Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2023-10-16 08:46:00


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 12357.18 1089.19 1089.19
Net Site Energy 12357.18 1089.19 1089.19
Total Source Energy 29984.55 2642.91 2642.91
Net Source Energy 29984.55 2642.91 2642.91


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 62.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3640.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 782.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 194.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 640.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 466.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 133.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 295.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.76 2541.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 7964.17 4393.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 62.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3640.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 782.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 194.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 466.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 133.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 295.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.76 2541.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 62.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3640.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 782.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 194.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 640.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 466.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 133.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 295.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.76 2541.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 381.69 229.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 234.17 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 701.98 387.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 381.69 229.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 234.17 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 701.98 387.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 7964.170 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 7964.170 100.00
     
Total On-Site and Utility Electric Sources 7964.170 100.00
Total Electricity End Uses 7964.170 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 3765.52 99.34
Air to Air Heat Recovery for Heating 24.88 0.66
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3790.40 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 59.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 6465.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.8143 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 11.3140 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 11.3140 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 5.7199 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 4.6285 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.0104 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.7639 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 7.1042 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 8.2882 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.4097 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 7.1042 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.8143 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 11.3140 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 11.3140 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 5.7199 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 4.6285 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.0104 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.7639 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 8.2882 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 8.2882 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 8.2882 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 8.2882 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 7.1042 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 8.2882 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 8.2882 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 8.2882 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.0104 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.0104 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.4097 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 7.1042 18.58 0.0000  
Total 11345.29             8.5566 3.54 41.0709  
Conditioned Total 11345.29             8.5566 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6520 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 27-JUL-19:10 30-JAN-18:49 - - - - - - - - - - 09-JAN-21:49
Heating 0.00 3396.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 191315.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 64632.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86439.81 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31546.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24682.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 5035.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3599.84 214907.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2394.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 431924.87 322552.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3396.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 191315.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 64632.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56456.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1243.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 24682.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 5035.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3599.84 214907.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1061.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1091.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 67.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11528.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2479.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 614.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5251.45 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2029.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1476.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 421.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 935.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.43 2755.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 197.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 25222.53 4762.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 5.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1016.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 178.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 130.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 82.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 242.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2223.17 419.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 5.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1016.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 178.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 130.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 82.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 242.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2223.17 419.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.89 0.521172 0.526000 1.52 1.00 0.500000 0.000731 0.000070 1.52 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.309226 0.165278 0.526000 0.162653 0.526000 0.500000 0.002305 0.000026 0.162653 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.273796 0.216160 0.526000 0.144017 0.576426 0.500000 0.001763 0.000014 0.144017 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.274320 0.456231 0.526000 0.144292 1.00 0.500000 0.000835 0.000022 0.144292 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.150567 0.479565 0.526000 0.079198 1.00 0.500000 0.000794 0.000012 0.079198 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.19 0.018648 0.526000 1.68 0.526000 0.500000 0.020431 0.000098 1.68 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.31 0.110080 0.526000 0.687664 0.526000 0.500000 0.003461 0.000074 0.687664 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.72 0.211173 0.526000 2.48 0.563127 0.500000 0.001804 0.000233 2.48 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.55 0.767330 0.526000 0.813617 1.00 0.500000 0.000497 0.000105 0.813617 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.21 0.114257 0.526000 1.16 0.526000 0.500000 0.003335 0.000094 1.16 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.31 0.109280 0.526000 1.22 0.526000 0.500000 0.003486 0.000098 1.22 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.21 0.064210 0.526000 1.16 0.526000 0.500000 0.010672 0.000062 1.16 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.786287 0.399395 0.526000 0.413587 1.00 0.500000 0.000954 0.000061 0.413587 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 8025.74 0.000070 167.36
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2949.56 0.000026 70.55
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1607.17 0.000014 35.58
MECH_FLR_1 VAV BOX REHEAT COIL 2550.78 0.000022 60.70
STORAGE_FLR_1 VAV BOX REHEAT COIL 1386.97 0.000012 32.94
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11174.14 0.000098 236.24
CAFE_FLR_1 VAV BOX REHEAT COIL 8494.57 0.000074 190.48
LOBBY_FLR_1 VAV BOX REHEAT COIL 26633.67 0.000233 587.00
ROOM_1_FLR_3 FAN COIL HEATING COIL 3431.39 0.000030 98.04
ROOM_2_FLR_3 FAN COIL HEATING COIL 3431.95 0.000030 98.06
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 19969.49 0.000175 570.55
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 19992.62 0.000175 571.21
ROOM_5_FLR_3 FAN COIL HEATING COIL 3429.80 0.000030 97.99
ROOM_6_FLR_3 FAN COIL HEATING COIL 3430.37 0.000030 98.01
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11991.09 0.000105 275.99
ROOM_1_FLR_6 FAN COIL HEATING COIL 1027.29 0.000009 29.35
ROOM_2_FLR_6 FAN COIL HEATING COIL 1027.74 0.000009 29.36
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 4954.09 0.000043 141.54
BANQUET_FLR_6 VAV BOX REHEAT COIL 10770.38 0.000094 233.79
DINING_FLR_6 VAV BOX REHEAT COIL 11157.13 0.000098 241.97
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7125.18 0.000062 149.86
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7004.65 0.000061 165.27
VAV WITH REHEAT HEATING COIL 63774.19 0.000558 1183.42
FLR_3_DOAS HEATING COIL 5950.05 0.000052 110.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.980456 0.000030 0.000328
ROOM_2_FLR_3 FAN COIL 0.991205 0.000030 0.000331
ROOM_3_MULT19_FLR_3 FAN COIL 5.44 0.000175 0.001781
ROOM_4_MULT19_FLR_3 FAN COIL 6.47 0.000175 0.002223
ROOM_5_FLR_3 FAN COIL 0.879492 0.000030 0.000296
ROOM_6_FLR_3 FAN COIL 0.886803 0.000030 0.000299
ROOM_1_FLR_6 FAN COIL 0.269911 0.000009 0.000090
ROOM_2_FLR_6 FAN COIL 0.272496 0.000009 0.000090
ROOM_3_MULT9_FLR_6 FAN COIL 1.08 0.000043 0.000371
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.980456
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.991205
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.44
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.47
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.879492
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.886803
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.269911
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.272496
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.08
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008757 12.80 0.008500 0.000328 0.980456  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008754 12.80 0.008500 0.000331 0.991205  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008675 12.80 0.008500 0.001781 5.44  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008863 12.80 0.008500 0.002223 6.47  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008788 12.80 0.008500 0.000296 0.879492  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008785 12.80 0.008500 0.000299 0.886803  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008734 12.80 0.008500 0.000090 0.269911  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008732 12.80 0.008500 0.000090 0.272496  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008841 12.80 0.008500 0.000371 1.08  
VAV WITH REHEAT COOLING COIL 28.88 6.70 0.013666 11.09 0.008500 0.023714 21.99 829161.05
FLR_3_DOAS COOLING COIL 33.20 6.70 0.017167 11.94 0.008500 0.003098 2.05 108329.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.67 11.67 22.18 11.67 21.99 21.99 0.300000 0.530638 21.99
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.99  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.023714 0.000020
VAV WITH REHEAT_HEATC_CONTROLLER 0.000558  
FLR_3_DOAS_COOLC_CONTROLLER 0.003098 0.000154
FLR_3_DOAS_HEATC_CONTROLLER 0.000052  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.032621 5326.07  
HEATSYS1 PUMP 0.002111 635.71 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002111 0.253309
COOLSYS1 0.032621 3.91
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 241290.00 241290.00 0.002111
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.032621 3687.42
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.032621 1140611.63 1143842.24 130.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.814 5.380 0.000 0.000 0.000 0.000 14.194 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 5.720 2.690 0.000 0.000 0.000 0.000 8.410 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 4.628 61.680 535.850 0.000 0.000 0.000 602.158 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.010 5.380 0.000 0.000 0.000 0.000 15.390 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.764 8.070 0.000 0.000 0.000 0.000 18.834 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.410 515.227 2419.260 0.000 0.000 0.000 2945.897 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17441.963 8.814 163.776 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17441.963
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 758.849 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 758.849
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 878.750 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 878.750
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 542.017 5.720 265.695 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 542.017
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 361.204 4.628 43.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 361.204
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1890.589 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1890.589
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 14081.185 10.764 33.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14081.185
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 203.259 8.288 135.506 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.259
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2766.397 7.104 132.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2766.397
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1178.676 11.410 53.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1178.676
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2927.804 7.104 132.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2927.804


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.393 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.408 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 3.444 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 3.444 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.2994E-01
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.2994E-01
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5506
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5431
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 0.2994E-01
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 0.2994E-01
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
29 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
30 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
31 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
32 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
33 4 19.715055 0.51780401E-02 12.415669 -0.24584718
34 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
35 2 168.49726 0.99923307E-02 62.094262 -2.4465849
36 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
37 0 57.057407 0.91053392E-05 16.929182  
38 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
39 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
40 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
41 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
42 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
43 4 19.715055 0.51780401E-02 12.415669 -0.24584718
44 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
45 2 168.49726 0.99923307E-02 62.094262 -2.4465849
46 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
47 0 57.057407 0.91053392E-05 16.929182  
48 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
49 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
50 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
51 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
52 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
53 4 19.715055 0.51780401E-02 12.415669 -0.24584718
54 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
55 2 168.49726 0.99923307E-02 62.094262 -2.4465849
56 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
57 0 57.057407 0.91053392E-05 16.929182  
58 9 0.75525440E-15 0.44740194E-16 -0.12773695E-09 -0.17413973E-17
59 8 0.18775242E-07 0.18212309E-12 0.34440251E-03 -0.21348098E-09
60 7 -0.11242372E-01 0.98045077E-08 -0.21646224E-01 0.12782986E-03
61 6 0.37819669 0.34662877E-05 0.44889448 -0.44276875E-02
62 5 -4.9255264 0.13123097E-03 -4.2627871 0.59897552E-01
63 4 31.830222 0.10869568E-02 20.742026 -0.40655401
64 3 -108.73045 0.23952585E-02 -54.243141 1.4791387
65 2 194.65663 0.13606195E-02 76.609648 -2.8614229
66 1 -170.25011 0.14657319E-03 -54.889188 2.7295613
67 0 57.057407 0.84265852E-06 15.620975  
68 9 0.85297796E-15 0.46957990E-16 -0.12703153E-09 -0.54240268E-18
69 8 0.18675511E-07 0.18384479E-12 0.34329809E-03 -0.21234699E-09
70 7 -0.11209220E-01 0.99091673E-08 -0.21598424E-01 0.12745291E-03
71 6 0.37729561 0.35050755E-05 0.44812211 -0.44170661E-02
72 5 -4.9167295 0.13275736E-03 -4.2568331 0.59788477E-01
73 4 31.791289 0.11000280E-02 20.718704 -0.40603713
74 3 -108.64755 0.24248953E-02 -54.197012 1.4779412
75 2 194.57440 0.13778728E-02 76.567430 -2.8601173
76 1 -170.21971 0.14847322E-03 -54.877080 2.7290284
77 0 57.057407 0.85387380E-06 15.623112  
78 7 -0.54138470E-12 0.12463713E-14 -0.64276224E-14 0.11113167E-15
79 6 0.12246794E-07 0.15689727E-09 0.20336639E-09 -0.66085082E-11
80 5 -0.43638646E-04 0.91064443E-06 -0.10338442E-05 0.73798452E-07
81 4 0.19644206E-01 0.40532412E-03 0.96204216E-03 -0.14823791E-03
82 3 -1.4347347 0.16410182E-01 -0.13915079 0.27725787E-01
83 2 17.082538 0.80550987E-01 2.2432332 -0.47694951
84 1 -41.597683 0.53207822E-01 -6.4041654 1.4049886
85 0 26.083068 0.22662127E-02 4.4519555  
86 7 -0.64276224E-14 0.12463713E-14 -0.54138470E-12 0.11113167E-15
87 6 0.20336639E-09 0.15689727E-09 0.12246794E-07 -0.66085082E-11
88 5 -0.10338442E-05 0.91064443E-06 -0.43638646E-04 0.73798452E-07
89 4 0.96204216E-03 0.40532412E-03 0.19644206E-01 -0.14823791E-03
90 3 -0.13915079 0.16410182E-01 -1.4347347 0.27725787E-01
91 2 2.2432332 0.80550987E-01 17.082538 -0.47694951
92 1 -6.4041654 0.53207822E-01 -41.597683 1.4049886
93 0 4.4519555 0.22662127E-02 26.083068  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.57_SHGC_0.25 37 1 VerySmooth 3.241 3.241 1.000 0.251    
2 RESWINDOW_U_0.57_SHGC_0.25 38 1 VerySmooth 3.241 3.241 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.2067E-002
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.2124E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.8863E-002
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.3195E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.6580E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.3071E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.9162E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.6591E-003
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.1412E-002
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.0270E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8966E-002
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.1771E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.3590E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.9647E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 3.2764E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.3236E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1793E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2218E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6986E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.3261E-003
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5885E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.3335E-003
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8719E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0154E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1793E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2218E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6986E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.3261E-003
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5885E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.3335E-003
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8719E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0154E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 39773.07746 39773.07746 2.89323 2.89323 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 21:50:00 28.74450 1.71587E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 8.70000 6.99286E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4250.11741 4250.11741 0.30923 0.30923 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2091.94973 2091.94973 8.97729E-002 8.97729E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3763.33028 3763.33028 0.27380 0.27380 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 29.74950 1.71606E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 847.80151 847.80151 3.63823E-002 9.17347E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3771.29661 3771.29661 0.27432 0.27432 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 29.74950 1.71606E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1789.98184 1789.98184 7.68148E-002 7.68148E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 2069.94785 2069.94785 0.15057 0.15057 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.08950 1.71632E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 969.38727 969.38727 4.16000E-002 5.77652E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 43833.86564 43833.86564 3.18886 3.18886 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.06600 1.71670E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2330.31099 2330.31099 0.10000 0.10000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 17954.06363 17954.06363 1.30735 1.30735 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 4868.72509 4868.72509 0.20893 0.67639 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 64865.26000 64865.26000 4.72049 4.72049 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 13541.61399 13541.61399 0.58112 1.89399 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 10001.34600 10001.34600 0.98046 0.98046 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 3431.38547 3431.38547 0.14812 0.14812 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10110.98887 10110.98887 0.99120 0.99120 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 3431.95314 3431.95314 0.14814 0.14814 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 55541.37214 55541.37214 5.44430 5.44430 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.20000 1.71672E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 19969.48875 19969.48875 0.86200 0.86200 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 66008.29678 66008.29678 6.47078 6.47078 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 19992.62465 19992.62465 0.86300 0.86300 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8971.41424 8971.41424 0.87949 0.87949 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 3429.80282 3429.80282 0.14805 0.14805 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9046.00288 9046.00288 0.88680 0.88680 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82150 1.71627E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 3430.37060 3430.37060 0.14807 0.14807 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 21263.95180 21263.95180 1.54680 1.54680 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 31.42450 1.71638E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 7700.94072 7700.94072 0.33048 0.47476 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2753.29385 2753.29385 0.26991 0.26991 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1027.29257 1027.29257 4.43438E-002 4.43438E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2779.65477 2779.65477 0.27250 0.27250 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1027.73638 1027.73638 4.43630E-002 4.43630E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11067.16392 11067.16392 1.08495 1.08495 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 33.20000 1.71672E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 4954.09228 4954.09228 0.21385 0.21385 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 8.70000 6.99286E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 30369.29864 30369.29864 2.21188 2.21188 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4635.47335 4635.47335 0.19893 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31752.88441 31752.88441 2.31262 2.31262 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4742.84066 4742.84066 0.20353 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30231.91911 30231.91911 2.20502 2.20502 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 32.59700 1.71661E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1030.29287 1030.29287 4.42099E-002 0.36735 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 8.70000 6.99286E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10809.11993 10809.11993 0.78629 0.78629 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13300 1.71671E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4823.75289 4823.75289 0.20701 0.20701 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 8.70000 6.99286E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 426812.00 21.98656 21.98656 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 70246.67 7.26540 7.26540 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 50573.62 16.89814 2.05125 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 19832.79 2.61994 2.05125 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.89323
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.52117
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.52184
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.31044E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.02127E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.52184
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8025.74205
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.02127E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 167.36302
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.30923
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16528
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16265
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.30520E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.58040E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.16265
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2949.55860
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.58040E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 70.55383
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27380
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21616
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14402
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57643
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.76259E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40602E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.14402
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1607.16518
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40602E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 35.58361
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27432
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.45623
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14429
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.35103E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.23154E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.14429
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2550.78386
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.23154E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 60.69885
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15057
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.47956
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.91982E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.94470E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21338E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.91982E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1386.96604
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21338E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.94141
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.18886
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.86481E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.67734
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.04311E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.77562E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.67734
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11174.13598
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.77562E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 236.24411
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30735
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11008
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.68766
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.46112E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.43142E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68766
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8494.57281
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.43142E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 190.48258
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.72049
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21117
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.48298
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56313
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.80421E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.33003E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.48298
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26633.66978
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.33003E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 586.99855
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.98046
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.98046
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.00193E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.27794E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68265
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75717E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.27794E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.98046
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3431.38520
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.00193E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 98.03892
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99120
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99120
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.00242E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.31127E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68265
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75416E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.31127E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99120
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3431.95288
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.00242E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 98.05514
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.44430
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.44430
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.74702E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.78138E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68358
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67526E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.78138E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.44430
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 19969.48793
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.74702E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 570.54984
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.47078
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.47078
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.74904E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.22303E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68276
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.86262E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.22303E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.47078
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 19992.62382
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.74904E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 571.21082
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.87949
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.87949
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.00054E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.96369E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68260
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78751E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.96369E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.87949
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3429.80255
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.00054E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 97.99371
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.88680
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.88680
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.00104E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.98662E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68260
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78529E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.98662E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.88680
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3430.37033
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.00104E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 98.00993
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.54680
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.76733
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.81362
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.96527E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04903E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.81362
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11991.09142
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04903E-004
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 275.98603
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.26991
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.26991
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.98720E-006
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 8.96934E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68269
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.73403E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.96934E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.26991
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1027.29250
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.98720E-006
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 29.35067
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27250
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.27250
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.99109E-006
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.04978E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68270
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.73175E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.04978E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27250
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1027.73631
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.99109E-006
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 29.36335
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.08495
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.08495
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.33406E-005
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.70679E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68251
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84106E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.70679E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.08495
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4954.09207
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.33406E-005
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 141.54252
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21188
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11426
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16345
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.33458E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.42239E-005
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16345
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10770.37568
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.42239E-005
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 233.79179
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.31262
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10928
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21644
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.48645E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.76074E-005
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21644
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11157.12881
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.76074E-005
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 241.97382
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.20502
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.42099E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.15984
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52600
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.06724E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.23342E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.15984
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7125.18390
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.23342E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 149.86484
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.78629
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39939
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52600
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41359
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.53943E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.12797E-005
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41359
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7004.64659
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.12797E-005
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 165.26572
318 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66691
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66691
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.18044
321 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66691
322 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.98656
323 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.98656
324 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.53064
326 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
334 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.98656
335 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
336 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.98656
337 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.87970
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.08896
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.36660E-002
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 829161.05346
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.37139E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.98656
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 63774.18730
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.57924E-004
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1183.41588
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.98656
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.37139E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.00806E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.57924E-004
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 33.20000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.94186
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.71672E-002
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 108329.82081
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.09822E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 5950.04693
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20536E-005
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 110.41113
367 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.09822E-003
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.53698E-004
370 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20536E-005
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.26213E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 5326.06937
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.11091E-003
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.25331
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.11091E-003
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 635.71344
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 241289.99854
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 241290.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.11091E-003
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.26213E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.91456
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.26213E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3687.41746
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.26213E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1140611.63127
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1143842.24000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 130.39802
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8067.20
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2962.50
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1614.90
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2562.21
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1393.19
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11231.10
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 8534.90
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 26762.43
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 3695.46
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 3696.07
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 21506.24
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 21531.15
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 3693.75
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 3694.36
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12046.53
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1106.34
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1106.82
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5335.30
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10823.96
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 11212.69
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7161.68
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7036.27
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 57095.44
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 5326.93


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 16541.59 14057.04 2484.55 0.85 2959.17 30.01
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 16714.14 14207.91 2506.23 0.85 2991.76 30.34
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 90518.93 77560.83 12958.10 0.86 16440.53 166.75
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 111179.34 93526.73 17652.61 0.84 19529.99 198.08
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 14916.40 12638.38 2278.02 0.85 2653.32 26.91
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 15034.67 12741.32 2293.34 0.85 2675.45 27.14
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4535.36 3863.02 672.34 0.85 814.96 8.27
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4576.95 3899.33 677.62 0.85 822.80 8.35
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 18573.50 15656.23 2917.27 0.84 3275.10 33.22
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 676240.28 444542.21 231698.07 0.66 96233.15 976.05
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 68061.43 43715.72 24345.72 0.64 9312.93 94.46


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.393 1.153   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 3.444 2.088   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.408 1.163   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 3.444 1.875   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.1798126838E-002 1.6884593216E-002 Pass Pass 1.2626440246E-003 2.3778167355E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 4.8751920240E-002 4.8510622391E-002 Pass Pass 9.2829117942E-003 1.2234041352E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 1.9332330978E-002 2.1309870680E-002 Pass Pass 2.1165231243E-003 3.2028077101E-003 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.0338853496E-002 9.5133495231E-003 Pass Pass 1.1913917283E-003 1.4289767079E-003 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 7.3407478880E-003 5.8862504100E-003 Pass Pass 9.1623533655E-004 9.0881665831E-004 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 6.3233240856E-002 0.2063833069 Pass Pass 1.5144513304E-002 4.3329574322E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 4.6442467860E-002 5.2415605466E-002 Pass Pass 9.3246831312E-003 1.7879699170E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.8094566291E-002 3.2438589826E-002 Pass Pass 2.9206550694E-003 4.6028294331E-003 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2640831461E-002 0.3323881879 Pass Pass 0.1433797680 0.8057835180 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 0.1058471619 0.2938149760 Pass Pass 8.5615135151E-002 0.2575826751 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.2383204847E-005 6.7612261960E-005 Pass Pass 3.1773096040E-002 4.0831205738E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 0.1155314349 0.2626811720 Pass Pass 8.9167638121E-002 0.2624744106 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2633502588E-002 0.3459800305 Pass Pass 0.1320326033 0.4659807650 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 0.1314947414 0.3684143846 Pass Pass 9.9452104176E-002 0.3702607694 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 8.9985596810E-003 7.1909131110E-003 Pass Pass 1.0289459621E-003 1.0705061556E-003 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2665136109E-002 0.3334390527 Pass Pass 0.1322281826 0.4777522361 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 0.1047753993 0.3054519508 Pass Pass 7.2980360923E-002 0.1661272079 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2665813196E-002 0.3324208896 Pass Pass 0.1583749228 0.7666186439 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 4.1469638287E-002 7.2606789611E-002 Pass Pass 6.0459217505E-003 1.7269790693E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.9019964491E-002 6.6869153298E-002 Pass Pass 6.1563400791E-003 1.9670155149E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 4.2334010667E-002 0.1139683711 Pass Pass 1.8416947643E-002 3.2610021243E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 2.1804659491E-002 1.6948818024E-002 Pass Pass 2.4071697835E-003 1.8724440696E-003 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3127.85 -111.1 -1443.7 -6150.3 15826.12 11248.92



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.153 1.393 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.153 1.393 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.153 1.393 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.153 1.393 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.153 1.393 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.163 1.408 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.163 1.408 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.163 1.408 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.163 1.408 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.163 1.408 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.786 3.444 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 1.786 3.444 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 1.786 3.444 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 1.786 3.444 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 1.786 3.444 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 1.786 3.444 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 1.786 3.444 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 1.786 3.444 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 1.786 3.444 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 1.786 3.444 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 1.786 3.444 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.979 3.444 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 1.627 3.444 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 1.979 3.444 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 1.627 3.444 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 1.627 3.444 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 1.627 3.444 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 1.979 3.444 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 1.979 3.444 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 1.979 3.444 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 1.627 3.444 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 3.241 0.251 0.276             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 3.241 0.251 0.276             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 3.241 0.251 0.276             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 3.241 0.251 0.276             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 3.241 0.251 0.276             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 3.241 0.251 0.276             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 3.241 0.251 0.276             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 3.241 0.251 0.276             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 3.241 0.251 0.276             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 3.241 0.251 0.276             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 3.241 0.251 0.276             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 3.241 0.251 0.276             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 3.241 0.251 0.276             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 3.241 0.251 0.276             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 3.241 0.251 0.276             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 3.241 0.251 0.276             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 3.241 0.251 0.276             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 3.241 0.251 0.276             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 3.241 0.251 0.276             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 3.241 0.251 0.276             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.57_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 3.241 0.251 0.276             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.57_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 3.241 0.251 0.276             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 3.241 0.251 0.276             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 3.241 0.251 0.276             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 3.241 0.251 0.276             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 3.241 0.251 0.276             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 3.241 0.251 0.276             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 3.241 0.251 0.276             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 3.241 0.251 0.276             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 3.241 0.251 0.276             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 3.241 0.251 0.276                      
North Total or Average             432.95 3.241 0.251 0.276                      
Non-North Total or Average             780.84 3.241 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.8143 1978.83 17441.96 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 161.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 11.3140 67.07 758.85 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.31
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 11.3140 77.67 878.75 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.46
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 5.7199 94.76 542.02 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 3.08
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 4.6285 78.04 361.20 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 3.98
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.0104 188.86 1890.59 LightsWired LTG_SCH_DINING 58.69 168.00 40.30 0.0000 Y 14.30
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.7639 1308.19 14081.18 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.69 0.0000 Y 110.18
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 8.2882 1863.81 15447.65 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.38
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 8.2882 1864.32 15451.87 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.41
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 7.1042 1557.62 11065.59 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 91.33
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 8.2882 39.02 323.42 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 8.2882 39.02 323.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 8.2882 220.77 1829.83 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 13.08
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 49.79 0.0000 Y 31.03
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 49.79 0.0000 Y 31.03
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.4097 103.30 1178.68 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.97
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 7.1042 412.12 2927.80 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 24.17
Interior Lighting Total       8.5566 11345.29 97077.49               457.22


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 12338.45 AstronomicalClock -   83.82 83.82 194.15
Exterior Lighting Total 12338.45           194.15



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 241290.00 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1143842.24 2.96 1144043.30 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11461.60 16541.59 14057.04 2484.55 0.85 - 2959.17 30.01
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11578.12 16714.14 14207.91 2506.23 0.85 - 2991.76 30.34
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 62287.35 90518.93 77560.83 12958.10 0.86 - 16440.53 166.75
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 77730.10 111179.34 93526.73 17652.61 0.84 - 19529.99 198.08
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10362.80 14916.40 12638.38 2278.02 0.85 - 2653.32 26.91
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10442.95 15034.67 12741.32 2293.34 0.85 - 2675.45 27.14
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3136.20 4535.36 3863.02 672.34 0.85 - 814.96 8.27
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3164.33 4576.95 3899.33 677.62 0.85 - 822.80 8.35
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 12961.09 18573.50 15656.23 2917.27 0.84 - 3275.10 33.22
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 829161.05 676240.28 444542.21 231698.07 0.66 - 96233.15 976.05
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 108329.82 68061.43 43715.72 24345.72 0.64 - 9312.93 94.46
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 8025.74 8067.20 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2949.56 2962.50 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1607.17 1614.90 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2550.78 2562.21 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1386.97 1393.19 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11174.14 11231.10 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 8494.57 8534.90 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 26633.67 26762.43 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3431.39 3695.46 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3431.95 3696.07 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 19969.49 21506.24 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 19992.62 21531.15 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3429.80 3693.75 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3430.37 3694.36 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 11991.09 12046.53 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1027.29 1106.34 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1027.74 1106.82 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 4954.09 5335.30 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10770.38 10823.96 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11157.13 11212.69 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7125.18 7161.68 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7004.65 7036.27 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 63774.19 57095.44 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 5950.05 5326.93 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.98 689.88 703.64 1.00 1.20 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.99 697.45 703.64 1.00 1.20 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.44 3830.80 703.64 1.00 0.97 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.47 4553.07 703.64 1.00 0.95 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.88 618.84 703.64 1.00 1.23 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.89 623.99 703.64 1.00 1.23 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 189.92 703.64 1.00 1.79 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 191.74 703.64 1.00 1.78 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.08 763.41 703.64 1.00 1.18 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1314.72 21.99 46615.35 2120.17 1.00 1.12 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.032621 5326.07 163269.44 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002111 635.71 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.032621 3687.42 113036.94 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 39773.08 39773.08 20.10 2.893 2.893 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 21:50:00 24.00 24.00 0.00911 28.74 0.01716 0.854 0.00
RETAIL_1_FLR_1 4250.12 4250.12 63.37 0.309 0.309 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00931 32.26 0.01717 0.079 0.00
RETAIL_2_FLR_1 3763.33 3763.33 48.45 0.274 0.274 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 24.00 24.00 0.00936 29.75 0.01716 0.092 0.00
MECH_FLR_1 3771.30 3771.30 22.96 0.274 0.274 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 24.00 24.00 0.00891 29.75 0.01716 0.000 0.00
STORAGE_FLR_1 2069.95 2069.95 21.84 0.151 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 24.00 24.00 0.00899 31.09 0.01716 0.058 0.00
LAUNDRY_FLR_1 43833.87 43833.87 561.69 3.189 3.189 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00857 33.07 0.01717 0.000 0.00
CAFE_FLR_1 17954.06 17954.06 95.06 1.307 1.307 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.99 0.01040 33.20 0.01717 0.676 0.00
LOBBY_FLR_1 64865.26 64865.26 49.58 4.720 4.720 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 23.99 0.01006 32.26 0.01717 1.894 0.00
ROOM_1_FLR_3 10001.35 10001.35 256.30 0.980 0.980 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00876 32.15 0.01717 0.062 0.00
ROOM_2_FLR_3 10110.99 10110.99 259.14 0.991 0.991 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00875 32.15 0.01717 0.062 0.00
ROOM_3_MULT19_FLR_3 55541.37 55541.37 2264.79 5.444 5.444 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 21.11 21.11 0.00868 33.20 0.01717 0.837 0.00
ROOM_4_MULT19_FLR_3 66008.30 66008.30 2690.86 6.471 6.471 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00886 31.70 0.01716 0.837 0.00
ROOM_5_FLR_3 8971.41 8971.41 229.91 0.879 0.879 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00879 30.82 0.01716 0.062 0.00
ROOM_6_FLR_3 9046.00 9046.00 231.85 0.887 0.887 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00879 30.82 0.01716 0.062 0.00
CORRIDOR_FLR_3 21263.95 21263.95 54.61 1.547 1.547 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.00 24.00 0.00952 31.42 0.01716 0.475 0.00
ROOM_1_FLR_6 2753.29 2753.29 70.56 0.270 0.270 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00873 32.26 0.01717 0.015 0.00
ROOM_2_FLR_6 2779.65 2779.65 71.24 0.272 0.272 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00873 32.15 0.01717 0.015 0.00
ROOM_3_MULT9_FLR_6 11067.16 11067.16 451.16 1.085 1.085 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 21.11 21.11 0.00884 33.20 0.01717 0.099 0.00
BANQUET_FLR_6 30369.30 30369.30 91.57 2.212 2.212 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01040 33.13 0.01717 1.188 0.00
DINING_FLR_6 31752.88 31752.88 95.74 2.313 2.313 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01032 33.13 0.01717 1.188 0.00
KITCHEN_FLR_6 30231.92 30231.92 292.65 2.205 2.205 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01015 32.60 0.01717 0.367 0.00
CORRIDOR_FLR_6 10809.12 10809.12 26.23 0.786 0.786 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00908 33.13 0.01717 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 21.25 0.00699 8.70 0.00699 0.854 0.00
RETAIL_1_FLR_1 2091.95 2091.95 31.19 0.090 0.090 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00790 8.70 0.00699 0.079 0.00
RETAIL_2_FLR_1 847.80 847.80 10.92 0.036 0.092 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00790 8.70 0.00699 0.092 0.00
MECH_FLR_1 1789.98 1789.98 10.90 0.077 0.077 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.000 0.00
STORAGE_FLR_1 969.39 969.39 10.23 0.042 0.058 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.058 0.00
LAUNDRY_FLR_1 2330.31 2330.31 29.86 0.100 0.100 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.000 0.00
CAFE_FLR_1 4868.73 4868.73 25.78 0.209 0.676 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00790 8.70 0.00699 0.676 0.00
LOBBY_FLR_1 13541.61 13541.61 10.35 0.581 1.894 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00790 8.70 0.00699 1.894 0.00
ROOM_1_FLR_3 3431.39 3431.39 87.93 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_2_FLR_3 3431.95 3431.95 87.96 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_3_MULT19_FLR_3 19969.49 19969.49 814.29 0.862 0.862 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00787 8.70 0.00699 0.837 0.00
ROOM_4_MULT19_FLR_3 19992.62 19992.62 815.01 0.863 0.863 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00787 8.70 0.00699 0.837 0.00
ROOM_5_FLR_3 3429.80 3429.80 87.89 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_6_FLR_3 3430.37 3430.37 87.92 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
CORRIDOR_FLR_3 7700.94 7700.94 19.78 0.330 0.475 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00792 8.70 0.00699 0.475 0.00
ROOM_1_FLR_6 1027.29 1027.29 26.33 0.044 0.044 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00788 8.70 0.00699 0.015 0.00
ROOM_2_FLR_6 1027.74 1027.74 26.34 0.044 0.044 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00788 8.70 0.00699 0.015 0.00
ROOM_3_MULT9_FLR_6 4954.09 4954.09 201.96 0.214 0.214 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00789 8.70 0.00699 0.099 0.00
BANQUET_FLR_6 4635.47 4635.47 13.98 0.199 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00793 8.70 0.00699 1.188 0.00
DINING_FLR_6 4742.84 4742.84 14.30 0.204 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00793 8.70 0.00699 1.188 0.00
KITCHEN_FLR_6 1030.29 1030.29 9.97 0.044 0.367 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00631 8.70 0.00699 0.367 0.00
CORRIDOR_FLR_6 4823.75 4823.75 11.70 0.207 0.207 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00794 8.70 0.00699 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.99 21.99 7.27 7.27 21.9866 11.6669 21.9866 0.5306 0.3000
FLR_3_DOAS 16.90 2.05 2.62 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 8025.742 8025.742 1.521837 0.00007021 167.363   1/21 00:10:00   1/21 00:10:00 8025.74 8025.74 1.521837 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 8070.85 8070.85
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2949.559 2949.559 0.162653 0.00002580 70.554 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2949.56 2949.56 0.162653 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789830 51.0079 2091.95 0.00 2965.00 2965.00
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1607.165 1607.165 0.144017 0.00001406 35.584 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1607.17 1607.17 0.144017 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00790258 51.0350 847.80 0.00 1615.91 1615.91
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2550.784 2550.784 0.144292 0.00002232 60.699 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2550.78 2550.78 0.144292 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789220 50.9688 1789.98 0.00 2564.33 2564.33
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1386.966 1386.966 0.079198 0.00001213 32.941 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1386.97 1386.97 0.079198 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788594 50.9289 969.39 0.00 1394.34 1394.34
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11174.136 11174.136 1.677342 0.00009776 236.244 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11174.14 11174.14 1.677342 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00788761 50.9398 2330.31 0.00 11236.63 11236.63
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 8494.573 8494.573 0.687664 0.00007431 190.483 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8494.57 8494.57 0.687664 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00790291 51.0372 4868.73 0.00 8540.55 8540.55
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 26633.670 26633.670 2.482977 0.00023300 586.999 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 26633.67 26633.67 2.482977 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00790043 51.0213 13541.61 0.00 26778.83 26778.83
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11461.596 -999.000 0.980456 0.00032779 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 11461.60 10778.41 0.980456 21.68 15.77 0.00875717 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00875717 56.0978 10001.35 0.00 11485.69 11267.99
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 3431.385 3431.385 0.148118 0.00003002 98.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 3431.39 3431.39 0.148118 21.11 14.76 0.00786255 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786255 50.4349 3431.39 0.00 3699.15 3699.15
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11578.118 -999.000 0.991205 0.00033113 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 11578.12 10895.60 0.991205 21.68 15.77 0.00875416 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00875416 56.0787 10110.99 0.00 11602.52 11391.37
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 3431.953 3431.953 0.148143 0.00003002 98.055 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 3431.95 3431.95 0.148143 21.11 14.76 0.00786258 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786258 50.4351 3431.95 0.00 3699.76 3699.76
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 62287.354 -999.000 5.444296 0.00178138 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown 7/21 15:00:00 62287.35 59708.41 5.444296 21.68 15.70 0.00867526 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00867526 55.5774 55541.37 0.00 62415.28 62415.28
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 19969.488 19969.488 0.862001 0.00017470 570.550 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 19969.49 19969.49 0.862001 21.11 14.76 0.00787326 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00787326 50.5025 19969.49 0.00 21527.81 21527.81
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 77730.100 -999.000 6.470775 0.00222303 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 77730.10 71353.08 6.470775 21.68 15.86 0.00886262 12.80 12.09 0.00850000 31.70 0.01716436 24.94 0.0000 21.11 0.00886262 56.7630 66008.30 0.00 77895.75 74417.66
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 19992.624 19992.624 0.863000 0.00017490 571.211 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 19992.62 19992.62 0.863000 21.11 14.76 0.00787335 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00787335 50.5031 19992.62 0.00 21552.75 21552.75
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10362.803 -999.000 0.879492 0.00029637 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 10362.80 9677.07 0.879492 21.68 15.79 0.00878751 12.80 12.09 0.00850000 30.82 0.01716268 24.71 0.0000 21.11 0.00878751 56.2895 8971.41 0.00 10384.06 10108.98
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 3429.803 3429.803 0.148050 0.00003001 97.994 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 3429.80 3429.80 0.148050 21.11 14.76 0.00786250 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786250 50.4346 3429.80 0.00 3697.44 3697.44
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10442.952 -999.000 0.886803 0.00029866 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 10442.95 9756.89 0.886803 21.68 15.79 0.00878529 12.80 12.09 0.00850000 30.82 0.01716268 24.71 0.0000 21.11 0.00878529 56.2754 9046.00 0.00 10464.41 10192.92
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 3430.370 3430.370 0.148074 0.00003001 98.010 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 3430.37 3430.37 0.148074 21.11 14.76 0.00786253 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786253 50.4347 3430.37 0.00 3698.06 3698.06
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 11991.091 11991.091 0.813617 0.00010490 275.986 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11991.09 11991.09 0.813617 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00792054 51.1495 7700.94 0.00 12055.39 12055.39
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3136.205 -999.000 0.269911 0.00008969 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3136.20 2965.17 0.269911 21.68 15.75 0.00873403 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00873403 55.9515 2753.29 0.00 3142.93 3142.93
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1027.293 1027.293 0.044344 0.00000899 29.351 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 1027.29 1027.29 0.044344 21.11 14.77 0.00788256 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788256 50.5616 1027.29 0.00 1107.46 1107.46
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3164.333 -999.000 0.272496 0.00009050 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 3164.33 2993.36 0.272496 21.68 15.75 0.00873175 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00873175 55.9371 2779.65 0.00 3171.13 3171.13
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1027.736 1027.736 0.044363 0.00000899 29.363 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 1027.74 1027.74 0.044363 21.11 14.77 0.00788261 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788261 50.5620 1027.74 0.00 1107.93 1107.93
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12961.090 -999.000 1.084947 0.00037068 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown 7/21 14:50:00 12961.09 11956.05 1.084947 21.68 15.84 0.00884106 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00884106 56.6278 11067.16 0.00 12989.19 12475.84
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 4954.092 4954.092 0.213847 0.00004334 141.543 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 4954.09 4954.09 0.213847 21.11 14.78 0.00788727 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788727 50.5914 4954.09 0.00 5340.68 5340.68
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10770.376 10770.376 1.163449 0.00009422 233.792 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10770.38 10770.38 1.163449 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00793249 51.2257 4635.47 0.00 10830.12 10830.12
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11157.129 11157.129 1.216437 0.00009761 241.974 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 11157.13 11157.13 1.216437 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00793391 51.2348 4742.84 0.00 11219.04 11219.04
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7125.184 7125.184 1.159842 0.00006233 149.865 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 7125.18 7125.18 1.159842 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00631301 40.8779 1030.29 0.00 7165.11 7165.11
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7004.647 7004.647 0.413587 0.00006128 165.266 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 7004.65 7004.65 0.413587 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00794254 51.2898 4823.75 0.00 7041.93 7041.93
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 829161.053 -999.000 21.986564 0.02371390 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 829161.05 474496.04 21.986564 28.88 21.91 0.01366603 11.09 11.09 0.00850000 33.20 0.01716721 25.32 53.0390 23.99 0.00967644 51.9542 301716.36 0.00 830392.00 475619.37
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 63774.187 63774.187 6.595969 0.00055792 1183.416 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 63774.19 63774.19 6.595969 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 176.7968 21.04 0.00769700 49.5866 48994.71 0.00 69133.13 69133.13
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 108329.821 -999.000 2.051317 0.00309822 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 108329.82 53987.08 2.051317 33.20 25.32 0.01716721 11.94 11.73 0.00850000 33.20 0.01716721 25.32 99.9965 21.11 0.00878028 56.2420 171326.19 0.00 108488.92 54853.91
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 5950.047 5950.047 0.615395 0.00005205 110.411 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 5950.05 5950.05 0.615395 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 333.3216 21.11 0.00787332 50.5029 60694.75 0.00 6450.03 6450.03



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 8025.742 8025.742 1.521837 0.00007021 167.363 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 3.2606 3.326181   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 8025.74 8025.74 1.0000 1.83037208 1.521837 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.07020553 60.00 32.22 27.78 0.000 8025.74 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 8070.85 8070.85 1.83037208 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2949.559 2949.559 0.162653 0.00002580 70.554 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.1983 1.222412 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2949.56 2949.56 1.0000 0.19562892 0.162653 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02580139 60.00 32.22 27.78 0.000 2949.56 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789830 21.00 0.00789830 51.0079 2091.95 0.00 2965.00 2965.00 0.19562892 16.60 13.15 0.00800000 36934.7 31.46 18.52 0.00800000 52091.0
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1607.165 1607.165 0.144017 0.00001406 35.584 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 0.6529 0.666072 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1607.17 1607.17 1.0000 0.17321453 0.144017 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01405875 60.00 32.22 27.78 0.000 1607.17 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00790258 21.00 0.00790258 51.0350 847.80 0.00 1615.91 1615.91 0.17321453 16.60 13.15 0.00800000 36934.7 25.75 16.58 0.00800000 46263.7
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2550.784 2550.784 0.144292 0.00002232 60.699 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.0363 1.057144 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2550.78 2550.78 1.0000 0.17354606 0.144292 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02231309 60.00 32.22 27.78 0.000 2550.78 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789220 21.00 0.00789220 50.9688 1789.98 0.00 2564.33 2564.33 0.17354606 16.60 13.15 0.00800000 36934.7 31.09 18.40 0.00800000 51710.8
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1386.966 1386.966 0.079198 0.00001213 32.941 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 0.5635 0.574813 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1386.97 1386.97 1.0000 0.09525470 0.079198 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01213255 60.00 32.22 27.78 0.000 1386.97 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788594 21.00 0.00788594 50.9289 969.39 0.00 1394.34 1394.34 0.09525470 16.60 13.15 0.00800000 36934.7 30.96 18.35 0.00800000 51572.7
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11174.136 11174.136 1.677342 0.00009776 236.244 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 4.5396 4.630998 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11174.14 11174.14 1.0000 2.01740410 1.677342 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09774624 60.00 32.22 27.78 0.000 11174.14 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00788761 21.00 0.00788761 50.9398 2330.31 0.00 11236.63 11236.63 2.01740410 16.60 13.15 0.00800000 36934.7 22.06 15.25 0.00800000 42504.6
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 8494.573 8494.573 0.687664 0.00007431 190.483 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 3.4510 3.520483 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8494.57 8494.57 1.0000 0.82708074 0.687664 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.07430665 60.00 32.22 27.78 0.000 8494.57 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00790291 21.00 0.00790291 51.0372 4868.73 0.00 8540.55 8540.55 0.82708074 16.60 13.15 0.00800000 36934.7 26.73 16.92 0.00800000 47260.9
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 26633.670 26633.670 2.482977 0.00023300 586.999 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 10.8203 11.038033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 26633.67 26633.67 1.0000 2.98637278 2.482977 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.23297919 60.00 32.22 27.78 0.000 26633.67 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00790043 21.00 0.00790043 51.0213 13541.61 0.00 26778.83 26778.83 2.98637278 16.60 13.15 0.00800000 36934.7 25.39 16.45 0.00800000 45901.7
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11461.596 -999.000 0.980456 0.00032779 -999.000 -999.0000 1.00000 1.00000 1021.1191 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.980456 1.17923254   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 1.0049 1.004845 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 11461.60 10778.41 1.0000 1.17923254 0.980456 21.68 15.77 0.00875717 44041.7 12.80 12.09 0.00850000 34322.2 0.32776065 6.70 15.03 8.33 0.000 11461.60 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00875717 21.11 0.00875717 56.0978 10001.35 0.00 11485.69 11267.99 1.17923254 21.68 15.78 0.00875717 44041.7 12.32 12.09 0.00868403 34301.8
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 3431.385 3431.385 0.148118 0.00003002 98.039 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.980456 1.17923254   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.3940 1.422100 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 3431.39 3431.39 1.0000 0.17814762 0.148118 21.11 14.76 0.00786255 41185.4 40.00 21.17 0.00800000 60796.0 0.03001619 60.00 32.22 27.78 0.000 3431.39 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786255 21.11 0.00786255 50.4349 3431.39 0.00 3699.15 3699.15 0.17814762 16.60 13.02 0.00786255 36586.7 36.97 20.17 0.00786255 57351.3
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11578.118 -999.000 0.991205 0.00033113 -999.000 -999.0000 1.00000 1.00000 1021.1135 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.991205 1.19216051   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 1.0151 1.015061 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 11578.12 10895.60 1.0000 1.19216051 0.991205 21.68 15.77 0.00875416 44034.1 12.80 12.09 0.00850000 34322.2 0.33109274 6.70 15.03 8.33 0.000 11578.12 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00875416 21.11 0.00875416 56.0787 10110.99 0.00 11602.52 11391.37 1.19216051 21.68 15.78 0.00875416 44034.1 12.32 12.09 0.00868398 34301.7
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 3431.953 3431.953 0.148143 0.00003002 98.055 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.991205 1.19216051   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.3943 1.422335 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 3431.95 3431.95 1.0000 0.17817709 0.148143 21.11 14.76 0.00786258 41185.4 40.00 21.17 0.00800000 60796.0 0.03002116 60.00 32.22 27.78 0.000 3431.95 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786258 21.11 0.00786258 50.4351 3431.95 0.00 3699.76 3699.76 0.17817709 16.60 13.02 0.00786258 36586.8 36.97 20.17 0.00786258 57351.3
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 62287.354 -999.000 5.444296 0.00178138 -999.000 -999.0000 1.00000 1.00000 1020.9669 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.444296 6.54806712   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 5.4609 5.460771 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown unknown unknown 7/21 15:00:00 Sensible 62287.35 59708.41 1.0000 6.54806712 5.444296 21.68 15.70 0.00867526 43834.5 12.80 12.09 0.00850000 34322.2 1.78119545 6.70 15.03 8.33 0.000 62287.35 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00867526 21.11 0.00867526 55.5774 55541.37 0.00 62415.28 62415.28 6.54806712 21.68 15.71 0.00867526 43834.5 12.35 12.09 0.00867526 34302.7
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 19969.488 19969.488 0.862001 0.00017470 570.550 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.444296 6.54806712   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 8.1129 8.276136 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 19969.49 19969.49 1.0000 1.03676219 0.862001 21.11 14.76 0.00787326 41212.6 40.00 21.17 0.00800000 60796.0 0.17468397 60.00 32.22 27.78 0.000 19969.49 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00787326 21.11 0.00787326 50.5025 19969.49 0.00 21527.81 21527.81 1.03676219 16.60 13.03 0.00787326 36613.8 36.97 20.17 0.00787326 57378.3
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 77730.100 -999.000 6.470775 0.00222303 -999.000 -999.0000 1.00000 1.00000 1021.3152 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.470775 7.78265336   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 6.8148 6.814646 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 77730.10 71353.08 1.0000 7.78265336 6.470775 21.68 15.86 0.00886262 44309.8 12.80 12.09 0.00850000 34322.2 2.22280273 6.70 15.03 8.33 0.000 77730.10 31.70 0.01716436 24.94 0.00000000 0.0000 21.11 0.00886262 21.11 0.00886262 56.7630 66008.30 0.00 77895.75 74417.66 7.78265336 21.68 15.87 0.00886262 44309.8 12.32 12.09 0.00868555 34300.9
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 19992.624 19992.624 0.863000 0.00017490 571.211 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.470775 7.78265336   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 8.1223 8.285724 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 19992.62 19992.62 1.0000 1.03796334 0.863000 21.11 14.76 0.00787335 41212.9 40.00 21.17 0.00800000 60796.0 0.17488635 60.00 32.22 27.78 0.000 19992.62 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00787335 21.11 0.00787335 50.5031 19992.62 0.00 21552.75 21552.75 1.03796334 16.60 13.03 0.00787335 36614.1 36.97 20.17 0.00787335 57378.6
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10362.803 -999.000 0.879492 0.00029637 -999.000 -999.0000 1.00000 1.00000 1021.1755 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.879492 1.05779893   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 0.9085 0.908513 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 10362.80 9677.07 1.0000 1.05779893 0.879492 21.68 15.79 0.00878751 44118.8 12.80 12.09 0.00850000 34322.2 0.29633908 6.70 15.03 8.33 0.000 10362.80 30.82 0.01716268 24.71 0.00000000 0.0000 21.11 0.00878751 21.11 0.00878751 56.2895 8971.41 0.00 10384.06 10108.98 1.05779893 21.68 15.81 0.00878751 44118.8 12.32 12.09 0.00868447 34302.1
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 3429.803 3429.803 0.148050 0.00003001 97.994 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.879492 1.05779893   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.3934 1.421444 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 3429.80 3429.80 1.0000 0.17806545 0.148050 21.11 14.76 0.00786250 41185.2 40.00 21.17 0.00800000 60796.0 0.03000235 60.00 32.22 27.78 0.000 3429.80 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786250 21.11 0.00786250 50.4346 3429.80 0.00 3697.44 3697.44 0.17806545 16.60 13.02 0.00786250 36586.6 36.97 20.17 0.00786250 57351.1
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10442.952 -999.000 0.886803 0.00029866 -999.000 -999.0000 1.00000 1.00000 1021.1714 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.886803 1.06659301   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 0.9156 0.915540 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 10442.95 9756.89 1.0000 1.06659301 0.886803 21.68 15.79 0.00878529 44113.1 12.80 12.09 0.00850000 34322.2 0.29863107 6.70 15.03 8.33 0.000 10442.95 30.82 0.01716268 24.71 0.00000000 0.0000 21.11 0.00878529 21.11 0.00878529 56.2754 9046.00 0.00 10464.41 10192.92 1.06659301 21.68 15.81 0.00878529 44113.1 12.32 12.09 0.00868444 34302.1
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 3430.370 3430.370 0.148074 0.00003001 98.010 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.886803 1.06659301   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 1.3936 1.421679 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 3430.37 3430.37 1.0000 0.17809493 0.148074 21.11 14.76 0.00786253 41185.3 40.00 21.17 0.00800000 60796.0 0.03000731 60.00 32.22 27.78 0.000 3430.37 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786253 21.11 0.00786253 50.4347 3430.37 0.00 3698.06 3698.06 0.17809493 16.60 13.02 0.00786253 36586.7 36.97 20.17 0.00786253 57351.2
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 11991.091 11991.091 0.813617 0.00010490 275.986 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 4.8715 4.969577 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11991.09 11991.09 1.0000 0.97856835 0.813617 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.10489260 60.00 32.22 27.78 0.000 11991.09 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00792054 21.00 0.00792054 51.1495 7700.94 0.00 12055.39 12055.39 0.97856835 16.60 13.15 0.00800000 36934.7 28.68 17.59 0.00800000 49254.1
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3136.205 -999.000 0.269911 0.00008969 -999.000 -999.0000 1.00000 1.00000 1021.0761 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.269911 0.32463307   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 0.2750 0.274953 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3136.20 2965.17 1.0000 0.32463307 0.269911 21.68 15.75 0.00873403 43983.0 12.80 12.09 0.00850000 34322.2 0.08968423 6.70 15.03 8.33 0.000 3136.20 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00873403 21.11 0.00873403 55.9515 2753.29 0.00 3142.93 3142.93 0.32463307 21.68 15.76 0.00873403 43983.0 12.20 12.09 0.00873403 34301.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1027.293 1027.293 0.044344 0.00000899 29.351 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.269911 0.32463307   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 0.4174 0.425750 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 1027.29 1027.29 1.0000 0.05333406 0.044344 21.11 14.77 0.00788256 41236.2 40.00 21.17 0.00800000 60796.0 0.00898629 60.00 32.22 27.78 0.000 1027.29 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788256 21.11 0.00788256 50.5616 1027.29 0.00 1107.46 1107.46 0.05333406 16.60 13.04 0.00788256 36637.4 36.97 20.18 0.00788256 57401.9
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3164.333 -999.000 0.272496 0.00009050 -999.000 -999.0000 1.00000 1.00000 1021.0719 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.272496 0.32774109   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 0.2774 0.277419 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 3164.33 2993.36 1.0000 0.32774109 0.272496 21.68 15.75 0.00873175 43977.2 12.80 12.09 0.00850000 34322.2 0.09048860 6.70 15.03 8.33 0.000 3164.33 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00873175 21.11 0.00873175 55.9371 2779.65 0.00 3171.13 3171.13 0.32774109 21.68 15.76 0.00873175 43977.2 12.21 12.09 0.00873175 34301.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1027.736 1027.736 0.044363 0.00000899 29.363 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.272496 0.32774109   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 0.4175 0.425934 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 1027.74 1027.74 1.0000 0.05335710 0.044363 21.11 14.77 0.00788261 41236.3 40.00 21.17 0.00800000 60796.0 0.00899017 60.00 32.22 27.78 0.000 1027.74 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788261 21.11 0.00788261 50.5620 1027.74 0.00 1107.93 1107.93 0.05335710 16.60 13.04 0.00788261 36637.5 36.97 20.18 0.00788261 57402.1
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12961.090 -999.000 1.084947 0.00037068 -999.000 -999.0000 1.00000 1.00000 1021.2751 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.084947 1.30490791   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 1.1363 1.136307 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown unknown unknown 7/21 14:50:00 Sensible 12961.09 11956.05 1.0000 1.30490791 1.084947 21.68 15.84 0.00884106 44254.8 12.80 12.09 0.00850000 34322.2 0.37064079 6.70 15.03 8.33 0.000 12961.09 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00884106 21.11 0.00884106 56.6278 11067.16 0.00 12989.19 12475.84 1.30490791 21.68 15.85 0.00884106 44254.8 12.32 12.09 0.00868519 34300.7
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 4954.092 4954.092 0.213847 0.00004334 141.543 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.084947 1.30490791   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 2.0127 2.053169 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 4954.09 4954.09 1.0000 0.25720250 0.213847 21.11 14.78 0.00788727 41248.2 40.00 21.17 0.00800000 60796.0 0.04333614 60.00 32.22 27.78 0.000 4954.09 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788727 21.11 0.00788727 50.5914 4954.09 0.00 5340.68 5340.68 0.25720250 16.60 13.04 0.00788727 36649.3 36.97 20.18 0.00788727 57413.8
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10770.376 10770.376 1.163449 0.00009422 233.792 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 4.3756 4.463664 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10770.38 10770.38 1.0000 1.39932512 1.163449 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09421433 60.00 32.22 27.78 0.000 10770.38 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00793249 21.00 0.00793249 51.2257 4635.47 0.00 10830.12 10830.12 1.39932512 16.60 13.15 0.00800000 36934.7 24.19 16.02 0.00800000 44674.3
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 11157.129 11157.129 1.216437 0.00009761 241.974 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 4.5327 4.623950 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 11157.13 11157.13 1.0000 1.46305572 1.216437 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09759747 60.00 32.22 27.78 0.000 11157.13 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00793391 21.00 0.00793391 51.2348 4742.84 0.00 11219.04 11219.04 1.46305572 16.60 13.15 0.00800000 36934.7 24.12 16.00 0.00800000 44603.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7125.184 7125.184 1.159842 0.00006233 149.865 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 2.8947 2.952955 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 7125.18 7125.18 1.0000 1.39498714 1.159842 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06232786 60.00 32.22 27.78 0.000 7125.18 8.70 0.00699286 8.70 0.00000000 0.0000 19.94 0.00631301 21.00 0.00631301 40.8779 1030.29 0.00 7165.11 7165.11 1.39498714 16.60 13.15 0.00800000 36934.7 21.64 15.09 0.00800000 42071.1
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7004.647 7004.647 0.413587 0.00006128 165.266 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 2.8457 2.902999 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 7004.65 7004.65 1.0000 0.49743724 0.413587 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06127345 60.00 32.22 27.78 0.000 7004.65 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00794254 21.00 0.00794254 51.2898 4823.75 0.00 7041.93 7041.93 0.49743724 16.60 13.15 0.00800000 36934.7 30.48 18.20 0.00800000 51091.1
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 829161.053 -999.000 21.986564 0.02371390 -999.000 -999.0000 1.00000 1.00000 1030.2445 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.986564 26.44409703   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 72.6944 72.694424 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 829161.05 474496.04 1.0000 26.44409703 21.986564 28.88 21.91 0.01366603 63931.1 11.09 11.09 0.00850000 32575.8 23.71148210 6.70 15.03 8.33 46615.346 782545.71 33.20 0.01716721 25.32 11.66146000 53.0390 23.99 0.00970247 23.99 0.00967644 51.9542 301716.36 0.00 830392.00 475619.37 26.44409703 28.88 21.93 0.01366603 63931.1 11.42 11.37 0.00834683 32529.3
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 63774.187 63774.187 6.595969 0.00055792 1183.416 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.986564 26.44409703   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 25.9091 26.430514 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 63774.19 63774.19 1.0000 7.93322911 6.595969 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.55786750 60.00 32.22 27.78 0.000 63774.19 8.70 0.00699286 8.70 11.66146000 176.7968 18.49 0.00772935 21.04 0.00769700 49.5866 48994.71 0.00 69133.13 69133.13 7.93322911 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 108329.821 -999.000 2.051317 0.00309822 -999.000 -999.0000 1.00000 1.00000 1036.7530 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 32.61802055 15.03 6.70 8.33 1140611.63 9.4975 9.497520 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 Sensible 108329.82 53987.08 1.0000 2.46719911 2.051317 33.20 25.32 0.01716721 77354.4 11.94 11.73 0.00850000 33446.3 3.09790311 6.70 15.03 8.33 2195.006 106134.81 33.20 0.01716721 25.32 2.05124512 99.9965 21.11 0.00878837 21.11 0.00878028 56.2420 171326.19 0.00 108488.92 54853.91 2.46719911 33.20 25.34 0.01716721 77354.4 11.75 11.72 0.00855008 33381.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 5950.047 5950.047 0.615395 0.00005205 110.411 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 2.11069483 54.44 82.22 27.78 246146.06 2.4173 2.465932 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 5950.05 5950.05 1.0000 0.74015973 0.615395 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.05204830 60.00 32.22 27.78 0.000 5950.05 8.70 0.00699286 8.70 2.05124512 333.3216 21.11 0.00787233 21.11 0.00787332 50.5029 60694.75 0.00 6450.03 6450.03 0.74015973 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2.67 7895.50 0.00
RETAIL_1_FLR_1 3483.17 4014.67 6.00
RETAIL_2_FLR_1 1035.83 6388.67 0.00
MECH_FLR_1 320.00 7018.17 4.50
STORAGE_FLR_1 80.17 7555.50 1.17
LAUNDRY_FLR_1 6661.67 2224.83 1687.17
CAFE_FLR_1 5227.67 2467.50 79.00
LOBBY_FLR_1 2542.50 4655.33 0.00
ROOM_1_FLR_3 31.17 7824.17 30.83
ROOM_2_FLR_3 423.17 7790.33 365.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 279.00 8751.50 279.00
ROOM_5_FLR_3 30.50 7658.17 30.50
ROOM_6_FLR_3 438.17 7655.50 370.33
CORRIDOR_FLR_3 0.00 8670.50 0.00
ROOM_1_FLR_6 376.83 7336.83 100.00
ROOM_2_FLR_6 832.50 7264.00 537.33
ROOM_3_MULT9_FLR_6 248.50 7497.83 56.33
BANQUET_FLR_6 6304.17 1479.00 14.50
DINING_FLR_6 7043.33 931.67 0.00
KITCHEN_FLR_6 8281.33 6606.00 6348.00
CORRIDOR_FLR_6 848.50 6479.50 3.50
Facility 8578.50 8760.00 6465.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.67 0.00 0.67
ROOM_2_FLR_3 0.00 1.50 0.00 1.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 8.33 0.00 8.33
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 14.00 0.00 14.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 9.33 0.00 9.33
ROOM_2_FLR_6 0.00 6.67 0.00 6.67
ROOM_3_MULT9_FLR_6 0.00 37.50 0.00 37.50
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 59.83 0.00 59.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.130 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.262 0.131 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.680 0.044 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.795 0.049 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.755 0.049 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 20.401 0.140 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 3.362 0.103 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.727 0.042 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.355 0.169 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.355 0.169 0.000 0.067
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.403 0.075 0.000 0.105
ROOM_5_FLR_3 0.95 1.50 118.94 0.355 0.169 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.355 0.169 0.000 0.066
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.614 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.355 0.169 0.000 0.079
ROOM_2_FLR_6 0.95 1.50 118.93 0.355 0.169 0.000 0.080
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.403 0.138 0.000 0.125
BANQUET_FLR_6 145.01 249.90 1010.89 4.387 0.049 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.629 0.049 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 17.829 0.141 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.182 0.034 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.752 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.644 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.154 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.529 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.503 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 13.578 0.002 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.936 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.256 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.409 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 3.852 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.018 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 10.141 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.806 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 46971085.03 0.00 46971085.03 0.00 46971085.03 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 5171039.00 0.00 5171039.00 299317.48 5470356.49 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 4452674.56 0.00 4452674.56 115536.93 4568211.48 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 4458559.70 0.00 4458559.70 273060.66 4731620.36 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 2444515.41 0.00 2444515.41 157540.96 2602056.37 1821682.01 71.92 34.94 8653.14 0.00
LAUNDRY_FLR_1 54472809.55 0.00 54472809.55 372850.38 54845659.93 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 21589653.39 0.00 21589653.39 661658.24 22251311.63 21330615.53 1004.62 523.58 7231.80 0.00
LOBBY_FLR_1 76932541.86 0.00 76932541.86 1890508.72 78823050.58 59728886.00 5.08 9.83 8745.08 0.00
ROOM_1_FLR_3 1460156.71 66734.97 1526891.69 173731.82 1700623.51 1946875.62 2190.00 5694.33 875.67 0.00
ROOM_2_FLR_3 1459985.63 68134.26 1528119.90 173718.57 1701838.47 1946647.51 2190.00 5694.48 875.52 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 48473.13 1148385.10 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19803829.30 67615.46 19871444.75 48486.38 19919931.13 26405105.73 2190.00 5780.23 789.77 0.00
ROOM_5_FLR_3 1460156.71 66828.81 1526985.53 173731.82 1700717.35 1946875.62 2190.00 5694.33 875.67 0.00
ROOM_6_FLR_3 1459985.63 68089.69 1528075.33 173718.57 1701793.90 1946647.51 2190.00 5694.33 875.67 0.00
CORRIDOR_FLR_3 25112062.11 0.00 25112062.11 210076.73 25322138.84 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 80865.73 445904.91 173766.55 619671.45 486718.90 2021.76 5687.66 1050.58 0.00
ROOM_2_FLR_6 364996.41 82348.63 447345.03 173753.29 621098.32 486661.88 2026.12 5693.41 1040.47 0.00
ROOM_3_MULT9_FLR_6 2345190.31 81029.95 2426220.26 88905.05 2515125.30 3126920.42 2190.00 5683.83 886.17 0.00
BANQUET_FLR_6 38009440.46 0.00 38009440.46 424294.23 38433734.69 37458366.31 5725.65 405.31 2629.05 0.00
DINING_FLR_6 40096232.37 0.00 40096232.37 424294.23 40520526.60 37458366.31 70.41 68.93 8620.66 0.00
KITCHEN_FLR_6 48105488.57 0.00 48105488.57 379841.71 48485330.28 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12790733.07 0.00 12790733.07 371767.87 13162500.94 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 7110409.47 0.21E+10 17507169.38 0.21E+10 0.43E+10 8760.00 6276.96 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.4894 0.0000 1.4894 0.0000 1.4894 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1640 0.0000 0.1640 0.0095 0.1735 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1412 0.0000 0.1412 0.0037 0.1449 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.1414 0.0000 0.1414 0.0087 0.1500 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0775 0.0000 0.0775 0.0050 0.0825 0.0578 71.92 34.94 8653.14
LAUNDRY_FLR_1 1.7273 0.0000 1.7273 0.0118 1.7391 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.6846 0.0000 0.6846 0.0210 0.7056 0.6764 1004.62 523.58 7231.80
LOBBY_FLR_1 2.4395 0.0000 2.4395 0.0599 2.4995 1.8940 5.08 9.83 8745.08
ROOM_1_FLR_3 0.0463 0.0021 0.0484 0.0055 0.0539 0.0617 2190.00 5694.33 875.67
ROOM_2_FLR_3 0.0463 0.0022 0.0485 0.0055 0.0540 0.0617 2190.00 5694.48 875.52
ROOM_4_MULT19_FLR_3 0.6280 0.0021 0.6301 0.0015 0.6317 0.8373 2190.00 5780.23 789.77
ROOM_5_FLR_3 0.0463 0.0021 0.0484 0.0055 0.0539 0.0617 2190.00 5694.33 875.67
ROOM_6_FLR_3 0.0463 0.0022 0.0485 0.0055 0.0540 0.0617 2190.00 5694.33 875.67
CORRIDOR_FLR_3 0.7963 0.0000 0.7963 0.0067 0.8030 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0026 0.0141 0.0055 0.0196 0.0154 2021.76 5687.66 1050.58
ROOM_2_FLR_6 0.0116 0.0026 0.0142 0.0055 0.0197 0.0154 2026.12 5693.41 1040.47
ROOM_3_MULT9_FLR_6 0.0744 0.0026 0.0769 0.0028 0.0798 0.0992 2190.00 5683.83 886.17
BANQUET_FLR_6 1.2053 0.0000 1.2053 0.0135 1.2187 1.1878 5725.65 405.31 2629.05
DINING_FLR_6 1.2714 0.0000 1.2714 0.0135 1.2849 1.1878 70.41 68.93 8620.66
KITCHEN_FLR_6 1.5254 0.0000 1.5254 0.0120 1.5375 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.4056 0.0000 0.4056 0.0118 0.4174 0.1256 0.00 0.00 8760.00
Total Facility 63.6172 0.2255 63.8427 0.4383 64.2810 73.9670 8760.00 6276.96 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.55E+09 0.00 0.55E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 43135961.56 581647.50 43717609.05 64690340.46 8750.43 9.40 0.17 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.4587 0.0000 17.4587 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 1.3678 0.0184 1.3863 2.0513 8750.43 9.40 0.17


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 8760.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 17.4587 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.7278 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1333
Defaulted Fields 1181
Fields with Defaults 3997
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
Electricity:Building 2448.25 31501.02 02-JAN-02:10 151313.73 02-JAN-20:10
Electricity:Zone:BASEMENT 304.40 3493.55 02-JAN-02:10 22822.84 02-JAN-20:10
Electricity:SpaceType:GENERAL 2441.16 31359.87 02-JAN-02:10 151072.40 02-JAN-20:10
InteriorLights:Electricity 782.98 7157.90 02-JAN-02:10 64632.59 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 782.98 7157.90 02-JAN-02:10 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity 782.98 7157.90 02-JAN-02:10 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 782.98 7157.90 02-JAN-02:10 64632.59 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 17.49 210.74 02-JAN-02:10 1283.20 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 20.26 244.03 02-JAN-02:10 1485.95 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.68 78.96 02-JAN-02:10 493.99 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.91 998.82 02-JAN-02:10 4897.88 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 28.64 388.01 01-JAN-13:10 2666.80 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 14.30 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 14.30 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.18 3167.50 02-JAN-02:10 19534.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.19 1056.09 02-JAN-02:10 9504.80 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.19 1056.09 02-JAN-02:10 9504.80 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 305.38 4267.82 01-JAN-02:10 22404.45 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 305.47 4268.99 01-JAN-02:10 22410.58 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.93 64.34 01-JAN-02:10 359.63 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.93 64.34 01-JAN-02:10 359.59 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.17 505.54 01-JAN-02:10 2653.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 206.89 2581.30 02-JAN-02:10 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.03 332.00 02-JAN-02:10 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.03 332.00 02-JAN-02:10 2988.03 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 206.89 2581.30 02-JAN-02:10 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 31.03 332.00 02-JAN-02:10 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 31.03 332.00 02-JAN-02:10 2988.03 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 453.81 6249.79 02-JAN-02:10 18934.39 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorEquipment:Electricity 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.26 1141.33 03-FEB-23:30 3255.79 22-DEC-07:30
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 3919.21 2600.06 25-JAN-04:00 218025.76 28-JUL-15:20
LowTempRefrigeration:Refrigeration:Electricity 20.33 0.00 01-JAN-11:10 1891.91 23-JUL-10:50
MedTempRefrigeration:Refrigeration:Electricity 34.84 942.28 25-JAN-03:30 1193.63 28-AUG-13:10
Fans:Electricity 466.32 10384.25 04-FEB-08:10 25804.80 28-JUL-18:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 783.53 19627.02 16-MAR-07:10 36791.97 28-JUL-18:20
ExteriorEquipment:Electricity 640.80 9445.83 02-JAN-02:20 39169.97 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.77 381.02 02-JAN-02:20 1291.59 02-JAN-21:10
ElectricityPurchased:Facility 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
ElectricityPurchased:Plant 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
Cogeneration:ElectricityPurchased 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
General:Cogeneration:ElectricityPurchased 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
ElectricityNet:Plant 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
Cogeneration:ElectricityNet 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
General:Cogeneration:ElectricityNet 7964.17 77361.06 25-JAN-04:00 431924.87 27-JUL-19:10
General:Fans:Electricity 466.32 10384.25 04-FEB-08:10 25804.80 28-JUL-18:20
ExteriorLights:Electricity 194.15 0.00 01-JAN-07:20 12338.45 01-JAN-00:10
General:ExteriorLights:Electricity 194.15 0.00 01-JAN-07:20 12338.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 295.44 8417.13 01-JAN-06:10 9938.94 04-APR-09:00
General:HeatRecovery:Electricity 295.44 8417.13 01-JAN-06:10 9938.94 04-APR-09:00
WaterSystems:Electricity 90.76 1086.72 01-SEP-00:20 4738.81 14-DEC-07:10
Water Heater:WaterSystems:Electricity 90.76 1086.72 01-SEP-00:20 4738.81 14-DEC-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 3640.07 0.00 25-JAN-04:00 209234.36 28-JUL-15:20
General:Cooling:Electricity 3640.07 0.00 25-JAN-04:00 209234.36 28-JUL-15:20
Pumps:Electricity 133.21 123.72 20-MAR-08:00 5129.86 25-DEC-23:00
General:Pumps:Electricity 133.21 123.72 20-MAR-08:00 5129.86 25-DEC-23:00
WIRED_LTG_ELECTRICITY 27.56 0.00 01-JAN-00:10 2275.07 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4393.01 31318.07 29-JUL-01:10 322552.83 30-JAN-18:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2604.18 15908.90 01-JAN-11:10 231493.51 03-FEB-17:30
WaterSystems:NaturalGas 2541.67 15908.90 01-JAN-11:10 219783.77 18-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2541.67 15908.90 01-JAN-11:10 219783.77 18-JAN-21:20
Heating:NaturalGas 62.51 0.00 01-JAN-00:10 46790.58 04-FEB-06:00
Boiler:Heating:NaturalGas 62.51 0.00 01-JAN-00:10 46790.58 04-FEB-06:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 11859.03 0.00 25-JAN-04:00 698844.29 25-DEC-23:00
PlantLoopCoolingDemand:HVAC 11859.03 0.00 25-JAN-04:00 698844.29 25-DEC-23:00
CoolingCoils:PlantLoopCoolingDemand 11859.03 0.00 25-JAN-04:00 698844.29 25-DEC-23:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 09-JAN-21:50
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 50638.21 179545.02 21-MAR-07:50 2796964.56 13-JUL-18:20
EnergyTransfer:Building 6712.06 109559.96 20-MAR-10:10 343772.29 29-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 749.97 10745.18 04-FEB-04:00 35691.88 23-JUL-10:50
Refrigeration:EnergyTransfer 186.21 4031.61 25-JAN-03:30 10340.53 18-JUL-07:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.11 2015.81 25-JAN-03:30 5170.27 18-JUL-07:20
General:Refrigeration:EnergyTransfer 93.11 2015.81 25-JAN-03:30 5170.27 18-JUL-07:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.11 2015.81 25-JAN-03:30 5170.27 18-JUL-07:20
EnergyTransfer:Plant 28237.63 28004.04 25-JAN-04:00 1615692.96 25-DEC-23:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.69 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 71.41 1776.85 25-JAN-03:30 2530.88 28-AUG-13:10
EnergyTransfer:Zone:BASEMENT 584.88 15750.72 20-MAR-14:00 20891.25 22-SEP-21:00
Heating:EnergyTransfer 1.16 0.00 01-JAN-00:10 9858.72 04-FEB-07:00
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 1.16 0.00 01-JAN-00:10 9858.72 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 6617.79 106465.05 04-FEB-07:20 340178.06 29-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 584.88 15750.72 20-MAR-14:00 20891.25 22-SEP-21:00
General:Cooling:EnergyTransfer 6617.79 106465.05 04-FEB-07:20 340178.06 29-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 584.88 15750.72 20-MAR-14:00 20891.25 22-SEP-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 63.95 1.56 16-MAR-06:40 3814.74 25-OCT-14:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 417.43 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 417.43 04-FEB-07:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 63.94 0.00 04-FEB-04:30 3814.74 25-OCT-14:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 63.94 0.00 04-FEB-04:30 3814.74 25-OCT-14:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 53.99 743.69 04-FEB-10:10 2469.87 28-JUL-20:50
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 53.99 743.69 04-FEB-10:10 2469.87 28-JUL-20:50
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 53.99 743.69 04-FEB-10:10 2469.87 28-JUL-20:50
EnergyTransfer:Zone:MECH_FLR_1 52.20 4.11 04-FEB-11:20 2512.83 29-JUL-20:30
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 24.60 04-FEB-10:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 24.60 04-FEB-10:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 52.20 0.00 04-FEB-08:00 2512.83 29-JUL-20:30
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 52.20 0.00 04-FEB-08:00 2512.83 29-JUL-20:30
EnergyTransfer:Zone:STORAGE_FLR_1 28.45 2.09 04-FEB-08:10 1188.46 29-JUL-19:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 20.41 04-FEB-08:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 20.41 04-FEB-08:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 28.45 0.00 04-FEB-07:10 1188.46 29-JUL-19:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 28.45 0.00 04-FEB-07:10 1188.46 29-JUL-19:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 611.10 8841.82 04-FEB-06:00 36553.14 28-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 611.10 8841.82 04-FEB-06:00 36553.14 28-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 611.10 8841.82 04-FEB-06:00 36553.14 28-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 280.32 2530.62 16-MAR-08:10 13732.99 25-OCT-15:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 280.32 2530.62 16-MAR-08:10 13732.99 25-OCT-15:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 280.32 2530.62 16-MAR-08:10 13732.99 25-OCT-15:10
EnergyTransfer:Zone:LOBBY_FLR_1 973.16 17348.50 16-MAR-09:10 42914.38 22-SEP-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 973.16 17348.50 16-MAR-09:10 42914.38 22-SEP-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 973.16 17348.50 16-MAR-09:10 42914.38 22-SEP-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 98.82 0.00 01-JAN-08:10 10250.26 30-SEP-15:20
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.11 0.00 01-JAN-00:10 1287.36 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.11 0.00 01-JAN-00:10 1287.36 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 98.71 0.00 01-JAN-08:10 10250.26 30-SEP-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 98.71 0.00 01-JAN-08:10 10250.26 30-SEP-15:20
EnergyTransfer:Zone:ROOM_2_FLR_3 85.26 0.00 01-JAN-08:10 10091.15 28-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.18 0.00 01-JAN-00:10 1485.40 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.18 0.00 01-JAN-00:10 1485.40 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 85.09 0.00 01-JAN-08:10 10091.15 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 85.09 0.00 01-JAN-08:10 10091.15 28-JUL-15:20
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 513.57 0.00 08-JAN-04:00 43441.28 03-DEC-14:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 513.57 0.00 08-JAN-04:00 43441.28 03-DEC-14:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 513.57 0.00 08-JAN-04:00 43441.28 03-DEC-14:10
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 718.28 0.00 01-JAN-08:10 68588.96 14-JUL-22:10
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.31 0.00 01-JAN-00:10 5052.62 03-FEB-17:30
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.31 0.00 01-JAN-00:10 5052.62 03-FEB-17:30
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 717.97 0.00 01-JAN-08:10 68588.96 14-JUL-22:10
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 717.97 0.00 01-JAN-08:10 68588.96 14-JUL-22:10
EnergyTransfer:Zone:ROOM_5_FLR_3 99.86 0.00 01-JAN-08:10 8823.71 29-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.08 0.00 01-JAN-00:10 1364.22 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.08 0.00 01-JAN-00:10 1364.22 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 99.78 0.00 01-JAN-08:10 8823.71 29-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 99.78 0.00 01-JAN-08:10 8823.71 29-JUL-15:10
EnergyTransfer:Zone:ROOM_6_FLR_3 86.18 0.00 01-JAN-08:10 8928.05 04-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.16 0.00 01-JAN-00:10 1593.78 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.16 0.00 01-JAN-00:10 1593.78 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 86.02 0.00 01-JAN-08:10 8928.05 04-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 86.02 0.00 01-JAN-08:10 8928.05 04-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 304.59 2926.90 04-FEB-07:10 10950.96 22-SEP-21:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 304.59 2926.90 04-FEB-07:10 10950.96 22-SEP-21:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 304.59 2926.90 04-FEB-07:10 10950.96 22-SEP-21:10
EnergyTransfer:Zone:ROOM_1_FLR_6 25.60 0.00 01-JAN-08:10 3105.39 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.11 0.00 01-JAN-00:10 656.97 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.11 0.00 01-JAN-00:10 656.97 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 25.49 0.00 01-JAN-08:10 3105.39 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 25.49 0.00 01-JAN-08:10 3105.39 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 22.25 0.00 01-JAN-08:10 3005.86 28-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.15 0.00 01-JAN-00:10 715.10 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.15 0.00 01-JAN-00:10 715.10 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 22.10 0.00 01-JAN-08:10 3005.86 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 22.10 0.00 01-JAN-08:10 3005.86 28-JUL-15:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 148.84 0.00 01-JAN-08:10 13751.69 25-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.06 0.00 01-JAN-00:10 1904.79 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.06 0.00 01-JAN-00:10 1904.79 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 148.78 0.00 01-JAN-08:10 13751.69 25-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 148.78 0.00 01-JAN-08:10 13751.69 25-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 512.33 10228.89 16-MAR-09:20 24229.92 28-JUL-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 512.33 10228.89 16-MAR-09:20 24229.92 28-JUL-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 512.33 10228.89 16-MAR-09:20 24229.92 28-JUL-21:10
EnergyTransfer:Zone:DINING_FLR_6 545.60 11760.28 16-MAR-09:20 25443.42 28-JUL-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 545.60 11760.28 16-MAR-09:20 25443.42 28-JUL-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 545.60 11760.28 16-MAR-09:20 25443.42 28-JUL-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 656.86 8712.44 04-FEB-04:00 30621.11 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 656.86 8712.44 04-FEB-04:00 30621.11 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 152.86 9.95 04-FEB-05:30 7576.18 29-JUL-16:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 680.10 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 680.10 04-FEB-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 152.86 0.00 04-FEB-05:30 7576.18 29-JUL-16:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 152.86 0.00 04-FEB-05:30 7576.18 29-JUL-16:10
PlantLoopHeatingDemand:Facility 574.91 6433.46 26-JUL-00:10 62278.23 04-FEB-07:20
PlantLoopHeatingDemand:Plant 535.81 6417.86 22-JUL-01:20 39067.46 20-JAN-07:30
WaterSystems:PlantLoopHeatingDemand 535.81 6417.86 22-JUL-01:20 39067.46 20-JAN-07:30
General:WaterSystems:PlantLoopHeatingDemand 535.81 6417.86 22-JUL-01:20 39067.46 20-JAN-07:30
EnergyTransfer:HVAC 15688.52 8904.57 12-DEC-08:20 942762.14 13-JUL-18:20
HeatingCoils:EnergyTransfer 39.09 0.00 01-JAN-00:10 33790.69 04-FEB-06:00
PlantLoopHeatingDemand:HVAC 39.09 0.00 01-JAN-00:10 33790.69 04-FEB-06:00
HeatingCoils:PlantLoopHeatingDemand 39.09 0.00 01-JAN-00:10 33790.69 04-FEB-06:00
CoolingCoils:EnergyTransfer 11859.03 0.00 25-JAN-04:00 698844.29 25-DEC-23:00
HeatRecoveryForHeating:EnergyTransfer 24.88 0.00 01-JAN-00:10 145689.69 04-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 3765.52 0.00 01-JAN-00:10 303067.35 25-JUL-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 535.81 6417.86 22-JUL-01:20 39067.46 20-JAN-07:30
WaterUse:WaterSystems:EnergyTransfer 535.81 6417.86 22-JUL-01:20 39067.46 20-JAN-07:30
Boilers:EnergyTransfer 38.78 0.00 01-JAN-00:10 33482.82 04-FEB-06:00
Chillers:EnergyTransfer 11964.93 0.00 25-JAN-04:00 704356.54 25-DEC-23:00
HeatRejection:EnergyTransfer 15605.01 0.00 25-JAN-04:00 880350.31 25-DEC-23:00
General:HeatRejection:EnergyTransfer 15605.01 0.00 25-JAN-04:00 880350.31 25-DEC-23:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -584.882 0.000 0.000 144.320 161.294 143.105 0.000 0.000 0.000 136.163 0.000 0.000 0.000 0.000 0.000
RETAIL_1_FLR_1 0.000 0.000 0.003 -63.942 0.000 0.000 14.706 7.307 10.186 21.278 0.000 0.945 12.503 0.000 -2.655 0.000 -0.331 -0.001
RETAIL_2_FLR_1 0.000 0.000 0.000 -53.987 0.000 0.000 17.111 8.462 11.795 0.000 0.000 0.408 16.341 0.000 0.000 0.000 -0.131 0.000
MECH_FLR_1 0.000 0.000 0.000 -52.197 0.000 0.000 3.661 8.366 12.471 0.000 0.000 0.966 27.008 0.000 0.000 0.000 -0.276 0.000
STORAGE_FLR_1 0.000 0.000 0.000 -28.452 0.000 0.000 2.829 3.079 3.598 0.000 0.000 0.568 18.536 0.000 0.000 0.000 -0.158 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -611.097 0.000 0.000 11.834 3.975 658.131 0.000 0.000 1.576 0.000 0.000 0.000 0.000 -0.444 -63.976
CAFE_FLR_1 0.000 0.000 0.000 -280.321 0.000 0.000 187.083 14.301 14.341 59.713 0.000 2.023 12.167 0.000 -8.385 0.000 -0.921 -0.001
LOBBY_FLR_1 0.000 0.000 0.000 -973.164 0.000 0.000 562.817 110.186 148.998 80.927 0.000 6.185 76.490 0.000 -9.980 0.000 -2.459 -0.001
ROOM_1_FLR_3 0.265 -84.324 0.000 -14.542 0.000 0.000 9.629 9.244 10.478 49.796 0.000 3.335 21.675 0.000 -4.494 0.000 -1.062 -0.000
ROOM_2_FLR_3 0.413 -70.263 0.000 -15.055 0.000 0.000 9.508 9.243 10.477 41.477 0.000 2.991 17.499 0.000 -4.885 0.000 -1.406 -0.000
ROOM_3_MULT19_FLR_3 0.000 -495.171 0.000 -18.396 0.000 0.000 0.000 110.385 194.997 219.466 0.000 3.264 68.028 0.000 -68.928 0.000 -13.645 -0.004
ROOM_4_MULT19_FLR_3 0.837 -515.447 0.000 -202.994 0.000 0.000 181.134 110.415 195.050 157.966 0.000 17.129 94.956 0.000 -24.619 0.000 -14.426 -0.011
ROOM_5_FLR_3 0.222 -85.379 0.000 -14.546 0.000 0.000 9.625 9.244 10.478 50.949 0.000 3.328 21.459 0.000 -4.301 0.000 -1.080 -0.000
ROOM_6_FLR_3 0.380 -71.175 0.000 -15.065 0.000 0.000 9.508 9.243 10.477 42.434 0.000 2.980 17.157 0.000 -4.542 0.000 -1.397 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.000 -304.586 0.000 0.000 115.323 91.336 0.000 48.129 0.000 2.934 53.699 0.000 -5.894 0.000 -0.940 0.000
ROOM_1_FLR_6 0.216 -21.959 0.000 -3.638 0.000 0.000 2.408 2.311 2.620 12.300 0.000 0.839 6.254 0.000 -1.070 0.000 -0.280 -0.000
ROOM_2_FLR_6 0.278 -18.448 0.000 -3.772 0.000 0.000 2.375 2.311 2.619 10.248 0.000 0.744 5.237 0.000 -1.198 0.000 -0.393 -0.000
ROOM_3_MULT9_FLR_6 0.247 -125.568 0.000 -23.392 0.000 0.000 21.655 13.076 23.098 59.839 0.000 4.242 33.432 0.000 -4.857 0.000 -1.771 -0.000
BANQUET_FLR_6 0.000 0.000 0.000 -512.336 0.000 0.000 321.102 31.030 175.857 14.804 0.000 1.179 0.000 0.000 -4.729 0.000 -0.701 -26.207
DINING_FLR_6 0.000 0.000 0.000 -545.602 0.000 0.000 319.641 31.030 175.857 14.323 0.000 1.146 9.423 0.000 -5.095 0.000 -0.723 -0.000
KITCHEN_FLR_6 0.000 0.000 0.000 -656.843 0.000 0.000 29.181 12.972 550.372 21.952 0.000 1.008 45.962 0.000 -3.976 0.000 -0.629 0.000
CORRIDOR_FLR_6 0.000 0.000 0.004 -152.859 0.000 0.000 30.479 24.166 0.000 21.641 0.000 1.221 78.475 0.000 -2.739 0.000 -0.388 0.000
Total Facility 2.858 -1487.733 0.008 -5131.669 0.000 0.000 2005.928 782.979 2365.005 927.240 0.000 59.012 772.464 0.000 -162.348 0.000 -43.561 -90.201


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-SEP-21:00 0.00 0.00 0.00 -20891.61 0.00 0.00 5942.64 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5901.25
RETAIL_1_FLR_1 25-OCT-14:30 0.00 0.00 0.00 -3814.81 0.00 0.00 225.90 166.00 252.59 3264.36 0.00 68.97 0.00 0.00 -0.00 0.00 0.00 -163.02
RETAIL_2_FLR_1 28-JUL-20:50 0.00 0.00 0.00 -2469.89 0.00 0.00 697.63 615.12 752.15 0.00 0.00 23.19 381.81 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 29-JUL-20:30 0.00 0.00 0.00 -2512.84 0.00 0.00 129.09 532.14 706.90 0.00 0.00 48.50 1096.21 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 29-JUL-19:00 0.00 0.00 0.00 -1188.46 0.00 0.00 85.11 195.87 203.92 0.00 0.00 49.26 654.31 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 28-JUL-20:00 0.00 0.00 0.00 -36553.08 0.00 0.00 408.89 325.08 44299.38 0.00 0.00 61.87 0.00 0.00 -0.00 0.00 0.00 -8542.14
CAFE_FLR_1 25-OCT-15:03 0.00 0.00 0.00 -13748.29 0.00 0.00 4948.00 103.98 355.63 7293.69 0.00 132.83 914.17 0.00 -0.00 0.00 0.00 0.00
LOBBY_FLR_1 22-SEP-21:10 0.00 0.00 0.00 -42917.41 0.00 0.00 26440.91 6336.53 7389.94 664.95 0.00 316.44 1768.64 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 15-MAR-15:01 0.00 -12420.15 0.00 -590.72 0.00 0.00 235.28 199.23 200.18 6873.12 0.00 0.00 6221.62 0.00 -0.00 0.00 -718.56 0.00
ROOM_2_FLR_3 13-JUN-18:11 0.00 -12349.05 0.00 -861.73 0.00 0.00 303.99 633.19 484.60 3103.82 0.00 32.09 8653.11 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 03-DEC-14:10 0.00 -43442.68 0.00 0.00 0.00 0.00 0.00 2803.75 2548.95 48442.86 0.00 0.00 0.00 0.00 -0.00 0.00 -334.42 -10018.46
ROOM_4_MULT19_FLR_3 13-JAN-19:01 0.00 -78967.98 0.00 -10304.89 0.00 0.00 6374.52 7563.69 9021.83 339.65 0.00 221.95 65751.24 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 16-MAR-15:01 0.00 -11153.14 0.00 -632.80 0.00 0.00 235.28 199.23 200.18 1759.87 0.00 0.00 9944.47 0.00 -0.00 0.00 -553.10 0.00
ROOM_6_FLR_3 20-APR-08:51 0.00 -11424.99 0.00 -845.08 0.00 0.00 79.86 313.04 452.99 4425.83 0.00 11.53 6986.83 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 22-SEP-21:10 0.00 0.00 0.00 -10951.42 0.00 0.00 5349.95 4979.51 0.00 680.25 0.00 148.66 0.00 0.00 -0.00 0.00 0.00 -206.97
ROOM_1_FLR_6 15-MAR-15:01 0.00 -3397.35 0.00 -146.88 0.00 0.00 58.82 49.81 50.05 1677.07 0.00 0.00 1907.51 0.00 -0.00 0.00 -199.02 0.00
ROOM_2_FLR_6 13-JUN-18:11 0.00 -3450.54 0.00 -221.90 0.00 0.00 73.43 158.30 121.15 749.04 0.00 5.32 2565.21 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 25-JAN-16:01 0.00 -14180.78 0.00 -1008.37 0.00 0.00 529.39 281.79 441.28 3541.75 0.00 0.00 11576.96 0.00 -0.00 0.00 -1182.03 0.00
BANQUET_FLR_6 28-JUL-21:10 0.00 0.00 0.00 -24232.29 0.00 0.00 15645.39 1992.02 6747.90 178.55 0.00 85.21 0.00 0.00 -0.00 0.00 0.00 -416.78
DINING_FLR_6 28-JUL-21:10 0.00 0.00 0.00 -25445.96 0.00 0.00 15645.30 1992.02 6747.90 162.17 0.00 85.20 813.36 0.00 -0.00 0.00 0.00 0.00
KITCHEN_FLR_6 23-JUL-10:50 0.00 0.00 0.00 -30618.52 0.00 0.00 461.93 353.60 24259.91 2802.70 0.00 124.72 2615.67 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 29-JUL-16:10 0.00 0.00 0.00 -7576.36 0.00 0.00 771.15 548.96 0.00 1680.56 0.00 158.31 4417.38 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:02 0.00 -166448.29 0.00 -213223.92 0.00 0.00 63336.90 52363.95 113378.48 36064.31 0.00 6034.04 108494.51 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 04-FEB-07:10 0.00 0.00 418.24 0.00 0.00 0.00 447.53 199.20 288.68 0.00 0.00 0.00 0.00 0.00 -727.24 0.00 -198.99 -427.41
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 04-FEB-10:10 0.00 0.00 24.61 0.00 0.00 0.00 65.77 228.06 353.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -87.03 -584.86
STORAGE_FLR_1 04-FEB-08:00 0.00 0.00 20.41 0.00 0.00 0.00 84.31 83.94 101.96 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -94.98 -195.65
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 03-FEB-19:03 4017.69 421.03 0.00 -421.03 0.00 0.00 356.40 633.26 484.65 0.00 0.00 0.00 0.00 0.00 -1538.33 0.00 -231.57 -3722.10
ROOM_2_FLR_3 19-MAR-15:04 3955.82 470.80 0.00 -470.80 0.00 0.00 132.05 234.78 221.23 1360.00 0.00 0.00 0.00 0.00 -0.00 0.00 -624.25 -5279.62
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 25-JAN-09:03 20969.30 5667.70 0.00 -5667.70 0.00 0.00 1809.11 3739.35 8433.45 0.00 0.00 0.00 0.00 0.00 -4015.87 0.00 -1451.26 -29484.07
ROOM_5_FLR_3 03-FEB-19:03 3817.17 419.67 0.00 -419.67 0.00 0.00 360.66 633.26 484.65 0.00 0.00 0.00 0.00 0.00 -1494.43 0.00 -231.06 -3570.25
ROOM_6_FLR_3 03-FEB-16:03 3865.79 447.53 0.00 -447.53 0.00 0.00 254.51 199.20 200.16 0.00 0.00 0.00 0.00 0.00 -130.49 0.00 -820.38 -3568.80
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 19-MAR-15:04 1159.95 118.51 0.00 -118.51 0.00 0.00 32.68 58.70 55.31 346.55 0.00 0.00 0.00 0.00 -0.00 0.00 -183.47 -1469.72
ROOM_2_FLR_6 15-DEC-16:03 1161.94 141.90 0.00 -141.90 0.00 0.00 62.62 49.80 50.04 77.63 0.00 0.00 0.00 0.00 -0.00 0.00 -101.11 -1300.92
ROOM_3_MULT9_FLR_6 30-JAN-16:05 4694.75 687.16 0.00 -687.16 0.00 0.00 543.58 281.79 441.28 0.00 0.00 0.00 0.00 0.00 -688.46 0.00 -204.30 -5068.65
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 04-FEB-07:10 0.00 0.00 680.22 0.00 0.00 0.00 916.63 658.76 0.00 0.00 0.00 0.00 0.00 0.00 -1116.97 0.00 -249.00 -889.63
Total Facility 15-MAR-15:04 -125899.41 143113.51 0.00 -143113.51 0.00 0.00 59665.57 16709.04 73912.59 61003.68 0.00 0.00 0.00 0.00 0.00 0.00 -13422.05 -71969.42



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.1804 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.9866 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6669 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6669 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8932 2.8932 1.5218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3092 0.3092 0.1627 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2738 0.2738 0.1440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2743 0.2743 0.1443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1506 0.1506 0.0792 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1889 3.1889 1.6773 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3073 1.3073 0.6877 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7205 4.7205 2.4830 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5468 1.5468 0.8136 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2119 2.2119 1.1634 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3126 2.3126 1.2164 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2050 2.2050 1.1598 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7863 0.7863 0.4136 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.1804 21.9866 22.1804 11.6669 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5218 1.5218 1.5218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1627 0.1627 0.1627 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1440 0.1440 0.1440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1443 0.1443 0.1443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0792 0.0792 0.0792 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6773 1.6773 1.6773 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6877 0.6877 0.6877 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4830 2.4830 2.4830 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8136 0.8136 0.8136 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1634 1.1634 1.1634 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2164 1.2164 1.2164 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1598 1.1598 1.1598 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4136 0.4136 0.4136 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6669 11.6669 11.6669 11.6669 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 59.83
Number of hours not met 59.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 62.51 46790.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3640.07 209234.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 782.98 64632.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 194.15 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.77 1291.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 466.32 25804.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 133.21 5129.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 295.44 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.76 4738.81 2541.67 219783.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.33 1891.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.84 1193.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1720.44 7964.17
Natural Gas 1788.84 4393.01
Additional 0.00 0.00
Total 3509.28 12357.18


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 69.01
Space Heating 0.00
Space Cooling 320.84
Fans (All) 41.10
Service Water Heating 8.00
Receptacle Equipment 146.16
Miscellaneous (All) 701.98
Subtotal 701.98


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 5.51
Service Water Heating 224.03
Miscellaneous (All) 387.21
Subtotal 387.21


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.34
Space Heating 0.51
Space Cooling 29.46
Fans (All) 3.77
Service Water Heating 21.30
Receptacle Equipment 27.89
Miscellaneous 10.73


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 4427.50 4332.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8758.33 1.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 4427.50 0.00 0.00 0.00 0.00
Max 8760.00 4332.50 0.00 0.00 0.00
Average 8562.99 197.01 0.00 0.00 0.00
Sum 188385.83 4334.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4153.67 0.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.33 0.00 0.00 0.00
Average 288887.03 0.02 0.00 0.00 0.00
Sum 6355514.67 0.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8234.17 525.83 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8750.17 9.83 0.00 0.00 0.00
ROOM_2_FLR_3 8542.67 217.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 3370.50 5389.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8598.67 161.33 0.00 0.00 0.00
ROOM_5_FLR_3 8751.67 8.33 0.00 0.00 0.00
ROOM_6_FLR_3 8485.50 274.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8736.17 23.83 0.00 0.00 0.00
ROOM_2_FLR_6 8405.00 355.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8741.50 18.50 0.00 0.00 0.00
BANQUET_FLR_6 8258.50 501.50 0.00 0.00 0.00
DINING_FLR_6 8609.33 150.67 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 3370.50 0.00 0.00 0.00 0.00
Max 8760.00 5389.50 0.00 0.00 0.00
Average 8412.90 347.10 0.00 0.00 0.00
Sum 185083.83 7636.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 643110.33 67306.67 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4079.67 74.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4092.67 61.33 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4084.17 69.83 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 3999.00 155.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1133387.33 112327.67 0.00 0.00 0.00
DINING_FLR_6 1211965.67 33749.33 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 112327.67 0.00 0.00 0.00
Average 279171.40 9715.64 0.00 0.00 0.00
Sum 6141770.83 213744.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:46:00

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.481119E+11 19624.67 03-JAN-22:00 22.20 20.64 0.711963E+10 4520.67 03-JAN-22:10 22.12 20.55
February 0.427808E+11 19065.69 17-FEB-22:00 23.90 20.81 0.634142E+10 4392.04 17-FEB-22:10 23.90 20.81
March 0.463931E+11 18877.34 31-MAR-21:00 23.30 18.01 0.691089E+10 4348.94 31-MAR-21:10 23.27 18.08
April 0.457427E+11 19105.04 14-APR-21:00 25.60 22.81 0.677843E+10 4401.26 14-APR-21:10 25.50 22.67
May 0.485831E+11 19497.06 19-MAY-21:00 26.10 22.26 0.719197E+10 4491.70 19-MAY-21:10 26.10 22.31
June 0.483162E+11 19860.42 30-JUN-21:00 27.80 24.57 0.715869E+10 4575.93 30-JUN-21:10 27.75 24.53
July 0.513431E+11 20292.25 28-JUL-21:00 29.40 24.13 0.757234E+10 4677.80 28-JUL-21:10 29.32 24.20
August 0.517290E+11 20633.85 23-AUG-21:00 26.70 22.36 0.766294E+10 4758.72 23-AUG-21:10 26.70 22.41
September 0.509375E+11 20891.25 22-SEP-21:00 28.30 25.04 0.752180E+10 4820.46 22-SEP-21:10 28.30 25.17
October 0.523879E+11 20672.48 25-OCT-21:00 26.70 20.95 0.773040E+10 4767.95 25-OCT-21:10 26.60 21.10
November 0.492944E+11 20542.57 10-NOV-22:00 23.30 21.05 0.727270E+10 4736.80 10-NOV-22:10 23.22 20.97
December 0.492620E+11 20135.68 08-DEC-22:00 23.90 22.40 0.728015E+10 4640.66 11-DEC-22:10 18.22 14.26
                     
Annual Sum or Average 0.584882E+12         0.865413E+11        
Minimum of Months 0.427808E+11 18877.34   22.20 18.01 0.634142E+10 4348.94   18.22 14.26
Maximum of Months 0.523879E+11 20891.25   29.40 25.04 0.773040E+10 4820.46   29.32 25.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.457833E+10 3434.26 02-JAN-14:30 28.90 24.11 0.678804E+09 482.76 13-JAN-22:10 24.32 21.03
February 0.432884E+10 3345.29 11-FEB-14:30 28.85 24.07 0.625228E+09 475.83 22-FEB-22:10 19.22 14.79
March 0.478808E+10 2295.00 27-MAR-19:20 25.20 21.25 0.704244E+09 491.15 27-MAR-21:10 24.90 21.81
April 0.506866E+10 2772.16 15-APR-18:03 29.82 21.94 0.705555E+09 491.78 11-APR-21:19 29.82 21.94
May 0.544474E+10 2644.30 17-MAY-19:30 26.95 22.51 0.757465E+09 491.78 19-MAY-21:19 26.10 22.36
June 0.549254E+10 2959.64 29-JUN-19:10 29.82 25.18 0.756670E+09 491.82 14-JUN-22:19 29.82 25.18
July 0.598431E+10 3354.58 29-JUL-18:03 33.12 24.14 0.794655E+09 491.82 12-JUL-22:19 33.12 24.14
August 0.587116E+10 3121.33 21-AUG-18:15 29.40 24.96 0.785239E+09 491.82 30-AUG-22:19 26.70 23.41
September 0.605849E+10 3646.24 30-SEP-13:50 31.02 24.64 0.770122E+09 491.82 12-SEP-22:19 31.02 24.64
October 0.614772E+10 3814.74 25-OCT-14:30 30.00 22.37 0.780262E+09 491.82 24-OCT-22:19 30.00 22.37
November 0.533008E+10 3777.78 07-NOV-14:00 28.30 20.78 0.714118E+09 491.82 07-NOV-23:19 24.03 21.96
December 0.484904E+10 3806.67 09-DEC-12:30 27.20 22.50 0.695795E+09 491.82 08-DEC-22:19 27.20 22.50
                     
Annual Sum or Average 0.639420E+11         0.876816E+10        
Minimum of Months 0.432884E+10 2295.00   25.20 20.78 0.625228E+09 475.83   19.22 14.79
Maximum of Months 0.614772E+10 3814.74   33.12 25.18 0.794655E+09 491.82   33.12 25.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.409021E+10 1854.82 03-JAN-22:00 22.20 20.64 0.776886E+09 531.29 03-JAN-22:10 22.12 20.55
February 0.377463E+10 1852.49 11-FEB-22:00 21.70 19.79 0.717685E+09 529.16 22-FEB-22:10 19.22 14.79
March 0.426383E+10 1926.48 28-MAR-21:00 24.40 21.00 0.812411E+09 552.21 28-MAR-21:10 24.32 20.85
April 0.440326E+10 2108.55 13-APR-21:00 25.60 22.81 0.820913E+09 569.49 13-APR-21:19 25.40 22.62
May 0.470993E+10 2229.53 17-MAY-20:40 26.30 22.65 0.875082E+09 569.49 19-MAY-21:19 26.10 22.36
June 0.468530E+10 2398.95 09-JUN-21:00 29.40 24.96 0.868788E+09 569.53 29-JUN-22:19 28.90 24.72
July 0.499203E+10 2469.87 28-JUL-20:50 29.22 24.11 0.915495E+09 569.53 07-JUL-22:19 29.22 24.11
August 0.488636E+10 2419.80 17-AUG-20:10 28.22 24.59 0.903065E+09 569.53 02-AUG-22:19 28.22 24.59
September 0.478023E+10 2353.91 01-SEP-20:10 28.90 23.48 0.880500E+09 569.53 01-SEP-22:19 28.53 23.75
October 0.480491E+10 2262.91 06-OCT-20:40 26.70 23.40 0.888932E+09 569.50 25-OCT-21:30 26.40 21.40
November 0.437914E+10 1961.15 07-NOV-22:00 24.40 22.09 0.813898E+09 562.45 07-NOV-22:10 24.40 22.09
December 0.421732E+10 1925.12 08-DEC-22:00 23.90 22.40 0.798640E+09 551.77 08-DEC-22:10 23.98 22.48
                     
Annual Sum or Average 0.539872E+11         0.100723E+11        
Minimum of Months 0.377463E+10 1852.49   21.70 19.79 0.717685E+09 529.16   19.22 14.79
Maximum of Months 0.499203E+10 2469.87   29.40 24.96 0.915495E+09 569.53   29.22 24.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.347678E+10 1699.23 03-JAN-22:00 22.20 20.64 0.156415E+09 102.97 03-JAN-22:10 22.12 20.55
February 0.336530E+10 1720.11 17-FEB-22:00 23.90 20.81 0.143786E+09 104.21 17-FEB-22:10 23.90 20.81
March 0.382044E+10 1746.48 30-MAR-21:00 23.90 19.84 0.162236E+09 105.78 30-MAR-21:10 23.90 19.88
April 0.425040E+10 1862.66 14-APR-21:00 25.60 22.81 0.165483E+09 112.74 14-APR-21:10 25.50 22.67
May 0.472783E+10 1946.90 22-MAY-21:00 27.80 22.72 0.183553E+09 117.97 22-MAY-21:10 27.70 22.63
June 0.483756E+10 2332.34 29-JUN-20:00 28.90 25.14 0.187603E+09 120.45 28-JUN-21:30 28.90 25.14
July 0.515232E+10 2512.83 29-JUL-20:30 28.60 23.43 0.197276E+09 120.45 31-JUL-22:19 28.77 25.17
August 0.494678E+10 2310.05 21-AUG-20:00 28.30 24.58 0.191742E+09 120.45 22-AUG-21:30 27.80 24.35
September 0.483178E+10 2283.94 22-SEP-20:00 28.30 25.04 0.187047E+09 120.45 19-SEP-21:10 28.30 25.04
October 0.476548E+10 1922.46 03-OCT-21:00 27.80 25.31 0.184467E+09 116.39 03-OCT-21:10 27.80 25.31
November 0.426320E+10 1849.32 04-NOV-21:10 26.20 24.62 0.166561E+09 111.89 10-NOV-22:10 23.22 20.97
December 0.375909E+10 1795.51 10-DEC-21:00 24.40 23.27 0.161396E+09 108.05 08-DEC-22:10 24.40 23.27
                     
Annual Sum or Average 0.521970E+11         0.208757E+10        
Minimum of Months 0.336530E+10 1699.23   22.20 19.84 0.143786E+09 102.97   22.12 19.88
Maximum of Months 0.515232E+10 2512.83   28.90 25.31 0.197276E+09 120.45   28.90 25.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191813E+10 918.03 03-JAN-22:10 22.12 20.55 0.120091E+09 77.94 03-JAN-22:10 22.12 20.55
February 0.184967E+10 926.95 11-FEB-22:10 21.60 19.69 0.110243E+09 78.63 17-FEB-22:10 23.90 20.81
March 0.208905E+10 939.62 30-MAR-21:10 23.90 19.88 0.124222E+09 79.67 30-MAR-21:10 23.90 19.88
April 0.231889E+10 998.47 14-APR-21:10 25.50 22.67 0.126358E+09 84.61 14-APR-21:10 25.50 22.67
May 0.256946E+10 1041.29 22-MAY-21:10 27.70 22.63 0.139579E+09 88.23 22-MAY-21:10 27.70 22.63
June 0.261876E+10 1085.40 29-JUN-21:10 28.90 24.82 0.142406E+09 92.05 29-JUN-21:10 28.90 24.82
July 0.277112E+10 1188.46 29-JUL-19:00 32.20 24.21 0.149973E+09 92.65 28-JUL-21:40 32.20 24.21
August 0.268481E+10 1086.65 21-AUG-21:10 28.22 25.01 0.146073E+09 92.15 21-AUG-21:10 28.22 25.01
September 0.262550E+10 1086.26 22-SEP-21:10 28.30 25.17 0.142380E+09 92.16 22-SEP-21:10 28.30 25.17
October 0.260189E+10 1036.11 01-OCT-00:10 27.93 23.96 0.140946E+09 87.50 03-OCT-21:10 27.80 25.31
November 0.233523E+10 997.00 04-NOV-21:10 26.20 24.62 0.127532E+09 84.40 03-NOV-21:10 26.20 24.62
December 0.206925E+10 970.04 09-DEC-22:00 23.90 22.40 0.123772E+09 81.66 08-DEC-22:10 23.90 22.40
                     
Annual Sum or Average 0.284518E+11         0.159357E+10        
Minimum of Months 0.184967E+10 918.03   21.60 19.69 0.110243E+09 77.94   22.12 19.88
Maximum of Months 0.277112E+10 1188.46   32.20 25.17 0.149973E+09 92.65   32.20 25.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.485848E+11 33995.88 02-JAN-21:00 22.20 19.62 0.532741E+09 381.63 25-JAN-23:10 12.20 8.81
February 0.445711E+11 33931.61 17-FEB-21:00 23.90 20.81 0.482667E+09 381.57 24-FEB-22:10 16.02 11.81
March 0.501984E+11 34683.49 27-MAR-20:00 24.40 20.99 0.538218E+09 381.55 14-MAR-21:10 24.40 20.99
April 0.501549E+11 35566.46 14-APR-20:00 26.10 23.27 0.522432E+09 381.58 20-APR-21:30 22.20 16.21
May 0.531513E+11 35832.97 31-MAY-20:00 27.80 24.12 0.544507E+09 381.51 24-MAY-21:10 27.80 24.12
June 0.525614E+11 36204.02 09-JUN-20:00 29.40 24.96 0.531549E+09 381.52 21-JUN-21:10 24.50 22.87
July 0.547367E+11 36553.14 28-JUL-20:00 28.30 23.96 0.548810E+09 381.51 14-JUL-22:10 28.30 23.96
August 0.536772E+11 36074.26 31-AUG-20:00 27.80 24.58 0.547514E+09 381.49 23-AUG-21:30 27.80 24.58
September 0.523485E+11 35972.12 08-SEP-20:00 30.60 24.86 0.529412E+09 381.51 05-SEP-22:10 30.60 24.86
October 0.527940E+11 35650.88 06-OCT-20:00 26.70 23.40 0.542639E+09 381.51 27-OCT-22:10 23.80 21.85
November 0.494303E+11 34821.75 10-NOV-21:00 24.40 21.68 0.520450E+09 381.52 14-NOV-22:10 18.30 14.23
December 0.488878E+11 34368.02 08-DEC-21:00 24.40 22.09 0.533525E+09 381.57 20-DEC-22:10 10.50 8.09
                     
Annual Sum or Average 0.611096E+12         0.637446E+10        
Minimum of Months 0.445711E+11 33931.61   22.20 19.62 0.482667E+09 381.49   10.50 8.09
Maximum of Months 0.547367E+11 36553.14   30.60 24.96 0.548810E+09 381.63   30.60 24.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.223138E+11 11893.59 02-JAN-14:30 28.90 24.11 0.977159E+10 6462.42 02-JAN-23:10 20.50 19.70
February 0.203031E+11 11799.56 11-FEB-14:30 28.85 24.07 0.893562E+10 6462.50 16-FEB-23:10 23.22 20.64
March 0.221574E+11 10649.38 27-MAR-21:10 24.90 21.81 0.996076E+10 6462.59 31-MAR-22:10 23.05 18.37
April 0.221439E+11 11211.02 14-APR-21:10 25.50 22.67 0.981063E+10 6462.64 10-APR-22:10 25.50 22.67
May 0.234376E+11 11451.61 22-MAY-21:10 27.70 22.63 0.103669E+11 6461.91 09-MAY-22:19 27.70 22.63
June 0.234764E+11 11747.52 29-JUN-21:10 28.90 24.82 0.102553E+11 6462.62 21-JUN-21:10 28.90 24.82
July 0.248553E+11 12334.00 28-JUL-21:10 29.32 24.20 0.106531E+11 6462.56 14-JUL-22:10 29.32 24.20
August 0.246950E+11 12246.45 31-AUG-21:10 27.77 24.60 0.106345E+11 6461.93 23-AUG-22:19 27.77 24.60
September 0.250403E+11 12967.37 08-SEP-21:10 29.90 24.64 0.103913E+11 6462.48 05-SEP-22:10 29.90 24.64
October 0.256429E+11 13747.23 25-OCT-15:03 29.22 22.14 0.106895E+11 6462.39 27-OCT-22:10 23.80 21.85
November 0.234798E+11 12754.80 07-NOV-16:03 28.22 22.20 0.100017E+11 6462.49 21-NOV-22:40 24.40 22.66
December 0.227736E+11 13198.50 09-DEC-12:30 27.20 22.50 0.991465E+10 6462.50 01-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.280319E+12         0.121386E+12        
Minimum of Months 0.203031E+11 10649.38   24.90 21.81 0.893562E+10 6461.91   20.50 18.37
Maximum of Months 0.256429E+11 13747.23   29.90 24.82 0.106895E+11 6462.64   29.90 24.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.764561E+11 33545.57 03-JAN-22:20 22.03 20.47 0.279167E+11 18748.38 03-JAN-22:40 21.87 20.31
February 0.697257E+11 33260.25 17-FEB-22:51 23.90 20.81 0.255141E+11 18582.22 17-FEB-23:10 23.90 20.81
March 0.772530E+11 33571.27 30-MAR-21:51 23.90 20.12 0.285458E+11 18762.26 30-MAR-21:40 23.90 20.12
April 0.778695E+11 35855.45 14-APR-21:10 25.50 22.67 0.284393E+11 19182.09 13-APR-21:10 25.50 22.67
May 0.833667E+11 37406.29 22-MAY-21:10 27.70 22.63 0.303712E+11 19184.73 19-MAY-22:19 27.70 22.63
June 0.835011E+11 40895.27 29-JUN-21:10 28.90 24.82 0.302525E+11 19184.80 21-JUN-21:19 28.90 24.82
July 0.883025E+11 42672.59 28-JUL-21:10 29.32 24.20 0.315116E+11 19185.95 14-JUL-22:10 29.32 24.20
August 0.868257E+11 42003.77 21-AUG-21:10 28.22 25.01 0.312982E+11 19185.18 23-AUG-22:19 26.50 22.88
September 0.856341E+11 42914.38 22-SEP-21:10 28.30 25.17 0.305381E+11 19185.72 25-SEP-22:10 23.90 23.16
October 0.862913E+11 40371.82 06-OCT-21:10 26.70 23.48 0.311104E+11 19185.23 18-OCT-22:19 25.60 19.47
November 0.797311E+11 37350.89 10-NOV-22:10 23.22 20.97 0.288988E+11 19185.76 10-NOV-23:10 22.52 20.48
December 0.782034E+11 35304.05 08-DEC-22:05 23.98 22.48 0.285124E+11 19185.74 08-DEC-23:10 24.50 22.98
                     
Annual Sum or Average 0.973160E+12         0.352909E+12        
Minimum of Months 0.697257E+11 33260.25   22.03 20.12 0.255141E+11 18582.22   21.87 19.47
Maximum of Months 0.883025E+11 42914.38   29.32 25.17 0.315116E+11 19185.95   29.32 24.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120092E+10 3235.01 25-JAN-16:01 17.80 8.74 98493708.03 56.70 06-JAN-22:10 17.80 8.74
February 0.134747E+10 3212.80 03-FEB-16:01 16.42 8.65 89114224.59 56.70 09-FEB-22:00 22.20 18.84
March 0.169506E+10 3252.86 15-MAR-15:01 17.30 8.90 98831245.07 56.70 25-MAR-23:10 23.30 21.05
April 0.208688E+10 3044.26 01-APR-15:02 27.88 24.57 95825194.09 56.70 14-APR-02:00 24.40 22.88
May 0.237898E+10 3068.30 30-MAY-15:02 30.18 23.97 99150187.21 56.70 20-MAY-04:19 30.18 23.97
June 0.243179E+10 3046.67 27-JUN-15:02 30.92 24.20 96002397.53 56.70 21-JUN-01:19 30.92 24.20
July 0.272602E+10 3049.13 06-JUL-15:02 30.50 24.92 99119257.30 56.70 20-JUL-21:00 28.30 24.59
August 0.259620E+10 3061.30 29-AUG-15:02 29.40 23.81 99208150.35 56.70 15-AUG-21:10 29.40 23.81
September 0.254212E+10 3059.95 21-SEP-18:02 29.40 25.15 95928554.46 56.70 19-SEP-21:30 29.40 25.15
October 0.245310E+10 3061.49 03-OCT-18:02 29.22 24.97 99124425.11 56.70 23-OCT-00:40 24.27 22.00
November 0.183296E+10 3022.73 05-NOV-15:02 27.80 23.86 95780731.13 56.70 28-NOV-22:10 25.00 22.32
December 0.138685E+10 3035.41 16-DEC-16:01 21.42 15.87 98502719.09 56.70 09-DEC-01:10 21.42 15.87
                     
Annual Sum or Average 0.246783E+11         0.116508E+10        
Minimum of Months 0.120092E+10 3022.73   16.42 8.65 89114224.59 56.70   17.80 8.74
Maximum of Months 0.272602E+10 3252.86   30.92 25.15 99208150.35 56.70   30.92 25.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.662307E+09 3103.67 25-JAN-16:01 17.80 8.74 0.101850E+09 73.96 03-JAN-22:10 17.80 8.74
February 0.857175E+09 3142.79 03-FEB-16:01 16.42 8.65 93951222.56 75.18 16-FEB-22:10 23.30 20.32
March 0.123355E+10 3257.01 15-MAR-15:01 17.30 8.90 0.104747E+09 78.27 30-MAR-21:10 23.90 19.88
April 0.176554E+10 3126.76 18-APR-21:51 17.80 13.01 0.101275E+09 79.63 10-APR-21:10 17.80 13.01
May 0.233250E+10 3076.26 10-MAY-16:31 25.53 22.56 0.100395E+09 75.58 25-MAY-21:10 23.90 22.59
June 0.245086E+10 3302.79 13-JUN-18:11 25.37 22.49 96535124.13 69.31 21-JUN-20:00 24.40 22.75
July 0.272013E+10 3066.80 12-JUL-18:02 28.90 25.29 99994787.65 79.18 14-JUL-21:10 23.22 22.08
August 0.253063E+10 3089.97 15-AUG-18:02 29.72 25.03 99536408.87 58.20 06-AUG-21:10 29.72 25.03
September 0.234819E+10 3072.00 08-SEP-18:02 31.02 24.58 96782580.18 77.15 05-SEP-21:10 31.02 24.58
October 0.210308E+10 3079.81 22-OCT-15:02 29.22 23.41 0.100027E+09 71.95 27-OCT-21:19 23.90 21.88
November 0.139928E+10 3075.34 19-NOV-16:01 26.70 20.69 98117457.74 74.61 21-NOV-22:10 24.40 22.53
December 0.868106E+09 3071.04 09-DEC-16:02 26.02 22.28 0.101989E+09 74.17 01-DEC-22:10 26.02 22.28
                     
Annual Sum or Average 0.212713E+11         0.119520E+10        
Minimum of Months 0.662307E+09 3066.80   16.42 8.65 93951222.56 58.20   17.80 8.74
Maximum of Months 0.272013E+10 3302.79   31.02 25.29 0.104747E+09 79.63   31.02 25.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.516789E+09 567.36 02-JAN-14:30 28.90 24.11 0.00 0.00 01-JAN-00:10 28.90 24.11
February 0.458620E+09 487.13 11-FEB-14:30 28.85 24.07 0.00 0.00 01-FEB-00:10 28.85 24.07
March 0.453075E+09 395.16 02-MAR-14:30 25.00 17.17 0.00 0.00 01-MAR-00:10 25.00 17.17
April 0.466075E+09 337.79 15-APR-17:17 31.13 22.55 0.00 0.00 01-APR-00:10 31.13 22.55
May 0.511425E+09 326.09 22-MAY-20:20 28.13 22.80 0.00 0.00 01-MAY-00:10 28.13 22.80
June 0.547118E+09 342.08 03-JUN-21:00 29.40 24.47 0.00 0.00 01-JUN-00:10 29.40 24.47
July 0.608846E+09 373.89 29-JUL-19:10 31.55 24.08 0.00 0.00 01-JUL-00:10 31.55 24.08
August 0.604788E+09 364.38 20-AUG-20:10 28.80 24.73 0.00 0.00 01-AUG-00:10 28.80 24.73
September 0.682072E+09 465.65 30-SEP-13:50 31.02 24.64 0.00 0.00 01-SEP-00:10 31.02 24.64
October 0.739128E+09 536.22 25-OCT-14:00 30.60 22.69 0.00 0.00 01-OCT-00:10 30.60 22.69
November 0.627867E+09 570.68 07-NOV-14:00 28.30 20.78 0.00 0.00 01-NOV-00:10 28.30 20.78
December 0.541721E+09 571.60 03-DEC-14:05 24.40 18.40 0.00 0.00 01-DEC-00:10 24.40 18.40
                     
Annual Sum or Average 0.675752E+10         0.00        
Minimum of Months 0.453075E+09 326.09   24.40 17.17 0.00 0.00   24.40 17.17
Maximum of Months 0.739128E+09 571.60   31.55 24.73 0.00 0.00   31.55 24.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.468641E+09 1174.62 13-JAN-19:01 24.40 20.63 0.101502E+09 72.83 03-JAN-22:10 24.40 20.63
February 0.491031E+09 1155.77 27-FEB-16:01 26.10 17.26 93312591.35 74.42 10-FEB-22:10 26.10 17.26
March 0.622654E+09 1156.94 29-MAR-18:02 24.90 20.49 0.103197E+09 74.26 31-MAR-21:10 23.27 18.08
April 0.755218E+09 1166.78 15-APR-18:02 29.82 21.94 99983167.82 75.32 25-APR-21:10 22.88 20.54
May 0.965447E+09 1168.55 30-MAY-18:02 29.72 24.14 0.100077E+09 75.45 25-MAY-21:10 29.72 24.14
June 0.102215E+10 1172.91 29-JUN-18:02 30.00 24.76 96281102.72 67.07 21-JUN-20:00 30.00 24.76
July 0.107830E+10 1172.24 27-JUL-18:02 31.83 25.86 99691686.93 77.53 14-JUL-21:10 31.83 25.86
August 0.100935E+10 1167.40 04-AUG-08:61 29.08 26.11 99275766.88 56.69 08-AUG-22:10 26.60 23.82
September 0.952795E+09 1166.26 01-SEP-08:61 28.07 24.19 96477785.75 75.91 05-SEP-21:10 23.90 22.65
October 0.875399E+09 1166.76 31-OCT-18:02 25.60 23.22 99630367.79 71.31 27-OCT-21:10 25.60 23.22
November 0.688188E+09 1170.30 28-NOV-19:01 25.00 21.60 97724119.17 72.52 21-NOV-22:10 25.00 21.60
December 0.517763E+09 1161.90 10-DEC-19:02 25.50 22.83 0.101737E+09 72.55 01-DEC-22:10 25.50 22.83
                     
Annual Sum or Average 0.944693E+10         0.118889E+10        
Minimum of Months 0.468641E+09 1155.77   24.40 17.26 93312591.35 56.69   22.88 17.26
Maximum of Months 0.107830E+10 1174.62   31.83 26.11 0.103197E+09 77.53   31.83 25.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124769E+10 2934.61 25-JAN-16:01 17.80 8.74 98674397.11 56.69 14-JAN-00:10 17.80 8.74
February 0.134621E+10 2839.61 03-FEB-16:01 16.42 8.65 89284303.18 56.69 21-FEB-22:19 17.77 14.14
March 0.166089E+10 2946.61 16-MAR-15:01 18.48 9.11 99039525.60 56.69 28-MAR-00:10 23.30 20.65
April 0.206748E+10 2786.13 21-APR-08:61 24.60 17.91 95918996.54 56.69 15-APR-02:30 24.60 17.91
May 0.238560E+10 2795.28 04-MAY-08:61 26.78 22.08 99187989.48 56.69 04-MAY-01:00 26.78 22.08
June 0.256512E+10 2801.07 03-JUN-08:62 28.40 24.58 96029281.02 56.69 17-JUN-04:40 25.60 21.66
July 0.280852E+10 2801.30 23-JUL-08:62 29.60 24.60 99136942.34 56.70 28-JUL-23:10 28.22 24.32
August 0.260115E+10 2785.95 31-AUG-08:61 29.50 24.18 99222747.14 56.70 16-AUG-21:00 29.50 24.18
September 0.263478E+10 2797.06 09-SEP-18:02 30.00 25.09 95953797.58 56.70 08-SEP-22:49 30.00 25.09
October 0.248741E+10 2810.45 17-OCT-08:61 25.78 18.68 99154915.84 56.70 06-OCT-22:10 25.78 18.68
November 0.184491E+10 2801.74 21-NOV-09:01 26.70 21.80 95862986.90 56.69 11-NOV-00:49 26.70 21.80
December 0.129630E+10 2794.26 09-DEC-09:01 26.20 22.58 98543030.39 56.69 05-DEC-22:49 26.20 22.58
                     
Annual Sum or Average 0.249461E+11         0.116601E+10        
Minimum of Months 0.124769E+10 2785.95   16.42 8.65 89284303.18 56.69   17.77 8.74
Maximum of Months 0.280852E+10 2946.61   30.00 25.09 99222747.14 56.70   30.00 25.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.706452E+09 2738.16 08-JAN-16:01 20.92 14.07 0.101991E+09 73.56 03-JAN-22:10 20.92 14.07
February 0.843609E+09 2985.38 28-FEB-09:51 24.40 16.28 94037488.52 74.50 17-FEB-22:10 24.40 16.28
March 0.121010E+10 2923.94 01-MAR-09:51 19.40 15.91 0.104411E+09 76.45 31-MAR-21:10 23.27 18.08
April 0.174020E+10 3067.52 20-APR-08:51 24.40 17.42 0.101259E+09 77.12 10-APR-21:10 24.40 17.42
May 0.233339E+10 2829.03 04-MAY-08:61 26.78 22.08 0.100533E+09 75.16 25-MAY-21:10 23.90 22.59
June 0.258165E+10 2918.15 13-JUN-18:11 25.37 22.49 96602097.84 70.06 21-JUN-20:00 24.40 22.75
July 0.280013E+10 2824.24 30-JUL-08:62 28.58 24.61 0.100069E+09 80.92 14-JUL-21:10 28.58 24.61
August 0.253552E+10 2813.08 11-AUG-15:02 29.82 24.37 99546767.95 58.03 06-AUG-21:10 29.82 24.37
September 0.243686E+10 2794.12 22-SEP-15:02 30.68 25.28 96878338.02 77.35 05-SEP-21:10 30.68 25.28
October 0.212671E+10 2864.68 17-OCT-08:61 25.78 18.68 0.100178E+09 73.12 27-OCT-21:19 23.90 21.88
November 0.139259E+10 2761.15 21-NOV-09:01 26.70 21.80 98377308.19 74.66 21-NOV-22:10 24.40 22.53
December 0.798731E+09 2739.59 09-DEC-09:01 26.20 22.58 0.101464E+09 71.85 07-DEC-22:19 26.20 22.58
                     
Annual Sum or Average 0.215060E+11         0.119535E+10        
Minimum of Months 0.706452E+09 2738.16   19.40 14.07 94037488.52 58.03   20.92 14.07
Maximum of Months 0.280013E+10 3067.52   30.68 25.28 0.104411E+09 80.92   30.68 25.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.586520E+10 2500.07 03-JAN-22:10 22.12 20.55 0.129019E+10 845.98 03-JAN-22:30 21.95 20.39
February 0.534179E+10 2437.93 17-FEB-22:10 23.90 20.81 0.118281E+10 826.04 17-FEB-23:10 23.90 20.81
March 0.604652E+10 2501.33 30-MAR-21:10 23.90 19.88 0.133290E+10 846.29 30-MAR-21:40 23.90 20.02
April 0.622187E+10 2585.99 14-APR-21:10 25.50 22.67 0.135191E+10 874.76 14-APR-21:30 25.30 22.39
May 0.660840E+10 2616.44 22-MAY-21:10 27.70 22.63 0.143456E+10 884.95 19-MAY-21:30 27.70 22.63
June 0.660964E+10 2687.34 29-JUN-21:10 28.90 24.82 0.143666E+10 908.61 29-JUN-21:40 28.90 24.82
July 0.694285E+10 2723.78 29-JUL-21:10 28.80 23.66 0.150223E+10 920.39 31-JUL-21:30 28.85 24.54
August 0.683913E+10 2721.39 21-AUG-21:10 28.22 25.01 0.148703E+10 920.12 21-AUG-21:30 28.05 24.96
September 0.668922E+10 2737.74 22-SEP-21:10 28.30 25.17 0.144927E+10 926.56 22-SEP-21:30 28.30 25.42
October 0.680114E+10 2670.68 25-OCT-21:10 26.60 21.10 0.147159E+10 903.07 25-OCT-21:30 26.40 21.40
November 0.622180E+10 2611.63 10-NOV-22:10 23.22 20.97 0.134756E+10 883.60 10-NOV-22:30 23.05 20.81
December 0.595882E+10 2547.43 10-DEC-22:10 24.32 23.25 0.131173E+10 859.79 08-DEC-23:10 24.32 23.25
                     
Annual Sum or Average 0.761464E+11         0.165984E+11        
Minimum of Months 0.534179E+10 2437.93   22.12 19.88 0.118281E+10 826.04   21.95 20.02
Maximum of Months 0.694285E+10 2737.74   28.90 25.17 0.150223E+10 926.56   28.90 25.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119161E+10 3531.16 25-JAN-16:01 17.80 8.74 98434553.00 56.69 13-JAN-22:19 17.80 8.74
February 0.139076E+10 3501.18 03-FEB-16:01 16.42 8.65 89063554.39 56.69 27-FEB-22:10 21.52 15.05
March 0.176471E+10 3544.40 15-MAR-15:01 17.30 8.90 98778261.02 56.70 31-MAR-21:00 23.10 18.41
April 0.217795E+10 3268.83 06-APR-15:02 25.28 20.24 95786176.78 56.70 14-APR-23:49 25.00 22.59
May 0.250432E+10 3324.00 28-MAY-15:02 28.35 25.51 99139754.96 56.70 15-MAY-23:00 28.35 25.51
June 0.254456E+10 3305.32 04-JUN-15:02 26.83 24.20 95989066.52 56.70 09-JUN-21:19 29.23 24.92
July 0.285299E+10 3314.85 11-JUL-18:02 29.90 24.79 99102565.80 56.70 04-JUL-00:20 29.90 24.79
August 0.270430E+10 3311.92 08-AUG-18:02 28.22 24.20 99189183.26 56.70 17-AUG-21:10 27.80 24.63
September 0.262093E+10 3332.87 30-SEP-15:02 31.10 24.59 95903766.90 56.70 02-SEP-01:00 31.10 24.59
October 0.249347E+10 3298.00 02-OCT-18:02 28.72 24.52 99089228.75 56.70 07-OCT-00:20 25.60 23.64
November 0.185174E+10 3300.50 02-NOV-18:02 27.12 22.55 95722225.46 56.70 17-NOV-23:10 24.13 22.49
December 0.139374E+10 3278.81 31-DEC-16:02 22.52 20.37 98446164.53 56.69 04-DEC-22:10 22.52 20.37
                     
Annual Sum or Average 0.254911E+11         0.116464E+10        
Minimum of Months 0.119161E+10 3268.83   16.42 8.65 89063554.39 56.69   17.80 8.74
Maximum of Months 0.285299E+10 3544.40   31.10 25.51 99189183.26 56.70   31.10 25.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.639177E+09 3415.04 25-JAN-16:01 17.80 8.74 0.102296E+09 75.72 03-JAN-22:10 17.80 8.74
February 0.892608E+09 3412.92 03-FEB-16:01 16.42 8.65 94563045.64 77.62 10-FEB-22:10 23.90 22.01
March 0.130079E+10 3530.54 15-MAR-15:01 17.30 8.90 0.105649E+09 80.15 30-MAR-21:10 23.90 19.88
April 0.187725E+10 3566.57 18-APR-21:51 17.80 13.01 0.101680E+09 82.66 03-APR-21:10 17.80 13.01
May 0.246553E+10 3470.64 10-MAY-16:31 25.53 22.56 0.100389E+09 77.36 25-MAY-21:10 23.90 22.59
June 0.256650E+10 3672.56 13-JUN-18:11 25.37 22.49 96559475.61 71.38 21-JUN-20:00 24.40 22.75
July 0.285102E+10 3338.23 11-JUL-18:02 29.90 24.79 0.100065E+09 83.01 14-JUL-21:10 23.22 22.08
August 0.263982E+10 3366.72 23-AUG-17:52 25.60 22.38 99514029.87 59.09 06-AUG-21:00 25.60 22.38
September 0.242841E+10 3346.27 11-SEP-15:02 25.18 23.90 96735678.51 79.25 05-SEP-21:10 25.18 23.90
October 0.214437E+10 3334.31 13-OCT-16:51 24.40 23.27 99858120.12 71.96 27-OCT-21:19 23.90 21.88
November 0.141904E+10 3330.30 05-NOV-15:02 27.80 23.86 98034884.13 75.80 21-NOV-22:10 24.40 22.53
December 0.872646E+09 3286.77 30-DEC-16:01 22.43 19.50 0.102227E+09 76.22 01-DEC-22:10 22.43 19.50
                     
Annual Sum or Average 0.220972E+11         0.119757E+10        
Minimum of Months 0.639177E+09 3286.77   16.42 8.65 94563045.64 59.09   17.80 8.74
Maximum of Months 0.285102E+10 3672.56   29.90 24.79 0.105649E+09 83.01   25.60 23.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117581E+10 1687.81 25-JAN-16:01 17.80 8.74 98834196.62 56.69 04-JAN-00:40 17.80 8.74
February 0.110498E+10 1615.45 03-FEB-19:02 13.03 7.08 89321790.23 56.69 08-FEB-00:10 20.50 19.00
March 0.115677E+10 1684.63 16-MAR-15:01 18.48 9.11 98939753.24 56.69 28-MAR-23:00 23.30 19.98
April 0.122148E+10 1584.05 14-APR-18:02 27.62 23.31 95801563.16 56.69 03-APR-23:10 27.62 23.31
May 0.135505E+10 1580.08 30-MAY-18:02 29.72 24.14 99135295.27 56.70 16-MAY-21:19 29.72 24.14
June 0.141490E+10 1584.57 28-JUN-18:02 29.90 24.59 95985296.94 56.70 26-JUN-21:30 29.90 24.59
July 0.154620E+10 1590.26 27-JUL-18:02 31.83 25.86 99099068.43 56.69 12-JUL-21:00 31.83 25.86
August 0.152709E+10 1592.99 31-AUG-15:02 32.12 24.95 99192061.77 56.69 29-AUG-21:30 32.12 24.95
September 0.163305E+10 1614.64 20-SEP-15:02 31.78 24.57 95938968.30 56.69 10-SEP-23:40 31.78 24.57
October 0.170982E+10 1615.17 03-OCT-15:02 31.60 25.08 99183120.57 56.70 04-OCT-21:19 26.50 23.17
November 0.144792E+10 1613.13 03-NOV-15:02 28.30 24.32 95899878.46 56.69 09-NOV-22:49 25.00 23.06
December 0.123813E+10 1594.86 06-DEC-16:02 26.02 22.41 98802012.59 56.69 05-DEC-23:49 26.02 22.41
                     
Annual Sum or Average 0.165312E+11         0.116613E+10        
Minimum of Months 0.110498E+10 1580.08   13.03 7.08 89321790.23 56.69   17.80 8.74
Maximum of Months 0.170982E+10 1687.81   32.12 25.86 99192061.77 56.70   32.12 25.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.390202E+11 20500.31 13-JAN-23:00 23.90 21.21 0.179225E+11 11348.40 02-JAN-23:10 23.90 21.21
February 0.361492E+11 20929.34 17-FEB-22:52 23.90 20.81 0.164453E+11 11348.61 14-FEB-23:10 23.90 20.81
March 0.409182E+11 21443.04 27-MAR-22:00 24.40 21.69 0.185013E+11 11348.77 22-MAR-22:10 24.40 21.69
April 0.416616E+11 22576.78 14-APR-21:10 25.50 22.67 0.182338E+11 11348.91 18-APR-22:10 17.62 12.99
May 0.453941E+11 23567.18 22-MAY-22:00 27.20 22.18 0.190615E+11 11348.89 24-MAY-21:10 24.40 22.88
June 0.455794E+11 24108.30 09-JUN-21:10 29.32 24.94 0.185823E+11 11348.89 21-JUN-21:10 24.50 22.87
July 0.476190E+11 24229.92 28-JUL-21:10 29.32 24.20 0.191694E+11 11348.75 14-JUL-22:10 29.32 24.20
August 0.464028E+11 23824.06 02-AUG-21:10 29.32 24.62 0.191526E+11 11347.78 28-AUG-22:19 24.80 22.91
September 0.447764E+11 23851.17 08-SEP-22:00 29.40 24.47 0.184929E+11 11348.58 05-SEP-22:10 29.40 24.47
October 0.443785E+11 22879.29 03-OCT-22:00 27.80 25.31 0.189662E+11 11348.38 27-OCT-22:10 23.80 21.85
November 0.406693E+11 22239.24 03-NOV-22:00 26.70 24.27 0.179740E+11 11348.60 21-NOV-22:40 24.40 22.66
December 0.397642E+11 21193.55 08-DEC-22:53 24.40 22.88 0.181039E+11 11348.60 01-DEC-23:10 24.40 22.88
                     
Annual Sum or Average 0.512333E+12         0.220606E+12        
Minimum of Months 0.361492E+11 20500.31   23.90 20.81 0.164453E+11 11347.78   17.62 12.99
Maximum of Months 0.476190E+11 24229.92   29.40 25.31 0.191694E+11 11348.91   29.40 24.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.418471E+11 21976.45 13-JAN-23:00 23.90 21.21 0.181905E+11 11348.41 02-JAN-23:10 23.90 21.21
February 0.387671E+11 22426.11 17-FEB-22:52 23.90 20.81 0.166491E+11 11348.61 14-FEB-23:10 23.90 20.81
March 0.438870E+11 22892.26 27-MAR-22:00 24.40 21.69 0.186917E+11 11348.78 22-MAR-22:10 24.40 21.69
April 0.445327E+11 23876.77 14-APR-21:10 25.50 22.67 0.183481E+11 11348.91 18-APR-22:10 17.62 12.99
May 0.483120E+11 24896.52 22-MAY-21:10 27.70 22.63 0.191320E+11 11348.89 24-MAY-21:10 24.40 22.88
June 0.482846E+11 25326.66 09-JUN-21:10 29.32 24.94 0.186243E+11 11348.90 21-JUN-21:10 24.50 22.87
July 0.503516E+11 25443.42 28-JUL-21:10 29.32 24.20 0.192033E+11 11348.75 14-JUL-22:10 29.32 24.20
August 0.491652E+11 25040.30 02-AUG-21:10 29.32 24.62 0.192041E+11 11347.80 28-AUG-22:19 24.80 22.91
September 0.473833E+11 25058.49 08-SEP-21:10 29.90 24.64 0.185385E+11 11348.58 05-SEP-22:10 29.90 24.64
October 0.470899E+11 24136.99 03-OCT-21:10 27.80 25.31 0.190367E+11 11348.39 27-OCT-22:10 23.80 21.85
November 0.433969E+11 23564.99 03-NOV-22:00 26.70 24.27 0.181151E+11 11348.61 21-NOV-22:40 24.40 22.66
December 0.425813E+11 22548.36 08-DEC-22:53 24.40 22.88 0.183336E+11 11348.60 01-DEC-23:10 24.40 22.88
                     
Annual Sum or Average 0.545599E+12         0.222067E+12        
Minimum of Months 0.387671E+11 21976.45   23.90 20.81 0.166491E+11 11347.80   17.62 12.99
Maximum of Months 0.503516E+11 25443.42   29.90 25.31 0.192041E+11 11348.91   29.90 24.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.520583E+11 28426.10 01-JAN-11:50 26.20 21.28 0.187318E+11 11319.58 21-JAN-18:19 17.60 13.28
February 0.477814E+11 28484.65 11-FEB-11:50 27.70 23.78 0.169244E+11 11319.58 04-FEB-18:19 27.70 23.78
March 0.537573E+11 28775.84 27-MAR-10:50 26.42 21.73 0.187518E+11 11319.66 25-MAR-17:19 26.42 21.73
April 0.540190E+11 29942.21 15-APR-10:50 29.63 22.91 0.181579E+11 11319.66 08-APR-17:19 29.63 22.91
May 0.572619E+11 30091.05 31-MAY-10:50 32.52 24.26 0.187782E+11 11319.66 20-MAY-17:19 32.52 24.26
June 0.565848E+11 30466.41 11-JUN-10:50 31.02 23.55 0.181880E+11 11319.66 10-JUN-17:19 31.02 23.55
July 0.591000E+11 30621.11 23-JUL-10:50 32.75 24.78 0.187891E+11 11319.66 01-JUL-17:19 32.75 24.78
August 0.578781E+11 30363.51 19-AUG-10:50 31.60 24.73 0.187906E+11 11319.65 19-AUG-17:19 30.53 24.22
September 0.563706E+11 30273.10 09-SEP-10:50 31.02 25.29 0.181821E+11 11319.65 23-SEP-17:19 30.40 24.46
October 0.568084E+11 29986.95 07-OCT-10:50 31.42 24.17 0.187748E+11 11319.65 07-OCT-17:19 28.13 23.44
November 0.528530E+11 28739.22 07-NOV-11:50 27.12 21.36 0.181490E+11 11319.57 04-NOV-17:19 27.12 21.36
December 0.523903E+11 28730.43 09-DEC-11:50 27.20 22.50 0.187371E+11 11319.59 16-DEC-18:19 19.40 15.49
                     
Annual Sum or Average 0.656863E+12         0.220955E+12        
Minimum of Months 0.477814E+11 28426.10   26.20 21.28 0.169244E+11 11319.57   17.60 13.28
Maximum of Months 0.591000E+11 30621.11   32.75 25.29 0.187906E+11 11319.66   32.75 24.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.106883E+11 5177.74 02-JAN-14:50 28.90 23.62 0.133212E+10 896.52 02-JAN-22:10 21.93 19.67
February 0.102359E+11 5317.16 11-FEB-15:30 28.05 24.05 0.123091E+10 884.92 17-FEB-22:19 23.90 20.81
March 0.116873E+11 5213.64 27-MAR-21:10 24.90 21.81 0.139524E+10 918.01 27-MAR-21:19 24.80 21.78
April 0.125828E+11 5584.69 15-APR-17:17 31.13 22.55 0.142115E+10 969.81 14-APR-21:10 31.13 22.55
May 0.137085E+11 5597.82 31-MAY-19:20 28.13 24.02 0.154498E+10 986.22 31-MAY-21:10 27.17 24.28
June 0.138521E+11 6340.22 29-JUN-18:03 30.00 24.76 0.155971E+10 1007.35 28-JUN-21:10 30.00 24.76
July 0.146955E+11 7576.18 29-JUL-16:10 35.40 24.35 0.163070E+10 1007.37 28-JUL-22:19 35.40 24.35
August 0.142192E+11 6650.37 19-AUG-17:02 30.82 24.23 0.160001E+10 1007.35 18-AUG-21:10 30.82 24.23
September 0.139835E+11 7133.26 09-SEP-13:20 31.50 25.30 0.155924E+10 1007.38 08-SEP-22:19 31.50 25.30
October 0.138781E+11 6234.36 07-OCT-14:00 30.00 23.64 0.155824E+10 999.94 06-OCT-21:10 30.00 23.64
November 0.122528E+11 5506.95 08-NOV-15:20 28.70 21.70 0.140444E+10 955.80 10-NOV-22:10 23.22 20.97
December 0.110750E+11 5433.71 09-DEC-15:30 26.40 22.31 0.136480E+10 926.68 08-DEC-22:19 26.40 22.31
                     
Annual Sum or Average 0.152859E+12         0.176015E+11        
Minimum of Months 0.102359E+11 5177.74   24.90 21.70 0.123091E+10 884.92   21.93 19.67
Maximum of Months 0.146955E+11 7576.18   35.40 25.30 0.163070E+10 1007.38   35.40 25.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 3114471.28 418.26 04-FEB-07:10 5.28
March 11683.38 18.47 16-MAR-07:07 6.97
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 3126154.66      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 3114471.28 418.26   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 42928.75 24.60 04-FEB-10:10 13.27
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 42928.75      
Minimum of Months 0.00 0.00   13.27
Maximum of Months 42928.75 24.60   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 44742.22 20.41 04-FEB-08:00 6.70
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 44742.22      
Minimum of Months 0.00 0.00   6.70
Maximum of Months 44742.22 20.41   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4160849.34 989.29 25-JAN-19:03 15.40
February 8719804.52 1004.41 03-FEB-19:03 13.03
March 2492580.85 978.76 19-MAR-15:04 16.78
April 1167977.08 928.63 20-APR-08:04 23.48
May 1211761.45 807.65 08-MAY-08:04 25.18
June 1040385.35 666.99 22-JUN-08:04 24.90
July 523280.00 467.29 04-JUL-08:05 28.07
August 580584.02 720.38 10-AUG-08:04 24.60
September 343280.71 657.80 15-SEP-08:04 25.37
October 673059.84 946.48 18-OCT-08:04 26.20
November 1838275.68 989.14 11-NOV-09:04 15.05
December 4249855.93 987.80 26-DEC-19:04 13.80
         
Annual Sum or Average 27001694.77      
Minimum of Months 343280.71 467.29   13.03
Maximum of Months 8719804.52 1004.41   28.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7615066.69 963.71 22-JAN-09:03 14.60
February 14581111.67 968.83 03-FEB-19:03 13.03
March 3819286.63 989.19 19-MAR-15:04 16.78
April 702797.84 922.26 02-APR-08:53 21.10
May 942755.56 901.50 26-MAY-08:04 25.68
June 727033.21 624.49 19-JUN-08:04 26.60
July 426602.34 415.18 31-JUL-08:05 28.58
August 560007.74 720.74 10-AUG-08:04 24.60
September 640630.51 820.05 15-SEP-08:04 25.37
October 939445.98 942.85 18-OCT-08:04 26.20
November 2733013.97 945.55 28-NOV-19:04 25.00
December 10163350.81 955.49 27-DEC-16:03 20.00
         
Annual Sum or Average 43851102.93      
Minimum of Months 426602.34 415.18   13.03
Maximum of Months 14581111.67 989.19   28.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 893138.38 275.92 25-JAN-09:03 11.57
February 614044.87 268.90 03-FEB-19:05 13.03
March 559239.46 268.27 20-MAR-08:05 11.28
April 283839.67 224.70 02-APR-08:54 21.10
May 223975.36 187.81 27-MAY-08:56 23.90
June 37963.09 101.32 24-JUN-18:07 26.20
July 28245.27 64.08 17-JUL-18:07 28.22
August 115801.43 158.51 13-AUG-18:07 28.62
September 124522.78 137.45 17-SEP-18:07 29.90
October 205158.91 225.80 21-OCT-21:56 25.00
November 389401.91 267.73 27-NOV-09:05 15.65
December 620367.88 265.51 12-DEC-09:06 13.07
         
Annual Sum or Average 4095699.02      
Minimum of Months 28245.27 64.08   11.28
Maximum of Months 893138.38 275.92   29.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3304263.62 940.29 25-JAN-16:04 17.80
February 8167122.22 954.28 03-FEB-19:03 13.03
March 2153484.95 950.80 19-MAR-15:04 16.78
April 57235.50 568.00 19-APR-08:05 19.37
May 31681.05 316.81 27-MAY-18:05 24.90
June 15957.33 186.17 15-JUN-08:04 23.68
July 0.00 0.00 01-JUL-00:10 26.83
August 119275.03 482.73 12-AUG-18:05 26.60
September 0.00 0.00 01-SEP-00:10 27.05
October 62494.34 405.61 18-OCT-08:04 26.20
November 595543.19 901.05 12-NOV-16:04 20.00
December 4608411.67 943.96 26-DEC-19:04 13.80
         
Annual Sum or Average 19115468.89      
Minimum of Months 0.00 0.00   13.03
Maximum of Months 8167122.22 954.28   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9098273.37 950.97 25-JAN-16:03 17.80
February 13057989.90 966.53 03-FEB-16:03 16.42
March 3242099.15 951.25 19-MAR-15:04 16.78
April 323191.28 646.60 01-APR-21:54 22.80
May 112819.34 577.87 28-MAY-06:55 25.00
June 990.96 13.21 18-JUN-21:56 23.90
July 0.00 0.00 01-JUL-00:10 26.83
August 113346.78 462.13 28-AUG-18:05 26.02
September 68062.00 474.03 07-SEP-06:55 24.40
October 188957.84 438.29 13-OCT-16:55 24.40
November 1191935.52 822.26 12-NOV-16:04 20.00
December 12293841.69 953.11 26-DEC-16:04 18.12
         
Annual Sum or Average 39691507.83      
Minimum of Months 0.00 0.00   16.42
Maximum of Months 13057989.90 966.53   26.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22796268.52 1136.91 25-JAN-19:03 15.40
February 26237996.68 1140.88 03-FEB-19:03 13.03
March 15922916.25 1160.23 19-MAR-15:04 16.78
April 1599174.25 1014.38 10-APR-08:04 24.60
May 1435289.96 1023.54 08-MAY-08:04 25.18
June 1303644.17 1062.52 15-JUN-08:04 23.68
July 844478.73 801.42 03-JUL-08:04 26.88
August 986843.70 1063.88 03-AUG-08:04 23.98
September 815460.51 848.55 15-SEP-08:04 25.37
October 1020453.74 964.76 18-OCT-08:04 26.20
November 8550244.08 1080.53 11-NOV-19:04 19.72
December 28080932.65 1118.64 15-DEC-16:04 19.32
         
Annual Sum or Average 0.109594E+09      
Minimum of Months 815460.51 801.42   13.03
Maximum of Months 28080932.65 1160.23   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 36886859.15 1110.70 31-JAN-16:04 17.12
February 35090235.06 1104.68 12-FEB-16:04 20.60
March 18499548.16 1156.75 19-MAR-15:04 16.78
April 771005.13 1012.90 12-APR-08:04 26.78
May 1072443.71 1062.06 26-MAY-08:04 25.68
June 911905.26 960.66 18-JUN-08:04 25.40
July 461521.04 352.44 31-JUL-08:05 28.58
August 866154.94 1026.22 25-AUG-08:04 25.68
September 1117072.00 1031.41 25-SEP-08:04 24.60
October 1366711.02 998.08 18-OCT-08:04 26.20
November 10480826.23 1019.83 20-NOV-09:04 25.18
December 46292084.12 1161.96 15-DEC-16:03 19.32
         
Annual Sum or Average 0.153816E+09      
Minimum of Months 461521.04 352.44   16.78
Maximum of Months 46292084.12 1161.96   28.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 752108.65 521.73 30-JAN-16:05 14.90
February 3427249.59 446.67 03-FEB-19:05 13.03
March 1436287.27 498.25 15-MAR-08:03 11.78
April 167001.56 505.54 19-APR-08:03 19.37
May 58543.32 129.94 27-MAY-08:06 23.90
June 17218.86 122.63 13-JUN-08:06 25.87
July 5981.64 31.07 24-JUL-08:06 29.08
August 15065.09 72.26 29-AUG-08:06 27.38
September 60095.23 126.44 05-SEP-08:06 24.50
October 39237.90 113.98 01-OCT-08:06 22.48
November 284172.73 327.72 12-NOV-09:05 14.68
December 641886.80 381.14 15-DEC-19:05 17.52
         
Annual Sum or Average 6904848.64      
Minimum of Months 5981.64 31.07   11.78
Maximum of Months 3427249.59 521.73   29.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:05 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 20.40
February 3980391.55 680.24 04-FEB-07:10 5.28
March 313754.74 94.95 16-MAR-07:10 6.97
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 4294146.29      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 3980391.55 680.24   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136942E+11 13190.31 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.123646E+11 13190.31 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.137364E+11 13190.31 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.132299E+11 13190.31 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.137180E+11 13190.31 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.132906E+11 13190.31 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.136573E+11 13190.31 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.137417E+11 13190.31 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.132352E+11 13190.31 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.136889E+11 13190.31 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.132800E+11 13190.31 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.136573E+11 13190.31 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.161294E+12     0.143105E+12    
Minimum of Months 0.123646E+11 13190.31   0.109726E+11 9632.53  
Maximum of Months 0.137417E+11 13190.31   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.620421E+09 597.59 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.560184E+09 597.59 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.622334E+09 597.59 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.599386E+09 597.59 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.621497E+09 597.59 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.602135E+09 597.59 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.618748E+09 597.59 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.622573E+09 597.59 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.599625E+09 597.59 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.620182E+09 597.59 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.601657E+09 597.59 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.618748E+09 597.59 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.730749E+10     0.101856E+11    
Minimum of Months 0.560184E+09 597.59   0.780982E+09 685.60  
Maximum of Months 0.622573E+09 597.59   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.718450E+09 692.02 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.648695E+09 692.02 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.720665E+09 692.02 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.694091E+09 692.02 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.719696E+09 692.02 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.697275E+09 692.02 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.716513E+09 692.02 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.720942E+09 692.02 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.694368E+09 692.02 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.718174E+09 692.02 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.696721E+09 692.02 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.716513E+09 692.02 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.846210E+10     0.117950E+11    
Minimum of Months 0.648695E+09 692.02   0.904380E+09 793.93  
Maximum of Months 0.720942E+09 692.02   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.261454E+09 251.84 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.236069E+09 251.84 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.262260E+09 251.84 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.252589E+09 251.84 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.261907E+09 251.84 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.253748E+09 251.84 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.260749E+09 251.84 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.262360E+09 251.84 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.252690E+09 251.84 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.261353E+09 251.84 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.253546E+09 251.84 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.260749E+09 251.84 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.307947E+10     0.359760E+10    
Minimum of Months 0.236069E+09 251.84   0.275845E+09 242.16  
Maximum of Months 0.262360E+09 251.84   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.337502E+09 325.08 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.304733E+09 325.08 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.338542E+09 325.08 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.326059E+09 325.08 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.338087E+09 325.08 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.327554E+09 325.08 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.336592E+09 325.08 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.338672E+09 325.08 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.326189E+09 325.08 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.337372E+09 325.08 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.327294E+09 325.08 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.336592E+09 325.08 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.397519E+10     0.679355E+11    
Minimum of Months 0.304733E+09 325.08   0.520895E+10 4572.80  
Maximum of Months 0.338672E+09 325.08   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.130117E+10 1701.53 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.114737E+10 1701.53 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.121364E+10 1701.53 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.113363E+10 1701.53 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.114198E+10 1701.53 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.111524E+10 1701.53 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.110146E+10 1701.53 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.116331E+10 1701.53 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.117481E+10 1701.53 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.126247E+10 1701.53 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.123468E+10 1701.53 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.131148E+10 1701.53 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.143012E+11     0.143405E+11    
Minimum of Months 0.110146E+10 1701.53   0.109956E+10 965.27  
Maximum of Months 0.131148E+10 1701.53   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.941516E+10 9504.80 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.848037E+10 9504.80 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.937977E+10 9504.80 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.900787E+10 9504.80 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.932221E+10 9504.80 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.904812E+10 9504.80 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.924837E+10 9504.80 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.934227E+10 9504.80 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.904204E+10 9504.80 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.938497E+10 9504.80 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.910724E+10 9504.80 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.940732E+10 9504.80 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110186E+12     0.148998E+12    
Minimum of Months 0.848037E+10 9504.80   0.114244E+11 10029.21  
Maximum of Months 0.941516E+10 9504.80   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123557E+09 111.79 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 0.111584E+09 111.79 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 0.122575E+09 111.79 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 0.119713E+09 111.79 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 0.123066E+09 111.79 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 0.118764E+09 111.79 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 0.124032E+09 111.79 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 0.122575E+09 111.79 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 0.119746E+09 111.79 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 0.123541E+09 111.79 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 0.119238E+09 111.79 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 0.124048E+09 111.79 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.145244E+10     0.256575E+10    
Minimum of Months 0.111584E+09 111.79   0.196843E+09 232.19  
Maximum of Months 0.124048E+09 111.79   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.193865E+10 1867.32 02-JAN-20:10 0.00 0.00
February 0.175042E+10 1867.32 01-FEB-20:10 0.00 0.00
March 0.194462E+10 1867.32 01-MAR-20:10 0.00 0.00
April 0.187292E+10 1867.32 03-APR-19:10 0.00 0.00
May 0.194201E+10 1867.32 01-MAY-19:10 0.00 0.00
June 0.188151E+10 1867.32 01-JUN-19:10 0.00 0.00
July 0.193342E+10 1867.32 03-JUL-19:10 0.00 0.00
August 0.194537E+10 1867.32 01-AUG-19:10 0.00 0.00
September 0.187367E+10 1867.32 01-SEP-19:10 0.00 0.00
October 0.193790E+10 1867.32 02-OCT-19:10 0.00 0.00
November 0.188002E+10 1867.32 01-NOV-19:10 0.00 0.00
December 0.193342E+10 1867.32 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.228339E+11     0.00 0.00
Minimum of Months 0.175042E+10 1867.32   0.00 0.00
Maximum of Months 0.194537E+10 1867.32   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.277206E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.245660E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.265720E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.249121E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.253041E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.243533E+10 2988.03 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.248349E+10 2988.03 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.256649E+10 2988.03 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.253987E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.269863E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.264279E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.275615E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.310302E+11     0.175857E+12    
Minimum of Months 0.243533E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.277206E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.277206E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.245660E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.265720E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.249121E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.253041E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.243533E+10 2988.03 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.248349E+10 2988.03 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.256649E+10 2988.03 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.253987E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.269863E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.264279E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.275615E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.310302E+11     0.175857E+12    
Minimum of Months 0.243533E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.277206E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110133E+10 1060.81 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.994402E+09 1060.81 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.110473E+10 1060.81 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.106399E+10 1060.81 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.110324E+10 1060.81 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.106887E+10 1060.81 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.109836E+10 1060.81 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.110515E+10 1060.81 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.106442E+10 1060.81 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.110091E+10 1060.81 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.106802E+10 1060.81 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.109836E+10 1060.81 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.129718E+11     0.433742E+12    
Minimum of Months 0.994402E+09 1060.81   0.332733E+11 16487.34  
Maximum of Months 0.110515E+10 1060.81   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.205176E+10 1976.27 02-JAN-20:10 0.00 0.00
February 0.185255E+10 1976.27 01-FEB-20:10 0.00 0.00
March 0.205809E+10 1976.27 01-MAR-20:10 0.00 0.00
April 0.198220E+10 1976.27 03-APR-19:10 0.00 0.00
May 0.205532E+10 1976.27 01-MAY-19:10 0.00 0.00
June 0.199129E+10 1976.27 01-JUN-19:10 0.00 0.00
July 0.204623E+10 1976.27 03-JUL-19:10 0.00 0.00
August 0.205888E+10 1976.27 01-AUG-19:10 0.00 0.00
September 0.198299E+10 1976.27 01-SEP-19:10 0.00 0.00
October 0.205097E+10 1976.27 02-OCT-19:10 0.00 0.00
November 0.198971E+10 1976.27 01-NOV-19:10 0.00 0.00
December 0.204623E+10 1976.27 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.241662E+11     0.00 0.00
Minimum of Months 0.185255E+10 1976.27   0.00 0.00
Maximum of Months 0.205888E+10 1976.27   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.136942E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.137364E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.132299E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.137180E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.132906E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.132352E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.136889E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.132800E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.161294E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.620421E+09 0.864900E+09 0.00 0.00 0.00 0.00 14239302.80 99038833.52
February 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 22475196.53 61483557.87
March 0.199990E+10 0.622334E+09 0.866718E+09 0.00 0.00 0.00 0.00 30107617.44 51673917.60
April 0.192973E+10 0.599386E+09 0.835931E+09 0.00 0.00 0.00 0.00 57122928.74 9300881.10
May 0.199475E+10 0.621497E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.109977E+09 309686.98
June 0.193394E+10 0.602135E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.135176E+09 1103.79
July 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.145249E+09 152349.15
August 0.199896E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.146695E+09 3098.68
September 0.192879E+10 0.599625E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.120930E+09 58339.32
October 0.199148E+10 0.620182E+09 0.864640E+09 0.00 0.00 0.00 0.00 95130690.97 574129.94
November 0.192552E+10 0.601657E+09 0.838269E+09 0.00 0.00 0.00 0.00 50210192.30 27117425.92
December 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 17590718.78 81556883.71
                   
Annual Sum or Average 0.234744E+11 0.730749E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.944903E+09 0.331270E+09
Minimum of Months 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 14239302.80 1103.79
Maximum of Months 0.199990E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.146695E+09 99038833.52



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.718450E+09 0.100156E+10 0.00 0.00 0.00 0.00 9211952.08 37038012.69
February 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 13363593.74 24498333.74
March 0.231589E+10 0.720665E+09 0.100366E+10 0.00 0.00 0.00 0.00 15320439.08 20764526.29
April 0.223463E+10 0.694091E+09 0.968011E+09 0.00 0.00 0.00 0.00 24885028.17 4911382.65
May 0.230993E+10 0.719696E+09 0.100276E+10 0.00 0.00 0.00 0.00 44798390.70 351807.21
June 0.223950E+10 0.697275E+09 0.971170E+09 0.00 0.00 0.00 0.00 54794707.50 660.40
July 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 58754015.62 74184.05
August 0.231480E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 59332897.55 2632.61
September 0.223354E+10 0.694368E+09 0.968312E+09 0.00 0.00 0.00 0.00 50315216.64 17801.52
October 0.230614E+10 0.718174E+09 0.100126E+10 0.00 0.00 0.00 0.00 41560042.16 445190.28
November 0.222975E+10 0.696721E+09 0.970719E+09 0.00 0.00 0.00 0.00 25224934.19 11409253.60
December 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 10733907.61 31110894.55
                   
Annual Sum or Average 0.271834E+11 0.846210E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.408295E+09 0.130625E+09
Minimum of Months 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 9211952.08 660.40
Maximum of Months 0.231589E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 59332897.55 37038012.69



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 24358950.63 79774078.35
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 35517887.68 51187391.61
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 42838636.25 43481111.86
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 65088703.85 8358578.96
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.104592E+09 678200.53
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 0.120434E+09 5355.35
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.130441E+09 376898.51
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.135898E+09 30889.80
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 0.114965E+09 44654.94
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.100379E+09 745879.14
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 63274298.34 24330560.74
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 28390248.65 66769709.99
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 0.966178E+09 0.275783E+09
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 24358950.63 5355.35
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.135898E+09 79774078.35



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.261454E+09 0.305485E+09 0.00 0.00 0.00 0.00 14054292.43 45847198.88
February 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 20620717.77 29342614.70
March 0.376747E+09 0.262260E+09 0.306128E+09 0.00 0.00 0.00 0.00 25130490.52 24943608.96
April 0.363528E+09 0.252589E+09 0.295253E+09 0.00 0.00 0.00 0.00 38296692.50 4651450.56
May 0.375778E+09 0.261907E+09 0.305852E+09 0.00 0.00 0.00 0.00 61927777.08 339137.48
June 0.364321E+09 0.253748E+09 0.296217E+09 0.00 0.00 0.00 0.00 71421824.20 738.85
July 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 76979300.26 145137.28
August 0.376571E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 79808350.95 10997.41
September 0.363352E+09 0.252690E+09 0.295345E+09 0.00 0.00 0.00 0.00 67796310.61 14418.73
October 0.375161E+09 0.261353E+09 0.305393E+09 0.00 0.00 0.00 0.00 58777612.59 402957.38
November 0.362735E+09 0.253546E+09 0.296079E+09 0.00 0.00 0.00 0.00 36887103.98 13892362.64
December 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 16485862.86 38289838.04
                   
Annual Sum or Average 0.442217E+10 0.307947E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.568186E+09 0.157880E+09
Minimum of Months 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 14054292.43 738.85
Maximum of Months 0.376747E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 79808350.95 45847198.88



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.337502E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 31884168.22 0.130047E+09
February 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 47497042.33 84897025.64
March 0.155131E+10 0.338542E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 57400014.95 72027282.91
April 0.149688E+10 0.326059E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 95157429.28 13888869.81
May 0.154732E+10 0.338087E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.169756E+09 514671.91
June 0.150015E+10 0.327554E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.208083E+09 37419.61
July 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.230565E+09 402046.71
August 0.155059E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.227612E+09 31374.61
September 0.149615E+10 0.326189E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.201327E+09 190906.44
October 0.154478E+10 0.337372E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.167825E+09 368306.34
November 0.149361E+10 0.327294E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 96442755.33 34930433.60
December 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 42706270.45 0.106965E+09
                   
Annual Sum or Average 0.182090E+11 0.397519E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.157625E+10 0.444301E+09
Minimum of Months 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 31884168.22 31374.61
Maximum of Months 0.155131E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.230565E+09 0.130047E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.130117E+10 0.121771E+10 0.00 0.00 0.00 0.00 28108461.24 0.260919E+09
February 0.236489E+11 0.114737E+10 0.109956E+10 0.00 0.00 0.00 0.00 44828664.86 0.167932E+09
March 0.262800E+11 0.121364E+10 0.122027E+10 0.00 0.00 0.00 0.00 61062598.23 0.142399E+09
April 0.253579E+11 0.113363E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.121630E+09 38362746.53
May 0.262123E+11 0.114198E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.235240E+09 4442712.92
June 0.254132E+11 0.111524E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.293676E+09 77837.06
July 0.261570E+11 0.110146E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.322753E+09 1332177.10
August 0.262677E+11 0.116331E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.317861E+09 218623.85
September 0.253456E+11 0.117481E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.260897E+09 879350.82
October 0.261693E+11 0.126247E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.197632E+09 6081386.41
November 0.253025E+11 0.123468E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.104162E+09 82155829.39
December 0.261570E+11 0.131148E+10 0.121533E+10 0.00 0.00 0.00 0.00 35062676.87 0.216044E+09
                   
Annual Sum or Average 0.308468E+12 0.143012E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.202291E+10 0.920845E+09
Minimum of Months 0.236489E+11 0.110146E+10 0.109956E+10 0.00 0.00 0.00 0.00 28108461.24 77837.06
Maximum of Months 0.262800E+11 0.131148E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.322753E+09 0.260919E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.941516E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.122207E+09 0.690083E+09
February 0.702046E+11 0.848037E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.184003E+09 0.451224E+09
March 0.780153E+11 0.937977E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.218567E+09 0.378467E+09
April 0.752779E+11 0.900787E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.381273E+09 0.100064E+09
May 0.778146E+11 0.932221E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.689469E+09 11544518.99
June 0.754422E+11 0.904812E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.842676E+09 137923.65
July 0.776503E+11 0.924837E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.928055E+09 3911860.01
August 0.779788E+11 0.934227E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.923131E+09 501762.97
September 0.752414E+11 0.904204E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.774104E+09 1820579.83
October 0.776868E+11 0.938497E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.617840E+09 15643186.00
November 0.751137E+11 0.910724E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.360003E+09 0.227001E+09
December 0.776503E+11 0.940732E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.143900E+09 0.579078E+09
                   
Annual Sum or Average 0.915726E+12 0.110186E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.618523E+10 0.245948E+10
Minimum of Months 0.702046E+11 0.848037E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.122207E+09 137923.65
Maximum of Months 0.780153E+11 0.941516E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.928055E+09 0.690083E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 11838020.96 55142428.09
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 18131465.69 33390894.98
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 25786763.39 29621929.51
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 45013744.11 3884291.42
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 84003382.83 168032.74
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.103190E+09 9801.67
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.114334E+09 23421.14
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.111797E+09 89604.51
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 99588292.47 0.00
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 82505913.55 62942.55
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 45377354.47 13675413.42
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 17627246.15 44859198.56
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.759193E+09 0.180928E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 11838020.96 0.00
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.114334E+09 55142428.09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 10168292.75 57955978.35
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 14999821.89 37268723.19
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 20999090.49 33695901.91
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 39883875.69 7331580.22
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 82060838.82 401490.61
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.102300E+09 40917.85
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.113280E+09 381389.45
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.111215E+09 141480.60
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 98333702.31 77395.29
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 80972651.41 265822.97
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 43788758.34 15822403.67
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 15504648.14 47509314.39
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.733507E+09 0.200892E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 10168292.75 40917.85
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.113280E+09 57955978.35



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.123557E+09 0.217935E+09 0.00 0.00 0.00 0.00 72324.52 38188229.45
February 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 129639.81 27680474.38
March 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 188648.36 26983282.30
April 0.00 0.119713E+09 0.210923E+09 0.00 0.00 0.00 0.00 1334714.40 14335040.11
May 0.00 0.123066E+09 0.217879E+09 0.00 0.00 0.00 0.00 4265460.70 5874935.37
June 0.00 0.118764E+09 0.210812E+09 0.00 0.00 0.00 0.00 6988415.41 2306475.53
July 0.00 0.124032E+09 0.217991E+09 0.00 0.00 0.00 0.00 9497699.05 2480283.89
August 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 8486748.56 2202544.74
September 0.00 0.119746E+09 0.210923E+09 0.00 0.00 0.00 0.00 7378581.64 3662687.50
October 0.00 0.123541E+09 0.217935E+09 0.00 0.00 0.00 0.00 3778849.13 5715811.59
November 0.00 0.119238E+09 0.210867E+09 0.00 0.00 0.00 0.00 712275.33 16409959.58
December 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 113329.60 33696559.31
                   
Annual Sum or Average 0.00 0.145244E+10 0.256575E+10 0.00 0.00 0.00 0.00 42946686.50 0.179536E+09
Minimum of Months 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 72324.52 2202544.74
Maximum of Months 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 9497699.05 38188229.45



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 3003374.88 16081504.02
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 4430410.58 10294778.89
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 6126433.24 8922600.09
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 11419585.05 1701293.73
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 23124325.83 91682.15
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 28740489.07 2838.37
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 31779405.47 60834.41
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 31251970.50 26248.06
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 27656098.26 8246.64
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 22897938.01 58520.03
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 12478821.37 4371697.91
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 4502923.54 13262255.49
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 0.207412E+09 54882499.79
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 3003374.88 2838.37
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 31779405.47 16081504.02



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 11759018.21 55689388.13
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 18057081.36 33828967.02
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 25674674.38 30370209.02
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 44838686.38 4016264.90
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 83831457.31 174098.42
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.103012E+09 9804.58
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.114196E+09 24377.30
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.111687E+09 91007.42
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 99448393.27 0.00
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 82375904.44 71762.81
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 45281389.78 13856273.40
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 17588577.51 45028141.88
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.757750E+09 0.183160E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 11759018.21 0.00
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.114196E+09 55689388.13



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 9765417.82 58648329.02
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 14613801.45 37929426.41
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 20719011.60 34119749.02
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 39491454.20 7696504.93
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 81768728.00 555773.02
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.102071E+09 68594.88
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.113116E+09 440651.95
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.111104E+09 141944.66
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 98075236.25 136692.85
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 80591619.60 385452.02
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 43358309.04 16398363.00
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 15377087.93 46811981.22
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.730052E+09 0.203333E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 9765417.82 68594.88
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.113116E+09 58648329.02



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.193865E+10 0.00 0.00 0.00 0.00 0.00 14977693.54 67432583.72
February 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 22717768.26 43447034.83
March 0.387034E+10 0.194462E+10 0.00 0.00 0.00 0.00 0.00 27172713.48 36918946.92
April 0.373454E+10 0.187292E+10 0.00 0.00 0.00 0.00 0.00 43781565.65 8467986.59
May 0.386038E+10 0.194201E+10 0.00 0.00 0.00 0.00 0.00 81709764.50 650766.77
June 0.374269E+10 0.188151E+10 0.00 0.00 0.00 0.00 0.00 98290240.42 239.88
July 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 0.107385E+09 129606.78
August 0.386853E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 0.107500E+09 28327.23
September 0.373273E+10 0.187367E+10 0.00 0.00 0.00 0.00 0.00 91427135.68 14614.98
October 0.385404E+10 0.193790E+10 0.00 0.00 0.00 0.00 0.00 74035717.04 829569.40
November 0.372639E+10 0.188002E+10 0.00 0.00 0.00 0.00 0.00 45093175.78 21466899.86
December 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 19294761.87 55679921.08
                   
Annual Sum or Average 0.454292E+11 0.228339E+11 0.00 0.00 0.00 0.00 0.00 0.733385E+09 0.235066E+09
Minimum of Months 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 14977693.54 239.88
Maximum of Months 0.387034E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 0.107500E+09 67432583.72



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 11449410.55 55769802.25
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 17585256.61 33762079.80
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 25064597.04 29889379.99
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 44080196.63 3957144.17
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 82938941.78 189682.71
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 0.102162E+09 11764.22
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113274E+09 26684.76
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.110752E+09 94815.60
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 98588737.04 0.00
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 81486324.32 62400.79
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 44587243.14 13820085.53
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 17158151.45 45389492.13
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 0.749128E+09 0.182973E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 11449410.55 0.00
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.113274E+09 55769802.25



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 9726204.14 59173286.71
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 14422429.20 38407562.99
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 20363583.04 35225761.85
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 39125959.42 7975948.93
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 81058054.92 460721.85
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 0.101284E+09 101396.18
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112288E+09 554578.99
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.110186E+09 151833.23
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 97434128.00 112795.31
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 80133402.45 180198.87
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 43036517.30 15837206.94
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 14998606.13 48301646.59
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 0.724057E+09 0.206483E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 9726204.14 101396.18
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.112288E+09 59173286.71



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 5768836.52 29078872.81
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 8902444.11 17606618.11
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 12770555.30 15607567.57
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 22545542.49 2032657.12
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 42454000.32 95090.36
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 52282237.56 6016.96
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 57966934.05 12887.86
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 56659905.15 47501.06
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 50368829.04 0.00
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 41544503.34 36522.14
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 22684764.77 7247714.92
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 8686425.11 23729649.14
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 0.382635E+09 95501098.04
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 5768836.52 0.00
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 57966934.05 29078872.81



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.277206E+10 0.149358E+11 0.00 0.00 0.00 0.00 21202753.48 0.185147E+09
February 0.415303E+11 0.245660E+10 0.134904E+11 0.00 0.00 0.00 0.00 30971472.54 0.126839E+09
March 0.461508E+11 0.265720E+10 0.149358E+11 0.00 0.00 0.00 0.00 32341139.07 0.111976E+09
April 0.445315E+11 0.249121E+10 0.144540E+11 0.00 0.00 0.00 0.00 62484126.40 40513463.61
May 0.460320E+11 0.253041E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.123120E+09 6495855.55
June 0.446286E+11 0.243533E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.163308E+09 374894.24
July 0.459349E+11 0.248349E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.186710E+09 1955190.71
August 0.461292E+11 0.256649E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.183859E+09 686258.60
September 0.445099E+11 0.253987E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.157551E+09 1601196.43
October 0.459565E+11 0.269863E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.122980E+09 6502816.90
November 0.444343E+11 0.264279E+10 0.144540E+11 0.00 0.00 0.00 0.00 68627213.44 63099430.23
December 0.459349E+11 0.275615E+10 0.149358E+11 0.00 0.00 0.00 0.00 25651197.53 0.155716E+09
                   
Annual Sum or Average 0.541708E+12 0.310302E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.117881E+10 0.700907E+09
Minimum of Months 0.415303E+11 0.243533E+10 0.134904E+11 0.00 0.00 0.00 0.00 21202753.48 374894.24
Maximum of Months 0.461508E+11 0.277206E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.186710E+09 0.185147E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.277206E+10 0.149358E+11 0.00 0.00 0.00 0.00 18923738.55 0.191369E+09
February 0.415303E+11 0.245660E+10 0.134904E+11 0.00 0.00 0.00 0.00 27924073.23 0.130624E+09
March 0.461508E+11 0.265720E+10 0.149358E+11 0.00 0.00 0.00 0.00 29042866.70 0.115401E+09
April 0.445315E+11 0.249121E+10 0.144540E+11 0.00 0.00 0.00 0.00 58938190.90 41657425.71
May 0.460320E+11 0.253041E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.120069E+09 6734554.92
June 0.446286E+11 0.243533E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.161074E+09 399173.53
July 0.459349E+11 0.248349E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.184873E+09 1985324.84
August 0.461292E+11 0.256649E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.181345E+09 733041.14
September 0.445099E+11 0.253987E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.155295E+09 1627905.26
October 0.459565E+11 0.269863E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.119944E+09 6628134.77
November 0.444343E+11 0.264279E+10 0.144540E+11 0.00 0.00 0.00 0.00 65408681.62 65055178.48
December 0.459349E+11 0.275615E+10 0.149358E+11 0.00 0.00 0.00 0.00 23413203.32 0.160933E+09
                   
Annual Sum or Average 0.541708E+12 0.310302E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.114625E+10 0.723148E+09
Minimum of Months 0.415303E+11 0.243533E+10 0.134904E+11 0.00 0.00 0.00 0.00 18923738.55 399173.53
Maximum of Months 0.461508E+11 0.277206E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.184873E+09 0.191369E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.110133E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 9001908.26 0.176636E+09
February 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 14637904.27 0.113556E+09
March 0.410691E+10 0.110473E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 18451636.78 0.100969E+09
April 0.396281E+10 0.106399E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 45496558.06 27383580.39
May 0.409635E+10 0.110324E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.110523E+09 2932873.17
June 0.397146E+10 0.106887E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.150641E+09 298867.05
July 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.173223E+09 942202.84
August 0.410499E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.168467E+09 1132380.40
September 0.396089E+10 0.106442E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.143796E+09 748912.48
October 0.408962E+10 0.110091E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.108016E+09 3018167.85
November 0.395417E+10 0.106802E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 51674944.01 53569473.62
December 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 14518946.24 0.147775E+09
                   
Annual Sum or Average 0.482060E+11 0.129718E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.100845E+10 0.628962E+09
Minimum of Months 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 9001908.26 298867.05
Maximum of Months 0.410691E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.173223E+09 0.176636E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.205176E+10 0.00 0.00 0.00 0.00 0.00 25823289.26 0.113536E+09
February 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 38552507.10 73005109.94
March 0.409620E+10 0.205809E+10 0.00 0.00 0.00 0.00 0.00 45255951.64 61683756.80
April 0.395248E+10 0.198220E+10 0.00 0.00 0.00 0.00 0.00 74005482.95 12138519.20
May 0.408566E+10 0.205532E+10 0.00 0.00 0.00 0.00 0.00 0.134015E+09 851714.67
June 0.396110E+10 0.199129E+10 0.00 0.00 0.00 0.00 0.00 0.160838E+09 6372.10
July 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 0.175864E+09 317830.66
August 0.409429E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 0.180343E+09 14289.88
September 0.395056E+10 0.198299E+10 0.00 0.00 0.00 0.00 0.00 0.152088E+09 32218.23
October 0.407896E+10 0.205097E+10 0.00 0.00 0.00 0.00 0.00 0.126629E+09 859866.48
November 0.394385E+10 0.198971E+10 0.00 0.00 0.00 0.00 0.00 76297294.20 32140980.25
December 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 31375068.93 93654306.15
                   
Annual Sum or Average 0.480803E+11 0.241662E+11 0.00 0.00 0.00 0.00 0.00 0.122109E+10 0.388241E+09
Minimum of Months 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 25823289.26 6372.10
Maximum of Months 0.409620E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 0.180343E+09 0.113536E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13190.31 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13190.31 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13190.31 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13190.31 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13190.31 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13190.31 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13190.31 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13190.31 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13190.31 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13190.31 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13190.31 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13190.31 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 597.59 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 61.73 07-JAN-15:00 144.57 25-JAN-07:00
February 1169.53 01-FEB-00:10 597.59 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 66.30 02-FEB-14:00 202.95 04-FEB-07:00
March 1169.53 01-MAR-00:10 597.59 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 64.49 13-MAR-16:00 179.45 16-MAR-07:00
April 1169.53 01-APR-00:10 597.59 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 96.53 17-APR-15:00 81.90 02-APR-05:03
May 1169.53 01-MAY-00:10 597.59 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 122.52 22-MAY-13:00 15.24 10-MAY-15:00
June 1169.53 01-JUN-00:10 597.59 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 97.08 11-JUN-13:00 1.83 05-JUN-22:00
July 1169.53 01-JUL-00:10 597.59 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 130.79 29-JUL-16:00 9.36 14-JUL-19:20
August 1169.53 01-AUG-00:10 597.59 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 112.96 23-AUG-13:00 4.17 05-AUG-17:55
September 1169.53 01-SEP-00:10 597.59 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 93.87 13-SEP-13:00 11.89 02-SEP-22:00
October 1169.53 01-OCT-23:10 597.59 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 93.86 09-OCT-11:00 22.57 26-OCT-14:00
November 1169.53 01-NOV-00:10 597.59 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 69.14 17-NOV-15:00 136.27 27-NOV-07:00
December 1169.53 01-DEC-00:10 597.59 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 56.46 10-DEC-14:00 165.52 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 56.46   1.83  
Maximum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 130.79   202.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 692.02 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 32.24 02-JAN-14:00 56.60 25-JAN-05:30
February 1354.32 01-FEB-00:10 692.02 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 33.04 11-FEB-14:00 78.34 04-FEB-07:00
March 1354.32 01-MAR-00:10 692.02 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 32.94 13-MAR-16:00 70.35 16-MAR-05:00
April 1354.32 01-APR-00:10 692.02 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 43.81 17-APR-15:00 36.83 02-APR-05:13
May 1354.32 01-MAY-00:10 692.02 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 53.36 22-MAY-13:00 9.12 07-MAY-05:17
June 1354.32 01-JUN-00:10 692.02 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 41.84 11-JUN-13:00 0.98 05-JUN-22:00
July 1354.32 01-JUL-00:10 692.02 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 53.48 29-JUL-16:00 3.86 14-JUL-20:00
August 1354.32 01-AUG-00:10 692.02 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 49.09 06-AUG-13:00 1.46 05-AUG-18:00
September 1354.32 01-SEP-00:10 692.02 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 42.36 13-SEP-13:00 4.59 02-SEP-22:00
October 1354.32 01-OCT-23:10 692.02 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 43.31 14-OCT-13:00 6.42 16-OCT-01:00
November 1354.32 01-NOV-00:10 692.02 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 34.78 17-NOV-15:00 56.23 27-NOV-03:00
December 1354.32 01-DEC-00:10 692.02 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 29.24 10-DEC-14:00 65.78 15-DEC-05:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 29.24   0.98  
Maximum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 53.48   78.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 77.38 02-JAN-14:00 131.89 25-JAN-07:00
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 79.50 11-FEB-14:00 185.13 04-FEB-07:00
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 82.64 13-MAR-16:00 163.71 16-MAR-07:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 101.72 17-APR-15:00 80.56 02-APR-05:13
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 119.75 22-MAY-13:00 19.97 07-MAY-05:17
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 91.79 11-JUN-13:00 2.78 05-JUN-22:00
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 121.02 29-JUL-16:00 11.83 14-JUL-20:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 110.05 06-AUG-13:00 5.54 05-AUG-18:00
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 95.45 13-SEP-13:00 9.26 02-SEP-22:00
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 100.18 14-OCT-13:00 13.49 28-OCT-03:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 83.34 17-NOV-15:00 125.35 27-NOV-03:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 68.53 10-DEC-14:00 150.98 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 68.53   2.78  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 121.02   185.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 251.84 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 44.15 02-JAN-14:00 76.10 25-JAN-07:00
February 220.32 01-FEB-00:10 251.84 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 45.58 11-FEB-14:00 106.81 04-FEB-07:00
March 220.32 01-MAR-00:10 251.84 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 47.44 13-MAR-16:00 94.44 16-MAR-07:00
April 220.32 01-APR-00:10 251.84 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 58.61 17-APR-15:00 46.11 02-APR-05:03
May 220.32 01-MAY-00:10 251.84 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 69.21 22-MAY-13:00 10.90 07-MAY-05:10
June 220.32 01-JUN-00:10 251.84 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 53.41 11-JUN-13:00 0.79 05-JUN-15:00
July 220.32 01-JUL-00:10 251.84 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 70.11 29-JUL-16:00 4.84 14-JUL-20:00
August 220.32 01-AUG-00:10 251.84 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 63.23 06-AUG-13:00 2.79 12-AUG-07:00
September 220.32 01-SEP-00:10 251.84 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 55.07 13-SEP-13:00 3.96 02-SEP-22:00
October 220.32 01-OCT-23:10 251.84 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 57.40 14-OCT-13:00 7.78 28-OCT-03:00
November 220.32 01-NOV-00:10 251.84 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 47.86 17-NOV-15:00 72.52 27-NOV-03:00
December 220.32 01-DEC-00:10 251.84 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 39.23 10-DEC-14:00 87.12 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 39.23   0.79  
Maximum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 70.11   106.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 325.08 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 114.42 02-JAN-14:00 199.99 25-JAN-07:10
February 907.20 01-FEB-00:10 325.08 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 121.43 11-FEB-14:00 252.85 04-FEB-07:00
March 907.20 01-MAR-00:10 325.08 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 120.24 13-MAR-16:00 247.26 16-MAR-07:00
April 907.20 01-APR-00:10 325.08 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 155.60 17-APR-15:00 111.02 02-APR-06:10
May 907.20 01-MAY-00:10 325.08 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 184.91 22-MAY-13:00 31.05 01-MAY-06:10
June 907.20 01-JUN-00:10 325.08 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 157.69 11-JUN-13:00 10.35 05-JUN-22:00
July 907.20 01-JUL-00:10 325.08 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 195.40 29-JUL-16:00 17.79 14-JUL-21:54
August 907.20 01-AUG-00:10 325.08 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 175.12 06-AUG-13:00 17.73 05-AUG-18:00
September 907.20 01-SEP-00:10 325.08 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 153.22 20-SEP-14:00 17.73 02-SEP-22:00
October 907.20 01-OCT-23:10 325.08 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 156.08 14-OCT-13:00 21.65 20-OCT-06:10
November 907.20 01-NOV-00:10 325.08 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 127.88 17-NOV-15:00 186.80 27-NOV-07:10
December 907.20 01-DEC-00:10 325.08 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 113.44 10-DEC-14:50 227.40 15-DEC-07:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 113.44   10.35  
Maximum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 195.40   252.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1701.53 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 141.14 07-JAN-15:00 343.65 25-JAN-05:20
February 15368.40 01-FEB-00:10 1701.53 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 157.24 02-FEB-14:00 448.70 04-FEB-07:00
March 15368.40 01-MAR-00:10 1701.53 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 153.16 05-MAR-14:00 410.85 16-MAR-05:00
April 15368.40 01-APR-00:10 1701.53 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 227.66 17-APR-15:00 206.22 02-APR-05:03
May 15368.40 01-MAY-00:10 1701.53 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 289.59 22-MAY-13:00 56.61 01-MAY-05:00
June 15368.40 01-JUN-00:10 1701.53 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 235.94 11-JUN-13:00 18.23 05-JUN-22:00
July 15368.40 01-JUL-00:10 1701.53 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 289.36 29-JUL-16:00 31.55 14-JUL-21:53
August 15368.40 01-AUG-00:10 1701.53 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 260.02 06-AUG-13:00 25.19 14-AUG-03:00
September 15368.40 01-SEP-00:10 1701.53 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 219.70 14-SEP-11:00 31.37 04-SEP-21:56
October 15368.40 01-OCT-23:10 1701.53 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 217.75 02-OCT-14:00 58.83 28-OCT-03:00
November 15368.40 01-NOV-00:10 1701.53 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 152.85 17-NOV-15:00 339.97 27-NOV-03:00
December 15368.40 01-DEC-00:10 1701.53 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 132.14 24-DEC-14:00 393.12 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 132.14   18.23  
Maximum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 289.59   448.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9504.80 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 480.83 02-JAN-14:00 987.40 25-JAN-05:30
February 45622.98 01-FEB-00:10 9504.80 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 495.91 11-FEB-14:00 1295.12 04-FEB-07:00
March 45622.98 01-MAR-00:10 9504.80 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 513.86 13-MAR-15:02 1199.59 16-MAR-05:00
April 45622.98 01-APR-00:10 9504.80 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 706.47 17-APR-15:00 618.92 02-APR-05:30
May 45622.98 01-MAY-00:10 9504.80 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 860.75 22-MAY-13:00 171.05 07-MAY-05:20
June 45622.98 01-JUN-00:10 9504.80 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 686.76 11-JUN-13:00 52.31 05-JUN-22:00
July 45622.98 01-JUL-00:10 9504.80 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 875.77 29-JUL-16:00 90.20 14-JUL-21:53
August 45622.98 01-AUG-00:10 9504.80 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 786.03 23-AUG-13:00 45.38 14-AUG-03:00
September 45622.98 01-SEP-00:10 9504.80 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 680.12 13-SEP-13:00 83.74 02-SEP-22:00
October 45622.98 01-OCT-23:10 9504.80 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 675.08 02-OCT-14:00 159.54 28-OCT-03:00
November 45622.98 01-NOV-00:10 9504.80 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 542.22 17-NOV-15:00 976.70 27-NOV-03:00
December 45622.98 01-DEC-00:10 9504.80 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 445.89 10-DEC-14:00 1140.98 15-DEC-05:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 445.89   45.38  
Maximum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 875.77   1295.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.92 04-FEB-07:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.27 16-MAR-07:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.53 17-APR-15:10 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:50
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 8.14 28-AUG-12:00
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:10 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:10 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 94.53   118.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.26 16-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.52 17-APR-15:10 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 12.93 07-MAY-06:00
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 5.61 21-JUN-17:50
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 16.40 02-JUL-18:00
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 10.19 12-AUG-07:20
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 8.46 04-SEP-21:50
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.89 14-OCT-16:00 14.68 01-OCT-08:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:08 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:08 97.17 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 37.72   5.61  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 111.79 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 4.12 02-JAN-14:10 34.94 25-JAN-07:00
February 0.00 01-FEB-00:10 111.79 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 5.06 11-FEB-14:00 42.14 04-FEB-07:00
March 0.00 01-MAR-00:10 111.79 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 5.01 13-MAR-16:00 40.66 16-MAR-07:00
April 0.00 01-APR-00:10 111.79 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 10.13 17-APR-15:00 24.26 02-APR-06:00
May 0.00 01-MAY-00:10 111.79 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 14.12 22-MAY-13:00 11.81 01-MAY-06:00
June 0.00 01-JUN-00:10 111.79 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 10.20 11-JUN-13:00 7.25 05-JUN-15:00
July 0.00 01-JUL-00:10 111.79 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 16.23 29-JUL-16:00 7.52 14-JUL-21:51
August 0.00 01-AUG-00:10 111.79 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 13.28 23-AUG-13:00 8.70 28-AUG-12:00
September 0.00 01-SEP-00:10 111.79 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 10.17 13-SEP-13:00 8.63 05-SEP-06:00
October 0.00 01-OCT-00:10 111.79 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 10.17 09-OCT-11:00 10.78 28-OCT-03:50
November 0.00 01-NOV-00:10 111.79 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 6.14 17-NOV-15:00 33.51 27-NOV-07:00
December 0.00 01-DEC-00:10 111.79 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 4.08 10-DEC-14:00 38.40 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 4.08   7.25  
Maximum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 16.23   42.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 11.90 02-JAN-14:00 23.73 25-JAN-07:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 12.38 11-FEB-16:10 33.19 04-FEB-07:00
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 15.37 13-MAR-16:00 29.49 16-MAR-07:10
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 20.24 17-APR-15:08 13.31 02-APR-06:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 22.33 29-MAY-16:00 3.92 01-MAY-06:00
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.63 10-JUN-16:00 1.11 05-JUN-15:00
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 26.38 29-JUL-16:00 3.20 14-JUL-18:00
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 20.48 21-AUG-16:00 2.52 12-AUG-07:20
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.47 20-SEP-16:00 1.37 04-SEP-21:50
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 19.51 14-OCT-16:00 3.22 26-OCT-14:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 14.94 17-NOV-16:10 22.38 27-NOV-07:00
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 13.03 10-DEC-16:10 27.12 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 11.90   1.11  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 26.38   33.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 86.70 25-JAN-08:40
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:08 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.47 16-MAR-07:10
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.53 17-APR-15:10 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.54 29-JUL-16:00 3.99 14-JUL-17:50
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 8.14 28-AUG-12:00
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:08 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:08 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 94.54   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.26 16-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.52 17-APR-15:10 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.01 29-MAY-16:00 13.67 01-MAY-07:10
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 7.24 13-JUN-07:10
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 17.68 14-JUL-18:00
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 10.11 12-AUG-07:20
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 8.68 04-SEP-21:50
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 14.40 01-OCT-08:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:10 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:08 97.17 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 37.72   7.24  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1867.32 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 52.41 02-JAN-14:00 101.84 25-JAN-07:00
February 2263.36 01-FEB-00:10 1867.32 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 57.92 11-FEB-14:00 142.82 04-FEB-07:00
March 2263.36 01-MAR-00:10 1867.32 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 58.11 13-MAR-16:00 128.95 16-MAR-05:00
April 2263.36 01-APR-00:10 1867.32 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 75.30 17-APR-15:00 66.80 02-APR-05:03
May 2263.36 01-MAY-00:10 1867.32 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 92.26 22-MAY-13:00 16.03 07-MAY-05:10
June 2263.36 01-JUN-00:10 1867.32 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 73.34 11-JUN-13:00 0.40 05-JUN-15:00
July 2263.36 01-JUL-00:10 1867.32 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 95.99 29-JUL-16:00 4.76 14-JUL-21:51
August 2263.36 01-AUG-00:10 1867.32 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 84.79 23-AUG-13:00 3.96 12-AUG-07:00
September 2263.36 01-SEP-00:10 1867.32 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 74.03 08-SEP-15:00 4.77 05-SEP-06:00
October 2263.36 01-OCT-23:10 1867.32 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 74.08 14-OCT-13:00 13.26 28-OCT-03:00
November 2263.36 01-NOV-00:10 1867.32 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 61.49 17-NOV-15:00 103.75 27-NOV-03:00
December 2263.36 01-DEC-00:10 1867.32 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 49.16 10-DEC-14:00 120.48 15-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 49.16   0.40  
Maximum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 95.99   142.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.32 01-JAN-11:00 85.47 25-JAN-07:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 43.96 11-FEB-16:10 119.38 04-FEB-07:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 54.67 13-MAR-16:00 105.72 16-MAR-07:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.15 17-APR-15:10 48.14 02-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 79.64 29-MAY-16:00 11.97 10-MAY-15:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 69.94 10-JUN-16:00 4.38 05-JUN-15:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.17 29-JUL-16:00 4.39 14-JUL-17:50
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.02 21-AUG-16:00 8.55 28-AUG-12:00
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 72.98 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.52 14-OCT-16:00 11.95 26-OCT-14:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.14 17-NOV-16:10 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.30 10-DEC-16:10 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 37.32   0.00  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 94.17   119.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.33 01-JAN-11:00 85.47 25-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 43.97 11-FEB-16:10 119.37 04-FEB-07:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 54.66 13-MAR-16:00 105.72 16-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.14 17-APR-15:10 48.13 02-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 79.64 29-MAY-16:00 11.96 10-MAY-15:00
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 69.94 10-JUN-16:00 10.70 21-JUN-17:50
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.16 29-JUL-16:00 21.45 02-JUL-18:00
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.00 21-AUG-16:00 9.66 05-AUG-18:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.97 20-SEP-16:00 11.06 04-SEP-21:50
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.52 14-OCT-16:00 14.47 01-OCT-08:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.14 17-NOV-16:10 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.30 10-DEC-16:10 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 37.33   9.66  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 94.16   119.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 19.10 01-JAN-11:00 43.73 25-JAN-07:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 20.97 11-FEB-16:50 61.08 04-FEB-07:00
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 27.97 13-MAR-16:00 54.09 16-MAR-07:00
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 36.90 17-APR-15:10 24.63 02-APR-06:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 40.75 29-MAY-16:00 6.12 10-MAY-15:00
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 35.79 10-JUN-16:00 2.24 05-JUN-15:00
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 48.17 29-JUL-16:00 2.25 14-JUL-17:50
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 37.35 21-AUG-16:00 4.38 28-AUG-12:00
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 37.33 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 35.56 14-OCT-16:00 6.12 26-OCT-14:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 26.38 17-NOV-16:10 41.25 27-NOV-07:00
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 22.71 10-DEC-16:10 49.95 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 19.10   0.00  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 48.17   61.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 106.77 02-JAN-14:00 237.69 25-JAN-05:20
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 99.61 11-FEB-14:00 312.99 04-FEB-07:00
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 99.46 13-MAR-15:00 286.63 16-MAR-05:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 141.92 17-APR-15:00 156.46 02-APR-05:30
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 177.71 22-MAY-13:00 57.11 07-MAY-06:00
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 137.88 11-JUN-13:00 13.43 06-JUN-03:08
July 26988.77 01-JUL-00:10 2988.03 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 183.79 29-JUL-16:00 21.95 14-JUL-21:54
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 168.10 23-AUG-13:00 25.93 12-AUG-07:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 146.42 13-SEP-13:00 31.80 05-SEP-06:00
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 143.70 02-OCT-14:00 50.42 28-OCT-03:10
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 117.93 17-NOV-15:00 231.80 27-NOV-03:00
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 99.71 10-DEC-15:00 270.22 15-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 99.46   13.43  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 183.79   312.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 103.26 02-JAN-14:00 239.92 25-JAN-05:20
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 96.31 11-FEB-14:00 315.83 04-FEB-07:00
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 95.41 13-MAR-15:00 288.75 16-MAR-05:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 139.33 17-APR-15:00 157.80 02-APR-06:00
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 174.71 22-MAY-13:00 58.21 07-MAY-06:00
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 135.83 11-JUN-13:00 14.32 05-JUN-15:10
July 26988.77 01-JUL-00:10 2988.03 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 183.79 29-JUL-16:00 21.95 14-JUL-21:54
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 165.93 23-AUG-13:00 27.35 12-AUG-07:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 143.97 13-SEP-13:00 31.81 05-SEP-06:00
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 140.73 02-OCT-14:00 50.43 28-OCT-03:10
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 115.00 17-NOV-15:00 234.15 27-NOV-03:00
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 97.09 10-DEC-15:00 272.24 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 95.41   14.32  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 183.79   315.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1060.81 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 70.95 02-JAN-14:00 222.04 25-JAN-07:50
February 2401.70 01-FEB-00:10 1060.81 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 78.25 11-FEB-14:00 278.77 04-FEB-07:20
March 2401.70 01-MAR-00:10 1060.81 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 77.58 13-MAR-16:00 272.44 16-MAR-07:00
April 2401.70 01-APR-00:10 1060.81 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 117.30 17-APR-15:00 144.61 02-APR-06:00
May 2401.70 01-MAY-00:10 1060.81 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 148.34 22-MAY-13:00 52.61 07-MAY-06:00
June 2401.70 01-JUN-00:10 1060.81 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 118.15 11-JUN-13:00 19.37 05-JUN-15:00
July 2401.70 01-JUL-00:10 1060.81 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 164.74 29-JUL-16:00 19.63 14-JUL-21:54
August 2401.70 01-AUG-00:10 1060.81 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 142.05 23-AUG-13:00 28.65 12-AUG-08:57
September 2401.70 01-SEP-00:10 1060.81 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 117.83 20-SEP-16:00 28.38 05-SEP-06:00
October 2401.70 01-OCT-23:10 1060.81 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 117.82 09-OCT-11:00 36.11 20-OCT-05:20
November 2401.70 01-NOV-00:10 1060.81 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 86.41 17-NOV-15:00 206.41 27-NOV-07:00
December 2401.70 01-DEC-00:10 1060.81 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 70.35 10-DEC-14:00 258.81 15-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 70.35   19.37  
Maximum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 164.74   278.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1976.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 86.89 07-JAN-13:00 181.17 25-JAN-07:00
February 2395.44 01-FEB-00:10 1976.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 90.12 02-FEB-14:00 253.69 04-FEB-07:00
March 2395.44 01-MAR-00:10 1976.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 96.82 13-MAR-16:00 224.48 16-MAR-07:00
April 2395.44 01-APR-00:10 1976.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 124.75 17-APR-15:00 107.32 02-APR-05:00
May 2395.44 01-MAY-00:10 1976.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 154.86 22-MAY-13:00 24.19 07-MAY-05:00
June 2395.44 01-JUN-00:10 1976.27 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 117.37 11-JUN-13:00 3.66 05-JUN-15:00
July 2395.44 01-JUL-00:10 1976.27 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 161.00 29-JUL-16:00 11.14 14-JUL-18:40
August 2395.44 01-AUG-00:10 1976.27 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 139.90 23-AUG-13:00 8.71 05-AUG-17:55
September 2395.44 01-SEP-00:10 1976.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 122.27 13-SEP-13:00 12.62 02-SEP-22:00
October 2395.44 01-OCT-23:10 1976.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 124.30 02-OCT-14:00 19.76 26-OCT-14:00
November 2395.44 01-NOV-00:10 1976.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 95.67 17-NOV-15:00 170.79 27-NOV-07:00
December 2395.44 01-DEC-00:10 1976.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 80.66 10-DEC-14:00 207.15 15-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 80.66   3.66  
Maximum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 161.00   253.69  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19624.67 03-JAN-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
February 19065.69 17-FEB-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
March 18877.34 31-MAR-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
April 19105.04 14-APR-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
May 19497.06 19-MAY-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
June 19860.42 30-JUN-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
July 20292.25 28-JUL-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
August 20633.85 23-AUG-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
September 20891.25 22-SEP-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 20672.48 25-OCT-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 20542.57 10-NOV-22:00 20447.81 23449.32 18251.11 0.00 0.00 0.00 0.00 0.00 0.00
December 20135.68 08-DEC-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 18877.34   10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20891.25   20447.81 23449.32 18251.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3434.26 02-JAN-14:30 259.90 166.00 252.59 0.00 0.00 0.00 0.00 56.93 0.00
February 3345.29 11-FEB-14:30 389.84 166.00 252.59 0.00 0.00 0.00 0.00 56.41 0.00
March 2295.00 27-MAR-19:20 909.64 597.59 685.60 0.00 0.00 0.00 0.00 14.10 0.00
April 2772.16 15-APR-18:03 4678.13 2788.77 3464.10 0.00 0.00 0.00 0.00 66.86 0.00
May 2644.30 17-MAY-19:30 909.64 597.59 685.60 0.00 0.00 0.00 0.00 34.45 0.00
June 2959.64 29-JUN-19:10 909.64 597.59 685.60 0.00 0.00 0.00 0.00 67.16 0.00
July 3354.58 29-JUL-18:03 4678.13 2788.77 3464.10 0.00 0.00 0.00 0.00 103.73 0.00
August 3121.33 21-AUG-18:15 1819.27 1062.39 1299.04 0.00 0.00 0.00 0.00 62.35 0.00
September 3646.24 30-SEP-13:50 389.84 166.00 252.59 0.00 0.00 0.00 0.00 80.65 0.00
October 3814.74 25-OCT-14:30 389.84 166.00 252.59 0.00 0.00 0.00 0.00 68.97 0.00
November 3777.78 07-NOV-14:00 259.90 166.00 252.59 0.00 0.00 0.00 0.00 49.66 0.00
December 3806.67 09-DEC-12:30 389.84 166.00 252.59 0.00 0.00 0.00 0.00 37.29 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2295.00   259.90 166.00 252.59 0.00 0.00 0.00 0.00 14.10 0.00
Maximum of Months 3814.74   4678.13 2788.77 3464.10 0.00 0.00 0.00 0.00 103.73 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1854.82 03-JAN-22:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 4.92
February 1852.49 11-FEB-22:00 1053.36 538.23 668.57 0.00 0.00 0.00 0.00 0.00 7.20
March 1926.48 28-MAR-21:00 9630.72 4921.00 6017.16 0.00 0.00 0.00 0.00 3.32 0.00
April 2108.55 13-APR-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 7.25 0.00
May 2229.53 17-MAY-20:40 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 10.39 0.00
June 2398.95 09-JUN-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 24.14 0.00
July 2469.87 28-JUL-20:50 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 23.19 0.00
August 2419.80 17-AUG-20:10 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 18.96 0.00
September 2353.91 01-SEP-20:10 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 21.91 0.00
October 2262.91 06-OCT-20:40 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 12.14 0.00
November 1961.15 07-NOV-22:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 2.41 0.00
December 1925.12 08-DEC-22:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 1.07 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1852.49   1053.36 538.23 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2469.87   9630.72 4921.00 6017.16 0.00 0.00 0.00 0.00 24.14 7.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1699.23 03-JAN-22:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 2.00
February 1720.11 17-FEB-22:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 15.07 0.00
March 1746.48 30-MAR-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 13.45 0.00
April 1862.66 14-APR-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 24.52 0.00
May 1946.90 22-MAY-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 42.56 0.00
June 2332.34 29-JUN-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 51.80 0.00
July 2512.83 29-JUL-20:30 222.77 532.14 706.90 0.00 0.00 0.00 0.00 48.50 0.00
August 2310.05 21-AUG-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 45.45 0.00
September 2283.94 22-SEP-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 45.63 0.00
October 1922.46 03-OCT-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 44.02 0.00
November 1849.32 04-NOV-21:10 222.77 456.12 618.54 0.00 0.00 0.00 0.00 31.99 0.00
December 1795.51 10-DEC-21:00 190.94 608.16 795.27 0.00 0.00 0.00 0.00 15.77 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1699.23   190.94 456.12 618.54 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2512.83   254.59 684.18 839.45 0.00 0.00 0.00 0.00 51.80 2.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 918.03 03-JAN-22:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 0.00 0.60
February 926.95 11-FEB-22:10 171.36 167.89 178.43 0.00 0.00 0.00 0.00 0.00 4.40
March 939.62 30-MAR-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 9.15 0.00
April 998.47 14-APR-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 15.18 0.00
May 1041.29 22-MAY-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 25.84 0.00
June 1085.40 29-JUN-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 30.41 0.00
July 1188.46 29-JUL-19:00 146.88 195.87 203.92 0.00 0.00 0.00 0.00 49.26 0.00
August 1086.65 21-AUG-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 26.20 0.00
September 1086.26 22-SEP-21:10 220.32 167.89 178.43 0.00 0.00 0.00 0.00 26.79 0.00
October 1036.11 01-OCT-00:10 171.36 83.94 101.96 0.00 0.00 0.00 0.00 27.45 0.00
November 997.00 04-NOV-21:10 171.36 167.89 178.43 0.00 0.00 0.00 0.00 19.61 0.00
December 970.04 09-DEC-22:00 171.36 195.87 203.92 0.00 0.00 0.00 0.00 7.05 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 918.03   146.88 83.94 101.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1188.46   220.32 195.87 203.92 0.00 0.00 0.00 0.00 49.26 4.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33995.88 02-JAN-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 26.72
February 33931.61 17-FEB-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 1.51
March 34683.49 27-MAR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 5.85 0.00
April 35566.46 14-APR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 30.54 0.00
May 35832.97 31-MAY-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 55.09 0.00
June 36204.02 09-JUN-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 77.90 0.00
July 36553.14 28-JUL-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 61.87 0.00
August 36074.26 31-AUG-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 55.21 0.00
September 35972.12 08-SEP-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 94.55 0.00
October 35650.88 06-OCT-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 39.16 0.00
November 34821.75 10-NOV-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 5.84 0.00
December 34368.02 08-DEC-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 5.85 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 33931.61   705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36553.14   705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 94.55 26.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11893.59 02-JAN-14:30 3415.20 103.98 355.63 0.00 0.00 0.00 0.00 125.87 0.00
February 11799.56 11-FEB-14:30 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 124.74 0.00
March 10649.38 27-MAR-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 23.54 0.00
April 11211.02 14-APR-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 38.90 0.00
May 11451.61 22-MAY-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 95.01 0.00
June 11747.52 29-JUN-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 125.66 0.00
July 12334.00 28-JUL-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 135.45 0.00
August 12246.45 31-AUG-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 97.26 0.00
September 12967.37 08-SEP-21:10 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 150.59 0.00
October 13747.23 25-OCT-15:03 51228.00 623.89 2133.76 0.00 0.00 0.00 0.00 132.83 0.00
November 12754.80 07-NOV-16:03 51228.00 623.89 2133.76 0.00 0.00 0.00 0.00 107.62 0.00
December 13198.50 09-DEC-12:30 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 82.47 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10649.38   3415.20 103.98 355.63 0.00 0.00 0.00 0.00 23.54 0.00
Maximum of Months 13747.23   51228.00 1134.35 2133.76 0.00 0.00 0.00 0.00 150.59 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33545.57 03-JAN-22:20 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 129.49
February 33260.25 17-FEB-22:51 364983.84 50692.26 59119.55 0.00 0.00 0.00 0.00 17.93 0.00
March 33571.27 30-MAR-21:51 410606.82 57028.80 66509.49 0.00 0.00 0.00 0.00 10.35 0.00
April 35855.45 14-APR-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 110.91 0.00
May 37406.29 22-MAY-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 271.25 0.00
June 40895.27 29-JUN-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 358.82 0.00
July 42672.59 28-JUL-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 386.78 0.00
August 42003.77 21-AUG-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 309.21 0.00
September 42914.38 22-SEP-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 316.44 0.00
October 40371.82 06-OCT-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 198.87 0.00
November 37350.89 10-NOV-22:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 58.59
December 35304.05 08-DEC-22:05 182491.92 25346.13 29559.77 0.00 0.00 0.00 0.00 0.00 1.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 33260.25   45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 42914.38   410606.82 57028.80 66509.49 0.00 0.00 0.00 0.00 386.78 129.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3235.01 25-JAN-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 32.48
February 3212.80 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 42.25
March 3252.86 15-MAR-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 36.30
April 3044.26 01-APR-15:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 34.96 0.00
May 3068.30 30-MAY-15:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 50.12 0.00
June 3046.67 27-JUN-15:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 55.58 0.00
July 3049.13 06-JUL-15:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 52.56 0.00
August 3061.30 29-AUG-15:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 45.45 0.00
September 3059.95 21-SEP-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 45.43 0.00
October 3061.49 03-OCT-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 44.37 0.00
November 3022.73 05-NOV-15:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 34.69 0.00
December 3035.41 16-DEC-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 7.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3022.73   324.00 298.84 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3252.86   831.60 949.89 726.98 0.00 0.00 0.00 0.00 55.58 42.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3103.67 25-JAN-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 27.46
February 3142.79 03-FEB-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 39.15
March 3257.01 15-MAR-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 35.67
April 3126.76 18-APR-21:51 1800.00 1191.67 895.45 0.00 0.00 0.00 0.00 0.00 39.30
May 3076.26 10-MAY-16:31 972.00 498.01 1264.17 0.00 0.00 0.00 0.00 8.64 0.00
June 3302.79 13-JUN-18:11 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 8.02 0.00
July 3066.80 12-JUL-18:02 831.60 949.78 726.90 0.00 0.00 0.00 0.00 42.28 0.00
August 3089.97 15-AUG-18:02 831.60 949.78 726.90 0.00 0.00 0.00 0.00 47.68 0.00
September 3072.00 08-SEP-18:02 831.60 949.78 726.90 0.00 0.00 0.00 0.00 56.06 0.00
October 3079.81 22-OCT-15:02 324.00 352.17 331.84 0.00 0.00 0.00 0.00 44.23 0.00
November 3075.34 19-NOV-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 27.63 0.00
December 3071.04 09-DEC-16:02 324.00 352.17 331.84 0.00 0.00 0.00 0.00 23.46 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3066.80   324.00 348.61 331.84 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3302.79   1800.00 1582.97 1264.17 0.00 0.00 0.00 0.00 56.06 39.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 567.36 02-JAN-14:30 0.00 31.30 30.96 0.00 0.00 0.00 0.00 4.12 0.00
February 487.13 11-FEB-14:30 0.00 36.89 33.54 0.00 0.00 0.00 0.00 4.03 0.00
March 395.16 02-MAR-14:30 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 3.27
April 337.79 15-APR-17:17 0.00 380.09 495.34 0.00 0.00 0.00 0.00 8.19 0.00
May 326.09 22-MAY-20:20 0.00 99.50 178.01 0.00 0.00 0.00 0.00 2.67 0.00
June 342.08 03-JUN-21:00 0.00 111.79 178.01 0.00 0.00 0.00 0.00 5.04 0.00
July 373.89 29-JUL-19:10 0.00 111.79 159.95 0.00 0.00 0.00 0.00 8.96 0.00
August 364.38 20-AUG-20:10 0.00 111.79 178.01 0.00 0.00 0.00 0.00 3.92 0.00
September 465.65 30-SEP-13:50 0.00 36.89 33.54 0.00 0.00 0.00 0.00 8.01 0.00
October 536.22 25-OCT-14:00 0.00 31.30 30.96 0.00 0.00 0.00 0.00 7.23 0.00
November 570.68 07-NOV-14:00 0.00 31.30 30.96 0.00 0.00 0.00 0.00 2.97 0.00
December 571.60 03-DEC-14:05 0.00 73.78 67.08 0.00 0.00 0.00 0.00 0.00 4.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 326.09   0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 571.60   0.00 380.09 495.34 0.00 0.00 0.00 0.00 8.96 4.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1174.62 13-JAN-19:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 2.92 0.00
February 1155.77 27-FEB-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 6.23 0.00
March 1156.94 29-MAR-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 3.99 0.00
April 1166.78 15-APR-18:02 702.00 670.94 712.25 0.00 0.00 0.00 0.00 13.05 0.00
May 1168.55 30-MAY-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 12.84 0.00
June 1172.91 29-JUN-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 13.36 0.00
July 1172.24 27-JUL-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 16.61 0.00
August 1167.40 04-AUG-08:61 252.00 344.41 776.76 0.00 0.00 0.00 0.00 11.74 0.00
September 1166.26 01-SEP-08:61 252.00 344.41 776.76 0.00 0.00 0.00 0.00 9.85 0.00
October 1166.76 31-OCT-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 5.31 0.00
November 1170.30 28-NOV-19:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 4.09 0.00
December 1161.90 10-DEC-19:02 702.00 670.94 712.25 0.00 0.00 0.00 0.00 5.13 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1155.77   252.00 219.17 343.22 0.00 0.00 0.00 0.00 2.92 0.00
Maximum of Months 1174.62   970.20 696.66 830.96 0.00 0.00 0.00 0.00 16.61 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2934.61 25-JAN-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 32.70
February 2839.61 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 39.86
March 2946.61 16-MAR-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 27.91
April 2786.13 21-APR-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 12.88 0.00
May 2795.28 04-MAY-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 27.33 0.00
June 2801.07 03-JUN-08:62 324.00 597.68 979.84 0.00 0.00 0.00 0.00 38.14 0.00
July 2801.30 23-JUL-08:62 324.00 597.68 979.84 0.00 0.00 0.00 0.00 46.01 0.00
August 2785.95 31-AUG-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 45.24 0.00
September 2797.06 09-SEP-18:02 702.00 1067.29 726.98 0.00 0.00 0.00 0.00 48.98 0.00
October 2810.45 17-OCT-08:61 360.00 782.68 1132.61 0.00 0.00 0.00 0.00 19.47 0.00
November 2801.74 21-NOV-09:01 252.00 547.88 792.83 0.00 0.00 0.00 0.00 26.88 0.00
December 2794.26 09-DEC-09:01 378.00 697.30 1143.15 0.00 0.00 0.00 0.00 23.15 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2785.95   252.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2946.61   702.00 1067.29 1143.15 0.00 0.00 0.00 0.00 48.98 39.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2738.16 08-JAN-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 11.19
February 2985.38 28-FEB-09:51 324.00 704.33 1019.23 0.00 0.00 0.00 0.00 2.22 0.00
March 2923.94 01-MAR-09:51 324.00 704.33 1019.23 0.00 0.00 0.00 0.00 0.00 29.36
April 3067.52 20-APR-08:51 324.00 704.33 1019.23 0.00 0.00 0.00 0.00 2.88 0.00
May 2829.03 04-MAY-08:61 252.00 547.81 792.74 0.00 0.00 0.00 0.00 27.38 0.00
June 2918.15 13-JUN-18:11 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 7.60 0.00
July 2824.24 30-JUL-08:62 324.00 597.61 979.73 0.00 0.00 0.00 0.00 39.51 0.00
August 2813.08 11-AUG-15:02 583.20 298.81 300.24 0.00 0.00 0.00 0.00 47.89 0.00
September 2794.12 22-SEP-15:02 583.20 298.81 300.24 0.00 0.00 0.00 0.00 53.44 0.00
October 2864.68 17-OCT-08:61 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 7.52 0.00
November 2761.15 21-NOV-09:01 252.00 547.81 792.74 0.00 0.00 0.00 0.00 27.21 0.00
December 2739.59 09-DEC-09:01 378.00 697.22 1143.02 0.00 0.00 0.00 0.00 23.52 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2738.16   252.00 298.81 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3067.52   1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 53.44 29.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2500.07 03-JAN-22:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 0.00 5.82
February 2437.93 17-FEB-22:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 11.07 0.00
March 2501.33 30-MAR-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 9.02 0.00
April 2585.99 14-APR-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 19.27 0.00
May 2616.44 22-MAY-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 36.09 0.00
June 2687.34 29-JUN-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 43.55 0.00
July 2723.78 29-JUL-21:10 1760.39 1244.88 0.00 0.00 0.00 0.00 0.00 41.48 0.00
August 2721.39 21-AUG-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 36.95 0.00
September 2737.74 22-SEP-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 37.17 0.00
October 2670.68 25-OCT-21:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 25.48 0.00
November 2611.63 10-NOV-22:10 2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 0.00 0.35
December 2547.43 10-DEC-22:10 2011.87 1037.40 0.00 0.00 0.00 0.00 0.00 10.89 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2437.93   1760.39 1037.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2737.74   2263.36 1244.88 0.00 0.00 0.00 0.00 0.00 43.55 5.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3531.16 25-JAN-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 32.74
February 3501.18 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 42.37
March 3544.40 15-MAR-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 36.42
April 3268.83 06-APR-15:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 18.40 0.00
May 3324.00 28-MAY-15:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 38.39 0.00
June 3305.32 04-JUN-15:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 28.79 0.00
July 3314.85 11-JUL-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 48.82 0.00
August 3311.92 08-AUG-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 37.76 0.00
September 3332.87 30-SEP-15:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 54.27 0.00
October 3298.00 02-OCT-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 41.00 0.00
November 3300.50 02-NOV-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 30.73 0.00
December 3278.81 31-DEC-16:02 324.00 352.21 331.88 0.00 0.00 0.00 0.00 0.00 0.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3268.83   324.00 298.84 300.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3544.40   831.60 949.89 726.98 0.00 0.00 0.00 0.00 54.27 42.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3415.04 25-JAN-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 28.82
February 3412.92 03-FEB-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 39.22
March 3530.54 15-MAR-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 35.51
April 3566.57 18-APR-21:51 1800.00 1191.67 895.45 0.00 0.00 0.00 0.00 0.00 44.26
May 3470.64 10-MAY-16:31 972.00 498.01 1264.17 0.00 0.00 0.00 0.00 3.92 0.00
June 3672.56 13-JUN-18:11 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 5.32 0.00
July 3338.23 11-JUL-18:02 831.60 949.78 726.90 0.00 0.00 0.00 0.00 48.84 0.00
August 3366.72 23-AUG-17:52 583.20 715.00 758.50 0.00 0.00 0.00 0.00 8.56 0.00
September 3346.27 11-SEP-15:02 583.20 298.81 300.24 0.00 0.00 0.00 0.00 17.58 0.00
October 3334.31 13-OCT-16:51 777.60 398.41 1011.33 0.00 0.00 0.00 0.00 6.67 0.00
November 3330.30 05-NOV-15:02 324.00 352.17 331.84 0.00 0.00 0.00 0.00 34.71 0.00
December 3286.77 30-DEC-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 1.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3286.77   324.00 298.81 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3672.56   1800.00 1582.97 1264.17 0.00 0.00 0.00 0.00 48.84 44.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1687.81 25-JAN-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 17.95
February 1615.45 03-FEB-19:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 0.00 34.29
March 1684.63 16-MAR-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 15.25
April 1584.05 14-APR-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 16.55 0.00
May 1580.08 30-MAY-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 23.64 0.00
June 1584.57 28-JUN-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 24.27 0.00
July 1590.26 27-JUL-18:02 831.60 597.13 712.25 0.00 0.00 0.00 0.00 30.39 0.00
August 1592.99 31-AUG-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 31.15 0.00
September 1614.64 20-SEP-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 29.84 0.00
October 1615.17 03-OCT-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 29.17 0.00
November 1613.13 03-NOV-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 18.27 0.00
December 1594.86 06-DEC-16:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 10.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1580.08   583.20 187.86 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1687.81   831.60 597.13 712.25 0.00 0.00 0.00 0.00 31.15 34.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20500.31 13-JAN-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 3.28
February 20929.34 17-FEB-22:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 3.41
March 21443.04 27-MAR-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 5.06 0.00
April 22576.78 14-APR-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 23.27 0.00
May 23567.18 22-MAY-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 51.13 0.00
June 24108.30 09-JUN-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.73 0.00
July 24229.92 28-JUL-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.21 0.00
August 23824.06 02-AUG-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.71 0.00
September 23851.17 08-SEP-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 86.89 0.00
October 22879.29 03-OCT-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 60.84 0.00
November 22239.24 03-NOV-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 42.99 0.00
December 21193.55 08-DEC-22:53 188921.38 13944.14 47235.32 0.00 0.00 0.00 0.00 4.96 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20500.31   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24229.92   215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 86.89 3.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21976.45 13-JAN-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 3.29
February 22426.11 17-FEB-22:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 3.41
March 22892.26 27-MAR-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 5.06 0.00
April 23876.77 14-APR-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 23.26 0.00
May 24896.52 22-MAY-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 59.26 0.00
June 25326.66 09-JUN-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.73 0.00
July 25443.42 28-JUL-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.20 0.00
August 25040.30 02-AUG-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 85.71 0.00
September 25058.49 08-SEP-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 94.91 0.00
October 24136.99 03-OCT-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 60.83 0.00
November 23564.99 03-NOV-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 42.99 0.00
December 22548.36 08-DEC-22:53 188921.38 13944.14 47235.32 0.00 0.00 0.00 0.00 4.96 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 21976.45   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25443.42   215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 94.91 3.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 28426.10 01-JAN-11:50 800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 31.41 0.00
February 28484.65 11-FEB-11:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 53.61 0.00
March 28775.84 27-MAR-10:50 533.71 294.67 14912.86 18744.03 0.00 0.00 0.00 34.65 0.00
April 29942.21 15-APR-10:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 81.20 0.00
May 30091.05 31-MAY-10:50 533.71 294.67 14912.86 18744.03 0.00 0.00 0.00 122.66 0.00
June 30466.41 11-JUN-10:50 800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 100.92 0.00
July 30621.11 23-JUL-10:50 800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 124.72 0.00
August 30363.51 19-AUG-10:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 109.68 0.00
September 30273.10 09-SEP-10:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 101.18 0.00
October 29986.95 07-OCT-10:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 106.94 0.00
November 28739.22 07-NOV-11:50 533.71 294.67 14912.86 18744.03 0.00 0.00 0.00 44.61 0.00
December 28730.43 09-DEC-11:50 800.57 294.67 14912.86 18744.03 0.00 0.00 0.00 46.03 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 28426.10   533.71 294.67 14912.86 18744.03 0.00 0.00 0.00 31.41 0.00
Maximum of Months 30621.11   800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 124.72 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5177.74 02-JAN-14:50 532.32 548.96 0.00 0.00 0.00 0.00 0.00 83.87 0.00
February 5317.16 11-FEB-15:30 798.48 548.96 0.00 0.00 0.00 0.00 0.00 67.91 0.00
March 5213.64 27-MAR-21:10 2395.44 1317.51 0.00 0.00 0.00 0.00 0.00 25.94 0.00
April 5584.69 15-APR-17:17 6387.84 5270.05 0.00 0.00 0.00 0.00 0.00 103.15 0.00
May 5597.82 31-MAY-19:20 1863.12 1976.27 0.00 0.00 0.00 0.00 0.00 61.01 0.00
June 6340.22 29-JUN-18:03 11178.72 10540.09 0.00 0.00 0.00 0.00 0.00 84.48 0.00
July 7576.18 29-JUL-16:10 1330.80 548.96 0.00 0.00 0.00 0.00 0.00 158.31 0.00
August 6650.37 19-AUG-17:02 12775.68 10540.09 0.00 0.00 0.00 0.00 0.00 95.99 0.00
September 7133.26 09-SEP-13:20 798.48 548.96 0.00 0.00 0.00 0.00 0.00 105.36 0.00
October 6234.36 07-OCT-14:00 798.48 548.96 0.00 0.00 0.00 0.00 0.00 84.45 0.00
November 5506.95 08-NOV-15:20 798.48 548.96 0.00 0.00 0.00 0.00 0.00 71.16 0.00
December 5433.71 09-DEC-15:30 798.48 548.96 0.00 0.00 0.00 0.00 0.00 40.67 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5177.74   532.32 548.96 0.00 0.00 0.00 0.00 0.00 25.94 0.00
Maximum of Months 7576.18   12775.68 10540.09 0.00 0.00 0.00 0.00 0.00 158.31 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.551289E+12 367397.14 06-JAN-20:00 0.391594E+12 322552.83 30-JAN-18:49
February 0.522368E+12 358791.36 11-FEB-20:19 0.350996E+12 322443.09 03-FEB-18:00
March 0.595509E+12 381903.60 13-MAR-19:10 0.383747E+12 319536.56 16-MAR-17:10
April 0.629456E+12 390154.67 14-APR-19:10 0.359910E+12 316606.64 03-APR-17:19
May 0.713305E+12 410227.73 29-MAY-19:10 0.365173E+12 314707.06 01-MAY-17:10
June 0.732463E+12 427423.15 29-JUN-19:19 0.348252E+12 312663.21 01-JUN-17:30
July 0.770240E+12 431924.87 27-JUL-19:10 0.357289E+12 311496.26 05-JUL-17:19
August 0.765655E+12 421841.21 02-AUG-19:10 0.359535E+12 312014.24 24-AUG-17:30
September 0.732660E+12 422602.41 18-SEP-19:10 0.351472E+12 314157.11 29-SEP-17:10
October 0.725145E+12 410537.59 03-OCT-19:19 0.369825E+12 316278.96 30-OCT-17:10
November 0.641070E+12 397846.47 29-NOV-20:49 0.366058E+12 318070.13 30-NOV-18:10
December 0.585010E+12 383734.28 25-DEC-20:00 0.389161E+12 321847.76 21-DEC-18:19
             
Annual Sum or Average 0.796417E+13     0.439301E+13    
Minimum of Months 0.522368E+12 358791.36   0.348252E+12 311496.26  
Maximum of Months 0.770240E+12 431924.87   0.391594E+12 322552.83  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.669446E+11 0.185225E+11 0.140828E+12 0.544238E+11 0.358225E+11 0.105650E+11 0.00 0.187334E+12 0.00 0.00 0.238819E+11 0.770590E+10 0.00
February 0.603086E+11 0.159832E+11 0.127191E+12 0.491570E+11 0.330042E+11 0.955685E+10 0.00 0.193669E+12 0.00 0.00 0.217819E+11 0.696333E+10 0.00
March 0.664897E+11 0.166865E+11 0.140882E+12 0.544261E+11 0.371073E+11 0.107784E+11 0.00 0.231484E+12 0.00 0.00 0.246778E+11 0.770451E+10 0.00
April 0.641552E+11 0.151615E+11 0.136245E+12 0.526676E+11 0.375652E+11 0.106750E+11 0.00 0.276149E+12 0.00 0.00 0.242573E+11 0.746613E+10 0.00
May 0.661633E+11 0.147765E+11 0.140860E+12 0.544246E+11 0.407945E+11 0.114897E+11 0.00 0.346107E+12 0.00 0.00 0.256807E+11 0.770548E+10 0.00
June 0.640060E+11 0.138956E+11 0.136336E+12 0.526699E+11 0.409335E+11 0.114798E+11 0.00 0.375623E+12 0.00 0.00 0.249197E+11 0.745782E+10 0.00
July 0.660176E+11 0.144878E+11 0.140770E+12 0.544221E+11 0.431038E+11 0.119540E+11 0.00 0.400755E+12 0.00 0.00 0.257318E+11 0.771324E+10 0.00
August 0.662310E+11 0.152725E+11 0.140892E+12 0.544260E+11 0.420858E+11 0.119146E+11 0.00 0.396075E+12 0.00 0.00 0.257433E+11 0.770531E+10 0.00
September 0.643445E+11 0.157315E+11 0.136256E+12 0.526678E+11 0.411728E+11 0.114762E+11 0.00 0.373487E+12 0.00 0.00 0.249166E+11 0.746735E+10 0.00
October 0.667153E+11 0.172788E+11 0.140818E+12 0.544236E+11 0.410105E+11 0.116159E+11 0.00 0.354570E+12 0.00 0.00 0.257072E+11 0.770399E+10 0.00
November 0.646685E+11 0.176341E+11 0.136330E+12 0.526688E+11 0.373692E+11 0.108857E+11 0.00 0.284884E+12 0.00 0.00 0.240713E+11 0.745012E+10 0.00
December 0.669349E+11 0.187150E+11 0.140770E+12 0.544227E+11 0.363550E+11 0.108208E+11 0.00 0.219937E+12 0.00 0.00 0.240672E+11 0.771403E+10 0.00
                           
Annual Sum or Average 0.782979E+12 0.194146E+12 0.165818E+13 0.640800E+12 0.466325E+12 0.133212E+12 0.00 0.364007E+13 0.00 0.00 0.295437E+12 0.907572E+11 0.00
Minimum of Months 0.603086E+11 0.138956E+11 0.127191E+12 0.491570E+11 0.330042E+11 0.955685E+10 0.00 0.187334E+12 0.00 0.00 0.217819E+11 0.696333E+10 0.00
Maximum of Months 0.669446E+11 0.187150E+11 0.140892E+12 0.544261E+11 0.431038E+11 0.119540E+11 0.00 0.400755E+12 0.00 0.00 0.257433E+11 0.771403E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.116360E+11 0.00 0.228040E+12 0.00 0.00
February 0.137204E+12 0.00 0.898510E+10 0.00 0.204807E+12 0.00 0.00
March 0.152024E+12 0.00 0.898739E+10 0.00 0.222736E+12 0.00 0.00
April 0.146956E+12 0.00 0.325709E+10 0.00 0.209697E+12 0.00 0.00
May 0.151978E+12 0.00 0.270594E+10 0.00 0.210489E+12 0.00 0.00
June 0.147114E+12 0.00 0.205483E+10 0.00 0.199083E+12 0.00 0.00
July 0.151820E+12 0.00 0.180332E+10 0.00 0.203666E+12 0.00 0.00
August 0.152039E+12 0.00 0.246064E+10 0.00 0.205036E+12 0.00 0.00
September 0.146971E+12 0.00 0.201977E+10 0.00 0.202482E+12 0.00 0.00
October 0.151903E+12 0.00 0.268517E+10 0.00 0.215237E+12 0.00 0.00
November 0.147091E+12 0.00 0.469311E+10 0.00 0.214274E+12 0.00 0.00
December 0.151820E+12 0.00 0.112196E+11 0.00 0.226121E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.625080E+11 0.00 0.254167E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.180332E+10 0.00 0.199083E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.116360E+11 0.00 0.228040E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 64632.59 02-JAN-20:10 12338.45 01-JAN-00:10 89171.45 02-JAN-07:10 39169.97 02-JAN-07:19 19733.27 03-JAN-16:10 4540.02 29-JAN-22:00 0.00 01-JAN-00:10
February 64632.59 01-FEB-20:10 12338.45 01-FEB-00:10 89171.45 01-FEB-07:10 39169.97 01-FEB-07:19 20210.84 11-FEB-16:19 4659.12 11-FEB-16:19 0.00 01-FEB-00:10
March 64632.59 01-MAR-20:10 12338.45 01-MAR-00:10 89171.45 01-MAR-07:10 39169.97 13-MAR-06:19 21189.79 27-MAR-18:10 4889.67 09-MAR-22:00 0.00 01-MAR-00:10
April 64632.59 03-APR-19:10 12338.45 01-APR-00:10 89171.45 03-APR-06:10 39169.97 03-APR-06:19 22466.56 17-APR-18:10 4697.06 01-APR-16:00 0.00 01-APR-00:10
May 64632.59 01-MAY-19:10 12338.45 01-MAY-00:10 89171.45 01-MAY-06:10 39169.57 25-MAY-06:19 23316.98 22-MAY-18:30 4864.80 30-MAY-20:00 0.00 01-MAY-00:10
June 64632.59 01-JUN-19:10 12338.45 01-JUN-00:10 89171.45 01-JUN-06:10 39169.68 15-JUN-06:19 24414.81 29-JUN-18:30 5009.84 26-JUN-18:30 0.00 01-JUN-00:10
July 64632.59 03-JUL-19:19 12338.45 01-JUL-00:10 89171.45 03-JUL-06:10 39169.57 13-JUL-06:19 25804.80 28-JUL-18:19 5068.84 13-JUL-18:19 0.00 01-JUL-00:10
August 64632.59 01-AUG-19:10 12338.45 01-AUG-00:10 89171.45 01-AUG-06:10 39169.97 21-AUG-06:19 24654.38 21-AUG-18:19 4953.63 21-AUG-18:30 0.00 01-AUG-00:10
September 64632.59 01-SEP-19:10 12338.45 01-SEP-00:10 89171.45 01-SEP-06:10 39169.97 01-SEP-06:19 24724.74 18-SEP-20:10 5102.69 02-SEP-21:49 0.00 01-SEP-00:10
October 64632.59 02-OCT-19:10 12338.45 01-OCT-00:10 89171.45 02-OCT-06:10 39169.97 02-OCT-06:19 22952.59 06-OCT-20:10 4924.79 03-OCT-20:00 0.00 01-OCT-00:10
November 64632.59 01-NOV-19:10 12338.45 01-NOV-00:10 89171.45 01-NOV-06:10 39169.97 01-NOV-06:19 21600.55 08-NOV-19:10 4791.61 21-NOV-20:40 0.00 01-NOV-00:10
December 64632.59 01-DEC-20:10 12338.45 01-DEC-00:10 89171.45 01-DEC-07:10 39169.97 05-DEC-07:19 21538.52 06-DEC-21:19 5129.86 25-DEC-22:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 64632.59   12338.45   89171.45   39169.57   19733.27   4540.02   0.00  
Maximum of Months 64632.59   12338.45   89171.45   39169.97   25804.80   5129.86   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 150842.86 02-JAN-13:00 0.00 0.00 9938.94 01-JAN-09:20 4738.52 03-JAN-07:10 0.00
February 165188.27 11-FEB-16:10 0.00 0.00 9938.94 01-FEB-09:20 4738.57 02-FEB-07:10 0.00
March 162646.01 09-MAR-22:00 0.00 0.00 9938.94 01-MAR-02:49 4738.76 06-MAR-19:10 0.00
April 177106.56 14-APR-15:20 0.00 0.00 9938.94 01-APR-00:10 4738.57 03-APR-18:10 0.00
May 186721.34 29-MAY-18:10 0.00 0.00 9938.94 01-MAY-00:10 4738.66 17-MAY-18:10 0.00
June 196584.50 08-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.66 19-JUN-18:10 0.00
July 209234.36 28-JUL-15:20 0.00 0.00 9938.94 01-JUL-00:10 4738.73 28-JUL-18:10 0.00
August 198484.65 21-AUG-15:00 0.00 0.00 9938.94 01-AUG-00:10 4738.72 09-AUG-18:10 0.00
September 197959.33 18-SEP-15:20 0.00 0.00 9938.94 01-SEP-00:10 4738.67 13-SEP-18:10 0.00
October 191582.36 03-OCT-15:20 0.00 0.00 9938.94 01-OCT-00:10 4738.65 02-OCT-18:10 0.00
November 169074.52 03-NOV-15:20 0.00 0.00 9938.94 01-NOV-00:10 4738.45 20-NOV-19:10 0.00
December 175993.78 25-DEC-22:00 0.00 0.00 9938.94 01-DEC-00:20 4738.81 14-DEC-07:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 150842.86   0.00 0.00 9938.94   4738.45   0.00
Maximum of Months 209234.36   0.00 0.00 9938.94   4738.81   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 367397.14 06-JAN-20:00 64632.59 86439.81 12338.45 31553.12 17878.83 4529.77 0.00 134150.80 0.00
February 358791.36 11-FEB-20:19 54981.58 82056.51 12338.45 31446.58 16113.77 4551.76 0.00 141454.57 0.00
March 381903.60 13-MAR-19:10 64632.59 86439.81 12338.45 31547.24 19943.16 4591.80 0.00 146208.91 0.00
April 390154.67 14-APR-19:10 64632.59 86439.81 12338.45 31547.24 21464.69 4623.50 0.00 153567.10 0.00
May 410227.73 29-MAY-19:10 59807.00 84978.71 12338.45 31511.17 21074.46 4843.85 0.00 180361.17 0.00
June 427423.15 29-JUN-19:19 64632.59 86439.81 12338.45 31552.79 23871.07 4961.83 0.00 187237.75 0.00
July 431924.87 27-JUL-19:10 64632.59 86439.81 12338.45 31546.78 24682.71 5035.93 0.00 191315.79 0.00
August 421841.21 02-AUG-19:10 64632.59 86439.81 12338.45 31546.33 23605.47 4898.94 0.00 182515.79 0.00
September 422602.41 18-SEP-19:10 64632.59 86439.81 12338.45 31547.24 24249.60 4911.58 0.00 182274.44 0.00
October 410537.59 03-OCT-19:19 64632.59 86439.81 12338.45 31553.12 21947.87 4854.90 0.00 172867.77 0.00
November 397846.47 29-NOV-20:49 64632.59 86439.81 12338.45 31553.12 19347.54 4748.23 0.00 162514.35 0.00
December 383734.28 25-DEC-20:00 59807.00 84978.71 12338.45 31515.42 15834.01 4834.32 0.00 159112.73 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 358791.36   54981.58 82056.51 12338.45 31446.58 15834.01 4529.77 0.00 134150.80 0.00
Maximum of Months 431924.87   64632.59 86439.81 12338.45 31553.12 24682.71 5035.93 0.00 191315.79 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 34487.77 25-JAN-09:20 0.00 219783.77 18-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 46790.58 04-FEB-05:00 0.00 218986.40 01-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 43192.23 16-MAR-08:09 0.00 214579.25 01-MAR-21:19 0.00
April 104248.32 01-APR-17:10 0.00 10409.03 19-APR-02:00 0.00 212727.13 03-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 10250.74 01-MAY-03:49 0.00 210819.17 01-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 8859.77 19-JUN-03:00 0.00 208734.44 02-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 7872.25 03-JUL-03:49 0.00 207559.79 03-JUL-20:30 0.00
August 104248.32 01-AUG-17:10 0.00 9136.42 29-AUG-03:00 0.00 208496.92 31-AUG-20:00 0.00
September 104248.32 01-SEP-17:10 0.00 8086.11 05-SEP-03:00 0.00 210245.14 29-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 9183.81 02-OCT-03:00 0.00 212481.55 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 25860.40 13-NOV-04:00 0.00 214267.56 30-NOV-21:40 0.00
December 104248.32 01-DEC-18:10 0.00 32390.05 21-DEC-03:00 0.00 217527.14 31-DEC-22:49 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 7872.25   0.00 207559.79   0.00
Maximum of Months 104248.32   0.00 46790.58   0.00 219783.77   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
October 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
November 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.67 21.69 0.67 21.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
June 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
July 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
                 
Annual Sum or Average 0.00   0.00   1.50 21.72 1.50 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.33 21.75 1.33 21.75
March 0.00 0.00 0.00 0.00 2.00 21.72 2.00 21.72
April 0.00 0.00 0.00 0.00 1.50 21.76 1.50 21.76
May 0.00 0.00 0.00 0.00 0.67 21.96 0.67 21.96
June 0.00 0.00 0.00 0.00 0.67 21.85 0.67 21.85
July 0.00 0.00 0.00 0.00 0.33 22.03 0.33 22.03
August 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
September 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
October 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
November 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
December 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78
                 
Annual Sum or Average 0.00   0.00   8.33 21.78 8.33 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 22.03 2.00 22.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
February 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
March 0.00 0.00 0.00 0.00 2.17 21.84 2.17 21.84
April 0.00 0.00 0.00 0.00 3.67 22.05 3.67 22.05
May 0.00 0.00 0.00 0.00 1.33 22.03 1.33 22.03
June 0.00 0.00 0.00 0.00 0.67 21.86 0.67 21.86
July 0.00 0.00 0.00 0.00 0.33 21.89 0.33 21.89
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.83 21.87 0.83 21.87
October 0.00 0.00 0.00 0.00 1.83 22.10 1.83 22.10
November 0.00 0.00 0.00 0.00 1.17 21.92 1.17 21.92
December 0.00 0.00 0.00 0.00 0.67 21.89 0.67 21.89
                 
Annual Sum or Average 0.00   0.00   14.00 21.95 14.00 21.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.67 22.10 3.67 22.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.72 0.83 21.72
May 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
June 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
July 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73
August 0.00 0.00 0.00 0.00 1.17 21.71 1.17 21.71
September 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
October 0.00 0.00 0.00 0.00 1.83 21.75 1.83 21.75
November 0.00 0.00 0.00 0.00 0.50 21.68 0.50 21.68
December 0.00 0.00 0.00 0.00 0.83 21.70 0.83 21.70
                 
Annual Sum or Average 0.00   0.00   9.33 21.73 9.33 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 21.78 1.83 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.83 21.68 0.83 21.68
April 0.00 0.00 0.00 0.00 1.33 21.72 1.33 21.72
May 0.00 0.00 0.00 0.00 0.67 21.84 0.67 21.84
June 0.00 0.00 0.00 0.00 1.00 21.75 1.00 21.75
July 0.00 0.00 0.00 0.00 1.17 21.79 1.17 21.79
August 0.00 0.00 0.00 0.00 0.67 21.69 0.67 21.69
September 0.00 0.00 0.00 0.00 0.67 21.68 0.67 21.68
October 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
                 
Annual Sum or Average 0.00   0.00   6.67 21.73 6.67 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.84 1.33 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.50 21.90 4.50 21.90
February 0.00 0.00 0.00 0.00 3.83 21.92 3.83 21.92
March 0.00 0.00 0.00 0.00 2.67 21.78 2.67 21.78
April 0.00 0.00 0.00 0.00 2.67 21.76 2.67 21.76
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
July 0.00 0.00 0.00 0.00 1.17 21.77 1.17 21.77
August 0.00 0.00 0.00 0.00 2.67 21.77 2.67 21.77
September 0.00 0.00 0.00 0.00 4.17 21.85 4.17 21.85
October 0.00 0.00 0.00 0.00 7.00 21.93 7.00 21.93
November 0.00 0.00 0.00 0.00 4.17 21.89 4.17 21.89
December 0.00 0.00 0.00 0.00 4.50 21.92 4.50 21.92
                 
Annual Sum or Average 0.00   0.00   37.50 21.87 37.50 21.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.00 21.93 7.00 21.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.41 0.00 22.41 0.00 22.41
February 672.00 22.26 0.00 22.26 0.00 22.26
March 744.00 22.07 0.00 22.07 0.00 22.07
April 720.00 22.23 0.00 22.23 0.00 22.23
May 744.00 22.49 0.00 22.49 0.00 22.49
June 720.00 22.76 0.00 22.76 0.00 22.76
July 695.17 23.01 0.00 23.01 0.00 23.01
August 595.33 23.03 0.00 23.03 0.00 23.03
September 393.83 23.12 2.67 23.13 0.00 23.13
October 473.50 23.12 0.00 23.12 0.00 23.12
November 658.50 22.92 0.00 22.92 0.00 22.92
December 735.17 22.63 0.00 22.63 0.00 22.63
             
Annual Sum or Average 7895.50 22.63 2.67 22.63 0.00 22.63
Minimum of Months 393.83 22.07 0.00 22.07 0.00 22.07
Maximum of Months 744.00 23.12 2.67 23.13 0.00 23.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 577.83 21.58 100.00 21.90 0.00 21.90
February 485.00 21.64 118.17 22.02 5.83 22.01
March 529.33 21.72 120.50 22.06 0.17 22.06
April 444.67 21.92 185.67 22.45 0.00 22.45
May 350.50 22.25 271.00 22.87 0.00 22.87
June 180.17 22.41 368.83 23.26 0.00 23.26
July 84.83 22.50 490.00 23.59 0.00 23.59
August 173.33 22.18 439.67 23.31 0.00 23.31
September 119.50 22.41 506.17 23.54 0.00 23.54
October 205.17 22.34 430.17 23.36 0.00 23.36
November 354.00 21.93 289.17 22.76 0.00 22.76
December 510.33 21.62 163.83 22.15 0.00 22.15
             
Annual Sum or Average 4014.67 21.88 3483.17 22.75 6.00 22.75
Minimum of Months 84.83 21.58 100.00 21.90 0.00 21.90
Maximum of Months 577.83 22.50 506.17 23.59 5.83 23.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 741.83 21.60 0.00 21.60 0.00 21.60
February 669.00 21.79 0.00 21.79 0.00 21.79
March 718.33 21.90 0.67 21.90 0.00 21.90
April 609.83 22.19 36.83 22.28 0.00 22.28
May 531.00 22.40 85.17 22.59 0.00 22.59
June 406.33 22.58 128.50 22.87 0.00 22.87
July 264.83 22.71 245.67 23.23 0.00 23.23
August 370.17 22.54 192.17 22.96 0.00 22.96
September 292.67 22.66 211.17 23.12 0.00 23.12
October 458.17 22.59 111.17 22.82 0.00 22.82
November 624.67 22.21 22.50 22.26 0.00 22.26
December 701.83 21.79 2.00 21.79 0.00 21.79
             
Annual Sum or Average 6388.67 22.14 1035.83 22.37 0.00 22.37
Minimum of Months 264.83 21.60 0.00 21.60 0.00 21.60
Maximum of Months 741.83 22.71 245.67 23.23 0.00 23.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.25 0.00 21.25 0.00 21.25
February 672.00 21.39 0.00 21.39 0.00 21.39
March 744.00 21.53 4.50 21.53 4.50 21.52
April 720.00 22.05 0.00 22.05 0.00 22.05
May 677.50 22.67 0.00 22.67 0.00 22.67
June 371.17 23.04 50.00 23.15 0.00 23.15
July 130.17 23.14 155.33 23.58 0.00 23.58
August 429.00 22.87 58.83 23.00 0.00 23.00
September 362.50 23.03 51.33 23.14 0.00 23.14
October 703.83 22.79 0.00 22.79 0.00 22.79
November 720.00 22.14 0.00 22.14 0.00 22.14
December 744.00 21.54 0.00 21.54 0.00 21.54
             
Annual Sum or Average 7018.17 22.11 320.00 22.19 4.50 22.19
Minimum of Months 130.17 21.25 0.00 21.25 0.00 21.25
Maximum of Months 744.00 23.14 155.33 23.58 4.50 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 0.00 21.24 0.00 21.24
February 672.00 21.37 0.00 21.37 0.00 21.37
March 744.00 21.50 1.17 21.50 1.17 21.49
April 720.00 21.99 0.00 21.99 0.00 21.99
May 730.50 22.64 0.00 22.64 0.00 22.64
June 511.17 23.04 7.00 23.05 0.00 23.05
July 261.83 23.17 48.67 23.28 0.00 23.28
August 504.33 22.88 17.50 22.91 0.00 22.91
September 468.00 23.04 5.83 23.05 0.00 23.05
October 735.67 22.77 0.00 22.77 0.00 22.77
November 720.00 22.11 0.00 22.11 0.00 22.11
December 744.00 21.52 0.00 21.52 0.00 21.52
             
Annual Sum or Average 7555.50 22.15 80.17 22.17 1.17 22.17
Minimum of Months 261.83 21.24 0.00 21.24 0.00 21.24
Maximum of Months 744.00 23.17 48.67 23.28 1.17 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 271.83 22.27 344.83 22.51 114.50 22.74
February 214.50 22.53 341.83 22.58 109.17 22.81
March 218.50 22.80 448.17 22.54 131.00 22.78
April 146.67 23.84 557.67 22.56 139.83 22.79
May 152.33 23.93 647.17 22.53 150.50 22.76
June 157.67 23.93 688.33 22.51 157.67 22.74
July 170.33 23.91 727.17 22.52 170.33 22.74
August 158.83 23.94 675.33 22.54 158.83 22.76
September 154.33 23.94 692.00 22.49 154.33 22.71
October 147.33 23.97 644.83 22.51 147.00 22.74
November 170.17 23.29 507.17 22.54 130.17 22.77
December 262.33 22.42 387.17 22.50 123.83 22.74
             
Annual Sum or Average 2224.83 23.25 6661.67 22.53 1687.17 22.76
Minimum of Months 146.67 22.27 341.83 22.49 109.17 22.71
Maximum of Months 271.83 23.97 727.17 22.58 170.33 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 411.67 22.04 238.00 22.60 0.00 22.60
February 333.83 22.06 248.67 22.70 0.00 22.70
March 352.33 21.96 270.67 22.62 0.00 22.62
April 269.67 22.01 338.00 22.85 0.00 22.85
May 191.67 22.12 434.17 23.13 2.33 23.14
June 117.00 22.49 503.83 23.43 25.50 23.45
July 60.67 22.79 614.00 23.56 20.50 23.58
August 108.83 22.32 553.83 23.47 16.00 23.48
September 37.67 22.38 626.00 23.66 4.17 23.66
October 65.00 22.37 623.17 23.64 9.50 23.65
November 159.67 22.09 476.50 23.27 1.00 23.27
December 359.50 22.07 300.83 22.78 0.00 22.78
             
Annual Sum or Average 2467.50 22.11 5227.67 23.15 79.00 23.16
Minimum of Months 37.67 21.96 238.00 22.60 0.00 22.60
Maximum of Months 411.67 22.79 626.00 23.66 25.50 23.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 696.17 22.08 11.00 22.11 0.00 22.11
February 618.83 22.17 4.50 22.18 0.00 22.18
March 644.33 22.14 18.33 22.18 0.00 22.18
April 526.33 22.34 72.33 22.50 0.00 22.50
May 363.00 22.42 223.33 22.90 0.00 22.90
June 218.67 22.54 358.67 23.29 0.00 23.29
July 122.33 22.64 436.00 23.53 0.00 23.53
August 205.50 22.52 383.17 23.32 0.00 23.32
September 103.67 22.59 441.00 23.54 0.00 23.54
October 164.33 22.58 367.33 23.36 0.00 23.36
November 403.00 22.40 164.50 22.77 0.00 22.77
December 589.17 22.12 62.33 22.27 0.00 22.27
             
Annual Sum or Average 4655.33 22.28 2542.50 22.79 0.00 22.79
Minimum of Months 103.67 22.08 4.50 22.11 0.00 22.11
Maximum of Months 696.17 22.64 441.00 23.54 0.00 23.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 722.50 21.60 4.00 21.60 4.00 21.61
February 640.00 21.59 5.50 21.60 5.50 21.61
March 699.50 21.57 4.33 21.57 4.33 21.58
April 658.83 21.58 0.17 21.58 0.17 21.58
May 656.67 21.52 0.33 21.53 0.33 21.53
June 616.00 21.47 0.33 21.47 0.00 21.47
July 617.00 21.42 0.00 21.42 0.00 21.42
August 628.00 21.45 5.67 21.46 5.67 21.48
September 597.83 21.42 0.00 21.42 0.00 21.42
October 635.67 21.47 0.83 21.47 0.83 21.47
November 650.83 21.54 2.67 21.55 2.67 21.55
December 701.33 21.55 7.33 21.56 7.33 21.57
             
Annual Sum or Average 7824.17 21.52 31.17 21.52 30.83 21.53
Minimum of Months 597.83 21.42 0.00 21.42 0.00 21.42
Maximum of Months 722.50 21.60 7.33 21.60 7.33 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 734.67 21.87 45.33 21.93 45.33 21.99
February 640.50 22.02 60.00 22.11 57.00 22.18
March 661.67 21.96 63.50 22.10 47.83 22.18
April 603.83 21.91 59.50 22.10 33.17 22.18
May 650.00 21.64 20.00 21.70 18.67 21.76
June 607.17 21.50 9.33 21.54 6.00 21.56
July 611.17 21.49 12.50 21.55 10.50 21.59
August 630.50 21.49 14.67 21.53 12.17 21.57
September 611.00 21.54 16.33 21.60 15.00 21.64
October 668.00 21.66 20.00 21.71 20.00 21.76
November 673.00 21.82 40.00 21.90 40.00 21.97
December 698.83 21.80 62.00 21.90 59.67 21.98
             
Annual Sum or Average 7790.33 21.73 423.17 21.82 365.33 21.88
Minimum of Months 603.83 21.49 9.33 21.53 6.00 21.56
Maximum of Months 734.67 22.02 63.50 22.11 59.67 22.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.84 29.50 21.88 29.50 21.93
February 671.33 22.01 45.83 22.09 45.83 22.16
March 743.00 22.00 42.50 22.08 42.50 22.14
April 714.17 22.07 25.83 22.12 25.83 22.17
May 744.00 21.81 16.33 21.85 16.33 21.88
June 719.50 21.75 6.33 21.77 6.33 21.78
July 744.00 21.78 11.00 21.81 11.00 21.84
August 744.00 21.73 6.67 21.74 6.67 21.75
September 719.50 21.77 10.00 21.79 10.00 21.81
October 744.00 21.77 14.50 21.80 14.50 21.83
November 720.00 21.86 29.00 21.91 29.00 21.95
December 744.00 21.87 41.50 21.94 41.50 21.99
             
Annual Sum or Average 8751.50 21.85 279.00 21.90 279.00 21.94
Minimum of Months 671.33 21.73 6.33 21.74 6.33 21.75
Maximum of Months 744.00 22.07 45.83 22.12 45.83 22.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 728.17 21.64 3.17 21.65 3.17 21.65
February 662.83 21.68 4.83 21.69 4.83 21.69
March 707.83 21.64 3.67 21.64 3.67 21.65
April 646.17 21.56 0.00 21.56 0.00 21.56
May 626.17 21.45 0.33 21.45 0.33 21.45
June 572.50 21.34 0.00 21.34 0.00 21.34
July 575.67 21.29 0.00 21.29 0.00 21.29
August 601.33 21.37 5.83 21.39 5.83 21.40
September 568.50 21.33 0.00 21.33 0.00 21.33
October 609.50 21.40 0.67 21.40 0.67 21.40
November 648.17 21.55 2.50 21.56 2.50 21.56
December 711.33 21.58 9.50 21.60 9.50 21.61
             
Annual Sum or Average 7658.17 21.50 30.50 21.50 30.50 21.51
Minimum of Months 568.50 21.29 0.00 21.29 0.00 21.29
Maximum of Months 728.17 21.68 9.50 21.69 9.50 21.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 734.50 21.92 46.83 22.01 45.00 22.08
February 656.00 22.11 60.67 22.21 56.67 22.29
March 689.83 22.07 60.67 22.21 48.33 22.31
April 592.83 21.94 59.67 22.16 33.50 22.26
May 603.67 21.53 24.67 21.63 19.33 21.71
June 561.33 21.37 10.33 21.42 6.17 21.45
July 565.33 21.35 14.83 21.43 10.67 21.49
August 600.50 21.41 14.67 21.45 12.50 21.49
September 574.33 21.45 16.83 21.52 14.17 21.58
October 647.33 21.64 21.17 21.71 19.50 21.78
November 692.67 21.92 42.83 22.02 41.17 22.11
December 737.17 21.86 65.00 21.95 63.33 22.02
             
Annual Sum or Average 7655.50 21.73 438.17 21.84 370.33 21.91
Minimum of Months 561.33 21.35 10.33 21.42 6.17 21.45
Maximum of Months 737.17 22.11 65.00 22.21 63.33 22.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.65 0.00 21.65 0.00 21.65
February 672.00 21.78 0.00 21.78 0.00 21.78
March 744.00 21.90 0.00 21.90 0.00 21.90
April 720.00 22.39 0.00 22.39 0.00 22.39
May 744.00 22.66 0.00 22.66 0.00 22.66
June 720.00 22.99 0.00 22.99 0.00 22.99
July 719.83 23.14 0.00 23.14 0.00 23.14
August 722.33 22.98 0.00 22.98 0.00 22.98
September 676.33 23.08 0.00 23.08 0.00 23.08
October 744.00 22.94 0.00 22.94 0.00 22.94
November 720.00 22.40 0.00 22.40 0.00 22.40
December 744.00 21.80 0.00 21.80 0.00 21.80
             
Annual Sum or Average 8670.50 22.47 0.00 22.47 0.00 22.47
Minimum of Months 672.00 21.65 0.00 21.65 0.00 21.65
Maximum of Months 744.00 23.14 0.00 23.14 0.00 23.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 683.17 21.49 17.33 21.51 15.50 21.52
February 600.00 21.47 26.17 21.51 18.50 21.52
March 654.33 21.44 19.83 21.47 14.83 21.49
April 602.33 21.41 20.33 21.47 4.33 21.48
May 602.33 21.36 22.33 21.43 2.33 21.44
June 575.00 21.34 23.83 21.42 0.33 21.42
July 581.00 21.30 43.17 21.44 0.00 21.44
August 595.83 21.35 46.00 21.49 7.33 21.51
September 568.17 21.32 46.33 21.47 4.00 21.48
October 593.50 21.34 44.67 21.47 4.50 21.48
November 614.50 21.43 29.17 21.50 8.17 21.52
December 666.67 21.45 37.67 21.51 20.17 21.53
             
Annual Sum or Average 7336.83 21.39 376.83 21.48 100.00 21.49
Minimum of Months 568.17 21.30 17.33 21.42 0.00 21.42
Maximum of Months 683.17 21.49 46.33 21.51 20.17 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 698.17 21.81 77.67 21.91 71.50 21.97
February 582.33 21.90 103.00 22.09 84.67 22.18
March 603.17 21.83 116.33 22.14 71.83 22.23
April 549.33 21.76 107.83 22.14 50.83 22.26
May 597.83 21.49 49.00 21.65 28.00 21.73
June 568.83 21.38 37.50 21.51 8.83 21.55
July 576.50 21.39 60.67 21.61 13.00 21.67
August 596.33 21.39 46.50 21.53 15.50 21.56
September 572.17 21.42 43.67 21.56 20.17 21.61
October 615.17 21.50 37.83 21.59 30.17 21.65
November 635.17 21.71 56.50 21.81 55.17 21.90
December 669.00 21.74 96.00 21.89 87.67 21.98
             
Annual Sum or Average 7264.00 21.62 832.50 21.80 537.33 21.88
Minimum of Months 549.33 21.38 37.50 21.51 8.83 21.55
Maximum of Months 698.17 21.90 116.33 22.14 87.67 22.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 643.00 21.45 33.83 21.54 6.33 21.55
February 584.67 21.48 21.33 21.53 10.17 21.54
March 665.17 21.51 13.50 21.53 13.50 21.55
April 648.33 21.55 3.17 21.56 3.17 21.56
May 656.67 21.52 2.33 21.53 2.33 21.53
June 623.33 21.49 0.00 21.49 0.00 21.49
July 625.83 21.44 0.17 21.44 0.17 21.44
August 630.67 21.46 4.83 21.47 4.67 21.48
September 584.50 21.38 28.83 21.47 1.67 21.48
October 598.83 21.38 57.67 21.55 3.50 21.55
November 599.50 21.42 43.67 21.55 2.33 21.55
December 637.33 21.44 39.17 21.54 8.50 21.56
             
Annual Sum or Average 7497.83 21.46 248.50 21.52 56.33 21.53
Minimum of Months 584.50 21.38 0.00 21.44 0.00 21.44
Maximum of Months 665.17 21.55 57.67 21.56 13.50 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 396.50 22.25 236.17 22.82 6.50 22.83
February 279.83 22.24 288.33 23.02 0.00 23.02
March 241.50 22.22 398.17 23.19 0.00 23.19
April 73.83 22.36 526.00 23.60 1.83 23.60
May 7.50 22.43 662.83 23.76 0.00 23.76
June 0.00 0.00 702.50 23.78 0.00 23.78
July 0.00 0.00 739.83 23.82 0.00 23.82
August 13.17 22.44 697.33 23.75 0.83 23.75
September 0.00 0.00 671.33 23.79 0.00 23.79
October 20.00 22.57 619.67 23.74 1.83 23.74
November 147.67 22.33 438.50 23.42 3.50 23.42
December 299.00 22.15 323.50 22.97 0.00 22.97
             
Annual Sum or Average 1479.00 22.24 6304.17 23.49 14.50 23.49
Minimum of Months 0.00 0.00 236.17 22.82 0.00 22.83
Maximum of Months 396.50 22.57 739.83 23.82 6.50 23.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 271.17 22.24 331.67 23.06 0.00 23.06
February 192.83 22.30 373.33 23.25 0.00 23.25
March 139.83 22.24 469.67 23.41 0.00 23.41
April 22.17 22.38 621.83 23.68 0.00 23.68
May 0.00 0.00 724.17 23.76 0.00 23.76
June 0.00 0.00 716.83 23.82 0.00 23.82
July 0.00 0.00 744.00 23.86 0.00 23.86
August 4.83 22.30 723.67 23.79 0.00 23.79
September 0.00 0.00 713.83 23.78 0.00 23.78
October 0.00 0.00 688.00 23.74 0.00 23.74
November 90.67 22.35 520.67 23.53 0.00 23.53
December 210.17 22.17 415.67 23.19 0.00 23.19
             
Annual Sum or Average 931.67 22.25 7043.33 23.59 0.00 23.59
Minimum of Months 0.00 0.00 331.67 23.06 0.00 23.06
Maximum of Months 271.17 22.38 744.00 23.86 0.00 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 590.00 23.63 628.67 23.69 513.33 23.78
February 519.33 23.70 576.17 23.72 465.33 23.80
March 563.00 23.78 667.17 23.73 521.33 23.80
April 523.33 23.95 685.00 23.76 516.67 23.83
May 550.50 23.98 738.83 23.76 550.33 23.83
June 542.33 23.98 719.83 23.79 542.33 23.85
July 561.33 23.98 744.00 23.79 561.33 23.85
August 556.00 23.98 741.83 23.78 556.00 23.84
September 540.83 23.98 720.00 23.78 540.83 23.84
October 546.50 23.98 739.83 23.76 546.50 23.83
November 536.83 23.87 672.17 23.74 515.83 23.82
December 576.00 23.70 647.83 23.71 518.17 23.79
             
Annual Sum or Average 6606.00 23.88 8281.33 23.75 6348.00 23.82
Minimum of Months 519.33 23.63 576.17 23.69 465.33 23.78
Maximum of Months 590.00 23.98 744.00 23.79 561.33 23.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.46 0.00 21.46 0.00 21.46
February 669.67 21.66 3.50 21.65 3.50 21.65
March 744.00 21.82 0.00 21.82 0.00 21.82
April 658.50 22.25 2.33 22.25 0.00 22.25
May 551.17 22.65 15.17 22.68 0.00 22.68
June 313.00 22.87 139.83 23.19 0.00 23.19
July 239.67 22.97 285.83 23.47 0.00 23.47
August 361.00 22.75 153.00 23.09 0.00 23.09
September 299.00 22.82 211.00 23.27 0.00 23.27
October 488.67 22.71 37.83 22.79 0.00 22.79
November 674.00 22.20 0.00 22.20 0.00 22.20
December 736.83 21.68 0.00 21.68 0.00 21.68
             
Annual Sum or Average 6479.50 22.16 848.50 22.36 3.50 22.36
Minimum of Months 239.67 21.46 0.00 21.46 0.00 21.46
Maximum of Months 744.00 22.97 285.83 23.47 3.50 23.47



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.41421 50.79816 0.05341 5.25077
February 672.00000 22.26457 51.53820 0.01932 5.17816
March 744.00000 22.06833 52.85371 -0.0236 5.21516
April 720.00000 22.23426 55.39295 0.03472 5.13872
May 744.00000 22.49488 55.06327 -0.9377 23.73485
June 720.00000 22.76279 54.30178 -0.8444 20.15027
July 744.00000 23.04515 53.46247 -0.7466 16.83877
August 744.00000 23.12201 53.26690 -0.7210 16.08780
September 720.00000 23.30268 52.61104 -0.6579 14.24082
October 744.00000 23.25333 52.71812 0.28781 6.77558
November 720.00000 22.96858 52.35521 0.20959 6.05410
December 744.00000 22.63775 52.31983 0.12162 5.51869
           
Annual Sum or Average 8760.00000 22.71661 53.06262 -0.2689 10.88925
Minimum of Months 672.00000 22.06833 50.79816 -0.9377 5.13872
Maximum of Months 744.00000 23.30268 55.39295 0.28781 23.73485



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.00967 52.32648 0.04077 6.81210
February 672.00000 22.15983 52.27730 0.08795 6.94274
March 744.00000 22.18895 53.11794 0.10234 6.76218
April 720.00000 22.52339 55.46017 0.21761 7.18795
May 744.00000 22.88939 55.61486 -0.6356 14.89203
June 720.00000 23.19303 55.24744 -0.5190 11.58905
July 744.00000 23.44787 54.37362 -0.4187 9.52156
August 744.00000 23.25249 55.10301 -0.4892 11.56004
September 720.00000 23.46598 54.01170 -0.3985 9.56700
October 744.00000 23.30296 54.16879 0.44234 9.92717
November 720.00000 22.79110 54.01442 0.28705 8.45184
December 744.00000 22.23225 54.17847 0.11951 7.36387
           
Annual Sum or Average 8760.00000 22.79099 54.16755 -0.0984 9.23364
Minimum of Months 672.00000 22.00967 52.27730 -0.6356 6.76218
Maximum of Months 744.00000 23.46598 55.61486 0.44234 14.89203



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.60605 54.10014 -0.0880 5.62347
February 672.00000 21.79798 53.91104 -0.0384 5.57979
March 744.00000 21.94896 54.33930 0.00523 5.66469
April 720.00000 22.38936 56.25498 0.13614 5.92418
May 744.00000 22.71055 56.11220 -0.7732 18.41918
June 720.00000 22.96601 55.64149 -0.6801 15.32358
July 744.00000 23.22194 54.85371 -0.5879 12.74744
August 744.00000 23.02396 55.52169 -0.6582 14.88305
September 720.00000 23.14943 54.93783 -0.6129 13.46089
October 744.00000 22.91560 55.43818 0.27538 6.85464
November 720.00000 22.36897 55.54500 0.12850 5.92079
December 744.00000 21.87548 55.72113 -0.0060 5.69990
           
Annual Sum or Average 8760.00000 22.50119 55.20429 -0.2431 9.70351
Minimum of Months 672.00000 21.60605 53.91104 -0.7732 5.57979
Maximum of Months 744.00000 23.22194 56.25498 0.27538 18.41918



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.81303 49.67216 0.45407 11.61173
February 672.00000 21.83663 49.90297 0.47935 12.20525
March 744.00000 21.87234 50.61250 0.51142 12.89644
April 720.00000 21.94723 53.48992 0.58602 14.44413
May 744.00000 22.04909 53.74484 -0.1613 9.95211
June 720.00000 22.13636 53.56766 -0.0944 9.48941
July 744.00000 22.17218 53.45512 -0.0653 9.29428
August 744.00000 22.09378 53.74215 -0.1310 9.79707
September 720.00000 22.11610 53.51463 -0.1052 9.49014
October 744.00000 22.02198 53.74514 0.62842 15.40051
November 720.00000 21.92162 52.70979 0.55654 13.78048
December 744.00000 21.83247 51.87516 0.48012 12.07989
           
Annual Sum or Average 8760.00000 21.98511 52.51508 0.26005 11.69826
Minimum of Months 672.00000 21.81303 49.67216 -0.1613 9.29428
Maximum of Months 744.00000 22.17218 53.74514 0.62842 15.40051



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.64585 56.79081 0.25882 7.75561
February 672.00000 22.73299 56.95562 0.28643 7.97012
March 744.00000 22.66259 58.00839 0.27215 7.73206
April 720.00000 22.85102 60.60909 0.34849 8.33647
May 744.00000 23.05362 60.89600 -0.5187 11.67563
June 720.00000 23.26835 60.49627 -0.4258 9.67729
July 744.00000 23.43451 59.89838 -0.3569 8.31633
August 744.00000 23.34578 60.22243 -0.3916 9.38109
September 720.00000 23.57119 59.07192 -0.2920 7.62819
October 744.00000 23.55330 59.03049 0.56377 12.20342
November 720.00000 23.21595 58.64292 0.45158 10.37236
December 744.00000 22.78685 58.69297 0.31515 8.47339
           
Annual Sum or Average 8760.00000 23.09500 59.12079 0.04086 9.13769
Minimum of Months 672.00000 22.64585 56.79081 -0.5187 7.62819
Maximum of Months 744.00000 23.57119 60.89600 0.56377 12.20342



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.16130 56.35624 0.06866 5.67407
February 672.00000 22.26381 56.45608 0.09765 5.79783
March 744.00000 22.29997 57.22194 0.11202 5.97477
April 720.00000 22.62462 59.46560 0.21729 6.43296
May 744.00000 22.95939 59.30044 -0.6588 14.85627
June 720.00000 23.24860 58.72680 -0.5481 11.90855
July 744.00000 23.40408 58.18541 -0.4879 10.45891
August 744.00000 23.26785 58.68752 -0.5394 11.79670
September 720.00000 23.41510 57.99458 -0.4829 10.40057
October 744.00000 23.27284 58.29382 0.39478 8.51139
November 720.00000 22.84947 58.05514 0.27336 7.12483
December 744.00000 22.37759 58.12642 0.14019 6.12117
           
Annual Sum or Average 8760.00000 22.84809 58.08044 -0.1193 8.77682
Minimum of Months 672.00000 22.16130 56.35624 -0.6588 5.67407
Maximum of Months 744.00000 23.41510 59.46560 0.39478 14.85627



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64585 56.00859 -0.1037 5.98959
February 672.00000 21.67192 55.37566 -0.0815 5.98547
March 744.00000 21.67274 55.01758 -0.0672 5.92282
April 720.00000 21.72553 55.54368 -0.0198 5.80559
May 744.00000 21.73701 55.72279 -1.0776 30.77168
June 720.00000 21.74018 55.82772 -1.0623 30.08580
July 744.00000 21.74427 55.24435 -1.0438 29.31788
August 744.00000 21.74142 55.86570 -1.0546 29.78881
September 720.00000 21.74211 55.36569 -1.0515 29.70037
October 744.00000 21.74057 55.25077 0.00520 5.77823
November 720.00000 21.71235 55.73874 -0.0379 5.85515
December 744.00000 21.65027 57.85616 -0.0783 5.90426
           
Annual Sum or Average 8760.00000 21.71045 55.73901 -0.4752 15.96896
Minimum of Months 672.00000 21.64585 55.01758 -1.0776 5.77823
Maximum of Months 744.00000 21.74427 57.85616 0.00520 30.77168



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.88848 58.66288 -0.0740 6.07099
February 672.00000 22.09173 57.27175 -0.0106 6.23212
March 744.00000 22.15270 56.11350 0.02240 6.27957
April 720.00000 22.20629 56.31242 0.07861 6.24086
May 744.00000 21.85560 55.95866 -1.0406 29.31543
June 720.00000 21.79171 55.77017 -1.0431 29.35197
July 744.00000 21.82073 55.32393 -1.0180 28.39229
August 744.00000 21.77544 56.14813 -1.0479 29.52108
September 720.00000 21.81692 56.09238 -1.0421 29.33858
October 744.00000 21.83493 56.81614 0.01197 5.80723
November 720.00000 21.92119 58.04349 -0.0078 5.89114
December 744.00000 21.90892 60.60489 -0.0414 6.05100
           
Annual Sum or Average 8760.00000 21.92053 56.92777 -0.4371 15.76367
Minimum of Months 672.00000 21.77544 55.32393 -1.0479 5.80723
Maximum of Months 744.00000 22.20629 60.60489 0.07861 29.52108



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.83732 55.94827 -0.1160 6.01874
February 672.00000 22.01520 55.84937 -0.0639 6.00703
March 744.00000 22.00720 55.69586 -0.0576 5.97638
April 720.00000 22.07872 56.79398 -0.0166 5.84288
May 744.00000 21.80798 56.27369 -1.1697 34.78670
June 720.00000 21.75160 55.89709 -1.1758 35.02219
July 744.00000 21.77965 55.79220 -1.1634 34.52227
August 744.00000 21.73106 56.32518 -1.1890 35.59193
September 720.00000 21.77107 56.47647 -1.1771 35.10633
October 744.00000 21.77284 57.09281 -0.0782 5.73565
November 720.00000 21.85976 57.07038 -0.0761 5.76496
December 744.00000 21.87414 58.42867 -0.0860 5.86640
           
Annual Sum or Average 8760.00000 21.85582 56.47446 -0.5337 18.09241
Minimum of Months 672.00000 21.73106 55.69586 -1.1890 5.73565
Maximum of Months 744.00000 22.07872 58.42867 -0.0166 35.59193



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67920 55.22070 -0.0953 5.98746
February 672.00000 21.70224 54.86518 -0.0752 5.96952
March 744.00000 21.71842 54.51647 -0.0592 5.90814
April 720.00000 21.74276 55.01903 -0.0177 5.84627
May 744.00000 21.74680 55.46897 -1.0728 30.62674
June 720.00000 21.75033 55.45919 -1.0458 29.43421
July 744.00000 21.75197 54.97916 -1.0332 28.93251
August 744.00000 21.74758 55.81332 -1.0509 29.68682
September 720.00000 21.75008 55.14931 -1.0392 29.22461
October 744.00000 21.74822 55.16601 0.00983 5.80226
November 720.00000 21.72777 55.58874 -0.0331 5.85151
December 744.00000 21.66129 57.94197 -0.0819 5.89279
           
Annual Sum or Average 8760.00000 21.72726 55.43841 -0.4687 15.82406
Minimum of Months 672.00000 21.66129 54.51647 -1.0728 5.80226
Maximum of Months 744.00000 21.75197 57.94197 0.00983 30.62674



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.94749 57.68685 -0.0606 6.13575
February 672.00000 22.15414 56.64219 0.00204 6.25104
March 744.00000 22.19002 55.64333 0.02861 6.25667
April 720.00000 22.24889 55.80614 0.08601 6.43346
May 744.00000 21.88005 55.77176 -1.0313 29.10984
June 720.00000 21.80633 55.44721 -1.0253 28.69090
July 744.00000 21.83295 55.07692 -1.0061 28.00969
August 744.00000 21.78162 56.07446 -1.0443 29.42374
September 720.00000 21.83498 55.84969 -1.0269 28.79398
October 744.00000 21.86245 56.34316 0.01889 5.91162
November 720.00000 21.97756 57.57580 0.00422 6.00777
December 744.00000 21.87829 60.80594 -0.0540 6.03775
           
Annual Sum or Average 8760.00000 21.94769 56.56389 -0.4285 15.64452
Minimum of Months 672.00000 21.78162 55.07692 -1.0443 5.91162
Maximum of Months 744.00000 22.24889 60.80594 0.08601 29.42374



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64071 57.41291 -0.1029 6.26690
February 672.00000 21.66728 56.43089 -0.0763 6.26219
March 744.00000 21.66701 55.91256 -0.0609 6.17928
April 720.00000 21.72335 56.39948 -0.0085 6.02104
May 744.00000 21.73831 56.15345 -1.0599 30.38571
June 720.00000 21.74066 56.05163 -1.0465 29.76668
July 744.00000 21.74485 55.46716 -1.0275 29.06684
August 744.00000 21.74123 56.27189 -1.0396 29.54040
September 720.00000 21.74094 55.89896 -1.0391 29.58889
October 744.00000 21.73828 56.13264 0.01268 5.98681
November 720.00000 21.70606 56.84542 -0.0332 6.07790
December 744.00000 21.64452 59.04263 -0.0773 6.16929
           
Annual Sum or Average 8760.00000 21.70788 56.50444 -0.4657 16.00118
Minimum of Months 672.00000 21.64071 55.46716 -1.0599 5.98681
Maximum of Months 744.00000 21.74485 59.04263 0.01268 30.38571



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.91835 59.69650 -0.0670 6.46532
February 672.00000 22.13515 57.88734 0.00585 6.73020
March 744.00000 22.21038 56.51617 0.04378 6.88076
April 720.00000 22.22622 56.78565 0.09637 6.69361
May 744.00000 21.85560 56.29114 -1.0228 28.98862
June 720.00000 21.79484 55.96310 -1.0261 29.03371
July 744.00000 21.82684 55.48820 -0.9995 28.15138
August 744.00000 21.77469 56.48827 -1.0331 29.26544
September 720.00000 21.81208 56.54415 -1.0307 29.22217
October 744.00000 21.81815 57.71197 0.01675 5.95171
November 720.00000 21.90563 58.93793 -0.0056 6.12049
December 744.00000 21.91969 61.47072 -0.0377 6.48317
           
Annual Sum or Average 8760.00000 21.93146 57.48308 -0.4244 15.88582
Minimum of Months 672.00000 21.77469 55.48820 -1.0331 5.95171
Maximum of Months 744.00000 22.22622 61.47072 0.09637 29.26544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.70694 54.74170 -0.0668 6.25273
February 672.00000 21.71672 55.02412 -0.0593 6.20639
March 744.00000 21.70528 55.21216 -0.0687 6.10489
April 720.00000 21.72504 56.39557 -0.0467 5.96838
May 744.00000 21.73597 56.36210 -1.1248 33.04329
June 720.00000 21.73926 56.23761 -1.1075 32.24398
July 744.00000 21.74348 55.82480 -1.0960 31.80160
August 744.00000 21.74163 56.12119 -1.0988 31.94219
September 720.00000 21.74908 55.74888 -1.0727 30.99043
October 744.00000 21.75465 55.77498 0.00687 6.05234
November 720.00000 21.73934 55.44522 -0.0209 6.12688
December 744.00000 21.70709 56.64381 -0.0488 6.17389
           
Annual Sum or Average 8760.00000 21.73040 55.79890 -0.4863 16.97580
Minimum of Months 672.00000 21.70528 54.74170 -1.1248 5.96838
Maximum of Months 744.00000 21.75465 56.64381 0.00687 33.04329



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.86060 56.51775 0.27924 7.69304
February 672.00000 23.03714 56.32641 0.33619 8.38203
March 744.00000 23.16523 56.65533 0.38206 9.12984
April 720.00000 23.47168 58.51834 0.49720 10.63094
May 744.00000 23.65901 58.14543 -0.2973 7.30641
June 720.00000 23.75816 57.71143 -0.2406 6.52641
July 744.00000 23.81601 57.48132 -0.2132 6.16446
August 744.00000 23.70684 58.00477 -0.2675 6.94168
September 720.00000 23.71973 57.83055 -0.2638 6.85767
October 744.00000 23.59245 58.40920 0.54308 11.48886
November 720.00000 23.30647 58.25589 0.44171 9.82696
December 744.00000 22.98752 58.29539 0.33240 8.35685
           
Annual Sum or Average 8760.00000 23.42504 57.68606 0.12594 8.27252
Minimum of Months 672.00000 22.86060 56.32641 -0.2973 6.16446
Maximum of Months 744.00000 23.81601 58.51834 0.54308 11.48886



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.04773 55.52167 0.35249 8.54941
February 672.00000 23.20428 55.35187 0.40451 9.31244
March 744.00000 23.31394 55.69904 0.44614 10.10056
April 720.00000 23.58016 57.63984 0.55037 11.70318
May 744.00000 23.73346 57.39165 -0.2343 6.48199
June 720.00000 23.81105 57.05889 -0.1872 5.96680
July 744.00000 23.85849 56.87587 -0.1643 5.72709
August 744.00000 23.76494 57.33153 -0.2126 6.28665
September 720.00000 23.77330 57.18037 -0.2113 6.24539
October 744.00000 23.66416 57.68115 0.58448 12.41037
November 720.00000 23.42571 57.38404 0.49668 10.78230
December 744.00000 23.15167 57.32205 0.39955 9.25855
           
Annual Sum or Average 8760.00000 23.52875 56.87742 0.18383 8.56146
Minimum of Months 672.00000 23.04773 55.35187 -0.2343 5.72709
Maximum of Months 744.00000 23.85849 57.68115 0.58448 12.41037



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.37927 53.91737 1.03836 31.93241
February 672.00000 23.40166 54.01427 1.06211 32.90711
March 744.00000 23.44548 54.52044 1.09443 33.98455
April 720.00000 23.51629 56.77295 1.16829 36.82559
May 744.00000 23.58267 56.84152 0.63075 20.31002
June 720.00000 23.64325 56.60523 0.68511 21.08578
July 744.00000 23.64551 56.51486 0.70512 21.86185
August 744.00000 23.62432 56.77486 0.66176 20.62592
September 720.00000 23.63300 56.55069 0.67539 20.97092
October 744.00000 23.57841 56.83973 1.20474 38.05687
November 720.00000 23.48680 56.21952 1.13386 35.43057
December 744.00000 23.40530 55.79556 1.06363 32.76988
           
Annual Sum or Average 8760.00000 23.52909 55.95667 0.92598 28.86732
Minimum of Months 672.00000 23.37927 53.91737 0.63075 20.31002
Maximum of Months 744.00000 23.64551 56.84152 1.20474 38.05687



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.24233 52.88370 -0.2376 6.48729
February 672.00000 21.37343 52.84192 -0.2006 6.17851
March 744.00000 21.49614 53.51570 -0.1647 6.00058
April 720.00000 21.99236 55.37973 -0.0206 5.21947
May 744.00000 22.65242 54.63888 -0.8774 21.57969
June 720.00000 23.17393 53.66436 -0.6975 15.40569
July 744.00000 23.41725 52.93894 -0.6149 13.06184
August 744.00000 23.09208 54.06453 -0.7236 16.39785
September 720.00000 23.20071 53.42245 -0.6867 15.13191
October 744.00000 22.77622 54.29043 0.17721 5.71563
November 720.00000 22.11201 54.49946 0.00675 5.45404
December 744.00000 21.52159 54.67420 -0.1518 6.00519
           
Annual Sum or Average 8760.00000 22.34237 53.90617 -0.3505 10.25212
Minimum of Months 672.00000 21.24233 52.84192 -0.8774 5.21947
Maximum of Months 744.00000 23.41725 55.37973 0.17721 21.57969



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64769 54.73640 -0.1523 5.88415
February 672.00000 21.78080 54.72789 -0.1194 5.63604
March 744.00000 21.90054 55.29742 -0.0844 5.56147
April 720.00000 22.39432 57.09180 0.05200 5.18793
May 744.00000 22.65808 57.23243 -0.9192 23.00817
June 720.00000 22.98700 56.64476 -0.8063 18.79222
July 744.00000 23.15514 56.15054 -0.7495 16.90118
August 744.00000 23.00041 56.69105 -0.8010 18.73011
September 720.00000 23.10954 56.13435 -0.7646 17.48353
October 744.00000 22.94493 56.34694 0.19028 5.78934
November 720.00000 22.39577 56.40338 0.04955 5.32888
December 744.00000 21.80388 56.79210 -0.1007 5.74913
           
Annual Sum or Average 8760.00000 22.48464 56.19524 -0.3522 11.21073
Minimum of Months 672.00000 21.64769 54.72789 -0.9192 5.18793
Maximum of Months 744.00000 23.15514 57.23243 0.19028 23.00817



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.46153 53.01507 -0.1675 6.12479
February 672.00000 21.66169 52.77315 -0.1128 5.83285
March 744.00000 21.82283 53.15321 -0.0661 5.80728
April 720.00000 22.35456 54.82239 0.08690 5.63630
May 744.00000 22.86504 54.14713 -0.7754 18.28343
June 720.00000 23.27869 53.22822 -0.6307 13.81431
July 744.00000 23.46596 52.66074 -0.5649 12.12493
August 744.00000 23.19759 53.55055 -0.6584 14.84907
September 720.00000 23.31167 52.98159 -0.6189 13.71391
October 744.00000 22.98486 53.74677 0.24618 6.53253
November 720.00000 22.27896 54.31576 0.06249 5.86154
December 744.00000 21.69464 54.75836 -0.0955 5.97776
           
Annual Sum or Average 8760.00000 22.53564 53.60020 -0.2759 9.57478
Minimum of Months 672.00000 21.46153 52.66074 -0.7754 5.63630
Maximum of Months 744.00000 23.46596 54.82239 0.24618 18.28343



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.25283 52.49688 -0.2338 6.46928
February 672.00000 21.39433 52.41755 -0.1934 6.15865
March 744.00000 21.52945 53.03714 -0.1543 5.97992
April 720.00000 22.04910 54.80812 -0.0034 5.24549
May 744.00000 22.75161 53.89007 -0.8374 20.21024
June 720.00000 23.29597 52.80898 -0.6490 14.07918
July 744.00000 23.52631 52.10231 -0.5693 11.95430
August 744.00000 23.17787 53.31254 -0.6874 15.39163
September 720.00000 23.29373 52.66499 -0.6480 14.09022
October 744.00000 22.83035 53.67744 0.19404 5.87163
November 720.00000 22.14471 53.98543 0.01791 5.50375
December 744.00000 21.54167 54.23625 -0.1452 6.00037
           
Annual Sum or Average 8760.00000 22.40400 53.29054 -0.3269 9.77589
Minimum of Months 672.00000 21.25283 52.10231 -0.8374 5.24549
Maximum of Months 744.00000 23.52631 54.80812 0.19404 20.21024



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.187334E+12 155469.87 07-JAN-09:53 740.00 0.599178E+12 0.00 0.786513E+12 3.10 4.03 02-JAN-22:53 0.00 0.00
February 0.193669E+12 175730.41 11-FEB-16:03 663.83 0.613589E+12 0.00 0.807258E+12 3.07 3.99 12-FEB-16:03 0.00 0.00
March 0.231484E+12 172318.55 09-MAR-22:52 741.00 0.749535E+12 0.00 0.981018E+12 3.15 4.01 19-MAR-08:54 0.00 0.00
April 0.276149E+12 185610.67 14-APR-15:03 720.00 0.892872E+12 0.00 0.116902E+13 3.20 3.98 26-APR-21:53 0.00 0.00
May 0.346107E+12 196869.75 29-MAY-18:03 744.00 0.114224E+13 0.00 0.148834E+13 3.30 4.04 10-MAY-15:03 0.00 0.00
June 0.375623E+12 209173.38 08-JUN-18:03 720.00 0.124271E+13 0.00 0.161834E+13 3.31 3.86 21-JUN-18:03 0.00 0.00
July 0.400755E+12 219483.50 28-JUL-15:03 744.00 0.131814E+13 0.00 0.171890E+13 3.30 4.04 14-JUL-21:52 0.00 0.00
August 0.396075E+12 204589.43 23-AUG-15:03 744.00 0.130545E+13 0.00 0.170153E+13 3.30 4.07 12-AUG-08:53 0.00 0.00
September 0.373487E+12 207103.00 18-SEP-15:05 720.00 0.123793E+13 0.00 0.161142E+13 3.32 4.03 04-SEP-21:52 0.00 0.00
October 0.354570E+12 201805.78 03-OCT-15:03 744.00 0.118335E+13 0.00 0.153792E+13 3.33 3.90 01-OCT-08:03 0.00 0.00
November 0.284884E+12 181201.98 30-NOV-16:03 720.00 0.955012E+12 0.00 0.123990E+13 3.30 4.04 24-NOV-09:54 0.00 0.00
December 0.219937E+12 185169.84 25-DEC-22:52 744.00 0.724915E+12 0.00 0.944853E+12 3.19 4.11 24-DEC-22:53 0.00 0.00
                         
Annual Sum or Average 0.364007E+13     8744.83 0.119649E+14 0.00 0.156050E+14 3.24     0.00 0.00
Minimum of Months 0.187334E+12 155469.87   663.83 0.599178E+12 0.00 0.786513E+12 3.07 3.86   0.00 0.00
Maximum of Months 0.400755E+12 219483.50   744.00 0.131814E+13 0.00 0.171890E+13 3.33 4.11   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.710989E+10 0.00 559.13 42367.28 31-JAN-16:04 0.00 27.63 51.70 0.02 0.00 0.01 0.18 31-JAN-16:04
February 0.561302E+10 0.00 453.01 49677.34 04-FEB-09:05 0.00 27.83 49.26 0.02 0.00 0.01 0.21 04-FEB-09:05
March 0.554513E+10 0.00 453.83 48940.86 20-MAR-08:05 0.00 28.28 47.67 0.02 0.00 0.01 0.20 20-MAR-08:05
April 0.204987E+10 0.00 263.06 24611.74 02-APR-15:07 0.00 29.41 40.81 0.01 0.00 0.00 0.10 02-APR-15:07
May 0.171984E+10 0.00 211.89 24138.10 21-MAY-18:07 0.00 29.01 38.02 0.00 0.00 0.00 0.10 21-MAY-18:07
June 0.127884E+10 0.00 155.89 18328.82 24-JUN-18:07 0.00 28.70 35.59 0.00 0.00 0.00 0.08 24-JUN-18:07
July 0.111487E+10 0.00 143.03 18014.85 17-JUL-18:07 0.00 28.25 34.45 0.00 0.00 0.00 0.07 17-JUL-18:07
August 0.156175E+10 0.00 201.31 25872.20 06-AUG-18:07 0.00 28.29 37.02 0.00 0.00 0.00 0.11 06-AUG-18:07
September 0.126218E+10 0.00 159.77 25450.39 04-SEP-18:07 0.00 28.64 35.72 0.00 0.00 0.00 0.11 04-SEP-18:07
October 0.170560E+10 0.00 212.03 24400.68 15-OCT-15:07 0.00 29.39 38.32 0.00 0.00 0.00 0.10 15-OCT-15:07
November 0.293849E+10 0.00 321.18 34155.65 27-NOV-09:05 0.00 29.12 43.01 0.01 0.00 0.00 0.14 27-NOV-09:05
December 0.687865E+10 0.00 495.36 49068.47 28-DEC-16:04 0.00 28.02 49.21 0.02 0.00 0.01 0.20 28-DEC-16:04
                           
Annual Sum or Average 0.387781E+11 0.00 3629.50     0.00 28.55 41.70 0.01 0.00 0.01    
Minimum of Months 0.111487E+10 0.00 143.03 18014.85   0.00 27.63 34.45 0.00 0.00 0.00 0.07  
Maximum of Months 0.710989E+10 0.00 559.13 49677.34   0.00 29.41 51.70 0.02 0.00 0.01 0.21  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.462607E+12 0.00 721.33 0.282820E+12 0.00 0.00 0.00 0.00 413594.41 07-JAN-04:00 199721.34 02-JAN-14:00 0.00 0.00 0.00
February 0.474154E+12 0.00 635.17 0.302561E+12 0.00 0.00 0.00 0.00 447930.10 11-FEB-20:20 204668.22 11-FEB-14:00 0.00 0.00 0.00
March 0.583137E+12 0.00 719.83 0.361303E+12 0.00 0.00 0.00 0.00 496798.51 09-MAR-21:50 215900.67 13-MAR-18:10 0.00 0.00 0.00
April 0.695680E+12 0.00 720.00 0.428198E+12 0.00 0.00 0.00 0.00 417612.81 25-APR-21:52 237130.52 17-APR-18:07 0.00 0.00 0.00
May 0.896390E+12 0.00 744.00 0.499604E+12 0.00 0.00 0.00 0.00 494624.20 24-MAY-18:10 245638.02 22-MAY-18:05 0.00 0.00 0.00
June 0.977346E+12 0.00 720.00 0.512561E+12 0.00 0.00 0.00 0.00 491835.16 06-JUN-19:10 253513.07 29-JUN-19:10 0.00 0.00 0.00
July 0.103375E+13 0.00 744.00 0.543261E+12 0.00 0.00 0.00 0.00 508302.20 02-JUL-19:30 267403.06 28-JUL-18:07 0.00 0.00 0.00
August 0.102962E+13 0.00 744.00 0.533814E+12 0.00 0.00 0.00 0.00 470784.07 05-AUG-18:15 252713.95 02-AUG-21:00 0.00 0.00 0.00
September 0.966218E+12 0.00 720.00 0.513181E+12 0.00 0.00 0.00 0.00 515510.10 02-SEP-21:50 256112.47 08-SEP-20:10 0.00 0.00 0.00
October 0.921917E+12 0.00 744.00 0.503529E+12 0.00 0.00 0.00 0.00 470031.43 01-OCT-06:47 235374.87 03-OCT-21:00 0.00 0.00 0.00
November 0.748657E+12 0.00 711.83 0.408585E+12 0.00 0.00 0.00 0.00 523811.02 21-NOV-20:25 223119.59 03-NOV-21:00 0.00 0.00 0.00
December 0.568295E+12 0.00 693.33 0.318296E+12 0.00 0.00 0.00 0.00 540985.32 25-DEC-22:00 202489.10 08-DEC-21:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.935776E+13 0.00 8617.50 0.520771E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.462607E+12 0.00 635.17 0.282820E+12 0.00 0.00 0.00 0.00 413594.41   199721.34   0.00 0.00 0.00
Maximum of Months 0.103375E+13 0.00 744.00 0.543261E+12 0.00 0.00 0.00 0.00 540985.32   267403.06   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.301691E+11 0.00 484.17 0.179484E+11 0.00 0.00 0.00 0.00 43623.15 07-JAN-09:01 18794.29 07-JAN-13:20 0.00 0.00 0.00
February 0.327933E+11 0.00 473.67 0.205798E+11 0.00 0.00 0.00 0.00 41142.31 11-FEB-19:02 19176.33 11-FEB-14:00 0.00 0.00 0.00
March 0.396844E+11 0.00 526.50 0.252332E+11 0.00 0.00 0.00 0.00 45083.14 14-MAR-08:61 19303.28 13-MAR-15:02 0.00 0.00 0.00
April 0.466409E+11 0.00 568.83 0.302448E+11 0.00 0.00 0.00 0.00 41272.91 25-APR-05:50 20307.02 17-APR-15:02 0.00 0.00 0.00
May 0.570018E+11 0.00 589.00 0.335535E+11 0.00 0.00 0.00 0.00 48557.43 28-MAY-18:03 21219.14 22-MAY-13:00 0.00 0.00 0.00
June 0.615163E+11 0.00 570.00 0.336005E+11 0.00 0.00 0.00 0.00 43550.80 18-JUN-20:40 20375.92 11-JUN-13:00 0.00 0.00 0.00
July 0.640607E+11 0.00 589.00 0.349295E+11 0.00 0.00 0.00 0.00 46761.66 02-JUL-17:00 21651.46 28-JUL-15:02 0.00 0.00 0.00
August 0.650703E+11 0.00 589.00 0.348901E+11 0.00 0.00 0.00 0.00 45991.92 12-AUG-08:03 21052.71 23-AUG-13:00 0.00 0.00 0.00
September 0.612178E+11 0.00 570.00 0.334368E+11 0.00 0.00 0.00 0.00 44301.83 04-SEP-21:51 20504.86 08-SEP-15:02 0.00 0.00 0.00
October 0.586650E+11 0.00 589.00 0.335288E+11 0.00 0.00 0.00 0.00 45227.74 01-OCT-08:20 20372.11 03-OCT-15:02 0.00 0.00 0.00
November 0.492529E+11 0.00 546.00 0.278917E+11 0.00 0.00 0.00 0.00 47107.67 08-NOV-09:03 19305.14 17-NOV-16:02 0.00 0.00 0.00
December 0.380834E+11 0.00 510.50 0.213310E+11 0.00 0.00 0.00 0.00 49518.84 23-DEC-19:03 18963.72 10-DEC-13:20 0.00 0.00 0.00
                               
Annual Sum or Average 0.604156E+12 0.00 6605.67 0.347168E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.301691E+11 0.00 473.67 0.179484E+11 0.00 0.00 0.00 0.00 41142.31   18794.29   0.00 0.00 0.00
Maximum of Months 0.650703E+11 0.00 589.00 0.349295E+11 0.00 0.00 0.00 0.00 49518.84   21651.46   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.494700E+10 0.00 603.32 0.218606E+10 0.00 0.00 0.00 0.00 17580.07 07-JAN-09:01 14161.79 25-JAN-16:01 0.00 0.00 0.00
February 0.573341E+10 0.00 574.32 0.277229E+10 0.00 0.00 0.00 0.00 17157.23 02-FEB-09:01 14165.59 03-FEB-16:01 0.00 0.00 0.00
March 0.738333E+10 0.00 638.05 0.382096E+10 0.00 0.00 0.00 0.00 17702.66 19-MAR-08:62 14163.30 15-MAR-15:01 0.00 0.00 0.00
April 0.917336E+10 0.00 671.54 0.507204E+10 0.00 0.00 0.00 0.00 15959.44 29-APR-08:61 13051.91 20-APR-15:02 0.00 0.00 0.00
May 0.107645E+11 0.00 709.74 0.609235E+10 0.00 0.00 0.00 0.00 16387.33 24-MAY-18:02 13096.15 12-MAY-18:02 0.00 0.00 0.00
June 0.112084E+11 0.00 689.96 0.642767E+10 0.00 0.00 0.00 0.00 15417.13 13-JUN-08:61 13046.38 27-JUN-15:02 0.00 0.00 0.00
July 0.125394E+11 0.00 716.40 0.747038E+10 0.00 0.00 0.00 0.00 14729.39 24-JUL-08:61 13025.65 06-JUL-15:02 0.00 0.00 0.00
August 0.119747E+11 0.00 712.56 0.699379E+10 0.00 0.00 0.00 0.00 17181.91 12-AUG-08:61 13117.14 08-AUG-15:02 0.00 0.00 0.00
September 0.116796E+11 0.00 691.48 0.683326E+10 0.00 0.00 0.00 0.00 15656.95 05-SEP-08:61 13110.03 09-SEP-18:02 0.00 0.00 0.00
October 0.111391E+11 0.00 712.85 0.637677E+10 0.00 0.00 0.00 0.00 16389.60 31-OCT-08:61 13162.24 03-OCT-18:02 0.00 0.00 0.00
November 0.816991E+10 0.00 656.32 0.417887E+10 0.00 0.00 0.00 0.00 16928.16 24-NOV-09:01 13041.45 20-NOV-19:02 0.00 0.00 0.00
December 0.595091E+10 0.00 614.40 0.281439E+10 0.00 0.00 0.00 0.00 17833.19 23-DEC-09:01 13543.64 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.110664E+12 0.00 7990.93 0.610388E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.494700E+10 0.00 574.32 0.218606E+10 0.00 0.00 0.00 0.00 14729.39   13025.65   0.00 0.00 0.00
Maximum of Months 0.125394E+11 0.00 716.40 0.747038E+10 0.00 0.00 0.00 0.00 17833.19   14165.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.219749E+10 0.00 337.05 0.813995E+09 0.00 0.00 0.00 0.00 17762.11 07-JAN-09:52 13699.05 25-JAN-16:01 0.00 0.00 0.00
February 0.315860E+10 0.00 351.29 0.142101E+10 0.00 0.00 0.00 0.00 17581.21 17-FEB-09:21 13960.56 03-FEB-16:01 0.00 0.00 0.00
March 0.494762E+10 0.00 432.90 0.245024E+10 0.00 0.00 0.00 0.00 18848.89 14-MAR-08:21 14314.81 15-MAR-15:01 0.00 0.00 0.00
April 0.746716E+10 0.00 520.58 0.417434E+10 0.00 0.00 0.00 0.00 17823.81 22-APR-08:21 13298.10 18-APR-21:51 0.00 0.00 0.00
May 0.104570E+11 0.00 670.19 0.600172E+10 0.00 0.00 0.00 0.00 17857.86 25-MAY-21:51 13236.95 12-MAY-18:02 0.00 0.00 0.00
June 0.112611E+11 0.00 676.26 0.652069E+10 0.00 0.00 0.00 0.00 18197.99 18-JUN-21:51 13860.07 13-JUN-18:11 0.00 0.00 0.00
July 0.124484E+11 0.00 697.38 0.748099E+10 0.00 0.00 0.00 0.00 17534.97 14-JUL-21:51 13901.10 05-JUL-17:52 0.00 0.00 0.00
August 0.116578E+11 0.00 698.96 0.673464E+10 0.00 0.00 0.00 0.00 17880.64 12-AUG-08:52 14093.91 23-AUG-17:52 0.00 0.00 0.00
September 0.107620E+11 0.00 662.72 0.610627E+10 0.00 0.00 0.00 0.00 17537.60 16-SEP-08:61 13244.20 30-SEP-18:02 0.00 0.00 0.00
October 0.949626E+10 0.00 663.20 0.508706E+10 0.00 0.00 0.00 0.00 17749.78 21-OCT-08:61 13288.31 14-OCT-18:02 0.00 0.00 0.00
November 0.600993E+10 0.00 524.86 0.282403E+10 0.00 0.00 0.00 0.00 17443.02 22-NOV-09:01 13204.85 01-NOV-18:02 0.00 0.00 0.00
December 0.326682E+10 0.00 358.89 0.142017E+10 0.00 0.00 0.00 0.00 18230.43 10-DEC-09:01 13240.70 09-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.931302E+11 0.00 6594.28 0.510352E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.219749E+10 0.00 337.05 0.813995E+09 0.00 0.00 0.00 0.00 17443.02   13204.85   0.00 0.00 0.00
Maximum of Months 0.124484E+11 0.00 698.96 0.748099E+10 0.00 0.00 0.00 0.00 18848.89   14314.81   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.421054E+11 0.00 694.83 0.235562E+11 0.00 0.00 0.00 0.00 45419.22 01-JAN-09:51 38829.14 02-JAN-11:50 0.00 0.00 0.00
February 0.375442E+11 0.00 638.12 0.193836E+11 0.00 0.00 0.00 0.00 42458.06 11-FEB-14:30 36858.06 11-FEB-14:30 0.00 0.00 0.00
March 0.377728E+11 0.00 692.08 0.167522E+11 0.00 0.00 0.00 0.00 33492.64 04-MAR-11:35 24538.70 02-MAR-14:30 0.00 0.00 0.00
April 0.393916E+11 0.00 707.20 0.161006E+11 0.00 0.00 0.00 0.00 30007.33 14-APR-16:10 18539.86 15-APR-17:20 0.00 0.00 0.00
May 0.451575E+11 0.00 738.56 0.179517E+11 0.00 0.00 0.00 0.00 30753.41 14-MAY-08:00 17339.50 22-MAY-20:20 0.00 0.00 0.00
June 0.494402E+11 0.00 716.97 0.206199E+11 0.00 0.00 0.00 0.00 31055.07 08-JUN-07:00 18999.02 03-JUN-21:00 0.00 0.00 0.00
July 0.547934E+11 0.00 742.67 0.244044E+11 0.00 0.00 0.00 0.00 32985.07 01-JUL-08:00 22399.40 29-JUL-19:10 0.00 0.00 0.00
August 0.546061E+11 0.00 741.86 0.243724E+11 0.00 0.00 0.00 0.00 33925.09 20-AUG-08:00 21377.04 20-AUG-20:10 0.00 0.00 0.00
September 0.605226E+11 0.00 720.00 0.313493E+11 0.00 0.00 0.00 0.00 41745.46 30-SEP-15:02 33900.33 30-SEP-13:50 0.00 0.00 0.00
October 0.643087E+11 0.00 743.67 0.359862E+11 0.00 0.00 0.00 0.00 45929.28 25-OCT-15:40 39496.51 25-OCT-12:00 0.00 0.00 0.00
November 0.536952E+11 0.00 704.55 0.291863E+11 0.00 0.00 0.00 0.00 47701.69 10-NOV-14:50 39668.82 08-NOV-11:03 0.00 0.00 0.00
December 0.451265E+11 0.00 699.16 0.239780E+11 0.00 0.00 0.00 0.00 46115.87 09-DEC-09:00 39993.36 14-DEC-13:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.584464E+12 0.00 8539.65 0.283641E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.375442E+11 0.00 638.12 0.161006E+11 0.00 0.00 0.00 0.00 30007.33   17339.50   0.00 0.00 0.00
Maximum of Months 0.643087E+11 0.00 743.67 0.359862E+11 0.00 0.00 0.00 0.00 47701.69   39993.36   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.276543E+11 0.00 352.33 0.139493E+11 0.00 0.00 0.00 0.00 116491.33 07-JAN-09:52 89336.54 24-JAN-19:01 0.00 0.00 0.00
February 0.303399E+11 0.00 328.66 0.167251E+11 0.00 0.00 0.00 0.00 114969.36 17-FEB-09:21 90244.26 03-FEB-19:02 0.00 0.00 0.00
March 0.410519E+11 0.00 410.03 0.231075E+11 0.00 0.00 0.00 0.00 124607.93 14-MAR-08:21 89827.24 15-MAR-20:12 0.00 0.00 0.00
April 0.530690E+11 0.00 466.20 0.314154E+11 0.00 0.00 0.00 0.00 115863.69 22-APR-08:21 87479.92 15-APR-18:02 0.00 0.00 0.00
May 0.731310E+11 0.00 615.19 0.445771E+11 0.00 0.00 0.00 0.00 118158.34 25-MAY-21:51 87435.33 19-MAY-18:02 0.00 0.00 0.00
June 0.794483E+11 0.00 625.12 0.503353E+11 0.00 0.00 0.00 0.00 119092.22 18-JUN-21:51 87567.56 01-JUN-18:02 0.00 0.00 0.00
July 0.837224E+11 0.00 646.59 0.536294E+11 0.00 0.00 0.00 0.00 112686.61 14-JUL-21:51 87514.00 27-JUL-18:02 0.00 0.00 0.00
August 0.783113E+11 0.00 638.65 0.481709E+11 0.00 0.00 0.00 0.00 116344.81 12-AUG-08:52 87519.98 21-AUG-08:62 0.00 0.00 0.00
September 0.733621E+11 0.00 606.98 0.444910E+11 0.00 0.00 0.00 0.00 119365.31 16-SEP-07:52 87164.79 01-SEP-08:61 0.00 0.00 0.00
October 0.656572E+11 0.00 590.75 0.377766E+11 0.00 0.00 0.00 0.00 114079.96 31-OCT-08:31 87647.49 31-OCT-18:02 0.00 0.00 0.00
November 0.484736E+11 0.00 471.24 0.270846E+11 0.00 0.00 0.00 0.00 114831.88 22-NOV-09:01 87461.75 02-NOV-18:02 0.00 0.00 0.00
December 0.323085E+11 0.00 379.72 0.168861E+11 0.00 0.00 0.00 0.00 117256.26 10-DEC-09:01 88852.41 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.686529E+12 0.00 6131.46 0.408148E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.276543E+11 0.00 328.66 0.139493E+11 0.00 0.00 0.00 0.00 112686.61   87164.79   0.00 0.00 0.00
Maximum of Months 0.837224E+11 0.00 646.59 0.536294E+11 0.00 0.00 0.00 0.00 124607.93   90244.26   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.522019E+10 0.00 621.54 0.247582E+10 0.00 0.00 0.00 0.00 15552.33 07-JAN-09:01 12734.28 25-JAN-16:01 0.00 0.00 0.00
February 0.576966E+10 0.00 586.04 0.286237E+10 0.00 0.00 0.00 0.00 15110.73 18-FEB-09:01 12434.03 03-FEB-16:01 0.00 0.00 0.00
March 0.726271E+10 0.00 668.97 0.377124E+10 0.00 0.00 0.00 0.00 15964.09 19-MAR-08:62 12737.31 15-MAR-15:01 0.00 0.00 0.00
April 0.912394E+10 0.00 692.63 0.503180E+10 0.00 0.00 0.00 0.00 14322.12 29-APR-08:61 11749.96 20-APR-18:01 0.00 0.00 0.00
May 0.107978E+11 0.00 721.20 0.616672E+10 0.00 0.00 0.00 0.00 14771.58 24-MAY-18:02 11801.89 07-MAY-15:02 0.00 0.00 0.00
June 0.117898E+11 0.00 702.01 0.701249E+10 0.00 0.00 0.00 0.00 12968.44 21-JUN-18:01 11781.43 11-JUN-18:02 0.00 0.00 0.00
July 0.128966E+11 0.00 726.71 0.795047E+10 0.00 0.00 0.00 0.00 13448.43 02-JUL-18:02 11796.70 23-JUL-18:02 0.00 0.00 0.00
August 0.119903E+11 0.00 720.56 0.712490E+10 0.00 0.00 0.00 0.00 15484.68 12-AUG-08:61 11718.81 14-AUG-15:02 0.00 0.00 0.00
September 0.120872E+11 0.00 700.90 0.732276E+10 0.00 0.00 0.00 0.00 13940.59 05-SEP-08:61 11816.86 09-SEP-18:02 0.00 0.00 0.00
October 0.112967E+11 0.00 722.74 0.659648E+10 0.00 0.00 0.00 0.00 14737.85 31-OCT-08:61 11823.96 25-OCT-18:02 0.00 0.00 0.00
November 0.824190E+10 0.00 667.23 0.437197E+10 0.00 0.00 0.00 0.00 15258.05 24-NOV-09:01 11753.21 21-NOV-09:01 0.00 0.00 0.00
December 0.556030E+10 0.00 607.72 0.264730E+10 0.00 0.00 0.00 0.00 16080.75 23-DEC-09:01 11964.51 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.112037E+12 0.00 8138.25 0.633343E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.522019E+10 0.00 586.04 0.247582E+10 0.00 0.00 0.00 0.00 12968.44   11718.81   0.00 0.00 0.00
Maximum of Months 0.128966E+11 0.00 726.71 0.795047E+10 0.00 0.00 0.00 0.00 16080.75   12737.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.245603E+10 0.00 342.57 0.102150E+10 0.00 0.00 0.00 0.00 16109.48 07-JAN-09:52 11768.18 08-JAN-16:01 0.00 0.00 0.00
February 0.312799E+10 0.00 369.60 0.142200E+10 0.00 0.00 0.00 0.00 16192.46 17-FEB-09:21 12431.55 28-FEB-09:51 0.00 0.00 0.00
March 0.486827E+10 0.00 456.40 0.243221E+10 0.00 0.00 0.00 0.00 16952.80 14-MAR-08:21 12650.50 15-MAR-15:01 0.00 0.00 0.00
April 0.739940E+10 0.00 533.12 0.409799E+10 0.00 0.00 0.00 0.00 16671.67 15-APR-08:31 12802.75 20-APR-08:51 0.00 0.00 0.00
May 0.104706E+11 0.00 679.55 0.604211E+10 0.00 0.00 0.00 0.00 16385.95 07-MAY-08:11 11897.75 29-MAY-18:02 0.00 0.00 0.00
June 0.118304E+11 0.00 687.07 0.711420E+10 0.00 0.00 0.00 0.00 17018.17 13-JUN-07:51 12388.84 22-JUN-07:52 0.00 0.00 0.00
July 0.127974E+11 0.00 706.16 0.796411E+10 0.00 0.00 0.00 0.00 15941.78 14-JUL-21:51 12292.17 05-JUL-17:52 0.00 0.00 0.00
August 0.116755E+11 0.00 707.32 0.685414E+10 0.00 0.00 0.00 0.00 16312.92 29-AUG-07:53 12420.97 23-AUG-17:52 0.00 0.00 0.00
September 0.111620E+11 0.00 671.97 0.649373E+10 0.00 0.00 0.00 0.00 16744.43 16-SEP-07:52 12479.09 17-SEP-07:52 0.00 0.00 0.00
October 0.964400E+10 0.00 671.22 0.531888E+10 0.00 0.00 0.00 0.00 16563.40 26-OCT-08:61 11871.46 05-OCT-15:02 0.00 0.00 0.00
November 0.601707E+10 0.00 535.95 0.299629E+10 0.00 0.00 0.00 0.00 17001.36 22-NOV-08:51 11737.33 19-NOV-19:02 0.00 0.00 0.00
December 0.297242E+10 0.00 345.75 0.131044E+10 0.00 0.00 0.00 0.00 16651.15 10-DEC-09:01 11768.14 26-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.944212E+11 0.00 6706.67 0.530676E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.245603E+10 0.00 342.57 0.102150E+10 0.00 0.00 0.00 0.00 15941.78   11737.33   0.00 0.00 0.00
Maximum of Months 0.127974E+11 0.00 707.32 0.796411E+10 0.00 0.00 0.00 0.00 17018.17   12802.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.124019E+10 0.00 541.09 0.575920E+09 0.00 0.00 0.00 0.00 5015.98 07-JAN-09:01 3891.13 25-JAN-16:01 0.00 0.00 0.00
February 0.148909E+10 0.00 548.53 0.750900E+09 0.00 0.00 0.00 0.00 4843.54 02-FEB-09:01 3892.23 03-FEB-16:01 0.00 0.00 0.00
March 0.193542E+10 0.00 615.92 0.101410E+10 0.00 0.00 0.00 0.00 5024.59 19-MAR-08:62 3891.70 15-MAR-15:01 0.00 0.00 0.00
April 0.238979E+10 0.00 677.46 0.132368E+10 0.00 0.00 0.00 0.00 4566.43 16-APR-08:61 3556.90 06-APR-15:02 0.00 0.00 0.00
May 0.283122E+10 0.00 711.44 0.158099E+10 0.00 0.00 0.00 0.00 4589.88 24-MAY-18:02 3605.73 28-MAY-15:02 0.00 0.00 0.00
June 0.293033E+10 0.00 690.68 0.163879E+10 0.00 0.00 0.00 0.00 4446.10 13-JUN-08:61 3594.85 04-JUN-15:02 0.00 0.00 0.00
July 0.327571E+10 0.00 717.89 0.192753E+10 0.00 0.00 0.00 0.00 4221.48 24-JUL-08:61 3599.26 30-JUL-18:02 0.00 0.00 0.00
August 0.311334E+10 0.00 712.15 0.177767E+10 0.00 0.00 0.00 0.00 4985.73 12-AUG-08:61 3591.78 06-AUG-18:02 0.00 0.00 0.00
September 0.300621E+10 0.00 690.58 0.172137E+10 0.00 0.00 0.00 0.00 4553.39 05-SEP-08:61 3592.76 15-SEP-18:02 0.00 0.00 0.00
October 0.282335E+10 0.00 711.14 0.158332E+10 0.00 0.00 0.00 0.00 4761.68 31-OCT-08:61 3584.87 02-OCT-18:02 0.00 0.00 0.00
November 0.206081E+10 0.00 641.26 0.104274E+10 0.00 0.00 0.00 0.00 4848.23 24-NOV-09:01 3599.34 02-NOV-18:02 0.00 0.00 0.00
December 0.151131E+10 0.00 562.30 0.731096E+09 0.00 0.00 0.00 0.00 5098.08 23-DEC-09:01 3695.17 20-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.286068E+11 0.00 7820.42 0.156681E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.124019E+10 0.00 541.09 0.575920E+09 0.00 0.00 0.00 0.00 4221.48   3556.90   0.00 0.00 0.00
Maximum of Months 0.327571E+10 0.00 717.89 0.192753E+10 0.00 0.00 0.00 0.00 5098.08   3892.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.543708E+09 0.00 296.59 0.210046E+09 0.00 0.00 0.00 0.00 5050.68 07-JAN-09:52 3815.03 25-JAN-16:01 0.00 0.00 0.00
February 0.837418E+09 0.00 335.72 0.390040E+09 0.00 0.00 0.00 0.00 5003.31 17-FEB-09:21 3843.51 03-FEB-16:01 0.00 0.00 0.00
March 0.132136E+10 0.00 420.95 0.660759E+09 0.00 0.00 0.00 0.00 5357.83 14-MAR-08:21 3928.10 15-MAR-15:01 0.00 0.00 0.00
April 0.198712E+10 0.00 526.14 0.111520E+10 0.00 0.00 0.00 0.00 5096.82 23-APR-07:52 3819.48 18-APR-21:51 0.00 0.00 0.00
May 0.276342E+10 0.00 672.75 0.157018E+10 0.00 0.00 0.00 0.00 5127.10 24-MAY-20:51 3671.10 10-MAY-16:31 0.00 0.00 0.00
June 0.294708E+10 0.00 677.34 0.166596E+10 0.00 0.00 0.00 0.00 5202.38 18-JUN-21:51 3893.91 13-JUN-18:11 0.00 0.00 0.00
July 0.325845E+10 0.00 698.91 0.193494E+10 0.00 0.00 0.00 0.00 5014.86 14-JUL-21:51 3898.61 05-JUL-17:52 0.00 0.00 0.00
August 0.303671E+10 0.00 699.26 0.171492E+10 0.00 0.00 0.00 0.00 5059.16 12-AUG-08:52 3942.87 23-AUG-17:52 0.00 0.00 0.00
September 0.278067E+10 0.00 662.03 0.153718E+10 0.00 0.00 0.00 0.00 5002.36 16-SEP-08:61 3639.47 15-SEP-18:02 0.00 0.00 0.00
October 0.241493E+10 0.00 663.95 0.124068E+10 0.00 0.00 0.00 0.00 5025.28 21-OCT-08:61 3627.21 03-OCT-18:02 0.00 0.00 0.00
November 0.152715E+10 0.00 517.01 0.695534E+09 0.00 0.00 0.00 0.00 4949.60 10-NOV-09:01 3625.34 06-NOV-19:02 0.00 0.00 0.00
December 0.842019E+09 0.00 333.23 0.365901E+09 0.00 0.00 0.00 0.00 5221.80 10-DEC-09:01 3566.29 26-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.242600E+11 0.00 6503.89 0.131013E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.543708E+09 0.00 296.59 0.210046E+09 0.00 0.00 0.00 0.00 4949.60   3566.29   0.00 0.00 0.00
Maximum of Months 0.325845E+10 0.00 699.26 0.193494E+10 0.00 0.00 0.00 0.00 5357.83   3942.87   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.111233E+11 0.00 657.65 0.693501E+10 0.00 0.00 0.00 0.00 20116.54 07-JAN-09:01 15790.81 25-JAN-16:01 0.00 0.00 0.00
February 0.106508E+11 0.00 601.88 0.643937E+10 0.00 0.00 0.00 0.00 19574.06 02-FEB-09:01 15655.45 03-FEB-19:02 0.00 0.00 0.00
March 0.112571E+11 0.00 657.68 0.653148E+10 0.00 0.00 0.00 0.00 20721.28 19-MAR-08:62 15792.33 15-MAR-15:01 0.00 0.00 0.00
April 0.118630E+11 0.00 673.10 0.675383E+10 0.00 0.00 0.00 0.00 18615.93 16-APR-08:61 14662.93 21-APR-18:02 0.00 0.00 0.00
May 0.134554E+11 0.00 707.03 0.767002E+10 0.00 0.00 0.00 0.00 19616.82 24-MAY-18:02 14635.75 07-MAY-15:02 0.00 0.00 0.00
June 0.142295E+11 0.00 687.84 0.842884E+10 0.00 0.00 0.00 0.00 17702.79 13-JUN-08:61 14619.45 28-JUN-18:02 0.00 0.00 0.00
July 0.155396E+11 0.00 713.54 0.954187E+10 0.00 0.00 0.00 0.00 17870.04 02-JUL-18:02 14617.87 27-JUL-18:02 0.00 0.00 0.00
August 0.153462E+11 0.00 709.20 0.943367E+10 0.00 0.00 0.00 0.00 20540.14 12-AUG-08:61 14637.89 29-AUG-18:02 0.00 0.00 0.00
September 0.163568E+11 0.00 692.30 0.104888E+11 0.00 0.00 0.00 0.00 18265.43 05-SEP-08:61 14652.38 09-SEP-18:02 0.00 0.00 0.00
October 0.169445E+11 0.00 717.34 0.109782E+11 0.00 0.00 0.00 0.00 19373.25 31-OCT-08:61 14654.96 03-OCT-15:02 0.00 0.00 0.00
November 0.141893E+11 0.00 675.02 0.893606E+10 0.00 0.00 0.00 0.00 20019.19 24-NOV-09:01 14667.97 07-NOV-19:02 0.00 0.00 0.00
December 0.120374E+11 0.00 659.19 0.736726E+10 0.00 0.00 0.00 0.00 20561.61 23-DEC-09:01 14528.16 09-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.162993E+12 0.00 8151.78 0.995044E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.106508E+11 0.00 601.88 0.643937E+10 0.00 0.00 0.00 0.00 17702.79   14528.16   0.00 0.00 0.00
Maximum of Months 0.169445E+11 0.00 717.34 0.109782E+11 0.00 0.00 0.00 0.00 20721.28   15792.33   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 555.54 361.23 194.31 887.11 205.25 0.00 0.00 0.00
February 490.42 278.92 211.50 827.30 170.62 0.00 0.00 0.00
March 379.01 156.70 222.31 655.94 136.30 0.00 0.00 0.00
April 271.75 55.67 216.09 528.84 83.41 0.00 0.00 0.00
May 212.18 6.74 205.44 458.90 29.33 0.00 0.00 0.00
June 200.14 0.42 199.72 461.22 7.76 0.00 0.00 0.00
July 214.16 1.80 212.36 500.70 20.34 0.00 0.00 0.00
August 240.75 18.00 222.75 544.44 7.70 0.00 0.00 0.00
September 312.20 77.13 235.07 682.61 27.32 0.00 0.00 0.00
October 433.29 206.02 227.26 833.26 47.83 0.00 0.00 0.00
November 490.86 275.48 215.37 854.67 99.79 0.00 0.00 0.00
December 535.60 338.19 197.42 870.76 179.21 0.00 0.00 0.00
                 
Annual Sum or Average 360.73 147.45 213.28 674.71 84.19 0.00 0.00 0.00
Minimum of Months 200.14 0.42 194.31 458.90 7.70 0.00 0.00 0.00
Maximum of Months 555.54 361.23 235.07 887.11 205.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1564.36 1017.20 547.16 2465.82 642.90 0.00 0.00 0.00
February 1380.98 785.42 595.57 2300.69 535.35 0.00 0.00 0.00
March 1067.25 441.25 626.01 1828.41 426.11 0.00 0.00 0.00
April 765.24 156.76 608.48 1484.59 259.14 0.00 0.00 0.00
May 597.48 18.97 578.52 1298.85 95.20 0.00 0.00 0.00
June 563.58 1.17 562.41 1314.07 33.62 0.00 0.00 0.00
July 603.05 5.06 597.99 1434.18 60.94 0.00 0.00 0.00
August 677.95 50.70 627.25 1542.14 30.76 0.00 0.00 0.00
September 879.14 217.19 661.95 1930.14 88.76 0.00 0.00 0.00
October 1220.12 580.15 639.96 2337.29 154.84 0.00 0.00 0.00
November 1382.22 775.75 606.47 2382.33 316.81 0.00 0.00 0.00
December 1508.22 952.31 555.91 2427.67 560.47 0.00 0.00 0.00
                 
Annual Sum or Average 1015.79 415.21 600.58 1893.48 265.88 0.00 0.00 0.00
Minimum of Months 563.58 1.17 547.16 1298.85 30.76 0.00 0.00 0.00
Maximum of Months 1564.36 1017.20 661.95 2465.82 642.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2032.19 1321.40 710.79 3334.59 791.10 0.00 0.00 0.00
February 1793.98 1020.30 773.67 3117.80 645.39 0.00 0.00 0.00
March 1386.42 573.21 813.22 2480.83 507.56 0.00 0.00 0.00
April 994.09 203.64 790.45 2015.25 300.16 0.00 0.00 0.00
May 776.16 24.64 751.52 1761.90 102.93 0.00 0.00 0.00
June 732.13 1.52 730.60 1781.85 37.02 0.00 0.00 0.00
July 783.39 6.58 776.82 1943.52 72.17 0.00 0.00 0.00
August 880.69 65.86 814.83 2095.95 31.52 0.00 0.00 0.00
September 1142.06 282.14 859.91 2629.64 104.41 0.00 0.00 0.00
October 1585.00 753.65 831.35 3167.76 165.95 0.00 0.00 0.00
November 1795.58 1007.74 787.84 3227.43 373.31 0.00 0.00 0.00
December 1959.26 1237.10 722.16 3271.47 683.48 0.00 0.00 0.00
                 
Annual Sum or Average 1319.57 539.38 780.19 2566.19 316.48 0.00 0.00 0.00
Minimum of Months 732.13 1.52 710.79 1761.90 31.52 0.00 0.00 0.00
Maximum of Months 2032.19 1321.40 859.91 3334.59 791.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 177.40 37.32 0.00 0.00 0.00
February 96.96 55.15 41.82 165.38 29.24 0.00 0.00 0.00
March 74.94 30.98 43.95 130.64 21.53 0.00 0.00 0.00
April 53.73 11.01 42.72 108.31 9.51 0.00 0.00 0.00
May 41.95 1.33 40.62 103.65 1.52 0.00 0.00 0.00
June 39.57 0.08 39.49 110.48 0.13 0.00 0.00 0.00
July 42.34 0.36 41.99 118.46 0.58 0.00 0.00 0.00
August 47.60 3.56 44.04 127.62 0.06 0.00 0.00 0.00
September 61.73 15.25 46.48 153.90 0.93 0.00 0.00 0.00
October 85.67 40.73 44.93 179.03 2.38 0.00 0.00 0.00
November 97.05 54.47 42.58 177.75 13.71 0.00 0.00 0.00
December 105.90 66.86 39.03 174.66 30.40 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 143.83 12.20 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 103.65 0.06 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 179.03 37.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 143.19 74.78 0.00 0.00 0.00
February 118.59 54.01 64.58 196.75 58.31 0.00 0.00 0.00
March 146.90 67.15 79.75 243.18 42.34 0.00 0.00 0.00
April 161.24 74.56 86.68 295.27 17.58 0.00 0.00 0.00
May 147.47 56.94 90.54 311.93 2.85 0.00 0.00 0.00
June 124.86 35.04 89.82 297.86 0.25 0.00 0.00 0.00
July 139.32 43.06 96.27 329.74 1.10 0.00 0.00 0.00
August 139.00 45.18 93.82 321.00 0.10 0.00 0.00 0.00
September 118.61 34.96 83.66 282.14 1.82 0.00 0.00 0.00
October 118.21 46.17 72.04 251.23 4.55 0.00 0.00 0.00
November 97.25 35.62 61.63 186.21 27.46 0.00 0.00 0.00
December 97.50 43.57 53.92 156.74 59.33 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 251.56 24.06 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 143.19 0.10 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 329.74 74.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 30.36 41.34 0.00 0.00 0.00
February 27.61 0.00 27.61 43.24 33.09 0.00 0.00 0.00
March 32.94 0.00 32.94 50.51 25.25 0.00 0.00 0.00
April 37.01 0.21 36.79 70.24 11.39 0.00 0.00 0.00
May 42.02 1.72 40.30 102.18 1.61 0.00 0.00 0.00
June 45.04 3.24 41.80 121.89 0.20 0.00 0.00 0.00
July 45.63 2.27 43.35 124.98 0.77 0.00 0.00 0.00
August 40.41 0.42 39.98 111.72 0.11 0.00 0.00 0.00
September 35.78 0.01 35.77 101.84 1.22 0.00 0.00 0.00
October 29.96 0.00 29.96 76.45 2.50 0.00 0.00 0.00
November 26.05 0.00 26.05 54.37 15.27 0.00 0.00 0.00
December 23.07 0.00 23.07 33.92 32.90 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 76.97 13.72 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 30.36 0.11 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 124.98 41.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 146.30 75.60 0.00 0.00 0.00
February 118.59 54.01 64.58 197.97 61.11 0.00 0.00 0.00
March 146.90 67.15 79.75 242.40 46.12 0.00 0.00 0.00
April 161.24 74.56 86.68 292.86 21.33 0.00 0.00 0.00
May 147.47 56.94 90.54 310.31 3.15 0.00 0.00 0.00
June 124.86 35.04 89.82 296.71 0.36 0.00 0.00 0.00
July 139.32 43.06 96.27 328.64 1.42 0.00 0.00 0.00
August 139.00 45.18 93.82 321.05 0.16 0.00 0.00 0.00
September 118.61 34.96 83.66 283.36 2.23 0.00 0.00 0.00
October 118.21 46.17 72.04 253.57 4.61 0.00 0.00 0.00
November 97.25 35.62 61.63 188.59 28.41 0.00 0.00 0.00
December 97.50 43.57 53.92 159.39 60.17 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 252.06 25.23 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 146.30 0.16 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 328.64 75.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.85 57.13 30.73 123.79 58.66 0.00 0.00 0.00
February 77.56 44.11 33.45 113.02 50.61 0.00 0.00 0.00
March 59.94 24.78 35.16 85.42 42.98 0.00 0.00 0.00
April 42.98 8.80 34.17 67.83 29.93 0.00 0.00 0.00
May 33.55 1.07 32.49 57.38 16.35 0.00 0.00 0.00
June 31.65 0.07 31.59 57.24 8.61 0.00 0.00 0.00
July 33.87 0.28 33.58 67.20 11.10 0.00 0.00 0.00
August 38.07 2.85 35.23 71.19 9.59 0.00 0.00 0.00
September 49.37 12.20 37.18 94.77 12.41 0.00 0.00 0.00
October 68.52 32.58 35.94 119.38 19.77 0.00 0.00 0.00
November 77.63 43.57 34.06 120.37 33.15 0.00 0.00 0.00
December 84.70 53.48 31.22 122.46 53.08 0.00 0.00 0.00
                 
Annual Sum or Average 57.05 23.32 33.73 91.57 28.76 0.00 0.00 0.00
Minimum of Months 31.65 0.07 30.73 57.24 8.61 0.00 0.00 0.00
Maximum of Months 87.85 57.13 37.18 123.79 58.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.66 0.00 18.66 25.23 32.63 0.00 0.00 0.00
February 22.09 0.00 22.09 36.35 25.48 0.00 0.00 0.00
March 26.35 0.00 26.35 43.22 18.31 0.00 0.00 0.00
April 29.61 0.17 29.44 60.44 7.14 0.00 0.00 0.00
May 33.62 1.38 32.24 87.80 0.96 0.00 0.00 0.00
June 36.04 2.59 33.45 103.80 0.05 0.00 0.00 0.00
July 36.50 1.82 34.69 106.65 0.35 0.00 0.00 0.00
August 32.33 0.34 31.99 96.21 0.02 0.00 0.00 0.00
September 28.63 0.01 28.62 87.55 0.51 0.00 0.00 0.00
October 23.97 0.00 23.97 66.67 1.32 0.00 0.00 0.00
November 20.84 0.00 20.84 46.78 11.47 0.00 0.00 0.00
December 18.46 0.00 18.46 28.47 25.79 0.00 0.00 0.00
                 
Annual Sum or Average 27.29 0.53 26.76 65.91 10.27 0.00 0.00 0.00
Minimum of Months 18.46 0.00 18.46 25.23 0.02 0.00 0.00 0.00
Maximum of Months 36.50 2.59 34.69 106.65 32.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 157.17 71.03 0.00 0.00 0.00
February 121.65 56.52 65.13 196.70 53.57 0.00 0.00 0.00
March 148.18 70.06 78.12 238.48 37.42 0.00 0.00 0.00
April 161.02 71.88 89.14 294.78 16.35 0.00 0.00 0.00
May 152.34 60.91 91.43 321.15 2.60 0.00 0.00 0.00
June 149.72 57.46 92.26 341.44 0.27 0.00 0.00 0.00
July 154.05 55.59 98.46 356.51 1.04 0.00 0.00 0.00
August 140.80 47.14 93.66 325.77 0.09 0.00 0.00 0.00
September 135.65 48.98 86.67 312.95 1.74 0.00 0.00 0.00
October 124.71 53.52 71.19 263.82 4.30 0.00 0.00 0.00
November 101.55 40.44 61.11 191.47 25.23 0.00 0.00 0.00
December 82.13 29.10 53.03 129.01 57.16 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 261.03 22.44 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 129.01 0.09 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 356.51 71.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 176.42 37.16 0.00 0.00 0.00
February 96.96 55.15 41.82 164.52 28.89 0.00 0.00 0.00
March 74.94 30.98 43.95 129.61 21.05 0.00 0.00 0.00
April 53.73 11.01 42.72 107.60 9.06 0.00 0.00 0.00
May 41.95 1.33 40.62 103.33 1.47 0.00 0.00 0.00
June 39.57 0.08 39.49 109.52 0.15 0.00 0.00 0.00
July 42.34 0.36 41.99 117.85 0.57 0.00 0.00 0.00
August 47.60 3.56 44.04 127.45 0.05 0.00 0.00 0.00
September 61.73 15.25 46.48 153.22 0.95 0.00 0.00 0.00
October 85.67 40.73 44.93 178.62 2.30 0.00 0.00 0.00
November 97.05 54.47 42.58 177.27 13.54 0.00 0.00 0.00
December 105.90 66.86 39.03 174.61 29.89 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 143.23 12.02 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 103.33 0.05 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 178.62 37.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 29.06 41.09 0.00 0.00 0.00
February 27.61 0.00 27.61 41.99 32.67 0.00 0.00 0.00
March 32.94 0.00 32.94 49.37 24.53 0.00 0.00 0.00
April 37.01 0.21 36.79 69.16 10.77 0.00 0.00 0.00
May 42.02 1.72 40.30 101.74 1.56 0.00 0.00 0.00
June 45.04 3.24 41.80 120.89 0.22 0.00 0.00 0.00
July 45.63 2.27 43.35 124.34 0.78 0.00 0.00 0.00
August 40.41 0.42 39.98 111.55 0.10 0.00 0.00 0.00
September 35.78 0.01 35.77 101.07 1.25 0.00 0.00 0.00
October 29.96 0.00 29.96 75.85 2.43 0.00 0.00 0.00
November 26.05 0.00 26.05 53.48 15.09 0.00 0.00 0.00
December 23.07 0.00 23.07 33.66 31.90 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 76.18 13.45 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 29.06 0.10 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 124.34 41.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 159.44 71.47 0.00 0.00 0.00
February 121.65 56.52 65.13 196.83 56.02 0.00 0.00 0.00
March 148.18 70.06 78.12 237.15 40.55 0.00 0.00 0.00
April 161.02 71.88 89.14 291.35 19.80 0.00 0.00 0.00
May 152.34 60.91 91.43 319.14 2.85 0.00 0.00 0.00
June 149.72 57.46 92.26 340.20 0.38 0.00 0.00 0.00
July 154.05 55.59 98.46 355.39 1.41 0.00 0.00 0.00
August 140.80 47.14 93.66 325.85 0.18 0.00 0.00 0.00
September 135.65 48.98 86.67 313.95 2.16 0.00 0.00 0.00
October 124.71 53.52 71.19 265.66 4.31 0.00 0.00 0.00
November 101.55 40.44 61.11 192.81 26.01 0.00 0.00 0.00
December 82.13 29.10 53.03 131.32 57.02 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 261.02 23.37 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 131.32 0.18 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 355.39 71.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 40.79 52.12 0.00 0.00 0.00
February 34.97 0.00 34.97 59.40 40.25 0.00 0.00 0.00
March 41.71 0.00 41.71 70.08 29.89 0.00 0.00 0.00
April 46.86 0.27 46.60 94.39 14.23 0.00 0.00 0.00
May 53.22 2.18 51.04 129.91 2.89 0.00 0.00 0.00
June 57.04 4.10 52.94 149.49 0.76 0.00 0.00 0.00
July 57.78 2.88 54.91 153.13 2.01 0.00 0.00 0.00
August 51.17 0.54 50.63 135.99 0.50 0.00 0.00 0.00
September 45.31 0.01 45.30 123.64 3.74 0.00 0.00 0.00
October 37.94 0.00 37.94 92.99 6.17 0.00 0.00 0.00
November 32.99 0.00 32.99 68.90 21.52 0.00 0.00 0.00
December 29.22 0.00 29.22 45.29 41.96 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 97.18 17.91 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 40.79 0.50 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 153.13 52.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.89 0.00 10.89 15.04 19.21 0.00 0.00 0.00
February 12.89 0.00 12.89 21.90 14.84 0.00 0.00 0.00
March 15.38 0.00 15.38 25.83 11.02 0.00 0.00 0.00
April 17.28 0.10 17.18 34.80 5.25 0.00 0.00 0.00
May 19.62 0.80 18.81 47.89 1.06 0.00 0.00 0.00
June 21.03 1.51 19.52 55.11 0.28 0.00 0.00 0.00
July 21.30 1.06 20.24 56.45 0.74 0.00 0.00 0.00
August 18.86 0.20 18.67 50.13 0.19 0.00 0.00 0.00
September 16.70 0.00 16.70 45.58 1.38 0.00 0.00 0.00
October 13.99 0.00 13.99 34.28 2.28 0.00 0.00 0.00
November 12.16 0.00 12.16 25.40 7.93 0.00 0.00 0.00
December 10.77 0.00 10.77 16.70 15.47 0.00 0.00 0.00
                 
Annual Sum or Average 15.92 0.31 15.61 35.82 6.60 0.00 0.00 0.00
Minimum of Months 10.77 0.00 10.77 15.04 0.19 0.00 0.00 0.00
Maximum of Months 21.30 1.51 20.24 56.45 19.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.25 33.32 17.93 84.67 17.65 0.00 0.00 0.00
February 45.24 25.73 19.51 79.20 13.78 0.00 0.00 0.00
March 34.96 14.46 20.51 63.08 10.32 0.00 0.00 0.00
April 25.07 5.14 19.93 51.92 5.33 0.00 0.00 0.00
May 19.57 0.62 18.95 48.15 1.10 0.00 0.00 0.00
June 18.46 0.04 18.43 49.49 0.27 0.00 0.00 0.00
July 19.76 0.17 19.59 53.12 0.74 0.00 0.00 0.00
August 22.21 1.66 20.55 57.52 0.18 0.00 0.00 0.00
September 28.80 7.12 21.69 70.06 1.35 0.00 0.00 0.00
October 39.97 19.01 20.97 82.57 2.22 0.00 0.00 0.00
November 45.28 25.41 19.87 83.47 7.37 0.00 0.00 0.00
December 49.41 31.20 18.21 83.21 14.58 0.00 0.00 0.00
                 
Annual Sum or Average 33.28 13.60 19.68 67.14 6.21 0.00 0.00 0.00
Minimum of Months 18.46 0.04 17.93 48.15 0.18 0.00 0.00 0.00
Maximum of Months 51.25 33.32 21.69 84.67 17.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.10 90.45 48.65 229.81 47.89 0.00 0.00 0.00
February 122.80 69.84 52.96 214.96 37.39 0.00 0.00 0.00
March 94.90 39.24 55.67 171.21 28.01 0.00 0.00 0.00
April 68.05 13.94 54.11 140.92 14.47 0.00 0.00 0.00
May 53.13 1.69 51.44 130.69 2.99 0.00 0.00 0.00
June 50.12 0.10 50.01 134.32 0.74 0.00 0.00 0.00
July 53.62 0.45 53.17 144.18 2.00 0.00 0.00 0.00
August 60.28 4.51 55.78 156.11 0.49 0.00 0.00 0.00
September 78.17 19.31 58.86 190.16 3.65 0.00 0.00 0.00
October 108.49 51.59 56.91 224.12 6.03 0.00 0.00 0.00
November 122.91 68.98 53.93 226.56 20.02 0.00 0.00 0.00
December 134.11 84.68 49.43 225.84 39.57 0.00 0.00 0.00
                 
Annual Sum or Average 90.33 36.92 53.40 182.24 16.85 0.00 0.00 0.00
Minimum of Months 50.12 0.10 48.65 130.69 0.49 0.00 0.00 0.00
Maximum of Months 139.10 90.45 58.86 229.81 47.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 174.83 36.33 0.00 0.00 0.00
February 96.96 55.15 41.82 162.52 28.39 0.00 0.00 0.00
March 74.94 30.98 43.95 127.94 20.62 0.00 0.00 0.00
April 53.73 11.01 42.72 106.12 8.59 0.00 0.00 0.00
May 41.95 1.33 40.62 102.79 1.26 0.00 0.00 0.00
June 39.57 0.08 39.49 110.04 0.07 0.00 0.00 0.00
July 42.34 0.36 41.99 117.86 0.41 0.00 0.00 0.00
August 47.60 3.56 44.04 127.07 0.04 0.00 0.00 0.00
September 61.73 15.25 46.48 152.79 0.58 0.00 0.00 0.00
October 85.67 40.73 44.93 177.58 1.81 0.00 0.00 0.00
November 97.05 54.47 42.58 175.62 12.80 0.00 0.00 0.00
December 105.90 66.86 39.03 172.00 29.50 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 142.16 11.63 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 102.79 0.04 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 177.58 36.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 139.61 72.67 0.00 0.00 0.00
February 118.59 54.01 64.58 192.55 56.59 0.00 0.00 0.00
March 146.90 67.15 79.75 238.21 40.55 0.00 0.00 0.00
April 161.24 74.56 86.68 290.53 15.85 0.00 0.00 0.00
May 147.47 56.94 90.54 308.83 2.34 0.00 0.00 0.00
June 124.86 35.04 89.82 295.81 0.12 0.00 0.00 0.00
July 139.32 43.06 96.27 327.49 0.77 0.00 0.00 0.00
August 139.00 45.18 93.82 318.97 0.05 0.00 0.00 0.00
September 118.61 34.96 83.66 280.12 1.10 0.00 0.00 0.00
October 118.21 46.17 72.04 249.39 3.41 0.00 0.00 0.00
November 97.25 35.62 61.63 183.42 25.58 0.00 0.00 0.00
December 97.50 43.57 53.92 153.09 57.56 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 248.47 22.91 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 139.61 0.05 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 327.49 72.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 29.56 41.16 0.00 0.00 0.00
February 27.61 0.00 27.61 41.97 33.24 0.00 0.00 0.00
March 32.94 0.00 32.94 48.86 25.48 0.00 0.00 0.00
April 37.01 0.21 36.79 68.57 11.12 0.00 0.00 0.00
May 42.02 1.72 40.30 101.14 1.41 0.00 0.00 0.00
June 45.04 3.24 41.80 121.14 0.16 0.00 0.00 0.00
July 45.63 2.27 43.35 124.25 0.68 0.00 0.00 0.00
August 40.41 0.42 39.98 111.26 0.09 0.00 0.00 0.00
September 35.78 0.01 35.77 101.43 0.90 0.00 0.00 0.00
October 29.96 0.00 29.96 76.24 1.89 0.00 0.00 0.00
November 26.05 0.00 26.05 53.72 14.54 0.00 0.00 0.00
December 23.07 0.00 23.07 33.02 32.66 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 76.10 13.53 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 29.56 0.09 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 124.25 41.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 143.43 74.88 0.00 0.00 0.00
February 118.59 54.01 64.58 194.14 61.26 0.00 0.00 0.00
March 146.90 67.15 79.75 237.26 46.20 0.00 0.00 0.00
April 161.24 74.56 86.68 287.99 20.66 0.00 0.00 0.00
May 147.47 56.94 90.54 307.15 2.72 0.00 0.00 0.00
June 124.86 35.04 89.82 294.58 0.29 0.00 0.00 0.00
July 139.32 43.06 96.27 326.34 1.24 0.00 0.00 0.00
August 139.00 45.18 93.82 318.99 0.12 0.00 0.00 0.00
September 118.61 34.96 83.66 281.46 1.64 0.00 0.00 0.00
October 118.21 46.17 72.04 251.94 3.50 0.00 0.00 0.00
November 97.25 35.62 61.63 186.28 27.01 0.00 0.00 0.00
December 97.50 43.57 53.92 156.43 59.48 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 249.13 24.76 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 143.43 0.12 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 326.34 74.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 161.09 104.75 56.34 252.98 55.03 0.00 0.00 0.00
February 142.21 80.88 61.33 236.73 42.14 0.00 0.00 0.00
March 109.90 45.44 64.46 188.32 29.36 0.00 0.00 0.00
April 78.80 16.14 62.66 159.68 10.91 0.00 0.00 0.00
May 61.53 1.95 59.57 157.44 1.59 0.00 0.00 0.00
June 58.04 0.12 57.92 167.78 0.07 0.00 0.00 0.00
July 62.10 0.52 61.58 179.77 0.45 0.00 0.00 0.00
August 69.81 5.22 64.59 192.58 0.02 0.00 0.00 0.00
September 90.53 22.37 68.17 227.93 0.64 0.00 0.00 0.00
October 125.64 59.74 65.90 262.02 2.46 0.00 0.00 0.00
November 142.33 79.88 62.45 256.51 19.10 0.00 0.00 0.00
December 155.31 98.06 57.25 249.71 44.80 0.00 0.00 0.00
                 
Annual Sum or Average 104.60 42.76 61.85 210.83 17.11 0.00 0.00 0.00
Minimum of Months 58.04 0.12 56.34 157.44 0.02 0.00 0.00 0.00
Maximum of Months 161.09 104.75 68.17 262.02 55.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 193.20 372.09 0.00 0.00 0.00
February 193.28 0.00 193.28 281.11 312.68 0.00 0.00 0.00
March 230.56 0.00 230.56 329.86 252.30 0.00 0.00 0.00
April 259.03 1.48 257.55 455.52 146.84 0.00 0.00 0.00
May 294.14 12.05 282.09 619.97 54.89 0.00 0.00 0.00
June 315.27 22.68 292.60 722.83 19.26 0.00 0.00 0.00
July 319.36 15.90 303.47 760.43 31.12 0.00 0.00 0.00
August 282.83 2.96 279.86 657.37 18.99 0.00 0.00 0.00
September 250.44 0.06 250.38 610.20 44.16 0.00 0.00 0.00
October 209.71 0.00 209.71 455.55 70.29 0.00 0.00 0.00
November 182.34 0.00 182.34 324.08 170.65 0.00 0.00 0.00
December 161.51 0.00 161.51 212.44 314.81 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 469.43 149.95 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 193.20 18.99 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 760.43 372.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 181.11 395.71 0.00 0.00 0.00
February 193.28 0.00 193.28 265.99 333.03 0.00 0.00 0.00
March 230.56 0.00 230.56 313.82 270.14 0.00 0.00 0.00
April 259.03 1.48 257.55 438.71 158.88 0.00 0.00 0.00
May 294.14 12.05 282.09 603.52 62.57 0.00 0.00 0.00
June 315.27 22.68 292.60 705.62 22.42 0.00 0.00 0.00
July 319.36 15.90 303.47 745.93 35.09 0.00 0.00 0.00
August 282.83 2.96 279.86 639.83 22.65 0.00 0.00 0.00
September 250.44 0.06 250.38 594.61 48.46 0.00 0.00 0.00
October 209.71 0.00 209.71 440.81 78.32 0.00 0.00 0.00
November 182.34 0.00 182.34 309.00 184.49 0.00 0.00 0.00
December 161.51 0.00 161.51 200.31 336.20 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 454.17 161.57 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 181.11 22.42 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 745.93 395.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 26.08 56.50 0.00 0.00 0.00
February 27.61 0.00 27.61 37.35 48.04 0.00 0.00 0.00
March 32.94 0.00 32.94 45.14 39.09 0.00 0.00 0.00
April 37.01 0.21 36.79 66.20 22.64 0.00 0.00 0.00
May 42.02 1.72 40.30 93.35 9.66 0.00 0.00 0.00
June 45.04 3.24 41.80 109.43 3.40 0.00 0.00 0.00
July 45.63 2.27 43.35 117.68 5.40 0.00 0.00 0.00
August 40.41 0.42 39.98 98.42 3.64 0.00 0.00 0.00
September 35.78 0.01 35.77 92.38 6.33 0.00 0.00 0.00
October 29.96 0.00 29.96 68.08 11.13 0.00 0.00 0.00
November 26.05 0.00 26.05 47.08 26.15 0.00 0.00 0.00
December 23.07 0.00 23.07 29.77 47.39 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 69.40 23.17 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 26.08 3.40 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 117.68 56.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.74 100.51 109.23 305.54 198.19 0.00 0.00 0.00
February 243.28 113.02 130.26 372.21 168.19 0.00 0.00 0.00
March 296.35 140.11 156.24 453.38 134.71 0.00 0.00 0.00
April 322.01 143.75 178.26 568.13 85.89 0.00 0.00 0.00
May 304.66 121.80 182.86 597.69 37.12 0.00 0.00 0.00
June 299.42 114.92 184.51 631.71 12.85 0.00 0.00 0.00
July 308.07 111.17 196.90 681.42 20.31 0.00 0.00 0.00
August 281.59 94.28 187.31 595.80 13.84 0.00 0.00 0.00
September 271.28 97.96 173.32 591.63 23.79 0.00 0.00 0.00
October 249.41 107.04 142.37 499.04 41.74 0.00 0.00 0.00
November 203.09 80.88 122.21 359.16 92.41 0.00 0.00 0.00
December 164.25 58.20 106.06 245.12 170.46 0.00 0.00 0.00
                 
Annual Sum or Average 262.80 106.89 155.91 492.22 82.92 0.00 0.00 0.00
Minimum of Months 164.25 58.20 106.06 245.12 12.85 0.00 0.00 0.00
Maximum of Months 322.01 143.75 196.90 681.42 198.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 174.67 51.53 0.00 0.00 0.00
February 96.96 55.15 41.82 160.23 44.15 0.00 0.00 0.00
March 74.94 30.98 43.95 124.57 36.61 0.00 0.00 0.00
April 53.73 11.01 42.72 103.34 22.76 0.00 0.00 0.00
May 41.95 1.33 40.62 92.35 9.84 0.00 0.00 0.00
June 39.57 0.08 39.49 97.14 3.39 0.00 0.00 0.00
July 42.34 0.36 41.99 110.12 5.46 0.00 0.00 0.00
August 47.60 3.56 44.04 113.50 3.69 0.00 0.00 0.00
September 61.73 15.25 46.48 145.18 6.33 0.00 0.00 0.00
October 85.67 40.73 44.93 171.88 10.88 0.00 0.00 0.00
November 97.05 54.47 42.58 172.23 24.35 0.00 0.00 0.00
December 105.90 66.86 39.03 172.06 44.05 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 136.32 21.82 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 92.35 3.39 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 174.67 51.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 38.50 52.41 0.00 0.00 0.00
February 34.97 0.00 34.97 56.32 41.41 0.00 0.00 0.00
March 41.71 0.00 41.71 66.27 31.26 0.00 0.00 0.00
April 46.86 0.27 46.60 89.78 15.81 0.00 0.00 0.00
May 53.22 2.18 51.04 120.79 4.02 0.00 0.00 0.00
June 57.04 4.10 52.94 138.32 1.22 0.00 0.00 0.00
July 57.78 2.88 54.91 142.47 3.19 0.00 0.00 0.00
August 51.17 0.54 50.63 126.54 1.02 0.00 0.00 0.00
September 45.31 0.01 45.30 114.62 4.77 0.00 0.00 0.00
October 37.94 0.00 37.94 86.88 7.20 0.00 0.00 0.00
November 32.99 0.00 32.99 64.56 21.50 0.00 0.00 0.00
December 29.22 0.00 29.22 42.24 43.14 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 90.77 18.82 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 38.50 1.02 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 142.47 52.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.43 0.00 26.43 34.45 46.89 0.00 0.00 0.00
February 31.29 0.00 31.29 50.39 37.05 0.00 0.00 0.00
March 37.32 0.00 37.32 59.29 27.97 0.00 0.00 0.00
April 41.93 0.24 41.69 80.33 14.15 0.00 0.00 0.00
May 47.61 1.95 45.66 108.07 3.59 0.00 0.00 0.00
June 51.04 3.67 47.36 123.75 1.09 0.00 0.00 0.00
July 51.70 2.57 49.12 127.47 2.85 0.00 0.00 0.00
August 45.78 0.48 45.30 113.22 0.92 0.00 0.00 0.00
September 40.54 0.01 40.53 102.55 4.27 0.00 0.00 0.00
October 33.95 0.00 33.95 77.73 6.44 0.00 0.00 0.00
November 29.52 0.00 29.52 57.76 19.24 0.00 0.00 0.00
December 26.14 0.00 26.14 37.79 38.60 0.00 0.00 0.00
                 
Annual Sum or Average 38.64 0.75 37.89 81.21 16.84 0.00 0.00 0.00
Minimum of Months 26.14 0.00 26.14 34.45 0.92 0.00 0.00 0.00
Maximum of Months 51.70 3.67 49.12 127.47 46.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 410.06 266.64 143.43 665.35 141.88 0.00 0.00 0.00
February 362.00 205.88 156.12 619.26 113.85 0.00 0.00 0.00
March 279.76 115.66 164.10 489.51 86.88 0.00 0.00 0.00
April 200.59 41.09 159.50 399.69 47.64 0.00 0.00 0.00
May 156.62 4.97 151.65 357.93 11.94 0.00 0.00 0.00
June 147.73 0.31 147.43 363.56 3.66 0.00 0.00 0.00
July 158.08 1.33 156.75 393.63 9.49 0.00 0.00 0.00
August 177.71 13.29 164.42 431.48 3.03 0.00 0.00 0.00
September 230.45 56.93 173.52 531.59 14.00 0.00 0.00 0.00
October 319.83 152.07 167.75 638.70 21.18 0.00 0.00 0.00
November 362.32 203.35 158.97 650.73 59.56 0.00 0.00 0.00
December 395.35 249.63 145.72 651.38 119.95 0.00 0.00 0.00
                 
Annual Sum or Average 266.27 108.84 157.43 515.54 52.49 0.00 0.00 0.00
Minimum of Months 147.73 0.31 143.43 357.93 3.03 0.00 0.00 0.00
Maximum of Months 410.06 266.64 173.52 665.35 141.88 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148795E+10 0.967519E+09 0.520433E+09 0.237604E+10 0.549732E+09
February 0.118642E+10 0.674762E+09 0.511657E+09 0.200141E+10 0.412765E+09
March 0.101513E+10 0.419697E+09 0.595431E+09 0.175688E+10 0.365056E+09
April 0.704385E+09 0.144292E+09 0.560093E+09 0.137075E+10 0.216206E+09
May 0.568300E+09 18039893.06 0.550260E+09 0.122912E+10 78568152.61
June 0.518766E+09 1079877.92 0.517686E+09 0.119549E+10 20112445.95
July 0.573595E+09 4816469.25 0.568779E+09 0.134108E+10 54485721.25
August 0.644834E+09 48222350.38 0.596611E+09 0.145823E+10 20623793.39
September 0.809229E+09 0.199919E+09 0.609311E+09 0.176934E+10 70825792.30
October 0.116052E+10 0.551817E+09 0.608706E+09 0.223180E+10 0.128099E+09
November 0.127230E+10 0.714056E+09 0.558244E+09 0.221529E+10 0.258647E+09
December 0.143456E+10 0.905795E+09 0.528761E+09 0.233223E+10 0.479988E+09
           
Annual Sum or Average 0.113760E+11 0.465001E+10 0.672597E+10 0.212777E+11 0.265511E+10
Minimum of Months 0.518766E+09 1079877.92 0.511657E+09 0.119549E+10 20112445.95
Maximum of Months 0.148795E+10 0.967519E+09 0.609311E+09 0.237604E+10 0.549732E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.418997E+10 0.272447E+10 0.146550E+10 0.660446E+10 0.172195E+10
February 0.334088E+10 0.190008E+10 0.144079E+10 0.556583E+10 0.129511E+10
March 0.285853E+10 0.118184E+10 0.167669E+10 0.489722E+10 0.114130E+10
April 0.198350E+10 0.406316E+09 0.157718E+10 0.384807E+10 0.671695E+09
May 0.160030E+10 50799149.42 0.154950E+10 0.347885E+10 0.254974E+09
June 0.146081E+10 3040865.03 0.145777E+10 0.340607E+10 87138740.32
July 0.161521E+10 13562859.83 0.160164E+10 0.384131E+10 0.163220E+09
August 0.181581E+10 0.135791E+09 0.168002E+10 0.413045E+10 82386994.44
September 0.227874E+10 0.562957E+09 0.171578E+10 0.500292E+10 0.230063E+09
October 0.326796E+10 0.155388E+10 0.171408E+10 0.626019E+10 0.414728E+09
November 0.358271E+10 0.201074E+10 0.157198E+10 0.617500E+10 0.821168E+09
December 0.403962E+10 0.255066E+10 0.148896E+10 0.650228E+10 0.150117E+10
           
Annual Sum or Average 0.320340E+11 0.130941E+11 0.189399E+11 0.597126E+11 0.838491E+10
Minimum of Months 0.146081E+10 3040865.03 0.144079E+10 0.340607E+10 82386994.44
Maximum of Months 0.418997E+10 0.272447E+10 0.171578E+10 0.660446E+10 0.172195E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544302E+10 0.353924E+10 0.190377E+10 0.893138E+10 0.211888E+10
February 0.433999E+10 0.246832E+10 0.187167E+10 0.754259E+10 0.156133E+10
March 0.371340E+10 0.153528E+10 0.217812E+10 0.664465E+10 0.135945E+10
April 0.257668E+10 0.527828E+09 0.204885E+10 0.522353E+10 0.778024E+09
May 0.207888E+10 65990986.10 0.201288E+10 0.471907E+10 0.275687E+09
June 0.189768E+10 3950256.73 0.189373E+10 0.461855E+10 95952662.72
July 0.209825E+10 17618926.79 0.208063E+10 0.520552E+10 0.193309E+09
August 0.235884E+10 0.176400E+09 0.218244E+10 0.561380E+10 84432702.50
September 0.296021E+10 0.731314E+09 0.222890E+10 0.681602E+10 0.270632E+09
October 0.424526E+10 0.201858E+10 0.222668E+10 0.848454E+10 0.444485E+09
November 0.465415E+10 0.261206E+10 0.204209E+10 0.836551E+10 0.967619E+09
December 0.524769E+10 0.331345E+10 0.193424E+10 0.876231E+10 0.183064E+10
           
Annual Sum or Average 0.416140E+11 0.170100E+11 0.246040E+11 0.809275E+11 0.998043E+10
Minimum of Months 0.189768E+10 3950256.73 0.187167E+10 0.461855E+10 84432702.50
Maximum of Months 0.544302E+10 0.353924E+10 0.222890E+10 0.893138E+10 0.211888E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.475159E+09 99956134.83
February 0.234576E+09 0.133412E+09 0.101164E+09 0.400080E+09 70726519.35
March 0.200709E+09 82981349.66 0.117728E+09 0.349916E+09 57678676.81
April 0.139270E+09 28528948.73 0.110741E+09 0.280744E+09 24637872.58
May 0.112364E+09 3566796.69 0.108797E+09 0.277621E+09 4084515.11
June 0.102570E+09 213510.41 0.102357E+09 0.286374E+09 331345.24
July 0.113411E+09 952298.69 0.112459E+09 0.317294E+09 1563765.28
August 0.127496E+09 9534386.88 0.117961E+09 0.341816E+09 156916.54
September 0.160000E+09 39527329.16 0.120472E+09 0.398899E+09 2414479.46
October 0.229456E+09 0.109104E+09 0.120353E+09 0.479506E+09 6383391.51
November 0.251556E+09 0.141181E+09 0.110375E+09 0.460739E+09 35525664.20
December 0.283637E+09 0.179091E+09 0.104546E+09 0.467820E+09 81430157.63
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.453597E+10 0.384889E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.277621E+09 156916.54
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.479506E+09 99956134.83



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.383518E+09 0.200295E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.475975E+09 0.141067E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.651322E+09 0.113409E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.765348E+09 45579421.21
May 0.394988E+09 0.152497E+09 0.242491E+09 0.835472E+09 7626160.40
June 0.323637E+09 90811701.15 0.232825E+09 0.772042E+09 641297.97
July 0.373167E+09 0.115324E+09 0.257843E+09 0.883163E+09 2959234.64
August 0.372297E+09 0.121012E+09 0.251286E+09 0.859769E+09 267312.26
September 0.307449E+09 90604734.42 0.216844E+09 0.731317E+09 4712681.87
October 0.316622E+09 0.123668E+09 0.192954E+09 0.672905E+09 12191517.03
November 0.252061E+09 92323391.94 0.159737E+09 0.482653E+09 71172256.18
December 0.261142E+09 0.116710E+09 0.144432E+09 0.419800E+09 0.158916E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.793328E+10 0.758837E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.383518E+09 267312.26
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.883163E+09 0.200295E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 81321289.81 0.110720E+09
February 66798791.70 0.00 66798791.70 0.104610E+09 80039854.79
March 88222215.26 1556.86 88220658.39 0.135299E+09 67621783.94
April 95917903.38 547620.98 95370282.40 0.182060E+09 29511677.38
May 0.112552E+09 4610857.06 0.107941E+09 0.273686E+09 4324727.48
June 0.116746E+09 8396627.57 0.108349E+09 0.315948E+09 517422.75
July 0.122202E+09 6082373.67 0.116120E+09 0.334736E+09 2054349.93
August 0.108221E+09 1134477.74 0.107087E+09 0.299236E+09 288087.25
September 92738767.59 21425.30 92717342.29 0.263970E+09 3159388.57
October 80243081.80 0.00 80243081.80 0.204758E+09 6683142.96
November 67521071.96 0.00 67521071.96 0.140925E+09 39567112.82
December 61801109.67 0.00 61801109.67 90856894.12 88123148.93
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.242741E+10 0.432611E+09
Minimum of Months 61801109.67 0.00 61801109.67 81321289.81 288087.25
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.334736E+09 0.110720E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.391859E+09 0.202498E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.478932E+09 0.147840E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.649235E+09 0.123527E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.759091E+09 55277421.75
May 0.394988E+09 0.152497E+09 0.242491E+09 0.831140E+09 8450172.69
June 0.323637E+09 90811701.15 0.232825E+09 0.769070E+09 929515.55
July 0.373167E+09 0.115324E+09 0.257843E+09 0.880237E+09 3803043.04
August 0.372297E+09 0.121012E+09 0.251286E+09 0.859898E+09 437807.64
September 0.307449E+09 90604734.42 0.216844E+09 0.734480E+09 5792739.04
October 0.316622E+09 0.123668E+09 0.192954E+09 0.679165E+09 12340938.15
November 0.252061E+09 92323391.94 0.159737E+09 0.488813E+09 73629233.61
December 0.261142E+09 0.116710E+09 0.144432E+09 0.426919E+09 0.161156E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.794884E+10 0.795682E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.391859E+09 437807.64
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.880237E+09 0.202498E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235309E+09 0.153006E+09 82302997.65 0.331549E+09 0.157102E+09
February 0.187624E+09 0.106708E+09 80915277.26 0.273413E+09 0.122425E+09
March 0.160536E+09 66371880.15 94163689.54 0.228801E+09 0.115111E+09
April 0.111394E+09 22818620.98 88575365.15 0.175816E+09 77583653.97
May 89873280.16 2852869.99 87020410.17 0.153699E+09 43786774.45
June 82039774.92 170774.37 81869000.56 0.148359E+09 22316876.91
July 90710703.00 761687.47 89949015.53 0.179994E+09 29726828.66
August 0.101976E+09 7625992.90 94350425.71 0.190687E+09 25691793.07
September 0.127974E+09 31615575.84 96358645.11 0.245632E+09 32163991.49
October 0.183529E+09 87265587.65 96262912.52 0.319756E+09 52947072.52
November 0.201205E+09 0.112922E+09 88282536.13 0.312000E+09 85930944.64
December 0.226865E+09 0.143244E+09 83620064.08 0.328003E+09 0.142160E+09
           
Annual Sum or Average 0.179903E+10 0.735364E+09 0.106367E+10 0.288771E+10 0.906946E+09
Minimum of Months 82039774.92 170774.37 80915277.26 0.148359E+09 22316876.91
Maximum of Months 0.235309E+09 0.153006E+09 96358645.11 0.331549E+09 0.157102E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49991117.79 0.00 49991117.79 67578208.35 87387918.83
February 53446117.01 0.00 53446117.01 87936726.13 61630760.26
March 70587127.69 1245.66 70585882.03 0.115755E+09 49031593.75
April 76744494.28 438154.86 76306339.42 0.156653E+09 18507501.76
May 90053455.50 3689174.61 86364280.90 0.235165E+09 2574076.89
June 93409270.91 6718192.47 86691078.44 0.269061E+09 140179.46
July 97774596.35 4866543.94 92908052.41 0.285644E+09 948992.63
August 86588371.69 907702.50 85680669.19 0.257685E+09 43634.39
September 74200848.51 17142.51 74183706.00 0.226920E+09 1330263.98
October 64202974.78 0.00 64202974.78 0.178581E+09 3524507.62
November 54024017.81 0.00 54024017.81 0.121253E+09 29737310.99
December 49447441.40 0.00 49447441.40 76261475.48 69080446.36
           
Annual Sum or Average 0.860470E+09 16638156.53 0.843832E+09 0.207849E+10 0.323937E+09
Minimum of Months 49447441.40 0.00 49447441.40 67578208.35 43634.39
Maximum of Months 97774596.35 6718192.47 92908052.41 0.285644E+09 87387918.83



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.420970E+09 0.190238E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.475867E+09 0.129588E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.638753E+09 0.100236E+09
April 0.417353E+09 0.186314E+09 0.231039E+09 0.764073E+09 42382440.93
May 0.408027E+09 0.163129E+09 0.244897E+09 0.860165E+09 6952219.42
June 0.388079E+09 0.148941E+09 0.239138E+09 0.885020E+09 696607.42
July 0.412596E+09 0.148889E+09 0.263707E+09 0.954886E+09 2782215.39
August 0.377126E+09 0.126265E+09 0.250860E+09 0.872552E+09 248235.25
September 0.351604E+09 0.126961E+09 0.224643E+09 0.811158E+09 4521872.31
October 0.334034E+09 0.143355E+09 0.190679E+09 0.706623E+09 11504335.15
November 0.263220E+09 0.104823E+09 0.158397E+09 0.496289E+09 65395371.83
December 0.219983E+09 77942147.70 0.142041E+09 0.345541E+09 0.153094E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.823190E+10 0.707638E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.345541E+09 248235.25
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.954886E+09 0.190238E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.472520E+09 99525970.22
February 0.234576E+09 0.133412E+09 0.101164E+09 0.398007E+09 69901821.85
March 0.200709E+09 82981349.66 0.117728E+09 0.347147E+09 56375889.08
April 0.139270E+09 28528948.73 0.110741E+09 0.278886E+09 23479032.22
May 0.112364E+09 3566796.69 0.108797E+09 0.276771E+09 3932744.17
June 0.102570E+09 213510.41 0.102357E+09 0.283873E+09 376925.11
July 0.113411E+09 952298.69 0.112459E+09 0.315652E+09 1538392.56
August 0.127496E+09 9534386.88 0.117961E+09 0.341373E+09 131181.23
September 0.160000E+09 39527329.16 0.120472E+09 0.397149E+09 2454963.96
October 0.229456E+09 0.109104E+09 0.120353E+09 0.478423E+09 6169771.96
November 0.251556E+09 0.141181E+09 0.110375E+09 0.459478E+09 35107479.18
December 0.283637E+09 0.179091E+09 0.104546E+09 0.467678E+09 80065331.12
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.451696E+10 0.379060E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.276771E+09 131181.23
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.478423E+09 99525970.22



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 77837772.01 0.110063E+09
February 66798791.70 0.00 66798791.70 0.101577E+09 79028263.07
March 88222215.26 1556.86 88220658.39 0.132223E+09 65709667.19
April 95917903.38 547620.98 95370282.40 0.179271E+09 27922119.79
May 0.112552E+09 4610857.06 0.107941E+09 0.272497E+09 4167380.76
June 0.116746E+09 8396627.57 0.108349E+09 0.313341E+09 563887.48
July 0.122202E+09 6082373.67 0.116120E+09 0.333044E+09 2093516.07
August 0.108221E+09 1134477.74 0.107087E+09 0.298773E+09 259674.10
September 92738767.59 21425.30 92717342.29 0.261961E+09 3235780.64
October 80243081.80 0.00 80243081.80 0.203152E+09 6513055.52
November 67521071.96 0.00 67521071.96 0.138626E+09 39100994.32
December 61801109.67 0.00 61801109.67 90164455.59 85442306.39
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.240247E+10 0.424099E+09
Minimum of Months 61801109.67 0.00 61801109.67 77837772.01 259674.10
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.333044E+09 0.110063E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.427040E+09 0.191428E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.476178E+09 0.135516E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.635170E+09 0.108615E+09
April 0.417353E+09 0.186314E+09 0.231039E+09 0.755187E+09 51313525.10
May 0.408027E+09 0.163129E+09 0.244897E+09 0.854786E+09 7645221.79
June 0.388079E+09 0.148941E+09 0.239138E+09 0.881807E+09 980682.55
July 0.412596E+09 0.148889E+09 0.263707E+09 0.951888E+09 3778926.56
August 0.377126E+09 0.126265E+09 0.250860E+09 0.872753E+09 479042.77
September 0.351604E+09 0.126961E+09 0.224643E+09 0.813746E+09 5591302.07
October 0.334034E+09 0.143355E+09 0.190679E+09 0.711543E+09 11550541.38
November 0.263220E+09 0.104823E+09 0.158397E+09 0.499753E+09 67410052.82
December 0.219983E+09 77942147.70 0.142041E+09 0.351738E+09 0.152730E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.823159E+10 0.737039E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.351738E+09 479042.77
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.951888E+09 0.191428E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 0.109265E+09 0.139585E+09
February 84596454.92 0.00 84596454.92 0.143709E+09 97364979.75
March 0.111728E+09 1971.67 0.111726E+09 0.187697E+09 80053366.22
April 0.121474E+09 693527.42 0.120780E+09 0.244665E+09 36894732.34
May 0.142540E+09 5839359.54 0.136701E+09 0.347940E+09 7735673.35
June 0.147852E+09 10633799.02 0.137218E+09 0.387468E+09 1971597.49
July 0.154761E+09 7702942.47 0.147058E+09 0.410138E+09 5379679.61
August 0.137055E+09 1436744.47 0.135618E+09 0.364226E+09 1349906.38
September 0.117448E+09 27133.79 0.117421E+09 0.320486E+09 9702800.20
October 0.101623E+09 0.00 0.101623E+09 0.249067E+09 16538768.38
November 85511177.30 0.00 85511177.30 0.178592E+09 55791007.60
December 78267205.96 0.00 78267205.96 0.121311E+09 0.112396E+09
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.306456E+10 0.564763E+09
Minimum of Months 78267205.96 0.00 78267205.96 0.109265E+09 1349906.38
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.410138E+09 0.139585E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29169767.54 0.00 29169767.54 40279595.01 51456816.09
February 31185756.15 0.00 31185756.15 52977146.42 35892763.10
March 41187518.84 726.84 41186792.00 69192733.99 29510985.54
April 44780336.12 255662.92 44524673.20 90193608.56 13600926.03
May 52546101.77 2152629.72 50393472.05 0.128265E+09 2851689.51
June 54504216.72 3920058.63 50584158.09 0.142837E+09 726812.47
July 57051379.78 2839623.55 54211756.23 0.151194E+09 1983172.66
August 50524228.81 529643.50 49994585.30 0.134269E+09 497631.39
September 43296121.35 10002.64 43286118.71 0.118144E+09 3576853.92
October 37462371.96 0.00 37462371.96 91816468.32 6097158.33
November 31522960.69 0.00 31522960.69 65836431.46 20566875.53
December 28852532.91 0.00 28852532.91 44720344.04 41433653.21
           
Annual Sum or Average 0.502083E+09 9708347.80 0.492375E+09 0.112972E+10 0.208195E+09
Minimum of Months 28852532.91 0.00 28852532.91 40279595.01 497631.39
Maximum of Months 57051379.78 3920058.63 54211756.23 0.151194E+09 51456816.09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137270E+09 89257568.62 48012355.27 0.226774E+09 47262198.94
February 0.109452E+09 62249486.00 47202813.38 0.191600E+09 33328632.19
March 93650183.18 38718763.36 54931419.82 0.168955E+09 27640170.32
April 64982902.08 13311492.51 51671409.57 0.134580E+09 13817929.26
May 52428562.51 1664252.96 50764309.54 0.128966E+09 2947349.97
June 47858801.41 99623.10 47759178.32 0.128268E+09 710836.59
July 52917082.30 444338.73 52472743.56 0.142278E+09 1977354.55
August 59489060.90 4448706.50 55040354.41 0.154050E+09 483349.63
September 74655163.70 18443292.50 56211871.19 0.181596E+09 3489505.38
October 0.107063E+09 50907336.51 56156024.54 0.221164E+09 5946594.87
November 0.117375E+09 65874561.67 51500584.55 0.216362E+09 19114958.35
December 0.132344E+09 83563227.84 48780680.41 0.222858E+09 39049140.68
           
Annual Sum or Average 0.104949E+10 0.428983E+09 0.620504E+09 0.211745E+10 0.195768E+09
Minimum of Months 47858801.41 99623.10 47202813.38 0.128268E+09 483349.63
Maximum of Months 0.137270E+09 89257568.62 56211871.19 0.226774E+09 47262198.94



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372579E+09 0.242263E+09 0.130315E+09 0.615510E+09 0.128279E+09
February 0.297076E+09 0.168958E+09 0.128118E+09 0.520041E+09 90460724.99
March 0.254186E+09 0.105091E+09 0.149095E+09 0.458579E+09 75021075.91
April 0.176377E+09 36130113.49 0.140247E+09 0.365277E+09 37504686.40
May 0.142302E+09 4517122.96 0.137785E+09 0.350040E+09 7999710.69
June 0.129899E+09 270397.47 0.129628E+09 0.348146E+09 1929355.92
July 0.143628E+09 1206026.21 0.142422E+09 0.386171E+09 5366944.70
August 0.161465E+09 12074699.40 0.149391E+09 0.418124E+09 1311909.76
September 0.202629E+09 50058868.35 0.152571E+09 0.492888E+09 9471231.35
October 0.290592E+09 0.138173E+09 0.152419E+09 0.600284E+09 16140274.81
November 0.318580E+09 0.178797E+09 0.139783E+09 0.587250E+09 51881906.83
December 0.359208E+09 0.226808E+09 0.132401E+09 0.604882E+09 0.105987E+09
           
Annual Sum or Average 0.284852E+10 0.116435E+10 0.168417E+10 0.574719E+10 0.531354E+09
Minimum of Months 0.129899E+09 270397.47 0.128118E+09 0.348146E+09 1311909.76
Maximum of Months 0.372579E+09 0.242263E+09 0.152571E+09 0.615510E+09 0.128279E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.468254E+09 97295992.00
February 0.234576E+09 0.133412E+09 0.101164E+09 0.393163E+09 68691876.60
March 0.200709E+09 82981349.66 0.117728E+09 0.342665E+09 55228012.77
April 0.139270E+09 28528948.73 0.110741E+09 0.275067E+09 22263453.36
May 0.112364E+09 3566796.69 0.108797E+09 0.275324E+09 3367038.49
June 0.102570E+09 213510.41 0.102357E+09 0.285235E+09 169632.60
July 0.113411E+09 952298.69 0.112459E+09 0.315677E+09 1097878.73
August 0.127496E+09 9534386.88 0.117961E+09 0.340347E+09 95149.76
September 0.160000E+09 39527329.16 0.120472E+09 0.396028E+09 1498794.98
October 0.229456E+09 0.109104E+09 0.120353E+09 0.475640E+09 4859906.74
November 0.251556E+09 0.141181E+09 0.110375E+09 0.455212E+09 33174386.04
December 0.283637E+09 0.179091E+09 0.104546E+09 0.460672E+09 79007248.66
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.448328E+10 0.366749E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.275067E+09 95149.76
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.475640E+09 97295992.00



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.373939E+09 0.194649E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.465814E+09 0.136900E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.638022E+09 0.108615E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.753066E+09 41082317.58
May 0.394988E+09 0.152497E+09 0.242491E+09 0.827176E+09 6273833.52
June 0.323637E+09 90811701.15 0.232825E+09 0.766730E+09 322819.96
July 0.373167E+09 0.115324E+09 0.257843E+09 0.877138E+09 2051140.57
August 0.372297E+09 0.121012E+09 0.251286E+09 0.854332E+09 123862.75
September 0.307449E+09 90604734.42 0.216844E+09 0.726081E+09 2863275.49
October 0.316622E+09 0.123668E+09 0.192954E+09 0.667973E+09 9120994.97
November 0.252061E+09 92323391.94 0.159737E+09 0.475426E+09 66291805.48
December 0.261142E+09 0.116710E+09 0.144432E+09 0.410042E+09 0.154171E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.783574E+10 0.722465E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.373939E+09 123862.75
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.877138E+09 0.194649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 79160731.21 0.110248E+09
February 66798791.70 0.00 66798791.70 0.101538E+09 80417213.07
March 88222215.26 1556.86 88220658.39 0.130878E+09 68250986.74
April 95917903.38 547620.98 95370282.40 0.177726E+09 28828608.59
May 0.112552E+09 4610857.06 0.107941E+09 0.270906E+09 3780279.61
June 0.116746E+09 8396627.57 0.108349E+09 0.314007E+09 423432.20
July 0.122202E+09 6082373.67 0.116120E+09 0.332779E+09 1819192.92
August 0.108221E+09 1134477.74 0.107087E+09 0.298005E+09 240000.40
September 92738767.59 21425.30 92717342.29 0.262916E+09 2338856.07
October 80243081.80 0.00 80243081.80 0.204208E+09 5068059.46
November 67521071.96 0.00 67521071.96 0.139250E+09 37677234.33
December 61801109.67 0.00 61801109.67 88433080.27 87487487.82
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.239981E+10 0.426580E+09
Minimum of Months 61801109.67 0.00 61801109.67 79160731.21 240000.40
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.332779E+09 0.110248E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.384168E+09 0.200564E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.469669E+09 0.148206E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.635487E+09 0.123742E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.746465E+09 53542240.30
May 0.394988E+09 0.152497E+09 0.242491E+09 0.822666E+09 7286121.12
June 0.323637E+09 90811701.15 0.232825E+09 0.763561E+09 758620.54
July 0.373167E+09 0.115324E+09 0.257843E+09 0.874071E+09 3326900.94
August 0.372297E+09 0.121012E+09 0.251286E+09 0.854380E+09 317120.70
September 0.307449E+09 90604734.42 0.216844E+09 0.729545E+09 4258924.24
October 0.316622E+09 0.123668E+09 0.192954E+09 0.674803E+09 9364037.14
November 0.252061E+09 92323391.94 0.159737E+09 0.482832E+09 70019234.86
December 0.261142E+09 0.116710E+09 0.144432E+09 0.418978E+09 0.159320E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.785662E+10 0.780705E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.384168E+09 317120.70
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.874071E+09 0.200564E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.431464E+09 0.280553E+09 0.150912E+09 0.677570E+09 0.147401E+09
February 0.344028E+09 0.195661E+09 0.148367E+09 0.572708E+09 0.101936E+09
March 0.294360E+09 0.121700E+09 0.172659E+09 0.504392E+09 78647520.48
April 0.204253E+09 41840441.24 0.162413E+09 0.413894E+09 28273443.01
May 0.164793E+09 5231049.65 0.159561E+09 0.421678E+09 4262252.44
June 0.150429E+09 313133.51 0.150116E+09 0.434892E+09 171422.50
July 0.166328E+09 1396637.42 0.164931E+09 0.481490E+09 1203486.02
August 0.186985E+09 13983093.38 0.173002E+09 0.515802E+09 51469.41
September 0.234655E+09 57970621.67 0.176684E+09 0.590805E+09 1660028.19
October 0.336520E+09 0.160011E+09 0.176509E+09 0.701790E+09 6592202.99
November 0.368931E+09 0.207056E+09 0.161876E+09 0.664886E+09 49513132.72
December 0.415981E+09 0.262654E+09 0.153327E+09 0.668832E+09 0.119992E+09
           
Annual Sum or Average 0.329873E+10 0.134837E+10 0.195036E+10 0.664874E+10 0.539704E+09
Minimum of Months 0.150429E+09 313133.51 0.148367E+09 0.413894E+09 51469.41
Maximum of Months 0.431464E+09 0.280553E+09 0.176684E+09 0.701790E+09 0.147401E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.517459E+09 0.996603E+09
February 0.467574E+09 0.00 0.467574E+09 0.680057E+09 0.756435E+09
March 0.617532E+09 10897.63 0.617521E+09 0.883506E+09 0.675750E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.118070E+10 0.380604E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.166053E+10 0.147025E+09
June 0.817192E+09 58774166.93 0.758418E+09 0.187356E+10 49912882.55
July 0.855382E+09 42575003.16 0.812807E+09 0.203675E+10 83348986.97
August 0.757519E+09 7941043.40 0.749578E+09 0.176070E+10 50867295.52
September 0.649147E+09 149971.41 0.648997E+09 0.158164E+10 0.114471E+09
October 0.561680E+09 0.00 0.561680E+09 0.122015E+10 0.188276E+09
November 0.472630E+09 0.00 0.472630E+09 0.840013E+09 0.442330E+09
December 0.432591E+09 0.00 0.432591E+09 0.569004E+09 0.843186E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.148041E+11 0.472881E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.517459E+09 49912882.55
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.203675E+10 0.996603E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.485079E+09 0.105986E+10
February 0.467574E+09 0.00 0.467574E+09 0.643489E+09 0.805663E+09
March 0.617532E+09 10897.63 0.617521E+09 0.840548E+09 0.723548E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.113713E+10 0.411809E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.161645E+10 0.167590E+09
June 0.817192E+09 58774166.93 0.758418E+09 0.182898E+10 58111487.94
July 0.855382E+09 42575003.16 0.812807E+09 0.199791E+10 93996473.91
August 0.757519E+09 7941043.40 0.749578E+09 0.171371E+10 60657609.93
September 0.649147E+09 149971.41 0.648997E+09 0.154122E+10 0.125602E+09
October 0.561680E+09 0.00 0.561680E+09 0.118067E+10 0.209772E+09
November 0.472630E+09 0.00 0.472630E+09 0.800925E+09 0.478204E+09
December 0.432591E+09 0.00 0.432591E+09 0.536514E+09 0.900469E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.143226E+11 0.509528E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.485079E+09 58111487.94
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.199791E+10 0.105986E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 69856709.47 0.151334E+09
February 66798791.70 0.00 66798791.70 90354919.44 0.116227E+09
March 88222215.26 1556.86 88220658.39 0.120894E+09 0.104708E+09
April 95917903.38 547620.98 95370282.40 0.171602E+09 58675443.83
May 0.112552E+09 4610857.06 0.107941E+09 0.250029E+09 25877210.22
June 0.116746E+09 8396627.57 0.108349E+09 0.283633E+09 8806199.51
July 0.122202E+09 6082373.67 0.116120E+09 0.315197E+09 14470839.26
August 0.108221E+09 1134477.74 0.107087E+09 0.263612E+09 9753355.95
September 92738767.59 21425.30 92717342.29 0.239450E+09 16410374.10
October 80243081.80 0.00 80243081.80 0.182343E+09 29800800.58
November 67521071.96 0.00 67521071.96 0.122040E+09 67775013.25
December 61801109.67 0.00 61801109.67 79723564.19 0.126936E+09
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.218874E+10 0.730774E+09
Minimum of Months 61801109.67 0.00 61801109.67 69856709.47 8806199.51
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.315197E+09 0.151334E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.561778E+09 0.269218E+09 0.292561E+09 0.818357E+09 0.530839E+09
February 0.588549E+09 0.273424E+09 0.315125E+09 0.900457E+09 0.406874E+09
March 0.793733E+09 0.375272E+09 0.418462E+09 0.121433E+10 0.360805E+09
April 0.834647E+09 0.372602E+09 0.462045E+09 0.147260E+10 0.222635E+09
May 0.815995E+09 0.326235E+09 0.489760E+09 0.160085E+10 99414200.87
June 0.776103E+09 0.297862E+09 0.478241E+09 0.163739E+10 33307266.18
July 0.825133E+09 0.297756E+09 0.527377E+09 0.182511E+10 54399998.19
August 0.754198E+09 0.252513E+09 0.501685E+09 0.159580E+10 37067855.96
September 0.703159E+09 0.253905E+09 0.449254E+09 0.153350E+10 61661207.81
October 0.668020E+09 0.286690E+09 0.381330E+09 0.133663E+10 0.111795E+09
November 0.526403E+09 0.209630E+09 0.316772E+09 0.930950E+09 0.239530E+09
December 0.439935E+09 0.155873E+09 0.284062E+09 0.656539E+09 0.456561E+09
           
Annual Sum or Average 0.828765E+10 0.337098E+10 0.491667E+10 0.155225E+11 0.261489E+10
Minimum of Months 0.439935E+09 0.155873E+09 0.284062E+09 0.656539E+09 33307266.18
Maximum of Months 0.834647E+09 0.375272E+09 0.527377E+09 0.182511E+10 0.530839E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.467824E+09 0.138021E+09
February 0.234576E+09 0.133412E+09 0.101164E+09 0.387625E+09 0.106802E+09
March 0.200709E+09 82981349.66 0.117728E+09 0.333648E+09 98046253.71
April 0.139270E+09 28528948.73 0.110741E+09 0.267856E+09 59006506.63
May 0.112364E+09 3566796.69 0.108797E+09 0.247342E+09 26357275.21
June 0.102570E+09 213510.41 0.102357E+09 0.251786E+09 8783527.08
July 0.113411E+09 952298.69 0.112459E+09 0.294941E+09 14616106.37
August 0.127496E+09 9534386.88 0.117961E+09 0.304009E+09 9882648.63
September 0.160000E+09 39527329.16 0.120472E+09 0.376307E+09 16400037.72
October 0.229456E+09 0.109104E+09 0.120353E+09 0.460360E+09 29150546.83
November 0.251556E+09 0.141181E+09 0.110375E+09 0.446430E+09 63120676.61
December 0.283637E+09 0.179091E+09 0.104546E+09 0.460847E+09 0.117975E+09
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.429897E+10 0.688162E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.247342E+09 8783527.08
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.467824E+09 0.138021E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 0.103116E+09 0.140368E+09
February 84596454.92 0.00 84596454.92 0.136249E+09 0.100173E+09
March 0.111728E+09 1971.67 0.111726E+09 0.177487E+09 83727660.06
April 0.121474E+09 693527.42 0.120780E+09 0.232717E+09 40979273.55
May 0.142540E+09 5839359.54 0.136701E+09 0.323521E+09 10761025.97
June 0.147852E+09 10633799.02 0.137218E+09 0.358515E+09 3170116.26
July 0.154761E+09 7702942.47 0.147058E+09 0.381593E+09 8541234.48
August 0.137055E+09 1436744.47 0.135618E+09 0.338937E+09 2745247.31
September 0.117448E+09 27133.79 0.117421E+09 0.297104E+09 12366553.23
October 0.101623E+09 0.00 0.101623E+09 0.232692E+09 19289202.00
November 85511177.30 0.00 85511177.30 0.167335E+09 55740091.74
December 78267205.96 0.00 78267205.96 0.113135E+09 0.115553E+09
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.286240E+10 0.593415E+09
Minimum of Months 78267205.96 0.00 78267205.96 0.103116E+09 2745247.31
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.381593E+09 0.140368E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70795903.72 0.00 70795903.72 92258383.18 0.125586E+09
February 75688768.75 0.00 75688768.75 0.121902E+09 89624760.46
March 99963347.83 1764.06 99961583.77 0.158798E+09 74911454.70
April 0.108683E+09 620501.61 0.108063E+09 0.208213E+09 36664311.31
May 0.127531E+09 5224497.11 0.122306E+09 0.289455E+09 9627930.71
June 0.132283E+09 9514100.27 0.122769E+09 0.320765E+09 2836315.03
July 0.138465E+09 6891851.82 0.131574E+09 0.341413E+09 7641874.86
August 0.122624E+09 1285460.72 0.121338E+09 0.303248E+09 2456183.17
September 0.105081E+09 24276.70 0.105057E+09 0.265820E+09 11064402.03
October 90922304.24 0.00 90922304.24 0.208190E+09 17258635.23
November 76507174.33 0.00 76507174.33 0.149715E+09 49870786.35
December 70025965.73 0.00 70025965.73 0.101223E+09 0.103385E+09
           
Annual Sum or Average 0.121857E+10 23562452.29 0.119501E+10 0.256100E+10 0.530928E+09
Minimum of Months 70025965.73 0.00 70025965.73 92258383.18 2456183.17
Maximum of Months 0.138465E+09 9514100.27 0.131574E+09 0.341413E+09 0.125586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109832E+10 0.714162E+09 0.384153E+09 0.178208E+10 0.380024E+09
February 0.875743E+09 0.498067E+09 0.377676E+09 0.149812E+10 0.275416E+09
March 0.749308E+09 0.309794E+09 0.439514E+09 0.131111E+10 0.232687E+09
April 0.519937E+09 0.106507E+09 0.413430E+09 0.103599E+10 0.123489E+09
May 0.419488E+09 13315914.90 0.406172E+09 0.958670E+09 31982390.96
June 0.382925E+09 797097.99 0.382128E+09 0.942350E+09 9486350.73
July 0.423397E+09 3555214.79 0.419842E+09 0.105430E+10 25411142.61
August 0.475980E+09 35594707.33 0.440385E+09 0.115569E+10 8124879.65
September 0.597326E+09 0.147567E+09 0.449759E+09 0.137788E+10 36282122.36
October 0.856629E+09 0.407317E+09 0.449312E+09 0.171069E+10 56718065.43
November 0.939135E+09 0.527071E+09 0.412063E+09 0.168669E+10 0.154385E+09
December 0.105890E+10 0.668601E+09 0.390301E+09 0.174467E+10 0.321282E+09
           
Annual Sum or Average 0.839708E+10 0.343235E+10 0.496474E+10 0.162582E+11 0.165529E+10
Minimum of Months 0.382925E+09 797097.99 0.377676E+09 0.942350E+09 8124879.65
Maximum of Months 0.109832E+10 0.714162E+09 0.449759E+09 0.178208E+10 0.380024E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 887.11 205.25 555.54 361.23 194.31 0.00 0.00
February 827.30 170.62 490.42 278.92 211.50 0.00 0.00
March 655.94 136.30 379.01 156.70 222.31 0.00 0.00
April 528.84 83.41 271.75 55.67 216.09 0.00 0.00
May 458.90 29.33 212.18 6.74 205.44 0.00 0.00
June 461.22 7.76 200.14 0.42 199.72 0.00 0.00
July 500.70 20.34 214.16 1.80 212.36 0.00 0.00
August 544.44 7.70 240.75 18.00 222.75 0.00 0.00
September 682.61 27.32 312.20 77.13 235.07 0.00 0.00
October 833.26 47.83 433.29 206.02 227.26 0.00 0.00
November 854.67 99.79 490.86 275.48 215.37 0.00 0.00
December 870.76 179.21 535.60 338.19 197.42 0.00 0.00
               
Annual Sum or Average 674.71 84.19 360.73 147.45 213.28 0.00 0.00
Minimum of Months 458.90 7.70 200.14 0.42 194.31 0.00 0.00
Maximum of Months 887.11 205.25 555.54 361.23 235.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2465.82 642.90 1564.36 1017.20 547.16 0.00 0.00
February 2300.69 535.35 1380.98 785.42 595.57 0.00 0.00
March 1828.41 426.11 1067.25 441.25 626.01 0.00 0.00
April 1484.59 259.14 765.24 156.76 608.48 0.00 0.00
May 1298.85 95.20 597.48 18.97 578.52 0.00 0.00
June 1314.07 33.62 563.58 1.17 562.41 0.00 0.00
July 1434.18 60.94 603.05 5.06 597.99 0.00 0.00
August 1542.14 30.76 677.95 50.70 627.25 0.00 0.00
September 1930.14 88.76 879.14 217.19 661.95 0.00 0.00
October 2337.29 154.84 1220.12 580.15 639.96 0.00 0.00
November 2382.33 316.81 1382.22 775.75 606.47 0.00 0.00
December 2427.67 560.47 1508.22 952.31 555.91 0.00 0.00
               
Annual Sum or Average 1893.48 265.88 1015.79 415.21 600.58 0.00 0.00
Minimum of Months 1298.85 30.76 563.58 1.17 547.16 0.00 0.00
Maximum of Months 2465.82 642.90 1564.36 1017.20 661.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3334.59 791.10 2032.19 1321.40 710.79 0.00 0.00
February 3117.80 645.39 1793.98 1020.30 773.67 0.00 0.00
March 2480.83 507.56 1386.42 573.21 813.22 0.00 0.00
April 2015.25 300.16 994.09 203.64 790.45 0.00 0.00
May 1761.90 102.93 776.16 24.64 751.52 0.00 0.00
June 1781.85 37.02 732.13 1.52 730.60 0.00 0.00
July 1943.52 72.17 783.39 6.58 776.82 0.00 0.00
August 2095.95 31.52 880.69 65.86 814.83 0.00 0.00
September 2629.64 104.41 1142.06 282.14 859.91 0.00 0.00
October 3167.76 165.95 1585.00 753.65 831.35 0.00 0.00
November 3227.43 373.31 1795.58 1007.74 787.84 0.00 0.00
December 3271.47 683.48 1959.26 1237.10 722.16 0.00 0.00
               
Annual Sum or Average 2566.19 316.48 1319.57 539.38 780.19 0.00 0.00
Minimum of Months 1761.90 31.52 732.13 1.52 710.79 0.00 0.00
Maximum of Months 3334.59 791.10 2032.19 1321.40 859.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 317.69 109.20 204.33 112.28 92.05 0.00 0.00
February 360.73 86.15 215.56 109.16 106.40 0.00 0.00
March 372.72 62.77 221.84 98.14 123.70 0.00 0.00
April 403.48 26.99 214.97 85.57 129.41 0.00 0.00
May 415.58 4.37 189.42 58.27 131.16 0.00 0.00
June 408.34 0.38 164.43 35.12 129.31 0.00 0.00
July 448.20 1.69 181.67 43.41 138.25 0.00 0.00
August 448.62 0.16 186.60 48.74 137.86 0.00 0.00
September 436.04 2.75 180.34 50.21 130.14 0.00 0.00
October 430.23 6.91 203.88 86.91 116.98 0.00 0.00
November 363.14 40.34 194.30 90.09 104.21 0.00 0.00
December 330.07 88.41 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 394.76 35.63 196.66 77.23 119.43 0.00 0.00
Minimum of Months 317.69 0.16 164.43 35.12 92.05 0.00 0.00
Maximum of Months 448.62 109.20 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 175.84 116.12 117.82 40.86 76.96 0.00 0.00
February 240.88 93.86 146.21 54.01 92.19 0.00 0.00
March 292.34 70.80 179.84 67.15 112.69 0.00 0.00
April 362.96 32.57 198.25 74.77 123.48 0.00 0.00
May 412.41 4.69 189.49 58.66 130.84 0.00 0.00
June 418.60 0.56 169.90 38.27 131.63 0.00 0.00
July 453.60 2.17 184.95 45.33 139.62 0.00 0.00
August 432.76 0.26 179.40 45.60 133.80 0.00 0.00
September 385.20 3.45 154.39 34.96 119.43 0.00 0.00
October 330.02 7.10 148.17 46.17 102.00 0.00 0.00
November 242.89 43.61 123.30 35.62 87.68 0.00 0.00
December 192.68 92.44 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 328.80 38.72 159.44 48.74 110.71 0.00 0.00
Minimum of Months 175.84 0.26 117.82 34.96 76.96 0.00 0.00
Maximum of Months 453.60 116.12 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 123.79 58.66 87.85 57.13 30.73 0.00 0.00
February 113.02 50.61 77.56 44.11 33.45 0.00 0.00
March 85.42 42.98 59.94 24.78 35.16 0.00 0.00
April 67.83 29.93 42.98 8.80 34.17 0.00 0.00
May 57.38 16.35 33.55 1.07 32.49 0.00 0.00
June 57.24 8.61 31.65 0.07 31.59 0.00 0.00
July 67.20 11.10 33.87 0.28 33.58 0.00 0.00
August 71.19 9.59 38.07 2.85 35.23 0.00 0.00
September 94.77 12.41 49.37 12.20 37.18 0.00 0.00
October 119.38 19.77 68.52 32.58 35.94 0.00 0.00
November 120.37 33.15 77.63 43.57 34.06 0.00 0.00
December 122.46 53.08 84.70 53.48 31.22 0.00 0.00
               
Annual Sum or Average 91.57 28.76 57.05 23.32 33.73 0.00 0.00
Minimum of Months 57.24 8.61 31.65 0.07 30.73 0.00 0.00
Maximum of Months 123.79 58.66 87.85 57.13 37.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.23 32.63 18.66 0.00 18.66 0.00 0.00
February 36.35 25.48 22.09 0.00 22.09 0.00 0.00
March 43.22 18.31 26.35 0.00 26.35 0.00 0.00
April 60.44 7.14 29.61 0.17 29.44 0.00 0.00
May 87.80 0.96 33.62 1.38 32.24 0.00 0.00
June 103.80 0.05 36.04 2.59 33.45 0.00 0.00
July 106.65 0.35 36.50 1.82 34.69 0.00 0.00
August 96.21 0.02 32.33 0.34 31.99 0.00 0.00
September 87.55 0.51 28.63 0.01 28.62 0.00 0.00
October 66.67 1.32 23.97 0.00 23.97 0.00 0.00
November 46.78 11.47 20.84 0.00 20.84 0.00 0.00
December 28.47 25.79 18.46 0.00 18.46 0.00 0.00
               
Annual Sum or Average 65.91 10.27 27.29 0.53 26.76 0.00 0.00
Minimum of Months 25.23 0.02 18.46 0.00 18.46 0.00 0.00
Maximum of Months 106.65 32.63 36.50 2.59 34.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 332.32 106.92 214.72 121.68 93.04 0.00 0.00
February 360.57 81.81 218.61 111.66 106.95 0.00 0.00
March 366.90 57.28 223.12 101.04 122.08 0.00 0.00
April 402.20 25.23 214.75 82.89 131.86 0.00 0.00
May 424.43 4.01 194.29 62.24 132.05 0.00 0.00
June 450.96 0.41 189.29 57.54 131.75 0.00 0.00
July 474.36 1.61 196.39 55.94 140.44 0.00 0.00
August 453.23 0.14 188.40 50.70 137.70 0.00 0.00
September 466.16 2.69 197.38 64.23 133.15 0.00 0.00
October 442.44 6.59 210.38 94.26 116.13 0.00 0.00
November 368.61 38.64 198.60 94.91 103.69 0.00 0.00
December 302.73 86.16 188.03 95.97 92.06 0.00 0.00
               
Annual Sum or Average 403.90 34.09 202.73 82.60 120.13 0.00 0.00
Minimum of Months 302.73 0.14 188.03 50.70 92.06 0.00 0.00
Maximum of Months 474.36 106.92 223.12 121.68 140.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 185.79 109.85 128.21 50.26 77.95 0.00 0.00
February 236.49 86.35 149.26 56.52 92.75 0.00 0.00
March 283.95 62.52 181.12 70.06 111.06 0.00 0.00
April 360.37 30.42 198.02 72.09 125.93 0.00 0.00
May 420.88 4.41 194.36 62.63 131.73 0.00 0.00
June 461.09 0.60 194.76 60.70 134.06 0.00 0.00
July 479.74 2.19 199.67 57.86 141.81 0.00 0.00
August 437.40 0.27 181.21 47.57 133.64 0.00 0.00
September 414.98 3.38 171.43 48.99 122.44 0.00 0.00
October 341.44 6.67 154.67 53.52 101.15 0.00 0.00
November 245.30 40.11 127.60 40.44 87.16 0.00 0.00
December 163.99 87.92 105.21 29.10 76.11 0.00 0.00
               
Annual Sum or Average 336.39 36.01 165.51 54.11 111.40 0.00 0.00
Minimum of Months 163.99 0.27 105.21 29.10 76.11 0.00 0.00
Maximum of Months 479.74 109.85 199.67 72.09 141.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 366.41 132.97 230.79 123.78 107.01 0.00 0.00
February 373.73 104.52 215.90 95.57 120.33 0.00 0.00
March 329.18 78.21 186.96 53.69 133.27 0.00 0.00
April 321.95 39.20 157.26 19.44 137.82 0.00 0.00
May 356.53 7.94 145.54 5.29 140.25 0.00 0.00
June 388.37 2.04 146.65 5.76 140.89 0.00 0.00
July 406.84 5.45 152.46 4.55 147.91 0.00 0.00
August 399.74 1.36 152.53 6.90 145.63 0.00 0.00
September 429.44 10.12 168.99 26.44 142.55 0.00 0.00
October 433.87 16.61 200.40 70.59 129.80 0.00 0.00
November 403.23 55.74 213.34 94.39 118.95 0.00 0.00
December 369.02 109.57 223.52 115.88 107.64 0.00 0.00
               
Annual Sum or Average 381.54 46.72 182.71 51.67 131.05 0.00 0.00
Minimum of Months 321.95 1.36 145.54 4.55 107.01 0.00 0.00
Maximum of Months 433.87 132.97 230.79 123.78 147.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 311.70 106.26 204.33 112.28 92.05 0.00 0.00
February 353.76 83.68 215.56 109.16 106.40 0.00 0.00
March 365.03 60.05 221.84 98.14 123.70 0.00 0.00
April 396.51 24.29 214.97 85.57 129.41 0.00 0.00
May 411.63 3.60 189.42 58.27 131.16 0.00 0.00
June 405.85 0.19 164.43 35.12 129.31 0.00 0.00
July 445.35 1.18 181.67 43.41 138.25 0.00 0.00
August 446.04 0.08 186.60 48.74 137.86 0.00 0.00
September 432.91 1.68 180.34 50.21 130.14 0.00 0.00
October 426.96 5.20 203.88 86.91 116.98 0.00 0.00
November 358.31 37.64 194.30 90.09 104.21 0.00 0.00
December 323.85 85.82 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 390.03 33.93 196.66 77.23 119.43 0.00 0.00
Minimum of Months 311.70 0.08 164.43 35.12 92.05 0.00 0.00
Maximum of Months 446.04 106.26 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 171.98 115.04 117.82 40.86 76.96 0.00 0.00
February 235.70 94.09 146.21 54.01 92.19 0.00 0.00
March 285.32 70.87 179.84 67.15 112.69 0.00 0.00
April 356.33 31.55 198.25 74.77 123.48 0.00 0.00
May 408.23 4.07 189.49 58.66 130.84 0.00 0.00
June 415.73 0.46 169.90 38.27 131.63 0.00 0.00
July 450.57 1.91 184.95 45.33 139.62 0.00 0.00
August 430.25 0.20 179.40 45.60 133.80 0.00 0.00
September 382.89 2.55 154.39 34.96 119.43 0.00 0.00
October 328.18 5.39 148.17 46.17 102.00 0.00 0.00
November 239.91 41.46 123.30 35.62 87.68 0.00 0.00
December 188.71 91.41 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 324.95 38.00 159.44 48.74 110.71 0.00 0.00
Minimum of Months 171.98 0.20 117.82 34.96 76.96 0.00 0.00
Maximum of Months 450.57 115.04 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 252.98 55.03 161.09 104.75 56.34 0.00 0.00
February 236.73 42.14 142.21 80.88 61.33 0.00 0.00
March 188.32 29.36 109.90 45.44 64.46 0.00 0.00
April 159.68 10.91 78.80 16.14 62.66 0.00 0.00
May 157.44 1.59 61.53 1.95 59.57 0.00 0.00
June 167.78 0.07 58.04 0.12 57.92 0.00 0.00
July 179.77 0.45 62.10 0.52 61.58 0.00 0.00
August 192.58 0.02 69.81 5.22 64.59 0.00 0.00
September 227.93 0.64 90.53 22.37 68.17 0.00 0.00
October 262.02 2.46 125.64 59.74 65.90 0.00 0.00
November 256.51 19.10 142.33 79.88 62.45 0.00 0.00
December 249.71 44.80 155.31 98.06 57.25 0.00 0.00
               
Annual Sum or Average 210.83 17.11 104.60 42.76 61.85 0.00 0.00
Minimum of Months 157.44 0.02 58.04 0.12 56.34 0.00 0.00
Maximum of Months 262.02 55.03 161.09 104.75 68.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 193.20 372.09 163.29 0.00 163.29 0.00 0.00
February 281.11 312.68 193.28 0.00 193.28 0.00 0.00
March 329.86 252.30 230.56 0.00 230.56 0.00 0.00
April 455.52 146.84 259.03 1.48 257.55 0.00 0.00
May 619.97 54.89 294.14 12.05 282.09 0.00 0.00
June 722.83 19.26 315.27 22.68 292.60 0.00 0.00
July 760.43 31.12 319.36 15.90 303.47 0.00 0.00
August 657.37 18.99 282.83 2.96 279.86 0.00 0.00
September 610.20 44.16 250.44 0.06 250.38 0.00 0.00
October 455.55 70.29 209.71 0.00 209.71 0.00 0.00
November 324.08 170.65 182.34 0.00 182.34 0.00 0.00
December 212.44 314.81 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 469.43 149.95 238.71 4.62 234.09 0.00 0.00
Minimum of Months 193.20 18.99 161.51 0.00 161.51 0.00 0.00
Maximum of Months 760.43 372.09 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 181.11 395.71 163.29 0.00 163.29 0.00 0.00
February 265.99 333.03 193.28 0.00 193.28 0.00 0.00
March 313.82 270.14 230.56 0.00 230.56 0.00 0.00
April 438.71 158.88 259.03 1.48 257.55 0.00 0.00
May 603.52 62.57 294.14 12.05 282.09 0.00 0.00
June 705.62 22.42 315.27 22.68 292.60 0.00 0.00
July 745.93 35.09 319.36 15.90 303.47 0.00 0.00
August 639.83 22.65 282.83 2.96 279.86 0.00 0.00
September 594.61 48.46 250.44 0.06 250.38 0.00 0.00
October 440.81 78.32 209.71 0.00 209.71 0.00 0.00
November 309.00 184.49 182.34 0.00 182.34 0.00 0.00
December 200.31 336.20 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 454.17 161.57 238.71 4.62 234.09 0.00 0.00
Minimum of Months 181.11 22.42 161.51 0.00 161.51 0.00 0.00
Maximum of Months 745.93 395.71 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 499.77 299.71 342.91 171.94 170.98 0.00 0.00
February 565.49 256.08 367.86 168.17 199.69 0.00 0.00
March 618.13 205.46 404.22 171.09 233.13 0.00 0.00
April 737.19 130.81 412.74 154.97 257.78 0.00 0.00
May 783.27 56.50 388.63 124.86 263.78 0.00 0.00
June 838.26 19.62 384.04 118.24 265.80 0.00 0.00
July 909.20 31.15 396.04 113.80 282.24 0.00 0.00
August 807.70 21.14 369.59 98.26 271.33 0.00 0.00
September 829.16 36.42 368.79 113.22 255.57 0.00 0.00
October 738.81 63.56 365.04 147.77 217.27 0.00 0.00
November 576.95 141.38 326.19 135.34 190.84 0.00 0.00
December 442.93 257.88 293.22 125.06 168.16 0.00 0.00
               
Annual Sum or Average 696.10 126.07 368.22 136.71 231.52 0.00 0.00
Minimum of Months 442.93 19.62 293.22 98.26 168.16 0.00 0.00
Maximum of Months 909.20 299.71 412.74 171.94 282.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 732.32 235.21 466.04 266.64 199.40 0.00 0.00
February 723.35 189.68 428.25 205.88 222.37 0.00 0.00
March 613.54 144.58 358.80 115.67 243.13 0.00 0.00
April 569.65 77.45 289.39 41.60 247.79 0.00 0.00
May 586.56 19.32 257.45 9.10 248.35 0.00 0.00
June 625.54 5.89 255.81 8.08 247.73 0.00 0.00
July 663.48 15.45 267.56 6.78 260.78 0.00 0.00
August 671.24 4.97 274.66 14.31 260.36 0.00 0.00
September 748.75 23.03 316.30 56.95 259.35 0.00 0.00
October 803.17 34.69 391.72 152.07 239.64 0.00 0.00
November 771.51 98.77 424.83 203.35 221.48 0.00 0.00
December 728.33 198.61 450.71 249.63 201.09 0.00 0.00
               
Annual Sum or Average 686.24 86.86 348.10 110.42 237.68 0.00 0.00
Minimum of Months 569.65 4.97 255.81 6.78 199.40 0.00 0.00
Maximum of Months 803.17 235.21 466.04 266.64 260.78 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.237604E+10 0.549732E+09 0.148795E+10 0.967519E+09 0.520433E+09 0.00 0.00
February 0.200141E+10 0.412765E+09 0.118642E+10 0.674762E+09 0.511657E+09 0.00 0.00
March 0.175688E+10 0.365056E+09 0.101513E+10 0.419697E+09 0.595431E+09 0.00 0.00
April 0.137075E+10 0.216206E+09 0.704385E+09 0.144292E+09 0.560093E+09 0.00 0.00
May 0.122912E+10 78568152.61 0.568300E+09 18039893.06 0.550260E+09 0.00 0.00
June 0.119549E+10 20112445.95 0.518766E+09 1079877.92 0.517686E+09 0.00 0.00
July 0.134108E+10 54485721.25 0.573595E+09 4816469.25 0.568779E+09 0.00 0.00
August 0.145823E+10 20623793.39 0.644834E+09 48222350.38 0.596611E+09 0.00 0.00
September 0.176934E+10 70825792.30 0.809229E+09 0.199919E+09 0.609311E+09 0.00 0.00
October 0.223180E+10 0.128099E+09 0.116052E+10 0.551817E+09 0.608706E+09 0.00 0.00
November 0.221529E+10 0.258647E+09 0.127230E+10 0.714056E+09 0.558244E+09 0.00 0.00
December 0.233223E+10 0.479988E+09 0.143456E+10 0.905795E+09 0.528761E+09 0.00 0.00
               
Annual Sum or Average 0.212777E+11 0.265511E+10 0.113760E+11 0.465001E+10 0.672597E+10 0.00 0.00
Minimum of Months 0.119549E+10 20112445.95 0.518766E+09 1079877.92 0.511657E+09 0.00 0.00
Maximum of Months 0.237604E+10 0.549732E+09 0.148795E+10 0.967519E+09 0.609311E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.660446E+10 0.172195E+10 0.418997E+10 0.272447E+10 0.146550E+10 0.00 0.00
February 0.556583E+10 0.129511E+10 0.334088E+10 0.190008E+10 0.144079E+10 0.00 0.00
March 0.489722E+10 0.114130E+10 0.285853E+10 0.118184E+10 0.167669E+10 0.00 0.00
April 0.384807E+10 0.671695E+09 0.198350E+10 0.406316E+09 0.157718E+10 0.00 0.00
May 0.347885E+10 0.254974E+09 0.160030E+10 50799149.42 0.154950E+10 0.00 0.00
June 0.340607E+10 87138740.32 0.146081E+10 3040865.03 0.145777E+10 0.00 0.00
July 0.384131E+10 0.163220E+09 0.161521E+10 13562859.83 0.160164E+10 0.00 0.00
August 0.413045E+10 82386994.44 0.181581E+10 0.135791E+09 0.168002E+10 0.00 0.00
September 0.500292E+10 0.230063E+09 0.227874E+10 0.562957E+09 0.171578E+10 0.00 0.00
October 0.626019E+10 0.414728E+09 0.326796E+10 0.155388E+10 0.171408E+10 0.00 0.00
November 0.617500E+10 0.821168E+09 0.358271E+10 0.201074E+10 0.157198E+10 0.00 0.00
December 0.650228E+10 0.150117E+10 0.403962E+10 0.255066E+10 0.148896E+10 0.00 0.00
               
Annual Sum or Average 0.597126E+11 0.838491E+10 0.320340E+11 0.130941E+11 0.189399E+11 0.00 0.00
Minimum of Months 0.340607E+10 82386994.44 0.146081E+10 3040865.03 0.144079E+10 0.00 0.00
Maximum of Months 0.660446E+10 0.172195E+10 0.418997E+10 0.272447E+10 0.171578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.893138E+10 0.211888E+10 0.544302E+10 0.353924E+10 0.190377E+10 0.00 0.00
February 0.754259E+10 0.156133E+10 0.433999E+10 0.246832E+10 0.187167E+10 0.00 0.00
March 0.664465E+10 0.135945E+10 0.371340E+10 0.153528E+10 0.217812E+10 0.00 0.00
April 0.522353E+10 0.778024E+09 0.257668E+10 0.527828E+09 0.204885E+10 0.00 0.00
May 0.471907E+10 0.275687E+09 0.207888E+10 65990986.10 0.201288E+10 0.00 0.00
June 0.461855E+10 95952662.72 0.189768E+10 3950256.73 0.189373E+10 0.00 0.00
July 0.520552E+10 0.193309E+09 0.209825E+10 17618926.79 0.208063E+10 0.00 0.00
August 0.561380E+10 84432702.50 0.235884E+10 0.176400E+09 0.218244E+10 0.00 0.00
September 0.681602E+10 0.270632E+09 0.296021E+10 0.731314E+09 0.222890E+10 0.00 0.00
October 0.848454E+10 0.444485E+09 0.424526E+10 0.201858E+10 0.222668E+10 0.00 0.00
November 0.836551E+10 0.967619E+09 0.465415E+10 0.261206E+10 0.204209E+10 0.00 0.00
December 0.876231E+10 0.183064E+10 0.524769E+10 0.331345E+10 0.193424E+10 0.00 0.00
               
Annual Sum or Average 0.809275E+11 0.998043E+10 0.416140E+11 0.170100E+11 0.246040E+11 0.00 0.00
Minimum of Months 0.461855E+10 84432702.50 0.189768E+10 3950256.73 0.187167E+10 0.00 0.00
Maximum of Months 0.893138E+10 0.211888E+10 0.544302E+10 0.353924E+10 0.222890E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.850897E+09 0.292470E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.872668E+09 0.208406E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.998285E+09 0.168135E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.104582E+10 69946044.33 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.111309E+10 11709838.11 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.105842E+10 972275.88 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.120046E+10 4522158.63 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.120158E+10 418989.37 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.113021E+10 7118106.66 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.115234E+10 18502960.28 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.941265E+09 0.104571E+09 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.884061E+09 0.236787E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.124491E+11 0.112356E+10 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.850897E+09 418989.37 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.120158E+10 0.292470E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.470980E+09 0.311017E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.582731E+09 0.227069E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.783008E+09 0.189622E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.940780E+09 84418429.94 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.110460E+10 12553710.89 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.108502E+10 1446732.22 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.121492E+10 5801254.20 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.115911E+10 697991.58 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.998445E+09 8946677.76 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.883916E+09 19017845.74 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.629571E+09 0.113029E+09 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.516077E+09 0.247581E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.103692E+11 0.122120E+10 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.470980E+09 697991.58 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.121492E+10 0.311017E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.331549E+09 0.157102E+09 0.235309E+09 0.153006E+09 82302997.65 0.00 0.00
February 0.273413E+09 0.122425E+09 0.187624E+09 0.106708E+09 80915277.26 0.00 0.00
March 0.228801E+09 0.115111E+09 0.160536E+09 66371880.15 94163689.54 0.00 0.00
April 0.175816E+09 77583653.97 0.111394E+09 22818620.98 88575365.15 0.00 0.00
May 0.153699E+09 43786774.45 89873280.16 2852869.99 87020410.17 0.00 0.00
June 0.148359E+09 22316876.91 82039774.92 170774.37 81869000.56 0.00 0.00
July 0.179994E+09 29726828.66 90710703.00 761687.47 89949015.53 0.00 0.00
August 0.190687E+09 25691793.07 0.101976E+09 7625992.90 94350425.71 0.00 0.00
September 0.245632E+09 32163991.49 0.127974E+09 31615575.84 96358645.11 0.00 0.00
October 0.319756E+09 52947072.52 0.183529E+09 87265587.65 96262912.52 0.00 0.00
November 0.312000E+09 85930944.64 0.201205E+09 0.112922E+09 88282536.13 0.00 0.00
December 0.328003E+09 0.142160E+09 0.226865E+09 0.143244E+09 83620064.08 0.00 0.00
               
Annual Sum or Average 0.288771E+10 0.906946E+09 0.179903E+10 0.735364E+09 0.106367E+10 0.00 0.00
Minimum of Months 0.148359E+09 22316876.91 82039774.92 170774.37 80915277.26 0.00 0.00
Maximum of Months 0.331549E+09 0.157102E+09 0.235309E+09 0.153006E+09 96358645.11 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 67578208.35 87387918.83 49991117.79 0.00 49991117.79 0.00 0.00
February 87936726.13 61630760.26 53446117.01 0.00 53446117.01 0.00 0.00
March 0.115755E+09 49031593.75 70587127.69 1245.66 70585882.03 0.00 0.00
April 0.156653E+09 18507501.76 76744494.28 438154.86 76306339.42 0.00 0.00
May 0.235165E+09 2574076.89 90053455.50 3689174.61 86364280.90 0.00 0.00
June 0.269061E+09 140179.46 93409270.91 6718192.47 86691078.44 0.00 0.00
July 0.285644E+09 948992.63 97774596.35 4866543.94 92908052.41 0.00 0.00
August 0.257685E+09 43634.39 86588371.69 907702.50 85680669.19 0.00 0.00
September 0.226920E+09 1330263.98 74200848.51 17142.51 74183706.00 0.00 0.00
October 0.178581E+09 3524507.62 64202974.78 0.00 64202974.78 0.00 0.00
November 0.121253E+09 29737310.99 54024017.81 0.00 54024017.81 0.00 0.00
December 76261475.48 69080446.36 49447441.40 0.00 49447441.40 0.00 0.00
               
Annual Sum or Average 0.207849E+10 0.323937E+09 0.860470E+09 16638156.53 0.843832E+09 0.00 0.00
Minimum of Months 67578208.35 43634.39 49447441.40 0.00 49447441.40 0.00 0.00
Maximum of Months 0.285644E+09 87387918.83 97774596.35 6718192.47 92908052.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.890097E+09 0.286370E+09 0.575104E+09 0.325914E+09 0.249190E+09 0.00 0.00
February 0.872298E+09 0.197913E+09 0.528872E+09 0.270134E+09 0.258738E+09 0.00 0.00
March 0.982696E+09 0.153408E+09 0.597604E+09 0.270631E+09 0.326974E+09 0.00 0.00
April 0.104249E+10 65393831.94 0.556623E+09 0.214843E+09 0.341780E+09 0.00 0.00
May 0.113680E+10 10748868.67 0.520390E+09 0.166696E+09 0.353695E+09 0.00 0.00
June 0.116889E+10 1073339.18 0.490649E+09 0.149155E+09 0.341494E+09 0.00 0.00
July 0.127053E+10 4309005.59 0.526007E+09 0.149841E+09 0.376166E+09 0.00 0.00
August 0.121392E+10 378707.20 0.504622E+09 0.135800E+09 0.368822E+09 0.00 0.00
September 0.120829E+10 6963962.41 0.511604E+09 0.166489E+09 0.345115E+09 0.00 0.00
October 0.118503E+10 17662320.17 0.563490E+09 0.252459E+09 0.311031E+09 0.00 0.00
November 0.955432E+09 0.100168E+09 0.514776E+09 0.246004E+09 0.268773E+09 0.00 0.00
December 0.810833E+09 0.230773E+09 0.503620E+09 0.257033E+09 0.246587E+09 0.00 0.00
               
Annual Sum or Average 0.127373E+11 0.107516E+10 0.639336E+10 0.260500E+10 0.378836E+10 0.00 0.00
Minimum of Months 0.810833E+09 378707.20 0.490649E+09 0.135800E+09 0.246587E+09 0.00 0.00
Maximum of Months 0.127053E+10 0.286370E+09 0.597604E+09 0.325914E+09 0.376166E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.497613E+09 0.294226E+09 0.343390E+09 0.134618E+09 0.208771E+09 0.00 0.00
February 0.572109E+09 0.208899E+09 0.361094E+09 0.136722E+09 0.224373E+09 0.00 0.00
March 0.760532E+09 0.167464E+09 0.485117E+09 0.187651E+09 0.297466E+09 0.00 0.00
April 0.934072E+09 78850171.44 0.513271E+09 0.186862E+09 0.326409E+09 0.00 0.00
May 0.112727E+10 11804347.78 0.520578E+09 0.167740E+09 0.352838E+09 0.00 0.00
June 0.119515E+10 1543856.13 0.504825E+09 0.157338E+09 0.347487E+09 0.00 0.00
July 0.128493E+10 5868470.73 0.534798E+09 0.154971E+09 0.379827E+09 0.00 0.00
August 0.117152E+10 734954.07 0.485347E+09 0.127400E+09 0.357947E+09 0.00 0.00
September 0.107564E+10 8758578.88 0.444343E+09 0.126983E+09 0.317360E+09 0.00 0.00
October 0.914507E+09 17875404.06 0.414277E+09 0.143355E+09 0.270922E+09 0.00 0.00
November 0.635828E+09 0.103961E+09 0.330741E+09 0.104823E+09 0.225919E+09 0.00 0.00
December 0.439222E+09 0.235491E+09 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
               
Annual Sum or Average 0.106084E+11 0.113548E+10 0.521957E+10 0.170640E+10 0.351316E+10 0.00 0.00
Minimum of Months 0.439222E+09 734954.07 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
Maximum of Months 0.128493E+10 0.294226E+09 0.534798E+09 0.187651E+09 0.379827E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.981387E+09 0.356142E+09 0.618146E+09 0.331521E+09 0.286625E+09 0.00 0.00
February 0.904135E+09 0.252856E+09 0.522310E+09 0.231207E+09 0.291103E+09 0.00 0.00
March 0.881663E+09 0.209465E+09 0.500751E+09 0.143812E+09 0.356939E+09 0.00 0.00
April 0.834506E+09 0.101609E+09 0.407614E+09 50390796.35 0.357223E+09 0.00 0.00
May 0.954938E+09 21260571.27 0.389816E+09 14173365.17 0.375643E+09 0.00 0.00
June 0.100666E+10 5278333.39 0.380113E+09 14923878.21 0.365189E+09 0.00 0.00
July 0.108967E+10 14596890.45 0.408357E+09 12192930.96 0.396164E+09 0.00 0.00
August 0.107066E+10 3634969.08 0.408534E+09 18489793.87 0.390044E+09 0.00 0.00
September 0.111310E+10 26226765.32 0.438028E+09 68539297.28 0.369489E+09 0.00 0.00
October 0.116209E+10 44476421.88 0.536740E+09 0.189080E+09 0.347660E+09 0.00 0.00
November 0.104518E+10 0.144491E+09 0.552989E+09 0.244672E+09 0.308318E+09 0.00 0.00
December 0.988370E+09 0.293464E+09 0.598672E+09 0.310371E+09 0.288301E+09 0.00 0.00
               
Annual Sum or Average 0.120324E+11 0.147350E+10 0.576207E+10 0.162937E+10 0.413270E+10 0.00 0.00
Minimum of Months 0.834506E+09 3634969.08 0.380113E+09 12192930.96 0.286625E+09 0.00 0.00
Maximum of Months 0.116209E+10 0.356142E+09 0.618146E+09 0.331521E+09 0.396164E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.834856E+09 0.284609E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.855827E+09 0.202442E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.977691E+09 0.160847E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.102775E+10 62963100.91 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.110250E+10 9640181.06 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.105196E+10 492219.75 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.119281E+10 3148681.85 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.119467E+10 205060.09 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.112210E+10 4357939.15 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.114357E+10 13937141.97 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.928735E+09 97563666.56 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.867406E+09 0.229869E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.122999E+11 0.107008E+10 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.834856E+09 205060.09 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.119467E+10 0.284609E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.460629E+09 0.308113E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.570215E+09 0.227632E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.764196E+09 0.189824E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.923605E+09 81784796.70 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.109340E+10 10897625.80 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.107757E+10 1181385.35 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.120682E+10 5112682.29 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.115237E+10 541552.65 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.992460E+09 6597012.39 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.879002E+09 14423277.45 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.621854E+09 0.107469E+09 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.505432E+09 0.244828E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.102475E+11 0.119840E+10 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.460629E+09 541552.65 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.120682E+10 0.308113E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.677570E+09 0.147401E+09 0.431464E+09 0.280553E+09 0.150912E+09 0.00 0.00
February 0.572708E+09 0.101936E+09 0.344028E+09 0.195661E+09 0.148367E+09 0.00 0.00
March 0.504392E+09 78647520.48 0.294360E+09 0.121700E+09 0.172659E+09 0.00 0.00
April 0.413894E+09 28273443.01 0.204253E+09 41840441.24 0.162413E+09 0.00 0.00
May 0.421678E+09 4262252.44 0.164793E+09 5231049.65 0.159561E+09 0.00 0.00
June 0.434892E+09 171422.50 0.150429E+09 313133.51 0.150116E+09 0.00 0.00
July 0.481490E+09 1203486.02 0.166328E+09 1396637.42 0.164931E+09 0.00 0.00
August 0.515802E+09 51469.41 0.186985E+09 13983093.38 0.173002E+09 0.00 0.00
September 0.590805E+09 1660028.19 0.234655E+09 57970621.67 0.176684E+09 0.00 0.00
October 0.701790E+09 6592202.99 0.336520E+09 0.160011E+09 0.176509E+09 0.00 0.00
November 0.664886E+09 49513132.72 0.368931E+09 0.207056E+09 0.161876E+09 0.00 0.00
December 0.668832E+09 0.119992E+09 0.415981E+09 0.262654E+09 0.153327E+09 0.00 0.00
               
Annual Sum or Average 0.664874E+10 0.539704E+09 0.329873E+10 0.134837E+10 0.195036E+10 0.00 0.00
Minimum of Months 0.413894E+09 51469.41 0.150429E+09 313133.51 0.148367E+09 0.00 0.00
Maximum of Months 0.701790E+09 0.147401E+09 0.431464E+09 0.280553E+09 0.176684E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.517459E+09 0.996603E+09 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.680057E+09 0.756435E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.883506E+09 0.675750E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.118070E+10 0.380604E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.166053E+10 0.147025E+09 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.187356E+10 49912882.55 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.203675E+10 83348986.97 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.176070E+10 50867295.52 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.158164E+10 0.114471E+09 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.122015E+10 0.188276E+09 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.840013E+09 0.442330E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.569004E+09 0.843186E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.148041E+11 0.472881E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.517459E+09 49912882.55 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.203675E+10 0.996603E+09 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.485079E+09 0.105986E+10 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.643489E+09 0.805663E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.840548E+09 0.723548E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.113713E+10 0.411809E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.161645E+10 0.167590E+09 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.182898E+10 58111487.94 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.199791E+10 93996473.91 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.171371E+10 60657609.93 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.154122E+10 0.125602E+09 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.118067E+10 0.209772E+09 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.800925E+09 0.478204E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.536514E+09 0.900469E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.143226E+11 0.509528E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.485079E+09 58111487.94 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.199791E+10 0.105986E+10 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.133858E+10 0.802739E+09 0.918453E+09 0.460513E+09 0.457941E+09 0.00 0.00
February 0.136803E+10 0.619500E+09 0.889924E+09 0.406836E+09 0.483088E+09 0.00 0.00
March 0.165561E+10 0.550303E+09 0.108266E+10 0.458255E+09 0.624410E+09 0.00 0.00
April 0.191081E+10 0.339066E+09 0.106984E+10 0.401679E+09 0.668156E+09 0.00 0.00
May 0.209791E+10 0.151339E+09 0.104091E+10 0.334413E+09 0.706498E+09 0.00 0.00
June 0.217276E+10 50845843.21 0.995419E+09 0.306472E+09 0.688947E+09 0.00 0.00
July 0.243519E+10 83433557.19 0.106075E+10 0.304791E+09 0.755955E+09 0.00 0.00
August 0.216334E+10 56629084.75 0.989915E+09 0.263182E+09 0.726733E+09 0.00 0.00
September 0.214919E+10 94407084.93 0.955897E+09 0.293453E+09 0.662444E+09 0.00 0.00
October 0.197884E+10 0.170250E+09 0.977720E+09 0.395794E+09 0.581926E+09 0.00 0.00
November 0.149546E+10 0.366464E+09 0.845480E+09 0.350811E+09 0.494669E+09 0.00 0.00
December 0.118635E+10 0.690713E+09 0.785373E+09 0.334964E+09 0.450409E+09 0.00 0.00
               
Annual Sum or Average 0.219521E+11 0.397569E+10 0.116123E+11 0.431116E+10 0.730118E+10 0.00 0.00
Minimum of Months 0.118635E+10 50845843.21 0.785373E+09 0.263182E+09 0.450409E+09 0.00 0.00
Maximum of Months 0.243519E+10 0.802739E+09 0.108266E+10 0.460513E+09 0.755955E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.196146E+10 0.629982E+09 0.124824E+10 0.714162E+09 0.534077E+09 0.00 0.00
February 0.174994E+10 0.458883E+09 0.103603E+10 0.498067E+09 0.537961E+09 0.00 0.00
March 0.164330E+10 0.387235E+09 0.960999E+09 0.309798E+09 0.651201E+09 0.00 0.00
April 0.147653E+10 0.200741E+09 0.750094E+09 0.107821E+09 0.642273E+09 0.00 0.00
May 0.157103E+10 51755101.82 0.689559E+09 24379771.54 0.665179E+09 0.00 0.00
June 0.162141E+10 15270269.19 0.663060E+09 20944997.28 0.642115E+09 0.00 0.00
July 0.177708E+10 41368280.14 0.716623E+09 18150009.08 0.698473E+09 0.00 0.00
August 0.179785E+10 13306866.68 0.735659E+09 38316912.53 0.697342E+09 0.00 0.00
September 0.194077E+10 59682185.30 0.819855E+09 0.147619E+09 0.672236E+09 0.00 0.00
October 0.215122E+10 92920275.35 0.104917E+10 0.407317E+09 0.641857E+09 0.00 0.00
November 0.199977E+10 0.256017E+09 0.110115E+10 0.527071E+09 0.574082E+09 0.00 0.00
December 0.195077E+10 0.531962E+09 0.120719E+10 0.668601E+09 0.538594E+09 0.00 0.00
               
Annual Sum or Average 0.216411E+11 0.273912E+10 0.109776E+11 0.348225E+10 0.749539E+10 0.00 0.00
Minimum of Months 0.147653E+10 13306866.68 0.663060E+09 18150009.08 0.534077E+09 0.00 0.00
Maximum of Months 0.215122E+10 0.629982E+09 0.124824E+10 0.714162E+09 0.698473E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770590E+10 -0.754277E+10 0.00 0.00 744.00 0.00 -163126306.9 81.21 0.00 0.00
February 0.696324E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -147282023.6 81.21 0.00 0.00
March 0.770438E+10 -0.754145E+10 0.00 0.00 744.00 0.00 -162936495.5 81.21 0.00 0.00
April 0.746608E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -157484117.8 81.21 0.00 0.00
May 0.770535E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -162546653.0 81.21 0.00 0.00
June 0.745768E+10 -0.730054E+10 0.00 0.00 720.00 0.00 -157138955.9 81.21 0.00 0.00
July 0.771323E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -162369174.6 81.21 0.00 0.00
August 0.770524E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -162430101.5 81.21 0.00 0.00
September 0.746711E+10 -0.730995E+10 0.00 0.00 720.00 0.00 -157165771.7 81.21 0.00 0.00
October 0.770400E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -162558165.4 81.21 0.00 0.00
November 0.745000E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -157566744.8 81.21 0.00 0.00
December 0.771389E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -163053388.9 81.21 0.00 0.00
                     
Annual Sum or Average 0.907561E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.191566E+10 81.21 0.00 0.00
Minimum of Months 0.696324E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -163126306.9 81.21 0.00 0.00
Maximum of Months 0.771389E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -147282023.6 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.974403E+11 -0.956666E+11 0.00 0.00 744.00 0.00 -0.177367E+10 81.26 0.00 0.00
February 0.875028E+11 -0.858968E+11 0.00 0.00 672.00 0.00 -0.160594E+10 81.25 0.00 0.00
March 0.951159E+11 -0.933321E+11 0.00 0.00 744.00 0.00 -0.178389E+10 81.25 0.00 0.00
April 0.895457E+11 -0.878243E+11 0.00 0.00 720.00 0.00 -0.172148E+10 81.25 0.00 0.00
May 0.898518E+11 -0.880808E+11 0.00 0.00 744.00 0.00 -0.177098E+10 81.25 0.00 0.00
June 0.849669E+11 -0.832610E+11 0.00 0.00 720.00 0.00 -0.170599E+10 81.25 0.00 0.00
July 0.869332E+11 -0.851794E+11 0.00 0.00 744.00 0.00 -0.175374E+10 81.23 0.00 0.00
August 0.874980E+11 -0.857461E+11 0.00 0.00 744.00 0.00 -0.175193E+10 81.24 0.00 0.00
September 0.864386E+11 -0.847484E+11 0.00 0.00 720.00 0.00 -0.169014E+10 81.24 0.00 0.00
October 0.919183E+11 -0.901705E+11 0.00 0.00 744.00 0.00 -0.174786E+10 81.24 0.00 0.00
November 0.915384E+11 -0.898386E+11 0.00 0.00 720.00 0.00 -0.169983E+10 81.24 0.00 0.00
December 0.966120E+11 -0.948454E+11 0.00 0.00 744.00 0.00 -0.176662E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.108536E+13 -0.106459E+13 0.00 0.00 8760.00 0.00 -0.207721E+11 81.24 0.00 0.00
Minimum of Months 0.849669E+11 -0.956666E+11 0.00 0.00 672.00 0.00 -0.178389E+10 81.23 0.00 0.00
Maximum of Months 0.974403E+11 -0.832610E+11 0.00 0.00 744.00 0.00 -0.160594E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.515633E+11 -0.500354E+11 0.00 0.00 744.00 0.00 -0.152783E+10 58.98 0.00 0.00
February 0.461458E+11 -0.447601E+11 0.00 0.00 672.00 0.00 -0.138562E+10 58.98 0.00 0.00
March 0.496070E+11 -0.480647E+11 0.00 0.00 744.00 0.00 -0.154225E+10 58.98 0.00 0.00
April 0.458176E+11 -0.443318E+11 0.00 0.00 720.00 0.00 -0.148576E+10 58.98 0.00 0.00
May 0.450341E+11 -0.435097E+11 0.00 0.00 744.00 0.00 -0.152435E+10 58.98 0.00 0.00
June 0.418773E+11 -0.404130E+11 0.00 0.00 720.00 0.00 -0.146433E+10 58.98 0.00 0.00
July 0.424800E+11 -0.409787E+11 0.00 0.00 744.00 0.00 -0.150133E+10 58.97 0.00 0.00
August 0.430103E+11 -0.415122E+11 0.00 0.00 744.00 0.00 -0.149811E+10 58.97 0.00 0.00
September 0.431211E+11 -0.416786E+11 0.00 0.00 720.00 0.00 -0.144251E+10 58.98 0.00 0.00
October 0.467814E+11 -0.452887E+11 0.00 0.00 744.00 0.00 -0.149270E+10 58.98 0.00 0.00
November 0.475090E+11 -0.460529E+11 0.00 0.00 720.00 0.00 -0.145611E+10 58.98 0.00 0.00
December 0.508406E+11 -0.493221E+11 0.00 0.00 744.00 0.00 -0.151846E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.553787E+12 -0.535948E+12 0.00 0.00 8760.00 0.00 -0.178394E+11 58.98 0.00 0.00
Minimum of Months 0.418773E+11 -0.500354E+11 0.00 0.00 672.00 0.00 -0.154225E+10 58.97 0.00 0.00
Maximum of Months 0.515633E+11 -0.404130E+11 0.00 0.00 744.00 0.00 -0.138562E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.87 0.86 01-JAN-07:40 5933.39 35.70 267.83 295.00 717.82 25.64 223.17 271.33
February 304.33 0.87 0.86 01-FEB-07:00 1797.99 25.07 115.00 283.83 521.01 21.66 173.17 246.50
March 362.67 0.87 0.86 01-MAR-09:09 1104.09 19.70 1.00 333.50 432.31 21.45 196.83 274.00
April 357.50 0.88 0.86 01-APR-08:39 895.90 19.54 0.00 333.83 362.69 21.24 202.33 264.83
May 389.00 0.88 0.86 01-MAY-07:49 778.98 18.80 0.00 352.50 312.24 20.51 158.83 252.00
June 388.17 0.89 0.86 01-JUN-07:00 733.18 18.12 0.00 329.17 290.50 19.86 129.50 231.17
July 403.83 0.88 0.86 01-JUL-07:19 824.69 18.89 0.00 361.50 330.55 20.62 203.50 273.67
August 348.33 0.88 0.86 01-AUG-07:49 979.06 19.25 0.00 347.33 385.64 20.96 208.67 283.17
September 349.67 0.88 0.86 01-SEP-07:30 1199.36 19.40 4.17 320.17 458.30 21.12 215.17 266.33
October 323.50 0.87 0.86 02-OCT-11:39 1541.46 21.57 44.17 318.83 554.21 21.99 237.33 278.50
November 314.83 0.87 0.86 01-NOV-07:10 3567.62 31.22 239.50 296.50 628.53 24.16 238.50 267.50
December 282.67 0.87 0.86 01-DEC-08:39 6095.91 36.46 279.00 284.67 741.99 25.23 219.17 258.33
                         
Annual Sum or Average 4111.50 0.87     1944.99 23.00 950.67 3856.83 462.17 21.86 2406.17 3167.33
Minimum of Months 282.67 0.87 0.86   733.18 18.12 0.00 283.83 290.50 19.86 129.50 231.17
Maximum of Months 403.83 0.89 0.86   6095.91 36.46 279.00 361.50 741.99 25.64 238.50 283.17



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.26 0.22 01-JAN-07:40 6279.20 35.73 267.83 301.00 1061.43 25.49 214.33 290.00
February 304.33 0.26 0.22 01-FEB-07:49 2074.84 25.17 119.17 291.83 797.05 21.88 177.67 269.33
March 362.67 0.26 0.22 01-MAR-07:49 1316.39 20.26 41.00 344.83 643.31 21.81 229.83 313.17
April 357.50 0.27 0.22 01-APR-07:19 1056.70 20.26 32.50 344.00 522.97 21.75 244.50 316.17
May 389.00 0.28 0.22 01-MAY-06:00 905.01 19.68 7.17 369.50 437.79 21.17 217.67 327.33
June 388.17 0.31 0.22 01-JUN-06:00 849.55 19.07 5.67 349.67 406.41 20.58 189.50 301.17
July 403.83 0.27 0.22 01-JUL-06:49 953.66 19.78 10.67 377.50 459.03 21.29 250.17 333.83
August 348.33 0.28 0.22 01-AUG-07:10 1129.69 20.05 46.33 360.17 535.71 21.54 249.67 326.83
September 349.67 0.27 0.22 01-SEP-06:00 1385.92 20.12 62.00 330.33 644.12 21.63 243.50 302.33
October 323.50 0.26 0.22 02-OCT-07:30 1800.00 21.96 76.83 326.67 811.67 22.28 250.17 307.17
November 314.83 0.25 0.22 01-NOV-06:00 3855.08 31.27 240.83 304.00 914.35 24.28 245.33 285.50
December 282.67 0.24 0.22 01-DEC-08:39 6444.00 36.52 279.17 292.50 1087.21 25.18 218.83 273.50
                         
Annual Sum or Average 4111.50 0.27     2152.82 23.55 1189.17 3992.00 668.98 22.26 2731.17 3646.33
Minimum of Months 282.67 0.24 0.22   849.55 19.07 5.67 291.83 406.41 20.58 177.67 269.33
Maximum of Months 403.83 0.31 0.22   6444.00 36.52 279.17 377.50 1087.21 25.49 250.17 333.83



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.69 0.60 01-JAN-10:20 358.47 14.68 0.00 262.33 178.83 18.12 0.00 110.67
February 304.33 0.67 0.60 01-FEB-09:39 418.09 15.61 0.00 265.50 200.09 18.91 0.00 147.67
March 362.67 0.65 0.60 01-MAR-13:20 506.32 16.57 0.00 330.00 236.19 19.78 0.00 226.67
April 357.50 0.63 0.60 01-APR-07:30 615.39 17.43 0.00 343.17 282.91 20.59 47.33 296.83
May 389.00 0.62 0.60 01-MAY-06:49 755.44 18.04 12.33 376.50 325.23 21.17 122.50 335.50
June 388.17 0.63 0.60 01-JUN-06:10 825.56 19.79 59.33 369.17 348.87 21.84 148.67 318.00
July 403.83 0.62 0.60 01-JUL-06:30 860.26 17.83 1.33 384.83 366.32 21.71 179.00 344.33
August 348.33 0.63 0.60 01-AUG-07:10 763.69 17.58 0.00 360.67 336.00 20.74 109.50 320.67
September 349.67 0.64 0.60 01-SEP-07:10 634.83 16.89 0.00 325.50 281.83 20.04 20.00 267.33
October 323.50 0.65 0.60 02-OCT-11:39 485.31 16.23 0.00 309.17 232.90 19.49 0.00 217.83
November 314.83 0.67 0.60 01-NOV-08:20 433.06 15.59 0.00 277.67 202.78 18.89 0.00 164.00
December 282.67 0.67 0.60 01-DEC-09:20 404.12 15.35 0.00 262.67 195.60 18.74 0.00 134.50
                         
Annual Sum or Average 4111.50 0.65     605.87 16.94 73.00 3867.17 272.15 20.13 627.00 2884.00
Minimum of Months 282.67 0.62 0.60   358.47 14.68 0.00 262.33 178.83 18.12 0.00 110.67
Maximum of Months 403.83 0.69 0.60   860.26 19.79 59.33 384.83 366.32 21.84 179.00 344.33



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.69 0.60 01-JAN-10:20 358.47 14.68 0.00 262.33 178.83 18.12 0.00 110.67
February 304.33 0.67 0.60 01-FEB-09:39 418.09 15.61 0.00 265.50 200.09 18.91 0.00 147.67
March 362.67 0.65 0.60 01-MAR-13:20 506.32 16.57 0.00 330.00 236.19 19.78 0.00 226.67
April 357.50 0.63 0.60 01-APR-07:30 615.39 17.43 0.00 343.17 282.91 20.59 47.33 296.83
May 389.00 0.62 0.60 01-MAY-06:49 755.44 18.04 12.33 376.50 325.23 21.17 122.50 335.50
June 388.17 0.63 0.60 01-JUN-06:10 825.56 19.79 59.33 369.17 348.87 21.84 148.67 318.00
July 403.83 0.62 0.60 01-JUL-06:30 860.26 17.83 1.33 384.83 366.32 21.71 179.00 344.33
August 348.33 0.63 0.60 01-AUG-07:10 763.69 17.58 0.00 360.67 336.00 20.74 109.50 320.67
September 349.67 0.64 0.60 01-SEP-07:10 634.83 16.89 0.00 325.50 281.83 20.04 20.00 267.33
October 323.50 0.65 0.60 02-OCT-11:39 485.31 16.23 0.00 309.17 232.90 19.49 0.00 217.83
November 314.83 0.67 0.60 01-NOV-08:20 433.06 15.59 0.00 277.67 202.78 18.89 0.00 164.00
December 282.67 0.67 0.60 01-DEC-09:20 404.12 15.35 0.00 262.67 195.60 18.74 0.00 134.50
                         
Annual Sum or Average 4111.50 0.65     605.87 16.94 73.00 3867.17 272.15 20.13 627.00 2884.00
Minimum of Months 282.67 0.62 0.60   358.47 14.68 0.00 262.33 178.83 18.12 0.00 110.67
Maximum of Months 403.83 0.69 0.60   860.26 19.79 59.33 384.83 366.32 21.84 179.00 344.33



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 16413.84 109.43 19-APR-15:13 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 200222.76 289.13 15-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 216636.61     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 200222.76 289.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.392244E+09 1427.08 31-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.234293E+09 2038.16 04-FEB-07:15 0.00 0.00 0.00 0.00 0.00
March 0.236365E+09 1643.73 16-MAR-07:07 0.00 0.00 0.00 0.00 0.00
April 13215960.58 538.33 19-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 3558055.25 331.32 01-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 91460822.10 1274.68 13-NOV-06:40 0.00 0.00 0.00 0.00 0.00
December 0.347605E+09 1406.73 27-DEC-07:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.131874E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.392244E+09 2038.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 81128809.37 581.90 31-JAN-10:20 0.00 0.00 0.00 0.00 0.00
February 75494160.84 698.83 04-FEB-11:02 0.00 0.00 0.00 0.00 0.00
March 71748252.83 660.63 20-MAR-10:03 0.00 0.00 0.00 0.00 0.00
April 116493.20 28.26 30-APR-14:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 12674932.38 417.00 13-NOV-10:05 0.00 0.00 0.00 0.00 0.00
December 84685218.26 531.19 21-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.325848E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 84685218.26 698.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.531513E+09 1232.42 25-JAN-10:10 0.00 0.00 0.00 0.00 0.00
February 0.316123E+09 1465.66 04-FEB-10:10 0.00 0.00 0.00 0.00 0.00
March 0.320801E+09 1341.70 16-MAR-10:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 30821467.48 582.75 13-NOV-10:30 0.00 0.00 0.00 0.00 0.00
December 0.389339E+09 1134.49 21-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158860E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.531513E+09 1465.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.279382E+09 650.44 25-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.166264E+09 810.83 04-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 0.175517E+09 723.76 16-MAR-09:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 13688727.06 280.81 13-NOV-10:05 0.00 0.00 0.00 0.00 0.00
December 0.202715E+09 580.07 21-DEC-08:63 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.837567E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.279382E+09 810.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.371059E+10 7354.90 23-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.298622E+10 7693.45 04-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.293464E+10 7104.66 20-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.196845E+10 5756.68 19-APR-04:00 0.00 0.00 0.00 0.00 0.00
May 0.166603E+10 5893.06 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 0.125875E+10 5164.85 19-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.110324E+10 4601.91 15-JUL-05:00 0.00 0.00 0.00 0.00 0.00
August 0.152883E+10 5371.52 29-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 0.123067E+10 4720.20 16-SEP-05:00 0.00 0.00 0.00 0.00 0.00
October 0.165942E+10 5421.68 02-OCT-04:00 0.00 0.00 0.00 0.00 0.00
November 0.234822E+10 7230.51 13-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.357485E+10 7472.08 21-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.259699E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.110324E+10 4601.91   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.371059E+10 7693.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.120771E+09 3007.61 23-JAN-07:07 0.00 0.00 0.00 0.00 0.00
February 83605356.24 3213.24 04-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.229453E+09 4352.26 16-MAR-08:06 0.00 0.00 0.00 0.00 0.00
April 12119285.81 1654.54 19-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 591917.83 949.18 01-MAY-08:08 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 5778997.48 725.48 28-AUG-14:00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 28686655.32 2731.19 13-NOV-07:07 0.00 0.00 0.00 0.00 0.00
December 0.179676E+09 2899.52 21-DEC-07:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.660682E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.229453E+09 4352.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 97637593.38 5044.32 31-JAN-09:08 0.00 0.00 0.00 0.00 0.00
February 0.182974E+09 5160.61 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.466152E+09 7496.61 16-MAR-09:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.178389E+09 4689.86 21-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.925153E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.466152E+09 7496.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.222324E+09 3822.48 26-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.346778E+09 5229.30 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.183183E+09 3483.88 21-MAR-08:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.282254E+09 3677.23 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.103454E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.346778E+09 5229.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108809E+10 3829.90 25-JAN-07:07 0.00 0.00 0.00 0.00 0.00
February 0.651800E+09 4806.94 04-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.585966E+09 4227.92 16-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 6471113.86 719.38 19-APR-06:15 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.234712E+09 3108.36 13-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.102697E+10 3624.39 21-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.359401E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108809E+10 4806.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10394638.94 825.09 25-JAN-09:10 0.00 0.00 0.00 0.00 0.00
February 145479.85 172.11 03-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 19061172.01 2215.91 16-MAR-08:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 14077015.85 524.69 15-DEC-11:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 43678306.64     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 19061172.01 2215.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 2157722.47 380.85 16-MAR-09:30 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2157722.47     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2157722.47 380.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 82564805.37 2249.64 25-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 66970995.87 2891.68 04-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 42020057.74 2249.72 16-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 1019905.47 579.42 19-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 23940222.88 1820.44 13-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 78778744.30 2202.13 21-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.295295E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 82564805.37 2891.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 5672.26 0.23 26-JAN-22:50 0.00 0.00 0.00 0.00 0.00
February 4767.73 0.23 17-FEB-04:15 0.00 0.00 0.00 0.00 0.00
March 6114.83 0.23 13-MAR-09:50 0.00 0.00 0.00 0.00 0.00
April 7458.03 0.23 21-APR-16:50 0.00 0.00 0.00 0.00 0.00
May 8642.27 0.23 21-MAY-05:07 0.00 0.00 0.00 0.00 0.00
June 9815.10 0.23 08-JUN-09:20 0.00 0.00 0.00 0.00 0.00
July 9777.18 0.23 12-JUL-05:05 0.00 0.00 0.00 0.00 0.00
August 8135.53 0.23 08-AUG-09:02 0.00 0.00 0.00 0.00 0.00
September 7395.81 0.23 26-SEP-03:15 0.00 0.00 0.00 0.00 0.00
October 7482.63 0.23 18-OCT-22:08 0.00 0.00 0.00 0.00 0.00
November 9666.95 0.23 02-NOV-22:08 0.00 0.00 0.00 0.00 0.00
December 9391.56 0.23 08-DEC-22:57 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 94319.88     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4767.73 0.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 9815.10 0.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 43549827.37 3527.46 16-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 59070371.48 3529.32 03-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 32366893.95 3529.18 19-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 5574206.06 3527.68 20-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 5984930.49 3272.16 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 5315371.74 2764.06 15-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 3065967.92 2260.50 04-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 3301857.03 2935.22 10-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 2253065.28 2716.85 15-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 3599893.58 3526.31 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 15366613.94 3526.50 11-NOV-19:04 0.00 0.00 0.00 0.00 0.00
December 49199311.51 3528.59 15-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.228648E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2253065.28 2260.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 59070371.48 3529.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 83269668.45 3578.02 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 88599038.32 3594.76 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 40639000.94 3580.94 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 3828815.96 3536.70 02-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 4861835.13 3365.04 26-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4138116.41 2813.15 19-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 2533129.21 2065.62 31-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 3307994.45 2936.47 10-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 3599382.96 3303.81 15-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 5261546.50 3531.52 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 21786930.92 3530.00 15-NOV-19:04 0.00 0.00 0.00 0.00 0.00
December 98043692.85 3532.38 27-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.359869E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2533129.21 2065.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 98043692.85 3594.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.130286E+09 20901.39 24-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.110330E+09 20906.46 04-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 88511475.50 20903.01 01-MAR-09:53 0.00 0.00 0.00 0.00 0.00
April 49510989.00 20907.77 02-APR-08:54 0.00 0.00 0.00 0.00 0.00
May 44973755.18 19649.04 27-MAY-08:56 0.00 0.00 0.00 0.00 0.00
June 17180228.23 14748.60 24-JUN-18:07 0.00 0.00 0.00 0.00 0.00
July 11528059.78 12064.06 17-JUL-18:07 0.00 0.00 0.00 0.00 0.00
August 27575692.64 17597.18 13-AUG-18:07 0.00 0.00 0.00 0.00 0.00
September 29672513.80 16164.33 17-SEP-18:07 0.00 0.00 0.00 0.00 0.00
October 46710293.61 20897.03 21-OCT-21:56 0.00 0.00 0.00 0.00 0.00
November 67317887.01 20887.53 27-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 99351360.78 20909.74 15-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.722948E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11528059.78 12064.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130286E+09 20909.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 45283333.28 3475.74 25-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 55736116.98 3481.99 03-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 24618387.38 3475.34 19-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 452412.13 2595.94 19-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 323891.75 1698.54 27-MAY-18:05 0.00 0.00 0.00 0.00 0.00
June 101719.49 1186.73 15-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 609738.24 2315.64 12-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 14868.43 173.46 05-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 419075.75 2004.79 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 9685304.29 3480.55 12-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 56522220.83 3478.29 26-DEC-19:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.193767E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 56522220.83 3481.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 94143892.87 3484.70 09-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 79026631.13 3482.80 03-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 31027508.34 3484.42 15-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 1921372.80 2782.24 01-APR-21:54 0.00 0.00 0.00 0.00 0.00
May 772607.26 2710.08 28-MAY-06:55 0.00 0.00 0.00 0.00 0.00
June 52931.44 603.63 18-JUN-21:56 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 675926.58 2240.42 28-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 367172.18 2312.83 07-SEP-06:55 0.00 0.00 0.00 0.00 0.00
October 1259678.02 2179.20 13-OCT-16:55 0.00 0.00 0.00 0.00 0.00
November 14697588.96 3262.31 12-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.110434E+09 3480.41 26-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.334379E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110434E+09 3484.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 48308905.68 1019.05 25-JAN-19:03 0.00 0.00 0.00 0.00 0.00
February 39116625.32 1070.58 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 29214633.23 1082.66 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1876251.29 956.38 10-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 1695212.86 966.17 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 1572083.16 998.72 15-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1153658.21 813.90 03-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1290894.00 997.72 03-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1093766.19 860.07 15-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 1332774.54 974.43 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 15072597.35 1017.05 11-NOV-19:04 0.00 0.00 0.00 0.00 0.00
December 48968807.34 1064.98 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190696E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1093766.19 813.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 48968807.34 1082.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 67842652.74 1081.81 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 50229275.75 1088.80 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 30784191.94 1089.53 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1011443.13 953.51 12-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 1334426.73 996.49 26-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 1194423.24 961.43 18-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 759188.10 458.83 31-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1150870.26 964.94 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1369190.90 966.76 25-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 1717080.03 946.53 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 17891733.37 1067.07 13-NOV-09:52 0.00 0.00 0.00 0.00 0.00
December 72058963.41 1079.05 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.247343E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 759188.10 458.83   0.00 0.00 0.00 0.00 0.00
Maximum of Months 72058963.41 1089.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 39310883.87 4554.50 30-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 64683551.08 4160.15 03-FEB-19:05 0.00 0.00 0.00 0.00 0.00
March 45024266.90 4607.10 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 3593837.51 4651.82 19-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1728187.96 2004.26 27-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 997126.30 1948.02 13-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 859154.59 1170.48 24-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 1544191.05 1516.64 29-AUG-08:06 0.00 0.00 0.00 0.00 0.00
September 2128921.58 1975.88 05-SEP-08:06 0.00 0.00 0.00 0.00 0.00
October 1871044.90 1856.43 01-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 15103063.11 3368.51 12-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 41909630.42 3738.51 15-DEC-19:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.218754E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 859154.59 1170.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 64683551.08 4651.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.462607E+12 0.282820E+12 413594.41 07-JAN-04:00 146849.19 0.87
February 0.00 0.00 0.474154E+12 0.302561E+12 447930.10 11-FEB-20:20 183143.98 0.85
March 0.00 0.00 0.583137E+12 0.361303E+12 496798.51 09-MAR-21:50 191543.97 0.88
April 0.00 0.00 0.695680E+12 0.428198E+12 417612.81 25-APR-21:52 182094.54 1.00
May 0.00 0.00 0.896390E+12 0.499604E+12 494624.20 24-MAY-18:10 189364.63 1.00
June 0.00 0.00 0.977346E+12 0.512561E+12 491835.16 06-JUN-19:10 225125.31 1.00
July 0.00 0.00 0.103375E+13 0.543261E+12 508302.20 02-JUL-19:30 193637.48 1.00
August 0.00 0.00 0.102962E+13 0.533814E+12 470784.07 05-AUG-18:15 187103.05 1.00
September 0.00 0.00 0.966218E+12 0.513181E+12 515510.10 02-SEP-21:50 188929.36 1.00
October 0.00 0.00 0.921917E+12 0.503529E+12 470031.43 01-OCT-06:47 170607.47 1.00
November 0.00 0.00 0.748657E+12 0.408585E+12 523811.02 21-NOV-20:25 194614.08 0.95
December 0.00 0.00 0.568295E+12 0.318296E+12 540985.32 25-DEC-22:00 181034.97 0.91
                 
Annual Sum or Average 0.00 0.00 0.935776E+13 0.520771E+13       0.96
Minimum of Months 0.00 0.00 0.462607E+12 0.282820E+12 413594.41   146849.19 0.85
Maximum of Months 0.00 0.00 0.103375E+13 0.543261E+12 540985.32   225125.31 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.301691E+11 0.179484E+11 43623.15 07-JAN-09:01 18027.09 0.61
February 0.00 0.00 0.327933E+11 0.205798E+11 41142.31 11-FEB-19:02 17304.71 0.67
March 0.00 0.00 0.396844E+11 0.252332E+11 45083.14 14-MAR-08:61 17985.20 0.66
April 0.00 0.00 0.466409E+11 0.302448E+11 41272.91 25-APR-05:50 15660.11 0.79
May 0.00 0.00 0.570018E+11 0.335535E+11 48557.43 28-MAY-18:03 17368.47 0.79
June 0.00 0.00 0.615163E+11 0.336005E+11 43550.80 18-JUN-20:40 17444.57 0.79
July 0.00 0.00 0.640607E+11 0.349295E+11 46761.66 02-JUL-17:00 16453.00 0.79
August 0.00 0.00 0.650703E+11 0.348901E+11 45991.92 12-AUG-08:03 16296.77 0.79
September 0.00 0.00 0.612178E+11 0.334368E+11 44301.83 04-SEP-21:51 16433.24 0.79
October 0.00 0.00 0.586650E+11 0.335288E+11 45227.74 01-OCT-08:20 16390.72 0.79
November 0.00 0.00 0.492529E+11 0.278917E+11 47107.67 08-NOV-09:03 17156.20 0.75
December 0.00 0.00 0.380834E+11 0.213310E+11 49518.84 23-DEC-19:03 17101.19 0.68
                 
Annual Sum or Average 0.00 0.00 0.604156E+12 0.347168E+12       0.74
Minimum of Months 0.00 0.00 0.301691E+11 0.179484E+11 41142.31   15660.11 0.61
Maximum of Months 0.00 0.00 0.650703E+11 0.349295E+11 49518.84   18027.09 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.494700E+10 0.218606E+10 17580.07 07-JAN-09:01 9664.63 0.79
February 0.00 0.00 0.573341E+10 0.277229E+10 17157.23 02-FEB-09:01 10007.81 0.84
March 0.00 0.00 0.738333E+10 0.382096E+10 17702.66 19-MAR-08:62 9259.04 0.83
April 0.00 0.00 0.917336E+10 0.507204E+10 15959.44 29-APR-08:61 10961.14 0.93
May 0.00 0.00 0.107645E+11 0.609235E+10 16387.33 24-MAY-18:02 10557.53 0.95
June 0.00 0.00 0.112084E+11 0.642767E+10 15417.13 13-JUN-08:61 11321.48 0.96
July 0.00 0.00 0.125394E+11 0.747038E+10 14729.39 24-JUL-08:61 11835.06 0.96
August 0.00 0.00 0.119747E+11 0.699379E+10 17181.91 12-AUG-08:61 9977.89 0.96
September 0.00 0.00 0.116796E+11 0.683326E+10 15656.95 05-SEP-08:61 11105.53 0.96
October 0.00 0.00 0.111391E+11 0.637677E+10 16389.60 31-OCT-08:61 10580.89 0.96
November 0.00 0.00 0.816991E+10 0.417887E+10 16928.16 24-NOV-09:01 10072.07 0.91
December 0.00 0.00 0.595091E+10 0.281439E+10 17833.19 23-DEC-09:01 9446.06 0.82
                 
Annual Sum or Average 0.00 0.00 0.110664E+12 0.610388E+11       0.91
Minimum of Months 0.00 0.00 0.494700E+10 0.218606E+10 14729.39   9259.04 0.79
Maximum of Months 0.00 0.00 0.125394E+11 0.747038E+10 17833.19   11835.06 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.219749E+10 0.813995E+09 17762.11 07-JAN-09:52 9379.27 0.44
February 0.00 0.00 0.315860E+10 0.142101E+10 17581.21 17-FEB-09:21 10268.84 0.52
March 0.00 0.00 0.494762E+10 0.245024E+10 18848.89 14-MAR-08:21 8988.86 0.57
April 0.00 0.00 0.746716E+10 0.417434E+10 17823.81 22-APR-08:21 10539.19 0.72
May 0.00 0.00 0.104570E+11 0.600172E+10 17857.86 25-MAY-21:51 10240.62 0.90
June 0.00 0.00 0.112611E+11 0.652069E+10 18197.99 18-JUN-21:51 10241.71 0.94
July 0.00 0.00 0.124484E+11 0.748099E+10 17534.97 14-JUL-21:51 11245.75 0.94
August 0.00 0.00 0.116578E+11 0.673464E+10 17880.64 12-AUG-08:52 9493.57 0.94
September 0.00 0.00 0.107620E+11 0.610627E+10 17537.60 16-SEP-08:61 9821.23 0.92
October 0.00 0.00 0.949626E+10 0.508706E+10 17749.78 21-OCT-08:61 11172.47 0.89
November 0.00 0.00 0.600993E+10 0.282403E+10 17443.02 22-NOV-09:01 9955.70 0.73
December 0.00 0.00 0.326682E+10 0.142017E+10 18230.43 10-DEC-09:01 10595.75 0.48
                 
Annual Sum or Average 0.00 0.00 0.931302E+11 0.510352E+11       0.75
Minimum of Months 0.00 0.00 0.219749E+10 0.813995E+09 17443.02   8988.86 0.44
Maximum of Months 0.00 0.00 0.124484E+11 0.748099E+10 18848.89   11245.75 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.421054E+11 0.235562E+11 45419.22 01-JAN-09:51 38209.64 0.86
February 0.00 0.00 0.375442E+11 0.193836E+11 42458.06 11-FEB-14:30 36858.06 0.91
March 0.00 0.00 0.377728E+11 0.167522E+11 33492.64 04-MAR-11:35 20559.17 0.89
April 0.00 0.00 0.393916E+11 0.161006E+11 30007.33 14-APR-16:10 17090.35 0.98
May 0.00 0.00 0.451575E+11 0.179517E+11 30753.41 14-MAY-08:00 15801.24 0.99
June 0.00 0.00 0.494402E+11 0.206199E+11 31055.07 08-JUN-07:00 16314.30 1.00
July 0.00 0.00 0.547934E+11 0.244044E+11 32985.07 01-JUL-08:00 17945.55 1.00
August 0.00 0.00 0.546061E+11 0.243724E+11 33925.09 20-AUG-08:00 19920.21 1.00
September 0.00 0.00 0.605226E+11 0.313493E+11 41745.46 30-SEP-15:02 32759.58 1.00
October 0.00 0.00 0.643087E+11 0.359862E+11 45929.28 25-OCT-15:40 38551.63 1.00
November 0.00 0.00 0.536952E+11 0.291863E+11 47701.69 10-NOV-14:50 37904.23 0.98
December 0.00 0.00 0.451265E+11 0.239780E+11 46115.87 09-DEC-09:00 35506.89 0.93
                 
Annual Sum or Average 0.00 0.00 0.584464E+12 0.283641E+12       0.96
Minimum of Months 0.00 0.00 0.375442E+11 0.161006E+11 30007.33   15801.24 0.86
Maximum of Months 0.00 0.00 0.643087E+11 0.359862E+11 47701.69   38551.63 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.276543E+11 0.139493E+11 116491.33 07-JAN-09:52 63235.97 0.45
February 0.00 0.00 0.303399E+11 0.167251E+11 114969.36 17-FEB-09:21 67507.58 0.48
March 0.00 0.00 0.410519E+11 0.231075E+11 124607.93 14-MAR-08:21 57041.88 0.54
April 0.00 0.00 0.530690E+11 0.314154E+11 115863.69 22-APR-08:21 69211.45 0.65
May 0.00 0.00 0.731310E+11 0.445771E+11 118158.34 25-MAY-21:51 67739.42 0.83
June 0.00 0.00 0.794483E+11 0.503353E+11 119092.22 18-JUN-21:51 66597.17 0.87
July 0.00 0.00 0.837224E+11 0.536294E+11 112686.61 14-JUL-21:51 75051.83 0.87
August 0.00 0.00 0.783113E+11 0.481709E+11 116344.81 12-AUG-08:52 63401.45 0.86
September 0.00 0.00 0.733621E+11 0.444910E+11 119365.31 16-SEP-07:52 68815.43 0.84
October 0.00 0.00 0.656572E+11 0.377766E+11 114079.96 31-OCT-08:31 63889.03 0.79
November 0.00 0.00 0.484736E+11 0.270846E+11 114831.88 22-NOV-09:01 67061.36 0.65
December 0.00 0.00 0.323085E+11 0.168861E+11 117256.26 10-DEC-09:01 70384.47 0.50
                 
Annual Sum or Average 0.00 0.00 0.686529E+12 0.408148E+12       0.69
Minimum of Months 0.00 0.00 0.276543E+11 0.139493E+11 112686.61   57041.88 0.45
Maximum of Months 0.00 0.00 0.837224E+11 0.536294E+11 124607.93   75051.83 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.522019E+10 0.247582E+10 15552.33 07-JAN-09:01 8939.56 0.81
February 0.00 0.00 0.576966E+10 0.286237E+10 15110.73 18-FEB-09:01 9314.99 0.86
March 0.00 0.00 0.726271E+10 0.377124E+10 15964.09 19-MAR-08:62 8353.72 0.87
April 0.00 0.00 0.912394E+10 0.503180E+10 14322.12 29-APR-08:61 9913.97 0.96
May 0.00 0.00 0.107978E+11 0.616672E+10 14771.58 24-MAY-18:02 9505.33 0.97
June 0.00 0.00 0.117898E+11 0.701249E+10 12968.44 21-JUN-18:01 10878.91 0.98
July 0.00 0.00 0.128966E+11 0.795047E+10 13448.43 02-JUL-18:02 10508.40 0.98
August 0.00 0.00 0.119903E+11 0.712490E+10 15484.68 12-AUG-08:61 8990.29 0.97
September 0.00 0.00 0.120872E+11 0.732276E+10 13940.59 05-SEP-08:61 10123.97 0.97
October 0.00 0.00 0.112967E+11 0.659648E+10 14737.85 31-OCT-08:61 9553.57 0.97
November 0.00 0.00 0.824190E+10 0.437197E+10 15258.05 24-NOV-09:01 9049.98 0.93
December 0.00 0.00 0.556030E+10 0.264730E+10 16080.75 23-DEC-09:01 8508.13 0.81
                 
Annual Sum or Average 0.00 0.00 0.112037E+12 0.633343E+11       0.92
Minimum of Months 0.00 0.00 0.522019E+10 0.247582E+10 12968.44   8353.72 0.81
Maximum of Months 0.00 0.00 0.128966E+11 0.795047E+10 16080.75   10878.91 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.245603E+10 0.102150E+10 16109.48 07-JAN-09:52 8596.27 0.45
February 0.00 0.00 0.312799E+10 0.142200E+10 16192.46 17-FEB-09:21 9812.54 0.55
March 0.00 0.00 0.486827E+10 0.243221E+10 16952.80 14-MAR-08:21 8056.06 0.60
April 0.00 0.00 0.739940E+10 0.409799E+10 16671.67 15-APR-08:31 10935.24 0.74
May 0.00 0.00 0.104706E+11 0.604211E+10 16385.95 07-MAY-08:11 11043.62 0.91
June 0.00 0.00 0.118304E+11 0.711420E+10 17018.17 13-JUN-07:51 11045.14 0.95
July 0.00 0.00 0.127974E+11 0.796411E+10 15941.78 14-JUL-21:51 10259.53 0.95
August 0.00 0.00 0.116755E+11 0.685414E+10 16312.92 29-AUG-07:53 9836.61 0.95
September 0.00 0.00 0.111620E+11 0.649373E+10 16744.43 16-SEP-07:52 9738.88 0.93
October 0.00 0.00 0.964400E+10 0.531888E+10 16563.40 26-OCT-08:61 10778.30 0.90
November 0.00 0.00 0.601707E+10 0.299629E+10 17001.36 22-NOV-08:51 10650.42 0.74
December 0.00 0.00 0.297242E+10 0.131044E+10 16651.15 10-DEC-09:01 9919.49 0.46
                 
Annual Sum or Average 0.00 0.00 0.944212E+11 0.530676E+11       0.76
Minimum of Months 0.00 0.00 0.245603E+10 0.102150E+10 15941.78   8056.06 0.45
Maximum of Months 0.00 0.00 0.127974E+11 0.796411E+10 17018.17   11045.14 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.124019E+10 0.575920E+09 5015.98 07-JAN-09:01 2494.13 0.71
February 0.00 0.00 0.148909E+10 0.750900E+09 4843.54 02-FEB-09:01 2636.15 0.81
March 0.00 0.00 0.193542E+10 0.101410E+10 5024.59 19-MAR-08:62 2406.19 0.80
April 0.00 0.00 0.238979E+10 0.132368E+10 4566.43 16-APR-08:61 2842.43 0.94
May 0.00 0.00 0.283122E+10 0.158099E+10 4589.88 24-MAY-18:02 2823.49 0.96
June 0.00 0.00 0.293033E+10 0.163879E+10 4446.10 13-JUN-08:61 2942.52 0.96
July 0.00 0.00 0.327571E+10 0.192753E+10 4221.48 24-JUL-08:61 3114.93 0.96
August 0.00 0.00 0.311334E+10 0.177767E+10 4985.73 12-AUG-08:61 2518.11 0.96
September 0.00 0.00 0.300621E+10 0.172137E+10 4553.39 05-SEP-08:61 2849.12 0.96
October 0.00 0.00 0.282335E+10 0.158332E+10 4761.68 31-OCT-08:61 2693.68 0.96
November 0.00 0.00 0.206081E+10 0.104274E+10 4848.23 24-NOV-09:01 2505.02 0.89
December 0.00 0.00 0.151131E+10 0.731096E+09 5098.08 23-DEC-09:01 2422.56 0.75
                 
Annual Sum or Average 0.00 0.00 0.286068E+11 0.156681E+11       0.89
Minimum of Months 0.00 0.00 0.124019E+10 0.575920E+09 4221.48   2406.19 0.71
Maximum of Months 0.00 0.00 0.327571E+10 0.192753E+10 5098.08   3114.93 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.543708E+09 0.210046E+09 5050.68 07-JAN-09:52 2484.63 0.39
February 0.00 0.00 0.837418E+09 0.390040E+09 5003.31 17-FEB-09:21 2716.43 0.50
March 0.00 0.00 0.132136E+10 0.660759E+09 5357.83 14-MAR-08:21 2334.25 0.56
April 0.00 0.00 0.198712E+10 0.111520E+10 5096.82 23-APR-07:52 2916.62 0.73
May 0.00 0.00 0.276342E+10 0.157018E+10 5127.10 24-MAY-20:51 2923.58 0.90
June 0.00 0.00 0.294708E+10 0.166596E+10 5202.38 18-JUN-21:51 2757.04 0.94
July 0.00 0.00 0.325845E+10 0.193494E+10 5014.86 14-JUL-21:51 3109.06 0.94
August 0.00 0.00 0.303671E+10 0.171492E+10 5059.16 12-AUG-08:52 2454.73 0.94
September 0.00 0.00 0.278067E+10 0.153718E+10 5002.36 16-SEP-08:61 2535.94 0.92
October 0.00 0.00 0.241493E+10 0.124068E+10 5025.28 21-OCT-08:61 2907.72 0.89
November 0.00 0.00 0.152715E+10 0.695534E+09 4949.60 10-NOV-09:01 2584.81 0.72
December 0.00 0.00 0.842019E+09 0.365901E+09 5221.80 10-DEC-09:01 2705.36 0.45
                 
Annual Sum or Average 0.00 0.00 0.242600E+11 0.131013E+11       0.74
Minimum of Months 0.00 0.00 0.543708E+09 0.210046E+09 4949.60   2334.25 0.39
Maximum of Months 0.00 0.00 0.325845E+10 0.193494E+10 5357.83   3109.06 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.111233E+11 0.693501E+10 20116.54 07-JAN-09:01 10517.49 0.85
February 0.00 0.00 0.106508E+11 0.643937E+10 19574.06 02-FEB-09:01 10949.19 0.88
March 0.00 0.00 0.112571E+11 0.653148E+10 20721.28 19-MAR-08:62 9866.99 0.85
April 0.00 0.00 0.118630E+11 0.675383E+10 18615.93 16-APR-08:61 11628.23 0.93
May 0.00 0.00 0.134554E+11 0.767002E+10 19616.82 24-MAY-18:02 10858.88 0.95
June 0.00 0.00 0.142295E+11 0.842884E+10 17702.79 13-JUN-08:61 12337.12 0.96
July 0.00 0.00 0.155396E+11 0.954187E+10 17870.04 02-JUL-18:02 12199.93 0.96
August 0.00 0.00 0.153462E+11 0.943367E+10 20540.14 12-AUG-08:61 10181.86 0.95
September 0.00 0.00 0.163568E+11 0.104888E+11 18265.43 05-SEP-08:61 11878.40 0.96
October 0.00 0.00 0.169445E+11 0.109782E+11 19373.25 31-OCT-08:61 11075.30 0.96
November 0.00 0.00 0.141893E+11 0.893606E+10 20019.19 24-NOV-09:01 10288.01 0.94
December 0.00 0.00 0.120374E+11 0.736726E+10 20561.61 23-DEC-09:01 10150.66 0.88
                 
Annual Sum or Average 0.00 0.00 0.162993E+12 0.995044E+11       0.92
Minimum of Months 0.00 0.00 0.106508E+11 0.643937E+10 17702.79   9866.99 0.85
Maximum of Months 0.00 0.00 0.169445E+11 0.109782E+11 20721.28   12337.12 0.96



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 2654.53 42367.28 31-JAN-16:04
February 0.00 0.00 01-FEB-00:03 2320.20 49677.34 04-FEB-09:05
March 0.00 0.00 01-MAR-00:05 2070.31 48940.86 20-MAR-08:05
April 0.00 0.00 01-APR-00:10 790.85 24611.74 02-APR-15:07
May 0.00 0.00 01-MAY-00:10 642.12 24138.10 21-MAY-18:07
June 0.00 0.00 01-JUN-00:10 493.38 18328.82 24-JUN-18:07
July 0.00 0.00 01-JUL-00:10 416.25 18014.85 17-JUL-18:07
August 0.00 0.00 01-AUG-00:10 583.09 25872.20 06-AUG-18:07
September 0.00 0.00 01-SEP-00:10 486.95 25450.39 04-SEP-18:07
October 0.00 0.00 01-OCT-00:10 636.80 24400.68 15-OCT-15:07
November 0.00 0.00 01-NOV-00:10 1133.68 34155.65 27-NOV-09:05
December 0.00 0.00 01-DEC-00:03 2568.19 49068.47 28-DEC-16:04
             
Annual Sum or Average 0.00     1229.65    
Minimum of Months 0.00 0.00   416.25 18014.85  
Maximum of Months 0.00 0.00   2654.53 49677.34  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 223707.50 585736.39 29-JAN-22:53 0.00 0.00 01-JAN-00:05
February 253633.06 617422.20 11-FEB-16:03 0.00 0.00 01-FEB-00:03
March 279844.20 687317.09 09-MAR-22:52 0.00 0.00 01-MAR-00:05
April 344472.40 618581.49 01-APR-15:03 0.00 0.00 01-APR-00:10
May 426462.62 648678.35 28-MAY-15:03 0.00 0.00 01-MAY-00:10
June 479441.62 707719.15 08-JUN-18:03 0.00 0.00 01-JUN-00:10
July 492138.90 710966.80 13-JUL-18:03 0.00 0.00 01-JUL-00:10
August 487401.00 681871.73 04-AUG-18:03 0.00 0.00 01-AUG-00:10
September 477596.02 684546.50 18-SEP-18:03 0.00 0.00 01-SEP-00:10
October 441812.25 672169.04 30-OCT-18:03 0.00 0.00 01-OCT-00:10
November 368445.87 657374.16 30-NOV-19:03 0.00 0.00 01-NOV-00:10
December 270652.43 747341.63 25-DEC-22:52 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 379405.45     0.00    
Minimum of Months 223707.50 585736.39   0.00 0.00  
Maximum of Months 492138.90 747341.63   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 20264.98 40750.17 20-JAN-07:18
February 0.00 0.00 01-FEB-00:03 20086.42 40566.66 01-FEB-07:10
March 0.00 0.00 01-MAR-00:05 19531.25 39795.33 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 18691.50 38057.01 04-APR-06:10
May 0.00 0.00 01-MAY-00:10 17836.25 36345.53 01-MAY-06:15
June 0.00 0.00 01-JUN-00:10 17184.27 34665.10 02-JUN-06:07
July 0.00 0.00 01-JUL-00:10 16893.65 33787.31 06-JUL-06:59
August 0.00 0.00 01-AUG-00:10 17092.48 34448.29 31-AUG-06:07
September 0.00 0.00 01-SEP-00:10 17671.67 35962.73 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 18497.54 37874.73 31-OCT-06:10
November 0.00 0.00 01-NOV-00:10 19353.25 39421.91 30-NOV-07:10
December 0.00 0.00 01-DEC-00:03 19999.91 40420.39 28-DEC-07:15
             
Annual Sum or Average 0.00     18583.67    
Minimum of Months 0.00 0.00   16893.65 33787.31  
Maximum of Months 0.00 0.00   20264.98 40750.17  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.69 1299.30 01-JAN-09:51 0.87
February 0.244774E+10 0.69 1299.30 01-FEB-09:52 0.87
March 0.271000E+10 0.69 1299.30 01-MAR-09:51 0.87
April 0.262258E+10 0.69 1299.30 01-APR-08:51 0.87
May 0.271000E+10 0.69 1299.30 01-MAY-08:31 0.87
June 0.262258E+10 0.69 1299.30 01-JUN-18:05 0.87
July 0.271000E+10 0.69 1299.30 01-JUL-08:05 0.87
August 0.271000E+10 0.69 1299.30 01-AUG-08:05 0.87
September 0.262258E+10 0.69 1299.30 02-SEP-08:05 0.87
October 0.271000E+10 0.69 1299.30 01-OCT-08:53 0.87
November 0.262258E+10 0.69 1299.30 01-NOV-08:53 0.87
December 0.271000E+10 0.69 1299.30 01-DEC-09:21 0.87
           
Annual Sum or Average 0.319080E+11 0.69      
Minimum of Months 0.244774E+10 0.69 1299.30   0.87
Maximum of Months 0.271000E+10 0.69 1299.30   0.87



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.280519E+11 0.71 13374.47 02-JAN-21:10 0.81
February 0.255479E+11 0.71 13248.41 17-FEB-21:20 0.80
March 0.285389E+11 0.71 13975.06 27-MAR-20:10 0.83
April 0.281773E+11 0.72 14929.31 14-APR-20:20 0.86
May 0.298606E+11 0.73 15838.26 22-MAY-20:10 0.89
June 0.296181E+11 0.74 17115.39 29-JUN-20:10 0.93
July 0.310276E+11 0.74 17906.87 28-JUL-20:10 0.95
August 0.304861E+11 0.74 17333.21 21-AUG-20:10 0.94
September 0.297169E+11 0.74 17509.73 18-SEP-20:10 0.94
October 0.297986E+11 0.73 16169.70 06-OCT-20:10 0.90
November 0.279992E+11 0.72 14784.72 03-NOV-21:00 0.85
December 0.281979E+11 0.71 13842.44 08-DEC-21:30 0.82
           
Annual Sum or Average 0.347021E+12 0.72      
Minimum of Months 0.255479E+11 0.71 13248.41   0.80
Maximum of Months 0.310276E+11 0.74 17906.87   0.95



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.26 76.61 01-JAN-00:05 0.26
February 0.185347E+09 0.26 76.61 01-FEB-00:03 0.26
March 0.205205E+09 0.26 76.61 01-MAR-00:05 0.26
April 0.198586E+09 0.26 76.61 01-APR-00:10 0.26
May 0.205205E+09 0.26 76.61 01-MAY-00:10 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:10 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:10 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:10 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.26 76.61 01-NOV-00:10 0.26
December 0.205205E+09 0.26 76.61 01-DEC-00:03 0.26
           
Annual Sum or Average 0.241613E+10 0.26      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.26 76.61   0.26



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 -0.0
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 -0.0
September 0.00 -0.0 0.00 01-SEP-00:10 -0.0
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.26
February 0.105030E+10 0.19 612.92 01-FEB-07:03 0.26
March 0.116283E+10 0.19 612.92 01-MAR-07:03 0.26
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.26
May 0.116283E+10 0.19 612.92 01-MAY-06:03 0.26
June 0.112532E+10 0.19 612.92 01-JUN-06:03 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:03 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:03 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:03 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:03 0.26
December 0.116283E+10 0.19 612.92 01-DEC-07:03 0.26
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.26



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.210605E+09 0.49 689.88 01-JAN-09:01 0.57
February 0.240990E+09 0.51 689.88 01-FEB-09:02 0.57
March 0.300289E+09 0.51 689.88 01-MAR-09:02 0.57
April 0.371456E+09 0.53 689.88 01-APR-08:61 0.57
May 0.425604E+09 0.55 689.88 01-MAY-08:62 0.57
June 0.437524E+09 0.55 689.88 01-JUN-08:61 0.57
July 0.497704E+09 0.55 689.88 01-JUL-08:62 0.57
August 0.470431E+09 0.55 689.88 01-AUG-08:62 0.57
September 0.460740E+09 0.55 689.88 01-SEP-08:61 0.57
October 0.436659E+09 0.55 689.88 01-OCT-08:61 0.57
November 0.317807E+09 0.53 689.88 01-NOV-08:62 0.57
December 0.243215E+09 0.50 689.88 01-DEC-09:01 0.57
           
Annual Sum or Average 0.441302E+10 0.53      
Minimum of Months 0.210605E+09 0.49 689.88   0.57
Maximum of Months 0.497704E+09 0.55 689.88   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103552E+09 0.31 697.45 01-JAN-09:51 0.57
February 0.139832E+09 0.33 697.45 01-FEB-16:01 0.57
March 0.203226E+09 0.36 697.45 01-MAR-09:51 0.57
April 0.301872E+09 0.41 697.45 01-APR-08:51 0.57
May 0.414893E+09 0.52 697.45 01-MAY-08:31 0.57
June 0.441178E+09 0.54 697.45 01-JUN-08:61 0.57
July 0.495815E+09 0.54 697.45 01-JUL-08:62 0.57
August 0.456514E+09 0.54 697.45 01-AUG-08:62 0.57
September 0.420029E+09 0.53 697.45 01-SEP-08:61 0.57
October 0.367334E+09 0.51 697.45 01-OCT-08:51 0.57
November 0.232517E+09 0.43 697.45 01-NOV-08:51 0.57
December 0.142936E+09 0.33 697.45 01-DEC-09:21 0.57
           
Annual Sum or Average 0.371970E+10 0.44      
Minimum of Months 0.103552E+09 0.31 697.45   0.57
Maximum of Months 0.495815E+09 0.54 697.45   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138173E+10 0.54 1770.91 02-JAN-14:30 0.57
February 0.123929E+10 0.54 1218.48 11-FEB-14:30 0.57
March 0.123680E+10 0.53 999.66 02-MAR-14:30 0.57
April 0.127001E+10 0.56 882.64 15-APR-17:20 0.57
May 0.139789E+10 0.57 854.99 22-MAY-20:20 0.57
June 0.148468E+10 0.57 893.15 03-JUN-21:00 0.57
July 0.163562E+10 0.57 963.82 29-JUL-19:10 0.57
August 0.162672E+10 0.57 943.69 20-AUG-20:10 0.57
September 0.179678E+10 0.57 1172.16 30-SEP-13:50 0.57
October 0.193376E+10 0.57 1774.74 25-OCT-12:30 0.57
November 0.166702E+10 0.56 1800.86 07-NOV-13:40 0.57
December 0.145574E+10 0.54 1873.15 03-DEC-13:50 0.57
           
Annual Sum or Average 0.181260E+11 0.56      
Minimum of Months 0.123680E+10 0.53 854.99   0.57
Maximum of Months 0.193376E+10 0.57 1873.15   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.110107E+10 0.28 4553.07 01-JAN-09:51 0.57
February 0.122269E+10 0.29 4553.07 01-FEB-09:52 0.57
March 0.166555E+10 0.32 4553.07 01-MAR-09:51 0.57
April 0.217712E+10 0.37 4553.07 01-APR-08:51 0.57
May 0.301095E+10 0.47 4553.07 01-MAY-08:31 0.57
June 0.325946E+10 0.50 4553.07 01-JUN-08:61 0.57
July 0.344776E+10 0.50 4553.07 01-JUL-08:62 0.57
August 0.317141E+10 0.49 4553.07 01-AUG-08:62 0.57
September 0.298963E+10 0.48 4553.07 01-SEP-08:61 0.57
October 0.264744E+10 0.46 4553.07 01-OCT-08:51 0.57
November 0.191200E+10 0.38 4553.07 01-NOV-08:51 0.57
December 0.126956E+10 0.30 4553.07 01-DEC-09:21 0.57
           
Annual Sum or Average 0.278746E+11 0.40      
Minimum of Months 0.110107E+10 0.28 4553.07   0.57
Maximum of Months 0.344776E+10 0.50 4553.07   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.217131E+09 0.51 618.84 01-JAN-09:01 0.57
February 0.236353E+09 0.52 618.84 01-FEB-09:02 0.57
March 0.288970E+09 0.53 618.84 01-MAR-09:02 0.57
April 0.364598E+09 0.55 618.84 01-APR-08:61 0.57
May 0.428490E+09 0.56 618.84 01-MAY-08:62 0.57
June 0.472033E+09 0.56 618.84 01-JUN-08:61 0.57
July 0.518918E+09 0.56 618.84 01-JUL-08:62 0.57
August 0.475177E+09 0.55 618.84 01-AUG-08:62 0.57
September 0.485934E+09 0.56 618.84 01-SEP-08:61 0.57
October 0.448994E+09 0.56 618.84 01-OCT-08:61 0.57
November 0.322058E+09 0.54 618.84 01-NOV-08:62 0.57
December 0.225207E+09 0.50 618.84 01-DEC-09:01 0.57
           
Annual Sum or Average 0.448386E+10 0.54      
Minimum of Months 0.217131E+09 0.50 618.84   0.57
Maximum of Months 0.518918E+09 0.56 618.84   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.111456E+09 0.31 623.99 01-JAN-09:51 0.57
February 0.133813E+09 0.34 623.99 01-FEB-09:52 0.57
March 0.195867E+09 0.37 623.99 01-MAR-09:51 0.57
April 0.298507E+09 0.42 623.99 01-APR-08:51 0.57
May 0.419090E+09 0.52 623.99 01-MAY-08:31 0.57
June 0.475943E+09 0.55 623.99 01-JUN-08:61 0.57
July 0.516663E+09 0.54 623.99 01-JUL-08:62 0.57
August 0.461854E+09 0.54 623.99 01-AUG-08:62 0.57
September 0.447522E+09 0.53 623.99 01-SEP-08:61 0.57
October 0.375461E+09 0.52 623.99 01-OCT-08:51 0.57
November 0.230083E+09 0.44 623.99 01-NOV-08:51 0.57
December 0.129264E+09 0.32 623.99 01-DEC-09:21 0.57
           
Annual Sum or Average 0.379552E+10 0.45      
Minimum of Months 0.111456E+09 0.31 623.99   0.57
Maximum of Months 0.516663E+09 0.55 623.99   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 58143477.12 0.50 189.92 01-JAN-09:01 0.57
February 66163763.77 0.52 189.92 01-FEB-09:02 0.57
March 82390135.03 0.52 189.92 01-MAR-16:01 0.57
April 99400534.36 0.54 189.92 01-APR-08:61 0.57
May 0.114264E+09 0.55 189.92 01-MAY-08:62 0.57
June 0.115518E+09 0.55 189.92 01-JUN-08:61 0.57
July 0.131224E+09 0.55 189.92 01-JUL-08:62 0.57
August 0.124165E+09 0.55 189.92 01-AUG-08:62 0.57
September 0.119795E+09 0.55 189.92 01-SEP-08:61 0.57
October 0.112238E+09 0.55 189.92 01-OCT-08:61 0.57
November 82722191.71 0.53 189.92 01-NOV-08:62 0.57
December 66589219.69 0.51 189.92 01-DEC-09:01 0.57
           
Annual Sum or Average 0.117261E+10 0.53      
Minimum of Months 58143477.12 0.50 189.92   0.57
Maximum of Months 0.131224E+09 0.55 189.92   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 31138323.29 0.32 191.74 01-JAN-09:51 0.57
February 40456905.61 0.34 191.74 01-FEB-16:01 0.57
March 57246160.69 0.36 191.74 01-MAR-16:01 0.57
April 81854217.39 0.42 191.74 01-APR-08:51 0.57
May 0.111391E+09 0.52 191.74 01-MAY-08:31 0.57
June 0.116594E+09 0.54 191.74 01-JUN-08:61 0.57
July 0.130910E+09 0.54 191.74 01-JUL-08:62 0.57
August 0.120436E+09 0.54 191.74 01-AUG-08:62 0.57
September 0.109468E+09 0.53 191.74 01-SEP-08:61 0.57
October 95090521.82 0.51 191.74 01-OCT-08:51 0.57
November 61565638.07 0.43 191.74 01-NOV-08:51 0.57
December 41825515.76 0.34 191.74 01-DEC-09:21 0.57
           
Annual Sum or Average 0.997976E+09 0.45      
Minimum of Months 31138323.29 0.32 191.74   0.57
Maximum of Months 0.130910E+09 0.54 191.74   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.477745E+09 0.53 763.41 01-JAN-09:01 0.57
February 0.453405E+09 0.53 763.41 01-FEB-09:02 0.57
March 0.460098E+09 0.53 763.41 01-MAR-09:02 0.57
April 0.476582E+09 0.54 763.41 01-APR-08:61 0.57
May 0.533287E+09 0.54 763.41 01-MAY-08:62 0.57
June 0.565987E+09 0.55 763.41 01-JUN-08:61 0.57
July 0.623628E+09 0.55 763.41 01-JUL-08:62 0.57
August 0.614988E+09 0.55 763.41 01-AUG-08:62 0.57
September 0.679543E+09 0.55 763.41 01-SEP-08:61 0.57
October 0.716868E+09 0.55 763.41 01-OCT-08:61 0.57
November 0.597742E+09 0.54 763.41 01-NOV-08:62 0.57
December 0.504749E+09 0.53 763.41 01-DEC-09:01 0.57
           
Annual Sum or Average 0.670462E+10 0.54      
Minimum of Months 0.453405E+09 0.53 763.41   0.57
Maximum of Months 0.716868E+09 0.55 763.41   0.57



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 55823360.48 50241024.43 232.67 31-JAN-16:04 209.40 209.40 25.26 0.29
February 43822915.50 39440623.95 310.61 04-FEB-09:05 279.55 279.55 32.41 0.43
March 42379966.00 38141969.40 288.67 20-MAR-08:05 259.81 259.81 29.84 0.39
April 15581987.12 14023788.41 149.98 20-APR-15:07 134.98 134.98 26.47 0.17
May 12747052.53 11472347.28 149.52 05-MAY-18:07 134.57 134.57 29.37 0.17
June 9254470.04 8329023.04 137.08 24-JUN-18:07 123.37 123.37 31.82 0.16
July 7960157.50 7164141.75 121.22 17-JUL-18:07 109.10 109.10 28.26 0.14
August 11286514.12 10157862.71 158.11 28-AUG-08:56 142.30 142.30 30.61 0.18
September 9147221.66 8232499.50 144.20 04-SEP-18:07 129.78 129.78 23.13 0.17
October 12764279.73 11487851.76 152.46 15-OCT-15:07 137.21 137.21 26.79 0.18
November 22923016.23 20630714.61 221.17 27-NOV-09:05 199.05 199.05 30.11 0.27
December 53815178.28 48433660.45 248.79 28-DEC-16:04 223.92 223.92 23.11 0.32
                 
Annual Sum or Average 0.297506E+09 0.267756E+09            
Minimum of Months 7960157.50 7164141.75 121.22   109.10 109.10 23.11 0.14
Maximum of Months 55823360.48 50241024.43 310.61   279.55 279.55 32.41 0.43



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.557625E+09 0.501862E+09 907.35 29-JAN-22:51 816.62 816.62 6.72 15.75
February 0.584943E+09 0.526449E+09 987.65 11-FEB-16:02 888.89 888.89 6.72 16.34
March 0.771172E+09 0.694055E+09 1250.27 09-MAR-22:52 1125.24 1125.24 6.72 18.06
April 0.977503E+09 0.879753E+09 1054.84 14-APR-18:02 949.35 949.35 6.72 16.80
May 0.147229E+10 0.132506E+10 1151.44 31-MAY-18:02 1036.30 1036.30 6.72 17.44
June 0.178860E+10 0.160974E+10 1389.01 08-JUN-18:02 1250.11 1250.11 6.72 18.88
July 0.194132E+10 0.174719E+10 1443.97 26-JUL-18:02 1299.58 1299.58 6.72 19.19
August 0.189863E+10 0.170876E+10 1304.58 15-AUG-18:02 1174.12 1174.12 6.72 18.39
September 0.178513E+10 0.160662E+10 1367.37 02-SEP-21:50 1230.63 1230.63 6.72 18.75
October 0.159841E+10 0.143857E+10 1231.62 30-OCT-18:02 1108.46 1108.46 6.72 17.95
November 0.118085E+10 0.106277E+10 1154.92 04-NOV-18:02 1039.43 1039.43 6.72 17.46
December 0.762307E+09 0.686077E+09 1484.82 25-DEC-22:52 1336.34 1336.34 6.72 19.41
                 
Annual Sum or Average 0.153188E+11 0.137869E+11            
Minimum of Months 0.557625E+09 0.501862E+09 907.35   816.62 816.62 6.72 15.75
Maximum of Months 0.194132E+10 0.174719E+10 1484.82   1336.34 1336.34 6.72 19.41



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.982328E+10 0.884095E+10 3687.42 01-JAN-00:05 3318.68 3318.68 9.42 32.62
February 0.881219E+10 0.793097E+10 3687.42 01-FEB-00:03 3318.68 3318.68 7.33 32.62
March 0.983655E+10 0.885290E+10 3687.42 01-MAR-00:05 3318.68 3318.68 7.72 32.62
April 0.955779E+10 0.860201E+10 3687.42 01-APR-00:10 3318.68 3318.68 9.25 32.62
May 0.987638E+10 0.888874E+10 3687.42 01-MAY-00:10 3318.68 3318.68 9.69 32.62
June 0.955779E+10 0.860201E+10 3687.42 01-JUN-00:10 3318.68 3318.68 10.14 32.62
July 0.987638E+10 0.888874E+10 3687.42 01-JUL-00:10 3318.68 3318.68 10.00 32.62
August 0.987638E+10 0.888874E+10 3687.42 01-AUG-00:10 3318.68 3318.68 10.39 32.62
September 0.955779E+10 0.860201E+10 3687.42 01-SEP-00:10 3318.68 3318.68 9.99 32.62
October 0.987638E+10 0.888874E+10 3687.42 01-OCT-00:10 3318.68 3318.68 10.04 32.62
November 0.955779E+10 0.860201E+10 3687.42 01-NOV-00:10 3318.68 3318.68 10.02 32.62
December 0.987638E+10 0.888874E+10 3687.42 01-DEC-00:03 3318.68 3318.68 9.49 32.62
                 
Annual Sum or Average 0.116085E+12 0.104477E+12            
Minimum of Months 0.881219E+10 0.793097E+10 3687.42   3318.68 3318.68 7.33 32.62
Maximum of Months 0.987638E+10 0.888874E+10 3687.42   3318.68 3318.68 10.39 32.62



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 51.42 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 51.86 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 51.60 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 54.04 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 54.01 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 54.75 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.36 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.19 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.27 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.28 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 54.23 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 51.83 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 51.42 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.75 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 24.66 24.66 2654.53 42367.28 31-JAN-16:04
February 0.00 0.00 01-FEB-00:03 25.59 60.00 2320.20 49677.34 04-FEB-09:05
March 0.00 0.00 01-MAR-00:05 29.52 29.52 2070.31 48940.86 20-MAR-08:05
April 0.00 0.00 01-APR-00:10 31.42 60.00 790.85 24611.74 02-APR-15:07
May 0.00 0.00 01-MAY-00:10 26.31 60.00 642.12 24138.10 21-MAY-18:07
June 0.00 0.00 01-JUN-00:10 29.27 60.00 493.38 18328.82 24-JUN-18:07
July 0.00 0.00 01-JUL-00:10 28.45 28.45 416.25 18014.85 17-JUL-18:07
August 0.00 0.00 01-AUG-00:10 29.08 60.00 583.09 25872.20 06-AUG-18:07
September 0.00 0.00 01-SEP-00:10 28.79 60.00 486.95 25450.39 04-SEP-18:07
October 0.00 0.00 01-OCT-00:10 30.47 30.47 636.80 24400.68 15-OCT-15:07
November 0.00 0.00 01-NOV-00:10 25.94 60.00 1133.68 34155.65 27-NOV-09:05
December 0.00 0.00 01-DEC-00:03 28.84 28.84 2568.19 49068.47 28-DEC-16:04
                 
Annual Sum or Average 0.00         1229.65    
Minimum of Months 0.00 0.00   24.66 24.66 416.25 18014.85  
Maximum of Months 0.00 0.00   31.42 60.00 2654.53 49677.34  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 223707.50 585736.39 29-JAN-22:53 10.99 6.70 0.00 0.00 01-JAN-00:05
February 253633.06 617422.20 11-FEB-16:03 11.22 6.70 0.00 0.00 01-FEB-00:03
March 279844.20 687317.09 09-MAR-22:52 11.73 6.70 0.00 0.00 01-MAR-00:05
April 344472.40 618581.49 01-APR-15:03 11.23 6.70 0.00 0.00 01-APR-00:10
May 426462.62 648678.35 28-MAY-15:03 11.45 6.70 0.00 0.00 01-MAY-00:10
June 479441.62 707719.15 08-JUN-18:03 11.88 6.70 0.00 0.00 01-JUN-00:10
July 492138.90 710966.80 13-JUL-18:03 11.90 6.70 0.00 0.00 01-JUL-00:10
August 487401.00 681871.73 04-AUG-18:03 11.69 6.70 0.00 0.00 01-AUG-00:10
September 477596.02 684546.50 18-SEP-18:03 11.71 6.70 0.00 0.00 01-SEP-00:10
October 441812.25 672169.04 30-OCT-18:03 11.62 6.70 0.00 0.00 01-OCT-00:10
November 368445.87 657374.16 30-NOV-19:03 11.51 6.70 0.00 0.00 01-NOV-00:10
December 270652.43 747341.63 25-DEC-22:52 12.17 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 379405.45         0.00    
Minimum of Months 223707.50 585736.39   10.99 6.70 0.00 0.00  
Maximum of Months 492138.90 747341.63   12.17 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 51.42 59.78 20264.98 40750.17 20-JAN-07:18
February 0.00 0.00 01-FEB-00:03 51.86 59.31 20086.42 40566.66 01-FEB-07:10
March 0.00 0.00 01-MAR-00:05 51.60 58.31 19531.25 39795.33 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 54.04 58.92 18691.50 38057.01 04-APR-06:10
May 0.00 0.00 01-MAY-00:10 54.01 58.58 17836.25 36345.53 01-MAY-06:15
June 0.00 0.00 01-JUN-00:10 54.75 59.28 17184.27 34665.10 02-JUN-06:07
July 0.00 0.00 01-JUL-00:10 54.36 58.70 16893.65 33787.31 06-JUL-06:59
August 0.00 0.00 01-AUG-00:10 54.19 58.35 17092.48 34448.29 31-AUG-06:07
September 0.00 0.00 01-SEP-00:10 54.27 58.72 17671.67 35962.73 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 53.28 58.30 18497.54 37874.73 31-OCT-06:10
November 0.00 0.00 01-NOV-00:10 54.23 59.11 19353.25 39421.91 30-NOV-07:10
December 0.00 0.00 01-DEC-00:03 51.83 58.68 19999.91 40420.39 28-DEC-07:15
                 
Annual Sum or Average 0.00         18583.67    
Minimum of Months 0.00 0.00   51.42 58.30 16893.65 33787.31  
Maximum of Months 0.00 0.00   54.75 59.78 20264.98 40750.17  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.661664E+10 0.00 0.462607E+12 0.280519E+11 0.00 0.00
February 0.511066E+10 0.00 0.474154E+12 0.255479E+11 0.00 0.00
March 0.526706E+10 0.00 0.583137E+12 0.285389E+11 0.00 0.00
April 0.200141E+10 0.00 0.695680E+12 0.281773E+11 0.00 0.00
May 0.167018E+10 0.00 0.896390E+12 0.298606E+11 0.00 0.00
June 0.125875E+10 0.00 0.977346E+12 0.296181E+11 0.00 0.00
July 0.110324E+10 0.00 0.103375E+13 0.310276E+11 0.00 0.00
August 0.153461E+10 0.00 0.102962E+13 0.304861E+11 0.00 0.00
September 0.123067E+10 0.00 0.966218E+12 0.297169E+11 0.00 0.00
October 0.165942E+10 0.00 0.921917E+12 0.297986E+11 0.00 0.00
November 0.278441E+10 0.00 0.748657E+12 0.279992E+11 0.00 0.00
December 0.635934E+10 0.00 0.568295E+12 0.281979E+11 0.00 0.00
             
Annual Sum or Average 0.365964E+11 0.00 0.935776E+13 0.347021E+12 0.00 0.00
Minimum of Months 0.110324E+10 0.00 0.462607E+12 0.255479E+11 0.00 0.00
Maximum of Months 0.661664E+10 0.00 0.103375E+13 0.310276E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 5672.26 0.00 0.301691E+11 0.271000E+10 0.00 0.00
February 4767.73 0.00 0.327933E+11 0.244774E+10 0.00 0.00
March 6114.83 0.00 0.396844E+11 0.271000E+10 0.00 0.00
April 7458.03 0.00 0.466409E+11 0.262258E+10 0.00 0.00
May 8642.27 0.00 0.570018E+11 0.271000E+10 0.00 0.00
June 9815.10 0.00 0.615163E+11 0.262258E+10 0.00 0.00
July 9777.18 0.00 0.640607E+11 0.271000E+10 0.00 0.00
August 8135.53 0.00 0.650703E+11 0.271000E+10 0.00 0.00
September 7395.81 0.00 0.612178E+11 0.262258E+10 0.00 0.00
October 7482.63 0.00 0.586650E+11 0.271000E+10 0.00 0.00
November 9666.95 0.00 0.492529E+11 0.262258E+10 0.00 0.00
December 9391.56 0.00 0.380834E+11 0.271000E+10 0.00 0.00
             
Annual Sum or Average 94319.88 0.00 0.604156E+12 0.319080E+11 0.00 0.00
Minimum of Months 4767.73 0.00 0.301691E+11 0.244774E+10 0.00 0.00
Maximum of Months 9815.10 0.00 0.650703E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.280519E+11 0.462607E+12 0.661664E+10 0.209864E+10 0.565541E+11 0.00 0.00 0.00
February 0.255479E+11 0.474154E+12 0.511066E+10 0.570083E+10 0.722431E+11 0.00 0.00 0.00
March 0.285389E+11 0.583137E+12 0.526706E+10 0.397420E+10 0.123998E+12 0.00 0.00 0.00
April 0.281773E+11 0.695680E+12 0.200141E+10 0.498220E+09 0.163032E+12 0.00 0.00 0.00
May 0.298606E+11 0.896390E+12 0.167018E+10 0.00 0.362928E+12 0.00 0.00 0.00
June 0.296181E+11 0.977346E+12 0.125875E+10 0.00 0.482757E+12 0.00 0.00 0.00
July 0.310276E+11 0.103375E+13 0.110324E+10 0.00 0.501719E+12 0.00 0.00 0.00
August 0.304861E+11 0.102962E+13 0.153461E+10 0.00 0.512649E+12 0.00 0.00 0.00
September 0.297169E+11 0.966218E+12 0.123067E+10 0.00 0.446232E+12 0.00 0.00 0.00
October 0.297986E+11 0.921917E+12 0.165942E+10 0.00 0.365660E+12 0.00 0.00 0.00
November 0.279992E+11 0.748657E+12 0.278441E+10 0.112828E+10 0.213180E+12 0.00 0.00 0.00
December 0.281979E+11 0.568295E+12 0.635934E+10 0.547985E+10 0.987909E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.347021E+12 0.935776E+13 0.365964E+11 0.188800E+11 0.339974E+13 0.00 0.00 0.00
Minimum of Months 0.255479E+11 0.462607E+12 0.110324E+10 0.00 0.565541E+11 0.00 0.00 0.00
Maximum of Months 0.310276E+11 0.103375E+13 0.661664E+10 0.570083E+10 0.512649E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.301691E+11 5672.26 0.130546E+10 0.518548E+10 0.00 0.00 0.00
February 0.244774E+10 0.327933E+11 4767.73 0.144780E+10 0.638814E+10 0.00 0.00 0.00
March 0.271000E+10 0.396844E+11 6114.83 0.109912E+10 0.134199E+11 0.00 0.00 0.00
April 0.262258E+10 0.466409E+11 7458.03 48080673.60 0.186857E+11 0.00 0.00 0.00
May 0.271000E+10 0.570018E+11 8642.27 0.00 0.391165E+11 0.00 0.00 0.00
June 0.262258E+10 0.615163E+11 9815.10 0.00 0.506323E+11 0.00 0.00 0.00
July 0.271000E+10 0.640607E+11 9777.18 0.00 0.530591E+11 0.00 0.00 0.00
August 0.271000E+10 0.650703E+11 8135.53 0.00 0.543303E+11 0.00 0.00 0.00
September 0.262258E+10 0.612178E+11 7395.81 0.00 0.491146E+11 0.00 0.00 0.00
October 0.271000E+10 0.586650E+11 7482.63 0.00 0.415200E+11 0.00 0.00 0.00
November 0.262258E+10 0.492529E+11 9666.95 0.388738E+09 0.241062E+11 0.00 0.00 0.00
December 0.271000E+10 0.380834E+11 9391.56 0.171518E+10 0.102150E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.604156E+12 94319.88 0.600438E+10 0.365773E+12 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.301691E+11 4767.73 0.00 0.518548E+10 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.650703E+11 9815.10 0.171518E+10 0.543303E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.280519E+11 0.661664E+10 0.462607E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.255479E+11 0.511066E+10 0.474154E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.285389E+11 0.526706E+10 0.583137E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.281773E+11 0.200141E+10 0.695680E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.298606E+11 0.167018E+10 0.896390E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.296181E+11 0.125875E+10 0.977346E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.310276E+11 0.110324E+10 0.103375E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.304861E+11 0.153461E+10 0.102962E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.297169E+11 0.123067E+10 0.966218E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.297986E+11 0.165942E+10 0.921917E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.279992E+11 0.278441E+10 0.748657E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.281979E+11 0.635934E+10 0.568295E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.347021E+12 0.365964E+11 0.935776E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.255479E+11 0.110324E+10 0.462607E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310276E+11 0.661664E+10 0.103375E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 5672.26 0.301691E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 4767.73 0.327933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 6114.83 0.396844E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 7458.03 0.466409E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 8642.27 0.570018E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 9815.10 0.615163E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 9777.18 0.640607E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 8135.53 0.650703E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 7395.81 0.612178E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 7482.63 0.586650E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 9666.95 0.492529E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 9391.56 0.380834E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 94319.88 0.604156E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 4767.73 0.301691E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 9815.10 0.650703E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.197097E+11 0.00 0.00 0.00 0.128777E+11 0.00 0.00 0.00 1.15
February 0.129628E+11 0.00 0.00 0.00 0.132670E+11 0.00 0.00 0.00 1.15
March 0.122563E+11 0.00 0.00 0.00 0.192027E+11 0.00 0.00 0.00 1.15
April 0.275392E+10 0.00 0.00 0.00 0.237623E+11 0.00 0.00 0.00 1.15
May 0.00 0.00 0.00 0.00 0.407036E+11 0.00 0.00 0.00 1.14
June 0.00 0.660423E+09 0.00 0.00 0.493545E+11 0.00 0.00 0.00 1.12
July 0.00 0.595752E+10 0.00 0.00 0.473523E+11 0.00 0.00 0.00 1.11
August 0.00 0.102782E+11 0.00 0.00 0.438130E+11 0.00 0.00 0.00 1.11
September 0.00 0.165347E+11 0.00 0.00 0.313609E+11 0.00 0.00 0.00 1.09
October 27948.49 0.118313E+11 0.00 0.00 0.307381E+11 0.00 0.00 0.00 1.12
November 0.487284E+10 0.399013E+10 0.00 90266.74 0.277808E+11 0.00 0.360225E+09 0.00 1.13
December 0.142371E+11 0.105470E+10 0.00 152440.43 0.188162E+11 0.00 0.430708E+09 0.00 1.15
                   
Annual Sum or Average 0.667926E+11 0.503069E+11 0.00 242707.17 0.359029E+12 0.00 0.790933E+09 0.00 1.13
Minimum of Months 0.00 0.00 0.00 0.00 0.128777E+11 0.00 0.00 0.00 1.09
Maximum of Months 0.197097E+11 0.165347E+11 0.00 152440.43 0.493545E+11 0.00 0.430708E+09 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.196476E+10 0.473759E+09 0.00 484838.73 0.925594E+09 0.00 0.141704E+09 0.00 2.24
February 0.120859E+10 0.426605E+09 0.00 687657.87 0.101051E+10 33306400.74 0.143278E+09 0.00 2.24
March 0.125862E+10 0.716045E+09 0.00 140827.92 0.133645E+10 4409481.43 46775251.47 0.00 2.23
April 0.271240E+09 0.109828E+10 0.00 37162.06 0.147084E+10 0.00 23059891.12 0.00 2.24
May 0.00 0.218592E+10 0.00 0.00 0.219375E+10 0.00 0.00 0.00 2.24
June 0.00 0.375656E+10 0.00 0.00 0.168113E+10 0.00 0.00 0.00 2.22
July 0.00 0.489024E+10 0.00 0.00 0.106070E+10 0.00 0.00 0.00 2.25
August 0.00 0.437319E+10 0.00 0.00 0.167240E+10 0.00 0.00 0.00 2.25
September 0.00 0.458877E+10 0.00 0.00 0.104018E+10 0.00 0.00 0.00 2.30
October 2987.12 0.347432E+10 0.00 0.00 0.146362E+10 0.00 0.00 0.00 2.35
November 0.514457E+09 0.213123E+10 0.00 198120.59 0.143800E+10 0.00 46827369.96 0.00 2.29
December 0.142650E+10 0.969553E+09 0.00 292656.58 0.123831E+10 0.00 0.140958E+09 0.00 2.28
                   
Annual Sum or Average 0.664417E+10 0.290845E+11 0.00 1841263.74 0.165315E+11 37715882.16 0.542602E+09 0.00 2.26
Minimum of Months 0.00 0.426605E+09 0.00 0.00 0.925594E+09 0.00 0.00 0.00 2.22
Maximum of Months 0.196476E+10 0.489024E+10 0.00 687657.87 0.219375E+10 33306400.74 0.143278E+09 0.00 2.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186519E+10 37200487.08 0.00 0.00 0.118146E+10 0.00 0.00 0.00 1.70
February 0.118651E+10 40893268.88 0.00 17311.78 0.121461E+10 0.00 40185726.79 0.00 1.70
March 0.114248E+10 0.106946E+09 0.00 10465.87 0.171027E+10 0.00 17366694.02 0.00 1.70
April 0.236805E+09 0.396714E+09 0.00 26234.31 0.185296E+10 0.00 23781683.46 0.00 1.70
May 0.00 0.935075E+09 0.00 0.00 0.292140E+10 0.00 0.00 0.00 1.70
June 0.00 0.173748E+10 0.00 0.00 0.300995E+10 0.00 0.00 0.00 1.67
July 0.00 0.249594E+10 0.00 0.00 0.258567E+10 0.00 0.00 0.00 1.66
August 0.00 0.205485E+10 0.00 0.00 0.309229E+10 0.00 0.00 0.00 1.66
September 0.00 0.206885E+10 0.00 0.00 0.248444E+10 0.00 0.00 0.00 1.62
October 2644.86 0.119928E+10 0.00 0.00 0.283215E+10 0.00 0.00 0.00 1.66
November 0.494620E+09 0.470484E+09 0.00 193.78 0.253611E+10 0.00 611315.38 0.00 1.68
December 0.135821E+10 0.169258E+09 0.00 13575.08 0.171120E+10 0.00 29857125.02 0.00 1.70
                   
Annual Sum or Average 0.628382E+10 0.117130E+11 0.00 67780.81 0.271325E+11 0.00 0.111803E+09 0.00 1.68
Minimum of Months 0.00 37200487.08 0.00 0.00 0.118146E+10 0.00 0.00 0.00 1.62
Maximum of Months 0.186519E+10 0.249594E+10 0.00 26234.31 0.309229E+10 0.00 40185726.79 0.00 1.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186876E+10 0.00 0.00 0.00 0.122100E+10 0.00 0.00 0.00 0.80
February 0.122359E+10 0.00 0.00 0.00 0.125791E+10 5471806.51 0.00 0.00 0.80
March 0.116208E+10 0.00 0.00 0.00 0.182070E+10 0.00 0.00 0.00 0.80
April 0.261112E+09 0.00 0.00 0.00 0.225302E+10 0.00 0.00 0.00 0.80
May 0.00 0.191843E+09 0.00 0.00 0.366746E+10 0.00 0.00 0.00 0.80
June 0.00 0.113038E+10 0.00 0.00 0.362154E+10 0.00 0.00 0.00 0.79
July 0.00 0.225138E+10 0.00 0.00 0.284789E+10 0.00 0.00 0.00 0.79
August 0.00 0.117669E+10 0.00 0.00 0.396476E+10 0.00 0.00 0.00 0.78
September 0.00 0.112597E+10 0.00 0.00 0.342034E+10 0.00 0.00 0.00 0.77
October 2649.93 95378944.75 0.00 0.00 0.394082E+10 0.00 0.00 0.00 0.78
November 0.496179E+09 0.00 0.00 0.00 0.301235E+10 0.00 0.00 0.00 0.80
December 0.139074E+10 0.00 0.00 0.00 0.188405E+10 0.00 0.00 0.00 0.80
                   
Annual Sum or Average 0.640246E+10 0.597163E+10 0.00 0.00 0.329118E+11 5471806.51 0.00 0.00 0.79
Minimum of Months 0.00 0.00 0.00 0.00 0.122100E+10 0.00 0.00 0.00 0.77
Maximum of Months 0.186876E+10 0.225138E+10 0.00 0.00 0.396476E+10 5471806.51 0.00 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.102571E+10 0.00 0.00 0.00 0.670171E+09 0.00 0.00 0.00 0.77
February 0.670077E+09 0.00 0.00 0.00 0.690432E+09 4520652.44 0.00 0.00 0.77
March 0.637832E+09 0.00 0.00 0.00 0.999332E+09 0.00 0.00 0.00 0.77
April 0.143317E+09 0.00 0.00 0.00 0.123662E+10 0.00 0.00 0.00 0.77
May 0.00 0.00 0.00 0.00 0.211827E+10 0.00 0.00 0.00 0.77
June 0.00 0.293085E+09 0.00 0.00 0.230975E+10 0.00 0.00 0.00 0.75
July 0.00 0.748352E+09 0.00 0.00 0.202708E+10 0.00 0.00 0.00 0.74
August 0.00 0.363920E+09 0.00 0.00 0.245105E+10 0.00 0.00 0.00 0.74
September 0.00 0.305648E+09 0.00 0.00 0.218689E+10 0.00 0.00 0.00 0.73
October 1454.47 0.00 0.00 0.00 0.221536E+10 0.00 0.00 0.00 0.75
November 0.272339E+09 0.00 0.00 0.00 0.165340E+10 0.00 0.00 0.00 0.76
December 0.763339E+09 0.00 0.00 0.00 0.103411E+10 0.00 0.00 0.00 0.76
                   
Annual Sum or Average 0.351262E+10 0.171100E+10 0.00 0.00 0.195925E+11 4520652.44 0.00 0.00 0.76
Minimum of Months 0.00 0.00 0.00 0.00 0.670171E+09 0.00 0.00 0.00 0.73
Maximum of Months 0.102571E+10 0.748352E+09 0.00 0.00 0.245105E+10 4520652.44 0.00 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.462872E+09 0.144526E+11 0.00 39778071.33 0.381174E+09 0.00 0.221012E+11 0.00 20.55
February 0.197416E+09 0.149227E+11 0.00 30959491.21 0.443987E+09 0.00 0.147140E+11 0.00 20.63
March 0.248150E+09 0.216560E+11 0.00 29136896.81 0.595446E+09 0.00 0.138334E+11 0.00 20.71
April 32880942.72 0.267898E+11 0.00 11325680.35 0.722586E+09 0.00 0.313347E+10 0.00 20.74
May 0.00 0.464483E+11 0.00 0.00 0.937842E+09 0.00 0.00 0.00 20.79
June 0.00 0.576953E+11 0.00 0.00 0.975277E+09 0.00 0.00 0.00 20.46
July 0.00 0.612393E+11 0.00 0.00 0.101897E+10 0.00 0.00 0.00 20.18
August 0.00 0.618342E+11 0.00 0.00 0.116600E+10 0.00 0.00 0.00 20.10
September 0.00 0.548041E+11 0.00 0.00 0.100735E+10 0.00 0.00 0.00 19.68
October 0.00 0.481658E+11 0.00 5393.83 0.101403E+10 0.00 25410.51 0.00 20.09
November 95587402.92 0.361844E+11 0.00 11468385.74 0.742526E+09 0.00 0.584744E+10 0.00 20.38
December 0.275406E+09 0.223769E+11 0.00 30100095.23 0.523121E+09 0.00 0.167349E+11 0.00 20.51
                   
Annual Sum or Average 0.131231E+10 0.466569E+12 0.00 0.152774E+09 0.952830E+10 0.00 0.763645E+11 0.00 20.40
Minimum of Months 0.00 0.144526E+11 0.00 0.00 0.381174E+09 0.00 0.00 0.00 19.68
Maximum of Months 0.462872E+09 0.618342E+11 0.00 39778071.33 0.116600E+10 0.00 0.221012E+11 0.00 20.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.424813E+10 0.390566E+10 0.00 6333464.11 0.197685E+10 0.00 0.465318E+10 0.00 3.37
February 0.268640E+10 0.388433E+10 0.00 6260338.22 0.214068E+10 0.00 0.316682E+10 0.00 3.37
March 0.278075E+10 0.585894E+10 0.00 3438058.75 0.283005E+10 0.00 0.275400E+10 0.00 3.36
April 0.396859E+09 0.748390E+10 0.00 1884063.87 0.329608E+10 0.00 0.845960E+09 0.00 3.36
May 0.00 0.133794E+11 0.00 0.00 0.511929E+10 0.00 0.00 0.00 3.36
June 0.00 0.184969E+11 0.00 0.00 0.448324E+10 0.00 0.00 0.00 3.34
July 0.00 0.214728E+11 0.00 0.00 0.317378E+10 0.00 0.00 0.00 3.32
August 0.00 0.208237E+11 0.00 0.00 0.422152E+10 0.00 0.00 0.00 3.33
September 0.00 0.203659E+11 0.00 0.00 0.236451E+10 0.00 0.00 0.00 3.34
October 0.00 0.172698E+11 0.00 8922.73 0.276165E+10 0.00 3706.21 0.00 3.41
November 0.116627E+10 0.126348E+11 0.00 1976570.24 0.213414E+10 0.00 0.119991E+10 0.00 3.39
December 0.280453E+10 0.717418E+10 0.00 4269161.41 0.197403E+10 0.00 0.381947E+10 0.00 3.39
                   
Annual Sum or Average 0.140829E+11 0.152750E+12 0.00 24170579.32 0.364758E+11 0.00 0.164394E+11 0.00 3.36
Minimum of Months 0.00 0.388433E+10 0.00 0.00 0.197403E+10 0.00 0.00 0.00 3.32
Maximum of Months 0.424813E+10 0.214728E+11 0.00 6333464.11 0.511929E+10 0.00 0.465318E+10 0.00 3.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.314123E+11 0.463139E+10 0.00 404537.16 0.163795E+11 0.00 0.744876E+09 0.00 1.75
February 0.185030E+11 0.436374E+10 0.00 1696597.83 0.172823E+11 0.00 0.264490E+10 0.00 1.75
March 0.185959E+11 0.890251E+10 0.00 915929.83 0.224280E+11 0.00 0.140019E+10 0.00 1.75
April 0.317490E+10 0.131916E+11 0.00 1934881.82 0.255847E+11 0.00 0.131637E+10 0.00 1.74
May 0.00 0.279493E+11 0.00 0.00 0.385531E+11 0.00 0.00 0.00 1.74
June 0.00 0.436441E+11 0.00 0.00 0.384961E+11 0.00 0.00 0.00 1.72
July 0.00 0.551596E+11 0.00 0.00 0.329411E+11 0.00 0.00 0.00 1.71
August 0.00 0.489803E+11 0.00 0.00 0.401223E+11 0.00 0.00 0.00 1.71
September 0.00 0.531468E+11 0.00 0.00 0.260911E+11 0.00 0.00 0.00 1.68
October 0.00 0.395597E+11 0.00 20547.44 0.301639E+11 0.00 25052.37 0.00 1.70
November 0.710413E+10 0.239701E+11 0.00 528183.08 0.279283E+11 0.00 0.143357E+10 0.00 1.73
December 0.206941E+11 0.104626E+11 0.00 1724563.29 0.219604E+11 0.00 0.323595E+10 0.00 1.74
                   
Annual Sum or Average 0.994844E+11 0.333962E+12 0.00 7225240.43 0.337931E+12 0.00 0.107759E+11 0.00 1.73
Minimum of Months 0.00 0.436374E+10 0.00 0.00 0.163795E+11 0.00 0.00 0.00 1.68
Maximum of Months 0.314123E+11 0.551596E+11 0.00 1934881.82 0.401223E+11 0.00 0.323595E+10 0.00 1.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 11538821.19 0.331205E+09 372769.61 5408085.78 2478782.70 24980061.41 0.482712E+09 27420.25 0.35
February 4069542.40 0.319301E+09 236766.49 4738882.35 2831723.30 44192341.98 0.275185E+09 19201.90 0.35
March 11045395.33 0.478269E+09 318097.43 3949730.02 1196050.62 17755584.38 0.273485E+09 20147.48 0.35
April 17805.94 0.651173E+09 386579.20 1659747.44 0.00 104471.49 46474760.98 39500.44 0.35
May 0.00 0.118433E+10 1461031.24 0.00 1058720.90 0.00 0.00 49516.91 0.36
June 0.00 0.150609E+10 2010077.62 0.00 0.00 0.00 0.00 42018.81 0.35
July 0.00 0.158190E+10 1333161.28 0.00 0.00 0.00 0.00 20171.70 0.35
August 0.00 0.161338E+10 1472968.09 0.00 4822449.01 0.00 0.00 23539.12 0.35
September 0.00 0.146346E+10 946315.57 0.00 0.00 0.00 0.00 13976.78 0.36
October 0.00 0.125707E+10 921823.43 0.00 0.00 0.00 0.00 30979.20 0.36
November 445191.39 0.912438E+09 1237007.08 1829194.72 2697810.05 8153070.50 0.126800E+09 30075.47 0.35
December 6159540.28 0.500161E+09 563733.86 3956594.73 1092747.25 38318291.67 0.322447E+09 21026.20 0.35
                   
Annual Sum or Average 33276296.54 0.117988E+11 11260330.91 21542235.03 16178283.82 0.133504E+09 0.152710E+10 337574.27 0.35
Minimum of Months 0.00 0.319301E+09 236766.49 0.00 0.00 0.00 0.00 13976.78 0.35
Maximum of Months 11538821.19 0.161338E+10 2010077.62 5408085.78 4822449.01 44192341.98 0.482712E+09 49516.91 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135686E+09 0.252308E+09 636937.24 2096498.60 81062290.00 57662112.56 0.329134E+09 37816.53 0.36
February 76409151.71 0.243647E+09 630932.75 2441363.30 78029673.86 57005437.67 0.192292E+09 43326.75 0.35
March 77570624.93 0.382740E+09 674990.78 1937426.94 96301455.22 28239382.60 0.198452E+09 31110.00 0.35
April 18314175.32 0.548502E+09 498104.99 916455.75 0.102491E+09 46315.90 28974184.89 30732.08 0.36
May 0.00 0.113074E+10 1303359.80 0.00 54679886.95 0.00 0.00 39162.23 0.36
June 0.00 0.148518E+10 1720146.71 0.00 21028540.01 0.00 0.00 29310.71 0.35
July 0.00 0.154784E+10 1273000.61 0.00 33939514.42 0.00 0.00 17202.53 0.35
August 0.00 0.159481E+10 1500498.45 0.00 23170483.98 0.00 0.00 22460.81 0.35
September 0.00 0.142104E+10 1462103.25 0.00 41716826.36 0.00 0.00 27607.80 0.36
October 0.00 0.119851E+10 1748005.13 0.00 57575226.78 0.00 0.00 41279.19 0.36
November 36619164.93 0.816113E+09 2185326.25 829748.46 97922228.28 10254114.20 89508209.31 74375.93 0.36
December 0.104512E+09 0.390760E+09 1035238.47 1517637.97 0.109932E+09 76949222.05 0.187860E+09 52867.07 0.36
                   
Annual Sum or Average 0.449110E+09 0.110122E+11 14668644.42 9739131.02 0.797849E+09 0.230157E+09 0.102622E+10 447251.63 0.36
Minimum of Months 0.00 0.243647E+09 498104.99 0.00 21028540.01 0.00 0.00 17202.53 0.35
Maximum of Months 0.135686E+09 0.159481E+10 2185326.25 2441363.30 0.109932E+09 76949222.05 0.329134E+09 74375.93 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 41829385.18 0.488214E+09 0.00 1772469.26 0.00 0.00 0.336838E+09 0.00 0.02
February 0.00 0.468680E+09 0.00 1041051.75 9655044.76 0.00 0.146885E+09 0.00 0.02
March 36628209.79 0.493908E+09 0.00 858469.79 0.00 0.00 0.217681E+09 0.00 0.02
April 0.00 0.610309E+09 0.00 146104.30 0.00 0.00 40533957.62 0.00 0.02
May 0.00 0.929187E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
June 0.00 0.104514E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
July 0.00 0.112759E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 0.00 0.115710E+10 0.00 0.00 35953783.56 0.00 0.00 0.00 0.02
September 0.00 0.113767E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
October 0.00 0.103871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
November 22493322.44 0.676688E+09 0.00 476540.21 0.00 0.00 46037241.67 0.00 0.02
December 24769854.79 0.714939E+09 0.00 1214873.96 3939495.45 0.00 0.231717E+09 0.00 0.02
                   
Annual Sum or Average 0.125721E+09 0.988814E+10 0.00 5509509.28 49548323.77 0.00 0.101969E+10 0.00 0.02
Minimum of Months 0.00 0.468680E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 41829385.18 0.115710E+10 0.00 1772469.26 35953783.56 0.00 0.336838E+09 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.184049E+10 0.327997E+10 5637510.67 39954743.05 0.124538E+10 41741003.60 0.519340E+10 135050.47 0.40
February 0.104989E+10 0.313233E+10 3923667.32 32903247.61 0.123617E+10 20804666.68 0.334753E+10 78785.61 0.40
March 0.105306E+10 0.495545E+10 8523340.10 27691018.96 0.154336E+10 17571867.52 0.305509E+10 161442.04 0.40
April 0.255998E+09 0.709544E+10 13953918.52 10307675.72 0.172789E+10 0.00 0.388192E+09 235306.66 0.40
May 0.00 0.148203E+11 21131032.69 0.00 0.125617E+10 0.00 0.00 171371.16 0.40
June 0.00 0.197988E+11 11942940.57 0.00 0.643812E+09 0.00 0.00 26837.79 0.40
July 0.00 0.209498E+11 11460142.24 0.00 0.512080E+09 0.00 0.00 20149.78 0.40
August 0.00 0.211674E+11 18413244.79 0.00 0.781762E+09 0.00 0.00 84125.91 0.40
September 0.00 0.187899E+11 15666848.18 0.00 0.105599E+10 0.00 0.00 94934.52 0.40
October 0.00 0.155702E+11 19570638.82 0.00 0.147240E+10 0.00 0.00 152709.87 0.40
November 0.514393E+09 0.106110E+11 18635681.96 14513413.82 0.179920E+10 5944627.43 0.132634E+10 168974.85 0.40
December 0.142194E+10 0.506271E+10 13409824.56 28369422.53 0.173004E+10 21991400.54 0.355789E+10 178646.14 0.40
                   
Annual Sum or Average 0.613578E+10 0.145233E+12 0.162269E+09 0.153740E+09 0.150042E+11 0.108054E+09 0.168684E+11 1508334.79 0.40
Minimum of Months 0.00 0.313233E+10 3923667.32 0.00 0.512080E+09 0.00 0.00 20149.78 0.40
Maximum of Months 0.184049E+10 0.211674E+11 21131032.69 39954743.05 0.179920E+10 41741003.60 0.519340E+10 235306.66 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5680623.15 0.331938E+09 104847.73 5666549.71 2033573.18 35993952.25 0.477298E+09 7706.54 0.35
February 4069542.40 0.319077E+09 162546.10 5051054.33 3146609.25 42468993.66 0.276597E+09 2471.61 0.35
March 6003663.87 0.479114E+09 177995.88 3978562.77 505772.58 13427695.15 0.282826E+09 5885.09 0.35
April 0.00 0.651599E+09 0.00 1706339.99 0.00 30947.22 46519498.64 0.00 0.35
May 0.00 0.118605E+10 54903.68 0.00 800780.55 0.00 0.00 1202.91 0.36
June 0.00 0.150810E+10 39155.40 0.00 0.00 0.00 0.00 648.26 0.35
July 0.00 0.158325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.35
August 0.00 0.161470E+10 168238.96 0.00 4822449.01 0.00 0.00 4787.42 0.35
September 0.00 0.146442E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.36
October 0.00 0.125793E+10 95908.72 0.00 0.00 0.00 0.00 2625.70 0.36
November 445191.39 0.913939E+09 164453.30 1995621.94 2296204.33 6567326.89 0.128219E+09 2602.94 0.35
December 6834968.27 0.500574E+09 163068.50 3852207.49 1092747.25 47310644.43 0.312884E+09 8780.38 0.35
                   
Annual Sum or Average 23033989.08 0.118107E+11 1131118.27 22250336.23 14698136.16 0.145800E+09 0.152434E+10 36710.85 0.35
Minimum of Months 0.00 0.319077E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 6834968.27 0.161470E+10 177995.88 5666549.71 4822449.01 47310644.43 0.477298E+09 8780.38 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135400E+09 0.253944E+09 338078.16 2324101.92 79745573.65 64941987.03 0.321912E+09 17673.73 0.36
February 75985919.60 0.244654E+09 338339.77 2512454.20 77344793.91 50522027.86 0.199127E+09 13587.30 0.35
March 77231925.16 0.383239E+09 417923.19 2066571.54 96075646.03 16036544.93 0.210865E+09 15323.99 0.35
April 17907471.62 0.548990E+09 173511.05 956186.45 0.102350E+09 28941.81 29358531.98 9855.05 0.36
May 0.00 0.113186E+10 245826.30 0.00 54652558.74 0.00 0.00 4670.48 0.36
June 0.00 0.148690E+10 29539.10 0.00 21028540.01 0.00 0.00 47.28 0.35
July 0.00 0.154913E+10 0.00 0.00 33939514.42 0.00 0.00 0.00 0.35
August 0.00 0.159604E+10 290715.78 0.00 23170483.98 0.00 0.00 4626.40 0.35
September 0.00 0.142242E+10 111593.43 0.00 41716826.36 0.00 0.00 2803.22 0.36
October 0.00 0.119997E+10 322162.74 0.00 57575226.78 0.00 0.00 8204.16 0.36
November 37295159.27 0.817590E+09 764773.16 991932.34 97922228.28 7830718.45 91093426.83 18237.77 0.36
December 0.104512E+09 0.390164E+09 854919.45 1358413.66 0.110732E+09 82260089.84 0.182708E+09 28206.13 0.35
                   
Annual Sum or Average 0.448332E+09 0.110249E+11 3887382.13 10209660.12 0.796253E+09 0.221620E+09 0.103506E+10 123235.51 0.36
Minimum of Months 0.00 0.244654E+09 0.00 0.00 21028540.01 0.00 0.00 0.00 0.35
Maximum of Months 0.135400E+09 0.159604E+10 854919.45 2512454.20 0.110732E+09 82260089.84 0.321912E+09 28206.13 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.105373E+11 0.00 0.00 0.00 0.688479E+10 0.00 0.00 0.00 0.62
February 0.693026E+10 0.00 0.00 0.00 0.709293E+10 0.00 0.00 0.00 0.62
March 0.655256E+10 0.00 0.00 0.00 0.102663E+11 0.00 0.00 0.00 0.62
April 0.147232E+10 0.00 0.00 0.00 0.127040E+11 0.00 0.00 0.00 0.62
May 0.00 0.00 0.00 0.00 0.217613E+11 0.00 0.00 0.00 0.62
June 0.00 0.00 0.00 0.00 0.267394E+11 0.00 0.00 0.00 0.61
July 0.00 0.246484E+09 0.00 0.00 0.282545E+11 0.00 0.00 0.00 0.60
August 0.00 0.132364E+09 0.00 0.00 0.287863E+11 0.00 0.00 0.00 0.60
September 0.00 0.548622E+09 0.00 0.00 0.250577E+11 0.00 0.00 0.00 0.59
October 14942.05 0.00 0.00 0.00 0.227588E+11 0.00 0.00 0.00 0.61
November 0.279779E+10 0.00 0.00 0.00 0.169856E+11 0.00 0.00 0.00 0.62
December 0.784192E+10 0.00 0.00 0.00 0.106236E+11 0.00 0.00 0.00 0.62
                   
Annual Sum or Average 0.361322E+11 0.927470E+09 0.00 0.00 0.217915E+12 0.00 0.00 0.00 0.61
Minimum of Months 0.00 0.00 0.00 0.00 0.688479E+10 0.00 0.00 0.00 0.59
Maximum of Months 0.105373E+11 0.548622E+09 0.00 0.00 0.287863E+11 0.00 0.00 0.00 0.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1464221.33 82971199.08 94316.49 1218033.83 448226.41 36558548.54 91919059.96 7298.59 0.35
February 1181289.88 79994797.26 54988.02 1060421.48 542047.42 23605276.47 56199575.95 5296.13 0.35
March 2754676.84 0.119810E+09 68053.95 934161.69 66355.59 21075542.87 51794529.67 6763.55 0.35
April 0.00 0.162775E+09 110188.20 382853.41 0.00 21158.71 11660184.34 14445.38 0.35
May 0.00 0.296334E+09 376325.44 0.00 0.00 0.00 0.00 15253.61 0.36
June 0.00 0.376503E+09 517912.73 0.00 0.00 0.00 0.00 13643.76 0.35
July 0.00 0.395242E+09 561887.99 0.00 0.00 0.00 0.00 8478.71 0.35
August 0.00 0.403175E+09 533552.71 0.00 1205612.25 0.00 0.00 10444.14 0.35
September 0.00 0.365673E+09 423049.88 0.00 0.00 0.00 0.00 8710.10 0.36
October 0.00 0.314092E+09 402613.09 0.00 0.00 0.00 0.00 11405.11 0.36
November 111297.85 0.228159E+09 357252.91 390992.35 574051.08 11449909.11 22354629.46 10252.02 0.35
December 1081773.00 0.125050E+09 130009.26 845152.74 273186.81 29678513.97 61114924.61 6660.71 0.35
                   
Annual Sum or Average 6593258.89 0.294978E+10 3630150.67 4831615.50 3109479.57 0.122389E+09 0.295043E+09 118651.81 0.35
Minimum of Months 0.00 79994797.26 54988.02 0.00 0.00 0.00 0.00 5296.13 0.35
Maximum of Months 2754676.84 0.403175E+09 561887.99 1218033.83 1205612.25 36558548.54 91919059.96 15253.61 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 34091711.53 63563284.32 131368.98 416249.24 19804905.94 48759437.62 47877097.96 11695.63 0.36
February 19255122.87 61217323.70 125243.28 537910.80 19237297.99 26463801.22 35780115.94 7820.73 0.35
March 19340130.57 95983240.63 120369.71 439469.32 23828248.33 21665462.66 35104878.53 5032.99 0.35
April 4476867.91 0.137130E+09 119700.30 212351.37 25622859.32 7697.48 7365866.21 8523.09 0.36
May 0.00 0.282738E+09 336799.84 0.00 13604619.38 0.00 0.00 11609.69 0.36
June 0.00 0.371249E+09 474747.37 0.00 5257135.00 0.00 0.00 9534.95 0.35
July 0.00 0.386802E+09 474455.89 0.00 8484878.60 0.00 0.00 4444.25 0.35
August 0.00 0.398577E+09 497753.99 0.00 5792620.99 0.00 0.00 9143.94 0.35
September 0.00 0.355151E+09 469187.10 0.00 10429206.59 0.00 0.00 12551.34 0.36
October 0.00 0.299613E+09 447427.36 0.00 14393806.70 0.00 0.00 15325.01 0.36
November 8900414.07 0.204244E+09 491460.43 154668.82 24322165.80 12148344.28 13099382.06 16108.01 0.36
December 25985600.98 98359874.11 231856.65 294841.51 26841662.98 39520605.11 26908453.18 11481.95 0.36
                   
Annual Sum or Average 0.112050E+09 0.275463E+10 3920370.89 2055491.06 0.197619E+09 0.148565E+09 0.166136E+09 123271.58 0.36
Minimum of Months 0.00 61217323.70 119700.30 0.00 5257135.00 0.00 0.00 4444.25 0.35
Maximum of Months 34091711.53 0.398577E+09 497753.99 537910.80 26841662.98 48759437.62 47877097.96 16108.01 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3839569.48 0.533957E+09 66652.73 12075318.69 2553451.87 18704037.29 0.808016E+09 2968.66 0.40
February 0.00 0.515050E+09 226435.65 8577673.62 2511327.04 47464325.69 0.471065E+09 7194.64 0.40
March 2784485.83 0.770466E+09 149656.52 6139312.58 0.00 25171645.80 0.457756E+09 8172.80 0.40
April 0.00 0.104613E+10 409563.85 2042513.38 0.00 87696.23 75376091.99 8653.15 0.40
May 0.00 0.190531E+10 572447.43 0.00 419904.74 0.00 0.00 6055.14 0.40
June 0.00 0.242197E+10 283198.36 0.00 0.00 0.00 0.00 1791.06 0.40
July 0.00 0.254256E+10 330860.36 0.00 0.00 0.00 0.00 613.29 0.40
August 0.00 0.259307E+10 616572.65 0.00 7745443.07 0.00 0.00 1544.96 0.40
September 0.00 0.235137E+10 664131.34 0.00 0.00 0.00 0.00 6204.25 0.40
October 0.00 0.201997E+10 569371.73 0.00 0.00 0.00 0.00 4013.25 0.40
November 511108.46 0.146785E+10 308889.68 3522967.43 3687985.06 9777700.18 0.206592E+09 4108.41 0.40
December 1586376.57 0.804656E+09 52915.53 8581088.68 1302404.22 18652016.72 0.566862E+09 2491.45 0.40
                   
Annual Sum or Average 8721540.33 0.189724E+11 4250695.83 40938874.38 18220516.01 0.119857E+09 0.258567E+10 53811.06 0.40
Minimum of Months 0.00 0.515050E+09 52915.53 0.00 0.00 0.00 0.00 613.29 0.40
Maximum of Months 3839569.48 0.259307E+10 664131.34 12075318.69 7745443.07 47464325.69 0.808016E+09 8653.15 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.337069E+10 0.841134E+10 0.00 20074562.12 0.160857E+10 0.00 0.117221E+11 0.00 4.25
February 0.164736E+10 0.894665E+10 0.00 16697760.91 0.143665E+10 0.00 0.837543E+10 0.00 4.29
March 0.201803E+10 0.140447E+11 0.00 16449247.55 0.119478E+10 0.00 0.742949E+10 0.00 4.32
April 0.141727E+09 0.179142E+11 0.00 9179570.87 0.111918E+10 0.00 0.202220E+10 0.00 4.40
May 0.00 0.325447E+11 0.00 0.00 0.948907E+09 0.00 0.00 0.00 4.55
June 0.00 0.415617E+11 0.00 0.00 0.717150E+09 0.00 0.00 0.00 4.57
July 0.00 0.444052E+11 0.00 0.00 0.688801E+09 0.00 0.00 0.00 4.54
August 0.00 0.440043E+11 0.00 0.00 0.106864E+10 0.00 0.00 0.00 4.46
September 0.00 0.387632E+11 0.00 0.00 0.969160E+09 0.00 0.00 0.00 4.35
October 0.00 0.330424E+11 0.00 16887.27 0.137018E+10 0.00 5612.99 0.00 4.34
November 0.503570E+09 0.236041E+11 0.00 6306892.93 0.175287E+10 0.00 0.351127E+10 0.00 4.30
December 0.264254E+10 0.136222E+11 0.00 15691286.19 0.194831E+10 0.00 0.862228E+10 0.00 4.27
                   
Annual Sum or Average 0.103239E+11 0.320865E+12 0.00 84416207.83 0.148232E+11 0.00 0.416828E+11 0.00 4.39
Minimum of Months 0.00 0.841134E+10 0.00 0.00 0.688801E+09 0.00 0.00 0.00 4.25
Maximum of Months 0.337069E+10 0.444052E+11 0.00 20074562.12 0.194831E+10 0.00 0.117221E+11 0.00 4.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.278274E+10 0.946955E+10 0.00 25146920.49 0.110284E+10 0.00 0.130580E+11 0.00 4.48
February 0.125349E+10 0.101295E+11 0.00 20888114.34 0.852598E+09 0.00 0.929309E+10 0.00 4.52
March 0.184305E+10 0.153631E+11 0.00 20159345.84 0.781798E+09 0.00 0.810541E+10 0.00 4.57
April 73199005.20 0.193818E+11 0.00 10633905.65 0.744949E+09 0.00 0.221395E+10 0.00 4.66
May 0.00 0.348058E+11 0.00 0.00 0.589655E+09 0.00 0.00 0.00 4.81
June 0.00 0.441640E+11 0.00 0.00 0.436922E+09 0.00 0.00 0.00 4.82
July 0.00 0.471901E+11 0.00 0.00 0.344853E+09 0.00 0.00 0.00 4.78
August 0.00 0.468269E+11 0.00 0.00 0.695812E+09 0.00 0.00 0.00 4.70
September 0.00 0.411342E+11 0.00 0.00 0.722167E+09 0.00 0.00 0.00 4.58
October 0.00 0.353042E+11 0.00 17716.71 0.956354E+09 0.00 5891.41 0.00 4.57
November 0.380016E+09 0.256115E+11 0.00 7925472.48 0.116166E+10 0.00 0.383872E+10 0.00 4.54
December 0.223800E+10 0.153279E+11 0.00 19240521.18 0.111858E+10 0.00 0.960965E+10 0.00 4.49
                   
Annual Sum or Average 0.857050E+10 0.344709E+12 0.00 0.104012E+09 0.950819E+10 0.00 0.461188E+11 0.00 4.63
Minimum of Months 0.00 0.946955E+10 0.00 0.00 0.344853E+09 0.00 0.00 0.00 4.48
Maximum of Months 0.278274E+10 0.471901E+11 0.00 25146920.49 0.116166E+10 0.00 0.130580E+11 0.00 4.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 827710.07 0.130639E+11 0.00 61518739.52 4231065.64 0.00 0.176179E+11 0.00 17.19
February 6861494.21 0.135818E+11 0.00 48983062.71 3224510.80 0.00 0.113503E+11 0.00 17.43
March 4565857.44 0.196687E+11 0.00 43353872.19 2150860.15 0.00 0.108350E+11 0.00 17.62
April 905990.42 0.249099E+11 0.00 15693314.64 0.00 0.00 0.242046E+10 0.00 18.12
May 0.00 0.434852E+11 0.00 0.00 0.00 0.00 0.00 0.00 18.44
June 0.00 0.545928E+11 0.00 0.00 0.00 0.00 0.00 0.00 18.41
July 0.00 0.589198E+11 0.00 0.00 0.00 0.00 0.00 0.00 18.36
August 0.00 0.585002E+11 0.00 0.00 0.00 0.00 0.00 0.00 18.01
September 0.00 0.522491E+11 0.00 0.00 0.00 0.00 0.00 0.00 17.76
October 0.00 0.449217E+11 0.00 8378.21 0.00 0.00 12922.26 0.00 17.81
November 795627.09 0.329766E+11 0.00 18115471.73 1699798.93 0.00 0.458604E+10 0.00 17.56
December 517505.48 0.201566E+11 0.00 44898430.91 320694.78 0.00 0.131777E+11 0.00 17.21
                   
Annual Sum or Average 14474184.69 0.437026E+12 0.00 0.232571E+09 11626930.29 0.00 0.599874E+11 0.00 17.83
Minimum of Months 0.00 0.130639E+11 0.00 0.00 0.00 0.00 0.00 0.00 17.19
Maximum of Months 6861494.21 0.589198E+11 0.00 61518739.52 4231065.64 0.00 0.176179E+11 0.00 18.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.535646E+10 0.00 0.00 0.00 0.349976E+10 0.00 0.00 0.00 1.20
February 0.345156E+10 0.00 0.00 0.00 0.360556E+10 71309780.59 0.00 0.00 1.20
March 0.329916E+10 0.00 0.00 0.00 0.521869E+10 31715949.27 0.00 0.00 1.20
April 0.747914E+09 0.625075E+09 0.00 1285.39 0.583277E+10 0.00 514080.08 0.00 1.20
May 0.00 0.219988E+10 0.00 0.00 0.886208E+10 0.00 0.00 0.00 1.20
June 0.00 0.622845E+10 0.00 0.00 0.740293E+10 0.00 0.00 0.00 1.18
July 0.00 0.872215E+10 0.00 0.00 0.592343E+10 0.00 0.00 0.00 1.17
August 0.00 0.615974E+10 0.00 0.00 0.859744E+10 0.00 0.00 0.00 1.16
September 0.00 0.632407E+10 0.00 0.00 0.681927E+10 0.00 0.00 0.00 1.15
October 7595.52 0.285503E+10 0.00 0.00 0.871964E+10 0.00 0.00 0.00 1.16
November 0.142221E+10 0.453733E+09 0.00 0.00 0.818061E+10 0.00 0.00 0.00 1.18
December 0.398630E+10 56487616.84 0.00 0.00 0.534380E+10 0.00 0.00 0.00 1.19
                   
Annual Sum or Average 0.182636E+11 0.336246E+11 0.00 1285.39 0.780060E+11 0.103026E+09 514080.08 0.00 1.18
Minimum of Months 0.00 0.00 0.00 0.00 0.349976E+10 0.00 0.00 0.00 1.15
Maximum of Months 0.535646E+10 0.872215E+10 0.00 1285.39 0.886208E+10 71309780.59 514080.08 0.00 1.20



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:46:00

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.196074E+12 0.240590E+09 0.123793E+11 0.165234E+10 0.807508E+12
February 0.224730E+12 -0.129656E+10 -0.727754E+10 -0.656507E+11 0.825944E+12
March 0.311207E+12 -0.333672E+10 -0.295992E+11 -0.173759E+12 0.100174E+13
April 0.330579E+12 -0.623936E+10 -0.712816E+11 -0.330641E+12 0.118744E+13
May 0.322888E+12 -0.123741E+11 -0.162275E+12 -0.692254E+12 0.150602E+13
June 0.281225E+12 -0.157876E+11 -0.213631E+12 -0.892318E+12 0.163504E+13
July 0.294834E+12 -0.167447E+11 -0.232322E+12 -0.939113E+12 0.173577E+13
August 0.325036E+12 -0.171027E+11 -0.233971E+12 -0.952984E+12 0.171879E+13
September 0.241140E+12 -0.154210E+11 -0.211500E+12 -0.837952E+12 0.162819E+13
October 0.232007E+12 -0.129806E+11 -0.171935E+12 -0.711040E+12 0.155577E+13
November 0.174929E+12 -0.773380E+10 -0.100931E+12 -0.424209E+12 0.125797E+13
December 0.193202E+12 -0.228763E+10 -0.213925E+11 -0.131958E+12 0.965798E+12
           
Annual Sum or Average 0.312785E+13 -0.111064E+12 -0.144374E+13 -0.615022E+13 0.158260E+14
Minimum of Months 0.174929E+12 -0.171027E+11 -0.233971E+12 -0.952984E+12 0.807508E+12
Maximum of Months 0.330579E+12 0.240590E+09 0.123793E+11 0.165234E+10 0.173577E+13