Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:46:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13400.13 | 1181.12 | 1181.12 |
Net Site Energy | 13400.13 | 1181.12 | 1181.12 |
Total Source Energy | 24560.56 | 2164.82 | 2164.82 |
Net Source Energy | 24560.56 | 2164.82 | 2164.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3311.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 604.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 513.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 81.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 192.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 3482.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4817.48 | 8582.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3311.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 604.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 513.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 81.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 192.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.76 | 3482.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3311.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 604.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 513.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 81.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 192.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.76 | 3482.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.72 | 598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.02 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 424.62 | 756.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.72 | 598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.02 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 424.62 | 756.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4817.485 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4817.485 | 100.00 |
Total On-Site and Utility Electric Sources | 4817.485 | 100.00 |
Total Electricity End Uses | 4817.485 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 125.75 | 2.38 |
Air to Air Heat Recovery for Heating | 5167.74 | 97.62 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5293.49 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 579.17 |
Time Setpoint Not Met During Occupied Cooling | 40.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7954.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 05-JAN-21:40 | - | - | - | - | - | - | - | - | - | - | 12-JAN-21:10 |
Heating | 0.00 | 770099.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 206994.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 52987.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31341.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28333.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6577.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4732.96 | 306775.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2416.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 420897.03 | 1151998.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 770099.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 206994.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 52987.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1038.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28333.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6577.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4732.96 | 306775.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3589.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1913.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2473.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1625.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 259.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 611.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.43 | 3774.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15256.97 | 9303.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 316.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1344.79 | 820.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 316.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1344.79 | 820.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.59 | 0.582379 | 0.495000 | 1.28 | 1.00 | 0.500000 | 0.000654 | 0.000068 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.453979 | 0.112579 | 0.495000 | 0.224720 | 0.495000 | 0.500000 | 0.003384 | 0.000046 | 0.224720 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.237878 | 0.248798 | 0.495000 | 0.117750 | 0.663462 | 0.500000 | 0.001531 | 0.000017 | 0.117750 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.184481 | 0.678408 | 0.495000 | 0.091318 | 1.00 | 0.500000 | 0.000562 | 0.000027 | 0.111908 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.109273 | 0.660788 | 0.495000 | 0.054090 | 1.00 | 0.500000 | 0.000577 | 0.000018 | 0.076010 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.39 | 0.017520 | 0.495000 | 1.68 | 0.495000 | 0.500000 | 0.021747 | 0.000103 | 1.68 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.81 | 0.079409 | 0.495000 | 0.897087 | 0.495000 | 0.500000 | 0.004798 | 0.000132 | 0.897087 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.31 | 0.187563 | 0.495000 | 2.63 | 0.500169 | 0.500000 | 0.002031 | 0.000328 | 2.63 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.71 | 0.694602 | 0.495000 | 0.845834 | 1.00 | 0.500000 | 0.000549 | 0.000161 | 0.845834 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113871 | 0.495000 | 1.10 | 0.495000 | 0.500000 | 0.003346 | 0.000128 | 1.10 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.33 | 0.108657 | 0.495000 | 1.15 | 0.495000 | 0.500000 | 0.003506 | 0.000132 | 1.15 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.39 | 0.059155 | 0.495000 | 1.18 | 0.495000 | 0.500000 | 0.011584 | 0.000088 | 1.18 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.832887 | 0.377049 | 0.495000 | 0.412279 | 1.00 | 0.500000 | 0.001010 | 0.000101 | 0.420981 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7822.09 | 0.000068 | 164.88 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5302.44 | 0.000046 | 137.25 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1930.97 | 0.000017 | 45.64 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3067.39 | 0.000027 | 83.71 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2083.51 | 0.000018 | 56.86 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11801.55 | 0.000103 | 251.17 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15033.73 | 0.000132 | 356.87 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 37540.04 | 0.000328 | 865.32 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9463.76 | 0.000083 | 270.44 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9471.63 | 0.000083 | 270.66 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 53515.97 | 0.000468 | 1529.28 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 53680.19 | 0.000470 | 1533.97 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9480.44 | 0.000083 | 270.92 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9488.31 | 0.000083 | 271.14 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 18430.10 | 0.000161 | 465.86 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2844.60 | 0.000025 | 81.28 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2844.82 | 0.000025 | 81.29 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13583.59 | 0.000119 | 388.15 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14612.71 | 0.000128 | 333.10 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15052.50 | 0.000132 | 342.23 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10059.66 | 0.000088 | 217.45 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11540.77 | 0.000101 | 314.97 |
VAV WITH REHEAT HEATING COIL | 402787.90 | 0.003524 | 5605.90 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.34 | 0.000083 | 0.000415 |
ROOM_2_FLR_3 FAN COIL | 1.27 | 0.000083 | 0.000396 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.47 | 0.000468 | 0.002581 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.29 | 0.000470 | 0.002049 |
ROOM_5_FLR_3 FAN COIL | 1.21 | 0.000083 | 0.000378 |
ROOM_6_FLR_3 FAN COIL | 1.15 | 0.000083 | 0.000360 |
ROOM_1_FLR_6 FAN COIL | 0.347370 | 0.000025 | 0.000108 |
ROOM_2_FLR_6 FAN COIL | 0.329521 | 0.000025 | 0.000102 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.70 | 0.000119 | 0.000533 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.34 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.27 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.47 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.29 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.21 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.15 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.347370 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.329521 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.70 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008624 | 12.80 | 0.008500 | 0.000415 | 1.34 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000396 | 1.27 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008556 | 12.80 | 0.008500 | 0.002581 | 8.47 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008805 | 12.80 | 0.008500 | 0.002049 | 6.29 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008637 | 12.80 | 0.008500 | 0.000378 | 1.21 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008645 | 12.80 | 0.008500 | 0.000360 | 1.15 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008619 | 12.80 | 0.008500 | 0.000108 | 0.347370 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008626 | 12.80 | 0.008500 | 0.000102 | 0.329521 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008662 | 12.80 | 0.008500 | 0.000533 | 1.70 | |
VAV WITH REHEAT COOLING COIL | 27.03 | 6.70 | 0.011174 | 10.91 | 0.008500 | 0.018007 | 23.44 | 629632.91 |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.001989 | 2.05 | 69550.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.79 | 11.67 | 23.58 | 11.67 | 23.44 | 23.44 | 0.300000 | 0.497892 | 23.44 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.44 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.44 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018007 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003524 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001989 | 0.000239 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026918 | 4394.87 | |
HEATSYS1 PUMP | 0.006620 | 1993.61 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006620 | 0.794381 |
COOLSYS1 | 0.026918 | 3.23 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 756689.05 | 756689.05 | 0.006620 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026918 | 3042.72 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026918 | 941189.01 | 941827.31 | 107.37 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.5913 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.57998040E-15 | -0.30968906E-15 | -0.16543531E-09 | -0.94394381E-17 |
29 | 8 | 0.24079056E-07 | 0.80583727E-13 | 0.40057412E-03 | -0.27378716E-09 |
30 | 7 | -0.12920082E-01 | 0.41010748E-08 | -0.24062383E-01 | 0.14690605E-03 |
31 | 6 | 0.42378547 | 0.14160748E-05 | 0.48776087 | -0.49650686E-02 |
32 | 5 | -5.3704470 | 0.52534619E-04 | -4.5614765 | 0.65414341E-01 |
33 | 4 | 33.798395 | 0.42724899E-03 | 21.909926 | -0.43268566 |
34 | 3 | -112.91846 | 0.92631763E-03 | -56.552255 | 1.5396438 |
35 | 2 | 198.80798 | 0.51863526E-03 | 78.726696 | -2.9273457 |
36 | 1 | -171.78376 | 0.55128408E-04 | -55.503401 | 2.7564403 |
37 | 0 | 57.057407 | 0.31226006E-06 | 15.518392 | |
38 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
39 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
40 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
41 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
42 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
43 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
44 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
45 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
46 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
47 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
48 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
49 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
50 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
51 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
52 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
53 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
54 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
55 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
56 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
57 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.33_SHGC_0.45 | 37 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
2 | RESWINDOW_U_0.33_SHGC_0.45 | 38 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1899 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1095 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.2170 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1276 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1259 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 5.1187E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2070E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.7298E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2163 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1307 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2480 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1518 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1392 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 6.3753E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.8462E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.3647E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.7877E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.7663E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.6897E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.0957E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.5066E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3987E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 5.1255E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.8174E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.7877E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.7663E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.6897E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.0957E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.5066E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3987E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 5.1255E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.8174E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34148.20414 | 34148.20414 | 2.58915 | 2.58915 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 25.03667 | 1.27170E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1338.26497 | 1338.26497 | 5.98596E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5986.74283 | 5986.74283 | 0.45398 | 0.45398 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4166.95561 | 4166.95561 | 0.18636 | 0.18636 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3136.95964 | 3136.95964 | 0.23788 | 0.23788 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1335.91076 | 1335.91076 | 5.97518E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2433.31783 | 2433.31783 | 0.18448 | 0.18448 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2502.01070 | 2502.01070 | 0.11191 | 0.11191 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1441.31541 | 1441.31541 | 0.10927 | 0.10927 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1699.42127 | 1699.42127 | 7.60103E-002 | 7.60103E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44764.83614 | 44764.83614 | 3.39421 | 3.39421 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3316.05116 | 3316.05116 | 0.14831 | 0.14831 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23880.11387 | 23880.11387 | 1.81230 | 1.81230 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10499.98839 | 10499.98839 | 0.46961 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 70066.77482 | 70066.77482 | 5.31467 | 5.31467 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 24244.08043 | 24244.08043 | 1.08437 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 13069.32732 | 13069.32732 | 1.33534 | 1.33534 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9463.75906 | 9463.75906 | 0.42574 | 0.42574 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12451.30766 | 12451.30766 | 1.27219 | 1.27219 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9471.63430 | 9471.63430 | 0.42610 | 0.42610 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 82875.44102 | 82875.44102 | 8.46706 | 8.46706 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 53515.97215 | 53515.97215 | 2.40765 | 2.40765 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 61584.86535 | 61584.86535 | 6.29239 | 6.29239 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 53680.19387 | 53680.19387 | 2.41504 | 2.41504 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11889.50470 | 11889.50470 | 1.21479 | 1.21479 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9480.44024 | 9480.44024 | 0.42649 | 0.42649 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11286.79650 | 11286.79650 | 1.15321 | 1.15321 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9488.31393 | 9488.31393 | 0.42685 | 0.42685 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 22537.14151 | 22537.14151 | 1.70876 | 1.70876 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 14153.88407 | 14153.88407 | 0.63308 | 0.63308 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3399.81039 | 3399.81039 | 0.34737 | 0.34737 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2844.59590 | 2844.59590 | 0.12797 | 0.12797 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3225.11761 | 3225.11761 | 0.32952 | 0.32952 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2844.82497 | 2844.82497 | 0.12798 | 0.12798 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 16641.34779 | 16641.34779 | 1.70033 | 1.70033 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 13583.59003 | 13583.59003 | 0.61109 | 0.61109 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29234.81733 | 29234.81733 | 2.21938 | 2.21938 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9058.42907 | 9058.42907 | 0.40516 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30638.20479 | 30638.20479 | 2.32588 | 2.32588 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9231.62746 | 9231.62746 | 0.41291 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31485.62845 | 31485.62845 | 2.39346 | 2.39346 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4078.98175 | 4078.98175 | 0.18242 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10985.15068 | 10985.15068 | 0.83289 | 0.83289 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9412.05326 | 9412.05326 | 0.42098 | 0.42098 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 386680.20 | 23.43936 | 23.43936 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 448862.32 | 7.83617 | 7.83617 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 20.53109 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 7.39491 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58915 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58238 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28163 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.54213E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.84311E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28163 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7822.09057 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.84311E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 164.88024 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45398 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11258 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22472 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38430E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.63881E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22472 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5302.44424 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63881E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 137.25415 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23788 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24880 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11775 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66346 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53136E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.68930E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11775 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1930.96941 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68930E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.64054 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18448 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67841 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.13180E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.61609E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.68349E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11191 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3067.39280 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68349E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.70972 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10927 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66079 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.40904E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.76584E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82275E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.60103E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2083.51098 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82275E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.86012 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39421 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.75199E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68013 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17467E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03245E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68013 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11801.54954 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03245E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.16561 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81230 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.94090E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.89709 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.79794E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31522E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89709 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15033.73272 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31522E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 356.87483 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.31467 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18756 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.63076 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50017 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03131E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28417E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.63076 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37540.03995 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28417E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 865.31869 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.33534 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.33534 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.27931E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.14569E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70753 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62438E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.14569E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.33534 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9463.75906 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.27931E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 270.43893 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.27219 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.27219 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.28620E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.95569E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70751 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63004E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.95569E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.27219 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9471.63430 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.28620E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 270.66391 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.46706 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.46706 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.68181E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.58054E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70818 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55631E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.58054E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.46706 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53515.97215 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68181E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1529.28227 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.29239 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.29239 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.69618E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.04901E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70726 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80541E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04901E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.29239 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53680.19387 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.69618E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1533.97404 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21479 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21479 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.29390E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.78452E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70750 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63722E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.78452E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21479 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9480.44024 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.29390E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 270.91549 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15321 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.15321 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.30079E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.59987E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70748 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64466E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.59987E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15321 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9488.31393 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30079E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.14043 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70876 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69460 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84583 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.48516E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61235E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84583 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18430.10109 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61235E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 465.86107 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34737 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34737 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.48858E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.07702E-004 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70754 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61948E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07702E-004 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34737 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2844.59590 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48858E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 81.28434 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32952 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32952 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.48878E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.02338E-004 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70752 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62565E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.02338E-004 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32952 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2844.82497 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48878E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 81.29089 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.70033 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.70033 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.18835E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.33171E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70736 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66152E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.33171E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.70033 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 13583.59003 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18835E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 388.14995 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21938 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11387 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.09859 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34588E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27838E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09859 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14612.70633 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27838E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.09633 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32588 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10866 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15131 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50645E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31686E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15131 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15052.50371 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31686E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 342.23327 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39346 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.91547E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18476 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15845E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.80063E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18476 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10059.65586 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.80063E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 217.45007 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83289 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37705 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41228 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01048E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00964E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42098 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11540.77231 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00964E-004 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.96761 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.78815 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67027 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.57629 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67027 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.43936 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.43936 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49789 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.43936 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.43936 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.02982 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90674 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11745E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 629632.90921 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.80074E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.43936 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 402787.89536 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.52376E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5605.90435 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.43936 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.80074E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.64441E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.52376E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.98912E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.98912E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.39397E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.69179E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4394.86833 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.61985E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.79438 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.61985E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1993.60687 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 756689.04565 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 756689.05000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.61985E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.69179E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.23015 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.69179E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3042.71558 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.69179E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 941189.00710 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 941827.31000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 107.36831 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7862.24 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5324.01 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1939.79 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3079.24 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2091.56 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11861.63 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15102.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 37715.27 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 10193.78 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 10202.26 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 57644.71 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 57821.58 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 10211.74 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 10220.22 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 18507.92 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3063.95 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3064.19 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14631.07 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14681.62 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15123.66 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10110.20 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11585.36 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 231057.33 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 22021.49 | 18620.12 | 3401.37 | 0.85 | 5115.72 | 51.89 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 21002.01 | 17746.73 | 3255.28 | 0.85 | 4867.69 | 49.37 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 137844.78 | 117478.15 | 20366.63 | 0.85 | 32892.20 | 333.61 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 107188.59 | 88878.15 | 18310.44 | 0.83 | 23360.88 | 236.94 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 20080.80 | 16954.59 | 3126.21 | 0.84 | 4640.76 | 47.07 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 19088.81 | 16103.58 | 2985.23 | 0.84 | 4398.46 | 44.61 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5722.75 | 4841.66 | 881.09 | 0.85 | 1330.75 | 13.50 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5435.52 | 4595.30 | 840.22 | 0.85 | 1262.05 | 12.80 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28231.35 | 23771.72 | 4459.63 | 0.84 | 6462.44 | 65.55 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 650511.50 | 430349.96 | 220161.54 | 0.66 | 103100.20 | 1045.70 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60070.69 | 38934.02 | 21136.67 | 0.65 | 8372.83 | 84.92 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.7546542076E-002 | 8.5424332743E-002 | Pass | Pass | 6.3903531720E-002 | 0.3721997156 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8145558685E-002 | 0.1637297104 | Pass | Pass | 0.5472975587 | 2.6259512626 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.9809041161E-002 | 9.8735063827E-002 | Pass | Pass | 0.2966186130 | 1.0063854757 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0934691582E-002 | 5.1658390835E-002 | Pass | Pass | 3.9538251315E-002 | 0.2492426639 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1918900036E-002 | 5.0400603863E-002 | Pass | Pass | 2.1341952006E-002 | 0.1444093248 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1828771497 | 0.5579939239 | Pass | Pass | 2.6738992710E-002 | 6.8050119331E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.9301564239E-002 | 0.1410359247 | Pass | Pass | 5.2238029149E-002 | 0.1119182515 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7413287939E-002 | 0.1046701300 | Pass | Pass | 5.8054390831E-002 | 0.1451102959 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.9826999595E-002 | 0.3253920215 | Pass | Pass | 0.3965641456 | 3.2756086740 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2680330088E-002 | 0.3397558394 | Pass | Pass | 6.6446534560E-002 | 0.2186514730 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.8031891715E-002 | 7.4838219959E-002 | Pass | Pass | 7.4765308899E-003 | 7.5024265863E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4783275908E-002 | 0.2190148050 | Pass | Pass | 5.7584162347E-002 | 0.1737865002 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2682038625E-002 | 0.3275041698 | Pass | Pass | 9.6125709922E-002 | 0.2739565146 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2740712735E-002 | 0.3350843109 | Pass | Pass | 7.4930792692E-002 | 0.2523285422 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3772285492E-002 | 5.6150823284E-002 | Pass | Pass | 4.5037017213E-002 | 7.7503399878E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.4757335612E-002 | 0.3502485682 | Pass | Pass | 0.1047582692 | 0.3128539220 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2686717983E-002 | 0.3449643309 | Pass | Pass | 5.1420774206E-002 | 0.1688847813 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.8384910699E-002 | 0.3137935036 | Pass | Pass | 0.3027193391 | 0.9728147776 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8088574007E-002 | 0.1758986108 | Pass | Pass | 2.1187886933E-002 | 5.1431271188E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2016285610E-002 | 0.1711621238 | Pass | Pass | 1.7637397114E-002 | 4.2174732404E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1357286182 | 0.3664638400 | Pass | Pass | 2.6138245120E-002 | 4.9891094369E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.8075206866E-002 | 8.2933531712E-002 | Pass | Pass | 7.0148240898E-002 | 0.3869535506 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3848.60 | 202.37 | 2557.85 | 10572.44 | 3510.00 | 20691.26 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.875 | 0.451 | 0.497 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.875 | 0.451 | 0.497 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.875 | 0.451 | 0.497 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.875 | 0.451 | 0.497 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.875 | 0.451 | 0.497 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.875 | 0.451 | 0.497 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.875 | 0.451 | 0.497 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.875 | 0.451 | 0.497 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 432.95 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.875 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.02 | 0.0000 | Y | 13.85 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.49 | 0.0000 | Y | 109.66 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 30.50 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 30.50 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 455.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.52 | 83.52 | 193.43 | |
Exterior Lighting Total | 12338.45 | 193.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 756689.05 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 941827.31 | 2.96 | 941992.86 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14495.75 | 22021.49 | 18620.12 | 3401.37 | 0.85 | - | 5115.72 | 51.89 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13831.41 | 21002.01 | 17746.73 | 3255.28 | 0.85 | - | 4867.69 | 49.37 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 90230.74 | 137844.78 | 117478.15 | 20366.63 | 0.85 | - | 32892.20 | 333.61 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 71645.49 | 107188.59 | 88878.15 | 18310.44 | 0.83 | - | 23360.88 | 236.94 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13232.89 | 20080.80 | 16954.59 | 3126.21 | 0.84 | - | 4640.76 | 47.07 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12587.23 | 19088.81 | 16103.58 | 2985.23 | 0.84 | - | 4398.46 | 44.61 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3765.89 | 5722.75 | 4841.66 | 881.09 | 0.85 | - | 1330.75 | 13.50 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3578.35 | 5435.52 | 4595.30 | 840.22 | 0.85 | - | 1262.05 | 12.80 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 18642.78 | 28231.35 | 23771.72 | 4459.63 | 0.84 | - | 6462.44 | 65.55 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 629632.91 | 650511.50 | 430349.96 | 220161.54 | 0.66 | - | 103100.20 | 1045.70 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60070.69 | 38934.02 | 21136.67 | 0.65 | - | 8372.83 | 84.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7822.09 | 7862.24 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5302.44 | 5324.01 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1930.97 | 1939.79 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3067.39 | 3079.24 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2083.51 | 2091.56 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11801.55 | 11861.63 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15033.73 | 15102.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37540.04 | 37715.27 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9463.76 | 10193.78 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9471.63 | 10202.26 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53515.97 | 57644.71 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53680.19 | 57821.58 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9480.44 | 10211.74 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9488.31 | 10220.22 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18430.10 | 18507.92 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2844.60 | 3063.95 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2844.82 | 3064.19 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 13583.59 | 14631.07 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14612.71 | 14681.62 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15052.50 | 15123.66 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10059.66 | 10110.20 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11540.77 | 11585.36 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 402787.90 | 231057.33 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.34 | 939.59 | 703.64 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.27 | 895.16 | 703.64 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.47 | 5957.73 | 703.64 | 1.00 | 0.94 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.29 | 4427.55 | 703.64 | 1.00 | 0.96 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 854.77 | 703.64 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 811.44 | 703.64 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.35 | 244.42 | 703.64 | 1.00 | 1.62 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 231.86 | 703.64 | 1.00 | 1.65 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.70 | 1196.41 | 703.64 | 1.00 | 1.09 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.44 | 52519.13 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026918 | 4394.87 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006620 | 1993.61 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026918 | 3042.72 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34148.20 | 34148.20 | 17.26 | 2.589 | 2.589 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00921 | 25.04 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5986.74 | 5986.74 | 89.26 | 0.454 | 0.454 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00899 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3136.96 | 3136.96 | 40.39 | 0.238 | 0.238 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00945 | 29.98 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 2433.32 | 2433.32 | 14.82 | 0.184 | 0.184 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 29.98 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1441.32 | 1441.32 | 15.21 | 0.109 | 0.109 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00899 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44764.84 | 44764.84 | 573.62 | 3.394 | 3.394 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 23880.11 | 23880.11 | 126.44 | 1.812 | 1.812 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00988 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 70066.77 | 70066.77 | 53.56 | 5.315 | 5.315 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00990 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 13069.33 | 13069.33 | 334.92 | 1.335 | 1.335 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00862 | 28.16 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12451.31 | 12451.31 | 319.12 | 1.272 | 1.272 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 82875.44 | 82875.44 | 3379.38 | 8.467 | 8.467 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00856 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 61584.87 | 61584.87 | 2510.54 | 6.292 | 6.292 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00881 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11889.50 | 11889.50 | 304.69 | 1.215 | 1.215 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00864 | 25.39 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11286.80 | 11286.80 | 289.28 | 1.153 | 1.153 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00864 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 22537.14 | 22537.14 | 57.88 | 1.709 | 1.709 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00940 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3399.81 | 3399.81 | 87.13 | 0.347 | 0.347 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3225.12 | 3225.12 | 82.66 | 0.330 | 0.330 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16641.35 | 16641.35 | 678.39 | 1.700 | 1.700 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00866 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29234.82 | 29234.82 | 88.15 | 2.219 | 2.219 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 30638.20 | 30638.20 | 92.38 | 2.326 | 2.326 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01036 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31485.63 | 31485.63 | 304.78 | 2.393 | 2.393 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.00998 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10985.15 | 10985.15 | 26.65 | 0.833 | 0.833 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1338.26 | 1338.26 | 0.68 | 0.060 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4166.96 | 4166.96 | 62.13 | 0.186 | 0.186 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00753 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1335.91 | 1335.91 | 17.20 | 0.060 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00744 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2502.01 | 2502.01 | 15.23 | 0.112 | 0.112 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00731 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1699.42 | 1699.42 | 17.93 | 0.076 | 0.076 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3316.05 | 3316.05 | 42.49 | 0.148 | 0.148 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00729 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 10499.99 | 10499.99 | 55.60 | 0.470 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 24244.08 | 24244.08 | 18.53 | 1.084 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9463.76 | 9463.76 | 242.52 | 0.426 | 0.426 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9471.63 | 9471.63 | 242.75 | 0.426 | 0.426 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53515.97 | 53515.97 | 2182.20 | 2.408 | 2.408 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53680.19 | 53680.19 | 2188.30 | 2.415 | 2.415 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9480.44 | 9480.44 | 242.95 | 0.426 | 0.426 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9488.31 | 9488.31 | 243.18 | 0.427 | 0.427 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14153.88 | 14153.88 | 36.35 | 0.633 | 0.633 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2844.60 | 2844.60 | 72.90 | 0.128 | 0.128 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2844.82 | 2844.82 | 72.91 | 0.128 | 0.128 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13583.59 | 13583.59 | 553.74 | 0.611 | 0.611 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9058.43 | 9058.43 | 27.31 | 0.405 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 9231.63 | 9231.63 | 27.83 | 0.413 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4078.98 | 4078.98 | 39.49 | 0.182 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00714 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9412.05 | 9412.05 | 22.84 | 0.421 | 0.421 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00773 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.44 | 23.44 | 7.84 | 7.84 | 23.4394 | 11.6703 | 23.4394 | 0.4979 | 0.3000 |
FLR_3_DOAS | 20.53 | 2.05 | 7.39 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7822.091 | 7822.091 | 1.281630 | 0.00006843 | 164.880 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7822.09 | 7822.09 | 1.281630 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00793165 | 49.1414 | 1338.26 | 0.00 | 7865.89 | 7865.89 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5302.444 | 5302.444 | 0.224720 | 0.00004639 | 137.254 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5302.44 | 5302.44 | 0.224720 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00752908 | 46.6831 | 4166.96 | 0.00 | 5329.17 | 5329.17 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1930.969 | 1930.969 | 0.117750 | 0.00001689 | 45.641 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1930.97 | 1930.97 | 0.117750 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00743993 | 46.1332 | 1335.91 | 0.00 | 1941.24 | 1941.24 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3067.393 | 3067.393 | 0.111908 | 0.00002683 | 83.710 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3067.39 | 3067.39 | 0.111908 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00730626 | 45.3143 | 2502.01 | 0.00 | 3082.60 | 3082.60 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2083.511 | 2083.511 | 0.076010 | 0.00001823 | 56.860 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2083.51 | 2083.51 | 0.076010 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00740274 | 45.9056 | 1699.42 | 0.00 | 2093.84 | 2093.84 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11801.550 | 11801.550 | 1.680132 | 0.00010325 | 251.166 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11801.55 | 11801.55 | 1.680132 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00728714 | 45.2008 | 3316.05 | 0.00 | 11867.41 | 11867.41 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15033.733 | 15033.733 | 0.897087 | 0.00013152 | 356.875 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15033.73 | 15033.73 | 0.897087 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00758381 | 47.0172 | 10499.99 | 0.00 | 15113.62 | 15113.62 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 37540.040 | 37540.040 | 2.630762 | 0.00032842 | 865.319 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37540.04 | 37540.04 | 2.630762 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00749144 | 46.4489 | 24244.08 | 0.00 | 37741.24 | 37741.24 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14495.747 | -999.000 | 1.335336 | 0.00041457 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 14495.75 | 14089.91 | 1.335336 | 21.71 | 15.25 | 0.00862438 | 12.80 | 11.72 | 0.00850000 | 28.16 | 0.01272245 | 20.56 | 0.0000 | 21.11 | 0.00862438 | 53.0144 | 13069.33 | 0.00 | 15125.72 | 15125.72 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9463.759 | 9463.759 | 0.425741 | 0.00008279 | 270.439 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9463.76 | 9463.76 | 0.425741 | 21.11 | 14.04 | 0.00752186 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752186 | 46.3226 | 9463.76 | 0.00 | 10201.88 | 10201.88 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13831.410 | -999.000 | 1.272192 | 0.00039557 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 13831.41 | 13427.05 | 1.272192 | 21.71 | 15.25 | 0.00863004 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00863004 | 53.0488 | 12451.31 | 0.00 | 14431.86 | 14431.86 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9471.634 | 9471.634 | 0.426095 | 0.00008286 | 270.664 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9471.63 | 9471.63 | 0.426095 | 21.11 | 14.04 | 0.00752227 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752227 | 46.3251 | 9471.63 | 0.00 | 10210.36 | 10210.36 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 90230.743 | -999.000 | 8.467059 | 0.00258054 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 90230.74 | 89069.30 | 8.467059 | 21.71 | 15.19 | 0.00855631 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00855631 | 52.5998 | 82875.44 | 0.00 | 94178.07 | 94178.07 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53515.972 | 53515.972 | 2.407652 | 0.00046818 | 1529.282 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53515.97 | 53515.97 | 2.407652 | 21.11 | 14.07 | 0.00755007 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755007 | 46.4907 | 53515.97 | 0.00 | 57691.07 | 57691.07 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 71645.487 | -999.000 | 6.292386 | 0.00204901 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 71645.49 | 66912.80 | 6.292386 | 21.71 | 15.40 | 0.00880541 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00880541 | 54.1119 | 61584.87 | 0.00 | 74678.78 | 71776.19 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 53680.194 | 53680.194 | 2.415040 | 0.00046962 | 1533.974 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53680.19 | 53680.19 | 2.415040 | 21.11 | 14.07 | 0.00755125 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755125 | 46.4979 | 53680.19 | 0.00 | 57868.11 | 57868.11 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13232.891 | -999.000 | 1.214792 | 0.00037845 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 13232.89 | 12825.33 | 1.214792 | 21.71 | 15.26 | 0.00863722 | 12.80 | 11.72 | 0.00850000 | 25.39 | 0.01271761 | 19.73 | 0.0000 | 21.11 | 0.00863722 | 53.0923 | 11889.50 | 0.00 | 13806.57 | 13806.57 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9480.440 | 9480.440 | 0.426492 | 0.00008294 | 270.915 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9480.44 | 9480.44 | 0.426492 | 21.11 | 14.04 | 0.00752265 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752265 | 46.3274 | 9480.44 | 0.00 | 10219.86 | 10219.86 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12587.235 | -999.000 | 1.153212 | 0.00035999 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 12587.23 | 12179.22 | 1.153212 | 21.71 | 15.26 | 0.00864466 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00864466 | 53.1374 | 11286.80 | 0.00 | 13132.16 | 13132.16 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9488.314 | 9488.314 | 0.426846 | 0.00008301 | 271.140 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9488.31 | 9488.31 | 0.426846 | 21.11 | 14.04 | 0.00752306 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752306 | 46.3299 | 9488.31 | 0.00 | 10228.35 | 10228.35 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 18430.101 | 18430.101 | 0.845834 | 0.00016123 | 465.861 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18430.10 | 18430.10 | 0.845834 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00760669 | 47.1535 | 14153.88 | 0.00 | 18524.80 | 18524.80 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3765.885 | -999.000 | 0.347370 | 0.00010770 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3765.89 | 3664.49 | 0.347370 | 21.71 | 15.24 | 0.00861948 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00861948 | 52.9847 | 3399.81 | 0.00 | 3929.17 | 3929.17 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2844.596 | 2844.596 | 0.127969 | 0.00002489 | 81.284 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2844.60 | 2844.60 | 0.127969 | 21.11 | 14.11 | 0.00759809 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00759809 | 46.7862 | 2844.60 | 0.00 | 3066.46 | 3066.46 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3578.351 | -999.000 | 0.329521 | 0.00010234 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3578.35 | 3477.17 | 0.329521 | 21.71 | 15.25 | 0.00862565 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00862565 | 53.0221 | 3225.12 | 0.00 | 3733.82 | 3733.82 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2844.825 | 2844.825 | 0.127979 | 0.00002489 | 81.291 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2844.82 | 2844.82 | 0.127979 | 21.11 | 14.11 | 0.00759815 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00759815 | 46.7866 | 2844.82 | 0.00 | 3066.71 | 3066.71 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 18642.784 | -999.000 | 1.700327 | 0.00053317 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 18642.78 | 17970.58 | 1.700327 | 21.71 | 15.28 | 0.00866152 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00866152 | 53.2400 | 16641.35 | 0.00 | 19447.34 | 19447.34 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13583.590 | 13583.590 | 0.611094 | 0.00011884 | 388.150 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13583.59 | 13583.59 | 0.611094 | 21.11 | 14.12 | 0.00761173 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00761173 | 46.8680 | 13583.59 | 0.00 | 14643.15 | 14643.15 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14612.706 | 14612.706 | 1.098591 | 0.00012784 | 333.096 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14612.71 | 14612.71 | 1.098591 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00768635 | 47.6426 | 9058.43 | 0.00 | 14691.32 | 14691.32 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15052.504 | 15052.504 | 1.151310 | 0.00013169 | 342.233 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 15052.50 | 15052.50 | 1.151310 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769200 | 47.6772 | 9231.63 | 0.00 | 15133.56 | 15133.56 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10059.656 | 10059.656 | 1.184762 | 0.00008801 | 217.450 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 10059.66 | 10059.66 | 1.184762 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00714387 | 44.3249 | 4078.98 | 0.00 | 10115.53 | 10115.53 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11540.772 | 11540.772 | 0.420981 | 0.00010096 | 314.968 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 11540.77 | 11540.77 | 0.420981 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773383 | 47.9326 | 9412.05 | 0.00 | 11598.00 | 11598.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 629632.909 | -999.000 | 23.439359 | 0.01800742 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 629632.91 | 444688.09 | 23.439359 | 27.03 | 19.09 | 0.01117449 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 49.7516 | 23.99 | 0.00959526 | 49.4335 | 308882.96 | 0.00 | 646868.14 | 441812.24 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 402787.895 | 402787.895 | 7.031808 | 0.00352376 | 5605.904 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 402787.90 | 402787.90 | 7.031808 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 165.8387 | 21.00 | 0.00757500 | 46.9578 | 93943.34 | 0.00 | 279056.13 | 279056.13 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00866497 | 53.2596 | 200948.51 | 0.00 | 71135.90 | 45208.06 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00755107 | 46.4969 | 164373.32 | 0.00 | 24421.86 | 24421.86 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7822.091 | 7822.091 | 1.281630 | 0.00006843 | 164.880 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.0133 | 1.033726 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7822.09 | 7822.09 | 1.0000 | 1.47890517 | 1.281630 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.06842408 | 60.00 | 32.22 | 27.78 | 0.000 | 7822.09 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793165 | 21.00 | 0.00793165 | 49.1414 | 1338.26 | 0.00 | 7865.89 | 7865.89 | 1.47890517 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.82 | 15.16 | 0.00800000 | 42253.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5302.444 | 5302.444 | 0.224720 | 0.00004639 | 137.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.6869 | 0.700743 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5302.44 | 5302.44 | 1.0000 | 0.25930963 | 0.224720 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.04638336 | 60.00 | 32.22 | 27.78 | 0.000 | 5302.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00752908 | 21.00 | 0.00752908 | 46.6831 | 4166.96 | 0.00 | 5329.17 | 5329.17 | 0.25930963 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.75 | 20.20 | 0.00800000 | 57486.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1930.969 | 1930.969 | 0.117750 | 0.00001689 | 45.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.2502 | 0.255187 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1930.97 | 1930.97 | 1.0000 | 0.13587426 | 0.117750 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01689124 | 60.00 | 32.22 | 27.78 | 0.000 | 1930.97 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00743993 | 21.00 | 0.00743993 | 46.1332 | 1335.91 | 0.00 | 1941.24 | 1941.24 | 0.13587426 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.61 | 18.24 | 0.00800000 | 51221.8 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3067.393 | 3067.393 | 0.111908 | 0.00002683 | 83.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.3974 | 0.405370 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3067.39 | 3067.39 | 1.0000 | 0.12913307 | 0.111908 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02683215 | 60.00 | 32.22 | 27.78 | 0.000 | 3067.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00730626 | 21.00 | 0.00730626 | 45.3143 | 2502.01 | 0.00 | 3082.60 | 3082.60 | 0.12913307 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2083.511 | 2083.511 | 0.076010 | 0.00001823 | 56.860 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.2699 | 0.275346 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2083.51 | 2083.51 | 1.0000 | 0.08771013 | 0.076010 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01822560 | 60.00 | 32.22 | 27.78 | 0.000 | 2083.51 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00740274 | 21.00 | 0.00740274 | 45.9056 | 1699.42 | 0.00 | 2093.84 | 2093.84 | 0.08771013 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11801.550 | 11801.550 | 1.680132 | 0.00010325 | 251.166 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.5289 | 1.559630 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11801.55 | 11801.55 | 1.0000 | 1.93874663 | 1.680132 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10323457 | 60.00 | 32.22 | 27.78 | 0.000 | 11801.55 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00728714 | 21.00 | 0.00728714 | 45.2008 | 3316.05 | 0.00 | 11867.41 | 11867.41 | 1.93874663 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.60 | 15.45 | 0.00800000 | 43055.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15033.733 | 15033.733 | 0.897087 | 0.00013152 | 356.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.9476 | 1.986778 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15033.73 | 15033.73 | 1.0000 | 1.03517132 | 0.897087 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13150824 | 60.00 | 32.22 | 27.78 | 0.000 | 15033.73 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00758381 | 21.00 | 0.00758381 | 47.0172 | 10499.99 | 0.00 | 15113.62 | 15113.62 | 1.03517132 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.92 | 18.34 | 0.00800000 | 51534.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37540.040 | 37540.040 | 2.630762 | 0.00032842 | 865.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 4.8632 | 4.961092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37540.04 | 37540.04 | 1.0000 | 3.03570153 | 2.630762 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.32838314 | 60.00 | 32.22 | 27.78 | 0.000 | 37540.04 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00749144 | 21.00 | 0.00749144 | 46.4489 | 24244.08 | 0.00 | 37741.24 | 37741.24 | 3.03570153 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.79 | 17.63 | 0.00800000 | 49367.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14495.747 | -999.000 | 1.335336 | 0.00041457 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8723 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.335336 | 1.54087734 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 1.5402 | 1.540124 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 14495.75 | 14089.91 | 1.0000 | 1.54087734 | 1.335336 | 21.71 | 15.25 | 0.00862438 | 43729.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.41452651 | 6.70 | 15.03 | 8.33 | 0.000 | 14495.75 | 28.16 | 0.01272245 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00862438 | 21.11 | 0.00862438 | 53.0144 | 13069.33 | 0.00 | 15125.72 | 15125.72 | 1.54087734 | 21.71 | 15.67 | 0.00862438 | 43729.7 | 12.09 | 11.93 | 0.00862438 | 33913.4 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9463.759 | 9463.759 | 0.425741 | 0.00008279 | 270.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.335336 | 1.54087734 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.2260 | 1.250680 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9463.76 | 9463.76 | 1.0000 | 0.49127326 | 0.425741 | 21.11 | 14.04 | 0.00752186 | 40317.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08278465 | 60.00 | 32.22 | 27.78 | 0.000 | 9463.76 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752186 | 21.11 | 0.00752186 | 46.3226 | 9463.76 | 0.00 | 10201.88 | 10201.88 | 0.49127326 | 16.60 | 12.68 | 0.00752186 | 35724.2 | 36.98 | 19.91 | 0.00752186 | 56490.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13831.410 | -999.000 | 1.272192 | 0.00039557 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8828 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.272192 | 1.46801451 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 1.4696 | 1.469540 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 13831.41 | 13427.05 | 1.0000 | 1.46801451 | 1.272192 | 21.71 | 15.25 | 0.00863004 | 43744.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.39552883 | 6.70 | 15.03 | 8.33 | 0.000 | 13831.41 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00863004 | 21.11 | 0.00863004 | 53.0488 | 12451.31 | 0.00 | 14431.86 | 14431.86 | 1.46801451 | 21.71 | 15.68 | 0.00863004 | 43744.0 | 12.08 | 11.93 | 0.00863004 | 33913.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9471.634 | 9471.634 | 0.426095 | 0.00008286 | 270.664 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.272192 | 1.46801451 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.2270 | 1.251721 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9471.63 | 9471.63 | 1.0000 | 0.49168207 | 0.426095 | 21.11 | 14.04 | 0.00752227 | 40318.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08285354 | 60.00 | 32.22 | 27.78 | 0.000 | 9471.63 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752227 | 21.11 | 0.00752227 | 46.3251 | 9471.63 | 0.00 | 10210.36 | 10210.36 | 0.49168207 | 16.60 | 12.68 | 0.00752227 | 35725.2 | 36.98 | 19.91 | 0.00752227 | 56491.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 90230.743 | -999.000 | 8.467059 | 0.00258054 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7458 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.467059 | 9.77034953 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 9.5869 | 9.586710 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 90230.74 | 89069.30 | 1.0000 | 9.77034953 | 8.467059 | 21.71 | 15.19 | 0.00855631 | 43557.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.58027639 | 6.70 | 15.03 | 8.33 | 0.000 | 90230.74 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00855631 | 21.11 | 0.00855631 | 52.5998 | 82875.44 | 0.00 | 94178.07 | 94178.07 | 9.77034953 | 21.71 | 15.61 | 0.00855631 | 43557.4 | 12.26 | 11.93 | 0.00855631 | 33918.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53515.972 | 53515.972 | 2.407652 | 0.00046818 | 1529.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.467059 | 9.77034953 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 6.9329 | 7.072386 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53515.97 | 53515.97 | 1.0000 | 2.77824954 | 2.407652 | 21.11 | 14.07 | 0.00755007 | 40390.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.46813331 | 60.00 | 32.22 | 27.78 | 0.000 | 53515.97 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755007 | 21.11 | 0.00755007 | 46.4907 | 53515.97 | 0.00 | 57691.07 | 57691.07 | 2.77824954 | 16.60 | 12.71 | 0.00755007 | 35795.6 | 36.98 | 19.93 | 0.00755007 | 56560.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 71645.487 | -999.000 | 6.292386 | 0.00204901 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2088 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.292386 | 7.26094090 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 7.6122 | 7.612089 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 71645.49 | 66912.80 | 1.0000 | 7.26094090 | 6.292386 | 21.71 | 15.40 | 0.00880541 | 44189.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.04880457 | 6.70 | 15.03 | 8.33 | 0.000 | 71645.49 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00880541 | 21.11 | 0.00880541 | 54.1119 | 61584.87 | 0.00 | 74678.78 | 71776.19 | 7.26094090 | 21.71 | 15.83 | 0.00880541 | 44189.4 | 12.03 | 11.93 | 0.00864698 | 33904.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53680.194 | 53680.194 | 2.415040 | 0.00046962 | 1533.974 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.292386 | 7.26094090 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 6.9541 | 7.094089 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53680.19 | 53680.19 | 1.0000 | 2.78677504 | 2.415040 | 21.11 | 14.07 | 0.00755125 | 40393.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.46956985 | 60.00 | 32.22 | 27.78 | 0.000 | 53680.19 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755125 | 21.11 | 0.00755125 | 46.4979 | 53680.19 | 0.00 | 57868.11 | 57868.11 | 2.78677504 | 16.60 | 12.71 | 0.00755125 | 35798.6 | 36.98 | 19.93 | 0.00755125 | 56563.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13232.891 | -999.000 | 1.214792 | 0.00037845 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8962 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.214792 | 1.40177862 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 1.4060 | 1.405950 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 13232.89 | 12825.33 | 1.0000 | 1.40177862 | 1.214792 | 21.71 | 15.26 | 0.00863722 | 43762.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.37841333 | 6.70 | 15.03 | 8.33 | 0.000 | 13232.89 | 25.39 | 0.01271761 | 19.73 | 0.00000000 | 0.0000 | 21.11 | 0.00863722 | 21.11 | 0.00863722 | 53.0923 | 11889.50 | 0.00 | 13806.57 | 13806.57 | 1.40177862 | 21.71 | 15.68 | 0.00863722 | 43762.3 | 12.06 | 11.93 | 0.00863722 | 33912.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9480.440 | 9480.440 | 0.426492 | 0.00008294 | 270.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.214792 | 1.40177862 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.2282 | 1.252885 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9480.44 | 9480.44 | 1.0000 | 0.49213921 | 0.426492 | 21.11 | 14.04 | 0.00752265 | 40319.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08293057 | 60.00 | 32.22 | 27.78 | 0.000 | 9480.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752265 | 21.11 | 0.00752265 | 46.3274 | 9480.44 | 0.00 | 10219.86 | 10219.86 | 0.49213921 | 16.60 | 12.68 | 0.00752265 | 35726.2 | 36.98 | 19.91 | 0.00752265 | 56492.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12587.235 | -999.000 | 1.153212 | 0.00035999 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9100 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.153212 | 1.33072055 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 1.3374 | 1.337351 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 12587.23 | 12179.22 | 1.0000 | 1.33072055 | 1.153212 | 21.71 | 15.26 | 0.00864466 | 43781.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.35994987 | 6.70 | 15.03 | 8.33 | 0.000 | 12587.23 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00864466 | 21.11 | 0.00864466 | 53.1374 | 11286.80 | 0.00 | 13132.16 | 13132.16 | 1.33072055 | 21.71 | 15.69 | 0.00864466 | 43781.2 | 12.04 | 11.93 | 0.00864466 | 33912.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9488.314 | 9488.314 | 0.426846 | 0.00008301 | 271.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.153212 | 1.33072055 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.2292 | 1.253925 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9488.31 | 9488.31 | 1.0000 | 0.49254794 | 0.426846 | 21.11 | 14.04 | 0.00752306 | 40320.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08299944 | 60.00 | 32.22 | 27.78 | 0.000 | 9488.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752306 | 21.11 | 0.00752306 | 46.3299 | 9488.31 | 0.00 | 10228.35 | 10228.35 | 0.49254794 | 16.60 | 12.68 | 0.00752306 | 35727.2 | 36.98 | 19.91 | 0.00752306 | 56493.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18430.101 | 18430.101 | 0.845834 | 0.00016123 | 465.861 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 2.3876 | 2.435624 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 18430.10 | 18430.10 | 1.0000 | 0.97602929 | 0.845834 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.16121812 | 60.00 | 32.22 | 27.78 | 0.000 | 18430.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760669 | 21.00 | 0.00760669 | 47.1535 | 14153.88 | 0.00 | 18524.80 | 18524.80 | 0.97602929 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.21 | 19.72 | 0.00800000 | 55914.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3765.885 | -999.000 | 0.347370 | 0.00010770 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8632 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.347370 | 0.40083845 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 0.4001 | 0.400113 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3765.89 | 3664.49 | 1.0000 | 0.40083845 | 0.347370 | 21.71 | 15.24 | 0.00861948 | 43717.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.10769084 | 6.70 | 15.03 | 8.33 | 0.000 | 3765.89 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00861948 | 21.11 | 0.00861948 | 52.9847 | 3399.81 | 0.00 | 3929.17 | 3929.17 | 0.40083845 | 21.71 | 15.67 | 0.00861948 | 43717.2 | 12.11 | 11.93 | 0.00861948 | 33914.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2844.596 | 2844.596 | 0.127969 | 0.00002489 | 81.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.347370 | 0.40083845 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.3685 | 0.375927 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2844.60 | 2844.60 | 1.0000 | 0.14766633 | 0.127969 | 21.11 | 14.11 | 0.00759809 | 40511.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02488323 | 60.00 | 32.22 | 27.78 | 0.000 | 2844.60 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00759809 | 21.11 | 0.00759809 | 46.7862 | 2844.60 | 0.00 | 3066.46 | 3066.46 | 0.14766633 | 16.60 | 12.76 | 0.00759809 | 35917.2 | 36.98 | 19.97 | 0.00759809 | 56683.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3578.351 | -999.000 | 0.329521 | 0.00010234 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8747 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.329521 | 0.38024254 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 0.3802 | 0.380188 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3578.35 | 3477.17 | 1.0000 | 0.38024254 | 0.329521 | 21.71 | 15.25 | 0.00862565 | 43732.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.10232803 | 6.70 | 15.03 | 8.33 | 0.000 | 3578.35 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00862565 | 21.11 | 0.00862565 | 53.0221 | 3225.12 | 0.00 | 3733.82 | 3733.82 | 0.38024254 | 21.71 | 15.67 | 0.00862565 | 43732.9 | 12.09 | 11.93 | 0.00862565 | 33913.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2844.825 | 2844.825 | 0.127979 | 0.00002489 | 81.291 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.329521 | 0.38024254 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 0.3685 | 0.375957 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2844.82 | 2844.82 | 1.0000 | 0.14767822 | 0.127979 | 21.11 | 14.11 | 0.00759815 | 40511.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02488523 | 60.00 | 32.22 | 27.78 | 0.000 | 2844.82 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00759815 | 21.11 | 0.00759815 | 46.7866 | 2844.82 | 0.00 | 3066.71 | 3066.71 | 0.14767822 | 16.60 | 12.76 | 0.00759815 | 35917.3 | 36.98 | 19.97 | 0.00759815 | 56683.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18642.784 | -999.000 | 1.700327 | 0.00053317 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9413 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.700327 | 1.96204925 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 1.9808 | 1.980732 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 18642.78 | 17970.58 | 1.0000 | 1.96204925 | 1.700327 | 21.71 | 15.28 | 0.00866152 | 43823.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.53311691 | 6.70 | 15.03 | 8.33 | 0.000 | 18642.78 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00866152 | 21.11 | 0.00866152 | 53.2400 | 16641.35 | 0.00 | 19447.34 | 19447.34 | 1.96204925 | 21.71 | 15.71 | 0.00866152 | 43823.9 | 12.00 | 11.93 | 0.00866152 | 33912.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13583.590 | 13583.590 | 0.611094 | 0.00011884 | 388.150 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.700327 | 1.96204925 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.7597 | 1.795135 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13583.59 | 13583.59 | 1.0000 | 0.70515676 | 0.611094 | 21.11 | 14.12 | 0.00761173 | 40546.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11882305 | 60.00 | 32.22 | 27.78 | 0.000 | 13583.59 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00761173 | 21.11 | 0.00761173 | 46.8680 | 13583.59 | 0.00 | 14643.15 | 14643.15 | 0.70515676 | 16.60 | 12.77 | 0.00761173 | 35951.7 | 36.98 | 19.98 | 0.00761173 | 56717.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14612.706 | 14612.706 | 1.098591 | 0.00012784 | 333.096 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.8930 | 1.931138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14612.71 | 14612.71 | 1.0000 | 1.26769121 | 1.098591 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12782529 | 60.00 | 32.22 | 27.78 | 0.000 | 14612.71 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00768635 | 21.00 | 0.00768635 | 47.6426 | 9058.43 | 0.00 | 14691.32 | 14691.32 | 1.26769121 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.97 | 17.35 | 0.00800000 | 48523.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15052.504 | 15052.504 | 1.151310 | 0.00013169 | 342.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.9500 | 1.989259 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 15052.50 | 15052.50 | 1.0000 | 1.32852467 | 1.151310 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13167244 | 60.00 | 32.22 | 27.78 | 0.000 | 15052.50 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769200 | 21.00 | 0.00769200 | 47.6772 | 9231.63 | 0.00 | 15133.56 | 15133.56 | 1.32852467 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.77 | 17.28 | 0.00800000 | 48326.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10059.656 | 10059.656 | 1.184762 | 0.00008801 | 217.450 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.3032 | 1.329431 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 10059.66 | 10059.66 | 1.0000 | 1.36712600 | 1.184762 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08799728 | 60.00 | 32.22 | 27.78 | 0.000 | 10059.66 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.75 | 0.00714387 | 21.00 | 0.00714387 | 44.3249 | 4078.98 | 0.00 | 10115.53 | 10115.53 | 1.36712600 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.86 | 15.90 | 0.00800000 | 44333.9 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11540.772 | 11540.772 | 0.420981 | 0.00010096 | 314.968 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 1.4951 | 1.525167 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 11540.77 | 11540.77 | 1.0000 | 0.48578095 | 0.420981 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10095341 | 60.00 | 32.22 | 27.78 | 0.000 | 11540.77 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00773383 | 21.00 | 0.00773383 | 47.9326 | 9412.05 | 0.00 | 11598.00 | 11598.00 | 0.48578095 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 629632.909 | -999.000 | 23.439359 | 0.01800742 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6128 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.439359 | 27.04725887 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 66.8976 | 66.897606 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 629632.91 | 444688.09 | 1.0000 | 27.04725887 | 23.439359 | 27.03 | 19.09 | 0.01117449 | 55668.8 | 10.91 | 10.91 | 0.00850000 | 32389.9 | 18.00558456 | 6.70 | 15.03 | 8.33 | 52519.133 | 577113.78 | 30.10 | 0.01272586 | 21.13 | 11.66146000 | 49.7516 | 23.99 | 0.00963792 | 23.99 | 0.00959526 | 49.4335 | 308882.96 | 0.00 | 646868.14 | 441812.24 | 27.04725887 | 27.03 | 19.57 | 0.01117449 | 55668.8 | 11.10 | 11.05 | 0.00816788 | 31752.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 402787.895 | 402787.895 | 7.031808 | 0.00352376 | 5605.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.439359 | 27.04725887 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 52.1802 | 53.230306 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 402787.90 | 402787.90 | 1.0000 | 8.11417766 | 7.031808 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.52340476 | 60.00 | 32.22 | 27.78 | 0.000 | 402787.90 | -32.70 | 0.00018338 | -32.70 | 11.66146000 | 165.8387 | 20.98 | 0.00760087 | 21.00 | 0.00757500 | 46.9578 | 93943.34 | 0.00 | 279056.13 | 279056.13 | 8.11417766 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 26.91514056 | 15.03 | 6.70 | 8.33 | 941189.01 | 7.3896 | 7.389598 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 1.98892074 | 6.70 | 15.03 | 8.33 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00866583 | 21.11 | 0.00866497 | 53.2596 | 200948.51 | 0.00 | 71135.90 | 45208.06 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.53 | 11.45 | 0.00838330 | 32732.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 6.61917058 | 54.44 | 82.22 | 27.78 | 771917.71 | 4.5666 | 4.658500 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00755085 | 21.11 | 0.00755107 | 46.4969 | 164373.32 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 23.44 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1023.17 | 6947.67 | 604.17 |
RETAIL_1_FLR_1 | 3575.67 | 7610.33 | 2804.33 |
RETAIL_2_FLR_1 | 2225.83 | 7288.00 | 1544.67 |
MECH_FLR_1 | 2971.83 | 7936.33 | 2720.33 |
STORAGE_FLR_1 | 3066.83 | 8352.33 | 2985.50 |
LAUNDRY_FLR_1 | 6591.33 | 3669.00 | 2630.50 |
CAFE_FLR_1 | 3554.83 | 6577.17 | 2054.17 |
LOBBY_FLR_1 | 2519.67 | 6478.00 | 1296.33 |
ROOM_1_FLR_3 | 3656.33 | 8273.83 | 3520.17 |
ROOM_2_FLR_3 | 4535.50 | 8080.33 | 4188.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3304.67 | 8648.33 | 3282.33 |
ROOM_5_FLR_3 | 3542.67 | 8198.33 | 3458.17 |
ROOM_6_FLR_3 | 4311.17 | 7961.50 | 4021.33 |
CORRIDOR_FLR_3 | 2854.17 | 8392.33 | 2788.00 |
ROOM_1_FLR_6 | 4109.67 | 8212.83 | 3921.33 |
ROOM_2_FLR_6 | 4916.33 | 8067.33 | 4567.83 |
ROOM_3_MULT9_FLR_6 | 3089.17 | 8163.17 | 2914.17 |
BANQUET_FLR_6 | 3686.00 | 4314.17 | 1004.67 |
DINING_FLR_6 | 4130.33 | 3378.50 | 831.50 |
KITCHEN_FLR_6 | 7901.00 | 6288.17 | 5814.67 |
CORRIDOR_FLR_6 | 3095.00 | 7722.67 | 2589.33 |
Facility | 8758.83 | 8760.00 | 7954.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 209.33 | 0.00 | 209.33 | 0.00 |
RETAIL_1_FLR_1 | 398.67 | 0.00 | 398.67 | 0.00 |
RETAIL_2_FLR_1 | 361.00 | 0.00 | 361.00 | 0.00 |
MECH_FLR_1 | 439.00 | 0.00 | 439.00 | 0.00 |
STORAGE_FLR_1 | 533.50 | 0.00 | 533.50 | 0.00 |
LAUNDRY_FLR_1 | 231.83 | 0.00 | 231.83 | 0.00 |
CAFE_FLR_1 | 353.50 | 0.00 | 353.50 | 0.00 |
LOBBY_FLR_1 | 328.67 | 0.00 | 328.67 | 0.00 |
ROOM_1_FLR_3 | 12.67 | 2.33 | 12.67 | 2.33 |
ROOM_2_FLR_3 | 42.33 | 6.83 | 42.33 | 6.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 149.17 | 16.83 | 149.17 | 16.83 |
ROOM_5_FLR_3 | 23.00 | 0.50 | 23.00 | 0.50 |
ROOM_6_FLR_3 | 58.50 | 14.67 | 58.50 | 14.67 |
CORRIDOR_FLR_3 | 395.00 | 0.00 | 395.00 | 0.00 |
ROOM_1_FLR_6 | 19.83 | 5.83 | 19.83 | 5.83 |
ROOM_2_FLR_6 | 59.50 | 12.67 | 59.50 | 12.67 |
ROOM_3_MULT9_FLR_6 | 1.33 | 2.17 | 1.33 | 2.17 |
BANQUET_FLR_6 | 119.33 | 0.00 | 119.33 | 0.00 |
DINING_FLR_6 | 106.67 | 0.00 | 106.67 | 0.00 |
KITCHEN_FLR_6 | 150.83 | 0.00 | 150.83 | 0.00 |
CORRIDOR_FLR_6 | 412.50 | 0.00 | 412.50 | 0.00 |
Facility | 579.17 | 40.17 | 579.17 | 40.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.001 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.136 | 0.142 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.415 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.513 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.525 | 0.053 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.421 | 0.153 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 4.455 | 0.112 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.890 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.184 | 0.000 | 0.041 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.184 | 0.000 | 0.031 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.082 | 0.000 | 0.068 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.184 | 0.000 | 0.041 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.184 | 0.000 | 0.042 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.650 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.184 | 0.000 | 0.048 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.184 | 0.000 | 0.033 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.150 | 0.000 | 0.076 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.718 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 5.111 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.189 | 0.153 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.201 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.646 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.062 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.337 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.493 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.474 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.437 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.112 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.554 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.497 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.796 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.980 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.950 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.019 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41593394.45 | 0.00 | 41593394.45 | 0.00 | 41593394.45 | 26946214.98 | 0.17 | 0.33 | 8759.50 | 0.00 |
RETAIL_1_FLR_1 | 7216655.93 | 0.00 | 7216655.93 | 326761.06 | 7543416.99 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3757959.95 | 0.00 | 3757959.95 | 126130.18 | 3884090.13 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2887381.17 | 0.00 | 2887381.17 | 298096.82 | 3185477.99 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1707293.60 | 0.00 | 1707293.60 | 171985.45 | 1879279.05 | 1821682.01 | 8757.00 | 0.83 | 2.17 | 0.00 |
LAUNDRY_FLR_1 | 62420988.95 | 0.00 | 62420988.95 | 407035.98 | 62828024.93 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28759910.55 | 0.00 | 28759910.55 | 722323.83 | 29482234.38 | 21330615.53 | 1.33 | 0.17 | 8758.50 | 0.00 |
LOBBY_FLR_1 | 84388230.94 | 0.00 | 84388230.94 | 2063844.16 | 86452075.10 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 41793.23 | 1501949.94 | 189663.05 | 1691612.99 | 1946875.62 | 2190.00 | 6051.00 | 519.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 31375.04 | 1491360.68 | 189648.58 | 1681009.25 | 1946647.51 | 2190.00 | 6199.84 | 370.16 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 151.06 | 1100063.03 | 52918.12 | 1152981.15 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 367.17 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 43429.53 | 19847258.82 | 52932.59 | 19900191.41 | 26405105.73 | 2190.00 | 6064.25 | 505.75 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 41873.29 | 1502030.00 | 189663.05 | 1691693.05 | 1946875.62 | 2190.00 | 6051.00 | 519.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 42480.09 | 1502465.73 | 189648.58 | 1692114.30 | 1946647.51 | 2190.00 | 6065.16 | 504.84 | 0.00 |
CORRIDOR_FLR_3 | 26688112.23 | 0.00 | 26688112.23 | 229340.78 | 26917453.01 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 49206.67 | 414245.84 | 189704.08 | 603949.92 | 486718.90 | 2061.07 | 6051.05 | 647.88 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 33140.45 | 398136.86 | 189689.61 | 587826.46 | 486661.88 | 2105.12 | 6225.82 | 429.06 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 49168.81 | 2394359.12 | 97059.25 | 2491418.37 | 3126920.42 | 2190.00 | 6050.33 | 519.67 | 0.00 |
BANQUET_FLR_6 | 40896632.61 | 0.00 | 40896632.61 | 463209.69 | 41359842.30 | 37458366.31 | 4482.34 | 190.92 | 4086.74 | 0.00 |
DINING_FLR_6 | 44284362.26 | 0.00 | 44284362.26 | 463209.69 | 44747571.94 | 37458366.31 | 3247.17 | 189.39 | 5323.44 | 0.00 |
KITCHEN_FLR_6 | 59913320.58 | 0.00 | 59913320.58 | 414680.06 | 60328000.64 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13045576.91 | 0.00 | 13045576.91 | 405865.71 | 13451442.61 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4467077.77 | 0.21E+10 | 19112579.17 | 0.22E+10 | 0.43E+10 | 8760.00 | 6719.32 | 8760.00 | 367.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3189 | 0.0000 | 1.3189 | 0.0000 | 1.3189 | 0.8545 | 0.17 | 0.33 | 8759.50 |
RETAIL_1_FLR_1 | 0.2288 | 0.0000 | 0.2288 | 0.0104 | 0.2392 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1192 | 0.0000 | 0.1192 | 0.0040 | 0.1232 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0916 | 0.0000 | 0.0916 | 0.0095 | 0.1010 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0541 | 0.0000 | 0.0541 | 0.0055 | 0.0596 | 0.0578 | 8757.00 | 0.83 | 2.17 |
LAUNDRY_FLR_1 | 1.9794 | 0.0000 | 1.9794 | 0.0129 | 1.9923 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9120 | 0.0000 | 0.9120 | 0.0229 | 0.9349 | 0.6764 | 1.33 | 0.17 | 8758.50 |
LOBBY_FLR_1 | 2.6759 | 0.0000 | 2.6759 | 0.0654 | 2.7414 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0060 | 0.0536 | 0.0617 | 2190.00 | 6051.00 | 519.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0060 | 0.0533 | 0.0617 | 2190.00 | 6199.84 | 370.16 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0014 | 0.6294 | 0.0017 | 0.6310 | 0.8373 | 2190.00 | 6064.25 | 505.75 |
ROOM_5_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0060 | 0.0536 | 0.0617 | 2190.00 | 6051.00 | 519.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0060 | 0.0537 | 0.0617 | 2190.00 | 6065.16 | 504.84 |
CORRIDOR_FLR_3 | 0.8463 | 0.0000 | 0.8463 | 0.0073 | 0.8535 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0016 | 0.0131 | 0.0060 | 0.0192 | 0.0154 | 2061.07 | 6051.05 | 647.88 |
ROOM_2_FLR_6 | 0.0116 | 0.0011 | 0.0126 | 0.0060 | 0.0186 | 0.0154 | 2105.12 | 6225.82 | 429.06 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0016 | 0.0759 | 0.0031 | 0.0790 | 0.0992 | 2190.00 | 6050.33 | 519.67 |
BANQUET_FLR_6 | 1.2968 | 0.0000 | 1.2968 | 0.0147 | 1.3115 | 1.1878 | 4482.34 | 190.92 | 4086.74 |
DINING_FLR_6 | 1.4042 | 0.0000 | 1.4042 | 0.0147 | 1.4189 | 1.1878 | 3247.17 | 189.39 | 5323.44 |
KITCHEN_FLR_6 | 1.8998 | 0.0000 | 1.8998 | 0.0131 | 1.9130 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4137 | 0.0000 | 0.4137 | 0.0129 | 0.4265 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.9389 | 0.1413 | 65.0802 | 0.4785 | 65.5587 | 73.9670 | 8760.00 | 6719.32 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 39705603.39 | 332618.16 | 40038221.56 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.6306 | 0.0000 | 17.6306 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2591 | 0.0105 | 1.2696 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3219.65 | 0.00 | 0.00 | 0.00 | 5540.35 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.3320 | 0.0000 | 0.0000 | 0.0000 | 17.2262 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5904 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
Electricity:Building | 2446.22 | 31038.60 | 03-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.12 | 30897.46 | 03-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.19 | 269.39 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.85 | 66.17 | 03-JUN-05:00 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.85 | 66.17 | 03-JUN-05:00 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.66 | 3093.58 | 27-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.67 | 982.16 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.67 | 982.16 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.36 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.36 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.02 | 870.63 | 05-JAN-23:30 | 3263.15 | 19-SEP-06:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 830.73 | 2495.65 | 03-APR-03:00 | 220492.80 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.21 | 0.00 | 01-JAN-11:10 | 1895.12 | 23-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.72 | 589.43 | 06-JAN-04:10 | 1203.64 | 14-AUG-13:10 |
Fans:Electricity | 513.37 | 10449.95 | 19-FEB-08:10 | 34142.78 | 30-JUN-20:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 728.08 | 12195.49 | 20-NOV-15:00 | 44777.78 | 30-JUN-19:20 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.95 | 03-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
ElectricityNet:Plant | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 4817.48 | 70486.36 | 07-OCT-03:00 | 420897.03 | 29-JUN-18:10 |
General:Fans:Electricity | 513.37 | 10449.95 | 19-FEB-08:10 | 34142.78 | 30-JUN-20:10 |
ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 192.94 | 0.00 | 04-FEB-14:10 | 9938.94 | 01-JAN-00:40 |
General:HeatRecovery:Electricity | 192.94 | 0.00 | 04-FEB-14:10 | 9938.94 | 01-JAN-00:40 |
WaterSystems:Electricity | 90.76 | 1086.57 | 25-JUL-00:50 | 4744.57 | 05-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.57 | 25-JUL-00:50 | 4744.57 | 05-JAN-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 604.18 | 0.00 | 01-JAN-00:10 | 206994.12 | 29-JUN-18:10 |
General:Cooling:Electricity | 604.18 | 0.00 | 01-JAN-00:10 | 206994.12 | 29-JUN-18:10 |
Pumps:Electricity | 81.86 | 47.92 | 03-OCT-10:10 | 6577.80 | 29-JUN-18:10 |
General:Pumps:Electricity | 81.86 | 47.92 | 03-OCT-10:10 | 6577.80 | 29-JUN-18:10 |
WIRED_LTG_ELECTRICITY | 27.49 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8582.64 | 29270.80 | 14-APR-01:50 | 1151998.84 | 05-JAN-21:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 6793.80 | 15908.90 | 03-MAY-10:10 | 1076875.08 | 05-JAN-21:40 |
WaterSystems:NaturalGas | 3482.46 | 15908.90 | 01-JAN-16:10 | 311635.74 | 27-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 3482.46 | 15908.90 | 01-JAN-16:10 | 311635.74 | 27-FEB-21:20 |
Heating:NaturalGas | 3311.35 | 0.00 | 10-APR-19:10 | 833562.85 | 06-JAN-05:00 |
Boiler:Heating:NaturalGas | 3311.35 | 0.00 | 10-APR-19:10 | 833562.85 | 06-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1846.75 | 0.00 | 01-JAN-00:10 | 662455.29 | 21-JUL-19:20 |
PlantLoopCoolingDemand:HVAC | 1846.75 | 0.00 | 01-JAN-00:10 | 662455.29 | 21-JUL-19:20 |
CoolingCoils:PlantLoopCoolingDemand | 1846.75 | 0.00 | 01-JAN-00:10 | 662455.29 | 21-JUL-19:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 07-MAR-01:40 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 07-MAR-01:40 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22544.55 | 138666.07 | 21-NOV-12:50 | 2845088.80 | 29-JUN-18:10 |
EnergyTransfer:Building | 4945.22 | 66463.43 | 09-JAN-11:10 | 361496.76 | 30-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 700.81 | 5605.85 | 07-JAN-04:20 | 37168.99 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 179.07 | 1860.89 | 06-JAN-04:00 | 10368.79 | 19-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.53 | 930.45 | 06-JAN-04:00 | 5184.40 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer | 89.53 | 930.45 | 06-JAN-04:00 | 5184.40 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.53 | 930.45 | 06-JAN-04:00 | 5184.40 | 19-SEP-06:30 |
EnergyTransfer:Plant | 7938.74 | 19225.45 | 24-SEP-01:50 | 1565252.06 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.50 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.03 | 718.28 | 06-JAN-04:10 | 2560.93 | 14-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 396.18 | 26.93 | 06-JAN-15:00 | 32744.28 | 02-DEC-06:00 |
Heating:EnergyTransfer | 472.06 | 0.00 | 08-FEB-11:30 | 136184.16 | 21-DEC-11:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1879.17 | 06-JAN-13:40 |
General:Heating:EnergyTransfer | 472.06 | 0.00 | 08-FEB-11:30 | 136184.16 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1879.17 | 06-JAN-13:40 |
Cooling:EnergyTransfer | 4383.62 | 18980.95 | 09-JAN-10:50 | 358792.51 | 30-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 396.18 | 0.00 | 06-JAN-13:40 | 32744.28 | 02-DEC-06:00 |
General:Cooling:EnergyTransfer | 4383.62 | 18980.95 | 09-JAN-10:50 | 358792.51 | 30-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 396.18 | 0.00 | 06-JAN-13:40 | 32744.28 | 02-DEC-06:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.49 | 0.00 | 15-MAR-21:40 | 5127.01 | 22-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 5.59 | 0.00 | 01-JAN-00:40 | 2835.50 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 5.59 | 0.00 | 01-JAN-00:40 | 2835.50 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 5127.01 | 22-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 5127.01 | 22-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 29.75 | 0.20 | 22-DEC-09:30 | 2125.68 | 30-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 985.25 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 985.25 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 29.59 | 0.00 | 01-JAN-10:30 | 2125.68 | 30-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 29.59 | 0.00 | 01-JAN-10:30 | 2125.68 | 30-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 19.92 | 0.07 | 30-DEC-23:40 | 1706.66 | 30-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 3.95 | 0.00 | 16-JAN-19:10 | 1670.47 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 3.95 | 0.00 | 16-JAN-19:10 | 1670.47 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.97 | 0.00 | 01-JAN-00:10 | 1706.66 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.97 | 0.00 | 01-JAN-00:10 | 1706.66 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.29 | 0.00 | 18-MAR-15:40 | 1089.58 | 06-JAN-13:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.94 | 0.00 | 18-JAN-21:50 | 1089.58 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.94 | 0.00 | 18-JAN-21:50 | 1089.58 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.36 | 0.00 | 01-JAN-00:10 | 824.15 | 30-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.36 | 0.00 | 01-JAN-00:10 | 824.15 | 30-JUN-19:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.10 | 2571.97 | 07-JAN-04:30 | 38897.26 | 29-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1323.74 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1323.74 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.10 | 1437.85 | 14-JAN-05:00 | 38897.26 | 29-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 583.10 | 1437.85 | 14-JAN-05:00 | 38897.26 | 29-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 216.12 | 2.56 | 08-DEC-08:40 | 18012.44 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.46 | 0.00 | 01-JAN-00:10 | 6629.37 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.46 | 0.00 | 01-JAN-00:10 | 6629.37 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.66 | 0.00 | 06-JAN-16:00 | 18012.44 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.66 | 0.00 | 06-JAN-16:00 | 18012.44 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 719.05 | 0.37 | 07-JAN-16:00 | 41385.93 | 29-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.77 | 0.00 | 01-JAN-00:10 | 15752.00 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.77 | 0.00 | 01-JAN-00:10 | 15752.00 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 718.28 | 0.00 | 06-JAN-13:30 | 41385.93 | 29-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 718.28 | 0.00 | 06-JAN-13:30 | 41385.93 | 29-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 81.50 | 0.00 | 01-JAN-11:10 | 13951.38 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 40.03 | 0.00 | 01-JAN-11:10 | 7932.33 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 40.03 | 0.00 | 01-JAN-11:10 | 7932.33 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.47 | 0.00 | 01-JAN-00:10 | 13951.38 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.47 | 0.00 | 01-JAN-00:10 | 13951.38 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 75.98 | 0.00 | 15-JAN-18:10 | 13818.78 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.57 | 0.00 | 15-JAN-18:10 | 8457.30 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.57 | 0.00 | 15-JAN-18:10 | 8457.30 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.42 | 0.00 | 01-JAN-00:10 | 13818.78 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.42 | 0.00 | 01-JAN-00:10 | 13818.78 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 263.86 | 0.00 | 01-JAN-00:10 | 68215.57 | 22-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 31.47 | 0.00 | 01-JAN-00:10 | 30712.07 | 24-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 31.47 | 0.00 | 01-JAN-00:10 | 30712.07 | 24-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 232.39 | 0.00 | 01-JAN-00:10 | 68215.57 | 22-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 232.39 | 0.00 | 01-JAN-00:10 | 68215.57 | 22-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 407.42 | 0.00 | 01-JAN-08:10 | 73768.76 | 05-JUL-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 157.54 | 0.00 | 01-JAN-08:10 | 47798.27 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 157.54 | 0.00 | 01-JAN-08:10 | 47798.27 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 249.88 | 0.00 | 01-JAN-00:10 | 73768.76 | 05-JUL-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 249.88 | 0.00 | 01-JAN-00:10 | 73768.76 | 05-JUL-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 80.82 | 0.00 | 01-JAN-11:10 | 12554.20 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.86 | 0.00 | 01-JAN-11:10 | 7967.82 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.86 | 0.00 | 01-JAN-11:10 | 7967.82 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 40.96 | 0.00 | 01-JAN-00:10 | 12554.20 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 40.96 | 0.00 | 01-JAN-00:10 | 12554.20 | 29-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.30 | 0.00 | 02-JAN-11:10 | 13662.75 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 47.44 | 0.00 | 02-JAN-11:10 | 8710.63 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 47.44 | 0.00 | 02-JAN-11:10 | 8710.63 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.85 | 0.00 | 01-JAN-00:10 | 13662.75 | 19-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.85 | 0.00 | 01-JAN-00:10 | 13662.75 | 19-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.15 | 0.31 | 02-DEC-15:20 | 12117.75 | 30-JUN-19:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 11.36 | 0.00 | 01-JAN-00:40 | 8888.40 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 11.36 | 0.00 | 01-JAN-00:40 | 8888.40 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 151.79 | 0.00 | 01-JAN-00:10 | 12117.75 | 30-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 151.79 | 0.00 | 01-JAN-00:10 | 12117.75 | 30-JUN-19:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.94 | 0.00 | 01-JAN-14:40 | 3693.99 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.69 | 0.00 | 01-JAN-14:40 | 2425.03 | 18-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.69 | 0.00 | 01-JAN-14:40 | 2425.03 | 18-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.25 | 0.00 | 01-JAN-00:10 | 3693.99 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.25 | 0.00 | 01-JAN-00:10 | 3693.99 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 23.09 | 0.00 | 16-JAN-08:10 | 3979.10 | 06-MAY-19:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.95 | 0.00 | 16-JAN-08:10 | 2541.11 | 18-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.95 | 0.00 | 16-JAN-08:10 | 2541.11 | 18-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.14 | 0.00 | 01-JAN-00:10 | 3979.10 | 06-MAY-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.14 | 0.00 | 01-JAN-00:10 | 3979.10 | 06-MAY-19:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 105.23 | 0.00 | 01-JAN-11:10 | 17979.03 | 25-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 40.95 | 0.00 | 01-JAN-10:20 | 10741.24 | 11-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 40.95 | 0.00 | 01-JAN-10:20 | 10741.24 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 64.28 | 0.00 | 01-JAN-00:10 | 17979.03 | 25-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 64.28 | 0.00 | 01-JAN-00:10 | 17979.03 | 25-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 403.27 | 429.83 | 06-JAN-15:00 | 23311.19 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4541.75 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4541.75 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 403.24 | 0.00 | 06-JAN-13:40 | 23311.19 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 403.24 | 0.00 | 06-JAN-13:40 | 23311.19 | 24-FEB-23:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 443.49 | 172.29 | 06-JAN-14:20 | 25733.84 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4233.77 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4233.77 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 443.47 | 0.00 | 06-JAN-13:40 | 25733.84 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 443.47 | 0.00 | 06-JAN-13:40 | 25733.84 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 530.81 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 530.81 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.28 | 2971.70 | 07-JAN-04:20 | 32098.81 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.28 | 2971.70 | 07-JAN-04:20 | 32098.81 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 80.44 | 0.13 | 02-MAR-23:00 | 6871.00 | 30-JUN-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 11.27 | 0.00 | 02-JAN-12:30 | 6245.51 | 07-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 11.27 | 0.00 | 02-JAN-12:30 | 6245.51 | 07-JAN-04:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 69.17 | 0.00 | 01-JAN-00:10 | 6871.00 | 30-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 69.17 | 0.00 | 01-JAN-00:10 | 6871.00 | 30-JUN-13:20 |
PlantLoopHeatingDemand:Facility | 3420.92 | 10734.37 | 17-AUG-02:10 | 736260.50 | 06-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 900.58 | 10726.85 | 25-AUG-03:00 | 66772.53 | 01-MAR-07:10 |
WaterSystems:PlantLoopHeatingDemand | 900.58 | 10726.85 | 25-AUG-03:00 | 66772.53 | 01-MAR-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 900.58 | 10726.85 | 25-AUG-03:00 | 66772.53 | 01-MAR-07:10 |
EnergyTransfer:HVAC | 9660.59 | 866.42 | 19-SEP-14:40 | 918556.57 | 29-JUN-18:10 |
HeatingCoils:EnergyTransfer | 2520.35 | 0.00 | 10-APR-19:10 | 682596.43 | 06-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 2520.35 | 0.00 | 10-APR-19:10 | 682596.43 | 06-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 2520.35 | 0.00 | 10-APR-19:10 | 682596.43 | 06-JAN-05:00 |
CoolingCoils:EnergyTransfer | 1846.75 | 0.00 | 01-JAN-00:10 | 662455.29 | 21-JUL-19:20 |
HeatRecoveryForHeating:EnergyTransfer | 5167.74 | 0.00 | 01-JAN-00:40 | 572180.39 | 24-FEB-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 125.75 | 0.00 | 01-JAN-00:10 | 264101.23 | 29-JUN-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 900.58 | 10726.85 | 25-AUG-03:00 | 66772.53 | 01-MAR-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 900.58 | 10726.85 | 25-AUG-03:00 | 66772.53 | 01-MAR-07:10 |
Boilers:EnergyTransfer | 2514.54 | 0.00 | 10-APR-19:10 | 680027.24 | 06-JAN-05:00 |
Chillers:EnergyTransfer | 1914.95 | 0.00 | 01-JAN-00:10 | 664877.09 | 21-JUL-19:20 |
HeatRejection:EnergyTransfer | 2519.14 | 0.00 | 01-JAN-00:10 | 866089.59 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 2519.14 | 0.00 | 01-JAN-00:10 | 866089.59 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.004 | -396.182 | 0.000 | 0.000 | 142.182 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -50.404 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 5.590 | -33.904 | 0.000 | 0.000 | 15.939 | 7.307 | 10.186 | 28.529 | 0.000 | 0.055 | 0.001 | 0.000 | -14.637 | 0.000 | -7.236 | -11.829 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.160 | -29.586 | 0.000 | 0.000 | 17.375 | 8.462 | 11.795 | 0.000 | 0.000 | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | -2.917 | -5.310 |
MECH_FLR_1 | 0.000 | 0.000 | 3.954 | -15.970 | 0.000 | 0.000 | 3.779 | 8.366 | 12.471 | 0.000 | 0.000 | 0.051 | 0.000 | 0.000 | 0.000 | 0.000 | -6.753 | -5.899 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.936 | -8.356 | 0.000 | 0.000 | 2.938 | 3.079 | 3.598 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -3.861 | -1.366 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.003 | -583.103 | 0.000 | 0.000 | 11.437 | 3.975 | 658.131 | 0.000 | 0.000 | 0.076 | 0.001 | 0.000 | 0.000 | 0.000 | -9.643 | -80.877 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.458 | -215.660 | 0.000 | 0.000 | 199.594 | 13.850 | 14.341 | 79.499 | 0.000 | 0.113 | 0.001 | 0.000 | -42.410 | 0.000 | -16.559 | -33.226 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.772 | -718.284 | 0.000 | 0.000 | 574.414 | 109.666 | 148.998 | 104.696 | 0.000 | 0.332 | 0.004 | 0.000 | -57.610 | 0.000 | -48.391 | -114.592 |
ROOM_1_FLR_3 | 46.543 | -36.153 | 0.000 | -11.822 | 0.000 | 0.000 | 9.763 | 9.244 | 10.478 | 51.672 | 0.000 | 0.243 | 0.000 | 0.000 | -34.548 | 0.000 | -17.237 | -28.183 |
ROOM_2_FLR_3 | 54.321 | -22.800 | 0.000 | -12.372 | 0.000 | 0.000 | 9.611 | 9.243 | 10.477 | 35.262 | 0.000 | 0.175 | 0.000 | 0.000 | -36.869 | 0.000 | -17.544 | -29.504 |
ROOM_3_MULT19_FLR_3 | 31.458 | -220.786 | 0.015 | -11.607 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 329.075 | 0.000 | 0.159 | 0.001 | 0.000 | -197.699 | 0.000 | -97.051 | -138.947 |
ROOM_4_MULT19_FLR_3 | 234.211 | -162.812 | 0.000 | -163.723 | 0.000 | 0.000 | 184.102 | 110.415 | 195.050 | 86.944 | 0.000 | 1.136 | 0.000 | 0.000 | -208.544 | 0.000 | -103.216 | -173.564 |
ROOM_5_FLR_3 | 46.359 | -35.639 | 0.000 | -11.826 | 0.000 | 0.000 | 9.758 | 9.244 | 10.478 | 51.144 | 0.000 | 0.244 | 0.000 | 0.000 | -33.949 | 0.000 | -17.265 | -28.547 |
ROOM_6_FLR_3 | 54.229 | -23.383 | 0.000 | -12.254 | 0.000 | 0.000 | 9.659 | 9.243 | 10.477 | 34.545 | 0.000 | 0.176 | 0.000 | 0.000 | -35.941 | 0.000 | -17.724 | -29.027 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 11.360 | -151.787 | 0.000 | 0.000 | 120.166 | 91.336 | 0.000 | 46.689 | 0.000 | 0.156 | 0.004 | 0.000 | -43.915 | 0.000 | -20.745 | -53.260 |
ROOM_1_FLR_6 | 15.417 | -9.020 | 0.000 | -2.952 | 0.000 | 0.000 | 2.444 | 2.311 | 2.620 | 12.864 | 0.000 | 0.062 | 0.000 | 0.000 | -8.621 | 0.000 | -4.330 | -10.794 |
ROOM_2_FLR_6 | 17.713 | -5.794 | 0.000 | -3.103 | 0.000 | 0.000 | 2.400 | 2.311 | 2.619 | 8.768 | 0.000 | 0.043 | 0.000 | 0.000 | -9.220 | 0.000 | -4.399 | -11.339 |
ROOM_3_MULT9_FLR_6 | 50.591 | -54.801 | 0.000 | -19.116 | 0.000 | 0.000 | 21.888 | 13.076 | 23.098 | 73.693 | 0.000 | 0.360 | 0.000 | 0.000 | -39.805 | 0.000 | -20.764 | -48.220 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.030 | -403.247 | 0.000 | 0.000 | 322.523 | 30.499 | 175.857 | 9.108 | 0.000 | 0.060 | 0.000 | 0.000 | -26.340 | 0.000 | -11.390 | -97.101 |
DINING_FLR_6 | 0.000 | 0.000 | 0.019 | -443.477 | 0.000 | 0.000 | 320.865 | 30.499 | 175.857 | 8.932 | 0.000 | 0.060 | 0.000 | 0.000 | -26.882 | 0.000 | -11.461 | -54.413 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -611.263 | 0.000 | 0.000 | 28.950 | 12.972 | 550.372 | 24.198 | 0.000 | 0.053 | 21.688 | 0.000 | -16.715 | 0.000 | -10.257 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 11.269 | -69.171 | 0.000 | 0.000 | 31.916 | 24.166 | 0.000 | 23.257 | 0.000 | 0.058 | 7.179 | 0.000 | -19.496 | 0.000 | -9.177 | -0.001 |
Total Facility | 550.842 | -571.188 | 37.570 | -3928.765 | 0.000 | 0.000 | 2041.703 | 780.945 | 2365.005 | 1008.877 | 0.000 | 3.663 | 28.885 | 0.000 | -853.200 | 0.000 | -457.918 | -1006.403 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-JAN-23:33 | 0.00 | 0.00 | 0.00 | -32935.46 | 0.00 | 0.00 | 7930.89 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 16552.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 22-OCT-12:40 | 0.00 | 0.00 | 0.00 | -5126.77 | 0.00 | 0.00 | 150.60 | 132.80 | 216.51 | 8322.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.57 | -3624.03 |
RETAIL_2_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -2601.40 | 0.00 | 0.00 | 710.73 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 640.10 | 0.00 | -0.00 | 0.00 | -235.37 | 0.00 |
MECH_FLR_1 | 30-JUN-20:00 | 0.00 | 0.00 | 0.00 | -1706.62 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 4.06 | 49.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 30-JUN-19:20 | 0.00 | 0.00 | 0.00 | -824.13 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 15.59 | 215.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -41029.60 | 0.00 | 0.00 | 408.89 | 325.08 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -793.84 | -3209.91 |
CAFE_FLR_1 | 22-OCT-12:00 | 0.00 | 0.00 | 0.00 | -18012.81 | 0.00 | 0.00 | 2968.69 | 124.78 | 406.43 | 23805.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -185.92 | -9106.64 |
LOBBY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -59260.78 | 0.00 | 0.00 | 23423.08 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 26337.28 | 0.00 | -6152.17 | 0.00 | -3881.42 | 0.00 |
ROOM_1_FLR_3 | 04-MAY-15:01 | 0.00 | -17246.16 | 0.00 | -697.63 | 0.00 | 0.00 | 235.29 | 199.23 | 200.18 | 12054.77 | 0.00 | 0.00 | 5424.30 | 0.00 | -0.00 | 0.00 | -169.98 | 0.00 |
ROOM_2_FLR_3 | 06-MAY-19:01 | 0.00 | -19245.31 | 0.00 | -689.24 | 0.00 | 0.00 | 232.89 | 711.45 | 653.15 | 3097.39 | 0.00 | 0.00 | 15537.79 | 0.00 | -0.00 | 0.00 | -298.11 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:30 | 0.00 | -68217.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.75 | 2548.95 | 100277.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1302.50 | -36110.86 |
ROOM_4_MULT19_FLR_3 | 21-MAY-21:01 | 0.00 | -88035.98 | 0.00 | -7707.28 | 0.00 | 0.00 | 6185.67 | 7223.75 | 6668.31 | 0.00 | 0.00 | 0.00 | 82988.25 | 0.00 | -5840.18 | 0.00 | -1482.53 | 0.00 |
ROOM_5_FLR_3 | 04-SEP-18:01 | 0.00 | -15718.15 | 0.00 | -503.67 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 0.00 | 0.00 | 0.00 | 15472.94 | 0.00 | -500.90 | 0.00 | -229.62 | 0.00 |
ROOM_6_FLR_3 | 31-JUL-08:32 | 0.00 | -16382.71 | 0.00 | -925.24 | 0.00 | 0.00 | 59.33 | 313.04 | 452.99 | 11105.15 | 0.00 | 0.00 | 5587.76 | 0.00 | -0.00 | 0.00 | -210.31 | 0.00 |
CORRIDOR_FLR_3 | 30-JUN-19:20 | 0.00 | 0.00 | 0.00 | -12117.96 | 0.00 | 0.00 | 4080.33 | 7469.27 | 0.00 | 2758.60 | 0.00 | 81.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2272.08 |
ROOM_1_FLR_6 | 04-MAY-15:01 | 0.00 | -4488.99 | 0.00 | -174.64 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 2998.26 | 0.00 | 0.00 | 1558.12 | 0.00 | -0.00 | 0.00 | -51.42 | 0.00 |
ROOM_2_FLR_6 | 06-MAY-18:42 | 0.00 | -5304.68 | 0.00 | -195.81 | 0.00 | 0.00 | 47.81 | 177.86 | 121.15 | 1401.94 | 0.00 | 0.00 | 3831.63 | 0.00 | -0.00 | 0.00 | -79.90 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-APR-15:01 | 0.00 | -22136.05 | 0.00 | -1070.62 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 9737.14 | 0.00 | 0.00 | 13010.63 | 0.00 | -0.00 | 0.00 | -793.58 | 0.00 |
BANQUET_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -26405.14 | 0.00 | 0.00 | 12671.87 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 7303.63 | 0.00 | -2409.16 | 0.00 | -897.14 | 0.00 |
DINING_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -28066.54 | 0.00 | 0.00 | 12418.37 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 9259.71 | 0.00 | -2444.70 | 0.00 | -902.77 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -32107.99 | 0.00 | 0.00 | 464.23 | 353.60 | 24259.91 | 4731.51 | 0.00 | 49.59 | 2249.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-JUN-13:20 | 0.00 | 0.00 | 0.00 | -6871.80 | 0.00 | 0.00 | 308.45 | 548.96 | 0.00 | 4095.53 | 0.00 | 100.35 | 1818.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-18:02 | 0.00 | -186140.24 | 0.00 | -204594.06 | 0.00 | 0.00 | 74565.63 | 52987.32 | 120482.43 | 75955.56 | 0.00 | 5412.06 | 61331.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-JAN-13:31 | 0.00 | 0.00 | 2538.36 | 0.00 | 0.00 | 0.00 | 2036.92 | 3664.03 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11788.14 |
RETAIL_1_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 3144.26 | 0.00 | 0.00 | 0.00 | 947.62 | 66.40 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1425.49 | 0.00 | -543.37 | -2333.76 |
RETAIL_2_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1073.13 | 0.00 | 0.00 | 0.00 | 241.64 | 192.23 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -211.74 | -1587.76 |
MECH_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1692.62 | 0.00 | 0.00 | 0.00 | 51.82 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -497.13 | -1746.63 |
STORAGE_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1102.48 | 0.00 | 0.00 | 0.00 | 40.35 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -284.11 | -1017.89 |
LAUNDRY_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 7757.28 | 0.00 | 0.00 | 0.00 | 784.38 | 36.12 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -654.75 | -17249.22 |
CAFE_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 8144.17 | 0.00 | 0.00 | 0.00 | 2845.31 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -334.56 | 0.00 | -1196.97 | -9917.55 |
LOBBY_FLR_1 | 09-JAN-10:41 | 0.00 | 0.00 | 18771.26 | 0.00 | 0.00 | 0.00 | 8116.08 | 2270.59 | 3694.97 | 26211.45 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3469.49 | -55594.87 |
ROOM_1_FLR_3 | 25-DEC-16:13 | 9006.99 | 371.45 | 0.00 | -371.45 | 0.00 | 0.00 | 147.99 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2907.14 | 0.00 | -1079.68 | -5624.23 |
ROOM_2_FLR_3 | 05-JAN-08:04 | 9903.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.15 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4445.91 | 0.00 | -1674.14 | -4769.82 |
ROOM_3_MULT19_FLR_3 | 24-DEC-06:00 | 30711.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21316.61 | 0.00 | -8093.38 | -5569.52 |
ROOM_4_MULT19_FLR_3 | 06-JAN-16:02 | 48786.71 | 3453.01 | 0.00 | -3453.01 | 0.00 | 0.00 | 5585.67 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17641.68 | 0.00 | -6910.98 | -35925.72 |
ROOM_5_FLR_3 | 06-JAN-08:04 | 9544.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.95 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4397.75 | 0.00 | -1792.51 | -4342.65 |
ROOM_6_FLR_3 | 06-JAN-08:03 | 9676.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.21 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4340.23 | 0.00 | -1790.92 | -4539.61 |
CORRIDOR_FLR_3 | 06-JAN-13:31 | 0.00 | 0.00 | 9180.98 | 0.00 | 0.00 | 0.00 | 1534.64 | 2074.80 | 0.00 | 7586.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1600.93 | -18775.71 |
ROOM_1_FLR_6 | 05-JAN-08:04 | 2887.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.73 | 0.00 | -419.04 | -1588.71 |
ROOM_2_FLR_6 | 06-JAN-08:03 | 2867.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.80 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1079.53 | 0.00 | -448.00 | -1588.42 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:13 | 12395.59 | 603.84 | 0.00 | -603.84 | 0.00 | 0.00 | 599.31 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3617.76 | 0.00 | -1331.49 | -8768.73 |
BANQUET_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6799.71 | 0.00 | 0.00 | 0.00 | 4790.66 | 553.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1544.86 | 0.00 | -785.71 | -16561.05 |
DINING_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6628.87 | 0.00 | 0.00 | 0.00 | 4753.80 | 553.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1566.93 | 0.00 | -790.30 | -16326.68 |
KITCHEN_FLR_6 | 14-JAN-04:51 | 0.00 | 0.00 | 3564.63 | 0.00 | 0.00 | 0.00 | 1922.90 | 117.87 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1701.20 | 0.00 | -706.50 | -8613.68 |
CORRIDOR_FLR_6 | 06-JAN-13:31 | 0.00 | 0.00 | 6370.11 | 0.00 | 0.00 | 0.00 | 414.18 | 548.96 | 0.00 | 4382.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -699.39 | -11016.18 |
Total Facility | 14-JAN-04:51 | 84162.24 | 22961.16 | 50099.66 | -22961.16 | 0.00 | 0.00 | 116680.59 | 7157.90 | 31990.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -82481.03 | 0.00 | -33606.57 | -174003.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.5763 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.4394 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.7881 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6703 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5892 | 2.5892 | 1.2816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4540 | 0.4540 | 0.2247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2379 | 0.2379 | 0.1177 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1845 | 0.1845 | 0.0913 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1093 | 0.1093 | 0.0541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3942 | 3.3942 | 1.6801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8123 | 1.8123 | 0.8971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3147 | 5.3147 | 2.6308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7088 | 1.7088 | 0.8458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2194 | 2.2194 | 1.0986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3259 | 2.3259 | 1.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3935 | 2.3935 | 1.1848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8329 | 0.8329 | 0.4123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.5763 | 23.4394 | 23.5763 | 11.6703 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2946 | 1.2946 | 1.2816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2270 | 0.2270 | 0.2247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1189 | 0.1189 | 0.1177 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0922 | 0.0922 | 0.0913 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0546 | 0.0546 | 0.0541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6971 | 1.6971 | 1.6801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9061 | 0.9061 | 0.8971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6573 | 2.6573 | 2.6308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8544 | 0.8544 | 0.8458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1097 | 1.1097 | 1.0986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1629 | 1.1629 | 1.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1967 | 1.1967 | 1.1848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.4123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.7881 | 11.6703 | 11.6703 | 11.6703 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 579.17 |
Number of hours cooling loads not met | 40.17 |
Number of hours not met | 619.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3311.35 | 833562.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 604.18 | 206994.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 780.95 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.43 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 513.37 | 34142.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 81.86 | 6577.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 192.94 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4744.57 | 3482.46 | 311635.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.21 | 1895.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.72 | 1203.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.20 | 4817.48 |
Natural Gas | 1788.84 | 8582.64 |
Additional | 0.00 | 0.00 |
Total | 3508.04 | 13400.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.83 |
Space Heating | 0.00 |
Space Cooling | 53.25 |
Fans (All) | 45.25 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 424.62 |
Subtotal | 424.62 |
Natural Gas [MJ/m2] | |
Space Heating | 291.87 |
Service Water Heating | 306.95 |
Miscellaneous (All) | 756.49 |
Subtotal | 756.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.83 |
Space Heating | 24.71 |
Space Cooling | 4.51 |
Fans (All) | 3.83 |
Service Water Heating | 26.67 |
Receptacle Equipment | 25.72 |
Miscellaneous | 8.73 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8639.00 | 121.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8293.50 | 466.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8593.67 | 166.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8293.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 466.50 | 0.00 | 0.00 | 0.00 |
Average | 8723.90 | 36.10 | 0.00 | 0.00 | 0.00 |
Sum | 191925.83 | 794.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4112.33 | 41.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4087.50 | 66.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 66.50 | 0.00 | 0.00 | 0.00 |
Average | 288882.13 | 4.92 | 0.00 | 0.00 | 0.00 |
Sum | 6355406.83 | 108.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8694.17 | 65.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8449.83 | 310.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8400.50 | 359.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8544.50 | 215.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8030.67 | 729.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8647.83 | 112.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8480.67 | 279.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8377.83 | 382.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8415.33 | 344.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8030.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 729.33 | 0.00 | 0.00 | 0.00 |
Average | 8629.40 | 130.60 | 0.00 | 0.00 | 0.00 |
Sum | 189846.83 | 2873.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58448.33 | 707.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 671673.50 | 38743.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1987158.33 | 128270.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4052.83 | 101.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4142.00 | 12.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4131.00 | 23.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4004.67 | 149.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1166322.17 | 79392.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1173209.67 | 72505.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107936.83 | 332.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1987158.33 | 128270.67 | 0.00 | 0.00 | 0.00 |
Average | 274330.79 | 14556.26 | 0.00 | 0.00 | 0.00 |
Sum | 6035277.33 | 320237.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344397E+11 | 32935.55 | 25-JAN-23:33 | -28.3 | -28.5 | 0.654451E+10 | 4836.92 | 24-JAN-22:19 | -28.3 | -28.5 |
February | 0.287683E+11 | 30843.32 | 13-FEB-23:01 | -26.2 | -26.5 | 0.642069E+10 | 4757.93 | 10-FEB-22:10 | -26.2 | -26.5 |
March | 0.283742E+11 | 29640.62 | 12-MAR-03:51 | -23.9 | -24.1 | 0.709625E+10 | 4599.22 | 01-MAR-22:10 | -23.9 | -24.1 |
April | 0.271355E+11 | 13331.27 | 22-APR-10:33 | 14.43 | 5.29 | 0.687996E+10 | 4425.78 | 26-APR-21:10 | 0.00 | -0.6 |
May | 0.298098E+11 | 14062.36 | 18-MAY-10:33 | 26.07 | 16.42 | 0.728226E+10 | 4542.13 | 12-MAY-22:10 | 26.07 | 16.42 |
June | 0.304700E+11 | 14823.36 | 25-JUN-10:33 | 27.43 | 22.06 | 0.725420E+10 | 4668.49 | 23-JUN-22:10 | 27.43 | 22.06 |
July | 0.340297E+11 | 15685.68 | 23-JUL-10:33 | 27.77 | 23.32 | 0.785729E+10 | 4837.10 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.367754E+11 | 19583.00 | 31-AUG-21:00 | 22.80 | 20.41 | 0.815362E+10 | 4837.09 | 11-AUG-22:10 | 22.80 | 20.41 |
September | 0.367426E+11 | 20828.08 | 08-SEP-21:00 | 11.70 | 7.35 | 0.792922E+10 | 4837.08 | 01-SEP-21:40 | 11.70 | 7.35 |
October | 0.378353E+11 | 21239.67 | 20-OCT-21:00 | 6.10 | 4.28 | 0.819859E+10 | 4837.06 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.353093E+11 | 20498.46 | 17-NOV-22:00 | 2.80 | -0.9 | 0.791169E+10 | 4837.15 | 01-NOV-01:10 | 2.80 | -0.9 |
December | 0.364911E+11 | 32744.28 | 02-DEC-06:00 | -27.8 | -28.0 | 0.715086E+10 | 4837.04 | 01-DEC-00:20 | -27.8 | -28.0 |
Annual Sum or Average | 0.396181E+12 | 0.886792E+11 | ||||||||
Minimum of Months | 0.271355E+11 | 13331.27 | -28.3 | -28.5 | 0.642069E+10 | 4425.78 | -28.3 | -28.5 | ||
Maximum of Months | 0.378353E+11 | 32935.55 | 27.77 | 23.32 | 0.819859E+10 | 4837.15 | 27.43 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387874E+09 | 2159.36 | 27-JAN-13:40 | -14.8 | -15.9 | 0.547340E+09 | 364.18 | 11-JAN-03:09 | -14.8 | -15.9 |
February | 0.109913E+10 | 3615.97 | 28-FEB-13:30 | 3.05 | -0.7 | 0.544761E+09 | 364.28 | 13-FEB-05:30 | 3.05 | -0.7 |
March | 0.161829E+10 | 3483.38 | 20-MAR-12:30 | 1.70 | -1.1 | 0.626831E+09 | 378.83 | 31-MAR-21:30 | 4.75 | 0.82 |
April | 0.284097E+10 | 3855.70 | 13-APR-13:10 | 17.98 | 6.86 | 0.624238E+09 | 429.24 | 13-APR-21:30 | 12.50 | 6.57 |
May | 0.445491E+10 | 3854.61 | 18-MAY-13:10 | 28.25 | 16.75 | 0.670260E+09 | 462.15 | 25-MAY-21:19 | 22.50 | 16.44 |
June | 0.469619E+10 | 3971.34 | 30-JUN-13:00 | 31.70 | 24.46 | 0.663070E+09 | 480.25 | 29-JUN-21:19 | 31.70 | 24.46 |
July | 0.539612E+10 | 4092.05 | 23-JUL-13:10 | 30.00 | 22.77 | 0.708478E+09 | 468.17 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.520853E+10 | 4480.13 | 26-AUG-12:40 | 25.40 | 19.23 | 0.698990E+09 | 464.57 | 08-AUG-21:19 | 25.40 | 19.23 |
September | 0.420963E+10 | 4496.55 | 01-SEP-13:15 | 24.80 | 18.00 | 0.641278E+09 | 451.33 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.266949E+10 | 5127.01 | 22-OCT-12:40 | 17.77 | 12.92 | 0.638759E+09 | 437.12 | 19-OCT-21:30 | 17.77 | 12.92 |
November | 0.106226E+10 | 3432.39 | 17-NOV-12:40 | 9.63 | 3.12 | 0.603734E+09 | 364.88 | 17-NOV-22:19 | 2.43 | -1.1 |
December | 0.260514E+09 | 2376.70 | 10-DEC-12:26 | -23.6 | -24.1 | 0.568035E+09 | 364.18 | 14-DEC-01:00 | -20.5 | -20.9 |
Annual Sum or Average | 0.339039E+11 | 0.753577E+10 | ||||||||
Minimum of Months | 0.260514E+09 | 2159.36 | -23.6 | -24.1 | 0.544761E+09 | 364.18 | -20.5 | -20.9 | ||
Maximum of Months | 0.539612E+10 | 5127.01 | 31.70 | 24.46 | 0.708478E+09 | 480.25 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153431E+10 | 2601.46 | 25-JAN-20:01 | -24.0 | -24.2 | 0.676864E+09 | 479.36 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.169867E+10 | 2168.05 | 24-FEB-22:52 | -23.9 | -24.3 | 0.667116E+09 | 518.45 | 22-FEB-22:30 | -23.9 | -24.3 |
March | 0.216495E+10 | 2074.57 | 07-MAR-00:41 | -23.8 | -24.0 | 0.783615E+09 | 541.81 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.251135E+10 | 1411.82 | 13-APR-21:00 | 13.30 | 6.73 | 0.819799E+09 | 569.53 | 12-APR-21:30 | 13.30 | 6.73 |
May | 0.299196E+10 | 1897.83 | 25-MAY-20:55 | 22.80 | 16.44 | 0.908632E+09 | 569.55 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.305035E+10 | 2125.68 | 30-JUN-20:10 | 23.77 | 17.76 | 0.894037E+09 | 569.55 | 15-JUN-21:40 | 23.77 | 17.76 |
July | 0.333199E+10 | 2001.82 | 24-JUL-20:05 | 21.32 | 18.93 | 0.941905E+09 | 569.55 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.321575E+10 | 1895.88 | 25-AUG-21:00 | 17.80 | 16.38 | 0.938044E+09 | 569.55 | 01-AUG-21:30 | 17.80 | 16.38 |
September | 0.283844E+10 | 1812.86 | 01-SEP-20:10 | 16.42 | 15.15 | 0.874989E+09 | 569.55 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.258462E+10 | 1472.49 | 19-OCT-21:00 | 12.80 | 9.78 | 0.846875E+09 | 569.52 | 20-OCT-21:19 | 6.10 | 4.28 |
November | 0.210874E+10 | 1169.69 | 17-NOV-21:00 | 3.30 | -0.9 | 0.757686E+09 | 536.29 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.155434E+10 | 1693.17 | 02-DEC-00:22 | -23.8 | -24.0 | 0.699236E+09 | 481.34 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.295855E+11 | 0.980880E+10 | ||||||||
Minimum of Months | 0.153431E+10 | 1169.69 | -24.0 | -24.3 | 0.667116E+09 | 479.36 | -24.0 | -24.3 | ||
Maximum of Months | 0.333199E+10 | 2601.46 | 23.77 | 18.93 | 0.941905E+09 | 569.55 | 23.77 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34305035.26 | 585.47 | 19-JAN-22:00 | -3.9 | -4.6 | 0.140957E+09 | 89.14 | 23-JAN-04:10 | -23.2 | -23.4 |
February | 0.181076E+09 | 694.81 | 21-FEB-21:00 | -1.1 | -2.5 | 0.135700E+09 | 92.32 | 21-FEB-22:10 | -3.0 | -4.4 |
March | 0.544427E+09 | 751.43 | 28-MAR-20:00 | 4.40 | 0.82 | 0.152864E+09 | 96.35 | 28-MAR-21:10 | 0.22 | -1.8 |
April | 0.145134E+10 | 904.23 | 18-APR-10:33 | 17.57 | 11.16 | 0.154560E+09 | 105.64 | 14-APR-21:10 | 17.57 | 11.16 |
May | 0.211802E+10 | 1106.06 | 25-MAY-20:55 | 22.80 | 16.44 | 0.180428E+09 | 120.45 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.225975E+10 | 1706.66 | 30-JUN-20:00 | 24.40 | 17.93 | 0.183477E+09 | 120.45 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.247248E+10 | 1487.38 | 24-JUL-19:55 | 21.70 | 19.11 | 0.196568E+09 | 120.45 | 01-JUL-01:10 | 21.70 | 19.11 |
August | 0.234833E+10 | 1240.43 | 09-AUG-19:54 | 23.30 | 19.93 | 0.193073E+09 | 120.45 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.204089E+10 | 1116.71 | 01-SEP-10:33 | 22.77 | 18.04 | 0.175006E+09 | 120.45 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.167575E+10 | 971.21 | 22-OCT-10:33 | 15.20 | 11.90 | 0.162483E+09 | 108.30 | 20-OCT-21:10 | 15.20 | 11.90 |
November | 0.793778E+09 | 763.06 | 01-NOV-20:00 | 13.30 | 11.34 | 0.147859E+09 | 98.10 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 49877511.02 | 623.90 | 05-DEC-21:00 | 0.00 | -0.0 | 0.146397E+09 | 89.35 | 05-DEC-22:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.159700E+11 | 0.196937E+10 | ||||||||
Minimum of Months | 34305035.26 | 585.47 | -3.9 | -4.6 | 0.135700E+09 | 89.14 | -23.2 | -23.4 | ||
Maximum of Months | 0.247248E+10 | 1706.66 | 24.40 | 19.93 | 0.196568E+09 | 120.45 | 21.73 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 455849.37 | 63.12 | 19-JAN-22:00 | -3.9 | -4.6 | 0.106355E+09 | 68.57 | 25-JAN-04:49 | -23.6 | -23.8 |
February | 30292288.27 | 288.98 | 21-FEB-21:40 | -2.2 | -3.7 | 0.103851E+09 | 68.57 | 13-FEB-05:30 | -2.2 | -3.7 |
March | 0.160252E+09 | 416.13 | 28-MAR-20:00 | 4.40 | 0.82 | 0.117023E+09 | 70.97 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.696019E+09 | 525.92 | 18-APR-10:33 | 17.57 | 11.16 | 0.116408E+09 | 78.91 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.120260E+10 | 633.34 | 18-MAY-10:33 | 26.07 | 16.42 | 0.134804E+09 | 90.01 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.128397E+10 | 824.15 | 30-JUN-19:20 | 26.67 | 18.68 | 0.137593E+09 | 92.66 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.140610E+10 | 688.98 | 23-JUL-10:33 | 27.77 | 23.32 | 0.147528E+09 | 92.66 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.134148E+10 | 655.24 | 26-AUG-10:33 | 22.43 | 17.42 | 0.144393E+09 | 90.94 | 09-AUG-22:10 | 22.43 | 17.42 |
September | 0.115687E+10 | 646.99 | 01-SEP-10:33 | 22.77 | 18.04 | 0.130232E+09 | 89.37 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.834665E+09 | 562.29 | 22-OCT-10:33 | 15.20 | 11.90 | 0.121679E+09 | 79.44 | 20-OCT-21:40 | 15.20 | 11.90 |
November | 0.241862E+09 | 424.07 | 01-NOV-20:00 | 13.30 | 11.34 | 0.113013E+09 | 72.52 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 1362937.38 | 125.02 | 05-DEC-22:00 | 0.00 | -0.0 | 0.111048E+09 | 68.57 | 13-DEC-04:19 | -23.7 | -24.0 |
Annual Sum or Average | 0.835593E+10 | 0.148393E+10 | ||||||||
Minimum of Months | 455849.37 | 63.12 | -3.9 | -4.6 | 0.103851E+09 | 68.57 | -23.7 | -24.0 | ||
Maximum of Months | 0.140610E+10 | 824.15 | 27.77 | 23.32 | 0.147528E+09 | 92.66 | 22.43 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462693E+11 | 41039.85 | 25-JAN-20:01 | -24.0 | -24.2 | 0.481793E+09 | 381.61 | 23-JAN-22:10 | -24.0 | -24.2 |
February | 0.422652E+11 | 39200.35 | 13-FEB-21:22 | -23.9 | -24.3 | 0.491221E+09 | 381.58 | 22-FEB-22:10 | -6.1 | -7.6 |
March | 0.477888E+11 | 37112.01 | 31-MAR-20:00 | 5.60 | 1.28 | 0.578032E+09 | 381.60 | 29-MAR-21:10 | 5.60 | 1.28 |
April | 0.479101E+11 | 37890.16 | 13-APR-20:00 | 14.40 | 6.82 | 0.575947E+09 | 381.66 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.515839E+11 | 38660.10 | 18-MAY-20:00 | 21.10 | 14.14 | 0.601052E+09 | 381.65 | 10-MAY-21:10 | 21.10 | 14.14 |
June | 0.507244E+11 | 38897.26 | 29-JUN-20:00 | 28.90 | 23.29 | 0.583249E+09 | 381.73 | 08-JUN-21:10 | 28.90 | 23.29 |
July | 0.526580E+11 | 38746.25 | 21-JUL-19:55 | 22.20 | 20.61 | 0.602623E+09 | 381.69 | 18-JUL-21:19 | 22.20 | 20.61 |
August | 0.523982E+11 | 38662.07 | 08-AUG-20:00 | 25.00 | 20.33 | 0.603156E+09 | 381.71 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.494679E+11 | 38452.45 | 01-SEP-20:00 | 16.70 | 15.32 | 0.580817E+09 | 381.70 | 12-SEP-21:10 | 9.03 | 7.48 |
October | 0.495112E+11 | 37892.37 | 19-OCT-20:00 | 13.30 | 10.24 | 0.595915E+09 | 381.67 | 20-OCT-21:10 | 6.10 | 4.28 |
November | 0.463106E+11 | 37195.14 | 01-NOV-20:00 | 13.30 | 11.34 | 0.570941E+09 | 381.63 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 0.462127E+11 | 39380.63 | 23-DEC-21:42 | -23.9 | -24.3 | 0.506940E+09 | 381.60 | 04-DEC-22:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.583100E+12 | 0.677169E+10 | ||||||||
Minimum of Months | 0.422652E+11 | 37112.01 | -24.0 | -24.3 | 0.481793E+09 | 381.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.526580E+11 | 41039.85 | 28.90 | 23.29 | 0.603156E+09 | 381.73 | 28.90 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111529E+11 | 9423.53 | 27-JAN-13:30 | -15.0 | -16.1 | 0.749479E+10 | 5236.02 | 19-JAN-22:40 | -15.0 | -16.1 |
February | 0.131136E+11 | 13492.24 | 28-FEB-13:30 | 3.05 | -0.7 | 0.750808E+10 | 6009.78 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.159699E+11 | 12952.39 | 20-MAR-12:30 | 1.70 | -1.1 | 0.883144E+10 | 6144.85 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.187147E+11 | 14384.33 | 22-APR-13:10 | 16.38 | 6.81 | 0.910713E+10 | 6460.70 | 13-APR-22:30 | 16.38 | 6.81 |
May | 0.220409E+11 | 13196.84 | 06-MAY-13:00 | 15.30 | 7.47 | 0.100367E+11 | 6462.76 | 26-MAY-22:10 | 16.75 | 14.05 |
June | 0.221500E+11 | 13001.35 | 30-JUN-15:03 | 32.12 | 24.53 | 0.991021E+10 | 6462.78 | 15-JUN-21:40 | 32.12 | 24.53 |
July | 0.241363E+11 | 14256.42 | 29-JUL-13:00 | 28.90 | 20.61 | 0.104479E+11 | 6462.78 | 26-JUL-21:30 | 28.90 | 20.61 |
August | 0.238427E+11 | 15630.91 | 26-AUG-12:40 | 25.40 | 19.23 | 0.104371E+11 | 6462.78 | 01-AUG-21:30 | 25.40 | 19.23 |
September | 0.213925E+11 | 15184.18 | 01-SEP-13:15 | 24.80 | 18.00 | 0.966352E+10 | 6462.70 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.187732E+11 | 18012.44 | 22-OCT-12:00 | 16.70 | 12.57 | 0.932707E+10 | 6461.56 | 19-OCT-23:19 | 16.70 | 12.57 |
November | 0.140853E+11 | 12822.74 | 17-NOV-12:40 | 9.63 | 3.12 | 0.840206E+10 | 6056.31 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.102857E+11 | 10802.45 | 10-DEC-12:24 | -23.6 | -24.1 | 0.770807E+10 | 5301.96 | 05-DEC-22:40 | -23.6 | -24.1 |
Annual Sum or Average | 0.215658E+12 | 0.108874E+12 | ||||||||
Minimum of Months | 0.102857E+11 | 9423.53 | -23.6 | -24.1 | 0.749479E+10 | 5236.02 | -23.6 | -24.1 | ||
Maximum of Months | 0.241363E+11 | 18012.44 | 32.12 | 24.53 | 0.104479E+11 | 6462.78 | 32.12 | 24.53 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455389E+11 | 59262.70 | 25-JAN-20:01 | -24.0 | -24.2 | 0.235322E+11 | 17186.38 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.458456E+11 | 57724.67 | 24-FEB-22:52 | -23.9 | -24.3 | 0.235453E+11 | 18466.12 | 22-FEB-22:49 | -23.9 | -24.3 |
March | 0.540454E+11 | 59034.79 | 07-MAR-00:51 | -24.4 | -24.6 | 0.277774E+11 | 19106.39 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.592594E+11 | 32949.91 | 13-APR-21:10 | 13.03 | 6.68 | 0.287475E+11 | 19184.74 | 13-APR-23:19 | 10.20 | 6.25 |
May | 0.690697E+11 | 38770.07 | 25-MAY-21:10 | 22.65 | 16.44 | 0.313377E+11 | 19186.20 | 26-MAY-22:10 | 16.75 | 14.05 |
June | 0.702165E+11 | 41385.93 | 29-JUN-21:10 | 27.62 | 23.70 | 0.307300E+11 | 19186.24 | 15-JUN-21:40 | 27.62 | 23.70 |
July | 0.759592E+11 | 40008.64 | 24-JUL-20:05 | 21.32 | 18.93 | 0.320293E+11 | 19186.25 | 06-JUL-22:10 | 21.32 | 18.93 |
August | 0.742754E+11 | 39280.19 | 08-AUG-21:05 | 22.62 | 18.95 | 0.320917E+11 | 19186.23 | 01-AUG-21:30 | 22.62 | 18.95 |
September | 0.663643E+11 | 38357.51 | 01-SEP-21:10 | 14.82 | 14.12 | 0.303853E+11 | 19186.11 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.612451E+11 | 34944.57 | 19-OCT-21:10 | 12.70 | 9.80 | 0.297936E+11 | 19184.88 | 20-OCT-23:19 | 7.20 | 5.55 |
November | 0.516484E+11 | 27106.86 | 17-NOV-21:00 | 3.30 | -0.9 | 0.269165E+11 | 19064.87 | 17-NOV-22:49 | 1.88 | -1.3 |
December | 0.448120E+11 | 51439.91 | 02-DEC-00:31 | -23.9 | -24.2 | 0.244260E+11 | 17283.29 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.718280E+12 | 0.341313E+12 | ||||||||
Minimum of Months | 0.448120E+11 | 27106.86 | -24.4 | -24.6 | 0.235322E+11 | 17186.38 | -24.0 | -24.3 | ||
Maximum of Months | 0.759592E+11 | 59262.70 | 27.62 | 23.70 | 0.320917E+11 | 19186.25 | 27.62 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2656725.91 | 1851.27 | 27-JAN-16:01 | -14.8 | -15.9 | 92336234.75 | 56.69 | 14-JAN-05:10 | -14.8 | -15.9 |
February | 53187891.83 | 4312.17 | 20-FEB-16:01 | 8.62 | 2.77 | 84695368.30 | 56.69 | 24-FEB-04:19 | -20.6 | -21.2 |
March | 0.187309E+09 | 4367.37 | 26-MAR-15:01 | 10.68 | 5.32 | 94853668.37 | 56.69 | 07-MAR-05:40 | 10.68 | 5.32 |
April | 0.632741E+09 | 4453.43 | 13-APR-15:01 | 20.00 | 8.11 | 93615171.76 | 56.69 | 13-APR-22:30 | 11.15 | 6.35 |
May | 0.164040E+10 | 4486.11 | 04-MAY-15:01 | 20.98 | 10.71 | 98696500.21 | 56.70 | 25-MAY-23:19 | 20.60 | 16.22 |
June | 0.195714E+10 | 4451.59 | 16-JUN-18:01 | 20.50 | 11.25 | 95699365.45 | 56.70 | 30-JUN-01:49 | 26.70 | 23.80 |
July | 0.247200E+10 | 3832.91 | 30-JUL-15:02 | 24.40 | 20.33 | 98977512.66 | 56.70 | 25-JUL-21:30 | 24.40 | 20.33 |
August | 0.199597E+10 | 3846.51 | 30-AUG-18:01 | 23.53 | 19.54 | 98848132.07 | 56.70 | 23-AUG-21:40 | 23.53 | 19.54 |
September | 0.106861E+10 | 4445.97 | 04-SEP-18:01 | 14.03 | 8.92 | 94932467.49 | 56.70 | 01-SEP-21:30 | 14.03 | 8.92 |
October | 0.336398E+09 | 4283.17 | 09-OCT-15:01 | 6.70 | 1.60 | 95843924.22 | 56.69 | 19-OCT-22:10 | 12.20 | 9.87 |
November | 18726629.49 | 4252.76 | 17-NOV-16:01 | 9.45 | 2.90 | 90768179.99 | 56.69 | 01-NOV-01:19 | 9.45 | 2.90 |
December | 1254170.27 | 82.31 | 02-DEC-14:00 | -18.1 | -18.9 | 92328465.44 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.103664E+11 | 0.113159E+10 | ||||||||
Minimum of Months | 1254170.27 | 82.31 | -18.1 | -18.9 | 84695368.30 | 56.69 | -20.6 | -21.2 | ||
Maximum of Months | 0.247200E+10 | 4486.11 | 24.40 | 20.33 | 98977512.66 | 56.70 | 26.70 | 23.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70460.35 | 556.52 | 17-JAN-16:04 | -4.2 | -5.3 | 91752239.83 | 56.69 | 10-JAN-04:19 | -4.2 | -5.3 |
February | 10346592.11 | 3879.95 | 08-FEB-16:01 | 4.22 | -1.0 | 83745603.49 | 56.69 | 28-FEB-04:19 | -15.6 | -16.0 |
March | 77260087.83 | 4111.12 | 28-MAR-18:01 | 6.93 | 2.56 | 93648555.23 | 56.69 | 07-MAR-05:49 | 6.93 | 2.56 |
April | 0.351933E+09 | 4871.05 | 11-APR-18:11 | 13.90 | 5.53 | 93950636.30 | 75.67 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.119227E+10 | 4983.64 | 06-MAY-19:01 | 14.13 | 6.69 | 0.105269E+09 | 91.16 | 04-MAY-18:10 | 14.13 | 6.69 |
June | 0.150082E+10 | 4191.35 | 20-JUN-21:51 | 13.90 | 11.62 | 0.105674E+09 | 93.71 | 15-JUN-18:10 | 13.90 | 11.62 |
July | 0.187593E+10 | 4443.74 | 04-JUL-16:51 | 25.00 | 20.01 | 0.110692E+09 | 101.34 | 06-JUL-18:10 | 23.12 | 15.53 |
August | 0.136682E+10 | 4412.46 | 07-AUG-16:21 | 24.15 | 19.94 | 0.108844E+09 | 96.09 | 02-AUG-18:10 | 24.15 | 19.94 |
September | 0.602548E+09 | 4771.68 | 04-SEP-18:01 | 14.03 | 8.92 | 98387900.71 | 85.27 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 0.120368E+09 | 3876.96 | 21-OCT-18:32 | 12.40 | 7.64 | 95489774.85 | 56.69 | 19-OCT-21:10 | 12.40 | 7.64 |
November | 6235542.39 | 2548.99 | 17-NOV-16:01 | 9.45 | 2.90 | 89948464.06 | 56.69 | 24-NOV-04:19 | -10.9 | -11.5 |
December | 5457.89 | 50.92 | 05-DEC-19:06 | 0.00 | -0.0 | 92106380.59 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.710461E+10 | 0.116951E+10 | ||||||||
Minimum of Months | 5457.89 | 50.92 | -4.2 | -5.3 | 83745603.49 | 56.69 | -15.6 | -16.0 | ||
Maximum of Months | 0.187593E+10 | 4983.64 | 25.00 | 20.01 | 0.110692E+09 | 101.34 | 24.15 | 19.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3918630.77 | 201.19 | 05-JAN-15:05 | -26.2 | -26.6 | 0.00 | 0.00 | 01-JAN-00:10 | -26.2 | -26.6 |
February | 6646928.00 | 141.16 | 28-FEB-15:05 | 6.10 | 1.55 | 0.00 | 0.00 | 01-FEB-00:10 | 6.10 | 1.55 |
March | 41820666.14 | 463.01 | 29-MAR-12:30 | 2.25 | -0.4 | 0.00 | 0.00 | 01-MAR-00:10 | 2.25 | -0.4 |
April | 0.214185E+09 | 646.84 | 13-APR-13:10 | 17.98 | 6.86 | 0.00 | 0.00 | 01-APR-00:10 | 17.98 | 6.86 |
May | 0.434136E+09 | 630.18 | 18-MAY-13:05 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.492026E+09 | 617.32 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.630570E+09 | 660.31 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.593040E+09 | 733.27 | 25-AUG-13:05 | 27.38 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 18.58 |
September | 0.420704E+09 | 743.83 | 01-SEP-13:05 | 24.60 | 17.97 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 17.97 |
October | 0.204265E+09 | 897.57 | 22-OCT-12:30 | 17.50 | 12.84 | 0.00 | 0.00 | 01-OCT-00:10 | 17.50 | 12.84 |
November | 14896815.10 | 371.38 | 17-NOV-13:30 | 10.30 | 3.32 | 0.00 | 0.00 | 01-NOV-00:10 | 10.30 | 3.32 |
December | 1569815.20 | 75.62 | 02-DEC-15:20 | -17.6 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -17.6 | -18.4 |
Annual Sum or Average | 0.305778E+10 | 0.00 | ||||||||
Minimum of Months | 1569815.20 | 75.62 | -26.2 | -26.6 | 0.00 | 0.00 | -26.2 | -26.6 | ||
Maximum of Months | 0.630570E+09 | 897.57 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1962177.09 | 258.00 | 18-JAN-19:05 | -3.2 | -3.4 | 91168449.03 | 56.69 | 31-JAN-23:49 | -23.3 | -23.7 |
February | 5552237.89 | 281.83 | 05-FEB-09:01 | -2.2 | -3.2 | 84379841.42 | 56.69 | 24-FEB-04:19 | -20.6 | -21.2 |
March | 27211663.30 | 1097.88 | 28-MAR-18:01 | 6.93 | 2.56 | 94493701.19 | 56.69 | 07-MAR-05:30 | 6.93 | 2.56 |
April | 0.170092E+09 | 1175.87 | 13-APR-19:41 | 14.60 | 6.84 | 93331105.10 | 56.69 | 17-APR-21:10 | 7.62 | 3.44 |
May | 0.527249E+09 | 1259.78 | 21-MAY-21:01 | 13.12 | 7.18 | 0.101150E+09 | 76.61 | 26-MAY-21:49 | 16.87 | 14.10 |
June | 0.658391E+09 | 1253.23 | 07-JUN-08:51 | 21.10 | 11.94 | 0.100719E+09 | 79.34 | 15-JUN-21:10 | 14.22 | 10.92 |
July | 0.724782E+09 | 1209.19 | 01-JUL-21:01 | 12.93 | 11.86 | 0.104907E+09 | 79.91 | 26-JUL-21:10 | 13.03 | 11.94 |
August | 0.590080E+09 | 1154.16 | 01-AUG-21:11 | 15.37 | 12.90 | 0.103930E+09 | 77.51 | 01-AUG-21:10 | 15.37 | 12.90 |
September | 0.387084E+09 | 1236.21 | 04-SEP-18:01 | 14.03 | 8.92 | 95877427.85 | 74.93 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.162002E+09 | 1122.70 | 20-OCT-18:11 | 12.23 | 7.41 | 96152987.03 | 56.69 | 19-OCT-21:10 | 12.23 | 7.41 |
November | 31338923.96 | 939.12 | 01-NOV-18:03 | 12.02 | 10.48 | 91500829.95 | 56.69 | 01-NOV-21:30 | 12.25 | 11.18 |
December | 2134917.56 | 273.07 | 06-DEC-19:05 | -7.2 | -7.4 | 92228713.76 | 56.69 | 12-DEC-00:20 | -14.8 | -15.5 |
Annual Sum or Average | 0.328788E+10 | 0.114984E+10 | ||||||||
Minimum of Months | 1962177.09 | 258.00 | -7.2 | -7.4 | 84379841.42 | 56.69 | -23.3 | -23.7 | ||
Maximum of Months | 0.724782E+09 | 1259.78 | 21.10 | 12.90 | 0.104907E+09 | 79.91 | 16.87 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1727041.08 | 82.59 | 27-JAN-13:20 | -15.2 | -16.2 | 92115067.90 | 56.69 | 07-JAN-04:30 | -15.2 | -16.2 |
February | 31836653.12 | 3750.72 | 28-FEB-16:02 | 6.02 | 1.46 | 84675891.13 | 56.69 | 10-FEB-04:19 | 6.02 | 1.46 |
March | 0.142466E+09 | 3940.18 | 31-MAR-15:01 | 8.40 | 2.82 | 95129156.99 | 56.69 | 07-MAR-05:30 | 8.40 | 2.82 |
April | 0.655654E+09 | 4027.66 | 13-APR-15:01 | 20.00 | 8.11 | 94089262.90 | 56.69 | 13-APR-22:19 | 11.33 | 6.36 |
May | 0.154960E+10 | 4053.85 | 03-MAY-15:01 | 21.07 | 10.43 | 98921837.27 | 56.70 | 25-MAY-21:00 | 21.90 | 16.42 |
June | 0.208014E+10 | 4023.56 | 16-JUN-18:01 | 20.50 | 11.25 | 95863353.55 | 56.70 | 30-JUN-22:40 | 18.10 | 14.50 |
July | 0.247025E+10 | 3696.50 | 29-JUL-08:61 | 24.18 | 20.45 | 99063738.09 | 56.70 | 31-JUL-21:00 | 16.40 | 13.37 |
August | 0.192438E+10 | 3611.20 | 24-AUG-08:62 | 18.77 | 17.13 | 98979917.33 | 56.70 | 23-AUG-21:40 | 18.77 | 17.13 |
September | 0.104355E+10 | 4055.47 | 04-SEP-18:01 | 14.03 | 8.92 | 95010902.47 | 56.69 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.307013E+09 | 3946.38 | 09-OCT-08:61 | -1.1 | -2.3 | 95874487.59 | 56.69 | 19-OCT-21:19 | 12.60 | 9.81 |
November | 33725787.70 | 3700.30 | 16-NOV-09:01 | -0.2 | -1.8 | 90688916.05 | 56.69 | 01-NOV-01:19 | -0.2 | -1.8 |
December | 645194.14 | 779.38 | 28-DEC-09:04 | -3.8 | -4.7 | 92263882.72 | 56.69 | 08-DEC-04:19 | -3.8 | -4.7 |
Annual Sum or Average | 0.102410E+11 | 0.113268E+10 | ||||||||
Minimum of Months | 645194.14 | 82.59 | -15.2 | -16.2 | 84675891.13 | 56.69 | -15.2 | -16.2 | ||
Maximum of Months | 0.247025E+10 | 4055.47 | 24.18 | 20.45 | 99063738.09 | 56.70 | 21.90 | 17.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 477.88 | 5.58 | 29-JAN-16:06 | -0.2 | -1.8 | 91433758.87 | 56.69 | 14-JAN-05:10 | -0.2 | -1.8 |
February | 2926218.08 | 758.13 | 28-FEB-09:03 | -9.9 | -10.9 | 83638329.22 | 56.69 | 03-FEB-04:19 | -9.9 | -10.9 |
March | 43337789.15 | 3607.57 | 26-MAR-08:61 | -0.9 | -2.8 | 93774701.55 | 56.69 | 07-MAR-05:30 | -0.9 | -2.8 |
April | 0.371561E+09 | 3827.49 | 22-APR-08:62 | 8.77 | 2.60 | 93893820.00 | 56.69 | 13-APR-21:00 | 8.77 | 2.60 |
May | 0.116132E+10 | 3973.49 | 06-MAY-19:01 | 14.13 | 6.69 | 0.102892E+09 | 76.68 | 18-MAY-21:40 | 17.67 | 12.46 |
June | 0.165217E+10 | 4157.38 | 28-JUN-07:52 | 25.00 | 20.32 | 0.103363E+09 | 80.18 | 15-JUN-21:10 | 25.00 | 20.32 |
July | 0.188548E+10 | 4326.94 | 31-JUL-08:32 | 18.70 | 13.63 | 0.108556E+09 | 80.75 | 26-JUL-21:10 | 18.70 | 13.63 |
August | 0.135198E+10 | 4065.52 | 11-AUG-08:51 | 20.00 | 17.15 | 0.106090E+09 | 77.48 | 04-AUG-21:10 | 20.00 | 17.15 |
September | 0.633341E+09 | 3961.63 | 04-SEP-18:01 | 14.03 | 8.92 | 96755609.98 | 75.05 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.104558E+09 | 3661.73 | 09-OCT-08:61 | -1.1 | -2.3 | 95265040.16 | 56.69 | 18-OCT-04:19 | 1.87 | 1.56 |
November | 6705896.85 | 672.77 | 10-NOV-09:03 | -6.4 | -7.7 | 89925348.68 | 56.69 | 24-NOV-04:19 | -10.9 | -11.5 |
December | 18588.67 | 122.72 | 05-DEC-19:06 | 0.00 | -0.0 | 92005943.37 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.721340E+10 | 0.115759E+10 | ||||||||
Minimum of Months | 477.88 | 5.58 | -9.9 | -10.9 | 83638329.22 | 56.69 | -15.3 | -15.8 | ||
Maximum of Months | 0.188548E+10 | 4326.94 | 25.00 | 20.32 | 0.108556E+09 | 80.75 | 25.00 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749800E+09 | 1704.71 | 26-JAN-07:00 | -33.3 | -33.4 | 0.113686E+10 | 704.47 | 10-JAN-04:00 | -33.3 | -33.4 |
February | 0.104525E+10 | 1728.49 | 14-FEB-07:00 | -33.3 | -33.4 | 0.107191E+10 | 717.09 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.196600E+10 | 1799.68 | 20-MAR-10:33 | 0.03 | -2.1 | 0.120818E+10 | 748.17 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.354678E+10 | 2190.67 | 22-APR-10:33 | 14.43 | 5.29 | 0.122552E+10 | 831.15 | 23-APR-23:19 | 14.27 | 10.45 |
May | 0.485020E+10 | 2503.16 | 18-MAY-10:33 | 26.07 | 16.42 | 0.140822E+10 | 914.52 | 25-MAY-21:49 | 22.05 | 16.43 |
June | 0.506908E+10 | 3029.44 | 30-JUN-19:20 | 26.67 | 18.68 | 0.142463E+10 | 951.85 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.557228E+10 | 2692.34 | 23-JUL-10:33 | 27.77 | 23.32 | 0.152965E+10 | 951.85 | 24-JUL-22:10 | 18.43 | 17.18 |
August | 0.525695E+10 | 2594.22 | 26-AUG-10:33 | 22.43 | 17.42 | 0.148417E+10 | 924.46 | 01-AUG-21:30 | 22.43 | 17.42 |
September | 0.450057E+10 | 2511.77 | 01-SEP-10:33 | 22.77 | 18.04 | 0.133178E+10 | 909.88 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.330233E+10 | 2230.51 | 22-OCT-10:33 | 15.20 | 11.90 | 0.124473E+10 | 813.21 | 22-OCT-23:19 | 6.50 | 5.21 |
November | 0.152823E+10 | 1689.18 | 17-NOV-11:33 | 8.17 | 2.57 | 0.116059E+10 | 726.50 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.559243E+09 | 1382.14 | 24-DEC-23:53 | -31.1 | -31.3 | 0.116137E+10 | 704.49 | 13-DEC-04:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.379467E+11 | 0.153876E+11 | ||||||||
Minimum of Months | 0.559243E+09 | 1382.14 | -33.3 | -33.4 | 0.107191E+10 | 704.47 | -33.3 | -33.4 | ||
Maximum of Months | 0.557228E+10 | 3029.44 | 27.77 | 23.32 | 0.152965E+10 | 951.85 | 22.43 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1103844.53 | 900.68 | 27-JAN-16:01 | -14.8 | -15.9 | 92125967.24 | 56.69 | 07-JAN-04:30 | -14.8 | -15.9 |
February | 50656525.26 | 4467.31 | 08-FEB-16:01 | 4.22 | -1.0 | 84342131.46 | 56.69 | 24-FEB-04:19 | -20.6 | -21.2 |
March | 0.188941E+09 | 4526.85 | 26-MAR-15:01 | 10.68 | 5.32 | 94471876.26 | 56.69 | 14-MAR-03:20 | 10.68 | 5.32 |
April | 0.634862E+09 | 4625.62 | 13-APR-15:01 | 20.00 | 8.11 | 93245867.19 | 56.69 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.164631E+10 | 4663.82 | 04-MAY-15:01 | 20.98 | 10.71 | 98574722.29 | 56.70 | 25-MAY-22:49 | 21.07 | 16.29 |
June | 0.196698E+10 | 4621.52 | 16-JUN-18:01 | 20.50 | 11.25 | 95613486.09 | 56.70 | 28-JUN-22:40 | 22.20 | 18.60 |
July | 0.247396E+10 | 3999.73 | 27-JUL-18:01 | 20.50 | 17.50 | 98901353.95 | 56.70 | 19-JUL-21:49 | 20.50 | 17.50 |
August | 0.196729E+10 | 3955.81 | 14-AUG-18:01 | 21.42 | 17.78 | 98723590.14 | 56.70 | 11-AUG-21:49 | 21.42 | 17.78 |
September | 0.991661E+09 | 4607.83 | 04-SEP-18:01 | 14.03 | 8.92 | 94709653.77 | 56.70 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.310608E+09 | 4438.88 | 09-OCT-15:01 | 6.70 | 1.60 | 95388092.39 | 56.69 | 18-OCT-22:49 | 8.90 | 6.97 |
November | 15143470.28 | 4407.35 | 17-NOV-16:01 | 9.45 | 2.90 | 90330923.22 | 56.69 | 01-NOV-04:19 | 9.45 | 2.90 |
December | 431538.83 | 68.94 | 02-DEC-14:00 | -18.1 | -18.9 | 92213827.03 | 56.69 | 30-DEC-02:20 | -6.7 | -7.6 |
Annual Sum or Average | 0.102479E+11 | 0.112864E+10 | ||||||||
Minimum of Months | 431538.83 | 68.94 | -18.1 | -18.9 | 84342131.46 | 56.69 | -20.6 | -21.2 | ||
Maximum of Months | 0.247396E+10 | 4663.82 | 21.42 | 17.78 | 98901353.95 | 56.70 | 22.20 | 18.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57965.97 | 457.44 | 20-JAN-16:05 | -5.9 | -7.4 | 91527948.15 | 56.69 | 14-JAN-05:10 | -5.9 | -7.4 |
February | 7209724.88 | 2918.86 | 08-FEB-16:01 | 4.22 | -1.0 | 83572430.32 | 56.69 | 26-FEB-02:20 | -11.1 | -12.0 |
March | 74098367.83 | 4257.50 | 28-MAR-18:01 | 6.93 | 2.56 | 93383551.10 | 56.69 | 07-MAR-05:30 | 6.93 | 2.56 |
April | 0.347563E+09 | 5097.02 | 11-APR-18:11 | 13.90 | 5.53 | 93801794.91 | 80.65 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.120993E+10 | 5500.47 | 06-MAY-18:42 | 14.68 | 6.91 | 0.106185E+09 | 99.52 | 04-MAY-18:10 | 14.68 | 6.91 |
June | 0.155174E+10 | 4450.92 | 08-JUN-21:51 | 16.70 | 13.06 | 0.106898E+09 | 101.46 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.193579E+10 | 4644.18 | 01-JUL-20:42 | 13.87 | 12.34 | 0.111742E+09 | 111.32 | 06-JUL-20:10 | 18.43 | 14.14 |
August | 0.137733E+10 | 4652.53 | 02-AUG-20:02 | 13.62 | 11.96 | 0.109892E+09 | 102.47 | 02-AUG-18:10 | 13.62 | 11.96 |
September | 0.530379E+09 | 5002.97 | 04-SEP-18:01 | 14.03 | 8.92 | 98597695.88 | 92.18 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 99023696.22 | 4007.70 | 21-OCT-18:32 | 12.40 | 7.64 | 95015993.97 | 56.69 | 31-OCT-04:19 | 10.00 | 8.78 |
November | 3783562.23 | 1211.46 | 17-NOV-16:01 | 9.45 | 2.90 | 89646104.66 | 56.69 | 01-NOV-04:19 | 9.45 | 2.90 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 91987933.97 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.713690E+10 | 0.117225E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -8.8 | -9.9 | 83572430.32 | 56.69 | -15.3 | -15.8 | ||
Maximum of Months | 0.193579E+10 | 5500.47 | 16.70 | 13.06 | 0.111742E+09 | 111.32 | 18.43 | 14.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78056069.60 | 2531.01 | 05-JAN-16:02 | -26.9 | -27.2 | 94091805.58 | 56.69 | 14-JAN-05:10 | -23.1 | -23.4 |
February | 0.203311E+09 | 2531.57 | 08-FEB-16:01 | 4.22 | -1.0 | 86387819.23 | 56.69 | 03-FEB-04:19 | 4.22 | -1.0 |
March | 0.278582E+09 | 2553.27 | 19-MAR-15:01 | 4.50 | 1.41 | 96185801.24 | 56.69 | 07-MAR-05:30 | 4.50 | 1.41 |
April | 0.518973E+09 | 2578.76 | 13-APR-15:01 | 20.00 | 8.11 | 94188953.63 | 56.69 | 12-APR-21:10 | 20.00 | 8.11 |
May | 0.938339E+09 | 2550.64 | 05-MAY-15:01 | 17.80 | 8.52 | 98707252.17 | 56.69 | 24-MAY-21:00 | 18.20 | 13.12 |
June | 0.107101E+10 | 2518.11 | 16-JUN-18:01 | 20.50 | 11.25 | 95618200.68 | 56.70 | 29-JUN-23:40 | 26.50 | 23.76 |
July | 0.133673E+10 | 2229.46 | 05-JUL-18:02 | 23.03 | 16.58 | 98863686.10 | 56.70 | 13-JUL-21:00 | 20.00 | 18.49 |
August | 0.123192E+10 | 2251.26 | 31-AUG-18:01 | 24.82 | 21.45 | 98782562.67 | 56.70 | 29-AUG-21:19 | 24.82 | 21.45 |
September | 0.847048E+09 | 2549.81 | 04-SEP-18:01 | 14.03 | 8.92 | 95109619.87 | 56.70 | 07-SEP-21:49 | 18.40 | 13.48 |
October | 0.455551E+09 | 2518.20 | 09-OCT-15:01 | 6.70 | 1.60 | 96623871.64 | 56.69 | 19-OCT-21:19 | 12.60 | 9.81 |
November | 0.138840E+09 | 2501.32 | 17-NOV-16:01 | 9.45 | 2.90 | 92063066.54 | 56.69 | 17-NOV-22:10 | 2.62 | -1.0 |
December | 43708792.51 | 2454.31 | 02-DEC-16:01 | -18.7 | -19.4 | 93592022.23 | 56.69 | 13-DEC-00:20 | -20.2 | -20.6 |
Annual Sum or Average | 0.714207E+10 | 0.114021E+10 | ||||||||
Minimum of Months | 43708792.51 | 2229.46 | -26.9 | -27.2 | 86387819.23 | 56.69 | -23.1 | -23.4 | ||
Maximum of Months | 0.133673E+10 | 2578.76 | 24.82 | 21.45 | 98863686.10 | 56.70 | 26.50 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272664E+11 | 26406.91 | 25-JAN-20:01 | -24.0 | -24.2 | 0.162749E+11 | 11347.89 | 17-JAN-00:20 | -24.0 | -24.2 |
February | 0.252113E+11 | 25497.33 | 24-FEB-22:52 | -23.9 | -24.3 | 0.160406E+11 | 11347.92 | 06-FEB-00:20 | -23.9 | -24.3 |
March | 0.296856E+11 | 25724.98 | 12-MAR-03:51 | -23.9 | -24.1 | 0.186696E+11 | 11347.94 | 12-MAR-23:19 | -12.0 | -13.6 |
April | 0.324620E+11 | 19658.35 | 13-APR-21:10 | 13.03 | 6.68 | 0.185251E+11 | 11347.94 | 02-APR-23:19 | 13.03 | 6.68 |
May | 0.391355E+11 | 22347.16 | 25-MAY-21:10 | 22.65 | 16.44 | 0.193125E+11 | 11352.77 | 18-MAY-21:19 | 22.65 | 16.44 |
June | 0.402829E+11 | 23183.63 | 29-JUN-21:20 | 27.43 | 23.63 | 0.187466E+11 | 11360.41 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.426267E+11 | 22607.88 | 21-JUL-21:52 | 21.70 | 20.13 | 0.193023E+11 | 11364.69 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.409472E+11 | 22125.16 | 08-AUG-21:05 | 22.62 | 18.95 | 0.193684E+11 | 11352.90 | 09-AUG-21:19 | 20.93 | 18.90 |
September | 0.361683E+11 | 21099.49 | 01-SEP-21:22 | 14.45 | 13.76 | 0.186466E+11 | 11349.03 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.333802E+11 | 19316.85 | 19-OCT-22:00 | 12.20 | 9.84 | 0.191149E+11 | 11347.94 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.289252E+11 | 18592.94 | 01-NOV-22:00 | 11.70 | 10.79 | 0.181855E+11 | 11347.94 | 13-NOV-00:20 | -9.4 | -10.0 |
December | 0.271531E+11 | 24877.48 | 13-DEC-04:21 | -23.9 | -24.2 | 0.169976E+11 | 11347.89 | 30-DEC-00:20 | -8.6 | -9.4 |
Annual Sum or Average | 0.403244E+12 | 0.219185E+12 | ||||||||
Minimum of Months | 0.252113E+11 | 18592.94 | -24.0 | -24.3 | 0.160406E+11 | 11347.89 | -24.0 | -24.3 | ||
Maximum of Months | 0.426267E+11 | 26406.91 | 27.43 | 23.63 | 0.193684E+11 | 11364.69 | 22.65 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302139E+11 | 28068.50 | 25-JAN-20:01 | -24.0 | -24.2 | 0.165795E+11 | 11347.97 | 30-JAN-00:20 | -4.0 | -4.5 |
February | 0.280685E+11 | 27027.58 | 24-FEB-22:52 | -23.9 | -24.3 | 0.163252E+11 | 11347.98 | 28-FEB-00:20 | -15.3 | -15.9 |
March | 0.332553E+11 | 27283.37 | 12-MAR-03:51 | -23.9 | -24.1 | 0.188940E+11 | 11348.01 | 12-MAR-23:19 | -12.0 | -13.6 |
April | 0.361710E+11 | 21359.32 | 13-APR-21:10 | 13.03 | 6.68 | 0.186349E+11 | 11347.99 | 02-APR-23:19 | 13.03 | 6.68 |
May | 0.426775E+11 | 23599.42 | 25-MAY-21:10 | 22.65 | 16.44 | 0.193407E+11 | 11378.84 | 18-MAY-21:19 | 22.65 | 16.44 |
June | 0.435465E+11 | 24396.12 | 29-JUN-21:20 | 27.43 | 23.63 | 0.187586E+11 | 11372.49 | 06-JUN-21:19 | 27.43 | 23.63 |
July | 0.457300E+11 | 23791.68 | 21-JUL-21:20 | 21.70 | 20.13 | 0.193090E+11 | 11379.47 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.441912E+11 | 23427.09 | 08-AUG-21:05 | 22.62 | 18.95 | 0.193858E+11 | 11380.83 | 23-AUG-21:19 | 20.00 | 17.61 |
September | 0.396690E+11 | 22375.61 | 01-SEP-21:10 | 14.82 | 14.12 | 0.186876E+11 | 11349.04 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.372395E+11 | 21022.44 | 19-OCT-21:10 | 12.70 | 9.80 | 0.192263E+11 | 11348.00 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.324761E+11 | 20619.58 | 01-NOV-21:10 | 12.62 | 11.43 | 0.184041E+11 | 11348.01 | 13-NOV-00:20 | -9.4 | -10.0 |
December | 0.302351E+11 | 26422.89 | 23-DEC-21:42 | -23.9 | -24.3 | 0.172969E+11 | 11347.97 | 04-DEC-00:20 | -23.9 | -24.3 |
Annual Sum or Average | 0.443474E+12 | 0.220843E+12 | ||||||||
Minimum of Months | 0.280685E+11 | 20619.58 | -24.0 | -24.3 | 0.163252E+11 | 11347.97 | -23.9 | -24.3 | ||
Maximum of Months | 0.457300E+11 | 28068.50 | 27.43 | 23.63 | 0.193858E+11 | 11380.83 | 27.43 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448568E+11 | 29003.00 | 25-JAN-20:01 | -24.0 | -24.2 | 0.185579E+11 | 11319.71 | 07-JAN-18:19 | -24.0 | -24.2 |
February | 0.421679E+11 | 28586.39 | 01-FEB-18:11 | -23.9 | -24.3 | 0.168873E+11 | 11319.65 | 25-FEB-18:19 | -12.2 | -13.9 |
March | 0.488434E+11 | 28865.67 | 26-MAR-10:33 | 3.87 | 1.06 | 0.187843E+11 | 11319.60 | 04-MAR-18:19 | 3.87 | 1.06 |
April | 0.507598E+11 | 30434.02 | 22-APR-10:33 | 14.43 | 5.29 | 0.182219E+11 | 11319.67 | 22-APR-17:19 | 17.93 | 7.72 |
May | 0.561506E+11 | 31500.22 | 18-MAY-10:33 | 26.07 | 16.42 | 0.188527E+11 | 11319.68 | 20-MAY-17:19 | 13.43 | 7.88 |
June | 0.561837E+11 | 32047.91 | 25-JUN-10:40 | 27.43 | 22.06 | 0.182559E+11 | 11319.67 | 24-JUN-17:19 | 27.43 | 22.06 |
July | 0.587314E+11 | 32117.58 | 23-JUL-10:40 | 27.77 | 23.32 | 0.188612E+11 | 11319.68 | 22-JUL-17:19 | 27.77 | 23.32 |
August | 0.573661E+11 | 31547.55 | 25-AUG-10:33 | 24.27 | 17.99 | 0.188663E+11 | 11319.68 | 12-AUG-17:19 | 24.27 | 17.99 |
September | 0.530661E+11 | 31303.49 | 01-SEP-10:33 | 22.77 | 18.04 | 0.182421E+11 | 11319.66 | 09-SEP-17:19 | 16.83 | 10.30 |
October | 0.514859E+11 | 29933.39 | 22-OCT-10:33 | 15.20 | 11.90 | 0.188317E+11 | 11319.58 | 21-OCT-17:19 | 15.20 | 11.90 |
November | 0.467213E+11 | 27069.32 | 17-NOV-11:50 | 8.53 | 2.74 | 0.182006E+11 | 11319.68 | 25-NOV-18:19 | -15.0 | -15.5 |
December | 0.449459E+11 | 27830.69 | 23-DEC-21:42 | -23.9 | -24.3 | 0.186240E+11 | 11319.71 | 23-DEC-18:19 | -23.9 | -24.3 |
Annual Sum or Average | 0.611279E+12 | 0.221186E+12 | ||||||||
Minimum of Months | 0.421679E+11 | 27069.32 | -24.0 | -24.3 | 0.168873E+11 | 11319.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.587314E+11 | 32117.58 | 27.77 | 23.32 | 0.188663E+11 | 11319.71 | 27.77 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139771E+09 | 1151.96 | 29-JAN-13:00 | -0.6 | -2.1 | 0.117356E+10 | 745.69 | 23-JAN-04:10 | -0.6 | -2.1 |
February | 0.117433E+10 | 3305.24 | 22-FEB-11:33 | -2.2 | -4.8 | 0.112691E+10 | 745.69 | 13-FEB-05:30 | -2.2 | -4.8 |
March | 0.291445E+10 | 3589.98 | 26-MAR-10:33 | 3.87 | 1.06 | 0.127711E+10 | 784.99 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.633300E+10 | 4352.30 | 18-APR-10:33 | 17.57 | 11.16 | 0.128284E+10 | 878.72 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.948094E+10 | 5471.53 | 18-MAY-14:10 | 28.57 | 16.73 | 0.148461E+10 | 998.87 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.101072E+11 | 6871.00 | 30-JUN-13:20 | 31.50 | 24.23 | 0.150660E+10 | 1007.40 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.110473E+11 | 6699.64 | 23-JUL-13:20 | 30.00 | 22.71 | 0.160896E+10 | 1007.40 | 21-JUL-22:10 | 30.00 | 22.71 |
August | 0.103242E+11 | 5639.69 | 24-AUG-15:03 | 26.10 | 17.69 | 0.156440E+10 | 989.66 | 08-AUG-21:40 | 26.10 | 17.69 |
September | 0.866333E+10 | 5386.76 | 01-SEP-15:03 | 26.10 | 17.79 | 0.138737E+10 | 968.60 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.625702E+10 | 4479.24 | 22-OCT-10:33 | 15.20 | 11.90 | 0.131132E+10 | 861.36 | 19-OCT-21:40 | 15.20 | 11.90 |
November | 0.261105E+10 | 3417.18 | 17-NOV-11:33 | 8.17 | 2.57 | 0.122861E+10 | 778.38 | 01-NOV-21:40 | 8.17 | 2.57 |
December | 0.118195E+09 | 1385.29 | 05-DEC-22:10 | 0.00 | -0.0 | 0.121235E+10 | 745.79 | 14-DEC-05:30 | -23.6 | -23.9 |
Annual Sum or Average | 0.691709E+11 | 0.161646E+11 | ||||||||
Minimum of Months | 0.118195E+09 | 1151.96 | -2.2 | -4.8 | 0.112691E+10 | 745.69 | -23.6 | -23.9 | ||
Maximum of Months | 0.110473E+11 | 6871.00 | 31.50 | 24.23 | 0.160896E+10 | 1007.40 | 30.00 | 22.71 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4019145.21 | 2538.35 | 06-JAN-13:31 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 4019145.21 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 4019145.21 | 2538.35 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171060E+10 | 3144.18 | 14-JAN-04:51 | -23.3 |
February | 0.911830E+09 | 2748.75 | 15-FEB-07:32 | -23.3 |
March | 0.525762E+09 | 3000.50 | 05-MAR-08:31 | -23.4 |
April | 51907694.49 | 663.63 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 32910889.92 | 786.93 | 30-OCT-06:50 | -9.4 |
November | 0.503458E+09 | 1674.94 | 25-NOV-07:20 | -19.0 |
December | 0.185332E+10 | 3027.91 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.558978E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.185332E+10 | 3144.18 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80423437.58 | 1073.12 | 06-JAN-13:31 | -23.3 |
February | 17350327.50 | 798.47 | 14-FEB-10:42 | -23.2 |
March | 961342.35 | 739.42 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 61135383.29 | 904.34 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.159870E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 80423437.58 | 1073.12 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151990E+10 | 1692.62 | 06-JAN-13:31 | -23.3 |
February | 0.735305E+09 | 1389.86 | 14-FEB-10:42 | -23.2 |
March | 0.306586E+09 | 1312.75 | 05-MAR-08:31 | -23.4 |
April | 985505.40 | 96.34 | 05-APR-04:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.116200E+09 | 528.76 | 25-NOV-17:00 | -15.6 |
December | 0.127499E+10 | 1513.71 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.395397E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.151990E+10 | 1692.62 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133472E+10 | 1102.48 | 06-JAN-13:31 | -23.3 |
February | 0.775536E+09 | 924.20 | 14-FEB-10:42 | -23.2 |
March | 0.406053E+09 | 879.70 | 05-MAR-08:31 | -23.4 |
April | 14888530.52 | 190.38 | 05-APR-04:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 3084485.91 | 96.08 | 30-OCT-07:04 | -9.0 |
November | 0.204409E+09 | 525.93 | 25-NOV-17:00 | -15.6 |
December | 0.119743E+10 | 1000.94 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.393613E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.133472E+10 | 1102.48 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2357197.63 | 7756.27 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 120546.62 | 1479.93 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 492553.25 | 4207.57 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 2970297.50 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 2357197.63 | 7756.27 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145623E+09 | 6451.44 | 09-JAN-10:41 | -23.4 |
February | 54336677.70 | 6583.92 | 02-FEB-10:11 | -23.3 |
March | 9211270.13 | 7203.27 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 1521635.69 | 365.84 | 24-NOV-09:03 | -10.0 |
December | 0.247354E+09 | 8144.07 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.458046E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.247354E+09 | 8144.07 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321215E+09 | 18771.15 | 09-JAN-10:41 | -23.4 |
February | 76364021.77 | 13380.02 | 17-FEB-09:51 | -22.8 |
March | 6504507.27 | 12816.15 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.368019E+09 | 16495.29 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.772102E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.368019E+09 | 18771.15 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266023E+10 | 2246.11 | 07-JAN-09:02 | -20.4 |
February | 0.161897E+10 | 2220.63 | 02-FEB-16:02 | -15.1 |
March | 0.112830E+10 | 2189.43 | 15-MAR-08:62 | -22.3 |
April | 0.342188E+09 | 2159.18 | 05-APR-08:61 | -8.5 |
May | 19442245.57 | 1584.68 | 01-MAY-08:62 | 1.73 |
June | 3696324.84 | 1273.89 | 09-JUN-08:03 | 11.10 |
July | 1281596.26 | 891.96 | 03-JUL-08:04 | 19.50 |
August | 4112409.30 | 1232.04 | 18-AUG-18:03 | 13.22 |
September | 30078044.38 | 1209.16 | 24-SEP-08:03 | 8.95 |
October | 0.394954E+09 | 2164.67 | 30-OCT-15:01 | 5.00 |
November | 0.119009E+10 | 2199.22 | 25-NOV-19:02 | -15.0 |
December | 0.261481E+10 | 2251.76 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.100082E+11 | |||
Minimum of Months | 1281596.26 | 891.96 | -22.3 | |
Maximum of Months | 0.266023E+10 | 2251.76 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311811E+10 | 2475.84 | 05-JAN-08:04 | -32.3 |
February | 0.200940E+10 | 2214.42 | 02-FEB-16:02 | -15.1 |
March | 0.141361E+10 | 2198.77 | 15-MAR-08:62 | -22.3 |
April | 0.428032E+09 | 2163.81 | 05-APR-08:61 | -8.5 |
May | 23612714.10 | 2024.00 | 01-MAY-08:62 | 1.73 |
June | 3169907.99 | 1029.78 | 05-JUN-08:53 | 17.80 |
July | 701439.82 | 718.85 | 15-JUL-08:54 | 23.90 |
August | 4341221.77 | 1255.33 | 25-AUG-08:53 | 20.60 |
September | 35013207.95 | 1508.25 | 04-SEP-18:04 | 14.03 |
October | 0.479921E+09 | 2148.67 | 30-OCT-15:01 | 5.00 |
November | 0.140481E+10 | 2184.73 | 25-NOV-19:02 | -15.0 |
December | 0.297061E+10 | 2244.32 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.118913E+11 | |||
Minimum of Months | 701439.82 | 718.85 | -32.3 | |
Maximum of Months | 0.311811E+10 | 2475.84 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162124E+09 | 404.09 | 09-JAN-05:00 | -33.3 |
February | 29740909.53 | 284.01 | 17-FEB-06:00 | -31.7 |
March | 92764.73 | 32.08 | 08-MAR-06:00 | -18.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 9560549.49 | 174.02 | 29-NOV-06:00 | -20.6 |
December | 0.212556E+09 | 404.11 | 24-DEC-06:00 | -31.1 |
Annual Sum or Average | 0.414074E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.3 | |
Maximum of Months | 0.212556E+09 | 404.11 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646510E+09 | 641.93 | 06-JAN-16:02 | -22.4 |
February | 0.396208E+09 | 631.81 | 01-FEB-16:01 | -20.2 |
March | 0.239442E+09 | 626.04 | 15-MAR-15:01 | -11.0 |
April | 24618525.95 | 589.73 | 04-APR-15:01 | -3.4 |
May | 542126.82 | 525.86 | 02-MAY-15:04 | 18.30 |
June | 225660.83 | 354.07 | 12-JUN-15:06 | 17.98 |
July | 66461.61 | 357.84 | 09-JUL-15:06 | 18.48 |
August | 350808.02 | 396.46 | 10-AUG-15:06 | 16.97 |
September | 1021992.32 | 357.73 | 05-SEP-18:44 | 11.43 |
October | 9971654.05 | 587.10 | 30-OCT-15:01 | 5.00 |
November | 0.170143E+09 | 624.82 | 25-NOV-16:02 | -14.2 |
December | 0.583831E+09 | 638.41 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.207293E+10 | |||
Minimum of Months | 66461.61 | 354.07 | -22.4 | |
Maximum of Months | 0.646510E+09 | 641.93 | 18.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264961E+10 | 2386.13 | 06-JAN-08:04 | -35.1 |
February | 0.160786E+10 | 2180.53 | 02-FEB-16:02 | -15.1 |
March | 0.111270E+10 | 2148.31 | 07-MAR-16:01 | -8.3 |
April | 0.328910E+09 | 2113.92 | 26-APR-15:01 | -0.6 |
May | 21785339.35 | 1077.15 | 11-MAY-18:04 | 14.15 |
June | 1820719.20 | 1184.20 | 09-JUN-08:03 | 11.10 |
July | 813694.58 | 933.02 | 03-JUL-08:04 | 19.50 |
August | 3569554.08 | 1132.90 | 03-AUG-08:03 | 13.40 |
September | 33208285.34 | 1536.70 | 04-SEP-18:03 | 14.03 |
October | 0.409184E+09 | 2125.16 | 29-OCT-18:01 | -3.0 |
November | 0.119583E+10 | 2163.33 | 25-NOV-16:02 | -14.2 |
December | 0.259879E+10 | 2200.51 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.996408E+10 | |||
Minimum of Months | 813694.58 | 933.02 | -35.1 | |
Maximum of Months | 0.264961E+10 | 2386.13 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311116E+10 | 2419.06 | 06-JAN-08:03 | -35.1 |
February | 0.200850E+10 | 2187.99 | 01-FEB-16:01 | -20.2 |
March | 0.139772E+10 | 2145.61 | 07-MAR-16:01 | -8.3 |
April | 0.405696E+09 | 2097.03 | 03-APR-08:61 | -1.5 |
May | 27210292.16 | 1501.94 | 14-MAY-20:43 | 13.67 |
June | 1641954.63 | 1015.54 | 12-JUN-08:04 | 13.17 |
July | 761062.68 | 933.63 | 09-JUL-08:04 | 13.40 |
August | 3626662.04 | 1100.95 | 17-AUG-18:03 | 13.12 |
September | 40806206.58 | 1591.76 | 08-SEP-19:43 | 13.68 |
October | 0.503307E+09 | 2106.67 | 29-OCT-18:01 | -3.0 |
November | 0.140372E+10 | 2157.98 | 25-NOV-16:02 | -14.2 |
December | 0.295694E+10 | 2214.26 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.118611E+11 | |||
Minimum of Months | 761062.68 | 933.63 | -35.1 | |
Maximum of Months | 0.311116E+10 | 2419.06 | 13.68 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117983E+10 | 2295.24 | 06-JAN-13:31 | -23.3 |
February | 0.342615E+09 | 1958.61 | 17-FEB-09:51 | -22.8 |
March | 0.101236E+09 | 1936.68 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 79817.26 | 28.90 | 30-OCT-06:20 | -9.4 |
November | 0.118786E+09 | 838.52 | 25-NOV-17:00 | -15.6 |
December | 0.109741E+10 | 2128.18 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.283996E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.117983E+10 | 2295.24 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345494E+10 | 2887.38 | 05-JAN-08:04 | -32.3 |
February | 0.219878E+10 | 2583.51 | 02-FEB-16:02 | -15.1 |
March | 0.158963E+10 | 2549.48 | 15-MAR-08:62 | -22.3 |
April | 0.555270E+09 | 2506.87 | 05-APR-08:61 | -8.5 |
May | 50520859.52 | 2356.92 | 01-MAY-08:62 | 1.73 |
June | 8989508.85 | 1266.61 | 12-JUN-08:03 | 13.17 |
July | 1471258.42 | 968.81 | 10-JUL-08:03 | 17.77 |
August | 9747458.70 | 1210.70 | 03-AUG-08:03 | 13.40 |
September | 79185151.41 | 1308.96 | 28-SEP-08:63 | 7.30 |
October | 0.648430E+09 | 2510.39 | 29-OCT-18:01 | -3.0 |
November | 0.168027E+10 | 2561.79 | 25-NOV-19:02 | -15.0 |
December | 0.341513E+10 | 2627.39 | 18-DEC-16:13 | -23.3 |
Annual Sum or Average | 0.136924E+11 | |||
Minimum of Months | 1471258.42 | 968.81 | -32.3 | |
Maximum of Months | 0.345494E+10 | 2887.38 | 17.77 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397092E+10 | 2867.53 | 06-JAN-08:03 | -35.1 |
February | 0.266484E+10 | 2571.82 | 02-FEB-16:13 | -15.2 |
March | 0.194495E+10 | 2552.75 | 15-MAR-08:62 | -22.3 |
April | 0.672217E+09 | 2495.46 | 05-APR-08:61 | -8.5 |
May | 53879012.51 | 2350.36 | 01-MAY-08:62 | 1.73 |
June | 7141107.67 | 1296.41 | 05-JUN-08:53 | 17.80 |
July | 699301.62 | 1061.66 | 31-JUL-08:53 | 18.90 |
August | 9553974.51 | 1189.64 | 21-AUG-08:53 | 19.40 |
September | 92407491.81 | 1425.23 | 28-SEP-08:63 | 7.30 |
October | 0.776639E+09 | 2481.63 | 29-OCT-18:01 | -3.0 |
November | 0.194833E+10 | 2537.97 | 25-NOV-19:02 | -15.0 |
December | 0.381081E+10 | 2610.57 | 18-DEC-16:13 | -23.3 |
Annual Sum or Average | 0.159524E+11 | |||
Minimum of Months | 699301.62 | 1061.66 | -35.1 | |
Maximum of Months | 0.397092E+10 | 2867.53 | 19.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122065E+10 | 1371.05 | 12-JAN-19:13 | -22.4 |
February | 0.705482E+09 | 1353.14 | 02-FEB-16:02 | -15.1 |
March | 0.494893E+09 | 1338.59 | 07-MAR-09:02 | -16.7 |
April | 0.150246E+09 | 1327.06 | 26-APR-15:01 | -0.6 |
May | 10698091.00 | 773.95 | 04-MAY-08:03 | 9.27 |
June | 2685128.68 | 758.24 | 22-JUN-15:04 | 18.40 |
July | 1261938.86 | 522.18 | 20-JUL-08:04 | 22.38 |
August | 2023556.31 | 671.88 | 17-AUG-18:03 | 13.12 |
September | 8569064.74 | 656.64 | 29-SEP-15:04 | 11.10 |
October | 0.156372E+09 | 1317.26 | 29-OCT-15:01 | 0.50 |
November | 0.531136E+09 | 1347.70 | 25-NOV-19:02 | -15.0 |
December | 0.126614E+10 | 1377.28 | 11-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.455016E+10 | |||
Minimum of Months | 1261938.86 | 522.18 | -22.4 | |
Maximum of Months | 0.126614E+10 | 1377.28 | 22.38 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19932314.50 | 6799.63 | 09-JAN-10:41 | -23.4 |
February | 1916259.77 | 3614.77 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 8115776.84 | 4751.55 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 29964351.12 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 19932314.50 | 6799.63 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12859425.02 | 6628.79 | 09-JAN-10:41 | -23.4 |
February | 1119431.29 | 3289.50 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 5209072.09 | 4516.48 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 19187928.40 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 12859425.02 | 6628.79 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 337914.19 | 3563.74 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 337914.19 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 337914.19 | 3563.74 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429082E+10 | 6370.09 | 06-JAN-13:31 | -23.3 |
February | 0.193207E+10 | 5605.44 | 17-FEB-09:51 | -22.8 |
March | 0.707534E+09 | 5603.18 | 05-MAR-08:31 | -23.4 |
April | 10925038.00 | 961.00 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 10834292.18 | 800.10 | 30-OCT-06:05 | -9.4 |
November | 0.463442E+09 | 2449.10 | 25-NOV-07:20 | -19.0 |
December | 0.385317E+10 | 6141.68 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.112688E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.429082E+10 | 6370.09 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139303E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118837E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123433E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.105668E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.959059E+09 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.864991E+09 | 1701.53 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.918620E+09 | 1701.53 | 07-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106084E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.113931E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.130162E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.132577E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.140704E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.138497E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.864991E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.140704E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.950561E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.851334E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939133E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.892880E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.912850E+10 | 9504.80 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.878720E+10 | 9504.80 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.905410E+10 | 9504.80 | 07-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923560E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.900325E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.942058E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.919679E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.950098E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109666E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.851334E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.950561E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282066E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246967E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266158E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.241957E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.235546E+10 | 2988.03 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221315E+10 | 2988.03 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230957E+10 | 2988.03 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247184E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250918E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272402E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271283E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.283138E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.304989E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221315E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.283138E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282066E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246967E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266158E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.241957E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.235546E+10 | 2988.03 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221315E+10 | 2988.03 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230957E+10 | 2988.03 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247184E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250918E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272402E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271283E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.283138E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.304989E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221315E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.283138E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129923E+10 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101496E+10 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926781E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 439092.96 | 0.554380E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6294082.22 | 0.274050E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17839583.32 | 0.140174E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22254718.81 | 0.109087E+09 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7551863.21 | 0.141911E+09 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 287228.73 | 0.290615E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517401E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742779E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122440E+10 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54666569.26 | 0.723578E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109087E+09 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22254718.81 | 0.129923E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507581E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395237E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363235E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 193127.84 | 0.224614E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2542625.18 | 0.121203E+09 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6538393.59 | 68276987.71 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8336609.36 | 55349280.19 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3185880.69 | 69608564.40 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 168456.72 | 0.127719E+09 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212569E+09 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293103E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478862E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20965093.38 | 0.291736E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55349280.19 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8336609.36 | 0.507581E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119661E+10 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926637E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839756E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 688738.93 | 0.502920E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6875875.98 | 0.271571E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15397641.56 | 0.155388E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19453678.03 | 0.128774E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8029576.84 | 0.159330E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509942.42 | 0.288761E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1338.85 | 0.477966E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674485E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113031E+10 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50956792.60 | 0.675251E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128774E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19453678.03 | 0.119661E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686942E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533787E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483913E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412562.66 | 0.287312E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4176099.65 | 0.152454E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9246742.82 | 86178687.49 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11834091.62 | 71029074.64 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4958034.60 | 87806338.43 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 333382.63 | 0.161618E+09 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1759.98 | 0.271894E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388411E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649587E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30962673.95 | 0.386093E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71029074.64 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11834091.62 | 0.686942E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165132E+10 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131175E+10 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122058E+10 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 709663.84 | 0.753209E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 8741990.65 | 0.394832E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 23191084.57 | 0.219466E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 30198554.02 | 0.169312E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 12481805.66 | 0.217617E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 786320.77 | 0.416840E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715701E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100036E+10 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157196E+10 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 76109419.50 | 0.964295E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169312E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 30198554.02 | 0.165132E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.139303E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289541E+10 |
February | 0.236489E+11 | 0.118837E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226839E+10 |
March | 0.262800E+11 | 0.123433E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208600E+10 |
April | 0.253579E+11 | 0.105668E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 896225.24 | 0.127813E+10 |
May | 0.262123E+11 | 0.959059E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12914255.40 | 0.674380E+09 |
June | 0.254132E+11 | 0.864991E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36487201.65 | 0.372881E+09 |
July | 0.261570E+11 | 0.918620E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46322499.72 | 0.298957E+09 |
August | 0.262677E+11 | 0.106084E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15651976.92 | 0.380186E+09 |
September | 0.253456E+11 | 0.113931E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 615008.18 | 0.712155E+09 |
October | 0.261693E+11 | 0.130162E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119663E+10 |
November | 0.253025E+11 | 0.132577E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166916E+10 |
December | 0.261570E+11 | 0.140704E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272631E+10 |
Annual Sum or Average | 0.308468E+12 | 0.138497E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112887E+09 | 0.165586E+11 |
Minimum of Months | 0.236489E+11 | 0.864991E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298957E+09 |
Maximum of Months | 0.262800E+11 | 0.140704E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46322499.72 | 0.289541E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.950561E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834920E+10 |
February | 0.702046E+11 | 0.851334E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654002E+10 |
March | 0.780153E+11 | 0.939133E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603408E+10 |
April | 0.752779E+11 | 0.892880E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2964503.25 | 0.374769E+10 |
May | 0.778146E+11 | 0.912850E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39889174.33 | 0.202309E+10 |
June | 0.754422E+11 | 0.878720E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105028E+09 | 0.114830E+10 |
July | 0.776503E+11 | 0.905410E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133733E+09 | 0.918539E+09 |
August | 0.779788E+11 | 0.923560E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47990150.82 | 0.116250E+10 |
September | 0.752414E+11 | 0.900325E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1913855.30 | 0.214313E+10 |
October | 0.776868E+11 | 0.942058E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355500E+10 |
November | 0.751137E+11 | 0.919679E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488246E+10 |
December | 0.776503E+11 | 0.950098E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788695E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109666E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331519E+09 | 0.483910E+11 |
Minimum of Months | 0.702046E+11 | 0.851334E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918539E+09 |
Maximum of Months | 0.780153E+11 | 0.950561E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133733E+09 | 0.834920E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767008E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588403E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533705E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436216.52 | 0.319190E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5380738.59 | 0.158106E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14304344.13 | 80352131.81 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18368994.57 | 57238131.80 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7761007.21 | 76583891.50 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 495698.07 | 0.166044E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17190.83 | 0.296914E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425237E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717095E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46764189.92 | 0.418588E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57238131.80 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18368994.57 | 0.767008E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765051E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584148E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528488E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 402283.70 | 0.317464E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4947962.72 | 0.166703E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12715967.08 | 92942936.89 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16506729.13 | 72412723.68 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6689130.49 | 89923654.96 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395304.55 | 0.170774E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129.11 | 0.294743E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421628E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716182E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41660506.76 | 0.422046E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72412723.68 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16506729.13 | 0.765051E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191388E+09 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155899E+09 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154523E+09 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111113E+09 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160309.45 | 67561797.92 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973635.53 | 43211639.38 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 788424.54 | 36090307.84 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 174655.62 | 44206686.32 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70719230.73 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104768E+09 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121521E+09 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174998E+09 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2097025.13 | 0.127600E+10 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36090307.84 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973635.53 | 0.191388E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213533E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163695E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148448E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 123808.22 | 88601517.73 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437810.04 | 44770258.42 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3614447.38 | 24077795.95 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4718797.32 | 18030426.35 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1959185.81 | 23114805.65 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131246.27 | 46499696.82 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.38 | 83066103.92 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119133E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200279E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11988173.41 | 0.117325E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18030426.35 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4718797.32 | 0.213533E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766560E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588501E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535463E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 442146.08 | 0.321113E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5401972.99 | 0.158816E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14311637.59 | 80860572.30 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18382651.38 | 57520281.77 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7789066.76 | 76938677.31 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 500197.83 | 0.166384E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17703.19 | 0.297214E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424911E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716940E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46845375.82 | 0.419122E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57520281.77 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18382651.38 | 0.766560E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764692E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583936E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529911E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415171.02 | 0.319511E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4966370.41 | 0.164509E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12676160.01 | 91419214.15 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16434932.59 | 71577341.07 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6722422.59 | 87326686.46 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 399749.02 | 0.168916E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.09 | 0.294782E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421520E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716101E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41618356.74 | 0.421420E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71577341.07 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16434932.59 | 0.764692E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927172E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713869E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647295E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452691.48 | 0.388982E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5143348.64 | 0.207717E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11917530.57 | 0.117188E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14876593.11 | 96987813.38 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6287974.81 | 0.117935E+09 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367687.06 | 0.215461E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362828E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518895E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871991E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39045825.67 | 0.518632E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96987813.38 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14876593.11 | 0.927172E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767518E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588050E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533339E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 425982.10 | 0.318998E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5254749.70 | 0.158749E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14049965.45 | 80916046.24 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18020371.59 | 57768524.74 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7559621.28 | 77103141.92 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 472603.51 | 0.166389E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15433.03 | 0.296376E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424721E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717920E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45798726.66 | 0.418785E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57768524.74 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18020371.59 | 0.767518E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765910E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584657E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528714E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 393901.60 | 0.317516E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4845523.85 | 0.168620E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12521919.10 | 94999543.50 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16220516.15 | 74168540.23 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6539382.07 | 91864033.99 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 379997.52 | 0.171622E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2972.47 | 0.294033E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421626E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717225E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40904212.76 | 0.423096E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74168540.23 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16220516.15 | 0.765910E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397236E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305236E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276548E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219731.54 | 0.165034E+09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2702813.61 | 81442736.86 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7212222.12 | 41409181.01 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9243372.29 | 29503554.00 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3877327.18 | 39535987.93 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 243472.36 | 85824149.80 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6947.51 | 0.153891E+09 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220657E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370670E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23505886.60 | 0.216699E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29503554.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9243372.29 | 0.397236E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193968E+10 |
February | 0.415303E+11 | 0.246967E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152643E+10 |
March | 0.461508E+11 | 0.266158E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141878E+10 |
April | 0.445315E+11 | 0.241957E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 422106.06 | 0.888703E+09 |
May | 0.460320E+11 | 0.235546E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6708227.63 | 0.483090E+09 |
June | 0.446286E+11 | 0.221315E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19682735.77 | 0.279741E+09 |
July | 0.459349E+11 | 0.230957E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23996941.35 | 0.219579E+09 |
August | 0.461292E+11 | 0.247184E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8608435.76 | 0.278956E+09 |
September | 0.445099E+11 | 0.250918E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339853.76 | 0.507665E+09 |
October | 0.459565E+11 | 0.272402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845586E+09 |
November | 0.444343E+11 | 0.271283E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116087E+10 |
December | 0.459349E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184104E+10 |
Annual Sum or Average | 0.541708E+12 | 0.304989E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59758300.33 | 0.113901E+11 |
Minimum of Months | 0.415303E+11 | 0.221315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219579E+09 |
Maximum of Months | 0.461508E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23996941.35 | 0.193968E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195080E+10 |
February | 0.415303E+11 | 0.246967E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153705E+10 |
March | 0.461508E+11 | 0.266158E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142880E+10 |
April | 0.445315E+11 | 0.241957E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 419489.09 | 0.894512E+09 |
May | 0.460320E+11 | 0.235546E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6673507.40 | 0.484903E+09 |
June | 0.446286E+11 | 0.221315E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19664150.56 | 0.280492E+09 |
July | 0.459349E+11 | 0.230957E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23907842.12 | 0.219908E+09 |
August | 0.461292E+11 | 0.247184E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8561026.72 | 0.280055E+09 |
September | 0.445099E+11 | 0.250918E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339707.79 | 0.510283E+09 |
October | 0.459565E+11 | 0.272402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851594E+09 |
November | 0.444343E+11 | 0.271283E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117047E+10 |
December | 0.459349E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185217E+10 |
Annual Sum or Average | 0.541708E+12 | 0.304989E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59565723.69 | 0.114610E+11 |
Minimum of Months | 0.415303E+11 | 0.221315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219908E+09 |
Maximum of Months | 0.461508E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23907842.12 | 0.195080E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174815E+10 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137727E+10 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128018E+10 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 377802.87 | 0.798334E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5989016.38 | 0.431287E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 17629179.59 | 0.249428E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21432276.91 | 0.195692E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7678179.39 | 0.249431E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 306342.12 | 0.454781E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761068E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105043E+10 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166058E+10 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 53412797.25 | 0.102566E+11 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195692E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21432276.91 | 0.174815E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163341E+10 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126360E+10 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114852E+10 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671819.69 | 0.688609E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7057787.47 | 0.368871E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18460837.04 | 0.209099E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22642401.02 | 0.170219E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8486791.89 | 0.209103E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364331.35 | 0.379692E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644234E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920948E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154040E+10 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57683968.47 | 0.917671E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170219E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22642401.02 | 0.163341E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 686.78 | 06-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 676.27 | 14-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 618.09 | 05-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.39 | 23-APR-17:00 | 451.59 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 25-MAY-18:00 | 312.16 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 29-JUN-16:00 | 242.33 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 | 15-JUL-14:00 | 176.81 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 | 08-AUG-15:30 | 199.85 | 19-AUG-04:10 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 01-SEP-15:30 | 242.63 | 06-SEP-04:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.40 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 553.03 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 668.76 | 24-DEC-11:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.81 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 686.78 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 276.86 | 06-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 279.11 | 14-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 254.43 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 23-APR-16:00 | 178.00 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 | 25-MAY-17:01 | 126.51 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 29-JUN-16:00 | 100.44 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 | 15-JUL-14:00 | 79.18 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 | 08-AUG-15:00 | 85.33 | 19-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 | 01-SEP-15:00 | 104.56 | 06-SEP-04:50 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 156.93 | 30-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 213.76 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 265.80 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.18 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 279.11 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 671.62 | 06-JAN-09:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 674.20 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 614.75 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.55 | 23-APR-16:00 | 411.92 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 25-MAY-17:01 | 285.77 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.96 | 29-JUN-16:00 | 233.62 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 15-JUL-14:00 | 187.21 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.61 | 08-AUG-16:00 | 196.81 | 19-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 01-SEP-16:00 | 238.87 | 06-SEP-04:40 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 | 19-OCT-15:00 | 363.45 | 30-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 504.49 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 642.51 | 24-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.21 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 109.96 | 674.20 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 383.06 | 06-JAN-09:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 385.68 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 351.74 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 23-APR-16:00 | 237.65 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 | 25-MAY-18:00 | 164.29 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 29-JUN-16:00 | 132.66 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.38 | 15-JUL-14:00 | 106.21 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 | 08-AUG-16:00 | 111.57 | 19-AUG-04:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 01-SEP-16:00 | 135.56 | 06-SEP-04:10 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 19-OCT-15:00 | 209.69 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 291.06 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 367.69 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.21 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 385.68 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 875.13 | 13-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 807.38 | 24-FEB-22:40 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 794.58 | 15-MAR-07:30 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 64.51 | 23-APR-16:00 | 610.64 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 93.86 | 25-MAY-17:00 | 435.59 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 168.28 | 29-JUN-16:00 | 328.27 | 04-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 111.92 | 23-JUL-16:00 | 249.15 | 02-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 111.50 | 08-AUG-16:00 | 275.01 | 19-AUG-05:08 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 48.97 | 01-SEP-16:00 | 343.52 | 06-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 539.00 | 30-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 726.71 | 29-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 827.52 | 19-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 249.15 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 168.28 | 875.13 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1558.88 | 06-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1526.04 | 14-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1392.85 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.44 | 23-APR-17:20 | 998.24 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 | 25-MAY-18:00 | 704.14 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 29-JUN-16:00 | 553.57 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 07-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.43 | 15-JUL-15:10 | 429.50 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.63 | 08-AUG-15:40 | 483.01 | 19-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 01-SEP-15:40 | 590.26 | 06-SEP-04:10 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 885.16 | 30-OCT-04:30 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1222.55 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1479.19 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.50 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 1558.88 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4559.07 | 06-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4545.98 | 14-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4150.90 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.93 | 23-APR-16:00 | 2951.37 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.18 | 25-MAY-17:01 | 2108.02 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.29 | 29-JUN-16:00 | 1677.76 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 07-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.82 | 15-JUL-15:00 | 1310.37 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.14 | 08-AUG-16:00 | 1449.39 | 19-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 01-SEP-16:00 | 1748.78 | 06-SEP-04:50 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2629.27 | 30-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3566.86 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4343.92 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1310.37 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 761.29 | 4559.07 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 460.23 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.50 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:10 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-16:00 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.38 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 427.49 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 460.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 455.39 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.05 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.41 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:07 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.14 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 426.24 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 455.39 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 118.72 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 113.95 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 99.69 | 16-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 77.84 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 25-MAY-18:00 | 58.69 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUN-16:00 | 48.24 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 15-JUL-14:00 | 39.30 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 08-AUG-15:10 | 41.68 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 49.85 | 06-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 67.37 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 77.93 | 29-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 106.60 | 24-DEC-08:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 118.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 126.49 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 123.20 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 111.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 23-APR-16:00 | 73.47 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 25-MAY-17:00 | 50.88 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 29-JUN-16:00 | 39.56 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 15-JUL-15:10 | 28.94 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 08-AUG-15:10 | 32.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 01-SEP-15:10 | 39.60 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 19-OCT-15:09 | 64.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 89.91 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 118.01 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 126.49 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 463.64 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.50 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.74 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:10 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:50 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 426.11 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 463.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 456.56 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 443.84 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:09 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 425.17 | 24-DEC-09:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 456.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 530.25 | 06-JAN-09:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 519.85 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 470.23 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 23-APR-16:00 | 317.31 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.06 | 25-MAY-18:00 | 219.69 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 29-JUN-16:00 | 178.73 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.09 | 15-JUL-14:00 | 143.31 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 | 08-AUG-16:00 | 148.75 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.77 | 01-SEP-16:00 | 183.93 | 06-SEP-04:03 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 280.02 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 388.53 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 495.83 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 530.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 459.72 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 446.10 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 | 23-APR-16:00 | 263.73 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 25-MAY-17:00 | 182.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 29-JUN-16:00 | 142.18 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 15-JUL-15:10 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-16:00 | 117.49 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 | 01-SEP-16:00 | 142.34 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:10 | 232.88 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.69 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 426.97 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 459.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 453.79 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 444.99 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.63 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 23-APR-16:00 | 263.72 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 25-MAY-17:00 | 182.75 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 29-JUN-16:00 | 142.17 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 15-JUL-15:10 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.48 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 01-SEP-15:10 | 142.33 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:07 | 232.87 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.67 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 424.91 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 453.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238.48 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 228.24 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 204.99 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 23-APR-16:00 | 134.94 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 25-MAY-17:00 | 93.51 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 29-JUN-16:00 | 72.75 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 15-JUL-15:10 | 53.27 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 08-AUG-15:10 | 60.11 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 01-SEP-16:00 | 72.83 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 19-OCT-15:10 | 119.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 165.10 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 219.02 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 238.48 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1056.20 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1045.20 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 965.09 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 23-APR-16:00 | 696.88 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 25-MAY-18:00 | 497.51 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 | 29-JUN-16:00 | 396.96 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 302.76 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.06 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:50 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 837.45 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1010.77 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.76 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 | 1056.20 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1055.33 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1045.82 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 966.95 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-APR-16:00 | 696.88 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 25-MAY-18:00 | 497.52 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 29-JUN-16:00 | 396.97 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 302.76 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.07 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:40 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 841.87 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1013.39 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.76 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 1055.33 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 911.51 | 06-JAN-08:20 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 883.19 | 14-FEB-07:30 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 814.77 | 15-MAR-07:20 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.19 | 23-APR-16:00 | 623.77 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.19 | 25-MAY-18:00 | 445.31 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 149.69 | 29-JUN-16:00 | 354.93 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 97.20 | 15-JUL-14:00 | 271.01 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 91.54 | 08-AUG-15:40 | 297.63 | 19-AUG-05:10 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 28.43 | 01-SEP-15:40 | 352.64 | 06-SEP-05:10 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 553.55 | 30-OCT-05:10 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 742.35 | 29-NOV-06:20 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 869.01 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 271.01 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 149.69 | 911.51 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 898.60 | 06-JAN-09:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 899.39 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 820.74 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 23-APR-16:00 | 562.52 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.97 | 25-MAY-18:00 | 389.31 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 29-JUN-16:00 | 306.82 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 | 15-JUL-14:00 | 244.57 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.59 | 08-AUG-16:00 | 256.35 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 01-SEP-15:30 | 314.44 | 06-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 496.52 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 688.60 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 858.59 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.57 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 899.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32935.55 | 25-JAN-23:33 | 34505.68 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30843.32 | 13-FEB-23:01 | 92015.14 | 35174.16 | 32446.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29640.62 | 12-MAR-03:51 | 89459.16 | 29311.22 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13331.27 | 22-APR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14062.36 | 18-MAY-10:33 | 7667.93 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14823.36 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15685.68 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19583.00 | 31-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20828.08 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21239.67 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20498.46 | 17-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32744.28 | 02-DEC-06:00 | 11501.89 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13331.27 | 7667.93 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32935.55 | 92015.14 | 35174.16 | 32446.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2159.36 | 27-JAN-13:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.53 |
February | 3615.97 | 28-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.20 |
March | 3483.38 | 20-MAR-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.88 |
April | 3855.70 | 13-APR-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 |
May | 3854.61 | 18-MAY-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 | 0.00 |
June | 3971.34 | 30-JUN-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
July | 4092.05 | 23-JUL-13:10 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 0.00 |
August | 4480.13 | 26-AUG-12:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
September | 4496.55 | 01-SEP-13:15 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 0.00 |
October | 5127.01 | 22-OCT-12:40 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.57 |
November | 3432.39 | 17-NOV-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.07 |
December | 2376.70 | 10-DEC-12:26 | 1949.22 | 995.99 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2159.36 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5127.01 | 1949.22 | 995.99 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 601.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2601.46 | 25-JAN-20:01 | 8426.88 | 5536.12 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.37 |
February | 2168.05 | 24-FEB-22:52 | 6771.60 | 2306.72 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.77 |
March | 2074.57 | 07-MAR-00:41 | 10834.56 | 1230.25 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.93 |
April | 1411.82 | 13-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.16 |
May | 1897.83 | 25-MAY-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
June | 2125.68 | 30-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 2001.82 | 24-JUL-20:05 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
August | 1895.88 | 25-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
September | 1812.86 | 01-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 |
October | 1472.49 | 19-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 |
November | 1169.69 | 17-NOV-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 |
December | 1693.17 | 02-DEC-00:22 | 6771.60 | 768.91 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1169.69 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | |
Maximum of Months | 2601.46 | 10834.56 | 5536.12 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 585.47 | 19-JAN-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.21 |
February | 694.81 | 21-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.50 |
March | 751.43 | 28-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.13 |
April | 904.23 | 18-APR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.03 |
May | 1106.06 | 25-MAY-20:55 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
June | 1706.66 | 30-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
July | 1487.38 | 24-JUL-19:55 | 445.54 | 1368.35 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
August | 1240.43 | 09-AUG-19:54 | 1113.84 | 3420.88 | 4197.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 |
September | 1116.71 | 01-SEP-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
October | 971.21 | 22-OCT-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.26 |
November | 763.06 | 01-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 |
December | 623.90 | 05-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 585.47 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1706.66 | 1113.84 | 3420.88 | 4197.23 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 282.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 63.12 | 19-JAN-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 |
February | 288.98 | 21-FEB-21:40 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.16 |
March | 416.13 | 28-MAR-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.66 |
April | 525.92 | 18-APR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
May | 633.34 | 18-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 0.00 |
June | 824.15 | 30-JUN-19:20 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 |
July | 688.98 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 0.00 |
August | 655.24 | 26-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 |
September | 646.99 | 01-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
October | 562.29 | 22-OCT-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
November | 424.07 | 01-NOV-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 |
December | 125.02 | 05-DEC-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 63.12 | 146.88 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 824.15 | 220.32 | 251.84 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 162.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41039.85 | 25-JAN-20:01 | 5644.80 | 2600.67 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 793.84 |
February | 39200.35 | 13-FEB-21:22 | 4838.40 | 1733.78 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 794.66 |
March | 37112.01 | 31-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 274.79 |
April | 37890.16 | 13-APR-20:00 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 136.04 |
May | 38660.10 | 18-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 |
June | 38897.26 | 29-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 67.29 | 0.00 |
July | 38746.25 | 21-JUL-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
August | 38662.07 | 08-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
September | 38452.45 | 01-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 104.75 |
October | 37892.37 | 19-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 156.47 |
November | 37195.14 | 01-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 153.36 |
December | 39380.63 | 23-DEC-21:42 | 4233.60 | 1517.06 | 23104.68 | 200723.75 | 0.00 | 0.00 | 0.00 | 0.00 | 784.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37112.01 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41039.85 | 5644.80 | 2600.67 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 67.29 | 794.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9423.53 | 27-JAN-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.72 |
February | 13492.24 | 28-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.33 |
March | 12952.39 | 20-MAR-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.58 |
April | 14384.33 | 22-APR-13:10 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.33 |
May | 13196.84 | 06-MAY-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.93 |
June | 13001.35 | 30-JUN-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 195.80 | 0.00 |
July | 14256.42 | 29-JUL-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 118.96 | 0.00 |
August | 15630.91 | 26-AUG-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 0.00 |
September | 15184.18 | 01-SEP-13:15 | 6830.40 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 0.00 |
October | 18012.44 | 22-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.92 |
November | 12822.74 | 17-NOV-12:40 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.93 |
December | 10802.45 | 10-DEC-12:24 | 25614.00 | 623.89 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9423.53 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18012.44 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 195.80 | 1330.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59262.70 | 25-JAN-20:01 | 283876.32 | 76038.40 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3881.42 |
February | 57724.67 | 24-FEB-22:52 | 228114.90 | 31682.67 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3883.51 |
March | 59034.79 | 07-MAR-00:51 | 410606.82 | 19009.60 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3892.63 |
April | 32949.91 | 13-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.75 |
May | 38770.07 | 25-MAY-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.21 |
June | 41385.93 | 29-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 253.24 | 0.00 |
July | 40008.64 | 24-JUL-20:05 | 81107.52 | 16897.42 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.71 |
August | 39280.19 | 08-AUG-21:05 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
September | 38357.51 | 01-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.25 |
October | 34944.57 | 19-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.45 |
November | 27106.86 | 17-NOV-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.16 |
December | 51439.91 | 02-DEC-00:31 | 364983.84 | 16897.42 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3854.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27106.86 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59262.70 | 410606.82 | 76038.40 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 253.24 | 3892.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1851.27 | 27-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.63 |
February | 4312.17 | 20-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.80 |
March | 4367.37 | 26-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 |
April | 4453.43 | 13-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
May | 4486.11 | 04-MAY-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
June | 4451.59 | 16-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 |
July | 3832.91 | 30-JUL-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 0.00 |
August | 3846.51 | 30-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
September | 4445.97 | 04-SEP-18:01 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.47 |
October | 4283.17 | 09-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.20 |
November | 4252.76 | 17-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 |
December | 82.31 | 02-DEC-14:00 | 54.00 | 58.70 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 82.31 | 54.00 | 58.70 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4486.11 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 295.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 556.52 | 17-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.12 |
February | 3879.95 | 08-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.32 |
March | 4111.12 | 28-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.37 |
April | 4871.05 | 11-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.95 |
May | 4983.64 | 06-MAY-19:01 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 |
June | 4191.35 | 20-JUN-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.73 |
July | 4443.74 | 04-JUL-16:51 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 4412.46 | 07-AUG-16:21 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
September | 4771.68 | 04-SEP-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 |
October | 3876.96 | 21-OCT-18:32 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 |
November | 2548.99 | 17-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.64 |
December | 50.92 | 05-DEC-19:06 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 50.92 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | |
Maximum of Months | 4983.64 | 1800.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 201.19 | 05-JAN-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 |
February | 141.16 | 28-FEB-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 |
March | 463.01 | 29-MAR-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 |
April | 646.84 | 13-APR-13:10 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
May | 630.18 | 18-MAY-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
June | 617.32 | 30-JUN-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 0.00 |
July | 660.31 | 23-JUL-13:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
August | 733.27 | 25-AUG-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
September | 743.83 | 01-SEP-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
October | 897.57 | 22-OCT-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
November | 371.38 | 17-NOV-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 |
December | 75.62 | 02-DEC-15:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 75.62 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 897.57 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 101.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 258.00 | 18-JAN-19:05 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 |
February | 281.83 | 05-FEB-09:01 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
March | 1097.88 | 28-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
April | 1175.87 | 13-APR-19:41 | 1386.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
May | 1259.78 | 21-MAY-21:01 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
June | 1253.23 | 07-JUN-08:51 | 288.00 | 393.62 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
July | 1209.19 | 01-JUL-21:01 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 |
August | 1154.16 | 01-AUG-21:11 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
September | 1236.21 | 04-SEP-18:01 | 1170.00 | 1118.23 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 |
October | 1122.70 | 20-OCT-18:11 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 |
November | 939.12 | 01-NOV-18:03 | 554.40 | 398.09 | 474.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 |
December | 273.07 | 06-DEC-19:05 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 258.00 | 288.00 | 393.62 | 474.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 | |
Maximum of Months | 1259.78 | 1800.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 82.59 | 27-JAN-13:20 | 36.00 | 49.81 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.01 |
February | 3750.72 | 28-FEB-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.20 |
March | 3940.18 | 31-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 |
April | 4027.66 | 13-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
May | 4053.85 | 03-MAY-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 |
June | 4023.56 | 16-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 |
July | 3696.50 | 29-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 | 0.00 |
August | 3611.20 | 24-AUG-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
September | 4055.47 | 04-SEP-18:01 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 |
October | 3946.38 | 09-OCT-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 |
November | 3700.30 | 16-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 |
December | 779.38 | 28-DEC-09:04 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 82.59 | 36.00 | 49.81 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4055.47 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 | 268.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5.58 | 29-JAN-16:06 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.75 |
February | 758.13 | 28-FEB-09:03 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.31 |
March | 3607.57 | 26-MAR-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 |
April | 3827.49 | 22-APR-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.79 |
May | 3973.49 | 06-MAY-19:01 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
June | 4157.38 | 28-JUN-07:52 | 464.40 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
July | 4326.94 | 31-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.58 |
August | 4065.52 | 11-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.40 |
September | 3961.63 | 04-SEP-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 |
October | 3661.73 | 09-OCT-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.92 |
November | 672.77 | 10-NOV-09:03 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.24 |
December | 122.72 | 05-DEC-19:06 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5.58 | 216.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | |
Maximum of Months | 4326.94 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1704.71 | 26-JAN-07:00 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.10 |
February | 1728.49 | 14-FEB-07:00 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.85 |
March | 1799.68 | 20-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.17 |
April | 2190.67 | 22-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.29 |
May | 2503.16 | 18-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 0.00 |
June | 3029.44 | 30-JUN-19:20 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 0.00 |
July | 2692.34 | 23-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 0.00 |
August | 2594.22 | 26-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
September | 2511.77 | 01-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
October | 2230.51 | 22-OCT-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.34 |
November | 1689.18 | 17-NOV-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 |
December | 1382.14 | 24-DEC-23:53 | 8047.49 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1382.14 | 1508.90 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3029.44 | 8047.49 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 519.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 900.68 | 27-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.00 |
February | 4467.31 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.01 |
March | 4526.85 | 26-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 |
April | 4625.62 | 13-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
May | 4663.82 | 04-MAY-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
June | 4621.52 | 16-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 |
July | 3999.73 | 27-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
August | 3955.81 | 14-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
September | 4607.83 | 04-SEP-18:01 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.71 |
October | 4438.88 | 09-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 |
November | 4407.35 | 17-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.63 |
December | 68.94 | 02-DEC-14:00 | 54.00 | 58.70 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 68.94 | 54.00 | 58.70 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | |
Maximum of Months | 4663.82 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 457.44 | 20-JAN-16:05 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.11 |
February | 2918.86 | 08-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 |
March | 4257.50 | 28-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.86 |
April | 5097.02 | 11-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 |
May | 5500.47 | 06-MAY-18:42 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.90 |
June | 4450.92 | 08-JUN-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.32 |
July | 4644.18 | 01-JUL-20:42 | 831.60 | 1067.17 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.91 |
August | 4652.53 | 02-AUG-20:02 | 961.20 | 949.78 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.69 |
September | 5002.97 | 04-SEP-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.24 |
October | 4007.70 | 21-OCT-18:32 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 |
November | 1211.46 | 17-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.74 |
December | 0.00 | 01-DEC-00:03 | 540.00 | 117.39 | 134.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 540.00 | 117.39 | 134.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.32 | |
Maximum of Months | 5500.47 | 1800.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2531.01 | 05-JAN-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.78 |
February | 2531.57 | 08-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 |
March | 2553.27 | 19-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 |
April | 2578.76 | 13-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
May | 2550.64 | 05-MAY-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
June | 2518.11 | 16-JUN-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
July | 2229.46 | 05-JUL-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 0.00 |
August | 2251.26 | 31-AUG-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 |
September | 2549.81 | 04-SEP-18:01 | 1170.00 | 1118.23 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 |
October | 2518.20 | 09-OCT-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
November | 2501.32 | 17-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 |
December | 2454.31 | 02-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2229.46 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2578.76 | 1170.00 | 1118.23 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 197.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26406.91 | 25-JAN-20:01 | 167930.11 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.14 |
February | 25497.33 | 24-FEB-22:52 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.90 |
March | 25724.98 | 12-MAR-03:51 | 209912.64 | 6640.07 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.37 |
April | 19658.35 | 13-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.29 |
May | 22347.16 | 25-MAY-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
June | 23183.63 | 29-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 | 0.00 |
July | 22607.88 | 21-JUL-21:52 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 |
August | 22125.16 | 08-AUG-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
September | 21099.49 | 01-SEP-21:22 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 |
October | 19316.85 | 19-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.74 |
November | 18592.94 | 01-NOV-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.27 |
December | 24877.48 | 13-DEC-04:21 | 269887.68 | 3320.03 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18592.94 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26406.91 | 269887.68 | 23904.24 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 | 897.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28068.50 | 25-JAN-20:01 | 167930.11 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.77 |
February | 27027.58 | 24-FEB-22:52 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.50 |
March | 27283.37 | 12-MAR-03:51 | 209912.64 | 6640.07 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.05 |
April | 21359.32 | 13-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.29 |
May | 23599.42 | 25-MAY-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
June | 24396.12 | 29-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 0.00 |
July | 23791.68 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 |
August | 23427.09 | 08-AUG-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
September | 22375.61 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.50 |
October | 21022.44 | 19-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.05 |
November | 20619.58 | 01-NOV-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.66 |
December | 26422.89 | 23-DEC-21:42 | 125947.58 | 13944.14 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20619.58 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28068.50 | 209912.64 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 902.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29003.00 | 25-JAN-20:01 | 14943.94 | 8486.47 | 119302.85 | 119961.77 | 0.00 | 0.00 | 0.00 | 0.00 | 810.31 |
February | 28586.39 | 01-FEB-18:11 | 9339.96 | 4950.44 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 810.53 |
March | 28865.67 | 26-MAR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 305.19 |
April | 30434.02 | 22-APR-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 143.49 |
May | 31500.22 | 18-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 28.07 | 0.00 |
June | 32047.91 | 25-JUN-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.22 | 0.00 |
July | 32117.58 | 23-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 49.59 | 0.00 |
August | 31547.55 | 25-AUG-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
September | 31303.49 | 01-SEP-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 |
October | 29933.39 | 22-OCT-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 |
November | 27069.32 | 17-NOV-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 234.98 |
December | 27830.69 | 23-DEC-21:42 | 11207.95 | 4950.44 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 800.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27069.32 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32117.58 | 14943.94 | 8486.47 | 119302.85 | 157449.82 | 0.00 | 0.00 | 0.00 | 49.59 | 810.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1151.96 | 29-JAN-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.47 |
February | 3305.24 | 22-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.83 |
March | 3589.98 | 26-MAR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.46 |
April | 4352.30 | 18-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
May | 5471.53 | 18-MAY-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 0.00 |
June | 6871.00 | 30-JUN-13:20 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.35 | 0.00 |
July | 6699.64 | 23-JUL-13:20 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 | 0.00 |
August | 5639.69 | 24-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 0.00 |
September | 5386.76 | 01-SEP-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
October | 4479.24 | 22-OCT-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 |
November | 3417.18 | 17-NOV-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.67 |
December | 1385.29 | 05-DEC-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1151.96 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6871.00 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.35 | 359.83 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.368825E+12 | 234705.94 | 12-JAN-20:10 | 0.135693E+13 | 1151998.84 | 05-JAN-21:40 |
February | 0.329289E+12 | 234968.91 | 08-FEB-20:10 | 0.935523E+12 | 1064959.96 | 01-FEB-21:19 |
March | 0.362486E+12 | 241017.38 | 28-MAR-19:19 | 0.801243E+12 | 906223.50 | 05-MAR-07:49 |
April | 0.360763E+12 | 302470.36 | 23-APR-18:10 | 0.562364E+12 | 578014.50 | 19-APR-17:10 |
May | 0.423256E+12 | 351403.07 | 25-MAY-19:00 | 0.529487E+12 | 546469.50 | 08-MAY-17:00 |
June | 0.475677E+12 | 420897.03 | 29-JUN-18:10 | 0.465479E+12 | 511652.87 | 02-JUN-20:00 |
July | 0.531506E+12 | 396080.61 | 21-JUL-19:19 | 0.458960E+12 | 465200.15 | 07-JUL-21:00 |
August | 0.484501E+12 | 377084.31 | 08-AUG-19:40 | 0.454552E+12 | 475594.60 | 18-AUG-20:00 |
September | 0.389454E+12 | 302683.87 | 01-SEP-19:10 | 0.516422E+12 | 523736.25 | 23-SEP-18:00 |
October | 0.371395E+12 | 261725.45 | 19-OCT-19:19 | 0.570702E+12 | 562638.04 | 03-OCT-17:40 |
November | 0.351670E+12 | 237906.73 | 02-NOV-19:19 | 0.672010E+12 | 629051.43 | 25-NOV-19:10 |
December | 0.368661E+12 | 233360.51 | 18-DEC-20:10 | 0.125897E+13 | 1114481.17 | 19-DEC-21:30 |
Annual Sum or Average | 0.481748E+13 | 0.858264E+13 | ||||
Minimum of Months | 0.329289E+12 | 233360.51 | 0.454552E+12 | 465200.15 | ||
Maximum of Months | 0.531506E+12 | 420897.03 | 0.135693E+13 | 1151998.84 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.672242E+11 | 0.212246E+11 | 0.140828E+12 | 0.544240E+11 | 0.443970E+11 | 0.194374E+10 | 0.00 | 0.366560E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.770942E+10 | 0.00 |
February | 0.604087E+11 | 0.174342E+11 | 0.127191E+12 | 0.491571E+11 | 0.372728E+11 | 0.210684E+10 | 0.00 | 0.108370E+10 | 0.00 | 0.00 | 0.231056E+11 | 0.696410E+10 | 0.00 |
March | 0.665308E+11 | 0.169456E+11 | 0.140882E+12 | 0.544261E+11 | 0.400908E+11 | 0.263331E+10 | 0.00 | 0.290936E+10 | 0.00 | 0.00 | 0.252309E+11 | 0.770423E+10 | 0.00 |
April | 0.638559E+11 | 0.140288E+11 | 0.136245E+12 | 0.526674E+11 | 0.392900E+11 | 0.578601E+10 | 0.00 | 0.178536E+11 | 0.00 | 0.00 | 0.185680E+11 | 0.746528E+10 | 0.00 |
May | 0.654368E+11 | 0.123631E+11 | 0.140860E+12 | 0.544241E+11 | 0.445092E+11 | 0.113659E+11 | 0.00 | 0.727520E+11 | 0.00 | 0.00 | 0.859770E+10 | 0.770455E+10 | 0.00 |
June | 0.630504E+11 | 0.108085E+11 | 0.136336E+12 | 0.526693E+11 | 0.453406E+11 | 0.126784E+11 | 0.00 | 0.135840E+12 | 0.00 | 0.00 | 0.634936E+10 | 0.745693E+10 | 0.00 |
July | 0.652926E+11 | 0.117117E+11 | 0.140770E+12 | 0.544216E+11 | 0.483046E+11 | 0.139968E+11 | 0.00 | 0.176818E+12 | 0.00 | 0.00 | 0.715298E+10 | 0.771255E+10 | 0.00 |
August | 0.658326E+11 | 0.135402E+11 | 0.140892E+12 | 0.544257E+11 | 0.470862E+11 | 0.130513E+11 | 0.00 | 0.132479E+12 | 0.00 | 0.00 | 0.414393E+10 | 0.770440E+10 | 0.00 |
September | 0.642088E+11 | 0.153614E+11 | 0.136256E+12 | 0.526677E+11 | 0.424602E+11 | 0.100647E+11 | 0.00 | 0.489652E+11 | 0.00 | 0.00 | 0.689039E+10 | 0.746647E+10 | 0.00 |
October | 0.668409E+11 | 0.183300E+11 | 0.140818E+12 | 0.544237E+11 | 0.412812E+11 | 0.508430E+10 | 0.00 | 0.133691E+11 | 0.00 | 0.00 | 0.183263E+11 | 0.770329E+10 | 0.00 |
November | 0.649892E+11 | 0.198920E+11 | 0.136330E+12 | 0.526690E+11 | 0.392111E+11 | 0.158033E+10 | 0.00 | 0.152725E+10 | 0.00 | 0.00 | 0.230280E+11 | 0.744954E+10 | 0.00 |
December | 0.672746E+11 | 0.217946E+11 | 0.140770E+12 | 0.544229E+11 | 0.441276E+11 | 0.156560E+10 | 0.00 | 0.220738E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.771613E+10 | 0.00 |
Annual Sum or Average | 0.780945E+12 | 0.193435E+12 | 0.165818E+13 | 0.640799E+12 | 0.513371E+12 | 0.818572E+11 | 0.00 | 0.604185E+12 | 0.00 | 0.00 | 0.192936E+12 | 0.907569E+11 | 0.00 |
Minimum of Months | 0.604087E+11 | 0.108085E+11 | 0.127191E+12 | 0.491571E+11 | 0.372728E+11 | 0.156560E+10 | 0.00 | 0.220738E+09 | 0.00 | 0.00 | 0.414393E+10 | 0.696410E+10 | 0.00 |
Maximum of Months | 0.672746E+11 | 0.217946E+11 | 0.140892E+12 | 0.544261E+11 | 0.483046E+11 | 0.139968E+11 | 0.00 | 0.176818E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.771613E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.895694E+12 | 0.00 | 0.309315E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.516557E+12 | 0.00 | 0.281762E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.337648E+12 | 0.00 | 0.311571E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.117361E+12 | 0.00 | 0.298048E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.752642E+11 | 0.00 | 0.302244E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.360275E+11 | 0.00 | 0.282338E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.261603E+11 | 0.00 | 0.280979E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.270030E+11 | 0.00 | 0.275511E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.101959E+12 | 0.00 | 0.267492E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.135272E+12 | 0.00 | 0.283527E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.239214E+12 | 0.00 | 0.285705E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.803188E+12 | 0.00 | 0.303964E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.331135E+13 | 0.00 | 0.348246E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.261603E+11 | 0.00 | 0.267492E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.895694E+12 | 0.00 | 0.311571E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 25758.08 | 12-JAN-19:10 | 4668.08 | 26-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 23791.92 | 13-FEB-19:10 | 3695.61 | 28-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 01-MAR-07:19 | 21753.38 | 03-MAR-19:10 | 4345.98 | 31-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.57 | 03-APR-06:19 | 26720.04 | 13-APR-21:10 | 6110.78 | 23-APR-18:30 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:30 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39167.99 | 22-MAY-06:19 | 31718.29 | 18-MAY-21:00 | 6329.37 | 18-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:49 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.59 | 09-JUN-06:19 | 34142.78 | 30-JUN-20:10 | 6577.80 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 07-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.09 | 03-JUL-06:19 | 33362.42 | 24-JUL-21:00 | 6571.83 | 21-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.68 | 31-AUG-06:19 | 33834.89 | 24-AUG-21:30 | 6441.96 | 08-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 18-SEP-06:19 | 33583.74 | 01-SEP-21:40 | 6222.91 | 01-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 29485.55 | 19-OCT-21:10 | 6133.99 | 19-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 23062.22 | 01-NOV-21:10 | 4396.48 | 01-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 24727.51 | 23-DEC-19:10 | 4695.88 | 20-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39167.99 | 21753.38 | 3695.61 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 34142.78 | 6577.80 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3983.14 | 27-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4744.57 | 05-JAN-07:30 | 0.00 |
February | 9976.95 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4743.22 | 14-FEB-07:30 | 0.00 |
March | 21669.99 | 31-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4739.84 | 15-MAR-06:00 | 0.00 |
April | 99848.24 | 23-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.74 | 03-APR-18:10 | 0.00 |
May | 137207.00 | 25-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.43 | 10-MAY-18:10 | 0.00 |
June | 206994.12 | 29-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-12:09 | 4738.35 | 19-JUN-18:10 | 0.00 |
July | 171267.93 | 15-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 02-JUL-04:40 | 4738.40 | 31-JUL-18:10 | 0.00 |
August | 172077.27 | 08-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 07-AUG-15:39 | 4738.38 | 14-AUG-18:10 | 0.00 |
September | 117681.00 | 01-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-12:09 | 4738.35 | 08-SEP-18:49 | 0.00 |
October | 83257.54 | 19-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:40 | 4738.20 | 20-OCT-06:10 | 0.00 |
November | 31392.78 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.55 | 20-NOV-19:10 | 0.00 |
December | 2907.22 | 02-DEC-14:09 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4743.04 | 20-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2907.22 | 0.00 | 0.00 | 9938.94 | 4738.20 | 0.00 | |||
Maximum of Months | 206994.12 | 0.00 | 0.00 | 9938.94 | 4744.57 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 234705.94 | 12-JAN-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23088.41 | 302.71 | 0.00 | 0.00 | 0.00 |
February | 234968.91 | 08-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 19464.16 | 3142.87 | 0.00 | 1311.73 | 0.00 |
March | 241017.38 | 28-MAR-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 19770.33 | 3736.50 | 0.00 | 6761.69 | 0.00 |
April | 302470.36 | 23-APR-18:10 | 51227.63 | 74651.16 | 0.00 | 31284.78 | 23428.11 | 6077.05 | 0.00 | 99848.24 | 0.00 |
May | 351403.07 | 25-MAY-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 27593.47 | 6171.25 | 0.00 | 106780.19 | 0.00 |
June | 420897.03 | 29-JUN-18:10 | 52987.32 | 77573.37 | 0.00 | 31341.98 | 28333.81 | 6577.80 | 0.00 | 206994.12 | 0.00 |
July | 396080.61 | 21-JUL-19:19 | 61533.41 | 86439.81 | 0.00 | 31549.51 | 29409.69 | 6571.83 | 0.00 | 164754.22 | 0.00 |
August | 377084.31 | 08-AUG-19:40 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 28618.83 | 6368.54 | 0.00 | 131535.92 | 0.00 |
September | 302683.87 | 01-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 26074.20 | 5588.52 | 0.00 | 70647.07 | 0.00 |
October | 261725.45 | 19-OCT-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 26179.56 | 4727.96 | 0.00 | 27986.10 | 0.00 |
November | 237906.73 | 02-NOV-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21245.53 | 3259.05 | 0.00 | 2186.66 | 0.00 |
December | 233360.51 | 18-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20884.75 | 1599.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 233360.51 | 51227.63 | 74651.16 | 0.00 | 31284.78 | 19464.16 | 302.71 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 420897.03 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 29409.69 | 6577.80 | 0.00 | 206994.12 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 833562.85 | 06-JAN-04:00 | 0.00 | 310264.49 | 30-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 806334.83 | 17-FEB-05:00 | 0.00 | 311635.74 | 27-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 750963.12 | 05-MAR-06:00 | 0.00 | 311594.59 | 02-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 207853.18 | 05-APR-06:10 | 0.00 | 308675.91 | 05-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 191558.04 | 13-MAY-22:19 | 0.00 | 303696.67 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 186271.64 | 16-JUN-22:40 | 0.00 | 295532.31 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 171394.85 | 07-JUL-23:00 | 0.00 | 284388.06 | 10-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 179400.32 | 19-AUG-00:40 | 0.00 | 279718.48 | 02-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 207980.03 | 28-SEP-08:09 | 0.00 | 281321.91 | 29-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 225961.77 | 31-OCT-08:09 | 0.00 | 289276.64 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 296500.46 | 25-NOV-16:30 | 0.00 | 297967.04 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 817409.02 | 24-DEC-05:00 | 0.00 | 304719.68 | 27-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 171394.85 | 0.00 | 279718.48 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 833562.85 | 0.00 | 311635.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 146.17 | 18.92 | 146.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 11.67 | 20.07 | 11.67 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51.50 | 19.67 | 51.50 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Annual Sum or Average | 209.33 | 19.17 | 209.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.17 | 20.07 | 146.17 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.33 | 16.61 | 179.33 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
February | 64.17 | 17.44 | 64.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
March | 19.67 | 18.06 | 19.67 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 135.50 | 16.92 | 135.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Annual Sum or Average | 398.67 | 16.92 | 398.67 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.33 | 18.06 | 179.33 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 165.83 | 18.05 | 165.83 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
February | 49.83 | 19.18 | 49.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
March | 10.67 | 19.73 | 10.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 134.67 | 18.90 | 134.67 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Annual Sum or Average | 361.00 | 18.57 | 361.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.83 | 19.73 | 165.83 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 227.50 | 18.83 | 227.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 44.83 | 19.71 | 44.83 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
March | 9.00 | 20.23 | 9.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 157.67 | 19.51 | 157.67 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 439.00 | 19.19 | 439.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 227.50 | 20.23 | 227.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.50 | 18.65 | 265.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 61.67 | 19.62 | 61.67 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
March | 12.33 | 20.03 | 12.33 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 194.00 | 19.29 | 194.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 533.50 | 19.03 | 533.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 265.50 | 20.03 | 265.50 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.50 | 12.20 | 109.50 | 12.20 | 0.00 | 12.20 | 0.00 | 12.20 |
February | 35.17 | 12.95 | 35.17 | 12.95 | 0.00 | 12.95 | 0.00 | 12.95 |
March | 11.33 | 14.55 | 11.33 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75.83 | 13.59 | 75.83 | 13.59 | 0.00 | 13.59 | 0.00 | 13.59 |
Annual Sum or Average | 231.83 | 12.89 | 231.83 | 12.89 | 0.00 | 12.89 | 0.00 | 12.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.50 | 14.55 | 109.50 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 158.00 | 17.11 | 158.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
February | 55.00 | 18.12 | 55.00 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
March | 12.33 | 18.41 | 12.33 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 128.17 | 17.79 | 128.17 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
Annual Sum or Average | 353.50 | 17.56 | 353.50 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.00 | 18.41 | 158.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 153.67 | 17.93 | 153.67 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
February | 45.00 | 19.10 | 45.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 8.17 | 19.50 | 8.17 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121.83 | 18.82 | 121.83 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 328.67 | 18.45 | 328.67 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.67 | 19.50 | 153.67 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 20.36 | 9.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.83 | 20.48 | 0.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 20.40 | 2.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 12.67 | 20.38 | 12.67 | 20.38 | 2.33 | 20.49 | 2.33 | 20.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.00 | 20.48 | 9.00 | 20.48 | 0.67 | 21.79 | 0.67 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 20.16 | 34.17 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
February | 1.50 | 20.34 | 1.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.82 | 2.83 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.86 | 0.83 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.94 | 0.50 | 21.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 20.28 | 6.67 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 42.33 | 20.19 | 42.33 | 20.19 | 6.83 | 20.31 | 6.83 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.17 | 20.34 | 34.17 | 20.34 | 2.83 | 21.94 | 2.83 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.50 | 19.93 | 90.50 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
February | 8.50 | 20.30 | 8.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 1.17 | 20.41 | 1.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.88 | 6.00 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.86 | 5.67 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.77 | 3.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.42 | 1.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 47.83 | 20.24 | 47.83 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
Annual Sum or Average | 149.17 | 20.06 | 149.17 | 20.06 | 16.83 | 20.15 | 16.83 | 20.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.50 | 20.42 | 90.50 | 20.42 | 6.00 | 21.88 | 6.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.50 | 20.32 | 20.50 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
February | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 20.42 | 2.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 23.00 | 20.33 | 23.00 | 20.33 | 0.50 | 20.35 | 0.50 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.50 | 20.46 | 20.50 | 20.46 | 0.33 | 21.76 | 0.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.33 | 20.06 | 43.33 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
February | 1.33 | 20.45 | 1.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.15 | 1.17 | 22.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.35 | 4.33 | 22.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.26 | 6.33 | 22.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.24 | 2.50 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.03 | 0.33 | 22.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 13.67 | 20.39 | 13.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Annual Sum or Average | 58.50 | 20.14 | 58.50 | 20.14 | 14.67 | 20.38 | 14.67 | 20.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.33 | 20.55 | 43.33 | 20.55 | 6.33 | 22.35 | 6.33 | 22.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.50 | 19.18 | 184.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
February | 52.00 | 19.86 | 52.00 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
March | 12.33 | 20.14 | 12.33 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 146.17 | 19.62 | 146.17 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
Annual Sum or Average | 395.00 | 19.47 | 395.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.50 | 20.14 | 184.50 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.00 | 20.36 | 16.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.83 | 20.45 | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.85 | 0.17 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.36 | 3.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 19.83 | 20.37 | 19.83 | 20.37 | 5.83 | 20.55 | 5.83 | 20.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.00 | 20.45 | 16.00 | 20.45 | 1.83 | 21.85 | 1.83 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.17 | 20.07 | 43.17 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
February | 1.83 | 20.31 | 1.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.81 | 3.83 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.88 | 3.67 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.92 | 1.00 | 21.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.50 | 20.33 | 14.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 59.50 | 20.14 | 59.50 | 20.14 | 12.67 | 20.30 | 12.67 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.17 | 20.33 | 43.17 | 20.33 | 3.83 | 21.92 | 3.83 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.45 | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 1.33 | 20.45 | 1.33 | 20.45 | 2.17 | 21.02 | 2.17 | 21.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.45 | 0.83 | 20.45 | 0.67 | 21.79 | 0.67 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.33 | 17.62 | 70.33 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
February | 10.83 | 18.84 | 10.83 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38.17 | 18.62 | 38.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
Annual Sum or Average | 119.33 | 18.05 | 119.33 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.33 | 18.84 | 70.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.67 | 17.57 | 63.67 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
February | 9.00 | 18.84 | 9.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34.00 | 18.64 | 34.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Annual Sum or Average | 106.67 | 18.02 | 106.67 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.67 | 18.84 | 63.67 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.33 | 14.25 | 71.33 | 14.25 | 0.00 | 14.25 | 0.00 | 14.25 |
February | 24.67 | 15.04 | 24.67 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
March | 6.83 | 16.49 | 6.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48.00 | 15.11 | 48.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
Annual Sum or Average | 150.83 | 14.75 | 150.83 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.33 | 16.49 | 71.33 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.17 | 18.37 | 191.17 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
February | 58.33 | 19.29 | 58.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
March | 15.67 | 19.80 | 15.67 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 147.33 | 19.02 | 147.33 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 412.50 | 18.78 | 412.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 191.17 | 19.80 | 191.17 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.56 | 247.00 | 21.10 | 247.00 | 20.83 |
February | 672.00 | 22.37 | 50.33 | 22.25 | 50.33 | 22.14 |
March | 744.00 | 22.31 | 8.17 | 22.29 | 8.17 | 22.28 |
April | 720.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
May | 744.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
June | 715.50 | 22.86 | 44.67 | 22.86 | 44.67 | 22.87 |
July | 476.33 | 23.22 | 147.33 | 23.33 | 79.50 | 23.35 |
August | 137.50 | 23.60 | 294.33 | 23.83 | 50.50 | 23.84 |
September | 201.67 | 23.73 | 120.83 | 23.81 | 13.50 | 23.82 |
October | 397.50 | 23.84 | 0.00 | 23.84 | 0.00 | 23.84 |
November | 651.17 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
December | 744.00 | 22.44 | 110.50 | 22.16 | 110.50 | 21.94 |
Annual Sum or Average | 6947.67 | 22.70 | 1023.17 | 22.65 | 604.17 | 22.54 |
Minimum of Months | 137.50 | 21.56 | 0.00 | 21.10 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 23.87 | 294.33 | 23.87 | 247.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.00 | 19.98 | 672.50 | 19.90 | 672.50 | 19.88 |
February | 640.67 | 20.76 | 469.33 | 20.68 | 460.17 | 20.63 |
March | 703.67 | 21.06 | 408.00 | 21.02 | 396.17 | 20.98 |
April | 652.50 | 21.29 | 133.00 | 21.35 | 103.83 | 21.31 |
May | 622.83 | 21.53 | 77.00 | 21.76 | 5.33 | 21.75 |
June | 552.33 | 21.60 | 118.17 | 21.97 | 0.00 | 21.97 |
July | 464.33 | 21.84 | 203.83 | 22.38 | 0.00 | 22.38 |
August | 512.83 | 21.68 | 175.33 | 22.20 | 0.00 | 22.20 |
September | 598.50 | 21.39 | 96.33 | 21.73 | 0.00 | 21.73 |
October | 678.33 | 21.14 | 124.67 | 21.31 | 73.00 | 21.29 |
November | 698.33 | 21.08 | 409.83 | 21.06 | 405.67 | 21.04 |
December | 744.00 | 20.27 | 687.67 | 20.23 | 687.67 | 20.22 |
Annual Sum or Average | 7610.33 | 21.07 | 3575.67 | 21.09 | 2804.33 | 20.96 |
Minimum of Months | 464.33 | 19.98 | 77.00 | 19.90 | 0.00 | 19.88 |
Maximum of Months | 744.00 | 21.84 | 687.67 | 22.38 | 687.67 | 22.38 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 473.67 | 20.24 | 473.67 | 20.16 |
February | 672.00 | 21.18 | 214.67 | 21.03 | 214.67 | 20.94 |
March | 744.00 | 21.64 | 85.83 | 21.55 | 85.83 | 21.48 |
April | 713.17 | 22.39 | 0.67 | 22.39 | 0.00 | 22.39 |
May | 590.00 | 22.95 | 53.17 | 23.03 | 0.00 | 23.03 |
June | 471.33 | 23.06 | 197.17 | 23.28 | 79.50 | 23.33 |
July | 285.67 | 23.37 | 375.50 | 23.65 | 126.50 | 23.68 |
August | 320.17 | 23.16 | 304.83 | 23.49 | 82.17 | 23.53 |
September | 562.83 | 22.91 | 57.17 | 22.99 | 19.17 | 23.01 |
October | 720.83 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
November | 720.00 | 21.68 | 35.67 | 21.65 | 35.67 | 21.62 |
December | 744.00 | 20.72 | 427.50 | 20.58 | 427.50 | 20.51 |
Annual Sum or Average | 7288.00 | 21.96 | 2225.83 | 21.94 | 1544.67 | 21.80 |
Minimum of Months | 285.67 | 20.42 | 0.00 | 20.24 | 0.00 | 20.16 |
Maximum of Months | 744.00 | 23.37 | 473.67 | 23.65 | 473.67 | 23.68 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.31 | 709.33 | 20.30 | 709.33 | 20.29 |
February | 672.00 | 20.91 | 561.33 | 20.90 | 561.33 | 20.89 |
March | 744.00 | 21.02 | 423.50 | 21.00 | 423.50 | 21.00 |
April | 720.00 | 21.41 | 77.67 | 21.37 | 77.67 | 21.34 |
May | 713.00 | 22.53 | 8.50 | 22.53 | 4.50 | 22.52 |
June | 559.83 | 22.88 | 70.00 | 23.00 | 0.00 | 23.00 |
July | 331.83 | 23.22 | 139.17 | 23.42 | 0.00 | 23.42 |
August | 550.33 | 23.11 | 35.00 | 23.16 | 0.00 | 23.16 |
September | 693.33 | 22.58 | 3.33 | 22.59 | 0.00 | 22.59 |
October | 744.00 | 21.58 | 4.50 | 21.58 | 4.50 | 21.58 |
November | 720.00 | 21.05 | 278.50 | 21.04 | 278.50 | 21.03 |
December | 744.00 | 20.66 | 661.00 | 20.65 | 661.00 | 20.64 |
Annual Sum or Average | 7936.33 | 21.64 | 2971.83 | 21.46 | 2720.33 | 21.31 |
Minimum of Months | 331.83 | 20.31 | 3.33 | 20.30 | 0.00 | 20.29 |
Maximum of Months | 744.00 | 23.22 | 709.33 | 23.42 | 709.33 | 23.42 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.13 | 722.33 | 20.12 | 722.33 | 20.12 |
February | 672.00 | 20.86 | 592.00 | 20.85 | 592.00 | 20.85 |
March | 744.00 | 20.99 | 469.17 | 20.98 | 469.17 | 20.98 |
April | 720.00 | 21.24 | 119.50 | 21.20 | 119.50 | 21.18 |
May | 735.83 | 22.29 | 8.33 | 22.28 | 8.33 | 22.26 |
June | 620.17 | 22.69 | 49.83 | 22.78 | 2.00 | 22.78 |
July | 508.83 | 23.10 | 33.50 | 23.15 | 0.00 | 23.15 |
August | 684.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
September | 714.67 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
October | 744.00 | 21.36 | 16.67 | 21.35 | 16.67 | 21.34 |
November | 720.00 | 21.01 | 358.67 | 21.01 | 358.67 | 21.00 |
December | 744.00 | 20.53 | 696.83 | 20.52 | 696.83 | 20.51 |
Annual Sum or Average | 8352.33 | 21.56 | 3066.83 | 21.33 | 2985.50 | 21.19 |
Minimum of Months | 508.83 | 20.13 | 0.00 | 20.12 | 0.00 | 20.12 |
Maximum of Months | 744.00 | 23.10 | 722.33 | 23.15 | 722.33 | 23.15 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.17 | 19.24 | 379.67 | 19.54 | 213.17 | 19.01 |
February | 319.50 | 21.09 | 354.17 | 21.79 | 147.33 | 21.60 |
March | 265.33 | 22.21 | 435.67 | 22.91 | 146.50 | 22.92 |
April | 225.00 | 23.11 | 544.83 | 23.41 | 152.17 | 23.50 |
May | 271.17 | 23.63 | 648.50 | 23.49 | 234.83 | 23.60 |
June | 299.50 | 23.92 | 679.33 | 23.50 | 292.67 | 23.61 |
July | 338.00 | 23.96 | 725.83 | 23.49 | 336.67 | 23.60 |
August | 321.17 | 23.96 | 720.67 | 23.49 | 319.17 | 23.60 |
September | 290.17 | 23.77 | 652.17 | 23.51 | 266.50 | 23.62 |
October | 247.00 | 23.30 | 616.33 | 23.42 | 185.83 | 23.52 |
November | 237.17 | 22.87 | 462.50 | 23.38 | 138.00 | 23.48 |
December | 409.83 | 20.02 | 371.67 | 20.50 | 197.67 | 20.13 |
Annual Sum or Average | 3669.00 | 22.36 | 6591.33 | 22.78 | 2630.50 | 22.78 |
Minimum of Months | 225.00 | 19.24 | 354.17 | 19.54 | 138.00 | 19.01 |
Maximum of Months | 445.17 | 23.96 | 725.83 | 23.51 | 336.67 | 23.62 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 20.25 | 501.67 | 20.05 | 501.00 | 19.96 |
February | 623.00 | 21.07 | 310.00 | 20.96 | 282.00 | 20.83 |
March | 681.83 | 21.54 | 155.83 | 21.52 | 120.67 | 21.41 |
April | 601.17 | 22.01 | 70.33 | 22.20 | 2.00 | 22.19 |
May | 451.17 | 22.43 | 177.83 | 22.80 | 7.50 | 22.81 |
June | 387.00 | 22.68 | 339.00 | 23.11 | 109.00 | 23.18 |
July | 311.50 | 23.18 | 554.00 | 23.45 | 201.17 | 23.49 |
August | 332.33 | 22.90 | 495.67 | 23.35 | 163.33 | 23.41 |
September | 417.17 | 22.26 | 208.50 | 22.75 | 25.67 | 22.78 |
October | 609.50 | 21.77 | 83.33 | 22.02 | 1.50 | 22.02 |
November | 684.17 | 21.44 | 130.83 | 21.43 | 112.50 | 21.38 |
December | 741.33 | 20.51 | 527.83 | 20.38 | 527.83 | 20.33 |
Annual Sum or Average | 6577.17 | 21.61 | 3554.83 | 21.80 | 2054.17 | 21.68 |
Minimum of Months | 311.50 | 20.25 | 70.33 | 20.05 | 1.50 | 19.96 |
Maximum of Months | 741.33 | 23.18 | 554.00 | 23.45 | 527.83 | 23.49 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.62 | 354.50 | 20.31 | 354.50 | 20.15 |
February | 672.00 | 21.56 | 110.67 | 21.36 | 110.67 | 21.21 |
March | 744.00 | 22.07 | 35.33 | 22.00 | 35.33 | 21.94 |
April | 673.33 | 22.70 | 5.50 | 22.71 | 0.00 | 22.71 |
May | 436.00 | 23.03 | 120.17 | 23.21 | 6.50 | 23.22 |
June | 334.50 | 23.21 | 323.83 | 23.52 | 111.50 | 23.58 |
July | 233.50 | 23.72 | 559.33 | 23.79 | 189.17 | 23.82 |
August | 244.67 | 23.53 | 526.00 | 23.73 | 165.33 | 23.77 |
September | 329.67 | 22.94 | 170.00 | 23.25 | 30.00 | 23.28 |
October | 603.50 | 22.55 | 21.00 | 22.60 | 0.00 | 22.60 |
November | 718.83 | 22.11 | 2.33 | 22.11 | 2.33 | 22.10 |
December | 744.00 | 20.96 | 291.00 | 20.70 | 291.00 | 20.56 |
Annual Sum or Average | 6478.00 | 22.12 | 2519.67 | 22.25 | 1296.33 | 22.15 |
Minimum of Months | 233.50 | 20.62 | 2.33 | 20.31 | 0.00 | 20.15 |
Maximum of Months | 744.00 | 23.72 | 559.33 | 23.79 | 354.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 737.17 | 20.51 | 737.17 | 20.51 |
February | 672.00 | 20.80 | 576.17 | 20.74 | 576.17 | 20.72 |
March | 743.83 | 20.95 | 516.83 | 20.85 | 516.83 | 20.80 |
April | 705.33 | 21.29 | 179.67 | 21.20 | 177.67 | 21.14 |
May | 685.83 | 21.53 | 19.17 | 21.56 | 5.50 | 21.56 |
June | 625.33 | 21.46 | 27.83 | 21.53 | 2.50 | 21.54 |
July | 603.33 | 21.36 | 49.17 | 21.51 | 0.17 | 21.51 |
August | 630.67 | 21.40 | 37.83 | 21.51 | 0.33 | 21.51 |
September | 670.83 | 21.44 | 10.33 | 21.47 | 2.17 | 21.47 |
October | 728.67 | 21.11 | 188.17 | 21.02 | 187.67 | 20.96 |
November | 720.00 | 20.80 | 570.67 | 20.74 | 570.67 | 20.72 |
December | 744.00 | 20.50 | 743.33 | 20.50 | 743.33 | 20.50 |
Annual Sum or Average | 8273.83 | 21.08 | 3656.33 | 20.97 | 3520.17 | 20.89 |
Minimum of Months | 603.33 | 20.50 | 10.33 | 20.50 | 0.17 | 20.50 |
Maximum of Months | 744.00 | 21.53 | 743.33 | 21.56 | 743.33 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
February | 672.00 | 20.56 | 649.50 | 20.54 | 649.50 | 20.54 |
March | 744.00 | 20.68 | 626.17 | 20.63 | 626.17 | 20.61 |
April | 699.83 | 21.13 | 269.17 | 21.08 | 258.33 | 21.00 |
May | 639.83 | 21.82 | 79.83 | 22.22 | 25.33 | 22.35 |
June | 577.50 | 22.11 | 137.50 | 22.74 | 63.83 | 22.99 |
July | 550.50 | 22.27 | 176.33 | 22.99 | 83.67 | 23.31 |
August | 586.33 | 22.07 | 140.00 | 22.67 | 61.50 | 22.90 |
September | 663.17 | 21.61 | 49.50 | 21.86 | 14.33 | 21.93 |
October | 739.17 | 21.02 | 267.67 | 20.92 | 266.00 | 20.85 |
November | 720.00 | 20.60 | 651.83 | 20.58 | 651.83 | 20.57 |
December | 744.00 | 20.46 | 744.00 | 20.46 | 744.00 | 20.46 |
Annual Sum or Average | 8080.33 | 21.17 | 4535.50 | 21.16 | 4188.50 | 21.08 |
Minimum of Months | 550.50 | 20.42 | 49.50 | 20.42 | 14.33 | 20.42 |
Maximum of Months | 744.00 | 22.27 | 744.00 | 22.99 | 744.00 | 23.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 738.33 | 20.43 | 738.33 | 20.43 |
February | 672.00 | 20.69 | 633.67 | 20.68 | 633.67 | 20.67 |
March | 744.00 | 20.85 | 524.83 | 20.81 | 524.83 | 20.79 |
April | 720.00 | 21.23 | 107.50 | 21.19 | 107.50 | 21.16 |
May | 734.50 | 21.78 | 0.50 | 21.79 | 0.00 | 21.79 |
June | 683.00 | 22.01 | 31.17 | 22.08 | 24.50 | 22.13 |
July | 695.00 | 22.10 | 50.83 | 22.21 | 35.83 | 22.28 |
August | 728.00 | 22.04 | 21.00 | 22.08 | 20.83 | 22.11 |
September | 719.83 | 21.60 | 2.50 | 21.61 | 2.50 | 21.61 |
October | 744.00 | 21.19 | 26.50 | 21.18 | 26.50 | 21.16 |
November | 720.00 | 20.89 | 453.33 | 20.83 | 453.33 | 20.81 |
December | 744.00 | 20.53 | 714.50 | 20.52 | 714.50 | 20.52 |
Annual Sum or Average | 8648.33 | 21.27 | 3304.67 | 21.12 | 3282.33 | 21.02 |
Minimum of Months | 672.00 | 20.43 | 0.50 | 20.43 | 0.00 | 20.43 |
Maximum of Months | 744.00 | 22.10 | 738.33 | 22.21 | 738.33 | 22.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 738.00 | 20.49 | 738.00 | 20.49 |
February | 672.00 | 20.80 | 574.17 | 20.74 | 574.17 | 20.72 |
March | 744.00 | 21.04 | 492.17 | 20.92 | 492.17 | 20.87 |
April | 708.67 | 21.40 | 153.17 | 21.31 | 153.17 | 21.24 |
May | 678.67 | 21.55 | 4.33 | 21.55 | 2.50 | 21.55 |
June | 595.00 | 21.39 | 24.00 | 21.46 | 2.33 | 21.47 |
July | 584.33 | 21.31 | 41.17 | 21.44 | 0.17 | 21.45 |
August | 621.67 | 21.38 | 18.33 | 21.44 | 0.17 | 21.44 |
September | 658.00 | 21.42 | 4.67 | 21.43 | 2.83 | 21.44 |
October | 728.00 | 21.13 | 186.83 | 21.04 | 186.83 | 20.98 |
November | 720.00 | 20.78 | 567.33 | 20.73 | 567.33 | 20.71 |
December | 744.00 | 20.49 | 738.50 | 20.49 | 738.50 | 20.49 |
Annual Sum or Average | 8198.33 | 21.08 | 3542.67 | 20.96 | 3458.17 | 20.88 |
Minimum of Months | 584.33 | 20.49 | 4.33 | 20.49 | 0.17 | 20.49 |
Maximum of Months | 744.00 | 21.55 | 738.50 | 21.55 | 738.50 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.40 | 744.00 | 20.40 | 744.00 | 20.40 |
February | 672.00 | 20.54 | 655.67 | 20.54 | 655.67 | 20.53 |
March | 744.00 | 20.75 | 598.83 | 20.70 | 598.83 | 20.68 |
April | 719.33 | 21.35 | 223.50 | 21.23 | 223.50 | 21.16 |
May | 655.67 | 21.80 | 29.67 | 21.91 | 7.50 | 21.92 |
June | 503.83 | 21.78 | 125.00 | 22.37 | 39.67 | 22.51 |
July | 474.33 | 21.96 | 177.50 | 22.77 | 61.17 | 23.02 |
August | 541.33 | 21.80 | 102.83 | 22.21 | 38.33 | 22.32 |
September | 699.00 | 21.69 | 9.17 | 21.70 | 7.67 | 21.72 |
October | 744.00 | 21.04 | 260.17 | 20.94 | 260.17 | 20.88 |
November | 720.00 | 20.60 | 641.67 | 20.57 | 641.67 | 20.57 |
December | 744.00 | 20.45 | 743.17 | 20.45 | 743.17 | 20.45 |
Annual Sum or Average | 7961.50 | 21.12 | 4311.17 | 21.06 | 4021.33 | 20.97 |
Minimum of Months | 474.33 | 20.40 | 9.17 | 20.40 | 7.50 | 20.40 |
Maximum of Months | 744.00 | 21.96 | 744.00 | 22.77 | 744.00 | 23.02 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 679.17 | 20.51 | 679.17 | 20.50 |
February | 672.00 | 20.91 | 501.83 | 20.89 | 501.83 | 20.89 |
March | 744.00 | 21.03 | 351.33 | 21.01 | 351.33 | 21.00 |
April | 720.00 | 21.47 | 49.00 | 21.44 | 49.00 | 21.41 |
May | 739.67 | 22.48 | 0.00 | 22.48 | 0.00 | 22.48 |
June | 649.17 | 22.83 | 97.67 | 22.91 | 70.67 | 22.94 |
July | 512.33 | 23.24 | 153.33 | 23.30 | 114.17 | 23.31 |
August | 688.67 | 22.95 | 64.17 | 22.97 | 64.17 | 22.98 |
September | 714.50 | 22.26 | 15.17 | 22.26 | 15.17 | 22.27 |
October | 744.00 | 21.32 | 11.17 | 21.32 | 11.17 | 21.32 |
November | 720.00 | 21.01 | 280.83 | 21.01 | 280.83 | 21.00 |
December | 744.00 | 20.72 | 650.50 | 20.70 | 650.50 | 20.69 |
Annual Sum or Average | 8392.33 | 21.67 | 2854.17 | 21.52 | 2788.00 | 21.41 |
Minimum of Months | 512.33 | 20.53 | 0.00 | 20.51 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 23.24 | 679.17 | 23.30 | 679.17 | 23.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 742.17 | 20.47 | 742.17 | 20.47 |
February | 672.00 | 20.71 | 612.67 | 20.67 | 612.67 | 20.65 |
March | 743.67 | 20.86 | 577.50 | 20.77 | 577.50 | 20.74 |
April | 700.83 | 21.20 | 292.33 | 21.09 | 290.00 | 21.03 |
May | 673.67 | 21.48 | 29.67 | 21.52 | 11.17 | 21.51 |
June | 607.50 | 21.40 | 45.17 | 21.52 | 8.33 | 21.53 |
July | 595.50 | 21.34 | 66.83 | 21.54 | 2.83 | 21.54 |
August | 622.17 | 21.35 | 57.17 | 21.51 | 4.67 | 21.51 |
September | 662.83 | 21.38 | 23.83 | 21.41 | 12.50 | 21.42 |
October | 726.67 | 21.01 | 300.50 | 20.91 | 297.67 | 20.84 |
November | 720.00 | 20.70 | 617.83 | 20.66 | 617.83 | 20.65 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8212.83 | 21.01 | 4109.67 | 20.91 | 3921.33 | 20.84 |
Minimum of Months | 595.50 | 20.47 | 23.83 | 20.47 | 2.83 | 20.47 |
Maximum of Months | 744.00 | 21.48 | 744.00 | 21.54 | 744.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.40 | 744.00 | 20.40 | 744.00 | 20.40 |
February | 672.00 | 20.52 | 657.83 | 20.51 | 657.83 | 20.51 |
March | 744.00 | 20.62 | 662.00 | 20.58 | 662.00 | 20.57 |
April | 697.17 | 21.05 | 390.17 | 21.00 | 375.00 | 20.93 |
May | 629.50 | 21.87 | 99.17 | 22.34 | 41.33 | 22.53 |
June | 577.83 | 22.27 | 160.17 | 22.95 | 90.00 | 23.28 |
July | 553.00 | 22.40 | 195.00 | 23.16 | 103.50 | 23.54 |
August | 586.00 | 22.17 | 162.00 | 22.83 | 85.83 | 23.13 |
September | 661.67 | 21.60 | 64.67 | 21.90 | 29.50 | 22.01 |
October | 738.17 | 20.92 | 367.67 | 20.81 | 365.17 | 20.74 |
November | 720.00 | 20.54 | 669.67 | 20.52 | 669.67 | 20.52 |
December | 744.00 | 20.44 | 744.00 | 20.44 | 744.00 | 20.44 |
Annual Sum or Average | 8067.33 | 21.16 | 4916.33 | 21.17 | 4567.83 | 21.10 |
Minimum of Months | 553.00 | 20.40 | 64.67 | 20.40 | 29.50 | 20.40 |
Maximum of Months | 744.00 | 22.40 | 744.00 | 23.16 | 744.00 | 23.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.83 | 20.90 | 643.50 | 20.80 | 643.50 | 20.77 |
February | 652.50 | 21.13 | 455.67 | 21.00 | 455.67 | 20.95 |
March | 720.17 | 21.16 | 410.33 | 21.04 | 410.33 | 20.98 |
April | 674.83 | 21.32 | 139.50 | 21.25 | 137.00 | 21.20 |
May | 680.67 | 21.52 | 15.83 | 21.54 | 4.33 | 21.54 |
June | 629.83 | 21.45 | 19.83 | 21.50 | 5.67 | 21.51 |
July | 626.83 | 21.40 | 44.00 | 21.53 | 4.50 | 21.54 |
August | 640.33 | 21.41 | 49.17 | 21.54 | 1.67 | 21.54 |
September | 645.00 | 21.40 | 35.83 | 21.50 | 1.67 | 21.51 |
October | 700.83 | 21.18 | 161.67 | 21.17 | 136.00 | 21.12 |
November | 706.33 | 21.02 | 437.00 | 20.92 | 437.00 | 20.88 |
December | 744.00 | 20.79 | 676.83 | 20.72 | 676.83 | 20.69 |
Annual Sum or Average | 8163.17 | 21.21 | 3089.17 | 21.13 | 2914.17 | 21.05 |
Minimum of Months | 626.83 | 20.79 | 15.83 | 20.72 | 1.67 | 20.69 |
Maximum of Months | 744.00 | 21.52 | 676.83 | 21.54 | 676.83 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.33 | 21.82 | 220.83 | 21.30 | 220.83 | 20.98 |
February | 637.83 | 22.73 | 59.00 | 22.53 | 59.00 | 22.36 |
March | 595.17 | 23.15 | 3.83 | 23.13 | 3.83 | 23.11 |
April | 278.50 | 23.38 | 31.17 | 23.44 | 0.00 | 23.44 |
May | 28.67 | 23.52 | 368.33 | 23.95 | 6.17 | 23.95 |
June | 126.17 | 23.99 | 673.00 | 23.98 | 126.17 | 23.98 |
July | 196.17 | 24.00 | 744.00 | 23.99 | 196.17 | 23.99 |
August | 176.83 | 24.00 | 736.67 | 23.97 | 176.83 | 23.97 |
September | 74.33 | 23.72 | 515.50 | 23.94 | 47.00 | 23.95 |
October | 224.00 | 23.22 | 136.17 | 23.51 | 0.00 | 23.51 |
November | 518.50 | 23.25 | 28.83 | 23.29 | 0.00 | 23.29 |
December | 726.67 | 22.26 | 168.67 | 21.87 | 168.67 | 21.61 |
Annual Sum or Average | 4314.17 | 22.85 | 3686.00 | 23.14 | 1004.67 | 23.03 |
Minimum of Months | 28.67 | 21.82 | 3.83 | 21.30 | 0.00 | 20.98 |
Maximum of Months | 731.33 | 24.00 | 744.00 | 23.99 | 220.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 681.67 | 21.90 | 173.50 | 21.37 | 173.50 | 21.02 |
February | 562.33 | 22.85 | 35.00 | 22.69 | 35.00 | 22.54 |
March | 432.83 | 23.21 | 6.50 | 23.20 | 2.17 | 23.19 |
April | 119.83 | 23.39 | 85.00 | 23.64 | 0.00 | 23.64 |
May | 9.50 | 23.81 | 505.33 | 23.99 | 6.00 | 23.99 |
June | 114.33 | 24.00 | 703.67 | 23.99 | 114.33 | 23.99 |
July | 179.33 | 24.00 | 744.00 | 23.99 | 179.33 | 23.99 |
August | 159.83 | 24.00 | 744.00 | 23.99 | 159.83 | 23.99 |
September | 33.00 | 23.99 | 645.67 | 23.98 | 33.00 | 23.98 |
October | 92.83 | 23.29 | 305.17 | 23.83 | 0.00 | 23.83 |
November | 341.50 | 23.32 | 54.17 | 23.40 | 0.00 | 23.40 |
December | 651.50 | 22.32 | 128.33 | 21.95 | 128.33 | 21.68 |
Annual Sum or Average | 3378.50 | 22.85 | 4130.33 | 23.28 | 831.50 | 23.18 |
Minimum of Months | 9.50 | 21.90 | 6.50 | 21.37 | 0.00 | 21.02 |
Maximum of Months | 681.67 | 24.00 | 744.00 | 23.99 | 179.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.83 | 21.50 | 551.50 | 22.01 | 359.17 | 21.95 |
February | 482.50 | 22.92 | 521.00 | 23.18 | 382.00 | 23.20 |
March | 522.67 | 23.58 | 617.50 | 23.69 | 464.17 | 23.72 |
April | 497.50 | 23.96 | 659.17 | 23.93 | 489.67 | 23.95 |
May | 541.83 | 23.99 | 736.83 | 23.95 | 541.83 | 23.96 |
June | 559.33 | 23.99 | 720.00 | 23.97 | 559.33 | 23.97 |
July | 592.50 | 23.99 | 744.00 | 23.98 | 592.50 | 23.98 |
August | 578.17 | 23.99 | 744.00 | 23.97 | 578.17 | 23.98 |
September | 526.00 | 23.99 | 720.00 | 23.94 | 526.00 | 23.96 |
October | 515.17 | 23.98 | 714.50 | 23.92 | 512.33 | 23.94 |
November | 485.83 | 23.84 | 608.00 | 23.89 | 444.83 | 23.92 |
December | 484.83 | 22.17 | 564.50 | 22.58 | 364.67 | 22.55 |
Annual Sum or Average | 6288.17 | 23.52 | 7901.00 | 23.63 | 5814.67 | 23.65 |
Minimum of Months | 482.50 | 21.50 | 521.00 | 22.01 | 359.17 | 21.95 |
Maximum of Months | 592.50 | 23.99 | 744.00 | 23.98 | 592.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.31 | 699.00 | 20.29 | 699.00 | 20.28 |
February | 672.00 | 20.86 | 501.33 | 20.83 | 501.33 | 20.82 |
March | 744.00 | 21.04 | 363.67 | 21.01 | 363.67 | 20.99 |
April | 720.00 | 21.42 | 40.50 | 21.40 | 40.50 | 21.38 |
May | 662.83 | 22.38 | 28.83 | 22.44 | 0.00 | 22.44 |
June | 509.50 | 22.69 | 121.00 | 22.91 | 0.00 | 22.91 |
July | 271.83 | 22.88 | 245.83 | 23.33 | 0.00 | 23.33 |
August | 492.17 | 22.72 | 101.17 | 22.91 | 0.00 | 22.91 |
September | 698.33 | 22.13 | 8.83 | 22.15 | 0.00 | 22.15 |
October | 744.00 | 21.32 | 19.50 | 21.31 | 19.50 | 21.30 |
November | 720.00 | 21.02 | 296.50 | 21.01 | 296.50 | 21.01 |
December | 744.00 | 20.60 | 668.83 | 20.58 | 668.83 | 20.57 |
Annual Sum or Average | 7722.67 | 21.47 | 3095.00 | 21.38 | 2589.33 | 21.24 |
Minimum of Months | 271.83 | 20.31 | 8.83 | 20.29 | 0.00 | 20.28 |
Maximum of Months | 744.00 | 22.88 | 699.00 | 23.33 | 699.00 | 23.33 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56013 | 14.38200 | -0.4180 | 11.64603 |
February | 672.00000 | 22.37280 | 16.81350 | -0.2186 | 6.69787 |
March | 744.00000 | 22.31206 | 21.14061 | -0.2157 | 6.27990 |
April | 720.00000 | 22.35601 | 25.41335 | -0.1807 | 5.87006 |
May | 744.00000 | 22.58959 | 36.54089 | -1.1025 | 30.90845 |
June | 720.00000 | 22.86150 | 50.73799 | -0.9111 | 22.86755 |
July | 744.00000 | 23.39444 | 56.07602 | -0.6788 | 14.94979 |
August | 744.00000 | 23.77506 | 53.76372 | -0.5490 | 11.46688 |
September | 720.00000 | 23.88248 | 41.57132 | -0.5889 | 12.44677 |
October | 744.00000 | 23.90580 | 30.89544 | 0.26208 | 6.49785 |
November | 720.00000 | 23.87845 | 23.11911 | 0.19784 | 5.91561 |
December | 744.00000 | 22.43519 | 15.62898 | -0.1969 | 7.65283 |
Annual Sum or Average | 8760.00000 | 22.94502 | 32.26654 | -0.3849 | 11.97806 |
Minimum of Months | 672.00000 | 21.56013 | 14.38200 | -1.1025 | 5.87006 |
Maximum of Months | 744.00000 | 23.90580 | 56.07602 | 0.26208 | 30.90845 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.98599 | 13.09460 | -0.9116 | 25.62972 |
February | 672.00000 | 20.90957 | 15.65145 | -0.6168 | 16.16936 |
March | 744.00000 | 21.21675 | 20.10330 | -0.4849 | 11.96237 |
April | 720.00000 | 21.52996 | 24.52868 | -0.3113 | 8.97138 |
May | 744.00000 | 21.86693 | 35.96328 | -1.1557 | 36.11666 |
June | 720.00000 | 22.03535 | 51.45791 | -0.9838 | 28.67778 |
July | 744.00000 | 22.42478 | 57.62866 | -0.7791 | 20.79318 |
August | 744.00000 | 22.24454 | 56.99997 | -0.8578 | 24.10999 |
September | 720.00000 | 21.78435 | 45.09682 | -1.1387 | 35.77820 |
October | 744.00000 | 21.38591 | 33.42947 | -0.3074 | 9.01226 |
November | 720.00000 | 21.16012 | 24.53476 | -0.5088 | 11.47029 |
December | 744.00000 | 20.27156 | 14.84465 | -0.8556 | 22.85703 |
Annual Sum or Average | 8760.00000 | 21.40288 | 32.87882 | -0.7437 | 20.99887 |
Minimum of Months | 672.00000 | 19.98599 | 13.09460 | -1.1557 | 8.97138 |
Maximum of Months | 744.00000 | 22.42478 | 57.62866 | -0.3074 | 36.11666 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41561 | 15.65624 | -0.7051 | 17.61376 |
February | 672.00000 | 21.18469 | 18.24245 | -0.4902 | 10.86949 |
March | 744.00000 | 21.63993 | 22.39214 | -0.3450 | 8.15285 |
April | 720.00000 | 22.40182 | 26.15291 | -0.1252 | 6.02543 |
May | 744.00000 | 23.12526 | 36.32623 | -0.8499 | 21.29258 |
June | 720.00000 | 23.28635 | 50.55363 | -0.6938 | 16.06927 |
July | 744.00000 | 23.55606 | 56.58107 | -0.5484 | 11.74085 |
August | 744.00000 | 23.45723 | 55.81593 | -0.5950 | 12.99134 |
September | 720.00000 | 23.09592 | 44.56232 | -0.8089 | 19.65866 |
October | 744.00000 | 22.41482 | 34.38441 | -0.0701 | 5.87838 |
November | 720.00000 | 21.68299 | 26.51958 | -0.3126 | 7.52266 |
December | 744.00000 | 20.71799 | 17.41507 | -0.6234 | 14.38479 |
Annual Sum or Average | 8760.00000 | 22.25292 | 33.80862 | -0.5145 | 12.70224 |
Minimum of Months | 672.00000 | 20.41561 | 15.65624 | -0.8499 | 5.87838 |
Maximum of Months | 744.00000 | 23.55606 | 56.58107 | -0.0701 | 21.29258 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79708 | 10.53499 | -0.0438 | 20.62937 |
February | 672.00000 | 22.16684 | 12.79249 | 0.30065 | 15.27101 |
March | 744.00000 | 22.80572 | 16.72701 | 0.49454 | 14.44555 |
April | 720.00000 | 23.12381 | 20.68068 | 0.63022 | 15.75731 |
May | 744.00000 | 23.20605 | 31.61002 | 0.06137 | 9.84676 |
June | 720.00000 | 23.20653 | 46.04877 | 0.17835 | 10.36115 |
July | 744.00000 | 23.22691 | 52.78974 | 0.24058 | 10.64311 |
August | 744.00000 | 23.21831 | 51.78961 | 0.21961 | 10.57357 |
September | 720.00000 | 23.21259 | 39.54524 | 0.10422 | 9.87753 |
October | 744.00000 | 23.15080 | 28.58051 | 0.68778 | 17.30695 |
November | 720.00000 | 23.05411 | 20.46854 | 0.57526 | 14.53690 |
December | 744.00000 | 21.39141 | 12.03143 | 0.10274 | 17.37739 |
Annual Sum or Average | 8760.00000 | 22.71306 | 28.73000 | 0.29509 | 13.88789 |
Minimum of Months | 672.00000 | 20.79708 | 10.53499 | -0.0438 | 9.84676 |
Maximum of Months | 744.00000 | 23.22691 | 52.78974 | 0.68778 | 20.62937 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.27790 | 17.84311 | -0.7383 | 19.87073 |
February | 672.00000 | 21.27145 | 20.45707 | -0.4251 | 12.03947 |
March | 744.00000 | 21.72394 | 24.75238 | -0.2657 | 8.72293 |
April | 720.00000 | 22.29210 | 28.82251 | -0.0495 | 6.90804 |
May | 744.00000 | 22.86765 | 39.37937 | -0.7495 | 19.30323 |
June | 720.00000 | 23.02874 | 53.80940 | -0.5823 | 14.23683 |
July | 744.00000 | 23.31333 | 59.85700 | -0.4130 | 10.04919 |
August | 744.00000 | 23.22772 | 59.06107 | -0.4576 | 11.58736 |
September | 720.00000 | 22.81887 | 47.69152 | -0.7155 | 18.79773 |
October | 744.00000 | 22.12858 | 37.22909 | -0.0482 | 7.32450 |
November | 720.00000 | 21.54988 | 29.11127 | -0.3137 | 8.39456 |
December | 744.00000 | 20.51821 | 19.69451 | -0.6916 | 17.33053 |
Annual Sum or Average | 8760.00000 | 22.08785 | 36.57028 | -0.4548 | 12.89606 |
Minimum of Months | 672.00000 | 20.27790 | 17.84311 | -0.7495 | 6.90804 |
Maximum of Months | 744.00000 | 23.31333 | 59.85700 | -0.0482 | 19.87073 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.61780 | 17.94203 | -0.6236 | 15.72417 |
February | 672.00000 | 21.56163 | 20.53013 | -0.3645 | 8.98703 |
March | 744.00000 | 22.06792 | 24.63418 | -0.2087 | 6.79950 |
April | 720.00000 | 22.76742 | 28.39961 | 0.00314 | 5.69312 |
May | 744.00000 | 23.33376 | 38.57878 | -0.7147 | 16.67782 |
June | 720.00000 | 23.46022 | 52.56173 | -0.5650 | 12.48868 |
July | 744.00000 | 23.63559 | 58.64855 | -0.4471 | 9.56566 |
August | 744.00000 | 23.59871 | 57.76627 | -0.4734 | 10.20397 |
September | 720.00000 | 23.37786 | 46.47850 | -0.6479 | 14.71905 |
October | 744.00000 | 22.79183 | 36.39651 | 0.06138 | 6.05096 |
November | 720.00000 | 22.11243 | 28.64029 | -0.1792 | 6.40225 |
December | 744.00000 | 20.95559 | 19.71391 | -0.5368 | 12.60090 |
Annual Sum or Average | 8760.00000 | 22.52685 | 35.94886 | -0.3921 | 10.51245 |
Minimum of Months | 672.00000 | 20.61780 | 17.94203 | -0.7147 | 5.69312 |
Maximum of Months | 744.00000 | 23.63559 | 58.64855 | 0.06138 | 16.67782 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51277 | 21.44707 | -0.8482 | 20.68790 |
February | 672.00000 | 20.79794 | 23.55023 | -0.7066 | 16.44816 |
March | 744.00000 | 20.94852 | 27.94505 | -0.5926 | 13.49985 |
April | 720.00000 | 21.32839 | 32.42529 | -0.3873 | 9.38172 |
May | 744.00000 | 21.66843 | 41.23644 | -1.2495 | 39.31924 |
June | 720.00000 | 21.69745 | 51.18088 | -1.1432 | 34.24058 |
July | 744.00000 | 21.72654 | 52.98176 | -1.0755 | 31.27557 |
August | 744.00000 | 21.68607 | 54.24346 | -1.1300 | 33.67123 |
September | 720.00000 | 21.56834 | 50.33726 | -1.2892 | 41.11653 |
October | 744.00000 | 21.15723 | 41.95704 | -0.4081 | 9.55661 |
November | 720.00000 | 20.79838 | 32.74661 | -0.6390 | 14.29360 |
December | 744.00000 | 20.49944 | 23.15207 | -0.8452 | 20.56867 |
Annual Sum or Average | 8760.00000 | 21.20079 | 37.84098 | -0.8607 | 23.71910 |
Minimum of Months | 672.00000 | 20.49944 | 21.44707 | -1.2892 | 9.38172 |
Maximum of Months | 744.00000 | 21.72654 | 54.24346 | -0.3873 | 41.11653 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.42094 | 21.57963 | -0.9051 | 22.92134 |
February | 672.00000 | 20.55603 | 23.90699 | -0.8027 | 19.20996 |
March | 744.00000 | 20.67885 | 28.34660 | -0.6897 | 15.82378 |
April | 720.00000 | 21.24089 | 32.62809 | -0.4400 | 10.50186 |
May | 744.00000 | 22.17796 | 40.87902 | -1.1273 | 36.49843 |
June | 720.00000 | 22.52503 | 50.45707 | -0.9132 | 28.79227 |
July | 744.00000 | 22.68884 | 52.69962 | -0.8077 | 25.35744 |
August | 744.00000 | 22.49595 | 54.27943 | -0.9166 | 28.33266 |
September | 720.00000 | 21.85016 | 50.46549 | -1.2468 | 40.53676 |
October | 744.00000 | 21.04304 | 42.31994 | -0.4622 | 10.30444 |
November | 720.00000 | 20.60278 | 33.10127 | -0.7054 | 16.02391 |
December | 744.00000 | 20.45765 | 23.24804 | -0.8826 | 22.04262 |
Annual Sum or Average | 8760.00000 | 21.39999 | 37.89829 | -0.8251 | 23.04993 |
Minimum of Months | 672.00000 | 20.42094 | 21.57963 | -1.2468 | 10.30444 |
Maximum of Months | 744.00000 | 22.68884 | 54.27943 | -0.4400 | 40.53676 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43054 | 20.38133 | -0.7976 | 19.18773 |
February | 672.00000 | 20.69008 | 22.91222 | -0.7015 | 15.80049 |
March | 744.00000 | 20.85260 | 27.39674 | -0.6137 | 13.24967 |
April | 720.00000 | 21.22972 | 31.69362 | -0.4507 | 9.50892 |
May | 744.00000 | 21.81219 | 40.17947 | -1.3287 | 42.67464 |
June | 720.00000 | 22.12138 | 50.33711 | -1.1333 | 33.61874 |
July | 744.00000 | 22.22485 | 54.56024 | -1.0634 | 30.60697 |
August | 744.00000 | 22.07727 | 54.84623 | -1.1370 | 33.56740 |
September | 720.00000 | 21.60213 | 48.92003 | -1.3711 | 44.43177 |
October | 744.00000 | 21.19238 | 40.99983 | -0.4062 | 8.59445 |
November | 720.00000 | 20.88633 | 31.91380 | -0.5760 | 12.29390 |
December | 744.00000 | 20.53263 | 22.09783 | -0.7587 | 17.77971 |
Annual Sum or Average | 8760.00000 | 21.30768 | 37.26518 | -0.8626 | 23.48901 |
Minimum of Months | 672.00000 | 20.43054 | 20.38133 | -1.3711 | 8.59445 |
Maximum of Months | 744.00000 | 22.22485 | 54.84623 | -0.4062 | 44.43177 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49104 | 21.43725 | -0.8517 | 20.83870 |
February | 672.00000 | 20.80196 | 23.53323 | -0.7058 | 16.33400 |
March | 744.00000 | 21.03809 | 27.81400 | -0.5728 | 13.11905 |
April | 720.00000 | 21.43279 | 32.34495 | -0.3569 | 9.05457 |
May | 744.00000 | 21.70564 | 41.07288 | -1.2436 | 39.04940 |
June | 720.00000 | 21.72619 | 50.54603 | -1.1208 | 33.31636 |
July | 744.00000 | 21.74152 | 52.42640 | -1.0714 | 31.18062 |
August | 744.00000 | 21.70407 | 53.96728 | -1.1304 | 33.69712 |
September | 720.00000 | 21.58711 | 50.28123 | -1.2857 | 40.97850 |
October | 744.00000 | 21.17273 | 41.83164 | -0.4091 | 9.54406 |
November | 720.00000 | 20.78056 | 32.75682 | -0.6419 | 14.34303 |
December | 744.00000 | 20.49195 | 23.14221 | -0.8453 | 20.61004 |
Annual Sum or Average | 8760.00000 | 21.22452 | 37.66916 | -0.8542 | 23.55434 |
Minimum of Months | 672.00000 | 20.49104 | 21.43725 | -1.2857 | 9.05457 |
Maximum of Months | 744.00000 | 21.74152 | 53.96728 | -0.3569 | 40.97850 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.40429 | 21.53301 | -0.9092 | 23.13612 |
February | 672.00000 | 20.54219 | 23.90604 | -0.8064 | 19.27300 |
March | 744.00000 | 20.75181 | 28.18064 | -0.6743 | 15.31007 |
April | 720.00000 | 21.34988 | 32.44166 | -0.4091 | 9.63603 |
May | 744.00000 | 22.05170 | 40.67869 | -1.1708 | 36.32840 |
June | 720.00000 | 22.43800 | 50.04531 | -0.9245 | 27.45257 |
July | 744.00000 | 22.64570 | 52.55788 | -0.8191 | 24.64015 |
August | 744.00000 | 22.34696 | 54.44311 | -0.9654 | 27.96697 |
September | 720.00000 | 21.74125 | 50.46052 | -1.2813 | 40.71977 |
October | 744.00000 | 21.04391 | 42.18370 | -0.4676 | 10.25388 |
November | 720.00000 | 20.59647 | 33.08548 | -0.7063 | 16.09814 |
December | 744.00000 | 20.45403 | 23.20416 | -0.8831 | 22.10347 |
Annual Sum or Average | 8760.00000 | 21.36877 | 37.79884 | -0.8350 | 22.76370 |
Minimum of Months | 672.00000 | 20.40429 | 21.53301 | -1.2813 | 9.63603 |
Maximum of Months | 744.00000 | 22.64570 | 54.44311 | -0.4091 | 40.71977 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46939 | 21.72157 | -0.9119 | 23.06925 |
February | 672.00000 | 20.70956 | 23.90771 | -0.7741 | 18.61606 |
March | 744.00000 | 20.86347 | 28.42415 | -0.6485 | 15.14910 |
April | 720.00000 | 21.25532 | 32.98958 | -0.4253 | 10.31773 |
May | 744.00000 | 21.64987 | 41.71954 | -1.2627 | 40.21281 |
June | 720.00000 | 21.68473 | 52.07058 | -1.1461 | 34.62020 |
July | 744.00000 | 21.71634 | 54.09706 | -1.0753 | 31.51856 |
August | 744.00000 | 21.66621 | 55.70195 | -1.1365 | 34.18848 |
September | 720.00000 | 21.52810 | 51.59858 | -1.3192 | 42.79166 |
October | 744.00000 | 21.06575 | 42.87141 | -0.4539 | 10.61334 |
November | 720.00000 | 20.70477 | 33.40065 | -0.6995 | 16.05920 |
December | 744.00000 | 20.47263 | 23.44904 | -0.9055 | 22.81966 |
Annual Sum or Average | 8760.00000 | 21.15087 | 38.57185 | -0.8975 | 25.04006 |
Minimum of Months | 672.00000 | 20.46939 | 21.72157 | -1.3192 | 10.31773 |
Maximum of Months | 744.00000 | 21.71634 | 55.70195 | -0.4253 | 42.79166 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.39594 | 21.82303 | -0.9659 | 25.34634 |
February | 672.00000 | 20.51585 | 24.22731 | -0.8632 | 21.35542 |
March | 744.00000 | 20.62366 | 28.79614 | -0.7430 | 17.52261 |
April | 720.00000 | 21.18202 | 33.24261 | -0.4767 | 11.65826 |
May | 744.00000 | 22.22951 | 41.19948 | -1.1148 | 37.46020 |
June | 720.00000 | 22.59546 | 50.84870 | -0.8840 | 29.58432 |
July | 744.00000 | 22.74378 | 53.16621 | -0.7812 | 26.10445 |
August | 744.00000 | 22.55275 | 54.98313 | -0.8952 | 29.09824 |
September | 720.00000 | 21.83857 | 51.59952 | -1.2681 | 42.32849 |
October | 744.00000 | 20.94202 | 43.27697 | -0.5125 | 11.53058 |
November | 720.00000 | 20.53685 | 33.73406 | -0.7624 | 17.85020 |
December | 744.00000 | 20.44209 | 23.51963 | -0.9409 | 24.31086 |
Annual Sum or Average | 8760.00000 | 21.38864 | 38.44059 | -0.8506 | 24.52921 |
Minimum of Months | 672.00000 | 20.39594 | 21.82303 | -1.2681 | 11.53058 |
Maximum of Months | 744.00000 | 22.74378 | 54.98313 | -0.4767 | 42.32849 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90490 | 23.65079 | -0.6948 | 16.60080 |
February | 672.00000 | 21.18969 | 25.61742 | -0.5515 | 13.33032 |
March | 744.00000 | 21.23333 | 29.74637 | -0.4848 | 11.67009 |
April | 720.00000 | 21.45063 | 33.91255 | -0.3460 | 9.04643 |
May | 744.00000 | 21.67170 | 42.11316 | -1.2904 | 41.43007 |
June | 720.00000 | 21.68299 | 52.01549 | -1.2006 | 36.95388 |
July | 744.00000 | 21.70789 | 54.36073 | -1.1402 | 34.24919 |
August | 744.00000 | 21.67455 | 54.84947 | -1.1666 | 35.51230 |
September | 720.00000 | 21.60444 | 50.16878 | -1.2788 | 40.92497 |
October | 744.00000 | 21.30165 | 42.60971 | -0.3475 | 8.91522 |
November | 720.00000 | 21.06322 | 34.16997 | -0.5358 | 12.34706 |
December | 744.00000 | 20.79242 | 25.30596 | -0.7275 | 17.35120 |
Annual Sum or Average | 8760.00000 | 21.35679 | 39.11511 | -0.8156 | 23.25757 |
Minimum of Months | 672.00000 | 20.79242 | 23.65079 | -1.2904 | 8.91522 |
Maximum of Months | 744.00000 | 21.70789 | 54.84947 | -0.3460 | 41.43007 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.85223 | 20.48859 | -0.3379 | 11.68813 |
February | 672.00000 | 22.79570 | 22.84856 | -0.0810 | 6.95203 |
March | 744.00000 | 23.31829 | 26.23419 | 0.09386 | 6.16527 |
April | 720.00000 | 23.73998 | 29.10993 | 0.26288 | 6.79132 |
May | 744.00000 | 23.93824 | 38.39181 | -0.4239 | 9.11291 |
June | 720.00000 | 23.97359 | 51.70969 | -0.2821 | 6.88078 |
July | 744.00000 | 23.98399 | 58.02128 | -0.2184 | 6.08549 |
August | 744.00000 | 23.96029 | 57.32598 | -0.2589 | 6.52461 |
September | 720.00000 | 23.89748 | 46.31792 | -0.4112 | 8.84258 |
October | 744.00000 | 23.72960 | 36.73304 | 0.31060 | 7.34056 |
November | 720.00000 | 23.44910 | 29.65697 | 0.15031 | 6.17521 |
December | 744.00000 | 22.29961 | 22.07784 | -0.2184 | 8.97531 |
Annual Sum or Average | 8760.00000 | 23.41269 | 36.66041 | -0.1187 | 7.63839 |
Minimum of Months | 672.00000 | 21.85223 | 20.48859 | -0.4239 | 6.08549 |
Maximum of Months | 744.00000 | 23.98399 | 58.02128 | 0.31060 | 11.68813 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07915 | 19.77705 | -0.2448 | 10.81789 |
February | 672.00000 | 23.03982 | 21.99690 | 0.01699 | 6.80578 |
March | 744.00000 | 23.52929 | 25.20325 | 0.18465 | 6.50358 |
April | 720.00000 | 23.87134 | 28.11349 | 0.33358 | 7.53448 |
May | 744.00000 | 23.98001 | 37.66971 | -0.3602 | 7.97706 |
June | 720.00000 | 23.99182 | 51.09071 | -0.2301 | 6.29412 |
July | 744.00000 | 23.99365 | 57.48651 | -0.1736 | 5.71208 |
August | 744.00000 | 23.98660 | 56.68956 | -0.2056 | 5.97746 |
September | 720.00000 | 23.95855 | 45.47416 | -0.3388 | 7.60132 |
October | 744.00000 | 23.86140 | 35.66182 | 0.38185 | 8.23310 |
November | 720.00000 | 23.66188 | 28.57090 | 0.24279 | 6.71125 |
December | 744.00000 | 22.52742 | 21.27830 | -0.1238 | 8.41309 |
Annual Sum or Average | 8760.00000 | 23.54056 | 35.83601 | -0.0441 | 7.39030 |
Minimum of Months | 672.00000 | 22.07915 | 19.77705 | -0.3602 | 5.71208 |
Maximum of Months | 744.00000 | 23.99365 | 57.48651 | 0.38185 | 10.81789 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.14890 | 20.10951 | 0.39916 | 22.33689 |
February | 672.00000 | 23.09266 | 20.80830 | 0.66644 | 22.39195 |
March | 744.00000 | 23.56332 | 23.69883 | 0.84054 | 24.27127 |
April | 720.00000 | 23.81232 | 26.89471 | 0.99042 | 28.04811 |
May | 744.00000 | 23.91086 | 36.94138 | 0.59723 | 17.35504 |
June | 720.00000 | 23.94772 | 50.28031 | 0.74717 | 21.03132 |
July | 744.00000 | 23.96320 | 56.58570 | 0.81354 | 23.00975 |
August | 744.00000 | 23.95402 | 55.67752 | 0.76374 | 21.35018 |
September | 720.00000 | 23.90678 | 44.38436 | 0.60528 | 17.02751 |
October | 744.00000 | 23.83133 | 34.33655 | 1.02394 | 29.16306 |
November | 720.00000 | 23.72885 | 27.07915 | 0.88807 | 24.19350 |
December | 744.00000 | 22.60495 | 21.03338 | 0.51530 | 21.31954 |
Annual Sum or Average | 8760.00000 | 23.53901 | 34.90865 | 0.73738 | 22.62730 |
Minimum of Months | 672.00000 | 22.14890 | 20.10951 | 0.39916 | 17.02751 |
Maximum of Months | 744.00000 | 23.96320 | 56.58570 | 1.02394 | 29.16306 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.13318 | 12.51439 | -0.8532 | 22.21160 |
February | 672.00000 | 20.86008 | 15.01325 | -0.6536 | 14.29705 |
March | 744.00000 | 20.98578 | 19.52162 | -0.5749 | 12.04477 |
April | 720.00000 | 21.23756 | 23.98273 | -0.4521 | 9.54374 |
May | 744.00000 | 22.30715 | 34.26136 | -1.1892 | 35.71041 |
June | 720.00000 | 22.82749 | 48.69408 | -0.9171 | 23.72366 |
July | 744.00000 | 23.25359 | 54.76349 | -0.7273 | 16.46555 |
August | 744.00000 | 22.98324 | 54.19555 | -0.8279 | 19.82671 |
September | 720.00000 | 22.30716 | 43.05195 | -1.1342 | 32.68899 |
October | 744.00000 | 21.35536 | 32.78748 | -0.3655 | 8.14331 |
November | 720.00000 | 21.00771 | 23.84227 | -0.5336 | 11.06335 |
December | 744.00000 | 20.53194 | 14.15441 | -0.7489 | 17.77071 |
Annual Sum or Average | 8760.00000 | 21.65353 | 31.49493 | -0.7488 | 18.65281 |
Minimum of Months | 672.00000 | 20.13318 | 12.51439 | -1.1892 | 8.14331 |
Maximum of Months | 744.00000 | 23.25359 | 54.76349 | -0.3655 | 35.71041 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52913 | 15.48991 | -0.7198 | 16.80050 |
February | 672.00000 | 20.91013 | 18.20531 | -0.6005 | 12.75966 |
March | 744.00000 | 21.02949 | 22.71853 | -0.5331 | 11.06000 |
April | 720.00000 | 21.46942 | 26.88656 | -0.3854 | 8.48651 |
May | 744.00000 | 22.48518 | 37.05054 | -1.1272 | 32.60309 |
June | 720.00000 | 22.91298 | 51.25746 | -0.8859 | 22.36651 |
July | 744.00000 | 23.35882 | 57.06512 | -0.6884 | 15.19833 |
August | 744.00000 | 22.99501 | 56.97012 | -0.8206 | 19.60354 |
September | 720.00000 | 22.26668 | 46.16890 | -1.1473 | 33.46221 |
October | 744.00000 | 21.32446 | 35.94477 | -0.3701 | 8.19435 |
November | 720.00000 | 21.00763 | 27.04010 | -0.5219 | 10.77532 |
December | 744.00000 | 20.71780 | 17.24578 | -0.6696 | 14.90617 |
Annual Sum or Average | 8760.00000 | 21.75568 | 34.43114 | -0.7064 | 17.20365 |
Minimum of Months | 672.00000 | 20.52913 | 15.48991 | -1.1473 | 8.19435 |
Maximum of Months | 744.00000 | 23.35882 | 57.06512 | -0.3701 | 33.46221 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31202 | 13.52413 | -0.8093 | 20.61987 |
February | 672.00000 | 20.86205 | 16.21026 | -0.6354 | 13.97451 |
March | 744.00000 | 21.04343 | 20.68996 | -0.5369 | 11.28323 |
April | 720.00000 | 21.42193 | 24.94019 | -0.3820 | 8.52630 |
May | 744.00000 | 22.51736 | 34.85445 | -1.0675 | 30.57542 |
June | 720.00000 | 22.97525 | 48.92491 | -0.8097 | 20.14431 |
July | 744.00000 | 23.36346 | 54.81160 | -0.6293 | 14.01592 |
August | 744.00000 | 23.01861 | 54.73614 | -0.7592 | 18.03645 |
September | 720.00000 | 22.17585 | 44.26840 | -1.1327 | 33.05283 |
October | 744.00000 | 21.32024 | 33.90877 | -0.3555 | 8.10811 |
November | 720.00000 | 21.01556 | 25.05033 | -0.5219 | 10.81902 |
December | 744.00000 | 20.60101 | 15.25373 | -0.7315 | 17.27838 |
Annual Sum or Average | 8760.00000 | 21.72399 | 32.35766 | -0.6979 | 17.21918 |
Minimum of Months | 672.00000 | 20.31202 | 13.52413 | -1.1327 | 8.10811 |
Maximum of Months | 744.00000 | 23.36346 | 54.81160 | -0.3555 | 33.05283 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31340 | 12.11404 | -0.8016 | 20.11152 |
February | 672.00000 | 20.90868 | 14.62452 | -0.6293 | 13.54841 |
March | 744.00000 | 21.01892 | 19.10648 | -0.5559 | 11.59182 |
April | 720.00000 | 21.41249 | 23.37487 | -0.4102 | 8.87050 |
May | 744.00000 | 22.57646 | 33.36824 | -1.1061 | 31.94698 |
June | 720.00000 | 23.07121 | 47.63877 | -0.8417 | 20.87564 |
July | 744.00000 | 23.49369 | 53.62823 | -0.6522 | 14.25867 |
August | 744.00000 | 23.25638 | 52.97342 | -0.7429 | 17.01791 |
September | 720.00000 | 22.62070 | 41.91566 | -1.0367 | 28.35597 |
October | 744.00000 | 21.58368 | 31.98256 | -0.3124 | 7.47916 |
November | 720.00000 | 21.05214 | 23.39515 | -0.5126 | 10.62529 |
December | 744.00000 | 20.66499 | 13.75977 | -0.7062 | 16.19143 |
Annual Sum or Average | 8760.00000 | 21.83636 | 30.75105 | -0.6927 | 16.76082 |
Minimum of Months | 672.00000 | 20.31340 | 12.11404 | -1.1061 | 7.47916 |
Maximum of Months | 744.00000 | 23.49369 | 53.62823 | -0.3124 | 31.94698 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.366560E+09 | 7222.41 | 27-JAN-16:01 | 50.40 | 0.114218E+10 | 0.00 | 0.150874E+10 | 0.21 | 3.12 | 01-JAN-10:31 | 0.00 | 0.00 |
February | 0.108370E+10 | 14418.35 | 28-FEB-16:02 | 130.65 | 0.337673E+10 | 0.00 | 0.446043E+10 | 0.61 | 3.12 | 04-FEB-17:30 | 0.00 | 0.00 |
March | 0.290936E+10 | 34130.77 | 31-MAR-18:01 | 193.36 | 0.906535E+10 | 0.00 | 0.119747E+11 | 0.81 | 3.12 | 06-MAR-15:30 | 0.00 | 0.00 |
April | 0.178536E+11 | 109422.07 | 23-APR-18:03 | 422.48 | 0.538441E+11 | 0.00 | 0.716976E+11 | 1.81 | 3.68 | 13-APR-15:03 | 0.00 | 0.00 |
May | 0.727520E+11 | 146458.21 | 25-MAY-18:03 | 726.32 | 0.216189E+12 | 0.00 | 0.288941E+12 | 2.95 | 3.68 | 04-MAY-15:03 | 0.00 | 0.00 |
June | 0.135840E+12 | 214112.99 | 29-JUN-18:03 | 719.33 | 0.432289E+12 | 0.00 | 0.568128E+12 | 3.09 | 4.15 | 27-JUN-21:52 | 0.00 | 0.00 |
July | 0.176818E+12 | 181508.35 | 15-JUL-15:03 | 744.00 | 0.584370E+12 | 0.00 | 0.761188E+12 | 3.19 | 4.18 | 21-JUL-21:52 | 0.00 | 0.00 |
August | 0.132479E+12 | 179697.02 | 08-AUG-15:03 | 742.97 | 0.422872E+12 | 0.00 | 0.555352E+12 | 3.09 | 4.15 | 09-AUG-21:52 | 0.00 | 0.00 |
September | 0.489652E+11 | 125438.99 | 01-SEP-15:03 | 684.01 | 0.146260E+12 | 0.00 | 0.195226E+12 | 2.90 | 3.87 | 01-SEP-08:52 | 0.00 | 0.00 |
October | 0.133691E+11 | 92584.46 | 19-OCT-15:03 | 379.14 | 0.401997E+11 | 0.00 | 0.535688E+11 | 1.58 | 3.63 | 22-OCT-15:03 | 0.00 | 0.00 |
November | 0.152725E+10 | 52774.76 | 01-NOV-15:02 | 119.76 | 0.465756E+10 | 0.00 | 0.618481E+10 | 0.52 | 3.12 | 19-NOV-09:01 | 0.00 | 0.00 |
December | 0.220738E+09 | 6588.58 | 06-DEC-19:05 | 34.01 | 0.687805E+09 | 0.00 | 0.908544E+09 | 0.14 | 3.12 | 01-DEC-09:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.604185E+12 | 4946.43 | 0.191495E+13 | 0.00 | 0.251914E+13 | 1.75 | 0.00 | 0.00 | ||||
Minimum of Months | 0.220738E+09 | 6588.58 | 34.01 | 0.687805E+09 | 0.00 | 0.908544E+09 | 0.14 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.176818E+12 | 214112.99 | 744.00 | 0.584370E+12 | 0.00 | 0.761188E+12 | 3.19 | 4.18 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.715350E+12 | 0.00 | 744.00 | 680027.24 | 06-JAN-05:00 | 0.00 | 36.66 | 60.00 | 2.72 | 0.00 | 0.35 | 0.90 | 06-JAN-05:00 |
February | 0.397742E+12 | 0.00 | 672.00 | 659332.77 | 17-FEB-06:00 | 0.00 | 37.76 | 60.00 | 1.70 | 0.00 | 0.22 | 0.87 | 17-FEB-06:00 |
March | 0.243975E+12 | 0.00 | 743.98 | 616808.78 | 05-MAR-07:00 | 0.00 | 38.22 | 60.00 | 0.96 | 0.00 | 0.12 | 0.82 | 05-MAR-07:00 |
April | 0.768348E+11 | 0.00 | 628.66 | 190655.07 | 07-APR-18:04 | 0.00 | 38.05 | 56.03 | 0.32 | 0.00 | 0.04 | 0.25 | 07-APR-18:04 |
May | 0.545026E+11 | 0.00 | 410.36 | 145278.63 | 05-MAY-08:05 | 0.00 | 30.01 | 45.06 | 0.17 | 0.00 | 0.03 | 0.19 | 05-MAY-08:05 |
June | 0.269600E+11 | 0.00 | 245.38 | 117775.40 | 16-JUN-22:40 | 0.00 | 29.32 | 40.04 | 0.08 | 0.00 | 0.01 | 0.16 | 16-JUN-22:40 |
July | 0.203737E+11 | 0.00 | 138.78 | 113948.19 | 02-JUL-04:30 | 0.00 | 27.69 | 33.86 | 0.06 | 0.00 | 0.01 | 0.15 | 02-JUL-04:30 |
August | 0.203462E+11 | 0.00 | 196.08 | 113430.82 | 19-AUG-00:40 | 0.00 | 28.09 | 36.64 | 0.06 | 0.00 | 0.01 | 0.15 | 19-AUG-00:40 |
September | 0.697473E+11 | 0.00 | 479.42 | 151780.12 | 25-SEP-08:05 | 0.00 | 30.87 | 49.30 | 0.22 | 0.00 | 0.04 | 0.20 | 25-SEP-08:05 |
October | 0.876764E+11 | 0.00 | 693.19 | 194992.75 | 31-OCT-08:03 | 0.00 | 39.64 | 57.99 | 0.36 | 0.00 | 0.04 | 0.26 | 31-OCT-08:03 |
November | 0.163610E+12 | 0.00 | 720.00 | 262625.67 | 25-NOV-09:03 | 0.00 | 39.08 | 60.00 | 0.71 | 0.00 | 0.08 | 0.35 | 25-NOV-09:03 |
December | 0.637421E+12 | 0.00 | 744.00 | 667419.12 | 24-DEC-06:00 | 0.00 | 37.23 | 60.00 | 2.48 | 0.00 | 0.31 | 0.88 | 24-DEC-06:00 |
Annual Sum or Average | 0.251454E+13 | 0.00 | 6415.84 | 0.00 | 34.36 | 51.51 | 0.82 | 0.00 | 0.11 | ||||
Minimum of Months | 0.203462E+11 | 0.00 | 138.78 | 113430.82 | 0.00 | 27.69 | 33.86 | 0.06 | 0.00 | 0.01 | 0.15 | ||
Maximum of Months | 0.715350E+12 | 0.00 | 744.00 | 680027.24 | 0.00 | 39.64 | 60.00 | 2.72 | 0.00 | 0.35 | 0.90 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.134043E+11 | 0.00 | 69.50 | 0.134043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185320.06 | 23-APR-18:10 | 185320.06 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.103904E+12 | 0.00 | 323.96 | 0.101607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280185.54 | 25-MAY-18:20 | 234854.45 | 25-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.274519E+12 | 0.00 | 504.42 | 0.191042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 474499.08 | 27-JUN-19:50 | 273783.96 | 29-JUN-18:05 | 0.00 | 0.00 | 0.00 |
July | 0.384403E+12 | 0.00 | 612.33 | 0.246494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 506740.44 | 21-JUL-19:20 | 236666.13 | 24-JUL-18:07 | 0.00 | 0.00 | 0.00 |
August | 0.260060E+12 | 0.00 | 572.33 | 0.181312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 458574.98 | 31-AUG-19:05 | 232528.82 | 08-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.582176E+11 | 0.00 | 238.11 | 0.502166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 255913.38 | 01-SEP-10:50 | 189024.38 | 01-SEP-15:13 | 0.00 | 0.00 | 0.00 |
October | 0.814646E+10 | 0.00 | 46.50 | 0.814646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131669.33 | 19-OCT-15:04 | 131669.33 | 19-OCT-15:04 | 0.00 | 0.00 | 0.00 |
November | 0.104414E+10 | 0.00 | 8.00 | 0.104414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54235.74 | 01-NOV-15:30 | 54235.74 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110370E+13 | 0.00 | 2375.16 | 0.793267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.384403E+12 | 0.00 | 612.33 | 0.246494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 506740.44 | 273783.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.823506E+09 | 0.00 | 40.83 | 0.823506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17157.66 | 23-APR-15:01 | 17157.66 | 23-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.698869E+10 | 0.00 | 227.00 | 0.673715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22951.99 | 26-MAY-09:03 | 18449.27 | 25-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.194790E+11 | 0.00 | 366.83 | 0.130069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37981.96 | 25-JUN-08:04 | 20613.55 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.282154E+11 | 0.00 | 464.17 | 0.170906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41146.07 | 05-JUL-13:00 | 19339.23 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.191980E+11 | 0.00 | 436.17 | 0.124591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36218.62 | 31-AUG-20:40 | 19166.92 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.390866E+10 | 0.00 | 149.17 | 0.315383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24121.93 | 01-SEP-01:00 | 17389.31 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.525162E+09 | 0.00 | 24.67 | 0.525162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14575.81 | 19-OCT-15:01 | 14575.81 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 78057595.70 | 0.00 | 4.83 | 78057595.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7087.99 | 01-NOV-15:02 | 7087.99 | 01-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792165E+11 | 0.00 | 1713.67 | 0.538743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.282154E+11 | 0.00 | 464.17 | 0.170906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41146.07 | 20613.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1483618.25 | 0.00 | 0.45 | 1483618.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7607.26 | 27-JAN-16:01 | 7607.26 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.174593E+09 | 0.00 | 23.34 | 0.174462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19556.63 | 04-FEB-16:01 | 19556.63 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.664292E+09 | 0.00 | 74.44 | 0.664055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19574.70 | 28-MAR-18:01 | 19574.70 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.232432E+10 | 0.00 | 240.87 | 0.216525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19570.14 | 16-APR-15:01 | 19570.14 | 16-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.631597E+10 | 0.00 | 585.95 | 0.440435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19574.48 | 04-MAY-15:01 | 19574.48 | 04-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.819312E+10 | 0.00 | 635.66 | 0.459695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21106.35 | 10-JUN-15:02 | 19578.69 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.108875E+11 | 0.00 | 700.20 | 0.593692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20505.06 | 05-JUL-08:61 | 17346.67 | 08-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.865489E+10 | 0.00 | 656.52 | 0.440273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20980.82 | 30-AUG-08:61 | 17301.95 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.409333E+10 | 0.00 | 474.36 | 0.217963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20458.90 | 19-SEP-15:02 | 19575.84 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.116927E+10 | 0.00 | 154.58 | 0.691433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19574.80 | 21-OCT-18:01 | 19574.80 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 33692061.78 | 0.00 | 9.24 | 31902131.95 | 0.00 | 0.00 | 0.00 | 0.00 | 19552.59 | 17-NOV-16:01 | 19552.59 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425125E+11 | 0.00 | 3555.62 | 0.252492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108875E+11 | 0.00 | 700.20 | 0.593692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21106.35 | 19578.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 218107.58 | 0.00 | 0.05 | 218107.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.29 | 17-JAN-16:04 | 1910.29 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 26367073.86 | 0.00 | 6.62 | 26282592.41 | 0.00 | 0.00 | 0.00 | 0.00 | 17850.72 | 28-FEB-16:02 | 17850.72 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.257385E+09 | 0.00 | 36.08 | 0.257239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18654.17 | 28-MAR-18:01 | 18654.17 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.119001E+10 | 0.00 | 152.94 | 0.108292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21339.13 | 11-APR-18:11 | 21339.13 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.428914E+10 | 0.00 | 463.20 | 0.280992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21974.24 | 06-MAY-18:42 | 21974.24 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.598717E+10 | 0.00 | 483.04 | 0.321435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22360.24 | 25-JUN-08:51 | 18655.16 | 03-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.794721E+10 | 0.00 | 513.26 | 0.424464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22649.27 | 30-JUL-08:41 | 19075.83 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.555774E+10 | 0.00 | 475.97 | 0.256263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20604.55 | 30-AUG-08:51 | 19041.76 | 07-AUG-16:21 | 0.00 | 0.00 | 0.00 |
September | 0.200955E+10 | 0.00 | 333.86 | 0.836101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21191.83 | 23-SEP-17:41 | 21191.83 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 0.330555E+09 | 0.00 | 69.65 | 0.163107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18035.58 | 21-OCT-18:32 | 18035.58 | 21-OCT-18:32 | 0.00 | 0.00 | 0.00 |
November | 4303609.03 | 0.00 | 0.74 | 2902849.13 | 0.00 | 0.00 | 0.00 | 0.00 | 10980.71 | 17-NOV-16:01 | 10980.71 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275997E+11 | 0.00 | 2535.41 | 0.152003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.794721E+10 | 0.00 | 513.26 | 0.424464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22649.27 | 21974.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 1623355.13 | 0.00 | 0.25 | 1623355.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2270.08 | 28-FEB-14:55 | 2270.08 | 28-FEB-14:55 | 0.00 | 0.00 | 0.00 |
March | 0.246875E+10 | 0.00 | 64.99 | 0.246875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36375.43 | 29-MAR-12:30 | 36375.43 | 29-MAR-12:30 | 0.00 | 0.00 | 0.00 |
April | 0.157283E+11 | 0.00 | 262.66 | 0.152051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50753.40 | 13-APR-13:10 | 50753.40 | 13-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.331983E+11 | 0.00 | 598.61 | 0.219234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50435.65 | 18-MAY-13:00 | 45259.23 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.393457E+11 | 0.00 | 639.96 | 0.167810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52415.21 | 30-JUN-12:40 | 38941.66 | 30-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.517897E+11 | 0.00 | 722.43 | 0.213692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55819.27 | 23-JUL-13:00 | 44257.83 | 23-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.479099E+11 | 0.00 | 712.54 | 0.210360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59796.59 | 26-AUG-12:40 | 53912.57 | 25-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.324053E+11 | 0.00 | 540.05 | 0.190086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61110.63 | 01-SEP-12:50 | 55489.54 | 01-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.149796E+11 | 0.00 | 221.52 | 0.126009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71416.43 | 22-OCT-12:30 | 63763.01 | 21-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.487573E+09 | 0.00 | 12.53 | 0.487573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29209.02 | 17-NOV-13:30 | 29209.02 | 17-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238315E+12 | 0.00 | 3775.54 | 0.130882E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.517897E+11 | 0.00 | 722.43 | 0.219234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71416.43 | 63763.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9196004.25 | 0.00 | 0.33 | 9196004.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14777.07 | 18-JAN-19:05 | 14777.07 | 18-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 22679887.36 | 0.00 | 1.73 | 22679887.36 | 0.00 | 0.00 | 0.00 | 0.00 | 16900.22 | 05-FEB-09:01 | 16900.22 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.476852E+09 | 0.00 | 32.42 | 0.476615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86004.49 | 28-MAR-18:01 | 86004.49 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.653225E+10 | 0.00 | 223.12 | 0.581417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91128.74 | 18-APR-18:01 | 91128.74 | 18-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.306915E+11 | 0.00 | 457.92 | 0.223000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95685.54 | 21-MAY-21:01 | 95685.54 | 21-MAY-21:01 | 0.00 | 0.00 | 0.00 |
June | 0.448608E+11 | 0.00 | 450.08 | 0.285715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107884.26 | 25-JUN-08:51 | 93447.54 | 07-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.522768E+11 | 0.00 | 465.21 | 0.315976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108316.42 | 30-JUL-08:41 | 90740.10 | 01-JUL-21:01 | 0.00 | 0.00 | 0.00 |
August | 0.407763E+11 | 0.00 | 433.07 | 0.224871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103057.49 | 28-AUG-21:51 | 86844.48 | 01-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.217487E+11 | 0.00 | 435.95 | 0.107830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98110.31 | 18-SEP-21:52 | 94199.45 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.516329E+10 | 0.00 | 236.60 | 0.261352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88277.42 | 20-OCT-18:11 | 88277.42 | 20-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 0.542827E+09 | 0.00 | 34.14 | 0.255832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75535.46 | 01-NOV-18:03 | 75535.46 | 01-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 11468062.01 | 0.00 | 0.41 | 11468062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 15977.69 | 06-DEC-19:05 | 15977.69 | 06-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203113E+12 | 0.00 | 2770.99 | 0.124943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9196004.25 | 0.00 | 0.33 | 9196004.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14777.07 | 14777.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.522768E+11 | 0.00 | 465.21 | 0.315976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108316.42 | 95685.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 74784752.43 | 0.00 | 17.04 | 74784752.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17346.39 | 28-FEB-16:02 | 17346.39 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.462003E+09 | 0.00 | 85.39 | 0.459057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17817.26 | 26-MAR-15:01 | 17817.26 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.239061E+10 | 0.00 | 277.34 | 0.221633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.15 | 18-APR-18:01 | 17823.15 | 18-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.595289E+10 | 0.00 | 599.44 | 0.403445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.02 | 04-MAY-08:62 | 17823.02 | 04-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.875394E+10 | 0.00 | 662.96 | 0.505060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19218.63 | 10-JUN-15:02 | 17821.30 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.109401E+11 | 0.00 | 713.63 | 0.606354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18564.80 | 22-JUL-08:61 | 15889.09 | 20-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.837838E+10 | 0.00 | 674.32 | 0.423171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444.47 | 09-AUG-08:61 | 15811.22 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.400434E+10 | 0.00 | 467.23 | 0.211010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18592.30 | 19-SEP-15:02 | 17822.60 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.107146E+10 | 0.00 | 148.30 | 0.613732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17817.75 | 09-OCT-08:61 | 17817.75 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 87621025.13 | 0.00 | 13.59 | 83037832.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16865.97 | 16-NOV-09:01 | 16865.97 | 16-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 242542.30 | 0.00 | 0.02 | 242542.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2829.66 | 28-DEC-09:04 | 2829.66 | 28-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421164E+11 | 0.00 | 3659.28 | 0.249376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109401E+11 | 0.00 | 713.63 | 0.606354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19218.63 | 17823.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 2055066.38 | 0.00 | 1.39 | 1929909.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2751.01 | 28-FEB-09:03 | 2751.01 | 28-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 0.116163E+09 | 0.00 | 23.40 | 0.115158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16392.23 | 26-MAR-08:61 | 16392.23 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.123808E+10 | 0.00 | 188.14 | 0.112197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16925.77 | 23-APR-08:61 | 16925.77 | 23-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.421566E+10 | 0.00 | 482.38 | 0.275341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17929.60 | 26-MAY-08:51 | 17328.14 | 06-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.667115E+10 | 0.00 | 512.63 | 0.383888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22043.92 | 28-JUN-07:52 | 19507.82 | 28-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.803556E+10 | 0.00 | 524.18 | 0.440323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22283.10 | 23-JUL-08:32 | 19068.76 | 31-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.552503E+10 | 0.00 | 492.28 | 0.264065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20004.74 | 30-AUG-08:51 | 17352.28 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.219044E+10 | 0.00 | 347.64 | 0.106323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18740.48 | 01-SEP-08:51 | 17366.41 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.292503E+09 | 0.00 | 60.29 | 0.158616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16524.66 | 09-OCT-08:61 | 16524.66 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 5283711.72 | 0.00 | 2.67 | 3770838.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2624.89 | 21-NOV-09:05 | 2377.30 | 10-NOV-09:03 | 0.00 | 0.00 | 0.00 |
December | 8278.15 | 0.00 | 0.02 | 8278.15 | 0.00 | 0.00 | 0.00 | 0.00 | 96.58 | 05-DEC-19:06 | 96.58 | 05-DEC-19:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282919E+11 | 0.00 | 2635.03 | 0.161009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.803556E+10 | 0.00 | 524.18 | 0.440323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22283.10 | 19507.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 322846.70 | 0.00 | 0.20 | 322846.70 | 0.00 | 0.00 | 0.00 | 0.00 | 857.81 | 27-JAN-16:01 | 857.81 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 43464727.55 | 0.00 | 21.31 | 43464727.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5084.98 | 04-FEB-16:01 | 5084.98 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.172950E+09 | 0.00 | 64.20 | 0.172838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5089.60 | 28-MAR-18:01 | 5089.60 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.595091E+09 | 0.00 | 210.22 | 0.559504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5088.65 | 16-APR-15:01 | 5088.65 | 16-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.160519E+10 | 0.00 | 532.16 | 0.115520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5089.70 | 04-MAY-15:01 | 5089.70 | 04-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.206769E+10 | 0.00 | 602.36 | 0.120505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5516.11 | 10-JUN-15:02 | 5090.21 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.272013E+10 | 0.00 | 687.86 | 0.152422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.06 | 05-JUL-08:61 | 4525.91 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.212776E+10 | 0.00 | 640.30 | 0.113062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.18 | 30-AUG-08:61 | 4467.05 | 22-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.962754E+09 | 0.00 | 403.95 | 0.545342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5370.78 | 19-SEP-15:02 | 5090.47 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.283466E+09 | 0.00 | 120.93 | 0.177234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5089.45 | 21-OCT-18:01 | 5089.45 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 7928884.58 | 0.00 | 6.42 | 7408198.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5083.99 | 17-NOV-16:01 | 5083.99 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105867E+11 | 0.00 | 3289.91 | 0.652120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.272013E+10 | 0.00 | 687.86 | 0.152422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.18 | 5090.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 40935.41 | 0.00 | 0.05 | 40935.41 | 0.00 | 0.00 | 0.00 | 0.00 | 371.85 | 20-JAN-16:05 | 371.85 | 20-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 4502679.62 | 0.00 | 4.99 | 4471694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3177.12 | 08-FEB-16:01 | 3177.12 | 08-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 64068046.69 | 0.00 | 32.65 | 64068046.69 | 0.00 | 0.00 | 0.00 | 0.00 | 4830.74 | 28-MAR-18:01 | 4830.74 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.301024E+09 | 0.00 | 132.06 | 0.277248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5581.92 | 11-APR-18:11 | 5581.92 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.110616E+10 | 0.00 | 426.62 | 0.750887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6100.85 | 06-MAY-18:42 | 6100.85 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.155927E+10 | 0.00 | 461.01 | 0.874058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5885.73 | 25-JUN-08:51 | 4872.97 | 08-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.204997E+10 | 0.00 | 513.27 | 0.112005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5943.03 | 30-JUL-08:41 | 5322.09 | 01-JUL-20:42 | 0.00 | 0.00 | 0.00 |
August | 0.140084E+10 | 0.00 | 466.90 | 0.673818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5468.34 | 27-AUG-21:51 | 5324.96 | 02-AUG-20:02 | 0.00 | 0.00 | 0.00 |
September | 0.447909E+09 | 0.00 | 273.11 | 0.200867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5588.63 | 23-SEP-17:41 | 5588.63 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 72247309.23 | 0.00 | 50.33 | 36560439.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4691.02 | 21-OCT-18:32 | 4691.02 | 21-OCT-18:32 | 0.00 | 0.00 | 0.00 |
November | 725455.74 | 0.00 | 0.44 | 391882.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.64 | 17-NOV-16:01 | 1194.64 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.700676E+10 | 0.00 | 2361.45 | 0.400246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.204997E+10 | 0.00 | 513.27 | 0.112005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6100.85 | 6100.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.616129E+09 | 0.00 | 48.87 | 0.616129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24930.66 | 27-JAN-16:01 | 24930.66 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.168042E+10 | 0.00 | 128.23 | 0.167389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24965.47 | 04-FEB-16:01 | 24965.47 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.229258E+10 | 0.00 | 167.07 | 0.228495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24979.28 | 26-MAR-18:01 | 24979.28 | 26-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.424776E+10 | 0.00 | 311.62 | 0.396864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24976.01 | 30-APR-15:01 | 24976.01 | 30-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.791925E+10 | 0.00 | 577.82 | 0.531381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24972.02 | 06-MAY-15:01 | 24972.02 | 06-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.990540E+10 | 0.00 | 629.36 | 0.521282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27730.17 | 19-JUN-18:01 | 24969.52 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.131436E+11 | 0.00 | 687.83 | 0.684213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28230.67 | 25-JUL-18:02 | 22253.73 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.119607E+11 | 0.00 | 658.44 | 0.626644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27618.41 | 30-AUG-08:61 | 22354.99 | 31-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.736721E+10 | 0.00 | 515.35 | 0.443463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26297.22 | 19-SEP-15:02 | 24974.99 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.372890E+10 | 0.00 | 247.66 | 0.265214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24972.31 | 21-OCT-18:01 | 24972.31 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.110749E+10 | 0.00 | 83.08 | 0.108758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24965.79 | 16-NOV-16:01 | 24965.79 | 16-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.330551E+09 | 0.00 | 32.61 | 0.330127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24928.02 | 02-DEC-16:01 | 24928.02 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642999E+11 | 0.00 | 4087.96 | 0.406833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.330551E+09 | 0.00 | 32.61 | 0.330127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24928.02 | 22253.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131436E+11 | 0.00 | 687.83 | 0.684213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28230.67 | 24979.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 955.44 | 665.88 | 289.56 | 802.89 | 920.21 | 0.00 | 0.00 | 0.00 |
February | 1192.84 | 802.58 | 390.26 | 1117.80 | 788.12 | 0.00 | 0.00 | 0.00 |
March | 1048.51 | 659.96 | 388.55 | 1006.97 | 652.04 | 0.00 | 0.00 | 0.00 |
April | 957.67 | 519.22 | 438.45 | 1004.69 | 424.57 | 0.00 | 0.00 | 0.00 |
May | 819.75 | 289.21 | 530.53 | 954.37 | 220.16 | 0.00 | 0.00 | 0.00 |
June | 720.29 | 189.77 | 530.53 | 899.65 | 139.65 | 0.00 | 0.00 | 0.00 |
July | 792.53 | 252.19 | 540.34 | 1026.60 | 127.51 | 0.00 | 0.00 | 0.00 |
August | 840.95 | 349.61 | 491.34 | 1053.98 | 149.91 | 0.00 | 0.00 | 0.00 |
September | 886.96 | 464.05 | 422.92 | 1023.64 | 253.96 | 0.00 | 0.00 | 0.00 |
October | 788.67 | 470.16 | 318.50 | 803.23 | 405.68 | 0.00 | 0.00 | 0.00 |
November | 688.88 | 431.96 | 256.92 | 611.78 | 606.06 | 0.00 | 0.00 | 0.00 |
December | 733.86 | 481.50 | 252.36 | 568.45 | 899.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.80 | 462.59 | 404.21 | 904.66 | 464.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.88 | 189.77 | 252.36 | 568.45 | 127.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1192.84 | 802.58 | 540.34 | 1117.80 | 920.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2690.46 | 1875.07 | 815.40 | 2244.55 | 2610.44 | 0.00 | 0.00 | 0.00 |
February | 3358.95 | 2260.01 | 1098.94 | 3124.19 | 2241.50 | 0.00 | 0.00 | 0.00 |
March | 2952.53 | 1858.39 | 1094.13 | 2812.41 | 1870.31 | 0.00 | 0.00 | 0.00 |
April | 2696.73 | 1462.08 | 1234.65 | 2802.01 | 1243.08 | 0.00 | 0.00 | 0.00 |
May | 2308.35 | 814.40 | 1493.95 | 2651.35 | 668.05 | 0.00 | 0.00 | 0.00 |
June | 2028.29 | 534.37 | 1493.93 | 2492.11 | 436.70 | 0.00 | 0.00 | 0.00 |
July | 2231.71 | 710.16 | 1521.56 | 2856.44 | 395.17 | 0.00 | 0.00 | 0.00 |
August | 2368.05 | 984.47 | 1383.58 | 2935.01 | 470.62 | 0.00 | 0.00 | 0.00 |
September | 2497.62 | 1306.72 | 1190.90 | 2851.96 | 774.90 | 0.00 | 0.00 | 0.00 |
October | 2220.83 | 1323.95 | 896.88 | 2239.75 | 1191.28 | 0.00 | 0.00 | 0.00 |
November | 1939.83 | 1216.37 | 723.46 | 1705.36 | 1735.76 | 0.00 | 0.00 | 0.00 |
December | 2066.49 | 1355.87 | 710.62 | 1586.60 | 2548.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2440.87 | 1302.62 | 1138.24 | 2520.90 | 1344.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1939.83 | 534.37 | 710.62 | 1586.60 | 395.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3358.95 | 2260.01 | 1521.56 | 3124.19 | 2610.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3495.06 | 2435.82 | 1059.24 | 2951.06 | 3517.90 | 0.00 | 0.00 | 0.00 |
February | 4363.46 | 2935.88 | 1427.58 | 4123.37 | 3017.28 | 0.00 | 0.00 | 0.00 |
March | 3835.50 | 2414.16 | 1421.34 | 3715.17 | 2525.60 | 0.00 | 0.00 | 0.00 |
April | 3503.21 | 1899.33 | 1603.88 | 3698.39 | 1694.58 | 0.00 | 0.00 | 0.00 |
May | 2998.68 | 1057.96 | 1940.72 | 3494.25 | 915.03 | 0.00 | 0.00 | 0.00 |
June | 2634.87 | 694.17 | 1940.70 | 3282.30 | 602.37 | 0.00 | 0.00 | 0.00 |
July | 2899.12 | 922.53 | 1976.59 | 3767.99 | 536.29 | 0.00 | 0.00 | 0.00 |
August | 3076.23 | 1278.88 | 1797.35 | 3866.68 | 640.04 | 0.00 | 0.00 | 0.00 |
September | 3244.55 | 1697.51 | 1547.05 | 3749.73 | 1065.77 | 0.00 | 0.00 | 0.00 |
October | 2884.99 | 1719.89 | 1165.10 | 2938.17 | 1641.24 | 0.00 | 0.00 | 0.00 |
November | 2519.95 | 1580.13 | 939.82 | 2240.48 | 2377.06 | 0.00 | 0.00 | 0.00 |
December | 2684.49 | 1761.35 | 923.13 | 2078.94 | 3453.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3170.82 | 1692.18 | 1478.64 | 3319.89 | 1826.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2519.95 | 694.17 | 923.13 | 2078.94 | 536.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4363.46 | 2935.88 | 1976.59 | 4123.37 | 3517.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.77 | 192.65 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 221.74 | 161.34 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 200.46 | 132.20 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 199.25 | 85.81 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 188.30 | 43.62 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 178.44 | 26.70 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 204.71 | 23.12 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 209.50 | 27.57 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 203.10 | 50.02 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 160.19 | 80.56 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 122.13 | 121.73 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 112.38 | 186.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 179.62 | 94.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 112.38 | 23.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 221.74 | 192.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 47.29 | 415.40 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 117.01 | 334.78 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 189.19 | 259.62 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 292.56 | 157.22 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 430.77 | 78.95 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 443.50 | 48.86 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 489.33 | 42.62 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 388.33 | 51.01 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 269.45 | 92.77 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 131.76 | 155.70 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 48.75 | 248.86 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 25.83 | 401.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 240.22 | 190.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 25.83 | 42.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 489.33 | 415.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.21 | 239.95 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 3.20 | 190.73 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 9.26 | 145.77 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 32.95 | 85.46 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 86.09 | 40.63 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 118.35 | 26.35 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 118.09 | 23.67 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 81.21 | 28.82 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.67 | 51.33 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 17.26 | 85.32 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.67 | 139.19 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 229.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 43.33 | 106.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 118.35 | 239.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 48.90 | 413.03 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 121.23 | 331.55 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 193.87 | 256.65 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 296.47 | 156.15 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 429.08 | 80.90 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 438.46 | 51.98 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 484.04 | 46.31 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 385.65 | 54.93 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 270.31 | 93.52 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 134.78 | 154.28 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 51.32 | 246.65 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 26.82 | 400.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 240.79 | 189.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 26.82 | 46.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 484.04 | 413.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.10 | 105.30 | 45.79 | 130.28 | 139.17 | 0.00 | 0.00 | 0.00 |
February | 188.64 | 126.92 | 61.72 | 177.73 | 124.39 | 0.00 | 0.00 | 0.00 |
March | 165.81 | 104.37 | 61.45 | 156.75 | 112.28 | 0.00 | 0.00 | 0.00 |
April | 151.45 | 82.11 | 69.34 | 149.95 | 86.97 | 0.00 | 0.00 | 0.00 |
May | 129.64 | 45.74 | 83.90 | 139.19 | 50.11 | 0.00 | 0.00 | 0.00 |
June | 113.91 | 30.01 | 83.90 | 129.82 | 34.81 | 0.00 | 0.00 | 0.00 |
July | 125.33 | 39.88 | 85.45 | 151.50 | 31.28 | 0.00 | 0.00 | 0.00 |
August | 132.99 | 55.29 | 77.70 | 156.32 | 37.44 | 0.00 | 0.00 | 0.00 |
September | 140.27 | 73.39 | 66.88 | 151.69 | 58.43 | 0.00 | 0.00 | 0.00 |
October | 124.72 | 74.35 | 50.37 | 119.35 | 83.30 | 0.00 | 0.00 | 0.00 |
November | 108.94 | 68.31 | 40.63 | 94.73 | 102.69 | 0.00 | 0.00 | 0.00 |
December | 116.05 | 76.15 | 39.91 | 93.47 | 131.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.08 | 73.16 | 63.92 | 137.30 | 82.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.94 | 30.01 | 39.91 | 93.47 | 31.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.64 | 126.92 | 85.45 | 177.73 | 139.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.79 | 0.00 | 21.79 | 0.11 | 197.28 | 0.00 | 0.00 | 0.00 |
February | 33.47 | 0.00 | 33.47 | 2.23 | 156.74 | 0.00 | 0.00 | 0.00 |
March | 41.19 | 0.00 | 41.19 | 7.09 | 118.97 | 0.00 | 0.00 | 0.00 |
April | 54.17 | 0.56 | 53.61 | 27.44 | 68.76 | 0.00 | 0.00 | 0.00 |
May | 75.97 | 4.03 | 71.94 | 72.96 | 31.47 | 0.00 | 0.00 | 0.00 |
June | 84.90 | 9.45 | 75.45 | 99.12 | 19.95 | 0.00 | 0.00 | 0.00 |
July | 81.17 | 7.12 | 74.04 | 99.58 | 17.30 | 0.00 | 0.00 | 0.00 |
August | 61.63 | 1.17 | 60.46 | 68.97 | 21.47 | 0.00 | 0.00 | 0.00 |
September | 47.99 | 0.05 | 47.94 | 40.07 | 40.11 | 0.00 | 0.00 | 0.00 |
October | 33.27 | 0.00 | 33.27 | 13.40 | 70.07 | 0.00 | 0.00 | 0.00 |
November | 22.03 | 0.00 | 22.03 | 1.80 | 115.99 | 0.00 | 0.00 | 0.00 |
December | 18.46 | 0.00 | 18.46 | 0.00 | 189.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.08 | 1.87 | 46.20 | 36.28 | 87.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.46 | 0.00 | 18.46 | 0.00 | 17.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.90 | 9.45 | 75.45 | 99.58 | 197.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 40.03 | 409.78 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 98.96 | 323.88 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 177.56 | 251.22 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 313.74 | 150.90 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 398.96 | 73.78 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 492.67 | 46.64 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 495.79 | 40.23 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 366.77 | 49.12 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 259.21 | 89.72 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 113.82 | 151.73 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 43.29 | 244.48 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 25.08 | 397.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 236.15 | 185.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 25.08 | 40.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 495.79 | 409.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.61 | 192.41 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 221.35 | 160.99 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 199.32 | 131.73 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 197.73 | 85.42 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 187.77 | 43.10 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 177.21 | 26.34 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 204.02 | 22.57 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 209.17 | 27.15 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 202.61 | 49.54 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 159.95 | 80.19 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 122.01 | 121.54 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 112.20 | 186.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 179.03 | 93.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 112.20 | 22.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 221.35 | 192.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.21 | 239.83 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 3.04 | 190.58 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 8.60 | 145.62 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 31.62 | 85.36 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 86.29 | 39.85 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 117.43 | 25.63 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 117.40 | 22.77 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 81.25 | 27.77 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.31 | 50.28 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 16.89 | 84.72 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.60 | 139.16 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 229.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 42.97 | 106.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 22.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 117.43 | 239.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 40.97 | 406.65 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 101.87 | 319.16 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 181.42 | 247.09 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 317.33 | 149.44 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 398.82 | 75.11 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 488.75 | 49.35 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 490.82 | 43.46 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 365.26 | 52.09 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 261.07 | 89.81 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 116.70 | 149.84 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 44.62 | 241.16 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 25.61 | 395.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 236.75 | 184.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 25.61 | 43.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 490.82 | 406.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.10 | 318.15 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 2.93 | 254.62 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 10.15 | 193.39 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 41.88 | 112.39 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 113.06 | 53.99 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 153.92 | 35.36 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 152.89 | 32.56 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 105.74 | 39.38 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 61.26 | 69.01 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 20.42 | 113.97 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 2.68 | 188.37 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 306.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 55.75 | 142.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 32.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 153.92 | 318.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.72 | 0.00 | 12.72 | 0.04 | 117.28 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 1.08 | 93.86 | 0.00 | 0.00 | 0.00 |
March | 24.04 | 0.00 | 24.04 | 3.74 | 71.29 | 0.00 | 0.00 | 0.00 |
April | 31.61 | 0.32 | 31.28 | 15.44 | 41.43 | 0.00 | 0.00 | 0.00 |
May | 44.33 | 2.35 | 41.98 | 41.68 | 19.90 | 0.00 | 0.00 | 0.00 |
June | 49.54 | 5.51 | 44.03 | 56.74 | 13.03 | 0.00 | 0.00 | 0.00 |
July | 47.36 | 4.16 | 43.20 | 56.36 | 12.00 | 0.00 | 0.00 | 0.00 |
August | 35.96 | 0.68 | 35.28 | 38.98 | 14.52 | 0.00 | 0.00 | 0.00 |
September | 28.00 | 0.03 | 27.97 | 22.58 | 25.44 | 0.00 | 0.00 | 0.00 |
October | 19.41 | 0.00 | 19.41 | 7.53 | 42.01 | 0.00 | 0.00 | 0.00 |
November | 12.85 | 0.00 | 12.85 | 0.99 | 69.44 | 0.00 | 0.00 | 0.00 |
December | 10.77 | 0.00 | 10.77 | 0.00 | 112.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.05 | 1.09 | 26.96 | 20.55 | 52.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.77 | 0.00 | 10.77 | 0.00 | 12.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.54 | 5.51 | 44.03 | 56.74 | 117.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.14 | 61.43 | 26.71 | 73.26 | 92.52 | 0.00 | 0.00 | 0.00 |
February | 110.04 | 74.04 | 36.00 | 103.13 | 77.69 | 0.00 | 0.00 | 0.00 |
March | 96.73 | 60.88 | 35.85 | 93.69 | 63.55 | 0.00 | 0.00 | 0.00 |
April | 88.35 | 47.90 | 40.45 | 93.87 | 41.22 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 26.68 | 48.94 | 88.91 | 21.87 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 17.51 | 48.94 | 83.55 | 14.22 | 0.00 | 0.00 | 0.00 |
July | 73.11 | 23.27 | 49.85 | 95.52 | 12.92 | 0.00 | 0.00 | 0.00 |
August | 77.58 | 32.25 | 45.33 | 98.22 | 15.02 | 0.00 | 0.00 | 0.00 |
September | 81.83 | 42.81 | 39.02 | 95.45 | 25.14 | 0.00 | 0.00 | 0.00 |
October | 72.76 | 43.37 | 29.38 | 75.01 | 39.16 | 0.00 | 0.00 | 0.00 |
November | 63.55 | 39.85 | 23.70 | 56.55 | 59.45 | 0.00 | 0.00 | 0.00 |
December | 67.70 | 44.42 | 23.28 | 51.56 | 90.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.97 | 42.68 | 37.29 | 83.92 | 45.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.55 | 17.51 | 23.28 | 51.56 | 12.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.04 | 74.04 | 49.85 | 103.13 | 92.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.24 | 166.73 | 72.51 | 198.84 | 251.13 | 0.00 | 0.00 | 0.00 |
February | 298.68 | 200.96 | 97.72 | 279.92 | 210.86 | 0.00 | 0.00 | 0.00 |
March | 262.54 | 165.25 | 97.29 | 254.30 | 172.49 | 0.00 | 0.00 | 0.00 |
April | 239.80 | 130.01 | 109.79 | 254.79 | 111.89 | 0.00 | 0.00 | 0.00 |
May | 205.26 | 72.42 | 132.84 | 241.32 | 59.36 | 0.00 | 0.00 | 0.00 |
June | 180.36 | 47.52 | 132.84 | 226.76 | 38.59 | 0.00 | 0.00 | 0.00 |
July | 198.45 | 63.15 | 135.30 | 259.27 | 35.07 | 0.00 | 0.00 | 0.00 |
August | 210.57 | 87.54 | 123.03 | 266.58 | 40.77 | 0.00 | 0.00 | 0.00 |
September | 222.09 | 116.20 | 105.90 | 259.06 | 68.23 | 0.00 | 0.00 | 0.00 |
October | 197.48 | 117.73 | 79.75 | 203.60 | 106.28 | 0.00 | 0.00 | 0.00 |
November | 172.49 | 108.16 | 64.33 | 153.48 | 161.37 | 0.00 | 0.00 | 0.00 |
December | 183.76 | 120.57 | 63.19 | 139.95 | 245.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.05 | 115.83 | 101.21 | 227.78 | 124.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.49 | 47.52 | 63.19 | 139.95 | 35.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.68 | 200.96 | 135.30 | 279.92 | 251.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.31 | 193.01 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 221.01 | 161.36 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 199.99 | 132.05 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 198.53 | 85.53 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 187.19 | 43.41 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 177.50 | 26.39 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 203.76 | 22.76 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 208.51 | 27.22 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 202.28 | 49.66 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 159.95 | 80.00 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 121.96 | 121.34 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 111.98 | 187.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 178.95 | 93.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 111.98 | 22.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 221.01 | 193.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 47.01 | 416.44 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 116.47 | 335.07 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 188.48 | 259.29 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 291.10 | 156.59 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 428.58 | 78.43 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 441.54 | 48.25 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 487.27 | 41.91 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 386.63 | 50.31 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 268.21 | 91.95 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 131.55 | 154.52 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 48.86 | 248.14 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 25.65 | 403.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 239.18 | 189.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 25.65 | 41.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 487.27 | 416.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.21 | 240.31 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 3.27 | 190.86 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 9.30 | 145.73 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 32.90 | 85.34 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 85.02 | 40.83 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 117.23 | 26.58 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 117.18 | 23.86 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 80.52 | 29.07 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.54 | 51.22 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 17.57 | 84.62 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.79 | 138.63 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 230.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 43.04 | 106.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 23.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 117.23 | 240.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 48.57 | 414.02 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 120.68 | 331.98 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 193.28 | 256.37 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 295.20 | 155.60 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 426.30 | 81.10 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 435.61 | 52.32 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 481.29 | 46.54 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 383.35 | 55.32 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 269.06 | 93.09 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 134.91 | 153.00 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 51.49 | 246.04 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 26.62 | 401.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 239.57 | 190.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 26.62 | 46.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 481.29 | 414.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.05 | 193.09 | 83.97 | 224.69 | 290.01 | 0.00 | 0.00 | 0.00 |
February | 345.89 | 232.72 | 113.16 | 315.93 | 243.03 | 0.00 | 0.00 | 0.00 |
March | 304.04 | 191.37 | 112.67 | 287.48 | 198.19 | 0.00 | 0.00 | 0.00 |
April | 277.70 | 150.56 | 127.14 | 287.98 | 126.90 | 0.00 | 0.00 | 0.00 |
May | 237.70 | 83.86 | 153.84 | 275.57 | 62.70 | 0.00 | 0.00 | 0.00 |
June | 208.87 | 55.03 | 153.84 | 262.46 | 37.78 | 0.00 | 0.00 | 0.00 |
July | 229.81 | 73.13 | 156.68 | 301.41 | 32.05 | 0.00 | 0.00 | 0.00 |
August | 243.85 | 101.38 | 142.48 | 306.80 | 39.11 | 0.00 | 0.00 | 0.00 |
September | 257.19 | 134.56 | 122.63 | 295.07 | 73.33 | 0.00 | 0.00 | 0.00 |
October | 228.69 | 136.33 | 92.36 | 230.82 | 120.60 | 0.00 | 0.00 | 0.00 |
November | 199.75 | 125.26 | 74.50 | 173.69 | 183.55 | 0.00 | 0.00 | 0.00 |
December | 212.80 | 139.62 | 73.18 | 158.63 | 281.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.35 | 134.14 | 117.21 | 259.64 | 140.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.75 | 55.03 | 73.18 | 158.63 | 32.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 345.89 | 232.72 | 156.68 | 315.93 | 290.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.33 | 1792.49 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 11.92 | 1471.17 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 43.90 | 1148.26 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 198.94 | 687.49 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 583.42 | 321.56 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 814.94 | 209.01 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 824.24 | 183.89 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 558.66 | 230.94 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 308.37 | 418.11 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 90.10 | 706.80 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 10.03 | 1139.60 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 1746.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 288.83 | 835.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 183.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 824.24 | 1792.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.24 | 1821.57 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 10.03 | 1500.25 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 39.69 | 1173.39 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 189.51 | 702.82 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 573.46 | 328.08 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 805.84 | 213.97 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 816.57 | 188.27 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 550.73 | 237.16 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 299.76 | 427.95 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 83.36 | 724.54 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 8.82 | 1168.62 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 1776.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 283.24 | 852.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 188.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 816.57 | 1821.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.50 | 222.45 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 4.53 | 181.50 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 12.93 | 139.86 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 45.07 | 84.35 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 113.66 | 41.50 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 149.25 | 27.73 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 151.46 | 23.95 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 110.00 | 27.96 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 66.75 | 48.76 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 25.81 | 81.15 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 4.67 | 134.62 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.06 | 215.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 57.39 | 102.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.06 | 23.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 151.46 | 222.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.34 | 92.18 | 130.15 | 96.51 | 760.61 | 0.00 | 0.00 | 0.00 |
February | 353.32 | 151.95 | 201.37 | 221.66 | 614.12 | 0.00 | 0.00 | 0.00 |
March | 480.26 | 241.44 | 238.82 | 390.14 | 481.48 | 0.00 | 0.00 | 0.00 |
April | 661.43 | 356.59 | 304.84 | 694.44 | 300.73 | 0.00 | 0.00 | 0.00 |
May | 718.37 | 316.83 | 401.53 | 898.87 | 155.21 | 0.00 | 0.00 | 0.00 |
June | 810.58 | 387.70 | 422.89 | 1093.42 | 104.15 | 0.00 | 0.00 | 0.00 |
July | 795.75 | 374.36 | 421.39 | 1108.00 | 89.71 | 0.00 | 0.00 | 0.00 |
August | 612.52 | 267.68 | 344.83 | 837.70 | 104.57 | 0.00 | 0.00 | 0.00 |
September | 491.82 | 220.68 | 271.14 | 600.70 | 178.20 | 0.00 | 0.00 | 0.00 |
October | 296.11 | 111.34 | 184.77 | 274.27 | 291.42 | 0.00 | 0.00 | 0.00 |
November | 189.68 | 63.17 | 126.51 | 104.01 | 470.46 | 0.00 | 0.00 | 0.00 |
December | 174.39 | 65.46 | 108.93 | 60.77 | 745.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.36 | 220.95 | 263.40 | 533.26 | 356.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.39 | 63.17 | 108.93 | 60.77 | 89.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.58 | 387.70 | 422.89 | 1108.00 | 760.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 166.92 | 180.06 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 231.20 | 154.69 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 211.59 | 127.70 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 215.52 | 84.09 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 214.43 | 44.24 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 206.03 | 29.24 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 234.92 | 24.96 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 236.60 | 28.46 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 224.42 | 48.60 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 173.95 | 77.70 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 129.27 | 118.76 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 118.45 | 176.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 196.69 | 90.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 118.45 | 24.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 236.60 | 180.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.08 | 318.72 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 2.54 | 257.30 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 9.02 | 196.27 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 39.48 | 113.82 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 109.23 | 54.94 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 149.87 | 36.24 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 149.33 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 102.43 | 40.47 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 58.79 | 69.90 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 18.72 | 116.12 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 2.39 | 191.81 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 308.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 53.81 | 144.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 33.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 149.87 | 318.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 0.00 | 30.86 | 0.07 | 285.11 | 0.00 | 0.00 | 0.00 |
February | 47.40 | 0.00 | 47.40 | 2.27 | 230.21 | 0.00 | 0.00 | 0.00 |
March | 58.34 | 0.00 | 58.33 | 8.07 | 175.61 | 0.00 | 0.00 | 0.00 |
April | 76.71 | 0.79 | 75.92 | 35.33 | 101.84 | 0.00 | 0.00 | 0.00 |
May | 107.58 | 5.71 | 101.88 | 97.73 | 49.15 | 0.00 | 0.00 | 0.00 |
June | 120.23 | 13.38 | 106.85 | 134.09 | 32.43 | 0.00 | 0.00 | 0.00 |
July | 114.95 | 10.09 | 104.86 | 133.61 | 29.78 | 0.00 | 0.00 | 0.00 |
August | 87.28 | 1.66 | 85.62 | 91.65 | 36.21 | 0.00 | 0.00 | 0.00 |
September | 67.96 | 0.07 | 67.89 | 52.60 | 62.54 | 0.00 | 0.00 | 0.00 |
October | 47.11 | 0.00 | 47.11 | 16.75 | 103.89 | 0.00 | 0.00 | 0.00 |
November | 31.19 | 0.00 | 31.19 | 2.14 | 171.61 | 0.00 | 0.00 | 0.00 |
December | 26.15 | 0.00 | 26.15 | 0.00 | 275.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.08 | 2.65 | 65.43 | 48.14 | 129.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.15 | 0.00 | 26.15 | 0.00 | 29.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 13.38 | 106.85 | 134.09 | 285.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 705.25 | 491.51 | 213.74 | 582.32 | 741.14 | 0.00 | 0.00 | 0.00 |
February | 880.48 | 592.41 | 288.06 | 816.48 | 625.87 | 0.00 | 0.00 | 0.00 |
March | 773.94 | 487.14 | 286.81 | 741.23 | 514.13 | 0.00 | 0.00 | 0.00 |
April | 706.89 | 383.25 | 323.64 | 741.24 | 333.63 | 0.00 | 0.00 | 0.00 |
May | 605.09 | 213.48 | 391.61 | 698.97 | 178.31 | 0.00 | 0.00 | 0.00 |
June | 531.68 | 140.07 | 391.60 | 655.69 | 116.93 | 0.00 | 0.00 | 0.00 |
July | 585.00 | 186.15 | 398.85 | 752.47 | 105.83 | 0.00 | 0.00 | 0.00 |
August | 620.74 | 258.06 | 362.68 | 773.97 | 123.88 | 0.00 | 0.00 | 0.00 |
September | 654.70 | 342.53 | 312.17 | 753.86 | 204.11 | 0.00 | 0.00 | 0.00 |
October | 582.15 | 347.05 | 235.10 | 591.94 | 318.86 | 0.00 | 0.00 | 0.00 |
November | 508.49 | 318.84 | 189.64 | 446.12 | 483.33 | 0.00 | 0.00 | 0.00 |
December | 541.69 | 355.41 | 186.27 | 408.95 | 729.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.82 | 341.46 | 298.37 | 662.50 | 371.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.49 | 140.07 | 186.27 | 408.95 | 105.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 880.48 | 592.41 | 398.85 | 816.48 | 741.14 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.215046E+10 | 0.246470E+10 |
February | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.270419E+10 | 0.190662E+10 |
March | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.269707E+10 | 0.174642E+10 |
April | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.260416E+10 | 0.110049E+10 |
May | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.255619E+10 | 0.589678E+09 |
June | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.233189E+10 | 0.361985E+09 |
July | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.274966E+10 | 0.341521E+09 |
August | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.282298E+10 | 0.401513E+09 |
September | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.265328E+10 | 0.658259E+09 |
October | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.215137E+10 | 0.108657E+10 |
November | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.158573E+10 | 0.157091E+10 |
December | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.152253E+10 | 0.240808E+10 |
Annual Sum or Average | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.285295E+11 | 0.146368E+11 |
Minimum of Months | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.152253E+10 | 0.341521E+09 |
Maximum of Months | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.282298E+10 | 0.246470E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.601180E+10 | 0.699181E+10 |
February | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.755804E+10 | 0.542264E+10 |
March | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.753275E+10 | 0.500943E+10 |
April | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.726281E+10 | 0.322207E+10 |
May | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.710139E+10 | 0.178930E+10 |
June | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.645955E+10 | 0.113192E+10 |
July | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.765070E+10 | 0.105843E+10 |
August | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.786113E+10 | 0.126052E+10 |
September | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.739229E+10 | 0.200853E+10 |
October | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.599895E+10 | 0.319073E+10 |
November | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.442030E+10 | 0.449910E+10 |
December | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.424955E+10 | 0.682603E+10 |
Annual Sum or Average | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.794992E+11 | 0.424105E+11 |
Minimum of Months | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.424955E+10 | 0.105843E+10 |
Maximum of Months | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.786113E+10 | 0.699181E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.790411E+10 | 0.942234E+10 |
February | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.997525E+10 | 0.729941E+10 |
March | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.995071E+10 | 0.676457E+10 |
April | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.958622E+10 | 0.439235E+10 |
May | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.935900E+10 | 0.245083E+10 |
June | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.850772E+10 | 0.156135E+10 |
July | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.100922E+11 | 0.143639E+10 |
August | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.103565E+11 | 0.171428E+10 |
September | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.971930E+10 | 0.276248E+10 |
October | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.786958E+10 | 0.439590E+10 |
November | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.580733E+10 | 0.616135E+10 |
December | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.556823E+10 | 0.924923E+10 |
Annual Sum or Average | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.104696E+12 | 0.576105E+11 |
Minimum of Months | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.556823E+10 | 0.143639E+10 |
Maximum of Months | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.103565E+11 | 0.942234E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.425256E+09 | 0.515985E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.536426E+09 | 0.390321E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.536899E+09 | 0.354097E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.516458E+09 | 0.222408E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.504333E+09 | 0.116831E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.462511E+09 | 69198334.41 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.548294E+09 | 61913412.76 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.561125E+09 | 73835719.46 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.526432E+09 | 0.129650E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.429064E+09 | 0.215785E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.316558E+09 | 0.315515E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.300988E+09 | 0.500429E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.566434E+10 | 0.296597E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.300988E+09 | 61913412.76 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.561125E+09 | 0.515985E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.126659E+09 | 0.111261E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.283066E+09 | 0.809898E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.506737E+09 | 0.695365E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.758303E+09 | 0.407525E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.115378E+10 | 0.211456E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.114956E+10 | 0.126651E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.131061E+10 | 0.114157E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.104009E+10 | 0.136628E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.698408E+09 | 0.240451E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.352908E+09 | 0.417019E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.126347E+09 | 0.645056E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 69195998.30 | 0.107611E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.757566E+10 | 0.599293E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 69195998.30 | 0.114157E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.131061E+10 | 0.111261E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 562037.64 | 0.642676E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7737314.45 | 0.461411E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 24809254.67 | 0.390426E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 85410370.88 | 0.221525E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.230592E+09 | 0.108835E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.306771E+09 | 68290374.89 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.316294E+09 | 63406374.90 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.217500E+09 | 77182028.75 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.123550E+09 | 0.133053E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 46236527.07 | 0.228516E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 6930389.30 | 0.360790E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 3217.72 | 0.615560E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.136640E+10 | 0.337167E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 3217.72 | 63406374.90 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.316294E+09 | 0.642676E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.130985E+09 | 0.110625E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.293272E+09 | 0.802089E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.519264E+09 | 0.687413E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.768454E+09 | 0.404754E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114924E+10 | 0.216678E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.113648E+10 | 0.134727E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.129645E+10 | 0.124036E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.103292E+10 | 0.147125E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.700650E+09 | 0.242416E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.360997E+09 | 0.413217E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.133026E+09 | 0.639313E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71839729.97 | 0.107185E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.759358E+10 | 0.598986E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71839729.97 | 0.124036E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.129645E+10 | 0.110625E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.348935E+09 | 0.372766E+09 |
February | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.429959E+09 | 0.300936E+09 |
March | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.419841E+09 | 0.300722E+09 |
April | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.388676E+09 | 0.225433E+09 |
May | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.372812E+09 | 0.134219E+09 |
June | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.336484E+09 | 90216167.78 |
July | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.405783E+09 | 83768218.53 |
August | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.418693E+09 | 0.100283E+09 |
September | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.393183E+09 | 0.151459E+09 |
October | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.319665E+09 | 0.223103E+09 |
November | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.245549E+09 | 0.266181E+09 |
December | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.250351E+09 | 0.352214E+09 |
Annual Sum or Average | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.432993E+10 | 0.260130E+10 |
Minimum of Months | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.245549E+09 | 83768218.53 |
Maximum of Months | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.429959E+09 | 0.372766E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58367319.83 | 0.00 | 58367319.83 | 281584.76 | 0.528396E+09 |
February | 80980322.72 | 0.00 | 80980322.72 | 5405524.96 | 0.379190E+09 |
March | 0.110332E+09 | 4218.19 | 0.110328E+09 | 18979668.52 | 0.318658E+09 |
April | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 71112824.04 | 0.178215E+09 |
May | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.195419E+09 | 84278419.17 |
June | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.256931E+09 | 51718100.12 |
July | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.266722E+09 | 46325033.24 |
August | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.184716E+09 | 57506893.73 |
September | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.103872E+09 | 0.103964E+09 |
October | 89098491.50 | 0.00 | 89098491.50 | 35897218.20 | 0.187668E+09 |
November | 57091439.30 | 0.00 | 57091439.30 | 4657330.19 | 0.300643E+09 |
December | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.507436E+09 |
Annual Sum or Average | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.114400E+10 | 0.274400E+10 |
Minimum of Months | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 46325033.24 |
Maximum of Months | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.266722E+09 | 0.528396E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 0.107214E+09 | 0.109756E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.239411E+09 | 0.783527E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.475586E+09 | 0.672857E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.813204E+09 | 0.391129E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.106858E+10 | 0.197617E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.127700E+10 | 0.120883E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.132792E+10 | 0.107750E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.982346E+09 | 0.131559E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.671878E+09 | 0.232549E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.304848E+09 | 0.406405E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.112208E+09 | 0.633698E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 67174663.55 | 0.106485E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.744737E+10 | 0.584039E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 67174663.55 | 0.107750E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.132792E+10 | 0.109756E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.424809E+09 | 0.515342E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.535489E+09 | 0.389459E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.533862E+09 | 0.352832E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.512509E+09 | 0.221404E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.502911E+09 | 0.115428E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.459319E+09 | 68270321.41 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.546448E+09 | 60461158.67 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.560244E+09 | 72726686.76 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.525165E+09 | 0.128403E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.428402E+09 | 0.214786E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.316253E+09 | 0.315039E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.300515E+09 | 0.500088E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.564593E+10 | 0.295424E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.300515E+09 | 60461158.67 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.560244E+09 | 0.515342E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 552765.62 | 0.642363E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7364585.15 | 0.461062E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 23028330.25 | 0.390033E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 81953307.99 | 0.221249E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.231127E+09 | 0.106737E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.304381E+09 | 66426782.53 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.314456E+09 | 60999546.88 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.217621E+09 | 74372001.24 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.122629E+09 | 0.130323E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 45229622.89 | 0.226905E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 6744325.73 | 0.360714E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 3229.35 | 0.615278E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.135509E+10 | 0.335646E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 3229.35 | 60999546.88 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.314456E+09 | 0.642363E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 0.109729E+09 | 0.108916E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.246440E+09 | 0.772120E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.485916E+09 | 0.661806E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.822512E+09 | 0.387348E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.106821E+10 | 0.201178E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.126683E+10 | 0.127919E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.131462E+10 | 0.116401E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.978299E+09 | 0.139508E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.676697E+09 | 0.232795E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.312571E+09 | 0.401323E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.115655E+09 | 0.625089E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 68590853.64 | 0.105894E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.746607E+10 | 0.581359E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 68590853.64 | 0.116401E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.131462E+10 | 0.108916E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 278175.21 | 0.852135E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 7082446.68 | 0.615978E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 27179536.52 | 0.517974E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 0.108546E+09 | 0.291308E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.302813E+09 | 0.144601E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.398953E+09 | 91645535.82 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.409489E+09 | 87206228.95 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.283215E+09 | 0.105478E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.158796E+09 | 0.178874E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 54699462.22 | 0.305259E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 6940416.47 | 0.488252E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.820148E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.175799E+10 | 0.449886E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 87206228.95 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.409489E+09 | 0.852135E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34057273.10 | 0.00 | 34057273.10 | 102546.90 | 0.314132E+09 |
February | 47251937.81 | 0.00 | 47251937.81 | 2610883.11 | 0.227075E+09 |
March | 64378875.70 | 2461.31 | 64376414.39 | 10019502.58 | 0.190947E+09 |
April | 81924229.66 | 841461.32 | 81082768.34 | 40014459.02 | 0.107388E+09 |
May | 0.118725E+09 | 6298531.16 | 0.112426E+09 | 0.111629E+09 | 53305739.32 |
June | 0.128402E+09 | 14285523.95 | 0.114116E+09 | 0.147071E+09 | 33784339.25 |
July | 0.126851E+09 | 11135203.99 | 0.115716E+09 | 0.150955E+09 | 32147826.92 |
August | 96322837.24 | 1832513.78 | 94490323.46 | 0.104405E+09 | 38883392.88 |
September | 72576611.07 | 74914.37 | 72501696.70 | 58538667.34 | 65940423.28 |
October | 51988881.22 | 0.00 | 51988881.22 | 20164486.70 | 0.112531E+09 |
November | 33312798.08 | 0.00 | 33312798.08 | 2558524.89 | 0.179990E+09 |
December | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 0.302341E+09 |
Annual Sum or Average | 0.884647E+09 | 34470609.88 | 0.850177E+09 | 0.648069E+09 | 0.165847E+10 |
Minimum of Months | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 32147826.92 |
Maximum of Months | 0.128402E+09 | 14285523.95 | 0.115716E+09 | 0.150955E+09 | 0.314132E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236084E+09 | 0.164534E+09 | 71549800.91 | 0.196220E+09 | 0.247818E+09 |
February | 0.266219E+09 | 0.179120E+09 | 87098230.94 | 0.249498E+09 | 0.187945E+09 |
March | 0.259080E+09 | 0.163071E+09 | 96009120.53 | 0.250950E+09 | 0.170219E+09 |
April | 0.229001E+09 | 0.124157E+09 | 0.104844E+09 | 0.243318E+09 | 0.106849E+09 |
May | 0.202555E+09 | 71462483.28 | 0.131092E+09 | 0.238136E+09 | 58575038.08 |
June | 0.172239E+09 | 45377083.81 | 0.126862E+09 | 0.216550E+09 | 36847898.95 |
July | 0.195830E+09 | 62315011.60 | 0.133515E+09 | 0.255851E+09 | 34608937.94 |
August | 0.207793E+09 | 86385450.33 | 0.121408E+09 | 0.263067E+09 | 40234443.74 |
September | 0.212093E+09 | 0.110964E+09 | 0.101129E+09 | 0.247398E+09 | 65154363.83 |
October | 0.194875E+09 | 0.116174E+09 | 78700257.98 | 0.200916E+09 | 0.104876E+09 |
November | 0.164726E+09 | 0.103291E+09 | 61435163.42 | 0.146566E+09 | 0.154107E+09 |
December | 0.181331E+09 | 0.118975E+09 | 62355771.56 | 0.138105E+09 | 0.242633E+09 |
Annual Sum or Average | 0.252183E+10 | 0.134583E+10 | 0.117600E+10 | 0.264658E+10 | 0.144987E+10 |
Minimum of Months | 0.164726E+09 | 45377083.81 | 61435163.42 | 0.138105E+09 | 34608937.94 |
Maximum of Months | 0.266219E+09 | 0.179120E+09 | 0.133515E+09 | 0.263067E+09 | 0.247818E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.640779E+09 | 0.446578E+09 | 0.194201E+09 | 0.532581E+09 | 0.672629E+09 |
February | 0.722572E+09 | 0.486170E+09 | 0.236402E+09 | 0.677190E+09 | 0.510121E+09 |
March | 0.703195E+09 | 0.442607E+09 | 0.260588E+09 | 0.681129E+09 | 0.462009E+09 |
April | 0.621556E+09 | 0.336987E+09 | 0.284569E+09 | 0.660415E+09 | 0.290011E+09 |
May | 0.549775E+09 | 0.193964E+09 | 0.355811E+09 | 0.646350E+09 | 0.158985E+09 |
June | 0.467492E+09 | 0.123163E+09 | 0.344329E+09 | 0.587760E+09 | 0.100013E+09 |
July | 0.531524E+09 | 0.169136E+09 | 0.362388E+09 | 0.694433E+09 | 93935736.67 |
August | 0.563993E+09 | 0.234468E+09 | 0.329525E+09 | 0.714017E+09 | 0.109205E+09 |
September | 0.575664E+09 | 0.301178E+09 | 0.274486E+09 | 0.671488E+09 | 0.176842E+09 |
October | 0.528929E+09 | 0.315321E+09 | 0.213609E+09 | 0.545328E+09 | 0.284655E+09 |
November | 0.447101E+09 | 0.280353E+09 | 0.166748E+09 | 0.397809E+09 | 0.418277E+09 |
December | 0.492170E+09 | 0.322923E+09 | 0.169246E+09 | 0.374846E+09 | 0.658555E+09 |
Annual Sum or Average | 0.684475E+10 | 0.365285E+10 | 0.319190E+10 | 0.718335E+10 | 0.393524E+10 |
Minimum of Months | 0.447101E+09 | 0.123163E+09 | 0.166748E+09 | 0.374846E+09 | 93935736.67 |
Maximum of Months | 0.722572E+09 | 0.486170E+09 | 0.362388E+09 | 0.714017E+09 | 0.672629E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.424019E+09 | 0.516946E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.534671E+09 | 0.390358E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.535654E+09 | 0.353696E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.514587E+09 | 0.221687E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.501381E+09 | 0.116260E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.460075E+09 | 68413535.74 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.545759E+09 | 60948393.31 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.558471E+09 | 72899611.54 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.524308E+09 | 0.128710E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.428421E+09 | 0.214272E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.316119E+09 | 0.314502E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.299915E+09 | 0.501547E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.564338E+10 | 0.296024E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.299915E+09 | 60948393.31 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.558471E+09 | 0.516946E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.125917E+09 | 0.111539E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.281775E+09 | 0.810613E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.504825E+09 | 0.694477E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.754521E+09 | 0.405874E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114790E+10 | 0.210061E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.114446E+10 | 0.125067E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.130511E+10 | 0.112247E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.103554E+10 | 0.134763E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.695200E+09 | 0.238335E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.352345E+09 | 0.413865E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.126634E+09 | 0.643184E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68708541.42 | 0.107966E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.754293E+10 | 0.598353E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68708541.42 | 0.112247E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.130511E+10 | 0.111539E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 555756.88 | 0.643650E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7909839.44 | 0.461727E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 24912023.09 | 0.390316E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 85284255.72 | 0.221206E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.227725E+09 | 0.109353E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.303869E+09 | 68891344.28 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.313850E+09 | 63916054.83 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.215675E+09 | 77849078.50 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.123229E+09 | 0.132772E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 47056864.89 | 0.226634E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 7235909.06 | 0.359335E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 4358.65 | 0.616897E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.135731E+10 | 0.337255E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 4358.65 | 63916054.83 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.313850E+09 | 0.643650E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.130096E+09 | 0.110890E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.291961E+09 | 0.803122E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.517686E+09 | 0.686667E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.765149E+09 | 0.403314E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114181E+10 | 0.217230E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.112909E+10 | 0.135601E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.128908E+10 | 0.124664E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.102677E+10 | 0.148162E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.697403E+09 | 0.241299E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.361339E+09 | 0.409787E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.133472E+09 | 0.637739E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71295663.10 | 0.107533E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.755516E+10 | 0.599181E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71295663.10 | 0.124664E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.128908E+10 | 0.110890E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.601821E+09 | 0.776762E+09 |
February | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.764294E+09 | 0.587948E+09 |
March | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.769986E+09 | 0.530844E+09 |
April | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.746441E+09 | 0.328936E+09 |
May | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.738074E+09 | 0.167936E+09 |
June | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.680284E+09 | 97915883.28 |
July | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.807292E+09 | 85836035.95 |
August | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.821744E+09 | 0.104745E+09 |
September | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.764820E+09 | 0.190079E+09 |
October | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.618218E+09 | 0.323026E+09 |
November | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.450215E+09 | 0.475771E+09 |
December | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.424888E+09 | 0.752951E+09 |
Annual Sum or Average | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.818808E+10 | 0.442275E+10 |
Minimum of Months | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.424888E+09 | 85836035.95 |
Maximum of Months | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.821744E+09 | 0.776762E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 887566.48 | 0.480100E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 28844368.29 | 0.355905E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.117585E+09 | 0.307550E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.515651E+09 | 0.178197E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.156263E+10 | 0.861270E+09 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.211232E+10 | 0.541761E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.220765E+10 | 0.492523E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.149630E+10 | 0.618542E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.799298E+09 | 0.108373E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.241316E+09 | 0.189310E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 26010594.67 | 0.295385E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.467720E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.910850E+10 | 0.263395E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.492523E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.220765E+10 | 0.480100E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 636671.25 | 0.487890E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 24269344.72 | 0.362940E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.106295E+09 | 0.314280E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.491209E+09 | 0.182170E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.153597E+10 | 0.878741E+09 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.208873E+10 | 0.554608E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.218709E+10 | 0.504258E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.147508E+10 | 0.635221E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.776978E+09 | 0.110926E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.223260E+09 | 0.194061E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 22857359.21 | 0.302905E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.475732E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.893237E+10 | 0.268819E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.504258E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.218709E+10 | 0.487890E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 1336573.78 | 0.595815E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 10961053.79 | 0.439083E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 34638679.07 | 0.374599E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 0.116811E+09 | 0.218640E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.304439E+09 | 0.111160E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.386868E+09 | 71883389.77 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.405674E+09 | 64136701.49 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.294614E+09 | 74894945.03 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.173023E+09 | 0.126398E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 69139996.97 | 0.217348E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 12101334.50 | 0.348936E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 168557.03 | 0.577328E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.180977E+10 | 0.322022E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 168557.03 | 64136701.49 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.405674E+09 | 0.595815E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595505E+09 | 0.246907E+09 | 0.348598E+09 | 0.258500E+09 | 0.203723E+10 |
February | 0.854744E+09 | 0.367601E+09 | 0.487143E+09 | 0.536241E+09 | 0.148567E+10 |
March | 0.128632E+10 | 0.646670E+09 | 0.639645E+09 | 0.104496E+10 | 0.128961E+10 |
April | 0.171443E+10 | 0.924292E+09 | 0.790139E+09 | 0.180000E+10 | 0.779487E+09 |
May | 0.192408E+10 | 0.848610E+09 | 0.107547E+10 | 0.240753E+10 | 0.415702E+09 |
June | 0.210103E+10 | 0.100491E+10 | 0.109612E+10 | 0.283415E+10 | 0.269967E+09 |
July | 0.213133E+10 | 0.100269E+10 | 0.112864E+10 | 0.296767E+10 | 0.240267E+09 |
August | 0.164056E+10 | 0.716963E+09 | 0.923598E+09 | 0.224369E+10 | 0.280092E+09 |
September | 0.127481E+10 | 0.572005E+09 | 0.702805E+09 | 0.155701E+10 | 0.461895E+09 |
October | 0.793108E+09 | 0.298216E+09 | 0.494892E+09 | 0.734603E+09 | 0.780526E+09 |
November | 0.491659E+09 | 0.163742E+09 | 0.327917E+09 | 0.269604E+09 | 0.121944E+10 |
December | 0.467099E+09 | 0.175331E+09 | 0.291768E+09 | 0.162771E+09 | 0.199712E+10 |
Annual Sum or Average | 0.152747E+11 | 0.696794E+10 | 0.830673E+10 | 0.168167E+11 | 0.112570E+11 |
Minimum of Months | 0.467099E+09 | 0.163742E+09 | 0.291768E+09 | 0.162771E+09 | 0.240267E+09 |
Maximum of Months | 0.213133E+10 | 0.100491E+10 | 0.112864E+10 | 0.296767E+10 | 0.203723E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.447074E+09 | 0.482278E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.559323E+09 | 0.374231E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.566717E+09 | 0.342042E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.558622E+09 | 0.217973E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.574328E+09 | 0.118502E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.534029E+09 | 75795328.58 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.629204E+09 | 66849947.88 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.633707E+09 | 76229627.66 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.581709E+09 | 0.125963E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.465908E+09 | 0.208102E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.335071E+09 | 0.307815E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.317249E+09 | 0.473187E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.620294E+10 | 0.286897E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.317249E+09 | 66849947.88 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.633707E+09 | 0.482278E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 217017.95 | 0.853655E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 6141273.18 | 0.622470E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 24168904.74 | 0.525702E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 0.102345E+09 | 0.295033E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.292559E+09 | 0.147142E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.388474E+09 | 93938032.97 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.399972E+09 | 89160652.14 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.274360E+09 | 0.108390E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.152371E+09 | 0.181185E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 50152117.08 | 0.311006E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 6196016.73 | 0.497178E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.825357E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.169696E+10 | 0.455021E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 89160652.14 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.399972E+09 | 0.853655E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82658026.82 | 0.00 | 82658026.82 | 194166.79 | 0.763643E+09 |
February | 0.114682E+09 | 0.00 | 0.114682E+09 | 5494620.38 | 0.556917E+09 |
March | 0.156249E+09 | 5973.67 | 0.156243E+09 | 21624010.65 | 0.470347E+09 |
April | 0.198833E+09 | 2042251.94 | 0.196790E+09 | 91568047.52 | 0.263967E+09 |
May | 0.288149E+09 | 15286724.70 | 0.272862E+09 | 0.261754E+09 | 0.131648E+09 |
June | 0.311635E+09 | 34671396.57 | 0.276964E+09 | 0.347569E+09 | 84046714.03 |
July | 0.307871E+09 | 27025475.21 | 0.280845E+09 | 0.357857E+09 | 79772373.30 |
August | 0.233778E+09 | 4447566.10 | 0.229331E+09 | 0.245471E+09 | 96976929.90 |
September | 0.176146E+09 | 181819.44 | 0.175964E+09 | 0.136327E+09 | 0.162106E+09 |
October | 0.126179E+09 | 0.00 | 0.126179E+09 | 44871289.17 | 0.278258E+09 |
November | 80851163.55 | 0.00 | 80851163.55 | 5543599.64 | 0.444802E+09 |
December | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 0.738366E+09 |
Annual Sum or Average | 0.214707E+10 | 83661207.63 | 0.206340E+10 | 0.151827E+10 | 0.407085E+10 |
Minimum of Months | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 79772373.30 |
Maximum of Months | 0.311635E+09 | 34671396.57 | 0.280845E+09 | 0.357857E+09 | 0.763643E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188894E+10 | 0.131646E+10 | 0.572480E+09 | 0.155967E+10 | 0.198507E+10 |
February | 0.213005E+10 | 0.143317E+10 | 0.696885E+09 | 0.197522E+10 | 0.151411E+10 |
March | 0.207293E+10 | 0.130475E+10 | 0.768182E+09 | 0.198532E+10 | 0.137704E+10 |
April | 0.183227E+10 | 0.993394E+09 | 0.838875E+09 | 0.192131E+10 | 0.864765E+09 |
May | 0.162067E+10 | 0.571781E+09 | 0.104889E+10 | 0.187212E+10 | 0.477595E+09 |
June | 0.137811E+10 | 0.363068E+09 | 0.101504E+10 | 0.169956E+10 | 0.303084E+09 |
July | 0.156686E+10 | 0.498591E+09 | 0.106827E+10 | 0.201543E+10 | 0.283453E+09 |
August | 0.166258E+10 | 0.691182E+09 | 0.971399E+09 | 0.207299E+10 | 0.331803E+09 |
September | 0.169698E+10 | 0.887836E+09 | 0.809149E+09 | 0.195401E+10 | 0.529052E+09 |
October | 0.155922E+10 | 0.929526E+09 | 0.629691E+09 | 0.158546E+10 | 0.854025E+09 |
November | 0.131800E+10 | 0.826446E+09 | 0.491551E+09 | 0.115635E+10 | 0.125280E+10 |
December | 0.145085E+10 | 0.951937E+09 | 0.498917E+09 | 0.109533E+10 | 0.195348E+10 |
Annual Sum or Average | 0.201775E+11 | 0.107681E+11 | 0.940933E+10 | 0.208927E+11 | 0.117263E+11 |
Minimum of Months | 0.131800E+10 | 0.363068E+09 | 0.491551E+09 | 0.109533E+10 | 0.283453E+09 |
Maximum of Months | 0.213005E+10 | 0.143317E+10 | 0.106827E+10 | 0.207299E+10 | 0.198507E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 802.89 | 920.21 | 955.44 | 665.88 | 289.56 | 0.00 | 0.00 |
February | 1117.80 | 788.12 | 1192.84 | 802.58 | 390.26 | 0.00 | 0.00 |
March | 1006.97 | 652.04 | 1048.51 | 659.96 | 388.55 | 0.00 | 0.00 |
April | 1004.69 | 424.57 | 957.67 | 519.22 | 438.45 | 0.00 | 0.00 |
May | 954.37 | 220.16 | 819.75 | 289.21 | 530.53 | 0.00 | 0.00 |
June | 899.65 | 139.65 | 720.29 | 189.77 | 530.53 | 0.00 | 0.00 |
July | 1026.60 | 127.51 | 792.53 | 252.19 | 540.34 | 0.00 | 0.00 |
August | 1053.98 | 149.91 | 840.95 | 349.61 | 491.34 | 0.00 | 0.00 |
September | 1023.64 | 253.96 | 886.96 | 464.05 | 422.92 | 0.00 | 0.00 |
October | 803.23 | 405.68 | 788.67 | 470.16 | 318.50 | 0.00 | 0.00 |
November | 611.78 | 606.06 | 688.88 | 431.96 | 256.92 | 0.00 | 0.00 |
December | 568.45 | 899.07 | 733.86 | 481.50 | 252.36 | 0.00 | 0.00 |
Annual Sum or Average | 904.66 | 464.13 | 866.80 | 462.59 | 404.21 | 0.00 | 0.00 |
Minimum of Months | 568.45 | 127.51 | 688.88 | 189.77 | 252.36 | 0.00 | 0.00 |
Maximum of Months | 1117.80 | 920.21 | 1192.84 | 802.58 | 540.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2244.55 | 2610.44 | 2690.46 | 1875.07 | 815.40 | 0.00 | 0.00 |
February | 3124.19 | 2241.50 | 3358.95 | 2260.01 | 1098.94 | 0.00 | 0.00 |
March | 2812.41 | 1870.31 | 2952.53 | 1858.39 | 1094.13 | 0.00 | 0.00 |
April | 2802.01 | 1243.08 | 2696.73 | 1462.08 | 1234.65 | 0.00 | 0.00 |
May | 2651.35 | 668.05 | 2308.35 | 814.40 | 1493.95 | 0.00 | 0.00 |
June | 2492.11 | 436.70 | 2028.29 | 534.37 | 1493.93 | 0.00 | 0.00 |
July | 2856.44 | 395.17 | 2231.71 | 710.16 | 1521.56 | 0.00 | 0.00 |
August | 2935.01 | 470.62 | 2368.05 | 984.47 | 1383.58 | 0.00 | 0.00 |
September | 2851.96 | 774.90 | 2497.62 | 1306.72 | 1190.90 | 0.00 | 0.00 |
October | 2239.75 | 1191.28 | 2220.83 | 1323.95 | 896.88 | 0.00 | 0.00 |
November | 1705.36 | 1735.76 | 1939.83 | 1216.37 | 723.46 | 0.00 | 0.00 |
December | 1586.60 | 2548.55 | 2066.49 | 1355.87 | 710.62 | 0.00 | 0.00 |
Annual Sum or Average | 2520.90 | 1344.83 | 2440.87 | 1302.62 | 1138.24 | 0.00 | 0.00 |
Minimum of Months | 1586.60 | 395.17 | 1939.83 | 534.37 | 710.62 | 0.00 | 0.00 |
Maximum of Months | 3124.19 | 2610.44 | 3358.95 | 2260.01 | 1521.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2951.06 | 3517.90 | 3495.06 | 2435.82 | 1059.24 | 0.00 | 0.00 |
February | 4123.37 | 3017.28 | 4363.46 | 2935.88 | 1427.58 | 0.00 | 0.00 |
March | 3715.17 | 2525.60 | 3835.50 | 2414.16 | 1421.34 | 0.00 | 0.00 |
April | 3698.39 | 1694.58 | 3503.21 | 1899.33 | 1603.88 | 0.00 | 0.00 |
May | 3494.25 | 915.03 | 2998.68 | 1057.96 | 1940.72 | 0.00 | 0.00 |
June | 3282.30 | 602.37 | 2634.87 | 694.17 | 1940.70 | 0.00 | 0.00 |
July | 3767.99 | 536.29 | 2899.12 | 922.53 | 1976.59 | 0.00 | 0.00 |
August | 3866.68 | 640.04 | 3076.23 | 1278.88 | 1797.35 | 0.00 | 0.00 |
September | 3749.73 | 1065.77 | 3244.55 | 1697.51 | 1547.05 | 0.00 | 0.00 |
October | 2938.17 | 1641.24 | 2884.99 | 1719.89 | 1165.10 | 0.00 | 0.00 |
November | 2240.48 | 2377.06 | 2519.95 | 1580.13 | 939.82 | 0.00 | 0.00 |
December | 2078.94 | 3453.27 | 2684.49 | 1761.35 | 923.13 | 0.00 | 0.00 |
Annual Sum or Average | 3319.89 | 1826.82 | 3170.82 | 1692.18 | 1478.64 | 0.00 | 0.00 |
Minimum of Months | 2078.94 | 536.29 | 2519.95 | 694.17 | 923.13 | 0.00 | 0.00 |
Maximum of Months | 4123.37 | 3517.90 | 4363.46 | 2935.88 | 1976.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.56 | 571.54 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 316.10 | 473.48 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 377.73 | 379.90 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 487.49 | 238.72 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 617.89 | 121.39 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 621.37 | 74.99 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 693.72 | 65.42 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 597.55 | 78.30 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 471.42 | 141.66 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 288.71 | 233.01 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 159.92 | 359.63 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 108.31 | 558.71 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 409.63 | 273.87 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 108.31 | 65.42 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 693.72 | 571.54 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.43 | 640.29 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 114.07 | 511.93 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 195.64 | 394.92 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 326.74 | 238.94 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 513.70 | 120.06 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 555.07 | 76.59 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 600.76 | 68.62 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 466.41 | 83.31 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 316.81 | 143.69 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 150.19 | 237.74 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 49.09 | 380.94 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 17.73 | 620.91 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 279.54 | 292.27 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 17.73 | 68.62 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 600.76 | 640.29 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.28 | 139.17 | 151.10 | 105.30 | 45.79 | 0.00 | 0.00 |
February | 177.73 | 124.39 | 188.64 | 126.92 | 61.72 | 0.00 | 0.00 |
March | 156.75 | 112.28 | 165.81 | 104.37 | 61.45 | 0.00 | 0.00 |
April | 149.95 | 86.97 | 151.45 | 82.11 | 69.34 | 0.00 | 0.00 |
May | 139.19 | 50.11 | 129.64 | 45.74 | 83.90 | 0.00 | 0.00 |
June | 129.82 | 34.81 | 113.91 | 30.01 | 83.90 | 0.00 | 0.00 |
July | 151.50 | 31.28 | 125.33 | 39.88 | 85.45 | 0.00 | 0.00 |
August | 156.32 | 37.44 | 132.99 | 55.29 | 77.70 | 0.00 | 0.00 |
September | 151.69 | 58.43 | 140.27 | 73.39 | 66.88 | 0.00 | 0.00 |
October | 119.35 | 83.30 | 124.72 | 74.35 | 50.37 | 0.00 | 0.00 |
November | 94.73 | 102.69 | 108.94 | 68.31 | 40.63 | 0.00 | 0.00 |
December | 93.47 | 131.50 | 116.05 | 76.15 | 39.91 | 0.00 | 0.00 |
Annual Sum or Average | 137.30 | 82.49 | 137.08 | 73.16 | 63.92 | 0.00 | 0.00 |
Minimum of Months | 93.47 | 31.28 | 108.94 | 30.01 | 39.91 | 0.00 | 0.00 |
Maximum of Months | 177.73 | 139.17 | 188.64 | 126.92 | 85.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.11 | 197.28 | 21.79 | 0.00 | 21.79 | 0.00 | 0.00 |
February | 2.23 | 156.74 | 33.47 | 0.00 | 33.47 | 0.00 | 0.00 |
March | 7.09 | 118.97 | 41.19 | 0.00 | 41.19 | 0.00 | 0.00 |
April | 27.44 | 68.76 | 54.17 | 0.56 | 53.61 | 0.00 | 0.00 |
May | 72.96 | 31.47 | 75.97 | 4.03 | 71.94 | 0.00 | 0.00 |
June | 99.12 | 19.95 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
July | 99.58 | 17.30 | 81.17 | 7.12 | 74.04 | 0.00 | 0.00 |
August | 68.97 | 21.47 | 61.63 | 1.17 | 60.46 | 0.00 | 0.00 |
September | 40.07 | 40.11 | 47.99 | 0.05 | 47.94 | 0.00 | 0.00 |
October | 13.40 | 70.07 | 33.27 | 0.00 | 33.27 | 0.00 | 0.00 |
November | 1.80 | 115.99 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
December | 0.00 | 189.45 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Annual Sum or Average | 36.28 | 87.01 | 48.08 | 1.87 | 46.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 17.30 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Maximum of Months | 99.58 | 197.28 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.45 | 568.00 | 300.08 | 177.75 | 122.33 | 0.00 | 0.00 |
February | 301.32 | 465.87 | 412.52 | 234.66 | 177.85 | 0.00 | 0.00 |
March | 365.57 | 371.63 | 447.45 | 251.21 | 196.24 | 0.00 | 0.00 |
April | 506.04 | 230.90 | 520.09 | 280.97 | 239.12 | 0.00 | 0.00 |
May | 583.52 | 113.67 | 521.29 | 215.61 | 305.68 | 0.00 | 0.00 |
June | 668.57 | 71.67 | 547.74 | 231.38 | 316.35 | 0.00 | 0.00 |
July | 698.85 | 61.84 | 554.60 | 237.06 | 317.54 | 0.00 | 0.00 |
August | 575.09 | 75.42 | 472.55 | 202.97 | 269.58 | 0.00 | 0.00 |
September | 460.26 | 137.69 | 421.30 | 202.10 | 219.20 | 0.00 | 0.00 |
October | 271.92 | 230.08 | 304.00 | 148.63 | 155.37 | 0.00 | 0.00 |
November | 155.10 | 355.82 | 231.05 | 116.99 | 114.06 | 0.00 | 0.00 |
December | 109.92 | 556.92 | 232.30 | 127.93 | 104.37 | 0.00 | 0.00 |
Annual Sum or Average | 405.44 | 269.13 | 413.58 | 201.95 | 211.63 | 0.00 | 0.00 |
Minimum of Months | 109.92 | 61.84 | 231.05 | 116.99 | 104.37 | 0.00 | 0.00 |
Maximum of Months | 698.85 | 568.00 | 554.60 | 280.97 | 317.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.61 | 631.91 | 138.41 | 46.10 | 92.32 | 0.00 | 0.00 |
February | 90.55 | 495.39 | 218.51 | 75.98 | 142.53 | 0.00 | 0.00 |
March | 178.37 | 381.06 | 291.63 | 120.73 | 170.90 | 0.00 | 0.00 |
April | 343.22 | 229.07 | 398.44 | 179.01 | 219.43 | 0.00 | 0.00 |
May | 483.55 | 113.39 | 454.16 | 163.47 | 290.69 | 0.00 | 0.00 |
June | 605.02 | 73.82 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
July | 607.49 | 65.50 | 499.35 | 196.10 | 303.25 | 0.00 | 0.00 |
August | 446.00 | 79.35 | 383.31 | 135.32 | 247.99 | 0.00 | 0.00 |
September | 306.38 | 138.09 | 305.91 | 110.41 | 195.50 | 0.00 | 0.00 |
October | 130.66 | 231.62 | 189.64 | 55.67 | 133.97 | 0.00 | 0.00 |
November | 41.76 | 374.86 | 122.38 | 31.59 | 90.79 | 0.00 | 0.00 |
December | 15.40 | 614.87 | 110.28 | 32.73 | 77.55 | 0.00 | 0.00 |
Annual Sum or Average | 273.86 | 284.92 | 302.28 | 112.83 | 189.46 | 0.00 | 0.00 |
Minimum of Months | 15.40 | 65.50 | 110.28 | 31.59 | 77.55 | 0.00 | 0.00 |
Maximum of Months | 607.49 | 631.91 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.90 | 713.74 | 374.59 | 228.16 | 146.43 | 0.00 | 0.00 |
February | 346.68 | 596.65 | 481.24 | 275.00 | 206.24 | 0.00 | 0.00 |
March | 343.89 | 482.73 | 448.51 | 226.14 | 222.37 | 0.00 | 0.00 |
April | 403.81 | 304.76 | 445.49 | 179.12 | 266.38 | 0.00 | 0.00 |
May | 481.92 | 152.08 | 445.46 | 107.83 | 337.63 | 0.00 | 0.00 |
June | 517.64 | 97.87 | 430.73 | 85.48 | 345.24 | 0.00 | 0.00 |
July | 561.49 | 90.00 | 447.40 | 101.85 | 345.55 | 0.00 | 0.00 |
August | 508.72 | 108.89 | 421.67 | 122.33 | 299.34 | 0.00 | 0.00 |
September | 437.81 | 187.26 | 407.87 | 159.11 | 248.76 | 0.00 | 0.00 |
October | 301.54 | 296.39 | 342.30 | 161.10 | 181.20 | 0.00 | 0.00 |
November | 192.41 | 457.36 | 283.76 | 148.01 | 135.75 | 0.00 | 0.00 |
December | 138.76 | 702.80 | 291.46 | 164.99 | 126.47 | 0.00 | 0.00 |
Annual Sum or Average | 370.13 | 348.13 | 401.16 | 162.57 | 238.59 | 0.00 | 0.00 |
Minimum of Months | 138.76 | 90.00 | 283.76 | 85.48 | 126.47 | 0.00 | 0.00 |
Maximum of Months | 561.49 | 713.74 | 481.24 | 275.00 | 345.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.72 | 572.84 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 314.75 | 473.70 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 376.61 | 379.48 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 485.27 | 237.75 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 614.53 | 120.60 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 618.45 | 74.06 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 690.70 | 64.33 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 594.84 | 77.23 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 469.36 | 140.48 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 288.34 | 231.35 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 159.97 | 358.63 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 107.67 | 560.39 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 407.91 | 273.38 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 107.67 | 64.33 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 690.70 | 572.84 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.17 | 641.72 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 113.66 | 512.54 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 195.06 | 394.58 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 325.30 | 238.14 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 509.85 | 120.46 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 551.14 | 77.19 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 597.12 | 69.06 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 463.41 | 83.92 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 315.32 | 143.03 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 150.63 | 235.77 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 49.51 | 379.89 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 17.58 | 622.77 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 278.04 | 292.37 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 17.58 | 69.06 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 597.12 | 641.72 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.69 | 290.01 | 277.05 | 193.09 | 83.97 | 0.00 | 0.00 |
February | 315.93 | 243.03 | 345.89 | 232.72 | 113.16 | 0.00 | 0.00 |
March | 287.48 | 198.19 | 304.04 | 191.37 | 112.67 | 0.00 | 0.00 |
April | 287.98 | 126.90 | 277.70 | 150.56 | 127.14 | 0.00 | 0.00 |
May | 275.57 | 62.70 | 237.70 | 83.86 | 153.84 | 0.00 | 0.00 |
June | 262.46 | 37.78 | 208.87 | 55.03 | 153.84 | 0.00 | 0.00 |
July | 301.41 | 32.05 | 229.81 | 73.13 | 156.68 | 0.00 | 0.00 |
August | 306.80 | 39.11 | 243.85 | 101.38 | 142.48 | 0.00 | 0.00 |
September | 295.07 | 73.33 | 257.19 | 134.56 | 122.63 | 0.00 | 0.00 |
October | 230.82 | 120.60 | 228.69 | 136.33 | 92.36 | 0.00 | 0.00 |
November | 173.69 | 183.55 | 199.75 | 125.26 | 74.50 | 0.00 | 0.00 |
December | 158.63 | 281.12 | 212.80 | 139.62 | 73.18 | 0.00 | 0.00 |
Annual Sum or Average | 259.64 | 140.24 | 251.35 | 134.14 | 117.21 | 0.00 | 0.00 |
Minimum of Months | 158.63 | 32.05 | 199.75 | 55.03 | 73.18 | 0.00 | 0.00 |
Maximum of Months | 315.93 | 290.01 | 345.89 | 232.72 | 156.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.33 | 1792.49 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 11.92 | 1471.17 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 43.90 | 1148.26 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 198.94 | 687.49 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 583.42 | 321.56 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 814.94 | 209.01 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 824.24 | 183.89 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 558.66 | 230.94 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 308.37 | 418.11 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 90.10 | 706.80 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 10.03 | 1139.60 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 1746.26 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 288.83 | 835.22 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 183.89 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 824.24 | 1792.49 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.24 | 1821.57 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 10.03 | 1500.25 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 39.69 | 1173.39 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 189.51 | 702.82 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 573.46 | 328.08 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 805.84 | 213.97 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 816.57 | 188.27 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 550.73 | 237.16 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 299.76 | 427.95 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 83.36 | 724.54 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 8.82 | 1168.62 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 1776.18 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 283.24 | 852.42 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 188.27 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 816.57 | 1821.57 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.37 | 1089.57 | 438.48 | 223.84 | 214.64 | 0.00 | 0.00 |
February | 413.34 | 906.26 | 631.00 | 310.64 | 320.36 | 0.00 | 0.00 |
March | 592.31 | 726.69 | 739.05 | 371.93 | 367.12 | 0.00 | 0.00 |
April | 946.66 | 460.81 | 918.48 | 459.95 | 458.53 | 0.00 | 0.00 |
May | 1223.41 | 237.40 | 975.39 | 379.05 | 596.34 | 0.00 | 0.00 |
June | 1446.95 | 159.37 | 1059.11 | 437.02 | 622.08 | 0.00 | 0.00 |
July | 1493.32 | 137.55 | 1053.89 | 433.13 | 620.76 | 0.00 | 0.00 |
August | 1183.57 | 160.28 | 855.82 | 338.27 | 517.54 | 0.00 | 0.00 |
September | 889.85 | 273.54 | 727.17 | 312.49 | 414.68 | 0.00 | 0.00 |
October | 470.62 | 446.85 | 493.62 | 204.30 | 289.32 | 0.00 | 0.00 |
November | 217.58 | 703.46 | 353.42 | 148.58 | 204.84 | 0.00 | 0.00 |
December | 119.37 | 1077.95 | 342.57 | 160.66 | 181.91 | 0.00 | 0.00 |
Annual Sum or Average | 767.31 | 530.02 | 715.83 | 314.76 | 401.07 | 0.00 | 0.00 |
Minimum of Months | 119.37 | 137.55 | 342.57 | 148.58 | 181.91 | 0.00 | 0.00 |
Maximum of Months | 1493.32 | 1089.57 | 1059.11 | 459.95 | 622.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 487.25 | 1249.75 | 770.60 | 491.51 | 279.09 | 0.00 | 0.00 |
February | 760.58 | 1052.68 | 980.87 | 592.41 | 388.45 | 0.00 | 0.00 |
March | 730.69 | 858.38 | 897.48 | 487.14 | 410.34 | 0.00 | 0.00 |
April | 812.60 | 545.84 | 869.34 | 384.92 | 484.42 | 0.00 | 0.00 |
May | 900.55 | 277.03 | 832.91 | 225.57 | 607.35 | 0.00 | 0.00 |
June | 932.90 | 178.84 | 786.29 | 168.40 | 617.89 | 0.00 | 0.00 |
July | 1030.27 | 163.76 | 828.42 | 207.52 | 620.90 | 0.00 | 0.00 |
August | 966.50 | 199.01 | 805.57 | 261.57 | 544.00 | 0.00 | 0.00 |
September | 864.38 | 335.69 | 798.61 | 342.68 | 455.94 | 0.00 | 0.00 |
October | 619.46 | 530.90 | 681.91 | 347.05 | 334.86 | 0.00 | 0.00 |
November | 418.04 | 814.14 | 574.54 | 318.84 | 255.70 | 0.00 | 0.00 |
December | 331.19 | 1235.42 | 597.06 | 355.41 | 241.65 | 0.00 | 0.00 |
Annual Sum or Average | 737.47 | 618.23 | 784.00 | 347.07 | 436.93 | 0.00 | 0.00 |
Minimum of Months | 331.19 | 163.76 | 574.54 | 168.40 | 241.65 | 0.00 | 0.00 |
Maximum of Months | 1030.27 | 1249.75 | 980.87 | 592.41 | 620.90 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.215046E+10 | 0.246470E+10 | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.00 | 0.00 |
February | 0.270419E+10 | 0.190662E+10 | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.00 | 0.00 |
March | 0.269707E+10 | 0.174642E+10 | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.00 | 0.00 |
April | 0.260416E+10 | 0.110049E+10 | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.00 | 0.00 |
May | 0.255619E+10 | 0.589678E+09 | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.00 | 0.00 |
June | 0.233189E+10 | 0.361985E+09 | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.00 | 0.00 |
July | 0.274966E+10 | 0.341521E+09 | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.00 | 0.00 |
August | 0.282298E+10 | 0.401513E+09 | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.00 | 0.00 |
September | 0.265328E+10 | 0.658259E+09 | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.00 | 0.00 |
October | 0.215137E+10 | 0.108657E+10 | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.00 | 0.00 |
November | 0.158573E+10 | 0.157091E+10 | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.00 | 0.00 |
December | 0.152253E+10 | 0.240808E+10 | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285295E+11 | 0.146368E+11 | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152253E+10 | 0.341521E+09 | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.00 | 0.00 |
Maximum of Months | 0.282298E+10 | 0.246470E+10 | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601180E+10 | 0.699181E+10 | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.00 | 0.00 |
February | 0.755804E+10 | 0.542264E+10 | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.00 | 0.00 |
March | 0.753275E+10 | 0.500943E+10 | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.00 | 0.00 |
April | 0.726281E+10 | 0.322207E+10 | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.00 | 0.00 |
May | 0.710139E+10 | 0.178930E+10 | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.00 | 0.00 |
June | 0.645955E+10 | 0.113192E+10 | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.00 | 0.00 |
July | 0.765070E+10 | 0.105843E+10 | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.00 | 0.00 |
August | 0.786113E+10 | 0.126052E+10 | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.00 | 0.00 |
September | 0.739229E+10 | 0.200853E+10 | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.00 | 0.00 |
October | 0.599895E+10 | 0.319073E+10 | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.00 | 0.00 |
November | 0.442030E+10 | 0.449910E+10 | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.00 | 0.00 |
December | 0.424955E+10 | 0.682603E+10 | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.794992E+11 | 0.424105E+11 | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424955E+10 | 0.105843E+10 | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.786113E+10 | 0.699181E+10 | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.790411E+10 | 0.942234E+10 | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.00 | 0.00 |
February | 0.997525E+10 | 0.729941E+10 | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.00 | 0.00 |
March | 0.995071E+10 | 0.676457E+10 | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.00 | 0.00 |
April | 0.958622E+10 | 0.439235E+10 | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.00 | 0.00 |
May | 0.935900E+10 | 0.245083E+10 | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.00 | 0.00 |
June | 0.850772E+10 | 0.156135E+10 | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.00 | 0.00 |
July | 0.100922E+11 | 0.143639E+10 | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.00 | 0.00 |
August | 0.103565E+11 | 0.171428E+10 | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.00 | 0.00 |
September | 0.971930E+10 | 0.276248E+10 | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.00 | 0.00 |
October | 0.786958E+10 | 0.439590E+10 | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.00 | 0.00 |
November | 0.580733E+10 | 0.616135E+10 | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.00 | 0.00 |
December | 0.556823E+10 | 0.924923E+10 | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104696E+12 | 0.576105E+11 | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556823E+10 | 0.143639E+10 | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103565E+11 | 0.942234E+10 | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454145E+09 | 0.153083E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.764716E+09 | 0.114544E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.101171E+10 | 0.101753E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.126358E+10 | 0.618754E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.165496E+10 | 0.325129E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.161059E+10 | 0.194372E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.185807E+10 | 0.175232E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.160047E+10 | 0.209719E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.122192E+10 | 0.367180E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.773269E+09 | 0.624100E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.414502E+09 | 0.932168E+09 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.290102E+09 | 0.149646E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129180E+11 | 0.863691E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.290102E+09 | 0.175232E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185807E+10 | 0.153083E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 97577082.17 | 0.171496E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.275962E+09 | 0.123845E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.523998E+09 | 0.105776E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.846906E+09 | 0.619320E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.137590E+10 | 0.321577E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.143874E+10 | 0.198515E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.160909E+10 | 0.183779E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.124924E+10 | 0.223127E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.821166E+09 | 0.372434E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.402271E+09 | 0.636770E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.127251E+09 | 0.987398E+09 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 47486170.61 | 0.166305E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.881559E+10 | 0.921714E+10 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 47486170.61 | 0.183779E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160909E+10 | 0.171496E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.348935E+09 | 0.372766E+09 | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.00 | 0.00 |
February | 0.429959E+09 | 0.300936E+09 | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.00 | 0.00 |
March | 0.419841E+09 | 0.300722E+09 | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.00 | 0.00 |
April | 0.388676E+09 | 0.225433E+09 | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.00 | 0.00 |
May | 0.372812E+09 | 0.134219E+09 | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.00 | 0.00 |
June | 0.336484E+09 | 90216167.78 | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.00 | 0.00 |
July | 0.405783E+09 | 83768218.53 | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.00 | 0.00 |
August | 0.418693E+09 | 0.100283E+09 | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.00 | 0.00 |
September | 0.393183E+09 | 0.151459E+09 | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.00 | 0.00 |
October | 0.319665E+09 | 0.223103E+09 | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.00 | 0.00 |
November | 0.245549E+09 | 0.266181E+09 | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.00 | 0.00 |
December | 0.250351E+09 | 0.352214E+09 | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432993E+10 | 0.260130E+10 | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.245549E+09 | 83768218.53 | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.00 | 0.00 |
Maximum of Months | 0.429959E+09 | 0.372766E+09 | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 281584.76 | 0.528396E+09 | 58367319.83 | 0.00 | 58367319.83 | 0.00 | 0.00 |
February | 5405524.96 | 0.379190E+09 | 80980322.72 | 0.00 | 80980322.72 | 0.00 | 0.00 |
March | 18979668.52 | 0.318658E+09 | 0.110332E+09 | 4218.19 | 0.110328E+09 | 0.00 | 0.00 |
April | 71112824.04 | 0.178215E+09 | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 0.00 | 0.00 |
May | 0.195419E+09 | 84278419.17 | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.00 | 0.00 |
June | 0.256931E+09 | 51718100.12 | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.00 | 0.00 |
July | 0.266722E+09 | 46325033.24 | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.00 | 0.00 |
August | 0.184716E+09 | 57506893.73 | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.00 | 0.00 |
September | 0.103872E+09 | 0.103964E+09 | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.00 | 0.00 |
October | 35897218.20 | 0.187668E+09 | 89098491.50 | 0.00 | 89098491.50 | 0.00 | 0.00 |
November | 4657330.19 | 0.300643E+09 | 57091439.30 | 0.00 | 57091439.30 | 0.00 | 0.00 |
December | 0.00 | 0.507436E+09 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.114400E+10 | 0.274400E+10 | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 46325033.24 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Maximum of Months | 0.266722E+09 | 0.528396E+09 | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.440458E+09 | 0.152134E+10 | 0.803744E+09 | 0.476088E+09 | 0.327656E+09 | 0.00 | 0.00 |
February | 0.728948E+09 | 0.112703E+10 | 0.997957E+09 | 0.567701E+09 | 0.430256E+09 | 0.00 | 0.00 |
March | 0.979138E+09 | 0.995379E+09 | 0.119846E+10 | 0.672848E+09 | 0.525610E+09 | 0.00 | 0.00 |
April | 0.131166E+10 | 0.598482E+09 | 0.134807E+10 | 0.728269E+09 | 0.619798E+09 | 0.00 | 0.00 |
May | 0.156291E+10 | 0.304466E+09 | 0.139622E+10 | 0.577492E+09 | 0.818725E+09 | 0.00 | 0.00 |
June | 0.173294E+10 | 0.185776E+09 | 0.141973E+10 | 0.599743E+09 | 0.819988E+09 | 0.00 | 0.00 |
July | 0.187179E+10 | 0.165636E+09 | 0.148544E+10 | 0.634931E+09 | 0.850508E+09 | 0.00 | 0.00 |
August | 0.154032E+10 | 0.202013E+09 | 0.126568E+10 | 0.543647E+09 | 0.722031E+09 | 0.00 | 0.00 |
September | 0.119299E+10 | 0.356896E+09 | 0.109200E+10 | 0.523838E+09 | 0.568166E+09 | 0.00 | 0.00 |
October | 0.728316E+09 | 0.616256E+09 | 0.814234E+09 | 0.398101E+09 | 0.416133E+09 | 0.00 | 0.00 |
November | 0.402016E+09 | 0.922292E+09 | 0.598885E+09 | 0.303248E+09 | 0.295637E+09 | 0.00 | 0.00 |
December | 0.294405E+09 | 0.149166E+10 | 0.622191E+09 | 0.342657E+09 | 0.279534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127859E+11 | 0.848722E+10 | 0.130426E+11 | 0.636856E+10 | 0.667404E+10 | 0.00 | 0.00 |
Minimum of Months | 0.294405E+09 | 0.165636E+09 | 0.598885E+09 | 0.303248E+09 | 0.279534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187179E+10 | 0.152134E+10 | 0.148544E+10 | 0.728269E+09 | 0.850508E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71261589.57 | 0.169250E+10 | 0.370723E+09 | 0.123462E+09 | 0.247261E+09 | 0.00 | 0.00 |
February | 0.219063E+09 | 0.119844E+10 | 0.528614E+09 | 0.183814E+09 | 0.344801E+09 | 0.00 | 0.00 |
March | 0.477741E+09 | 0.102064E+10 | 0.781101E+09 | 0.323363E+09 | 0.457737E+09 | 0.00 | 0.00 |
April | 0.889627E+09 | 0.593759E+09 | 0.103276E+10 | 0.463981E+09 | 0.568774E+09 | 0.00 | 0.00 |
May | 0.129514E+10 | 0.303712E+09 | 0.121641E+10 | 0.437826E+09 | 0.778584E+09 | 0.00 | 0.00 |
June | 0.156820E+10 | 0.191336E+09 | 0.132562E+10 | 0.533091E+09 | 0.792533E+09 | 0.00 | 0.00 |
July | 0.162711E+10 | 0.175438E+09 | 0.133745E+10 | 0.525230E+09 | 0.812220E+09 | 0.00 | 0.00 |
August | 0.119458E+10 | 0.212540E+09 | 0.102666E+10 | 0.362432E+09 | 0.664227E+09 | 0.00 | 0.00 |
September | 0.794145E+09 | 0.357936E+09 | 0.792907E+09 | 0.286183E+09 | 0.506723E+09 | 0.00 | 0.00 |
October | 0.349956E+09 | 0.620383E+09 | 0.507940E+09 | 0.149118E+09 | 0.358822E+09 | 0.00 | 0.00 |
November | 0.108241E+09 | 0.971645E+09 | 0.317202E+09 | 81876671.53 | 0.235325E+09 | 0.00 | 0.00 |
December | 41237384.46 | 0.164686E+10 | 0.295375E+09 | 87671849.66 | 0.207703E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.863630E+10 | 0.898519E+10 | 0.953276E+10 | 0.355805E+10 | 0.597471E+10 | 0.00 | 0.00 |
Minimum of Months | 41237384.46 | 0.175438E+09 | 0.295375E+09 | 81876671.53 | 0.207703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162711E+10 | 0.169250E+10 | 0.133745E+10 | 0.533091E+09 | 0.812220E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.554153E+09 | 0.191169E+10 | 0.100331E+10 | 0.611112E+09 | 0.392194E+09 | 0.00 | 0.00 |
February | 0.838682E+09 | 0.144342E+10 | 0.116422E+10 | 0.665290E+09 | 0.498931E+09 | 0.00 | 0.00 |
March | 0.921067E+09 | 0.129294E+10 | 0.120129E+10 | 0.605687E+09 | 0.595605E+09 | 0.00 | 0.00 |
April | 0.104668E+10 | 0.789942E+09 | 0.115471E+10 | 0.464267E+09 | 0.690447E+09 | 0.00 | 0.00 |
May | 0.129078E+10 | 0.407318E+09 | 0.119312E+10 | 0.288811E+09 | 0.904305E+09 | 0.00 | 0.00 |
June | 0.134171E+10 | 0.253670E+09 | 0.111644E+10 | 0.221577E+09 | 0.894867E+09 | 0.00 | 0.00 |
July | 0.150389E+10 | 0.241060E+09 | 0.119831E+10 | 0.272792E+09 | 0.925516E+09 | 0.00 | 0.00 |
August | 0.136255E+10 | 0.291647E+09 | 0.112940E+10 | 0.327657E+09 | 0.801744E+09 | 0.00 | 0.00 |
September | 0.113479E+10 | 0.485387E+09 | 0.105721E+10 | 0.412420E+09 | 0.644789E+09 | 0.00 | 0.00 |
October | 0.807635E+09 | 0.793848E+09 | 0.916821E+09 | 0.431495E+09 | 0.485326E+09 | 0.00 | 0.00 |
November | 0.498727E+09 | 0.118548E+10 | 0.735506E+09 | 0.383644E+09 | 0.351862E+09 | 0.00 | 0.00 |
December | 0.371661E+09 | 0.188239E+10 | 0.780633E+09 | 0.441899E+09 | 0.338735E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116723E+11 | 0.109788E+11 | 0.126510E+11 | 0.512665E+10 | 0.752432E+10 | 0.00 | 0.00 |
Minimum of Months | 0.371661E+09 | 0.241060E+09 | 0.735506E+09 | 0.221577E+09 | 0.338735E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150389E+10 | 0.191169E+10 | 0.120129E+10 | 0.665290E+09 | 0.925516E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451894E+09 | 0.153429E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.761451E+09 | 0.114598E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.100871E+10 | 0.101640E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.125781E+10 | 0.616260E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.164596E+10 | 0.323006E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.160301E+10 | 0.191952E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.184998E+10 | 0.172313E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.159321E+10 | 0.206860E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.121658E+10 | 0.364116E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.772287E+09 | 0.619658E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.414647E+09 | 0.929580E+09 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.288377E+09 | 0.150096E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128639E+11 | 0.862137E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.288377E+09 | 0.172313E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184998E+10 | 0.153429E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96891062.97 | 0.171879E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.274969E+09 | 0.123995E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.522450E+09 | 0.105684E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.843181E+09 | 0.617267E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.136559E+10 | 0.322633E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.142855E+10 | 0.200085E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.159933E+10 | 0.184981E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.124120E+10 | 0.224761E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.817300E+09 | 0.370739E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.403449E+09 | 0.631473E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.128321E+09 | 0.984687E+09 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 47096671.69 | 0.166802E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876833E+10 | 0.922022E+10 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 47096671.69 | 0.184981E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159933E+10 | 0.171879E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601821E+09 | 0.776762E+09 | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.00 | 0.00 |
February | 0.764294E+09 | 0.587948E+09 | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.00 | 0.00 |
March | 0.769986E+09 | 0.530844E+09 | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.00 | 0.00 |
April | 0.746441E+09 | 0.328936E+09 | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.00 | 0.00 |
May | 0.738074E+09 | 0.167936E+09 | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.00 | 0.00 |
June | 0.680284E+09 | 97915883.28 | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.00 | 0.00 |
July | 0.807292E+09 | 85836035.95 | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.00 | 0.00 |
August | 0.821744E+09 | 0.104745E+09 | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.00 | 0.00 |
September | 0.764820E+09 | 0.190079E+09 | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.00 | 0.00 |
October | 0.618218E+09 | 0.323026E+09 | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.00 | 0.00 |
November | 0.450215E+09 | 0.475771E+09 | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.00 | 0.00 |
December | 0.424888E+09 | 0.752951E+09 | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.818808E+10 | 0.442275E+10 | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424888E+09 | 85836035.95 | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.821744E+09 | 0.776762E+09 | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 887566.48 | 0.480100E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 28844368.29 | 0.355905E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 0.117585E+09 | 0.307550E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.515651E+09 | 0.178197E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.156263E+10 | 0.861270E+09 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.211232E+10 | 0.541761E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.220765E+10 | 0.492523E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.149630E+10 | 0.618542E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.799298E+09 | 0.108373E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.241316E+09 | 0.189310E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 26010594.67 | 0.295385E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.467720E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.910850E+10 | 0.263395E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.492523E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220765E+10 | 0.480100E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 636671.25 | 0.487890E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 24269344.72 | 0.362940E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 0.106295E+09 | 0.314280E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.491209E+09 | 0.182170E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.153597E+10 | 0.878741E+09 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.208873E+10 | 0.554608E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.218709E+10 | 0.504258E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.147508E+10 | 0.635221E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.776978E+09 | 0.110926E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.223260E+09 | 0.194061E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 22857359.21 | 0.302905E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.475732E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.893237E+10 | 0.268819E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.504258E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218709E+10 | 0.487890E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509888E+09 | 0.291830E+10 | 0.117442E+10 | 0.599533E+09 | 0.574892E+09 | 0.00 | 0.00 |
February | 0.999959E+09 | 0.219241E+10 | 0.152651E+10 | 0.751489E+09 | 0.775022E+09 | 0.00 | 0.00 |
March | 0.158644E+10 | 0.194636E+10 | 0.197947E+10 | 0.996166E+09 | 0.983302E+09 | 0.00 | 0.00 |
April | 0.245375E+10 | 0.119442E+10 | 0.238070E+10 | 0.119218E+10 | 0.118852E+10 | 0.00 | 0.00 |
May | 0.327679E+10 | 0.635853E+09 | 0.261249E+10 | 0.101526E+10 | 0.159723E+10 | 0.00 | 0.00 |
June | 0.375050E+10 | 0.413100E+09 | 0.274521E+10 | 0.113276E+10 | 0.161244E+10 | 0.00 | 0.00 |
July | 0.399971E+10 | 0.368417E+09 | 0.282274E+10 | 0.116009E+10 | 0.166265E+10 | 0.00 | 0.00 |
August | 0.317008E+10 | 0.429284E+09 | 0.229222E+10 | 0.906028E+09 | 0.138619E+10 | 0.00 | 0.00 |
September | 0.230649E+10 | 0.709008E+09 | 0.188482E+10 | 0.809981E+09 | 0.107484E+10 | 0.00 | 0.00 |
October | 0.126052E+10 | 0.119684E+10 | 0.132212E+10 | 0.547198E+09 | 0.774919E+09 | 0.00 | 0.00 |
November | 0.563960E+09 | 0.182338E+10 | 0.916052E+09 | 0.385113E+09 | 0.530939E+09 | 0.00 | 0.00 |
December | 0.319726E+09 | 0.288718E+10 | 0.917533E+09 | 0.430317E+09 | 0.487216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241978E+11 | 0.167146E+11 | 0.225743E+11 | 0.992612E+10 | 0.126482E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319726E+09 | 0.368417E+09 | 0.916052E+09 | 0.385113E+09 | 0.487216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.399971E+10 | 0.291830E+10 | 0.282274E+10 | 0.119218E+10 | 0.166265E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130505E+10 | 0.334734E+10 | 0.206398E+10 | 0.131646E+10 | 0.747524E+09 | 0.00 | 0.00 |
February | 0.184001E+10 | 0.254665E+10 | 0.237291E+10 | 0.143317E+10 | 0.939745E+09 | 0.00 | 0.00 |
March | 0.195709E+10 | 0.229907E+10 | 0.240382E+10 | 0.130476E+10 | 0.109906E+10 | 0.00 | 0.00 |
April | 0.210627E+10 | 0.141481E+10 | 0.225333E+10 | 0.997719E+09 | 0.125562E+10 | 0.00 | 0.00 |
May | 0.241204E+10 | 0.741989E+09 | 0.223088E+10 | 0.604154E+09 | 0.162672E+10 | 0.00 | 0.00 |
June | 0.241808E+10 | 0.463545E+09 | 0.203806E+10 | 0.436491E+09 | 0.160156E+10 | 0.00 | 0.00 |
July | 0.275948E+10 | 0.438614E+09 | 0.221884E+10 | 0.555822E+09 | 0.166302E+10 | 0.00 | 0.00 |
August | 0.258868E+10 | 0.533032E+09 | 0.215765E+10 | 0.700600E+09 | 0.145705E+10 | 0.00 | 0.00 |
September | 0.224047E+10 | 0.870113E+09 | 0.207001E+10 | 0.888221E+09 | 0.118179E+10 | 0.00 | 0.00 |
October | 0.165917E+10 | 0.142198E+10 | 0.182642E+10 | 0.929526E+09 | 0.896898E+09 | 0.00 | 0.00 |
November | 0.108356E+10 | 0.211025E+10 | 0.148921E+10 | 0.826446E+09 | 0.662769E+09 | 0.00 | 0.00 |
December | 0.887070E+09 | 0.330895E+10 | 0.159917E+10 | 0.951937E+09 | 0.647228E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232570E+11 | 0.194963E+11 | 0.247243E+11 | 0.109453E+11 | 0.137790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.887070E+09 | 0.438614E+09 | 0.148921E+10 | 0.436491E+09 | 0.647228E+09 | 0.00 | 0.00 |
Maximum of Months | 0.275948E+10 | 0.334734E+10 | 0.240382E+10 | 0.143317E+10 | 0.166302E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770937E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166591898.7 | 81.21 | 0.00 | 0.00 |
February | 0.696403E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148067978.1 | 81.21 | 0.00 | 0.00 |
March | 0.770408E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162605922.8 | 81.21 | 0.00 | 0.00 |
April | 0.746528E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156683707.4 | 81.21 | 0.00 | 0.00 |
May | 0.770441E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161634762.8 | 81.21 | 0.00 | 0.00 |
June | 0.745685E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156322677.6 | 81.21 | 0.00 | 0.00 |
July | 0.771234E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161490977.9 | 81.21 | 0.00 | 0.00 |
August | 0.770432E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161515976.6 | 81.21 | 0.00 | 0.00 |
September | 0.746635E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156431050.9 | 81.21 | 0.00 | 0.00 |
October | 0.770329E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161853231.0 | 81.21 | 0.00 | 0.00 |
November | 0.744935E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156910128.3 | 81.21 | 0.00 | 0.00 |
December | 0.771617E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165308560.8 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907558E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191542E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696403E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -166591898.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771617E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148067978.1 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129329E+12 | -0.127565E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176463E+10 | 80.10 | 0.00 | 0.00 |
February | 0.116968E+12 | -0.115406E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156234E+10 | 79.76 | 0.00 | 0.00 |
March | 0.129468E+12 | -0.127734E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173343E+10 | 79.82 | 0.00 | 0.00 |
April | 0.125045E+12 | -0.123356E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168976E+10 | 80.28 | 0.00 | 0.00 |
May | 0.128798E+12 | -0.127037E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176169E+10 | 81.03 | 0.00 | 0.00 |
June | 0.120972E+12 | -0.119267E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170478E+10 | 81.30 | 0.00 | 0.00 |
July | 0.120308E+12 | -0.118564E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174443E+10 | 81.27 | 0.00 | 0.00 |
August | 0.117890E+12 | -0.116157E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173269E+10 | 81.26 | 0.00 | 0.00 |
September | 0.114496E+12 | -0.112822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167369E+10 | 81.26 | 0.00 | 0.00 |
October | 0.121421E+12 | -0.119692E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172891E+10 | 81.26 | 0.00 | 0.00 |
November | 0.122515E+12 | -0.120840E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167548E+10 | 81.32 | 0.00 | 0.00 |
December | 0.128930E+12 | -0.127171E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175930E+10 | 80.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.147614E+13 | -0.145561E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205311E+11 | 80.79 | 0.00 | 0.00 |
Minimum of Months | 0.114496E+12 | -0.127734E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176463E+10 | 79.76 | 0.00 | 0.00 |
Maximum of Months | 0.129468E+12 | -0.112822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156234E+10 | 81.32 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.849943E+11 | -0.834304E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156386E+10 | 58.99 | 0.00 | 0.00 |
February | 0.784891E+11 | -0.771072E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138185E+10 | 58.99 | 0.00 | 0.00 |
March | 0.866175E+11 | -0.850851E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153243E+10 | 58.99 | 0.00 | 0.00 |
April | 0.812807E+11 | -0.797995E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148120E+10 | 58.99 | 0.00 | 0.00 |
May | 0.798111E+11 | -0.782903E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152079E+10 | 58.99 | 0.00 | 0.00 |
June | 0.727549E+11 | -0.712941E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146071E+10 | 58.98 | 0.00 | 0.00 |
July | 0.712265E+11 | -0.697394E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148711E+10 | 58.98 | 0.00 | 0.00 |
August | 0.692247E+11 | -0.677536E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147114E+10 | 58.98 | 0.00 | 0.00 |
September | 0.673034E+11 | -0.658840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141935E+10 | 58.98 | 0.00 | 0.00 |
October | 0.721637E+11 | -0.706980E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146572E+10 | 58.98 | 0.00 | 0.00 |
November | 0.739089E+11 | -0.724893E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141957E+10 | 58.98 | 0.00 | 0.00 |
December | 0.810716E+11 | -0.795444E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152725E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.918846E+12 | -0.901115E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177310E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.673034E+11 | -0.850851E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156386E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.866175E+11 | -0.658840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138185E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.87 | 0.86 | 01-JAN-08:39 | 4819.80 | 35.99 | 235.33 | 243.67 | 3997.19 | 36.97 | 241.00 | 225.50 |
February | 265.33 | 0.87 | 0.86 | 01-FEB-08:39 | 7655.64 | 36.13 | 258.50 | 259.50 | 3210.03 | 32.22 | 259.17 | 241.50 |
March | 254.17 | 0.87 | 0.86 | 02-MAR-10:39 | 9970.23 | 33.91 | 213.50 | 326.33 | 897.95 | 23.19 | 239.50 | 277.83 |
April | 296.33 | 0.87 | 0.86 | 01-APR-08:09 | 1705.92 | 20.99 | 110.00 | 357.33 | 694.46 | 22.60 | 262.67 | 303.50 |
May | 437.50 | 0.87 | 0.86 | 01-MAY-06:49 | 1602.41 | 20.64 | 166.33 | 417.83 | 625.90 | 22.35 | 329.33 | 353.00 |
June | 401.83 | 0.87 | 0.86 | 01-JUN-05:40 | 1523.50 | 20.69 | 175.83 | 418.00 | 607.49 | 22.40 | 297.67 | 355.67 |
July | 409.17 | 0.87 | 0.86 | 01-JUL-05:49 | 1637.74 | 21.04 | 209.50 | 424.83 | 657.02 | 22.75 | 321.17 | 366.00 |
August | 352.83 | 0.87 | 0.86 | 01-AUG-07:40 | 1925.02 | 21.20 | 187.33 | 383.50 | 759.40 | 22.90 | 280.33 | 328.17 |
September | 344.17 | 0.87 | 0.86 | 01-SEP-06:00 | 3364.22 | 24.27 | 204.17 | 335.50 | 764.38 | 22.46 | 255.17 | 289.67 |
October | 299.00 | 0.87 | 0.86 | 01-OCT-06:49 | 5513.14 | 32.20 | 271.00 | 301.83 | 1085.70 | 24.94 | 232.33 | 265.17 |
November | 255.50 | 0.87 | 0.86 | 01-NOV-08:09 | 3835.37 | 34.60 | 245.83 | 246.00 | 3025.34 | 35.21 | 247.83 | 218.00 |
December | 226.33 | 0.87 | 0.86 | 01-DEC-08:20 | 3528.46 | 34.05 | 211.00 | 229.00 | 2800.49 | 35.09 | 216.50 | 202.50 |
Annual Sum or Average | 3785.50 | 0.87 | 3563.90 | 26.72 | 2488.33 | 3943.33 | 1402.09 | 26.00 | 3182.67 | 3426.50 | ||
Minimum of Months | 226.33 | 0.87 | 0.86 | 1523.50 | 20.64 | 110.00 | 229.00 | 607.49 | 22.35 | 216.50 | 202.50 | |
Maximum of Months | 437.50 | 0.87 | 0.86 | 9970.23 | 36.13 | 271.00 | 424.83 | 3997.19 | 36.97 | 329.33 | 366.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.24 | 0.22 | 01-JAN-08:30 | 5293.54 | 36.08 | 237.17 | 249.50 | 4468.69 | 37.04 | 241.83 | 236.50 |
February | 265.33 | 0.24 | 0.22 | 01-FEB-08:39 | 8207.70 | 36.22 | 258.83 | 266.50 | 3756.81 | 32.08 | 240.50 | 252.50 |
March | 254.17 | 0.25 | 0.22 | 02-MAR-10:39 | 10529.02 | 34.08 | 214.67 | 335.83 | 1454.63 | 22.93 | 230.33 | 307.33 |
April | 296.33 | 0.26 | 0.22 | 01-APR-07:40 | 2142.65 | 21.01 | 113.83 | 371.17 | 1129.97 | 22.50 | 263.17 | 338.33 |
May | 437.50 | 0.26 | 0.22 | 01-MAY-05:00 | 1903.58 | 21.03 | 196.67 | 430.00 | 926.01 | 22.57 | 339.00 | 397.33 |
June | 401.83 | 0.26 | 0.22 | 01-JUN-05:10 | 1799.80 | 21.14 | 210.17 | 434.00 | 882.83 | 22.68 | 318.83 | 396.17 |
July | 409.17 | 0.25 | 0.22 | 01-JUL-05:19 | 1947.23 | 21.40 | 231.83 | 439.83 | 965.49 | 22.95 | 342.50 | 403.50 |
August | 352.83 | 0.25 | 0.22 | 01-AUG-07:40 | 2294.05 | 21.46 | 191.00 | 395.33 | 1127.09 | 23.02 | 299.33 | 361.67 |
September | 344.17 | 0.25 | 0.22 | 01-SEP-06:40 | 3748.01 | 24.45 | 204.17 | 345.17 | 1147.00 | 22.57 | 255.67 | 318.33 |
October | 299.00 | 0.24 | 0.22 | 01-OCT-06:49 | 5889.62 | 32.37 | 274.67 | 309.83 | 1463.02 | 25.03 | 226.00 | 286.67 |
November | 255.50 | 0.25 | 0.22 | 01-NOV-07:00 | 4174.22 | 34.69 | 246.67 | 253.00 | 3363.43 | 35.30 | 248.50 | 234.33 |
December | 226.33 | 0.24 | 0.22 | 01-DEC-08:09 | 3896.98 | 34.19 | 212.67 | 238.00 | 3166.85 | 35.20 | 217.83 | 217.67 |
Annual Sum or Average | 3785.50 | 0.25 | 3946.27 | 26.94 | 2592.33 | 4068.17 | 1783.04 | 26.09 | 3223.50 | 3750.33 | ||
Minimum of Months | 226.33 | 0.24 | 0.22 | 1799.80 | 21.01 | 113.83 | 238.00 | 882.83 | 22.50 | 217.83 | 217.67 | |
Maximum of Months | 437.50 | 0.26 | 0.22 | 10529.02 | 36.22 | 274.67 | 439.83 | 4468.69 | 37.04 | 342.50 | 403.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419084E+12 | 384685.20 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242790E+12 | 376753.50 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150560E+12 | 362492.59 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548315E+11 | 133181.87 | 19-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.529430E+11 | 129192.04 | 05-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266324E+11 | 117044.75 | 16-JUN-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203294E+11 | 113194.11 | 02-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200386E+11 | 120418.32 | 19-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.675002E+11 | 126355.86 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.643394E+11 | 149680.69 | 09-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866501E+11 | 139285.76 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366975E+12 | 370543.06 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157267E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.200386E+11 | 113194.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419084E+12 | 384685.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468992E+10 | 7287.15 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105746E+10 | 7109.49 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.378032E+09 | 6788.29 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246371E+10 | 6973.70 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.468992E+10 | 7287.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.707503E+10 | 5004.76 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416011E+10 | 4887.02 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322429E+10 | 4668.43 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152148E+10 | 2077.24 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361157E+09 | 1393.51 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163353E+09 | 1124.22 | 04-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31495354.77 | 568.83 | 09-JUL-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89542839.77 | 977.76 | 19-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.480725E+09 | 1091.13 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178357E+10 | 2200.71 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329136E+10 | 3083.85 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685957E+10 | 4783.19 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31495354.77 | 568.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.707503E+10 | 5004.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172041E+10 | 1812.36 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.667156E+09 | 1770.27 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231405E+09 | 1692.02 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1093531.69 | 177.35 | 04-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1302869.20 | 126.83 | 30-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86026652.08 | 542.65 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143384E+10 | 1733.11 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172041E+10 | 1812.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391899E+10 | 2603.50 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230344E+10 | 2542.40 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144052E+10 | 2428.93 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220179E+09 | 771.40 | 05-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1436310.01 | 259.46 | 01-MAY-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84748106.87 | 483.15 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847790E+09 | 1101.97 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347993E+10 | 2488.50 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.391899E+10 | 2603.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274583E+10 | 1648.36 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177412E+10 | 1609.89 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123426E+10 | 1538.43 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279759E+09 | 566.22 | 05-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6759300.51 | 242.70 | 01-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172524E+09 | 436.24 | 30-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858716E+09 | 865.34 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250932E+10 | 1575.96 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274583E+10 | 1648.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.629034E+10 | 11001.53 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233469E+10 | 10732.93 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807667E+09 | 10247.36 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18516402.67 | 786.25 | 05-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 193403.81 | 142.40 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9503003.48 | 906.12 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78961510.90 | 1682.24 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506501E+10 | 10527.64 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.629034E+10 | 11001.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127922E+11 | 14114.26 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.525873E+10 | 13786.24 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276431E+10 | 13176.46 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555079E+09 | 4154.98 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14008784.36 | 1417.50 | 09-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2911042.54 | 1297.66 | 09-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11298540.08 | 1455.65 | 15-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73554141.09 | 2141.96 | 20-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.870367E+09 | 3972.47 | 06-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238354E+10 | 6006.11 | 24-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116991E+11 | 13496.70 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127922E+11 | 14114.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273973E+11 | 35177.09 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.953419E+10 | 34363.05 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305002E+10 | 32849.09 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8072105.00 | 2190.26 | 27-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9681203.19 | 1640.00 | 30-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863851E+09 | 9557.91 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229312E+11 | 33644.28 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.273973E+11 | 35177.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248258E+11 | 17370.72 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133987E+11 | 16963.41 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812324E+10 | 16206.94 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144679E+10 | 5144.92 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1390419.91 | 1127.28 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242272E+10 | 5432.37 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.838252E+10 | 8661.60 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231736E+11 | 16604.11 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248258E+11 | 17370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151285E+11 | 10806.46 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.859957E+10 | 10550.67 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.540282E+10 | 10076.10 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123401E+10 | 3552.92 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28106698.55 | 1331.42 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1587192.99 | 368.20 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136333E+10 | 3395.88 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.469396E+10 | 5034.53 | 25-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138265E+11 | 10325.19 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151285E+11 | 10806.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.771765E+10 | 13683.00 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258203E+10 | 13345.49 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662432E+09 | 12719.67 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616499E+10 | 13087.72 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.771765E+10 | 13683.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.769148E+10 | 14092.44 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253074E+10 | 13744.96 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.646497E+09 | 13100.75 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608896E+10 | 13479.57 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769148E+10 | 14092.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504399E+10 | 9362.24 | 06-JAN-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173594E+10 | 9157.73 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567922E+09 | 8732.98 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383118E+10 | 8982.17 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504399E+10 | 9362.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272832E+11 | 36176.29 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146826E+11 | 35661.29 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765465E+10 | 34299.09 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.828534E+09 | 5624.77 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17177758.31 | 1382.91 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21534.43 | 0.34 | 30-JUN-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21829.09 | 0.34 | 28-JUL-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22684.57 | 0.33 | 27-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5915.76 | 0.34 | 01-SEP-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255729E+09 | 3973.78 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316836E+10 | 8916.33 | 25-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233409E+11 | 34985.37 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5915.76 | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272832E+11 | 36176.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112677E+11 | 9044.80 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693887E+10 | 9043.88 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494483E+10 | 9044.39 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168935E+10 | 9042.91 | 04-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146012E+09 | 6704.86 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25606832.41 | 5133.93 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6318739.00 | 3867.82 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30795117.98 | 4959.87 | 18-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.242958E+09 | 4916.35 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197876E+10 | 9043.12 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.515665E+10 | 9044.53 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110000E+11 | 9045.52 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6318739.00 | 3867.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112677E+11 | 9045.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129485E+11 | 8948.65 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842858E+10 | 8947.57 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.607677E+10 | 8948.32 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206845E+10 | 8947.14 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163800E+09 | 8654.42 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22072860.80 | 4300.73 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3748904.99 | 3247.76 | 15-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31185232.79 | 5289.13 | 25-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285683E+09 | 5838.33 | 04-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237699E+10 | 8947.08 | 29-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.599865E+10 | 8949.14 | 09-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122936E+11 | 8949.22 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3748904.99 | 3247.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129485E+11 | 8949.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114296E+11 | 29108.25 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208124E+10 | 20316.82 | 17-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5966983.72 | 2117.99 | 08-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659198E+09 | 12303.20 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149635E+11 | 29109.69 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149635E+11 | 29109.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.639958E+11 | 49039.01 | 06-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401834E+11 | 48989.44 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267757E+11 | 48982.17 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541478E+10 | 47508.51 | 04-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185665E+09 | 42378.50 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27737910.86 | 31097.18 | 12-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11262093.58 | 31574.89 | 09-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50005851.20 | 33710.25 | 10-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149320E+09 | 30904.27 | 02-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395109E+10 | 47424.12 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202719E+11 | 48989.35 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577902E+11 | 48990.44 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11262093.58 | 30904.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.639958E+11 | 49039.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112492E+11 | 8854.92 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690651E+10 | 8853.74 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.489377E+10 | 8854.43 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162576E+10 | 8838.38 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166328E+09 | 4437.23 | 11-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15668741.46 | 4826.37 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4681731.76 | 4030.61 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26499322.66 | 4612.26 | 03-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271666E+09 | 5986.96 | 04-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205935E+10 | 8852.70 | 29-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.518898E+10 | 8854.65 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109541E+11 | 8855.68 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4681731.76 | 4030.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112492E+11 | 8855.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129717E+11 | 8745.05 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844721E+10 | 8744.08 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.603839E+10 | 8744.83 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196224E+10 | 8741.53 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193021E+09 | 5888.20 | 14-MAY-20:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13413383.67 | 4221.70 | 12-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3820757.89 | 3905.92 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26584265.53 | 4529.54 | 17-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333571E+09 | 6218.04 | 08-SEP-19:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249431E+10 | 8743.62 | 29-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600924E+10 | 8744.78 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122814E+11 | 8745.85 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3820757.89 | 3905.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129717E+11 | 8745.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356586E+10 | 2625.06 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228733E+10 | 2624.77 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168187E+10 | 2625.04 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636154E+09 | 2624.96 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81938815.46 | 2550.60 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20059709.45 | 1281.86 | 12-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2479988.00 | 1015.47 | 10-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16339640.52 | 1227.63 | 03-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129171E+09 | 1440.57 | 28-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.752641E+09 | 2625.19 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176213E+10 | 2625.47 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350272E+10 | 2625.33 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2479988.00 | 1015.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356586E+10 | 2625.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404997E+10 | 2589.34 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272580E+10 | 2589.13 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202923E+10 | 2589.73 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.758622E+09 | 2589.24 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81734448.40 | 2530.58 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14867023.66 | 1340.02 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 947590.91 | 1118.43 | 31-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15216593.21 | 1257.95 | 20-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147931E+09 | 1566.58 | 28-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.888867E+09 | 2589.59 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202249E+10 | 2589.75 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386915E+10 | 2589.61 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 947590.91 | 1118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404997E+10 | 2589.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124436E+11 | 12613.11 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724834E+10 | 12609.95 | 09-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522231E+10 | 12611.71 | 03-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184554E+10 | 12568.28 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222679E+09 | 7152.98 | 04-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47982259.20 | 7239.39 | 22-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14923429.14 | 5308.16 | 20-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35471268.02 | 6279.85 | 17-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231997E+09 | 6120.36 | 29-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195474E+10 | 12483.96 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549574E+10 | 12611.97 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126323E+11 | 12613.10 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14923429.14 | 5308.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126323E+11 | 12613.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.134043E+11 | 0.134043E+11 | 185320.06 | 23-APR-18:10 | 185320.06 | 0.02 |
May | 0.00 | 0.00 | 0.103904E+12 | 0.101607E+12 | 280185.54 | 25-MAY-18:20 | 234854.45 | 0.29 |
June | 0.00 | 0.00 | 0.274519E+12 | 0.191042E+12 | 474499.08 | 27-JUN-19:50 | 210267.89 | 0.60 |
July | 0.00 | 0.00 | 0.384403E+12 | 0.246494E+12 | 506740.44 | 21-JUL-19:20 | 207293.60 | 0.82 |
August | 0.00 | 0.00 | 0.260060E+12 | 0.181312E+12 | 458574.98 | 31-AUG-19:05 | 204339.15 | 0.77 |
September | 0.00 | 0.00 | 0.582176E+11 | 0.502166E+11 | 255913.38 | 01-SEP-10:50 | 166328.59 | 0.23 |
October | 0.00 | 0.00 | 0.814646E+10 | 0.814646E+10 | 131669.33 | 19-OCT-15:04 | 131669.33 | 0.03 |
November | 0.00 | 0.00 | 0.104414E+10 | 0.104414E+10 | 54235.74 | 01-NOV-15:30 | 54235.74 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110370E+13 | 0.793267E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.384403E+12 | 0.246494E+12 | 506740.44 | 234854.45 | 0.82 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.823506E+09 | 0.823506E+09 | 17157.66 | 23-APR-15:01 | 17157.66 | 0.01 |
May | 0.00 | 0.00 | 0.698869E+10 | 0.673715E+10 | 22951.99 | 26-MAY-09:03 | 13603.47 | 0.22 |
June | 0.00 | 0.00 | 0.194790E+11 | 0.130069E+11 | 37981.96 | 25-JUN-08:04 | 17634.05 | 0.45 |
July | 0.00 | 0.00 | 0.282154E+11 | 0.170906E+11 | 41146.07 | 05-JUL-13:00 | 16537.85 | 0.62 |
August | 0.00 | 0.00 | 0.191980E+11 | 0.124591E+11 | 36218.62 | 31-AUG-20:40 | 16016.83 | 0.59 |
September | 0.00 | 0.00 | 0.390866E+10 | 0.315383E+10 | 24121.93 | 01-SEP-01:00 | 8846.91 | 0.15 |
October | 0.00 | 0.00 | 0.525162E+09 | 0.525162E+09 | 14575.81 | 19-OCT-15:01 | 14575.81 | 0.01 |
November | 0.00 | 0.00 | 78057595.70 | 78057595.70 | 7087.99 | 01-NOV-15:02 | 7087.99 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.792165E+11 | 0.538743E+11 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.282154E+11 | 0.170906E+11 | 41146.07 | 17634.05 | 0.62 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1483618.25 | 1483618.25 | 7607.26 | 27-JAN-16:01 | 7607.26 | 0.00 |
February | 0.00 | 0.00 | 0.174593E+09 | 0.174462E+09 | 19556.63 | 04-FEB-16:01 | 19556.63 | 0.00 |
March | 0.00 | 0.00 | 0.664292E+09 | 0.664055E+09 | 19574.70 | 28-MAR-18:01 | 19574.70 | 0.00 |
April | 0.00 | 0.00 | 0.232432E+10 | 0.216525E+10 | 19570.14 | 16-APR-15:01 | 19570.14 | 0.06 |
May | 0.00 | 0.00 | 0.631597E+10 | 0.440435E+10 | 19574.48 | 04-MAY-15:01 | 19574.48 | 0.54 |
June | 0.00 | 0.00 | 0.819312E+10 | 0.459695E+10 | 21106.35 | 10-JUN-15:02 | 13825.97 | 0.86 |
July | 0.00 | 0.00 | 0.108875E+11 | 0.593692E+10 | 20505.06 | 05-JUL-08:61 | 14915.74 | 0.94 |
August | 0.00 | 0.00 | 0.865489E+10 | 0.440273E+10 | 20980.82 | 30-AUG-08:61 | 14574.90 | 0.88 |
September | 0.00 | 0.00 | 0.409333E+10 | 0.217963E+10 | 20458.90 | 19-SEP-15:02 | 14071.88 | 0.63 |
October | 0.00 | 0.00 | 0.116927E+10 | 0.691433E+09 | 19574.80 | 21-OCT-18:01 | 19574.80 | 0.19 |
November | 0.00 | 0.00 | 33692061.78 | 31902131.95 | 19552.59 | 17-NOV-16:01 | 19552.59 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.425125E+11 | 0.252492E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108875E+11 | 0.593692E+10 | 21106.35 | 19574.80 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 218107.58 | 218107.58 | 1910.29 | 17-JAN-16:04 | 1910.29 | 0.00 |
February | 0.00 | 0.00 | 26367073.86 | 26282592.41 | 17850.72 | 28-FEB-16:02 | 17850.72 | 0.00 |
March | 0.00 | 0.00 | 0.257385E+09 | 0.257239E+09 | 18654.17 | 28-MAR-18:01 | 18654.17 | 0.00 |
April | 0.00 | 0.00 | 0.119001E+10 | 0.108292E+10 | 21339.13 | 11-APR-18:11 | 21339.13 | 0.04 |
May | 0.00 | 0.00 | 0.428914E+10 | 0.280992E+10 | 21974.24 | 06-MAY-18:42 | 21974.24 | 0.44 |
June | 0.00 | 0.00 | 0.598717E+10 | 0.321435E+10 | 22360.24 | 25-JUN-08:51 | 14612.65 | 0.65 |
July | 0.00 | 0.00 | 0.794721E+10 | 0.424464E+10 | 22649.27 | 30-JUL-08:41 | 14217.30 | 0.69 |
August | 0.00 | 0.00 | 0.555774E+10 | 0.256263E+10 | 20604.55 | 30-AUG-08:51 | 13903.80 | 0.64 |
September | 0.00 | 0.00 | 0.200955E+10 | 0.836101E+09 | 21191.83 | 23-SEP-17:41 | 21191.83 | 0.45 |
October | 0.00 | 0.00 | 0.330555E+09 | 0.163107E+09 | 18035.58 | 21-OCT-18:32 | 18035.58 | 0.08 |
November | 0.00 | 0.00 | 4303609.03 | 2902849.13 | 10980.71 | 17-NOV-16:01 | 10980.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.275997E+11 | 0.152003E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.794721E+10 | 0.424464E+10 | 22649.27 | 21974.24 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1623355.13 | 1623355.13 | 2270.08 | 28-FEB-14:55 | 2270.08 | 0.00 |
March | 0.00 | 0.00 | 0.246875E+10 | 0.246875E+10 | 36375.43 | 29-MAR-12:30 | 36375.43 | 0.00 |
April | 0.00 | 0.00 | 0.157283E+11 | 0.152051E+11 | 50753.40 | 13-APR-13:10 | 50753.40 | 0.03 |
May | 0.00 | 0.00 | 0.331983E+11 | 0.219234E+11 | 50435.65 | 18-MAY-13:00 | 40130.11 | 0.44 |
June | 0.00 | 0.00 | 0.393457E+11 | 0.167810E+11 | 52415.21 | 30-JUN-12:40 | 38604.19 | 0.83 |
July | 0.00 | 0.00 | 0.517897E+11 | 0.213692E+11 | 55819.27 | 23-JUL-13:00 | 44037.15 | 0.97 |
August | 0.00 | 0.00 | 0.479099E+11 | 0.210360E+11 | 59796.59 | 26-AUG-12:40 | 53036.01 | 0.96 |
September | 0.00 | 0.00 | 0.324053E+11 | 0.190086E+11 | 61110.63 | 01-SEP-12:50 | 55101.08 | 0.62 |
October | 0.00 | 0.00 | 0.149796E+11 | 0.126009E+11 | 71416.43 | 22-OCT-12:30 | 58143.51 | 0.13 |
November | 0.00 | 0.00 | 0.487573E+09 | 0.487573E+09 | 29209.02 | 17-NOV-13:30 | 29209.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238315E+12 | 0.130882E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.517897E+11 | 0.219234E+11 | 71416.43 | 58143.51 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9196004.25 | 9196004.25 | 14777.07 | 18-JAN-19:05 | 14777.07 | 0.00 |
February | 0.00 | 0.00 | 22679887.36 | 22679887.36 | 16900.22 | 05-FEB-09:01 | 16900.22 | 0.00 |
March | 0.00 | 0.00 | 0.476852E+09 | 0.476615E+09 | 86004.49 | 28-MAR-18:01 | 86004.49 | 0.00 |
April | 0.00 | 0.00 | 0.653225E+10 | 0.581417E+10 | 91128.74 | 18-APR-18:01 | 91128.74 | 0.07 |
May | 0.00 | 0.00 | 0.306915E+11 | 0.223000E+11 | 95685.54 | 21-MAY-21:01 | 95685.54 | 0.41 |
June | 0.00 | 0.00 | 0.448608E+11 | 0.285715E+11 | 107884.26 | 25-JUN-08:51 | 72222.02 | 0.60 |
July | 0.00 | 0.00 | 0.522768E+11 | 0.315976E+11 | 108316.42 | 30-JUL-08:41 | 68568.24 | 0.63 |
August | 0.00 | 0.00 | 0.407763E+11 | 0.224871E+11 | 103057.49 | 28-AUG-21:51 | 71612.74 | 0.58 |
September | 0.00 | 0.00 | 0.217487E+11 | 0.107830E+11 | 98110.31 | 18-SEP-21:52 | 70986.15 | 0.59 |
October | 0.00 | 0.00 | 0.516329E+10 | 0.261352E+10 | 88277.42 | 20-OCT-18:11 | 88277.42 | 0.25 |
November | 0.00 | 0.00 | 0.542827E+09 | 0.255832E+09 | 75535.46 | 01-NOV-18:03 | 75535.46 | 0.03 |
December | 0.00 | 0.00 | 11468062.01 | 11468062.01 | 15977.69 | 06-DEC-19:05 | 15977.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.203113E+12 | 0.124943E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 9196004.25 | 9196004.25 | 14777.07 | 14777.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.522768E+11 | 0.315976E+11 | 108316.42 | 95685.54 | 0.63 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 74784752.43 | 74784752.43 | 17346.39 | 28-FEB-16:02 | 17346.39 | 0.00 |
March | 0.00 | 0.00 | 0.462003E+09 | 0.459057E+09 | 17817.26 | 26-MAR-15:01 | 17817.26 | 0.00 |
April | 0.00 | 0.00 | 0.239061E+10 | 0.221633E+10 | 17823.15 | 18-APR-18:01 | 17823.15 | 0.07 |
May | 0.00 | 0.00 | 0.595289E+10 | 0.403445E+10 | 17823.02 | 04-MAY-08:62 | 17823.02 | 0.56 |
June | 0.00 | 0.00 | 0.875394E+10 | 0.505060E+10 | 19218.63 | 10-JUN-15:02 | 12532.27 | 0.89 |
July | 0.00 | 0.00 | 0.109401E+11 | 0.606354E+10 | 18564.80 | 22-JUL-08:61 | 13714.43 | 0.96 |
August | 0.00 | 0.00 | 0.837838E+10 | 0.423171E+10 | 18444.47 | 09-AUG-08:61 | 13806.60 | 0.91 |
September | 0.00 | 0.00 | 0.400434E+10 | 0.211010E+10 | 18592.30 | 19-SEP-15:02 | 12676.34 | 0.62 |
October | 0.00 | 0.00 | 0.107146E+10 | 0.613732E+09 | 17817.75 | 09-OCT-08:61 | 17817.75 | 0.17 |
November | 0.00 | 0.00 | 87621025.13 | 83037832.00 | 16865.97 | 16-NOV-09:01 | 16865.97 | 0.00 |
December | 0.00 | 0.00 | 242542.30 | 242542.30 | 2829.66 | 28-DEC-09:04 | 2829.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.421164E+11 | 0.249376E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109401E+11 | 0.606354E+10 | 19218.63 | 17823.15 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2055066.38 | 1929909.81 | 2751.01 | 28-FEB-09:03 | 2751.01 | 0.00 |
March | 0.00 | 0.00 | 0.116163E+09 | 0.115158E+09 | 16392.23 | 26-MAR-08:61 | 16392.23 | 0.00 |
April | 0.00 | 0.00 | 0.123808E+10 | 0.112197E+10 | 16925.77 | 23-APR-08:61 | 16925.77 | 0.05 |
May | 0.00 | 0.00 | 0.421566E+10 | 0.275341E+10 | 17929.60 | 26-MAY-08:51 | 15621.05 | 0.46 |
June | 0.00 | 0.00 | 0.667115E+10 | 0.383888E+10 | 22043.92 | 28-JUN-07:52 | 19507.82 | 0.69 |
July | 0.00 | 0.00 | 0.803556E+10 | 0.440323E+10 | 22283.10 | 23-JUL-08:32 | 16329.23 | 0.70 |
August | 0.00 | 0.00 | 0.552503E+10 | 0.264065E+10 | 20004.74 | 30-AUG-08:51 | 14795.02 | 0.66 |
September | 0.00 | 0.00 | 0.219044E+10 | 0.106323E+10 | 18740.48 | 01-SEP-08:51 | 16210.64 | 0.47 |
October | 0.00 | 0.00 | 0.292503E+09 | 0.158616E+09 | 16524.66 | 09-OCT-08:61 | 16524.66 | 0.07 |
November | 0.00 | 0.00 | 5283711.72 | 3770838.43 | 2624.89 | 21-NOV-09:05 | 661.16 | 0.00 |
December | 0.00 | 0.00 | 8278.15 | 8278.15 | 96.58 | 05-DEC-19:06 | 96.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282919E+11 | 0.161009E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.803556E+10 | 0.440323E+10 | 22283.10 | 19507.82 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 322846.70 | 322846.70 | 857.81 | 27-JAN-16:01 | 857.81 | 0.00 |
February | 0.00 | 0.00 | 43464727.55 | 43464727.55 | 5084.98 | 04-FEB-16:01 | 5084.98 | 0.00 |
March | 0.00 | 0.00 | 0.172950E+09 | 0.172838E+09 | 5089.60 | 28-MAR-18:01 | 5089.60 | 0.00 |
April | 0.00 | 0.00 | 0.595091E+09 | 0.559504E+09 | 5088.65 | 16-APR-15:01 | 5088.65 | 0.05 |
May | 0.00 | 0.00 | 0.160519E+10 | 0.115520E+10 | 5089.70 | 04-MAY-15:01 | 5089.70 | 0.51 |
June | 0.00 | 0.00 | 0.206769E+10 | 0.120505E+10 | 5516.11 | 10-JUN-15:02 | 3429.18 | 0.81 |
July | 0.00 | 0.00 | 0.272013E+10 | 0.152422E+10 | 5555.06 | 05-JUL-08:61 | 3695.48 | 0.92 |
August | 0.00 | 0.00 | 0.212776E+10 | 0.113062E+10 | 5612.18 | 30-AUG-08:61 | 3579.47 | 0.86 |
September | 0.00 | 0.00 | 0.962754E+09 | 0.545342E+09 | 5370.78 | 19-SEP-15:02 | 3597.72 | 0.53 |
October | 0.00 | 0.00 | 0.283466E+09 | 0.177234E+09 | 5089.45 | 21-OCT-18:01 | 5089.45 | 0.15 |
November | 0.00 | 0.00 | 7928884.58 | 7408198.65 | 5083.99 | 17-NOV-16:01 | 5083.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105867E+11 | 0.652120E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.272013E+10 | 0.152422E+10 | 5612.18 | 5089.70 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 40935.41 | 40935.41 | 371.85 | 20-JAN-16:05 | 371.85 | 0.00 |
February | 0.00 | 0.00 | 4502679.62 | 4471694.50 | 3177.12 | 08-FEB-16:01 | 3177.12 | 0.00 |
March | 0.00 | 0.00 | 64068046.69 | 64068046.69 | 4830.74 | 28-MAR-18:01 | 4830.74 | 0.00 |
April | 0.00 | 0.00 | 0.301024E+09 | 0.277248E+09 | 5581.92 | 11-APR-18:11 | 5581.92 | 0.04 |
May | 0.00 | 0.00 | 0.110616E+10 | 0.750887E+09 | 6100.85 | 06-MAY-18:42 | 6100.85 | 0.41 |
June | 0.00 | 0.00 | 0.155927E+10 | 0.874058E+09 | 5885.73 | 25-JUN-08:51 | 3771.49 | 0.63 |
July | 0.00 | 0.00 | 0.204997E+10 | 0.112005E+10 | 5943.03 | 30-JUL-08:41 | 3585.24 | 0.69 |
August | 0.00 | 0.00 | 0.140084E+10 | 0.673818E+09 | 5468.34 | 27-AUG-21:51 | 4161.30 | 0.63 |
September | 0.00 | 0.00 | 0.447909E+09 | 0.200867E+09 | 5588.63 | 23-SEP-17:41 | 5588.63 | 0.37 |
October | 0.00 | 0.00 | 72247309.23 | 36560439.82 | 4691.02 | 21-OCT-18:32 | 4691.02 | 0.06 |
November | 0.00 | 0.00 | 725455.74 | 391882.42 | 1194.64 | 17-NOV-16:01 | 1194.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.700676E+10 | 0.400246E+10 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204997E+10 | 0.112005E+10 | 6100.85 | 6100.85 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.616129E+09 | 0.616129E+09 | 24930.66 | 27-JAN-16:01 | 24930.66 | 0.00 |
February | 0.00 | 0.00 | 0.168042E+10 | 0.167389E+10 | 24965.47 | 04-FEB-16:01 | 24965.47 | 0.00 |
March | 0.00 | 0.00 | 0.229258E+10 | 0.228495E+10 | 24979.28 | 26-MAR-18:01 | 24979.28 | 0.00 |
April | 0.00 | 0.00 | 0.424776E+10 | 0.396864E+10 | 24976.01 | 30-APR-15:01 | 24976.01 | 0.08 |
May | 0.00 | 0.00 | 0.791925E+10 | 0.531381E+10 | 24972.02 | 06-MAY-15:01 | 24972.02 | 0.56 |
June | 0.00 | 0.00 | 0.990540E+10 | 0.521282E+10 | 27730.17 | 19-JUN-18:01 | 17899.45 | 0.86 |
July | 0.00 | 0.00 | 0.131436E+11 | 0.684213E+10 | 28230.67 | 25-JUL-18:02 | 17501.42 | 0.92 |
August | 0.00 | 0.00 | 0.119607E+11 | 0.626644E+10 | 27618.41 | 30-AUG-08:61 | 17751.55 | 0.88 |
September | 0.00 | 0.00 | 0.736721E+10 | 0.443463E+10 | 26297.22 | 19-SEP-15:02 | 18452.25 | 0.69 |
October | 0.00 | 0.00 | 0.372890E+10 | 0.265214E+10 | 24972.31 | 21-OCT-18:01 | 24972.31 | 0.30 |
November | 0.00 | 0.00 | 0.110749E+10 | 0.108758E+10 | 24965.79 | 16-NOV-16:01 | 24965.79 | 0.01 |
December | 0.00 | 0.00 | 0.330551E+09 | 0.330127E+09 | 24928.02 | 02-DEC-16:01 | 24928.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.642999E+11 | 0.406833E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.330551E+09 | 0.330127E+09 | 24928.02 | 17501.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131436E+11 | 0.684213E+10 | 28230.67 | 24979.28 | 0.92 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 267081.16 | 680027.24 | 06-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 164410.41 | 659332.77 | 17-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 91089.72 | 616808.78 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29643.07 | 190655.07 | 07-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20348.95 | 145278.63 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10401.25 | 117775.40 | 16-JUN-22:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 7606.69 | 113948.19 | 02-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 7596.39 | 113430.82 | 19-AUG-00:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26908.70 | 151780.12 | 25-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32734.62 | 194992.75 | 31-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 63120.96 | 262625.67 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 237985.84 | 667419.12 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 79735.49 | ||||
Minimum of Months | 0.00 | 0.00 | 7596.39 | 113430.82 | ||
Maximum of Months | 0.00 | 0.00 | 267081.16 | 680027.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 426.44 | 22504.54 | 27-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1395.80 | 44926.58 | 28-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3384.61 | 106349.11 | 31-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 20773.18 | 383120.88 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80715.70 | 494630.41 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 166777.98 | 683414.89 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218178.68 | 664877.09 | 21-JUL-19:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 157882.42 | 598347.24 | 08-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56427.60 | 447118.27 | 01-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 15008.86 | 332587.28 | 19-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1796.90 | 149722.88 | 01-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 256.80 | 20529.56 | 06-DEC-19:05 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 60722.77 | 0.00 | ||||
Minimum of Months | 256.80 | 20529.56 | 0.00 | 0.00 | ||
Maximum of Months | 218178.68 | 683414.89 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 32705.08 | 67623.27 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 33428.28 | 68299.13 | 23-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 33322.33 | 68298.65 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32343.43 | 66902.34 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30789.89 | 64302.99 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 29068.47 | 60692.13 | 01-JUN-06:34 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27603.32 | 56974.48 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 26864.27 | 54782.04 | 01-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26985.60 | 55246.19 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27960.65 | 58122.79 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 29528.97 | 61661.85 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 31257.18 | 64991.92 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30135.26 | ||||
Minimum of Months | 0.00 | 0.00 | 26864.27 | 54782.04 | ||
Maximum of Months | 0.00 | 0.00 | 33428.28 | 68299.13 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.73 | 1299.30 | 14-JAN-16:50 | 0.92 |
February | 0.244774E+10 | 0.73 | 1299.30 | 15-FEB-06:02 | 0.92 |
March | 0.271000E+10 | 0.73 | 1299.30 | 07-MAR-03:50 | 0.92 |
April | 0.262258E+10 | 0.73 | 1299.30 | 13-APR-15:03 | 0.92 |
May | 0.271000E+10 | 0.72 | 1299.30 | 24-MAY-09:02 | 0.91 |
June | 0.262258E+10 | 0.72 | 1299.30 | 06-JUN-09:02 | 0.91 |
July | 0.271000E+10 | 0.72 | 1299.30 | 14-JUL-09:04 | 0.91 |
August | 0.271000E+10 | 0.72 | 1299.30 | 20-AUG-15:15 | 0.91 |
September | 0.262258E+10 | 0.72 | 1299.30 | 01-SEP-08:59 | 0.91 |
October | 0.271000E+10 | 0.72 | 1299.30 | 20-OCT-08:62 | 0.91 |
November | 0.262258E+10 | 0.73 | 1299.30 | 25-NOV-16:30 | 0.92 |
December | 0.271000E+10 | 0.73 | 1299.30 | 11-DEC-17:00 | 0.92 |
Annual Sum or Average | 0.319080E+11 | 0.72 | |||
Minimum of Months | 0.244774E+10 | 0.72 | 1299.30 | 0.91 | |
Maximum of Months | 0.271000E+10 | 0.73 | 1299.30 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292329E+11 | 0.75 | 16777.66 | 19-JAN-21:10 | 0.95 |
February | 0.275989E+11 | 0.77 | 17201.30 | 21-FEB-19:20 | 0.96 |
March | 0.318715E+11 | 0.79 | 17983.15 | 31-MAR-21:10 | 0.99 |
April | 0.325490E+11 | 0.81 | 22600.82 | 13-APR-21:10 | 1.13 |
May | 0.361467E+11 | 0.84 | 26706.28 | 18-MAY-21:10 | 1.25 |
June | 0.361616E+11 | 0.85 | 27896.45 | 30-JUN-21:10 | 1.27 |
July | 0.380353E+11 | 0.85 | 28026.07 | 24-JUL-21:10 | 1.28 |
August | 0.379208E+11 | 0.85 | 29217.77 | 25-AUG-21:10 | 1.31 |
September | 0.351753E+11 | 0.84 | 28570.68 | 01-SEP-21:10 | 1.29 |
October | 0.346187E+11 | 0.82 | 25715.48 | 19-OCT-21:10 | 1.22 |
November | 0.316639E+11 | 0.80 | 20310.63 | 01-NOV-21:10 | 1.06 |
December | 0.296496E+11 | 0.76 | 17359.23 | 06-DEC-21:10 | 0.97 |
Annual Sum or Average | 0.400624E+12 | 0.81 | |||
Minimum of Months | 0.275989E+11 | 0.75 | 16777.66 | 0.95 | |
Maximum of Months | 0.380353E+11 | 0.85 | 29217.77 | 1.31 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:03 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.28 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.885404E+09 | 0.55 | 939.59 | 01-JAN-09:02 | 0.60 |
February | 0.496007E+09 | 0.49 | 939.59 | 01-FEB-09:02 | 0.60 |
March | 0.378375E+09 | 0.47 | 939.59 | 01-MAR-09:01 | 0.60 |
April | 0.256973E+09 | 0.48 | 939.59 | 02-APR-08:61 | 0.60 |
May | 0.318970E+09 | 0.54 | 939.59 | 01-MAY-15:01 | 0.60 |
June | 0.372183E+09 | 0.54 | 939.59 | 01-JUN-15:01 | 0.60 |
July | 0.461637E+09 | 0.56 | 939.59 | 01-JUL-08:61 | 0.60 |
August | 0.371216E+09 | 0.54 | 939.59 | 01-AUG-15:01 | 0.60 |
September | 0.226889E+09 | 0.51 | 939.59 | 01-SEP-08:62 | 0.59 |
October | 0.231102E+09 | 0.46 | 939.59 | 01-OCT-15:01 | 0.60 |
November | 0.360390E+09 | 0.47 | 939.59 | 01-NOV-08:62 | 0.60 |
December | 0.812439E+09 | 0.56 | 939.59 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.517159E+10 | 0.51 | |||
Minimum of Months | 0.226889E+09 | 0.46 | 939.59 | 0.59 | |
Maximum of Months | 0.885404E+09 | 0.56 | 939.59 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104123E+10 | 0.58 | 895.16 | 01-JAN-09:02 | 0.60 |
February | 0.588769E+09 | 0.54 | 895.16 | 01-FEB-09:02 | 0.60 |
March | 0.416340E+09 | 0.50 | 895.16 | 01-MAR-09:01 | 0.60 |
April | 0.222736E+09 | 0.43 | 895.16 | 01-APR-18:02 | 0.60 |
May | 0.224783E+09 | 0.43 | 895.16 | 01-MAY-08:62 | 0.60 |
June | 0.265900E+09 | 0.41 | 895.16 | 01-JUN-08:51 | 0.60 |
July | 0.329891E+09 | 0.41 | 895.16 | 01-JUL-08:51 | 0.60 |
August | 0.234438E+09 | 0.40 | 895.16 | 01-AUG-08:51 | 0.59 |
September | 0.130419E+09 | 0.41 | 895.16 | 01-SEP-08:51 | 0.59 |
October | 0.213671E+09 | 0.43 | 895.16 | 01-OCT-15:01 | 0.60 |
November | 0.394636E+09 | 0.50 | 895.16 | 01-NOV-08:62 | 0.60 |
December | 0.948072E+09 | 0.59 | 895.16 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.501089E+10 | 0.47 | |||
Minimum of Months | 0.130419E+09 | 0.40 | 895.16 | 0.59 | |
Maximum of Months | 0.104123E+10 | 0.59 | 895.16 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.887646E+09 | 0.26 | 1602.41 | 09-JAN-05:00 | 0.61 |
February | 0.178610E+09 | 0.07 | 1268.01 | 17-FEB-06:00 | 0.61 |
March | 0.100585E+09 | 0.05 | 1186.25 | 29-MAR-12:30 | 0.60 |
April | 0.572594E+09 | 0.22 | 1593.91 | 13-APR-13:10 | 0.60 |
May | 0.123410E+10 | 0.48 | 1597.05 | 18-MAY-13:05 | 0.60 |
June | 0.138515E+10 | 0.53 | 1578.74 | 30-JUN-13:00 | 0.60 |
July | 0.172762E+10 | 0.58 | 1677.79 | 23-JUL-13:20 | 0.60 |
August | 0.162664E+10 | 0.57 | 1841.30 | 25-AUG-13:00 | 0.60 |
September | 0.118581E+10 | 0.45 | 1868.11 | 01-SEP-13:10 | 0.60 |
October | 0.552430E+09 | 0.18 | 3206.82 | 22-OCT-12:15 | 0.60 |
November | 85672617.25 | 0.04 | 983.81 | 17-NOV-13:30 | 0.60 |
December | 0.118450E+10 | 0.37 | 1602.41 | 24-DEC-06:00 | 0.61 |
Annual Sum or Average | 0.107214E+11 | 0.32 | |||
Minimum of Months | 85672617.25 | 0.04 | 983.81 | 0.60 | |
Maximum of Months | 0.172762E+10 | 0.58 | 3206.82 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495461E+10 | 0.51 | 4427.55 | 01-JAN-00:31 | 0.60 |
February | 0.279176E+10 | 0.46 | 4427.55 | 01-FEB-09:02 | 0.60 |
March | 0.180604E+10 | 0.43 | 4427.55 | 01-MAR-09:01 | 0.60 |
April | 0.803134E+09 | 0.41 | 4427.55 | 02-APR-15:01 | 0.60 |
May | 0.146022E+10 | 0.38 | 4427.55 | 01-MAY-08:62 | 0.60 |
June | 0.194581E+10 | 0.37 | 4427.55 | 01-JUN-08:51 | 0.60 |
July | 0.216030E+10 | 0.37 | 4427.55 | 01-JUL-08:51 | 0.60 |
August | 0.163138E+10 | 0.35 | 4427.55 | 01-AUG-08:51 | 0.59 |
September | 0.978274E+09 | 0.37 | 4427.55 | 01-SEP-08:51 | 0.59 |
October | 0.674798E+09 | 0.42 | 4427.55 | 01-OCT-08:61 | 0.60 |
November | 0.138780E+10 | 0.43 | 4427.55 | 01-NOV-18:03 | 0.60 |
December | 0.434991E+10 | 0.50 | 4427.55 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.249440E+11 | 0.42 | |||
Minimum of Months | 0.674798E+09 | 0.35 | 4427.55 | 0.59 | |
Maximum of Months | 0.495461E+10 | 0.51 | 4427.55 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.859668E+09 | 0.55 | 854.77 | 01-JAN-09:02 | 0.60 |
February | 0.469068E+09 | 0.48 | 854.77 | 01-FEB-09:02 | 0.60 |
March | 0.346567E+09 | 0.47 | 854.77 | 01-MAR-09:01 | 0.60 |
April | 0.243255E+09 | 0.49 | 854.77 | 02-APR-08:61 | 0.60 |
May | 0.294510E+09 | 0.55 | 854.77 | 01-MAY-08:62 | 0.60 |
June | 0.381423E+09 | 0.56 | 854.77 | 01-JUN-08:62 | 0.60 |
July | 0.448590E+09 | 0.57 | 854.77 | 01-JUL-08:61 | 0.60 |
August | 0.347586E+09 | 0.55 | 854.77 | 01-AUG-08:62 | 0.59 |
September | 0.218752E+09 | 0.51 | 854.77 | 01-SEP-08:62 | 0.60 |
October | 0.218926E+09 | 0.46 | 854.77 | 01-OCT-08:61 | 0.60 |
November | 0.342731E+09 | 0.47 | 854.77 | 02-NOV-08:62 | 0.60 |
December | 0.792819E+09 | 0.57 | 854.77 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.496390E+10 | 0.52 | |||
Minimum of Months | 0.218752E+09 | 0.46 | 854.77 | 0.59 | |
Maximum of Months | 0.859668E+09 | 0.57 | 854.77 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.983923E+09 | 0.58 | 811.44 | 01-JAN-07:00 | 0.60 |
February | 0.571269E+09 | 0.54 | 811.44 | 01-FEB-09:02 | 0.60 |
March | 0.389075E+09 | 0.49 | 811.44 | 01-MAR-09:01 | 0.60 |
April | 0.206561E+09 | 0.45 | 811.44 | 01-APR-18:02 | 0.60 |
May | 0.219119E+09 | 0.46 | 811.44 | 01-MAY-08:62 | 0.60 |
June | 0.292841E+09 | 0.44 | 811.44 | 01-JUN-08:51 | 0.60 |
July | 0.332371E+09 | 0.42 | 811.44 | 01-JUL-08:32 | 0.60 |
August | 0.231161E+09 | 0.41 | 811.44 | 01-AUG-08:51 | 0.59 |
September | 0.141922E+09 | 0.43 | 811.44 | 01-SEP-08:51 | 0.59 |
October | 0.204955E+09 | 0.43 | 811.44 | 01-OCT-08:61 | 0.60 |
November | 0.376829E+09 | 0.50 | 811.44 | 01-NOV-08:62 | 0.60 |
December | 0.900359E+09 | 0.58 | 811.44 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.485038E+10 | 0.48 | |||
Minimum of Months | 0.141922E+09 | 0.41 | 811.44 | 0.59 | |
Maximum of Months | 0.983923E+09 | 0.58 | 811.44 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269033E+09 | 0.57 | 244.42 | 01-JAN-09:02 | 0.60 |
February | 0.153696E+09 | 0.51 | 244.42 | 01-FEB-09:02 | 0.60 |
March | 0.115657E+09 | 0.49 | 244.42 | 01-MAR-09:01 | 0.60 |
April | 75437475.80 | 0.49 | 244.42 | 01-APR-18:02 | 0.60 |
May | 85908045.33 | 0.53 | 244.42 | 01-MAY-08:62 | 0.60 |
June | 97496454.15 | 0.54 | 244.42 | 01-JUN-15:01 | 0.60 |
July | 0.117702E+09 | 0.56 | 244.42 | 01-JUL-08:61 | 0.60 |
August | 93764321.95 | 0.54 | 244.42 | 01-AUG-15:01 | 0.60 |
September | 60001001.51 | 0.50 | 244.42 | 01-SEP-08:62 | 0.59 |
October | 70775570.84 | 0.47 | 244.42 | 01-OCT-15:01 | 0.60 |
November | 0.110777E+09 | 0.50 | 244.42 | 01-NOV-08:62 | 0.60 |
December | 0.252294E+09 | 0.58 | 244.42 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.150254E+10 | 0.52 | |||
Minimum of Months | 60001001.51 | 0.47 | 244.42 | 0.59 | |
Maximum of Months | 0.269033E+09 | 0.58 | 244.42 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.300213E+09 | 0.59 | 231.86 | 01-JAN-09:02 | 0.60 |
February | 0.185733E+09 | 0.56 | 231.86 | 01-FEB-09:02 | 0.60 |
March | 0.128720E+09 | 0.52 | 231.86 | 01-MAR-09:01 | 0.60 |
April | 66859610.90 | 0.45 | 231.86 | 01-APR-18:02 | 0.60 |
May | 61677333.71 | 0.44 | 231.86 | 01-MAY-08:62 | 0.60 |
June | 71126630.75 | 0.41 | 231.86 | 01-JUN-08:51 | 0.60 |
July | 87534638.72 | 0.41 | 231.86 | 01-JUL-08:51 | 0.60 |
August | 60175232.57 | 0.39 | 231.86 | 01-AUG-08:51 | 0.59 |
September | 35957371.22 | 0.41 | 231.86 | 01-SEP-08:51 | 0.59 |
October | 66756096.13 | 0.44 | 231.86 | 01-OCT-15:01 | 0.60 |
November | 0.121894E+09 | 0.53 | 231.86 | 01-NOV-08:62 | 0.60 |
December | 0.281963E+09 | 0.59 | 231.86 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.146861E+10 | 0.48 | |||
Minimum of Months | 35957371.22 | 0.39 | 231.86 | 0.59 | |
Maximum of Months | 0.300213E+09 | 0.59 | 231.86 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.904345E+09 | 0.52 | 1196.41 | 01-JAN-09:02 | 0.60 |
February | 0.555582E+09 | 0.50 | 1196.41 | 01-FEB-09:02 | 0.60 |
March | 0.459875E+09 | 0.50 | 1196.41 | 01-MAR-09:01 | 0.60 |
April | 0.346938E+09 | 0.51 | 1196.41 | 02-APR-08:61 | 0.60 |
May | 0.385138E+09 | 0.54 | 1196.41 | 01-MAY-15:01 | 0.60 |
June | 0.420548E+09 | 0.54 | 1196.41 | 01-JUN-15:01 | 0.60 |
July | 0.525539E+09 | 0.55 | 1196.41 | 01-JUL-08:61 | 0.60 |
August | 0.491013E+09 | 0.54 | 1196.41 | 01-AUG-15:01 | 0.60 |
September | 0.360463E+09 | 0.51 | 1196.41 | 01-SEP-08:62 | 0.59 |
October | 0.351059E+09 | 0.47 | 1196.41 | 01-OCT-08:61 | 0.60 |
November | 0.419906E+09 | 0.48 | 1196.41 | 02-NOV-15:01 | 0.60 |
December | 0.877655E+09 | 0.53 | 1196.41 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.609806E+10 | 0.52 | |||
Minimum of Months | 0.346938E+09 | 0.47 | 1196.41 | 0.59 | |
Maximum of Months | 0.904345E+09 | 0.55 | 1196.41 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.124456E+10 | 0.112010E+10 | 1951.39 | 09-JAN-05:00 | 1756.25 | 1756.25 | 35.03 | 6.51 |
February | 0.498179E+09 | 0.448362E+09 | 1885.23 | 17-FEB-06:00 | 1696.70 | 1696.70 | 35.44 | 6.42 |
March | 0.184905E+09 | 0.166414E+09 | 1658.12 | 05-MAR-05:20 | 1492.31 | 1492.31 | 35.97 | 6.10 |
April | 15679676.31 | 14111708.68 | 70.25 | 05-APR-06:10 | 63.22 | 63.22 | 36.82 | 1.55 |
May | 8138728.94 | 7324856.05 | 43.03 | 20-MAY-08:05 | 38.73 | 38.73 | 36.19 | 1.22 |
June | 3213857.01 | 2892471.31 | 26.83 | 16-JUN-22:40 | 24.15 | 24.15 | 30.64 | 0.96 |
July | 2600835.82 | 2340752.24 | 26.04 | 02-JUL-04:30 | 23.44 | 23.44 | 31.14 | 0.94 |
August | 2322200.89 | 2089980.80 | 33.77 | 19-AUG-06:20 | 30.39 | 30.39 | 41.62 | 1.08 |
September | 10909853.24 | 9818867.91 | 65.59 | 27-SEP-08:07 | 59.03 | 59.03 | 36.23 | 1.50 |
October | 18730759.52 | 16857683.56 | 81.00 | 31-OCT-08:03 | 72.90 | 72.90 | 31.97 | 1.66 |
November | 54123286.62 | 48710957.96 | 178.78 | 25-NOV-09:03 | 160.91 | 160.91 | 33.80 | 2.40 |
December | 0.105395E+10 | 0.948552E+09 | 1952.19 | 24-DEC-06:00 | 1756.97 | 1756.97 | 35.47 | 6.51 |
Annual Sum or Average | 0.309731E+10 | 0.278758E+10 | ||||||
Minimum of Months | 2322200.89 | 2089980.80 | 26.04 | 23.44 | 23.44 | 30.64 | 0.94 | |
Maximum of Months | 0.124456E+10 | 0.112010E+10 | 1952.19 | 1756.97 | 1756.97 | 41.62 | 6.51 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 18791241.07 | 16912116.96 | 502.09 | 27-JAN-16:01 | 451.88 | 451.88 | 6.72 | 1.00 |
February | 61679028.07 | 55511125.26 | 918.64 | 08-FEB-16:01 | 826.78 | 826.78 | 6.72 | 1.93 |
March | 0.202061E+09 | 0.181855E+09 | 2014.80 | 28-MAR-15:01 | 1813.32 | 1813.32 | 6.72 | 5.04 |
April | 0.101844E+10 | 0.916593E+09 | 3090.88 | 23-APR-18:01 | 2781.79 | 2781.79 | 6.72 | 10.81 |
May | 0.327350E+10 | 0.294615E+10 | 3291.02 | 10-MAY-18:01 | 2961.91 | 2961.91 | 6.72 | 13.10 |
June | 0.467164E+10 | 0.420447E+10 | 3497.18 | 29-JUN-18:02 | 3147.46 | 3147.46 | 6.72 | 16.93 |
July | 0.571624E+10 | 0.514462E+10 | 3481.21 | 21-JUL-19:20 | 3133.09 | 3133.09 | 6.72 | 16.58 |
August | 0.478236E+10 | 0.430412E+10 | 3377.15 | 08-AUG-18:02 | 3039.43 | 3039.43 | 6.72 | 14.48 |
September | 0.243710E+10 | 0.219339E+10 | 3177.30 | 01-SEP-15:13 | 2859.57 | 2859.57 | 6.72 | 11.68 |
October | 0.784207E+09 | 0.705786E+09 | 3196.41 | 19-OCT-15:01 | 2876.77 | 2876.77 | 6.72 | 11.89 |
November | 90251204.10 | 81226083.69 | 1998.41 | 01-NOV-15:02 | 1798.57 | 1798.57 | 6.72 | 4.98 |
December | 10754052.86 | 9678647.57 | 522.12 | 06-DEC-19:05 | 469.91 | 469.91 | 6.72 | 1.04 |
Annual Sum or Average | 0.230670E+11 | 0.207603E+11 | ||||||
Minimum of Months | 10754052.86 | 9678647.57 | 502.09 | 451.88 | 451.88 | 6.72 | 1.00 | |
Maximum of Months | 0.571624E+10 | 0.514462E+10 | 3497.18 | 3147.46 | 3147.46 | 6.72 | 16.93 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.552070E+09 | 0.496863E+09 | 3042.72 | 01-JAN-10:31 | 2738.44 | 2738.44 | 6.74 | 26.92 |
February | 0.143108E+10 | 0.128798E+10 | 3042.72 | 01-FEB-10:50 | 2738.44 | 2738.44 | 6.73 | 26.92 |
March | 0.211803E+10 | 0.190623E+10 | 3042.72 | 01-MAR-16:04 | 2738.44 | 2738.44 | 6.75 | 26.92 |
April | 0.462772E+10 | 0.416495E+10 | 3042.72 | 01-APR-08:62 | 2738.44 | 2738.44 | 6.98 | 26.92 |
May | 0.795591E+10 | 0.716032E+10 | 3042.72 | 01-MAY-05:03 | 2738.44 | 2738.44 | 6.73 | 26.92 |
June | 0.787942E+10 | 0.709147E+10 | 3042.72 | 01-JUN-00:05 | 2738.44 | 2738.44 | 6.81 | 26.92 |
July | 0.814961E+10 | 0.733465E+10 | 3042.72 | 01-JUL-00:10 | 2738.44 | 2738.44 | 7.49 | 26.92 |
August | 0.813829E+10 | 0.732446E+10 | 3042.72 | 01-AUG-00:05 | 2738.44 | 2738.44 | 7.63 | 26.92 |
September | 0.749253E+10 | 0.674328E+10 | 3042.72 | 01-SEP-00:05 | 2738.44 | 2738.44 | 8.79 | 26.92 |
October | 0.415305E+10 | 0.373775E+10 | 3042.72 | 01-OCT-00:10 | 2738.44 | 2738.44 | 6.82 | 26.92 |
November | 0.131178E+10 | 0.118061E+10 | 3042.72 | 01-NOV-05:03 | 2738.44 | 2738.44 | 6.73 | 26.92 |
December | 0.372588E+09 | 0.335329E+09 | 3042.72 | 01-DEC-09:50 | 2738.44 | 2738.44 | 6.73 | 26.92 |
Annual Sum or Average | 0.541821E+11 | 0.487639E+11 | ||||||
Minimum of Months | 0.372588E+09 | 0.335329E+09 | 3042.72 | 2738.44 | 2738.44 | 6.73 | 26.92 | |
Maximum of Months | 0.814961E+10 | 0.733465E+10 | 3042.72 | 2738.44 | 2738.44 | 8.79 | 26.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 45.91 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 46.55 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 46.57 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.35 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.37 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 50.95 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.37 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 51.32 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 51.91 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.84 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 50.60 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 47.68 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.91 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.91 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 36.01 | 60.00 | 267081.16 | 680027.24 | 06-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 36.75 | 60.00 | 164410.41 | 659332.77 | 17-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 43.09 | 60.00 | 91089.72 | 616808.78 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.29 | 60.00 | 29643.07 | 190655.07 | 07-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 49.89 | 60.00 | 20348.95 | 145278.63 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.18 | 60.00 | 10401.25 | 117775.40 | 16-JUN-22:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 35.32 | 35.32 | 7606.69 | 113948.19 | 02-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 31.27 | 31.27 | 7596.39 | 113430.82 | 19-AUG-00:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 33.18 | 33.18 | 26908.70 | 151780.12 | 25-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.04 | 60.00 | 32734.62 | 194992.75 | 31-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 47.66 | 60.00 | 63120.96 | 262625.67 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 38.40 | 60.00 | 237985.84 | 667419.12 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 79735.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.18 | 31.27 | 7596.39 | 113430.82 | ||
Maximum of Months | 0.00 | 0.00 | 52.29 | 60.00 | 267081.16 | 680027.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 426.44 | 22504.54 | 27-JAN-16:01 | 6.90 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1395.80 | 44926.58 | 28-FEB-16:02 | 7.10 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3384.61 | 106349.11 | 31-MAR-18:01 | 7.64 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 20773.18 | 383120.88 | 23-APR-18:03 | 10.10 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80715.70 | 494630.41 | 25-MAY-18:03 | 11.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 166777.98 | 683414.89 | 29-JUN-18:03 | 12.76 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218178.68 | 664877.09 | 21-JUL-19:20 | 12.60 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 157882.42 | 598347.24 | 08-AUG-15:03 | 12.01 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56427.60 | 447118.27 | 01-SEP-15:03 | 10.66 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 15008.86 | 332587.28 | 19-OCT-15:03 | 9.65 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1796.90 | 149722.88 | 01-NOV-15:02 | 8.03 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 256.80 | 20529.56 | 06-DEC-19:05 | 6.88 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 60722.77 | 0.00 | ||||||
Minimum of Months | 256.80 | 20529.56 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 218178.68 | 683414.89 | 12.76 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 45.91 | 59.76 | 32705.08 | 67623.27 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.55 | 58.86 | 33428.28 | 68299.13 | 23-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 46.57 | 59.45 | 33322.33 | 68298.65 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.35 | 59.45 | 32343.43 | 66902.34 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.37 | 59.36 | 30789.89 | 64302.99 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.95 | 59.59 | 29068.47 | 60692.13 | 01-JUN-06:34 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.37 | 58.86 | 27603.32 | 56974.48 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 51.32 | 58.79 | 26864.27 | 54782.04 | 01-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.91 | 59.79 | 26985.60 | 55246.19 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.84 | 59.05 | 27960.65 | 58122.79 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 50.60 | 58.26 | 29528.97 | 61661.85 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 47.68 | 58.77 | 31257.18 | 64991.92 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30135.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.91 | 58.26 | 26864.27 | 54782.04 | ||
Maximum of Months | 0.00 | 0.00 | 51.91 | 59.79 | 33428.28 | 68299.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.546121E+12 | 0.00 | 0.00 | 0.292329E+11 | 0.00 | 0.00 |
February | 0.298727E+12 | 0.00 | 0.00 | 0.275989E+11 | 0.00 | 0.00 |
March | 0.179093E+12 | 0.00 | 0.00 | 0.318715E+11 | 0.00 | 0.00 |
April | 0.601165E+11 | 0.00 | 0.134043E+11 | 0.325490E+11 | 0.00 | 0.00 |
May | 0.533561E+11 | 0.00 | 0.103904E+12 | 0.361467E+11 | 0.00 | 0.00 |
June | 0.267987E+11 | 0.00 | 0.274519E+12 | 0.361616E+11 | 0.00 | 0.00 |
July | 0.203609E+11 | 0.00 | 0.384403E+12 | 0.380353E+11 | 0.00 | 0.00 |
August | 0.201394E+11 | 0.00 | 0.260060E+12 | 0.379208E+11 | 0.00 | 0.00 |
September | 0.680561E+11 | 0.00 | 0.582176E+11 | 0.351753E+11 | 0.00 | 0.00 |
October | 0.710571E+11 | 0.00 | 0.814646E+10 | 0.346187E+11 | 0.00 | 0.00 |
November | 0.108137E+12 | 0.00 | 0.104414E+10 | 0.316639E+11 | 0.00 | 0.00 |
December | 0.476502E+12 | 0.00 | 0.00 | 0.296496E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.192846E+13 | 0.00 | 0.110370E+13 | 0.400624E+12 | 0.00 | 0.00 |
Minimum of Months | 0.201394E+11 | 0.00 | 0.00 | 0.275989E+11 | 0.00 | 0.00 |
Maximum of Months | 0.546121E+12 | 0.00 | 0.384403E+12 | 0.380353E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.272832E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.146826E+11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.765465E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.828534E+09 | 0.00 | 0.823506E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 17177758.31 | 0.00 | 0.698869E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 21534.43 | 0.00 | 0.194790E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 21829.09 | 0.00 | 0.282154E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 22684.57 | 0.00 | 0.191980E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 5915.76 | 0.00 | 0.390866E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.255729E+09 | 0.00 | 0.525162E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.316836E+10 | 0.00 | 78057595.70 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.233409E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.772313E+11 | 0.00 | 0.792165E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 5915.76 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.272832E+11 | 0.00 | 0.282154E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.292329E+11 | 0.00 | 0.546121E+12 | 0.736884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275989E+11 | 0.00 | 0.298727E+12 | 0.726991E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318715E+11 | 0.00 | 0.179093E+12 | 0.776060E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325490E+11 | 0.134043E+11 | 0.601165E+11 | 0.457917E+12 | 92381602.93 | 0.00 | 0.00 | 0.00 |
May | 0.361467E+11 | 0.103904E+12 | 0.533561E+11 | 0.110437E+12 | 0.255788E+10 | 0.00 | 0.00 | 0.00 |
June | 0.361616E+11 | 0.274519E+12 | 0.267987E+11 | 0.200658E+11 | 0.392729E+11 | 0.00 | 0.00 | 0.00 |
July | 0.380353E+11 | 0.384403E+12 | 0.203609E+11 | 0.124350E+10 | 0.517467E+11 | 0.00 | 0.00 | 0.00 |
August | 0.379208E+11 | 0.260060E+12 | 0.201394E+11 | 0.612591E+10 | 0.183905E+11 | 0.00 | 0.00 | 0.00 |
September | 0.351753E+11 | 0.582176E+11 | 0.680561E+11 | 0.897761E+11 | 0.116295E+09 | 0.00 | 0.00 | 0.00 |
October | 0.346187E+11 | 0.814646E+10 | 0.710571E+11 | 0.397097E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316639E+11 | 0.104414E+10 | 0.108137E+12 | 0.671808E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296496E+11 | 0.00 | 0.476502E+12 | 0.752386E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400624E+12 | 0.110370E+13 | 0.192846E+13 | 0.474679E+13 | 0.112177E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275989E+11 | 0.00 | 0.201394E+11 | 0.124350E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.380353E+11 | 0.384403E+12 | 0.546121E+12 | 0.776060E+12 | 0.517467E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.272832E+11 | 0.608720E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.146826E+11 | 0.607093E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.765465E+10 | 0.645626E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.823506E+09 | 0.828534E+09 | 0.412023E+11 | 54448815.47 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.698869E+10 | 17177758.31 | 0.150880E+11 | 0.636630E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.194790E+11 | 21534.43 | 0.450084E+10 | 0.450268E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.282154E+11 | 21829.09 | 0.200134E+10 | 0.594087E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.191980E+11 | 22684.57 | 0.237966E+10 | 0.236080E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.390866E+10 | 5915.76 | 0.142436E+11 | 78542631.63 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.525162E+09 | 0.255729E+09 | 0.373338E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 78057595.70 | 0.316836E+10 | 0.561666E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.233409E+11 | 0.618850E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.792165E+11 | 0.772313E+11 | 0.420945E+12 | 0.135740E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 5915.76 | 0.200134E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.282154E+11 | 0.272832E+11 | 0.645626E+11 | 0.594087E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.292329E+11 | 0.546121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275989E+11 | 0.298727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318715E+11 | 0.179093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325490E+11 | 0.601165E+11 | 0.134043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361467E+11 | 0.533561E+11 | 0.103904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.361616E+11 | 0.267987E+11 | 0.274519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.380353E+11 | 0.203609E+11 | 0.384403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379208E+11 | 0.201394E+11 | 0.260060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351753E+11 | 0.680561E+11 | 0.582176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346187E+11 | 0.710571E+11 | 0.814646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316639E+11 | 0.108137E+12 | 0.104414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296496E+11 | 0.476502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400624E+12 | 0.192846E+13 | 0.110370E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275989E+11 | 0.201394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.380353E+11 | 0.546121E+12 | 0.384403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.272832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.146826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.765465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.828534E+09 | 0.823506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 17177758.31 | 0.698869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 21534.43 | 0.194790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 21829.09 | 0.282154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 22684.57 | 0.191980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 5915.76 | 0.390866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.255729E+09 | 0.525162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.316836E+10 | 78057595.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.233409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.772313E+11 | 0.792165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 5915.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.272832E+11 | 0.282154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.564628E+11 | 0.00 | 0.00 | 1150296.74 | 0.00 | 0.352672E+11 | 0.269466E+10 | 0.00 | 0.96 |
February | 0.599179E+11 | 0.00 | 0.00 | 387670.61 | 0.00 | 0.382128E+10 | 0.202342E+10 | 0.00 | 0.97 |
March | 0.577454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300234E+09 | 0.00 | 0.00 | 0.97 |
April | 0.464015E+11 | 0.00 | 0.00 | 0.00 | 103884.10 | 0.00 | 0.00 | 0.00 | 0.97 |
May | 0.418979E+11 | 0.00 | 0.00 | 0.00 | 0.114096E+09 | 0.00 | 0.00 | 0.00 | 0.97 |
June | 0.267571E+11 | 0.113873E+09 | 0.00 | 117501.00 | 0.378373E+10 | 0.00 | 0.850369E+09 | 0.00 | 0.98 |
July | 0.121509E+11 | 0.148209E+10 | 0.00 | 9628219.39 | 0.496367E+10 | 0.00 | 0.101743E+11 | 0.00 | 0.99 |
August | 0.307907E+10 | 0.115510E+10 | 0.00 | 41921978.10 | 0.139872E+10 | 0.00 | 0.271960E+11 | 0.00 | 1.03 |
September | 0.213799E+10 | 607811.59 | 0.00 | 60894086.60 | 15237803.77 | 0.00 | 0.485399E+11 | 0.00 | 1.07 |
October | 0.172354E+10 | 0.00 | 0.00 | 63305708.00 | 0.00 | 0.00 | 0.533645E+11 | 0.00 | 1.08 |
November | 0.267961E+10 | 0.00 | 0.00 | 56558999.13 | 0.00 | 0.00 | 0.510547E+11 | 0.00 | 1.06 |
December | 0.617023E+11 | 0.00 | 0.00 | 6998554.92 | 0.00 | 0.139276E+11 | 0.116743E+11 | 0.00 | 0.97 |
Annual Sum or Average | 0.372656E+12 | 0.275167E+10 | 0.00 | 0.240963E+09 | 0.102756E+11 | 0.533164E+11 | 0.207572E+12 | 0.00 | 1.00 |
Minimum of Months | 0.172354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
Maximum of Months | 0.617023E+11 | 0.148209E+10 | 0.00 | 63305708.00 | 0.496367E+10 | 0.352672E+11 | 0.533645E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133521E+10 | 0.00 | 0.00 | 36911.86 | 0.00 | 0.151308E+11 | 0.107612E+09 | 0.00 | 3.06 |
February | 0.307903E+10 | 0.00 | 0.00 | 584137.94 | 0.00 | 0.799233E+10 | 0.537475E+09 | 0.00 | 3.09 |
March | 0.492637E+10 | 0.00 | 0.00 | 815941.81 | 0.00 | 0.467872E+10 | 0.649278E+09 | 0.00 | 3.09 |
April | 0.641765E+10 | 18260.56 | 0.00 | 1489381.27 | 0.00 | 0.923785E+09 | 0.909246E+09 | 0.00 | 3.14 |
May | 0.683745E+10 | 19060573.84 | 0.00 | 1509455.03 | 3193062.09 | 0.00 | 0.544166E+09 | 0.00 | 3.14 |
June | 0.459215E+10 | 0.440195E+09 | 0.00 | 821837.68 | 0.293887E+09 | 0.00 | 0.252252E+09 | 0.00 | 3.14 |
July | 0.360308E+10 | 0.705989E+09 | 0.00 | 908529.72 | 0.488924E+09 | 0.00 | 0.308400E+09 | 0.00 | 3.20 |
August | 0.464826E+10 | 0.299396E+09 | 0.00 | 1811773.63 | 0.166070E+09 | 0.00 | 0.457665E+09 | 0.00 | 3.23 |
September | 0.723957E+10 | 3720280.76 | 0.00 | 2532222.96 | 20637.50 | 0.00 | 0.984094E+09 | 0.00 | 3.22 |
October | 0.747393E+10 | 0.00 | 0.00 | 1842302.07 | 0.00 | 0.558304E+09 | 0.891093E+09 | 0.00 | 3.18 |
November | 0.445690E+10 | 0.00 | 0.00 | 425108.99 | 0.00 | 0.383419E+10 | 0.407452E+09 | 0.00 | 3.09 |
December | 0.127309E+10 | 0.00 | 0.00 | 1202.94 | 0.00 | 0.139417E+11 | 23476351.60 | 0.00 | 3.04 |
Annual Sum or Average | 0.558827E+11 | 0.146838E+10 | 0.00 | 12778805.90 | 0.952095E+09 | 0.470598E+11 | 0.607221E+10 | 0.00 | 3.14 |
Minimum of Months | 0.127309E+10 | 0.00 | 0.00 | 1202.94 | 0.00 | 0.00 | 23476351.60 | 0.00 | 3.04 |
Maximum of Months | 0.747393E+10 | 0.705989E+09 | 0.00 | 2532222.96 | 0.488924E+09 | 0.151308E+11 | 0.984094E+09 | 0.00 | 3.23 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.423960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444171E+10 | 0.00 | 0.00 | 1.39 |
February | 0.461720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143402E+10 | 0.00 | 0.00 | 1.39 |
March | 0.498874E+10 | 0.00 | 0.00 | 5098.95 | 0.00 | 0.311515E+09 | 35485762.59 | 0.00 | 1.39 |
April | 0.380336E+10 | 0.00 | 0.00 | 315818.41 | 9544.34 | 0.00 | 0.462273E+09 | 0.00 | 1.40 |
May | 0.246721E+10 | 4924133.52 | 0.00 | 1629935.58 | 5701935.60 | 0.00 | 0.143003E+10 | 0.00 | 1.43 |
June | 0.138926E+10 | 0.244280E+09 | 0.00 | 1625857.19 | 0.136968E+09 | 0.00 | 0.118939E+10 | 0.00 | 1.45 |
July | 0.571667E+09 | 0.432697E+09 | 0.00 | 2322115.43 | 0.196799E+09 | 0.00 | 0.154268E+10 | 0.00 | 1.48 |
August | 0.910418E+09 | 0.123302E+09 | 0.00 | 2401850.43 | 0.110273E+09 | 0.00 | 0.181873E+10 | 0.00 | 1.46 |
September | 0.277858E+10 | 99403.00 | 0.00 | 1207226.12 | 1356890.85 | 0.00 | 0.148963E+10 | 0.00 | 1.42 |
October | 0.404939E+10 | 0.00 | 0.00 | 287919.11 | 0.00 | 0.00 | 0.522210E+09 | 0.00 | 1.40 |
November | 0.452875E+10 | 0.00 | 0.00 | 689.66 | 0.00 | 0.00 | 9713416.98 | 0.00 | 1.40 |
December | 0.444087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354284E+10 | 0.00 | 0.00 | 1.38 |
Annual Sum or Average | 0.387850E+11 | 0.805302E+09 | 0.00 | 9796510.88 | 0.451108E+09 | 0.973009E+10 | 0.850014E+10 | 0.00 | 1.42 |
Minimum of Months | 0.571667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
Maximum of Months | 0.498874E+10 | 0.432697E+09 | 0.00 | 2401850.43 | 0.196799E+09 | 0.444171E+10 | 0.181873E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649258E+10 | 0.00 | 0.00 | 0.51 |
February | 0.955699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373967E+10 | 0.00 | 0.00 | 0.51 |
March | 0.208383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205532E+10 | 0.00 | 0.00 | 0.51 |
April | 0.327627E+10 | 0.00 | 0.00 | 0.00 | 7401.89 | 29905753.43 | 0.00 | 0.00 | 0.51 |
May | 0.293794E+10 | 244645.63 | 0.00 | 85731.71 | 7884873.44 | 0.00 | 47720760.43 | 0.00 | 0.51 |
June | 0.191373E+10 | 0.142621E+09 | 0.00 | 150433.26 | 0.148087E+09 | 0.00 | 57316097.83 | 0.00 | 0.52 |
July | 0.128984E+10 | 0.175559E+09 | 0.00 | 507900.09 | 0.296179E+09 | 0.00 | 0.300351E+09 | 0.00 | 0.52 |
August | 0.193132E+10 | 25443702.76 | 0.00 | 224708.58 | 0.149333E+09 | 0.00 | 0.132070E+09 | 0.00 | 0.52 |
September | 0.325022E+10 | 0.00 | 0.00 | 36652.65 | 1129022.71 | 0.00 | 26601097.44 | 0.00 | 0.52 |
October | 0.353911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.267504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844668E+09 | 0.00 | 0.00 | 0.51 |
December | 0.423303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577373E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.245247E+11 | 0.343868E+09 | 0.00 | 1005426.29 | 0.602621E+09 | 0.189359E+11 | 0.564059E+09 | 0.00 | 0.51 |
Minimum of Months | 0.248441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.353911E+10 | 0.175559E+09 | 0.00 | 507900.09 | 0.296179E+09 | 0.649258E+10 | 0.300351E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10462543.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398569E+10 | 0.00 | 0.00 | 0.52 |
February | 0.226781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255556E+10 | 0.00 | 0.00 | 0.52 |
March | 0.718062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173381E+10 | 0.00 | 0.00 | 0.52 |
April | 0.178557E+10 | 0.00 | 0.00 | 0.00 | 4384.36 | 0.172779E+09 | 0.00 | 0.00 | 0.52 |
May | 0.176827E+10 | 0.00 | 0.00 | 0.00 | 4815355.38 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.115712E+10 | 58169207.01 | 0.00 | 33083.20 | 0.107836E+09 | 0.00 | 8536649.21 | 0.00 | 0.53 |
July | 0.926409E+09 | 35182745.98 | 0.00 | 16076.13 | 0.236178E+09 | 0.00 | 12496054.22 | 0.00 | 0.53 |
August | 0.122183E+10 | 1096083.86 | 0.00 | 7.07 | 0.101663E+09 | 0.00 | 3336.97 | 0.00 | 0.53 |
September | 0.194046E+10 | 0.00 | 0.00 | 0.00 | 668753.65 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.205135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44969214.56 | 0.00 | 0.00 | 0.52 |
November | 0.110210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982728E+09 | 0.00 | 0.00 | 0.52 |
December | 21336910.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365082E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.129297E+11 | 94448036.84 | 0.00 | 49166.40 | 0.451166E+09 | 0.131264E+11 | 21036040.40 | 0.00 | 0.53 |
Minimum of Months | 10462543.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.205135E+10 | 58169207.01 | 0.00 | 33083.20 | 0.236178E+09 | 0.398569E+10 | 12496054.22 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.947816E+10 | 0.00 | 0.00 | 71988872.45 | 0.00 | 0.373082E+11 | 0.875596E+11 | 0.00 | 22.07 |
February | 0.533017E+10 | 0.00 | 0.00 | 76539319.80 | 0.00 | 0.122727E+11 | 0.806362E+11 | 0.00 | 22.93 |
March | 0.257138E+10 | 0.00 | 0.00 | 94178768.49 | 0.00 | 0.386905E+10 | 0.831152E+11 | 0.00 | 23.45 |
April | 0.156446E+09 | 136185.17 | 0.00 | 98437327.59 | 0.00 | 0.00 | 0.725040E+11 | 0.00 | 23.63 |
May | 44521703.41 | 0.160808E+09 | 0.00 | 0.120443E+09 | 0.00 | 0.00 | 0.659483E+11 | 0.00 | 23.84 |
June | 26742086.07 | 0.620862E+10 | 0.00 | 99681409.80 | 6669061.46 | 0.00 | 0.426194E+11 | 0.00 | 23.83 |
July | 29158557.30 | 0.102925E+11 | 0.00 | 87329608.59 | 17954315.27 | 0.00 | 0.336921E+11 | 0.00 | 23.85 |
August | 17938090.65 | 0.393563E+10 | 0.00 | 0.102504E+09 | 5061447.94 | 0.00 | 0.445282E+11 | 0.00 | 23.95 |
September | 36112891.83 | 21045459.26 | 0.00 | 0.107303E+09 | 0.00 | 0.00 | 0.727977E+11 | 0.00 | 23.90 |
October | 0.163902E+09 | 0.00 | 0.00 | 96501426.79 | 0.00 | 0.00 | 0.776389E+11 | 0.00 | 23.67 |
November | 0.306314E+09 | 0.00 | 0.00 | 92854710.13 | 0.00 | 0.00 | 0.765804E+11 | 0.00 | 23.62 |
December | 0.116471E+11 | 0.00 | 0.00 | 74206703.84 | 0.00 | 0.253964E+11 | 0.883815E+11 | 0.00 | 22.32 |
Annual Sum or Average | 0.298079E+11 | 0.206188E+11 | 0.00 | 0.112197E+10 | 29684824.67 | 0.788464E+11 | 0.826002E+12 | 0.00 | 23.42 |
Minimum of Months | 17938090.65 | 0.00 | 0.00 | 71988872.45 | 0.00 | 0.00 | 0.336921E+11 | 0.00 | 22.07 |
Maximum of Months | 0.116471E+11 | 0.102925E+11 | 0.00 | 0.120443E+09 | 17954315.27 | 0.373082E+11 | 0.883815E+11 | 0.00 | 23.95 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329773E+11 | 0.00 | 0.00 | 409864.49 | 0.00 | 0.320528E+11 | 0.110083E+10 | 0.00 | 4.34 |
February | 0.302102E+11 | 0.00 | 0.00 | 3894808.85 | 0.00 | 0.108356E+11 | 0.531959E+10 | 0.00 | 4.39 |
March | 0.295650E+11 | 0.00 | 0.00 | 5717049.76 | 0.00 | 0.263297E+10 | 0.878104E+10 | 0.00 | 4.40 |
April | 0.179540E+11 | 72867.08 | 0.00 | 12173704.50 | 0.00 | 0.00 | 0.149505E+11 | 0.00 | 4.46 |
May | 0.999977E+10 | 77450238.38 | 0.00 | 20397946.59 | 8059292.22 | 0.00 | 0.195053E+11 | 0.00 | 4.47 |
June | 0.562675E+10 | 0.240372E+10 | 0.00 | 17662497.12 | 0.473192E+09 | 0.00 | 0.137368E+11 | 0.00 | 4.48 |
July | 0.270195E+10 | 0.407350E+10 | 0.00 | 19880191.02 | 0.627821E+09 | 0.00 | 0.129443E+11 | 0.00 | 4.54 |
August | 0.445473E+10 | 0.156347E+10 | 0.00 | 25902762.25 | 0.256393E+09 | 0.00 | 0.159628E+11 | 0.00 | 4.57 |
September | 0.108566E+11 | 13404351.37 | 0.00 | 22536016.92 | 0.00 | 0.00 | 0.219202E+11 | 0.00 | 4.57 |
October | 0.208029E+11 | 0.00 | 0.00 | 12952206.78 | 0.00 | 0.00 | 0.147137E+11 | 0.00 | 4.51 |
November | 0.297004E+11 | 0.00 | 0.00 | 2922771.43 | 0.00 | 0.139020E+09 | 0.489048E+10 | 0.00 | 4.40 |
December | 0.339570E+11 | 0.00 | 0.00 | 124455.28 | 0.00 | 0.265126E+11 | 0.340482E+09 | 0.00 | 4.32 |
Annual Sum or Average | 0.228807E+12 | 0.813161E+10 | 0.00 | 0.144574E+09 | 0.136546E+10 | 0.721730E+11 | 0.134166E+12 | 0.00 | 4.45 |
Minimum of Months | 0.270195E+10 | 0.00 | 0.00 | 124455.28 | 0.00 | 0.00 | 0.340482E+09 | 0.00 | 4.32 |
Maximum of Months | 0.339570E+11 | 0.407350E+10 | 0.00 | 25902762.25 | 0.627821E+09 | 0.320528E+11 | 0.219202E+11 | 0.00 | 4.57 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851200E+11 | 0.00 | 0.00 | 1.84 |
February | 0.107568E+12 | 0.00 | 0.00 | 620877.26 | 0.00 | 0.250681E+11 | 0.252280E+10 | 0.00 | 1.84 |
March | 0.105281E+12 | 0.00 | 0.00 | 2994177.50 | 0.00 | 0.520477E+10 | 0.870593E+10 | 0.00 | 1.85 |
April | 0.638290E+11 | 210625.39 | 0.00 | 20062419.92 | 2614.20 | 0.00 | 0.316954E+11 | 0.00 | 1.86 |
May | 0.321690E+11 | 0.143278E+09 | 0.00 | 62506934.86 | 92202687.47 | 0.00 | 0.556680E+11 | 0.00 | 1.91 |
June | 0.150190E+11 | 0.644604E+10 | 0.00 | 64096520.12 | 0.201625E+10 | 0.00 | 0.434387E+11 | 0.00 | 1.95 |
July | 0.667244E+10 | 0.111039E+11 | 0.00 | 73234982.48 | 0.275968E+10 | 0.00 | 0.419055E+11 | 0.00 | 1.99 |
August | 0.112703E+11 | 0.384268E+10 | 0.00 | 84380929.56 | 0.134291E+10 | 0.00 | 0.512961E+11 | 0.00 | 1.97 |
September | 0.303542E+11 | 23202206.16 | 0.00 | 65623051.82 | 9324792.15 | 0.00 | 0.659094E+11 | 0.00 | 1.91 |
October | 0.631604E+11 | 0.00 | 0.00 | 28542516.66 | 0.00 | 0.00 | 0.393989E+11 | 0.00 | 1.87 |
November | 0.930886E+11 | 0.00 | 0.00 | 2199062.41 | 0.00 | 0.00 | 0.830769E+10 | 0.00 | 1.86 |
December | 0.109749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685478E+11 | 0.00 | 0.00 | 1.83 |
Annual Sum or Average | 0.746941E+12 | 0.215593E+11 | 0.00 | 0.404261E+09 | 0.622037E+10 | 0.183941E+12 | 0.348849E+12 | 0.00 | 1.89 |
Minimum of Months | 0.667244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
Maximum of Months | 0.109749E+12 | 0.111039E+11 | 0.00 | 84380929.56 | 0.275968E+10 | 0.851200E+11 | 0.659094E+11 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27418242.49 | 0.00 | 0.00 | 22578.64 | 0.00 | 0.334971E+10 | 2126540.99 | 0.00 | 0.35 |
February | 54095317.87 | 0.00 | 0.00 | 639699.95 | 0.00 | 0.210998E+10 | 39761499.80 | 0.00 | 0.35 |
March | 62686401.11 | 0.00 | 0.00 | 2214923.21 | 0.00 | 0.158711E+10 | 0.158234E+09 | 0.00 | 0.35 |
April | 47042542.88 | 1087565.70 | 0.00 | 6526303.53 | 0.00 | 0.764882E+09 | 0.526150E+09 | 0.00 | 0.35 |
May | 15216071.17 | 16043060.90 | 3592.82 | 14938911.37 | 0.00 | 0.102791E+09 | 0.100322E+10 | 998.21 | 0.36 |
June | 10483755.18 | 0.206803E+09 | 176687.27 | 13221240.69 | 242534.35 | 15656809.00 | 0.609880E+09 | 15172.09 | 0.36 |
July | 2741954.51 | 0.368215E+09 | 342533.93 | 11144064.13 | 0.00 | 533082.43 | 0.379429E+09 | 18978.62 | 0.36 |
August | 6627811.80 | 0.153918E+09 | 133635.77 | 12058537.01 | 0.00 | 16625712.16 | 0.515906E+09 | 11939.85 | 0.36 |
September | 23563335.86 | 9684751.87 | 4176.46 | 11212438.85 | 0.00 | 0.205550E+09 | 0.877341E+09 | 2455.20 | 0.36 |
October | 51296360.60 | 0.00 | 0.00 | 3598605.97 | 0.00 | 0.901430E+09 | 0.413821E+09 | 0.00 | 0.35 |
November | 50343376.64 | 0.00 | 0.00 | 274212.12 | 0.00 | 0.136817E+10 | 30269439.57 | 0.00 | 0.36 |
December | 18700891.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300431E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.370216E+09 | 0.755752E+09 | 660626.24 | 75851515.48 | 242534.35 | 0.134267E+11 | 0.455614E+10 | 49543.98 | 0.35 |
Minimum of Months | 2741954.51 | 0.00 | 0.00 | 0.00 | 0.00 | 533082.43 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 62686401.11 | 0.368215E+09 | 342533.93 | 14938911.37 | 242534.35 | 0.334971E+10 | 0.100322E+10 | 18978.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3119.32 | 0.00 | 0.337875E+10 | 130318.11 | 0.00 | 0.35 |
February | 14119432.75 | 0.00 | 0.00 | 175653.15 | 0.00 | 0.217060E+10 | 19322666.49 | 0.00 | 0.35 |
March | 30378763.61 | 0.00 | 0.00 | 1034111.81 | 0.00 | 0.167974E+10 | 98886667.92 | 0.00 | 0.35 |
April | 99162784.98 | 1043057.27 | 0.00 | 3908344.37 | 44381.01 | 0.867200E+09 | 0.374172E+09 | 0.00 | 0.35 |
May | 0.162495E+09 | 15500811.75 | 15483.47 | 10429077.66 | 523613.41 | 0.109760E+09 | 0.853352E+09 | 5863.07 | 0.36 |
June | 0.142640E+09 | 0.175530E+09 | 269874.94 | 9038903.52 | 31390118.57 | 13555618.02 | 0.483931E+09 | 23822.73 | 0.36 |
July | 0.106824E+09 | 0.290754E+09 | 411770.07 | 7534177.15 | 77351745.77 | 415377.92 | 0.279029E+09 | 16278.08 | 0.36 |
August | 0.136826E+09 | 0.120362E+09 | 175933.01 | 8269032.77 | 33483263.41 | 16631105.42 | 0.389428E+09 | 25047.18 | 0.36 |
September | 0.146839E+09 | 8370114.55 | 5925.53 | 6665300.04 | 1306829.26 | 0.224601E+09 | 0.739431E+09 | 7378.71 | 0.36 |
October | 84841729.84 | 0.00 | 0.00 | 1594883.81 | 0.00 | 0.103498E+10 | 0.248574E+09 | 0.00 | 0.35 |
November | 37669631.31 | 0.00 | 0.00 | 55592.28 | 0.00 | 0.140448E+10 | 6676448.23 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 241.08 | 0.00 | 0.302253E+10 | 123225.82 | 0.00 | 0.35 |
Annual Sum or Average | 0.961796E+09 | 0.611559E+09 | 878987.01 | 48708436.98 | 0.144100E+09 | 0.139232E+11 | 0.349306E+10 | 78389.77 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 241.08 | 0.00 | 415377.92 | 123225.82 | 0.00 | 0.35 |
Maximum of Months | 0.162495E+09 | 0.290754E+09 | 411770.07 | 10429077.66 | 77351745.77 | 0.337875E+10 | 0.853352E+09 | 25047.18 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206281E+09 | 0.00 | 0.00 | 0.02 |
February | 0.884096E+09 | 0.00 | 0.00 | 2391.27 | 0.00 | 33240015.36 | 3407922.11 | 0.00 | 0.02 |
March | 0.807701E+09 | 0.00 | 0.00 | 900782.43 | 0.00 | 0.00 | 0.300971E+09 | 0.00 | 0.02 |
April | 0.574110E+09 | 18398632.85 | 0.00 | 2770729.92 | 0.00 | 0.00 | 0.710421E+09 | 0.00 | 0.02 |
May | 65725411.59 | 29123999.50 | 0.00 | 3263488.98 | 0.00 | 0.00 | 0.811888E+09 | 0.00 | 0.02 |
June | 51325252.31 | 0.259980E+09 | 0.00 | 2113299.88 | 0.00 | 0.00 | 0.471402E+09 | 0.00 | 0.02 |
July | 25817293.84 | 0.480606E+09 | 0.00 | 1623315.74 | 0.00 | 0.00 | 0.157511E+09 | 0.00 | 0.02 |
August | 42192456.37 | 0.349473E+09 | 0.00 | 2247804.58 | 0.00 | 0.00 | 0.218317E+09 | 0.00 | 0.02 |
September | 0.276037E+09 | 21151237.38 | 0.00 | 4074679.75 | 0.00 | 0.00 | 0.726257E+09 | 0.00 | 0.02 |
October | 0.753883E+09 | 0.00 | 0.00 | 2745675.27 | 0.00 | 0.00 | 0.472075E+09 | 0.00 | 0.02 |
November | 0.875338E+09 | 0.00 | 0.00 | 98486.69 | 0.00 | 24590671.81 | 57559444.57 | 0.00 | 0.02 |
December | 0.584335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421438E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.603843E+10 | 0.115873E+10 | 0.00 | 19840654.50 | 0.00 | 0.685550E+09 | 0.392981E+10 | 0.00 | 0.02 |
Minimum of Months | 25817293.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.109787E+10 | 0.480606E+09 | 0.00 | 4074679.75 | 0.00 | 0.421438E+09 | 0.811888E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364433E+09 | 0.00 | 0.00 | 167319.09 | 0.00 | 0.454192E+11 | 48719708.52 | 0.00 | 0.40 |
February | 0.672682E+09 | 0.00 | 0.00 | 615346.40 | 0.00 | 0.285969E+11 | 0.628678E+09 | 0.00 | 0.40 |
March | 0.997980E+09 | 0.00 | 0.00 | 4556751.41 | 0.00 | 0.201897E+11 | 0.335985E+10 | 0.00 | 0.40 |
April | 0.136224E+10 | 12897445.70 | 107032.94 | 35965240.01 | 1742677.11 | 0.443479E+10 | 0.124036E+11 | 3292.15 | 0.40 |
May | 0.246537E+10 | 0.200739E+09 | 92458.19 | 0.119889E+09 | 16806087.31 | 36540397.28 | 0.127878E+11 | 13233.38 | 0.40 |
June | 0.207253E+10 | 0.234948E+10 | 432735.83 | 0.113797E+09 | 0.460780E+09 | 7550781.90 | 0.661167E+10 | 33702.82 | 0.41 |
July | 0.158060E+10 | 0.390283E+10 | 839061.04 | 87349768.25 | 0.109525E+10 | 1871862.99 | 0.367187E+10 | 16537.65 | 0.41 |
August | 0.195761E+10 | 0.151711E+10 | 3818233.36 | 0.101830E+09 | 0.568490E+09 | 7275475.34 | 0.540935E+10 | 120480.08 | 0.40 |
September | 0.215395E+10 | 0.108380E+09 | 179819.48 | 87691283.86 | 22864931.22 | 73905932.07 | 0.128432E+11 | 17375.33 | 0.40 |
October | 0.117376E+10 | 0.00 | 0.00 | 31236048.62 | 0.00 | 0.270400E+10 | 0.146740E+11 | 0.00 | 0.40 |
November | 0.956273E+09 | 0.00 | 0.00 | 4799156.34 | 0.00 | 0.148185E+11 | 0.387366E+10 | 0.00 | 0.40 |
December | 0.379514E+09 | 0.00 | 0.00 | 218455.98 | 0.00 | 0.405365E+11 | 84239550.44 | 0.00 | 0.40 |
Annual Sum or Average | 0.161369E+11 | 0.809143E+10 | 5469340.83 | 0.588116E+09 | 0.216594E+10 | 0.156827E+12 | 0.763967E+11 | 204621.42 | 0.40 |
Minimum of Months | 0.364433E+09 | 0.00 | 0.00 | 167319.09 | 0.00 | 1871862.99 | 48719708.52 | 0.00 | 0.40 |
Maximum of Months | 0.246537E+10 | 0.390283E+10 | 3818233.36 | 0.119889E+09 | 0.109525E+10 | 0.454192E+11 | 0.146740E+11 | 120480.08 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20133504.32 | 0.00 | 0.00 | 30.16 | 0.00 | 0.335843E+10 | 720368.70 | 0.00 | 0.35 |
February | 54396674.07 | 0.00 | 0.00 | 388273.23 | 0.00 | 0.207965E+10 | 70037190.50 | 0.00 | 0.35 |
March | 53717866.70 | 0.00 | 0.00 | 1627791.91 | 0.00 | 0.155772E+10 | 0.197187E+09 | 0.00 | 0.35 |
April | 37241350.88 | 1083609.86 | 2436.83 | 6552200.29 | 0.00 | 0.725610E+09 | 0.575197E+09 | 1519.01 | 0.35 |
May | 11565612.14 | 16043060.90 | 3517.17 | 13962912.18 | 0.00 | 0.125593E+09 | 0.985048E+09 | 1073.86 | 0.36 |
June | 3896326.90 | 0.206889E+09 | 97743.96 | 14932291.85 | 242534.35 | 7988030.58 | 0.622425E+09 | 8993.97 | 0.36 |
July | 2250106.86 | 0.368353E+09 | 214490.48 | 11955774.92 | 0.00 | 513282.90 | 0.379129E+09 | 8950.44 | 0.36 |
August | 6375425.97 | 0.152888E+09 | 135788.39 | 12062547.69 | 1026637.47 | 13980017.99 | 0.518800E+09 | 13831.24 | 0.36 |
September | 23930898.33 | 9684751.87 | 2514.54 | 10316198.99 | 0.00 | 0.217082E+09 | 0.866338E+09 | 4117.12 | 0.36 |
October | 49296398.32 | 0.00 | 0.00 | 3270361.94 | 0.00 | 0.942206E+09 | 0.375374E+09 | 0.00 | 0.35 |
November | 51946744.54 | 0.00 | 0.00 | 387658.76 | 0.00 | 0.134994E+10 | 46775736.25 | 0.00 | 0.36 |
December | 6335774.12 | 0.00 | 0.00 | 4014.00 | 0.00 | 0.301619E+10 | 474745.94 | 0.00 | 0.35 |
Annual Sum or Average | 0.321087E+09 | 0.754941E+09 | 456491.37 | 75460055.92 | 1269171.83 | 0.133949E+11 | 0.463751E+10 | 38485.63 | 0.35 |
Minimum of Months | 2250106.86 | 0.00 | 0.00 | 30.16 | 0.00 | 513282.90 | 474745.94 | 0.00 | 0.35 |
Maximum of Months | 54396674.07 | 0.368353E+09 | 214490.48 | 14932291.85 | 1026637.47 | 0.335843E+10 | 0.985048E+09 | 13831.24 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 13.30 | 0.00 | 0.337883E+10 | 52393.08 | 0.00 | 0.35 |
February | 15497452.30 | 0.00 | 0.00 | 33814.52 | 0.00 | 0.217786E+10 | 10825867.63 | 0.00 | 0.35 |
March | 43273011.39 | 0.00 | 0.00 | 470951.60 | 0.00 | 0.167387E+10 | 92421055.65 | 0.00 | 0.35 |
April | 87472761.01 | 1076297.44 | 6534.21 | 4183192.55 | 0.00 | 0.798754E+09 | 0.454033E+09 | 4606.63 | 0.35 |
May | 0.151987E+09 | 15605946.09 | 0.00 | 10054456.07 | 439825.62 | 0.139954E+09 | 0.834040E+09 | 0.00 | 0.36 |
June | 0.131549E+09 | 0.176430E+09 | 42899.48 | 11051067.47 | 30731776.77 | 8142055.90 | 0.498424E+09 | 8824.29 | 0.36 |
July | 0.105519E+09 | 0.292982E+09 | 396915.06 | 8083147.35 | 75142985.78 | 627703.76 | 0.279572E+09 | 11043.31 | 0.36 |
August | 0.135642E+09 | 0.120392E+09 | 151761.01 | 8392586.92 | 33487997.22 | 14684287.93 | 0.392435E+09 | 14181.23 | 0.36 |
September | 0.135121E+09 | 8373761.36 | 2170.79 | 6454969.05 | 1306829.26 | 0.263019E+09 | 0.712941E+09 | 7486.64 | 0.36 |
October | 86138451.84 | 0.00 | 0.00 | 1313476.46 | 0.00 | 0.108040E+10 | 0.202132E+09 | 0.00 | 0.35 |
November | 29580531.93 | 0.00 | 0.00 | 63458.09 | 0.00 | 0.140062E+10 | 18616914.84 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 852.38 | 0.00 | 0.302249E+10 | 166915.60 | 0.00 | 0.35 |
Annual Sum or Average | 0.921781E+09 | 0.614860E+09 | 600280.54 | 50101985.75 | 0.141109E+09 | 0.139593E+11 | 0.349566E+10 | 46142.10 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13.30 | 0.00 | 627703.76 | 52393.08 | 0.00 | 0.35 |
Maximum of Months | 0.151987E+09 | 0.292982E+09 | 396915.06 | 11051067.47 | 75142985.78 | 0.337883E+10 | 0.834040E+09 | 14181.23 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.762323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547893E+11 | 0.00 | 0.00 | 0.65 |
February | 0.191639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243255E+11 | 0.00 | 0.00 | 0.65 |
March | 0.296343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870540E+10 | 0.00 | 0.00 | 0.65 |
April | 0.306235E+11 | 0.00 | 0.00 | 0.00 | 68560.13 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 0.276512E+11 | 0.00 | 0.00 | 0.00 | 75299797.97 | 0.00 | 0.00 | 0.00 | 0.65 |
June | 0.180377E+11 | 0.854532E+09 | 0.00 | 494829.36 | 0.172141E+10 | 0.00 | 0.186615E+09 | 0.00 | 0.66 |
July | 0.136379E+11 | 0.871813E+09 | 0.00 | 1003206.61 | 0.337154E+10 | 0.00 | 0.104371E+10 | 0.00 | 0.66 |
August | 0.190443E+11 | 0.00 | 0.00 | 5795.54 | 0.160689E+10 | 0.00 | 61987281.75 | 0.00 | 0.66 |
September | 0.303438E+11 | 0.00 | 0.00 | 0.00 | 10457590.55 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.327223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58762696.76 | 0.00 | 0.00 | 0.65 |
November | 0.272630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533832E+10 | 0.00 | 0.00 | 0.65 |
December | 0.859386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487905E+11 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.264339E+12 | 0.172635E+10 | 0.00 | 1503831.51 | 0.678566E+10 | 0.142008E+12 | 0.129231E+10 | 0.00 | 0.65 |
Minimum of Months | 0.762323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.327223E+11 | 0.871813E+09 | 0.00 | 1003206.61 | 0.337154E+10 | 0.547893E+11 | 0.104371E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2386721.70 | 0.00 | 0.00 | 4456.56 | 0.00 | 0.842152E+09 | 277415.37 | 0.00 | 0.35 |
February | 9303126.93 | 0.00 | 0.00 | 150206.64 | 0.00 | 0.532693E+09 | 8972649.20 | 0.00 | 0.35 |
March | 11446833.56 | 0.00 | 0.00 | 549846.45 | 0.00 | 0.406550E+09 | 34015043.32 | 0.00 | 0.35 |
April | 10860142.73 | 271891.43 | 0.00 | 1637932.52 | 0.00 | 0.212400E+09 | 0.111252E+09 | 0.00 | 0.35 |
May | 4221181.95 | 4010765.22 | 1010.16 | 3676202.57 | 0.00 | 56460212.47 | 0.219685E+09 | 137.60 | 0.36 |
June | 2675256.53 | 51624951.29 | 43162.00 | 3243850.27 | 137947.94 | 12307538.73 | 0.144084E+09 | 3402.06 | 0.36 |
July | 772424.14 | 92075555.42 | 63773.80 | 2644224.73 | 0.00 | 174147.16 | 94871195.15 | 4794.78 | 0.36 |
August | 1694480.64 | 38487772.91 | 25905.47 | 2838929.66 | 0.00 | 9994611.05 | 0.123277E+09 | 2280.42 | 0.36 |
September | 6148111.79 | 2421187.97 | 1165.88 | 2631163.07 | 0.00 | 89044838.51 | 0.181593E+09 | 492.03 | 0.36 |
October | 12047256.28 | 0.00 | 0.00 | 843264.93 | 0.00 | 0.261337E+09 | 68309355.98 | 0.00 | 0.35 |
November | 9946909.38 | 0.00 | 0.00 | 64408.35 | 0.00 | 0.348869E+09 | 3383638.66 | 0.00 | 0.36 |
December | 1439303.17 | 0.00 | 0.00 | 25.15 | 0.00 | 0.754292E+09 | 20619.26 | 0.00 | 0.35 |
Annual Sum or Average | 72941748.81 | 0.188892E+09 | 135017.31 | 18284510.91 | 137947.94 | 0.352627E+10 | 0.989740E+09 | 11106.89 | 0.35 |
Minimum of Months | 772424.14 | 0.00 | 0.00 | 25.15 | 0.00 | 174147.16 | 20619.26 | 0.00 | 0.35 |
Maximum of Months | 12047256.28 | 92075555.42 | 63773.80 | 3676202.57 | 137947.94 | 0.842152E+09 | 0.219685E+09 | 4794.78 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 584.06 | 0.00 | 0.844688E+09 | 32775.30 | 0.00 | 0.35 |
February | 2110156.05 | 0.00 | 0.00 | 30123.61 | 0.00 | 0.545080E+09 | 3833902.73 | 0.00 | 0.35 |
March | 4773183.11 | 0.00 | 0.00 | 240211.97 | 0.00 | 0.426274E+09 | 21222232.33 | 0.00 | 0.35 |
April | 22766037.68 | 260764.32 | 0.00 | 981737.34 | 11095.25 | 0.232179E+09 | 80183682.60 | 0.00 | 0.35 |
May | 38911030.65 | 3875202.94 | 3484.34 | 2640124.96 | 130903.35 | 50544723.52 | 0.191913E+09 | 1852.30 | 0.36 |
June | 34121872.20 | 43882209.94 | 68695.69 | 2349899.97 | 7847529.64 | 9014042.15 | 0.116806E+09 | 4957.79 | 0.36 |
July | 25811043.52 | 72727576.02 | 97183.86 | 1917669.65 | 19304990.80 | 113120.71 | 70608621.04 | 3577.28 | 0.36 |
August | 33834856.07 | 29981235.71 | 49231.44 | 2053987.84 | 8474667.35 | 9565331.66 | 92334276.60 | 6311.60 | 0.36 |
September | 36639196.30 | 2092528.64 | 1551.53 | 1551303.06 | 326707.31 | 0.100640E+09 | 0.140554E+09 | 1774.53 | 0.36 |
October | 18652657.83 | 0.00 | 0.00 | 352916.45 | 0.00 | 0.287829E+09 | 35662106.32 | 0.00 | 0.35 |
November | 6187288.37 | 0.00 | 0.00 | 8137.87 | 0.00 | 0.355657E+09 | 368584.31 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755664E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.223807E+09 | 0.152820E+09 | 220146.86 | 12126696.77 | 36095893.71 | 0.361725E+10 | 0.753519E+09 | 18473.49 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113120.71 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 38911030.65 | 72727576.02 | 97183.86 | 2640124.96 | 19304990.80 | 0.844688E+09 | 0.191913E+09 | 6311.60 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70983274.68 | 0.00 | 0.00 | 1436673.68 | 0.00 | 0.513550E+10 | 0.219622E+09 | 0.00 | 0.40 |
February | 47279541.44 | 0.00 | 0.00 | 3571446.50 | 0.00 | 0.310158E+10 | 0.388228E+09 | 0.00 | 0.40 |
March | 47643969.88 | 0.00 | 0.00 | 5367460.34 | 0.00 | 0.231166E+10 | 0.542809E+09 | 0.00 | 0.40 |
April | 32893676.12 | 1746763.57 | 0.00 | 10248250.14 | 0.00 | 0.103647E+10 | 0.107998E+10 | 0.00 | 0.40 |
May | 21018142.29 | 25767118.44 | 6553.18 | 18591943.91 | 0.00 | 0.169005E+09 | 0.161621E+10 | 820.56 | 0.40 |
June | 13751933.72 | 0.331528E+09 | 220217.46 | 15896288.95 | 1071171.57 | 27768044.50 | 0.985346E+09 | 29658.90 | 0.40 |
July | 4403914.37 | 0.589453E+09 | 518466.11 | 12644883.54 | 1966936.18 | 1410387.23 | 0.614109E+09 | 40984.55 | 0.41 |
August | 9803149.08 | 0.245985E+09 | 200494.14 | 15582519.21 | 1242376.63 | 21708447.72 | 0.838230E+09 | 17559.09 | 0.40 |
September | 37175757.29 | 15562574.13 | 2.87 | 17774820.22 | 0.00 | 0.203512E+09 | 0.153665E+10 | 2970.55 | 0.40 |
October | 78874498.76 | 0.00 | 0.00 | 8906748.71 | 0.00 | 0.109173E+10 | 0.102112E+10 | 0.00 | 0.40 |
November | 56360160.63 | 0.00 | 0.00 | 2365634.32 | 0.00 | 0.196809E+10 | 0.300542E+09 | 0.00 | 0.40 |
December | 37916813.57 | 0.00 | 0.00 | 697082.84 | 0.00 | 0.464230E+10 | 0.174413E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.458105E+09 | 0.121004E+10 | 945733.77 | 0.113084E+09 | 4280484.38 | 0.197107E+11 | 0.931725E+10 | 91993.66 | 0.40 |
Minimum of Months | 4403914.37 | 0.00 | 0.00 | 697082.84 | 0.00 | 1410387.23 | 0.174413E+09 | 0.00 | 0.40 |
Maximum of Months | 78874498.76 | 0.589453E+09 | 518466.11 | 18591943.91 | 1966936.18 | 0.513550E+10 | 0.161621E+10 | 40984.55 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426690E+11 | 0.00 | 0.00 | 15760619.30 | 0.00 | 0.157383E+11 | 0.231289E+11 | 0.00 | 4.01 |
February | 0.253104E+11 | 0.00 | 0.00 | 23441601.66 | 0.00 | 0.240687E+10 | 0.301100E+11 | 0.00 | 4.10 |
March | 0.139307E+11 | 0.00 | 0.00 | 39817894.99 | 0.00 | 0.00 | 0.391443E+11 | 0.00 | 4.27 |
April | 0.136733E+10 | 89424.81 | 0.00 | 61480559.25 | 0.00 | 0.00 | 0.448909E+11 | 0.00 | 4.63 |
May | 0.107592E+09 | 0.115463E+09 | 0.00 | 94940677.92 | 0.00 | 0.00 | 0.473070E+11 | 0.00 | 5.19 |
June | 0.00 | 0.445380E+10 | 0.00 | 84734296.07 | 0.00 | 0.00 | 0.331564E+11 | 0.00 | 5.43 |
July | 0.00 | 0.727260E+10 | 0.00 | 76938252.25 | 0.00 | 0.00 | 0.276199E+11 | 0.00 | 5.55 |
August | 1486432.90 | 0.259477E+10 | 0.00 | 86171202.65 | 0.00 | 0.00 | 0.346076E+11 | 0.00 | 5.37 |
September | 97492203.16 | 13749443.83 | 0.00 | 80732116.26 | 0.00 | 0.00 | 0.501090E+11 | 0.00 | 5.03 |
October | 0.141827E+10 | 0.00 | 0.00 | 60007283.07 | 0.00 | 0.00 | 0.482316E+11 | 0.00 | 4.63 |
November | 0.728048E+10 | 0.00 | 0.00 | 41378170.88 | 0.00 | 0.00 | 0.388153E+11 | 0.00 | 4.36 |
December | 0.406895E+11 | 0.00 | 0.00 | 19913368.09 | 0.00 | 0.839873E+10 | 0.262033E+11 | 0.00 | 4.02 |
Annual Sum or Average | 0.132872E+12 | 0.144505E+11 | 0.00 | 0.685316E+09 | 0.00 | 0.265439E+11 | 0.443324E+12 | 0.00 | 4.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15760619.30 | 0.00 | 0.00 | 0.231289E+11 | 0.00 | 4.01 |
Maximum of Months | 0.426690E+11 | 0.727260E+10 | 0.00 | 94940677.92 | 0.00 | 0.157383E+11 | 0.501090E+11 | 0.00 | 5.55 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406376E+11 | 0.00 | 0.00 | 22436140.88 | 0.00 | 0.148375E+11 | 0.307317E+11 | 0.00 | 4.27 |
February | 0.219052E+11 | 0.00 | 0.00 | 33192278.64 | 0.00 | 0.213329E+10 | 0.377455E+11 | 0.00 | 4.40 |
March | 0.992358E+10 | 0.00 | 0.00 | 54107581.92 | 0.00 | 0.00 | 0.478192E+11 | 0.00 | 4.66 |
April | 0.436745E+09 | 100769.70 | 0.00 | 75986517.07 | 0.00 | 0.00 | 0.503976E+11 | 0.00 | 5.08 |
May | 3920773.85 | 0.125384E+09 | 0.00 | 0.106899E+09 | 0.00 | 0.00 | 0.514732E+11 | 0.00 | 5.64 |
June | 0.00 | 0.478624E+10 | 0.00 | 93786673.22 | 0.00 | 0.00 | 0.357491E+11 | 0.00 | 5.86 |
July | 0.00 | 0.782056E+10 | 0.00 | 83676117.20 | 0.00 | 0.00 | 0.294815E+11 | 0.00 | 5.94 |
August | 0.00 | 0.281181E+10 | 0.00 | 95087959.47 | 0.00 | 0.00 | 0.371341E+11 | 0.00 | 5.79 |
September | 3158783.96 | 14572180.43 | 0.00 | 92355503.14 | 0.00 | 0.00 | 0.547330E+11 | 0.00 | 5.48 |
October | 0.241941E+09 | 0.00 | 0.00 | 74519230.83 | 0.00 | 0.00 | 0.544011E+11 | 0.00 | 5.09 |
November | 0.250490E+10 | 0.00 | 0.00 | 56126447.23 | 0.00 | 0.00 | 0.479356E+11 | 0.00 | 4.77 |
December | 0.386117E+11 | 0.00 | 0.00 | 27979902.87 | 0.00 | 0.788366E+10 | 0.334358E+11 | 0.00 | 4.30 |
Annual Sum or Average | 0.114269E+12 | 0.155587E+11 | 0.00 | 0.816153E+09 | 0.00 | 0.248545E+11 | 0.511038E+12 | 0.00 | 5.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22436140.88 | 0.00 | 0.00 | 0.294815E+11 | 0.00 | 4.27 |
Maximum of Months | 0.406376E+11 | 0.782056E+10 | 0.00 | 0.106899E+09 | 0.00 | 0.148375E+11 | 0.547330E+11 | 0.00 | 5.94 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.856875E+10 | 0.00 | 0.00 | 89058942.69 | 0.00 | 0.173796E+11 | 0.834346E+11 | 0.00 | 18.82 |
February | 0.418858E+10 | 0.00 | 0.00 | 94092932.44 | 0.00 | 0.601644E+10 | 0.746660E+11 | 0.00 | 20.50 |
March | 0.248857E+10 | 0.00 | 0.00 | 0.114664E+09 | 0.00 | 0.162599E+10 | 0.778403E+11 | 0.00 | 21.68 |
April | 0.00 | 193713.29 | 0.00 | 0.121249E+09 | 0.00 | 0.00 | 0.701694E+11 | 0.00 | 22.80 |
May | 0.00 | 0.212815E+09 | 0.00 | 0.148319E+09 | 0.00 | 0.00 | 0.628319E+11 | 0.00 | 23.67 |
June | 0.00 | 0.703101E+10 | 0.00 | 0.124782E+09 | 0.00 | 0.00 | 0.394122E+11 | 0.00 | 24.01 |
July | 0.00 | 0.114754E+11 | 0.00 | 0.107537E+09 | 0.00 | 0.00 | 0.305387E+11 | 0.00 | 24.18 |
August | 0.00 | 0.452132E+10 | 0.00 | 0.125824E+09 | 0.00 | 0.00 | 0.406923E+11 | 0.00 | 23.86 |
September | 0.00 | 29559251.90 | 0.00 | 0.131685E+09 | 0.00 | 0.00 | 0.690614E+11 | 0.00 | 23.41 |
October | 0.00 | 0.00 | 0.00 | 0.115656E+09 | 0.00 | 0.00 | 0.741491E+11 | 0.00 | 22.48 |
November | 0.00 | 0.00 | 0.00 | 0.108168E+09 | 0.00 | 0.00 | 0.710113E+11 | 0.00 | 21.68 |
December | 0.833805E+10 | 0.00 | 0.00 | 93036506.80 | 0.00 | 0.113910E+11 | 0.835493E+11 | 0.00 | 19.10 |
Annual Sum or Average | 0.235839E+11 | 0.232703E+11 | 0.00 | 0.137407E+10 | 0.00 | 0.364130E+11 | 0.777356E+12 | 0.00 | 22.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89058942.69 | 0.00 | 0.00 | 0.305387E+11 | 0.00 | 18.82 |
Maximum of Months | 0.856875E+10 | 0.114754E+11 | 0.00 | 0.148319E+09 | 0.00 | 0.173796E+11 | 0.835493E+11 | 0.00 | 24.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282101E+11 | 0.00 | 0.00 | 1.19 |
February | 0.593740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152600E+11 | 0.00 | 0.00 | 1.19 |
March | 0.114833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720432E+10 | 0.00 | 0.00 | 1.19 |
April | 0.146899E+11 | 0.00 | 0.00 | 0.00 | 33417.78 | 0.236688E+09 | 0.00 | 0.00 | 1.19 |
May | 0.131553E+11 | 33080531.44 | 0.00 | 722360.92 | 4739390.04 | 0.00 | 0.321939E+09 | 0.00 | 1.20 |
June | 0.846733E+10 | 0.949342E+09 | 0.00 | 1055070.59 | 0.424858E+09 | 0.00 | 0.414497E+09 | 0.00 | 1.22 |
July | 0.604860E+10 | 0.153262E+10 | 0.00 | 2202372.88 | 0.631588E+09 | 0.00 | 0.110627E+10 | 0.00 | 1.23 |
August | 0.879086E+10 | 0.409508E+09 | 0.00 | 1003363.56 | 0.382760E+09 | 0.00 | 0.522025E+09 | 0.00 | 1.21 |
September | 0.146426E+11 | 3619871.64 | 0.00 | 207432.84 | 1497991.50 | 0.00 | 0.147935E+09 | 0.00 | 1.20 |
October | 0.157951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183191E+09 | 0.00 | 0.00 | 1.19 |
November | 0.114483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444236E+10 | 0.00 | 0.00 | 1.20 |
December | 0.206450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259001E+11 | 0.00 | 0.00 | 1.18 |
Annual Sum or Average | 0.114728E+12 | 0.292817E+10 | 0.00 | 5190600.80 | 0.144548E+10 | 0.814366E+11 | 0.251266E+10 | 0.00 | 1.20 |
Minimum of Months | 0.206450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
Maximum of Months | 0.157951E+11 | 0.153262E+10 | 0.00 | 2202372.88 | 0.631588E+09 | 0.282101E+11 | 0.110627E+10 | 0.00 | 1.23 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.143769E+12 | 0.338668E+11 | 0.419489E+12 | 0.161174E+13 | 0.197954E+12 |
February | 0.231337E+12 | 0.272118E+11 | 0.336603E+12 | 0.135188E+13 | 0.137509E+12 |
March | 0.330130E+12 | 0.258766E+11 | 0.326053E+12 | 0.134241E+13 | 0.121162E+12 |
April | 0.445350E+12 | 0.169620E+11 | 0.215532E+12 | 0.931584E+12 | 0.126757E+12 |
May | 0.500450E+12 | 0.960109E+10 | 0.118785E+12 | 0.548991E+12 | 0.326621E+12 |
June | 0.522769E+12 | 0.377377E+10 | 0.445953E+11 | 0.225266E+12 | 0.595311E+12 |
July | 0.532578E+12 | 0.142169E+10 | 0.148723E+11 | 0.104739E+12 | 0.786732E+12 |
August | 0.441390E+12 | 0.404093E+10 | 0.531927E+11 | 0.257458E+12 | 0.580413E+12 |
September | 0.332141E+12 | 0.981779E+10 | 0.128709E+12 | 0.572073E+12 | 0.242962E+12 |
October | 0.177312E+12 | 0.160450E+11 | 0.212998E+12 | 0.906781E+12 | 0.115726E+12 |
November | 0.911754E+11 | 0.214488E+11 | 0.282570E+12 | 0.115938E+13 | 0.961409E+11 |
December | 0.100197E+12 | 0.323009E+11 | 0.404453E+12 | 0.155999E+13 | 0.182703E+12 |
Annual Sum or Average | 0.384860E+13 | 0.202367E+12 | 0.255785E+13 | 0.105723E+14 | 0.350999E+13 |
Minimum of Months | 0.911754E+11 | 0.142169E+10 | 0.148723E+11 | 0.104739E+12 | 0.961409E+11 |