Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:46:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11000.72 | 969.63 | 969.63 |
Net Site Energy | 11000.72 | 969.63 | 969.63 |
Total Source Energy | 21148.45 | 1864.07 | 1864.07 |
Net Source Energy | 21148.45 | 1864.07 | 1864.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1535.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 291.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 492.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 69.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 147.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3247.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4428.07 | 6572.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1535.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 291.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 492.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 69.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 147.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3247.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1535.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 291.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 492.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 69.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 147.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3247.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 83.26 | 421.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.06 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 390.30 | 579.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 83.26 | 421.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.06 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 390.30 | 579.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4428.068 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4428.068 | 100.00 |
Total On-Site and Utility Electric Sources | 4428.068 | 100.00 |
Total Electricity End Uses | 4428.068 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1.16 | 0.04 |
Air to Air Heat Recovery for Heating | 2914.09 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2915.25 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 22.00 |
Time Setpoint Not Met During Occupied Cooling | 24.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7241.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-18:10 | 21-FEB-18:40 | - | - | - | - | - | - | - | - | - | - | 27-APR-20:10 |
Heating | 0.00 | 188508.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118965.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 51055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 74651.16 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31287.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25061.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4818.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4250.41 | 278726.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2384.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 322411.82 | 571482.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 188508.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 118965.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 51055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 44668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 983.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25061.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4818.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4250.41 | 278726.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 216.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1088.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1080.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1664.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 922.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2476.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1560.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 465.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.40 | 3520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14023.69 | 7124.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 137.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 310.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1236.08 | 627.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 137.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 310.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1236.08 | 627.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.49 | 0.604915 | 0.515000 | 1.28 | 1.00 | 0.500000 | 0.000630 | 0.000072 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.449122 | 0.113796 | 0.515000 | 0.231298 | 0.515000 | 0.500000 | 0.003348 | 0.000030 | 0.231298 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.228225 | 0.259321 | 0.515000 | 0.117536 | 0.691523 | 0.500000 | 0.001469 | 0.000012 | 0.117536 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.168996 | 0.740569 | 0.515000 | 0.087033 | 1.00 | 0.500000 | 0.000514 | 0.000016 | 0.087033 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.099186 | 0.727992 | 0.515000 | 0.051081 | 1.00 | 0.500000 | 0.000523 | 0.000010 | 0.051081 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.28 | 0.018155 | 0.515000 | 1.69 | 0.515000 | 0.500000 | 0.020986 | 0.000093 | 1.69 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.79 | 0.080544 | 0.515000 | 0.920177 | 0.515000 | 0.500000 | 0.004730 | 0.000092 | 0.920177 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.14 | 0.193936 | 0.515000 | 2.65 | 0.517163 | 0.500000 | 0.001965 | 0.000238 | 2.65 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.60 | 0.743614 | 0.515000 | 0.822008 | 1.00 | 0.500000 | 0.000512 | 0.000105 | 0.822008 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119683 | 0.515000 | 1.09 | 0.515000 | 0.500000 | 0.003183 | 0.000094 | 1.09 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114276 | 0.515000 | 1.14 | 0.515000 | 0.500000 | 0.003334 | 0.000098 | 1.14 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.062339 | 0.515000 | 1.17 | 0.515000 | 0.500000 | 0.010993 | 0.000064 | 1.17 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.818584 | 0.383637 | 0.515000 | 0.421571 | 1.00 | 0.500000 | 0.000993 | 0.000067 | 0.421571 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8181.90 | 0.000072 | 172.59 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3470.60 | 0.000030 | 80.24 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1357.75 | 0.000012 | 30.22 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1826.66 | 0.000016 | 45.31 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1167.94 | 0.000010 | 29.66 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10583.94 | 0.000093 | 223.04 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10533.55 | 0.000092 | 234.20 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 27207.31 | 0.000238 | 597.44 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4878.63 | 0.000043 | 139.42 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4883.21 | 0.000043 | 139.55 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 27921.03 | 0.000244 | 797.92 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 28021.21 | 0.000245 | 800.78 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4868.88 | 0.000043 | 139.14 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4873.46 | 0.000043 | 139.27 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12009.87 | 0.000105 | 276.45 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1506.58 | 0.000013 | 43.05 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1507.70 | 0.000013 | 43.08 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7239.41 | 0.000063 | 206.88 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10777.16 | 0.000094 | 235.76 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11147.20 | 0.000098 | 243.54 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7317.56 | 0.000064 | 154.18 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7605.64 | 0.000067 | 182.10 |
VAV WITH REHEAT HEATING COIL | 169910.11 | 0.001486 | 2899.15 |
FLR_3_DOAS HEATING COIL | 15471.26 | 0.000135 | 263.98 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.18 | 0.000043 | 0.000371 |
ROOM_2_FLR_3 FAN COIL | 1.06 | 0.000043 | 0.000333 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.44 | 0.000244 | 0.002608 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.38 | 0.000245 | 0.001784 |
ROOM_5_FLR_3 FAN COIL | 1.07 | 0.000043 | 0.000338 |
ROOM_6_FLR_3 FAN COIL | 0.968200 | 0.000043 | 0.000305 |
ROOM_1_FLR_6 FAN COIL | 0.310433 | 0.000013 | 0.000098 |
ROOM_2_FLR_6 FAN COIL | 0.276053 | 0.000013 | 0.000087 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.72 | 0.000063 | 0.000547 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.18 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.44 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.38 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.07 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.968200 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.310433 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.276053 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.72 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008560 | 12.80 | 0.008500 | 0.000371 | 1.18 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008567 | 12.80 | 0.008500 | 0.000333 | 1.06 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008499 | 12.80 | 0.008499 | 0.002608 | 8.44 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008757 | 12.80 | 0.008500 | 0.001784 | 5.38 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.000338 | 1.07 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008573 | 12.80 | 0.008500 | 0.000305 | 0.968200 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.000098 | 0.310433 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000087 | 0.276053 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008595 | 12.80 | 0.008500 | 0.000547 | 1.72 | |
VAV WITH REHEAT COOLING COIL | 25.24 | 6.70 | 0.008988 | 10.96 | 0.008500 | 0.012140 | 22.53 | 424478.77 |
FLR_3_DOAS COOLING COIL | 26.40 | 6.70 | 0.008407 | 11.92 | 0.008407 | 0.001033 | 2.05 | 36112.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.65 | 11.66 | 22.53 | 22.53 | 0.300000 | 0.517772 | 22.53 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.53 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.53 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.012140 | 0.000039 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001486 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001033 | 0.000461 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000135 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.019644 | 3207.19 | |
HEATSYS1 PUMP | 0.003362 | 1012.41 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003362 | 0.403410 |
COOLSYS1 | 0.019644 | 2.36 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 384268.55 | 384268.55 | 0.003362 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.019644 | 2220.45 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.019644 | 686840.63 | 687464.38 | 78.37 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.38_SHGC_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1603 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.1706E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1831 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1067 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1066 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3266E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3971E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4607E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1825 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1094 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2092 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1269 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1179 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3891E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.9373E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9973E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.0209E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.3231E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0980E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7593E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9478E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1762E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3283E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5348E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.0209E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.3231E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0980E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7593E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9478E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1762E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3283E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5348E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33943.01453 | 33943.01453 | 2.49270 | 2.49270 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1476.18913 | 1476.18913 | 6.39534E-002 | 0.85446 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6115.21157 | 6115.21157 | 0.44912 | 0.44912 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2263.61159 | 2263.61159 | 9.80632E-002 | 9.80632E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3107.40666 | 3107.40666 | 0.22823 | 0.22823 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 744.45752 | 744.45752 | 3.22518E-002 | 9.17347E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2301.46263 | 2301.46263 | 0.16900 | 0.16900 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1372.65377 | 1372.65377 | 5.94667E-002 | 5.94667E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1350.74568 | 1350.74568 | 9.91859E-002 | 9.91859E-002 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 901.43693 | 901.43693 | 3.90524E-002 | 5.77652E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44601.78168 | 44601.78168 | 3.27540 | 3.27540 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1785.67773 | 1785.67773 | 7.73583E-002 | 7.73583E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24308.95499 | 24308.95499 | 1.78675 | 1.78675 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5731.13052 | 5731.13052 | 0.24828 | 0.67639 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69965.50564 | 69965.50564 | 5.14003 | 5.14003 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13393.69475 | 13393.69475 | 0.58025 | 1.89399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11921.25023 | 11921.25023 | 1.17969 | 1.17969 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 25.36867 | 8.40546E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4878.71661 | 4878.71661 | 0.21259 | 0.21259 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10684.04341 | 10684.04341 | 1.05726 | 1.05726 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4883.29431 | 4883.29431 | 0.21279 | 0.21279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 85259.28889 | 85259.28889 | 8.43661 | 8.43661 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 27921.25642 | 27921.25642 | 1.21672 | 1.21672 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54415.84785 | 54415.84785 | 5.38499 | 5.38499 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 28021.43756 | 28021.43756 | 1.22109 | 1.22109 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10845.66933 | 10845.66933 | 1.07325 | 1.07325 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4868.95955 | 4868.95955 | 0.21217 | 0.21217 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9784.07598 | 9784.07598 | 0.96820 | 0.96820 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4873.53913 | 4873.53913 | 0.21237 | 0.21237 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21735.08737 | 21735.08737 | 1.59613 | 1.59613 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7719.30404 | 7719.30404 | 0.33442 | 0.47476 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3137.05838 | 3137.05838 | 0.31043 | 0.31043 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49000 | 8.40565E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1506.60273 | 1506.60273 | 6.56515E-002 | 6.56515E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2789.63139 | 2789.63139 | 0.27605 | 0.27605 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1507.72960 | 1507.72960 | 6.57006E-002 | 6.57006E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17407.39801 | 17407.39801 | 1.72262 | 1.72262 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7239.50525 | 7239.50525 | 0.31547 | 0.31547 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28718.88030 | 28718.88030 | 2.11160 | 2.11160 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5100.10423 | 5100.10423 | 0.22095 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30078.05662 | 30078.05662 | 2.21151 | 2.21151 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5201.95037 | 5201.95037 | 0.22536 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30847.84029 | 30847.84029 | 2.27120 | 2.27120 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1241.92595 | 1241.92595 | 5.37951E-002 | 0.36735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11147.03914 | 11147.03914 | 0.81858 | 0.81858 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5404.73341 | 5404.73341 | 0.23415 | 0.23415 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | -4.30000 | 2.65759E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 335331.02 | 22.52819 | 22.52819 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 182545.09 | 7.26103 | 7.26103 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 33397.10 | 19.09445 | 2.05125 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51569.06 | 3.73456 | 2.05125 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49270 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60491 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28374 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.29841E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.15788E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28374 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8181.89785 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15788E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.58979 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44912 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11380 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23130 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34809E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03623E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23130 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3470.59983 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03623E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 80.24463 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22823 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25932 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11754 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69152 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46922E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18782E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11754 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1357.74857 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18782E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.22206 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.16900 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74057 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.70330E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.14469E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59804E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.70330E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1826.65954 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59804E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.31332 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.91859E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72799 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.10807E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.23357E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02176E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.10807E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1167.93715 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02176E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.65994 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.27540 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.81553E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68683 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09856E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.25930E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68683 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10583.94342 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.25930E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.03658 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.78675 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.05444E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.92018 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.73031E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.21521E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.92018 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10533.54739 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.21521E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 234.20283 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.14003 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19394 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.64712 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51716 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96456E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38021E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.64712 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27207.30768 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38021E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 597.44126 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17969 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.17969 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.26804E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.70850E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68925 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56044E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.70850E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17969 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4878.63413 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26804E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 139.42233 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05726 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05726 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.27205E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.32991E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68924 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56730E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.32991E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05726 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4883.21175 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.27205E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 139.55311 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.43661 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.43661 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.44265E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.60813E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68967 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49873E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49873E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60813E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.43661 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 27921.02683 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44265E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 797.91660 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.38499 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.38499 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.45142E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.78431E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68876 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75680E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.78431E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.38499 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 28021.20719 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45142E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 800.77878 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07325 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07325 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.25951E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.37942E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68925 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56637E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.37942E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07325 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4868.87722 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25951E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 139.14357 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96820 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.96820 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.26351E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.05441E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68923 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57326E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.05441E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.96820 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4873.45673 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26351E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 139.27441 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59613 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74361 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82201 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.12363E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05068E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82201 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12009.86510 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05068E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.45431 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31043 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31043 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.31802E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.75086E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68926 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55746E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.75086E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31043 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1506.57805 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31802E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.05275 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27605 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27605 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.31901E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.68789E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68925 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56454E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.68789E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27605 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1507.70490 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31901E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.08495 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.72262 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.72262 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.33335E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.46665E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68902 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59497E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.46665E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.72262 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7239.40992 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.33335E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 206.87522 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11160 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11968 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.08748 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18341E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.42833E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08748 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10777.16287 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.42833E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.76135 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21151 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11428 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13893 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33402E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.75206E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13893 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11147.20020 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.75206E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 243.54145 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27120 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.23389E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16967 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09928E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.40172E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16967 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7317.56465 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.40172E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 154.17540 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81858 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38364 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42157 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.93127E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.65374E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42157 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7605.63728 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.65374E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.09591 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66446 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66446 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.64944 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66446 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.52819 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.52819 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51777 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.52819 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.52819 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.23759 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95895 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.98751E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 424478.77474 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.21400E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.52819 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 169910.11171 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48645E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2899.14574 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.52819 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.21400E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.92248E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.48645E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91985 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 36112.10278 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03280E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15471.26131 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35349E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 263.98335 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03280E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.61067E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.35349E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.96436E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3207.19231 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.36175E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.40341 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.36175E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1012.41114 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 384268.55129 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 384268.55000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.36175E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.96436E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.35723 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.96436E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2220.44741 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.96436E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 686840.63247 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 687464.38000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 78.37094 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8223.74 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3486.61 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1364.26 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1834.40 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1172.77 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10638.11 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10584.10 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 27339.56 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5254.90 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5259.83 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30074.24 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 30182.13 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5244.40 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5249.33 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12065.52 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1622.72 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1623.93 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7797.46 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10830.50 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11202.43 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7355.02 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7639.09 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129269.88 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11770.74 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19207.78 | 16622.44 | 2585.34 | 0.87 | 3743.68 | 37.97 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17236.55 | 14905.01 | 2331.53 | 0.86 | 3353.45 | 34.01 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 135789.05 | 118330.09 | 17458.96 | 0.87 | 26888.42 | 272.72 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 90879.07 | 77016.49 | 13862.58 | 0.85 | 16938.33 | 171.80 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17494.24 | 15129.43 | 2364.81 | 0.86 | 3404.41 | 34.53 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15802.24 | 13655.59 | 2146.65 | 0.86 | 3069.64 | 31.13 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5051.67 | 4373.19 | 678.48 | 0.87 | 985.37 | 9.99 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4498.18 | 3890.93 | 607.25 | 0.87 | 875.77 | 8.88 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28228.76 | 24335.39 | 3893.37 | 0.86 | 5453.30 | 55.31 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 527520.75 | 382595.88 | 144924.87 | 0.73 | 88242.56 | 895.01 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 44891.31 | 33390.37 | 11500.94 | 0.74 | 6895.25 | 69.94 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8575225577E-002 | 2.3039927773E-002 | Pass | Pass | 5.5316188086E-003 | 1.7938865682E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3881991019E-002 | 4.3883204548E-002 | Pass | Pass | 5.8861923876E-002 | 8.7597331897E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6786472628E-002 | 2.8111919081E-002 | Pass | Pass | 7.3145219815E-003 | 2.0166190143E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7498512692E-003 | 9.3467051802E-003 | Pass | Pass | 2.5797152567E-002 | 5.5586194328E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8679324338E-004 | 2.2687983562E-004 | Pass | Pass | 5.7889508252E-002 | 9.7832208929E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0937144228E-002 | 0.2039668034 | Pass | Pass | 1.9420542505E-002 | 5.2323197119E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2116998771E-002 | 7.1590639012E-002 | Pass | Pass | 1.8002834673E-002 | 3.9001306777E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7107493599E-002 | 4.2269474247E-002 | Pass | Pass | 8.0317780971E-003 | 1.8983168722E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0125010601E-002 | 0.1196603478 | Pass | Pass | 0.3624361559 | 2.0917044704 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5101402628E-002 | 0.2072210242 | Pass | Pass | 0.1117876461 | 0.4832183952 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5118434918E-002 | 4.0688581616E-002 | Pass | Pass | 5.9123540666E-002 | 0.2053458872 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3773562262E-002 | 7.7888201567E-002 | Pass | Pass | 0.3481741091 | 2.3143225886 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8853728850E-002 | 0.1206167721 | Pass | Pass | 0.1297309485 | 0.8380251775 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9831040918E-002 | 0.2020646435 | Pass | Pass | 0.1952674644 | 0.8349094688 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.1005542971E-003 | 3.2241200078E-003 | Pass | Pass | 3.0911780339E-002 | 5.2270040802E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6681465535E-002 | 0.1815810809 | Pass | Pass | 0.1063067624 | 0.4185881137 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.0519494944E-002 | 0.2708344171 | Pass | Pass | 0.1084931693 | 0.3500504868 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.2153119693E-002 | 0.2234118034 | Pass | Pass | 0.3324539276 | 1.5155340836 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.2910950678E-002 | 7.0341857445E-002 | Pass | Pass | 1.3156428184E-002 | 4.0110364560E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2392937619E-002 | 5.6193283126E-002 | Pass | Pass | 1.3839887312E-002 | 4.0636603543E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1900104168E-002 | 6.5139399861E-002 | Pass | Pass | 2.0854420925E-002 | 4.2297397127E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9933857495E-003 | 1.3278563972E-002 | Pass | Pass | 3.0997144374E-002 | 3.8435523672E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3449.09 | 151.41 | 2073.36 | 8470.83 | 1895.57 | 16040.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.381 | 0.420 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.381 | 0.420 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.381 | 0.420 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.381 | 0.420 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.73 | 0.0000 | Y | 14.10 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.58 | 0.0000 | Y | 109.92 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.45 | 0.0000 | Y | 30.82 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.45 | 0.0000 | Y | 30.82 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.33 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.54 | 83.54 | 193.49 | |
Exterior Lighting Total | 12338.45 | 193.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 384268.55 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 687464.38 | 2.96 | 687585.22 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12967.09 | 19207.78 | 16622.44 | 2585.34 | 0.87 | - | 3743.68 | 37.97 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11643.31 | 17236.55 | 14905.01 | 2331.53 | 0.86 | - | 3353.45 | 34.01 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 91195.39 | 135789.05 | 118330.09 | 17458.96 | 0.87 | - | 26888.42 | 272.72 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62389.90 | 90879.07 | 77016.49 | 13862.58 | 0.85 | - | 16938.33 | 171.80 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11816.42 | 17494.24 | 15129.43 | 2364.81 | 0.86 | - | 3404.41 | 34.53 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10680.00 | 15802.24 | 13655.59 | 2146.65 | 0.86 | - | 3069.64 | 31.13 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3409.47 | 5051.67 | 4373.19 | 678.48 | 0.87 | - | 985.37 | 9.99 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3037.80 | 4498.18 | 3890.93 | 607.25 | 0.87 | - | 875.77 | 8.88 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 19114.61 | 28228.76 | 24335.39 | 3893.37 | 0.86 | - | 5453.30 | 55.31 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 424478.77 | 527520.75 | 382595.88 | 144924.87 | 0.73 | - | 88242.56 | 895.01 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 36112.10 | 44891.31 | 33390.37 | 11500.94 | 0.74 | - | 6895.25 | 69.94 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8181.90 | 8223.74 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3470.60 | 3486.61 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1357.75 | 1364.26 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1826.66 | 1834.40 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1167.94 | 1172.77 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10583.94 | 10638.11 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10533.55 | 10584.10 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27207.31 | 27339.56 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4878.63 | 5254.90 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4883.21 | 5259.83 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 27921.03 | 30074.24 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 28021.21 | 30182.13 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4868.88 | 5244.40 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4873.46 | 5249.33 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12009.87 | 12065.52 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1506.58 | 1622.72 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1507.70 | 1623.93 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7239.41 | 7797.46 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10777.16 | 10830.50 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11147.20 | 11202.43 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7317.56 | 7355.02 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7605.64 | 7639.09 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 169910.11 | 129269.88 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15471.26 | 11770.74 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 830.07 | 703.64 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 743.92 | 703.64 | 1.00 | 1.18 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.44 | 5936.30 | 703.64 | 1.00 | 0.94 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.38 | 3789.08 | 703.64 | 1.00 | 0.97 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 755.18 | 703.64 | 1.00 | 1.18 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 681.26 | 703.64 | 1.00 | 1.20 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 218.43 | 703.64 | 1.00 | 1.69 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 194.24 | 703.64 | 1.00 | 1.77 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.72 | 1212.10 | 703.64 | 1.00 | 1.09 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.53 | 50477.54 | 2240.64 | 1.00 | 1.11 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.019644 | 3207.19 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003362 | 1012.41 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.019644 | 2220.45 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33943.01 | 33943.01 | 17.15 | 2.493 | 2.493 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 24.00 | 24.00 | 0.00921 | 23.31 | 0.00840 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6115.21 | 6115.21 | 91.17 | 0.449 | 0.449 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00889 | 26.17 | 0.00841 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3107.41 | 3107.41 | 40.01 | 0.228 | 0.228 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00940 | 26.22 | 0.00841 | 0.092 | 0.00 |
MECH_FLR_1 | 2301.46 | 2301.46 | 14.01 | 0.169 | 0.169 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00875 | 26.22 | 0.00841 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1350.75 | 1350.75 | 14.25 | 0.099 | 0.099 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00882 | 26.40 | 0.00841 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44601.78 | 44601.78 | 571.53 | 3.275 | 3.275 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00854 | 26.40 | 0.00841 | 0.000 | 0.00 |
CAFE_FLR_1 | 24308.95 | 24308.95 | 128.71 | 1.787 | 1.787 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00981 | 26.17 | 0.00841 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69965.51 | 69965.51 | 53.48 | 5.140 | 5.140 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00985 | 26.25 | 0.00841 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11921.25 | 11921.25 | 305.50 | 1.180 | 1.180 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00856 | 25.37 | 0.00841 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10684.04 | 10684.04 | 273.83 | 1.057 | 1.057 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 25.13 | 0.00841 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 85259.29 | 85259.29 | 3476.59 | 8.437 | 8.437 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 26.17 | 0.00841 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54415.85 | 54415.85 | 2218.29 | 5.385 | 5.385 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00876 | 26.40 | 0.00841 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10845.67 | 10845.67 | 277.94 | 1.073 | 1.073 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 22.94 | 0.00840 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9784.08 | 9784.08 | 250.76 | 0.968 | 0.968 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00857 | 21.65 | 0.00840 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21735.09 | 21735.09 | 55.82 | 1.596 | 1.596 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00936 | 26.40 | 0.00841 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3137.06 | 3137.06 | 80.39 | 0.310 | 0.310 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 25.49 | 0.00841 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2789.63 | 2789.63 | 71.50 | 0.276 | 0.276 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00856 | 25.13 | 0.00841 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17407.40 | 17407.40 | 709.62 | 1.723 | 1.723 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00859 | 26.25 | 0.00841 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28718.88 | 28718.88 | 86.59 | 2.112 | 2.112 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01045 | 26.40 | 0.00841 | 1.188 | 0.00 |
DINING_FLR_6 | 30078.06 | 30078.06 | 90.69 | 2.212 | 2.212 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01037 | 26.40 | 0.00841 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30847.84 | 30847.84 | 298.61 | 2.271 | 2.271 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 25.58 | 0.00841 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11147.04 | 11147.04 | 27.05 | 0.819 | 0.819 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00894 | 26.40 | 0.00841 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1476.19 | 1476.19 | 0.75 | 0.064 | 0.854 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -4.30 | 0.00266 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2263.61 | 2263.61 | 33.75 | 0.098 | 0.098 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00748 | -4.30 | 0.00266 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 744.46 | 744.46 | 9.59 | 0.032 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -4.30 | 0.00266 | 0.092 | 0.00 |
MECH_FLR_1 | 1372.65 | 1372.65 | 8.36 | 0.059 | 0.059 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00725 | -4.30 | 0.00266 | 0.000 | 0.00 |
STORAGE_FLR_1 | 901.44 | 901.44 | 9.51 | 0.039 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00733 | -4.30 | 0.00266 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1785.68 | 1785.68 | 22.88 | 0.077 | 0.077 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00722 | -4.30 | 0.00266 | 0.000 | 0.00 |
CAFE_FLR_1 | 5731.13 | 5731.13 | 30.35 | 0.248 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00754 | -4.30 | 0.00266 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13393.69 | 13393.69 | 10.24 | 0.580 | 1.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00745 | -4.30 | 0.00266 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4878.72 | 4878.72 | 125.02 | 0.213 | 0.213 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00744 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4883.29 | 4883.29 | 125.16 | 0.213 | 0.213 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00744 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27921.26 | 27921.26 | 1138.54 | 1.217 | 1.217 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00748 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 28021.44 | 28021.44 | 1142.31 | 1.221 | 1.221 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00748 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4868.96 | 4868.96 | 124.77 | 0.212 | 0.212 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00744 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4873.54 | 4873.54 | 124.91 | 0.212 | 0.212 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00744 | -4.30 | 0.00266 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7719.30 | 7719.30 | 19.82 | 0.334 | 0.475 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00756 | -4.30 | 0.00266 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1506.60 | 1506.60 | 38.61 | 0.066 | 0.066 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1507.73 | 1507.73 | 38.64 | 0.066 | 0.066 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7239.51 | 7239.51 | 295.12 | 0.315 | 0.315 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00756 | -4.30 | 0.00266 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5100.10 | 5100.10 | 15.38 | 0.221 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00766 | -4.30 | 0.00266 | 1.188 | 0.00 |
DINING_FLR_6 | 5201.95 | 5201.95 | 15.68 | 0.225 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 21.00 | 21.00 | 0.00766 | -4.30 | 0.00266 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1241.93 | 1241.93 | 12.02 | 0.054 | 0.367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00538 | -4.30 | 0.00266 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5404.73 | 5404.73 | 13.11 | 0.234 | 0.234 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 21.00 | 21.00 | 0.00771 | -4.30 | 0.00266 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.53 | 22.53 | 7.26 | 7.26 | 22.5282 | 11.6645 | 22.5282 | 0.5178 | 0.3000 |
FLR_3_DOAS | 19.09 | 2.05 | 3.73 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8181.898 | 8181.898 | 1.283738 | 0.00007158 | 172.590 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8181.90 | 8181.90 | 1.283738 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00796855 | 50.9692 | 1476.19 | 0.00 | 8227.70 | 8227.70 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3470.600 | 3470.600 | 0.231298 | 0.00003036 | 80.245 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3470.60 | 3470.60 | 0.231298 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00747691 | 47.8633 | 2263.61 | 0.00 | 3489.18 | 3489.18 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1357.749 | 1357.749 | 0.117536 | 0.00001188 | 30.222 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1357.75 | 1357.75 | 0.117536 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00739630 | 47.3525 | 744.46 | 0.00 | 1365.12 | 1365.12 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1826.660 | 1826.660 | 0.087033 | 0.00001598 | 45.313 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1826.66 | 1826.66 | 0.087033 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00725004 | 46.4270 | 1372.65 | 0.00 | 1836.10 | 1836.10 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1167.937 | 1167.937 | 0.051081 | 0.00001022 | 29.660 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1167.94 | 1167.94 | 0.051081 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00732972 | 46.9313 | 901.44 | 0.00 | 1173.93 | 1173.93 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10583.943 | 10583.943 | 1.686833 | 0.00009259 | 223.037 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 10583.94 | 10583.94 | 1.686833 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00721827 | 46.2267 | 1785.68 | 0.00 | 10643.21 | 10643.21 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10533.547 | 10533.547 | 0.920177 | 0.00009215 | 234.203 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 10533.55 | 10533.55 | 0.920177 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00753755 | 48.2466 | 5731.13 | 0.00 | 10590.75 | 10590.75 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 27207.308 | 27207.308 | 2.647117 | 0.00023802 | 597.441 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 27207.31 | 27207.31 | 2.647117 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00744528 | 47.6624 | 13393.69 | 0.00 | 27355.81 | 27355.81 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12967.087 | -999.000 | 1.179686 | 0.00037085 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 12967.09 | 12779.51 | 1.179686 | 21.69 | 15.50 | 0.00856044 | 12.80 | 12.00 | 0.00850000 | 25.37 | 0.00840546 | 16.68 | 0.0000 | 21.11 | 0.00856044 | 54.3331 | 11921.25 | 0.00 | 13113.19 | 13113.19 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4878.634 | 4878.634 | 0.212594 | 0.00004268 | 139.422 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 4878.63 | 4878.63 | 0.212594 | 21.11 | 14.28 | 0.00744367 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00744367 | 47.3295 | 4878.72 | 0.00 | 5259.29 | 5259.29 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11643.308 | -999.000 | 1.057257 | 0.00033299 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 11643.31 | 11456.06 | 1.057257 | 21.69 | 15.51 | 0.00856730 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856730 | 54.3760 | 10684.04 | 0.00 | 11774.22 | 11774.22 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4883.212 | 4883.212 | 0.212794 | 0.00004272 | 139.553 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 4883.21 | 4883.21 | 0.212794 | 21.11 | 14.28 | 0.00744418 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00744418 | 47.3327 | 4883.29 | 0.00 | 5264.23 | 5264.23 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 91195.393 | -999.000 | 8.436606 | 0.00260813 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 91195.39 | 91195.39 | 8.436606 | 21.69 | 15.45 | 0.00849873 | 12.80 | 12.00 | 0.00849873 | 26.17 | 0.00840672 | 16.96 | 0.0000 | 21.11 | 0.00849873 | 53.9455 | 85259.29 | 0.00 | 92222.24 | 92222.24 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 27921.027 | 27921.027 | 1.216723 | 0.00024427 | 797.917 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 27921.03 | 27921.03 | 1.216723 | 21.11 | 14.31 | 0.00748068 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00748068 | 47.5610 | 27921.26 | 0.00 | 30099.74 | 30099.74 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62389.902 | -999.000 | 5.384993 | 0.00178431 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 62389.90 | 58727.09 | 5.384993 | 21.69 | 15.67 | 0.00875680 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 0.0000 | 21.11 | 0.00875680 | 55.5631 | 54415.85 | 0.00 | 63077.71 | 61802.68 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 28021.207 | 28021.207 | 1.221088 | 0.00024514 | 800.779 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 28021.21 | 28021.21 | 1.221088 | 21.11 | 14.31 | 0.00748222 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00748222 | 47.5708 | 28021.44 | 0.00 | 30207.73 | 30207.73 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11816.418 | -999.000 | 1.073250 | 0.00033794 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 11816.42 | 11628.97 | 1.073250 | 21.69 | 15.51 | 0.00856637 | 12.80 | 12.00 | 0.00850000 | 22.94 | 0.00840167 | 15.82 | 0.0000 | 21.11 | 0.00856637 | 54.3702 | 10845.67 | 0.00 | 11949.32 | 11949.32 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4868.877 | 4868.877 | 0.212169 | 0.00004260 | 139.144 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 4868.88 | 4868.88 | 0.212169 | 21.11 | 14.28 | 0.00744267 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00744267 | 47.3232 | 4868.96 | 0.00 | 5248.77 | 5248.77 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10679.997 | -999.000 | 0.968200 | 0.00030544 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 10680.00 | 10493.30 | 0.968200 | 21.69 | 15.51 | 0.00857326 | 12.80 | 12.00 | 0.00850000 | 21.65 | 0.00839969 | 15.35 | 0.0000 | 21.11 | 0.00857326 | 54.4134 | 9784.08 | 0.00 | 10799.87 | 10799.87 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4873.457 | 4873.457 | 0.212368 | 0.00004264 | 139.274 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 4873.46 | 4873.46 | 0.212368 | 21.11 | 14.28 | 0.00744318 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00744318 | 47.3264 | 4873.54 | 0.00 | 5253.71 | 5253.71 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12009.865 | 12009.865 | 0.822008 | 0.00010507 | 276.454 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 12009.87 | 12009.87 | 0.822008 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00756176 | 48.3988 | 7719.30 | 0.00 | 12074.26 | 12074.26 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3409.470 | -999.000 | 0.310433 | 0.00009751 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3409.47 | 3362.55 | 0.310433 | 21.69 | 15.50 | 0.00855746 | 12.80 | 12.00 | 0.00850000 | 25.49 | 0.00840565 | 16.72 | 0.0000 | 21.11 | 0.00855746 | 54.3144 | 3137.06 | 0.00 | 3447.92 | 3447.92 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1506.578 | 1506.578 | 0.065651 | 0.00001318 | 43.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1506.58 | 1506.58 | 0.065651 | 21.11 | 14.37 | 0.00754043 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00754043 | 47.9373 | 1506.60 | 0.00 | 1624.13 | 1624.13 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3037.795 | -999.000 | 0.276053 | 0.00008688 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 3037.80 | 2990.91 | 0.276053 | 21.69 | 15.51 | 0.00856454 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856454 | 54.3588 | 2789.63 | 0.00 | 3071.98 | 3071.98 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1507.705 | 1507.705 | 0.065701 | 0.00001319 | 43.085 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1507.70 | 1507.70 | 0.065701 | 21.11 | 14.37 | 0.00754077 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00754077 | 47.9395 | 1507.73 | 0.00 | 1625.34 | 1625.34 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 19114.610 | -999.000 | 1.722617 | 0.00054667 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 19114.61 | 18683.66 | 1.722617 | 21.69 | 15.53 | 0.00859497 | 12.80 | 12.00 | 0.00850000 | 26.25 | 0.00840684 | 16.99 | 0.0000 | 21.11 | 0.00859497 | 54.5499 | 17407.40 | 0.00 | 19327.80 | 19327.80 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7239.410 | 7239.410 | 0.315470 | 0.00006333 | 206.875 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 7239.41 | 7239.41 | 0.315470 | 21.11 | 14.38 | 0.00755801 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00755801 | 48.0475 | 7239.51 | 0.00 | 7804.28 | 7804.28 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10777.163 | 10777.163 | 1.087475 | 0.00009428 | 235.761 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 10777.16 | 10777.16 | 1.087475 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00765849 | 49.0107 | 5100.10 | 0.00 | 10836.82 | 10836.82 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11147.200 | 11147.200 | 1.138925 | 0.00009752 | 243.541 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 11147.20 | 11147.20 | 1.138925 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00766475 | 49.0513 | 5201.95 | 0.00 | 11208.93 | 11208.93 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7317.565 | 7317.565 | 1.169670 | 0.00006402 | 154.175 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7317.56 | 7317.56 | 1.169670 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00537861 | 34.5533 | 1241.93 | 0.00 | 7358.54 | 7358.54 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7605.637 | 7605.637 | 0.421571 | 0.00006654 | 182.096 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 7605.64 | 7605.64 | 0.421571 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00771447 | 49.3651 | 5404.73 | 0.00 | 7645.44 | 7645.44 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 424478.775 | -999.000 | 22.528192 | 0.01214004 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 424478.77 | 390079.76 | 22.528192 | 25.24 | 17.12 | 0.00898751 | 10.96 | 10.96 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 51.7639 | 23.99 | 0.00956771 | 50.8924 | 306474.72 | 0.00 | 428343.03 | 379600.21 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 169910.112 | 169910.112 | 6.758458 | 0.00148645 | 2899.146 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 169910.11 | 169910.11 | 6.758458 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 172.5462 | 21.02 | 0.00752704 | 48.1181 | 51922.90 | 0.00 | 156352.66 | 156352.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 36112.10 | 36112.10 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 11.92 | 11.55 | 0.00840708 | 26.40 | 0.00840708 | 17.04 | 99.9965 | 21.11 | 0.00860017 | 54.5815 | 192959.04 | 0.00 | 36442.34 | 36442.34 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 15471.26 | 15471.26 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 333.3216 | 21.11 | 0.00748195 | 47.5691 | 85701.04 | 0.00 | 14236.78 | 14236.78 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8181.898 | 8181.898 | 1.283738 | 0.00007158 | 172.590 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 2.0872 | 2.129213 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8181.90 | 8181.90 | 1.0000 | 1.52940992 | 1.283738 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.07157151 | 60.00 | 32.22 | 27.78 | 0.000 | 8181.90 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796855 | 21.00 | 0.00796855 | 50.9692 | 1476.19 | 0.00 | 8227.70 | 8227.70 | 1.52940992 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.88 | 15.18 | 0.00800000 | 42314.4 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3470.600 | 3470.600 | 0.231298 | 0.00003036 | 80.245 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.8854 | 0.903170 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3470.60 | 3470.60 | 1.0000 | 0.27556192 | 0.231298 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03035922 | 60.00 | 32.22 | 27.78 | 0.000 | 3470.60 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00747691 | 21.00 | 0.00747691 | 47.8633 | 2263.61 | 0.00 | 3489.18 | 3489.18 | 0.27556192 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.02 | 17.71 | 0.00800000 | 49596.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1357.749 | 1357.749 | 0.117536 | 0.00001188 | 30.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.3464 | 0.353333 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1357.75 | 1357.75 | 1.0000 | 0.14002921 | 0.117536 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01187697 | 60.00 | 32.22 | 27.78 | 0.000 | 1357.75 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00739630 | 21.00 | 0.00739630 | 47.3525 | 744.46 | 0.00 | 1365.12 | 1365.12 | 0.14002921 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.16 | 16.72 | 0.00800000 | 46683.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1826.660 | 1826.660 | 0.087033 | 0.00001598 | 45.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.4660 | 0.475360 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1826.66 | 1826.66 | 1.0000 | 0.10368868 | 0.087033 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01597878 | 60.00 | 32.22 | 27.78 | 0.000 | 1826.66 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00725004 | 21.00 | 0.00725004 | 46.4270 | 1372.65 | 0.00 | 1836.10 | 1836.10 | 0.10368868 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.97 | 19.33 | 0.00800000 | 54642.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1167.937 | 1167.937 | 0.051081 | 0.00001022 | 29.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.2979 | 0.303938 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1167.94 | 1167.94 | 1.0000 | 0.06085616 | 0.051081 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01021658 | 60.00 | 32.22 | 27.78 | 0.000 | 1167.94 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00732972 | 21.00 | 0.00732972 | 46.9313 | 901.44 | 0.00 | 1173.93 | 1173.93 | 0.06085616 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.52 | 19.82 | 0.00800000 | 56225.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10583.943 | 10583.943 | 1.686833 | 0.00009259 | 223.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 2.7000 | 2.754309 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 10583.94 | 10583.94 | 1.0000 | 2.00964571 | 1.686833 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09258351 | 60.00 | 32.22 | 27.78 | 0.000 | 10583.94 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00721827 | 21.00 | 0.00721827 | 46.2267 | 1785.68 | 0.00 | 10643.21 | 10643.21 | 2.00964571 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.79 | 15.15 | 0.00800000 | 42230.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10533.547 | 10533.547 | 0.920177 | 0.00009215 | 234.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 2.6871 | 2.741194 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 10533.55 | 10533.55 | 1.0000 | 1.09627288 | 0.920177 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09214267 | 60.00 | 32.22 | 27.78 | 0.000 | 10533.55 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00753755 | 21.00 | 0.00753755 | 48.2466 | 5731.13 | 0.00 | 10590.75 | 10590.75 | 1.09627288 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.07 | 16.69 | 0.00800000 | 46595.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27207.308 | 27207.308 | 2.647117 | 0.00023802 | 597.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 6.9406 | 7.080285 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 27207.31 | 27207.31 | 1.0000 | 3.15370122 | 2.647117 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.23799712 | 60.00 | 32.22 | 27.78 | 0.000 | 27207.31 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00744528 | 21.00 | 0.00744528 | 47.6624 | 13393.69 | 0.00 | 27355.81 | 27355.81 | 3.15370122 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.11 | 16.35 | 0.00800000 | 45608.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12967.087 | -999.000 | 1.179686 | 0.00037085 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7534 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.179686 | 1.40544499 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 1.8879 | 1.887897 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 12967.09 | 12779.51 | 1.0000 | 1.40544499 | 1.179686 | 21.69 | 15.50 | 0.00856044 | 43548.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.37081228 | 6.70 | 15.03 | 8.33 | 0.000 | 12967.09 | 25.37 | 0.00840546 | 16.68 | 0.00000000 | 0.0000 | 21.11 | 0.00856044 | 21.11 | 0.00856044 | 54.3331 | 11921.25 | 0.00 | 13113.19 | 13113.19 | 1.40544499 | 21.69 | 15.61 | 0.00856044 | 43548.5 | 12.55 | 12.06 | 0.00856044 | 34218.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4878.634 | 4878.634 | 0.212594 | 0.00004268 | 139.422 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.179686 | 1.40544499 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.2445 | 1.269590 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 4878.63 | 4878.63 | 1.0000 | 0.25327864 | 0.212594 | 21.11 | 14.28 | 0.00744367 | 40120.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04267607 | 60.00 | 32.22 | 27.78 | 0.000 | 4878.63 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00744367 | 21.11 | 0.00744367 | 47.3295 | 4878.72 | 0.00 | 5259.29 | 5259.29 | 0.25327864 | 16.60 | 12.61 | 0.00744367 | 35526.2 | 36.98 | 19.85 | 0.00744367 | 56291.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11643.308 | -999.000 | 1.057257 | 0.00033299 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7662 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057257 | 1.25958664 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 1.6952 | 1.695166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 11643.31 | 11456.06 | 1.0000 | 1.25958664 | 1.057257 | 21.69 | 15.51 | 0.00856730 | 43565.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.33295695 | 6.70 | 15.03 | 8.33 | 0.000 | 11643.31 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856730 | 21.11 | 0.00856730 | 54.3760 | 10684.04 | 0.00 | 11774.22 | 11774.22 | 1.25958664 | 21.69 | 15.62 | 0.00856730 | 43565.9 | 12.53 | 12.06 | 0.00856730 | 34218.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4883.212 | 4883.212 | 0.212794 | 0.00004272 | 139.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057257 | 1.25958664 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.2457 | 1.270781 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 4883.21 | 4883.21 | 1.0000 | 0.25351629 | 0.212794 | 21.11 | 14.28 | 0.00744418 | 40122.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04271611 | 60.00 | 32.22 | 27.78 | 0.000 | 4883.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00744418 | 21.11 | 0.00744418 | 47.3327 | 4883.29 | 0.00 | 5264.23 | 5264.23 | 0.25351629 | 16.60 | 12.61 | 0.00744418 | 35527.5 | 36.98 | 19.85 | 0.00744418 | 56292.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 91195.393 | -999.000 | 8.436606 | 0.00260813 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6387 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.436606 | 10.05113574 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 13.2775 | 13.277271 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 91195.39 | 91195.39 | 1.0000 | 10.05113574 | 8.436606 | 21.69 | 15.45 | 0.00849873 | 43392.1 | 12.80 | 12.00 | 0.00849873 | 34319.0 | 2.60786193 | 6.70 | 15.03 | 8.33 | 0.000 | 91195.39 | 26.17 | 0.00840672 | 16.96 | 0.00000000 | 0.0000 | 21.11 | 0.00849873 | 21.11 | 0.00849873 | 53.9455 | 85259.29 | 0.00 | 92222.24 | 92222.24 | 10.05113574 | 21.69 | 15.56 | 0.00849873 | 43392.1 | 12.70 | 12.06 | 0.00849873 | 34216.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27921.027 | 27921.027 | 1.216723 | 0.00024427 | 797.917 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.436606 | 10.05113574 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 7.1227 | 7.266019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 27921.03 | 27921.03 | 1.0000 | 1.44956918 | 1.216723 | 21.11 | 14.31 | 0.00748068 | 40215.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.24424041 | 60.00 | 32.22 | 27.78 | 0.000 | 27921.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00748068 | 21.11 | 0.00748068 | 47.5610 | 27921.26 | 0.00 | 30099.74 | 30099.74 | 1.44956918 | 16.60 | 12.64 | 0.00748068 | 35619.9 | 36.98 | 19.88 | 0.00748068 | 56384.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62389.902 | -999.000 | 5.384993 | 0.00178431 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1185 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.384993 | 6.41552962 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 9.0836 | 9.083437 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 62389.90 | 58727.09 | 1.0000 | 6.41552962 | 5.384993 | 21.69 | 15.67 | 0.00875680 | 44047.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 1.78412796 | 6.70 | 15.03 | 8.33 | 0.000 | 62389.90 | 26.40 | 0.00840708 | 17.04 | 0.00000000 | 0.0000 | 21.11 | 0.00875680 | 21.11 | 0.00875680 | 55.5631 | 54415.85 | 0.00 | 63077.71 | 61802.68 | 6.41552962 | 21.69 | 15.78 | 0.00875680 | 44047.0 | 12.25 | 12.05 | 0.00867805 | 34215.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28021.207 | 28021.207 | 1.221088 | 0.00024514 | 800.779 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.384993 | 6.41552962 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 7.1482 | 7.292090 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 28021.21 | 28021.21 | 1.0000 | 1.45477021 | 1.221088 | 21.11 | 14.31 | 0.00748222 | 40219.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.24511674 | 60.00 | 32.22 | 27.78 | 0.000 | 28021.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00748222 | 21.11 | 0.00748222 | 47.5708 | 28021.44 | 0.00 | 30207.73 | 30207.73 | 1.45477021 | 16.60 | 12.64 | 0.00748222 | 35623.8 | 36.98 | 19.88 | 0.00748222 | 56388.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11816.418 | -999.000 | 1.073250 | 0.00033794 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7645 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.073250 | 1.27864060 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 1.7204 | 1.720370 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 11816.42 | 11628.97 | 1.0000 | 1.27864060 | 1.073250 | 21.69 | 15.51 | 0.00856637 | 43563.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.33790728 | 6.70 | 15.03 | 8.33 | 0.000 | 11816.42 | 22.94 | 0.00840167 | 15.82 | 0.00000000 | 0.0000 | 21.11 | 0.00856637 | 21.11 | 0.00856637 | 54.3702 | 10845.67 | 0.00 | 11949.32 | 11949.32 | 1.27864060 | 21.69 | 15.62 | 0.00856637 | 43563.6 | 12.53 | 12.06 | 0.00856637 | 34218.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4868.877 | 4868.877 | 0.212169 | 0.00004260 | 139.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.073250 | 1.27864060 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.2421 | 1.267051 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 4868.88 | 4868.88 | 1.0000 | 0.25277210 | 0.212169 | 21.11 | 14.28 | 0.00744267 | 40118.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04259072 | 60.00 | 32.22 | 27.78 | 0.000 | 4868.88 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00744267 | 21.11 | 0.00744267 | 47.3232 | 4868.96 | 0.00 | 5248.77 | 5248.77 | 0.25277210 | 16.60 | 12.61 | 0.00744267 | 35523.7 | 36.98 | 19.85 | 0.00744267 | 56288.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10679.997 | -999.000 | 0.968200 | 0.00030544 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7773 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.968200 | 1.15348581 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 1.5549 | 1.554916 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 10680.00 | 10493.30 | 1.0000 | 1.15348581 | 0.968200 | 21.69 | 15.51 | 0.00857326 | 43581.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.30540971 | 6.70 | 15.03 | 8.33 | 0.000 | 10680.00 | 21.65 | 0.00839969 | 15.35 | 0.00000000 | 0.0000 | 21.11 | 0.00857326 | 21.11 | 0.00857326 | 54.4134 | 9784.08 | 0.00 | 10799.87 | 10799.87 | 1.15348581 | 21.69 | 15.62 | 0.00857326 | 43581.1 | 12.52 | 12.06 | 0.00857326 | 34218.3 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4873.457 | 4873.457 | 0.212368 | 0.00004264 | 139.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.968200 | 1.15348581 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.2432 | 1.268242 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 4873.46 | 4873.46 | 1.0000 | 0.25300985 | 0.212368 | 21.11 | 14.28 | 0.00744318 | 40119.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04263078 | 60.00 | 32.22 | 27.78 | 0.000 | 4873.46 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00744318 | 21.11 | 0.00744318 | 47.3264 | 4873.54 | 0.00 | 5253.71 | 5253.71 | 0.25300985 | 16.60 | 12.61 | 0.00744318 | 35525.0 | 36.98 | 19.85 | 0.00744318 | 56289.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12009.865 | 12009.865 | 0.822008 | 0.00010507 | 276.454 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 3.0637 | 3.125383 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 12009.87 | 12009.87 | 1.0000 | 0.97931700 | 0.822008 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.10505682 | 60.00 | 32.22 | 27.78 | 0.000 | 12009.87 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00756176 | 21.00 | 0.00756176 | 48.3988 | 7719.30 | 0.00 | 12074.26 | 12074.26 | 0.97931700 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.69 | 17.60 | 0.00800000 | 49264.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3409.470 | -999.000 | 0.310433 | 0.00009751 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7479 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.310433 | 0.36984060 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 0.4964 | 0.496390 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3409.47 | 3362.55 | 1.0000 | 0.36984060 | 0.310433 | 21.69 | 15.50 | 0.00855746 | 43541.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.09749864 | 6.70 | 15.03 | 8.33 | 0.000 | 3409.47 | 25.49 | 0.00840565 | 16.72 | 0.00000000 | 0.0000 | 21.11 | 0.00855746 | 21.11 | 0.00855746 | 54.3144 | 3137.06 | 0.00 | 3447.92 | 3447.92 | 0.36984060 | 21.69 | 15.61 | 0.00855746 | 43541.0 | 12.56 | 12.06 | 0.00855746 | 34218.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1506.578 | 1506.578 | 0.065651 | 0.00001318 | 43.053 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.310433 | 0.36984060 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.3843 | 0.392064 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1506.58 | 1506.58 | 1.0000 | 0.07821533 | 0.065651 | 21.11 | 14.37 | 0.00754043 | 40366.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01317886 | 60.00 | 32.22 | 27.78 | 0.000 | 1506.58 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754043 | 21.11 | 0.00754043 | 47.9373 | 1506.60 | 0.00 | 1624.13 | 1624.13 | 0.07821533 | 16.60 | 12.70 | 0.00754043 | 35771.2 | 36.98 | 19.93 | 0.00754043 | 56536.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3037.795 | -999.000 | 0.276053 | 0.00008688 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7611 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276053 | 0.32888123 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 0.4423 | 0.442277 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 3037.80 | 2990.91 | 1.0000 | 0.32888123 | 0.276053 | 21.69 | 15.51 | 0.00856454 | 43559.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.08687007 | 6.70 | 15.03 | 8.33 | 0.000 | 3037.80 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856454 | 21.11 | 0.00856454 | 54.3588 | 2789.63 | 0.00 | 3071.98 | 3071.98 | 0.32888123 | 21.69 | 15.61 | 0.00856454 | 43559.0 | 12.54 | 12.06 | 0.00856454 | 34218.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1507.705 | 1507.705 | 0.065701 | 0.00001319 | 43.085 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276053 | 0.32888123 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 0.3846 | 0.392357 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1507.70 | 1507.70 | 1.0000 | 0.07827383 | 0.065701 | 21.11 | 14.37 | 0.00754077 | 40367.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01318871 | 60.00 | 32.22 | 27.78 | 0.000 | 1507.70 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00754077 | 21.11 | 0.00754077 | 47.9395 | 1507.73 | 0.00 | 1625.34 | 1625.34 | 0.07827383 | 16.60 | 12.70 | 0.00754077 | 35772.1 | 36.98 | 19.93 | 0.00754077 | 56536.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19114.610 | -999.000 | 1.722617 | 0.00054667 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8176 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.722617 | 2.05227806 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 2.7830 | 2.782924 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 19114.61 | 18683.66 | 1.0000 | 2.05227806 | 1.722617 | 21.69 | 15.53 | 0.00859497 | 43636.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.54660946 | 6.70 | 15.03 | 8.33 | 0.000 | 19114.61 | 26.25 | 0.00840684 | 16.99 | 0.00000000 | 0.0000 | 21.11 | 0.00859497 | 21.11 | 0.00859497 | 54.5499 | 17407.40 | 0.00 | 19327.80 | 19327.80 | 2.05227806 | 21.69 | 15.64 | 0.00859497 | 43636.0 | 12.46 | 12.06 | 0.00859497 | 34218.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7239.410 | 7239.410 | 0.315470 | 0.00006333 | 206.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.722617 | 2.05227806 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.8468 | 1.883945 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 7239.41 | 7239.41 | 1.0000 | 0.37584252 | 0.315470 | 21.11 | 14.38 | 0.00755801 | 40411.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06332706 | 60.00 | 32.22 | 27.78 | 0.000 | 7239.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00755801 | 21.11 | 0.00755801 | 48.0475 | 7239.51 | 0.00 | 7804.28 | 7804.28 | 0.37584252 | 16.60 | 12.72 | 0.00755801 | 35815.7 | 36.98 | 19.94 | 0.00755801 | 56580.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10777.163 | 10777.163 | 1.087475 | 0.00009428 | 235.761 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 2.7493 | 2.804591 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 10777.16 | 10777.16 | 1.0000 | 1.29558746 | 1.087475 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09427370 | 60.00 | 32.22 | 27.78 | 0.000 | 10777.16 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00765849 | 21.00 | 0.00765849 | 49.0107 | 5100.10 | 0.00 | 10836.82 | 10836.82 | 1.29558746 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.80 | 16.24 | 0.00800000 | 45299.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11147.200 | 11147.200 | 1.138925 | 0.00009752 | 243.541 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 2.8437 | 2.900888 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | Sensible | 11147.20 | 11147.20 | 1.0000 | 1.35688349 | 1.138925 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09751062 | 60.00 | 32.22 | 27.78 | 0.000 | 11147.20 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00766475 | 21.00 | 0.00766475 | 49.0513 | 5201.95 | 0.00 | 11208.93 | 11208.93 | 1.35688349 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.70 | 16.21 | 0.00800000 | 45195.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7317.565 | 7317.565 | 1.169670 | 0.00006402 | 154.175 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.8667 | 1.904284 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7317.56 | 7317.56 | 1.0000 | 1.39351153 | 1.169670 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06401072 | 60.00 | 32.22 | 27.78 | 0.000 | 7317.56 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.15 | 0.00537861 | 21.00 | 0.00537861 | 34.5533 | 1241.93 | 0.00 | 7358.54 | 7358.54 | 1.39351153 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.78 | 15.14 | 0.00800000 | 42215.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7605.637 | 7605.637 | 0.421571 | 0.00006654 | 182.096 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 1.9402 | 1.979251 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | Sensible | 7605.64 | 7605.64 | 1.0000 | 0.50224758 | 0.421571 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06653065 | 60.00 | 32.22 | 27.78 | 0.000 | 7605.64 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00771447 | 21.00 | 0.00771447 | 49.3651 | 5404.73 | 0.00 | 7645.44 | 7645.44 | 0.50224758 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.53 | 18.54 | 0.00800000 | 52157.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 424478.775 | -999.000 | 22.528192 | 0.01214004 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5473 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.528192 | 26.83945710 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 61.8016 | 61.801640 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 424478.77 | 390079.76 | 1.0000 | 26.83945710 | 22.528192 | 25.24 | 17.12 | 0.00898751 | 48258.6 | 10.96 | 10.96 | 0.00850000 | 32443.1 | 12.13880081 | 6.70 | 15.03 | 8.33 | 50477.536 | 374001.24 | 26.40 | 0.00840708 | 17.04 | 11.66146000 | 51.7639 | 23.99 | 0.00961082 | 23.99 | 0.00956771 | 50.8924 | 306474.72 | 0.00 | 428343.03 | 379600.21 | 26.83945710 | 25.24 | 17.23 | 0.00898751 | 48258.6 | 11.39 | 11.27 | 0.00826745 | 32299.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 169910.112 | 169910.112 | 6.758458 | 0.00148645 | 2899.146 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.528192 | 26.83945710 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 43.3442 | 44.216502 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 169910.11 | 169910.11 | 1.0000 | 8.05183713 | 6.758458 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 1.48629615 | 60.00 | 32.22 | 27.78 | 0.000 | 169910.11 | -4.30 | 0.00265759 | -4.30 | 11.66146000 | 172.5462 | 20.96 | 0.00749378 | 21.02 | 0.00752704 | 48.1181 | 51922.90 | 0.00 | 156352.66 | 156352.66 | 8.05183713 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4683 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 19.64155130 | 15.03 | 6.70 | 8.33 | 686840.63 | 5.2577 | 5.257712 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 36112.10 | 36112.10 | 1.0000 | 2.44388195 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 47966.0 | 11.92 | 11.55 | 0.00840708 | 33189.4 | 1.03269621 | 6.70 | 15.03 | 8.33 | 2195.006 | 33917.10 | 26.40 | 0.00840708 | 17.04 | 2.05124512 | 99.9965 | 21.11 | 0.00859705 | 21.11 | 0.00860017 | 54.5815 | 192959.04 | 0.00 | 36442.34 | 36442.34 | 2.44388195 | 26.40 | 17.15 | 0.00840708 | 47966.0 | 11.79 | 11.58 | 0.00840708 | 33054.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 3.36140599 | 54.44 | 82.22 | 27.78 | 392002.11 | 3.9467 | 4.026159 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 15471.26 | 15471.26 | 1.0000 | 0.73316458 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 0.13533554 | 60.00 | 32.22 | 27.78 | 0.000 | 15471.26 | -4.30 | 0.00265759 | -4.30 | 2.05124512 | 333.3216 | 21.11 | 0.00748135 | 21.11 | 0.00748195 | 47.5691 | 85701.04 | 0.00 | 14236.78 | 14236.78 | 0.73316458 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.53 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2.83 | 8284.33 | 0.00 |
RETAIL_1_FLR_1 | 892.17 | 8121.83 | 513.50 |
RETAIL_2_FLR_1 | 166.00 | 8095.83 | 0.00 |
MECH_FLR_1 | 55.83 | 8749.00 | 55.83 |
STORAGE_FLR_1 | 86.50 | 8760.00 | 86.50 |
LAUNDRY_FLR_1 | 7259.00 | 3200.00 | 2489.83 |
CAFE_FLR_1 | 838.83 | 7239.33 | 20.00 |
LOBBY_FLR_1 | 602.00 | 7132.17 | 9.83 |
ROOM_1_FLR_3 | 1461.50 | 8449.00 | 1441.50 |
ROOM_2_FLR_3 | 2372.33 | 8315.83 | 2118.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 323.00 | 8752.00 | 322.50 |
ROOM_5_FLR_3 | 1411.17 | 8396.67 | 1410.67 |
ROOM_6_FLR_3 | 2114.33 | 8508.17 | 2033.00 |
CORRIDOR_FLR_3 | 37.00 | 8760.00 | 37.00 |
ROOM_1_FLR_6 | 2334.00 | 8352.83 | 2257.67 |
ROOM_2_FLR_6 | 3284.67 | 8276.17 | 3039.83 |
ROOM_3_MULT9_FLR_6 | 802.33 | 8202.17 | 735.50 |
BANQUET_FLR_6 | 3895.17 | 1876.50 | 7.67 |
DINING_FLR_6 | 5587.50 | 770.83 | 7.17 |
KITCHEN_FLR_6 | 8475.83 | 6204.67 | 6189.67 |
CORRIDOR_FLR_6 | 77.83 | 8628.33 | 60.33 |
Facility | 8756.17 | 8760.00 | 7241.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 7.50 | 1.00 | 7.50 | 1.00 |
ROOM_2_FLR_3 | 16.67 | 7.17 | 16.67 | 7.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.67 | 10.67 | 0.67 | 10.67 |
ROOM_5_FLR_3 | 7.50 | 0.00 | 7.50 | 0.00 |
ROOM_6_FLR_3 | 15.00 | 7.00 | 15.00 | 7.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 7.67 | 2.50 | 7.67 | 2.50 |
ROOM_2_FLR_6 | 18.50 | 12.67 | 18.50 | 12.67 |
ROOM_3_MULT9_FLR_6 | 2.33 | 0.67 | 2.33 | 0.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 22.00 | 24.17 | 22.00 | 24.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.978 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.177 | 0.139 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.398 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.487 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.495 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.232 | 0.149 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.501 | 0.109 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.874 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.027 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.180 | 0.000 | 0.022 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.080 | 0.000 | 0.046 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.027 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.180 | 0.000 | 0.030 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.631 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.180 | 0.000 | 0.031 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.180 | 0.000 | 0.021 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.147 | 0.000 | 0.049 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.637 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.067 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.937 | 0.150 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.222 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.941 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.056 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.348 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.470 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.478 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.260 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.335 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.806 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.608 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.833 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.020 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.168 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.178 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40646914.50 | 0.00 | 40646914.50 | 0.00 | 40646914.50 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 7321496.09 | 0.00 | 7321496.09 | 319403.00 | 7640899.09 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3714615.69 | 0.00 | 3714615.69 | 123289.96 | 3837905.65 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2744672.72 | 0.00 | 2744672.72 | 291384.23 | 3036056.94 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1610882.05 | 0.00 | 1610882.05 | 168112.65 | 1778994.70 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 61943031.29 | 0.00 | 61943031.29 | 397870.28 | 62340901.57 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29102891.28 | 0.00 | 29102891.28 | 706058.42 | 29808949.71 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83726529.44 | 0.00 | 83726529.44 | 2017370.18 | 85743899.63 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 28016.32 | 1488173.03 | 185391.43 | 1673564.46 | 1946875.62 | 2190.00 | 6236.00 | 334.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 22056.15 | 1482041.78 | 185377.29 | 1667419.07 | 1946647.51 | 2190.00 | 6331.21 | 238.79 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 12.63 | 1099924.60 | 51726.29 | 1151650.89 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.17 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 29728.63 | 19833557.93 | 51740.43 | 19885298.36 | 26405105.73 | 2190.00 | 6240.72 | 329.28 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 27992.40 | 1488149.11 | 185391.43 | 1673540.55 | 1946875.62 | 2190.00 | 6236.00 | 334.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 30928.35 | 1490913.98 | 185377.29 | 1676291.27 | 1946647.51 | 2190.00 | 6236.28 | 333.72 | 0.00 |
CORRIDOR_FLR_3 | 25922835.75 | 0.00 | 25922835.75 | 224175.54 | 26147011.29 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 31767.92 | 396807.10 | 185430.49 | 582237.59 | 486718.90 | 2086.60 | 6238.81 | 434.60 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 21017.98 | 386014.39 | 185416.35 | 571430.73 | 486661.88 | 2134.10 | 6364.74 | 261.16 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 31691.93 | 2376882.24 | 94872.73 | 2471754.97 | 3126920.42 | 2190.00 | 6236.17 | 333.83 | 0.00 |
BANQUET_FLR_6 | 40215320.60 | 0.00 | 40215320.60 | 452774.66 | 40668095.26 | 37458366.31 | 4038.74 | 195.30 | 4525.96 | 0.00 |
DINING_FLR_6 | 43940806.52 | 0.00 | 43940806.52 | 452774.66 | 44393581.19 | 37458366.31 | 2694.45 | 223.32 | 5842.24 | 0.00 |
KITCHEN_FLR_6 | 59296004.24 | 0.00 | 59296004.24 | 405338.30 | 59701342.53 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13294749.75 | 0.00 | 13294749.75 | 396722.51 | 13691472.26 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 3034321.97 | 0.21E+10 | 18682123.06 | 0.21E+10 | 0.43E+10 | 8760.00 | 6876.89 | 8760.00 | 365.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2889 | 0.0000 | 1.2889 | 0.0000 | 1.2889 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2322 | 0.0000 | 0.2322 | 0.0101 | 0.2423 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1178 | 0.0000 | 0.1178 | 0.0039 | 0.1217 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0870 | 0.0000 | 0.0870 | 0.0092 | 0.0963 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0511 | 0.0000 | 0.0511 | 0.0053 | 0.0564 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 1.9642 | 0.0000 | 1.9642 | 0.0126 | 1.9768 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9228 | 0.0000 | 0.9228 | 0.0224 | 0.9452 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6550 | 0.0000 | 2.6550 | 0.0640 | 2.7189 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0009 | 0.0472 | 0.0059 | 0.0531 | 0.0617 | 2190.00 | 6236.00 | 334.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0007 | 0.0470 | 0.0059 | 0.0529 | 0.0617 | 2190.00 | 6331.21 | 238.79 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0009 | 0.6289 | 0.0016 | 0.6306 | 0.8373 | 2190.00 | 6240.72 | 329.28 |
ROOM_5_FLR_3 | 0.0463 | 0.0009 | 0.0472 | 0.0059 | 0.0531 | 0.0617 | 2190.00 | 6236.00 | 334.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0059 | 0.0532 | 0.0617 | 2190.00 | 6236.28 | 333.72 |
CORRIDOR_FLR_3 | 0.8220 | 0.0000 | 0.8220 | 0.0071 | 0.8291 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0010 | 0.0126 | 0.0059 | 0.0185 | 0.0154 | 2086.60 | 6238.81 | 434.60 |
ROOM_2_FLR_6 | 0.0116 | 0.0007 | 0.0122 | 0.0059 | 0.0181 | 0.0154 | 2134.10 | 6364.74 | 261.16 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0010 | 0.0754 | 0.0030 | 0.0784 | 0.0992 | 2190.00 | 6236.17 | 333.83 |
BANQUET_FLR_6 | 1.2752 | 0.0000 | 1.2752 | 0.0144 | 1.2896 | 1.1878 | 4038.74 | 195.30 | 4525.96 |
DINING_FLR_6 | 1.3934 | 0.0000 | 1.3934 | 0.0144 | 1.4077 | 1.1878 | 2694.45 | 223.32 | 5842.24 |
KITCHEN_FLR_6 | 1.8803 | 0.0000 | 1.8803 | 0.0129 | 1.8931 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4216 | 0.0000 | 0.4216 | 0.0126 | 0.4342 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.7368 | 0.0962 | 64.8329 | 0.4677 | 65.3007 | 73.9670 | 8760.00 | 6876.89 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 42324470.08 | 223212.30 | 42547682.38 | 64690340.46 | 8759.78 | 0.22 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.6099 | 0.0000 | 18.6099 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3421 | 0.0071 | 1.3492 | 2.0513 | 8759.78 | 0.22 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4422.36 | 0.00 | 0.00 | 0.00 | 4337.64 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.7624 | 0.0000 | 0.0000 | 0.0000 | 18.4587 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6953 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
Electricity:Building | 2447.36 | 31087.76 | 01-JUL-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.27 | 30946.61 | 01-JUL-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.44 | 293.96 | 10-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.10 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.10 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.92 | 3093.58 | 01-JUL-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.92 | 982.16 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.92 | 982.16 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.68 | 2448.50 | 20-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.68 | 2448.50 | 20-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.88 | 1114.65 | 10-JAN-23:30 | 3264.92 | 27-JUN-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 506.50 | 2607.99 | 27-APR-02:40 | 130201.71 | 22-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.44 | 0.00 | 01-JAN-11:10 | 1893.32 | 23-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.35 | 971.28 | 11-JAN-04:10 | 1202.70 | 08-AUG-13:10 |
Fans:Electricity | 492.84 | 11701.17 | 30-DEC-08:10 | 30205.92 | 13-JUN-21:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 661.68 | 12523.66 | 06-NOV-15:00 | 37008.38 | 22-JUL-18:20 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 01-JUL-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
ElectricityPurchased:Plant | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
Cogeneration:ElectricityPurchased | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
ElectricityNet:Plant | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
Cogeneration:ElectricityNet | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
General:Cogeneration:ElectricityNet | 4428.07 | 70207.65 | 27-MAY-04:40 | 322411.82 | 22-JUL-18:10 |
General:Fans:Electricity | 492.84 | 11701.17 | 30-DEC-08:10 | 30205.92 | 13-JUN-21:30 |
ExteriorLights:Electricity | 193.49 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.49 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 147.07 | 0.00 | 06-JAN-11:40 | 9938.94 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 147.07 | 0.00 | 06-JAN-11:40 | 9938.94 | 01-JAN-00:10 |
WaterSystems:Electricity | 90.75 | 1086.58 | 14-JUN-00:30 | 4738.61 | 03-APR-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.58 | 14-JUN-00:30 | 4738.61 | 03-APR-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 291.43 | 0.00 | 01-JAN-00:10 | 118965.02 | 22-JUL-18:10 |
General:Cooling:Electricity | 291.43 | 0.00 | 01-JAN-00:10 | 118965.02 | 22-JUL-18:10 |
Pumps:Electricity | 69.54 | 54.17 | 03-MAY-07:10 | 4844.63 | 14-AUG-18:40 |
General:Pumps:Electricity | 69.54 | 54.17 | 03-MAY-07:10 | 4844.63 | 14-AUG-18:40 |
WIRED_LTG_ELECTRICITY | 27.53 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6572.66 | 29270.80 | 01-MAY-02:10 | 571482.88 | 21-FEB-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4783.82 | 15908.90 | 27-APR-10:10 | 467234.56 | 21-FEB-18:40 |
WaterSystems:NaturalGas | 3247.99 | 15908.90 | 23-JAN-16:10 | 287228.02 | 17-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 3247.99 | 15908.90 | 23-JAN-16:10 | 287228.02 | 17-FEB-22:00 |
Heating:NaturalGas | 1535.83 | 0.00 | 07-APR-18:30 | 211025.41 | 16-DEC-16:10 |
Boiler:Heating:NaturalGas | 1535.83 | 0.00 | 07-APR-18:30 | 211025.41 | 16-DEC-16:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 846.93 | 0.00 | 01-JAN-00:10 | 420992.44 | 25-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 846.93 | 0.00 | 01-JAN-00:10 | 420992.44 | 25-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 846.93 | 0.00 | 01-JAN-00:10 | 420992.44 | 25-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-APR-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:50 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13377.28 | 135380.54 | 17-OCT-13:20 | 1710648.78 | 22-JUL-18:20 |
EnergyTransfer:Building | 4586.91 | 82445.85 | 04-JAN-11:10 | 332413.78 | 22-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 711.86 | 11236.64 | 11-JAN-04:00 | 36353.50 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.07 | 4017.20 | 10-JAN-23:10 | 10379.14 | 27-JUN-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.54 | 2008.60 | 10-JAN-23:10 | 5189.57 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer | 91.54 | 2008.60 | 10-JAN-23:10 | 5189.57 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.54 | 2008.60 | 10-JAN-23:10 | 5189.57 | 27-JUN-06:20 |
EnergyTransfer:Plant | 4002.10 | 15929.97 | 15-APR-01:10 | 980767.04 | 25-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.93 | 1863.84 | 11-JAN-04:10 | 2558.10 | 08-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 386.24 | 10302.71 | 20-MAR-14:00 | 17744.29 | 06-OCT-21:00 |
Heating:EnergyTransfer | 103.33 | 0.00 | 01-JAN-08:10 | 51397.31 | 27-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 103.33 | 0.00 | 01-JAN-08:10 | 51397.31 | 27-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4392.05 | 75197.15 | 27-DEC-15:00 | 328850.15 | 22-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 386.24 | 10302.71 | 20-MAR-14:00 | 17744.29 | 06-OCT-21:00 |
General:Cooling:EnergyTransfer | 4392.05 | 75197.15 | 27-DEC-15:00 | 328850.15 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 386.24 | 10302.71 | 20-MAR-14:00 | 17744.29 | 06-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.65 | 0.00 | 15-FEB-17:50 | 3938.50 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 668.48 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 668.48 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.25 | 0.00 | 02-JAN-07:10 | 3938.50 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.25 | 0.00 | 02-JAN-07:10 | 3938.50 | 27-SEP-13:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.72 | 439.89 | 10-DEC-16:00 | 1676.68 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.72 | 439.89 | 10-DEC-16:00 | 1676.68 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.72 | 439.89 | 10-DEC-16:00 | 1676.68 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 19.65 | 0.15 | 10-JAN-11:00 | 1106.01 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 156.78 | 12-JAN-14:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 156.78 | 12-JAN-14:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 19.64 | 0.00 | 10-JAN-04:20 | 1106.01 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 19.64 | 0.00 | 10-JAN-04:20 | 1106.01 | 23-JUL-10:40 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.10 | 0.01 | 30-DEC-01:10 | 637.73 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 191.80 | 12-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 191.80 | 12-JAN-15:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.04 | 0.00 | 03-JAN-10:10 | 637.73 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.04 | 0.00 | 03-JAN-10:10 | 637.73 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.08 | 9620.90 | 30-DEC-06:00 | 38320.04 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.08 | 9620.90 | 30-DEC-06:00 | 38320.04 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.08 | 9620.90 | 30-DEC-06:00 | 38320.04 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 225.88 | 719.37 | 10-DEC-16:00 | 13832.13 | 23-SEP-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 225.88 | 719.37 | 10-DEC-16:00 | 13832.13 | 23-SEP-12:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 225.88 | 719.37 | 10-DEC-16:00 | 13832.13 | 23-SEP-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 743.66 | 10850.63 | 10-DEC-16:00 | 35271.28 | 12-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 743.66 | 10850.63 | 10-DEC-16:00 | 35271.28 | 12-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 743.66 | 10850.63 | 10-DEC-16:00 | 35271.28 | 12-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 45.34 | 0.00 | 01-JAN-08:10 | 11240.21 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.52 | 0.00 | 01-JAN-08:10 | 4376.14 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.52 | 0.00 | 01-JAN-08:10 | 4376.14 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 30.82 | 0.00 | 01-JAN-00:10 | 11240.21 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 30.82 | 0.00 | 01-JAN-00:10 | 11240.21 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.79 | 0.00 | 01-JAN-08:10 | 11372.89 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.03 | 0.00 | 01-JAN-08:10 | 4648.03 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.03 | 0.00 | 01-JAN-08:10 | 4648.03 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.76 | 0.00 | 01-JAN-00:10 | 11372.89 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.76 | 0.00 | 01-JAN-00:10 | 11372.89 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 193.46 | 0.00 | 01-JAN-00:10 | 52412.26 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 193.46 | 0.00 | 01-JAN-00:10 | 52412.26 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 193.46 | 0.00 | 01-JAN-00:10 | 52412.26 | 27-SEP-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 257.25 | 0.00 | 01-JAN-08:10 | 64870.71 | 22-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.16 | 0.00 | 01-JAN-07:10 | 25586.33 | 11-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.16 | 0.00 | 01-JAN-07:10 | 25586.33 | 11-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 244.09 | 0.00 | 01-JAN-00:10 | 64870.71 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 244.09 | 0.00 | 01-JAN-00:10 | 64870.71 | 22-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 45.63 | 0.00 | 01-JAN-08:10 | 10469.26 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 14.51 | 0.00 | 01-JAN-08:10 | 4400.72 | 30-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 14.51 | 0.00 | 01-JAN-08:10 | 4400.72 | 30-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 31.12 | 0.00 | 01-JAN-00:10 | 10469.26 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 31.12 | 0.00 | 01-JAN-00:10 | 10469.26 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 38.75 | 0.00 | 01-JAN-08:10 | 11716.63 | 22-JUL-08:50 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.89 | 0.00 | 01-JAN-08:10 | 4761.07 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.89 | 0.00 | 01-JAN-08:10 | 4761.07 | 12-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 20.86 | 0.00 | 01-JAN-00:10 | 11716.63 | 22-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 20.86 | 0.00 | 01-JAN-00:10 | 11716.63 | 22-JUL-08:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.69 | 4.26 | 31-DEC-15:50 | 10166.97 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.09 | 0.00 | 01-JAN-00:10 | 1047.22 | 10-DEC-16:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.09 | 0.00 | 01-JAN-00:10 | 1047.22 | 10-DEC-16:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.60 | 0.00 | 03-JAN-12:10 | 10166.97 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.60 | 0.00 | 03-JAN-12:10 | 10166.97 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.48 | 0.00 | 01-JAN-08:10 | 3049.90 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.83 | 0.00 | 01-JAN-08:10 | 1467.84 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.83 | 0.00 | 01-JAN-08:10 | 1467.84 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.65 | 0.00 | 01-JAN-00:10 | 3049.90 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.65 | 0.00 | 01-JAN-00:10 | 3049.90 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.86 | 0.00 | 01-JAN-08:10 | 3152.41 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.98 | 0.00 | 01-JAN-08:10 | 1489.66 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.98 | 0.00 | 01-JAN-08:10 | 1489.66 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.88 | 0.00 | 01-JAN-00:10 | 3152.41 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.88 | 0.00 | 01-JAN-00:10 | 3152.41 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 66.81 | 0.00 | 01-JAN-08:10 | 16648.39 | 12-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.84 | 0.00 | 01-JAN-08:10 | 6403.04 | 10-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.84 | 0.00 | 01-JAN-08:10 | 6403.04 | 10-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.97 | 0.00 | 01-JAN-00:10 | 16648.39 | 12-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.97 | 0.00 | 01-JAN-00:10 | 16648.39 | 12-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 413.11 | 8416.85 | 12-JAN-15:00 | 21289.21 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 413.11 | 8416.85 | 12-JAN-15:00 | 21289.21 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 413.11 | 8416.85 | 12-JAN-15:00 | 21289.21 | 21-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 457.00 | 9424.47 | 12-JAN-15:00 | 22708.87 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 457.00 | 9424.47 | 12-JAN-15:00 | 22708.87 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 457.00 | 9424.47 | 12-JAN-15:00 | 22708.87 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.32 | 9128.81 | 11-JAN-04:00 | 31274.00 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.32 | 9128.81 | 11-JAN-04:00 | 31274.00 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.92 | 4.68 | 30-DEC-08:50 | 5429.22 | 23-JUL-10:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 616.28 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 616.28 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.90 | 0.00 | 04-JAN-09:30 | 5429.22 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.90 | 0.00 | 04-JAN-09:30 | 5429.22 | 23-JUL-10:50 |
PlantLoopHeatingDemand:Facility | 1824.45 | 10228.08 | 08-AUG-01:30 | 184424.04 | 16-DEC-16:10 |
PlantLoopHeatingDemand:Plant | 798.37 | 10163.95 | 16-AUG-02:30 | 55884.83 | 13-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 798.37 | 10163.95 | 16-AUG-02:30 | 55884.83 | 13-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 798.37 | 10163.95 | 16-AUG-02:30 | 55884.83 | 13-FEB-07:40 |
EnergyTransfer:HVAC | 4788.27 | 525.75 | 08-SEP-14:50 | 454924.67 | 10-JAN-19:20 |
HeatingCoils:EnergyTransfer | 1026.09 | 0.00 | 07-APR-18:30 | 165391.74 | 16-DEC-16:10 |
PlantLoopHeatingDemand:HVAC | 1026.09 | 0.00 | 07-APR-18:30 | 165391.74 | 16-DEC-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 1026.09 | 0.00 | 07-APR-18:30 | 165391.74 | 16-DEC-16:10 |
CoolingCoils:EnergyTransfer | 846.93 | 0.00 | 01-JAN-00:10 | 420992.44 | 25-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2914.09 | 0.00 | 06-JAN-11:40 | 394629.83 | 17-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1.16 | 0.00 | 01-JAN-00:10 | 32333.70 | 22-JUL-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 798.37 | 10163.95 | 16-AUG-02:30 | 55884.83 | 13-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 798.37 | 10163.95 | 16-AUG-02:30 | 55884.83 | 13-FEB-07:40 |
Boilers:EnergyTransfer | 1018.29 | 0.00 | 07-APR-18:30 | 165669.06 | 16-DEC-16:10 |
Chillers:EnergyTransfer | 901.24 | 0.00 | 01-JAN-00:10 | 422350.74 | 25-JUN-18:10 |
HeatRejection:EnergyTransfer | 1192.67 | 0.00 | 01-JAN-00:10 | 523876.59 | 25-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 1192.67 | 0.00 | 01-JAN-00:10 | 523876.59 | 25-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -386.238 | 0.000 | 0.000 | 140.304 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -58.466 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.397 | -34.253 | 0.000 | 0.000 | 15.966 | 7.307 | 10.186 | 22.113 | 0.000 | 0.005 | 0.000 | 0.000 | -11.434 | 0.000 | -4.721 | -5.568 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -31.716 | 0.000 | 0.000 | 17.226 | 8.462 | 11.795 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -1.975 | -3.795 |
MECH_FLR_1 | 0.000 | 0.000 | 0.005 | -19.641 | 0.000 | 0.000 | 3.792 | 8.366 | 12.471 | 0.000 | 0.000 | 0.006 | 0.000 | 0.000 | 0.000 | 0.000 | -4.454 | -0.546 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.059 | -10.042 | 0.000 | 0.000 | 2.950 | 3.079 | 3.598 | 0.000 | 0.000 | 0.003 | 2.885 | 0.000 | 0.000 | 0.000 | -2.533 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -588.083 | 0.000 | 0.000 | 11.266 | 3.975 | 658.131 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -6.675 | -78.623 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -225.878 | 0.000 | 0.000 | 199.823 | 14.100 | 14.341 | 61.451 | 0.000 | 0.011 | 0.000 | 0.000 | -33.795 | 0.000 | -11.018 | -19.035 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -743.659 | 0.000 | 0.000 | 568.919 | 109.921 | 148.998 | 80.849 | 0.000 | 0.034 | 0.000 | 0.000 | -46.819 | 0.000 | -32.982 | -85.262 |
ROOM_1_FLR_3 | 19.574 | -25.655 | 0.000 | -10.211 | 0.000 | 0.000 | 9.739 | 9.244 | 10.478 | 41.241 | 0.000 | 0.026 | 0.000 | 0.000 | -25.967 | 0.000 | -11.485 | -16.984 |
ROOM_2_FLR_3 | 23.415 | -14.596 | 0.000 | -10.546 | 0.000 | 0.000 | 9.656 | 9.243 | 10.477 | 28.179 | 0.000 | 0.017 | 0.000 | 0.000 | -26.369 | 0.000 | -11.662 | -17.814 |
ROOM_3_MULT19_FLR_3 | 0.000 | -179.960 | 0.000 | -13.501 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 244.538 | 0.000 | 0.009 | 0.012 | 0.000 | -181.618 | 0.000 | -76.755 | -98.095 |
ROOM_4_MULT19_FLR_3 | 46.656 | -137.288 | 0.000 | -140.293 | 0.000 | 0.000 | 184.230 | 110.415 | 195.050 | 66.514 | 0.000 | 0.123 | 0.000 | 0.000 | -145.661 | 0.000 | -71.143 | -108.604 |
ROOM_5_FLR_3 | 19.467 | -25.864 | 0.000 | -10.220 | 0.000 | 0.000 | 9.731 | 9.244 | 10.478 | 41.661 | 0.000 | 0.026 | 0.000 | 0.000 | -25.504 | 0.000 | -11.513 | -17.507 |
ROOM_6_FLR_3 | 23.204 | -15.739 | 0.000 | -10.437 | 0.000 | 0.000 | 9.693 | 9.243 | 10.477 | 28.496 | 0.000 | 0.017 | 0.000 | 0.000 | -25.642 | 0.000 | -11.809 | -17.504 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.091 | -169.600 | 0.000 | 0.000 | 121.061 | 91.336 | 0.000 | 37.362 | 0.000 | 0.018 | 0.000 | 0.000 | -33.148 | 0.000 | -13.585 | -33.534 |
ROOM_1_FLR_6 | 7.243 | -6.510 | 0.000 | -2.549 | 0.000 | 0.000 | 2.438 | 2.311 | 2.620 | 10.246 | 0.000 | 0.007 | 0.000 | 0.000 | -6.425 | 0.000 | -2.891 | -6.490 |
ROOM_2_FLR_6 | 8.457 | -3.711 | 0.000 | -2.648 | 0.000 | 0.000 | 2.412 | 2.311 | 2.619 | 6.976 | 0.000 | 0.004 | 0.000 | 0.000 | -6.532 | 0.000 | -2.917 | -6.973 |
ROOM_3_MULT9_FLR_6 | 18.406 | -45.036 | 0.000 | -16.499 | 0.000 | 0.000 | 21.839 | 13.076 | 23.098 | 57.025 | 0.000 | 0.038 | 0.000 | 0.000 | -30.454 | 0.000 | -14.157 | -27.336 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -413.107 | 0.000 | 0.000 | 316.336 | 30.820 | 175.857 | 6.418 | 0.000 | 0.005 | 0.000 | 0.000 | -19.789 | 0.000 | -8.058 | -88.483 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -457.004 | 0.000 | 0.000 | 315.065 | 30.820 | 175.857 | 6.185 | 0.000 | 0.005 | 0.000 | 0.000 | -20.353 | 0.000 | -8.124 | -42.451 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -620.304 | 0.000 | 0.000 | 28.383 | 12.972 | 550.372 | 19.661 | 0.000 | 0.004 | 29.512 | 0.000 | -13.347 | 0.000 | -7.253 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.017 | -84.905 | 0.000 | 0.000 | 32.144 | 24.166 | 0.000 | 18.357 | 0.000 | 0.005 | 31.124 | 0.000 | -14.878 | 0.000 | -6.030 | -0.001 |
Total Facility | 166.421 | -454.359 | 0.570 | -4001.331 | 0.000 | 0.000 | 2022.975 | 782.094 | 2365.005 | 777.273 | 0.000 | 0.375 | 63.534 | 0.000 | -667.735 | 0.000 | -321.741 | -733.068 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-21:00 | 0.00 | 0.00 | 0.00 | -17745.24 | 0.00 | 0.00 | 5924.41 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9029.38 |
RETAIL_1_FLR_1 | 27-SEP-13:20 | 0.00 | 0.00 | 0.00 | -3938.54 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 6002.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31.27 | -2601.37 |
RETAIL_2_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1676.87 | 0.00 | 0.00 | 697.60 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.20 | -355.80 |
MECH_FLR_1 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -1108.78 | 0.00 | 0.00 | 57.96 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 493.58 | 0.00 | -0.00 | 0.00 | -24.27 | 0.00 |
STORAGE_FLR_1 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -639.32 | 0.00 | 0.00 | 45.10 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 421.18 | 0.00 | -0.00 | 0.00 | -12.86 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38319.61 | 0.00 | 0.00 | 408.86 | 325.08 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.99 | -6669.72 |
CAFE_FLR_1 | 23-SEP-12:30 | 0.00 | 0.00 | 0.00 | -13832.01 | 0.00 | 0.00 | 2968.60 | 103.98 | 355.63 | 16721.39 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -131.40 | -6186.19 |
LOBBY_FLR_1 | 12-SEP-21:10 | 0.00 | 0.00 | 0.00 | -35271.82 | 0.00 | 0.00 | 26439.79 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1721.92 | 0.00 | -669.02 | -2503.51 |
ROOM_1_FLR_3 | 14-APR-15:01 | 0.00 | -14836.83 | 0.00 | -523.59 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 10345.81 | 0.00 | 0.00 | 4673.90 | 0.00 | -0.00 | 0.00 | -293.98 | 0.00 |
ROOM_2_FLR_3 | 11-JUL-19:11 | 0.00 | -14059.60 | 0.00 | -710.86 | 0.00 | 0.00 | 283.79 | 711.45 | 653.15 | 1274.93 | 0.00 | 0.00 | 12164.73 | 0.00 | -0.00 | 0.00 | -317.59 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27-SEP-13:15 | 0.00 | -52413.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 71141.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -775.68 | -22684.15 |
ROOM_4_MULT19_FLR_3 | 20-APR-18:01 | 0.00 | -70969.43 | 0.00 | -7343.10 | 0.00 | 0.00 | 6468.61 | 7563.69 | 9021.83 | 0.00 | 0.00 | 0.00 | 58375.70 | 0.00 | -1767.64 | 0.00 | -1349.65 | 0.00 |
ROOM_5_FLR_3 | 14-APR-15:01 | 0.00 | -13400.04 | 0.00 | -517.59 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 3304.41 | 0.00 | 0.00 | 10270.19 | 0.00 | -0.00 | 0.00 | -291.67 | 0.00 |
ROOM_6_FLR_3 | 23-JUL-08:32 | 0.00 | -13720.01 | 0.00 | -993.20 | 0.00 | 0.00 | 89.74 | 398.41 | 653.15 | 9184.30 | 0.00 | 0.00 | 4579.76 | 0.00 | -0.00 | 0.00 | -192.15 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -10193.11 | 0.00 | 0.00 | 1864.72 | 2489.76 | 0.00 | 6312.20 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -66.52 | -407.05 |
ROOM_1_FLR_6 | 14-APR-15:01 | 0.00 | -3907.23 | 0.00 | -131.11 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 2575.20 | 0.00 | 0.00 | 1378.47 | 0.00 | -0.00 | 0.00 | -74.01 | 0.00 |
ROOM_2_FLR_6 | 11-JUL-18:52 | 0.00 | -3819.41 | 0.00 | -208.76 | 0.00 | 0.00 | 56.75 | 158.30 | 121.15 | 664.22 | 0.00 | 0.00 | 3116.72 | 0.00 | -0.00 | 0.00 | -88.97 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11-JAN-16:01 | 0.00 | -21131.74 | 0.00 | -805.93 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 187.57 | 0.00 | 0.00 | 21326.71 | 0.00 | -0.00 | 0.00 | -829.07 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -21287.69 | 0.00 | 0.00 | 15643.95 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.85 | 0.00 | -119.88 | -2448.45 |
DINING_FLR_6 | 13-JUN-21:11 | 0.00 | 0.00 | 0.00 | -23015.15 | 0.00 | 0.00 | 15622.56 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.16 | 0.00 | -172.08 | -447.09 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31303.50 | 0.00 | 0.00 | 464.22 | 353.60 | 24259.91 | 3781.38 | 0.00 | 0.00 | 2492.14 | 0.00 | -0.00 | 0.00 | -47.74 | 0.00 |
CORRIDOR_FLR_6 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -5441.21 | 0.00 | 0.00 | 480.02 | 658.76 | 0.00 | 3088.51 | 0.00 | 0.00 | 1250.34 | 0.00 | -0.00 | 0.00 | -36.42 | 0.00 |
Total Facility | 22-JUL-18:02 | 0.00 | -154921.80 | 0.00 | -196566.32 | 0.00 | 0.00 | 64345.41 | 51055.14 | 113378.48 | 61184.27 | 0.00 | 3905.86 | 57618.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10-JAN-08:00 | 0.00 | 0.00 | 668.34 | 0.00 | 0.00 | 0.00 | 358.01 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1097.26 | 0.00 | -346.72 | -347.37 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-JAN-14:50 | 0.00 | 0.00 | 156.79 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -254.85 | -445.10 |
STORAGE_FLR_1 | 12-JAN-15:00 | 0.00 | 0.00 | 191.81 | 0.00 | 0.00 | 0.00 | 33.73 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -147.04 | -237.66 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-DEC-16:13 | 5219.05 | 376.16 | 0.00 | -376.16 | 0.00 | 0.00 | 266.43 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1683.91 | 0.00 | -510.27 | -3690.73 |
ROOM_2_FLR_3 | 27-DEC-16:13 | 5128.54 | 369.19 | 0.00 | -369.19 | 0.00 | 0.00 | 266.63 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1672.04 | 0.00 | -507.54 | -3614.97 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-JAN-16:01 | 26896.37 | 4076.94 | 0.00 | -4076.94 | 0.00 | 0.00 | 5481.61 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9669.09 | 0.00 | -3389.77 | -25425.12 |
ROOM_5_FLR_3 | 30-DEC-16:13 | 5117.35 | 374.07 | 0.00 | -374.07 | 0.00 | 0.00 | 148.01 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1596.00 | 0.00 | -548.04 | -3577.38 |
ROOM_6_FLR_3 | 29-JUL-15:04 | 5080.26 | 471.86 | 0.00 | -471.86 | 0.00 | 0.00 | 130.71 | 234.78 | 221.23 | 1182.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -513.27 | -6336.68 |
CORRIDOR_FLR_3 | 10-DEC-16:00 | 0.00 | 0.00 | 1047.20 | 0.00 | 0.00 | 0.00 | 1385.80 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.19 | 0.00 | -593.30 | -1569.35 |
ROOM_1_FLR_6 | 27-DEC-16:13 | 1586.43 | 92.84 | 0.00 | -92.84 | 0.00 | 0.00 | 66.65 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -417.18 | 0.00 | -127.56 | -1208.20 |
ROOM_2_FLR_6 | 27-DEC-16:13 | 1550.89 | 90.58 | 0.00 | -90.58 | 0.00 | 0.00 | 66.91 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.13 | 0.00 | -126.67 | -1177.83 |
ROOM_3_MULT9_FLR_6 | 10-DEC-16:13 | 7694.45 | 615.00 | 0.00 | -615.00 | 0.00 | 0.00 | 332.95 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1688.02 | 0.00 | -554.09 | -6605.14 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-JAN-08:00 | 0.00 | 0.00 | 616.12 | 0.00 | 0.00 | 0.00 | 733.31 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1388.66 | 0.00 | -432.29 | -626.40 |
Total Facility | 30-DEC-16:13 | -26022.61 | 90286.88 | 1371.67 | -90286.88 | 0.00 | 0.00 | 35324.30 | 19060.81 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37835.87 | 0.00 | -13895.11 | -52841.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.6494 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5282 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6645 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6645 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4927 | 2.4927 | 1.2837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4491 | 0.4491 | 0.2313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2282 | 0.2282 | 0.1175 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1690 | 0.1690 | 0.0870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0992 | 0.0992 | 0.0511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2754 | 3.2754 | 1.6868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7868 | 1.7868 | 0.9202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1400 | 5.1400 | 2.6471 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5961 | 1.5961 | 0.8220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1116 | 2.1116 | 1.0875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2115 | 2.2115 | 1.1389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2712 | 2.2712 | 1.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8186 | 0.8186 | 0.4216 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.6494 | 22.5282 | 22.6494 | 11.6645 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2837 | 1.2837 | 1.2837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2313 | 0.2313 | 0.2313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1175 | 0.1175 | 0.1175 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0870 | 0.0870 | 0.0870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0511 | 0.0511 | 0.0511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6868 | 1.6868 | 1.6868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9202 | 0.9202 | 0.9202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6471 | 2.6471 | 2.6471 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8220 | 0.8220 | 0.8220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0875 | 1.0875 | 1.0875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1389 | 1.1389 | 1.1389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1697 | 1.1697 | 1.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4216 | 0.4216 | 0.4216 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6645 | 11.6645 | 11.6645 | 11.6645 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 22.00 |
Number of hours cooling loads not met | 24.17 |
Number of hours not met | 46.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1535.83 | 211025.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 291.43 | 118965.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.09 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.49 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 492.84 | 30205.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 69.54 | 4844.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 147.07 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.61 | 3247.99 | 287228.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.44 | 1893.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.35 | 1202.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.06 | 4428.07 |
Natural Gas | 1788.84 | 6572.66 |
Additional | 0.00 | 0.00 |
Total | 3508.90 | 11000.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.94 |
Space Heating | 0.00 |
Space Cooling | 25.69 |
Fans (All) | 43.44 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 390.30 |
Subtotal | 390.30 |
Natural Gas [MJ/m2] | |
Space Heating | 135.37 |
Service Water Heating | 286.29 |
Miscellaneous (All) | 579.33 |
Subtotal | 579.33 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.11 |
Space Heating | 13.96 |
Space Cooling | 2.65 |
Fans (All) | 4.48 |
Service Water Heating | 30.35 |
Receptacle Equipment | 31.33 |
Miscellaneous | 10.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8680.17 | 79.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8575.17 | 184.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8624.83 | 135.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8575.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 184.83 | 0.00 | 0.00 | 0.00 |
Average | 8741.55 | 18.45 | 0.00 | 0.00 | 0.00 |
Sum | 192314.17 | 405.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4132.83 | 21.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4110.67 | 43.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 43.33 | 0.00 | 0.00 | 0.00 |
Average | 288884.11 | 2.93 | 0.00 | 0.00 | 0.00 |
Sum | 6355450.50 | 64.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8644.83 | 115.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8321.00 | 439.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8591.00 | 169.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8321.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 439.00 | 0.00 | 0.00 | 0.00 |
Average | 8724.94 | 35.06 | 0.00 | 0.00 | 0.00 |
Sum | 191948.67 | 771.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710182.33 | 234.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2110771.17 | 4657.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4108.50 | 45.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4153.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4080.33 | 73.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1243060.83 | 2654.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1244052.00 | 1663.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108253.50 | 15.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2110771.17 | 4657.83 | 0.00 | 0.00 | 0.00 |
Average | 288462.28 | 424.77 | 0.00 | 0.00 | 0.00 |
Sum | 6346170.17 | 9344.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319554E+11 | 14042.80 | 20-JAN-21:00 | 1.00 | 0.17 | 0.768680E+10 | 4794.59 | 12-JAN-22:10 | 1.00 | 0.17 |
February | 0.282810E+11 | 13747.15 | 03-FEB-21:00 | 1.00 | 1.00 | 0.683577E+10 | 4730.98 | 01-FEB-22:10 | 1.00 | 1.00 |
March | 0.304531E+11 | 13610.93 | 25-MAR-10:33 | 11.33 | 8.27 | 0.742267E+10 | 4649.97 | 01-MAR-22:10 | 11.33 | 8.27 |
April | 0.302833E+11 | 14995.51 | 30-APR-10:33 | 19.33 | 11.65 | 0.716813E+10 | 4597.03 | 21-APR-22:10 | 19.33 | 11.65 |
May | 0.313162E+11 | 14567.93 | 21-MAY-10:33 | 13.67 | 10.30 | 0.740753E+10 | 4612.35 | 04-MAY-21:10 | 13.67 | 10.30 |
June | 0.311735E+11 | 15241.29 | 25-JUN-10:33 | 20.00 | 13.96 | 0.726338E+10 | 4667.04 | 16-JUN-21:19 | 20.00 | 13.96 |
July | 0.333940E+11 | 15655.81 | 23-JUL-10:33 | 21.00 | 15.99 | 0.765008E+10 | 4784.17 | 28-JUL-21:19 | 12.20 | 11.48 |
August | 0.340027E+11 | 15680.75 | 19-AUG-10:33 | 18.00 | 14.38 | 0.778871E+10 | 4824.59 | 31-AUG-22:10 | 12.13 | 10.56 |
September | 0.338167E+11 | 17013.90 | 29-SEP-21:00 | 12.00 | 7.58 | 0.768522E+10 | 4837.08 | 11-SEP-21:19 | 12.00 | 7.58 |
October | 0.348116E+11 | 17744.29 | 06-OCT-21:00 | 6.00 | 4.60 | 0.799985E+10 | 4837.01 | 27-OCT-21:19 | 8.00 | 8.00 |
November | 0.334524E+11 | 17272.56 | 17-NOV-22:00 | 6.00 | 5.05 | 0.774458E+10 | 4837.02 | 01-NOV-22:10 | 6.00 | 5.05 |
December | 0.332969E+11 | 16400.01 | 01-DEC-22:00 | 4.00 | 3.53 | 0.790436E+10 | 4836.97 | 04-DEC-22:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.386237E+12 | 0.905571E+11 | ||||||||
Minimum of Months | 0.282810E+11 | 13610.93 | 1.00 | 0.17 | 0.683577E+10 | 4597.03 | 1.00 | 0.17 | ||
Maximum of Months | 0.348116E+11 | 17744.29 | 21.00 | 15.99 | 0.799985E+10 | 4837.08 | 20.00 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130033E+10 | 2557.73 | 21-JAN-11:33 | 6.33 | 5.22 | 0.622782E+09 | 364.15 | 05-JAN-04:40 | 6.33 | 5.22 |
February | 0.149616E+10 | 2943.19 | 04-FEB-13:30 | 9.00 | 6.13 | 0.564665E+09 | 364.16 | 15-FEB-05:10 | 5.83 | 2.56 |
March | 0.135904E+10 | 2103.37 | 25-MAR-10:33 | 11.33 | 8.27 | 0.622924E+09 | 364.19 | 17-MAR-23:00 | 11.33 | 8.27 |
April | 0.349692E+10 | 3207.55 | 30-APR-13:00 | 22.00 | 13.06 | 0.621123E+09 | 413.95 | 28-APR-21:30 | 22.00 | 13.06 |
May | 0.352841E+10 | 2664.86 | 23-MAY-10:33 | 20.00 | 14.59 | 0.635974E+09 | 415.42 | 22-MAY-21:30 | 20.00 | 14.59 |
June | 0.405054E+10 | 2693.09 | 13-JUN-10:33 | 22.00 | 15.85 | 0.622463E+09 | 424.58 | 13-JUN-21:30 | 14.00 | 12.84 |
July | 0.457594E+10 | 3157.02 | 22-JUL-13:30 | 28.00 | 16.51 | 0.654910E+09 | 432.00 | 21-JUL-21:30 | 28.00 | 16.51 |
August | 0.490902E+10 | 3176.43 | 19-AUG-13:10 | 20.67 | 15.34 | 0.666621E+09 | 433.90 | 14-AUG-21:30 | 20.67 | 15.34 |
September | 0.461171E+10 | 3938.72 | 27-SEP-13:20 | 21.33 | 13.25 | 0.641514E+09 | 432.37 | 12-SEP-21:30 | 21.33 | 13.25 |
October | 0.274510E+10 | 3551.52 | 07-OCT-13:10 | 17.00 | 9.32 | 0.632766E+09 | 392.92 | 03-OCT-21:30 | 17.00 | 9.32 |
November | 0.148029E+10 | 2537.96 | 11-NOV-11:33 | 9.00 | 6.87 | 0.602078E+09 | 364.19 | 06-NOV-05:00 | 9.00 | 6.87 |
December | 0.699357E+09 | 2301.84 | 08-DEC-11:35 | 6.67 | 4.51 | 0.620651E+09 | 364.16 | 09-DEC-05:40 | 1.00 | 0.59 |
Annual Sum or Average | 0.342528E+11 | 0.750847E+10 | ||||||||
Minimum of Months | 0.699357E+09 | 2103.37 | 6.33 | 4.51 | 0.564665E+09 | 364.15 | 1.00 | 0.59 | ||
Maximum of Months | 0.490902E+10 | 3938.72 | 28.00 | 16.51 | 0.666621E+09 | 433.90 | 28.00 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236886E+10 | 1148.12 | 20-JAN-21:00 | 1.00 | 0.17 | 0.791308E+09 | 518.88 | 20-JAN-22:30 | 0.50 | 0.10 |
February | 0.218480E+10 | 1135.46 | 27-FEB-21:00 | 6.00 | 6.00 | 0.722059E+09 | 516.66 | 27-FEB-23:10 | 3.83 | 3.83 |
March | 0.242518E+10 | 1153.75 | 20-MAR-20:00 | 7.00 | 4.68 | 0.802541E+09 | 520.55 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.269808E+10 | 1430.66 | 28-APR-21:00 | 12.00 | 8.90 | 0.832398E+09 | 569.51 | 28-APR-21:19 | 11.67 | 8.73 |
May | 0.280996E+10 | 1466.96 | 23-MAY-21:00 | 12.00 | 9.78 | 0.865276E+09 | 569.55 | 22-MAY-21:49 | 12.00 | 9.78 |
June | 0.286928E+10 | 1644.36 | 13-JUN-20:50 | 14.50 | 13.05 | 0.863065E+09 | 569.55 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.305983E+10 | 1676.68 | 21-JUL-21:00 | 17.00 | 13.95 | 0.901214E+09 | 569.55 | 19-JUL-21:19 | 17.00 | 13.95 |
August | 0.310328E+10 | 1613.28 | 14-AUG-21:00 | 18.20 | 11.89 | 0.914549E+09 | 569.55 | 07-AUG-21:49 | 18.20 | 11.89 |
September | 0.292021E+10 | 1614.72 | 12-SEP-21:00 | 15.00 | 13.80 | 0.870837E+09 | 569.55 | 11-SEP-21:19 | 15.00 | 13.80 |
October | 0.265450E+10 | 1310.40 | 01-OCT-10:33 | 13.67 | 9.65 | 0.841066E+09 | 567.10 | 03-OCT-21:40 | 8.00 | 6.49 |
November | 0.236532E+10 | 1161.41 | 10-NOV-21:00 | 4.00 | 4.00 | 0.777733E+09 | 522.84 | 10-NOV-23:10 | 3.83 | 3.45 |
December | 0.225631E+10 | 1098.10 | 21-DEC-21:00 | 2.00 | 2.00 | 0.775139E+09 | 506.37 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.317156E+11 | 0.995718E+10 | ||||||||
Minimum of Months | 0.218480E+10 | 1098.10 | 1.00 | 0.17 | 0.722059E+09 | 506.37 | 0.50 | 0.10 | ||
Maximum of Months | 0.310328E+10 | 1676.68 | 18.20 | 13.95 | 0.914549E+09 | 569.55 | 18.20 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110739E+10 | 724.28 | 18-JAN-21:00 | 8.00 | 6.97 | 0.153225E+09 | 96.14 | 18-JAN-22:10 | 7.97 | 7.42 |
February | 0.107839E+10 | 716.72 | 22-FEB-21:00 | 5.00 | 4.08 | 0.138551E+09 | 95.21 | 22-FEB-22:10 | 4.17 | 3.62 |
March | 0.138336E+10 | 739.26 | 20-MAR-20:00 | 7.00 | 4.68 | 0.155141E+09 | 97.01 | 20-MAR-21:10 | 4.90 | 3.99 |
April | 0.176561E+10 | 1006.23 | 30-APR-10:33 | 19.33 | 11.65 | 0.159960E+09 | 108.29 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.188705E+10 | 981.22 | 23-MAY-10:33 | 20.00 | 14.59 | 0.169056E+09 | 110.95 | 23-MAY-21:19 | 12.00 | 9.78 |
June | 0.200489E+10 | 1031.90 | 13-JUN-10:33 | 22.00 | 15.85 | 0.173350E+09 | 116.10 | 13-JUN-21:19 | 14.00 | 12.84 |
July | 0.215854E+10 | 1108.80 | 23-JUL-10:33 | 21.00 | 15.99 | 0.183145E+09 | 118.00 | 24-JUL-21:19 | 13.67 | 13.29 |
August | 0.217803E+10 | 1045.46 | 19-AUG-10:33 | 18.00 | 14.38 | 0.185001E+09 | 116.43 | 18-AUG-21:10 | 18.00 | 14.38 |
September | 0.200173E+10 | 1003.10 | 13-SEP-10:33 | 19.67 | 15.19 | 0.173293E+09 | 114.37 | 13-SEP-21:10 | 12.00 | 10.35 |
October | 0.175909E+10 | 919.59 | 01-OCT-10:33 | 13.67 | 9.65 | 0.163320E+09 | 106.78 | 02-OCT-21:10 | 8.00 | 6.98 |
November | 0.138627E+10 | 762.24 | 11-NOV-11:33 | 9.00 | 6.87 | 0.150013E+09 | 97.85 | 10-NOV-22:10 | 9.00 | 6.87 |
December | 0.930576E+09 | 695.78 | 20-DEC-21:00 | 7.00 | 6.47 | 0.152485E+09 | 93.75 | 20-DEC-22:10 | 4.83 | 4.43 |
Annual Sum or Average | 0.196409E+11 | 0.195654E+10 | ||||||||
Minimum of Months | 0.930576E+09 | 695.78 | 5.00 | 4.08 | 0.138551E+09 | 93.75 | 4.17 | 3.62 | ||
Maximum of Months | 0.217803E+10 | 1108.80 | 22.00 | 15.99 | 0.185001E+09 | 118.00 | 18.00 | 14.38 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414938E+09 | 398.18 | 18-JAN-21:00 | 8.00 | 6.97 | 0.116847E+09 | 70.98 | 18-JAN-23:10 | 7.80 | 7.23 |
February | 0.408752E+09 | 393.57 | 22-FEB-21:00 | 5.00 | 4.08 | 0.105589E+09 | 70.19 | 07-FEB-23:10 | 5.00 | 4.08 |
March | 0.598426E+09 | 410.99 | 25-MAR-18:10 | 10.50 | 9.68 | 0.117620E+09 | 71.17 | 20-MAR-22:10 | 10.50 | 9.68 |
April | 0.984793E+09 | 581.56 | 30-APR-10:33 | 19.33 | 11.65 | 0.119533E+09 | 81.07 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.106322E+10 | 567.14 | 23-MAY-10:33 | 20.00 | 14.59 | 0.126195E+09 | 81.87 | 23-MAY-22:10 | 11.83 | 9.72 |
June | 0.113521E+10 | 596.86 | 13-JUN-10:33 | 22.00 | 15.85 | 0.129631E+09 | 85.73 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.122445E+10 | 639.33 | 23-JUL-10:33 | 21.00 | 15.99 | 0.137048E+09 | 86.81 | 24-JUL-21:40 | 13.33 | 13.15 |
August | 0.123552E+10 | 601.81 | 19-AUG-10:33 | 18.00 | 14.38 | 0.138413E+09 | 85.79 | 18-AUG-21:30 | 18.00 | 14.38 |
September | 0.113216E+10 | 578.70 | 13-SEP-10:33 | 19.67 | 15.19 | 0.129506E+09 | 84.23 | 13-SEP-21:40 | 12.00 | 10.35 |
October | 0.955435E+09 | 526.41 | 01-OCT-10:33 | 13.67 | 9.65 | 0.121939E+09 | 78.29 | 02-OCT-22:10 | 8.00 | 6.98 |
November | 0.621410E+09 | 434.48 | 11-NOV-11:33 | 9.00 | 6.87 | 0.113473E+09 | 72.16 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.267311E+09 | 383.90 | 20-DEC-21:00 | 7.00 | 6.47 | 0.116696E+09 | 69.00 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.100416E+11 | 0.147249E+10 | ||||||||
Minimum of Months | 0.267311E+09 | 383.90 | 5.00 | 4.08 | 0.105589E+09 | 69.00 | 3.17 | 3.09 | ||
Maximum of Months | 0.123552E+10 | 639.33 | 22.00 | 15.99 | 0.138413E+09 | 86.81 | 18.00 | 14.38 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483464E+11 | 36737.28 | 23-JAN-21:00 | 9.00 | 7.43 | 0.585925E+09 | 381.64 | 23-JAN-22:10 | 8.00 | 7.45 |
February | 0.437992E+11 | 36697.28 | 22-FEB-21:00 | 5.00 | 4.08 | 0.529455E+09 | 381.60 | 06-FEB-22:10 | 5.00 | 4.08 |
March | 0.489346E+11 | 36822.53 | 30-MAR-20:00 | 7.00 | 4.67 | 0.588120E+09 | 381.61 | 20-MAR-21:10 | 7.00 | 4.67 |
April | 0.487585E+11 | 37883.15 | 28-APR-20:00 | 13.00 | 9.28 | 0.571076E+09 | 381.63 | 28-APR-21:10 | 11.83 | 8.82 |
May | 0.505595E+11 | 38008.31 | 22-MAY-20:00 | 17.00 | 12.89 | 0.590746E+09 | 381.64 | 16-MAY-21:10 | 17.00 | 12.89 |
June | 0.497260E+11 | 38307.78 | 13-JUN-20:00 | 17.00 | 13.95 | 0.573960E+09 | 381.64 | 08-JUN-21:10 | 17.00 | 13.95 |
July | 0.515541E+11 | 38320.04 | 21-JUL-20:00 | 21.00 | 15.02 | 0.592658E+09 | 381.67 | 17-JUL-21:10 | 21.00 | 15.02 |
August | 0.519363E+11 | 38206.71 | 14-AUG-20:00 | 20.70 | 12.26 | 0.594334E+09 | 381.68 | 14-AUG-21:10 | 17.83 | 11.86 |
September | 0.496034E+11 | 38040.78 | 13-SEP-20:00 | 15.00 | 12.66 | 0.573528E+09 | 381.69 | 21-SEP-21:10 | 8.00 | 7.37 |
October | 0.496956E+11 | 37387.02 | 06-OCT-20:00 | 8.00 | 6.07 | 0.589631E+09 | 381.67 | 03-OCT-21:10 | 8.00 | 6.07 |
November | 0.472347E+11 | 36838.63 | 08-NOV-21:00 | 11.00 | 11.00 | 0.568426E+09 | 381.64 | 21-NOV-22:19 | 8.67 | 7.78 |
December | 0.479340E+11 | 36502.06 | 20-DEC-21:00 | 7.00 | 6.47 | 0.584618E+09 | 381.61 | 11-DEC-22:10 | 7.00 | 6.47 |
Annual Sum or Average | 0.588082E+12 | 0.694248E+10 | ||||||||
Minimum of Months | 0.437992E+11 | 36502.06 | 5.00 | 4.08 | 0.529455E+09 | 381.60 | 5.00 | 4.08 | ||
Maximum of Months | 0.519363E+11 | 38320.04 | 21.00 | 15.02 | 0.594334E+09 | 381.69 | 21.00 | 15.02 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159369E+11 | 10628.81 | 21-JAN-11:33 | 6.33 | 5.22 | 0.868189E+10 | 5715.26 | 17-JAN-22:40 | 6.33 | 5.22 |
February | 0.152391E+11 | 12041.61 | 04-FEB-13:30 | 9.00 | 6.13 | 0.793300E+10 | 5722.42 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.159863E+11 | 8958.50 | 25-MAR-10:33 | 11.33 | 8.27 | 0.872964E+10 | 5694.97 | 20-MAR-21:40 | 11.33 | 8.27 |
April | 0.202057E+11 | 12310.13 | 29-APR-13:00 | 19.00 | 12.80 | 0.911220E+10 | 6350.67 | 28-APR-21:40 | 19.00 | 12.80 |
May | 0.203579E+11 | 10608.05 | 23-MAY-10:33 | 20.00 | 14.59 | 0.934629E+10 | 6338.77 | 22-MAY-21:40 | 20.00 | 14.59 |
June | 0.207606E+11 | 10960.36 | 25-JUN-10:33 | 20.00 | 13.96 | 0.928678E+10 | 6377.32 | 13-JUN-22:10 | 20.00 | 13.96 |
July | 0.223447E+11 | 11771.14 | 22-JUL-13:30 | 28.00 | 16.51 | 0.974535E+10 | 6462.76 | 21-JUL-22:10 | 28.00 | 16.51 |
August | 0.232698E+11 | 12357.15 | 28-AUG-15:03 | 24.00 | 15.59 | 0.100097E+11 | 6462.65 | 14-AUG-22:10 | 24.00 | 15.59 |
September | 0.226136E+11 | 13832.13 | 23-SEP-12:30 | 19.00 | 14.78 | 0.959857E+10 | 6462.74 | 11-SEP-21:19 | 19.00 | 14.78 |
October | 0.190131E+11 | 13607.27 | 07-OCT-13:00 | 17.00 | 9.21 | 0.919244E+10 | 6217.71 | 03-OCT-21:40 | 17.00 | 9.21 |
November | 0.158805E+11 | 10655.03 | 11-NOV-11:33 | 9.00 | 6.87 | 0.849395E+10 | 5737.21 | 03-NOV-21:40 | 9.00 | 6.87 |
December | 0.142684E+11 | 9357.88 | 08-DEC-11:35 | 6.67 | 4.51 | 0.851533E+10 | 5514.30 | 21-DEC-22:40 | 3.00 | 3.00 |
Annual Sum or Average | 0.225876E+12 | 0.108645E+12 | ||||||||
Minimum of Months | 0.142684E+11 | 8958.50 | 6.33 | 4.51 | 0.793300E+10 | 5514.30 | 3.00 | 3.00 | ||
Maximum of Months | 0.232698E+11 | 13832.13 | 28.00 | 16.51 | 0.100097E+11 | 6462.76 | 28.00 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566099E+11 | 27459.39 | 21-JAN-11:33 | 6.33 | 5.22 | 0.279054E+11 | 18336.35 | 17-JAN-23:10 | 6.33 | 5.22 |
February | 0.521001E+11 | 27152.77 | 04-FEB-11:33 | 7.67 | 5.05 | 0.254265E+11 | 18189.07 | 27-FEB-22:49 | 4.17 | 4.17 |
March | 0.574527E+11 | 26584.12 | 20-MAR-20:00 | 7.00 | 4.68 | 0.282177E+11 | 18305.89 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.630256E+11 | 32740.65 | 30-APR-10:33 | 19.33 | 11.65 | 0.289110E+11 | 19183.64 | 17-APR-21:00 | 19.33 | 11.65 |
May | 0.652248E+11 | 31831.20 | 23-MAY-20:08 | 13.67 | 10.55 | 0.299461E+11 | 19186.23 | 22-MAY-21:49 | 13.67 | 10.55 |
June | 0.661141E+11 | 34075.12 | 13-JUN-21:12 | 14.00 | 12.84 | 0.297214E+11 | 19186.27 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.702920E+11 | 35035.21 | 21-JUL-21:10 | 17.00 | 13.87 | 0.309385E+11 | 19186.24 | 19-JUL-21:19 | 17.00 | 13.87 |
August | 0.716624E+11 | 34808.42 | 18-AUG-21:10 | 15.50 | 12.88 | 0.314258E+11 | 19186.23 | 02-AUG-21:30 | 15.50 | 12.88 |
September | 0.680943E+11 | 35271.28 | 12-SEP-21:10 | 15.17 | 13.86 | 0.301073E+11 | 19186.13 | 11-SEP-21:19 | 15.17 | 13.86 |
October | 0.625476E+11 | 30955.50 | 01-OCT-10:33 | 13.67 | 9.65 | 0.294213E+11 | 19183.45 | 02-OCT-21:40 | 8.00 | 6.98 |
November | 0.561804E+11 | 28049.71 | 11-NOV-11:33 | 9.00 | 6.87 | 0.273836E+11 | 18432.93 | 03-NOV-22:10 | 9.00 | 6.87 |
December | 0.543528E+11 | 25531.48 | 21-DEC-21:00 | 2.00 | 2.00 | 0.274022E+11 | 17953.23 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.743657E+12 | 0.346807E+12 | ||||||||
Minimum of Months | 0.521001E+11 | 25531.48 | 2.00 | 2.00 | 0.254265E+11 | 17953.23 | 3.17 | 3.09 | ||
Maximum of Months | 0.716624E+11 | 35271.28 | 19.33 | 13.87 | 0.314258E+11 | 19186.27 | 19.33 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20093264.24 | 2904.13 | 19-JAN-16:01 | 7.67 | 7.22 | 94359993.25 | 56.69 | 10-JAN-04:19 | 7.67 | 7.22 |
February | 67659797.86 | 3760.57 | 17-FEB-16:01 | 5.83 | 3.30 | 85869032.56 | 56.69 | 01-FEB-01:19 | 5.83 | 3.30 |
March | 43875392.29 | 3659.04 | 10-MAR-16:01 | 7.83 | 4.01 | 95000129.31 | 56.69 | 03-MAR-04:19 | 7.83 | 4.01 |
April | 0.742677E+09 | 3840.11 | 14-APR-15:01 | 12.17 | 8.09 | 94738070.94 | 56.69 | 21-APR-03:30 | 9.10 | 7.78 |
May | 0.892139E+09 | 3765.67 | 11-MAY-18:01 | 16.67 | 9.33 | 97986024.92 | 56.70 | 22-MAY-21:19 | 14.67 | 12.52 |
June | 0.130893E+10 | 3401.91 | 05-JUN-15:01 | 14.00 | 11.65 | 95484926.00 | 56.70 | 13-JUN-21:00 | 14.00 | 12.84 |
July | 0.161354E+10 | 3446.30 | 18-JUL-15:01 | 17.83 | 15.39 | 98666896.77 | 56.70 | 19-JUL-21:10 | 14.00 | 12.84 |
August | 0.155435E+10 | 3437.35 | 15-AUG-18:01 | 16.83 | 14.37 | 98827050.52 | 56.70 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.114656E+10 | 3393.03 | 12-SEP-18:01 | 16.83 | 14.92 | 95293342.96 | 56.69 | 13-SEP-00:49 | 14.83 | 13.13 |
October | 0.283334E+09 | 3704.16 | 06-OCT-18:01 | 11.33 | 7.72 | 96272786.25 | 56.69 | 05-OCT-21:10 | 11.33 | 7.72 |
November | 24396807.18 | 2998.47 | 10-NOV-16:01 | 10.33 | 8.12 | 91647458.75 | 56.69 | 21-NOV-04:19 | 1.67 | 1.53 |
December | 6196313.86 | 284.23 | 24-DEC-09:06 | 7.00 | 5.53 | 93318835.04 | 56.69 | 19-DEC-04:19 | 7.00 | 5.53 |
Annual Sum or Average | 0.770375E+10 | 0.113746E+10 | ||||||||
Minimum of Months | 6196313.86 | 284.23 | 5.83 | 3.30 | 85869032.56 | 56.69 | 1.67 | 1.53 | ||
Maximum of Months | 0.161354E+10 | 3840.11 | 17.83 | 15.39 | 98827050.52 | 56.70 | 14.83 | 13.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7636441.74 | 2439.62 | 19-JAN-16:01 | 7.67 | 7.22 | 93421823.08 | 56.69 | 01-JAN-02:20 | 7.67 | 7.22 |
February | 24656828.48 | 3150.23 | 17-FEB-16:01 | 5.83 | 3.30 | 84877481.93 | 56.69 | 14-FEB-04:19 | 5.83 | 3.30 |
March | 27267473.33 | 2719.30 | 10-MAR-16:01 | 7.83 | 4.01 | 94528807.91 | 56.69 | 14-MAR-03:20 | 2.07 | 1.49 |
April | 0.442955E+09 | 3443.22 | 14-APR-15:01 | 12.17 | 8.09 | 95173700.12 | 79.47 | 28-APR-18:10 | 15.67 | 10.95 |
May | 0.637866E+09 | 3536.81 | 11-MAY-19:31 | 13.67 | 8.80 | 99841645.49 | 86.25 | 23-MAY-18:10 | 17.67 | 12.17 |
June | 0.103203E+10 | 3647.28 | 20-JUN-20:01 | 14.00 | 12.24 | 99548594.06 | 89.73 | 26-JUN-18:10 | 18.00 | 16.13 |
July | 0.112127E+10 | 3692.59 | 11-JUL-19:11 | 13.67 | 12.13 | 0.107259E+09 | 87.79 | 12-JUL-18:10 | 19.00 | 13.74 |
August | 0.933219E+09 | 3544.27 | 01-AUG-19:31 | 14.33 | 11.35 | 0.106522E+09 | 83.15 | 17-AUG-18:10 | 20.50 | 15.86 |
September | 0.585338E+09 | 3592.47 | 14-SEP-18:01 | 14.00 | 12.84 | 97868900.61 | 74.93 | 12-SEP-18:10 | 14.00 | 12.84 |
October | 0.112533E+09 | 3301.53 | 06-OCT-18:01 | 11.33 | 7.72 | 95577240.45 | 56.69 | 08-OCT-01:19 | 10.00 | 8.75 |
November | 10892834.49 | 2548.88 | 10-NOV-16:01 | 10.33 | 8.12 | 90824206.54 | 56.69 | 03-NOV-03:20 | 10.33 | 8.12 |
December | 3952158.33 | 285.82 | 02-DEC-09:06 | 7.00 | 6.47 | 92754620.87 | 56.69 | 26-DEC-04:19 | 2.00 | 0.60 |
Annual Sum or Average | 0.493962E+10 | 0.115820E+10 | ||||||||
Minimum of Months | 3952158.33 | 285.82 | 5.83 | 3.30 | 84877481.93 | 56.69 | 2.00 | 0.60 | ||
Maximum of Months | 0.112127E+10 | 3692.59 | 14.33 | 12.84 | 0.107259E+09 | 89.73 | 20.50 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34285933.23 | 382.59 | 21-JAN-11:25 | 6.00 | 5.05 | 0.00 | 0.00 | 01-JAN-00:10 | 6.00 | 5.05 |
February | 28991787.24 | 270.64 | 19-FEB-14:30 | 6.00 | 4.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.00 | 4.14 |
March | 11535204.89 | 129.85 | 25-MAR-14:05 | 11.83 | 9.32 | 0.00 | 0.00 | 01-MAR-00:10 | 11.83 | 9.32 |
April | 0.282894E+09 | 566.81 | 30-APR-12:50 | 22.00 | 13.22 | 0.00 | 0.00 | 01-APR-00:10 | 22.00 | 13.22 |
May | 0.233280E+09 | 435.75 | 22-MAY-13:20 | 22.33 | 15.12 | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 15.12 |
June | 0.305349E+09 | 443.99 | 13-JUN-13:20 | 24.37 | 17.19 | 0.00 | 0.00 | 01-JUN-00:10 | 24.37 | 17.19 |
July | 0.406958E+09 | 518.09 | 22-JUL-13:30 | 28.00 | 16.51 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.51 |
August | 0.506636E+09 | 555.07 | 20-AUG-13:00 | 23.00 | 14.82 | 0.00 | 0.00 | 01-AUG-00:10 | 23.00 | 14.82 |
September | 0.513075E+09 | 689.66 | 27-SEP-13:15 | 21.33 | 13.25 | 0.00 | 0.00 | 01-SEP-00:10 | 21.33 | 13.25 |
October | 0.187231E+09 | 630.31 | 07-OCT-13:00 | 17.00 | 9.21 | 0.00 | 0.00 | 01-OCT-00:10 | 17.00 | 9.21 |
November | 28034065.58 | 334.64 | 11-NOV-13:30 | 9.00 | 7.22 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.22 |
December | 7283955.13 | 118.54 | 26-DEC-15:05 | 5.50 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 5.50 | 3.13 |
Annual Sum or Average | 0.254555E+10 | 0.00 | ||||||||
Minimum of Months | 7283955.13 | 118.54 | 5.50 | 3.13 | 0.00 | 0.00 | 5.50 | 3.13 | ||
Maximum of Months | 0.513075E+09 | 689.66 | 28.00 | 17.19 | 0.00 | 0.00 | 28.00 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66296096.26 | 821.66 | 29-JAN-09:02 | 11.00 | 8.46 | 95161822.23 | 56.69 | 29-JAN-02:20 | 11.00 | 8.46 |
February | 60965069.67 | 755.27 | 21-FEB-19:02 | 6.83 | 6.83 | 86138984.85 | 56.69 | 14-FEB-04:19 | 6.83 | 6.83 |
March | 0.149371E+09 | 926.36 | 30-MAR-18:03 | 7.00 | 4.68 | 96129723.03 | 56.69 | 20-MAR-21:10 | 7.00 | 4.68 |
April | 0.305045E+09 | 1030.43 | 20-APR-18:01 | 13.67 | 8.59 | 94347675.35 | 60.62 | 27-APR-20:10 | 11.50 | 8.67 |
May | 0.389304E+09 | 1020.57 | 11-MAY-19:31 | 13.67 | 8.80 | 98129878.49 | 73.67 | 22-MAY-21:19 | 14.67 | 12.52 |
June | 0.508854E+09 | 1024.96 | 08-JUN-19:11 | 14.00 | 9.33 | 96445894.79 | 77.30 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.532101E+09 | 1013.13 | 10-JUL-21:51 | 17.00 | 13.49 | 0.101267E+09 | 75.19 | 19-JUL-21:10 | 14.00 | 12.84 |
August | 0.466985E+09 | 980.06 | 21-AUG-21:01 | 14.17 | 12.31 | 0.101350E+09 | 74.72 | 17-AUG-21:10 | 14.17 | 12.31 |
September | 0.374662E+09 | 953.33 | 14-SEP-18:01 | 14.00 | 12.84 | 95400566.28 | 72.34 | 11-SEP-21:10 | 14.00 | 12.84 |
October | 0.216054E+09 | 969.75 | 07-OCT-18:01 | 10.67 | 8.16 | 96429561.36 | 56.69 | 17-OCT-22:10 | 11.17 | 11.17 |
November | 0.103338E+09 | 850.70 | 09-NOV-19:02 | 9.00 | 9.00 | 92510248.21 | 56.69 | 08-NOV-22:19 | 9.00 | 9.00 |
December | 38750810.23 | 758.25 | 02-DEC-09:02 | 7.00 | 6.47 | 94845154.19 | 56.69 | 04-DEC-22:10 | 7.00 | 7.00 |
Annual Sum or Average | 0.321173E+10 | 0.114816E+10 | ||||||||
Minimum of Months | 38750810.23 | 755.27 | 6.83 | 4.68 | 86138984.85 | 56.69 | 6.83 | 4.68 | ||
Maximum of Months | 0.532101E+09 | 1030.43 | 17.00 | 13.49 | 0.101350E+09 | 77.30 | 14.67 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33894736.43 | 2425.93 | 21-JAN-16:01 | 5.75 | 4.88 | 94322170.74 | 56.69 | 13-JAN-04:19 | 5.75 | 4.88 |
February | 52194674.39 | 3224.31 | 17-FEB-16:01 | 5.83 | 3.30 | 85805544.01 | 56.69 | 17-FEB-04:19 | 5.83 | 3.30 |
March | 39702056.98 | 2634.46 | 25-MAR-15:01 | 11.00 | 9.40 | 95070040.07 | 56.69 | 03-MAR-04:19 | 11.00 | 9.40 |
April | 0.834715E+09 | 3479.42 | 14-APR-15:01 | 12.17 | 8.09 | 95212650.01 | 56.69 | 29-APR-23:19 | 10.77 | 8.97 |
May | 0.888291E+09 | 3447.69 | 11-MAY-18:01 | 16.67 | 9.33 | 98406382.64 | 56.69 | 11-MAY-21:10 | 11.50 | 9.00 |
June | 0.121664E+10 | 3125.22 | 24-JUN-08:61 | 14.00 | 11.82 | 95658954.53 | 56.69 | 13-JUN-21:10 | 14.00 | 11.82 |
July | 0.150824E+10 | 3192.87 | 18-JUL-15:01 | 17.83 | 15.39 | 98890013.42 | 56.70 | 21-JUL-21:19 | 17.00 | 13.80 |
August | 0.159820E+10 | 3145.89 | 10-AUG-15:01 | 20.67 | 15.35 | 98988549.16 | 56.69 | 16-AUG-22:49 | 15.17 | 14.47 |
September | 0.125845E+10 | 3188.88 | 10-SEP-18:01 | 18.67 | 15.77 | 95596982.12 | 56.69 | 14-SEP-22:40 | 13.00 | 12.44 |
October | 0.302466E+09 | 3355.84 | 07-OCT-18:01 | 10.67 | 8.16 | 96445935.15 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 34624203.19 | 2534.25 | 11-NOV-09:02 | 6.50 | 5.33 | 91623993.02 | 56.69 | 03-NOV-03:20 | 6.50 | 5.33 |
December | 13598060.28 | 522.88 | 06-DEC-09:03 | 2.33 | 1.83 | 93397765.93 | 56.69 | 31-DEC-02:20 | 0.00 | -0.5 |
Annual Sum or Average | 0.778100E+10 | 0.113942E+10 | ||||||||
Minimum of Months | 13598060.28 | 522.88 | 2.33 | 1.83 | 85805544.01 | 56.69 | 0.00 | -0.5 | ||
Maximum of Months | 0.159820E+10 | 3479.42 | 20.67 | 15.77 | 98988549.16 | 56.70 | 17.00 | 14.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8771299.43 | 461.51 | 23-JAN-09:04 | 8.17 | 7.61 | 93408214.88 | 56.69 | 03-JAN-04:19 | 8.17 | 7.61 |
February | 16830083.37 | 2096.01 | 20-FEB-09:02 | 3.33 | 2.81 | 84737214.99 | 56.69 | 24-FEB-04:19 | -1.0 | -1.0 |
March | 20538497.96 | 1435.07 | 25-MAR-15:01 | 11.00 | 9.40 | 94604327.48 | 56.69 | 14-MAR-03:20 | 11.00 | 9.40 |
April | 0.522807E+09 | 3140.96 | 14-APR-15:01 | 12.17 | 8.09 | 95358184.53 | 61.13 | 27-APR-20:10 | 11.50 | 8.67 |
May | 0.653958E+09 | 3285.09 | 23-MAY-08:51 | 19.00 | 14.78 | 99243475.68 | 74.15 | 22-MAY-21:10 | 19.00 | 14.78 |
June | 0.975131E+09 | 3417.02 | 26-JUN-08:51 | 19.00 | 14.26 | 97924388.61 | 77.29 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.111612E+10 | 3678.28 | 23-JUL-08:32 | 19.67 | 15.53 | 0.103397E+09 | 76.20 | 10-JUL-21:40 | 19.67 | 15.53 |
August | 0.104738E+10 | 3453.87 | 17-AUG-08:51 | 19.00 | 15.90 | 0.103698E+09 | 74.07 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.712582E+09 | 3384.37 | 11-SEP-08:51 | 19.00 | 15.28 | 97188415.18 | 71.46 | 11-SEP-21:10 | 13.83 | 12.58 |
October | 0.124911E+09 | 2940.98 | 07-OCT-18:01 | 10.67 | 8.16 | 95737064.94 | 56.69 | 08-OCT-01:19 | 10.00 | 8.75 |
November | 12155583.18 | 1456.61 | 11-NOV-09:02 | 6.50 | 5.33 | 90792752.75 | 56.69 | 28-NOV-04:19 | 1.67 | 0.43 |
December | 4362534.30 | 375.51 | 06-DEC-09:05 | 2.33 | 1.83 | 92835613.40 | 56.69 | 26-DEC-04:19 | 2.00 | 0.60 |
Annual Sum or Average | 0.521554E+10 | 0.114892E+10 | ||||||||
Minimum of Months | 4362534.30 | 375.51 | 2.33 | 1.83 | 84737214.99 | 56.69 | -1.0 | -1.0 | ||
Maximum of Months | 0.111612E+10 | 3678.28 | 19.67 | 15.90 | 0.103698E+09 | 77.29 | 19.67 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222287E+10 | 1761.10 | 21-JAN-11:33 | 6.33 | 5.22 | 0.120015E+10 | 722.42 | 17-JAN-23:10 | 6.33 | 5.22 |
February | 0.231009E+10 | 1760.04 | 22-FEB-11:33 | 10.00 | 8.60 | 0.108568E+10 | 722.85 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.267404E+10 | 1667.61 | 20-MAR-18:10 | 7.83 | 5.10 | 0.120791E+10 | 729.13 | 20-MAR-21:49 | 4.50 | 3.61 |
April | 0.407400E+10 | 2386.02 | 30-APR-10:33 | 19.33 | 11.65 | 0.124474E+10 | 839.82 | 30-APR-23:19 | 11.63 | 8.77 |
May | 0.438052E+10 | 2290.35 | 23-MAY-10:33 | 20.00 | 14.59 | 0.131591E+10 | 844.53 | 23-MAY-21:40 | 12.00 | 9.78 |
June | 0.458120E+10 | 2386.70 | 13-JUN-10:33 | 22.00 | 15.85 | 0.133346E+10 | 876.85 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.492454E+10 | 2548.34 | 23-JUL-10:33 | 21.00 | 15.99 | 0.140623E+10 | 894.98 | 24-JUL-21:40 | 13.33 | 13.15 |
August | 0.498732E+10 | 2443.38 | 19-AUG-10:33 | 18.00 | 14.38 | 0.142356E+10 | 880.23 | 21-AUG-21:00 | 15.00 | 12.66 |
September | 0.459098E+10 | 2346.07 | 13-SEP-10:33 | 19.67 | 15.19 | 0.133522E+10 | 866.31 | 13-SEP-21:40 | 12.00 | 10.35 |
October | 0.359702E+10 | 2186.05 | 01-OCT-10:33 | 13.67 | 9.65 | 0.125017E+10 | 814.49 | 03-OCT-21:40 | 8.00 | 6.49 |
November | 0.243719E+10 | 1771.89 | 11-NOV-11:33 | 9.00 | 6.87 | 0.116204E+10 | 723.60 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.162006E+10 | 1464.43 | 21-DEC-22:00 | 3.00 | 3.00 | 0.119886E+10 | 710.11 | 21-DEC-22:49 | 3.00 | 3.00 |
Annual Sum or Average | 0.423998E+11 | 0.151639E+11 | ||||||||
Minimum of Months | 0.162006E+10 | 1464.43 | 3.00 | 3.00 | 0.108568E+10 | 710.11 | 3.00 | 3.00 | ||
Maximum of Months | 0.498732E+10 | 2548.34 | 22.00 | 15.99 | 0.142356E+10 | 894.98 | 15.00 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15670112.91 | 3058.64 | 19-JAN-16:01 | 7.67 | 7.22 | 93810438.85 | 56.69 | 10-JAN-04:19 | 7.67 | 7.22 |
February | 68426732.18 | 3938.13 | 17-FEB-16:01 | 5.83 | 3.30 | 85404975.52 | 56.69 | 17-FEB-04:19 | 5.83 | 3.30 |
March | 39743564.39 | 2896.58 | 23-MAR-18:01 | 7.67 | 5.83 | 94569394.96 | 56.69 | 10-MAR-04:19 | 7.67 | 5.83 |
April | 0.773022E+09 | 4038.34 | 14-APR-15:01 | 12.17 | 8.09 | 94627587.29 | 56.69 | 20-APR-21:30 | 11.00 | 7.72 |
May | 0.900116E+09 | 3947.08 | 11-MAY-18:01 | 16.67 | 9.33 | 97859789.41 | 56.70 | 22-MAY-21:19 | 14.67 | 12.52 |
June | 0.131552E+10 | 3592.46 | 05-JUN-15:01 | 14.00 | 11.65 | 95416496.81 | 56.70 | 12-JUN-21:19 | 16.33 | 12.85 |
July | 0.164215E+10 | 3613.64 | 22-JUL-08:61 | 24.00 | 16.56 | 98603912.27 | 56.70 | 21-JUL-21:40 | 24.00 | 16.56 |
August | 0.153205E+10 | 3609.56 | 15-AUG-18:01 | 16.83 | 14.37 | 98740801.86 | 56.70 | 02-AUG-03:30 | 16.83 | 14.37 |
September | 0.107937E+10 | 3547.06 | 12-SEP-18:01 | 16.83 | 14.92 | 95148271.65 | 56.69 | 21-SEP-23:00 | 9.00 | 7.01 |
October | 0.253470E+09 | 3876.75 | 06-OCT-18:01 | 11.33 | 7.72 | 95878620.43 | 56.69 | 07-OCT-23:19 | 10.67 | 9.24 |
November | 22001365.78 | 3166.30 | 10-NOV-16:01 | 10.33 | 8.12 | 91113960.54 | 56.69 | 12-NOV-02:20 | 6.00 | 5.49 |
December | 4582853.86 | 277.71 | 02-DEC-09:06 | 7.00 | 6.47 | 92842777.39 | 56.69 | 15-DEC-04:19 | 1.67 | 0.85 |
Annual Sum or Average | 0.764613E+10 | 0.113402E+10 | ||||||||
Minimum of Months | 4582853.86 | 277.71 | 5.83 | 3.30 | 85404975.52 | 56.69 | 1.67 | 0.85 | ||
Maximum of Months | 0.164215E+10 | 4038.34 | 24.00 | 16.56 | 98740801.86 | 56.70 | 24.00 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4474926.73 | 1975.47 | 19-JAN-16:01 | 7.67 | 7.22 | 92936187.79 | 56.69 | 13-JAN-04:19 | 7.67 | 7.22 |
February | 18974357.61 | 2770.17 | 27-FEB-16:02 | 8.00 | 6.56 | 84366966.70 | 56.69 | 18-FEB-02:20 | 8.00 | 6.56 |
March | 23213377.46 | 2616.17 | 23-MAR-18:01 | 7.67 | 5.83 | 94066283.00 | 56.69 | 31-MAR-03:20 | 3.50 | 2.46 |
April | 0.458759E+09 | 3592.09 | 14-APR-15:01 | 12.17 | 8.09 | 95343603.44 | 87.26 | 28-APR-18:10 | 15.67 | 10.95 |
May | 0.637423E+09 | 3786.62 | 23-MAY-19:42 | 14.33 | 10.77 | 0.100230E+09 | 93.77 | 22-MAY-18:10 | 14.33 | 10.77 |
June | 0.104175E+10 | 3862.03 | 22-JUN-18:42 | 14.33 | 11.96 | 0.100263E+09 | 95.97 | 21-JUN-18:10 | 14.33 | 11.96 |
July | 0.116762E+10 | 4028.18 | 11-JUL-18:52 | 14.00 | 12.24 | 0.108833E+09 | 94.46 | 12-JUL-18:10 | 19.00 | 13.74 |
August | 0.920144E+09 | 3729.06 | 29-AUG-18:31 | 13.67 | 12.33 | 0.107737E+09 | 89.02 | 17-AUG-18:10 | 13.67 | 12.33 |
September | 0.510176E+09 | 3779.85 | 14-SEP-18:01 | 14.00 | 12.84 | 98313943.34 | 80.89 | 12-SEP-18:10 | 14.00 | 12.84 |
October | 91002228.96 | 3448.49 | 06-OCT-18:01 | 11.33 | 7.72 | 95121661.95 | 56.69 | 06-OCT-03:20 | 11.33 | 7.72 |
November | 6918802.46 | 2380.14 | 10-NOV-16:01 | 10.33 | 8.12 | 90276766.39 | 56.69 | 28-NOV-04:19 | 1.67 | 0.43 |
December | 1193578.94 | 69.40 | 21-DEC-14:00 | 8.00 | 6.98 | 92400343.23 | 56.69 | 19-DEC-04:19 | 8.00 | 6.98 |
Annual Sum or Average | 0.488164E+10 | 0.115989E+10 | ||||||||
Minimum of Months | 1193578.94 | 69.40 | 7.67 | 5.83 | 84366966.70 | 56.69 | 1.67 | 0.43 | ||
Maximum of Months | 0.116762E+10 | 4028.18 | 14.33 | 12.84 | 0.108833E+09 | 95.97 | 19.00 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161084E+09 | 2437.56 | 11-JAN-16:01 | -2.2 | -4.4 | 95859480.01 | 56.69 | 29-JAN-02:20 | 9.90 | 9.45 |
February | 0.197129E+09 | 1970.31 | 27-FEB-16:02 | 8.00 | 6.56 | 87081142.21 | 56.69 | 14-FEB-04:19 | 8.00 | 6.56 |
March | 83133771.40 | 2068.10 | 25-MAR-15:01 | 11.00 | 9.40 | 96027934.36 | 56.69 | 14-MAR-03:20 | 11.00 | 9.40 |
April | 0.679532E+09 | 2074.21 | 29-APR-08:61 | 15.17 | 11.12 | 95183012.92 | 56.69 | 27-APR-22:30 | 15.17 | 11.12 |
May | 0.584761E+09 | 2437.47 | 11-MAY-18:01 | 16.67 | 9.33 | 98234973.41 | 56.69 | 11-MAY-21:19 | 11.00 | 8.70 |
June | 0.738297E+09 | 2271.62 | 08-JUN-18:02 | 15.83 | 9.50 | 95482861.22 | 56.69 | 26-JUN-23:30 | 15.00 | 14.41 |
July | 0.923467E+09 | 2266.46 | 16-JUL-18:01 | 18.67 | 15.16 | 98666297.61 | 56.69 | 17-JUL-23:10 | 16.00 | 14.66 |
August | 0.106659E+10 | 2194.46 | 12-AUG-18:01 | 17.83 | 14.24 | 98768764.54 | 56.69 | 17-AUG-23:00 | 14.00 | 12.84 |
September | 0.104700E+10 | 2244.54 | 14-SEP-18:01 | 14.00 | 12.84 | 95494388.10 | 56.70 | 11-SEP-21:10 | 14.00 | 12.84 |
October | 0.436736E+09 | 2433.87 | 06-OCT-18:01 | 11.33 | 7.72 | 97178552.21 | 56.69 | 07-OCT-23:00 | 10.00 | 8.90 |
November | 0.137533E+09 | 2023.77 | 10-NOV-16:01 | 10.33 | 8.12 | 92959298.99 | 56.69 | 05-NOV-23:19 | 10.33 | 8.12 |
December | 52723041.30 | 1884.71 | 21-DEC-16:02 | 6.83 | 6.31 | 94740358.46 | 56.69 | 01-DEC-04:19 | 6.83 | 6.31 |
Annual Sum or Average | 0.610798E+10 | 0.114568E+10 | ||||||||
Minimum of Months | 52723041.30 | 1884.71 | -2.2 | -4.4 | 87081142.21 | 56.69 | 6.83 | 6.31 | ||
Maximum of Months | 0.106659E+10 | 2437.56 | 18.67 | 15.16 | 98768764.54 | 56.70 | 16.00 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313184E+11 | 17643.66 | 18-JAN-23:00 | 7.80 | 7.26 | 0.189140E+11 | 11348.01 | 26-JAN-00:20 | 7.97 | 7.26 |
February | 0.286534E+11 | 17459.92 | 07-FEB-23:00 | 7.00 | 7.00 | 0.171363E+11 | 11347.95 | 17-FEB-04:19 | -2.0 | -2.3 |
March | 0.329129E+11 | 17792.78 | 20-MAR-21:10 | 4.90 | 3.99 | 0.191403E+11 | 11347.98 | 03-MAR-04:19 | 4.90 | 3.99 |
April | 0.346570E+11 | 19885.34 | 28-APR-21:10 | 11.83 | 8.82 | 0.186018E+11 | 11348.15 | 23-APR-23:19 | 11.83 | 8.82 |
May | 0.366371E+11 | 20625.32 | 22-MAY-21:10 | 14.83 | 12.59 | 0.192589E+11 | 11349.19 | 22-MAY-21:49 | 14.17 | 12.31 |
June | 0.377060E+11 | 21254.40 | 13-JUN-21:12 | 14.00 | 12.84 | 0.187137E+11 | 11349.22 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.396633E+11 | 21289.21 | 21-JUL-21:10 | 17.00 | 13.87 | 0.192759E+11 | 11349.20 | 10-JUL-22:10 | 17.00 | 13.87 |
August | 0.393408E+11 | 20865.38 | 14-AUG-21:10 | 17.83 | 11.86 | 0.193456E+11 | 11349.20 | 17-AUG-21:30 | 14.50 | 13.02 |
September | 0.360614E+11 | 20216.78 | 12-SEP-22:00 | 16.00 | 14.13 | 0.186322E+11 | 11349.05 | 11-SEP-21:19 | 16.00 | 14.13 |
October | 0.340003E+11 | 18519.96 | 02-OCT-22:00 | 8.00 | 6.98 | 0.191136E+11 | 11348.28 | 15-OCT-23:19 | 8.00 | 7.63 |
November | 0.312332E+11 | 18194.92 | 08-NOV-23:00 | 11.00 | 11.00 | 0.183647E+11 | 11348.19 | 24-NOV-00:20 | 8.00 | 8.00 |
December | 0.309217E+11 | 16976.67 | 04-DEC-23:00 | 7.00 | 7.00 | 0.188744E+11 | 11347.97 | 01-DEC-04:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.413105E+12 | 0.225371E+12 | ||||||||
Minimum of Months | 0.286534E+11 | 16976.67 | 4.90 | 3.99 | 0.171363E+11 | 11347.95 | -2.0 | -2.3 | ||
Maximum of Months | 0.396633E+11 | 21289.21 | 17.83 | 14.13 | 0.193456E+11 | 11349.22 | 17.00 | 14.13 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350889E+11 | 19671.31 | 18-JAN-23:00 | 7.80 | 7.26 | 0.191057E+11 | 11348.05 | 26-JAN-00:20 | 7.97 | 7.26 |
February | 0.320691E+11 | 19495.32 | 07-FEB-23:00 | 7.00 | 7.00 | 0.173082E+11 | 11348.00 | 17-FEB-04:19 | -2.0 | -2.3 |
March | 0.368776E+11 | 19804.34 | 30-MAR-21:10 | 5.92 | 4.10 | 0.192859E+11 | 11348.02 | 03-MAR-04:19 | 5.92 | 4.10 |
April | 0.383727E+11 | 21468.48 | 28-APR-21:10 | 11.83 | 8.82 | 0.186789E+11 | 11348.18 | 23-APR-23:19 | 11.83 | 8.82 |
May | 0.404391E+11 | 22178.49 | 22-MAY-21:10 | 14.83 | 12.59 | 0.193171E+11 | 11349.20 | 22-MAY-21:49 | 14.17 | 12.31 |
June | 0.412038E+11 | 23015.16 | 13-JUN-21:11 | 14.00 | 12.84 | 0.187465E+11 | 11366.21 | 13-JUN-21:19 | 14.00 | 12.84 |
July | 0.431553E+11 | 22708.87 | 21-JUL-21:20 | 17.00 | 13.80 | 0.193019E+11 | 11370.43 | 21-JUL-21:19 | 17.00 | 13.80 |
August | 0.427846E+11 | 22296.90 | 14-AUG-21:10 | 17.83 | 11.86 | 0.193756E+11 | 11349.20 | 17-AUG-21:30 | 14.50 | 13.02 |
September | 0.395196E+11 | 21674.92 | 12-SEP-22:00 | 16.00 | 14.13 | 0.186808E+11 | 11349.05 | 11-SEP-21:19 | 16.00 | 14.13 |
October | 0.378734E+11 | 20412.46 | 12-OCT-22:00 | 12.00 | 10.91 | 0.192291E+11 | 11348.36 | 15-OCT-23:19 | 8.00 | 7.63 |
November | 0.349582E+11 | 20217.34 | 08-NOV-23:00 | 11.00 | 11.00 | 0.185291E+11 | 11348.25 | 24-NOV-00:20 | 8.00 | 8.00 |
December | 0.346604E+11 | 19026.40 | 04-DEC-23:00 | 7.00 | 7.00 | 0.190844E+11 | 11348.01 | 01-DEC-04:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.457003E+12 | 0.226643E+12 | ||||||||
Minimum of Months | 0.320691E+11 | 19026.40 | 5.92 | 4.10 | 0.173082E+11 | 11348.00 | -2.0 | -2.3 | ||
Maximum of Months | 0.431553E+11 | 23015.16 | 17.83 | 14.13 | 0.193756E+11 | 11370.43 | 17.00 | 14.13 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494946E+11 | 27436.79 | 15-JAN-11:50 | 8.83 | 6.51 | 0.188166E+11 | 11319.60 | 07-JAN-18:19 | 8.83 | 6.51 |
February | 0.451192E+11 | 27634.73 | 22-FEB-11:33 | 10.00 | 8.60 | 0.169965E+11 | 11319.61 | 25-FEB-18:19 | 3.67 | 3.36 |
March | 0.506184E+11 | 28415.19 | 25-MAR-10:45 | 11.42 | 8.36 | 0.188298E+11 | 11319.64 | 18-MAR-17:19 | 11.42 | 8.36 |
April | 0.521739E+11 | 30739.97 | 30-APR-10:33 | 19.33 | 11.65 | 0.182273E+11 | 11319.68 | 29-APR-17:19 | 19.33 | 11.65 |
May | 0.542105E+11 | 30543.91 | 23-MAY-10:33 | 20.00 | 14.59 | 0.188394E+11 | 11319.69 | 20-MAY-17:19 | 20.00 | 14.59 |
June | 0.538342E+11 | 30871.61 | 25-JUN-10:33 | 20.00 | 13.96 | 0.182438E+11 | 11319.66 | 24-JUN-17:19 | 20.00 | 13.96 |
July | 0.562052E+11 | 31312.08 | 23-JUL-10:40 | 21.00 | 15.99 | 0.188482E+11 | 11319.69 | 15-JUL-17:19 | 21.00 | 15.99 |
August | 0.562544E+11 | 30716.38 | 19-AUG-10:33 | 18.00 | 14.38 | 0.188562E+11 | 11319.69 | 19-AUG-17:19 | 18.00 | 14.38 |
September | 0.532789E+11 | 30296.75 | 10-SEP-10:50 | 18.83 | 14.72 | 0.182372E+11 | 11319.66 | 09-SEP-17:19 | 18.83 | 14.72 |
October | 0.518856E+11 | 29297.72 | 07-OCT-10:33 | 14.67 | 10.10 | 0.188308E+11 | 11319.63 | 21-OCT-17:19 | 8.67 | 7.29 |
November | 0.484276E+11 | 27327.72 | 11-NOV-11:50 | 9.00 | 6.94 | 0.182136E+11 | 11319.61 | 04-NOV-17:19 | 9.00 | 6.94 |
December | 0.488177E+11 | 26567.21 | 03-DEC-11:50 | 6.83 | 4.26 | 0.188136E+11 | 11319.64 | 09-DEC-18:19 | 4.00 | 2.43 |
Annual Sum or Average | 0.620320E+12 | 0.221753E+12 | ||||||||
Minimum of Months | 0.451192E+11 | 26567.21 | 6.83 | 4.26 | 0.169965E+11 | 11319.60 | 3.67 | 2.43 | ||
Maximum of Months | 0.562544E+11 | 31312.08 | 21.00 | 15.99 | 0.188562E+11 | 11319.69 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401477E+10 | 3724.32 | 21-JAN-11:33 | 6.33 | 5.22 | 0.126997E+10 | 757.22 | 23-JAN-22:40 | 8.00 | 7.45 |
February | 0.429897E+10 | 3782.17 | 22-FEB-11:33 | 10.00 | 8.60 | 0.114933E+10 | 758.60 | 27-FEB-22:30 | 4.50 | 4.50 |
March | 0.543276E+10 | 3825.24 | 25-MAR-10:45 | 11.42 | 8.36 | 0.127724E+10 | 767.06 | 20-MAR-21:40 | 11.42 | 8.36 |
April | 0.820823E+10 | 5068.11 | 30-APR-10:33 | 19.33 | 11.65 | 0.130983E+10 | 892.69 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.887026E+10 | 4984.25 | 23-MAY-10:33 | 20.00 | 14.59 | 0.137494E+10 | 907.09 | 23-MAY-21:30 | 12.00 | 9.78 |
June | 0.945624E+10 | 5199.44 | 13-JUN-17:12 | 25.97 | 17.22 | 0.140601E+10 | 945.52 | 13-JUN-21:30 | 14.00 | 12.84 |
July | 0.101736E+11 | 5441.47 | 23-JUL-10:33 | 21.00 | 15.99 | 0.148348E+10 | 949.44 | 21-JUL-21:30 | 21.00 | 15.99 |
August | 0.101838E+11 | 5128.38 | 19-AUG-10:33 | 18.00 | 14.38 | 0.148872E+10 | 928.66 | 14-AUG-21:30 | 18.00 | 14.38 |
September | 0.920192E+10 | 4948.88 | 13-SEP-10:33 | 19.67 | 15.19 | 0.137873E+10 | 906.71 | 12-SEP-21:40 | 19.67 | 15.19 |
October | 0.712547E+10 | 4403.10 | 01-OCT-10:33 | 13.67 | 9.65 | 0.130054E+10 | 823.85 | 02-OCT-21:40 | 8.00 | 6.98 |
November | 0.485965E+10 | 3763.49 | 11-NOV-11:33 | 9.00 | 6.87 | 0.122896E+10 | 762.71 | 08-NOV-22:49 | 9.00 | 6.87 |
December | 0.307891E+10 | 3427.12 | 06-DEC-11:33 | 7.67 | 5.48 | 0.126893E+10 | 745.60 | 29-DEC-04:40 | 3.00 | 0.66 |
Annual Sum or Average | 0.849046E+11 | 0.159367E+11 | ||||||||
Minimum of Months | 0.307891E+10 | 3427.12 | 6.33 | 5.22 | 0.114933E+10 | 745.60 | 3.00 | 0.66 | ||
Maximum of Months | 0.101838E+11 | 5441.47 | 25.97 | 17.22 | 0.148872E+10 | 949.44 | 21.00 | 15.99 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94652382.27 | 668.48 | 10-JAN-08:00 | -6.0 |
February | 36459976.06 | 511.33 | 17-FEB-07:20 | -3.7 |
March | 17736069.99 | 282.33 | 16-MAR-06:10 | 1.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 54759.63 | 45.71 | 28-OCT-06:50 | 4.50 |
November | 26513821.94 | 371.10 | 29-NOV-09:04 | 1.17 |
December | 0.221694E+09 | 559.26 | 30-DEC-09:02 | 0.00 |
Annual Sum or Average | 0.397111E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.221694E+09 | 668.48 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4061758.44 | 156.78 | 12-JAN-14:50 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 1307335.17 | 70.45 | 30-DEC-17:00 | 1.00 |
Annual Sum or Average | 5369093.61 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 4061758.44 | 156.78 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30555156.54 | 191.80 | 12-JAN-15:00 | -1.0 |
February | 1116499.27 | 36.52 | 26-FEB-06:00 | -1.0 |
March | 377857.31 | 33.03 | 15-MAR-12:40 | 1.67 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 2548337.27 | 80.18 | 29-NOV-16:00 | 4.00 |
December | 24706437.31 | 155.97 | 30-DEC-16:50 | 1.17 |
Annual Sum or Average | 59304287.71 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 30555156.54 | 191.80 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.722190E+09 | 1293.85 | 04-JAN-16:13 | 3.83 |
February | 0.521046E+09 | 1243.55 | 25-FEB-16:13 | 5.00 |
March | 0.480528E+09 | 1261.58 | 15-MAR-15:13 | 3.00 |
April | 78414298.06 | 1250.38 | 21-APR-08:03 | 11.83 |
May | 46476127.72 | 1183.09 | 14-MAY-15:03 | 11.83 |
June | 4146124.18 | 1245.01 | 09-JUN-08:03 | 13.33 |
July | 3984160.79 | 1130.15 | 01-JUL-08:03 | 13.17 |
August | 2211041.36 | 1031.27 | 08-AUG-15:04 | 17.17 |
September | 9203578.87 | 1174.30 | 20-SEP-18:04 | 12.33 |
October | 0.212584E+09 | 1239.68 | 19-OCT-15:02 | 9.00 |
November | 0.545524E+09 | 1295.18 | 29-NOV-16:13 | 3.67 |
December | 0.100433E+10 | 1304.77 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.363064E+10 | |||
Minimum of Months | 2211041.36 | 1031.27 | 3.00 | |
Maximum of Months | 0.100433E+10 | 1304.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929239E+09 | 1279.23 | 12-JAN-16:13 | -1.0 |
February | 0.688650E+09 | 1254.12 | 17-FEB-09:02 | 1.33 |
March | 0.558687E+09 | 1238.87 | 15-MAR-15:13 | 3.00 |
April | 0.116175E+09 | 1198.23 | 11-APR-08:61 | 7.17 |
May | 54321112.54 | 1106.45 | 05-MAY-08:62 | 8.17 |
June | 3793276.04 | 1149.55 | 04-JUN-18:04 | 12.83 |
July | 3970535.87 | 1177.42 | 02-JUL-18:04 | 13.00 |
August | 2298287.06 | 1237.86 | 07-AUG-08:53 | 16.00 |
September | 14480694.52 | 1200.08 | 18-SEP-18:04 | 14.67 |
October | 0.294344E+09 | 1219.63 | 19-OCT-15:02 | 9.00 |
November | 0.694736E+09 | 1275.06 | 29-NOV-16:13 | 3.67 |
December | 0.114694E+10 | 1282.14 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.450763E+10 | |||
Minimum of Months | 2298287.06 | 1106.45 | -1.0 | |
Maximum of Months | 0.114694E+10 | 1282.14 | 16.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55607930.28 | 353.90 | 11-JAN-16:01 | -2.2 |
February | 25713434.65 | 330.62 | 17-FEB-16:01 | 5.83 |
March | 4401830.25 | 339.23 | 28-MAR-15:03 | 9.83 |
April | 807112.16 | 339.15 | 19-APR-15:05 | 12.83 |
May | 610035.92 | 327.02 | 26-MAY-15:06 | 15.67 |
June | 326598.88 | 335.51 | 01-JUN-15:06 | 16.00 |
July | 226561.27 | 310.86 | 29-JUL-15:06 | 16.83 |
August | 297348.55 | 295.39 | 23-AUG-15:06 | 17.17 |
September | 708855.76 | 339.33 | 21-SEP-15:04 | 16.17 |
October | 1832488.86 | 340.78 | 17-OCT-15:05 | 15.67 |
November | 16776602.96 | 336.54 | 29-NOV-16:02 | 3.83 |
December | 65825620.15 | 340.95 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.173134E+09 | |||
Minimum of Months | 226561.27 | 295.39 | -2.2 | |
Maximum of Months | 65825620.15 | 353.90 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.726656E+09 | 1267.00 | 04-JAN-16:13 | 3.83 |
February | 0.549913E+09 | 1224.87 | 01-FEB-16:13 | 7.00 |
March | 0.485488E+09 | 1235.14 | 15-MAR-15:13 | 3.00 |
April | 72739667.93 | 1157.45 | 10-APR-15:02 | 7.17 |
May | 47399287.70 | 1253.93 | 28-MAY-08:03 | 8.83 |
June | 6363837.84 | 1164.35 | 17-JUN-18:04 | 14.83 |
July | 3023713.31 | 1238.32 | 29-JUL-15:04 | 16.83 |
August | 1923151.42 | 1071.14 | 08-AUG-15:04 | 17.17 |
September | 6009786.20 | 1119.71 | 02-SEP-08:04 | 13.33 |
October | 0.211856E+09 | 1218.06 | 27-OCT-15:02 | 9.00 |
November | 0.549341E+09 | 1265.80 | 29-NOV-16:13 | 3.67 |
December | 0.965792E+09 | 1279.34 | 30-DEC-16:13 | 1.67 |
Annual Sum or Average | 0.362651E+10 | |||
Minimum of Months | 1923151.42 | 1071.14 | 1.67 | |
Maximum of Months | 0.965792E+09 | 1279.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.922431E+09 | 1268.40 | 10-JAN-16:01 | -3.0 |
February | 0.727804E+09 | 1240.48 | 16-FEB-16:01 | 6.00 |
March | 0.561771E+09 | 1213.34 | 15-MAR-15:13 | 3.00 |
April | 0.106641E+09 | 1246.53 | 26-APR-18:04 | 12.67 |
May | 57674238.57 | 1011.75 | 27-MAY-18:04 | 13.00 |
June | 6336900.15 | 1167.66 | 16-JUN-18:04 | 14.00 |
July | 2157926.91 | 1270.19 | 29-JUL-15:04 | 16.83 |
August | 1133197.98 | 1168.89 | 08-AUG-15:04 | 17.17 |
September | 10525401.00 | 1261.66 | 17-SEP-15:04 | 16.00 |
October | 0.289689E+09 | 1199.00 | 27-OCT-15:02 | 9.00 |
November | 0.690068E+09 | 1246.33 | 29-NOV-16:13 | 3.67 |
December | 0.109613E+10 | 1254.79 | 30-DEC-16:13 | 1.67 |
Annual Sum or Average | 0.447237E+10 | |||
Minimum of Months | 1133197.98 | 1011.75 | -3.0 | |
Maximum of Months | 0.109613E+10 | 1270.19 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5144043.66 | 169.93 | 12-JAN-13:50 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 1514714.10 | 118.36 | 30-NOV-14:50 | 6.00 |
December | 16136936.43 | 261.81 | 10-DEC-16:00 | 4.00 |
Annual Sum or Average | 22795694.18 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 16136936.43 | 261.81 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111949E+10 | 1572.80 | 03-JAN-16:13 | 3.67 |
February | 0.820767E+09 | 1519.77 | 25-FEB-16:13 | 5.00 |
March | 0.772958E+09 | 1528.96 | 15-MAR-15:13 | 3.00 |
April | 0.176910E+09 | 1462.55 | 11-APR-08:61 | 7.17 |
May | 0.118177E+09 | 1440.17 | 05-MAY-08:62 | 8.17 |
June | 11863702.54 | 1100.12 | 28-JUN-18:03 | 12.00 |
July | 14282897.44 | 1119.52 | 02-JUL-08:03 | 12.33 |
August | 3504113.29 | 1076.52 | 30-AUG-08:03 | 14.33 |
September | 38862318.87 | 1142.70 | 30-SEP-08:03 | 11.00 |
October | 0.414054E+09 | 1502.01 | 27-OCT-15:02 | 9.00 |
November | 0.871562E+09 | 1575.50 | 29-NOV-16:13 | 3.67 |
December | 0.146738E+10 | 1586.44 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.582981E+10 | |||
Minimum of Months | 3504113.29 | 1076.52 | 3.00 | |
Maximum of Months | 0.146738E+10 | 1586.44 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137917E+10 | 1548.58 | 11-JAN-09:13 | -3.7 |
February | 0.103047E+10 | 1503.93 | 17-FEB-09:02 | 1.33 |
March | 0.872293E+09 | 1497.98 | 15-MAR-15:13 | 3.00 |
April | 0.239823E+09 | 1443.43 | 11-APR-08:61 | 7.17 |
May | 0.135624E+09 | 1415.98 | 05-MAY-08:62 | 8.17 |
June | 11040269.83 | 1145.13 | 09-JUN-08:03 | 13.33 |
July | 13211656.54 | 1174.76 | 02-JUL-18:04 | 13.00 |
August | 2784088.50 | 1154.60 | 20-AUG-08:53 | 17.00 |
September | 56252465.84 | 1201.64 | 06-SEP-15:03 | 13.83 |
October | 0.541772E+09 | 1475.99 | 27-OCT-15:02 | 9.00 |
November | 0.105649E+10 | 1542.95 | 29-NOV-16:13 | 3.67 |
December | 0.164084E+10 | 1550.89 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.697977E+10 | |||
Minimum of Months | 2784088.50 | 1145.13 | -3.7 | |
Maximum of Months | 0.164084E+10 | 1550.89 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255189E+09 | 847.03 | 04-JAN-16:13 | 3.83 |
February | 0.177998E+09 | 792.65 | 02-FEB-09:02 | 4.33 |
March | 0.183517E+09 | 813.43 | 15-MAR-15:13 | 3.00 |
April | 22561325.35 | 715.84 | 16-APR-18:04 | 9.83 |
May | 20044469.66 | 758.89 | 29-MAY-18:04 | 11.00 |
June | 3670410.67 | 692.82 | 06-JUN-18:04 | 11.83 |
July | 1866043.93 | 754.38 | 29-JUL-15:04 | 16.83 |
August | 1543454.48 | 614.46 | 08-AUG-15:04 | 17.17 |
September | 2339703.26 | 681.69 | 07-SEP-18:04 | 13.00 |
October | 56855318.59 | 795.74 | 27-OCT-15:02 | 9.00 |
November | 0.170237E+09 | 844.97 | 30-NOV-16:13 | 6.00 |
December | 0.419877E+09 | 854.94 | 10-DEC-16:13 | 4.00 |
Annual Sum or Average | 0.131570E+10 | |||
Minimum of Months | 1543454.48 | 614.46 | 3.00 | |
Maximum of Months | 0.419877E+09 | 854.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8999822.39 | 616.28 | 10-JAN-08:00 | -6.0 |
February | 1074411.40 | 398.49 | 17-FEB-07:20 | -3.7 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 12970.85 | 35.61 | 29-NOV-09:10 | 1.17 |
December | 6539010.17 | 336.63 | 27-DEC-09:08 | -0.7 |
Annual Sum or Average | 16626214.81 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 8999822.39 | 616.28 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141974E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120913E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125940E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.106959E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.968984E+09 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.871045E+09 | 1701.53 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.918775E+09 | 1701.53 | 17-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.105931E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.115330E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.133573E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.136582E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.146961E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.141004E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.871045E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.146961E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954008E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854159E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.942203E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.892724E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.913316E+10 | 9504.80 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.878766E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.904831E+10 | 9504.80 | 17-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923041E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.901095E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.945687E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.924772E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.957456E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109921E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854159E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.957456E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286423E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250408E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268933E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243034E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.236847E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223314E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231335E+10 | 2988.03 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246665E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252321E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276186E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.276225E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.290344E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308203E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223314E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.290344E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286423E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250408E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268933E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243034E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.236847E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223314E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231335E+10 | 2988.03 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246665E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252321E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276186E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.276225E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.290344E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308203E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223314E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.290344E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567980E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509612E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503471E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173760.74 | 0.399329E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7922.23 | 0.374305E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1113434.84 | 0.256590E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3567724.94 | 0.219046E+09 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 522551.33 | 0.200736E+09 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264994E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394042E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466019E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564514E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5385394.08 | 0.472064E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200736E+09 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3567724.94 | 0.567980E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227749E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204755E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204766E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64390.97 | 0.167516E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22458.36 | 0.160581E+09 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 452307.65 | 0.116988E+09 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1323032.97 | 0.102006E+09 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261426.86 | 93976075.92 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116684E+09 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165190E+09 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189983E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224681E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2123616.80 | 0.197487E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93976075.92 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1323032.97 | 0.227749E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516997E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462451E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462562E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277189.50 | 0.371803E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123659.61 | 0.359511E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264453.08 | 0.265133E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221951.77 | 0.232368E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809024.93 | 0.212031E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40000.19 | 0.260860E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368804E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427083E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514700E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5736279.09 | 0.445430E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212031E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221951.77 | 0.516997E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297213E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265811E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265071E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171850.64 | 0.210325E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76374.84 | 0.202783E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 771344.02 | 0.148731E+09 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1936202.40 | 0.129787E+09 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 504686.14 | 0.117992E+09 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33084.62 | 0.146114E+09 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208294E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244240E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296363E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3493542.67 | 0.253272E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117992E+09 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1936202.40 | 0.297213E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784945E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702432E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707768E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 334085.84 | 0.558330E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 94355.51 | 0.534912E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 1697254.78 | 0.383197E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 4676950.34 | 0.329451E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 1187805.41 | 0.298632E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 123413.11 | 0.376886E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560444E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656586E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781728E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 8113864.99 | 0.667531E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298632E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 4676950.34 | 0.784945E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.141974E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128545E+10 |
February | 0.236489E+11 | 0.120913E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115746E+10 |
March | 0.262800E+11 | 0.125940E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114403E+10 |
April | 0.253579E+11 | 0.106959E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 347493.55 | 0.939507E+09 |
May | 0.262123E+11 | 0.968984E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7816.99 | 0.886332E+09 |
June | 0.254132E+11 | 0.871045E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2250669.86 | 0.631875E+09 |
July | 0.261570E+11 | 0.918775E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7351299.89 | 0.549990E+09 |
August | 0.262677E+11 | 0.105931E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1042941.66 | 0.514967E+09 |
September | 0.253456E+11 | 0.115330E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653398E+09 |
October | 0.261693E+11 | 0.133573E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922409E+09 |
November | 0.253025E+11 | 0.136582E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106448E+10 |
December | 0.261570E+11 | 0.146961E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126843E+10 |
Annual Sum or Average | 0.308468E+12 | 0.141004E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11000221.95 | 0.110183E+11 |
Minimum of Months | 0.236489E+11 | 0.871045E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514967E+09 |
Maximum of Months | 0.262800E+11 | 0.146961E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7351299.89 | 0.128545E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.954008E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380260E+10 |
February | 0.702046E+11 | 0.854159E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341898E+10 |
March | 0.780153E+11 | 0.942203E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341819E+10 |
April | 0.752779E+11 | 0.892724E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1173932.93 | 0.279404E+10 |
May | 0.778146E+11 | 0.913316E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 286471.85 | 0.267259E+10 |
June | 0.754422E+11 | 0.878766E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7287189.85 | 0.194730E+10 |
July | 0.776503E+11 | 0.904831E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21430872.17 | 0.169972E+10 |
August | 0.779788E+11 | 0.923041E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3902550.50 | 0.157160E+10 |
September | 0.752414E+11 | 0.901095E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195739E+10 |
October | 0.776868E+11 | 0.945687E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276713E+10 |
November | 0.751137E+11 | 0.924772E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317880E+10 |
December | 0.776503E+11 | 0.957456E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375320E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109921E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 34081017.30 | 0.329816E+11 |
Minimum of Months | 0.702046E+11 | 0.854159E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157160E+10 |
Maximum of Months | 0.780153E+11 | 0.957456E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21430872.17 | 0.380260E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326366E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294310E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292291E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 232492.56 | 0.233794E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65713.29 | 0.221866E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 969824.98 | 0.154353E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2563972.98 | 0.128971E+09 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 727778.88 | 0.114702E+09 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 249115.14 | 0.150915E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228181E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268551E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321919E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4808897.83 | 0.273622E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114702E+09 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2563972.98 | 0.326366E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322384E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290281E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290309E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 230845.36 | 0.232834E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16655.42 | 0.223712E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 869413.61 | 0.160284E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2315955.93 | 0.141851E+09 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 581366.36 | 0.126751E+09 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20654.64 | 0.154233E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225120E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265129E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319291E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4034891.32 | 0.275218E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126751E+09 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2315955.93 | 0.322384E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110121E+09 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99801706.27 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95179705.94 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90126317.36 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87816677.33 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 724.97 | 67879843.14 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121472.61 | 61221442.61 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2385.22 | 57701438.65 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67294565.41 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88508593.36 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94948070.88 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89191447.78 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124582.79 | 0.100979E+10 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57701438.65 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121472.61 | 0.110121E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91703739.64 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82249528.99 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82619896.55 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66960.82 | 64643820.03 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9033.48 | 61669155.91 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 256896.06 | 43245053.80 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 667595.67 | 36910183.97 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180352.74 | 32836516.69 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13969.48 | 41663409.96 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63688774.74 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75653914.87 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91224014.25 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1194808.25 | 0.768108E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32836516.69 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 667595.67 | 91703739.64 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326288E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294178E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292850E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237278.34 | 0.235663E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66429.88 | 0.223404E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 979036.84 | 0.154994E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2555847.52 | 0.129668E+09 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 733621.94 | 0.115237E+09 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 254993.38 | 0.151892E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228944E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268462E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322230E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4827207.91 | 0.274381E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115237E+09 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2555847.52 | 0.326288E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322382E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289858E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290922E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 236361.05 | 0.235185E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20491.11 | 0.224482E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 876874.62 | 0.158953E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2291354.62 | 0.137205E+09 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 590867.72 | 0.123559E+09 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24030.29 | 0.154729E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226227E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265002E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319628E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4039979.40 | 0.274813E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123559E+09 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2291354.62 | 0.322382E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397330E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355535E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354412E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185380.98 | 0.284414E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82666.53 | 0.274802E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 972646.74 | 0.199547E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2570276.39 | 0.173808E+09 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583022.47 | 0.158607E+09 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12334.02 | 0.196816E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278613E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326209E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396197E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4406327.12 | 0.339629E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158607E+09 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2570276.39 | 0.397330E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325526E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293663E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291857E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 221228.66 | 0.234637E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62100.58 | 0.222673E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 935947.68 | 0.155260E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2503776.65 | 0.129923E+09 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704028.79 | 0.115599E+09 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 232235.36 | 0.151623E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227951E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267726E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321375E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4659317.72 | 0.273781E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115599E+09 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2503776.65 | 0.325526E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321792E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289427E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289728E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220283.20 | 0.234141E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14356.76 | 0.225280E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 839601.41 | 0.162356E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2262078.83 | 0.145026E+09 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 564045.05 | 0.129505E+09 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18761.60 | 0.155817E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224589E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264201E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319229E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3919126.84 | 0.276109E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129505E+09 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2262078.83 | 0.321792E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170498E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153392E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152181E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116874.54 | 0.121081E+09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32419.12 | 0.114619E+09 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485113.61 | 79553425.38 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1287164.84 | 66570198.02 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 362943.77 | 59223054.01 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 118252.84 | 78124601.38 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118921E+09 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140459E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2402768.72 | 0.142278E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59223054.01 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1287164.84 | 0.170498E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.286423E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925568E+09 |
February | 0.415303E+11 | 0.250408E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830538E+09 |
March | 0.461508E+11 | 0.268933E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843540E+09 |
April | 0.445315E+11 | 0.243034E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676846E+09 |
May | 0.460320E+11 | 0.236847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653032E+09 |
June | 0.446286E+11 | 0.223314E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 665266.70 | 0.478927E+09 |
July | 0.459349E+11 | 0.231335E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3531726.86 | 0.418884E+09 |
August | 0.461292E+11 | 0.246665E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 499124.08 | 0.383952E+09 |
September | 0.445099E+11 | 0.252321E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470111E+09 |
October | 0.459565E+11 | 0.276186E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675535E+09 |
November | 0.444343E+11 | 0.276225E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779998E+09 |
December | 0.459349E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921278E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308203E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 4696117.63 | 0.805821E+10 |
Minimum of Months | 0.415303E+11 | 0.223314E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383952E+09 |
Maximum of Months | 0.461508E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3531726.86 | 0.925568E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.286423E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934615E+09 |
February | 0.415303E+11 | 0.250408E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838549E+09 |
March | 0.461508E+11 | 0.268933E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851204E+09 |
April | 0.445315E+11 | 0.243034E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681324E+09 |
May | 0.460320E+11 | 0.236847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656722E+09 |
June | 0.446286E+11 | 0.223314E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 665246.99 | 0.481180E+09 |
July | 0.459349E+11 | 0.231335E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3477313.03 | 0.420561E+09 |
August | 0.461292E+11 | 0.246665E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 498871.51 | 0.386019E+09 |
September | 0.445099E+11 | 0.252321E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473148E+09 |
October | 0.459565E+11 | 0.276186E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681803E+09 |
November | 0.444343E+11 | 0.276225E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788000E+09 |
December | 0.459349E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930822E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308203E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 4641431.53 | 0.812395E+10 |
Minimum of Months | 0.415303E+11 | 0.223314E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386019E+09 |
Maximum of Months | 0.461508E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3477313.03 | 0.934615E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838194E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750064E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760358E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606037E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584099E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 600008.63 | 0.427654E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3108934.87 | 0.373323E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 449050.02 | 0.343108E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420980E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608731E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705605E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835115E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 4157993.51 | 0.725327E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343108E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3108934.87 | 0.838194E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706001E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632210E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629835E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118765.95 | 0.506780E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19790.67 | 0.486858E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936693.54 | 0.356421E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3662074.98 | 0.311185E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663683.76 | 0.281401E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344317E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490961E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579969E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703726E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5401008.90 | 0.602966E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281401E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3662074.98 | 0.706001E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 348.06 | 11-JAN-24:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 322.59 | 17-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 279.64 | 08-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | 30-APR-18:00 | 265.40 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 22-MAY-15:00 | 240.81 | 06-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 13-JUN-17:00 | 186.87 | 07-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 22-JUL-18:00 | 173.83 | 31-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.65 | 14-AUG-18:00 | 160.56 | 20-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 200.67 | 21-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 239.17 | 15-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 297.51 | 29-NOV-02:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 306.91 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.56 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 348.06 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 140.24 | 11-JAN-24:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 128.18 | 17-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 112.54 | 08-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 30-APR-17:00 | 109.29 | 08-APR-05:03 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 22-MAY-15:00 | 99.40 | 06-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 13-JUN-17:00 | 80.79 | 07-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 22-JUL-18:00 | 76.60 | 31-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 14-AUG-17:00 | 72.15 | 23-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 88.26 | 20-SEP-24:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 100.80 | 07-OCT-04:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 119.50 | 29-NOV-02:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 125.16 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.15 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 140.24 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 317.53 | 11-JAN-24:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 294.25 | 17-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 255.10 | 08-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 30-APR-17:00 | 246.48 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 22-MAY-15:00 | 224.15 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 | 13-JUN-17:00 | 181.78 | 07-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 22-JUL-18:00 | 174.36 | 31-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 | 14-AUG-17:00 | 166.00 | 20-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 11-SEP-17:00 | 198.39 | 20-SEP-24:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 226.66 | 07-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 271.40 | 29-NOV-02:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 281.02 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 317.53 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 183.20 | 11-JAN-24:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 169.77 | 17-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 147.18 | 08-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 30-APR-17:00 | 140.03 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.64 | 22-MAY-15:00 | 127.35 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 13-JUN-17:00 | 103.08 | 07-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 22-JUL-18:00 | 98.83 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 14-AUG-17:00 | 93.77 | 20-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 11-SEP-17:00 | 112.43 | 20-SEP-24:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 129.19 | 07-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 156.58 | 29-NOV-02:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 161.54 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.77 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 183.20 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 479.83 | 10-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 449.68 | 17-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 395.65 | 08-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 38.78 | 30-APR-17:00 | 364.05 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 18.45 | 22-MAY-15:18 | 328.85 | 07-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 72.47 | 13-JUN-17:00 | 275.41 | 08-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 100.97 | 21-JUL-17:00 | 256.42 | 05-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 71.90 | 14-AUG-17:00 | 246.07 | 24-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 13.31 | 11-SEP-17:00 | 296.72 | 21-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 329.64 | 04-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 401.71 | 28-NOV-23:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 430.09 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 246.07 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 100.97 | 479.83 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 796.24 | 11-JAN-24:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 715.36 | 18-FEB-02:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 621.84 | 08-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 | 30-APR-18:00 | 616.21 | 08-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 22-MAY-15:00 | 561.56 | 06-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.93 | 13-JUN-17:00 | 453.37 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 17-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.83 | 22-JUL-18:00 | 429.33 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.62 | 14-AUG-18:00 | 403.80 | 23-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 498.84 | 20-SEP-24:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 570.06 | 07-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 678.77 | 29-NOV-02:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 699.13 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.80 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 168.83 | 796.24 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2343.95 | 11-JAN-24:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2131.79 | 17-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1878.45 | 08-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.12 | 30-APR-17:00 | 1832.94 | 08-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 | 22-MAY-15:00 | 1675.43 | 06-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.12 | 13-JUN-17:00 | 1363.70 | 07-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 17-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.72 | 22-JUL-18:00 | 1293.80 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.75 | 14-AUG-17:00 | 1216.41 | 23-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1479.88 | 20-SEP-24:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1692.46 | 07-OCT-04:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2012.50 | 29-NOV-02:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2089.86 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.41 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 458.72 | 2343.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.36 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.44 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 13-JUN-17:00 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 11-SEP-17:00 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 13-JUN-17:00 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 13-SEP-15:10 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.27 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 | 203.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.25 | 11-JAN-24:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 60.02 | 17-FEB-21:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 49.50 | 02-MAR-21:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 52.20 | 08-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 48.25 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 13-JUN-17:00 | 40.27 | 01-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 22-JUL-18:00 | 38.63 | 31-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 14-AUG-17:02 | 37.41 | 24-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 44.09 | 21-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 49.10 | 07-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 53.71 | 28-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 51.05 | 26-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.41 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 63.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 56.70 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 52.57 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 45.61 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 30-APR-19:00 | 43.31 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 22-MAY-15:10 | 39.32 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 13-JUN-17:00 | 30.58 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 22-JUL-18:10 | 28.46 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 14-AUG-17:00 | 26.31 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 13-SEP-15:10 | 32.82 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.06 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.51 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 50.04 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 56.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.36 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.44 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 13-JUN-17:00 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 11-SEP-17:00 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 13-JUN-17:00 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 13-SEP-15:09 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.26 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 203.16 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.68 | 11-JAN-24:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 226.77 | 17-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 196.65 | 08-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | 30-APR-17:00 | 188.70 | 08-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 | 22-MAY-15:00 | 172.71 | 06-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 13-JUN-17:00 | 138.73 | 07-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 | 22-JUL-18:00 | 133.02 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 14-AUG-17:00 | 125.93 | 20-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 11-SEP-17:00 | 151.16 | 20-SEP-24:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 175.03 | 07-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 209.19 | 29-NOV-02:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 215.80 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.93 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 | 244.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.66 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.84 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.91 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 30-APR-19:00 | 155.64 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 22-MAY-15:10 | 141.37 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 | 13-JUN-17:00 | 110.02 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 22-JUL-18:10 | 102.43 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 14-AUG-17:00 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 11-SEP-17:00 | 118.04 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.41 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 174.31 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.76 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 203.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.64 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.83 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.90 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 30-APR-19:00 | 155.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 22-MAY-15:10 | 141.36 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 | 13-JUN-17:00 | 110.01 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 22-JUL-18:10 | 102.42 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 14-AUG-17:00 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 13-SEP-15:10 | 118.03 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.40 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 174.30 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.75 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 203.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 104.20 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 96.62 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 83.86 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 30-APR-19:00 | 79.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 22-MAY-15:10 | 72.33 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 13-JUN-17:00 | 56.29 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 22-JUL-18:10 | 52.41 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 | 14-AUG-17:00 | 48.47 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 13-SEP-15:10 | 60.39 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 71.84 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 89.18 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 91.97 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 104.20 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 549.97 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 513.85 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 452.19 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 431.70 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 396.99 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 13-JUN-17:00 | 319.55 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 22-JUL-18:00 | 300.86 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 | 14-AUG-17:00 | 281.81 | 20-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 339.50 | 21-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 393.11 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 478.48 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 491.22 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.81 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 549.97 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 549.98 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 513.86 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 452.20 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 431.70 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 397.00 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 13-JUN-17:00 | 319.56 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 22-JUL-18:00 | 300.86 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 | 14-AUG-17:00 | 281.81 | 20-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 339.50 | 21-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 394.31 | 15-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 478.49 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 491.22 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.81 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 549.98 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 492.33 | 11-JAN-24:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 459.94 | 17-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 404.74 | 08-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 386.39 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 352.53 | 06-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 42.45 | 13-JUN-17:00 | 283.62 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 85.07 | 22-JUL-18:00 | 267.93 | 05-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 42.58 | 14-AUG-17:00 | 252.22 | 24-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 303.86 | 21-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 339.45 | 07-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 410.89 | 29-NOV-00:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 439.63 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 252.22 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 85.07 | 492.33 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 433.96 | 11-JAN-24:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 402.26 | 17-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 348.93 | 08-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | 30-APR-18:00 | 331.28 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 22-MAY-15:00 | 300.74 | 06-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 | 13-JUN-17:00 | 240.30 | 01-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.88 | 22-JUL-18:00 | 227.81 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.85 | 14-AUG-18:00 | 215.13 | 20-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 260.60 | 20-SEP-24:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.67 | 15-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 371.16 | 29-NOV-02:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 382.83 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.13 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.88 | 433.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14042.80 | 20-JAN-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13747.15 | 03-FEB-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13610.93 | 25-MAR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14995.51 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14567.93 | 21-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15241.29 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15655.81 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15680.75 | 19-AUG-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17013.90 | 29-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17744.29 | 06-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17272.56 | 17-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16400.01 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13610.93 | 8945.92 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17744.29 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2557.73 | 21-JAN-11:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.82 |
February | 2943.19 | 04-FEB-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.79 |
March | 2103.37 | 25-MAR-10:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.66 |
April | 3207.55 | 30-APR-13:00 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
May | 2664.86 | 23-MAY-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
June | 2693.09 | 13-JUN-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
July | 3157.02 | 22-JUL-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 0.00 |
August | 3176.43 | 19-AUG-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 |
September | 3938.72 | 27-SEP-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 |
October | 3551.52 | 07-OCT-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.31 |
November | 2537.96 | 11-NOV-11:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.23 |
December | 2301.84 | 08-DEC-11:35 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2103.37 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3938.72 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 208.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1148.12 | 20-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.25 |
February | 1135.46 | 27-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 |
March | 1153.75 | 20-MAR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
April | 1430.66 | 28-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 |
May | 1466.96 | 23-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.18 |
June | 1644.36 | 13-JUN-20:50 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.98 |
July | 1676.68 | 21-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 |
August | 1613.28 | 14-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 |
September | 1614.72 | 12-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 |
October | 1310.40 | 01-OCT-10:33 | 1354.32 | 692.02 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
November | 1161.41 | 10-NOV-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
December | 1098.10 | 21-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1098.10 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | |
Maximum of Months | 1676.68 | 1354.32 | 692.02 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 724.28 | 18-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.37 |
February | 716.72 | 22-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.89 |
March | 739.26 | 20-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.91 |
April | 1006.23 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 |
May | 981.22 | 23-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
June | 1031.90 | 13-JUN-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
July | 1108.80 | 23-JUL-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 |
August | 1045.46 | 19-AUG-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.72 |
September | 1003.10 | 13-SEP-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 |
October | 919.59 | 01-OCT-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 |
November | 762.24 | 11-NOV-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.35 |
December | 695.78 | 20-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 695.78 | 190.94 | 570.15 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | |
Maximum of Months | 1108.80 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 398.18 | 18-JAN-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.66 |
February | 393.57 | 22-FEB-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.40 |
March | 410.99 | 25-MAR-18:10 | 734.40 | 979.34 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 |
April | 581.56 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
May | 567.14 | 23-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
June | 596.86 | 13-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
July | 639.33 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 |
August | 601.81 | 19-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
September | 578.70 | 13-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
October | 526.41 | 01-OCT-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.80 |
November | 434.48 | 11-NOV-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.46 |
December | 383.90 | 20-DEC-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 383.90 | 146.88 | 209.86 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | |
Maximum of Months | 639.33 | 734.40 | 979.34 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36737.28 | 23-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 227.87 |
February | 36697.28 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 291.54 |
March | 36822.53 | 30-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 262.34 |
April | 37883.15 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 165.09 |
May | 38008.31 | 22-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.66 |
June | 38307.78 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.61 |
July | 38320.04 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
August | 38206.71 | 14-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 |
September | 38040.78 | 13-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 |
October | 37387.02 | 06-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 244.60 |
November | 36838.63 | 08-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 |
December | 36502.06 | 20-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 261.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36502.06 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 | |
Maximum of Months | 38320.04 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 291.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10628.81 | 21-JAN-11:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.51 |
February | 12041.61 | 04-FEB-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.25 |
March | 8958.50 | 25-MAR-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.52 |
April | 12310.13 | 29-APR-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 |
May | 10608.05 | 23-MAY-10:33 | 10245.60 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.15 |
June | 10960.36 | 25-JUN-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.32 |
July | 11771.14 | 22-JUL-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 | 0.00 |
August | 12357.15 | 28-AUG-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
September | 13832.13 | 23-SEP-12:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.40 |
October | 13607.27 | 07-OCT-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.13 |
November | 10655.03 | 11-NOV-11:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.51 |
December | 9357.88 | 08-DEC-11:35 | 6830.40 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8958.50 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13832.13 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 | 472.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27459.39 | 21-JAN-11:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1273.96 |
February | 27152.77 | 04-FEB-11:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.14 |
March | 26584.12 | 20-MAR-20:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.37 |
April | 32740.65 | 30-APR-10:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.53 |
May | 31831.20 | 23-MAY-20:08 | 405537.60 | 84487.11 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.46 |
June | 34075.12 | 13-JUN-21:12 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.96 |
July | 35035.21 | 21-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.75 |
August | 34808.42 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.49 |
September | 35271.28 | 12-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.02 |
October | 30955.50 | 01-OCT-10:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.02 |
November | 28049.71 | 11-NOV-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.32 |
December | 25531.48 | 21-DEC-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25531.48 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.53 | |
Maximum of Months | 35271.28 | 456229.80 | 84487.11 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2904.13 | 19-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.51 |
February | 3760.57 | 17-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.52 |
March | 3659.04 | 10-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.41 |
April | 3840.11 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.50 |
May | 3765.67 | 11-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
June | 3401.91 | 05-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 |
July | 3446.30 | 18-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
August | 3437.35 | 15-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 |
September | 3393.03 | 12-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 |
October | 3704.16 | 06-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.38 |
November | 2998.47 | 10-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 |
December | 284.23 | 24-DEC-09:06 | 270.00 | 498.07 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 284.23 | 270.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | |
Maximum of Months | 3840.11 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2439.62 | 19-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 |
February | 3150.23 | 17-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.23 |
March | 2719.30 | 10-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.98 |
April | 3443.22 | 14-APR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 |
May | 3536.81 | 11-MAY-19:31 | 1247.40 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.20 |
June | 3647.28 | 20-JUN-20:01 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.44 |
July | 3692.59 | 11-JUL-19:11 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 |
August | 3544.27 | 01-AUG-19:31 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.69 |
September | 3592.47 | 14-SEP-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.45 |
October | 3301.53 | 06-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.06 |
November | 2548.88 | 10-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.23 |
December | 285.82 | 02-DEC-09:06 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 285.82 | 270.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.20 | |
Maximum of Months | 3692.59 | 1602.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 382.59 | 21-JAN-11:25 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.66 |
February | 270.64 | 19-FEB-14:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 |
March | 129.85 | 25-MAR-14:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.38 |
April | 566.81 | 30-APR-12:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
May | 435.75 | 22-MAY-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
June | 443.99 | 13-JUN-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
July | 518.09 | 22-JUL-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 555.07 | 20-AUG-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
September | 689.66 | 27-SEP-13:15 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
October | 630.31 | 07-OCT-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 |
November | 334.64 | 11-NOV-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 |
December | 118.54 | 26-DEC-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 118.54 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 689.66 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 41.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 821.66 | 29-JAN-09:02 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 |
February | 755.27 | 21-FEB-19:02 | 693.00 | 497.61 | 593.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.39 |
March | 926.36 | 30-MAR-18:03 | 554.40 | 398.09 | 474.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
April | 1030.43 | 20-APR-18:01 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
May | 1020.57 | 11-MAY-19:31 | 1247.40 | 1006.40 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
June | 1024.96 | 08-JUN-19:11 | 1108.80 | 894.58 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 |
July | 1013.13 | 10-JUL-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 |
August | 980.06 | 21-AUG-21:01 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 |
September | 953.33 | 14-SEP-18:01 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 |
October | 969.75 | 07-OCT-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 |
November | 850.70 | 09-NOV-19:02 | 693.00 | 497.61 | 593.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.69 |
December | 758.25 | 02-DEC-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 755.27 | 216.00 | 250.48 | 474.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | |
Maximum of Months | 1030.43 | 1800.00 | 1006.40 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2425.93 | 21-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.40 |
February | 3224.31 | 17-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.15 |
March | 2634.46 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 |
April | 3479.42 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 |
May | 3447.69 | 11-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 |
June | 3125.22 | 24-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.37 |
July | 3192.87 | 18-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.05 |
August | 3145.89 | 10-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
September | 3188.88 | 10-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
October | 3355.84 | 07-OCT-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 |
November | 2534.25 | 11-NOV-09:02 | 270.00 | 498.07 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.13 |
December | 522.88 | 06-DEC-09:03 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 522.88 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | |
Maximum of Months | 3479.42 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 461.51 | 23-JAN-09:04 | 180.00 | 391.30 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.29 |
February | 2096.01 | 20-FEB-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.70 |
March | 1435.07 | 25-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.75 |
April | 3140.96 | 14-APR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.63 |
May | 3285.09 | 23-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 |
June | 3417.02 | 26-JUN-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
July | 3678.28 | 23-JUL-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
August | 3453.87 | 17-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 |
September | 3384.37 | 11-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 |
October | 2940.98 | 07-OCT-18:01 | 819.00 | 1245.03 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.60 |
November | 1456.61 | 11-NOV-09:02 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.08 |
December | 375.51 | 06-DEC-09:05 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 375.51 | 180.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | |
Maximum of Months | 3678.28 | 819.00 | 1245.03 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1761.10 | 21-JAN-11:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.00 |
February | 1760.04 | 22-FEB-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.55 |
March | 1667.61 | 20-MAR-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 |
April | 2386.02 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 |
May | 2290.35 | 23-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 |
June | 2386.70 | 13-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
July | 2548.34 | 23-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
August | 2443.38 | 19-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 |
September | 2346.07 | 13-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
October | 2186.05 | 01-OCT-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.03 |
November | 1771.89 | 11-NOV-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 |
December | 1464.43 | 21-DEC-22:00 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1464.43 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | |
Maximum of Months | 2548.34 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3058.64 | 19-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.78 |
February | 3938.13 | 17-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.75 |
March | 2896.58 | 23-MAR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.33 |
April | 4038.34 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 |
May | 3947.08 | 11-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.31 |
June | 3592.46 | 05-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.99 |
July | 3613.64 | 22-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 0.00 |
August | 3609.56 | 15-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 |
September | 3547.06 | 12-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
October | 3876.75 | 06-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.57 |
November | 3166.30 | 10-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.22 |
December | 277.71 | 02-DEC-09:06 | 270.00 | 498.07 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 277.71 | 270.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4038.34 | 970.20 | 1108.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 119.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1975.47 | 19-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 |
February | 2770.17 | 27-FEB-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.75 |
March | 2616.17 | 23-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
April | 3592.09 | 14-APR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.68 |
May | 3786.62 | 23-MAY-19:42 | 831.60 | 1067.17 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.03 |
June | 3862.03 | 22-JUN-18:42 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.90 |
July | 4028.18 | 11-JUL-18:52 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 |
August | 3729.06 | 29-AUG-18:31 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.21 |
September | 3779.85 | 14-SEP-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 |
October | 3448.49 | 06-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.77 |
November | 2380.14 | 10-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.94 |
December | 69.40 | 21-DEC-14:00 | 36.00 | 49.80 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 69.40 | 36.00 | 49.80 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.68 | |
Maximum of Months | 4028.18 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2437.56 | 11-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.12 |
February | 1970.31 | 27-FEB-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 |
March | 2068.10 | 25-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 |
April | 2074.21 | 29-APR-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
May | 2437.47 | 11-MAY-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
June | 2271.62 | 08-JUN-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
July | 2266.46 | 16-JUL-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 |
August | 2194.46 | 12-AUG-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 |
September | 2244.54 | 14-SEP-18:01 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
October | 2433.87 | 06-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 |
November | 2023.77 | 10-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.45 |
December | 1884.71 | 21-DEC-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1884.71 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | |
Maximum of Months | 2437.56 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17643.66 | 18-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.49 |
February | 17459.92 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.07 |
March | 17792.78 | 20-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.03 |
April | 19885.34 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.32 |
May | 20625.32 | 22-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.33 |
June | 21254.40 | 13-JUN-21:12 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.07 |
July | 21289.21 | 21-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 |
August | 20865.38 | 14-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 |
September | 20216.78 | 12-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.26 |
October | 18519.96 | 02-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.60 |
November | 18194.92 | 08-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.39 |
December | 16976.67 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16976.67 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 | |
Maximum of Months | 21289.21 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19671.31 | 18-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.49 |
February | 19495.32 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.07 |
March | 19804.34 | 30-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.50 |
April | 21468.48 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.33 |
May | 22178.49 | 22-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.33 |
June | 23015.16 | 13-JUN-21:11 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 |
July | 22708.87 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.00 |
August | 22296.90 | 14-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 |
September | 21674.92 | 12-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.27 |
October | 20412.46 | 12-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.88 |
November | 20217.34 | 08-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.40 |
December | 19026.40 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19026.40 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 | |
Maximum of Months | 23015.16 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27436.79 | 15-JAN-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 241.21 |
February | 27634.73 | 22-FEB-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 215.34 |
March | 28415.19 | 25-MAR-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 194.66 |
April | 30739.97 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 |
May | 30543.91 | 23-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
June | 30871.61 | 25-JUN-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 61.44 |
July | 31312.08 | 23-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 |
August | 30716.38 | 19-AUG-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 92.01 |
September | 30296.75 | 10-SEP-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 |
October | 29297.72 | 07-OCT-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 |
November | 27327.72 | 11-NOV-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 236.10 |
December | 26567.21 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 273.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26567.21 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 | |
Maximum of Months | 31312.08 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 273.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3724.32 | 21-JAN-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.62 |
February | 3782.17 | 22-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.51 |
March | 3825.24 | 25-MAR-10:45 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.09 |
April | 5068.11 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 |
May | 4984.25 | 23-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 |
June | 5199.44 | 13-JUN-17:12 | 5323.20 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 0.00 |
July | 5441.47 | 23-JUL-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 |
August | 5128.38 | 19-AUG-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.74 |
September | 4948.88 | 13-SEP-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 |
October | 4403.10 | 01-OCT-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.86 |
November | 3763.49 | 11-NOV-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.06 |
December | 3427.12 | 06-DEC-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3427.12 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5441.47 | 5323.20 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 232.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.363168E+12 | 236234.88 | 18-JAN-20:19 | 0.587546E+12 | 569412.86 | 30-JAN-18:49 |
February | 0.327550E+12 | 236105.86 | 27-FEB-20:10 | 0.494780E+12 | 571482.88 | 21-FEB-18:40 |
March | 0.356528E+12 | 238930.03 | 20-MAR-19:10 | 0.583023E+12 | 570628.40 | 16-MAR-17:49 |
April | 0.362166E+12 | 288737.08 | 30-APR-18:19 | 0.548522E+12 | 536214.85 | 11-APR-17:49 |
May | 0.370776E+12 | 267814.75 | 22-MAY-19:49 | 0.582213E+12 | 525095.41 | 01-MAY-19:10 |
June | 0.375560E+12 | 313741.70 | 12-JUN-18:10 | 0.518002E+12 | 498887.50 | 06-JUN-20:49 |
July | 0.405534E+12 | 322411.82 | 22-JUL-18:10 | 0.491249E+12 | 472139.99 | 03-JUL-20:00 |
August | 0.413253E+12 | 307128.47 | 14-AUG-18:10 | 0.469651E+12 | 387768.68 | 27-AUG-20:49 |
September | 0.382131E+12 | 275371.51 | 13-SEP-19:49 | 0.514170E+12 | 502520.02 | 20-SEP-20:10 |
October | 0.361356E+12 | 248280.38 | 05-OCT-19:19 | 0.609134E+12 | 537780.36 | 30-OCT-17:40 |
November | 0.346517E+12 | 236974.20 | 15-NOV-20:40 | 0.607903E+12 | 565041.04 | 21-NOV-18:40 |
December | 0.363530E+12 | 235011.21 | 20-DEC-20:49 | 0.566463E+12 | 560214.84 | 19-DEC-18:00 |
Annual Sum or Average | 0.442807E+13 | 0.657266E+13 | ||||
Minimum of Months | 0.327550E+12 | 235011.21 | 0.469651E+12 | 387768.68 | ||
Maximum of Months | 0.413253E+12 | 322411.82 | 0.609134E+12 | 571482.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.673725E+11 | 0.211506E+11 | 0.140828E+12 | 0.544240E+11 | 0.402353E+11 | 0.274188E+10 | 0.00 | 0.180989E+10 | 0.00 | 0.00 | 0.216765E+11 | 0.770487E+10 | 0.00 |
February | 0.605265E+11 | 0.174046E+11 | 0.127191E+12 | 0.491571E+11 | 0.361385E+11 | 0.254269E+10 | 0.00 | 0.183417E+10 | 0.00 | 0.00 | 0.210726E+11 | 0.696244E+10 | 0.00 |
March | 0.666420E+11 | 0.169382E+11 | 0.140882E+12 | 0.544262E+11 | 0.399785E+11 | 0.310768E+10 | 0.00 | 0.218411E+10 | 0.00 | 0.00 | 0.194373E+11 | 0.770353E+10 | 0.00 |
April | 0.638888E+11 | 0.140362E+11 | 0.136245E+12 | 0.526674E+11 | 0.405517E+11 | 0.696714E+10 | 0.00 | 0.229074E+11 | 0.00 | 0.00 | 0.123842E+11 | 0.746522E+10 | 0.00 |
May | 0.654774E+11 | 0.124372E+11 | 0.140860E+12 | 0.544241E+11 | 0.421320E+11 | 0.778611E+10 | 0.00 | 0.249022E+11 | 0.00 | 0.00 | 0.979340E+10 | 0.770475E+10 | 0.00 |
June | 0.630969E+11 | 0.109343E+11 | 0.136336E+12 | 0.526693E+11 | 0.424213E+11 | 0.868987E+10 | 0.00 | 0.448261E+11 | 0.00 | 0.00 | 0.399727E+10 | 0.745699E+10 | 0.00 |
July | 0.652946E+11 | 0.117857E+11 | 0.140770E+12 | 0.544216E+11 | 0.445494E+11 | 0.939529E+10 | 0.00 | 0.633184E+11 | 0.00 | 0.00 | 0.300099E+10 | 0.771272E+10 | 0.00 |
August | 0.658154E+11 | 0.135846E+11 | 0.140892E+12 | 0.544257E+11 | 0.445020E+11 | 0.955402E+10 | 0.00 | 0.694497E+11 | 0.00 | 0.00 | 0.201181E+10 | 0.770448E+10 | 0.00 |
September | 0.642586E+11 | 0.153688E+11 | 0.136256E+12 | 0.526677E+11 | 0.421744E+11 | 0.875829E+10 | 0.00 | 0.466611E+11 | 0.00 | 0.00 | 0.339751E+10 | 0.746655E+10 | 0.00 |
October | 0.669869E+11 | 0.183004E+11 | 0.140818E+12 | 0.544238E+11 | 0.407776E+11 | 0.541229E+10 | 0.00 | 0.111083E+11 | 0.00 | 0.00 | 0.105634E+11 | 0.770331E+10 | 0.00 |
November | 0.651790E+11 | 0.198254E+11 | 0.136330E+12 | 0.526691E+11 | 0.389192E+11 | 0.301735E+10 | 0.00 | 0.203308E+10 | 0.00 | 0.00 | 0.160309E+11 | 0.744934E+10 | 0.00 |
December | 0.675549E+11 | 0.217206E+11 | 0.140770E+12 | 0.544230E+11 | 0.404593E+11 | 0.156293E+10 | 0.00 | 0.395745E+09 | 0.00 | 0.00 | 0.237091E+11 | 0.771305E+10 | 0.00 |
Annual Sum or Average | 0.782094E+12 | 0.193487E+12 | 0.165818E+13 | 0.640799E+12 | 0.492839E+12 | 0.695356E+11 | 0.00 | 0.291430E+12 | 0.00 | 0.00 | 0.147075E+12 | 0.907473E+11 | 0.00 |
Minimum of Months | 0.605265E+11 | 0.109343E+11 | 0.127191E+12 | 0.491571E+11 | 0.361385E+11 | 0.156293E+10 | 0.00 | 0.395745E+09 | 0.00 | 0.00 | 0.201181E+10 | 0.696244E+10 | 0.00 |
Maximum of Months | 0.675549E+11 | 0.217206E+11 | 0.140892E+12 | 0.544262E+11 | 0.445494E+11 | 0.955402E+10 | 0.00 | 0.694497E+11 | 0.00 | 0.00 | 0.237091E+11 | 0.771305E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.150974E+12 | 0.00 | 0.284654E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.992729E+11 | 0.00 | 0.258303E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.146228E+12 | 0.00 | 0.284771E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.129569E+12 | 0.00 | 0.271998E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.154240E+12 | 0.00 | 0.275995E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.108662E+12 | 0.00 | 0.262226E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.722739E+11 | 0.00 | 0.267155E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.518040E+11 | 0.00 | 0.265808E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.108708E+12 | 0.00 | 0.258491E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.186463E+12 | 0.00 | 0.270768E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.193896E+12 | 0.00 | 0.266915E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.133742E+12 | 0.00 | 0.280901E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.153583E+13 | 0.00 | 0.324799E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.518040E+11 | 0.00 | 0.258303E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.193896E+12 | 0.00 | 0.284771E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 22410.49 | 10-JAN-19:10 | 3652.30 | 21-JAN-11:00 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 20974.79 | 07-FEB-19:10 | 3628.59 | 27-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 01-MAR-07:19 | 21151.12 | 30-MAR-20:10 | 3679.41 | 20-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.97 | 10-APR-06:19 | 26096.30 | 28-APR-21:10 | 4676.40 | 29-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39168.78 | 01-MAY-06:19 | 27761.40 | 22-MAY-21:49 | 4631.50 | 22-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:30 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.28 | 15-JUN-06:19 | 30205.92 | 13-JUN-21:30 | 4758.37 | 25-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 17-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.39 | 25-JUL-06:19 | 29180.82 | 21-JUL-21:00 | 4818.01 | 22-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.68 | 15-AUG-06:19 | 29206.12 | 17-AUG-21:30 | 4844.63 | 14-AUG-18:40 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 18-SEP-06:19 | 29230.70 | 11-SEP-21:10 | 4742.18 | 25-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 24073.50 | 03-OCT-21:10 | 4254.26 | 07-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 22020.80 | 08-NOV-21:10 | 3660.09 | 03-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 22340.36 | 29-DEC-19:10 | 3073.31 | 18-DEC-14:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.28 | 20974.79 | 3073.31 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 30205.92 | 4844.63 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12649.03 | 21-JAN-10:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.27 | 17-JAN-07:10 | 0.00 |
February | 13048.02 | 19-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.24 | 01-FEB-19:10 | 0.00 |
March | 11964.17 | 20-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.36 | 27-MAR-18:10 | 0.00 |
April | 87074.26 | 30-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.61 | 03-APR-18:10 | 0.00 |
May | 82958.06 | 22-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-01:00 | 4738.24 | 30-MAY-06:19 | 0.00 |
June | 105249.75 | 12-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-01:30 | 4738.32 | 02-JUN-18:10 | 0.00 |
July | 118965.02 | 22-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 03-JUL-21:10 | 4738.28 | 21-JUL-18:30 | 0.00 |
August | 98738.22 | 14-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 14-AUG-12:39 | 4738.34 | 14-AUG-06:10 | 0.00 |
September | 85396.53 | 13-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 04-SEP-05:19 | 4738.43 | 20-SEP-18:10 | 0.00 |
October | 54578.02 | 07-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-02:09 | 4738.26 | 10-OCT-06:19 | 0.00 |
November | 11250.86 | 11-NOV-13:30 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.16 | 27-NOV-19:10 | 0.00 |
December | 2999.69 | 02-DEC-09:09 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.55 | 20-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2999.69 | 0.00 | 0.00 | 9938.94 | 4738.16 | 0.00 | |||
Maximum of Months | 118965.02 | 0.00 | 0.00 | 9938.94 | 4738.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 236234.88 | 18-JAN-20:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 19975.66 | 2571.22 | 0.00 | 2492.29 | 0.00 |
February | 236105.86 | 27-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20051.10 | 2569.02 | 0.00 | 2330.19 | 0.00 |
March | 238930.03 | 20-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20495.11 | 2794.74 | 0.00 | 4546.13 | 0.00 |
April | 288737.08 | 30-APR-18:19 | 51227.63 | 74651.16 | 0.00 | 31292.57 | 24516.28 | 4621.85 | 0.00 | 86201.91 | 0.00 |
May | 267814.75 | 22-MAY-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21900.97 | 3984.69 | 0.00 | 40486.17 | 0.00 |
June | 313741.70 | 12-JUN-18:10 | 52987.32 | 77573.37 | 0.00 | 31341.98 | 24744.36 | 4750.31 | 0.00 | 105249.75 | 0.00 |
July | 322411.82 | 22-JUL-18:10 | 51055.14 | 74651.16 | 0.00 | 31287.56 | 25061.02 | 4818.01 | 0.00 | 118965.02 | 0.00 |
August | 307128.47 | 14-AUG-18:10 | 53184.46 | 77573.37 | 0.00 | 31342.09 | 24584.03 | 4643.45 | 0.00 | 98738.22 | 0.00 |
September | 275371.51 | 13-SEP-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 25885.92 | 4122.34 | 0.00 | 44043.75 | 0.00 |
October | 248280.38 | 05-OCT-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21681.91 | 3292.81 | 0.00 | 12130.19 | 0.00 |
November | 236974.20 | 15-NOV-20:40 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 20321.24 | 2604.53 | 0.00 | 2682.76 | 0.00 |
December | 235011.21 | 20-DEC-20:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 19801.65 | 2520.23 | 0.00 | 1372.36 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 235011.21 | 51055.14 | 74651.16 | 0.00 | 31287.56 | 19801.65 | 2520.23 | 0.00 | 1372.36 | 0.00 | |
Maximum of Months | 322411.82 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 25885.92 | 4818.01 | 0.00 | 118965.02 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 194747.75 | 31-JAN-11:39 | 0.00 | 286947.19 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 198766.20 | 05-FEB-11:50 | 0.00 | 287228.02 | 17-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 196570.45 | 13-MAR-10:50 | 0.00 | 286777.72 | 06-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 189662.53 | 11-APR-07:30 | 0.00 | 284461.82 | 05-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 191757.34 | 27-MAY-22:40 | 0.00 | 280769.93 | 04-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 181472.16 | 07-JUN-10:20 | 0.00 | 270121.76 | 02-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 164707.36 | 09-JUL-03:00 | 0.00 | 248377.26 | 27-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 165663.36 | 24-AUG-05:40 | 0.00 | 248006.23 | 08-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 193262.05 | 28-SEP-06:10 | 0.00 | 249615.89 | 20-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 197467.60 | 31-OCT-08:09 | 0.00 | 271206.76 | 25-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 203900.53 | 12-NOV-11:50 | 0.00 | 281061.97 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 211025.41 | 16-DEC-16:10 | 0.00 | 284635.69 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 164707.36 | 0.00 | 248006.23 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 211025.41 | 0.00 | 287228.02 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.47 | 2.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.48 | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.46 | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 4.67 | 20.46 | 4.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 7.50 | 20.46 | 7.50 | 20.46 | 1.00 | 20.54 | 1.00 | 20.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.48 | 4.67 | 20.48 | 0.50 | 21.75 | 0.50 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.44 | 4.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.17 | 20.46 | 0.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.99 | 0.33 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.03 | 1.67 | 22.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.93 | 3.33 | 21.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.87 | 0.50 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 20.45 | 1.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 9.67 | 20.45 | 9.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 16.67 | 20.45 | 16.67 | 20.45 | 7.17 | 20.71 | 7.17 | 20.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.67 | 20.52 | 9.67 | 20.52 | 3.33 | 22.03 | 3.33 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.26 | 0.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.82 | 4.17 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.72 | 2.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 0.67 | 20.33 | 0.67 | 20.33 | 10.67 | 21.62 | 10.67 | 21.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.54 | 0.50 | 20.54 | 4.17 | 21.82 | 4.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.48 | 2.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.46 | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 4.50 | 20.45 | 4.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 7.50 | 20.46 | 7.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.48 | 4.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.41 | 4.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 1.00 | 20.48 | 1.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.17 | 20.45 | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.36 | 0.33 | 22.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.46 | 0.33 | 22.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.35 | 1.17 | 22.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.29 | 1.83 | 22.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.20 | 2.00 | 22.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.03 | 1.33 | 22.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 20.47 | 2.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 7.67 | 20.43 | 7.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 15.00 | 20.43 | 15.00 | 20.43 | 7.00 | 20.78 | 7.00 | 21.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 20.48 | 7.67 | 20.48 | 2.00 | 22.46 | 2.00 | 22.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.51 | 2.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 4.17 | 20.48 | 4.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 7.67 | 20.50 | 7.67 | 20.50 | 2.50 | 20.68 | 2.50 | 20.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 20.51 | 4.17 | 20.51 | 0.67 | 21.85 | 0.67 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 20.47 | 5.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.00 | 20.54 | 1.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.93 | 1.00 | 21.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.94 | 1.00 | 21.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.09 | 2.67 | 22.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.04 | 4.33 | 22.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.83 | 2.67 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 20.49 | 2.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 10.17 | 20.49 | 10.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 18.50 | 20.49 | 18.50 | 20.49 | 12.67 | 20.86 | 12.67 | 21.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 20.55 | 10.17 | 20.55 | 4.33 | 22.09 | 4.33 | 22.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 2.33 | 20.49 | 2.33 | 20.49 | 0.67 | 20.64 | 0.67 | 20.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.51 | 1.67 | 20.51 | 0.67 | 21.72 | 0.67 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
February | 672.00 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
March | 744.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
April | 720.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
May | 744.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
June | 720.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
July | 714.17 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
August | 678.83 | 23.20 | 0.50 | 23.20 | 0.00 | 23.20 |
September | 577.17 | 23.41 | 2.33 | 23.41 | 0.00 | 23.41 |
October | 605.50 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
November | 631.50 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
December | 733.17 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 8284.33 | 23.12 | 2.83 | 23.12 | 0.00 | 23.12 |
Minimum of Months | 577.17 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
Maximum of Months | 744.00 | 23.57 | 2.33 | 23.57 | 0.00 | 23.57 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 734.17 | 21.08 | 149.67 | 21.07 | 148.83 | 21.06 |
February | 652.83 | 21.09 | 40.50 | 21.10 | 36.17 | 21.10 |
March | 744.00 | 21.02 | 39.33 | 21.02 | 39.33 | 21.02 |
April | 658.33 | 21.28 | 29.33 | 21.39 | 0.00 | 21.39 |
May | 702.50 | 21.23 | 12.50 | 21.27 | 0.00 | 21.27 |
June | 666.33 | 21.28 | 19.83 | 21.34 | 0.00 | 21.34 |
July | 641.17 | 21.39 | 62.67 | 21.58 | 0.00 | 21.58 |
August | 606.17 | 21.47 | 103.00 | 21.80 | 0.00 | 21.80 |
September | 571.00 | 21.40 | 115.33 | 21.81 | 0.00 | 21.81 |
October | 690.00 | 21.14 | 29.33 | 21.25 | 0.00 | 21.25 |
November | 713.33 | 21.08 | 37.00 | 21.08 | 35.50 | 21.07 |
December | 742.00 | 21.04 | 253.67 | 21.03 | 253.67 | 21.02 |
Annual Sum or Average | 8121.83 | 21.20 | 892.17 | 21.29 | 513.50 | 21.28 |
Minimum of Months | 571.00 | 21.02 | 12.50 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.47 | 253.67 | 21.81 | 253.67 | 21.81 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
February | 672.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
March | 744.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
April | 702.67 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
May | 716.17 | 22.56 | 1.83 | 22.56 | 0.00 | 22.56 |
June | 624.50 | 22.76 | 22.33 | 22.80 | 0.00 | 22.80 |
July | 549.17 | 22.81 | 65.00 | 22.93 | 0.00 | 22.93 |
August | 545.17 | 22.95 | 48.33 | 23.03 | 0.00 | 23.03 |
September | 595.83 | 22.89 | 28.50 | 22.94 | 0.00 | 22.94 |
October | 738.33 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
November | 720.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
December | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Annual Sum or Average | 8095.83 | 22.27 | 166.00 | 22.30 | 0.00 | 22.30 |
Minimum of Months | 545.17 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Maximum of Months | 744.00 | 22.95 | 65.00 | 23.03 | 0.00 | 23.03 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 43.50 | 21.07 | 43.50 | 21.06 |
February | 672.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
March | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
April | 720.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
May | 744.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
June | 720.00 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
July | 733.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
August | 744.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
September | 720.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
October | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
November | 720.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
December | 744.00 | 21.03 | 12.33 | 21.03 | 12.33 | 21.03 |
Annual Sum or Average | 8749.00 | 21.78 | 55.83 | 21.77 | 55.83 | 21.77 |
Minimum of Months | 672.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 22.81 | 43.50 | 22.81 | 43.50 | 22.81 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 64.17 | 21.01 | 64.17 | 21.01 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
May | 744.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
June | 720.00 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
July | 744.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
August | 744.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
September | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
October | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
November | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
December | 744.00 | 21.00 | 22.33 | 21.00 | 22.33 | 21.00 |
Annual Sum or Average | 8760.00 | 21.60 | 86.50 | 21.59 | 86.50 | 21.58 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.56 | 64.17 | 22.56 | 64.17 | 22.56 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 241.17 | 22.96 | 553.33 | 23.27 | 154.00 | 23.39 |
February | 219.00 | 23.01 | 530.17 | 23.26 | 145.00 | 23.38 |
March | 247.50 | 23.00 | 584.17 | 23.26 | 162.67 | 23.38 |
April | 257.67 | 23.27 | 593.83 | 23.31 | 192.50 | 23.44 |
May | 275.00 | 23.41 | 632.17 | 23.33 | 219.17 | 23.46 |
June | 301.33 | 23.64 | 637.83 | 23.38 | 264.00 | 23.51 |
July | 303.33 | 23.78 | 671.67 | 23.40 | 280.50 | 23.53 |
August | 303.83 | 23.81 | 669.17 | 23.41 | 284.17 | 23.54 |
September | 291.83 | 23.64 | 633.83 | 23.39 | 255.67 | 23.52 |
October | 279.50 | 23.33 | 632.67 | 23.32 | 215.50 | 23.45 |
November | 242.00 | 23.11 | 576.00 | 23.29 | 168.17 | 23.41 |
December | 237.83 | 22.92 | 544.17 | 23.26 | 148.50 | 23.38 |
Annual Sum or Average | 3200.00 | 23.36 | 7259.00 | 23.33 | 2489.83 | 23.46 |
Minimum of Months | 219.00 | 22.92 | 530.17 | 23.26 | 145.00 | 23.38 |
Maximum of Months | 303.83 | 23.81 | 671.67 | 23.41 | 284.17 | 23.54 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.67 | 21.45 | 8.00 | 21.47 | 0.83 | 21.47 |
February | 636.00 | 21.52 | 15.50 | 21.58 | 0.00 | 21.58 |
March | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
April | 601.67 | 22.06 | 56.17 | 22.20 | 0.00 | 22.20 |
May | 652.50 | 22.01 | 39.50 | 22.09 | 0.00 | 22.09 |
June | 583.17 | 22.18 | 77.50 | 22.31 | 9.00 | 22.32 |
July | 448.83 | 22.16 | 157.83 | 22.48 | 0.50 | 22.48 |
August | 366.50 | 22.34 | 211.17 | 22.78 | 2.33 | 22.79 |
September | 388.17 | 22.29 | 205.17 | 22.77 | 0.00 | 22.77 |
October | 661.67 | 21.84 | 54.50 | 21.99 | 0.00 | 21.99 |
November | 699.83 | 21.53 | 5.17 | 21.55 | 0.00 | 21.55 |
December | 737.33 | 21.31 | 8.33 | 21.31 | 7.33 | 21.30 |
Annual Sum or Average | 7239.33 | 21.78 | 838.83 | 21.96 | 20.00 | 21.96 |
Minimum of Months | 366.50 | 21.31 | 0.00 | 21.31 | 0.00 | 21.30 |
Maximum of Months | 744.00 | 22.34 | 211.17 | 22.78 | 9.00 | 22.79 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
February | 672.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
March | 744.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
April | 663.50 | 22.74 | 1.17 | 22.74 | 0.00 | 22.74 |
May | 649.67 | 22.69 | 9.50 | 22.71 | 0.00 | 22.71 |
June | 482.83 | 22.76 | 69.67 | 22.90 | 8.33 | 22.91 |
July | 389.33 | 22.76 | 192.00 | 23.13 | 0.33 | 23.13 |
August | 269.83 | 22.80 | 194.50 | 23.25 | 1.17 | 23.25 |
September | 358.00 | 22.90 | 135.17 | 23.16 | 0.00 | 23.16 |
October | 695.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
November | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
December | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
Annual Sum or Average | 7132.17 | 22.42 | 602.00 | 22.54 | 9.83 | 22.54 |
Minimum of Months | 269.83 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
Maximum of Months | 744.00 | 22.90 | 194.50 | 23.25 | 8.33 | 23.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 321.17 | 20.79 | 321.17 | 20.73 |
February | 672.00 | 21.03 | 183.17 | 20.93 | 183.17 | 20.86 |
March | 744.00 | 20.98 | 163.50 | 20.90 | 163.50 | 20.85 |
April | 698.67 | 21.48 | 4.00 | 21.48 | 2.83 | 21.47 |
May | 718.17 | 21.47 | 1.33 | 21.48 | 0.00 | 21.48 |
June | 669.33 | 21.53 | 5.67 | 21.54 | 0.00 | 21.54 |
July | 670.67 | 21.50 | 7.17 | 21.52 | 0.00 | 21.52 |
August | 666.67 | 21.49 | 3.00 | 21.50 | 0.00 | 21.50 |
September | 666.50 | 21.51 | 1.67 | 21.51 | 0.00 | 21.51 |
October | 735.00 | 21.22 | 22.17 | 21.18 | 22.17 | 21.15 |
November | 720.00 | 20.95 | 198.50 | 20.84 | 198.50 | 20.77 |
December | 744.00 | 20.70 | 550.17 | 20.64 | 550.17 | 20.62 |
Annual Sum or Average | 8449.00 | 21.22 | 1461.50 | 21.12 | 1441.50 | 21.05 |
Minimum of Months | 666.50 | 20.70 | 1.33 | 20.64 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.53 | 550.17 | 21.54 | 550.17 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 467.00 | 20.60 | 467.00 | 20.56 |
February | 672.00 | 20.80 | 329.83 | 20.69 | 329.83 | 20.64 |
March | 744.00 | 20.87 | 247.50 | 20.78 | 247.50 | 20.73 |
April | 701.50 | 21.39 | 19.83 | 21.46 | 9.67 | 21.45 |
May | 711.17 | 21.50 | 26.67 | 21.66 | 6.67 | 21.72 |
June | 652.83 | 21.74 | 50.50 | 22.04 | 13.83 | 22.15 |
July | 618.67 | 21.94 | 105.00 | 22.53 | 30.33 | 22.74 |
August | 611.50 | 21.88 | 86.83 | 22.33 | 11.50 | 22.41 |
September | 652.17 | 21.57 | 37.00 | 21.76 | 0.00 | 21.76 |
October | 744.00 | 21.09 | 37.83 | 21.03 | 37.83 | 20.98 |
November | 720.00 | 20.77 | 313.50 | 20.66 | 313.50 | 20.60 |
December | 744.00 | 20.57 | 650.83 | 20.53 | 650.83 | 20.52 |
Annual Sum or Average | 8315.83 | 21.21 | 2372.33 | 21.20 | 2118.50 | 21.11 |
Minimum of Months | 611.50 | 20.57 | 19.83 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.94 | 650.83 | 22.53 | 650.83 | 22.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 129.67 | 20.94 | 129.67 | 20.90 |
February | 672.00 | 21.05 | 23.33 | 21.03 | 23.33 | 21.01 |
March | 744.00 | 21.17 | 4.00 | 21.17 | 4.00 | 21.16 |
April | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
May | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
June | 716.17 | 21.68 | 0.50 | 21.68 | 0.00 | 21.68 |
July | 739.83 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
August | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
September | 720.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.09 | 28.00 | 21.06 | 28.00 | 21.03 |
December | 744.00 | 20.96 | 137.50 | 20.88 | 137.50 | 20.82 |
Annual Sum or Average | 8752.00 | 21.37 | 323.00 | 21.33 | 322.50 | 21.31 |
Minimum of Months | 672.00 | 20.96 | 0.00 | 20.88 | 0.00 | 20.82 |
Maximum of Months | 744.00 | 21.85 | 137.50 | 21.85 | 137.50 | 21.85 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 318.50 | 20.78 | 318.50 | 20.73 |
February | 672.00 | 21.02 | 197.83 | 20.93 | 197.83 | 20.87 |
March | 744.00 | 21.01 | 155.67 | 20.93 | 155.67 | 20.88 |
April | 696.33 | 21.58 | 1.33 | 21.58 | 1.33 | 21.58 |
May | 723.17 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
June | 664.17 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
July | 665.50 | 21.52 | 0.50 | 21.53 | 0.00 | 21.53 |
August | 631.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
September | 648.50 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
October | 744.00 | 21.29 | 20.83 | 21.25 | 20.83 | 21.22 |
November | 720.00 | 20.94 | 189.67 | 20.84 | 189.67 | 20.77 |
December | 744.00 | 20.72 | 526.83 | 20.65 | 526.83 | 20.62 |
Annual Sum or Average | 8396.67 | 21.24 | 1411.17 | 21.14 | 1410.67 | 21.07 |
Minimum of Months | 631.00 | 20.72 | 0.00 | 20.65 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.58 | 526.83 | 21.58 | 526.83 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 462.17 | 20.60 | 462.17 | 20.56 |
February | 672.00 | 20.77 | 365.83 | 20.69 | 365.83 | 20.65 |
March | 744.00 | 20.91 | 223.00 | 20.83 | 223.00 | 20.78 |
April | 713.17 | 21.59 | 10.67 | 21.59 | 8.17 | 21.58 |
May | 726.00 | 21.62 | 5.67 | 21.65 | 0.00 | 21.65 |
June | 657.33 | 21.72 | 24.00 | 21.83 | 1.00 | 21.84 |
July | 656.50 | 21.90 | 28.33 | 22.03 | 3.33 | 22.06 |
August | 683.83 | 22.01 | 17.17 | 22.08 | 0.00 | 22.08 |
September | 703.33 | 21.81 | 8.00 | 21.85 | 0.00 | 21.85 |
October | 744.00 | 21.14 | 32.33 | 21.10 | 32.33 | 21.05 |
November | 720.00 | 20.76 | 314.17 | 20.65 | 314.17 | 20.59 |
December | 744.00 | 20.58 | 623.00 | 20.54 | 623.00 | 20.52 |
Annual Sum or Average | 8508.17 | 21.28 | 2114.33 | 21.15 | 2033.00 | 21.05 |
Minimum of Months | 656.50 | 20.58 | 5.67 | 20.54 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 22.01 | 623.00 | 22.08 | 623.00 | 22.08 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 22.17 | 21.01 | 22.17 | 21.01 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
May | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
June | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
July | 744.00 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
August | 744.00 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
September | 720.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
October | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.00 | 14.83 | 21.00 | 14.83 | 21.00 |
Annual Sum or Average | 8760.00 | 21.62 | 37.00 | 21.62 | 37.00 | 21.62 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.57 | 22.17 | 22.57 | 22.17 | 22.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 486.00 | 20.71 | 486.00 | 20.67 |
February | 671.67 | 20.93 | 340.33 | 20.82 | 340.33 | 20.77 |
March | 744.00 | 20.89 | 346.83 | 20.82 | 346.83 | 20.79 |
April | 686.33 | 21.43 | 28.00 | 21.42 | 23.50 | 21.40 |
May | 706.83 | 21.42 | 7.50 | 21.44 | 1.67 | 21.44 |
June | 653.00 | 21.47 | 14.00 | 21.51 | 0.00 | 21.51 |
July | 651.67 | 21.44 | 24.67 | 21.51 | 0.00 | 21.51 |
August | 643.17 | 21.42 | 15.17 | 21.46 | 0.00 | 21.46 |
September | 655.33 | 21.45 | 12.17 | 21.49 | 0.00 | 21.49 |
October | 732.83 | 21.14 | 55.17 | 21.06 | 55.17 | 20.98 |
November | 720.00 | 20.84 | 324.83 | 20.73 | 324.83 | 20.67 |
December | 744.00 | 20.61 | 679.33 | 20.59 | 679.33 | 20.58 |
Annual Sum or Average | 8352.83 | 21.14 | 2334.00 | 21.03 | 2257.67 | 20.95 |
Minimum of Months | 643.17 | 20.61 | 7.50 | 20.59 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.47 | 679.33 | 21.51 | 679.33 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 599.67 | 20.54 | 599.67 | 20.53 |
February | 672.00 | 20.69 | 513.50 | 20.63 | 513.50 | 20.61 |
March | 744.00 | 20.78 | 457.17 | 20.72 | 457.17 | 20.69 |
April | 699.50 | 21.41 | 55.83 | 21.47 | 46.00 | 21.48 |
May | 709.00 | 21.53 | 33.67 | 21.74 | 15.67 | 21.85 |
June | 642.67 | 21.80 | 56.50 | 22.17 | 24.33 | 22.37 |
July | 617.33 | 22.12 | 117.33 | 22.81 | 50.17 | 23.14 |
August | 599.00 | 21.96 | 101.17 | 22.53 | 26.67 | 22.72 |
September | 640.67 | 21.55 | 48.33 | 21.82 | 5.17 | 21.86 |
October | 744.00 | 21.00 | 109.33 | 20.88 | 109.33 | 20.79 |
November | 720.00 | 20.65 | 457.17 | 20.56 | 457.17 | 20.52 |
December | 744.00 | 20.50 | 735.00 | 20.50 | 735.00 | 20.49 |
Annual Sum or Average | 8276.17 | 21.18 | 3284.67 | 21.17 | 3039.83 | 21.09 |
Minimum of Months | 599.00 | 20.50 | 33.67 | 20.50 | 5.17 | 20.49 |
Maximum of Months | 744.00 | 22.12 | 735.00 | 22.81 | 735.00 | 23.14 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.83 | 21.14 | 177.67 | 21.04 | 177.67 | 20.97 |
February | 649.00 | 21.21 | 66.67 | 21.15 | 66.00 | 21.10 |
March | 744.00 | 21.18 | 80.17 | 21.13 | 80.17 | 21.08 |
April | 663.00 | 21.48 | 6.50 | 21.50 | 0.00 | 21.50 |
May | 691.67 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
June | 660.67 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
July | 660.17 | 21.47 | 2.00 | 21.48 | 0.00 | 21.48 |
August | 638.50 | 21.41 | 17.33 | 21.46 | 0.00 | 21.46 |
September | 621.83 | 21.42 | 36.50 | 21.53 | 0.00 | 21.53 |
October | 697.50 | 21.28 | 14.00 | 21.27 | 10.17 | 21.26 |
November | 705.17 | 21.16 | 68.33 | 21.09 | 68.33 | 21.02 |
December | 740.83 | 20.98 | 333.17 | 20.86 | 333.17 | 20.79 |
Annual Sum or Average | 8202.17 | 21.30 | 802.33 | 21.26 | 735.50 | 21.20 |
Minimum of Months | 621.83 | 20.98 | 0.00 | 20.86 | 0.00 | 20.79 |
Maximum of Months | 744.00 | 21.50 | 333.17 | 21.53 | 333.17 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.17 | 23.09 | 42.17 | 23.18 | 0.00 | 23.18 |
February | 291.83 | 23.11 | 49.50 | 23.24 | 0.00 | 23.24 |
March | 245.00 | 23.11 | 62.00 | 23.29 | 0.00 | 23.29 |
April | 101.83 | 23.25 | 208.33 | 23.75 | 0.00 | 23.75 |
May | 53.33 | 23.20 | 442.50 | 23.89 | 0.00 | 23.89 |
June | 11.00 | 23.72 | 651.83 | 23.95 | 7.33 | 23.95 |
July | 0.00 | 0.00 | 716.00 | 23.96 | 0.00 | 23.96 |
August | 0.33 | 23.99 | 717.33 | 23.94 | 0.33 | 23.94 |
September | 12.83 | 23.16 | 567.50 | 23.92 | 0.00 | 23.92 |
October | 156.00 | 23.06 | 291.33 | 23.66 | 0.00 | 23.66 |
November | 275.67 | 23.05 | 132.00 | 23.36 | 0.00 | 23.36 |
December | 375.50 | 23.05 | 14.67 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 1876.50 | 23.10 | 3895.17 | 23.68 | 7.67 | 23.68 |
Minimum of Months | 0.00 | 0.00 | 14.67 | 23.08 | 0.00 | 23.08 |
Maximum of Months | 375.50 | 23.99 | 717.33 | 23.96 | 7.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 176.50 | 23.13 | 207.67 | 23.60 | 0.00 | 23.60 |
February | 130.83 | 23.20 | 201.33 | 23.68 | 0.00 | 23.68 |
March | 104.83 | 23.27 | 297.00 | 23.80 | 0.00 | 23.80 |
April | 5.17 | 23.24 | 437.00 | 23.98 | 0.00 | 23.98 |
May | 0.50 | 23.12 | 628.33 | 23.98 | 0.00 | 23.98 |
June | 7.17 | 24.00 | 704.00 | 23.98 | 7.17 | 23.98 |
July | 0.00 | 0.00 | 741.67 | 23.98 | 0.00 | 23.98 |
August | 0.00 | 0.00 | 740.50 | 23.97 | 0.00 | 23.97 |
September | 0.00 | 0.00 | 671.50 | 23.96 | 0.00 | 23.96 |
October | 14.50 | 23.20 | 503.50 | 23.96 | 0.00 | 23.96 |
November | 115.83 | 23.17 | 297.17 | 23.76 | 0.00 | 23.76 |
December | 215.50 | 23.12 | 157.83 | 23.49 | 0.00 | 23.49 |
Annual Sum or Average | 770.83 | 23.18 | 5587.50 | 23.88 | 7.17 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 157.83 | 23.49 | 0.00 | 23.49 |
Maximum of Months | 215.50 | 24.00 | 741.67 | 23.98 | 7.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 509.17 | 23.96 | 685.33 | 23.91 | 500.50 | 23.93 |
February | 461.33 | 23.98 | 614.17 | 23.92 | 459.00 | 23.94 |
March | 515.50 | 23.99 | 707.00 | 23.91 | 515.50 | 23.93 |
April | 510.83 | 23.99 | 709.00 | 23.91 | 510.83 | 23.93 |
May | 535.33 | 23.99 | 742.50 | 23.91 | 535.33 | 23.94 |
June | 532.17 | 23.99 | 719.83 | 23.94 | 532.17 | 23.95 |
July | 554.33 | 23.99 | 744.00 | 23.94 | 554.33 | 23.96 |
August | 549.50 | 23.99 | 744.00 | 23.94 | 549.50 | 23.96 |
September | 516.33 | 23.99 | 720.00 | 23.93 | 516.33 | 23.95 |
October | 525.83 | 23.99 | 739.83 | 23.90 | 525.83 | 23.93 |
November | 497.00 | 23.99 | 680.83 | 23.91 | 496.50 | 23.93 |
December | 497.33 | 23.98 | 669.33 | 23.92 | 493.83 | 23.94 |
Annual Sum or Average | 6204.67 | 23.99 | 8475.83 | 23.92 | 6189.67 | 23.94 |
Minimum of Months | 461.33 | 23.96 | 614.17 | 23.90 | 459.00 | 23.93 |
Maximum of Months | 554.33 | 23.99 | 744.00 | 23.94 | 554.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 43.83 | 21.02 | 43.83 | 21.02 |
February | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
May | 741.33 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
June | 698.00 | 22.26 | 4.00 | 22.27 | 0.00 | 22.27 |
July | 681.17 | 22.45 | 11.50 | 22.47 | 0.00 | 22.47 |
August | 710.33 | 22.50 | 2.00 | 22.50 | 0.00 | 22.50 |
September | 709.50 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.00 | 16.50 | 21.00 | 16.50 | 21.00 |
Annual Sum or Average | 8628.33 | 21.58 | 77.83 | 21.58 | 60.33 | 21.58 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.50 | 43.83 | 22.50 | 43.83 | 22.50 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.17502 | 34.62822 | 0.08991 | 5.29764 |
February | 672.00000 | 23.00380 | 35.97531 | 0.05477 | 5.17810 |
March | 744.00000 | 22.76470 | 35.57541 | -0.0091 | 5.13363 |
April | 720.00000 | 22.76898 | 35.14789 | -0.0091 | 5.16559 |
May | 744.00000 | 22.76527 | 40.59941 | -1.0107 | 26.76697 |
June | 720.00000 | 22.87845 | 47.92908 | -0.9206 | 23.09511 |
July | 744.00000 | 23.11701 | 49.47603 | -0.8221 | 19.49046 |
August | 744.00000 | 23.25606 | 49.47551 | -0.7715 | 17.74940 |
September | 720.00000 | 23.50294 | 44.81142 | -0.7112 | 15.85863 |
October | 744.00000 | 23.60131 | 40.19966 | 0.24149 | 6.31263 |
November | 720.00000 | 23.61766 | 36.75219 | 0.22147 | 6.12430 |
December | 744.00000 | 23.47336 | 33.79701 | 0.16195 | 5.65968 |
Annual Sum or Average | 8760.00000 | 23.16132 | 40.39127 | -0.2925 | 11.86580 |
Minimum of Months | 672.00000 | 22.76470 | 33.79701 | -1.0107 | 5.13363 |
Maximum of Months | 744.00000 | 23.61766 | 49.47603 | 0.24149 | 26.76697 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10738 | 36.40176 | -0.4283 | 9.40592 |
February | 672.00000 | 21.15926 | 37.50819 | -0.3865 | 8.86024 |
March | 744.00000 | 21.01688 | 36.85101 | -0.4395 | 9.15266 |
April | 720.00000 | 21.47730 | 35.65330 | -0.2240 | 7.51274 |
May | 744.00000 | 21.34174 | 41.82377 | -1.3562 | 44.39746 |
June | 720.00000 | 21.41639 | 49.95777 | -1.2418 | 38.67660 |
July | 744.00000 | 21.65107 | 51.66622 | -1.1288 | 34.00075 |
August | 744.00000 | 21.84804 | 51.51453 | -1.0442 | 30.99670 |
September | 720.00000 | 21.86222 | 47.02225 | -1.0749 | 33.27556 |
October | 744.00000 | 21.31931 | 43.57044 | -0.2614 | 7.63191 |
November | 720.00000 | 21.09678 | 39.96598 | -0.3975 | 8.73597 |
December | 744.00000 | 21.04390 | 36.15737 | -0.4874 | 10.25862 |
Annual Sum or Average | 8760.00000 | 21.36224 | 42.37191 | -0.7082 | 20.31583 |
Minimum of Months | 672.00000 | 21.01688 | 35.65330 | -1.3562 | 7.51274 |
Maximum of Months | 744.00000 | 21.86222 | 51.66622 | -0.2240 | 44.39746 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.76455 | 37.89499 | -0.2186 | 6.31674 |
February | 672.00000 | 21.84889 | 38.90580 | -0.1894 | 5.99790 |
March | 744.00000 | 21.82739 | 38.08174 | -0.2003 | 6.14430 |
April | 720.00000 | 22.56039 | 36.38948 | -0.0143 | 5.45341 |
May | 744.00000 | 22.60496 | 41.84250 | -1.0035 | 26.96600 |
June | 720.00000 | 22.89111 | 48.86491 | -0.8513 | 20.92527 |
July | 744.00000 | 23.04986 | 50.57533 | -0.7794 | 18.59108 |
August | 744.00000 | 23.16312 | 50.70982 | -0.7375 | 16.91529 |
September | 720.00000 | 23.04328 | 46.88439 | -0.8069 | 19.37671 |
October | 744.00000 | 22.34824 | 43.93408 | -0.0263 | 5.39315 |
November | 720.00000 | 21.90802 | 41.00074 | -0.1623 | 5.84456 |
December | 744.00000 | 21.57037 | 37.90765 | -0.2721 | 6.79228 |
Annual Sum or Average | 8760.00000 | 22.38366 | 42.77501 | -0.4403 | 12.10034 |
Minimum of Months | 672.00000 | 21.57037 | 36.38948 | -1.0035 | 5.39315 |
Maximum of Months | 744.00000 | 23.16312 | 50.70982 | -0.0143 | 26.96600 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.96334 | 31.16260 | 0.63072 | 15.95959 |
February | 672.00000 | 22.96269 | 32.24045 | 0.64131 | 16.23044 |
March | 744.00000 | 22.96489 | 31.36633 | 0.64386 | 16.37625 |
April | 720.00000 | 23.00684 | 30.93378 | 0.68613 | 17.48128 |
May | 744.00000 | 23.01415 | 36.27200 | -0.0051 | 10.20577 |
June | 720.00000 | 23.03135 | 43.71347 | 0.07314 | 10.34934 |
July | 744.00000 | 23.04656 | 45.86866 | 0.10016 | 10.27471 |
August | 744.00000 | 23.04109 | 46.22040 | 0.10859 | 10.38736 |
September | 720.00000 | 23.04962 | 42.09649 | 0.06840 | 10.20583 |
October | 744.00000 | 23.02084 | 37.69146 | 0.71641 | 18.31400 |
November | 720.00000 | 22.99261 | 34.17893 | 0.66577 | 16.91965 |
December | 744.00000 | 22.93895 | 30.89901 | 0.61373 | 15.52805 |
Annual Sum or Average | 8760.00000 | 23.00288 | 36.91591 | 0.41046 | 14.00425 |
Minimum of Months | 672.00000 | 22.93895 | 30.89901 | -0.0051 | 10.20577 |
Maximum of Months | 744.00000 | 23.04962 | 46.22040 | 0.71641 | 18.31400 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51081 | 40.59434 | -0.2335 | 6.86332 |
February | 672.00000 | 21.62356 | 41.57065 | -0.1818 | 6.50517 |
March | 744.00000 | 21.43823 | 41.01288 | -0.2465 | 6.55580 |
April | 720.00000 | 22.28237 | 39.17832 | 0.03879 | 6.19123 |
May | 744.00000 | 22.15029 | 45.06777 | -1.0050 | 27.79568 |
June | 720.00000 | 22.34826 | 52.55192 | -0.8637 | 21.94621 |
July | 744.00000 | 22.57622 | 54.17330 | -0.7525 | 18.56983 |
August | 744.00000 | 22.84562 | 53.89820 | -0.6414 | 15.40228 |
September | 720.00000 | 22.83327 | 49.68142 | -0.6715 | 17.22349 |
October | 744.00000 | 22.02461 | 46.95588 | -0.0134 | 6.21110 |
November | 720.00000 | 21.57862 | 43.90603 | -0.1890 | 6.36607 |
December | 744.00000 | 21.32243 | 40.53511 | -0.3144 | 7.50428 |
Annual Sum or Average | 8760.00000 | 22.04562 | 45.78869 | -0.4248 | 12.30117 |
Minimum of Months | 672.00000 | 21.32243 | 39.17832 | -1.0050 | 6.19123 |
Maximum of Months | 744.00000 | 22.84562 | 54.17330 | 0.03879 | 27.79568 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.12325 | 39.81748 | -0.1005 | 5.71379 |
February | 672.00000 | 22.20948 | 40.80039 | -0.0692 | 5.49937 |
March | 744.00000 | 22.14857 | 40.06818 | -0.0906 | 5.66486 |
April | 720.00000 | 22.82277 | 38.53196 | 0.09344 | 5.64421 |
May | 744.00000 | 22.82131 | 43.99171 | -0.8745 | 21.91729 |
June | 720.00000 | 23.05745 | 51.06226 | -0.7334 | 16.99903 |
July | 744.00000 | 23.19984 | 52.77896 | -0.6631 | 14.95870 |
August | 744.00000 | 23.33107 | 52.84054 | -0.6119 | 13.31550 |
September | 720.00000 | 23.28600 | 48.87930 | -0.6573 | 14.69395 |
October | 744.00000 | 22.65759 | 45.84461 | 0.08922 | 5.67150 |
November | 720.00000 | 22.25226 | 42.89522 | -0.0455 | 5.53020 |
December | 744.00000 | 21.93485 | 39.77203 | -0.1562 | 5.98099 |
Annual Sum or Average | 8760.00000 | 22.65515 | 44.79998 | -0.3201 | 10.16413 |
Minimum of Months | 672.00000 | 21.93485 | 38.53196 | -0.8745 | 5.49937 |
Maximum of Months | 744.00000 | 23.33107 | 52.84054 | 0.09344 | 21.91729 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89386 | 44.63256 | -0.5176 | 11.10437 |
February | 672.00000 | 21.03024 | 45.29115 | -0.4608 | 9.96282 |
March | 744.00000 | 20.97737 | 45.04886 | -0.4741 | 9.92691 |
April | 720.00000 | 21.53446 | 43.71250 | -0.2390 | 7.20871 |
May | 744.00000 | 21.53707 | 48.68649 | -1.3339 | 43.12679 |
June | 720.00000 | 21.65274 | 52.64597 | -1.2138 | 37.34115 |
July | 744.00000 | 21.67701 | 52.77179 | -1.1775 | 35.71643 |
August | 744.00000 | 21.68395 | 53.14485 | -1.1757 | 35.65576 |
September | 720.00000 | 21.64280 | 52.09018 | -1.2394 | 38.69621 |
October | 744.00000 | 21.24731 | 52.12482 | -0.3217 | 7.83043 |
November | 720.00000 | 20.94973 | 48.91321 | -0.4708 | 10.03920 |
December | 744.00000 | 20.70136 | 44.67628 | -0.5923 | 12.74129 |
Annual Sum or Average | 8760.00000 | 21.29451 | 48.66483 | -0.7703 | 21.68953 |
Minimum of Months | 672.00000 | 20.70136 | 43.71250 | -1.3339 | 7.20871 |
Maximum of Months | 744.00000 | 21.68395 | 53.14485 | -0.2390 | 43.12679 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68897 | 45.16177 | -0.5863 | 12.61633 |
February | 672.00000 | 20.79876 | 45.88371 | -0.5383 | 11.33863 |
March | 744.00000 | 20.87481 | 45.30124 | -0.5085 | 10.59480 |
April | 720.00000 | 21.48570 | 43.91671 | -0.2811 | 7.79872 |
May | 744.00000 | 21.64270 | 48.61502 | -1.3286 | 44.08345 |
June | 720.00000 | 21.99089 | 52.10629 | -1.1316 | 35.84012 |
July | 744.00000 | 22.38688 | 51.64108 | -0.9935 | 31.91943 |
August | 744.00000 | 22.34299 | 52.70265 | -1.0194 | 31.29527 |
September | 720.00000 | 21.84270 | 52.85251 | -1.2330 | 39.24202 |
October | 744.00000 | 21.08643 | 52.64406 | -0.3846 | 8.44985 |
November | 720.00000 | 20.76692 | 49.40351 | -0.5304 | 11.18527 |
December | 744.00000 | 20.56600 | 45.03353 | -0.6360 | 13.90083 |
Annual Sum or Average | 8760.00000 | 21.37590 | 48.78683 | -0.7658 | 21.58390 |
Minimum of Months | 672.00000 | 20.56600 | 43.91671 | -1.3286 | 7.79872 |
Maximum of Months | 744.00000 | 22.38688 | 52.85251 | -0.2811 | 44.08345 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00820 | 43.46744 | -0.4632 | 9.66602 |
February | 672.00000 | 21.05248 | 44.39581 | -0.4427 | 9.13929 |
March | 744.00000 | 21.17208 | 43.54249 | -0.3983 | 8.37325 |
April | 720.00000 | 21.41499 | 42.92207 | -0.3172 | 7.33835 |
May | 744.00000 | 21.49205 | 47.52025 | -1.4207 | 46.87109 |
June | 720.00000 | 21.68969 | 51.12685 | -1.3054 | 41.19390 |
July | 744.00000 | 21.86366 | 51.88855 | -1.2370 | 37.95915 |
August | 744.00000 | 21.84713 | 52.37384 | -1.2499 | 38.39413 |
September | 720.00000 | 21.56307 | 51.64182 | -1.3734 | 44.42823 |
October | 744.00000 | 21.24771 | 50.55106 | -0.3294 | 7.32514 |
November | 720.00000 | 21.08501 | 47.41688 | -0.4100 | 8.60594 |
December | 744.00000 | 20.95906 | 43.17784 | -0.4848 | 10.01960 |
Annual Sum or Average | 8760.00000 | 21.36805 | 47.51911 | -0.7881 | 22.51987 |
Minimum of Months | 672.00000 | 20.95906 | 42.92207 | -1.4207 | 7.32514 |
Maximum of Months | 744.00000 | 21.86366 | 52.37384 | -0.3172 | 46.87109 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88970 | 44.63365 | -0.5175 | 11.07769 |
February | 672.00000 | 21.02255 | 45.29289 | -0.4673 | 9.96610 |
March | 744.00000 | 21.00670 | 44.95621 | -0.4682 | 9.82682 |
April | 720.00000 | 21.63570 | 43.44664 | -0.2050 | 7.03344 |
May | 744.00000 | 21.61791 | 48.13194 | -1.3065 | 41.86013 |
June | 720.00000 | 21.68746 | 52.25091 | -1.2122 | 37.30450 |
July | 744.00000 | 21.71451 | 52.36047 | -1.1736 | 35.55647 |
August | 744.00000 | 21.71219 | 52.46224 | -1.1631 | 35.14171 |
September | 720.00000 | 21.69619 | 51.38872 | -1.2091 | 37.34833 |
October | 744.00000 | 21.28744 | 51.79846 | -0.3112 | 7.74675 |
November | 720.00000 | 20.94456 | 48.90844 | -0.4713 | 9.99803 |
December | 744.00000 | 20.71749 | 44.61063 | -0.5840 | 12.54500 |
Annual Sum or Average | 8760.00000 | 21.32842 | 48.37152 | -0.7596 | 21.35882 |
Minimum of Months | 672.00000 | 20.71749 | 43.44664 | -1.3065 | 7.03344 |
Maximum of Months | 744.00000 | 21.71451 | 52.46224 | -0.2050 | 41.86013 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68873 | 45.15238 | -0.5853 | 12.58997 |
February | 672.00000 | 20.77429 | 45.93220 | -0.5485 | 11.53287 |
March | 744.00000 | 20.90702 | 45.19596 | -0.5019 | 10.44754 |
April | 720.00000 | 21.61241 | 43.53172 | -0.2418 | 7.24422 |
May | 744.00000 | 21.68077 | 48.17235 | -1.3140 | 42.29078 |
June | 720.00000 | 21.91544 | 52.16238 | -1.1618 | 35.62862 |
July | 744.00000 | 22.13717 | 52.29374 | -1.0703 | 31.81047 |
August | 744.00000 | 22.16954 | 52.72765 | -1.0632 | 31.05425 |
September | 720.00000 | 21.86855 | 52.05341 | -1.2115 | 37.39772 |
October | 744.00000 | 21.14468 | 52.36931 | -0.3696 | 8.23144 |
November | 720.00000 | 20.75968 | 49.41108 | -0.5312 | 11.18868 |
December | 744.00000 | 20.58350 | 44.96430 | -0.6275 | 13.68278 |
Annual Sum or Average | 8760.00000 | 21.35621 | 48.67947 | -0.7705 | 21.15075 |
Minimum of Months | 672.00000 | 20.58350 | 43.53172 | -1.3140 | 7.24422 |
Maximum of Months | 744.00000 | 22.16954 | 52.72765 | -0.2418 | 42.29078 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78703 | 45.71190 | -0.5733 | 12.48815 |
February | 672.00000 | 20.92952 | 46.34634 | -0.5103 | 11.09762 |
March | 744.00000 | 20.89182 | 46.12764 | -0.5171 | 10.90762 |
April | 720.00000 | 21.51879 | 44.38143 | -0.2506 | 7.60185 |
May | 744.00000 | 21.51780 | 49.49327 | -1.3510 | 44.23922 |
June | 720.00000 | 21.64334 | 53.45910 | -1.2181 | 37.82460 |
July | 744.00000 | 21.67036 | 53.63230 | -1.1771 | 35.98162 |
August | 744.00000 | 21.67262 | 54.12644 | -1.1810 | 36.17915 |
September | 720.00000 | 21.62157 | 53.20162 | -1.2600 | 39.95501 |
October | 744.00000 | 21.17290 | 53.43149 | -0.3586 | 8.50806 |
November | 720.00000 | 20.84263 | 50.19378 | -0.5213 | 11.19972 |
December | 744.00000 | 20.60968 | 45.71407 | -0.6476 | 14.25823 |
Annual Sum or Average | 8760.00000 | 21.24056 | 49.67158 | -0.7994 | 22.59614 |
Minimum of Months | 672.00000 | 20.60968 | 44.38143 | -1.3510 | 7.60185 |
Maximum of Months | 744.00000 | 21.67262 | 54.12644 | -0.2506 | 44.23922 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59486 | 46.26002 | -0.6410 | 14.12036 |
February | 672.00000 | 20.68611 | 47.00698 | -0.5923 | 12.71799 |
March | 744.00000 | 20.78156 | 46.41652 | -0.5539 | 11.69273 |
April | 720.00000 | 21.49601 | 44.57224 | -0.2894 | 8.34691 |
May | 744.00000 | 21.66440 | 49.32864 | -1.3339 | 45.28701 |
June | 720.00000 | 22.04618 | 52.67157 | -1.1135 | 36.37443 |
July | 744.00000 | 22.49966 | 51.92450 | -0.9521 | 32.43244 |
August | 744.00000 | 22.43136 | 53.25400 | -0.9897 | 31.60067 |
September | 720.00000 | 21.86959 | 53.85345 | -1.2404 | 40.43319 |
October | 744.00000 | 20.99611 | 54.05360 | -0.4272 | 9.28252 |
November | 720.00000 | 20.65426 | 50.73354 | -0.5833 | 12.53607 |
December | 744.00000 | 20.49946 | 46.03006 | -0.6876 | 15.42024 |
Annual Sum or Average | 8760.00000 | 21.35529 | 49.68879 | -0.7850 | 22.58010 |
Minimum of Months | 672.00000 | 20.49946 | 44.57224 | -1.3339 | 8.34691 |
Maximum of Months | 744.00000 | 22.49966 | 54.05360 | -0.2894 | 45.28701 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.18590 | 45.16041 | -0.4107 | 9.58616 |
February | 672.00000 | 21.28400 | 45.88379 | -0.3653 | 8.77171 |
March | 744.00000 | 21.18326 | 45.63999 | -0.4119 | 8.97960 |
April | 720.00000 | 21.62800 | 44.56297 | -0.2022 | 7.19871 |
May | 744.00000 | 21.58871 | 49.27264 | -1.3380 | 43.57411 |
June | 720.00000 | 21.65510 | 53.22528 | -1.2557 | 39.46921 |
July | 744.00000 | 21.67961 | 53.37805 | -1.2170 | 37.72299 |
August | 744.00000 | 21.68046 | 52.93921 | -1.1939 | 36.81703 |
September | 720.00000 | 21.68076 | 51.20406 | -1.2093 | 37.77400 |
October | 744.00000 | 21.40966 | 51.88700 | -0.2572 | 7.41475 |
November | 720.00000 | 21.20761 | 49.21330 | -0.3781 | 8.80783 |
December | 744.00000 | 20.98860 | 45.24935 | -0.4981 | 11.02003 |
Annual Sum or Average | 8760.00000 | 21.43095 | 48.98696 | -0.7307 | 21.51138 |
Minimum of Months | 672.00000 | 20.98860 | 44.56297 | -1.3380 | 7.19871 |
Maximum of Months | 744.00000 | 21.68076 | 53.37805 | -0.2022 | 43.57411 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54153 | 39.86414 | 0.25732 | 6.87296 |
February | 672.00000 | 23.59014 | 40.74443 | 0.28085 | 6.96022 |
March | 744.00000 | 23.66926 | 39.59109 | 0.30756 | 7.26920 |
April | 720.00000 | 23.83239 | 38.52432 | 0.37697 | 8.13886 |
May | 744.00000 | 23.86478 | 43.37013 | -0.4549 | 9.54944 |
June | 720.00000 | 23.92185 | 49.90104 | -0.3525 | 7.75093 |
July | 744.00000 | 23.94535 | 51.81039 | -0.3192 | 7.24988 |
August | 744.00000 | 23.92517 | 52.23847 | -0.3306 | 7.38974 |
September | 720.00000 | 23.87897 | 48.81842 | -0.4029 | 8.59232 |
October | 744.00000 | 23.73010 | 45.41203 | 0.37578 | 8.15795 |
November | 720.00000 | 23.60871 | 42.54000 | 0.30421 | 7.30406 |
December | 744.00000 | 23.50699 | 39.63268 | 0.24172 | 6.68595 |
Annual Sum or Average | 8760.00000 | 23.75194 | 44.39409 | 0.02204 | 7.66274 |
Minimum of Months | 672.00000 | 23.50699 | 38.52432 | -0.4549 | 6.68595 |
Maximum of Months | 744.00000 | 23.94535 | 52.23847 | 0.37697 | 9.54944 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73274 | 38.63770 | 0.34426 | 7.79239 |
February | 672.00000 | 23.77902 | 39.52686 | 0.36687 | 7.98037 |
March | 744.00000 | 23.83277 | 38.39905 | 0.38816 | 8.30304 |
April | 720.00000 | 23.93231 | 37.53635 | 0.43870 | 9.11468 |
May | 744.00000 | 23.94431 | 42.40848 | -0.3731 | 8.02357 |
June | 720.00000 | 23.97271 | 49.08006 | -0.2850 | 6.79935 |
July | 744.00000 | 23.98338 | 51.05418 | -0.2582 | 6.48425 |
August | 744.00000 | 23.97089 | 51.46159 | -0.2676 | 6.57292 |
September | 720.00000 | 23.94801 | 47.91375 | -0.3286 | 7.39134 |
October | 744.00000 | 23.86581 | 44.24840 | 0.44773 | 9.29765 |
November | 720.00000 | 23.78451 | 41.31500 | 0.38725 | 8.35122 |
December | 744.00000 | 23.71011 | 38.40504 | 0.33163 | 7.57858 |
Annual Sum or Average | 8760.00000 | 23.87172 | 43.35659 | 0.09765 | 7.80486 |
Minimum of Months | 672.00000 | 23.71011 | 37.53635 | -0.3731 | 6.48425 |
Maximum of Months | 744.00000 | 23.98338 | 51.46159 | 0.44773 | 9.29765 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76950 | 36.95625 | 0.98365 | 27.62807 |
February | 672.00000 | 23.76573 | 37.87154 | 0.99813 | 28.28446 |
March | 744.00000 | 23.79559 | 36.96486 | 1.01326 | 28.72746 |
April | 720.00000 | 23.83777 | 36.42498 | 1.08663 | 32.01848 |
May | 744.00000 | 23.85418 | 41.34209 | 0.54962 | 16.20701 |
June | 720.00000 | 23.89531 | 48.15553 | 0.64699 | 18.54937 |
July | 744.00000 | 23.90701 | 50.17365 | 0.68190 | 19.46902 |
August | 744.00000 | 23.91139 | 50.47547 | 0.68347 | 19.50496 |
September | 720.00000 | 23.88428 | 46.74088 | 0.61652 | 17.91578 |
October | 744.00000 | 23.82851 | 42.77398 | 1.08343 | 31.70889 |
November | 720.00000 | 23.79033 | 39.72664 | 1.01773 | 28.92978 |
December | 744.00000 | 23.75547 | 36.74269 | 0.96385 | 26.79463 |
Annual Sum or Average | 8760.00000 | 23.83327 | 42.05518 | 0.85950 | 24.61810 |
Minimum of Months | 672.00000 | 23.75547 | 36.42498 | 0.54962 | 16.20701 |
Maximum of Months | 744.00000 | 23.91139 | 50.47547 | 1.08663 | 32.01848 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00837 | 35.91153 | -0.4514 | 9.30793 |
February | 672.00000 | 21.00522 | 37.09543 | -0.4420 | 9.09466 |
March | 744.00000 | 21.02101 | 36.25686 | -0.4376 | 9.02622 |
April | 720.00000 | 21.47549 | 35.01180 | -0.3188 | 7.34239 |
May | 744.00000 | 21.66841 | 40.53786 | -1.3742 | 44.30344 |
June | 720.00000 | 22.23002 | 47.24717 | -1.1375 | 32.51014 |
July | 744.00000 | 22.49571 | 48.79060 | -1.0348 | 28.00260 |
August | 744.00000 | 22.55640 | 49.02786 | -1.0135 | 26.79688 |
September | 720.00000 | 22.25451 | 45.56599 | -1.1397 | 32.58863 |
October | 744.00000 | 21.36785 | 42.88809 | -0.3008 | 7.02532 |
November | 720.00000 | 21.03491 | 39.50036 | -0.4140 | 8.62362 |
December | 744.00000 | 21.00038 | 35.60132 | -0.4622 | 9.48188 |
Annual Sum or Average | 8760.00000 | 21.59632 | 41.14485 | -0.7123 | 18.73662 |
Minimum of Months | 672.00000 | 21.00038 | 35.01180 | -1.3742 | 7.02532 |
Maximum of Months | 744.00000 | 22.55640 | 49.02786 | -0.3008 | 44.30344 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00836 | 39.09401 | -0.4428 | 9.13349 |
February | 672.00000 | 21.01381 | 40.27121 | -0.4297 | 8.86649 |
March | 744.00000 | 21.01888 | 39.39655 | -0.4325 | 8.92755 |
April | 720.00000 | 21.61274 | 37.84817 | -0.2799 | 6.89463 |
May | 744.00000 | 21.81731 | 43.27270 | -1.3231 | 41.65483 |
June | 720.00000 | 22.24547 | 50.21980 | -1.1296 | 32.11219 |
July | 744.00000 | 22.48660 | 51.82017 | -1.0338 | 27.98360 |
August | 744.00000 | 22.57442 | 52.01457 | -1.0024 | 26.33995 |
September | 720.00000 | 22.30401 | 48.44079 | -1.1194 | 31.66836 |
October | 744.00000 | 21.36253 | 45.92083 | -0.3001 | 7.10346 |
November | 720.00000 | 21.01504 | 42.61463 | -0.4175 | 8.66641 |
December | 744.00000 | 21.00066 | 38.77697 | -0.4559 | 9.35954 |
Annual Sum or Average | 8760.00000 | 21.62476 | 44.16566 | -0.6990 | 18.28516 |
Minimum of Months | 672.00000 | 21.00066 | 37.84817 | -1.3231 | 6.89463 |
Maximum of Months | 744.00000 | 22.57442 | 52.01457 | -0.2799 | 41.65483 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01751 | 36.92640 | -0.4356 | 9.02816 |
February | 672.00000 | 21.03556 | 38.09411 | -0.4158 | 8.64680 |
March | 744.00000 | 21.02349 | 37.20833 | -0.4171 | 8.66163 |
April | 720.00000 | 21.64978 | 35.60138 | -0.2444 | 6.73560 |
May | 744.00000 | 21.77779 | 41.11862 | -1.2889 | 40.24364 |
June | 720.00000 | 22.29414 | 47.78385 | -1.0592 | 29.38032 |
July | 744.00000 | 22.54287 | 49.36253 | -0.9584 | 25.30406 |
August | 744.00000 | 22.54521 | 49.78022 | -0.9562 | 24.89277 |
September | 720.00000 | 22.14598 | 46.53077 | -1.1216 | 32.19298 |
October | 744.00000 | 21.25293 | 43.98855 | -0.3055 | 7.13306 |
November | 720.00000 | 21.02274 | 40.44567 | -0.4037 | 8.44359 |
December | 744.00000 | 21.00355 | 36.61797 | -0.4513 | 9.27678 |
Annual Sum or Average | 8760.00000 | 21.61216 | 41.97963 | -0.6732 | 17.54912 |
Minimum of Months | 672.00000 | 21.00355 | 35.60138 | -1.2889 | 6.73560 |
Maximum of Months | 744.00000 | 22.54521 | 49.78022 | -0.2444 | 40.24364 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06898 | 35.38112 | -0.4319 | 8.97280 |
February | 672.00000 | 21.06813 | 36.56733 | -0.4227 | 8.76487 |
March | 744.00000 | 21.12388 | 35.64738 | -0.4107 | 8.58209 |
April | 720.00000 | 21.72591 | 34.11643 | -0.2650 | 6.71945 |
May | 744.00000 | 21.93636 | 39.52058 | -1.2923 | 40.11235 |
June | 720.00000 | 22.48883 | 46.14332 | -1.0580 | 28.95358 |
July | 744.00000 | 22.75170 | 47.67032 | -0.9559 | 24.76585 |
August | 744.00000 | 22.81458 | 47.89494 | -0.9338 | 23.58388 |
September | 720.00000 | 22.52086 | 44.47106 | -1.0580 | 28.91191 |
October | 744.00000 | 21.62736 | 41.85972 | -0.2440 | 6.42053 |
November | 720.00000 | 21.16280 | 38.80919 | -0.3819 | 8.13113 |
December | 744.00000 | 21.03408 | 35.13624 | -0.4469 | 9.20147 |
Annual Sum or Average | 8760.00000 | 21.78062 | 40.29179 | -0.6600 | 16.98002 |
Minimum of Months | 672.00000 | 21.03408 | 34.11643 | -1.2923 | 6.42053 |
Maximum of Months | 744.00000 | 22.81458 | 47.89494 | -0.2440 | 40.11235 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.180989E+10 | 15106.01 | 21-JAN-16:01 | 208.54 | 0.563945E+10 | 0.00 | 0.744934E+10 | 0.87 | 3.12 | 01-JAN-11:00 | 0.00 | 0.00 |
February | 0.183417E+10 | 15362.14 | 19-FEB-16:02 | 214.74 | 0.571515E+10 | 0.00 | 0.754932E+10 | 1.00 | 3.12 | 01-FEB-16:06 | 0.00 | 0.00 |
March | 0.218411E+10 | 21553.81 | 20-MAR-18:03 | 259.46 | 0.680541E+10 | 0.00 | 0.898953E+10 | 1.09 | 3.12 | 01-MAR-07:40 | 0.00 | 0.00 |
April | 0.229074E+11 | 93436.85 | 30-APR-18:03 | 601.42 | 0.715348E+11 | 0.00 | 0.944421E+11 | 2.60 | 3.93 | 28-APR-15:03 | 0.00 | 0.00 |
May | 0.249022E+11 | 90529.28 | 22-MAY-15:03 | 671.74 | 0.768093E+11 | 0.00 | 0.101712E+12 | 2.80 | 3.88 | 23-MAY-15:03 | 0.00 | 0.00 |
June | 0.448261E+11 | 114288.71 | 12-JUN-18:03 | 714.84 | 0.140564E+12 | 0.00 | 0.185390E+12 | 3.07 | 4.18 | 25-JUN-18:03 | 0.00 | 0.00 |
July | 0.633184E+11 | 125433.39 | 22-JUL-18:03 | 743.50 | 0.195362E+12 | 0.00 | 0.258680E+12 | 3.06 | 3.97 | 24-JUL-15:03 | 0.00 | 0.00 |
August | 0.694497E+11 | 108032.37 | 14-AUG-18:03 | 744.00 | 0.211773E+12 | 0.00 | 0.281223E+12 | 3.04 | 3.99 | 18-AUG-15:03 | 0.00 | 0.00 |
September | 0.466611E+11 | 92269.87 | 13-SEP-15:03 | 713.61 | 0.145292E+12 | 0.00 | 0.191954E+12 | 3.06 | 3.98 | 12-SEP-15:03 | 0.00 | 0.00 |
October | 0.111083E+11 | 63866.58 | 07-OCT-15:03 | 463.88 | 0.341795E+11 | 0.00 | 0.452878E+11 | 1.94 | 3.85 | 07-OCT-15:03 | 0.00 | 0.00 |
November | 0.203308E+10 | 21982.71 | 10-NOV-16:01 | 231.79 | 0.633239E+10 | 0.00 | 0.836547E+10 | 1.00 | 3.12 | 01-NOV-05:03 | 0.00 | 0.00 |
December | 0.395745E+09 | 10808.97 | 10-DEC-09:02 | 79.69 | 0.123311E+10 | 0.00 | 0.162886E+10 | 0.33 | 3.12 | 01-DEC-21:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.291430E+12 | 5647.22 | 0.901240E+12 | 0.00 | 0.119267E+13 | 1.99 | 0.00 | 0.00 | ||||
Minimum of Months | 0.395745E+09 | 10808.97 | 79.69 | 0.123311E+10 | 0.00 | 0.162886E+10 | 0.33 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.694497E+11 | 125433.39 | 744.00 | 0.211773E+12 | 0.00 | 0.281223E+12 | 3.07 | 4.18 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.998403E+11 | 0.00 | 744.00 | 167466.69 | 30-JAN-16:02 | 0.00 | 39.43 | 60.00 | 0.40 | 0.00 | 0.10 | 0.44 | 30-JAN-16:02 |
February | 0.638991E+11 | 0.00 | 672.00 | 156596.16 | 06-FEB-16:02 | 0.00 | 40.34 | 60.00 | 0.30 | 0.00 | 0.07 | 0.41 | 06-FEB-16:02 |
March | 0.924881E+11 | 0.00 | 744.00 | 148249.05 | 28-MAR-08:04 | 0.00 | 39.51 | 60.00 | 0.36 | 0.00 | 0.09 | 0.39 | 28-MAR-08:04 |
April | 0.832061E+11 | 0.00 | 637.43 | 131239.11 | 07-APR-08:05 | 0.00 | 36.03 | 56.32 | 0.29 | 0.00 | 0.08 | 0.34 | 07-APR-08:05 |
May | 0.105042E+12 | 0.00 | 653.64 | 134196.82 | 05-MAY-08:05 | 0.00 | 33.05 | 55.84 | 0.34 | 0.00 | 0.10 | 0.35 | 05-MAY-08:05 |
June | 0.757961E+11 | 0.00 | 513.99 | 112975.55 | 07-JUN-10:20 | 0.00 | 27.50 | 50.00 | 0.23 | 0.00 | 0.08 | 0.29 | 07-JUN-10:20 |
July | 0.513582E+11 | 0.00 | 409.16 | 102538.62 | 09-JUL-04:00 | 0.00 | 26.33 | 44.40 | 0.15 | 0.00 | 0.05 | 0.27 | 09-JUL-04:00 |
August | 0.382200E+11 | 0.00 | 363.22 | 103133.78 | 24-AUG-05:40 | 0.00 | 26.58 | 42.96 | 0.11 | 0.00 | 0.04 | 0.27 | 24-AUG-05:40 |
September | 0.741517E+11 | 0.00 | 460.92 | 120746.53 | 28-SEP-06:10 | 0.00 | 28.63 | 48.13 | 0.24 | 0.00 | 0.07 | 0.31 | 28-SEP-06:10 |
October | 0.120086E+12 | 0.00 | 713.49 | 175991.23 | 19-OCT-08:04 | 0.00 | 35.11 | 58.72 | 0.41 | 0.00 | 0.12 | 0.46 | 19-OCT-08:04 |
November | 0.124423E+12 | 0.00 | 720.00 | 169243.11 | 21-NOV-16:02 | 0.00 | 38.18 | 60.00 | 0.48 | 0.00 | 0.12 | 0.44 | 21-NOV-16:02 |
December | 0.897749E+11 | 0.00 | 744.00 | 178407.92 | 16-DEC-16:04 | 0.00 | 38.92 | 60.00 | 0.37 | 0.00 | 0.09 | 0.46 | 16-DEC-16:04 |
Annual Sum or Average | 0.101829E+13 | 0.00 | 7375.84 | 0.00 | 34.10 | 54.67 | 0.31 | 0.00 | 0.08 | ||||
Minimum of Months | 0.382200E+11 | 0.00 | 363.22 | 102538.62 | 0.00 | 26.33 | 42.96 | 0.11 | 0.00 | 0.04 | 0.27 | ||
Maximum of Months | 0.124423E+12 | 0.00 | 744.00 | 178407.92 | 0.00 | 40.34 | 60.00 | 0.48 | 0.00 | 0.12 | 0.46 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.151075E+11 | 0.00 | 65.83 | 0.150929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185786.96 | 30-APR-18:10 | 185786.96 | 30-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.152687E+11 | 0.00 | 82.50 | 0.152687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159744.49 | 22-MAY-15:12 | 159744.49 | 22-MAY-15:12 | 0.00 | 0.00 | 0.00 |
June | 0.489415E+11 | 0.00 | 224.94 | 0.466760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 334242.58 | 25-JUN-18:00 | 210009.60 | 12-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.845862E+11 | 0.00 | 372.79 | 0.835524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 234938.17 | 22-JUL-18:10 | 234938.17 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.984892E+11 | 0.00 | 433.50 | 0.974914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213064.67 | 14-AUG-18:10 | 213064.67 | 14-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.507150E+11 | 0.00 | 274.83 | 0.503602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160169.77 | 11-SEP-17:04 | 160169.77 | 11-SEP-17:04 | 0.00 | 0.00 | 0.00 |
October | 0.262849E+10 | 0.00 | 30.83 | 0.262849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71691.26 | 07-OCT-15:03 | 71691.26 | 07-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 49361593.28 | 0.00 | 1.00 | 49361593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28531.01 | 24-NOV-11:50 | 28531.01 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315786E+12 | 0.00 | 1486.24 | 0.311119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.984892E+11 | 0.00 | 433.50 | 0.974914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 334242.58 | 234938.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.871147E+09 | 0.00 | 37.50 | 0.871147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17043.06 | 30-APR-15:02 | 17043.06 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.908483E+09 | 0.00 | 48.17 | 0.908483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17029.10 | 22-MAY-15:02 | 17029.10 | 22-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.290719E+10 | 0.00 | 130.50 | 0.269885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 25-JUN-18:03 | 17887.72 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.528320E+10 | 0.00 | 236.67 | 0.509036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20042.47 | 23-JUL-15:53 | 19221.97 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.612254E+10 | 0.00 | 286.00 | 0.589875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19239.53 | 17-AUG-15:02 | 17960.43 | 14-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.309471E+10 | 0.00 | 152.83 | 0.300011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537.15 | 10-SEP-15:55 | 16368.41 | 13-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.156128E+09 | 0.00 | 16.67 | 0.156128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8578.33 | 07-OCT-15:06 | 8578.33 | 07-OCT-15:06 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193434E+11 | 0.00 | 908.33 | 0.186238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.612254E+10 | 0.00 | 286.00 | 0.589875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 19221.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 31099644.64 | 0.00 | 8.52 | 16752824.69 | 0.00 | 0.00 | 0.00 | 0.00 | 13229.26 | 25-JAN-16:01 | 13229.26 | 25-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.200575E+09 | 0.00 | 38.12 | 0.113022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16843.53 | 17-FEB-16:01 | 16843.53 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 96448244.64 | 0.00 | 21.93 | 61125021.97 | 0.00 | 0.00 | 0.00 | 0.00 | 16594.69 | 10-MAR-16:01 | 16594.69 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.262443E+10 | 0.00 | 350.00 | 0.167121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16842.87 | 12-APR-15:01 | 16842.87 | 12-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.323152E+10 | 0.00 | 406.55 | 0.187152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16843.16 | 11-MAY-18:01 | 16843.16 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.508679E+10 | 0.00 | 580.33 | 0.272243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16485.61 | 04-JUN-08:62 | 15195.25 | 22-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.652918E+10 | 0.00 | 618.85 | 0.354936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16342.85 | 29-JUL-15:01 | 15402.79 | 18-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.619403E+10 | 0.00 | 667.60 | 0.314326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17240.25 | 08-AUG-15:01 | 15390.88 | 15-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.436944E+10 | 0.00 | 539.19 | 0.225045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16702.68 | 16-SEP-15:02 | 15025.87 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.935147E+09 | 0.00 | 154.68 | 0.517523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16816.43 | 06-OCT-18:01 | 16816.43 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 42649195.18 | 0.00 | 12.73 | 21953869.56 | 0.00 | 0.00 | 0.00 | 0.00 | 13661.63 | 10-NOV-16:01 | 13661.63 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 289201.82 | 0.00 | 0.22 | 75695.80 | 0.00 | 0.00 | 0.00 | 0.00 | 758.16 | 24-DEC-09:06 | 397.55 | 26-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293416E+11 | 0.00 | 3398.73 | 0.159387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 289201.82 | 0.00 | 0.22 | 75695.80 | 0.00 | 0.00 | 0.00 | 0.00 | 758.16 | 397.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.652918E+10 | 0.00 | 667.60 | 0.354936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17240.25 | 16843.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4424494.79 | 0.00 | 1.65 | 2142390.44 | 0.00 | 0.00 | 0.00 | 0.00 | 11036.07 | 19-JAN-16:01 | 11036.07 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 48680686.66 | 0.00 | 14.07 | 24221515.42 | 0.00 | 0.00 | 0.00 | 0.00 | 14135.15 | 17-FEB-16:01 | 14135.15 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 48974623.32 | 0.00 | 12.88 | 28693281.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12055.21 | 10-MAR-16:01 | 12055.21 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.143075E+10 | 0.00 | 224.70 | 0.898904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15102.99 | 12-APR-15:01 | 15102.99 | 12-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.216052E+10 | 0.00 | 316.13 | 0.119516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15458.94 | 22-MAY-21:31 | 15407.18 | 11-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.382987E+10 | 0.00 | 495.86 | 0.197081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17656.44 | 26-JUN-21:01 | 15640.38 | 20-JUN-20:01 | 0.00 | 0.00 | 0.00 |
July | 0.425741E+10 | 0.00 | 470.07 | 0.213158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16877.90 | 24-JUL-20:01 | 15729.35 | 11-JUL-19:11 | 0.00 | 0.00 | 0.00 |
August | 0.328709E+10 | 0.00 | 458.17 | 0.141475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16216.55 | 11-AUG-19:11 | 15162.37 | 01-AUG-19:31 | 0.00 | 0.00 | 0.00 |
September | 0.187147E+10 | 0.00 | 360.19 | 0.761787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15893.22 | 14-SEP-18:01 | 15455.71 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.306895E+09 | 0.00 | 67.26 | 0.164725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14798.40 | 06-OCT-18:01 | 14798.40 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 7189129.55 | 0.00 | 3.12 | 3296316.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11530.60 | 10-NOV-16:01 | 11530.60 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 187259.43 | 0.00 | 0.12 | 31241.72 | 0.00 | 0.00 | 0.00 | 0.00 | 764.45 | 02-DEC-09:06 | 145.18 | 02-DEC-09:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172535E+11 | 0.00 | 2424.23 | 0.859610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 187259.43 | 0.00 | 0.12 | 31241.72 | 0.00 | 0.00 | 0.00 | 0.00 | 764.45 | 145.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.425741E+10 | 0.00 | 495.86 | 0.213158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17656.44 | 15729.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167522E+10 | 0.00 | 56.57 | 0.143749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30109.18 | 21-JAN-11:25 | 30109.18 | 21-JAN-11:25 | 0.00 | 0.00 | 0.00 |
February | 0.129660E+10 | 0.00 | 52.03 | 0.117778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21355.45 | 19-FEB-14:30 | 21355.45 | 19-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.211357E+11 | 0.00 | 426.47 | 0.169498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44523.55 | 30-APR-12:50 | 40688.91 | 15-APR-13:15 | 0.00 | 0.00 | 0.00 |
May | 0.172630E+11 | 0.00 | 423.93 | 0.895340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35205.99 | 23-MAY-12:50 | 27955.58 | 02-MAY-13:05 | 0.00 | 0.00 | 0.00 |
June | 0.231114E+11 | 0.00 | 540.46 | 0.720922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36534.11 | 13-JUN-13:05 | 20960.34 | 13-JUN-13:20 | 0.00 | 0.00 | 0.00 |
July | 0.314918E+11 | 0.00 | 627.64 | 0.110446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41514.43 | 22-JUL-13:20 | 27812.42 | 22-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.394720E+11 | 0.00 | 673.64 | 0.161977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44987.17 | 20-AUG-12:50 | 31797.54 | 20-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.397273E+11 | 0.00 | 609.68 | 0.196254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54955.71 | 12-SEP-12:30 | 47661.97 | 27-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.136258E+11 | 0.00 | 258.95 | 0.843647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49467.38 | 07-OCT-13:00 | 49467.38 | 07-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.119174E+10 | 0.00 | 47.46 | 0.102571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26359.48 | 11-NOV-13:30 | 26359.48 | 11-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189990E+12 | 0.00 | 3716.85 | 0.920576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.397273E+11 | 0.00 | 673.64 | 0.196254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54955.71 | 49467.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102574E+10 | 0.00 | 83.37 | 0.353301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64499.38 | 29-JAN-09:02 | 64499.38 | 29-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.804429E+09 | 0.00 | 77.40 | 0.272324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58602.88 | 21-FEB-19:02 | 58602.88 | 21-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.405573E+10 | 0.00 | 217.73 | 0.186960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72831.49 | 30-MAR-18:03 | 72831.49 | 30-MAR-18:03 | 0.00 | 0.00 | 0.00 |
April | 0.134245E+11 | 0.00 | 390.18 | 0.799237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77051.45 | 20-APR-18:01 | 77051.45 | 20-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.201771E+11 | 0.00 | 467.75 | 0.114827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76486.94 | 11-MAY-19:31 | 76486.94 | 11-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.325242E+11 | 0.00 | 472.85 | 0.195659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84286.07 | 26-JUN-21:01 | 76990.32 | 08-JUN-19:11 | 0.00 | 0.00 | 0.00 |
July | 0.339225E+11 | 0.00 | 442.00 | 0.206606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81592.88 | 17-JUL-21:51 | 73992.06 | 26-JUL-19:51 | 0.00 | 0.00 | 0.00 |
August | 0.279050E+11 | 0.00 | 400.52 | 0.157460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81753.35 | 16-AUG-21:52 | 72452.99 | 21-AUG-21:01 | 0.00 | 0.00 | 0.00 |
September | 0.201737E+11 | 0.00 | 434.87 | 0.101537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79831.94 | 10-SEP-20:31 | 71750.58 | 29-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.739745E+10 | 0.00 | 313.03 | 0.296093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73972.76 | 07-OCT-18:01 | 73972.76 | 07-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.217608E+10 | 0.00 | 138.52 | 0.715851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69629.96 | 24-NOV-19:02 | 66007.15 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.262813E+09 | 0.00 | 34.32 | 97426609.86 | 0.00 | 0.00 | 0.00 | 0.00 | 58928.35 | 02-DEC-09:02 | 58928.35 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163849E+12 | 0.00 | 3472.54 | 0.918707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.262813E+09 | 0.00 | 34.32 | 97426609.86 | 0.00 | 0.00 | 0.00 | 0.00 | 58602.88 | 58602.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.339225E+11 | 0.00 | 472.85 | 0.206606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84286.07 | 77051.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 70851533.85 | 0.00 | 19.07 | 26198987.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10999.88 | 21-JAN-16:01 | 10999.88 | 21-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.129619E+09 | 0.00 | 27.37 | 59815189.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14487.00 | 17-FEB-16:01 | 14487.00 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 70950093.41 | 0.00 | 28.19 | 30106717.92 | 0.00 | 0.00 | 0.00 | 0.00 | 11920.04 | 25-MAR-15:01 | 11920.04 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.299338E+10 | 0.00 | 409.37 | 0.180174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15330.95 | 12-APR-15:01 | 15330.95 | 12-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.323832E+10 | 0.00 | 453.86 | 0.172591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15330.24 | 11-MAY-18:01 | 15330.24 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.474208E+10 | 0.00 | 581.73 | 0.240883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15119.74 | 04-JUN-08:62 | 13798.66 | 30-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.609652E+10 | 0.00 | 650.83 | 0.315781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15006.81 | 08-JUL-08:61 | 14106.07 | 18-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.643213E+10 | 0.00 | 684.61 | 0.330955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15623.41 | 08-AUG-15:01 | 13807.12 | 12-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.487904E+10 | 0.00 | 577.34 | 0.254376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15314.08 | 16-SEP-15:02 | 14095.69 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.102297E+10 | 0.00 | 166.53 | 0.563338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15053.25 | 07-OCT-18:01 | 15053.25 | 07-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 71508988.73 | 0.00 | 19.65 | 27888085.03 | 0.00 | 0.00 | 0.00 | 0.00 | 11808.22 | 11-NOV-09:02 | 11808.22 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 14634742.23 | 0.00 | 8.38 | 4385512.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1761.23 | 06-DEC-09:03 | 650.78 | 06-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297620E+11 | 0.00 | 3626.93 | 0.156593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14634742.23 | 0.00 | 8.38 | 4385512.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1761.23 | 650.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.643213E+10 | 0.00 | 684.61 | 0.330955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15623.41 | 15330.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2673602.22 | 0.00 | 2.05 | 548790.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1667.32 | 23-JAN-09:04 | 513.38 | 23-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 17970602.49 | 0.00 | 9.30 | 5334118.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9515.44 | 20-FEB-09:02 | 9515.44 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 21440598.35 | 0.00 | 8.00 | 6811191.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5863.91 | 25-MAR-15:01 | 5099.38 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.172142E+10 | 0.00 | 292.37 | 0.102619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13836.87 | 14-APR-15:01 | 13836.87 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.223761E+10 | 0.00 | 362.75 | 0.120273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13711.22 | 11-MAY-19:31 | 13711.22 | 11-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.362636E+10 | 0.00 | 499.53 | 0.185192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15003.32 | 26-JUN-21:01 | 14271.23 | 26-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.421735E+10 | 0.00 | 518.48 | 0.215868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15830.88 | 23-JUL-08:32 | 15830.88 | 23-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.380999E+10 | 0.00 | 516.90 | 0.184315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14456.11 | 17-AUG-08:51 | 14456.11 | 17-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.246367E+10 | 0.00 | 429.64 | 0.119969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14184.90 | 11-SEP-08:51 | 14184.90 | 11-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.344176E+09 | 0.00 | 74.29 | 0.176266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13065.94 | 07-OCT-18:01 | 13065.94 | 07-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 7414693.69 | 0.00 | 3.91 | 1991889.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6080.20 | 11-NOV-09:02 | 4412.40 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 741764.66 | 0.00 | 0.35 | 149902.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.99 | 06-DEC-09:05 | 332.90 | 06-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184708E+11 | 0.00 | 2717.57 | 0.947347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 741764.66 | 0.00 | 0.35 | 149902.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.99 | 332.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.421735E+10 | 0.00 | 518.48 | 0.215868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15830.88 | 15830.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6914499.88 | 0.00 | 7.47 | 3865253.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3495.17 | 19-JAN-16:01 | 3495.17 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 54437245.02 | 0.00 | 34.75 | 30953983.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.45 | 17-FEB-16:01 | 4431.45 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 23436405.82 | 0.00 | 20.26 | 14571788.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3315.26 | 23-MAR-18:01 | 3315.26 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.713904E+09 | 0.00 | 304.97 | 0.481547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.22 | 12-APR-15:01 | 4431.22 | 12-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.846400E+09 | 0.00 | 351.40 | 0.525097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.14 | 11-MAY-18:01 | 4431.14 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.130306E+10 | 0.00 | 508.09 | 0.748203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4530.08 | 04-JUN-08:62 | 4021.75 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.167328E+10 | 0.00 | 590.21 | 0.959871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4432.51 | 08-JUL-08:61 | 4039.79 | 22-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.152911E+10 | 0.00 | 622.57 | 0.829502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4550.33 | 08-AUG-15:01 | 4067.82 | 15-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.104759E+10 | 0.00 | 459.94 | 0.576682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4449.57 | 02-SEP-08:61 | 3967.85 | 03-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.221398E+09 | 0.00 | 124.04 | 0.131410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4425.95 | 06-OCT-18:01 | 4425.95 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 10905799.80 | 0.00 | 11.50 | 5386598.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3628.36 | 10-NOV-16:01 | 3628.36 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 41629.68 | 0.00 | 0.12 | 8237.26 | 0.00 | 0.00 | 0.00 | 0.00 | 181.19 | 02-DEC-09:06 | 28.89 | 02-DEC-09:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743048E+10 | 0.00 | 3035.33 | 0.430710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 41629.68 | 0.00 | 0.12 | 8237.26 | 0.00 | 0.00 | 0.00 | 0.00 | 181.19 | 28.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.167328E+10 | 0.00 | 622.57 | 0.959871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4550.33 | 4431.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 549022.07 | 0.00 | 0.73 | 239806.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2094.80 | 19-JAN-16:01 | 1803.12 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 9030342.36 | 0.00 | 11.96 | 4328765.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3164.75 | 27-FEB-16:02 | 3164.75 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 10562500.29 | 0.00 | 10.17 | 5915174.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2950.02 | 23-MAR-18:01 | 2950.02 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.395675E+09 | 0.00 | 197.46 | 0.262884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3942.70 | 12-APR-15:01 | 3942.70 | 12-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.567002E+09 | 0.00 | 278.29 | 0.334757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4233.84 | 22-MAY-21:31 | 4216.38 | 23-MAY-19:42 | 0.00 | 0.00 | 0.00 |
June | 0.990687E+09 | 0.00 | 441.34 | 0.547297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.45 | 26-JUN-21:01 | 4295.58 | 22-JUN-18:42 | 0.00 | 0.00 | 0.00 |
July | 0.112719E+10 | 0.00 | 454.87 | 0.592904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4527.42 | 23-JUL-21:31 | 4481.60 | 11-JUL-18:52 | 0.00 | 0.00 | 0.00 |
August | 0.811569E+09 | 0.00 | 451.07 | 0.371296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353.00 | 17-AUG-21:11 | 4012.59 | 29-AUG-18:31 | 0.00 | 0.00 | 0.00 |
September | 0.417875E+09 | 0.00 | 286.08 | 0.184395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4243.49 | 12-SEP-20:11 | 4077.61 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 66494590.92 | 0.00 | 45.51 | 38443653.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3879.60 | 06-OCT-18:01 | 3879.60 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 834403.37 | 0.00 | 0.87 | 352377.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2671.39 | 10-NOV-16:01 | 2407.73 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439747E+10 | 0.00 | 2178.34 | 0.234281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112719E+10 | 0.00 | 454.87 | 0.592904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.45 | 4481.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119694E+10 | 0.00 | 138.31 | 0.649401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24652.89 | 10-JAN-16:01 | 24652.89 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.148032E+10 | 0.00 | 155.40 | 0.770387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19893.86 | 27-FEB-16:02 | 19893.86 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.442639E+09 | 0.00 | 89.04 | 0.181169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21150.90 | 25-MAR-15:01 | 21150.90 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.549495E+10 | 0.00 | 444.10 | 0.325397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21125.61 | 29-APR-08:61 | 21125.61 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.464142E+10 | 0.00 | 449.91 | 0.228978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24658.89 | 11-MAY-18:01 | 24658.89 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.627820E+10 | 0.00 | 576.26 | 0.286883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25013.87 | 26-JUN-18:02 | 23460.28 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.821891E+10 | 0.00 | 621.78 | 0.392825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24414.77 | 29-JUL-15:01 | 22772.52 | 16-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.954685E+10 | 0.00 | 666.93 | 0.494181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25293.79 | 08-AUG-15:01 | 22084.58 | 12-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.923771E+10 | 0.00 | 603.60 | 0.545321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24998.62 | 16-SEP-15:02 | 22095.91 | 15-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.344221E+10 | 0.00 | 302.21 | 0.197177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24662.60 | 06-OCT-18:01 | 24662.60 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.963437E+09 | 0.00 | 120.41 | 0.434343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20461.05 | 10-NOV-16:01 | 20461.05 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.359119E+09 | 0.00 | 45.00 | 0.193574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19602.95 | 21-DEC-16:02 | 19602.95 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513027E+11 | 0.00 | 4212.95 | 0.269365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.359119E+09 | 0.00 | 45.00 | 0.181169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19602.95 | 19602.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.954685E+10 | 0.00 | 666.93 | 0.545321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25293.79 | 24662.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 526.65 | 341.04 | 185.61 | 526.17 | 508.85 | 0.00 | 0.00 | 0.00 |
February | 639.06 | 389.50 | 249.57 | 655.27 | 491.66 | 0.00 | 0.00 | 0.00 |
March | 394.43 | 114.02 | 280.42 | 330.18 | 409.91 | 0.00 | 0.00 | 0.00 |
April | 808.56 | 358.28 | 450.29 | 934.10 | 339.58 | 0.00 | 0.00 | 0.00 |
May | 677.84 | 219.58 | 458.26 | 733.03 | 288.99 | 0.00 | 0.00 | 0.00 |
June | 625.72 | 151.33 | 474.39 | 713.41 | 212.04 | 0.00 | 0.00 | 0.00 |
July | 674.45 | 208.66 | 465.80 | 822.44 | 194.94 | 0.00 | 0.00 | 0.00 |
August | 792.15 | 354.92 | 437.23 | 1007.43 | 214.98 | 0.00 | 0.00 | 0.00 |
September | 949.31 | 560.29 | 389.02 | 1185.80 | 282.84 | 0.00 | 0.00 | 0.00 |
October | 633.43 | 365.19 | 268.24 | 705.30 | 377.55 | 0.00 | 0.00 | 0.00 |
November | 457.43 | 278.17 | 179.26 | 460.83 | 462.71 | 0.00 | 0.00 | 0.00 |
December | 362.99 | 232.76 | 130.23 | 351.86 | 574.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.52 | 296.63 | 330.89 | 701.21 | 362.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.99 | 114.02 | 130.23 | 330.18 | 194.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 949.31 | 560.29 | 474.39 | 1185.80 | 574.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1483.01 | 960.34 | 522.67 | 1464.68 | 1471.67 | 0.00 | 0.00 | 0.00 |
February | 1799.56 | 1096.79 | 702.77 | 1825.33 | 1426.64 | 0.00 | 0.00 | 0.00 |
March | 1110.70 | 321.07 | 789.63 | 911.84 | 1190.96 | 0.00 | 0.00 | 0.00 |
April | 2276.87 | 1008.88 | 1267.98 | 2599.58 | 1010.75 | 0.00 | 0.00 | 0.00 |
May | 1908.76 | 618.33 | 1290.43 | 2031.59 | 867.45 | 0.00 | 0.00 | 0.00 |
June | 1761.98 | 426.13 | 1335.85 | 1971.40 | 651.52 | 0.00 | 0.00 | 0.00 |
July | 1899.22 | 587.57 | 1311.65 | 2278.14 | 601.40 | 0.00 | 0.00 | 0.00 |
August | 2230.66 | 999.44 | 1231.21 | 2801.21 | 667.65 | 0.00 | 0.00 | 0.00 |
September | 2673.19 | 1577.74 | 1095.45 | 3305.88 | 863.17 | 0.00 | 0.00 | 0.00 |
October | 1783.71 | 1028.36 | 755.35 | 1964.07 | 1122.25 | 0.00 | 0.00 | 0.00 |
November | 1288.09 | 783.31 | 504.77 | 1282.02 | 1352.07 | 0.00 | 0.00 | 0.00 |
December | 1022.16 | 655.44 | 366.72 | 979.72 | 1655.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1767.06 | 835.28 | 931.77 | 1948.61 | 1071.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1022.16 | 321.07 | 366.72 | 911.84 | 601.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2673.19 | 1577.74 | 1335.85 | 3305.88 | 1655.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1926.52 | 1247.54 | 678.98 | 1923.56 | 2034.57 | 0.00 | 0.00 | 0.00 |
February | 2337.73 | 1424.80 | 912.94 | 2400.60 | 1964.38 | 0.00 | 0.00 | 0.00 |
March | 1442.86 | 417.08 | 1025.78 | 1187.16 | 1664.56 | 0.00 | 0.00 | 0.00 |
April | 2957.78 | 1310.59 | 1647.18 | 3433.36 | 1389.46 | 0.00 | 0.00 | 0.00 |
May | 2479.59 | 803.25 | 1676.34 | 2671.86 | 1207.57 | 0.00 | 0.00 | 0.00 |
June | 2288.91 | 553.57 | 1735.34 | 2584.23 | 913.40 | 0.00 | 0.00 | 0.00 |
July | 2467.19 | 763.28 | 1703.91 | 2995.06 | 839.37 | 0.00 | 0.00 | 0.00 |
August | 2897.75 | 1298.33 | 1599.42 | 3697.62 | 918.58 | 0.00 | 0.00 | 0.00 |
September | 3472.62 | 2049.57 | 1423.05 | 4365.36 | 1178.24 | 0.00 | 0.00 | 0.00 |
October | 2317.14 | 1335.90 | 981.24 | 2585.66 | 1560.07 | 0.00 | 0.00 | 0.00 |
November | 1673.30 | 1017.57 | 655.73 | 1680.66 | 1881.14 | 0.00 | 0.00 | 0.00 |
December | 1327.84 | 851.45 | 476.39 | 1281.94 | 2291.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2295.51 | 1085.08 | 1210.43 | 2563.71 | 1484.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1327.84 | 417.08 | 476.39 | 1187.16 | 839.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3472.62 | 2049.57 | 1735.34 | 4365.36 | 2291.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 105.90 | 100.28 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 131.06 | 97.79 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 65.95 | 81.52 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 185.24 | 68.28 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 143.34 | 59.20 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 138.64 | 43.17 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 161.40 | 38.89 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 199.89 | 41.90 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 236.47 | 55.43 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 141.07 | 74.61 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 92.32 | 91.17 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.78 | 113.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 139.15 | 72.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 65.95 | 38.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 236.47 | 113.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 41.02 | 202.25 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 94.84 | 191.91 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 69.55 | 152.74 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 268.47 | 124.04 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 313.49 | 104.92 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 368.04 | 77.22 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 391.83 | 69.82 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 331.70 | 76.40 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 254.34 | 103.41 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 106.18 | 142.75 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 39.42 | 179.47 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 12.51 | 226.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 191.28 | 137.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 12.51 | 69.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 391.83 | 226.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.81 | 111.44 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 5.07 | 105.02 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 15.28 | 84.30 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 44.04 | 66.61 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 54.85 | 53.41 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 77.29 | 40.00 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 77.48 | 36.87 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 60.06 | 41.42 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 40.05 | 56.77 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 15.41 | 77.03 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 2.84 | 96.91 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.16 | 121.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 33.00 | 74.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.16 | 36.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 77.48 | 121.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 43.58 | 199.86 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 98.44 | 189.38 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 71.35 | 151.71 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 271.96 | 123.09 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 314.35 | 104.96 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 366.09 | 78.32 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 386.88 | 72.21 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 329.20 | 79.12 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 256.48 | 103.37 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 109.69 | 140.86 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 41.81 | 177.28 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 13.65 | 224.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 192.26 | 136.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 13.65 | 72.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 386.88 | 224.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.29 | 53.93 | 29.35 | 77.82 | 100.63 | 0.00 | 0.00 | 0.00 |
February | 101.06 | 61.60 | 39.47 | 97.48 | 98.34 | 0.00 | 0.00 | 0.00 |
March | 62.38 | 18.03 | 44.35 | 46.98 | 78.59 | 0.00 | 0.00 | 0.00 |
April | 127.87 | 56.66 | 71.21 | 136.33 | 74.74 | 0.00 | 0.00 | 0.00 |
May | 107.20 | 34.73 | 72.47 | 102.42 | 67.32 | 0.00 | 0.00 | 0.00 |
June | 98.95 | 23.93 | 75.02 | 97.82 | 52.16 | 0.00 | 0.00 | 0.00 |
July | 106.66 | 33.00 | 73.66 | 115.97 | 48.24 | 0.00 | 0.00 | 0.00 |
August | 125.27 | 56.13 | 69.15 | 147.48 | 52.12 | 0.00 | 0.00 | 0.00 |
September | 150.13 | 88.61 | 61.52 | 177.06 | 65.11 | 0.00 | 0.00 | 0.00 |
October | 100.17 | 57.75 | 42.42 | 103.70 | 84.00 | 0.00 | 0.00 | 0.00 |
November | 72.34 | 43.99 | 28.35 | 67.56 | 96.29 | 0.00 | 0.00 | 0.00 |
December | 57.40 | 36.81 | 20.60 | 55.56 | 93.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99.24 | 46.91 | 52.33 | 102.03 | 75.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 57.40 | 18.03 | 20.60 | 46.98 | 48.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.13 | 88.61 | 75.02 | 177.06 | 100.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.60 | 0.00 | 14.60 | 1.07 | 93.72 | 0.00 | 0.00 | 0.00 |
February | 22.79 | 0.00 | 22.79 | 3.34 | 87.30 | 0.00 | 0.00 | 0.00 |
March | 31.55 | 0.00 | 31.55 | 11.11 | 70.42 | 0.00 | 0.00 | 0.00 |
April | 51.55 | 0.34 | 51.21 | 36.68 | 53.30 | 0.00 | 0.00 | 0.00 |
May | 64.45 | 3.29 | 61.16 | 46.32 | 42.53 | 0.00 | 0.00 | 0.00 |
June | 71.00 | 4.44 | 66.56 | 65.74 | 31.10 | 0.00 | 0.00 | 0.00 |
July | 67.51 | 3.97 | 63.54 | 66.93 | 28.13 | 0.00 | 0.00 | 0.00 |
August | 53.15 | 0.99 | 52.16 | 52.15 | 31.38 | 0.00 | 0.00 | 0.00 |
September | 40.31 | 0.02 | 40.29 | 34.30 | 44.23 | 0.00 | 0.00 | 0.00 |
October | 25.81 | 0.00 | 25.81 | 12.10 | 63.79 | 0.00 | 0.00 | 0.00 |
November | 15.51 | 0.00 | 15.51 | 1.78 | 81.87 | 0.00 | 0.00 | 0.00 |
December | 10.56 | 0.00 | 10.56 | 0.04 | 103.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.14 | 1.10 | 38.04 | 27.75 | 60.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.56 | 0.00 | 10.56 | 0.04 | 28.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 4.44 | 66.56 | 66.93 | 103.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.24 | 27.58 | 41.66 | 39.76 | 199.15 | 0.00 | 0.00 | 0.00 |
February | 104.56 | 38.96 | 65.60 | 67.97 | 187.81 | 0.00 | 0.00 | 0.00 |
March | 108.63 | 21.43 | 87.21 | 68.30 | 151.20 | 0.00 | 0.00 | 0.00 |
April | 291.02 | 136.45 | 154.57 | 309.63 | 118.74 | 0.00 | 0.00 | 0.00 |
May | 306.41 | 133.65 | 172.76 | 318.00 | 101.60 | 0.00 | 0.00 | 0.00 |
June | 303.21 | 121.13 | 182.08 | 338.06 | 74.82 | 0.00 | 0.00 | 0.00 |
July | 309.46 | 131.45 | 178.01 | 361.23 | 67.19 | 0.00 | 0.00 | 0.00 |
August | 293.97 | 140.73 | 153.24 | 351.40 | 72.82 | 0.00 | 0.00 | 0.00 |
September | 263.92 | 140.24 | 123.69 | 303.03 | 99.26 | 0.00 | 0.00 | 0.00 |
October | 128.37 | 53.68 | 74.69 | 115.40 | 140.09 | 0.00 | 0.00 | 0.00 |
November | 66.44 | 22.61 | 43.83 | 37.92 | 175.34 | 0.00 | 0.00 | 0.00 |
December | 49.42 | 18.49 | 30.92 | 24.30 | 219.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.50 | 82.30 | 109.19 | 195.05 | 133.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.42 | 18.49 | 30.92 | 24.30 | 67.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.46 | 140.73 | 182.08 | 361.23 | 219.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 105.70 | 100.13 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 131.00 | 97.37 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 65.55 | 81.34 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 183.56 | 68.10 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 142.08 | 58.73 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 138.10 | 42.45 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 160.79 | 38.22 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 199.03 | 41.49 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 235.15 | 55.26 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 140.42 | 74.44 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 92.15 | 91.01 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.48 | 113.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 138.47 | 71.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 65.55 | 38.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 235.15 | 113.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.65 | 111.22 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 4.78 | 104.37 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 14.88 | 84.14 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 42.18 | 66.53 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 53.80 | 52.93 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 77.33 | 39.14 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 78.16 | 35.63 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 59.69 | 40.24 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 38.54 | 56.31 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 14.70 | 76.88 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 2.68 | 96.65 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.13 | 121.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 32.52 | 73.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.13 | 35.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 78.16 | 121.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.24 | 27.58 | 41.66 | 41.39 | 195.67 | 0.00 | 0.00 | 0.00 |
February | 104.56 | 38.96 | 65.60 | 70.62 | 184.21 | 0.00 | 0.00 | 0.00 |
March | 108.63 | 21.43 | 87.21 | 69.94 | 150.03 | 0.00 | 0.00 | 0.00 |
April | 291.02 | 136.45 | 154.57 | 312.70 | 117.64 | 0.00 | 0.00 | 0.00 |
May | 306.41 | 133.65 | 172.76 | 319.40 | 101.38 | 0.00 | 0.00 | 0.00 |
June | 303.21 | 121.13 | 182.08 | 337.50 | 75.54 | 0.00 | 0.00 | 0.00 |
July | 309.46 | 131.45 | 178.01 | 359.69 | 68.83 | 0.00 | 0.00 | 0.00 |
August | 293.97 | 140.73 | 153.24 | 350.94 | 74.70 | 0.00 | 0.00 | 0.00 |
September | 263.92 | 140.24 | 123.69 | 305.31 | 98.75 | 0.00 | 0.00 | 0.00 |
October | 128.37 | 53.68 | 74.69 | 118.57 | 138.00 | 0.00 | 0.00 | 0.00 |
November | 66.44 | 22.61 | 43.83 | 39.69 | 172.39 | 0.00 | 0.00 | 0.00 |
December | 49.42 | 18.49 | 30.92 | 25.07 | 216.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.50 | 82.30 | 109.19 | 196.35 | 132.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.42 | 18.49 | 30.92 | 25.07 | 68.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.46 | 140.73 | 182.08 | 359.69 | 216.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 1.52 | 151.69 | 0.00 | 0.00 | 0.00 |
February | 36.08 | 0.00 | 36.08 | 4.76 | 140.80 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 0.00 | 49.93 | 17.80 | 112.20 | 0.00 | 0.00 | 0.00 |
April | 81.59 | 0.54 | 81.05 | 57.34 | 87.52 | 0.00 | 0.00 | 0.00 |
May | 102.01 | 5.20 | 96.81 | 72.30 | 70.93 | 0.00 | 0.00 | 0.00 |
June | 112.38 | 7.03 | 105.35 | 102.42 | 53.64 | 0.00 | 0.00 | 0.00 |
July | 106.85 | 6.28 | 100.57 | 103.79 | 49.14 | 0.00 | 0.00 | 0.00 |
August | 84.13 | 1.57 | 82.56 | 79.84 | 55.42 | 0.00 | 0.00 | 0.00 |
September | 63.81 | 0.04 | 63.77 | 51.55 | 76.92 | 0.00 | 0.00 | 0.00 |
October | 40.86 | 0.00 | 40.86 | 18.32 | 103.85 | 0.00 | 0.00 | 0.00 |
November | 24.55 | 0.00 | 24.55 | 2.63 | 131.65 | 0.00 | 0.00 | 0.00 |
December | 16.72 | 0.00 | 16.72 | 0.04 | 166.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.95 | 1.73 | 60.22 | 42.89 | 99.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.72 | 0.00 | 16.72 | 0.04 | 49.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.38 | 7.03 | 105.35 | 103.79 | 166.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.52 | 0.00 | 8.52 | 0.56 | 55.92 | 0.00 | 0.00 | 0.00 |
February | 13.30 | 0.00 | 13.30 | 1.76 | 51.90 | 0.00 | 0.00 | 0.00 |
March | 18.41 | 0.00 | 18.41 | 6.56 | 41.36 | 0.00 | 0.00 | 0.00 |
April | 30.08 | 0.20 | 29.88 | 21.14 | 32.26 | 0.00 | 0.00 | 0.00 |
May | 37.61 | 1.92 | 35.69 | 26.65 | 26.15 | 0.00 | 0.00 | 0.00 |
June | 41.43 | 2.59 | 38.84 | 37.76 | 19.77 | 0.00 | 0.00 | 0.00 |
July | 39.39 | 2.32 | 37.07 | 38.26 | 18.11 | 0.00 | 0.00 | 0.00 |
August | 31.01 | 0.58 | 30.43 | 29.43 | 20.43 | 0.00 | 0.00 | 0.00 |
September | 23.52 | 0.01 | 23.51 | 19.00 | 28.36 | 0.00 | 0.00 | 0.00 |
October | 15.06 | 0.00 | 15.06 | 6.75 | 38.28 | 0.00 | 0.00 | 0.00 |
November | 9.05 | 0.00 | 9.05 | 0.97 | 48.53 | 0.00 | 0.00 | 0.00 |
December | 6.16 | 0.00 | 6.16 | 0.01 | 61.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.84 | 0.64 | 22.20 | 15.81 | 36.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.16 | 0.00 | 6.16 | 0.01 | 18.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.43 | 2.59 | 38.84 | 38.26 | 61.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.59 | 31.46 | 17.12 | 49.19 | 49.08 | 0.00 | 0.00 | 0.00 |
February | 58.96 | 35.93 | 23.02 | 61.31 | 47.39 | 0.00 | 0.00 | 0.00 |
March | 36.39 | 10.52 | 25.87 | 30.52 | 39.63 | 0.00 | 0.00 | 0.00 |
April | 74.59 | 33.05 | 41.54 | 87.83 | 32.78 | 0.00 | 0.00 | 0.00 |
May | 62.53 | 20.26 | 42.28 | 68.10 | 28.89 | 0.00 | 0.00 | 0.00 |
June | 57.73 | 13.96 | 43.76 | 65.95 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 62.22 | 19.25 | 42.97 | 76.37 | 19.87 | 0.00 | 0.00 | 0.00 |
August | 73.08 | 32.74 | 40.34 | 94.20 | 21.53 | 0.00 | 0.00 | 0.00 |
September | 87.58 | 51.69 | 35.89 | 111.24 | 27.76 | 0.00 | 0.00 | 0.00 |
October | 58.44 | 33.69 | 24.75 | 66.25 | 36.51 | 0.00 | 0.00 | 0.00 |
November | 42.20 | 25.66 | 16.54 | 43.03 | 44.77 | 0.00 | 0.00 | 0.00 |
December | 33.49 | 21.47 | 12.01 | 32.65 | 56.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.89 | 27.37 | 30.53 | 65.46 | 35.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.49 | 10.52 | 12.01 | 30.52 | 19.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.58 | 51.69 | 43.76 | 111.24 | 56.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.87 | 85.39 | 46.48 | 133.51 | 133.21 | 0.00 | 0.00 | 0.00 |
February | 160.02 | 97.53 | 62.49 | 166.41 | 128.63 | 0.00 | 0.00 | 0.00 |
March | 98.77 | 28.55 | 70.22 | 82.84 | 107.57 | 0.00 | 0.00 | 0.00 |
April | 202.46 | 89.71 | 112.75 | 238.38 | 88.97 | 0.00 | 0.00 | 0.00 |
May | 169.73 | 54.98 | 114.75 | 184.85 | 78.42 | 0.00 | 0.00 | 0.00 |
June | 156.68 | 37.89 | 118.79 | 179.00 | 58.75 | 0.00 | 0.00 | 0.00 |
July | 168.88 | 52.25 | 116.63 | 207.28 | 53.94 | 0.00 | 0.00 | 0.00 |
August | 198.35 | 88.87 | 109.48 | 255.69 | 58.45 | 0.00 | 0.00 | 0.00 |
September | 237.70 | 140.29 | 97.41 | 301.92 | 75.34 | 0.00 | 0.00 | 0.00 |
October | 158.61 | 91.44 | 67.17 | 179.82 | 99.10 | 0.00 | 0.00 | 0.00 |
November | 114.54 | 69.65 | 44.89 | 116.80 | 121.51 | 0.00 | 0.00 | 0.00 |
December | 90.89 | 58.28 | 32.61 | 88.61 | 153.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.13 | 74.27 | 82.86 | 177.68 | 96.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.89 | 28.55 | 32.61 | 82.84 | 53.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.70 | 140.29 | 118.79 | 301.92 | 153.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 106.13 | 98.94 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 131.03 | 96.92 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 66.02 | 80.50 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 183.97 | 67.87 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 142.02 | 59.10 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 137.23 | 43.08 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 159.95 | 38.75 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 198.58 | 41.52 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 235.33 | 54.91 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 140.82 | 73.66 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 92.39 | 90.00 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.90 | 112.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 138.50 | 71.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 66.02 | 38.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 235.33 | 112.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 41.35 | 199.20 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 94.90 | 189.87 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 69.64 | 150.70 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 265.87 | 123.07 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 310.21 | 104.59 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 364.22 | 76.93 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 388.17 | 69.46 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 328.81 | 75.60 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 252.59 | 102.27 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 105.88 | 140.69 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 39.68 | 176.95 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 12.73 | 223.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 189.83 | 135.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 12.73 | 69.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 388.17 | 223.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.97 | 109.71 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 5.29 | 103.73 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 15.51 | 83.12 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 43.11 | 66.20 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 53.53 | 53.37 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 75.53 | 40.14 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 75.55 | 37.31 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 58.82 | 41.76 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 39.65 | 56.51 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 15.64 | 75.78 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 3.05 | 95.31 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.21 | 120.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 32.46 | 73.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.21 | 37.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 75.55 | 120.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 44.07 | 196.91 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 98.83 | 187.23 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 71.62 | 149.63 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 269.39 | 122.19 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 310.77 | 104.88 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 361.53 | 78.57 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 381.84 | 72.89 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 325.40 | 79.46 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 254.67 | 102.70 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 109.79 | 138.62 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 42.30 | 174.73 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 13.90 | 221.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 190.64 | 135.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 13.90 | 72.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 381.84 | 221.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.71 | 98.89 | 53.82 | 150.48 | 151.17 | 0.00 | 0.00 | 0.00 |
February | 185.31 | 112.94 | 72.37 | 187.47 | 147.66 | 0.00 | 0.00 | 0.00 |
March | 114.37 | 33.06 | 81.31 | 93.26 | 121.67 | 0.00 | 0.00 | 0.00 |
April | 234.46 | 103.89 | 130.57 | 267.52 | 100.53 | 0.00 | 0.00 | 0.00 |
May | 196.56 | 63.67 | 132.88 | 207.73 | 86.64 | 0.00 | 0.00 | 0.00 |
June | 181.44 | 43.88 | 137.56 | 202.74 | 62.20 | 0.00 | 0.00 | 0.00 |
July | 195.57 | 60.50 | 135.07 | 236.12 | 55.76 | 0.00 | 0.00 | 0.00 |
August | 229.70 | 102.92 | 126.79 | 291.36 | 60.35 | 0.00 | 0.00 | 0.00 |
September | 275.27 | 162.47 | 112.81 | 342.86 | 81.58 | 0.00 | 0.00 | 0.00 |
October | 183.68 | 105.90 | 77.78 | 202.78 | 112.05 | 0.00 | 0.00 | 0.00 |
November | 132.64 | 80.66 | 51.98 | 131.41 | 138.22 | 0.00 | 0.00 | 0.00 |
December | 105.26 | 67.49 | 37.76 | 100.53 | 172.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 181.96 | 86.01 | 95.95 | 200.92 | 107.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.26 | 33.06 | 37.76 | 93.26 | 55.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.27 | 162.47 | 137.56 | 342.86 | 172.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.71 | 0.00 | 127.71 | 3.59 | 946.88 | 0.00 | 0.00 | 0.00 |
February | 199.42 | 0.00 | 199.42 | 13.46 | 888.72 | 0.00 | 0.00 | 0.00 |
March | 275.99 | 0.00 | 275.99 | 68.90 | 717.70 | 0.00 | 0.00 | 0.00 |
April | 450.98 | 3.00 | 447.98 | 266.30 | 545.17 | 0.00 | 0.00 | 0.00 |
May | 563.83 | 28.75 | 535.08 | 333.33 | 445.08 | 0.00 | 0.00 | 0.00 |
June | 621.15 | 38.85 | 582.30 | 500.53 | 333.60 | 0.00 | 0.00 | 0.00 |
July | 590.59 | 34.74 | 555.86 | 514.90 | 302.15 | 0.00 | 0.00 | 0.00 |
August | 464.99 | 8.70 | 456.29 | 396.59 | 337.04 | 0.00 | 0.00 | 0.00 |
September | 352.69 | 0.21 | 352.48 | 250.21 | 469.05 | 0.00 | 0.00 | 0.00 |
October | 225.82 | 0.00 | 225.82 | 76.29 | 664.81 | 0.00 | 0.00 | 0.00 |
November | 135.69 | 0.00 | 135.69 | 6.43 | 847.48 | 0.00 | 0.00 | 0.00 |
December | 92.40 | 0.00 | 92.40 | 0.00 | 1047.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.41 | 9.59 | 332.82 | 203.51 | 627.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.40 | 0.00 | 92.40 | 0.00 | 302.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.15 | 38.85 | 582.30 | 514.90 | 1047.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.71 | 0.00 | 127.71 | 2.52 | 976.41 | 0.00 | 0.00 | 0.00 |
February | 199.42 | 0.00 | 199.42 | 10.56 | 916.59 | 0.00 | 0.00 | 0.00 |
March | 275.99 | 0.00 | 275.99 | 61.19 | 739.13 | 0.00 | 0.00 | 0.00 |
April | 450.98 | 3.00 | 447.98 | 255.17 | 557.78 | 0.00 | 0.00 | 0.00 |
May | 563.83 | 28.75 | 535.08 | 320.18 | 454.93 | 0.00 | 0.00 | 0.00 |
June | 621.15 | 38.85 | 582.30 | 488.23 | 340.89 | 0.00 | 0.00 | 0.00 |
July | 590.59 | 34.74 | 555.86 | 503.58 | 308.78 | 0.00 | 0.00 | 0.00 |
August | 464.99 | 8.70 | 456.29 | 386.44 | 345.08 | 0.00 | 0.00 | 0.00 |
September | 352.69 | 0.21 | 352.48 | 240.65 | 480.13 | 0.00 | 0.00 | 0.00 |
October | 225.82 | 0.00 | 225.82 | 69.09 | 684.75 | 0.00 | 0.00 | 0.00 |
November | 135.69 | 0.00 | 135.69 | 4.63 | 876.02 | 0.00 | 0.00 | 0.00 |
December | 92.40 | 0.00 | 92.40 | 0.00 | 1079.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.41 | 9.59 | 332.82 | 196.13 | 645.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.40 | 0.00 | 92.40 | 0.00 | 308.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.15 | 38.85 | 582.30 | 503.58 | 1079.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 3.11 | 110.42 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 6.96 | 105.52 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 20.19 | 85.03 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 56.45 | 68.60 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 69.19 | 59.34 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 96.56 | 45.35 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 99.88 | 41.58 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 79.97 | 44.07 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 53.53 | 58.11 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 21.23 | 78.78 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 4.59 | 98.49 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.59 | 124.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 42.87 | 76.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.59 | 41.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 99.88 | 124.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.47 | 55.15 | 83.32 | 93.83 | 393.37 | 0.00 | 0.00 | 0.00 |
February | 209.10 | 77.91 | 131.19 | 154.22 | 376.77 | 0.00 | 0.00 | 0.00 |
March | 217.25 | 42.85 | 174.40 | 163.43 | 307.25 | 0.00 | 0.00 | 0.00 |
April | 582.00 | 272.88 | 309.12 | 686.11 | 247.69 | 0.00 | 0.00 | 0.00 |
May | 612.78 | 267.28 | 345.50 | 698.34 | 224.96 | 0.00 | 0.00 | 0.00 |
June | 606.38 | 242.24 | 364.14 | 748.11 | 172.21 | 0.00 | 0.00 | 0.00 |
July | 618.87 | 262.88 | 355.99 | 800.48 | 156.86 | 0.00 | 0.00 | 0.00 |
August | 587.90 | 281.45 | 306.45 | 780.84 | 163.90 | 0.00 | 0.00 | 0.00 |
September | 527.81 | 280.46 | 247.35 | 674.60 | 209.14 | 0.00 | 0.00 | 0.00 |
October | 256.72 | 107.36 | 149.36 | 266.80 | 286.69 | 0.00 | 0.00 | 0.00 |
November | 132.86 | 45.21 | 87.65 | 90.03 | 354.87 | 0.00 | 0.00 | 0.00 |
December | 98.82 | 36.98 | 61.84 | 56.22 | 449.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 382.96 | 164.59 | 218.37 | 435.46 | 278.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.82 | 36.98 | 61.84 | 56.22 | 156.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 618.87 | 281.45 | 364.14 | 800.48 | 449.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 111.78 | 99.93 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 138.46 | 98.95 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 73.50 | 82.91 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 201.12 | 69.88 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 158.76 | 64.30 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 157.41 | 48.50 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 181.69 | 44.20 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 219.61 | 45.77 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 253.71 | 57.69 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 151.37 | 76.65 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 97.50 | 93.07 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 73.64 | 117.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 151.37 | 74.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 73.50 | 44.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 253.71 | 117.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 1.19 | 154.05 | 0.00 | 0.00 | 0.00 |
February | 36.08 | 0.00 | 36.08 | 3.86 | 143.46 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 0.00 | 49.93 | 16.36 | 114.04 | 0.00 | 0.00 | 0.00 |
April | 81.59 | 0.54 | 81.05 | 53.45 | 88.61 | 0.00 | 0.00 | 0.00 |
May | 102.01 | 5.20 | 96.81 | 68.10 | 71.80 | 0.00 | 0.00 | 0.00 |
June | 112.38 | 7.03 | 105.35 | 97.46 | 54.89 | 0.00 | 0.00 | 0.00 |
July | 106.85 | 6.28 | 100.57 | 98.80 | 50.27 | 0.00 | 0.00 | 0.00 |
August | 84.13 | 1.57 | 82.56 | 75.93 | 56.18 | 0.00 | 0.00 | 0.00 |
September | 63.81 | 0.04 | 63.77 | 48.83 | 77.07 | 0.00 | 0.00 | 0.00 |
October | 40.86 | 0.00 | 40.86 | 16.87 | 104.94 | 0.00 | 0.00 | 0.00 |
November | 24.55 | 0.00 | 24.55 | 2.11 | 134.43 | 0.00 | 0.00 | 0.00 |
December | 16.72 | 0.00 | 16.72 | 0.01 | 169.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.95 | 1.73 | 60.22 | 40.44 | 101.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.72 | 0.00 | 16.72 | 0.01 | 50.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.38 | 7.03 | 105.35 | 98.80 | 169.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.67 | 0.00 | 20.67 | 1.06 | 137.80 | 0.00 | 0.00 | 0.00 |
February | 32.28 | 0.00 | 32.28 | 3.45 | 128.35 | 0.00 | 0.00 | 0.00 |
March | 44.68 | 0.00 | 44.68 | 14.64 | 102.03 | 0.00 | 0.00 | 0.00 |
April | 73.00 | 0.49 | 72.52 | 47.82 | 79.28 | 0.00 | 0.00 | 0.00 |
May | 91.27 | 4.65 | 86.62 | 60.93 | 64.24 | 0.00 | 0.00 | 0.00 |
June | 100.55 | 6.29 | 94.26 | 87.20 | 49.11 | 0.00 | 0.00 | 0.00 |
July | 95.60 | 5.62 | 89.98 | 88.40 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 75.27 | 1.41 | 73.86 | 67.94 | 50.26 | 0.00 | 0.00 | 0.00 |
September | 57.09 | 0.03 | 57.06 | 43.69 | 68.96 | 0.00 | 0.00 | 0.00 |
October | 36.56 | 0.00 | 36.56 | 15.09 | 93.89 | 0.00 | 0.00 | 0.00 |
November | 21.96 | 0.00 | 21.96 | 1.89 | 120.27 | 0.00 | 0.00 | 0.00 |
December | 14.96 | 0.00 | 14.96 | 0.01 | 152.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.43 | 1.55 | 53.88 | 36.18 | 90.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.96 | 0.00 | 14.96 | 0.01 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.55 | 6.29 | 94.26 | 88.40 | 152.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 388.74 | 251.73 | 137.01 | 388.79 | 397.96 | 0.00 | 0.00 | 0.00 |
February | 471.72 | 287.50 | 184.22 | 483.94 | 385.76 | 0.00 | 0.00 | 0.00 |
March | 291.15 | 84.16 | 206.99 | 238.05 | 322.48 | 0.00 | 0.00 | 0.00 |
April | 596.83 | 264.46 | 332.38 | 689.71 | 266.04 | 0.00 | 0.00 | 0.00 |
May | 500.34 | 162.08 | 338.26 | 532.18 | 235.01 | 0.00 | 0.00 | 0.00 |
June | 461.87 | 111.70 | 350.17 | 513.15 | 177.92 | 0.00 | 0.00 | 0.00 |
July | 497.84 | 154.02 | 343.83 | 596.08 | 163.39 | 0.00 | 0.00 | 0.00 |
August | 584.72 | 261.98 | 322.74 | 740.74 | 175.10 | 0.00 | 0.00 | 0.00 |
September | 700.72 | 413.57 | 287.15 | 879.42 | 223.18 | 0.00 | 0.00 | 0.00 |
October | 467.56 | 269.56 | 198.00 | 523.68 | 295.86 | 0.00 | 0.00 | 0.00 |
November | 337.65 | 205.33 | 132.32 | 339.46 | 365.81 | 0.00 | 0.00 | 0.00 |
December | 267.94 | 171.81 | 96.13 | 258.01 | 460.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.20 | 218.95 | 244.25 | 514.54 | 288.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.94 | 84.16 | 96.13 | 238.05 | 163.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 700.72 | 413.57 | 350.17 | 879.42 | 460.72 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141058E+10 | 0.913437E+09 | 0.497142E+09 | 0.140930E+10 | 0.136292E+10 |
February | 0.154602E+10 | 0.942266E+09 | 0.603757E+09 | 0.158522E+10 | 0.118943E+10 |
March | 0.105645E+10 | 0.305385E+09 | 0.751065E+09 | 0.884359E+09 | 0.109789E+10 |
April | 0.209580E+10 | 0.928651E+09 | 0.116715E+10 | 0.242119E+10 | 0.880194E+09 |
May | 0.181553E+10 | 0.588130E+09 | 0.122740E+10 | 0.196335E+10 | 0.774023E+09 |
June | 0.162186E+10 | 0.392246E+09 | 0.122962E+10 | 0.184917E+10 | 0.549614E+09 |
July | 0.180646E+10 | 0.558869E+09 | 0.124759E+10 | 0.220283E+10 | 0.522124E+09 |
August | 0.212171E+10 | 0.950629E+09 | 0.117108E+10 | 0.269831E+10 | 0.575795E+09 |
September | 0.246060E+10 | 0.145227E+10 | 0.100834E+10 | 0.307358E+10 | 0.733115E+09 |
October | 0.169659E+10 | 0.978133E+09 | 0.718459E+09 | 0.188908E+10 | 0.101124E+10 |
November | 0.118565E+10 | 0.721021E+09 | 0.464633E+09 | 0.119448E+10 | 0.119935E+10 |
December | 0.972235E+09 | 0.623425E+09 | 0.348810E+09 | 0.942427E+09 | 0.153798E+10 |
Annual Sum or Average | 0.197895E+11 | 0.935446E+10 | 0.104350E+11 | 0.221133E+11 | 0.114337E+11 |
Minimum of Months | 0.972235E+09 | 0.305385E+09 | 0.348810E+09 | 0.884359E+09 | 0.522124E+09 |
Maximum of Months | 0.246060E+10 | 0.145227E+10 | 0.124759E+10 | 0.307358E+10 | 0.153798E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397210E+10 | 0.257218E+10 | 0.139992E+10 | 0.392299E+10 | 0.394171E+10 |
February | 0.435350E+10 | 0.265336E+10 | 0.170014E+10 | 0.441584E+10 | 0.345132E+10 |
March | 0.297490E+10 | 0.859945E+09 | 0.211495E+10 | 0.244226E+10 | 0.318986E+10 |
April | 0.590163E+10 | 0.261502E+10 | 0.328662E+10 | 0.673810E+10 | 0.261987E+10 |
May | 0.511242E+10 | 0.165614E+10 | 0.345628E+10 | 0.544141E+10 | 0.232338E+10 |
June | 0.456706E+10 | 0.110454E+10 | 0.346252E+10 | 0.510986E+10 | 0.168873E+10 |
July | 0.508687E+10 | 0.157374E+10 | 0.351313E+10 | 0.610176E+10 | 0.161079E+10 |
August | 0.597459E+10 | 0.267691E+10 | 0.329768E+10 | 0.750276E+10 | 0.178824E+10 |
September | 0.692890E+10 | 0.408949E+10 | 0.283941E+10 | 0.856885E+10 | 0.223734E+10 |
October | 0.477749E+10 | 0.275436E+10 | 0.202313E+10 | 0.526056E+10 | 0.300582E+10 |
November | 0.333872E+10 | 0.203035E+10 | 0.130838E+10 | 0.332300E+10 | 0.350457E+10 |
December | 0.273775E+10 | 0.175552E+10 | 0.982227E+09 | 0.262408E+10 | 0.443372E+10 |
Annual Sum or Average | 0.557259E+11 | 0.263415E+11 | 0.293844E+11 | 0.614515E+11 | 0.337953E+11 |
Minimum of Months | 0.273775E+10 | 0.859945E+09 | 0.982227E+09 | 0.244226E+10 | 0.161079E+10 |
Maximum of Months | 0.692890E+10 | 0.408949E+10 | 0.351313E+10 | 0.856885E+10 | 0.443372E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515998E+10 | 0.334141E+10 | 0.181858E+10 | 0.515206E+10 | 0.544939E+10 |
February | 0.565545E+10 | 0.344687E+10 | 0.220858E+10 | 0.580754E+10 | 0.475223E+10 |
March | 0.386456E+10 | 0.111712E+10 | 0.274744E+10 | 0.317968E+10 | 0.445835E+10 |
April | 0.766656E+10 | 0.339706E+10 | 0.426950E+10 | 0.889928E+10 | 0.360149E+10 |
May | 0.664133E+10 | 0.215142E+10 | 0.448991E+10 | 0.715631E+10 | 0.323436E+10 |
June | 0.593287E+10 | 0.143486E+10 | 0.449801E+10 | 0.669831E+10 | 0.236753E+10 |
July | 0.660813E+10 | 0.204438E+10 | 0.456376E+10 | 0.802197E+10 | 0.224817E+10 |
August | 0.776133E+10 | 0.347745E+10 | 0.428388E+10 | 0.990372E+10 | 0.246033E+10 |
September | 0.900103E+10 | 0.531248E+10 | 0.368855E+10 | 0.113150E+11 | 0.305399E+10 |
October | 0.620623E+10 | 0.357807E+10 | 0.262816E+10 | 0.692544E+10 | 0.417848E+10 |
November | 0.433719E+10 | 0.263754E+10 | 0.169966E+10 | 0.435628E+10 | 0.487592E+10 |
December | 0.355649E+10 | 0.228052E+10 | 0.127597E+10 | 0.343355E+10 | 0.613885E+10 |
Annual Sum or Average | 0.723912E+11 | 0.342192E+11 | 0.381720E+11 | 0.808492E+11 | 0.468191E+11 |
Minimum of Months | 0.355649E+10 | 0.111712E+10 | 0.127597E+10 | 0.317968E+10 | 0.224817E+10 |
Maximum of Months | 0.900103E+10 | 0.531248E+10 | 0.456376E+10 | 0.113150E+11 | 0.613885E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.283635E+09 | 0.268595E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.317072E+09 | 0.236572E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.176643E+09 | 0.218352E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.480134E+09 | 0.176974E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.383924E+09 | 0.158555E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.359359E+09 | 0.111907E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.432304E+09 | 0.104160E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.535393E+09 | 0.112213E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.612924E+09 | 0.143671E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.377852E+09 | 0.199826E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.239301E+09 | 0.236306E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.189571E+09 | 0.304369E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.438811E+10 | 0.227150E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.176643E+09 | 0.104160E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.612924E+09 | 0.304369E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.109855E+09 | 0.541701E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.229426E+09 | 0.464261E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.186277E+09 | 0.409092E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.695881E+09 | 0.321519E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.839658E+09 | 0.281029E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.953964E+09 | 0.200155E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.104948E+10 | 0.187005E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.888419E+09 | 0.204639E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.659254E+09 | 0.268049E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.284398E+09 | 0.382354E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.102183E+09 | 0.465178E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 33507816.52 | 0.605639E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.603230E+10 | 0.433062E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 33507816.52 | 0.187005E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.104948E+10 | 0.605639E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 4852280.63 | 0.298478E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 12269747.08 | 0.254056E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 40916345.56 | 0.225787E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.114142E+09 | 0.172640E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.146918E+09 | 0.143060E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.200330E+09 | 0.103681E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.207528E+09 | 98742393.61 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.160872E+09 | 0.110941E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.103800E+09 | 0.147152E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 41283438.07 | 0.206314E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 7369570.34 | 0.251180E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 433793.31 | 0.325753E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.104072E+10 | 0.233778E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 433793.31 | 98742393.61 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.207528E+09 | 0.325753E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.116720E+09 | 0.535299E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.238138E+09 | 0.458139E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.191104E+09 | 0.406353E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.704910E+09 | 0.319060E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.841942E+09 | 0.281132E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.948914E+09 | 0.202999E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103623E+10 | 0.193401E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.881731E+09 | 0.211904E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.664803E+09 | 0.267936E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.293784E+09 | 0.377290E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.108378E+09 | 0.459513E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 36550158.49 | 0.600586E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.606320E+10 | 0.431361E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 36550158.49 | 0.193401E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103623E+10 | 0.600586E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223073E+09 | 0.144453E+09 | 78619531.41 | 0.208436E+09 | 0.269521E+09 |
February | 0.244492E+09 | 0.149012E+09 | 95480078.80 | 0.235835E+09 | 0.237901E+09 |
March | 0.167070E+09 | 48294353.64 | 0.118776E+09 | 0.125838E+09 | 0.210505E+09 |
April | 0.331436E+09 | 0.146859E+09 | 0.184577E+09 | 0.353377E+09 | 0.193730E+09 |
May | 0.287114E+09 | 93008268.71 | 0.194106E+09 | 0.274319E+09 | 0.180317E+09 |
June | 0.256487E+09 | 62030643.78 | 0.194456E+09 | 0.253544E+09 | 0.135193E+09 |
July | 0.285680E+09 | 88380901.82 | 0.197299E+09 | 0.310615E+09 | 0.129200E+09 |
August | 0.335533E+09 | 0.150335E+09 | 0.185199E+09 | 0.395010E+09 | 0.139589E+09 |
September | 0.389127E+09 | 0.229665E+09 | 0.159462E+09 | 0.458939E+09 | 0.168775E+09 |
October | 0.268304E+09 | 0.154684E+09 | 0.113619E+09 | 0.277761E+09 | 0.224991E+09 |
November | 0.187502E+09 | 0.114024E+09 | 73478494.01 | 0.175106E+09 | 0.249588E+09 |
December | 0.153752E+09 | 98589840.04 | 55161885.59 | 0.148825E+09 | 0.250406E+09 |
Annual Sum or Average | 0.312957E+10 | 0.147934E+10 | 0.165023E+10 | 0.321760E+10 | 0.238972E+10 |
Minimum of Months | 0.153752E+09 | 48294353.64 | 55161885.59 | 0.125838E+09 | 0.129200E+09 |
Maximum of Months | 0.389127E+09 | 0.229665E+09 | 0.197299E+09 | 0.458939E+09 | 0.269521E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39098135.84 | 0.00 | 39098135.84 | 2857231.22 | 0.251012E+09 |
February | 55145008.79 | 0.00 | 55145008.79 | 8074971.03 | 0.211185E+09 |
March | 84495288.28 | 571.09 | 84494717.18 | 29762872.92 | 0.188605E+09 |
April | 0.133615E+09 | 888034.53 | 0.132727E+09 | 95079836.81 | 0.138161E+09 |
May | 0.172620E+09 | 8802627.26 | 0.163817E+09 | 0.124063E+09 | 0.113912E+09 |
June | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.170391E+09 | 80615112.74 |
July | 0.180813E+09 | 10634633.66 | 0.170179E+09 | 0.179265E+09 | 75333642.32 |
August | 0.142358E+09 | 2662252.34 | 0.139696E+09 | 0.139666E+09 | 84039387.96 |
September | 0.104495E+09 | 61759.92 | 0.104433E+09 | 88903551.05 | 0.114633E+09 |
October | 69137333.33 | 0.00 | 69137333.33 | 32417733.51 | 0.170861E+09 |
November | 40201192.52 | 0.00 | 40201192.52 | 4605300.50 | 0.212207E+09 |
December | 28289467.61 | 0.00 | 28289467.61 | 96993.49 | 0.276019E+09 |
Annual Sum or Average | 0.123430E+10 | 34561329.80 | 0.119974E+10 | 0.875184E+09 | 0.191659E+10 |
Minimum of Months | 28289467.61 | 0.00 | 28289467.61 | 96993.49 | 75333642.32 |
Maximum of Months | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.179265E+09 | 0.276019E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185446E+09 | 73858251.45 | 0.111587E+09 | 0.106488E+09 | 0.533408E+09 |
February | 0.252944E+09 | 94250751.19 | 0.158693E+09 | 0.164440E+09 | 0.454354E+09 |
March | 0.290958E+09 | 57386715.51 | 0.233571E+09 | 0.182939E+09 | 0.404963E+09 |
April | 0.754324E+09 | 0.353674E+09 | 0.400650E+09 | 0.802552E+09 | 0.307770E+09 |
May | 0.820699E+09 | 0.357967E+09 | 0.462732E+09 | 0.851733E+09 | 0.272135E+09 |
June | 0.785919E+09 | 0.313959E+09 | 0.471960E+09 | 0.876260E+09 | 0.193931E+09 |
July | 0.828856E+09 | 0.352075E+09 | 0.476782E+09 | 0.967527E+09 | 0.179956E+09 |
August | 0.787372E+09 | 0.376942E+09 | 0.410430E+09 | 0.941197E+09 | 0.195043E+09 |
September | 0.684094E+09 | 0.363500E+09 | 0.320594E+09 | 0.785445E+09 | 0.257275E+09 |
October | 0.343823E+09 | 0.143781E+09 | 0.200042E+09 | 0.309083E+09 | 0.375206E+09 |
November | 0.172200E+09 | 58593481.72 | 0.113606E+09 | 98281257.25 | 0.454485E+09 |
December | 0.132354E+09 | 49526930.11 | 82827209.84 | 65094161.92 | 0.587789E+09 |
Annual Sum or Average | 0.603899E+10 | 0.259551E+10 | 0.344347E+10 | 0.615104E+10 | 0.421631E+10 |
Minimum of Months | 0.132354E+09 | 49526930.11 | 82827209.84 | 65094161.92 | 0.179956E+09 |
Maximum of Months | 0.828856E+09 | 0.376942E+09 | 0.476782E+09 | 0.967527E+09 | 0.587789E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.283110E+09 | 0.268197E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.316906E+09 | 0.235548E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.175571E+09 | 0.217865E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.475786E+09 | 0.176521E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.380538E+09 | 0.157292E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.357953E+09 | 0.110019E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.430664E+09 | 0.102379E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.533084E+09 | 0.111132E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.609520E+09 | 0.143242E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.376105E+09 | 0.199379E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.238850E+09 | 0.235907E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.188769E+09 | 0.304744E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.436686E+10 | 0.226222E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.175571E+09 | 0.102379E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.609520E+09 | 0.304744E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 4419138.61 | 0.297880E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 11562371.45 | 0.252500E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 39852167.05 | 0.225349E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.109321E+09 | 0.172442E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.144103E+09 | 0.141766E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.200434E+09 | 0.101455E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.209333E+09 | 95434039.39 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.159878E+09 | 0.107792E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 99891582.86 | 0.145957E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 39370703.49 | 0.205911E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 6935698.58 | 0.250506E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 344011.52 | 0.325875E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.102544E+10 | 0.232287E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 344011.52 | 95434039.39 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.209333E+09 | 0.325875E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185446E+09 | 73858251.45 | 0.111587E+09 | 0.110864E+09 | 0.524093E+09 |
February | 0.252944E+09 | 94250751.19 | 0.158693E+09 | 0.170842E+09 | 0.445638E+09 |
March | 0.290958E+09 | 57386715.51 | 0.233571E+09 | 0.187324E+09 | 0.401842E+09 |
April | 0.754324E+09 | 0.353674E+09 | 0.400650E+09 | 0.810519E+09 | 0.304916E+09 |
May | 0.820699E+09 | 0.357967E+09 | 0.462732E+09 | 0.855482E+09 | 0.271539E+09 |
June | 0.785919E+09 | 0.313959E+09 | 0.471960E+09 | 0.874791E+09 | 0.195799E+09 |
July | 0.828856E+09 | 0.352075E+09 | 0.476782E+09 | 0.963388E+09 | 0.184365E+09 |
August | 0.787372E+09 | 0.376942E+09 | 0.410430E+09 | 0.939963E+09 | 0.200070E+09 |
September | 0.684094E+09 | 0.363500E+09 | 0.320594E+09 | 0.791367E+09 | 0.255959E+09 |
October | 0.343823E+09 | 0.143781E+09 | 0.200042E+09 | 0.317586E+09 | 0.369619E+09 |
November | 0.172200E+09 | 58593481.72 | 0.113606E+09 | 0.102869E+09 | 0.446845E+09 |
December | 0.132354E+09 | 49526930.11 | 82827209.84 | 67157667.53 | 0.580615E+09 |
Annual Sum or Average | 0.603899E+10 | 0.259551E+10 | 0.344347E+10 | 0.619215E+10 | 0.418130E+10 |
Minimum of Months | 0.132354E+09 | 49526930.11 | 82827209.84 | 67157667.53 | 0.184365E+09 |
Maximum of Months | 0.828856E+09 | 0.376942E+09 | 0.476782E+09 | 0.963388E+09 | 0.580615E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61885949.27 | 0.00 | 61885949.27 | 4058066.41 | 0.406282E+09 |
February | 87285522.53 | 0.00 | 87285522.53 | 11519945.56 | 0.340613E+09 |
March | 0.133742E+09 | 903.95 | 0.133741E+09 | 47664805.19 | 0.300523E+09 |
April | 0.211490E+09 | 1405613.30 | 0.210085E+09 | 0.148635E+09 | 0.226841E+09 |
May | 0.273229E+09 | 13933118.10 | 0.259296E+09 | 0.193661E+09 | 0.189969E+09 |
June | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.265482E+09 | 0.139040E+09 |
July | 0.286198E+09 | 16832884.36 | 0.269365E+09 | 0.277978E+09 | 0.131606E+09 |
August | 0.225330E+09 | 4213909.69 | 0.221116E+09 | 0.213850E+09 | 0.148430E+09 |
September | 0.165399E+09 | 97755.85 | 0.165301E+09 | 0.133612E+09 | 0.199374E+09 |
October | 0.109433E+09 | 0.00 | 0.109433E+09 | 49076253.80 | 0.278140E+09 |
November | 63631907.44 | 0.00 | 63631907.44 | 6821647.51 | 0.341239E+09 |
December | 44777596.68 | 0.00 | 44777596.68 | 95816.97 | 0.447165E+09 |
Annual Sum or Average | 0.195370E+10 | 54704927.91 | 0.189899E+10 | 0.135245E+10 | 0.314922E+10 |
Minimum of Months | 44777596.68 | 0.00 | 44777596.68 | 95816.97 | 0.131606E+09 |
Maximum of Months | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.277978E+09 | 0.447165E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 22813723.39 | 0.00 | 22813723.39 | 1495971.31 | 0.149773E+09 |
February | 32177057.81 | 0.00 | 32177057.81 | 4246728.94 | 0.125564E+09 |
March | 49302916.72 | 333.23 | 49302583.49 | 17571220.84 | 0.110785E+09 |
April | 77964135.71 | 518167.26 | 77445968.45 | 54793061.04 | 83622959.89 |
May | 0.100723E+09 | 5136324.26 | 95587169.75 | 71391469.27 | 70030603.37 |
June | 0.107383E+09 | 6716920.21 | 0.100666E+09 | 97867640.07 | 51256079.95 |
July | 0.105504E+09 | 6205298.17 | 99299092.38 | 0.102474E+09 | 48515482.52 |
August | 83065992.48 | 1553421.60 | 81512570.89 | 78834006.30 | 54717602.49 |
September | 60972753.66 | 36036.85 | 60936716.80 | 49254839.47 | 73497472.65 |
October | 40341565.27 | 0.00 | 40341565.27 | 18091539.24 | 0.102534E+09 |
November | 23457355.87 | 0.00 | 23457355.87 | 2514741.74 | 0.125795E+09 |
December | 16506876.23 | 0.00 | 16506876.23 | 35322.10 | 0.164844E+09 |
Annual Sum or Average | 0.720213E+09 | 20166501.58 | 0.700047E+09 | 0.498571E+09 | 0.116093E+10 |
Minimum of Months | 16506876.23 | 0.00 | 16506876.23 | 35322.10 | 48515482.52 |
Maximum of Months | 0.107383E+09 | 6716920.21 | 0.100666E+09 | 0.102474E+09 | 0.164844E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130132E+09 | 84268280.43 | 45863564.89 | 0.131748E+09 | 0.131456E+09 |
February | 0.142627E+09 | 86927885.14 | 55699349.91 | 0.148321E+09 | 0.114647E+09 |
March | 97462209.09 | 28173040.24 | 69289168.85 | 81745707.71 | 0.106149E+09 |
April | 0.193347E+09 | 85671773.91 | 0.107675E+09 | 0.227648E+09 | 84959451.54 |
May | 0.167491E+09 | 54257392.42 | 0.113234E+09 | 0.182412E+09 | 77383312.40 |
June | 0.149624E+09 | 36186255.57 | 0.113438E+09 | 0.170938E+09 | 56100953.11 |
July | 0.166654E+09 | 51557967.26 | 0.115096E+09 | 0.204543E+09 | 53229828.62 |
August | 0.195737E+09 | 87699320.48 | 0.108038E+09 | 0.252314E+09 | 57678043.38 |
September | 0.227001E+09 | 0.133978E+09 | 93023788.67 | 0.288325E+09 | 71947748.45 |
October | 0.156518E+09 | 90236746.51 | 66281111.23 | 0.177445E+09 | 97791507.81 |
November | 0.109382E+09 | 66517073.52 | 42864484.41 | 0.111542E+09 | 0.116041E+09 |
December | 89692753.44 | 57513463.20 | 32179290.24 | 87438838.02 | 0.151330E+09 |
Annual Sum or Average | 0.182567E+10 | 0.862987E+09 | 0.962682E+09 | 0.206442E+10 | 0.111871E+10 |
Minimum of Months | 89692753.44 | 28173040.24 | 32179290.24 | 81745707.71 | 53229828.62 |
Maximum of Months | 0.227001E+09 | 0.133978E+09 | 0.115096E+09 | 0.288325E+09 | 0.151330E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353204E+09 | 0.228721E+09 | 0.124483E+09 | 0.357591E+09 | 0.356798E+09 |
February | 0.387119E+09 | 0.235940E+09 | 0.151179E+09 | 0.402574E+09 | 0.311176E+09 |
March | 0.264532E+09 | 76467393.88 | 0.188065E+09 | 0.221875E+09 | 0.288110E+09 |
April | 0.524783E+09 | 0.232531E+09 | 0.292252E+09 | 0.617884E+09 | 0.230597E+09 |
May | 0.454606E+09 | 0.147266E+09 | 0.307340E+09 | 0.495102E+09 | 0.210034E+09 |
June | 0.406111E+09 | 98216899.36 | 0.307894E+09 | 0.463962E+09 | 0.152269E+09 |
July | 0.452334E+09 | 0.139939E+09 | 0.312395E+09 | 0.555172E+09 | 0.144477E+09 |
August | 0.531270E+09 | 0.238034E+09 | 0.293237E+09 | 0.684833E+09 | 0.156550E+09 |
September | 0.616128E+09 | 0.363643E+09 | 0.252486E+09 | 0.782573E+09 | 0.195281E+09 |
October | 0.424821E+09 | 0.244921E+09 | 0.179900E+09 | 0.481623E+09 | 0.265426E+09 |
November | 0.296884E+09 | 0.180541E+09 | 0.116343E+09 | 0.302747E+09 | 0.314960E+09 |
December | 0.243444E+09 | 0.156103E+09 | 87341175.83 | 0.237327E+09 | 0.410741E+09 |
Annual Sum or Average | 0.495524E+10 | 0.234232E+10 | 0.261292E+10 | 0.560326E+10 | 0.303642E+10 |
Minimum of Months | 0.243444E+09 | 76467393.88 | 87341175.83 | 0.221875E+09 | 0.144477E+09 |
Maximum of Months | 0.616128E+09 | 0.363643E+09 | 0.312395E+09 | 0.782573E+09 | 0.410741E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.284253E+09 | 0.264988E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.316979E+09 | 0.234480E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.176821E+09 | 0.215620E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.476849E+09 | 0.175931E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.380388E+09 | 0.158282E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.355696E+09 | 0.111651E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.428408E+09 | 0.103798E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.531881E+09 | 0.111207E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.609981E+09 | 0.142333E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.377175E+09 | 0.197279E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.239462E+09 | 0.233289E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.189905E+09 | 0.301469E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.436780E+10 | 0.225033E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.176821E+09 | 0.103798E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.609981E+09 | 0.301469E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.110760E+09 | 0.533548E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.229587E+09 | 0.459329E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.186536E+09 | 0.403627E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.689125E+09 | 0.318989E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.830863E+09 | 0.280135E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.944070E+09 | 0.199407E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103968E+10 | 0.186030E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.880676E+09 | 0.202498E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.654714E+09 | 0.265093E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.283597E+09 | 0.376828E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.102862E+09 | 0.458666E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 34097285.60 | 0.598888E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.598656E+10 | 0.428304E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 34097285.60 | 0.186030E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103968E+10 | 0.598888E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 5265217.70 | 0.293834E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 12792940.88 | 0.250934E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 41529800.78 | 0.222628E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.111734E+09 | 0.171590E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.143387E+09 | 0.142941E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.195780E+09 | 0.104053E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.202351E+09 | 99931132.02 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.157538E+09 | 0.111851E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.102776E+09 | 0.146469E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 41894284.15 | 0.202963E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 7902581.55 | 0.247033E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 565244.22 | 0.321653E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.102352E+10 | 0.231588E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 565244.22 | 99931132.02 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.202351E+09 | 0.321653E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.118028E+09 | 0.527407E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.239087E+09 | 0.452936E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.191831E+09 | 0.400772E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.698249E+09 | 0.316723E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.832358E+09 | 0.280915E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.937092E+09 | 0.203662E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.102273E+10 | 0.195229E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.871545E+09 | 0.212821E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.660107E+09 | 0.266204E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.294054E+09 | 0.371284E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.109641E+09 | 0.452894E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 37222758.62 | 0.594303E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.601194E+10 | 0.427515E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 37222758.62 | 0.195229E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.102273E+10 | 0.594303E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409028E+09 | 0.264871E+09 | 0.144158E+09 | 0.403033E+09 | 0.404895E+09 |
February | 0.448303E+09 | 0.273230E+09 | 0.175073E+09 | 0.453536E+09 | 0.357213E+09 |
March | 0.306341E+09 | 88552987.85 | 0.217788E+09 | 0.249792E+09 | 0.325883E+09 |
April | 0.607724E+09 | 0.269282E+09 | 0.338442E+09 | 0.693412E+09 | 0.260572E+09 |
May | 0.526456E+09 | 0.170541E+09 | 0.355915E+09 | 0.556378E+09 | 0.232048E+09 |
June | 0.470297E+09 | 0.113740E+09 | 0.356557E+09 | 0.525508E+09 | 0.161232E+09 |
July | 0.523825E+09 | 0.162056E+09 | 0.361769E+09 | 0.632428E+09 | 0.149360E+09 |
August | 0.615237E+09 | 0.275655E+09 | 0.339582E+09 | 0.780368E+09 | 0.161632E+09 |
September | 0.713507E+09 | 0.421116E+09 | 0.292391E+09 | 0.888683E+09 | 0.211463E+09 |
October | 0.491964E+09 | 0.283631E+09 | 0.208334E+09 | 0.543126E+09 | 0.300125E+09 |
November | 0.343806E+09 | 0.209075E+09 | 0.134731E+09 | 0.340608E+09 | 0.358265E+09 |
December | 0.281921E+09 | 0.180775E+09 | 0.101145E+09 | 0.269248E+09 | 0.461125E+09 |
Annual Sum or Average | 0.573841E+10 | 0.271252E+10 | 0.302588E+10 | 0.633612E+10 | 0.338381E+10 |
Minimum of Months | 0.281921E+09 | 88552987.85 | 0.101145E+09 | 0.249792E+09 | 0.149360E+09 |
Maximum of Months | 0.713507E+09 | 0.421116E+09 | 0.361769E+09 | 0.888683E+09 | 0.461125E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342050E+09 | 0.00 | 0.342050E+09 | 9612593.55 | 0.253612E+10 |
February | 0.482437E+09 | 0.00 | 0.482437E+09 | 32564022.18 | 0.215000E+10 |
March | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.184541E+09 | 0.192229E+10 |
April | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.690241E+09 | 0.141308E+10 |
May | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.892785E+09 | 0.119211E+10 |
June | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.129739E+10 | 0.864700E+09 |
July | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.137911E+10 | 0.809291E+09 |
August | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.106223E+10 | 0.902736E+09 |
September | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.648538E+09 | 0.121577E+10 |
October | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.204326E+09 | 0.178064E+10 |
November | 0.351700E+09 | 0.00 | 0.351700E+09 | 16656208.39 | 0.219667E+10 |
December | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.280553E+10 |
Annual Sum or Average | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.641799E+10 | 0.197889E+11 |
Minimum of Months | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.809291E+09 |
Maximum of Months | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.137911E+10 | 0.280553E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342050E+09 | 0.00 | 0.342050E+09 | 6748476.57 | 0.261521E+10 |
February | 0.482437E+09 | 0.00 | 0.482437E+09 | 25548248.70 | 0.221740E+10 |
March | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.163882E+09 | 0.197968E+10 |
April | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.661407E+09 | 0.144577E+10 |
May | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.857565E+09 | 0.121849E+10 |
June | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.126549E+10 | 0.883596E+09 |
July | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.134878E+10 | 0.827030E+09 |
August | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.103504E+10 | 0.924262E+09 |
September | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.623753E+09 | 0.124451E+10 |
October | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.185046E+09 | 0.183402E+10 |
November | 0.351700E+09 | 0.00 | 0.351700E+09 | 12005933.26 | 0.227064E+10 |
December | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.289226E+10 |
Annual Sum or Average | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.618527E+10 | 0.203529E+11 |
Minimum of Months | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.827030E+09 |
Maximum of Months | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.134878E+10 | 0.289226E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 8321866.75 | 0.295736E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 16842809.08 | 0.255262E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 54081634.03 | 0.227745E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.146328E+09 | 0.177808E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.185319E+09 | 0.158944E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.250291E+09 | 0.117552E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.267512E+09 | 0.111363E+09 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.214193E+09 | 0.118037E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.138741E+09 | 0.150623E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 56868799.82 | 0.210992E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 11903989.55 | 0.255279E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 1567455.37 | 0.333762E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.135197E+10 | 0.241310E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 1567455.37 | 0.111363E+09 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.267512E+09 | 0.333762E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370865E+09 | 0.147706E+09 | 0.223159E+09 | 0.251325E+09 | 0.105360E+10 |
February | 0.505852E+09 | 0.188488E+09 | 0.317364E+09 | 0.373088E+09 | 0.911472E+09 |
March | 0.581875E+09 | 0.114765E+09 | 0.467109E+09 | 0.437726E+09 | 0.822932E+09 |
April | 0.150854E+10 | 0.707297E+09 | 0.801243E+09 | 0.177841E+10 | 0.642022E+09 |
May | 0.164128E+10 | 0.715884E+09 | 0.925398E+09 | 0.187044E+10 | 0.602523E+09 |
June | 0.157173E+10 | 0.627874E+09 | 0.943852E+09 | 0.193909E+10 | 0.446377E+09 |
July | 0.165759E+10 | 0.704099E+09 | 0.953495E+09 | 0.214401E+10 | 0.420125E+09 |
August | 0.157463E+10 | 0.753831E+09 | 0.820802E+09 | 0.209139E+10 | 0.438985E+09 |
September | 0.136809E+10 | 0.726948E+09 | 0.641142E+09 | 0.174857E+10 | 0.542091E+09 |
October | 0.687597E+09 | 0.287541E+09 | 0.400056E+09 | 0.714602E+09 | 0.767860E+09 |
November | 0.344375E+09 | 0.117179E+09 | 0.227196E+09 | 0.233364E+09 | 0.919820E+09 |
December | 0.264689E+09 | 99046826.15 | 0.165643E+09 | 0.150578E+09 | 0.120362E+10 |
Annual Sum or Average | 0.120771E+11 | 0.519066E+10 | 0.688646E+10 | 0.137326E+11 | 0.877143E+10 |
Minimum of Months | 0.264689E+09 | 99046826.15 | 0.165643E+09 | 0.150578E+09 | 0.420125E+09 |
Maximum of Months | 0.165759E+10 | 0.753831E+09 | 0.953495E+09 | 0.214401E+10 | 0.120362E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.299386E+09 | 0.267646E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.334974E+09 | 0.239371E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.196850E+09 | 0.222059E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.521308E+09 | 0.181117E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.425226E+09 | 0.172231E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.408019E+09 | 0.125709E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.486632E+09 | 0.118398E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.588191E+09 | 0.122586E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.657621E+09 | 0.149537E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.405434E+09 | 0.205307E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.252707E+09 | 0.241232E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.197241E+09 | 0.314119E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.477359E+10 | 0.235931E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.196850E+09 | 0.118398E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.657621E+09 | 0.314119E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61885949.27 | 0.00 | 61885949.27 | 3174818.30 | 0.412598E+09 |
February | 87285522.53 | 0.00 | 87285522.53 | 9334313.63 | 0.347057E+09 |
March | 0.133742E+09 | 903.95 | 0.133741E+09 | 43817833.11 | 0.305437E+09 |
April | 0.211490E+09 | 1405613.30 | 0.210085E+09 | 0.138544E+09 | 0.229688E+09 |
May | 0.273229E+09 | 13933118.10 | 0.259296E+09 | 0.182391E+09 | 0.192301E+09 |
June | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.252613E+09 | 0.142265E+09 |
July | 0.286198E+09 | 16832884.36 | 0.269365E+09 | 0.264637E+09 | 0.134643E+09 |
August | 0.225330E+09 | 4213909.69 | 0.221116E+09 | 0.203375E+09 | 0.150466E+09 |
September | 0.165399E+09 | 97755.85 | 0.165301E+09 | 0.126574E+09 | 0.199771E+09 |
October | 0.109433E+09 | 0.00 | 0.109433E+09 | 45187112.78 | 0.281079E+09 |
November | 63631907.44 | 0.00 | 63631907.44 | 5479553.50 | 0.348435E+09 |
December | 44777596.68 | 0.00 | 44777596.68 | 33005.71 | 0.455195E+09 |
Annual Sum or Average | 0.195370E+10 | 54704927.91 | 0.189899E+10 | 0.127516E+10 | 0.319894E+10 |
Minimum of Months | 44777596.68 | 0.00 | 44777596.68 | 33005.71 | 0.134643E+09 |
Maximum of Months | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.264637E+09 | 0.455195E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55369593.29 | 0.00 | 55369593.29 | 2840521.97 | 0.369085E+09 |
February | 78094687.73 | 0.00 | 78094687.73 | 8351445.77 | 0.310512E+09 |
March | 0.119660E+09 | 808.76 | 0.119659E+09 | 39203981.31 | 0.273276E+09 |
April | 0.189221E+09 | 1257607.54 | 0.187964E+09 | 0.123956E+09 | 0.205502E+09 |
May | 0.244459E+09 | 12466013.55 | 0.231993E+09 | 0.163186E+09 | 0.172053E+09 |
June | 0.260622E+09 | 16302167.51 | 0.244320E+09 | 0.226014E+09 | 0.127285E+09 |
July | 0.256062E+09 | 15060445.42 | 0.241002E+09 | 0.236772E+09 | 0.120466E+09 |
August | 0.201604E+09 | 3770200.96 | 0.197833E+09 | 0.181960E+09 | 0.134622E+09 |
September | 0.147983E+09 | 87462.53 | 0.147895E+09 | 0.113246E+09 | 0.178736E+09 |
October | 97910193.05 | 0.00 | 97910193.05 | 40429081.02 | 0.251483E+09 |
November | 56931708.69 | 0.00 | 56931708.69 | 4902577.28 | 0.311727E+09 |
December | 40062685.41 | 0.00 | 40062685.41 | 29530.33 | 0.407219E+09 |
Annual Sum or Average | 0.174798E+10 | 48944706.28 | 0.169904E+10 | 0.114089E+10 | 0.286196E+10 |
Minimum of Months | 40062685.41 | 0.00 | 40062685.41 | 29530.33 | 0.120466E+09 |
Maximum of Months | 0.260622E+09 | 16302167.51 | 0.244320E+09 | 0.236772E+09 | 0.407219E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104120E+10 | 0.674242E+09 | 0.366961E+09 | 0.104133E+10 | 0.106590E+10 |
February | 0.114118E+10 | 0.695522E+09 | 0.445658E+09 | 0.117074E+10 | 0.933224E+09 |
March | 0.779808E+09 | 0.225416E+09 | 0.554392E+09 | 0.637602E+09 | 0.863737E+09 |
April | 0.154699E+10 | 0.685472E+09 | 0.861523E+09 | 0.178773E+10 | 0.689568E+09 |
May | 0.134012E+10 | 0.434121E+09 | 0.906000E+09 | 0.142538E+10 | 0.629449E+09 |
June | 0.119717E+10 | 0.289531E+09 | 0.907634E+09 | 0.133009E+10 | 0.461180E+09 |
July | 0.133342E+10 | 0.412522E+09 | 0.920901E+09 | 0.159653E+10 | 0.437635E+09 |
August | 0.156612E+10 | 0.701694E+09 | 0.864425E+09 | 0.198401E+10 | 0.468975E+09 |
September | 0.181627E+10 | 0.107197E+10 | 0.744296E+09 | 0.227947E+10 | 0.578478E+09 |
October | 0.125232E+10 | 0.721997E+09 | 0.530324E+09 | 0.140263E+10 | 0.792438E+09 |
November | 0.875177E+09 | 0.532212E+09 | 0.342965E+09 | 0.879887E+09 | 0.948176E+09 |
December | 0.717644E+09 | 0.460173E+09 | 0.257471E+09 | 0.691058E+09 | 0.123398E+10 |
Annual Sum or Average | 0.146074E+11 | 0.690488E+10 | 0.770255E+10 | 0.162265E+11 | 0.910274E+10 |
Minimum of Months | 0.717644E+09 | 0.225416E+09 | 0.257471E+09 | 0.637602E+09 | 0.437635E+09 |
Maximum of Months | 0.181627E+10 | 0.107197E+10 | 0.920901E+09 | 0.227947E+10 | 0.123398E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 526.17 | 508.85 | 526.65 | 341.04 | 185.61 | 0.00 | 0.00 |
February | 655.27 | 491.66 | 639.06 | 389.50 | 249.57 | 0.00 | 0.00 |
March | 330.18 | 409.91 | 394.43 | 114.02 | 280.42 | 0.00 | 0.00 |
April | 934.10 | 339.58 | 808.56 | 358.28 | 450.29 | 0.00 | 0.00 |
May | 733.03 | 288.99 | 677.84 | 219.58 | 458.26 | 0.00 | 0.00 |
June | 713.41 | 212.04 | 625.72 | 151.33 | 474.39 | 0.00 | 0.00 |
July | 822.44 | 194.94 | 674.45 | 208.66 | 465.80 | 0.00 | 0.00 |
August | 1007.43 | 214.98 | 792.15 | 354.92 | 437.23 | 0.00 | 0.00 |
September | 1185.80 | 282.84 | 949.31 | 560.29 | 389.02 | 0.00 | 0.00 |
October | 705.30 | 377.55 | 633.43 | 365.19 | 268.24 | 0.00 | 0.00 |
November | 460.83 | 462.71 | 457.43 | 278.17 | 179.26 | 0.00 | 0.00 |
December | 351.86 | 574.22 | 362.99 | 232.76 | 130.23 | 0.00 | 0.00 |
Annual Sum or Average | 701.21 | 362.56 | 627.52 | 296.63 | 330.89 | 0.00 | 0.00 |
Minimum of Months | 330.18 | 194.94 | 362.99 | 114.02 | 130.23 | 0.00 | 0.00 |
Maximum of Months | 1185.80 | 574.22 | 949.31 | 560.29 | 474.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1464.68 | 1471.67 | 1483.01 | 960.34 | 522.67 | 0.00 | 0.00 |
February | 1825.33 | 1426.64 | 1799.56 | 1096.79 | 702.77 | 0.00 | 0.00 |
March | 911.84 | 1190.96 | 1110.70 | 321.07 | 789.63 | 0.00 | 0.00 |
April | 2599.58 | 1010.75 | 2276.87 | 1008.88 | 1267.98 | 0.00 | 0.00 |
May | 2031.59 | 867.45 | 1908.76 | 618.33 | 1290.43 | 0.00 | 0.00 |
June | 1971.40 | 651.52 | 1761.98 | 426.13 | 1335.85 | 0.00 | 0.00 |
July | 2278.14 | 601.40 | 1899.22 | 587.57 | 1311.65 | 0.00 | 0.00 |
August | 2801.21 | 667.65 | 2230.66 | 999.44 | 1231.21 | 0.00 | 0.00 |
September | 3305.88 | 863.17 | 2673.19 | 1577.74 | 1095.45 | 0.00 | 0.00 |
October | 1964.07 | 1122.25 | 1783.71 | 1028.36 | 755.35 | 0.00 | 0.00 |
November | 1282.02 | 1352.07 | 1288.09 | 783.31 | 504.77 | 0.00 | 0.00 |
December | 979.72 | 1655.36 | 1022.16 | 655.44 | 366.72 | 0.00 | 0.00 |
Annual Sum or Average | 1948.61 | 1071.64 | 1767.06 | 835.28 | 931.77 | 0.00 | 0.00 |
Minimum of Months | 911.84 | 601.40 | 1022.16 | 321.07 | 366.72 | 0.00 | 0.00 |
Maximum of Months | 3305.88 | 1655.36 | 2673.19 | 1577.74 | 1335.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1923.56 | 2034.57 | 1926.52 | 1247.54 | 678.98 | 0.00 | 0.00 |
February | 2400.60 | 1964.38 | 2337.73 | 1424.80 | 912.94 | 0.00 | 0.00 |
March | 1187.16 | 1664.56 | 1442.86 | 417.08 | 1025.78 | 0.00 | 0.00 |
April | 3433.36 | 1389.46 | 2957.78 | 1310.59 | 1647.18 | 0.00 | 0.00 |
May | 2671.86 | 1207.57 | 2479.59 | 803.25 | 1676.34 | 0.00 | 0.00 |
June | 2584.23 | 913.40 | 2288.91 | 553.57 | 1735.34 | 0.00 | 0.00 |
July | 2995.06 | 839.37 | 2467.19 | 763.28 | 1703.91 | 0.00 | 0.00 |
August | 3697.62 | 918.58 | 2897.75 | 1298.33 | 1599.42 | 0.00 | 0.00 |
September | 4365.36 | 1178.24 | 3472.62 | 2049.57 | 1423.05 | 0.00 | 0.00 |
October | 2585.66 | 1560.07 | 2317.14 | 1335.90 | 981.24 | 0.00 | 0.00 |
November | 1680.66 | 1881.14 | 1673.30 | 1017.57 | 655.73 | 0.00 | 0.00 |
December | 1281.94 | 2291.98 | 1327.84 | 851.45 | 476.39 | 0.00 | 0.00 |
Annual Sum or Average | 2563.71 | 1484.62 | 2295.51 | 1085.08 | 1210.43 | 0.00 | 0.00 |
Minimum of Months | 1187.16 | 839.37 | 1327.84 | 417.08 | 476.39 | 0.00 | 0.00 |
Maximum of Months | 4365.36 | 2291.98 | 3472.62 | 2049.57 | 1735.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.43 | 293.05 | 172.39 | 89.80 | 82.59 | 0.00 | 0.00 |
February | 221.07 | 284.86 | 247.10 | 128.41 | 118.69 | 0.00 | 0.00 |
March | 133.54 | 232.31 | 186.61 | 43.43 | 143.18 | 0.00 | 0.00 |
April | 451.61 | 190.22 | 415.69 | 172.27 | 243.43 | 0.00 | 0.00 |
May | 454.26 | 161.55 | 434.22 | 165.50 | 268.72 | 0.00 | 0.00 |
June | 505.48 | 119.19 | 447.82 | 163.35 | 284.47 | 0.00 | 0.00 |
July | 551.98 | 107.45 | 463.23 | 186.57 | 276.67 | 0.00 | 0.00 |
August | 530.68 | 117.39 | 434.22 | 190.43 | 243.79 | 0.00 | 0.00 |
September | 489.29 | 157.32 | 412.02 | 212.18 | 199.84 | 0.00 | 0.00 |
October | 244.86 | 214.97 | 244.82 | 115.63 | 129.18 | 0.00 | 0.00 |
November | 126.44 | 265.33 | 154.96 | 74.03 | 80.92 | 0.00 | 0.00 |
December | 74.86 | 331.33 | 107.74 | 53.33 | 54.40 | 0.00 | 0.00 |
Annual Sum or Average | 326.93 | 205.85 | 310.06 | 132.70 | 177.36 | 0.00 | 0.00 |
Minimum of Months | 74.86 | 107.45 | 107.74 | 43.43 | 54.40 | 0.00 | 0.00 |
Maximum of Months | 551.98 | 331.33 | 463.23 | 212.18 | 284.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.66 | 307.57 | 86.50 | 22.37 | 64.13 | 0.00 | 0.00 |
February | 100.60 | 291.48 | 149.24 | 51.40 | 97.84 | 0.00 | 0.00 |
March | 84.60 | 233.99 | 148.05 | 20.89 | 127.16 | 0.00 | 0.00 |
April | 314.35 | 188.05 | 320.25 | 101.86 | 218.39 | 0.00 | 0.00 |
May | 367.30 | 156.48 | 380.75 | 126.19 | 254.56 | 0.00 | 0.00 |
June | 441.41 | 116.35 | 412.84 | 138.98 | 273.86 | 0.00 | 0.00 |
July | 462.61 | 107.31 | 414.25 | 150.27 | 263.98 | 0.00 | 0.00 |
August | 388.17 | 119.44 | 344.03 | 121.50 | 222.53 | 0.00 | 0.00 |
September | 295.19 | 158.80 | 274.71 | 101.43 | 173.28 | 0.00 | 0.00 |
October | 123.77 | 216.56 | 151.84 | 43.43 | 108.41 | 0.00 | 0.00 |
November | 43.01 | 272.54 | 83.90 | 19.04 | 64.86 | 0.00 | 0.00 |
December | 12.58 | 344.62 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Annual Sum or Average | 223.39 | 209.04 | 234.91 | 75.42 | 159.49 | 0.00 | 0.00 |
Minimum of Months | 12.58 | 107.31 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Maximum of Months | 462.61 | 344.62 | 414.25 | 150.27 | 273.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 77.82 | 100.63 | 83.29 | 53.93 | 29.35 | 0.00 | 0.00 |
February | 97.48 | 98.34 | 101.06 | 61.60 | 39.47 | 0.00 | 0.00 |
March | 46.98 | 78.59 | 62.38 | 18.03 | 44.35 | 0.00 | 0.00 |
April | 136.33 | 74.74 | 127.87 | 56.66 | 71.21 | 0.00 | 0.00 |
May | 102.42 | 67.32 | 107.20 | 34.73 | 72.47 | 0.00 | 0.00 |
June | 97.82 | 52.16 | 98.95 | 23.93 | 75.02 | 0.00 | 0.00 |
July | 115.97 | 48.24 | 106.66 | 33.00 | 73.66 | 0.00 | 0.00 |
August | 147.48 | 52.12 | 125.27 | 56.13 | 69.15 | 0.00 | 0.00 |
September | 177.06 | 65.11 | 150.13 | 88.61 | 61.52 | 0.00 | 0.00 |
October | 103.70 | 84.00 | 100.17 | 57.75 | 42.42 | 0.00 | 0.00 |
November | 67.56 | 96.29 | 72.34 | 43.99 | 28.35 | 0.00 | 0.00 |
December | 55.56 | 93.49 | 57.40 | 36.81 | 20.60 | 0.00 | 0.00 |
Annual Sum or Average | 102.03 | 75.78 | 99.24 | 46.91 | 52.33 | 0.00 | 0.00 |
Minimum of Months | 46.98 | 48.24 | 57.40 | 18.03 | 20.60 | 0.00 | 0.00 |
Maximum of Months | 177.06 | 100.63 | 150.13 | 88.61 | 75.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.07 | 93.72 | 14.60 | 0.00 | 14.60 | 0.00 | 0.00 |
February | 3.34 | 87.30 | 22.79 | 0.00 | 22.79 | 0.00 | 0.00 |
March | 11.11 | 70.42 | 31.55 | 0.00 | 31.55 | 0.00 | 0.00 |
April | 36.68 | 53.30 | 51.55 | 0.34 | 51.21 | 0.00 | 0.00 |
May | 46.32 | 42.53 | 64.45 | 3.29 | 61.16 | 0.00 | 0.00 |
June | 65.74 | 31.10 | 71.00 | 4.44 | 66.56 | 0.00 | 0.00 |
July | 66.93 | 28.13 | 67.51 | 3.97 | 63.54 | 0.00 | 0.00 |
August | 52.15 | 31.38 | 53.15 | 0.99 | 52.16 | 0.00 | 0.00 |
September | 34.30 | 44.23 | 40.31 | 0.02 | 40.29 | 0.00 | 0.00 |
October | 12.10 | 63.79 | 25.81 | 0.00 | 25.81 | 0.00 | 0.00 |
November | 1.78 | 81.87 | 15.51 | 0.00 | 15.51 | 0.00 | 0.00 |
December | 0.04 | 103.05 | 10.56 | 0.00 | 10.56 | 0.00 | 0.00 |
Annual Sum or Average | 27.75 | 60.77 | 39.14 | 1.10 | 38.04 | 0.00 | 0.00 |
Minimum of Months | 0.04 | 28.13 | 10.56 | 0.00 | 10.56 | 0.00 | 0.00 |
Maximum of Months | 66.93 | 103.05 | 71.00 | 4.44 | 66.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.65 | 291.48 | 173.37 | 95.00 | 78.36 | 0.00 | 0.00 |
February | 194.43 | 280.64 | 230.91 | 115.97 | 114.94 | 0.00 | 0.00 |
March | 132.14 | 230.82 | 186.62 | 43.97 | 142.65 | 0.00 | 0.00 |
April | 489.00 | 182.66 | 450.89 | 207.29 | 243.60 | 0.00 | 0.00 |
May | 456.30 | 156.55 | 440.44 | 177.06 | 263.37 | 0.00 | 0.00 |
June | 474.18 | 115.29 | 426.93 | 151.05 | 275.88 | 0.00 | 0.00 |
July | 520.17 | 103.56 | 442.81 | 172.70 | 270.11 | 0.00 | 0.00 |
August | 548.15 | 112.03 | 450.59 | 210.91 | 239.69 | 0.00 | 0.00 |
September | 535.56 | 151.90 | 451.62 | 251.02 | 200.60 | 0.00 | 0.00 |
October | 254.41 | 213.12 | 253.61 | 125.89 | 127.72 | 0.00 | 0.00 |
November | 126.96 | 263.25 | 156.88 | 77.60 | 79.27 | 0.00 | 0.00 |
December | 90.90 | 329.35 | 121.19 | 64.51 | 56.67 | 0.00 | 0.00 |
Annual Sum or Average | 330.27 | 202.18 | 315.57 | 140.95 | 174.62 | 0.00 | 0.00 |
Minimum of Months | 90.90 | 103.56 | 121.19 | 43.97 | 56.67 | 0.00 | 0.00 |
Maximum of Months | 548.15 | 329.35 | 451.62 | 251.02 | 275.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 37.73 | 301.58 | 87.48 | 27.58 | 59.91 | 0.00 | 0.00 |
February | 70.91 | 284.09 | 133.05 | 38.96 | 94.09 | 0.00 | 0.00 |
March | 82.55 | 231.90 | 148.06 | 21.43 | 126.63 | 0.00 | 0.00 |
April | 351.29 | 180.57 | 355.45 | 136.88 | 218.57 | 0.00 | 0.00 |
May | 371.08 | 152.19 | 386.96 | 137.76 | 249.21 | 0.00 | 0.00 |
June | 413.60 | 113.45 | 391.95 | 126.68 | 265.27 | 0.00 | 0.00 |
July | 436.65 | 103.27 | 393.83 | 136.41 | 257.42 | 0.00 | 0.00 |
August | 409.59 | 113.90 | 360.40 | 141.98 | 218.42 | 0.00 | 0.00 |
September | 340.36 | 151.57 | 314.31 | 140.27 | 174.04 | 0.00 | 0.00 |
October | 130.51 | 212.11 | 160.63 | 53.68 | 106.95 | 0.00 | 0.00 |
November | 38.82 | 265.50 | 85.82 | 22.61 | 63.21 | 0.00 | 0.00 |
December | 20.47 | 333.72 | 62.62 | 18.49 | 44.12 | 0.00 | 0.00 |
Annual Sum or Average | 225.90 | 203.28 | 240.41 | 83.67 | 156.74 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 103.27 | 62.62 | 18.49 | 44.12 | 0.00 | 0.00 |
Maximum of Months | 436.65 | 333.72 | 393.83 | 141.98 | 265.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 166.98 | 372.11 | 212.08 | 116.86 | 95.22 | 0.00 | 0.00 |
February | 224.86 | 359.34 | 268.36 | 133.46 | 134.90 | 0.00 | 0.00 |
March | 135.40 | 298.45 | 203.49 | 39.07 | 164.43 | 0.00 | 0.00 |
April | 404.31 | 241.14 | 388.73 | 123.51 | 265.22 | 0.00 | 0.00 |
May | 348.08 | 200.55 | 371.88 | 82.36 | 289.52 | 0.00 | 0.00 |
June | 381.45 | 150.13 | 368.22 | 61.47 | 306.74 | 0.00 | 0.00 |
July | 422.39 | 137.77 | 377.35 | 80.10 | 297.25 | 0.00 | 0.00 |
August | 458.14 | 154.81 | 386.58 | 123.77 | 262.81 | 0.00 | 0.00 |
September | 482.73 | 207.39 | 412.62 | 192.03 | 220.58 | 0.00 | 0.00 |
October | 267.99 | 274.58 | 272.97 | 125.13 | 147.83 | 0.00 | 0.00 |
November | 154.52 | 337.55 | 190.34 | 95.32 | 95.02 | 0.00 | 0.00 |
December | 108.12 | 425.17 | 147.26 | 79.76 | 67.50 | 0.00 | 0.00 |
Annual Sum or Average | 296.18 | 262.78 | 299.81 | 104.01 | 195.80 | 0.00 | 0.00 |
Minimum of Months | 108.12 | 137.77 | 147.26 | 39.07 | 67.50 | 0.00 | 0.00 |
Maximum of Months | 482.73 | 425.17 | 412.62 | 192.03 | 306.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 138.23 | 288.88 | 172.39 | 89.80 | 82.59 | 0.00 | 0.00 |
February | 221.28 | 282.14 | 247.10 | 128.41 | 118.69 | 0.00 | 0.00 |
March | 133.73 | 229.27 | 186.61 | 43.43 | 143.18 | 0.00 | 0.00 |
April | 447.69 | 188.79 | 415.69 | 172.27 | 243.43 | 0.00 | 0.00 |
May | 449.57 | 161.03 | 434.22 | 165.50 | 268.72 | 0.00 | 0.00 |
June | 500.19 | 118.74 | 447.82 | 163.35 | 284.47 | 0.00 | 0.00 |
July | 546.80 | 106.89 | 463.23 | 186.57 | 276.67 | 0.00 | 0.00 |
August | 526.43 | 116.16 | 434.22 | 190.43 | 243.79 | 0.00 | 0.00 |
September | 486.43 | 155.69 | 412.02 | 212.18 | 199.84 | 0.00 | 0.00 |
October | 244.42 | 212.06 | 244.82 | 115.63 | 129.18 | 0.00 | 0.00 |
November | 126.93 | 261.82 | 154.96 | 74.03 | 80.92 | 0.00 | 0.00 |
December | 75.43 | 327.95 | 107.74 | 53.33 | 54.40 | 0.00 | 0.00 |
Annual Sum or Average | 324.89 | 203.73 | 310.06 | 132.70 | 177.36 | 0.00 | 0.00 |
Minimum of Months | 75.43 | 106.89 | 107.74 | 43.43 | 54.40 | 0.00 | 0.00 |
Maximum of Months | 546.80 | 327.95 | 463.23 | 212.18 | 284.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.42 | 303.00 | 86.50 | 22.37 | 64.13 | 0.00 | 0.00 |
February | 101.27 | 288.10 | 149.24 | 51.40 | 97.84 | 0.00 | 0.00 |
March | 85.11 | 230.74 | 148.05 | 20.89 | 127.16 | 0.00 | 0.00 |
April | 310.76 | 186.66 | 320.25 | 101.86 | 218.39 | 0.00 | 0.00 |
May | 362.37 | 156.32 | 380.75 | 126.19 | 254.56 | 0.00 | 0.00 |
June | 435.11 | 116.76 | 412.84 | 138.98 | 273.86 | 0.00 | 0.00 |
July | 455.62 | 108.43 | 414.25 | 150.27 | 263.98 | 0.00 | 0.00 |
August | 383.00 | 120.00 | 344.03 | 121.50 | 222.53 | 0.00 | 0.00 |
September | 292.88 | 157.76 | 274.71 | 101.43 | 173.28 | 0.00 | 0.00 |
October | 124.09 | 213.06 | 151.84 | 43.43 | 108.41 | 0.00 | 0.00 |
November | 43.80 | 268.49 | 83.90 | 19.04 | 64.86 | 0.00 | 0.00 |
December | 12.95 | 340.82 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Annual Sum or Average | 221.22 | 207.12 | 234.91 | 75.42 | 159.49 | 0.00 | 0.00 |
Minimum of Months | 12.95 | 108.43 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Maximum of Months | 455.62 | 340.82 | 414.25 | 150.27 | 273.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.48 | 151.17 | 152.71 | 98.89 | 53.82 | 0.00 | 0.00 |
February | 187.47 | 147.66 | 185.31 | 112.94 | 72.37 | 0.00 | 0.00 |
March | 93.26 | 121.67 | 114.37 | 33.06 | 81.31 | 0.00 | 0.00 |
April | 267.52 | 100.53 | 234.46 | 103.89 | 130.57 | 0.00 | 0.00 |
May | 207.73 | 86.64 | 196.56 | 63.67 | 132.88 | 0.00 | 0.00 |
June | 202.74 | 62.20 | 181.44 | 43.88 | 137.56 | 0.00 | 0.00 |
July | 236.12 | 55.76 | 195.57 | 60.50 | 135.07 | 0.00 | 0.00 |
August | 291.36 | 60.35 | 229.70 | 102.92 | 126.79 | 0.00 | 0.00 |
September | 342.86 | 81.58 | 275.27 | 162.47 | 112.81 | 0.00 | 0.00 |
October | 202.78 | 112.05 | 183.68 | 105.90 | 77.78 | 0.00 | 0.00 |
November | 131.41 | 138.22 | 132.64 | 80.66 | 51.98 | 0.00 | 0.00 |
December | 100.53 | 172.16 | 105.26 | 67.49 | 37.76 | 0.00 | 0.00 |
Annual Sum or Average | 200.92 | 107.30 | 181.96 | 86.01 | 95.95 | 0.00 | 0.00 |
Minimum of Months | 93.26 | 55.76 | 105.26 | 33.06 | 37.76 | 0.00 | 0.00 |
Maximum of Months | 342.86 | 172.16 | 275.27 | 162.47 | 137.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.59 | 946.88 | 127.71 | 0.00 | 127.71 | 0.00 | 0.00 |
February | 13.46 | 888.72 | 199.42 | 0.00 | 199.42 | 0.00 | 0.00 |
March | 68.90 | 717.70 | 275.99 | 0.00 | 275.99 | 0.00 | 0.00 |
April | 266.30 | 545.17 | 450.98 | 3.00 | 447.98 | 0.00 | 0.00 |
May | 333.33 | 445.08 | 563.83 | 28.75 | 535.08 | 0.00 | 0.00 |
June | 500.53 | 333.60 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
July | 514.90 | 302.15 | 590.59 | 34.74 | 555.86 | 0.00 | 0.00 |
August | 396.59 | 337.04 | 464.99 | 8.70 | 456.29 | 0.00 | 0.00 |
September | 250.21 | 469.05 | 352.69 | 0.21 | 352.48 | 0.00 | 0.00 |
October | 76.29 | 664.81 | 225.82 | 0.00 | 225.82 | 0.00 | 0.00 |
November | 6.43 | 847.48 | 135.69 | 0.00 | 135.69 | 0.00 | 0.00 |
December | 0.00 | 1047.47 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Annual Sum or Average | 203.51 | 627.50 | 342.41 | 9.59 | 332.82 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 302.15 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Maximum of Months | 514.90 | 1047.47 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.52 | 976.41 | 127.71 | 0.00 | 127.71 | 0.00 | 0.00 |
February | 10.56 | 916.59 | 199.42 | 0.00 | 199.42 | 0.00 | 0.00 |
March | 61.19 | 739.13 | 275.99 | 0.00 | 275.99 | 0.00 | 0.00 |
April | 255.17 | 557.78 | 450.98 | 3.00 | 447.98 | 0.00 | 0.00 |
May | 320.18 | 454.93 | 563.83 | 28.75 | 535.08 | 0.00 | 0.00 |
June | 488.23 | 340.89 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
July | 503.58 | 308.78 | 590.59 | 34.74 | 555.86 | 0.00 | 0.00 |
August | 386.44 | 345.08 | 464.99 | 8.70 | 456.29 | 0.00 | 0.00 |
September | 240.65 | 480.13 | 352.69 | 0.21 | 352.48 | 0.00 | 0.00 |
October | 69.09 | 684.75 | 225.82 | 0.00 | 225.82 | 0.00 | 0.00 |
November | 4.63 | 876.02 | 135.69 | 0.00 | 135.69 | 0.00 | 0.00 |
December | 0.00 | 1079.85 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Annual Sum or Average | 196.13 | 645.39 | 342.41 | 9.59 | 332.82 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 308.78 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Maximum of Months | 503.58 | 1079.85 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.67 | 585.66 | 260.84 | 122.58 | 138.26 | 0.00 | 0.00 |
February | 290.57 | 572.15 | 363.94 | 154.92 | 209.02 | 0.00 | 0.00 |
March | 253.75 | 471.82 | 334.66 | 65.39 | 269.27 | 0.00 | 0.00 |
April | 937.90 | 380.38 | 806.29 | 344.14 | 462.15 | 0.00 | 0.00 |
May | 920.72 | 343.03 | 827.36 | 314.80 | 512.55 | 0.00 | 0.00 |
June | 998.86 | 262.84 | 818.83 | 277.71 | 541.12 | 0.00 | 0.00 |
July | 1079.18 | 239.77 | 836.60 | 309.10 | 527.50 | 0.00 | 0.00 |
August | 1077.94 | 251.26 | 810.95 | 352.86 | 458.09 | 0.00 | 0.00 |
September | 977.64 | 320.75 | 765.89 | 391.27 | 374.63 | 0.00 | 0.00 |
October | 436.27 | 438.97 | 414.22 | 179.56 | 234.66 | 0.00 | 0.00 |
November | 184.96 | 539.26 | 242.69 | 100.21 | 142.48 | 0.00 | 0.00 |
December | 120.32 | 681.14 | 183.79 | 83.00 | 100.79 | 0.00 | 0.00 |
Annual Sum or Average | 623.45 | 423.23 | 555.95 | 224.61 | 331.34 | 0.00 | 0.00 |
Minimum of Months | 120.32 | 239.77 | 183.79 | 65.39 | 100.79 | 0.00 | 0.00 |
Maximum of Months | 1079.18 | 681.14 | 836.60 | 391.27 | 541.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.83 | 662.60 | 432.52 | 251.73 | 180.79 | 0.00 | 0.00 |
February | 476.28 | 642.60 | 540.08 | 287.50 | 252.58 | 0.00 | 0.00 |
March | 265.25 | 534.75 | 385.76 | 84.16 | 301.60 | 0.00 | 0.00 |
April | 790.33 | 433.28 | 751.43 | 265.48 | 485.95 | 0.00 | 0.00 |
May | 654.54 | 364.39 | 693.63 | 171.94 | 521.69 | 0.00 | 0.00 |
June | 690.78 | 274.89 | 674.80 | 125.02 | 549.78 | 0.00 | 0.00 |
July | 777.03 | 252.39 | 700.30 | 165.93 | 534.37 | 0.00 | 0.00 |
August | 882.86 | 279.78 | 744.12 | 264.96 | 479.16 | 0.00 | 0.00 |
September | 970.48 | 367.74 | 821.62 | 413.64 | 407.98 | 0.00 | 0.00 |
October | 550.72 | 489.77 | 544.98 | 269.56 | 275.41 | 0.00 | 0.00 |
November | 329.60 | 606.63 | 384.16 | 205.33 | 178.83 | 0.00 | 0.00 |
December | 237.86 | 762.53 | 299.61 | 171.81 | 127.80 | 0.00 | 0.00 |
Annual Sum or Average | 582.10 | 471.78 | 580.58 | 222.24 | 358.34 | 0.00 | 0.00 |
Minimum of Months | 237.86 | 252.39 | 299.61 | 84.16 | 127.80 | 0.00 | 0.00 |
Maximum of Months | 970.48 | 762.53 | 821.62 | 413.64 | 549.78 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140930E+10 | 0.136292E+10 | 0.141058E+10 | 0.913437E+09 | 0.497142E+09 | 0.00 | 0.00 |
February | 0.158522E+10 | 0.118943E+10 | 0.154602E+10 | 0.942266E+09 | 0.603757E+09 | 0.00 | 0.00 |
March | 0.884359E+09 | 0.109789E+10 | 0.105645E+10 | 0.305385E+09 | 0.751065E+09 | 0.00 | 0.00 |
April | 0.242119E+10 | 0.880194E+09 | 0.209580E+10 | 0.928651E+09 | 0.116715E+10 | 0.00 | 0.00 |
May | 0.196335E+10 | 0.774023E+09 | 0.181553E+10 | 0.588130E+09 | 0.122740E+10 | 0.00 | 0.00 |
June | 0.184917E+10 | 0.549614E+09 | 0.162186E+10 | 0.392246E+09 | 0.122962E+10 | 0.00 | 0.00 |
July | 0.220283E+10 | 0.522124E+09 | 0.180646E+10 | 0.558869E+09 | 0.124759E+10 | 0.00 | 0.00 |
August | 0.269831E+10 | 0.575795E+09 | 0.212171E+10 | 0.950629E+09 | 0.117108E+10 | 0.00 | 0.00 |
September | 0.307358E+10 | 0.733115E+09 | 0.246060E+10 | 0.145227E+10 | 0.100834E+10 | 0.00 | 0.00 |
October | 0.188908E+10 | 0.101124E+10 | 0.169659E+10 | 0.978133E+09 | 0.718459E+09 | 0.00 | 0.00 |
November | 0.119448E+10 | 0.119935E+10 | 0.118565E+10 | 0.721021E+09 | 0.464633E+09 | 0.00 | 0.00 |
December | 0.942427E+09 | 0.153798E+10 | 0.972235E+09 | 0.623425E+09 | 0.348810E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.221133E+11 | 0.114337E+11 | 0.197895E+11 | 0.935446E+10 | 0.104350E+11 | 0.00 | 0.00 |
Minimum of Months | 0.884359E+09 | 0.522124E+09 | 0.972235E+09 | 0.305385E+09 | 0.348810E+09 | 0.00 | 0.00 |
Maximum of Months | 0.307358E+10 | 0.153798E+10 | 0.246060E+10 | 0.145227E+10 | 0.124759E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.392299E+10 | 0.394171E+10 | 0.397210E+10 | 0.257218E+10 | 0.139992E+10 | 0.00 | 0.00 |
February | 0.441584E+10 | 0.345132E+10 | 0.435350E+10 | 0.265336E+10 | 0.170014E+10 | 0.00 | 0.00 |
March | 0.244226E+10 | 0.318986E+10 | 0.297490E+10 | 0.859945E+09 | 0.211495E+10 | 0.00 | 0.00 |
April | 0.673810E+10 | 0.261987E+10 | 0.590163E+10 | 0.261502E+10 | 0.328662E+10 | 0.00 | 0.00 |
May | 0.544141E+10 | 0.232338E+10 | 0.511242E+10 | 0.165614E+10 | 0.345628E+10 | 0.00 | 0.00 |
June | 0.510986E+10 | 0.168873E+10 | 0.456706E+10 | 0.110454E+10 | 0.346252E+10 | 0.00 | 0.00 |
July | 0.610176E+10 | 0.161079E+10 | 0.508687E+10 | 0.157374E+10 | 0.351313E+10 | 0.00 | 0.00 |
August | 0.750276E+10 | 0.178824E+10 | 0.597459E+10 | 0.267691E+10 | 0.329768E+10 | 0.00 | 0.00 |
September | 0.856885E+10 | 0.223734E+10 | 0.692890E+10 | 0.408949E+10 | 0.283941E+10 | 0.00 | 0.00 |
October | 0.526056E+10 | 0.300582E+10 | 0.477749E+10 | 0.275436E+10 | 0.202313E+10 | 0.00 | 0.00 |
November | 0.332300E+10 | 0.350457E+10 | 0.333872E+10 | 0.203035E+10 | 0.130838E+10 | 0.00 | 0.00 |
December | 0.262408E+10 | 0.443372E+10 | 0.273775E+10 | 0.175552E+10 | 0.982227E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.614515E+11 | 0.337953E+11 | 0.557259E+11 | 0.263415E+11 | 0.293844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244226E+10 | 0.161079E+10 | 0.273775E+10 | 0.859945E+09 | 0.982227E+09 | 0.00 | 0.00 |
Maximum of Months | 0.856885E+10 | 0.443372E+10 | 0.692890E+10 | 0.408949E+10 | 0.351313E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515206E+10 | 0.544939E+10 | 0.515998E+10 | 0.334141E+10 | 0.181858E+10 | 0.00 | 0.00 |
February | 0.580754E+10 | 0.475223E+10 | 0.565545E+10 | 0.344687E+10 | 0.220858E+10 | 0.00 | 0.00 |
March | 0.317968E+10 | 0.445835E+10 | 0.386456E+10 | 0.111712E+10 | 0.274744E+10 | 0.00 | 0.00 |
April | 0.889928E+10 | 0.360149E+10 | 0.766656E+10 | 0.339706E+10 | 0.426950E+10 | 0.00 | 0.00 |
May | 0.715631E+10 | 0.323436E+10 | 0.664133E+10 | 0.215142E+10 | 0.448991E+10 | 0.00 | 0.00 |
June | 0.669831E+10 | 0.236753E+10 | 0.593287E+10 | 0.143486E+10 | 0.449801E+10 | 0.00 | 0.00 |
July | 0.802197E+10 | 0.224817E+10 | 0.660813E+10 | 0.204438E+10 | 0.456376E+10 | 0.00 | 0.00 |
August | 0.990372E+10 | 0.246033E+10 | 0.776133E+10 | 0.347745E+10 | 0.428388E+10 | 0.00 | 0.00 |
September | 0.113150E+11 | 0.305399E+10 | 0.900103E+10 | 0.531248E+10 | 0.368855E+10 | 0.00 | 0.00 |
October | 0.692544E+10 | 0.417848E+10 | 0.620623E+10 | 0.357807E+10 | 0.262816E+10 | 0.00 | 0.00 |
November | 0.435628E+10 | 0.487592E+10 | 0.433719E+10 | 0.263754E+10 | 0.169966E+10 | 0.00 | 0.00 |
December | 0.343355E+10 | 0.613885E+10 | 0.355649E+10 | 0.228052E+10 | 0.127597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.808492E+11 | 0.468191E+11 | 0.723912E+11 | 0.342192E+11 | 0.381720E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317968E+10 | 0.224817E+10 | 0.355649E+10 | 0.111712E+10 | 0.127597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113150E+11 | 0.613885E+10 | 0.900103E+10 | 0.531248E+10 | 0.456376E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368088E+09 | 0.784894E+09 | 0.461724E+09 | 0.240525E+09 | 0.221199E+09 | 0.00 | 0.00 |
February | 0.534807E+09 | 0.689142E+09 | 0.597787E+09 | 0.310648E+09 | 0.287140E+09 | 0.00 | 0.00 |
March | 0.357683E+09 | 0.622208E+09 | 0.499814E+09 | 0.116324E+09 | 0.383489E+09 | 0.00 | 0.00 |
April | 0.117056E+10 | 0.493040E+09 | 0.107747E+10 | 0.446512E+09 | 0.630959E+09 | 0.00 | 0.00 |
May | 0.121670E+10 | 0.432699E+09 | 0.116302E+10 | 0.443266E+09 | 0.719753E+09 | 0.00 | 0.00 |
June | 0.131020E+10 | 0.308942E+09 | 0.116075E+10 | 0.423404E+09 | 0.737350E+09 | 0.00 | 0.00 |
July | 0.147842E+10 | 0.287797E+09 | 0.124072E+10 | 0.499696E+09 | 0.741026E+09 | 0.00 | 0.00 |
August | 0.142136E+10 | 0.314404E+09 | 0.116303E+10 | 0.510058E+09 | 0.652968E+09 | 0.00 | 0.00 |
September | 0.126823E+10 | 0.407770E+09 | 0.106795E+10 | 0.549963E+09 | 0.517991E+09 | 0.00 | 0.00 |
October | 0.655845E+09 | 0.575776E+09 | 0.655720E+09 | 0.309712E+09 | 0.346008E+09 | 0.00 | 0.00 |
November | 0.327742E+09 | 0.687741E+09 | 0.401645E+09 | 0.191897E+09 | 0.209748E+09 | 0.00 | 0.00 |
December | 0.200501E+09 | 0.887430E+09 | 0.288559E+09 | 0.142844E+09 | 0.145716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103101E+11 | 0.649184E+10 | 0.977819E+10 | 0.418485E+10 | 0.559335E+10 | 0.00 | 0.00 |
Minimum of Months | 0.200501E+09 | 0.287797E+09 | 0.288559E+09 | 0.116324E+09 | 0.145716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147842E+10 | 0.887430E+09 | 0.124072E+10 | 0.549963E+09 | 0.741026E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111589E+09 | 0.823794E+09 | 0.231694E+09 | 59922886.42 | 0.171771E+09 | 0.00 | 0.00 |
February | 0.243368E+09 | 0.705155E+09 | 0.361033E+09 | 0.124345E+09 | 0.236688E+09 | 0.00 | 0.00 |
March | 0.226597E+09 | 0.626716E+09 | 0.396539E+09 | 55944870.75 | 0.340595E+09 | 0.00 | 0.00 |
April | 0.814784E+09 | 0.487433E+09 | 0.830090E+09 | 0.264012E+09 | 0.566078E+09 | 0.00 | 0.00 |
May | 0.983770E+09 | 0.419103E+09 | 0.101980E+10 | 0.337984E+09 | 0.681816E+09 | 0.00 | 0.00 |
June | 0.114414E+10 | 0.301576E+09 | 0.107009E+10 | 0.360237E+09 | 0.709855E+09 | 0.00 | 0.00 |
July | 0.123904E+10 | 0.287432E+09 | 0.110954E+10 | 0.402490E+09 | 0.707049E+09 | 0.00 | 0.00 |
August | 0.103967E+10 | 0.319910E+09 | 0.921450E+09 | 0.325430E+09 | 0.596020E+09 | 0.00 | 0.00 |
September | 0.765132E+09 | 0.411616E+09 | 0.712050E+09 | 0.262902E+09 | 0.449148E+09 | 0.00 | 0.00 |
October | 0.331494E+09 | 0.580030E+09 | 0.406684E+09 | 0.116318E+09 | 0.290366E+09 | 0.00 | 0.00 |
November | 0.111486E+09 | 0.706431E+09 | 0.217465E+09 | 49338807.43 | 0.168126E+09 | 0.00 | 0.00 |
December | 33682066.43 | 0.923036E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.704475E+10 | 0.659223E+10 | 0.740813E+10 | 0.237851E+10 | 0.502962E+10 | 0.00 | 0.00 |
Minimum of Months | 33682066.43 | 0.287432E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123904E+10 | 0.923036E+09 | 0.110954E+10 | 0.402490E+09 | 0.709855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208436E+09 | 0.269521E+09 | 0.223073E+09 | 0.144453E+09 | 78619531.41 | 0.00 | 0.00 |
February | 0.235835E+09 | 0.237901E+09 | 0.244492E+09 | 0.149012E+09 | 95480078.80 | 0.00 | 0.00 |
March | 0.125838E+09 | 0.210505E+09 | 0.167070E+09 | 48294353.64 | 0.118776E+09 | 0.00 | 0.00 |
April | 0.353377E+09 | 0.193730E+09 | 0.331436E+09 | 0.146859E+09 | 0.184577E+09 | 0.00 | 0.00 |
May | 0.274319E+09 | 0.180317E+09 | 0.287114E+09 | 93008268.71 | 0.194106E+09 | 0.00 | 0.00 |
June | 0.253544E+09 | 0.135193E+09 | 0.256487E+09 | 62030643.78 | 0.194456E+09 | 0.00 | 0.00 |
July | 0.310615E+09 | 0.129200E+09 | 0.285680E+09 | 88380901.82 | 0.197299E+09 | 0.00 | 0.00 |
August | 0.395010E+09 | 0.139589E+09 | 0.335533E+09 | 0.150335E+09 | 0.185199E+09 | 0.00 | 0.00 |
September | 0.458939E+09 | 0.168775E+09 | 0.389127E+09 | 0.229665E+09 | 0.159462E+09 | 0.00 | 0.00 |
October | 0.277761E+09 | 0.224991E+09 | 0.268304E+09 | 0.154684E+09 | 0.113619E+09 | 0.00 | 0.00 |
November | 0.175106E+09 | 0.249588E+09 | 0.187502E+09 | 0.114024E+09 | 73478494.01 | 0.00 | 0.00 |
December | 0.148825E+09 | 0.250406E+09 | 0.153752E+09 | 98589840.04 | 55161885.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.321760E+10 | 0.238972E+10 | 0.312957E+10 | 0.147934E+10 | 0.165023E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125838E+09 | 0.129200E+09 | 0.153752E+09 | 48294353.64 | 55161885.59 | 0.00 | 0.00 |
Maximum of Months | 0.458939E+09 | 0.269521E+09 | 0.389127E+09 | 0.229665E+09 | 0.197299E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2857231.22 | 0.251012E+09 | 39098135.84 | 0.00 | 39098135.84 | 0.00 | 0.00 |
February | 8074971.03 | 0.211185E+09 | 55145008.79 | 0.00 | 55145008.79 | 0.00 | 0.00 |
March | 29762872.92 | 0.188605E+09 | 84495288.28 | 571.09 | 84494717.18 | 0.00 | 0.00 |
April | 95079836.81 | 0.138161E+09 | 0.133615E+09 | 888034.53 | 0.132727E+09 | 0.00 | 0.00 |
May | 0.124063E+09 | 0.113912E+09 | 0.172620E+09 | 8802627.26 | 0.163817E+09 | 0.00 | 0.00 |
June | 0.170391E+09 | 80615112.74 | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.00 | 0.00 |
July | 0.179265E+09 | 75333642.32 | 0.180813E+09 | 10634633.66 | 0.170179E+09 | 0.00 | 0.00 |
August | 0.139666E+09 | 84039387.96 | 0.142358E+09 | 2662252.34 | 0.139696E+09 | 0.00 | 0.00 |
September | 88903551.05 | 0.114633E+09 | 0.104495E+09 | 61759.92 | 0.104433E+09 | 0.00 | 0.00 |
October | 32417733.51 | 0.170861E+09 | 69137333.33 | 0.00 | 69137333.33 | 0.00 | 0.00 |
November | 4605300.50 | 0.212207E+09 | 40201192.52 | 0.00 | 40201192.52 | 0.00 | 0.00 |
December | 96993.49 | 0.276019E+09 | 28289467.61 | 0.00 | 28289467.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.875184E+09 | 0.191659E+10 | 0.123430E+10 | 34561329.80 | 0.119974E+10 | 0.00 | 0.00 |
Minimum of Months | 96993.49 | 75333642.32 | 28289467.61 | 0.00 | 28289467.61 | 0.00 | 0.00 |
Maximum of Months | 0.179265E+09 | 0.276019E+09 | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368681E+09 | 0.780689E+09 | 0.464342E+09 | 0.254460E+09 | 0.209881E+09 | 0.00 | 0.00 |
February | 0.470372E+09 | 0.678928E+09 | 0.558620E+09 | 0.280553E+09 | 0.278067E+09 | 0.00 | 0.00 |
March | 0.353914E+09 | 0.618233E+09 | 0.499837E+09 | 0.117767E+09 | 0.382070E+09 | 0.00 | 0.00 |
April | 0.126750E+10 | 0.473452E+09 | 0.116870E+10 | 0.537284E+09 | 0.631418E+09 | 0.00 | 0.00 |
May | 0.122215E+10 | 0.419304E+09 | 0.117966E+10 | 0.474251E+09 | 0.705413E+09 | 0.00 | 0.00 |
June | 0.122908E+10 | 0.298821E+09 | 0.110659E+10 | 0.391513E+09 | 0.715078E+09 | 0.00 | 0.00 |
July | 0.139323E+10 | 0.277372E+09 | 0.118603E+10 | 0.462573E+09 | 0.723454E+09 | 0.00 | 0.00 |
August | 0.146816E+10 | 0.300058E+09 | 0.120687E+10 | 0.564898E+09 | 0.641975E+09 | 0.00 | 0.00 |
September | 0.138818E+10 | 0.393733E+09 | 0.117060E+10 | 0.650638E+09 | 0.519960E+09 | 0.00 | 0.00 |
October | 0.681418E+09 | 0.570815E+09 | 0.679269E+09 | 0.337174E+09 | 0.342095E+09 | 0.00 | 0.00 |
November | 0.329092E+09 | 0.682351E+09 | 0.406624E+09 | 0.201152E+09 | 0.205473E+09 | 0.00 | 0.00 |
December | 0.243474E+09 | 0.882143E+09 | 0.324582E+09 | 0.172789E+09 | 0.151793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104153E+11 | 0.637590E+10 | 0.995173E+10 | 0.444505E+10 | 0.550668E+10 | 0.00 | 0.00 |
Minimum of Months | 0.243474E+09 | 0.277372E+09 | 0.324582E+09 | 0.117767E+09 | 0.151793E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146816E+10 | 0.882143E+09 | 0.120687E+10 | 0.650638E+09 | 0.723454E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101056E+09 | 0.807747E+09 | 0.234312E+09 | 73858251.45 | 0.160454E+09 | 0.00 | 0.00 |
February | 0.171544E+09 | 0.687278E+09 | 0.321866E+09 | 94250751.19 | 0.227615E+09 | 0.00 | 0.00 |
March | 0.221114E+09 | 0.621129E+09 | 0.396563E+09 | 57387429.28 | 0.339176E+09 | 0.00 | 0.00 |
April | 0.910531E+09 | 0.468050E+09 | 0.921320E+09 | 0.354784E+09 | 0.566537E+09 | 0.00 | 0.00 |
May | 0.993906E+09 | 0.407626E+09 | 0.103645E+10 | 0.368969E+09 | 0.667476E+09 | 0.00 | 0.00 |
June | 0.107204E+10 | 0.294071E+09 | 0.101593E+10 | 0.328347E+09 | 0.687583E+09 | 0.00 | 0.00 |
July | 0.116953E+10 | 0.276607E+09 | 0.105484E+10 | 0.365366E+09 | 0.689477E+09 | 0.00 | 0.00 |
August | 0.109704E+10 | 0.305064E+09 | 0.965296E+09 | 0.380269E+09 | 0.585027E+09 | 0.00 | 0.00 |
September | 0.882212E+09 | 0.392869E+09 | 0.814695E+09 | 0.363577E+09 | 0.451118E+09 | 0.00 | 0.00 |
October | 0.349552E+09 | 0.568125E+09 | 0.430233E+09 | 0.143781E+09 | 0.286452E+09 | 0.00 | 0.00 |
November | 0.100621E+09 | 0.688167E+09 | 0.222445E+09 | 58593481.72 | 0.163851E+09 | 0.00 | 0.00 |
December | 54836138.19 | 0.893825E+09 | 0.167711E+09 | 49526930.11 | 0.118184E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.712399E+10 | 0.641056E+10 | 0.758166E+10 | 0.263871E+10 | 0.494295E+10 | 0.00 | 0.00 |
Minimum of Months | 54836138.19 | 0.276607E+09 | 0.167711E+09 | 49526930.11 | 0.118184E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116953E+10 | 0.893825E+09 | 0.105484E+10 | 0.380269E+09 | 0.689477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.447234E+09 | 0.996650E+09 | 0.568036E+09 | 0.312990E+09 | 0.255046E+09 | 0.00 | 0.00 |
February | 0.543980E+09 | 0.869319E+09 | 0.649209E+09 | 0.322868E+09 | 0.326341E+09 | 0.00 | 0.00 |
March | 0.362657E+09 | 0.799369E+09 | 0.545040E+09 | 0.104642E+09 | 0.440398E+09 | 0.00 | 0.00 |
April | 0.104797E+10 | 0.625028E+09 | 0.100758E+10 | 0.320126E+09 | 0.687458E+09 | 0.00 | 0.00 |
May | 0.932298E+09 | 0.537149E+09 | 0.996049E+09 | 0.220592E+09 | 0.775457E+09 | 0.00 | 0.00 |
June | 0.988717E+09 | 0.389134E+09 | 0.954413E+09 | 0.159341E+09 | 0.795073E+09 | 0.00 | 0.00 |
July | 0.113134E+10 | 0.369002E+09 | 0.101069E+10 | 0.214535E+09 | 0.796155E+09 | 0.00 | 0.00 |
August | 0.122709E+10 | 0.414633E+09 | 0.103540E+10 | 0.331501E+09 | 0.703903E+09 | 0.00 | 0.00 |
September | 0.125122E+10 | 0.537560E+09 | 0.106950E+10 | 0.497754E+09 | 0.571747E+09 | 0.00 | 0.00 |
October | 0.717782E+09 | 0.735437E+09 | 0.731114E+09 | 0.335158E+09 | 0.395956E+09 | 0.00 | 0.00 |
November | 0.400512E+09 | 0.874922E+09 | 0.493355E+09 | 0.247058E+09 | 0.246297E+09 | 0.00 | 0.00 |
December | 0.289595E+09 | 0.113878E+10 | 0.394422E+09 | 0.213617E+09 | 0.180805E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.934040E+10 | 0.828698E+10 | 0.945482E+10 | 0.328018E+10 | 0.617464E+10 | 0.00 | 0.00 |
Minimum of Months | 0.289595E+09 | 0.369002E+09 | 0.394422E+09 | 0.104642E+09 | 0.180805E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125122E+10 | 0.113878E+10 | 0.106950E+10 | 0.497754E+09 | 0.796155E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.370226E+09 | 0.773749E+09 | 0.461724E+09 | 0.240525E+09 | 0.221199E+09 | 0.00 | 0.00 |
February | 0.535309E+09 | 0.682552E+09 | 0.597787E+09 | 0.310648E+09 | 0.287140E+09 | 0.00 | 0.00 |
March | 0.358186E+09 | 0.614077E+09 | 0.499814E+09 | 0.116324E+09 | 0.383489E+09 | 0.00 | 0.00 |
April | 0.116040E+10 | 0.489348E+09 | 0.107747E+10 | 0.446512E+09 | 0.630959E+09 | 0.00 | 0.00 |
May | 0.120413E+10 | 0.431294E+09 | 0.116302E+10 | 0.443266E+09 | 0.719753E+09 | 0.00 | 0.00 |
June | 0.129648E+10 | 0.307774E+09 | 0.116075E+10 | 0.423404E+09 | 0.737350E+09 | 0.00 | 0.00 |
July | 0.146454E+10 | 0.286282E+09 | 0.124072E+10 | 0.499696E+09 | 0.741026E+09 | 0.00 | 0.00 |
August | 0.140998E+10 | 0.311126E+09 | 0.116303E+10 | 0.510058E+09 | 0.652968E+09 | 0.00 | 0.00 |
September | 0.126083E+10 | 0.403561E+09 | 0.106795E+10 | 0.549963E+09 | 0.517991E+09 | 0.00 | 0.00 |
October | 0.654652E+09 | 0.567988E+09 | 0.655720E+09 | 0.309712E+09 | 0.346008E+09 | 0.00 | 0.00 |
November | 0.328998E+09 | 0.678629E+09 | 0.401645E+09 | 0.191897E+09 | 0.209748E+09 | 0.00 | 0.00 |
December | 0.202034E+09 | 0.878388E+09 | 0.288559E+09 | 0.142844E+09 | 0.145716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102458E+11 | 0.642477E+10 | 0.977819E+10 | 0.418485E+10 | 0.559335E+10 | 0.00 | 0.00 |
Minimum of Months | 0.202034E+09 | 0.286282E+09 | 0.288559E+09 | 0.116324E+09 | 0.145716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146454E+10 | 0.878388E+09 | 0.124072E+10 | 0.549963E+09 | 0.741026E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113612E+09 | 0.811559E+09 | 0.231694E+09 | 59922886.42 | 0.171771E+09 | 0.00 | 0.00 |
February | 0.244986E+09 | 0.696977E+09 | 0.361033E+09 | 0.124345E+09 | 0.236688E+09 | 0.00 | 0.00 |
March | 0.227967E+09 | 0.618006E+09 | 0.396539E+09 | 55944870.75 | 0.340595E+09 | 0.00 | 0.00 |
April | 0.805500E+09 | 0.483829E+09 | 0.830090E+09 | 0.264012E+09 | 0.566078E+09 | 0.00 | 0.00 |
May | 0.970582E+09 | 0.418694E+09 | 0.101980E+10 | 0.337984E+09 | 0.681816E+09 | 0.00 | 0.00 |
June | 0.112780E+10 | 0.302642E+09 | 0.107009E+10 | 0.360237E+09 | 0.709855E+09 | 0.00 | 0.00 |
July | 0.122035E+10 | 0.290425E+09 | 0.110954E+10 | 0.402490E+09 | 0.707049E+09 | 0.00 | 0.00 |
August | 0.102582E+10 | 0.321405E+09 | 0.921450E+09 | 0.325430E+09 | 0.596020E+09 | 0.00 | 0.00 |
September | 0.759133E+09 | 0.408923E+09 | 0.712050E+09 | 0.262902E+09 | 0.449148E+09 | 0.00 | 0.00 |
October | 0.332356E+09 | 0.570655E+09 | 0.406684E+09 | 0.116318E+09 | 0.290366E+09 | 0.00 | 0.00 |
November | 0.113541E+09 | 0.695925E+09 | 0.217465E+09 | 49338807.43 | 0.168126E+09 | 0.00 | 0.00 |
December | 34685691.17 | 0.912854E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.697633E+10 | 0.653189E+10 | 0.740813E+10 | 0.237851E+10 | 0.502962E+10 | 0.00 | 0.00 |
Minimum of Months | 34685691.17 | 0.290425E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122035E+10 | 0.912854E+09 | 0.110954E+10 | 0.402490E+09 | 0.709855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403033E+09 | 0.404895E+09 | 0.409028E+09 | 0.264871E+09 | 0.144158E+09 | 0.00 | 0.00 |
February | 0.453536E+09 | 0.357213E+09 | 0.448303E+09 | 0.273230E+09 | 0.175073E+09 | 0.00 | 0.00 |
March | 0.249792E+09 | 0.325883E+09 | 0.306341E+09 | 88552987.85 | 0.217788E+09 | 0.00 | 0.00 |
April | 0.693412E+09 | 0.260572E+09 | 0.607724E+09 | 0.269282E+09 | 0.338442E+09 | 0.00 | 0.00 |
May | 0.556378E+09 | 0.232048E+09 | 0.526456E+09 | 0.170541E+09 | 0.355915E+09 | 0.00 | 0.00 |
June | 0.525508E+09 | 0.161232E+09 | 0.470297E+09 | 0.113740E+09 | 0.356557E+09 | 0.00 | 0.00 |
July | 0.632428E+09 | 0.149360E+09 | 0.523825E+09 | 0.162056E+09 | 0.361769E+09 | 0.00 | 0.00 |
August | 0.780368E+09 | 0.161632E+09 | 0.615237E+09 | 0.275655E+09 | 0.339582E+09 | 0.00 | 0.00 |
September | 0.888683E+09 | 0.211463E+09 | 0.713507E+09 | 0.421116E+09 | 0.292391E+09 | 0.00 | 0.00 |
October | 0.543126E+09 | 0.300125E+09 | 0.491964E+09 | 0.283631E+09 | 0.208334E+09 | 0.00 | 0.00 |
November | 0.340608E+09 | 0.358265E+09 | 0.343806E+09 | 0.209075E+09 | 0.134731E+09 | 0.00 | 0.00 |
December | 0.269248E+09 | 0.461125E+09 | 0.281921E+09 | 0.180775E+09 | 0.101145E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.633612E+10 | 0.338381E+10 | 0.573841E+10 | 0.271252E+10 | 0.302588E+10 | 0.00 | 0.00 |
Minimum of Months | 0.249792E+09 | 0.149360E+09 | 0.281921E+09 | 88552987.85 | 0.101145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.888683E+09 | 0.461125E+09 | 0.713507E+09 | 0.421116E+09 | 0.361769E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9612593.55 | 0.253612E+10 | 0.342050E+09 | 0.00 | 0.342050E+09 | 0.00 | 0.00 |
February | 32564022.18 | 0.215000E+10 | 0.482437E+09 | 0.00 | 0.482437E+09 | 0.00 | 0.00 |
March | 0.184541E+09 | 0.192229E+10 | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.00 | 0.00 |
April | 0.690241E+09 | 0.141308E+10 | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.00 | 0.00 |
May | 0.892785E+09 | 0.119211E+10 | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.00 | 0.00 |
June | 0.129739E+10 | 0.864700E+09 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
July | 0.137911E+10 | 0.809291E+09 | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.00 | 0.00 |
August | 0.106223E+10 | 0.902736E+09 | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.00 | 0.00 |
September | 0.648538E+09 | 0.121577E+10 | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.00 | 0.00 |
October | 0.204326E+09 | 0.178064E+10 | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.00 | 0.00 |
November | 16656208.39 | 0.219667E+10 | 0.351700E+09 | 0.00 | 0.351700E+09 | 0.00 | 0.00 |
December | 0.00 | 0.280553E+10 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.641799E+10 | 0.197889E+11 | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.809291E+09 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137911E+10 | 0.280553E+10 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6748476.57 | 0.261521E+10 | 0.342050E+09 | 0.00 | 0.342050E+09 | 0.00 | 0.00 |
February | 25548248.70 | 0.221740E+10 | 0.482437E+09 | 0.00 | 0.482437E+09 | 0.00 | 0.00 |
March | 0.163882E+09 | 0.197968E+10 | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.00 | 0.00 |
April | 0.661407E+09 | 0.144577E+10 | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.00 | 0.00 |
May | 0.857565E+09 | 0.121849E+10 | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.00 | 0.00 |
June | 0.126549E+10 | 0.883596E+09 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
July | 0.134878E+10 | 0.827030E+09 | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.00 | 0.00 |
August | 0.103504E+10 | 0.924262E+09 | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.00 | 0.00 |
September | 0.623753E+09 | 0.124451E+10 | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.00 | 0.00 |
October | 0.185046E+09 | 0.183402E+10 | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.00 | 0.00 |
November | 12005933.26 | 0.227064E+10 | 0.351700E+09 | 0.00 | 0.351700E+09 | 0.00 | 0.00 |
December | 0.00 | 0.289226E+10 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.618527E+10 | 0.203529E+11 | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.827030E+09 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134878E+10 | 0.289226E+10 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.510682E+09 | 0.156863E+10 | 0.698627E+09 | 0.328308E+09 | 0.370319E+09 | 0.00 | 0.00 |
February | 0.702949E+09 | 0.138415E+10 | 0.880450E+09 | 0.374790E+09 | 0.505660E+09 | 0.00 | 0.00 |
March | 0.679636E+09 | 0.126371E+10 | 0.896359E+09 | 0.175146E+09 | 0.721213E+09 | 0.00 | 0.00 |
April | 0.243104E+10 | 0.985943E+09 | 0.208991E+10 | 0.892017E+09 | 0.119790E+10 | 0.00 | 0.00 |
May | 0.246607E+10 | 0.918784E+09 | 0.221599E+10 | 0.843169E+09 | 0.137282E+10 | 0.00 | 0.00 |
June | 0.258906E+10 | 0.681290E+09 | 0.212241E+10 | 0.719815E+09 | 0.140259E+10 | 0.00 | 0.00 |
July | 0.289047E+10 | 0.642210E+09 | 0.224075E+10 | 0.827889E+09 | 0.141286E+10 | 0.00 | 0.00 |
August | 0.288715E+10 | 0.672978E+09 | 0.217206E+10 | 0.945114E+09 | 0.122694E+10 | 0.00 | 0.00 |
September | 0.253405E+10 | 0.831373E+09 | 0.198520E+10 | 0.101416E+10 | 0.971033E+09 | 0.00 | 0.00 |
October | 0.116849E+10 | 0.117575E+10 | 0.110945E+10 | 0.480935E+09 | 0.628519E+09 | 0.00 | 0.00 |
November | 0.479409E+09 | 0.139777E+10 | 0.629044E+09 | 0.259737E+09 | 0.369308E+09 | 0.00 | 0.00 |
December | 0.322258E+09 | 0.182438E+10 | 0.492275E+09 | 0.222309E+09 | 0.269966E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.196613E+11 | 0.133470E+11 | 0.175325E+11 | 0.708339E+10 | 0.104491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322258E+09 | 0.642210E+09 | 0.492275E+09 | 0.175146E+09 | 0.269966E+09 | 0.00 | 0.00 |
Maximum of Months | 0.289047E+10 | 0.182438E+10 | 0.224075E+10 | 0.101416E+10 | 0.141286E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.974477E+09 | 0.177471E+10 | 0.115846E+10 | 0.674242E+09 | 0.484216E+09 | 0.00 | 0.00 |
February | 0.115222E+10 | 0.155459E+10 | 0.130656E+10 | 0.695522E+09 | 0.611038E+09 | 0.00 | 0.00 |
March | 0.710445E+09 | 0.143227E+10 | 0.103321E+10 | 0.225418E+09 | 0.807792E+09 | 0.00 | 0.00 |
April | 0.204854E+10 | 0.112306E+10 | 0.194771E+10 | 0.688135E+09 | 0.125957E+10 | 0.00 | 0.00 |
May | 0.175313E+10 | 0.975974E+09 | 0.185781E+10 | 0.460520E+09 | 0.139729E+10 | 0.00 | 0.00 |
June | 0.179049E+10 | 0.712508E+09 | 0.174908E+10 | 0.324054E+09 | 0.142503E+10 | 0.00 | 0.00 |
July | 0.208120E+10 | 0.676000E+09 | 0.187568E+10 | 0.444416E+09 | 0.143127E+10 | 0.00 | 0.00 |
August | 0.236465E+10 | 0.749376E+09 | 0.199305E+10 | 0.709678E+09 | 0.128337E+10 | 0.00 | 0.00 |
September | 0.251549E+10 | 0.953188E+09 | 0.212965E+10 | 0.107216E+10 | 0.105749E+10 | 0.00 | 0.00 |
October | 0.147504E+10 | 0.131179E+10 | 0.145966E+10 | 0.721997E+09 | 0.737667E+09 | 0.00 | 0.00 |
November | 0.854314E+09 | 0.157238E+10 | 0.995740E+09 | 0.532212E+09 | 0.463528E+09 | 0.00 | 0.00 |
December | 0.637085E+09 | 0.204236E+10 | 0.802484E+09 | 0.460173E+09 | 0.342311E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183571E+11 | 0.148782E+11 | 0.183091E+11 | 0.700852E+10 | 0.113006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.637085E+09 | 0.676000E+09 | 0.802484E+09 | 0.225418E+09 | 0.342311E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251549E+10 | 0.204236E+10 | 0.212965E+10 | 0.107216E+10 | 0.143127E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770482E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162026502.2 | 81.21 | 0.00 | 0.00 |
February | 0.696234E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146356201.1 | 81.21 | 0.00 | 0.00 |
March | 0.770344E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161953368.3 | 81.21 | 0.00 | 0.00 |
April | 0.746522E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156615456.7 | 81.21 | 0.00 | 0.00 |
May | 0.770458E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161790828.2 | 81.21 | 0.00 | 0.00 |
June | 0.745699E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156462089.7 | 81.21 | 0.00 | 0.00 |
July | 0.771248E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161645576.8 | 81.21 | 0.00 | 0.00 |
August | 0.770443E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161632890.1 | 81.21 | 0.00 | 0.00 |
September | 0.746641E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156491052.8 | 81.21 | 0.00 | 0.00 |
October | 0.770330E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161861035.7 | 81.21 | 0.00 | 0.00 |
November | 0.744917E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156743484.2 | 81.21 | 0.00 | 0.00 |
December | 0.771293E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162065727.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907461E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190564E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696234E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162065727.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771293E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146356201.1 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121898E+12 | -0.120147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175117E+10 | 81.27 | 0.00 | 0.00 |
February | 0.110622E+12 | -0.109035E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158641E+10 | 81.27 | 0.00 | 0.00 |
March | 0.121902E+12 | -0.120138E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176360E+10 | 81.27 | 0.00 | 0.00 |
April | 0.116432E+12 | -0.114726E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170646E+10 | 81.27 | 0.00 | 0.00 |
May | 0.118127E+12 | -0.116364E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176323E+10 | 81.26 | 0.00 | 0.00 |
June | 0.112191E+12 | -0.110488E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170294E+10 | 81.26 | 0.00 | 0.00 |
July | 0.114314E+12 | -0.112561E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175249E+10 | 81.26 | 0.00 | 0.00 |
August | 0.113706E+12 | -0.111957E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174835E+10 | 81.26 | 0.00 | 0.00 |
September | 0.110598E+12 | -0.108914E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168458E+10 | 81.25 | 0.00 | 0.00 |
October | 0.115887E+12 | -0.114149E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173787E+10 | 81.26 | 0.00 | 0.00 |
November | 0.114265E+12 | -0.112583E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168144E+10 | 81.26 | 0.00 | 0.00 |
December | 0.120266E+12 | -0.118524E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174197E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.139021E+13 | -0.136959E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206205E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.110598E+12 | -0.120147E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176360E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.121902E+12 | -0.108914E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158641E+10 | 81.27 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.725890E+11 | -0.710927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149625E+10 | 58.98 | 0.00 | 0.00 |
February | 0.660139E+11 | -0.646560E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.135791E+10 | 58.98 | 0.00 | 0.00 |
March | 0.726624E+11 | -0.711490E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151340E+10 | 58.98 | 0.00 | 0.00 |
April | 0.689709E+11 | -0.675065E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146440E+10 | 58.98 | 0.00 | 0.00 |
May | 0.694101E+11 | -0.678968E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151335E+10 | 58.98 | 0.00 | 0.00 |
June | 0.653710E+11 | -0.639111E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145993E+10 | 58.98 | 0.00 | 0.00 |
July | 0.660937E+11 | -0.645951E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149863E+10 | 58.98 | 0.00 | 0.00 |
August | 0.656365E+11 | -0.641436E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149280E+10 | 58.98 | 0.00 | 0.00 |
September | 0.639616E+11 | -0.625270E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143468E+10 | 58.98 | 0.00 | 0.00 |
October | 0.674368E+11 | -0.659584E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147841E+10 | 58.98 | 0.00 | 0.00 |
November | 0.670771E+11 | -0.656470E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143006E+10 | 58.98 | 0.00 | 0.00 |
December | 0.711903E+11 | -0.697065E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148376E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.816413E+12 | -0.798790E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.176236E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.639616E+11 | -0.711490E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151340E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.726624E+11 | -0.625270E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135791E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.87 | 0.86 | 01-JAN-08:39 | 3370.77 | 36.53 | 191.67 | 226.00 | 2715.88 | 37.48 | 192.00 | 187.00 |
February | 217.00 | 0.87 | 0.86 | 01-FEB-11:39 | 4958.33 | 35.87 | 212.00 | 247.67 | 2174.54 | 31.92 | 194.67 | 210.67 |
March | 215.50 | 0.87 | 0.86 | 01-MAR-11:39 | 3215.22 | 29.59 | 161.50 | 313.83 | 667.82 | 21.68 | 136.00 | 251.67 |
April | 359.67 | 0.87 | 0.86 | 01-APR-07:19 | 1866.57 | 20.90 | 192.17 | 360.17 | 735.92 | 22.61 | 281.33 | 316.67 |
May | 417.17 | 0.87 | 0.86 | 01-MAY-07:10 | 1497.46 | 20.41 | 155.50 | 413.17 | 589.00 | 22.12 | 297.00 | 350.67 |
June | 410.67 | 0.87 | 0.86 | 01-JUN-06:19 | 1467.33 | 20.63 | 154.33 | 415.83 | 574.85 | 22.32 | 299.50 | 353.83 |
July | 429.00 | 0.87 | 0.86 | 01-JUL-06:30 | 1434.35 | 20.49 | 162.83 | 424.00 | 572.45 | 22.20 | 313.83 | 365.33 |
August | 396.33 | 0.87 | 0.86 | 01-AUG-06:40 | 1632.91 | 20.60 | 188.50 | 385.17 | 655.47 | 22.33 | 299.00 | 333.83 |
September | 337.67 | 0.87 | 0.86 | 01-SEP-07:00 | 5617.92 | 27.26 | 219.17 | 332.33 | 786.17 | 22.74 | 265.00 | 290.83 |
October | 234.00 | 0.87 | 0.86 | 01-OCT-06:00 | 6323.09 | 35.14 | 217.00 | 282.67 | 1095.65 | 25.41 | 193.00 | 230.67 |
November | 171.33 | 0.87 | 0.86 | 01-NOV-11:50 | 3930.05 | 36.25 | 167.33 | 221.83 | 2868.44 | 36.50 | 165.67 | 164.33 |
December | 131.67 | 0.87 | 0.86 | 02-DEC-08:50 | 3233.30 | 37.32 | 128.50 | 186.67 | 2601.23 | 38.27 | 128.67 | 125.17 |
Annual Sum or Average | 3515.67 | 0.87 | 2862.95 | 25.97 | 2150.50 | 3809.33 | 1068.03 | 25.24 | 2765.67 | 3180.67 | ||
Minimum of Months | 131.67 | 0.87 | 0.86 | 1434.35 | 20.41 | 128.50 | 186.67 | 572.45 | 21.68 | 128.67 | 125.17 | |
Maximum of Months | 429.00 | 0.87 | 0.86 | 6323.09 | 37.32 | 219.17 | 424.00 | 2868.44 | 38.27 | 313.83 | 365.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.27 | 0.22 | 01-JAN-08:39 | 3702.74 | 36.60 | 191.67 | 234.83 | 3047.32 | 37.53 | 192.00 | 212.33 |
February | 217.00 | 0.25 | 0.22 | 01-FEB-11:39 | 5335.82 | 35.95 | 212.17 | 254.83 | 2547.96 | 31.94 | 200.50 | 234.67 |
March | 215.50 | 0.27 | 0.22 | 01-MAR-11:39 | 3464.58 | 29.86 | 162.50 | 325.17 | 916.26 | 22.11 | 186.50 | 288.17 |
April | 359.67 | 0.26 | 0.22 | 01-APR-06:00 | 2221.91 | 21.17 | 187.17 | 368.33 | 1090.14 | 22.73 | 298.00 | 344.83 |
May | 417.17 | 0.26 | 0.22 | 01-MAY-06:49 | 1770.13 | 20.87 | 181.33 | 425.00 | 860.73 | 22.41 | 326.83 | 394.17 |
June | 410.67 | 0.25 | 0.22 | 01-JUN-05:40 | 1720.23 | 21.14 | 189.17 | 430.33 | 826.83 | 22.66 | 326.00 | 390.83 |
July | 429.00 | 0.26 | 0.22 | 01-JUL-05:40 | 1700.67 | 20.95 | 195.83 | 436.50 | 837.89 | 22.49 | 343.00 | 405.83 |
August | 396.33 | 0.26 | 0.22 | 01-AUG-05:00 | 1962.64 | 20.92 | 176.83 | 395.17 | 984.19 | 22.49 | 316.33 | 365.50 |
September | 337.67 | 0.26 | 0.22 | 01-SEP-07:40 | 6043.77 | 27.49 | 212.33 | 340.33 | 1211.06 | 22.72 | 270.67 | 318.67 |
October | 234.00 | 0.25 | 0.22 | 01-OCT-06:49 | 6721.29 | 35.27 | 217.33 | 291.83 | 1493.77 | 25.45 | 207.17 | 264.50 |
November | 171.33 | 0.26 | 0.22 | 01-NOV-11:39 | 4271.67 | 36.32 | 167.50 | 233.00 | 3209.29 | 36.55 | 166.17 | 195.00 |
December | 131.67 | 0.26 | 0.22 | 02-DEC-08:39 | 3566.45 | 37.39 | 128.67 | 198.83 | 2933.06 | 38.32 | 128.67 | 155.17 |
Annual Sum or Average | 3515.67 | 0.26 | 3184.46 | 26.27 | 2222.50 | 3934.17 | 1388.46 | 25.42 | 2961.83 | 3569.67 | ||
Minimum of Months | 131.67 | 0.25 | 0.22 | 1700.67 | 20.87 | 128.67 | 198.83 | 826.83 | 22.11 | 128.67 | 155.17 | |
Maximum of Months | 429.00 | 0.27 | 0.22 | 6721.29 | 37.39 | 217.33 | 436.50 | 3209.29 | 38.32 | 343.00 | 405.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.70 | 0.60 | 01-JAN-10:50 | 368.78 | 14.16 | 0.00 | 205.67 | 171.61 | 17.56 | 0.00 | 65.17 |
February | 217.00 | 0.66 | 0.60 | 01-FEB-12:09 | 480.84 | 15.69 | 0.00 | 236.33 | 222.48 | 18.98 | 0.00 | 137.67 |
March | 215.50 | 0.65 | 0.60 | 01-MAR-11:39 | 616.26 | 16.23 | 0.00 | 313.83 | 257.71 | 19.33 | 3.17 | 216.67 |
April | 359.67 | 0.62 | 0.60 | 01-APR-07:19 | 772.32 | 18.16 | 0.00 | 367.67 | 356.91 | 21.35 | 164.83 | 332.67 |
May | 417.17 | 0.61 | 0.60 | 01-MAY-06:00 | 936.67 | 19.61 | 30.00 | 433.00 | 424.85 | 23.55 | 273.17 | 407.67 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1070.80 | 20.54 | 49.50 | 436.83 | 488.67 | 24.00 | 292.00 | 408.50 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:49 | 985.44 | 20.68 | 61.33 | 445.50 | 457.35 | 23.65 | 295.00 | 419.17 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:40 | 777.05 | 18.45 | 6.83 | 399.50 | 366.76 | 21.64 | 194.00 | 363.67 |
September | 337.67 | 0.63 | 0.60 | 01-SEP-07:00 | 607.50 | 17.37 | 0.00 | 333.83 | 300.80 | 20.61 | 38.17 | 284.67 |
October | 234.00 | 0.64 | 0.60 | 01-OCT-07:49 | 533.87 | 16.34 | 0.00 | 274.83 | 252.12 | 19.60 | 0.17 | 174.83 |
November | 171.33 | 0.68 | 0.60 | 01-NOV-12:20 | 404.55 | 14.79 | 0.00 | 204.50 | 188.83 | 18.14 | 0.00 | 74.00 |
December | 131.67 | 0.71 | 0.60 | 02-DEC-11:09 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 |
Annual Sum or Average | 3515.67 | 0.63 | 737.42 | 17.94 | 147.67 | 3817.00 | 341.18 | 21.26 | 1260.50 | 2919.50 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 | |
Maximum of Months | 429.00 | 0.71 | 0.60 | 1070.80 | 20.68 | 61.33 | 445.50 | 488.67 | 24.00 | 295.00 | 419.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.70 | 0.60 | 01-JAN-10:50 | 368.78 | 14.16 | 0.00 | 205.67 | 171.61 | 17.56 | 0.00 | 65.17 |
February | 217.00 | 0.66 | 0.60 | 01-FEB-12:09 | 480.84 | 15.69 | 0.00 | 236.33 | 222.48 | 18.98 | 0.00 | 137.67 |
March | 215.50 | 0.65 | 0.60 | 01-MAR-11:39 | 616.26 | 16.23 | 0.00 | 313.83 | 257.71 | 19.33 | 3.17 | 216.67 |
April | 359.67 | 0.62 | 0.60 | 01-APR-07:19 | 772.32 | 18.16 | 0.00 | 367.67 | 356.91 | 21.35 | 164.83 | 332.67 |
May | 417.17 | 0.61 | 0.60 | 01-MAY-06:00 | 936.67 | 19.61 | 30.00 | 433.00 | 424.85 | 23.55 | 273.17 | 407.67 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1070.80 | 20.54 | 49.50 | 436.83 | 488.67 | 24.00 | 292.00 | 408.50 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:49 | 985.44 | 20.68 | 61.33 | 445.50 | 457.35 | 23.65 | 295.00 | 419.17 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:40 | 777.05 | 18.45 | 6.83 | 399.50 | 366.76 | 21.64 | 194.00 | 363.67 |
September | 337.67 | 0.63 | 0.60 | 01-SEP-07:00 | 607.50 | 17.37 | 0.00 | 333.83 | 300.80 | 20.61 | 38.17 | 284.67 |
October | 234.00 | 0.64 | 0.60 | 01-OCT-07:49 | 533.87 | 16.34 | 0.00 | 274.83 | 252.12 | 19.60 | 0.17 | 174.83 |
November | 171.33 | 0.68 | 0.60 | 01-NOV-12:20 | 404.55 | 14.79 | 0.00 | 204.50 | 188.83 | 18.14 | 0.00 | 74.00 |
December | 131.67 | 0.71 | 0.60 | 02-DEC-11:09 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 |
Annual Sum or Average | 3515.67 | 0.63 | 737.42 | 17.94 | 147.67 | 3817.00 | 341.18 | 21.26 | 1260.50 | 2919.50 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 | |
Maximum of Months | 429.00 | 0.71 | 0.60 | 1070.80 | 20.68 | 61.33 | 445.50 | 488.67 | 24.00 | 295.00 | 419.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532648E+11 | 120773.11 | 06-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295070E+11 | 130614.17 | 19-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630521E+11 | 117852.14 | 26-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779741E+11 | 117282.39 | 10-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101706E+12 | 118396.30 | 27-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.753375E+11 | 115075.66 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510360E+11 | 101331.39 | 15-JUL-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381397E+11 | 102574.66 | 24-AUG-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.733499E+11 | 121125.94 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106271E+12 | 118413.79 | 30-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.912400E+11 | 124895.25 | 28-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299505E+11 | 127487.65 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.295070E+11 | 101331.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106271E+12 | 130614.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299568E+10 | 2171.33 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238476E+10 | 2016.36 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282956E+10 | 1906.55 | 15-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104306E+10 | 1559.49 | 10-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104058E+10 | 1430.56 | 05-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.497373E+09 | 1167.55 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.340705E+09 | 969.65 | 09-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199842E+09 | 807.70 | 09-AUG-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400812E+09 | 1137.13 | 17-SEP-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173121E+10 | 1598.49 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261845E+10 | 1972.44 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366017E+10 | 2065.28 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.199842E+09 | 807.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366017E+10 | 2171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19565376.89 | 287.63 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7051931.82 | 223.26 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6191675.86 | 219.25 | 16-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6419247.66 | 240.91 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50017878.17 | 327.59 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89246110.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50017878.17 | 327.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.466880E+09 | 736.50 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343636E+09 | 514.35 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216354E+09 | 496.29 | 16-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 890139.76 | 212.01 | 01-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 433022.75 | 39.32 | 29-OCT-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164268E+09 | 551.85 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625123E+09 | 651.87 | 30-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625123E+09 | 736.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527141E+09 | 525.08 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417558E+09 | 399.71 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323823E+09 | 387.47 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11986855.50 | 187.29 | 01-APR-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13014.23 | 42.10 | 05-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34307004.21 | 169.37 | 16-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270685E+09 | 433.63 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664064E+09 | 488.56 | 30-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.664064E+09 | 525.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118300E+09 | 1315.23 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98198477.05 | 1119.14 | 17-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85684277.11 | 1018.29 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19844687.63 | 810.48 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16778518.11 | 648.88 | 15-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1035534.76 | 249.17 | 08-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 765995.52 | 188.88 | 05-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77779.40 | 64.82 | 12-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 724884.83 | 249.17 | 09-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34216796.22 | 757.18 | 23-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77784060.35 | 1068.97 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138295E+09 | 1363.11 | 30-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 77779.40 | 64.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138295E+09 | 1363.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201461E+10 | 5663.38 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134337E+10 | 5163.59 | 16-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189635E+10 | 5043.81 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198320E+09 | 4091.57 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271133E+09 | 3206.08 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68451910.68 | 3132.60 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6611383.02 | 1476.95 | 08-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17576136.90 | 2169.50 | 09-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31336917.39 | 2576.46 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.928290E+09 | 4309.72 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174584E+10 | 5208.00 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305473E+10 | 5484.86 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6611383.02 | 1476.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305473E+10 | 5663.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313678E+09 | 5900.39 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109849E+09 | 4806.93 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117925E+09 | 4103.43 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 398770.97 | 329.80 | 16-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150261E+09 | 4923.06 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769929E+09 | 6439.10 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769929E+09 | 6439.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580654E+10 | 6448.45 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406885E+10 | 5828.80 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414339E+10 | 5451.57 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113020E+09 | 2537.93 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 951384.46 | 1034.01 | 18-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153700E+10 | 4509.57 | 20-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452952E+10 | 6068.98 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.818266E+10 | 6412.50 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.818266E+10 | 6448.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353065E+10 | 3355.40 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255120E+10 | 3140.49 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218028E+10 | 2444.37 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250316E+09 | 1902.63 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56268790.55 | 997.61 | 06-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886595E+09 | 1859.55 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246652E+10 | 2833.01 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441587E+10 | 3083.66 | 27-DEC-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.441587E+10 | 3355.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256857E+09 | 3091.75 | 12-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83240968.97 | 1520.19 | 17-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2041521.93 | 1535.92 | 15-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7695.13 | 0.64 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6260.53 | 0.63 | 27-MAY-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12381.74 | 0.67 | 24-JUN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25492.16 | 0.68 | 12-JUL-19:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23976.73 | 0.66 | 18-AUG-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12646.93 | 0.67 | 17-SEP-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2880.11 | 0.64 | 07-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6868145.00 | 640.87 | 29-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51874153.82 | 1702.44 | 27-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2880.11 | 0.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256857E+09 | 3091.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336911E+10 | 5186.17 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251976E+10 | 5157.65 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243154E+10 | 5186.09 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552396E+09 | 5018.12 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374183E+09 | 4489.37 | 14-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38867637.61 | 4452.20 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48692345.89 | 4257.65 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11153139.68 | 4045.27 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109717E+09 | 4501.97 | 19-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127940E+10 | 5103.50 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267785E+10 | 5186.44 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.445238E+10 | 5186.93 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11153139.68 | 4045.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445238E+10 | 5186.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419035E+10 | 5104.15 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319304E+10 | 5104.13 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276140E+10 | 5103.81 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.773018E+09 | 4962.19 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440467E+09 | 4595.19 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37215842.01 | 4270.02 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47113504.62 | 4359.06 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10586699.19 | 4590.77 | 07-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166332E+09 | 4411.59 | 18-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167867E+10 | 5031.12 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327531E+10 | 5104.19 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502242E+10 | 5104.80 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10586699.19 | 4270.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502242E+10 | 5104.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105238E+11 | 28380.42 | 11-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759355E+10 | 27645.83 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365639E+10 | 27597.76 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.606453E+09 | 27163.31 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201546E+09 | 26776.90 | 26-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49158801.14 | 27165.62 | 03-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40769521.42 | 25970.08 | 29-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49519258.76 | 25269.33 | 23-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102984E+09 | 27174.85 | 24-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144186E+10 | 27171.01 | 24-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576116E+10 | 28030.93 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125191E+11 | 28179.65 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 40769521.42 | 25269.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125191E+11 | 28380.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.339142E+10 | 5103.48 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264096E+10 | 5089.53 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246087E+10 | 5103.38 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517689E+09 | 4919.57 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.376489E+09 | 4568.78 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65189022.72 | 4326.85 | 29-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37578083.51 | 4599.56 | 29-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11599884.30 | 4237.33 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85330160.06 | 4324.40 | 02-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128121E+10 | 5026.21 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269658E+10 | 5103.75 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431562E+10 | 5104.26 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11599884.30 | 4237.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431562E+10 | 5104.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416893E+10 | 5021.91 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336060E+10 | 5022.54 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279012E+10 | 5021.45 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698942E+09 | 4861.19 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.445496E+09 | 3973.91 | 27-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71496934.58 | 4379.08 | 16-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35368297.17 | 4741.90 | 29-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8374196.36 | 4404.74 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146629E+09 | 4684.31 | 17-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165470E+10 | 4953.97 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326931E+10 | 5022.03 | 21-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484669E+10 | 5022.47 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8374196.36 | 3973.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.484669E+10 | 5022.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122510E+10 | 1562.27 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.919382E+09 | 1562.25 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.890203E+09 | 1562.11 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250866E+09 | 1530.44 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184684E+09 | 1508.95 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35959136.74 | 1098.67 | 29-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32042480.36 | 1094.36 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11000994.01 | 1093.07 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78895063.00 | 1109.51 | 30-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.526372E+09 | 1561.59 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.983055E+09 | 1562.28 | 23-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155752E+10 | 1562.24 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11000994.01 | 1093.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155752E+10 | 1562.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147659E+10 | 1531.50 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112960E+10 | 1531.47 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993729E+09 | 1531.33 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327728E+09 | 1508.70 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208940E+09 | 1482.24 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33170884.74 | 1113.57 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28820523.40 | 1149.87 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7771632.24 | 1145.45 | 20-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107334E+09 | 1236.46 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666142E+09 | 1531.41 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116872E+10 | 1531.74 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172910E+10 | 1531.52 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7771632.24 | 1113.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172910E+10 | 1531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.302406E+10 | 7677.32 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221369E+10 | 7541.61 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240625E+10 | 7625.56 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.495789E+09 | 6238.49 | 16-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450062E+09 | 6596.62 | 29-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83478209.47 | 6068.65 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 59066806.69 | 6693.17 | 29-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18622828.22 | 5567.91 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75630842.41 | 5983.88 | 07-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989723E+09 | 7503.31 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226164E+10 | 7677.78 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457583E+10 | 7678.44 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 18622828.22 | 5567.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457583E+10 | 7678.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.151075E+11 | 0.150929E+11 | 185786.96 | 30-APR-18:10 | 185786.96 | 0.03 |
May | 0.00 | 0.00 | 0.152687E+11 | 0.152687E+11 | 159744.49 | 22-MAY-15:12 | 159744.49 | 0.09 |
June | 0.00 | 0.00 | 0.489415E+11 | 0.466760E+11 | 334242.58 | 25-JUN-18:00 | 148852.15 | 0.30 |
July | 0.00 | 0.00 | 0.845862E+11 | 0.835524E+11 | 234938.17 | 22-JUL-18:10 | 234938.17 | 0.49 |
August | 0.00 | 0.00 | 0.984892E+11 | 0.974914E+11 | 213064.67 | 14-AUG-18:10 | 213064.67 | 0.56 |
September | 0.00 | 0.00 | 0.507150E+11 | 0.503602E+11 | 160169.77 | 11-SEP-17:04 | 160169.77 | 0.36 |
October | 0.00 | 0.00 | 0.262849E+10 | 0.262849E+10 | 71691.26 | 07-OCT-15:03 | 71691.26 | 0.01 |
November | 0.00 | 0.00 | 49361593.28 | 49361593.28 | 28531.01 | 24-NOV-11:50 | 28531.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315786E+12 | 0.311119E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.984892E+11 | 0.974914E+11 | 334242.58 | 234938.17 | 0.56 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.871147E+09 | 0.871147E+09 | 17043.06 | 30-APR-15:02 | 17043.06 | 0.02 |
May | 0.00 | 0.00 | 0.908483E+09 | 0.908483E+09 | 17029.10 | 22-MAY-15:02 | 17029.10 | 0.05 |
June | 0.00 | 0.00 | 0.290719E+10 | 0.269885E+10 | 31376.35 | 25-JUN-18:03 | 14441.62 | 0.18 |
July | 0.00 | 0.00 | 0.528320E+10 | 0.509036E+10 | 20042.47 | 23-JUL-15:53 | 14923.03 | 0.31 |
August | 0.00 | 0.00 | 0.612254E+10 | 0.589875E+10 | 19239.53 | 17-AUG-15:02 | 14671.97 | 0.37 |
September | 0.00 | 0.00 | 0.309471E+10 | 0.300011E+10 | 18537.15 | 10-SEP-15:55 | 13442.60 | 0.20 |
October | 0.00 | 0.00 | 0.156128E+09 | 0.156128E+09 | 8578.33 | 07-OCT-15:06 | 8578.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193434E+11 | 0.186238E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.612254E+10 | 0.589875E+10 | 31376.35 | 17043.06 | 0.37 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 31099644.64 | 16752824.69 | 13229.26 | 25-JAN-16:01 | 13229.26 | 0.01 |
February | 0.00 | 0.00 | 0.200575E+09 | 0.113022E+09 | 16843.53 | 17-FEB-16:01 | 16843.53 | 0.05 |
March | 0.00 | 0.00 | 96448244.64 | 61125021.97 | 16594.69 | 10-MAR-16:01 | 16594.69 | 0.02 |
April | 0.00 | 0.00 | 0.262443E+10 | 0.167121E+10 | 16842.87 | 12-APR-15:01 | 16842.87 | 0.45 |
May | 0.00 | 0.00 | 0.323152E+10 | 0.187152E+10 | 16843.16 | 11-MAY-18:01 | 16843.16 | 0.54 |
June | 0.00 | 0.00 | 0.508679E+10 | 0.272243E+10 | 16485.61 | 04-JUN-08:62 | 13838.62 | 0.81 |
July | 0.00 | 0.00 | 0.652918E+10 | 0.354936E+10 | 16342.85 | 29-JUL-15:01 | 14505.46 | 0.83 |
August | 0.00 | 0.00 | 0.619403E+10 | 0.314326E+10 | 17240.25 | 08-AUG-15:01 | 13580.48 | 0.90 |
September | 0.00 | 0.00 | 0.436944E+10 | 0.225045E+10 | 16702.68 | 16-SEP-15:02 | 12459.83 | 0.75 |
October | 0.00 | 0.00 | 0.935147E+09 | 0.517523E+09 | 16816.43 | 06-OCT-18:01 | 16816.43 | 0.20 |
November | 0.00 | 0.00 | 42649195.18 | 21953869.56 | 13661.63 | 10-NOV-16:01 | 13661.63 | 0.02 |
December | 0.00 | 0.00 | 289201.82 | 75695.80 | 758.16 | 24-DEC-09:06 | 132.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.293416E+11 | 0.159387E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 289201.82 | 75695.80 | 758.16 | 132.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.652918E+10 | 0.354936E+10 | 17240.25 | 16843.53 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4424494.79 | 2142390.44 | 11036.07 | 19-JAN-16:01 | 11036.07 | 0.00 |
February | 0.00 | 0.00 | 48680686.66 | 24221515.42 | 14135.15 | 17-FEB-16:01 | 14135.15 | 0.02 |
March | 0.00 | 0.00 | 48974623.32 | 28693281.96 | 12055.21 | 10-MAR-16:01 | 12055.21 | 0.01 |
April | 0.00 | 0.00 | 0.143075E+10 | 0.898904E+09 | 15102.99 | 12-APR-15:01 | 15102.99 | 0.29 |
May | 0.00 | 0.00 | 0.216052E+10 | 0.119516E+10 | 15458.94 | 22-MAY-21:31 | 14430.24 | 0.42 |
June | 0.00 | 0.00 | 0.382987E+10 | 0.197081E+10 | 17656.44 | 26-JUN-21:01 | 13786.33 | 0.69 |
July | 0.00 | 0.00 | 0.425741E+10 | 0.213158E+10 | 16877.90 | 24-JUL-20:01 | 14481.41 | 0.63 |
August | 0.00 | 0.00 | 0.328709E+10 | 0.141475E+10 | 16216.55 | 11-AUG-19:11 | 12947.45 | 0.62 |
September | 0.00 | 0.00 | 0.187147E+10 | 0.761787E+09 | 15893.22 | 14-SEP-18:01 | 15455.71 | 0.50 |
October | 0.00 | 0.00 | 0.306895E+09 | 0.164725E+09 | 14798.40 | 06-OCT-18:01 | 14798.40 | 0.09 |
November | 0.00 | 0.00 | 7189129.55 | 3296316.90 | 11530.60 | 10-NOV-16:01 | 11530.60 | 0.00 |
December | 0.00 | 0.00 | 187259.43 | 31241.72 | 764.45 | 02-DEC-09:06 | 145.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172535E+11 | 0.859610E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 187259.43 | 31241.72 | 764.45 | 145.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.425741E+10 | 0.213158E+10 | 17656.44 | 15455.71 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167522E+10 | 0.143749E+10 | 30109.18 | 21-JAN-11:25 | 30109.18 | 0.02 |
February | 0.00 | 0.00 | 0.129660E+10 | 0.117778E+10 | 21355.45 | 19-FEB-14:30 | 21355.45 | 0.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211357E+11 | 0.169498E+11 | 44523.55 | 30-APR-12:50 | 32861.29 | 0.19 |
May | 0.00 | 0.00 | 0.172630E+11 | 0.895340E+10 | 35205.99 | 23-MAY-12:50 | 19347.46 | 0.42 |
June | 0.00 | 0.00 | 0.231114E+11 | 0.720922E+10 | 36534.11 | 13-JUN-13:05 | 20922.73 | 0.75 |
July | 0.00 | 0.00 | 0.314918E+11 | 0.110446E+11 | 41514.43 | 22-JUL-13:20 | 27778.27 | 0.84 |
August | 0.00 | 0.00 | 0.394720E+11 | 0.161977E+11 | 44987.17 | 20-AUG-12:50 | 31575.12 | 0.91 |
September | 0.00 | 0.00 | 0.397273E+11 | 0.196254E+11 | 54955.71 | 12-SEP-12:30 | 46027.99 | 0.84 |
October | 0.00 | 0.00 | 0.136258E+11 | 0.843647E+10 | 49467.38 | 07-OCT-13:00 | 49467.38 | 0.27 |
November | 0.00 | 0.00 | 0.119174E+10 | 0.102571E+10 | 26359.48 | 11-NOV-13:30 | 26359.48 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189990E+12 | 0.920576E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.397273E+11 | 0.196254E+11 | 54955.71 | 49467.38 | 0.91 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102574E+10 | 0.353301E+09 | 64499.38 | 29-JAN-09:02 | 64499.38 | 0.11 |
February | 0.00 | 0.00 | 0.804429E+09 | 0.272324E+09 | 58602.88 | 21-FEB-19:02 | 58602.88 | 0.11 |
March | 0.00 | 0.00 | 0.405573E+10 | 0.186960E+10 | 72831.49 | 30-MAR-18:03 | 72831.49 | 0.26 |
April | 0.00 | 0.00 | 0.134245E+11 | 0.799237E+10 | 77051.45 | 20-APR-18:01 | 77051.45 | 0.50 |
May | 0.00 | 0.00 | 0.201771E+11 | 0.114827E+11 | 76486.94 | 11-MAY-19:31 | 76486.94 | 0.63 |
June | 0.00 | 0.00 | 0.325242E+11 | 0.195659E+11 | 84286.07 | 26-JUN-21:01 | 68491.64 | 0.66 |
July | 0.00 | 0.00 | 0.339225E+11 | 0.206606E+11 | 81592.88 | 17-JUL-21:51 | 64417.91 | 0.59 |
August | 0.00 | 0.00 | 0.279050E+11 | 0.157460E+11 | 81753.35 | 16-AUG-21:52 | 63830.81 | 0.54 |
September | 0.00 | 0.00 | 0.201737E+11 | 0.101537E+11 | 79831.94 | 10-SEP-20:31 | 63692.94 | 0.60 |
October | 0.00 | 0.00 | 0.739745E+10 | 0.296093E+10 | 73972.76 | 07-OCT-18:01 | 73972.76 | 0.41 |
November | 0.00 | 0.00 | 0.217608E+10 | 0.715851E+09 | 69629.96 | 24-NOV-19:02 | 61963.47 | 0.19 |
December | 0.00 | 0.00 | 0.262813E+09 | 97426609.86 | 58928.35 | 02-DEC-09:02 | 58928.35 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.163849E+12 | 0.918707E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.262813E+09 | 97426609.86 | 58602.88 | 58602.88 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.339225E+11 | 0.206606E+11 | 84286.07 | 77051.45 | 0.66 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 70851533.85 | 26198987.48 | 10999.88 | 21-JAN-16:01 | 10999.88 | 0.02 |
February | 0.00 | 0.00 | 0.129619E+09 | 59815189.19 | 14487.00 | 17-FEB-16:01 | 14487.00 | 0.04 |
March | 0.00 | 0.00 | 70950093.41 | 30106717.92 | 11920.04 | 25-MAR-15:01 | 11920.04 | 0.03 |
April | 0.00 | 0.00 | 0.299338E+10 | 0.180174E+10 | 15330.95 | 12-APR-15:01 | 15330.95 | 0.53 |
May | 0.00 | 0.00 | 0.323832E+10 | 0.172591E+10 | 15330.24 | 11-MAY-18:01 | 15330.24 | 0.60 |
June | 0.00 | 0.00 | 0.474208E+10 | 0.240883E+10 | 15119.74 | 04-JUN-08:62 | 12671.73 | 0.81 |
July | 0.00 | 0.00 | 0.609652E+10 | 0.315781E+10 | 15006.81 | 08-JUL-08:61 | 13136.18 | 0.87 |
August | 0.00 | 0.00 | 0.643213E+10 | 0.330955E+10 | 15623.41 | 08-AUG-15:01 | 12223.20 | 0.92 |
September | 0.00 | 0.00 | 0.487904E+10 | 0.254376E+10 | 15314.08 | 16-SEP-15:02 | 11784.18 | 0.80 |
October | 0.00 | 0.00 | 0.102297E+10 | 0.563338E+09 | 15053.25 | 07-OCT-18:01 | 15053.25 | 0.22 |
November | 0.00 | 0.00 | 71508988.73 | 27888085.03 | 11808.22 | 11-NOV-09:02 | 11808.22 | 0.03 |
December | 0.00 | 0.00 | 14634742.23 | 4385512.55 | 1761.23 | 06-DEC-09:03 | 650.78 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.297620E+11 | 0.156593E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 14634742.23 | 4385512.55 | 1761.23 | 650.78 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.643213E+10 | 0.330955E+10 | 15623.41 | 15330.95 | 0.92 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2673602.22 | 548790.64 | 1667.32 | 23-JAN-09:04 | 513.38 | 0.00 |
February | 0.00 | 0.00 | 17970602.49 | 5334118.42 | 9515.44 | 20-FEB-09:02 | 9515.44 | 0.01 |
March | 0.00 | 0.00 | 21440598.35 | 6811191.38 | 5863.91 | 25-MAR-15:01 | 4044.91 | 0.01 |
April | 0.00 | 0.00 | 0.172142E+10 | 0.102619E+10 | 13836.87 | 14-APR-15:01 | 13836.87 | 0.39 |
May | 0.00 | 0.00 | 0.223761E+10 | 0.120273E+10 | 13711.22 | 11-MAY-19:31 | 13711.22 | 0.49 |
June | 0.00 | 0.00 | 0.362636E+10 | 0.185192E+10 | 15003.32 | 26-JUN-21:01 | 11853.09 | 0.69 |
July | 0.00 | 0.00 | 0.421735E+10 | 0.215868E+10 | 15830.88 | 23-JUL-08:32 | 15830.88 | 0.70 |
August | 0.00 | 0.00 | 0.380999E+10 | 0.184315E+10 | 14456.11 | 17-AUG-08:51 | 14456.11 | 0.69 |
September | 0.00 | 0.00 | 0.246367E+10 | 0.119969E+10 | 14184.90 | 11-SEP-08:51 | 14184.90 | 0.60 |
October | 0.00 | 0.00 | 0.344176E+09 | 0.176266E+09 | 13065.94 | 07-OCT-18:01 | 13065.94 | 0.10 |
November | 0.00 | 0.00 | 7414693.69 | 1991889.27 | 6080.20 | 11-NOV-09:02 | 4412.40 | 0.01 |
December | 0.00 | 0.00 | 741764.66 | 149902.10 | 1144.99 | 06-DEC-09:05 | 332.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184708E+11 | 0.947347E+10 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 741764.66 | 149902.10 | 1144.99 | 332.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.421735E+10 | 0.215868E+10 | 15830.88 | 15830.88 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6914499.88 | 3865253.12 | 3495.17 | 19-JAN-16:01 | 3495.17 | 0.01 |
February | 0.00 | 0.00 | 54437245.02 | 30953983.94 | 4431.45 | 17-FEB-16:01 | 4431.45 | 0.04 |
March | 0.00 | 0.00 | 23436405.82 | 14571788.77 | 3315.26 | 23-MAR-18:01 | 3315.26 | 0.02 |
April | 0.00 | 0.00 | 0.713904E+09 | 0.481547E+09 | 4431.22 | 12-APR-15:01 | 4431.22 | 0.39 |
May | 0.00 | 0.00 | 0.846400E+09 | 0.525097E+09 | 4431.14 | 11-MAY-18:01 | 4431.14 | 0.47 |
June | 0.00 | 0.00 | 0.130306E+10 | 0.748203E+09 | 4530.08 | 04-JUN-08:62 | 3378.70 | 0.71 |
July | 0.00 | 0.00 | 0.167328E+10 | 0.959871E+09 | 4432.51 | 08-JUL-08:61 | 3409.32 | 0.79 |
August | 0.00 | 0.00 | 0.152911E+10 | 0.829502E+09 | 4550.33 | 08-AUG-15:01 | 3521.40 | 0.84 |
September | 0.00 | 0.00 | 0.104759E+10 | 0.576682E+09 | 4449.57 | 02-SEP-08:61 | 3392.49 | 0.64 |
October | 0.00 | 0.00 | 0.221398E+09 | 0.131410E+09 | 4425.95 | 06-OCT-18:01 | 4425.95 | 0.16 |
November | 0.00 | 0.00 | 10905799.80 | 5386598.27 | 3628.36 | 10-NOV-16:01 | 3628.36 | 0.02 |
December | 0.00 | 0.00 | 41629.68 | 8237.26 | 181.19 | 02-DEC-09:06 | 28.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.743048E+10 | 0.430710E+10 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 41629.68 | 8237.26 | 181.19 | 28.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.167328E+10 | 0.959871E+09 | 4550.33 | 4431.45 | 0.84 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 549022.07 | 239806.96 | 2094.80 | 19-JAN-16:01 | 1803.12 | 0.00 |
February | 0.00 | 0.00 | 9030342.36 | 4328765.55 | 3164.75 | 27-FEB-16:02 | 3164.75 | 0.02 |
March | 0.00 | 0.00 | 10562500.29 | 5915174.07 | 2950.02 | 23-MAR-18:01 | 2950.02 | 0.01 |
April | 0.00 | 0.00 | 0.395675E+09 | 0.262884E+09 | 3942.70 | 12-APR-15:01 | 3942.70 | 0.25 |
May | 0.00 | 0.00 | 0.567002E+09 | 0.334757E+09 | 4233.84 | 22-MAY-21:31 | 3954.14 | 0.37 |
June | 0.00 | 0.00 | 0.990687E+09 | 0.547297E+09 | 4582.45 | 26-JUN-21:01 | 3713.58 | 0.61 |
July | 0.00 | 0.00 | 0.112719E+10 | 0.592904E+09 | 4527.42 | 23-JUL-21:31 | 3752.00 | 0.61 |
August | 0.00 | 0.00 | 0.811569E+09 | 0.371296E+09 | 4353.00 | 17-AUG-21:11 | 3656.73 | 0.61 |
September | 0.00 | 0.00 | 0.417875E+09 | 0.184395E+09 | 4243.49 | 12-SEP-20:11 | 3564.83 | 0.40 |
October | 0.00 | 0.00 | 66494590.92 | 38443653.02 | 3879.60 | 06-OCT-18:01 | 3879.60 | 0.06 |
November | 0.00 | 0.00 | 834403.37 | 352377.86 | 2671.39 | 10-NOV-16:01 | 2407.73 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.439747E+10 | 0.234281E+10 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112719E+10 | 0.592904E+09 | 4582.45 | 3954.14 | 0.61 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119694E+10 | 0.649401E+09 | 24652.89 | 10-JAN-16:01 | 24652.89 | 0.16 |
February | 0.00 | 0.00 | 0.148032E+10 | 0.770387E+09 | 19893.86 | 27-FEB-16:02 | 19893.86 | 0.23 |
March | 0.00 | 0.00 | 0.442639E+09 | 0.181169E+09 | 21150.90 | 25-MAR-15:01 | 21150.90 | 0.11 |
April | 0.00 | 0.00 | 0.549495E+10 | 0.325397E+10 | 21125.61 | 29-APR-08:61 | 21125.61 | 0.61 |
May | 0.00 | 0.00 | 0.464142E+10 | 0.228978E+10 | 24658.89 | 11-MAY-18:01 | 24658.89 | 0.60 |
June | 0.00 | 0.00 | 0.627820E+10 | 0.286883E+10 | 25013.87 | 26-JUN-18:02 | 20486.99 | 0.80 |
July | 0.00 | 0.00 | 0.821891E+10 | 0.392825E+10 | 24414.77 | 29-JUL-15:01 | 20931.37 | 0.84 |
August | 0.00 | 0.00 | 0.954685E+10 | 0.494181E+10 | 25293.79 | 08-AUG-15:01 | 19662.27 | 0.90 |
September | 0.00 | 0.00 | 0.923771E+10 | 0.545321E+10 | 24998.62 | 16-SEP-15:02 | 18971.09 | 0.84 |
October | 0.00 | 0.00 | 0.344221E+10 | 0.197177E+10 | 24662.60 | 06-OCT-18:01 | 24662.60 | 0.40 |
November | 0.00 | 0.00 | 0.963437E+09 | 0.434343E+09 | 20461.05 | 10-NOV-16:01 | 20461.05 | 0.17 |
December | 0.00 | 0.00 | 0.359119E+09 | 0.193574E+09 | 19602.95 | 21-DEC-16:02 | 19602.95 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.513027E+11 | 0.269365E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.359119E+09 | 0.181169E+09 | 19602.95 | 18971.09 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.954685E+10 | 0.545321E+10 | 25293.79 | 24662.60 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 37276.10 | 167466.69 | 30-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26413.34 | 156596.16 | 06-FEB-16:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 34531.10 | 148249.05 | 28-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32101.12 | 131239.11 | 07-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 39218.36 | 134196.82 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 29242.34 | 112975.55 | 07-JUN-10:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19174.97 | 102538.62 | 09-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14269.72 | 103133.78 | 24-AUG-05:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28607.91 | 120746.53 | 28-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 44835.15 | 175991.23 | 19-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 48002.78 | 169243.11 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 33518.10 | 178407.92 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 32289.66 | ||||
Minimum of Months | 0.00 | 0.00 | 14269.72 | 102538.62 | ||
Maximum of Months | 0.00 | 0.00 | 48002.78 | 178407.92 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2105.53 | 47069.28 | 21-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 2362.41 | 47867.36 | 19-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2540.85 | 67160.17 | 20-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 27598.29 | 357173.59 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28677.30 | 344894.04 | 22-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 54229.77 | 439224.65 | 25-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 72939.72 | 425132.45 | 22-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 79066.97 | 395838.02 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56054.17 | 362005.73 | 13-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 12761.17 | 245827.52 | 07-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2443.05 | 68496.60 | 10-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 460.39 | 33679.99 | 10-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 28578.13 | 0.00 | ||||
Minimum of Months | 460.39 | 33679.99 | 0.00 | 0.00 | ||
Maximum of Months | 79066.97 | 439224.65 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 28108.02 | 57257.35 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28291.29 | 57344.61 | 17-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 28129.23 | 57254.63 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27609.92 | 56412.10 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26917.28 | 55214.61 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26226.31 | 53626.01 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25687.12 | 52254.61 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25518.97 | 51583.30 | 01-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 25693.23 | 52247.61 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26195.09 | 53633.04 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26894.39 | 55135.97 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27591.54 | 56417.60 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 26897.09 | ||||
Minimum of Months | 0.00 | 0.00 | 25518.97 | 51583.30 | ||
Maximum of Months | 0.00 | 0.00 | 28291.29 | 57344.61 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.70 | 1299.30 | 01-JAN-17:10 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 10-FEB-10:05 | 0.88 |
March | 0.271000E+10 | 0.70 | 1299.30 | 01-MAR-09:04 | 0.88 |
April | 0.262258E+10 | 0.70 | 1299.30 | 11-APR-15:15 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 01-MAY-16:50 | 0.88 |
June | 0.262258E+10 | 0.70 | 1299.30 | 02-JUN-15:07 | 0.88 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-18:07 | 0.88 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-15:18 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 01-SEP-15:09 | 0.88 |
October | 0.271000E+10 | 0.70 | 1299.30 | 01-OCT-15:50 | 0.88 |
November | 0.262258E+10 | 0.70 | 1299.30 | 17-NOV-16:30 | 0.88 |
December | 0.271000E+10 | 0.70 | 1299.30 | 07-DEC-10:05 | 0.88 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331589E+11 | 0.79 | 18075.14 | 18-JAN-21:10 | 0.98 |
February | 0.300914E+11 | 0.79 | 18025.65 | 27-FEB-21:10 | 0.98 |
March | 0.337982E+11 | 0.80 | 18252.13 | 22-MAR-20:10 | 0.99 |
April | 0.337232E+11 | 0.81 | 21811.78 | 28-APR-21:10 | 1.10 |
May | 0.351664E+11 | 0.82 | 22197.59 | 22-MAY-21:10 | 1.10 |
June | 0.348720E+11 | 0.82 | 23690.29 | 13-JUN-21:10 | 1.15 |
July | 0.363205E+11 | 0.83 | 24001.56 | 21-JUL-21:10 | 1.16 |
August | 0.363573E+11 | 0.83 | 23990.65 | 14-AUG-21:10 | 1.16 |
September | 0.346187E+11 | 0.82 | 23803.80 | 12-SEP-21:10 | 1.15 |
October | 0.343945E+11 | 0.81 | 20769.96 | 03-OCT-21:10 | 1.07 |
November | 0.326326E+11 | 0.80 | 19152.18 | 08-NOV-21:10 | 1.01 |
December | 0.329868E+11 | 0.79 | 18088.50 | 20-DEC-21:10 | 0.98 |
Annual Sum or Average | 0.408120E+12 | 0.81 | |||
Minimum of Months | 0.300914E+11 | 0.79 | 18025.65 | 0.98 | |
Maximum of Months | 0.363573E+11 | 0.83 | 24001.56 | 1.16 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:10 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321728E+09 | 0.42 | 830.07 | 01-JAN-09:02 | 0.58 |
February | 0.258342E+09 | 0.42 | 830.07 | 01-FEB-09:02 | 0.58 |
March | 0.255469E+09 | 0.41 | 830.07 | 01-MAR-09:02 | 0.58 |
April | 0.212950E+09 | 0.48 | 830.07 | 01-APR-15:01 | 0.58 |
May | 0.216146E+09 | 0.47 | 830.07 | 01-MAY-15:01 | 0.58 |
June | 0.247320E+09 | 0.50 | 830.07 | 01-JUN-08:62 | 0.58 |
July | 0.309256E+09 | 0.51 | 830.07 | 01-JUL-08:62 | 0.58 |
August | 0.286567E+09 | 0.52 | 830.07 | 01-AUG-08:62 | 0.58 |
September | 0.227109E+09 | 0.51 | 830.07 | 01-SEP-15:01 | 0.58 |
October | 0.199789E+09 | 0.44 | 830.07 | 01-OCT-08:61 | 0.58 |
November | 0.271809E+09 | 0.42 | 830.07 | 01-NOV-08:62 | 0.58 |
December | 0.401793E+09 | 0.45 | 830.07 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.320828E+10 | 0.46 | |||
Minimum of Months | 0.199789E+09 | 0.41 | 830.07 | 0.58 | |
Maximum of Months | 0.401793E+09 | 0.52 | 830.07 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351042E+09 | 0.44 | 743.92 | 01-JAN-09:02 | 0.58 |
February | 0.275209E+09 | 0.41 | 743.92 | 01-FEB-09:02 | 0.58 |
March | 0.256379E+09 | 0.41 | 743.92 | 01-MAR-09:02 | 0.58 |
April | 0.165625E+09 | 0.43 | 743.92 | 01-APR-15:01 | 0.58 |
May | 0.163662E+09 | 0.43 | 743.92 | 01-MAY-15:01 | 0.58 |
June | 0.184375E+09 | 0.43 | 743.92 | 01-JUN-08:62 | 0.58 |
July | 0.196582E+09 | 0.39 | 743.92 | 01-JUL-08:62 | 0.58 |
August | 0.149418E+09 | 0.36 | 743.92 | 01-AUG-08:51 | 0.58 |
September | 0.114659E+09 | 0.39 | 743.92 | 01-SEP-15:01 | 0.58 |
October | 0.190100E+09 | 0.41 | 743.92 | 01-OCT-15:02 | 0.58 |
November | 0.289070E+09 | 0.42 | 743.92 | 01-NOV-08:62 | 0.58 |
December | 0.409091E+09 | 0.47 | 743.92 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.274521E+10 | 0.42 | |||
Minimum of Months | 0.114659E+09 | 0.36 | 743.92 | 0.58 | |
Maximum of Months | 0.409091E+09 | 0.47 | 743.92 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 76519035.72 | 0.04 | 1032.26 | 21-JAN-11:25 | 0.58 |
February | 61995821.02 | 0.05 | 802.65 | 22-FEB-11:25 | 0.58 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.856445E+09 | 0.34 | 1445.86 | 30-APR-12:50 | 0.58 |
May | 0.734735E+09 | 0.33 | 1151.76 | 22-MAY-13:15 | 0.58 |
June | 0.922006E+09 | 0.43 | 1175.89 | 13-JUN-13:20 | 0.58 |
July | 0.119510E+10 | 0.49 | 1338.24 | 22-JUL-13:30 | 0.58 |
August | 0.144825E+10 | 0.52 | 1428.24 | 20-AUG-13:00 | 0.58 |
September | 0.146015E+10 | 0.49 | 1732.18 | 27-SEP-12:40 | 0.58 |
October | 0.546405E+09 | 0.20 | 1563.63 | 07-OCT-13:00 | 0.58 |
November | 55909682.89 | 0.04 | 927.15 | 11-NOV-13:30 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.735751E+10 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146015E+10 | 0.52 | 1732.18 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102750E+10 | 0.41 | 3789.08 | 01-JAN-09:02 | 0.58 |
February | 0.786749E+09 | 0.41 | 3789.08 | 01-FEB-16:02 | 0.58 |
March | 0.662982E+09 | 0.41 | 3789.08 | 02-MAR-19:02 | 0.58 |
April | 0.802893E+09 | 0.40 | 3789.08 | 01-APR-08:62 | 0.58 |
May | 0.100274E+10 | 0.39 | 3789.08 | 01-MAY-08:62 | 0.58 |
June | 0.142979E+10 | 0.38 | 3789.08 | 01-JUN-08:62 | 0.58 |
July | 0.147069E+10 | 0.35 | 3789.08 | 01-JUL-08:62 | 0.58 |
August | 0.118808E+10 | 0.31 | 3789.08 | 01-AUG-08:51 | 0.58 |
September | 0.910409E+09 | 0.35 | 3789.08 | 01-SEP-08:53 | 0.58 |
October | 0.584841E+09 | 0.40 | 3789.08 | 01-OCT-08:61 | 0.58 |
November | 0.724708E+09 | 0.41 | 3789.08 | 02-NOV-18:02 | 0.58 |
December | 0.113910E+10 | 0.41 | 3789.08 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.117305E+11 | 0.39 | |||
Minimum of Months | 0.584841E+09 | 0.31 | 3789.08 | 0.58 | |
Maximum of Months | 0.147069E+10 | 0.41 | 3789.08 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301252E+09 | 0.42 | 755.18 | 01-JAN-16:01 | 0.58 |
February | 0.244022E+09 | 0.41 | 755.18 | 01-FEB-09:02 | 0.58 |
March | 0.237912E+09 | 0.41 | 755.18 | 01-MAR-09:02 | 0.58 |
April | 0.217475E+09 | 0.51 | 755.18 | 01-APR-15:01 | 0.58 |
May | 0.206824E+09 | 0.50 | 755.18 | 01-MAY-08:62 | 0.58 |
June | 0.227187E+09 | 0.52 | 755.18 | 01-JUN-08:62 | 0.58 |
July | 0.276992E+09 | 0.54 | 755.18 | 01-JUL-08:62 | 0.58 |
August | 0.289521E+09 | 0.54 | 755.18 | 01-AUG-08:62 | 0.58 |
September | 0.239239E+09 | 0.53 | 755.18 | 01-SEP-15:01 | 0.58 |
October | 0.190323E+09 | 0.45 | 755.18 | 01-OCT-08:61 | 0.58 |
November | 0.254213E+09 | 0.42 | 755.18 | 01-NOV-08:62 | 0.58 |
December | 0.364006E+09 | 0.45 | 755.18 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.304897E+10 | 0.47 | |||
Minimum of Months | 0.190323E+09 | 0.41 | 755.18 | 0.58 | |
Maximum of Months | 0.364006E+09 | 0.54 | 755.18 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338515E+09 | 0.44 | 681.26 | 01-JAN-16:01 | 0.58 |
February | 0.266134E+09 | 0.42 | 681.26 | 01-FEB-09:02 | 0.58 |
March | 0.240537E+09 | 0.41 | 681.26 | 01-MAR-09:02 | 0.58 |
April | 0.165242E+09 | 0.44 | 681.26 | 01-APR-15:01 | 0.58 |
May | 0.162907E+09 | 0.45 | 681.26 | 01-MAY-08:62 | 0.58 |
June | 0.178202E+09 | 0.46 | 681.26 | 01-JUN-08:62 | 0.58 |
July | 0.196070E+09 | 0.43 | 681.26 | 01-JUL-08:62 | 0.58 |
August | 0.176372E+09 | 0.41 | 681.26 | 01-AUG-08:51 | 0.58 |
September | 0.138487E+09 | 0.44 | 681.26 | 01-SEP-15:01 | 0.58 |
October | 0.177366E+09 | 0.41 | 681.26 | 01-OCT-08:61 | 0.58 |
November | 0.270081E+09 | 0.42 | 681.26 | 01-NOV-08:62 | 0.58 |
December | 0.375420E+09 | 0.47 | 681.26 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.268533E+10 | 0.43 | |||
Minimum of Months | 0.138487E+09 | 0.41 | 681.26 | 0.58 | |
Maximum of Months | 0.375420E+09 | 0.47 | 681.26 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 99877010.02 | 0.45 | 218.43 | 01-JAN-09:02 | 0.58 |
February | 79428044.54 | 0.43 | 218.43 | 01-FEB-09:02 | 0.58 |
March | 78566077.95 | 0.42 | 218.43 | 01-MAR-09:02 | 0.58 |
April | 65296991.99 | 0.48 | 218.43 | 01-APR-08:62 | 0.58 |
May | 63773427.64 | 0.48 | 218.43 | 01-MAY-15:01 | 0.58 |
June | 67234201.87 | 0.51 | 218.43 | 01-JUN-15:01 | 0.58 |
July | 82562878.03 | 0.52 | 218.43 | 01-JUL-15:01 | 0.58 |
August | 72449581.15 | 0.52 | 218.43 | 01-AUG-15:01 | 0.58 |
September | 60549879.57 | 0.51 | 218.43 | 01-SEP-15:01 | 0.58 |
October | 62725919.66 | 0.44 | 218.43 | 01-OCT-15:02 | 0.58 |
November | 84419947.91 | 0.43 | 218.43 | 01-NOV-08:62 | 0.58 |
December | 0.122740E+09 | 0.48 | 218.43 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.939624E+09 | 0.47 | |||
Minimum of Months | 60549879.57 | 0.42 | 218.43 | 0.58 | |
Maximum of Months | 0.122740E+09 | 0.52 | 218.43 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113056E+09 | 0.47 | 194.24 | 01-JAN-09:02 | 0.58 |
February | 83166718.54 | 0.43 | 194.24 | 01-FEB-09:02 | 0.58 |
March | 77744805.87 | 0.42 | 194.24 | 01-MAR-09:02 | 0.58 |
April | 52120098.39 | 0.43 | 194.24 | 01-APR-08:62 | 0.58 |
May | 49523209.46 | 0.43 | 194.24 | 01-MAY-15:01 | 0.58 |
June | 50887208.54 | 0.44 | 194.24 | 01-JUN-08:62 | 0.58 |
July | 54341813.06 | 0.40 | 194.24 | 01-JUL-15:01 | 0.58 |
August | 37825719.47 | 0.37 | 194.24 | 01-AUG-08:51 | 0.58 |
September | 32224170.95 | 0.39 | 194.24 | 01-SEP-15:01 | 0.58 |
October | 60485602.71 | 0.41 | 194.24 | 01-OCT-15:02 | 0.58 |
November | 88570343.27 | 0.44 | 194.24 | 01-NOV-08:62 | 0.58 |
December | 0.126535E+09 | 0.52 | 194.24 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.826480E+09 | 0.43 | |||
Minimum of Months | 32224170.95 | 0.37 | 194.24 | 0.58 | |
Maximum of Months | 0.126535E+09 | 0.52 | 194.24 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.368839E+09 | 0.45 | 1212.10 | 01-JAN-16:01 | 0.58 |
February | 0.308678E+09 | 0.45 | 1212.10 | 01-FEB-09:02 | 0.58 |
March | 0.292639E+09 | 0.42 | 1212.10 | 01-MAR-09:02 | 0.58 |
April | 0.344013E+09 | 0.51 | 1212.10 | 01-APR-15:01 | 0.58 |
May | 0.287323E+09 | 0.49 | 1212.10 | 01-MAY-15:01 | 0.58 |
June | 0.295798E+09 | 0.51 | 1212.10 | 01-JUN-08:62 | 0.58 |
July | 0.369282E+09 | 0.52 | 1212.10 | 01-JUL-08:62 | 0.58 |
August | 0.418218E+09 | 0.52 | 1212.10 | 01-AUG-15:01 | 0.58 |
September | 0.426455E+09 | 0.53 | 1212.10 | 01-SEP-15:01 | 0.58 |
October | 0.293072E+09 | 0.47 | 1212.10 | 01-OCT-08:61 | 0.58 |
November | 0.301416E+09 | 0.45 | 1212.10 | 01-NOV-15:02 | 0.58 |
December | 0.455762E+09 | 0.45 | 1212.10 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.416149E+10 | 0.48 | |||
Minimum of Months | 0.287323E+09 | 0.42 | 1212.10 | 0.58 | |
Maximum of Months | 0.455762E+09 | 0.53 | 1212.10 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.808405E+09 | 0.727565E+09 | 747.04 | 30-JAN-16:02 | 672.33 | 672.33 | 34.09 | 1.55 |
February | 0.567098E+09 | 0.510388E+09 | 731.98 | 06-FEB-16:02 | 658.78 | 658.78 | 34.17 | 1.45 |
March | 0.717041E+09 | 0.645337E+09 | 718.94 | 28-MAR-08:04 | 647.05 | 647.05 | 34.26 | 1.38 |
April | 0.569259E+09 | 0.512333E+09 | 714.27 | 06-APR-08:07 | 642.84 | 642.84 | 38.07 | 1.35 |
May | 0.670853E+09 | 0.603768E+09 | 695.47 | 05-MAY-08:05 | 625.92 | 625.92 | 34.61 | 1.26 |
June | 0.472936E+09 | 0.425643E+09 | 665.53 | 08-JUN-06:05 | 598.98 | 598.98 | 41.20 | 1.14 |
July | 0.320991E+09 | 0.288891E+09 | 624.24 | 09-JUL-04:00 | 561.81 | 561.81 | 35.58 | 1.00 |
August | 0.238820E+09 | 0.214938E+09 | 610.65 | 23-AUG-04:07 | 549.59 | 549.59 | 35.15 | 0.96 |
September | 0.465434E+09 | 0.418891E+09 | 688.43 | 28-SEP-06:05 | 619.59 | 619.59 | 36.74 | 1.23 |
October | 0.798330E+09 | 0.718497E+09 | 760.02 | 19-OCT-08:04 | 684.02 | 684.02 | 34.35 | 1.64 |
November | 0.880384E+09 | 0.792346E+09 | 750.98 | 21-NOV-16:02 | 675.88 | 675.88 | 34.27 | 1.57 |
December | 0.770795E+09 | 0.693715E+09 | 761.37 | 16-DEC-16:04 | 685.23 | 685.23 | 34.17 | 1.65 |
Annual Sum or Average | 0.728035E+10 | 0.655231E+10 | ||||||
Minimum of Months | 0.238820E+09 | 0.214938E+09 | 610.65 | 549.59 | 549.59 | 34.09 | 0.96 | |
Maximum of Months | 0.880384E+09 | 0.792346E+09 | 761.37 | 685.23 | 685.23 | 41.20 | 1.65 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.138194E+09 | 0.124375E+09 | 1159.99 | 21-JAN-09:02 | 1043.99 | 1043.99 | 6.72 | 2.68 |
February | 0.143116E+09 | 0.128804E+09 | 1256.92 | 20-FEB-09:02 | 1131.22 | 1131.22 | 6.72 | 2.97 |
March | 0.188317E+09 | 0.169485E+09 | 1457.60 | 20-MAR-15:01 | 1311.84 | 1311.84 | 6.72 | 3.63 |
April | 0.146619E+10 | 0.131957E+10 | 2439.98 | 29-APR-15:03 | 2195.98 | 2195.98 | 6.72 | 10.15 |
May | 0.161728E+10 | 0.145555E+10 | 2413.53 | 22-MAY-15:02 | 2172.18 | 2172.18 | 6.72 | 9.73 |
June | 0.237862E+10 | 0.214076E+10 | 2517.37 | 12-JUN-18:02 | 2265.64 | 2265.64 | 6.72 | 11.61 |
July | 0.300274E+10 | 0.270246E+10 | 2562.93 | 22-JUL-18:03 | 2306.64 | 2306.64 | 6.72 | 12.59 |
August | 0.323964E+10 | 0.291567E+10 | 2576.27 | 14-AUG-18:40 | 2318.64 | 2318.64 | 6.72 | 12.87 |
September | 0.246436E+10 | 0.221792E+10 | 2510.82 | 25-SEP-15:03 | 2259.74 | 2259.74 | 6.72 | 11.47 |
October | 0.777569E+09 | 0.699812E+09 | 2196.66 | 07-OCT-15:03 | 1976.99 | 1976.99 | 6.72 | 7.38 |
November | 0.159980E+09 | 0.143982E+09 | 1483.94 | 05-NOV-15:01 | 1335.55 | 1335.55 | 6.72 | 3.72 |
December | 26776253.19 | 24098627.87 | 826.95 | 02-DEC-09:02 | 744.25 | 744.25 | 6.72 | 1.78 |
Annual Sum or Average | 0.156028E+11 | 0.140425E+11 | ||||||
Minimum of Months | 26776253.19 | 24098627.87 | 826.95 | 744.25 | 744.25 | 6.72 | 1.78 | |
Maximum of Months | 0.323964E+10 | 0.291567E+10 | 2576.27 | 2318.64 | 2318.64 | 6.72 | 12.87 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.166697E+10 | 0.150027E+10 | 2220.45 | 01-JAN-09:00 | 1998.40 | 1998.40 | 6.77 | 19.64 |
February | 0.171658E+10 | 0.154493E+10 | 2220.45 | 01-FEB-06:15 | 1998.40 | 1998.40 | 6.74 | 19.64 |
March | 0.207401E+10 | 0.186661E+10 | 2220.45 | 01-MAR-07:05 | 1998.40 | 1998.40 | 6.74 | 19.64 |
April | 0.480751E+10 | 0.432676E+10 | 2220.45 | 01-APR-06:40 | 1998.40 | 1998.40 | 6.73 | 19.64 |
May | 0.536966E+10 | 0.483270E+10 | 2220.45 | 01-MAY-00:05 | 1998.40 | 1998.40 | 7.10 | 19.64 |
June | 0.571414E+10 | 0.514273E+10 | 2220.45 | 01-JUN-00:05 | 1998.40 | 1998.40 | 6.92 | 19.64 |
July | 0.594325E+10 | 0.534892E+10 | 2220.45 | 01-JUL-00:10 | 1998.40 | 1998.40 | 6.85 | 19.64 |
August | 0.594725E+10 | 0.535252E+10 | 2220.45 | 01-AUG-00:05 | 1998.40 | 1998.40 | 7.01 | 19.64 |
September | 0.570433E+10 | 0.513390E+10 | 2220.45 | 01-SEP-00:05 | 1998.40 | 1998.40 | 6.99 | 19.64 |
October | 0.370808E+10 | 0.333727E+10 | 2220.45 | 01-OCT-00:10 | 1998.40 | 1998.40 | 6.80 | 19.64 |
November | 0.185281E+10 | 0.166753E+10 | 2220.45 | 01-NOV-05:03 | 1998.40 | 1998.40 | 6.74 | 19.64 |
December | 0.637046E+09 | 0.573342E+09 | 2220.45 | 01-DEC-07:50 | 1998.40 | 1998.40 | 6.73 | 19.64 |
Annual Sum or Average | 0.451416E+11 | 0.406275E+11 | ||||||
Minimum of Months | 0.637046E+09 | 0.573342E+09 | 2220.45 | 1998.40 | 1998.40 | 6.73 | 19.64 | |
Maximum of Months | 0.594725E+10 | 0.535252E+10 | 2220.45 | 1998.40 | 1998.40 | 7.10 | 19.64 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.37 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.67 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.30 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.86 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.72 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 51.25 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.89 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.20 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.04 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.27 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.85 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.66 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.30 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.20 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 40.49 | 60.00 | 37276.10 | 167466.69 | 30-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 43.99 | 60.00 | 26413.34 | 156596.16 | 06-FEB-16:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45.38 | 60.00 | 34531.10 | 148249.05 | 28-MAR-08:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 46.39 | 60.00 | 32101.12 | 131239.11 | 07-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.15 | 60.00 | 39218.36 | 134196.82 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.44 | 60.00 | 29242.34 | 112975.55 | 07-JUN-10:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.12 | 60.00 | 19174.97 | 102538.62 | 09-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.83 | 60.00 | 14269.72 | 103133.78 | 24-AUG-05:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.88 | 60.00 | 28607.91 | 120746.53 | 28-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.66 | 60.00 | 44835.15 | 175991.23 | 19-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 47.79 | 60.00 | 48002.78 | 169243.11 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 42.40 | 60.00 | 33518.10 | 178407.92 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 32289.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.88 | 60.00 | 14269.72 | 102538.62 | ||
Maximum of Months | 0.00 | 0.00 | 47.79 | 60.00 | 48002.78 | 178407.92 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2105.53 | 47069.28 | 21-JAN-16:01 | 7.27 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 2362.41 | 47867.36 | 19-FEB-16:02 | 7.28 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2540.85 | 67160.17 | 20-MAR-18:03 | 7.52 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 27598.29 | 357173.59 | 30-APR-18:03 | 11.04 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28677.30 | 344894.04 | 22-MAY-15:03 | 10.89 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 54229.77 | 439224.65 | 25-JUN-18:03 | 12.04 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 72939.72 | 425132.45 | 22-JUL-18:03 | 11.87 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 79066.97 | 395838.02 | 14-AUG-18:03 | 11.51 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56054.17 | 362005.73 | 13-SEP-15:03 | 11.10 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 12761.17 | 245827.52 | 07-OCT-15:03 | 9.69 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2443.05 | 68496.60 | 10-NOV-16:01 | 7.53 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 460.39 | 33679.99 | 10-DEC-09:02 | 7.11 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 28578.13 | 0.00 | ||||||
Minimum of Months | 460.39 | 33679.99 | 7.11 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 79066.97 | 439224.65 | 12.04 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.37 | 59.42 | 28108.02 | 57257.35 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.67 | 59.60 | 28291.29 | 57344.61 | 17-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.30 | 58.71 | 28129.23 | 57254.63 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.86 | 59.59 | 27609.92 | 56412.10 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.72 | 59.61 | 26917.28 | 55214.61 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 51.25 | 58.34 | 26226.31 | 53626.01 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.89 | 58.73 | 25687.12 | 52254.61 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.20 | 59.41 | 25518.97 | 51583.30 | 01-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.04 | 58.86 | 25693.23 | 52247.61 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.27 | 58.98 | 26195.09 | 53633.04 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.85 | 59.21 | 26894.39 | 55135.97 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.66 | 58.33 | 27591.54 | 56417.60 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 26897.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.30 | 58.33 | 25518.97 | 51583.30 | ||
Maximum of Months | 0.00 | 0.00 | 52.20 | 59.61 | 28291.29 | 57344.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.690578E+11 | 0.00 | 0.00 | 0.331589E+11 | 0.00 | 0.00 |
February | 0.408315E+11 | 0.00 | 0.00 | 0.300914E+11 | 0.00 | 0.00 |
March | 0.748516E+11 | 0.00 | 0.00 | 0.337982E+11 | 0.00 | 0.00 |
April | 0.796116E+11 | 0.00 | 0.151075E+11 | 0.337232E+11 | 0.00 | 0.00 |
May | 0.103091E+12 | 0.00 | 0.152687E+11 | 0.351664E+11 | 0.00 | 0.00 |
June | 0.759044E+11 | 0.00 | 0.489415E+11 | 0.348720E+11 | 0.00 | 0.00 |
July | 0.513840E+11 | 0.00 | 0.845862E+11 | 0.363205E+11 | 0.00 | 0.00 |
August | 0.383572E+11 | 0.00 | 0.984892E+11 | 0.363573E+11 | 0.00 | 0.00 |
September | 0.737827E+11 | 0.00 | 0.507150E+11 | 0.346187E+11 | 0.00 | 0.00 |
October | 0.111423E+12 | 0.00 | 0.262849E+10 | 0.343945E+11 | 0.00 | 0.00 |
November | 0.103270E+12 | 0.00 | 49361593.28 | 0.326326E+11 | 0.00 | 0.00 |
December | 0.515114E+11 | 0.00 | 0.00 | 0.329868E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.873076E+12 | 0.00 | 0.315786E+12 | 0.408120E+12 | 0.00 | 0.00 |
Minimum of Months | 0.383572E+11 | 0.00 | 0.00 | 0.300914E+11 | 0.00 | 0.00 |
Maximum of Months | 0.111423E+12 | 0.00 | 0.984892E+11 | 0.363573E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.256857E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 83240968.97 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 2041521.93 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
April | 7695.13 | 0.00 | 0.871147E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 6260.53 | 0.00 | 0.908483E+09 | 0.271000E+10 | 0.00 | 0.00 |
June | 12381.74 | 0.00 | 0.290719E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 25492.16 | 0.00 | 0.528320E+10 | 0.271000E+10 | 0.00 | 0.00 |
August | 23976.73 | 0.00 | 0.612254E+10 | 0.271000E+10 | 0.00 | 0.00 |
September | 12646.93 | 0.00 | 0.309471E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 2880.11 | 0.00 | 0.156128E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 6868145.00 | 0.00 | 0.00 | 0.262258E+10 | 0.00 | 0.00 |
December | 51874153.82 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.400973E+09 | 0.00 | 0.193434E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 2880.11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.256857E+09 | 0.00 | 0.612254E+10 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331589E+11 | 0.00 | 0.690578E+11 | 0.469805E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300914E+11 | 0.00 | 0.408315E+11 | 0.446350E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337982E+11 | 0.00 | 0.748516E+11 | 0.377125E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337232E+11 | 0.151075E+11 | 0.796116E+11 | 0.205992E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351664E+11 | 0.152687E+11 | 0.103091E+12 | 0.132272E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.348720E+11 | 0.489415E+11 | 0.759044E+11 | 0.193227E+11 | 0.120913E+09 | 0.00 | 0.00 | 0.00 |
July | 0.363205E+11 | 0.845862E+11 | 0.513840E+11 | 0.399422E+10 | 0.702199E+09 | 0.00 | 0.00 | 0.00 |
August | 0.363573E+11 | 0.984892E+11 | 0.383572E+11 | 0.102208E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346187E+11 | 0.507150E+11 | 0.737827E+11 | 0.203233E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343945E+11 | 0.262849E+10 | 0.111423E+12 | 0.151824E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326326E+11 | 49361593.28 | 0.103270E+12 | 0.288790E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329868E+11 | 0.00 | 0.515114E+11 | 0.503820E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408120E+12 | 0.315786E+12 | 0.873076E+12 | 0.262064E+13 | 0.823112E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300914E+11 | 0.00 | 0.383572E+11 | 0.102208E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363573E+11 | 0.984892E+11 | 0.111423E+12 | 0.503820E+12 | 0.702199E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.256857E+09 | 0.420723E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 83240968.97 | 0.384670E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 2041521.93 | 0.366236E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.871147E+09 | 7695.13 | 0.260210E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.908483E+09 | 6260.53 | 0.217424E+11 | 2150578.68 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.290719E+10 | 12381.74 | 0.955353E+10 | 0.123014E+09 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.528320E+10 | 25492.16 | 0.580121E+10 | 0.187550E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.612254E+10 | 23976.73 | 0.419070E+10 | 26373329.80 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.309471E+10 | 12646.93 | 0.103632E+11 | 1828335.83 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.156128E+09 | 2880.11 | 0.237033E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 6868145.00 | 0.320624E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 51874153.82 | 0.428466E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.193434E+11 | 0.400973E+09 | 0.293447E+12 | 0.340916E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 2880.11 | 0.419070E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.612254E+10 | 0.256857E+09 | 0.428466E+11 | 0.187550E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331589E+11 | 0.690578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300914E+11 | 0.408315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337982E+11 | 0.748516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337232E+11 | 0.796116E+11 | 0.151075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351664E+11 | 0.103091E+12 | 0.152687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.348720E+11 | 0.759044E+11 | 0.489415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.363205E+11 | 0.513840E+11 | 0.845862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363573E+11 | 0.383572E+11 | 0.984892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346187E+11 | 0.737827E+11 | 0.507150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343945E+11 | 0.111423E+12 | 0.262849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326326E+11 | 0.103270E+12 | 49361593.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329868E+11 | 0.515114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408120E+12 | 0.873076E+12 | 0.315786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300914E+11 | 0.383572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363573E+11 | 0.111423E+12 | 0.984892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.256857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 83240968.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 2041521.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 7695.13 | 0.871147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 6260.53 | 0.908483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 12381.74 | 0.290719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 25492.16 | 0.528320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 23976.73 | 0.612254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 12646.93 | 0.309471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 2880.11 | 0.156128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 6868145.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 51874153.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.400973E+09 | 0.193434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 2880.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.256857E+09 | 0.612254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.411181E+11 | 0.00 | 0.00 | 3493585.57 | 0.00 | 0.00 | 0.743132E+10 | 0.00 | 0.97 |
February | 0.383047E+11 | 0.00 | 0.00 | 922165.63 | 0.00 | 0.00 | 0.381875E+10 | 0.00 | 0.98 |
March | 0.493978E+11 | 0.00 | 0.00 | 22407.55 | 0.00 | 0.00 | 0.259055E+09 | 0.00 | 0.97 |
April | 0.505334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
May | 0.543715E+11 | 0.00 | 0.00 | 567.18 | 0.00 | 0.00 | 33791011.26 | 0.00 | 0.97 |
June | 0.458624E+11 | 0.00 | 0.00 | 240963.31 | 39391242.91 | 0.00 | 0.243705E+10 | 0.00 | 0.97 |
July | 0.393450E+11 | 0.00 | 0.00 | 2227661.27 | 1287836.75 | 0.00 | 0.544494E+10 | 0.00 | 0.97 |
August | 0.339963E+11 | 0.00 | 0.00 | 5256514.71 | 0.00 | 0.00 | 0.858927E+10 | 0.00 | 0.98 |
September | 0.215839E+11 | 0.00 | 0.00 | 14790587.92 | 0.00 | 0.00 | 0.273452E+11 | 0.00 | 0.99 |
October | 0.217663E+11 | 0.00 | 0.00 | 19758096.65 | 0.00 | 0.00 | 0.344943E+11 | 0.00 | 0.99 |
November | 0.214132E+11 | 0.00 | 0.00 | 19559058.61 | 0.00 | 0.00 | 0.310060E+11 | 0.00 | 0.99 |
December | 0.288500E+11 | 0.00 | 0.00 | 11249985.94 | 0.00 | 0.00 | 0.173835E+11 | 0.00 | 0.98 |
Annual Sum or Average | 0.446543E+12 | 0.00 | 0.00 | 77521594.32 | 40679079.66 | 0.00 | 0.138243E+12 | 0.00 | 0.98 |
Minimum of Months | 0.214132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.543715E+11 | 0.00 | 0.00 | 19758096.65 | 39391242.91 | 0.00 | 0.344943E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.685673E+10 | 0.00 | 0.00 | 73623.46 | 0.00 | 0.169987E+10 | 0.191371E+09 | 0.00 | 3.15 |
February | 0.646667E+10 | 0.00 | 0.00 | 185047.76 | 0.00 | 0.839521E+09 | 0.290243E+09 | 0.00 | 3.17 |
March | 0.835814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588806E+09 | 0.00 | 0.00 | 3.16 |
April | 0.835555E+10 | 0.00 | 0.00 | 875547.04 | 0.00 | 0.00 | 0.766654E+09 | 0.00 | 3.18 |
May | 0.941571E+10 | 0.00 | 0.00 | 253671.60 | 0.00 | 0.00 | 0.386552E+09 | 0.00 | 3.16 |
June | 0.848491E+10 | 0.00 | 0.00 | 254311.81 | 7097329.83 | 0.00 | 0.217256E+09 | 0.00 | 3.17 |
July | 0.769522E+10 | 243752.45 | 0.00 | 672435.31 | 161.84 | 0.00 | 0.375927E+09 | 0.00 | 3.17 |
August | 0.706791E+10 | 0.00 | 0.00 | 1757530.94 | 0.00 | 0.00 | 0.624127E+09 | 0.00 | 3.20 |
September | 0.783046E+10 | 0.00 | 0.00 | 2739627.25 | 0.00 | 0.00 | 0.100157E+10 | 0.00 | 3.26 |
October | 0.938006E+10 | 0.00 | 0.00 | 740258.10 | 0.00 | 5492991.56 | 0.627127E+09 | 0.00 | 3.19 |
November | 0.852177E+10 | 0.00 | 0.00 | 58305.79 | 0.00 | 0.571238E+09 | 0.190772E+09 | 0.00 | 3.15 |
December | 0.476911E+10 | 0.00 | 0.00 | 15486.87 | 0.00 | 0.346464E+10 | 53907810.46 | 0.00 | 3.17 |
Annual Sum or Average | 0.932022E+11 | 243752.45 | 0.00 | 7625845.93 | 7097491.67 | 0.716956E+10 | 0.472551E+10 | 0.00 | 3.18 |
Minimum of Months | 0.476911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
Maximum of Months | 0.941571E+10 | 243752.45 | 0.00 | 2739627.25 | 7097329.83 | 0.346464E+10 | 0.100157E+10 | 0.00 | 3.26 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
February | 0.385681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
March | 0.454647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
April | 0.411399E+10 | 0.00 | 0.00 | 270447.14 | 0.00 | 0.00 | 0.514842E+09 | 0.00 | 1.40 |
May | 0.440865E+10 | 0.00 | 0.00 | 322558.09 | 0.00 | 0.00 | 0.576914E+09 | 0.00 | 1.39 |
June | 0.336061E+10 | 0.00 | 0.00 | 677765.11 | 3606570.45 | 0.00 | 0.107355E+10 | 0.00 | 1.40 |
July | 0.274337E+10 | 82714.46 | 0.00 | 1287843.74 | 35196.88 | 0.00 | 0.138988E+10 | 0.00 | 1.41 |
August | 0.239251E+10 | 0.00 | 0.00 | 1305696.58 | 0.00 | 0.00 | 0.153893E+10 | 0.00 | 1.41 |
September | 0.304054E+10 | 0.00 | 0.00 | 918537.12 | 0.00 | 0.00 | 0.142729E+10 | 0.00 | 1.41 |
October | 0.479189E+10 | 0.00 | 0.00 | 128685.92 | 0.00 | 0.00 | 0.277271E+09 | 0.00 | 1.40 |
November | 0.471766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
December | 0.421146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.466294E+11 | 82714.46 | 0.00 | 4911533.71 | 3641767.33 | 0.00 | 0.679868E+10 | 0.00 | 1.40 |
Minimum of Months | 0.239251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
Maximum of Months | 0.479189E+10 | 82714.46 | 0.00 | 1305696.58 | 3606570.45 | 0.00 | 0.153893E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78616011.50 | 0.00 | 0.00 | 0.48 |
February | 0.285588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
March | 0.336657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.342599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.327455E+10 | 0.00 | 0.00 | 0.00 | 2670589.46 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.301895E+10 | 0.00 | 0.00 | 9543.02 | 87310.86 | 0.00 | 17796722.91 | 0.00 | 0.49 |
August | 0.288751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.328605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.375370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.349333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.307611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42381068.65 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.393402E+11 | 0.00 | 0.00 | 9543.02 | 2757900.32 | 0.120997E+09 | 17796722.91 | 0.00 | 0.49 |
Minimum of Months | 0.285588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.375370E+10 | 0.00 | 0.00 | 9543.02 | 2670589.46 | 78616011.50 | 17796722.91 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297620E+09 | 0.00 | 0.00 | 0.49 |
February | 0.163044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45715365.35 | 0.00 | 0.00 | 0.50 |
March | 0.196460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11279719.40 | 0.00 | 0.00 | 0.49 |
April | 0.201076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.216482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.192187E+10 | 0.00 | 0.00 | 0.00 | 1567401.68 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.178231E+10 | 0.00 | 0.00 | 0.00 | 51243.81 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.169471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.192862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.220309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.201692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33363579.91 | 0.00 | 0.00 | 0.49 |
December | 0.152614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304141E+09 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.224786E+11 | 0.00 | 0.00 | 0.00 | 1618645.49 | 0.692120E+09 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.152614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.220309E+10 | 0.00 | 0.00 | 0.00 | 1567401.68 | 0.304141E+09 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213594E+09 | 0.00 | 0.00 | 91454378.83 | 0.00 | 0.00 | 0.739476E+11 | 0.00 | 23.10 |
February | 0.190623E+09 | 0.00 | 0.00 | 82127289.03 | 0.00 | 0.00 | 0.642052E+11 | 0.00 | 23.24 |
March | 0.161463E+09 | 0.00 | 0.00 | 88082547.74 | 0.00 | 0.00 | 0.756676E+11 | 0.00 | 23.21 |
April | 0.163080E+09 | 0.00 | 0.00 | 99018625.01 | 0.00 | 0.00 | 0.776976E+11 | 0.00 | 23.21 |
May | 0.198960E+09 | 0.00 | 0.00 | 0.103437E+09 | 0.00 | 0.00 | 0.836783E+11 | 0.00 | 23.17 |
June | 0.154817E+09 | 63726951.75 | 0.00 | 0.110184E+09 | 0.00 | 0.00 | 0.744739E+11 | 0.00 | 23.30 |
July | 0.109603E+09 | 1692218.40 | 0.00 | 0.123040E+09 | 0.00 | 0.00 | 0.687189E+11 | 0.00 | 23.20 |
August | 70998889.18 | 0.00 | 0.00 | 0.123152E+09 | 0.00 | 0.00 | 0.659389E+11 | 0.00 | 23.38 |
September | 0.155735E+09 | 0.00 | 0.00 | 0.108796E+09 | 0.00 | 0.00 | 0.751868E+11 | 0.00 | 23.35 |
October | 0.241799E+09 | 0.00 | 0.00 | 91848710.18 | 0.00 | 0.00 | 0.849893E+11 | 0.00 | 23.30 |
November | 0.228461E+09 | 0.00 | 0.00 | 87816938.87 | 0.00 | 0.00 | 0.781405E+11 | 0.00 | 23.10 |
December | 0.216859E+09 | 0.00 | 0.00 | 91843862.52 | 0.00 | 0.00 | 0.699283E+11 | 0.00 | 23.20 |
Annual Sum or Average | 0.210599E+10 | 65419170.15 | 0.00 | 0.120080E+10 | 0.00 | 0.00 | 0.892573E+12 | 0.00 | 23.23 |
Minimum of Months | 70998889.18 | 0.00 | 0.00 | 82127289.03 | 0.00 | 0.00 | 0.642052E+11 | 0.00 | 23.10 |
Maximum of Months | 0.241799E+09 | 63726951.75 | 0.00 | 0.123152E+09 | 0.00 | 0.00 | 0.849893E+11 | 0.00 | 23.38 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.314425E+11 | 0.00 | 0.00 | 1052412.48 | 0.00 | 0.00 | 0.336146E+10 | 0.00 | 4.47 |
February | 0.261325E+11 | 0.00 | 0.00 | 1628125.10 | 0.00 | 0.00 | 0.409985E+10 | 0.00 | 4.50 |
March | 0.336925E+11 | 0.00 | 0.00 | 174953.19 | 0.00 | 0.00 | 0.190108E+10 | 0.00 | 4.47 |
April | 0.184381E+11 | 0.00 | 0.00 | 8989454.64 | 0.00 | 0.00 | 0.178410E+11 | 0.00 | 4.51 |
May | 0.223418E+11 | 0.00 | 0.00 | 5943529.40 | 0.00 | 0.00 | 0.166497E+11 | 0.00 | 4.48 |
June | 0.154958E+11 | 812822.44 | 0.00 | 7923738.38 | 27422610.44 | 0.00 | 0.191172E+11 | 0.00 | 4.50 |
July | 0.130309E+11 | 934228.38 | 0.00 | 12624104.57 | 643.85 | 0.00 | 0.190646E+11 | 0.00 | 4.50 |
August | 0.793575E+10 | 0.00 | 0.00 | 20036329.25 | 0.00 | 0.00 | 0.226264E+11 | 0.00 | 4.53 |
September | 0.113265E+11 | 0.00 | 0.00 | 22247516.71 | 0.00 | 0.00 | 0.237273E+11 | 0.00 | 4.60 |
October | 0.244636E+11 | 0.00 | 0.00 | 7025266.66 | 0.00 | 0.00 | 0.153525E+11 | 0.00 | 4.52 |
November | 0.310485E+11 | 0.00 | 0.00 | 1120282.26 | 0.00 | 0.00 | 0.588721E+10 | 0.00 | 4.46 |
December | 0.320495E+11 | 0.00 | 0.00 | 214992.31 | 0.00 | 0.00 | 0.921293E+09 | 0.00 | 4.49 |
Annual Sum or Average | 0.267398E+12 | 1747050.82 | 0.00 | 88980704.94 | 27423254.29 | 0.00 | 0.150550E+12 | 0.00 | 4.50 |
Minimum of Months | 0.793575E+10 | 0.00 | 0.00 | 174953.19 | 0.00 | 0.00 | 0.921293E+09 | 0.00 | 4.46 |
Maximum of Months | 0.336925E+11 | 934228.38 | 0.00 | 22247516.71 | 27422610.44 | 0.00 | 0.237273E+11 | 0.00 | 4.60 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959737E+11 | 0.00 | 0.00 | 951335.94 | 0.00 | 0.00 | 0.414329E+10 | 0.00 | 1.86 |
February | 0.814202E+11 | 0.00 | 0.00 | 1095562.64 | 0.00 | 0.00 | 0.544069E+10 | 0.00 | 1.87 |
March | 0.961964E+11 | 0.00 | 0.00 | 1347718.03 | 0.00 | 0.00 | 0.619668E+10 | 0.00 | 1.86 |
April | 0.672424E+11 | 0.00 | 0.00 | 17438304.74 | 0.00 | 0.00 | 0.370297E+11 | 0.00 | 1.87 |
May | 0.718207E+11 | 0.00 | 0.00 | 19927798.14 | 0.00 | 0.00 | 0.404877E+11 | 0.00 | 1.87 |
June | 0.438432E+11 | 907596.86 | 0.00 | 35206719.76 | 80318638.76 | 0.00 | 0.561121E+11 | 0.00 | 1.88 |
July | 0.370591E+11 | 1862873.32 | 0.00 | 50885696.17 | 792694.86 | 0.00 | 0.561555E+11 | 0.00 | 1.89 |
August | 0.260140E+11 | 0.00 | 0.00 | 58324055.97 | 0.00 | 0.00 | 0.629229E+11 | 0.00 | 1.90 |
September | 0.358363E+11 | 0.00 | 0.00 | 48743330.18 | 0.00 | 0.00 | 0.651859E+11 | 0.00 | 1.89 |
October | 0.813330E+11 | 0.00 | 0.00 | 13147552.30 | 0.00 | 0.00 | 0.328859E+11 | 0.00 | 1.87 |
November | 0.966427E+11 | 0.00 | 0.00 | 1833774.98 | 0.00 | 0.00 | 0.960548E+10 | 0.00 | 1.86 |
December | 0.932194E+11 | 0.00 | 0.00 | 185949.64 | 0.00 | 0.00 | 0.162971E+10 | 0.00 | 1.87 |
Annual Sum or Average | 0.826601E+12 | 2770470.18 | 0.00 | 0.249088E+09 | 81111333.63 | 0.00 | 0.377795E+12 | 0.00 | 1.87 |
Minimum of Months | 0.260140E+11 | 0.00 | 0.00 | 185949.64 | 0.00 | 0.00 | 0.162971E+10 | 0.00 | 1.86 |
Maximum of Months | 0.966427E+11 | 1862873.32 | 0.00 | 58324055.97 | 80318638.76 | 0.00 | 0.651859E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60576537.12 | 0.00 | 0.00 | 343588.12 | 0.00 | 0.129942E+10 | 41219065.71 | 0.00 | 0.35 |
February | 61500103.50 | 0.00 | 0.00 | 985580.78 | 0.00 | 0.110729E+10 | 90000460.42 | 0.00 | 0.36 |
March | 70036299.16 | 0.00 | 0.00 | 529181.38 | 0.00 | 0.123133E+10 | 0.101362E+09 | 0.00 | 0.35 |
April | 42430059.81 | 0.00 | 0.00 | 8900954.98 | 0.00 | 0.449863E+09 | 0.860522E+09 | 0.00 | 0.35 |
May | 43295921.84 | 19975.59 | 0.00 | 10666069.35 | 0.00 | 0.309555E+09 | 0.999425E+09 | 0.00 | 0.35 |
June | 21832454.43 | 4714033.19 | 0.00 | 14475255.56 | 0.00 | 18591040.50 | 0.106596E+10 | 0.00 | 0.35 |
July | 12558966.66 | 2788778.02 | 0.00 | 18595493.26 | 0.00 | 31529552.85 | 0.980645E+09 | 0.00 | 0.35 |
August | 2241147.07 | 801102.61 | 0.00 | 18218373.54 | 19898.06 | 2353103.41 | 0.101285E+10 | 0.00 | 0.35 |
September | 15325372.19 | 195053.79 | 0.00 | 13245434.94 | 0.00 | 88845452.94 | 0.105499E+10 | 0.00 | 0.35 |
October | 56364387.22 | 0.00 | 0.00 | 3195368.09 | 0.00 | 0.862548E+09 | 0.480598E+09 | 0.00 | 0.36 |
November | 61931498.25 | 0.00 | 0.00 | 358299.01 | 0.00 | 0.123533E+10 | 58521894.50 | 0.00 | 0.35 |
December | 44733880.76 | 0.00 | 0.00 | 6691.82 | 0.00 | 0.134137E+10 | 2871965.22 | 0.00 | 0.36 |
Annual Sum or Average | 0.492827E+09 | 8518943.20 | 0.00 | 89520290.83 | 19898.06 | 0.797803E+10 | 0.674896E+10 | 0.00 | 0.35 |
Minimum of Months | 2241147.07 | 0.00 | 0.00 | 6691.82 | 0.00 | 2353103.41 | 2871965.22 | 0.00 | 0.35 |
Maximum of Months | 70036299.16 | 4714033.19 | 0.00 | 18595493.26 | 19898.06 | 0.134137E+10 | 0.106596E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50326616.00 | 0.00 | 0.00 | 57641.07 | 0.00 | 0.134414E+10 | 6869380.40 | 0.00 | 0.35 |
February | 61900337.87 | 0.00 | 0.00 | 337404.55 | 0.00 | 0.115473E+10 | 42660471.99 | 0.00 | 0.36 |
March | 68394757.45 | 0.00 | 0.00 | 294502.18 | 0.00 | 0.126680E+10 | 67604847.11 | 0.00 | 0.35 |
April | 0.110527E+09 | 0.00 | 0.00 | 6197634.70 | 0.00 | 0.580264E+09 | 0.664567E+09 | 0.00 | 0.35 |
May | 0.125891E+09 | 12717.88 | 0.00 | 8056918.55 | 7255.37 | 0.360748E+09 | 0.868087E+09 | 0.00 | 0.35 |
June | 0.140491E+09 | 2822644.68 | 0.00 | 12430419.70 | 1890836.20 | 20967026.36 | 0.946837E+09 | 0.00 | 0.36 |
July | 0.209231E+09 | 2296395.34 | 0.00 | 13990042.37 | 492055.93 | 31504850.17 | 0.788481E+09 | 0.00 | 0.36 |
August | 0.256406E+09 | 771938.02 | 0.00 | 11610764.80 | 48966.46 | 2367760.96 | 0.765156E+09 | 0.00 | 0.36 |
September | 0.158070E+09 | 48237.59 | 0.00 | 7759497.77 | 146793.35 | 0.142982E+09 | 0.863453E+09 | 0.00 | 0.36 |
October | 91074411.83 | 0.00 | 0.00 | 1575747.64 | 0.00 | 0.105150E+10 | 0.258392E+09 | 0.00 | 0.36 |
November | 61734811.05 | 0.00 | 0.00 | 90677.38 | 0.00 | 0.128081E+10 | 13355047.76 | 0.00 | 0.35 |
December | 36083006.89 | 0.00 | 0.00 | 3635.13 | 0.00 | 0.135223E+10 | 511248.59 | 0.00 | 0.36 |
Annual Sum or Average | 0.137013E+10 | 5951933.51 | 0.00 | 62404885.86 | 2585907.30 | 0.858903E+10 | 0.528597E+10 | 0.00 | 0.35 |
Minimum of Months | 36083006.89 | 0.00 | 0.00 | 3635.13 | 0.00 | 2367760.96 | 511248.59 | 0.00 | 0.35 |
Maximum of Months | 0.256406E+09 | 2822644.68 | 0.00 | 13990042.37 | 1890836.20 | 0.135223E+10 | 0.946837E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.958239E+09 | 0.00 | 0.00 | 334820.01 | 0.00 | 0.00 | 0.234316E+09 | 0.00 | 0.02 |
February | 0.749428E+09 | 0.00 | 0.00 | 465728.61 | 0.00 | 0.00 | 0.407927E+09 | 0.00 | 0.02 |
March | 0.108660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 0.265620E+09 | 0.00 | 0.00 | 3418823.63 | 0.00 | 0.00 | 0.110168E+10 | 0.00 | 0.02 |
May | 0.363821E+09 | 0.00 | 0.00 | 2602658.05 | 0.00 | 0.00 | 0.101820E+10 | 0.00 | 0.02 |
June | 48037016.80 | 11328354.44 | 0.00 | 2597658.75 | 0.00 | 0.00 | 0.103699E+10 | 0.00 | 0.02 |
July | 0.102863E+09 | 776832.96 | 0.00 | 3802102.21 | 0.00 | 0.00 | 0.747368E+09 | 0.00 | 0.02 |
August | 24689271.70 | 1582100.62 | 0.00 | 4902398.22 | 0.00 | 0.00 | 0.675115E+09 | 0.00 | 0.02 |
September | 0.109975E+09 | 266269.18 | 0.00 | 5380753.40 | 0.00 | 0.00 | 0.843723E+09 | 0.00 | 0.02 |
October | 0.723923E+09 | 0.00 | 0.00 | 2237415.80 | 0.00 | 0.00 | 0.644457E+09 | 0.00 | 0.02 |
November | 0.976758E+09 | 0.00 | 0.00 | 273974.50 | 0.00 | 0.00 | 0.223568E+09 | 0.00 | 0.02 |
December | 0.719805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.612976E+10 | 13953557.20 | 0.00 | 26016333.19 | 0.00 | 0.00 | 0.693334E+10 | 0.00 | 0.02 |
Minimum of Months | 24689271.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.108660E+10 | 11328354.44 | 0.00 | 5380753.40 | 0.00 | 0.00 | 0.110168E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.900853E+09 | 0.00 | 0.00 | 10653654.75 | 0.00 | 0.844380E+10 | 0.965373E+10 | 0.00 | 0.40 |
February | 0.839641E+09 | 0.00 | 0.00 | 9787852.93 | 0.00 | 0.676860E+10 | 0.946805E+10 | 0.00 | 0.40 |
March | 0.949889E+09 | 0.00 | 0.00 | 26231955.05 | 0.00 | 0.160245E+10 | 0.164536E+11 | 0.00 | 0.40 |
April | 0.154211E+10 | 0.00 | 0.00 | 80029197.32 | 0.00 | 91538122.32 | 0.167550E+11 | 0.00 | 0.40 |
May | 0.176526E+10 | 172510.43 | 0.00 | 0.101428E+09 | 98414.78 | 56465179.02 | 0.165622E+11 | 0.00 | 0.40 |
June | 0.206631E+10 | 30625498.02 | 9675.59 | 0.142154E+09 | 33297738.02 | 21335440.95 | 0.129722E+11 | 2628.76 | 0.40 |
July | 0.311548E+10 | 29066100.95 | 0.00 | 0.159374E+09 | 8757567.75 | 13767856.68 | 0.108619E+11 | 0.00 | 0.40 |
August | 0.373653E+10 | 5166413.30 | 0.00 | 0.134145E+09 | 5968663.51 | 14846595.82 | 0.101610E+11 | 0.00 | 0.40 |
September | 0.217444E+10 | 297693.91 | 0.00 | 97177271.23 | 2347783.76 | 37787043.21 | 0.135917E+11 | 0.00 | 0.40 |
October | 0.123537E+10 | 0.00 | 0.00 | 42003681.75 | 0.00 | 0.226330E+09 | 0.175209E+11 | 0.00 | 0.40 |
November | 0.886389E+09 | 0.00 | 0.00 | 17297746.45 | 0.00 | 0.427138E+10 | 0.132181E+11 | 0.00 | 0.40 |
December | 0.859430E+09 | 0.00 | 0.00 | 5464205.79 | 0.00 | 0.115996E+11 | 0.637405E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.200717E+11 | 65328216.60 | 9675.59 | 0.825746E+09 | 50470167.81 | 0.331479E+11 | 0.153592E+12 | 2628.76 | 0.40 |
Minimum of Months | 0.839641E+09 | 0.00 | 0.00 | 5464205.79 | 0.00 | 13767856.68 | 0.637405E+10 | 0.00 | 0.40 |
Maximum of Months | 0.373653E+10 | 30625498.02 | 9675.59 | 0.159374E+09 | 33297738.02 | 0.115996E+11 | 0.175209E+11 | 2628.76 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60576537.12 | 0.00 | 0.00 | 292493.97 | 0.00 | 0.127673E+10 | 63957146.73 | 0.00 | 0.35 |
February | 61515910.35 | 0.00 | 0.00 | 616363.21 | 0.00 | 0.110193E+10 | 95715210.10 | 0.00 | 0.36 |
March | 70036299.16 | 0.00 | 0.00 | 365757.54 | 0.00 | 0.121099E+10 | 0.121870E+09 | 0.00 | 0.35 |
April | 25082031.73 | 0.00 | 0.00 | 9616331.95 | 0.00 | 0.420178E+09 | 0.906839E+09 | 0.00 | 0.35 |
May | 26526580.58 | 19975.59 | 0.00 | 10362527.30 | 0.00 | 0.311731E+09 | 0.101432E+10 | 0.00 | 0.35 |
June | 14325315.52 | 4714033.19 | 0.00 | 13557844.34 | 0.00 | 43913012.04 | 0.104906E+10 | 0.00 | 0.35 |
July | 5072497.67 | 2788778.02 | 0.00 | 16619430.12 | 0.00 | 17969606.05 | 0.100367E+10 | 0.00 | 0.35 |
August | 2168058.23 | 801102.61 | 0.00 | 18223244.19 | 19898.06 | 2036856.25 | 0.101323E+10 | 0.00 | 0.35 |
September | 6689073.18 | 195053.79 | 0.00 | 14193544.53 | 0.00 | 60853004.69 | 0.109067E+10 | 0.00 | 0.35 |
October | 55731214.90 | 0.00 | 0.00 | 3248501.54 | 0.00 | 0.860125E+09 | 0.483602E+09 | 0.00 | 0.36 |
November | 62327298.09 | 0.00 | 0.00 | 352410.02 | 0.00 | 0.122053E+10 | 72939559.38 | 0.00 | 0.35 |
December | 45038332.73 | 0.00 | 0.00 | 81123.05 | 0.00 | 0.131187E+10 | 31994699.03 | 0.00 | 0.36 |
Annual Sum or Average | 0.435089E+09 | 8518943.20 | 0.00 | 87529571.78 | 19898.06 | 0.783885E+10 | 0.694787E+10 | 0.00 | 0.35 |
Minimum of Months | 2168058.23 | 0.00 | 0.00 | 81123.05 | 0.00 | 2036856.25 | 31994699.03 | 0.00 | 0.35 |
Maximum of Months | 70036299.16 | 4714033.19 | 0.00 | 18223244.19 | 19898.06 | 0.131187E+10 | 0.109067E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50430016.86 | 0.00 | 0.00 | 40780.48 | 0.00 | 0.132910E+10 | 21822395.90 | 0.00 | 0.35 |
February | 59940747.56 | 0.00 | 0.00 | 126197.34 | 0.00 | 0.115710E+10 | 42458423.65 | 0.00 | 0.36 |
March | 68730937.06 | 0.00 | 0.00 | 154354.16 | 0.00 | 0.126387E+10 | 70335548.89 | 0.00 | 0.35 |
April | 93856956.45 | 0.00 | 0.00 | 7106733.62 | 0.00 | 0.510185E+09 | 0.750408E+09 | 0.00 | 0.35 |
May | 0.105010E+09 | 12717.88 | 0.00 | 8234389.62 | 7255.37 | 0.362085E+09 | 0.887454E+09 | 0.00 | 0.35 |
June | 0.125557E+09 | 2822644.68 | 0.00 | 11551982.15 | 1890836.20 | 47318911.31 | 0.936297E+09 | 0.00 | 0.36 |
July | 0.192474E+09 | 2296395.34 | 0.00 | 12506918.84 | 492055.93 | 18791111.03 | 0.819435E+09 | 0.00 | 0.35 |
August | 0.242149E+09 | 771938.02 | 0.00 | 12467798.09 | 48966.46 | 1638984.24 | 0.779285E+09 | 0.00 | 0.36 |
September | 0.136504E+09 | 49223.08 | 0.00 | 9007565.36 | 145807.86 | 0.113214E+09 | 0.913538E+09 | 0.00 | 0.36 |
October | 91074411.83 | 0.00 | 0.00 | 1545900.29 | 0.00 | 0.102805E+10 | 0.281872E+09 | 0.00 | 0.36 |
November | 61734811.05 | 0.00 | 0.00 | 77236.94 | 0.00 | 0.126483E+10 | 29345883.03 | 0.00 | 0.35 |
December | 36659221.95 | 0.00 | 0.00 | 13327.64 | 0.00 | 0.134925E+10 | 2898179.46 | 0.00 | 0.36 |
Annual Sum or Average | 0.126412E+10 | 5952919.00 | 0.00 | 62833184.53 | 2584921.82 | 0.844544E+10 | 0.553515E+10 | 0.00 | 0.35 |
Minimum of Months | 36659221.95 | 0.00 | 0.00 | 13327.64 | 0.00 | 1638984.24 | 2898179.46 | 0.00 | 0.35 |
Maximum of Months | 0.242149E+09 | 2822644.68 | 0.00 | 12506918.84 | 1890836.20 | 0.134925E+10 | 0.936297E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562655E+09 | 0.00 | 0.00 | 0.63 |
February | 0.269732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 0.317965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.323577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.348370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.309274E+11 | 0.00 | 0.00 | 0.00 | 25223135.60 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.286815E+11 | 0.00 | 0.00 | 0.00 | 824632.04 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.272719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.310360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.354529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.326988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294983E+09 | 0.00 | 0.00 | 0.63 |
December | 0.276965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175705E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.370256E+12 | 0.00 | 0.00 | 0.00 | 26047767.64 | 0.261468E+10 | 0.00 | 0.00 | 0.63 |
Minimum of Months | 0.269732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.354529E+11 | 0.00 | 0.00 | 0.00 | 25223135.60 | 0.175705E+10 | 0.00 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12687403.65 | 0.00 | 0.00 | 73875.12 | 0.00 | 0.332326E+09 | 5301265.05 | 0.00 | 0.35 |
February | 14581484.22 | 0.00 | 0.00 | 245132.85 | 0.00 | 0.282890E+09 | 17227267.73 | 0.00 | 0.36 |
March | 16874387.53 | 0.00 | 0.00 | 123019.80 | 0.00 | 0.315565E+09 | 18252375.55 | 0.00 | 0.35 |
April | 10415279.05 | 0.00 | 0.00 | 2294037.34 | 0.00 | 0.154764E+09 | 0.172956E+09 | 0.00 | 0.35 |
May | 9841988.11 | 4993.90 | 0.00 | 2677274.76 | 0.00 | 0.126045E+09 | 0.202171E+09 | 0.00 | 0.35 |
June | 4791916.36 | 1178508.30 | 0.00 | 3593094.86 | 0.00 | 26403018.23 | 0.245426E+09 | 0.00 | 0.35 |
July | 2413390.96 | 697194.50 | 0.00 | 4675087.69 | 0.00 | 27618380.94 | 0.226125E+09 | 0.00 | 0.35 |
August | 542014.56 | 200275.65 | 0.00 | 4470654.62 | 4974.52 | 6507644.12 | 0.247395E+09 | 0.00 | 0.35 |
September | 3364479.85 | 48763.45 | 0.00 | 3124779.39 | 0.00 | 65149916.09 | 0.221461E+09 | 0.00 | 0.36 |
October | 14188072.66 | 0.00 | 0.00 | 728846.10 | 0.00 | 0.259433E+09 | 76327009.07 | 0.00 | 0.36 |
November | 15382460.55 | 0.00 | 0.00 | 86230.41 | 0.00 | 0.315668E+09 | 7899324.89 | 0.00 | 0.35 |
December | 8472794.62 | 0.00 | 0.00 | 896.18 | 0.00 | 0.338671E+09 | 102462.29 | 0.00 | 0.36 |
Annual Sum or Average | 0.113556E+09 | 2129735.80 | 0.00 | 22092929.11 | 4974.52 | 0.225104E+10 | 0.144064E+10 | 0.00 | 0.35 |
Minimum of Months | 542014.56 | 0.00 | 0.00 | 896.18 | 0.00 | 6507644.12 | 102462.29 | 0.00 | 0.35 |
Maximum of Months | 16874387.53 | 1178508.30 | 0.00 | 4675087.69 | 4974.52 | 0.338671E+09 | 0.247395E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8336857.57 | 0.00 | 0.00 | 7363.64 | 0.00 | 0.341303E+09 | 700353.53 | 0.00 | 0.35 |
February | 12637816.57 | 0.00 | 0.00 | 58444.50 | 0.00 | 0.292989E+09 | 9221822.26 | 0.00 | 0.36 |
March | 16534504.28 | 0.00 | 0.00 | 63563.33 | 0.00 | 0.321987E+09 | 12188928.24 | 0.00 | 0.35 |
April | 26445565.14 | 0.00 | 0.00 | 1627578.08 | 0.00 | 0.183954E+09 | 0.128362E+09 | 0.00 | 0.35 |
May | 29575435.87 | 3179.47 | 0.00 | 2044046.55 | 1813.84 | 0.140224E+09 | 0.168852E+09 | 0.00 | 0.35 |
June | 31266595.57 | 705661.17 | 0.00 | 3214751.61 | 472709.05 | 24014728.94 | 0.221685E+09 | 0.00 | 0.36 |
July | 48337504.24 | 574098.84 | 0.00 | 3719469.51 | 123013.98 | 23854305.04 | 0.184890E+09 | 0.00 | 0.36 |
August | 61354803.71 | 192984.51 | 0.00 | 2926870.29 | 12241.61 | 3257559.09 | 0.191346E+09 | 0.00 | 0.36 |
September | 38867389.45 | 12305.77 | 0.00 | 1786430.89 | 36451.97 | 85468982.50 | 0.166943E+09 | 0.00 | 0.36 |
October | 22768602.96 | 0.00 | 0.00 | 342807.34 | 0.00 | 0.290634E+09 | 36889835.75 | 0.00 | 0.36 |
November | 12974584.39 | 0.00 | 0.00 | 12225.31 | 0.00 | 0.323516E+09 | 2493985.76 | 0.00 | 0.35 |
December | 3736693.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343469E+09 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.312836E+09 | 1488229.75 | 0.00 | 15803551.03 | 646230.45 | 0.237467E+10 | 0.112357E+10 | 0.00 | 0.35 |
Minimum of Months | 3736693.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3257559.09 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 61354803.71 | 705661.17 | 0.00 | 3719469.51 | 472709.05 | 0.343469E+09 | 0.221685E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69315402.00 | 0.00 | 0.00 | 3017397.03 | 0.00 | 0.164187E+10 | 0.536872E+09 | 0.00 | 0.40 |
February | 60171372.36 | 0.00 | 0.00 | 3945734.95 | 0.00 | 0.132180E+10 | 0.637433E+09 | 0.00 | 0.40 |
March | 97197821.42 | 0.00 | 0.00 | 1926735.33 | 0.00 | 0.154321E+10 | 0.611469E+09 | 0.00 | 0.40 |
April | 18280913.83 | 0.00 | 0.00 | 15248968.75 | 0.00 | 0.446243E+09 | 0.170731E+10 | 0.00 | 0.40 |
May | 30693279.87 | 32083.25 | 0.00 | 14073068.10 | 0.00 | 0.407495E+09 | 0.173679E+10 | 0.00 | 0.40 |
June | 22926147.83 | 7571313.99 | 0.00 | 17483429.78 | 0.00 | 48034693.15 | 0.171179E+10 | 0.00 | 0.40 |
July | 12251927.41 | 4479118.66 | 0.00 | 22527558.79 | 0.00 | 20524005.04 | 0.162041E+10 | 0.00 | 0.40 |
August | 2347705.23 | 1286668.79 | 0.00 | 25524877.13 | 31958.72 | 4767091.89 | 0.163076E+10 | 0.00 | 0.40 |
September | 10242348.50 | 313280.25 | 0.00 | 23273350.70 | 0.00 | 36462352.44 | 0.181304E+10 | 0.00 | 0.40 |
October | 60729206.89 | 0.00 | 0.00 | 8565434.54 | 0.00 | 0.811880E+09 | 0.137174E+10 | 0.00 | 0.40 |
November | 63274718.84 | 0.00 | 0.00 | 2616921.39 | 0.00 | 0.148247E+10 | 0.629776E+09 | 0.00 | 0.40 |
December | 64843221.52 | 0.00 | 0.00 | 810970.32 | 0.00 | 0.198109E+10 | 0.184135E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.512274E+09 | 13682464.95 | 0.00 | 0.139014E+09 | 31958.72 | 0.974585E+10 | 0.141915E+11 | 0.00 | 0.40 |
Minimum of Months | 2347705.23 | 0.00 | 0.00 | 810970.32 | 0.00 | 4767091.89 | 0.184135E+09 | 0.00 | 0.40 |
Maximum of Months | 97197821.42 | 7571313.99 | 0.00 | 25524877.13 | 31958.72 | 0.198109E+10 | 0.181304E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449739E+10 | 0.00 | 0.00 | 47126599.39 | 0.00 | 0.00 | 0.405639E+11 | 0.00 | 4.32 |
February | 0.225686E+10 | 0.00 | 0.00 | 44293589.98 | 0.00 | 0.00 | 0.371313E+11 | 0.00 | 4.37 |
March | 0.164529E+10 | 0.00 | 0.00 | 54113918.13 | 0.00 | 0.00 | 0.456934E+11 | 0.00 | 4.45 |
April | 0.643687E+09 | 0.00 | 0.00 | 71336332.29 | 0.00 | 0.00 | 0.498359E+11 | 0.00 | 4.66 |
May | 0.388881E+09 | 0.00 | 0.00 | 79094964.81 | 0.00 | 0.00 | 0.551761E+11 | 0.00 | 4.74 |
June | 65031542.74 | 40520729.61 | 0.00 | 90542371.93 | 0.00 | 0.00 | 0.527472E+11 | 0.00 | 4.98 |
July | 13485085.66 | 1294571.89 | 0.00 | 0.103159E+09 | 0.00 | 0.00 | 0.498130E+11 | 0.00 | 5.03 |
August | 68156633.26 | 0.00 | 0.00 | 98709164.88 | 0.00 | 0.00 | 0.475346E+11 | 0.00 | 5.00 |
September | 0.274419E+09 | 0.00 | 0.00 | 81365471.40 | 0.00 | 0.00 | 0.512214E+11 | 0.00 | 4.81 |
October | 0.133297E+10 | 0.00 | 0.00 | 59968920.01 | 0.00 | 0.00 | 0.527814E+11 | 0.00 | 4.55 |
November | 0.266316E+10 | 0.00 | 0.00 | 49182376.74 | 0.00 | 0.00 | 0.461203E+11 | 0.00 | 4.40 |
December | 0.425849E+10 | 0.00 | 0.00 | 45362157.53 | 0.00 | 0.00 | 0.382931E+11 | 0.00 | 4.32 |
Annual Sum or Average | 0.181078E+11 | 41815301.50 | 0.00 | 0.824255E+09 | 0.00 | 0.00 | 0.566912E+12 | 0.00 | 4.64 |
Minimum of Months | 13485085.66 | 0.00 | 0.00 | 44293589.98 | 0.00 | 0.00 | 0.371313E+11 | 0.00 | 4.32 |
Maximum of Months | 0.449739E+10 | 40520729.61 | 0.00 | 0.103159E+09 | 0.00 | 0.00 | 0.551761E+11 | 0.00 | 5.03 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110658E+10 | 0.00 | 0.00 | 62830180.96 | 0.00 | 0.00 | 0.482603E+11 | 0.00 | 4.73 |
February | 0.577466E+09 | 0.00 | 0.00 | 59168822.48 | 0.00 | 0.00 | 0.425865E+11 | 0.00 | 4.78 |
March | 0.200048E+09 | 0.00 | 0.00 | 69470175.41 | 0.00 | 0.00 | 0.519071E+11 | 0.00 | 4.90 |
April | 7378617.62 | 0.00 | 0.00 | 85979028.03 | 0.00 | 0.00 | 0.553278E+11 | 0.00 | 5.11 |
May | 14260163.05 | 0.00 | 0.00 | 93320511.03 | 0.00 | 0.00 | 0.608432E+11 | 0.00 | 5.19 |
June | 0.00 | 44145798.40 | 0.00 | 0.103427E+09 | 0.00 | 0.00 | 0.573928E+11 | 0.00 | 5.41 |
July | 0.00 | 1400244.28 | 0.00 | 0.116236E+09 | 0.00 | 0.00 | 0.539560E+11 | 0.00 | 5.45 |
August | 0.00 | 0.00 | 0.00 | 0.112640E+09 | 0.00 | 0.00 | 0.514596E+11 | 0.00 | 5.42 |
September | 16256625.86 | 0.00 | 0.00 | 95219952.15 | 0.00 | 0.00 | 0.560777E+11 | 0.00 | 5.23 |
October | 0.130722E+09 | 0.00 | 0.00 | 74632215.19 | 0.00 | 0.00 | 0.593399E+11 | 0.00 | 5.00 |
November | 0.489573E+09 | 0.00 | 0.00 | 64448214.23 | 0.00 | 0.00 | 0.530254E+11 | 0.00 | 4.82 |
December | 0.134926E+10 | 0.00 | 0.00 | 61659119.68 | 0.00 | 0.00 | 0.452525E+11 | 0.00 | 4.73 |
Annual Sum or Average | 0.389154E+10 | 45546042.68 | 0.00 | 0.999032E+09 | 0.00 | 0.00 | 0.635429E+12 | 0.00 | 5.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 59168822.48 | 0.00 | 0.00 | 0.425865E+11 | 0.00 | 4.73 |
Maximum of Months | 0.134926E+10 | 44145798.40 | 0.00 | 0.116236E+09 | 0.00 | 0.00 | 0.608432E+11 | 0.00 | 5.45 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.110836E+09 | 0.00 | 0.00 | 0.690565E+11 | 0.00 | 21.18 |
February | 0.00 | 0.00 | 0.00 | 0.100680E+09 | 0.00 | 0.00 | 0.600842E+11 | 0.00 | 21.45 |
March | 0.00 | 0.00 | 0.00 | 0.106461E+09 | 0.00 | 0.00 | 0.716529E+11 | 0.00 | 21.49 |
April | 0.00 | 0.00 | 0.00 | 0.127088E+09 | 0.00 | 0.00 | 0.750615E+11 | 0.00 | 22.24 |
May | 0.00 | 0.00 | 0.00 | 0.134222E+09 | 0.00 | 0.00 | 0.804620E+11 | 0.00 | 22.25 |
June | 0.00 | 69588681.39 | 0.00 | 0.143886E+09 | 0.00 | 0.00 | 0.691671E+11 | 0.00 | 22.57 |
July | 0.00 | 2275146.32 | 0.00 | 0.160679E+09 | 0.00 | 0.00 | 0.633278E+11 | 0.00 | 22.64 |
August | 0.00 | 0.00 | 0.00 | 0.160216E+09 | 0.00 | 0.00 | 0.596265E+11 | 0.00 | 22.65 |
September | 0.00 | 0.00 | 0.00 | 0.141660E+09 | 0.00 | 0.00 | 0.685287E+11 | 0.00 | 22.49 |
October | 0.00 | 0.00 | 0.00 | 0.113529E+09 | 0.00 | 0.00 | 0.800751E+11 | 0.00 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.105522E+09 | 0.00 | 0.00 | 0.734692E+11 | 0.00 | 21.28 |
December | 0.00 | 0.00 | 0.00 | 0.110742E+09 | 0.00 | 0.00 | 0.642259E+11 | 0.00 | 21.12 |
Annual Sum or Average | 0.00 | 71863827.71 | 0.00 | 0.151552E+10 | 0.00 | 0.00 | 0.834738E+12 | 0.00 | 21.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100680E+09 | 0.00 | 0.00 | 0.596265E+11 | 0.00 | 21.12 |
Maximum of Months | 0.00 | 69588681.39 | 0.00 | 0.160679E+09 | 0.00 | 0.00 | 0.804620E+11 | 0.00 | 22.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323555E+09 | 0.00 | 0.00 | 1.22 |
February | 0.137858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47496439.06 | 0.00 | 0.00 | 1.22 |
March | 0.163070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
April | 0.165845E+11 | 0.00 | 0.00 | 20385.79 | 0.00 | 0.00 | 10256310.02 | 0.00 | 1.22 |
May | 0.178610E+11 | 0.00 | 0.00 | 343.75 | 0.00 | 0.00 | 5380140.10 | 0.00 | 1.22 |
June | 0.158221E+11 | 0.00 | 0.00 | 85839.93 | 12935810.05 | 0.00 | 39101735.03 | 0.00 | 1.23 |
July | 0.145219E+11 | 430187.00 | 0.00 | 420104.31 | 294.98 | 0.00 | 0.187220E+09 | 0.00 | 1.23 |
August | 0.138899E+11 | 0.00 | 0.00 | 92277.52 | 0.00 | 0.00 | 96557532.26 | 0.00 | 1.23 |
September | 0.158992E+11 | 0.00 | 0.00 | 11274.73 | 0.00 | 0.00 | 17732388.54 | 0.00 | 1.23 |
October | 0.181822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 0.169185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2468699.70 | 0.00 | 0.00 | 1.21 |
December | 0.148007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304625E+09 | 0.00 | 0.00 | 1.22 |
Annual Sum or Average | 0.190194E+12 | 430187.00 | 0.00 | 630226.03 | 12936105.03 | 0.678145E+09 | 0.356248E+09 | 0.00 | 1.22 |
Minimum of Months | 0.137858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
Maximum of Months | 0.181822E+11 | 430187.00 | 0.00 | 420104.31 | 12935810.05 | 0.323555E+09 | 0.187220E+09 | 0.00 | 1.23 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.788848E+11 | 0.172688E+11 | 0.238542E+12 | 0.944632E+12 | 0.732634E+11 |
February | 0.128448E+12 | 0.155975E+11 | 0.213847E+12 | 0.860225E+12 | 0.561804E+11 |
March | 0.165511E+12 | 0.156666E+11 | 0.214932E+12 | 0.871337E+12 | 0.766981E+11 |
April | 0.420842E+12 | 0.128494E+11 | 0.167975E+12 | 0.723422E+12 | 0.155805E+12 |
May | 0.547558E+12 | 0.121976E+11 | 0.163515E+12 | 0.689004E+12 | 0.166770E+12 |
June | 0.555018E+12 | 0.888058E+10 | 0.123825E+12 | 0.511913E+12 | 0.234927E+12 |
July | 0.556646E+12 | 0.802972E+10 | 0.110418E+12 | 0.459095E+12 | 0.297710E+12 |
August | 0.446395E+12 | 0.780425E+10 | 0.102916E+12 | 0.434761E+12 | 0.312937E+12 |
September | 0.325598E+12 | 0.900003E+10 | 0.121284E+12 | 0.515249E+12 | 0.242987E+12 |
October | 0.147252E+12 | 0.125130E+11 | 0.173342E+12 | 0.710656E+12 | 0.126118E+12 |
November | 0.578821E+11 | 0.143896E+11 | 0.201642E+12 | 0.799614E+12 | 0.917417E+11 |
December | 0.190515E+11 | 0.172146E+11 | 0.241123E+12 | 0.950677E+12 | 0.604248E+11 |
Annual Sum or Average | 0.344909E+13 | 0.151412E+12 | 0.207336E+13 | 0.847058E+13 | 0.189556E+13 |
Minimum of Months | 0.190515E+11 | 0.780425E+10 | 0.102916E+12 | 0.434761E+12 | 0.561804E+11 |
Maximum of Months | 0.556646E+12 | 0.172688E+11 | 0.241123E+12 | 0.950677E+12 | 0.312937E+12 |