Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:45:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11794.27 | 1039.57 | 1039.57 |
Net Site Energy | 11794.27 | 1039.57 | 1039.57 |
Total Source Energy | 25132.93 | 2215.28 | 2215.28 |
Net Source Energy | 25132.93 | 2215.28 | 2215.28 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1169.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1794.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 454.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 98.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2907.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5927.96 | 5866.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1169.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1794.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 454.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 98.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.76 | 2907.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1169.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1794.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 454.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 98.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.76 | 2907.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.94 | 359.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.42 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.50 | 517.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.94 | 359.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.42 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.50 | 517.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5927.964 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5927.964 | 100.00 |
Total On-Site and Utility Electric Sources | 5927.964 | 100.00 |
Total Electricity End Uses | 5927.964 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1092.53 | 62.21 |
Air to Air Heat Recovery for Heating | 663.54 | 37.79 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1756.06 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 19.00 |
Time Setpoint Not Met During Occupied Cooling | 40.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7735.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-19:19 | 03-JAN-18:19 | - | - | - | - | - | - | - | - | - | - | 03-MAR-21:49 |
Heating | 0.00 | 227286.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 174878.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31552.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24124.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4320.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3828.45 | 246805.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1868.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 413922.72 | 578340.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 227286.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 174878.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1248.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 24124.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4320.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3828.45 | 246805.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1091.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1267.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5684.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1439.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 311.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 480.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.44 | 3152.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18773.86 | 6359.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 501.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 42.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 277.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1654.77 | 560.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 501.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 42.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 277.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1654.77 | 560.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.53 | 0.595520 | 0.527000 | 1.33 | 1.00 | 0.500000 | 0.000640 | 0.000072 | 1.33 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.316173 | 0.161647 | 0.527000 | 0.166623 | 0.527000 | 0.500000 | 0.002357 | 0.000032 | 0.166623 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.236548 | 0.250198 | 0.527000 | 0.124661 | 0.667194 | 0.500000 | 0.001523 | 0.000014 | 0.124661 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.204052 | 0.613342 | 0.527000 | 0.107535 | 1.00 | 0.500000 | 0.000621 | 0.000020 | 0.107535 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.120034 | 0.601549 | 0.527000 | 0.063258 | 1.00 | 0.500000 | 0.000633 | 0.000012 | 0.063258 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.38 | 0.017608 | 0.527000 | 1.78 | 0.527000 | 0.500000 | 0.021638 | 0.000099 | 1.78 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.39 | 0.103630 | 0.527000 | 0.731856 | 0.527000 | 0.500000 | 0.003677 | 0.000094 | 0.731856 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.81 | 0.207305 | 0.527000 | 2.53 | 0.552814 | 0.500000 | 0.001838 | 0.000258 | 2.53 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.51 | 0.786725 | 0.527000 | 0.795067 | 1.00 | 0.500000 | 0.000484 | 0.000121 | 0.795067 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113215 | 0.527000 | 1.18 | 0.527000 | 0.500000 | 0.003365 | 0.000107 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.34 | 0.108052 | 0.527000 | 1.23 | 0.527000 | 0.500000 | 0.003526 | 0.000110 | 1.23 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.31 | 0.061205 | 0.527000 | 1.22 | 0.527000 | 0.500000 | 0.011196 | 0.000072 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.761732 | 0.412269 | 0.527000 | 0.401433 | 1.00 | 0.500000 | 0.000924 | 0.000075 | 0.401433 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8207.89 | 0.000072 | 173.03 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3648.72 | 0.000032 | 92.20 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1554.52 | 0.000014 | 35.07 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2284.86 | 0.000020 | 57.26 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1420.78 | 0.000012 | 36.17 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11298.33 | 0.000099 | 238.67 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10765.90 | 0.000094 | 249.18 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29532.91 | 0.000258 | 660.27 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6286.16 | 0.000055 | 179.64 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6298.59 | 0.000055 | 179.99 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 36024.28 | 0.000315 | 1029.43 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 36271.02 | 0.000317 | 1036.48 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6260.67 | 0.000055 | 178.91 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6273.11 | 0.000055 | 179.26 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13855.77 | 0.000121 | 331.12 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1905.02 | 0.000017 | 54.44 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1909.94 | 0.000017 | 54.58 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9107.89 | 0.000080 | 260.26 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12189.33 | 0.000107 | 268.67 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12606.52 | 0.000110 | 277.46 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8272.44 | 0.000072 | 175.54 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8538.92 | 0.000075 | 214.04 |
VAV WITH REHEAT HEATING COIL | 177214.68 | 0.001550 | 2991.03 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000144 | 278.70 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.02 | 0.000055 | 0.000325 |
ROOM_2_FLR_3 FAN COIL | 1.01 | 0.000055 | 0.000322 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.15 | 0.000315 | 0.001912 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.50 | 0.000317 | 0.002139 |
ROOM_5_FLR_3 FAN COIL | 0.925109 | 0.000055 | 0.000296 |
ROOM_6_FLR_3 FAN COIL | 0.917201 | 0.000055 | 0.000294 |
ROOM_1_FLR_6 FAN COIL | 0.268501 | 0.000017 | 0.000085 |
ROOM_2_FLR_6 FAN COIL | 0.265367 | 0.000017 | 0.000084 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.22 | 0.000080 | 0.000393 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.02 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.01 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.15 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.50 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.925109 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.917201 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.268501 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.265367 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.22 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008695 | 12.80 | 0.008500 | 0.000325 | 1.02 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008697 | 12.80 | 0.008500 | 0.000322 | 1.01 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008607 | 12.80 | 0.008500 | 0.001912 | 6.15 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008822 | 12.80 | 0.008500 | 0.002139 | 6.50 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008716 | 12.80 | 0.008500 | 0.000296 | 0.925109 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008718 | 12.80 | 0.008500 | 0.000294 | 0.917201 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008686 | 12.80 | 0.008500 | 0.000085 | 0.268501 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008688 | 12.80 | 0.008500 | 0.000084 | 0.265367 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008757 | 12.80 | 0.008500 | 0.000393 | 1.22 | |
VAV WITH REHEAT COOLING COIL | 29.50 | 6.70 | 0.012236 | 10.92 | 0.008500 | 0.020844 | 22.02 | 728811.08 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.002607 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 22.14 | 11.67 | 22.02 | 22.02 | 0.300000 | 0.529944 | 22.02 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.02 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.02 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020844 | 0.000023 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001550 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000144 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.029301 | 4783.99 | |
HEATSYS1 PUMP | 0.003746 | 1128.26 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003746 | 0.449572 |
COOLSYS1 | 0.029301 | 3.52 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 428240.67 | 428240.67 | 0.003746 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.029301 | 3312.12 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.029301 | 1024521.61 | 1025130.85 | 116.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.8537E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0323E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1102 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3566E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1969E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.5953E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1080 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9517E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1204 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3475E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9001E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.2853E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3109E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3137E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7873E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9610E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7300E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.9150E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3109E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3137E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7873E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9610E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7300E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.9150E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33598.76609 | 33598.76609 | 2.53202 | 2.53202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 28.93750 | 1.44633E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1415.62029 | 1415.62029 | 6.29350E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4194.81813 | 4194.81813 | 0.31617 | 0.31617 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2801.34189 | 2801.34189 | 0.12454 | 0.12454 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3138.45881 | 3138.45881 | 0.23655 | 0.23655 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 920.56551 | 920.56551 | 4.09254E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2707.88492 | 2707.88492 | 0.20405 | 0.20405 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 31.17000 | 1.44674E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1738.11227 | 1738.11227 | 7.72707E-002 | 7.72707E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1592.91668 | 1592.91668 | 0.12003 | 0.12003 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1099.12755 | 1099.12755 | 4.88636E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44812.57117 | 44812.57117 | 3.37724 | 3.37724 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2250.64565 | 2250.64565 | 0.10005 | 0.10005 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18409.47449 | 18409.47449 | 1.38872 | 1.38872 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7043.52054 | 7043.52054 | 0.31313 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63780.88052 | 63780.88052 | 4.80855 | 4.80855 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16644.77202 | 16644.77202 | 0.73997 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10068.12025 | 10068.12025 | 1.02247 | 1.02247 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6286.22830 | 6286.22830 | 0.28110 | 0.28110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9960.20519 | 9960.20519 | 1.01151 | 1.01151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6298.66090 | 6298.66090 | 0.28165 | 0.28165 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 60576.18047 | 60576.18047 | 6.15131 | 6.15131 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 36024.48373 | 36024.48373 | 1.61093 | 1.61093 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 64022.72894 | 64022.72894 | 6.50180 | 6.50180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 36271.22411 | 36271.22411 | 1.62196 | 1.62196 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9109.40082 | 9109.40082 | 0.92511 | 0.92511 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6260.74071 | 6260.74071 | 0.27996 | 0.27996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9031.52472 | 9031.52472 | 0.91720 | 0.91720 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6273.18118 | 6273.18118 | 0.28051 | 0.28051 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20019.61793 | 20019.61793 | 1.50867 | 1.50867 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9811.22680 | 9811.22680 | 0.43618 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2643.88852 | 2643.88852 | 0.26850 | 0.26850 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44708E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1905.03917 | 1905.03917 | 8.51864E-002 | 8.51864E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2613.02954 | 2613.02954 | 0.26537 | 0.26537 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1909.96570 | 1909.96570 | 8.54067E-002 | 8.54067E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11973.56663 | 11973.56663 | 1.21599 | 1.21599 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9107.97269 | 9107.97269 | 0.40728 | 0.40728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29583.99648 | 29583.99648 | 2.23224 | 2.23224 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6204.41150 | 6204.41150 | 0.27583 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30997.98012 | 30997.98012 | 2.33890 | 2.33890 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6335.61173 | 6335.61173 | 0.28166 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30614.90261 | 30614.90261 | 2.31330 | 2.31330 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2087.27056 | 2087.27056 | 9.27798E-002 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10108.01532 | 10108.01532 | 0.76173 | 0.76173 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6496.39481 | 6496.39481 | 0.28881 | 0.28881 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 429001.07 | 22.01518 | 22.01518 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 198093.87 | 7.38269 | 7.38269 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 17.65378 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.93399 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53202 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59552 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33437 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.39777E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.18062E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33437 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8207.89347 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18062E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 173.03139 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31617 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16165 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16662 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35699E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.19206E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16662 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3648.72129 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.19206E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 92.20029 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23655 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25020 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12466 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66719 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52280E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35996E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12466 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1554.52113 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35996E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 35.07204 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20405 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61334 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10754 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.21187E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99889E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10754 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2284.85687 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99889E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.25538 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12003 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60155 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.32582E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.33365E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24296E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.32582E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1420.78268 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24296E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.16523 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.37724 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.76079E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.77981 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16380E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.88427E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77981 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11298.32666 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.88427E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.66610 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38872 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10363 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73186 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67655E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.41848E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73186 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10765.90295 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.41848E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.17592 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.80855 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20731 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.53411 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55281 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83787E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.58367E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.53411 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29532.91487 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58367E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 660.26552 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02247 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.02247 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.49940E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.25328E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70362 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69493E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25328E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02247 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6286.15610 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.49940E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.63642 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01151 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01151 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.51028E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.22047E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70362 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69735E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.22047E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01151 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6298.58857 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.51028E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.99161 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.15131 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.15131 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.15156E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.91179E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70441 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60709E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.91179E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.15131 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 36024.28491 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.15156E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1029.43399 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.50180 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.50180 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.17315E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.13861E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70353 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82234E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.13861E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.50180 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 36271.02402 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17315E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1036.48324 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92511 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.92511 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.47711E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.95986E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70358 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71591E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.95986E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92511 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6260.66879 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.47711E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 178.90827 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91720 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.91720 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.48799E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.93606E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70357 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71786E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.93606E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91720 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6273.10912 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.48799E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 179.26368 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50867 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78673 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79507 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.84286E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21216E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79507 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13855.76883 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21216E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.12335 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26850 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.26850 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.66659E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.52185E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70363 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68554E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.52185E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26850 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1905.01798 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66659E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 54.43635 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26537 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.26537 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.67090E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.42773E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70363 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68793E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.42773E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26537 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1909.94445 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67090E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 54.57709 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21599 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21599 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.96798E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.93230E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70345 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75666E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.93230E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21599 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9107.89221 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96798E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 260.25861 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23224 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11321 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17639 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36529E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06638E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17639 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12189.32937 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06638E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 268.67151 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33890 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10805 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23260 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.52608E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10287E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23260 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12606.52452 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10287E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.46205 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31330 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.12046E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21911 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11965E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.23709E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21911 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8272.43941 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.23709E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 175.54204 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76173 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41227 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40143 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.24153E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.47022E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40143 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8538.91599 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.47022E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 214.03805 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66682 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66682 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.13818 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66682 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.01518 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.01518 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52994 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.01518 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.01518 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.50351 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92185 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.22364E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 728811.07640 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.08439E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.01518 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 177214.68047 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55035E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2991.03004 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.01518 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.08439E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.28456E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.55035E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60720E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44458E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 278.69642 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60720E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82645E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44458E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.93012E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4783.98872 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.74644E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.44957 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.74644E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1128.26206 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 428240.66897 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 428240.67000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.74644E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.93012E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.51614 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.93012E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3312.11674 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.93012E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1024521.61214 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1025130.85000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 116.86492 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8250.00 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3664.09 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1561.91 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2294.55 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1426.73 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11356.18 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10815.89 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29674.60 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6771.11 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6784.50 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 38803.27 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 39069.01 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6743.66 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6757.06 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13917.39 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2051.93 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2057.24 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9810.26 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12248.63 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12667.94 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8314.63 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8575.14 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 131797.98 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 12280.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17079.48 | 14386.13 | 2693.35 | 0.84 | 3726.80 | 37.80 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16903.71 | 14234.36 | 2669.36 | 0.84 | 3685.44 | 37.38 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 101115.19 | 86005.28 | 15109.92 | 0.85 | 22741.58 | 230.66 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 111079.78 | 92319.97 | 18759.81 | 0.83 | 23329.88 | 236.62 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15510.97 | 13035.50 | 2475.48 | 0.84 | 3360.92 | 34.09 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15383.69 | 12925.83 | 2457.86 | 0.84 | 3331.21 | 33.79 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4477.53 | 3775.30 | 702.24 | 0.84 | 980.14 | 9.94 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4427.17 | 3731.86 | 695.31 | 0.84 | 968.33 | 9.82 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 20537.52 | 17185.14 | 3352.38 | 0.84 | 4396.27 | 44.59 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 653434.08 | 424127.24 | 229306.84 | 0.65 | 97183.15 | 985.69 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64827.35 | 41208.20 | 23619.15 | 0.64 | 8819.06 | 89.45 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3959694260E-002 | 1.9802624166E-002 | Pass | Pass | 5.4018203888E-003 | 1.8413289218E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3730138763E-003 | 1.0793065132E-003 | Pass | Pass | 0.2396206252 | 0.6974710400 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1608964194E-003 | 1.1367230670E-002 | Pass | Pass | 1.7745719908E-002 | 4.4735179839E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6234712130E-004 | 3.4546475450E-004 | Pass | Pass | 3.5668841802E-002 | 7.2734138133E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.2388975518E-004 | 3.3029708389E-004 | Pass | Pass | 0.3458595192 | 1.9075565141 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.8880859484E-002 | 0.1896560856 | Pass | Pass | 1.8507163563E-002 | 5.1346783480E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8725444046E-003 | 6.7406617879E-003 | Pass | Pass | 2.6513165098E-002 | 7.1195814592E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3696376928E-002 | 2.5307536984E-002 | Pass | Pass | 1.4898147876E-002 | 4.5761314874E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4134975215E-002 | 0.1700187830 | Pass | Pass | 0.1470441486 | 0.6365962752 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.5866156055E-002 | 0.1759346763 | Pass | Pass | 0.1439537384 | 0.6242630403 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.7445235453E-002 | 4.4149903754E-002 | Pass | Pass | 7.2444090651E-003 | 7.2995935581E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.7957715700E-002 | 0.1191928919 | Pass | Pass | 0.2967643483 | 1.3530476226 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2651629873E-002 | 0.1651619308 | Pass | Pass | 0.1565053862 | 0.6867136791 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4370753526E-002 | 0.1710769278 | Pass | Pass | 0.1526271906 | 0.6713912365 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0362292741E-004 | 3.1266661731E-004 | Pass | Pass | 3.6709776918E-002 | 7.2137356984E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.4470946527E-002 | 0.2347645819 | Pass | Pass | 9.4738278752E-002 | 0.3420749793 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6436289194E-002 | 0.2413381672 | Pass | Pass | 9.3035650036E-002 | 0.3360909269 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5640266044E-002 | 0.1163907383 | Pass | Pass | 0.1018379687 | 0.3016643128 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8743658180E-002 | 9.8102442780E-002 | Pass | Pass | 6.1352233644E-003 | 1.4532202276E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9936919614E-002 | 9.3286122642E-002 | Pass | Pass | 5.2865598033E-003 | 1.2385764726E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6376949887E-002 | 0.1402656643 | Pass | Pass | 1.8812651255E-002 | 3.2574562041E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2287552233E-004 | 4.9868801757E-004 | Pass | Pass | 3.2495469850E-002 | 3.9339076845E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2999.36 | 32.75 | 462.63 | 1478.10 | 8204.16 | 13176.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.20 | 0.0000 | Y | 14.27 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.70 | 0.0000 | Y | 110.23 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 31.20 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 31.20 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.02 | |
Exterior Lighting Total | 12338.45 | 194.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 428240.67 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1025130.85 | 2.96 | 1025311.04 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11375.38 | 17079.48 | 14386.13 | 2693.35 | 0.84 | - | 3726.80 | 37.80 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11260.66 | 16903.71 | 14234.36 | 2669.36 | 0.84 | - | 3685.44 | 37.38 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66847.20 | 101115.19 | 86005.28 | 15109.92 | 0.85 | - | 22741.58 | 230.66 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 74778.24 | 111079.78 | 92319.97 | 18759.81 | 0.83 | - | 23329.88 | 236.62 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10349.40 | 15510.97 | 13035.50 | 2475.48 | 0.84 | - | 3360.92 | 34.09 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10266.20 | 15383.69 | 12925.83 | 2457.86 | 0.84 | - | 3331.21 | 33.79 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2979.74 | 4477.53 | 3775.30 | 702.24 | 0.84 | - | 980.14 | 9.94 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2946.83 | 4427.17 | 3731.86 | 695.31 | 0.84 | - | 968.33 | 9.82 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13749.61 | 20537.52 | 17185.14 | 3352.38 | 0.84 | - | 4396.27 | 44.59 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 728811.08 | 653434.08 | 424127.24 | 229306.84 | 0.65 | - | 97183.15 | 985.69 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64827.35 | 41208.20 | 23619.15 | 0.64 | - | 8819.06 | 89.45 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8207.89 | 8250.00 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3648.72 | 3664.09 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1554.52 | 1561.91 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2284.86 | 2294.55 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1420.78 | 1426.73 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11298.33 | 11356.18 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10765.90 | 10815.89 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29532.91 | 29674.60 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6286.16 | 6771.11 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6298.59 | 6784.50 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 36024.28 | 38803.27 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 36271.02 | 39069.01 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6260.67 | 6743.66 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6273.11 | 6757.06 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13855.77 | 13917.39 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1905.02 | 2051.93 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1909.94 | 2057.24 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9107.89 | 9810.26 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12189.33 | 12248.63 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12606.52 | 12667.94 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8272.44 | 8314.63 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8538.92 | 8575.14 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 177214.68 | 131797.98 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 12280.59 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 719.45 | 703.64 | 1.00 | 1.19 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 711.74 | 703.64 | 1.00 | 1.19 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.15 | 4328.28 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.50 | 4574.90 | 703.64 | 1.00 | 0.95 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 650.94 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.92 | 645.38 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 188.93 | 703.64 | 1.00 | 1.79 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 186.72 | 703.64 | 1.00 | 1.80 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 855.62 | 703.64 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.02 | 49328.06 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.029301 | 4783.99 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003746 | 1128.26 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029301 | 3312.12 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33598.77 | 33598.77 | 16.98 | 2.532 | 2.532 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00922 | 28.94 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4194.82 | 4194.82 | 62.54 | 0.316 | 0.316 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00924 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3138.46 | 3138.46 | 40.41 | 0.237 | 0.237 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00948 | 31.88 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2707.88 | 2707.88 | 16.49 | 0.204 | 0.204 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 24.00 | 24.00 | 0.00895 | 31.17 | 0.01447 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1592.92 | 1592.92 | 16.81 | 0.120 | 0.120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00901 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44812.57 | 44812.57 | 574.23 | 3.377 | 3.377 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00856 | 34.02 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18409.47 | 18409.47 | 97.48 | 1.389 | 1.389 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01031 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63780.88 | 63780.88 | 48.76 | 4.809 | 4.809 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01005 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10068.12 | 10068.12 | 258.01 | 1.022 | 1.022 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00869 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9960.21 | 9960.21 | 255.28 | 1.012 | 1.012 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00870 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 60576.18 | 60576.18 | 2470.09 | 6.151 | 6.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00861 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 64022.73 | 64022.73 | 2609.92 | 6.502 | 6.502 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00882 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9109.40 | 9109.40 | 233.44 | 0.925 | 0.925 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00872 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9031.52 | 9031.52 | 231.47 | 0.917 | 0.917 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00872 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20019.62 | 20019.62 | 51.41 | 1.509 | 1.509 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00954 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2643.89 | 2643.89 | 67.75 | 0.269 | 0.269 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00869 | 33.07 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2613.03 | 2613.03 | 66.97 | 0.265 | 0.265 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00869 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11973.57 | 11973.57 | 488.11 | 1.216 | 1.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00876 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29584.00 | 29584.00 | 89.20 | 2.232 | 2.232 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01043 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30997.98 | 30997.98 | 93.46 | 2.339 | 2.339 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01034 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30614.90 | 30614.90 | 296.36 | 2.313 | 2.313 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10108.02 | 10108.02 | 24.53 | 0.762 | 0.762 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00908 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1415.62 | 1415.62 | 0.72 | 0.063 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2801.34 | 2801.34 | 41.77 | 0.125 | 0.125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 920.57 | 920.57 | 11.85 | 0.041 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00748 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1738.11 | 1738.11 | 10.58 | 0.077 | 0.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00736 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1099.13 | 1099.13 | 11.60 | 0.049 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2250.65 | 2250.65 | 28.84 | 0.100 | 0.100 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00733 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 7043.52 | 7043.52 | 37.29 | 0.313 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00760 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16644.77 | 16644.77 | 12.72 | 0.740 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6286.23 | 6286.23 | 161.09 | 0.281 | 0.281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6298.66 | 6298.66 | 161.43 | 0.282 | 0.282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 36024.48 | 36024.48 | 1468.96 | 1.611 | 1.611 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00757 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 36271.22 | 36271.22 | 1478.61 | 1.622 | 1.622 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00757 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6260.74 | 6260.74 | 160.44 | 0.280 | 0.280 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00753 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6273.18 | 6273.18 | 160.78 | 0.281 | 0.281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9811.23 | 9811.23 | 25.20 | 0.436 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1905.04 | 1905.04 | 48.82 | 0.085 | 0.085 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00761 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1909.97 | 1909.97 | 48.95 | 0.085 | 0.085 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00761 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9107.97 | 9107.97 | 371.29 | 0.407 | 0.407 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6204.41 | 6204.41 | 18.71 | 0.276 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6335.61 | 6335.61 | 19.10 | 0.282 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2087.27 | 2087.27 | 20.21 | 0.093 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00656 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6496.39 | 6496.39 | 15.76 | 0.289 | 0.289 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00775 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.02 | 22.02 | 7.38 | 7.38 | 22.0152 | 11.6668 | 22.0152 | 0.5299 | 0.3000 |
FLR_3_DOAS | 17.65 | 2.05 | 4.93 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8207.893 | 8207.893 | 1.334375 | 0.00007181 | 173.031 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8207.89 | 8207.89 | 1.334375 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00795992 | 49.6157 | 1415.62 | 0.00 | 8253.85 | 8253.85 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3648.721 | 3648.721 | 0.166623 | 0.00003192 | 92.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3648.72 | 3648.72 | 0.166623 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754793 | 47.0805 | 2801.34 | 0.00 | 3667.47 | 3667.47 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1554.521 | 1554.521 | 0.124661 | 0.00001360 | 35.072 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1554.52 | 1554.52 | 0.124661 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00747622 | 46.6372 | 920.57 | 0.00 | 1562.92 | 1562.92 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2284.857 | 2284.857 | 0.107535 | 0.00001999 | 57.255 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2284.86 | 2284.86 | 0.107535 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00735916 | 45.9156 | 1738.11 | 0.00 | 2296.63 | 2296.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1420.783 | 1420.783 | 0.063258 | 0.00001243 | 36.165 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1420.78 | 1420.78 | 0.063258 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740952 | 46.2261 | 1099.13 | 0.00 | 1428.07 | 1428.07 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11298.327 | 11298.327 | 1.779806 | 0.00009884 | 238.666 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11298.33 | 11298.33 | 1.779806 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00732836 | 45.7270 | 2250.65 | 0.00 | 11361.54 | 11361.54 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10765.903 | 10765.903 | 0.731856 | 0.00009418 | 249.176 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 10765.90 | 10765.90 | 0.731856 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00759871 | 47.3931 | 7043.52 | 0.00 | 10823.53 | 10823.53 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29532.915 | 29532.915 | 2.534106 | 0.00025837 | 660.266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 29532.91 | 29532.91 | 2.534106 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00752183 | 46.9184 | 16644.77 | 0.00 | 29692.96 | 29692.96 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11375.378 | -999.000 | 1.022470 | 0.00032533 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 11375.38 | 10879.82 | 1.022470 | 21.70 | 15.37 | 0.00869493 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00869493 | 53.7694 | 10068.12 | 0.00 | 11799.25 | 11799.25 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6286.156 | 6286.156 | 0.281097 | 0.00005499 | 179.636 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6286.16 | 6286.16 | 0.281097 | 21.11 | 14.11 | 0.00753606 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753606 | 46.6882 | 6286.23 | 0.00 | 6776.61 | 6776.61 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11260.657 | -999.000 | 1.011511 | 0.00032205 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 11260.66 | 10764.29 | 1.011511 | 21.70 | 15.37 | 0.00869735 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00869735 | 53.7841 | 9960.21 | 0.00 | 11680.07 | 11680.07 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6298.589 | 6298.589 | 0.281653 | 0.00005510 | 179.992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6298.59 | 6298.59 | 0.281653 | 21.11 | 14.11 | 0.00753693 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753693 | 46.6936 | 6298.66 | 0.00 | 6790.01 | 6790.01 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 66847.197 | -999.000 | 6.151308 | 0.00191179 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 66847.20 | 65215.45 | 6.151308 | 21.70 | 15.29 | 0.00860709 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00860709 | 53.2313 | 60576.18 | 0.00 | 69369.83 | 69369.83 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 36024.285 | 36024.285 | 1.610930 | 0.00031516 | 1029.434 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 36024.28 | 36024.28 | 1.610930 | 21.11 | 14.14 | 0.00756819 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00756819 | 46.8836 | 36024.48 | 0.00 | 38835.23 | 38835.23 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 74778.240 | -999.000 | 6.501797 | 0.00213861 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 74778.24 | 69540.64 | 6.501797 | 21.70 | 15.48 | 0.00882234 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00882234 | 54.5460 | 64022.73 | 0.00 | 77524.07 | 74301.34 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 36271.024 | 36271.024 | 1.621964 | 0.00031731 | 1036.483 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 36271.02 | 36271.02 | 1.621964 | 21.11 | 14.15 | 0.00757080 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00757080 | 46.8996 | 36271.22 | 0.00 | 39101.22 | 39101.22 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10349.404 | -999.000 | 0.925109 | 0.00029599 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10349.40 | 9852.36 | 0.925109 | 21.70 | 15.39 | 0.00871591 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00871591 | 53.8974 | 9109.40 | 0.00 | 10733.55 | 10733.55 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6260.669 | 6260.669 | 0.279957 | 0.00005477 | 178.908 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6260.67 | 6260.67 | 0.279957 | 21.11 | 14.11 | 0.00753432 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753432 | 46.6776 | 6260.74 | 0.00 | 6749.13 | 6749.13 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10266.199 | -999.000 | 0.917201 | 0.00029361 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10266.20 | 9768.92 | 0.917201 | 21.70 | 15.39 | 0.00871786 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00871786 | 53.9093 | 9031.52 | 0.00 | 10647.12 | 10647.12 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6273.109 | 6273.109 | 0.280514 | 0.00005488 | 179.264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6273.11 | 6273.11 | 0.280514 | 21.11 | 14.11 | 0.00753520 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00753520 | 46.6830 | 6273.18 | 0.00 | 6762.54 | 6762.54 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13855.769 | 13855.769 | 0.795067 | 0.00012122 | 331.123 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 13855.77 | 13855.77 | 0.795067 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763183 | 47.5958 | 9811.23 | 0.00 | 13928.34 | 13928.34 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2979.738 | -999.000 | 0.268501 | 0.00008522 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2979.74 | 2855.92 | 0.268501 | 21.70 | 15.36 | 0.00868554 | 12.80 | 11.77 | 0.00850000 | 33.07 | 0.01447082 | 23.19 | 0.0000 | 21.11 | 0.00868554 | 53.7121 | 2643.89 | 0.00 | 3090.97 | 3090.97 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1905.018 | 1905.018 | 0.085186 | 0.00001667 | 54.436 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1905.02 | 1905.02 | 0.085186 | 21.11 | 14.18 | 0.00761167 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00761167 | 47.1510 | 1905.04 | 0.00 | 2053.65 | 2053.65 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2946.825 | -999.000 | 0.265367 | 0.00008428 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2946.83 | 2822.87 | 0.265367 | 21.70 | 15.36 | 0.00868793 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00868793 | 53.7266 | 2613.03 | 0.00 | 3056.78 | 3056.78 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1909.944 | 1909.944 | 0.085407 | 0.00001671 | 54.577 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1909.94 | 1909.94 | 0.085407 | 21.11 | 14.18 | 0.00761263 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00761263 | 47.1569 | 1909.97 | 0.00 | 2058.96 | 2058.96 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13749.609 | -999.000 | 1.215993 | 0.00039323 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 13749.61 | 12971.66 | 1.215993 | 21.70 | 15.42 | 0.00875666 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00875666 | 54.1462 | 11973.57 | 0.00 | 14258.27 | 13895.22 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9107.892 | 9107.892 | 0.407280 | 0.00007968 | 260.259 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 9107.89 | 9107.89 | 0.407280 | 21.11 | 14.20 | 0.00762505 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00762505 | 47.2324 | 9107.97 | 0.00 | 9818.53 | 9818.53 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12189.329 | 12189.329 | 1.176392 | 0.00010664 | 268.672 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 12189.33 | 12189.33 | 1.176392 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770216 | 48.0295 | 6204.41 | 0.00 | 12255.76 | 12255.76 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12606.525 | 12606.525 | 1.232599 | 0.00011029 | 277.462 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12606.52 | 12606.52 | 1.232599 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770802 | 48.0657 | 6335.61 | 0.00 | 12675.27 | 12675.27 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8272.439 | 8272.439 | 1.219107 | 0.00007237 | 175.542 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8272.44 | 8272.44 | 1.219107 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00656178 | 40.9998 | 2087.27 | 0.00 | 8318.65 | 8318.65 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8538.916 | 8538.916 | 0.401433 | 0.00007470 | 214.038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 8538.92 | 8538.92 | 0.401433 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00774863 | 48.3154 | 6496.39 | 0.00 | 8582.90 | 8582.90 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 728811.076 | -999.000 | 22.015179 | 0.02084390 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 728811.08 | 483630.88 | 22.015179 | 29.50 | 20.69 | 0.01223644 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 52.9701 | 23.99 | 0.00968688 | 50.2040 | 291932.56 | 0.00 | 743867.67 | 482493.98 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 177214.680 | 177214.680 | 6.604554 | 0.00155035 | 2991.030 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 177214.68 | 177214.68 | 6.604554 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 176.5670 | 21.02 | 0.00759615 | 47.3224 | 64127.92 | 0.00 | 159370.92 | 159370.92 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00871922 | 53.9163 | 173426.47 | 0.00 | 92683.44 | 56170.47 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00756973 | 46.8931 | 110337.50 | 0.00 | 14849.77 | 14849.77 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8207.893 | 8207.893 | 1.334375 | 0.00007181 | 173.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.8788 | 1.916654 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8207.89 | 8207.89 | 1.0000 | 1.54917771 | 1.334375 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07179891 | 60.00 | 32.22 | 27.78 | 0.000 | 8207.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795992 | 21.00 | 0.00795992 | 49.6157 | 1415.62 | 0.00 | 8253.85 | 8253.85 | 1.54917771 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.82 | 15.16 | 0.00800000 | 42262.6 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3648.721 | 3648.721 | 0.166623 | 0.00003192 | 92.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.8352 | 0.852026 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3648.72 | 3648.72 | 1.0000 | 0.19344588 | 0.166623 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03191735 | 60.00 | 32.22 | 27.78 | 0.000 | 3648.72 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00754793 | 21.00 | 0.00754793 | 47.0805 | 2801.34 | 0.00 | 3667.47 | 3667.47 | 0.19344588 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.19 | 19.72 | 0.00800000 | 55893.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1554.521 | 1554.521 | 0.124661 | 0.00001360 | 35.072 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.3558 | 0.363002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1554.52 | 1554.52 | 1.0000 | 0.14472803 | 0.124661 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01359824 | 60.00 | 32.22 | 27.78 | 0.000 | 1554.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00747622 | 21.00 | 0.00747622 | 46.6372 | 920.57 | 0.00 | 1562.92 | 1562.92 | 0.14472803 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.19 | 17.08 | 0.00800000 | 47733.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2284.857 | 2284.857 | 0.107535 | 0.00001999 | 57.255 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.5230 | 0.533545 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2284.86 | 2284.86 | 1.0000 | 0.12484581 | 0.107535 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01998689 | 60.00 | 32.22 | 27.78 | 0.000 | 2284.86 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00735916 | 21.00 | 0.00735916 | 45.9156 | 1738.11 | 0.00 | 2296.63 | 2296.63 | 0.12484581 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.64 | 19.54 | 0.00800000 | 55330.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1420.783 | 1420.783 | 0.063258 | 0.00001243 | 36.165 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.3252 | 0.331772 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1420.78 | 1420.78 | 1.0000 | 0.07344123 | 0.063258 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01242836 | 60.00 | 32.22 | 27.78 | 0.000 | 1420.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00740952 | 21.00 | 0.00740952 | 46.2261 | 1099.13 | 0.00 | 1428.07 | 1428.07 | 0.07344123 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.67 | 19.87 | 0.00800000 | 56379.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11298.327 | 11298.327 | 1.779806 | 0.00009884 | 238.666 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 2.5863 | 2.638312 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11298.33 | 11298.33 | 1.0000 | 2.06631342 | 1.779806 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09883261 | 60.00 | 32.22 | 27.78 | 0.000 | 11298.33 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00732836 | 21.00 | 0.00732836 | 45.7270 | 2250.65 | 0.00 | 11361.54 | 11361.54 | 2.06631342 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.99 | 15.22 | 0.00800000 | 42433.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10765.903 | 10765.903 | 0.731856 | 0.00009418 | 249.176 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 2.4644 | 2.513984 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 10765.90 | 10765.90 | 1.0000 | 0.84966772 | 0.731856 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09417521 | 60.00 | 32.22 | 27.78 | 0.000 | 10765.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00759871 | 21.00 | 0.00759871 | 47.3931 | 7043.52 | 0.00 | 10823.53 | 10823.53 | 0.84966772 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.09 | 17.73 | 0.00800000 | 49673.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29532.915 | 29532.915 | 2.534106 | 0.00025837 | 660.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 6.7603 | 6.896336 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 29532.91 | 29532.91 | 1.0000 | 2.94203715 | 2.534106 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.25834047 | 60.00 | 32.22 | 27.78 | 0.000 | 29532.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00752183 | 21.00 | 0.00752183 | 46.9184 | 16644.77 | 0.00 | 29692.96 | 29692.96 | 2.94203715 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.50 | 16.84 | 0.00800000 | 47027.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11375.378 | -999.000 | 1.022470 | 0.00032533 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0034 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.022470 | 1.18706404 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 1.1103 | 1.110290 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 11375.38 | 10879.82 | 1.0000 | 1.18706404 | 1.022470 | 21.70 | 15.37 | 0.00869493 | 43905.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.32529511 | 6.70 | 15.03 | 8.33 | 0.000 | 11375.38 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00869493 | 21.11 | 0.00869493 | 53.7694 | 10068.12 | 0.00 | 11799.25 | 11799.25 | 1.18706404 | 21.70 | 15.73 | 0.00869493 | 43905.0 | 11.97 | 11.95 | 0.00869493 | 33965.1 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6286.156 | 6286.156 | 0.281097 | 0.00005499 | 179.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.022470 | 1.18706404 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.4389 | 1.467903 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6286.16 | 6286.16 | 1.0000 | 0.32634712 | 0.281097 | 21.11 | 14.11 | 0.00753606 | 40355.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05498843 | 60.00 | 32.22 | 27.78 | 0.000 | 6286.16 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753606 | 21.11 | 0.00753606 | 46.6882 | 6286.23 | 0.00 | 6776.61 | 6776.61 | 0.32634712 | 16.60 | 12.70 | 0.00753606 | 35760.1 | 36.98 | 19.92 | 0.00753606 | 56525.2 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11260.657 | -999.000 | 1.011511 | 0.00032205 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0079 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.011511 | 1.17434057 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 1.0991 | 1.099093 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 11260.66 | 10764.29 | 1.0000 | 1.17434057 | 1.011511 | 21.70 | 15.37 | 0.00869735 | 43911.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.32201451 | 6.70 | 15.03 | 8.33 | 0.000 | 11260.66 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00869735 | 21.11 | 0.00869735 | 53.7841 | 9960.21 | 0.00 | 11680.07 | 11680.07 | 1.17434057 | 21.70 | 15.74 | 0.00869735 | 43911.1 | 11.96 | 11.95 | 0.00869735 | 33965.1 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6298.589 | 6298.589 | 0.281653 | 0.00005510 | 179.992 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.011511 | 1.17434057 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.4418 | 1.470806 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6298.59 | 6298.59 | 1.0000 | 0.32699256 | 0.281653 | 21.11 | 14.11 | 0.00753693 | 40357.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05509718 | 60.00 | 32.22 | 27.78 | 0.000 | 6298.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753693 | 21.11 | 0.00753693 | 46.6936 | 6298.66 | 0.00 | 6790.01 | 6790.01 | 0.32699256 | 16.60 | 12.70 | 0.00753693 | 35762.3 | 36.98 | 19.92 | 0.00753693 | 56527.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66847.197 | -999.000 | 6.151308 | 0.00191179 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8402 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.151308 | 7.14152484 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 6.5247 | 6.524601 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 66847.20 | 65215.45 | 1.0000 | 7.14152484 | 6.151308 | 21.70 | 15.29 | 0.00860709 | 43682.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.91159066 | 6.70 | 15.03 | 8.33 | 0.000 | 66847.20 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00860709 | 21.11 | 0.00860709 | 53.2313 | 60576.18 | 0.00 | 69369.83 | 69369.83 | 7.14152484 | 21.70 | 15.66 | 0.00860709 | 43682.5 | 12.19 | 11.95 | 0.00860709 | 33969.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36024.285 | 36024.285 | 1.610930 | 0.00031516 | 1029.434 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.151308 | 7.14152484 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 8.2462 | 8.412159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 36024.28 | 36024.28 | 1.0000 | 1.87025218 | 1.610930 | 21.11 | 14.14 | 0.00756819 | 40437.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31512401 | 60.00 | 32.22 | 27.78 | 0.000 | 36024.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00756819 | 21.11 | 0.00756819 | 46.8836 | 36024.48 | 0.00 | 38835.23 | 38835.23 | 1.87025218 | 16.60 | 12.73 | 0.00756819 | 35841.5 | 36.98 | 19.95 | 0.00756819 | 56606.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74778.240 | -999.000 | 6.501797 | 0.00213861 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2403 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.501797 | 7.54843341 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 7.2988 | 7.298708 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 74778.24 | 69540.64 | 1.0000 | 7.54843341 | 6.501797 | 21.70 | 15.48 | 0.00882234 | 44228.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.13839011 | 6.70 | 15.03 | 8.33 | 0.000 | 74778.24 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00882234 | 21.11 | 0.00882234 | 54.5460 | 64022.73 | 0.00 | 77524.07 | 74301.34 | 7.54843341 | 21.70 | 15.85 | 0.00882234 | 44228.7 | 12.06 | 11.95 | 0.00865314 | 33958.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36271.024 | 36271.024 | 1.621964 | 0.00031731 | 1036.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.501797 | 7.54843341 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 8.3027 | 8.469776 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 36271.02 | 36271.02 | 1.0000 | 1.88306200 | 1.621964 | 21.11 | 14.15 | 0.00757080 | 40444.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.31728237 | 60.00 | 32.22 | 27.78 | 0.000 | 36271.02 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00757080 | 21.11 | 0.00757080 | 46.8996 | 36271.22 | 0.00 | 39101.22 | 39101.22 | 1.88306200 | 16.60 | 12.73 | 0.00757080 | 35848.1 | 36.98 | 19.95 | 0.00757080 | 56612.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10349.404 | -999.000 | 0.925109 | 0.00029599 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0424 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.925109 | 1.07403017 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 1.0102 | 1.010151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10349.40 | 9852.36 | 1.0000 | 1.07403017 | 0.925109 | 21.70 | 15.39 | 0.00871591 | 43958.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.29595592 | 6.70 | 15.03 | 8.33 | 0.000 | 10349.40 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00871591 | 21.11 | 0.00871591 | 53.8974 | 9109.40 | 0.00 | 10733.55 | 10733.55 | 1.07403017 | 21.70 | 15.75 | 0.00871591 | 43958.2 | 11.92 | 11.92 | 0.00871591 | 33964.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6260.669 | 6260.669 | 0.279957 | 0.00005477 | 178.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.925109 | 1.07403017 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.4331 | 1.461951 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6260.67 | 6260.67 | 1.0000 | 0.32502394 | 0.279957 | 21.11 | 14.11 | 0.00753432 | 40350.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05476547 | 60.00 | 32.22 | 27.78 | 0.000 | 6260.67 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753432 | 21.11 | 0.00753432 | 46.6776 | 6260.74 | 0.00 | 6749.13 | 6749.13 | 0.32502394 | 16.60 | 12.70 | 0.00753432 | 35755.7 | 36.98 | 19.92 | 0.00753432 | 56520.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10266.199 | -999.000 | 0.917201 | 0.00029361 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0461 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.917201 | 1.06484848 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 1.0020 | 1.002029 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10266.20 | 9768.92 | 1.0000 | 1.06484848 | 0.917201 | 21.70 | 15.39 | 0.00871786 | 43963.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.29357655 | 6.70 | 15.03 | 8.33 | 0.000 | 10266.20 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00871786 | 21.11 | 0.00871786 | 53.9093 | 9031.52 | 0.00 | 10647.12 | 10647.12 | 1.06484848 | 21.70 | 15.75 | 0.00871786 | 43963.2 | 11.91 | 11.91 | 0.00871786 | 33964.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6273.109 | 6273.109 | 0.280514 | 0.00005488 | 179.264 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.917201 | 1.06484848 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.4360 | 1.464856 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6273.11 | 6273.11 | 1.0000 | 0.32566978 | 0.280514 | 21.11 | 14.11 | 0.00753520 | 40353.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05487430 | 60.00 | 32.22 | 27.78 | 0.000 | 6273.11 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00753520 | 21.11 | 0.00753520 | 46.6830 | 6273.18 | 0.00 | 6762.54 | 6762.54 | 0.32566978 | 16.60 | 12.70 | 0.00753520 | 35758.0 | 36.98 | 19.92 | 0.00753520 | 56523.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13855.769 | 13855.769 | 0.795067 | 0.00012122 | 331.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 3.1717 | 3.235510 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 13855.77 | 13855.77 | 1.0000 | 0.92305377 | 0.795067 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.12120394 | 60.00 | 32.22 | 27.78 | 0.000 | 13855.77 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00763183 | 21.00 | 0.00763183 | 47.5958 | 9811.23 | 0.00 | 13928.34 | 13928.34 | 0.92305377 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.40 | 18.50 | 0.00800000 | 52024.1 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2979.738 | -999.000 | 0.268501 | 0.00008522 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9860 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.268501 | 0.31172283 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 0.2908 | 0.290836 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2979.74 | 2855.92 | 1.0000 | 0.31172283 | 0.268501 | 21.70 | 15.36 | 0.00868554 | 43881.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.08520983 | 6.70 | 15.03 | 8.33 | 0.000 | 2979.74 | 33.07 | 0.01447082 | 23.19 | 0.00000000 | 0.0000 | 21.11 | 0.00868554 | 21.11 | 0.00868554 | 53.7121 | 2643.89 | 0.00 | 3090.97 | 3090.97 | 0.31172283 | 21.70 | 15.73 | 0.00868554 | 43881.1 | 11.99 | 11.95 | 0.00868554 | 33965.4 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1905.018 | 1905.018 | 0.085186 | 0.00001667 | 54.436 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.268501 | 0.31172283 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.4361 | 0.444848 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1905.02 | 1905.02 | 1.0000 | 0.09889944 | 0.085186 | 21.11 | 14.18 | 0.00761167 | 40547.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01666423 | 60.00 | 32.22 | 27.78 | 0.000 | 1905.02 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00761167 | 21.11 | 0.00761167 | 47.1510 | 1905.04 | 0.00 | 2053.65 | 2053.65 | 0.09889944 | 16.60 | 12.77 | 0.00761167 | 35951.6 | 36.98 | 19.98 | 0.00761167 | 56716.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2946.825 | -999.000 | 0.265367 | 0.00008428 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9904 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.265367 | 0.30808449 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 0.2876 | 0.287624 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2946.83 | 2822.87 | 1.0000 | 0.30808449 | 0.265367 | 21.70 | 15.36 | 0.00868793 | 43887.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.08426866 | 6.70 | 15.03 | 8.33 | 0.000 | 2946.83 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00868793 | 21.11 | 0.00868793 | 53.7266 | 2613.03 | 0.00 | 3056.78 | 3056.78 | 0.30808449 | 21.70 | 15.73 | 0.00868793 | 43887.2 | 11.99 | 11.95 | 0.00868793 | 33965.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1909.944 | 1909.944 | 0.085407 | 0.00001671 | 54.577 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.265367 | 0.30808449 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 0.4372 | 0.445998 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1909.94 | 1909.94 | 1.0000 | 0.09915520 | 0.085407 | 21.11 | 14.18 | 0.00761263 | 40549.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01670732 | 60.00 | 32.22 | 27.78 | 0.000 | 1909.94 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00761263 | 21.11 | 0.00761263 | 47.1569 | 1909.97 | 0.00 | 2058.96 | 2058.96 | 0.09915520 | 16.60 | 12.77 | 0.00761263 | 35954.0 | 36.98 | 19.98 | 0.00761263 | 56719.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13749.609 | -999.000 | 1.215993 | 0.00039323 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1182 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.215993 | 1.41173988 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 1.3421 | 1.342027 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 13749.61 | 12971.66 | 1.0000 | 1.41173988 | 1.215993 | 21.70 | 15.42 | 0.00875666 | 44061.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.39318961 | 6.70 | 15.03 | 8.33 | 0.000 | 13749.61 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00875666 | 21.11 | 0.00875666 | 54.1462 | 11973.57 | 0.00 | 14258.27 | 13895.22 | 1.41173988 | 21.70 | 15.79 | 0.00875666 | 44061.7 | 12.06 | 11.95 | 0.00865475 | 33961.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9107.892 | 9107.892 | 0.407280 | 0.00007968 | 260.259 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.215993 | 1.41173988 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 2.0849 | 2.126816 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 9107.89 | 9107.89 | 1.0000 | 0.47284215 | 0.407280 | 21.11 | 14.20 | 0.00762505 | 40581.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07967169 | 60.00 | 32.22 | 27.78 | 0.000 | 9107.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00762505 | 21.11 | 0.00762505 | 47.2324 | 9107.97 | 0.00 | 9818.53 | 9818.53 | 0.47284215 | 16.60 | 12.79 | 0.00762505 | 35985.4 | 36.98 | 19.99 | 0.00762505 | 56750.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12189.329 | 12189.329 | 1.176392 | 0.00010664 | 268.672 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 2.7902 | 2.846374 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 12189.33 | 12189.33 | 1.0000 | 1.36576402 | 1.176392 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10662669 | 60.00 | 32.22 | 27.78 | 0.000 | 12189.33 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770216 | 21.00 | 0.00770216 | 48.0295 | 6204.41 | 0.00 | 12255.76 | 12255.76 | 1.36576402 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.40 | 16.46 | 0.00800000 | 45908.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12606.525 | 12606.525 | 1.232599 | 0.00011029 | 277.462 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 2.8857 | 2.943794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 12606.52 | 12606.52 | 1.0000 | 1.43101907 | 1.232599 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11027613 | 60.00 | 32.22 | 27.78 | 0.000 | 12606.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770802 | 21.00 | 0.00770802 | 48.0657 | 6335.61 | 0.00 | 12675.27 | 12675.27 | 1.43101907 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.29 | 16.42 | 0.00800000 | 45792.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8272.439 | 8272.439 | 1.219107 | 0.00007237 | 175.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.8936 | 1.931727 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8272.44 | 8272.44 | 1.0000 | 1.41535442 | 1.219107 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07236353 | 60.00 | 32.22 | 27.78 | 0.000 | 8272.44 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.51 | 0.00656178 | 21.00 | 0.00656178 | 40.9998 | 2087.27 | 0.00 | 8318.65 | 8318.65 | 1.41535442 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.36 | 15.36 | 0.00800000 | 42812.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8538.916 | 8538.916 | 0.401433 | 0.00007470 | 214.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 1.9546 | 1.993953 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 8538.92 | 8538.92 | 1.0000 | 0.46605429 | 0.401433 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07469454 | 60.00 | 32.22 | 27.78 | 0.000 | 8538.92 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00774863 | 21.00 | 0.00774863 | 48.3154 | 6496.39 | 0.00 | 8582.90 | 8582.90 | 0.46605429 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.66 | 19.55 | 0.00800000 | 55350.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 728811.076 | -999.000 | 22.015179 | 0.02084390 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.5869 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.015179 | 25.55910582 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 71.1367 | 71.136721 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 728811.08 | 483630.88 | 1.0000 | 25.55910582 | 22.015179 | 29.50 | 20.69 | 0.01223644 | 60920.0 | 10.92 | 10.92 | 0.00850000 | 32405.3 | 20.84177823 | 6.70 | 15.03 | 8.33 | 49328.059 | 679483.02 | 34.40 | 0.01447326 | 23.54 | 11.66146000 | 52.9701 | 23.99 | 0.00971708 | 23.99 | 0.00968688 | 50.2040 | 291932.56 | 0.00 | 743867.67 | 482493.98 | 25.55910582 | 29.50 | 21.11 | 0.01223644 | 60920.0 | 11.13 | 11.07 | 0.00818103 | 31816.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 177214.680 | 177214.680 | 6.604554 | 0.00155035 | 2991.030 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.015179 | 25.55910582 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 40.5656 | 41.382030 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 177214.68 | 177214.68 | 1.0000 | 7.66773175 | 6.604554 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 1.55019318 | 60.00 | 32.22 | 27.78 | 0.000 | 177214.68 | -6.30 | 0.00229779 | -6.30 | 11.66146000 | 176.5670 | 20.98 | 0.00759331 | 21.02 | 0.00759615 | 47.3224 | 64127.92 | 0.00 | 159370.92 | 159370.92 | 7.66773175 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 29.29819939 | 15.03 | 6.70 | 8.33 | 1024521.61 | 8.8979 | 8.897920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 2.60693021 | 6.70 | 15.03 | 8.33 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00872448 | 21.11 | 0.00871922 | 53.9163 | 173426.47 | 0.00 | 92683.44 | 56170.47 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.54 | 11.47 | 0.00839502 | 32771.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 3.74605401 | 54.44 | 82.22 | 27.78 | 436859.18 | 3.7798 | 3.855870 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.14444298 | 60.00 | 32.22 | 27.78 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00756785 | 21.11 | 0.00756973 | 46.8931 | 110337.50 | 0.00 | 14849.77 | 14849.77 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 22.02 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 97.83 | 8705.33 | 97.83 |
RETAIL_1_FLR_1 | 1586.00 | 7652.50 | 1001.67 |
RETAIL_2_FLR_1 | 336.50 | 8151.83 | 95.83 |
MECH_FLR_1 | 1015.50 | 8681.67 | 1015.50 |
STORAGE_FLR_1 | 1112.17 | 8759.83 | 1112.17 |
LAUNDRY_FLR_1 | 4770.00 | 3969.00 | 1774.00 |
CAFE_FLR_1 | 1821.17 | 6576.00 | 415.83 |
LOBBY_FLR_1 | 721.17 | 7488.50 | 10.33 |
ROOM_1_FLR_3 | 1338.00 | 8234.00 | 1334.17 |
ROOM_2_FLR_3 | 2174.83 | 8151.00 | 2126.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1288.67 | 8746.83 | 1288.17 |
ROOM_5_FLR_3 | 1261.33 | 8168.83 | 1259.50 |
ROOM_6_FLR_3 | 2146.17 | 8115.50 | 2085.00 |
CORRIDOR_FLR_3 | 605.00 | 8760.00 | 605.00 |
ROOM_1_FLR_6 | 1915.17 | 8054.17 | 1843.83 |
ROOM_2_FLR_6 | 2744.17 | 7934.17 | 2607.50 |
ROOM_3_MULT9_FLR_6 | 813.67 | 8166.50 | 808.17 |
BANQUET_FLR_6 | 3785.67 | 4626.83 | 640.17 |
DINING_FLR_6 | 4542.17 | 3442.50 | 291.33 |
KITCHEN_FLR_6 | 7676.00 | 6894.00 | 6105.33 |
CORRIDOR_FLR_6 | 973.50 | 8192.50 | 872.33 |
Facility | 8459.67 | 8760.00 | 7735.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10.17 | 0.00 | 10.17 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 2.83 | 0.17 | 2.83 | 0.17 |
ROOM_2_FLR_3 | 5.67 | 2.33 | 5.67 | 2.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.67 | 12.00 | 1.67 | 12.00 |
ROOM_5_FLR_3 | 2.33 | 0.00 | 2.33 | 0.00 |
ROOM_6_FLR_3 | 4.67 | 22.50 | 4.67 | 22.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 2.50 | 3.33 | 2.50 | 3.33 |
ROOM_2_FLR_6 | 5.50 | 6.33 | 5.50 | 6.33 |
ROOM_3_MULT9_FLR_6 | 1.17 | 8.00 | 1.17 | 8.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 2.17 | 0.00 | 2.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 19.00 | 40.67 | 19.00 | 40.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.993 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.250 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.455 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.592 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.604 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.947 | 0.144 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.521 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.758 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.175 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.078 | 0.000 | 0.108 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.175 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.068 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.601 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.175 | 0.000 | 0.081 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.175 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.142 | 0.000 | 0.130 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.336 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.591 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.221 | 0.145 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.146 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.866 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.991 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.276 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.519 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.529 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.158 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.135 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.542 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.527 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.088 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.288 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.506 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.008 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41440411.86 | 0.00 | 41440411.86 | 0.00 | 41440411.86 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5177817.69 | 0.00 | 5177817.69 | 310220.85 | 5488038.55 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3872408.06 | 0.00 | 3872408.06 | 119745.64 | 3992153.70 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3339617.89 | 0.00 | 3339617.89 | 283007.56 | 3622625.45 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1964548.54 | 0.00 | 1964548.54 | 163279.77 | 2127828.31 | 1821682.01 | 832.72 | 301.52 | 7625.76 | 0.00 |
LAUNDRY_FLR_1 | 58726210.55 | 0.00 | 58726210.55 | 386432.37 | 59112642.92 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22746411.72 | 0.00 | 22746411.72 | 685760.76 | 23432172.49 | 21330615.53 | 1016.99 | 136.45 | 7606.56 | 0.00 |
LOBBY_FLR_1 | 78720213.42 | 0.00 | 78720213.42 | 1959375.13 | 80679588.55 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 69845.79 | 1530002.50 | 180061.18 | 1710063.68 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 70339.59 | 1530325.23 | 180047.44 | 1710372.66 | 1946647.51 | 2190.00 | 5692.79 | 877.21 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 4132.12 | 1104044.09 | 50239.09 | 1154283.18 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 406.33 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 69677.63 | 19873506.93 | 50252.83 | 19923759.75 | 26405105.73 | 2190.00 | 5735.63 | 834.37 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 69867.71 | 1530024.42 | 180061.18 | 1710085.60 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 69736.08 | 1529721.72 | 180047.44 | 1709769.15 | 1946647.51 | 2190.00 | 5688.25 | 881.75 | 0.00 |
CORRIDOR_FLR_3 | 24691633.62 | 0.00 | 24691633.62 | 217730.19 | 24909363.80 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 83632.77 | 448671.95 | 180098.20 | 628770.15 | 486718.90 | 1994.56 | 5687.97 | 1077.47 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 82559.99 | 447556.40 | 180084.46 | 627640.86 | 486661.88 | 1996.66 | 5701.23 | 1062.11 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 83715.01 | 2428905.32 | 92144.54 | 2521049.87 | 3126920.42 | 2190.00 | 5684.17 | 885.83 | 0.00 |
BANQUET_FLR_6 | 37698185.15 | 0.00 | 37698185.15 | 439754.55 | 38137939.70 | 37458366.31 | 404.74 | 7169.94 | 1185.33 | 0.00 |
DINING_FLR_6 | 39891446.67 | 0.00 | 39891446.67 | 439754.55 | 40331201.22 | 37458366.31 | 0.00 | 0.06 | 8759.94 | 0.00 |
KITCHEN_FLR_6 | 49263664.15 | 0.00 | 49263664.15 | 393682.28 | 49657346.42 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12467668.42 | 0.00 | 12467668.42 | 385314.24 | 12852982.66 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7648325.88 | 0.21E+10 | 18144986.26 | 0.21E+10 | 0.43E+10 | 8760.00 | 8521.31 | 8760.00 | 406.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3141 | 0.0000 | 1.3141 | 0.0000 | 1.3141 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1642 | 0.0000 | 0.1642 | 0.0098 | 0.1740 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1228 | 0.0000 | 0.1228 | 0.0038 | 0.1266 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1059 | 0.0000 | 0.1059 | 0.0090 | 0.1149 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0623 | 0.0000 | 0.0623 | 0.0052 | 0.0675 | 0.0578 | 832.72 | 301.52 | 7625.76 |
LAUNDRY_FLR_1 | 1.8622 | 0.0000 | 1.8622 | 0.0123 | 1.8744 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7213 | 0.0000 | 0.7213 | 0.0217 | 0.7430 | 0.6764 | 1016.99 | 136.45 | 7606.56 |
LOBBY_FLR_1 | 2.4962 | 0.0000 | 2.4962 | 0.0621 | 2.5583 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0057 | 0.0542 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0057 | 0.0542 | 0.0617 | 2190.00 | 5692.79 | 877.21 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0022 | 0.6302 | 0.0016 | 0.6318 | 0.8373 | 2190.00 | 5735.63 | 834.37 |
ROOM_5_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0057 | 0.0542 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0057 | 0.0542 | 0.0617 | 2190.00 | 5688.25 | 881.75 |
CORRIDOR_FLR_3 | 0.7830 | 0.0000 | 0.7830 | 0.0069 | 0.7899 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0027 | 0.0142 | 0.0057 | 0.0199 | 0.0154 | 1994.56 | 5687.97 | 1077.47 |
ROOM_2_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0057 | 0.0199 | 0.0154 | 1996.66 | 5701.23 | 1062.11 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0027 | 0.0770 | 0.0029 | 0.0799 | 0.0992 | 2190.00 | 5684.17 | 885.83 |
BANQUET_FLR_6 | 1.1954 | 0.0000 | 1.1954 | 0.0139 | 1.2093 | 1.1878 | 404.74 | 7169.94 | 1185.33 |
DINING_FLR_6 | 1.2649 | 0.0000 | 1.2649 | 0.0139 | 1.2789 | 1.1878 | 0.00 | 0.06 | 8759.94 |
KITCHEN_FLR_6 | 1.5621 | 0.0000 | 1.5621 | 0.0125 | 1.5746 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3953 | 0.0000 | 0.3953 | 0.0122 | 0.4076 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.5580 | 0.2326 | 63.7905 | 0.4543 | 64.2448 | 73.9670 | 8760.00 | 8521.31 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40192371.46 | 603506.69 | 40795878.15 | 64690340.46 | 8759.50 | 0.17 | 0.33 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.2414 | 0.0000 | 16.2414 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2745 | 0.0191 | 1.2936 | 2.0513 | 8759.50 | 0.17 | 0.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4482.94 | 0.00 | 0.00 | 0.00 | 4277.06 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 16.3471 | 0.0000 | 0.0000 | 0.0000 | 16.1344 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6099 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 3997 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
Electricity:Building | 2448.61 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.52 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.61 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.23 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.23 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.23 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.06 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.06 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.51 | 1102.74 | 11-FEB-23:30 | 3253.46 | 20-JAN-07:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2038.38 | 2713.24 | 08-MAR-02:10 | 204925.01 | 08-JUL-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.21 | 0.00 | 01-JAN-11:10 | 1901.75 | 15-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.20 | 927.69 | 20-MAR-02:30 | 1192.36 | 17-FEB-14:10 |
Fans:Electricity | 454.56 | 10932.11 | 07-JAN-08:10 | 25586.54 | 07-JUL-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 627.93 | 11780.66 | 01-FEB-15:00 | 36573.17 | 07-JUL-18:20 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
ElectricityPurchased:Plant | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
Cogeneration:ElectricityPurchased | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
ElectricityNet:Plant | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
Cogeneration:ElectricityNet | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
General:Cogeneration:ElectricityNet | 5927.96 | 69540.75 | 08-MAR-02:10 | 413922.72 | 18-AUG-19:20 |
General:Fans:Electricity | 454.56 | 10932.11 | 07-JAN-08:10 | 25586.54 | 07-JUL-18:20 |
ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 151.60 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
General:HeatRecovery:Electricity | 151.60 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
WaterSystems:Electricity | 90.76 | 1086.77 | 21-JUL-00:20 | 4738.99 | 04-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.77 | 21-JUL-00:20 | 4738.99 | 04-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1794.90 | 0.00 | 01-JAN-00:10 | 196491.06 | 08-JUL-15:20 |
General:Cooling:Electricity | 1794.90 | 0.00 | 01-JAN-00:10 | 196491.06 | 08-JUL-15:20 |
Pumps:Electricity | 98.30 | 88.96 | 27-DEC-18:50 | 4712.76 | 18-JUL-19:00 |
General:Pumps:Electricity | 98.30 | 88.96 | 27-DEC-18:50 | 4712.76 | 18-JUL-19:00 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5866.30 | 32848.94 | 03-AUG-00:10 | 578340.49 | 03-JAN-18:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4077.46 | 15908.90 | 25-JUN-10:10 | 490159.46 | 12-FEB-17:10 |
WaterSystems:NaturalGas | 2907.84 | 15908.90 | 10-JAN-16:10 | 270809.75 | 10-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2907.84 | 15908.90 | 10-JAN-16:10 | 270809.75 | 10-FEB-21:20 |
Heating:NaturalGas | 1169.62 | 0.00 | 21-FEB-20:40 | 268438.17 | 03-JAN-16:10 |
Boiler:Heating:NaturalGas | 1169.62 | 0.00 | 21-FEB-20:40 | 268438.17 | 03-JAN-16:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5764.55 | 0.00 | 01-JAN-00:10 | 640659.55 | 25-JUL-22:00 |
PlantLoopCoolingDemand:HVAC | 5764.55 | 0.00 | 01-JAN-00:10 | 640659.55 | 25-JUL-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5764.55 | 0.00 | 01-JAN-00:10 | 640659.55 | 25-JUL-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 28700.24 | 163128.72 | 29-NOV-11:20 | 2548455.43 | 06-JUL-18:10 |
EnergyTransfer:Building | 5349.66 | 74363.23 | 06-FEB-11:10 | 331839.55 | 07-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 727.70 | 9928.73 | 12-FEB-04:00 | 36054.33 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 182.18 | 3940.11 | 20-MAR-02:30 | 10329.54 | 07-JUL-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 1970.05 | 20-MAR-02:30 | 5164.77 | 07-JUL-07:20 |
General:Refrigeration:EnergyTransfer | 91.09 | 1970.05 | 20-MAR-02:30 | 5164.77 | 07-JUL-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 1970.05 | 20-MAR-02:30 | 5164.77 | 07-JUL-07:20 |
EnergyTransfer:Plant | 15032.39 | 28648.16 | 16-FEB-00:20 | 1475003.30 | 25-JUL-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.49 | 1733.08 | 20-MAR-02:30 | 2527.08 | 17-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 427.58 | 4835.84 | 16-APR-16:50 | 17344.20 | 13-OCT-21:00 |
Heating:EnergyTransfer | 95.51 | 0.00 | 01-JAN-08:10 | 73808.89 | 07-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 95.51 | 0.00 | 01-JAN-08:10 | 73808.89 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5163.06 | 64118.73 | 08-JAN-15:00 | 329138.92 | 07-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 427.58 | 4835.84 | 16-APR-16:50 | 17344.20 | 13-OCT-21:00 |
General:Cooling:EnergyTransfer | 5163.06 | 64118.73 | 08-JAN-15:00 | 329138.92 | 07-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 427.58 | 4835.84 | 16-APR-16:50 | 17344.20 | 13-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.42 | 0.05 | 03-JAN-01:40 | 2734.00 | 19-AUG-13:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.87 | 0.00 | 01-JAN-00:20 | 1147.95 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.87 | 0.00 | 01-JAN-00:20 | 1147.95 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.55 | 0.00 | 01-JAN-15:50 | 2734.00 | 19-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.55 | 0.00 | 01-JAN-15:50 | 2734.00 | 19-AUG-13:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.39 | 147.16 | 08-JAN-15:50 | 1979.28 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.39 | 147.16 | 08-JAN-15:50 | 1979.28 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.39 | 147.16 | 08-JAN-15:50 | 1979.28 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.67 | 0.01 | 13-JAN-06:00 | 1412.64 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.45 | 0.00 | 01-JAN-00:10 | 547.36 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.45 | 0.00 | 01-JAN-00:10 | 547.36 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.21 | 0.00 | 03-JAN-10:10 | 1412.64 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.21 | 0.00 | 03-JAN-10:10 | 1412.64 | 18-AUG-21:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.18 | 0.01 | 04-DEC-17:00 | 803.46 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.55 | 0.00 | 01-JAN-00:10 | 393.31 | 12-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.55 | 0.00 | 01-JAN-00:10 | 393.31 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.62 | 0.00 | 01-JAN-16:50 | 803.46 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.62 | 0.00 | 01-JAN-16:50 | 803.46 | 18-AUG-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.73 | 8839.79 | 13-FEB-05:00 | 38634.75 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.73 | 8839.79 | 13-FEB-05:00 | 38634.75 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.73 | 8839.79 | 13-FEB-05:00 | 38634.75 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 241.03 | 6.48 | 10-JAN-10:30 | 11836.73 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 436.51 | 09-JAN-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 436.51 | 09-JAN-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.02 | 0.00 | 07-JAN-16:50 | 11836.73 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.02 | 0.00 | 07-JAN-16:50 | 11836.73 | 18-AUG-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 848.35 | 5722.54 | 08-JAN-16:00 | 38596.59 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 848.35 | 5722.54 | 08-JAN-16:00 | 38596.59 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 848.35 | 5722.54 | 08-JAN-16:00 | 38596.59 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 62.43 | 0.00 | 01-JAN-08:10 | 10157.42 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.30 | 0.00 | 01-JAN-08:10 | 5701.98 | 07-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.30 | 0.00 | 01-JAN-08:10 | 5701.98 | 07-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.13 | 0.00 | 01-JAN-00:10 | 10157.42 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.13 | 0.00 | 01-JAN-00:10 | 10157.42 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.71 | 0.00 | 01-JAN-08:10 | 10311.04 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.54 | 0.00 | 01-JAN-08:10 | 6030.63 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.54 | 0.00 | 01-JAN-08:10 | 6030.63 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.17 | 0.00 | 01-JAN-00:10 | 10311.04 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.17 | 0.00 | 01-JAN-00:10 | 10311.04 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 278.02 | 0.00 | 01-JAN-00:10 | 38828.20 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3522.27 | 09-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3522.27 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 277.97 | 0.00 | 01-JAN-00:10 | 38828.20 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 277.97 | 0.00 | 01-JAN-00:10 | 38828.20 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 443.79 | 0.00 | 01-JAN-08:10 | 73785.15 | 16-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 26.49 | 0.00 | 01-JAN-00:10 | 33594.03 | 03-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 26.49 | 0.00 | 01-JAN-00:10 | 33594.03 | 03-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 417.30 | 0.00 | 01-JAN-08:10 | 73785.15 | 16-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 417.30 | 0.00 | 01-JAN-08:10 | 73785.15 | 16-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 62.42 | 0.00 | 01-JAN-08:10 | 9156.38 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.22 | 0.00 | 01-JAN-08:10 | 5814.52 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.22 | 0.00 | 01-JAN-08:10 | 5814.52 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.21 | 0.00 | 01-JAN-00:10 | 9156.38 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.21 | 0.00 | 01-JAN-00:10 | 9156.38 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 55.90 | 0.00 | 01-JAN-08:10 | 10027.77 | 04-JUN-09:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.44 | 0.00 | 01-JAN-08:10 | 5846.43 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.44 | 0.00 | 01-JAN-08:10 | 5846.43 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.47 | 0.00 | 01-JAN-00:10 | 10027.77 | 04-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.47 | 0.00 | 01-JAN-00:10 | 10027.77 | 04-JUN-09:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 219.16 | 2.05 | 12-FEB-00:50 | 9931.90 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.40 | 0.00 | 01-JAN-00:10 | 2028.71 | 07-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.40 | 0.00 | 01-JAN-00:10 | 2028.71 | 07-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 218.76 | 0.00 | 03-JAN-09:10 | 9931.90 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 218.76 | 0.00 | 03-JAN-09:10 | 9931.90 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.75 | 0.00 | 01-JAN-08:10 | 2789.97 | 08-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.06 | 0.00 | 01-JAN-08:10 | 1806.76 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.06 | 0.00 | 01-JAN-08:10 | 1806.76 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.69 | 0.00 | 01-JAN-00:10 | 2789.97 | 08-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.69 | 0.00 | 01-JAN-00:10 | 2789.97 | 08-JUL-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.42 | 0.00 | 01-JAN-08:10 | 2842.96 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.11 | 0.00 | 01-JAN-08:10 | 1818.75 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.11 | 0.00 | 01-JAN-08:10 | 1818.75 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.31 | 0.00 | 01-JAN-00:10 | 2842.96 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.31 | 0.00 | 01-JAN-00:10 | 2842.96 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 92.45 | 0.00 | 01-JAN-08:10 | 14396.93 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 0.00 | 01-JAN-08:10 | 8230.48 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 0.00 | 01-JAN-08:10 | 8230.48 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 83.72 | 0.00 | 01-JAN-00:10 | 14396.93 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 83.72 | 0.00 | 01-JAN-00:10 | 14396.93 | 10-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 463.90 | 7776.96 | 08-JAN-16:00 | 23355.63 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 463.90 | 7776.96 | 08-JAN-16:00 | 23355.63 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 463.90 | 7776.96 | 08-JAN-16:00 | 23355.63 | 07-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 500.56 | 9174.05 | 08-JAN-16:00 | 24658.84 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 500.56 | 9174.05 | 08-JAN-16:00 | 24658.84 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 500.56 | 9174.05 | 08-JAN-16:00 | 24658.84 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 636.61 | 7945.28 | 12-FEB-04:00 | 30992.45 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 636.61 | 7945.28 | 12-FEB-04:00 | 30992.45 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.10 | 0.00 | 18-JAN-10:20 | 6057.87 | 08-JUL-17:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.30 | 0.00 | 01-JAN-00:10 | 2258.67 | 12-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.30 | 0.00 | 01-JAN-00:10 | 2258.67 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.80 | 0.00 | 02-JAN-07:10 | 6057.87 | 08-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.80 | 0.00 | 02-JAN-07:10 | 6057.87 | 08-JUL-17:20 |
PlantLoopHeatingDemand:Facility | 1469.16 | 7745.07 | 19-AUG-00:10 | 239329.28 | 17-JAN-09:10 |
PlantLoopHeatingDemand:Plant | 671.59 | 7488.63 | 01-AUG-02:00 | 51950.61 | 03-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.63 | 01-AUG-02:00 | 51950.61 | 03-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 671.59 | 7488.63 | 01-AUG-02:00 | 51950.61 | 03-FEB-08:00 |
EnergyTransfer:HVAC | 8318.19 | 6720.05 | 27-DEC-18:50 | 815578.47 | 06-JUL-18:10 |
HeatingCoils:EnergyTransfer | 797.57 | 0.00 | 21-FEB-20:40 | 213748.05 | 03-JAN-16:10 |
PlantLoopHeatingDemand:HVAC | 797.57 | 0.00 | 21-FEB-20:40 | 213748.05 | 03-JAN-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 797.57 | 0.00 | 21-FEB-20:40 | 213748.05 | 03-JAN-16:10 |
CoolingCoils:EnergyTransfer | 5764.55 | 0.00 | 01-JAN-00:10 | 640659.55 | 25-JUL-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 663.54 | 0.00 | 01-JAN-08:10 | 415242.51 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1092.53 | 0.00 | 01-JAN-00:10 | 262065.14 | 07-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 671.59 | 7488.63 | 01-AUG-02:00 | 51950.61 | 03-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 671.59 | 7488.63 | 01-AUG-02:00 | 51950.61 | 03-FEB-08:00 |
Boilers:EnergyTransfer | 791.88 | 0.00 | 21-FEB-20:40 | 213853.61 | 03-JAN-16:10 |
Chillers:EnergyTransfer | 5841.46 | 0.00 | 01-JAN-00:10 | 645222.13 | 25-JUL-22:00 |
HeatRejection:EnergyTransfer | 7636.37 | 0.00 | 01-JAN-00:10 | 804058.06 | 25-JUL-22:00 |
General:HeatRejection:EnergyTransfer | 7636.37 | 0.00 | 01-JAN-00:10 | 804058.06 | 25-JUL-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -427.579 | 0.000 | 0.000 | 151.242 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -28.062 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.870 | -41.551 | 0.000 | 0.000 | 15.688 | 7.307 | 10.186 | 19.228 | 0.000 | 0.452 | 0.001 | 0.000 | -7.995 | 0.000 | -2.390 | -1.795 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -39.393 | 0.000 | 0.000 | 17.775 | 8.462 | 11.795 | 0.000 | 0.000 | 0.179 | 2.138 | 0.000 | 0.000 | 0.000 | -0.956 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.455 | -27.211 | 0.000 | 0.000 | 3.827 | 8.366 | 12.471 | 0.000 | 0.000 | 0.431 | 3.852 | 0.000 | 0.000 | 0.000 | -2.192 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.554 | -14.622 | 0.000 | 0.000 | 2.963 | 3.079 | 3.598 | 0.000 | 0.000 | 0.258 | 5.423 | 0.000 | 0.000 | 0.000 | -1.254 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -606.733 | 0.000 | 0.000 | 11.868 | 3.975 | 658.131 | 0.000 | 0.000 | 0.652 | 0.000 | 0.000 | 0.000 | 0.000 | -3.203 | -64.691 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.002 | -241.025 | 0.000 | 0.000 | 198.266 | 14.268 | 14.341 | 53.574 | 0.000 | 0.957 | 0.000 | 0.000 | -24.001 | 0.000 | -5.628 | -10.753 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -848.358 | 0.000 | 0.000 | 589.016 | 110.230 | 148.998 | 71.568 | 0.000 | 2.886 | 0.000 | 0.000 | -31.762 | 0.000 | -16.107 | -26.471 |
ROOM_1_FLR_3 | 13.309 | -43.230 | 0.000 | -11.906 | 0.000 | 0.000 | 9.700 | 9.244 | 10.478 | 39.184 | 0.000 | 1.331 | 0.000 | 0.000 | -19.762 | 0.000 | -6.255 | -2.095 |
ROOM_2_FLR_3 | 16.856 | -33.153 | 0.000 | -12.331 | 0.000 | 0.000 | 9.604 | 9.243 | 10.477 | 30.230 | 0.000 | 1.165 | 0.000 | 0.000 | -21.014 | 0.000 | -6.603 | -4.474 |
ROOM_3_MULT19_FLR_3 | 0.043 | -262.381 | 0.000 | -15.588 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 197.943 | 0.000 | 1.781 | 0.008 | 0.000 | -153.422 | 0.000 | -46.332 | -27.425 |
ROOM_4_MULT19_FLR_3 | 50.731 | -274.931 | 0.000 | -166.578 | 0.000 | 0.000 | 182.493 | 110.415 | 195.050 | 91.576 | 0.000 | 6.842 | 0.000 | 0.000 | -118.563 | 0.000 | -47.040 | -29.994 |
ROOM_5_FLR_3 | 13.206 | -43.278 | 0.000 | -11.916 | 0.000 | 0.000 | 9.693 | 9.244 | 10.478 | 38.966 | 0.000 | 1.329 | 0.001 | 0.000 | -19.072 | 0.000 | -6.280 | -2.371 |
ROOM_6_FLR_3 | 16.740 | -33.443 | 0.000 | -12.325 | 0.000 | 0.000 | 9.609 | 9.243 | 10.477 | 29.461 | 0.000 | 1.165 | 0.000 | 0.000 | -19.755 | 0.000 | -6.551 | -4.621 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.399 | -218.764 | 0.000 | 0.000 | 121.109 | 91.336 | 0.000 | 36.459 | 0.000 | 1.328 | 0.001 | 0.000 | -23.214 | 0.000 | -6.781 | -1.872 |
ROOM_1_FLR_6 | 4.909 | -11.561 | 0.000 | -2.974 | 0.000 | 0.000 | 2.428 | 2.311 | 2.620 | 9.691 | 0.000 | 0.334 | 0.000 | 0.000 | -4.909 | 0.000 | -1.592 | -1.256 |
ROOM_2_FLR_6 | 6.003 | -9.116 | 0.000 | -3.084 | 0.000 | 0.000 | 2.402 | 2.311 | 2.619 | 7.469 | 0.000 | 0.289 | 0.000 | 0.000 | -5.235 | 0.000 | -1.693 | -1.965 |
ROOM_3_MULT9_FLR_6 | 12.286 | -68.053 | 0.000 | -19.219 | 0.000 | 0.000 | 21.765 | 13.076 | 23.098 | 49.455 | 0.000 | 1.713 | 0.002 | 0.000 | -22.791 | 0.000 | -8.387 | -2.942 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -463.903 | 0.000 | 0.000 | 328.302 | 31.204 | 175.857 | 9.377 | 0.000 | 0.503 | 0.000 | 0.000 | -15.129 | 0.000 | -4.019 | -62.192 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -500.567 | 0.000 | 0.000 | 325.458 | 31.204 | 175.857 | 9.039 | 0.000 | 0.485 | 0.000 | 0.000 | -15.739 | 0.000 | -4.091 | -21.646 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -636.589 | 0.000 | 0.000 | 29.433 | 12.972 | 550.372 | 18.338 | 0.000 | 0.405 | 39.434 | 0.000 | -10.611 | 0.000 | -3.754 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.299 | -103.798 | 0.000 | 0.000 | 31.941 | 24.166 | 0.000 | 17.144 | 0.000 | 0.528 | 42.243 | 0.000 | -10.518 | 0.000 | -3.006 | -0.001 |
Total Facility | 134.082 | -779.147 | 3.580 | -4426.014 | 0.000 | 0.000 | 2074.580 | 783.338 | 2365.005 | 728.702 | 0.000 | 25.015 | 93.105 | 0.000 | -523.493 | 0.000 | -184.113 | -294.627 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-NOV-23:03 | 0.00 | 0.00 | 0.00 | -17425.32 | 0.00 | 0.00 | 6870.58 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 2102.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 19-AUG-13:40 | 0.00 | 0.00 | 0.00 | -2734.00 | 0.00 | 0.00 | 225.91 | 166.00 | 252.59 | 2480.86 | 0.00 | 106.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -497.63 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -1979.29 | 0.00 | 0.00 | 697.63 | 615.12 | 752.15 | 0.00 | 0.00 | 30.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -115.90 |
MECH_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -1412.66 | 0.00 | 0.00 | 167.49 | 456.12 | 618.54 | 0.00 | 0.00 | 70.48 | 100.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -803.48 | 0.00 | 0.00 | 132.12 | 167.89 | 178.43 | 0.00 | 0.00 | 42.81 | 282.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-MAY-19:03 | 0.00 | 0.00 | 0.00 | -39208.45 | 0.00 | 0.00 | 408.95 | 325.08 | 44299.38 | 0.00 | 0.00 | 46.28 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5871.24 |
CAFE_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -11837.96 | 0.00 | 0.00 | 8908.46 | 1134.35 | 711.25 | 445.87 | 0.00 | 166.90 | 471.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -38599.51 | 0.00 | 0.00 | 26440.91 | 6336.53 | 7389.94 | 649.70 | 0.00 | 476.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2694.24 |
ROOM_1_FLR_3 | 27-FEB-16:01 | 0.00 | -13238.37 | 0.00 | -703.65 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 6714.70 | 0.00 | 9.12 | 6583.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:41 | 0.00 | -13608.05 | 0.00 | -549.57 | 0.00 | 0.00 | 373.56 | 633.19 | 726.90 | 0.00 | 0.00 | 0.00 | 14224.27 | 0.00 | -1545.25 | 0.00 | -255.04 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -38825.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 48519.80 | 0.00 | 293.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14719.03 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -90738.56 | 0.00 | -7755.52 | 0.00 | 0.00 | 7126.68 | 7563.69 | 13532.74 | 0.00 | 0.00 | 0.00 | 79510.24 | 0.00 | -7841.55 | 0.00 | -1397.72 | 0.00 |
ROOM_5_FLR_3 | 13-MAR-15:01 | 0.00 | -11976.46 | 0.00 | -702.77 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 2855.71 | 0.00 | 38.93 | 9149.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -12122.84 | 0.00 | -922.30 | 0.00 | 0.00 | 107.52 | 398.41 | 653.15 | 6846.52 | 0.00 | 0.00 | 5066.13 | 0.00 | -0.00 | 0.00 | -26.59 | 0.00 |
CORRIDOR_FLR_3 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -9932.36 | 0.00 | 0.00 | 5497.78 | 4979.51 | 0.00 | 701.27 | 0.00 | 232.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1479.04 |
ROOM_1_FLR_6 | 09-APR-15:01 | 0.00 | -3480.26 | 0.00 | -176.39 | 0.00 | 0.00 | 32.68 | 58.70 | 55.31 | 1741.33 | 0.00 | 0.00 | 1789.23 | 0.00 | -0.00 | 0.00 | -20.61 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3670.10 | 0.00 | -145.98 | 0.00 | 0.00 | 90.03 | 158.30 | 181.72 | 0.00 | 0.00 | 0.00 | 3861.37 | 0.00 | -408.03 | 0.00 | -67.32 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-MAR-15:01 | 0.00 | -16165.29 | 0.00 | -1159.93 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 7133.28 | 0.00 | 219.51 | 8719.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 07-JUL-21:10 | 0.00 | 0.00 | 0.00 | -23357.92 | 0.00 | 0.00 | 15645.52 | 1992.02 | 6747.90 | 291.03 | 0.00 | 99.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1417.59 |
DINING_FLR_6 | 07-JUL-21:10 | 0.00 | 0.00 | 0.00 | -24661.32 | 0.00 | 0.00 | 15645.42 | 1992.02 | 6747.90 | 275.92 | 0.00 | 99.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -98.97 |
KITCHEN_FLR_6 | 15-APR-10:40 | 0.00 | 0.00 | 0.00 | -31421.39 | 0.00 | 0.00 | 478.49 | 294.67 | 24259.91 | 3120.97 | 0.00 | 5.85 | 3261.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-17:13 | 0.00 | 0.00 | 0.00 | -6058.44 | 0.00 | 0.00 | 925.36 | 1317.51 | 0.00 | 1285.61 | 0.00 | 139.92 | 2390.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-18:02 | 0.00 | -167159.74 | 0.00 | -196329.84 | 0.00 | 0.00 | 75534.56 | 53381.59 | 120482.43 | 44214.25 | 0.00 | 6277.46 | 63599.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-07:00 | 0.00 | 0.00 | 1147.99 | 0.00 | 0.00 | 0.00 | 660.31 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1617.41 | 0.00 | -430.12 | -248.65 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-FEB-09:03 | 0.00 | 0.00 | 548.20 | 0.00 | 0.00 | 0.00 | 109.60 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -372.57 | -866.74 |
STORAGE_FLR_1 | 12-FEB-07:10 | 0.00 | 0.00 | 393.31 | 0.00 | 0.00 | 0.00 | 119.42 | 111.93 | 127.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -231.97 | -520.14 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 09-JAN-09:20 | 0.00 | 0.00 | 440.37 | 0.00 | 0.00 | 0.00 | 2359.32 | 166.37 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1997.43 | 0.00 | -667.33 | -809.33 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-JAN-19:13 | 6190.43 | 360.89 | 0.00 | -360.89 | 0.00 | 0.00 | 320.88 | 711.53 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3201.49 | 0.00 | -765.90 | -3740.09 |
ROOM_2_FLR_3 | 12-FEB-09:02 | 6260.74 | 269.14 | 0.00 | -269.14 | 0.00 | 0.00 | 163.33 | 398.41 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3012.12 | 0.00 | -895.04 | -3568.46 |
ROOM_3_MULT19_FLR_3 | 09-JAN-05:00 | 3522.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 7252.17 | 0.00 | -12309.59 | 0.00 | -2732.65 | 0.00 |
ROOM_4_MULT19_FLR_3 | 03-FEB-16:01 | 35472.03 | 3660.50 | 0.00 | -3660.50 | 0.00 | 0.00 | 5564.89 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9034.58 | 0.00 | -2688.24 | -35420.10 |
ROOM_5_FLR_3 | 05-DEC-16:03 | 6077.08 | 419.14 | 0.00 | -419.14 | 0.00 | 0.00 | 251.37 | 199.23 | 200.18 | 404.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -834.96 | -6297.64 |
ROOM_6_FLR_3 | 07-JAN-16:13 | 6050.15 | 345.65 | 0.00 | -345.65 | 0.00 | 0.00 | 149.89 | 234.78 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2485.95 | 0.00 | -717.57 | -3452.53 |
CORRIDOR_FLR_3 | 07-JAN-17:00 | 0.00 | 0.00 | 2028.68 | 0.00 | 0.00 | 0.00 | 2089.26 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3215.83 | 0.00 | -918.42 | -2058.49 |
ROOM_1_FLR_6 | 07-JAN-19:13 | 1837.75 | 87.69 | 0.00 | -87.69 | 0.00 | 0.00 | 80.67 | 177.88 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -798.17 | 0.00 | -190.93 | -1228.37 |
ROOM_2_FLR_6 | 12-FEB-09:13 | 1854.48 | 83.11 | 0.00 | -83.11 | 0.00 | 0.00 | 37.87 | 99.60 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -747.80 | 0.00 | -227.64 | -1179.80 |
ROOM_3_MULT9_FLR_6 | 07-JAN-16:13 | 8510.87 | 566.40 | 0.00 | -566.40 | 0.00 | 0.00 | 333.91 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2454.44 | 0.00 | -831.43 | -6378.76 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-07:10 | 0.00 | 0.00 | 2258.59 | 0.00 | 0.00 | 0.00 | 1310.79 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2198.93 | 0.00 | -545.81 | -1702.98 |
Total Facility | 07-JAN-16:13 | -1344.85 | 79351.41 | 5592.79 | -79351.41 | 0.00 | 0.00 | 36940.88 | 17941.45 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50317.90 | 0.00 | -17835.65 | -65814.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.1382 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.0152 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6668 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5320 | 2.5320 | 1.3344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3162 | 0.3162 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2365 | 0.2365 | 0.1247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2041 | 0.2041 | 0.1075 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1200 | 0.1200 | 0.0633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3772 | 3.3772 | 1.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3887 | 1.3887 | 0.7319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8085 | 4.8085 | 2.5341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5087 | 1.5087 | 0.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2322 | 2.2322 | 1.1764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3389 | 2.3389 | 1.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3133 | 2.3133 | 1.2191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7617 | 0.7617 | 0.4014 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.1382 | 22.0152 | 22.1382 | 11.6668 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3344 | 1.3344 | 1.3344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1666 | 0.1666 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1247 | 0.1247 | 0.1247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1075 | 0.1075 | 0.1075 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0633 | 0.0633 | 0.0633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7798 | 1.7798 | 1.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7319 | 0.7319 | 0.7319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5341 | 2.5341 | 2.5341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7951 | 0.7951 | 0.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1764 | 1.1764 | 1.1764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2326 | 1.2326 | 1.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2191 | 1.2191 | 1.2191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4014 | 0.4014 | 0.4014 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6668 | 11.6668 | 11.6668 | 11.6668 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 19.00 |
Number of hours cooling loads not met | 40.67 |
Number of hours not met | 59.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1169.62 | 268438.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1794.90 | 196491.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.34 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.02 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 454.56 | 25586.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 98.30 | 4712.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 151.60 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4738.99 | 2907.84 | 270809.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.21 | 1901.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.20 | 1192.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.69 | 5927.96 |
Natural Gas | 1788.84 | 5866.30 |
Additional | 0.00 | 0.00 |
Total | 3508.53 | 11794.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.05 |
Space Heating | 0.00 |
Space Cooling | 158.21 |
Fans (All) | 40.07 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 522.50 |
Subtotal | 522.50 |
Natural Gas [MJ/m2] | |
Space Heating | 103.09 |
Service Water Heating | 256.30 |
Miscellaneous (All) | 517.07 |
Subtotal | 517.07 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.64 |
Space Heating | 9.92 |
Space Cooling | 15.22 |
Fans (All) | 3.85 |
Service Water Heating | 25.42 |
Receptacle Equipment | 29.23 |
Miscellaneous | 9.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6995.17 | 1764.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6995.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1764.83 | 0.00 | 0.00 | 0.00 |
Average | 8679.51 | 80.49 | 0.00 | 0.00 | 0.00 |
Sum | 190949.17 | 1770.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8571.17 | 188.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6352.83 | 2407.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8614.00 | 146.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8530.50 | 229.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8532.00 | 228.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8656.00 | 104.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6352.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2407.17 | 0.00 | 0.00 | 0.00 |
Average | 8608.06 | 151.94 | 0.00 | 0.00 | 0.00 |
Sum | 189377.33 | 3342.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4115.50 | 38.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4117.00 | 37.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4115.00 | 39.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4103.17 | 50.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1222419.00 | 23296.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 23296.00 | 0.00 | 0.00 | 0.00 |
Average | 287820.62 | 1066.42 | 0.00 | 0.00 | 0.00 |
Sum | 6332053.67 | 23461.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355908E+11 | 14707.78 | 31-JAN-22:00 | 14.90 | 11.03 | 0.640408E+10 | 4034.88 | 27-JAN-22:10 | 14.90 | 11.03 |
February | 0.293014E+11 | 14506.34 | 01-FEB-22:00 | 8.90 | 8.32 | 0.565029E+10 | 3969.11 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.288834E+11 | 14096.64 | 01-MAR-22:00 | 11.10 | 10.21 | 0.619555E+10 | 3863.03 | 01-MAR-22:10 | 11.02 | 10.13 |
April | 0.245088E+11 | 13629.52 | 19-APR-21:00 | 18.90 | 16.14 | 0.592088E+10 | 3741.08 | 14-APR-21:10 | 18.90 | 16.14 |
May | 0.293479E+11 | 14126.23 | 15-MAY-19:03 | 26.73 | 15.81 | 0.618232E+10 | 3838.03 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.345981E+11 | 14779.35 | 30-JUN-21:00 | 22.80 | 21.19 | 0.621434E+10 | 4029.62 | 30-JUN-21:10 | 22.77 | 21.16 |
July | 0.382942E+11 | 15605.97 | 14-JUL-21:00 | 28.30 | 21.42 | 0.672042E+10 | 4246.80 | 14-JUL-21:10 | 28.22 | 21.44 |
August | 0.406677E+11 | 16476.04 | 18-AUG-21:00 | 31.10 | 22.83 | 0.714178E+10 | 4481.56 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.413550E+11 | 17269.92 | 15-SEP-21:00 | 25.00 | 18.13 | 0.723445E+10 | 4709.01 | 14-SEP-21:10 | 25.00 | 18.13 |
October | 0.431040E+11 | 17344.20 | 13-OCT-21:00 | 13.30 | 9.72 | 0.754521E+10 | 4745.81 | 13-OCT-21:10 | 13.12 | 9.56 |
November | 0.415778E+11 | 17425.58 | 21-NOV-23:03 | 0.82 | -1.2 | 0.729849E+10 | 4724.98 | 08-NOV-22:10 | 0.82 | -1.2 |
December | 0.403492E+11 | 16774.75 | 01-DEC-22:00 | 3.90 | 0.00 | 0.711195E+10 | 4620.63 | 01-DEC-22:10 | 3.80 | -0.3 |
Annual Sum or Average | 0.427578E+12 | 0.796197E+11 | ||||||||
Minimum of Months | 0.245088E+11 | 13629.52 | 0.82 | -1.2 | 0.565029E+10 | 3741.08 | 0.82 | -1.2 | ||
Maximum of Months | 0.431040E+11 | 17425.58 | 31.10 | 22.83 | 0.754521E+10 | 4745.81 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126758E+10 | 2030.41 | 29-JAN-13:30 | 14.45 | 6.22 | 0.620878E+09 | 364.14 | 02-JAN-03:49 | 14.45 | 6.22 |
February | 0.168281E+10 | 2142.77 | 21-FEB-14:30 | 22.25 | 10.82 | 0.565097E+09 | 398.83 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.309978E+10 | 2107.57 | 30-MAR-14:20 | 27.80 | 17.60 | 0.636813E+09 | 437.66 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.349396E+10 | 2334.73 | 15-APR-13:45 | 27.62 | 15.00 | 0.622594E+09 | 430.90 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.421306E+10 | 2032.15 | 19-MAY-19:20 | 27.40 | 17.96 | 0.654197E+09 | 442.70 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.469213E+10 | 2126.40 | 13-JUN-19:20 | 30.20 | 22.02 | 0.674550E+09 | 467.69 | 13-JUN-21:10 | 28.12 | 21.63 |
July | 0.505945E+10 | 2487.47 | 08-JUL-17:04 | 34.40 | 23.36 | 0.718942E+09 | 491.78 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.530391E+10 | 2734.00 | 19-AUG-13:40 | 33.70 | 23.70 | 0.745336E+09 | 491.78 | 18-AUG-21:19 | 33.70 | 23.70 |
September | 0.452094E+10 | 2565.98 | 25-SEP-15:03 | 29.40 | 19.56 | 0.663001E+09 | 478.41 | 07-SEP-21:10 | 29.40 | 19.56 |
October | 0.367511E+10 | 2717.95 | 10-OCT-13:40 | 29.03 | 20.94 | 0.650986E+09 | 451.18 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.275297E+10 | 2174.91 | 15-NOV-14:00 | 21.10 | 11.33 | 0.609503E+09 | 392.21 | 08-NOV-22:10 | 21.10 | 11.33 |
December | 0.178939E+10 | 2110.52 | 10-DEC-14:00 | 16.70 | 7.82 | 0.624284E+09 | 387.61 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.415511E+11 | 0.778618E+10 | ||||||||
Minimum of Months | 0.126758E+10 | 2030.41 | 14.45 | 6.22 | 0.565097E+09 | 364.14 | 14.45 | 6.22 | ||
Maximum of Months | 0.530391E+10 | 2734.00 | 34.40 | 23.70 | 0.745336E+09 | 491.78 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233138E+10 | 1383.20 | 31-JAN-22:10 | 14.52 | 10.85 | 0.726461E+09 | 476.54 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.239223E+10 | 1460.84 | 28-FEB-22:10 | 18.63 | 10.80 | 0.666315E+09 | 503.87 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.320790E+10 | 1553.35 | 30-MAR-21:00 | 23.90 | 16.89 | 0.768526E+09 | 532.26 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.331157E+10 | 1563.27 | 17-APR-21:10 | 20.00 | 14.08 | 0.763509E+09 | 536.18 | 14-APR-21:10 | 20.00 | 14.08 |
May | 0.361289E+10 | 1603.35 | 19-MAY-21:00 | 23.90 | 16.26 | 0.812515E+09 | 549.69 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.371629E+10 | 1644.00 | 27-JUN-21:10 | 27.02 | 21.02 | 0.831923E+09 | 563.69 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.393838E+10 | 1902.62 | 07-JUL-21:00 | 30.60 | 22.80 | 0.874715E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.401832E+10 | 1979.28 | 18-AUG-21:00 | 31.10 | 22.83 | 0.894783E+09 | 569.53 | 18-AUG-22:19 | 29.23 | 23.14 |
September | 0.365125E+10 | 1752.06 | 08-SEP-21:00 | 25.60 | 21.61 | 0.815769E+09 | 569.49 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.344009E+10 | 1587.61 | 10-OCT-21:10 | 21.10 | 18.77 | 0.788807E+09 | 547.02 | 11-OCT-21:10 | 15.82 | 9.51 |
November | 0.305418E+10 | 1453.23 | 02-NOV-21:10 | 17.02 | 14.40 | 0.730589E+09 | 500.97 | 08-NOV-22:10 | 13.62 | 6.96 |
December | 0.271859E+10 | 1438.80 | 12-DEC-22:10 | 18.30 | 14.66 | 0.734377E+09 | 493.08 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.393931E+11 | 0.940829E+10 | ||||||||
Minimum of Months | 0.233138E+10 | 1383.20 | 14.52 | 10.80 | 0.666315E+09 | 476.54 | 13.62 | 6.96 | ||
Maximum of Months | 0.401832E+10 | 1979.28 | 31.10 | 22.83 | 0.894783E+09 | 569.55 | 29.23 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474584E+09 | 1078.47 | 31-JAN-22:00 | 14.90 | 11.03 | 0.151756E+09 | 91.87 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.927736E+09 | 1122.37 | 28-FEB-22:10 | 18.63 | 10.80 | 0.137419E+09 | 95.59 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.194762E+10 | 1195.64 | 30-MAR-21:00 | 23.90 | 16.89 | 0.154006E+09 | 100.81 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.243809E+10 | 1211.97 | 15-APR-13:45 | 27.62 | 15.00 | 0.151524E+09 | 101.92 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.297153E+10 | 1272.21 | 19-MAY-21:00 | 23.90 | 16.26 | 0.163215E+09 | 107.07 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.317453E+10 | 1357.27 | 29-JUN-21:10 | 25.92 | 21.53 | 0.172148E+09 | 114.05 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.340030E+10 | 1408.00 | 07-JUL-21:10 | 30.40 | 22.79 | 0.183244E+09 | 118.50 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.344183E+10 | 1412.64 | 18-AUG-21:10 | 30.82 | 22.88 | 0.186142E+09 | 118.92 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.307150E+10 | 1346.72 | 08-SEP-21:00 | 25.60 | 21.61 | 0.166294E+09 | 113.23 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.255810E+10 | 1223.09 | 18-OCT-21:10 | 23.22 | 22.46 | 0.156480E+09 | 102.79 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.180852E+10 | 1139.53 | 03-NOV-21:10 | 18.22 | 16.16 | 0.147717E+09 | 96.30 | 03-NOV-21:10 | 18.22 | 16.16 |
December | 0.996431E+09 | 1114.83 | 12-DEC-22:10 | 18.30 | 14.66 | 0.151872E+09 | 94.39 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.272108E+11 | 0.192182E+10 | ||||||||
Minimum of Months | 0.474584E+09 | 1078.47 | 14.90 | 10.80 | 0.137419E+09 | 91.87 | 14.52 | 10.80 | ||
Maximum of Months | 0.344183E+10 | 1412.64 | 30.82 | 22.88 | 0.186142E+09 | 118.92 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139420E+09 | 595.95 | 31-JAN-21:55 | 14.90 | 11.03 | 0.116671E+09 | 68.57 | 02-JAN-02:39 | 14.90 | 11.03 |
February | 0.394547E+09 | 637.50 | 28-FEB-22:10 | 18.63 | 10.80 | 0.105500E+09 | 71.05 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.955997E+09 | 677.33 | 30-MAR-21:00 | 23.90 | 16.89 | 0.117734E+09 | 74.82 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.131513E+10 | 711.68 | 15-APR-13:45 | 27.62 | 15.00 | 0.115000E+09 | 75.21 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.169243E+10 | 718.86 | 19-MAY-21:00 | 23.90 | 16.26 | 0.123087E+09 | 79.18 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.182971E+10 | 768.97 | 29-JUN-21:10 | 25.92 | 21.53 | 0.129543E+09 | 84.32 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.196011E+10 | 800.47 | 07-JUL-21:10 | 30.40 | 22.79 | 0.137885E+09 | 87.86 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.198497E+10 | 803.46 | 18-AUG-21:10 | 30.82 | 22.88 | 0.140137E+09 | 88.20 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.176467E+10 | 762.93 | 08-SEP-21:10 | 25.50 | 21.60 | 0.125087E+09 | 83.74 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.136741E+10 | 693.04 | 18-OCT-21:10 | 23.22 | 22.46 | 0.118842E+09 | 76.12 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.859407E+09 | 645.87 | 03-NOV-21:10 | 18.22 | 16.16 | 0.113044E+09 | 71.43 | 03-NOV-21:10 | 18.22 | 16.16 |
December | 0.357873E+09 | 633.89 | 12-DEC-22:10 | 18.30 | 14.66 | 0.116718E+09 | 70.24 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.146217E+11 | 0.145925E+10 | ||||||||
Minimum of Months | 0.139420E+09 | 595.95 | 14.90 | 10.80 | 0.105500E+09 | 68.57 | 14.90 | 10.80 | ||
Maximum of Months | 0.198497E+10 | 803.46 | 30.82 | 22.88 | 0.140137E+09 | 88.20 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479576E+11 | 36415.54 | 31-JAN-21:00 | 17.20 | 12.43 | 0.531884E+09 | 381.54 | 24-JAN-22:10 | 17.20 | 12.43 |
February | 0.442374E+11 | 36945.84 | 28-FEB-21:00 | 20.60 | 11.78 | 0.482323E+09 | 381.57 | 10-FEB-23:10 | 20.60 | 11.78 |
March | 0.507693E+11 | 37436.77 | 30-MAR-20:00 | 24.40 | 16.98 | 0.539003E+09 | 381.55 | 13-MAR-21:00 | 24.40 | 16.98 |
April | 0.499810E+11 | 37640.52 | 17-APR-19:55 | 22.80 | 15.38 | 0.521446E+09 | 381.58 | 24-APR-22:10 | 12.70 | 10.55 |
May | 0.527947E+11 | 39178.31 | 15-MAY-19:03 | 26.73 | 15.81 | 0.540749E+09 | 381.53 | 15-MAY-21:40 | 22.40 | 15.16 |
June | 0.522153E+11 | 38350.53 | 13-JUN-20:00 | 29.40 | 21.98 | 0.526235E+09 | 381.56 | 08-JUN-21:30 | 29.40 | 21.98 |
July | 0.541767E+11 | 38634.75 | 07-JUL-20:00 | 31.10 | 23.22 | 0.542176E+09 | 381.51 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.545412E+11 | 38537.68 | 18-AUG-20:00 | 31.70 | 22.32 | 0.545123E+09 | 381.51 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.513202E+11 | 38235.88 | 07-SEP-20:00 | 27.20 | 22.45 | 0.523214E+09 | 381.56 | 14-SEP-21:00 | 18.90 | 14.00 |
October | 0.513398E+11 | 37522.39 | 10-OCT-20:00 | 22.20 | 19.19 | 0.537282E+09 | 381.57 | 06-OCT-21:10 | 22.20 | 19.19 |
November | 0.485818E+11 | 36836.70 | 03-NOV-20:00 | 18.90 | 16.38 | 0.518202E+09 | 381.61 | 21-NOV-23:10 | 0.82 | -1.2 |
December | 0.488179E+11 | 36658.68 | 12-DEC-21:00 | 18.30 | 14.62 | 0.533016E+09 | 381.57 | 15-DEC-22:10 | 5.50 | 3.86 |
Annual Sum or Average | 0.606733E+12 | 0.634065E+10 | ||||||||
Minimum of Months | 0.442374E+11 | 36415.54 | 17.20 | 11.78 | 0.482323E+09 | 381.51 | 0.82 | -1.2 | ||
Maximum of Months | 0.545412E+11 | 39178.31 | 31.70 | 23.22 | 0.545123E+09 | 381.61 | 29.40 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153266E+11 | 8974.16 | 29-JAN-13:00 | 13.90 | 6.14 | 0.836225E+10 | 5690.61 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.153207E+11 | 9147.19 | 28-FEB-22:30 | 18.10 | 10.49 | 0.777829E+10 | 6084.37 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.197467E+11 | 9640.09 | 30-MAR-21:50 | 22.98 | 16.53 | 0.912577E+10 | 6374.00 | 30-MAR-21:19 | 22.98 | 16.53 |
April | 0.198865E+11 | 10202.75 | 15-APR-13:45 | 27.62 | 15.00 | 0.896201E+10 | 6295.48 | 17-APR-21:40 | 20.00 | 13.94 |
May | 0.215689E+11 | 9626.20 | 19-MAY-21:12 | 23.33 | 16.07 | 0.952755E+10 | 6363.76 | 19-MAY-21:19 | 23.33 | 16.07 |
June | 0.221552E+11 | 10523.26 | 13-JUN-21:10 | 28.12 | 21.63 | 0.967712E+10 | 6461.58 | 14-JUN-22:19 | 25.20 | 19.70 |
July | 0.234830E+11 | 11364.65 | 07-JUL-21:10 | 30.40 | 22.79 | 0.101507E+11 | 6462.54 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.242159E+11 | 11836.73 | 18-AUG-21:10 | 30.82 | 22.88 | 0.104342E+11 | 6462.46 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.220459E+11 | 10947.03 | 07-SEP-21:10 | 25.40 | 21.43 | 0.959118E+10 | 6462.47 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.210249E+11 | 11478.46 | 10-OCT-15:03 | 29.08 | 20.63 | 0.939405E+10 | 6462.39 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.189383E+11 | 9480.22 | 11-NOV-13:00 | 21.10 | 11.68 | 0.863757E+10 | 6026.62 | 08-NOV-22:40 | 21.10 | 11.68 |
December | 0.173107E+11 | 9251.98 | 10-DEC-13:00 | 15.60 | 7.72 | 0.856209E+10 | 6048.57 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.241023E+12 | 0.110203E+12 | ||||||||
Minimum of Months | 0.153207E+11 | 8974.16 | 13.90 | 6.14 | 0.777829E+10 | 5690.61 | 13.37 | 10.31 | ||
Maximum of Months | 0.242159E+11 | 11836.73 | 30.82 | 22.88 | 0.104342E+11 | 6462.54 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577988E+11 | 29705.89 | 31-JAN-22:30 | 13.75 | 10.50 | 0.251313E+11 | 16907.20 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.559927E+11 | 30923.92 | 28-FEB-22:52 | 17.30 | 10.02 | 0.232462E+11 | 17647.25 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.694482E+11 | 32340.02 | 30-MAR-22:00 | 22.80 | 16.45 | 0.269495E+11 | 18331.58 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.697879E+11 | 32182.57 | 17-APR-22:00 | 20.00 | 13.85 | 0.265799E+11 | 18280.10 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.753179E+11 | 32878.43 | 19-MAY-22:00 | 22.20 | 15.66 | 0.282321E+11 | 18649.80 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.767253E+11 | 33897.61 | 13-JUN-22:00 | 27.20 | 20.99 | 0.286431E+11 | 19181.12 | 13-JUN-22:10 | 27.12 | 20.92 |
July | 0.809889E+11 | 37401.50 | 07-JUL-21:10 | 30.40 | 22.79 | 0.299826E+11 | 19185.93 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.824328E+11 | 38596.59 | 18-AUG-21:10 | 30.82 | 22.88 | 0.305893E+11 | 19185.83 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.760254E+11 | 35356.06 | 07-SEP-21:10 | 25.40 | 21.43 | 0.282783E+11 | 19182.04 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.732477E+11 | 32865.66 | 10-OCT-22:00 | 21.10 | 18.56 | 0.276577E+11 | 18631.51 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.670359E+11 | 31004.48 | 02-NOV-22:00 | 16.10 | 14.10 | 0.257407E+11 | 17570.52 | 02-NOV-22:10 | 16.10 | 14.10 |
December | 0.635531E+11 | 30914.45 | 12-DEC-23:00 | 18.30 | 14.87 | 0.256798E+11 | 17520.35 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.848354E+12 | 0.326711E+12 | ||||||||
Minimum of Months | 0.559927E+11 | 29705.89 | 13.75 | 10.02 | 0.232462E+11 | 16907.20 | 13.37 | 9.75 | ||
Maximum of Months | 0.824328E+11 | 38596.59 | 30.82 | 22.88 | 0.305893E+11 | 19185.93 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47398643.00 | 3385.98 | 29-JAN-16:01 | 16.52 | 6.64 | 94121502.00 | 56.69 | 17-JAN-23:19 | 16.52 | 6.64 |
February | 0.181442E+09 | 3485.55 | 27-FEB-16:01 | 22.70 | 11.34 | 85920623.58 | 56.69 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.599772E+09 | 3480.32 | 13-MAR-15:01 | 23.98 | 13.14 | 97539231.96 | 59.47 | 23-MAR-21:19 | 15.20 | 10.46 |
April | 0.103100E+10 | 3483.79 | 09-APR-15:01 | 21.70 | 11.33 | 95014655.09 | 56.69 | 12-APR-21:49 | 18.07 | 13.39 |
May | 0.150316E+10 | 3481.79 | 10-MAY-18:01 | 20.92 | 10.48 | 98744799.83 | 56.70 | 31-MAY-21:40 | 21.93 | 18.81 |
June | 0.205920E+10 | 3103.19 | 16-JUN-15:02 | 28.77 | 20.97 | 95888410.73 | 56.69 | 22-JUN-22:00 | 20.00 | 19.66 |
July | 0.232140E+10 | 3125.51 | 30-JUL-15:02 | 30.60 | 23.73 | 99003529.11 | 56.69 | 05-JUL-00:00 | 30.60 | 23.73 |
August | 0.244315E+10 | 3135.90 | 20-AUG-18:01 | 25.55 | 22.49 | 99172136.50 | 56.69 | 20-AUG-01:39 | 25.55 | 22.49 |
September | 0.162286E+10 | 3090.09 | 04-SEP-18:01 | 26.83 | 21.37 | 95522154.49 | 56.69 | 08-SEP-00:10 | 22.80 | 20.15 |
October | 0.820368E+09 | 3255.88 | 31-OCT-18:01 | 12.20 | 6.42 | 97655296.27 | 56.69 | 10-OCT-21:00 | 12.20 | 6.42 |
November | 0.310962E+09 | 3476.94 | 08-NOV-16:01 | 21.60 | 10.05 | 93666173.09 | 56.69 | 02-NOV-22:49 | 21.60 | 10.05 |
December | 91997509.58 | 3429.18 | 10-DEC-16:01 | 18.62 | 9.23 | 95025918.72 | 56.69 | 12-DEC-23:49 | 17.88 | 14.79 |
Annual Sum or Average | 0.130327E+11 | 0.114727E+10 | ||||||||
Minimum of Months | 47398643.00 | 3090.09 | 12.20 | 6.42 | 85920623.58 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.244315E+10 | 3485.55 | 30.60 | 23.73 | 99172136.50 | 59.47 | 30.60 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13701487.52 | 2733.83 | 29-JAN-16:01 | 16.52 | 6.64 | 93089924.32 | 56.91 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 64794534.97 | 3416.28 | 27-FEB-16:01 | 22.70 | 11.34 | 85748801.21 | 65.65 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.320769E+09 | 3411.13 | 13-MAR-15:01 | 23.98 | 13.14 | 98949402.74 | 71.77 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.725796E+09 | 3529.84 | 26-APR-18:41 | 14.60 | 7.53 | 99220883.41 | 73.63 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.124510E+10 | 3539.41 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104230E+09 | 74.72 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.191443E+10 | 3099.32 | 05-JUN-21:51 | 22.20 | 17.55 | 99392607.83 | 81.44 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.216430E+10 | 3152.05 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102294E+09 | 79.58 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.221966E+10 | 3090.32 | 28-AUG-15:02 | 29.50 | 22.37 | 0.101498E+09 | 75.53 | 23-AUG-21:19 | 29.50 | 22.37 |
September | 0.128696E+10 | 3376.53 | 18-SEP-16:01 | 25.40 | 17.60 | 99499276.69 | 74.89 | 11-SEP-21:19 | 25.40 | 17.60 |
October | 0.439109E+09 | 3154.32 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100134E+09 | 71.60 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.117952E+09 | 3398.80 | 08-NOV-16:01 | 21.60 | 10.05 | 93333999.68 | 62.03 | 02-NOV-21:40 | 21.60 | 10.05 |
December | 29543948.06 | 3249.87 | 10-DEC-16:01 | 18.62 | 9.23 | 93860374.06 | 60.24 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.105421E+11 | 0.117125E+10 | ||||||||
Minimum of Months | 13701487.52 | 2733.83 | 13.68 | 6.54 | 85748801.21 | 56.91 | 14.52 | 7.53 | ||
Maximum of Months | 0.221966E+10 | 3539.41 | 29.50 | 22.37 | 0.104230E+09 | 81.44 | 29.50 | 22.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15977168.91 | 171.49 | 31-JAN-15:20 | 20.73 | 13.19 | 0.00 | 0.00 | 01-JAN-00:10 | 20.73 | 13.19 |
February | 73465516.49 | 381.09 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.208461E+09 | 368.61 | 30-MAR-13:40 | 27.43 | 17.97 | 0.00 | 0.00 | 01-MAR-00:10 | 27.43 | 17.97 |
April | 0.262263E+09 | 348.70 | 15-APR-13:53 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.350583E+09 | 297.83 | 19-MAY-19:10 | 27.85 | 18.11 | 0.00 | 0.00 | 01-MAY-00:10 | 27.85 | 18.11 |
June | 0.469490E+09 | 340.60 | 24-JUN-19:10 | 30.22 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 30.22 | 21.43 |
July | 0.550131E+09 | 383.57 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.633209E+09 | 415.57 | 19-AUG-13:50 | 33.80 | 23.78 | 0.00 | 0.00 | 01-AUG-00:10 | 33.80 | 23.78 |
September | 0.478745E+09 | 475.61 | 24-SEP-12:40 | 28.70 | 19.86 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 19.86 |
October | 0.338970E+09 | 510.90 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.194540E+09 | 428.88 | 08-NOV-14:10 | 20.78 | 9.75 | 0.00 | 0.00 | 01-NOV-00:10 | 20.78 | 9.75 |
December | 81704920.19 | 401.18 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.365754E+10 | 0.00 | ||||||||
Minimum of Months | 15977168.91 | 171.49 | 17.50 | 8.24 | 0.00 | 0.00 | 17.50 | 8.24 | ||
Maximum of Months | 0.633209E+09 | 510.90 | 34.40 | 23.78 | 0.00 | 0.00 | 34.40 | 23.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45568302.51 | 983.67 | 31-JAN-16:01 | 19.90 | 13.55 | 94631605.20 | 64.33 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.117556E+09 | 1215.62 | 28-FEB-22:52 | 17.30 | 10.02 | 86664127.21 | 68.96 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.293096E+09 | 1211.37 | 31-MAR-20:12 | 13.87 | 8.46 | 98304129.03 | 70.75 | 28-MAR-21:10 | 13.87 | 8.46 |
April | 0.445817E+09 | 1217.35 | 09-APR-15:01 | 21.70 | 11.33 | 98191427.39 | 73.03 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.637609E+09 | 1295.98 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103222E+09 | 74.29 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.835233E+09 | 1158.11 | 18-JUN-18:02 | 26.93 | 22.05 | 98674562.11 | 78.50 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.911955E+09 | 1161.36 | 13-JUL-15:02 | 34.40 | 22.99 | 0.101865E+09 | 77.29 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.908580E+09 | 1156.01 | 10-AUG-08:61 | 27.48 | 23.62 | 0.101043E+09 | 75.45 | 31-AUG-21:30 | 21.65 | 19.90 |
September | 0.638949E+09 | 1153.94 | 07-SEP-18:02 | 29.72 | 22.85 | 99172520.03 | 75.97 | 01-SEP-21:10 | 29.72 | 22.85 |
October | 0.368673E+09 | 1214.77 | 11-OCT-21:52 | 14.40 | 8.97 | 99760466.71 | 73.20 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.203267E+09 | 1149.92 | 08-NOV-16:01 | 21.60 | 10.05 | 94091036.66 | 68.35 | 03-NOV-21:00 | 21.60 | 10.05 |
December | 84449601.62 | 1013.38 | 11-DEC-16:01 | 21.02 | 15.88 | 95395680.18 | 65.55 | 12-DEC-22:00 | 18.30 | 14.87 |
Annual Sum or Average | 0.549075E+10 | 0.117102E+10 | ||||||||
Minimum of Months | 45568302.51 | 983.67 | 13.68 | 6.54 | 86664127.21 | 64.33 | 13.22 | 8.46 | ||
Maximum of Months | 0.911955E+09 | 1295.98 | 34.40 | 23.62 | 0.103222E+09 | 78.50 | 29.72 | 22.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37451058.23 | 3042.92 | 29-JAN-16:01 | 16.52 | 6.64 | 94213734.43 | 56.69 | 09-JAN-00:20 | 16.52 | 6.64 |
February | 0.192526E+09 | 3167.79 | 27-FEB-16:01 | 22.70 | 11.34 | 86091010.62 | 56.69 | 21-FEB-22:19 | 22.70 | 11.34 |
March | 0.535753E+09 | 3169.80 | 13-MAR-15:01 | 23.98 | 13.14 | 97697355.33 | 56.69 | 30-MAR-21:40 | 23.17 | 16.60 |
April | 0.993547E+09 | 3166.24 | 09-APR-15:01 | 21.70 | 11.33 | 95295669.63 | 56.69 | 18-APR-21:19 | 19.80 | 15.14 |
May | 0.153547E+10 | 3140.92 | 10-MAY-18:01 | 20.92 | 10.48 | 98962584.13 | 56.69 | 08-MAY-21:00 | 20.92 | 10.48 |
June | 0.210366E+10 | 2887.59 | 13-JUN-08:61 | 25.37 | 20.63 | 96005709.92 | 56.69 | 13-JUN-00:49 | 25.37 | 20.63 |
July | 0.239696E+10 | 2881.83 | 21-JUL-08:61 | 26.15 | 22.30 | 99059857.83 | 56.69 | 04-JUL-00:30 | 26.15 | 22.30 |
August | 0.245873E+10 | 2860.23 | 26-AUG-08:61 | 23.07 | 18.51 | 99213345.67 | 56.70 | 17-AUG-21:10 | 23.07 | 18.51 |
September | 0.162894E+10 | 2844.80 | 12-SEP-18:01 | 27.52 | 20.94 | 95616987.33 | 56.69 | 09-SEP-00:30 | 27.52 | 20.94 |
October | 0.797389E+09 | 2843.24 | 02-OCT-18:01 | 24.22 | 19.50 | 97825148.68 | 56.69 | 10-OCT-21:00 | 21.10 | 18.56 |
November | 0.286746E+09 | 3148.81 | 08-NOV-16:01 | 21.60 | 10.05 | 93861268.16 | 56.69 | 02-NOV-21:19 | 21.60 | 10.05 |
December | 84394672.49 | 3110.49 | 10-DEC-16:01 | 18.62 | 9.23 | 95137362.02 | 56.69 | 12-DEC-23:00 | 17.80 | 14.77 |
Annual Sum or Average | 0.130516E+11 | 0.114898E+10 | ||||||||
Minimum of Months | 37451058.23 | 2843.24 | 16.52 | 6.64 | 86091010.62 | 56.69 | 16.52 | 6.64 | ||
Maximum of Months | 0.245873E+10 | 3169.80 | 27.52 | 22.30 | 99213345.67 | 56.70 | 27.52 | 22.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14202903.43 | 2083.24 | 31-JAN-16:01 | 19.90 | 13.55 | 93126917.39 | 57.47 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 84587554.47 | 3114.48 | 27-FEB-16:01 | 22.70 | 11.34 | 85674481.60 | 64.95 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.299802E+09 | 3115.75 | 13-MAR-15:01 | 23.98 | 13.14 | 98168115.48 | 68.67 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.715678E+09 | 3121.38 | 09-APR-15:01 | 21.70 | 11.33 | 98646030.16 | 71.45 | 17-APR-21:00 | 20.00 | 13.85 |
May | 0.127381E+10 | 3203.44 | 18-MAY-08:51 | 24.40 | 17.97 | 0.104070E+09 | 75.58 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.193073E+10 | 3261.40 | 04-JUN-08:51 | 24.40 | 18.28 | 99749057.88 | 78.29 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.220614E+10 | 3029.48 | 25-JUL-08:51 | 24.40 | 20.24 | 0.102871E+09 | 79.96 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.221807E+10 | 3092.16 | 26-AUG-08:51 | 24.40 | 19.19 | 0.101788E+09 | 76.64 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.128031E+10 | 3126.47 | 15-SEP-08:51 | 21.70 | 14.94 | 99588744.32 | 74.40 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.447396E+09 | 2794.32 | 09-OCT-18:01 | 24.13 | 18.81 | 99549090.50 | 71.38 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.119209E+09 | 2890.08 | 08-NOV-16:01 | 21.60 | 10.05 | 92917666.36 | 62.53 | 03-NOV-21:30 | 21.60 | 10.05 |
December | 26904130.48 | 2289.78 | 12-DEC-16:01 | 22.12 | 16.00 | 93828329.89 | 59.72 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.106168E+11 | 0.116998E+10 | ||||||||
Minimum of Months | 14202903.43 | 2083.24 | 19.90 | 10.05 | 85674481.60 | 57.47 | 14.52 | 10.05 | ||
Maximum of Months | 0.221807E+10 | 3261.40 | 24.40 | 20.24 | 0.104070E+09 | 79.96 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184196E+10 | 1974.47 | 31-JAN-22:10 | 14.52 | 10.85 | 0.119897E+10 | 716.92 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.248034E+10 | 2067.14 | 28-FEB-22:10 | 18.63 | 10.80 | 0.108732E+10 | 749.98 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.445768E+10 | 2159.36 | 30-MAR-21:51 | 22.80 | 16.45 | 0.122383E+10 | 778.04 | 30-MAR-21:19 | 22.80 | 16.45 |
April | 0.500901E+10 | 2356.37 | 15-APR-13:45 | 27.62 | 15.00 | 0.121790E+10 | 801.53 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.562862E+10 | 2278.94 | 19-MAY-21:12 | 23.33 | 16.07 | 0.130555E+10 | 819.43 | 19-MAY-21:19 | 23.33 | 16.07 |
June | 0.583236E+10 | 2409.74 | 29-JUN-21:10 | 25.92 | 21.53 | 0.134739E+10 | 862.16 | 29-JUN-21:19 | 25.73 | 21.59 |
July | 0.619160E+10 | 2460.35 | 07-JUL-21:10 | 30.40 | 22.79 | 0.142175E+10 | 881.03 | 07-JUL-21:19 | 30.20 | 22.78 |
August | 0.622628E+10 | 2482.97 | 18-AUG-21:10 | 30.82 | 22.88 | 0.143529E+10 | 889.13 | 18-AUG-21:19 | 30.53 | 22.93 |
September | 0.566107E+10 | 2373.48 | 08-SEP-21:10 | 25.50 | 21.60 | 0.130672E+10 | 850.12 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.489145E+10 | 2203.76 | 11-OCT-21:10 | 15.82 | 9.51 | 0.124225E+10 | 795.03 | 11-OCT-21:19 | 15.53 | 9.41 |
November | 0.380978E+10 | 2033.94 | 02-NOV-21:10 | 17.02 | 14.40 | 0.116515E+10 | 734.08 | 02-NOV-21:40 | 16.47 | 14.23 |
December | 0.266070E+10 | 2023.80 | 12-DEC-22:10 | 18.30 | 14.66 | 0.119983E+10 | 732.03 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.546908E+11 | 0.151519E+11 | ||||||||
Minimum of Months | 0.184196E+10 | 1974.47 | 14.52 | 9.51 | 0.108732E+10 | 716.92 | 13.75 | 9.41 | ||
Maximum of Months | 0.622628E+10 | 2482.97 | 30.82 | 22.88 | 0.143529E+10 | 889.13 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34516041.43 | 3528.05 | 29-JAN-16:01 | 16.52 | 6.64 | 93534153.82 | 56.69 | 26-JAN-23:19 | 16.52 | 6.64 |
February | 0.169294E+09 | 3652.95 | 27-FEB-16:01 | 22.70 | 11.34 | 85480054.50 | 56.69 | 28-FEB-02:09 | 12.80 | 7.01 |
March | 0.599398E+09 | 3646.73 | 13-MAR-15:01 | 23.98 | 13.14 | 97300272.97 | 58.17 | 23-MAR-21:19 | 15.20 | 10.46 |
April | 0.108129E+10 | 3656.75 | 09-APR-15:01 | 21.70 | 11.33 | 94929252.11 | 56.69 | 12-APR-21:40 | 18.33 | 13.45 |
May | 0.162510E+10 | 3644.44 | 10-MAY-18:01 | 20.92 | 10.48 | 98719879.72 | 56.70 | 03-MAY-21:10 | 20.92 | 10.48 |
June | 0.220792E+10 | 3202.53 | 18-JUN-18:02 | 26.93 | 22.05 | 95872425.37 | 56.70 | 26-JUN-00:40 | 24.40 | 21.65 |
July | 0.248631E+10 | 3196.00 | 26-JUL-18:02 | 30.13 | 24.13 | 98989545.71 | 56.70 | 13-JUL-00:49 | 30.13 | 24.13 |
August | 0.260950E+10 | 3250.89 | 23-AUG-18:02 | 26.02 | 23.74 | 99161807.83 | 56.70 | 02-AUG-01:30 | 26.02 | 23.74 |
September | 0.168620E+10 | 3252.10 | 03-SEP-15:02 | 29.50 | 22.84 | 95466980.53 | 56.69 | 19-SEP-21:10 | 19.72 | 15.39 |
October | 0.827301E+09 | 3438.19 | 31-OCT-18:01 | 12.20 | 6.42 | 97427996.83 | 56.69 | 10-OCT-21:19 | 12.20 | 6.42 |
November | 0.285998E+09 | 3640.23 | 08-NOV-16:01 | 21.60 | 10.05 | 93354539.64 | 56.69 | 04-NOV-02:49 | 21.60 | 10.05 |
December | 75545531.87 | 3582.40 | 10-DEC-16:01 | 18.62 | 9.23 | 94446862.59 | 56.70 | 13-DEC-03:30 | 16.95 | 14.90 |
Annual Sum or Average | 0.136884E+11 | 0.114468E+10 | ||||||||
Minimum of Months | 34516041.43 | 3196.00 | 12.20 | 6.42 | 85480054.50 | 56.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.260950E+10 | 3656.75 | 30.13 | 24.13 | 99161807.83 | 58.17 | 30.13 | 24.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10506871.04 | 1996.00 | 20-JAN-16:01 | 17.12 | 12.56 | 92683639.89 | 56.69 | 11-JAN-23:19 | 17.12 | 12.56 |
February | 57279360.04 | 3572.25 | 27-FEB-16:01 | 22.70 | 11.34 | 85448013.15 | 66.35 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.315612E+09 | 3560.19 | 13-MAR-15:01 | 23.98 | 13.14 | 98850186.79 | 72.42 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.769885E+09 | 3755.71 | 09-APR-20:11 | 13.70 | 8.28 | 99747953.51 | 75.91 | 14-APR-21:30 | 18.60 | 13.02 |
May | 0.138373E+10 | 3816.08 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104742E+09 | 77.83 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.208905E+10 | 3254.89 | 05-JUN-21:51 | 22.20 | 17.55 | 99394769.94 | 83.72 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.235551E+10 | 3287.78 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102213E+09 | 80.29 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.240114E+10 | 3261.80 | 08-AUG-17:52 | 26.70 | 23.52 | 0.101409E+09 | 75.63 | 07-AUG-21:00 | 26.70 | 23.52 |
September | 0.136392E+10 | 3506.46 | 18-SEP-16:01 | 25.40 | 17.60 | 99515603.38 | 75.13 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.437553E+09 | 3412.49 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100167E+09 | 72.29 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.100196E+09 | 3545.68 | 08-NOV-16:01 | 21.60 | 10.05 | 92943109.68 | 61.64 | 02-NOV-21:40 | 21.60 | 10.05 |
December | 22644443.24 | 3330.45 | 10-DEC-16:01 | 18.62 | 9.23 | 93291450.86 | 59.22 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.113070E+11 | 0.117041E+10 | ||||||||
Minimum of Months | 10506871.04 | 1996.00 | 13.68 | 6.54 | 85448013.15 | 56.69 | 13.68 | 6.54 | ||
Maximum of Months | 0.240114E+10 | 3816.08 | 26.70 | 23.52 | 0.104742E+09 | 83.72 | 26.70 | 23.52 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145427E+09 | 1874.13 | 28-JAN-16:01 | 12.20 | 4.56 | 95901627.51 | 58.04 | 19-JAN-22:49 | 12.20 | 4.56 |
February | 0.250543E+09 | 1919.16 | 27-FEB-16:01 | 22.70 | 11.34 | 87169522.60 | 61.00 | 16-FEB-22:49 | 22.70 | 11.34 |
March | 0.545766E+09 | 1925.05 | 13-MAR-15:01 | 23.98 | 13.14 | 98002603.28 | 62.44 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.698595E+09 | 1877.60 | 09-APR-18:01 | 20.45 | 11.08 | 95130117.95 | 56.69 | 20-APR-21:30 | 18.90 | 15.28 |
May | 0.917867E+09 | 1873.17 | 10-MAY-18:01 | 20.92 | 10.48 | 98733826.74 | 56.69 | 22-MAY-21:00 | 18.90 | 17.09 |
June | 0.119215E+10 | 1708.33 | 28-JUN-18:02 | 30.50 | 23.40 | 95867303.93 | 56.69 | 28-JUN-00:40 | 30.50 | 23.40 |
July | 0.136569E+10 | 1704.88 | 23-JUL-18:02 | 28.80 | 22.43 | 98984014.10 | 56.70 | 07-JUL-21:00 | 28.80 | 22.43 |
August | 0.151709E+10 | 1711.39 | 21-AUG-18:02 | 29.82 | 24.23 | 99168040.99 | 56.70 | 02-AUG-21:19 | 29.82 | 24.23 |
September | 0.112688E+10 | 1715.68 | 04-SEP-18:01 | 26.83 | 21.37 | 95559220.89 | 56.70 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.786807E+09 | 1856.49 | 12-OCT-18:01 | 17.23 | 10.36 | 98097655.90 | 56.69 | 11-OCT-00:10 | 17.23 | 10.36 |
November | 0.492768E+09 | 1920.42 | 08-NOV-16:01 | 21.60 | 10.05 | 94697003.44 | 56.69 | 03-NOV-22:00 | 21.60 | 10.05 |
December | 0.262540E+09 | 1900.06 | 10-DEC-16:01 | 18.62 | 9.23 | 96638143.05 | 56.69 | 13-DEC-02:09 | 16.20 | 14.20 |
Annual Sum or Average | 0.930213E+10 | 0.115395E+10 | ||||||||
Minimum of Months | 0.145427E+09 | 1704.88 | 12.20 | 4.56 | 87169522.60 | 56.69 | 12.20 | 4.56 | ||
Maximum of Months | 0.151709E+10 | 1925.05 | 30.50 | 24.23 | 99168040.99 | 62.44 | 30.50 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335272E+11 | 17429.84 | 19-JAN-22:57 | 18.30 | 16.51 | 0.165885E+11 | 11347.23 | 30-JAN-23:19 | 11.70 | 8.91 |
February | 0.316632E+11 | 18638.12 | 28-FEB-22:53 | 17.30 | 10.02 | 0.154393E+11 | 11348.05 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.376832E+11 | 20349.90 | 30-MAR-21:53 | 22.80 | 16.45 | 0.179734E+11 | 11348.36 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.381264E+11 | 20452.44 | 17-APR-21:52 | 20.00 | 13.85 | 0.177898E+11 | 11348.64 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.414778E+11 | 21373.72 | 19-MAY-21:05 | 23.62 | 16.17 | 0.187897E+11 | 11348.58 | 16-MAY-22:10 | 23.62 | 16.17 |
June | 0.425620E+11 | 22600.77 | 13-JUN-22:00 | 27.20 | 20.99 | 0.184643E+11 | 11348.72 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.447838E+11 | 23355.63 | 07-JUL-21:10 | 30.40 | 22.79 | 0.190484E+11 | 11348.71 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.449400E+11 | 23089.80 | 18-AUG-21:10 | 30.82 | 22.88 | 0.191497E+11 | 11348.54 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.403365E+11 | 21779.68 | 07-SEP-21:10 | 25.40 | 21.43 | 0.181844E+11 | 11348.54 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.384562E+11 | 20228.26 | 18-OCT-21:53 | 22.80 | 21.95 | 0.180673E+11 | 11348.35 | 02-OCT-22:10 | 22.80 | 21.95 |
November | 0.354071E+11 | 18540.84 | 03-NOV-21:53 | 17.80 | 16.05 | 0.169422E+11 | 11348.08 | 03-NOV-22:10 | 17.80 | 16.05 |
December | 0.349368E+11 | 18049.71 | 12-DEC-22:55 | 18.30 | 14.87 | 0.169686E+11 | 11347.25 | 12-DEC-23:19 | 18.13 | 14.84 |
Annual Sum or Average | 0.463900E+12 | 0.213405E+12 | ||||||||
Minimum of Months | 0.316632E+11 | 17429.84 | 17.30 | 10.02 | 0.154393E+11 | 11347.23 | 11.70 | 8.91 | ||
Maximum of Months | 0.449400E+11 | 23355.63 | 30.82 | 22.88 | 0.191497E+11 | 11348.72 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364382E+11 | 19351.70 | 19-JAN-22:57 | 18.30 | 16.51 | 0.169109E+11 | 11347.29 | 30-JAN-23:19 | 11.70 | 8.91 |
February | 0.343783E+11 | 20534.49 | 28-FEB-22:53 | 17.30 | 10.02 | 0.157503E+11 | 11348.07 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.408557E+11 | 22143.89 | 30-MAR-21:53 | 22.80 | 16.45 | 0.183235E+11 | 11348.37 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.413259E+11 | 22098.16 | 17-APR-21:52 | 20.00 | 13.85 | 0.180548E+11 | 11348.65 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.448608E+11 | 22949.96 | 30-MAY-21:05 | 23.62 | 21.16 | 0.189657E+11 | 11348.58 | 16-MAY-22:10 | 23.62 | 21.16 |
June | 0.456414E+11 | 24068.74 | 13-JUN-21:10 | 28.12 | 21.63 | 0.185477E+11 | 11348.72 | 07-JUN-22:10 | 28.12 | 21.63 |
July | 0.478195E+11 | 24658.84 | 07-JUL-21:10 | 30.40 | 22.79 | 0.191191E+11 | 11348.71 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.479296E+11 | 24375.18 | 18-AUG-21:10 | 30.82 | 22.88 | 0.192084E+11 | 11348.54 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.434675E+11 | 23250.29 | 07-SEP-21:10 | 25.40 | 21.43 | 0.183357E+11 | 11348.55 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.416384E+11 | 22049.37 | 18-OCT-21:53 | 22.80 | 21.95 | 0.183906E+11 | 11348.36 | 02-OCT-22:10 | 22.80 | 21.95 |
November | 0.383497E+11 | 20506.51 | 03-NOV-21:53 | 17.80 | 16.05 | 0.173086E+11 | 11348.10 | 03-NOV-22:10 | 17.80 | 16.05 |
December | 0.378586E+11 | 19995.12 | 12-DEC-22:55 | 18.30 | 14.87 | 0.173341E+11 | 11347.29 | 15-DEC-23:19 | 5.00 | 4.00 |
Annual Sum or Average | 0.500564E+12 | 0.216249E+12 | ||||||||
Minimum of Months | 0.343783E+11 | 19351.70 | 17.30 | 10.02 | 0.157503E+11 | 11347.29 | 5.00 | 4.00 | ||
Maximum of Months | 0.479296E+11 | 24658.84 | 30.82 | 22.88 | 0.192084E+11 | 11348.72 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479570E+11 | 26695.83 | 29-JAN-11:40 | 12.43 | 5.39 | 0.187029E+11 | 11319.56 | 14-JAN-18:19 | 12.43 | 5.39 |
February | 0.449206E+11 | 27921.45 | 26-FEB-11:40 | 22.07 | 11.70 | 0.169023E+11 | 11319.56 | 11-FEB-18:19 | 22.07 | 11.70 |
March | 0.526985E+11 | 28352.18 | 30-MAR-10:45 | 21.83 | 17.67 | 0.187362E+11 | 11319.51 | 04-MAR-18:19 | 21.83 | 17.67 |
April | 0.529131E+11 | 31433.75 | 15-APR-10:40 | 24.83 | 14.24 | 0.181399E+11 | 11333.42 | 15-APR-17:30 | 25.85 | 15.37 |
May | 0.565725E+11 | 30041.62 | 06-MAY-10:50 | 27.02 | 19.73 | 0.187598E+11 | 11322.76 | 13-MAY-17:10 | 26.02 | 14.15 |
June | 0.563933E+11 | 30477.59 | 25-JUN-10:50 | 29.90 | 23.43 | 0.181720E+11 | 11319.67 | 10-JUN-17:19 | 29.90 | 23.43 |
July | 0.587755E+11 | 30992.45 | 08-JUL-10:50 | 33.53 | 24.57 | 0.187774E+11 | 11319.65 | 08-JUL-17:19 | 34.40 | 23.36 |
August | 0.588659E+11 | 30822.11 | 27-AUG-10:50 | 30.03 | 22.67 | 0.187869E+11 | 11319.65 | 26-AUG-17:19 | 30.03 | 22.67 |
September | 0.547761E+11 | 30326.70 | 09-SEP-10:50 | 30.32 | 23.97 | 0.181598E+11 | 11319.65 | 23-SEP-17:19 | 27.23 | 18.81 |
October | 0.536145E+11 | 29000.39 | 09-OCT-10:50 | 24.03 | 18.11 | 0.187386E+11 | 11319.57 | 14-OCT-17:19 | 21.67 | 13.44 |
November | 0.497392E+11 | 27551.56 | 11-NOV-11:40 | 18.50 | 11.57 | 0.181166E+11 | 11319.52 | 04-NOV-17:19 | 18.50 | 11.57 |
December | 0.493843E+11 | 27152.55 | 12-DEC-11:50 | 20.22 | 16.28 | 0.187102E+11 | 11319.56 | 02-DEC-18:19 | 20.22 | 16.28 |
Annual Sum or Average | 0.636611E+12 | 0.220703E+12 | ||||||||
Minimum of Months | 0.449206E+11 | 26695.83 | 12.43 | 5.39 | 0.169023E+11 | 11319.51 | 12.43 | 5.39 | ||
Maximum of Months | 0.588659E+11 | 31433.75 | 33.53 | 24.57 | 0.187869E+11 | 11333.42 | 34.40 | 23.43 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226923E+10 | 3905.55 | 31-JAN-21:30 | 16.05 | 11.74 | 0.126859E+10 | 745.62 | 05-JAN-03:39 | 16.05 | 11.74 |
February | 0.391498E+10 | 4147.46 | 28-FEB-22:10 | 18.63 | 10.80 | 0.114940E+10 | 789.35 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.797933E+10 | 4480.77 | 30-MAR-21:10 | 23.72 | 16.82 | 0.129108E+10 | 845.72 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.954949E+10 | 5166.29 | 15-APR-13:45 | 27.62 | 15.00 | 0.128641E+10 | 869.49 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.114344E+11 | 4873.87 | 20-MAY-15:30 | 28.05 | 18.93 | 0.139257E+10 | 905.11 | 19-MAY-21:10 | 28.05 | 18.93 |
June | 0.121033E+11 | 5123.27 | 24-JUN-18:02 | 31.93 | 22.02 | 0.145825E+10 | 951.68 | 13-JUN-21:10 | 31.93 | 22.02 |
July | 0.129126E+11 | 6058.43 | 08-JUL-17:13 | 34.40 | 23.36 | 0.154630E+10 | 1000.25 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.130270E+11 | 5472.96 | 18-AUG-15:30 | 34.70 | 23.13 | 0.156734E+10 | 997.72 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.113477E+11 | 5027.91 | 07-SEP-16:00 | 31.70 | 23.71 | 0.137464E+10 | 932.83 | 07-SEP-21:10 | 25.40 | 21.43 |
October | 0.905455E+10 | 4599.48 | 11-OCT-15:50 | 26.28 | 17.62 | 0.130502E+10 | 846.98 | 10-OCT-21:10 | 26.28 | 17.62 |
November | 0.640041E+10 | 4164.29 | 05-NOV-15:10 | 23.98 | 18.38 | 0.123054E+10 | 770.34 | 02-NOV-21:30 | 23.98 | 18.38 |
December | 0.380470E+10 | 4041.57 | 12-DEC-22:10 | 18.30 | 14.66 | 0.126913E+10 | 766.74 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.103798E+12 | 0.161393E+11 | ||||||||
Minimum of Months | 0.226923E+10 | 3905.55 | 16.05 | 10.80 | 0.114940E+10 | 745.62 | 16.05 | 10.80 | ||
Maximum of Months | 0.130270E+11 | 6058.43 | 34.70 | 23.71 | 0.156734E+10 | 1000.25 | 34.40 | 23.36 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476709E+09 | 1048.55 | 08-JAN-06:00 | -5.0 |
February | 0.238811E+09 | 1147.95 | 12-FEB-07:00 | -12.8 |
March | 7901026.06 | 248.78 | 22-MAR-09:20 | 4.40 |
April | 3147595.98 | 273.65 | 06-APR-06:07 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1105213.11 | 109.43 | 26-OCT-06:50 | 2.20 |
November | 29251462.31 | 719.43 | 21-NOV-07:10 | -2.8 |
December | 0.112894E+09 | 857.12 | 01-DEC-07:10 | -3.8 |
Annual Sum or Average | 0.869819E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.476709E+09 | 1147.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269805E+09 | 547.01 | 08-JAN-06:00 | -5.0 |
February | 0.156227E+09 | 548.21 | 12-FEB-09:03 | -10.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 1218897.30 | 99.56 | 22-NOV-04:50 | -2.8 |
December | 27487623.59 | 283.25 | 18-DEC-05:00 | -5.0 |
Annual Sum or Average | 0.454739E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.2 | |
Maximum of Months | 0.269805E+09 | 548.21 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310042E+09 | 385.51 | 08-JAN-06:00 | -5.0 |
February | 0.174275E+09 | 393.31 | 12-FEB-07:10 | -12.7 |
March | 962507.93 | 53.55 | 19-MAR-05:00 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 7989902.31 | 147.25 | 22-NOV-08:04 | -2.2 |
December | 61066716.64 | 265.59 | 18-DEC-08:03 | -5.0 |
Annual Sum or Average | 0.554336E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.7 | |
Maximum of Months | 0.310042E+09 | 393.31 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1923854.17 | 440.42 | 09-JAN-09:20 | -3.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 1923854.17 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 1923854.17 | 440.42 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.984327E+09 | 1547.60 | 07-JAN-19:13 | -5.6 |
February | 0.571651E+09 | 1546.08 | 12-FEB-09:02 | -10.2 |
March | 0.103546E+09 | 1468.29 | 23-MAR-08:62 | 6.97 |
April | 32517621.30 | 1458.31 | 06-APR-08:62 | 5.37 |
May | 2120276.83 | 1246.09 | 24-MAY-15:04 | 18.30 |
June | 1251264.18 | 1054.40 | 15-JUN-08:04 | 22.57 |
July | 658532.12 | 848.63 | 03-JUL-08:04 | 24.60 |
August | 731034.20 | 980.84 | 25-AUG-08:04 | 22.15 |
September | 2003843.61 | 1114.21 | 28-SEP-15:04 | 19.22 |
October | 63474714.50 | 1459.67 | 31-OCT-08:62 | 7.80 |
November | 0.212987E+09 | 1491.73 | 30-NOV-16:02 | 7.20 |
December | 0.600293E+09 | 1506.19 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.257556E+10 | |||
Minimum of Months | 658532.12 | 848.63 | -10.2 | |
Maximum of Months | 0.984327E+09 | 1547.60 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124640E+10 | 1550.81 | 07-JAN-16:13 | -4.3 |
February | 0.731788E+09 | 1565.21 | 12-FEB-09:02 | -10.2 |
March | 0.140240E+09 | 1469.37 | 23-MAR-08:62 | 6.97 |
April | 37343178.26 | 1464.75 | 06-APR-08:62 | 5.37 |
May | 1947600.40 | 1167.61 | 10-MAY-21:24 | 14.15 |
June | 667301.51 | 1070.26 | 07-JUN-08:53 | 18.90 |
July | 270700.38 | 607.22 | 28-JUL-21:54 | 17.80 |
August | 283784.37 | 756.18 | 09-AUG-08:04 | 26.38 |
September | 1927147.70 | 941.96 | 14-SEP-08:03 | 15.55 |
October | 84618618.98 | 1480.24 | 26-OCT-08:62 | 5.05 |
November | 0.323005E+09 | 1519.21 | 22-NOV-09:02 | 1.05 |
December | 0.815948E+09 | 1530.54 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.338444E+10 | |||
Minimum of Months | 270700.38 | 607.22 | -10.2 | |
Maximum of Months | 0.124640E+10 | 1565.21 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 559555.43 | 46.35 | 09-JAN-05:00 | -2.2 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 559555.43 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 559555.43 | 46.35 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171424E+09 | 462.27 | 06-JAN-16:02 | -0.6 |
February | 94624078.35 | 466.74 | 03-FEB-16:01 | 1.60 |
March | 3322796.83 | 455.44 | 07-MAR-16:03 | 15.78 |
April | 780929.03 | 432.95 | 08-APR-21:55 | 16.70 |
May | 431331.16 | 345.37 | 24-MAY-15:06 | 18.30 |
June | 107095.70 | 274.52 | 07-JUN-15:06 | 23.98 |
July | 50950.63 | 182.92 | 28-JUL-15:06 | 19.40 |
August | 113689.44 | 158.71 | 30-AUG-21:56 | 22.80 |
September | 374801.94 | 329.83 | 13-SEP-15:06 | 25.40 |
October | 1579830.69 | 417.40 | 23-OCT-15:05 | 17.62 |
November | 13629891.90 | 434.97 | 22-NOV-16:01 | 12.02 |
December | 62136488.15 | 448.77 | 03-DEC-16:01 | 6.52 |
Annual Sum or Average | 0.348576E+09 | |||
Minimum of Months | 50950.63 | 158.71 | -0.6 | |
Maximum of Months | 0.171424E+09 | 466.74 | 25.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.986669E+09 | 1508.05 | 07-JAN-16:13 | -4.3 |
February | 0.561141E+09 | 1479.67 | 06-FEB-09:02 | 0.10 |
March | 0.110168E+09 | 1430.86 | 23-MAR-08:62 | 6.97 |
April | 32093347.92 | 1030.23 | 30-APR-18:04 | 19.82 |
May | 1212105.08 | 994.69 | 10-MAY-18:04 | 20.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 113482.59 | 579.11 | 28-JUL-18:05 | 18.90 |
August | 14751.91 | 172.11 | 31-AUG-08:04 | 21.10 |
September | 1006947.41 | 860.45 | 29-SEP-15:04 | 21.52 |
October | 66145751.82 | 1424.28 | 31-OCT-08:62 | 7.80 |
November | 0.209622E+09 | 1458.74 | 30-NOV-16:02 | 7.20 |
December | 0.585803E+09 | 1519.41 | 05-DEC-16:03 | 15.82 |
Annual Sum or Average | 0.255399E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.3 | |
Maximum of Months | 0.986669E+09 | 1519.41 | 21.52 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125649E+10 | 1512.55 | 07-JAN-16:13 | -4.3 |
February | 0.715180E+09 | 1503.30 | 03-FEB-16:01 | 1.60 |
March | 0.145418E+09 | 1435.38 | 22-MAR-15:02 | 5.10 |
April | 37297160.17 | 1085.95 | 06-APR-18:03 | 14.63 |
May | 845080.24 | 783.36 | 11-MAY-21:54 | 16.70 |
June | 155430.83 | 562.41 | 01-JUN-21:54 | 22.80 |
July | 65353.55 | 329.93 | 28-JUL-21:54 | 17.80 |
August | 54927.64 | 206.20 | 30-AUG-21:54 | 22.80 |
September | 1267638.15 | 795.97 | 29-SEP-15:04 | 21.52 |
October | 90122771.80 | 1424.58 | 31-OCT-08:62 | 7.80 |
November | 0.313392E+09 | 1463.27 | 30-NOV-16:02 | 7.20 |
December | 0.798705E+09 | 1492.44 | 03-DEC-16:01 | 6.52 |
Annual Sum or Average | 0.335899E+10 | |||
Minimum of Months | 54927.64 | 206.20 | -4.3 | |
Maximum of Months | 0.125649E+10 | 1512.55 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76938460.15 | 507.18 | 07-JAN-17:00 | -5.0 |
February | 22427366.96 | 485.04 | 12-FEB-08:03 | -11.9 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 496719.81 | 114.84 | 18-DEC-07:07 | -5.1 |
Annual Sum or Average | 99862546.92 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 76938460.15 | 507.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145111E+10 | 1837.74 | 07-JAN-19:13 | -5.6 |
February | 0.870645E+09 | 1829.62 | 12-FEB-09:13 | -9.8 |
March | 0.205100E+09 | 1741.41 | 23-MAR-08:62 | 6.97 |
April | 63643305.22 | 1734.48 | 06-APR-08:62 | 5.37 |
May | 2896727.84 | 1225.92 | 24-MAY-15:04 | 18.30 |
June | 1224391.22 | 987.74 | 15-JUN-08:04 | 22.57 |
July | 683246.23 | 895.87 | 03-JUL-08:04 | 24.60 |
August | 810892.88 | 927.02 | 26-AUG-08:04 | 23.07 |
September | 3774479.65 | 1122.70 | 30-SEP-15:03 | 17.88 |
October | 0.132829E+09 | 1734.02 | 26-OCT-08:62 | 5.05 |
November | 0.381039E+09 | 1762.10 | 21-NOV-09:02 | -0.1 |
December | 0.948733E+09 | 1774.40 | 18-DEC-09:02 | -1.7 |
Annual Sum or Average | 0.406249E+10 | |||
Minimum of Months | 683246.23 | 895.87 | -9.8 | |
Maximum of Months | 0.145111E+10 | 1837.74 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177902E+10 | 1839.11 | 07-JAN-19:13 | -5.6 |
February | 0.107248E+10 | 1854.50 | 12-FEB-09:13 | -9.8 |
March | 0.257129E+09 | 1746.12 | 19-MAR-08:62 | 4.27 |
April | 68006397.01 | 1741.47 | 06-APR-08:62 | 5.37 |
May | 1787023.02 | 1099.85 | 24-MAY-15:04 | 18.30 |
June | 666940.44 | 1068.56 | 10-JUN-08:53 | 20.60 |
July | 151615.84 | 637.67 | 28-JUL-21:54 | 17.80 |
August | 310576.31 | 953.89 | 09-AUG-08:04 | 26.38 |
September | 2761008.62 | 1212.78 | 28-SEP-15:04 | 19.22 |
October | 0.166354E+09 | 1757.20 | 26-OCT-08:62 | 5.05 |
November | 0.536675E+09 | 1787.30 | 22-NOV-09:02 | 1.05 |
December | 0.122383E+10 | 1806.00 | 18-DEC-09:13 | -1.3 |
Annual Sum or Average | 0.510917E+10 | |||
Minimum of Months | 151615.84 | 637.67 | -9.8 | |
Maximum of Months | 0.177902E+10 | 1854.50 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403680E+09 | 945.65 | 07-JAN-16:13 | -4.3 |
February | 0.224815E+09 | 924.50 | 12-FEB-09:02 | -10.2 |
March | 37765527.47 | 918.94 | 02-MAR-16:04 | 16.52 |
April | 17155611.50 | 881.25 | 06-APR-08:62 | 5.37 |
May | 690353.62 | 609.77 | 10-MAY-18:04 | 20.92 |
June | 128598.71 | 300.51 | 02-JUN-08:04 | 22.48 |
July | 159801.71 | 238.32 | 14-JUL-08:05 | 27.48 |
August | 91062.93 | 160.03 | 11-AUG-08:06 | 23.48 |
September | 517884.22 | 328.16 | 29-SEP-08:04 | 14.78 |
October | 19820165.93 | 876.73 | 31-OCT-08:62 | 7.80 |
November | 61131423.39 | 904.28 | 30-NOV-16:02 | 7.20 |
December | 0.203957E+09 | 913.15 | 25-DEC-16:02 | 6.02 |
Annual Sum or Average | 0.969912E+09 | |||
Minimum of Months | 91062.93 | 160.03 | -10.2 | |
Maximum of Months | 0.403680E+09 | 945.65 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.757604E+09 | 2130.11 | 08-JAN-06:00 | -5.0 |
February | 0.386850E+09 | 2258.67 | 12-FEB-07:10 | -12.7 |
March | 659788.22 | 185.63 | 19-MAR-07:07 | 1.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 30385657.36 | 1132.59 | 22-NOV-07:10 | -3.2 |
December | 0.123824E+09 | 1666.36 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.129932E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.7 | |
Maximum of Months | 0.757604E+09 | 2258.67 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134280E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120899E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123603E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.111336E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.108100E+10 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.101086E+10 | 1701.53 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.106112E+10 | 1701.53 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.111364E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.117807E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.130270E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.128147E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.133830E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142683E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.101086E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.134280E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.946100E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854664E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.940393E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.900238E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.926941E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.894715E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.921296E+10 | 9504.80 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.930143E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.905589E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.943856E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.915501E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.943598E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110230E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854664E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.946100E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282832E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.254291E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269152E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249082E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246334E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233884E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243716E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251767E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256392E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.279095E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271429E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282403E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233884E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282832E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282832E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.254291E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269152E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249082E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246334E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233884E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243716E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251767E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256392E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.279095E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271429E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282403E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233884E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282832E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 756.16 | 0.564687E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 677874.56 | 0.392087E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4564766.64 | 0.244628E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18328843.29 | 0.147417E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43279781.17 | 65942826.69 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96714757.98 | 18880020.07 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115678E+09 | 6985949.65 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114353E+09 | 1312978.08 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48179513.77 | 34028941.82 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9223813.66 | 0.185880E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248367.38 | 0.291068E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50305.79 | 0.437480E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452301E+09 | 0.239040E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 756.16 | 1312978.08 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115678E+09 | 0.564687E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.92 | 0.218300E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 685520.10 | 0.152235E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2361682.19 | 97131278.12 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8579831.37 | 62131392.05 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17603049.01 | 31735398.91 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36886537.13 | 11641334.66 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44089322.20 | 5739984.86 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43661040.85 | 1778437.35 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19452292.54 | 17988123.99 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4996152.90 | 74970113.99 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 630724.99 | 0.113515E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85374.77 | 0.169077E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179032E+09 | 0.956242E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291.92 | 1778437.35 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44089322.20 | 0.218300E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.54 | 0.513558E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728919.62 | 0.355537E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6485910.32 | 0.219748E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22460153.64 | 0.136095E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43593153.76 | 66717384.10 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86895098.17 | 24873626.40 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102926E+09 | 13059520.90 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103758E+09 | 3575279.03 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48069775.15 | 38148355.56 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13716083.87 | 0.165279E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1650755.03 | 0.259760E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 209404.03 | 0.395322E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431493E+09 | 0.219167E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 686.54 | 3575279.03 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103758E+09 | 0.513558E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 398.30 | 0.296227E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1001089.72 | 0.204916E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3868029.65 | 0.126188E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13265546.70 | 77192579.11 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25923107.95 | 36614495.12 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51844639.65 | 13043037.43 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61478749.17 | 6427071.15 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62552264.43 | 1596264.44 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29239850.46 | 20380042.41 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8191402.27 | 93999621.09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 970420.00 | 0.149324E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120809.47 | 0.227979E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258456E+09 | 0.125389E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 398.30 | 1596264.44 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62552264.43 | 0.296227E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 981.56 | 0.733768E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 2257849.78 | 0.515070E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 6870513.87 | 0.330207E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 27005124.82 | 0.208554E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 56767144.13 | 0.102509E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.129466E+09 | 30068196.60 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.164751E+09 | 14478515.06 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.172000E+09 | 3744268.72 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 72866019.23 | 54746416.77 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 17504661.41 | 0.250605E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 2091671.86 | 0.386171E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 286045.25 | 0.572619E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.651866E+09 | 0.320254E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 981.56 | 3744268.72 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.172000E+09 | 0.733768E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.134280E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.48 | 0.125994E+10 |
February | 0.236489E+11 | 0.120899E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1565010.45 | 0.885842E+09 |
March | 0.262800E+11 | 0.123603E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8830946.41 | 0.579236E+09 |
April | 0.253579E+11 | 0.111336E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39403511.81 | 0.364966E+09 |
May | 0.262123E+11 | 0.108100E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93192112.79 | 0.190289E+09 |
June | 0.254132E+11 | 0.101086E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207085E+09 | 71891193.78 |
July | 0.261570E+11 | 0.106112E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247222E+09 | 36669840.64 |
August | 0.262677E+11 | 0.111364E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239102E+09 | 13149535.83 |
September | 0.253456E+11 | 0.117807E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98889070.91 | 0.109901E+09 |
October | 0.261693E+11 | 0.130270E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19340499.35 | 0.452850E+09 |
November | 0.253025E+11 | 0.128147E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2544921.31 | 0.676454E+09 |
December | 0.261570E+11 | 0.133830E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112392.75 | 0.986384E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142683E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957289E+09 | 0.562757E+10 |
Minimum of Months | 0.236489E+11 | 0.101086E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.48 | 13149535.83 |
Maximum of Months | 0.262800E+11 | 0.134280E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247222E+09 | 0.125994E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.946100E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4671.63 | 0.360654E+10 |
February | 0.702046E+11 | 0.854664E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9751933.51 | 0.253304E+10 |
March | 0.780153E+11 | 0.940393E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35257221.22 | 0.164284E+10 |
April | 0.752779E+11 | 0.900238E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135598E+09 | 0.105739E+10 |
May | 0.778146E+11 | 0.926941E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282747E+09 | 0.557189E+09 |
June | 0.754422E+11 | 0.894715E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599811E+09 | 0.213144E+09 |
July | 0.776503E+11 | 0.921296E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719641E+09 | 0.112492E+09 |
August | 0.779788E+11 | 0.930143E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708143E+09 | 38157057.78 |
September | 0.752414E+11 | 0.905589E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309116E+09 | 0.325524E+09 |
October | 0.776868E+11 | 0.943856E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75444862.17 | 0.128229E+10 |
November | 0.751137E+11 | 0.915501E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9214494.61 | 0.192116E+10 |
December | 0.776503E+11 | 0.943598E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1129094.95 | 0.281675E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110230E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288586E+10 | 0.161065E+11 |
Minimum of Months | 0.702046E+11 | 0.854664E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4671.63 | 38157057.78 |
Maximum of Months | 0.780153E+11 | 0.946100E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719641E+09 | 0.360654E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324684E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 458080.10 | 0.226488E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2901543.12 | 0.145799E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9859151.55 | 88950698.67 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23380920.90 | 40299017.04 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60917264.99 | 10529510.19 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78570935.88 | 4249735.11 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83354728.01 | 578359.94 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32809464.53 | 20016823.14 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6168351.87 | 0.107950E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401516.85 | 0.170615E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18423.21 | 0.252851E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298840E+09 | 0.139301E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578359.94 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83354728.01 | 0.324684E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320510E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 377736.48 | 0.224364E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440605.74 | 0.146059E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9060364.58 | 93666575.66 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21909650.13 | 46999240.67 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58359459.19 | 14059132.06 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75773197.64 | 7517953.96 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80222209.45 | 1971831.32 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30427158.14 | 23927472.43 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5359744.92 | 0.109595E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291190.51 | 0.167785E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21849.18 | 0.248041E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284243E+09 | 0.140450E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1971831.32 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80222209.45 | 0.320510E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93492175.38 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74972273.67 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21167.27 | 64508218.69 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191045.31 | 46452335.10 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1068387.47 | 30569797.65 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5543417.35 | 14975505.04 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859236.74 | 11368313.36 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7082202.18 | 8100857.74 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1555550.00 | 21802037.81 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116276.36 | 53386914.91 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71915138.28 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90338582.67 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23437282.67 | 0.581882E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8100857.74 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859236.74 | 93492175.38 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90863526.50 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 152623.52 | 63555796.97 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 754868.47 | 40684035.65 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2719520.66 | 25909742.93 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6276110.28 | 12818401.82 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16423293.90 | 3707301.27 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21284833.78 | 1983186.94 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22587703.37 | 452081.79 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8689313.89 | 6681160.65 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646285.25 | 30693506.93 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 102869.84 | 47433456.08 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15053.52 | 70623744.65 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80652476.48 | 0.395406E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452081.79 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22587703.37 | 90863526.50 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325234E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 458196.94 | 0.227342E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2925514.95 | 0.147082E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9852596.26 | 90149265.48 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23283173.92 | 40878447.78 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60806518.07 | 10778143.70 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78439428.54 | 4331111.91 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83229351.92 | 611978.99 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32764133.73 | 20249426.57 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6163731.70 | 0.108739E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 410308.74 | 0.171352E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18369.34 | 0.253393E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298351E+09 | 0.140014E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611978.99 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83229351.92 | 0.325234E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320788E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 358214.71 | 0.224747E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2538016.67 | 0.146018E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8958506.32 | 94017801.69 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21748004.49 | 47756770.62 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57958929.29 | 15231966.69 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75332074.15 | 8662631.82 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79933709.80 | 2588928.17 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30213054.04 | 24623443.57 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5356668.97 | 0.109672E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 393933.03 | 0.167310E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44916.53 | 0.248224E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282836E+09 | 0.140964E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588928.17 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79933709.80 | 0.320788E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.83 | 0.396047E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211794.40 | 0.274496E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4692531.46 | 0.170687E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15576882.13 | 0.107251E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31573615.98 | 53187293.37 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66981494.94 | 18757978.15 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80999869.66 | 9456740.98 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83162191.65 | 2278694.38 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36586722.09 | 29113617.82 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9772268.82 | 0.128496E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182782.26 | 0.200451E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151912.50 | 0.305053E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331892E+09 | 0.169527E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.83 | 2278694.38 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83162191.65 | 0.396047E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323716E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436168.87 | 0.226027E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822352.09 | 0.146017E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9596985.45 | 89515406.50 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22910006.90 | 40892825.41 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60147046.89 | 10771994.39 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77668744.54 | 4389240.25 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82335813.03 | 602929.57 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32169130.32 | 20274529.90 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5989475.54 | 0.108162E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 372837.55 | 0.170605E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16801.79 | 0.251926E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294465E+09 | 0.139290E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602929.57 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82335813.03 | 0.323716E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320390E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356280.19 | 0.224387E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2342524.32 | 0.146436E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8737369.79 | 95026127.26 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21463519.72 | 48240812.31 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57646568.80 | 14293192.51 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74957583.63 | 7579972.81 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79315282.25 | 1943965.20 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29821872.65 | 24230504.16 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5120915.40 | 0.110102E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 277944.60 | 0.167564E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22316.49 | 0.247257E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280062E+09 | 0.140745E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1943965.20 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79315282.25 | 0.320390E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170166E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220087.20 | 0.118740E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1442401.77 | 76137666.10 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4906807.26 | 46248471.02 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11745310.71 | 20948352.47 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30815066.11 | 5513855.78 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39773143.52 | 2247726.59 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42129230.07 | 312448.81 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16431264.39 | 10483866.52 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3033715.13 | 56483610.88 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185399.45 | 89598206.86 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8413.89 | 0.132891E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150691E+09 | 0.729771E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312448.81 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42129230.07 | 0.170166E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851866E+09 |
February | 0.415303E+11 | 0.254291E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1254210.48 | 0.609827E+09 |
March | 0.461508E+11 | 0.269152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4334320.41 | 0.417737E+09 |
April | 0.445315E+11 | 0.249082E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18230611.58 | 0.281264E+09 |
May | 0.460320E+11 | 0.246334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41425401.95 | 0.161830E+09 |
June | 0.446286E+11 | 0.233884E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106630E+09 | 65951991.09 |
July | 0.459349E+11 | 0.243716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134492E+09 | 40125289.36 |
August | 0.461292E+11 | 0.251767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132139E+09 | 16388458.60 |
September | 0.445099E+11 | 0.256392E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52094360.20 | 97031918.31 |
October | 0.459565E+11 | 0.279095E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11676437.87 | 0.327221E+09 |
November | 0.444343E+11 | 0.271429E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 916993.10 | 0.473753E+09 |
December | 0.459349E+11 | 0.282403E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124604.01 | 0.676432E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503318E+09 | 0.401943E+10 |
Minimum of Months | 0.415303E+11 | 0.233884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16388458.60 |
Maximum of Months | 0.461508E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134492E+09 | 0.851866E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860328E+09 |
February | 0.415303E+11 | 0.254291E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 980661.34 | 0.618202E+09 |
March | 0.461508E+11 | 0.269152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3654451.85 | 0.427934E+09 |
April | 0.445315E+11 | 0.249082E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16163292.70 | 0.287912E+09 |
May | 0.460320E+11 | 0.246334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38441304.35 | 0.165461E+09 |
June | 0.446286E+11 | 0.233884E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103842E+09 | 66914935.13 |
July | 0.459349E+11 | 0.243716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132144E+09 | 41006256.18 |
August | 0.461292E+11 | 0.251767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129636E+09 | 16800826.06 |
September | 0.445099E+11 | 0.256392E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49002241.52 | 99640234.34 |
October | 0.459565E+11 | 0.279095E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10161593.01 | 0.335860E+09 |
November | 0.444343E+11 | 0.271429E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 632919.44 | 0.484331E+09 |
December | 0.459349E+11 | 0.282403E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74671.80 | 0.686621E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484734E+09 | 0.409101E+10 |
Minimum of Months | 0.415303E+11 | 0.233884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16800826.06 |
Maximum of Months | 0.461508E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132144E+09 | 0.860328E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811499E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 144997.60 | 0.579796E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1909240.08 | 0.394438E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9907394.42 | 0.256178E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 28279269.59 | 0.138866E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 87810785.33 | 48582119.58 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.116931E+09 | 28430389.53 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.117346E+09 | 10382113.64 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 37372004.74 | 81078460.39 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5268683.38 | 0.306386E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12751.91 | 0.451683E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646486E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.404982E+09 | 0.375381E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10382113.64 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.117346E+09 | 0.811499E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703240E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1822872.53 | 0.487537E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7342333.27 | 0.303223E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23877492.80 | 0.189149E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48676217.40 | 93838182.72 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107316E+09 | 33806030.74 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129405E+09 | 16845283.58 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131729E+09 | 4267473.91 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60133900.03 | 48318180.80 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15425226.10 | 0.226631E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1813418.06 | 0.356564E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228946.32 | 0.542083E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527770E+09 | 0.300550E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4267473.91 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131729E+09 | 0.703240E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 31-JAN-15:00 | 354.81 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.34 | 28-FEB-14:40 | 430.12 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 30-MAR-16:00 | 246.26 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 17-APR-16:00 | 259.87 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.08 | 30-MAY-14:00 | 158.39 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.96 | 06-JUN-15:00 | 117.49 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 08-JUL-16:00 | 44.44 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.99 | 01-AUG-17:00 | 35.80 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.62 | 03-SEP-17:00 | 110.08 | 29-SEP-04:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 10-OCT-16:00 | 230.87 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 19-NOV-15:40 | 303.45 | 22-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 12-DEC-15:50 | 338.32 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 35.80 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 430.12 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 31-JAN-15:00 | 136.97 | 27-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 26-FEB-15:00 | 171.87 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 30-MAR-14:00 | 95.05 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 12-APR-14:00 | 100.52 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 | 30-MAY-14:00 | 64.39 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 | 06-JUN-15:00 | 50.15 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.53 | 08-JUL-15:00 | 23.83 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.10 | 01-AUG-15:00 | 20.05 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 07-SEP-15:00 | 46.25 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 | 10-OCT-16:00 | 89.64 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 19-NOV-15:00 | 117.12 | 22-NOV-06:05 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 12-DEC-15:00 | 130.58 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 20.05 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 58.53 | 171.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 31-JAN-15:00 | 323.70 | 27-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 26-FEB-15:00 | 406.17 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.76 | 30-MAR-14:00 | 224.63 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.27 | 12-APR-14:00 | 237.08 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.34 | 30-MAY-14:00 | 144.50 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.61 | 06-JUN-15:00 | 113.81 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.76 | 08-JUL-15:00 | 53.57 | 28-JUL-23:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 | 01-AUG-15:00 | 46.00 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.36 | 07-SEP-15:00 | 105.74 | 14-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 10-OCT-16:00 | 210.61 | 26-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 05-NOV-16:00 | 276.79 | 22-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 12-DEC-14:00 | 308.63 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 46.00 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 135.76 | 406.17 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 31-JAN-15:00 | 186.76 | 27-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 26-FEB-15:00 | 232.67 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.29 | 30-MAR-14:00 | 129.60 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 | 12-APR-14:00 | 136.78 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.36 | 30-MAY-14:00 | 83.37 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.02 | 06-JUN-15:00 | 64.38 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 08-JUL-15:00 | 29.17 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 01-AUG-15:00 | 24.82 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 07-SEP-15:00 | 59.29 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.18 | 10-OCT-16:00 | 121.51 | 26-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 05-NOV-16:00 | 159.69 | 22-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 12-DEC-14:00 | 178.06 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 24.82 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 232.67 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 1.42 | 31-JAN-15:00 | 474.44 | 07-JAN-22:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 56.31 | 28-FEB-14:10 | 558.67 | 12-FEB-07:20 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 94.63 | 30-MAR-15:40 | 322.76 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 110.85 | 12-APR-14:00 | 333.28 | 06-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 132.97 | 19-MAY-14:00 | 224.08 | 11-MAY-06:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 180.74 | 06-JUN-15:00 | 164.92 | 08-JUN-06:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 212.26 | 08-JUL-15:00 | 90.05 | 28-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 191.05 | 01-AUG-15:00 | 72.65 | 25-AUG-06:20 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 146.91 | 07-SEP-16:00 | 161.28 | 14-SEP-06:20 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 124.32 | 10-OCT-16:00 | 321.95 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 47.94 | 05-NOV-16:00 | 403.72 | 22-NOV-07:20 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 25.76 | 12-DEC-14:00 | 452.40 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.42 | 72.65 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 212.26 | 558.67 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 31-JAN-15:00 | 784.48 | 27-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 28-FEB-14:40 | 984.31 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.59 | 30-MAR-14:00 | 544.36 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.53 | 17-APR-14:00 | 577.68 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.79 | 30-MAY-14:00 | 360.74 | 11-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.92 | 06-JUN-15:00 | 296.19 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.84 | 08-JUL-16:00 | 148.07 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.66 | 01-AUG-15:00 | 112.68 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.20 | 08-SEP-14:00 | 272.58 | 14-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.11 | 10-OCT-16:00 | 521.02 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.46 | 19-NOV-15:30 | 670.83 | 22-NOV-06:40 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 12-DEC-15:50 | 747.97 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 112.68 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 323.84 | 984.31 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 31-JAN-15:00 | 2241.06 | 27-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.57 | 28-FEB-14:40 | 2812.17 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.91 | 30-MAR-14:00 | 1569.87 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.58 | 12-APR-14:00 | 1697.20 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.43 | 30-MAY-14:00 | 1075.47 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.78 | 06-JUN-15:00 | 861.31 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 968.93 | 08-JUL-16:00 | 431.47 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 884.23 | 01-AUG-15:00 | 346.98 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.36 | 07-SEP-15:00 | 799.90 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.32 | 10-OCT-16:00 | 1521.22 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.87 | 19-NOV-15:00 | 1946.40 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.38 | 12-DEC-15:00 | 2136.78 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 346.98 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 968.93 | 2812.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.09 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:09 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 32.60 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 19.12 | 25-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:07 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.06 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:10 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:09 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 34.42 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 26.56 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.08 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 12-DEC-14:00 | 197.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 60.31 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 66.02 | 03-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 30-MAR-14:10 | 48.24 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 12-APR-14:00 | 49.46 | 06-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 19-MAY-14:00 | 35.95 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 06-JUN-15:00 | 29.42 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 08-JUL-15:00 | 17.99 | 28-JUL-23:40 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 02-AUG-16:00 | 15.70 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 07-SEP-16:00 | 27.67 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 10-OCT-16:00 | 46.61 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 55.42 | 21-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 61.38 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 66.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 57.80 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 26-FEB-16:07 | 72.45 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 30-MAR-16:00 | 40.19 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 17-APR-15:10 | 42.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 19-MAY-16:00 | 25.96 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 06-JUN-15:10 | 19.32 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 08-JUL-15:10 | 10.77 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 02-AUG-16:00 | 7.21 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 07-SEP-16:00 | 18.12 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 10-OCT-16:00 | 37.70 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-NOV-16:00 | 49.46 | 22-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 12-DEC-14:00 | 55.12 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 72.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.08 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:07 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.02 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 08-JUL-15:10 | 32.47 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 21.11 | 25-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 05-NOV-16:00 | 177.22 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:07 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.07 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:09 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:09 | 151.93 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 33.81 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 25.79 | 27-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.08 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 12-DEC-14:00 | 197.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 31-JAN-15:00 | 249.43 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.52 | 26-FEB-15:00 | 312.89 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 | 30-MAR-14:00 | 173.19 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.65 | 12-APR-14:00 | 182.77 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 | 30-MAY-14:00 | 113.86 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.29 | 06-JUN-15:00 | 89.76 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 | 08-JUL-15:00 | 41.58 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 01-AUG-15:00 | 33.31 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.11 | 07-SEP-15:00 | 81.89 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 10-OCT-16:00 | 162.41 | 26-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 | 19-NOV-15:00 | 213.33 | 22-NOV-06:50 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 12-DEC-15:00 | 237.83 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 33.31 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 | 312.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.57 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:09 | 260.11 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.48 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:10 | 152.39 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 08-JUL-15:50 | 31.18 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 19.51 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.36 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.54 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.68 | 22-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 12-DEC-16:09 | 197.97 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 260.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 207.55 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:07 | 259.33 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:09 | 152.38 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.43 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 08-JUL-15:50 | 34.47 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 25.38 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.53 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.67 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 12-DEC-14:00 | 197.96 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 259.33 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 106.20 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 26-FEB-16:10 | 133.08 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 30-MAR-16:00 | 73.92 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 | 17-APR-15:10 | 77.97 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 19-MAY-16:00 | 47.81 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 06-JUN-15:10 | 35.64 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 08-JUL-15:10 | 16.80 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 02-AUG-16:00 | 9.98 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 07-SEP-16:00 | 33.44 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 10-OCT-16:00 | 69.35 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 05-NOV-16:00 | 90.91 | 22-NOV-06:17 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 12-DEC-16:10 | 101.29 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 133.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 527.69 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 | 26-FEB-15:00 | 644.08 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 30-MAR-14:00 | 381.59 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.70 | 12-APR-14:00 | 404.83 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.04 | 19-MAY-14:00 | 267.64 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.93 | 06-JUN-15:00 | 215.35 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 08-JUL-15:00 | 114.23 | 28-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.78 | 01-AUG-15:00 | 94.75 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.53 | 07-SEP-15:00 | 201.31 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 10-OCT-14:00 | 362.42 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 | 19-NOV-15:00 | 458.98 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 12-DEC-15:00 | 493.13 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.75 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 644.08 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 529.93 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 26-FEB-15:00 | 647.05 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.12 | 30-MAR-14:00 | 385.49 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.88 | 12-APR-14:00 | 407.71 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.41 | 19-MAY-14:00 | 270.88 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 | 06-JUN-15:00 | 217.23 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 08-JUL-15:00 | 114.23 | 28-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.75 | 01-AUG-15:00 | 94.76 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 07-SEP-15:00 | 203.60 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.28 | 10-OCT-14:00 | 365.29 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | 19-NOV-15:00 | 461.46 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 12-DEC-15:00 | 495.47 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | 647.05 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 500.46 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 13.02 | 28-FEB-14:00 | 596.31 | 12-FEB-08:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 52.62 | 30-MAR-15:40 | 360.86 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 68.81 | 12-APR-14:00 | 353.67 | 06-APR-06:30 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 91.83 | 19-MAY-15:40 | 246.77 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 141.74 | 06-JUN-15:00 | 184.93 | 08-JUN-06:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 174.08 | 08-JUL-15:00 | 102.18 | 28-JUL-23:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 152.09 | 02-AUG-16:00 | 84.75 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 106.44 | 07-SEP-16:00 | 177.39 | 14-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 83.23 | 10-OCT-16:00 | 341.03 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.48 | 05-NOV-16:00 | 426.57 | 22-NOV-07:40 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 477.61 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 174.08 | 596.31 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 442.38 | 27-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 28-FEB-14:40 | 547.48 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 | 30-MAR-14:00 | 307.41 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.27 | 12-APR-14:00 | 324.36 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.01 | 19-MAY-14:00 | 198.27 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.09 | 06-JUN-15:00 | 151.48 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 08-JUL-15:00 | 69.76 | 28-JUL-23:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.10 | 01-AUG-15:00 | 57.41 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.24 | 07-SEP-15:00 | 138.20 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 10-OCT-16:00 | 288.31 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 19-NOV-15:00 | 378.45 | 22-NOV-06:40 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 | 12-DEC-15:00 | 421.84 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 547.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14707.78 | 31-JAN-22:00 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14506.34 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14096.64 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13629.52 | 19-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14126.23 | 15-MAY-19:03 | 26837.75 | 39570.93 | 28897.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14779.35 | 30-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15605.97 | 14-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16476.04 | 18-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17269.92 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17344.20 | 13-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17425.58 | 21-NOV-23:03 | 46007.57 | 17587.08 | 16223.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16774.75 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13629.52 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17425.58 | 46007.57 | 39570.93 | 28897.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2030.41 | 29-JAN-13:30 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 |
February | 2142.77 | 21-FEB-14:30 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
March | 2107.57 | 30-MAR-14:20 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 0.00 |
April | 2334.73 | 15-APR-13:45 | 1559.38 | 663.99 | 1010.36 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 0.00 |
May | 2032.15 | 19-MAY-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 48.56 | 0.00 |
June | 2126.40 | 13-JUN-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 73.89 | 0.00 |
July | 2487.47 | 08-JUL-17:04 | 6237.50 | 3187.16 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 113.75 | 0.00 |
August | 2734.00 | 19-AUG-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
September | 2565.98 | 25-SEP-15:03 | 4548.18 | 1161.99 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 | 0.00 |
October | 2717.95 | 10-OCT-13:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 | 0.00 |
November | 2174.91 | 15-NOV-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 |
December | 2110.52 | 10-DEC-14:00 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2030.41 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2734.00 | 6237.50 | 3187.16 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 113.75 | 104.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1383.20 | 31-JAN-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 |
February | 1460.84 | 28-FEB-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 |
March | 1553.35 | 30-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
April | 1563.27 | 17-APR-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
May | 1603.35 | 19-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
June | 1644.00 | 27-JUN-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 | 0.00 |
July | 1902.62 | 07-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 1979.28 | 18-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
September | 1752.06 | 08-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 0.00 |
October | 1587.61 | 10-OCT-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 |
November | 1453.23 | 02-NOV-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 |
December | 1438.80 | 12-DEC-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1383.20 | 1203.84 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1979.28 | 1354.32 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 34.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1078.47 | 31-JAN-22:00 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
February | 1122.37 | 28-FEB-22:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 |
March | 1195.64 | 30-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 |
April | 1211.97 | 15-APR-13:45 | 381.89 | 760.20 | 1237.08 | 0.00 | 0.00 | 0.00 | 0.00 | 61.52 | 0.00 |
May | 1272.21 | 19-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | 0.00 |
June | 1357.27 | 29-JUN-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 0.00 |
July | 1408.00 | 07-JUL-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 66.73 | 0.00 |
August | 1412.64 | 18-AUG-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 0.00 |
September | 1346.72 | 08-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
October | 1223.09 | 18-OCT-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 0.00 |
November | 1139.53 | 03-NOV-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 |
December | 1114.83 | 12-DEC-22:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1078.47 | 254.59 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1412.64 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 68.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 595.95 | 31-JAN-21:55 | 391.68 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 |
February | 637.50 | 28-FEB-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
March | 677.33 | 30-MAR-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 0.00 |
April | 711.68 | 15-APR-13:45 | 293.76 | 279.81 | 356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 0.00 |
May | 718.86 | 19-MAY-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
June | 768.97 | 29-JUN-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 0.00 |
July | 800.47 | 07-JUL-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 0.00 |
August | 803.46 | 18-AUG-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 | 0.00 |
September | 762.93 | 08-SEP-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 |
October | 693.04 | 18-OCT-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 | 0.00 |
November | 645.87 | 03-NOV-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
December | 633.89 | 12-DEC-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 595.95 | 195.84 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 803.46 | 391.68 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 | 37.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36415.54 | 31-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 |
February | 36945.84 | 28-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 |
March | 37436.77 | 30-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
April | 37640.52 | 17-APR-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 |
May | 39178.31 | 15-MAY-19:03 | 2116.80 | 975.25 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 46.28 | 0.00 |
June | 38350.53 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.92 | 0.00 |
July | 38634.75 | 07-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 97.79 | 0.00 |
August | 38537.68 | 18-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 105.81 | 0.00 |
September | 38235.88 | 07-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
October | 37522.39 | 10-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 36836.70 | 03-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 |
December | 36658.68 | 12-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36415.54 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39178.31 | 2116.80 | 975.25 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 105.81 | 99.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8974.16 | 29-JAN-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.63 |
February | 9147.19 | 28-FEB-22:30 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.13 |
March | 9640.09 | 30-MAR-21:50 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 |
April | 10202.75 | 15-APR-13:45 | 20491.20 | 415.93 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 | 0.00 |
May | 9626.20 | 19-MAY-21:12 | 61473.60 | 4537.41 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
June | 10523.26 | 13-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 0.00 |
July | 11364.65 | 07-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 | 0.00 |
August | 11836.73 | 18-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 166.90 | 0.00 |
September | 10947.03 | 07-SEP-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 | 0.00 |
October | 11478.46 | 10-OCT-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 124.97 | 0.00 |
November | 9480.22 | 11-NOV-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.95 |
December | 9251.98 | 10-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8974.16 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11836.73 | 61473.60 | 4537.41 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 166.90 | 246.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29705.89 | 31-JAN-22:30 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.87 |
February | 30923.92 | 28-FEB-22:52 | 273737.88 | 38019.20 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.99 |
March | 32340.02 | 30-MAR-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 |
April | 32182.57 | 17-APR-22:00 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.83 |
May | 32878.43 | 19-MAY-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.25 |
June | 33897.61 | 13-JUN-22:00 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 227.06 | 0.00 |
July | 37401.50 | 07-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 448.14 | 0.00 |
August | 38596.59 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 | 0.00 |
September | 35356.06 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.55 | 0.00 |
October | 32865.66 | 10-OCT-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.16 |
November | 31004.48 | 02-NOV-22:00 | 228114.90 | 31682.67 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.29 |
December | 30914.45 | 12-DEC-23:00 | 182491.92 | 25346.13 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29705.89 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38596.59 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 | 668.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3385.98 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 |
February | 3485.55 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 0.00 |
March | 3480.32 | 13-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 0.00 |
April | 3483.79 | 09-APR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
May | 3481.79 | 10-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
June | 3103.19 | 16-JUN-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 40.61 | 0.00 |
July | 3125.51 | 30-JUL-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 | 0.00 |
August | 3135.90 | 20-AUG-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 0.00 |
September | 3090.09 | 04-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 0.00 |
October | 3255.88 | 31-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.11 |
November | 3476.94 | 08-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
December | 3429.18 | 10-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3090.09 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3485.55 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 | 66.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2733.83 | 29-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 |
February | 3416.28 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 |
March | 3411.13 | 13-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
April | 3529.84 | 26-APR-18:41 | 1247.40 | 1424.67 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 |
May | 3539.41 | 09-MAY-20:41 | 1441.80 | 1424.67 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
June | 3099.32 | 05-JUN-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
July | 3152.05 | 02-JUL-21:51 | 1108.80 | 1209.46 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
August | 3090.32 | 28-AUG-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 | 0.00 |
September | 3376.53 | 18-SEP-16:01 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 0.00 |
October | 3154.32 | 15-OCT-16:21 | 858.60 | 528.25 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 0.00 |
November | 3398.80 | 08-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
December | 3249.87 | 10-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2733.83 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3539.41 | 1441.80 | 1424.67 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 | 63.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 171.49 | 31-JAN-15:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
February | 381.09 | 26-FEB-14:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
March | 368.61 | 30-MAR-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
April | 348.70 | 15-APR-13:53 | 0.00 | 110.67 | 100.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
May | 297.83 | 19-MAY-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 0.00 |
June | 340.60 | 24-JUN-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
July | 383.57 | 08-JUL-17:30 | 0.00 | 95.02 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 0.00 |
August | 415.57 | 19-AUG-13:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | 0.00 |
September | 475.61 | 24-SEP-12:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 0.00 |
October | 510.90 | 10-OCT-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
November | 428.88 | 08-NOV-14:10 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
December | 401.18 | 10-DEC-14:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 171.49 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 510.90 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 17.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 983.67 | 31-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 |
February | 1215.62 | 28-FEB-22:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 |
March | 1211.37 | 31-MAR-20:12 | 961.20 | 597.13 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 |
April | 1217.35 | 09-APR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
May | 1295.98 | 09-MAY-20:41 | 1441.80 | 895.70 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
June | 1158.11 | 18-JUN-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | 0.00 |
July | 1161.36 | 13-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 |
August | 1156.01 | 10-AUG-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 |
September | 1153.94 | 07-SEP-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 0.00 |
October | 1214.77 | 11-OCT-21:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 |
November | 1149.92 | 08-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
December | 1013.38 | 11-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 983.67 | 252.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1295.98 | 1441.80 | 895.70 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 18.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3042.92 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 |
February | 3167.79 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
March | 3169.80 | 13-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 0.00 |
April | 3166.24 | 09-APR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
May | 3140.92 | 10-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
June | 2887.59 | 13-JUN-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 0.00 |
July | 2881.83 | 21-JUL-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 |
August | 2860.23 | 26-AUG-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
September | 2844.80 | 12-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 0.00 |
October | 2843.24 | 02-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
November | 3148.81 | 08-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 |
December | 3110.49 | 10-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2843.24 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3169.80 | 970.20 | 1108.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 38.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2083.24 | 31-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
February | 3114.48 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
March | 3115.75 | 13-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 0.00 |
April | 3121.38 | 09-APR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
May | 3203.44 | 18-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
June | 3261.40 | 04-JUN-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
July | 3029.48 | 25-JUL-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 |
August | 3092.16 | 26-AUG-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
September | 3126.47 | 15-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 |
October | 2794.32 | 09-OCT-18:01 | 819.00 | 1245.03 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
November | 2890.08 | 08-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
December | 2289.78 | 12-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2083.24 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3261.40 | 819.00 | 1245.03 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 16.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1974.47 | 31-JAN-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.51 |
February | 2067.14 | 28-FEB-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
March | 2159.36 | 30-MAR-21:51 | 15843.49 | 8714.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
April | 2356.37 | 15-APR-13:45 | 3017.81 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 | 0.00 |
May | 2278.94 | 19-MAY-21:12 | 9053.42 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
June | 2409.74 | 29-JUN-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
July | 2460.35 | 07-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.79 | 0.00 |
August | 2482.97 | 18-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 | 0.00 |
September | 2373.48 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 0.00 |
October | 2203.76 | 11-OCT-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 |
November | 2033.94 | 02-NOV-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.13 |
December | 2023.80 | 12-DEC-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1974.47 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2482.97 | 15843.49 | 8714.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 | 55.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3528.05 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 |
February | 3652.95 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
March | 3646.73 | 13-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 0.00 |
April | 3656.75 | 09-APR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
May | 3644.44 | 10-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 |
June | 3202.53 | 18-JUN-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 0.00 |
July | 3196.00 | 26-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 | 0.00 |
August | 3250.89 | 23-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 0.00 |
September | 3252.10 | 03-SEP-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 0.00 |
October | 3438.19 | 31-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 |
November | 3640.23 | 08-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 |
December | 3582.40 | 10-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3196.00 | 324.00 | 348.65 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3656.75 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 | 67.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1996.00 | 20-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.76 |
February | 3572.25 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
March | 3560.19 | 13-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
April | 3755.71 | 09-APR-20:11 | 1247.40 | 1600.75 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.57 |
May | 3816.08 | 09-MAY-20:41 | 1441.80 | 1424.67 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 |
June | 3254.89 | 05-JUN-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
July | 3287.78 | 02-JUL-21:51 | 1108.80 | 1209.46 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
August | 3261.80 | 08-AUG-17:52 | 583.20 | 715.00 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 |
September | 3506.46 | 18-SEP-16:01 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 | 0.00 |
October | 3412.49 | 15-OCT-16:21 | 858.60 | 528.25 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
November | 3545.68 | 08-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
December | 3330.45 | 10-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1996.00 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3816.08 | 1441.80 | 1600.75 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 67.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1874.13 | 28-JAN-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
February | 1919.16 | 27-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
March | 1925.05 | 13-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
April | 1877.60 | 09-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
May | 1873.17 | 10-MAY-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
June | 1708.33 | 28-JUN-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 |
July | 1704.88 | 23-JUL-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 |
August | 1711.39 | 21-AUG-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
September | 1715.68 | 04-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 0.00 |
October | 1856.49 | 12-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 |
November | 1920.42 | 08-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
December | 1900.06 | 10-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1704.88 | 378.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1925.05 | 970.20 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 37.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17429.84 | 19-JAN-22:57 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 |
February | 18638.12 | 28-FEB-22:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.46 |
March | 20349.90 | 30-MAR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
April | 20452.44 | 17-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 |
May | 21373.72 | 19-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
June | 22600.77 | 13-JUN-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.40 | 0.00 |
July | 23355.63 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 0.00 |
August | 23089.80 | 18-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 0.00 |
September | 21779.68 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
October | 20228.26 | 18-OCT-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
November | 18540.84 | 03-NOV-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.09 |
December | 18049.71 | 12-DEC-22:55 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17429.84 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23355.63 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 111.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19351.70 | 19-JAN-22:57 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 |
February | 20534.49 | 28-FEB-22:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.46 |
March | 22143.89 | 30-MAR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
April | 22098.16 | 17-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 |
May | 22949.96 | 30-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
June | 24068.74 | 13-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 | 0.00 |
July | 24658.84 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 0.00 |
August | 24375.18 | 18-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 0.00 |
September | 23250.29 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
October | 22049.37 | 18-OCT-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
November | 20506.51 | 03-NOV-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.09 |
December | 19995.12 | 12-DEC-22:55 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19351.70 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24658.84 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 111.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26695.83 | 29-JAN-11:40 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 177.70 |
February | 27921.45 | 26-FEB-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 |
March | 28352.18 | 30-MAR-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 32.72 |
April | 31433.75 | 15-APR-10:40 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 5.85 | 0.00 |
May | 30041.62 | 06-MAY-10:50 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 41.72 | 0.00 |
June | 30477.59 | 25-JUN-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 82.14 | 0.00 |
July | 30992.45 | 08-JUL-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 130.95 | 0.00 |
August | 30822.11 | 27-AUG-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.71 | 0.00 |
September | 30326.70 | 09-SEP-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 87.74 | 0.00 |
October | 29000.39 | 09-OCT-10:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
November | 27551.56 | 11-NOV-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 82.23 |
December | 27152.55 | 12-DEC-11:50 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26695.83 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31433.75 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 130.95 | 177.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3905.55 | 31-JAN-21:30 | 2129.28 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.12 |
February | 4147.46 | 28-FEB-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 |
March | 4480.77 | 30-MAR-21:10 | 9581.76 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 0.00 |
April | 5166.29 | 15-APR-13:45 | 3193.92 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.56 | 0.00 |
May | 4873.87 | 20-MAY-15:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.28 | 0.00 |
June | 5123.27 | 24-JUN-18:02 | 9581.76 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.74 | 0.00 |
July | 6058.43 | 08-JUL-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.92 | 0.00 |
August | 5472.96 | 18-AUG-15:30 | 2661.60 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 0.00 |
September | 5027.91 | 07-SEP-16:00 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.83 | 0.00 |
October | 4599.48 | 11-OCT-15:50 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 0.00 |
November | 4164.29 | 05-NOV-15:10 | 4790.88 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 | 0.00 |
December | 4041.57 | 12-DEC-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3905.55 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6058.43 | 9581.76 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 74.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.356683E+12 | 287428.45 | 19-JAN-20:49 | 0.707666E+12 | 578340.49 | 03-JAN-18:19 |
February | 0.337200E+12 | 287176.65 | 28-FEB-20:49 | 0.572230E+12 | 577680.80 | 12-FEB-17:10 |
March | 0.406177E+12 | 339990.54 | 30-MAR-19:10 | 0.540324E+12 | 517876.71 | 22-MAR-18:10 |
April | 0.451251E+12 | 337378.70 | 04-APR-19:00 | 0.451565E+12 | 525662.25 | 05-APR-20:00 |
May | 0.551832E+12 | 367444.90 | 30-MAY-19:49 | 0.412991E+12 | 351074.50 | 01-MAY-17:10 |
June | 0.621399E+12 | 391363.59 | 28-JUN-19:49 | 0.374769E+12 | 336545.41 | 02-JUN-17:10 |
July | 0.698002E+12 | 411174.63 | 07-JUL-19:49 | 0.378460E+12 | 318180.43 | 03-JUL-17:00 |
August | 0.711247E+12 | 413922.72 | 18-AUG-19:19 | 0.378037E+12 | 318160.38 | 31-AUG-17:19 |
September | 0.588048E+12 | 390611.80 | 07-SEP-19:10 | 0.373775E+12 | 333484.44 | 28-SEP-17:30 |
October | 0.459849E+12 | 380202.13 | 18-OCT-19:00 | 0.452321E+12 | 459259.27 | 25-OCT-20:49 |
November | 0.386040E+12 | 318500.76 | 27-NOV-20:10 | 0.542260E+12 | 547945.41 | 21-NOV-20:49 |
December | 0.360237E+12 | 277349.48 | 12-DEC-20:10 | 0.681902E+12 | 566841.21 | 03-DEC-18:40 |
Annual Sum or Average | 0.592796E+13 | 0.586630E+13 | ||||
Minimum of Months | 0.337200E+12 | 277349.48 | 0.373775E+12 | 318160.38 | ||
Maximum of Months | 0.711247E+12 | 413922.72 | 0.707666E+12 | 578340.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671446E+11 | 0.192036E+11 | 0.140828E+12 | 0.544239E+11 | 0.368513E+11 | 0.398401E+10 | 0.00 | 0.858326E+10 | 0.00 | 0.00 | 0.128281E+11 | 0.770631E+10 | 0.00 |
February | 0.606091E+11 | 0.163904E+11 | 0.127191E+12 | 0.491572E+11 | 0.329343E+11 | 0.501152E+10 | 0.00 | 0.265205E+11 | 0.00 | 0.00 | 0.777631E+10 | 0.696370E+10 | 0.00 |
March | 0.666049E+11 | 0.167606E+11 | 0.140882E+12 | 0.544262E+11 | 0.362320E+11 | 0.827458E+10 | 0.00 | 0.662554E+11 | 0.00 | 0.00 | 0.385246E+10 | 0.770461E+10 | 0.00 |
April | 0.641287E+11 | 0.148358E+11 | 0.136245E+12 | 0.526676E+11 | 0.362928E+11 | 0.893634E+10 | 0.00 | 0.118737E+12 | 0.00 | 0.00 | 0.688540E+10 | 0.746635E+10 | 0.00 |
May | 0.659154E+11 | 0.141251E+11 | 0.140860E+12 | 0.544244E+11 | 0.392445E+11 | 0.968641E+10 | 0.00 | 0.201245E+12 | 0.00 | 0.00 | 0.133485E+11 | 0.770569E+10 | 0.00 |
June | 0.636076E+11 | 0.131404E+11 | 0.136336E+12 | 0.526697E+11 | 0.406312E+11 | 0.982816E+10 | 0.00 | 0.272746E+12 | 0.00 | 0.00 | 0.198610E+11 | 0.745802E+10 | 0.00 |
July | 0.658492E+11 | 0.137771E+11 | 0.140770E+12 | 0.544220E+11 | 0.428298E+11 | 0.105193E+11 | 0.00 | 0.332057E+12 | 0.00 | 0.00 | 0.247888E+11 | 0.771350E+10 | 0.00 |
August | 0.660429E+11 | 0.147839E+11 | 0.140892E+12 | 0.544259E+11 | 0.432411E+11 | 0.106403E+11 | 0.00 | 0.342745E+12 | 0.00 | 0.00 | 0.254674E+11 | 0.770528E+10 | 0.00 |
September | 0.644097E+11 | 0.156205E+11 | 0.136256E+12 | 0.526678E+11 | 0.385262E+11 | 0.965745E+10 | 0.00 | 0.240899E+12 | 0.00 | 0.00 | 0.174201E+11 | 0.746758E+10 | 0.00 |
October | 0.669938E+11 | 0.175749E+11 | 0.140818E+12 | 0.544238E+11 | 0.369675E+11 | 0.904612E+10 | 0.00 | 0.113694E+12 | 0.00 | 0.00 | 0.738424E+10 | 0.770443E+10 | 0.00 |
November | 0.649060E+11 | 0.182634E+11 | 0.136330E+12 | 0.526690E+11 | 0.347784E+11 | 0.732151E+10 | 0.00 | 0.542093E+11 | 0.00 | 0.00 | 0.510774E+10 | 0.745060E+10 | 0.00 |
December | 0.671261E+11 | 0.195441E+11 | 0.140770E+12 | 0.544228E+11 | 0.360288E+11 | 0.539392E+10 | 0.00 | 0.172118E+11 | 0.00 | 0.00 | 0.687694E+10 | 0.771443E+10 | 0.00 |
Annual Sum or Average | 0.783338E+12 | 0.194020E+12 | 0.165818E+13 | 0.640800E+12 | 0.454558E+12 | 0.982996E+11 | 0.00 | 0.179490E+13 | 0.00 | 0.00 | 0.151597E+12 | 0.907605E+11 | 0.00 |
Minimum of Months | 0.606091E+11 | 0.131404E+11 | 0.127191E+12 | 0.491572E+11 | 0.329343E+11 | 0.398401E+10 | 0.00 | 0.858326E+10 | 0.00 | 0.00 | 0.385246E+10 | 0.696370E+10 | 0.00 |
Maximum of Months | 0.671446E+11 | 0.195441E+11 | 0.140892E+12 | 0.544262E+11 | 0.432411E+11 | 0.106403E+11 | 0.00 | 0.342745E+12 | 0.00 | 0.00 | 0.254674E+11 | 0.771443E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.284417E+12 | 0.00 | 0.271331E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.189601E+12 | 0.00 | 0.245426E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.122486E+12 | 0.00 | 0.265814E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.581021E+11 | 0.00 | 0.246507E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.193872E+11 | 0.00 | 0.241625E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.513871E+10 | 0.00 | 0.222516E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.382719E+10 | 0.00 | 0.222813E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.364723E+10 | 0.00 | 0.222352E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.574708E+10 | 0.00 | 0.221058E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.608463E+11 | 0.00 | 0.239572E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.150634E+12 | 0.00 | 0.244535E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.265788E+12 | 0.00 | 0.264294E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.116962E+13 | 0.00 | 0.290784E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.364723E+10 | 0.00 | 0.221058E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.284417E+12 | 0.00 | 0.271331E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 21157.07 | 07-JAN-16:19 | 4218.00 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 19117.33 | 11-FEB-19:10 | 4226.13 | 12-FEB-17:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 01-MAR-07:19 | 21427.69 | 30-MAR-18:10 | 4172.89 | 18-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.97 | 03-APR-06:19 | 24150.86 | 17-APR-18:10 | 4176.26 | 05-APR-22:49 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.97 | 08-MAY-06:19 | 23744.29 | 15-MAY-18:19 | 4340.88 | 30-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:30 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39169.68 | 23-JUN-06:19 | 24588.40 | 05-JUN-18:19 | 4505.33 | 26-JUN-21:00 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39169.86 | 28-JUL-06:19 | 25586.54 | 07-JUL-18:19 | 4712.76 | 18-JUL-18:00 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:19 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.97 | 14-AUG-06:19 | 25188.72 | 02-AUG-18:19 | 4587.33 | 23-AUG-22:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 01-SEP-06:19 | 23495.06 | 07-SEP-18:10 | 4414.17 | 09-SEP-21:00 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 21105.39 | 10-OCT-18:10 | 4460.99 | 18-OCT-21:00 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 18782.20 | 05-NOV-15:09 | 4202.99 | 21-NOV-09:00 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 18457.14 | 13-DEC-21:10 | 4220.94 | 18-DEC-10:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.68 | 18457.14 | 4172.89 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 25586.54 | 4712.76 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 74347.67 | 19-JAN-22:00 | 0.00 | 0.00 | 9938.94 | 02-JAN-03:49 | 4738.99 | 04-JAN-07:10 | 0.00 |
February | 90794.30 | 26-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-03:09 | 4738.74 | 09-FEB-19:10 | 0.00 |
March | 110516.47 | 30-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 04-MAR-16:19 | 4738.53 | 09-MAR-07:10 | 0.00 |
April | 112323.44 | 04-APR-15:09 | 0.00 | 0.00 | 9938.94 | 02-APR-12:50 | 4738.66 | 03-APR-18:10 | 0.00 |
May | 145470.37 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-15:30 | 4738.53 | 22-MAY-18:10 | 0.00 |
June | 171754.44 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-08:30 | 4738.72 | 28-JUN-18:10 | 0.00 |
July | 196491.06 | 08-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.73 | 07-JUL-18:10 | 0.00 |
August | 188954.93 | 18-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.73 | 23-AUG-18:10 | 0.00 |
September | 170301.49 | 07-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.64 | 11-SEP-18:10 | 0.00 |
October | 152394.60 | 18-OCT-21:00 | 0.00 | 0.00 | 9938.94 | 01-OCT-15:20 | 4738.25 | 11-OCT-18:30 | 0.00 |
November | 106389.48 | 05-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 02-NOV-12:30 | 4738.35 | 10-NOV-07:10 | 0.00 |
December | 81309.29 | 12-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.72 | 26-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 74347.67 | 0.00 | 0.00 | 9938.94 | 4738.25 | 0.00 | |||
Maximum of Months | 196491.06 | 0.00 | 0.00 | 9938.94 | 4738.99 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 287428.45 | 19-JAN-20:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 15446.63 | 3490.55 | 0.00 | 67258.73 | 0.00 |
February | 287176.65 | 28-FEB-20:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 16899.89 | 3444.51 | 0.00 | 66188.63 | 0.00 |
March | 339990.54 | 30-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20181.90 | 3840.97 | 0.00 | 104618.04 | 0.00 |
April | 337378.70 | 04-APR-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 19708.52 | 3801.50 | 0.00 | 103002.41 | 0.00 |
May | 367444.90 | 30-MAY-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21263.00 | 4159.49 | 0.00 | 131195.64 | 0.00 |
June | 391363.59 | 28-JUN-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 22476.59 | 4322.67 | 0.00 | 153245.60 | 0.00 |
July | 411174.63 | 07-JUL-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 23986.43 | 4345.88 | 0.00 | 172051.05 | 0.00 |
August | 413922.72 | 18-AUG-19:19 | 64632.59 | 86439.81 | 12338.45 | 31552.61 | 24124.76 | 4320.06 | 0.00 | 174878.36 | 0.00 |
September | 390611.80 | 07-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22535.12 | 4299.24 | 0.00 | 152584.44 | 0.00 |
October | 380202.13 | 18-OCT-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 17894.17 | 4371.19 | 0.00 | 147016.40 | 0.00 |
November | 318500.76 | 27-NOV-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 16306.45 | 3654.88 | 0.00 | 88846.96 | 0.00 |
December | 277349.48 | 12-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 16255.19 | 3455.29 | 0.00 | 56835.12 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 277349.48 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 15446.63 | 3444.51 | 0.00 | 56835.12 | 0.00 | |
Maximum of Months | 413922.72 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 24124.76 | 4371.19 | 0.00 | 174878.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 268438.17 | 03-JAN-16:10 | 0.00 | 267002.04 | 31-JAN-18:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 260767.61 | 07-FEB-09:09 | 0.00 | 270809.75 | 10-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 233713.02 | 18-MAR-08:09 | 0.00 | 252005.66 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 237714.96 | 06-APR-07:10 | 0.00 | 246791.26 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 97457.69 | 11-MAY-05:00 | 0.00 | 244542.74 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 30053.09 | 10-JUN-04:00 | 0.00 | 232353.83 | 02-JUN-19:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 11490.74 | 29-JUL-04:40 | 0.00 | 214486.44 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 9929.66 | 21-AUG-03:30 | 0.00 | 214352.55 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 35964.55 | 30-SEP-15:09 | 0.00 | 229413.34 | 28-SEP-20:10 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 233196.22 | 26-OCT-07:10 | 0.00 | 244263.31 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 244102.47 | 22-NOV-09:30 | 0.00 | 246512.37 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 259611.63 | 21-DEC-09:09 | 0.00 | 250245.74 | 28-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 9929.66 | 0.00 | 214352.55 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 268438.17 | 0.00 | 270809.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.39 | 4.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 6.17 | 20.08 | 6.17 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.17 | 20.20 | 10.17 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 20.39 | 6.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.48 | 2.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.83 | 20.51 | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.48 | 2.83 | 20.48 | 0.17 | 20.52 | 0.17 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.51 | 2.00 | 20.51 | 0.17 | 21.69 | 0.17 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.46 | 3.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.33 | 20.43 | 1.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.84 | 1.00 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
November | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 0.67 | 20.54 | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 5.67 | 20.47 | 5.67 | 20.47 | 2.33 | 20.69 | 2.33 | 20.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.55 | 3.50 | 20.55 | 1.00 | 21.84 | 1.00 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.33 | 1.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 0.33 | 20.20 | 0.33 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.78 | 2.67 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.88 | 3.83 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.30 | 1.67 | 20.30 | 12.00 | 21.48 | 12.00 | 21.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.33 | 1.33 | 20.33 | 3.83 | 21.88 | 3.83 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.44 | 1.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.46 | 2.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.52 | 1.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.46 | 3.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.33 | 20.51 | 1.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.88 | 0.83 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.09 | 2.33 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.13 | 5.67 | 22.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.20 | 6.67 | 22.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.06 | 4.50 | 22.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.11 | 2.50 | 22.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 20.48 | 4.67 | 20.48 | 22.50 | 21.64 | 22.50 | 21.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.51 | 3.33 | 20.51 | 6.67 | 22.20 | 6.67 | 22.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.43 | 1.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 0.67 | 20.47 | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.75 | 1.50 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.44 | 2.50 | 20.44 | 3.33 | 20.96 | 3.33 | 21.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.47 | 1.83 | 20.47 | 1.50 | 21.75 | 1.50 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.43 | 3.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 1.33 | 20.35 | 1.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.75 | 3.50 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.82 | 0.17 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 5.50 | 20.42 | 5.50 | 20.42 | 6.33 | 20.90 | 6.33 | 21.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.52 | 3.67 | 20.52 | 3.50 | 21.83 | 3.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.47 | 1.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.82 | 1.83 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.47 | 1.17 | 20.47 | 8.00 | 21.48 | 8.00 | 21.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.47 | 1.17 | 20.47 | 2.17 | 21.82 | 2.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.76 | 2.00 | 24.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.70 | 0.17 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 24.76 | 2.17 | 24.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.76 | 2.00 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 4.33 | 21.36 | 4.33 | 21.36 |
February | 672.00 | 21.18 | 43.50 | 21.16 | 43.50 | 21.16 |
March | 744.00 | 21.08 | 31.17 | 21.07 | 31.17 | 21.07 |
April | 720.00 | 20.98 | 18.83 | 20.98 | 18.83 | 20.98 |
May | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
June | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
July | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
August | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
September | 688.83 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
October | 727.33 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
November | 713.17 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
December | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
Annual Sum or Average | 8705.33 | 21.87 | 97.83 | 21.86 | 97.83 | 21.85 |
Minimum of Months | 672.00 | 20.98 | 0.00 | 20.98 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 22.98 | 43.50 | 22.98 | 43.50 | 22.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 401.33 | 21.03 | 401.33 | 21.02 |
February | 666.67 | 21.12 | 234.17 | 21.08 | 234.17 | 21.06 |
March | 731.50 | 21.25 | 55.00 | 21.24 | 52.00 | 21.22 |
April | 691.67 | 21.31 | 17.33 | 21.31 | 14.83 | 21.31 |
May | 735.17 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
June | 581.83 | 21.84 | 21.83 | 21.89 | 0.00 | 21.89 |
July | 472.50 | 21.90 | 157.33 | 22.31 | 0.00 | 22.31 |
August | 368.33 | 22.08 | 264.67 | 22.72 | 0.00 | 22.72 |
September | 560.50 | 21.59 | 97.50 | 21.90 | 0.00 | 21.90 |
October | 669.83 | 21.37 | 36.67 | 21.49 | 1.00 | 21.49 |
November | 692.83 | 21.19 | 66.17 | 21.17 | 65.17 | 21.16 |
December | 737.67 | 21.13 | 234.00 | 21.10 | 233.17 | 21.08 |
Annual Sum or Average | 7652.50 | 21.39 | 1586.00 | 21.49 | 1001.67 | 21.44 |
Minimum of Months | 368.33 | 21.06 | 0.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.08 | 401.33 | 22.72 | 401.33 | 22.72 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.08 | 34.83 | 21.08 | 34.83 | 21.08 |
February | 672.00 | 21.18 | 54.50 | 21.17 | 54.50 | 21.16 |
March | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
April | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 733.17 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
June | 621.50 | 22.33 | 26.17 | 22.38 | 0.00 | 22.38 |
July | 560.83 | 22.44 | 81.17 | 22.61 | 0.00 | 22.61 |
August | 499.83 | 22.59 | 112.33 | 22.81 | 0.00 | 22.81 |
September | 651.67 | 22.21 | 21.00 | 22.26 | 0.00 | 22.26 |
October | 740.83 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
November | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
December | 744.00 | 21.15 | 6.50 | 21.15 | 6.50 | 21.15 |
Annual Sum or Average | 8151.83 | 21.71 | 336.50 | 21.76 | 95.83 | 21.76 |
Minimum of Months | 499.83 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
Maximum of Months | 744.00 | 22.59 | 112.33 | 22.81 | 54.50 | 22.81 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 459.50 | 21.00 | 459.50 | 21.00 |
February | 672.00 | 21.01 | 233.50 | 21.01 | 233.50 | 21.01 |
March | 744.00 | 21.07 | 68.00 | 21.07 | 68.00 | 21.06 |
April | 720.00 | 21.23 | 3.33 | 21.22 | 3.33 | 21.22 |
May | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
June | 720.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
July | 703.17 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
August | 706.50 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
September | 720.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
October | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
November | 720.00 | 21.04 | 38.33 | 21.04 | 38.33 | 21.04 |
December | 744.00 | 21.01 | 212.83 | 21.01 | 212.83 | 21.00 |
Annual Sum or Average | 8681.67 | 21.59 | 1015.50 | 21.53 | 1015.50 | 21.48 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.82 | 459.50 | 22.82 | 459.50 | 22.82 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 483.00 | 21.00 | 483.00 | 21.00 |
February | 672.00 | 21.00 | 250.17 | 21.00 | 250.17 | 21.00 |
March | 744.00 | 21.03 | 73.67 | 21.03 | 73.67 | 21.02 |
April | 720.00 | 21.12 | 4.00 | 21.12 | 4.00 | 21.12 |
May | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
June | 720.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
July | 744.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
August | 743.83 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
September | 720.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
October | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
November | 720.00 | 21.01 | 54.17 | 21.01 | 54.17 | 21.01 |
December | 744.00 | 21.00 | 247.17 | 21.00 | 247.17 | 21.00 |
Annual Sum or Average | 8759.83 | 21.51 | 1112.17 | 21.45 | 1112.17 | 21.40 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.66 | 483.00 | 22.66 | 483.00 | 22.66 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 543.00 | 21.66 | 221.00 | 22.17 | 119.33 | 22.42 |
February | 458.50 | 21.74 | 228.83 | 22.25 | 112.33 | 22.50 |
March | 429.67 | 21.97 | 300.17 | 22.45 | 139.00 | 22.69 |
April | 304.33 | 22.40 | 349.50 | 22.66 | 143.67 | 22.89 |
May | 226.00 | 23.12 | 479.50 | 22.68 | 163.50 | 22.92 |
June | 190.17 | 23.61 | 557.67 | 22.62 | 170.83 | 22.86 |
July | 185.50 | 23.78 | 603.83 | 22.61 | 178.33 | 22.84 |
August | 185.83 | 23.86 | 619.83 | 22.61 | 184.17 | 22.84 |
September | 194.00 | 23.45 | 504.67 | 22.68 | 163.33 | 22.91 |
October | 309.83 | 22.41 | 369.50 | 22.62 | 146.83 | 22.86 |
November | 429.67 | 21.89 | 284.17 | 22.38 | 128.00 | 22.63 |
December | 512.50 | 21.73 | 251.33 | 22.24 | 124.67 | 22.48 |
Annual Sum or Average | 3969.00 | 22.32 | 4770.00 | 22.50 | 1774.00 | 22.74 |
Minimum of Months | 185.50 | 21.66 | 221.00 | 22.17 | 112.33 | 22.42 |
Maximum of Months | 543.00 | 23.86 | 619.83 | 22.68 | 184.17 | 22.92 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.50 | 21.22 | 83.67 | 21.19 | 83.67 | 21.18 |
February | 662.50 | 21.42 | 49.00 | 21.39 | 49.00 | 21.37 |
March | 688.00 | 21.75 | 20.50 | 21.80 | 0.00 | 21.80 |
April | 612.17 | 21.78 | 26.17 | 21.85 | 0.00 | 21.85 |
May | 571.50 | 21.91 | 69.17 | 22.07 | 0.00 | 22.07 |
June | 366.00 | 22.08 | 268.00 | 22.65 | 27.17 | 22.69 |
July | 309.83 | 22.30 | 377.17 | 22.96 | 63.17 | 23.02 |
August | 293.83 | 22.83 | 520.50 | 23.27 | 146.83 | 23.34 |
September | 370.67 | 22.04 | 283.50 | 22.65 | 30.50 | 22.70 |
October | 563.83 | 21.88 | 103.17 | 22.12 | 9.00 | 22.13 |
November | 667.67 | 21.66 | 10.83 | 21.69 | 0.00 | 21.69 |
December | 727.50 | 21.38 | 9.50 | 21.38 | 6.50 | 21.38 |
Annual Sum or Average | 6576.00 | 21.74 | 1821.17 | 22.08 | 415.83 | 22.11 |
Minimum of Months | 293.83 | 21.22 | 9.50 | 21.19 | 0.00 | 21.18 |
Maximum of Months | 742.50 | 22.83 | 520.50 | 23.27 | 146.83 | 23.34 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.25 | 5.83 | 21.25 | 5.83 | 21.25 |
February | 672.00 | 21.42 | 4.50 | 21.42 | 4.50 | 21.41 |
March | 738.67 | 21.72 | 0.50 | 21.72 | 0.00 | 21.72 |
April | 706.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
May | 687.00 | 22.08 | 10.17 | 22.10 | 0.00 | 22.10 |
June | 475.67 | 22.23 | 112.00 | 22.50 | 0.00 | 22.50 |
July | 413.00 | 22.29 | 210.00 | 22.75 | 0.00 | 22.75 |
August | 345.50 | 22.38 | 292.83 | 22.96 | 0.00 | 22.96 |
September | 525.17 | 22.24 | 81.17 | 22.42 | 0.00 | 22.42 |
October | 717.50 | 21.98 | 4.17 | 21.99 | 0.00 | 21.99 |
November | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
December | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
Annual Sum or Average | 7488.50 | 21.82 | 721.17 | 21.97 | 10.33 | 21.97 |
Minimum of Months | 345.50 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 22.38 | 292.83 | 22.96 | 5.83 | 22.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 510.67 | 20.79 | 510.67 | 20.77 |
February | 672.00 | 21.03 | 292.67 | 20.92 | 292.67 | 20.86 |
March | 736.67 | 21.41 | 32.17 | 21.38 | 32.17 | 21.35 |
April | 701.33 | 21.53 | 13.33 | 21.53 | 13.33 | 21.54 |
May | 695.00 | 21.56 | 3.17 | 21.56 | 3.17 | 21.57 |
June | 622.00 | 21.47 | 4.50 | 21.48 | 4.50 | 21.49 |
July | 621.33 | 21.41 | 18.17 | 21.45 | 15.67 | 21.49 |
August | 606.83 | 21.38 | 8.50 | 21.40 | 7.17 | 21.42 |
September | 648.33 | 21.50 | 11.33 | 21.52 | 11.33 | 21.54 |
October | 724.33 | 21.44 | 41.33 | 21.44 | 41.33 | 21.43 |
November | 718.17 | 21.34 | 87.17 | 21.29 | 87.17 | 21.25 |
December | 744.00 | 21.05 | 315.00 | 20.97 | 315.00 | 20.92 |
Annual Sum or Average | 8234.00 | 21.32 | 1338.00 | 21.26 | 1334.17 | 21.20 |
Minimum of Months | 606.83 | 20.85 | 3.17 | 20.79 | 3.17 | 20.77 |
Maximum of Months | 744.00 | 21.56 | 510.67 | 21.56 | 510.67 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.63 | 596.00 | 20.59 | 596.00 | 20.58 |
February | 672.00 | 20.92 | 345.17 | 20.78 | 345.17 | 20.71 |
March | 737.83 | 21.46 | 64.83 | 21.39 | 64.83 | 21.33 |
April | 687.00 | 21.79 | 39.50 | 21.83 | 30.83 | 21.84 |
May | 652.50 | 21.90 | 65.00 | 22.05 | 47.83 | 22.11 |
June | 599.33 | 21.80 | 63.17 | 21.99 | 55.00 | 22.12 |
July | 608.33 | 21.78 | 106.50 | 22.04 | 98.67 | 22.22 |
August | 608.83 | 21.69 | 74.00 | 21.90 | 72.33 | 22.05 |
September | 653.67 | 21.90 | 71.33 | 22.05 | 67.33 | 22.15 |
October | 723.50 | 21.56 | 78.50 | 21.57 | 78.00 | 21.57 |
November | 720.00 | 21.19 | 169.00 | 21.11 | 169.00 | 21.05 |
December | 744.00 | 20.79 | 501.83 | 20.72 | 501.83 | 20.69 |
Annual Sum or Average | 8151.00 | 21.43 | 2174.83 | 21.38 | 2126.83 | 21.33 |
Minimum of Months | 599.33 | 20.63 | 39.50 | 20.59 | 30.83 | 20.58 |
Maximum of Months | 744.00 | 21.90 | 596.00 | 22.05 | 596.00 | 22.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 462.17 | 20.84 | 462.17 | 20.82 |
February | 672.00 | 21.10 | 231.67 | 21.00 | 231.67 | 20.94 |
March | 744.00 | 21.44 | 23.50 | 21.42 | 23.50 | 21.41 |
April | 718.67 | 21.80 | 5.83 | 21.81 | 5.83 | 21.83 |
May | 737.33 | 22.02 | 29.83 | 22.07 | 29.83 | 22.11 |
June | 718.50 | 22.00 | 50.33 | 22.10 | 50.17 | 22.19 |
July | 742.33 | 22.01 | 85.33 | 22.16 | 85.00 | 22.27 |
August | 743.17 | 21.93 | 66.17 | 22.04 | 66.17 | 22.14 |
September | 718.83 | 22.00 | 46.83 | 22.09 | 46.83 | 22.16 |
October | 744.00 | 21.62 | 29.50 | 21.65 | 29.50 | 21.69 |
November | 720.00 | 21.31 | 36.50 | 21.29 | 36.50 | 21.27 |
December | 744.00 | 21.05 | 221.00 | 20.99 | 221.00 | 20.96 |
Annual Sum or Average | 8746.83 | 21.60 | 1288.67 | 21.57 | 1288.17 | 21.55 |
Minimum of Months | 672.00 | 20.90 | 5.83 | 20.84 | 5.83 | 20.82 |
Maximum of Months | 744.00 | 22.02 | 462.17 | 22.16 | 462.17 | 22.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 488.00 | 20.82 | 488.00 | 20.80 |
February | 672.00 | 21.08 | 283.33 | 20.97 | 283.33 | 20.91 |
March | 744.00 | 21.50 | 35.33 | 21.47 | 35.33 | 21.44 |
April | 715.50 | 21.64 | 10.83 | 21.64 | 10.83 | 21.64 |
May | 698.00 | 21.60 | 2.67 | 21.61 | 2.67 | 21.61 |
June | 596.33 | 21.42 | 1.67 | 21.42 | 1.33 | 21.43 |
July | 580.00 | 21.29 | 13.67 | 21.33 | 12.33 | 21.36 |
August | 581.17 | 21.30 | 5.50 | 21.32 | 5.33 | 21.33 |
September | 643.17 | 21.50 | 11.33 | 21.52 | 11.33 | 21.55 |
October | 730.67 | 21.50 | 41.50 | 21.49 | 41.50 | 21.49 |
November | 720.00 | 21.39 | 79.17 | 21.34 | 79.17 | 21.31 |
December | 744.00 | 21.07 | 288.33 | 21.00 | 288.33 | 20.96 |
Annual Sum or Average | 8168.83 | 21.35 | 1261.33 | 21.28 | 1259.50 | 21.23 |
Minimum of Months | 580.00 | 20.88 | 1.67 | 20.82 | 1.33 | 20.80 |
Maximum of Months | 744.00 | 21.64 | 488.00 | 21.64 | 488.00 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 589.33 | 20.60 | 589.33 | 20.59 |
February | 672.00 | 20.94 | 335.67 | 20.81 | 335.67 | 20.74 |
March | 744.00 | 21.46 | 66.33 | 21.41 | 66.33 | 21.37 |
April | 713.33 | 21.90 | 29.67 | 21.91 | 27.33 | 21.92 |
May | 657.50 | 21.98 | 67.33 | 22.14 | 47.33 | 22.21 |
June | 565.00 | 21.79 | 72.50 | 22.10 | 56.00 | 22.27 |
July | 575.00 | 21.80 | 109.00 | 22.16 | 98.83 | 22.40 |
August | 583.50 | 21.68 | 75.67 | 21.95 | 72.17 | 22.15 |
September | 654.50 | 21.96 | 77.00 | 22.14 | 68.83 | 22.26 |
October | 742.67 | 21.63 | 74.33 | 21.64 | 73.83 | 21.64 |
November | 720.00 | 21.16 | 160.00 | 21.10 | 160.00 | 21.06 |
December | 744.00 | 20.79 | 489.33 | 20.73 | 489.33 | 20.71 |
Annual Sum or Average | 8115.50 | 21.45 | 2146.17 | 21.42 | 2085.00 | 21.39 |
Minimum of Months | 565.00 | 20.65 | 29.67 | 20.60 | 27.33 | 20.59 |
Maximum of Months | 744.00 | 21.98 | 589.33 | 22.16 | 589.33 | 22.40 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 268.83 | 21.00 | 268.83 | 21.00 |
February | 672.00 | 21.02 | 182.50 | 21.02 | 182.50 | 21.02 |
March | 744.00 | 21.12 | 28.83 | 21.11 | 28.83 | 21.11 |
April | 720.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
May | 744.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
June | 720.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
July | 744.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
August | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
September | 720.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
October | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
November | 720.00 | 21.03 | 10.00 | 21.03 | 10.00 | 21.03 |
December | 744.00 | 21.01 | 114.83 | 21.00 | 114.83 | 21.00 |
Annual Sum or Average | 8760.00 | 21.60 | 605.00 | 21.56 | 605.00 | 21.53 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.64 | 268.83 | 22.64 | 268.83 | 22.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.74 | 585.50 | 20.69 | 585.50 | 20.67 |
February | 671.17 | 20.94 | 358.83 | 20.82 | 358.83 | 20.77 |
March | 733.33 | 21.36 | 84.50 | 21.29 | 84.50 | 21.24 |
April | 680.17 | 21.46 | 35.00 | 21.46 | 35.00 | 21.46 |
May | 655.67 | 21.45 | 17.00 | 21.46 | 16.67 | 21.46 |
June | 593.00 | 21.38 | 17.67 | 21.43 | 11.17 | 21.45 |
July | 599.33 | 21.35 | 53.50 | 21.47 | 28.50 | 21.51 |
August | 589.00 | 21.32 | 48.50 | 21.46 | 16.33 | 21.49 |
September | 621.00 | 21.41 | 29.50 | 21.47 | 22.67 | 21.50 |
October | 707.67 | 21.36 | 65.00 | 21.33 | 64.50 | 21.32 |
November | 715.83 | 21.27 | 165.67 | 21.20 | 165.67 | 21.15 |
December | 744.00 | 20.93 | 454.50 | 20.85 | 454.50 | 20.81 |
Annual Sum or Average | 8054.17 | 21.24 | 1915.17 | 21.17 | 1843.83 | 21.11 |
Minimum of Months | 589.00 | 20.74 | 17.00 | 20.69 | 11.17 | 20.67 |
Maximum of Months | 744.00 | 21.46 | 585.50 | 21.47 | 585.50 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 641.50 | 20.53 | 641.50 | 20.52 |
February | 671.00 | 20.85 | 404.33 | 20.72 | 404.33 | 20.67 |
March | 732.17 | 21.40 | 131.00 | 21.29 | 130.83 | 21.21 |
April | 649.33 | 21.71 | 72.17 | 21.80 | 52.33 | 21.79 |
May | 600.83 | 21.78 | 102.17 | 22.04 | 64.50 | 22.11 |
June | 574.17 | 21.73 | 82.33 | 21.98 | 64.67 | 22.13 |
July | 590.33 | 21.73 | 139.33 | 22.05 | 112.00 | 22.22 |
August | 588.33 | 21.63 | 103.00 | 21.89 | 83.67 | 22.05 |
September | 614.17 | 21.79 | 90.83 | 21.97 | 82.67 | 22.09 |
October | 706.50 | 21.48 | 111.67 | 21.49 | 105.17 | 21.48 |
November | 719.33 | 21.12 | 282.50 | 21.02 | 282.50 | 20.97 |
December | 744.00 | 20.68 | 583.33 | 20.63 | 583.33 | 20.60 |
Annual Sum or Average | 7934.17 | 21.34 | 2744.17 | 21.30 | 2607.50 | 21.25 |
Minimum of Months | 574.17 | 20.56 | 72.17 | 20.53 | 52.33 | 20.52 |
Maximum of Months | 744.00 | 21.79 | 641.50 | 22.05 | 641.50 | 22.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.21 | 310.33 | 21.08 | 310.33 | 21.01 |
February | 664.67 | 21.28 | 186.00 | 21.17 | 186.00 | 21.09 |
March | 727.33 | 21.50 | 23.83 | 21.47 | 23.83 | 21.45 |
April | 687.83 | 21.53 | 8.33 | 21.53 | 8.33 | 21.52 |
May | 694.00 | 21.55 | 6.17 | 21.56 | 6.17 | 21.57 |
June | 642.67 | 21.53 | 11.33 | 21.55 | 11.33 | 21.57 |
July | 638.33 | 21.46 | 26.00 | 21.50 | 26.00 | 21.54 |
August | 624.67 | 21.43 | 18.00 | 21.46 | 18.00 | 21.49 |
September | 636.50 | 21.47 | 13.83 | 21.50 | 12.17 | 21.52 |
October | 679.67 | 21.41 | 33.83 | 21.42 | 30.00 | 21.41 |
November | 691.50 | 21.47 | 32.83 | 21.44 | 32.83 | 21.41 |
December | 735.33 | 21.33 | 143.17 | 21.24 | 143.17 | 21.18 |
Annual Sum or Average | 8166.50 | 21.43 | 813.67 | 21.39 | 808.17 | 21.35 |
Minimum of Months | 624.67 | 21.21 | 6.17 | 21.08 | 6.17 | 21.01 |
Maximum of Months | 744.00 | 21.55 | 310.33 | 21.56 | 310.33 | 21.57 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.83 | 22.01 | 19.83 | 22.05 | 9.17 | 22.07 |
February | 594.67 | 22.17 | 36.83 | 22.26 | 7.50 | 22.27 |
March | 531.50 | 22.46 | 118.50 | 22.71 | 26.83 | 22.75 |
April | 337.17 | 22.60 | 284.50 | 23.16 | 43.83 | 23.21 |
May | 228.33 | 23.12 | 490.67 | 23.57 | 108.33 | 23.62 |
June | 110.33 | 23.70 | 609.67 | 23.77 | 88.33 | 23.79 |
July | 74.33 | 23.81 | 691.17 | 23.77 | 66.17 | 23.79 |
August | 83.50 | 23.91 | 684.83 | 23.79 | 79.00 | 23.81 |
September | 214.67 | 23.22 | 510.67 | 23.62 | 119.33 | 23.67 |
October | 438.67 | 22.47 | 228.00 | 22.92 | 49.67 | 22.99 |
November | 594.67 | 22.36 | 79.50 | 22.53 | 29.00 | 22.57 |
December | 699.17 | 22.18 | 31.50 | 22.24 | 13.00 | 22.26 |
Annual Sum or Average | 4626.83 | 22.45 | 3785.67 | 23.05 | 640.17 | 23.11 |
Minimum of Months | 74.33 | 22.01 | 19.83 | 22.05 | 7.50 | 22.07 |
Maximum of Months | 719.83 | 23.91 | 691.17 | 23.79 | 119.33 | 23.81 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 684.17 | 22.12 | 31.00 | 22.19 | 6.33 | 22.21 |
February | 511.83 | 22.21 | 68.00 | 22.40 | 5.50 | 22.41 |
March | 408.83 | 22.53 | 183.17 | 22.92 | 22.50 | 22.96 |
April | 214.33 | 22.72 | 392.33 | 23.42 | 33.50 | 23.45 |
May | 106.83 | 23.39 | 596.83 | 23.70 | 65.33 | 23.73 |
June | 16.00 | 23.43 | 683.17 | 23.76 | 9.17 | 23.76 |
July | 11.83 | 23.59 | 728.00 | 23.79 | 8.83 | 23.79 |
August | 3.33 | 23.99 | 735.83 | 23.77 | 3.33 | 23.77 |
September | 95.17 | 23.49 | 612.00 | 23.70 | 65.83 | 23.73 |
October | 274.00 | 22.54 | 336.17 | 23.22 | 41.83 | 23.27 |
November | 483.50 | 22.45 | 130.17 | 22.73 | 23.00 | 22.77 |
December | 632.67 | 22.28 | 45.50 | 22.38 | 6.17 | 22.40 |
Annual Sum or Average | 3442.50 | 22.42 | 4542.17 | 23.19 | 291.33 | 23.22 |
Minimum of Months | 3.33 | 22.12 | 31.00 | 22.19 | 3.33 | 22.21 |
Maximum of Months | 684.17 | 23.99 | 735.83 | 23.79 | 65.83 | 23.79 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 609.33 | 23.22 | 556.00 | 23.55 | 445.83 | 23.67 |
February | 558.33 | 23.32 | 513.33 | 23.60 | 425.67 | 23.71 |
March | 611.50 | 23.52 | 608.00 | 23.67 | 508.33 | 23.76 |
April | 555.33 | 23.76 | 619.17 | 23.76 | 508.17 | 23.83 |
May | 556.17 | 23.93 | 706.50 | 23.75 | 544.83 | 23.82 |
June | 538.83 | 23.97 | 704.17 | 23.77 | 535.33 | 23.83 |
July | 559.67 | 23.98 | 742.83 | 23.76 | 559.67 | 23.83 |
August | 561.17 | 23.98 | 744.00 | 23.77 | 561.17 | 23.83 |
September | 531.83 | 23.98 | 703.67 | 23.75 | 530.67 | 23.82 |
October | 586.83 | 23.70 | 637.67 | 23.73 | 526.50 | 23.80 |
November | 598.17 | 23.45 | 571.83 | 23.65 | 484.50 | 23.75 |
December | 626.83 | 23.30 | 568.83 | 23.59 | 474.67 | 23.70 |
Annual Sum or Average | 6894.00 | 23.67 | 7676.00 | 23.70 | 6105.33 | 23.78 |
Minimum of Months | 531.83 | 23.22 | 513.33 | 23.55 | 425.67 | 23.67 |
Maximum of Months | 626.83 | 23.98 | 744.00 | 23.77 | 561.17 | 23.83 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 402.33 | 21.00 | 402.33 | 21.00 |
February | 672.00 | 21.02 | 218.67 | 21.01 | 218.67 | 21.01 |
March | 744.00 | 21.11 | 36.00 | 21.11 | 36.00 | 21.10 |
April | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
May | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
June | 657.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
July | 506.67 | 22.61 | 59.17 | 22.73 | 0.00 | 22.73 |
August | 482.83 | 22.75 | 42.00 | 22.84 | 0.00 | 22.84 |
September | 714.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
October | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
November | 720.00 | 21.03 | 41.50 | 21.03 | 41.50 | 21.03 |
December | 744.00 | 21.00 | 173.83 | 21.00 | 173.83 | 21.00 |
Annual Sum or Average | 8192.50 | 21.57 | 973.50 | 21.54 | 872.33 | 21.49 |
Minimum of Months | 482.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.75 | 402.33 | 22.84 | 402.33 | 22.84 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36462 | 28.45331 | -0.3753 | 8.12209 |
February | 672.00000 | 21.17532 | 31.47012 | -0.4129 | 8.75999 |
March | 744.00000 | 21.07874 | 38.37339 | -0.4063 | 8.63408 |
April | 720.00000 | 20.98496 | 48.54938 | -0.3818 | 8.19459 |
May | 744.00000 | 21.08175 | 56.35732 | -1.4983 | 50.82152 |
June | 720.00000 | 21.35514 | 56.48115 | -1.3769 | 44.36628 |
July | 744.00000 | 21.82352 | 57.27266 | -1.1988 | 35.33695 |
August | 744.00000 | 22.38182 | 55.56354 | -1.0062 | 26.58142 |
September | 720.00000 | 22.87910 | 53.65257 | -0.8369 | 20.01057 |
October | 744.00000 | 22.98166 | 46.04325 | 0.15032 | 5.60426 |
November | 720.00000 | 22.98604 | 34.87350 | 0.07803 | 5.33748 |
December | 744.00000 | 22.38367 | 30.57935 | -0.1028 | 5.43387 |
Annual Sum or Average | 8760.00000 | 21.87681 | 44.87613 | -0.6155 | 19.01125 |
Minimum of Months | 672.00000 | 20.98496 | 28.45331 | -1.4983 | 5.33748 |
Maximum of Months | 744.00000 | 22.98604 | 57.27266 | 0.15032 | 50.82152 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05702 | 27.85541 | -0.5126 | 11.02565 |
February | 672.00000 | 21.14287 | 30.57988 | -0.4380 | 9.85942 |
March | 744.00000 | 21.27738 | 37.12881 | -0.2933 | 7.72227 |
April | 720.00000 | 21.38230 | 46.88277 | -0.1876 | 6.70503 |
May | 744.00000 | 21.50447 | 54.84964 | -1.1904 | 35.62548 |
June | 720.00000 | 22.07463 | 54.59316 | -0.9578 | 25.72789 |
July | 744.00000 | 22.41470 | 56.47677 | -0.8161 | 20.81259 |
August | 744.00000 | 22.76311 | 55.62752 | -0.6860 | 16.46211 |
September | 720.00000 | 21.99294 | 56.62875 | -0.9835 | 27.73150 |
October | 744.00000 | 21.57802 | 49.09187 | -0.1241 | 6.70906 |
November | 720.00000 | 21.27497 | 37.28082 | -0.3070 | 7.99346 |
December | 744.00000 | 21.14430 | 31.55995 | -0.4289 | 9.56451 |
Annual Sum or Average | 8760.00000 | 21.63741 | 44.95367 | -0.5779 | 15.52431 |
Minimum of Months | 672.00000 | 21.05702 | 27.85541 | -1.1904 | 6.70503 |
Maximum of Months | 744.00000 | 22.76311 | 56.62875 | -0.1241 | 35.62548 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08303 | 29.52123 | -0.4361 | 9.17085 |
February | 672.00000 | 21.18018 | 32.19792 | -0.3830 | 8.42219 |
March | 744.00000 | 21.44700 | 38.46016 | -0.2561 | 6.90618 |
April | 720.00000 | 21.69491 | 47.67848 | -0.1329 | 5.96590 |
May | 744.00000 | 21.95048 | 54.96614 | -1.1029 | 31.31950 |
June | 720.00000 | 22.48843 | 54.60652 | -0.9069 | 23.19017 |
July | 744.00000 | 22.71322 | 56.44227 | -0.8116 | 19.80494 |
August | 744.00000 | 22.90448 | 55.99766 | -0.7433 | 17.30121 |
September | 720.00000 | 22.33439 | 56.73480 | -0.9481 | 24.83066 |
October | 744.00000 | 21.71692 | 50.22849 | -0.1099 | 5.74111 |
November | 720.00000 | 21.35503 | 38.67343 | -0.2795 | 7.01866 |
December | 744.00000 | 21.15402 | 33.17737 | -0.3803 | 8.31303 |
Annual Sum or Average | 8760.00000 | 21.83910 | 45.79433 | -0.5419 | 14.03081 |
Minimum of Months | 672.00000 | 21.08303 | 29.52123 | -1.1029 | 5.74111 |
Maximum of Months | 744.00000 | 22.90448 | 56.73480 | -0.1099 | 31.31950 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.80052 | 24.32631 | 0.29368 | 10.33765 |
February | 672.00000 | 21.83334 | 26.91941 | 0.33924 | 11.07474 |
March | 744.00000 | 21.89253 | 33.33491 | 0.42974 | 12.59767 |
April | 720.00000 | 21.92768 | 42.81702 | 0.51517 | 14.17866 |
May | 744.00000 | 21.95542 | 50.44689 | -0.2227 | 13.17928 |
June | 720.00000 | 21.99990 | 51.25657 | -0.1683 | 12.84496 |
July | 744.00000 | 22.01012 | 53.50682 | -0.1412 | 12.46665 |
August | 744.00000 | 22.02467 | 53.48032 | -0.1287 | 12.55115 |
September | 720.00000 | 21.96848 | 53.08800 | -0.1926 | 12.81694 |
October | 744.00000 | 21.90143 | 45.31880 | 0.51802 | 14.10015 |
November | 720.00000 | 21.87149 | 33.40237 | 0.41307 | 12.13807 |
December | 744.00000 | 21.82419 | 27.86187 | 0.34004 | 10.97470 |
Annual Sum or Average | 8760.00000 | 21.91790 | 41.38963 | 0.16514 | 12.44350 |
Minimum of Months | 672.00000 | 21.80052 | 24.32631 | -0.2227 | 10.33765 |
Maximum of Months | 744.00000 | 22.02467 | 53.50682 | 0.51802 | 14.17866 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.22028 | 33.53239 | -0.3630 | 8.36023 |
February | 672.00000 | 21.44199 | 36.03535 | -0.2639 | 7.44408 |
March | 744.00000 | 21.84831 | 42.02312 | -0.0756 | 6.17250 |
April | 720.00000 | 21.98172 | 51.30456 | 0.02800 | 6.05162 |
May | 744.00000 | 22.18988 | 58.60716 | -0.8850 | 22.72468 |
June | 720.00000 | 22.63405 | 58.59155 | -0.6962 | 16.53904 |
July | 744.00000 | 22.84997 | 60.44549 | -0.5928 | 13.70042 |
August | 744.00000 | 23.11510 | 59.80293 | -0.4861 | 11.04632 |
September | 720.00000 | 22.63463 | 60.23098 | -0.6884 | 16.82516 |
October | 744.00000 | 22.19738 | 53.32159 | 0.10234 | 6.45716 |
November | 720.00000 | 21.76514 | 42.17867 | -0.1001 | 6.27121 |
December | 744.00000 | 21.41634 | 37.00071 | -0.2587 | 7.22408 |
Annual Sum or Average | 8760.00000 | 22.11177 | 49.49287 | -0.3573 | 10.75423 |
Minimum of Months | 672.00000 | 21.22028 | 33.53239 | -0.8850 | 6.05162 |
Maximum of Months | 744.00000 | 23.11510 | 60.44549 | 0.10234 | 22.72468 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25085 | 32.31570 | -0.3584 | 8.01031 |
February | 672.00000 | 21.41873 | 34.85772 | -0.2893 | 7.29069 |
March | 744.00000 | 21.73204 | 41.02354 | -0.1518 | 6.16397 |
April | 720.00000 | 21.93236 | 50.17919 | -0.0395 | 5.73354 |
May | 744.00000 | 22.17134 | 57.38915 | -0.9803 | 26.22600 |
June | 720.00000 | 22.62903 | 57.27078 | -0.8040 | 19.67860 |
July | 744.00000 | 22.81762 | 59.13129 | -0.7181 | 16.84411 |
August | 744.00000 | 22.98378 | 58.76444 | -0.6560 | 14.85981 |
September | 720.00000 | 22.54948 | 59.12920 | -0.8213 | 20.19076 |
October | 744.00000 | 22.02946 | 52.47806 | 0.00383 | 5.57680 |
November | 720.00000 | 21.68905 | 41.10013 | -0.1624 | 6.09801 |
December | 744.00000 | 21.40120 | 35.82981 | -0.2829 | 7.11367 |
Annual Sum or Average | 8760.00000 | 22.05397 | 48.35969 | -0.4394 | 12.01041 |
Minimum of Months | 672.00000 | 21.25085 | 32.31570 | -0.9803 | 5.57680 |
Maximum of Months | 744.00000 | 22.98378 | 59.13129 | 0.00383 | 26.22600 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85424 | 38.00657 | -0.5810 | 12.70575 |
February | 672.00000 | 21.03461 | 40.10862 | -0.4851 | 10.96210 |
March | 744.00000 | 21.43000 | 43.59282 | -0.2871 | 7.61748 |
April | 720.00000 | 21.57775 | 51.18985 | -0.1642 | 6.51057 |
May | 744.00000 | 21.67316 | 55.51652 | -1.1853 | 35.78923 |
June | 720.00000 | 21.72525 | 53.71837 | -1.1165 | 32.70703 |
July | 744.00000 | 21.72878 | 56.00674 | -1.0832 | 31.21631 |
August | 744.00000 | 21.73821 | 55.25826 | -1.0719 | 30.74256 |
September | 720.00000 | 21.67868 | 57.30668 | -1.1555 | 34.46781 |
October | 744.00000 | 21.49086 | 55.30432 | -0.1853 | 6.60852 |
November | 720.00000 | 21.34581 | 45.98030 | -0.3306 | 8.16624 |
December | 744.00000 | 21.04539 | 42.03946 | -0.4822 | 10.50477 |
Annual Sum or Average | 8760.00000 | 21.44541 | 49.55168 | -0.6787 | 19.04989 |
Minimum of Months | 672.00000 | 20.85424 | 38.00657 | -1.1853 | 6.51057 |
Maximum of Months | 744.00000 | 21.73821 | 57.30668 | -0.1642 | 35.78923 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63353 | 38.47736 | -0.6585 | 14.79698 |
February | 672.00000 | 20.91530 | 40.39447 | -0.5407 | 12.31846 |
March | 744.00000 | 21.47286 | 44.02916 | -0.3032 | 7.99860 |
April | 720.00000 | 21.89648 | 51.28407 | -0.1108 | 6.63507 |
May | 744.00000 | 22.13124 | 55.96164 | -1.0546 | 30.40888 |
June | 720.00000 | 22.07954 | 54.20709 | -1.0103 | 28.57379 |
July | 744.00000 | 22.06919 | 56.97299 | -0.9793 | 27.24097 |
August | 744.00000 | 21.99314 | 56.47314 | -1.0026 | 28.07159 |
September | 720.00000 | 22.04489 | 58.77858 | -1.0610 | 30.53562 |
October | 744.00000 | 21.63009 | 56.39112 | -0.1798 | 6.84989 |
November | 720.00000 | 21.19285 | 46.84300 | -0.3956 | 9.14122 |
December | 744.00000 | 20.78671 | 42.73826 | -0.5685 | 12.41617 |
Annual Sum or Average | 8760.00000 | 21.57332 | 50.26515 | -0.6565 | 17.95278 |
Minimum of Months | 672.00000 | 20.63353 | 38.47736 | -1.0610 | 6.63507 |
Maximum of Months | 744.00000 | 22.13124 | 58.77858 | -0.1108 | 30.53562 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89969 | 36.91973 | -0.5446 | 11.67306 |
February | 672.00000 | 21.10060 | 38.38713 | -0.4648 | 10.14839 |
March | 744.00000 | 21.43855 | 42.11966 | -0.3188 | 7.64821 |
April | 720.00000 | 21.80703 | 49.06679 | -0.1665 | 6.41619 |
May | 744.00000 | 22.03766 | 54.84018 | -1.1479 | 33.89817 |
June | 720.00000 | 22.00567 | 54.76476 | -1.1261 | 33.09685 |
July | 744.00000 | 22.01819 | 57.62470 | -1.0962 | 31.86809 |
August | 744.00000 | 21.93299 | 57.42636 | -1.1293 | 33.20181 |
September | 720.00000 | 22.00319 | 57.36095 | -1.1441 | 33.76943 |
October | 744.00000 | 21.61763 | 53.59125 | -0.1982 | 6.40616 |
November | 720.00000 | 21.30779 | 44.25652 | -0.3554 | 8.13379 |
December | 744.00000 | 21.05190 | 40.81076 | -0.4676 | 9.94962 |
Annual Sum or Average | 8760.00000 | 21.60390 | 48.99074 | -0.6815 | 18.90587 |
Minimum of Months | 672.00000 | 20.89969 | 36.91973 | -1.1479 | 6.40616 |
Maximum of Months | 744.00000 | 22.03766 | 57.62470 | -0.1665 | 33.89817 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88267 | 37.93318 | -0.5752 | 12.55005 |
February | 672.00000 | 21.08464 | 40.00017 | -0.4706 | 10.70532 |
March | 744.00000 | 21.49767 | 43.37293 | -0.2766 | 7.53080 |
April | 720.00000 | 21.64595 | 50.58754 | -0.1520 | 6.46540 |
May | 744.00000 | 21.71080 | 54.37411 | -1.1720 | 35.24645 |
June | 720.00000 | 21.74614 | 53.01171 | -1.1056 | 32.30100 |
July | 744.00000 | 21.74079 | 55.34393 | -1.0732 | 30.86847 |
August | 744.00000 | 21.74722 | 54.86752 | -1.0677 | 30.63594 |
September | 720.00000 | 21.69475 | 56.57661 | -1.1514 | 34.33043 |
October | 744.00000 | 21.53425 | 54.52351 | -0.1796 | 6.59705 |
November | 720.00000 | 21.38618 | 45.83027 | -0.3231 | 8.02711 |
December | 744.00000 | 21.07369 | 41.92982 | -0.4750 | 10.30806 |
Annual Sum or Average | 8760.00000 | 21.48044 | 49.07639 | -0.6700 | 18.84742 |
Minimum of Months | 672.00000 | 20.88267 | 37.93318 | -1.1720 | 6.46540 |
Maximum of Months | 744.00000 | 21.74722 | 56.57661 | -0.1520 | 35.24645 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64770 | 38.42666 | -0.6557 | 14.70889 |
February | 672.00000 | 20.93848 | 40.31879 | -0.5313 | 12.04142 |
March | 744.00000 | 21.46296 | 43.96324 | -0.3085 | 7.85808 |
April | 720.00000 | 21.92121 | 50.82517 | -0.1075 | 6.44197 |
May | 744.00000 | 22.18217 | 54.95479 | -1.0371 | 29.83531 |
June | 720.00000 | 22.17118 | 53.54632 | -0.9785 | 27.96769 |
July | 744.00000 | 22.15865 | 56.27744 | -0.9464 | 26.81776 |
August | 744.00000 | 22.04440 | 56.00753 | -0.9864 | 27.91818 |
September | 720.00000 | 22.09778 | 57.89608 | -1.0467 | 30.21452 |
October | 744.00000 | 21.63347 | 55.80001 | -0.1819 | 6.71540 |
November | 720.00000 | 21.15799 | 46.84669 | -0.4033 | 9.08459 |
December | 744.00000 | 20.79416 | 42.67656 | -0.5654 | 12.28119 |
Annual Sum or Average | 8760.00000 | 21.60370 | 49.84561 | -0.6468 | 17.69480 |
Minimum of Months | 672.00000 | 20.64770 | 38.42666 | -1.0467 | 6.44197 |
Maximum of Months | 744.00000 | 22.18217 | 57.89608 | -0.1075 | 30.21452 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.73916 | 38.76080 | -0.6444 | 14.44748 |
February | 672.00000 | 20.94633 | 40.91659 | -0.5324 | 12.22710 |
March | 744.00000 | 21.38574 | 44.20617 | -0.3069 | 8.09313 |
April | 720.00000 | 21.56496 | 51.85834 | -0.1643 | 6.73104 |
May | 744.00000 | 21.67334 | 55.93097 | -1.1696 | 35.28600 |
June | 720.00000 | 21.72596 | 53.89300 | -1.0983 | 32.11473 |
July | 744.00000 | 21.72952 | 56.36213 | -1.0630 | 30.54574 |
August | 744.00000 | 21.73933 | 55.48123 | -1.0522 | 30.09317 |
September | 720.00000 | 21.67195 | 58.04643 | -1.1480 | 34.30763 |
October | 744.00000 | 21.45228 | 56.29967 | -0.1982 | 6.92463 |
November | 720.00000 | 21.28562 | 46.84720 | -0.3620 | 8.84384 |
December | 744.00000 | 20.93327 | 42.98357 | -0.5372 | 11.83710 |
Annual Sum or Average | 8760.00000 | 21.40598 | 50.18020 | -0.6910 | 19.33239 |
Minimum of Months | 672.00000 | 20.73916 | 38.76080 | -1.1696 | 6.73104 |
Maximum of Months | 744.00000 | 21.73933 | 58.04643 | -0.1643 | 35.28600 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56273 | 39.21187 | -0.7144 | 16.48952 |
February | 672.00000 | 20.85506 | 41.17593 | -0.5839 | 13.56889 |
March | 744.00000 | 21.43847 | 44.59503 | -0.3214 | 8.55074 |
April | 720.00000 | 21.93302 | 51.70789 | -0.0989 | 7.01187 |
May | 744.00000 | 22.16646 | 55.99447 | -1.0252 | 29.69595 |
June | 720.00000 | 22.07646 | 54.27025 | -0.9906 | 28.02137 |
July | 744.00000 | 22.06070 | 57.22046 | -0.9593 | 26.62961 |
August | 744.00000 | 21.98496 | 56.63183 | -0.9841 | 27.47260 |
September | 720.00000 | 22.03893 | 59.29203 | -1.0511 | 30.39741 |
October | 744.00000 | 21.61152 | 57.30277 | -0.1887 | 7.29006 |
November | 720.00000 | 21.11958 | 47.73660 | -0.4319 | 9.99962 |
December | 744.00000 | 20.68129 | 43.69656 | -0.6240 | 13.95096 |
Annual Sum or Average | 8760.00000 | 21.54705 | 50.78732 | -0.6654 | 18.28849 |
Minimum of Months | 672.00000 | 20.56273 | 39.21187 | -1.0511 | 7.01187 |
Maximum of Months | 744.00000 | 22.16646 | 59.29203 | -0.0989 | 30.39741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20882 | 39.01441 | -0.4577 | 10.60010 |
February | 672.00000 | 21.30293 | 40.81089 | -0.3902 | 9.41052 |
March | 744.00000 | 21.53769 | 43.52641 | -0.2521 | 7.41863 |
April | 720.00000 | 21.61498 | 51.06671 | -0.1682 | 6.64639 |
May | 744.00000 | 21.67349 | 55.74746 | -1.2145 | 37.24849 |
June | 720.00000 | 21.72136 | 54.58351 | -1.1585 | 34.65499 |
July | 744.00000 | 21.72576 | 56.82000 | -1.1230 | 33.00522 |
August | 744.00000 | 21.73938 | 55.60117 | -1.1030 | 32.18547 |
September | 720.00000 | 21.68757 | 56.59902 | -1.1669 | 35.13634 |
October | 744.00000 | 21.57797 | 53.93523 | -0.1529 | 6.56000 |
November | 720.00000 | 21.54018 | 45.57106 | -0.2492 | 7.45343 |
December | 744.00000 | 21.35206 | 42.39983 | -0.3670 | 8.90510 |
Annual Sum or Average | 8760.00000 | 21.55801 | 49.68683 | -0.6520 | 19.16121 |
Minimum of Months | 672.00000 | 21.20882 | 39.01441 | -1.2145 | 6.56000 |
Maximum of Months | 744.00000 | 21.73938 | 56.82000 | -0.1529 | 37.24849 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.06280 | 33.65550 | -0.1334 | 6.51566 |
February | 672.00000 | 22.34415 | 35.82784 | -0.0297 | 6.49604 |
March | 744.00000 | 22.80728 | 41.43370 | 0.15471 | 6.67741 |
April | 720.00000 | 23.14376 | 49.54065 | 0.31328 | 7.99340 |
May | 744.00000 | 23.42043 | 55.79165 | -0.4563 | 10.28190 |
June | 720.00000 | 23.63777 | 55.70740 | -0.3418 | 7.99432 |
July | 744.00000 | 23.69279 | 57.52519 | -0.2971 | 7.27896 |
August | 744.00000 | 23.69253 | 57.52167 | -0.2958 | 7.23682 |
September | 720.00000 | 23.43265 | 58.19751 | -0.4326 | 9.78263 |
October | 744.00000 | 22.93474 | 52.37520 | 0.26725 | 7.42327 |
November | 720.00000 | 22.59126 | 41.76043 | 0.08869 | 6.36032 |
December | 744.00000 | 22.26823 | 36.89361 | -0.0448 | 6.24253 |
Annual Sum or Average | 8760.00000 | 23.00559 | 48.08343 | -0.1013 | 7.52647 |
Minimum of Months | 672.00000 | 22.06280 | 33.65550 | -0.4563 | 6.24253 |
Maximum of Months | 744.00000 | 23.69279 | 58.19751 | 0.31328 | 10.28190 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.24564 | 32.98025 | -0.0565 | 6.30216 |
February | 672.00000 | 22.55510 | 35.04765 | 0.05396 | 6.60654 |
March | 744.00000 | 23.05086 | 40.47426 | 0.24605 | 7.30655 |
April | 720.00000 | 23.34785 | 48.50055 | 0.39497 | 9.04482 |
May | 744.00000 | 23.57273 | 54.75268 | -0.3582 | 8.36023 |
June | 720.00000 | 23.72843 | 54.87570 | -0.2692 | 6.90757 |
July | 744.00000 | 23.76817 | 56.75244 | -0.2320 | 6.42973 |
August | 744.00000 | 23.76097 | 56.77257 | -0.2339 | 6.43750 |
September | 720.00000 | 23.56906 | 57.19663 | -0.3421 | 8.08180 |
October | 744.00000 | 23.16410 | 51.27224 | 0.35463 | 8.42303 |
November | 720.00000 | 22.84178 | 40.82327 | 0.18141 | 6.82549 |
December | 744.00000 | 22.49256 | 36.10354 | 0.04157 | 6.26628 |
Annual Sum or Average | 8760.00000 | 23.17771 | 47.19333 | -0.0190 | 7.24949 |
Minimum of Months | 672.00000 | 22.24564 | 32.98025 | -0.3582 | 6.26628 |
Maximum of Months | 744.00000 | 23.76817 | 57.19663 | 0.39497 | 9.04482 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.24247 | 32.05551 | 0.78787 | 23.27551 |
February | 672.00000 | 23.28767 | 34.02371 | 0.84788 | 25.27260 |
March | 744.00000 | 23.37404 | 39.11162 | 0.96256 | 29.15915 |
April | 720.00000 | 23.43475 | 47.25017 | 1.06796 | 33.17661 |
May | 744.00000 | 23.50041 | 53.66486 | 0.56693 | 19.98961 |
June | 720.00000 | 23.57039 | 54.12943 | 0.64137 | 21.05387 |
July | 744.00000 | 23.59339 | 56.04387 | 0.67750 | 21.64746 |
August | 744.00000 | 23.60991 | 55.98506 | 0.68335 | 21.52614 |
September | 720.00000 | 23.53100 | 55.96241 | 0.59206 | 19.82731 |
October | 744.00000 | 23.41101 | 49.60440 | 1.05549 | 32.46615 |
November | 720.00000 | 23.33089 | 39.41241 | 0.92722 | 27.88598 |
December | 744.00000 | 23.27891 | 34.88662 | 0.84386 | 25.04433 |
Annual Sum or Average | 8760.00000 | 23.43118 | 46.07454 | 0.80412 | 25.02001 |
Minimum of Months | 672.00000 | 23.24247 | 32.05551 | 0.56693 | 19.82731 |
Maximum of Months | 744.00000 | 23.60991 | 56.04387 | 1.06796 | 33.17661 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99864 | 26.41948 | -0.5410 | 11.27578 |
February | 672.00000 | 20.99907 | 29.34907 | -0.5051 | 10.55641 |
March | 744.00000 | 21.02884 | 36.23151 | -0.4253 | 9.01538 |
April | 720.00000 | 21.12257 | 46.11288 | -0.3298 | 7.53005 |
May | 744.00000 | 21.42270 | 53.86291 | -1.3486 | 42.94602 |
June | 720.00000 | 22.20760 | 53.11520 | -1.0750 | 29.72526 |
July | 744.00000 | 22.54190 | 55.17726 | -0.9442 | 24.19182 |
August | 744.00000 | 22.66386 | 55.12171 | -0.9012 | 22.29853 |
September | 720.00000 | 21.89431 | 55.82514 | -1.1667 | 33.91832 |
October | 744.00000 | 21.13282 | 49.02431 | -0.3080 | 7.16119 |
November | 720.00000 | 21.00961 | 36.35122 | -0.4315 | 9.07910 |
December | 744.00000 | 21.00161 | 30.33625 | -0.4940 | 10.27878 |
Annual Sum or Average | 8760.00000 | 21.50547 | 43.98708 | -0.7070 | 18.20645 |
Minimum of Months | 672.00000 | 20.99864 | 26.41948 | -1.3486 | 7.16119 |
Maximum of Months | 744.00000 | 22.66386 | 55.82514 | -0.3080 | 42.94602 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00092 | 29.83821 | -0.5047 | 10.43893 |
February | 672.00000 | 21.02381 | 32.66648 | -0.4712 | 9.81156 |
March | 744.00000 | 21.11777 | 39.29140 | -0.3888 | 8.41294 |
April | 720.00000 | 21.38539 | 48.55059 | -0.2627 | 6.81049 |
May | 744.00000 | 21.72124 | 55.83837 | -1.2635 | 38.56812 |
June | 720.00000 | 22.33592 | 55.31194 | -1.0501 | 28.48713 |
July | 744.00000 | 22.58673 | 57.13621 | -0.9500 | 24.26352 |
August | 744.00000 | 22.64056 | 57.13195 | -0.9312 | 23.40784 |
September | 720.00000 | 22.06120 | 57.83003 | -1.1300 | 32.10708 |
October | 744.00000 | 21.28732 | 51.60390 | -0.2711 | 6.71716 |
November | 720.00000 | 21.03425 | 39.50189 | -0.4139 | 8.74259 |
December | 744.00000 | 21.00571 | 33.64748 | -0.4700 | 9.76214 |
Annual Sum or Average | 8760.00000 | 21.60366 | 46.60166 | -0.6769 | 17.33653 |
Minimum of Months | 672.00000 | 21.00092 | 29.83821 | -1.2635 | 6.71716 |
Maximum of Months | 744.00000 | 22.64056 | 57.83003 | -0.2627 | 38.56812 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99933 | 27.63531 | -0.5215 | 10.85169 |
February | 672.00000 | 21.02264 | 30.44579 | -0.4744 | 9.96911 |
March | 744.00000 | 21.11348 | 37.05883 | -0.3713 | 8.23230 |
April | 720.00000 | 21.41013 | 46.26947 | -0.2275 | 6.65197 |
May | 744.00000 | 21.84743 | 53.11934 | -1.1603 | 33.88976 |
June | 720.00000 | 22.60555 | 52.06210 | -0.8924 | 22.49938 |
July | 744.00000 | 22.90573 | 53.70967 | -0.7734 | 18.41586 |
August | 744.00000 | 23.00255 | 53.53540 | -0.7399 | 16.97126 |
September | 720.00000 | 22.04406 | 55.50502 | -1.0743 | 29.95936 |
October | 744.00000 | 21.25842 | 49.37398 | -0.2540 | 6.64972 |
November | 720.00000 | 21.03046 | 37.29923 | -0.4047 | 8.64811 |
December | 744.00000 | 21.00288 | 31.43402 | -0.4755 | 9.91303 |
Annual Sum or Average | 8760.00000 | 21.69141 | 44.02307 | -0.6149 | 15.24529 |
Minimum of Months | 672.00000 | 20.99933 | 27.63531 | -1.1603 | 6.64972 |
Maximum of Months | 744.00000 | 23.00255 | 55.50502 | -0.2275 | 33.88976 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00264 | 26.08437 | -0.5321 | 11.07451 |
February | 672.00000 | 21.01302 | 29.00169 | -0.4955 | 10.35870 |
March | 744.00000 | 21.07285 | 35.79973 | -0.4119 | 8.81598 |
April | 720.00000 | 21.22579 | 45.49565 | -0.3051 | 7.26677 |
May | 744.00000 | 21.58622 | 53.04111 | -1.2968 | 40.34917 |
June | 720.00000 | 22.40243 | 52.21543 | -1.0138 | 27.13849 |
July | 744.00000 | 22.74224 | 54.24512 | -0.8811 | 21.82567 |
August | 744.00000 | 22.86206 | 54.20060 | -0.8388 | 20.06677 |
September | 720.00000 | 22.09562 | 54.87264 | -1.1034 | 31.02103 |
October | 744.00000 | 21.23264 | 48.42993 | -0.2835 | 6.90944 |
November | 720.00000 | 21.04468 | 35.94673 | -0.4191 | 8.88083 |
December | 744.00000 | 21.00761 | 29.99519 | -0.4858 | 10.11751 |
Annual Sum or Average | 8760.00000 | 21.61127 | 43.35243 | -0.6733 | 17.02243 |
Minimum of Months | 672.00000 | 21.00264 | 26.08437 | -1.2968 | 6.90944 |
Maximum of Months | 744.00000 | 22.86206 | 54.87264 | -0.2835 | 40.34917 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.858326E+10 | 80683.84 | 19-JAN-22:53 | 210.99 | 0.253276E+11 | 0.00 | 0.339109E+11 | 0.87 | 3.52 | 19-JAN-22:53 | 0.00 | 0.00 |
February | 0.265205E+11 | 102619.74 | 26-FEB-16:01 | 334.44 | 0.763606E+11 | 0.00 | 0.102881E+12 | 1.49 | 3.53 | 25-FEB-16:01 | 0.00 | 0.00 |
March | 0.662554E+11 | 120470.60 | 30-MAR-18:03 | 629.33 | 0.192986E+12 | 0.00 | 0.259242E+12 | 2.53 | 3.70 | 31-MAR-08:53 | 0.00 | 0.00 |
April | 0.118737E+12 | 125932.94 | 04-APR-15:03 | 691.53 | 0.353089E+12 | 0.00 | 0.471826E+12 | 2.87 | 3.92 | 22-APR-21:53 | 0.00 | 0.00 |
May | 0.201245E+12 | 156977.76 | 30-MAY-18:03 | 742.92 | 0.635885E+12 | 0.00 | 0.837130E+12 | 3.12 | 4.11 | 26-MAY-21:53 | 0.00 | 0.00 |
June | 0.272746E+12 | 180980.31 | 28-JUN-18:03 | 720.00 | 0.893730E+12 | 0.00 | 0.116648E+13 | 3.25 | 4.18 | 22-JUN-21:52 | 0.00 | 0.00 |
July | 0.332057E+12 | 202366.72 | 08-JUL-15:03 | 744.00 | 0.111998E+13 | 0.00 | 0.145204E+13 | 3.40 | 4.20 | 28-JUL-15:03 | 0.00 | 0.00 |
August | 0.342745E+12 | 198609.64 | 18-AUG-18:03 | 744.00 | 0.116067E+13 | 0.00 | 0.150341E+13 | 3.40 | 4.13 | 07-AUG-21:54 | 0.00 | 0.00 |
September | 0.240899E+12 | 175076.91 | 07-SEP-15:03 | 720.00 | 0.805440E+12 | 0.00 | 0.104634E+13 | 3.28 | 4.09 | 27-SEP-21:53 | 0.00 | 0.00 |
October | 0.113694E+12 | 162553.30 | 18-OCT-21:53 | 697.15 | 0.364941E+12 | 0.00 | 0.478635E+12 | 2.92 | 4.13 | 19-OCT-08:52 | 0.00 | 0.00 |
November | 0.542093E+11 | 118888.07 | 05-NOV-15:03 | 542.27 | 0.161980E+12 | 0.00 | 0.216189E+12 | 2.28 | 3.95 | 04-NOV-15:02 | 0.00 | 0.00 |
December | 0.172118E+11 | 95770.81 | 12-DEC-16:01 | 342.95 | 0.510746E+11 | 0.00 | 0.682864E+11 | 1.41 | 3.93 | 13-DEC-16:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.179490E+13 | 7119.58 | 0.584146E+13 | 0.00 | 0.763637E+13 | 2.57 | 0.00 | 0.00 | ||||
Minimum of Months | 0.858326E+10 | 80683.84 | 210.99 | 0.253276E+11 | 0.00 | 0.339109E+11 | 0.87 | 3.52 | 0.00 | 0.00 | ||
Maximum of Months | 0.342745E+12 | 202366.72 | 744.00 | 0.116067E+13 | 0.00 | 0.150341E+13 | 3.40 | 4.20 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.201819E+12 | 0.00 | 744.00 | 235587.36 | 17-JAN-09:02 | 0.00 | 35.70 | 60.00 | 0.76 | 0.00 | 0.18 | 0.55 | 17-JAN-09:02 |
February | 0.133141E+12 | 0.00 | 660.85 | 228868.53 | 07-FEB-09:02 | 0.00 | 34.10 | 59.47 | 0.54 | 0.00 | 0.13 | 0.53 | 07-FEB-09:02 |
March | 0.785946E+11 | 0.00 | 686.43 | 204072.23 | 18-MAR-08:03 | 0.00 | 32.90 | 57.98 | 0.26 | 0.00 | 0.07 | 0.48 | 18-MAR-08:03 |
April | 0.368433E+11 | 0.00 | 634.75 | 185161.07 | 06-APR-08:03 | 0.00 | 35.11 | 57.27 | 0.13 | 0.00 | 0.03 | 0.43 | 06-APR-08:03 |
May | 0.121088E+11 | 0.00 | 567.41 | 60672.31 | 11-MAY-06:00 | 0.00 | 33.48 | 54.01 | 0.04 | 0.00 | 0.01 | 0.14 | 11-MAY-06:00 |
June | 0.334127E+10 | 0.00 | 400.23 | 39486.55 | 10-JUN-08:55 | 0.00 | 29.27 | 46.21 | 0.01 | 0.00 | 0.00 | 0.09 | 10-JUN-08:55 |
July | 0.249697E+10 | 0.00 | 351.74 | 43852.65 | 28-JUL-15:06 | 0.00 | 30.17 | 44.30 | 0.01 | 0.00 | 0.00 | 0.10 | 28-JUL-15:06 |
August | 0.237975E+10 | 0.00 | 329.47 | 31481.73 | 30-AUG-21:56 | 0.00 | 30.82 | 43.79 | 0.01 | 0.00 | 0.00 | 0.07 | 30-AUG-21:56 |
September | 0.368770E+10 | 0.00 | 449.10 | 56184.30 | 30-SEP-15:05 | 0.00 | 30.70 | 48.80 | 0.01 | 0.00 | 0.00 | 0.13 | 30-SEP-15:05 |
October | 0.386809E+11 | 0.00 | 609.51 | 162440.33 | 26-OCT-06:50 | 0.00 | 30.05 | 54.19 | 0.12 | 0.00 | 0.03 | 0.38 | 26-OCT-06:50 |
November | 0.980841E+11 | 0.00 | 694.41 | 188228.68 | 20-NOV-19:03 | 0.00 | 31.87 | 58.81 | 0.35 | 0.00 | 0.09 | 0.44 | 20-NOV-19:03 |
December | 0.180700E+12 | 0.00 | 739.33 | 230408.51 | 21-DEC-09:02 | 0.00 | 33.85 | 59.80 | 0.65 | 0.00 | 0.16 | 0.54 | 21-DEC-09:02 |
Annual Sum or Average | 0.791877E+12 | 0.00 | 6867.24 | 0.00 | 32.33 | 53.68 | 0.24 | 0.00 | 0.06 | ||||
Minimum of Months | 0.237975E+10 | 0.00 | 329.47 | 31481.73 | 0.00 | 29.27 | 43.79 | 0.01 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.201819E+12 | 0.00 | 744.00 | 235587.36 | 0.00 | 35.70 | 60.00 | 0.76 | 0.00 | 0.18 | 0.55 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.196983E+11 | 0.00 | 85.17 | 0.145651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194257.23 | 19-JAN-22:00 | 128136.75 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.584548E+11 | 0.00 | 240.17 | 0.503816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178345.62 | 26-FEB-15:20 | 178345.62 | 26-FEB-15:20 | 0.00 | 0.00 | 0.00 |
March | 0.139842E+12 | 0.00 | 436.50 | 0.123506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246105.72 | 31-MAR-10:50 | 211906.25 | 30-MAR-19:40 | 0.00 | 0.00 | 0.00 |
April | 0.264659E+12 | 0.00 | 600.50 | 0.210488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296626.72 | 21-APR-18:06 | 248315.04 | 15-APR-13:45 | 0.00 | 0.00 | 0.00 |
May | 0.490993E+12 | 0.00 | 720.83 | 0.322533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 418866.42 | 30-MAY-21:20 | 262256.33 | 16-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.689340E+12 | 0.00 | 714.67 | 0.420772E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 464887.70 | 26-JUN-21:00 | 262801.26 | 10-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.878222E+12 | 0.00 | 744.00 | 0.470266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 486211.25 | 18-JUL-19:04 | 258317.15 | 07-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.906158E+12 | 0.00 | 744.00 | 0.489905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 485166.89 | 23-AUG-23:00 | 257584.98 | 18-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.633398E+12 | 0.00 | 718.50 | 0.367662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478038.58 | 27-SEP-18:15 | 229689.67 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.277117E+12 | 0.00 | 539.83 | 0.177396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 503578.87 | 18-OCT-21:00 | 203505.51 | 11-OCT-16:10 | 0.00 | 0.00 | 0.00 |
November | 0.121628E+12 | 0.00 | 367.33 | 0.896940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 269527.92 | 27-NOV-19:03 | 160200.47 | 05-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.359586E+11 | 0.00 | 165.53 | 0.265349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 221480.03 | 13-DEC-11:40 | 153279.44 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451547E+13 | 0.00 | 6077.03 | 0.276370E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.196983E+11 | 0.00 | 85.17 | 0.145651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178345.62 | 128136.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.906158E+12 | 0.00 | 744.00 | 0.489905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 503578.87 | 262801.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.698511E+09 | 0.00 | 30.83 | 0.529225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13371.86 | 19-JAN-16:05 | 12205.06 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.197485E+10 | 0.00 | 88.33 | 0.195141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16160.71 | 28-FEB-16:01 | 16160.71 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.711480E+10 | 0.00 | 245.17 | 0.650605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22806.81 | 28-MAR-15:01 | 18079.89 | 30-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.142939E+11 | 0.00 | 373.17 | 0.114853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29104.22 | 30-APR-15:01 | 18440.51 | 17-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.301457E+11 | 0.00 | 535.17 | 0.200527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39091.41 | 30-MAY-21:50 | 19090.73 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.447861E+11 | 0.00 | 553.17 | 0.279633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.50 | 29-JUN-08:03 | 20561.18 | 06-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.562039E+11 | 0.00 | 589.00 | 0.315020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 26-JUL-08:03 | 21492.41 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.576988E+11 | 0.00 | 589.00 | 0.326640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47944.72 | 24-AUG-08:61 | 20879.89 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.401268E+11 | 0.00 | 550.67 | 0.243980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45948.22 | 17-SEP-08:03 | 19663.99 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.162046E+11 | 0.00 | 307.17 | 0.100482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44490.71 | 18-OCT-21:50 | 18633.77 | 10-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.573209E+10 | 0.00 | 170.67 | 0.416627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191.70 | 19-NOV-24:00 | 16648.11 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.118515E+10 | 0.00 | 51.50 | 0.940863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19688.72 | 13-DEC-11:00 | 14720.89 | 12-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276165E+12 | 0.00 | 4083.83 | 0.172207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.698511E+09 | 0.00 | 30.83 | 0.529225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13371.86 | 12205.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.576988E+11 | 0.00 | 589.00 | 0.326640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 21492.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 97240493.00 | 0.00 | 29.72 | 88506454.34 | 0.00 | 0.00 | 0.00 | 0.00 | 14983.34 | 29-JAN-16:01 | 14983.34 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.532111E+09 | 0.00 | 102.72 | 0.468603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14998.65 | 28-FEB-19:01 | 14998.65 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.209382E+10 | 0.00 | 319.59 | 0.133500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15584.02 | 28-MAR-15:01 | 14996.33 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.392967E+10 | 0.00 | 506.56 | 0.207790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16317.97 | 02-APR-15:01 | 14995.33 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.631703E+10 | 0.00 | 656.26 | 0.306177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16398.50 | 27-MAY-08:62 | 15000.72 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.904358E+10 | 0.00 | 677.59 | 0.481826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17174.84 | 29-JUN-08:61 | 13470.56 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.105924E+11 | 0.00 | 701.63 | 0.580553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17907.98 | 30-JUL-08:62 | 13496.91 | 30-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.112332E+11 | 0.00 | 711.03 | 0.617435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17143.62 | 29-AUG-08:61 | 13508.54 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.708268E+10 | 0.00 | 637.55 | 0.337946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17400.66 | 17-SEP-08:61 | 13394.26 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.316909E+10 | 0.00 | 426.72 | 0.148631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17272.84 | 01-OCT-15:01 | 14534.80 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.989275E+09 | 0.00 | 216.31 | 0.568401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16527.70 | 04-NOV-15:02 | 14998.06 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.249328E+09 | 0.00 | 65.69 | 0.158394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15672.08 | 13-DEC-16:02 | 14993.75 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553295E+11 | 0.00 | 5051.37 | 0.294225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 97240493.00 | 0.00 | 29.72 | 88506454.34 | 0.00 | 0.00 | 0.00 | 0.00 | 14983.34 | 13394.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112332E+11 | 0.00 | 711.03 | 0.617435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17907.98 | 15000.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6891917.63 | 0.00 | 2.32 | 5036486.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13381.68 | 20-JAN-16:01 | 12071.40 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 91360534.56 | 0.00 | 30.35 | 68856998.16 | 0.00 | 0.00 | 0.00 | 0.00 | 14838.83 | 21-FEB-16:01 | 14838.83 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.874211E+09 | 0.00 | 164.40 | 0.463351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15560.58 | 28-MAR-15:01 | 14836.32 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.244780E+10 | 0.00 | 360.63 | 0.119128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16417.74 | 02-APR-15:01 | 15320.66 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.493337E+10 | 0.00 | 487.72 | 0.243348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16963.91 | 07-MAY-17:42 | 15334.90 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.820336E+10 | 0.00 | 562.32 | 0.463022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18313.78 | 26-JUN-08:21 | 13351.19 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.961217E+10 | 0.00 | 587.41 | 0.556252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18322.32 | 23-JUL-08:51 | 13563.24 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.100132E+11 | 0.00 | 619.05 | 0.560653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19374.22 | 20-AUG-07:52 | 14415.46 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.531491E+10 | 0.00 | 479.61 | 0.251318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17536.33 | 17-SEP-08:52 | 14250.76 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.138609E+10 | 0.00 | 231.26 | 0.552718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17335.65 | 18-OCT-21:52 | 13973.12 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.178098E+09 | 0.00 | 63.26 | 92005636.34 | 0.00 | 0.00 | 0.00 | 0.00 | 16322.60 | 04-NOV-15:02 | 14839.07 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 25899086.46 | 0.00 | 10.22 | 16998369.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14682.81 | 12-DEC-16:01 | 14366.15 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430873E+11 | 0.00 | 3598.56 | 0.231362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6891917.63 | 0.00 | 2.32 | 5036486.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13381.68 | 12071.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100132E+11 | 0.00 | 619.05 | 0.560653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19374.22 | 15334.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.521047E+09 | 0.00 | 29.86 | 0.371114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13097.84 | 29-JAN-13:30 | 13097.84 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.486895E+10 | 0.00 | 114.67 | 0.473022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29924.46 | 26-FEB-14:50 | 29924.46 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.154053E+11 | 0.00 | 406.92 | 0.995497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32273.41 | 30-MAR-13:30 | 28247.39 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.200111E+11 | 0.00 | 530.04 | 0.852873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27471.07 | 15-APR-13:30 | 21443.78 | 10-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 0.285591E+11 | 0.00 | 673.80 | 0.979836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25466.21 | 30-MAY-17:20 | 16569.63 | 10-MAY-15:06 | 0.00 | 0.00 | 0.00 |
June | 0.397398E+11 | 0.00 | 703.38 | 0.150918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29934.09 | 25-JUN-17:20 | 16785.18 | 24-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.480087E+11 | 0.00 | 739.25 | 0.192138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33588.12 | 08-JUL-17:30 | 21057.49 | 08-JUL-17:30 | 0.00 | 0.00 | 0.00 |
August | 0.555631E+11 | 0.00 | 742.97 | 0.242848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36675.06 | 19-AUG-15:02 | 24466.07 | 19-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.403407E+11 | 0.00 | 683.03 | 0.170465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40014.46 | 24-SEP-12:30 | 31570.78 | 24-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.267073E+11 | 0.00 | 520.11 | 0.127605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43260.16 | 10-OCT-13:30 | 36258.61 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.143118E+11 | 0.00 | 369.42 | 0.107125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34278.90 | 06-NOV-13:40 | 33662.03 | 08-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 0.544698E+10 | 0.00 | 160.07 | 0.397432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33270.36 | 12-DEC-12:30 | 31496.39 | 10-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299484E+12 | 0.00 | 5673.52 | 0.136467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.521047E+09 | 0.00 | 29.86 | 0.371114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13097.84 | 13097.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.555631E+11 | 0.00 | 742.97 | 0.242848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43260.16 | 36258.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.951331E+09 | 0.00 | 48.22 | 0.357034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88642.13 | 19-JAN-22:53 | 79232.66 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.413075E+10 | 0.00 | 144.60 | 0.247764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96257.35 | 18-FEB-09:02 | 94381.57 | 28-FEB-22:52 | 0.00 | 0.00 | 0.00 |
March | 0.131783E+11 | 0.00 | 316.69 | 0.787918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95635.22 | 28-MAR-21:52 | 94687.59 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.263272E+11 | 0.00 | 383.18 | 0.145035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104763.15 | 30-APR-21:52 | 93103.14 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.435628E+11 | 0.00 | 441.85 | 0.245998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109025.97 | 07-MAY-17:42 | 98950.83 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.609160E+11 | 0.00 | 521.58 | 0.367369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115678.10 | 26-JUN-08:21 | 87014.42 | 18-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.691290E+11 | 0.00 | 551.15 | 0.413993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117328.31 | 23-JUL-08:51 | 86940.29 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.693543E+11 | 0.00 | 571.72 | 0.402744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125853.18 | 20-AUG-07:52 | 88435.61 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.446244E+11 | 0.00 | 440.45 | 0.241877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112785.87 | 17-SEP-08:52 | 86843.34 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.200413E+11 | 0.00 | 368.51 | 0.910412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115172.44 | 18-OCT-21:52 | 95121.34 | 11-OCT-21:52 | 0.00 | 0.00 | 0.00 |
November | 0.798902E+10 | 0.00 | 236.23 | 0.429453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102733.29 | 05-NOV-21:52 | 91070.70 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 0.220602E+10 | 0.00 | 109.32 | 0.983738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99482.96 | 13-DEC-21:02 | 78386.57 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362411E+12 | 0.00 | 4133.50 | 0.206798E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.951331E+09 | 0.00 | 48.22 | 0.357034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88642.13 | 78386.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.693543E+11 | 0.00 | 571.72 | 0.413993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125853.18 | 98950.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 57427992.23 | 0.00 | 25.00 | 43804429.38 | 0.00 | 0.00 | 0.00 | 0.00 | 13409.27 | 29-JAN-16:01 | 13409.27 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.577116E+09 | 0.00 | 118.49 | 0.483570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13587.11 | 28-FEB-19:01 | 13587.11 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.180879E+10 | 0.00 | 349.91 | 0.104752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14030.79 | 28-MAR-15:01 | 13585.55 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.379620E+10 | 0.00 | 526.40 | 0.193597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14869.90 | 02-APR-15:01 | 13584.87 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.652843E+10 | 0.00 | 678.63 | 0.327883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14932.28 | 27-MAY-08:62 | 13588.84 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.928736E+10 | 0.00 | 697.88 | 0.505515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15367.29 | 23-JUN-08:61 | 12226.28 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.109706E+11 | 0.00 | 715.09 | 0.613343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16218.97 | 30-JUL-08:62 | 12211.33 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.113297E+11 | 0.00 | 722.13 | 0.633529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15546.46 | 24-AUG-08:61 | 12226.85 | 21-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.715417E+10 | 0.00 | 646.69 | 0.353727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15795.47 | 17-SEP-08:61 | 12256.78 | 15-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.311622E+10 | 0.00 | 444.55 | 0.143307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15857.60 | 01-OCT-15:01 | 12243.48 | 05-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.876648E+09 | 0.00 | 217.93 | 0.457363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14936.01 | 04-NOV-15:02 | 13586.99 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.205937E+09 | 0.00 | 68.20 | 0.110372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14127.15 | 13-DEC-16:02 | 13581.43 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557086E+11 | 0.00 | 5210.90 | 0.298516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 57427992.23 | 0.00 | 25.00 | 43804429.38 | 0.00 | 0.00 | 0.00 | 0.00 | 13409.27 | 12211.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113297E+11 | 0.00 | 722.13 | 0.633529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16218.97 | 13588.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6034065.99 | 0.00 | 2.70 | 4592522.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8900.65 | 31-JAN-16:01 | 7465.28 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.163322E+09 | 0.00 | 39.95 | 0.115287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13463.84 | 27-FEB-16:01 | 13463.84 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.779887E+09 | 0.00 | 172.47 | 0.382450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14049.64 | 28-MAR-15:01 | 13467.71 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.244487E+10 | 0.00 | 375.48 | 0.117993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15003.91 | 02-APR-15:01 | 13470.41 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.511951E+10 | 0.00 | 505.14 | 0.262221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15732.59 | 30-MAY-08:51 | 13411.36 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.832197E+10 | 0.00 | 576.40 | 0.472648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17269.02 | 29-JUN-08:51 | 13462.99 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.984703E+10 | 0.00 | 598.13 | 0.573965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17139.36 | 23-JUL-08:51 | 12504.68 | 25-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.100590E+11 | 0.00 | 627.39 | 0.567698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17678.41 | 20-AUG-07:52 | 13139.21 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.534045E+10 | 0.00 | 496.77 | 0.259468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16930.72 | 06-SEP-08:31 | 13028.50 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.146733E+10 | 0.00 | 239.65 | 0.595916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15860.79 | 01-OCT-15:01 | 12048.68 | 09-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.183826E+09 | 0.00 | 59.35 | 81027017.17 | 0.00 | 0.00 | 0.00 | 0.00 | 14859.30 | 05-NOV-15:02 | 12563.92 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 18657733.07 | 0.00 | 8.40 | 7573470.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13749.66 | 13-DEC-16:02 | 9935.02 | 12-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437519E+11 | 0.00 | 3701.82 | 0.237268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6034065.99 | 0.00 | 2.70 | 4592522.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8900.65 | 7465.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100590E+11 | 0.00 | 627.39 | 0.573965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17678.41 | 13470.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17341998.30 | 0.00 | 16.68 | 16131230.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3932.53 | 29-JAN-16:01 | 3932.53 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.130442E+09 | 0.00 | 86.48 | 0.115913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3936.21 | 21-FEB-16:01 | 3936.21 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.540693E+09 | 0.00 | 293.67 | 0.356198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4057.82 | 28-MAR-15:01 | 3935.98 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.105157E+10 | 0.00 | 477.98 | 0.593120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.24 | 02-APR-15:01 | 3935.75 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.171866E+10 | 0.00 | 647.79 | 0.882984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4435.55 | 27-MAY-08:62 | 3936.86 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.243142E+10 | 0.00 | 677.44 | 0.134677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4672.86 | 29-JUN-08:61 | 3493.98 | 18-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.283981E+10 | 0.00 | 701.46 | 0.160670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4911.65 | 30-JUL-08:62 | 3496.01 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.300269E+10 | 0.00 | 710.58 | 0.169666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4694.94 | 29-AUG-08:61 | 3544.14 | 23-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.184562E+10 | 0.00 | 622.75 | 0.914540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4767.17 | 17-SEP-08:61 | 3520.44 | 03-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.821202E+09 | 0.00 | 385.14 | 0.410105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4588.06 | 18-OCT-08:62 | 3853.61 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.240298E+09 | 0.00 | 174.70 | 0.144382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4392.39 | 04-NOV-15:02 | 3936.43 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 52662851.52 | 0.00 | 50.36 | 34146691.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4152.02 | 13-DEC-16:02 | 3935.35 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146924E+11 | 0.00 | 4845.04 | 0.811765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17341998.30 | 0.00 | 16.68 | 16131230.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3932.53 | 3493.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.300269E+10 | 0.00 | 710.58 | 0.169666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4911.65 | 3936.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1480333.11 | 0.00 | 0.95 | 996982.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.84 | 20-JAN-16:01 | 2002.84 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 22075188.11 | 0.00 | 19.18 | 16360247.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.87 | 21-FEB-16:01 | 3890.87 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.225700E+09 | 0.00 | 148.27 | 0.123623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.83 | 28-MAR-15:01 | 3890.44 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.670246E+09 | 0.00 | 345.70 | 0.342953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4274.61 | 30-APR-21:52 | 4084.78 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.139133E+10 | 0.00 | 492.43 | 0.728801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4511.50 | 07-MAY-17:42 | 4144.27 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.224870E+10 | 0.00 | 566.81 | 0.132358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4984.07 | 26-JUN-08:21 | 3529.07 | 05-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.262184E+10 | 0.00 | 590.13 | 0.156386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4930.96 | 23-JUL-08:51 | 3560.11 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.271448E+10 | 0.00 | 620.66 | 0.156431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5275.61 | 20-AUG-07:52 | 3825.00 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.141933E+10 | 0.00 | 478.90 | 0.695162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4762.37 | 17-SEP-08:52 | 3714.85 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.364235E+09 | 0.00 | 205.42 | 0.152851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4736.61 | 18-OCT-21:52 | 3679.77 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 39439933.86 | 0.00 | 37.87 | 21252255.75 | 0.00 | 0.00 | 0.00 | 0.00 | 4328.97 | 04-NOV-15:02 | 3890.97 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 4092673.27 | 0.00 | 5.10 | 2573042.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3886.05 | 12-DEC-16:01 | 3710.81 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117230E+11 | 0.00 | 3511.42 | 0.653632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1480333.11 | 0.00 | 0.95 | 996982.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.84 | 2002.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.271448E+10 | 0.00 | 620.66 | 0.156431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5275.61 | 4144.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100692E+10 | 0.00 | 137.88 | 0.897858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17906.31 | 10-JAN-16:01 | 17906.31 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.183303E+10 | 0.00 | 202.70 | 0.157295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18223.01 | 19-FEB-16:02 | 17908.36 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.433349E+10 | 0.00 | 442.08 | 0.292248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17922.30 | 31-MAR-15:01 | 17907.76 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.598464E+10 | 0.00 | 536.43 | 0.327521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19371.86 | 21-APR-18:01 | 17908.09 | 27-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.858415E+10 | 0.00 | 656.98 | 0.423382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19764.30 | 27-MAY-08:62 | 17905.25 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.116178E+11 | 0.00 | 673.35 | 0.615033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22005.98 | 29-JUN-08:61 | 16126.81 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.138770E+11 | 0.00 | 698.42 | 0.755179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22396.28 | 30-JUL-08:62 | 16131.21 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.154652E+11 | 0.00 | 708.49 | 0.894050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21776.72 | 29-AUG-08:61 | 16158.51 | 21-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.110058E+11 | 0.00 | 641.98 | 0.596536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21586.36 | 17-SEP-08:61 | 16175.11 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.700532E+10 | 0.00 | 526.49 | 0.403728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20982.72 | 18-OCT-08:62 | 17907.29 | 26-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.398212E+10 | 0.00 | 404.53 | 0.267093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19808.03 | 04-NOV-15:02 | 17908.17 | 11-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.203570E+10 | 0.00 | 228.07 | 0.161883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18906.77 | 13-DEC-16:02 | 17907.90 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.867311E+11 | 0.00 | 5857.40 | 0.498374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100692E+10 | 0.00 | 137.88 | 0.897858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17906.31 | 16126.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.154652E+11 | 0.00 | 708.49 | 0.894050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22396.28 | 17908.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.26 | 366.27 | 160.99 | 607.11 | 578.61 | 0.00 | 0.00 | 0.00 |
February | 491.15 | 327.66 | 163.48 | 618.37 | 476.64 | 0.00 | 0.00 | 0.00 |
March | 449.12 | 235.68 | 213.44 | 637.19 | 295.51 | 0.00 | 0.00 | 0.00 |
April | 338.00 | 112.77 | 225.23 | 546.24 | 227.51 | 0.00 | 0.00 | 0.00 |
May | 271.69 | 33.25 | 238.45 | 481.94 | 130.17 | 0.00 | 0.00 | 0.00 |
June | 249.47 | 13.93 | 235.54 | 518.87 | 71.28 | 0.00 | 0.00 | 0.00 |
July | 250.25 | 16.88 | 233.37 | 540.93 | 41.43 | 0.00 | 0.00 | 0.00 |
August | 301.54 | 56.67 | 244.87 | 641.64 | 31.85 | 0.00 | 0.00 | 0.00 |
September | 340.43 | 132.46 | 207.97 | 621.62 | 100.84 | 0.00 | 0.00 | 0.00 |
October | 478.03 | 308.97 | 169.06 | 735.78 | 260.76 | 0.00 | 0.00 | 0.00 |
November | 522.27 | 348.52 | 173.76 | 717.92 | 364.70 | 0.00 | 0.00 | 0.00 |
December | 523.54 | 368.30 | 155.25 | 648.74 | 476.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.80 | 192.80 | 202.00 | 609.72 | 253.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 13.93 | 155.25 | 481.94 | 31.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.26 | 368.30 | 244.87 | 735.78 | 578.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1484.72 | 1031.40 | 453.32 | 1690.45 | 1661.00 | 0.00 | 0.00 | 0.00 |
February | 1383.03 | 922.68 | 460.35 | 1722.10 | 1386.65 | 0.00 | 0.00 | 0.00 |
March | 1264.70 | 663.66 | 601.04 | 1771.92 | 890.86 | 0.00 | 0.00 | 0.00 |
April | 951.78 | 317.55 | 634.23 | 1517.28 | 694.27 | 0.00 | 0.00 | 0.00 |
May | 765.07 | 93.63 | 671.45 | 1334.03 | 421.30 | 0.00 | 0.00 | 0.00 |
June | 702.49 | 39.22 | 663.27 | 1443.85 | 242.91 | 0.00 | 0.00 | 0.00 |
July | 704.68 | 47.53 | 657.15 | 1512.85 | 151.08 | 0.00 | 0.00 | 0.00 |
August | 849.11 | 159.58 | 689.52 | 1802.26 | 121.41 | 0.00 | 0.00 | 0.00 |
September | 958.64 | 373.00 | 585.64 | 1731.06 | 338.07 | 0.00 | 0.00 | 0.00 |
October | 1346.11 | 870.05 | 476.06 | 2051.76 | 798.00 | 0.00 | 0.00 | 0.00 |
November | 1470.69 | 981.40 | 489.29 | 2000.67 | 1082.90 | 0.00 | 0.00 | 0.00 |
December | 1474.27 | 1037.10 | 437.17 | 1806.43 | 1382.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1111.73 | 542.91 | 568.82 | 1698.81 | 761.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 702.49 | 39.22 | 437.17 | 1334.03 | 121.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.72 | 1037.10 | 689.52 | 2051.76 | 1661.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1928.74 | 1339.84 | 588.89 | 2237.78 | 2227.80 | 0.00 | 0.00 | 0.00 |
February | 1796.64 | 1198.62 | 598.02 | 2288.63 | 1851.54 | 0.00 | 0.00 | 0.00 |
March | 1642.92 | 862.13 | 780.79 | 2368.69 | 1172.68 | 0.00 | 0.00 | 0.00 |
April | 1236.41 | 412.51 | 823.90 | 2031.60 | 917.37 | 0.00 | 0.00 | 0.00 |
May | 993.87 | 121.63 | 872.25 | 1787.67 | 552.04 | 0.00 | 0.00 | 0.00 |
June | 912.57 | 50.95 | 861.62 | 1934.29 | 313.71 | 0.00 | 0.00 | 0.00 |
July | 915.42 | 61.75 | 853.67 | 2030.39 | 191.46 | 0.00 | 0.00 | 0.00 |
August | 1103.04 | 207.31 | 895.73 | 2425.00 | 145.25 | 0.00 | 0.00 | 0.00 |
September | 1245.33 | 484.54 | 760.78 | 2317.06 | 435.51 | 0.00 | 0.00 | 0.00 |
October | 1748.68 | 1130.24 | 618.43 | 2744.61 | 1046.13 | 0.00 | 0.00 | 0.00 |
November | 1910.51 | 1274.89 | 635.62 | 2665.99 | 1435.61 | 0.00 | 0.00 | 0.00 |
December | 1915.16 | 1347.25 | 567.91 | 2398.79 | 1848.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1444.20 | 705.27 | 738.93 | 2269.40 | 1007.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 912.57 | 50.95 | 567.91 | 1787.67 | 145.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.74 | 1347.25 | 895.73 | 2744.61 | 2227.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 117.47 | 126.41 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 119.69 | 103.96 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 122.57 | 64.06 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 105.37 | 49.08 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 93.53 | 26.98 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 106.12 | 12.47 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 113.73 | 5.87 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 136.23 | 2.92 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.95 | 18.43 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 145.10 | 54.51 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 140.47 | 78.19 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 126.12 | 103.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.97 | 53.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 93.53 | 2.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 145.10 | 126.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.97 | 267.78 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 94.98 | 216.26 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 176.71 | 124.35 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.54 | 90.39 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 266.52 | 49.94 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 322.56 | 23.14 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 320.31 | 10.87 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 316.95 | 5.44 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 221.10 | 34.54 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 158.77 | 107.64 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 100.76 | 161.67 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.78 | 218.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 195.29 | 108.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.78 | 5.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 322.56 | 267.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.72 | 151.65 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.75 | 120.98 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.79 | 68.83 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 45.06 | 50.24 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 69.51 | 27.31 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 100.98 | 12.42 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 103.66 | 6.39 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.93 | 3.24 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 54.49 | 19.96 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.16 | 58.99 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.59 | 87.27 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.41 | 120.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.63 | 60.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.72 | 3.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 103.66 | 151.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.63 | 263.31 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 98.43 | 213.21 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 179.41 | 123.70 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.52 | 92.91 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.19 | 53.48 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 319.60 | 24.97 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.46 | 12.33 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 315.57 | 6.14 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 220.72 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 161.31 | 107.84 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 105.32 | 158.56 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 65.11 | 214.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 196.22 | 108.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 65.11 | 6.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 319.60 | 263.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.38 | 57.92 | 25.46 | 89.59 | 106.89 | 0.00 | 0.00 | 0.00 |
February | 77.67 | 51.82 | 25.85 | 87.51 | 100.97 | 0.00 | 0.00 | 0.00 |
March | 71.03 | 37.27 | 33.75 | 83.86 | 79.12 | 0.00 | 0.00 | 0.00 |
April | 53.45 | 17.83 | 35.62 | 69.86 | 64.62 | 0.00 | 0.00 | 0.00 |
May | 42.97 | 5.26 | 37.71 | 59.22 | 43.61 | 0.00 | 0.00 | 0.00 |
June | 39.45 | 2.20 | 37.25 | 66.58 | 27.44 | 0.00 | 0.00 | 0.00 |
July | 39.57 | 2.67 | 36.91 | 71.41 | 20.19 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 8.96 | 38.72 | 88.90 | 17.46 | 0.00 | 0.00 | 0.00 |
September | 53.84 | 20.95 | 32.89 | 84.38 | 36.87 | 0.00 | 0.00 | 0.00 |
October | 75.60 | 48.86 | 26.74 | 102.26 | 71.78 | 0.00 | 0.00 | 0.00 |
November | 82.59 | 55.11 | 27.48 | 98.18 | 93.01 | 0.00 | 0.00 | 0.00 |
December | 82.79 | 58.24 | 24.55 | 89.43 | 108.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.43 | 30.49 | 31.95 | 82.59 | 64.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.45 | 2.20 | 24.55 | 59.22 | 17.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.38 | 58.24 | 38.72 | 102.26 | 108.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.71 | 0.00 | 15.71 | 1.96 | 127.22 | 0.00 | 0.00 | 0.00 |
February | 17.41 | 0.00 | 17.41 | 7.72 | 101.02 | 0.00 | 0.00 | 0.00 |
March | 24.45 | 0.00 | 24.45 | 19.00 | 55.60 | 0.00 | 0.00 | 0.00 |
April | 29.65 | 0.17 | 29.48 | 37.84 | 39.76 | 0.00 | 0.00 | 0.00 |
May | 35.37 | 1.11 | 34.27 | 58.18 | 21.08 | 0.00 | 0.00 | 0.00 |
June | 38.91 | 2.55 | 36.35 | 84.61 | 8.87 | 0.00 | 0.00 | 0.00 |
July | 36.85 | 1.89 | 34.96 | 87.14 | 4.33 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 0.38 | 32.34 | 81.51 | 1.88 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 46.05 | 15.26 | 0.00 | 0.00 | 0.00 |
October | 18.77 | 0.00 | 18.77 | 20.16 | 47.89 | 0.00 | 0.00 | 0.00 |
November | 16.80 | 0.00 | 16.80 | 9.92 | 72.42 | 0.00 | 0.00 | 0.00 |
December | 14.52 | 0.00 | 14.52 | 2.30 | 101.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.53 | 0.51 | 25.02 | 38.21 | 49.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 0.00 | 14.52 | 1.96 | 1.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.91 | 2.55 | 36.35 | 87.14 | 127.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 51.83 | 260.10 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 94.45 | 204.46 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 147.80 | 115.11 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 223.98 | 83.18 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 280.29 | 45.91 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 335.85 | 20.97 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 343.48 | 10.44 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 322.38 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 224.56 | 32.80 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 147.33 | 100.13 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 86.00 | 148.78 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 52.14 | 205.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 193.04 | 102.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 51.83 | 5.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 343.48 | 260.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.87 | 126.10 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.66 | 103.73 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.63 | 63.50 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.37 | 48.76 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.57 | 26.81 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 105.31 | 12.31 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 113.03 | 5.79 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 135.90 | 2.82 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.44 | 18.23 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.27 | 54.13 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.81 | 77.85 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.51 | 102.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.23 | 53.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.57 | 2.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.27 | 126.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.58 | 151.68 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.34 | 121.14 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.39 | 68.08 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.15 | 49.61 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.25 | 26.91 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 99.56 | 12.19 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 102.39 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.26 | 3.12 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.64 | 19.72 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.46 | 58.39 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.39 | 86.74 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.27 | 120.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 44.93 | 60.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.58 | 3.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 102.39 | 151.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 53.79 | 253.72 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 97.53 | 200.56 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 151.22 | 113.73 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 224.37 | 85.23 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 277.41 | 49.07 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 331.38 | 22.55 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 339.10 | 11.81 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 320.05 | 5.68 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 223.22 | 34.93 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 150.12 | 99.72 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 90.73 | 144.64 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 55.15 | 199.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 193.35 | 101.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 53.79 | 5.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 339.10 | 253.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.28 | 192.19 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.94 | 151.12 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 32.72 | 81.26 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 63.60 | 57.75 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 95.95 | 31.05 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 132.13 | 15.76 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 132.87 | 9.13 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 121.82 | 5.45 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 73.17 | 24.34 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 33.97 | 70.12 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 17.04 | 106.88 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.93 | 151.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 60.55 | 74.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.28 | 5.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 132.87 | 192.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.17 | 0.00 | 9.17 | 1.21 | 70.85 | 0.00 | 0.00 | 0.00 |
February | 10.16 | 0.00 | 10.16 | 4.77 | 55.71 | 0.00 | 0.00 | 0.00 |
March | 14.27 | 0.00 | 14.27 | 12.06 | 29.96 | 0.00 | 0.00 | 0.00 |
April | 17.30 | 0.10 | 17.20 | 23.45 | 21.29 | 0.00 | 0.00 | 0.00 |
May | 20.64 | 0.65 | 19.99 | 35.37 | 11.44 | 0.00 | 0.00 | 0.00 |
June | 22.70 | 1.49 | 21.21 | 48.71 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 21.50 | 1.10 | 20.40 | 48.98 | 3.36 | 0.00 | 0.00 | 0.00 |
August | 19.10 | 0.22 | 18.87 | 44.91 | 2.01 | 0.00 | 0.00 | 0.00 |
September | 14.41 | 0.01 | 14.41 | 26.98 | 8.97 | 0.00 | 0.00 | 0.00 |
October | 10.95 | 0.00 | 10.95 | 12.52 | 25.85 | 0.00 | 0.00 | 0.00 |
November | 9.80 | 0.00 | 9.80 | 6.28 | 39.40 | 0.00 | 0.00 | 0.00 |
December | 8.47 | 0.00 | 8.47 | 1.45 | 55.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.90 | 0.30 | 14.60 | 22.32 | 27.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.47 | 0.00 | 8.47 | 1.21 | 2.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.70 | 1.49 | 21.21 | 48.98 | 70.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.64 | 33.79 | 14.85 | 55.35 | 57.76 | 0.00 | 0.00 | 0.00 |
February | 45.31 | 30.23 | 15.08 | 56.88 | 47.11 | 0.00 | 0.00 | 0.00 |
March | 41.43 | 21.74 | 19.69 | 59.52 | 27.98 | 0.00 | 0.00 | 0.00 |
April | 31.18 | 10.40 | 20.78 | 51.56 | 21.49 | 0.00 | 0.00 | 0.00 |
May | 25.07 | 3.07 | 22.00 | 45.87 | 12.12 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.28 | 21.73 | 50.27 | 6.26 | 0.00 | 0.00 | 0.00 |
July | 23.09 | 1.56 | 21.53 | 52.87 | 3.49 | 0.00 | 0.00 | 0.00 |
August | 27.82 | 5.23 | 22.59 | 63.15 | 2.03 | 0.00 | 0.00 | 0.00 |
September | 31.41 | 12.22 | 19.19 | 59.52 | 8.90 | 0.00 | 0.00 | 0.00 |
October | 44.10 | 28.50 | 15.60 | 69.70 | 24.16 | 0.00 | 0.00 | 0.00 |
November | 48.18 | 32.15 | 16.03 | 67.25 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 33.98 | 14.32 | 59.67 | 46.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.42 | 17.79 | 18.64 | 57.65 | 24.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.01 | 1.28 | 14.32 | 45.87 | 2.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.64 | 33.98 | 22.59 | 69.70 | 57.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.02 | 91.71 | 40.31 | 150.24 | 156.78 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 82.05 | 40.94 | 154.40 | 127.86 | 0.00 | 0.00 | 0.00 |
March | 112.46 | 59.01 | 53.45 | 161.54 | 75.94 | 0.00 | 0.00 | 0.00 |
April | 84.63 | 28.24 | 56.40 | 139.95 | 58.33 | 0.00 | 0.00 | 0.00 |
May | 68.03 | 8.33 | 59.71 | 124.51 | 32.91 | 0.00 | 0.00 | 0.00 |
June | 62.47 | 3.49 | 58.98 | 136.43 | 16.99 | 0.00 | 0.00 | 0.00 |
July | 62.66 | 4.23 | 58.43 | 143.50 | 9.47 | 0.00 | 0.00 | 0.00 |
August | 75.50 | 14.19 | 61.31 | 171.40 | 5.51 | 0.00 | 0.00 | 0.00 |
September | 85.24 | 33.17 | 52.08 | 161.55 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 119.70 | 77.37 | 42.33 | 189.18 | 65.58 | 0.00 | 0.00 | 0.00 |
November | 130.78 | 87.27 | 43.51 | 182.53 | 94.15 | 0.00 | 0.00 | 0.00 |
December | 131.09 | 92.22 | 38.87 | 161.97 | 127.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.86 | 48.28 | 50.58 | 156.46 | 65.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.47 | 3.49 | 38.87 | 124.51 | 5.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 92.22 | 61.31 | 189.18 | 156.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.94 | 125.91 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.81 | 103.49 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.05 | 63.75 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 103.72 | 49.00 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 91.83 | 26.93 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 104.90 | 12.20 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 112.56 | 5.64 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.95 | 2.70 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.58 | 18.11 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 143.61 | 54.12 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.50 | 77.60 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.48 | 102.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 119.77 | 53.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 91.83 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 143.61 | 125.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.78 | 266.90 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 94.09 | 215.18 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 174.09 | 123.59 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 232.02 | 90.16 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 262.62 | 49.80 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 318.98 | 22.58 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.30 | 10.42 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 314.02 | 5.04 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.57 | 33.88 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 156.62 | 106.78 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 99.68 | 160.49 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.56 | 217.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.07 | 107.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.56 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 318.98 | 266.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.81 | 151.31 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.81 | 120.57 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.38 | 68.69 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 43.92 | 50.71 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 67.86 | 27.76 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 99.76 | 12.32 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 102.52 | 6.28 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 94.95 | 3.04 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.65 | 19.80 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.78 | 58.84 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.71 | 86.57 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.64 | 119.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.02 | 60.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.81 | 3.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 102.52 | 151.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.46 | 262.78 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 97.64 | 212.33 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 176.94 | 123.18 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 231.64 | 93.57 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 259.82 | 54.13 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 315.86 | 24.63 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 314.30 | 11.98 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 312.54 | 5.74 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.07 | 36.59 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 159.25 | 107.38 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 104.75 | 157.22 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 65.30 | 212.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.99 | 108.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 65.30 | 5.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 315.86 | 262.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.89 | 106.21 | 46.68 | 163.12 | 192.82 | 0.00 | 0.00 | 0.00 |
February | 142.42 | 95.01 | 47.41 | 167.93 | 158.34 | 0.00 | 0.00 | 0.00 |
March | 130.23 | 68.34 | 61.89 | 174.54 | 95.57 | 0.00 | 0.00 | 0.00 |
April | 98.01 | 32.70 | 65.31 | 152.27 | 71.40 | 0.00 | 0.00 | 0.00 |
May | 78.78 | 9.64 | 69.14 | 137.18 | 38.22 | 0.00 | 0.00 | 0.00 |
June | 72.34 | 4.04 | 68.30 | 158.11 | 16.60 | 0.00 | 0.00 | 0.00 |
July | 72.57 | 4.89 | 67.67 | 169.67 | 7.39 | 0.00 | 0.00 | 0.00 |
August | 87.44 | 16.43 | 71.00 | 202.15 | 3.38 | 0.00 | 0.00 | 0.00 |
September | 98.72 | 38.41 | 60.31 | 182.30 | 26.10 | 0.00 | 0.00 | 0.00 |
October | 138.62 | 89.59 | 49.02 | 207.90 | 81.71 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 101.06 | 50.39 | 198.92 | 118.98 | 0.00 | 0.00 | 0.00 |
December | 151.81 | 106.80 | 45.02 | 176.08 | 157.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.48 | 55.91 | 58.58 | 174.25 | 80.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.34 | 4.04 | 45.02 | 137.18 | 3.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.89 | 106.80 | 71.00 | 207.90 | 192.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 14.76 | 1137.77 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 60.33 | 922.08 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 148.69 | 540.93 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 302.41 | 397.81 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 465.52 | 236.43 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 663.86 | 129.77 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 672.28 | 83.61 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 615.06 | 62.69 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 359.01 | 190.65 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 158.16 | 474.73 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 75.88 | 680.70 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 16.12 | 925.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 297.35 | 479.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 14.76 | 62.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 672.28 | 1137.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 13.11 | 1168.07 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 55.60 | 951.93 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 136.91 | 566.20 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 287.14 | 415.90 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 448.64 | 248.38 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 648.75 | 136.99 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 658.39 | 89.65 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 601.78 | 68.47 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 344.91 | 203.34 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 147.24 | 499.07 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 67.56 | 709.29 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 13.55 | 958.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 286.62 | 499.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 13.11 | 68.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 658.39 | 1168.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.56 | 159.49 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.01 | 128.69 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 25.90 | 73.67 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 52.86 | 53.19 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 81.14 | 31.60 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 113.00 | 17.64 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 116.02 | 10.95 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 107.53 | 7.93 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 64.57 | 23.64 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 28.48 | 63.34 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.97 | 92.60 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 2.97 | 128.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 51.82 | 65.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.56 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 116.02 | 159.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.23 | 73.86 | 88.36 | 108.38 | 536.11 | 0.00 | 0.00 | 0.00 |
February | 203.60 | 109.60 | 94.00 | 199.91 | 431.20 | 0.00 | 0.00 | 0.00 |
March | 256.16 | 116.85 | 139.31 | 319.80 | 251.33 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 141.33 | 168.31 | 484.52 | 187.01 | 0.00 | 0.00 | 0.00 |
May | 339.21 | 143.45 | 195.76 | 602.54 | 116.72 | 0.00 | 0.00 | 0.00 |
June | 350.85 | 146.95 | 203.90 | 713.49 | 65.78 | 0.00 | 0.00 | 0.00 |
July | 341.97 | 143.47 | 198.50 | 726.43 | 41.30 | 0.00 | 0.00 | 0.00 |
August | 313.43 | 124.33 | 189.10 | 682.83 | 29.90 | 0.00 | 0.00 | 0.00 |
September | 256.88 | 113.51 | 143.37 | 488.64 | 86.64 | 0.00 | 0.00 | 0.00 |
October | 219.71 | 114.36 | 105.35 | 323.04 | 220.55 | 0.00 | 0.00 | 0.00 |
November | 174.98 | 78.93 | 96.05 | 190.44 | 311.18 | 0.00 | 0.00 | 0.00 |
December | 151.85 | 69.12 | 82.73 | 110.57 | 428.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.97 | 114.63 | 142.34 | 413.68 | 224.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.85 | 69.12 | 82.73 | 108.38 | 29.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.85 | 146.95 | 203.90 | 726.43 | 536.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 119.07 | 130.03 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 122.07 | 109.05 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 128.32 | 68.91 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 113.46 | 53.49 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 103.88 | 32.75 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 116.61 | 18.43 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 124.14 | 11.11 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 146.64 | 7.94 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 135.20 | 23.34 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 152.24 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 145.95 | 81.69 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 128.43 | 107.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 128.05 | 58.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 103.88 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 152.24 | 130.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.00 | 195.72 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.03 | 154.17 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 30.37 | 83.42 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 60.21 | 59.51 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 91.07 | 33.14 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 125.57 | 17.97 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 125.34 | 11.07 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 114.03 | 7.58 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 69.68 | 25.58 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 31.74 | 72.03 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 15.60 | 109.38 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.42 | 155.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 57.09 | 76.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.00 | 7.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 125.57 | 195.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 0.00 | 22.25 | 2.69 | 175.11 | 0.00 | 0.00 | 0.00 |
February | 24.66 | 0.00 | 24.66 | 10.76 | 137.93 | 0.00 | 0.00 | 0.00 |
March | 34.63 | 0.00 | 34.63 | 27.17 | 74.63 | 0.00 | 0.00 | 0.00 |
April | 41.99 | 0.25 | 41.74 | 53.87 | 53.25 | 0.00 | 0.00 | 0.00 |
May | 50.10 | 1.57 | 48.53 | 81.48 | 29.65 | 0.00 | 0.00 | 0.00 |
June | 55.10 | 3.61 | 51.48 | 112.35 | 16.08 | 0.00 | 0.00 | 0.00 |
July | 52.18 | 2.67 | 49.51 | 112.14 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 46.35 | 0.54 | 45.80 | 102.02 | 6.78 | 0.00 | 0.00 | 0.00 |
September | 34.98 | 0.01 | 34.97 | 62.35 | 22.88 | 0.00 | 0.00 | 0.00 |
October | 26.58 | 0.00 | 26.58 | 28.40 | 64.44 | 0.00 | 0.00 | 0.00 |
November | 23.79 | 0.00 | 23.79 | 13.96 | 97.86 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 3.06 | 138.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.16 | 0.73 | 35.43 | 51.08 | 68.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 2.69 | 6.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.10 | 3.61 | 51.48 | 112.35 | 175.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.19 | 270.36 | 118.83 | 434.94 | 468.49 | 0.00 | 0.00 | 0.00 |
February | 362.53 | 241.86 | 120.67 | 446.49 | 383.96 | 0.00 | 0.00 | 0.00 |
March | 331.52 | 173.96 | 157.55 | 464.69 | 229.55 | 0.00 | 0.00 | 0.00 |
April | 249.49 | 83.24 | 166.25 | 400.18 | 177.56 | 0.00 | 0.00 | 0.00 |
May | 200.55 | 24.54 | 176.01 | 351.94 | 103.85 | 0.00 | 0.00 | 0.00 |
June | 184.14 | 10.28 | 173.86 | 382.74 | 57.17 | 0.00 | 0.00 | 0.00 |
July | 184.72 | 12.46 | 172.26 | 400.63 | 34.12 | 0.00 | 0.00 | 0.00 |
August | 222.58 | 41.83 | 180.75 | 481.05 | 22.89 | 0.00 | 0.00 | 0.00 |
September | 251.29 | 97.77 | 153.51 | 463.85 | 75.29 | 0.00 | 0.00 | 0.00 |
October | 352.86 | 228.06 | 124.79 | 546.74 | 198.55 | 0.00 | 0.00 | 0.00 |
November | 385.51 | 257.25 | 128.26 | 528.75 | 283.29 | 0.00 | 0.00 | 0.00 |
December | 386.45 | 271.85 | 114.60 | 468.88 | 380.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.42 | 142.31 | 149.11 | 447.62 | 200.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.14 | 10.28 | 114.60 | 351.94 | 22.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.19 | 271.85 | 180.75 | 546.74 | 468.49 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.162609E+10 | 0.154975E+10 |
February | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.149596E+10 | 0.115308E+10 |
March | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.170666E+10 | 0.791488E+09 |
April | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.141585E+10 | 0.589700E+09 |
May | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.129082E+10 | 0.348659E+09 |
June | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.134491E+10 | 0.184752E+09 |
July | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.144883E+10 | 0.110969E+09 |
August | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.171857E+10 | 85318332.75 |
September | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.161123E+10 | 0.261368E+09 |
October | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.197072E+10 | 0.698416E+09 |
November | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.186086E+10 | 0.945302E+09 |
December | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.173759E+10 | 0.127612E+10 |
Annual Sum or Average | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.192281E+11 | 0.799493E+10 |
Minimum of Months | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.129082E+10 | 85318332.75 |
Maximum of Months | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.197072E+10 | 0.154975E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.452770E+10 | 0.444882E+10 |
February | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.416611E+10 | 0.335458E+10 |
March | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.474590E+10 | 0.238609E+10 |
April | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.393280E+10 | 0.179956E+10 |
May | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.357307E+10 | 0.112840E+10 |
June | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.374247E+10 | 0.629623E+09 |
July | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.405201E+10 | 0.404644E+09 |
August | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.482718E+10 | 0.325182E+09 |
September | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.448690E+10 | 0.876278E+09 |
October | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.549542E+10 | 0.213736E+10 |
November | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.518574E+10 | 0.280687E+10 |
December | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.483835E+10 | 0.370391E+10 |
Annual Sum or Average | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.535736E+11 | 0.240013E+11 |
Minimum of Months | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.357307E+10 | 0.325182E+09 |
Maximum of Months | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.549542E+10 | 0.444882E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.599368E+10 | 0.596694E+10 |
February | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.553667E+10 | 0.447924E+10 |
March | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.634431E+10 | 0.314092E+10 |
April | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.526592E+10 | 0.237783E+10 |
May | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.478810E+10 | 0.147857E+10 |
June | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.501368E+10 | 0.813133E+09 |
July | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.543821E+10 | 0.512800E+09 |
August | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.649511E+10 | 0.389042E+09 |
September | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.600583E+10 | 0.112885E+10 |
October | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.735117E+10 | 0.280196E+10 |
November | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.691023E+10 | 0.372110E+10 |
December | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.642493E+10 | 0.495165E+10 |
Annual Sum or Average | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.715678E+11 | 0.317620E+11 |
Minimum of Months | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.478810E+10 | 0.389042E+09 |
Maximum of Months | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.735117E+10 | 0.596694E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.314629E+09 | 0.338571E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.289559E+09 | 0.251492E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.328294E+09 | 0.171585E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.273113E+09 | 0.127212E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.250507E+09 | 72251408.81 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.275060E+09 | 32319116.00 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.304612E+09 | 15732758.46 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.364881E+09 | 7821378.28 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.323871E+09 | 47760006.86 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.388625E+09 | 0.146004E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.364086E+09 | 0.202657E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.337793E+09 | 0.276177E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.381503E+10 | 0.168958E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.250507E+09 | 7821378.28 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.388625E+09 | 0.338571E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.165970E+09 | 0.717227E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.229765E+09 | 0.523179E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.473304E+09 | 0.333056E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.610521E+09 | 0.234287E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.713847E+09 | 0.133753E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.836077E+09 | 59979338.56 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.857905E+09 | 29123506.33 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.848932E+09 | 14571063.94 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.573079E+09 | 89529856.69 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.425258E+09 | 0.288311E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.261161E+09 | 0.419044E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162788E+09 | 0.586480E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.615861E+10 | 0.342854E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162788E+09 | 14571063.94 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.857905E+09 | 0.717227E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7280228.38 | 0.406172E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23589872.27 | 0.292684E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 61043216.76 | 0.184348E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.116797E+09 | 0.130223E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.186176E+09 | 73135370.48 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.261752E+09 | 32204665.41 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.277639E+09 | 17111242.72 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.256936E+09 | 8677190.08 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.141242E+09 | 51729892.80 |
October | 62833545.17 | 0.00 | 62833545.17 | 64713930.94 | 0.157991E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32625846.01 | 0.226202E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9132050.44 | 0.322193E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.143893E+10 | 0.190267E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7280228.38 | 8677190.08 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.277639E+09 | 0.406172E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175789E+09 | 0.705253E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.238119E+09 | 0.515798E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.480544E+09 | 0.331331E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.610475E+09 | 0.240825E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.707596E+09 | 0.143245E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.828412E+09 | 64716237.09 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.850278E+09 | 33015551.81 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.845218E+09 | 16444038.32 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.572107E+09 | 95757442.22 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.432061E+09 | 0.288849E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.272985E+09 | 0.410999E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174399E+09 | 0.573968E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.618799E+10 | 0.342020E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174399E+09 | 16444038.32 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.850278E+09 | 0.705253E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.239945E+09 | 0.286306E+09 |
February | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.211711E+09 | 0.244268E+09 |
March | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.224602E+09 | 0.211903E+09 |
April | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.181078E+09 | 0.167500E+09 |
May | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.158604E+09 | 0.116814E+09 |
June | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.172584E+09 | 71120341.80 |
July | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.191254E+09 | 54085144.04 |
August | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.238107E+09 | 46773098.41 |
September | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.218707E+09 | 95565548.94 |
October | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.273903E+09 | 0.192252E+09 |
November | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.254474E+09 | 0.241081E+09 |
December | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.239540E+09 | 0.291048E+09 |
Annual Sum or Average | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.260451E+10 | 0.201872E+10 |
Minimum of Months | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.158604E+09 | 46773098.41 |
Maximum of Months | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.273903E+09 | 0.291048E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42076451.99 | 0.00 | 42076451.99 | 5241694.06 | 0.340754E+09 |
February | 42124339.93 | 0.00 | 42124339.93 | 18679986.82 | 0.244389E+09 |
March | 65492691.15 | 1318.99 | 65491372.16 | 50882212.91 | 0.148921E+09 |
April | 76848851.72 | 448829.91 | 76400021.81 | 98071653.47 | 0.103065E+09 |
May | 94747450.04 | 2971603.27 | 91775846.77 | 0.155824E+09 | 56460572.96 |
June | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.219314E+09 | 22990660.81 |
July | 98689421.90 | 5056973.36 | 93632448.53 | 0.233400E+09 | 11596054.22 |
August | 87654522.95 | 1029768.70 | 86624754.24 | 0.218304E+09 | 5027099.84 |
September | 64031230.67 | 25170.94 | 64006059.72 | 0.119356E+09 | 39552171.77 |
October | 50273499.29 | 0.00 | 50273499.29 | 53999475.59 | 0.128265E+09 |
November | 43541540.27 | 0.00 | 43541540.27 | 25724266.09 | 0.187717E+09 |
December | 38896548.34 | 0.00 | 38896548.34 | 6147260.63 | 0.271306E+09 |
Annual Sum or Average | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.120494E+10 | 0.156004E+10 |
Minimum of Months | 38896548.34 | 0.00 | 38896548.34 | 5241694.06 | 5027099.84 |
Maximum of Months | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.233400E+09 | 0.340754E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.138824E+09 | 0.696640E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.228502E+09 | 0.494626E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.395870E+09 | 0.308306E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.580553E+09 | 0.215608E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.750735E+09 | 0.122966E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.870521E+09 | 54350256.16 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.919966E+09 | 27964833.11 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.863459E+09 | 13666293.50 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.582051E+09 | 85017056.37 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.394597E+09 | 0.268201E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.222909E+09 | 0.385627E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.139645E+09 | 0.551262E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.608763E+10 | 0.322423E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.138824E+09 | 13666293.50 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.919966E+09 | 0.696640E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.313033E+09 | 0.337750E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.287072E+09 | 0.250951E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.325778E+09 | 0.170079E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.270536E+09 | 0.126392E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.247947E+09 | 71815160.59 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.272976E+09 | 31913602.80 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.302732E+09 | 15510183.53 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.364001E+09 | 7545154.37 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.322561E+09 | 47241782.41 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.386412E+09 | 0.144979E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.362393E+09 | 0.201785E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.336171E+09 | 0.275609E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379161E+10 | 0.168157E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.247947E+09 | 7545154.37 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.386412E+09 | 0.337750E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 6904265.85 | 0.406256E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 22594688.79 | 0.293050E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 59959212.81 | 0.182349E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.114431E+09 | 0.128597E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.182808E+09 | 72063912.12 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.258071E+09 | 31594065.28 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.274253E+09 | 17016945.28 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.255156E+09 | 8365030.49 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.139035E+09 | 51117940.99 |
October | 62833545.17 | 0.00 | 62833545.17 | 62835880.16 | 0.156393E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32112303.33 | 0.224827E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 8753348.21 | 0.322395E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141691E+10 | 0.189402E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 6904265.85 | 8365030.49 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.274253E+09 | 0.406256E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.144084E+09 | 0.679575E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.235946E+09 | 0.485194E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.405020E+09 | 0.304611E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.581557E+09 | 0.220928E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.743028E+09 | 0.131439E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.858933E+09 | 58446677.21 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.908245E+09 | 31642811.17 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.857221E+09 | 15210940.58 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.578581E+09 | 90536726.38 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.402093E+09 | 0.267077E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.235171E+09 | 0.374901E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.147712E+09 | 0.534354E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.609759E+10 | 0.319392E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.144084E+09 | 15210940.58 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.908245E+09 | 0.679575E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8785351.38 | 0.514760E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 31301348.89 | 0.365583E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 87629842.64 | 0.217655E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.164851E+09 | 0.149698E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.256995E+09 | 83151735.70 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.342484E+09 | 40854932.04 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.355885E+09 | 24447433.07 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.326278E+09 | 14597932.57 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.189669E+09 | 63085982.24 |
October | 79574720.39 | 0.00 | 79574720.39 | 90978504.05 | 0.187805E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 44178818.55 | 0.277041E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 10531934.29 | 0.406757E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.190957E+10 | 0.234544E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8785351.38 | 14597932.57 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.355885E+09 | 0.514760E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24551567.91 | 0.00 | 24551567.91 | 3238644.29 | 0.189762E+09 |
February | 24579510.47 | 0.00 | 24579510.47 | 11538973.29 | 0.134769E+09 |
March | 38214920.19 | 769.63 | 38214150.56 | 32303988.46 | 80236605.38 |
April | 44841228.59 | 261891.81 | 44579336.78 | 60770944.65 | 55184816.83 |
May | 55285042.92 | 1733927.56 | 53551115.36 | 94738872.73 | 30653172.82 |
June | 58842496.02 | 3858865.82 | 54983630.20 | 0.126254E+09 | 15060819.62 |
July | 57585179.58 | 2950738.93 | 54634440.65 | 0.131194E+09 | 9012336.12 |
August | 51146327.01 | 600869.02 | 50545457.99 | 0.120279E+09 | 5381402.40 |
September | 37362159.44 | 14687.22 | 37347472.22 | 69920014.11 | 23256105.24 |
October | 29334536.86 | 0.00 | 29334536.86 | 33538443.71 | 69232788.25 |
November | 25406445.47 | 0.00 | 25406445.47 | 16286141.82 | 0.102129E+09 |
December | 22696097.29 | 0.00 | 22696097.29 | 3882507.07 | 0.149947E+09 |
Annual Sum or Average | 0.469846E+09 | 9421749.97 | 0.460424E+09 | 0.703946E+09 | 0.864625E+09 |
Minimum of Months | 22696097.29 | 0.00 | 22696097.29 | 3238644.29 | 5381402.40 |
Maximum of Months | 58842496.02 | 3858865.82 | 54983630.20 | 0.131194E+09 | 0.189762E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130282E+09 | 90503082.87 | 39778691.28 | 0.148258E+09 | 0.154709E+09 |
February | 0.109615E+09 | 73128454.63 | 36486217.96 | 0.137616E+09 | 0.113960E+09 |
March | 0.110976E+09 | 58234705.39 | 52740862.99 | 0.159405E+09 | 74936318.98 |
April | 80823152.87 | 26965191.36 | 53857961.51 | 0.133646E+09 | 55702903.19 |
May | 67134435.80 | 8215580.81 | 58918854.99 | 0.122871E+09 | 32473634.96 |
June | 59654024.21 | 3330445.64 | 56323578.57 | 0.130287E+09 | 16223392.52 |
July | 61834899.83 | 4170846.82 | 57664053.01 | 0.141611E+09 | 9341778.51 |
August | 74508055.00 | 14002973.25 | 60505081.75 | 0.169137E+09 | 5441394.94 |
September | 81405849.48 | 31674060.78 | 49731788.71 | 0.154275E+09 | 23066860.26 |
October | 0.118119E+09 | 76345167.07 | 41774144.65 | 0.186686E+09 | 64715598.58 |
November | 0.124888E+09 | 83337782.51 | 41549955.12 | 0.174316E+09 | 89909958.83 |
December | 0.129365E+09 | 91003310.47 | 38361315.54 | 0.159829E+09 | 0.125320E+09 |
Annual Sum or Average | 0.114860E+10 | 0.560912E+09 | 0.587693E+09 | 0.181794E+10 | 0.765800E+09 |
Minimum of Months | 59654024.21 | 3330445.64 | 36486217.96 | 0.122871E+09 | 5441394.94 |
Maximum of Months | 0.130282E+09 | 91003310.47 | 60505081.75 | 0.186686E+09 | 0.154709E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353611E+09 | 0.245644E+09 | 0.107968E+09 | 0.402402E+09 | 0.419911E+09 |
February | 0.297517E+09 | 0.198486E+09 | 99031058.63 | 0.373518E+09 | 0.309309E+09 |
March | 0.301210E+09 | 0.158061E+09 | 0.143149E+09 | 0.432658E+09 | 0.203392E+09 |
April | 0.219371E+09 | 73189044.97 | 0.146182E+09 | 0.362742E+09 | 0.151189E+09 |
May | 0.182217E+09 | 22298766.77 | 0.159918E+09 | 0.333497E+09 | 88140087.62 |
June | 0.161913E+09 | 9039510.68 | 0.152874E+09 | 0.353625E+09 | 44033605.73 |
July | 0.167833E+09 | 11320531.40 | 0.156512E+09 | 0.384361E+09 | 25355497.69 |
August | 0.202230E+09 | 38006933.66 | 0.164223E+09 | 0.459073E+09 | 14769058.89 |
September | 0.220952E+09 | 85969879.73 | 0.134982E+09 | 0.418735E+09 | 62608176.96 |
October | 0.320600E+09 | 0.207216E+09 | 0.113384E+09 | 0.506705E+09 | 0.175651E+09 |
November | 0.338971E+09 | 0.226196E+09 | 0.112775E+09 | 0.473130E+09 | 0.244034E+09 |
December | 0.351122E+09 | 0.247002E+09 | 0.104120E+09 | 0.433809E+09 | 0.340144E+09 |
Annual Sum or Average | 0.311755E+10 | 0.152243E+10 | 0.159512E+10 | 0.493425E+10 | 0.207854E+10 |
Minimum of Months | 0.161913E+09 | 9039510.68 | 99031058.63 | 0.333497E+09 | 14769058.89 |
Maximum of Months | 0.353611E+09 | 0.247002E+09 | 0.164223E+09 | 0.506705E+09 | 0.419911E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.313224E+09 | 0.337231E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.287428E+09 | 0.250369E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.324226E+09 | 0.170759E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.268837E+09 | 0.127001E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.245970E+09 | 72116010.21 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.271890E+09 | 31633363.67 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.301493E+09 | 15097989.61 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.361463E+09 | 7236938.61 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.320315E+09 | 46934444.76 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.384646E+09 | 0.144952E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.361583E+09 | 0.201151E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.336084E+09 | 0.274327E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.377716E+10 | 0.167881E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.245970E+09 | 7236938.61 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.384646E+09 | 0.337231E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.165475E+09 | 0.714861E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.227621E+09 | 0.520557E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.466283E+09 | 0.331028E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.601407E+09 | 0.233682E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.703392E+09 | 0.133372E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.826809E+09 | 58536497.27 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.849845E+09 | 27898823.07 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.841076E+09 | 13500233.29 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.566521E+09 | 87821737.53 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.419494E+09 | 0.285992E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.258378E+09 | 0.415987E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162210E+09 | 0.582396E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.608851E+10 | 0.340563E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.162210E+09 | 13500233.29 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.849845E+09 | 0.714861E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7533104.25 | 0.405281E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23742640.54 | 0.291682E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 59945059.25 | 0.183982E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.113849E+09 | 0.131452E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.181744E+09 | 74358242.08 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.258572E+09 | 31932098.03 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.274594E+09 | 16809768.20 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.254314E+09 | 8129575.50 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.139053E+09 | 51312520.25 |
October | 62833545.17 | 0.00 | 62833545.17 | 63699995.71 | 0.157608E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32950963.79 | 0.224386E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9760504.03 | 0.319675E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141976E+10 | 0.189661E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7533104.25 | 8129575.50 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.274594E+09 | 0.405281E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175327E+09 | 0.703825E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.236216E+09 | 0.513671E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.473922E+09 | 0.329913E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.600421E+09 | 0.242544E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.695892E+09 | 0.144990E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.818710E+09 | 63839938.30 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.841825E+09 | 32083601.92 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.837115E+09 | 15383002.21 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.565230E+09 | 94850306.10 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.426539E+09 | 0.287616E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.271504E+09 | 0.407518E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174898E+09 | 0.570114E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.611760E+10 | 0.340635E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174898E+09 | 15383002.21 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.841825E+09 | 0.703825E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.436908E+09 | 0.516457E+09 |
February | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.406245E+09 | 0.383055E+09 |
March | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.467475E+09 | 0.255964E+09 |
April | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.394681E+09 | 0.185063E+09 |
May | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.367425E+09 | 0.102364E+09 |
June | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.409829E+09 | 43029232.60 |
July | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.454444E+09 | 19794759.46 |
August | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.541430E+09 | 9062449.85 |
September | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.472528E+09 | 67652888.63 |
October | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.556836E+09 | 0.218848E+09 |
November | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.515599E+09 | 0.308399E+09 |
December | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.471624E+09 | 0.422672E+09 |
Annual Sum or Average | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.549502E+10 | 0.253236E+10 |
Minimum of Months | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.367425E+09 | 9062449.85 |
Maximum of Months | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.556836E+09 | 0.516457E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 39545006.16 | 0.304741E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.145946E+09 | 0.223069E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.398254E+09 | 0.144882E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.783853E+09 | 0.103113E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.124684E+10 | 0.633254E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.172072E+10 | 0.336355E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.180064E+10 | 0.223935E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.164739E+10 | 0.167903E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.930542E+09 | 0.494168E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.423610E+09 | 0.127152E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.196676E+09 | 0.176438E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 43170438.56 | 0.247932E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.937718E+10 | 0.151289E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 39545006.16 | 0.167903E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.180064E+10 | 0.304741E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 35118759.58 | 0.312855E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.134509E+09 | 0.230292E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.366699E+09 | 0.151651E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.744256E+09 | 0.107801E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.120164E+10 | 0.665269E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.168156E+10 | 0.355083E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.176344E+10 | 0.240118E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.161180E+10 | 0.183400E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.894008E+09 | 0.527058E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.394373E+09 | 0.133671E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.175113E+09 | 0.183848E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 36287010.75 | 0.256660E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.903880E+10 | 0.157387E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 35118759.58 | 0.183400E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.176344E+10 | 0.312855E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 6852890.45 | 0.427184E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 24227177.61 | 0.311317E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 69373665.58 | 0.197311E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.137008E+09 | 0.137863E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.217331E+09 | 84631425.77 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.292897E+09 | 45731987.55 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.310756E+09 | 29338346.15 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.288020E+09 | 21233124.15 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.167368E+09 | 61264157.81 |
October | 62833545.17 | 0.00 | 62833545.17 | 76270856.19 | 0.169653E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 36202478.10 | 0.240014E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 7964919.32 | 0.344204E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.163427E+10 | 0.206974E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 6852890.45 | 21233124.15 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.310756E+09 | 0.427184E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434507E+09 | 0.197839E+09 | 0.236668E+09 | 0.290287E+09 | 0.143592E+10 |
February | 0.492555E+09 | 0.265149E+09 | 0.227406E+09 | 0.483631E+09 | 0.104317E+10 |
March | 0.686097E+09 | 0.312962E+09 | 0.373136E+09 | 0.856561E+09 | 0.673171E+09 |
April | 0.802608E+09 | 0.366340E+09 | 0.436268E+09 | 0.125586E+10 | 0.484733E+09 |
May | 0.908547E+09 | 0.384217E+09 | 0.524331E+09 | 0.161385E+10 | 0.312629E+09 |
June | 0.909412E+09 | 0.380907E+09 | 0.528506E+09 | 0.184937E+10 | 0.170509E+09 |
July | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.194568E+10 | 0.110624E+09 |
August | 0.839504E+09 | 0.333007E+09 | 0.506497E+09 | 0.182889E+10 | 80088422.83 |
September | 0.665833E+09 | 0.294206E+09 | 0.371628E+09 | 0.126655E+10 | 0.224562E+09 |
October | 0.588469E+09 | 0.306304E+09 | 0.282165E+09 | 0.865218E+09 | 0.590730E+09 |
November | 0.453550E+09 | 0.204592E+09 | 0.248958E+09 | 0.493616E+09 | 0.806568E+09 |
December | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.296151E+09 | 0.114807E+10 |
Annual Sum or Average | 0.810373E+10 | 0.361493E+10 | 0.448879E+10 | 0.130457E+11 | 0.708077E+10 |
Minimum of Months | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.290287E+09 | 80088422.83 |
Maximum of Months | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.194568E+10 | 0.143592E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.318914E+09 | 0.348268E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.295316E+09 | 0.263809E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.343698E+09 | 0.184560E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.294076E+09 | 0.138650E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.278227E+09 | 87729905.07 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.302244E+09 | 47770250.52 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.332501E+09 | 29749724.94 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.392766E+09 | 21263717.44 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.350447E+09 | 60490733.87 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.407772E+09 | 0.158793E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.378298E+09 | 0.211735E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.343979E+09 | 0.287801E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.403824E+10 | 0.184062E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.278227E+09 | 21263717.44 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.407772E+09 | 0.348268E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8043796.19 | 0.524225E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 29093934.74 | 0.372962E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 81332804.57 | 0.223424E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.156054E+09 | 0.154259E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.243917E+09 | 88749610.69 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.325476E+09 | 46574308.14 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.335707E+09 | 29645989.00 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.305412E+09 | 20310145.18 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.180619E+09 | 66294986.39 |
October | 79574720.39 | 0.00 | 79574720.39 | 85004357.10 | 0.192913E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 40443917.69 | 0.283520E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 9163952.72 | 0.415470E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.180027E+10 | 0.241835E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8043796.19 | 20310145.18 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.335707E+09 | 0.524225E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59587394.23 | 0.00 | 59587394.23 | 7196814.93 | 0.469017E+09 |
February | 59655211.68 | 0.00 | 59655211.68 | 26030453.64 | 0.333691E+09 |
March | 92748761.43 | 1867.91 | 92746893.52 | 72768768.42 | 0.199898E+09 |
April | 0.108831E+09 | 635619.29 | 0.108195E+09 | 0.139623E+09 | 0.138016E+09 |
May | 0.134178E+09 | 4208294.36 | 0.129970E+09 | 0.218234E+09 | 79404612.95 |
June | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.291205E+09 | 41670209.96 |
July | 0.139761E+09 | 7161532.19 | 0.132599E+09 | 0.300358E+09 | 26524378.68 |
August | 0.124134E+09 | 1458327.18 | 0.122675E+09 | 0.273253E+09 | 18171563.85 |
September | 90679085.44 | 35646.33 | 90643439.12 | 0.161600E+09 | 59314375.51 |
October | 71195803.84 | 0.00 | 71195803.84 | 76053720.38 | 0.172600E+09 |
November | 61662207.79 | 0.00 | 61662207.79 | 36185326.40 | 0.253664E+09 |
December | 55084111.20 | 0.00 | 55084111.20 | 8199023.22 | 0.371707E+09 |
Annual Sum or Average | 0.114033E+10 | 22866870.75 | 0.111746E+10 | 0.161071E+10 | 0.216368E+10 |
Minimum of Months | 55084111.20 | 0.00 | 55084111.20 | 7196814.93 | 18171563.85 |
Maximum of Months | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.300358E+09 | 0.469017E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104240E+10 | 0.724128E+09 | 0.318275E+09 | 0.116496E+10 | 0.125481E+10 |
February | 0.877042E+09 | 0.585111E+09 | 0.291931E+09 | 0.108014E+10 | 0.928884E+09 |
March | 0.887931E+09 | 0.465944E+09 | 0.421987E+09 | 0.124463E+10 | 0.614815E+09 |
April | 0.646677E+09 | 0.215752E+09 | 0.430925E+09 | 0.103727E+10 | 0.460241E+09 |
May | 0.537152E+09 | 65733982.34 | 0.471418E+09 | 0.942640E+09 | 0.278140E+09 |
June | 0.477300E+09 | 26647349.68 | 0.450653E+09 | 0.992065E+09 | 0.148191E+09 |
July | 0.494749E+09 | 33371514.17 | 0.461378E+09 | 0.107304E+10 | 91380725.52 |
August | 0.596149E+09 | 0.112040E+09 | 0.484109E+09 | 0.128845E+10 | 61312706.21 |
September | 0.651339E+09 | 0.253428E+09 | 0.397911E+09 | 0.120230E+10 | 0.195148E+09 |
October | 0.945089E+09 | 0.610848E+09 | 0.334241E+09 | 0.146439E+10 | 0.531805E+09 |
November | 0.999244E+09 | 0.666797E+09 | 0.332447E+09 | 0.137051E+10 | 0.734293E+09 |
December | 0.103506E+10 | 0.728130E+09 | 0.306934E+09 | 0.125585E+10 | 0.102013E+10 |
Annual Sum or Average | 0.919014E+10 | 0.448793E+10 | 0.470221E+10 | 0.141163E+11 | 0.631916E+10 |
Minimum of Months | 0.477300E+09 | 26647349.68 | 0.291931E+09 | 0.942640E+09 | 61312706.21 |
Maximum of Months | 0.104240E+10 | 0.728130E+09 | 0.484109E+09 | 0.146439E+10 | 0.125481E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 607.11 | 578.61 | 527.26 | 366.27 | 160.99 | 0.00 | 0.00 |
February | 618.37 | 476.64 | 491.15 | 327.66 | 163.48 | 0.00 | 0.00 |
March | 637.19 | 295.51 | 449.12 | 235.68 | 213.44 | 0.00 | 0.00 |
April | 546.24 | 227.51 | 338.00 | 112.77 | 225.23 | 0.00 | 0.00 |
May | 481.94 | 130.17 | 271.69 | 33.25 | 238.45 | 0.00 | 0.00 |
June | 518.87 | 71.28 | 249.47 | 13.93 | 235.54 | 0.00 | 0.00 |
July | 540.93 | 41.43 | 250.25 | 16.88 | 233.37 | 0.00 | 0.00 |
August | 641.64 | 31.85 | 301.54 | 56.67 | 244.87 | 0.00 | 0.00 |
September | 621.62 | 100.84 | 340.43 | 132.46 | 207.97 | 0.00 | 0.00 |
October | 735.78 | 260.76 | 478.03 | 308.97 | 169.06 | 0.00 | 0.00 |
November | 717.92 | 364.70 | 522.27 | 348.52 | 173.76 | 0.00 | 0.00 |
December | 648.74 | 476.45 | 523.54 | 368.30 | 155.25 | 0.00 | 0.00 |
Annual Sum or Average | 609.72 | 253.52 | 394.80 | 192.80 | 202.00 | 0.00 | 0.00 |
Minimum of Months | 481.94 | 31.85 | 249.47 | 13.93 | 155.25 | 0.00 | 0.00 |
Maximum of Months | 735.78 | 578.61 | 527.26 | 368.30 | 244.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1690.45 | 1661.00 | 1484.72 | 1031.40 | 453.32 | 0.00 | 0.00 |
February | 1722.10 | 1386.65 | 1383.03 | 922.68 | 460.35 | 0.00 | 0.00 |
March | 1771.92 | 890.86 | 1264.70 | 663.66 | 601.04 | 0.00 | 0.00 |
April | 1517.28 | 694.27 | 951.78 | 317.55 | 634.23 | 0.00 | 0.00 |
May | 1334.03 | 421.30 | 765.07 | 93.63 | 671.45 | 0.00 | 0.00 |
June | 1443.85 | 242.91 | 702.49 | 39.22 | 663.27 | 0.00 | 0.00 |
July | 1512.85 | 151.08 | 704.68 | 47.53 | 657.15 | 0.00 | 0.00 |
August | 1802.26 | 121.41 | 849.11 | 159.58 | 689.52 | 0.00 | 0.00 |
September | 1731.06 | 338.07 | 958.64 | 373.00 | 585.64 | 0.00 | 0.00 |
October | 2051.76 | 798.00 | 1346.11 | 870.05 | 476.06 | 0.00 | 0.00 |
November | 2000.67 | 1082.90 | 1470.69 | 981.40 | 489.29 | 0.00 | 0.00 |
December | 1806.43 | 1382.88 | 1474.27 | 1037.10 | 437.17 | 0.00 | 0.00 |
Annual Sum or Average | 1698.81 | 761.08 | 1111.73 | 542.91 | 568.82 | 0.00 | 0.00 |
Minimum of Months | 1334.03 | 121.41 | 702.49 | 39.22 | 437.17 | 0.00 | 0.00 |
Maximum of Months | 2051.76 | 1661.00 | 1484.72 | 1037.10 | 689.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2237.78 | 2227.80 | 1928.74 | 1339.84 | 588.89 | 0.00 | 0.00 |
February | 2288.63 | 1851.54 | 1796.64 | 1198.62 | 598.02 | 0.00 | 0.00 |
March | 2368.69 | 1172.68 | 1642.92 | 862.13 | 780.79 | 0.00 | 0.00 |
April | 2031.60 | 917.37 | 1236.41 | 412.51 | 823.90 | 0.00 | 0.00 |
May | 1787.67 | 552.04 | 993.87 | 121.63 | 872.25 | 0.00 | 0.00 |
June | 1934.29 | 313.71 | 912.57 | 50.95 | 861.62 | 0.00 | 0.00 |
July | 2030.39 | 191.46 | 915.42 | 61.75 | 853.67 | 0.00 | 0.00 |
August | 2425.00 | 145.25 | 1103.04 | 207.31 | 895.73 | 0.00 | 0.00 |
September | 2317.06 | 435.51 | 1245.33 | 484.54 | 760.78 | 0.00 | 0.00 |
October | 2744.61 | 1046.13 | 1748.68 | 1130.24 | 618.43 | 0.00 | 0.00 |
November | 2665.99 | 1435.61 | 1910.51 | 1274.89 | 635.62 | 0.00 | 0.00 |
December | 2398.79 | 1848.73 | 1915.16 | 1347.25 | 567.91 | 0.00 | 0.00 |
Annual Sum or Average | 2269.40 | 1007.17 | 1444.20 | 705.27 | 738.93 | 0.00 | 0.00 |
Minimum of Months | 1787.67 | 145.25 | 912.57 | 50.95 | 567.91 | 0.00 | 0.00 |
Maximum of Months | 2744.61 | 2227.80 | 1928.74 | 1347.25 | 895.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.65 | 374.41 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 200.03 | 305.58 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 295.28 | 184.41 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 339.56 | 138.11 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 359.86 | 76.72 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 428.65 | 35.58 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 434.02 | 16.73 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 453.19 | 8.36 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 345.91 | 52.84 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 300.70 | 158.99 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 232.66 | 231.29 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 170.70 | 305.88 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 310.63 | 156.66 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 159.65 | 8.36 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 453.19 | 374.41 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.96 | 406.57 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 102.36 | 328.37 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 200.12 | 190.45 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 279.53 | 142.10 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 333.08 | 80.17 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 419.81 | 36.62 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 420.77 | 18.37 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 411.43 | 9.31 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 275.10 | 56.79 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 184.28 | 165.63 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 116.07 | 244.00 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 64.26 | 330.33 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 239.65 | 166.59 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 59.96 | 9.31 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 420.77 | 406.57 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 89.59 | 106.89 | 83.38 | 57.92 | 25.46 | 0.00 | 0.00 |
February | 87.51 | 100.97 | 77.67 | 51.82 | 25.85 | 0.00 | 0.00 |
March | 83.86 | 79.12 | 71.03 | 37.27 | 33.75 | 0.00 | 0.00 |
April | 69.86 | 64.62 | 53.45 | 17.83 | 35.62 | 0.00 | 0.00 |
May | 59.22 | 43.61 | 42.97 | 5.26 | 37.71 | 0.00 | 0.00 |
June | 66.58 | 27.44 | 39.45 | 2.20 | 37.25 | 0.00 | 0.00 |
July | 71.41 | 20.19 | 39.57 | 2.67 | 36.91 | 0.00 | 0.00 |
August | 88.90 | 17.46 | 47.69 | 8.96 | 38.72 | 0.00 | 0.00 |
September | 84.38 | 36.87 | 53.84 | 20.95 | 32.89 | 0.00 | 0.00 |
October | 102.26 | 71.78 | 75.60 | 48.86 | 26.74 | 0.00 | 0.00 |
November | 98.18 | 93.01 | 82.59 | 55.11 | 27.48 | 0.00 | 0.00 |
December | 89.43 | 108.66 | 82.79 | 58.24 | 24.55 | 0.00 | 0.00 |
Annual Sum or Average | 82.59 | 64.01 | 62.43 | 30.49 | 31.95 | 0.00 | 0.00 |
Minimum of Months | 59.22 | 17.46 | 39.45 | 2.20 | 24.55 | 0.00 | 0.00 |
Maximum of Months | 102.26 | 108.66 | 83.38 | 58.24 | 38.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.96 | 127.22 | 15.71 | 0.00 | 15.71 | 0.00 | 0.00 |
February | 7.72 | 101.02 | 17.41 | 0.00 | 17.41 | 0.00 | 0.00 |
March | 19.00 | 55.60 | 24.45 | 0.00 | 24.45 | 0.00 | 0.00 |
April | 37.84 | 39.76 | 29.65 | 0.17 | 29.48 | 0.00 | 0.00 |
May | 58.18 | 21.08 | 35.37 | 1.11 | 34.27 | 0.00 | 0.00 |
June | 84.61 | 8.87 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
July | 87.14 | 4.33 | 36.85 | 1.89 | 34.96 | 0.00 | 0.00 |
August | 81.51 | 1.88 | 32.73 | 0.38 | 32.34 | 0.00 | 0.00 |
September | 46.05 | 15.26 | 24.70 | 0.01 | 24.69 | 0.00 | 0.00 |
October | 20.16 | 47.89 | 18.77 | 0.00 | 18.77 | 0.00 | 0.00 |
November | 9.92 | 72.42 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
December | 2.30 | 101.29 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Annual Sum or Average | 38.21 | 49.47 | 25.53 | 0.51 | 25.02 | 0.00 | 0.00 |
Minimum of Months | 1.96 | 1.88 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Maximum of Months | 87.14 | 127.22 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 151.41 | 368.90 | 185.37 | 109.35 | 76.01 | 0.00 | 0.00 |
February | 203.43 | 298.51 | 198.92 | 119.59 | 79.33 | 0.00 | 0.00 |
March | 266.17 | 175.34 | 216.89 | 105.03 | 111.86 | 0.00 | 0.00 |
April | 324.63 | 128.22 | 221.66 | 92.97 | 128.69 | 0.00 | 0.00 |
May | 371.04 | 70.90 | 223.34 | 78.30 | 145.03 | 0.00 | 0.00 |
June | 440.22 | 32.34 | 224.76 | 76.24 | 148.53 | 0.00 | 0.00 |
July | 456.33 | 16.06 | 220.48 | 75.08 | 145.40 | 0.00 | 0.00 |
August | 458.22 | 7.86 | 216.35 | 73.37 | 142.97 | 0.00 | 0.00 |
September | 348.43 | 50.46 | 195.76 | 82.95 | 112.81 | 0.00 | 0.00 |
October | 289.74 | 152.40 | 204.38 | 118.27 | 86.10 | 0.00 | 0.00 |
November | 222.44 | 223.25 | 190.76 | 108.38 | 82.38 | 0.00 | 0.00 |
December | 167.77 | 298.84 | 179.44 | 107.38 | 72.06 | 0.00 | 0.00 |
Annual Sum or Average | 308.90 | 151.19 | 206.55 | 95.44 | 111.11 | 0.00 | 0.00 |
Minimum of Months | 151.41 | 7.86 | 179.44 | 73.37 | 72.06 | 0.00 | 0.00 |
Maximum of Months | 458.22 | 368.90 | 224.76 | 119.59 | 148.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.61 | 393.64 | 100.75 | 36.93 | 63.82 | 0.00 | 0.00 |
February | 95.32 | 310.14 | 123.57 | 54.80 | 68.77 | 0.00 | 0.00 |
March | 167.50 | 175.71 | 158.65 | 58.43 | 100.22 | 0.00 | 0.00 |
April | 264.79 | 131.13 | 191.89 | 70.89 | 121.00 | 0.00 | 0.00 |
May | 344.95 | 75.26 | 213.83 | 73.12 | 140.71 | 0.00 | 0.00 |
June | 430.80 | 34.60 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
July | 441.48 | 18.15 | 217.05 | 74.10 | 142.95 | 0.00 | 0.00 |
August | 415.29 | 8.78 | 197.63 | 62.65 | 134.98 | 0.00 | 0.00 |
September | 276.03 | 53.83 | 159.32 | 56.77 | 102.56 | 0.00 | 0.00 |
October | 169.07 | 153.59 | 133.32 | 57.18 | 76.14 | 0.00 | 0.00 |
November | 95.86 | 224.12 | 108.49 | 39.47 | 69.02 | 0.00 | 0.00 |
December | 47.86 | 309.32 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 233.55 | 156.61 | 160.41 | 57.96 | 102.45 | 0.00 | 0.00 |
Minimum of Months | 44.61 | 8.78 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 441.48 | 393.64 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.46 | 444.95 | 214.70 | 125.50 | 89.19 | 0.00 | 0.00 |
February | 208.12 | 360.92 | 206.01 | 112.27 | 93.74 | 0.00 | 0.00 |
March | 262.38 | 211.69 | 206.86 | 80.76 | 126.11 | 0.00 | 0.00 |
April | 278.20 | 158.51 | 180.04 | 39.01 | 141.03 | 0.00 | 0.00 |
May | 301.03 | 86.84 | 169.73 | 13.80 | 155.93 | 0.00 | 0.00 |
June | 366.66 | 43.94 | 169.76 | 10.30 | 159.46 | 0.00 | 0.00 |
July | 377.87 | 25.09 | 165.57 | 9.87 | 155.70 | 0.00 | 0.00 |
August | 401.20 | 14.94 | 174.22 | 20.25 | 153.97 | 0.00 | 0.00 |
September | 321.15 | 66.29 | 170.17 | 45.41 | 124.76 | 0.00 | 0.00 |
October | 302.06 | 182.39 | 204.46 | 105.87 | 98.59 | 0.00 | 0.00 |
November | 262.54 | 264.55 | 215.35 | 119.42 | 95.93 | 0.00 | 0.00 |
December | 204.17 | 358.79 | 210.85 | 126.20 | 84.66 | 0.00 | 0.00 |
Annual Sum or Average | 289.03 | 184.03 | 190.59 | 67.17 | 123.42 | 0.00 | 0.00 |
Minimum of Months | 177.46 | 14.94 | 165.57 | 9.87 | 84.66 | 0.00 | 0.00 |
Maximum of Months | 401.20 | 444.95 | 215.35 | 126.20 | 159.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.22 | 373.30 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 198.46 | 304.23 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 291.18 | 183.38 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 334.34 | 137.75 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 354.24 | 76.51 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 423.85 | 34.75 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 429.85 | 16.04 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 448.98 | 7.74 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 342.01 | 51.86 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 297.11 | 157.78 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 230.83 | 229.75 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 170.13 | 303.95 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 307.29 | 155.67 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 159.22 | 7.74 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 448.98 | 373.30 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 60.12 | 405.94 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 101.73 | 327.17 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 197.17 | 189.72 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 274.40 | 143.12 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 327.04 | 81.27 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 414.88 | 36.22 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 416.52 | 17.95 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 407.43 | 8.72 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 271.58 | 56.26 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 181.77 | 164.96 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 115.68 | 242.01 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 64.92 | 328.19 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 236.85 | 165.99 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 60.12 | 8.72 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 416.52 | 405.94 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.12 | 192.82 | 152.89 | 106.21 | 46.68 | 0.00 | 0.00 |
February | 167.93 | 158.34 | 142.42 | 95.01 | 47.41 | 0.00 | 0.00 |
March | 174.54 | 95.57 | 130.23 | 68.34 | 61.89 | 0.00 | 0.00 |
April | 152.27 | 71.40 | 98.01 | 32.70 | 65.31 | 0.00 | 0.00 |
May | 137.18 | 38.22 | 78.78 | 9.64 | 69.14 | 0.00 | 0.00 |
June | 158.11 | 16.60 | 72.34 | 4.04 | 68.30 | 0.00 | 0.00 |
July | 169.67 | 7.39 | 72.57 | 4.89 | 67.67 | 0.00 | 0.00 |
August | 202.15 | 3.38 | 87.44 | 16.43 | 71.00 | 0.00 | 0.00 |
September | 182.30 | 26.10 | 98.72 | 38.41 | 60.31 | 0.00 | 0.00 |
October | 207.90 | 81.71 | 138.62 | 89.59 | 49.02 | 0.00 | 0.00 |
November | 198.92 | 118.98 | 151.44 | 101.06 | 50.39 | 0.00 | 0.00 |
December | 176.08 | 157.81 | 151.81 | 106.80 | 45.02 | 0.00 | 0.00 |
Annual Sum or Average | 174.25 | 80.30 | 114.48 | 55.91 | 58.58 | 0.00 | 0.00 |
Minimum of Months | 137.18 | 3.38 | 72.34 | 4.04 | 45.02 | 0.00 | 0.00 |
Maximum of Months | 207.90 | 192.82 | 152.89 | 106.80 | 71.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.76 | 1137.77 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 60.33 | 922.08 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 148.69 | 540.93 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 302.41 | 397.81 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 465.52 | 236.43 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 663.86 | 129.77 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 672.28 | 83.61 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 615.06 | 62.69 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 359.01 | 190.65 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 158.16 | 474.73 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 75.88 | 680.70 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 16.12 | 925.67 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 297.35 | 479.73 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 14.76 | 62.69 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 672.28 | 1137.77 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.11 | 1168.07 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 55.60 | 951.93 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 136.91 | 566.20 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 287.14 | 415.90 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 448.64 | 248.38 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 648.75 | 136.99 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 658.39 | 89.65 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 601.78 | 68.47 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 344.91 | 203.34 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 147.24 | 499.07 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 67.56 | 709.29 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 13.55 | 958.26 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 286.62 | 499.07 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 13.11 | 68.47 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 658.39 | 1168.07 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.93 | 777.55 | 286.11 | 146.28 | 139.83 | 0.00 | 0.00 |
February | 301.20 | 638.14 | 322.47 | 174.39 | 148.09 | 0.00 | 0.00 |
March | 465.15 | 385.03 | 375.52 | 163.44 | 212.08 | 0.00 | 0.00 |
April | 644.73 | 287.60 | 413.53 | 163.85 | 249.68 | 0.00 | 0.00 |
May | 785.61 | 179.13 | 437.14 | 151.41 | 285.73 | 0.00 | 0.00 |
June | 942.17 | 100.93 | 448.80 | 152.90 | 295.91 | 0.00 | 0.00 |
July | 966.45 | 63.21 | 437.50 | 149.17 | 288.33 | 0.00 | 0.00 |
August | 936.97 | 45.74 | 413.96 | 136.02 | 277.94 | 0.00 | 0.00 |
September | 687.61 | 132.81 | 355.07 | 139.71 | 215.36 | 0.00 | 0.00 |
October | 497.95 | 337.37 | 337.68 | 175.45 | 162.23 | 0.00 | 0.00 |
November | 338.20 | 473.30 | 299.24 | 147.84 | 151.40 | 0.00 | 0.00 |
December | 212.10 | 634.74 | 273.51 | 141.94 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 581.50 | 336.47 | 366.94 | 153.39 | 213.55 | 0.00 | 0.00 |
Minimum of Months | 181.93 | 45.74 | 273.51 | 136.02 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 966.45 | 777.55 | 448.80 | 175.45 | 295.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.76 | 790.45 | 436.30 | 270.36 | 165.94 | 0.00 | 0.00 |
February | 437.75 | 644.54 | 414.75 | 241.86 | 172.89 | 0.00 | 0.00 |
March | 516.71 | 382.08 | 404.85 | 173.96 | 230.88 | 0.00 | 0.00 |
April | 513.62 | 289.69 | 338.41 | 83.76 | 254.65 | 0.00 | 0.00 |
May | 523.17 | 165.31 | 306.64 | 27.87 | 278.77 | 0.00 | 0.00 |
June | 618.95 | 89.51 | 300.82 | 17.93 | 282.89 | 0.00 | 0.00 |
July | 637.29 | 54.27 | 295.22 | 18.12 | 277.10 | 0.00 | 0.00 |
August | 696.90 | 37.06 | 320.72 | 42.98 | 277.74 | 0.00 | 0.00 |
September | 595.77 | 123.64 | 325.37 | 97.80 | 227.57 | 0.00 | 0.00 |
October | 601.64 | 329.79 | 409.15 | 228.06 | 181.08 | 0.00 | 0.00 |
November | 542.06 | 474.29 | 435.89 | 257.25 | 178.64 | 0.00 | 0.00 |
December | 440.87 | 640.28 | 430.00 | 271.85 | 158.15 | 0.00 | 0.00 |
Annual Sum or Average | 543.64 | 333.53 | 367.99 | 143.85 | 224.15 | 0.00 | 0.00 |
Minimum of Months | 391.76 | 37.06 | 295.22 | 17.93 | 158.15 | 0.00 | 0.00 |
Maximum of Months | 696.90 | 790.45 | 436.30 | 271.85 | 282.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162609E+10 | 0.154975E+10 | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.00 | 0.00 |
February | 0.149596E+10 | 0.115308E+10 | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.00 | 0.00 |
March | 0.170666E+10 | 0.791488E+09 | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.00 | 0.00 |
April | 0.141585E+10 | 0.589700E+09 | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.00 | 0.00 |
May | 0.129082E+10 | 0.348659E+09 | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.00 | 0.00 |
June | 0.134491E+10 | 0.184752E+09 | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.00 | 0.00 |
July | 0.144883E+10 | 0.110969E+09 | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.00 | 0.00 |
August | 0.171857E+10 | 85318332.75 | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.00 | 0.00 |
September | 0.161123E+10 | 0.261368E+09 | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.00 | 0.00 |
October | 0.197072E+10 | 0.698416E+09 | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.00 | 0.00 |
November | 0.186086E+10 | 0.945302E+09 | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.00 | 0.00 |
December | 0.173759E+10 | 0.127612E+10 | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192281E+11 | 0.799493E+10 | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129082E+10 | 85318332.75 | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197072E+10 | 0.154975E+10 | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452770E+10 | 0.444882E+10 | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.00 | 0.00 |
February | 0.416611E+10 | 0.335458E+10 | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.00 | 0.00 |
March | 0.474590E+10 | 0.238609E+10 | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.00 | 0.00 |
April | 0.393280E+10 | 0.179956E+10 | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.00 | 0.00 |
May | 0.357307E+10 | 0.112840E+10 | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.00 | 0.00 |
June | 0.374247E+10 | 0.629623E+09 | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.00 | 0.00 |
July | 0.405201E+10 | 0.404644E+09 | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.00 | 0.00 |
August | 0.482718E+10 | 0.325182E+09 | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.00 | 0.00 |
September | 0.448690E+10 | 0.876278E+09 | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.00 | 0.00 |
October | 0.549542E+10 | 0.213736E+10 | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.00 | 0.00 |
November | 0.518574E+10 | 0.280687E+10 | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.00 | 0.00 |
December | 0.483835E+10 | 0.370391E+10 | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.535736E+11 | 0.240013E+11 | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.357307E+10 | 0.325182E+09 | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.549542E+10 | 0.444882E+10 | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.599368E+10 | 0.596694E+10 | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.00 | 0.00 |
February | 0.553667E+10 | 0.447924E+10 | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.00 | 0.00 |
March | 0.634431E+10 | 0.314092E+10 | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.00 | 0.00 |
April | 0.526592E+10 | 0.237783E+10 | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.00 | 0.00 |
May | 0.478810E+10 | 0.147857E+10 | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.00 | 0.00 |
June | 0.501368E+10 | 0.813133E+09 | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.00 | 0.00 |
July | 0.543821E+10 | 0.512800E+09 | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.00 | 0.00 |
August | 0.649511E+10 | 0.389042E+09 | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.00 | 0.00 |
September | 0.600583E+10 | 0.112885E+10 | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.00 | 0.00 |
October | 0.735117E+10 | 0.280196E+10 | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.00 | 0.00 |
November | 0.691023E+10 | 0.372110E+10 | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.00 | 0.00 |
December | 0.642493E+10 | 0.495165E+10 | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715678E+11 | 0.317620E+11 | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.478810E+10 | 0.389042E+09 | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.735117E+10 | 0.596694E+10 | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.427608E+09 | 0.100281E+10 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.483922E+09 | 0.739269E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.790874E+09 | 0.493917E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.880127E+09 | 0.357992E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.963840E+09 | 0.205489E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.111106E+10 | 92218006.29 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.116248E+10 | 44822924.70 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.121381E+10 | 22391358.35 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.896611E+09 | 0.136951E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.805404E+09 | 0.425836E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.603051E+09 | 0.599505E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.457197E+09 | 0.819272E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.979599E+10 | 0.494047E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.427608E+09 | 22391358.35 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121381E+10 | 0.100281E+10 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160600E+09 | 0.108896E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.247619E+09 | 0.794392E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.536006E+09 | 0.510096E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.724544E+09 | 0.368320E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.892109E+09 | 0.214717E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.108815E+10 | 94909305.33 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.112700E+10 | 49205562.04 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.110196E+10 | 24928177.28 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.713064E+09 | 0.147203E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.493570E+09 | 0.443635E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.300857E+09 | 0.632446E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.172126E+09 | 0.884756E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.755760E+10 | 0.525356E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160600E+09 | 24928177.28 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112700E+10 | 0.108896E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239945E+09 | 0.286306E+09 | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.00 | 0.00 |
February | 0.211711E+09 | 0.244268E+09 | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.00 | 0.00 |
March | 0.224602E+09 | 0.211903E+09 | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.00 | 0.00 |
April | 0.181078E+09 | 0.167500E+09 | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.00 | 0.00 |
May | 0.158604E+09 | 0.116814E+09 | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.00 | 0.00 |
June | 0.172584E+09 | 71120341.80 | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.00 | 0.00 |
July | 0.191254E+09 | 54085144.04 | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.00 | 0.00 |
August | 0.238107E+09 | 46773098.41 | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.00 | 0.00 |
September | 0.218707E+09 | 95565548.94 | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.00 | 0.00 |
October | 0.273903E+09 | 0.192252E+09 | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.00 | 0.00 |
November | 0.254474E+09 | 0.241081E+09 | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.00 | 0.00 |
December | 0.239540E+09 | 0.291048E+09 | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.260451E+10 | 0.201872E+10 | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.00 | 0.00 |
Minimum of Months | 0.158604E+09 | 46773098.41 | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.00 | 0.00 |
Maximum of Months | 0.273903E+09 | 0.291048E+09 | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5241694.06 | 0.340754E+09 | 42076451.99 | 0.00 | 42076451.99 | 0.00 | 0.00 |
February | 18679986.82 | 0.244389E+09 | 42124339.93 | 0.00 | 42124339.93 | 0.00 | 0.00 |
March | 50882212.91 | 0.148921E+09 | 65492691.15 | 1318.99 | 65491372.16 | 0.00 | 0.00 |
April | 98071653.47 | 0.103065E+09 | 76848851.72 | 448829.91 | 76400021.81 | 0.00 | 0.00 |
May | 0.155824E+09 | 56460572.96 | 94747450.04 | 2971603.27 | 91775846.77 | 0.00 | 0.00 |
June | 0.219314E+09 | 22990660.81 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
July | 0.233400E+09 | 11596054.22 | 98689421.90 | 5056973.36 | 93632448.53 | 0.00 | 0.00 |
August | 0.218304E+09 | 5027099.84 | 87654522.95 | 1029768.70 | 86624754.24 | 0.00 | 0.00 |
September | 0.119356E+09 | 39552171.77 | 64031230.67 | 25170.94 | 64006059.72 | 0.00 | 0.00 |
October | 53999475.59 | 0.128265E+09 | 50273499.29 | 0.00 | 50273499.29 | 0.00 | 0.00 |
November | 25724266.09 | 0.187717E+09 | 43541540.27 | 0.00 | 43541540.27 | 0.00 | 0.00 |
December | 6147260.63 | 0.271306E+09 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.120494E+10 | 0.156004E+10 | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.00 | 0.00 |
Minimum of Months | 5241694.06 | 5027099.84 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Maximum of Months | 0.233400E+09 | 0.340754E+09 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405537E+09 | 0.988071E+09 | 0.496486E+09 | 0.292891E+09 | 0.203596E+09 | 0.00 | 0.00 |
February | 0.492146E+09 | 0.722149E+09 | 0.481219E+09 | 0.289311E+09 | 0.191908E+09 | 0.00 | 0.00 |
March | 0.712900E+09 | 0.469637E+09 | 0.580914E+09 | 0.281299E+09 | 0.299614E+09 | 0.00 | 0.00 |
April | 0.841446E+09 | 0.332358E+09 | 0.574551E+09 | 0.240974E+09 | 0.333577E+09 | 0.00 | 0.00 |
May | 0.993804E+09 | 0.189904E+09 | 0.598187E+09 | 0.209729E+09 | 0.388458E+09 | 0.00 | 0.00 |
June | 0.114105E+10 | 83812873.42 | 0.582588E+09 | 0.197605E+09 | 0.384983E+09 | 0.00 | 0.00 |
July | 0.122224E+10 | 43015718.52 | 0.590525E+09 | 0.201092E+09 | 0.389433E+09 | 0.00 | 0.00 |
August | 0.122729E+10 | 21042263.24 | 0.579466E+09 | 0.196526E+09 | 0.382940E+09 | 0.00 | 0.00 |
September | 0.903134E+09 | 0.130781E+09 | 0.507408E+09 | 0.214997E+09 | 0.292411E+09 | 0.00 | 0.00 |
October | 0.776031E+09 | 0.408201E+09 | 0.547407E+09 | 0.316785E+09 | 0.230622E+09 | 0.00 | 0.00 |
November | 0.576556E+09 | 0.578665E+09 | 0.494448E+09 | 0.280911E+09 | 0.213537E+09 | 0.00 | 0.00 |
December | 0.449351E+09 | 0.800406E+09 | 0.480619E+09 | 0.287609E+09 | 0.193010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.974148E+10 | 0.476804E+10 | 0.651382E+10 | 0.300973E+10 | 0.350409E+10 | 0.00 | 0.00 |
Minimum of Months | 0.405537E+09 | 21042263.24 | 0.480619E+09 | 0.196526E+09 | 0.191908E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122729E+10 | 0.988071E+09 | 0.598187E+09 | 0.316785E+09 | 0.389433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119488E+09 | 0.105433E+10 | 0.269858E+09 | 98926312.94 | 0.170931E+09 | 0.00 | 0.00 |
February | 0.230594E+09 | 0.750297E+09 | 0.298943E+09 | 0.132584E+09 | 0.166359E+09 | 0.00 | 0.00 |
March | 0.448636E+09 | 0.470616E+09 | 0.424928E+09 | 0.156494E+09 | 0.268435E+09 | 0.00 | 0.00 |
April | 0.686344E+09 | 0.339880E+09 | 0.497381E+09 | 0.183744E+09 | 0.313637E+09 | 0.00 | 0.00 |
May | 0.923902E+09 | 0.201569E+09 | 0.572725E+09 | 0.195836E+09 | 0.376889E+09 | 0.00 | 0.00 |
June | 0.111664E+10 | 89679727.80 | 0.580777E+09 | 0.198732E+09 | 0.382045E+09 | 0.00 | 0.00 |
July | 0.118246E+10 | 48624985.11 | 0.581347E+09 | 0.198474E+09 | 0.382873E+09 | 0.00 | 0.00 |
August | 0.111231E+10 | 23507302.61 | 0.529335E+09 | 0.167803E+09 | 0.361533E+09 | 0.00 | 0.00 |
September | 0.715482E+09 | 0.139521E+09 | 0.412969E+09 | 0.147145E+09 | 0.265824E+09 | 0.00 | 0.00 |
October | 0.452834E+09 | 0.411375E+09 | 0.357089E+09 | 0.153163E+09 | 0.203926E+09 | 0.00 | 0.00 |
November | 0.248462E+09 | 0.580906E+09 | 0.281211E+09 | 0.102303E+09 | 0.178908E+09 | 0.00 | 0.00 |
December | 0.128187E+09 | 0.828470E+09 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.736534E+10 | 0.493878E+10 | 0.505854E+10 | 0.182778E+10 | 0.323077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.119488E+09 | 23507302.61 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118246E+10 | 0.105433E+10 | 0.581347E+09 | 0.198732E+09 | 0.382873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475303E+09 | 0.119176E+10 | 0.575045E+09 | 0.336147E+09 | 0.238898E+09 | 0.00 | 0.00 |
February | 0.503491E+09 | 0.873138E+09 | 0.498387E+09 | 0.271614E+09 | 0.226773E+09 | 0.00 | 0.00 |
March | 0.702771E+09 | 0.566995E+09 | 0.554065E+09 | 0.216298E+09 | 0.337767E+09 | 0.00 | 0.00 |
April | 0.721082E+09 | 0.410847E+09 | 0.466674E+09 | 0.101127E+09 | 0.365548E+09 | 0.00 | 0.00 |
May | 0.806268E+09 | 0.232586E+09 | 0.454606E+09 | 36951836.71 | 0.417654E+09 | 0.00 | 0.00 |
June | 0.950371E+09 | 0.113894E+09 | 0.440030E+09 | 26696625.66 | 0.413333E+09 | 0.00 | 0.00 |
July | 0.101208E+10 | 67190563.29 | 0.443462E+09 | 26446478.24 | 0.417015E+09 | 0.00 | 0.00 |
August | 0.107459E+10 | 40009233.85 | 0.466627E+09 | 54240731.23 | 0.412387E+09 | 0.00 | 0.00 |
September | 0.832417E+09 | 0.171834E+09 | 0.441071E+09 | 0.117698E+09 | 0.323373E+09 | 0.00 | 0.00 |
October | 0.809025E+09 | 0.488521E+09 | 0.547629E+09 | 0.283562E+09 | 0.264067E+09 | 0.00 | 0.00 |
November | 0.680504E+09 | 0.685707E+09 | 0.558184E+09 | 0.309534E+09 | 0.248651E+09 | 0.00 | 0.00 |
December | 0.546859E+09 | 0.960974E+09 | 0.564750E+09 | 0.338005E+09 | 0.226745E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.911476E+10 | 0.580346E+10 | 0.601053E+10 | 0.211832E+10 | 0.389221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.475303E+09 | 40009233.85 | 0.440030E+09 | 26446478.24 | 0.226745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107459E+10 | 0.119176E+10 | 0.575045E+09 | 0.338005E+09 | 0.417654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426444E+09 | 0.999838E+09 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.480119E+09 | 0.735995E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.779888E+09 | 0.491167E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.866614E+09 | 0.357053E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.948793E+09 | 0.204919E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.109861E+10 | 90079994.78 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.115130E+10 | 42959230.60 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.120254E+10 | 20735591.95 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.886495E+09 | 0.134415E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.795787E+09 | 0.422591E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.598324E+09 | 0.595502E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.455679E+09 | 0.814107E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.969059E+10 | 0.490936E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.426444E+09 | 20735591.95 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120254E+10 | 0.999838E+09 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161027E+09 | 0.108727E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.246096E+09 | 0.791490E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.528110E+09 | 0.508138E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.711247E+09 | 0.370973E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.875952E+09 | 0.217664E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.107538E+10 | 93870488.14 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.111561E+10 | 48080571.35 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.109126E+10 | 23342427.55 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.703941E+09 | 0.145821E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.486853E+09 | 0.441838E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.299839E+09 | 0.627288E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.173887E+09 | 0.879017E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.746920E+10 | 0.523479E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.161027E+09 | 23342427.55 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111561E+10 | 0.108727E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.436908E+09 | 0.516457E+09 | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.00 | 0.00 |
February | 0.406245E+09 | 0.383055E+09 | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.00 | 0.00 |
March | 0.467475E+09 | 0.255964E+09 | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.00 | 0.00 |
April | 0.394681E+09 | 0.185063E+09 | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.00 | 0.00 |
May | 0.367425E+09 | 0.102364E+09 | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.00 | 0.00 |
June | 0.409829E+09 | 43029232.60 | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.00 | 0.00 |
July | 0.454444E+09 | 19794759.46 | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.00 | 0.00 |
August | 0.541430E+09 | 9062449.85 | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.00 | 0.00 |
September | 0.472528E+09 | 67652888.63 | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.00 | 0.00 |
October | 0.556836E+09 | 0.218848E+09 | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.00 | 0.00 |
November | 0.515599E+09 | 0.308399E+09 | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.00 | 0.00 |
December | 0.471624E+09 | 0.422672E+09 | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.549502E+10 | 0.253236E+10 | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.367425E+09 | 9062449.85 | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.556836E+09 | 0.516457E+09 | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39545006.16 | 0.304741E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.145946E+09 | 0.223069E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.398254E+09 | 0.144882E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.783853E+09 | 0.103113E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.124684E+10 | 0.633254E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.172072E+10 | 0.336355E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.180064E+10 | 0.223935E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.164739E+10 | 0.167903E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.930542E+09 | 0.494168E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.423610E+09 | 0.127152E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.196676E+09 | 0.176438E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 43170438.56 | 0.247932E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.937718E+10 | 0.151289E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 39545006.16 | 0.167903E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180064E+10 | 0.304741E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 35118759.58 | 0.312855E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.134509E+09 | 0.230292E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.366699E+09 | 0.151651E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.744256E+09 | 0.107801E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.120164E+10 | 0.665269E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.168156E+10 | 0.355083E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.176344E+10 | 0.240118E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.161180E+10 | 0.183400E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.894008E+09 | 0.527058E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.394373E+09 | 0.133671E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.175113E+09 | 0.183848E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 36287010.75 | 0.256660E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.903880E+10 | 0.157387E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 35118759.58 | 0.183400E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176344E+10 | 0.312855E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.487272E+09 | 0.208259E+10 | 0.766313E+09 | 0.391803E+09 | 0.374510E+09 | 0.00 | 0.00 |
February | 0.728660E+09 | 0.154378E+10 | 0.780127E+09 | 0.421877E+09 | 0.358251E+09 | 0.00 | 0.00 |
March | 0.124587E+10 | 0.103127E+10 | 0.100579E+10 | 0.437771E+09 | 0.568023E+09 | 0.00 | 0.00 |
April | 0.167115E+10 | 0.745447E+09 | 0.107188E+10 | 0.424692E+09 | 0.647183E+09 | 0.00 | 0.00 |
May | 0.210419E+10 | 0.479773E+09 | 0.117085E+10 | 0.405538E+09 | 0.765309E+09 | 0.00 | 0.00 |
June | 0.244212E+10 | 0.261619E+09 | 0.116330E+10 | 0.396310E+09 | 0.766990E+09 | 0.00 | 0.00 |
July | 0.258853E+10 | 0.169308E+09 | 0.117181E+10 | 0.399539E+09 | 0.772269E+09 | 0.00 | 0.00 |
August | 0.250959E+10 | 0.122497E+09 | 0.110874E+10 | 0.364305E+09 | 0.744437E+09 | 0.00 | 0.00 |
September | 0.178229E+10 | 0.344240E+09 | 0.920329E+09 | 0.362120E+09 | 0.558209E+09 | 0.00 | 0.00 |
October | 0.133370E+10 | 0.903618E+09 | 0.904454E+09 | 0.469926E+09 | 0.434528E+09 | 0.00 | 0.00 |
November | 0.876602E+09 | 0.122680E+10 | 0.775627E+09 | 0.383200E+09 | 0.392427E+09 | 0.00 | 0.00 |
December | 0.568102E+09 | 0.170008E+10 | 0.732571E+09 | 0.380168E+09 | 0.352403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183381E+11 | 0.106110E+11 | 0.115718E+11 | 0.483725E+10 | 0.673454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.487272E+09 | 0.122497E+09 | 0.732571E+09 | 0.362120E+09 | 0.352403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.258853E+10 | 0.208259E+10 | 0.117181E+10 | 0.469926E+09 | 0.772269E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104929E+10 | 0.211715E+10 | 0.116859E+10 | 0.724128E+09 | 0.444462E+09 | 0.00 | 0.00 |
February | 0.105900E+10 | 0.155927E+10 | 0.100337E+10 | 0.585111E+09 | 0.418262E+09 | 0.00 | 0.00 |
March | 0.138396E+10 | 0.102337E+10 | 0.108434E+10 | 0.465948E+09 | 0.618396E+09 | 0.00 | 0.00 |
April | 0.133132E+10 | 0.750884E+09 | 0.877147E+09 | 0.217098E+09 | 0.660049E+09 | 0.00 | 0.00 |
May | 0.140125E+10 | 0.442756E+09 | 0.821300E+09 | 74645838.28 | 0.746654E+09 | 0.00 | 0.00 |
June | 0.160431E+10 | 0.231997E+09 | 0.779732E+09 | 46480736.68 | 0.733252E+09 | 0.00 | 0.00 |
July | 0.170692E+10 | 0.145368E+09 | 0.790720E+09 | 48537407.44 | 0.742182E+09 | 0.00 | 0.00 |
August | 0.186658E+10 | 99265121.47 | 0.859026E+09 | 0.115128E+09 | 0.743898E+09 | 0.00 | 0.00 |
September | 0.154424E+10 | 0.320471E+09 | 0.843369E+09 | 0.253504E+09 | 0.589865E+09 | 0.00 | 0.00 |
October | 0.161144E+10 | 0.883303E+09 | 0.109586E+10 | 0.610848E+09 | 0.485011E+09 | 0.00 | 0.00 |
November | 0.140502E+10 | 0.122935E+10 | 0.112983E+10 | 0.666797E+09 | 0.463028E+09 | 0.00 | 0.00 |
December | 0.118083E+10 | 0.171493E+10 | 0.115171E+10 | 0.728130E+09 | 0.423585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171442E+11 | 0.105181E+11 | 0.116050E+11 | 0.453636E+10 | 0.706864E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104929E+10 | 99265121.47 | 0.779732E+09 | 46480736.68 | 0.418262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186658E+10 | 0.211715E+10 | 0.116859E+10 | 0.728130E+09 | 0.746654E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770631E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163525401.2 | 81.21 | 0.00 | 0.00 |
February | 0.696354E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147581344.2 | 81.21 | 0.00 | 0.00 |
March | 0.770459E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163143419.3 | 81.21 | 0.00 | 0.00 |
April | 0.746629E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157710614.3 | 81.21 | 0.00 | 0.00 |
May | 0.770557E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162780864.8 | 81.21 | 0.00 | 0.00 |
June | 0.745787E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157338584.2 | 81.21 | 0.00 | 0.00 |
July | 0.771338E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162518172.6 | 81.21 | 0.00 | 0.00 |
August | 0.770529E+10 | -0.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162472052.2 | 81.21 | 0.00 | 0.00 |
September | 0.746738E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157447090.1 | 81.21 | 0.00 | 0.00 |
October | 0.770446E+10 | -0.754142E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163037477.8 | 81.21 | 0.00 | 0.00 |
November | 0.745043E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158001184.5 | 81.21 | 0.00 | 0.00 |
December | 0.771426E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163417906.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907593E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191897E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696354E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163525401.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771426E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147581344.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116112E+12 | -0.114306E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180551E+10 | 81.26 | 0.00 | 0.00 |
February | 0.105019E+12 | -0.103383E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163591E+10 | 81.26 | 0.00 | 0.00 |
March | 0.113691E+12 | -0.111877E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181407E+10 | 81.26 | 0.00 | 0.00 |
April | 0.105410E+12 | -0.103652E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175811E+10 | 81.26 | 0.00 | 0.00 |
May | 0.103261E+12 | -0.101448E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181370E+10 | 81.25 | 0.00 | 0.00 |
June | 0.950574E+11 | -0.933103E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174709E+10 | 81.25 | 0.00 | 0.00 |
July | 0.951785E+11 | -0.933873E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179118E+10 | 81.25 | 0.00 | 0.00 |
August | 0.949467E+11 | -0.931722E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177443E+10 | 81.25 | 0.00 | 0.00 |
September | 0.944501E+11 | -0.927476E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170253E+10 | 81.24 | 0.00 | 0.00 |
October | 0.102414E+12 | -0.100657E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175621E+10 | 81.24 | 0.00 | 0.00 |
November | 0.104589E+12 | -0.102890E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169957E+10 | 81.25 | 0.00 | 0.00 |
December | 0.113079E+12 | -0.111304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177474E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.124321E+13 | -0.122213E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210731E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.944501E+11 | -0.114306E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181407E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.116112E+12 | -0.927476E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163591E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.676702E+11 | -0.660983E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157187E+10 | 58.98 | 0.00 | 0.00 |
February | 0.612595E+11 | -0.598326E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142691E+10 | 58.98 | 0.00 | 0.00 |
March | 0.656517E+11 | -0.640678E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158383E+10 | 58.98 | 0.00 | 0.00 |
April | 0.595269E+11 | -0.579905E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153647E+10 | 58.98 | 0.00 | 0.00 |
May | 0.566346E+11 | -0.550510E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158357E+10 | 58.98 | 0.00 | 0.00 |
June | 0.506157E+11 | -0.490943E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152139E+10 | 58.98 | 0.00 | 0.00 |
July | 0.496183E+11 | -0.480658E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155247E+10 | 58.98 | 0.00 | 0.00 |
August | 0.494585E+11 | -0.479294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152916E+10 | 58.98 | 0.00 | 0.00 |
September | 0.500460E+11 | -0.485862E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145975E+10 | 58.98 | 0.00 | 0.00 |
October | 0.558420E+11 | -0.543379E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150415E+10 | 58.98 | 0.00 | 0.00 |
November | 0.587651E+11 | -0.573095E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145553E+10 | 58.98 | 0.00 | 0.00 |
December | 0.650419E+11 | -0.635126E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152926E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.690130E+12 | -0.671876E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182544E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.494585E+11 | -0.660983E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158383E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.676702E+11 | -0.479294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142691E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:30 | 5291.40 | 34.04 | 271.33 | 275.83 | 815.87 | 25.51 | 167.33 | 246.50 |
February | 263.00 | 0.88 | 0.86 | 01-FEB-13:39 | 4693.55 | 30.88 | 192.00 | 250.50 | 574.83 | 21.91 | 111.17 | 205.33 |
March | 351.67 | 0.88 | 0.86 | 01-MAR-09:09 | 1162.57 | 19.56 | 11.17 | 322.50 | 447.11 | 20.97 | 162.33 | 257.83 |
April | 369.33 | 0.88 | 0.86 | 01-APR-10:09 | 929.75 | 19.06 | 0.00 | 329.17 | 368.40 | 20.80 | 152.83 | 251.33 |
May | 407.00 | 0.88 | 0.86 | 01-MAY-07:00 | 880.72 | 19.02 | 0.00 | 363.00 | 349.28 | 20.75 | 190.50 | 279.17 |
June | 411.67 | 0.88 | 0.86 | 01-JUN-07:40 | 813.01 | 18.79 | 0.00 | 364.33 | 327.03 | 20.53 | 175.17 | 263.33 |
July | 411.00 | 0.88 | 0.86 | 01-JUL-08:39 | 860.31 | 18.88 | 0.00 | 369.00 | 343.09 | 20.61 | 208.67 | 277.83 |
August | 390.50 | 0.88 | 0.86 | 01-AUG-08:20 | 1065.38 | 19.54 | 0.83 | 355.17 | 416.56 | 21.25 | 236.33 | 289.83 |
September | 298.50 | 0.88 | 0.86 | 01-SEP-08:09 | 1120.56 | 19.48 | 0.17 | 312.67 | 442.39 | 21.21 | 176.83 | 239.67 |
October | 293.50 | 0.88 | 0.86 | 01-OCT-10:39 | 2703.03 | 24.73 | 106.17 | 294.50 | 457.32 | 21.05 | 108.67 | 222.50 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-09:09 | 5262.95 | 34.79 | 286.00 | 275.67 | 661.27 | 25.18 | 182.17 | 246.00 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4951.97 | 34.55 | 270.50 | 271.83 | 914.41 | 26.67 | 174.83 | 236.67 |
Annual Sum or Average | 4071.00 | 0.88 | 2235.57 | 23.61 | 1138.17 | 3784.17 | 488.05 | 21.99 | 2046.83 | 3016.00 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 813.01 | 18.79 | 0.00 | 250.50 | 327.03 | 20.53 | 108.67 | 205.33 | |
Maximum of Months | 411.67 | 0.88 | 0.86 | 5291.40 | 34.79 | 286.00 | 369.00 | 914.41 | 26.67 | 236.33 | 289.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.25 | 0.22 | 01-JAN-08:00 | 5610.83 | 34.17 | 273.00 | 283.33 | 1134.61 | 25.42 | 177.00 | 265.50 |
February | 263.00 | 0.28 | 0.22 | 01-FEB-10:30 | 4997.31 | 30.97 | 193.17 | 261.17 | 877.96 | 21.97 | 111.50 | 226.17 |
March | 351.67 | 0.27 | 0.22 | 01-MAR-08:39 | 1409.85 | 19.99 | 34.33 | 334.00 | 693.58 | 21.25 | 180.50 | 301.33 |
April | 369.33 | 0.28 | 0.22 | 01-APR-08:20 | 1112.00 | 19.73 | 14.00 | 344.83 | 550.07 | 21.25 | 191.67 | 306.67 |
May | 407.00 | 0.28 | 0.22 | 01-MAY-07:30 | 1027.85 | 19.84 | 16.83 | 384.00 | 495.86 | 21.34 | 258.00 | 335.00 |
June | 411.67 | 0.28 | 0.22 | 01-JUN-06:00 | 947.65 | 19.65 | 13.17 | 383.33 | 461.17 | 21.17 | 242.33 | 336.33 |
July | 411.00 | 0.28 | 0.22 | 01-JUL-07:10 | 999.10 | 19.73 | 22.33 | 387.00 | 481.35 | 21.23 | 258.17 | 338.50 |
August | 390.50 | 0.27 | 0.22 | 01-AUG-07:10 | 1236.39 | 20.27 | 57.67 | 369.83 | 586.92 | 21.77 | 278.67 | 333.00 |
September | 298.50 | 0.28 | 0.22 | 01-SEP-07:30 | 1332.47 | 20.05 | 36.17 | 325.67 | 653.62 | 21.58 | 199.00 | 291.83 |
October | 293.50 | 0.27 | 0.22 | 01-OCT-08:20 | 3000.10 | 24.84 | 115.67 | 307.00 | 751.50 | 21.10 | 119.67 | 268.50 |
November | 299.00 | 0.26 | 0.22 | 01-NOV-08:09 | 5569.13 | 34.88 | 287.17 | 282.50 | 965.39 | 25.14 | 184.17 | 267.00 |
December | 285.17 | 0.25 | 0.22 | 01-DEC-07:49 | 5276.78 | 34.65 | 272.33 | 280.33 | 1236.96 | 26.58 | 181.33 | 259.67 |
Annual Sum or Average | 4071.00 | 0.27 | 2456.83 | 24.11 | 1335.83 | 3943.00 | 708.31 | 22.32 | 2382.00 | 3529.50 | ||
Minimum of Months | 263.00 | 0.25 | 0.22 | 947.65 | 19.65 | 13.17 | 261.17 | 461.17 | 21.10 | 111.50 | 226.17 | |
Maximum of Months | 411.67 | 0.28 | 0.22 | 5610.83 | 34.88 | 287.17 | 387.00 | 1236.96 | 26.58 | 278.67 | 338.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102291E+12 | 146998.67 | 15-JAN-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680071E+11 | 138918.27 | 08-FEB-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511044E+11 | 135350.33 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178734E+11 | 141691.65 | 05-APR-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205195E+10 | 58487.01 | 11-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173079E+09 | 29793.29 | 08-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116558E+09 | 12873.76 | 14-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246456E+11 | 135997.45 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682743E+11 | 148929.98 | 21-NOV-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116653E+12 | 145046.96 | 03-DEC-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116653E+12 | 148929.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423735E+09 | 2727.60 | 01-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252953E+10 | 5069.19 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601572E+10 | 5678.80 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.883954E+10 | 5737.66 | 07-APR-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.572428E+10 | 5681.34 | 14-MAY-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.502840E+09 | 4226.70 | 01-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.883954E+10 | 5737.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354025E+10 | 2525.86 | 09-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251211E+10 | 2524.80 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136893E+10 | 1857.07 | 22-MAR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.876968E+09 | 1880.02 | 06-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.390276E+09 | 1154.07 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 60672788.33 | 726.52 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39576622.95 | 601.78 | 29-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197244E+09 | 1025.69 | 29-SEP-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.972559E+09 | 1716.76 | 31-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159231E+10 | 2323.77 | 21-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270589E+10 | 2460.65 | 01-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354025E+10 | 2525.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.922213E+09 | 1054.02 | 08-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583530E+09 | 908.16 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199121E+09 | 666.91 | 23-MAR-10:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77607578.69 | 526.30 | 06-APR-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10017012.47 | 193.83 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5256210.39 | 173.99 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87264231.57 | 616.18 | 30-OCT-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208350E+09 | 637.52 | 22-NOV-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567104E+09 | 784.28 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.922213E+09 | 1054.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257190E+10 | 1581.08 | 08-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174161E+10 | 1580.51 | 13-FEB-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860943E+09 | 944.93 | 19-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327623E+09 | 832.37 | 06-APR-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26247107.76 | 298.63 | 11-MAY-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 556722.03 | 62.42 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.316463E+09 | 760.95 | 26-OCT-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.901981E+09 | 1135.99 | 22-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181273E+10 | 1318.05 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257190E+10 | 1581.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180313E+10 | 983.83 | 08-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125552E+10 | 983.35 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688336E+09 | 662.21 | 19-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291856E+09 | 581.73 | 06-APR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38328980.80 | 255.29 | 11-MAY-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3462482.52 | 140.81 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303622E+09 | 550.58 | 26-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.735545E+09 | 756.15 | 22-NOV-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133826E+10 | 873.06 | 18-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180313E+10 | 983.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.578245E+10 | 7779.83 | 18-JAN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.469877E+10 | 7780.17 | 08-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.431415E+10 | 7553.42 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358777E+10 | 7310.31 | 06-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324155E+10 | 6695.95 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256673E+10 | 6301.96 | 10-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242732E+10 | 6504.50 | 29-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236587E+10 | 5866.64 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293581E+10 | 6695.96 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394165E+10 | 7311.92 | 30-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437551E+10 | 7778.83 | 22-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523453E+10 | 7779.08 | 26-DEC-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.236587E+10 | 5866.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.578245E+10 | 7780.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.411542E+10 | 7432.00 | 09-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271764E+10 | 6648.05 | 06-FEB-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121334E+10 | 5503.88 | 22-MAR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.688374E+09 | 5072.10 | 06-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290284E+09 | 3268.18 | 11-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33736101.38 | 1897.37 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32328566.73 | 1296.45 | 28-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162089E+09 | 2993.96 | 29-SEP-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.837491E+09 | 5125.74 | 30-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116053E+10 | 5390.12 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260903E+10 | 5807.05 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411542E+10 | 7432.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.975371E+10 | 18693.52 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628879E+10 | 16715.91 | 06-FEB-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217027E+10 | 12168.19 | 22-MAR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102971E+10 | 8772.69 | 06-APR-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189207E+09 | 3671.75 | 11-MAY-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71237875.81 | 3068.27 | 29-SEP-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104945E+10 | 11339.82 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194889E+10 | 11677.75 | 30-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.529007E+10 | 14618.42 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.975371E+10 | 18693.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134741E+11 | 9576.08 | 07-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878529E+10 | 9569.84 | 12-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306742E+10 | 6795.28 | 22-MAR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823415E+09 | 5264.89 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12673280.60 | 1086.57 | 01-MAY-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5142649.22 | 729.65 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184473E+10 | 6608.86 | 30-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478269E+10 | 7565.11 | 22-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.993295E+10 | 8104.78 | 18-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134741E+11 | 9576.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885025E+10 | 5908.66 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.586577E+10 | 5906.72 | 03-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256057E+10 | 4049.30 | 19-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100566E+10 | 3861.80 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92623699.18 | 1517.93 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58216995.82 | 981.66 | 29-SEP-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171149E+10 | 3796.40 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372819E+10 | 4998.51 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669836E+10 | 5524.25 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.885025E+10 | 5908.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.921027E+09 | 4100.78 | 11-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497425E+09 | 3606.23 | 06-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10094796.60 | 769.02 | 22-MAR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3755328.82 | 489.51 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72107284.63 | 2254.62 | 22-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335417E+09 | 3899.84 | 18-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.921027E+09 | 4100.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420176E+09 | 3360.14 | 27-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207276E+09 | 3240.40 | 03-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9338926.24 | 579.62 | 22-NOV-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69846769.72 | 2274.59 | 18-DEC-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420176E+09 | 3360.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.546844E+09 | 3364.65 | 08-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325549E+09 | 3786.12 | 12-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68000105.21 | 1690.27 | 19-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25967590.49 | 1724.94 | 06-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 896999.37 | 353.43 | 11-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 220343.10 | 207.28 | 29-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26098402.48 | 1548.90 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137322E+09 | 2449.51 | 22-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322492E+09 | 2780.33 | 18-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.546844E+09 | 3786.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717425E+09 | 4346.02 | 07-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598556E+09 | 5383.97 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6532.58 | 0.26 | 09-MAR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9358.53 | 0.26 | 07-APR-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10814.38 | 0.26 | 08-MAY-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8958.60 | 0.26 | 24-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8558.84 | 0.26 | 11-JUL-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9141.40 | 0.26 | 11-AUG-03:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12343.68 | 0.26 | 01-SEP-00:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11769.86 | 0.26 | 14-OCT-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36790033.22 | 1146.50 | 22-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124300E+09 | 2124.67 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6532.58 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717425E+09 | 5383.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435280E+10 | 6206.31 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262136E+10 | 6206.64 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662500E+09 | 6116.52 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210813E+09 | 6078.78 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13914116.38 | 4945.84 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6082559.03 | 4330.93 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3917876.92 | 3726.49 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3944804.09 | 4068.03 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18231928.02 | 4504.26 | 28-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.431888E+09 | 6089.48 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117914E+10 | 6191.24 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286025E+10 | 6206.09 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3917876.92 | 3726.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435280E+10 | 6206.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537162E+10 | 6202.36 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326263E+10 | 6202.59 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.846350E+09 | 6118.96 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228279E+09 | 6095.09 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9795619.22 | 4582.05 | 10-MAY-21:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3629509.11 | 4365.71 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1992384.40 | 2713.06 | 28-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1884020.54 | 3371.71 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13259933.70 | 3938.47 | 23-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.546726E+09 | 6144.41 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167271E+10 | 6202.78 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372790E+10 | 6202.64 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1884020.54 | 2713.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537162E+10 | 6202.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37482215.13 | 3158.86 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37482215.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37482215.13 | 3158.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198837E+11 | 36490.77 | 07-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111866E+11 | 36403.70 | 03-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123784E+10 | 34534.10 | 23-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337028E+09 | 34060.69 | 08-APR-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66278302.58 | 30086.26 | 24-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20005431.83 | 26056.27 | 07-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8994257.34 | 19833.15 | 28-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24413706.78 | 18999.09 | 30-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61625651.72 | 30156.05 | 13-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474025E+09 | 33720.42 | 23-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317928E+10 | 35263.46 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103430E+11 | 35695.14 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8994257.34 | 18999.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198837E+11 | 36490.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437408E+10 | 6055.89 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258252E+10 | 6056.44 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.682919E+09 | 5963.35 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216045E+09 | 4254.09 | 30-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13680960.37 | 4168.20 | 10-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72335.25 | 462.39 | 23-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 835177.53 | 2670.13 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 195812.36 | 1148.45 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14162008.43 | 3812.70 | 29-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.447819E+09 | 5942.85 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116705E+10 | 6048.51 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280970E+10 | 6055.60 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 72335.25 | 462.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437408E+10 | 6056.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.540936E+10 | 6053.70 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319872E+10 | 6054.26 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860849E+09 | 5981.43 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240503E+09 | 4440.17 | 24-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9102584.64 | 3461.58 | 15-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 979032.55 | 2653.49 | 01-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 451468.28 | 1659.65 | 28-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 525428.52 | 1277.69 | 30-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10448536.44 | 3572.20 | 29-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.574639E+09 | 5943.54 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163894E+10 | 6054.48 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367662E+10 | 6054.33 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 451468.28 | 1277.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.540936E+10 | 6054.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153307E+10 | 1823.66 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.946059E+09 | 1823.69 | 08-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277179E+09 | 1822.29 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93744609.83 | 1814.47 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7832564.89 | 1227.01 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1525049.57 | 1069.71 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 991114.04 | 980.39 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1058688.82 | 1011.87 | 26-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9624274.97 | 1175.27 | 30-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189128E+09 | 1816.01 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471832E+09 | 1823.56 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105578E+10 | 1823.41 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 991114.04 | 980.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153307E+10 | 1823.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184328E+10 | 1822.36 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114477E+10 | 1825.09 | 01-FEB-21:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333037E+09 | 1822.21 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95043212.58 | 1818.96 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3505356.48 | 1154.63 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 890788.89 | 1150.53 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 305197.94 | 710.78 | 28-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 475076.56 | 1037.38 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6117066.18 | 1219.89 | 28-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227974E+09 | 1822.02 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633654E+09 | 1822.27 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132504E+10 | 1822.26 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 305197.94 | 710.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184328E+10 | 1825.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.431995E+10 | 8606.03 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254106E+10 | 8606.99 | 07-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611927E+09 | 8423.23 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.268184E+09 | 8372.10 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20503760.36 | 5890.65 | 10-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2366131.85 | 3411.10 | 02-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3125299.07 | 2876.37 | 14-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1993525.21 | 2256.46 | 11-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18239141.48 | 3425.96 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345323E+09 | 8369.05 | 30-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868254E+09 | 8536.74 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246614E+10 | 8578.56 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1993525.21 | 2256.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431995E+10 | 8606.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.196983E+11 | 0.145651E+11 | 194257.23 | 19-JAN-22:00 | 99705.45 | 0.08 |
February | 0.00 | 0.00 | 0.584548E+11 | 0.503816E+11 | 178345.62 | 26-FEB-15:20 | 178345.62 | 0.16 |
March | 0.00 | 0.00 | 0.139842E+12 | 0.123506E+12 | 246105.72 | 31-MAR-10:50 | 141808.79 | 0.31 |
April | 0.00 | 0.00 | 0.264659E+12 | 0.210488E+12 | 296626.72 | 21-APR-18:06 | 153873.52 | 0.69 |
May | 0.00 | 0.00 | 0.490993E+12 | 0.322533E+12 | 418866.42 | 30-MAY-21:20 | 185147.67 | 0.92 |
June | 0.00 | 0.00 | 0.689340E+12 | 0.420772E+12 | 464887.70 | 26-JUN-21:00 | 193341.14 | 0.92 |
July | 0.00 | 0.00 | 0.878222E+12 | 0.470266E+12 | 486211.25 | 18-JUL-19:04 | 192827.51 | 1.00 |
August | 0.00 | 0.00 | 0.906158E+12 | 0.489905E+12 | 485166.89 | 23-AUG-23:00 | 173848.96 | 1.00 |
September | 0.00 | 0.00 | 0.633398E+12 | 0.367662E+12 | 478038.58 | 27-SEP-18:15 | 181032.46 | 1.00 |
October | 0.00 | 0.00 | 0.277117E+12 | 0.177396E+12 | 503578.87 | 18-OCT-21:00 | 189521.21 | 0.60 |
November | 0.00 | 0.00 | 0.121628E+12 | 0.896940E+11 | 269527.92 | 27-NOV-19:03 | 141400.48 | 0.28 |
December | 0.00 | 0.00 | 0.359586E+11 | 0.265349E+11 | 221480.03 | 13-DEC-11:40 | 115422.51 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.451547E+13 | 0.276370E+13 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.196983E+11 | 0.145651E+11 | 178345.62 | 99705.45 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.906158E+12 | 0.489905E+12 | 503578.87 | 193341.14 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.698511E+09 | 0.529225E+09 | 13371.86 | 19-JAN-16:05 | 8414.77 | 0.03 |
February | 0.00 | 0.00 | 0.197485E+10 | 0.195141E+10 | 16160.71 | 28-FEB-16:01 | 16160.71 | 0.04 |
March | 0.00 | 0.00 | 0.711480E+10 | 0.650605E+10 | 22806.81 | 28-MAR-15:01 | 16439.19 | 0.20 |
April | 0.00 | 0.00 | 0.142939E+11 | 0.114853E+11 | 29104.22 | 30-APR-15:01 | 15804.81 | 0.46 |
May | 0.00 | 0.00 | 0.301457E+11 | 0.200527E+11 | 39091.41 | 30-MAY-21:50 | 15428.17 | 0.70 |
June | 0.00 | 0.00 | 0.447861E+11 | 0.279633E+11 | 45326.50 | 29-JUN-08:03 | 17336.41 | 0.73 |
July | 0.00 | 0.00 | 0.562039E+11 | 0.315020E+11 | 49419.14 | 26-JUL-08:03 | 16840.26 | 0.79 |
August | 0.00 | 0.00 | 0.576988E+11 | 0.326640E+11 | 47944.72 | 24-AUG-08:61 | 17407.09 | 0.79 |
September | 0.00 | 0.00 | 0.401268E+11 | 0.243980E+11 | 45948.22 | 17-SEP-08:03 | 17077.80 | 0.76 |
October | 0.00 | 0.00 | 0.162046E+11 | 0.100482E+11 | 44490.71 | 18-OCT-21:50 | 16050.94 | 0.36 |
November | 0.00 | 0.00 | 0.573209E+10 | 0.416627E+10 | 27191.70 | 19-NOV-24:00 | 13347.24 | 0.16 |
December | 0.00 | 0.00 | 0.118515E+10 | 0.940863E+09 | 19688.72 | 13-DEC-11:00 | 9728.33 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.276165E+12 | 0.172207E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.698511E+09 | 0.529225E+09 | 13371.86 | 8414.77 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.576988E+11 | 0.326640E+11 | 49419.14 | 17407.09 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 97240493.00 | 88506454.34 | 14983.34 | 29-JAN-16:01 | 14983.34 | 0.01 |
February | 0.00 | 0.00 | 0.532111E+09 | 0.468603E+09 | 14998.65 | 28-FEB-19:01 | 14998.65 | 0.04 |
March | 0.00 | 0.00 | 0.209382E+10 | 0.133500E+10 | 15584.02 | 28-MAR-15:01 | 11800.32 | 0.28 |
April | 0.00 | 0.00 | 0.392967E+10 | 0.207790E+10 | 16317.97 | 02-APR-15:01 | 11228.24 | 0.65 |
May | 0.00 | 0.00 | 0.631703E+10 | 0.306177E+10 | 16398.50 | 27-MAY-08:62 | 10339.71 | 0.85 |
June | 0.00 | 0.00 | 0.904358E+10 | 0.481826E+10 | 17174.84 | 29-JUN-08:61 | 10553.45 | 0.94 |
July | 0.00 | 0.00 | 0.105924E+11 | 0.580553E+10 | 17907.98 | 30-JUL-08:62 | 9955.46 | 0.94 |
August | 0.00 | 0.00 | 0.112332E+11 | 0.617435E+10 | 17143.62 | 29-AUG-08:61 | 10576.38 | 0.96 |
September | 0.00 | 0.00 | 0.708268E+10 | 0.337946E+10 | 17400.66 | 17-SEP-08:61 | 10358.50 | 0.89 |
October | 0.00 | 0.00 | 0.316909E+10 | 0.148631E+10 | 17272.84 | 01-OCT-15:01 | 10459.50 | 0.56 |
November | 0.00 | 0.00 | 0.989275E+09 | 0.568401E+09 | 16527.70 | 04-NOV-15:02 | 10195.27 | 0.21 |
December | 0.00 | 0.00 | 0.249328E+09 | 0.158394E+09 | 15672.08 | 13-DEC-16:02 | 10248.60 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.553295E+11 | 0.294225E+11 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 97240493.00 | 88506454.34 | 14983.34 | 9955.46 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.112332E+11 | 0.617435E+10 | 17907.98 | 14998.65 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6891917.63 | 5036486.39 | 13381.68 | 20-JAN-16:01 | 11543.67 | 0.00 |
February | 0.00 | 0.00 | 91360534.56 | 68856998.16 | 14838.83 | 21-FEB-16:01 | 14838.83 | 0.02 |
March | 0.00 | 0.00 | 0.874211E+09 | 0.463351E+09 | 15560.58 | 28-MAR-15:01 | 11570.83 | 0.16 |
April | 0.00 | 0.00 | 0.244780E+10 | 0.119128E+10 | 16417.74 | 02-APR-15:01 | 10899.44 | 0.47 |
May | 0.00 | 0.00 | 0.493337E+10 | 0.243348E+10 | 16963.91 | 07-MAY-17:42 | 12522.90 | 0.63 |
June | 0.00 | 0.00 | 0.820336E+10 | 0.463022E+10 | 18313.78 | 26-JUN-08:21 | 10630.77 | 0.78 |
July | 0.00 | 0.00 | 0.961217E+10 | 0.556252E+10 | 18322.32 | 23-JUL-08:51 | 10427.17 | 0.79 |
August | 0.00 | 0.00 | 0.100132E+11 | 0.560653E+10 | 19374.22 | 20-AUG-07:52 | 10450.22 | 0.83 |
September | 0.00 | 0.00 | 0.531491E+10 | 0.251318E+10 | 17536.33 | 17-SEP-08:52 | 9711.20 | 0.67 |
October | 0.00 | 0.00 | 0.138609E+10 | 0.552718E+09 | 17335.65 | 18-OCT-21:52 | 9825.21 | 0.31 |
November | 0.00 | 0.00 | 0.178098E+09 | 92005636.34 | 16322.60 | 04-NOV-15:02 | 9913.76 | 0.07 |
December | 0.00 | 0.00 | 25899086.46 | 16998369.45 | 14682.81 | 12-DEC-16:01 | 11178.09 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.430873E+11 | 0.231362E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 6891917.63 | 5036486.39 | 13381.68 | 9711.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100132E+11 | 0.560653E+10 | 19374.22 | 14838.83 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.521047E+09 | 0.371114E+09 | 13097.84 | 29-JAN-13:30 | 13097.84 | 0.01 |
February | 0.00 | 0.00 | 0.486895E+10 | 0.473022E+10 | 29924.46 | 26-FEB-14:50 | 29924.46 | 0.01 |
March | 0.00 | 0.00 | 0.154053E+11 | 0.995497E+10 | 32273.41 | 30-MAR-13:30 | 19408.94 | 0.30 |
April | 0.00 | 0.00 | 0.200111E+11 | 0.852873E+10 | 27471.07 | 15-APR-13:30 | 17143.07 | 0.64 |
May | 0.00 | 0.00 | 0.285591E+11 | 0.979836E+10 | 25466.21 | 30-MAY-17:20 | 12149.43 | 0.89 |
June | 0.00 | 0.00 | 0.397398E+11 | 0.150918E+11 | 29934.09 | 25-JUN-17:20 | 16581.04 | 0.98 |
July | 0.00 | 0.00 | 0.480087E+11 | 0.192138E+11 | 33588.12 | 08-JUL-17:30 | 21057.49 | 0.99 |
August | 0.00 | 0.00 | 0.555631E+11 | 0.242848E+11 | 36675.06 | 19-AUG-15:02 | 23257.40 | 1.00 |
September | 0.00 | 0.00 | 0.403407E+11 | 0.170465E+11 | 40014.46 | 24-SEP-12:30 | 31380.35 | 0.95 |
October | 0.00 | 0.00 | 0.267073E+11 | 0.127605E+11 | 43260.16 | 10-OCT-13:30 | 36258.61 | 0.67 |
November | 0.00 | 0.00 | 0.143118E+11 | 0.107125E+11 | 34278.90 | 06-NOV-13:40 | 24923.15 | 0.23 |
December | 0.00 | 0.00 | 0.544698E+10 | 0.397432E+10 | 33270.36 | 12-DEC-12:30 | 20040.93 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.299484E+12 | 0.136467E+12 | 0.57 | |||
Minimum of Months | 0.00 | 0.00 | 0.521047E+09 | 0.371114E+09 | 13097.84 | 12149.43 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.555631E+11 | 0.242848E+11 | 43260.16 | 36258.61 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.951331E+09 | 0.357034E+09 | 88642.13 | 19-JAN-22:53 | 58961.51 | 0.05 |
February | 0.00 | 0.00 | 0.413075E+10 | 0.247764E+10 | 96257.35 | 18-FEB-09:02 | 73722.72 | 0.13 |
March | 0.00 | 0.00 | 0.131783E+11 | 0.787918E+10 | 95635.22 | 28-MAR-21:52 | 78303.29 | 0.27 |
April | 0.00 | 0.00 | 0.263272E+11 | 0.145035E+11 | 104763.15 | 30-APR-21:52 | 72957.09 | 0.48 |
May | 0.00 | 0.00 | 0.435628E+11 | 0.245998E+11 | 109025.97 | 07-MAY-17:42 | 79141.73 | 0.57 |
June | 0.00 | 0.00 | 0.609160E+11 | 0.367369E+11 | 115678.10 | 26-JUN-08:21 | 67657.72 | 0.72 |
July | 0.00 | 0.00 | 0.691290E+11 | 0.413993E+11 | 117328.31 | 23-JUL-08:51 | 67989.42 | 0.74 |
August | 0.00 | 0.00 | 0.693543E+11 | 0.402744E+11 | 125853.18 | 20-AUG-07:52 | 65866.49 | 0.77 |
September | 0.00 | 0.00 | 0.446244E+11 | 0.241877E+11 | 112785.87 | 17-SEP-08:52 | 65994.73 | 0.61 |
October | 0.00 | 0.00 | 0.200413E+11 | 0.910412E+10 | 115172.44 | 18-OCT-21:52 | 66263.67 | 0.49 |
November | 0.00 | 0.00 | 0.798902E+10 | 0.429453E+10 | 102733.29 | 05-NOV-21:52 | 70771.93 | 0.21 |
December | 0.00 | 0.00 | 0.220602E+10 | 0.983738E+09 | 99482.96 | 13-DEC-21:02 | 70818.13 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.362411E+12 | 0.206798E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.951331E+09 | 0.357034E+09 | 88642.13 | 58961.51 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.693543E+11 | 0.413993E+11 | 125853.18 | 79141.73 | 0.77 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 57427992.23 | 43804429.38 | 13409.27 | 29-JAN-16:01 | 13409.27 | 0.01 |
February | 0.00 | 0.00 | 0.577116E+09 | 0.483570E+09 | 13587.11 | 28-FEB-19:01 | 13587.11 | 0.06 |
March | 0.00 | 0.00 | 0.180879E+10 | 0.104752E+10 | 14030.79 | 28-MAR-15:01 | 10788.03 | 0.31 |
April | 0.00 | 0.00 | 0.379620E+10 | 0.193597E+10 | 14869.90 | 02-APR-15:01 | 10139.80 | 0.68 |
May | 0.00 | 0.00 | 0.652843E+10 | 0.327883E+10 | 14932.28 | 27-MAY-08:62 | 9481.74 | 0.88 |
June | 0.00 | 0.00 | 0.928736E+10 | 0.505515E+10 | 15367.29 | 23-JUN-08:61 | 9759.67 | 0.97 |
July | 0.00 | 0.00 | 0.109706E+11 | 0.613343E+10 | 16218.97 | 30-JUL-08:62 | 9067.33 | 0.96 |
August | 0.00 | 0.00 | 0.113297E+11 | 0.633529E+10 | 15546.46 | 24-AUG-08:61 | 9605.30 | 0.97 |
September | 0.00 | 0.00 | 0.715417E+10 | 0.353727E+10 | 15795.47 | 17-SEP-08:61 | 9400.56 | 0.90 |
October | 0.00 | 0.00 | 0.311622E+10 | 0.143307E+10 | 15857.60 | 01-OCT-15:01 | 9348.30 | 0.59 |
November | 0.00 | 0.00 | 0.876648E+09 | 0.457363E+09 | 14936.01 | 04-NOV-15:02 | 9173.68 | 0.22 |
December | 0.00 | 0.00 | 0.205937E+09 | 0.110372E+09 | 14127.15 | 13-DEC-16:02 | 9390.89 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.557086E+11 | 0.298516E+11 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 57427992.23 | 43804429.38 | 13409.27 | 9067.33 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.113297E+11 | 0.633529E+10 | 16218.97 | 13587.11 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6034065.99 | 4592522.96 | 8900.65 | 31-JAN-16:01 | 7465.28 | 0.00 |
February | 0.00 | 0.00 | 0.163322E+09 | 0.115287E+09 | 13463.84 | 27-FEB-16:01 | 13463.84 | 0.03 |
March | 0.00 | 0.00 | 0.779887E+09 | 0.382450E+09 | 14049.64 | 28-MAR-15:01 | 10595.60 | 0.18 |
April | 0.00 | 0.00 | 0.244487E+10 | 0.117993E+10 | 15003.91 | 02-APR-15:01 | 9854.19 | 0.49 |
May | 0.00 | 0.00 | 0.511951E+10 | 0.262221E+10 | 15732.59 | 30-MAY-08:51 | 12376.86 | 0.66 |
June | 0.00 | 0.00 | 0.832197E+10 | 0.472648E+10 | 17269.02 | 29-JUN-08:51 | 10875.49 | 0.80 |
July | 0.00 | 0.00 | 0.984703E+10 | 0.573965E+10 | 17139.36 | 23-JUL-08:51 | 11401.79 | 0.80 |
August | 0.00 | 0.00 | 0.100590E+11 | 0.567698E+10 | 17678.41 | 20-AUG-07:52 | 9584.44 | 0.84 |
September | 0.00 | 0.00 | 0.534045E+10 | 0.259468E+10 | 16930.72 | 06-SEP-08:31 | 10982.01 | 0.69 |
October | 0.00 | 0.00 | 0.146733E+10 | 0.595916E+09 | 15860.79 | 01-OCT-15:01 | 9162.79 | 0.32 |
November | 0.00 | 0.00 | 0.183826E+09 | 81027017.17 | 14859.30 | 05-NOV-15:02 | 9805.27 | 0.07 |
December | 0.00 | 0.00 | 18657733.07 | 7573470.49 | 13749.66 | 13-DEC-16:02 | 8541.56 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.437519E+11 | 0.237268E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 6034065.99 | 4592522.96 | 8900.65 | 7465.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100590E+11 | 0.573965E+10 | 17678.41 | 13463.84 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17341998.30 | 16131230.27 | 3932.53 | 29-JAN-16:01 | 3932.53 | 0.00 |
February | 0.00 | 0.00 | 0.130442E+09 | 0.115913E+09 | 3936.21 | 21-FEB-16:01 | 3936.21 | 0.04 |
March | 0.00 | 0.00 | 0.540693E+09 | 0.356198E+09 | 4057.82 | 28-MAR-15:01 | 3117.66 | 0.26 |
April | 0.00 | 0.00 | 0.105157E+10 | 0.593120E+09 | 4216.24 | 02-APR-15:01 | 2994.34 | 0.61 |
May | 0.00 | 0.00 | 0.171866E+10 | 0.882984E+09 | 4435.55 | 27-MAY-08:62 | 2531.87 | 0.85 |
June | 0.00 | 0.00 | 0.243142E+10 | 0.134677E+10 | 4672.86 | 29-JUN-08:61 | 2629.64 | 0.94 |
July | 0.00 | 0.00 | 0.283981E+10 | 0.160670E+10 | 4911.65 | 30-JUL-08:62 | 2410.87 | 0.94 |
August | 0.00 | 0.00 | 0.300269E+10 | 0.169666E+10 | 4694.94 | 29-AUG-08:61 | 2610.90 | 0.96 |
September | 0.00 | 0.00 | 0.184562E+10 | 0.914540E+09 | 4767.17 | 17-SEP-08:61 | 2548.35 | 0.86 |
October | 0.00 | 0.00 | 0.821202E+09 | 0.410105E+09 | 4588.06 | 18-OCT-08:62 | 2368.45 | 0.51 |
November | 0.00 | 0.00 | 0.240298E+09 | 0.144382E+09 | 4392.39 | 04-NOV-15:02 | 2648.91 | 0.17 |
December | 0.00 | 0.00 | 52662851.52 | 34146691.82 | 4152.02 | 13-DEC-16:02 | 2665.96 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.146924E+11 | 0.811765E+10 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 17341998.30 | 16131230.27 | 3932.53 | 2368.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.300269E+10 | 0.169666E+10 | 4911.65 | 3936.21 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1480333.11 | 996982.99 | 2908.84 | 20-JAN-16:01 | 2002.84 | 0.00 |
February | 0.00 | 0.00 | 22075188.11 | 16360247.65 | 3890.87 | 21-FEB-16:01 | 3890.87 | 0.01 |
March | 0.00 | 0.00 | 0.225700E+09 | 0.123623E+09 | 4069.83 | 28-MAR-15:01 | 3037.45 | 0.16 |
April | 0.00 | 0.00 | 0.670246E+09 | 0.342953E+09 | 4274.61 | 30-APR-21:52 | 2731.87 | 0.45 |
May | 0.00 | 0.00 | 0.139133E+10 | 0.728801E+09 | 4511.50 | 07-MAY-17:42 | 3370.10 | 0.64 |
June | 0.00 | 0.00 | 0.224870E+10 | 0.132358E+10 | 4984.07 | 26-JUN-08:21 | 2656.67 | 0.79 |
July | 0.00 | 0.00 | 0.262184E+10 | 0.156386E+10 | 4930.96 | 23-JUL-08:51 | 2638.16 | 0.79 |
August | 0.00 | 0.00 | 0.271448E+10 | 0.156431E+10 | 5275.61 | 20-AUG-07:52 | 2548.12 | 0.83 |
September | 0.00 | 0.00 | 0.141933E+10 | 0.695162E+09 | 4762.37 | 17-SEP-08:52 | 2420.20 | 0.67 |
October | 0.00 | 0.00 | 0.364235E+09 | 0.152851E+09 | 4736.61 | 18-OCT-21:52 | 2471.34 | 0.28 |
November | 0.00 | 0.00 | 39439933.86 | 21252255.75 | 4328.97 | 04-NOV-15:02 | 2566.90 | 0.04 |
December | 0.00 | 0.00 | 4092673.27 | 2573042.77 | 3886.05 | 12-DEC-16:01 | 2915.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117230E+11 | 0.653632E+10 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 1480333.11 | 996982.99 | 2908.84 | 2002.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271448E+10 | 0.156431E+10 | 5275.61 | 3890.87 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100692E+10 | 0.897858E+09 | 17906.31 | 10-JAN-16:01 | 17906.31 | 0.05 |
February | 0.00 | 0.00 | 0.183303E+10 | 0.157295E+10 | 18223.01 | 19-FEB-16:02 | 13512.78 | 0.12 |
March | 0.00 | 0.00 | 0.433349E+10 | 0.292248E+10 | 17922.30 | 31-MAR-15:01 | 14707.94 | 0.38 |
April | 0.00 | 0.00 | 0.598464E+10 | 0.327521E+10 | 19371.86 | 21-APR-18:01 | 13642.91 | 0.68 |
May | 0.00 | 0.00 | 0.858415E+10 | 0.423382E+10 | 19764.30 | 27-MAY-08:62 | 12237.44 | 0.86 |
June | 0.00 | 0.00 | 0.116178E+11 | 0.615033E+10 | 22005.98 | 29-JUN-08:61 | 11552.64 | 0.94 |
July | 0.00 | 0.00 | 0.138770E+11 | 0.755179E+10 | 22396.28 | 30-JUL-08:62 | 11232.95 | 0.94 |
August | 0.00 | 0.00 | 0.154652E+11 | 0.894050E+10 | 21776.72 | 29-AUG-08:61 | 11735.97 | 0.95 |
September | 0.00 | 0.00 | 0.110058E+11 | 0.596536E+10 | 21586.36 | 17-SEP-08:61 | 11877.68 | 0.89 |
October | 0.00 | 0.00 | 0.700532E+10 | 0.403728E+10 | 20982.72 | 18-OCT-08:62 | 11210.69 | 0.69 |
November | 0.00 | 0.00 | 0.398212E+10 | 0.267093E+10 | 19808.03 | 04-NOV-15:02 | 12994.34 | 0.39 |
December | 0.00 | 0.00 | 0.203570E+10 | 0.161883E+10 | 18906.77 | 13-DEC-16:02 | 13565.36 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.867311E+11 | 0.498374E+11 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.100692E+10 | 0.897858E+09 | 17906.31 | 11210.69 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.154652E+11 | 0.894050E+10 | 22396.28 | 17906.31 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 75350.63 | 235587.36 | 17-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 55035.04 | 228868.53 | 07-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 29343.86 | 204072.23 | 18-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14214.24 | 185161.07 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 4520.90 | 60672.31 | 11-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1289.07 | 39486.55 | 10-JUN-08:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 932.26 | 43852.65 | 28-JUL-15:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 888.50 | 31481.73 | 30-AUG-21:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1422.72 | 56184.30 | 30-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14441.79 | 162440.33 | 26-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 37841.10 | 188228.68 | 20-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 67465.59 | 230408.51 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 25110.26 | ||||
Minimum of Months | 0.00 | 0.00 | 888.50 | 31481.73 | ||
Maximum of Months | 0.00 | 0.00 | 75350.63 | 235587.36 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9456.25 | 284301.00 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 31564.40 | 351895.05 | 27-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 72052.84 | 422195.42 | 28-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 136222.57 | 444510.15 | 04-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237412.28 | 597449.19 | 30-MAY-21:53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 344803.21 | 662387.16 | 26-JUN-21:53 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 418153.08 | 685567.47 | 25-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 433344.34 | 670648.76 | 20-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 310740.74 | 635694.60 | 09-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 136253.31 | 662998.52 | 18-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62492.33 | 432803.38 | 05-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19069.08 | 358163.90 | 13-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185231.63 | 0.00 | ||||
Minimum of Months | 9456.25 | 284301.00 | 0.00 | 0.00 | ||
Maximum of Months | 433344.34 | 685567.47 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 26247.57 | 53441.07 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26300.97 | 53462.94 | 02-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25490.37 | 52617.92 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23946.96 | 49789.38 | 03-APR-06:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22132.96 | 46356.58 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20523.92 | 42524.20 | 01-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19531.97 | 39666.74 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19480.73 | 39534.39 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20326.38 | 41950.72 | 29-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21867.61 | 45797.70 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23685.48 | 49475.72 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 25284.02 | 52168.81 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 22882.19 | ||||
Minimum of Months | 0.00 | 0.00 | 19480.73 | 39534.39 | ||
Maximum of Months | 0.00 | 0.00 | 26300.97 | 53462.94 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.72 | 1299.30 | 01-JAN-00:03 | 0.91 |
February | 0.244774E+10 | 0.72 | 1299.30 | 01-FEB-00:03 | 0.91 |
March | 0.271000E+10 | 0.72 | 1299.30 | 01-MAR-00:05 | 0.91 |
April | 0.262258E+10 | 0.72 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.262258E+10 | 0.71 | 1299.30 | 01-JUN-00:10 | 0.90 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.271000E+10 | 0.71 | 1299.30 | 01-AUG-00:10 | 0.90 |
September | 0.262258E+10 | 0.71 | 1299.30 | 01-SEP-00:10 | 0.90 |
October | 0.271000E+10 | 0.72 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.262258E+10 | 0.72 | 1299.30 | 01-NOV-00:10 | 0.91 |
December | 0.271000E+10 | 0.72 | 1299.30 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.319080E+11 | 0.72 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.90 | |
Maximum of Months | 0.271000E+10 | 0.72 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.291088E+11 | 0.77 | 13478.59 | 19-JAN-21:00 | 0.86 |
February | 0.265483E+11 | 0.77 | 14025.18 | 28-FEB-21:10 | 0.88 |
March | 0.299381E+11 | 0.78 | 14935.99 | 30-MAR-20:10 | 0.91 |
April | 0.294400E+11 | 0.78 | 16769.60 | 17-APR-18:03 | 0.97 |
May | 0.309741E+11 | 0.79 | 18190.49 | 15-MAY-19:10 | 1.02 |
June | 0.307397E+11 | 0.80 | 16086.96 | 12-JUN-19:40 | 0.95 |
July | 0.320043E+11 | 0.80 | 17338.02 | 07-JUL-20:10 | 0.99 |
August | 0.321199E+11 | 0.80 | 17594.33 | 18-AUG-20:10 | 1.00 |
September | 0.299611E+11 | 0.79 | 16140.33 | 07-SEP-20:20 | 0.95 |
October | 0.300633E+11 | 0.78 | 14768.29 | 18-OCT-20:10 | 0.90 |
November | 0.286761E+11 | 0.77 | 13872.37 | 02-NOV-20:00 | 0.87 |
December | 0.292899E+11 | 0.77 | 13647.50 | 13-DEC-21:00 | 0.86 |
Annual Sum or Average | 0.358864E+12 | 0.78 | |||
Minimum of Months | 0.265483E+11 | 0.77 | 13478.59 | 0.86 | |
Maximum of Months | 0.321199E+11 | 0.80 | 18190.49 | 1.02 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | -0.0 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:03 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321164E+09 | 0.45 | 719.45 | 01-JAN-16:02 | 0.59 |
February | 0.232325E+09 | 0.44 | 719.45 | 01-FEB-09:02 | 0.60 |
March | 0.163519E+09 | 0.46 | 719.45 | 02-MAR-16:01 | 0.59 |
April | 0.198528E+09 | 0.50 | 719.45 | 01-APR-15:02 | 0.59 |
May | 0.265740E+09 | 0.53 | 719.45 | 01-MAY-15:01 | 0.59 |
June | 0.369497E+09 | 0.56 | 719.45 | 01-JUN-08:61 | 0.59 |
July | 0.419285E+09 | 0.56 | 719.45 | 01-JUL-08:61 | 0.59 |
August | 0.441059E+09 | 0.57 | 719.45 | 01-AUG-08:61 | 0.59 |
September | 0.286696E+09 | 0.54 | 719.45 | 01-SEP-08:62 | 0.59 |
October | 0.185523E+09 | 0.48 | 719.45 | 01-OCT-15:01 | 0.59 |
November | 0.153231E+09 | 0.45 | 719.45 | 01-NOV-15:01 | 0.59 |
December | 0.232864E+09 | 0.43 | 719.45 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.326943E+10 | 0.50 | |||
Minimum of Months | 0.153231E+09 | 0.43 | 719.45 | 0.59 | |
Maximum of Months | 0.441059E+09 | 0.57 | 719.45 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394691E+09 | 0.48 | 711.74 | 01-JAN-16:02 | 0.59 |
February | 0.266832E+09 | 0.43 | 711.74 | 01-FEB-09:02 | 0.60 |
March | 0.121545E+09 | 0.35 | 711.74 | 03-MAR-09:02 | 0.59 |
April | 0.133426E+09 | 0.37 | 711.74 | 01-APR-15:02 | 0.59 |
May | 0.207296E+09 | 0.39 | 711.74 | 01-MAY-15:01 | 0.59 |
June | 0.337923E+09 | 0.46 | 711.74 | 01-JUN-08:51 | 0.59 |
July | 0.385772E+09 | 0.47 | 711.74 | 01-JUL-08:31 | 0.59 |
August | 0.395075E+09 | 0.49 | 711.74 | 01-AUG-07:51 | 0.59 |
September | 0.214036E+09 | 0.40 | 711.74 | 01-SEP-08:51 | 0.59 |
October | 0.114535E+09 | 0.35 | 711.74 | 01-OCT-15:01 | 0.59 |
November | 0.148908E+09 | 0.37 | 711.74 | 01-NOV-08:62 | 0.59 |
December | 0.273180E+09 | 0.42 | 711.74 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.299322E+10 | 0.42 | |||
Minimum of Months | 0.114535E+09 | 0.35 | 711.74 | 0.59 | |
Maximum of Months | 0.395075E+09 | 0.49 | 711.74 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 29737725.38 | 0.03 | 486.56 | 29-JAN-13:30 | 0.60 |
February | 0.181515E+09 | 0.10 | 961.85 | 26-FEB-14:50 | 0.60 |
March | 0.577326E+09 | 0.33 | 961.72 | 30-MAR-13:40 | 0.59 |
April | 0.734803E+09 | 0.44 | 898.20 | 15-APR-13:30 | 0.59 |
May | 0.979837E+09 | 0.54 | 789.43 | 19-MAY-19:10 | 0.59 |
June | 0.128833E+10 | 0.58 | 895.82 | 24-JUN-17:20 | 0.59 |
July | 0.149065E+10 | 0.59 | 997.61 | 08-JUL-17:30 | 0.59 |
August | 0.169560E+10 | 0.59 | 1070.20 | 19-AUG-13:50 | 0.59 |
September | 0.129375E+10 | 0.56 | 1207.22 | 24-SEP-12:40 | 0.59 |
October | 0.926097E+09 | 0.42 | 1290.89 | 10-OCT-13:30 | 0.59 |
November | 0.527066E+09 | 0.31 | 1075.99 | 06-NOV-13:50 | 0.59 |
December | 0.206878E+09 | 0.13 | 1006.82 | 10-DEC-14:30 | 0.60 |
Annual Sum or Average | 0.993158E+10 | 0.38 | |||
Minimum of Months | 29737725.38 | 0.03 | 486.56 | 0.59 | |
Maximum of Months | 0.169560E+10 | 0.59 | 1290.89 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162906E+10 | 0.41 | 4574.90 | 01-JAN-09:02 | 0.59 |
February | 0.111596E+10 | 0.38 | 4574.90 | 01-FEB-16:02 | 0.60 |
March | 0.759874E+09 | 0.34 | 4574.90 | 01-MAR-09:02 | 0.60 |
April | 0.114775E+10 | 0.34 | 4574.90 | 01-APR-08:62 | 0.60 |
May | 0.178630E+10 | 0.35 | 4574.90 | 01-MAY-08:53 | 0.59 |
June | 0.257439E+10 | 0.43 | 4574.90 | 01-JUN-08:51 | 0.59 |
July | 0.285253E+10 | 0.44 | 4574.90 | 01-JUL-08:31 | 0.59 |
August | 0.283274E+10 | 0.46 | 4574.90 | 01-AUG-07:51 | 0.59 |
September | 0.176061E+10 | 0.36 | 4574.90 | 01-SEP-08:51 | 0.59 |
October | 0.891195E+09 | 0.33 | 4574.90 | 01-OCT-08:53 | 0.59 |
November | 0.704111E+09 | 0.36 | 4574.90 | 01-NOV-15:01 | 0.59 |
December | 0.104668E+10 | 0.40 | 4574.90 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.191012E+11 | 0.38 | |||
Minimum of Months | 0.704111E+09 | 0.33 | 4574.90 | 0.59 | |
Maximum of Months | 0.285253E+10 | 0.46 | 4574.90 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309189E+09 | 0.44 | 650.94 | 01-JAN-16:02 | 0.59 |
February | 0.224731E+09 | 0.45 | 650.94 | 01-FEB-09:02 | 0.60 |
March | 0.146510E+09 | 0.47 | 650.94 | 02-MAR-16:01 | 0.59 |
April | 0.185697E+09 | 0.51 | 650.94 | 01-APR-15:02 | 0.59 |
May | 0.263996E+09 | 0.55 | 650.94 | 01-MAY-15:01 | 0.59 |
June | 0.374018E+09 | 0.58 | 650.94 | 01-JUN-08:61 | 0.59 |
July | 0.434608E+09 | 0.57 | 650.94 | 01-JUL-08:61 | 0.59 |
August | 0.443204E+09 | 0.58 | 650.94 | 01-AUG-08:61 | 0.59 |
September | 0.282075E+09 | 0.54 | 650.94 | 01-SEP-08:62 | 0.59 |
October | 0.173345E+09 | 0.50 | 650.94 | 01-OCT-15:01 | 0.59 |
November | 0.140208E+09 | 0.45 | 650.94 | 01-NOV-08:62 | 0.59 |
December | 0.211681E+09 | 0.43 | 650.94 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.318926E+10 | 0.51 | |||
Minimum of Months | 0.140208E+09 | 0.43 | 650.94 | 0.59 | |
Maximum of Months | 0.443204E+09 | 0.58 | 650.94 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394400E+09 | 0.47 | 645.38 | 01-JAN-16:02 | 0.59 |
February | 0.250496E+09 | 0.43 | 645.38 | 01-FEB-09:02 | 0.60 |
March | 0.111078E+09 | 0.35 | 645.38 | 02-MAR-16:01 | 0.59 |
April | 0.129302E+09 | 0.39 | 645.38 | 01-APR-15:02 | 0.59 |
May | 0.209364E+09 | 0.41 | 645.38 | 01-MAY-15:01 | 0.59 |
June | 0.342176E+09 | 0.48 | 645.38 | 01-JUN-08:51 | 0.59 |
July | 0.399592E+09 | 0.48 | 645.38 | 01-JUL-08:31 | 0.59 |
August | 0.398580E+09 | 0.50 | 645.38 | 01-AUG-07:51 | 0.59 |
September | 0.209630E+09 | 0.41 | 645.38 | 01-SEP-08:51 | 0.59 |
October | 0.113392E+09 | 0.36 | 645.38 | 01-OCT-15:01 | 0.59 |
November | 0.136992E+09 | 0.36 | 645.38 | 01-NOV-08:62 | 0.59 |
December | 0.256468E+09 | 0.42 | 645.38 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.295147E+10 | 0.42 | |||
Minimum of Months | 0.111078E+09 | 0.35 | 645.38 | 0.59 | |
Maximum of Months | 0.399592E+09 | 0.50 | 645.38 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108634E+09 | 0.46 | 188.93 | 01-JAN-09:02 | 0.59 |
February | 76256762.74 | 0.46 | 188.93 | 01-FEB-09:02 | 0.60 |
March | 48290106.85 | 0.46 | 188.93 | 02-MAR-16:01 | 0.59 |
April | 55918645.97 | 0.50 | 188.93 | 01-APR-15:02 | 0.59 |
May | 73692892.41 | 0.54 | 188.93 | 01-MAY-15:01 | 0.59 |
June | 0.100388E+09 | 0.56 | 188.93 | 01-JUN-08:61 | 0.59 |
July | 0.114906E+09 | 0.56 | 188.93 | 01-JUL-08:61 | 0.59 |
August | 0.120020E+09 | 0.57 | 188.93 | 01-AUG-08:61 | 0.59 |
September | 76174449.01 | 0.54 | 188.93 | 01-SEP-08:62 | 0.59 |
October | 53015826.72 | 0.48 | 188.93 | 01-OCT-15:01 | 0.59 |
November | 47425282.62 | 0.45 | 188.93 | 01-NOV-08:62 | 0.59 |
December | 74202236.38 | 0.45 | 188.93 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.948925E+09 | 0.50 | |||
Minimum of Months | 47425282.62 | 0.45 | 188.93 | 0.59 | |
Maximum of Months | 0.120020E+09 | 0.57 | 188.93 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134663E+09 | 0.51 | 186.72 | 01-JAN-09:02 | 0.59 |
February | 85371541.26 | 0.45 | 186.72 | 01-FEB-09:02 | 0.60 |
March | 37280443.66 | 0.36 | 186.72 | 02-MAR-09:02 | 0.59 |
April | 38770590.28 | 0.38 | 186.72 | 01-APR-15:02 | 0.59 |
May | 59212272.07 | 0.40 | 186.72 | 01-MAY-15:01 | 0.59 |
June | 94011905.37 | 0.47 | 186.72 | 01-JUN-08:51 | 0.59 |
July | 0.108273E+09 | 0.47 | 186.72 | 01-JUL-08:31 | 0.59 |
August | 0.109173E+09 | 0.50 | 186.72 | 01-AUG-07:51 | 0.59 |
September | 58202441.96 | 0.41 | 186.72 | 01-SEP-08:51 | 0.59 |
October | 34919558.96 | 0.36 | 186.72 | 01-OCT-15:01 | 0.59 |
November | 48452706.08 | 0.38 | 186.72 | 01-NOV-08:62 | 0.59 |
December | 88395328.04 | 0.45 | 186.72 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.896727E+09 | 0.43 | |||
Minimum of Months | 34919558.96 | 0.36 | 186.72 | 0.59 | |
Maximum of Months | 0.134663E+09 | 0.51 | 186.72 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342957E+09 | 0.47 | 855.62 | 01-JAN-16:02 | 0.59 |
February | 0.269128E+09 | 0.46 | 855.62 | 01-FEB-09:02 | 0.60 |
March | 0.250393E+09 | 0.49 | 855.62 | 02-MAR-16:01 | 0.59 |
April | 0.282045E+09 | 0.51 | 855.62 | 01-APR-08:62 | 0.59 |
May | 0.346934E+09 | 0.53 | 855.62 | 01-MAY-15:01 | 0.59 |
June | 0.464357E+09 | 0.56 | 855.62 | 01-JUN-08:61 | 0.59 |
July | 0.541912E+09 | 0.56 | 855.62 | 01-JUL-08:61 | 0.59 |
August | 0.607632E+09 | 0.57 | 855.62 | 01-AUG-08:61 | 0.59 |
September | 0.437412E+09 | 0.54 | 855.62 | 01-SEP-08:62 | 0.59 |
October | 0.334115E+09 | 0.51 | 855.62 | 01-OCT-08:62 | 0.59 |
November | 0.249447E+09 | 0.50 | 855.62 | 01-NOV-15:01 | 0.59 |
December | 0.270526E+09 | 0.48 | 855.62 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.439686E+10 | 0.51 | |||
Minimum of Months | 0.249447E+09 | 0.46 | 855.62 | 0.59 | |
Maximum of Months | 0.607632E+09 | 0.57 | 855.62 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.132847E+10 | 0.119562E+10 | 894.19 | 17-JAN-09:02 | 804.77 | 804.77 | 35.49 | 2.30 |
February | 0.876893E+09 | 0.789204E+09 | 884.89 | 07-FEB-09:02 | 796.40 | 796.40 | 35.03 | 2.19 |
March | 0.519842E+09 | 0.467858E+09 | 856.58 | 18-MAR-08:03 | 770.92 | 770.92 | 34.42 | 1.91 |
April | 0.275537E+09 | 0.247983E+09 | 816.20 | 05-APR-22:50 | 734.58 | 734.58 | 37.35 | 1.62 |
May | 0.102517E+09 | 92265549.07 | 392.75 | 11-MAY-05:00 | 353.47 | 353.47 | 30.35 | 0.49 |
June | 25988034.15 | 23389230.74 | 245.73 | 03-JUN-21:56 | 221.16 | 221.16 | 27.37 | 0.28 |
July | 19586464.45 | 17627818.01 | 258.48 | 28-JUL-15:06 | 232.63 | 232.63 | 24.59 | 0.30 |
August | 18973501.90 | 17076151.71 | 229.93 | 30-AUG-21:56 | 206.94 | 206.94 | 30.95 | 0.26 |
September | 30317737.37 | 27285963.63 | 321.67 | 30-SEP-15:05 | 289.51 | 289.51 | 24.78 | 0.38 |
October | 0.268817E+09 | 0.241935E+09 | 830.95 | 26-OCT-06:03 | 747.86 | 747.86 | 40.39 | 1.71 |
November | 0.639869E+09 | 0.575882E+09 | 867.81 | 22-NOV-09:30 | 781.03 | 781.03 | 37.61 | 2.01 |
December | 0.115265E+10 | 0.103739E+10 | 888.72 | 21-DEC-09:02 | 799.84 | 799.84 | 35.35 | 2.24 |
Annual Sum or Average | 0.525946E+10 | 0.473352E+10 | ||||||
Minimum of Months | 18973501.90 | 17076151.71 | 229.93 | 206.94 | 206.94 | 24.59 | 0.26 | |
Maximum of Months | 0.132847E+10 | 0.119562E+10 | 894.19 | 804.77 | 804.77 | 40.39 | 2.30 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11472658.22 | 10325392.40 | 276.22 | 31-JAN-16:01 | 248.60 | 248.60 | 6.72 | 8.73 |
February | 31012381.52 | 27911143.36 | 293.20 | 26-FEB-16:01 | 263.88 | 263.88 | 6.72 | 8.97 |
March | 0.122495E+09 | 0.110245E+09 | 522.84 | 30-MAR-18:03 | 470.56 | 470.56 | 6.72 | 11.66 |
April | 0.291112E+09 | 0.262000E+09 | 679.04 | 13-APR-15:03 | 611.13 | 611.13 | 6.72 | 13.07 |
May | 0.597324E+09 | 0.537592E+09 | 1103.48 | 30-MAY-21:53 | 993.14 | 993.14 | 6.72 | 16.10 |
June | 0.109299E+10 | 0.983692E+09 | 1244.84 | 26-JUN-21:52 | 1120.36 | 1120.36 | 6.72 | 16.94 |
July | 0.150022E+10 | 0.135019E+10 | 1352.74 | 18-JUL-19:00 | 1217.46 | 1217.46 | 6.72 | 17.54 |
August | 0.162185E+10 | 0.145966E+10 | 1282.27 | 20-AUG-21:52 | 1154.04 | 1154.04 | 6.72 | 17.15 |
September | 0.917953E+09 | 0.826158E+09 | 1143.57 | 09-SEP-21:52 | 1029.21 | 1029.21 | 6.72 | 16.35 |
October | 0.336441E+09 | 0.302797E+09 | 1226.37 | 18-OCT-21:52 | 1103.73 | 1103.73 | 6.72 | 16.83 |
November | 91615198.07 | 82453678.26 | 498.31 | 05-NOV-15:02 | 448.48 | 448.48 | 6.72 | 11.41 |
December | 23711550.09 | 21340395.08 | 351.75 | 13-DEC-16:02 | 316.57 | 316.57 | 6.72 | 9.75 |
Annual Sum or Average | 0.663819E+10 | 0.597437E+10 | ||||||
Minimum of Months | 11472658.22 | 10325392.40 | 276.22 | 248.60 | 248.60 | 6.72 | 8.73 | |
Maximum of Months | 0.162185E+10 | 0.145966E+10 | 1352.74 | 1217.46 | 1217.46 | 6.72 | 17.54 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.251575E+10 | 0.226418E+10 | 3312.12 | 01-JAN-01:00 | 2980.91 | 2980.91 | 6.74 | 29.30 |
February | 0.398772E+10 | 0.358895E+10 | 3312.12 | 01-FEB-00:03 | 2980.91 | 2980.91 | 6.76 | 29.30 |
March | 0.750393E+10 | 0.675354E+10 | 3312.12 | 01-MAR-00:05 | 2980.91 | 2980.91 | 7.34 | 29.30 |
April | 0.824551E+10 | 0.742096E+10 | 3312.12 | 01-APR-00:10 | 2980.91 | 2980.91 | 6.82 | 29.30 |
May | 0.885826E+10 | 0.797243E+10 | 3312.12 | 01-MAY-00:10 | 2980.91 | 2980.91 | 8.53 | 29.30 |
June | 0.858501E+10 | 0.772651E+10 | 3312.12 | 01-JUN-00:10 | 2980.91 | 2980.91 | 9.48 | 29.30 |
July | 0.887117E+10 | 0.798406E+10 | 3312.12 | 01-JUL-00:10 | 2980.91 | 2980.91 | 10.53 | 29.30 |
August | 0.887117E+10 | 0.798406E+10 | 3312.12 | 01-AUG-00:10 | 2980.91 | 2980.91 | 9.80 | 29.30 |
September | 0.858501E+10 | 0.772651E+10 | 3312.12 | 01-SEP-00:10 | 2980.91 | 2980.91 | 9.37 | 29.30 |
October | 0.831255E+10 | 0.748130E+10 | 3312.12 | 01-OCT-00:10 | 2980.91 | 2980.91 | 8.10 | 29.30 |
November | 0.646585E+10 | 0.581926E+10 | 3312.12 | 01-NOV-05:03 | 2980.91 | 2980.91 | 6.74 | 29.30 |
December | 0.408924E+10 | 0.368031E+10 | 3312.12 | 01-DEC-09:05 | 2980.91 | 2980.91 | 6.78 | 29.30 |
Annual Sum or Average | 0.848912E+11 | 0.764021E+11 | ||||||
Minimum of Months | 0.251575E+10 | 0.226418E+10 | 3312.12 | 2980.91 | 2980.91 | 6.74 | 29.30 | |
Maximum of Months | 0.887117E+10 | 0.798406E+10 | 3312.12 | 2980.91 | 2980.91 | 10.53 | 29.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 48.29 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.40 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.85 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.28 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.43 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.81 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.52 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.21 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.23 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.73 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.28 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.94 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.29 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.23 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 35.57 | 60.00 | 75350.63 | 235587.36 | 17-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 35.03 | 60.00 | 55035.04 | 228868.53 | 07-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 28.31 | 28.31 | 29343.86 | 204072.23 | 18-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.04 | 60.00 | 14214.24 | 185161.07 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.52 | 60.00 | 4520.90 | 60672.31 | 11-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 34.54 | 60.00 | 1289.07 | 39486.55 | 10-JUN-08:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.72 | 60.00 | 932.26 | 43852.65 | 28-JUL-15:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.43 | 60.00 | 888.50 | 31481.73 | 30-AUG-21:56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.79 | 60.00 | 1422.72 | 56184.30 | 30-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 40.66 | 60.00 | 14441.79 | 162440.33 | 26-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 33.25 | 60.00 | 37841.10 | 188228.68 | 20-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 38.72 | 60.00 | 67465.59 | 230408.51 | 21-DEC-09:02 |
Annual Sum or Average | 0.00 | 25110.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 27.79 | 28.31 | 888.50 | 31481.73 | ||
Maximum of Months | 0.00 | 0.00 | 40.66 | 60.00 | 75350.63 | 235587.36 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9456.25 | 284301.00 | 19-JAN-22:53 | 9.01 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 31564.40 | 351895.05 | 27-FEB-16:03 | 9.57 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 72052.84 | 422195.42 | 28-MAR-18:03 | 10.14 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 136222.57 | 444510.15 | 04-APR-15:03 | 10.32 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237412.28 | 597449.19 | 30-MAY-21:53 | 11.57 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 344803.21 | 662387.16 | 26-JUN-21:53 | 12.10 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 418153.08 | 685567.47 | 25-JUL-21:52 | 12.29 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 433344.34 | 670648.76 | 20-AUG-21:52 | 12.17 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 310740.74 | 635694.60 | 09-SEP-21:52 | 11.88 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 136253.31 | 662998.52 | 18-OCT-21:53 | 12.10 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62492.33 | 432803.38 | 05-NOV-15:03 | 10.23 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19069.08 | 358163.90 | 13-DEC-16:02 | 9.62 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185231.63 | 0.00 | ||||||
Minimum of Months | 9456.25 | 284301.00 | 9.01 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 433344.34 | 685567.47 | 12.29 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48.29 | 59.85 | 26247.57 | 53441.07 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.40 | 59.69 | 26300.97 | 53462.94 | 02-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.85 | 59.75 | 25490.37 | 52617.92 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.28 | 58.69 | 23946.96 | 49789.38 | 03-APR-06:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.43 | 58.29 | 22132.96 | 46356.58 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.81 | 59.69 | 20523.92 | 42524.20 | 01-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.52 | 58.65 | 19531.97 | 39666.74 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.21 | 59.50 | 19480.73 | 39534.39 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.23 | 59.69 | 20326.38 | 41950.72 | 29-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.73 | 58.76 | 21867.61 | 45797.70 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.28 | 59.53 | 23685.48 | 49475.72 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.94 | 59.27 | 25284.02 | 52168.81 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 22882.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.29 | 58.29 | 19480.73 | 39534.39 | ||
Maximum of Months | 0.00 | 0.00 | 54.23 | 59.85 | 26300.97 | 53462.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.155417E+12 | 0.00 | 0.196983E+11 | 0.291088E+11 | 0.00 | 0.00 |
February | 0.106016E+12 | 0.00 | 0.584548E+11 | 0.265483E+11 | 0.00 | 0.00 |
March | 0.736413E+11 | 0.00 | 0.139842E+12 | 0.299381E+11 | 0.00 | 0.00 |
April | 0.354479E+11 | 0.00 | 0.264659E+12 | 0.294400E+11 | 0.00 | 0.00 |
May | 0.120683E+11 | 0.00 | 0.490993E+12 | 0.309741E+11 | 0.00 | 0.00 |
June | 0.333705E+10 | 0.00 | 0.689340E+12 | 0.307397E+11 | 0.00 | 0.00 |
July | 0.249922E+10 | 0.00 | 0.878222E+12 | 0.320043E+11 | 0.00 | 0.00 |
August | 0.236587E+10 | 0.00 | 0.906158E+12 | 0.321199E+11 | 0.00 | 0.00 |
September | 0.355580E+10 | 0.00 | 0.633398E+12 | 0.299611E+11 | 0.00 | 0.00 |
October | 0.357402E+11 | 0.00 | 0.277117E+12 | 0.300633E+11 | 0.00 | 0.00 |
November | 0.879271E+11 | 0.00 | 0.121628E+12 | 0.286761E+11 | 0.00 | 0.00 |
December | 0.153570E+12 | 0.00 | 0.359586E+11 | 0.292899E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.671585E+12 | 0.00 | 0.451547E+13 | 0.358864E+12 | 0.00 | 0.00 |
Minimum of Months | 0.236587E+10 | 0.00 | 0.196983E+11 | 0.265483E+11 | 0.00 | 0.00 |
Maximum of Months | 0.155417E+12 | 0.00 | 0.906158E+12 | 0.321199E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.717425E+09 | 0.00 | 0.698511E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.598556E+09 | 0.00 | 0.197485E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 6532.58 | 0.00 | 0.711480E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 9358.53 | 0.00 | 0.142939E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 10814.38 | 0.00 | 0.301457E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 8958.60 | 0.00 | 0.447861E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 8558.84 | 0.00 | 0.562039E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 9141.40 | 0.00 | 0.576988E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 12343.68 | 0.00 | 0.401268E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 11769.86 | 0.00 | 0.162046E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 36790033.22 | 0.00 | 0.573209E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.124300E+09 | 0.00 | 0.118515E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.147715E+10 | 0.00 | 0.276165E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 6532.58 | 0.00 | 0.698511E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.717425E+09 | 0.00 | 0.576988E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.291088E+11 | 0.196983E+11 | 0.155417E+12 | 0.255012E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265483E+11 | 0.584548E+11 | 0.106016E+12 | 0.141708E+12 | 0.192766E+09 | 0.00 | 0.00 | 0.00 |
March | 0.299381E+11 | 0.139842E+12 | 0.736413E+11 | 0.463071E+10 | 0.318494E+10 | 0.00 | 0.00 | 0.00 |
April | 0.294400E+11 | 0.264659E+12 | 0.354479E+11 | 0.669427E+10 | 0.133344E+11 | 0.00 | 0.00 | 0.00 |
May | 0.309741E+11 | 0.490993E+12 | 0.120683E+11 | 0.00 | 0.544585E+11 | 0.00 | 0.00 | 0.00 |
June | 0.307397E+11 | 0.689340E+12 | 0.333705E+10 | 0.00 | 0.171461E+12 | 0.00 | 0.00 | 0.00 |
July | 0.320043E+11 | 0.878222E+12 | 0.249922E+10 | 0.00 | 0.262515E+12 | 0.00 | 0.00 | 0.00 |
August | 0.321199E+11 | 0.906158E+12 | 0.236587E+10 | 0.00 | 0.336847E+12 | 0.00 | 0.00 | 0.00 |
September | 0.299611E+11 | 0.633398E+12 | 0.355580E+10 | 0.00 | 0.115985E+12 | 0.00 | 0.00 | 0.00 |
October | 0.300633E+11 | 0.277117E+12 | 0.357402E+11 | 0.137509E+10 | 0.247789E+11 | 0.00 | 0.00 | 0.00 |
November | 0.286761E+11 | 0.121628E+12 | 0.879271E+11 | 0.265311E+11 | 0.224245E+10 | 0.00 | 0.00 | 0.00 |
December | 0.292899E+11 | 0.359586E+11 | 0.153570E+12 | 0.870984E+11 | 72174206.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358864E+12 | 0.451547E+13 | 0.671585E+12 | 0.523050E+12 | 0.985073E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265483E+11 | 0.196983E+11 | 0.236587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.321199E+11 | 0.906158E+12 | 0.155417E+12 | 0.255012E+12 | 0.336847E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.698511E+09 | 0.717425E+09 | 0.414898E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.197485E+10 | 0.598556E+09 | 0.260360E+11 | 1701110.41 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.711480E+10 | 6532.58 | 0.119244E+11 | 0.422942E+09 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.142939E+11 | 9358.53 | 0.554193E+10 | 0.898201E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.301457E+11 | 10814.38 | 0.979610E+09 | 0.469892E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.447861E+11 | 8958.60 | 0.278777E+09 | 0.180706E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.562039E+11 | 8558.84 | 0.00 | 0.294008E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.576988E+11 | 9141.40 | 0.00 | 0.379679E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.401268E+11 | 12343.68 | 0.190641E+09 | 0.136204E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.162046E+11 | 11769.86 | 0.735402E+10 | 0.226871E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.573209E+10 | 36790033.22 | 0.167602E+11 | 0.105457E+09 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.118515E+10 | 0.124300E+09 | 0.299301E+11 | 1378023.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.276165E+12 | 0.147715E+10 | 0.140486E+12 | 0.107457E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.698511E+09 | 6532.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.576988E+11 | 0.717425E+09 | 0.414898E+11 | 0.379679E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.291088E+11 | 0.155417E+12 | 0.196983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265483E+11 | 0.106016E+12 | 0.584548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299381E+11 | 0.736413E+11 | 0.139842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.294400E+11 | 0.354479E+11 | 0.264659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309741E+11 | 0.120683E+11 | 0.490993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.307397E+11 | 0.333705E+10 | 0.689340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.320043E+11 | 0.249922E+10 | 0.878222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.321199E+11 | 0.236587E+10 | 0.906158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299611E+11 | 0.355580E+10 | 0.633398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300633E+11 | 0.357402E+11 | 0.277117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286761E+11 | 0.879271E+11 | 0.121628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292899E+11 | 0.153570E+12 | 0.359586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358864E+12 | 0.671585E+12 | 0.451547E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265483E+11 | 0.236587E+10 | 0.196983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.321199E+11 | 0.155417E+12 | 0.906158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.717425E+09 | 0.698511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.598556E+09 | 0.197485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 6532.58 | 0.711480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 9358.53 | 0.142939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 10814.38 | 0.301457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 8958.60 | 0.447861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 8558.84 | 0.562039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 9141.40 | 0.576988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 12343.68 | 0.401268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 11769.86 | 0.162046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 36790033.22 | 0.573209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.124300E+09 | 0.118515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.147715E+10 | 0.276165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 6532.58 | 0.698511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.717425E+09 | 0.576988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606135E+11 | 0.00 | 0.00 | 0.00 | 6504252.50 | 0.00 | 0.00 | 0.00 | 1.00 |
February | 0.481709E+11 | 0.00 | 0.00 | 0.00 | 10816263.71 | 0.00 | 0.00 | 0.00 | 1.00 |
March | 0.441563E+11 | 0.00 | 0.00 | 0.00 | 0.389507E+09 | 20197964.75 | 0.00 | 0.00 | 1.00 |
April | 0.271906E+11 | 0.00 | 0.277635E+09 | 0.00 | 0.169249E+10 | 0.381266E+09 | 0.00 | 2673578.14 | 1.00 |
May | 0.108408E+11 | 0.00 | 24044335.34 | 0.00 | 0.811320E+10 | 0.00 | 0.00 | 68713.81 | 1.00 |
June | 0.457781E+10 | 0.00 | 0.00 | 0.00 | 0.227138E+11 | 0.00 | 0.00 | 0.00 | 0.97 |
July | 74196673.63 | 0.00 | 0.00 | 0.00 | 0.353633E+11 | 0.00 | 0.00 | 0.00 | 0.96 |
August | 11756195.91 | 0.00 | 0.00 | 0.00 | 0.371335E+11 | 0.00 | 0.00 | 0.00 | 0.96 |
September | 0.580280E+10 | 0.121514E+10 | 0.00 | 675813.73 | 0.180311E+11 | 0.00 | 0.789115E+09 | 0.00 | 1.00 |
October | 0.295269E+11 | 0.576347E+09 | 0.00 | 2000558.45 | 0.515596E+10 | 0.00 | 0.430776E+10 | 0.00 | 1.01 |
November | 0.407402E+11 | 45303484.17 | 0.00 | 2501087.22 | 0.753319E+09 | 0.00 | 0.663222E+10 | 0.00 | 1.01 |
December | 0.614514E+11 | 0.00 | 0.00 | 37258.02 | 0.126054E+09 | 0.00 | 0.344446E+09 | 0.00 | 1.00 |
Annual Sum or Average | 0.333157E+12 | 0.183679E+10 | 0.301680E+09 | 5214717.42 | 0.129490E+12 | 0.401464E+09 | 0.120735E+11 | 2742291.96 | 0.99 |
Minimum of Months | 11756195.91 | 0.00 | 0.00 | 0.00 | 6504252.50 | 0.00 | 0.00 | 0.00 | 0.96 |
Maximum of Months | 0.614514E+11 | 0.121514E+10 | 0.277635E+09 | 2501087.22 | 0.371335E+11 | 0.381266E+09 | 0.663222E+10 | 2673578.14 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464115E+10 | 0.00 | 0.00 | 6258.15 | 812186.28 | 0.291356E+10 | 14086929.43 | 0.00 | 2.26 |
February | 0.441616E+10 | 615747.04 | 0.00 | 31417.21 | 734880.25 | 0.157916E+10 | 19757698.04 | 0.00 | 2.27 |
March | 0.523361E+10 | 5311411.12 | 0.00 | 7994.36 | 43326367.82 | 0.276153E+09 | 6555738.30 | 0.00 | 2.27 |
April | 0.335700E+10 | 9220386.63 | 0.00 | 30914.63 | 0.237124E+09 | 84826269.99 | 1056223.61 | 0.00 | 2.28 |
May | 0.135250E+10 | 16773199.65 | 0.00 | 2917.15 | 0.999333E+09 | 0.00 | 1197314.21 | 0.00 | 2.26 |
June | 0.571618E+09 | 0.657232E+09 | 0.00 | 54.08 | 0.217905E+10 | 0.00 | 13201.19 | 0.00 | 2.21 |
July | 9264941.68 | 0.145961E+10 | 0.00 | 0.00 | 0.295782E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
August | 1467996.66 | 0.224304E+10 | 0.00 | 0.00 | 0.241225E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
September | 0.820568E+09 | 0.530159E+09 | 0.00 | 58482.15 | 0.187770E+10 | 0.00 | 2622427.82 | 0.00 | 2.26 |
October | 0.405944E+10 | 0.114444E+09 | 0.00 | 231735.13 | 0.606053E+09 | 66506345.16 | 98999377.27 | 0.00 | 2.28 |
November | 0.545280E+10 | 1956915.17 | 0.00 | 290882.99 | 97767102.80 | 0.342943E+09 | 0.119664E+09 | 0.00 | 2.28 |
December | 0.608564E+10 | 1488090.99 | 0.00 | 35409.65 | 14252214.96 | 0.157282E+10 | 57963102.63 | 0.00 | 2.27 |
Annual Sum or Average | 0.360012E+11 | 0.503986E+10 | 0.00 | 696065.50 | 0.114262E+11 | 0.683596E+10 | 0.321916E+09 | 0.00 | 2.25 |
Minimum of Months | 1467996.66 | 0.00 | 0.00 | 0.00 | 734880.25 | 0.00 | 0.00 | 0.00 | 2.19 |
Maximum of Months | 0.608564E+10 | 0.224304E+10 | 0.00 | 290882.99 | 0.295782E+10 | 0.291356E+10 | 0.119664E+09 | 0.00 | 2.28 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.566266E+10 | 0.00 | 0.00 | 0.00 | 607643.41 | 0.00 | 0.00 | 0.00 | 1.46 |
February | 0.450025E+10 | 0.00 | 0.00 | 0.00 | 1010482.19 | 0.00 | 0.00 | 0.00 | 1.47 |
March | 0.412647E+10 | 0.00 | 0.00 | 2052.32 | 36388728.27 | 0.00 | 614533.70 | 0.00 | 1.47 |
April | 0.253973E+10 | 0.00 | 0.00 | 14345.68 | 0.184304E+09 | 0.00 | 36091264.88 | 0.00 | 1.47 |
May | 0.100166E+10 | 14814555.74 | 0.00 | 24668.48 | 0.745393E+09 | 0.00 | 11097900.06 | 0.00 | 1.46 |
June | 0.401935E+09 | 0.294822E+09 | 0.00 | 21258.13 | 0.182716E+10 | 0.00 | 25714470.32 | 0.00 | 1.43 |
July | 6931637.35 | 0.629853E+09 | 0.00 | 0.00 | 0.267707E+10 | 0.00 | 0.00 | 0.00 | 1.42 |
August | 1098292.99 | 0.911724E+09 | 0.00 | 0.00 | 0.256376E+10 | 0.00 | 0.00 | 0.00 | 1.41 |
September | 0.561500E+09 | 0.194978E+09 | 0.00 | 38417.86 | 0.160328E+10 | 0.00 | 54357681.68 | 0.00 | 1.46 |
October | 0.312557E+10 | 7363145.77 | 0.00 | 14005.08 | 0.528163E+09 | 0.00 | 35522024.51 | 0.00 | 1.47 |
November | 0.442588E+10 | 0.00 | 0.00 | 0.00 | 74609290.78 | 0.00 | 0.00 | 0.00 | 1.47 |
December | 0.577313E+10 | 0.00 | 0.00 | 0.00 | 11776230.92 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | 0.321268E+11 | 0.205355E+10 | 0.00 | 114747.55 | 0.102535E+11 | 0.00 | 0.163398E+09 | 0.00 | 1.45 |
Minimum of Months | 1098292.99 | 0.00 | 0.00 | 0.00 | 607643.41 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.577313E+10 | 0.911724E+09 | 0.00 | 38417.86 | 0.267707E+10 | 0.00 | 54357681.68 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263106E+10 | 0.00 | 0.00 | 0.00 | 524167.52 | 0.225368E+10 | 0.00 | 0.00 | 0.59 |
February | 0.266233E+10 | 0.00 | 0.00 | 0.00 | 871665.75 | 0.121969E+10 | 0.00 | 0.00 | 0.60 |
March | 0.356012E+10 | 0.00 | 0.00 | 0.00 | 31389774.56 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.222197E+10 | 0.00 | 0.00 | 0.00 | 0.158985E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.873646E+09 | 0.00 | 0.00 | 0.00 | 0.655773E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.368918E+09 | 0.00 | 0.00 | 0.00 | 0.183047E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 5979393.73 | 64824285.37 | 0.00 | 0.00 | 0.278505E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 947413.42 | 69441309.97 | 0.00 | 0.00 | 0.292309E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.531287E+09 | 0.00 | 0.00 | 0.00 | 0.155103E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.272684E+10 | 0.00 | 0.00 | 0.00 | 0.461958E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
November | 0.377243E+10 | 0.00 | 0.00 | 0.00 | 64359732.50 | 45438458.68 | 0.00 | 0.00 | 0.60 |
December | 0.449417E+10 | 0.00 | 0.00 | 0.00 | 10158454.31 | 0.485865E+09 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.238497E+11 | 0.134266E+09 | 0.00 | 0.00 | 0.104737E+11 | 0.400468E+10 | 0.00 | 0.00 | 0.59 |
Minimum of Months | 947413.42 | 0.00 | 0.00 | 0.00 | 524167.52 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.449417E+10 | 69441309.97 | 0.00 | 0.00 | 0.292309E+10 | 0.225368E+10 | 0.00 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.894422E+09 | 0.00 | 0.00 | 0.00 | 308344.42 | 0.197906E+10 | 0.00 | 0.00 | 0.61 |
February | 0.121896E+10 | 0.00 | 0.00 | 0.00 | 512762.16 | 0.106466E+10 | 0.00 | 0.00 | 0.61 |
March | 0.204301E+10 | 0.00 | 0.00 | 0.00 | 18465207.03 | 51247693.59 | 0.00 | 0.00 | 0.61 |
April | 0.130709E+10 | 0.00 | 0.00 | 0.00 | 93523832.70 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.513927E+09 | 0.00 | 0.00 | 0.00 | 0.385762E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.217018E+09 | 0.00 | 0.00 | 0.00 | 0.107679E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 3517411.15 | 0.00 | 0.00 | 0.00 | 0.167645E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 557321.14 | 0.00 | 0.00 | 0.00 | 0.176037E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.312532E+09 | 0.00 | 0.00 | 0.00 | 0.912400E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.160408E+10 | 0.00 | 0.00 | 0.00 | 0.271749E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.211208E+10 | 0.00 | 0.00 | 0.00 | 37859965.60 | 0.133800E+09 | 0.00 | 0.00 | 0.61 |
December | 0.209011E+10 | 0.00 | 0.00 | 0.00 | 5975766.46 | 0.839425E+09 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.123173E+11 | 0.00 | 0.00 | 0.00 | 0.624017E+10 | 0.406818E+10 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 557321.14 | 0.00 | 0.00 | 0.00 | 308344.42 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.211208E+10 | 0.00 | 0.00 | 0.00 | 0.176037E+10 | 0.197906E+10 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188826E+10 | 8675456.76 | 0.00 | 72074251.73 | 0.00 | 0.00 | 0.832649E+11 | 0.00 | 21.87 |
February | 0.131892E+10 | 13855137.85 | 0.00 | 67983953.62 | 571735.66 | 0.00 | 0.666067E+11 | 0.00 | 22.03 |
March | 0.548467E+09 | 0.518579E+09 | 0.00 | 77160780.87 | 19560503.44 | 0.00 | 0.616631E+11 | 0.00 | 22.22 |
April | 0.351185E+09 | 0.268049E+10 | 0.00 | 70996870.18 | 72209804.33 | 0.00 | 0.383872E+11 | 0.00 | 22.28 |
May | 0.114580E+09 | 0.111477E+11 | 0.00 | 42454013.73 | 0.361036E+09 | 0.00 | 0.149050E+11 | 0.00 | 22.17 |
June | 45465716.15 | 0.315750E+11 | 0.00 | 18628425.89 | 0.657602E+09 | 0.00 | 0.626655E+10 | 0.00 | 21.70 |
July | 0.00 | 0.492807E+11 | 0.00 | 666501.01 | 0.924625E+09 | 0.00 | 98297989.33 | 0.00 | 21.36 |
August | 0.00 | 0.520698E+11 | 0.00 | 162019.50 | 0.926466E+09 | 0.00 | 15518547.83 | 0.00 | 21.37 |
September | 72491656.24 | 0.266272E+11 | 0.00 | 26914981.16 | 0.547286E+09 | 0.00 | 0.928782E+10 | 0.00 | 22.01 |
October | 0.560588E+09 | 0.802885E+10 | 0.00 | 63923645.96 | 0.155837E+09 | 0.00 | 0.472692E+11 | 0.00 | 22.21 |
November | 0.773434E+09 | 0.109142E+10 | 0.00 | 69443692.79 | 23508351.92 | 0.00 | 0.663696E+11 | 0.00 | 22.17 |
December | 0.152076E+10 | 0.166022E+09 | 0.00 | 72802016.47 | 2109773.27 | 0.00 | 0.856838E+11 | 0.00 | 21.99 |
Annual Sum or Average | 0.719415E+10 | 0.183208E+12 | 0.00 | 0.583211E+09 | 0.369081E+10 | 0.00 | 0.479818E+12 | 0.00 | 21.95 |
Minimum of Months | 0.00 | 8675456.76 | 0.00 | 162019.50 | 0.00 | 0.00 | 15518547.83 | 0.00 | 21.36 |
Maximum of Months | 0.188826E+10 | 0.520698E+11 | 0.00 | 77160780.87 | 0.926466E+09 | 0.00 | 0.856838E+11 | 0.00 | 22.28 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321923E+11 | 0.00 | 0.00 | 252057.99 | 3567346.33 | 85019751.13 | 0.966713E+09 | 0.00 | 3.53 |
February | 0.236526E+11 | 2847368.19 | 0.00 | 1199856.93 | 3084959.71 | 0.00 | 0.276620E+10 | 0.00 | 3.54 |
March | 0.176810E+11 | 45612288.95 | 0.00 | 3289003.06 | 0.168018E+09 | 0.00 | 0.654494E+10 | 0.00 | 3.56 |
April | 0.943484E+10 | 0.230623E+09 | 0.00 | 4358474.85 | 0.851388E+09 | 0.00 | 0.568303E+10 | 0.00 | 3.56 |
May | 0.241703E+10 | 0.147418E+10 | 0.00 | 4643993.75 | 0.298884E+10 | 0.00 | 0.352413E+10 | 0.00 | 3.54 |
June | 0.891055E+09 | 0.718475E+10 | 0.00 | 2061789.99 | 0.527679E+10 | 0.00 | 0.161765E+10 | 0.00 | 3.46 |
July | 5424205.88 | 0.125840E+11 | 0.00 | 196626.81 | 0.685230E+10 | 0.00 | 35073348.70 | 0.00 | 3.43 |
August | 159686.88 | 0.156345E+11 | 0.00 | 93464.24 | 0.483559E+10 | 0.00 | 6194695.47 | 0.00 | 3.43 |
September | 0.114856E+10 | 0.653070E+10 | 0.00 | 3370434.55 | 0.404011E+10 | 0.00 | 0.246390E+10 | 0.00 | 3.53 |
October | 0.108129E+11 | 0.168980E+10 | 0.00 | 5563976.17 | 0.145658E+10 | 0.00 | 0.773973E+10 | 0.00 | 3.57 |
November | 0.196715E+11 | 80747435.34 | 0.00 | 3238799.41 | 0.357268E+09 | 0.00 | 0.630869E+10 | 0.00 | 3.56 |
December | 0.307750E+11 | 7011121.50 | 0.00 | 1017010.32 | 62124647.28 | 0.00 | 0.311679E+10 | 0.00 | 3.54 |
Annual Sum or Average | 0.148682E+12 | 0.454647E+11 | 0.00 | 29285488.08 | 0.268957E+11 | 85019751.13 | 0.407730E+11 | 0.00 | 3.52 |
Minimum of Months | 159686.88 | 0.00 | 0.00 | 93464.24 | 3084959.71 | 0.00 | 6194695.47 | 0.00 | 3.43 |
Maximum of Months | 0.321923E+11 | 0.156345E+11 | 0.00 | 5563976.17 | 0.685230E+10 | 85019751.13 | 0.773973E+10 | 0.00 | 3.57 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115111E+12 | 0.00 | 0.00 | 0.00 | 12352199.71 | 0.00 | 0.00 | 0.00 | 1.76 |
February | 0.909763E+11 | 0.00 | 0.00 | 115020.61 | 20541122.81 | 0.00 | 0.504808E+09 | 0.00 | 1.77 |
March | 0.821585E+11 | 12806796.76 | 0.00 | 714251.14 | 0.726905E+09 | 0.00 | 0.173631E+10 | 0.00 | 1.78 |
April | 0.490503E+11 | 12965746.71 | 0.00 | 2152303.78 | 0.373358E+10 | 0.00 | 0.330920E+10 | 0.00 | 1.78 |
May | 0.175480E+11 | 0.185644E+10 | 0.00 | 3074003.92 | 0.135971E+11 | 0.00 | 0.303675E+10 | 0.00 | 1.77 |
June | 0.598520E+10 | 0.144322E+11 | 0.00 | 2439602.25 | 0.287035E+11 | 0.00 | 0.270606E+10 | 0.00 | 1.73 |
July | 48838970.31 | 0.240728E+11 | 0.00 | 108513.49 | 0.431500E+11 | 0.00 | 91959120.00 | 0.00 | 1.71 |
August | 4191836.11 | 0.296575E+11 | 0.00 | 149612.21 | 0.410062E+11 | 0.00 | 17984695.94 | 0.00 | 1.71 |
September | 0.780113E+10 | 0.103590E+11 | 0.00 | 3554218.46 | 0.261988E+11 | 0.00 | 0.471528E+10 | 0.00 | 1.76 |
October | 0.596989E+11 | 0.264408E+10 | 0.00 | 1882313.19 | 0.824212E+10 | 0.00 | 0.455825E+10 | 0.00 | 1.78 |
November | 0.885336E+11 | 9314663.52 | 0.00 | 248771.51 | 0.150735E+10 | 0.00 | 0.143561E+10 | 0.00 | 1.78 |
December | 0.117195E+12 | 0.00 | 0.00 | 38223.82 | 0.239388E+09 | 0.00 | 0.161471E+09 | 0.00 | 1.77 |
Annual Sum or Average | 0.634110E+12 | 0.830572E+11 | 0.00 | 14476834.38 | 0.167138E+12 | 0.00 | 0.222737E+11 | 0.00 | 1.76 |
Minimum of Months | 4191836.11 | 0.00 | 0.00 | 0.00 | 12352199.71 | 0.00 | 0.00 | 0.00 | 1.71 |
Maximum of Months | 0.117195E+12 | 0.296575E+11 | 0.00 | 3554218.46 | 0.431500E+11 | 0.00 | 0.471528E+10 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60759798.16 | 0.00 | 0.00 | 631253.08 | 0.00 | 0.120739E+10 | 98050625.26 | 0.00 | 0.35 |
February | 67224209.18 | 18186.83 | 0.00 | 2091228.35 | 0.00 | 0.866893E+09 | 0.260586E+09 | 1160.93 | 0.35 |
March | 69974872.16 | 11336856.74 | 6795.69 | 5244173.99 | 172924.38 | 0.427551E+09 | 0.586472E+09 | 3753.08 | 0.35 |
April | 21743845.29 | 45279195.76 | 73963.84 | 7470694.40 | 3056251.51 | 0.118799E+09 | 0.625402E+09 | 13246.63 | 0.35 |
May | 1747802.09 | 0.255687E+09 | 90421.77 | 5136754.59 | 1003268.11 | 1374124.38 | 0.277926E+09 | 13082.27 | 0.36 |
June | 677910.71 | 0.767854E+09 | 422956.06 | 2555374.23 | 0.00 | 227213.18 | 0.120421E+09 | 32818.23 | 0.36 |
July | 0.00 | 0.109075E+10 | 651075.01 | 194145.61 | 2889960.24 | 37372.87 | 3670000.28 | 26159.87 | 0.35 |
August | 0.00 | 0.118949E+10 | 654453.32 | 59575.22 | 0.00 | 9139.35 | 351450.33 | 28816.74 | 0.36 |
September | 1401214.35 | 0.575161E+09 | 630904.73 | 2630409.83 | 4962877.78 | 5719588.94 | 0.158219E+09 | 42198.15 | 0.36 |
October | 38249051.09 | 0.149392E+09 | 163693.83 | 5737403.89 | 3791681.92 | 0.303140E+09 | 0.525727E+09 | 16982.31 | 0.36 |
November | 39995255.96 | 8808380.63 | 10109.71 | 3221598.16 | 1225092.91 | 0.615162E+09 | 0.479514E+09 | 7907.48 | 0.35 |
December | 69697135.68 | 457434.16 | 80.75 | 1135963.36 | 351852.84 | 0.109919E+10 | 0.170484E+09 | 2775.01 | 0.35 |
Annual Sum or Average | 0.371471E+09 | 0.409423E+10 | 2704454.69 | 36108574.70 | 17453909.70 | 0.464549E+10 | 0.330682E+10 | 188900.69 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 59575.22 | 0.00 | 9139.35 | 351450.33 | 0.00 | 0.35 |
Maximum of Months | 69974872.16 | 0.118949E+10 | 654453.32 | 7470694.40 | 4962877.78 | 0.120739E+10 | 0.625402E+09 | 42198.15 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51533551.86 | 0.00 | 0.00 | 93980.61 | 0.00 | 0.128854E+10 | 26500145.17 | 0.00 | 0.35 |
February | 93901465.01 | 11319.17 | 6852.35 | 674101.06 | 0.00 | 0.972188E+09 | 0.129891E+09 | 1173.98 | 0.35 |
March | 0.201754E+09 | 9265383.67 | 23546.72 | 2342152.69 | 2216771.13 | 0.523137E+09 | 0.361882E+09 | 13278.59 | 0.35 |
April | 0.147295E+09 | 35002305.16 | 128016.08 | 5234618.43 | 13274007.77 | 0.127529E+09 | 0.493267E+09 | 12655.32 | 0.35 |
May | 93249675.60 | 0.216957E+09 | 300236.43 | 3117172.98 | 39474229.61 | 787661.65 | 0.188997E+09 | 32102.75 | 0.36 |
June | 25982116.85 | 0.651524E+09 | 400057.58 | 2160884.80 | 0.116273E+09 | 150262.79 | 95574141.15 | 22136.92 | 0.36 |
July | 3763667.99 | 0.934394E+09 | 491948.60 | 69044.21 | 0.159289E+09 | 14138.99 | 54210.44 | 11320.33 | 0.36 |
August | 420115.67 | 0.107043E+10 | 579622.84 | 0.00 | 0.119008E+09 | 0.00 | 0.00 | 13471.22 | 0.36 |
September | 57714323.33 | 0.459625E+09 | 696234.78 | 1733852.81 | 0.120363E+09 | 689913.94 | 0.107812E+09 | 44001.67 | 0.36 |
October | 0.145764E+09 | 0.114427E+09 | 622957.86 | 2341317.60 | 38262263.63 | 0.364720E+09 | 0.359926E+09 | 33986.63 | 0.36 |
November | 0.137123E+09 | 5039503.01 | 44814.55 | 1167615.64 | 4956527.53 | 0.784859E+09 | 0.214610E+09 | 9467.96 | 0.35 |
December | 85947902.27 | 408233.70 | 107.98 | 250907.35 | 400958.48 | 0.120456E+10 | 49591388.08 | 2747.44 | 0.35 |
Annual Sum or Average | 0.104445E+10 | 0.349709E+10 | 3294395.77 | 19185648.18 | 0.613518E+09 | 0.526718E+10 | 0.202810E+10 | 196342.81 | 0.35 |
Minimum of Months | 420115.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.201754E+09 | 0.107043E+10 | 696234.78 | 5234618.43 | 0.159289E+09 | 0.128854E+10 | 0.493267E+09 | 44001.67 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837168E+09 | 0.00 | 0.00 | 78331.19 | 1420140.90 | 0.00 | 60060593.24 | 0.00 | 0.02 |
February | 0.590345E+09 | 0.00 | 0.00 | 780122.08 | 0.00 | 0.00 | 0.213610E+09 | 0.00 | 0.02 |
March | 0.377481E+09 | 19815711.73 | 0.00 | 1721856.71 | 0.00 | 0.00 | 0.611981E+09 | 0.00 | 0.02 |
April | 0.170053E+09 | 79932817.90 | 0.00 | 1643478.60 | 8168429.84 | 0.00 | 0.264715E+09 | 0.00 | 0.02 |
May | 11199065.17 | 0.300189E+09 | 0.00 | 375431.74 | 0.00 | 0.00 | 0.108319E+09 | 0.00 | 0.02 |
June | 0.00 | 0.550046E+09 | 0.00 | 165075.48 | 0.00 | 0.00 | 44100986.81 | 0.00 | 0.02 |
July | 0.00 | 0.815318E+09 | 0.00 | 0.00 | 6324951.82 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.909530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 36173863.94 | 0.592925E+09 | 0.00 | 610442.82 | 21415963.91 | 0.00 | 23445183.89 | 0.00 | 0.02 |
October | 0.173880E+09 | 0.213784E+09 | 0.00 | 1999600.13 | 12395649.08 | 0.00 | 0.476000E+09 | 0.00 | 0.02 |
November | 0.357145E+09 | 39328833.38 | 0.00 | 1944276.94 | 3766583.45 | 0.00 | 0.608691E+09 | 0.00 | 0.02 |
December | 0.763560E+09 | 0.00 | 0.00 | 929533.25 | 0.00 | 0.00 | 0.412565E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.331700E+10 | 0.352087E+10 | 0.00 | 10248148.93 | 53491719.00 | 0.00 | 0.282349E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.837168E+09 | 0.909530E+09 | 0.00 | 1999600.13 | 21415963.91 | 0.00 | 0.611981E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117407E+10 | 0.00 | 0.00 | 6928295.08 | 0.00 | 0.128102E+11 | 0.454682E+10 | 0.00 | 0.40 |
February | 0.157068E+10 | 211284.11 | 30056.80 | 21581099.05 | 0.00 | 0.710000E+10 | 0.753964E+10 | 21069.12 | 0.40 |
March | 0.273667E+10 | 0.122209E+09 | 185763.91 | 47389308.91 | 33779965.24 | 0.691694E+09 | 0.112974E+11 | 72927.40 | 0.40 |
April | 0.200388E+10 | 0.464368E+09 | 998377.65 | 79611439.80 | 0.191313E+09 | 0.101161E+09 | 0.830505E+10 | 68415.13 | 0.40 |
May | 0.127552E+10 | 0.281238E+10 | 6413310.37 | 43940739.29 | 0.663848E+09 | 5482348.11 | 0.255652E+10 | 198735.07 | 0.40 |
June | 0.364570E+09 | 0.882552E+10 | 3936587.05 | 23768367.87 | 0.159093E+10 | 1008433.42 | 0.129084E+10 | 43371.50 | 0.40 |
July | 51051898.50 | 0.126622E+11 | 2876705.30 | 1405303.80 | 0.217686E+10 | 38394.01 | 419964.50 | 35382.44 | 0.40 |
August | 5698617.07 | 0.144530E+11 | 11753309.48 | 0.00 | 0.167718E+10 | 0.00 | 0.00 | 88125.01 | 0.40 |
September | 0.784042E+09 | 0.602705E+10 | 13422386.48 | 27499814.32 | 0.183661E+10 | 5506640.64 | 0.146109E+10 | 152980.57 | 0.41 |
October | 0.197616E+10 | 0.151589E+10 | 1962777.09 | 49704163.32 | 0.562128E+09 | 0.258129E+09 | 0.955435E+10 | 74870.20 | 0.40 |
November | 0.185999E+10 | 68589999.16 | 456637.40 | 35330004.21 | 67232322.57 | 0.208574E+10 | 0.114520E+11 | 47508.34 | 0.40 |
December | 0.129880E+10 | 5561871.33 | 0.00 | 14015826.48 | 5438761.22 | 0.851441E+10 | 0.835386E+10 | 14306.02 | 0.40 |
Annual Sum or Average | 0.151011E+11 | 0.469570E+11 | 42035911.52 | 0.351174E+09 | 0.880533E+10 | 0.315734E+11 | 0.663580E+11 | 817690.79 | 0.40 |
Minimum of Months | 5698617.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.273667E+10 | 0.144530E+11 | 13422386.48 | 79611439.80 | 0.217686E+10 | 0.128102E+11 | 0.114520E+11 | 198735.07 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60759798.16 | 0.00 | 0.00 | 374143.68 | 0.00 | 0.120897E+10 | 96723315.57 | 0.00 | 0.35 |
February | 62373549.17 | 18186.83 | 0.00 | 2232404.62 | 0.00 | 0.861478E+09 | 0.270711E+09 | 1160.93 | 0.35 |
March | 59285390.03 | 11357395.48 | 13572.45 | 4858643.98 | 140575.62 | 0.427541E+09 | 0.597558E+09 | 8786.33 | 0.35 |
April | 17182652.23 | 45779441.49 | 54809.03 | 7686980.29 | 2579872.27 | 0.124216E+09 | 0.624330E+09 | 8534.96 | 0.35 |
May | 106343.02 | 0.255737E+09 | 49795.39 | 5663835.38 | 1003268.11 | 5578247.04 | 0.274836E+09 | 3227.51 | 0.36 |
June | 0.00 | 0.768309E+09 | 0.00 | 2857707.28 | 0.00 | 0.00 | 0.121024E+09 | 0.00 | 0.36 |
July | 0.00 | 0.109138E+10 | 41157.16 | 192443.62 | 2889960.24 | 73699.26 | 3635375.87 | 761.93 | 0.35 |
August | 0.00 | 0.119017E+10 | 5995.88 | 70295.04 | 0.00 | 0.00 | 349869.86 | 612.17 | 0.36 |
September | 1401214.35 | 0.575882E+09 | 373440.46 | 2922977.68 | 4529377.56 | 5729854.14 | 0.157916E+09 | 12070.11 | 0.36 |
October | 26617760.77 | 0.150440E+09 | 144683.90 | 5558216.15 | 2773376.33 | 0.308803E+09 | 0.531875E+09 | 6713.32 | 0.36 |
November | 39312465.76 | 9033262.20 | 16068.54 | 3162257.23 | 991671.18 | 0.595994E+09 | 0.499424E+09 | 10488.82 | 0.35 |
December | 69230252.95 | 457434.16 | 0.00 | 894413.80 | 351852.84 | 0.107990E+10 | 0.190490E+09 | 2855.75 | 0.35 |
Annual Sum or Average | 0.336269E+09 | 0.409856E+10 | 699522.82 | 36474318.75 | 15259954.14 | 0.461828E+10 | 0.336887E+10 | 55211.84 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 70295.04 | 0.00 | 0.00 | 349869.86 | 0.00 | 0.35 |
Maximum of Months | 69230252.95 | 0.119017E+10 | 373440.46 | 7686980.29 | 4529377.56 | 0.120897E+10 | 0.624330E+09 | 12070.11 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58396753.50 | 0.00 | 0.00 | 64681.98 | 0.00 | 0.128154E+10 | 26666231.23 | 0.00 | 0.35 |
February | 96164669.60 | 18184.70 | 0.00 | 897037.54 | 0.00 | 0.944285E+09 | 0.155307E+09 | 1160.80 | 0.35 |
March | 0.201333E+09 | 9238323.02 | 48396.10 | 2236986.16 | 2212775.98 | 0.514469E+09 | 0.371076E+09 | 19485.01 | 0.35 |
April | 0.145098E+09 | 36206075.14 | 135653.80 | 5597458.68 | 12068701.19 | 0.138387E+09 | 0.484244E+09 | 6554.19 | 0.35 |
May | 91465559.56 | 0.217826E+09 | 130808.85 | 3374960.70 | 38801223.40 | 2148598.24 | 0.189162E+09 | 5581.16 | 0.36 |
June | 25307213.44 | 0.653914E+09 | 147233.32 | 2333273.85 | 0.114153E+09 | 70225.04 | 96156693.26 | 5351.83 | 0.36 |
July | 3763667.99 | 0.938145E+09 | 50060.40 | 68771.71 | 0.155991E+09 | 14138.99 | 54482.95 | 989.60 | 0.36 |
August | 420115.67 | 0.107176E+10 | 258162.50 | 0.00 | 0.118015E+09 | 0.00 | 0.00 | 2459.79 | 0.36 |
September | 57036426.67 | 0.461193E+09 | 581850.31 | 1868859.41 | 0.118931E+09 | 709156.80 | 0.108336E+09 | 22988.64 | 0.36 |
October | 0.145015E+09 | 0.118251E+09 | 449980.19 | 2508459.03 | 34622854.72 | 0.369335E+09 | 0.355892E+09 | 23240.98 | 0.36 |
November | 0.137123E+09 | 5047606.16 | 39754.10 | 995268.05 | 4956527.53 | 0.767164E+09 | 0.232477E+09 | 6425.26 | 0.35 |
December | 84830710.79 | 410034.45 | 0.00 | 162288.12 | 400958.48 | 0.121248E+10 | 42883359.31 | 1054.67 | 0.35 |
Annual Sum or Average | 0.104595E+10 | 0.351200E+10 | 1841899.57 | 20108045.22 | 0.600153E+09 | 0.523060E+10 | 0.206225E+10 | 95291.93 | 0.35 |
Minimum of Months | 420115.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.201333E+09 | 0.107176E+10 | 581850.31 | 5597458.68 | 0.155991E+09 | 0.128154E+10 | 0.484244E+09 | 23240.98 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.324947E+11 | 0.00 | 0.00 | 0.00 | 3875459.06 | 0.362086E+10 | 0.00 | 0.00 | 0.60 |
February | 0.268793E+11 | 0.00 | 0.00 | 0.00 | 6444704.78 | 0.182264E+10 | 0.00 | 0.00 | 0.61 |
March | 0.263219E+11 | 0.00 | 0.00 | 0.00 | 0.232082E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.164283E+11 | 0.00 | 0.00 | 0.00 | 0.117546E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.645935E+10 | 0.00 | 0.00 | 0.00 | 0.484849E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.272762E+10 | 0.00 | 0.00 | 0.00 | 0.135337E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 44208949.63 | 0.00 | 0.00 | 0.00 | 0.210707E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 7004748.96 | 0.00 | 0.00 | 0.00 | 0.221254E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.392810E+10 | 0.00 | 0.00 | 0.00 | 0.114676E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 0.201610E+11 | 0.00 | 0.00 | 0.00 | 0.341551E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.282276E+11 | 0.00 | 0.00 | 0.00 | 0.475847E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
December | 0.366735E+11 | 0.00 | 0.00 | 0.00 | 75107045.17 | 0.146652E+09 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.200353E+12 | 0.00 | 0.00 | 0.00 | 0.784302E+11 | 0.559015E+10 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 7004748.96 | 0.00 | 0.00 | 0.00 | 3875459.06 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.366735E+11 | 0.00 | 0.00 | 0.00 | 0.221254E+11 | 0.362086E+10 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14845670.61 | 0.00 | 0.00 | 111961.06 | 0.00 | 0.309543E+09 | 17207204.01 | 0.00 | 0.35 |
February | 14992836.52 | 4546.71 | 0.00 | 486577.53 | 0.00 | 0.238304E+09 | 45415101.78 | 290.23 | 0.35 |
March | 16681736.31 | 2848481.65 | 619.36 | 1253835.46 | 30034.73 | 0.145699E+09 | 0.108676E+09 | 946.73 | 0.35 |
April | 5052748.40 | 11452633.82 | 18581.88 | 1817836.96 | 631227.99 | 50663103.59 | 0.135820E+09 | 3220.73 | 0.35 |
May | 347824.02 | 64108054.32 | 23197.03 | 1247216.50 | 64680.93 | 4573179.30 | 65377945.65 | 2408.09 | 0.36 |
June | 0.00 | 0.191999E+09 | 70180.09 | 621123.49 | 0.00 | 57018.84 | 30292337.72 | 8078.62 | 0.36 |
July | 0.00 | 0.272694E+09 | 155854.30 | 43066.34 | 722490.06 | 19970.31 | 912343.04 | 6766.93 | 0.35 |
August | 0.00 | 0.297373E+09 | 161392.26 | 13333.50 | 0.00 | 2284.84 | 89422.88 | 8349.81 | 0.36 |
September | 350303.59 | 0.143810E+09 | 137059.75 | 585134.06 | 1240719.44 | 3923273.70 | 37133733.75 | 11033.41 | 0.36 |
October | 9231213.14 | 37587004.63 | 57035.80 | 1373293.38 | 693344.08 | 0.100884E+09 | 0.106724E+09 | 3784.05 | 0.36 |
November | 10198978.72 | 2260450.59 | 2492.89 | 730429.20 | 247917.79 | 0.188259E+09 | 85285129.67 | 2011.41 | 0.35 |
December | 15446164.01 | 114358.54 | 141.47 | 233411.99 | 87963.21 | 0.291092E+09 | 28355798.21 | 572.47 | 0.35 |
Annual Sum or Average | 87147475.31 | 0.102425E+10 | 626554.85 | 8517219.47 | 3718378.25 | 0.133302E+10 | 0.661290E+09 | 47462.49 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13333.50 | 0.00 | 2284.84 | 89422.88 | 0.00 | 0.35 |
Maximum of Months | 16681736.31 | 0.297373E+09 | 161392.26 | 1817836.96 | 1240719.44 | 0.309543E+09 | 0.135820E+09 | 11033.41 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9760363.56 | 0.00 | 0.00 | 17153.74 | 0.00 | 0.329958E+09 | 1931644.79 | 0.00 | 0.35 |
February | 22688186.50 | 2829.79 | 1700.50 | 149293.62 | 0.00 | 0.258036E+09 | 18290196.51 | 306.09 | 0.35 |
March | 49941006.13 | 2316424.95 | 5449.98 | 537721.47 | 554192.78 | 0.161007E+09 | 60793058.29 | 3677.32 | 0.35 |
April | 36702673.49 | 9038027.79 | 31952.24 | 1309521.89 | 3031050.44 | 46019513.55 | 0.109300E+09 | 3215.61 | 0.35 |
May | 22969876.04 | 54452295.38 | 60958.95 | 789362.12 | 9669205.26 | 594003.55 | 47184541.08 | 8359.00 | 0.36 |
June | 6342307.63 | 0.162886E+09 | 95655.78 | 539422.29 | 29068206.17 | 29079.74 | 24056041.74 | 5024.91 | 0.36 |
July | 940917.00 | 0.233646E+09 | 76790.72 | 16616.81 | 39822336.61 | 3150.57 | 14581.02 | 1278.25 | 0.36 |
August | 105028.92 | 0.267624E+09 | 128073.21 | 0.00 | 29752019.29 | 0.00 | 0.00 | 3688.44 | 0.36 |
September | 14273716.03 | 0.115370E+09 | 160947.20 | 391793.07 | 29641598.04 | 2789888.71 | 24532127.25 | 9684.19 | 0.36 |
October | 36421797.79 | 29292996.14 | 122211.08 | 520901.37 | 8913482.26 | 0.118009E+09 | 63236489.40 | 7986.85 | 0.36 |
November | 32950286.26 | 1259875.75 | 11077.59 | 241024.69 | 1239131.88 | 0.221118E+09 | 30130731.40 | 2493.04 | 0.35 |
December | 18168912.20 | 102058.43 | 129.05 | 43350.54 | 100239.62 | 0.309122E+09 | 7754434.94 | 584.80 | 0.35 |
Annual Sum or Average | 0.251265E+09 | 0.875991E+09 | 694946.31 | 4556161.62 | 0.151791E+09 | 0.144668E+10 | 0.387224E+09 | 46298.51 | 0.35 |
Minimum of Months | 105028.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 49941006.13 | 0.267624E+09 | 160947.20 | 1309521.89 | 39822336.61 | 0.329958E+09 | 0.109300E+09 | 9684.19 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65992218.86 | 0.00 | 0.00 | 3510064.58 | 0.00 | 0.158959E+10 | 0.536209E+09 | 0.00 | 0.40 |
February | 81163371.51 | 25020.49 | 1383.17 | 5847736.31 | 0.00 | 0.111317E+10 | 0.722014E+09 | 4671.21 | 0.40 |
March | 57322583.06 | 18381029.40 | 9323.29 | 10186659.51 | 111968.41 | 0.422374E+09 | 0.125957E+10 | 738.05 | 0.40 |
April | 27669803.80 | 74088213.88 | 51504.30 | 11047590.89 | 3631051.52 | 0.160403E+09 | 0.104308E+10 | 1942.45 | 0.40 |
May | 1264554.70 | 0.410829E+09 | 0.00 | 6985966.23 | 1611371.32 | 6034892.60 | 0.445362E+09 | 1216.13 | 0.40 |
June | 0.00 | 0.123382E+10 | 170120.86 | 3081435.21 | 0.00 | 327116.23 | 0.195561E+09 | 3948.89 | 0.40 |
July | 0.00 | 0.175233E+10 | 622019.22 | 271781.66 | 4641629.69 | 118370.03 | 5876164.73 | 11904.87 | 0.40 |
August | 0.00 | 0.191112E+10 | 435578.19 | 88868.29 | 0.00 | 14678.92 | 571289.03 | 8232.96 | 0.40 |
September | 2250521.66 | 0.924325E+09 | 369286.11 | 4230984.82 | 8131080.17 | 4304386.34 | 0.258994E+09 | 5488.91 | 0.40 |
October | 26077105.02 | 0.241849E+09 | 18074.03 | 11970770.80 | 4454381.67 | 0.223611E+09 | 0.114025E+10 | 1369.50 | 0.40 |
November | 28100335.93 | 14781147.80 | 3643.72 | 10105997.32 | 1358958.42 | 0.521355E+09 | 0.126803E+10 | 173.84 | 0.40 |
December | 51278058.95 | 1304400.62 | 0.00 | 5488227.13 | 0.00 | 0.127159E+10 | 0.824664E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.341119E+09 | 0.658285E+10 | 1680932.89 | 72816082.74 | 23940441.20 | 0.531289E+10 | 0.770019E+10 | 39686.81 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 88868.29 | 0.00 | 14678.92 | 571289.03 | 0.00 | 0.40 |
Maximum of Months | 81163371.51 | 0.191112E+10 | 622019.22 | 11970770.80 | 8131080.17 | 0.158959E+10 | 0.126803E+10 | 11904.87 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.265559E+11 | 0.00 | 0.00 | 16779778.91 | 5734186.58 | 0.00 | 0.268909E+11 | 0.00 | 4.22 |
February | 0.170383E+11 | 1049463.62 | 0.00 | 22026645.43 | 8486216.95 | 0.00 | 0.255060E+11 | 0.00 | 4.24 |
March | 0.984394E+10 | 0.226569E+09 | 0.00 | 36399112.82 | 0.118160E+09 | 0.00 | 0.293530E+11 | 0.00 | 4.29 |
April | 0.345460E+10 | 0.144845E+10 | 0.00 | 42750310.43 | 0.302822E+09 | 0.00 | 0.212528E+11 | 0.00 | 4.34 |
May | 0.526905E+09 | 0.676490E+10 | 0.00 | 34988313.01 | 0.636501E+09 | 0.00 | 0.931473E+10 | 0.00 | 4.40 |
June | 0.117345E+09 | 0.207729E+11 | 0.00 | 15575062.10 | 0.741359E+09 | 0.00 | 0.409340E+10 | 0.00 | 4.45 |
July | 0.00 | 0.326310E+11 | 0.00 | 1105435.29 | 0.988995E+09 | 0.00 | 66900679.60 | 0.00 | 4.44 |
August | 0.00 | 0.346112E+11 | 0.00 | 351686.04 | 0.991528E+09 | 0.00 | 10568859.80 | 0.00 | 4.44 |
September | 0.258795E+09 | 0.166884E+11 | 0.00 | 18721139.39 | 0.100134E+10 | 0.00 | 0.574530E+10 | 0.00 | 4.39 |
October | 0.601668E+10 | 0.452717E+10 | 0.00 | 32374111.92 | 0.687228E+09 | 0.00 | 0.240523E+11 | 0.00 | 4.31 |
November | 0.114611E+11 | 0.417838E+09 | 0.00 | 27350904.67 | 0.289788E+09 | 0.00 | 0.304094E+11 | 0.00 | 4.27 |
December | 0.214916E+11 | 3271994.98 | 0.00 | 21588355.88 | 0.107858E+09 | 0.00 | 0.330138E+11 | 0.00 | 4.24 |
Annual Sum or Average | 0.967653E+11 | 0.118093E+12 | 0.00 | 0.270011E+09 | 0.587980E+10 | 0.00 | 0.209709E+12 | 0.00 | 4.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 351686.04 | 5734186.58 | 0.00 | 10568859.80 | 0.00 | 4.22 |
Maximum of Months | 0.265559E+11 | 0.346112E+11 | 0.00 | 42750310.43 | 0.100134E+10 | 0.00 | 0.330138E+11 | 0.00 | 4.45 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235563E+11 | 2018628.40 | 0.00 | 22784209.11 | 3989532.78 | 0.00 | 0.324946E+11 | 0.00 | 4.43 |
February | 0.149306E+11 | 7875094.51 | 0.00 | 29537147.51 | 2116192.84 | 0.00 | 0.297954E+11 | 0.00 | 4.47 |
March | 0.714529E+10 | 0.293487E+09 | 0.00 | 47435876.69 | 69664421.43 | 0.00 | 0.342673E+11 | 0.00 | 4.54 |
April | 0.218968E+10 | 0.170369E+10 | 0.00 | 53277382.41 | 0.150663E+09 | 0.00 | 0.240128E+11 | 0.00 | 4.62 |
May | 0.209472E+09 | 0.747431E+10 | 0.00 | 41480790.66 | 0.392501E+09 | 0.00 | 0.102658E+11 | 0.00 | 4.69 |
June | 63371182.81 | 0.222252E+11 | 0.00 | 18141500.06 | 0.627188E+09 | 0.00 | 0.441196E+10 | 0.00 | 4.74 |
July | 0.00 | 0.349192E+11 | 0.00 | 1193439.07 | 0.726103E+09 | 0.00 | 71674653.01 | 0.00 | 4.71 |
August | 0.00 | 0.369346E+11 | 0.00 | 373481.61 | 0.803767E+09 | 0.00 | 11207258.09 | 0.00 | 4.71 |
September | 0.130177E+09 | 0.181530E+11 | 0.00 | 22591736.85 | 0.647383E+09 | 0.00 | 0.625659E+10 | 0.00 | 4.67 |
October | 0.420625E+10 | 0.504599E+10 | 0.00 | 42106612.79 | 0.515512E+09 | 0.00 | 0.275664E+11 | 0.00 | 4.56 |
November | 0.963293E+10 | 0.601304E+09 | 0.00 | 36233052.06 | 0.145879E+09 | 0.00 | 0.344577E+11 | 0.00 | 4.50 |
December | 0.187815E+11 | 82753879.61 | 0.00 | 29122425.27 | 33685289.54 | 0.00 | 0.384468E+11 | 0.00 | 4.45 |
Annual Sum or Average | 0.808455E+11 | 0.127444E+12 | 0.00 | 0.344278E+09 | 0.411845E+10 | 0.00 | 0.242058E+12 | 0.00 | 4.59 |
Minimum of Months | 0.00 | 2018628.40 | 0.00 | 373481.61 | 2116192.84 | 0.00 | 11207258.09 | 0.00 | 4.43 |
Maximum of Months | 0.235563E+11 | 0.369346E+11 | 0.00 | 53277382.41 | 0.803767E+09 | 0.00 | 0.384468E+11 | 0.00 | 4.74 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6140584.45 | 7605352.36 | 0.00 | 0.105126E+09 | 0.00 | 0.00 | 0.655695E+11 | 0.00 | 16.79 |
February | 15455048.63 | 13960331.36 | 0.00 | 98633729.17 | 0.00 | 0.00 | 0.522492E+11 | 0.00 | 17.31 |
March | 6617344.33 | 0.524316E+09 | 0.00 | 0.106622E+09 | 0.00 | 0.00 | 0.485817E+11 | 0.00 | 18.08 |
April | 13925777.49 | 0.263179E+10 | 0.00 | 92537930.55 | 0.00 | 0.00 | 0.296185E+11 | 0.00 | 18.67 |
May | 2761653.85 | 0.109967E+11 | 0.00 | 53239688.49 | 0.00 | 0.00 | 0.112512E+11 | 0.00 | 18.98 |
June | 0.00 | 0.294864E+11 | 0.00 | 24180550.82 | 0.00 | 0.00 | 0.473895E+10 | 0.00 | 19.00 |
July | 0.00 | 0.457826E+11 | 0.00 | 811924.66 | 0.00 | 0.00 | 68731315.40 | 0.00 | 18.86 |
August | 0.00 | 0.481485E+11 | 0.00 | 279540.96 | 0.00 | 0.00 | 10703326.12 | 0.00 | 18.84 |
September | 3056705.84 | 0.242640E+11 | 0.00 | 33670776.65 | 0.00 | 0.00 | 0.703094E+10 | 0.00 | 18.86 |
October | 5913895.99 | 0.714840E+10 | 0.00 | 90015061.42 | 0.00 | 0.00 | 0.370070E+11 | 0.00 | 18.27 |
November | 8345428.33 | 0.104069E+10 | 0.00 | 97310000.33 | 0.00 | 0.00 | 0.517065E+11 | 0.00 | 17.76 |
December | 2534539.52 | 0.159070E+09 | 0.00 | 0.104722E+09 | 0.00 | 0.00 | 0.673695E+11 | 0.00 | 17.18 |
Annual Sum or Average | 64750978.43 | 0.170204E+12 | 0.00 | 0.807150E+09 | 0.00 | 0.00 | 0.375202E+12 | 0.00 | 18.22 |
Minimum of Months | 0.00 | 7605352.36 | 0.00 | 279540.96 | 0.00 | 0.00 | 10703326.12 | 0.00 | 16.79 |
Maximum of Months | 15455048.63 | 0.481485E+11 | 0.00 | 0.106622E+09 | 0.00 | 0.00 | 0.673695E+11 | 0.00 | 19.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126758E+11 | 0.00 | 0.00 | 0.00 | 1956737.94 | 0.555910E+10 | 0.00 | 0.00 | 1.15 |
February | 0.115574E+11 | 0.00 | 0.00 | 0.00 | 3253962.47 | 0.293434E+10 | 0.00 | 0.00 | 1.15 |
March | 0.132284E+11 | 0.00 | 0.00 | 0.00 | 0.117179E+09 | 61629831.82 | 0.00 | 0.00 | 1.16 |
April | 0.829471E+10 | 0.00 | 0.00 | 0.00 | 0.593497E+09 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 0.326136E+10 | 0.00 | 0.00 | 0.00 | 0.244803E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
June | 0.137719E+10 | 0.347160E+09 | 0.00 | 0.00 | 0.648606E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
July | 22321311.48 | 0.245310E+10 | 0.00 | 0.00 | 0.819421E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
August | 3536731.47 | 0.259388E+10 | 0.00 | 0.00 | 0.857754E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.198331E+10 | 14790849.27 | 0.00 | 0.00 | 0.577525E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
October | 0.101794E+11 | 0.00 | 0.00 | 0.00 | 0.172451E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
November | 0.137768E+11 | 0.00 | 0.00 | 0.00 | 0.240257E+09 | 0.475396E+09 | 0.00 | 0.00 | 1.16 |
December | 0.169590E+11 | 0.00 | 0.00 | 0.00 | 37921908.64 | 0.163168E+10 | 0.00 | 0.00 | 1.15 |
Annual Sum or Average | 0.933193E+11 | 0.540893E+10 | 0.00 | 0.00 | 0.341997E+11 | 0.106621E+11 | 0.00 | 0.00 | 1.15 |
Minimum of Months | 3536731.47 | 0.00 | 0.00 | 0.00 | 1956737.94 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.169590E+11 | 0.259388E+10 | 0.00 | 0.00 | 0.857754E+10 | 0.555910E+10 | 0.00 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:45:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.178464E+12 | 0.162047E+11 | 0.219067E+12 | 0.798200E+12 | 0.131440E+12 |
February | 0.185899E+12 | 0.117646E+11 | 0.158530E+12 | 0.576881E+12 | 0.172855E+12 |
March | 0.275553E+12 | 0.829486E+10 | 0.114330E+12 | 0.399895E+12 | 0.318205E+12 |
April | 0.311503E+12 | 0.470234E+10 | 0.649177E+11 | 0.229758E+12 | 0.509155E+12 |
May | 0.343016E+12 | -293689196.0 | -0.133496E+10 | -0.264663E+11 | 0.861838E+12 |
June | 0.350140E+12 | -0.627724E+10 | -0.846007E+11 | -0.336177E+12 | 0.118534E+13 |
July | 0.325806E+12 | -0.109781E+11 | -0.147794E+12 | -0.583582E+12 | 0.147059E+13 |
August | 0.300703E+12 | -0.127410E+11 | -0.168955E+12 | -0.679138E+12 | 0.152183E+13 |
September | 0.224917E+12 | -0.426683E+10 | -0.542939E+11 | -0.229747E+12 | 0.106503E+13 |
October | 0.214024E+12 | 0.468379E+10 | 0.666290E+11 | 0.233750E+12 | 0.516729E+12 |
November | 0.148033E+12 | 0.885362E+10 | 0.121075E+12 | 0.449201E+12 | 0.283065E+12 |
December | 0.141302E+12 | 0.128002E+11 | 0.175063E+12 | 0.645478E+12 | 0.168068E+12 |
Annual Sum or Average | 0.299936E+13 | 0.327472E+11 | 0.462634E+12 | 0.147805E+13 | 0.820415E+13 |
Minimum of Months | 0.141302E+12 | -0.127410E+11 | -0.168955E+12 | -0.679138E+12 | 0.131440E+12 |
Maximum of Months | 0.350140E+12 | 0.162047E+11 | 0.219067E+12 | 0.798200E+12 | 0.152183E+13 |