21843702.18 | 0.00 | 0.557912E+09 | 0.00 | 2.26 |
September | 0.798213E+09 | 0.201295E+09 | 0.00 | 5554509.11 | 7599494.06 | 0.00 | 0.865712E+09 | 0.00 | 2.54 |
October | 0.250506E+10 | 37273934.88 | 0.00 | 6162690.71 | 637632.43 | 0.00 | 0.151073E+10 | 0.00 | 2.56 |
November | 0.448794E+10 | 0.00 | 0.00 | 3687097.72 | 0.00 | 51179483.09 | 0.170520E+10 | 0.00 | 2.42 |
December | 0.519335E+10 | 0.00 | 0.00 | 1261748.68 | 0.00 | 0.337650E+09 | 0.116523E+10 | 0.00 | 2.23 |
Annual Sum or Average | 0.334946E+11 | 0.164207E+10 | 0.00 | 35532786.28 | 0.185064E+09 | 0.536026E+09 | 0.106411E+11 | 0.00 | 2.29 |
Minimum of Months | 61334645.67 | 0.00 | 0.00 | 1175208.59 | 0.00 | 0.00 | 0.218248E+09 | 0.00 | 2.11 |
Maximum of Months | 0.575310E+10 | 0.804856E+09 | 0.00 | 6162690.71 | 0.151096E+09 | 0.337650E+09 | 0.170520E+10 | 0.00 | 2.56 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412227E+10 | 0.00 | 0.00 | 475365.97 | 0.00 | 0.00 | 0.977806E+09 | 0.00 | 1.39 |
February | 0.302181E+10 | 0.00 | 0.00 | 653295.54 | 0.00 | 0.00 | 0.109129E+10 | 0.00 | 1.40 |
March | 0.270652E+10 | 0.00 | 0.00 | 1061299.18 | 0.00 | 0.00 | 0.145897E+10 | 0.00 | 1.42 |
April | 0.825623E+09 | 3509696.16 | 0.00 | 3058698.97 | 5516535.02 | 0.00 | 0.180253E+10 | 0.00 | 1.48 |
May | 0.142100E+09 | 38704017.25 | 0.00 | 5109354.63 | 11990937.02 | 0.00 | 0.150235E+10 | 0.00 | 1.53 |
June | 12990035.83 | 0.144135E+09 | 0.00 | 5440340.93 | 6901887.69 | 0.00 | 0.911796E+09 | 0.00 | 1.46 |
July | 352334.57 | 0.677456E+09 | 0.00 | 2790276.00 | 53383383.75 | 0.00 | 0.249139E+09 | 0.00 | 1.44 |
August | 28532514.98 | 0.187047E+09 | 0.00 | 5086989.41 | 13898019.63 | 0.00 | 0.772967E+09 | 0.00 | 1.51 |
September | 34856153.05 | 0.115601E+09 | 0.00 | 5708402.32 | 10524969.64 | 0.00 | 0.136081E+10 | 0.00 | 1.61 |
October | 0.575557E+09 | 19058587.23 | 0.00 | 4157745.11 | 1682718.73 | 0.00 | 0.247044E+10 | 0.00 | 1.53 |
November | 0.247945E+10 | 0.00 | 0.00 | 1429635.83 | 0.00 | 0.00 | 0.194989E+10 | 0.00 | 1.42 |
December | 0.414012E+10 | 0.00 | 0.00 | 290993.89 | 0.00 | 0.00 | 0.712341E+09 | 0.00 | 1.39 |
Annual Sum or Average | 0.180902E+11 | 0.118551E+10 | 0.00 | 35262397.77 | 0.103898E+09 | 0.00 | 0.152603E+11 | 0.00 | 1.47 |
Minimum of Months | 352334.57 | 0.00 | 0.00 | 290993.89 | 0.00 | 0.00 | 0.249139E+09 | 0.00 | 1.39 |
Maximum of Months | 0.414012E+10 | 0.677456E+09 | 0.00 | 5708402.32 | 53383383.75 | 0.00 | 0.247044E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
February | 0.361882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 0.364910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.220088E+10 | 0.00 | 0.00 | 49695.72 | 7972787.11 | 0.00 | 29747833.76 | 0.00 | 0.58 |
May | 0.911207E+09 | 10219746.53 | 0.00 | 1401000.23 | 34504214.83 | 0.00 | 0.416972E+09 | 0.00 | 0.59 |
June | 73283618.67 | 0.130030E+09 | 0.00 | 4090943.24 | 6101574.51 | 0.00 | 0.669148E+09 | 0.00 | 0.58 |
July | 3709152.11 | 0.524469E+09 | 0.00 | 2216371.57 | 98923153.00 | 0.00 | 0.198243E+09 | 0.00 | 0.58 |
August | 0.150777E+09 | 0.155439E+09 | 0.00 | 3080704.72 | 16615264.93 | 0.00 | 0.483479E+09 | 0.00 | 0.58 |
September | 0.568319E+09 | 49267363.46 | 0.00 | 1676440.19 | 56423406.90 | 0.00 | 0.504529E+09 | 0.00 | 0.59 |
October | 0.238808E+10 | 6040736.29 | 0.00 | 255407.61 | 10991644.43 | 0.00 | 0.123211E+09 | 0.00 | 0.59 |
November | 0.384058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 0.428631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.261893E+11 | 0.875466E+09 | 0.00 | 12770563.28 | 0.231532E+09 | 0.00 | 0.242533E+10 | 0.00 | 0.58 |
Minimum of Months | 3709152.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.449821E+10 | 0.524469E+09 | 0.00 | 4090943.24 | 98923153.00 | 0.00 | 0.669148E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 0.214654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.216450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.132312E+10 | 0.00 | 0.00 | 0.00 | 4729130.75 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.686690E+09 | 1708636.35 | 0.00 | 229281.96 | 24817230.94 | 0.00 | 89263308.51 | 0.00 | 0.59 |
June | 0.122369E+09 | 69538805.42 | 0.00 | 1443741.20 | 8529207.64 | 0.00 | 0.289749E+09 | 0.00 | 0.56 |
July | 13170922.37 | 0.228216E+09 | 0.00 | 938603.63 | 0.119146E+09 | 0.00 | 96374968.15 | 0.00 | 0.55 |
August | 0.184706E+09 | 71970516.12 | 0.00 | 936402.04 | 24118878.36 | 0.00 | 0.176543E+09 | 0.00 | 0.57 |
September | 0.536667E+09 | 16861523.11 | 0.00 | 284889.90 | 44627103.29 | 0.00 | 88068002.47 | 0.00 | 0.59 |
October | 0.147525E+10 | 1640586.14 | 0.00 | 34290.60 | 7902441.32 | 0.00 | 12588175.69 | 0.00 | 0.60 |
November | 0.227807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.254246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.161417E+11 | 0.389936E+09 | 0.00 | 3867209.33 | 0.233870E+09 | 0.00 | 0.752586E+09 | 0.00 | 0.59 |
Minimum of Months | 13170922.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.266816E+10 | 0.228216E+09 | 0.00 | 1443741.20 | 0.119146E+09 | 0.00 | 0.289749E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49127881.93 | 0.00 | 0.00 | 0.100426E+09 | 0.00 | 0.00 | 0.878712E+11 | 0.00 | 23.66 |
February | 53619243.40 | 0.00 | 0.00 | 92948520.95 | 0.00 | 0.00 | 0.710974E+11 | 0.00 | 23.91 |
March | 12168687.66 | 0.00 | 0.00 | 0.110634E+09 | 0.00 | 0.00 | 0.719490E+11 | 0.00 | 24.21 |
April | 0.00 | 0.126783E+09 | 0.00 | 0.122507E+09 | 0.00 | 0.00 | 0.431675E+11 | 0.00 | 24.10 |
May | 0.00 | 0.717404E+09 | 0.00 | 0.120950E+09 | 0.00 | 0.00 | 0.249552E+11 | 0.00 | 23.43 |
June | 0.00 | 0.220362E+10 | 0.00 | 88268568.76 | 0.00 | 0.00 | 0.123858E+11 | 0.00 | 20.82 |
July | 0.00 | 0.110521E+11 | 0.00 | 34235844.67 | 0.00 | 0.00 | 0.316774E+10 | 0.00 | 20.49 |
August | 0.00 | 0.304663E+10 | 0.00 | 85073611.50 | 0.00 | 0.00 | 0.111275E+11 | 0.00 | 21.74 |
September | 0.00 | 0.187376E+10 | 0.00 | 99799034.03 | 0.00 | 0.00 | 0.203062E+11 | 0.00 | 23.57 |
October | 0.00 | 0.332939E+09 | 0.00 | 0.116149E+09 | 0.00 | 0.00 | 0.490917E+11 | 0.00 | 24.37 |
November | 13645197.00 | 0.00 | 0.00 | 0.103943E+09 | 0.00 | 0.00 | 0.758332E+11 | 0.00 | 23.84 |
December | 90816552.35 | 0.00 | 0.00 | 99526866.34 | 0.00 | 0.00 | 0.835924E+11 | 0.00 | 23.70 |
Annual Sum or Average | 0.219378E+09 | 0.193532E+11 | 0.00 | 0.117446E+10 | 0.00 | 0.00 | 0.554545E+12 | 0.00 | 23.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34235844.67 | 0.00 | 0.00 | 0.316774E+10 | 0.00 | 20.49 |
Maximum of Months | 90816552.35 | 0.110521E+11 | 0.00 | 0.122507E+09 | 0.00 | 0.00 | 0.878712E+11 | 0.00 | 24.37 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.618373E+10 | 0.00 | 0.00 | 22483709.92 | 0.00 | 0.00 | 0.251062E+11 | 0.00 | 3.56 |
February | 0.399011E+10 | 0.00 | 0.00 | 23139864.30 | 0.00 | 0.00 | 0.210841E+11 | 0.00 | 3.60 |
March | 0.506100E+10 | 0.00 | 0.00 | 25096652.41 | 0.00 | 0.00 | 0.199370E+11 | 0.00 | 3.54 |
April | 0.225200E+10 | 59083788.53 | 0.00 | 31223979.29 | 113375.87 | 0.00 | 0.136796E+11 | 0.00 | 3.71 |
May | 0.781791E+09 | 0.297083E+09 | 0.00 | 31946851.98 | 8120889.30 | 0.00 | 0.922326E+10 | 0.00 | 3.74 |
June | 0.132764E+09 | 0.908793E+09 | 0.00 | 29232953.80 | 12588372.11 | 0.00 | 0.548705E+10 | 0.00 | 3.57 |
July | 7755585.46 | 0.407257E+10 | 0.00 | 15460676.72 | 0.240178E+09 | 0.00 | 0.153430E+10 | 0.00 | 3.54 |
August | 0.205699E+09 | 0.119090E+10 | 0.00 | 29851714.75 | 35256719.10 | 0.00 | 0.475116E+10 | 0.00 | 3.78 |
September | 0.199350E+09 | 0.821472E+09 | 0.00 | 37522603.75 | 16204736.74 | 0.00 | 0.829432E+10 | 0.00 | 4.16 |
October | 0.148181E+10 | 0.145991E+09 | 0.00 | 44351434.33 | 1636560.22 | 0.00 | 0.176055E+11 | 0.00 | 4.16 |
November | 0.357114E+10 | 0.00 | 0.00 | 33514487.25 | 0.00 | 0.00 | 0.244823E+11 | 0.00 | 3.84 |
December | 0.676883E+10 | 0.00 | 0.00 | 19152983.20 | 0.00 | 0.00 | 0.228032E+11 | 0.00 | 3.52 |
Annual Sum or Average | 0.306360E+11 | 0.749589E+10 | 0.00 | 0.342978E+09 | 0.314098E+09 | 0.00 | 0.173988E+12 | 0.00 | 3.73 |
Minimum of Months | 7755585.46 | 0.00 | 0.00 | 15460676.72 | 0.00 | 0.00 | 0.153430E+10 | 0.00 | 3.52 |
Maximum of Months | 0.676883E+10 | 0.407257E+10 | 0.00 | 44351434.33 | 0.240178E+09 | 0.00 | 0.251062E+11 | 0.00 | 4.16 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.398844E+11 | 0.00 | 0.00 | 42275533.42 | 0.00 | 0.00 | 0.649362E+11 | 0.00 | 1.70 |
February | 0.272327E+11 | 0.00 | 0.00 | 46200038.95 | 0.00 | 0.00 | 0.576508E+11 | 0.00 | 1.72 |
March | 0.265297E+11 | 0.00 | 0.00 | 56175133.87 | 0.00 | 0.00 | 0.599700E+11 | 0.00 | 1.74 |
April | 0.873704E+10 | 0.162371E+09 | 0.00 | 86913293.60 | 20105308.90 | 0.00 | 0.472977E+11 | 0.00 | 1.85 |
May | 0.222357E+10 | 0.858527E+09 | 0.00 | 0.111452E+09 | 0.165711E+09 | 0.00 | 0.336770E+11 | 0.00 | 1.90 |
June | 0.312891E+09 | 0.283735E+10 | 0.00 | 0.109053E+09 | 0.172429E+09 | 0.00 | 0.197897E+11 | 0.00 | 1.80 |
July | 4180000.62 | 0.139788E+11 | 0.00 | 57828159.00 | 0.103476E+10 | 0.00 | 0.547299E+10 | 0.00 | 1.78 |
August | 0.517442E+09 | 0.377587E+10 | 0.00 | 0.105914E+09 | 0.297972E+09 | 0.00 | 0.170723E+11 | 0.00 | 1.87 |
September | 0.435070E+09 | 0.238838E+10 | 0.00 | 0.123599E+09 | 0.179563E+09 | 0.00 | 0.298605E+11 | 0.00 | 2.00 |
October | 0.499354E+10 | 0.403158E+09 | 0.00 | 0.125515E+09 | 17522169.24 | 0.00 | 0.609716E+11 | 0.00 | 1.94 |
November | 0.153835E+11 | 0.00 | 0.00 | 79520428.67 | 0.00 | 0.00 | 0.777684E+11 | 0.00 | 1.77 |
December | 0.444091E+11 | 0.00 | 0.00 | 34593819.36 | 0.00 | 0.00 | 0.547042E+11 | 0.00 | 1.69 |
Annual Sum or Average | 0.170663E+12 | 0.244045E+11 | 0.00 | 0.979040E+09 | 0.188807E+10 | 0.00 | 0.529171E+12 | 0.00 | 1.81 |
Minimum of Months | 4180000.62 | 0.00 | 0.00 | 34593819.36 | 0.00 | 0.00 | 0.547299E+10 | 0.00 | 1.69 |
Maximum of Months | 0.444091E+11 | 0.139788E+11 | 0.00 | 0.125515E+09 | 0.103476E+10 | 0.00 | 0.777684E+11 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61389283.61 | 0.00 | 0.00 | 2968050.86 | 0.00 | 0.825354E+09 | 0.421180E+09 | 0.00 | 0.35 |
February | 42985758.06 | 0.00 | 0.00 | 4227842.89 | 0.00 | 0.543498E+09 | 0.526965E+09 | 0.00 | 0.35 |
March | 45332751.88 | 0.00 | 0.00 | 7690802.13 | 0.00 | 0.382814E+09 | 0.744376E+09 | 0.00 | 0.35 |
April | 14430916.68 | 3955357.81 | 0.00 | 14474912.48 | 0.00 | 45692019.31 | 0.734084E+09 | 0.00 | 0.35 |
May | 93327.85 | 26922110.54 | 0.00 | 14183375.01 | 0.00 | 552949.41 | 0.465476E+09 | 0.00 | 0.36 |
June | 0.00 | 59661947.94 | 0.00 | 10819448.48 | 0.00 | 27825.69 | 0.131772E+09 | 0.00 | 0.36 |
July | 0.00 | 0.504056E+09 | 0.00 | 527504.65 | 0.00 | 0.00 | 1268667.02 | 0.00 | 0.36 |
August | 0.00 | 0.222678E+09 | 0.00 | 5523669.21 | 0.00 | 127368.13 | 58455436.81 | 0.00 | 0.35 |
September | 0.00 | 0.215926E+09 | 0.00 | 9429949.07 | 0.00 | 172842.74 | 0.251024E+09 | 0.00 | 0.36 |
October | 7288347.96 | 29138639.92 | 0.00 | 13838692.06 | 2654.41 | 2209766.13 | 0.783822E+09 | 0.00 | 0.35 |
November | 20120409.57 | 103098.87 | 0.00 | 6774681.62 | 0.00 | 0.441072E+09 | 0.728630E+09 | 0.00 | 0.35 |
December | 66612389.04 | 0.00 | 0.00 | 2085408.04 | 0.00 | 0.905220E+09 | 0.342412E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.258253E+09 | 0.106244E+10 | 0.00 | 92544336.51 | 2654.41 | 0.314674E+10 | 0.518947E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 527504.65 | 0.00 | 0.00 | 1268667.02 | 0.00 | 0.35 |
Maximum of Months | 66612389.04 | 0.504056E+09 | 0.00 | 14474912.48 | 2654.41 | 0.905220E+09 | 0.783822E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92928075.20 | 0.00 | 0.00 | 946573.66 | 0.00 | 0.107641E+10 | 0.140453E+09 | 0.00 | 0.35 |
February | 0.134872E+09 | 0.00 | 0.00 | 1308916.15 | 0.00 | 0.746298E+09 | 0.235066E+09 | 0.00 | 0.35 |
March | 0.176754E+09 | 0.00 | 0.00 | 3296719.46 | 0.00 | 0.491222E+09 | 0.508803E+09 | 0.00 | 0.35 |
April | 0.139654E+09 | 3785947.70 | 0.00 | 11478790.16 | 168946.68 | 50495437.86 | 0.606959E+09 | 0.00 | 0.35 |
May | 91570117.80 | 25814460.05 | 2119.12 | 11769130.70 | 1101997.26 | 286219.86 | 0.376624E+09 | 379.79 | 0.36 |
June | 36730850.03 | 58347752.75 | 0.00 | 8455474.08 | 1307204.93 | 6758.45 | 97409848.75 | 0.00 | 0.36 |
July | 825054.35 | 0.433497E+09 | 0.00 | 408718.84 | 70500070.80 | 0.00 | 562188.04 | 0.00 | 0.36 |
August | 27819493.74 | 0.196708E+09 | 10194.46 | 4012239.68 | 25933735.34 | 8142.61 | 32259087.10 | 67.99 | 0.36 |
September | 82511030.90 | 0.188589E+09 | 10246.38 | 6578844.84 | 27301585.78 | 147502.06 | 0.171359E+09 | 386.07 | 0.36 |
October | 0.163976E+09 | 25973889.12 | 4603.97 | 7168268.45 | 3159130.22 | 7601238.67 | 0.628319E+09 | 256.69 | 0.36 |
November | 0.136152E+09 | 88827.60 | 0.00 | 2321882.06 | 14259.19 | 0.649736E+09 | 0.408246E+09 | 0.00 | 0.35 |
December | 90400706.96 | 0.00 | 0.00 | 515834.57 | 0.00 | 0.114322E+10 | 82040169.37 | 0.00 | 0.35 |
Annual Sum or Average | 0.117419E+10 | 0.932804E+09 | 27163.92 | 58261392.64 | 0.129487E+09 | 0.416543E+10 | 0.328810E+10 | 1090.55 | 0.35 |
Minimum of Months | 825054.35 | 0.00 | 0.00 | 408718.84 | 0.00 | 0.00 | 562188.04 | 0.00 | 0.35 |
Maximum of Months | 0.176754E+09 | 0.433497E+09 | 10246.38 | 11769130.70 | 70500070.80 | 0.114322E+10 | 0.628319E+09 | 386.07 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268795E+09 | 0.00 | 0.00 | 2990102.90 | 0.00 | 0.00 | 0.103724E+10 | 0.00 | 0.02 |
February | 0.191162E+09 | 0.00 | 0.00 | 2652264.99 | 0.00 | 0.00 | 0.854553E+09 | 0.00 | 0.02 |
March | 99278879.20 | 0.00 | 0.00 | 2637406.26 | 0.00 | 0.00 | 0.876661E+09 | 0.00 | 0.02 |
April | 13857447.20 | 7514647.98 | 0.00 | 2656443.36 | 0.00 | 0.00 | 0.384694E+09 | 0.00 | 0.02 |
May | 0.00 | 52202711.29 | 0.00 | 1412898.06 | 0.00 | 0.00 | 0.114002E+09 | 0.00 | 0.02 |
June | 0.00 | 70692478.90 | 0.00 | 1471130.14 | 0.00 | 0.00 | 41430802.58 | 0.00 | 0.02 |
July | 0.00 | 0.294892E+09 | 0.00 | 222940.87 | 0.00 | 0.00 | 6694014.93 | 0.00 | 0.02 |
August | 0.00 | 0.115234E+09 | 0.00 | 1167771.56 | 0.00 | 0.00 | 36151091.07 | 0.00 | 0.02 |
September | 0.00 | 0.115107E+09 | 0.00 | 2138692.57 | 0.00 | 0.00 | 84042964.37 | 0.00 | 0.02 |
October | 21464382.30 | 31085601.80 | 0.00 | 3932343.80 | 0.00 | 0.00 | 0.557646E+09 | 0.00 | 0.02 |
November | 0.190497E+09 | 0.00 | 0.00 | 4050107.83 | 0.00 | 0.00 | 0.805488E+09 | 0.00 | 0.02 |
December | 0.344632E+09 | 0.00 | 0.00 | 2307258.20 | 0.00 | 0.00 | 0.994601E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.112969E+10 | 0.686730E+09 | 0.00 | 27639360.52 | 0.00 | 0.00 | 0.579320E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 222940.87 | 0.00 | 0.00 | 6694014.93 | 0.00 | 0.02 |
Maximum of Months | 0.344632E+09 | 0.294892E+09 | 0.00 | 4050107.83 | 0.00 | 0.00 | 0.103724E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126051E+10 | 0.00 | 0.00 | 15352523.86 | 0.00 | 0.533027E+10 | 0.111732E+11 | 0.00 | 0.40 |
February | 0.182945E+10 | 0.00 | 0.00 | 25698279.90 | 0.00 | 0.290126E+10 | 0.104024E+11 | 0.00 | 0.40 |
March | 0.239757E+10 | 0.00 | 0.00 | 50249622.04 | 0.00 | 0.807941E+09 | 0.127513E+11 | 0.00 | 0.40 |
April | 0.194730E+10 | 43805211.98 | 0.00 | 0.112940E+09 | 9840557.71 | 12585679.32 | 0.889518E+10 | 0.00 | 0.40 |
May | 0.128286E+10 | 0.335009E+09 | 0.00 | 0.110469E+09 | 30130383.66 | 2456541.15 | 0.511851E+10 | 0.00 | 0.40 |
June | 0.498232E+09 | 0.785865E+09 | 0.00 | 77279852.82 | 23318914.36 | 0.00 | 0.135881E+10 | 0.00 | 0.40 |
July | 11191367.25 | 0.586377E+10 | 0.00 | 3481690.12 | 0.972643E+09 | 0.00 | 9688079.24 | 0.00 | 0.40 |
August | 0.377492E+09 | 0.264551E+10 | 0.00 | 37031094.10 | 0.374629E+09 | 0.00 | 0.454941E+09 | 0.00 | 0.40 |
September | 0.116907E+10 | 0.251020E+10 | 98838.15 | 59125894.34 | 0.418268E+09 | 0.00 | 0.230664E+10 | 4061.32 | 0.40 |
October | 0.226806E+10 | 0.331248E+09 | 108877.09 | 81011901.41 | 63878657.80 | 10600465.44 | 0.858767E+10 | 2355.78 | 0.40 |
November | 0.186626E+10 | 148980.10 | 0.00 | 31821757.26 | 1249330.35 | 0.189119E+10 | 0.124399E+11 | 0.00 | 0.40 |
December | 0.125210E+10 | 0.00 | 0.00 | 11422077.55 | 0.00 | 0.832100E+10 | 0.826860E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.161601E+11 | 0.125156E+11 | 207715.24 | 0.615884E+09 | 0.189396E+10 | 0.192773E+11 | 0.817669E+11 | 6417.10 | 0.40 |
Minimum of Months | 11191367.25 | 0.00 | 0.00 | 3481690.12 | 0.00 | 0.00 | 9688079.24 | 0.00 | 0.40 |
Maximum of Months | 0.239757E+10 | 0.586377E+10 | 108877.09 | 0.112940E+09 | 0.972643E+09 | 0.832100E+10 | 0.127513E+11 | 4061.32 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 62035511.47 | 0.00 | 0.00 | 2934038.05 | 0.00 | 0.823477E+09 | 0.422445E+09 | 0.00 | 0.35 |
February | 37733120.18 | 0.00 | 0.00 | 4921058.10 | 0.00 | 0.498980E+09 | 0.576041E+09 | 0.00 | 0.35 |
March | 28789607.55 | 0.00 | 0.00 | 7843944.03 | 0.00 | 0.370683E+09 | 0.772898E+09 | 0.00 | 0.35 |
April | 2421480.66 | 3955357.81 | 0.00 | 15875812.58 | 0.00 | 45279053.62 | 0.745105E+09 | 0.00 | 0.35 |
May | 0.00 | 26922110.54 | 0.00 | 16176831.38 | 0.00 | 28594.62 | 0.464100E+09 | 0.00 | 0.36 |
June | 0.00 | 59661947.94 | 0.00 | 12319552.80 | 0.00 | 0.00 | 0.130300E+09 | 0.00 | 0.36 |
July | 0.00 | 0.504032E+09 | 23608.66 | 532127.32 | 0.00 | 0.00 | 1264044.36 | 422.32 | 0.36 |
August | 0.00 | 0.222678E+09 | 0.00 | 6152102.43 | 0.00 | 30478.14 | 57923893.58 | 0.00 | 0.35 |
September | 0.00 | 0.215926E+09 | 0.00 | 10159513.04 | 0.00 | 0.00 | 0.250468E+09 | 0.00 | 0.36 |
October | 6706734.44 | 29141294.33 | 0.00 | 13052067.75 | 0.00 | 10923595.92 | 0.776477E+09 | 0.00 | 0.35 |
November | 23948156.54 | 103098.87 | 0.00 | 7115244.88 | 0.00 | 0.456326E+09 | 0.709207E+09 | 0.00 | 0.35 |
December | 69417740.26 | 0.00 | 0.00 | 2235440.98 | 0.00 | 0.879386E+09 | 0.365290E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.231052E+09 | 0.106242E+10 | 23608.66 | 99317733.34 | 0.00 | 0.308511E+10 | 0.527152E+10 | 422.32 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 532127.32 | 0.00 | 0.00 | 1264044.36 | 0.00 | 0.35 |
Maximum of Months | 69417740.26 | 0.504032E+09 | 23608.66 | 16176831.38 | 0.00 | 0.879386E+09 | 0.776477E+09 | 422.32 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92928075.20 | 0.00 | 0.00 | 479020.67 | 0.00 | 0.107384E+10 | 0.143488E+09 | 0.00 | 0.35 |
February | 0.134723E+09 | 0.00 | 0.00 | 1845508.64 | 0.00 | 0.661364E+09 | 0.319613E+09 | 0.00 | 0.35 |
March | 0.173811E+09 | 0.00 | 0.00 | 4049631.75 | 0.00 | 0.455317E+09 | 0.546898E+09 | 0.00 | 0.35 |
April | 0.127985E+09 | 3785947.70 | 0.00 | 12795663.70 | 168946.68 | 52971556.42 | 0.614834E+09 | 0.00 | 0.35 |
May | 88215177.12 | 25857298.18 | 0.00 | 12818196.03 | 1061658.04 | 89636.92 | 0.379126E+09 | 0.00 | 0.36 |
June | 35911950.07 | 58264025.94 | 0.00 | 9030205.54 | 1390931.73 | 0.00 | 97660775.69 | 0.00 | 0.36 |
July | 825054.35 | 0.435404E+09 | 32470.22 | 379744.14 | 68560412.85 | 0.00 | 591162.74 | 401.40 | 0.36 |
August | 27208262.70 | 0.197226E+09 | 0.00 | 4046521.41 | 25425660.48 | 8142.61 | 32836036.41 | 0.00 | 0.36 |
September | 81416753.82 | 0.189818E+09 | 0.00 | 6730732.82 | 26082807.18 | 62274.30 | 0.172387E+09 | 0.00 | 0.36 |
October | 0.157831E+09 | 26001913.51 | 0.00 | 7418567.37 | 3135966.49 | 18515534.44 | 0.623299E+09 | 0.00 | 0.36 |
November | 0.137199E+09 | 38614.27 | 0.00 | 2664112.77 | 64472.52 | 0.625624E+09 | 0.430969E+09 | 0.00 | 0.35 |
December | 90939270.96 | 0.00 | 0.00 | 376681.21 | 0.00 | 0.111433E+10 | 0.110529E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.114899E+10 | 0.936396E+09 | 32470.22 | 62634586.05 | 0.125891E+09 | 0.400213E+10 | 0.347223E+10 | 401.40 | 0.35 |
Minimum of Months | 825054.35 | 0.00 | 0.00 | 376681.21 | 0.00 | 0.00 | 591162.74 | 0.00 | 0.35 |
Maximum of Months | 0.173811E+09 | 0.435404E+09 | 32470.22 | 12818196.03 | 68560412.85 | 0.111433E+10 | 0.623299E+09 | 401.40 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.330533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
February | 0.265915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 0.268140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.163909E+11 | 0.00 | 0.00 | 0.00 | 58584877.46 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.846065E+10 | 17864182.32 | 0.00 | 2454283.25 | 0.310741E+09 | 0.00 | 0.114757E+10 | 0.00 | 0.58 |
June | 0.166733E+10 | 0.770880E+09 | 0.00 | 13924471.43 | 0.181066E+09 | 0.00 | 0.339970E+10 | 0.00 | 0.54 |
July | 0.317679E+09 | 0.189743E+10 | 0.00 | 6795400.06 | 0.233643E+10 | 0.00 | 0.100944E+10 | 0.00 | 0.53 |
August | 0.248784E+10 | 0.782129E+09 | 0.00 | 8679210.83 | 0.393758E+09 | 0.00 | 0.196882E+10 | 0.00 | 0.55 |
September | 0.567494E+10 | 0.272380E+09 | 0.00 | 5840511.54 | 0.489663E+09 | 0.00 | 0.207996E+10 | 0.00 | 0.58 |
October | 0.181521E+11 | 25326717.12 | 0.00 | 625238.36 | 92893125.77 | 0.00 | 0.281356E+09 | 0.00 | 0.59 |
November | 0.282210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 0.314652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31059110.94 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.199296E+12 | 0.376601E+10 | 0.00 | 38319115.47 | 0.386313E+10 | 31059110.94 | 0.988685E+10 | 0.00 | 0.57 |
Minimum of Months | 0.317679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.330533E+11 | 0.189743E+10 | 0.00 | 13924471.43 | 0.233643E+10 | 31059110.94 | 0.339970E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15634308.18 | 0.00 | 0.00 | 632789.41 | 0.00 | 0.241708E+09 | 69747378.55 | 0.00 | 0.35 |
February | 11843891.14 | 0.00 | 0.00 | 927455.33 | 0.00 | 0.181625E+09 | 85022244.11 | 0.00 | 0.35 |
March | 11307618.07 | 0.00 | 0.00 | 1763278.04 | 0.00 | 0.150935E+09 | 0.131047E+09 | 0.00 | 0.35 |
April | 3372926.69 | 988839.45 | 0.00 | 3446685.20 | 0.00 | 30215870.21 | 0.165135E+09 | 0.00 | 0.35 |
May | 23331.96 | 6730318.94 | 46.76 | 3333624.70 | 0.00 | 844046.68 | 0.115875E+09 | 161.94 | 0.36 |
June | 0.00 | 14915486.99 | 0.00 | 2598110.11 | 0.00 | 27707.83 | 33029092.38 | 0.00 | 0.36 |
July | 0.00 | 0.126014E+09 | 0.00 | 131559.18 | 0.00 | 0.00 | 317483.74 | 0.00 | 0.36 |
August | 0.00 | 55662614.77 | 6328.66 | 1313428.18 | 0.00 | 45966.33 | 14667224.02 | 544.42 | 0.36 |
September | 0.00 | 53981563.48 | 0.00 | 2195966.34 | 0.00 | 271700.14 | 62689097.16 | 0.00 | 0.36 |
October | 2281586.52 | 7285323.58 | 0.00 | 3103335.32 | 0.00 | 22528681.29 | 0.173876E+09 | 0.00 | 0.35 |
November | 6322159.56 | 25774.72 | 0.00 | 1410305.57 | 0.00 | 0.154178E+09 | 0.137238E+09 | 0.00 | 0.35 |
December | 17067390.33 | 0.00 | 0.00 | 445918.11 | 0.00 | 0.259677E+09 | 51892408.82 | 0.00 | 0.35 |
Annual Sum or Average | 67853212.46 | 0.265604E+09 | 6375.42 | 21302455.51 | 0.00 | 0.104206E+10 | 0.104054E+10 | 706.35 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 131559.18 | 0.00 | 0.00 | 317483.74 | 0.00 | 0.35 |
Maximum of Months | 17067390.33 | 0.126014E+09 | 6328.66 | 3446685.20 | 0.00 | 0.259677E+09 | 0.173876E+09 | 544.42 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22202313.18 | 0.00 | 0.00 | 165622.49 | 0.00 | 0.285659E+09 | 19658043.28 | 0.00 | 0.35 |
February | 33717891.79 | 0.00 | 0.00 | 244428.13 | 0.00 | 0.215226E+09 | 30197957.76 | 0.00 | 0.35 |
March | 44188564.96 | 0.00 | 0.00 | 678936.68 | 0.00 | 0.171503E+09 | 78648931.44 | 0.00 | 0.35 |
April | 34848125.59 | 946486.92 | 0.00 | 2741673.48 | 42236.67 | 30674452.10 | 0.133882E+09 | 0.00 | 0.35 |
May | 22857265.08 | 6450068.87 | 4014.89 | 2807543.82 | 275499.31 | 215001.34 | 94182493.74 | 155.99 | 0.36 |
June | 9182712.51 | 14601121.48 | 144.48 | 2089239.89 | 312372.35 | 0.00 | 24378780.43 | 101.11 | 0.36 |
July | 206263.59 | 0.108373E+09 | 925.57 | 106414.54 | 17625017.70 | 0.00 | 136312.18 | 61.34 | 0.36 |
August | 6954873.44 | 49176734.26 | 2540.87 | 981077.80 | 6483433.84 | 3744.84 | 8085044.71 | 256.39 | 0.36 |
September | 20627757.73 | 47143683.75 | 5664.10 | 1530127.96 | 6825396.45 | 153678.91 | 42837564.98 | 494.45 | 0.36 |
October | 41418289.80 | 6501875.76 | 0.00 | 1464515.10 | 782594.24 | 27343955.28 | 0.131539E+09 | 0.00 | 0.36 |
November | 33746270.79 | 19513.07 | 0.00 | 419723.33 | 6258.62 | 0.214043E+09 | 50904976.86 | 0.00 | 0.35 |
December | 22357969.38 | 0.00 | 0.00 | 85767.19 | 0.00 | 0.295947E+09 | 10652677.04 | 0.00 | 0.35 |
Annual Sum or Average | 0.292308E+09 | 0.233213E+09 | 13289.91 | 13315070.42 | 32352809.18 | 0.124077E+10 | 0.625105E+09 | 1069.28 | 0.35 |
Minimum of Months | 206263.59 | 0.00 | 0.00 | 85767.19 | 0.00 | 0.00 | 136312.18 | 0.00 | 0.35 |
Maximum of Months | 44188564.96 | 0.108373E+09 | 5664.10 | 2807543.82 | 17625017.70 | 0.295947E+09 | 0.133882E+09 | 494.45 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22881501.79 | 0.00 | 0.00 | 11752559.38 | 0.00 | 0.790159E+09 | 0.128066E+10 | 0.00 | 0.40 |
February | 16399420.35 | 0.00 | 0.00 | 11892555.38 | 0.00 | 0.535438E+09 | 0.123139E+10 | 0.00 | 0.40 |
March | 23566878.66 | 0.00 | 0.00 | 13230216.77 | 0.00 | 0.425041E+09 | 0.143373E+10 | 0.00 | 0.40 |
April | 4631190.15 | 6352788.52 | 0.00 | 18611764.96 | 0.00 | 98673621.38 | 0.117693E+10 | 0.00 | 0.40 |
May | 0.00 | 43240203.06 | 0.00 | 16897406.14 | 0.00 | 3315004.63 | 0.751217E+09 | 0.00 | 0.40 |
June | 0.00 | 95824387.17 | 0.00 | 13507845.95 | 0.00 | 91479.77 | 0.215465E+09 | 0.00 | 0.40 |
July | 0.00 | 0.809576E+09 | 0.00 | 665244.21 | 0.00 | 0.00 | 2219627.23 | 0.00 | 0.40 |
August | 0.00 | 0.357624E+09 | 23679.91 | 7430416.86 | 0.00 | 83302.17 | 95449120.95 | 96.77 | 0.40 |
September | 0.00 | 0.346804E+09 | 0.00 | 13333974.71 | 0.00 | 382158.73 | 0.404883E+09 | 0.00 | 0.40 |
October | 8907055.42 | 46804483.71 | 0.00 | 23783254.05 | 0.00 | 1163557.85 | 0.126254E+10 | 0.00 | 0.40 |
November | 25072899.98 | 165589.40 | 0.00 | 17370500.27 | 0.00 | 0.463625E+09 | 0.141581E+10 | 0.00 | 0.40 |
December | 23972918.78 | 0.00 | 0.00 | 10440845.11 | 0.00 | 0.924073E+09 | 0.115570E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.125432E+09 | 0.170639E+10 | 23679.91 | 0.158917E+09 | 0.00 | 0.324204E+10 | 0.104260E+11 | 96.77 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 665244.21 | 0.00 | 0.00 | 2219627.23 | 0.00 | 0.40 |
Maximum of Months | 25072899.98 | 0.809576E+09 | 23679.91 | 23783254.05 | 0.00 | 0.924073E+09 | 0.143373E+10 | 96.77 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145520E+10 | 0.00 | 0.00 | 55799690.09 | 0.00 | 0.00 | 0.541338E+11 | 0.00 | 4.56 |
February | 0.797398E+09 | 0.00 | 0.00 | 56692833.02 | 0.00 | 0.00 | 0.453536E+11 | 0.00 | 4.71 |
March | 0.508048E+09 | 0.00 | 0.00 | 72356577.86 | 0.00 | 0.00 | 0.482278E+11 | 0.00 | 4.92 |
April | 50925453.21 | 96806853.15 | 0.00 | 90956013.35 | 0.00 | 0.00 | 0.326519E+11 | 0.00 | 5.39 |
May | 0.00 | 0.577210E+09 | 0.00 | 94576407.76 | 0.00 | 0.00 | 0.211212E+11 | 0.00 | 5.63 |
June | 0.00 | 0.177577E+10 | 0.00 | 76460801.84 | 0.00 | 0.00 | 0.115782E+11 | 0.00 | 5.30 |
July | 0.00 | 0.857671E+10 | 0.00 | 34330406.62 | 0.00 | 0.00 | 0.311428E+10 | 0.00 | 5.20 |
August | 0.00 | 0.228195E+10 | 0.00 | 72352249.88 | 0.00 | 0.00 | 0.994339E+10 | 0.00 | 5.38 |
September | 0.00 | 0.138080E+10 | 0.00 | 78969728.65 | 0.00 | 0.00 | 0.167835E+11 | 0.00 | 5.60 |
October | 8407151.56 | 0.218808E+09 | 0.00 | 86839914.04 | 0.00 | 0.00 | 0.362036E+11 | 0.00 | 5.34 |
November | 0.587815E+09 | 0.00 | 0.00 | 64375358.43 | 0.00 | 0.00 | 0.491072E+11 | 0.00 | 4.75 |
December | 0.163039E+10 | 0.00 | 0.00 | 52618208.46 | 0.00 | 0.00 | 0.503002E+11 | 0.00 | 4.50 |
Annual Sum or Average | 0.503819E+10 | 0.149081E+11 | 0.00 | 0.836328E+09 | 0.00 | 0.00 | 0.378519E+12 | 0.00 | 5.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34330406.62 | 0.00 | 0.00 | 0.311428E+10 | 0.00 | 4.50 |
Maximum of Months | 0.163039E+10 | 0.857671E+10 | 0.00 | 94576407.76 | 0.00 | 0.00 | 0.541338E+11 | 0.00 | 5.63 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300270E+09 | 0.00 | 0.00 | 70072552.55 | 0.00 | 0.00 | 0.608589E+11 | 0.00 | 5.01 |
February | 0.180125E+09 | 0.00 | 0.00 | 69078888.10 | 0.00 | 0.00 | 0.505503E+11 | 0.00 | 5.17 |
March | 20543957.38 | 0.00 | 0.00 | 85625485.82 | 0.00 | 0.00 | 0.533367E+11 | 0.00 | 5.39 |
April | 0.00 | 0.106576E+09 | 0.00 | 0.101164E+09 | 0.00 | 0.00 | 0.352558E+11 | 0.00 | 5.84 |
May | 0.00 | 0.624848E+09 | 0.00 | 0.101870E+09 | 0.00 | 0.00 | 0.224250E+11 | 0.00 | 6.01 |
June | 0.00 | 0.190332E+10 | 0.00 | 81026613.23 | 0.00 | 0.00 | 0.121692E+11 | 0.00 | 5.62 |
July | 0.00 | 0.914217E+10 | 0.00 | 36121404.80 | 0.00 | 0.00 | 0.326330E+10 | 0.00 | 5.52 |
August | 0.00 | 0.243735E+10 | 0.00 | 76999019.69 | 0.00 | 0.00 | 0.104892E+11 | 0.00 | 5.72 |
September | 0.00 | 0.148430E+10 | 0.00 | 84827987.61 | 0.00 | 0.00 | 0.177905E+11 | 0.00 | 5.97 |
October | 0.00 | 0.234999E+09 | 0.00 | 96614866.99 | 0.00 | 0.00 | 0.389792E+11 | 0.00 | 5.76 |
November | 81519501.39 | 0.00 | 0.00 | 77416745.12 | 0.00 | 0.00 | 0.542773E+11 | 0.00 | 5.19 |
December | 0.445766E+09 | 0.00 | 0.00 | 67407625.27 | 0.00 | 0.00 | 0.566453E+11 | 0.00 | 4.94 |
Annual Sum or Average | 0.102822E+10 | 0.159336E+11 | 0.00 | 0.948225E+09 | 0.00 | 0.00 | 0.416041E+12 | 0.00 | 5.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 36121404.80 | 0.00 | 0.00 | 0.326330E+10 | 0.00 | 4.94 |
Maximum of Months | 0.445766E+09 | 0.914217E+10 | 0.00 | 0.101870E+09 | 0.00 | 0.00 | 0.608589E+11 | 0.00 | 6.01 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.113553E+09 | 0.00 | 0.00 | 0.828582E+11 | 0.00 | 22.82 |
February | 0.00 | 0.00 | 0.00 | 0.106613E+09 | 0.00 | 0.00 | 0.663734E+11 | 0.00 | 23.28 |
March | 0.00 | 0.00 | 0.00 | 0.126133E+09 | 0.00 | 0.00 | 0.659108E+11 | 0.00 | 23.68 |
April | 0.00 | 0.185929E+09 | 0.00 | 0.139286E+09 | 0.00 | 0.00 | 0.392645E+11 | 0.00 | 24.02 |
May | 0.00 | 0.104397E+10 | 0.00 | 0.131043E+09 | 0.00 | 0.00 | 0.221173E+11 | 0.00 | 23.74 |
June | 0.00 | 0.299003E+10 | 0.00 | 95802090.03 | 0.00 | 0.00 | 0.111942E+11 | 0.00 | 21.79 |
July | 0.00 | 0.122941E+11 | 0.00 | 36108575.93 | 0.00 | 0.00 | 0.280437E+10 | 0.00 | 21.52 |
August | 0.00 | 0.350336E+10 | 0.00 | 94524647.37 | 0.00 | 0.00 | 0.101531E+11 | 0.00 | 22.38 |
September | 0.00 | 0.233617E+10 | 0.00 | 0.108036E+09 | 0.00 | 0.00 | 0.179044E+11 | 0.00 | 23.72 |
October | 0.00 | 0.371815E+09 | 0.00 | 0.134276E+09 | 0.00 | 0.00 | 0.449706E+11 | 0.00 | 24.13 |
November | 0.00 | 0.00 | 0.00 | 0.118456E+09 | 0.00 | 0.00 | 0.705672E+11 | 0.00 | 23.22 |
December | 0.00 | 0.00 | 0.00 | 0.112280E+09 | 0.00 | 0.00 | 0.795867E+11 | 0.00 | 22.77 |
Annual Sum or Average | 0.00 | 0.227253E+11 | 0.00 | 0.131611E+10 | 0.00 | 0.00 | 0.513705E+12 | 0.00 | 23.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 36108575.93 | 0.00 | 0.00 | 0.280437E+10 | 0.00 | 21.52 |
Maximum of Months | 0.00 | 0.122941E+11 | 0.00 | 0.139286E+09 | 0.00 | 0.00 | 0.828582E+11 | 0.00 | 24.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108596E+09 | 0.00 | 0.00 | 1.12 |
February | 0.134349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108447E+09 | 0.00 | 0.00 | 1.12 |
March | 0.136155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41135343.05 | 0.00 | 0.00 | 1.13 |
April | 0.809004E+10 | 17845038.97 | 0.00 | 870604.42 | 12002089.42 | 0.00 | 0.257419E+09 | 0.00 | 1.13 |
May | 0.361513E+10 | 0.173405E+09 | 0.00 | 6283359.28 | 14164789.52 | 0.00 | 0.128988E+10 | 0.00 | 1.13 |
June | 0.713637E+09 | 0.631563E+09 | 0.00 | 10773661.77 | 1133094.86 | 0.00 | 0.188483E+10 | 0.00 | 1.14 |
July | 0.131772E+09 | 0.209509E+10 | 0.00 | 4706171.65 | 0.295077E+09 | 0.00 | 0.554501E+09 | 0.00 | 1.12 |
August | 0.100121E+10 | 0.651825E+09 | 0.00 | 8739990.98 | 48988502.52 | 0.00 | 0.128204E+10 | 0.00 | 1.14 |
September | 0.267192E+10 | 0.387809E+09 | 0.00 | 7222330.53 | 46659497.29 | 0.00 | 0.127801E+10 | 0.00 | 1.17 |
October | 0.883606E+10 | 62578030.47 | 0.00 | 2051080.95 | 4683450.03 | 0.00 | 0.552117E+09 | 0.00 | 1.15 |
November | 0.143732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
December | 0.155682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473135E+09 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.987773E+11 | 0.402012E+10 | 0.00 | 40647199.59 | 0.422708E+09 | 0.731313E+09 | 0.709880E+10 | 0.00 | 1.13 |
Minimum of Months | 0.131772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 0.167258E+11 | 0.209509E+10 | 0.00 | 10773661.77 | 0.295077E+09 | 0.473135E+09 | 0.188483E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:45:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.189832E+12 | 0.127363E+11 | 0.161249E+12 | 0.674170E+12 | 0.136711E+12 |
February | 0.197533E+12 | 0.103227E+11 | 0.125726E+12 | 0.537714E+12 | 0.153970E+12 |
March | 0.317591E+12 | 0.988736E+10 | 0.118056E+12 | 0.509513E+12 | 0.210208E+12 |
April | 0.330494E+12 | 0.547653E+10 | 0.634390E+11 | 0.291569E+12 | 0.448647E+12 |
May | 0.363328E+12 | 0.287966E+10 | 0.313553E+11 | 0.165841E+12 | 0.697972E+12 |
June | 0.346073E+12 | 0.719439E+09 | 0.305151E+10 | 0.520770E+11 | 0.897805E+12 |
July | 0.334967E+12 | -0.288758E+10 | -0.367400E+11 | -0.134439E+12 | 0.111395E+13 |
August | 0.304617E+12 | -45764832.5 | 0.225117E+10 | 0.211792E+11 | 0.941033E+12 |
September | 0.260389E+12 | 0.148069E+10 | 0.188646E+11 | 0.106773E+12 | 0.786376E+12 |
October | 0.244032E+12 | 0.572518E+10 | 0.699724E+11 | 0.329089E+12 | 0.448982E+12 |
November | 0.187152E+12 | 0.103926E+11 | 0.128362E+12 | 0.564103E+12 | 0.189305E+12 |
December | 0.153426E+12 | 0.139449E+11 | 0.174818E+12 | 0.746015E+12 | 0.115196E+12 |
Annual Sum or Average | 0.322943E+13 | 0.706322E+11 | 0.860404E+12 | 0.386360E+13 | 0.614016E+13 |
Minimum of Months | 0.153426E+12 | -0.288758E+10 | -0.367400E+11 | -0.134439E+12 | 0.115196E+12 |
Maximum of Months | 0.363328E+12 | 0.139449E+11 | 0.174818E+12 | 0.746015E+12 | 0.111395E+13 |