Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:46:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11118.40 | 980.00 | 980.00 |
Net Site Energy | 11118.40 | 980.00 | 980.00 |
Total Source Energy | 24922.74 | 2196.75 | 2196.75 |
Net Source Energy | 24922.74 | 2196.75 | 2196.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 478.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1896.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 610.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 93.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 149.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2671.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6178.78 | 4939.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 478.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1896.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 610.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 93.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 149.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2671.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 478.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1896.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 610.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 93.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 149.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2671.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 237.21 | 277.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.26 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 544.61 | 435.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 237.21 | 277.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 221.26 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 544.61 | 435.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6178.781 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6178.781 | 100.00 |
Total On-Site and Utility Electric Sources | 6178.781 | 100.00 |
Total Electricity End Uses | 6178.781 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 502.33 | 64.28 |
Air to Air Heat Recovery for Heating | 279.17 | 35.72 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 781.50 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 600.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7301.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:00 | 07-DEC-21:10 | - | - | - | - | - | - | - | - | - | - | 17-JAN-21:19 |
Heating | 0.00 | 167479.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184526.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31553.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42059.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3793.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3751.82 | 242640.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1871.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 440906.66 | 485244.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 167479.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 184526.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42059.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3793.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3751.82 | 242640.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 519.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6006.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1932.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 297.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 473.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2896.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19568.20 | 5354.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 45.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 529.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1724.79 | 471.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 45.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 529.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1724.79 | 471.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.89 | 0.522213 | 0.473000 | 1.37 | 1.00 | 0.500000 | 0.000730 | 0.000057 | 1.37 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.374404 | 0.136506 | 0.473000 | 0.177093 | 0.473000 | 0.500000 | 0.002791 | 0.000028 | 0.177093 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.266756 | 0.221864 | 0.473000 | 0.126176 | 0.591639 | 0.500000 | 0.001717 | 0.000012 | 0.126176 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.244757 | 0.511336 | 0.473000 | 0.115770 | 1.00 | 0.500000 | 0.000745 | 0.000017 | 0.115770 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.144190 | 0.500773 | 0.473000 | 0.068202 | 1.00 | 0.500000 | 0.000761 | 0.000010 | 0.068202 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.62 | 0.016417 | 0.473000 | 1.71 | 0.473000 | 0.500000 | 0.023207 | 0.000088 | 1.71 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.57 | 0.091525 | 0.473000 | 0.743738 | 0.473000 | 0.500000 | 0.004163 | 0.000082 | 0.743738 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.34 | 0.186562 | 0.473000 | 2.53 | 0.497498 | 0.500000 | 0.002042 | 0.000223 | 2.53 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.76 | 0.672992 | 0.473000 | 0.834194 | 1.00 | 0.500000 | 0.000566 | 0.000106 | 0.834194 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.46 | 0.102733 | 0.473000 | 1.16 | 0.473000 | 0.500000 | 0.003709 | 0.000094 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.57 | 0.098188 | 0.473000 | 1.22 | 0.473000 | 0.500000 | 0.003880 | 0.000097 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.49 | 0.056776 | 0.473000 | 1.18 | 0.473000 | 0.500000 | 0.012070 | 0.000061 | 1.18 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.891164 | 0.352392 | 0.473000 | 0.421521 | 0.939712 | 0.500000 | 0.001081 | 0.000065 | 0.421521 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6546.67 | 0.000057 | 136.52 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3153.37 | 0.000028 | 76.73 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1344.58 | 0.000012 | 29.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1946.77 | 0.000017 | 46.77 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1185.40 | 0.000010 | 28.69 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10072.44 | 0.000088 | 212.54 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9341.79 | 0.000082 | 212.84 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 25464.81 | 0.000223 | 563.36 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4965.71 | 0.000043 | 141.89 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4970.23 | 0.000043 | 142.02 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 28712.65 | 0.000251 | 820.44 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 28813.41 | 0.000252 | 823.32 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4956.04 | 0.000043 | 141.62 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4960.57 | 0.000043 | 141.75 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12162.09 | 0.000106 | 284.04 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1515.97 | 0.000013 | 43.32 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1516.50 | 0.000013 | 43.33 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7305.37 | 0.000064 | 208.74 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10735.39 | 0.000094 | 235.21 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11103.41 | 0.000097 | 242.97 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6984.94 | 0.000061 | 147.46 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7461.95 | 0.000065 | 181.33 |
VAV WITH REHEAT HEATING COIL | 130858.93 | 0.001145 | 2296.10 |
FLR_3_DOAS HEATING COIL | 10951.44 | 0.000096 | 192.16 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.24 | 0.000043 | 0.000355 |
ROOM_2_FLR_3 FAN COIL | 1.23 | 0.000043 | 0.000352 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.23 | 0.000251 | 0.002062 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.76 | 0.000252 | 0.002311 |
ROOM_5_FLR_3 FAN COIL | 1.09 | 0.000043 | 0.000313 |
ROOM_6_FLR_3 FAN COIL | 1.09 | 0.000043 | 0.000311 |
ROOM_1_FLR_6 FAN COIL | 0.327822 | 0.000013 | 0.000094 |
ROOM_2_FLR_6 FAN COIL | 0.325552 | 0.000013 | 0.000093 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.46 | 0.000064 | 0.000424 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.23 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.23 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.76 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.327822 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.325552 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.46 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000355 | 1.24 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000352 | 1.23 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008456 | 12.80 | 0.008456 | 0.002062 | 7.23 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008656 | 12.80 | 0.008500 | 0.002311 | 7.76 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000313 | 1.09 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000311 | 1.09 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000094 | 0.327822 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000093 | 0.325552 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000424 | 1.46 | |
VAV WITH REHEAT COOLING COIL | 31.99 | 6.70 | 0.007708 | 10.79 | 0.007708 | 0.016557 | 24.51 | 578902.01 |
FLR_3_DOAS COOLING COIL | 40.80 | 6.70 | 0.005631 | 11.84 | 0.005631 | 0.001886 | 2.05 | 65945.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.32 | 11.65 | 24.64 | 11.65 | 24.51 | 24.51 | 0.300000 | 0.475440 | 24.51 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.51 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.51 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016557 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001145 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001886 | 0.000252 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000096 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.024758 | 4042.22 | |
HEATSYS1 PUMP | 0.002948 | 887.96 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002948 | 0.353819 |
COOLSYS1 | 0.024758 | 2.97 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 337030.42 | 337030.42 | 0.002948 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.024758 | 2798.56 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.024758 | 865666.58 | 866329.43 | 98.76 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6855 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.12938067E-14 | 0.41601190E-16 | -0.13825196E-09 | -0.61617685E-17 |
29 | 8 | 0.20259350E-07 | 0.15574452E-12 | 0.36060849E-03 | -0.23035579E-09 |
30 | 7 | -0.11728067E-01 | 0.82340017E-08 | -0.22346249E-01 | 0.13335239E-03 |
31 | 6 | 0.39139693 | 0.28900057E-05 | 0.46018966 | -0.45832853E-02 |
32 | 5 | -5.0543823 | 0.10873450E-03 | -4.3497742 | 0.61495273E-01 |
33 | 4 | 32.400414 | 0.89561747E-03 | 21.082566 | -0.41412424 |
34 | 3 | -109.94425 | 0.19639160E-02 | -54.916625 | 1.4966738 |
35 | 2 | 195.86041 | 0.11107406E-02 | 77.226367 | -2.8805378 |
36 | 1 | -170.69506 | 0.11917429E-03 | -55.066722 | 2.7373596 |
37 | 0 | 57.057407 | 0.68218560E-06 | 15.590186 | |
38 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
39 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
40 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
41 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
42 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
43 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
44 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
45 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
46 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
47 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
48 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
49 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
50 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
51 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
52 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
53 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
54 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
55 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
56 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
57 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
58 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
59 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
60 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
61 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
62 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
63 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
64 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
65 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
66 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
67 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
68 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
69 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
70 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
71 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
72 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
73 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
74 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
75 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
76 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
77 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.535_SHGC_0.25 | 37 | 1 | VerySmooth | 3.042 | 3.042 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.535_SHGC_0.25 | 38 | 1 | VerySmooth | 3.042 | 3.042 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.42074E-002 | 0.16139 | 0.60667 | 0.60667 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.94082E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.42074E-002 | 0.16139 | 0.60667 | 0.60667 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.94082E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.6041E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2579E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1068 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6408E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2226E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6724E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1083 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2112E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1206 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6741E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9915E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3747E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3261E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3285E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7936E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0043E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7153E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8520E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3261E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3285E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7936E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0043E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7153E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8520E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36078.21615 | 36078.21615 | 2.88746 | 2.88746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 32.55400 | 5.61839E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4677.80982 | 4677.80982 | 0.37440 | 0.37440 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2305.06847 | 2305.06847 | 0.10883 | 0.10883 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3332.71582 | 3332.71582 | 0.26676 | 0.26676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 37.27550 | 5.62563E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 740.20906 | 740.20906 | 3.49479E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3058.56704 | 3058.56704 | 0.24476 | 0.24476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 34.63767 | 5.62158E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1392.32593 | 1392.32593 | 6.57365E-002 | 6.57365E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1801.83247 | 1801.83247 | 0.14419 | 0.14419 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 37.82967 | 5.62649E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 858.75570 | 858.75570 | 4.05448E-002 | 5.77652E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45259.55933 | 45259.55933 | 3.62213 | 3.62213 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 39.64733 | 5.62931E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1867.89648 | 1867.89648 | 8.81880E-002 | 8.81880E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19628.23757 | 19628.23757 | 1.57238 | 1.57238 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5778.87837 | 5778.87837 | 0.27284 | 0.67639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66736.09637 | 66736.09637 | 5.34320 | 5.34320 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13358.35854 | 13358.35854 | 0.63070 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11473.73968 | 11473.73968 | 1.23733 | 1.23733 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4965.77920 | 4965.77920 | 0.23582 | 0.23582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11401.46218 | 11401.46218 | 1.22954 | 1.22954 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4970.30335 | 4970.30335 | 0.23604 | 0.23604 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 67010.75758 | 67010.75758 | 7.22626 | 7.22626 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 28712.84537 | 28712.84537 | 1.36359 | 1.36359 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 71959.36414 | 71959.36414 | 7.76052 | 7.76052 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 28813.60575 | 28813.60575 | 1.36838 | 1.36838 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10130.94877 | 10130.94877 | 1.09252 | 1.09252 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4956.11409 | 4956.11409 | 0.23536 | 0.23536 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10068.68636 | 10068.68636 | 1.08581 | 1.08581 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4960.64044 | 4960.64044 | 0.23558 | 0.23558 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 22036.81386 | 22036.81386 | 1.76362 | 1.76362 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8165.41969 | 8165.41969 | 0.38552 | 0.47476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3039.88493 | 3039.88493 | 0.32782 | 0.32782 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1515.98647 | 1515.98647 | 7.19938E-002 | 7.19938E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3018.83357 | 3018.83357 | 0.32555 | 0.32555 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1516.52177 | 1516.52177 | 7.20193E-002 | 7.20193E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13494.60099 | 13494.60099 | 1.45531 | 1.45531 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7305.44810 | 7305.44810 | 0.34694 | 0.34694 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30698.94101 | 30698.94101 | 2.45999 | 2.45999 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5160.25096 | 5160.25096 | 0.24363 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32120.58270 | 32120.58270 | 2.57387 | 2.57387 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5270.40542 | 5270.40542 | 0.24883 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31076.28184 | 31076.28184 | 2.49372 | 2.49372 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1354.17596 | 1354.17596 | 6.39269E-002 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11135.38867 | 11135.38867 | 0.89116 | 0.89116 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5442.19417 | 5442.19417 | 0.25695 | 0.25695 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 516624.38 | 24.51121 | 24.51121 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 130117.30 | 7.31169 | 7.31169 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 63092.52 | 21.21221 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 36503.53 | 4.16573 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88746 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52221 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.36577 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.29588E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.72731E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.36577 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6546.67008 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.72731E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 136.51952 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37440 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13651 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17709 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79109E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.75871E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17709 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3153.37405 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75871E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 76.73352 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26676 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22186 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12618 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59164 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71726E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17630E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12618 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1344.58049 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17630E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.94881 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24476 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51134 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11577 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.45106E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70312E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11577 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1946.76797 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70312E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.76680 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14419 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50077 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.82020E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.60824E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03704E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.82020E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1185.40173 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03704E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.68561 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.62213 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.64174E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.71327 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32070E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.81181E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.71327 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10072.43630 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.81181E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.54080 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57238 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.15252E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74374 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16279E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.17261E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74374 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9341.78990 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17261E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.84142 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.34320 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18656 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52734 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49750 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04222E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22777E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52734 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25464.80978 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22777E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.36438 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23733 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23733 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.34422E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.54671E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51659E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.54671E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23733 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4965.70945 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.34422E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 141.89314 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.22954 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.22954 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.34818E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.52447E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51669E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.52447E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.22954 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4970.23354 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.34818E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 142.02239 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.22626 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.22626 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.51191E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.06173E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74182 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45637E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45637E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.06173E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.22626 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 28712.64777 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51191E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 820.44193 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.76052 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.76052 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.52072E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.31050E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74094 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65632E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.31050E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.76052 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 28813.40750 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52072E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 823.32061 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09252 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.09252 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.33576E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.13295E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51810E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.13295E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09252 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4956.04447 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33576E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 141.61702 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08581 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.08581 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.33972E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.11373E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51815E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.11373E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.08581 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4960.57076 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33972E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 141.74633 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.76362 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67299 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83419 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.66128E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06399E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83419 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12162.08579 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06399E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.03709 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32782 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32782 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.32623E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.39436E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51567E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.39436E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32782 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1515.96591 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32623E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.31665 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32555 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32555 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.32670E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.32955E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74152 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51577E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.32955E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32555 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1516.50120 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32670E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.33194 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.45531 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.45531 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.39106E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.24130E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74117 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57707E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.24130E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.45531 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7305.36859 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.39106E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 208.73967 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45999 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10273 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16357 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70863E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.39178E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16357 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10735.38629 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.39178E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.20552 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57387 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.81880E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21744 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.88031E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.71375E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21744 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11103.40982 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.71375E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 242.97283 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49372 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.67763E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17953 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47300 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20698E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11073E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17953 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6984.94215 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11073E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.45997 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89116 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35239 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47300 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42152 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93971 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08118E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.52804E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42152 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7461.94592 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.52804E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 181.33091 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.31883 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65361 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.63765 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65361 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.51121 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.51121 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47544 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.51121 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.51121 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.98703 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.78892 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70760E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70760E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 578902.01491 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.65565E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.51121 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 130858.92965 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14481E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2296.10268 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.51121 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.65565E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.87615E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14481E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 40.80000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.83593 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 65945.85541 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.88604E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 10951.44367 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.58080E-005 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 192.15837 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.88604E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.52481E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.58080E-005 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.47580E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4042.21746 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.94849E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.35382 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.94849E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 887.95545 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 337030.42279 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 337030.42000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.94849E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.47580E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.97095 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.47580E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2798.56349 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.47580E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 865666.58012 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 866329.43000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 98.76156 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6580.75 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3167.47 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1351.14 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1955.57 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1190.73 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10124.39 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9386.47 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 25589.69 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5349.31 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5354.18 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30930.55 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 31039.08 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5338.90 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5343.78 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12219.12 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1633.04 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1633.62 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7869.53 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10789.24 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11159.15 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7020.96 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7495.35 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 105391.02 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 8820.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 13488.70 | 10890.19 | 2598.51 | 0.81 | 1124.11 | 11.40 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 13404.05 | 10821.80 | 2582.26 | 0.81 | 1117.06 | 11.33 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 87727.52 | 72215.33 | 15512.19 | 0.82 | 8646.23 | 87.69 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 128690.17 | 104458.01 | 24232.16 | 0.81 | 59262.66 | 601.07 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 11914.40 | 9618.49 | 2295.91 | 0.81 | 992.97 | 10.07 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 11841.30 | 9559.46 | 2281.84 | 0.81 | 986.88 | 10.01 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3572.95 | 2884.77 | 688.18 | 0.81 | 297.75 | 3.02 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3548.29 | 2864.84 | 683.45 | 0.81 | 295.69 | 3.00 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23761.52 | 19460.22 | 4301.30 | 0.82 | 12680.23 | 128.61 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 682457.97 | 433468.52 | 248989.45 | 0.64 | 142524.69 | 1445.56 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 52598.14 | 33952.87 | 18645.27 | 0.65 | 5719.18 | 58.01 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6846848684E-002 | 2.4513029829E-002 | Pass | Pass | 1.2557356209E-002 | 2.9176037253E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7378680870E-002 | 6.9800904670E-002 | Pass | Pass | 4.1865357251E-002 | 4.9606134509E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9323715890E-002 | 3.0962116536E-002 | Pass | Pass | 1.1672655570E-002 | 2.9524210082E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3059414763E-003 | 1.4566804294E-002 | Pass | Pass | 2.1608064397E-002 | 3.7212223799E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7112554154E-003 | 6.6979510248E-003 | Pass | Pass | 2.3972784882E-002 | 2.7609593708E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.5787252474E-002 | 0.1859013814 | Pass | Pass | 2.0796156702E-002 | 5.2180558184E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1973920261E-002 | 6.8012933235E-002 | Pass | Pass | 1.7626353823E-002 | 2.8899705869E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7369234313E-002 | 4.1749736547E-002 | Pass | Pass | 1.1310834471E-002 | 2.7221764000E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2089905155E-002 | 0.1805549234 | Pass | Pass | 0.3653186580 | 1.2070587335 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8814308514E-002 | 0.1996764475 | Pass | Pass | 0.2094446560 | 0.7160445850 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1865174554E-002 | 4.2553886156E-002 | Pass | Pass | 6.1929990003E-002 | 0.1848844271 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0314349068E-002 | 5.4939897025E-002 | Pass | Pass | 1.4712583666 | 15.4249811499 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9961716885E-002 | 0.2036458911 | Pass | Pass | 0.1603079360 | 0.4894279967 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.9066225794E-002 | 8.2353176869E-002 | Pass | Pass | 0.2694163484 | 1.3726563284 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.1890171375E-002 | 1.1869398379E-002 | Pass | Pass | 1.8471028007E-002 | 3.8964170125E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.8295251261E-002 | 0.1990768128 | Pass | Pass | 0.2950125645 | 1.1056404477 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.4527414651E-002 | 0.2265128439 | Pass | Pass | 0.1857286772 | 0.7097897601 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9645928445E-002 | 0.2973707589 | Pass | Pass | 0.1776150580 | 0.4164398332 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.1980627614E-002 | 7.8081807960E-002 | Pass | Pass | 1.4865922997E-002 | 4.0304838887E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8743802979E-002 | 5.8296646497E-002 | Pass | Pass | 1.6715379415E-002 | 4.3295952875E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6517065244E-002 | 8.1292328653E-002 | Pass | Pass | 2.2978012548E-002 | 4.4821453863E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.2610437072E-002 | 1.6905411776E-002 | Pass | Pass | 3.3890892240E-002 | 3.9086961605E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2728.87 | 45.09 | 495.89 | 2458.86 | 7791.31 | 13520.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.042 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.042 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.042 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 3.042 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 3.042 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 3.042 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.042 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.042 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 3.042 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 3.042 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 3.042 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.03 | 0.0000 | Y | 14.21 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 31.21 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 31.21 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.79 | 83.79 | 194.06 | |
Exterior Lighting Total | 12338.45 | 194.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 337030.42 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 866329.43 | 2.96 | 866481.71 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12401.37 | 13488.70 | 10890.19 | 2598.51 | 0.81 | - | 1124.11 | 11.40 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12323.59 | 13404.05 | 10821.80 | 2582.26 | 0.81 | - | 1117.06 | 11.33 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 72090.09 | 87727.52 | 72215.33 | 15512.19 | 0.82 | - | 8646.23 | 87.69 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 80788.72 | 128690.17 | 104458.01 | 24232.16 | 0.81 | - | 59262.66 | 601.07 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10954.61 | 11914.40 | 9618.49 | 2295.91 | 0.81 | - | 992.97 | 10.07 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10887.41 | 11841.30 | 9559.46 | 2281.84 | 0.81 | - | 986.88 | 10.01 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3284.82 | 3572.95 | 2884.77 | 688.18 | 0.81 | - | 297.75 | 3.02 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3262.16 | 3548.29 | 2864.84 | 683.45 | 0.81 | - | 295.69 | 3.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14830.07 | 23761.52 | 19460.22 | 4301.30 | 0.82 | - | 12680.23 | 128.61 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 578902.01 | 682457.97 | 433468.52 | 248989.45 | 0.64 | - | 142524.69 | 1445.56 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 65945.86 | 52598.14 | 33952.87 | 18645.27 | 0.65 | - | 5719.18 | 58.01 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6546.67 | 6580.75 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3153.37 | 3167.47 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1344.58 | 1351.14 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1946.77 | 1955.57 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1185.40 | 1190.73 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10072.44 | 10124.39 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9341.79 | 9386.47 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25464.81 | 25589.69 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4965.71 | 5349.31 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4970.23 | 5354.18 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 28712.65 | 30930.55 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 28813.41 | 31039.08 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4956.04 | 5338.90 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4960.57 | 5343.78 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12162.09 | 12219.12 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1515.97 | 1633.04 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1516.50 | 1633.62 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7305.37 | 7869.53 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10735.39 | 10789.24 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11103.41 | 11159.15 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6984.94 | 7020.96 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7461.95 | 7495.35 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 130858.93 | 105391.02 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 10951.44 | 8820.06 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.24 | 870.63 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.23 | 865.15 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.23 | 5084.66 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.76 | 5460.58 | 703.64 | 1.00 | 0.94 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 768.74 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 764.02 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 230.67 | 703.64 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 229.07 | 703.64 | 1.00 | 1.66 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.46 | 1024.01 | 703.64 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.51 | 54920.77 | 2240.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.024758 | 4042.22 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002948 | 887.96 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.024758 | 2798.56 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36078.22 | 36078.22 | 18.23 | 2.887 | 2.887 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00917 | 32.55 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4677.81 | 4677.81 | 69.74 | 0.374 | 0.374 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00894 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3332.72 | 3332.72 | 42.91 | 0.267 | 0.267 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00930 | 37.28 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 3058.57 | 3058.57 | 18.62 | 0.245 | 0.245 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00859 | 34.64 | 0.00562 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1801.83 | 1801.83 | 19.01 | 0.144 | 0.144 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00866 | 37.83 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45259.56 | 45259.56 | 579.96 | 3.622 | 3.622 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00853 | 39.65 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 19628.24 | 19628.24 | 103.93 | 1.572 | 1.572 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01008 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66736.10 | 66736.10 | 51.01 | 5.343 | 5.343 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00989 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11473.74 | 11473.74 | 294.03 | 1.237 | 1.237 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11401.46 | 11401.46 | 292.21 | 1.230 | 1.230 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 38.94 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 67010.76 | 67010.76 | 2732.47 | 7.226 | 7.226 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00846 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 71959.36 | 71959.36 | 2933.46 | 7.761 | 7.761 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00866 | 40.27 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10130.95 | 10130.95 | 259.62 | 1.093 | 1.093 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00852 | 36.74 | 0.00562 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10068.69 | 10068.69 | 258.06 | 1.086 | 1.086 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00852 | 36.41 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 22036.81 | 22036.81 | 56.59 | 1.764 | 1.764 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00931 | 40.53 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3039.88 | 3039.88 | 77.90 | 0.328 | 0.328 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3018.83 | 3018.83 | 77.37 | 0.326 | 0.326 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13494.60 | 13494.60 | 550.11 | 1.455 | 1.455 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00858 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30698.94 | 30698.94 | 92.56 | 2.460 | 2.460 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01031 | 40.67 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 32120.58 | 32120.58 | 96.85 | 2.574 | 2.574 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01023 | 40.67 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31076.28 | 31076.28 | 300.82 | 2.494 | 2.494 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01005 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11135.39 | 11135.39 | 27.02 | 0.891 | 0.891 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00846 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2305.07 | 2305.07 | 34.37 | 0.109 | 0.109 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 740.21 | 740.21 | 9.53 | 0.035 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00762 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1392.33 | 1392.33 | 8.48 | 0.066 | 0.066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00753 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 858.76 | 858.76 | 9.06 | 0.041 | 0.058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00756 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1867.90 | 1867.90 | 23.94 | 0.088 | 0.088 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00753 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 5778.88 | 5778.88 | 30.60 | 0.273 | 0.676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00771 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13358.36 | 13358.36 | 10.21 | 0.631 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00765 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4965.78 | 4965.78 | 127.26 | 0.236 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4970.30 | 4970.30 | 127.39 | 0.236 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 28712.85 | 28712.85 | 1170.81 | 1.364 | 1.364 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00768 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 28813.61 | 28813.61 | 1174.60 | 1.368 | 1.368 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00768 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4956.11 | 4956.11 | 127.01 | 0.235 | 0.235 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4960.64 | 4960.64 | 127.14 | 0.236 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8165.42 | 8165.42 | 20.97 | 0.386 | 0.475 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1515.99 | 1515.99 | 38.85 | 0.072 | 0.072 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00771 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1516.52 | 1516.52 | 38.87 | 0.072 | 0.072 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00771 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7305.45 | 7305.45 | 297.81 | 0.347 | 0.347 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5160.25 | 5160.25 | 15.56 | 0.244 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 5270.41 | 5270.41 | 15.89 | 0.249 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1354.18 | 1354.18 | 13.11 | 0.064 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00614 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5442.19 | 5442.19 | 13.21 | 0.257 | 0.257 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.51 | 24.51 | 7.31 | 7.31 | 24.5112 | 11.6536 | 24.5112 | 0.4754 | 0.3000 |
FLR_3_DOAS | 21.21 | 2.05 | 4.17 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6546.670 | 6546.670 | 1.365769 | 0.00005727 | 136.520 | 12/21 00:10:00 | 12/21 00:10:00 | 6546.67 | 6546.67 | 1.365769 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 6583.47 | 6583.47 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3153.374 | 3153.374 | 0.177093 | 0.00002759 | 76.734 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3153.37 | 3153.37 | 0.177093 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00767780 | 45.0844 | 2305.07 | 0.00 | 3169.78 | 3169.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1344.580 | 1344.580 | 0.126176 | 0.00001176 | 29.949 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1344.58 | 1344.58 | 0.126176 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00761940 | 44.7449 | 740.21 | 0.00 | 1351.88 | 1351.88 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1946.768 | 1946.768 | 0.115770 | 0.00001703 | 46.767 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1946.77 | 1946.77 | 0.115770 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00753411 | 44.2501 | 1392.33 | 0.00 | 1956.94 | 1956.94 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1185.402 | 1185.402 | 0.068202 | 0.00001037 | 28.686 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1185.40 | 1185.40 | 0.068202 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00756062 | 44.4039 | 858.76 | 0.00 | 1191.58 | 1191.58 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10072.436 | 10072.436 | 1.713267 | 0.00008812 | 212.541 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10072.44 | 10072.44 | 1.713267 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00752692 | 44.2090 | 1867.90 | 0.00 | 10128.81 | 10128.81 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9341.790 | 9341.790 | 0.743738 | 0.00008173 | 212.841 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9341.79 | 9341.79 | 0.743738 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00771293 | 45.2880 | 5778.88 | 0.00 | 9392.06 | 9392.06 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25464.810 | 25464.810 | 2.527336 | 0.00022278 | 563.364 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25464.81 | 25464.81 | 2.527336 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00765156 | 44.9315 | 13358.36 | 0.00 | 25603.38 | 25603.38 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12401.365 | -999.000 | 1.237333 | 0.00035467 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12401.37 | 12357.35 | 1.237333 | 21.74 | 14.62 | 0.00851659 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851659 | 49.6029 | 11473.74 | 0.00 | 8872.25 | 8872.25 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4965.709 | 4965.709 | 0.235824 | 0.00004344 | 141.893 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4965.71 | 4965.71 | 0.235824 | 21.11 | 13.64 | 0.00765693 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00765693 | 44.6579 | 4965.78 | 0.00 | 5353.17 | 5353.17 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12323.594 | -999.000 | 1.229538 | 0.00035245 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12323.59 | 12279.59 | 1.229538 | 21.74 | 14.62 | 0.00851669 | 12.80 | 11.23 | 0.00850000 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00851669 | 49.6035 | 11401.46 | 0.00 | 8816.66 | 8816.66 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4970.234 | 4970.234 | 0.236038 | 0.00004348 | 142.022 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4970.23 | 4970.23 | 0.236038 | 21.11 | 13.64 | 0.00765723 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00765723 | 44.6597 | 4970.30 | 0.00 | 5358.05 | 5358.05 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 72090.088 | -999.000 | 7.226264 | 0.00206173 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 72090.09 | 72090.09 | 7.226264 | 21.74 | 14.57 | 0.00845637 | 12.80 | 11.19 | 0.00845637 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00845637 | 49.2562 | 67010.76 | 0.00 | 57713.63 | 57713.63 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 28712.648 | 28712.648 | 1.363593 | 0.00025119 | 820.442 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 28712.65 | 28712.65 | 1.363593 | 21.11 | 13.66 | 0.00768300 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00768300 | 44.8074 | 28712.85 | 0.00 | 30953.16 | 30953.16 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 80788.721 | -999.000 | 7.760519 | 0.00231050 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 80788.72 | 78164.93 | 7.760519 | 21.74 | 14.74 | 0.00865632 | 12.80 | 11.23 | 0.00850000 | 40.27 | 0.00563027 | 18.42 | 0.0000 | 21.11 | 0.00865632 | 50.4069 | 71959.36 | 0.00 | 89378.81 | 87011.11 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 28813.408 | 28813.408 | 1.368378 | 0.00025207 | 823.321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 28813.41 | 28813.41 | 1.368378 | 21.11 | 13.66 | 0.00768393 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00768393 | 44.8128 | 28813.61 | 0.00 | 31061.78 | 31061.78 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10954.607 | -999.000 | 1.092525 | 0.00031329 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10954.61 | 10912.19 | 1.092525 | 21.74 | 14.63 | 0.00851810 | 12.80 | 11.23 | 0.00850000 | 36.74 | 0.00562481 | 17.31 | 0.0000 | 21.11 | 0.00851810 | 49.6116 | 10130.95 | 0.00 | 7837.88 | 7837.88 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4956.044 | 4956.044 | 0.235365 | 0.00004336 | 141.617 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4956.04 | 4956.04 | 0.235365 | 21.11 | 13.64 | 0.00765632 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00765632 | 44.6544 | 4956.11 | 0.00 | 5342.75 | 5342.75 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10887.414 | -999.000 | 1.085811 | 0.00031137 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10887.41 | 10845.16 | 1.085811 | 21.74 | 14.63 | 0.00851815 | 12.80 | 11.23 | 0.00850000 | 36.41 | 0.00562429 | 17.20 | 0.0000 | 21.11 | 0.00851815 | 49.6119 | 10068.69 | 0.00 | 7789.82 | 7789.82 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4960.571 | 4960.571 | 0.235580 | 0.00004340 | 141.746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4960.57 | 4960.57 | 0.235580 | 21.11 | 13.64 | 0.00765663 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00765663 | 44.6562 | 4960.64 | 0.00 | 5347.63 | 5347.63 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12162.086 | 12162.086 | 0.834194 | 0.00010640 | 284.037 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12162.09 | 12162.09 | 0.834194 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00773983 | 45.4432 | 8165.42 | 0.00 | 12227.00 | 12227.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3284.816 | -999.000 | 0.327822 | 0.00009394 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3284.82 | 3273.80 | 0.327822 | 21.74 | 14.62 | 0.00851567 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851567 | 49.5976 | 3039.88 | 0.00 | 2349.92 | 2349.92 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1515.966 | 1515.966 | 0.071994 | 0.00001326 | 43.317 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1515.97 | 1515.97 | 0.071994 | 21.11 | 13.69 | 0.00771419 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00771419 | 44.9878 | 1515.99 | 0.00 | 1634.25 | 1634.25 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3262.157 | -999.000 | 0.325552 | 0.00009330 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3262.16 | 3251.15 | 0.325552 | 21.74 | 14.62 | 0.00851577 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00851577 | 49.5982 | 3018.83 | 0.00 | 2333.72 | 2333.72 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1516.501 | 1516.501 | 0.072019 | 0.00001327 | 43.332 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1516.50 | 1516.50 | 0.072019 | 21.11 | 13.69 | 0.00771430 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00771430 | 44.9884 | 1516.52 | 0.00 | 1634.83 | 1634.83 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14830.070 | -999.000 | 1.455312 | 0.00042413 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 14830.07 | 14588.64 | 1.455312 | 21.74 | 14.68 | 0.00857707 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00857707 | 49.9513 | 13494.60 | 0.00 | 16427.61 | 16427.61 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7305.369 | 7305.369 | 0.346937 | 0.00006391 | 208.740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7305.37 | 7305.37 | 0.346937 | 21.11 | 13.70 | 0.00772595 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00772595 | 45.0553 | 7305.45 | 0.00 | 7875.40 | 7875.40 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10735.386 | 10735.386 | 1.163574 | 0.00009392 | 235.206 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10735.39 | 10735.39 | 1.163574 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778921 | 45.7299 | 5160.25 | 0.00 | 10794.79 | 10794.79 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11103.410 | 11103.410 | 1.217439 | 0.00009714 | 242.973 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 11103.41 | 11103.41 | 1.217439 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779336 | 45.7545 | 5270.41 | 0.00 | 11164.87 | 11164.87 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6984.942 | 6984.942 | 1.179530 | 0.00006111 | 147.460 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 6984.94 | 6984.94 | 1.179530 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00613695 | 36.1307 | 1354.18 | 0.00 | 7024.03 | 7024.03 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7461.946 | 7461.946 | 0.421521 | 0.00006528 | 181.331 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 7461.95 | 7461.95 | 0.421521 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00782316 | 45.9269 | 5442.19 | 0.00 | 7500.78 | 7500.78 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 578902.015 | -999.000 | 24.511214 | 0.01655652 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 578902.01 | 578902.01 | 24.511214 | 31.99 | 17.41 | 0.00770760 | 10.79 | 9.61 | 0.00770760 | 40.80 | 0.00563111 | 18.58 | 47.5760 | 23.99 | 0.00954300 | 46.5803 | 306065.13 | 0.00 | 619021.09 | 605768.53 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 130858.930 | 130858.930 | 7.353364 | 0.00114481 | 2296.103 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 130858.93 | 130858.93 | 7.353364 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 158.5867 | 21.61 | 0.00786771 | 44.4992 | 50809.09 | 0.00 | 127530.50 | 127530.50 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 65945.855 | -999.000 | 2.051317 | 0.00188604 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 65945.86 | 65945.86 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 11.84 | 7.85 | 0.00563111 | 40.80 | 0.00563111 | 18.58 | 99.9965 | 21.11 | 0.00855968 | 49.8509 | 196159.85 | 0.00 | 65994.93 | 65994.93 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10951.44 | 10951.44 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 333.3216 | 21.11 | 0.00768364 | 44.8111 | 87717.24 | 0.00 | 10672.89 | 10672.89 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6546.670 | 6546.670 | 1.365769 | 0.00005727 | 136.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 1.9041 | 1.942457 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6546.67 | 6546.67 | 1.0000 | 1.49305099 | 1.365769 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.05726728 | 60.00 | 32.22 | 27.78 | 0.000 | 6546.67 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 6583.47 | 6583.47 | 1.49305099 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3153.374 | 3153.374 | 0.177093 | 0.00002759 | 76.734 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.9172 | 0.935635 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3153.37 | 3153.37 | 1.0000 | 0.19359739 | 0.177093 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.02758428 | 60.00 | 32.22 | 27.78 | 0.000 | 3153.37 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00767780 | 21.00 | 0.00767780 | 45.0844 | 2305.07 | 0.00 | 3169.78 | 3169.78 | 0.19359739 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.66 | 18.91 | 0.00800000 | 53307.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1344.580 | 1344.580 | 0.126176 | 0.00001176 | 29.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.3911 | 0.398949 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1344.58 | 1344.58 | 1.0000 | 0.13793445 | 0.126176 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01176178 | 60.00 | 32.22 | 27.78 | 0.000 | 1344.58 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00761940 | 21.00 | 0.00761940 | 44.7449 | 740.21 | 0.00 | 1351.88 | 1351.88 | 0.13793445 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.21 | 16.74 | 0.00800000 | 46735.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1946.768 | 1946.768 | 0.115770 | 0.00001703 | 46.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.5662 | 0.577624 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1946.77 | 1946.77 | 1.0000 | 0.12655928 | 0.115770 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01702944 | 60.00 | 32.22 | 27.78 | 0.000 | 1946.77 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00753411 | 21.00 | 0.00753411 | 44.2501 | 1392.33 | 0.00 | 1956.94 | 1956.94 | 0.12655928 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.76 | 18.62 | 0.00800000 | 52397.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1185.402 | 1185.402 | 0.068202 | 0.00001037 | 28.686 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.3448 | 0.351720 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1185.40 | 1185.40 | 1.0000 | 0.07455799 | 0.068202 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01036935 | 60.00 | 32.22 | 27.78 | 0.000 | 1185.40 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00756062 | 21.00 | 0.00756062 | 44.4039 | 858.76 | 0.00 | 1191.58 | 1191.58 | 0.07455799 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.27 | 18.79 | 0.00800000 | 52916.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10072.436 | 10072.436 | 1.713267 | 0.00008812 | 212.541 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 2.9296 | 2.988584 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10072.44 | 10072.44 | 1.0000 | 1.87293349 | 1.713267 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.08810908 | 60.00 | 32.22 | 27.78 | 0.000 | 10072.44 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00752692 | 21.00 | 0.00752692 | 44.2090 | 1867.90 | 0.00 | 10128.81 | 10128.81 | 1.87293349 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.90 | 15.19 | 0.00800000 | 42342.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9341.790 | 9341.790 | 0.743738 | 0.00008173 | 212.841 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 2.7171 | 2.771794 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9341.79 | 9341.79 | 1.0000 | 0.81304970 | 0.743738 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.08171772 | 60.00 | 32.22 | 27.78 | 0.000 | 9341.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00771293 | 21.00 | 0.00771293 | 45.2880 | 5778.88 | 0.00 | 9392.06 | 9392.06 | 0.81304970 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.93 | 17.34 | 0.00800000 | 48486.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25464.810 | 25464.810 | 2.527336 | 0.00022278 | 563.364 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 7.4066 | 7.555641 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25464.81 | 25464.81 | 1.0000 | 2.76286886 | 2.527336 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.22275454 | 60.00 | 32.22 | 27.78 | 0.000 | 25464.81 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00765156 | 21.00 | 0.00765156 | 44.9315 | 13358.36 | 0.00 | 25603.38 | 25603.38 | 2.76286886 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.69 | 16.56 | 0.00800000 | 46201.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12401.365 | -999.000 | 1.237333 | 0.00035467 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6719 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.237333 | 1.35264497 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 1.4326 | 1.432553 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12401.37 | 12357.35 | 1.0000 | 1.35264497 | 1.237333 | 21.74 | 14.62 | 0.00851659 | 43490.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.35463467 | 6.70 | 15.03 | 8.33 | 0.000 | 12401.37 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851659 | 21.11 | 0.00851659 | 49.6029 | 11473.74 | 0.00 | 8872.25 | 8872.25 | 1.35264497 | 21.74 | 15.59 | 0.00851659 | 43490.4 | 15.32 | 13.14 | 0.00851659 | 36931.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4965.709 | 4965.709 | 0.235824 | 0.00004344 | 141.893 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.237333 | 1.35264497 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 1.4443 | 1.473371 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4965.71 | 4965.71 | 1.0000 | 0.25780095 | 0.235824 | 21.11 | 13.64 | 0.00765693 | 40662.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04343776 | 60.00 | 32.22 | 27.78 | 0.000 | 4965.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00765693 | 21.11 | 0.00765693 | 44.6579 | 4965.78 | 0.00 | 5353.17 | 5353.17 | 0.25780095 | 16.60 | 12.82 | 0.00765693 | 36066.1 | 36.98 | 20.01 | 0.00765693 | 56830.9 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12323.594 | -999.000 | 1.229538 | 0.00035245 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6721 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.229538 | 1.34412411 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 1.4236 | 1.423569 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12323.59 | 12279.59 | 1.0000 | 1.34412411 | 1.229538 | 21.74 | 14.62 | 0.00851669 | 43490.7 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.35241071 | 6.70 | 15.03 | 8.33 | 0.000 | 12323.59 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00851669 | 21.11 | 0.00851669 | 49.6035 | 11401.46 | 0.00 | 8816.66 | 8816.66 | 1.34412411 | 21.74 | 15.59 | 0.00851669 | 43490.7 | 15.31 | 13.14 | 0.00851669 | 36931.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4970.234 | 4970.234 | 0.236038 | 0.00004348 | 142.022 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.229538 | 1.34412411 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 1.4456 | 1.474714 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4970.23 | 4970.23 | 1.0000 | 0.25803583 | 0.236038 | 21.11 | 13.64 | 0.00765723 | 40663.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04347734 | 60.00 | 32.22 | 27.78 | 0.000 | 4970.23 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00765723 | 21.11 | 0.00765723 | 44.6597 | 4970.30 | 0.00 | 5358.05 | 5358.05 | 0.25803583 | 16.60 | 12.82 | 0.00765723 | 36066.9 | 36.98 | 20.01 | 0.00765723 | 56831.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72090.088 | -999.000 | 7.226264 | 0.00206173 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5600 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.226264 | 7.89970994 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 8.3277 | 8.327541 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 72090.09 | 72090.09 | 1.0000 | 7.89970994 | 7.226264 | 21.74 | 14.57 | 0.00845637 | 43337.7 | 12.80 | 11.19 | 0.00845637 | 34212.0 | 2.06151858 | 6.70 | 15.03 | 8.33 | 0.000 | 72090.09 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00845637 | 21.11 | 0.00845637 | 49.2562 | 67010.76 | 0.00 | 57713.63 | 57713.63 | 7.89970994 | 21.74 | 15.54 | 0.00845637 | 43337.7 | 14.58 | 12.79 | 0.00845637 | 36031.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28712.648 | 28712.648 | 1.363593 | 0.00025119 | 820.442 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.226264 | 7.89970994 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 8.3512 | 8.519304 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 28712.65 | 28712.65 | 1.0000 | 1.49067200 | 1.363593 | 21.11 | 13.66 | 0.00768300 | 40729.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.25116514 | 60.00 | 32.22 | 27.78 | 0.000 | 28712.65 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00768300 | 21.11 | 0.00768300 | 44.8074 | 28712.85 | 0.00 | 30953.16 | 30953.16 | 1.49067200 | 16.60 | 12.84 | 0.00768300 | 36132.2 | 36.97 | 20.03 | 0.00768300 | 56896.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80788.721 | -999.000 | 7.760519 | 0.00231050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9317 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.760519 | 8.48375395 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 9.3325 | 9.332371 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 80788.72 | 78164.93 | 1.0000 | 8.48375395 | 7.760519 | 21.74 | 14.74 | 0.00865632 | 43845.0 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 2.31026836 | 6.70 | 15.03 | 8.33 | 0.000 | 80788.72 | 40.27 | 0.00563027 | 18.42 | 0.00000000 | 0.0000 | 21.11 | 0.00865632 | 21.11 | 0.00865632 | 50.4069 | 71959.36 | 0.00 | 89378.81 | 87011.11 | 8.48375395 | 21.74 | 15.71 | 0.00865632 | 43845.0 | 11.70 | 11.69 | 0.00854569 | 33309.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28813.408 | 28813.408 | 1.368378 | 0.00025207 | 823.321 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.760519 | 8.48375395 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 8.3805 | 8.549201 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 28813.41 | 28813.41 | 1.0000 | 1.49590313 | 1.368378 | 21.11 | 13.66 | 0.00768393 | 40731.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.25204654 | 60.00 | 32.22 | 27.78 | 0.000 | 28813.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00768393 | 21.11 | 0.00768393 | 44.8128 | 28813.61 | 0.00 | 31061.78 | 31061.78 | 1.49590313 | 16.60 | 12.84 | 0.00768393 | 36134.5 | 36.97 | 20.03 | 0.00768393 | 56899.1 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10954.607 | -999.000 | 1.092525 | 0.00031329 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6747 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.092525 | 1.19434200 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 1.2655 | 1.265430 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10954.61 | 10912.19 | 1.0000 | 1.19434200 | 1.092525 | 21.74 | 14.63 | 0.00851810 | 43494.3 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.31326255 | 6.70 | 15.03 | 8.33 | 0.000 | 10954.61 | 36.74 | 0.00562481 | 17.31 | 0.00000000 | 0.0000 | 21.11 | 0.00851810 | 21.11 | 0.00851810 | 49.6116 | 10130.95 | 0.00 | 7837.88 | 7837.88 | 1.19434200 | 21.74 | 15.59 | 0.00851810 | 43494.3 | 15.31 | 13.14 | 0.00851810 | 36931.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4956.044 | 4956.044 | 0.235365 | 0.00004336 | 141.617 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.092525 | 1.19434200 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 1.4415 | 1.470504 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4956.04 | 4956.04 | 1.0000 | 0.25729918 | 0.235365 | 21.11 | 13.64 | 0.00765632 | 40661.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04335322 | 60.00 | 32.22 | 27.78 | 0.000 | 4956.04 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00765632 | 21.11 | 0.00765632 | 44.6544 | 4956.11 | 0.00 | 5342.75 | 5342.75 | 0.25729918 | 16.60 | 12.82 | 0.00765632 | 36064.6 | 36.98 | 20.01 | 0.00765632 | 56829.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10887.414 | -999.000 | 1.085811 | 0.00031137 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6748 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.085811 | 1.18700181 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 1.2577 | 1.257668 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10887.41 | 10845.16 | 1.0000 | 1.18700181 | 1.085811 | 21.74 | 14.63 | 0.00851815 | 43494.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.31134108 | 6.70 | 15.03 | 8.33 | 0.000 | 10887.41 | 36.41 | 0.00562429 | 17.20 | 0.00000000 | 0.0000 | 21.11 | 0.00851815 | 21.11 | 0.00851815 | 49.6119 | 10068.69 | 0.00 | 7789.82 | 7789.82 | 1.18700181 | 21.74 | 15.59 | 0.00851815 | 43494.4 | 15.31 | 13.14 | 0.00851815 | 36931.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4960.571 | 4960.571 | 0.235580 | 0.00004340 | 141.746 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.085811 | 1.18700181 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 1.4428 | 1.471847 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4960.57 | 4960.57 | 1.0000 | 0.25753417 | 0.235580 | 21.11 | 13.64 | 0.00765663 | 40662.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04339281 | 60.00 | 32.22 | 27.78 | 0.000 | 4960.57 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00765663 | 21.11 | 0.00765663 | 44.6562 | 4960.64 | 0.00 | 5347.63 | 5347.63 | 0.25753417 | 16.60 | 12.82 | 0.00765663 | 36065.4 | 36.98 | 20.01 | 0.00765663 | 56830.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12162.086 | 12162.086 | 0.834194 | 0.00010640 | 284.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 3.5374 | 3.608602 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12162.09 | 12162.09 | 1.0000 | 0.91193622 | 0.834194 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10638838 | 60.00 | 32.22 | 27.78 | 0.000 | 12162.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00773983 | 21.00 | 0.00773983 | 45.4432 | 8165.42 | 0.00 | 12227.00 | 12227.00 | 0.91193622 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.75 | 17.95 | 0.00800000 | 50342.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3284.816 | -999.000 | 0.327822 | 0.00009394 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6702 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.327822 | 0.35837352 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 0.3795 | 0.379448 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3284.82 | 3273.80 | 1.0000 | 0.35837352 | 0.327822 | 21.74 | 14.62 | 0.00851567 | 43488.1 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.09393399 | 6.70 | 15.03 | 8.33 | 0.000 | 3284.82 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851567 | 21.11 | 0.00851567 | 49.5976 | 3039.88 | 0.00 | 2349.92 | 2349.92 | 0.35837352 | 21.74 | 15.59 | 0.00851567 | 43488.1 | 15.32 | 13.14 | 0.00851567 | 36930.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1515.966 | 1515.966 | 0.071994 | 0.00001326 | 43.317 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.327822 | 0.35837352 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.4409 | 0.449801 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1515.97 | 1515.97 | 1.0000 | 0.07870325 | 0.071994 | 21.11 | 13.69 | 0.00771419 | 40808.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01326098 | 60.00 | 32.22 | 27.78 | 0.000 | 1515.97 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00771419 | 21.11 | 0.00771419 | 44.9878 | 1515.99 | 0.00 | 1634.25 | 1634.25 | 0.07870325 | 16.60 | 12.87 | 0.00771419 | 36211.1 | 36.97 | 20.06 | 0.00771419 | 56975.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3262.157 | -999.000 | 0.325552 | 0.00009330 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6704 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.325552 | 0.35589178 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 0.3768 | 0.376831 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3262.16 | 3251.15 | 1.0000 | 0.35589178 | 0.325552 | 21.74 | 14.62 | 0.00851577 | 43488.3 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.09328603 | 6.70 | 15.03 | 8.33 | 0.000 | 3262.16 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00851577 | 21.11 | 0.00851577 | 49.5982 | 3018.83 | 0.00 | 2333.72 | 2333.72 | 0.35589178 | 21.74 | 15.59 | 0.00851577 | 43488.3 | 15.32 | 13.14 | 0.00851577 | 36931.0 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1516.501 | 1516.501 | 0.072019 | 0.00001327 | 43.332 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.325552 | 0.35589178 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 0.4411 | 0.449960 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1516.50 | 1516.50 | 1.0000 | 0.07873104 | 0.072019 | 21.11 | 13.69 | 0.00771430 | 40808.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01326566 | 60.00 | 32.22 | 27.78 | 0.000 | 1516.50 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00771430 | 21.11 | 0.00771430 | 44.9884 | 1516.52 | 0.00 | 1634.83 | 1634.83 | 0.07873104 | 16.60 | 12.87 | 0.00771430 | 36211.4 | 36.97 | 20.06 | 0.00771430 | 56976.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14830.070 | -999.000 | 1.455312 | 0.00042413 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7843 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.455312 | 1.59093838 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 1.7131 | 1.713107 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 14830.07 | 14588.64 | 1.0000 | 1.59093838 | 1.455312 | 21.74 | 14.68 | 0.00857707 | 43643.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.42408694 | 6.70 | 15.03 | 8.33 | 0.000 | 14830.07 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00857707 | 21.11 | 0.00857707 | 49.9513 | 13494.60 | 0.00 | 16427.61 | 16427.61 | 1.59093838 | 21.74 | 15.64 | 0.00857707 | 43643.8 | 11.63 | 11.63 | 0.00857707 | 33318.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7305.369 | 7305.369 | 0.346937 | 0.00006391 | 208.740 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.455312 | 1.59093838 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 2.1248 | 2.167569 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7305.37 | 7305.37 | 1.0000 | 0.37926898 | 0.346937 | 21.11 | 13.70 | 0.00772595 | 40838.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06390403 | 60.00 | 32.22 | 27.78 | 0.000 | 7305.37 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00772595 | 21.11 | 0.00772595 | 45.0553 | 7305.45 | 0.00 | 7875.40 | 7875.40 | 0.37926898 | 16.60 | 12.88 | 0.00772595 | 36240.9 | 36.97 | 20.06 | 0.00772595 | 57005.6 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10735.386 | 10735.386 | 1.163574 | 0.00009392 | 235.206 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 3.1224 | 3.185287 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10735.39 | 10735.39 | 1.0000 | 1.27201255 | 1.163574 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09390826 | 60.00 | 32.22 | 27.78 | 0.000 | 10735.39 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00778921 | 21.00 | 0.00778921 | 45.7299 | 5160.25 | 0.00 | 10794.79 | 10794.79 | 1.27201255 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.92 | 16.29 | 0.00800000 | 45421.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11103.410 | 11103.410 | 1.217439 | 0.00009714 | 242.973 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 3.2295 | 3.294483 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 11103.41 | 11103.41 | 1.0000 | 1.33089780 | 1.217439 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09712756 | 60.00 | 32.22 | 27.78 | 0.000 | 11103.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00779336 | 21.00 | 0.00779336 | 45.7545 | 5270.41 | 0.00 | 11164.87 | 11164.87 | 1.33089780 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.83 | 16.25 | 0.00800000 | 45323.7 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6984.942 | 6984.942 | 1.179530 | 0.00006111 | 147.460 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 2.0316 | 2.072496 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 6984.94 | 6984.94 | 1.0000 | 1.28945559 | 1.179530 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06110109 | 60.00 | 32.22 | 27.78 | 0.000 | 6984.94 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.23 | 0.00613695 | 21.00 | 0.00613695 | 36.1307 | 1354.18 | 0.00 | 7024.03 | 7024.03 | 1.28945559 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.94 | 15.20 | 0.00800000 | 42382.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7461.946 | 7461.946 | 0.421521 | 0.00006528 | 181.331 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 2.1703 | 2.214027 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 7461.95 | 7461.95 | 1.0000 | 0.46080382 | 0.421521 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06527370 | 60.00 | 32.22 | 27.78 | 0.000 | 7461.95 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00782316 | 21.00 | 0.00782316 | 45.9269 | 5442.19 | 0.00 | 7500.78 | 7500.78 | 0.46080382 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.56 | 18.88 | 0.00800000 | 53212.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 578902.015 | -999.000 | 24.511214 | 0.01655652 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1680 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.511214 | 26.79551727 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 66.8736 | 66.873555 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 578902.01 | 578902.01 | 1.0000 | 26.79551727 | 24.511214 | 31.99 | 17.41 | 0.00770760 | 51876.4 | 10.79 | 9.61 | 0.00770760 | 30272.0 | 16.55483541 | 6.70 | 15.03 | 8.33 | 54920.772 | 523981.24 | 40.80 | 0.00563111 | 18.58 | 11.66146000 | 47.5760 | 23.99 | 0.00959206 | 23.99 | 0.00954300 | 46.5803 | 306065.13 | 0.00 | 619021.09 | 605768.53 | 26.79551727 | 31.99 | 18.46 | 0.00770760 | 51876.4 | 9.81 | 9.78 | 0.00751127 | 28774.7 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 130858.930 | 130858.930 | 7.353364 | 0.00114481 | 2296.103 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.511214 | 26.79551727 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 38.0610 | 38.827038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | Sensible | 130858.93 | 130858.93 | 1.0000 | 8.03865518 | 7.353364 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 1.14469422 | 60.00 | 32.22 | 27.78 | 0.000 | 130858.93 | 0.50 | 0.00431558 | 0.50 | 11.66146000 | 158.5867 | 18.49 | 0.00773446 | 21.61 | 0.00786771 | 44.4992 | 50809.09 | 0.00 | 127530.50 | 127530.50 | 8.03865518 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 65945.855 | -999.000 | 2.051317 | 0.00188604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.3079 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 24.75542904 | 15.03 | 6.70 | 8.33 | 865666.58 | 7.6179 | 7.617928 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 65945.86 | 65945.86 | 1.0000 | 2.24248814 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 55507.6 | 11.84 | 7.85 | 0.00563111 | 26100.2 | 1.88585072 | 6.70 | 15.03 | 8.33 | 2195.006 | 63750.85 | 40.80 | 0.00563111 | 18.58 | 2.05124512 | 99.9965 | 21.11 | 0.00855214 | 21.11 | 0.00855968 | 49.8509 | 196159.85 | 0.00 | 65994.93 | 65994.93 | 2.24248814 | 40.80 | 19.66 | 0.00563111 | 55507.6 | 11.81 | 8.61 | 0.00563111 | 26078.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 2.94818839 | 54.44 | 82.22 | 27.78 | 343813.29 | 3.1853 | 3.249393 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10951.44 | 10951.44 | 1.0000 | 0.67274644 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 0.09579823 | 60.00 | 32.22 | 27.78 | 0.000 | 10951.44 | 0.50 | 0.00431558 | 0.50 | 2.05124512 | 333.3216 | 21.11 | 0.00768203 | 21.11 | 0.00768364 | 44.8111 | 87717.24 | 0.00 | 10672.89 | 10672.89 | 0.67274644 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.51 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1905.00 | 6223.33 | 567.50 |
RETAIL_1_FLR_1 | 3130.17 | 4665.33 | 611.00 |
RETAIL_2_FLR_1 | 2301.83 | 5195.00 | 702.50 |
MECH_FLR_1 | 1744.33 | 6049.83 | 86.83 |
STORAGE_FLR_1 | 1646.17 | 6287.50 | 168.33 |
LAUNDRY_FLR_1 | 8019.83 | 3564.17 | 3321.17 |
CAFE_FLR_1 | 4710.50 | 3050.83 | 1178.67 |
LOBBY_FLR_1 | 2982.50 | 3918.67 | 1044.00 |
ROOM_1_FLR_3 | 410.50 | 7811.33 | 196.00 |
ROOM_2_FLR_3 | 707.67 | 7851.83 | 515.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 239.33 | 8753.83 | 239.33 |
ROOM_5_FLR_3 | 482.50 | 7819.33 | 198.67 |
ROOM_6_FLR_3 | 875.50 | 7617.83 | 498.83 |
CORRIDOR_FLR_3 | 1586.83 | 7063.50 | 790.33 |
ROOM_1_FLR_6 | 932.67 | 7615.83 | 499.50 |
ROOM_2_FLR_6 | 1362.00 | 7698.67 | 991.33 |
ROOM_3_MULT9_FLR_6 | 127.67 | 7854.83 | 93.33 |
BANQUET_FLR_6 | 4744.33 | 2121.83 | 1125.83 |
DINING_FLR_6 | 5496.17 | 1366.33 | 1056.83 |
KITCHEN_FLR_6 | 8582.00 | 6691.67 | 6681.50 |
CORRIDOR_FLR_6 | 2028.83 | 5951.33 | 524.83 |
Facility | 8748.67 | 8760.00 | 7301.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 304.83 | 0.00 | 304.83 |
ROOM_2_FLR_3 | 0.00 | 295.00 | 0.00 | 295.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 7.33 | 0.00 | 7.33 |
ROOM_5_FLR_3 | 0.00 | 291.67 | 0.00 | 291.67 |
ROOM_6_FLR_3 | 0.00 | 345.83 | 0.00 | 345.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 367.33 | 0.00 | 367.33 |
ROOM_2_FLR_6 | 0.00 | 341.00 | 0.00 | 341.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 19.33 | 0.00 | 19.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 600.17 | 0.00 | 600.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.020 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.364 | 0.134 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.434 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.599 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.594 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.428 | 0.143 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.675 | 0.105 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.747 | 0.043 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.173 | 0.000 | 0.052 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.173 | 0.000 | 0.051 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.077 | 0.000 | 0.080 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.173 | 0.000 | 0.052 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.173 | 0.000 | 0.051 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.569 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.173 | 0.000 | 0.061 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.173 | 0.000 | 0.058 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.140 | 0.000 | 0.097 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.830 | 0.050 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.188 | 0.050 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.426 | 0.144 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.130 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.493 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.359 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.945 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.463 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.417 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 10.238 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.581 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.172 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.325 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.388 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.574 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 8.616 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.705 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42243087.07 | 0.00 | 42243087.07 | 0.00 | 42243087.07 | 26946214.98 | 298.86 | 39.42 | 8421.72 | 0.00 |
RETAIL_1_FLR_1 | 5402719.30 | 0.00 | 5402719.30 | 305216.72 | 5707936.03 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3784471.31 | 0.00 | 3784471.31 | 117814.04 | 3902285.35 | 2892943.94 | 104.91 | 42.55 | 8612.54 | 0.00 |
MECH_FLR_1 | 3353754.26 | 0.00 | 3353754.26 | 278442.40 | 3632196.66 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1921470.98 | 0.00 | 1921470.98 | 160645.93 | 2082116.91 | 1821682.01 | 2725.44 | 379.22 | 5655.33 | 0.00 |
LAUNDRY_FLR_1 | 56929014.08 | 0.00 | 56929014.08 | 380198.88 | 57309212.96 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23553379.90 | 0.00 | 23553379.90 | 674698.84 | 24228078.75 | 21330615.53 | 3271.12 | 242.89 | 5245.99 | 0.00 |
LOBBY_FLR_1 | 77575210.61 | 0.00 | 77575210.61 | 1927768.70 | 79502979.31 | 59728886.00 | 171.98 | 81.06 | 8506.97 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 53641.17 | 1513797.89 | 177156.17 | 1690954.06 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 52748.09 | 1512733.73 | 177142.66 | 1689876.39 | 1946647.51 | 2190.00 | 5880.63 | 689.37 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 49428.56 | 1149340.53 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 51544.67 | 19855373.96 | 49442.08 | 19904816.04 | 26405105.73 | 2190.00 | 5907.65 | 662.35 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 53731.30 | 1513888.01 | 177156.17 | 1691044.18 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 52205.24 | 1512190.87 | 177142.66 | 1689333.53 | 1946647.51 | 2190.00 | 5877.08 | 692.92 | 0.00 |
CORRIDOR_FLR_3 | 23248629.48 | 0.00 | 23248629.48 | 214217.46 | 23462846.93 | 14972100.18 | 7.89 | 9.67 | 8742.44 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 62557.96 | 427597.14 | 177191.96 | 604789.11 | 486718.90 | 2021.80 | 5878.64 | 859.56 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 59326.77 | 424323.18 | 177178.45 | 601501.62 | 486661.88 | 2043.49 | 5887.72 | 828.79 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 62732.88 | 2407923.19 | 90657.61 | 2498580.80 | 3126920.42 | 2190.00 | 5876.17 | 693.83 | 0.00 |
BANQUET_FLR_6 | 41770522.12 | 0.00 | 41770522.12 | 432658.25 | 42203180.36 | 37458366.31 | 3458.08 | 521.85 | 4780.07 | 0.00 |
DINING_FLR_6 | 44867950.62 | 0.00 | 44867950.62 | 432658.25 | 45300608.87 | 37458366.31 | 565.71 | 192.34 | 8001.95 | 0.00 |
KITCHEN_FLR_6 | 57776910.00 | 0.00 | 57776910.00 | 387329.44 | 58164239.44 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12207204.50 | 0.00 | 12207204.50 | 379096.44 | 12586300.94 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 5453178.44 | 0.21E+10 | 17852245.51 | 0.21E+10 | 0.43E+10 | 8760.00 | 6627.69 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3395 | 0.0000 | 1.3395 | 0.0000 | 1.3395 | 0.8545 | 298.86 | 39.42 | 8421.72 |
RETAIL_1_FLR_1 | 0.1713 | 0.0000 | 0.1713 | 0.0097 | 0.1810 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1200 | 0.0000 | 0.1200 | 0.0037 | 0.1237 | 0.0917 | 104.91 | 42.55 | 8612.54 |
MECH_FLR_1 | 0.1063 | 0.0000 | 0.1063 | 0.0088 | 0.1152 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0609 | 0.0000 | 0.0609 | 0.0051 | 0.0660 | 0.0578 | 2725.44 | 379.22 | 5655.33 |
LAUNDRY_FLR_1 | 1.8052 | 0.0000 | 1.8052 | 0.0121 | 1.8173 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7469 | 0.0000 | 0.7469 | 0.0214 | 0.7683 | 0.6764 | 3271.12 | 242.89 | 5245.99 |
LOBBY_FLR_1 | 2.4599 | 0.0000 | 2.4599 | 0.0611 | 2.5210 | 1.8940 | 171.98 | 81.06 | 8506.97 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0056 | 0.0536 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0056 | 0.0536 | 0.0617 | 2190.00 | 5880.63 | 689.37 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0016 | 0.6296 | 0.0016 | 0.6312 | 0.8373 | 2190.00 | 5907.65 | 662.35 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0056 | 0.0536 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0056 | 0.0536 | 0.0617 | 2190.00 | 5877.08 | 692.92 |
CORRIDOR_FLR_3 | 0.7372 | 0.0000 | 0.7372 | 0.0068 | 0.7440 | 0.4748 | 7.89 | 9.67 | 8742.44 |
ROOM_1_FLR_6 | 0.0116 | 0.0020 | 0.0136 | 0.0056 | 0.0192 | 0.0154 | 2021.80 | 5878.64 | 859.56 |
ROOM_2_FLR_6 | 0.0116 | 0.0019 | 0.0135 | 0.0056 | 0.0191 | 0.0154 | 2043.49 | 5887.72 | 828.79 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0020 | 0.0764 | 0.0029 | 0.0792 | 0.0992 | 2190.00 | 5876.17 | 693.83 |
BANQUET_FLR_6 | 1.3245 | 0.0000 | 1.3245 | 0.0137 | 1.3383 | 1.1878 | 3458.08 | 521.85 | 4780.07 |
DINING_FLR_6 | 1.4228 | 0.0000 | 1.4228 | 0.0137 | 1.4365 | 1.1878 | 565.71 | 192.34 | 8001.95 |
KITCHEN_FLR_6 | 1.8321 | 0.0000 | 1.8321 | 0.0123 | 1.8444 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3871 | 0.0000 | 0.3871 | 0.0120 | 0.3991 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.8847 | 0.1729 | 64.0577 | 0.4470 | 64.5046 | 73.9670 | 8760.00 | 6627.69 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.47E+09 | 0.00 | 0.47E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 35636200.53 | 448488.08 | 36084688.62 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.9549 | 0.0000 | 14.9549 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.1300 | 0.0142 | 1.1442 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4721.73 | 0.00 | 0.00 | 0.00 | 4038.27 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 16.0605 | 0.0000 | 0.0000 | 0.0000 | 13.6659 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.4274 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
Electricity:Building | 2448.51 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.42 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.55 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.21 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.21 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.18 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.07 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.07 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.72 | 1114.48 | 23-APR-22:30 | 3261.56 | 01-SEP-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2135.74 | 2701.75 | 14-DEC-02:30 | 214651.02 | 28-JUN-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.47 | 0.00 | 01-JAN-11:10 | 1893.19 | 17-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.16 | 964.11 | 16-DEC-03:30 | 1203.01 | 13-NOV-14:10 |
Fans:Electricity | 610.12 | 11084.66 | 04-NOV-07:10 | 50214.83 | 07-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 781.44 | 11777.30 | 12-FEB-15:00 | 60995.58 | 07-SEP-21:10 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
ElectricityPurchased:Plant | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
Cogeneration:ElectricityPurchased | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
General:Cogeneration:ElectricityPurchased | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
ElectricityNet:Plant | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
Cogeneration:ElectricityNet | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
General:Cogeneration:ElectricityNet | 6178.78 | 69956.38 | 24-FEB-03:40 | 440906.66 | 21-JUL-20:00 |
General:Fans:Electricity | 610.12 | 11084.66 | 04-NOV-07:10 | 50214.83 | 07-SEP-21:10 |
ExteriorLights:Electricity | 194.06 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.06 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 149.55 | 0.00 | 01-JAN-11:10 | 9938.94 | 11-JUN-08:10 |
General:HeatRecovery:Electricity | 149.55 | 0.00 | 01-JAN-11:10 | 9938.94 | 11-JUN-08:10 |
WaterSystems:Electricity | 90.74 | 1086.56 | 27-JUL-01:00 | 4738.72 | 01-JUN-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 27-JUL-01:00 | 4738.72 | 01-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1896.43 | 0.00 | 01-JAN-00:10 | 203708.69 | 28-JUN-18:10 |
General:Cooling:Electricity | 1896.43 | 0.00 | 01-JAN-00:10 | 203708.69 | 28-JUN-18:10 |
Pumps:Electricity | 93.93 | 48.68 | 25-OCT-07:20 | 4495.93 | 28-JUN-18:20 |
General:Pumps:Electricity | 93.93 | 48.68 | 25-OCT-07:20 | 4495.93 | 28-JUN-18:20 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4939.62 | 29270.80 | 11-MAR-02:10 | 485244.58 | 07-DEC-21:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3150.78 | 15908.90 | 07-JAN-11:10 | 426436.66 | 01-JAN-23:40 |
WaterSystems:NaturalGas | 2671.90 | 15908.90 | 06-JAN-16:10 | 245489.84 | 26-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 2671.90 | 15908.90 | 06-JAN-16:10 | 245489.84 | 26-JAN-21:20 |
Heating:NaturalGas | 478.88 | 0.00 | 02-JAN-14:00 | 191614.88 | 02-JAN-04:10 |
Boiler:Heating:NaturalGas | 478.88 | 0.00 | 02-JAN-14:00 | 191614.88 | 02-JAN-04:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5452.72 | 0.00 | 01-JAN-00:10 | 611601.69 | 10-SEP-22:00 |
PlantLoopCoolingDemand:HVAC | 5452.72 | 0.00 | 01-JAN-00:10 | 611601.69 | 10-SEP-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5452.72 | 0.00 | 01-JAN-00:10 | 611601.69 | 10-SEP-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 26512.46 | 126600.17 | 06-MAR-11:30 | 2340338.03 | 13-JUL-18:20 |
EnergyTransfer:Building | 6036.98 | 92519.97 | 12-FEB-15:00 | 388392.93 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 747.30 | 10868.64 | 07-DEC-04:00 | 36613.66 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 181.86 | 4016.00 | 23-APR-22:20 | 10359.20 | 01-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.93 | 2008.00 | 23-APR-22:20 | 5179.60 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 90.93 | 2008.00 | 23-APR-22:20 | 5179.60 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.93 | 2008.00 | 23-APR-22:20 | 5179.60 | 01-SEP-06:20 |
EnergyTransfer:Plant | 13934.60 | 18201.22 | 23-NOV-02:00 | 1414862.19 | 10-SEP-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.56 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.37 | 1842.34 | 16-DEC-03:30 | 2559.02 | 13-NOV-14:10 |
EnergyTransfer:Zone:BASEMENT | 455.22 | 9929.41 | 27-MAR-14:00 | 26064.84 | 08-SEP-21:00 |
Heating:EnergyTransfer | 14.03 | 0.00 | 01-JAN-08:10 | 24832.75 | 07-DEC-05:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 14.03 | 0.00 | 01-JAN-08:10 | 24832.75 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5932.02 | 88119.47 | 01-JAN-06:00 | 384849.76 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 455.22 | 9929.41 | 27-MAR-14:00 | 26064.84 | 08-SEP-21:00 |
General:Cooling:EnergyTransfer | 5932.02 | 88119.47 | 01-JAN-06:00 | 384849.76 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 455.22 | 9929.41 | 27-MAR-14:00 | 26064.84 | 08-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.91 | 0.96 | 27-MAR-07:00 | 3966.92 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 187.04 | 16-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 187.04 | 16-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.91 | 0.00 | 26-MAR-04:40 | 3966.92 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.91 | 0.00 | 26-MAR-04:40 | 3966.92 | 02-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.53 | 803.36 | 12-FEB-16:00 | 2579.43 | 28-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.53 | 803.36 | 12-FEB-16:00 | 2579.43 | 28-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.53 | 803.36 | 12-FEB-16:00 | 2579.43 | 28-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 34.32 | 334.96 | 07-DEC-05:00 | 2514.27 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.32 | 334.96 | 07-DEC-05:00 | 2514.27 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.32 | 334.96 | 07-DEC-05:00 | 2514.27 | 28-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 19.07 | 125.36 | 07-DEC-05:00 | 1292.25 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.07 | 125.36 | 07-DEC-05:00 | 1292.25 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.07 | 125.36 | 07-DEC-05:00 | 1292.25 | 28-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 617.86 | 10185.50 | 07-DEC-05:00 | 39944.02 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 617.86 | 10185.50 | 07-DEC-05:00 | 39944.02 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 617.86 | 10185.50 | 07-DEC-05:00 | 39944.02 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 261.55 | 3012.60 | 12-FEB-16:00 | 14236.60 | 01-NOV-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 261.55 | 3012.60 | 12-FEB-16:00 | 14236.60 | 01-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 261.55 | 3012.60 | 12-FEB-16:00 | 14236.60 | 01-NOV-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 865.26 | 16610.72 | 12-FEB-16:00 | 46920.63 | 28-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 865.26 | 16610.72 | 12-FEB-16:00 | 46920.63 | 28-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 865.26 | 16610.72 | 12-FEB-16:00 | 46920.63 | 28-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 90.79 | 0.00 | 01-JAN-08:10 | 9706.16 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.40 | 0.00 | 01-JAN-08:10 | 2415.54 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.40 | 0.00 | 01-JAN-08:10 | 2415.54 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.39 | 0.00 | 01-JAN-00:10 | 9706.16 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.39 | 0.00 | 01-JAN-00:10 | 9706.16 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 76.64 | 0.00 | 01-JAN-08:10 | 9738.76 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.81 | 0.00 | 01-JAN-08:10 | 3640.16 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.81 | 0.00 | 01-JAN-08:10 | 3640.16 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.83 | 0.00 | 01-JAN-00:10 | 9738.76 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.83 | 0.00 | 01-JAN-00:10 | 9738.76 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 495.73 | 0.00 | 01-JAN-00:10 | 48548.77 | 20-NOV-14:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 495.73 | 0.00 | 01-JAN-00:10 | 48548.77 | 20-NOV-14:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 495.73 | 0.00 | 01-JAN-00:10 | 48548.77 | 20-NOV-14:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 572.71 | 0.00 | 01-JAN-08:10 | 82893.52 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.41 | 0.00 | 01-JAN-08:10 | 15338.83 | 07-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.41 | 0.00 | 01-JAN-08:10 | 15338.83 | 07-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 570.30 | 0.00 | 01-JAN-00:10 | 82893.52 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 570.30 | 0.00 | 01-JAN-00:10 | 82893.52 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 93.94 | 0.00 | 01-JAN-08:10 | 8340.78 | 30-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.42 | 0.00 | 01-JAN-08:10 | 2427.97 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.42 | 0.00 | 01-JAN-08:10 | 2427.97 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.52 | 0.00 | 01-JAN-00:10 | 8340.78 | 30-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.52 | 0.00 | 01-JAN-00:10 | 8340.78 | 30-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 79.06 | 0.00 | 01-JAN-08:10 | 8909.72 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.76 | 0.00 | 01-JAN-08:10 | 3100.45 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.76 | 0.00 | 01-JAN-08:10 | 3100.45 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.30 | 0.00 | 01-JAN-00:10 | 8909.72 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.30 | 0.00 | 01-JAN-00:10 | 8909.72 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 233.16 | 2510.93 | 12-FEB-16:00 | 15512.59 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 233.16 | 2510.93 | 12-FEB-16:00 | 15512.59 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 233.16 | 2510.93 | 12-FEB-16:00 | 15512.59 | 28-JUN-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.24 | 0.00 | 01-JAN-08:10 | 2593.53 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.92 | 0.00 | 01-JAN-08:10 | 899.76 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.92 | 0.00 | 01-JAN-08:10 | 899.76 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.32 | 0.00 | 01-JAN-00:10 | 2593.53 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.32 | 0.00 | 01-JAN-00:10 | 2593.53 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.26 | 0.00 | 01-JAN-08:10 | 2601.71 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.55 | 0.00 | 01-JAN-08:10 | 1078.79 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.55 | 0.00 | 01-JAN-08:10 | 1078.79 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.71 | 0.00 | 01-JAN-00:10 | 2601.71 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.71 | 0.00 | 01-JAN-00:10 | 2601.71 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.99 | 0.00 | 01-JAN-08:10 | 17123.68 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.77 | 0.00 | 01-JAN-00:10 | 2351.83 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.77 | 0.00 | 01-JAN-00:10 | 2351.83 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.22 | 0.00 | 01-JAN-01:50 | 17123.68 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.22 | 0.00 | 01-JAN-01:50 | 17123.68 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 478.25 | 8942.21 | 07-DEC-10:20 | 24926.81 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 478.25 | 8942.21 | 07-DEC-10:20 | 24926.81 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 478.25 | 8942.21 | 07-DEC-10:20 | 24926.81 | 28-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 514.90 | 9878.94 | 07-DEC-10:20 | 26104.52 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 514.90 | 9878.94 | 07-DEC-10:20 | 26104.52 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 514.90 | 9878.94 | 07-DEC-10:20 | 26104.52 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.36 | 8761.74 | 07-DEC-04:00 | 31527.93 | 13-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.36 | 8761.74 | 07-DEC-04:00 | 31527.93 | 13-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.32 | 8.51 | 06-DEC-07:10 | 8109.89 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 97.46 | 07-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 97.46 | 07-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.32 | 0.00 | 06-DEC-07:10 | 8109.89 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.32 | 0.00 | 06-DEC-07:10 | 8109.89 | 28-JUN-18:20 |
PlantLoopHeatingDemand:Facility | 891.21 | 6298.87 | 26-JUL-00:20 | 165712.85 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 584.55 | 6298.87 | 26-JUL-00:20 | 46103.65 | 24-JAN-07:40 |
WaterSystems:PlantLoopHeatingDemand | 584.55 | 6298.87 | 26-JUL-00:20 | 46103.65 | 24-JAN-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 584.55 | 6298.87 | 26-JUL-00:20 | 46103.65 | 24-JAN-07:40 |
EnergyTransfer:HVAC | 6540.88 | 367.90 | 11-FEB-08:20 | 709349.63 | 13-JUL-18:10 |
HeatingCoils:EnergyTransfer | 306.67 | 0.00 | 02-JAN-14:00 | 130031.63 | 02-JAN-04:10 |
PlantLoopHeatingDemand:HVAC | 306.67 | 0.00 | 02-JAN-14:00 | 130031.63 | 02-JAN-04:10 |
HeatingCoils:PlantLoopHeatingDemand | 306.67 | 0.00 | 02-JAN-14:00 | 130031.63 | 02-JAN-04:10 |
CoolingCoils:EnergyTransfer | 5452.72 | 0.00 | 01-JAN-00:10 | 611601.69 | 10-SEP-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 279.17 | 0.00 | 01-JAN-11:10 | 311666.60 | 07-DEC-06:10 |
HeatRecoveryForCooling:EnergyTransfer | 502.33 | 0.00 | 01-JAN-00:10 | 170977.05 | 17-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 584.55 | 6298.87 | 26-JUL-00:20 | 46103.65 | 24-JAN-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 584.55 | 6298.87 | 26-JUL-00:20 | 46103.65 | 24-JAN-07:40 |
Boilers:EnergyTransfer | 304.45 | 0.00 | 02-JAN-14:00 | 126072.63 | 07-DEC-09:10 |
Chillers:EnergyTransfer | 5529.12 | 0.00 | 01-JAN-00:10 | 617191.97 | 10-SEP-22:00 |
HeatRejection:EnergyTransfer | 7425.55 | 0.00 | 01-JAN-00:10 | 770581.76 | 10-SEP-22:00 |
General:HeatRejection:EnergyTransfer | 7425.55 | 0.00 | 01-JAN-00:10 | 770581.76 | 10-SEP-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -455.221 | 0.000 | 0.000 | 137.412 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 13.409 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.001 | -54.906 | 0.000 | 0.000 | 14.531 | 7.307 | 10.186 | 26.259 | 0.000 | 0.907 | 4.660 | 0.000 | -7.496 | 0.000 | -1.448 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -41.530 | 0.000 | 0.000 | 16.127 | 8.462 | 11.795 | 0.000 | 0.000 | 0.353 | 5.420 | 0.000 | 0.000 | 0.000 | -0.627 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -34.325 | 0.000 | 0.000 | 3.545 | 8.366 | 12.471 | 0.000 | 0.000 | 0.850 | 10.406 | 0.000 | 0.000 | 0.000 | -1.314 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -19.066 | 0.000 | 0.000 | 2.749 | 3.079 | 3.598 | 0.000 | 0.000 | 0.495 | 9.884 | 0.000 | 0.000 | 0.000 | -0.740 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -617.865 | 0.000 | 0.000 | 11.004 | 3.975 | 658.131 | 0.000 | 0.000 | 1.191 | 0.000 | 0.000 | 0.000 | 0.000 | -2.028 | -54.409 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -261.551 | 0.000 | 0.000 | 181.504 | 14.206 | 14.341 | 72.927 | 0.000 | 1.999 | 3.450 | 0.000 | -23.188 | 0.000 | -3.688 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -865.264 | 0.000 | 0.000 | 536.776 | 110.180 | 148.998 | 97.558 | 0.000 | 5.753 | 7.072 | 0.000 | -30.433 | 0.000 | -10.639 | -0.001 |
ROOM_1_FLR_3 | 2.658 | -78.713 | 0.000 | -11.930 | 0.000 | 0.000 | 9.626 | 9.244 | 10.478 | 57.750 | 0.000 | 2.827 | 16.863 | 0.000 | -15.199 | 0.000 | -3.603 | -0.002 |
ROOM_2_FLR_3 | 4.668 | -63.454 | 0.000 | -12.232 | 0.000 | 0.000 | 9.558 | 9.243 | 10.477 | 44.890 | 0.000 | 2.738 | 13.784 | 0.000 | -15.811 | 0.000 | -3.862 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -479.469 | 0.000 | -16.257 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 289.416 | 0.000 | 6.862 | 53.453 | 0.000 | -130.844 | 0.000 | -28.542 | -0.006 |
ROOM_4_MULT19_FLR_3 | 8.895 | -413.998 | 0.000 | -162.779 | 0.000 | 0.000 | 182.642 | 110.415 | 195.050 | 141.050 | 0.000 | 15.262 | 35.849 | 0.000 | -83.288 | 0.000 | -29.098 | -0.011 |
ROOM_5_FLR_3 | 2.667 | -81.841 | 0.000 | -11.926 | 0.000 | 0.000 | 9.624 | 9.244 | 10.478 | 59.501 | 0.000 | 2.827 | 17.535 | 0.000 | -14.469 | 0.000 | -3.640 | -0.000 |
ROOM_6_FLR_3 | 4.467 | -65.742 | 0.000 | -12.266 | 0.000 | 0.000 | 9.555 | 9.243 | 10.477 | 45.884 | 0.000 | 2.726 | 13.976 | 0.000 | -14.450 | 0.000 | -3.870 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -233.161 | 0.000 | 0.000 | 112.311 | 91.336 | 0.000 | 51.608 | 0.000 | 2.612 | 0.001 | 0.000 | -20.407 | 0.000 | -4.059 | -0.240 |
ROOM_1_FLR_6 | 1.383 | -19.800 | 0.000 | -2.987 | 0.000 | 0.000 | 2.407 | 2.311 | 2.620 | 14.359 | 0.000 | 0.702 | 3.661 | 0.000 | -3.732 | 0.000 | -0.923 | -0.000 |
ROOM_2_FLR_6 | 2.138 | -16.249 | 0.000 | -3.052 | 0.000 | 0.000 | 2.393 | 2.311 | 2.619 | 11.183 | 0.000 | 0.679 | 2.820 | 0.000 | -3.864 | 0.000 | -0.978 | -0.000 |
ROOM_3_MULT9_FLR_6 | 1.792 | -119.219 | 0.000 | -19.023 | 0.000 | 0.000 | 21.676 | 13.076 | 23.098 | 72.861 | 0.000 | 3.366 | 24.719 | 0.000 | -17.248 | 0.000 | -5.100 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -478.250 | 0.000 | 0.000 | 314.697 | 31.213 | 175.857 | 13.207 | 0.000 | 1.241 | 0.000 | 0.000 | -12.988 | 0.000 | -2.482 | -42.494 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -514.909 | 0.000 | 0.000 | 314.281 | 31.213 | 175.857 | 12.910 | 0.000 | 1.239 | 0.000 | 0.000 | -13.384 | 0.000 | -2.501 | -4.705 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -656.347 | 0.000 | 0.000 | 28.076 | 12.972 | 550.372 | 26.184 | 0.000 | 1.109 | 49.896 | 0.000 | -10.029 | 0.000 | -2.232 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -123.317 | 0.000 | 0.000 | 29.830 | 24.166 | 0.000 | 24.402 | 0.000 | 1.114 | 54.765 | 0.000 | -9.185 | 0.000 | -1.775 | -0.001 |
Total Facility | 28.667 | -1338.483 | 0.001 | -4608.164 | 0.000 | 0.000 | 1950.325 | 783.243 | 2365.005 | 1061.947 | 0.000 | 56.851 | 341.623 | 0.000 | -426.015 | 0.000 | -113.149 | -101.876 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-SEP-21:00 | 0.00 | 0.00 | 0.00 | -26065.39 | 0.00 | 0.00 | 5924.43 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -709.26 |
RETAIL_1_FLR_1 | 02-OCT-12:40 | 0.00 | 0.00 | 0.00 | -3967.02 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4203.41 | 0.00 | 103.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -908.61 |
RETAIL_2_FLR_1 | 28-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2579.17 | 0.00 | 0.00 | 697.62 | 615.12 | 752.15 | 0.00 | 0.00 | 43.44 | 470.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2513.89 | 0.00 | 0.00 | 129.09 | 684.18 | 839.45 | 0.00 | 0.00 | 120.54 | 740.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -1292.08 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 82.35 | 616.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39937.70 | 0.00 | 0.00 | 408.91 | 325.08 | 44299.38 | 0.00 | 0.00 | 164.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5260.28 |
CAFE_FLR_1 | 01-NOV-15:03 | 0.00 | 0.00 | 0.00 | -14251.88 | 0.00 | 0.00 | 4947.94 | 103.98 | 355.63 | 10365.64 | 0.00 | 111.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1633.13 |
LOBBY_FLR_1 | 28-JUN-21:10 | 0.00 | 0.00 | 0.00 | -46918.53 | 0.00 | 0.00 | 26440.47 | 6336.53 | 7389.94 | 1311.37 | 0.00 | 690.13 | 4750.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-JUN-18:02 | 0.00 | -9201.80 | 0.00 | -711.58 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 7642.41 | 0.00 | 388.69 | 428.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-08:61 | 0.00 | -10023.02 | 0.00 | -848.99 | 0.00 | 0.00 | 108.70 | 398.41 | 653.15 | 1141.42 | 0.00 | 54.75 | 8515.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-14:30 | 0.00 | -48548.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 54714.72 | 0.00 | 37.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10935.08 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -120803.87 | 0.00 | -10577.96 | 0.00 | 0.00 | 2233.21 | 4759.18 | 12159.85 | 8739.41 | 0.00 | 419.13 | 103071.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 13-AUG-08:61 | 0.00 | -8076.60 | 0.00 | -709.73 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 7623.91 | 0.00 | 194.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -214.83 |
ROOM_6_FLR_3 | 21-MAY-08:61 | 0.00 | -9737.35 | 0.00 | -980.87 | 0.00 | 0.00 | 88.36 | 398.41 | 653.15 | 7261.10 | 0.00 | 0.00 | 2361.96 | 0.00 | -0.00 | 0.00 | -44.77 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -15510.80 | 0.00 | 0.00 | 4080.40 | 7469.27 | 0.00 | 3185.52 | 0.00 | 438.02 | 337.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 27-JUN-18:02 | 0.00 | -2452.91 | 0.00 | -178.65 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 1896.10 | 0.00 | 96.59 | 275.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 01-JUL-08:61 | 0.00 | -2610.11 | 0.00 | -208.14 | 0.00 | 0.00 | 27.67 | 99.60 | 163.29 | 292.71 | 0.00 | 14.79 | 2220.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:01 | 0.00 | -20728.15 | 0.00 | -1083.67 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 8215.08 | 0.00 | 202.30 | 12141.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24926.81 | 0.00 | 0.00 | 15621.87 | 1992.02 | 6747.90 | 532.57 | 0.00 | 148.71 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -116.26 |
DINING_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -26104.60 | 0.00 | 0.00 | 15618.01 | 1992.02 | 6747.90 | 517.41 | 0.00 | 148.69 | 1080.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 13-AUG-10:40 | 0.00 | 0.00 | 0.00 | -31544.12 | 0.00 | 0.00 | 464.22 | 353.60 | 24259.91 | 3207.45 | 0.00 | 124.54 | 3134.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 28-JUN-18:13 | 0.00 | 0.00 | 0.00 | -8109.82 | 0.00 | 0.00 | 1079.60 | 1756.68 | 0.00 | 1822.94 | 0.00 | 206.96 | 3243.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUN-18:02 | 0.00 | -202240.35 | 0.00 | -224123.66 | 0.00 | 0.00 | 74062.37 | 53184.46 | 120482.43 | 86139.33 | 0.00 | 9284.30 | 83211.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-DEC-07:20 | 0.00 | 0.00 | 187.01 | 0.00 | 0.00 | 0.00 | 447.52 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 214.05 | 0.00 | -1112.06 | 0.00 | -224.40 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-MAR-08:62 | 4894.57 | 374.96 | 0.00 | -374.96 | 0.00 | 0.00 | 152.11 | 398.46 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -715.37 | 0.00 | -347.18 | -5035.80 |
ROOM_2_FLR_3 | 08-DEC-09:02 | 5068.40 | 302.18 | 0.00 | -302.18 | 0.00 | 0.00 | 106.46 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -538.72 | 0.00 | -245.27 | -5156.91 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-MAR-16:04 | 31163.21 | 5282.01 | 0.00 | -5282.01 | 0.00 | 0.00 | 2551.45 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -193.78 | 0.00 | -17003.62 | -23440.44 |
ROOM_5_FLR_3 | 12-FEB-16:02 | 4689.07 | 369.33 | 0.00 | -369.33 | 0.00 | 0.00 | 153.71 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -349.40 | 0.00 | -176.07 | -4773.38 |
ROOM_6_FLR_3 | 07-DEC-16:01 | 4874.15 | 365.75 | 0.00 | -365.75 | 0.00 | 0.00 | 275.46 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -707.53 | 0.00 | -563.41 | -4278.03 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 26-MAR-08:62 | 1478.23 | 81.95 | 0.00 | -81.95 | 0.00 | 0.00 | 39.39 | 99.61 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -160.27 | 0.00 | -82.70 | -1537.57 |
ROOM_2_FLR_6 | 01-JAN-09:02 | 1522.94 | 67.85 | 0.00 | -67.85 | 0.00 | 0.00 | 40.79 | 99.60 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -313.46 | 0.00 | -90.07 | -1423.09 |
ROOM_3_MULT9_FLR_6 | 07-FEB-16:04 | 7495.98 | 647.14 | 0.00 | -647.14 | 0.00 | 0.00 | 530.13 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -464.99 | 0.00 | -1652.61 | -6631.58 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-DEC-07:10 | 0.00 | 0.00 | 97.82 | 0.00 | 0.00 | 0.00 | 733.29 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1525.63 | 0.00 | -281.70 | -121.70 |
Total Facility | 16-DEC-09:03 | -85138.56 | 124211.93 | 0.00 | -124211.93 | 0.00 | 0.00 | 32858.36 | 29463.28 | 96972.77 | 73146.60 | 0.00 | 0.00 | 0.00 | 0.00 | -10807.06 | 0.00 | -10597.57 | -125897.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.6377 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.5112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.3188 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6536 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8875 | 2.8875 | 1.3658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3744 | 0.3744 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2668 | 0.2668 | 0.1262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2448 | 0.2448 | 0.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1442 | 0.1442 | 0.0682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6221 | 3.6221 | 1.7133 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5724 | 1.5724 | 0.7437 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3432 | 5.3432 | 2.5273 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7636 | 1.7636 | 0.8342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4600 | 2.4600 | 1.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5739 | 2.5739 | 1.2174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4937 | 2.4937 | 1.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8912 | 0.8912 | 0.4215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.6377 | 24.5112 | 24.6377 | 11.6536 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4437 | 1.4437 | 1.3658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1872 | 0.1872 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1334 | 0.1334 | 0.1262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1224 | 0.1224 | 0.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0721 | 0.0721 | 0.0682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8111 | 1.8111 | 1.7133 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7862 | 0.7862 | 0.7437 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6716 | 2.6716 | 2.5273 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8818 | 0.8818 | 0.8342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2300 | 1.2300 | 1.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2869 | 1.2869 | 1.2174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2469 | 1.2469 | 1.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4456 | 0.4456 | 0.4215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.3188 | 11.6536 | 11.6536 | 11.6536 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 600.17 |
Number of hours not met | 600.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 478.88 | 191614.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1896.43 | 203708.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.24 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.06 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 610.12 | 50214.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 93.93 | 4495.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 149.55 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.72 | 2671.90 | 245489.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.47 | 1893.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.16 | 1203.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.90 | 6178.78 |
Natural Gas | 1788.84 | 4939.62 |
Additional | 0.00 | 0.00 |
Total | 3508.74 | 11118.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.04 |
Space Heating | 0.00 |
Space Cooling | 167.16 |
Fans (All) | 53.78 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 544.61 |
Subtotal | 544.61 |
Natural Gas [MJ/m2] | |
Space Heating | 42.21 |
Service Water Heating | 235.51 |
Miscellaneous (All) | 435.39 |
Subtotal | 435.39 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.04 |
Space Heating | 4.31 |
Space Cooling | 17.06 |
Fans (All) | 5.49 |
Service Water Heating | 24.85 |
Receptacle Equipment | 31.00 |
Miscellaneous | 10.25 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8153.17 | 606.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8153.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 606.83 | 0.00 | 0.00 | 0.00 |
Average | 8732.23 | 27.77 | 0.00 | 0.00 | 0.00 |
Sum | 192109.17 | 610.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8171.67 | 588.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8293.00 | 467.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7917.67 | 842.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8252.50 | 507.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8294.00 | 466.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7917.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 842.33 | 0.00 | 0.00 | 0.00 |
Average | 8623.92 | 136.08 | 0.00 | 0.00 | 0.00 |
Sum | 189726.17 | 2993.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58963.67 | 192.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 640994.17 | 69422.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1951148.50 | 164280.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4152.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100277.67 | 80.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1139785.00 | 105930.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1147385.17 | 98329.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108082.67 | 186.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1951148.50 | 164280.50 | 0.00 | 0.00 | 0.00 |
Average | 268958.12 | 19928.92 | 0.00 | 0.00 | 0.00 |
Sum | 5917078.67 | 438436.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364858E+11 | 19776.74 | 27-JAN-22:00 | 12.00 | 4.58 | 0.814793E+10 | 4837.08 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.288897E+11 | 17935.66 | 01-FEB-22:00 | 10.00 | 5.32 | 0.700802E+10 | 4837.94 | 01-FEB-01:10 | 10.00 | 5.32 |
March | 0.298776E+11 | 14538.12 | 29-MAR-04:15 | 4.00 | 0.43 | 0.738234E+10 | 4726.25 | 01-MAR-22:10 | 4.00 | 0.43 |
April | 0.311766E+11 | 14942.96 | 30-APR-10:33 | 30.00 | 11.09 | 0.735734E+10 | 4746.74 | 21-APR-22:10 | 30.00 | 11.09 |
May | 0.313761E+11 | 14530.10 | 07-MAY-10:33 | 30.00 | 12.89 | 0.739323E+10 | 4666.43 | 01-MAY-22:10 | 30.00 | 12.89 |
June | 0.323960E+11 | 15570.30 | 28-JUN-18:10 | 40.83 | 17.83 | 0.737079E+10 | 4721.34 | 23-JUN-21:19 | 40.83 | 17.83 |
July | 0.394135E+11 | 21249.56 | 14-JUL-21:00 | 28.00 | 20.32 | 0.814704E+10 | 4837.16 | 07-JUL-22:10 | 28.00 | 20.32 |
August | 0.431293E+11 | 23264.16 | 04-AUG-21:00 | 23.00 | 18.90 | 0.823843E+10 | 4837.09 | 21-AUG-00:20 | 26.00 | 16.49 |
September | 0.468283E+11 | 26064.84 | 08-SEP-21:00 | 32.20 | 19.39 | 0.797557E+10 | 4837.16 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.473096E+11 | 25696.81 | 05-OCT-21:00 | 24.00 | 13.11 | 0.823532E+10 | 4837.31 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.447658E+11 | 25341.93 | 01-NOV-21:00 | 18.00 | 13.11 | 0.796309E+10 | 4837.24 | 01-NOV-01:39 | 18.00 | 13.11 |
December | 0.435700E+11 | 24513.51 | 01-DEC-22:00 | 10.00 | 4.18 | 0.822983E+10 | 4837.39 | 12-DEC-22:10 | 12.83 | 9.59 |
Annual Sum or Average | 0.455218E+12 | 0.934489E+11 | ||||||||
Minimum of Months | 0.288897E+11 | 14530.10 | 4.00 | 0.43 | 0.700802E+10 | 4666.43 | 4.00 | 0.43 | ||
Maximum of Months | 0.473096E+11 | 26064.84 | 40.83 | 20.32 | 0.823843E+10 | 4837.94 | 40.83 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442325E+10 | 3647.53 | 14-JAN-13:40 | 26.67 | 10.98 | 0.719145E+09 | 471.46 | 19-JAN-22:19 | 14.33 | 6.76 |
February | 0.279667E+10 | 2664.63 | 01-FEB-14:00 | 16.00 | 7.74 | 0.601163E+09 | 440.69 | 01-FEB-00:10 | 16.00 | 7.74 |
March | 0.334407E+10 | 2777.21 | 18-MAR-13:40 | 26.27 | 12.12 | 0.687991E+09 | 485.29 | 16-MAR-21:30 | 26.27 | 12.12 |
April | 0.459110E+10 | 3126.82 | 14-APR-14:10 | 34.17 | 14.15 | 0.756510E+09 | 491.84 | 12-APR-23:10 | 34.17 | 14.15 |
May | 0.475231E+10 | 2631.71 | 31-MAY-18:13 | 35.33 | 13.34 | 0.796523E+09 | 491.86 | 10-MAY-23:10 | 35.33 | 13.34 |
June | 0.555885E+10 | 3463.89 | 28-JUN-18:17 | 40.67 | 17.68 | 0.801294E+09 | 491.86 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.553023E+10 | 3207.61 | 21-JUL-18:30 | 38.00 | 19.28 | 0.823766E+09 | 491.85 | 01-JUL-00:10 | 38.00 | 19.28 |
August | 0.570444E+10 | 3653.69 | 28-AUG-12:30 | 37.00 | 20.85 | 0.823717E+09 | 491.84 | 17-AUG-21:30 | 37.00 | 20.85 |
September | 0.547452E+10 | 3940.11 | 28-SEP-13:30 | 36.10 | 16.03 | 0.790591E+09 | 491.84 | 07-SEP-21:19 | 36.10 | 16.03 |
October | 0.498428E+10 | 3966.92 | 02-OCT-12:40 | 34.00 | 19.29 | 0.766688E+09 | 491.86 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.413931E+10 | 3833.08 | 21-NOV-13:30 | 25.00 | 10.74 | 0.693329E+09 | 491.84 | 01-NOV-22:10 | 25.00 | 10.74 |
December | 0.360636E+10 | 3527.90 | 25-DEC-13:00 | 25.00 | 11.61 | 0.682774E+09 | 467.02 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.549054E+11 | 0.894349E+10 | ||||||||
Minimum of Months | 0.279667E+10 | 2631.71 | 16.00 | 7.74 | 0.601163E+09 | 440.69 | 14.33 | 6.76 | ||
Maximum of Months | 0.570444E+10 | 3966.92 | 40.67 | 20.85 | 0.823766E+09 | 491.86 | 40.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305514E+10 | 1727.91 | 27-JAN-21:10 | 16.17 | 6.63 | 0.921105E+09 | 569.55 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.251559E+10 | 1488.78 | 01-FEB-22:00 | 10.00 | 5.32 | 0.795902E+09 | 569.55 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.292042E+10 | 1779.54 | 17-MAR-21:00 | 21.60 | 12.64 | 0.904833E+09 | 569.55 | 22-MAR-21:19 | 12.90 | 6.94 |
April | 0.352117E+10 | 2295.56 | 14-APR-21:00 | 29.00 | 13.30 | 0.926904E+09 | 569.56 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.382151E+10 | 2245.29 | 31-MAY-21:00 | 29.00 | 11.22 | 0.963546E+09 | 569.56 | 10-MAY-23:19 | 29.00 | 11.22 |
June | 0.420327E+10 | 2579.43 | 28-JUN-21:00 | 35.00 | 14.57 | 0.939503E+09 | 569.56 | 09-JUN-23:19 | 35.00 | 14.57 |
July | 0.416942E+10 | 2442.14 | 20-JUL-20:10 | 35.17 | 18.52 | 0.966010E+09 | 569.55 | 01-JUL-00:10 | 35.17 | 18.52 |
August | 0.415311E+10 | 2481.87 | 15-AUG-20:10 | 34.67 | 18.05 | 0.969744E+09 | 569.55 | 04-AUG-22:10 | 34.67 | 18.05 |
September | 0.385303E+10 | 2441.67 | 07-SEP-21:00 | 33.30 | 19.43 | 0.935426E+09 | 569.55 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.348244E+10 | 2271.61 | 05-OCT-20:10 | 26.50 | 13.28 | 0.947847E+09 | 569.57 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.299030E+10 | 1984.25 | 01-NOV-20:10 | 20.50 | 13.68 | 0.894469E+09 | 569.55 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.284384E+10 | 1636.32 | 26-DEC-22:00 | 15.00 | 7.29 | 0.891234E+09 | 569.52 | 01-DEC-22:19 | 15.00 | 7.29 |
Annual Sum or Average | 0.415292E+11 | 0.110565E+11 | ||||||||
Minimum of Months | 0.251559E+10 | 1488.78 | 10.00 | 5.32 | 0.795902E+09 | 569.52 | 11.67 | 4.41 | ||
Maximum of Months | 0.420327E+10 | 2579.43 | 35.17 | 19.43 | 0.969744E+09 | 569.57 | 35.17 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227086E+10 | 1094.58 | 08-JAN-11:33 | 20.33 | 13.54 | 0.170282E+09 | 109.30 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.193639E+10 | 1096.94 | 01-FEB-07:03 | 5.00 | 3.59 | 0.148054E+09 | 105.45 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.228389E+10 | 1149.63 | 18-MAR-18:10 | 25.13 | 12.09 | 0.170865E+09 | 113.58 | 17-MAR-21:19 | 25.13 | 12.09 |
April | 0.273209E+10 | 1598.33 | 25-APR-21:00 | 27.00 | 14.17 | 0.186649E+09 | 120.46 | 11-APR-22:10 | 27.00 | 14.17 |
May | 0.314240E+10 | 1846.86 | 18-MAY-20:00 | 30.00 | 12.86 | 0.201239E+09 | 120.46 | 10-MAY-23:30 | 30.00 | 12.86 |
June | 0.391931E+10 | 2514.27 | 28-JUN-20:00 | 37.00 | 15.57 | 0.199085E+09 | 120.46 | 09-JUN-23:40 | 37.00 | 15.57 |
July | 0.390475E+10 | 2401.71 | 21-JUL-20:00 | 37.00 | 20.84 | 0.204712E+09 | 120.46 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.368924E+10 | 2279.84 | 15-AUG-20:00 | 35.00 | 18.06 | 0.205025E+09 | 120.46 | 30-AUG-21:19 | 31.67 | 17.46 |
September | 0.330068E+10 | 2161.56 | 08-SEP-20:00 | 33.80 | 19.77 | 0.197162E+09 | 120.46 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.277854E+10 | 1978.81 | 02-OCT-20:00 | 27.00 | 20.01 | 0.189128E+09 | 120.46 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.229255E+10 | 1183.22 | 02-NOV-18:04 | 23.67 | 15.30 | 0.168450E+09 | 115.33 | 02-NOV-21:10 | 20.00 | 15.60 |
December | 0.207399E+10 | 1094.29 | 30-DEC-06:08 | 4.00 | 0.61 | 0.162701E+09 | 106.70 | 26-DEC-22:10 | 4.00 | 0.61 |
Annual Sum or Average | 0.343247E+11 | 0.220335E+10 | ||||||||
Minimum of Months | 0.193639E+10 | 1094.29 | 4.00 | 0.61 | 0.148054E+09 | 105.45 | 4.00 | 0.61 | ||
Maximum of Months | 0.391931E+10 | 2514.27 | 37.00 | 20.84 | 0.205025E+09 | 120.46 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130234E+10 | 638.13 | 08-JAN-11:33 | 20.33 | 13.54 | 0.128677E+09 | 81.05 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.110713E+10 | 625.29 | 01-FEB-07:03 | 5.00 | 3.59 | 0.111629E+09 | 79.39 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.130545E+10 | 668.55 | 18-MAR-10:33 | 23.83 | 14.74 | 0.128787E+09 | 84.51 | 17-MAR-21:40 | 23.83 | 14.74 |
April | 0.156111E+10 | 787.60 | 15-APR-10:33 | 28.00 | 13.04 | 0.140642E+09 | 92.66 | 14-APR-21:40 | 28.00 | 13.04 |
May | 0.174205E+10 | 832.41 | 09-MAY-20:00 | 31.00 | 13.10 | 0.152493E+09 | 92.66 | 10-MAY-23:10 | 25.83 | 15.07 |
June | 0.210541E+10 | 1292.25 | 28-JUN-19:10 | 39.50 | 16.83 | 0.152920E+09 | 92.66 | 09-JUN-23:49 | 39.50 | 16.83 |
July | 0.209831E+10 | 1201.95 | 21-JUL-20:00 | 37.00 | 20.84 | 0.157194E+09 | 92.66 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.198943E+10 | 1121.19 | 15-AUG-20:00 | 35.00 | 18.06 | 0.157083E+09 | 92.66 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.179522E+10 | 1052.56 | 08-SEP-20:00 | 33.80 | 19.77 | 0.150518E+09 | 92.66 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.157216E+10 | 917.68 | 03-OCT-21:00 | 30.00 | 18.69 | 0.142798E+09 | 92.66 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.131634E+10 | 678.16 | 02-NOV-18:04 | 23.67 | 15.30 | 0.126981E+09 | 85.78 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.117074E+10 | 632.38 | 30-DEC-06:08 | 4.00 | 0.61 | 0.123048E+09 | 79.48 | 26-DEC-22:40 | 4.00 | 0.61 |
Annual Sum or Average | 0.190657E+11 | 0.167277E+10 | ||||||||
Minimum of Months | 0.110713E+10 | 625.29 | 4.00 | 0.61 | 0.111629E+09 | 79.39 | 4.00 | 0.61 | ||
Maximum of Months | 0.210541E+10 | 1292.25 | 39.50 | 20.84 | 0.157194E+09 | 92.66 | 39.50 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505283E+11 | 37931.12 | 27-JAN-21:00 | 17.00 | 6.99 | 0.606188E+09 | 381.76 | 10-JAN-22:10 | 17.00 | 6.99 |
February | 0.450556E+11 | 37578.70 | 22-FEB-21:00 | 13.00 | 10.72 | 0.545653E+09 | 381.73 | 28-FEB-22:10 | 12.55 | 9.16 |
March | 0.507458E+11 | 38284.55 | 16-MAR-20:00 | 22.20 | 12.56 | 0.607681E+09 | 381.74 | 21-MAR-21:10 | 18.62 | 10.88 |
April | 0.513693E+11 | 39189.55 | 14-APR-20:00 | 31.00 | 13.66 | 0.594582E+09 | 381.77 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.539279E+11 | 39309.65 | 18-MAY-20:00 | 30.00 | 12.86 | 0.617034E+09 | 381.81 | 11-MAY-21:10 | 30.00 | 12.86 |
June | 0.535671E+11 | 39944.02 | 28-JUN-20:00 | 37.00 | 15.57 | 0.600506E+09 | 381.87 | 23-JUN-21:10 | 37.00 | 15.57 |
July | 0.547336E+11 | 39774.62 | 21-JUL-20:00 | 37.00 | 20.84 | 0.617392E+09 | 381.86 | 07-JUL-21:10 | 37.00 | 20.84 |
August | 0.547427E+11 | 39672.81 | 15-AUG-20:00 | 35.00 | 18.06 | 0.618038E+09 | 382.22 | 09-AUG-21:10 | 35.00 | 18.06 |
September | 0.521837E+11 | 39517.26 | 08-SEP-20:00 | 33.80 | 19.77 | 0.595642E+09 | 381.90 | 19-SEP-21:10 | 28.02 | 15.82 |
October | 0.522530E+11 | 39131.45 | 03-OCT-20:00 | 30.00 | 18.25 | 0.611775E+09 | 381.85 | 06-OCT-21:10 | 26.00 | 13.09 |
November | 0.491356E+11 | 38248.15 | 01-NOV-20:00 | 21.00 | 13.76 | 0.587119E+09 | 381.78 | 01-NOV-21:10 | 18.00 | 13.11 |
December | 0.496185E+11 | 37655.46 | 22-DEC-21:00 | 14.00 | 5.51 | 0.603370E+09 | 381.83 | 12-DEC-22:10 | 14.00 | 5.51 |
Annual Sum or Average | 0.617861E+12 | 0.720498E+10 | ||||||||
Minimum of Months | 0.450556E+11 | 37578.70 | 13.00 | 5.51 | 0.545653E+09 | 381.73 | 12.55 | 5.51 | ||
Maximum of Months | 0.547427E+11 | 39944.02 | 37.00 | 20.84 | 0.618038E+09 | 382.22 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217098E+11 | 13941.73 | 14-JAN-13:30 | 26.50 | 10.97 | 0.107595E+11 | 6462.53 | 24-JAN-22:10 | 12.83 | 6.74 |
February | 0.160903E+11 | 10617.40 | 25-FEB-14:25 | 17.50 | 9.25 | 0.934212E+10 | 6463.27 | 01-FEB-01:10 | 17.50 | 9.25 |
March | 0.182276E+11 | 10893.72 | 18-MAR-13:30 | 26.35 | 12.25 | 0.105089E+11 | 6462.62 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.215316E+11 | 12170.36 | 14-APR-21:10 | 28.67 | 13.19 | 0.105406E+11 | 6462.68 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.222066E+11 | 11730.15 | 09-MAY-21:10 | 28.83 | 12.76 | 0.109028E+11 | 6461.97 | 31-MAY-04:19 | 19.00 | 9.54 |
June | 0.241625E+11 | 13307.60 | 28-JUN-21:10 | 34.67 | 14.46 | 0.106343E+11 | 6462.30 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.246891E+11 | 13206.64 | 21-JUL-21:10 | 33.83 | 20.81 | 0.109503E+11 | 6462.07 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.252690E+11 | 13080.43 | 15-AUG-21:10 | 32.67 | 17.73 | 0.109949E+11 | 6462.63 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.244631E+11 | 13908.25 | 28-SEP-15:03 | 37.52 | 15.49 | 0.106158E+11 | 6462.57 | 21-SEP-22:10 | 37.52 | 15.49 |
October | 0.232623E+11 | 13856.97 | 05-OCT-15:03 | 34.00 | 15.75 | 0.108642E+11 | 6462.63 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.203795E+11 | 14250.92 | 01-NOV-15:03 | 28.83 | 16.12 | 0.103702E+11 | 6462.52 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.195566E+11 | 13473.53 | 25-DEC-13:00 | 25.00 | 11.61 | 0.104809E+11 | 6461.91 | 23-DEC-02:20 | 25.00 | 11.61 |
Annual Sum or Average | 0.261548E+12 | 0.126964E+12 | ||||||||
Minimum of Months | 0.160903E+11 | 10617.40 | 17.50 | 9.25 | 0.934212E+10 | 6461.91 | 12.00 | 6.59 | ||
Maximum of Months | 0.252690E+11 | 14250.92 | 37.52 | 20.81 | 0.109949E+11 | 6463.27 | 37.52 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664314E+11 | 35816.79 | 27-JAN-21:10 | 16.17 | 6.63 | 0.320842E+11 | 19185.93 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.546491E+11 | 32334.79 | 01-FEB-22:10 | 9.67 | 5.16 | 0.282026E+11 | 19189.59 | 01-FEB-01:10 | 9.67 | 5.16 |
March | 0.627353E+11 | 36439.21 | 17-MAR-21:10 | 21.42 | 12.50 | 0.316315E+11 | 19186.15 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.719583E+11 | 42341.34 | 14-APR-21:10 | 28.67 | 13.19 | 0.313339E+11 | 19186.15 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.771841E+11 | 41817.64 | 09-MAY-21:10 | 28.83 | 12.76 | 0.324305E+11 | 19185.63 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.827055E+11 | 46920.63 | 28-JUN-21:10 | 34.67 | 14.46 | 0.315982E+11 | 19186.03 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.843898E+11 | 46170.82 | 21-JUL-20:10 | 36.50 | 20.90 | 0.325190E+11 | 19185.41 | 07-JUL-04:19 | 36.50 | 20.90 |
August | 0.842531E+11 | 45721.23 | 15-AUG-21:10 | 32.67 | 17.73 | 0.326740E+11 | 19186.05 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.800928E+11 | 45696.66 | 07-SEP-21:10 | 32.75 | 19.42 | 0.315462E+11 | 19185.98 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.741882E+11 | 43781.47 | 03-OCT-21:10 | 29.50 | 18.57 | 0.323873E+11 | 19186.27 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.646438E+11 | 38808.25 | 01-NOV-20:10 | 20.50 | 13.68 | 0.310369E+11 | 19185.95 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.620253E+11 | 35035.56 | 26-DEC-22:10 | 14.83 | 7.20 | 0.315062E+11 | 19185.32 | 01-DEC-01:19 | 14.83 | 7.20 |
Annual Sum or Average | 0.865257E+12 | 0.378951E+12 | ||||||||
Minimum of Months | 0.546491E+11 | 32334.79 | 9.67 | 5.16 | 0.282026E+11 | 19185.32 | 9.67 | 4.41 | ||
Maximum of Months | 0.843898E+11 | 46920.63 | 36.50 | 20.90 | 0.326740E+11 | 19189.59 | 36.50 | 20.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987726E+09 | 2380.23 | 31-JAN-16:02 | 29.00 | 10.73 | 98373007.58 | 56.69 | 06-JAN-22:19 | 29.00 | 10.73 |
February | 0.377454E+09 | 2343.32 | 28-FEB-16:01 | 19.00 | 8.42 | 87767695.83 | 56.69 | 21-FEB-22:10 | 19.00 | 8.42 |
March | 0.802378E+09 | 2362.17 | 23-MAR-15:01 | 24.80 | 11.21 | 98116085.91 | 56.69 | 16-MAR-22:30 | 24.80 | 11.21 |
April | 0.221995E+10 | 2440.14 | 14-APR-18:01 | 33.50 | 13.96 | 96076813.11 | 56.70 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.262510E+10 | 2434.09 | 31-MAY-18:01 | 35.67 | 13.49 | 99445593.16 | 56.69 | 22-MAY-21:30 | 35.67 | 13.49 |
June | 0.329623E+10 | 2478.34 | 27-JUN-18:02 | 39.83 | 15.83 | 98283599.55 | 62.06 | 26-JUN-21:10 | 39.83 | 15.83 |
July | 0.305836E+10 | 2452.23 | 01-JUL-18:01 | 35.83 | 13.66 | 99749913.18 | 59.59 | 05-JUL-21:10 | 31.67 | 12.95 |
August | 0.299859E+10 | 2464.46 | 25-AUG-18:01 | 38.67 | 17.09 | 99843874.32 | 56.70 | 28-AUG-03:20 | 29.67 | 19.01 |
September | 0.263924E+10 | 2421.49 | 12-SEP-18:01 | 32.93 | 18.22 | 96273915.68 | 56.70 | 08-SEP-23:00 | 32.93 | 18.22 |
October | 0.182885E+10 | 2429.40 | 15-OCT-15:01 | 31.00 | 12.59 | 98987692.21 | 56.70 | 03-OCT-21:40 | 31.00 | 12.59 |
November | 0.990352E+09 | 2406.79 | 20-NOV-16:02 | 26.83 | 12.13 | 95188572.26 | 56.69 | 01-NOV-21:00 | 26.83 | 12.13 |
December | 0.522843E+09 | 2378.53 | 22-DEC-16:02 | 24.83 | 10.00 | 97654997.91 | 56.69 | 12-DEC-22:10 | 24.83 | 10.00 |
Annual Sum or Average | 0.223471E+11 | 0.116576E+10 | ||||||||
Minimum of Months | 0.377454E+09 | 2343.32 | 19.00 | 8.42 | 87767695.83 | 56.69 | 19.00 | 8.42 | ||
Maximum of Months | 0.329623E+10 | 2478.34 | 39.83 | 18.22 | 99843874.32 | 62.06 | 39.83 | 19.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339564E+09 | 2304.00 | 31-JAN-16:02 | 29.00 | 10.73 | 99336477.24 | 66.66 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.128547E+09 | 2276.10 | 28-FEB-16:01 | 19.00 | 8.42 | 87411170.03 | 58.14 | 09-FEB-22:30 | 19.00 | 8.42 |
March | 0.436026E+09 | 2320.67 | 23-MAR-15:01 | 24.80 | 11.21 | 0.100935E+09 | 73.09 | 17-MAR-21:10 | 24.80 | 11.21 |
April | 0.187406E+10 | 2424.15 | 26-APR-08:41 | 25.67 | 12.21 | 98755548.97 | 77.64 | 26-APR-21:40 | 16.33 | 9.48 |
May | 0.248345E+10 | 2585.16 | 08-MAY-08:61 | 27.17 | 12.22 | 0.101086E+09 | 57.18 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.326521E+10 | 2634.26 | 14-JUN-08:61 | 27.67 | 11.24 | 0.100092E+09 | 62.72 | 26-JUN-21:10 | 33.67 | 14.50 |
July | 0.302163E+10 | 2718.02 | 01-JUL-08:61 | 27.50 | 10.46 | 0.100441E+09 | 60.16 | 05-JUL-21:10 | 31.67 | 12.95 |
August | 0.280517E+10 | 2462.85 | 24-AUG-08:21 | 27.50 | 13.17 | 0.101203E+09 | 79.12 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.231383E+10 | 2399.51 | 06-SEP-18:01 | 33.07 | 19.98 | 97940285.12 | 76.38 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.123400E+10 | 2369.83 | 15-OCT-15:01 | 31.00 | 12.59 | 0.102028E+09 | 74.31 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.421473E+09 | 2330.22 | 20-NOV-16:02 | 26.83 | 12.13 | 96727876.49 | 72.15 | 01-NOV-21:40 | 26.83 | 12.13 |
December | 0.133941E+09 | 2288.66 | 25-DEC-16:02 | 25.67 | 11.87 | 96683271.18 | 58.19 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.184569E+11 | 0.118264E+10 | ||||||||
Minimum of Months | 0.128547E+09 | 2276.10 | 19.00 | 8.42 | 87411170.03 | 57.18 | 14.48 | 5.13 | ||
Maximum of Months | 0.326521E+10 | 2718.02 | 33.07 | 19.98 | 0.102028E+09 | 79.12 | 33.67 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578454E+09 | 615.61 | 14-JAN-13:40 | 26.67 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 26.67 | 10.98 |
February | 0.214938E+09 | 464.63 | 01-FEB-14:15 | 15.67 | 7.45 | 0.00 | 0.00 | 01-FEB-00:10 | 15.67 | 7.45 |
March | 0.250768E+09 | 427.45 | 18-MAR-14:10 | 26.28 | 11.98 | 0.00 | 0.00 | 01-MAR-00:10 | 26.28 | 11.98 |
April | 0.530970E+09 | 440.48 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.531988E+09 | 371.35 | 09-MAY-17:13 | 34.67 | 14.40 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 14.40 |
June | 0.683976E+09 | 465.22 | 28-JUN-19:10 | 39.50 | 16.83 | 0.00 | 0.00 | 01-JUN-00:10 | 39.50 | 16.83 |
July | 0.694246E+09 | 449.71 | 21-JUL-20:20 | 36.00 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 20.94 |
August | 0.734335E+09 | 501.79 | 27-AUG-14:00 | 40.00 | 18.27 | 0.00 | 0.00 | 01-AUG-00:10 | 40.00 | 18.27 |
September | 0.735330E+09 | 582.71 | 28-SEP-13:30 | 36.10 | 16.03 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 16.03 |
October | 0.649970E+09 | 607.15 | 18-OCT-13:30 | 30.50 | 12.03 | 0.00 | 0.00 | 01-OCT-00:10 | 30.50 | 12.03 |
November | 0.495066E+09 | 638.80 | 20-NOV-14:30 | 27.00 | 11.68 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 11.68 |
December | 0.422734E+09 | 610.09 | 25-DEC-13:30 | 25.50 | 11.81 | 0.00 | 0.00 | 01-DEC-00:10 | 25.50 | 11.81 |
Annual Sum or Average | 0.652277E+10 | 0.00 | ||||||||
Minimum of Months | 0.214938E+09 | 371.35 | 15.67 | 7.45 | 0.00 | 0.00 | 15.67 | 7.45 | ||
Maximum of Months | 0.735330E+09 | 638.80 | 40.00 | 20.94 | 0.00 | 0.00 | 40.00 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251950E+09 | 1522.26 | 31-JAN-19:01 | 23.00 | 8.93 | 97958075.84 | 68.32 | 27-JAN-22:10 | 23.00 | 8.93 |
February | 0.209818E+09 | 1409.40 | 27-FEB-19:01 | 13.67 | 7.91 | 87429066.75 | 63.09 | 09-FEB-22:49 | 13.67 | 7.91 |
March | 0.333468E+09 | 1556.10 | 15-MAR-18:01 | 26.55 | 12.82 | 99741440.26 | 72.05 | 23-MAR-21:10 | 14.80 | 7.70 |
April | 0.675502E+09 | 1565.33 | 30-APR-08:51 | 25.00 | 9.17 | 97188718.76 | 72.63 | 26-APR-21:49 | 25.00 | 9.17 |
May | 0.884290E+09 | 1679.80 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100184E+09 | 56.69 | 24-MAY-21:10 | 25.83 | 11.29 |
June | 0.113721E+10 | 1725.12 | 11-JUN-08:61 | 26.33 | 12.62 | 97042612.47 | 56.69 | 05-JUN-21:00 | 26.33 | 12.62 |
July | 0.111558E+10 | 1728.72 | 01-JUL-08:61 | 27.50 | 10.46 | 99491854.53 | 56.69 | 24-JUL-21:30 | 31.00 | 18.54 |
August | 0.102050E+10 | 1575.61 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100210E+09 | 76.96 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.888877E+09 | 1561.80 | 29-SEP-08:21 | 27.75 | 14.34 | 97225511.46 | 74.93 | 21-SEP-21:10 | 27.75 | 14.34 |
October | 0.544929E+09 | 1555.64 | 19-OCT-18:01 | 25.67 | 11.41 | 0.100647E+09 | 71.85 | 11-OCT-21:19 | 25.67 | 11.41 |
November | 0.281974E+09 | 1526.60 | 10-NOV-16:01 | 24.50 | 12.16 | 95539645.46 | 70.91 | 02-NOV-21:00 | 24.50 | 12.16 |
December | 0.159835E+09 | 1457.41 | 23-DEC-16:01 | 22.67 | 9.83 | 96388798.25 | 59.32 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.750392E+10 | 0.116905E+10 | ||||||||
Minimum of Months | 0.159835E+09 | 1409.40 | 13.67 | 7.91 | 87429066.75 | 56.69 | 13.67 | 7.15 | ||
Maximum of Months | 0.113721E+10 | 1728.72 | 27.75 | 14.34 | 0.100647E+09 | 76.96 | 31.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.946851E+09 | 2090.38 | 31-JAN-16:02 | 29.00 | 10.73 | 98648240.60 | 56.69 | 19-JAN-22:10 | 29.00 | 10.73 |
February | 0.434897E+09 | 2055.21 | 18-FEB-16:01 | 21.67 | 13.97 | 88211475.89 | 56.69 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.842819E+09 | 2095.06 | 23-MAR-15:01 | 24.80 | 11.21 | 98531765.57 | 56.69 | 16-MAR-22:30 | 24.80 | 11.21 |
April | 0.226624E+10 | 2151.51 | 14-APR-15:01 | 35.00 | 14.57 | 96038113.88 | 56.70 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.272240E+10 | 2177.67 | 20-MAY-08:61 | 26.50 | 11.05 | 99320207.10 | 56.76 | 10-MAY-21:10 | 26.50 | 11.05 |
June | 0.338415E+10 | 2182.49 | 14-JUN-08:61 | 27.67 | 11.24 | 97512859.16 | 61.26 | 26-JUN-21:10 | 33.67 | 14.50 |
July | 0.326526E+10 | 2193.95 | 22-JUL-08:61 | 33.00 | 19.64 | 99555161.58 | 59.21 | 05-JUL-21:10 | 33.00 | 19.64 |
August | 0.317204E+10 | 2196.55 | 13-AUG-08:61 | 31.17 | 20.60 | 99645320.53 | 60.58 | 25-AUG-21:10 | 31.50 | 13.17 |
September | 0.273295E+10 | 2160.75 | 09-SEP-08:61 | 28.77 | 20.10 | 96204765.62 | 56.70 | 09-SEP-23:00 | 26.10 | 18.04 |
October | 0.190178E+10 | 2143.88 | 04-OCT-08:62 | 25.33 | 18.36 | 99117906.88 | 56.70 | 03-OCT-22:00 | 25.33 | 18.36 |
November | 0.929300E+09 | 2119.38 | 10-NOV-09:01 | 21.33 | 9.26 | 95362892.89 | 56.69 | 02-NOV-21:19 | 21.33 | 9.26 |
December | 0.531837E+09 | 2077.59 | 25-DEC-16:02 | 25.67 | 11.87 | 98035325.54 | 56.69 | 12-DEC-22:10 | 25.67 | 11.87 |
Annual Sum or Average | 0.231305E+11 | 0.116618E+10 | ||||||||
Minimum of Months | 0.434897E+09 | 2055.21 | 21.33 | 9.26 | 88211475.89 | 56.69 | 14.00 | 9.26 | ||
Maximum of Months | 0.338415E+10 | 2196.55 | 35.00 | 20.60 | 99645320.53 | 61.26 | 33.67 | 19.64 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336739E+09 | 2087.69 | 27-JAN-09:51 | 20.00 | 7.78 | 98858995.94 | 65.52 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.191303E+09 | 2007.73 | 26-FEB-09:01 | 11.33 | 8.84 | 87530403.56 | 59.10 | 09-FEB-22:30 | 11.33 | 8.84 |
March | 0.494650E+09 | 2086.62 | 18-MAR-08:51 | 20.00 | 13.27 | 0.100682E+09 | 71.42 | 16-MAR-21:10 | 20.00 | 13.27 |
April | 0.186478E+10 | 2473.79 | 13-APR-08:51 | 25.00 | 10.97 | 99117082.79 | 73.62 | 19-APR-21:30 | 20.50 | 9.19 |
May | 0.249397E+10 | 2679.62 | 21-MAY-08:61 | 25.33 | 11.05 | 0.102358E+09 | 56.79 | 10-MAY-21:10 | 25.33 | 11.05 |
June | 0.331727E+10 | 2514.26 | 13-JUN-08:11 | 26.00 | 10.40 | 99959518.27 | 62.27 | 26-JUN-21:10 | 33.67 | 14.50 |
July | 0.321234E+10 | 2518.61 | 01-JUL-08:61 | 27.50 | 10.46 | 0.100526E+09 | 59.89 | 05-JUL-21:10 | 31.67 | 12.95 |
August | 0.295980E+10 | 2548.42 | 24-AUG-08:61 | 26.50 | 12.85 | 0.101297E+09 | 78.79 | 04-AUG-21:10 | 26.50 | 12.85 |
September | 0.237734E+10 | 2438.30 | 15-SEP-08:51 | 25.00 | 16.27 | 98316361.64 | 76.31 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.128207E+10 | 2414.12 | 17-OCT-08:51 | 24.00 | 9.54 | 0.102223E+09 | 72.88 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.390092E+09 | 2248.08 | 10-NOV-09:51 | 23.00 | 9.98 | 96245312.57 | 70.51 | 02-NOV-21:30 | 23.00 | 9.98 |
December | 0.154477E+09 | 2003.95 | 23-DEC-16:01 | 22.67 | 9.83 | 96471038.92 | 56.69 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.190748E+11 | 0.118358E+10 | ||||||||
Minimum of Months | 0.154477E+09 | 2003.95 | 11.33 | 7.78 | 87530403.56 | 56.69 | 11.33 | 5.13 | ||
Maximum of Months | 0.331727E+10 | 2679.62 | 27.50 | 16.27 | 0.102358E+09 | 78.79 | 33.67 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422243E+10 | 2020.35 | 29-JAN-11:33 | 21.33 | 8.67 | 0.136230E+10 | 859.87 | 31-JAN-22:40 | 13.83 | 4.56 |
February | 0.345162E+10 | 1987.14 | 01-FEB-07:03 | 5.00 | 3.59 | 0.116244E+10 | 848.12 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.411224E+10 | 2058.85 | 18-MAR-10:45 | 24.12 | 14.75 | 0.134394E+10 | 861.91 | 17-MAR-21:40 | 24.12 | 14.75 |
April | 0.484519E+10 | 2441.43 | 15-APR-10:33 | 28.00 | 13.04 | 0.145962E+10 | 951.84 | 14-APR-21:30 | 28.00 | 13.04 |
May | 0.529952E+10 | 2456.88 | 20-MAY-10:33 | 31.33 | 12.44 | 0.156395E+10 | 951.86 | 10-MAY-22:00 | 31.33 | 12.44 |
June | 0.607990E+10 | 3878.15 | 28-JUN-19:10 | 39.50 | 16.83 | 0.156648E+10 | 951.87 | 09-JUN-23:49 | 39.50 | 16.83 |
July | 0.595871E+10 | 3432.88 | 21-JUL-19:10 | 37.83 | 19.56 | 0.160809E+10 | 951.86 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.586813E+10 | 3277.63 | 15-AUG-18:17 | 37.67 | 18.63 | 0.160846E+10 | 951.85 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.544257E+10 | 3113.76 | 08-SEP-18:13 | 35.90 | 20.02 | 0.154613E+10 | 951.86 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.497749E+10 | 2810.06 | 05-OCT-18:13 | 31.00 | 15.12 | 0.150087E+10 | 951.86 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.417930E+10 | 2107.94 | 01-NOV-18:10 | 23.67 | 14.38 | 0.133669E+10 | 886.32 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.385291E+10 | 2048.13 | 30-DEC-06:08 | 4.00 | 0.61 | 0.129236E+10 | 837.13 | 26-DEC-22:40 | 4.00 | 0.61 |
Annual Sum or Average | 0.582900E+11 | 0.173513E+11 | ||||||||
Minimum of Months | 0.345162E+10 | 1987.14 | 4.00 | 0.61 | 0.116244E+10 | 837.13 | 4.00 | 0.61 | ||
Maximum of Months | 0.607990E+10 | 3878.15 | 39.50 | 20.02 | 0.160846E+10 | 951.87 | 39.50 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.877529E+09 | 2514.80 | 05-JAN-16:02 | 24.00 | 9.77 | 98151435.75 | 56.69 | 02-JAN-22:00 | 24.00 | 9.77 |
February | 0.321868E+09 | 2471.77 | 28-FEB-16:01 | 19.00 | 8.42 | 87482957.59 | 56.70 | 10-FEB-00:10 | 19.00 | 8.42 |
March | 0.749421E+09 | 2487.37 | 23-MAR-15:01 | 24.80 | 11.21 | 97924212.71 | 56.70 | 13-MAR-22:00 | 24.80 | 11.21 |
April | 0.223195E+10 | 2587.70 | 14-APR-18:01 | 33.50 | 13.96 | 96102512.06 | 56.70 | 11-APR-21:49 | 33.50 | 13.96 |
May | 0.266892E+10 | 2576.88 | 31-MAY-18:01 | 35.67 | 13.49 | 99533430.23 | 56.70 | 10-MAY-23:40 | 35.67 | 13.49 |
June | 0.346021E+10 | 2631.56 | 27-JUN-18:02 | 39.83 | 15.83 | 98877046.79 | 63.43 | 26-JUN-21:10 | 39.83 | 15.83 |
July | 0.318643E+10 | 2594.48 | 01-JUL-18:01 | 35.83 | 13.66 | 99916883.42 | 60.30 | 05-JUL-21:10 | 31.67 | 12.95 |
August | 0.310641E+10 | 2615.02 | 25-AUG-18:01 | 38.67 | 17.09 | 0.100005E+09 | 58.17 | 25-AUG-21:10 | 31.50 | 13.17 |
September | 0.266488E+10 | 2563.83 | 04-SEP-15:01 | 31.60 | 21.45 | 96330986.70 | 56.70 | 05-SEP-21:40 | 28.47 | 19.19 |
October | 0.172598E+10 | 2567.23 | 18-OCT-15:01 | 30.00 | 11.77 | 98852220.96 | 56.70 | 02-OCT-23:30 | 30.00 | 11.77 |
November | 0.873759E+09 | 2547.85 | 20-NOV-16:02 | 26.83 | 12.13 | 94950128.14 | 56.69 | 20-NOV-22:10 | 14.00 | 9.66 |
December | 0.454507E+09 | 2516.34 | 22-DEC-16:02 | 24.83 | 10.00 | 97332360.43 | 56.69 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.223219E+11 | 0.116546E+10 | ||||||||
Minimum of Months | 0.321868E+09 | 2471.77 | 19.00 | 8.42 | 87482957.59 | 56.69 | 14.00 | 7.20 | ||
Maximum of Months | 0.346021E+10 | 2631.56 | 39.83 | 21.45 | 0.100005E+09 | 63.43 | 39.83 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269525E+09 | 2419.76 | 31-JAN-16:02 | 29.00 | 10.73 | 98793777.66 | 64.31 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 97010798.05 | 2391.59 | 28-FEB-16:01 | 19.00 | 8.42 | 87004413.00 | 56.69 | 22-FEB-23:49 | 19.00 | 8.42 |
March | 0.391675E+09 | 2440.59 | 23-MAR-15:01 | 24.80 | 11.21 | 0.100790E+09 | 73.50 | 31-MAR-18:10 | 21.23 | 7.98 |
April | 0.190568E+10 | 2561.14 | 14-APR-18:01 | 33.50 | 13.96 | 98628120.12 | 79.97 | 20-APR-18:10 | 21.67 | 7.62 |
May | 0.255462E+10 | 2680.85 | 08-MAY-08:61 | 27.17 | 12.22 | 0.100835E+09 | 56.70 | 30-MAY-21:10 | 27.83 | 12.44 |
June | 0.344935E+10 | 2730.08 | 14-JUN-08:61 | 27.67 | 11.24 | 0.100577E+09 | 64.26 | 26-JUN-21:10 | 33.67 | 14.50 |
July | 0.315719E+10 | 2818.27 | 01-JUL-08:61 | 27.50 | 10.46 | 0.100546E+09 | 61.03 | 05-JUL-21:10 | 31.67 | 12.95 |
August | 0.292494E+10 | 2594.07 | 25-AUG-18:01 | 38.67 | 17.09 | 0.101168E+09 | 78.76 | 04-AUG-21:10 | 38.67 | 17.09 |
September | 0.235531E+10 | 2526.75 | 06-SEP-18:01 | 33.07 | 19.98 | 97722573.65 | 75.27 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.115957E+10 | 2497.91 | 15-OCT-15:01 | 31.00 | 12.59 | 0.101432E+09 | 72.91 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.343193E+09 | 2455.66 | 20-NOV-16:02 | 26.83 | 12.13 | 96105650.33 | 71.62 | 01-NOV-21:30 | 26.83 | 12.13 |
December | 0.104178E+09 | 2407.51 | 22-DEC-16:02 | 24.83 | 10.00 | 96100844.50 | 56.69 | 22-DEC-22:00 | 10.00 | 3.01 |
Annual Sum or Average | 0.187122E+11 | 0.117970E+10 | ||||||||
Minimum of Months | 97010798.05 | 2391.59 | 19.00 | 8.42 | 87004413.00 | 56.69 | 10.00 | 3.01 | ||
Maximum of Months | 0.344935E+10 | 2818.27 | 38.67 | 19.98 | 0.101432E+09 | 79.97 | 38.67 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118569E+10 | 2407.23 | 05-JAN-16:02 | 24.00 | 9.77 | 98849546.10 | 56.69 | 20-JAN-22:40 | 11.83 | 10.07 |
February | 0.531897E+09 | 2368.93 | 28-FEB-16:01 | 19.00 | 8.42 | 88464886.96 | 56.69 | 14-FEB-22:40 | 19.00 | 8.42 |
March | 0.661330E+09 | 2368.81 | 31-MAR-15:01 | 22.80 | 8.55 | 98426939.28 | 56.69 | 09-MAR-22:49 | 22.80 | 8.55 |
April | 0.128131E+10 | 2407.22 | 14-APR-15:01 | 35.00 | 14.57 | 95668863.40 | 56.69 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.135099E+10 | 2389.06 | 09-MAY-15:01 | 35.00 | 14.52 | 99079106.11 | 56.69 | 26-MAY-02:49 | 21.50 | 13.47 |
June | 0.170055E+10 | 2397.11 | 08-JUN-15:01 | 39.83 | 15.81 | 96010109.52 | 56.69 | 16-JUN-21:49 | 33.17 | 13.86 |
July | 0.171756E+10 | 2390.94 | 01-JUL-08:61 | 27.50 | 10.46 | 99112409.59 | 56.70 | 20-JUL-21:00 | 33.00 | 18.18 |
August | 0.176960E+10 | 2413.80 | 26-AUG-15:01 | 41.00 | 16.32 | 99210643.90 | 56.70 | 15-AUG-21:00 | 41.00 | 16.32 |
September | 0.170576E+10 | 1907.61 | 24-SEP-08:61 | 24.18 | 17.45 | 95929558.01 | 56.70 | 06-SEP-21:40 | 24.18 | 17.45 |
October | 0.141699E+10 | 2423.56 | 18-OCT-15:01 | 30.00 | 11.77 | 98904547.17 | 56.70 | 05-OCT-21:10 | 30.00 | 11.77 |
November | 0.103709E+10 | 2407.63 | 20-NOV-16:02 | 26.83 | 12.13 | 95531275.90 | 56.69 | 03-NOV-01:00 | 26.83 | 12.13 |
December | 0.887760E+09 | 2403.22 | 22-DEC-16:02 | 24.83 | 10.00 | 98575777.77 | 56.69 | 12-DEC-22:30 | 24.83 | 10.00 |
Annual Sum or Average | 0.152465E+11 | 0.116376E+10 | ||||||||
Minimum of Months | 0.531897E+09 | 1907.61 | 19.00 | 8.42 | 88464886.96 | 56.69 | 11.83 | 8.42 | ||
Maximum of Months | 0.176960E+10 | 2423.56 | 41.00 | 17.45 | 99210643.90 | 56.70 | 41.00 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350719E+11 | 19413.08 | 06-JAN-22:10 | 17.67 | 9.28 | 0.191896E+11 | 11348.70 | 02-JAN-00:20 | 17.67 | 9.28 |
February | 0.309235E+11 | 18979.78 | 21-FEB-23:00 | 14.00 | 12.80 | 0.173175E+11 | 11349.72 | 01-FEB-00:00 | 14.00 | 12.80 |
March | 0.361880E+11 | 20982.82 | 17-MAR-21:10 | 21.42 | 12.50 | 0.192958E+11 | 11348.79 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.405699E+11 | 23048.39 | 14-APR-21:10 | 28.67 | 13.19 | 0.187077E+11 | 11348.94 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.442722E+11 | 23273.35 | 09-MAY-21:20 | 28.67 | 12.70 | 0.193485E+11 | 11354.30 | 19-MAY-21:19 | 28.33 | 11.33 |
June | 0.465199E+11 | 24926.81 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187612E+11 | 11381.95 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.472628E+11 | 24618.20 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193101E+11 | 11377.40 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.465151E+11 | 24161.78 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193910E+11 | 11368.49 | 14-AUG-22:00 | 31.00 | 17.56 |
September | 0.435433E+11 | 23932.67 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187092E+11 | 11368.91 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.396709E+11 | 23108.32 | 03-OCT-21:10 | 29.50 | 18.57 | 0.192771E+11 | 11348.76 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.345907E+11 | 20842.41 | 02-NOV-21:53 | 20.00 | 16.05 | 0.185863E+11 | 11348.65 | 24-NOV-00:30 | 4.00 | -1.2 |
December | 0.331178E+11 | 19001.08 | 26-DEC-22:10 | 14.83 | 7.20 | 0.191168E+11 | 11348.67 | 18-DEC-00:20 | 14.83 | 7.20 |
Annual Sum or Average | 0.478246E+12 | 0.227011E+12 | ||||||||
Minimum of Months | 0.309235E+11 | 18979.78 | 14.00 | 7.20 | 0.173175E+11 | 11348.65 | 4.00 | -1.2 | ||
Maximum of Months | 0.472628E+11 | 24926.81 | 34.33 | 20.69 | 0.193910E+11 | 11381.95 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384631E+11 | 21078.48 | 06-JAN-22:10 | 17.67 | 9.28 | 0.192586E+11 | 11348.72 | 02-JAN-00:20 | 17.67 | 9.28 |
February | 0.342264E+11 | 20691.79 | 21-FEB-22:10 | 14.00 | 12.80 | 0.173983E+11 | 11349.97 | 01-FEB-00:00 | 14.00 | 12.80 |
March | 0.397482E+11 | 22426.74 | 17-MAR-21:10 | 21.42 | 12.50 | 0.193602E+11 | 11348.79 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.434971E+11 | 24227.13 | 14-APR-21:10 | 28.67 | 13.19 | 0.187168E+11 | 11350.30 | 25-APR-21:19 | 26.67 | 13.95 |
May | 0.471441E+11 | 24471.43 | 09-MAY-21:20 | 28.67 | 12.70 | 0.193503E+11 | 11368.10 | 26-MAY-21:19 | 25.00 | 9.45 |
June | 0.492022E+11 | 26104.52 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187620E+11 | 11390.51 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.499992E+11 | 25794.38 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193109E+11 | 11384.78 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.492543E+11 | 25341.77 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193920E+11 | 11368.27 | 14-AUG-22:00 | 31.00 | 17.56 |
September | 0.461844E+11 | 25088.31 | 07-SEP-21:20 | 32.20 | 19.40 | 0.187106E+11 | 11378.37 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.427147E+11 | 24259.03 | 03-OCT-21:10 | 29.50 | 18.57 | 0.193023E+11 | 11348.76 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.378465E+11 | 22196.53 | 02-NOV-21:10 | 20.00 | 15.60 | 0.186441E+11 | 11348.68 | 24-NOV-00:30 | 4.00 | -1.2 |
December | 0.366243E+11 | 20560.65 | 26-DEC-22:10 | 14.83 | 7.20 | 0.192205E+11 | 11348.69 | 18-DEC-00:20 | 14.83 | 7.20 |
Annual Sum or Average | 0.514905E+12 | 0.227427E+12 | ||||||||
Minimum of Months | 0.342264E+11 | 20560.65 | 14.00 | 7.20 | 0.173983E+11 | 11348.68 | 4.00 | -1.2 | ||
Maximum of Months | 0.499992E+11 | 26104.52 | 34.33 | 20.69 | 0.193920E+11 | 11390.51 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522156E+11 | 28286.44 | 29-JAN-11:50 | 21.67 | 8.74 | 0.188447E+11 | 11319.57 | 07-JAN-18:19 | 21.67 | 8.74 |
February | 0.464950E+11 | 28173.45 | 18-FEB-11:33 | 19.33 | 14.12 | 0.170228E+11 | 11319.52 | 25-FEB-18:19 | 15.67 | 9.08 |
March | 0.526525E+11 | 29179.13 | 18-MAR-10:45 | 24.12 | 14.75 | 0.188567E+11 | 11319.64 | 18-MAR-17:19 | 26.63 | 12.71 |
April | 0.549350E+11 | 30543.93 | 30-APR-10:33 | 30.00 | 11.09 | 0.182589E+11 | 11319.81 | 29-APR-17:19 | 30.00 | 11.09 |
May | 0.580530E+11 | 30743.59 | 07-MAY-10:33 | 30.00 | 12.89 | 0.188709E+11 | 11319.66 | 13-MAY-17:19 | 29.67 | 11.30 |
June | 0.586993E+11 | 31519.36 | 18-JUN-10:50 | 35.67 | 17.76 | 0.182662E+11 | 11319.65 | 17-JUN-17:19 | 35.67 | 17.76 |
July | 0.601214E+11 | 31508.52 | 22-JUL-10:50 | 35.83 | 19.54 | 0.188684E+11 | 11319.68 | 29-JUL-17:19 | 35.90 | 19.14 |
August | 0.598031E+11 | 31553.99 | 13-AUG-10:40 | 33.67 | 21.36 | 0.188756E+11 | 11319.66 | 19-AUG-17:19 | 31.33 | 19.30 |
September | 0.567000E+11 | 31352.06 | 09-SEP-10:33 | 33.43 | 20.70 | 0.182618E+11 | 11319.66 | 30-SEP-17:19 | 33.07 | 16.08 |
October | 0.551931E+11 | 30605.03 | 02-OCT-10:45 | 32.67 | 19.11 | 0.188606E+11 | 11319.70 | 07-OCT-17:19 | 20.00 | 13.38 |
November | 0.507780E+11 | 29048.34 | 01-NOV-10:33 | 24.33 | 16.10 | 0.182395E+11 | 11319.56 | 04-NOV-17:19 | 17.67 | 8.15 |
December | 0.507183E+11 | 28148.54 | 25-DEC-11:50 | 22.67 | 10.24 | 0.188340E+11 | 11319.56 | 16-DEC-18:19 | 22.67 | 10.24 |
Annual Sum or Average | 0.656364E+12 | 0.222060E+12 | ||||||||
Minimum of Months | 0.464950E+11 | 28148.54 | 19.33 | 8.74 | 0.170228E+11 | 11319.52 | 15.67 | 8.15 | ||
Maximum of Months | 0.601214E+11 | 31553.99 | 35.83 | 21.36 | 0.188756E+11 | 11319.81 | 35.90 | 19.30 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829932E+10 | 4133.72 | 29-JAN-11:33 | 21.33 | 8.67 | 0.141268E+10 | 894.93 | 31-JAN-22:19 | 14.27 | 4.94 |
February | 0.681390E+10 | 3892.14 | 26-FEB-11:33 | 15.33 | 10.16 | 0.121483E+10 | 875.04 | 01-FEB-00:10 | 15.33 | 10.16 |
March | 0.819124E+10 | 4455.59 | 18-MAR-17:12 | 26.63 | 12.71 | 0.141153E+10 | 937.69 | 17-MAR-21:40 | 26.63 | 12.71 |
April | 0.102039E+11 | 6420.37 | 14-APR-15:03 | 35.00 | 14.57 | 0.156068E+10 | 1007.41 | 12-APR-22:00 | 35.00 | 14.57 |
May | 0.114392E+11 | 6097.25 | 09-MAY-15:03 | 35.00 | 14.52 | 0.166708E+10 | 1007.44 | 10-MAY-23:19 | 25.67 | 15.01 |
June | 0.137201E+11 | 8110.12 | 28-JUN-18:17 | 40.67 | 17.68 | 0.165476E+10 | 1007.44 | 09-JUN-23:30 | 40.67 | 17.68 |
July | 0.136466E+11 | 7444.40 | 20-JUL-18:17 | 38.33 | 19.15 | 0.170434E+10 | 1007.43 | 07-JUL-22:10 | 38.33 | 19.15 |
August | 0.133658E+11 | 7485.34 | 11-AUG-15:25 | 38.00 | 21.21 | 0.170523E+10 | 1007.41 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.120528E+11 | 7512.76 | 07-SEP-15:03 | 37.28 | 19.77 | 0.163647E+10 | 1007.41 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.101345E+11 | 7057.85 | 02-OCT-13:10 | 34.17 | 19.45 | 0.155844E+10 | 1007.41 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.824288E+10 | 4431.06 | 01-NOV-17:12 | 25.33 | 14.39 | 0.138095E+10 | 947.23 | 01-NOV-21:30 | 18.00 | 13.11 |
December | 0.720676E+10 | 4014.22 | 25-DEC-11:33 | 22.33 | 10.13 | 0.134312E+10 | 877.89 | 26-DEC-22:30 | 14.50 | 7.04 |
Annual Sum or Average | 0.123317E+12 | 0.182501E+11 | ||||||||
Minimum of Months | 0.681390E+10 | 3892.14 | 15.33 | 8.67 | 0.121483E+10 | 875.04 | 14.27 | 4.94 | ||
Maximum of Months | 0.137201E+11 | 8110.12 | 40.67 | 21.21 | 0.170523E+10 | 1007.44 | 40.67 | 19.15 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 308249.99 | 107.73 | 27-MAR-06:10 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 735968.19 | 187.04 | 16-DEC-07:20 | 1.33 |
Annual Sum or Average | 1044218.18 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 735968.19 | 187.04 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32825611.62 | 851.07 | 01-JAN-09:02 | 5.90 |
February | 77747962.04 | 1202.79 | 12-FEB-16:02 | 14.00 |
March | 53392754.69 | 1223.68 | 26-MAR-08:62 | 7.75 |
April | 630165.21 | 641.89 | 11-APR-08:05 | 23.33 |
May | 24731.51 | 206.10 | 01-MAY-08:06 | 19.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 34219.86 | 261.77 | 30-AUG-08:05 | 26.67 |
September | 29131.95 | 207.51 | 03-SEP-08:06 | 20.18 |
October | 4070438.95 | 668.79 | 12-OCT-08:03 | 12.33 |
November | 23423727.61 | 801.38 | 30-NOV-19:04 | 14.00 |
December | 0.158226E+09 | 1211.12 | 08-DEC-09:02 | 10.50 |
Annual Sum or Average | 0.350405E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.90 | |
Maximum of Months | 0.158226E+09 | 1223.68 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90727238.80 | 1265.70 | 01-JAN-09:02 | 5.90 |
February | 0.140809E+09 | 1234.47 | 03-FEB-09:02 | 10.33 |
March | 72726525.21 | 1237.63 | 26-MAR-08:62 | 7.75 |
April | 325440.31 | 545.67 | 08-APR-08:54 | 20.00 |
May | 128265.24 | 496.76 | 03-MAY-08:35 | 27.00 |
June | 4863.87 | 81.06 | 13-JUN-08:16 | 26.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 32619.22 | 252.75 | 22-SEP-08:54 | 23.80 |
October | 8389643.07 | 956.46 | 25-OCT-08:62 | 8.50 |
November | 58628479.92 | 1229.94 | 23-NOV-09:02 | 5.45 |
December | 0.330297E+09 | 1267.14 | 08-DEC-09:02 | 10.50 |
Annual Sum or Average | 0.702069E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.45 | |
Maximum of Months | 0.330297E+09 | 1267.14 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4343257.40 | 403.99 | 19-JAN-09:03 | 13.67 |
February | 2295877.69 | 405.12 | 01-FEB-16:03 | 15.83 |
March | 2303793.92 | 410.02 | 11-MAR-16:04 | 15.78 |
April | 1101431.34 | 377.85 | 19-APR-21:54 | 20.00 |
May | 441558.00 | 375.17 | 12-MAY-08:44 | 24.83 |
June | 28607.51 | 80.21 | 30-JUN-08:06 | 31.33 |
July | 206537.96 | 243.15 | 02-JUL-08:15 | 27.07 |
August | 264542.32 | 236.04 | 25-AUG-08:04 | 27.50 |
September | 398988.85 | 321.13 | 03-SEP-21:55 | 23.30 |
October | 1324123.27 | 407.27 | 22-OCT-15:04 | 15.83 |
November | 2398290.55 | 403.12 | 29-NOV-09:03 | 13.50 |
December | 16578447.02 | 403.65 | 10-DEC-09:03 | 11.67 |
Annual Sum or Average | 31685455.83 | |||
Minimum of Months | 28607.51 | 80.21 | 11.67 | |
Maximum of Months | 16578447.02 | 410.02 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40543958.05 | 702.90 | 03-JAN-19:04 | 14.67 |
February | 74826146.69 | 1172.31 | 12-FEB-16:02 | 14.00 |
March | 51130086.18 | 733.41 | 25-MAR-18:04 | 13.43 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 4533.09 | 52.89 | 03-SEP-08:06 | 20.18 |
October | 3027453.76 | 480.70 | 27-OCT-08:05 | 14.33 |
November | 29162054.79 | 845.31 | 25-NOV-16:04 | 17.00 |
December | 0.156407E+09 | 1039.33 | 06-DEC-16:04 | 15.67 |
Annual Sum or Average | 0.355101E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.43 | |
Maximum of Months | 0.156407E+09 | 1172.31 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106112E+09 | 1210.19 | 01-JAN-19:01 | 11.03 |
February | 0.125917E+09 | 1174.97 | 12-FEB-16:02 | 14.00 |
March | 70657638.91 | 607.61 | 06-MAR-16:04 | 16.70 |
April | 7851.64 | 60.30 | 27-APR-21:56 | 21.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 6934404.14 | 767.03 | 25-OCT-15:04 | 17.00 |
November | 70758738.53 | 815.82 | 23-NOV-19:02 | 8.83 |
December | 0.308991E+09 | 1218.59 | 07-DEC-16:01 | 15.67 |
Annual Sum or Average | 0.689379E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.83 | |
Maximum of Months | 0.308991E+09 | 1218.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118205E+09 | 1465.63 | 01-JAN-09:02 | 5.90 |
February | 0.202356E+09 | 1436.59 | 12-FEB-16:02 | 14.00 |
March | 0.135640E+09 | 1478.27 | 26-MAR-08:62 | 7.75 |
April | 1340617.97 | 525.69 | 06-APR-08:05 | 21.50 |
May | 154364.08 | 277.62 | 26-MAY-08:06 | 24.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 27642.38 | 199.19 | 30-AUG-08:05 | 26.67 |
September | 71988.85 | 254.81 | 22-SEP-08:04 | 22.47 |
October | 28518045.50 | 1439.22 | 25-OCT-08:62 | 8.50 |
November | 89718796.15 | 1342.03 | 24-NOV-09:02 | 9.00 |
December | 0.341370E+09 | 1467.71 | 05-DEC-09:02 | 7.33 |
Annual Sum or Average | 0.917403E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.90 | |
Maximum of Months | 0.341370E+09 | 1478.27 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242271E+09 | 1522.98 | 01-JAN-09:02 | 5.90 |
February | 0.316928E+09 | 1487.26 | 03-FEB-09:02 | 10.33 |
March | 0.167098E+09 | 1492.41 | 26-MAR-08:62 | 7.75 |
April | 513171.56 | 599.50 | 28-APR-08:53 | 23.00 |
May | 225731.58 | 597.20 | 01-MAY-08:53 | 22.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 9754.50 | 89.19 | 27-JUL-08:16 | 25.67 |
August | 6258.81 | 83.45 | 06-AUG-08:45 | 24.83 |
September | 105144.00 | 275.25 | 23-SEP-08:55 | 26.10 |
October | 45713731.41 | 1465.35 | 25-OCT-08:62 | 8.50 |
November | 0.170407E+09 | 1487.07 | 23-NOV-09:02 | 5.45 |
December | 0.605959E+09 | 1522.22 | 17-DEC-09:02 | 6.50 |
Annual Sum or Average | 0.154924E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.45 | |
Maximum of Months | 0.605959E+09 | 1522.98 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4743918.82 | 367.36 | 01-JAN-19:04 | 11.03 |
February | 17964955.24 | 833.00 | 07-FEB-16:04 | 16.00 |
March | 20804680.96 | 736.05 | 27-MAR-08:62 | 9.77 |
April | 708929.21 | 742.76 | 20-APR-08:03 | 15.50 |
May | 828734.60 | 770.09 | 09-MAY-08:03 | 26.33 |
June | 233315.71 | 818.46 | 14-JUN-08:03 | 27.67 |
July | 667021.82 | 738.45 | 01-JUL-08:03 | 27.50 |
August | 723896.55 | 485.61 | 29-AUG-08:04 | 26.67 |
September | 663611.22 | 505.05 | 14-SEP-08:04 | 23.67 |
October | 1106191.36 | 624.96 | 12-OCT-08:03 | 12.33 |
November | 4833908.43 | 594.23 | 07-NOV-19:04 | 16.83 |
December | 31947624.99 | 641.47 | 30-DEC-09:04 | 10.50 |
Annual Sum or Average | 85226788.93 | |||
Minimum of Months | 233315.71 | 367.36 | 9.77 | |
Maximum of Months | 31947624.99 | 833.00 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 82276.40 | 97.83 | 07-DEC-07:10 | 1.33 |
Annual Sum or Average | 82276.40 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 82276.40 | 97.83 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131164E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118120E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122987E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.112540E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.110891E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.100416E+10 | 1701.53 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.106539E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.117264E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.116624E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.126210E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.125740E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.132084E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142058E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.100416E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.132084E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.941761E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.852043E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939752E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899636E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929742E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.898034E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.924329E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.937166E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.903632E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.938587E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.912659E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.940611E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110180E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.852043E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.941761E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282599E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.252316E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268928E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249094E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.247993E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.231901E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243156E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259008E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254782E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276953E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.272091E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282446E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312127E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.231901E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282599E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282599E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.252316E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268928E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249094E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.247993E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.231901E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243156E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259008E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254782E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276953E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.272091E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282446E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312127E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.231901E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282599E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2336551.84 | 0.237803E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245093E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6876581.73 | 0.204460E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64066079.90 | 67069887.82 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110078E+09 | 32452200.54 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200188E+09 | 5235474.75 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185428E+09 | 3176388.78 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170980E+09 | 4526747.15 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118399E+09 | 11024317.51 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43386594.93 | 0.114085E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4384342.03 | 0.211565E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 629852.67 | 0.311768E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906753E+09 | 0.144826E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3176388.78 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200188E+09 | 0.311768E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1593986.00 | 99874885.11 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104683E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3105633.53 | 90586759.79 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25692880.37 | 31624503.93 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42607451.22 | 16613103.72 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77148136.25 | 2868768.04 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71246641.72 | 1832163.73 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65700125.89 | 2811369.58 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45868565.93 | 6112066.63 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17482389.10 | 50141060.96 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2153592.59 | 90462042.57 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 495609.41 | 0.129442E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353095E+09 | 0.627052E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1832163.73 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77148136.25 | 0.129442E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7584566.81 | 0.205141E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19538.43 | 0.219101E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9826672.83 | 0.189010E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65704910.15 | 67399884.68 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101148E+09 | 37091057.20 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180985E+09 | 6767642.24 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166846E+09 | 4266014.00 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154370E+09 | 6396267.67 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108138E+09 | 13817796.71 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44446048.60 | 0.106492E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8043034.88 | 0.187920E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2714738.21 | 0.270203E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849828E+09 | 0.131361E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19538.43 | 4266014.00 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180985E+09 | 0.270203E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4398836.47 | 0.116059E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13177.15 | 0.123989E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820127.15 | 0.106489E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38984038.85 | 37151605.37 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59510994.04 | 20233634.25 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104590E+09 | 3798199.97 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96499544.65 | 2383085.51 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89491276.36 | 3432930.81 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63045402.21 | 7395556.45 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26151438.59 | 59247542.31 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4708636.58 | 0.105851E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1562452.37 | 0.153756E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494775E+09 | 0.739787E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13177.15 | 2383085.51 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104590E+09 | 0.153756E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 4667381.59 | 0.323261E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354574E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 8651422.49 | 0.302320E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 84494478.01 | 93556543.04 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.139864E+09 | 44102392.86 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.259890E+09 | 5805355.25 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.242737E+09 | 3889874.76 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.224931E+09 | 6441782.27 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.157746E+09 | 14387654.08 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 59793513.87 | 0.157244E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 6701964.08 | 0.291872E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 1372608.80 | 0.430176E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.119085E+10 | 0.202763E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3889874.76 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.259890E+09 | 0.430176E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.131164E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5128066.56 | 0.594368E+09 |
February | 0.236489E+11 | 0.118120E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621199E+09 |
March | 0.262800E+11 | 0.122987E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13545369.43 | 0.530400E+09 |
April | 0.253579E+11 | 0.112540E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140532E+09 | 0.177091E+09 |
May | 0.262123E+11 | 0.110891E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243413E+09 | 91745363.13 |
June | 0.254132E+11 | 0.100416E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444556E+09 | 16105655.59 |
July | 0.261570E+11 | 0.106539E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409068E+09 | 10311470.25 |
August | 0.262677E+11 | 0.117264E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376235E+09 | 15489395.83 |
September | 0.253456E+11 | 0.116624E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260470E+09 | 33703158.97 |
October | 0.261693E+11 | 0.126210E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95128909.93 | 0.292634E+09 |
November | 0.253025E+11 | 0.125740E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9374224.01 | 0.533686E+09 |
December | 0.261570E+11 | 0.132084E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1322776.37 | 0.771209E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142058E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199877E+10 | 0.368794E+10 |
Minimum of Months | 0.236489E+11 | 0.100416E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10311470.25 |
Maximum of Months | 0.262800E+11 | 0.132084E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444556E+09 | 0.771209E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.941761E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16819145.05 | 0.169719E+10 |
February | 0.702046E+11 | 0.852043E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179569E+10 |
March | 0.780153E+11 | 0.939752E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45107412.84 | 0.154339E+10 |
April | 0.752779E+11 | 0.899636E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416543E+09 | 0.519938E+09 |
May | 0.778146E+11 | 0.929742E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701301E+09 | 0.271325E+09 |
June | 0.754422E+11 | 0.898034E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126929E+10 | 46869647.99 |
July | 0.776503E+11 | 0.924329E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116960E+10 | 30048157.75 |
August | 0.779788E+11 | 0.937166E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107633E+10 | 46527751.52 |
September | 0.752414E+11 | 0.903632E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747371E+09 | 0.100272E+09 |
October | 0.776868E+11 | 0.938587E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277183E+09 | 0.844015E+09 |
November | 0.751137E+11 | 0.912659E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28786078.82 | 0.153375E+10 |
December | 0.776503E+11 | 0.940611E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4882899.16 | 0.221028E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110180E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575322E+10 | 0.106393E+11 |
Minimum of Months | 0.702046E+11 | 0.852043E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30048157.75 |
Maximum of Months | 0.780153E+11 | 0.941761E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126929E+10 | 0.221028E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3352460.01 | 0.122770E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.30 | 0.136537E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5888928.38 | 0.112968E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51430453.43 | 29055109.86 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83011722.36 | 10957068.65 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142483E+09 | 546415.05 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138390E+09 | 434657.20 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128669E+09 | 593597.83 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94728194.85 | 1978032.50 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36106053.44 | 53487700.62 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4453103.81 | 0.109104E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 921090.73 | 0.170431E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689436E+09 | 0.748863E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.30 | 434657.20 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142483E+09 | 0.170431E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3800270.75 | 0.122691E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5111.44 | 0.134242E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5584715.30 | 0.115392E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50434870.35 | 32091259.24 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81495691.60 | 13048304.52 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140135E+09 | 1268218.84 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137532E+09 | 792824.65 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127368E+09 | 1555826.72 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93131117.57 | 3475697.90 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35451580.87 | 56511714.48 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4586561.38 | 0.110270E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203870.25 | 0.166415E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680729E+09 | 0.757754E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5111.44 | 792824.65 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140135E+09 | 0.166415E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47508.43 | 57150581.04 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59412646.15 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 127138.35 | 53292965.38 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5116013.32 | 20852113.00 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10181224.58 | 12499472.71 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22621249.55 | 3538340.81 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19308707.04 | 2840373.31 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17783509.09 | 4099532.83 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11305199.90 | 7030589.76 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3730746.33 | 31599557.64 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68120.40 | 52160770.05 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71078058.16 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90289416.99 | 0.375555E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2840373.31 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22621249.55 | 71078058.16 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458430.44 | 33756284.91 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1129.25 | 37538890.06 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1730607.22 | 31808660.07 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14514724.03 | 8556921.95 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23179619.85 | 3472811.89 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40324013.31 | 261527.79 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38849639.67 | 181063.62 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36015442.17 | 359126.85 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26332473.87 | 856399.95 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10263138.50 | 15379588.98 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575693.36 | 30272229.47 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 495301.81 | 46390799.53 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194740E+09 | 0.208834E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1129.25 | 181063.62 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40324013.31 | 46390799.53 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3397090.88 | 0.123623E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2012.45 | 0.137935E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5892205.22 | 0.114483E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51696016.26 | 29551461.22 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83037547.18 | 11112231.05 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142516E+09 | 546481.37 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138209E+09 | 437255.86 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128614E+09 | 618790.28 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94657011.47 | 2043135.00 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36187693.41 | 54144892.89 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4485239.30 | 0.109674E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 930960.93 | 0.171561E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689625E+09 | 0.755730E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2012.45 | 437255.86 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142516E+09 | 0.171561E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3646816.19 | 0.122545E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.62 | 0.135266E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5442555.89 | 0.116454E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50111862.42 | 33992131.81 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80763482.43 | 15665286.80 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139416E+09 | 1883714.36 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137107E+09 | 1117688.36 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127051E+09 | 2034740.21 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92615127.55 | 4268526.28 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35175567.73 | 57929523.54 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4497346.86 | 0.110028E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1151218.47 | 0.166373E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676979E+09 | 0.767558E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.62 | 1117688.36 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139416E+09 | 0.166373E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4540257.37 | 0.160644E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24523.47 | 0.168607E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7224357.35 | 0.145481E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50438600.09 | 50934580.48 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79072510.70 | 27157684.53 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139486E+09 | 5001094.11 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129137E+09 | 3158048.22 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119486E+09 | 4578056.40 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83529678.14 | 10033537.83 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33010003.01 | 82969082.05 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5372282.77 | 0.146085E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1682208.47 | 0.210076E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653002E+09 | 0.101472E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24523.47 | 3158048.22 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139486E+09 | 0.210076E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3238705.60 | 0.123126E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1691.09 | 0.136653E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5739052.32 | 0.113290E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50693921.96 | 29263010.44 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82105258.78 | 11157945.39 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140830E+09 | 579773.48 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137219E+09 | 458260.67 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127517E+09 | 623037.48 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93771851.01 | 2026318.44 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35674469.96 | 53673615.76 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4340342.06 | 0.109369E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 878438.68 | 0.170580E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682011E+09 | 0.750801E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1691.09 | 458260.67 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140830E+09 | 0.170580E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3835057.44 | 0.122501E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4243.33 | 0.134029E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5453698.29 | 0.115702E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49818161.32 | 32026478.37 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80717754.94 | 12718915.26 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138563E+09 | 1160883.47 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136389E+09 | 731159.97 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126378E+09 | 1443728.79 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92356835.74 | 3198344.75 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35169643.33 | 56009745.53 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4557658.26 | 0.109784E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1229834.12 | 0.165899E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674472E+09 | 0.755204E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4243.33 | 731159.97 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138563E+09 | 0.165899E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1676823.00 | 63922681.14 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 924.25 | 71375713.04 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2959754.99 | 58872354.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26388665.92 | 14998325.56 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42506461.19 | 5707758.14 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74165444.94 | 296515.78 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70903780.55 | 234360.77 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65950179.05 | 319450.67 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48365647.62 | 1051044.63 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18441743.72 | 27829492.77 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2217023.71 | 56723508.96 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 458997.57 | 88975891.91 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354035E+09 | 0.390307E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 924.25 | 234360.77 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74165444.94 | 88975891.91 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3563085.92 | 0.390320E+09 |
February | 0.415303E+11 | 0.252316E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425376E+09 |
March | 0.461508E+11 | 0.268928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7440312.68 | 0.367236E+09 |
April | 0.445315E+11 | 0.249094E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86132961.33 | 0.121111E+09 |
May | 0.460320E+11 | 0.247993E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147504E+09 | 63016826.06 |
June | 0.446286E+11 | 0.231901E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277685E+09 | 11100934.02 |
July | 0.459349E+11 | 0.243156E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254935E+09 | 7160565.13 |
August | 0.461292E+11 | 0.259008E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234741E+09 | 11129935.94 |
September | 0.445099E+11 | 0.254782E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162386E+09 | 23763383.65 |
October | 0.459565E+11 | 0.276953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59936742.80 | 0.195739E+09 |
November | 0.444343E+11 | 0.272091E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5785462.37 | 0.354324E+09 |
December | 0.459349E+11 | 0.282446E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 990015.73 | 0.511837E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312127E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124110E+10 | 0.248211E+10 |
Minimum of Months | 0.415303E+11 | 0.231901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7160565.13 |
Maximum of Months | 0.461508E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277685E+09 | 0.511837E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3145163.61 | 0.393453E+09 |
February | 0.415303E+11 | 0.252316E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429548E+09 |
March | 0.461508E+11 | 0.268928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7152827.74 | 0.370436E+09 |
April | 0.445315E+11 | 0.249094E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85857046.17 | 0.121385E+09 |
May | 0.460320E+11 | 0.247993E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147416E+09 | 63028237.54 |
June | 0.446286E+11 | 0.231901E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277654E+09 | 11101210.06 |
July | 0.459349E+11 | 0.243156E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254901E+09 | 7160800.34 |
August | 0.461292E+11 | 0.259008E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234697E+09 | 11130300.92 |
September | 0.445099E+11 | 0.254782E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162316E+09 | 23767744.35 |
October | 0.459565E+11 | 0.276953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59661225.18 | 0.196923E+09 |
November | 0.444343E+11 | 0.272091E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5312989.37 | 0.356939E+09 |
December | 0.459349E+11 | 0.282446E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 802818.97 | 0.516564E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312127E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123892E+10 | 0.250144E+10 |
Minimum of Months | 0.415303E+11 | 0.231901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7160800.34 |
Maximum of Months | 0.461508E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277654E+09 | 0.516564E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2767927.79 | 0.350829E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384194E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6356333.23 | 0.330482E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 76889429.11 | 0.108179E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.132062E+09 | 56258647.26 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.248703E+09 | 9931340.97 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.228312E+09 | 6405366.56 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.210196E+09 | 9942853.86 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.145364E+09 | 21242827.96 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 53403116.25 | 0.175762E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4675783.30 | 0.318052E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 680324.90 | 0.461077E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.110941E+10 | 0.223236E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6405366.56 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.248703E+09 | 0.461077E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5937865.21 | 0.280170E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298642E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10342963.87 | 0.256603E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80546071.41 | 89264014.49 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132194E+09 | 47156633.06 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244022E+09 | 8313052.37 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224389E+09 | 5294272.43 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207250E+09 | 7844511.90 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143928E+09 | 17128207.49 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55647062.57 | 0.141031E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7737834.62 | 0.253299E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1988563.05 | 0.369840E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111398E+10 | 0.177459E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5294272.43 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244022E+09 | 0.369840E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 31-JAN-16:00 | 237.29 | 01-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 184.38 | 01-FEB-05:03 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 20-MAR-17:00 | 236.45 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.52 | 14-APR-16:00 | 148.99 | 21-APR-04:10 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.37 | 31-MAY-17:00 | 112.90 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 28-JUN-16:00 | 54.56 | 21-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 19-JUL-13:00 | 56.50 | 01-JUL-05:55 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.91 | 25-AUG-14:00 | 66.09 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 | 08-SEP-15:00 | 62.70 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 01-OCT-13:00 | 181.02 | 25-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.30 | 01-NOV-15:00 | 243.48 | 23-NOV-06:30 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 21-DEC-15:00 | 255.97 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 255.97 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 31-JAN-16:00 | 98.07 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 80.66 | 01-FEB-05:50 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 20-MAR-17:00 | 97.71 | 26-MAR-05:50 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 14-APR-15:00 | 67.70 | 21-APR-04:40 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.85 | 15-MAY-17:00 | 51.02 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 28-JUN-16:00 | 25.01 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.01 | 19-JUL-13:00 | 25.19 | 01-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 25-AUG-14:00 | 29.52 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 08-SEP-15:00 | 31.21 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 | 01-OCT-13:00 | 79.73 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 01-NOV-15:00 | 103.07 | 23-NOV-06:20 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 21-DEC-15:00 | 106.68 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 106.68 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 | 31-JAN-16:50 | 216.45 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 18-FEB-14:00 | 178.06 | 01-FEB-07:40 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 20-MAR-17:00 | 219.49 | 26-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.21 | 14-APR-16:30 | 150.87 | 21-APR-04:40 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.55 | 15-MAY-17:00 | 114.73 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.77 | 28-JUN-16:00 | 59.12 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 19-JUL-13:00 | 59.55 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.83 | 25-AUG-14:00 | 69.12 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.92 | 08-SEP-15:00 | 71.40 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 | 01-OCT-13:00 | 179.97 | 25-OCT-06:30 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 01-NOV-15:00 | 231.97 | 23-NOV-06:20 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 | 21-DEC-15:00 | 237.13 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 59.12 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 164.77 | 237.13 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 31-JAN-17:00 | 124.88 | 01-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 18-FEB-14:00 | 100.98 | 01-FEB-06:30 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 20-MAR-17:00 | 124.97 | 26-MAR-04:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 | 14-APR-16:30 | 85.50 | 21-APR-04:10 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.56 | 15-MAY-17:00 | 64.84 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 28-JUN-16:00 | 33.78 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 19-JUL-13:00 | 34.35 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.48 | 25-AUG-14:00 | 37.98 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 | 08-SEP-15:00 | 39.62 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.54 | 01-OCT-13:00 | 101.88 | 25-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 01-NOV-15:00 | 132.07 | 23-NOV-06:03 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 21-DEC-15:00 | 135.56 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 33.78 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 135.56 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 77.48 | 31-JAN-17:00 | 338.69 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 269.32 | 28-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 78.56 | 20-MAR-17:00 | 333.95 | 26-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 155.34 | 14-APR-17:00 | 220.60 | 21-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 180.78 | 15-MAY-17:00 | 151.39 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 240.79 | 28-JUN-17:00 | 80.72 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 210.09 | 19-JUL-13:00 | 81.30 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 229.80 | 25-AUG-17:00 | 95.27 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 194.47 | 08-SEP-16:00 | 100.68 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 179.18 | 01-OCT-13:00 | 267.76 | 25-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 72.37 | 01-NOV-15:00 | 344.28 | 23-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 40.67 | 25-DEC-16:00 | 362.22 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 240.79 | 362.22 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 31-JAN-17:00 | 563.23 | 01-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 469.05 | 01-FEB-05:10 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.44 | 20-MAR-17:00 | 547.14 | 26-MAR-04:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.78 | 14-APR-16:00 | 388.38 | 21-APR-04:10 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.66 | 31-MAY-17:00 | 293.85 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.32 | 28-JUN-16:00 | 143.21 | 21-JUN-06:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.45 | 19-JUL-13:00 | 144.24 | 01-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.04 | 25-AUG-14:00 | 159.06 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.11 | 08-SEP-15:00 | 175.13 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.70 | 01-OCT-13:00 | 448.64 | 25-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.67 | 01-NOV-15:00 | 575.11 | 23-NOV-06:10 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.90 | 21-DEC-15:00 | 617.58 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 399.32 | 617.58 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.21 | 31-JAN-16:00 | 1649.29 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1359.42 | 01-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.58 | 20-MAR-17:00 | 1632.84 | 26-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 712.76 | 14-APR-17:00 | 1134.16 | 21-APR-04:10 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 850.01 | 15-MAY-17:00 | 839.76 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.85 | 28-JUN-16:00 | 409.26 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.79 | 19-JUL-13:00 | 412.20 | 01-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.19 | 26-AUG-16:00 | 482.99 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 920.29 | 08-SEP-15:00 | 510.57 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.73 | 01-OCT-13:00 | 1339.35 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.45 | 01-NOV-15:00 | 1712.47 | 23-NOV-06:40 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.87 | 21-DEC-15:00 | 1801.24 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.26 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.85 | 1801.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 | 31-JAN-17:00 | 138.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:10 | 106.71 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 20-MAR-17:00 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.54 | 14-APR-16:00 | 85.69 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.97 | 31-MAY-16:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.76 | 17-JUN-16:00 | 19.78 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 | 18-JUL-16:00 | 19.92 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 | 25-AUG-15:50 | 40.44 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.80 | 08-SEP-16:00 | 28.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.95 | 03-OCT-16:00 | 106.07 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 01-NOV-15:10 | 142.34 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 | 25-DEC-16:10 | 149.60 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 19.78 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 115.76 | 149.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-16:50 | 138.73 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:10 | 106.70 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 20-MAR-17:00 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 | 14-APR-15:50 | 85.69 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.62 | 31-MAY-16:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.77 | 17-JUN-16:00 | 32.23 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 | 18-JUL-16:00 | 31.78 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.17 | 25-AUG-15:50 | 40.51 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 | 08-SEP-16:00 | 34.50 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 03-OCT-16:00 | 106.06 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 | 01-NOV-15:10 | 142.33 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 25-DEC-16:10 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 31.78 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 115.77 | 149.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 31-JAN-16:00 | 47.38 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 39.88 | 01-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 16-MAR-15:00 | 45.56 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 14-APR-15:00 | 32.90 | 21-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 31-MAY-17:00 | 26.34 | 01-MAY-04:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 28-JUN-16:00 | 15.23 | 21-JUN-06:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 19-JUL-13:00 | 15.34 | 01-JUL-05:55 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.40 | 25-AUG-14:00 | 17.18 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 | 08-SEP-15:00 | 17.89 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 01-OCT-13:00 | 39.77 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 01-NOV-15:00 | 48.09 | 23-NOV-06:20 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 50.23 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 50.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 31-JAN-16:50 | 38.72 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 18-FEB-16:04 | 29.78 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 16-MAR-15:10 | 38.59 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 14-APR-16:00 | 23.92 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 31-MAY-17:00 | 16.43 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 28-JUN-16:00 | 8.01 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 20-JUL-15:10 | 7.43 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 25-AUG-15:40 | 10.25 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 08-SEP-15:10 | 9.56 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 03-OCT-16:00 | 29.60 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 | 01-NOV-15:07 | 39.73 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 | 25-DEC-16:07 | 41.75 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 7.43 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 41.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 31-JAN-17:00 | 138.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:10 | 106.73 | 01-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 20-MAR-17:00 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.18 | 14-APR-16:10 | 85.69 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 31-MAY-17:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.75 | 16-JUN-16:00 | 19.78 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.25 | 18-JUL-16:00 | 19.92 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.64 | 25-AUG-17:00 | 40.44 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 | 08-SEP-16:00 | 28.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.37 | 03-OCT-16:00 | 106.85 | 25-OCT-07:20 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.06 | 01-NOV-15:10 | 142.34 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 25-DEC-16:10 | 149.60 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 19.78 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 118.75 | 149.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-16:40 | 138.73 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 18-FEB-16:10 | 106.70 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:10 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.20 | 14-APR-16:00 | 85.69 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.64 | 31-MAY-17:00 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.16 | 16-JUN-16:00 | 36.26 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.41 | 20-JUL-15:10 | 34.26 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 25-AUG-17:00 | 41.28 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 | 08-SEP-16:00 | 34.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 | 03-OCT-16:00 | 106.06 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 01-NOV-15:10 | 142.33 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 25-DEC-16:10 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 34.26 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 118.16 | 149.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.24 | 31-JAN-17:00 | 166.87 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 18-FEB-14:00 | 138.36 | 01-FEB-05:15 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 16-MAR-15:00 | 170.24 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.24 | 14-APR-17:00 | 117.40 | 21-APR-04:03 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 | 15-MAY-17:00 | 87.09 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 28-JUN-16:00 | 44.63 | 21-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 19-JUL-13:00 | 45.37 | 01-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.35 | 25-AUG-14:00 | 50.35 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 | 08-SEP-15:00 | 52.90 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.42 | 01-OCT-13:00 | 137.63 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 01-NOV-15:00 | 179.69 | 23-NOV-06:03 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 21-DEC-15:00 | 184.76 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 44.63 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 184.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 31-JAN-17:00 | 139.17 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 18-FEB-16:09 | 107.12 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 | 20-MAR-17:00 | 138.69 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 14-APR-16:00 | 86.10 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.38 | 31-MAY-16:00 | 59.28 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.42 | 17-JUN-16:00 | 20.16 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 | 19-JUL-16:00 | 20.30 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | 25-AUG-15:10 | 39.95 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 | 08-SEP-16:00 | 29.27 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.39 | 03-OCT-16:00 | 106.48 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 | 01-NOV-15:10 | 142.77 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 | 25-DEC-16:10 | 150.03 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 20.16 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 115.42 | 150.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 31-JAN-16:50 | 139.16 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 18-FEB-16:07 | 107.11 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 | 20-MAR-17:00 | 138.68 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.64 | 14-APR-15:10 | 86.09 | 21-APR-04:10 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 31-MAY-16:00 | 59.27 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.39 | 17-JUN-16:00 | 30.23 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.97 | 19-JUL-16:00 | 30.08 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.55 | 25-AUG-15:10 | 39.54 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.38 | 08-SEP-16:00 | 32.01 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 | 03-OCT-16:00 | 106.47 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 | 01-NOV-15:10 | 142.76 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 25-DEC-16:10 | 150.02 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 30.08 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 115.39 | 150.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 31-JAN-16:50 | 71.20 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 18-FEB-16:07 | 54.81 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 | 16-MAR-15:10 | 70.96 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 14-APR-15:50 | 44.05 | 21-APR-04:10 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 31-MAY-17:00 | 30.33 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 | 28-JUN-16:00 | 10.31 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 20-JUL-15:10 | 10.39 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 25-AUG-15:50 | 19.73 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.65 | 08-SEP-15:50 | 14.98 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 03-OCT-16:00 | 54.48 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 01-NOV-15:10 | 73.05 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25-DEC-16:10 | 76.76 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 10.31 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 | 76.76 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 | 31-JAN-17:00 | 387.14 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 308.09 | 28-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 16-MAR-15:00 | 385.81 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 14-APR-16:00 | 256.14 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.21 | 31-MAY-17:00 | 190.02 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 28-JUN-16:00 | 93.38 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 | 19-JUL-13:00 | 94.06 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.24 | 25-AUG-14:00 | 109.94 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 | 08-SEP-15:00 | 116.13 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 01-OCT-13:00 | 306.21 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 01-NOV-15:00 | 396.02 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 | 21-DEC-15:00 | 413.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.38 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 413.89 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.97 | 31-JAN-17:00 | 387.14 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 308.09 | 28-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 16-MAR-15:00 | 385.81 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 14-APR-16:00 | 256.14 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.21 | 31-MAY-17:00 | 190.02 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 28-JUN-16:00 | 93.39 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 | 19-JUL-13:00 | 94.06 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.24 | 25-AUG-14:00 | 109.94 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 | 08-SEP-15:00 | 116.13 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 01-OCT-13:00 | 306.30 | 25-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 01-NOV-15:00 | 396.05 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 21-DEC-15:00 | 413.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.62 | 413.89 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 65.51 | 31-JAN-16:40 | 346.49 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 275.75 | 28-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 62.55 | 16-MAR-15:40 | 345.32 | 26-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 141.68 | 14-APR-15:50 | 229.30 | 21-APR-04:10 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 166.87 | 31-MAY-17:00 | 170.11 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 228.10 | 28-JUN-16:00 | 83.54 | 21-JUN-05:55 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 205.17 | 19-JUL-13:00 | 84.14 | 01-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 216.97 | 25-AUG-14:00 | 98.26 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 183.71 | 08-SEP-15:00 | 103.90 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 167.42 | 01-OCT-13:00 | 274.11 | 25-OCT-06:05 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 65.19 | 01-NOV-15:00 | 354.45 | 23-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 25.67 | 21-DEC-15:00 | 370.45 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 228.10 | 370.45 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.31 | 31-JAN-17:00 | 296.18 | 01-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 237.02 | 01-FEB-05:03 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 | 15-MAR-15:40 | 295.15 | 26-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 | 14-APR-15:00 | 197.90 | 21-APR-04:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.11 | 31-MAY-17:00 | 151.63 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.06 | 28-JUN-16:00 | 75.21 | 21-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 19-JUL-13:00 | 77.46 | 01-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 | 25-AUG-14:00 | 90.83 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 08-SEP-15:00 | 88.55 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.71 | 01-OCT-13:00 | 233.37 | 25-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 01-NOV-15:00 | 304.40 | 23-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 | 21-DEC-15:00 | 319.40 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.06 | 319.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19776.74 | 27-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17935.66 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14538.12 | 29-MAR-04:15 | 23003.78 | 5862.24 | 6083.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14942.96 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14530.10 | 07-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15570.30 | 28-JUN-18:10 | 44729.58 | 58623.31 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21249.56 | 14-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23264.16 | 04-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26064.84 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25696.81 | 05-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25341.93 | 01-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24513.51 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14530.10 | 10223.90 | 5862.24 | 6083.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26064.84 | 44729.58 | 58623.31 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3647.53 | 14-JAN-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
February | 2664.63 | 01-FEB-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.47 |
March | 2777.21 | 18-MAR-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
April | 3126.82 | 14-APR-14:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 104.37 | 0.00 |
May | 2631.71 | 31-MAY-18:13 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 115.85 | 0.00 |
June | 3463.89 | 28-JUN-18:17 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
July | 3207.61 | 21-JUL-18:30 | 909.64 | 531.19 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 142.30 | 0.00 |
August | 3653.69 | 28-AUG-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 0.00 |
September | 3940.11 | 28-SEP-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.11 | 0.00 |
October | 3966.92 | 02-OCT-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 0.00 |
November | 3833.08 | 21-NOV-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
December | 3527.90 | 25-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2631.71 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3966.92 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 87.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1727.91 | 27-JAN-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
February | 1488.78 | 01-FEB-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.40 |
March | 1779.54 | 17-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
April | 2295.56 | 14-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 | 0.00 |
May | 2245.29 | 31-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 0.00 |
June | 2579.43 | 28-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.44 | 0.00 |
July | 2442.14 | 20-JUL-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 0.00 |
August | 2481.87 | 15-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 0.00 |
September | 2441.67 | 07-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 0.00 |
October | 2271.61 | 05-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
November | 1984.25 | 01-NOV-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
December | 1636.32 | 26-DEC-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1488.78 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2579.43 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 60.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1094.58 | 08-JAN-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
February | 1096.94 | 01-FEB-07:03 | 381.89 | 1140.29 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.45 |
March | 1149.63 | 18-MAR-18:10 | 1336.61 | 3724.96 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 0.00 |
April | 1598.33 | 25-APR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.77 | 0.00 |
May | 1846.86 | 18-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 0.00 |
June | 2514.27 | 28-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 120.54 | 0.00 |
July | 2401.71 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 | 0.00 |
August | 2279.84 | 15-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 | 0.00 |
September | 2161.56 | 08-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 | 0.00 |
October | 1978.81 | 02-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 0.00 |
November | 1183.22 | 02-NOV-18:04 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
December | 1094.29 | 30-DEC-06:08 | 1113.84 | 1140.29 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1094.29 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2514.27 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 | 180.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 638.13 | 08-JAN-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 |
February | 625.29 | 01-FEB-07:03 | 293.76 | 419.72 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.72 |
March | 668.55 | 18-MAR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 0.00 |
April | 787.60 | 15-APR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 | 0.00 |
May | 832.41 | 09-MAY-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 | 0.00 |
June | 1292.25 | 28-JUN-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 | 0.00 |
July | 1201.95 | 21-JUL-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 69.81 | 0.00 |
August | 1121.19 | 15-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | 0.00 |
September | 1052.56 | 08-SEP-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 0.00 |
October | 917.68 | 03-OCT-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 0.00 |
November | 678.16 | 02-NOV-18:04 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 0.00 |
December | 632.38 | 30-DEC-06:08 | 856.80 | 419.71 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 625.29 | 171.36 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1292.25 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 | 103.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37931.12 | 27-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 95.20 |
February | 37578.70 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 151.20 |
March | 38284.55 | 16-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
April | 39189.55 | 14-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 90.16 | 0.00 |
May | 39309.65 | 18-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.94 | 0.00 |
June | 39944.02 | 28-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 164.61 | 0.00 |
July | 39774.62 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 165.23 | 0.00 |
August | 39672.81 | 15-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 140.45 | 0.00 |
September | 39517.26 | 08-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 125.97 | 0.00 |
October | 39131.45 | 03-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.90 | 0.00 |
November | 38248.15 | 01-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 |
December | 37655.46 | 22-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 137.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37578.70 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39944.02 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 165.23 | 151.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13941.73 | 14-JAN-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 58.71 | 0.00 |
February | 10617.40 | 25-FEB-14:25 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 |
March | 10893.72 | 18-MAR-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
April | 12170.36 | 14-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 0.00 |
May | 11730.15 | 09-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 111.58 | 0.00 |
June | 13307.60 | 28-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 241.59 | 0.00 |
July | 13206.64 | 21-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 224.41 | 0.00 |
August | 13080.43 | 15-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 198.18 | 0.00 |
September | 13908.25 | 28-SEP-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 304.50 | 0.00 |
October | 13856.97 | 05-OCT-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 227.15 | 0.00 |
November | 14250.92 | 01-NOV-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 111.82 | 0.00 |
December | 13473.53 | 25-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10617.40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14250.92 | 59766.00 | 1134.35 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 304.50 | 155.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35816.79 | 27-JAN-21:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.47 |
February | 32334.79 | 01-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.70 |
March | 36439.21 | 17-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.79 |
April | 42341.34 | 14-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 307.22 | 0.00 |
May | 41817.64 | 09-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 318.66 | 0.00 |
June | 46920.63 | 28-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 690.13 | 0.00 |
July | 46170.82 | 21-JUL-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 807.13 | 0.00 |
August | 45721.23 | 15-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 566.12 | 0.00 |
September | 45696.66 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 573.45 | 0.00 |
October | 43781.47 | 03-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 363.19 | 0.00 |
November | 38808.25 | 01-NOV-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.97 |
December | 35035.56 | 26-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32334.79 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46920.63 | 45622.98 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 807.13 | 1012.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2380.23 | 31-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 | 0.00 |
February | 2343.32 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 |
March | 2362.17 | 23-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 11.64 | 0.00 |
April | 2440.14 | 14-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 61.85 | 0.00 |
May | 2434.09 | 31-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | 0.00 |
June | 2478.34 | 27-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 | 0.00 |
July | 2452.23 | 01-JUL-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 75.45 | 0.00 |
August | 2464.46 | 25-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 | 0.00 |
September | 2421.49 | 12-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 0.00 |
October | 2429.40 | 15-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 47.97 | 0.00 |
November | 2406.79 | 20-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 | 0.00 |
December | 2378.53 | 22-DEC-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2343.32 | 378.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2478.34 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 | 24.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2304.00 | 31-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.92 | 0.00 |
February | 2276.10 | 28-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
March | 2320.67 | 23-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
April | 2424.15 | 26-APR-08:41 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 0.00 |
May | 2585.16 | 08-MAY-08:61 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 0.00 |
June | 2634.26 | 14-JUN-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 0.00 |
July | 2718.02 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
August | 2462.85 | 24-AUG-08:21 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 0.00 |
September | 2399.51 | 06-SEP-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 | 0.00 |
October | 2369.83 | 15-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 0.00 |
November | 2330.22 | 20-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | 0.00 |
December | 2288.66 | 25-DEC-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2276.10 | 288.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2718.02 | 970.20 | 1108.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 | 23.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 615.61 | 14-JAN-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
February | 464.63 | 01-FEB-14:15 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
March | 427.45 | 18-MAR-14:10 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
April | 440.48 | 14-APR-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 0.00 |
May | 371.35 | 09-MAY-17:13 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
June | 465.22 | 28-JUN-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 0.00 |
July | 449.71 | 21-JUL-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 |
August | 501.79 | 27-AUG-14:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 0.00 |
September | 582.71 | 28-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
October | 607.15 | 18-OCT-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
November | 638.80 | 20-NOV-14:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
December | 610.09 | 25-DEC-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 371.35 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 638.80 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 19.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1522.26 | 31-JAN-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
February | 1409.40 | 27-FEB-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
March | 1556.10 | 15-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 |
April | 1565.33 | 30-APR-08:51 | 432.00 | 500.97 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 |
May | 1679.80 | 20-MAY-08:61 | 486.00 | 563.59 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
June | 1725.12 | 11-JUN-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 |
July | 1728.72 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
August | 1575.61 | 24-AUG-08:21 | 288.00 | 393.62 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 0.00 |
September | 1561.80 | 29-SEP-08:21 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 0.00 |
October | 1555.64 | 19-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
November | 1526.60 | 10-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 0.00 |
December | 1457.41 | 23-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1409.40 | 252.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1728.72 | 970.20 | 696.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 14.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2090.38 | 31-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 37.47 | 0.00 |
February | 2055.21 | 18-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 |
March | 2095.06 | 23-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 0.00 |
April | 2151.51 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 | 0.00 |
May | 2177.67 | 20-MAY-08:61 | 486.00 | 896.53 | 1469.76 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 0.00 |
June | 2182.49 | 14-JUN-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
July | 2193.95 | 22-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 | 0.00 |
August | 2196.55 | 13-AUG-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | 0.00 |
September | 2160.75 | 09-SEP-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 34.54 | 0.00 |
October | 2143.88 | 04-OCT-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 |
November | 2119.38 | 10-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 |
December | 2077.59 | 25-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2055.21 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2196.55 | 680.40 | 896.53 | 1469.76 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 | 10.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2087.69 | 27-JAN-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 |
February | 2007.73 | 26-FEB-09:01 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 |
March | 2086.62 | 18-MAR-08:51 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.92 |
April | 2473.79 | 13-APR-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 |
May | 2679.62 | 21-MAY-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 |
June | 2514.26 | 13-JUN-08:11 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 |
July | 2518.61 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 0.00 |
August | 2548.42 | 24-AUG-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 |
September | 2438.30 | 15-SEP-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
October | 2414.12 | 17-OCT-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
November | 2248.08 | 10-NOV-09:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 |
December | 2003.95 | 23-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2003.95 | 252.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2679.62 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 73.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2020.35 | 29-JAN-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
February | 1987.14 | 01-FEB-07:03 | 3017.81 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.12 |
March | 2058.85 | 18-MAR-10:45 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 0.00 |
April | 2441.43 | 15-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 0.00 |
May | 2456.88 | 20-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 | 0.00 |
June | 3878.15 | 28-JUN-19:10 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 0.00 |
July | 3432.88 | 21-JUL-19:10 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.44 | 0.00 |
August | 3277.63 | 15-AUG-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 0.00 |
September | 3113.76 | 08-SEP-18:13 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 | 0.00 |
October | 2810.06 | 05-OCT-18:13 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 | 0.00 |
November | 2107.94 | 01-NOV-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 0.00 |
December | 2048.13 | 30-DEC-06:08 | 8801.94 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1987.14 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3878.15 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 142.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2514.80 | 05-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 0.00 |
February | 2471.77 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 |
March | 2487.37 | 23-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
April | 2587.70 | 14-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 | 0.00 |
May | 2576.88 | 31-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 | 0.00 |
June | 2631.56 | 27-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 96.59 | 0.00 |
July | 2594.48 | 01-JUL-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 75.01 | 0.00 |
August | 2615.02 | 25-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 90.90 | 0.00 |
September | 2563.83 | 04-SEP-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 51.48 | 0.00 |
October | 2567.23 | 18-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
November | 2547.85 | 20-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 | 0.00 |
December | 2516.34 | 22-DEC-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2471.77 | 378.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2631.56 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 96.59 | 24.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2419.76 | 31-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 | 0.00 |
February | 2391.59 | 28-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 |
March | 2440.59 | 23-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 0.00 |
April | 2561.14 | 14-APR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 | 0.00 |
May | 2680.85 | 08-MAY-08:61 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 0.00 |
June | 2730.08 | 14-JUN-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
July | 2818.27 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
August | 2594.07 | 25-AUG-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 | 0.00 |
September | 2526.75 | 06-SEP-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
October | 2497.91 | 15-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 0.00 |
November | 2455.66 | 20-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | 0.00 |
December | 2407.51 | 22-DEC-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2391.59 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2818.27 | 970.20 | 1108.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 | 23.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2407.23 | 05-JAN-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
February | 2368.93 | 28-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
March | 2368.81 | 31-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
April | 2407.22 | 14-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 0.00 |
May | 2389.06 | 09-MAY-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 0.00 |
June | 2397.11 | 08-JUN-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 | 0.00 |
July | 2390.94 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 |
August | 2413.80 | 26-AUG-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 0.00 |
September | 1907.61 | 24-SEP-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
October | 2423.56 | 18-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 0.00 |
November | 2407.63 | 20-NOV-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 0.00 |
December | 2403.22 | 22-DEC-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1907.61 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2423.56 | 680.40 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 11.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19413.08 | 06-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 |
February | 18979.78 | 21-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.61 |
March | 20982.82 | 17-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 |
April | 23048.39 | 14-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 0.00 |
May | 23273.35 | 09-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 | 0.00 |
June | 24926.81 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.71 | 0.00 |
July | 24618.20 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 139.94 | 0.00 |
August | 24161.78 | 10-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 0.00 |
September | 23932.67 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 0.00 |
October | 23108.32 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 | 0.00 |
November | 20842.41 | 02-NOV-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.75 |
December | 19001.08 | 26-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18979.78 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24926.81 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 148.71 | 157.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21078.48 | 06-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 |
February | 20691.79 | 21-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.63 |
March | 22426.74 | 17-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 |
April | 24227.13 | 14-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 0.00 |
May | 24471.43 | 09-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.55 | 0.00 |
June | 26104.52 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.69 | 0.00 |
July | 25794.38 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 139.92 | 0.00 |
August | 25341.77 | 10-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 125.43 | 0.00 |
September | 25088.31 | 07-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 119.32 | 0.00 |
October | 24259.03 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 | 0.00 |
November | 22196.53 | 02-NOV-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.68 |
December | 20560.65 | 26-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20560.65 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26104.52 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.69 | 157.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28286.44 | 29-JAN-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 |
February | 28173.45 | 18-FEB-11:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 |
March | 29179.13 | 18-MAR-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
April | 30543.93 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 78.25 | 0.00 |
May | 30743.59 | 07-MAY-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 78.57 | 0.00 |
June | 31519.36 | 18-JUN-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 148.97 | 0.00 |
July | 31508.52 | 22-JUL-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 151.80 | 0.00 |
August | 31553.99 | 13-AUG-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 124.54 | 0.00 |
September | 31352.06 | 09-SEP-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 122.91 | 0.00 |
October | 30605.03 | 02-OCT-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 112.74 | 0.00 |
November | 29048.34 | 01-NOV-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 3.22 | 0.00 |
December | 28148.54 | 25-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28148.54 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31553.99 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 151.80 | 65.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4133.72 | 29-JAN-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
February | 3892.14 | 26-FEB-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
March | 4455.59 | 18-MAR-17:12 | 6387.84 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 0.00 |
April | 6420.37 | 14-APR-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 | 0.00 |
May | 6097.25 | 09-MAY-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 0.00 |
June | 8110.12 | 28-JUN-18:17 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 0.00 |
July | 7444.40 | 20-JUL-18:17 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.78 | 0.00 |
August | 7485.34 | 11-AUG-15:25 | 2661.60 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.76 | 0.00 |
September | 7512.76 | 07-SEP-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.33 | 0.00 |
October | 7057.85 | 02-OCT-13:10 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 0.00 |
November | 4431.06 | 01-NOV-17:12 | 5323.20 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 0.00 |
December | 4014.22 | 25-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3892.14 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8110.12 | 9315.60 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 94.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.417775E+12 | 303800.14 | 31-JAN-19:10 | 0.493532E+12 | 455659.66 | 01-JAN-23:40 |
February | 0.332170E+12 | 252306.50 | 09-FEB-20:10 | 0.466039E+12 | 413875.04 | 04-FEB-20:10 |
March | 0.408923E+12 | 313115.92 | 16-MAR-18:30 | 0.465804E+12 | 435439.73 | 25-MAR-22:00 |
April | 0.513242E+12 | 372812.85 | 14-APR-19:19 | 0.374000E+12 | 341152.29 | 04-APR-17:49 |
May | 0.577644E+12 | 382755.09 | 31-MAY-19:19 | 0.369976E+12 | 318083.62 | 01-MAY-17:19 |
June | 0.648518E+12 | 436084.89 | 28-JUN-19:30 | 0.347779E+12 | 314047.92 | 01-JUN-17:19 |
July | 0.677426E+12 | 440906.66 | 21-JUL-19:00 | 0.353958E+12 | 311130.11 | 05-JUL-17:19 |
August | 0.669898E+12 | 422799.50 | 15-AUG-19:10 | 0.355781E+12 | 312345.51 | 31-AUG-17:30 |
September | 0.622554E+12 | 426732.35 | 08-SEP-19:10 | 0.351738E+12 | 315588.29 | 29-SEP-17:49 |
October | 0.507280E+12 | 388378.19 | 03-OCT-19:10 | 0.398466E+12 | 325626.56 | 31-OCT-17:49 |
November | 0.412329E+12 | 317421.27 | 01-NOV-18:10 | 0.437784E+12 | 468619.09 | 23-NOV-20:40 |
December | 0.391021E+12 | 263543.26 | 26-DEC-20:10 | 0.524760E+12 | 485244.58 | 07-DEC-21:10 |
Annual Sum or Average | 0.617878E+13 | 0.493962E+13 | ||||
Minimum of Months | 0.332170E+12 | 252306.50 | 0.347779E+12 | 311130.11 | ||
Maximum of Months | 0.677426E+12 | 440906.66 | 0.524760E+12 | 485244.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670654E+11 | 0.190037E+11 | 0.140828E+12 | 0.544239E+11 | 0.442786E+11 | 0.766689E+10 | 0.00 | 0.669989E+11 | 0.00 | 0.00 | 0.460682E+10 | 0.770454E+10 | 0.00 |
February | 0.605156E+11 | 0.163016E+11 | 0.127191E+12 | 0.491571E+11 | 0.361965E+11 | 0.634340E+10 | 0.00 | 0.225066E+11 | 0.00 | 0.00 | 0.224882E+10 | 0.696207E+10 | 0.00 |
March | 0.665879E+11 | 0.167606E+11 | 0.140882E+12 | 0.544262E+11 | 0.417874E+11 | 0.756772E+10 | 0.00 | 0.628552E+11 | 0.00 | 0.00 | 0.512932E+10 | 0.770305E+10 | 0.00 |
April | 0.641350E+11 | 0.149024E+11 | 0.136245E+12 | 0.526676E+11 | 0.493785E+11 | 0.778389E+10 | 0.00 | 0.162856E+12 | 0.00 | 0.00 | 0.127881E+11 | 0.746499E+10 | 0.00 |
May | 0.660045E+11 | 0.142657E+11 | 0.140860E+12 | 0.544245E+11 | 0.539044E+11 | 0.810204E+10 | 0.00 | 0.210404E+12 | 0.00 | 0.00 | 0.167803E+11 | 0.770426E+10 | 0.00 |
June | 0.635945E+11 | 0.133329E+11 | 0.136336E+12 | 0.526696E+11 | 0.612551E+11 | 0.830487E+10 | 0.00 | 0.278566E+12 | 0.00 | 0.00 | 0.219209E+11 | 0.745688E+10 | 0.00 |
July | 0.658726E+11 | 0.139548E+11 | 0.140770E+12 | 0.544220E+11 | 0.615471E+11 | 0.868569E+10 | 0.00 | 0.295075E+12 | 0.00 | 0.00 | 0.240842E+11 | 0.771237E+10 | 0.00 |
August | 0.663169E+11 | 0.148876E+11 | 0.140892E+12 | 0.544261E+11 | 0.617344E+11 | 0.864767E+10 | 0.00 | 0.287295E+12 | 0.00 | 0.00 | 0.226514E+11 | 0.770437E+10 | 0.00 |
September | 0.643461E+11 | 0.156353E+11 | 0.136256E+12 | 0.526678E+11 | 0.590961E+11 | 0.836493E+10 | 0.00 | 0.254219E+12 | 0.00 | 0.00 | 0.193359E+11 | 0.746622E+10 | 0.00 |
October | 0.668577E+11 | 0.175305E+11 | 0.140818E+12 | 0.544237E+11 | 0.527798E+11 | 0.808510E+10 | 0.00 | 0.144364E+12 | 0.00 | 0.00 | 0.948297E+10 | 0.770300E+10 | 0.00 |
November | 0.648668E+11 | 0.181153E+11 | 0.136330E+12 | 0.526689E+11 | 0.448162E+11 | 0.738240E+10 | 0.00 | 0.712990E+11 | 0.00 | 0.00 | 0.435216E+10 | 0.744905E+10 | 0.00 |
December | 0.670797E+11 | 0.193664E+11 | 0.140770E+12 | 0.544227E+11 | 0.433504E+11 | 0.699378E+10 | 0.00 | 0.399944E+11 | 0.00 | 0.00 | 0.616848E+10 | 0.771271E+10 | 0.00 |
Annual Sum or Average | 0.783243E+12 | 0.194057E+12 | 0.165818E+13 | 0.640800E+12 | 0.610124E+12 | 0.939284E+11 | 0.00 | 0.189643E+13 | 0.00 | 0.00 | 0.149549E+12 | 0.907435E+11 | 0.00 |
Minimum of Months | 0.605156E+11 | 0.133329E+11 | 0.127191E+12 | 0.491571E+11 | 0.361965E+11 | 0.634340E+10 | 0.00 | 0.225066E+11 | 0.00 | 0.00 | 0.224882E+10 | 0.696207E+10 | 0.00 |
Maximum of Months | 0.670797E+11 | 0.193664E+11 | 0.140892E+12 | 0.544262E+11 | 0.617344E+11 | 0.868569E+10 | 0.00 | 0.295075E+12 | 0.00 | 0.00 | 0.240842E+11 | 0.771271E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.898172E+11 | 0.00 | 0.251797E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.102789E+12 | 0.00 | 0.226046E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.710245E+11 | 0.00 | 0.242756E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.370900E+10 | 0.00 | 0.223335E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.136014E+09 | 0.00 | 0.217862E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 15000162.34 | 0.00 | 0.200650E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 60499870.41 | 0.00 | 0.202077E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 75295292.75 | 0.00 | 0.203667E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 98916253.39 | 0.00 | 0.204669E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.230569E+11 | 0.00 | 0.223506E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.619060E+11 | 0.00 | 0.228787E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.126189E+12 | 0.00 | 0.246750E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.478877E+12 | 0.00 | 0.267190E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 15000162.34 | 0.00 | 0.200650E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.126189E+12 | 0.00 | 0.251797E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 32438.53 | 31-JAN-22:10 | 3504.59 | 01-JAN-09:09 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 26165.15 | 01-FEB-22:10 | 3490.16 | 08-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 31966.90 | 17-MAR-21:00 | 3565.82 | 17-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.97 | 03-APR-06:19 | 39808.68 | 14-APR-21:10 | 3921.67 | 25-APR-19:49 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.86 | 26-MAY-06:19 | 40801.54 | 10-MAY-21:10 | 3685.96 | 29-MAY-20:49 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.43 | 02-JUN-06:19 | 46923.20 | 29-JUN-21:10 | 4495.93 | 28-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39169.68 | 14-JUL-06:19 | 48616.54 | 07-JUL-21:10 | 4271.36 | 07-JUL-20:19 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.97 | 04-AUG-06:19 | 48920.38 | 25-AUG-21:10 | 4211.90 | 27-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 01-SEP-06:19 | 50214.83 | 07-SEP-21:10 | 4216.11 | 18-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 48331.16 | 06-OCT-21:10 | 4028.91 | 05-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 36087.48 | 01-NOV-21:00 | 3631.86 | 01-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 32481.20 | 26-DEC-22:10 | 3507.76 | 07-DEC-09:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.43 | 26165.15 | 3490.16 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 50214.83 | 4495.93 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 104303.82 | 31-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4738.65 | 02-JAN-19:10 | 0.00 |
February | 66876.49 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-07:19 | 4738.26 | 22-FEB-19:10 | 0.00 |
March | 101543.27 | 16-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 09-MAR-13:50 | 4738.31 | 31-MAR-18:49 | 0.00 |
April | 140314.26 | 14-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-08:50 | 4738.67 | 27-APR-18:10 | 0.00 |
May | 156306.77 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-09:39 | 4738.29 | 16-MAY-06:30 | 0.00 |
June | 203708.69 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.72 | 01-JUN-18:10 | 0.00 |
July | 184544.51 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.58 | 20-JUL-18:10 | 0.00 |
August | 184722.41 | 25-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.57 | 10-AUG-18:10 | 0.00 |
September | 174987.77 | 08-SEP-18:19 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.60 | 28-SEP-18:10 | 0.00 |
October | 149395.51 | 01-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.56 | 05-OCT-18:10 | 0.00 |
November | 112138.14 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-12:09 | 4738.03 | 10-NOV-19:10 | 0.00 |
December | 87845.09 | 25-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 02-DEC-13:09 | 4738.39 | 20-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 66876.49 | 0.00 | 0.00 | 9938.94 | 4738.03 | 0.00 | |||
Maximum of Months | 203708.69 | 0.00 | 0.00 | 9938.94 | 4738.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 303800.14 | 31-JAN-19:10 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 27904.50 | 3154.40 | 0.00 | 86408.21 | 0.00 |
February | 252306.50 | 09-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20981.28 | 2882.04 | 0.00 | 27478.04 | 0.00 |
March | 313115.92 | 16-MAR-18:30 | 57474.69 | 77573.37 | 12338.45 | 31354.49 | 25593.83 | 3560.48 | 0.00 | 88383.63 | 0.00 |
April | 372812.85 | 14-APR-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 33151.09 | 3321.23 | 0.00 | 125625.99 | 0.00 |
May | 382755.09 | 31-MAY-19:19 | 64632.59 | 86439.81 | 12338.45 | 31551.77 | 32602.02 | 3262.66 | 0.00 | 135843.58 | 0.00 |
June | 436084.89 | 28-JUN-19:30 | 64632.59 | 86439.81 | 12338.45 | 31552.47 | 39015.52 | 4404.44 | 0.00 | 181830.45 | 0.00 |
July | 440906.66 | 21-JUL-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 42059.48 | 3793.98 | 0.00 | 184526.64 | 0.00 |
August | 422799.50 | 15-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 41192.04 | 3732.41 | 0.00 | 167423.96 | 0.00 |
September | 426732.35 | 08-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 42019.26 | 3739.04 | 0.00 | 170647.98 | 0.00 |
October | 388378.19 | 03-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 38611.45 | 3535.80 | 0.00 | 135774.56 | 0.00 |
November | 317421.27 | 01-NOV-18:10 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 29921.79 | 3631.86 | 0.00 | 96736.77 | 0.00 |
December | 263543.26 | 26-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 26047.80 | 2905.24 | 0.00 | 34178.66 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 252306.50 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 20981.28 | 2882.04 | 0.00 | 27478.04 | 0.00 | |
Maximum of Months | 440906.66 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 42059.48 | 4404.44 | 0.00 | 184526.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 191614.88 | 02-JAN-04:10 | 0.00 | 245489.84 | 26-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 183800.65 | 08-FEB-07:10 | 0.00 | 245341.38 | 01-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 184585.77 | 27-MAR-01:30 | 0.00 | 244516.45 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 136100.95 | 21-APR-06:10 | 0.00 | 237616.57 | 01-APR-21:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 11008.85 | 01-MAY-03:00 | 0.00 | 214034.25 | 01-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 2919.81 | 05-JUN-08:09 | 0.00 | 210200.39 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4518.99 | 10-JUL-08:09 | 0.00 | 207303.64 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4405.82 | 10-AUG-08:09 | 0.00 | 208508.10 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 5137.54 | 12-SEP-08:09 | 0.00 | 211811.08 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 175428.55 | 12-OCT-06:10 | 0.00 | 223889.98 | 31-OCT-20:10 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 185353.75 | 24-NOV-01:00 | 0.00 | 243496.59 | 29-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 188185.84 | 06-DEC-09:30 | 0.00 | 244944.84 | 28-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 2919.81 | 0.00 | 207303.64 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 191614.88 | 0.00 | 245489.84 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.85 | 4.67 | 21.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.90 | 3.17 | 21.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 22.14 | 25.33 | 22.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 21.87 | 27.17 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 22.51 | 106.17 | 22.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 22.18 | 40.50 | 22.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 22.21 | 47.67 | 22.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 22.13 | 29.67 | 22.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 22.24 | 15.00 | 22.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.94 | 4.33 | 21.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
Annual Sum or Average | 0.00 | 0.00 | 304.83 | 22.25 | 304.83 | 22.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.83 | 0.50 | 21.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 22.51 | 106.17 | 22.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.74 | 1.17 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 22.12 | 19.17 | 22.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 21.88 | 29.17 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 22.57 | 118.83 | 22.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 22.18 | 45.67 | 22.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 22.11 | 48.83 | 22.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 22.01 | 23.17 | 22.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 22.08 | 8.67 | 22.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 295.00 | 22.27 | 295.00 | 22.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 22.57 | 118.83 | 22.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.78 | 4.67 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 21.76 | 7.33 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.78 | 4.67 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 21.92 | 15.83 | 21.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 21.96 | 20.83 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 118.67 | 22.20 | 118.67 | 22.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 21.97 | 45.50 | 21.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 21.99 | 43.33 | 21.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 21.96 | 29.50 | 21.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 22.02 | 14.00 | 22.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 291.67 | 22.06 | 291.67 | 22.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 118.67 | 22.20 | 118.67 | 22.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.90 | 1.67 | 21.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 22.22 | 20.83 | 22.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 22.31 | 36.00 | 22.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 147.33 | 22.38 | 147.33 | 22.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 22.05 | 56.67 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 22.04 | 43.50 | 22.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 22.05 | 29.00 | 22.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22.18 | 10.17 | 22.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.86 | 0.67 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 345.83 | 22.23 | 345.83 | 22.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 147.33 | 22.38 | 147.33 | 22.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.83 | 5.17 | 21.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.89 | 5.67 | 21.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 22.15 | 34.17 | 22.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 21.93 | 40.33 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 | 22.71 | 121.33 | 22.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 22.26 | 52.33 | 22.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 22.36 | 51.00 | 22.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 22.21 | 34.33 | 22.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 22.28 | 16.50 | 22.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.98 | 5.17 | 21.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.83 | 0.83 | 21.83 |
Annual Sum or Average | 0.00 | 0.00 | 367.33 | 22.35 | 367.33 | 22.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.83 | 0.50 | 21.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 | 22.71 | 121.33 | 22.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.15 | 23.83 | 22.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 21.92 | 42.00 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 131.83 | 22.79 | 131.83 | 22.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 22.31 | 55.67 | 22.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 22.26 | 50.50 | 22.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 22.07 | 26.67 | 22.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.14 | 8.83 | 22.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 341.00 | 22.40 | 341.00 | 22.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 131.83 | 22.79 | 131.83 | 22.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.89 | 2.17 | 21.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.73 | 2.00 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.71 | 1.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.82 | 3.00 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.90 | 4.50 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.93 | 3.67 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.92 | 1.67 | 21.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.33 | 21.85 | 19.33 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.93 | 4.50 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 605.00 | 23.80 | 8.67 | 23.80 | 0.00 | 23.80 |
February | 639.83 | 23.24 | 1.83 | 23.24 | 0.00 | 23.24 |
March | 744.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
April | 720.00 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
May | 744.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
June | 719.17 | 23.02 | 2.00 | 23.02 | 2.00 | 23.02 |
July | 314.00 | 23.82 | 450.33 | 23.89 | 193.17 | 23.91 |
August | 260.33 | 23.97 | 587.33 | 23.95 | 197.00 | 23.96 |
September | 123.67 | 24.00 | 543.83 | 24.00 | 122.83 | 24.00 |
October | 295.67 | 24.00 | 149.67 | 24.00 | 22.83 | 24.00 |
November | 376.17 | 24.00 | 155.67 | 24.00 | 29.67 | 24.00 |
December | 681.50 | 23.99 | 5.67 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 6223.33 | 23.36 | 1905.00 | 23.50 | 567.50 | 23.53 |
Minimum of Months | 123.67 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
Maximum of Months | 744.00 | 24.00 | 587.33 | 24.00 | 197.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 527.50 | 22.18 | 107.33 | 22.49 | 0.00 | 22.49 |
February | 589.33 | 21.57 | 28.17 | 21.68 | 0.00 | 21.68 |
March | 659.00 | 21.83 | 40.67 | 21.89 | 15.00 | 21.87 |
April | 357.67 | 22.69 | 92.83 | 22.96 | 0.00 | 22.96 |
May | 347.50 | 22.94 | 21.50 | 23.00 | 0.00 | 23.00 |
June | 105.00 | 23.33 | 436.00 | 23.86 | 0.33 | 23.86 |
July | 211.17 | 23.62 | 646.83 | 23.81 | 171.00 | 23.79 |
August | 214.33 | 23.55 | 671.67 | 23.76 | 184.83 | 23.73 |
September | 184.00 | 23.38 | 614.83 | 23.74 | 137.50 | 23.71 |
October | 373.67 | 22.47 | 244.67 | 23.05 | 24.00 | 23.07 |
November | 501.67 | 22.07 | 133.33 | 22.34 | 33.17 | 22.29 |
December | 594.50 | 21.78 | 92.33 | 21.88 | 45.17 | 21.83 |
Annual Sum or Average | 4665.33 | 22.31 | 3130.17 | 22.91 | 611.00 | 22.94 |
Minimum of Months | 105.00 | 21.57 | 21.50 | 21.68 | 0.00 | 21.68 |
Maximum of Months | 659.00 | 23.62 | 671.67 | 23.86 | 184.83 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 636.00 | 23.22 | 4.33 | 23.23 | 0.00 | 23.23 |
February | 619.50 | 22.73 | 10.50 | 22.74 | 6.33 | 22.75 |
March | 643.33 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
April | 417.17 | 23.57 | 13.17 | 23.59 | 0.00 | 23.59 |
May | 397.17 | 23.67 | 7.50 | 23.68 | 0.00 | 23.68 |
June | 88.83 | 23.68 | 239.67 | 23.91 | 2.33 | 23.91 |
July | 256.00 | 23.97 | 577.00 | 23.94 | 206.50 | 23.95 |
August | 236.33 | 23.97 | 620.83 | 23.94 | 228.33 | 23.94 |
September | 177.00 | 23.97 | 578.33 | 23.93 | 174.67 | 23.94 |
October | 421.33 | 23.46 | 153.83 | 23.58 | 35.67 | 23.61 |
November | 568.00 | 23.24 | 96.67 | 23.30 | 48.67 | 23.29 |
December | 734.33 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
Annual Sum or Average | 5195.00 | 23.27 | 2301.83 | 23.47 | 702.50 | 23.51 |
Minimum of Months | 88.83 | 22.73 | 0.00 | 22.74 | 0.00 | 22.75 |
Maximum of Months | 734.33 | 23.97 | 620.83 | 23.94 | 228.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.04 | 5.17 | 22.03 | 5.17 | 22.03 |
February | 672.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
March | 744.00 | 22.00 | 4.83 | 22.00 | 4.83 | 21.99 |
April | 703.50 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
May | 691.50 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
June | 205.67 | 23.97 | 60.67 | 23.98 | 0.00 | 23.98 |
July | 92.50 | 23.99 | 534.33 | 23.98 | 13.33 | 23.98 |
August | 59.83 | 23.93 | 573.00 | 23.96 | 0.33 | 23.96 |
September | 79.17 | 23.80 | 429.17 | 23.91 | 17.67 | 23.91 |
October | 595.00 | 22.87 | 93.17 | 23.02 | 1.50 | 23.02 |
November | 718.67 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
December | 744.00 | 21.61 | 44.00 | 21.57 | 44.00 | 21.54 |
Annual Sum or Average | 6049.83 | 22.51 | 1744.33 | 22.82 | 86.83 | 22.81 |
Minimum of Months | 59.83 | 21.61 | 0.00 | 21.57 | 0.00 | 21.54 |
Maximum of Months | 744.00 | 23.99 | 573.00 | 23.98 | 44.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.89 | 1.17 | 21.89 | 1.17 | 21.89 |
February | 672.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
March | 744.00 | 21.83 | 4.17 | 21.82 | 4.17 | 21.82 |
April | 715.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
May | 728.83 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
June | 247.50 | 23.92 | 52.83 | 23.93 | 0.00 | 23.93 |
July | 127.33 | 23.94 | 525.33 | 23.95 | 32.33 | 23.95 |
August | 91.00 | 23.81 | 537.17 | 23.91 | 21.67 | 23.91 |
September | 142.00 | 23.70 | 378.83 | 23.83 | 39.67 | 23.82 |
October | 611.67 | 22.70 | 81.33 | 22.84 | 4.00 | 22.85 |
November | 720.00 | 22.08 | 7.50 | 22.09 | 7.50 | 22.09 |
December | 744.00 | 21.47 | 57.83 | 21.44 | 57.83 | 21.41 |
Annual Sum or Average | 6287.50 | 22.41 | 1646.17 | 22.70 | 168.33 | 22.70 |
Minimum of Months | 91.00 | 21.47 | 0.00 | 21.44 | 0.00 | 21.41 |
Maximum of Months | 744.00 | 23.94 | 537.17 | 23.95 | 57.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.33 | 23.48 | 636.83 | 23.59 | 185.00 | 23.66 |
February | 249.17 | 23.71 | 604.00 | 23.58 | 222.50 | 23.66 |
March | 257.83 | 23.68 | 650.83 | 23.61 | 226.33 | 23.68 |
April | 237.83 | 23.88 | 645.67 | 23.69 | 225.83 | 23.76 |
May | 248.33 | 23.99 | 675.50 | 23.73 | 246.83 | 23.78 |
June | 339.50 | 23.98 | 695.83 | 23.70 | 339.50 | 23.77 |
July | 428.67 | 23.91 | 734.50 | 23.66 | 428.67 | 23.73 |
August | 434.83 | 23.91 | 737.33 | 23.64 | 434.83 | 23.71 |
September | 394.17 | 23.94 | 716.33 | 23.64 | 394.17 | 23.72 |
October | 279.50 | 23.79 | 677.33 | 23.64 | 258.00 | 23.72 |
November | 246.67 | 23.65 | 640.00 | 23.59 | 213.00 | 23.67 |
December | 215.33 | 23.17 | 605.67 | 23.52 | 146.50 | 23.60 |
Annual Sum or Average | 3564.17 | 23.79 | 8019.83 | 23.64 | 3321.17 | 23.71 |
Minimum of Months | 215.33 | 23.17 | 604.00 | 23.52 | 146.50 | 23.60 |
Maximum of Months | 434.83 | 23.99 | 737.33 | 23.73 | 434.83 | 23.78 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 195.33 | 23.16 | 271.17 | 23.63 | 11.17 | 23.62 |
February | 366.67 | 22.68 | 196.33 | 23.08 | 47.17 | 23.11 |
March | 391.17 | 22.78 | 170.50 | 23.13 | 6.33 | 23.14 |
April | 140.33 | 23.18 | 273.33 | 23.71 | 0.00 | 23.71 |
May | 127.17 | 23.16 | 254.50 | 23.71 | 0.00 | 23.71 |
June | 25.67 | 23.58 | 550.67 | 23.95 | 14.00 | 23.96 |
July | 323.50 | 23.92 | 684.00 | 23.91 | 318.67 | 23.92 |
August | 362.67 | 23.90 | 711.50 | 23.91 | 360.50 | 23.91 |
September | 282.33 | 23.90 | 707.67 | 23.92 | 282.33 | 23.92 |
October | 174.50 | 23.43 | 415.00 | 23.80 | 59.67 | 23.81 |
November | 243.17 | 23.19 | 347.00 | 23.53 | 78.83 | 23.49 |
December | 418.33 | 23.09 | 128.83 | 23.30 | 0.00 | 23.30 |
Annual Sum or Average | 3050.83 | 23.30 | 4710.50 | 23.68 | 1178.67 | 23.70 |
Minimum of Months | 25.67 | 22.68 | 128.83 | 23.08 | 0.00 | 23.11 |
Maximum of Months | 418.33 | 23.92 | 711.50 | 23.95 | 360.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 339.33 | 23.48 | 39.17 | 23.52 | 9.17 | 23.52 |
February | 452.33 | 23.04 | 90.67 | 23.18 | 32.50 | 23.21 |
March | 457.67 | 23.08 | 51.67 | 23.17 | 5.00 | 23.17 |
April | 287.00 | 23.53 | 43.17 | 23.59 | 0.00 | 23.59 |
May | 257.67 | 23.49 | 32.33 | 23.55 | 0.00 | 23.55 |
June | 59.33 | 23.53 | 356.83 | 23.92 | 10.50 | 23.92 |
July | 300.33 | 23.96 | 624.50 | 23.92 | 286.50 | 23.93 |
August | 325.00 | 23.96 | 667.33 | 23.93 | 324.50 | 23.94 |
September | 246.33 | 23.96 | 668.33 | 23.94 | 246.33 | 23.94 |
October | 238.50 | 23.61 | 226.00 | 23.78 | 53.83 | 23.80 |
November | 358.33 | 23.52 | 180.33 | 23.60 | 75.67 | 23.59 |
December | 596.83 | 23.37 | 2.17 | 23.37 | 0.00 | 23.37 |
Annual Sum or Average | 3918.67 | 23.49 | 2982.50 | 23.67 | 1044.00 | 23.71 |
Minimum of Months | 59.33 | 23.04 | 2.17 | 23.17 | 0.00 | 23.17 |
Maximum of Months | 596.83 | 23.96 | 668.33 | 23.94 | 324.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 727.50 | 21.60 | 4.33 | 21.60 | 4.33 | 21.60 |
February | 667.67 | 21.42 | 1.17 | 21.42 | 1.17 | 21.42 |
March | 734.83 | 21.54 | 20.17 | 21.52 | 20.17 | 21.51 |
April | 666.67 | 21.64 | 1.00 | 21.64 | 0.00 | 21.64 |
May | 693.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
June | 540.17 | 21.56 | 54.67 | 21.72 | 0.00 | 21.72 |
July | 571.00 | 21.39 | 40.67 | 21.52 | 0.00 | 21.52 |
August | 547.50 | 21.35 | 55.83 | 21.52 | 0.50 | 21.52 |
September | 556.83 | 21.36 | 48.33 | 21.51 | 4.50 | 21.53 |
October | 673.33 | 21.56 | 15.17 | 21.59 | 0.00 | 21.59 |
November | 692.50 | 21.56 | 56.33 | 21.56 | 52.50 | 21.55 |
December | 740.33 | 21.52 | 112.83 | 21.46 | 112.83 | 21.42 |
Annual Sum or Average | 7811.33 | 21.52 | 410.50 | 21.56 | 196.00 | 21.55 |
Minimum of Months | 540.17 | 21.35 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 740.33 | 21.66 | 112.83 | 21.72 | 112.83 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.17 | 21.61 | 36.50 | 21.58 | 36.50 | 21.55 |
February | 671.33 | 21.28 | 9.33 | 21.27 | 9.33 | 21.26 |
March | 731.67 | 21.67 | 38.17 | 21.66 | 34.00 | 21.63 |
April | 673.67 | 21.88 | 8.67 | 21.93 | 0.00 | 21.93 |
May | 686.83 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
June | 506.50 | 21.66 | 68.67 | 21.87 | 0.00 | 21.87 |
July | 564.00 | 21.45 | 41.83 | 21.58 | 4.83 | 21.60 |
August | 554.67 | 21.52 | 58.50 | 21.72 | 16.33 | 21.77 |
September | 568.00 | 21.61 | 50.00 | 21.77 | 22.17 | 21.83 |
October | 695.33 | 21.83 | 6.00 | 21.84 | 3.17 | 21.85 |
November | 712.67 | 21.68 | 99.00 | 21.65 | 98.33 | 21.63 |
December | 744.00 | 21.28 | 291.00 | 21.18 | 291.00 | 21.12 |
Annual Sum or Average | 7851.83 | 21.61 | 707.67 | 21.64 | 515.67 | 21.62 |
Minimum of Months | 506.50 | 21.28 | 0.00 | 21.18 | 0.00 | 21.12 |
Maximum of Months | 744.00 | 21.88 | 291.00 | 21.93 | 291.00 | 21.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 9.83 | 21.42 | 9.83 | 21.41 |
February | 672.00 | 21.30 | 1.67 | 21.29 | 1.67 | 21.29 |
March | 744.00 | 21.60 | 4.00 | 21.60 | 4.00 | 21.59 |
April | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
June | 719.83 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
July | 743.17 | 21.77 | 1.67 | 21.78 | 1.67 | 21.78 |
August | 741.00 | 21.82 | 9.17 | 21.85 | 9.17 | 21.87 |
September | 717.83 | 21.87 | 11.50 | 21.89 | 11.50 | 21.92 |
October | 744.00 | 21.77 | 1.33 | 21.77 | 1.33 | 21.77 |
November | 720.00 | 21.52 | 47.67 | 21.52 | 47.67 | 21.53 |
December | 744.00 | 21.23 | 152.50 | 21.19 | 152.50 | 21.16 |
Annual Sum or Average | 8753.83 | 21.66 | 239.33 | 21.65 | 239.33 | 21.64 |
Minimum of Months | 672.00 | 21.23 | 0.00 | 21.19 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.87 | 152.50 | 21.89 | 152.50 | 21.92 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.69 | 8.17 | 21.68 | 8.17 | 21.68 |
February | 672.00 | 21.52 | 1.83 | 21.52 | 1.83 | 21.52 |
March | 739.67 | 21.64 | 16.17 | 21.63 | 16.17 | 21.62 |
April | 683.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 707.83 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 503.33 | 21.42 | 36.00 | 21.55 | 0.00 | 21.55 |
July | 554.33 | 21.33 | 83.50 | 21.59 | 0.00 | 21.59 |
August | 539.00 | 21.27 | 98.00 | 21.58 | 0.17 | 21.59 |
September | 543.17 | 21.31 | 52.67 | 21.48 | 2.17 | 21.49 |
October | 678.33 | 21.60 | 16.00 | 21.64 | 0.00 | 21.64 |
November | 710.67 | 21.64 | 63.17 | 21.61 | 63.17 | 21.59 |
December | 744.00 | 21.60 | 107.00 | 21.53 | 107.00 | 21.49 |
Annual Sum or Average | 7819.33 | 21.55 | 482.50 | 21.60 | 198.67 | 21.59 |
Minimum of Months | 503.33 | 21.27 | 0.00 | 21.48 | 0.00 | 21.49 |
Maximum of Months | 744.00 | 21.71 | 107.00 | 21.71 | 107.00 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.61 | 40.00 | 21.58 | 40.00 | 21.56 |
February | 672.00 | 21.35 | 11.83 | 21.34 | 11.83 | 21.33 |
March | 742.00 | 21.79 | 27.83 | 21.76 | 27.17 | 21.74 |
April | 652.83 | 21.90 | 27.33 | 22.05 | 0.00 | 22.05 |
May | 637.00 | 21.79 | 45.00 | 22.08 | 0.83 | 22.08 |
June | 444.50 | 21.48 | 80.50 | 21.88 | 0.17 | 21.89 |
July | 534.33 | 21.37 | 84.50 | 21.68 | 4.83 | 21.70 |
August | 523.67 | 21.41 | 104.00 | 21.80 | 16.17 | 21.87 |
September | 527.67 | 21.53 | 66.50 | 21.83 | 21.00 | 21.92 |
October | 678.00 | 21.87 | 12.83 | 21.93 | 2.17 | 21.94 |
November | 717.83 | 21.68 | 99.33 | 21.64 | 98.83 | 21.60 |
December | 744.00 | 21.28 | 275.83 | 21.20 | 275.83 | 21.16 |
Annual Sum or Average | 7617.83 | 21.60 | 875.50 | 21.70 | 498.83 | 21.69 |
Minimum of Months | 444.50 | 21.28 | 11.83 | 21.20 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.90 | 275.83 | 22.08 | 275.83 | 22.08 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
February | 672.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
March | 744.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
April | 717.83 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
May | 736.33 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
June | 348.00 | 23.86 | 44.50 | 23.87 | 2.17 | 23.87 |
July | 356.00 | 23.89 | 488.00 | 23.89 | 233.83 | 23.89 |
August | 351.17 | 23.82 | 520.83 | 23.84 | 261.33 | 23.84 |
September | 301.83 | 23.76 | 391.17 | 23.80 | 201.83 | 23.80 |
October | 628.33 | 23.02 | 86.33 | 23.12 | 35.17 | 23.15 |
November | 720.00 | 22.33 | 48.67 | 22.33 | 48.67 | 22.32 |
December | 744.00 | 21.69 | 7.33 | 21.68 | 7.33 | 21.68 |
Annual Sum or Average | 7063.50 | 22.71 | 1586.83 | 22.91 | 790.33 | 22.97 |
Minimum of Months | 301.83 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
Maximum of Months | 744.00 | 23.89 | 520.83 | 23.89 | 261.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 718.00 | 21.55 | 31.00 | 21.53 | 31.00 | 21.51 |
February | 663.17 | 21.35 | 33.17 | 21.32 | 33.17 | 21.30 |
March | 729.50 | 21.49 | 57.83 | 21.46 | 57.00 | 21.42 |
April | 638.67 | 21.57 | 10.17 | 21.58 | 4.83 | 21.58 |
May | 666.17 | 21.61 | 0.67 | 21.61 | 0.00 | 21.61 |
June | 488.00 | 21.45 | 103.33 | 21.78 | 0.00 | 21.78 |
July | 549.33 | 21.36 | 91.83 | 21.62 | 0.83 | 21.63 |
August | 530.00 | 21.31 | 118.83 | 21.65 | 3.17 | 21.66 |
September | 542.83 | 21.34 | 91.00 | 21.60 | 9.33 | 21.62 |
October | 665.67 | 21.51 | 51.00 | 21.57 | 24.00 | 21.55 |
November | 686.67 | 21.51 | 112.17 | 21.49 | 104.50 | 21.46 |
December | 737.83 | 21.47 | 231.67 | 21.37 | 231.67 | 21.30 |
Annual Sum or Average | 7615.83 | 21.47 | 932.67 | 21.54 | 499.50 | 21.51 |
Minimum of Months | 488.00 | 21.31 | 0.67 | 21.32 | 0.00 | 21.30 |
Maximum of Months | 737.83 | 21.61 | 231.67 | 21.78 | 231.67 | 21.78 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.00 | 21.53 | 115.83 | 21.45 | 115.83 | 21.39 |
February | 670.50 | 21.20 | 76.50 | 21.14 | 76.50 | 21.10 |
March | 724.83 | 21.61 | 81.00 | 21.58 | 74.00 | 21.52 |
April | 651.83 | 21.80 | 12.33 | 21.86 | 1.50 | 21.86 |
May | 669.50 | 21.81 | 1.00 | 21.82 | 0.00 | 21.82 |
June | 460.17 | 21.57 | 113.17 | 21.94 | 0.00 | 21.94 |
July | 542.17 | 21.42 | 93.00 | 21.68 | 6.67 | 21.70 |
August | 533.00 | 21.47 | 114.33 | 21.79 | 21.50 | 21.84 |
September | 559.83 | 21.58 | 83.00 | 21.80 | 33.67 | 21.88 |
October | 689.67 | 21.74 | 51.33 | 21.73 | 44.00 | 21.70 |
November | 710.17 | 21.58 | 182.33 | 21.50 | 179.50 | 21.45 |
December | 744.00 | 21.19 | 438.17 | 21.07 | 438.17 | 21.02 |
Annual Sum or Average | 7698.67 | 21.54 | 1362.00 | 21.57 | 991.33 | 21.52 |
Minimum of Months | 460.17 | 21.19 | 1.00 | 21.07 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.81 | 438.17 | 21.94 | 438.17 | 21.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 637.17 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
February | 632.83 | 21.45 | 1.83 | 21.45 | 1.83 | 21.45 |
March | 722.67 | 21.58 | 18.00 | 21.56 | 18.00 | 21.55 |
April | 671.83 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 735.67 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 645.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
July | 639.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
August | 613.83 | 21.41 | 1.00 | 21.41 | 0.67 | 21.42 |
September | 592.00 | 21.41 | 15.33 | 21.45 | 3.00 | 21.46 |
October | 642.33 | 21.46 | 16.50 | 21.51 | 0.00 | 21.51 |
November | 639.83 | 21.48 | 36.83 | 21.49 | 31.67 | 21.49 |
December | 681.17 | 21.52 | 38.17 | 21.50 | 38.17 | 21.48 |
Annual Sum or Average | 7854.83 | 21.51 | 127.67 | 21.52 | 93.33 | 21.52 |
Minimum of Months | 592.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.42 |
Maximum of Months | 735.67 | 21.71 | 38.17 | 21.71 | 38.17 | 21.71 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 182.00 | 23.47 | 107.67 | 23.66 | 8.33 | 23.66 |
February | 148.50 | 23.45 | 307.00 | 23.81 | 45.00 | 23.82 |
March | 118.33 | 23.45 | 310.17 | 23.84 | 4.83 | 23.84 |
April | 9.83 | 23.76 | 272.50 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 346.00 | 24.00 | 0.00 | 24.00 |
June | 13.33 | 24.00 | 669.67 | 24.00 | 13.33 | 24.00 |
July | 300.17 | 24.00 | 698.67 | 24.00 | 300.17 | 24.00 |
August | 344.67 | 24.00 | 723.50 | 24.00 | 344.67 | 24.00 |
September | 271.83 | 24.00 | 720.00 | 23.99 | 271.83 | 23.99 |
October | 107.67 | 23.75 | 336.33 | 23.93 | 58.83 | 23.94 |
November | 207.00 | 23.70 | 242.67 | 23.82 | 78.83 | 23.83 |
December | 418.50 | 23.59 | 10.17 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 2121.83 | 23.76 | 4744.33 | 23.92 | 1125.83 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 10.17 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 418.50 | 24.00 | 723.50 | 24.00 | 344.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.17 | 23.58 | 194.00 | 23.90 | 7.17 | 23.90 |
February | 56.33 | 23.80 | 450.67 | 23.94 | 37.00 | 23.95 |
March | 33.17 | 23.60 | 436.67 | 23.95 | 4.50 | 23.95 |
April | 0.00 | 0.00 | 372.00 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 449.00 | 24.00 | 0.00 | 24.00 |
June | 12.33 | 24.00 | 693.83 | 24.00 | 12.33 | 24.00 |
July | 284.33 | 24.00 | 709.67 | 24.00 | 284.33 | 24.00 |
August | 322.50 | 24.00 | 730.50 | 24.00 | 322.50 | 24.00 |
September | 254.00 | 24.00 | 720.00 | 24.00 | 254.00 | 24.00 |
October | 74.17 | 23.89 | 427.67 | 23.98 | 57.33 | 23.98 |
November | 113.00 | 23.84 | 296.67 | 23.93 | 77.67 | 23.94 |
December | 168.33 | 23.57 | 15.50 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 1366.33 | 23.89 | 5496.17 | 23.97 | 1056.83 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 15.50 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 322.50 | 24.00 | 730.50 | 24.00 | 322.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 504.67 | 23.99 | 717.83 | 23.95 | 504.17 | 23.96 |
February | 472.17 | 23.99 | 664.67 | 23.94 | 472.17 | 23.95 |
March | 514.50 | 23.99 | 724.33 | 23.96 | 514.50 | 23.97 |
April | 510.83 | 23.99 | 718.00 | 23.98 | 510.83 | 23.99 |
May | 534.67 | 23.99 | 744.00 | 23.99 | 534.67 | 23.99 |
June | 564.17 | 23.99 | 720.00 | 23.99 | 564.17 | 23.99 |
July | 695.83 | 23.99 | 744.00 | 23.99 | 695.83 | 23.99 |
August | 705.33 | 23.99 | 744.00 | 23.99 | 705.33 | 23.99 |
September | 643.67 | 23.99 | 720.00 | 23.99 | 643.67 | 23.99 |
October | 547.50 | 23.99 | 737.17 | 23.97 | 547.50 | 23.98 |
November | 517.67 | 23.98 | 691.17 | 23.96 | 516.50 | 23.96 |
December | 480.67 | 23.97 | 656.83 | 23.96 | 472.17 | 23.97 |
Annual Sum or Average | 6691.67 | 23.99 | 8582.00 | 23.97 | 6681.50 | 23.98 |
Minimum of Months | 472.17 | 23.97 | 656.83 | 23.94 | 472.17 | 23.95 |
Maximum of Months | 705.33 | 23.99 | 744.00 | 23.99 | 705.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
February | 672.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
March | 744.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
April | 597.33 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
May | 486.17 | 23.52 | 0.67 | 23.52 | 0.00 | 23.52 |
June | 114.83 | 23.68 | 137.33 | 23.85 | 0.00 | 23.85 |
July | 192.67 | 23.83 | 580.17 | 23.92 | 146.17 | 23.91 |
August | 195.33 | 23.77 | 627.17 | 23.87 | 159.83 | 23.86 |
September | 169.00 | 23.64 | 496.33 | 23.82 | 120.00 | 23.81 |
October | 580.33 | 22.77 | 109.17 | 22.95 | 20.83 | 22.97 |
November | 711.67 | 22.17 | 25.50 | 22.16 | 25.50 | 22.15 |
December | 744.00 | 21.61 | 52.50 | 21.57 | 52.50 | 21.53 |
Annual Sum or Average | 5951.33 | 22.45 | 2028.83 | 22.80 | 524.83 | 22.84 |
Minimum of Months | 114.83 | 21.56 | 0.00 | 21.56 | 0.00 | 21.53 |
Maximum of Months | 744.00 | 23.83 | 627.17 | 23.92 | 159.83 | 23.91 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.82747 | 25.44114 | 0.20187 | 5.98385 |
February | 672.00000 | 23.26205 | 39.13717 | 0.14106 | 5.59148 |
March | 744.00000 | 22.70643 | 32.04316 | -0.0470 | 5.27582 |
April | 720.00000 | 23.03383 | 23.79958 | -0.0154 | 5.21444 |
May | 744.00000 | 22.73905 | 23.52277 | -1.1282 | 32.01762 |
June | 720.00000 | 23.02115 | 35.04324 | -0.9490 | 24.34365 |
July | 744.00000 | 23.82224 | 49.55337 | -0.5495 | 11.79773 |
August | 744.00000 | 23.92703 | 51.67818 | -0.4853 | 10.08102 |
September | 720.00000 | 23.99539 | 50.04318 | -0.4532 | 9.40188 |
October | 744.00000 | 23.99670 | 30.26982 | 0.30531 | 7.13669 |
November | 720.00000 | 23.99819 | 29.49893 | 0.29753 | 7.06483 |
December | 744.00000 | 23.99164 | 18.12374 | 0.21021 | 5.95373 |
Annual Sum or Average | 8760.00000 | 23.52910 | 33.96434 | -0.2080 | 10.85738 |
Minimum of Months | 672.00000 | 22.70643 | 18.12374 | -1.1282 | 5.21444 |
Maximum of Months | 744.00000 | 23.99819 | 51.67818 | 0.30531 | 32.01762 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.69592 | 26.06977 | 0.04004 | 7.00435 |
February | 672.00000 | 21.84363 | 41.43885 | -0.1303 | 6.73588 |
March | 744.00000 | 22.05385 | 32.13108 | -0.1221 | 6.79548 |
April | 720.00000 | 23.30816 | 22.20431 | 0.17549 | 6.78715 |
May | 744.00000 | 23.46584 | 21.43574 | -0.7031 | 16.65175 |
June | 720.00000 | 23.84495 | 31.92725 | -0.4487 | 9.78325 |
July | 744.00000 | 23.83417 | 48.59552 | -0.3487 | 8.14025 |
August | 744.00000 | 23.79043 | 51.36354 | -0.3368 | 8.05830 |
September | 720.00000 | 23.74885 | 50.49400 | -0.3575 | 8.50434 |
October | 744.00000 | 23.18325 | 31.22498 | 0.21550 | 8.02492 |
November | 720.00000 | 22.62337 | 31.74993 | 0.05255 | 7.04995 |
December | 744.00000 | 22.22447 | 19.35222 | -0.1495 | 7.82807 |
Annual Sum or Average | 8760.00000 | 23.05772 | 33.93674 | -0.1768 | 8.46560 |
Minimum of Months | 672.00000 | 21.84363 | 19.35222 | -0.7031 | 6.73588 |
Maximum of Months | 744.00000 | 23.84495 | 51.36354 | 0.21550 | 16.65175 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.32561 | 27.06687 | 0.12209 | 5.60922 |
February | 672.00000 | 22.81164 | 40.99351 | 0.07421 | 5.48917 |
March | 744.00000 | 23.02910 | 32.34577 | 0.07828 | 5.67529 |
April | 720.00000 | 23.74097 | 23.36034 | 0.21917 | 6.24780 |
May | 744.00000 | 23.81898 | 22.56129 | -0.6639 | 14.51064 |
June | 720.00000 | 23.93472 | 33.16735 | -0.5244 | 10.96546 |
July | 744.00000 | 23.91702 | 49.66277 | -0.4255 | 9.04462 |
August | 744.00000 | 23.91183 | 52.33325 | -0.4101 | 8.69781 |
September | 720.00000 | 23.90422 | 51.44935 | -0.4258 | 8.97032 |
October | 744.00000 | 23.65071 | 32.26234 | 0.25351 | 6.87439 |
November | 720.00000 | 23.36811 | 32.23290 | 0.16837 | 6.06296 |
December | 744.00000 | 22.97727 | 20.63058 | -0.0136 | 5.39035 |
Annual Sum or Average | 8760.00000 | 23.53620 | 34.78593 | -0.1305 | 7.81086 |
Minimum of Months | 672.00000 | 22.81164 | 20.63058 | -0.6639 | 5.39035 |
Maximum of Months | 744.00000 | 23.93472 | 52.33325 | 0.25351 | 14.51064 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36799 | 22.53556 | 0.71624 | 17.85777 |
February | 672.00000 | 23.31826 | 35.43035 | 0.77587 | 19.82806 |
March | 744.00000 | 23.34340 | 27.42269 | 0.74582 | 18.80243 |
April | 720.00000 | 23.45265 | 19.63664 | 0.77258 | 19.45156 |
May | 744.00000 | 23.48625 | 19.04401 | 0.13801 | 9.07748 |
June | 720.00000 | 23.50818 | 30.50358 | 0.26455 | 9.97304 |
July | 744.00000 | 23.49288 | 47.17831 | 0.35463 | 11.09666 |
August | 744.00000 | 23.46794 | 49.95172 | 0.36108 | 11.24291 |
September | 720.00000 | 23.46294 | 48.86596 | 0.33097 | 10.88129 |
October | 744.00000 | 23.42899 | 28.54177 | 0.80858 | 20.77266 |
November | 720.00000 | 23.37610 | 27.79961 | 0.75781 | 19.27652 |
December | 744.00000 | 23.32313 | 15.87295 | 0.64223 | 15.74301 |
Annual Sum or Average | 8760.00000 | 23.41955 | 31.02241 | 0.55415 | 15.30148 |
Minimum of Months | 672.00000 | 23.31826 | 15.87295 | 0.13801 | 9.07748 |
Maximum of Months | 744.00000 | 23.50818 | 49.95172 | 0.80858 | 20.77266 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73380 | 30.39426 | 0.35254 | 8.19133 |
February | 672.00000 | 23.18105 | 44.54764 | 0.24619 | 7.17295 |
March | 744.00000 | 23.27784 | 36.20009 | 0.22520 | 6.95007 |
April | 720.00000 | 23.78705 | 27.11414 | 0.35477 | 8.06250 |
May | 744.00000 | 23.77661 | 26.47193 | -0.5209 | 11.16870 |
June | 720.00000 | 23.88410 | 36.78604 | -0.3530 | 7.99078 |
July | 744.00000 | 23.89810 | 53.12547 | -0.2396 | 6.56654 |
August | 744.00000 | 23.90343 | 55.63849 | -0.2105 | 6.24831 |
September | 720.00000 | 23.92069 | 54.57527 | -0.2096 | 6.29449 |
October | 744.00000 | 23.81638 | 35.56189 | 0.43432 | 9.70407 |
November | 720.00000 | 23.66621 | 35.74189 | 0.36213 | 8.46370 |
December | 744.00000 | 23.46094 | 24.34597 | 0.20964 | 6.86862 |
Annual Sum or Average | 8760.00000 | 23.69504 | 38.32256 | 0.05285 | 7.81319 |
Minimum of Months | 672.00000 | 23.18105 | 24.34597 | -0.5209 | 6.24831 |
Maximum of Months | 744.00000 | 23.92069 | 55.63849 | 0.43432 | 11.16870 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.71266 | 29.56961 | 0.25542 | 6.54498 |
February | 672.00000 | 23.30128 | 43.11733 | 0.22472 | 6.44137 |
March | 744.00000 | 23.38794 | 34.87399 | 0.19919 | 6.32269 |
April | 720.00000 | 23.77728 | 26.07893 | 0.26949 | 6.71753 |
May | 744.00000 | 23.79284 | 25.26059 | -0.6195 | 13.30187 |
June | 720.00000 | 23.89324 | 35.80418 | -0.4806 | 10.08212 |
July | 744.00000 | 23.89577 | 52.16051 | -0.3704 | 8.14947 |
August | 744.00000 | 23.90743 | 54.78231 | -0.3495 | 7.72370 |
September | 720.00000 | 23.92441 | 53.76125 | -0.3539 | 7.76751 |
October | 744.00000 | 23.82740 | 34.68010 | 0.34174 | 7.82208 |
November | 720.00000 | 23.70154 | 34.66951 | 0.28860 | 7.08591 |
December | 744.00000 | 23.48519 | 23.37951 | 0.14395 | 5.72892 |
Annual Sum or Average | 8760.00000 | 23.71950 | 37.29481 | -0.0394 | 7.81741 |
Minimum of Months | 672.00000 | 23.30128 | 23.37951 | -0.6195 | 5.72892 |
Maximum of Months | 744.00000 | 23.92441 | 54.78231 | 0.34174 | 13.30187 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64112 | 35.47908 | -0.2454 | 7.28666 |
February | 672.00000 | 21.43025 | 49.70961 | -0.2690 | 7.14954 |
March | 744.00000 | 21.55933 | 40.14325 | -0.2569 | 7.24289 |
April | 720.00000 | 21.76030 | 30.54803 | -0.1507 | 6.62115 |
May | 744.00000 | 21.77854 | 29.97257 | -1.1938 | 36.37157 |
June | 720.00000 | 21.96655 | 39.12960 | -1.0034 | 28.36775 |
July | 744.00000 | 21.81627 | 48.78528 | -1.0278 | 28.98630 |
August | 744.00000 | 21.81920 | 50.92290 | -1.0195 | 28.77242 |
September | 720.00000 | 21.79036 | 51.74135 | -1.0458 | 29.83272 |
October | 744.00000 | 21.71958 | 38.01369 | -0.1471 | 6.72565 |
November | 720.00000 | 21.63088 | 39.81665 | -0.2172 | 7.07019 |
December | 744.00000 | 21.53189 | 28.31933 | -0.3653 | 8.79438 |
Annual Sum or Average | 8760.00000 | 21.70502 | 40.13605 | -0.5808 | 17.00416 |
Minimum of Months | 672.00000 | 21.43025 | 28.31933 | -1.1938 | 6.62115 |
Maximum of Months | 744.00000 | 21.96655 | 51.74135 | -0.1471 | 36.37157 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.61048 | 35.45592 | -0.3177 | 7.85466 |
February | 672.00000 | 21.28175 | 50.06782 | -0.3386 | 7.81742 |
March | 744.00000 | 21.72271 | 39.88438 | -0.2537 | 7.36211 |
April | 720.00000 | 22.00915 | 30.31905 | -0.1212 | 6.53796 |
May | 744.00000 | 21.99500 | 29.73910 | -1.1418 | 33.95828 |
June | 720.00000 | 22.15912 | 38.96374 | -0.9451 | 26.08034 |
July | 744.00000 | 21.88904 | 48.83411 | -1.0077 | 28.13323 |
August | 744.00000 | 21.95418 | 51.09515 | -0.9933 | 27.65423 |
September | 720.00000 | 21.98129 | 52.06433 | -1.0155 | 28.48699 |
October | 744.00000 | 21.93910 | 37.74030 | -0.1444 | 6.68342 |
November | 720.00000 | 21.69492 | 40.02895 | -0.2559 | 7.46191 |
December | 744.00000 | 21.27998 | 28.59517 | -0.4811 | 10.50793 |
Annual Sum or Average | 8760.00000 | 21.79542 | 40.15027 | -0.5867 | 16.61006 |
Minimum of Months | 672.00000 | 21.27998 | 28.59517 | -1.1418 | 6.53796 |
Maximum of Months | 744.00000 | 22.15912 | 52.06433 | -0.1212 | 33.95828 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42014 | 33.93430 | -0.3838 | 8.25715 |
February | 672.00000 | 21.29662 | 47.11842 | -0.3371 | 7.52929 |
March | 744.00000 | 21.59899 | 37.87059 | -0.3034 | 7.34552 |
April | 720.00000 | 21.82107 | 28.98827 | -0.2587 | 6.98732 |
May | 744.00000 | 21.86277 | 28.55832 | -1.3332 | 42.63805 |
June | 720.00000 | 21.85639 | 37.66941 | -1.2339 | 37.80447 |
July | 744.00000 | 21.77675 | 45.10092 | -1.2237 | 37.31688 |
August | 744.00000 | 21.83390 | 47.25837 | -1.2075 | 36.62664 |
September | 720.00000 | 21.87867 | 48.62157 | -1.1990 | 36.22633 |
October | 744.00000 | 21.77405 | 35.43864 | -0.2486 | 6.95827 |
November | 720.00000 | 21.51704 | 37.76390 | -0.3283 | 7.79098 |
December | 744.00000 | 21.23115 | 26.95634 | -0.4877 | 10.13251 |
Annual Sum or Average | 8760.00000 | 21.65734 | 37.86097 | -0.7147 | 20.55512 |
Minimum of Months | 672.00000 | 21.23115 | 26.95634 | -1.3332 | 6.95827 |
Maximum of Months | 744.00000 | 21.87867 | 48.62157 | -0.2486 | 42.63805 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68771 | 35.44790 | -0.2365 | 7.22501 |
February | 672.00000 | 21.52030 | 49.11909 | -0.2421 | 7.01274 |
March | 744.00000 | 21.64772 | 39.97492 | -0.2299 | 7.06915 |
April | 720.00000 | 21.77334 | 30.59007 | -0.1408 | 6.57473 |
May | 744.00000 | 21.78544 | 30.00886 | -1.1780 | 35.69045 |
June | 720.00000 | 21.96231 | 39.37810 | -0.9919 | 27.72968 |
July | 744.00000 | 21.82671 | 49.12807 | -1.0005 | 27.94149 |
August | 744.00000 | 21.82315 | 51.27687 | -0.9973 | 27.88788 |
September | 720.00000 | 21.79839 | 51.80276 | -1.0319 | 29.27047 |
October | 744.00000 | 21.75286 | 37.97224 | -0.1318 | 6.68456 |
November | 720.00000 | 21.66294 | 39.95345 | -0.2135 | 7.01157 |
December | 744.00000 | 21.59658 | 28.29101 | -0.3479 | 8.54409 |
Annual Sum or Average | 8760.00000 | 21.73754 | 40.17031 | -0.5641 | 16.61992 |
Minimum of Months | 672.00000 | 21.52030 | 28.29101 | -1.1780 | 6.57473 |
Maximum of Months | 744.00000 | 21.96231 | 51.80276 | -0.1318 | 35.69045 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60984 | 35.48592 | -0.3197 | 7.70764 |
February | 672.00000 | 21.34743 | 49.56516 | -0.3151 | 7.46294 |
March | 744.00000 | 21.79269 | 39.66628 | -0.2307 | 7.02305 |
April | 720.00000 | 22.14596 | 30.14539 | -0.0871 | 6.77469 |
May | 744.00000 | 22.19608 | 29.73098 | -1.0698 | 32.33279 |
June | 720.00000 | 22.24118 | 39.04498 | -0.9088 | 25.07158 |
July | 744.00000 | 21.93380 | 49.01284 | -0.9713 | 26.95323 |
August | 744.00000 | 22.00127 | 51.04062 | -0.9607 | 26.72576 |
September | 720.00000 | 22.06242 | 51.69185 | -0.9822 | 27.74386 |
October | 744.00000 | 22.03948 | 37.51298 | -0.1158 | 6.69497 |
November | 720.00000 | 21.68488 | 40.08987 | -0.2627 | 7.36809 |
December | 744.00000 | 21.27904 | 28.58385 | -0.4765 | 10.22197 |
Annual Sum or Average | 8760.00000 | 21.86350 | 40.05212 | -0.5603 | 16.06891 |
Minimum of Months | 672.00000 | 21.27904 | 28.58385 | -1.0698 | 6.69497 |
Maximum of Months | 744.00000 | 22.24118 | 51.69185 | -0.0871 | 32.33279 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60776 | 35.92624 | -0.2743 | 7.80591 |
February | 672.00000 | 21.37642 | 50.79838 | -0.2999 | 7.68951 |
March | 744.00000 | 21.52650 | 40.67038 | -0.2783 | 7.67535 |
April | 720.00000 | 21.76048 | 30.60195 | -0.1510 | 6.89239 |
May | 744.00000 | 21.78782 | 29.92895 | -1.1868 | 36.36854 |
June | 720.00000 | 22.01785 | 39.17802 | -0.9665 | 27.47418 |
July | 744.00000 | 21.83238 | 48.94663 | -1.0062 | 28.42078 |
August | 744.00000 | 21.83438 | 51.18263 | -1.0004 | 28.37864 |
September | 720.00000 | 21.79575 | 52.27309 | -1.0377 | 29.78232 |
October | 744.00000 | 21.69734 | 38.34915 | -0.1643 | 7.09298 |
November | 720.00000 | 21.59311 | 40.57952 | -0.2441 | 7.53904 |
December | 744.00000 | 21.48141 | 28.64100 | -0.4039 | 9.61700 |
Annual Sum or Average | 8760.00000 | 21.69411 | 40.50500 | -0.5866 | 17.12898 |
Minimum of Months | 672.00000 | 21.37642 | 28.64100 | -1.1868 | 6.89239 |
Maximum of Months | 744.00000 | 22.01785 | 52.27309 | -0.1510 | 36.36854 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53611 | 36.04265 | -0.3588 | 8.58773 |
February | 672.00000 | 21.20657 | 51.24237 | -0.3766 | 8.54174 |
March | 744.00000 | 21.68819 | 40.45536 | -0.2751 | 7.85698 |
April | 720.00000 | 21.98506 | 30.44749 | -0.1246 | 6.79776 |
May | 744.00000 | 21.96477 | 29.79063 | -1.1440 | 34.29794 |
June | 720.00000 | 22.19662 | 39.03346 | -0.9107 | 25.27170 |
July | 744.00000 | 21.89848 | 48.97182 | -0.9876 | 27.61059 |
August | 744.00000 | 21.95101 | 51.29159 | -0.9792 | 27.38187 |
September | 720.00000 | 21.95512 | 52.57682 | -1.0159 | 28.66643 |
October | 744.00000 | 21.86697 | 38.16073 | -0.1722 | 7.08904 |
November | 720.00000 | 21.60618 | 40.87764 | -0.2961 | 8.12649 |
December | 744.00000 | 21.18613 | 29.02980 | -0.5322 | 11.73070 |
Annual Sum or Average | 8760.00000 | 21.75593 | 40.57224 | -0.5997 | 16.89381 |
Minimum of Months | 672.00000 | 21.18613 | 29.02980 | -1.1440 | 6.79776 |
Maximum of Months | 744.00000 | 22.19662 | 52.57682 | -0.1246 | 34.29794 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71079 | 35.56250 | -0.1798 | 7.12478 |
February | 672.00000 | 21.56089 | 47.89682 | -0.2172 | 6.93824 |
March | 744.00000 | 21.62798 | 39.72577 | -0.2393 | 7.26773 |
April | 720.00000 | 21.70711 | 31.86476 | -0.1898 | 6.96541 |
May | 744.00000 | 21.72693 | 31.67034 | -1.2770 | 40.33034 |
June | 720.00000 | 21.74848 | 39.28744 | -1.1652 | 34.97573 |
July | 744.00000 | 21.74662 | 44.79398 | -1.1371 | 33.66272 |
August | 744.00000 | 21.74726 | 46.28971 | -1.1207 | 33.06788 |
September | 720.00000 | 21.74835 | 47.23863 | -1.1131 | 32.84462 |
October | 744.00000 | 21.71652 | 36.91042 | -0.1459 | 6.85430 |
November | 720.00000 | 21.68384 | 38.98303 | -0.1780 | 6.98260 |
December | 744.00000 | 21.67374 | 29.52136 | -0.2629 | 7.96161 |
Annual Sum or Average | 8760.00000 | 21.70078 | 39.07130 | -0.6047 | 18.82650 |
Minimum of Months | 672.00000 | 21.56089 | 29.52136 | -1.2770 | 6.85430 |
Maximum of Months | 744.00000 | 21.74848 | 47.89682 | -0.1459 | 40.33034 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.83894 | 30.36925 | 0.31078 | 7.20883 |
February | 672.00000 | 23.79067 | 42.88889 | 0.37465 | 8.20294 |
March | 744.00000 | 23.85263 | 34.77886 | 0.35733 | 7.90027 |
April | 720.00000 | 23.97694 | 26.38080 | 0.39435 | 8.37532 |
May | 744.00000 | 23.99265 | 25.48781 | -0.4202 | 8.79642 |
June | 720.00000 | 23.99584 | 36.17062 | -0.2911 | 6.91077 |
July | 744.00000 | 23.99562 | 52.31970 | -0.1892 | 5.95525 |
August | 744.00000 | 23.99484 | 55.02001 | -0.1829 | 5.83218 |
September | 720.00000 | 23.99329 | 54.12723 | -0.2096 | 6.04579 |
October | 744.00000 | 23.93469 | 35.29772 | 0.42110 | 9.10386 |
November | 720.00000 | 23.86630 | 35.23714 | 0.35936 | 8.08374 |
December | 744.00000 | 23.75853 | 24.29149 | 0.22501 | 6.28399 |
Annual Sum or Average | 8760.00000 | 23.91648 | 37.65171 | 0.09385 | 7.38536 |
Minimum of Months | 672.00000 | 23.75853 | 24.29149 | -0.4202 | 5.83218 |
Maximum of Months | 744.00000 | 23.99584 | 55.02001 | 0.42110 | 9.10386 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.92456 | 29.56678 | 0.36517 | 7.91311 |
February | 672.00000 | 23.90146 | 41.92107 | 0.43851 | 9.20551 |
March | 744.00000 | 23.93688 | 33.96940 | 0.41284 | 8.71626 |
April | 720.00000 | 23.99097 | 25.88437 | 0.42594 | 8.90932 |
May | 744.00000 | 23.99512 | 25.07131 | -0.3812 | 8.14341 |
June | 720.00000 | 23.99666 | 35.82347 | -0.2550 | 6.50345 |
July | 744.00000 | 23.99648 | 51.96406 | -0.1535 | 5.70208 |
August | 744.00000 | 23.99598 | 54.65351 | -0.1468 | 5.58658 |
September | 720.00000 | 23.99521 | 53.73944 | -0.1730 | 5.75490 |
October | 744.00000 | 23.97020 | 34.72118 | 0.45869 | 9.73740 |
November | 720.00000 | 23.94361 | 34.45585 | 0.41119 | 8.85631 |
December | 744.00000 | 23.87638 | 23.41970 | 0.28982 | 6.88752 |
Annual Sum or Average | 8760.00000 | 23.96054 | 37.05542 | 0.13904 | 7.64863 |
Minimum of Months | 672.00000 | 23.87638 | 23.41970 | -0.3812 | 5.58658 |
Maximum of Months | 744.00000 | 23.99666 | 54.65351 | 0.45869 | 9.73740 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.89113 | 28.65692 | 1.00781 | 28.38964 |
February | 672.00000 | 23.89269 | 40.65068 | 1.07224 | 30.97540 |
March | 744.00000 | 23.90944 | 33.10762 | 1.05074 | 30.11996 |
April | 720.00000 | 23.97661 | 25.73330 | 1.10222 | 32.30776 |
May | 744.00000 | 23.98805 | 25.11907 | 0.59447 | 16.25030 |
June | 720.00000 | 23.99236 | 35.80858 | 0.73830 | 19.97544 |
July | 744.00000 | 23.99301 | 51.50370 | 0.82624 | 22.71768 |
August | 744.00000 | 23.99286 | 54.07245 | 0.83122 | 22.88053 |
September | 720.00000 | 23.99267 | 53.10802 | 0.79145 | 21.50229 |
October | 744.00000 | 23.95668 | 34.14161 | 1.12085 | 33.23183 |
November | 720.00000 | 23.90651 | 33.53347 | 1.04977 | 30.17077 |
December | 744.00000 | 23.84498 | 22.38082 | 0.92472 | 25.26925 |
Annual Sum or Average | 8760.00000 | 23.94493 | 36.44430 | 0.92469 | 26.11133 |
Minimum of Months | 672.00000 | 23.84498 | 22.38082 | 0.59447 | 16.25030 |
Maximum of Months | 744.00000 | 23.99301 | 54.07245 | 1.12085 | 33.23183 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89185 | 25.66948 | -0.2665 | 6.69549 |
February | 672.00000 | 21.48020 | 40.54768 | -0.2784 | 6.77742 |
March | 744.00000 | 21.82794 | 30.97547 | -0.2485 | 6.74081 |
April | 720.00000 | 23.06262 | 21.01450 | -0.0072 | 5.33757 |
May | 744.00000 | 23.56411 | 19.85099 | -0.8405 | 20.12224 |
June | 720.00000 | 23.97032 | 30.41708 | -0.6116 | 12.96870 |
July | 744.00000 | 23.95414 | 47.00614 | -0.5059 | 10.54972 |
August | 744.00000 | 23.89232 | 49.83330 | -0.5133 | 10.67584 |
September | 720.00000 | 23.80525 | 49.14481 | -0.5526 | 11.57904 |
October | 744.00000 | 22.90422 | 30.20550 | 0.01683 | 6.09189 |
November | 720.00000 | 22.08429 | 30.96617 | -0.1843 | 6.26286 |
December | 744.00000 | 21.47009 | 18.62471 | -0.4126 | 8.80271 |
Annual Sum or Average | 8760.00000 | 22.83223 | 32.79108 | -0.3681 | 9.40891 |
Minimum of Months | 672.00000 | 21.47009 | 18.62471 | -0.8405 | 5.33757 |
Maximum of Months | 744.00000 | 23.97032 | 49.83330 | 0.01683 | 20.12224 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.19752 | 28.63174 | -0.1960 | 6.00504 |
February | 672.00000 | 21.61095 | 43.62055 | -0.2517 | 6.41281 |
March | 744.00000 | 21.97991 | 34.09902 | -0.2153 | 6.28387 |
April | 720.00000 | 23.17136 | 24.48092 | 0.01785 | 5.31988 |
May | 744.00000 | 23.54481 | 23.53920 | -0.8562 | 20.65853 |
June | 720.00000 | 23.92353 | 33.98622 | -0.6434 | 13.83298 |
July | 744.00000 | 23.88732 | 50.52890 | -0.5466 | 11.45618 |
August | 744.00000 | 23.84224 | 53.35037 | -0.5445 | 11.35335 |
September | 720.00000 | 23.80010 | 52.53473 | -0.5665 | 11.87127 |
October | 744.00000 | 23.14878 | 33.34044 | 0.07335 | 5.98207 |
November | 720.00000 | 22.33412 | 34.01583 | -0.1279 | 5.70335 |
December | 744.00000 | 21.68930 | 21.76509 | -0.3623 | 8.02079 |
Annual Sum or Average | 8760.00000 | 22.93415 | 36.09535 | -0.3527 | 9.43545 |
Minimum of Months | 672.00000 | 21.61095 | 21.76509 | -0.8562 | 5.31988 |
Maximum of Months | 744.00000 | 23.92353 | 53.35037 | 0.07335 | 20.65853 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08861 | 26.59858 | -0.1974 | 6.20495 |
February | 672.00000 | 21.56400 | 41.55007 | -0.2406 | 6.44826 |
March | 744.00000 | 21.96954 | 31.92099 | -0.1926 | 6.34432 |
April | 720.00000 | 23.34667 | 21.96422 | 0.09623 | 5.71350 |
May | 744.00000 | 23.68424 | 21.00706 | -0.7444 | 17.10349 |
June | 720.00000 | 23.93374 | 31.66427 | -0.5543 | 11.64185 |
July | 744.00000 | 23.93948 | 47.96743 | -0.4456 | 9.42844 |
August | 744.00000 | 23.89701 | 50.76730 | -0.4452 | 9.37447 |
September | 720.00000 | 23.83847 | 49.99512 | -0.4808 | 10.09599 |
October | 744.00000 | 23.01075 | 31.21142 | 0.07426 | 6.43082 |
November | 720.00000 | 22.18263 | 31.97431 | -0.1380 | 6.13027 |
December | 744.00000 | 21.60899 | 19.65969 | -0.3638 | 8.21242 |
Annual Sum or Average | 8760.00000 | 22.92875 | 33.79300 | -0.3036 | 8.61388 |
Minimum of Months | 672.00000 | 21.56400 | 19.65969 | -0.7444 | 5.71350 |
Maximum of Months | 744.00000 | 23.93948 | 50.76730 | 0.09623 | 17.10349 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.03992 | 25.13807 | -0.2364 | 6.43705 |
February | 672.00000 | 21.65187 | 39.83971 | -0.2428 | 6.42802 |
March | 744.00000 | 22.00261 | 30.36158 | -0.2119 | 6.43790 |
April | 720.00000 | 23.25458 | 20.46966 | 0.03461 | 5.40185 |
May | 744.00000 | 23.71906 | 19.37632 | -0.7885 | 18.31340 |
June | 720.00000 | 23.98970 | 30.05074 | -0.5977 | 12.60404 |
July | 744.00000 | 23.97540 | 46.59494 | -0.4921 | 10.26076 |
August | 744.00000 | 23.93818 | 49.35091 | -0.4928 | 10.22578 |
September | 720.00000 | 23.89030 | 48.56257 | -0.5210 | 10.84506 |
October | 744.00000 | 23.08081 | 29.60973 | 0.05541 | 6.12060 |
November | 720.00000 | 22.25932 | 30.33994 | -0.1478 | 6.05592 |
December | 744.00000 | 21.60551 | 18.17992 | -0.3850 | 8.38995 |
Annual Sum or Average | 8760.00000 | 22.95692 | 32.26070 | -0.3366 | 8.98340 |
Minimum of Months | 672.00000 | 21.60551 | 18.17992 | -0.7885 | 5.40185 |
Maximum of Months | 744.00000 | 23.98970 | 49.35091 | 0.05541 | 18.31340 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.669989E+11 | 117375.11 | 31-JAN-16:02 | 699.61 | 0.194120E+12 | 0.00 | 0.261119E+12 | 2.81 | 3.78 | 31-JAN-19:03 | 0.00 | 0.00 |
February | 0.225066E+11 | 79284.21 | 09-FEB-16:02 | 571.38 | 0.661355E+11 | 0.00 | 0.886421E+11 | 2.58 | 3.60 | 09-FEB-16:02 | 0.00 | 0.00 |
March | 0.628552E+11 | 116051.66 | 16-MAR-15:03 | 697.29 | 0.178699E+12 | 0.00 | 0.241554E+12 | 2.77 | 3.68 | 08-MAR-16:01 | 0.00 | 0.00 |
April | 0.162856E+12 | 160458.95 | 14-APR-18:03 | 720.00 | 0.473890E+12 | 0.00 | 0.636746E+12 | 2.91 | 3.71 | 18-APR-21:53 | 0.00 | 0.00 |
May | 0.210404E+12 | 172354.94 | 31-MAY-18:03 | 744.00 | 0.602035E+12 | 0.00 | 0.812439E+12 | 2.85 | 3.62 | 13-MAY-21:51 | 0.00 | 0.00 |
June | 0.278566E+12 | 209807.61 | 27-JUN-18:03 | 720.00 | 0.768694E+12 | 0.00 | 0.104726E+13 | 2.79 | 3.51 | 20-JUN-06:42 | 0.00 | 0.00 |
July | 0.295075E+12 | 190506.57 | 20-JUL-18:03 | 744.00 | 0.868398E+12 | 0.00 | 0.116347E+13 | 2.96 | 3.93 | 14-JUL-01:00 | 0.00 | 0.00 |
August | 0.287295E+12 | 203520.26 | 25-AUG-15:03 | 744.00 | 0.847955E+12 | 0.00 | 0.113525E+13 | 2.98 | 4.05 | 18-AUG-22:00 | 0.00 | 0.00 |
September | 0.254219E+12 | 183168.42 | 08-SEP-18:03 | 720.00 | 0.778354E+12 | 0.00 | 0.103257E+13 | 3.05 | 4.14 | 03-SEP-08:53 | 0.00 | 0.00 |
October | 0.144364E+12 | 161569.17 | 02-OCT-18:03 | 739.17 | 0.427732E+12 | 0.00 | 0.572097E+12 | 2.95 | 3.76 | 16-OCT-21:53 | 0.00 | 0.00 |
November | 0.712990E+11 | 122704.11 | 01-NOV-15:03 | 681.17 | 0.207809E+12 | 0.00 | 0.279108E+12 | 2.82 | 4.12 | 13-NOV-16:03 | 0.00 | 0.00 |
December | 0.399944E+11 | 102021.90 | 22-DEC-16:02 | 620.70 | 0.115294E+12 | 0.00 | 0.155289E+12 | 2.51 | 3.77 | 02-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.189643E+13 | 8401.32 | 0.552912E+13 | 0.00 | 0.742555E+13 | 2.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.225066E+11 | 79284.21 | 571.38 | 0.661355E+11 | 0.00 | 0.886421E+11 | 2.51 | 3.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.295075E+12 | 209807.61 | 744.00 | 0.868398E+12 | 0.00 | 0.116347E+13 | 3.05 | 4.14 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.569748E+11 | 0.00 | 388.46 | 145882.90 | 01-JAN-09:03 | 0.00 | 35.93 | 49.20 | 0.21 | 0.00 | 0.06 | 0.43 | 01-JAN-09:03 |
February | 0.653243E+11 | 0.00 | 488.40 | 118383.30 | 09-FEB-09:04 | 0.00 | 34.92 | 52.91 | 0.26 | 0.00 | 0.08 | 0.35 | 09-FEB-09:04 |
March | 0.448085E+11 | 0.00 | 327.39 | 131102.11 | 26-MAR-08:03 | 0.00 | 33.21 | 44.63 | 0.16 | 0.00 | 0.05 | 0.39 | 26-MAR-08:03 |
April | 0.250249E+10 | 0.00 | 38.09 | 86894.25 | 21-APR-06:05 | 0.00 | 32.45 | 34.05 | 0.01 | 0.00 | 0.00 | 0.26 | 21-APR-06:05 |
May | 93645111.53 | 0.00 | 4.85 | 36436.00 | 01-MAY-08:53 | 0.00 | 36.52 | 36.70 | 0.00 | 0.00 | 0.00 | 0.11 | 01-MAY-08:53 |
June | 9338355.73 | 0.00 | 0.49 | 12724.08 | 05-JUN-08:06 | 0.00 | 41.71 | 41.72 | 0.00 | 0.00 | 0.00 | 0.04 | 05-JUN-08:06 |
July | 37664213.14 | 0.00 | 1.26 | 16478.13 | 02-JUL-08:15 | 0.00 | 42.05 | 42.08 | 0.00 | 0.00 | 0.00 | 0.05 | 02-JUL-08:15 |
August | 46931631.50 | 0.00 | 1.70 | 19159.56 | 25-AUG-08:04 | 0.00 | 42.26 | 42.30 | 0.00 | 0.00 | 0.00 | 0.06 | 25-AUG-08:04 |
September | 61826209.24 | 0.00 | 2.21 | 19530.87 | 03-SEP-21:55 | 0.00 | 41.88 | 41.94 | 0.00 | 0.00 | 0.00 | 0.06 | 03-SEP-21:55 |
October | 0.146950E+11 | 0.00 | 133.21 | 124305.50 | 25-OCT-08:03 | 0.00 | 36.32 | 41.15 | 0.05 | 0.00 | 0.02 | 0.37 | 25-OCT-08:03 |
November | 0.393521E+11 | 0.00 | 321.65 | 122351.66 | 23-NOV-19:03 | 0.00 | 35.80 | 46.94 | 0.14 | 0.00 | 0.05 | 0.36 | 23-NOV-19:03 |
December | 0.805451E+11 | 0.00 | 539.54 | 148250.02 | 16-DEC-09:03 | 0.00 | 37.20 | 54.41 | 0.31 | 0.00 | 0.09 | 0.44 | 16-DEC-09:03 |
Annual Sum or Average | 0.304452E+12 | 0.00 | 2247.25 | 0.00 | 37.54 | 43.96 | 0.09 | 0.00 | 0.03 | ||||
Minimum of Months | 9338355.73 | 0.00 | 0.49 | 12724.08 | 0.00 | 32.45 | 34.05 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.805451E+11 | 0.00 | 539.54 | 148250.02 | 0.00 | 42.26 | 54.41 | 0.31 | 0.00 | 0.09 | 0.44 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107053E+12 | 0.00 | 371.19 | 0.106620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 180871.39 | 31-JAN-16:03 | 180871.39 | 31-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 0.259170E+11 | 0.00 | 217.37 | 0.258887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104703.88 | 18-FEB-14:00 | 104703.88 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.115953E+12 | 0.00 | 419.31 | 0.115953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198650.90 | 16-MAR-18:07 | 198650.90 | 16-MAR-18:07 | 0.00 | 0.00 | 0.00 |
April | 0.319688E+12 | 0.00 | 658.83 | 0.319688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261477.13 | 14-APR-18:10 | 261477.13 | 14-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.416056E+12 | 0.00 | 734.67 | 0.416056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 273312.14 | 31-MAY-18:17 | 273312.14 | 31-MAY-18:17 | 0.00 | 0.00 | 0.00 |
June | 0.525161E+12 | 0.00 | 720.00 | 0.524272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 332777.62 | 17-JUN-17:17 | 316772.41 | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.610996E+12 | 0.00 | 744.00 | 0.534460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 412165.47 | 13-JUL-18:01 | 312164.74 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.597337E+12 | 0.00 | 744.00 | 0.527586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 442736.90 | 18-AUG-22:00 | 305253.42 | 10-AUG-18:13 | 0.00 | 0.00 | 0.00 |
September | 0.550077E+12 | 0.00 | 720.00 | 0.475461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 470761.78 | 10-SEP-20:40 | 301382.13 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.281643E+12 | 0.00 | 603.33 | 0.273739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334711.16 | 02-OCT-20:00 | 275380.18 | 04-OCT-18:17 | 0.00 | 0.00 | 0.00 |
November | 0.122609E+12 | 0.00 | 421.00 | 0.108761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 202202.38 | 01-NOV-18:10 | 202202.38 | 01-NOV-18:10 | 0.00 | 0.00 | 0.00 |
December | 0.568426E+11 | 0.00 | 296.45 | 0.568426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159791.22 | 22-DEC-16:03 | 159791.22 | 22-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372933E+13 | 0.00 | 6650.16 | 0.348532E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.259170E+11 | 0.00 | 217.37 | 0.258887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104703.88 | 104703.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.610996E+12 | 0.00 | 744.00 | 0.534460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 470761.78 | 316772.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.673159E+10 | 0.00 | 239.17 | 0.667634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16934.02 | 31-JAN-16:02 | 16934.02 | 31-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.173081E+10 | 0.00 | 131.50 | 0.173081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13679.85 | 18-FEB-14:00 | 13679.85 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.789044E+10 | 0.00 | 282.00 | 0.789044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17344.04 | 16-MAR-15:01 | 17344.04 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.209561E+11 | 0.00 | 514.83 | 0.209561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19388.91 | 14-APR-15:01 | 19388.91 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.271661E+11 | 0.00 | 580.50 | 0.271661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19755.34 | 31-MAY-15:01 | 19755.34 | 31-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.323567E+11 | 0.00 | 570.00 | 0.323334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22704.06 | 17-JUN-16:00 | 21845.29 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.374524E+11 | 0.00 | 589.00 | 0.329774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30440.72 | 27-JUL-06:50 | 21329.02 | 19-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.371941E+11 | 0.00 | 589.00 | 0.326157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35354.65 | 05-AUG-08:15 | 21432.61 | 25-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.352438E+11 | 0.00 | 570.00 | 0.299154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39084.40 | 04-SEP-08:13 | 20640.43 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.180490E+11 | 0.00 | 461.33 | 0.174630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28456.52 | 03-OCT-08:61 | 20194.83 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.849529E+10 | 0.00 | 283.00 | 0.712001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24520.20 | 12-NOV-13:20 | 17440.75 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.357258E+10 | 0.00 | 152.17 | 0.357258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15709.29 | 25-DEC-16:02 | 15709.29 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236839E+12 | 0.00 | 4962.50 | 0.220417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173081E+10 | 0.00 | 131.50 | 0.173081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13679.85 | 13679.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.374524E+11 | 0.00 | 589.00 | 0.329774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39084.40 | 21845.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.361783E+10 | 0.00 | 489.81 | 0.332192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11452.63 | 08-JAN-19:02 | 10283.22 | 13-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.124692E+10 | 0.00 | 249.73 | 0.914801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10774.50 | 18-FEB-16:01 | 10283.32 | 09-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.282584E+10 | 0.00 | 433.24 | 0.227235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10944.90 | 06-MAR-16:02 | 10283.41 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.865544E+10 | 0.00 | 676.37 | 0.839289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10282.98 | 18-APR-15:01 | 10282.98 | 18-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.102892E+11 | 0.00 | 713.35 | 0.101792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10283.68 | 11-MAY-18:01 | 10283.68 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.133462E+11 | 0.00 | 705.38 | 0.126321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10373.11 | 03-JUN-16:45 | 10373.11 | 03-JUN-16:45 | 0.00 | 0.00 | 0.00 |
July | 0.128796E+11 | 0.00 | 723.84 | 0.105619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11803.90 | 27-JUL-08:61 | 10386.86 | 30-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.126399E+11 | 0.00 | 722.21 | 0.101484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12251.57 | 05-AUG-08:61 | 10380.66 | 07-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.111053E+11 | 0.00 | 694.81 | 0.859100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12929.00 | 04-SEP-08:61 | 10382.12 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.715389E+10 | 0.00 | 637.15 | 0.620896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11359.54 | 03-OCT-08:61 | 10283.47 | 02-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.368788E+10 | 0.00 | 498.87 | 0.309240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12888.46 | 12-NOV-09:02 | 10283.26 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.181789E+10 | 0.00 | 313.76 | 0.180422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10282.59 | 03-DEC-16:01 | 10282.59 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892659E+11 | 0.00 | 6858.51 | 0.781201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.124692E+10 | 0.00 | 249.73 | 0.914801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10282.59 | 10282.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133462E+11 | 0.00 | 723.84 | 0.126321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12929.00 | 10386.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.901007E+09 | 0.00 | 191.39 | 0.809179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11610.90 | 08-JAN-20:12 | 10218.57 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.270874E+09 | 0.00 | 82.92 | 0.186241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10557.77 | 18-FEB-16:01 | 10216.86 | 01-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.121391E+10 | 0.00 | 237.53 | 0.900108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10251.76 | 23-MAR-21:11 | 10251.76 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.710849E+10 | 0.00 | 576.81 | 0.688626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10737.81 | 26-APR-21:51 | 10737.81 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.964691E+10 | 0.00 | 632.57 | 0.954856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11335.34 | 08-MAY-08:61 | 11335.34 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.132026E+11 | 0.00 | 665.00 | 0.125128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11451.41 | 21-JUN-07:42 | 11451.41 | 21-JUN-07:42 | 0.00 | 0.00 | 0.00 |
July | 0.127041E+11 | 0.00 | 703.24 | 0.104364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13414.85 | 27-JUL-08:11 | 11770.51 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.117372E+11 | 0.00 | 676.29 | 0.937071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13611.82 | 28-AUG-18:31 | 10993.69 | 25-AUG-07:31 | 0.00 | 0.00 | 0.00 |
September | 0.957166E+10 | 0.00 | 618.71 | 0.733621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13700.47 | 04-SEP-08:51 | 10443.47 | 08-SEP-06:51 | 0.00 | 0.00 | 0.00 |
October | 0.451319E+10 | 0.00 | 448.73 | 0.376890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13177.83 | 03-OCT-08:61 | 10778.33 | 01-OCT-07:42 | 0.00 | 0.00 | 0.00 |
November | 0.120991E+10 | 0.00 | 246.90 | 0.927245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13031.94 | 13-NOV-16:01 | 10218.58 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.284924E+09 | 0.00 | 73.04 | 0.284087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10217.98 | 03-DEC-16:01 | 10217.98 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723649E+11 | 0.00 | 5153.11 | 0.629666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.270874E+09 | 0.00 | 73.04 | 0.186241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10217.98 | 10216.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132026E+11 | 0.00 | 703.24 | 0.125128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13700.47 | 11770.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.450314E+11 | 0.00 | 596.69 | 0.430305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49552.42 | 14-JAN-13:40 | 49552.42 | 14-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 0.161896E+11 | 0.00 | 371.55 | 0.122780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36908.08 | 01-FEB-14:15 | 36908.08 | 01-FEB-14:15 | 0.00 | 0.00 | 0.00 |
March | 0.188666E+11 | 0.00 | 481.27 | 0.153562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34055.11 | 18-MAR-13:40 | 33968.07 | 18-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.411591E+11 | 0.00 | 684.83 | 0.405875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35011.73 | 14-APR-13:40 | 35011.73 | 14-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.412495E+11 | 0.00 | 738.38 | 0.412495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29578.95 | 09-MAY-17:13 | 29578.95 | 09-MAY-17:13 | 0.00 | 0.00 | 0.00 |
June | 0.533303E+11 | 0.00 | 720.00 | 0.515861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37510.34 | 29-JUN-19:10 | 36953.50 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.555768E+11 | 0.00 | 744.00 | 0.392274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36743.90 | 23-JUL-08:00 | 33231.04 | 21-JUL-20:20 | 0.00 | 0.00 | 0.00 |
August | 0.587627E+11 | 0.00 | 742.92 | 0.412945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40662.70 | 28-AUG-12:30 | 40537.17 | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.591502E+11 | 0.00 | 720.00 | 0.426676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47413.77 | 28-SEP-13:30 | 45362.08 | 28-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.509496E+11 | 0.00 | 683.37 | 0.442027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48883.98 | 18-OCT-13:30 | 48883.98 | 18-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.385067E+11 | 0.00 | 569.54 | 0.343294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51386.88 | 20-NOV-14:30 | 51386.88 | 20-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.325590E+11 | 0.00 | 497.80 | 0.324131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49116.21 | 25-DEC-13:30 | 49116.21 | 25-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.511331E+12 | 0.00 | 7550.34 | 0.438223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.161896E+11 | 0.00 | 371.55 | 0.122780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29578.95 | 29578.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.591502E+11 | 0.00 | 744.00 | 0.515861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51386.88 | 51386.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.911517E+10 | 0.00 | 320.53 | 0.733785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119006.59 | 31-JAN-19:01 | 119006.59 | 31-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.887065E+10 | 0.00 | 304.17 | 0.330942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113237.35 | 27-FEB-19:01 | 113237.35 | 27-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.150543E+11 | 0.00 | 355.59 | 0.919031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121284.88 | 16-MAR-15:01 | 121284.88 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.394496E+11 | 0.00 | 505.49 | 0.367281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122724.88 | 26-APR-21:51 | 122724.88 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.545393E+11 | 0.00 | 577.37 | 0.532953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128999.34 | 20-MAY-08:61 | 128999.34 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.759969E+11 | 0.00 | 641.39 | 0.647375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131669.99 | 11-JUN-08:61 | 131669.99 | 11-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.819535E+11 | 0.00 | 671.27 | 0.548701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131889.04 | 01-JUL-08:61 | 131889.04 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.745938E+11 | 0.00 | 637.41 | 0.470219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123549.49 | 28-AUG-18:31 | 122002.97 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.637552E+11 | 0.00 | 570.11 | 0.374364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123634.46 | 03-SEP-08:52 | 121820.16 | 29-SEP-08:21 | 0.00 | 0.00 | 0.00 |
October | 0.314108E+11 | 0.00 | 449.50 | 0.225137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121227.70 | 19-OCT-15:01 | 121227.70 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.126145E+11 | 0.00 | 314.70 | 0.771342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119439.63 | 10-NOV-16:01 | 119439.63 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.464043E+10 | 0.00 | 211.22 | 0.451876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116487.48 | 03-DEC-09:02 | 116487.48 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471994E+12 | 0.00 | 5558.77 | 0.348673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.464043E+10 | 0.00 | 211.22 | 0.330942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113237.35 | 113237.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.819535E+11 | 0.00 | 671.27 | 0.647375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131889.04 | 131889.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.346248E+10 | 0.00 | 495.76 | 0.315401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10119.28 | 08-JAN-19:02 | 9082.78 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.150612E+10 | 0.00 | 304.37 | 0.105270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10427.10 | 18-FEB-09:02 | 9170.45 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.298515E+10 | 0.00 | 483.96 | 0.238338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9346.01 | 06-MAR-16:02 | 9083.16 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.885317E+10 | 0.00 | 701.19 | 0.861156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9082.25 | 18-APR-15:01 | 9082.25 | 18-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.107179E+11 | 0.00 | 731.57 | 0.106266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9082.96 | 10-MAY-15:01 | 9082.96 | 10-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.137545E+11 | 0.00 | 714.50 | 0.132193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9145.44 | 17-JUN-18:02 | 9145.44 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.137916E+11 | 0.00 | 734.02 | 0.117178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9745.36 | 09-JUL-08:61 | 9184.00 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.134203E+11 | 0.00 | 732.43 | 0.111598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10705.15 | 04-AUG-08:61 | 9170.65 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.115430E+11 | 0.00 | 704.13 | 0.930643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11342.58 | 03-SEP-08:61 | 9142.10 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.748250E+10 | 0.00 | 662.67 | 0.662773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10016.50 | 22-OCT-08:62 | 9164.79 | 07-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.342700E+10 | 0.00 | 500.97 | 0.288462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11813.34 | 13-NOV-16:01 | 9082.48 | 21-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.185226E+10 | 0.00 | 331.78 | 0.183794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9082.72 | 27-DEC-09:02 | 9082.72 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927961E+11 | 0.00 | 7097.35 | 0.825818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.150612E+10 | 0.00 | 304.37 | 0.105270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9082.25 | 9082.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137916E+11 | 0.00 | 734.02 | 0.132193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11813.34 | 9184.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.893807E+09 | 0.00 | 193.76 | 0.790120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10211.09 | 08-JAN-20:12 | 9213.02 | 27-JAN-09:51 | 0.00 | 0.00 | 0.00 |
February | 0.502558E+09 | 0.00 | 118.92 | 0.312056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10229.05 | 18-FEB-09:02 | 9037.77 | 26-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.144461E+10 | 0.00 | 285.21 | 0.108353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9088.92 | 18-MAR-08:51 | 9088.92 | 18-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.705372E+10 | 0.00 | 601.43 | 0.683941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10472.47 | 05-APR-08:51 | 10472.47 | 05-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.968920E+10 | 0.00 | 647.99 | 0.960383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11566.09 | 21-MAY-08:61 | 11566.09 | 21-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.134472E+11 | 0.00 | 676.05 | 0.129377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11532.44 | 13-JUN-07:52 | 11532.44 | 13-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.135534E+11 | 0.00 | 713.64 | 0.115535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12424.79 | 27-JUL-08:11 | 11510.51 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.124556E+11 | 0.00 | 685.69 | 0.103524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12060.75 | 28-AUG-18:31 | 11037.80 | 24-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.989946E+10 | 0.00 | 627.87 | 0.790482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12990.45 | 04-SEP-08:51 | 10331.16 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.473313E+10 | 0.00 | 481.93 | 0.402752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12149.32 | 03-OCT-08:61 | 10281.16 | 17-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.108234E+10 | 0.00 | 229.57 | 0.833360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11439.57 | 13-NOV-16:01 | 9721.43 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.337667E+09 | 0.00 | 86.57 | 0.332708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9025.39 | 25-DEC-16:02 | 9025.39 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.750926E+11 | 0.00 | 5348.62 | 0.665710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.337667E+09 | 0.00 | 86.57 | 0.312056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9025.39 | 9025.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135534E+11 | 0.00 | 713.64 | 0.129377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12990.45 | 11566.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.819799E+09 | 0.00 | 398.33 | 0.759765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.45 | 08-JAN-19:02 | 2723.93 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.277079E+09 | 0.00 | 195.55 | 0.210307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.66 | 18-FEB-16:01 | 2723.95 | 09-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.673221E+09 | 0.00 | 371.72 | 0.555200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.99 | 23-MAR-15:01 | 2723.99 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.218238E+10 | 0.00 | 661.55 | 0.211308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.85 | 18-APR-15:01 | 2723.85 | 18-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.262231E+10 | 0.00 | 710.86 | 0.258994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.99 | 11-MAY-18:01 | 2723.99 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.351696E+10 | 0.00 | 705.44 | 0.332503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2795.90 | 30-JUN-08:61 | 2795.53 | 03-JUN-17:00 | 0.00 | 0.00 | 0.00 |
July | 0.337387E+10 | 0.00 | 724.07 | 0.275819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.38 | 27-JUL-08:61 | 2750.05 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.328967E+10 | 0.00 | 720.78 | 0.263886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3399.78 | 04-AUG-08:61 | 2754.54 | 25-AUG-17:04 | 0.00 | 0.00 | 0.00 |
September | 0.280846E+10 | 0.00 | 692.38 | 0.215101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.01 | 03-SEP-08:61 | 2743.30 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.169305E+10 | 0.00 | 589.46 | 0.145525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.96 | 03-OCT-08:61 | 2724.00 | 30-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.821484E+09 | 0.00 | 412.18 | 0.697438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3427.83 | 12-NOV-16:02 | 2723.93 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.405604E+09 | 0.00 | 252.06 | 0.402531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.75 | 03-DEC-16:01 | 2723.75 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224839E+11 | 0.00 | 6434.38 | 0.196566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.277079E+09 | 0.00 | 195.55 | 0.210307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.75 | 2723.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.351696E+10 | 0.00 | 724.07 | 0.332503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.01 | 2795.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.182800E+09 | 0.00 | 126.38 | 0.169483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2837.26 | 08-JAN-16:01 | 2705.12 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 49871424.96 | 0.00 | 51.21 | 36187805.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2848.57 | 18-FEB-16:01 | 2704.65 | 01-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.275865E+09 | 0.00 | 184.34 | 0.212599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2713.20 | 23-MAR-21:11 | 2713.20 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.181630E+10 | 0.00 | 571.93 | 0.175429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2840.22 | 26-APR-21:51 | 2840.22 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.249177E+10 | 0.00 | 633.71 | 0.246272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2968.31 | 08-MAY-08:61 | 2968.31 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.350318E+10 | 0.00 | 665.85 | 0.331686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2993.59 | 14-JUN-08:61 | 2993.59 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.333906E+10 | 0.00 | 704.08 | 0.273529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3599.77 | 27-JUL-08:11 | 3080.32 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.307791E+10 | 0.00 | 676.46 | 0.245729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3644.72 | 28-AUG-18:31 | 2855.92 | 25-AUG-07:31 | 0.00 | 0.00 | 0.00 |
September | 0.244400E+10 | 0.00 | 619.08 | 0.185199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3715.98 | 04-SEP-08:51 | 2730.77 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.106608E+10 | 0.00 | 409.38 | 0.883383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579.64 | 03-OCT-08:61 | 2735.71 | 16-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.241545E+09 | 0.00 | 172.26 | 0.191372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3518.25 | 13-NOV-16:01 | 2707.52 | 01-NOV-21:52 | 0.00 | 0.00 | 0.00 |
December | 54878234.24 | 0.00 | 43.51 | 54598324.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2704.96 | 03-DEC-16:01 | 2704.96 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185433E+11 | 0.00 | 4858.18 | 0.161261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 49871424.96 | 0.00 | 43.51 | 36187805.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2704.96 | 2704.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.350318E+10 | 0.00 | 704.08 | 0.331686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3715.98 | 3080.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.995928E+10 | 0.00 | 625.96 | 0.898585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22875.74 | 01-JAN-16:02 | 22875.74 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.437378E+10 | 0.00 | 412.79 | 0.264428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22876.64 | 01-FEB-16:01 | 22876.64 | 01-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.517715E+10 | 0.00 | 511.76 | 0.347757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22871.11 | 08-MAR-16:01 | 22871.11 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.104580E+11 | 0.00 | 670.68 | 0.951485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22877.92 | 13-APR-18:01 | 22877.92 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.109011E+11 | 0.00 | 704.17 | 0.103429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22878.37 | 29-MAY-18:01 | 22878.37 | 29-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.144851E+11 | 0.00 | 696.66 | 0.113130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22879.12 | 08-JUN-15:01 | 22879.12 | 08-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.160177E+11 | 0.00 | 718.35 | 0.103548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22858.75 | 03-JUL-15:01 | 22858.75 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.166722E+11 | 0.00 | 717.89 | 0.109742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22876.03 | 25-AUG-15:01 | 22876.03 | 25-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.161365E+11 | 0.00 | 694.04 | 0.102456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22758.70 | 03-SEP-08:61 | 18621.94 | 24-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.122878E+11 | 0.00 | 671.77 | 0.982757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22873.05 | 31-OCT-18:01 | 22873.05 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.890808E+10 | 0.00 | 589.18 | 0.728130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22875.96 | 20-NOV-16:02 | 22875.96 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.729589E+10 | 0.00 | 510.92 | 0.721703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22875.59 | 25-DEC-16:02 | 22875.59 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132673E+12 | 0.00 | 7524.16 | 0.102179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.437378E+10 | 0.00 | 412.79 | 0.264428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22758.70 | 18621.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166722E+11 | 0.00 | 718.35 | 0.113130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22879.12 | 22879.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.71 | 667.64 | 168.07 | 1280.91 | 423.60 | 0.00 | 0.00 | 0.00 |
February | 521.47 | 349.59 | 171.87 | 721.86 | 394.64 | 0.00 | 0.00 | 0.00 |
March | 431.69 | 218.75 | 212.94 | 652.87 | 358.47 | 0.00 | 0.00 | 0.00 |
April | 378.88 | 156.07 | 222.81 | 729.94 | 205.30 | 0.00 | 0.00 | 0.00 |
May | 253.16 | 44.04 | 209.12 | 546.58 | 138.49 | 0.00 | 0.00 | 0.00 |
June | 214.28 | 16.35 | 197.94 | 623.34 | 52.40 | 0.00 | 0.00 | 0.00 |
July | 217.14 | 20.65 | 196.50 | 613.43 | 34.81 | 0.00 | 0.00 | 0.00 |
August | 268.51 | 75.62 | 192.88 | 702.81 | 46.61 | 0.00 | 0.00 | 0.00 |
September | 381.40 | 161.20 | 220.20 | 832.87 | 71.35 | 0.00 | 0.00 | 0.00 |
October | 612.22 | 423.82 | 188.40 | 1042.11 | 254.13 | 0.00 | 0.00 | 0.00 |
November | 719.63 | 552.71 | 166.92 | 1091.94 | 378.02 | 0.00 | 0.00 | 0.00 |
December | 778.28 | 616.61 | 161.67 | 1140.84 | 502.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 467.74 | 275.23 | 192.51 | 832.66 | 237.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.28 | 16.35 | 161.67 | 546.58 | 34.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 835.71 | 667.64 | 222.81 | 1280.91 | 502.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2353.32 | 1880.03 | 473.29 | 3556.97 | 1302.71 | 0.00 | 0.00 | 0.00 |
February | 1468.41 | 984.43 | 483.99 | 1979.99 | 1260.26 | 0.00 | 0.00 | 0.00 |
March | 1215.60 | 615.98 | 599.62 | 1781.77 | 1134.98 | 0.00 | 0.00 | 0.00 |
April | 1066.89 | 439.48 | 627.41 | 2028.36 | 619.80 | 0.00 | 0.00 | 0.00 |
May | 712.87 | 124.01 | 588.87 | 1520.45 | 414.88 | 0.00 | 0.00 | 0.00 |
June | 603.41 | 46.04 | 557.38 | 1752.42 | 150.99 | 0.00 | 0.00 | 0.00 |
July | 611.46 | 58.14 | 553.32 | 1718.48 | 105.53 | 0.00 | 0.00 | 0.00 |
August | 756.09 | 212.94 | 543.15 | 1966.87 | 143.27 | 0.00 | 0.00 | 0.00 |
September | 1074.00 | 453.93 | 620.07 | 2326.71 | 217.02 | 0.00 | 0.00 | 0.00 |
October | 1723.96 | 1193.45 | 530.51 | 2897.43 | 777.80 | 0.00 | 0.00 | 0.00 |
November | 2026.44 | 1556.40 | 470.05 | 3026.36 | 1173.19 | 0.00 | 0.00 | 0.00 |
December | 2191.58 | 1736.32 | 455.26 | 3158.26 | 1548.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.12 | 775.03 | 542.09 | 2312.50 | 735.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.41 | 46.04 | 455.26 | 1520.45 | 105.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2353.32 | 1880.03 | 627.41 | 3556.97 | 1548.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3057.09 | 2442.27 | 614.83 | 4731.10 | 1698.85 | 0.00 | 0.00 | 0.00 |
February | 1907.55 | 1278.83 | 628.73 | 2640.90 | 1684.95 | 0.00 | 0.00 | 0.00 |
March | 1579.13 | 800.19 | 778.94 | 2377.81 | 1512.00 | 0.00 | 0.00 | 0.00 |
April | 1385.95 | 570.91 | 815.04 | 2724.83 | 808.53 | 0.00 | 0.00 | 0.00 |
May | 926.06 | 161.09 | 764.97 | 2049.57 | 542.53 | 0.00 | 0.00 | 0.00 |
June | 783.87 | 59.80 | 724.06 | 2368.46 | 193.96 | 0.00 | 0.00 | 0.00 |
July | 794.32 | 75.52 | 718.79 | 2323.79 | 133.23 | 0.00 | 0.00 | 0.00 |
August | 982.21 | 276.63 | 705.58 | 2649.48 | 178.95 | 0.00 | 0.00 | 0.00 |
September | 1395.19 | 589.68 | 805.51 | 3120.41 | 271.88 | 0.00 | 0.00 | 0.00 |
October | 2239.52 | 1550.35 | 689.17 | 3863.86 | 1012.06 | 0.00 | 0.00 | 0.00 |
November | 2632.46 | 2021.85 | 610.62 | 4024.09 | 1538.11 | 0.00 | 0.00 | 0.00 |
December | 2846.99 | 2255.58 | 591.41 | 4200.09 | 2040.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711.02 | 1006.81 | 704.21 | 3093.55 | 965.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 783.87 | 59.80 | 591.41 | 2049.57 | 133.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3057.09 | 2442.27 | 815.04 | 4731.10 | 2040.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.07 | 77.69 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 145.28 | 75.68 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 131.04 | 68.52 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 152.05 | 31.85 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 119.36 | 19.00 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 141.60 | 5.02 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 142.73 | 3.11 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 157.41 | 3.52 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 180.19 | 6.07 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 213.92 | 41.77 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.71 | 68.76 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.25 | 95.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.80 | 41.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 119.36 | 3.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.07 | 95.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 185.84 | 160.50 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 121.19 | 153.38 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 191.50 | 130.76 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 375.70 | 59.21 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 410.70 | 35.20 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 506.17 | 9.11 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 401.07 | 5.70 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 374.43 | 6.45 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 308.99 | 11.47 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 239.60 | 83.74 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 182.56 | 141.24 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 131.69 | 199.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 286.51 | 82.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 121.19 | 5.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 506.17 | 199.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.49 | 85.22 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.72 | 82.03 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 32.12 | 72.56 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 70.97 | 31.54 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 99.12 | 17.01 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 154.11 | 4.44 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 140.47 | 2.81 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 115.28 | 3.62 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 95.70 | 6.53 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.11 | 46.10 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.90 | 75.99 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.47 | 104.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.14 | 44.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.47 | 2.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 154.11 | 104.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 192.63 | 157.62 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 125.83 | 149.75 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 193.95 | 131.47 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.29 | 60.65 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 409.04 | 35.82 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 503.42 | 9.57 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 400.34 | 5.89 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 374.62 | 7.12 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 309.89 | 12.20 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 243.20 | 84.59 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 187.65 | 139.63 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 138.97 | 193.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 288.70 | 82.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 125.83 | 5.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 503.42 | 193.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.16 | 105.58 | 26.58 | 190.42 | 91.50 | 0.00 | 0.00 | 0.00 |
February | 82.47 | 55.29 | 27.18 | 102.31 | 92.93 | 0.00 | 0.00 | 0.00 |
March | 68.27 | 34.59 | 33.67 | 89.08 | 83.30 | 0.00 | 0.00 | 0.00 |
April | 59.92 | 24.68 | 35.24 | 105.33 | 47.13 | 0.00 | 0.00 | 0.00 |
May | 40.04 | 6.96 | 33.07 | 77.09 | 33.04 | 0.00 | 0.00 | 0.00 |
June | 33.89 | 2.59 | 31.30 | 90.10 | 13.88 | 0.00 | 0.00 | 0.00 |
July | 34.34 | 3.26 | 31.07 | 86.68 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 42.46 | 11.96 | 30.50 | 101.73 | 14.80 | 0.00 | 0.00 | 0.00 |
September | 60.32 | 25.49 | 34.82 | 121.75 | 20.31 | 0.00 | 0.00 | 0.00 |
October | 96.82 | 67.02 | 29.79 | 153.40 | 57.36 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 87.41 | 26.40 | 160.52 | 84.20 | 0.00 | 0.00 | 0.00 |
December | 123.08 | 97.51 | 25.57 | 168.68 | 107.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.97 | 43.53 | 30.44 | 120.75 | 54.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.89 | 2.59 | 25.57 | 77.09 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.16 | 105.58 | 35.24 | 190.42 | 107.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.03 | 0.00 | 16.03 | 16.13 | 67.50 | 0.00 | 0.00 | 0.00 |
February | 18.27 | 0.00 | 18.27 | 10.53 | 67.08 | 0.00 | 0.00 | 0.00 |
March | 24.29 | 0.00 | 24.28 | 27.16 | 57.68 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.44 | 29.30 | 62.16 | 23.13 | 0.00 | 0.00 | 0.00 |
May | 34.89 | 2.96 | 31.92 | 85.68 | 12.06 | 0.00 | 0.00 | 0.00 |
June | 40.29 | 7.36 | 32.93 | 133.64 | 2.58 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 3.70 | 30.76 | 120.34 | 1.78 | 0.00 | 0.00 | 0.00 |
August | 27.73 | 0.68 | 27.05 | 99.76 | 2.23 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 0.02 | 26.14 | 82.55 | 4.14 | 0.00 | 0.00 | 0.00 |
October | 20.22 | 0.00 | 20.22 | 39.46 | 35.32 | 0.00 | 0.00 | 0.00 |
November | 16.85 | 0.00 | 16.85 | 16.56 | 59.89 | 0.00 | 0.00 | 0.00 |
December | 14.98 | 0.00 | 14.98 | 9.48 | 85.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.35 | 1.27 | 24.08 | 58.85 | 34.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 0.00 | 14.98 | 9.48 | 1.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.29 | 7.36 | 32.93 | 133.64 | 85.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 158.71 | 144.88 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 139.33 | 143.15 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 202.30 | 120.86 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 379.03 | 52.68 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 428.85 | 30.67 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 524.37 | 7.87 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 460.63 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 426.79 | 6.17 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 337.16 | 10.68 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 256.15 | 76.77 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 152.86 | 129.27 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 122.17 | 182.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 299.80 | 75.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 122.17 | 5.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 524.37 | 182.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.12 | 77.05 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 143.62 | 75.68 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 129.31 | 68.33 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.38 | 31.68 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 118.54 | 18.80 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 140.99 | 4.77 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 141.49 | 3.03 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 156.45 | 3.51 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 179.52 | 6.02 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.73 | 41.47 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.01 | 68.03 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.07 | 95.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 173.77 | 41.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 118.54 | 3.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.12 | 95.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 17.55 | 84.09 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 11.70 | 82.45 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 30.48 | 72.24 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.23 | 31.41 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 96.52 | 16.77 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 152.75 | 4.26 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 138.91 | 2.75 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 113.90 | 3.62 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 94.46 | 6.57 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 43.58 | 46.07 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.17 | 74.82 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 10.74 | 104.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 66.76 | 43.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 10.74 | 2.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 152.75 | 104.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 165.88 | 141.10 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 144.22 | 139.32 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 204.88 | 121.19 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 376.90 | 53.72 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 422.90 | 30.91 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 519.39 | 8.02 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 459.04 | 5.11 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 425.93 | 6.71 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 336.37 | 11.22 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 258.42 | 77.45 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 157.82 | 126.63 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 129.30 | 174.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 300.85 | 74.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 129.30 | 5.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 519.39 | 174.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 21.68 | 117.68 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 15.45 | 112.67 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 41.33 | 97.36 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 90.72 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 123.96 | 28.63 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 191.43 | 9.28 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 167.70 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 137.50 | 8.58 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 113.82 | 14.64 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 54.05 | 67.91 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 22.71 | 105.93 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 12.74 | 143.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 83.07 | 63.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 12.74 | 6.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 191.43 | 143.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.36 | 0.00 | 9.36 | 7.99 | 43.38 | 0.00 | 0.00 | 0.00 |
February | 10.66 | 0.00 | 10.66 | 5.69 | 41.54 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 0.00 | 14.17 | 15.24 | 35.89 | 0.00 | 0.00 | 0.00 |
April | 17.35 | 0.26 | 17.10 | 33.44 | 17.33 | 0.00 | 0.00 | 0.00 |
May | 20.36 | 1.73 | 18.63 | 45.70 | 10.55 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 4.30 | 19.21 | 70.57 | 3.42 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 2.16 | 17.95 | 61.82 | 2.33 | 0.00 | 0.00 | 0.00 |
August | 16.18 | 0.40 | 15.78 | 50.69 | 3.16 | 0.00 | 0.00 | 0.00 |
September | 15.26 | 0.01 | 15.25 | 41.96 | 5.40 | 0.00 | 0.00 | 0.00 |
October | 11.80 | 0.00 | 11.80 | 19.93 | 25.03 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 0.00 | 9.83 | 8.37 | 39.05 | 0.00 | 0.00 | 0.00 |
December | 8.74 | 0.00 | 8.74 | 4.70 | 52.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.79 | 0.74 | 14.05 | 30.62 | 23.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.74 | 0.00 | 8.74 | 4.70 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.51 | 4.30 | 19.21 | 70.57 | 52.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.10 | 61.59 | 15.51 | 121.88 | 38.78 | 0.00 | 0.00 | 0.00 |
February | 48.11 | 32.25 | 15.86 | 68.55 | 37.44 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 20.18 | 19.64 | 62.00 | 34.22 | 0.00 | 0.00 | 0.00 |
April | 34.95 | 14.40 | 20.56 | 71.34 | 17.87 | 0.00 | 0.00 | 0.00 |
May | 23.36 | 4.06 | 19.29 | 54.86 | 11.85 | 0.00 | 0.00 | 0.00 |
June | 19.77 | 1.51 | 18.26 | 64.08 | 3.95 | 0.00 | 0.00 | 0.00 |
July | 20.03 | 1.90 | 18.13 | 62.68 | 2.58 | 0.00 | 0.00 | 0.00 |
August | 24.77 | 6.98 | 17.79 | 70.34 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 35.19 | 14.87 | 20.31 | 81.40 | 5.35 | 0.00 | 0.00 | 0.00 |
October | 56.48 | 39.10 | 17.38 | 99.23 | 22.99 | 0.00 | 0.00 | 0.00 |
November | 66.39 | 50.99 | 15.40 | 103.64 | 34.91 | 0.00 | 0.00 | 0.00 |
December | 71.80 | 56.88 | 14.92 | 108.91 | 46.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.15 | 25.39 | 17.76 | 80.85 | 21.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.77 | 1.51 | 14.92 | 54.86 | 2.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.10 | 61.59 | 20.56 | 121.88 | 46.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.26 | 167.17 | 42.09 | 330.82 | 105.25 | 0.00 | 0.00 | 0.00 |
February | 130.57 | 87.54 | 43.04 | 186.06 | 101.62 | 0.00 | 0.00 | 0.00 |
March | 108.09 | 54.77 | 53.32 | 168.28 | 92.87 | 0.00 | 0.00 | 0.00 |
April | 94.87 | 39.08 | 55.79 | 193.62 | 48.50 | 0.00 | 0.00 | 0.00 |
May | 63.39 | 11.03 | 52.36 | 148.90 | 32.17 | 0.00 | 0.00 | 0.00 |
June | 53.66 | 4.09 | 49.56 | 173.94 | 10.72 | 0.00 | 0.00 | 0.00 |
July | 54.37 | 5.17 | 49.20 | 170.13 | 7.00 | 0.00 | 0.00 | 0.00 |
August | 67.23 | 18.94 | 48.30 | 190.93 | 9.08 | 0.00 | 0.00 | 0.00 |
September | 95.50 | 40.36 | 55.14 | 220.93 | 14.52 | 0.00 | 0.00 | 0.00 |
October | 153.30 | 106.12 | 47.17 | 269.34 | 62.41 | 0.00 | 0.00 | 0.00 |
November | 180.19 | 138.40 | 41.80 | 281.31 | 94.76 | 0.00 | 0.00 | 0.00 |
December | 194.88 | 154.40 | 40.48 | 295.59 | 126.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.12 | 68.92 | 48.20 | 219.44 | 58.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.66 | 4.09 | 40.48 | 148.90 | 7.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.26 | 167.17 | 55.79 | 330.82 | 126.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 257.45 | 76.89 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 144.16 | 74.81 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 129.77 | 68.04 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 150.76 | 30.93 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 119.11 | 18.09 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 141.42 | 4.57 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 142.84 | 2.91 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 157.23 | 3.21 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 179.59 | 5.52 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.58 | 40.68 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 219.21 | 67.92 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.29 | 94.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 173.95 | 40.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 119.11 | 2.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 257.45 | 94.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 184.22 | 157.93 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 119.55 | 151.01 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 189.34 | 129.25 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 372.25 | 57.47 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 408.24 | 33.60 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 503.16 | 8.42 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 399.76 | 5.38 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 373.18 | 5.97 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 307.98 | 10.54 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 238.13 | 81.27 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 180.83 | 138.83 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 130.60 | 196.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 284.66 | 81.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 119.55 | 5.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 503.16 | 196.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.99 | 83.52 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.75 | 80.61 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 31.96 | 71.92 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 70.74 | 30.74 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 99.29 | 16.26 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 153.70 | 4.14 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 140.51 | 2.66 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 115.46 | 3.37 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 96.04 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.56 | 44.58 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.30 | 74.39 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.93 | 103.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.29 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.93 | 2.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 153.70 | 103.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 191.98 | 154.45 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 124.78 | 147.02 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 192.01 | 130.18 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 373.02 | 58.96 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 406.77 | 34.01 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 500.33 | 8.80 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 399.01 | 5.53 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 373.51 | 6.57 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 309.13 | 11.12 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 242.36 | 81.78 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 186.84 | 136.68 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 138.87 | 190.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 287.27 | 80.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 124.78 | 5.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 500.33 | 190.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 242.33 | 193.60 | 48.74 | 371.97 | 116.96 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 101.37 | 49.84 | 206.62 | 114.69 | 0.00 | 0.00 | 0.00 |
March | 125.18 | 63.43 | 61.75 | 187.71 | 101.40 | 0.00 | 0.00 | 0.00 |
April | 109.86 | 45.26 | 64.61 | 225.34 | 43.84 | 0.00 | 0.00 | 0.00 |
May | 73.41 | 12.77 | 60.64 | 181.73 | 24.86 | 0.00 | 0.00 | 0.00 |
June | 62.14 | 4.74 | 57.40 | 221.19 | 5.44 | 0.00 | 0.00 | 0.00 |
July | 62.97 | 5.99 | 56.98 | 218.00 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 77.86 | 21.93 | 55.93 | 237.86 | 4.21 | 0.00 | 0.00 | 0.00 |
September | 110.60 | 46.74 | 63.85 | 267.26 | 7.61 | 0.00 | 0.00 | 0.00 |
October | 177.53 | 122.90 | 54.63 | 310.41 | 60.59 | 0.00 | 0.00 | 0.00 |
November | 208.67 | 160.27 | 48.40 | 317.16 | 102.85 | 0.00 | 0.00 | 0.00 |
December | 225.68 | 178.80 | 46.88 | 330.60 | 145.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.63 | 79.81 | 55.82 | 256.71 | 60.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.14 | 4.74 | 46.88 | 181.73 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.33 | 193.60 | 64.61 | 371.97 | 145.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 86.88 | 752.10 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 50.74 | 768.67 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 170.85 | 649.27 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 448.78 | 302.29 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 634.94 | 182.09 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1017.69 | 61.31 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 881.22 | 45.29 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 719.39 | 63.29 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 592.64 | 102.13 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 266.01 | 426.56 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 92.23 | 683.59 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 43.85 | 924.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 418.79 | 411.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 43.85 | 45.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1017.69 | 924.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 78.34 | 772.11 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 43.80 | 794.68 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 159.69 | 667.85 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 439.15 | 310.88 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 624.77 | 187.75 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1006.13 | 64.05 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 869.56 | 47.94 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 708.75 | 67.17 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 583.02 | 107.48 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 257.35 | 438.94 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 84.24 | 703.19 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 37.75 | 950.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 409.38 | 424.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 37.75 | 47.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1006.13 | 950.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 15.83 | 107.09 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 9.18 | 109.99 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 28.63 | 94.54 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 72.51 | 46.39 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 101.07 | 30.35 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 155.67 | 12.23 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 135.73 | 9.56 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 113.42 | 12.66 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 94.87 | 18.27 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.18 | 63.21 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 16.58 | 97.64 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 8.74 | 129.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 66.64 | 60.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 8.74 | 9.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 155.67 | 129.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.87 | 151.81 | 90.06 | 318.52 | 361.73 | 0.00 | 0.00 | 0.00 |
February | 240.43 | 138.34 | 102.10 | 273.54 | 375.94 | 0.00 | 0.00 | 0.00 |
March | 298.56 | 153.60 | 144.96 | 396.88 | 320.94 | 0.00 | 0.00 | 0.00 |
April | 425.45 | 253.49 | 171.96 | 765.33 | 162.91 | 0.00 | 0.00 | 0.00 |
May | 441.66 | 262.07 | 179.60 | 861.59 | 112.14 | 0.00 | 0.00 | 0.00 |
June | 459.53 | 285.49 | 174.04 | 1047.39 | 45.83 | 0.00 | 0.00 | 0.00 |
July | 388.70 | 219.32 | 169.38 | 904.29 | 35.67 | 0.00 | 0.00 | 0.00 |
August | 369.23 | 210.95 | 158.27 | 847.59 | 47.41 | 0.00 | 0.00 | 0.00 |
September | 302.56 | 145.93 | 156.63 | 672.34 | 66.76 | 0.00 | 0.00 | 0.00 |
October | 303.63 | 184.69 | 118.94 | 516.63 | 216.37 | 0.00 | 0.00 | 0.00 |
November | 233.65 | 140.21 | 93.44 | 304.55 | 333.20 | 0.00 | 0.00 | 0.00 |
December | 213.43 | 129.08 | 84.35 | 243.62 | 435.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.95 | 189.82 | 137.13 | 597.56 | 208.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.43 | 129.08 | 84.35 | 243.62 | 35.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.53 | 285.49 | 179.60 | 1047.39 | 435.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.72 | 96.17 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 142.87 | 98.89 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 128.45 | 90.05 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 153.64 | 47.56 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 120.33 | 32.99 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 141.49 | 13.18 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 137.82 | 10.05 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 155.72 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 179.52 | 18.24 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 214.43 | 58.27 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.73 | 87.78 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.20 | 114.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.08 | 56.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 120.33 | 10.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.72 | 114.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 19.29 | 118.60 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 13.11 | 115.08 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 37.89 | 99.27 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 85.16 | 49.01 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 118.47 | 30.14 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 186.51 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 161.74 | 7.07 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 132.03 | 9.75 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 108.98 | 16.14 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 51.15 | 68.03 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 20.39 | 106.61 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 10.91 | 145.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 79.11 | 64.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 10.91 | 7.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 186.51 | 145.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.71 | 0.00 | 22.71 | 17.26 | 106.10 | 0.00 | 0.00 | 0.00 |
February | 25.87 | 0.00 | 25.87 | 11.73 | 102.96 | 0.00 | 0.00 | 0.00 |
March | 34.39 | 0.00 | 34.39 | 33.90 | 88.82 | 0.00 | 0.00 | 0.00 |
April | 42.12 | 0.62 | 41.50 | 76.19 | 43.85 | 0.00 | 0.00 | 0.00 |
May | 49.41 | 4.20 | 45.21 | 106.00 | 26.96 | 0.00 | 0.00 | 0.00 |
June | 57.06 | 10.43 | 46.63 | 166.88 | 8.89 | 0.00 | 0.00 | 0.00 |
July | 48.81 | 5.24 | 43.56 | 144.71 | 6.33 | 0.00 | 0.00 | 0.00 |
August | 39.27 | 0.96 | 38.31 | 118.13 | 8.72 | 0.00 | 0.00 | 0.00 |
September | 37.04 | 0.02 | 37.01 | 97.51 | 14.44 | 0.00 | 0.00 | 0.00 |
October | 28.64 | 0.00 | 28.64 | 45.76 | 60.87 | 0.00 | 0.00 | 0.00 |
November | 23.86 | 0.00 | 23.86 | 18.24 | 95.38 | 0.00 | 0.00 | 0.00 |
December | 21.21 | 0.00 | 21.21 | 9.76 | 129.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.90 | 1.79 | 34.11 | 70.78 | 57.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 0.00 | 21.21 | 9.76 | 6.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.06 | 10.43 | 46.63 | 166.88 | 129.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.87 | 492.81 | 124.06 | 960.13 | 313.64 | 0.00 | 0.00 | 0.00 |
February | 384.91 | 258.05 | 126.87 | 535.94 | 306.45 | 0.00 | 0.00 | 0.00 |
March | 318.65 | 161.47 | 157.18 | 481.30 | 280.42 | 0.00 | 0.00 | 0.00 |
April | 279.66 | 115.20 | 164.46 | 550.86 | 149.16 | 0.00 | 0.00 | 0.00 |
May | 186.87 | 32.51 | 154.36 | 422.20 | 99.41 | 0.00 | 0.00 | 0.00 |
June | 158.17 | 12.07 | 146.11 | 499.07 | 33.46 | 0.00 | 0.00 | 0.00 |
July | 160.28 | 15.24 | 145.04 | 483.96 | 22.82 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 55.82 | 142.38 | 545.54 | 30.15 | 0.00 | 0.00 | 0.00 |
September | 281.53 | 118.99 | 162.54 | 633.84 | 47.05 | 0.00 | 0.00 | 0.00 |
October | 451.90 | 312.84 | 139.06 | 779.55 | 184.96 | 0.00 | 0.00 | 0.00 |
November | 531.19 | 407.98 | 123.21 | 815.49 | 282.03 | 0.00 | 0.00 | 0.00 |
December | 574.48 | 455.14 | 119.34 | 858.61 | 378.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.26 | 203.16 | 142.10 | 631.38 | 176.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.17 | 12.07 | 119.34 | 422.20 | 22.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.87 | 492.81 | 164.46 | 960.13 | 378.15 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.343079E+10 | 0.113458E+10 |
February | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.174631E+10 | 0.954712E+09 |
March | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.174864E+10 | 0.960113E+09 |
April | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.189201E+10 | 0.532146E+09 |
May | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.146395E+10 | 0.370920E+09 |
June | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.161570E+10 | 0.135817E+09 |
July | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.164302E+10 | 93236497.02 |
August | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.188241E+10 | 0.124841E+09 |
September | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.215880E+10 | 0.184950E+09 |
October | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.279118E+10 | 0.680652E+09 |
November | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.283032E+10 | 0.979825E+09 |
December | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.305562E+10 | 0.134459E+10 |
Annual Sum or Average | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.262588E+11 | 0.749639E+10 |
Minimum of Months | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.146395E+10 | 93236497.02 |
Maximum of Months | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.343079E+10 | 0.134459E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.952699E+10 | 0.348919E+10 |
February | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.479000E+10 | 0.304883E+10 |
March | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.477229E+10 | 0.303994E+10 |
April | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.525752E+10 | 0.160653E+10 |
May | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.407238E+10 | 0.111121E+10 |
June | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.454226E+10 | 0.391364E+09 |
July | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.460277E+10 | 0.282645E+09 |
August | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.526805E+10 | 0.383729E+09 |
September | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.603083E+10 | 0.562514E+09 |
October | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.776047E+10 | 0.208326E+10 |
November | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.784432E+10 | 0.304090E+10 |
December | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.845907E+10 | 0.414776E+10 |
Annual Sum or Average | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.729270E+11 | 0.231879E+11 |
Minimum of Months | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.407238E+10 | 0.282645E+09 |
Maximum of Months | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.952699E+10 | 0.414776E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.126718E+11 | 0.455021E+10 |
February | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.638887E+10 | 0.407622E+10 |
March | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.636872E+10 | 0.404974E+10 |
April | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.706277E+10 | 0.209571E+10 |
May | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.548958E+10 | 0.145312E+10 |
June | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.613904E+10 | 0.502734E+09 |
July | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.622404E+10 | 0.356832E+09 |
August | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.709635E+10 | 0.479299E+09 |
September | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.808809E+10 | 0.704707E+09 |
October | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.103490E+11 | 0.271069E+10 |
November | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.104305E+11 | 0.398677E+10 |
December | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.112495E+11 | 0.546653E+10 |
Annual Sum or Average | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.975582E+11 | 0.304326E+11 |
Minimum of Months | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.548958E+10 | 0.356832E+09 |
Maximum of Months | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.126718E+11 | 0.546653E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.693904E+09 | 0.208081E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.351452E+09 | 0.183078E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.350972E+09 | 0.183535E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.394126E+09 | 82546916.31 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.319702E+09 | 50895975.95 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.367020E+09 | 13003191.55 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.382287E+09 | 8331883.57 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.421619E+09 | 9426056.35 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.467052E+09 | 15743099.12 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.572955E+09 | 0.111883E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.572076E+09 | 0.178230E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619384E+09 | 0.256470E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.551255E+10 | 0.130122E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.319702E+09 | 8331883.57 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.693904E+09 | 0.256470E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.497747E+09 | 0.429885E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.293184E+09 | 0.371050E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.512922E+09 | 0.350223E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.973802E+09 | 0.153465E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110002E+10 | 94278678.73 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.131199E+10 | 23604369.50 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107423E+10 | 15278282.45 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100288E+10 | 17275674.66 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.800891E+09 | 29728222.82 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.641754E+09 | 0.224284E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.473195E+09 | 0.366092E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.352706E+09 | 0.533795E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.903532E+10 | 0.260896E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.293184E+09 | 15278282.45 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.131199E+10 | 0.533795E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 49516130.35 | 0.228255E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30771947.98 | 0.198459E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 86033787.22 | 0.194336E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.183947E+09 | 81757901.96 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.265485E+09 | 45567028.58 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.399457E+09 | 11513324.72 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.376222E+09 | 7533821.22 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.308767E+09 | 9704938.04 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.248060E+09 | 16937976.73 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.120821E+09 | 0.123474E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 48993201.24 | 0.196968E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 30721527.18 | 0.281162E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.214879E+10 | 0.139567E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30721527.18 | 7533821.22 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.399457E+09 | 0.281162E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.515944E+09 | 0.422160E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.304402E+09 | 0.362283E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.519471E+09 | 0.352133E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.975348E+09 | 0.157202E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109557E+10 | 95948975.81 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130486E+10 | 24805398.23 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107227E+10 | 15764078.43 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100339E+10 | 19070065.96 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.803245E+09 | 31629907.13 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.651385E+09 | 0.226558E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.486378E+09 | 0.361927E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.372207E+09 | 0.518317E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.910447E+10 | 0.258780E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.304402E+09 | 15764078.43 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130486E+10 | 0.518317E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.510015E+09 | 0.245076E+09 |
February | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.247519E+09 | 0.224808E+09 |
March | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.238586E+09 | 0.223122E+09 |
April | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.273022E+09 | 0.122151E+09 |
May | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.206469E+09 | 88484835.82 |
June | 87837819.98 | 6701448.63 | 81136371.35 | 0.233538E+09 | 35988796.44 |
July | 91975290.32 | 8744924.55 | 83230365.76 | 0.232176E+09 | 29510513.14 |
August | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.272462E+09 | 39643469.11 |
September | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.315584E+09 | 52640471.50 |
October | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.410877E+09 | 0.153620E+09 |
November | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.416065E+09 | 0.218235E+09 |
December | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.451788E+09 | 0.288355E+09 |
Annual Sum or Average | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.380810E+10 | 0.172164E+10 |
Minimum of Months | 87837819.98 | 6701448.63 | 65755807.07 | 0.206469E+09 | 29510513.14 |
Maximum of Months | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.510015E+09 | 0.288355E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42944949.46 | 0.00 | 42944949.46 | 43192655.83 | 0.180793E+09 |
February | 44199004.85 | 0.00 | 44199004.85 | 25467981.31 | 0.162281E+09 |
March | 65045237.58 | 2573.27 | 65042664.31 | 72752022.14 | 0.154487E+09 |
April | 77090857.89 | 1135053.46 | 75955804.43 | 0.161110E+09 | 59959368.02 |
May | 93441433.49 | 7934259.35 | 85507174.14 | 0.229487E+09 | 32294418.21 |
June | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.346401E+09 | 6681597.56 |
July | 92312481.83 | 9919050.97 | 82393430.86 | 0.322325E+09 | 4756200.65 |
August | 74279179.59 | 1823766.12 | 72455413.47 | 0.267200E+09 | 5964374.05 |
September | 67785290.05 | 41951.47 | 67743338.59 | 0.213965E+09 | 10735103.68 |
October | 54159300.98 | 0.00 | 54159300.98 | 0.105697E+09 | 94588139.47 |
November | 43668987.75 | 0.00 | 43668987.75 | 42927135.72 | 0.155234E+09 |
December | 40114513.77 | 0.00 | 40114513.77 | 25390333.90 | 0.228125E+09 |
Annual Sum or Average | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.185591E+10 | 0.109590E+10 |
Minimum of Months | 40114513.77 | 0.00 | 40114513.77 | 25390333.90 | 4756200.65 |
Maximum of Months | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.346401E+09 | 0.228125E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.425081E+09 | 0.388050E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.337064E+09 | 0.346304E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.541828E+09 | 0.323719E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.982451E+09 | 0.136555E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114863E+10 | 82158436.59 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.135917E+10 | 20405790.56 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.123374E+10 | 13555715.72 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.114312E+10 | 16527616.57 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.873917E+09 | 27689823.60 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.686072E+09 | 0.205624E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.396219E+09 | 0.335063E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.327228E+09 | 0.487548E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.945452E+10 | 0.238320E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.327228E+09 | 13555715.72 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.135917E+10 | 0.487548E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.691352E+09 | 0.206366E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.347440E+09 | 0.183084E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.346342E+09 | 0.183017E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.392379E+09 | 82120695.79 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.317486E+09 | 50346204.94 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.365451E+09 | 12355302.42 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.378964E+09 | 8125720.35 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.419041E+09 | 9397565.34 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.465306E+09 | 15614473.14 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.569774E+09 | 0.111081E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570263E+09 | 0.176328E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.616215E+09 | 0.255653E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.548001E+10 | 0.129349E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.317486E+09 | 8125720.35 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.691352E+09 | 0.255653E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 46999400.98 | 0.225216E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 28315722.83 | 0.199459E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 81629408.72 | 0.193494E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.179452E+09 | 81416580.14 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.258520E+09 | 44910199.68 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.395923E+09 | 11037874.47 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.372050E+09 | 7361891.32 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.305068E+09 | 9695469.47 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.244850E+09 | 17027347.05 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.116728E+09 | 0.123406E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 47093160.83 | 0.193927E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 28764478.89 | 0.279892E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.210539E+10 | 0.138684E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 28315722.83 | 7361891.32 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.395923E+09 | 0.279892E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.444295E+09 | 0.377934E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.348887E+09 | 0.337045E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.548757E+09 | 0.324607E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.976928E+09 | 0.139239E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.113268E+10 | 82780346.96 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.134626E+10 | 20786667.94 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.122949E+10 | 13687686.22 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.114081E+10 | 17960633.86 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.871874E+09 | 29076691.66 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.692149E+09 | 0.207452E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.409064E+09 | 0.328213E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.346317E+09 | 0.468659E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.948751E+10 | 0.234744E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.346317E+09 | 13687686.22 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.134626E+10 | 0.468659E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 58073716.02 | 0.315204E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 37364845.62 | 0.272578E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.110705E+09 | 0.260773E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.235134E+09 | 0.121825E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.332020E+09 | 76679285.75 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.496188E+09 | 24043927.23 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.449159E+09 | 16929494.73 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.368281E+09 | 22985187.72 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.295021E+09 | 37952133.16 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.144770E+09 | 0.181894E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 58876403.89 | 0.274573E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 34122523.45 | 0.385035E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.261972E+10 | 0.199047E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 34122523.45 | 16929494.73 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.496188E+09 | 0.385035E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25058335.32 | 0.00 | 25058335.32 | 21408376.37 | 0.116197E+09 |
February | 25790075.39 | 0.00 | 25790075.39 | 13774229.25 | 0.100483E+09 |
March | 37953831.47 | 1501.50 | 37952329.97 | 40810584.75 | 96131855.82 |
April | 44982438.94 | 662302.56 | 44320136.38 | 86680222.56 | 44909766.36 |
May | 54522983.56 | 4629632.44 | 49893351.11 | 0.122396E+09 | 28267159.77 |
June | 60934981.96 | 11133860.83 | 49801121.12 | 0.182916E+09 | 8863587.16 |
July | 53864241.38 | 5787756.38 | 48076485.00 | 0.165579E+09 | 6240912.75 |
August | 43341827.45 | 1064165.72 | 42277661.74 | 0.135764E+09 | 8473291.94 |
September | 39552649.37 | 24478.64 | 39528170.73 | 0.108757E+09 | 13990727.76 |
October | 31601898.29 | 0.00 | 31601898.29 | 53368285.89 | 67053535.34 |
November | 25480810.94 | 0.00 | 25480810.94 | 21704280.35 | 0.101219E+09 |
December | 23406778.91 | 0.00 | 23406778.91 | 12578975.05 | 0.141940E+09 |
Annual Sum or Average | 0.466491E+09 | 23303698.08 | 0.443187E+09 | 0.965736E+09 | 0.733770E+09 |
Minimum of Months | 23406778.91 | 0.00 | 23406778.91 | 12578975.05 | 6240912.75 |
Maximum of Months | 60934981.96 | 11133860.83 | 49893351.11 | 0.182916E+09 | 0.141940E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206500E+09 | 0.164969E+09 | 41530470.22 | 0.326456E+09 | 0.103864E+09 |
February | 0.116382E+09 | 78022138.43 | 38359370.38 | 0.165837E+09 | 90576578.46 |
March | 0.106667E+09 | 54051088.25 | 52616188.64 | 0.166057E+09 | 91645339.37 |
April | 90598271.93 | 37319698.27 | 53278573.67 | 0.184903E+09 | 46318465.43 |
May | 62554278.62 | 10881561.56 | 51672717.06 | 0.146936E+09 | 31747960.81 |
June | 51241154.51 | 3909363.47 | 47331791.04 | 0.166105E+09 | 10233320.64 |
July | 53654793.16 | 5101447.54 | 48553345.62 | 0.167882E+09 | 6907659.53 |
August | 66346579.02 | 18685521.81 | 47661057.22 | 0.188410E+09 | 8960085.74 |
September | 91202342.18 | 38546673.46 | 52655668.72 | 0.210979E+09 | 13866330.31 |
October | 0.151275E+09 | 0.104723E+09 | 46552209.79 | 0.265788E+09 | 61581980.72 |
November | 0.172081E+09 | 0.132165E+09 | 39915655.96 | 0.268644E+09 | 90489817.57 |
December | 0.192308E+09 | 0.152359E+09 | 39948749.01 | 0.291692E+09 | 0.125253E+09 |
Annual Sum or Average | 0.136081E+10 | 0.800734E+09 | 0.560076E+09 | 0.254969E+10 | 0.681444E+09 |
Minimum of Months | 51241154.51 | 3909363.47 | 38359370.38 | 0.146936E+09 | 6907659.53 |
Maximum of Months | 0.206500E+09 | 0.164969E+09 | 53278573.67 | 0.326456E+09 | 0.125253E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560483E+09 | 0.447760E+09 | 0.112722E+09 | 0.886069E+09 | 0.281907E+09 |
February | 0.315883E+09 | 0.211768E+09 | 0.104115E+09 | 0.450117E+09 | 0.245843E+09 |
March | 0.289517E+09 | 0.146706E+09 | 0.142811E+09 | 0.450713E+09 | 0.248744E+09 |
April | 0.245902E+09 | 0.101293E+09 | 0.144609E+09 | 0.501865E+09 | 0.125717E+09 |
May | 0.169785E+09 | 29534783.85 | 0.140250E+09 | 0.398813E+09 | 86170459.54 |
June | 0.139079E+09 | 10610812.10 | 0.128468E+09 | 0.450844E+09 | 27775325.39 |
July | 0.145630E+09 | 13846372.09 | 0.131784E+09 | 0.455665E+09 | 18748800.90 |
August | 0.180078E+09 | 50716328.22 | 0.129362E+09 | 0.511383E+09 | 24319505.44 |
September | 0.247542E+09 | 0.104624E+09 | 0.142918E+09 | 0.572639E+09 | 37636056.75 |
October | 0.410591E+09 | 0.284239E+09 | 0.126352E+09 | 0.721404E+09 | 0.167146E+09 |
November | 0.467063E+09 | 0.358724E+09 | 0.108339E+09 | 0.729155E+09 | 0.245608E+09 |
December | 0.521963E+09 | 0.413534E+09 | 0.108429E+09 | 0.791713E+09 | 0.339962E+09 |
Annual Sum or Average | 0.369352E+10 | 0.217336E+10 | 0.152016E+10 | 0.692038E+10 | 0.184958E+10 |
Minimum of Months | 0.139079E+09 | 10610812.10 | 0.104115E+09 | 0.398813E+09 | 18748800.90 |
Maximum of Months | 0.560483E+09 | 0.447760E+09 | 0.144609E+09 | 0.886069E+09 | 0.339962E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.689555E+09 | 0.205953E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.348742E+09 | 0.180978E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.347566E+09 | 0.182237E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.390762E+09 | 80169447.21 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.319021E+09 | 48440456.06 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.366564E+09 | 11848347.96 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.382593E+09 | 7789260.39 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.421129E+09 | 8610123.58 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.465507E+09 | 14301398.27 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.569382E+09 | 0.108970E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.568200E+09 | 0.176043E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.616800E+09 | 0.254239E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.548582E+10 | 0.127958E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.319021E+09 | 7789260.39 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.689555E+09 | 0.254239E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.493411E+09 | 0.423003E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.289221E+09 | 0.365315E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.507128E+09 | 0.346177E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.964865E+09 | 0.148958E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109342E+10 | 89984173.47 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130420E+10 | 21818776.94 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107071E+10 | 14414780.11 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.999534E+09 | 15985589.57 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.798295E+09 | 27332287.43 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.637812E+09 | 0.217685E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.468723E+09 | 0.359843E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.349801E+09 | 0.526199E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.897712E+10 | 0.255672E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.289221E+09 | 14414780.11 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130420E+10 | 0.526199E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 50868575.17 | 0.223713E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30844236.69 | 0.195007E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 85604985.23 | 0.192636E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.183347E+09 | 79675646.97 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.265931E+09 | 43551521.09 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.398393E+09 | 10719859.07 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.376352E+09 | 7126609.84 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.309235E+09 | 9020423.95 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.248926E+09 | 15468110.27 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.122017E+09 | 0.119391E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 50015555.54 | 0.192830E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 31954484.67 | 0.276097E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.215349E+10 | 0.136524E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30844236.69 | 7126609.84 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.398393E+09 | 0.276097E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.514206E+09 | 0.413690E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.301876E+09 | 0.355679E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.514268E+09 | 0.348666E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.966873E+09 | 0.152832E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.108950E+10 | 91098712.44 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.129686E+10 | 22797938.97 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.106870E+10 | 14798607.78 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100040E+10 | 17591445.93 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.801272E+09 | 28826959.10 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.649146E+09 | 0.219041E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.484277E+09 | 0.354278E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.371961E+09 | 0.509223E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.905934E+10 | 0.252852E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.301876E+09 | 14798607.78 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.129686E+10 | 0.509223E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.996279E+09 | 0.313268E+09 |
February | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.499852E+09 | 0.277456E+09 |
March | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.502765E+09 | 0.271585E+09 |
April | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.584079E+09 | 0.113621E+09 |
May | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.486744E+09 | 66571840.25 |
June | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.573331E+09 | 14096427.17 |
July | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.583892E+09 | 10031114.92 |
August | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.637076E+09 | 11279940.79 |
September | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.692749E+09 | 19722528.65 |
October | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.831390E+09 | 0.162283E+09 |
November | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.822067E+09 | 0.266599E+09 |
December | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.885488E+09 | 0.389916E+09 |
Annual Sum or Average | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.809571E+10 | 0.191643E+10 |
Minimum of Months | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.486744E+09 | 10031114.92 |
Maximum of Months | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.996279E+09 | 0.389916E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.232706E+09 | 0.201443E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.122760E+09 | 0.185956E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.457601E+09 | 0.173900E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.116323E+10 | 0.783548E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.170061E+10 | 0.487707E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.263785E+10 | 0.158904E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.236026E+10 | 0.121295E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.192683E+10 | 0.169515E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.153611E+10 | 0.264718E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.712475E+09 | 0.114249E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.239053E+09 | 0.177187E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.117455E+09 | 0.247485E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.132070E+11 | 0.129879E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.117455E+09 | 0.121295E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.263785E+10 | 0.247485E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.209821E+09 | 0.206803E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.105955E+09 | 0.192249E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.427716E+09 | 0.178876E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.113829E+10 | 0.805800E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.167339E+10 | 0.502867E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.260789E+10 | 0.166014E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.232904E+10 | 0.128399E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.189831E+10 | 0.179907E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.151120E+10 | 0.278591E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.689294E+09 | 0.117565E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.218359E+09 | 0.182268E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.101110E+09 | 0.254494E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.129104E+11 | 0.133841E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.101110E+09 | 0.128399E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.260789E+10 | 0.254494E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 42398108.33 | 0.286829E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 22201156.94 | 0.266089E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 76684370.27 | 0.253207E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.187957E+09 | 0.120245E+09 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.270698E+09 | 81287989.43 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.403500E+09 | 31703217.36 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.363551E+09 | 25607775.89 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.303774E+09 | 33905754.18 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.245916E+09 | 47365940.56 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.118325E+09 | 0.169299E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 42987040.78 | 0.253094E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 23417681.61 | 0.346608E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.210141E+10 | 0.191524E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 22201156.94 | 25607775.89 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.403500E+09 | 0.346608E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647832E+09 | 0.406608E+09 | 0.241223E+09 | 0.853128E+09 | 0.968868E+09 |
February | 0.581660E+09 | 0.334662E+09 | 0.246998E+09 | 0.661738E+09 | 0.909471E+09 |
March | 0.799654E+09 | 0.411405E+09 | 0.388250E+09 | 0.106299E+10 | 0.859614E+09 |
April | 0.110278E+10 | 0.657056E+09 | 0.445720E+09 | 0.198374E+10 | 0.422272E+09 |
May | 0.118295E+10 | 0.701920E+09 | 0.481032E+09 | 0.230769E+10 | 0.300363E+09 |
June | 0.119111E+10 | 0.739991E+09 | 0.451119E+09 | 0.271483E+10 | 0.118783E+09 |
July | 0.104108E+10 | 0.587423E+09 | 0.453658E+09 | 0.242204E+10 | 95534548.84 |
August | 0.988937E+09 | 0.565014E+09 | 0.423923E+09 | 0.227018E+10 | 0.126984E+09 |
September | 0.784240E+09 | 0.378243E+09 | 0.405997E+09 | 0.174270E+10 | 0.173044E+09 |
October | 0.813243E+09 | 0.494683E+09 | 0.318561E+09 | 0.138375E+10 | 0.579519E+09 |
November | 0.605626E+09 | 0.363437E+09 | 0.242189E+09 | 0.789403E+09 | 0.863659E+09 |
December | 0.571644E+09 | 0.345721E+09 | 0.225923E+09 | 0.652514E+09 | 0.116624E+10 |
Annual Sum or Average | 0.103108E+11 | 0.598616E+10 | 0.432459E+10 | 0.188447E+11 | 0.658436E+10 |
Minimum of Months | 0.571644E+09 | 0.334662E+09 | 0.225923E+09 | 0.652514E+09 | 95534548.84 |
Maximum of Months | 0.119111E+10 | 0.739991E+09 | 0.481032E+09 | 0.271483E+10 | 0.116624E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.695641E+09 | 0.257591E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.345625E+09 | 0.239229E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.344028E+09 | 0.241195E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.398231E+09 | 0.123284E+09 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.322294E+09 | 88363305.65 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.366737E+09 | 34162914.84 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.369131E+09 | 26928670.80 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.417080E+09 | 34678742.50 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.465307E+09 | 47269282.16 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.574340E+09 | 0.156077E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.572137E+09 | 0.227514E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619257E+09 | 0.305723E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.548981E+10 | 0.178202E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.322294E+09 | 26928670.80 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.695641E+09 | 0.305723E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 51674503.24 | 0.317667E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 31716167.05 | 0.278398E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.101485E+09 | 0.265878E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.220734E+09 | 0.127042E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.317321E+09 | 80719274.27 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.483446E+09 | 25749719.51 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.433213E+09 | 18941238.72 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.353622E+09 | 26107621.30 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.282486E+09 | 41845011.28 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.136987E+09 | 0.182205E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 52841614.30 | 0.276341E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 29211691.06 | 0.388960E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.249474E+10 | 0.202985E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 29211691.06 | 18941238.72 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.483446E+09 | 0.388960E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60817333.99 | 0.00 | 60817333.99 | 46233373.84 | 0.284187E+09 |
February | 62593289.17 | 0.00 | 62593289.17 | 28376574.84 | 0.249083E+09 |
March | 92115091.26 | 3644.19 | 92111447.08 | 90798575.41 | 0.237882E+09 |
April | 0.109174E+09 | 1607428.26 | 0.107566E+09 | 0.197492E+09 | 0.113665E+09 |
May | 0.132329E+09 | 11236257.28 | 0.121093E+09 | 0.283909E+09 | 72219840.54 |
June | 0.147891E+09 | 27022215.34 | 0.120869E+09 | 0.432541E+09 | 23038371.61 |
July | 0.130730E+09 | 14047058.93 | 0.116683E+09 | 0.387597E+09 | 16946798.05 |
August | 0.105192E+09 | 2582762.23 | 0.102609E+09 | 0.316387E+09 | 23358587.70 |
September | 95995470.41 | 59410.39 | 95936060.02 | 0.252741E+09 | 37438890.15 |
October | 76698758.25 | 0.00 | 76698758.25 | 0.122563E+09 | 0.163022E+09 |
November | 61842695.04 | 0.00 | 61842695.04 | 47277592.53 | 0.247234E+09 |
December | 56808956.88 | 0.00 | 56808956.88 | 26135810.67 | 0.347960E+09 |
Annual Sum or Average | 0.113219E+10 | 56558776.60 | 0.107563E+10 | 0.223205E+10 | 0.181604E+10 |
Minimum of Months | 56808956.88 | 0.00 | 56808956.88 | 26135810.67 | 16946798.05 |
Maximum of Months | 0.147891E+09 | 27022215.34 | 0.121093E+09 | 0.432541E+09 | 0.347960E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165223E+10 | 0.131994E+10 | 0.332291E+09 | 0.257160E+10 | 0.840056E+09 |
February | 0.931184E+09 | 0.624266E+09 | 0.306919E+09 | 0.129654E+10 | 0.741360E+09 |
March | 0.853459E+09 | 0.432470E+09 | 0.420989E+09 | 0.128910E+10 | 0.751074E+09 |
April | 0.724889E+09 | 0.298600E+09 | 0.426289E+09 | 0.142783E+10 | 0.386621E+09 |
May | 0.500505E+09 | 87064857.88 | 0.413440E+09 | 0.113082E+10 | 0.266258E+09 |
June | 0.409987E+09 | 31279350.23 | 0.378708E+09 | 0.129358E+10 | 86737148.02 |
July | 0.429299E+09 | 40817377.39 | 0.388482E+09 | 0.129625E+10 | 61128477.49 |
August | 0.530848E+09 | 0.149505E+09 | 0.381343E+09 | 0.146119E+10 | 80746177.55 |
September | 0.729722E+09 | 0.308417E+09 | 0.421305E+09 | 0.164290E+10 | 0.121952E+09 |
October | 0.121037E+10 | 0.837901E+09 | 0.372471E+09 | 0.208796E+10 | 0.495390E+09 |
November | 0.137684E+10 | 0.105747E+10 | 0.319371E+09 | 0.211375E+10 | 0.731016E+09 |
December | 0.153868E+10 | 0.121905E+10 | 0.319635E+09 | 0.229971E+10 | 0.101284E+10 |
Annual Sum or Average | 0.108880E+11 | 0.640678E+10 | 0.448124E+10 | 0.199112E+11 | 0.557517E+10 |
Minimum of Months | 0.409987E+09 | 31279350.23 | 0.306919E+09 | 0.113082E+10 | 61128477.49 |
Maximum of Months | 0.165223E+10 | 0.131994E+10 | 0.426289E+09 | 0.257160E+10 | 0.101284E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1280.91 | 423.60 | 835.71 | 667.64 | 168.07 | 0.00 | 0.00 |
February | 721.86 | 394.64 | 521.47 | 349.59 | 171.87 | 0.00 | 0.00 |
March | 652.87 | 358.47 | 431.69 | 218.75 | 212.94 | 0.00 | 0.00 |
April | 729.94 | 205.30 | 378.88 | 156.07 | 222.81 | 0.00 | 0.00 |
May | 546.58 | 138.49 | 253.16 | 44.04 | 209.12 | 0.00 | 0.00 |
June | 623.34 | 52.40 | 214.28 | 16.35 | 197.94 | 0.00 | 0.00 |
July | 613.43 | 34.81 | 217.14 | 20.65 | 196.50 | 0.00 | 0.00 |
August | 702.81 | 46.61 | 268.51 | 75.62 | 192.88 | 0.00 | 0.00 |
September | 832.87 | 71.35 | 381.40 | 161.20 | 220.20 | 0.00 | 0.00 |
October | 1042.11 | 254.13 | 612.22 | 423.82 | 188.40 | 0.00 | 0.00 |
November | 1091.94 | 378.02 | 719.63 | 552.71 | 166.92 | 0.00 | 0.00 |
December | 1140.84 | 502.01 | 778.28 | 616.61 | 161.67 | 0.00 | 0.00 |
Annual Sum or Average | 832.66 | 237.71 | 467.74 | 275.23 | 192.51 | 0.00 | 0.00 |
Minimum of Months | 546.58 | 34.81 | 214.28 | 16.35 | 161.67 | 0.00 | 0.00 |
Maximum of Months | 1280.91 | 502.01 | 835.71 | 667.64 | 222.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3556.97 | 1302.71 | 2353.32 | 1880.03 | 473.29 | 0.00 | 0.00 |
February | 1979.99 | 1260.26 | 1468.41 | 984.43 | 483.99 | 0.00 | 0.00 |
March | 1781.77 | 1134.98 | 1215.60 | 615.98 | 599.62 | 0.00 | 0.00 |
April | 2028.36 | 619.80 | 1066.89 | 439.48 | 627.41 | 0.00 | 0.00 |
May | 1520.45 | 414.88 | 712.87 | 124.01 | 588.87 | 0.00 | 0.00 |
June | 1752.42 | 150.99 | 603.41 | 46.04 | 557.38 | 0.00 | 0.00 |
July | 1718.48 | 105.53 | 611.46 | 58.14 | 553.32 | 0.00 | 0.00 |
August | 1966.87 | 143.27 | 756.09 | 212.94 | 543.15 | 0.00 | 0.00 |
September | 2326.71 | 217.02 | 1074.00 | 453.93 | 620.07 | 0.00 | 0.00 |
October | 2897.43 | 777.80 | 1723.96 | 1193.45 | 530.51 | 0.00 | 0.00 |
November | 3026.36 | 1173.19 | 2026.44 | 1556.40 | 470.05 | 0.00 | 0.00 |
December | 3158.26 | 1548.60 | 2191.58 | 1736.32 | 455.26 | 0.00 | 0.00 |
Annual Sum or Average | 2312.50 | 735.28 | 1317.12 | 775.03 | 542.09 | 0.00 | 0.00 |
Minimum of Months | 1520.45 | 105.53 | 603.41 | 46.04 | 455.26 | 0.00 | 0.00 |
Maximum of Months | 3556.97 | 1548.60 | 2353.32 | 1880.03 | 627.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4731.10 | 1698.85 | 3057.09 | 2442.27 | 614.83 | 0.00 | 0.00 |
February | 2640.90 | 1684.95 | 1907.55 | 1278.83 | 628.73 | 0.00 | 0.00 |
March | 2377.81 | 1512.00 | 1579.13 | 800.19 | 778.94 | 0.00 | 0.00 |
April | 2724.83 | 808.53 | 1385.95 | 570.91 | 815.04 | 0.00 | 0.00 |
May | 2049.57 | 542.53 | 926.06 | 161.09 | 764.97 | 0.00 | 0.00 |
June | 2368.46 | 193.96 | 783.87 | 59.80 | 724.06 | 0.00 | 0.00 |
July | 2323.79 | 133.23 | 794.32 | 75.52 | 718.79 | 0.00 | 0.00 |
August | 2649.48 | 178.95 | 982.21 | 276.63 | 705.58 | 0.00 | 0.00 |
September | 3120.41 | 271.88 | 1395.19 | 589.68 | 805.51 | 0.00 | 0.00 |
October | 3863.86 | 1012.06 | 2239.52 | 1550.35 | 689.17 | 0.00 | 0.00 |
November | 4024.09 | 1538.11 | 2632.46 | 2021.85 | 610.62 | 0.00 | 0.00 |
December | 4200.09 | 2040.97 | 2846.99 | 2255.58 | 591.41 | 0.00 | 0.00 |
Annual Sum or Average | 3093.55 | 965.01 | 1711.02 | 1006.81 | 704.21 | 0.00 | 0.00 |
Minimum of Months | 2049.57 | 133.23 | 783.87 | 59.80 | 591.41 | 0.00 | 0.00 |
Maximum of Months | 4731.10 | 2040.97 | 3057.09 | 2442.27 | 815.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.71 | 228.99 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 259.62 | 222.21 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 319.97 | 196.71 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 527.53 | 90.83 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 530.06 | 54.20 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 647.77 | 14.12 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 543.80 | 8.81 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 531.83 | 9.96 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 489.16 | 17.53 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 450.48 | 122.47 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 395.53 | 202.26 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 350.47 | 282.59 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 457.81 | 120.49 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 259.62 | 8.81 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 647.77 | 282.59 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.18 | 241.90 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 136.70 | 229.94 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 223.97 | 201.93 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 447.02 | 91.95 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 506.57 | 51.24 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 656.48 | 12.96 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 540.46 | 8.35 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 489.73 | 10.57 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 405.59 | 18.73 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 287.63 | 130.01 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 205.28 | 214.36 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 148.90 | 296.95 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 355.86 | 125.34 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 136.70 | 8.35 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 656.48 | 296.95 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.42 | 91.50 | 132.16 | 105.58 | 26.58 | 0.00 | 0.00 |
February | 102.31 | 92.93 | 82.47 | 55.29 | 27.18 | 0.00 | 0.00 |
March | 89.08 | 83.30 | 68.27 | 34.59 | 33.67 | 0.00 | 0.00 |
April | 105.33 | 47.13 | 59.92 | 24.68 | 35.24 | 0.00 | 0.00 |
May | 77.09 | 33.04 | 40.04 | 6.96 | 33.07 | 0.00 | 0.00 |
June | 90.10 | 13.88 | 33.89 | 2.59 | 31.30 | 0.00 | 0.00 |
July | 86.68 | 11.02 | 34.34 | 3.26 | 31.07 | 0.00 | 0.00 |
August | 101.73 | 14.80 | 42.46 | 11.96 | 30.50 | 0.00 | 0.00 |
September | 121.75 | 20.31 | 60.32 | 25.49 | 34.82 | 0.00 | 0.00 |
October | 153.40 | 57.36 | 96.82 | 67.02 | 29.79 | 0.00 | 0.00 |
November | 160.52 | 84.20 | 113.80 | 87.41 | 26.40 | 0.00 | 0.00 |
December | 168.68 | 107.66 | 123.08 | 97.51 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 120.75 | 54.59 | 73.97 | 43.53 | 30.44 | 0.00 | 0.00 |
Minimum of Months | 77.09 | 11.02 | 33.89 | 2.59 | 25.57 | 0.00 | 0.00 |
Maximum of Months | 190.42 | 107.66 | 132.16 | 105.58 | 35.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.13 | 67.50 | 16.03 | 0.00 | 16.03 | 0.00 | 0.00 |
February | 10.53 | 67.08 | 18.27 | 0.00 | 18.27 | 0.00 | 0.00 |
March | 27.16 | 57.68 | 24.29 | 0.00 | 24.28 | 0.00 | 0.00 |
April | 62.16 | 23.13 | 29.74 | 0.44 | 29.30 | 0.00 | 0.00 |
May | 85.68 | 12.06 | 34.89 | 2.96 | 31.92 | 0.00 | 0.00 |
June | 133.64 | 2.58 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
July | 120.34 | 1.78 | 34.47 | 3.70 | 30.76 | 0.00 | 0.00 |
August | 99.76 | 2.23 | 27.73 | 0.68 | 27.05 | 0.00 | 0.00 |
September | 82.55 | 4.14 | 26.15 | 0.02 | 26.14 | 0.00 | 0.00 |
October | 39.46 | 35.32 | 20.22 | 0.00 | 20.22 | 0.00 | 0.00 |
November | 16.56 | 59.89 | 16.85 | 0.00 | 16.85 | 0.00 | 0.00 |
December | 9.48 | 85.17 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Annual Sum or Average | 58.85 | 34.75 | 25.35 | 1.27 | 24.08 | 0.00 | 0.00 |
Minimum of Months | 9.48 | 1.78 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Maximum of Months | 133.64 | 85.17 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.03 | 220.13 | 286.18 | 207.91 | 78.27 | 0.00 | 0.00 |
February | 280.13 | 216.01 | 223.33 | 138.29 | 85.04 | 0.00 | 0.00 |
March | 327.74 | 185.33 | 234.64 | 120.06 | 114.59 | 0.00 | 0.00 |
April | 526.95 | 80.90 | 287.65 | 157.61 | 130.04 | 0.00 | 0.00 |
May | 545.13 | 47.22 | 270.90 | 139.75 | 131.15 | 0.00 | 0.00 |
June | 664.87 | 12.14 | 272.15 | 145.99 | 126.16 | 0.00 | 0.00 |
July | 601.81 | 7.79 | 237.29 | 113.75 | 123.55 | 0.00 | 0.00 |
August | 583.05 | 9.49 | 237.72 | 120.44 | 117.28 | 0.00 | 0.00 |
September | 516.39 | 16.42 | 226.70 | 104.84 | 121.86 | 0.00 | 0.00 |
October | 467.65 | 117.02 | 272.87 | 176.15 | 96.72 | 0.00 | 0.00 |
November | 370.61 | 195.04 | 259.12 | 179.39 | 79.73 | 0.00 | 0.00 |
December | 348.54 | 273.77 | 260.60 | 186.46 | 74.14 | 0.00 | 0.00 |
Annual Sum or Average | 471.69 | 114.70 | 255.97 | 149.33 | 106.63 | 0.00 | 0.00 |
Minimum of Months | 280.13 | 7.79 | 223.33 | 104.84 | 74.14 | 0.00 | 0.00 |
Maximum of Months | 664.87 | 273.77 | 287.65 | 207.91 | 131.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.62 | 217.38 | 140.98 | 75.91 | 65.07 | 0.00 | 0.00 |
February | 148.44 | 214.29 | 143.06 | 69.17 | 73.89 | 0.00 | 0.00 |
March | 228.93 | 187.01 | 179.64 | 76.81 | 102.83 | 0.00 | 0.00 |
April | 443.39 | 82.38 | 249.91 | 127.30 | 122.61 | 0.00 | 0.00 |
May | 519.19 | 47.45 | 264.45 | 134.75 | 129.71 | 0.00 | 0.00 |
June | 672.14 | 12.28 | 280.14 | 151.96 | 128.18 | 0.00 | 0.00 |
July | 597.92 | 7.83 | 237.44 | 114.30 | 123.14 | 0.00 | 0.00 |
August | 539.78 | 10.28 | 219.29 | 106.33 | 112.95 | 0.00 | 0.00 |
September | 430.35 | 17.30 | 183.98 | 72.99 | 110.99 | 0.00 | 0.00 |
October | 297.55 | 119.08 | 177.10 | 92.35 | 84.75 | 0.00 | 0.00 |
November | 169.08 | 194.54 | 137.89 | 70.11 | 67.78 | 0.00 | 0.00 |
December | 130.11 | 269.54 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Annual Sum or Average | 363.74 | 114.55 | 195.17 | 96.50 | 98.67 | 0.00 | 0.00 |
Minimum of Months | 130.11 | 7.83 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Maximum of Months | 672.14 | 269.54 | 280.14 | 151.96 | 129.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 470.58 | 293.30 | 321.09 | 228.77 | 92.33 | 0.00 | 0.00 |
February | 266.63 | 284.15 | 218.26 | 119.79 | 98.47 | 0.00 | 0.00 |
March | 284.75 | 258.24 | 200.53 | 74.96 | 125.57 | 0.00 | 0.00 |
April | 388.93 | 130.52 | 194.25 | 54.43 | 139.83 | 0.00 | 0.00 |
May | 371.37 | 81.16 | 162.32 | 21.51 | 140.82 | 0.00 | 0.00 |
June | 498.61 | 25.95 | 160.71 | 21.55 | 139.16 | 0.00 | 0.00 |
July | 461.79 | 17.69 | 149.07 | 15.10 | 133.97 | 0.00 | 0.00 |
August | 449.21 | 23.91 | 152.08 | 27.39 | 124.70 | 0.00 | 0.00 |
September | 458.05 | 39.86 | 187.34 | 55.27 | 132.07 | 0.00 | 0.00 |
October | 438.44 | 174.23 | 253.58 | 145.22 | 108.36 | 0.00 | 0.00 |
November | 405.33 | 263.93 | 283.08 | 189.39 | 93.69 | 0.00 | 0.00 |
December | 405.62 | 354.13 | 299.12 | 211.28 | 87.84 | 0.00 | 0.00 |
Annual Sum or Average | 409.12 | 161.77 | 215.19 | 97.05 | 118.14 | 0.00 | 0.00 |
Minimum of Months | 266.63 | 17.69 | 149.07 | 15.10 | 87.84 | 0.00 | 0.00 |
Maximum of Months | 498.61 | 354.13 | 321.09 | 228.77 | 140.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 433.07 | 226.22 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 257.19 | 219.30 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 316.61 | 194.79 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 522.78 | 88.18 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 527.34 | 51.68 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 644.59 | 12.99 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 542.60 | 8.29 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 530.40 | 9.17 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 487.56 | 16.05 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 447.94 | 119.18 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 392.74 | 199.44 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 349.12 | 279.61 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 455.32 | 118.35 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 257.19 | 8.29 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 644.59 | 279.61 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.04 | 237.04 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 135.66 | 225.76 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 221.81 | 199.94 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 443.49 | 89.44 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 504.58 | 48.79 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 653.11 | 12.01 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 539.21 | 7.87 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 488.80 | 9.78 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 405.17 | 17.09 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 287.27 | 125.71 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 204.88 | 209.83 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 149.35 | 291.75 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 354.61 | 122.52 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 135.66 | 7.87 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 653.11 | 291.75 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 371.97 | 116.96 | 242.33 | 193.60 | 48.74 | 0.00 | 0.00 |
February | 206.62 | 114.69 | 151.21 | 101.37 | 49.84 | 0.00 | 0.00 |
March | 187.71 | 101.40 | 125.18 | 63.43 | 61.75 | 0.00 | 0.00 |
April | 225.34 | 43.84 | 109.86 | 45.26 | 64.61 | 0.00 | 0.00 |
May | 181.73 | 24.86 | 73.41 | 12.77 | 60.64 | 0.00 | 0.00 |
June | 221.19 | 5.44 | 62.14 | 4.74 | 57.40 | 0.00 | 0.00 |
July | 218.00 | 3.75 | 62.97 | 5.99 | 56.98 | 0.00 | 0.00 |
August | 237.86 | 4.21 | 77.86 | 21.93 | 55.93 | 0.00 | 0.00 |
September | 267.26 | 7.61 | 110.60 | 46.74 | 63.85 | 0.00 | 0.00 |
October | 310.41 | 60.59 | 177.53 | 122.90 | 54.63 | 0.00 | 0.00 |
November | 317.16 | 102.85 | 208.67 | 160.27 | 48.40 | 0.00 | 0.00 |
December | 330.60 | 145.58 | 225.68 | 178.80 | 46.88 | 0.00 | 0.00 |
Annual Sum or Average | 256.71 | 60.77 | 135.63 | 79.81 | 55.82 | 0.00 | 0.00 |
Minimum of Months | 181.73 | 3.75 | 62.14 | 4.74 | 46.88 | 0.00 | 0.00 |
Maximum of Months | 371.97 | 145.58 | 242.33 | 193.60 | 64.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 86.88 | 752.10 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 50.74 | 768.67 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 170.85 | 649.27 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 448.78 | 302.29 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 634.94 | 182.09 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1017.69 | 61.31 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 881.22 | 45.29 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 719.39 | 63.29 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 592.64 | 102.13 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 266.01 | 426.56 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 92.23 | 683.59 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 43.85 | 924.00 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 418.79 | 411.84 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 43.85 | 45.29 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1017.69 | 924.00 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 78.34 | 772.11 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 43.80 | 794.68 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 159.69 | 667.85 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 439.15 | 310.88 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 624.77 | 187.75 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1006.13 | 64.05 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 869.56 | 47.94 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 708.75 | 67.17 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 583.02 | 107.48 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 257.35 | 438.94 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 84.24 | 703.19 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 37.75 | 950.17 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 409.38 | 424.41 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 37.75 | 47.94 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1006.13 | 950.17 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 580.51 | 551.43 | 427.15 | 283.81 | 143.33 | 0.00 | 0.00 |
February | 410.10 | 569.34 | 366.37 | 207.46 | 158.92 | 0.00 | 0.00 |
March | 541.90 | 493.48 | 414.26 | 196.85 | 217.41 | 0.00 | 0.00 |
April | 984.30 | 249.69 | 537.54 | 284.90 | 252.64 | 0.00 | 0.00 |
May | 1079.62 | 172.11 | 535.32 | 274.48 | 260.84 | 0.00 | 0.00 |
June | 1343.60 | 70.30 | 552.26 | 297.92 | 254.33 | 0.00 | 0.00 |
July | 1177.25 | 54.69 | 474.70 | 228.03 | 246.68 | 0.00 | 0.00 |
August | 1116.34 | 72.64 | 456.98 | 226.75 | 230.22 | 0.00 | 0.00 |
September | 945.77 | 102.31 | 410.66 | 177.82 | 232.84 | 0.00 | 0.00 |
October | 768.15 | 330.75 | 449.95 | 268.49 | 181.46 | 0.00 | 0.00 |
November | 528.00 | 504.75 | 396.99 | 249.50 | 147.50 | 0.00 | 0.00 |
December | 462.67 | 658.08 | 386.03 | 250.99 | 135.03 | 0.00 | 0.00 |
Annual Sum or Average | 830.28 | 318.03 | 451.12 | 245.82 | 205.30 | 0.00 | 0.00 |
Minimum of Months | 410.10 | 54.69 | 366.37 | 177.82 | 135.03 | 0.00 | 0.00 |
Maximum of Months | 1343.60 | 658.08 | 552.26 | 297.92 | 260.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 979.05 | 520.72 | 664.96 | 492.81 | 172.15 | 0.00 | 0.00 |
February | 546.64 | 510.35 | 439.71 | 258.05 | 181.66 | 0.00 | 0.00 |
March | 549.75 | 465.17 | 391.48 | 161.47 | 230.01 | 0.00 | 0.00 |
April | 711.93 | 241.74 | 368.86 | 116.51 | 252.35 | 0.00 | 0.00 |
May | 643.15 | 152.99 | 291.49 | 41.39 | 250.10 | 0.00 | 0.00 |
June | 849.67 | 49.50 | 279.00 | 34.15 | 244.86 | 0.00 | 0.00 |
July | 789.34 | 35.14 | 263.64 | 26.35 | 237.30 | 0.00 | 0.00 |
August | 795.15 | 48.06 | 281.37 | 57.86 | 223.51 | 0.00 | 0.00 |
September | 840.26 | 77.56 | 359.96 | 119.04 | 240.92 | 0.00 | 0.00 |
October | 870.44 | 307.83 | 512.54 | 312.84 | 199.71 | 0.00 | 0.00 |
November | 838.08 | 467.99 | 581.72 | 407.98 | 173.74 | 0.00 | 0.00 |
December | 854.45 | 628.46 | 619.39 | 455.14 | 164.25 | 0.00 | 0.00 |
Annual Sum or Average | 773.77 | 291.24 | 421.29 | 206.96 | 214.33 | 0.00 | 0.00 |
Minimum of Months | 546.64 | 35.14 | 263.64 | 26.35 | 164.25 | 0.00 | 0.00 |
Maximum of Months | 979.05 | 628.46 | 664.96 | 492.81 | 252.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343079E+10 | 0.113458E+10 | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.00 | 0.00 |
February | 0.174631E+10 | 0.954712E+09 | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.00 | 0.00 |
March | 0.174864E+10 | 0.960113E+09 | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.00 | 0.00 |
April | 0.189201E+10 | 0.532146E+09 | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.00 | 0.00 |
May | 0.146395E+10 | 0.370920E+09 | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.00 | 0.00 |
June | 0.161570E+10 | 0.135817E+09 | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.00 | 0.00 |
July | 0.164302E+10 | 93236497.02 | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.00 | 0.00 |
August | 0.188241E+10 | 0.124841E+09 | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.00 | 0.00 |
September | 0.215880E+10 | 0.184950E+09 | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.00 | 0.00 |
October | 0.279118E+10 | 0.680652E+09 | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.00 | 0.00 |
November | 0.283032E+10 | 0.979825E+09 | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.00 | 0.00 |
December | 0.305562E+10 | 0.134459E+10 | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262588E+11 | 0.749639E+10 | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.00 | 0.00 |
Minimum of Months | 0.146395E+10 | 93236497.02 | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.343079E+10 | 0.134459E+10 | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952699E+10 | 0.348919E+10 | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.00 | 0.00 |
February | 0.479000E+10 | 0.304883E+10 | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.00 | 0.00 |
March | 0.477229E+10 | 0.303994E+10 | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.00 | 0.00 |
April | 0.525752E+10 | 0.160653E+10 | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.00 | 0.00 |
May | 0.407238E+10 | 0.111121E+10 | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.00 | 0.00 |
June | 0.454226E+10 | 0.391364E+09 | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.00 | 0.00 |
July | 0.460277E+10 | 0.282645E+09 | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.00 | 0.00 |
August | 0.526805E+10 | 0.383729E+09 | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.00 | 0.00 |
September | 0.603083E+10 | 0.562514E+09 | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.00 | 0.00 |
October | 0.776047E+10 | 0.208326E+10 | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.00 | 0.00 |
November | 0.784432E+10 | 0.304090E+10 | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.00 | 0.00 |
December | 0.845907E+10 | 0.414776E+10 | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.729270E+11 | 0.231879E+11 | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407238E+10 | 0.282645E+09 | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.00 | 0.00 |
Maximum of Months | 0.952699E+10 | 0.414776E+10 | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126718E+11 | 0.455021E+10 | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.00 | 0.00 |
February | 0.638887E+10 | 0.407622E+10 | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.00 | 0.00 |
March | 0.636872E+10 | 0.404974E+10 | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.00 | 0.00 |
April | 0.706277E+10 | 0.209571E+10 | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.00 | 0.00 |
May | 0.548958E+10 | 0.145312E+10 | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.00 | 0.00 |
June | 0.613904E+10 | 0.502734E+09 | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.00 | 0.00 |
July | 0.622404E+10 | 0.356832E+09 | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.00 | 0.00 |
August | 0.709635E+10 | 0.479299E+09 | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.00 | 0.00 |
September | 0.808809E+10 | 0.704707E+09 | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.00 | 0.00 |
October | 0.103490E+11 | 0.271069E+10 | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.00 | 0.00 |
November | 0.104305E+11 | 0.398677E+10 | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.00 | 0.00 |
December | 0.112495E+11 | 0.546653E+10 | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.975582E+11 | 0.304326E+11 | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.548958E+10 | 0.356832E+09 | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126718E+11 | 0.546653E+10 | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116701E+10 | 0.613324E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.628071E+09 | 0.537565E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.857001E+09 | 0.526865E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.136735E+10 | 0.235439E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.141972E+10 | 0.145171E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.167901E+10 | 36604985.56 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.145651E+10 | 23608905.70 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.142446E+10 | 26663958.50 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.126790E+10 | 45432619.06 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120658E+10 | 0.328033E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.102521E+10 | 0.524258E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.938703E+09 | 0.756879E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144375E+11 | 0.379984E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.628071E+09 | 23608905.70 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167901E+10 | 0.756879E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562937E+09 | 0.647893E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.330706E+09 | 0.556273E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.599894E+09 | 0.540859E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.115868E+10 | 0.238346E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135679E+10 | 0.137247E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.170160E+10 | 33601713.79 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.144756E+10 | 22359191.81 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.131169E+10 | 28312461.04 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.105129E+10 | 48557556.37 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.770401E+09 | 0.348227E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.532097E+09 | 0.555621E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.398804E+09 | 0.795354E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112225E+11 | 0.395265E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.330706E+09 | 22359191.81 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170160E+10 | 0.795354E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.510015E+09 | 0.245076E+09 | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.00 | 0.00 |
February | 0.247519E+09 | 0.224808E+09 | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.00 | 0.00 |
March | 0.238586E+09 | 0.223122E+09 | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.00 | 0.00 |
April | 0.273022E+09 | 0.122151E+09 | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.00 | 0.00 |
May | 0.206469E+09 | 88484835.82 | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.00 | 0.00 |
June | 0.233538E+09 | 35988796.44 | 87837819.98 | 6701448.63 | 81136371.35 | 0.00 | 0.00 |
July | 0.232176E+09 | 29510513.14 | 91975290.32 | 8744924.55 | 83230365.76 | 0.00 | 0.00 |
August | 0.272462E+09 | 39643469.11 | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.00 | 0.00 |
September | 0.315584E+09 | 52640471.50 | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.00 | 0.00 |
October | 0.410877E+09 | 0.153620E+09 | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.00 | 0.00 |
November | 0.416065E+09 | 0.218235E+09 | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.00 | 0.00 |
December | 0.451788E+09 | 0.288355E+09 | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.380810E+10 | 0.172164E+10 | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.00 | 0.00 |
Minimum of Months | 0.206469E+09 | 29510513.14 | 87837819.98 | 6701448.63 | 65755807.07 | 0.00 | 0.00 |
Maximum of Months | 0.510015E+09 | 0.288355E+09 | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43192655.83 | 0.180793E+09 | 42944949.46 | 0.00 | 42944949.46 | 0.00 | 0.00 |
February | 25467981.31 | 0.162281E+09 | 44199004.85 | 0.00 | 44199004.85 | 0.00 | 0.00 |
March | 72752022.14 | 0.154487E+09 | 65045237.58 | 2573.27 | 65042664.31 | 0.00 | 0.00 |
April | 0.161110E+09 | 59959368.02 | 77090857.89 | 1135053.46 | 75955804.43 | 0.00 | 0.00 |
May | 0.229487E+09 | 32294418.21 | 93441433.49 | 7934259.35 | 85507174.14 | 0.00 | 0.00 |
June | 0.346401E+09 | 6681597.56 | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.00 | 0.00 |
July | 0.322325E+09 | 4756200.65 | 92312481.83 | 9919050.97 | 82393430.86 | 0.00 | 0.00 |
August | 0.267200E+09 | 5964374.05 | 74279179.59 | 1823766.12 | 72455413.47 | 0.00 | 0.00 |
September | 0.213965E+09 | 10735103.68 | 67785290.05 | 41951.47 | 67743338.59 | 0.00 | 0.00 |
October | 0.105697E+09 | 94588139.47 | 54159300.98 | 0.00 | 54159300.98 | 0.00 | 0.00 |
November | 42927135.72 | 0.155234E+09 | 43668987.75 | 0.00 | 43668987.75 | 0.00 | 0.00 |
December | 25390333.90 | 0.228125E+09 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.185591E+10 | 0.109590E+10 | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.00 | 0.00 |
Minimum of Months | 25390333.90 | 4756200.65 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Maximum of Months | 0.346401E+09 | 0.228125E+09 | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111162E+10 | 0.589608E+09 | 0.766505E+09 | 0.556878E+09 | 0.209627E+09 | 0.00 | 0.00 |
February | 0.677685E+09 | 0.522569E+09 | 0.540277E+09 | 0.334558E+09 | 0.205719E+09 | 0.00 | 0.00 |
March | 0.877823E+09 | 0.496389E+09 | 0.628463E+09 | 0.321558E+09 | 0.306905E+09 | 0.00 | 0.00 |
April | 0.136586E+10 | 0.209700E+09 | 0.745596E+09 | 0.408534E+09 | 0.337062E+09 | 0.00 | 0.00 |
May | 0.146008E+10 | 0.126466E+09 | 0.725583E+09 | 0.374306E+09 | 0.351277E+09 | 0.00 | 0.00 |
June | 0.172334E+10 | 31478610.70 | 0.705417E+09 | 0.378400E+09 | 0.327016E+09 | 0.00 | 0.00 |
July | 0.161190E+10 | 20871633.45 | 0.635569E+09 | 0.304666E+09 | 0.330904E+09 | 0.00 | 0.00 |
August | 0.156164E+10 | 25411887.21 | 0.636696E+09 | 0.322574E+09 | 0.314123E+09 | 0.00 | 0.00 |
September | 0.133849E+10 | 42571531.95 | 0.587611E+09 | 0.271747E+09 | 0.315864E+09 | 0.00 | 0.00 |
October | 0.125256E+10 | 0.313414E+09 | 0.730860E+09 | 0.471799E+09 | 0.259061E+09 | 0.00 | 0.00 |
November | 0.960624E+09 | 0.505533E+09 | 0.671635E+09 | 0.464986E+09 | 0.206650E+09 | 0.00 | 0.00 |
December | 0.933517E+09 | 0.733274E+09 | 0.697993E+09 | 0.499406E+09 | 0.198587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148751E+11 | 0.361729E+10 | 0.807221E+10 | 0.470941E+10 | 0.336279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.677685E+09 | 20871633.45 | 0.540277E+09 | 0.271747E+09 | 0.198587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172334E+10 | 0.733274E+09 | 0.766505E+09 | 0.556878E+09 | 0.351277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470383E+09 | 0.582239E+09 | 0.377613E+09 | 0.203319E+09 | 0.174294E+09 | 0.00 | 0.00 |
February | 0.359103E+09 | 0.518404E+09 | 0.346092E+09 | 0.167343E+09 | 0.178749E+09 | 0.00 | 0.00 |
March | 0.613161E+09 | 0.500875E+09 | 0.481151E+09 | 0.205720E+09 | 0.275431E+09 | 0.00 | 0.00 |
April | 0.114926E+10 | 0.213531E+09 | 0.647778E+09 | 0.329970E+09 | 0.317808E+09 | 0.00 | 0.00 |
May | 0.139059E+10 | 0.127081E+09 | 0.708304E+09 | 0.360901E+09 | 0.347403E+09 | 0.00 | 0.00 |
June | 0.174218E+10 | 31818933.63 | 0.726118E+09 | 0.393870E+09 | 0.332248E+09 | 0.00 | 0.00 |
July | 0.160147E+10 | 20977541.94 | 0.635953E+09 | 0.306130E+09 | 0.329823E+09 | 0.00 | 0.00 |
August | 0.144575E+10 | 27535191.61 | 0.587340E+09 | 0.284806E+09 | 0.302534E+09 | 0.00 | 0.00 |
September | 0.111546E+10 | 44839191.90 | 0.476868E+09 | 0.189187E+09 | 0.287681E+09 | 0.00 | 0.00 |
October | 0.796966E+09 | 0.318947E+09 | 0.474341E+09 | 0.247359E+09 | 0.226982E+09 | 0.00 | 0.00 |
November | 0.438260E+09 | 0.504242E+09 | 0.357413E+09 | 0.181731E+09 | 0.175682E+09 | 0.00 | 0.00 |
December | 0.348476E+09 | 0.721945E+09 | 0.335979E+09 | 0.172873E+09 | 0.163106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114711E+11 | 0.361244E+10 | 0.615495E+10 | 0.304321E+10 | 0.311174E+10 | 0.00 | 0.00 |
Minimum of Months | 0.348476E+09 | 20977541.94 | 0.335979E+09 | 0.167343E+09 | 0.163106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174218E+10 | 0.721945E+09 | 0.726118E+09 | 0.393870E+09 | 0.347403E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126041E+10 | 0.785577E+09 | 0.860015E+09 | 0.612730E+09 | 0.247286E+09 | 0.00 | 0.00 |
February | 0.645024E+09 | 0.687411E+09 | 0.528015E+09 | 0.289790E+09 | 0.238224E+09 | 0.00 | 0.00 |
March | 0.762672E+09 | 0.691680E+09 | 0.537094E+09 | 0.200762E+09 | 0.336332E+09 | 0.00 | 0.00 |
April | 0.100811E+10 | 0.338297E+09 | 0.503505E+09 | 0.141072E+09 | 0.362433E+09 | 0.00 | 0.00 |
May | 0.994678E+09 | 0.217377E+09 | 0.434765E+09 | 57604611.69 | 0.377160E+09 | 0.00 | 0.00 |
June | 0.129240E+10 | 67266476.13 | 0.416551E+09 | 55856451.63 | 0.360695E+09 | 0.00 | 0.00 |
July | 0.123685E+10 | 47388530.82 | 0.399265E+09 | 40435810.09 | 0.358829E+09 | 0.00 | 0.00 |
August | 0.120315E+10 | 64052189.08 | 0.407338E+09 | 73352738.99 | 0.333986E+09 | 0.00 | 0.00 |
September | 0.118728E+10 | 0.103328E+09 | 0.485590E+09 | 0.143261E+09 | 0.342329E+09 | 0.00 | 0.00 |
October | 0.117431E+10 | 0.466658E+09 | 0.679193E+09 | 0.388962E+09 | 0.290232E+09 | 0.00 | 0.00 |
November | 0.105061E+10 | 0.684117E+09 | 0.733746E+09 | 0.490890E+09 | 0.242857E+09 | 0.00 | 0.00 |
December | 0.108642E+10 | 0.948505E+09 | 0.801172E+09 | 0.565893E+09 | 0.235279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129019E+11 | 0.510166E+10 | 0.678625E+10 | 0.306061E+10 | 0.372564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.645024E+09 | 47388530.82 | 0.399265E+09 | 40435810.09 | 0.235279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129240E+10 | 0.948505E+09 | 0.860015E+09 | 0.612730E+09 | 0.377160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115992E+10 | 0.605912E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.622205E+09 | 0.530535E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.848011E+09 | 0.521731E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.135506E+10 | 0.228557E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.141243E+10 | 0.138417E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.167077E+10 | 33666163.83 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.145330E+10 | 22204002.49 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.142062E+10 | 24555602.22 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.126376E+10 | 41595399.39 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.119976E+10 | 0.319218E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.101799E+10 | 0.516954E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.935084E+09 | 0.748921E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143589E+11 | 0.373227E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.622205E+09 | 22204002.49 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167077E+10 | 0.748921E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562566E+09 | 0.634895E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.328196E+09 | 0.546161E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.594088E+09 | 0.535517E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.114953E+10 | 0.231817E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135146E+10 | 0.130672E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.169287E+10 | 31142535.70 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.144422E+10 | 21088739.28 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.130921E+10 | 26193398.05 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.105019E+10 | 44285565.13 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.769425E+09 | 0.336694E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.531054E+09 | 0.543869E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.400020E+09 | 0.781425E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111828E+11 | 0.386376E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.328196E+09 | 21088739.28 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169287E+10 | 0.781425E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996279E+09 | 0.313268E+09 | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.00 | 0.00 |
February | 0.499852E+09 | 0.277456E+09 | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.00 | 0.00 |
March | 0.502765E+09 | 0.271585E+09 | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.00 | 0.00 |
April | 0.584079E+09 | 0.113621E+09 | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.00 | 0.00 |
May | 0.486744E+09 | 66571840.25 | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.00 | 0.00 |
June | 0.573331E+09 | 14096427.17 | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.00 | 0.00 |
July | 0.583892E+09 | 10031114.92 | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.00 | 0.00 |
August | 0.637076E+09 | 11279940.79 | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.00 | 0.00 |
September | 0.692749E+09 | 19722528.65 | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.00 | 0.00 |
October | 0.831390E+09 | 0.162283E+09 | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.00 | 0.00 |
November | 0.822067E+09 | 0.266599E+09 | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.00 | 0.00 |
December | 0.885488E+09 | 0.389916E+09 | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.809571E+10 | 0.191643E+10 | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.00 | 0.00 |
Minimum of Months | 0.486744E+09 | 10031114.92 | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.00 | 0.00 |
Maximum of Months | 0.996279E+09 | 0.389916E+09 | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232706E+09 | 0.201443E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.122760E+09 | 0.185956E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.457601E+09 | 0.173900E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.116323E+10 | 0.783548E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.170061E+10 | 0.487707E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.263785E+10 | 0.158904E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.236026E+10 | 0.121295E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.192683E+10 | 0.169515E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.153611E+10 | 0.264718E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.712475E+09 | 0.114249E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.239053E+09 | 0.177187E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.117455E+09 | 0.247485E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132070E+11 | 0.129879E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117455E+09 | 0.121295E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263785E+10 | 0.247485E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.209821E+09 | 0.206803E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.105955E+09 | 0.192249E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.427716E+09 | 0.178876E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.113829E+10 | 0.805800E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.167339E+10 | 0.502867E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.260789E+10 | 0.166014E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.232904E+10 | 0.128399E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.189831E+10 | 0.179907E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.151120E+10 | 0.278591E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.689294E+09 | 0.117565E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.218359E+09 | 0.182268E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.101110E+09 | 0.254494E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129104E+11 | 0.133841E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.101110E+09 | 0.128399E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.260789E+10 | 0.254494E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155483E+10 | 0.147695E+10 | 0.114407E+10 | 0.760168E+09 | 0.383905E+09 | 0.00 | 0.00 |
February | 0.992112E+09 | 0.137734E+10 | 0.886328E+09 | 0.501877E+09 | 0.384451E+09 | 0.00 | 0.00 |
March | 0.145144E+10 | 0.132175E+10 | 0.110956E+10 | 0.527249E+09 | 0.582308E+09 | 0.00 | 0.00 |
April | 0.255131E+10 | 0.647189E+09 | 0.139330E+10 | 0.738458E+09 | 0.654838E+09 | 0.00 | 0.00 |
May | 0.289166E+10 | 0.460988E+09 | 0.143380E+10 | 0.735158E+09 | 0.698645E+09 | 0.00 | 0.00 |
June | 0.348262E+10 | 0.182206E+09 | 0.143145E+10 | 0.772218E+09 | 0.659232E+09 | 0.00 | 0.00 |
July | 0.315313E+10 | 0.146484E+09 | 0.127145E+10 | 0.610754E+09 | 0.660695E+09 | 0.00 | 0.00 |
August | 0.299001E+10 | 0.194547E+09 | 0.122397E+10 | 0.607340E+09 | 0.616627E+09 | 0.00 | 0.00 |
September | 0.245143E+10 | 0.265187E+09 | 0.106442E+10 | 0.460908E+09 | 0.603516E+09 | 0.00 | 0.00 |
October | 0.205742E+10 | 0.885893E+09 | 0.120514E+10 | 0.719123E+09 | 0.486021E+09 | 0.00 | 0.00 |
November | 0.136857E+10 | 0.130831E+10 | 0.102901E+10 | 0.646691E+09 | 0.382315E+09 | 0.00 | 0.00 |
December | 0.123922E+10 | 0.176261E+10 | 0.103393E+10 | 0.672254E+09 | 0.361677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.261838E+11 | 0.100294E+11 | 0.142264E+11 | 0.775220E+10 | 0.647423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.992112E+09 | 0.146484E+09 | 0.886328E+09 | 0.460908E+09 | 0.361677E+09 | 0.00 | 0.00 |
Maximum of Months | 0.348262E+10 | 0.176261E+10 | 0.143380E+10 | 0.772218E+09 | 0.698645E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262230E+10 | 0.139470E+10 | 0.178102E+10 | 0.131994E+10 | 0.461083E+09 | 0.00 | 0.00 |
February | 0.132242E+10 | 0.123463E+10 | 0.106374E+10 | 0.624266E+09 | 0.439472E+09 | 0.00 | 0.00 |
March | 0.147246E+10 | 0.124591E+10 | 0.104853E+10 | 0.432478E+09 | 0.616053E+09 | 0.00 | 0.00 |
April | 0.184532E+10 | 0.626596E+09 | 0.956085E+09 | 0.302004E+09 | 0.654081E+09 | 0.00 | 0.00 |
May | 0.172262E+10 | 0.409773E+09 | 0.780737E+09 | 0.110860E+09 | 0.669877E+09 | 0.00 | 0.00 |
June | 0.220234E+10 | 0.128304E+09 | 0.723175E+09 | 88503980.79 | 0.634671E+09 | 0.00 | 0.00 |
July | 0.211416E+10 | 94115745.87 | 0.706145E+09 | 70564670.40 | 0.635580E+09 | 0.00 | 0.00 |
August | 0.212972E+10 | 0.128735E+09 | 0.753612E+09 | 0.154975E+09 | 0.598637E+09 | 0.00 | 0.00 |
September | 0.217794E+10 | 0.201047E+09 | 0.933011E+09 | 0.308543E+09 | 0.624468E+09 | 0.00 | 0.00 |
October | 0.233138E+10 | 0.824483E+09 | 0.137280E+10 | 0.837901E+09 | 0.534895E+09 | 0.00 | 0.00 |
November | 0.217231E+10 | 0.121304E+10 | 0.150781E+10 | 0.105747E+10 | 0.450334E+09 | 0.00 | 0.00 |
December | 0.228856E+10 | 0.168326E+10 | 0.165898E+10 | 0.121905E+10 | 0.439939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244015E+11 | 0.918460E+10 | 0.132856E+11 | 0.652656E+10 | 0.675909E+10 | 0.00 | 0.00 |
Minimum of Months | 0.132242E+10 | 94115745.87 | 0.706145E+09 | 70564670.40 | 0.439472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.262230E+10 | 0.168326E+10 | 0.178102E+10 | 0.131994E+10 | 0.669877E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770447E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161688431.2 | 81.21 | 0.00 | 0.00 |
February | 0.696199E+10 | -0.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146037131.0 | 81.21 | 0.00 | 0.00 |
March | 0.770309E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161636984.4 | 81.21 | 0.00 | 0.00 |
April | 0.746483E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156245730.2 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161422424.9 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203435.0 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408252.7 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408746.2 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156202511.4 | 81.21 | 0.00 | 0.00 |
October | 0.770294E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161508322.4 | 81.21 | 0.00 | 0.00 |
November | 0.744885E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156431821.4 | 81.21 | 0.00 | 0.00 |
December | 0.771267E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161816127.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907424E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190201E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696199E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161816127.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771267E+10 | -0.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146037131.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.107704E+12 | -0.105973E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173080E+10 | 81.25 | 0.00 | 0.00 |
February | 0.966629E+11 | -0.950842E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157871E+10 | 81.25 | 0.00 | 0.00 |
March | 0.103762E+12 | -0.101997E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176475E+10 | 81.25 | 0.00 | 0.00 |
April | 0.954274E+11 | -0.937295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169788E+10 | 81.24 | 0.00 | 0.00 |
May | 0.930326E+11 | -0.912690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176356E+10 | 81.25 | 0.00 | 0.00 |
June | 0.856450E+11 | -0.839465E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169847E+10 | 81.25 | 0.00 | 0.00 |
July | 0.862450E+11 | -0.845145E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173052E+10 | 81.23 | 0.00 | 0.00 |
August | 0.869199E+11 | -0.851923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172766E+10 | 81.24 | 0.00 | 0.00 |
September | 0.873917E+11 | -0.857220E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166971E+10 | 81.23 | 0.00 | 0.00 |
October | 0.954880E+11 | -0.937626E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172541E+10 | 81.24 | 0.00 | 0.00 |
November | 0.978036E+11 | -0.961337E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166986E+10 | 81.24 | 0.00 | 0.00 |
December | 0.105527E+12 | -0.103801E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172580E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.114161E+13 | -0.112113E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204831E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.856450E+11 | -0.105973E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176475E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.107704E+12 | -0.839465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157871E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.603931E+11 | -0.589242E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146887E+10 | 58.98 | 0.00 | 0.00 |
February | 0.540352E+11 | -0.526871E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134804E+10 | 58.98 | 0.00 | 0.00 |
March | 0.570618E+11 | -0.555461E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151564E+10 | 58.98 | 0.00 | 0.00 |
April | 0.508828E+11 | -0.494293E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145350E+10 | 58.98 | 0.00 | 0.00 |
May | 0.477783E+11 | -0.462642E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151419E+10 | 58.98 | 0.00 | 0.00 |
June | 0.424588E+11 | -0.410049E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145385E+10 | 58.97 | 0.00 | 0.00 |
July | 0.418740E+11 | -0.404051E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146882E+10 | 58.97 | 0.00 | 0.00 |
August | 0.424978E+11 | -0.410333E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146445E+10 | 58.97 | 0.00 | 0.00 |
September | 0.439340E+11 | -0.425195E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141451E+10 | 58.98 | 0.00 | 0.00 |
October | 0.498504E+11 | -0.483887E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146168E+10 | 58.98 | 0.00 | 0.00 |
November | 0.528977E+11 | -0.514832E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141456E+10 | 58.98 | 0.00 | 0.00 |
December | 0.585102E+11 | -0.570482E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146201E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.602174E+12 | -0.584734E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.174401E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.418740E+11 | -0.589242E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151564E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.603931E+11 | -0.404051E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134804E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.87 | 0.86 | 01-JAN-07:00 | 8303.49 | 39.08 | 307.00 | 292.67 | 1154.85 | 28.03 | 189.17 | 287.50 |
February | 241.00 | 0.87 | 0.86 | 01-FEB-07:49 | 4813.81 | 32.61 | 187.33 | 267.33 | 592.11 | 23.38 | 134.33 | 205.83 |
March | 344.33 | 0.88 | 0.86 | 01-MAR-07:00 | 1114.22 | 19.69 | 11.50 | 326.67 | 422.82 | 21.05 | 162.83 | 258.17 |
April | 380.33 | 0.88 | 0.86 | 01-APR-08:50 | 772.00 | 19.30 | 0.00 | 333.17 | 336.58 | 21.05 | 183.00 | 267.33 |
May | 403.17 | 0.88 | 0.86 | 01-MAY-08:09 | 622.65 | 19.09 | 0.00 | 359.67 | 275.63 | 20.87 | 100.83 | 235.67 |
June | 418.17 | 0.89 | 0.86 | 01-JUN-08:20 | 503.83 | 18.46 | 0.00 | 361.33 | 229.43 | 20.28 | 29.00 | 129.50 |
July | 399.50 | 0.88 | 0.86 | 01-JUL-09:30 | 620.48 | 18.53 | 0.00 | 362.67 | 264.72 | 20.32 | 90.00 | 195.83 |
August | 361.83 | 0.88 | 0.86 | 01-AUG-08:50 | 691.97 | 18.90 | 0.00 | 340.33 | 294.45 | 20.66 | 96.33 | 212.83 |
September | 350.17 | 0.88 | 0.86 | 01-SEP-07:30 | 1020.11 | 19.22 | 0.50 | 322.00 | 409.17 | 20.97 | 176.33 | 265.00 |
October | 348.00 | 0.87 | 0.86 | 01-OCT-07:49 | 2798.30 | 25.74 | 135.33 | 321.00 | 455.52 | 21.69 | 142.83 | 273.67 |
November | 288.50 | 0.87 | 0.86 | 01-NOV-08:09 | 7916.24 | 37.84 | 282.83 | 287.00 | 904.39 | 26.57 | 167.83 | 264.67 |
December | 290.67 | 0.87 | 0.86 | 01-DEC-07:40 | 7638.18 | 38.90 | 287.83 | 280.83 | 1321.43 | 28.77 | 185.33 | 273.33 |
Annual Sum or Average | 4135.50 | 0.88 | 2709.49 | 24.58 | 1212.33 | 3854.67 | 517.54 | 22.48 | 1657.83 | 2869.33 | ||
Minimum of Months | 241.00 | 0.87 | 0.86 | 503.83 | 18.46 | 0.00 | 267.33 | 229.43 | 20.28 | 29.00 | 129.50 | |
Maximum of Months | 418.17 | 0.89 | 0.86 | 8303.49 | 39.08 | 307.00 | 362.67 | 1321.43 | 28.77 | 189.17 | 287.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.26 | 0.22 | 01-JAN-07:49 | 8767.75 | 39.13 | 307.00 | 295.17 | 1616.31 | 27.50 | 165.00 | 292.67 |
February | 241.00 | 0.26 | 0.22 | 01-FEB-07:49 | 5159.06 | 32.56 | 187.67 | 273.17 | 936.90 | 23.24 | 132.00 | 249.00 |
March | 344.33 | 0.28 | 0.22 | 01-MAR-07:30 | 1351.04 | 20.13 | 23.50 | 338.67 | 660.27 | 21.32 | 186.83 | 306.83 |
April | 380.33 | 0.29 | 0.22 | 01-APR-07:30 | 967.61 | 19.83 | 22.67 | 345.00 | 531.77 | 21.38 | 219.33 | 321.00 |
May | 403.17 | 0.28 | 0.22 | 01-MAY-07:10 | 762.05 | 19.86 | 0.33 | 378.00 | 414.67 | 21.41 | 235.17 | 342.17 |
June | 418.17 | 0.29 | 0.22 | 01-JUN-06:00 | 619.25 | 19.33 | 0.00 | 383.33 | 344.55 | 20.92 | 140.67 | 345.33 |
July | 399.50 | 0.29 | 0.22 | 01-JUL-07:19 | 742.53 | 19.40 | 0.50 | 386.50 | 386.40 | 20.95 | 177.83 | 335.50 |
August | 361.83 | 0.28 | 0.22 | 01-AUG-07:40 | 846.46 | 19.63 | 2.17 | 355.67 | 448.53 | 21.17 | 172.83 | 315.17 |
September | 350.17 | 0.28 | 0.22 | 01-SEP-06:00 | 1229.75 | 19.79 | 24.33 | 332.33 | 618.23 | 21.34 | 206.67 | 305.17 |
October | 348.00 | 0.27 | 0.22 | 01-OCT-07:19 | 3119.56 | 25.77 | 140.17 | 326.50 | 775.82 | 21.62 | 140.33 | 308.67 |
November | 288.50 | 0.25 | 0.22 | 01-NOV-07:40 | 8331.06 | 37.91 | 283.33 | 292.50 | 1319.63 | 26.16 | 148.67 | 279.83 |
December | 290.67 | 0.24 | 0.22 | 01-DEC-07:30 | 8096.77 | 38.96 | 287.83 | 285.33 | 1778.08 | 28.28 | 168.33 | 278.00 |
Annual Sum or Average | 4135.50 | 0.27 | 2958.63 | 25.04 | 1279.50 | 3992.17 | 766.08 | 22.67 | 2093.67 | 3679.33 | ||
Minimum of Months | 241.00 | 0.24 | 0.22 | 619.25 | 19.33 | 0.00 | 273.17 | 344.55 | 20.92 | 132.00 | 249.00 | |
Maximum of Months | 418.17 | 0.29 | 0.22 | 8767.75 | 39.13 | 307.00 | 386.50 | 1778.08 | 28.28 | 235.17 | 345.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535988E+11 | 106009.01 | 02-JAN-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604527E+11 | 106519.73 | 28-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417482E+11 | 106015.53 | 31-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239753E+10 | 81406.11 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31732750.82 | 10975.06 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142060E+11 | 106424.95 | 13-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371007E+11 | 107010.26 | 23-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695784E+11 | 109103.46 | 16-DEC-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.695784E+11 | 109103.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 58554196.02 | 1008.28 | 02-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324666E+09 | 1031.16 | 08-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227777E+09 | 1166.54 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89524.94 | 81.94 | 21-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16419695.69 | 466.78 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50525785.44 | 921.68 | 24-NOV-04:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300947E+09 | 1242.77 | 16-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324666E+09 | 1242.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18939300.37 | 547.64 | 02-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 359619.63 | 225.41 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4072522.82 | 372.21 | 27-MAR-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42527490.97 | 409.59 | 07-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65898933.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42527490.97 | 547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16756424.67 | 355.71 | 02-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2406050.89 | 117.64 | 13-FEB-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7132821.92 | 242.26 | 27-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48894197.70 | 281.69 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75189495.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48894197.70 | 355.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5191035.46 | 4043.70 | 02-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 590703.16 | 1373.86 | 29-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 678375.35 | 3391.88 | 24-NOV-04:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2168982.93 | 3485.92 | 30-DEC-04:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8629096.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5191035.46 | 4043.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24023109.97 | 1462.21 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1307838.85 | 1502.96 | 27-MAR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25330948.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24023109.97 | 1502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19838578.94 | 2520.51 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71210456.90 | 2507.11 | 12-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63984761.08 | 2572.57 | 20-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71210456.90 | 2572.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101928E+09 | 2448.22 | 02-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140490E+09 | 1683.66 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101161E+09 | 1828.93 | 29-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14362065.38 | 1430.54 | 24-NOV-04:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506780E+09 | 2610.12 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.506780E+09 | 2610.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12839.38 | 0.34 | 13-JAN-16:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8073.07 | 0.32 | 10-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8919.95 | 0.34 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26065.56 | 0.34 | 08-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22631.98 | 0.34 | 08-MAY-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15745.57 | 0.34 | 09-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14201.11 | 0.34 | 08-JUL-01:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14529.94 | 0.34 | 04-AUG-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13531.26 | 0.34 | 02-SEP-20:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16391.25 | 0.34 | 23-OCT-18:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11811.15 | 0.34 | 14-NOV-00:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1157742.71 | 112.49 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1322482.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8073.07 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1157742.71 | 112.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267625E+09 | 3647.83 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.557681E+09 | 5063.13 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369472E+09 | 5062.35 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3185128.26 | 2840.31 | 11-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 217070.44 | 1199.50 | 01-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71967.38 | 437.74 | 29-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 316106.42 | 1457.56 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 381706.75 | 1230.14 | 03-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50014001.48 | 2791.48 | 12-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195674E+09 | 3281.82 | 30-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.893564E+09 | 5052.24 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.893564E+09 | 5063.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606259E+09 | 5133.54 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.894548E+09 | 5073.12 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.475989E+09 | 5087.59 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2164577.82 | 2484.85 | 08-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 831505.32 | 2319.58 | 03-MAY-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46918.91 | 781.98 | 13-JUN-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47754.24 | 320.74 | 27-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24863.93 | 132.24 | 23-AUG-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 363254.44 | 1421.51 | 22-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88947627.68 | 3985.65 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409581E+09 | 5089.03 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167373E+10 | 5212.11 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24863.93 | 132.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167373E+10 | 5212.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111453E+10 | 29023.41 | 03-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940413E+09 | 29031.67 | 03-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.613734E+09 | 29021.69 | 12-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104477E+09 | 29018.43 | 10-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44538380.26 | 29005.66 | 25-MAY-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5640905.60 | 12449.33 | 30-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30942783.80 | 22774.06 | 02-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39486251.52 | 21271.63 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54109540.83 | 26856.45 | 23-SEP-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158708E+09 | 29012.79 | 17-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688643E+09 | 29022.32 | 25-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392522E+10 | 29642.38 | 07-DEC-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5640905.60 | 12449.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392522E+10 | 29642.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313003E+09 | 2944.52 | 03-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.532622E+09 | 4942.85 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352737E+09 | 3176.65 | 08-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 533922.81 | 452.03 | 29-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56202.66 | 655.70 | 03-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47226433.79 | 2104.39 | 27-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236778E+09 | 3528.11 | 25-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.890959E+09 | 4000.64 | 06-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.890959E+09 | 4942.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.662908E+09 | 4929.49 | 01-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.791072E+09 | 4950.70 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447264E+09 | 2638.82 | 06-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 888421.54 | 710.53 | 27-APR-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80781660.61 | 3236.57 | 25-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460693E+09 | 3519.38 | 23-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157544E+10 | 4992.61 | 07-DEC-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157544E+10 | 4992.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174395E+09 | 1518.65 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276942E+09 | 1530.43 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188549E+09 | 1533.55 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3810431.29 | 609.18 | 06-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 303243.78 | 378.70 | 26-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19134.50 | 119.35 | 27-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83636.99 | 307.62 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 167673.13 | 350.34 | 22-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48076743.70 | 1502.65 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134459E+09 | 1427.32 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416153E+09 | 1536.89 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416153E+09 | 1536.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320645E+09 | 1557.48 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402200E+09 | 1535.84 | 03-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224357E+09 | 1539.61 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2000109.06 | 680.88 | 28-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 371395.32 | 676.37 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 813.10 | 12.20 | 20-JUN-06:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29177.36 | 205.75 | 27-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25534.33 | 196.54 | 06-AUG-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 204213.56 | 375.08 | 23-SEP-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70620022.69 | 1519.72 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227685E+09 | 1544.94 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.691811E+09 | 1558.16 | 18-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 813.10 | 12.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691811E+09 | 1558.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111901E+09 | 3644.59 | 01-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.379595E+09 | 6999.07 | 07-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374110E+09 | 7072.79 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11993208.53 | 6189.54 | 20-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9851355.12 | 6739.34 | 09-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2648942.34 | 6993.27 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7026925.46 | 6373.21 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7812453.53 | 4909.58 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7062784.10 | 5071.42 | 14-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39982916.87 | 5537.63 | 12-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121763E+09 | 5308.62 | 07-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518308E+09 | 5648.55 | 30-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2648942.34 | 3644.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.518308E+09 | 7072.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107053E+12 | 0.106620E+12 | 180871.39 | 31-JAN-16:03 | 180871.39 | 0.04 |
February | 0.00 | 0.00 | 0.259170E+11 | 0.258887E+11 | 104703.88 | 18-FEB-14:00 | 104703.88 | 0.13 |
March | 0.00 | 0.00 | 0.115953E+12 | 0.115953E+12 | 198650.90 | 16-MAR-18:07 | 198650.90 | 0.11 |
April | 0.00 | 0.00 | 0.319688E+12 | 0.319688E+12 | 261477.13 | 14-APR-18:10 | 261477.13 | 0.04 |
May | 0.00 | 0.00 | 0.416056E+12 | 0.416056E+12 | 273312.14 | 31-MAY-18:17 | 273312.14 | 0.01 |
June | 0.00 | 0.00 | 0.525161E+12 | 0.524272E+12 | 332777.62 | 17-JUN-17:17 | 272916.13 | 0.33 |
July | 0.00 | 0.00 | 0.610996E+12 | 0.534460E+12 | 412165.47 | 13-JUL-18:01 | 221438.36 | 0.81 |
August | 0.00 | 0.00 | 0.597337E+12 | 0.527586E+12 | 442736.90 | 18-AUG-22:00 | 207678.51 | 0.86 |
September | 0.00 | 0.00 | 0.550077E+12 | 0.475461E+12 | 470761.78 | 10-SEP-20:40 | 208277.96 | 0.87 |
October | 0.00 | 0.00 | 0.281643E+12 | 0.273739E+12 | 334711.16 | 02-OCT-20:00 | 252250.21 | 0.29 |
November | 0.00 | 0.00 | 0.122609E+12 | 0.108761E+12 | 202202.38 | 01-NOV-18:10 | 202202.38 | 0.24 |
December | 0.00 | 0.00 | 0.568426E+11 | 0.568426E+11 | 159791.22 | 22-DEC-16:03 | 159791.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372933E+13 | 0.348532E+13 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.259170E+11 | 0.258887E+11 | 104703.88 | 104703.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.610996E+12 | 0.534460E+12 | 470761.78 | 273312.14 | 0.87 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.673159E+10 | 0.667634E+10 | 16934.02 | 31-JAN-16:02 | 16934.02 | 0.02 |
February | 0.00 | 0.00 | 0.173081E+10 | 0.173081E+10 | 13679.85 | 18-FEB-14:00 | 13679.85 | 0.08 |
March | 0.00 | 0.00 | 0.789044E+10 | 0.789044E+10 | 17344.04 | 16-MAR-15:01 | 17344.04 | 0.09 |
April | 0.00 | 0.00 | 0.209561E+11 | 0.209561E+11 | 19388.91 | 14-APR-15:01 | 19388.91 | 0.04 |
May | 0.00 | 0.00 | 0.271661E+11 | 0.271661E+11 | 19755.34 | 31-MAY-15:01 | 19755.34 | 0.02 |
June | 0.00 | 0.00 | 0.323567E+11 | 0.323334E+11 | 22704.06 | 17-JUN-16:00 | 19551.03 | 0.15 |
July | 0.00 | 0.00 | 0.374524E+11 | 0.329774E+11 | 30440.72 | 27-JUL-06:50 | 15040.23 | 0.63 |
August | 0.00 | 0.00 | 0.371941E+11 | 0.326157E+11 | 35354.65 | 05-AUG-08:15 | 16213.38 | 0.69 |
September | 0.00 | 0.00 | 0.352438E+11 | 0.299154E+11 | 39084.40 | 04-SEP-08:13 | 15974.14 | 0.69 |
October | 0.00 | 0.00 | 0.180490E+11 | 0.174630E+11 | 28456.52 | 03-OCT-08:61 | 17371.72 | 0.23 |
November | 0.00 | 0.00 | 0.849529E+10 | 0.712001E+10 | 24520.20 | 12-NOV-13:20 | 13863.49 | 0.18 |
December | 0.00 | 0.00 | 0.357258E+10 | 0.357258E+10 | 15709.29 | 25-DEC-16:02 | 15709.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236839E+12 | 0.220417E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.173081E+10 | 0.173081E+10 | 13679.85 | 13679.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.374524E+11 | 0.329774E+11 | 39084.40 | 19755.34 | 0.69 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361783E+10 | 0.332192E+10 | 11452.63 | 08-JAN-19:02 | 8458.29 | 0.19 |
February | 0.00 | 0.00 | 0.124692E+10 | 0.914801E+09 | 10774.50 | 18-FEB-16:01 | 9908.08 | 0.28 |
March | 0.00 | 0.00 | 0.282584E+10 | 0.227235E+10 | 10944.90 | 06-MAR-16:02 | 8795.56 | 0.39 |
April | 0.00 | 0.00 | 0.865544E+10 | 0.839289E+10 | 10282.98 | 18-APR-15:01 | 10282.98 | 0.19 |
May | 0.00 | 0.00 | 0.102892E+11 | 0.101792E+11 | 10283.68 | 11-MAY-18:01 | 10283.68 | 0.08 |
June | 0.00 | 0.00 | 0.133462E+11 | 0.126321E+11 | 10373.11 | 03-JUN-16:45 | 10373.11 | 0.60 |
July | 0.00 | 0.00 | 0.128796E+11 | 0.105619E+11 | 11803.90 | 27-JUL-08:61 | 9349.24 | 0.83 |
August | 0.00 | 0.00 | 0.126399E+11 | 0.101484E+11 | 12251.57 | 05-AUG-08:61 | 9054.80 | 0.87 |
September | 0.00 | 0.00 | 0.111053E+11 | 0.859100E+10 | 12929.00 | 04-SEP-08:61 | 8603.82 | 0.96 |
October | 0.00 | 0.00 | 0.715389E+10 | 0.620896E+10 | 11359.54 | 03-OCT-08:61 | 9638.37 | 0.45 |
November | 0.00 | 0.00 | 0.368788E+10 | 0.309240E+10 | 12888.46 | 12-NOV-09:02 | 7723.38 | 0.32 |
December | 0.00 | 0.00 | 0.181789E+10 | 0.180422E+10 | 10282.59 | 03-DEC-16:01 | 10282.59 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.892659E+11 | 0.781201E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.124692E+10 | 0.914801E+09 | 10282.59 | 7723.38 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.133462E+11 | 0.126321E+11 | 12929.00 | 10373.11 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.901007E+09 | 0.809179E+09 | 11610.90 | 08-JAN-20:12 | 8021.59 | 0.07 |
February | 0.00 | 0.00 | 0.270874E+09 | 0.186241E+09 | 10557.77 | 18-FEB-16:01 | 9414.66 | 0.09 |
March | 0.00 | 0.00 | 0.121391E+10 | 0.900108E+09 | 10251.76 | 23-MAR-21:11 | 10251.76 | 0.24 |
April | 0.00 | 0.00 | 0.710849E+10 | 0.688626E+10 | 10737.81 | 26-APR-21:51 | 10737.81 | 0.16 |
May | 0.00 | 0.00 | 0.964691E+10 | 0.954856E+10 | 11335.34 | 08-MAY-08:61 | 11335.34 | 0.07 |
June | 0.00 | 0.00 | 0.132026E+11 | 0.125128E+11 | 11451.41 | 21-JUN-07:42 | 11451.41 | 0.60 |
July | 0.00 | 0.00 | 0.127041E+11 | 0.104364E+11 | 13414.85 | 27-JUL-08:11 | 9057.75 | 0.81 |
August | 0.00 | 0.00 | 0.117372E+11 | 0.937071E+10 | 13611.82 | 28-AUG-18:31 | 9687.96 | 0.82 |
September | 0.00 | 0.00 | 0.957166E+10 | 0.733621E+10 | 13700.47 | 04-SEP-08:51 | 8373.63 | 0.86 |
October | 0.00 | 0.00 | 0.451319E+10 | 0.376890E+10 | 13177.83 | 03-OCT-08:61 | 9589.14 | 0.34 |
November | 0.00 | 0.00 | 0.120991E+10 | 0.927245E+09 | 13031.94 | 13-NOV-16:01 | 8425.98 | 0.17 |
December | 0.00 | 0.00 | 0.284924E+09 | 0.284087E+09 | 10217.98 | 03-DEC-16:01 | 10217.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.723649E+11 | 0.629666E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.270874E+09 | 0.186241E+09 | 10217.98 | 8021.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132026E+11 | 0.125128E+11 | 13700.47 | 11451.41 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.450314E+11 | 0.430305E+11 | 49552.42 | 14-JAN-13:40 | 49552.42 | 0.14 |
February | 0.00 | 0.00 | 0.161896E+11 | 0.122780E+11 | 36908.08 | 01-FEB-14:15 | 36908.08 | 0.32 |
March | 0.00 | 0.00 | 0.188666E+11 | 0.153562E+11 | 34055.11 | 18-MAR-13:40 | 32071.21 | 0.27 |
April | 0.00 | 0.00 | 0.411591E+11 | 0.405875E+11 | 35011.73 | 14-APR-13:40 | 35011.73 | 0.04 |
May | 0.00 | 0.00 | 0.412495E+11 | 0.412495E+11 | 29578.95 | 09-MAY-17:13 | 29578.95 | 0.00 |
June | 0.00 | 0.00 | 0.533303E+11 | 0.515861E+11 | 37510.34 | 29-JUN-19:10 | 30658.27 | 0.12 |
July | 0.00 | 0.00 | 0.555768E+11 | 0.392274E+11 | 36743.90 | 23-JUL-08:00 | 27141.49 | 0.76 |
August | 0.00 | 0.00 | 0.587627E+11 | 0.412945E+11 | 40662.70 | 28-AUG-12:30 | 30841.70 | 0.86 |
September | 0.00 | 0.00 | 0.591502E+11 | 0.426676E+11 | 47413.77 | 28-SEP-13:30 | 44192.25 | 0.89 |
October | 0.00 | 0.00 | 0.509496E+11 | 0.442027E+11 | 48883.98 | 18-OCT-13:30 | 48883.98 | 0.41 |
November | 0.00 | 0.00 | 0.385067E+11 | 0.343294E+11 | 51386.88 | 20-NOV-14:30 | 51386.88 | 0.29 |
December | 0.00 | 0.00 | 0.325590E+11 | 0.324131E+11 | 49116.21 | 25-DEC-13:30 | 49116.21 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.511331E+12 | 0.438223E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.161896E+11 | 0.122780E+11 | 29578.95 | 27141.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.591502E+11 | 0.515861E+11 | 51386.88 | 51386.88 | 0.89 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.911517E+10 | 0.733785E+10 | 119006.59 | 31-JAN-19:01 | 119006.59 | 0.12 |
February | 0.00 | 0.00 | 0.887065E+10 | 0.330942E+10 | 113237.35 | 27-FEB-19:01 | 113237.35 | 0.39 |
March | 0.00 | 0.00 | 0.150543E+11 | 0.919031E+10 | 121284.88 | 16-MAR-15:01 | 121284.88 | 0.33 |
April | 0.00 | 0.00 | 0.394496E+11 | 0.367281E+11 | 122724.88 | 26-APR-21:51 | 122724.88 | 0.12 |
May | 0.00 | 0.00 | 0.545393E+11 | 0.532953E+11 | 128999.34 | 20-MAY-08:61 | 128999.34 | 0.05 |
June | 0.00 | 0.00 | 0.759969E+11 | 0.647375E+11 | 131669.99 | 11-JUN-08:61 | 131669.99 | 0.50 |
July | 0.00 | 0.00 | 0.819535E+11 | 0.548701E+11 | 131889.04 | 01-JUL-08:61 | 131889.04 | 0.77 |
August | 0.00 | 0.00 | 0.745938E+11 | 0.470219E+11 | 123549.49 | 28-AUG-18:31 | 87070.00 | 0.77 |
September | 0.00 | 0.00 | 0.637552E+11 | 0.374364E+11 | 123634.46 | 03-SEP-08:52 | 80298.29 | 0.79 |
October | 0.00 | 0.00 | 0.314108E+11 | 0.225137E+11 | 121227.70 | 19-OCT-15:01 | 121227.70 | 0.32 |
November | 0.00 | 0.00 | 0.126145E+11 | 0.771342E+10 | 119439.63 | 10-NOV-16:01 | 119439.63 | 0.20 |
December | 0.00 | 0.00 | 0.464043E+10 | 0.451876E+10 | 116487.48 | 03-DEC-09:02 | 116487.48 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.471994E+12 | 0.348673E+12 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.464043E+10 | 0.330942E+10 | 113237.35 | 80298.29 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.819535E+11 | 0.647375E+11 | 131889.04 | 131889.04 | 0.79 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.346248E+10 | 0.315401E+10 | 10119.28 | 08-JAN-19:02 | 7422.14 | 0.21 |
February | 0.00 | 0.00 | 0.150612E+10 | 0.105270E+10 | 10427.10 | 18-FEB-09:02 | 8081.62 | 0.35 |
March | 0.00 | 0.00 | 0.298515E+10 | 0.238338E+10 | 9346.01 | 06-MAR-16:02 | 7349.01 | 0.43 |
April | 0.00 | 0.00 | 0.885317E+10 | 0.861156E+10 | 9082.25 | 18-APR-15:01 | 9082.25 | 0.20 |
May | 0.00 | 0.00 | 0.107179E+11 | 0.106266E+11 | 9082.96 | 10-MAY-15:01 | 9082.96 | 0.09 |
June | 0.00 | 0.00 | 0.137545E+11 | 0.132193E+11 | 9145.44 | 17-JUN-18:02 | 9145.44 | 0.61 |
July | 0.00 | 0.00 | 0.137916E+11 | 0.117178E+11 | 9745.36 | 09-JUL-08:61 | 8699.58 | 0.84 |
August | 0.00 | 0.00 | 0.134203E+11 | 0.111598E+11 | 10705.15 | 04-AUG-08:61 | 8074.44 | 0.89 |
September | 0.00 | 0.00 | 0.115430E+11 | 0.930643E+10 | 11342.58 | 03-SEP-08:61 | 7650.89 | 0.98 |
October | 0.00 | 0.00 | 0.748250E+10 | 0.662773E+10 | 10016.50 | 22-OCT-08:62 | 8524.08 | 0.47 |
November | 0.00 | 0.00 | 0.342700E+10 | 0.288462E+10 | 11813.34 | 13-NOV-16:01 | 7119.21 | 0.32 |
December | 0.00 | 0.00 | 0.185226E+10 | 0.183794E+10 | 9082.72 | 27-DEC-09:02 | 9082.72 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.927961E+11 | 0.825818E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.150612E+10 | 0.105270E+10 | 9082.25 | 7119.21 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.137916E+11 | 0.132193E+11 | 11813.34 | 9145.44 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.893807E+09 | 0.790120E+09 | 10211.09 | 08-JAN-20:12 | 7023.31 | 0.08 |
February | 0.00 | 0.00 | 0.502558E+09 | 0.312056E+09 | 10229.05 | 18-FEB-09:02 | 7816.24 | 0.15 |
March | 0.00 | 0.00 | 0.144461E+10 | 0.108353E+10 | 9088.92 | 18-MAR-08:51 | 9088.92 | 0.29 |
April | 0.00 | 0.00 | 0.705372E+10 | 0.683941E+10 | 10472.47 | 05-APR-08:51 | 10472.47 | 0.18 |
May | 0.00 | 0.00 | 0.968920E+10 | 0.960383E+10 | 11566.09 | 21-MAY-08:61 | 11566.09 | 0.08 |
June | 0.00 | 0.00 | 0.134472E+11 | 0.129377E+11 | 11532.44 | 13-JUN-07:52 | 11532.44 | 0.62 |
July | 0.00 | 0.00 | 0.135534E+11 | 0.115535E+11 | 12424.79 | 27-JUL-08:11 | 9216.73 | 0.83 |
August | 0.00 | 0.00 | 0.124556E+11 | 0.103524E+11 | 12060.75 | 28-AUG-18:31 | 8696.42 | 0.84 |
September | 0.00 | 0.00 | 0.989946E+10 | 0.790482E+10 | 12990.45 | 04-SEP-08:51 | 8827.26 | 0.87 |
October | 0.00 | 0.00 | 0.473313E+10 | 0.402752E+10 | 12149.32 | 03-OCT-08:61 | 9402.61 | 0.38 |
November | 0.00 | 0.00 | 0.108234E+10 | 0.833360E+09 | 11439.57 | 13-NOV-16:01 | 6547.56 | 0.16 |
December | 0.00 | 0.00 | 0.337667E+09 | 0.332708E+09 | 9025.39 | 25-DEC-16:02 | 9025.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.750926E+11 | 0.665710E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.337667E+09 | 0.312056E+09 | 9025.39 | 6547.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135534E+11 | 0.129377E+11 | 12990.45 | 11566.09 | 0.87 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.819799E+09 | 0.759765E+09 | 2865.45 | 08-JAN-19:02 | 1996.90 | 0.16 |
February | 0.00 | 0.00 | 0.277079E+09 | 0.210307E+09 | 2922.66 | 18-FEB-16:01 | 2608.46 | 0.22 |
March | 0.00 | 0.00 | 0.673221E+09 | 0.555200E+09 | 2723.99 | 23-MAR-15:01 | 2723.99 | 0.33 |
April | 0.00 | 0.00 | 0.218238E+10 | 0.211308E+10 | 2723.85 | 18-APR-15:01 | 2723.85 | 0.19 |
May | 0.00 | 0.00 | 0.262231E+10 | 0.258994E+10 | 2723.99 | 11-MAY-18:01 | 2723.99 | 0.08 |
June | 0.00 | 0.00 | 0.351696E+10 | 0.332503E+10 | 2795.90 | 30-JUN-08:61 | 2690.10 | 0.61 |
July | 0.00 | 0.00 | 0.337387E+10 | 0.275819E+10 | 3255.38 | 27-JUL-08:61 | 2391.82 | 0.84 |
August | 0.00 | 0.00 | 0.328967E+10 | 0.263886E+10 | 3399.78 | 04-AUG-08:61 | 2294.87 | 0.87 |
September | 0.00 | 0.00 | 0.280846E+10 | 0.215101E+10 | 3613.01 | 03-SEP-08:61 | 2151.22 | 0.96 |
October | 0.00 | 0.00 | 0.169305E+10 | 0.145525E+10 | 3163.96 | 03-OCT-08:61 | 2452.07 | 0.43 |
November | 0.00 | 0.00 | 0.821484E+09 | 0.697438E+09 | 3427.83 | 12-NOV-16:02 | 2053.25 | 0.26 |
December | 0.00 | 0.00 | 0.405604E+09 | 0.402531E+09 | 2723.75 | 03-DEC-16:01 | 2723.75 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.224839E+11 | 0.196566E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.277079E+09 | 0.210307E+09 | 2723.75 | 1996.90 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.351696E+10 | 0.332503E+10 | 3613.01 | 2723.99 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182800E+09 | 0.169483E+09 | 2837.26 | 08-JAN-16:01 | 2632.78 | 0.05 |
February | 0.00 | 0.00 | 49871424.96 | 36187805.86 | 2848.57 | 18-FEB-16:01 | 2466.76 | 0.06 |
March | 0.00 | 0.00 | 0.275865E+09 | 0.212599E+09 | 2713.20 | 23-MAR-21:11 | 2713.20 | 0.19 |
April | 0.00 | 0.00 | 0.181630E+10 | 0.175429E+10 | 2840.22 | 26-APR-21:51 | 2840.22 | 0.17 |
May | 0.00 | 0.00 | 0.249177E+10 | 0.246272E+10 | 2968.31 | 08-MAY-08:61 | 2968.31 | 0.07 |
June | 0.00 | 0.00 | 0.350318E+10 | 0.331686E+10 | 2993.59 | 14-JUN-08:61 | 2993.59 | 0.62 |
July | 0.00 | 0.00 | 0.333906E+10 | 0.273529E+10 | 3599.77 | 27-JUL-08:11 | 2317.06 | 0.82 |
August | 0.00 | 0.00 | 0.307791E+10 | 0.245729E+10 | 3644.72 | 28-AUG-18:31 | 2518.73 | 0.82 |
September | 0.00 | 0.00 | 0.244400E+10 | 0.185199E+10 | 3715.98 | 04-SEP-08:51 | 2133.79 | 0.86 |
October | 0.00 | 0.00 | 0.106608E+10 | 0.883383E+09 | 3579.64 | 03-OCT-08:61 | 2395.74 | 0.33 |
November | 0.00 | 0.00 | 0.241545E+09 | 0.191372E+09 | 3518.25 | 13-NOV-16:01 | 2184.33 | 0.13 |
December | 0.00 | 0.00 | 54878234.24 | 54598324.04 | 2704.96 | 03-DEC-16:01 | 2704.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185433E+11 | 0.161261E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 49871424.96 | 36187805.86 | 2704.96 | 2133.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.350318E+10 | 0.331686E+10 | 3715.98 | 2993.59 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.995928E+10 | 0.898585E+10 | 22875.74 | 01-JAN-16:02 | 22875.74 | 0.28 |
February | 0.00 | 0.00 | 0.437378E+10 | 0.264428E+10 | 22876.64 | 01-FEB-16:01 | 22876.64 | 0.49 |
March | 0.00 | 0.00 | 0.517715E+10 | 0.347757E+10 | 22871.11 | 08-MAR-16:01 | 22871.11 | 0.46 |
April | 0.00 | 0.00 | 0.104580E+11 | 0.951485E+10 | 22877.92 | 13-APR-18:01 | 22877.92 | 0.23 |
May | 0.00 | 0.00 | 0.109011E+11 | 0.103429E+11 | 22878.37 | 29-MAY-18:01 | 22878.37 | 0.13 |
June | 0.00 | 0.00 | 0.144851E+11 | 0.113130E+11 | 22879.12 | 08-JUN-15:01 | 22879.12 | 0.68 |
July | 0.00 | 0.00 | 0.160177E+11 | 0.103548E+11 | 22858.75 | 03-JUL-15:01 | 22858.75 | 0.86 |
August | 0.00 | 0.00 | 0.166722E+11 | 0.109742E+11 | 22876.03 | 25-AUG-15:01 | 22876.03 | 0.87 |
September | 0.00 | 0.00 | 0.161365E+11 | 0.102456E+11 | 22758.70 | 03-SEP-08:61 | 15115.08 | 0.96 |
October | 0.00 | 0.00 | 0.122878E+11 | 0.982757E+10 | 22873.05 | 31-OCT-18:01 | 22873.05 | 0.48 |
November | 0.00 | 0.00 | 0.890808E+10 | 0.728130E+10 | 22875.96 | 20-NOV-16:02 | 22875.96 | 0.37 |
December | 0.00 | 0.00 | 0.729589E+10 | 0.721703E+10 | 22875.59 | 25-DEC-16:02 | 22875.59 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.132673E+12 | 0.102179E+12 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.437378E+10 | 0.264428E+10 | 22758.70 | 15115.08 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.166722E+11 | 0.113130E+11 | 22879.12 | 22879.12 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 21271.97 | 145882.90 | 01-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 27002.45 | 118383.30 | 09-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 16729.59 | 131102.11 | 26-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 965.47 | 86894.25 | 21-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 34.97 | 36436.00 | 01-MAY-08:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 3.60 | 12724.08 | 05-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.06 | 16478.13 | 02-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.52 | 19159.56 | 25-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.85 | 19530.87 | 03-SEP-21:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5486.47 | 124305.50 | 25-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 15182.14 | 122351.66 | 23-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30072.08 | 148250.02 | 16-DEC-09:03 |
Annual Sum or Average | 0.00 | 9654.10 | ||||
Minimum of Months | 0.00 | 0.00 | 3.60 | 12724.08 | ||
Maximum of Months | 0.00 | 0.00 | 30072.08 | 148250.02 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 72475.95 | 385976.75 | 31-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 27337.75 | 285341.26 | 09-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66718.62 | 392263.03 | 15-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 182827.89 | 485559.32 | 14-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 224774.21 | 491997.07 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 296564.11 | 545479.47 | 01-JUN-18:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 324222.58 | 620803.88 | 13-JUL-18:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 316590.20 | 573128.11 | 09-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 300290.90 | 662318.65 | 10-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 159696.97 | 514940.66 | 01-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80173.39 | 407458.03 | 01-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 43045.98 | 376490.09 | 02-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 175327.14 | 0.00 | ||||
Minimum of Months | 27337.75 | 285341.26 | 0.00 | 0.00 | ||
Maximum of Months | 324222.58 | 662318.65 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 23575.08 | 47657.07 | 24-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23354.87 | 47528.27 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22317.57 | 46176.40 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20652.76 | 42917.67 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18860.89 | 39462.87 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17412.60 | 35892.76 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16680.07 | 33494.83 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16914.43 | 34391.17 | 30-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 17995.39 | 37171.19 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19652.71 | 41210.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21442.90 | 44623.21 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22877.03 | 46990.33 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 20126.73 | ||||
Minimum of Months | 0.00 | 0.00 | 16680.07 | 33494.83 | ||
Maximum of Months | 0.00 | 0.00 | 23575.08 | 47657.07 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.76 | 1299.30 | 03-JAN-09:03 | 0.97 |
February | 0.244774E+10 | 0.76 | 1299.30 | 07-FEB-16:03 | 0.96 |
March | 0.271000E+10 | 0.76 | 1299.30 | 02-MAR-16:04 | 0.96 |
April | 0.262258E+10 | 0.77 | 1299.30 | 28-APR-18:03 | 0.97 |
May | 0.271000E+10 | 0.77 | 1299.30 | 13-MAY-18:03 | 0.97 |
June | 0.262258E+10 | 0.76 | 1299.30 | 03-JUN-18:20 | 0.96 |
July | 0.271000E+10 | 0.76 | 1299.30 | 05-JUL-18:17 | 0.96 |
August | 0.271000E+10 | 0.76 | 1299.30 | 02-AUG-18:04 | 0.96 |
September | 0.262258E+10 | 0.76 | 1299.30 | 01-SEP-18:04 | 0.96 |
October | 0.271000E+10 | 0.76 | 1299.30 | 13-OCT-08:03 | 0.97 |
November | 0.262258E+10 | 0.76 | 1299.30 | 01-NOV-08:52 | 0.96 |
December | 0.271000E+10 | 0.77 | 1299.30 | 06-DEC-16:03 | 0.97 |
Annual Sum or Average | 0.319080E+11 | 0.76 | |||
Minimum of Months | 0.244774E+10 | 0.76 | 1299.30 | 0.96 | |
Maximum of Months | 0.271000E+10 | 0.77 | 1299.30 | 0.97 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355264E+11 | 0.86 | 26705.53 | 19-JAN-22:10 | 1.29 |
February | 0.299845E+11 | 0.82 | 22661.99 | 01-FEB-22:10 | 1.17 |
March | 0.343289E+11 | 0.84 | 26688.57 | 16-MAR-21:10 | 1.28 |
April | 0.379039E+11 | 0.90 | 32638.02 | 14-APR-21:10 | 1.45 |
May | 0.408437E+11 | 0.92 | 32562.82 | 19-MAY-21:10 | 1.45 |
June | 0.445098E+11 | 0.98 | 36598.20 | 29-JUN-21:10 | 1.55 |
July | 0.457147E+11 | 0.97 | 38815.80 | 21-JUL-21:10 | 1.60 |
August | 0.465010E+11 | 0.98 | 39976.74 | 25-AUG-21:10 | 1.65 |
September | 0.451489E+11 | 0.98 | 41650.26 | 08-SEP-21:10 | 1.68 |
October | 0.417420E+11 | 0.93 | 41076.62 | 06-OCT-21:10 | 1.67 |
November | 0.366518E+11 | 0.88 | 32199.84 | 01-NOV-21:10 | 1.43 |
December | 0.353044E+11 | 0.85 | 27895.54 | 26-DEC-22:10 | 1.32 |
Annual Sum or Average | 0.474160E+12 | 0.91 | |||
Minimum of Months | 0.299845E+11 | 0.82 | 22661.99 | 1.17 | |
Maximum of Months | 0.465010E+11 | 0.98 | 41650.26 | 1.68 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.29 | 76.61 | 01-JAN-00:03 | 0.29 |
February | 0.185347E+09 | 0.29 | 76.61 | 01-FEB-00:10 | 0.29 |
March | 0.205205E+09 | 0.29 | 76.61 | 01-MAR-00:05 | 0.29 |
April | 0.198586E+09 | 0.29 | 76.61 | 01-APR-00:10 | 0.29 |
May | 0.205205E+09 | 0.29 | 76.61 | 01-MAY-00:05 | 0.29 |
June | 0.198586E+09 | 0.29 | 76.61 | 01-JUN-00:05 | 0.29 |
July | 0.205205E+09 | 0.29 | 76.61 | 01-JUL-00:10 | 0.29 |
August | 0.205205E+09 | 0.29 | 76.61 | 01-AUG-00:05 | 0.29 |
September | 0.198586E+09 | 0.29 | 76.61 | 01-SEP-00:05 | 0.29 |
October | 0.205205E+09 | 0.29 | 76.61 | 01-OCT-00:10 | 0.29 |
November | 0.198586E+09 | 0.29 | 76.61 | 01-NOV-00:05 | 0.29 |
December | 0.205205E+09 | 0.29 | 76.61 | 01-DEC-00:10 | 0.29 |
Annual Sum or Average | 0.241613E+10 | 0.29 | |||
Minimum of Months | 0.185347E+09 | 0.29 | 76.61 | 0.29 | |
Maximum of Months | 0.205205E+09 | 0.29 | 76.61 | 0.29 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.21 | 612.92 | 01-JAN-07:10 | 0.29 |
February | 0.105030E+10 | 0.21 | 612.92 | 01-FEB-07:03 | 0.29 |
March | 0.116283E+10 | 0.21 | 612.92 | 01-MAR-07:05 | 0.29 |
April | 0.112532E+10 | 0.21 | 612.92 | 01-APR-06:05 | 0.29 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.29 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.29 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.29 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.29 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.29 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.29 |
November | 0.112532E+10 | 0.21 | 612.92 | 01-NOV-06:05 | 0.29 |
December | 0.116283E+10 | 0.21 | 612.92 | 01-DEC-07:05 | 0.29 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.29 | |
Maximum of Months | 0.116283E+10 | 0.21 | 612.92 | 0.29 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360684E+09 | 0.56 | 870.63 | 01-JAN-16:02 | 0.63 |
February | 0.198170E+09 | 0.49 | 870.63 | 01-FEB-16:01 | 0.63 |
March | 0.314832E+09 | 0.52 | 870.63 | 01-MAR-16:01 | 0.63 |
April | 0.750455E+09 | 0.60 | 870.63 | 01-APR-08:62 | 0.63 |
May | 0.865562E+09 | 0.61 | 870.63 | 01-MAY-08:62 | 0.64 |
June | 0.123587E+10 | 0.62 | 870.63 | 01-JUN-08:61 | 0.63 |
July | 0.103651E+10 | 0.61 | 870.63 | 01-JUL-08:61 | 0.64 |
August | 0.999015E+09 | 0.61 | 870.63 | 01-AUG-08:61 | 0.63 |
September | 0.870684E+09 | 0.61 | 870.63 | 01-SEP-08:61 | 0.63 |
October | 0.612388E+09 | 0.58 | 870.63 | 01-OCT-08:61 | 0.63 |
November | 0.339408E+09 | 0.55 | 870.63 | 01-NOV-08:62 | 0.63 |
December | 0.273813E+09 | 0.53 | 870.63 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.785739E+10 | 0.57 | |||
Minimum of Months | 0.198170E+09 | 0.49 | 870.63 | 0.63 | |
Maximum of Months | 0.123587E+10 | 0.62 | 870.63 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171244E+09 | 0.40 | 865.15 | 01-JAN-09:02 | 0.63 |
February | 0.146095E+09 | 0.41 | 865.15 | 01-FEB-16:01 | 0.63 |
March | 0.186665E+09 | 0.38 | 865.15 | 01-MAR-16:01 | 0.63 |
April | 0.626288E+09 | 0.51 | 865.15 | 01-APR-08:51 | 0.63 |
May | 0.817050E+09 | 0.54 | 865.15 | 01-MAY-08:51 | 0.64 |
June | 0.123819E+10 | 0.58 | 865.15 | 01-JUN-07:22 | 0.63 |
July | 0.102885E+10 | 0.60 | 865.15 | 01-JUL-08:61 | 0.64 |
August | 0.934197E+09 | 0.57 | 865.15 | 01-AUG-08:61 | 0.63 |
September | 0.751462E+09 | 0.54 | 865.15 | 01-SEP-08:61 | 0.63 |
October | 0.398404E+09 | 0.44 | 865.15 | 01-OCT-07:42 | 0.63 |
November | 0.167811E+09 | 0.39 | 865.15 | 01-NOV-08:52 | 0.63 |
December | 0.213522E+09 | 0.41 | 865.15 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.667978E+10 | 0.48 | |||
Minimum of Months | 0.146095E+09 | 0.38 | 865.15 | 0.63 | |
Maximum of Months | 0.123819E+10 | 0.60 | 865.15 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.242703E+10 | 0.51 | 3041.28 | 12-JAN-14:30 | 0.63 |
February | 0.944364E+09 | 0.35 | 1599.33 | 25-FEB-14:30 | 0.63 |
March | 0.115773E+10 | 0.41 | 1583.26 | 18-MAR-14:00 | 0.63 |
April | 0.217798E+10 | 0.60 | 1535.16 | 14-APR-13:40 | 0.64 |
May | 0.223588E+10 | 0.63 | 1356.67 | 09-MAY-17:13 | 0.64 |
June | 0.272335E+10 | 0.63 | 2742.85 | 29-JUN-19:10 | 0.63 |
July | 0.264688E+10 | 0.63 | 1560.23 | 21-JUL-20:20 | 0.63 |
August | 0.276227E+10 | 0.63 | 2545.35 | 28-AUG-12:30 | 0.63 |
September | 0.286954E+10 | 0.63 | 3131.71 | 28-SEP-13:40 | 0.63 |
October | 0.269452E+10 | 0.58 | 3245.97 | 06-OCT-13:40 | 0.63 |
November | 0.204740E+10 | 0.50 | 3104.72 | 01-NOV-15:01 | 0.63 |
December | 0.174189E+10 | 0.43 | 2749.64 | 25-DEC-13:30 | 0.64 |
Annual Sum or Average | 0.264288E+11 | 0.55 | |||
Minimum of Months | 0.944364E+09 | 0.35 | 1356.67 | 0.63 | |
Maximum of Months | 0.286954E+10 | 0.63 | 3245.97 | 0.64 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.612097E+09 | 0.36 | 5460.58 | 03-JAN-09:03 | 0.64 |
February | 0.558308E+09 | 0.40 | 5460.58 | 01-FEB-09:02 | 0.63 |
March | 0.800890E+09 | 0.35 | 5460.58 | 01-MAR-09:02 | 0.63 |
April | 0.178667E+10 | 0.45 | 5460.58 | 01-APR-08:51 | 0.64 |
May | 0.243319E+10 | 0.49 | 5460.58 | 01-MAY-08:51 | 0.64 |
June | 0.367156E+10 | 0.56 | 5460.58 | 01-JUN-07:22 | 0.63 |
July | 0.353426E+10 | 0.57 | 5460.58 | 01-JUL-08:61 | 0.64 |
August | 0.314161E+10 | 0.54 | 5460.58 | 01-AUG-08:61 | 0.63 |
September | 0.269985E+10 | 0.50 | 5460.58 | 01-SEP-08:61 | 0.63 |
October | 0.140100E+10 | 0.39 | 5460.58 | 01-OCT-08:61 | 0.63 |
November | 0.657861E+09 | 0.34 | 5460.58 | 01-NOV-08:52 | 0.63 |
December | 0.768984E+09 | 0.39 | 5460.58 | 01-DEC-09:03 | 0.63 |
Annual Sum or Average | 0.220663E+11 | 0.45 | |||
Minimum of Months | 0.558308E+09 | 0.34 | 5460.58 | 0.63 | |
Maximum of Months | 0.367156E+10 | 0.57 | 5460.58 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.347020E+09 | 0.57 | 768.74 | 01-JAN-09:02 | 0.63 |
February | 0.202791E+09 | 0.52 | 768.74 | 01-FEB-09:02 | 0.63 |
March | 0.314322E+09 | 0.55 | 768.74 | 01-MAR-09:02 | 0.63 |
April | 0.762244E+09 | 0.62 | 768.74 | 01-APR-08:62 | 0.63 |
May | 0.902767E+09 | 0.62 | 768.74 | 01-MAY-08:62 | 0.64 |
June | 0.130942E+10 | 0.63 | 768.74 | 01-JUN-07:00 | 0.63 |
July | 0.115386E+10 | 0.62 | 768.74 | 01-JUL-08:61 | 0.64 |
August | 0.110365E+10 | 0.62 | 768.74 | 01-AUG-08:61 | 0.63 |
September | 0.930204E+09 | 0.62 | 768.74 | 01-SEP-08:61 | 0.63 |
October | 0.643113E+09 | 0.60 | 768.74 | 01-OCT-08:61 | 0.63 |
November | 0.322700E+09 | 0.56 | 768.74 | 01-NOV-08:62 | 0.63 |
December | 0.263963E+09 | 0.53 | 768.74 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.825606E+10 | 0.59 | |||
Minimum of Months | 0.202791E+09 | 0.52 | 768.74 | 0.63 | |
Maximum of Months | 0.130942E+10 | 0.63 | 768.74 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159984E+09 | 0.38 | 764.02 | 01-JAN-19:01 | 0.63 |
February | 0.138287E+09 | 0.40 | 764.02 | 01-FEB-09:02 | 0.63 |
March | 0.189905E+09 | 0.39 | 764.02 | 01-MAR-09:02 | 0.63 |
April | 0.607638E+09 | 0.53 | 764.02 | 01-APR-08:51 | 0.63 |
May | 0.815624E+09 | 0.55 | 764.02 | 01-MAY-08:51 | 0.64 |
June | 0.129600E+10 | 0.59 | 764.02 | 01-JUN-07:22 | 0.63 |
July | 0.113766E+10 | 0.60 | 764.02 | 01-JUL-07:42 | 0.64 |
August | 0.101924E+10 | 0.58 | 764.02 | 01-AUG-08:61 | 0.63 |
September | 0.782725E+09 | 0.55 | 764.02 | 01-SEP-07:02 | 0.63 |
October | 0.409817E+09 | 0.46 | 764.02 | 01-OCT-07:42 | 0.63 |
November | 0.151694E+09 | 0.37 | 764.02 | 01-NOV-08:52 | 0.63 |
December | 0.189300E+09 | 0.40 | 764.02 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.689786E+10 | 0.49 | |||
Minimum of Months | 0.138287E+09 | 0.37 | 764.02 | 0.63 | |
Maximum of Months | 0.129600E+10 | 0.60 | 764.02 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 94360812.65 | 0.55 | 230.67 | 01-JAN-09:02 | 0.63 |
February | 58100577.39 | 0.49 | 230.67 | 01-FEB-16:01 | 0.63 |
March | 84532617.37 | 0.52 | 230.67 | 01-MAR-16:01 | 0.63 |
April | 0.191660E+09 | 0.60 | 230.67 | 01-APR-08:62 | 0.63 |
May | 0.222113E+09 | 0.61 | 230.67 | 01-MAY-08:62 | 0.64 |
June | 0.323228E+09 | 0.62 | 230.67 | 01-JUN-08:61 | 0.63 |
July | 0.270618E+09 | 0.61 | 230.67 | 01-JUL-08:61 | 0.64 |
August | 0.258753E+09 | 0.61 | 230.67 | 01-AUG-08:61 | 0.63 |
September | 0.220126E+09 | 0.61 | 230.67 | 01-SEP-08:61 | 0.63 |
October | 0.150701E+09 | 0.58 | 230.67 | 01-OCT-08:61 | 0.63 |
November | 86230193.02 | 0.54 | 230.67 | 01-NOV-08:62 | 0.63 |
December | 78702531.49 | 0.52 | 230.67 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.203913E+10 | 0.57 | |||
Minimum of Months | 58100577.39 | 0.49 | 230.67 | 0.63 | |
Maximum of Months | 0.323228E+09 | 0.62 | 230.67 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 52834330.61 | 0.40 | 229.07 | 01-JAN-09:02 | 0.63 |
February | 47881368.74 | 0.41 | 229.07 | 01-FEB-09:02 | 0.63 |
March | 52670685.16 | 0.38 | 229.07 | 01-MAR-16:01 | 0.63 |
April | 0.161837E+09 | 0.51 | 229.07 | 01-APR-08:51 | 0.63 |
May | 0.211680E+09 | 0.54 | 229.07 | 01-MAY-08:51 | 0.64 |
June | 0.325397E+09 | 0.58 | 229.07 | 01-JUN-07:22 | 0.63 |
July | 0.269270E+09 | 0.60 | 229.07 | 01-JUL-08:61 | 0.64 |
August | 0.242442E+09 | 0.57 | 229.07 | 01-AUG-08:61 | 0.63 |
September | 0.191975E+09 | 0.54 | 229.07 | 01-SEP-08:61 | 0.63 |
October | 99827587.69 | 0.44 | 229.07 | 01-OCT-08:61 | 0.63 |
November | 47313936.29 | 0.38 | 229.07 | 01-NOV-08:52 | 0.63 |
December | 69301579.96 | 0.41 | 229.07 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.177243E+10 | 0.48 | |||
Minimum of Months | 47313936.29 | 0.38 | 229.07 | 0.63 | |
Maximum of Months | 0.325397E+09 | 0.60 | 229.07 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.448984E+09 | 0.59 | 1024.01 | 01-JAN-09:02 | 0.63 |
February | 0.234636E+09 | 0.54 | 1024.01 | 01-FEB-09:02 | 0.63 |
March | 0.278922E+09 | 0.55 | 1024.01 | 01-MAR-09:02 | 0.63 |
April | 0.463348E+09 | 0.60 | 1024.01 | 01-APR-08:62 | 0.63 |
May | 0.478861E+09 | 0.60 | 1024.01 | 01-MAY-15:01 | 0.63 |
June | 0.675778E+09 | 0.61 | 1024.01 | 01-JUN-08:61 | 0.63 |
July | 0.676411E+09 | 0.61 | 1024.01 | 01-JUL-08:61 | 0.64 |
August | 0.694231E+09 | 0.61 | 1024.01 | 01-AUG-08:61 | 0.63 |
September | 0.684124E+09 | 0.61 | 1024.01 | 01-SEP-08:61 | 0.63 |
October | 0.549999E+09 | 0.60 | 1024.01 | 01-OCT-08:61 | 0.63 |
November | 0.397508E+09 | 0.58 | 1024.01 | 01-NOV-08:62 | 0.63 |
December | 0.368488E+09 | 0.58 | 1024.01 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.595129E+10 | 0.59 | |||
Minimum of Months | 0.234636E+09 | 0.54 | 1024.01 | 0.63 | |
Maximum of Months | 0.694231E+09 | 0.61 | 1024.01 | 0.64 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.381342E+09 | 0.343208E+09 | 673.12 | 02-JAN-04:25 | 605.80 | 605.80 | 39.10 | 1.49 |
February | 0.437967E+09 | 0.394170E+09 | 654.03 | 09-FEB-05:00 | 588.63 | 588.63 | 39.83 | 1.35 |
March | 0.302039E+09 | 0.271835E+09 | 660.94 | 26-MAR-08:03 | 594.85 | 594.85 | 37.52 | 1.40 |
April | 16490479.60 | 14841431.64 | 506.36 | 21-APR-06:10 | 455.72 | 455.72 | 34.23 | 0.77 |
May | 797326.93 | 717594.24 | 219.24 | 01-MAY-08:53 | 197.32 | 197.32 | 25.67 | 0.25 |
June | 114975.54 | 103477.99 | 151.15 | 30-JUN-08:06 | 136.04 | 136.04 | 42.45 | 0.17 |
July | 459706.99 | 413736.29 | 194.00 | 02-JUL-08:15 | 174.60 | 174.60 | 42.06 | 0.22 |
August | 578455.22 | 520609.70 | 222.14 | 25-AUG-08:04 | 199.93 | 199.93 | 42.12 | 0.26 |
September | 736099.41 | 662489.47 | 219.65 | 23-SEP-08:55 | 197.68 | 197.68 | 41.82 | 0.25 |
October | 97563225.66 | 87806903.10 | 643.44 | 25-OCT-08:03 | 579.10 | 579.10 | 36.76 | 1.28 |
November | 0.264792E+09 | 0.238313E+09 | 667.45 | 24-NOV-04:37 | 600.71 | 600.71 | 40.09 | 1.44 |
December | 0.555049E+09 | 0.499544E+09 | 679.42 | 16-DEC-09:03 | 611.47 | 611.47 | 37.09 | 1.55 |
Annual Sum or Average | 0.205793E+10 | 0.185214E+10 | ||||||
Minimum of Months | 114975.54 | 103477.99 | 151.15 | 136.04 | 136.04 | 25.67 | 0.17 | |
Maximum of Months | 0.555049E+09 | 0.499544E+09 | 679.42 | 611.47 | 611.47 | 42.45 | 1.55 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.108777E+09 | 97898852.35 | 369.85 | 26-JAN-16:02 | 332.87 | 332.87 | 6.72 | 9.10 |
February | 33008751.18 | 29707876.07 | 282.91 | 18-FEB-16:01 | 254.62 | 254.62 | 6.72 | 8.06 |
March | 0.112274E+09 | 0.101047E+09 | 823.98 | 17-MAR-18:01 | 741.58 | 741.58 | 6.72 | 12.91 |
April | 0.389350E+09 | 0.350415E+09 | 1075.20 | 25-APR-19:50 | 967.68 | 967.68 | 6.72 | 14.45 |
May | 0.477257E+09 | 0.429532E+09 | 839.49 | 29-MAY-20:50 | 755.54 | 755.54 | 6.72 | 13.01 |
June | 0.926704E+09 | 0.834033E+09 | 1696.35 | 30-JUN-18:02 | 1526.72 | 1526.72 | 6.72 | 17.45 |
July | 0.106125E+10 | 0.955121E+09 | 1424.89 | 07-JUL-20:20 | 1282.40 | 1282.40 | 6.72 | 16.24 |
August | 0.102311E+10 | 0.920796E+09 | 1443.93 | 27-AUG-18:02 | 1299.54 | 1299.54 | 6.72 | 16.33 |
September | 0.986144E+09 | 0.887529E+09 | 1450.14 | 18-SEP-18:13 | 1305.13 | 1305.13 | 6.72 | 16.36 |
October | 0.412249E+09 | 0.371024E+09 | 1182.44 | 05-OCT-20:10 | 1064.20 | 1064.20 | 6.72 | 15.03 |
November | 0.130709E+09 | 0.117638E+09 | 889.94 | 01-NOV-18:01 | 800.94 | 800.94 | 6.72 | 13.34 |
December | 57003446.85 | 51303102.17 | 361.11 | 21-DEC-16:02 | 325.00 | 325.00 | 6.72 | 9.00 |
Annual Sum or Average | 0.571783E+10 | 0.514604E+10 | ||||||
Minimum of Months | 33008751.18 | 29707876.07 | 282.91 | 254.62 | 254.62 | 6.72 | 8.06 | |
Maximum of Months | 0.106125E+10 | 0.955121E+09 | 1696.35 | 1526.72 | 1526.72 | 6.72 | 17.45 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.704846E+10 | 0.634362E+10 | 2798.56 | 01-JAN-08:40 | 2518.71 | 2518.71 | 6.76 | 24.76 |
February | 0.575653E+10 | 0.518088E+10 | 2798.56 | 01-FEB-00:10 | 2518.71 | 2518.71 | 6.94 | 24.76 |
March | 0.702509E+10 | 0.632258E+10 | 2798.56 | 01-MAR-00:05 | 2518.71 | 2518.71 | 6.80 | 24.76 |
April | 0.725388E+10 | 0.652849E+10 | 2798.56 | 01-APR-00:10 | 2518.71 | 2518.71 | 6.94 | 24.76 |
May | 0.749567E+10 | 0.674611E+10 | 2798.56 | 01-MAY-00:05 | 2518.71 | 2518.71 | 7.88 | 24.76 |
June | 0.725388E+10 | 0.652849E+10 | 2798.56 | 01-JUN-00:05 | 2518.71 | 2518.71 | 8.96 | 24.76 |
July | 0.749567E+10 | 0.674611E+10 | 2798.56 | 01-JUL-00:10 | 2518.71 | 2518.71 | 9.41 | 24.76 |
August | 0.749567E+10 | 0.674611E+10 | 2798.56 | 01-AUG-00:05 | 2518.71 | 2518.71 | 9.68 | 24.76 |
September | 0.725388E+10 | 0.652849E+10 | 2798.56 | 01-SEP-00:05 | 2518.71 | 2518.71 | 9.21 | 24.76 |
October | 0.744698E+10 | 0.670228E+10 | 2798.56 | 01-OCT-00:10 | 2518.71 | 2518.71 | 8.98 | 24.76 |
November | 0.686272E+10 | 0.617645E+10 | 2798.56 | 01-NOV-00:05 | 2518.71 | 2518.71 | 7.43 | 24.76 |
December | 0.625342E+10 | 0.562808E+10 | 2798.56 | 01-DEC-00:10 | 2518.71 | 2518.71 | 6.78 | 24.76 |
Annual Sum or Average | 0.846419E+11 | 0.761777E+11 | ||||||
Minimum of Months | 0.575653E+10 | 0.518088E+10 | 2798.56 | 2518.71 | 2518.71 | 6.76 | 24.76 | |
Maximum of Months | 0.749567E+10 | 0.674611E+10 | 2798.56 | 2518.71 | 2518.71 | 9.68 | 24.76 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 49.85 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.49 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 50.87 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.33 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.96 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.51 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.68 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.90 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.45 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.09 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.71 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 51.30 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.85 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.90 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 40.07 | 60.00 | 21271.97 | 145882.90 | 01-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33.32 | 60.00 | 27002.45 | 118383.30 | 09-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 42.13 | 60.00 | 16729.59 | 131102.11 | 26-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 40.36 | 40.36 | 965.47 | 86894.25 | 21-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32.02 | 32.02 | 34.97 | 36436.00 | 01-MAY-08:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 40.95 | 40.95 | 3.60 | 12724.08 | 05-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 42.44 | 42.44 | 14.06 | 16478.13 | 02-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 42.40 | 42.40 | 17.52 | 19159.56 | 25-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 42.05 | 42.05 | 23.85 | 19530.87 | 03-SEP-21:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42.33 | 42.33 | 5486.47 | 124305.50 | 25-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 34.02 | 34.02 | 15182.14 | 122351.66 | 23-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.63 | 60.00 | 30072.08 | 148250.02 | 16-DEC-09:03 |
Annual Sum or Average | 0.00 | 9654.10 | ||||||
Minimum of Months | 0.00 | 0.00 | 29.63 | 32.02 | 3.60 | 12724.08 | ||
Maximum of Months | 0.00 | 0.00 | 42.44 | 60.00 | 30072.08 | 148250.02 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 72475.95 | 385976.75 | 31-JAN-19:03 | 10.42 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 27337.75 | 285341.26 | 09-FEB-16:02 | 9.45 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66718.62 | 392263.03 | 15-MAR-18:03 | 10.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 182827.89 | 485559.32 | 14-APR-18:03 | 11.38 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 224774.21 | 491997.07 | 31-MAY-18:03 | 11.44 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 296564.11 | 545479.47 | 01-JUN-18:05 | 11.96 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 324222.58 | 620803.88 | 13-JUL-18:01 | 12.69 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 316590.20 | 573128.11 | 09-AUG-18:03 | 12.23 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 300290.90 | 662318.65 | 10-SEP-21:52 | 13.09 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 159696.97 | 514940.66 | 01-OCT-18:03 | 11.67 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80173.39 | 407458.03 | 01-NOV-15:03 | 10.63 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 43045.98 | 376490.09 | 02-DEC-16:01 | 10.33 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 175327.14 | 0.00 | ||||||
Minimum of Months | 27337.75 | 285341.26 | 9.45 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 324222.58 | 662318.65 | 13.09 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 49.85 | 59.83 | 23575.08 | 47657.07 | 24-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.49 | 58.54 | 23354.87 | 47528.27 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 50.87 | 59.02 | 22317.57 | 46176.40 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.33 | 59.07 | 20652.76 | 42917.67 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.96 | 59.23 | 18860.89 | 39462.87 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.51 | 59.32 | 17412.60 | 35892.76 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.68 | 59.16 | 16680.07 | 33494.83 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.90 | 59.66 | 16914.43 | 34391.17 | 30-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.45 | 58.93 | 17995.39 | 37171.19 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.09 | 58.38 | 19652.71 | 41210.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.71 | 59.65 | 21442.90 | 44623.21 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.30 | 59.11 | 22877.03 | 46990.33 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 20126.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.85 | 58.38 | 16680.07 | 33494.83 | ||
Maximum of Months | 0.00 | 0.00 | 54.90 | 59.83 | 23575.08 | 47657.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.538201E+11 | 0.00 | 0.107053E+12 | 0.355264E+11 | 0.00 | 0.00 |
February | 0.610159E+11 | 0.00 | 0.259170E+11 | 0.299845E+11 | 0.00 | 0.00 |
March | 0.420902E+11 | 0.00 | 0.115953E+12 | 0.343289E+11 | 0.00 | 0.00 |
April | 0.239762E+10 | 0.00 | 0.319688E+12 | 0.379039E+11 | 0.00 | 0.00 |
May | 31732750.82 | 0.00 | 0.416056E+12 | 0.408437E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.525161E+12 | 0.445098E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.610996E+12 | 0.457147E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.597337E+12 | 0.465010E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.550077E+12 | 0.451489E+11 | 0.00 | 0.00 |
October | 0.142224E+11 | 0.00 | 0.281643E+12 | 0.417420E+11 | 0.00 | 0.00 |
November | 0.371663E+11 | 0.00 | 0.122609E+12 | 0.366518E+11 | 0.00 | 0.00 |
December | 0.705438E+11 | 0.00 | 0.568426E+11 | 0.353044E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.281288E+12 | 0.00 | 0.372933E+13 | 0.474160E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.259170E+11 | 0.299845E+11 | 0.00 | 0.00 |
Maximum of Months | 0.705438E+11 | 0.00 | 0.610996E+12 | 0.465010E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 12839.38 | 0.00 | 0.673159E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 8073.07 | 0.00 | 0.173081E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 8919.95 | 0.00 | 0.789044E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 26065.56 | 0.00 | 0.209561E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 22631.98 | 0.00 | 0.271661E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 15745.57 | 0.00 | 0.323567E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 14201.11 | 0.00 | 0.374524E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 14529.94 | 0.00 | 0.371941E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 13531.26 | 0.00 | 0.352438E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 16391.25 | 0.00 | 0.180490E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 11811.15 | 0.00 | 0.849529E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 1157742.71 | 0.00 | 0.357258E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 1322482.93 | 0.00 | 0.236839E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 8073.07 | 0.00 | 0.173081E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 1157742.71 | 0.00 | 0.374524E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355264E+11 | 0.107053E+12 | 0.538201E+11 | 0.130664E+11 | 0.254237E+09 | 0.00 | 0.00 | 0.00 |
February | 0.299845E+11 | 0.259170E+11 | 0.610159E+11 | 0.100583E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343289E+11 | 0.115953E+12 | 0.420902E+11 | 0.199280E+11 | 0.883568E+09 | 0.00 | 0.00 | 0.00 |
April | 0.379039E+11 | 0.319688E+12 | 0.239762E+10 | 0.105839E+11 | 0.205548E+11 | 0.00 | 0.00 | 0.00 |
May | 0.408437E+11 | 0.416056E+12 | 31732750.82 | 0.138278E+11 | 0.407157E+11 | 0.00 | 0.00 | 0.00 |
June | 0.445098E+11 | 0.525161E+12 | 0.00 | 0.254817E+11 | 0.758459E+11 | 0.00 | 0.00 | 0.00 |
July | 0.457147E+11 | 0.610996E+12 | 0.00 | 0.119673E+11 | 0.105913E+12 | 0.00 | 0.00 | 0.00 |
August | 0.465010E+11 | 0.597337E+12 | 0.00 | 0.134270E+11 | 0.929677E+11 | 0.00 | 0.00 | 0.00 |
September | 0.451489E+11 | 0.550077E+12 | 0.00 | 0.113352E+11 | 0.684232E+11 | 0.00 | 0.00 | 0.00 |
October | 0.417420E+11 | 0.281643E+12 | 0.142224E+11 | 0.807304E+10 | 0.183008E+11 | 0.00 | 0.00 | 0.00 |
November | 0.366518E+11 | 0.122609E+12 | 0.371663E+11 | 0.131910E+11 | 0.548462E+09 | 0.00 | 0.00 | 0.00 |
December | 0.353044E+11 | 0.568426E+11 | 0.705438E+11 | 0.706604E+11 | 26742878.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474160E+12 | 0.372933E+13 | 0.281288E+12 | 0.212548E+12 | 0.424434E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299845E+11 | 0.259170E+11 | 0.00 | 0.100583E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465010E+11 | 0.610996E+12 | 0.705438E+11 | 0.706604E+11 | 0.105913E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.673159E+10 | 12839.38 | 0.111955E+11 | 9741928.20 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.173081E+10 | 8073.07 | 0.101526E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.789044E+10 | 8919.95 | 0.937194E+10 | 83283017.87 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.209561E+11 | 26065.56 | 0.178868E+10 | 0.197007E+10 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.271661E+11 | 22631.98 | 0.153421E+10 | 0.384587E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.323567E+11 | 15745.57 | 0.135819E+10 | 0.947447E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.374524E+11 | 14201.11 | 0.373519E+09 | 0.229304E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.371941E+11 | 14529.94 | 0.334714E+09 | 0.206160E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.352438E+11 | 13531.26 | 0.261500E+09 | 0.155117E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.180490E+11 | 16391.25 | 0.303828E+10 | 0.335545E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.849529E+10 | 11811.15 | 0.851527E+10 | 93405320.53 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.357258E+10 | 1157742.71 | 0.186997E+11 | 3360480.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.236839E+12 | 1322482.93 | 0.666242E+11 | 0.778937E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.173081E+10 | 8073.07 | 0.261500E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.374524E+11 | 1157742.71 | 0.186997E+11 | 0.229304E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.355264E+11 | 0.538201E+11 | 0.107053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299845E+11 | 0.610159E+11 | 0.259170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343289E+11 | 0.420902E+11 | 0.115953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379039E+11 | 0.239762E+10 | 0.319688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408437E+11 | 31732750.82 | 0.416056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.445098E+11 | 0.00 | 0.525161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.457147E+11 | 0.00 | 0.610996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465010E+11 | 0.00 | 0.597337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.451489E+11 | 0.00 | 0.550077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417420E+11 | 0.142224E+11 | 0.281643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366518E+11 | 0.371663E+11 | 0.122609E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353044E+11 | 0.705438E+11 | 0.568426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474160E+12 | 0.281288E+12 | 0.372933E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299845E+11 | 0.00 | 0.259170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465010E+11 | 0.705438E+11 | 0.610996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 12839.38 | 0.673159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 8073.07 | 0.173081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 8919.95 | 0.789044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 26065.56 | 0.209561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 22631.98 | 0.271661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 15745.57 | 0.323567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 14201.11 | 0.374524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 14529.94 | 0.371941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 13531.26 | 0.352438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 16391.25 | 0.180490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 11811.15 | 0.849529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 1157742.71 | 0.357258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 1322482.93 | 0.236839E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 8073.07 | 0.173081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 1157742.71 | 0.374524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292973E+10 | 895720.98 | 0.00 | 49841851.75 | 292465.31 | 0.00 | 0.430844E+11 | 0.00 | 1.03 |
February | 0.344108E+11 | 0.00 | 0.00 | 6094210.70 | 0.00 | 0.00 | 0.114408E+11 | 0.00 | 0.98 |
March | 0.394843E+11 | 0.00 | 0.00 | 142424.40 | 12113326.38 | 0.00 | 0.472120E+09 | 0.00 | 0.98 |
April | 0.175403E+11 | 0.00 | 0.00 | 1525149.73 | 0.590324E+09 | 0.00 | 0.123023E+10 | 0.00 | 0.94 |
May | 0.125157E+11 | 0.00 | 0.00 | 57431.79 | 0.135344E+10 | 0.00 | 99407363.63 | 0.00 | 0.91 |
June | 0.551710E+10 | 26421157.44 | 0.00 | 1289678.68 | 0.310741E+10 | 0.00 | 0.206185E+09 | 0.00 | 0.77 |
July | 0.506696E+09 | 0.533035E+10 | 0.00 | 21953786.06 | 0.951897E+09 | 0.00 | 0.221038E+10 | 0.00 | 0.81 |
August | 109313.67 | 0.527350E+10 | 0.00 | 36493404.89 | 0.262055E+09 | 0.00 | 0.379904E+10 | 0.00 | 0.92 |
September | 0.00 | 0.580454E+10 | 0.00 | 50511502.13 | 4886388.58 | 0.00 | 0.718986E+10 | 0.00 | 1.12 |
October | 0.00 | 0.814690E+09 | 0.00 | 0.102580E+09 | 0.00 | 0.00 | 0.360914E+11 | 0.00 | 1.27 |
November | 0.00 | 15509961.93 | 0.00 | 0.106930E+09 | 0.00 | 0.00 | 0.525960E+11 | 0.00 | 1.29 |
December | 2777503.73 | 0.00 | 0.00 | 99441770.66 | 0.00 | 0.00 | 0.625694E+11 | 0.00 | 1.21 |
Annual Sum or Average | 0.112907E+12 | 0.172659E+11 | 0.00 | 0.476862E+09 | 0.628242E+10 | 0.00 | 0.220989E+12 | 0.00 | 1.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 57431.79 | 0.00 | 0.00 | 99407363.63 | 0.00 | 0.77 |
Maximum of Months | 0.394843E+11 | 0.580454E+10 | 0.00 | 0.106930E+09 | 0.310741E+10 | 0.00 | 0.625694E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421687E+10 | 301291.97 | 0.00 | 5295789.79 | 0.00 | 0.00 | 0.158716E+10 | 0.00 | 2.62 |
February | 0.535037E+10 | 0.00 | 0.00 | 1049281.12 | 0.00 | 0.00 | 0.643720E+09 | 0.00 | 2.33 |
March | 0.482618E+10 | 1339403.13 | 0.00 | 1054233.46 | 393683.57 | 17514039.48 | 0.341906E+09 | 0.00 | 2.33 |
April | 0.167036E+10 | 0.105453E+09 | 0.00 | 3681821.22 | 126322.66 | 0.00 | 0.777036E+09 | 0.00 | 2.40 |
May | 0.102767E+10 | 0.201129E+09 | 0.00 | 2604488.71 | 3126981.81 | 0.00 | 0.618887E+09 | 0.00 | 2.27 |
June | 0.123149E+09 | 0.533211E+09 | 0.00 | 3486994.90 | 960176.77 | 0.00 | 0.644145E+09 | 0.00 | 2.11 |
July | 65869641.61 | 0.891230E+09 | 0.00 | 1942659.36 | 28786016.67 | 0.00 | 0.281930E+09 | 0.00 | 2.05 |
August | 95924031.07 | 0.823787E+09 | 0.00 | 2195062.07 | 21376695.42 | 0.00 | 0.324180E+09 | 0.00 | 2.21 |
September | 0.198516E+09 | 0.681557E+09 | 0.00 | 2668036.22 | 90612243.36 | 0.00 | 0.470893E+09 | 0.00 | 2.40 |
October | 0.228282E+10 | 0.147614E+09 | 0.00 | 4848415.79 | 1432133.95 | 0.00 | 0.111986E+10 | 0.00 | 2.61 |
November | 0.379056E+10 | 309088.74 | 0.00 | 4425602.73 | 1834530.07 | 0.00 | 0.137148E+10 | 0.00 | 2.58 |
December | 0.521939E+10 | 0.00 | 0.00 | 3220838.96 | 0.00 | 40010838.91 | 0.116532E+10 | 0.00 | 2.46 |
Annual Sum or Average | 0.288677E+11 | 0.338593E+10 | 0.00 | 36473224.32 | 0.148649E+09 | 57524878.40 | 0.934652E+10 | 0.00 | 2.36 |
Minimum of Months | 65869641.61 | 0.00 | 0.00 | 1049281.12 | 0.00 | 0.00 | 0.281930E+09 | 0.00 | 2.05 |
Maximum of Months | 0.535037E+10 | 0.891230E+09 | 0.00 | 5295789.79 | 90612243.36 | 40010838.91 | 0.158716E+10 | 0.00 | 2.62 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205097E+10 | 12547.77 | 0.00 | 1752983.56 | 97221.98 | 0.00 | 0.202380E+10 | 0.00 | 1.44 |
February | 0.338371E+10 | 0.00 | 0.00 | 514194.18 | 0.00 | 0.00 | 0.850793E+09 | 0.00 | 1.42 |
March | 0.241967E+10 | 0.00 | 0.00 | 1278747.86 | 1119081.04 | 0.00 | 0.130463E+10 | 0.00 | 1.44 |
April | 0.176556E+09 | 42638668.77 | 0.00 | 4847110.38 | 12049849.85 | 0.00 | 0.173645E+10 | 0.00 | 1.52 |
May | 25137964.02 | 0.110429E+09 | 0.00 | 5034027.10 | 15980838.57 | 0.00 | 0.130780E+10 | 0.00 | 1.51 |
June | 73536.51 | 0.298800E+09 | 0.00 | 5282400.46 | 8204594.49 | 0.00 | 0.691062E+09 | 0.00 | 1.37 |
July | 420915.94 | 0.595362E+09 | 0.00 | 2791134.04 | 27885715.85 | 0.00 | 0.307485E+09 | 0.00 | 1.31 |
August | 1137161.84 | 0.491332E+09 | 0.00 | 3284544.36 | 29734988.24 | 0.00 | 0.360831E+09 | 0.00 | 1.37 |
September | 4302892.76 | 0.447293E+09 | 0.00 | 3448407.21 | 35920254.05 | 0.00 | 0.548636E+09 | 0.00 | 1.44 |
October | 0.718007E+09 | 67934699.96 | 0.00 | 3982900.40 | 3809822.56 | 0.00 | 0.182101E+10 | 0.00 | 1.51 |
November | 0.171719E+10 | 98235.31 | 0.00 | 1956618.69 | 1326936.10 | 0.00 | 0.191939E+10 | 0.00 | 1.46 |
December | 0.316605E+10 | 0.00 | 0.00 | 773456.40 | 0.00 | 0.00 | 0.132115E+10 | 0.00 | 1.41 |
Annual Sum or Average | 0.136632E+11 | 0.205390E+10 | 0.00 | 34946524.65 | 0.136129E+09 | 0.00 | 0.141930E+11 | 0.00 | 1.43 |
Minimum of Months | 73536.51 | 0.00 | 0.00 | 514194.18 | 0.00 | 0.00 | 0.307485E+09 | 0.00 | 1.31 |
Maximum of Months | 0.338371E+10 | 0.595362E+09 | 0.00 | 5282400.46 | 35920254.05 | 0.00 | 0.202380E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365308E+10 | 0.00 | 0.00 | 0.00 | 100717.26 | 0.00 | 0.00 | 0.00 | 0.61 |
February | 0.387577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
March | 0.338694E+10 | 0.00 | 0.00 | 0.00 | 1026792.74 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.139264E+10 | 331488.20 | 0.00 | 565745.76 | 49707691.11 | 0.00 | 0.202534E+09 | 0.00 | 0.60 |
May | 0.478554E+09 | 38150340.97 | 0.00 | 1903809.21 | 76815443.69 | 0.00 | 0.612655E+09 | 0.00 | 0.60 |
June | 145756.66 | 0.302412E+09 | 0.00 | 4827538.32 | 1561203.37 | 0.00 | 0.591502E+09 | 0.00 | 0.60 |
July | 5864146.92 | 0.576003E+09 | 0.00 | 2473138.19 | 20054239.32 | 0.00 | 0.263275E+09 | 0.00 | 0.58 |
August | 29601525.03 | 0.445858E+09 | 0.00 | 2562229.77 | 36409964.76 | 0.00 | 0.268352E+09 | 0.00 | 0.57 |
September | 59071633.42 | 0.350509E+09 | 0.00 | 2111873.46 | 83765748.15 | 0.00 | 0.394029E+09 | 0.00 | 0.58 |
October | 0.195988E+10 | 46793893.75 | 0.00 | 784229.93 | 18095482.27 | 0.00 | 0.233326E+09 | 0.00 | 0.61 |
November | 0.324766E+10 | 0.00 | 0.00 | 0.00 | 1307640.48 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.409101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.221802E+11 | 0.176006E+10 | 0.00 | 15228564.65 | 0.288845E+09 | 0.00 | 0.256567E+10 | 0.00 | 0.60 |
Minimum of Months | 145756.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.409101E+10 | 0.576003E+09 | 0.00 | 4827538.32 | 83765748.15 | 0.00 | 0.612655E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215208E+10 | 0.00 | 0.00 | 0.00 | 59334.06 | 0.00 | 0.00 | 0.00 | 0.62 |
February | 0.228327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
March | 0.199530E+10 | 0.00 | 0.00 | 0.00 | 604899.16 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.913051E+09 | 12274.11 | 0.00 | 53872.11 | 29466549.46 | 0.00 | 24317577.55 | 0.00 | 0.60 |
May | 0.489329E+09 | 13250268.88 | 0.00 | 465526.35 | 54337533.28 | 0.00 | 0.141528E+09 | 0.00 | 0.59 |
June | 7240788.28 | 0.171387E+09 | 0.00 | 2229935.83 | 2676779.25 | 0.00 | 0.303200E+09 | 0.00 | 0.56 |
July | 6852008.46 | 0.309081E+09 | 0.00 | 1198122.51 | 18570912.10 | 0.00 | 0.133952E+09 | 0.00 | 0.54 |
August | 30827398.35 | 0.231243E+09 | 0.00 | 998246.11 | 35903937.31 | 0.00 | 0.131967E+09 | 0.00 | 0.54 |
September | 0.104107E+09 | 0.159980E+09 | 0.00 | 646679.87 | 82222597.46 | 0.00 | 0.151334E+09 | 0.00 | 0.56 |
October | 0.123381E+10 | 23260146.83 | 0.00 | 174421.20 | 13755017.47 | 0.00 | 54614150.20 | 0.00 | 0.62 |
November | 0.191325E+10 | 0.00 | 0.00 | 0.00 | 770350.82 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 0.241008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.135392E+11 | 0.908213E+09 | 0.00 | 5766803.98 | 0.238368E+09 | 0.00 | 0.940912E+09 | 0.00 | 0.59 |
Minimum of Months | 6852008.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.241008E+10 | 0.309081E+09 | 0.00 | 2229935.83 | 82222597.46 | 0.00 | 0.303200E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112451E+09 | 1490500.93 | 0.00 | 0.113762E+09 | 0.00 | 0.00 | 0.666316E+11 | 0.00 | 23.21 |
February | 58392176.67 | 0.00 | 0.00 | 92627180.51 | 0.00 | 0.00 | 0.695449E+11 | 0.00 | 23.08 |
March | 40632444.81 | 15195364.96 | 0.00 | 0.113346E+09 | 0.00 | 0.00 | 0.610647E+11 | 0.00 | 23.59 |
April | 0.00 | 0.748637E+09 | 0.00 | 0.111387E+09 | 0.00 | 0.00 | 0.277820E+11 | 0.00 | 22.43 |
May | 0.00 | 0.175928E+10 | 0.00 | 95185009.31 | 0.00 | 0.00 | 0.180496E+11 | 0.00 | 21.57 |
June | 0.00 | 0.424183E+10 | 0.00 | 64096969.38 | 0.00 | 0.00 | 0.792927E+10 | 0.00 | 17.85 |
July | 0.00 | 0.886665E+10 | 0.00 | 32891463.95 | 0.00 | 0.00 | 0.360088E+10 | 0.00 | 17.70 |
August | 0.00 | 0.748578E+10 | 0.00 | 40774208.79 | 0.00 | 0.00 | 0.443170E+10 | 0.00 | 18.59 |
September | 0.00 | 0.700963E+10 | 0.00 | 51664576.10 | 0.00 | 0.00 | 0.727446E+10 | 0.00 | 19.95 |
October | 3554664.95 | 0.100974E+10 | 0.00 | 0.108092E+09 | 0.00 | 0.00 | 0.395661E+11 | 0.00 | 22.89 |
November | 51179941.17 | 19351592.08 | 0.00 | 0.110077E+09 | 0.00 | 0.00 | 0.593648E+11 | 0.00 | 23.49 |
December | 93166717.97 | 0.00 | 0.00 | 0.105658E+09 | 0.00 | 0.00 | 0.748058E+11 | 0.00 | 22.87 |
Annual Sum or Average | 0.359376E+09 | 0.311576E+11 | 0.00 | 0.103956E+10 | 0.00 | 0.00 | 0.440046E+12 | 0.00 | 21.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32891463.95 | 0.00 | 0.00 | 0.360088E+10 | 0.00 | 17.70 |
Maximum of Months | 0.112451E+09 | 0.886665E+10 | 0.00 | 0.113762E+09 | 0.00 | 0.00 | 0.748058E+11 | 0.00 | 23.59 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238747E+10 | 1097895.45 | 0.00 | 43924332.52 | 0.00 | 0.00 | 0.230586E+11 | 0.00 | 4.01 |
February | 0.657637E+10 | 0.00 | 0.00 | 19270164.36 | 0.00 | 0.00 | 0.189455E+11 | 0.00 | 3.55 |
March | 0.526615E+10 | 7218618.64 | 0.00 | 23878597.63 | 20606.77 | 0.00 | 0.169649E+11 | 0.00 | 3.58 |
April | 0.987511E+09 | 0.391402E+09 | 0.00 | 32458927.79 | 1177935.74 | 0.00 | 0.104463E+11 | 0.00 | 3.81 |
May | 0.345759E+09 | 0.778211E+09 | 0.00 | 26340019.27 | 13469094.54 | 0.00 | 0.759125E+10 | 0.00 | 3.66 |
June | 25994330.66 | 0.189607E+10 | 0.00 | 25477907.08 | 24239214.76 | 0.00 | 0.399670E+10 | 0.00 | 3.27 |
July | 4443350.14 | 0.365998E+10 | 0.00 | 14820373.14 | 78564995.99 | 0.00 | 0.179003E+10 | 0.00 | 3.22 |
August | 17046986.53 | 0.322236E+10 | 0.00 | 17659155.06 | 54104626.60 | 0.00 | 0.217298E+10 | 0.00 | 3.45 |
September | 52609740.82 | 0.305867E+10 | 0.00 | 20212993.61 | 57875610.84 | 0.00 | 0.339879E+10 | 0.00 | 3.76 |
October | 0.139579E+10 | 0.548906E+09 | 0.00 | 39218960.22 | 2699809.46 | 0.00 | 0.141659E+11 | 0.00 | 4.07 |
November | 0.160963E+10 | 1147423.97 | 0.00 | 39043918.66 | 7704464.03 | 0.00 | 0.210237E+11 | 0.00 | 3.95 |
December | 0.412457E+10 | 0.00 | 0.00 | 30863990.10 | 0.00 | 0.00 | 0.234365E+11 | 0.00 | 3.75 |
Annual Sum or Average | 0.227933E+11 | 0.135651E+11 | 0.00 | 0.333169E+09 | 0.239856E+09 | 0.00 | 0.146991E+12 | 0.00 | 3.67 |
Minimum of Months | 4443350.14 | 0.00 | 0.00 | 14820373.14 | 0.00 | 0.00 | 0.179003E+10 | 0.00 | 3.22 |
Maximum of Months | 0.657637E+10 | 0.365998E+10 | 0.00 | 43924332.52 | 78564995.99 | 0.00 | 0.234365E+11 | 0.00 | 4.07 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118430E+11 | 2198721.22 | 0.00 | 94306754.32 | 0.00 | 0.00 | 0.729695E+11 | 0.00 | 1.77 |
February | 0.324108E+11 | 0.00 | 0.00 | 40383276.77 | 0.00 | 0.00 | 0.536453E+11 | 0.00 | 1.71 |
March | 0.223531E+11 | 6833797.64 | 0.00 | 60889289.99 | 15581734.38 | 0.00 | 0.540468E+11 | 0.00 | 1.76 |
April | 0.246168E+10 | 0.101818E+10 | 0.00 | 0.104438E+09 | 77308061.15 | 0.00 | 0.380172E+11 | 0.00 | 1.85 |
May | 0.488095E+09 | 0.230323E+10 | 0.00 | 0.102414E+09 | 0.215436E+09 | 0.00 | 0.280835E+11 | 0.00 | 1.84 |
June | 17489391.37 | 0.576963E+10 | 0.00 | 0.101670E+09 | 0.263506E+09 | 0.00 | 0.144247E+11 | 0.00 | 1.62 |
July | 2712831.92 | 0.119430E+11 | 0.00 | 57417605.44 | 0.550362E+09 | 0.00 | 0.647639E+10 | 0.00 | 1.59 |
August | 5557740.92 | 0.987881E+10 | 0.00 | 67531090.67 | 0.523080E+09 | 0.00 | 0.770184E+10 | 0.00 | 1.66 |
September | 73484293.97 | 0.961436E+10 | 0.00 | 73099329.06 | 0.315283E+09 | 0.00 | 0.120898E+11 | 0.00 | 1.78 |
October | 0.553097E+10 | 0.147318E+10 | 0.00 | 0.111442E+09 | 18518273.91 | 0.00 | 0.482118E+11 | 0.00 | 1.88 |
November | 0.852148E+10 | 2282309.94 | 0.00 | 89840964.87 | 26310267.15 | 0.00 | 0.672814E+11 | 0.00 | 1.80 |
December | 0.256657E+11 | 0.00 | 0.00 | 58829059.65 | 0.00 | 0.00 | 0.660135E+11 | 0.00 | 1.71 |
Annual Sum or Average | 0.109374E+12 | 0.420117E+11 | 0.00 | 0.962261E+09 | 0.200539E+10 | 0.00 | 0.468962E+12 | 0.00 | 1.75 |
Minimum of Months | 2712831.92 | 0.00 | 0.00 | 40383276.77 | 0.00 | 0.00 | 0.647639E+10 | 0.00 | 1.59 |
Maximum of Months | 0.324108E+11 | 0.119430E+11 | 0.00 | 0.111442E+09 | 0.550362E+09 | 0.00 | 0.729695E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4716919.28 | 414990.90 | 0.00 | 11045626.35 | 0.00 | 0.232931E+09 | 0.898434E+09 | 0.00 | 0.35 |
February | 41068976.43 | 34884.02 | 0.00 | 4689456.87 | 0.00 | 0.455008E+09 | 0.609993E+09 | 0.00 | 0.36 |
March | 33525116.65 | 72039.82 | 0.00 | 9438437.30 | 0.00 | 0.288143E+09 | 0.752822E+09 | 0.00 | 0.36 |
April | 0.00 | 6566788.81 | 0.00 | 16236352.30 | 0.00 | 615815.12 | 0.594398E+09 | 0.00 | 0.35 |
May | 0.00 | 14176090.30 | 0.00 | 14601689.06 | 0.00 | 51124.17 | 0.407965E+09 | 0.00 | 0.35 |
June | 0.00 | 65249045.70 | 0.00 | 12590136.01 | 0.00 | 0.00 | 0.135641E+09 | 0.00 | 0.36 |
July | 0.00 | 0.500479E+09 | 0.00 | 2657468.03 | 0.00 | 0.00 | 50322074.70 | 0.00 | 0.36 |
August | 0.00 | 0.459229E+09 | 19522.66 | 2089970.18 | 0.00 | 0.00 | 33392433.58 | 1621.17 | 0.36 |
September | 0.00 | 0.377088E+09 | 34605.04 | 3795711.05 | 0.00 | 4906.24 | 45143796.35 | 494.06 | 0.36 |
October | 3828181.26 | 65085708.97 | 0.00 | 11811249.39 | 0.00 | 43939025.39 | 0.648199E+09 | 0.00 | 0.36 |
November | 5560943.77 | 8917036.39 | 12671.12 | 10040433.22 | 551793.79 | 0.177704E+09 | 0.795065E+09 | 1314.02 | 0.36 |
December | 26485708.83 | 0.00 | 0.00 | 6041235.28 | 455545.54 | 0.553568E+09 | 0.673295E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.115186E+09 | 0.149731E+10 | 66798.81 | 0.105038E+09 | 1007339.34 | 0.175196E+10 | 0.564467E+10 | 3429.25 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2089970.18 | 0.00 | 0.00 | 33392433.58 | 0.00 | 0.35 |
Maximum of Months | 41068976.43 | 0.500479E+09 | 34605.04 | 16236352.30 | 551793.79 | 0.553568E+09 | 0.898434E+09 | 1621.17 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175168E+09 | 122227.26 | 0.00 | 3553457.60 | 292715.02 | 0.479307E+09 | 0.488964E+09 | 0.00 | 0.35 |
February | 0.152260E+09 | 34879.94 | 0.00 | 1744688.64 | 0.00 | 0.665796E+09 | 0.290828E+09 | 0.00 | 0.36 |
March | 0.215455E+09 | 72031.38 | 0.00 | 4814365.85 | 0.00 | 0.364922E+09 | 0.498610E+09 | 0.00 | 0.36 |
April | 0.103207E+09 | 6535633.50 | 3483.49 | 12847960.64 | 26180.30 | 433232.92 | 0.494691E+09 | 722.12 | 0.35 |
May | 79861843.11 | 14172855.80 | 640.68 | 12005361.47 | 736.91 | 25776.43 | 0.330676E+09 | 195.97 | 0.36 |
June | 31943053.45 | 65236219.24 | 0.00 | 10959078.49 | 5181.57 | 1508.25 | 0.105310E+09 | 0.00 | 0.36 |
July | 10656347.07 | 0.492890E+09 | 0.00 | 2195641.89 | 7530535.68 | 0.00 | 40121346.45 | 0.00 | 0.36 |
August | 8484293.90 | 0.441487E+09 | 0.00 | 1504544.51 | 17709061.07 | 0.00 | 25489408.08 | 0.00 | 0.36 |
September | 16119038.98 | 0.340410E+09 | 50537.67 | 2858373.57 | 36616515.39 | 0.00 | 29961266.54 | 1773.16 | 0.36 |
October | 0.163500E+09 | 61146313.31 | 8077.49 | 6808713.52 | 3921779.05 | 78753087.46 | 0.458633E+09 | 1913.38 | 0.36 |
November | 0.193126E+09 | 7470616.88 | 12403.32 | 3860875.93 | 1997103.90 | 0.337011E+09 | 0.454258E+09 | 1580.18 | 0.36 |
December | 0.152441E+09 | 0.00 | 0.00 | 1727467.35 | 455492.17 | 0.879468E+09 | 0.225606E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.130222E+10 | 0.142958E+10 | 75142.65 | 64880529.45 | 68555301.06 | 0.280572E+10 | 0.344315E+10 | 6184.81 | 0.36 |
Minimum of Months | 8484293.90 | 0.00 | 0.00 | 1504544.51 | 0.00 | 0.00 | 25489408.08 | 0.00 | 0.35 |
Maximum of Months | 0.215455E+09 | 0.492890E+09 | 50537.67 | 12847960.64 | 36616515.39 | 0.879468E+09 | 0.498610E+09 | 1913.38 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 1735141.74 | 0.00 | 6637992.25 | 0.00 | 0.00 | 0.778834E+09 | 0.00 | 0.02 |
February | 0.274428E+09 | 0.00 | 0.00 | 2279199.94 | 0.00 | 0.00 | 0.901614E+09 | 0.00 | 0.02 |
March | 0.150053E+09 | 0.00 | 0.00 | 2552001.64 | 0.00 | 0.00 | 0.673448E+09 | 0.00 | 0.02 |
April | 0.00 | 16247092.86 | 0.00 | 3202035.52 | 0.00 | 0.00 | 0.143515E+09 | 0.00 | 0.02 |
May | 0.00 | 23304562.22 | 0.00 | 2108068.29 | 0.00 | 0.00 | 40418561.16 | 0.00 | 0.02 |
June | 0.00 | 0.165147E+09 | 0.00 | 330226.46 | 0.00 | 0.00 | 2681999.38 | 0.00 | 0.02 |
July | 0.00 | 0.246675E+09 | 0.00 | 111929.75 | 0.00 | 0.00 | 907099.07 | 0.00 | 0.02 |
August | 0.00 | 0.274709E+09 | 0.00 | 126319.23 | 0.00 | 0.00 | 869394.77 | 0.00 | 0.02 |
September | 0.00 | 0.229323E+09 | 0.00 | 875946.05 | 0.00 | 0.00 | 13830951.83 | 0.00 | 0.02 |
October | 0.00 | 37869888.94 | 0.00 | 4508040.87 | 0.00 | 0.00 | 0.414273E+09 | 0.00 | 0.02 |
November | 6098171.92 | 1768933.58 | 0.00 | 5078092.51 | 0.00 | 0.00 | 0.776842E+09 | 0.00 | 0.02 |
December | 46563232.32 | 0.00 | 0.00 | 4960413.66 | 0.00 | 0.00 | 0.919068E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.477143E+09 | 0.996779E+09 | 0.00 | 32770266.16 | 0.00 | 0.00 | 0.466630E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 111929.75 | 0.00 | 0.00 | 869394.77 | 0.00 | 0.02 |
Maximum of Months | 0.274428E+09 | 0.274709E+09 | 0.00 | 6637992.25 | 0.00 | 0.00 | 0.919068E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237712E+10 | 1387705.21 | 231637.84 | 45661590.62 | 3970503.69 | 0.680096E+09 | 0.124554E+11 | 38596.40 | 0.40 |
February | 0.205554E+10 | 473125.39 | 0.00 | 38142337.53 | 0.00 | 0.169845E+09 | 0.128015E+11 | 0.00 | 0.41 |
March | 0.294721E+10 | 977062.48 | 0.00 | 65483314.04 | 0.00 | 0.346998E+09 | 0.113414E+11 | 0.00 | 0.40 |
April | 0.146567E+10 | 75464504.58 | 280050.81 | 0.103047E+09 | 13176204.57 | 8819969.52 | 0.671273E+10 | 143354.43 | 0.40 |
May | 0.109764E+10 | 0.190825E+09 | 31450.68 | 99231217.98 | 1379965.32 | 1402947.24 | 0.453362E+10 | 30913.10 | 0.40 |
June | 0.433288E+09 | 0.884249E+09 | 632925.88 | 85476585.49 | 70284.95 | 227689.38 | 0.149143E+10 | 8507.64 | 0.40 |
July | 0.144547E+09 | 0.667601E+10 | 9582828.15 | 17346868.07 | 0.102147E+09 | 20390.19 | 0.556637E+09 | 166674.40 | 0.40 |
August | 0.115084E+09 | 0.597280E+10 | 10863762.89 | 11366352.25 | 0.244843E+09 | 0.00 | 0.354790E+09 | 216077.56 | 0.40 |
September | 0.219267E+09 | 0.458059E+10 | 10433767.09 | 24370622.65 | 0.523475E+09 | 0.00 | 0.420186E+09 | 352294.78 | 0.40 |
October | 0.223326E+10 | 0.807600E+09 | 1377500.73 | 69241301.14 | 73619705.38 | 33499644.54 | 0.726345E+10 | 147865.70 | 0.40 |
November | 0.264391E+10 | 0.100994E+09 | 232048.70 | 46825410.35 | 27326284.71 | 0.366334E+09 | 0.103480E+11 | 61562.71 | 0.40 |
December | 0.206777E+10 | 0.00 | 0.00 | 27395121.94 | 6178478.01 | 0.333031E+10 | 0.116554E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.178003E+11 | 0.192914E+11 | 33665972.76 | 0.633588E+09 | 0.996186E+09 | 0.493755E+10 | 0.799346E+11 | 1165846.71 | 0.40 |
Minimum of Months | 0.115084E+09 | 0.00 | 0.00 | 11366352.25 | 0.00 | 0.00 | 0.354790E+09 | 0.00 | 0.40 |
Maximum of Months | 0.294721E+10 | 0.667601E+10 | 10863762.89 | 0.103047E+09 | 0.523475E+09 | 0.333031E+10 | 0.128015E+11 | 352294.78 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4740848.78 | 394902.11 | 19921.03 | 10993706.14 | 0.00 | 0.257807E+09 | 0.873586E+09 | 167.76 | 0.35 |
February | 28899731.69 | 34884.02 | 0.00 | 5452069.07 | 0.00 | 0.428958E+09 | 0.647449E+09 | 0.00 | 0.36 |
March | 21200004.60 | 72039.82 | 0.00 | 9887419.96 | 0.00 | 0.271948E+09 | 0.780892E+09 | 0.00 | 0.36 |
April | 0.00 | 6566788.81 | 0.00 | 17604832.57 | 0.00 | 0.00 | 0.593645E+09 | 0.00 | 0.35 |
May | 0.00 | 14176090.30 | 0.00 | 16601564.05 | 0.00 | 0.00 | 0.406016E+09 | 0.00 | 0.35 |
June | 0.00 | 65249045.70 | 0.00 | 13335950.73 | 0.00 | 0.00 | 0.134895E+09 | 0.00 | 0.36 |
July | 0.00 | 0.500479E+09 | 0.00 | 2695444.86 | 0.00 | 0.00 | 50284097.87 | 0.00 | 0.36 |
August | 0.00 | 0.459250E+09 | 0.00 | 2042469.71 | 0.00 | 0.00 | 33439934.05 | 0.00 | 0.36 |
September | 0.00 | 0.377123E+09 | 0.00 | 3938377.56 | 0.00 | 4489.15 | 45001546.93 | 0.00 | 0.36 |
October | 795692.29 | 65085708.97 | 0.00 | 12608705.91 | 0.00 | 39675011.17 | 0.654698E+09 | 0.00 | 0.36 |
November | 7601400.09 | 8915721.13 | 13598.42 | 10094803.21 | 551793.79 | 0.205342E+09 | 0.765333E+09 | 1701.97 | 0.36 |
December | 25460698.14 | 0.00 | 0.00 | 6681640.90 | 455545.54 | 0.551189E+09 | 0.676058E+09 | 0.00 | 0.35 |
Annual Sum or Average | 88698375.59 | 0.149735E+10 | 33519.45 | 0.111937E+09 | 1007339.34 | 0.175492E+10 | 0.566130E+10 | 1869.74 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2042469.71 | 0.00 | 0.00 | 33439934.05 | 0.00 | 0.35 |
Maximum of Months | 28899731.69 | 0.500479E+09 | 19921.03 | 17604832.57 | 551793.79 | 0.551189E+09 | 0.873586E+09 | 1701.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174958E+09 | 102304.95 | 16187.03 | 4134217.28 | 292715.02 | 0.479130E+09 | 0.488770E+09 | 3735.29 | 0.35 |
February | 0.151539E+09 | 34879.94 | 0.00 | 2400777.89 | 0.00 | 0.553668E+09 | 0.403021E+09 | 0.00 | 0.36 |
March | 0.210660E+09 | 72031.38 | 0.00 | 5975619.63 | 0.00 | 0.322387E+09 | 0.544779E+09 | 0.00 | 0.36 |
April | 98879400.50 | 6562940.59 | 0.00 | 13698605.05 | 3078.83 | 120479.52 | 0.498480E+09 | 0.00 | 0.36 |
May | 77350984.17 | 14173692.45 | 0.00 | 12603748.52 | 736.91 | 0.00 | 0.332614E+09 | 0.00 | 0.36 |
June | 31015047.97 | 65236219.24 | 0.00 | 11210752.22 | 5181.57 | 0.00 | 0.105988E+09 | 0.00 | 0.36 |
July | 10565367.57 | 0.492978E+09 | 0.00 | 2146995.44 | 7442333.29 | 0.00 | 40260972.40 | 0.00 | 0.36 |
August | 8458618.37 | 0.441653E+09 | 0.00 | 1395154.44 | 17542965.36 | 0.00 | 25624473.67 | 0.00 | 0.36 |
September | 16032766.99 | 0.341173E+09 | 0.00 | 2818393.96 | 35905505.79 | 0.00 | 30087518.13 | 0.00 | 0.36 |
October | 0.160867E+09 | 61330520.71 | 0.00 | 7470281.16 | 3747562.51 | 75607522.81 | 0.463750E+09 | 0.00 | 0.36 |
November | 0.193195E+09 | 7469355.65 | 13721.73 | 4107870.53 | 1997103.90 | 0.352911E+09 | 0.438041E+09 | 1523.00 | 0.36 |
December | 0.152441E+09 | 0.00 | 0.00 | 1846039.36 | 455492.17 | 0.808642E+09 | 0.296313E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.128596E+10 | 0.143079E+10 | 29908.76 | 69808455.48 | 67392675.35 | 0.259247E+10 | 0.366773E+10 | 5258.28 | 0.36 |
Minimum of Months | 8458618.37 | 0.00 | 0.00 | 1395154.44 | 0.00 | 0.00 | 25624473.67 | 0.00 | 0.35 |
Maximum of Months | 0.210660E+09 | 0.492978E+09 | 16187.03 | 13698605.05 | 35905505.79 | 0.808642E+09 | 0.544779E+09 | 3735.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263226E+11 | 0.00 | 0.00 | 0.00 | 725728.80 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.279272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.244049E+11 | 0.00 | 0.00 | 0.00 | 7398662.97 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.111261E+11 | 9850685.75 | 0.00 | 737168.82 | 0.350712E+09 | 0.00 | 0.339240E+09 | 0.00 | 0.59 |
May | 0.620622E+10 | 0.122546E+09 | 0.00 | 4201355.13 | 0.704117E+09 | 0.00 | 0.149965E+10 | 0.00 | 0.57 |
June | 0.434667E+09 | 0.185384E+10 | 0.00 | 18407381.45 | 0.164663E+09 | 0.00 | 0.321799E+10 | 0.00 | 0.52 |
July | 0.210319E+09 | 0.313076E+10 | 0.00 | 8929769.45 | 0.638745E+09 | 0.00 | 0.143503E+10 | 0.00 | 0.50 |
August | 0.517464E+09 | 0.238863E+10 | 0.00 | 9549788.45 | 0.783157E+09 | 0.00 | 0.144929E+10 | 0.00 | 0.51 |
September | 0.126369E+10 | 0.175775E+10 | 0.00 | 7155882.74 | 0.117492E+10 | 0.00 | 0.185451E+10 | 0.00 | 0.54 |
October | 0.147917E+11 | 0.295471E+09 | 0.00 | 2564266.60 | 0.157162E+09 | 0.00 | 0.977798E+09 | 0.00 | 0.60 |
November | 0.234014E+11 | 0.00 | 0.00 | 0.00 | 9422340.84 | 0.00 | 0.00 | 0.00 | 0.61 |
December | 0.294782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.166085E+12 | 0.955884E+10 | 0.00 | 51545612.64 | 0.399103E+10 | 0.00 | 0.107735E+11 | 0.00 | 0.57 |
Minimum of Months | 0.210319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.294782E+11 | 0.313076E+10 | 0.00 | 18407381.45 | 0.117492E+10 | 0.00 | 0.321799E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1446865.69 | 103747.73 | 0.00 | 2471174.53 | 0.00 | 0.118517E+09 | 0.164347E+09 | 0.00 | 0.35 |
February | 10341989.62 | 8721.01 | 0.00 | 1040437.64 | 0.00 | 0.160041E+09 | 0.106267E+09 | 0.00 | 0.36 |
March | 8381279.16 | 18009.96 | 0.00 | 2225867.60 | 0.00 | 0.113309E+09 | 0.147066E+09 | 0.00 | 0.36 |
April | 0.00 | 1641697.20 | 0.00 | 3866979.39 | 0.00 | 2141345.36 | 0.146804E+09 | 0.00 | 0.35 |
May | 0.00 | 3542062.92 | 1691.96 | 3460209.05 | 0.00 | 44203.00 | 0.102150E+09 | 267.70 | 0.35 |
June | 0.00 | 16312261.42 | 0.00 | 3109368.13 | 0.00 | 0.00 | 33948345.24 | 0.00 | 0.36 |
July | 0.00 | 0.125120E+09 | 0.00 | 637682.71 | 0.00 | 0.00 | 12607202.98 | 0.00 | 0.36 |
August | 0.00 | 0.114799E+09 | 13263.30 | 496793.67 | 0.00 | 0.00 | 8373807.27 | 342.41 | 0.36 |
September | 0.00 | 94266941.50 | 13573.21 | 886487.74 | 0.00 | 4926.93 | 11344688.74 | 271.83 | 0.36 |
October | 1665216.82 | 16267478.06 | 3846.95 | 2637963.53 | 0.00 | 37193584.62 | 0.135448E+09 | 102.24 | 0.36 |
November | 2774892.21 | 2229259.10 | 3298.99 | 2199915.76 | 137948.45 | 90867286.18 | 0.151251E+09 | 197.30 | 0.36 |
December | 7520902.71 | 0.00 | 0.00 | 1318756.49 | 113886.39 | 0.190365E+09 | 0.115643E+09 | 0.00 | 0.35 |
Annual Sum or Average | 32131146.20 | 0.374309E+09 | 35674.41 | 24351636.22 | 251834.83 | 0.712483E+09 | 0.113525E+10 | 1181.47 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 496793.67 | 0.00 | 0.00 | 8373807.27 | 0.00 | 0.35 |
Maximum of Months | 10341989.62 | 0.125120E+09 | 13573.21 | 3866979.39 | 137948.45 | 0.190365E+09 | 0.164347E+09 | 342.41 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44089981.63 | 25576.24 | 4835.17 | 719799.99 | 73178.76 | 0.180119E+09 | 61819014.61 | 145.41 | 0.35 |
February | 38003591.99 | 8719.98 | 0.00 | 354867.96 | 0.00 | 0.203284E+09 | 36014839.99 | 0.00 | 0.36 |
March | 53665225.39 | 18007.85 | 0.00 | 1075076.33 | 0.00 | 0.124315E+09 | 91895105.27 | 0.00 | 0.36 |
April | 25664080.68 | 1632900.53 | 1760.22 | 3092675.80 | 6545.07 | 521530.95 | 0.123516E+09 | 299.03 | 0.35 |
May | 19965460.78 | 3540154.97 | 2492.99 | 2910136.00 | 184.23 | 10245.29 | 82756292.34 | 775.15 | 0.36 |
June | 7985763.36 | 16309054.81 | 0.00 | 2771023.55 | 1295.39 | 0.00 | 26296584.60 | 0.00 | 0.36 |
July | 2664086.77 | 0.123209E+09 | 13325.15 | 539636.60 | 1882633.92 | 0.00 | 10039610.49 | 119.92 | 0.36 |
August | 2121073.47 | 0.110370E+09 | 1641.18 | 360229.83 | 4427265.27 | 0.00 | 6388258.32 | 75.89 | 0.36 |
September | 4029759.74 | 85093475.85 | 21358.61 | 675083.60 | 9154128.85 | 885.40 | 7528941.02 | 776.87 | 0.36 |
October | 40851026.45 | 15274253.47 | 1624.30 | 1467963.94 | 993063.02 | 50137817.69 | 84466846.53 | 580.02 | 0.36 |
November | 48216017.38 | 1867654.22 | 3324.33 | 776173.95 | 499275.97 | 0.129043E+09 | 69028718.30 | 171.55 | 0.36 |
December | 38110296.93 | 0.00 | 0.00 | 342431.22 | 113873.04 | 0.248578E+09 | 27779759.12 | 0.00 | 0.35 |
Annual Sum or Average | 0.325366E+09 | 0.357349E+09 | 50361.96 | 15085098.77 | 17151443.52 | 0.936010E+09 | 0.627530E+09 | 2943.83 | 0.36 |
Minimum of Months | 2121073.47 | 0.00 | 0.00 | 342431.22 | 0.00 | 0.00 | 6388258.32 | 0.00 | 0.35 |
Maximum of Months | 53665225.39 | 0.123209E+09 | 21358.61 | 3092675.80 | 9154128.85 | 0.248578E+09 | 0.123516E+09 | 776.87 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 666526.16 | 0.00 | 23720432.83 | 0.00 | 76982362.39 | 0.174172E+10 | 0.00 | 0.40 |
February | 23200561.76 | 56028.01 | 0.00 | 11209497.87 | 0.00 | 0.305314E+09 | 0.144429E+10 | 0.00 | 0.41 |
March | 17389486.09 | 115704.77 | 0.00 | 15023793.08 | 0.00 | 0.272402E+09 | 0.143611E+10 | 0.00 | 0.40 |
April | 0.00 | 10547066.18 | 0.00 | 19979236.55 | 0.00 | 2295321.84 | 0.959468E+09 | 0.00 | 0.40 |
May | 0.00 | 22755842.53 | 4417.09 | 17509598.35 | 0.00 | 487242.44 | 0.660779E+09 | 8275.64 | 0.40 |
June | 0.00 | 0.104798E+09 | 0.00 | 14215925.47 | 0.00 | 67632.67 | 0.223793E+09 | 0.00 | 0.40 |
July | 0.00 | 0.803177E+09 | 598867.23 | 3065964.96 | 0.00 | 26083.23 | 81999578.71 | 54819.64 | 0.40 |
August | 0.00 | 0.737015E+09 | 534630.78 | 2544596.61 | 0.00 | 64451.31 | 54380033.27 | 62101.56 | 0.40 |
September | 0.00 | 0.605384E+09 | 286739.84 | 5228094.85 | 0.00 | 50060.38 | 73332560.71 | 35479.16 | 0.40 |
October | 0.00 | 0.104487E+09 | 41361.54 | 19117430.14 | 0.00 | 17827959.68 | 0.109983E+10 | 7207.11 | 0.40 |
November | 1845545.15 | 14335980.92 | 7228.14 | 19956455.45 | 886248.34 | 91283664.14 | 0.147436E+10 | 1104.10 | 0.40 |
December | 4798611.88 | 0.00 | 0.00 | 17147820.53 | 731661.87 | 0.382789E+09 | 0.161800E+10 | 0.00 | 0.40 |
Annual Sum or Average | 47234204.87 | 0.240334E+10 | 1473244.62 | 0.168719E+09 | 1617910.21 | 0.114959E+10 | 0.108681E+11 | 168987.21 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2544596.61 | 0.00 | 26083.23 | 54380033.27 | 0.00 | 0.40 |
Maximum of Months | 23200561.76 | 0.803177E+09 | 598867.23 | 23720432.83 | 886248.34 | 0.382789E+09 | 0.174172E+10 | 62101.56 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.416281E+09 | 1016303.99 | 0.00 | 74022596.94 | 0.00 | 0.00 | 0.448315E+11 | 0.00 | 4.69 |
February | 0.434453E+09 | 0.00 | 0.00 | 59079500.46 | 0.00 | 0.00 | 0.459475E+11 | 0.00 | 4.63 |
March | 0.255800E+09 | 10905206.46 | 0.00 | 77213204.47 | 0.00 | 0.00 | 0.425128E+11 | 0.00 | 4.89 |
April | 3793173.67 | 0.594700E+09 | 0.00 | 84850355.04 | 0.00 | 0.00 | 0.229454E+11 | 0.00 | 5.24 |
May | 0.00 | 0.142644E+10 | 0.00 | 77824928.92 | 0.00 | 0.00 | 0.163710E+11 | 0.00 | 5.29 |
June | 0.00 | 0.348261E+10 | 0.00 | 60298612.63 | 0.00 | 0.00 | 0.800924E+10 | 0.00 | 4.63 |
July | 0.00 | 0.695181E+10 | 0.00 | 33417416.10 | 0.00 | 0.00 | 0.357888E+10 | 0.00 | 4.54 |
August | 0.00 | 0.570805E+10 | 0.00 | 39706307.81 | 0.00 | 0.00 | 0.424818E+10 | 0.00 | 4.68 |
September | 0.00 | 0.538078E+10 | 0.00 | 44802573.26 | 0.00 | 0.00 | 0.668178E+10 | 0.00 | 4.95 |
October | 0.124215E+09 | 0.765781E+09 | 0.00 | 78834087.51 | 0.00 | 0.00 | 0.291698E+11 | 0.00 | 5.09 |
November | 0.237231E+09 | 13225979.66 | 0.00 | 73001235.17 | 0.00 | 0.00 | 0.404036E+11 | 0.00 | 4.82 |
December | 0.969405E+09 | 0.00 | 0.00 | 63104431.99 | 0.00 | 0.00 | 0.472259E+11 | 0.00 | 4.49 |
Annual Sum or Average | 0.244118E+10 | 0.243353E+11 | 0.00 | 0.766155E+09 | 0.00 | 0.00 | 0.311925E+12 | 0.00 | 4.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33417416.10 | 0.00 | 0.00 | 0.357888E+10 | 0.00 | 4.49 |
Maximum of Months | 0.969405E+09 | 0.695181E+10 | 0.00 | 84850355.04 | 0.00 | 0.00 | 0.472259E+11 | 0.00 | 5.29 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71570410.23 | 1096559.94 | 0.00 | 87126303.84 | 0.00 | 0.00 | 0.491590E+11 | 0.00 | 5.10 |
February | 52667386.45 | 0.00 | 0.00 | 71294894.47 | 0.00 | 0.00 | 0.507229E+11 | 0.00 | 5.07 |
March | 11526373.41 | 12146751.82 | 0.00 | 90477404.13 | 0.00 | 0.00 | 0.465539E+11 | 0.00 | 5.33 |
April | 0.00 | 0.645617E+09 | 0.00 | 92694355.64 | 0.00 | 0.00 | 0.244287E+11 | 0.00 | 5.61 |
May | 0.00 | 0.153682E+10 | 0.00 | 83058815.95 | 0.00 | 0.00 | 0.172674E+11 | 0.00 | 5.63 |
June | 0.00 | 0.372260E+10 | 0.00 | 63499909.21 | 0.00 | 0.00 | 0.837905E+10 | 0.00 | 4.90 |
July | 0.00 | 0.739895E+10 | 0.00 | 35148909.12 | 0.00 | 0.00 | 0.374753E+10 | 0.00 | 4.80 |
August | 0.00 | 0.609426E+10 | 0.00 | 41822563.06 | 0.00 | 0.00 | 0.445316E+10 | 0.00 | 4.96 |
September | 0.00 | 0.573872E+10 | 0.00 | 47532771.93 | 0.00 | 0.00 | 0.702437E+10 | 0.00 | 5.25 |
October | 1737907.48 | 0.821213E+09 | 0.00 | 88017781.42 | 0.00 | 0.00 | 0.314715E+11 | 0.00 | 5.47 |
November | 26938108.63 | 13910312.50 | 0.00 | 85883955.59 | 0.00 | 0.00 | 0.441558E+11 | 0.00 | 5.23 |
December | 0.265880E+09 | 0.00 | 0.00 | 77117241.25 | 0.00 | 0.00 | 0.524833E+11 | 0.00 | 4.90 |
Annual Sum or Average | 0.430320E+09 | 0.259853E+11 | 0.00 | 0.863675E+09 | 0.00 | 0.00 | 0.339847E+12 | 0.00 | 5.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 35148909.12 | 0.00 | 0.00 | 0.374753E+10 | 0.00 | 4.80 |
Maximum of Months | 0.265880E+09 | 0.739895E+10 | 0.00 | 92694355.64 | 0.00 | 0.00 | 0.524833E+11 | 0.00 | 5.63 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2353576.88 | 2088903.20 | 0.00 | 0.131680E+09 | 0.00 | 0.00 | 0.582167E+11 | 0.00 | 22.59 |
February | 0.00 | 0.00 | 0.00 | 0.106913E+09 | 0.00 | 0.00 | 0.640710E+11 | 0.00 | 22.42 |
March | 0.00 | 21384085.17 | 0.00 | 0.129252E+09 | 0.00 | 0.00 | 0.540984E+11 | 0.00 | 22.87 |
April | 0.00 | 0.107618E+10 | 0.00 | 0.120661E+09 | 0.00 | 0.00 | 0.239627E+11 | 0.00 | 22.37 |
May | 0.00 | 0.246726E+10 | 0.00 | 0.100726E+09 | 0.00 | 0.00 | 0.154478E+11 | 0.00 | 21.84 |
June | 0.00 | 0.571403E+10 | 0.00 | 66503035.54 | 0.00 | 0.00 | 0.692904E+10 | 0.00 | 18.84 |
July | 0.00 | 0.103256E+11 | 0.00 | 35041477.05 | 0.00 | 0.00 | 0.311985E+10 | 0.00 | 18.73 |
August | 0.00 | 0.903821E+10 | 0.00 | 42509771.23 | 0.00 | 0.00 | 0.380890E+10 | 0.00 | 19.41 |
September | 0.00 | 0.795667E+10 | 0.00 | 54296596.17 | 0.00 | 0.00 | 0.634594E+10 | 0.00 | 20.52 |
October | 0.00 | 0.127602E+10 | 0.00 | 0.119418E+09 | 0.00 | 0.00 | 0.347012E+11 | 0.00 | 22.61 |
November | 0.00 | 24913123.04 | 0.00 | 0.126409E+09 | 0.00 | 0.00 | 0.524852E+11 | 0.00 | 22.83 |
December | 0.00 | 0.00 | 0.00 | 0.121704E+09 | 0.00 | 0.00 | 0.667050E+11 | 0.00 | 22.13 |
Annual Sum or Average | 2353576.88 | 0.379023E+11 | 0.00 | 0.115511E+10 | 0.00 | 0.00 | 0.389892E+12 | 0.00 | 21.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 35041477.05 | 0.00 | 0.00 | 0.311985E+10 | 0.00 | 18.73 |
Maximum of Months | 2353576.88 | 0.103256E+11 | 0.00 | 0.131680E+09 | 0.00 | 0.00 | 0.667050E+11 | 0.00 | 22.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133009E+11 | 0.00 | 0.00 | 0.00 | 366712.71 | 0.00 | 0.00 | 0.00 | 1.15 |
February | 0.141117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
March | 0.123233E+11 | 0.00 | 0.00 | 21244.29 | 3738564.28 | 0.00 | 8573932.32 | 0.00 | 1.16 |
April | 0.484629E+10 | 0.183120E+09 | 0.00 | 3578423.14 | 17613506.26 | 0.00 | 0.950133E+09 | 0.00 | 1.14 |
May | 0.250314E+10 | 0.470516E+09 | 0.00 | 5824822.83 | 11522143.91 | 0.00 | 0.140448E+10 | 0.00 | 1.13 |
June | 0.288955E+09 | 0.135184E+10 | 0.00 | 8942914.87 | 417960.22 | 0.00 | 0.154846E+10 | 0.00 | 1.10 |
July | 0.157015E+09 | 0.223371E+10 | 0.00 | 5193310.81 | 37411508.42 | 0.00 | 0.676085E+09 | 0.00 | 1.06 |
August | 0.235833E+09 | 0.190149E+10 | 0.00 | 5209505.58 | 46760649.19 | 0.00 | 0.758608E+09 | 0.00 | 1.09 |
September | 0.572359E+09 | 0.146268E+10 | 0.00 | 5055433.14 | 0.207798E+09 | 0.00 | 0.100908E+10 | 0.00 | 1.11 |
October | 0.721884E+10 | 0.256248E+09 | 0.00 | 2331011.36 | 9929910.11 | 0.00 | 0.745716E+09 | 0.00 | 1.16 |
November | 0.118117E+11 | 111378.98 | 0.00 | 56886.00 | 4649755.16 | 0.00 | 13019562.81 | 0.00 | 1.16 |
December | 0.148847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10769865.15 | 0.00 | 0.00 | 1.14 |
Annual Sum or Average | 0.822547E+11 | 0.785972E+10 | 0.00 | 36213552.03 | 0.340209E+09 | 10769865.15 | 0.711416E+10 | 0.00 | 1.13 |
Minimum of Months | 0.157015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.148847E+11 | 0.223371E+10 | 0.00 | 8942914.87 | 0.207798E+09 | 10769865.15 | 0.154846E+10 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149133E+12 | 0.856437E+10 | 0.100020E+12 | 0.446402E+12 | 0.309631E+12 |
February | 0.186042E+12 | 0.853110E+10 | 0.112424E+12 | 0.444534E+12 | 0.139505E+12 |
March | 0.247774E+12 | 0.806248E+10 | 0.950201E+11 | 0.415678E+12 | 0.283343E+12 |
April | 0.295478E+12 | 0.329716E+10 | 0.326046E+11 | 0.182319E+12 | 0.654652E+12 |
May | 0.301172E+12 | 0.171646E+10 | 0.109345E+11 | 0.982068E+11 | 0.829694E+12 |
June | 0.315506E+12 | -417970120.7 | -0.222433E+11 | -0.148858E+11 | 0.106342E+13 |
July | 0.299639E+12 | -0.313899E+10 | -0.457403E+11 | -0.146593E+12 | 0.117976E+13 |
August | 0.251206E+12 | -0.255626E+10 | -0.370791E+11 | -0.117922E+12 | 0.115208E+13 |
September | 0.211754E+12 | -0.160931E+10 | -0.208594E+11 | -0.677569E+11 | 0.104938E+13 |
October | 0.191272E+12 | 0.448657E+10 | 0.512124E+11 | 0.252229E+12 | 0.597083E+12 |
November | 0.162149E+12 | 0.761416E+10 | 0.916249E+11 | 0.408415E+12 | 0.316857E+12 |
December | 0.117741E+12 | 0.105416E+11 | 0.127967E+12 | 0.558169E+12 | 0.215899E+12 |
Annual Sum or Average | 0.272887E+13 | 0.450914E+11 | 0.495886E+12 | 0.245880E+13 | 0.779130E+13 |
Minimum of Months | 0.117741E+12 | -0.313899E+10 | -0.457403E+11 | -0.146593E+12 | 0.139505E+12 |
Maximum of Months | 0.315506E+12 | 0.105416E+11 | 0.127967E+12 | 0.558169E+12 | 0.117976E+13 |