Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:46:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10531.18 | 928.24 | 928.24 |
Net Site Energy | 10531.18 | 928.24 | 928.24 |
Total Source Energy | 21618.19 | 1905.48 | 1905.48 |
Net Source Energy | 21618.19 | 1905.48 | 1905.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 909.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 876.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 517.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2934.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4897.93 | 5633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 909.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 876.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 517.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 75.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2934.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 909.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 876.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 517.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 75.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 2934.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 137.44 | 338.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 208.13 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.72 | 496.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 137.44 | 338.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 208.13 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.72 | 496.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4897.932 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4897.932 | 100.00 |
Total On-Site and Utility Electric Sources | 4897.932 | 100.00 |
Total Electricity End Uses | 4897.932 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 48.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7325.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-19:10 | 29-MAR-17:00 | - | - | - | - | - | - | - | - | - | - | 19-JAN-21:10 |
Heating | 0.00 | 143432.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116518.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31547.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27713.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2866.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3840.06 | 244962.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1829.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 347724.97 | 492643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 143432.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 116518.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1243.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27713.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2866.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3840.06 | 244962.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1057.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 986.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2775.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1637.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 237.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.40 | 3181.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15511.75 | 6106.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 86.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 244.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 280.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1367.24 | 538.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 86.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 244.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 280.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1367.24 | 538.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.44 | 0.619050 | 0.546000 | 1.33 | 1.00 | 0.500000 | 0.000615 | 0.000060 | 1.33 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.315391 | 0.162048 | 0.546000 | 0.172203 | 0.546000 | 0.500000 | 0.002351 | 0.000024 | 0.172203 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.226854 | 0.260889 | 0.546000 | 0.123862 | 0.695704 | 0.500000 | 0.001460 | 0.000011 | 0.123862 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.183298 | 0.682786 | 0.546000 | 0.100081 | 1.00 | 0.500000 | 0.000558 | 0.000014 | 0.100081 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.106740 | 0.676473 | 0.546000 | 0.058280 | 1.00 | 0.500000 | 0.000563 | 0.000009 | 0.058280 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.018017 | 0.546000 | 1.80 | 0.546000 | 0.500000 | 0.021147 | 0.000094 | 1.80 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.39 | 0.103667 | 0.546000 | 0.757969 | 0.546000 | 0.500000 | 0.003675 | 0.000074 | 0.757969 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.68 | 0.212896 | 0.546000 | 2.56 | 0.567724 | 0.500000 | 0.001790 | 0.000209 | 2.56 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.43 | 0.828058 | 0.546000 | 0.782615 | 1.00 | 0.500000 | 0.000460 | 0.000091 | 0.782615 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.12 | 0.118980 | 0.546000 | 1.16 | 0.546000 | 0.500000 | 0.003202 | 0.000088 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113470 | 0.546000 | 1.22 | 0.546000 | 0.500000 | 0.003358 | 0.000091 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063545 | 0.546000 | 1.22 | 0.546000 | 0.500000 | 0.010784 | 0.000057 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.708550 | 0.443213 | 0.546000 | 0.386869 | 1.00 | 0.500000 | 0.000860 | 0.000055 | 0.386869 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6891.48 | 0.000060 | 143.71 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2688.18 | 0.000024 | 62.67 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1235.18 | 0.000011 | 27.06 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1617.43 | 0.000014 | 37.95 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 998.11 | 0.000009 | 23.68 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10767.14 | 0.000094 | 226.33 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8458.07 | 0.000074 | 187.66 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 23864.09 | 0.000209 | 519.32 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3978.72 | 0.000035 | 113.69 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3978.91 | 0.000035 | 113.70 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 23080.56 | 0.000202 | 659.51 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 23095.49 | 0.000202 | 659.94 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3977.89 | 0.000035 | 113.67 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3978.08 | 0.000035 | 113.67 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10400.73 | 0.000091 | 236.21 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1222.35 | 0.000011 | 34.93 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1221.90 | 0.000011 | 34.91 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5902.84 | 0.000052 | 168.67 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10072.48 | 0.000088 | 217.70 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10435.06 | 0.000091 | 225.29 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6521.51 | 0.000057 | 136.24 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6318.94 | 0.000055 | 148.55 |
VAV WITH REHEAT HEATING COIL | 97628.78 | 0.000854 | 1749.84 |
FLR_3_DOAS HEATING COIL | 9427.25 | 0.000082 | 168.97 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.991879 | 0.000035 | 0.000310 |
ROOM_2_FLR_3 FAN COIL | 0.955322 | 0.000035 | 0.000299 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.18 | 0.000202 | 0.001897 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.81 | 0.000202 | 0.001902 |
ROOM_5_FLR_3 FAN COIL | 0.876946 | 0.000035 | 0.000275 |
ROOM_6_FLR_3 FAN COIL | 0.843836 | 0.000035 | 0.000265 |
ROOM_1_FLR_6 FAN COIL | 0.256743 | 0.000011 | 0.000080 |
ROOM_2_FLR_6 FAN COIL | 0.246731 | 0.000011 | 0.000077 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.21 | 0.000052 | 0.000384 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.991879 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.955322 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.18 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.81 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.876946 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.843836 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.256743 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.246731 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.21 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000310 | 0.991879 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000299 | 0.955322 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008495 | 12.80 | 0.008495 | 0.001897 | 6.18 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008737 | 12.80 | 0.008500 | 0.001902 | 5.81 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000275 | 0.876946 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008580 | 12.80 | 0.008500 | 0.000265 | 0.843836 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.000080 | 0.256743 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000077 | 0.246731 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008633 | 12.80 | 0.008500 | 0.000384 | 1.21 | |
VAV WITH REHEAT COOLING COIL | 28.00 | 6.70 | 0.008888 | 10.94 | 0.008500 | 0.013213 | 21.24 | 461991.35 |
FLR_3_DOAS COOLING COIL | 31.30 | 6.70 | 0.008233 | 11.91 | 0.008233 | 0.001371 | 2.05 | 47946.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 21.36 | 11.66 | 21.24 | 21.24 | 0.300000 | 0.549005 | 21.24 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.24 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.24 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013213 | 0.000036 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000854 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001371 | 0.000347 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000082 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.020072 | 3277.14 | |
HEATSYS1 PUMP | 0.002430 | 731.80 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002430 | 0.291597 |
COOLSYS1 | 0.020072 | 2.41 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 277761.16 | 277761.16 | 0.002430 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.020072 | 2268.88 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.020072 | 701821.33 | 702420.09 | 80.08 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.5713E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3008E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1063 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6946E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2253E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6856E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1081 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2611E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1204 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.7369E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9985E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3898E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3289E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3312E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7943E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0055E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7164E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8561E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3289E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3312E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7943E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0055E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7164E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8561E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 32900.83733 | 32900.83733 | 2.43578 | 2.43578 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 27.50267 | 8.22747E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4259.71279 | 4259.71279 | 0.31539 | 0.31539 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1796.46532 | 1796.46532 | 7.84587E-002 | 7.92179E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3063.85819 | 3063.85819 | 0.22685 | 0.22685 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 29.90567 | 8.23127E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 593.81589 | 593.81589 | 2.59347E-002 | 9.17347E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2476.13456 | 2476.13456 | 0.18330 | 0.18330 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 29.46067 | 8.23057E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1099.29300 | 1099.29300 | 4.80111E-002 | 4.80111E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1441.91371 | 1441.91371 | 0.10674 | 0.10674 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 31.12200 | 8.23321E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 696.36614 | 696.36614 | 3.04135E-002 | 5.77652E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44582.23536 | 44582.23536 | 3.30054 | 3.30054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1438.04755 | 1438.04755 | 6.28052E-002 | 6.28052E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18733.90364 | 18733.90364 | 1.38822 | 1.38822 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4532.77187 | 4532.77187 | 0.19796 | 0.67638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63220.68297 | 63220.68297 | 4.68227 | 4.68227 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 10625.67304 | 10625.67304 | 0.46407 | 1.89399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9942.67585 | 9942.67585 | 0.99188 | 0.99188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3978.77372 | 3978.77372 | 0.17479 | 0.17479 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9576.22434 | 9576.22434 | 0.95532 | 0.95532 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3978.95673 | 3978.95673 | 0.17480 | 0.17480 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 61964.44707 | 61964.44707 | 6.18129 | 6.18129 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 23080.70139 | 23080.70139 | 1.01396 | 1.01396 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 58271.51870 | 58271.51870 | 5.81335 | 5.81335 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 23095.62754 | 23095.62754 | 1.01462 | 1.01462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8790.57060 | 8790.57060 | 0.87695 | 0.87695 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16150 | 8.22694E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3977.94413 | 3977.94413 | 0.17475 | 0.17475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8458.67076 | 8458.67076 | 0.84384 | 0.84384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3978.12712 | 3978.12712 | 0.17476 | 0.17476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19361.37977 | 19361.37977 | 1.43336 | 1.43336 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6347.45406 | 6347.45406 | 0.27722 | 0.47476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2573.61543 | 2573.61543 | 0.25674 | 0.25674 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1222.36123 | 1222.36123 | 5.36988E-002 | 5.36988E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2473.25167 | 2473.25167 | 0.24673 | 0.24673 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1221.91252 | 1221.91252 | 5.36791E-002 | 5.36791E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12082.17579 | 12082.17579 | 1.20535 | 1.20535 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5902.89687 | 5902.89687 | 0.25932 | 0.25932 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28655.74058 | 28655.74058 | 2.12408 | 2.12408 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4065.72533 | 4065.72533 | 0.17757 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30047.80398 | 30047.80398 | 2.22723 | 2.22723 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4136.36393 | 4136.36393 | 0.18065 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30017.68062 | 30017.68062 | 2.22810 | 2.22810 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 263.64858 | 263.64858 | 1.15380E-002 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9570.95087 | 9570.95087 | 0.70855 | 0.70855 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.22583 | 8.23338E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4314.99227 | 4314.99227 | 0.18846 | 0.18846 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 3.80000 | 5.05843E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 383438.95 | 21.24349 | 21.24349 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 109842.69 | 7.17035 | 7.17035 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45064.07 | 16.63334 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 31423.05 | 3.09437 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43578 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61905 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32994 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.15459E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.02897E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32994 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6891.47805 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.02897E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.70989 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31539 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16205 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17220 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35116E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.35174E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17220 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2688.18439 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35174E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.67226 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22685 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26089 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12386 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69570 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46039E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08059E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12386 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1235.17700 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08059E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 27.06147 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18330 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68279 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10008 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.58008E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41500E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10008 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1617.42653 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41500E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.94888 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10674 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67647 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.82799E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.63216E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.73191E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.82799E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 998.11047 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.73191E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 23.68319 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.30054 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.80171E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.80210 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11466E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.41956E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80210 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10767.13959 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.41956E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 226.32613 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38822 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10367 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75797 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67523E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.39949E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75797 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8458.07154 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.39949E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 187.65831 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.68227 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21290 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55652 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56772 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78960E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08773E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55652 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23864.08642 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08773E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.31931 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99188 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99188 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.48076E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.10154E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56858E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.10154E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99188 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3978.72425 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48076E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 113.69134 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95532 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95532 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.48092E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.98930E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57110E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.98930E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95532 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3978.90725 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48092E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 113.69657 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.18129 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.18129 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.01919E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.89652E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69438 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49513E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49513E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.89652E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.18129 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 23080.56157 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01919E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 659.51365 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.81335 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.81335 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.02049E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.90178E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69348 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73697E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.90178E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.81335 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 23095.48763 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02049E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 659.94012 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.87695 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.87695 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.48004E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.74862E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69394 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57718E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.74862E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.87695 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3977.89467 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48004E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 113.66764 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84384 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84384 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.48020E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.64698E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58012E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.64698E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84384 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3978.07766 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48020E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 113.67287 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43336 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.82806 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78261 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.60113E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.09901E-005 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78261 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10400.72635 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.09901E-005 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 236.20748 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25674 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.25674 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06936E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.02325E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56634E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.02325E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25674 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1222.34643 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06936E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 34.92711 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24673 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24673 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06897E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.71563E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56882E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.71563E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24673 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1221.89772 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06897E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 34.91429 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20535 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.20535 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.16406E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.83519E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69366 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63259E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.83519E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20535 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5902.83937 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16406E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.66558 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12408 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11898 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15975 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20222E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.81185E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15975 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10072.48359 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.81185E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 217.70287 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22723 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11347 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21607 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35773E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.12904E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21607 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10435.05569 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.12904E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 225.29422 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22810 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.35448E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21654 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54600 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07841E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.70531E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21654 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6521.51451 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70531E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 136.23864 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70855 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44321 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38687 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.59631E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.52809E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38687 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6318.94145 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.52809E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 148.55474 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66278 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66278 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.36041 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66278 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.24349 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.24349 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.54901 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.24349 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.24349 |
337 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.00330 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94367 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.88799E-003 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 461991.35453 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.32129E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.24349 |
345 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 97628.77975 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.54099E-004 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1749.83537 |
348 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.24349 |
349 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.32129E-002 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.60398E-005 |
351 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.54099E-004 |
352 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
354 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.30000 |
355 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91243 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 47946.24805 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37126E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
362 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 9427.24706 |
363 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24737E-005 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.96790 |
365 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
366 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37126E-003 |
367 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.47266E-004 |
368 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.24737E-005 |
369 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.00720E-002 |
370 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3277.14445 |
371 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.42998E-003 |
372 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.29160 |
373 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.42998E-003 |
374 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 731.80200 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
376 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 277761.15894 |
377 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 277761.16000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.42998E-003 |
379 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.00720E-002 |
380 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.40864 |
381 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.00720E-002 |
382 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2268.87763 |
383 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.00720E-002 |
384 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 701821.32694 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 702420.09000 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 80.07589 |
387 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
389 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
390 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
391 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6927.12 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2700.52 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1241.29 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1624.80 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1002.62 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10822.42 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 8498.81 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 23982.88 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 4285.38 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 4285.58 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 24859.31 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 24875.39 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 4284.49 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 4284.68 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10449.67 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1316.53 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1316.05 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6357.64 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10122.92 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10487.36 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6555.19 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6347.71 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 81929.82 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 7911.32 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 16176.76 | 13934.98 | 2241.79 | 0.86 | 3283.34 | 33.30 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15587.91 | 13423.88 | 2164.03 | 0.86 | 3161.50 | 32.07 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 99538.32 | 86426.76 | 13111.55 | 0.87 | 20670.02 | 209.65 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 97779.73 | 82703.96 | 15075.76 | 0.85 | 19007.94 | 192.79 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14325.30 | 12328.06 | 1997.25 | 0.86 | 2900.30 | 29.42 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13792.00 | 11865.16 | 1926.84 | 0.86 | 2789.96 | 28.30 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4185.52 | 3606.41 | 579.11 | 0.86 | 850.08 | 8.62 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4024.17 | 3466.40 | 557.76 | 0.86 | 816.72 | 8.28 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19895.15 | 17015.80 | 2879.34 | 0.86 | 3969.53 | 40.26 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 528303.41 | 370819.32 | 157484.09 | 0.70 | 82198.15 | 833.70 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51303.12 | 35829.51 | 15473.61 | 0.70 | 7298.17 | 74.02 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.1473318766E-002 | 2.2627522056E-002 | Pass | Pass | 8.5756048688E-003 | 1.8300747314E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8554939660E-002 | 4.3860148424E-002 | Pass | Pass | 4.9161189716E-002 | 6.1588198663E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2226355522E-002 | 3.0193336095E-002 | Pass | Pass | 1.0491274240E-002 | 2.1185072358E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4419138464E-003 | 1.3705596292E-002 | Pass | Pass | 1.4736597941E-002 | 3.0499704310E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7087983212E-003 | 7.0758031671E-003 | Pass | Pass | 1.8861084909E-002 | 2.9275037446E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4792803953E-002 | 0.2285237849 | Pass | Pass | 1.9711002612E-002 | 4.9347702851E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.1312490755E-002 | 7.7777271352E-002 | Pass | Pass | 1.5605166038E-002 | 2.6471392999E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6028239764E-002 | 4.4899788269E-002 | Pass | Pass | 1.0500539243E-002 | 2.0078460452E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4509753399E-002 | 8.5484943576E-002 | Pass | Pass | 0.3932417873 | 1.7198993852 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8438181016E-002 | 7.0223197182E-002 | Pass | Pass | 0.4500040088 | 3.6089537889 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.8633140678E-002 | 6.7258530477E-002 | Pass | Pass | 1.7989164266E-002 | 0.1141286791 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6437114235E-002 | 0.1363734158 | Pass | Pass | 0.3015945245 | 1.6353859159 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6611725610E-002 | 0.1918531035 | Pass | Pass | 0.3960728795 | 2.5011342352 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.9360687391E-002 | 0.1498385086 | Pass | Pass | 0.7200449124 | 3.3946578151 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.7870679276E-003 | 9.2495786515E-003 | Pass | Pass | 2.0059584067E-002 | 3.4796061037E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3923846840E-002 | 7.8941030990E-002 | Pass | Pass | 0.1612880194 | 0.6523765514 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4520401552E-002 | 0.1256178635 | Pass | Pass | 0.1632119995 | 0.7341973328 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.4269383817E-002 | 0.2265049822 | Pass | Pass | 0.3417653281 | 1.1417051581 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3057796440E-002 | 7.3151935839E-002 | Pass | Pass | 1.2690634860E-002 | 3.4248059345E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.2539960680E-002 | 6.2452549843E-002 | Pass | Pass | 1.3778672416E-002 | 3.6796455445E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.2240705893E-002 | 9.9093610827E-002 | Pass | Pass | 2.1177054225E-002 | 3.9150895579E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1721879672E-003 | 1.3122892995E-002 | Pass | Pass | 1.7235694659E-002 | 2.0934266687E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3547.76 | 78.88 | 1069.05 | 4308.03 | 4215.30 | 13219.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.42 | 0.0000 | Y | 14.34 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.67 | 0.0000 | Y | 110.15 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.05 | 0.0000 | Y | 31.19 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.05 | 0.0000 | Y | 31.19 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.75 | 83.75 | 193.98 | |
Exterior Lighting Total | 12338.45 | 193.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 277761.16 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 702420.09 | 2.96 | 702543.56 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10844.81 | 16176.76 | 13934.98 | 2241.79 | 0.86 | - | 3283.34 | 33.30 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10452.34 | 15587.91 | 13423.88 | 2164.03 | 0.86 | - | 3161.50 | 32.07 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66313.28 | 99538.32 | 86426.76 | 13111.55 | 0.87 | - | 20670.02 | 209.65 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66497.40 | 97779.73 | 82703.96 | 15075.76 | 0.85 | - | 19007.94 | 192.79 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9610.80 | 14325.30 | 12328.06 | 1997.25 | 0.86 | - | 2900.30 | 29.42 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9255.37 | 13792.00 | 11865.16 | 1926.84 | 0.86 | - | 2789.96 | 28.30 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2805.40 | 4185.52 | 3606.41 | 579.11 | 0.86 | - | 850.08 | 8.62 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2697.83 | 4024.17 | 3466.40 | 557.76 | 0.86 | - | 816.72 | 8.28 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13410.08 | 19895.15 | 17015.80 | 2879.34 | 0.86 | - | 3969.53 | 40.26 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 461991.35 | 528303.41 | 370819.32 | 157484.09 | 0.70 | - | 82198.15 | 833.70 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 47946.25 | 51303.12 | 35829.51 | 15473.61 | 0.70 | - | 7298.17 | 74.02 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6891.48 | 6927.12 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2688.18 | 2700.52 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1235.18 | 1241.29 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1617.43 | 1624.80 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 998.11 | 1002.62 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10767.14 | 10822.42 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8458.07 | 8498.81 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23864.09 | 23982.88 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3978.72 | 4285.38 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3978.91 | 4285.58 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 23080.56 | 24859.31 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 23095.49 | 24875.39 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3977.89 | 4284.49 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3978.08 | 4284.68 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10400.73 | 10449.67 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1222.35 | 1316.53 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1221.90 | 1316.05 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 5902.84 | 6357.64 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10072.48 | 10122.92 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10435.06 | 10487.36 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6521.51 | 6555.19 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6318.94 | 6347.71 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 97628.78 | 81929.82 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 9427.25 | 7911.32 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 697.92 | 703.64 | 1.00 | 1.20 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 672.20 | 703.64 | 1.00 | 1.21 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.18 | 4349.38 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.81 | 4090.49 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.88 | 617.05 | 703.64 | 1.00 | 1.23 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 593.75 | 703.64 | 1.00 | 1.24 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 180.65 | 703.64 | 1.00 | 1.83 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 173.61 | 703.64 | 1.00 | 1.86 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 848.13 | 703.64 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.24 | 47598.98 | 2240.64 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.020072 | 3277.14 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002430 | 731.80 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.020072 | 2268.88 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 32900.84 | 32900.84 | 16.63 | 2.436 | 2.436 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00923 | 27.50 | 0.00823 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4259.71 | 4259.71 | 63.51 | 0.315 | 0.315 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00905 | 30.93 | 0.00823 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3063.86 | 3063.86 | 39.45 | 0.227 | 0.227 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00941 | 29.91 | 0.00823 | 0.092 | 0.00 |
MECH_FLR_1 | 2476.13 | 2476.13 | 15.08 | 0.183 | 0.183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 24.00 | 24.00 | 0.00872 | 29.46 | 0.00823 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1441.91 | 1441.91 | 15.22 | 0.107 | 0.107 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00880 | 31.12 | 0.00823 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44582.24 | 44582.24 | 571.28 | 3.301 | 3.301 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 31.30 | 0.00823 | 0.000 | 0.00 |
CAFE_FLR_1 | 18733.90 | 18733.90 | 99.19 | 1.388 | 1.388 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 23.99 | 0.01019 | 30.93 | 0.00823 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63220.68 | 63220.68 | 48.33 | 4.682 | 4.682 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00999 | 31.08 | 0.00823 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9942.68 | 9942.68 | 254.80 | 0.992 | 0.992 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9576.22 | 9576.22 | 245.43 | 0.955 | 0.955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00823 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 61964.45 | 61964.45 | 2526.70 | 6.181 | 6.181 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 31.08 | 0.00823 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 58271.52 | 58271.52 | 2375.47 | 5.813 | 5.813 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 21.11 | 21.11 | 0.00874 | 31.30 | 0.00823 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8790.57 | 8790.57 | 225.27 | 0.877 | 0.877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 21.11 | 21.11 | 0.00858 | 27.16 | 0.00823 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8458.67 | 8458.67 | 216.79 | 0.844 | 0.844 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00858 | 26.66 | 0.00823 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19361.38 | 19361.38 | 49.72 | 1.433 | 1.433 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00946 | 31.30 | 0.00823 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2573.62 | 2573.62 | 65.95 | 0.257 | 0.257 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2473.25 | 2473.25 | 63.39 | 0.247 | 0.247 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12082.18 | 12082.18 | 492.54 | 1.205 | 1.205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00863 | 31.08 | 0.00823 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28655.74 | 28655.74 | 86.40 | 2.124 | 2.124 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.98 | 0.01046 | 31.30 | 0.00823 | 1.188 | 0.00 |
DINING_FLR_6 | 30047.80 | 30047.80 | 90.60 | 2.227 | 2.227 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.01037 | 31.30 | 0.00823 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30017.68 | 30017.68 | 290.57 | 2.228 | 2.228 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01011 | 30.50 | 0.00823 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9570.95 | 9570.95 | 23.22 | 0.709 | 0.709 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00901 | 31.23 | 0.00823 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 21.60 | 0.00506 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1796.47 | 1796.47 | 26.78 | 0.078 | 0.079 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 593.82 | 593.82 | 7.65 | 0.026 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00761 | 3.80 | 0.00506 | 0.092 | 0.00 |
MECH_FLR_1 | 1099.29 | 1099.29 | 6.69 | 0.048 | 0.048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00752 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 696.37 | 696.37 | 7.35 | 0.030 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1438.05 | 1438.05 | 18.43 | 0.063 | 0.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 4532.77 | 4532.77 | 24.00 | 0.198 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 10625.67 | 10625.67 | 8.12 | 0.464 | 1.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00764 | 3.80 | 0.00506 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3978.77 | 3978.77 | 101.96 | 0.175 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3978.96 | 3978.96 | 101.98 | 0.175 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 23080.70 | 23080.70 | 941.15 | 1.014 | 1.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23095.63 | 23095.63 | 941.50 | 1.015 | 1.015 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3977.94 | 3977.94 | 101.94 | 0.175 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3978.13 | 3978.13 | 101.96 | 0.175 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6347.45 | 6347.45 | 16.30 | 0.277 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00772 | 3.80 | 0.00506 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1222.36 | 1222.36 | 31.32 | 0.054 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00771 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1221.91 | 1221.91 | 31.32 | 0.054 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00771 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5902.90 | 5902.90 | 240.63 | 0.259 | 0.259 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4065.73 | 4065.73 | 12.26 | 0.178 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 1.188 | 0.00 |
DINING_FLR_6 | 4136.36 | 4136.36 | 12.47 | 0.181 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 263.65 | 263.65 | 2.55 | 0.012 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00428 | 3.80 | 0.00506 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4314.99 | 4314.99 | 10.47 | 0.188 | 0.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00781 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.24 | 21.24 | 7.17 | 7.17 | 21.2435 | 11.6628 | 21.2435 | 0.5490 | 0.3000 |
FLR_3_DOAS | 16.63 | 2.05 | 3.09 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6891.478 | 6891.478 | 1.329935 | 0.00006029 | 143.710 | 12/21 00:10:00 | 12/21 00:10:00 | 6891.48 | 6891.48 | 1.329935 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6930.21 | 6930.21 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2688.184 | 2688.184 | 0.172203 | 0.00002352 | 62.672 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2688.18 | 2688.18 | 0.172203 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00765885 | 48.6185 | 1796.47 | 0.00 | 2702.54 | 2702.54 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1235.177 | 1235.177 | 0.123862 | 0.00001081 | 27.061 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1235.18 | 1235.18 | 0.123862 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00760900 | 48.3054 | 593.82 | 0.00 | 1242.01 | 1242.01 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1617.427 | 1617.427 | 0.100081 | 0.00001415 | 37.949 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1617.43 | 1617.43 | 0.100081 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00751844 | 47.7373 | 1099.29 | 0.00 | 1626.05 | 1626.05 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 998.110 | 998.110 | 0.058280 | 0.00000873 | 23.683 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 998.11 | 998.11 | 0.058280 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755496 | 47.9665 | 696.37 | 0.00 | 1003.41 | 1003.41 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10767.140 | 10767.140 | 1.802096 | 0.00009420 | 226.326 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10767.14 | 10767.14 | 1.802096 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00750125 | 47.6300 | 1438.05 | 0.00 | 10827.48 | 10827.48 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8458.072 | 8458.072 | 0.757969 | 0.00007399 | 187.658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8458.07 | 8458.07 | 0.757969 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00769676 | 48.8560 | 4532.77 | 0.00 | 8504.04 | 8504.04 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 23864.086 | 23864.086 | 2.556518 | 0.00020877 | 519.319 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23864.09 | 23864.09 | 2.556518 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00763837 | 48.4896 | 10625.67 | 0.00 | 23996.38 | 23996.38 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10844.811 | -999.000 | 0.991879 | 0.00031015 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 10844.81 | 10669.27 | 0.991879 | 21.69 | 15.43 | 0.00856858 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00856858 | 53.9461 | 9942.68 | 0.00 | 11051.87 | 11051.87 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3978.724 | 3978.724 | 0.174789 | 0.00003481 | 113.691 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3978.72 | 3978.72 | 0.174789 | 21.11 | 14.39 | 0.00764621 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764621 | 48.2095 | 3978.77 | 0.00 | 4289.19 | 4289.19 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10452.339 | -999.000 | 0.955322 | 0.00029893 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 10452.34 | 10277.04 | 0.955322 | 21.69 | 15.43 | 0.00857110 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00857110 | 53.9618 | 9576.22 | 0.00 | 10651.79 | 10651.79 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3978.907 | 3978.907 | 0.174797 | 0.00003481 | 113.697 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3978.91 | 3978.91 | 0.174797 | 21.11 | 14.39 | 0.00764625 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764625 | 48.2097 | 3978.96 | 0.00 | 4289.38 | 4289.38 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 66313.280 | -999.000 | 6.181294 | 0.00189652 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 66313.28 | 66313.28 | 6.181294 | 21.69 | 15.37 | 0.00849513 | 12.80 | 11.93 | 0.00849513 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00849513 | 53.4887 | 61964.45 | 0.00 | 67590.85 | 67590.85 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 23080.562 | 23080.562 | 1.013960 | 0.00020192 | 659.514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23080.56 | 23080.56 | 1.013960 | 21.11 | 14.41 | 0.00767330 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00767330 | 48.3777 | 23080.70 | 0.00 | 24881.62 | 24881.62 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 66497.400 | -999.000 | 5.813354 | 0.00190178 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | 8/21 14:50:00 | 66497.40 | 62920.34 | 5.813354 | 21.69 | 15.58 | 0.00873697 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 0.0000 | 21.11 | 0.00873697 | 54.9925 | 58271.52 | 0.00 | 67741.91 | 66620.84 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 23095.488 | 23095.488 | 1.014615 | 0.00020205 | 659.940 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23095.49 | 23095.49 | 1.014615 | 21.11 | 14.41 | 0.00767341 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00767341 | 48.3784 | 23095.63 | 0.00 | 24897.71 | 24897.71 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9610.796 | -999.000 | 0.876946 | 0.00027486 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | 8/21 09:30:00 | 9610.80 | 9436.09 | 0.876946 | 21.69 | 15.44 | 0.00857718 | 12.80 | 11.93 | 0.00850000 | 27.16 | 0.00822694 | 17.07 | 0.0000 | 21.11 | 0.00857718 | 53.9995 | 8790.57 | 0.00 | 9793.93 | 9793.93 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3977.895 | 3977.895 | 0.174753 | 0.00003480 | 113.668 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3977.89 | 3977.89 | 0.174753 | 21.11 | 14.39 | 0.00764615 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764615 | 48.2091 | 3977.94 | 0.00 | 4288.29 | 4288.29 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9255.372 | -999.000 | 0.843836 | 0.00026470 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 9255.37 | 9080.84 | 0.843836 | 21.69 | 15.44 | 0.00858012 | 12.80 | 11.93 | 0.00850000 | 26.66 | 0.00822614 | 16.89 | 0.0000 | 21.11 | 0.00858012 | 54.0178 | 8458.67 | 0.00 | 9431.62 | 9431.62 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3978.078 | 3978.078 | 0.174761 | 0.00003480 | 113.673 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3978.08 | 3978.08 | 0.174761 | 21.11 | 14.39 | 0.00764618 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00764618 | 48.2093 | 3978.13 | 0.00 | 4288.49 | 4288.49 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 10400.726 | 10400.726 | 0.782615 | 0.00009099 | 236.207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10400.73 | 10400.73 | 0.782615 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00772224 | 49.0153 | 6347.45 | 0.00 | 10456.76 | 10456.76 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2805.397 | -999.000 | 0.256743 | 0.00008023 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 2805.40 | 2761.45 | 0.256743 | 21.69 | 15.43 | 0.00856634 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00856634 | 53.9322 | 2573.62 | 0.00 | 2858.99 | 2858.99 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1222.346 | 1222.346 | 0.053699 | 0.00001069 | 34.927 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1222.35 | 1222.35 | 0.053699 | 21.11 | 14.44 | 0.00770546 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00770546 | 48.5784 | 1222.36 | 0.00 | 1317.73 | 1317.73 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2697.835 | -999.000 | 0.246731 | 0.00007716 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 2697.83 | 2654.02 | 0.246731 | 21.69 | 15.43 | 0.00856882 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00856882 | 53.9476 | 2473.25 | 0.00 | 2749.34 | 2749.34 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1221.898 | 1221.898 | 0.053679 | 0.00001069 | 34.914 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1221.90 | 1221.90 | 0.053679 | 21.11 | 14.44 | 0.00770538 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00770538 | 48.5780 | 1221.91 | 0.00 | 1317.24 | 1317.24 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13410.078 | -999.000 | 1.205348 | 0.00038352 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 13410.08 | 12996.66 | 1.205348 | 21.69 | 15.49 | 0.00863259 | 12.80 | 11.93 | 0.00850000 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00863259 | 54.3443 | 12082.18 | 0.00 | 13664.58 | 13664.58 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5902.839 | 5902.839 | 0.259318 | 0.00005164 | 168.666 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5902.84 | 5902.84 | 0.259318 | 21.11 | 14.45 | 0.00771783 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00771783 | 48.6553 | 5902.90 | 0.00 | 6363.45 | 6363.45 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10072.484 | 10072.484 | 1.159747 | 0.00008812 | 217.703 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 10072.48 | 10072.48 | 1.159747 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777664 | 49.3571 | 4065.73 | 0.00 | 10128.43 | 10128.43 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10435.056 | 10435.056 | 1.216067 | 0.00009129 | 225.294 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 10435.06 | 10435.06 | 1.216067 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778001 | 49.3778 | 4136.36 | 0.00 | 10493.03 | 10493.03 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6521.515 | 6521.515 | 1.216543 | 0.00005705 | 136.239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 6521.51 | 6521.51 | 1.216543 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00428366 | 27.3427 | 263.65 | 0.00 | 6558.14 | 6558.14 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 6318.941 | 6318.941 | 0.386869 | 0.00005528 | 148.555 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 6318.94 | 6318.94 | 0.386869 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781301 | 49.5845 | 4314.99 | 0.00 | 6352.61 | 6352.61 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 461991.355 | -999.000 | 21.243487 | 0.01321289 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 461991.35 | 436600.99 | 21.243487 | 28.00 | 17.89 | 0.00888799 | 10.94 | 10.94 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 54.8943 | 23.99 | 0.00964798 | 50.9004 | 286686.20 | 0.00 | 468409.55 | 426555.95 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 97628.780 | 97628.780 | 6.373046 | 0.00085410 | 1749.835 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 97628.78 | 97628.78 | 6.373046 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 182.9809 | 21.13 | 0.00701701 | 44.2362 | 39665.19 | 0.00 | 99173.17 | 99173.17 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 47946.25 | 47946.25 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 11.91 | 11.29 | 0.00823349 | 31.30 | 0.00823349 | 18.45 | 99.9965 | 21.11 | 0.00861347 | 54.2247 | 166734.10 | 0.00 | 48578.76 | 48578.76 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9427.25 | 9427.25 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 333.3216 | 21.11 | 0.00767355 | 48.3793 | 70437.30 | 0.00 | 9576.38 | 9576.38 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6891.478 | 6891.478 | 1.329935 | 0.00006029 | 143.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 2.4321 | 2.481081 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6891.48 | 6891.48 | 1.0000 | 1.57168881 | 1.329935 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06028351 | 60.00 | 32.22 | 27.78 | 0.000 | 6891.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6930.21 | 6930.21 | 1.57168881 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2688.184 | 2688.184 | 0.172203 | 0.00002352 | 62.672 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.9487 | 0.967804 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2688.18 | 2688.18 | 1.0000 | 0.20350609 | 0.172203 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02351501 | 60.00 | 32.22 | 27.78 | 0.000 | 2688.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00765885 | 21.00 | 0.00765885 | 48.6185 | 1796.47 | 0.00 | 2702.54 | 2702.54 | 0.20350609 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.62 | 17.91 | 0.00800000 | 50214.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1235.177 | 1235.177 | 0.123862 | 0.00001081 | 27.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.4359 | 0.444690 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1235.18 | 1235.18 | 1.0000 | 0.14637774 | 0.123862 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01080476 | 60.00 | 32.22 | 27.78 | 0.000 | 1235.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00760900 | 21.00 | 0.00760900 | 48.3054 | 593.82 | 0.00 | 1242.01 | 1242.01 | 0.14637774 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.92 | 16.29 | 0.00800000 | 45419.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1617.427 | 1617.427 | 0.100081 | 0.00001415 | 37.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.5708 | 0.582308 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1617.43 | 1617.43 | 1.0000 | 0.11827328 | 0.100081 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01414851 | 60.00 | 32.22 | 27.78 | 0.000 | 1617.43 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00751844 | 21.00 | 0.00751844 | 47.7373 | 1099.29 | 0.00 | 1626.05 | 1626.05 | 0.11827328 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.08 | 18.07 | 0.00800000 | 50683.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 998.110 | 998.110 | 0.058280 | 0.00000873 | 23.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.3523 | 0.359341 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 998.11 | 998.11 | 1.0000 | 0.06887398 | 0.058280 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00873102 | 60.00 | 32.22 | 27.78 | 0.000 | 998.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00755496 | 21.00 | 0.00755496 | 47.9665 | 696.37 | 0.00 | 1003.41 | 1003.41 | 0.06887398 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.89 | 18.33 | 0.00800000 | 51503.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10767.140 | 10767.140 | 1.802096 | 0.00009420 | 226.326 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 3.7999 | 3.876402 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10767.14 | 10767.14 | 1.0000 | 2.12967847 | 1.802096 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09418603 | 60.00 | 32.22 | 27.78 | 0.000 | 10767.14 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00750125 | 21.00 | 0.00750125 | 47.6300 | 1438.05 | 0.00 | 10827.48 | 10827.48 | 2.12967847 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.59 | 15.07 | 0.00800000 | 42018.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8458.072 | 8458.072 | 0.757969 | 0.00007399 | 187.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 2.9850 | 3.045088 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8458.07 | 8458.07 | 1.0000 | 0.89575101 | 0.757969 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07398735 | 60.00 | 32.22 | 27.78 | 0.000 | 8458.07 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00769676 | 21.00 | 0.00769676 | 48.8560 | 4532.77 | 0.00 | 8504.04 | 8504.04 | 0.89575101 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.91 | 16.64 | 0.00800000 | 46428.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23864.086 | 23864.086 | 2.556518 | 0.00020877 | 519.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 8.4221 | 8.591585 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23864.09 | 23864.09 | 1.0000 | 3.02123890 | 2.556518 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.20875214 | 60.00 | 32.22 | 27.78 | 0.000 | 23864.09 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00763837 | 21.00 | 0.00763837 | 48.4896 | 10625.67 | 0.00 | 23996.38 | 23996.38 | 3.02123890 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.39 | 16.10 | 0.00800000 | 44877.3 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10844.811 | -999.000 | 0.991879 | 0.00031015 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7686 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.991879 | 1.17218184 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 1.5452 | 1.545209 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 10844.81 | 10669.27 | 1.0000 | 1.17218184 | 0.991879 | 21.69 | 15.43 | 0.00856858 | 43574.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.31012280 | 6.70 | 15.03 | 8.33 | 0.000 | 10844.81 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00856858 | 21.11 | 0.00856858 | 53.9461 | 9942.68 | 0.00 | 11051.87 | 11051.87 | 1.17218184 | 21.69 | 15.62 | 0.00856858 | 43574.0 | 12.46 | 12.03 | 0.00856858 | 34145.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3978.724 | 3978.724 | 0.174789 | 0.00003481 | 113.691 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.991879 | 1.17218184 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 1.4042 | 1.432426 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3978.72 | 3978.72 | 1.0000 | 0.20656203 | 0.174789 | 21.11 | 14.39 | 0.00764621 | 40635.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03480406 | 60.00 | 32.22 | 27.78 | 0.000 | 3978.72 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764621 | 21.11 | 0.00764621 | 48.2095 | 3978.77 | 0.00 | 4289.19 | 4289.19 | 0.20656203 | 16.60 | 12.81 | 0.00764621 | 36039.0 | 36.98 | 20.00 | 0.00764621 | 56803.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10452.339 | -999.000 | 0.955322 | 0.00029893 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7733 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.955322 | 1.12897973 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 1.4893 | 1.489288 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 10452.34 | 10277.04 | 1.0000 | 1.12897973 | 0.955322 | 21.69 | 15.43 | 0.00857110 | 43580.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.29889949 | 6.70 | 15.03 | 8.33 | 0.000 | 10452.34 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00857110 | 21.11 | 0.00857110 | 53.9618 | 9576.22 | 0.00 | 10651.79 | 10651.79 | 1.12897973 | 21.69 | 15.62 | 0.00857110 | 43580.4 | 12.45 | 12.03 | 0.00857110 | 34145.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3978.907 | 3978.907 | 0.174797 | 0.00003481 | 113.697 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.955322 | 1.12897973 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 1.4042 | 1.432492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3978.91 | 3978.91 | 1.0000 | 0.20657153 | 0.174797 | 21.11 | 14.39 | 0.00764625 | 40635.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03480567 | 60.00 | 32.22 | 27.78 | 0.000 | 3978.91 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764625 | 21.11 | 0.00764625 | 48.2097 | 3978.96 | 0.00 | 4289.38 | 4289.38 | 0.20657153 | 16.60 | 12.81 | 0.00764625 | 36039.1 | 36.98 | 20.01 | 0.00764625 | 56803.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66313.280 | -999.000 | 6.181294 | 0.00189652 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6320 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.181294 | 7.30492137 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 9.4487 | 9.448565 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 66313.28 | 66313.28 | 1.0000 | 7.30492137 | 6.181294 | 21.69 | 15.37 | 0.00849513 | 43387.8 | 12.80 | 11.93 | 0.00849513 | 34309.9 | 1.89632252 | 6.70 | 15.03 | 8.33 | 0.000 | 66313.28 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00849513 | 21.11 | 0.00849513 | 53.4887 | 61964.45 | 0.00 | 67590.85 | 67590.85 | 7.30492137 | 21.69 | 15.55 | 0.00849513 | 43387.8 | 12.63 | 12.02 | 0.00849513 | 34135.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23080.562 | 23080.562 | 1.013960 | 0.00020192 | 659.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.181294 | 7.30492137 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 8.1456 | 8.309499 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23080.56 | 23080.56 | 1.0000 | 1.19827590 | 1.013960 | 21.11 | 14.41 | 0.00767330 | 40704.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.20189822 | 60.00 | 32.22 | 27.78 | 0.000 | 23080.56 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00767330 | 21.11 | 0.00767330 | 48.3777 | 23080.70 | 0.00 | 24881.62 | 24881.62 | 1.19827590 | 16.60 | 12.83 | 0.00767330 | 36107.6 | 36.98 | 20.03 | 0.00767330 | 56872.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66497.400 | -999.000 | 5.813354 | 0.00190178 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0816 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.813354 | 6.87009830 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 9.4750 | 9.474799 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | unknown | unknown | 8/21 14:50:00 | Sensible | 66497.40 | 62920.34 | 1.0000 | 6.87009830 | 5.813354 | 21.69 | 15.58 | 0.00873697 | 44001.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 1.90158771 | 6.70 | 15.03 | 8.33 | 0.000 | 66497.40 | 31.30 | 0.00823349 | 18.45 | 0.00000000 | 0.0000 | 21.11 | 0.00873697 | 21.11 | 0.00873697 | 54.9925 | 58271.52 | 0.00 | 67741.91 | 66620.84 | 6.87009830 | 21.69 | 15.77 | 0.00873697 | 44001.4 | 12.20 | 12.02 | 0.00867231 | 34141.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23095.488 | 23095.488 | 1.014615 | 0.00020205 | 659.940 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.813354 | 6.87009830 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 8.1508 | 8.314873 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23095.49 | 23095.49 | 1.0000 | 1.19905082 | 1.014615 | 21.11 | 14.41 | 0.00767341 | 40704.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.20202879 | 60.00 | 32.22 | 27.78 | 0.000 | 23095.49 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00767341 | 21.11 | 0.00767341 | 48.3784 | 23095.63 | 0.00 | 24897.71 | 24897.71 | 1.19905082 | 16.60 | 12.83 | 0.00767341 | 36107.9 | 36.98 | 20.03 | 0.00767341 | 56872.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9610.796 | -999.000 | 0.876946 | 0.00027486 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7845 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.876946 | 1.03635586 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 1.3694 | 1.369382 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | unknown | unknown | 8/21 09:30:00 | Sensible | 9610.80 | 9436.09 | 1.0000 | 1.03635586 | 0.876946 | 21.69 | 15.44 | 0.00857718 | 43595.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.27483439 | 6.70 | 15.03 | 8.33 | 0.000 | 9610.80 | 27.16 | 0.00822694 | 17.07 | 0.00000000 | 0.0000 | 21.11 | 0.00857718 | 21.11 | 0.00857718 | 53.9995 | 8790.57 | 0.00 | 9793.93 | 9793.93 | 1.03635586 | 21.69 | 15.63 | 0.00857718 | 43595.8 | 12.44 | 12.03 | 0.00857718 | 34145.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3977.895 | 3977.895 | 0.174753 | 0.00003480 | 113.668 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.876946 | 1.03635586 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 1.4039 | 1.432128 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3977.89 | 3977.89 | 1.0000 | 0.20651896 | 0.174753 | 21.11 | 14.39 | 0.00764615 | 40635.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03479681 | 60.00 | 32.22 | 27.78 | 0.000 | 3977.89 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764615 | 21.11 | 0.00764615 | 48.2091 | 3977.94 | 0.00 | 4288.29 | 4288.29 | 0.20651896 | 16.60 | 12.81 | 0.00764615 | 36038.8 | 36.98 | 20.00 | 0.00764615 | 56803.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9255.372 | -999.000 | 0.843836 | 0.00026470 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7900 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.843836 | 0.99722700 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 1.3188 | 1.318740 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 9255.37 | 9080.84 | 1.0000 | 0.99722700 | 0.843836 | 21.69 | 15.44 | 0.00858012 | 43603.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.26467051 | 6.70 | 15.03 | 8.33 | 0.000 | 9255.37 | 26.66 | 0.00822614 | 16.89 | 0.00000000 | 0.0000 | 21.11 | 0.00858012 | 21.11 | 0.00858012 | 54.0178 | 8458.67 | 0.00 | 9431.62 | 9431.62 | 0.99722700 | 21.69 | 15.63 | 0.00858012 | 43603.3 | 12.43 | 12.03 | 0.00858012 | 34145.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3978.078 | 3978.078 | 0.174761 | 0.00003480 | 113.673 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.843836 | 0.99722700 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 1.4039 | 1.432194 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3978.08 | 3978.08 | 1.0000 | 0.20652846 | 0.174761 | 21.11 | 14.39 | 0.00764618 | 40635.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03479841 | 60.00 | 32.22 | 27.78 | 0.000 | 3978.08 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00764618 | 21.11 | 0.00764618 | 48.2093 | 3978.13 | 0.00 | 4288.49 | 4288.49 | 0.20652846 | 16.60 | 12.81 | 0.00764618 | 36038.9 | 36.98 | 20.00 | 0.00764618 | 56803.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10400.726 | 10400.726 | 0.782615 | 0.00009099 | 236.207 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 3.6706 | 3.744486 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10400.73 | 10400.73 | 1.0000 | 0.92487727 | 0.782615 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09098081 | 60.00 | 32.22 | 27.78 | 0.000 | 10400.73 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00772224 | 21.00 | 0.00772224 | 49.0153 | 6347.45 | 0.00 | 10456.76 | 10456.76 | 0.92487727 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.69 | 17.25 | 0.00800000 | 48240.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2805.397 | -999.000 | 0.256743 | 0.00008023 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7644 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.256743 | 0.30341373 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 0.3997 | 0.399723 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 2805.40 | 2761.45 | 1.0000 | 0.30341373 | 0.256743 | 21.69 | 15.43 | 0.00856634 | 43568.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.08022431 | 6.70 | 15.03 | 8.33 | 0.000 | 2805.40 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00856634 | 21.11 | 0.00856634 | 53.9322 | 2573.62 | 0.00 | 2858.99 | 2858.99 | 0.30341373 | 21.69 | 15.62 | 0.00856634 | 43568.3 | 12.46 | 12.03 | 0.00856634 | 34145.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1222.346 | 1222.346 | 0.053699 | 0.00001069 | 34.927 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.256743 | 0.30341373 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.4314 | 0.440071 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1222.35 | 1222.35 | 1.0000 | 0.06346012 | 0.053699 | 21.11 | 14.44 | 0.00770546 | 40786.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01069253 | 60.00 | 32.22 | 27.78 | 0.000 | 1222.35 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00770546 | 21.11 | 0.00770546 | 48.5784 | 1222.36 | 0.00 | 1317.73 | 1317.73 | 0.06346012 | 16.60 | 12.86 | 0.00770546 | 36189.0 | 36.97 | 20.05 | 0.00770546 | 56953.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2697.835 | -999.000 | 0.246731 | 0.00007716 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7690 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246731 | 0.29158160 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 0.3844 | 0.384398 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 2697.83 | 2654.02 | 1.0000 | 0.29158160 | 0.246731 | 21.69 | 15.43 | 0.00856882 | 43574.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.07714841 | 6.70 | 15.03 | 8.33 | 0.000 | 2697.83 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00856882 | 21.11 | 0.00856882 | 53.9476 | 2473.25 | 0.00 | 2749.34 | 2749.34 | 0.29158160 | 21.69 | 15.62 | 0.00856882 | 43574.6 | 12.46 | 12.03 | 0.00856882 | 34145.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1221.898 | 1221.898 | 0.053679 | 0.00001069 | 34.914 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246731 | 0.29158160 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 0.4312 | 0.439909 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1221.90 | 1221.90 | 1.0000 | 0.06343683 | 0.053679 | 21.11 | 14.44 | 0.00770538 | 40785.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01068860 | 60.00 | 32.22 | 27.78 | 0.000 | 1221.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00770538 | 21.11 | 0.00770538 | 48.5780 | 1221.91 | 0.00 | 1317.24 | 1317.24 | 0.06343683 | 16.60 | 12.86 | 0.00770538 | 36188.8 | 36.97 | 20.05 | 0.00770538 | 56953.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13410.078 | -999.000 | 1.205348 | 0.00038352 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8876 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.205348 | 1.42445405 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 1.9108 | 1.910718 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 13410.08 | 12996.66 | 1.0000 | 1.42445405 | 1.205348 | 21.69 | 15.49 | 0.00863259 | 43736.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.38348025 | 6.70 | 15.03 | 8.33 | 0.000 | 13410.08 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00863259 | 21.11 | 0.00863259 | 54.3443 | 12082.18 | 0.00 | 13664.58 | 13664.58 | 1.42445405 | 21.69 | 15.68 | 0.00863259 | 43736.4 | 12.30 | 12.02 | 0.00863259 | 34143.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5902.839 | 5902.839 | 0.259318 | 0.00005164 | 168.666 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.205348 | 1.42445405 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 2.0832 | 2.125149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5902.84 | 5902.84 | 1.0000 | 0.30645652 | 0.259318 | 21.11 | 14.45 | 0.00771783 | 40817.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05163535 | 60.00 | 32.22 | 27.78 | 0.000 | 5902.84 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00771783 | 21.11 | 0.00771783 | 48.6553 | 5902.90 | 0.00 | 6363.45 | 6363.45 | 0.30645652 | 16.60 | 12.88 | 0.00771783 | 36220.3 | 36.97 | 20.06 | 0.00771783 | 56984.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10072.484 | 10072.484 | 1.159747 | 0.00008812 | 217.703 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 3.5548 | 3.626311 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | Sensible | 10072.48 | 10072.48 | 1.0000 | 1.37056440 | 1.159747 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08810949 | 60.00 | 32.22 | 27.78 | 0.000 | 10072.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00777664 | 21.00 | 0.00777664 | 49.3571 | 4065.73 | 0.00 | 10128.43 | 10128.43 | 1.37056440 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.85 | 15.90 | 0.00800000 | 44324.7 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10435.056 | 10435.056 | 1.216067 | 0.00009129 | 225.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 3.6827 | 3.756845 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | Sensible | 10435.06 | 10435.06 | 1.0000 | 1.43712248 | 1.216067 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09128111 | 60.00 | 32.22 | 27.78 | 0.000 | 10435.06 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00778001 | 21.00 | 0.00778001 | 49.3778 | 4136.36 | 0.00 | 10493.03 | 10493.03 | 1.43712248 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.76 | 15.87 | 0.00800000 | 44236.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6521.515 | 6521.515 | 1.216543 | 0.00005705 | 136.239 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 2.3016 | 2.347886 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 6521.51 | 6521.51 | 1.0000 | 1.43768443 | 1.216543 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05704723 | 60.00 | 32.22 | 27.78 | 0.000 | 6521.51 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 14.62 | 0.00428366 | 21.00 | 0.00428366 | 27.3427 | 263.65 | 0.00 | 6558.14 | 6558.14 | 1.43768443 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.07 | 14.88 | 0.00800000 | 41496.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6318.941 | 6318.941 | 0.386869 | 0.00005528 | 148.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 2.2301 | 2.274955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | Sensible | 6318.94 | 6318.94 | 1.0000 | 0.45719295 | 0.386869 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05527522 | 60.00 | 32.22 | 27.78 | 0.000 | 6318.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00781301 | 21.00 | 0.00781301 | 49.5845 | 4314.99 | 0.00 | 6352.61 | 6352.61 | 0.45719295 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.23 | 18.11 | 0.00800000 | 50829.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 461991.355 | -999.000 | 21.243487 | 0.01321289 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3623 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.243487 | 25.10509950 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 65.8275 | 65.827489 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 461991.35 | 436600.99 | 1.0000 | 25.10509950 | 21.243487 | 28.00 | 17.89 | 0.00888799 | 50829.8 | 10.94 | 10.94 | 0.00850000 | 32427.5 | 13.21154641 | 6.70 | 15.03 | 8.33 | 47598.977 | 414392.38 | 31.30 | 0.00823349 | 18.45 | 11.66146000 | 54.8943 | 23.99 | 0.00968496 | 23.99 | 0.00964798 | 50.9004 | 286686.20 | 0.00 | 468409.55 | 426555.95 | 25.10509950 | 28.00 | 18.09 | 0.00888799 | 50829.8 | 11.37 | 11.22 | 0.00822697 | 32171.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 97628.780 | 97628.780 | 6.373046 | 0.00085410 | 1749.835 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.243487 | 25.10509950 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 34.4550 | 35.148464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | Sensible | 97628.78 | 97628.78 | 1.0000 | 7.53152985 | 6.373046 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.85401203 | 60.00 | 32.22 | 27.78 | 0.000 | 97628.78 | 3.80 | 0.00505843 | 3.80 | 11.66146000 | 182.9809 | 17.93 | 0.00720618 | 21.13 | 0.00701701 | 44.2362 | 39665.19 | 0.00 | 99173.17 | 99173.17 | 7.53152985 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1456 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 20.06995356 | 15.03 | 6.70 | 8.33 | 701821.33 | 6.8317 | 6.831689 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 47946.25 | 47946.25 | 1.0000 | 2.42420295 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 52522.0 | 11.91 | 11.29 | 0.00823349 | 32743.9 | 1.37111674 | 6.70 | 15.03 | 8.33 | 2195.006 | 45751.24 | 31.30 | 0.00823349 | 18.45 | 2.05124512 | 99.9965 | 21.11 | 0.00860890 | 21.11 | 0.00861347 | 54.2247 | 166734.10 | 0.00 | 48578.76 | 48578.76 | 2.42420295 | 31.30 | 18.65 | 0.00823349 | 52522.0 | 11.66 | 11.35 | 0.00823349 | 32483.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 2.42972791 | 54.44 | 82.22 | 27.78 | 283351.21 | 3.3271 | 3.394012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9427.25 | 9427.25 | 1.0000 | 0.72726088 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.08246526 | 60.00 | 32.22 | 27.78 | 0.000 | 9427.25 | 3.80 | 0.00505843 | 3.80 | 2.05124512 | 333.3216 | 21.11 | 0.00767206 | 21.11 | 0.00767355 | 48.3793 | 70437.30 | 0.00 | 9576.38 | 9576.38 | 0.72726088 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.24 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 71.67 | 8080.50 | 0.00 |
RETAIL_1_FLR_1 | 802.83 | 7372.67 | 20.17 |
RETAIL_2_FLR_1 | 1054.33 | 6959.00 | 288.00 |
MECH_FLR_1 | 0.00 | 8655.00 | 0.00 |
STORAGE_FLR_1 | 2.67 | 8758.83 | 2.67 |
LAUNDRY_FLR_1 | 7479.33 | 3484.83 | 2883.83 |
CAFE_FLR_1 | 3184.17 | 5250.67 | 1151.83 |
LOBBY_FLR_1 | 2128.83 | 5819.33 | 894.67 |
ROOM_1_FLR_3 | 64.83 | 8284.17 | 64.17 |
ROOM_2_FLR_3 | 879.17 | 7779.50 | 331.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 122.33 | 8722.00 | 119.33 |
ROOM_5_FLR_3 | 67.17 | 8588.00 | 67.17 |
ROOM_6_FLR_3 | 539.33 | 8247.67 | 324.67 |
CORRIDOR_FLR_3 | 167.00 | 8758.83 | 167.00 |
ROOM_1_FLR_6 | 235.00 | 8128.67 | 227.50 |
ROOM_2_FLR_6 | 1273.00 | 7674.67 | 708.83 |
ROOM_3_MULT9_FLR_6 | 33.17 | 8147.00 | 25.17 |
BANQUET_FLR_6 | 6150.83 | 1908.83 | 905.17 |
DINING_FLR_6 | 7061.33 | 1154.00 | 796.17 |
KITCHEN_FLR_6 | 8444.33 | 6543.67 | 6399.83 |
CORRIDOR_FLR_6 | 20.83 | 8514.33 | 10.50 |
Facility | 8680.67 | 8760.00 | 7325.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_2_FLR_3 | 0.00 | 3.33 | 0.00 | 3.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 15.83 | 0.00 | 15.83 |
ROOM_5_FLR_3 | 0.00 | 1.50 | 0.00 | 1.50 |
ROOM_6_FLR_3 | 0.00 | 25.17 | 0.00 | 25.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 4.67 | 0.00 | 4.67 |
ROOM_2_FLR_6 | 0.00 | 10.00 | 0.00 | 10.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 6.33 | 0.00 | 6.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 48.50 | 0.00 | 48.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.012 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.417 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.483 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.563 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.568 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.126 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.790 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.831 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.175 | 0.000 | 0.093 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.096 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.404 | 0.078 | 0.000 | 0.157 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.356 | 0.175 | 0.000 | 0.093 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.101 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.603 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.356 | 0.176 | 0.000 | 0.104 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.098 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.404 | 0.143 | 0.000 | 0.166 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.892 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 5.282 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.274 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.127 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.984 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.302 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.438 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.548 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.552 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.767 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.610 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.763 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.586 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.116 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.321 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.842 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.095 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.081 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41938435.29 | 0.00 | 41938435.29 | 0.00 | 41938435.29 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5531822.85 | 0.00 | 5531822.85 | 310101.36 | 5841924.21 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3917739.26 | 0.00 | 3917739.26 | 119699.52 | 4037438.77 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3151643.20 | 0.00 | 3151643.20 | 282898.54 | 3434541.74 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1835293.78 | 0.00 | 1835293.78 | 163216.88 | 1998510.66 | 1821682.01 | 56.75 | 8703.25 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 64088592.63 | 0.00 | 64088592.63 | 386283.51 | 64474876.14 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 24301170.16 | 0.00 | 24301170.16 | 685496.60 | 24986666.77 | 14544917.54 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 81312468.54 | 0.00 | 81312468.54 | 1958620.37 | 83271088.91 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 95190.16 | 1555346.87 | 179991.83 | 1735338.70 | 1946875.62 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 97603.78 | 1557589.42 | 179978.09 | 1737567.51 | 1946647.51 | 2190.00 | 5421.77 | 1148.23 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 215.88 | 1100127.85 | 50219.74 | 1150347.59 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 367.33 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 100545.10 | 19904374.39 | 50233.47 | 19954607.86 | 26405105.73 | 2190.00 | 5360.35 | 1209.65 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 95371.78 | 1555528.49 | 179991.83 | 1735520.32 | 1946875.62 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 102991.18 | 1562976.82 | 179978.09 | 1742954.91 | 1946647.51 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
CORRIDOR_FLR_3 | 24645322.15 | 0.00 | 24645322.15 | 217646.33 | 24862968.49 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 107072.90 | 472112.08 | 180028.86 | 652140.94 | 486718.90 | 1889.35 | 5356.86 | 1513.79 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 100182.79 | 465179.20 | 180015.12 | 645194.32 | 486661.88 | 1943.54 | 5502.91 | 1313.55 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 106931.97 | 2452122.28 | 92109.06 | 2544231.34 | 3126920.42 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
BANQUET_FLR_6 | 42245116.05 | 0.00 | 42245116.05 | 439585.22 | 42684701.28 | 37458366.31 | 3794.16 | 272.22 | 4693.62 | 0.00 |
DINING_FLR_6 | 45608475.60 | 0.00 | 45608475.60 | 439585.22 | 46048060.83 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 59952052.24 | 0.00 | 59952052.24 | 393530.69 | 60345582.93 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12184334.80 | 0.00 | 12184334.80 | 385165.88 | 12569500.68 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 10392105.24 | 0.21E+10 | 18137997.94 | 0.21E+10 | 0.43E+10 | 8760.00 | 8757.00 | 8760.00 | 367.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3299 | 0.0000 | 1.3299 | 0.0000 | 1.3299 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1754 | 0.0000 | 0.1754 | 0.0098 | 0.1852 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1242 | 0.0000 | 0.1242 | 0.0038 | 0.1280 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0999 | 0.0000 | 0.0999 | 0.0090 | 0.1089 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0582 | 0.0000 | 0.0582 | 0.0052 | 0.0634 | 0.0578 | 56.75 | 8703.25 | 0.00 |
LAUNDRY_FLR_1 | 2.0322 | 0.0000 | 2.0322 | 0.0122 | 2.0445 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7706 | 0.0000 | 0.7706 | 0.0217 | 0.7923 | 0.4612 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.5784 | 0.0000 | 2.5784 | 0.0621 | 2.6405 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0030 | 0.0493 | 0.0057 | 0.0550 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0031 | 0.0494 | 0.0057 | 0.0551 | 0.0617 | 2190.00 | 5421.77 | 1148.23 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0032 | 0.6312 | 0.0016 | 0.6328 | 0.8373 | 2190.00 | 5360.35 | 1209.65 |
ROOM_5_FLR_3 | 0.0463 | 0.0030 | 0.0493 | 0.0057 | 0.0550 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0033 | 0.0496 | 0.0057 | 0.0553 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
CORRIDOR_FLR_3 | 0.7815 | 0.0000 | 0.7815 | 0.0069 | 0.7884 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0034 | 0.0150 | 0.0057 | 0.0207 | 0.0154 | 1889.35 | 5356.86 | 1513.79 |
ROOM_2_FLR_6 | 0.0116 | 0.0032 | 0.0148 | 0.0057 | 0.0205 | 0.0154 | 1943.54 | 5502.91 | 1313.55 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0034 | 0.0778 | 0.0029 | 0.0807 | 0.0992 | 2190.00 | 5347.50 | 1222.50 |
BANQUET_FLR_6 | 1.3396 | 0.0000 | 1.3396 | 0.0139 | 1.3535 | 1.1878 | 3794.16 | 272.22 | 4693.62 |
DINING_FLR_6 | 1.4462 | 0.0000 | 1.4462 | 0.0139 | 1.4602 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.9011 | 0.0000 | 1.9011 | 0.0125 | 1.9135 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3864 | 0.0000 | 0.3864 | 0.0122 | 0.3986 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.5274 | 0.3290 | 64.8565 | 0.4541 | 65.3106 | 73.7518 | 8760.00 | 8757.00 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 41645591.30 | 806105.54 | 42451696.84 | 64690340.46 | 8758.83 | 1.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.1888 | 0.0000 | 18.1888 | 6.7817 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3206 | 0.0256 | 1.3461 | 2.0513 | 8758.83 | 1.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 7636.92 | 0.00 | 0.00 | 0.00 | 1123.08 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.2764 | 0.0000 | 0.0000 | 0.0000 | 17.6090 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6681 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1329 |
Defaulted Fields | 1180 |
Fields with Defaults | 3961 |
Autosized Fields | 347 |
Autosizable Fields | 400 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
Electricity:Building | 2448.58 | 31319.00 | 03-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.49 | 31177.85 | 03-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.68 | 367.70 | 13-MAY-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.34 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.34 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.15 | 3142.86 | 03-JUN-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.15 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.15 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.05 | 2514.90 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.05 | 2514.90 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.31 | 1114.62 | 03-FEB-23:30 | 3263.24 | 14-JUL-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1097.54 | 2870.52 | 07-FEB-03:50 | 170659.36 | 16-OCT-11:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.47 | 0.00 | 01-JAN-11:10 | 1892.43 | 30-SEP-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.75 | 928.61 | 07-JAN-02:40 | 1203.34 | 11-FEB-14:10 |
Fans:Electricity | 517.02 | 12117.39 | 30-MAR-07:10 | 34359.01 | 16-OCT-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 538.79 | 12762.72 | 29-JAN-02:30 | 35192.53 | 16-OCT-22:00 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 18-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.01 | 27-MAY-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
ElectricityPurchased:Plant | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
Cogeneration:ElectricityPurchased | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
General:Cogeneration:ElectricityPurchased | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
ElectricityNet:Plant | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
Cogeneration:ElectricityNet | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
General:Cogeneration:ElectricityNet | 4897.93 | 68863.97 | 27-MAY-04:50 | 347724.97 | 29-SEP-19:10 |
General:Fans:Electricity | 517.02 | 12117.39 | 30-MAR-07:10 | 34359.01 | 16-OCT-22:00 |
ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
WaterSystems:Electricity | 90.75 | 1086.57 | 09-SEP-00:10 | 4738.73 | 23-JAN-19:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.57 | 09-SEP-00:10 | 4738.73 | 23-JAN-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 876.52 | 0.00 | 01-JAN-00:40 | 163331.85 | 16-OCT-11:10 |
General:Cooling:Electricity | 876.52 | 0.00 | 01-JAN-00:40 | 163331.85 | 16-OCT-11:10 |
Pumps:Electricity | 75.06 | 61.87 | 26-MAR-10:20 | 4278.15 | 29-SEP-15:20 |
General:Pumps:Electricity | 75.06 | 61.87 | 26-MAR-10:20 | 4278.15 | 29-SEP-15:20 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5633.25 | 29270.80 | 26-APR-01:10 | 492643.28 | 29-MAR-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3844.41 | 15908.90 | 04-JAN-11:10 | 398267.53 | 05-JAN-21:10 |
WaterSystems:NaturalGas | 2934.53 | 15908.90 | 03-JAN-16:10 | 246302.21 | 13-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2934.53 | 15908.90 | 03-JAN-16:10 | 246302.21 | 13-FEB-21:20 |
Heating:NaturalGas | 909.88 | 0.00 | 02-JAN-11:10 | 200468.55 | 08-JAN-07:00 |
Boiler:Heating:NaturalGas | 909.88 | 0.00 | 02-JAN-11:10 | 200468.55 | 08-JAN-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2747.06 | 0.00 | 01-JAN-00:10 | 505100.14 | 17-AUG-15:20 |
PlantLoopCoolingDemand:HVAC | 2747.06 | 0.00 | 01-JAN-00:10 | 505100.14 | 17-AUG-15:20 |
CoolingCoils:PlantLoopCoolingDemand | 2747.06 | 0.00 | 01-JAN-00:10 | 505100.14 | 17-AUG-15:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 16207.91 | 127277.56 | 27-MAR-13:40 | 1931265.94 | 17-AUG-15:20 |
EnergyTransfer:Building | 5027.92 | 92384.39 | 29-MAR-12:00 | 299606.01 | 16-OCT-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 730.71 | 11776.38 | 07-JAN-03:00 | 35343.72 | 30-SEP-10:50 |
Refrigeration:EnergyTransfer | 185.59 | 3946.22 | 07-JAN-02:40 | 10369.20 | 14-JUL-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.80 | 1973.11 | 07-JAN-02:40 | 5184.60 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer | 92.80 | 1973.11 | 07-JAN-02:40 | 5184.60 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.80 | 1973.11 | 07-JAN-02:40 | 5184.60 | 14-JUL-06:20 |
EnergyTransfer:Plant | 7848.39 | 20186.23 | 27-MAR-13:40 | 1163814.64 | 17-AUG-15:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.13 | 1735.82 | 07-JAN-02:40 | 2560.03 | 11-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 395.94 | 9930.69 | 31-MAR-14:00 | 22039.30 | 08-JAN-07:00 |
Heating:EnergyTransfer | 9.69 | 0.00 | 01-JAN-08:10 | 15090.16 | 28-MAR-08:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.69 | 0.00 | 01-JAN-08:10 | 15090.16 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4925.43 | 89648.28 | 29-MAR-12:00 | 296060.46 | 16-OCT-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 395.94 | 9930.69 | 31-MAR-14:00 | 22039.30 | 08-JAN-07:00 |
General:Cooling:EnergyTransfer | 4925.43 | 89648.28 | 29-MAR-12:00 | 296060.46 | 16-OCT-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 395.94 | 9930.69 | 31-MAR-14:00 | 22039.30 | 08-JAN-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.64 | 3.27 | 30-MAR-05:00 | 4079.22 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 94.09 | 30-MAR-06:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 94.09 | 30-MAR-06:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.64 | 0.00 | 30-MAR-05:10 | 4079.22 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.64 | 0.00 | 30-MAR-05:10 | 4079.22 | 16-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.94 | 753.86 | 29-MAR-12:10 | 1976.92 | 16-OCT-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.94 | 753.86 | 29-MAR-12:10 | 1976.92 | 16-OCT-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.94 | 753.86 | 29-MAR-12:10 | 1976.92 | 16-OCT-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.24 | 277.34 | 30-MAR-04:00 | 1250.40 | 27-JAN-05:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.24 | 277.34 | 30-MAR-04:00 | 1250.40 | 27-JAN-05:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.24 | 277.34 | 30-MAR-04:00 | 1250.40 | 27-JAN-05:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.34 | 82.73 | 30-MAR-04:00 | 721.29 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.34 | 82.73 | 30-MAR-04:00 | 721.29 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.34 | 82.73 | 30-MAR-04:00 | 721.29 | 30-SEP-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.08 | 9934.31 | 09-JAN-05:00 | 38405.20 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.08 | 9934.31 | 09-JAN-05:00 | 38405.20 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.08 | 9934.31 | 09-JAN-05:00 | 38405.20 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 233.40 | 2261.56 | 29-MAR-12:10 | 14032.50 | 19-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 233.40 | 2261.56 | 29-MAR-12:10 | 14032.50 | 19-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 233.40 | 2261.56 | 29-MAR-12:10 | 14032.50 | 19-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 793.22 | 16243.17 | 29-MAR-12:10 | 38613.24 | 16-OCT-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 793.22 | 16243.17 | 29-MAR-12:10 | 38613.24 | 16-OCT-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 793.22 | 16243.17 | 29-MAR-12:10 | 38613.24 | 16-OCT-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.22 | 0.00 | 01-JAN-08:10 | 9885.90 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.07 | 0.00 | 01-JAN-08:10 | 1948.02 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.07 | 0.00 | 01-JAN-08:10 | 1948.02 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.16 | 0.00 | 01-JAN-00:10 | 9885.90 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.16 | 0.00 | 01-JAN-00:10 | 9885.90 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 32.05 | 0.00 | 01-JAN-08:10 | 9344.71 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.95 | 0.00 | 01-JAN-08:10 | 2079.64 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.95 | 0.00 | 01-JAN-08:10 | 2079.64 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.10 | 0.00 | 01-JAN-00:10 | 9344.71 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.10 | 0.00 | 01-JAN-00:10 | 9344.71 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.45 | 0.00 | 01-JAN-00:10 | 49429.39 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.45 | 0.00 | 01-JAN-00:10 | 49429.39 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.45 | 0.00 | 01-JAN-00:10 | 49429.39 | 16-OCT-12:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 348.25 | 0.00 | 01-JAN-08:10 | 61767.31 | 04-OCT-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.74 | 0.00 | 01-JAN-00:10 | 7332.26 | 25-MAR-15:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.74 | 0.00 | 01-JAN-00:10 | 7332.26 | 25-MAR-15:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 347.51 | 0.00 | 01-JAN-08:10 | 61767.31 | 04-OCT-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 347.51 | 0.00 | 01-JAN-08:10 | 61767.31 | 04-OCT-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 47.60 | 0.00 | 01-JAN-08:10 | 9529.54 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.18 | 0.00 | 01-JAN-07:20 | 2070.27 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.18 | 0.00 | 01-JAN-07:20 | 2070.27 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 46.42 | 0.00 | 01-JAN-00:10 | 9529.54 | 15-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 46.42 | 0.00 | 01-JAN-00:10 | 9529.54 | 15-OCT-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.82 | 0.00 | 01-JAN-08:10 | 9881.74 | 17-OCT-08:40 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.14 | 0.00 | 01-JAN-07:20 | 2155.58 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.14 | 0.00 | 01-JAN-07:20 | 2155.58 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.68 | 0.00 | 01-JAN-00:10 | 9881.74 | 17-OCT-08:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.68 | 0.00 | 01-JAN-00:10 | 9881.74 | 17-OCT-08:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.09 | 2291.75 | 29-MAR-12:00 | 10328.99 | 28-JAN-07:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.09 | 2291.75 | 29-MAR-12:00 | 10328.99 | 28-JAN-07:00 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 209.09 | 2291.75 | 29-MAR-12:00 | 10328.99 | 28-JAN-07:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.53 | 0.00 | 01-JAN-08:10 | 2619.31 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.75 | 0.00 | 01-JAN-08:10 | 663.71 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.75 | 0.00 | 01-JAN-08:10 | 663.71 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.78 | 0.00 | 01-JAN-00:10 | 2619.31 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.78 | 0.00 | 01-JAN-00:10 | 2619.31 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.31 | 0.00 | 01-JAN-08:10 | 2472.94 | 17-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.22 | 0.00 | 01-JAN-08:10 | 719.92 | 03-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.22 | 0.00 | 01-JAN-08:10 | 719.92 | 03-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.09 | 0.00 | 01-JAN-00:10 | 2472.94 | 17-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.09 | 0.00 | 01-JAN-00:10 | 2472.94 | 17-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.76 | 0.00 | 01-JAN-08:10 | 13591.57 | 30-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.64 | 0.00 | 01-JAN-07:10 | 2586.37 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.64 | 0.00 | 01-JAN-07:10 | 2586.37 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.12 | 0.00 | 01-JAN-00:10 | 13591.57 | 30-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.12 | 0.00 | 01-JAN-00:10 | 13591.57 | 30-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 443.34 | 9348.50 | 29-MAR-11:40 | 21457.64 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 443.34 | 9348.50 | 29-MAR-11:40 | 21457.64 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 443.34 | 9348.50 | 29-MAR-11:40 | 21457.64 | 29-SEP-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 483.38 | 10366.48 | 29-MAR-11:40 | 22822.13 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 483.38 | 10366.48 | 29-MAR-11:40 | 22822.13 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 483.38 | 10366.48 | 29-MAR-11:40 | 22822.13 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 637.92 | 9719.58 | 07-JAN-03:10 | 30327.92 | 30-SEP-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 637.92 | 9719.58 | 07-JAN-03:10 | 30327.92 | 30-SEP-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.60 | 472.53 | 30-MAR-06:10 | 5237.17 | 30-SEP-13:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.60 | 472.53 | 30-MAR-06:10 | 5237.17 | 30-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.60 | 472.53 | 30-MAR-06:10 | 5237.17 | 30-SEP-13:40 |
PlantLoopHeatingDemand:Facility | 1266.48 | 8695.71 | 03-AUG-02:10 | 185069.71 | 08-JAN-07:00 |
PlantLoopHeatingDemand:Plant | 681.94 | 8695.71 | 03-AUG-02:10 | 47495.28 | 30-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 681.94 | 8695.71 | 03-AUG-02:10 | 47495.28 | 30-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 681.94 | 8695.71 | 03-AUG-02:10 | 47495.28 | 30-JAN-07:10 |
EnergyTransfer:HVAC | 3331.60 | 359.12 | 16-MAY-07:30 | 505100.14 | 17-AUG-15:20 |
HeatingCoils:EnergyTransfer | 584.54 | 0.00 | 02-JAN-11:10 | 158806.62 | 08-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 584.54 | 0.00 | 02-JAN-11:10 | 158806.62 | 08-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 584.54 | 0.00 | 02-JAN-11:10 | 158806.62 | 08-JAN-07:00 |
CoolingCoils:EnergyTransfer | 2747.06 | 0.00 | 01-JAN-00:10 | 505100.14 | 17-AUG-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 681.94 | 8695.71 | 03-AUG-02:10 | 47495.28 | 30-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 681.94 | 8695.71 | 03-AUG-02:10 | 47495.28 | 30-JAN-07:10 |
Boilers:EnergyTransfer | 580.72 | 0.00 | 02-JAN-11:10 | 157985.91 | 08-JAN-07:00 |
Chillers:EnergyTransfer | 2808.21 | 0.00 | 01-JAN-00:40 | 506806.24 | 17-AUG-15:20 |
HeatRejection:EnergyTransfer | 3684.73 | 0.00 | 01-JAN-00:40 | 640697.21 | 18-AUG-15:10 |
General:HeatRejection:EnergyTransfer | 3684.73 | 0.00 | 01-JAN-00:40 | 640697.21 | 18-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -395.940 | 0.000 | 0.000 | 142.388 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -50.847 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -44.642 | 0.000 | 0.000 | 15.441 | 7.307 | 10.186 | 21.164 | 0.000 | 0.046 | 1.039 | 0.000 | -8.211 | 0.000 | -2.331 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.935 | 0.000 | 0.000 | 16.720 | 8.462 | 11.795 | 0.000 | 0.000 | 0.020 | 0.964 | 0.000 | 0.000 | 0.000 | -1.026 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -27.242 | 0.000 | 0.000 | 3.684 | 8.366 | 12.471 | 0.000 | 0.000 | 0.053 | 4.892 | 0.000 | 0.000 | 0.000 | -2.225 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -15.339 | 0.000 | 0.000 | 2.869 | 3.079 | 3.598 | 0.000 | 0.000 | 0.032 | 7.007 | 0.000 | 0.000 | 0.000 | -1.246 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -605.083 | 0.000 | 0.000 | 11.373 | 3.975 | 658.131 | 0.000 | 0.000 | 0.081 | 0.000 | 0.000 | 0.000 | 0.000 | -3.288 | -65.190 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -233.397 | 0.000 | 0.000 | 188.239 | 14.344 | 14.341 | 58.455 | 0.000 | 0.101 | 0.000 | 0.000 | -25.598 | 0.000 | -5.972 | -10.512 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -793.222 | 0.000 | 0.000 | 552.522 | 110.149 | 148.998 | 77.660 | 0.000 | 0.316 | 0.000 | 0.000 | -34.259 | 0.000 | -17.391 | -44.773 |
ROOM_1_FLR_3 | 2.669 | -40.326 | 0.000 | -11.432 | 0.000 | 0.000 | 9.656 | 9.244 | 10.478 | 43.625 | 0.000 | 0.181 | 1.619 | 0.000 | -18.970 | 0.000 | -6.744 | -0.001 |
ROOM_2_FLR_3 | 4.230 | -20.086 | 0.000 | -12.289 | 0.000 | 0.000 | 9.451 | 9.243 | 10.477 | 30.963 | 0.000 | 0.139 | 0.000 | 0.000 | -19.696 | 0.000 | -7.851 | -4.581 |
ROOM_3_MULT19_FLR_3 | 0.000 | -277.809 | 0.000 | -16.639 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 221.970 | 0.000 | 0.141 | 0.003 | 0.000 | -161.475 | 0.000 | -49.341 | -22.229 |
ROOM_4_MULT19_FLR_3 | 7.486 | -193.153 | 0.000 | -161.091 | 0.000 | 0.000 | 181.729 | 110.415 | 195.050 | 66.280 | 0.000 | 0.975 | 0.001 | 0.000 | -104.267 | 0.000 | -67.094 | -36.330 |
ROOM_5_FLR_3 | 2.899 | -36.703 | 0.000 | -11.434 | 0.000 | 0.000 | 9.650 | 9.244 | 10.478 | 40.503 | 0.000 | 0.180 | 0.463 | 0.000 | -18.509 | 0.000 | -6.773 | -0.001 |
ROOM_6_FLR_3 | 4.504 | -18.926 | 0.000 | -12.111 | 0.000 | 0.000 | 9.513 | 9.243 | 10.477 | 27.673 | 0.000 | 0.134 | 0.000 | 0.000 | -18.736 | 0.000 | -7.662 | -4.108 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -209.095 | 0.000 | 0.000 | 117.590 | 91.336 | 0.000 | 36.730 | 0.000 | 0.166 | 0.000 | 0.000 | -23.173 | 0.000 | -6.737 | -6.818 |
ROOM_1_FLR_6 | 1.405 | -9.577 | 0.000 | -2.859 | 0.000 | 0.000 | 2.416 | 2.311 | 2.620 | 10.767 | 0.000 | 0.045 | 0.000 | 0.000 | -4.683 | 0.000 | -1.738 | -0.706 |
ROOM_2_FLR_6 | 2.034 | -4.821 | 0.000 | -3.083 | 0.000 | 0.000 | 2.360 | 2.311 | 2.619 | 7.616 | 0.000 | 0.034 | 0.000 | 0.000 | -4.881 | 0.000 | -1.989 | -2.200 |
ROOM_3_MULT9_FLR_6 | 2.221 | -64.307 | 0.000 | -18.385 | 0.000 | 0.000 | 21.711 | 13.076 | 23.098 | 54.625 | 0.000 | 0.256 | 0.001 | 0.000 | -21.925 | 0.000 | -9.995 | -0.373 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -443.344 | 0.000 | 0.000 | 316.388 | 31.195 | 175.857 | 6.154 | 0.000 | 0.046 | 0.000 | 0.000 | -14.204 | 0.000 | -4.257 | -67.836 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -483.380 | 0.000 | 0.000 | 315.309 | 31.195 | 175.857 | 5.831 | 0.000 | 0.043 | 0.000 | 0.000 | -14.672 | 0.000 | -4.305 | -25.879 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -637.902 | 0.000 | 0.000 | 28.439 | 12.972 | 550.372 | 18.655 | 0.000 | 0.036 | 41.462 | 0.000 | -10.213 | 0.000 | -3.820 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -102.598 | 0.000 | 0.000 | 31.218 | 24.166 | 0.000 | 17.767 | 0.000 | 0.055 | 42.871 | 0.000 | -10.479 | 0.000 | -3.000 | 0.000 |
Total Facility | 27.448 | -665.709 | 0.000 | -4277.443 | 0.000 | 0.000 | 1988.666 | 783.315 | 2365.005 | 746.438 | 0.000 | 3.080 | 100.324 | 0.000 | -513.950 | 0.000 | -214.784 | -342.384 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | -22035.96 | 0.00 | 0.00 | 5812.89 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 7770.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 | -4079.25 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4751.44 | 0.00 | 129.44 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1370.82 |
RETAIL_2_FLR_1 | 16-OCT-20:10 | 0.00 | 0.00 | 0.00 | -1976.49 | 0.00 | 0.00 | 697.63 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15.74 | -72.67 |
MECH_FLR_1 | 27-JAN-04:55 | 0.00 | 0.00 | 0.00 | -1252.39 | 0.00 | 0.00 | 193.53 | 76.02 | 176.73 | 0.00 | 0.00 | 0.00 | 1002.52 | 0.00 | -0.00 | 0.00 | -196.41 | 0.00 |
STORAGE_FLR_1 | 30-SEP-10:33 | 0.00 | 0.00 | 0.00 | -723.21 | 0.00 | 0.00 | 44.95 | 69.95 | 89.22 | 0.00 | 0.00 | 44.00 | 475.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -38405.17 | 0.00 | 0.00 | 408.77 | 325.08 | 44299.38 | 0.00 | 0.00 | 14.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6642.25 |
CAFE_FLR_1 | 19-NOV-11:00 | 0.00 | 0.00 | 0.00 | -14037.80 | 0.00 | 0.00 | 4947.82 | 124.78 | 406.43 | 13664.85 | 0.00 | 50.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5156.74 |
LOBBY_FLR_1 | 16-OCT-21:10 | 0.00 | 0.00 | 0.00 | -38604.09 | 0.00 | 0.00 | 26440.88 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 440.06 | 0.00 | -1583.45 | 0.00 | -419.88 | 0.00 |
ROOM_1_FLR_3 | 13-OCT-15:01 | 0.00 | -12729.91 | 0.00 | -730.09 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 6735.28 | 0.00 | 131.26 | 5958.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-OCT-08:61 | 0.00 | -12682.43 | 0.00 | -769.83 | 0.00 | 0.00 | 125.32 | 398.41 | 653.15 | 1227.26 | 0.00 | 116.75 | 10931.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:20 | 0.00 | -49429.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 55564.12 | 0.00 | 1181.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12047.71 |
ROOM_4_MULT19_FLR_3 | 14-OCT-08:61 | 0.00 | -79686.64 | 0.00 | -10589.20 | 0.00 | 0.00 | 2407.29 | 4759.18 | 12159.85 | 6684.47 | 0.00 | 595.96 | 63669.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-OCT-08:61 | 0.00 | -11455.20 | 0.00 | -742.93 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 7039.77 | 0.00 | 126.34 | 3849.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-OCT-08:21 | 0.00 | -12727.49 | 0.00 | -925.56 | 0.00 | 0.00 | 71.66 | 313.04 | 452.99 | 6545.40 | 0.00 | 57.06 | 6212.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 28-JAN-07:00 | 0.00 | 0.00 | 0.00 | -10327.21 | 0.00 | 0.00 | 4837.41 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.32 | 0.00 | -1830.49 | 0.00 | -630.79 | 0.00 |
ROOM_1_FLR_6 | 13-OCT-15:01 | 0.00 | -3298.57 | 0.00 | -182.77 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 1665.62 | 0.00 | 32.34 | 1624.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 14-OCT-08:61 | 0.00 | -3189.10 | 0.00 | -184.85 | 0.00 | 0.00 | 32.18 | 99.60 | 163.29 | 317.29 | 0.00 | 31.52 | 2730.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 26-OCT-15:01 | 0.00 | -15717.96 | 0.00 | -1186.01 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 4854.94 | 0.00 | 0.00 | 10862.42 | 0.00 | -0.00 | 0.00 | -65.87 | 0.00 |
BANQUET_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -21457.93 | 0.00 | 0.00 | 15644.26 | 1992.02 | 6747.90 | 0.00 | 0.00 | 7.86 | 0.00 | 0.00 | -214.88 | 0.00 | 0.00 | -2719.23 |
DINING_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -22822.58 | 0.00 | 0.00 | 15644.16 | 1992.02 | 6747.90 | 0.00 | 0.00 | 7.86 | 0.00 | 0.00 | -230.99 | 0.00 | 0.00 | -1338.37 |
KITCHEN_FLR_6 | 30-SEP-10:50 | 0.00 | 0.00 | 0.00 | -30365.19 | 0.00 | 0.00 | 461.49 | 294.67 | 24259.91 | 2355.79 | 0.00 | 93.96 | 2899.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-SEP-13:40 | 0.00 | 0.00 | 0.00 | -5237.53 | 0.00 | 0.00 | 462.68 | 548.96 | 0.00 | 2835.69 | 0.00 | 109.46 | 1280.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-OCT-08:61 | 0.00 | -178163.10 | 0.00 | -156638.61 | 0.00 | 0.00 | 50308.54 | 24800.21 | 89868.82 | 97835.19 | 0.00 | 3798.69 | 68190.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 30-MAR-06:15 | 0.00 | 0.00 | 107.92 | 0.00 | 0.00 | 0.00 | 358.53 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -635.09 | 0.00 | -185.99 | -410.38 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-MAR-18:04 | 4469.30 | 415.32 | 0.00 | -415.32 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1146.78 | 0.00 | -202.48 | -4573.45 |
ROOM_2_FLR_3 | 08-MAY-18:14 | 4417.10 | 417.15 | 0.00 | -417.15 | 0.00 | 0.00 | 335.19 | 633.19 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -238.35 | 0.00 | -178.93 | -5452.79 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 16-MAR-15:05 | 23197.73 | 5824.56 | 0.00 | -5824.56 | 0.00 | 0.00 | 4786.82 | 2379.59 | 3726.41 | 968.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13256.98 | -21801.60 |
ROOM_5_FLR_3 | 16-NOV-16:04 | 4338.69 | 416.85 | 0.00 | -416.85 | 0.00 | 0.00 | 236.51 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.88 | 0.00 | -660.49 | -4259.24 |
ROOM_6_FLR_3 | 22-NOV-16:03 | 4243.37 | 415.40 | 0.00 | -415.40 | 0.00 | 0.00 | 254.30 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -759.53 | 0.00 | -648.16 | -3489.34 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 11-MAY-15:04 | 1293.73 | 117.69 | 0.00 | -117.69 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 520.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -206.63 | -1766.13 |
ROOM_2_FLR_6 | 30-NOV-19:03 | 1286.43 | 103.70 | 0.00 | -103.70 | 0.00 | 0.00 | 90.21 | 158.30 | 121.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -286.01 | 0.00 | -52.42 | -1317.66 |
ROOM_3_MULT9_FLR_6 | 20-MAR-15:04 | 6203.64 | 672.72 | 0.00 | -672.72 | 0.00 | 0.00 | 533.40 | 281.79 | 441.28 | 207.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1762.11 | -5905.25 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-MAR-15:04 | -71638.13 | 125587.62 | 0.00 | -125587.62 | 0.00 | 0.00 | 56796.83 | 16598.37 | 73912.59 | 21319.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18433.60 | -78555.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.3604 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.2435 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6628 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6628 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000970 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4358 | 2.4358 | 1.3299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3154 | 0.3154 | 0.1722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2269 | 0.2269 | 0.1239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1833 | 0.1833 | 0.1001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1067 | 0.1067 | 0.0583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3005 | 3.3005 | 1.8021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3882 | 1.3882 | 0.7580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6823 | 4.6823 | 2.5565 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4334 | 1.4334 | 0.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1241 | 2.1241 | 1.1597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2272 | 2.2272 | 1.2161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2281 | 2.2281 | 1.2165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7086 | 0.7086 | 0.3869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.3604 | 21.2435 | 21.3604 | 11.6628 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3299 | 1.3299 | 1.3299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1722 | 0.1722 | 0.1722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1239 | 0.1239 | 0.1239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1001 | 0.1001 | 0.1001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0583 | 0.0583 | 0.0583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8021 | 1.8021 | 1.8021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7580 | 0.7580 | 0.7580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5565 | 2.5565 | 2.5565 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7826 | 0.7826 | 0.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1597 | 1.1597 | 1.1597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2161 | 1.2161 | 1.2161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2165 | 1.2165 | 1.2165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3869 | 0.3869 | 0.3869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6628 | 11.6628 | 11.6628 | 11.6628 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 48.50 |
Number of hours not met | 48.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 909.88 | 200468.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 876.52 | 163331.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.31 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.98 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 517.02 | 34359.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 75.06 | 4278.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.73 | 2934.53 | 246302.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.47 | 1892.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.75 | 1203.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.48 | 4897.93 |
Natural Gas | 1788.84 | 5633.25 |
Additional | 0.00 | 0.00 |
Total | 3509.32 | 10531.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.04 |
Space Heating | 0.00 |
Space Cooling | 77.26 |
Fans (All) | 45.57 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 431.72 |
Subtotal | 431.72 |
Natural Gas [MJ/m2] | |
Space Heating | 80.20 |
Service Water Heating | 258.66 |
Miscellaneous (All) | 496.53 |
Subtotal | 496.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.44 |
Space Heating | 8.64 |
Space Cooling | 8.32 |
Fans (All) | 4.91 |
Service Water Heating | 28.73 |
Receptacle Equipment | 32.73 |
Miscellaneous | 9.23 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6751.00 | 2009.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8670.33 | 89.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6751.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2009.00 | 0.00 | 0.00 | 0.00 |
Average | 8662.68 | 97.32 | 0.00 | 0.00 | 0.00 |
Sum | 190579.00 | 2141.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.67 | 2.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4139.33 | 14.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Average | 288886.27 | 0.77 | 0.00 | 0.00 | 0.00 |
Sum | 6355498.00 | 17.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7916.33 | 843.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7972.50 | 787.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8507.00 | 253.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5588.50 | 3171.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8632.67 | 127.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8375.50 | 384.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7883.50 | 876.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7983.67 | 776.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8689.83 | 70.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 5588.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3171.50 | 0.00 | 0.00 | 0.00 |
Average | 8428.27 | 331.73 | 0.00 | 0.00 | 0.00 |
Sum | 185421.83 | 7298.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59154.17 | 1.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 606277.33 | 104139.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1831718.67 | 283710.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4046.67 | 107.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4144.67 | 9.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3975.50 | 178.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1064037.33 | 181677.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1083387.17 | 162327.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107580.50 | 688.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1831718.67 | 283710.33 | 0.00 | 0.00 | 0.00 |
Average | 255576.06 | 33310.98 | 0.00 | 0.00 | 0.00 |
Sum | 5622673.33 | 732841.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:08
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354035E+11 | 22039.30 | 08-JAN-07:00 | 1.00 | -0.3 | 0.766037E+10 | 4837.05 | 24-JAN-23:10 | 14.33 | 10.84 |
February | 0.292595E+11 | 17075.64 | 04-FEB-05:55 | 5.00 | 0.22 | 0.668271E+10 | 4781.81 | 01-FEB-22:19 | 5.00 | 0.22 |
March | 0.320285E+11 | 17459.17 | 08-MAR-02:00 | 4.00 | 3.53 | 0.720043E+10 | 4523.42 | 24-MAR-21:19 | 13.00 | 11.68 |
April | 0.304450E+11 | 14831.77 | 30-APR-10:33 | 25.67 | 16.97 | 0.698297E+10 | 4506.62 | 14-APR-21:19 | 25.67 | 16.97 |
May | 0.315129E+11 | 14516.97 | 28-MAY-10:33 | 21.00 | 15.43 | 0.723499E+10 | 4509.11 | 12-MAY-21:10 | 21.00 | 15.43 |
June | 0.304362E+11 | 14720.82 | 25-JUN-10:33 | 23.00 | 17.26 | 0.695438E+10 | 4460.15 | 09-JUN-21:19 | 23.00 | 17.26 |
July | 0.333110E+11 | 15579.95 | 23-JUL-10:33 | 25.67 | 20.39 | 0.740357E+10 | 4626.08 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.338024E+11 | 15573.18 | 06-AUG-10:33 | 24.33 | 20.00 | 0.751692E+10 | 4654.07 | 25-AUG-22:10 | 16.00 | 16.00 |
September | 0.336531E+11 | 16136.23 | 30-SEP-10:33 | 30.57 | 17.23 | 0.747966E+10 | 4811.28 | 28-SEP-22:10 | 30.57 | 17.23 |
October | 0.360144E+11 | 16963.10 | 20-OCT-21:00 | 16.00 | 13.03 | 0.791727E+10 | 4837.09 | 18-OCT-21:30 | 16.00 | 13.03 |
November | 0.347427E+11 | 17143.44 | 22-NOV-22:00 | 11.00 | 2.60 | 0.768162E+10 | 4837.05 | 09-NOV-23:10 | 11.00 | 2.60 |
December | 0.353310E+11 | 18064.07 | 03-DEC-00:55 | 5.00 | 5.00 | 0.775801E+10 | 4837.04 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.395940E+12 | 0.884729E+11 | ||||||||
Minimum of Months | 0.292595E+11 | 14516.97 | 1.00 | -0.3 | 0.668271E+10 | 4460.15 | 5.00 | 0.22 | ||
Maximum of Months | 0.360144E+11 | 22039.30 | 30.57 | 20.39 | 0.791727E+10 | 4837.09 | 30.57 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372666E+10 | 3235.98 | 14-JAN-12:40 | 25.33 | 11.70 | 0.669878E+09 | 438.17 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.306729E+10 | 2853.54 | 02-FEB-12:40 | 19.33 | 12.36 | 0.598141E+09 | 436.67 | 01-FEB-22:30 | 19.33 | 12.36 |
March | 0.303834E+10 | 2513.48 | 11-MAR-13:00 | 24.00 | 13.82 | 0.651461E+09 | 434.55 | 23-MAR-21:30 | 13.50 | 12.93 |
April | 0.344002E+10 | 2005.10 | 08-APR-10:33 | 21.67 | 16.37 | 0.644351E+09 | 435.53 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.332403E+10 | 1948.75 | 04-MAY-10:33 | 22.00 | 15.73 | 0.648825E+09 | 437.82 | 04-MAY-21:30 | 17.00 | 15.07 |
June | 0.351227E+10 | 1873.81 | 25-JUN-10:33 | 23.00 | 17.26 | 0.646509E+09 | 433.98 | 28-JUN-21:40 | 17.00 | 16.37 |
July | 0.395820E+10 | 2052.57 | 30-JUL-10:33 | 24.67 | 20.10 | 0.695868E+09 | 450.10 | 31-JUL-21:30 | 18.85 | 17.85 |
August | 0.416157E+10 | 2128.52 | 27-AUG-10:33 | 23.33 | 18.72 | 0.720570E+09 | 457.69 | 18-AUG-21:30 | 23.33 | 18.72 |
September | 0.405318E+10 | 3462.92 | 30-SEP-13:10 | 32.00 | 16.98 | 0.693515E+09 | 491.81 | 29-SEP-21:30 | 32.00 | 16.98 |
October | 0.450775E+10 | 4079.22 | 16-OCT-12:10 | 35.68 | 17.48 | 0.723799E+09 | 491.84 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.387856E+10 | 3601.89 | 19-NOV-12:30 | 26.50 | 15.22 | 0.661403E+09 | 441.43 | 27-NOV-22:30 | 16.00 | 5.61 |
December | 0.397358E+10 | 3437.42 | 19-DEC-12:50 | 25.83 | 11.54 | 0.678559E+09 | 454.78 | 05-DEC-22:30 | 25.83 | 11.54 |
Annual Sum or Average | 0.446415E+11 | 0.803288E+10 | ||||||||
Minimum of Months | 0.303834E+10 | 1873.81 | 19.33 | 11.54 | 0.598141E+09 | 433.98 | 13.50 | 5.61 | ||
Maximum of Months | 0.450775E+10 | 4079.22 | 35.68 | 20.10 | 0.723799E+09 | 491.84 | 32.00 | 18.72 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304771E+10 | 1676.89 | 28-JAN-07:00 | 3.00 | 2.55 | 0.851935E+09 | 569.55 | 18-JAN-23:10 | 3.00 | 2.55 |
February | 0.267105E+10 | 1550.97 | 04-FEB-05:55 | 5.00 | 0.22 | 0.779220E+09 | 569.51 | 02-FEB-23:10 | 5.00 | 0.22 |
March | 0.294173E+10 | 1561.51 | 08-MAR-02:00 | 4.00 | 3.53 | 0.846038E+09 | 569.51 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.295634E+10 | 1481.64 | 27-APR-21:00 | 14.00 | 12.84 | 0.853656E+09 | 569.55 | 26-APR-22:10 | 14.00 | 12.84 |
May | 0.302662E+10 | 1490.45 | 03-MAY-21:00 | 16.00 | 14.77 | 0.878309E+09 | 569.55 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.304784E+10 | 1546.33 | 30-JUN-21:00 | 16.00 | 14.76 | 0.869923E+09 | 569.55 | 19-JUN-22:10 | 16.00 | 14.76 |
July | 0.330909E+10 | 1656.94 | 31-JUL-21:00 | 19.00 | 17.66 | 0.916840E+09 | 569.55 | 26-JUL-22:10 | 19.00 | 17.66 |
August | 0.337277E+10 | 1724.42 | 18-AUG-21:00 | 19.00 | 17.66 | 0.929253E+09 | 569.55 | 02-AUG-22:10 | 19.00 | 17.66 |
September | 0.319199E+10 | 1928.89 | 29-SEP-21:00 | 24.60 | 13.50 | 0.889962E+09 | 569.55 | 13-SEP-22:10 | 24.60 | 13.50 |
October | 0.331249E+10 | 1976.92 | 16-OCT-20:10 | 20.50 | 12.73 | 0.920389E+09 | 569.55 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.298258E+10 | 1539.55 | 29-NOV-23:00 | 7.00 | 4.66 | 0.859028E+09 | 569.54 | 10-NOV-22:30 | 7.00 | 4.66 |
December | 0.307488E+10 | 1538.80 | 03-DEC-00:55 | 5.00 | 5.00 | 0.868766E+09 | 569.54 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.369351E+11 | 0.104633E+11 | ||||||||
Minimum of Months | 0.267105E+10 | 1481.64 | 3.00 | 0.22 | 0.779220E+09 | 569.51 | 3.00 | 0.22 | ||
Maximum of Months | 0.337277E+10 | 1976.92 | 24.60 | 17.66 | 0.929253E+09 | 569.55 | 24.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212150E+10 | 1252.31 | 27-JAN-04:55 | 4.00 | 3.53 | 0.164368E+09 | 109.36 | 18-JAN-22:19 | 4.00 | 3.53 |
February | 0.191679E+10 | 1172.63 | 04-FEB-05:55 | 5.00 | 0.22 | 0.150148E+09 | 107.50 | 03-FEB-22:10 | 5.00 | 0.22 |
March | 0.205649E+10 | 1067.06 | 07-MAR-23:00 | 6.00 | 5.05 | 0.163790E+09 | 107.00 | 24-MAR-21:19 | 13.00 | 11.68 |
April | 0.215347E+10 | 1107.99 | 30-APR-10:33 | 25.67 | 16.97 | 0.165860E+09 | 110.05 | 27-APR-21:19 | 25.67 | 16.97 |
May | 0.228255E+10 | 1122.39 | 04-MAY-10:33 | 22.00 | 15.73 | 0.174640E+09 | 112.61 | 04-MAY-21:19 | 17.00 | 15.07 |
June | 0.235153E+10 | 1168.63 | 25-JUN-10:33 | 23.00 | 17.26 | 0.175920E+09 | 115.09 | 30-JUN-21:19 | 16.03 | 15.21 |
July | 0.256182E+10 | 1220.40 | 23-JUL-10:33 | 25.67 | 20.39 | 0.186739E+09 | 116.87 | 19-JUL-21:19 | 25.67 | 20.39 |
August | 0.256190E+10 | 1214.66 | 19-AUG-10:33 | 24.67 | 20.11 | 0.187437E+09 | 117.07 | 18-AUG-21:19 | 24.67 | 20.11 |
September | 0.238438E+10 | 1251.07 | 30-SEP-10:33 | 30.57 | 17.23 | 0.177217E+09 | 118.30 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.249185E+10 | 1246.30 | 16-OCT-10:33 | 36.33 | 17.49 | 0.184987E+09 | 120.42 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.216239E+10 | 1115.71 | 29-NOV-23:00 | 7.00 | 4.66 | 0.166618E+09 | 109.69 | 01-NOV-21:10 | 7.00 | 4.66 |
December | 0.219692E+10 | 1174.65 | 03-DEC-00:55 | 5.00 | 5.00 | 0.167088E+09 | 109.40 | 05-DEC-22:19 | 17.33 | 9.44 |
Annual Sum or Average | 0.272416E+11 | 0.206481E+10 | ||||||||
Minimum of Months | 0.191679E+10 | 1067.06 | 4.00 | 0.22 | 0.150148E+09 | 107.00 | 4.00 | 0.22 | ||
Maximum of Months | 0.256190E+10 | 1252.31 | 36.33 | 20.39 | 0.187437E+09 | 120.42 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116982E+10 | 716.45 | 27-JAN-04:55 | 4.00 | 3.53 | 0.124078E+09 | 81.10 | 18-JAN-23:10 | 4.00 | 3.53 |
February | 0.108043E+10 | 672.04 | 04-FEB-05:55 | 5.00 | 0.22 | 0.112894E+09 | 79.61 | 03-FEB-23:10 | 5.00 | 0.22 |
March | 0.113136E+10 | 599.76 | 23-MAR-10:33 | 22.00 | 16.70 | 0.123445E+09 | 79.31 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.121695E+10 | 638.30 | 30-APR-10:33 | 25.67 | 16.97 | 0.124754E+09 | 81.48 | 27-APR-22:10 | 25.67 | 16.97 |
May | 0.128887E+10 | 646.21 | 04-MAY-10:33 | 22.00 | 15.73 | 0.131111E+09 | 83.54 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.133034E+10 | 670.77 | 25-JUN-10:33 | 23.00 | 17.26 | 0.132157E+09 | 85.05 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.145089E+10 | 701.52 | 23-JUL-10:33 | 25.67 | 20.39 | 0.140290E+09 | 86.57 | 19-JUL-22:10 | 25.67 | 20.39 |
August | 0.145146E+10 | 697.87 | 19-AUG-10:33 | 24.67 | 20.11 | 0.140860E+09 | 86.66 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.135110E+10 | 723.20 | 30-SEP-10:33 | 30.57 | 17.23 | 0.133292E+09 | 88.21 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.141124E+10 | 722.83 | 16-OCT-10:33 | 36.33 | 17.49 | 0.139036E+09 | 89.43 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.122281E+10 | 636.33 | 19-NOV-11:33 | 26.00 | 15.32 | 0.125260E+09 | 81.25 | 01-NOV-22:10 | 26.00 | 15.32 |
December | 0.123414E+10 | 665.90 | 03-DEC-00:55 | 5.00 | 5.00 | 0.125791E+09 | 81.54 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.153394E+11 | 0.155297E+10 | ||||||||
Minimum of Months | 0.108043E+10 | 599.76 | 4.00 | 0.22 | 0.112894E+09 | 79.31 | 4.00 | 0.22 | ||
Maximum of Months | 0.145146E+10 | 723.20 | 36.33 | 20.39 | 0.140860E+09 | 89.43 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505566E+11 | 37510.91 | 24-JAN-21:00 | 17.00 | 11.91 | 0.571099E+09 | 381.67 | 20-JAN-22:10 | 17.00 | 11.91 |
February | 0.455328E+11 | 37408.81 | 03-FEB-21:00 | 13.00 | 7.33 | 0.522498E+09 | 381.67 | 22-FEB-22:10 | 12.00 | 10.34 |
March | 0.505200E+11 | 37602.79 | 23-MAR-20:00 | 14.00 | 13.42 | 0.574797E+09 | 381.69 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.495805E+11 | 37878.56 | 26-APR-20:00 | 17.00 | 15.07 | 0.563177E+09 | 381.68 | 11-APR-21:10 | 17.00 | 15.07 |
May | 0.513360E+11 | 37899.22 | 04-MAY-20:00 | 17.00 | 15.07 | 0.582619E+09 | 381.65 | 02-MAY-21:10 | 17.00 | 15.07 |
June | 0.503058E+11 | 37909.20 | 30-JUN-20:00 | 16.00 | 15.39 | 0.565551E+09 | 381.71 | 20-JUN-21:10 | 16.00 | 15.39 |
July | 0.524115E+11 | 38155.41 | 19-JUL-20:00 | 19.00 | 18.34 | 0.584068E+09 | 381.69 | 14-JUL-21:19 | 19.00 | 18.34 |
August | 0.527069E+11 | 38119.76 | 18-AUG-20:00 | 19.00 | 17.66 | 0.585581E+09 | 381.67 | 15-AUG-21:19 | 19.00 | 17.66 |
September | 0.502770E+11 | 38405.20 | 29-SEP-20:00 | 25.00 | 13.58 | 0.564981E+09 | 381.70 | 29-SEP-21:10 | 24.58 | 13.52 |
October | 0.519838E+11 | 38253.45 | 16-OCT-20:00 | 21.00 | 13.07 | 0.584729E+09 | 381.77 | 23-OCT-21:10 | 17.00 | 13.47 |
November | 0.492964E+11 | 37409.85 | 28-NOV-21:00 | 13.00 | 6.31 | 0.562337E+09 | 381.73 | 06-NOV-22:10 | 13.00 | 6.31 |
December | 0.505767E+11 | 37642.11 | 05-DEC-21:00 | 16.00 | 9.09 | 0.574055E+09 | 381.80 | 28-DEC-22:10 | 9.83 | 3.98 |
Annual Sum or Average | 0.605084E+12 | 0.683549E+10 | ||||||||
Minimum of Months | 0.455328E+11 | 37408.81 | 13.00 | 6.31 | 0.522498E+09 | 381.65 | 9.83 | 3.98 | ||
Maximum of Months | 0.527069E+11 | 38405.20 | 25.00 | 18.34 | 0.585581E+09 | 381.80 | 24.58 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204353E+11 | 12684.27 | 14-JAN-12:40 | 25.33 | 11.70 | 0.100399E+11 | 6462.53 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.172635E+11 | 10751.21 | 20-FEB-11:00 | 16.00 | 9.07 | 0.908256E+10 | 6462.04 | 02-FEB-00:20 | 16.00 | 9.07 |
March | 0.184295E+11 | 10449.86 | 11-MAR-12:50 | 24.00 | 13.82 | 0.978208E+10 | 6461.96 | 24-MAR-23:19 | 13.00 | 11.12 |
April | 0.183095E+11 | 9149.78 | 08-APR-10:33 | 21.67 | 16.37 | 0.977632E+10 | 6462.67 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.181383E+11 | 8767.13 | 04-MAY-21:20 | 17.00 | 15.07 | 0.989913E+10 | 6462.65 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.181394E+11 | 8608.33 | 25-JUN-10:33 | 23.00 | 17.26 | 0.979230E+10 | 6462.75 | 19-JUN-22:10 | 23.00 | 17.26 |
July | 0.196505E+11 | 9197.51 | 30-JUL-10:33 | 24.67 | 20.10 | 0.102896E+11 | 6462.73 | 10-JUL-22:10 | 24.67 | 20.10 |
August | 0.204242E+11 | 9527.06 | 27-AUG-10:33 | 23.33 | 18.72 | 0.105418E+11 | 6462.73 | 02-AUG-22:10 | 23.33 | 18.72 |
September | 0.199797E+11 | 12162.03 | 30-SEP-12:00 | 32.00 | 17.11 | 0.102046E+11 | 6462.62 | 12-SEP-22:10 | 32.00 | 17.11 |
October | 0.217821E+11 | 13773.16 | 15-OCT-12:00 | 32.00 | 16.89 | 0.106050E+11 | 6462.64 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.198948E+11 | 14032.50 | 19-NOV-11:00 | 26.00 | 15.07 | 0.100248E+11 | 6462.40 | 10-NOV-22:30 | 26.00 | 15.07 |
December | 0.209490E+11 | 12540.04 | 16-DEC-13:00 | 26.00 | 13.31 | 0.101915E+11 | 6462.37 | 05-DEC-23:10 | 26.00 | 13.31 |
Annual Sum or Average | 0.233396E+12 | 0.120229E+12 | ||||||||
Minimum of Months | 0.172635E+11 | 8608.33 | 16.00 | 9.07 | 0.908256E+10 | 6461.96 | 13.00 | 9.07 | ||
Maximum of Months | 0.217821E+11 | 14032.50 | 32.00 | 20.10 | 0.106050E+11 | 6462.75 | 32.00 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667466E+11 | 37352.55 | 09-JAN-05:55 | 2.00 | -0.2 | 0.300066E+11 | 19185.88 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.582633E+11 | 33501.66 | 04-FEB-05:55 | 5.00 | 0.22 | 0.274099E+11 | 19185.34 | 02-FEB-00:20 | 5.00 | 0.22 |
March | 0.639271E+11 | 33463.56 | 08-MAR-02:00 | 4.00 | 3.53 | 0.297135E+11 | 19183.49 | 02-MAR-22:00 | 4.00 | 3.53 |
April | 0.631717E+11 | 31054.24 | 26-APR-21:52 | 16.00 | 15.39 | 0.296095E+11 | 19186.11 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.646618E+11 | 32021.87 | 04-MAY-21:53 | 17.00 | 15.07 | 0.305118E+11 | 19186.01 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.647144E+11 | 31939.38 | 30-JUN-21:52 | 16.10 | 16.10 | 0.300523E+11 | 19186.23 | 19-JUN-22:10 | 16.10 | 16.10 |
July | 0.694351E+11 | 33402.29 | 19-JUL-21:52 | 18.00 | 17.35 | 0.313321E+11 | 19186.17 | 26-JUL-22:10 | 17.00 | 15.84 |
August | 0.707427E+11 | 34122.84 | 18-AUG-21:10 | 19.00 | 17.66 | 0.316950E+11 | 19186.17 | 02-AUG-22:10 | 19.00 | 17.66 |
September | 0.677643E+11 | 38120.54 | 29-SEP-21:10 | 24.58 | 13.52 | 0.305544E+11 | 19186.02 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.714677E+11 | 38613.24 | 16-OCT-21:10 | 18.33 | 11.06 | 0.317217E+11 | 19186.08 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.650251E+11 | 32583.17 | 29-NOV-23:00 | 7.00 | 4.66 | 0.300629E+11 | 19185.69 | 10-NOV-22:30 | 7.00 | 4.66 |
December | 0.672996E+11 | 33671.80 | 05-DEC-22:10 | 17.17 | 9.45 | 0.305346E+11 | 19186.20 | 01-DEC-00:40 | 17.17 | 9.45 |
Annual Sum or Average | 0.793220E+12 | 0.363204E+12 | ||||||||
Minimum of Months | 0.582633E+11 | 31054.24 | 2.00 | -0.2 | 0.274099E+11 | 19183.49 | 4.00 | 0.22 | ||
Maximum of Months | 0.714677E+11 | 38613.24 | 24.58 | 17.66 | 0.317217E+11 | 19186.23 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579877E+09 | 3310.36 | 14-JAN-16:01 | 23.00 | 12.42 | 97947791.99 | 56.69 | 20-JAN-22:19 | 13.33 | 13.33 |
February | 0.507405E+09 | 3321.30 | 03-FEB-16:01 | 20.50 | 10.05 | 88165762.48 | 56.69 | 16-FEB-22:10 | 12.00 | 11.46 |
March | 0.531594E+09 | 2875.30 | 15-MAR-15:01 | 16.83 | 14.45 | 97626891.22 | 56.69 | 23-MAR-22:30 | 12.50 | 12.23 |
April | 0.100092E+10 | 3070.09 | 01-APR-18:02 | 17.83 | 8.84 | 95264508.53 | 56.69 | 27-APR-02:09 | 15.83 | 15.22 |
May | 0.958234E+09 | 3055.94 | 24-MAY-08:61 | 18.00 | 8.80 | 98412218.22 | 56.69 | 05-MAY-21:40 | 18.00 | 8.80 |
June | 0.125917E+10 | 3016.81 | 29-JUN-18:01 | 21.50 | 18.39 | 95506174.17 | 56.69 | 30-JUN-03:39 | 17.00 | 16.37 |
July | 0.169786E+10 | 2998.39 | 22-JUL-18:02 | 21.67 | 18.43 | 98864297.02 | 56.70 | 25-JUL-21:40 | 17.00 | 16.79 |
August | 0.174526E+10 | 2998.92 | 05-AUG-15:01 | 22.67 | 18.32 | 98985813.16 | 56.70 | 07-AUG-21:30 | 18.00 | 17.35 |
September | 0.143014E+10 | 2976.66 | 21-SEP-15:02 | 27.67 | 19.86 | 95573973.32 | 56.69 | 22-SEP-22:00 | 17.00 | 17.00 |
October | 0.141637E+10 | 3364.99 | 13-OCT-15:01 | 27.67 | 14.85 | 98667712.99 | 56.69 | 18-OCT-21:10 | 14.83 | 14.34 |
November | 0.750610E+09 | 3281.62 | 27-NOV-16:01 | 19.67 | 7.55 | 95098596.92 | 56.69 | 10-NOV-23:10 | 19.67 | 7.55 |
December | 0.661475E+09 | 3321.08 | 19-DEC-16:01 | 20.67 | 8.11 | 98053970.50 | 56.69 | 07-DEC-22:10 | 20.67 | 8.11 |
Annual Sum or Average | 0.125389E+11 | 0.115817E+10 | ||||||||
Minimum of Months | 0.507405E+09 | 2875.30 | 16.83 | 7.55 | 88165762.48 | 56.69 | 12.00 | 7.55 | ||
Maximum of Months | 0.174526E+10 | 3364.99 | 27.67 | 19.86 | 98985813.16 | 56.70 | 20.67 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196554E+09 | 3172.73 | 15-JAN-16:01 | 21.83 | 10.39 | 97314108.95 | 64.21 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.222903E+09 | 3181.50 | 03-FEB-16:01 | 20.50 | 10.05 | 87778999.38 | 56.69 | 14-FEB-22:10 | 13.00 | 12.44 |
March | 0.283244E+09 | 2882.19 | 23-MAR-15:01 | 21.83 | 17.37 | 97854692.82 | 56.84 | 22-MAR-18:10 | 21.83 | 17.37 |
April | 0.642307E+09 | 3105.72 | 23-APR-18:11 | 14.67 | 13.07 | 98503794.74 | 74.17 | 26-APR-21:40 | 16.00 | 15.39 |
May | 0.719183E+09 | 3065.49 | 24-MAY-08:51 | 18.00 | 9.64 | 0.102716E+09 | 74.38 | 03-MAY-21:40 | 18.00 | 9.64 |
June | 0.894040E+09 | 2938.96 | 22-JUN-20:11 | 15.00 | 13.18 | 0.104839E+09 | 78.35 | 30-JUN-18:10 | 18.83 | 16.43 |
July | 0.120758E+10 | 2854.64 | 15-JUL-15:01 | 21.83 | 18.03 | 0.111540E+09 | 78.06 | 25-JUL-21:40 | 17.00 | 16.79 |
August | 0.114819E+10 | 2879.10 | 05-AUG-15:01 | 22.67 | 18.32 | 0.110673E+09 | 77.34 | 09-AUG-21:40 | 18.00 | 17.36 |
September | 0.884640E+09 | 2887.87 | 18-SEP-15:01 | 19.83 | 15.05 | 0.101999E+09 | 73.15 | 13-SEP-21:40 | 19.83 | 15.05 |
October | 0.801410E+09 | 3363.12 | 14-OCT-08:61 | 27.67 | 13.01 | 0.103898E+09 | 74.90 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.311152E+09 | 3145.35 | 27-NOV-16:01 | 19.67 | 7.55 | 95039810.88 | 65.49 | 10-NOV-22:10 | 19.67 | 7.55 |
December | 0.213911E+09 | 3181.65 | 19-DEC-16:01 | 20.67 | 8.11 | 97435647.90 | 64.82 | 05-DEC-22:40 | 20.67 | 8.11 |
Annual Sum or Average | 0.752512E+10 | 0.120959E+10 | ||||||||
Minimum of Months | 0.196554E+09 | 2854.64 | 14.67 | 7.55 | 87778999.38 | 56.69 | 13.00 | 7.55 | ||
Maximum of Months | 0.120758E+10 | 3363.12 | 27.67 | 18.32 | 0.111540E+09 | 78.35 | 21.83 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411857E+09 | 571.00 | 14-JAN-12:40 | 25.33 | 11.70 | 0.00 | 0.00 | 01-JAN-00:10 | 25.33 | 11.70 |
February | 0.263118E+09 | 497.86 | 02-FEB-12:30 | 19.50 | 11.91 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 11.91 |
March | 0.193315E+09 | 419.27 | 11-MAR-13:10 | 24.00 | 13.64 | 0.00 | 0.00 | 01-MAR-00:10 | 24.00 | 13.64 |
April | 0.218976E+09 | 293.83 | 08-APR-12:40 | 22.33 | 16.70 | 0.00 | 0.00 | 01-APR-00:10 | 22.33 | 16.70 |
May | 0.132192E+09 | 269.56 | 04-MAY-15:03 | 22.00 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 22.00 | 16.32 |
June | 0.177561E+09 | 187.50 | 30-JUN-07:00 | 18.00 | 16.69 | 0.00 | 0.00 | 01-JUN-00:10 | 18.00 | 16.69 |
July | 0.274465E+09 | 273.83 | 23-JUL-15:03 | 24.00 | 19.32 | 0.00 | 0.00 | 01-JUL-00:10 | 24.00 | 19.32 |
August | 0.365940E+09 | 283.49 | 30-AUG-13:00 | 24.00 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.00 | 18.12 |
September | 0.409171E+09 | 538.04 | 30-SEP-13:05 | 32.00 | 16.98 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.98 |
October | 0.529706E+09 | 650.39 | 16-OCT-12:20 | 35.37 | 17.35 | 0.00 | 0.00 | 01-OCT-00:10 | 35.37 | 17.35 |
November | 0.427059E+09 | 607.19 | 19-NOV-12:30 | 26.50 | 15.22 | 0.00 | 0.00 | 01-NOV-00:10 | 26.50 | 15.22 |
December | 0.470981E+09 | 586.94 | 19-DEC-13:00 | 26.00 | 11.60 | 0.00 | 0.00 | 01-DEC-00:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.387434E+10 | 0.00 | ||||||||
Minimum of Months | 0.132192E+09 | 187.50 | 18.00 | 11.60 | 0.00 | 0.00 | 18.00 | 11.60 | ||
Maximum of Months | 0.529706E+09 | 650.39 | 35.37 | 19.32 | 0.00 | 0.00 | 35.37 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248991E+09 | 1105.03 | 15-JAN-16:01 | 21.83 | 10.39 | 97388757.60 | 68.52 | 18-JAN-22:00 | 16.00 | 13.03 |
February | 0.258643E+09 | 1070.07 | 03-FEB-16:01 | 20.50 | 10.05 | 87669954.67 | 58.19 | 13-FEB-21:19 | 14.67 | 14.08 |
March | 0.295902E+09 | 1035.38 | 10-MAR-19:12 | 13.00 | 8.09 | 97336626.93 | 57.24 | 05-MAR-02:39 | 13.00 | 8.09 |
April | 0.379153E+09 | 1087.38 | 01-APR-15:01 | 22.83 | 11.17 | 95624876.89 | 71.15 | 25-APR-21:10 | 14.83 | 14.24 |
May | 0.437936E+09 | 1063.46 | 24-MAY-08:51 | 18.00 | 9.64 | 99782509.44 | 71.48 | 04-MAY-21:00 | 18.00 | 9.64 |
June | 0.470618E+09 | 1032.81 | 22-JUN-20:11 | 15.00 | 13.18 | 0.100114E+09 | 74.04 | 30-JUN-21:00 | 16.10 | 16.10 |
July | 0.548285E+09 | 1042.33 | 04-JUL-08:51 | 22.00 | 15.83 | 0.105700E+09 | 75.47 | 07-JUL-21:10 | 15.17 | 13.86 |
August | 0.516241E+09 | 1013.85 | 22-AUG-15:01 | 20.83 | 15.93 | 0.105219E+09 | 73.57 | 07-AUG-21:00 | 20.83 | 15.93 |
September | 0.432908E+09 | 1017.49 | 01-SEP-15:01 | 20.67 | 15.86 | 98717076.28 | 71.26 | 22-SEP-21:00 | 17.00 | 16.37 |
October | 0.441585E+09 | 1187.85 | 14-OCT-08:61 | 27.67 | 13.01 | 0.102037E+09 | 74.07 | 04-OCT-21:19 | 27.67 | 13.01 |
November | 0.290165E+09 | 1087.25 | 19-NOV-09:41 | 25.67 | 13.67 | 94321755.95 | 68.08 | 10-NOV-22:10 | 25.67 | 13.67 |
December | 0.252110E+09 | 1092.49 | 05-DEC-16:02 | 22.67 | 12.42 | 97153138.36 | 68.55 | 06-DEC-22:10 | 14.50 | 9.28 |
Annual Sum or Average | 0.457254E+10 | 0.118106E+10 | ||||||||
Minimum of Months | 0.248991E+09 | 1013.85 | 13.00 | 8.09 | 87669954.67 | 57.24 | 13.00 | 8.09 | ||
Maximum of Months | 0.548285E+09 | 1187.85 | 27.67 | 15.93 | 0.105700E+09 | 75.47 | 27.67 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606315E+09 | 2955.54 | 14-JAN-16:01 | 23.00 | 12.42 | 98249227.38 | 56.69 | 19-JAN-22:49 | 14.00 | 12.84 |
February | 0.475612E+09 | 2967.68 | 01-FEB-09:01 | 22.33 | 11.86 | 88246528.57 | 56.69 | 16-FEB-22:10 | 12.00 | 11.46 |
March | 0.521902E+09 | 2637.60 | 22-MAR-15:01 | 19.83 | 16.12 | 97806164.47 | 56.69 | 23-MAR-22:19 | 12.67 | 12.30 |
April | 0.912015E+09 | 2914.58 | 02-APR-08:62 | 17.33 | 8.66 | 95406141.29 | 56.69 | 27-APR-00:49 | 15.00 | 14.90 |
May | 0.833107E+09 | 2951.58 | 24-MAY-08:61 | 18.00 | 8.80 | 98496687.11 | 56.69 | 05-MAY-21:40 | 18.00 | 8.80 |
June | 0.108186E+10 | 2699.37 | 30-JUN-15:01 | 22.95 | 17.86 | 95544384.33 | 56.69 | 19-JUN-00:40 | 22.95 | 17.86 |
July | 0.154962E+10 | 2722.17 | 01-JUL-08:61 | 20.33 | 16.91 | 99023981.32 | 56.69 | 19-JUL-21:00 | 18.00 | 17.35 |
August | 0.165693E+10 | 2709.68 | 31-AUG-08:62 | 20.50 | 17.08 | 99131718.80 | 56.69 | 07-AUG-21:30 | 20.50 | 17.08 |
September | 0.124984E+10 | 2700.15 | 08-SEP-15:01 | 21.83 | 18.03 | 95489282.27 | 56.69 | 30-SEP-23:19 | 18.27 | 17.76 |
October | 0.135352E+10 | 3049.57 | 14-OCT-08:61 | 27.67 | 13.01 | 98732003.99 | 56.69 | 18-OCT-21:10 | 14.83 | 14.34 |
November | 0.702664E+09 | 2972.63 | 27-NOV-09:01 | 21.17 | 8.41 | 95244275.13 | 56.69 | 10-NOV-22:19 | 21.17 | 8.41 |
December | 0.661709E+09 | 2993.66 | 05-DEC-09:01 | 24.33 | 12.02 | 98276226.32 | 56.69 | 07-DEC-22:19 | 12.53 | 12.47 |
Annual Sum or Average | 0.116051E+11 | 0.115965E+10 | ||||||||
Minimum of Months | 0.475612E+09 | 2637.60 | 17.33 | 8.41 | 88246528.57 | 56.69 | 12.00 | 8.41 | ||
Maximum of Months | 0.165693E+10 | 3049.57 | 27.67 | 18.03 | 99131718.80 | 56.69 | 22.95 | 17.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230805E+09 | 2815.22 | 14-JAN-16:01 | 23.00 | 12.42 | 97367180.41 | 63.28 | 24-JAN-22:30 | 15.50 | 11.34 |
February | 0.218893E+09 | 2883.15 | 01-FEB-09:51 | 24.00 | 12.54 | 87543370.63 | 56.69 | 01-FEB-22:19 | 13.00 | 11.68 |
March | 0.293808E+09 | 2776.56 | 23-MAR-08:51 | 19.00 | 14.76 | 97648680.37 | 56.69 | 23-MAR-22:10 | 12.83 | 12.37 |
April | 0.617984E+09 | 3092.05 | 02-APR-08:51 | 19.00 | 9.47 | 97188038.60 | 70.21 | 26-APR-21:49 | 16.00 | 15.39 |
May | 0.657385E+09 | 3183.94 | 24-MAY-08:51 | 18.00 | 9.64 | 0.101231E+09 | 71.52 | 04-MAY-21:40 | 18.00 | 9.64 |
June | 0.819457E+09 | 2996.46 | 14-JUN-08:51 | 22.00 | 16.42 | 0.101579E+09 | 72.23 | 30-JUN-21:49 | 16.08 | 15.88 |
July | 0.114131E+10 | 2999.77 | 04-JUL-08:51 | 22.00 | 15.83 | 0.108211E+09 | 74.31 | 19-JUL-21:40 | 18.00 | 17.57 |
August | 0.112259E+10 | 2881.31 | 22-AUG-08:51 | 19.00 | 14.76 | 0.108062E+09 | 74.17 | 18-AUG-21:30 | 19.00 | 14.76 |
September | 0.775376E+09 | 2917.41 | 12-SEP-08:51 | 21.00 | 15.98 | 0.100025E+09 | 69.90 | 13-SEP-21:40 | 17.00 | 16.37 |
October | 0.763756E+09 | 3413.27 | 17-OCT-08:21 | 27.50 | 13.36 | 0.103130E+09 | 73.22 | 16-OCT-21:40 | 27.50 | 13.36 |
November | 0.300844E+09 | 2828.00 | 28-NOV-09:51 | 21.00 | 8.49 | 94656739.53 | 62.21 | 10-NOV-22:10 | 21.00 | 8.49 |
December | 0.227252E+09 | 3065.13 | 05-DEC-09:41 | 25.67 | 12.88 | 97428380.90 | 64.71 | 05-DEC-22:40 | 17.67 | 9.41 |
Annual Sum or Average | 0.716946E+10 | 0.119407E+10 | ||||||||
Minimum of Months | 0.218893E+09 | 2776.56 | 18.00 | 8.49 | 87543370.63 | 56.69 | 12.83 | 8.49 | ||
Maximum of Months | 0.114131E+10 | 3413.27 | 27.50 | 16.42 | 0.108211E+09 | 74.31 | 27.50 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418445E+10 | 2582.25 | 28-JAN-07:00 | 3.00 | 2.55 | 0.128971E+10 | 824.56 | 20-JAN-23:10 | 3.00 | 2.55 |
February | 0.370014E+10 | 2304.65 | 04-FEB-05:55 | 5.00 | 0.22 | 0.117387E+10 | 821.26 | 03-FEB-23:10 | 5.00 | 0.22 |
March | 0.400571E+10 | 2161.22 | 08-MAR-01:00 | 5.00 | 4.08 | 0.128005E+10 | 819.07 | 24-MAR-21:49 | 13.00 | 11.39 |
April | 0.414231E+10 | 2154.89 | 30-APR-10:33 | 25.67 | 16.97 | 0.129214E+10 | 833.37 | 27-APR-21:49 | 25.67 | 16.97 |
May | 0.431759E+10 | 2159.42 | 04-MAY-10:33 | 22.00 | 15.73 | 0.134550E+10 | 853.55 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.440262E+10 | 2224.61 | 25-JUN-10:33 | 23.00 | 17.26 | 0.134459E+10 | 866.98 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.482842E+10 | 2319.46 | 23-JUL-10:33 | 25.67 | 20.39 | 0.143222E+10 | 878.94 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.489292E+10 | 2341.68 | 19-AUG-10:33 | 24.67 | 20.11 | 0.145166E+10 | 888.95 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.454741E+10 | 2405.87 | 30-SEP-10:33 | 30.57 | 17.23 | 0.137134E+10 | 892.16 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.476984E+10 | 2420.50 | 17-OCT-10:33 | 31.00 | 16.57 | 0.143420E+10 | 915.55 | 17-OCT-21:49 | 18.00 | 14.47 |
November | 0.417797E+10 | 2164.90 | 19-NOV-11:33 | 26.00 | 15.32 | 0.130081E+10 | 851.67 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.430435E+10 | 2291.48 | 03-DEC-00:55 | 5.00 | 5.00 | 0.131559E+10 | 836.10 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.522737E+11 | 0.160317E+11 | ||||||||
Minimum of Months | 0.370014E+10 | 2154.89 | 3.00 | 0.22 | 0.117387E+10 | 819.07 | 3.00 | 0.22 | ||
Maximum of Months | 0.489292E+10 | 2582.25 | 31.00 | 20.39 | 0.145166E+10 | 915.55 | 30.57 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486606E+09 | 3424.84 | 14-JAN-16:01 | 23.00 | 12.42 | 97694853.73 | 56.69 | 19-JAN-01:49 | 12.33 | 10.50 |
February | 0.423618E+09 | 3430.17 | 03-FEB-16:01 | 20.50 | 10.05 | 87901169.11 | 56.69 | 01-FEB-22:10 | 20.50 | 10.05 |
March | 0.480010E+09 | 3040.74 | 15-MAR-15:01 | 16.83 | 14.45 | 97424978.87 | 56.69 | 23-MAR-21:40 | 13.33 | 12.77 |
April | 0.960869E+09 | 3196.08 | 01-APR-18:02 | 17.83 | 8.84 | 95204185.87 | 56.69 | 11-APR-21:00 | 13.00 | 13.00 |
May | 0.903266E+09 | 3125.40 | 24-MAY-08:61 | 18.00 | 8.80 | 98351155.55 | 56.70 | 08-MAY-02:39 | 18.00 | 8.80 |
June | 0.124169E+10 | 3106.79 | 29-JUN-18:01 | 21.50 | 18.39 | 95465579.32 | 56.69 | 16-JUN-00:10 | 21.50 | 18.39 |
July | 0.171478E+10 | 3134.65 | 27-JUL-18:01 | 20.67 | 17.73 | 98834656.99 | 56.69 | 31-JUL-21:10 | 18.95 | 17.72 |
August | 0.173913E+10 | 3067.85 | 01-AUG-18:01 | 17.83 | 15.38 | 98937708.18 | 56.70 | 14-AUG-21:10 | 18.83 | 17.61 |
September | 0.136469E+10 | 3034.75 | 24-SEP-15:01 | 18.83 | 17.02 | 95502107.36 | 56.69 | 06-SEP-23:00 | 18.83 | 17.02 |
October | 0.129600E+10 | 3481.33 | 13-OCT-15:01 | 27.67 | 14.85 | 98542251.53 | 56.69 | 17-OCT-21:19 | 18.00 | 14.77 |
November | 0.620037E+09 | 3387.08 | 30-NOV-16:01 | 17.83 | 11.31 | 94866207.63 | 56.69 | 10-NOV-22:10 | 17.83 | 11.31 |
December | 0.550206E+09 | 3434.34 | 19-DEC-16:01 | 20.67 | 8.11 | 97766030.17 | 56.69 | 05-DEC-22:10 | 20.67 | 8.11 |
Annual Sum or Average | 0.117809E+11 | 0.115649E+10 | ||||||||
Minimum of Months | 0.423618E+09 | 3034.75 | 16.83 | 8.11 | 87901169.11 | 56.69 | 12.33 | 8.11 | ||
Maximum of Months | 0.173913E+10 | 3481.33 | 27.67 | 18.39 | 98937708.18 | 56.70 | 21.50 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133191E+09 | 3269.04 | 14-JAN-16:01 | 23.00 | 12.42 | 96806568.00 | 62.62 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.157835E+09 | 3273.06 | 03-FEB-16:01 | 20.50 | 10.05 | 87419215.30 | 56.69 | 01-FEB-22:10 | 20.50 | 10.05 |
March | 0.231246E+09 | 3007.79 | 19-MAR-18:11 | 13.67 | 12.71 | 97757292.95 | 59.38 | 22-MAR-18:10 | 15.50 | 14.39 |
April | 0.593725E+09 | 3314.09 | 23-APR-18:11 | 14.67 | 13.07 | 99055263.27 | 78.22 | 26-APR-18:10 | 18.67 | 15.37 |
May | 0.674911E+09 | 3172.27 | 24-MAY-08:51 | 18.00 | 9.64 | 0.103246E+09 | 76.19 | 03-MAY-21:40 | 18.00 | 9.64 |
June | 0.919189E+09 | 3089.20 | 04-JUN-19:31 | 15.00 | 13.18 | 0.106275E+09 | 83.18 | 30-JUN-18:10 | 18.83 | 16.43 |
July | 0.128749E+10 | 2974.90 | 08-JUL-21:11 | 15.00 | 13.80 | 0.113188E+09 | 82.37 | 25-JUL-18:10 | 20.67 | 18.14 |
August | 0.119569E+10 | 2859.67 | 05-AUG-15:01 | 22.67 | 18.32 | 0.111942E+09 | 80.46 | 03-AUG-18:10 | 22.67 | 18.32 |
September | 0.843203E+09 | 2960.70 | 18-SEP-15:01 | 19.83 | 15.05 | 0.102150E+09 | 73.59 | 13-SEP-21:40 | 19.83 | 15.05 |
October | 0.711152E+09 | 3374.01 | 14-OCT-08:61 | 27.67 | 13.01 | 0.103398E+09 | 74.31 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.205047E+09 | 3232.91 | 27-NOV-16:01 | 19.67 | 7.55 | 94541454.63 | 63.25 | 10-NOV-22:10 | 19.67 | 7.55 |
December | 0.137727E+09 | 3276.85 | 19-DEC-16:01 | 20.67 | 8.11 | 96816252.92 | 62.87 | 05-DEC-22:40 | 20.67 | 8.11 |
Annual Sum or Average | 0.709040E+10 | 0.121260E+10 | ||||||||
Minimum of Months | 0.133191E+09 | 2859.67 | 13.67 | 7.55 | 87419215.30 | 56.69 | 15.50 | 7.55 | ||
Maximum of Months | 0.128749E+10 | 3374.01 | 27.67 | 18.32 | 0.113188E+09 | 83.18 | 22.67 | 18.32 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.865820E+09 | 1870.60 | 14-JAN-16:01 | 23.00 | 12.42 | 98696482.03 | 57.37 | 29-JAN-04:10 | 8.00 | 8.00 |
February | 0.588181E+09 | 1860.80 | 03-FEB-16:01 | 20.50 | 10.05 | 88707673.97 | 57.30 | 21-FEB-02:39 | 9.00 | 7.93 |
March | 0.507486E+09 | 1627.43 | 24-MAR-18:01 | 13.00 | 11.87 | 98052987.78 | 57.36 | 11-MAR-02:49 | 13.00 | 11.87 |
April | 0.600672E+09 | 1740.91 | 01-APR-18:02 | 17.83 | 8.84 | 95230112.68 | 56.69 | 03-APR-22:40 | 12.67 | 12.67 |
May | 0.428709E+09 | 1669.12 | 24-MAY-08:61 | 18.00 | 8.80 | 98065092.28 | 56.69 | 05-MAY-21:49 | 18.00 | 8.80 |
June | 0.522946E+09 | 1640.20 | 21-JUN-15:01 | 22.00 | 16.41 | 95135717.56 | 56.69 | 16-JUN-21:49 | 22.00 | 16.41 |
July | 0.745015E+09 | 1672.36 | 29-JUL-15:02 | 23.83 | 19.84 | 98668759.96 | 56.69 | 06-JUL-22:49 | 23.83 | 19.84 |
August | 0.904689E+09 | 1679.42 | 05-AUG-15:01 | 22.67 | 18.32 | 98870626.88 | 56.69 | 18-AUG-21:19 | 19.00 | 17.66 |
September | 0.912558E+09 | 1647.33 | 21-SEP-15:02 | 27.67 | 19.86 | 95414173.04 | 56.69 | 25-SEP-21:30 | 16.00 | 15.70 |
October | 0.111879E+10 | 1878.26 | 26-OCT-15:01 | 22.67 | 12.63 | 98748778.55 | 57.31 | 30-OCT-03:49 | 9.00 | 6.63 |
November | 0.874653E+09 | 1846.82 | 27-NOV-09:01 | 21.17 | 8.41 | 95614748.83 | 57.35 | 06-NOV-02:49 | 21.17 | 8.41 |
December | 0.943375E+09 | 1870.83 | 29-DEC-16:01 | 21.17 | 10.21 | 98750247.20 | 57.32 | 01-DEC-04:00 | 21.17 | 10.21 |
Annual Sum or Average | 0.901289E+10 | 0.115996E+10 | ||||||||
Minimum of Months | 0.428709E+09 | 1627.43 | 13.00 | 8.41 | 88707673.97 | 56.69 | 8.00 | 6.63 | ||
Maximum of Months | 0.111879E+10 | 1878.26 | 27.67 | 19.86 | 98870626.88 | 57.37 | 23.83 | 19.84 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353142E+11 | 19573.72 | 18-JAN-22:10 | 16.83 | 13.41 | 0.187975E+11 | 11348.63 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.318920E+11 | 18987.20 | 01-FEB-23:00 | 13.00 | 11.29 | 0.172013E+11 | 11347.80 | 08-FEB-00:20 | 12.67 | 6.27 |
March | 0.357081E+11 | 19342.98 | 24-MAR-22:00 | 13.00 | 11.29 | 0.190177E+11 | 11347.81 | 14-MAR-03:20 | 13.00 | 11.29 |
April | 0.361837E+11 | 20276.21 | 26-APR-21:52 | 16.00 | 15.39 | 0.185843E+11 | 11348.97 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.379018E+11 | 20670.42 | 04-MAY-21:53 | 17.00 | 15.07 | 0.192335E+11 | 11348.93 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.383584E+11 | 20904.66 | 27-JUN-21:52 | 17.00 | 16.37 | 0.186858E+11 | 11349.13 | 19-JUN-22:10 | 17.00 | 16.37 |
July | 0.407495E+11 | 21103.54 | 19-JUL-21:52 | 18.00 | 17.35 | 0.192570E+11 | 11349.09 | 05-JUL-22:10 | 18.00 | 17.35 |
August | 0.406347E+11 | 20972.97 | 18-AUG-21:52 | 19.00 | 17.66 | 0.193289E+11 | 11349.09 | 02-AUG-22:10 | 19.00 | 17.66 |
September | 0.378858E+11 | 21457.64 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186224E+11 | 11348.82 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.388196E+11 | 21166.41 | 04-OCT-21:53 | 21.00 | 18.98 | 0.192119E+11 | 11348.91 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.346597E+11 | 19221.33 | 10-NOV-23:00 | 15.00 | 13.80 | 0.184558E+11 | 11348.34 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.352360E+11 | 19691.94 | 05-DEC-22:54 | 18.00 | 9.37 | 0.189233E+11 | 11348.89 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.443343E+12 | 0.225319E+12 | ||||||||
Minimum of Months | 0.318920E+11 | 18987.20 | 13.00 | 9.37 | 0.172013E+11 | 11347.80 | 12.67 | 6.27 | ||
Maximum of Months | 0.407495E+11 | 21457.64 | 24.58 | 18.98 | 0.193289E+11 | 11349.13 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387036E+11 | 21236.21 | 18-JAN-22:10 | 16.83 | 13.41 | 0.189703E+11 | 11348.64 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.350861E+11 | 20696.76 | 01-FEB-22:10 | 13.00 | 11.77 | 0.173274E+11 | 11347.82 | 08-FEB-00:20 | 12.67 | 6.27 |
March | 0.392579E+11 | 20943.18 | 24-MAR-21:10 | 13.00 | 11.77 | 0.191806E+11 | 11347.84 | 14-MAR-03:20 | 13.00 | 11.77 |
April | 0.396173E+11 | 21808.03 | 26-APR-21:52 | 16.00 | 15.39 | 0.186615E+11 | 11348.97 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.414893E+11 | 22126.63 | 04-MAY-21:10 | 17.00 | 15.07 | 0.193010E+11 | 11348.93 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.417144E+11 | 22329.30 | 27-JUN-21:52 | 17.00 | 16.37 | 0.187290E+11 | 11349.13 | 19-JUN-22:10 | 17.00 | 16.37 |
July | 0.440338E+11 | 22494.30 | 19-JUL-21:52 | 18.00 | 17.35 | 0.192884E+11 | 11349.10 | 05-JUL-22:10 | 18.00 | 17.35 |
August | 0.438233E+11 | 22318.93 | 18-AUG-21:52 | 19.00 | 17.66 | 0.193627E+11 | 11349.09 | 02-AUG-22:10 | 19.00 | 17.66 |
September | 0.410674E+11 | 22822.13 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186684E+11 | 11348.83 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.420074E+11 | 22555.39 | 04-OCT-21:53 | 21.00 | 18.98 | 0.192647E+11 | 11348.92 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.379616E+11 | 20910.76 | 10-NOV-22:14 | 15.00 | 13.80 | 0.185661E+11 | 11348.36 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.386177E+11 | 21279.47 | 05-DEC-22:54 | 18.00 | 9.37 | 0.190785E+11 | 11349.14 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.483380E+12 | 0.226399E+12 | ||||||||
Minimum of Months | 0.350861E+11 | 20696.76 | 13.00 | 9.37 | 0.173274E+11 | 11347.82 | 12.67 | 6.27 | ||
Maximum of Months | 0.440338E+11 | 22822.13 | 24.58 | 18.98 | 0.193627E+11 | 11349.14 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525747E+11 | 28397.33 | 14-JAN-11:45 | 26.00 | 11.78 | 0.187883E+11 | 11319.60 | 07-JAN-18:19 | 26.00 | 11.78 |
February | 0.473335E+11 | 28274.49 | 01-FEB-11:45 | 25.50 | 14.48 | 0.169974E+11 | 11319.70 | 25-FEB-18:19 | 11.00 | 9.85 |
March | 0.527249E+11 | 29060.64 | 19-MAR-10:45 | 19.67 | 15.35 | 0.188060E+11 | 11319.62 | 25-MAR-17:19 | 11.00 | 10.47 |
April | 0.525478E+11 | 29534.41 | 30-APR-10:33 | 25.67 | 16.97 | 0.182284E+11 | 11319.58 | 15-APR-17:19 | 25.67 | 16.97 |
May | 0.542658E+11 | 29215.25 | 04-MAY-10:33 | 22.00 | 15.73 | 0.188375E+11 | 11319.57 | 20-MAY-17:19 | 17.00 | 12.68 |
June | 0.535703E+11 | 29589.53 | 25-JUN-10:33 | 23.00 | 17.26 | 0.182420E+11 | 11319.62 | 17-JUN-17:19 | 23.00 | 17.26 |
July | 0.563422E+11 | 29992.11 | 23-JUL-10:33 | 25.67 | 20.39 | 0.188491E+11 | 11319.65 | 01-JUL-17:19 | 25.67 | 20.39 |
August | 0.564413E+11 | 29917.52 | 19-AUG-10:33 | 24.67 | 20.11 | 0.188567E+11 | 11319.65 | 19-AUG-17:19 | 23.67 | 17.53 |
September | 0.534956E+11 | 30353.72 | 30-SEP-10:50 | 30.78 | 17.57 | 0.182389E+11 | 11319.61 | 30-SEP-17:19 | 25.00 | 17.45 |
October | 0.548853E+11 | 30204.80 | 15-OCT-10:50 | 31.83 | 16.40 | 0.188429E+11 | 11319.60 | 14-OCT-17:19 | 31.83 | 16.40 |
November | 0.512084E+11 | 28967.04 | 19-NOV-11:45 | 26.00 | 15.39 | 0.182125E+11 | 11319.58 | 25-NOV-18:19 | 13.00 | 11.13 |
December | 0.525257E+11 | 28266.56 | 19-DEC-11:45 | 25.00 | 11.20 | 0.187974E+11 | 11319.67 | 02-DEC-18:19 | 25.00 | 11.20 |
Annual Sum or Average | 0.637915E+12 | 0.221697E+12 | ||||||||
Minimum of Months | 0.473335E+11 | 28266.56 | 19.67 | 11.20 | 0.169974E+11 | 11319.57 | 11.00 | 9.85 | ||
Maximum of Months | 0.564413E+11 | 30353.72 | 31.83 | 20.39 | 0.188567E+11 | 11319.70 | 31.83 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781302E+10 | 4348.34 | 06-JAN-23:00 | 5.00 | 2.03 | 0.134939E+10 | 872.64 | 18-JAN-22:40 | 16.33 | 13.19 |
February | 0.711494E+10 | 4128.13 | 01-FEB-11:33 | 25.00 | 14.29 | 0.121972E+10 | 851.66 | 01-FEB-22:40 | 13.00 | 11.48 |
March | 0.767019E+10 | 4261.27 | 11-MAR-11:33 | 24.00 | 13.82 | 0.134893E+10 | 869.73 | 24-MAR-21:40 | 13.00 | 11.48 |
April | 0.831000E+10 | 4445.40 | 30-APR-10:33 | 25.67 | 16.97 | 0.137033E+10 | 894.22 | 27-APR-21:40 | 25.67 | 16.97 |
May | 0.860108E+10 | 4512.89 | 04-MAY-10:33 | 22.00 | 15.73 | 0.141986E+10 | 916.97 | 04-MAY-21:40 | 17.00 | 15.07 |
June | 0.887776E+10 | 4579.97 | 30-JUN-10:33 | 23.33 | 17.95 | 0.143173E+10 | 923.73 | 27-JUN-21:40 | 23.33 | 17.95 |
July | 0.974975E+10 | 4814.29 | 30-JUL-10:33 | 24.67 | 20.10 | 0.152690E+10 | 940.54 | 31-JUL-21:40 | 18.80 | 17.92 |
August | 0.985770E+10 | 4803.61 | 19-AUG-10:33 | 24.67 | 20.11 | 0.154507E+10 | 945.42 | 18-AUG-21:40 | 24.67 | 20.11 |
September | 0.907684E+10 | 5237.17 | 30-SEP-13:40 | 32.00 | 17.36 | 0.144871E+10 | 971.36 | 29-SEP-21:40 | 32.00 | 17.36 |
October | 0.940541E+10 | 5126.36 | 16-OCT-13:00 | 34.10 | 16.81 | 0.150234E+10 | 975.94 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.804964E+10 | 4527.94 | 19-NOV-11:33 | 26.00 | 15.32 | 0.134090E+10 | 885.56 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.807155E+10 | 4363.68 | 19-DEC-11:33 | 25.00 | 11.16 | 0.135889E+10 | 882.86 | 05-DEC-22:40 | 25.00 | 11.16 |
Annual Sum or Average | 0.102598E+12 | 0.168628E+11 | ||||||||
Minimum of Months | 0.711494E+10 | 4128.13 | 5.00 | 2.03 | 0.121972E+10 | 851.66 | 13.00 | 11.10 | ||
Maximum of Months | 0.985770E+10 | 5237.17 | 34.10 | 20.11 | 0.154507E+10 | 975.94 | 32.00 | 20.11 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 207569.94 | 107.92 | 30-MAR-06:15 | 5.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 207569.94 | |||
Minimum of Months | 0.00 | 0.00 | 5.87 | |
Maximum of Months | 207569.94 | 107.92 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66406318.58 | 1110.54 | 25-JAN-16:04 | 15.00 |
February | 38332340.12 | 1111.73 | 23-FEB-16:04 | 14.00 |
March | 78561354.31 | 1117.29 | 21-MAR-18:04 | 13.83 |
April | 10469446.58 | 1093.48 | 17-APR-15:04 | 17.33 |
May | 7284989.14 | 1108.99 | 11-MAY-15:04 | 17.00 |
June | 1906113.76 | 1107.48 | 16-JUN-15:04 | 17.17 |
July | 1477135.42 | 1070.77 | 04-JUL-08:04 | 19.50 |
August | 1406110.86 | 829.12 | 03-AUG-08:04 | 21.17 |
September | 2386048.69 | 1067.62 | 21-SEP-18:04 | 19.00 |
October | 2719372.56 | 1104.79 | 23-OCT-15:04 | 17.00 |
November | 12848261.88 | 1084.97 | 09-NOV-16:04 | 17.83 |
December | 42539332.96 | 1093.69 | 11-DEC-16:04 | 13.83 |
Annual Sum or Average | 0.266337E+09 | |||
Minimum of Months | 1406110.86 | 829.12 | 13.83 | |
Maximum of Months | 78561354.31 | 1117.29 | 21.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147404E+09 | 1102.14 | 28-JAN-16:04 | 13.83 |
February | 65617858.62 | 1084.66 | 10-FEB-16:03 | 15.22 |
March | 0.104887E+09 | 1090.42 | 13-MAR-18:04 | 13.00 |
April | 11734924.28 | 1093.02 | 14-APR-15:04 | 17.67 |
May | 6088116.76 | 1104.32 | 08-MAY-18:14 | 14.67 |
June | 1138479.29 | 1092.01 | 08-JUN-15:04 | 18.00 |
July | 299007.01 | 606.70 | 08-JUL-08:54 | 19.00 |
August | 358121.09 | 669.61 | 22-AUG-08:53 | 19.00 |
September | 1734002.39 | 951.91 | 01-SEP-08:53 | 19.00 |
October | 1993801.75 | 1088.25 | 23-OCT-15:04 | 17.00 |
November | 37842517.36 | 1100.08 | 23-NOV-19:03 | 12.67 |
December | 0.109226E+09 | 1099.14 | 28-DEC-19:03 | 12.83 |
Annual Sum or Average | 0.488324E+09 | |||
Minimum of Months | 299007.01 | 606.70 | 12.67 | |
Maximum of Months | 0.147404E+09 | 1104.32 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1612408.35 | 297.07 | 10-JAN-09:03 | 12.67 |
February | 1433434.59 | 302.34 | 18-FEB-16:04 | 15.83 |
March | 1364998.64 | 305.24 | 16-MAR-15:05 | 15.83 |
April | 643101.96 | 301.00 | 18-APR-15:04 | 16.00 |
May | 665600.44 | 301.53 | 12-MAY-15:05 | 15.83 |
June | 222964.42 | 279.31 | 06-JUN-15:06 | 17.83 |
July | 47617.31 | 145.34 | 10-JUL-21:57 | 16.00 |
August | 76148.50 | 127.04 | 22-AUG-08:54 | 19.00 |
September | 392250.74 | 272.47 | 20-SEP-08:53 | 18.00 |
October | 466845.07 | 272.53 | 25-OCT-21:56 | 19.00 |
November | 1401484.33 | 300.62 | 24-NOV-16:03 | 15.83 |
December | 1345556.87 | 294.31 | 09-DEC-16:04 | 14.83 |
Annual Sum or Average | 9672411.22 | |||
Minimum of Months | 47617.31 | 127.04 | 12.67 | |
Maximum of Months | 1612408.35 | 305.24 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66237647.62 | 1071.41 | 31-JAN-16:04 | 14.67 |
February | 46281728.95 | 1077.23 | 18-FEB-16:04 | 15.83 |
March | 89071846.58 | 1071.23 | 03-MAR-16:04 | 14.83 |
April | 10389281.53 | 1083.00 | 18-APR-15:04 | 16.00 |
May | 9346464.27 | 1050.71 | 16-MAY-15:04 | 18.83 |
June | 2067375.51 | 1053.59 | 16-JUN-15:04 | 17.17 |
July | 304741.66 | 632.60 | 09-JUL-18:05 | 17.83 |
August | 354658.43 | 794.00 | 21-AUG-18:04 | 16.83 |
September | 1916690.38 | 1023.58 | 21-SEP-18:04 | 19.00 |
October | 1910233.43 | 1061.17 | 23-OCT-15:04 | 17.00 |
November | 18221085.91 | 1084.73 | 16-NOV-16:04 | 15.67 |
December | 49170455.79 | 1060.38 | 14-DEC-16:04 | 13.83 |
Annual Sum or Average | 0.295272E+09 | |||
Minimum of Months | 304741.66 | 632.60 | 13.83 | |
Maximum of Months | 89071846.58 | 1084.73 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141521E+09 | 1037.55 | 06-JAN-16:03 | 16.67 |
February | 82264151.24 | 1018.53 | 19-FEB-19:03 | 13.00 |
March | 0.118061E+09 | 1050.38 | 21-MAR-15:04 | 16.83 |
April | 12820463.02 | 1049.99 | 17-APR-15:04 | 17.33 |
May | 8451591.33 | 1030.23 | 16-MAY-15:04 | 18.83 |
June | 1107269.77 | 1034.45 | 08-JUN-15:04 | 18.00 |
July | 205791.59 | 422.36 | 08-JUL-21:14 | 15.00 |
August | 208332.37 | 490.73 | 22-AUG-21:55 | 16.30 |
September | 1205709.30 | 827.21 | 18-SEP-15:04 | 19.83 |
October | 2235387.91 | 1031.41 | 23-OCT-15:04 | 17.00 |
November | 50156066.36 | 1060.89 | 22-NOV-16:03 | 15.67 |
December | 0.117412E+09 | 1044.20 | 27-DEC-19:03 | 14.17 |
Annual Sum or Average | 0.535649E+09 | |||
Minimum of Months | 205791.59 | 422.36 | 13.00 | |
Maximum of Months | 0.141521E+09 | 1060.89 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167736E+09 | 1277.65 | 16-JAN-16:04 | 18.00 |
February | 0.122210E+09 | 1146.27 | 25-FEB-16:03 | 11.00 |
March | 0.179473E+09 | 1184.24 | 30-MAR-08:62 | 9.50 |
April | 29257543.08 | 1244.20 | 17-APR-15:04 | 17.33 |
May | 23885735.04 | 1293.85 | 11-MAY-15:04 | 17.00 |
June | 2862169.12 | 1291.85 | 16-JUN-15:04 | 17.17 |
July | 1329536.35 | 1036.31 | 26-JUL-08:04 | 21.17 |
August | 1152563.36 | 921.06 | 03-AUG-08:04 | 21.17 |
September | 2517589.56 | 1027.32 | 21-SEP-18:04 | 19.00 |
October | 10963224.66 | 1287.49 | 23-OCT-15:04 | 17.00 |
November | 67302892.82 | 1078.65 | 09-NOV-16:04 | 17.83 |
December | 0.140950E+09 | 1254.49 | 17-DEC-19:03 | 13.17 |
Annual Sum or Average | 0.749640E+09 | |||
Minimum of Months | 1152563.36 | 921.06 | 9.50 | |
Maximum of Months | 0.179473E+09 | 1293.85 | 21.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318586E+09 | 1255.49 | 20-JAN-16:04 | 16.83 |
February | 0.190134E+09 | 1185.33 | 09-FEB-09:01 | 11.90 |
March | 0.228843E+09 | 1277.41 | 18-MAR-15:04 | 16.83 |
April | 31157212.57 | 1250.38 | 14-APR-15:04 | 17.67 |
May | 18346817.01 | 1284.34 | 11-MAY-15:04 | 17.00 |
June | 1210298.87 | 1273.24 | 08-JUN-15:04 | 18.00 |
July | 281125.06 | 615.46 | 08-JUL-08:54 | 19.00 |
August | 377667.67 | 959.51 | 22-AUG-08:53 | 19.00 |
September | 1771334.62 | 882.76 | 11-SEP-08:53 | 21.00 |
October | 14720207.00 | 1262.18 | 23-OCT-15:04 | 17.00 |
November | 0.136871E+09 | 1286.40 | 30-NOV-19:03 | 13.67 |
December | 0.277140E+09 | 1205.04 | 15-DEC-09:01 | 12.33 |
Annual Sum or Average | 0.121944E+10 | |||
Minimum of Months | 281125.06 | 615.46 | 11.90 | |
Maximum of Months | 0.318586E+09 | 1286.40 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8738391.88 | 435.65 | 31-JAN-19:05 | 11.83 |
February | 8422883.55 | 469.33 | 25-FEB-09:04 | 11.17 |
March | 31901207.88 | 689.42 | 20-MAR-15:04 | 15.67 |
April | 4483051.31 | 685.39 | 17-APR-15:04 | 17.33 |
May | 6140675.19 | 674.74 | 09-MAY-15:04 | 16.17 |
June | 1694439.33 | 666.29 | 16-JUN-15:04 | 17.17 |
July | 950630.29 | 643.43 | 08-JUL-18:04 | 17.83 |
August | 463616.01 | 419.31 | 22-AUG-18:04 | 17.00 |
September | 1027345.35 | 477.52 | 22-SEP-18:04 | 18.00 |
October | 956336.34 | 677.46 | 23-OCT-15:04 | 17.00 |
November | 1091403.04 | 682.22 | 24-NOV-16:04 | 15.83 |
December | 5425123.10 | 612.68 | 17-DEC-19:04 | 13.17 |
Annual Sum or Average | 71295103.27 | |||
Minimum of Months | 463616.01 | 419.31 | 11.17 | |
Maximum of Months | 31901207.88 | 689.42 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130497E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.114673E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125376E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.113983E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.112129E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.107741E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.111560E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.115503E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.120189E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128074E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.124997E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.129666E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.143439E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.107741E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.130497E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.941787E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.847556E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.940788E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.900527E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929404E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.899654E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.924755E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.933252E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.906632E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.940530E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.911494E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.938557E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110149E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.847556E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.941787E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278781E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246232E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268528E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249776E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250863E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.240793E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.248899E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.255593E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.257519E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275378E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268255E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278872E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311949E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.240793E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.278872E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278781E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246232E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268528E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249776E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250863E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.240793E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.248899E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.255593E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.257519E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275378E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268255E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278872E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311949E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.240793E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.278872E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1030039.48 | 0.287464E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72274.42 | 0.248343E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.288243E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1242587.02 | 0.202698E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 130728.78 | 0.189046E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3014951.22 | 0.126793E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9395099.78 | 95372191.92 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7732073.50 | 97634823.18 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8048023.43 | 0.132475E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13957260.39 | 0.137851E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624280.28 | 0.246545E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 394808.96 | 0.278216E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45642128.27 | 0.233068E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 95372191.92 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13957260.39 | 0.288243E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 785395.32 | 0.117592E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99415.40 | 0.104754E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140981.87 | 0.121409E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 774239.60 | 90659692.01 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95753.10 | 88938113.71 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 738708.82 | 63582186.79 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255496.14 | 49538468.76 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3584531.50 | 48271701.67 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3216034.62 | 59945799.30 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6409353.24 | 62209893.25 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526151.48 | 0.104147E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 606601.45 | 0.114958E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20232662.54 | 0.102601E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95753.10 | 48271701.67 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6409353.24 | 0.121409E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2645782.57 | 0.254253E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 397245.87 | 0.226114E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 765401.52 | 0.265183E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2538646.18 | 0.194475E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309674.15 | 0.195989E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1507721.71 | 0.140958E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7246706.47 | 0.108916E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8716249.04 | 0.103574E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8232824.32 | 0.128024E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16181030.48 | 0.135550E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1938721.42 | 0.224747E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2591286.94 | 0.247357E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53071290.66 | 0.222514E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 309674.15 | 0.103574E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16181030.48 | 0.265183E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1564523.46 | 0.144056E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 243596.42 | 0.127444E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 459922.56 | 0.150095E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1529661.81 | 0.109093E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 221332.27 | 0.109509E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1049574.08 | 78048509.63 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4575944.34 | 59634198.20 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5490526.27 | 56669567.28 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4919773.85 | 70736267.90 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9567192.79 | 74908764.97 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152468.27 | 0.126414E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1540073.70 | 0.139609E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32314589.82 | 0.124622E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 221332.27 | 56669567.28 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9567192.79 | 0.150095E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 2616504.59 | 0.386371E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 367835.91 | 0.344807E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 470860.50 | 0.405475E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2608074.80 | 0.293637E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 400661.76 | 0.290769E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 3098660.89 | 0.201642E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 13679158.48 | 0.148978E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16279744.07 | 0.142242E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 12655301.75 | 0.180658E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 24451656.09 | 0.188363E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 2149324.27 | 0.333202E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 2249199.41 | 0.371851E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 81026982.50 | 0.328799E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 367835.91 | 0.142242E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 24451656.09 | 0.405475E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.130497E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2023667.21 | 0.706930E+09 |
February | 0.236489E+11 | 0.114673E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153669.51 | 0.619056E+09 |
March | 0.262800E+11 | 0.125376E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708595E+09 |
April | 0.253579E+11 | 0.113983E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2465672.66 | 0.522802E+09 |
May | 0.262123E+11 | 0.112129E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 363302.92 | 0.497614E+09 |
June | 0.254132E+11 | 0.107741E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6275501.84 | 0.352152E+09 |
July | 0.261570E+11 | 0.111560E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21171717.85 | 0.271713E+09 |
August | 0.262677E+11 | 0.115503E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18605543.58 | 0.271137E+09 |
September | 0.253456E+11 | 0.120189E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17076740.02 | 0.349894E+09 |
October | 0.261693E+11 | 0.128074E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30840187.77 | 0.363999E+09 |
November | 0.253025E+11 | 0.124997E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1382092.69 | 0.620569E+09 |
December | 0.261570E+11 | 0.129666E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 872625.04 | 0.687958E+09 |
Annual Sum or Average | 0.308468E+12 | 0.143439E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101231E+09 | 0.597242E+10 |
Minimum of Months | 0.236489E+11 | 0.107741E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271137E+09 |
Maximum of Months | 0.262800E+11 | 0.130497E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30840187.77 | 0.708595E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.941787E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9631619.31 | 0.200705E+10 |
February | 0.702046E+11 | 0.847556E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1138371.48 | 0.178468E+10 |
March | 0.780153E+11 | 0.940788E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1420766.28 | 0.205847E+10 |
April | 0.752779E+11 | 0.900527E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10811311.54 | 0.152858E+10 |
May | 0.778146E+11 | 0.929404E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1561569.27 | 0.150317E+10 |
June | 0.754422E+11 | 0.899654E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12810390.57 | 0.107621E+10 |
July | 0.776503E+11 | 0.924755E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55620527.08 | 0.829300E+09 |
August | 0.779788E+11 | 0.933252E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60057011.41 | 0.805510E+09 |
September | 0.752414E+11 | 0.906632E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51652378.15 | 0.100949E+10 |
October | 0.776868E+11 | 0.940530E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98953971.61 | 0.105533E+10 |
November | 0.751137E+11 | 0.911494E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5951218.48 | 0.177266E+10 |
December | 0.776503E+11 | 0.938557E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6179099.11 | 0.196102E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110149E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315788E+09 | 0.173915E+11 |
Minimum of Months | 0.702046E+11 | 0.847556E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1138371.48 | 0.805510E+09 |
Maximum of Months | 0.780153E+11 | 0.941787E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98953971.61 | 0.205847E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1074658.27 | 0.159382E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 189589.75 | 0.139485E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179766.80 | 0.166425E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 980314.73 | 0.115805E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91452.76 | 0.113347E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1222735.61 | 73213587.36 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5676173.46 | 48281599.93 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6685087.93 | 45130777.15 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6417832.67 | 64603724.23 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11222909.36 | 66290526.23 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 844064.25 | 0.133496E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 936418.25 | 0.152219E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35521003.84 | 0.127768E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91452.76 | 45130777.15 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11222909.36 | 0.166425E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1251076.82 | 0.156346E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220605.49 | 0.137664E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228027.85 | 0.165860E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 882538.32 | 0.120995E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62953.13 | 0.120899E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 820512.27 | 88069569.81 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4719169.07 | 67536941.35 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5471805.00 | 62395339.42 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6169592.86 | 74932692.82 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10776376.21 | 73981404.23 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 981524.08 | 0.132424E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1233571.95 | 0.149636E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32817753.04 | 0.135074E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62953.13 | 62395339.42 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10776376.21 | 0.165860E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69944190.71 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61922212.87 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71236181.28 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 585.52 | 56464088.62 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56636113.30 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44466372.57 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44411.60 | 37065887.59 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30152.00 | 35930854.38 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 657849.28 | 41388648.47 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127562.57 | 41796626.00 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 450.89 | 62009328.92 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68123236.76 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861011.86 | 0.646984E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35930854.38 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127562.57 | 71236181.28 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436765.95 | 43564494.62 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81572.64 | 38280470.37 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94492.90 | 46009273.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 325083.19 | 32165713.89 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33556.58 | 32131308.26 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 286645.66 | 22429760.40 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1441875.09 | 16365413.13 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1722416.28 | 15115517.34 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785823.94 | 19215962.68 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3212833.78 | 19748889.03 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 377607.83 | 36344400.73 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 470582.50 | 41475800.54 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10269256.35 | 0.362847E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33556.58 | 15115517.34 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3212833.78 | 46009273.00 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1045831.29 | 0.160217E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185839.17 | 0.139756E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171286.78 | 0.167171E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 941620.40 | 0.116483E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89406.99 | 0.113965E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1141141.36 | 73433800.89 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5580794.32 | 48683934.64 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6540513.37 | 45446228.57 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6391549.16 | 64596150.71 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11214270.68 | 66559937.26 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 830463.38 | 0.133939E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 922995.10 | 0.152781E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35055712.01 | 0.128303E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89406.99 | 45446228.57 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11214270.68 | 0.167171E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1175971.92 | 0.156467E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165867.49 | 0.137256E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 172435.78 | 0.165992E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 720748.04 | 0.119590E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60415.13 | 0.119423E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 735848.82 | 84196353.01 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4565954.15 | 64094015.17 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5222095.00 | 60023733.45 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6057008.31 | 72407116.48 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10433297.60 | 73214358.97 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 920247.83 | 0.131529E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1086760.18 | 0.149536E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31316650.25 | 0.133373E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60415.13 | 60023733.45 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10433297.60 | 0.165992E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1987671.23 | 0.195800E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290538.71 | 0.173157E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442510.57 | 0.202925E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1857611.36 | 0.147832E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267602.91 | 0.146463E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1550626.96 | 0.102760E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6254284.88 | 78972938.05 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6954579.25 | 76667026.44 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6531803.52 | 95444151.71 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12409307.36 | 0.101438E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1353706.26 | 0.171755E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698714.18 | 0.190945E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41598957.18 | 0.168416E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267602.91 | 76667026.44 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12409307.36 | 0.202925E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1024433.86 | 0.159830E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 182993.61 | 0.139737E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165587.64 | 0.166905E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 920838.91 | 0.116704E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80108.34 | 0.114361E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1111929.33 | 74125573.19 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5423327.53 | 49097321.90 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6392286.62 | 45848770.33 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6310879.58 | 65379003.92 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11020902.56 | 66861612.03 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 812797.88 | 0.133974E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 898353.15 | 0.152588E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34344439.01 | 0.128541E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80108.34 | 45848770.33 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11020902.56 | 0.166905E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1234617.16 | 0.156119E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 229180.24 | 0.137601E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 199798.78 | 0.166521E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 800680.67 | 0.122945E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54941.26 | 0.122829E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 736980.50 | 90947304.75 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4510107.98 | 70575533.09 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5220924.61 | 64826893.75 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6094085.95 | 76014570.63 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10676922.50 | 73917942.30 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 992795.71 | 0.132238E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1274461.67 | 0.149147E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32025497.02 | 0.136368E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54941.26 | 64826893.75 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10676922.50 | 0.166521E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489694.05 | 83112665.92 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90012.66 | 72712600.92 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79948.82 | 86464972.95 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 464688.57 | 59868692.17 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41383.18 | 58271810.47 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 585807.91 | 37555303.64 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2801315.75 | 24917369.87 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3262887.84 | 23362054.54 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3221616.41 | 33430619.66 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5598551.23 | 34498253.24 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392339.76 | 69553430.86 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 443824.35 | 79378403.77 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17472070.54 | 0.663126E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41383.18 | 23362054.54 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5598551.23 | 86464972.95 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.278781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1325586.58 | 0.481498E+09 |
February | 0.415303E+11 | 0.246232E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202068.09 | 0.432245E+09 |
March | 0.461508E+11 | 0.268528E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55939.37 | 0.507189E+09 |
April | 0.445315E+11 | 0.249776E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 911252.36 | 0.379552E+09 |
May | 0.460320E+11 | 0.250863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28195.09 | 0.379993E+09 |
June | 0.446286E+11 | 0.240793E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 283174.48 | 0.275323E+09 |
July | 0.459349E+11 | 0.248899E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5030302.83 | 0.210390E+09 |
August | 0.461292E+11 | 0.255593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5925298.46 | 0.200215E+09 |
September | 0.445099E+11 | 0.257519E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10036451.69 | 0.248879E+09 |
October | 0.459565E+11 | 0.275378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20151207.95 | 0.254387E+09 |
November | 0.444343E+11 | 0.268255E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1151954.18 | 0.420567E+09 |
December | 0.459349E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1202919.36 | 0.466374E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311949E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 46304350.44 | 0.425661E+10 |
Minimum of Months | 0.415303E+11 | 0.240793E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28195.09 | 0.200215E+09 |
Maximum of Months | 0.461508E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20151207.95 | 0.507189E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.278781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1003182.90 | 0.488119E+09 |
February | 0.415303E+11 | 0.246232E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153956.95 | 0.437904E+09 |
March | 0.461508E+11 | 0.268528E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7985.04 | 0.514041E+09 |
April | 0.445315E+11 | 0.249776E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 763836.88 | 0.383495E+09 |
May | 0.460320E+11 | 0.250863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.87 | 0.383768E+09 |
June | 0.446286E+11 | 0.240793E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137384.15 | 0.277826E+09 |
July | 0.459349E+11 | 0.248899E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4504290.12 | 0.211833E+09 |
August | 0.461292E+11 | 0.255593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5233969.97 | 0.201635E+09 |
September | 0.445099E+11 | 0.257519E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9879807.33 | 0.251388E+09 |
October | 0.459565E+11 | 0.275378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19481617.16 | 0.256661E+09 |
November | 0.444343E+11 | 0.268255E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 978198.34 | 0.425572E+09 |
December | 0.459349E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 882764.89 | 0.472495E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311949E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 43032515.58 | 0.430474E+10 |
Minimum of Months | 0.415303E+11 | 0.240793E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.87 | 0.201635E+09 |
Maximum of Months | 0.461508E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19481617.16 | 0.514041E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 602788.56 | 0.433293E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 79934.77 | 0.389936E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456010E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 607355.04 | 0.340506E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340282E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 43409.95 | 0.246318E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3741413.80 | 0.187272E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4236042.54 | 0.178524E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8797263.55 | 0.223509E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16668172.63 | 0.227433E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 744952.40 | 0.378183E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 450811.75 | 0.418324E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 35972144.99 | 0.381959E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178524E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16668172.63 | 0.456010E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2554031.08 | 0.346980E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379249.33 | 0.304981E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369285.23 | 0.362393E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1856608.06 | 0.266709E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99863.03 | 0.263366E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002444.83 | 0.187856E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7305727.89 | 0.144726E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7925135.55 | 0.139409E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10093778.31 | 0.172167E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19258090.50 | 0.178110E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1782459.05 | 0.299371E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2084316.04 | 0.333630E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54710988.90 | 0.299970E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99863.03 | 0.139409E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19258090.50 | 0.362393E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 | 17-JAN-11:55 | 244.89 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 01-FEB-12:00 | 196.97 | 04-FEB-05:55 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-11:00 | 210.81 | 08-MAR-02:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 30-APR-10:55 | 170.90 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 03-MAY-12:00 | 158.98 | 15-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 | 29-JUN-10:55 | 121.19 | 13-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 | 19-JUL-10:55 | 101.81 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.34 | 14-AUG-10:55 | 92.67 | 28-AUG-03:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 29-SEP-10:55 | 123.30 | 20-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 16-OCT-10:55 | 149.90 | 30-OCT-03:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 19-NOV-13:00 | 182.24 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 | 16-DEC-13:00 | 197.47 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 244.89 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 13-JAN-14:00 | 96.83 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 01-FEB-11:55 | 82.39 | 04-FEB-05:55 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 11-MAR-11:50 | 83.40 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 26-APR-13:00 | 68.38 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 03-MAY-12:00 | 69.25 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 | 29-JUN-10:55 | 55.59 | 13-JUN-04:40 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 | 19-JUL-10:55 | 48.32 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 14-AUG-10:55 | 43.37 | 28-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.27 | 29-SEP-10:55 | 56.70 | 20-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 | 16-OCT-10:55 | 66.50 | 27-OCT-04:20 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 19-NOV-13:00 | 78.77 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 16-DEC-13:00 | 81.61 | 03-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 43.37 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 | 96.83 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 13-JAN-14:00 | 228.86 | 08-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 | 01-FEB-11:55 | 187.35 | 04-FEB-05:55 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 11-MAR-11:55 | 192.30 | 08-MAR-02:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.26 | 26-APR-13:00 | 155.87 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 03-MAY-12:00 | 156.61 | 27-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 | 29-JUN-10:55 | 124.71 | 13-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.47 | 19-JUL-10:55 | 107.94 | 06-JUL-01:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 14-AUG-10:55 | 95.89 | 28-AUG-06:50 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 29-SEP-10:55 | 124.88 | 20-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.74 | 16-OCT-10:55 | 148.79 | 12-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 | 19-NOV-13:00 | 174.45 | 29-NOV-23:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 16-DEC-13:00 | 186.52 | 03-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 95.89 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 139.74 | 228.86 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 13-JAN-14:00 | 132.04 | 08-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 01-FEB-11:55 | 107.07 | 04-FEB-05:55 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 11-MAR-11:50 | 110.95 | 08-MAR-02:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 26-APR-13:00 | 89.93 | 01-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 03-MAY-12:00 | 88.97 | 27-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 29-JUN-10:55 | 70.73 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 19-JUL-10:55 | 60.76 | 06-JUL-01:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 | 14-AUG-10:55 | 53.56 | 28-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.53 | 29-SEP-10:55 | 70.91 | 20-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 | 16-OCT-10:55 | 84.41 | 27-OCT-04:05 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 19-NOV-13:00 | 98.22 | 29-NOV-23:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 16-DEC-13:00 | 105.92 | 03-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 53.56 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 | 132.04 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 67.35 | 14-JAN-11:50 | 300.56 | 08-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 60.31 | 01-FEB-11:55 | 258.57 | 06-FEB-23:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 39.24 | 11-MAR-11:50 | 277.63 | 29-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 65.66 | 26-APR-13:00 | 226.76 | 15-APR-22:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 27.87 | 04-MAY-12:00 | 220.88 | 15-MAY-05:08 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 51.99 | 29-JUN-10:50 | 186.41 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 94.42 | 19-JUL-10:50 | 144.97 | 08-JUL-24:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 94.78 | 14-AUG-10:50 | 147.79 | 28-AUG-07:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 202.86 | 29-SEP-10:50 | 179.21 | 20-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 213.39 | 16-OCT-10:50 | 226.36 | 12-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 65.42 | 19-NOV-13:10 | 259.59 | 23-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 57.36 | 16-DEC-13:00 | 275.22 | 12-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 27.87 | 144.97 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 213.39 | 300.56 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 17-JAN-11:55 | 554.63 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.53 | 01-FEB-12:00 | 469.14 | 04-FEB-05:55 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 471.22 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 | 26-APR-13:00 | 386.00 | 04-APR-04:05 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 03-MAY-12:00 | 395.64 | 19-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.77 | 29-JUN-10:55 | 327.04 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.79 | 19-JUL-10:55 | 278.78 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.69 | 14-AUG-10:55 | 257.22 | 28-AUG-03:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.34 | 29-SEP-10:55 | 332.55 | 20-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.37 | 16-OCT-10:55 | 391.81 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.61 | 19-NOV-13:00 | 446.88 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 16-DEC-13:00 | 461.64 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.22 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 317.37 | 554.63 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.93 | 13-JAN-14:00 | 1584.46 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.82 | 01-FEB-11:55 | 1384.53 | 04-FEB-05:55 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.52 | 11-MAR-11:50 | 1394.81 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.72 | 26-APR-13:00 | 1158.69 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.69 | 03-MAY-12:00 | 1171.15 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 | 29-JUN-10:55 | 962.44 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.19 | 19-JUL-10:55 | 818.98 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.88 | 14-AUG-10:55 | 742.93 | 28-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 911.26 | 29-SEP-10:55 | 965.80 | 20-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 951.70 | 16-OCT-10:55 | 1131.37 | 27-OCT-04:20 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.26 | 19-NOV-13:00 | 1308.08 | 29-NOV-23:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.79 | 16-DEC-13:00 | 1354.97 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 94.52 | 742.93 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 951.70 | 1584.46 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:51 | 115.41 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 15-AUG-10:00 | 53.85 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-09:55 | 100.72 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 53.85 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 01-FEB-11:55 | 115.40 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.44 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 19-JUL-10:00 | 64.55 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 15-AUG-10:00 | 61.99 | 21-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.89 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 16-OCT-10:01 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-09:58 | 100.71 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 61.99 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 146.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 50.11 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 42.05 | 04-FEB-05:55 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 43.69 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 26-APR-13:00 | 34.81 | 15-APR-22:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 34.91 | 27-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 29.23 | 13-JUN-04:05 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 19-JUL-12:00 | 26.16 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 18-AUG-12:00 | 24.45 | 24-AUG-02:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 29-SEP-11:00 | 30.08 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 16-OCT-10:55 | 34.70 | 29-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 19-NOV-13:00 | 39.13 | 23-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 43.39 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 50.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 14-JAN-11:00 | 40.94 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 01-FEB-11:55 | 32.21 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 11-MAR-11:00 | 34.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 26-APR-13:00 | 27.98 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 03-MAY-10:00 | 26.18 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 30-JUN-10:00 | 19.93 | 13-JUN-04:30 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 19-JUL-10:00 | 17.36 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 15-AUG-10:00 | 16.47 | 21-AUG-20:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 29-SEP-10:00 | 19.79 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 16-OCT-10:01 | 24.11 | 30-OCT-03:40 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 19-NOV-09:58 | 28.11 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 05-DEC-10:00 | 32.29 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 16.47 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 40.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:51 | 115.41 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 26-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 15-AUG-10:00 | 59.86 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 100.72 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 56.57 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-10:00 | 115.40 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.44 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.24 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 58.64 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 15-AUG-10:00 | 59.86 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.89 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 19-NOV-10:00 | 100.71 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 58.64 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 146.70 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 13-JAN-14:00 | 176.44 | 08-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 01-FEB-11:55 | 144.80 | 04-FEB-05:55 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 11-MAR-11:50 | 148.32 | 08-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 | 26-APR-13:00 | 120.29 | 01-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 03-MAY-12:00 | 119.11 | 27-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 29-JUN-10:55 | 93.94 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 19-JUL-10:55 | 81.58 | 06-JUL-01:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 14-AUG-10:55 | 72.97 | 24-AUG-02:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.08 | 29-SEP-10:55 | 95.73 | 20-SEP-03:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 | 16-OCT-10:55 | 114.19 | 30-OCT-03:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 19-NOV-13:00 | 131.69 | 29-NOV-23:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.45 | 16-DEC-13:00 | 143.57 | 03-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 72.97 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 | 176.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 14-JAN-11:00 | 147.18 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 01-FEB-09:51 | 115.86 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 11-MAR-11:00 | 123.90 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 30-APR-10:00 | 100.69 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 03-MAY-10:00 | 93.79 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 30-JUN-10:00 | 71.83 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 19-JUL-10:00 | 56.99 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 15-AUG-10:00 | 52.55 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.78 | 29-SEP-10:00 | 71.33 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 | 16-OCT-10:00 | 86.28 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-09:53 | 101.16 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 | 05-DEC-09:55 | 116.15 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 52.55 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 | 147.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 14-JAN-11:00 | 147.17 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | 01-FEB-11:55 | 115.85 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 11-MAR-11:00 | 123.89 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 30-APR-10:00 | 100.69 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 03-MAY-10:00 | 93.79 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 30-JUN-10:00 | 72.06 | 02-JUN-20:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 19-JUL-10:00 | 68.99 | 10-JUL-18:01 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 15-AUG-10:00 | 67.12 | 26-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 29-SEP-10:00 | 71.32 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 16-OCT-10:01 | 86.27 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-10:00 | 101.16 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 | 05-DEC-10:00 | 116.14 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 67.12 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 147.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 14-JAN-11:00 | 75.30 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 01-FEB-09:51 | 59.28 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 11-MAR-11:00 | 63.39 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 30-APR-10:00 | 51.52 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 03-MAY-10:00 | 47.99 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 30-JUN-10:00 | 36.75 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 19-JUL-10:00 | 29.16 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 15-AUG-10:00 | 27.61 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 29-SEP-10:00 | 36.49 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 16-OCT-10:00 | 44.50 | 30-OCT-03:40 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 19-NOV-10:30 | 51.97 | 30-NOV-02:70 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 05-DEC-10:00 | 59.42 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 27.61 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 75.30 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.45 | 13-JAN-14:00 | 361.55 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 01-FEB-11:55 | 322.21 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 11-MAR-11:40 | 331.11 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.32 | 26-APR-13:00 | 288.78 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 03-MAY-12:00 | 278.98 | 15-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 | 29-JUN-10:55 | 224.92 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.74 | 19-JUL-10:55 | 188.00 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | 14-AUG-10:55 | 170.32 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.24 | 29-SEP-10:55 | 223.35 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.34 | 16-OCT-10:55 | 260.40 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 19-NOV-13:00 | 297.09 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 19-DEC-13:00 | 317.74 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 170.32 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 212.34 | 361.55 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 | 13-JAN-14:00 | 363.79 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 01-FEB-11:55 | 324.09 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 11-MAR-11:40 | 334.35 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 26-APR-13:00 | 292.47 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 03-MAY-12:00 | 278.99 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 29-JUN-10:55 | 224.92 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.13 | 19-JUL-10:55 | 188.00 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 | 14-AUG-10:55 | 170.32 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.91 | 29-SEP-10:55 | 223.35 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.79 | 16-OCT-10:55 | 260.40 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 19-NOV-13:00 | 297.15 | 24-NOV-01:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | 19-DEC-13:00 | 320.59 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 170.32 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 209.79 | 363.79 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 27.84 | 14-JAN-11:00 | 321.59 | 03-JAN-07:10 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.67 | 01-FEB-11:55 | 270.68 | 09-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 292.32 | 29-MAR-22:50 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 42.05 | 26-APR-13:00 | 264.61 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 248.79 | 19-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 13.22 | 29-JUN-10:55 | 201.36 | 13-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 56.41 | 19-JUL-12:00 | 159.38 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 56.52 | 18-AUG-12:00 | 152.01 | 28-AUG-06:10 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 167.08 | 29-SEP-11:10 | 190.55 | 20-SEP-03:20 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 180.85 | 16-OCT-11:00 | 232.83 | 12-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 42.11 | 19-NOV-13:00 | 265.87 | 23-NOV-22:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 27.93 | 16-DEC-13:00 | 298.95 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 152.01 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 180.85 | 321.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 | 14-JAN-11:00 | 311.89 | 08-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 | 01-FEB-11:55 | 246.24 | 04-FEB-05:55 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 11-MAR-11:00 | 263.41 | 08-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 | 26-APR-13:00 | 213.78 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 03-MAY-12:00 | 205.05 | 27-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 29-JUN-10:55 | 162.66 | 13-JUN-04:05 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.93 | 19-JUL-10:55 | 141.63 | 06-JUL-01:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 14-AUG-10:55 | 127.00 | 28-AUG-03:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.83 | 29-SEP-10:55 | 163.59 | 20-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.04 | 16-OCT-10:55 | 195.22 | 27-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.16 | 19-NOV-13:00 | 228.35 | 29-NOV-23:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 | 16-DEC-13:00 | 246.81 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 127.00 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.04 | 311.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22039.30 | 08-JAN-07:00 | 8945.92 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17075.64 | 04-FEB-05:55 | 23003.78 | 2931.30 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17459.17 | 08-MAR-02:00 | 11501.89 | 2198.39 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14831.77 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14516.97 | 28-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14720.82 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15579.95 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15573.18 | 06-AUG-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16136.23 | 30-SEP-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16963.10 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17143.44 | 22-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18064.07 | 03-DEC-00:55 | 17891.83 | 8793.54 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14516.97 | 8945.92 | 2198.39 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22039.30 | 23003.78 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3235.98 | 14-JAN-12:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
February | 2853.54 | 02-FEB-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 |
March | 2513.48 | 11-MAR-13:00 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
April | 2005.10 | 08-APR-10:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
May | 1948.75 | 04-MAY-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
June | 1873.81 | 25-JUN-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 0.00 |
July | 2052.57 | 30-JUL-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 | 0.00 |
August | 2128.52 | 27-AUG-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
September | 3462.92 | 30-SEP-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 0.00 |
October | 4079.22 | 16-OCT-12:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 0.00 |
November | 3601.89 | 19-NOV-12:30 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 0.00 |
December | 3437.42 | 19-DEC-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1873.81 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4079.22 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 54.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1676.89 | 28-JAN-07:00 | 1053.36 | 230.67 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.94 |
February | 1550.97 | 04-FEB-05:55 | 2708.64 | 153.78 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.39 |
March | 1561.51 | 08-MAR-02:00 | 1354.32 | 115.34 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.40 |
April | 1481.64 | 27-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.06 |
May | 1490.45 | 03-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 |
June | 1546.33 | 30-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 |
July | 1656.94 | 31-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 |
August | 1724.42 | 18-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 |
September | 1928.89 | 29-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
October | 1976.92 | 16-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
November | 1539.55 | 29-NOV-23:00 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 |
December | 1538.80 | 03-DEC-00:55 | 2106.72 | 461.34 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1481.64 | 1053.36 | 115.34 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1976.92 | 2708.64 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 87.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1252.31 | 27-JAN-04:55 | 572.83 | 152.04 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.41 |
February | 1172.63 | 04-FEB-05:55 | 572.83 | 152.04 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.35 |
March | 1067.06 | 07-MAR-23:00 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.61 |
April | 1107.99 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 0.00 |
May | 1122.39 | 04-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
June | 1168.63 | 25-JUN-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
July | 1220.40 | 23-JUL-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.62 | 0.00 |
August | 1214.66 | 19-AUG-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 0.00 |
September | 1251.07 | 30-SEP-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 0.00 |
October | 1246.30 | 16-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 132.57 | 0.00 |
November | 1115.71 | 29-NOV-23:00 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.45 |
December | 1174.65 | 03-DEC-00:55 | 445.54 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1067.06 | 190.94 | 152.04 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1252.31 | 572.83 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 132.57 | 196.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 716.45 | 27-JAN-04:55 | 440.64 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.11 |
February | 672.04 | 04-FEB-05:55 | 440.64 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.07 |
March | 599.76 | 23-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
April | 638.30 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.00 |
May | 646.21 | 04-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
June | 670.77 | 25-JUN-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 0.00 |
July | 701.52 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 0.00 |
August | 697.87 | 19-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 0.00 |
September | 723.20 | 30-SEP-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
October | 722.83 | 16-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 76.73 | 0.00 |
November | 636.33 | 19-NOV-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 | 0.00 |
December | 665.90 | 03-DEC-00:55 | 342.72 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 599.76 | 146.88 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 723.20 | 440.64 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 76.73 | 112.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37510.91 | 24-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 |
February | 37408.81 | 03-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 |
March | 37602.79 | 23-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.51 |
April | 37878.56 | 26-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
May | 37899.22 | 04-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
June | 37909.20 | 30-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.91 |
July | 38155.41 | 19-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 |
August | 38119.76 | 18-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.06 |
September | 38405.20 | 29-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.19 | 0.00 |
October | 38253.45 | 16-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 |
November | 37409.85 | 28-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 |
December | 37642.11 | 05-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37408.81 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38405.20 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.19 | 164.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12684.27 | 14-JAN-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
February | 10751.21 | 20-FEB-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.88 |
March | 10449.86 | 11-MAR-12:50 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
April | 9149.78 | 08-APR-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 |
May | 8767.13 | 04-MAY-21:20 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.59 |
June | 8608.33 | 25-JUN-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 |
July | 9197.51 | 30-JUL-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
August | 9527.06 | 27-AUG-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
September | 12162.03 | 30-SEP-12:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 197.59 | 0.00 |
October | 13773.16 | 15-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 198.53 | 0.00 |
November | 14032.50 | 19-NOV-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 0.00 |
December | 12540.04 | 16-DEC-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8608.33 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14032.50 | 15368.40 | 1134.35 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 198.53 | 208.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37352.55 | 09-JAN-05:55 | 91245.96 | 4224.36 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526.21 |
February | 33501.66 | 04-FEB-05:55 | 91245.96 | 2112.18 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1384.53 |
March | 33463.56 | 08-MAR-02:00 | 45622.98 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.81 |
April | 31054.24 | 26-APR-21:52 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.08 |
May | 32021.87 | 04-MAY-21:53 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.32 |
June | 31939.38 | 30-JUN-21:52 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.32 |
July | 33402.29 | 19-JUL-21:52 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.54 |
August | 34122.84 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.32 |
September | 38120.54 | 29-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 | 0.00 |
October | 38613.24 | 16-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.88 |
November | 32583.17 | 29-NOV-23:00 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.08 |
December | 33671.80 | 05-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31054.24 | 45622.98 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38613.24 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 | 1526.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3310.36 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 |
February | 3321.30 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
March | 2875.30 | 15-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 |
April | 3070.09 | 01-APR-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 |
May | 3055.94 | 24-MAY-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 |
June | 3016.81 | 29-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
July | 2998.39 | 22-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
August | 2998.92 | 05-AUG-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
September | 2976.66 | 21-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 33.99 | 0.00 |
October | 3364.99 | 13-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.82 | 0.00 |
November | 3281.62 | 27-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 |
December | 3321.08 | 19-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2875.30 | 252.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3364.99 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 33.99 | 39.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3172.73 | 15-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
February | 3181.50 | 03-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
March | 2882.19 | 23-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 |
April | 3105.72 | 23-APR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.72 |
May | 3065.49 | 24-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 |
June | 2938.96 | 22-JUN-20:11 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.56 |
July | 2854.64 | 15-JUL-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
August | 2879.10 | 05-AUG-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
September | 2887.87 | 18-SEP-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 |
October | 3363.12 | 14-OCT-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 | 0.00 |
November | 3145.35 | 27-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
December | 3181.65 | 19-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2854.64 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3363.12 | 1602.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 | 64.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 571.00 | 14-JAN-12:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
February | 497.86 | 02-FEB-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
March | 419.27 | 11-MAR-13:10 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
April | 293.83 | 08-APR-12:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
May | 269.56 | 04-MAY-15:03 | 0.00 | 219.11 | 343.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
June | 187.50 | 30-JUN-07:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 |
July | 273.83 | 23-JUL-15:03 | 0.00 | 221.35 | 325.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
August | 283.49 | 30-AUG-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
September | 538.04 | 30-SEP-13:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 0.00 |
October | 650.39 | 16-OCT-12:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 |
November | 607.19 | 19-NOV-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 586.94 | 19-DEC-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 187.50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 650.39 | 0.00 | 221.35 | 343.13 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 16.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1105.03 | 15-JAN-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
February | 1070.07 | 03-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
March | 1035.38 | 10-MAR-19:12 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 |
April | 1087.38 | 01-APR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
May | 1063.46 | 24-MAY-08:51 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
June | 1032.81 | 22-JUN-20:11 | 1602.00 | 995.22 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
July | 1042.33 | 04-JUL-08:51 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
August | 1013.85 | 22-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
September | 1017.49 | 01-SEP-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 |
October | 1187.85 | 14-OCT-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
November | 1087.25 | 19-NOV-09:41 | 432.00 | 500.97 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 0.00 |
December | 1092.49 | 05-DEC-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1013.85 | 360.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1187.85 | 1602.00 | 995.22 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 17.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2955.54 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
February | 2967.68 | 01-FEB-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 |
March | 2637.60 | 22-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
April | 2914.58 | 02-APR-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 |
May | 2951.58 | 24-MAY-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 |
June | 2699.37 | 30-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 |
July | 2722.17 | 01-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
August | 2709.68 | 31-AUG-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
September | 2700.15 | 08-SEP-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 |
October | 3049.57 | 14-OCT-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 0.00 |
November | 2972.63 | 27-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
December | 2993.66 | 05-DEC-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2637.60 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3049.57 | 680.40 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 35.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2815.22 | 14-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 0.00 |
February | 2883.15 | 01-FEB-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
March | 2776.56 | 23-MAR-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.36 |
April | 3092.05 | 02-APR-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.79 |
May | 3183.94 | 24-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.19 |
June | 2996.46 | 14-JUN-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
July | 2999.77 | 04-JUL-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 |
August | 2881.31 | 22-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 |
September | 2917.41 | 12-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
October | 3413.27 | 17-OCT-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
November | 2828.00 | 28-NOV-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 |
December | 3065.13 | 05-DEC-09:41 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2776.56 | 252.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3413.27 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 43.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2582.25 | 28-JAN-07:00 | 1760.39 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 |
February | 2304.65 | 04-FEB-05:55 | 4526.71 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.80 |
March | 2161.22 | 08-MAR-01:00 | 2263.36 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.44 |
April | 2154.89 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
May | 2159.42 | 04-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
June | 2224.61 | 25-JUN-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 0.00 |
July | 2319.46 | 23-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 | 0.00 |
August | 2341.68 | 19-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 |
September | 2405.87 | 30-SEP-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 | 0.00 |
October | 2420.50 | 17-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 0.00 |
November | 2164.90 | 19-NOV-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 0.00 |
December | 2291.48 | 03-DEC-00:55 | 3520.78 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2154.89 | 1508.90 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2582.25 | 4526.71 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 157.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3424.84 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
February | 3430.17 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
March | 3040.74 | 15-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.48 |
April | 3196.08 | 01-APR-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 |
May | 3125.40 | 24-MAY-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 |
June | 3106.79 | 29-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
July | 3134.65 | 27-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 |
August | 3067.85 | 01-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 |
September | 3034.75 | 24-SEP-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
October | 3481.33 | 13-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 0.00 |
November | 3387.08 | 30-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 |
December | 3434.34 | 19-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3034.75 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3481.33 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 39.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3269.04 | 14-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 0.00 |
February | 3273.06 | 03-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 |
March | 3007.79 | 19-MAR-18:11 | 1053.00 | 1600.75 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 |
April | 3314.09 | 23-APR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 |
May | 3172.27 | 24-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
June | 3089.20 | 04-JUN-19:31 | 1053.00 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.47 |
July | 2974.90 | 08-JUL-21:11 | 1247.40 | 1360.64 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 |
August | 2859.67 | 05-AUG-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 2960.70 | 18-SEP-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 |
October | 3374.01 | 14-OCT-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 | 0.00 |
November | 3232.91 | 27-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 |
December | 3276.85 | 19-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2859.67 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3374.01 | 1247.40 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 | 69.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1870.60 | 14-JAN-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
February | 1860.80 | 03-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 |
March | 1627.43 | 24-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.22 |
April | 1740.91 | 01-APR-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
May | 1669.12 | 24-MAY-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
June | 1640.20 | 21-JUN-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
July | 1672.36 | 29-JUL-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 0.00 |
August | 1679.42 | 05-AUG-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 1647.33 | 21-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 |
October | 1878.26 | 26-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 1846.82 | 27-NOV-09:01 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
December | 1870.83 | 29-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1627.43 | 252.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1878.26 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 34.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19573.72 | 18-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 |
February | 18987.20 | 01-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
March | 19342.98 | 24-MAR-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.73 |
April | 20276.21 | 26-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 |
May | 20670.42 | 04-MAY-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.92 |
June | 20904.66 | 27-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.73 |
July | 21103.54 | 19-JUL-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
August | 20972.97 | 18-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
September | 21457.64 | 29-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
October | 21166.41 | 04-OCT-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
November | 19221.33 | 10-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.67 |
December | 19691.94 | 05-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18987.20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21457.64 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 187.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21236.21 | 18-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 |
February | 20696.76 | 01-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.95 |
March | 20943.18 | 24-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
April | 21808.03 | 26-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 |
May | 22126.63 | 04-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.86 |
June | 22329.30 | 27-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.73 |
July | 22494.30 | 19-JUL-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
August | 22318.93 | 18-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
September | 22822.13 | 29-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
October | 22555.39 | 04-OCT-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
November | 20910.76 | 10-NOV-22:14 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 |
December | 21279.47 | 05-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20696.76 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22822.13 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 187.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28397.33 | 14-JAN-11:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 27.78 | 0.00 |
February | 28274.49 | 01-FEB-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 20.45 | 0.00 |
March | 29060.64 | 19-MAR-10:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
April | 29534.41 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 22.90 | 0.00 |
May | 29215.25 | 04-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
June | 29589.53 | 25-JUN-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
July | 29992.11 | 23-JUL-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 22.98 | 0.00 |
August | 29917.52 | 19-AUG-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
September | 30353.72 | 30-SEP-10:50 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 93.96 | 0.00 |
October | 30204.80 | 15-OCT-10:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 109.40 | 0.00 |
November | 28967.04 | 19-NOV-11:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 27.71 | 0.00 |
December | 28266.56 | 19-DEC-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28266.56 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30353.72 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 109.40 | 65.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4348.34 | 06-JAN-23:00 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.85 |
February | 4128.13 | 01-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 0.00 |
March | 4261.27 | 11-MAR-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 |
April | 4445.40 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 0.00 |
May | 4512.89 | 04-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 |
June | 4579.97 | 30-JUN-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
July | 4814.29 | 30-JUL-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 | 0.00 |
August | 4803.61 | 19-AUG-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 0.00 |
September | 5237.17 | 30-SEP-13:40 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 0.00 |
October | 5126.36 | 16-OCT-13:00 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.28 | 0.00 |
November | 4527.94 | 19-NOV-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 | 0.00 |
December | 4363.68 | 19-DEC-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4128.13 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5237.17 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.28 | 250.85 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.382444E+12 | 272154.00 | 17-JAN-20:10 | 0.565423E+12 | 486523.70 | 06-JAN-20:10 |
February | 0.334797E+12 | 244857.62 | 13-FEB-19:19 | 0.496327E+12 | 482152.81 | 06-FEB-20:00 |
March | 0.366063E+12 | 259178.39 | 23-MAR-19:19 | 0.577403E+12 | 492643.28 | 29-MAR-17:00 |
April | 0.379584E+12 | 273111.91 | 26-APR-19:10 | 0.468671E+12 | 430647.26 | 15-APR-21:00 |
May | 0.390815E+12 | 271813.34 | 04-MAY-19:10 | 0.467822E+12 | 415681.50 | 10-MAY-20:49 |
June | 0.410233E+12 | 285348.13 | 29-JUN-19:10 | 0.395783E+12 | 377112.86 | 12-JUN-20:00 |
July | 0.479199E+12 | 317793.95 | 18-JUL-18:10 | 0.394399E+12 | 347199.29 | 24-JUL-17:10 |
August | 0.493544E+12 | 307420.23 | 14-AUG-19:10 | 0.394033E+12 | 347244.95 | 24-AUG-17:10 |
September | 0.437678E+12 | 347724.97 | 29-SEP-19:10 | 0.388201E+12 | 347590.32 | 27-SEP-17:49 |
October | 0.460676E+12 | 316333.80 | 04-OCT-19:00 | 0.426780E+12 | 382830.40 | 11-OCT-20:00 |
November | 0.375434E+12 | 259028.62 | 01-NOV-19:19 | 0.497622E+12 | 453553.32 | 04-NOV-20:10 |
December | 0.387466E+12 | 270445.76 | 05-DEC-20:10 | 0.560784E+12 | 486664.63 | 21-DEC-20:19 |
Annual Sum or Average | 0.489793E+13 | 0.563325E+13 | ||||
Minimum of Months | 0.334797E+12 | 244857.62 | 0.388201E+12 | 347199.29 | ||
Maximum of Months | 0.493544E+12 | 347724.97 | 0.577403E+12 | 492643.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.669826E+11 | 0.191147E+11 | 0.140828E+12 | 0.544238E+11 | 0.423010E+11 | 0.602671E+10 | 0.00 | 0.398327E+11 | 0.00 | 0.00 | 0.00 | 0.770519E+10 | 0.00 |
February | 0.603145E+11 | 0.163386E+11 | 0.127191E+12 | 0.491570E+11 | 0.381997E+11 | 0.551019E+10 | 0.00 | 0.263754E+11 | 0.00 | 0.00 | 0.00 | 0.696239E+10 | 0.00 |
March | 0.666141E+11 | 0.167457E+11 | 0.140882E+12 | 0.544262E+11 | 0.418564E+11 | 0.586573E+10 | 0.00 | 0.267035E+11 | 0.00 | 0.00 | 0.00 | 0.770383E+10 | 0.00 |
April | 0.641719E+11 | 0.148876E+11 | 0.136245E+12 | 0.526676E+11 | 0.418500E+11 | 0.632132E+10 | 0.00 | 0.508495E+11 | 0.00 | 0.00 | 0.00 | 0.746525E+10 | 0.00 |
May | 0.660709E+11 | 0.142139E+11 | 0.140860E+12 | 0.544246E+11 | 0.432718E+11 | 0.651132E+10 | 0.00 | 0.524530E+11 | 0.00 | 0.00 | 0.00 | 0.770478E+10 | 0.00 |
June | 0.638617E+11 | 0.131775E+11 | 0.136336E+12 | 0.526699E+11 | 0.430278E+11 | 0.621488E+10 | 0.00 | 0.823156E+11 | 0.00 | 0.00 | 0.00 | 0.745702E+10 | 0.00 |
July | 0.660419E+11 | 0.138734E+11 | 0.140770E+12 | 0.544221E+11 | 0.457083E+11 | 0.662828E+10 | 0.00 | 0.138707E+12 | 0.00 | 0.00 | 0.00 | 0.771273E+10 | 0.00 |
August | 0.661918E+11 | 0.148580E+11 | 0.140892E+12 | 0.544260E+11 | 0.461077E+11 | 0.669850E+10 | 0.00 | 0.151300E+12 | 0.00 | 0.00 | 0.00 | 0.770448E+10 | 0.00 |
September | 0.644665E+11 | 0.156427E+11 | 0.136256E+12 | 0.526679E+11 | 0.438212E+11 | 0.631788E+10 | 0.00 | 0.105862E+12 | 0.00 | 0.00 | 0.00 | 0.746654E+10 | 0.00 |
October | 0.668642E+11 | 0.175305E+11 | 0.140818E+12 | 0.544237E+11 | 0.460833E+11 | 0.664499E+10 | 0.00 | 0.115313E+12 | 0.00 | 0.00 | 0.00 | 0.770317E+10 | 0.00 |
November | 0.647710E+11 | 0.181597E+11 | 0.136330E+12 | 0.526689E+11 | 0.420087E+11 | 0.618213E+10 | 0.00 | 0.427857E+11 | 0.00 | 0.00 | 0.00 | 0.744934E+10 | 0.00 |
December | 0.669635E+11 | 0.194405E+11 | 0.140770E+12 | 0.544226E+11 | 0.427847E+11 | 0.613610E+10 | 0.00 | 0.440244E+11 | 0.00 | 0.00 | 0.00 | 0.771325E+10 | 0.00 |
Annual Sum or Average | 0.783315E+12 | 0.193983E+12 | 0.165818E+13 | 0.640800E+12 | 0.517021E+12 | 0.750580E+11 | 0.00 | 0.876524E+12 | 0.00 | 0.00 | 0.00 | 0.907480E+11 | 0.00 |
Minimum of Months | 0.603145E+11 | 0.131775E+11 | 0.127191E+12 | 0.491570E+11 | 0.381997E+11 | 0.551019E+10 | 0.00 | 0.263754E+11 | 0.00 | 0.00 | 0.00 | 0.696239E+10 | 0.00 |
Maximum of Months | 0.669826E+11 | 0.194405E+11 | 0.140892E+12 | 0.544262E+11 | 0.461077E+11 | 0.669850E+10 | 0.00 | 0.151300E+12 | 0.00 | 0.00 | 0.00 | 0.771325E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.156829E+12 | 0.00 | 0.256675E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.127079E+12 | 0.00 | 0.232044E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.170154E+12 | 0.00 | 0.255225E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.780577E+11 | 0.00 | 0.243657E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.680934E+11 | 0.00 | 0.247750E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.124033E+11 | 0.00 | 0.236266E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.801307E+09 | 0.00 | 0.241777E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.365491E+09 | 0.00 | 0.241629E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.568180E+10 | 0.00 | 0.235549E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.280920E+11 | 0.00 | 0.246784E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.107810E+12 | 0.00 | 0.242722E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.154511E+12 | 0.00 | 0.254452E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.909877E+12 | 0.00 | 0.293453E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.365491E+09 | 0.00 | 0.232044E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.170154E+12 | 0.00 | 0.256675E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 18-JAN-07:19 | 27164.48 | 18-JAN-22:00 | 2862.97 | 09-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.57 | 10-FEB-07:19 | 26059.39 | 01-FEB-22:10 | 2850.71 | 03-FEB-21:00 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 26084.94 | 23-MAR-21:10 | 2863.95 | 28-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.57 | 05-APR-06:19 | 27904.74 | 26-APR-21:00 | 2849.43 | 01-APR-06:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.18 | 09-MAY-06:19 | 28848.63 | 04-MAY-21:00 | 2847.45 | 14-MAY-04:40 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39169.18 | 16-JUN-06:19 | 29148.18 | 27-JUN-21:00 | 2819.74 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:10 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39169.18 | 12-JUL-06:19 | 30444.71 | 19-JUL-21:00 | 3348.52 | 18-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.57 | 21-AUG-06:19 | 30754.48 | 18-AUG-21:00 | 3332.40 | 14-AUG-10:50 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 18-SEP-06:19 | 32398.35 | 29-SEP-21:10 | 4278.15 | 29-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 05-OCT-06:19 | 34359.01 | 16-OCT-21:00 | 3794.07 | 17-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 27436.40 | 10-NOV-22:19 | 3123.77 | 19-NOV-10:00 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 08-DEC-07:19 | 29698.23 | 05-DEC-22:00 | 2856.43 | 25-DEC-02:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.18 | 26059.39 | 2819.74 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 34359.01 | 4278.15 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 80718.65 | 14-JAN-10:00 | 0.00 | 0.00 | 0.00 | 4738.73 | 23-JAN-19:10 | 0.00 |
February | 73460.65 | 01-FEB-11:50 | 0.00 | 0.00 | 0.00 | 4738.32 | 13-FEB-19:10 | 0.00 |
March | 77029.53 | 23-MAR-15:09 | 0.00 | 0.00 | 0.00 | 4738.43 | 09-MAR-19:10 | 0.00 |
April | 79919.51 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 4738.49 | 19-APR-18:10 | 0.00 |
May | 69349.18 | 04-MAY-15:09 | 0.00 | 0.00 | 0.00 | 4738.62 | 10-MAY-18:10 | 0.00 |
June | 89200.53 | 29-JUN-10:50 | 0.00 | 0.00 | 0.00 | 4738.51 | 29-JUN-06:00 | 0.00 |
July | 126118.86 | 19-JUL-15:20 | 0.00 | 0.00 | 0.00 | 4738.21 | 26-JUL-18:19 | 0.00 |
August | 134572.76 | 18-AUG-15:09 | 0.00 | 0.00 | 0.00 | 4738.28 | 25-AUG-06:19 | 0.00 |
September | 156051.00 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 4738.32 | 08-SEP-18:10 | 0.00 |
October | 163331.85 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 4738.28 | 16-OCT-18:10 | 0.00 |
November | 90741.35 | 19-NOV-10:00 | 0.00 | 0.00 | 0.00 | 4738.62 | 16-NOV-19:10 | 0.00 |
December | 83453.85 | 05-DEC-09:50 | 0.00 | 0.00 | 0.00 | 4738.59 | 11-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 69349.18 | 0.00 | 0.00 | 0.00 | 4738.21 | 0.00 | ||
Maximum of Months | 163331.85 | 0.00 | 0.00 | 0.00 | 4738.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 272154.00 | 17-JAN-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21624.46 | 2413.52 | 0.00 | 47706.36 | 0.00 |
February | 244857.62 | 13-FEB-19:19 | 57474.69 | 77573.37 | 12338.45 | 31354.49 | 21007.46 | 2433.55 | 0.00 | 35952.21 | 0.00 |
March | 259178.39 | 23-MAR-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 23862.66 | 2404.19 | 0.00 | 31628.92 | 0.00 |
April | 273111.91 | 26-APR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21033.56 | 2440.03 | 0.00 | 48352.58 | 0.00 |
May | 271813.34 | 04-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21182.07 | 2425.00 | 0.00 | 47194.60 | 0.00 |
June | 285348.13 | 29-JUN-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21277.63 | 2536.39 | 0.00 | 60464.94 | 0.00 |
July | 317793.95 | 18-JUL-18:10 | 54719.87 | 77573.37 | 0.00 | 31342.30 | 24528.93 | 3348.52 | 0.00 | 119914.34 | 0.00 |
August | 307420.23 | 14-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21442.00 | 2774.77 | 0.00 | 81942.60 | 0.00 |
September | 347724.97 | 29-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 27713.17 | 2866.06 | 0.00 | 116518.42 | 0.00 |
October | 316333.80 | 04-OCT-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 22459.07 | 2848.15 | 0.00 | 89784.58 | 0.00 |
November | 259028.62 | 01-NOV-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 23983.16 | 2429.68 | 0.00 | 31730.59 | 0.00 |
December | 270445.76 | 05-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22549.25 | 2388.76 | 0.00 | 45197.93 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 244857.62 | 54719.87 | 77573.37 | 0.00 | 31342.30 | 21007.46 | 2388.76 | 0.00 | 31628.92 | 0.00 | |
Maximum of Months | 347724.97 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 27713.17 | 3348.52 | 0.00 | 119914.34 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 200468.55 | 08-JAN-06:00 | 0.00 | 246234.18 | 30-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 153134.10 | 27-FEB-07:49 | 0.00 | 246302.21 | 13-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 185892.53 | 30-MAR-02:00 | 0.00 | 246094.50 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 152870.90 | 20-APR-03:00 | 0.00 | 245528.98 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 153595.19 | 27-MAY-04:00 | 0.00 | 244926.71 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 106955.27 | 13-JUN-03:00 | 0.00 | 244239.18 | 02-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 44563.94 | 06-JUL-02:00 | 0.00 | 243620.23 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 15284.33 | 28-AUG-03:00 | 0.00 | 243543.65 | 29-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 100662.10 | 20-SEP-03:00 | 0.00 | 244028.89 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 151285.38 | 28-OCT-04:00 | 0.00 | 244762.87 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 152848.03 | 04-NOV-19:49 | 0.00 | 245415.77 | 28-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 155123.26 | 23-DEC-05:00 | 0.00 | 245984.50 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 15284.33 | 0.00 | 243543.65 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 200468.55 | 0.00 | 246302.21 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.95 | 2.50 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.95 | 3.17 | 21.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.95 | 2.50 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.83 | 0.50 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.91 | 0.83 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 21.79 | 3.33 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.91 | 0.83 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.77 | 2.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.80 | 5.33 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.76 | 4.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.78 | 2.00 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 21.78 | 15.83 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.80 | 5.33 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.87 | 0.33 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.99 | 1.33 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.86 | 2.50 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.08 | 3.50 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.20 | 6.50 | 22.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.22 | 6.67 | 22.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.00 | 2.83 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.94 | 1.33 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.06 | 0.17 | 22.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 25.17 | 22.10 | 25.17 | 22.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.22 | 6.67 | 22.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.98 | 1.00 | 21.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.02 | 3.50 | 22.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 22.00 | 4.67 | 22.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.02 | 3.50 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.93 | 0.67 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.73 | 3.17 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.72 | 2.00 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.93 | 0.67 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.91 | 1.33 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.00 | 21.79 | 10.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.93 | 3.17 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.97 | 0.67 | 21.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.01 | 4.50 | 22.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
Annual Sum or Average | 0.00 | 0.00 | 6.33 | 21.96 | 6.33 | 21.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.01 | 4.50 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 681.67 | 23.10 | 5.33 | 23.10 | 0.00 | 23.10 |
February | 668.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
March | 744.00 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
April | 720.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
May | 744.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
June | 720.00 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
July | 743.67 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
August | 730.33 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
September | 570.00 | 23.10 | 7.67 | 23.11 | 0.00 | 23.11 |
October | 505.67 | 23.36 | 41.17 | 23.40 | 0.00 | 23.40 |
November | 554.33 | 23.44 | 15.33 | 23.45 | 0.00 | 23.45 |
December | 698.00 | 23.25 | 2.17 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 8080.50 | 22.85 | 71.67 | 22.86 | 0.00 | 22.86 |
Minimum of Months | 505.67 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
Maximum of Months | 744.00 | 23.44 | 41.17 | 23.45 | 0.00 | 23.45 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 595.67 | 21.60 | 90.50 | 21.88 | 8.33 | 21.87 |
February | 571.83 | 21.49 | 56.00 | 21.70 | 3.17 | 21.69 |
March | 671.83 | 21.36 | 49.17 | 21.50 | 6.33 | 21.50 |
April | 655.83 | 21.65 | 17.67 | 21.70 | 0.33 | 21.70 |
May | 737.50 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
June | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
July | 694.67 | 22.09 | 7.17 | 22.10 | 0.00 | 22.10 |
August | 556.33 | 22.26 | 102.50 | 22.45 | 0.00 | 22.45 |
September | 512.33 | 22.11 | 151.17 | 22.48 | 0.00 | 22.48 |
October | 510.33 | 22.15 | 155.33 | 22.56 | 0.00 | 22.56 |
November | 566.33 | 21.79 | 90.67 | 22.08 | 1.17 | 22.08 |
December | 580.00 | 21.70 | 82.67 | 21.98 | 0.83 | 21.98 |
Annual Sum or Average | 7372.67 | 21.76 | 802.83 | 21.95 | 20.17 | 21.95 |
Minimum of Months | 510.33 | 21.36 | 0.00 | 21.44 | 0.00 | 21.44 |
Maximum of Months | 737.50 | 22.26 | 155.33 | 22.56 | 8.33 | 22.56 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 715.50 | 22.50 | 6.50 | 22.51 | 0.00 | 22.51 |
February | 643.67 | 22.57 | 1.83 | 22.57 | 0.00 | 22.57 |
March | 720.67 | 22.34 | 5.00 | 22.35 | 0.00 | 22.35 |
April | 610.33 | 22.65 | 33.67 | 22.71 | 1.50 | 22.71 |
May | 658.17 | 22.63 | 21.33 | 22.67 | 0.00 | 22.67 |
June | 529.50 | 22.73 | 88.83 | 22.88 | 19.50 | 22.90 |
July | 426.67 | 22.93 | 246.83 | 23.23 | 86.83 | 23.27 |
August | 403.33 | 23.06 | 315.67 | 23.37 | 114.17 | 23.40 |
September | 387.83 | 22.94 | 184.00 | 23.21 | 34.67 | 23.22 |
October | 496.00 | 23.08 | 133.50 | 23.23 | 31.33 | 23.25 |
November | 646.00 | 22.86 | 14.33 | 22.88 | 0.00 | 22.88 |
December | 721.33 | 22.71 | 2.83 | 22.72 | 0.00 | 22.72 |
Annual Sum or Average | 6959.00 | 22.71 | 1054.33 | 22.85 | 288.00 | 22.88 |
Minimum of Months | 387.83 | 22.34 | 1.83 | 22.35 | 0.00 | 22.35 |
Maximum of Months | 721.33 | 23.08 | 315.67 | 23.37 | 114.17 | 23.40 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
February | 672.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
March | 744.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
April | 720.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
May | 744.00 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
June | 719.17 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
July | 716.50 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
August | 717.17 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
September | 714.50 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
October | 699.67 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
November | 720.00 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
December | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
Annual Sum or Average | 8655.00 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
Minimum of Months | 672.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
Maximum of Months | 744.00 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.56 | 2.67 | 21.55 | 2.67 | 21.55 |
February | 672.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
March | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
April | 720.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
May | 744.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
June | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
July | 744.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
August | 744.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
September | 718.83 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
October | 744.00 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
November | 720.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
December | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
Annual Sum or Average | 8758.83 | 22.11 | 2.67 | 22.11 | 2.67 | 22.11 |
Minimum of Months | 672.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
Maximum of Months | 744.00 | 22.74 | 2.67 | 22.74 | 2.67 | 22.74 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.50 | 22.96 | 558.83 | 23.11 | 194.17 | 23.27 |
February | 254.83 | 23.15 | 540.83 | 23.16 | 181.50 | 23.31 |
March | 306.33 | 23.11 | 593.83 | 23.11 | 218.50 | 23.29 |
April | 294.33 | 23.54 | 623.50 | 23.23 | 250.17 | 23.39 |
May | 305.67 | 23.52 | 648.67 | 23.23 | 257.67 | 23.39 |
June | 295.67 | 23.80 | 654.83 | 23.27 | 277.50 | 23.43 |
July | 297.67 | 23.96 | 703.00 | 23.26 | 296.83 | 23.43 |
August | 300.33 | 23.96 | 706.17 | 23.26 | 299.67 | 23.42 |
September | 290.50 | 23.84 | 661.50 | 23.27 | 277.67 | 23.43 |
October | 281.17 | 23.59 | 652.17 | 23.25 | 242.50 | 23.40 |
November | 284.83 | 23.24 | 581.50 | 23.22 | 212.00 | 23.37 |
December | 281.00 | 22.90 | 554.50 | 23.11 | 175.67 | 23.27 |
Annual Sum or Average | 3484.83 | 23.47 | 7479.33 | 23.21 | 2883.83 | 23.37 |
Minimum of Months | 254.83 | 22.90 | 540.83 | 23.11 | 175.67 | 23.27 |
Maximum of Months | 306.33 | 23.96 | 706.17 | 23.27 | 299.67 | 23.43 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.33 | 22.55 | 209.17 | 22.99 | 15.83 | 23.01 |
February | 417.33 | 22.48 | 154.33 | 22.82 | 12.50 | 22.83 |
March | 530.83 | 22.21 | 120.33 | 22.48 | 2.33 | 22.48 |
April | 422.33 | 22.58 | 173.17 | 22.86 | 33.67 | 22.91 |
May | 637.00 | 22.45 | 67.17 | 22.57 | 38.83 | 22.63 |
June | 583.00 | 22.61 | 174.33 | 22.86 | 137.00 | 22.99 |
July | 531.67 | 23.04 | 362.17 | 23.26 | 282.00 | 23.37 |
August | 399.50 | 23.49 | 539.50 | 23.52 | 315.67 | 23.59 |
September | 309.67 | 23.33 | 514.17 | 23.53 | 204.33 | 23.59 |
October | 263.83 | 23.09 | 421.00 | 23.54 | 87.33 | 23.59 |
November | 327.83 | 22.89 | 259.83 | 23.30 | 22.33 | 23.30 |
December | 408.33 | 22.74 | 189.00 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 5250.67 | 22.74 | 3184.17 | 23.10 | 1151.83 | 23.18 |
Minimum of Months | 263.83 | 22.21 | 67.17 | 22.48 | 0.00 | 22.48 |
Maximum of Months | 637.00 | 23.49 | 539.50 | 23.54 | 315.67 | 23.59 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 568.17 | 22.75 | 53.17 | 22.85 | 7.50 | 22.86 |
February | 528.33 | 22.82 | 40.50 | 22.89 | 5.50 | 22.89 |
March | 611.83 | 22.54 | 37.83 | 22.62 | 0.00 | 22.62 |
April | 473.17 | 22.71 | 122.33 | 22.94 | 13.83 | 22.97 |
May | 523.50 | 22.69 | 102.50 | 22.88 | 19.17 | 22.91 |
June | 434.50 | 22.82 | 251.83 | 23.19 | 94.17 | 23.27 |
July | 497.83 | 23.18 | 380.33 | 23.46 | 223.67 | 23.55 |
August | 486.17 | 23.40 | 408.50 | 23.61 | 283.00 | 23.68 |
September | 334.67 | 23.33 | 340.50 | 23.59 | 167.17 | 23.65 |
October | 296.17 | 23.27 | 259.67 | 23.54 | 63.50 | 23.59 |
November | 458.17 | 23.09 | 100.67 | 23.23 | 17.17 | 23.24 |
December | 606.83 | 23.03 | 31.00 | 23.07 | 0.00 | 23.07 |
Annual Sum or Average | 5819.33 | 22.94 | 2128.83 | 23.18 | 894.67 | 23.25 |
Minimum of Months | 296.17 | 22.54 | 31.00 | 22.62 | 0.00 | 22.62 |
Maximum of Months | 611.83 | 23.40 | 408.50 | 23.61 | 283.00 | 23.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.00 | 21.55 | 18.33 | 21.54 | 18.33 | 21.53 |
February | 657.33 | 21.47 | 9.00 | 21.46 | 9.00 | 21.46 |
March | 727.67 | 21.44 | 12.00 | 21.42 | 12.00 | 21.41 |
April | 683.33 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
May | 725.67 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
June | 674.33 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
July | 659.17 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
August | 649.67 | 21.47 | 0.17 | 21.47 | 0.17 | 21.47 |
September | 651.50 | 21.51 | 0.67 | 21.52 | 0.00 | 21.52 |
October | 694.83 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
November | 691.83 | 21.55 | 8.50 | 21.55 | 8.50 | 21.54 |
December | 736.83 | 21.58 | 16.17 | 21.57 | 16.17 | 21.56 |
Annual Sum or Average | 8284.17 | 21.53 | 64.83 | 21.52 | 64.17 | 21.52 |
Minimum of Months | 649.67 | 21.44 | 0.00 | 21.42 | 0.00 | 21.41 |
Maximum of Months | 736.83 | 21.58 | 18.33 | 21.57 | 18.33 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.41 | 54.50 | 21.38 | 54.50 | 21.36 |
February | 672.00 | 21.39 | 19.17 | 21.39 | 19.17 | 21.38 |
March | 731.67 | 21.40 | 22.00 | 21.41 | 15.17 | 21.40 |
April | 637.17 | 21.64 | 42.17 | 21.83 | 0.00 | 21.83 |
May | 652.83 | 21.72 | 49.50 | 21.93 | 0.00 | 21.93 |
June | 551.17 | 21.92 | 114.83 | 22.46 | 5.83 | 22.48 |
July | 512.50 | 22.07 | 196.17 | 22.85 | 50.17 | 22.95 |
August | 525.67 | 22.05 | 189.33 | 22.74 | 62.50 | 22.83 |
September | 594.17 | 21.94 | 72.33 | 22.19 | 14.50 | 22.21 |
October | 694.33 | 22.01 | 39.67 | 22.10 | 30.00 | 22.15 |
November | 720.00 | 21.55 | 25.00 | 21.54 | 25.00 | 21.53 |
December | 744.00 | 21.44 | 54.50 | 21.42 | 54.50 | 21.40 |
Annual Sum or Average | 7779.50 | 21.69 | 879.17 | 21.92 | 331.33 | 21.94 |
Minimum of Months | 512.50 | 21.39 | 19.17 | 21.38 | 0.00 | 21.36 |
Maximum of Months | 744.00 | 22.07 | 196.17 | 22.85 | 62.50 | 22.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 8.17 | 21.37 | 8.17 | 21.37 |
February | 672.00 | 21.36 | 9.83 | 21.36 | 9.83 | 21.35 |
March | 744.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
April | 720.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 712.67 | 22.05 | 1.17 | 22.06 | 0.00 | 22.06 |
July | 724.50 | 22.26 | 23.67 | 22.30 | 22.00 | 22.33 |
August | 734.17 | 22.21 | 22.50 | 22.24 | 22.33 | 22.27 |
September | 720.00 | 21.93 | 5.67 | 21.94 | 5.67 | 21.95 |
October | 742.67 | 21.90 | 17.67 | 21.94 | 17.67 | 21.97 |
November | 720.00 | 21.41 | 14.00 | 21.40 | 14.00 | 21.40 |
December | 744.00 | 21.36 | 19.67 | 21.35 | 19.67 | 21.35 |
Annual Sum or Average | 8722.00 | 21.71 | 122.33 | 21.72 | 119.33 | 21.73 |
Minimum of Months | 672.00 | 21.36 | 0.00 | 21.35 | 0.00 | 21.35 |
Maximum of Months | 744.00 | 22.26 | 23.67 | 22.30 | 22.33 | 22.33 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 19.00 | 21.61 | 19.00 | 21.60 |
February | 672.00 | 21.52 | 9.33 | 21.52 | 9.33 | 21.51 |
March | 744.00 | 21.52 | 11.67 | 21.51 | 11.67 | 21.50 |
April | 719.33 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
May | 743.83 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
June | 716.67 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
July | 704.67 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
August | 668.33 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
September | 694.50 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
October | 716.67 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
November | 720.00 | 21.65 | 8.67 | 21.64 | 8.67 | 21.64 |
December | 744.00 | 21.63 | 18.50 | 21.62 | 18.50 | 21.61 |
Annual Sum or Average | 8588.00 | 21.62 | 67.17 | 21.61 | 67.17 | 21.61 |
Minimum of Months | 668.33 | 21.52 | 0.00 | 21.51 | 0.00 | 21.50 |
Maximum of Months | 744.00 | 21.67 | 19.00 | 21.67 | 19.00 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.42 | 45.83 | 21.40 | 45.83 | 21.38 |
February | 672.00 | 21.37 | 18.33 | 21.37 | 18.33 | 21.36 |
March | 742.00 | 21.45 | 19.00 | 21.43 | 18.50 | 21.42 |
April | 705.83 | 21.81 | 7.50 | 21.84 | 0.00 | 21.84 |
May | 722.33 | 21.87 | 9.17 | 21.91 | 0.00 | 21.91 |
June | 641.33 | 22.07 | 45.50 | 22.24 | 2.67 | 22.25 |
July | 552.67 | 22.20 | 128.83 | 22.63 | 51.67 | 22.75 |
August | 581.83 | 22.29 | 123.83 | 22.66 | 66.17 | 22.81 |
September | 689.67 | 22.06 | 29.50 | 22.14 | 13.67 | 22.16 |
October | 733.67 | 22.07 | 34.17 | 22.13 | 30.17 | 22.17 |
November | 718.83 | 21.50 | 26.83 | 21.49 | 26.83 | 21.48 |
December | 743.67 | 21.44 | 50.83 | 21.42 | 50.83 | 21.40 |
Annual Sum or Average | 8247.67 | 21.78 | 539.33 | 21.87 | 324.67 | 21.90 |
Minimum of Months | 552.67 | 21.37 | 7.50 | 21.37 | 0.00 | 21.36 |
Maximum of Months | 743.83 | 22.29 | 128.83 | 22.66 | 66.17 | 22.81 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
February | 672.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
March | 744.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
April | 720.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
May | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
June | 720.00 | 22.31 | 8.83 | 22.32 | 8.83 | 22.32 |
July | 744.00 | 22.66 | 51.17 | 22.67 | 51.17 | 22.67 |
August | 744.00 | 22.76 | 68.17 | 22.76 | 68.17 | 22.76 |
September | 720.00 | 22.55 | 16.83 | 22.55 | 16.83 | 22.55 |
October | 742.83 | 22.69 | 22.00 | 22.70 | 22.00 | 22.70 |
November | 720.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
December | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
Annual Sum or Average | 8758.83 | 22.16 | 167.00 | 22.17 | 167.00 | 22.18 |
Minimum of Months | 672.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
Maximum of Months | 744.00 | 22.76 | 68.17 | 22.76 | 68.17 | 22.76 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 724.83 | 21.50 | 55.67 | 21.47 | 55.67 | 21.44 |
February | 652.83 | 21.40 | 28.83 | 21.39 | 28.83 | 21.37 |
March | 717.17 | 21.37 | 34.33 | 21.34 | 34.33 | 21.32 |
April | 668.67 | 21.50 | 4.00 | 21.50 | 4.00 | 21.49 |
May | 706.83 | 21.52 | 0.33 | 21.52 | 0.33 | 21.52 |
June | 655.00 | 21.49 | 0.33 | 21.49 | 0.33 | 21.49 |
July | 639.17 | 21.44 | 1.33 | 21.44 | 1.33 | 21.44 |
August | 631.17 | 21.41 | 5.00 | 21.43 | 4.50 | 21.44 |
September | 634.67 | 21.46 | 7.00 | 21.47 | 4.17 | 21.47 |
October | 681.83 | 21.51 | 5.33 | 21.52 | 1.17 | 21.53 |
November | 684.50 | 21.50 | 31.83 | 21.48 | 31.83 | 21.47 |
December | 732.00 | 21.53 | 61.00 | 21.50 | 61.00 | 21.47 |
Annual Sum or Average | 8128.67 | 21.47 | 235.00 | 21.46 | 227.50 | 21.45 |
Minimum of Months | 631.17 | 21.37 | 0.33 | 21.34 | 0.33 | 21.32 |
Maximum of Months | 732.00 | 21.53 | 61.00 | 21.52 | 61.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 122.17 | 21.28 | 122.17 | 21.24 |
February | 672.00 | 21.33 | 48.83 | 21.30 | 48.83 | 21.28 |
March | 725.83 | 21.36 | 55.33 | 21.36 | 45.83 | 21.32 |
April | 610.50 | 21.58 | 62.00 | 21.86 | 6.00 | 21.87 |
May | 623.33 | 21.64 | 68.17 | 21.96 | 0.17 | 21.96 |
June | 543.50 | 22.02 | 133.83 | 22.70 | 28.83 | 22.85 |
July | 521.00 | 22.31 | 216.17 | 23.15 | 93.33 | 23.37 |
August | 524.00 | 22.15 | 215.67 | 22.92 | 98.33 | 23.08 |
September | 563.00 | 21.83 | 103.17 | 22.18 | 32.83 | 22.21 |
October | 684.67 | 21.93 | 52.67 | 22.04 | 37.50 | 22.09 |
November | 718.83 | 21.48 | 59.33 | 21.45 | 59.33 | 21.42 |
December | 744.00 | 21.35 | 135.67 | 21.30 | 135.67 | 21.25 |
Annual Sum or Average | 7674.67 | 21.66 | 1273.00 | 21.93 | 708.83 | 21.96 |
Minimum of Months | 521.00 | 21.33 | 48.83 | 21.28 | 0.17 | 21.24 |
Maximum of Months | 744.00 | 22.31 | 216.17 | 23.15 | 135.67 | 23.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.67 | 21.49 | 2.00 | 21.49 | 2.00 | 21.48 |
February | 628.17 | 21.48 | 2.83 | 21.48 | 2.83 | 21.48 |
March | 700.67 | 21.45 | 10.83 | 21.44 | 10.83 | 21.42 |
April | 693.33 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
May | 744.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
June | 720.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 733.83 | 21.66 | 0.50 | 21.66 | 0.50 | 21.66 |
August | 673.17 | 21.52 | 1.33 | 21.53 | 1.33 | 21.53 |
September | 627.33 | 21.43 | 1.83 | 21.44 | 0.17 | 21.44 |
October | 650.00 | 21.46 | 5.50 | 21.48 | 0.33 | 21.48 |
November | 649.33 | 21.52 | 4.50 | 21.53 | 3.33 | 21.52 |
December | 664.50 | 21.50 | 3.83 | 21.50 | 3.83 | 21.50 |
Annual Sum or Average | 8147.00 | 21.53 | 33.17 | 21.53 | 25.17 | 21.53 |
Minimum of Months | 627.33 | 21.43 | 0.00 | 21.44 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 21.66 | 10.83 | 21.66 | 10.83 | 21.66 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 263.00 | 23.08 | 265.83 | 23.52 | 12.67 | 23.53 |
February | 164.17 | 23.28 | 304.33 | 23.71 | 11.17 | 23.72 |
March | 147.67 | 22.98 | 397.33 | 23.66 | 1.00 | 23.66 |
April | 27.33 | 23.59 | 587.83 | 23.89 | 13.17 | 23.89 |
May | 21.50 | 23.76 | 641.00 | 23.91 | 16.00 | 23.91 |
June | 91.83 | 23.99 | 701.67 | 23.91 | 91.50 | 23.92 |
July | 218.67 | 24.00 | 744.00 | 23.94 | 218.67 | 23.95 |
August | 282.17 | 24.00 | 744.00 | 23.93 | 282.17 | 23.94 |
September | 175.17 | 24.00 | 704.83 | 23.90 | 175.17 | 23.92 |
October | 91.67 | 23.77 | 544.17 | 23.89 | 63.83 | 23.90 |
November | 150.50 | 23.42 | 333.00 | 23.77 | 19.83 | 23.78 |
December | 275.17 | 23.25 | 182.83 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 1908.83 | 23.56 | 6150.83 | 23.83 | 905.17 | 23.84 |
Minimum of Months | 21.50 | 22.98 | 182.83 | 23.52 | 0.00 | 23.53 |
Maximum of Months | 282.17 | 24.00 | 744.00 | 23.94 | 282.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 135.67 | 23.11 | 390.33 | 23.72 | 4.83 | 23.73 |
February | 38.33 | 23.43 | 443.83 | 23.88 | 6.67 | 23.88 |
March | 49.33 | 22.97 | 555.50 | 23.84 | 0.00 | 23.84 |
April | 11.00 | 24.00 | 665.83 | 23.93 | 11.00 | 23.93 |
May | 9.00 | 24.00 | 717.50 | 23.94 | 9.00 | 23.94 |
June | 73.50 | 24.00 | 717.17 | 23.95 | 73.50 | 23.96 |
July | 200.67 | 24.00 | 744.00 | 23.97 | 200.67 | 23.97 |
August | 265.67 | 24.00 | 744.00 | 23.96 | 265.67 | 23.97 |
September | 151.33 | 24.00 | 718.00 | 23.94 | 151.33 | 23.95 |
October | 62.00 | 23.97 | 608.17 | 23.94 | 59.33 | 23.94 |
November | 56.33 | 23.60 | 462.67 | 23.89 | 14.17 | 23.89 |
December | 101.17 | 23.28 | 294.33 | 23.77 | 0.00 | 23.77 |
Annual Sum or Average | 1154.00 | 23.74 | 7061.33 | 23.91 | 796.17 | 23.92 |
Minimum of Months | 9.00 | 22.97 | 294.33 | 23.72 | 0.00 | 23.73 |
Maximum of Months | 265.67 | 24.00 | 744.00 | 23.97 | 265.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 567.33 | 23.76 | 660.67 | 23.82 | 517.67 | 23.87 |
February | 483.83 | 23.94 | 637.33 | 23.89 | 473.17 | 23.92 |
March | 561.33 | 23.83 | 690.50 | 23.84 | 528.00 | 23.88 |
April | 525.17 | 23.99 | 713.67 | 23.91 | 524.67 | 23.93 |
May | 545.83 | 23.99 | 740.17 | 23.91 | 545.83 | 23.93 |
June | 547.00 | 23.99 | 720.00 | 23.93 | 547.00 | 23.95 |
July | 574.50 | 23.99 | 744.00 | 23.95 | 574.50 | 23.96 |
August | 576.83 | 23.99 | 744.00 | 23.95 | 576.83 | 23.96 |
September | 546.50 | 23.99 | 720.00 | 23.94 | 546.50 | 23.95 |
October | 544.17 | 23.99 | 739.83 | 23.93 | 544.17 | 23.95 |
November | 517.67 | 23.95 | 680.00 | 23.90 | 508.33 | 23.93 |
December | 553.50 | 23.81 | 654.17 | 23.85 | 513.17 | 23.89 |
Annual Sum or Average | 6543.67 | 23.94 | 8444.33 | 23.90 | 6399.83 | 23.93 |
Minimum of Months | 483.83 | 23.76 | 637.33 | 23.82 | 473.17 | 23.87 |
Maximum of Months | 576.83 | 23.99 | 744.00 | 23.95 | 576.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.66 | 5.33 | 21.66 | 5.33 | 21.65 |
February | 672.00 | 21.63 | 2.17 | 21.62 | 2.17 | 21.62 |
March | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
April | 720.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
May | 744.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
June | 714.17 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
July | 690.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
August | 634.00 | 22.83 | 3.33 | 22.84 | 0.00 | 22.84 |
September | 694.50 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
October | 693.67 | 22.60 | 7.00 | 22.61 | 0.00 | 22.61 |
November | 720.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
December | 744.00 | 21.73 | 3.00 | 21.73 | 3.00 | 21.73 |
Annual Sum or Average | 8514.33 | 22.15 | 20.83 | 22.15 | 10.50 | 22.15 |
Minimum of Months | 634.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Maximum of Months | 744.00 | 22.83 | 7.00 | 22.84 | 5.33 | 22.84 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.15586 | 38.75475 | 0.12433 | 5.68830 |
February | 672.00000 | 22.77280 | 42.39155 | 0.04295 | 5.23843 |
March | 744.00000 | 22.46884 | 46.68660 | -0.0058 | 5.20790 |
April | 720.00000 | 22.50354 | 51.40402 | 0.02974 | 5.21671 |
May | 744.00000 | 22.52742 | 50.97486 | -1.0251 | 27.38320 |
June | 720.00000 | 22.43758 | 58.21721 | -1.0107 | 26.75089 |
July | 744.00000 | 22.77850 | 60.72464 | -0.8675 | 21.09891 |
August | 744.00000 | 22.88729 | 61.23875 | -0.8242 | 19.53243 |
September | 720.00000 | 23.21177 | 56.80554 | -0.7334 | 16.58881 |
October | 744.00000 | 23.47786 | 45.75985 | 0.25207 | 6.56529 |
November | 720.00000 | 23.52545 | 39.72958 | 0.22305 | 6.28597 |
December | 744.00000 | 23.28243 | 33.59957 | 0.12068 | 5.60029 |
Annual Sum or Average | 8760.00000 | 22.92031 | 48.88100 | -0.3083 | 12.64469 |
Minimum of Months | 672.00000 | 22.43758 | 33.59957 | -1.0251 | 5.20790 |
Maximum of Months | 744.00000 | 23.52545 | 61.23875 | 0.25207 | 27.38320 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.05114 | 40.15091 | -0.0554 | 7.13758 |
February | 672.00000 | 21.83660 | 43.66015 | -0.1023 | 6.88154 |
March | 744.00000 | 21.57839 | 47.94132 | -0.1544 | 6.95396 |
April | 720.00000 | 21.79577 | 52.39127 | -0.0504 | 6.06133 |
May | 744.00000 | 21.45836 | 52.95584 | -1.2681 | 39.19595 |
June | 720.00000 | 21.68899 | 59.70278 | -1.1293 | 32.36156 |
July | 744.00000 | 22.14517 | 62.19734 | -0.9354 | 23.99452 |
August | 744.00000 | 22.50431 | 61.95885 | -0.7995 | 19.39069 |
September | 720.00000 | 22.52679 | 58.15691 | -0.8131 | 20.91939 |
October | 744.00000 | 22.64749 | 47.03786 | 0.16653 | 7.11881 |
November | 720.00000 | 22.22942 | 41.58378 | 0.00960 | 6.80233 |
December | 744.00000 | 22.18295 | 34.69947 | -0.0475 | 7.08851 |
Annual Sum or Average | 8760.00000 | 22.05550 | 50.22662 | -0.4336 | 15.38165 |
Minimum of Months | 672.00000 | 21.45836 | 34.69947 | -1.2681 | 6.06133 |
Maximum of Months | 744.00000 | 22.64749 | 62.19734 | 0.16653 | 39.19595 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.54397 | 40.82919 | 0.02136 | 5.63936 |
February | 672.00000 | 22.61937 | 43.65764 | 0.05238 | 5.43760 |
March | 744.00000 | 22.37912 | 47.74420 | 0.01896 | 5.59017 |
April | 720.00000 | 22.80490 | 51.42173 | 0.15241 | 5.96696 |
May | 744.00000 | 22.74876 | 51.23255 | -0.8830 | 22.12582 |
June | 720.00000 | 22.96171 | 57.48873 | -0.7618 | 17.87899 |
July | 744.00000 | 23.22094 | 60.29976 | -0.6430 | 14.18227 |
August | 744.00000 | 23.32278 | 60.84151 | -0.5997 | 12.98443 |
September | 720.00000 | 23.26026 | 57.59194 | -0.6459 | 14.22341 |
October | 744.00000 | 23.29412 | 47.11104 | 0.25824 | 6.79916 |
November | 720.00000 | 22.94617 | 41.86089 | 0.12816 | 5.71535 |
December | 744.00000 | 22.74434 | 35.50742 | 0.03659 | 5.38208 |
Annual Sum or Average | 8760.00000 | 22.90523 | 49.65438 | -0.2407 | 10.19067 |
Minimum of Months | 672.00000 | 22.37912 | 35.50742 | -0.8830 | 5.38208 |
Maximum of Months | 744.00000 | 23.32278 | 60.84151 | 0.25824 | 22.12582 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.71498 | 36.00098 | 0.64763 | 17.07658 |
February | 672.00000 | 22.80732 | 38.60180 | 0.68344 | 17.78221 |
March | 744.00000 | 22.72208 | 42.45936 | 0.68843 | 18.09288 |
April | 720.00000 | 22.83109 | 46.95420 | 0.76082 | 20.00141 |
May | 744.00000 | 22.84324 | 46.48826 | 0.02126 | 10.77953 |
June | 720.00000 | 22.85117 | 53.36502 | 0.08696 | 10.83907 |
July | 744.00000 | 22.86231 | 56.92073 | 0.13014 | 10.75769 |
August | 744.00000 | 22.85601 | 57.79034 | 0.13908 | 10.92427 |
September | 720.00000 | 22.86151 | 54.32534 | 0.09872 | 10.74298 |
October | 744.00000 | 22.88025 | 43.61031 | 0.76724 | 20.20057 |
November | 720.00000 | 22.86131 | 37.45547 | 0.70037 | 18.26799 |
December | 744.00000 | 22.76005 | 30.86661 | 0.62689 | 16.29264 |
Annual Sum or Average | 8760.00000 | 22.82072 | 45.43037 | 0.44434 | 15.12683 |
Minimum of Months | 672.00000 | 22.71498 | 30.86661 | 0.02126 | 10.74298 |
Maximum of Months | 744.00000 | 22.88025 | 57.79034 | 0.76724 | 20.20057 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.05426 | 43.90897 | 0.25370 | 7.63674 |
February | 672.00000 | 22.92814 | 47.12947 | 0.22068 | 7.06863 |
March | 744.00000 | 22.58157 | 51.28761 | 0.14954 | 6.75220 |
April | 720.00000 | 22.88874 | 55.31458 | 0.26313 | 7.03819 |
May | 744.00000 | 22.58427 | 55.73022 | -0.8391 | 20.72474 |
June | 720.00000 | 22.75279 | 62.23488 | -0.7224 | 16.82523 |
July | 744.00000 | 23.01101 | 65.03545 | -0.5891 | 12.89992 |
August | 744.00000 | 23.27462 | 65.03134 | -0.4769 | 10.24695 |
September | 720.00000 | 23.38078 | 61.21879 | -0.4589 | 10.28313 |
October | 744.00000 | 23.49275 | 50.58341 | 0.43148 | 9.60672 |
November | 720.00000 | 23.32610 | 45.12238 | 0.33314 | 8.09515 |
December | 744.00000 | 23.20384 | 38.80919 | 0.26435 | 7.47335 |
Annual Sum or Average | 8760.00000 | 23.04031 | 53.47484 | -0.0996 | 10.41296 |
Minimum of Months | 672.00000 | 22.58157 | 38.80919 | -0.8391 | 6.75220 |
Maximum of Months | 744.00000 | 23.49275 | 65.03545 | 0.43148 | 20.72474 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.96734 | 43.08325 | 0.16216 | 6.17921 |
February | 672.00000 | 23.00832 | 45.90173 | 0.18251 | 6.10298 |
March | 744.00000 | 22.73738 | 49.96514 | 0.13941 | 6.04677 |
April | 720.00000 | 23.04481 | 53.88647 | 0.24641 | 6.74126 |
May | 744.00000 | 22.98543 | 53.69528 | -0.7605 | 18.01067 |
June | 720.00000 | 23.14204 | 60.00326 | -0.6544 | 14.81221 |
July | 744.00000 | 23.30224 | 63.00727 | -0.5662 | 12.39963 |
August | 744.00000 | 23.39377 | 63.53353 | -0.5250 | 11.32631 |
September | 720.00000 | 23.41379 | 60.07591 | -0.5426 | 11.67203 |
October | 744.00000 | 23.51181 | 49.49448 | 0.35558 | 7.98568 |
November | 720.00000 | 23.30975 | 44.18134 | 0.25652 | 6.72875 |
December | 744.00000 | 23.15714 | 37.91248 | 0.17632 | 5.98013 |
Annual Sum or Average | 8760.00000 | 23.16508 | 52.08518 | -0.1295 | 9.52135 |
Minimum of Months | 672.00000 | 22.73738 | 37.91248 | -0.7605 | 5.98013 |
Maximum of Months | 744.00000 | 23.51181 | 63.53353 | 0.35558 | 18.01067 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57917 | 46.21910 | -0.2311 | 7.06095 |
February | 672.00000 | 21.50581 | 49.26678 | -0.2320 | 6.89915 |
March | 744.00000 | 21.47719 | 52.63843 | -0.2247 | 6.89266 |
April | 720.00000 | 21.63567 | 54.18639 | -0.1278 | 6.22697 |
May | 744.00000 | 21.61362 | 54.38635 | -1.2646 | 39.47523 |
June | 720.00000 | 21.65781 | 57.00349 | -1.1934 | 36.08240 |
July | 744.00000 | 21.70517 | 57.14820 | -1.1350 | 33.49034 |
August | 744.00000 | 21.70855 | 57.45234 | -1.1275 | 33.21075 |
September | 720.00000 | 21.68710 | 56.70387 | -1.1639 | 34.91082 |
October | 744.00000 | 21.67876 | 49.63199 | -0.1122 | 6.20970 |
November | 720.00000 | 21.62241 | 46.82914 | -0.1927 | 6.74152 |
December | 744.00000 | 21.59946 | 41.00439 | -0.2467 | 7.23842 |
Annual Sum or Average | 8760.00000 | 21.62321 | 51.87414 | -0.6067 | 18.77520 |
Minimum of Months | 672.00000 | 21.47719 | 41.00439 | -1.2646 | 6.20970 |
Maximum of Months | 744.00000 | 21.70855 | 57.45234 | -0.1122 | 39.47523 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.40616 | 47.54374 | -0.3141 | 7.72982 |
February | 672.00000 | 21.39491 | 50.37118 | -0.2865 | 7.27780 |
March | 744.00000 | 21.44466 | 53.62687 | -0.2526 | 7.15558 |
April | 720.00000 | 21.93430 | 54.50846 | -0.0806 | 6.66700 |
May | 744.00000 | 22.02727 | 53.66994 | -1.1503 | 35.18862 |
June | 720.00000 | 22.52119 | 55.71855 | -0.9422 | 27.83876 |
July | 744.00000 | 22.81509 | 56.40839 | -0.8089 | 23.40570 |
August | 744.00000 | 22.72443 | 57.82057 | -0.8382 | 23.91385 |
September | 720.00000 | 22.28689 | 57.80001 | -1.0111 | 29.00716 |
October | 744.00000 | 22.12574 | 50.62115 | -0.0447 | 6.30316 |
November | 720.00000 | 21.55471 | 48.39255 | -0.2459 | 7.00889 |
December | 744.00000 | 21.44378 | 41.93418 | -0.3320 | 7.89214 |
Annual Sum or Average | 8760.00000 | 21.97691 | 52.36534 | -0.5271 | 15.83202 |
Minimum of Months | 672.00000 | 21.39491 | 41.93418 | -1.1503 | 6.30316 |
Maximum of Months | 744.00000 | 22.81509 | 57.82057 | -0.0447 | 35.18862 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37366 | 44.80490 | -0.3293 | 7.57313 |
February | 672.00000 | 21.35898 | 47.74027 | -0.3090 | 7.19129 |
March | 744.00000 | 21.38195 | 51.14966 | -0.2813 | 6.87842 |
April | 720.00000 | 21.59295 | 53.55202 | -0.2004 | 6.20997 |
May | 744.00000 | 21.70817 | 52.45687 | -1.3060 | 41.03788 |
June | 720.00000 | 22.07235 | 55.95040 | -1.1439 | 33.56383 |
July | 744.00000 | 22.30050 | 58.32750 | -1.0420 | 29.28211 |
August | 744.00000 | 22.23154 | 59.74828 | -1.0656 | 30.17145 |
September | 720.00000 | 21.92753 | 58.01683 | -1.1922 | 35.59454 |
October | 744.00000 | 21.90706 | 49.23127 | -0.1387 | 6.13737 |
November | 720.00000 | 21.40852 | 46.11034 | -0.3032 | 7.19706 |
December | 744.00000 | 21.36128 | 39.49321 | -0.3630 | 7.95838 |
Annual Sum or Average | 8760.00000 | 21.72132 | 51.38953 | -0.6415 | 18.29731 |
Minimum of Months | 672.00000 | 21.35898 | 39.49321 | -1.3060 | 6.13737 |
Maximum of Months | 744.00000 | 22.30050 | 59.74828 | -0.1387 | 41.03788 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62543 | 45.94364 | -0.2185 | 6.90317 |
February | 672.00000 | 21.52221 | 49.29920 | -0.2320 | 6.86995 |
March | 744.00000 | 21.51791 | 52.30048 | -0.2178 | 6.83667 |
April | 720.00000 | 21.67593 | 53.97577 | -0.1251 | 6.21310 |
May | 744.00000 | 21.64758 | 54.20358 | -1.2677 | 39.61043 |
June | 720.00000 | 21.67503 | 57.31005 | -1.2046 | 36.59220 |
July | 744.00000 | 21.73257 | 57.22860 | -1.1388 | 33.68127 |
August | 744.00000 | 21.73388 | 57.32065 | -1.1268 | 33.19457 |
September | 720.00000 | 21.68822 | 57.41718 | -1.1797 | 35.59725 |
October | 744.00000 | 21.69384 | 49.85089 | -0.1116 | 6.16579 |
November | 720.00000 | 21.64783 | 46.91970 | -0.1912 | 6.65852 |
December | 744.00000 | 21.63039 | 40.95528 | -0.2401 | 7.10600 |
Annual Sum or Average | 8760.00000 | 21.65003 | 51.89303 | -0.6068 | 18.85651 |
Minimum of Months | 672.00000 | 21.51791 | 40.95528 | -1.2677 | 6.16579 |
Maximum of Months | 744.00000 | 21.73388 | 57.41718 | -0.1116 | 39.61043 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41664 | 47.24367 | -0.3083 | 7.53596 |
February | 672.00000 | 21.37371 | 50.39014 | -0.2955 | 7.21890 |
March | 744.00000 | 21.45492 | 53.35093 | -0.2524 | 7.00988 |
April | 720.00000 | 21.86436 | 54.59898 | -0.1013 | 6.22313 |
May | 744.00000 | 21.94721 | 54.01579 | -1.1858 | 36.04806 |
June | 720.00000 | 22.30695 | 57.09315 | -1.0171 | 29.19039 |
July | 744.00000 | 22.63453 | 57.62964 | -0.8694 | 24.11508 |
August | 744.00000 | 22.60772 | 58.69621 | -0.8753 | 24.24782 |
September | 720.00000 | 22.15041 | 59.20345 | -1.0666 | 30.74806 |
October | 744.00000 | 22.10281 | 50.95122 | -0.0529 | 6.09455 |
November | 720.00000 | 21.50772 | 48.50938 | -0.2607 | 6.93392 |
December | 744.00000 | 21.44634 | 41.98598 | -0.3307 | 7.71419 |
Annual Sum or Average | 8760.00000 | 21.90483 | 52.80315 | -0.5528 | 16.13897 |
Minimum of Months | 672.00000 | 21.37371 | 41.98598 | -1.1858 | 6.09455 |
Maximum of Months | 744.00000 | 22.63453 | 59.20345 | -0.0529 | 36.04806 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54454 | 47.19139 | -0.2577 | 7.49949 |
February | 672.00000 | 21.45991 | 50.44537 | -0.2599 | 7.32951 |
March | 744.00000 | 21.44237 | 53.83542 | -0.2455 | 7.29059 |
April | 720.00000 | 21.62862 | 55.40338 | -0.1312 | 6.42294 |
May | 744.00000 | 21.60858 | 55.53938 | -1.2727 | 40.10549 |
June | 720.00000 | 21.65535 | 58.18152 | -1.1914 | 36.20076 |
July | 744.00000 | 21.70402 | 58.20471 | -1.1280 | 33.37517 |
August | 744.00000 | 21.70433 | 58.70173 | -1.1235 | 33.22882 |
September | 720.00000 | 21.67710 | 58.41840 | -1.1679 | 35.29722 |
October | 744.00000 | 21.66123 | 50.88912 | -0.1233 | 6.41885 |
November | 720.00000 | 21.58968 | 48.03394 | -0.2172 | 7.10521 |
December | 744.00000 | 21.56007 | 41.85413 | -0.2772 | 7.72525 |
Annual Sum or Average | 8760.00000 | 21.60378 | 53.05830 | -0.6186 | 19.07113 |
Minimum of Months | 672.00000 | 21.44237 | 41.85413 | -1.2727 | 6.41885 |
Maximum of Months | 744.00000 | 21.70433 | 58.70173 | -0.1233 | 40.10549 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33321 | 48.63535 | -0.3533 | 8.36684 |
February | 672.00000 | 21.32910 | 51.65819 | -0.3215 | 7.84737 |
March | 744.00000 | 21.42056 | 54.82627 | -0.2726 | 7.60814 |
April | 720.00000 | 21.98781 | 55.37468 | -0.0709 | 7.10580 |
May | 744.00000 | 22.07189 | 54.43726 | -1.1400 | 35.47746 |
June | 720.00000 | 22.62812 | 55.96996 | -0.9024 | 27.82086 |
July | 744.00000 | 22.93330 | 56.14805 | -0.7605 | 23.30855 |
August | 744.00000 | 22.81202 | 57.83710 | -0.8028 | 23.91558 |
September | 720.00000 | 22.29252 | 58.99004 | -1.0075 | 29.40614 |
October | 744.00000 | 22.06779 | 51.81476 | -0.0636 | 6.54979 |
November | 720.00000 | 21.48232 | 49.73288 | -0.2827 | 7.53847 |
December | 744.00000 | 21.35346 | 42.89271 | -0.3783 | 8.66546 |
Annual Sum or Average | 8760.00000 | 21.97999 | 53.18573 | -0.5310 | 16.18222 |
Minimum of Months | 672.00000 | 21.32910 | 42.89271 | -1.1400 | 6.54979 |
Maximum of Months | 744.00000 | 22.93330 | 58.99004 | -0.0636 | 35.47746 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68844 | 45.25183 | -0.1629 | 6.83046 |
February | 672.00000 | 21.60278 | 48.57918 | -0.1929 | 6.81121 |
March | 744.00000 | 21.55579 | 51.86580 | -0.2056 | 6.91516 |
April | 720.00000 | 21.64667 | 54.44168 | -0.1470 | 6.41265 |
May | 744.00000 | 21.58306 | 55.79559 | -1.3288 | 42.63960 |
June | 720.00000 | 21.61252 | 59.74175 | -1.2683 | 39.59366 |
July | 744.00000 | 21.67936 | 60.31878 | -1.2071 | 36.78936 |
August | 744.00000 | 21.69487 | 59.34342 | -1.1800 | 35.64024 |
September | 720.00000 | 21.67578 | 56.87660 | -1.1924 | 36.38859 |
October | 744.00000 | 21.69655 | 49.45514 | -0.1036 | 6.37277 |
November | 720.00000 | 21.70231 | 45.80311 | -0.1488 | 6.69701 |
December | 744.00000 | 21.69940 | 40.48968 | -0.1786 | 7.01877 |
Annual Sum or Average | 8760.00000 | 21.65347 | 52.34038 | -0.6122 | 19.92293 |
Minimum of Months | 672.00000 | 21.55579 | 40.48968 | -1.3288 | 6.37277 |
Maximum of Months | 744.00000 | 21.70231 | 60.31878 | -0.1036 | 42.63960 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.56211 | 43.58550 | 0.33424 | 7.86309 |
February | 672.00000 | 23.68115 | 45.72058 | 0.37964 | 8.31474 |
March | 744.00000 | 23.63439 | 49.38922 | 0.39684 | 8.63330 |
April | 720.00000 | 23.81490 | 52.88616 | 0.48712 | 10.14145 |
May | 744.00000 | 23.83909 | 52.31953 | -0.3850 | 8.28898 |
June | 720.00000 | 23.88414 | 58.31383 | -0.3001 | 7.01971 |
July | 744.00000 | 23.91766 | 61.41513 | -0.2483 | 6.35221 |
August | 744.00000 | 23.90304 | 62.28805 | -0.2509 | 6.38831 |
September | 720.00000 | 23.86779 | 59.36816 | -0.3061 | 7.11509 |
October | 744.00000 | 23.85043 | 49.47854 | 0.48922 | 10.28956 |
November | 720.00000 | 23.72920 | 44.53117 | 0.39012 | 8.51188 |
December | 744.00000 | 23.63371 | 38.64372 | 0.31768 | 7.44129 |
Annual Sum or Average | 8760.00000 | 23.77673 | 51.51744 | 0.10694 | 8.02580 |
Minimum of Months | 672.00000 | 23.56211 | 38.64372 | -0.3850 | 6.35221 |
Maximum of Months | 744.00000 | 23.91766 | 62.28805 | 0.48922 | 10.28956 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.71501 | 42.59534 | 0.40537 | 8.85891 |
February | 672.00000 | 23.82120 | 44.68290 | 0.44878 | 9.44116 |
March | 744.00000 | 23.78681 | 48.31986 | 0.46911 | 9.84785 |
April | 720.00000 | 23.90945 | 51.93783 | 0.54405 | 11.32240 |
May | 744.00000 | 23.92417 | 51.39870 | -0.3051 | 7.05650 |
June | 720.00000 | 23.94591 | 57.49479 | -0.2310 | 6.19617 |
July | 744.00000 | 23.96242 | 60.68836 | -0.1882 | 5.77514 |
August | 744.00000 | 23.95112 | 61.56156 | -0.1910 | 5.79942 |
September | 720.00000 | 23.93019 | 58.55804 | -0.2390 | 6.29746 |
October | 744.00000 | 23.91722 | 48.71250 | 0.53550 | 11.24312 |
November | 720.00000 | 23.84826 | 43.57574 | 0.45245 | 9.54984 |
December | 744.00000 | 23.77619 | 37.68302 | 0.38605 | 8.37968 |
Annual Sum or Average | 8760.00000 | 23.87405 | 50.62426 | 0.17212 | 8.30441 |
Minimum of Months | 672.00000 | 23.71501 | 37.68302 | -0.3051 | 5.77514 |
Maximum of Months | 744.00000 | 23.96242 | 61.56156 | 0.54405 | 11.32240 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.63839 | 41.22223 | 1.03858 | 31.13054 |
February | 672.00000 | 23.76934 | 43.34662 | 1.08086 | 32.09879 |
March | 744.00000 | 23.68945 | 46.88447 | 1.09092 | 33.03641 |
April | 720.00000 | 23.84220 | 50.79998 | 1.18526 | 36.42570 |
May | 744.00000 | 23.84552 | 50.40462 | 0.60095 | 17.34166 |
June | 720.00000 | 23.88745 | 56.56592 | 0.68587 | 19.11120 |
July | 744.00000 | 23.91134 | 59.75115 | 0.74474 | 20.60021 |
August | 744.00000 | 23.91364 | 60.49937 | 0.75071 | 20.72625 |
September | 720.00000 | 23.89278 | 57.40484 | 0.69058 | 19.14251 |
October | 744.00000 | 23.88048 | 47.76395 | 1.18638 | 36.35918 |
November | 720.00000 | 23.78456 | 42.34528 | 1.08876 | 32.41884 |
December | 744.00000 | 23.67629 | 36.44116 | 1.01538 | 29.90100 |
Annual Sum or Average | 8760.00000 | 23.81085 | 49.47716 | 0.92887 | 27.32511 |
Minimum of Months | 672.00000 | 23.63839 | 36.44116 | 0.60095 | 17.34166 |
Maximum of Months | 744.00000 | 23.91364 | 60.49937 | 1.18638 | 36.42570 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55534 | 39.76964 | -0.2655 | 7.00349 |
February | 672.00000 | 21.60259 | 42.83778 | -0.2359 | 6.33151 |
March | 744.00000 | 21.44951 | 46.96800 | -0.2501 | 6.59673 |
April | 720.00000 | 21.88342 | 50.82704 | -0.1168 | 5.53022 |
May | 744.00000 | 22.04372 | 50.02125 | -1.1789 | 34.38820 |
June | 720.00000 | 22.42383 | 56.02449 | -1.0071 | 26.57717 |
July | 744.00000 | 22.73613 | 59.04800 | -0.8767 | 21.31252 |
August | 744.00000 | 22.73386 | 60.08340 | -0.8713 | 21.09808 |
September | 720.00000 | 22.54107 | 56.85554 | -0.9604 | 24.63964 |
October | 744.00000 | 22.64767 | 45.67986 | 0.04650 | 5.41818 |
November | 720.00000 | 21.96417 | 40.85360 | -0.1566 | 5.75943 |
December | 744.00000 | 21.68925 | 34.15147 | -0.2654 | 6.76354 |
Annual Sum or Average | 8760.00000 | 22.10895 | 48.61274 | -0.5133 | 14.33556 |
Minimum of Months | 672.00000 | 21.44951 | 34.15147 | -1.1789 | 5.41818 |
Maximum of Months | 744.00000 | 22.73613 | 60.08340 | 0.04650 | 34.38820 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68058 | 42.87194 | -0.2331 | 6.52812 |
February | 672.00000 | 21.71982 | 45.95381 | -0.2074 | 6.02920 |
March | 744.00000 | 21.53797 | 50.05464 | -0.2272 | 6.33931 |
April | 720.00000 | 21.95837 | 53.96516 | -0.0981 | 5.42930 |
May | 744.00000 | 22.02190 | 53.43964 | -1.1945 | 35.15179 |
June | 720.00000 | 22.31279 | 59.72382 | -1.0521 | 28.53427 |
July | 744.00000 | 22.66173 | 62.44171 | -0.9093 | 22.53933 |
August | 744.00000 | 22.75809 | 63.07734 | -0.8707 | 21.05590 |
September | 720.00000 | 22.55231 | 60.10560 | -0.9636 | 24.74443 |
October | 744.00000 | 22.69069 | 48.91139 | 0.05857 | 5.38793 |
November | 720.00000 | 22.07667 | 44.01724 | -0.1285 | 5.53969 |
December | 744.00000 | 21.87444 | 37.20604 | -0.2198 | 6.21618 |
Annual Sum or Average | 8760.00000 | 22.15657 | 51.83327 | -0.5056 | 14.50965 |
Minimum of Months | 672.00000 | 21.53797 | 37.20604 | -1.1945 | 5.38793 |
Maximum of Months | 744.00000 | 22.75809 | 63.07734 | 0.05857 | 35.15179 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.66018 | 40.66878 | -0.2185 | 6.54930 |
February | 672.00000 | 21.62599 | 43.84496 | -0.2078 | 6.22880 |
March | 744.00000 | 21.57367 | 47.71704 | -0.1982 | 6.27343 |
April | 720.00000 | 22.07276 | 51.37214 | -0.0444 | 5.43832 |
May | 744.00000 | 22.08043 | 50.98012 | -1.1310 | 32.33893 |
June | 720.00000 | 22.46007 | 56.96092 | -0.9544 | 24.61491 |
July | 744.00000 | 22.82891 | 59.54471 | -0.8020 | 18.76909 |
August | 744.00000 | 22.90984 | 60.20230 | -0.7686 | 17.65342 |
September | 720.00000 | 22.62104 | 57.57613 | -0.8922 | 22.21629 |
October | 744.00000 | 22.66905 | 46.60930 | 0.08195 | 5.71070 |
November | 720.00000 | 21.91721 | 42.02635 | -0.1429 | 5.81295 |
December | 744.00000 | 21.73444 | 35.22703 | -0.2321 | 6.50325 |
Annual Sum or Average | 8760.00000 | 22.18305 | 49.41138 | -0.4607 | 13.21814 |
Minimum of Months | 672.00000 | 21.57367 | 35.22703 | -1.1310 | 5.43832 |
Maximum of Months | 744.00000 | 22.90984 | 60.20230 | 0.08195 | 32.33893 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71280 | 39.01974 | -0.2316 | 6.74152 |
February | 672.00000 | 21.80096 | 41.98162 | -0.1937 | 5.98221 |
March | 744.00000 | 21.62210 | 46.12807 | -0.2127 | 6.29542 |
April | 720.00000 | 22.07832 | 49.88357 | -0.0752 | 5.41078 |
May | 744.00000 | 22.25867 | 49.03443 | -1.1125 | 31.32070 |
June | 720.00000 | 22.63839 | 54.96130 | -0.9403 | 23.90179 |
July | 744.00000 | 22.95364 | 57.94060 | -0.8084 | 18.93052 |
August | 744.00000 | 22.94854 | 58.97368 | -0.8041 | 18.76466 |
September | 720.00000 | 22.74663 | 55.80971 | -0.8966 | 22.18452 |
October | 744.00000 | 22.86023 | 44.73867 | 0.09257 | 5.59117 |
November | 720.00000 | 22.16530 | 40.00783 | -0.1138 | 5.55074 |
December | 744.00000 | 21.87490 | 33.40569 | -0.2259 | 6.41039 |
Annual Sum or Average | 8760.00000 | 22.30806 | 47.67623 | -0.4619 | 13.13595 |
Minimum of Months | 672.00000 | 21.62210 | 33.40569 | -1.1125 | 5.41078 |
Maximum of Months | 744.00000 | 22.95364 | 58.97368 | 0.09257 | 31.32070 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.398327E+11 | 88478.82 | 15-JAN-09:52 | 639.84 | 0.119575E+12 | 0.00 | 0.159408E+12 | 2.61 | 3.85 | 15-JAN-16:01 | 0.00 | 0.00 |
February | 0.263754E+11 | 83882.00 | 01-FEB-09:51 | 595.30 | 0.788406E+11 | 0.00 | 0.105216E+12 | 2.70 | 3.89 | 03-FEB-16:03 | 0.00 | 0.00 |
March | 0.267035E+11 | 86220.26 | 23-MAR-15:03 | 618.14 | 0.805111E+11 | 0.00 | 0.107215E+12 | 2.54 | 3.96 | 23-MAR-15:03 | 0.00 | 0.00 |
April | 0.508495E+11 | 84247.24 | 11-APR-15:03 | 710.57 | 0.151512E+12 | 0.00 | 0.202362E+12 | 2.98 | 3.83 | 08-APR-15:03 | 0.00 | 0.00 |
May | 0.524530E+11 | 81467.69 | 04-MAY-15:03 | 738.87 | 0.152777E+12 | 0.00 | 0.205230E+12 | 2.96 | 3.91 | 05-MAY-15:03 | 0.00 | 0.00 |
June | 0.823156E+11 | 95859.65 | 28-JUN-15:03 | 720.00 | 0.251337E+12 | 0.00 | 0.333652E+12 | 3.00 | 4.06 | 29-JUN-18:03 | 0.00 | 0.00 |
July | 0.138707E+12 | 138787.11 | 19-JUL-15:03 | 744.00 | 0.469749E+12 | 0.00 | 0.608456E+12 | 3.26 | 4.31 | 31-JUL-21:54 | 0.00 | 0.00 |
August | 0.151300E+12 | 143327.03 | 18-AUG-15:03 | 744.00 | 0.524625E+12 | 0.00 | 0.675925E+12 | 3.35 | 4.23 | 15-AUG-21:54 | 0.00 | 0.00 |
September | 0.105862E+12 | 158717.55 | 29-SEP-15:03 | 720.00 | 0.338976E+12 | 0.00 | 0.444838E+12 | 3.11 | 4.20 | 08-SEP-21:53 | 0.00 | 0.00 |
October | 0.115313E+12 | 164172.84 | 16-OCT-11:00 | 744.00 | 0.377604E+12 | 0.00 | 0.492917E+12 | 3.16 | 4.26 | 01-OCT-21:54 | 0.00 | 0.00 |
November | 0.427857E+11 | 103629.91 | 19-NOV-09:41 | 681.44 | 0.128838E+12 | 0.00 | 0.171623E+12 | 2.87 | 3.98 | 18-NOV-16:01 | 0.00 | 0.00 |
December | 0.440244E+11 | 99249.99 | 05-DEC-09:41 | 654.15 | 0.133863E+12 | 0.00 | 0.177888E+12 | 2.68 | 3.90 | 19-DEC-16:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.876524E+12 | 8310.31 | 0.280821E+13 | 0.00 | 0.368473E+13 | 2.94 | 0.00 | 0.00 | ||||
Minimum of Months | 0.263754E+11 | 81467.69 | 595.30 | 0.788406E+11 | 0.00 | 0.105216E+12 | 2.54 | 3.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.151300E+12 | 164172.84 | 744.00 | 0.524625E+12 | 0.00 | 0.675925E+12 | 3.35 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.104826E+12 | 0.00 | 538.65 | 157985.91 | 08-JAN-07:00 | 0.00 | 35.13 | 53.72 | 0.39 | 0.00 | 0.14 | 0.57 | 08-JAN-07:00 |
February | 0.799486E+11 | 0.00 | 524.60 | 114777.01 | 05-FEB-06:00 | 0.00 | 33.41 | 53.98 | 0.32 | 0.00 | 0.12 | 0.41 | 05-FEB-06:00 |
March | 0.110910E+12 | 0.00 | 586.48 | 145961.47 | 30-MAR-03:00 | 0.00 | 32.53 | 53.93 | 0.40 | 0.00 | 0.15 | 0.53 | 30-MAR-03:00 |
April | 0.473281E+11 | 0.00 | 398.74 | 108312.68 | 01-APR-05:00 | 0.00 | 29.35 | 46.24 | 0.15 | 0.00 | 0.07 | 0.39 | 01-APR-05:00 |
May | 0.412501E+11 | 0.00 | 370.11 | 96727.15 | 14-MAY-04:50 | 0.00 | 28.93 | 44.00 | 0.13 | 0.00 | 0.06 | 0.35 | 14-MAY-04:50 |
June | 0.746435E+10 | 0.00 | 157.87 | 64253.74 | 13-JUN-04:00 | 0.00 | 29.11 | 36.21 | 0.02 | 0.00 | 0.01 | 0.23 | 13-JUN-04:00 |
July | 0.484472E+09 | 0.00 | 36.20 | 26771.94 | 06-JUL-03:00 | 0.00 | 32.36 | 33.78 | 0.00 | 0.00 | 0.00 | 0.10 | 06-JUL-03:00 |
August | 0.221638E+09 | 0.00 | 27.52 | 24722.60 | 28-AUG-08:54 | 0.00 | 37.65 | 38.58 | 0.00 | 0.00 | 0.00 | 0.09 | 28-AUG-08:54 |
September | 0.342225E+10 | 0.00 | 84.27 | 60473.10 | 20-SEP-04:00 | 0.00 | 33.62 | 37.11 | 0.01 | 0.00 | 0.00 | 0.22 | 20-SEP-04:00 |
October | 0.168895E+11 | 0.00 | 166.55 | 90885.20 | 28-OCT-05:00 | 0.00 | 33.01 | 39.43 | 0.05 | 0.00 | 0.02 | 0.33 | 28-OCT-05:00 |
November | 0.669501E+11 | 0.00 | 455.79 | 104821.87 | 24-NOV-04:00 | 0.00 | 32.91 | 50.20 | 0.25 | 0.00 | 0.09 | 0.38 | 24-NOV-04:00 |
December | 0.101020E+12 | 0.00 | 515.31 | 120212.37 | 23-DEC-06:00 | 0.00 | 35.53 | 53.18 | 0.38 | 0.00 | 0.14 | 0.43 | 23-DEC-06:00 |
Annual Sum or Average | 0.580715E+12 | 0.00 | 3862.09 | 0.00 | 32.81 | 44.98 | 0.18 | 0.00 | 0.07 | ||||
Minimum of Months | 0.221638E+09 | 0.00 | 27.52 | 24722.60 | 0.00 | 28.93 | 33.78 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.110910E+12 | 0.00 | 586.48 | 157985.91 | 0.00 | 37.65 | 53.98 | 0.40 | 0.00 | 0.15 | 0.57 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.574553E+11 | 0.00 | 283.83 | 0.573052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209208.80 | 14-JAN-11:45 | 209208.80 | 14-JAN-11:45 | 0.00 | 0.00 | 0.00 |
February | 0.319855E+11 | 0.00 | 231.17 | 0.312701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197295.73 | 01-FEB-11:45 | 197295.73 | 01-FEB-11:45 | 0.00 | 0.00 | 0.00 |
March | 0.354940E+11 | 0.00 | 211.50 | 0.348869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180825.23 | 23-MAR-10:45 | 176188.36 | 11-MAR-11:45 | 0.00 | 0.00 | 0.00 |
April | 0.846909E+11 | 0.00 | 356.00 | 0.833200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 247984.44 | 26-APR-10:45 | 208185.26 | 30-APR-10:45 | 0.00 | 0.00 | 0.00 |
May | 0.906633E+11 | 0.00 | 435.00 | 0.897867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158994.96 | 18-MAY-10:45 | 157585.28 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.167383E+12 | 0.00 | 613.50 | 0.146626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310015.27 | 29-JUN-10:45 | 191716.12 | 29-JUN-10:45 | 0.00 | 0.00 | 0.00 |
July | 0.342462E+12 | 0.00 | 735.17 | 0.224523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 379363.38 | 31-JUL-10:45 | 241504.60 | 19-JUL-10:45 | 0.00 | 0.00 | 0.00 |
August | 0.385564E+12 | 0.00 | 736.67 | 0.234349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 406692.91 | 14-AUG-10:45 | 241588.81 | 14-AUG-10:45 | 0.00 | 0.00 | 0.00 |
September | 0.227607E+12 | 0.00 | 675.00 | 0.176344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 372683.64 | 22-SEP-12:00 | 364780.78 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.258823E+12 | 0.00 | 618.00 | 0.208948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 384235.76 | 16-OCT-10:45 | 384235.76 | 16-OCT-10:45 | 0.00 | 0.00 | 0.00 |
November | 0.597894E+11 | 0.00 | 340.67 | 0.591585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213902.40 | 19-NOV-11:45 | 213902.40 | 19-NOV-11:45 | 0.00 | 0.00 | 0.00 |
December | 0.662692E+11 | 0.00 | 294.83 | 0.662692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193106.60 | 19-DEC-11:45 | 193106.60 | 19-DEC-11:45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180819E+13 | 0.00 | 5531.33 | 0.141279E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.319855E+11 | 0.00 | 211.50 | 0.312701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158994.96 | 157585.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.385564E+12 | 0.00 | 736.67 | 0.234349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 406692.91 | 384235.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.352394E+10 | 0.00 | 171.17 | 0.349905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20570.98 | 13-JAN-14:00 | 20570.98 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.189694E+10 | 0.00 | 130.67 | 0.184114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 01-FEB-09:51 | 17583.23 | 01-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.213914E+10 | 0.00 | 109.83 | 0.197595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22012.17 | 22-MAR-13:00 | 17622.52 | 11-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.536186E+10 | 0.00 | 211.67 | 0.504844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22090.96 | 26-APR-13:00 | 22090.96 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.568659E+10 | 0.00 | 273.33 | 0.557961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18829.64 | 04-MAY-13:00 | 17662.38 | 03-MAY-12:15 | 0.00 | 0.00 | 0.00 |
June | 0.127689E+11 | 0.00 | 460.00 | 0.101524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30817.80 | 29-JUN-12:30 | 17826.82 | 29-JUN-12:15 | 0.00 | 0.00 | 0.00 |
July | 0.285718E+11 | 0.00 | 581.00 | 0.167816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 31-JUL-12:30 | 23766.73 | 31-JUL-12:30 | 0.00 | 0.00 | 0.00 |
August | 0.326065E+11 | 0.00 | 582.67 | 0.176854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38729.91 | 14-AUG-10:00 | 22286.10 | 18-AUG-12:20 | 0.00 | 0.00 | 0.00 |
September | 0.185738E+11 | 0.00 | 518.17 | 0.130116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39619.58 | 22-SEP-12:15 | 35123.90 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.206208E+11 | 0.00 | 461.00 | 0.151880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38860.24 | 01-OCT-12:10 | 34150.37 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.354751E+10 | 0.00 | 209.17 | 0.347968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21516.80 | 19-NOV-13:05 | 21516.80 | 19-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.428641E+10 | 0.00 | 177.33 | 0.428428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20480.92 | 05-DEC-09:55 | 20480.92 | 05-DEC-09:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139584E+12 | 0.00 | 3886.00 | 0.985272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.189694E+10 | 0.00 | 109.83 | 0.184114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 17583.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.326065E+11 | 0.00 | 582.67 | 0.176854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 35123.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.191871E+10 | 0.00 | 401.15 | 0.100795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14239.27 | 03-JAN-16:01 | 14239.27 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.170032E+10 | 0.00 | 315.67 | 0.933308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14578.27 | 13-FEB-16:02 | 14235.03 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.185571E+10 | 0.00 | 336.20 | 0.855041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13923.36 | 18-MAR-15:01 | 12711.73 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.386004E+10 | 0.00 | 543.96 | 0.185618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14007.03 | 08-APR-08:62 | 13760.34 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.360462E+10 | 0.00 | 550.01 | 0.165849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14271.68 | 06-MAY-08:62 | 13511.27 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.526085E+10 | 0.00 | 608.43 | 0.237790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.67 | 16-JUN-15:01 | 12916.61 | 30-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.757089E+10 | 0.00 | 679.85 | 0.359344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15059.65 | 30-JUL-08:61 | 12923.86 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.786349E+10 | 0.00 | 689.27 | 0.374912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.58 | 18-AUG-08:62 | 12952.03 | 05-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.609180E+10 | 0.00 | 647.71 | 0.283976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15073.32 | 22-SEP-08:62 | 12922.43 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.555890E+10 | 0.00 | 636.55 | 0.327707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15208.21 | 01-OCT-08:61 | 14240.33 | 18-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.263101E+10 | 0.00 | 480.45 | 0.137677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14561.31 | 12-NOV-09:02 | 14237.95 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.218230E+10 | 0.00 | 424.10 | 0.154968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14241.72 | 05-DEC-16:02 | 14241.72 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500986E+11 | 0.00 | 6313.34 | 0.250747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.170032E+10 | 0.00 | 315.67 | 0.855041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13923.36 | 12711.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.786349E+10 | 0.00 | 689.27 | 0.374912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.58 | 14241.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.400726E+09 | 0.00 | 143.13 | 0.189930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13714.97 | 14-JAN-16:01 | 13714.97 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.551930E+09 | 0.00 | 167.41 | 0.246052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13875.69 | 13-FEB-16:02 | 13713.65 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.790828E+09 | 0.00 | 200.58 | 0.299648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13816.83 | 22-MAR-18:51 | 12327.64 | 09-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.216010E+10 | 0.00 | 404.16 | 0.820813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14773.55 | 26-APR-21:51 | 13265.72 | 23-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.240894E+10 | 0.00 | 424.40 | 0.950428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14292.55 | 02-MAY-21:51 | 13101.59 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.333356E+10 | 0.00 | 395.35 | 0.141358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15305.42 | 28-JUN-21:51 | 12520.08 | 22-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.488563E+10 | 0.00 | 417.03 | 0.234808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15544.72 | 19-JUL-21:51 | 12122.86 | 15-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.463556E+10 | 0.00 | 413.12 | 0.213766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15525.07 | 19-AUG-08:51 | 12346.60 | 05-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.328257E+10 | 0.00 | 399.47 | 0.134100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15020.53 | 30-SEP-21:51 | 12346.95 | 18-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.258425E+10 | 0.00 | 381.13 | 0.141163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15449.47 | 01-OCT-08:52 | 14207.90 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.752993E+09 | 0.00 | 255.22 | 0.314451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13996.38 | 12-NOV-09:02 | 13715.44 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.424619E+09 | 0.00 | 164.70 | 0.286869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13719.51 | 31-DEC-16:01 | 13719.51 | 31-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262117E+11 | 0.00 | 3765.70 | 0.117601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.400726E+09 | 0.00 | 143.13 | 0.189930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13714.97 | 12122.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.488563E+10 | 0.00 | 424.40 | 0.234808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15544.72 | 14207.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.314637E+11 | 0.00 | 538.45 | 0.215651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44774.73 | 14-JAN-12:40 | 44774.73 | 14-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.197937E+11 | 0.00 | 386.79 | 0.126937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39959.64 | 02-FEB-12:30 | 37324.44 | 03-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.142695E+11 | 0.00 | 381.60 | 0.571585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33022.58 | 11-MAR-13:10 | 26644.32 | 11-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.164759E+11 | 0.00 | 488.65 | 0.522226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25114.32 | 08-APR-12:40 | 17008.11 | 02-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.923484E+10 | 0.00 | 439.86 | 0.199727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23781.09 | 04-MAY-15:03 | 10876.41 | 04-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.133570E+11 | 0.00 | 509.98 | 0.293034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18311.57 | 30-JUN-07:00 | 5692.27 | 30-JUN-07:00 | 0.00 | 0.00 | 0.00 |
July | 0.223705E+11 | 0.00 | 637.91 | 0.596089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25725.06 | 23-JUL-15:03 | 11341.46 | 23-JUL-15:03 | 0.00 | 0.00 | 0.00 |
August | 0.304191E+11 | 0.00 | 719.79 | 0.979213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24633.28 | 27-AUG-12:10 | 11892.12 | 30-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.329171E+11 | 0.00 | 692.84 | 0.134121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42230.61 | 30-SEP-13:05 | 39382.80 | 30-SEP-13:05 | 0.00 | 0.00 | 0.00 |
October | 0.414860E+11 | 0.00 | 677.86 | 0.264774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51380.22 | 16-OCT-12:20 | 51380.22 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.328573E+11 | 0.00 | 564.99 | 0.208223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48376.09 | 19-NOV-12:30 | 43338.76 | 19-NOV-10:40 | 0.00 | 0.00 | 0.00 |
December | 0.358677E+11 | 0.00 | 568.37 | 0.281757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46025.56 | 19-DEC-13:00 | 46025.56 | 19-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300512E+12 | 0.00 | 6607.09 | 0.154765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.923484E+10 | 0.00 | 381.60 | 0.199727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18311.57 | 5692.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.414860E+11 | 0.00 | 719.79 | 0.281757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51380.22 | 51380.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.978209E+10 | 0.00 | 300.03 | 0.472958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84898.66 | 20-JAN-19:01 | 82287.63 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.111114E+11 | 0.00 | 360.76 | 0.493709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83490.59 | 13-FEB-21:12 | 81136.55 | 03-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.139423E+11 | 0.00 | 380.01 | 0.585970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82361.33 | 22-MAR-18:51 | 80138.50 | 10-MAR-19:12 | 0.00 | 0.00 | 0.00 |
April | 0.215816E+11 | 0.00 | 411.02 | 0.101262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89739.03 | 26-APR-21:51 | 81006.83 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.258125E+11 | 0.00 | 407.34 | 0.133562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87568.42 | 04-MAY-21:51 | 79511.29 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.299231E+11 | 0.00 | 345.36 | 0.162785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92943.37 | 28-JUN-21:51 | 76796.30 | 22-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.365632E+11 | 0.00 | 361.24 | 0.206085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94996.09 | 19-JUL-21:51 | 76127.49 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.338858E+11 | 0.00 | 348.50 | 0.181904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93875.40 | 16-AUG-21:51 | 74631.11 | 22-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.263197E+11 | 0.00 | 327.88 | 0.132247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93243.26 | 22-SEP-21:52 | 75240.94 | 02-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.235691E+11 | 0.00 | 354.14 | 0.145993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93073.43 | 01-OCT-08:52 | 86737.19 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.129231E+11 | 0.00 | 373.76 | 0.628219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85374.22 | 09-NOV-22:53 | 81350.07 | 28-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.903571E+10 | 0.00 | 307.36 | 0.546505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81865.66 | 05-DEC-16:02 | 81865.66 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254450E+12 | 0.00 | 4277.40 | 0.133657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.903571E+10 | 0.00 | 300.03 | 0.472958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81865.66 | 74631.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.365632E+11 | 0.00 | 411.02 | 0.206085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94996.09 | 86737.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.204059E+10 | 0.00 | 414.03 | 0.118754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12597.74 | 03-JAN-16:01 | 12597.74 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.159971E+10 | 0.00 | 311.11 | 0.927738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12597.84 | 01-FEB-09:01 | 12597.84 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.183639E+10 | 0.00 | 336.10 | 0.867316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12306.10 | 15-MAR-15:01 | 11351.97 | 19-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.351168E+10 | 0.00 | 549.63 | 0.169643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12592.62 | 02-APR-08:62 | 12592.62 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.309002E+10 | 0.00 | 539.55 | 0.140316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12751.14 | 06-MAY-08:62 | 12588.93 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.446306E+10 | 0.00 | 619.98 | 0.197884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12979.13 | 28-JUN-08:62 | 11440.55 | 22-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.692840E+10 | 0.00 | 703.90 | 0.326331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12760.44 | 13-JUL-18:01 | 11464.72 | 06-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.750859E+10 | 0.00 | 708.23 | 0.359781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12994.27 | 08-AUG-08:62 | 11475.37 | 31-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.525808E+10 | 0.00 | 646.98 | 0.241236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13212.99 | 23-SEP-08:62 | 11456.09 | 08-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.527047E+10 | 0.00 | 641.23 | 0.317353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13489.85 | 01-OCT-08:61 | 12598.90 | 18-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.243818E+10 | 0.00 | 474.52 | 0.140161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12893.94 | 12-NOV-09:02 | 12595.62 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.218862E+10 | 0.00 | 431.81 | 0.165657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12598.68 | 23-DEC-09:01 | 12598.68 | 23-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461338E+11 | 0.00 | 6377.06 | 0.235662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.159971E+10 | 0.00 | 311.11 | 0.867316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12306.10 | 11351.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.750859E+10 | 0.00 | 708.23 | 0.359781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13489.85 | 12598.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.535782E+09 | 0.00 | 148.35 | 0.288243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12176.85 | 20-JAN-19:01 | 12032.71 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.556899E+09 | 0.00 | 151.86 | 0.296744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12247.36 | 01-FEB-09:51 | 12247.36 | 01-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.857113E+09 | 0.00 | 205.91 | 0.381529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12082.71 | 24-MAR-15:01 | 11581.45 | 23-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.210116E+10 | 0.00 | 387.44 | 0.989115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12939.02 | 02-APR-08:51 | 12939.02 | 02-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.216571E+10 | 0.00 | 411.27 | 0.972426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13274.28 | 24-MAY-08:51 | 13274.28 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.297547E+10 | 0.00 | 407.24 | 0.132169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13835.82 | 30-JUN-08:51 | 12316.39 | 14-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.458800E+10 | 0.00 | 432.25 | 0.219690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14344.28 | 30-JUL-08:51 | 12270.87 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.452885E+10 | 0.00 | 433.39 | 0.212270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14576.97 | 18-AUG-08:51 | 11945.14 | 22-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.273979E+10 | 0.00 | 406.33 | 0.121024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14010.14 | 10-SEP-08:51 | 11984.76 | 12-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.241698E+10 | 0.00 | 389.76 | 0.143134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14032.94 | 17-OCT-08:21 | 14032.94 | 17-OCT-08:21 | 0.00 | 0.00 | 0.00 |
November | 0.731584E+09 | 0.00 | 203.03 | 0.364404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12361.73 | 12-NOV-09:02 | 12038.60 | 28-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.463394E+09 | 0.00 | 146.43 | 0.326505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12770.69 | 05-DEC-09:41 | 12770.69 | 05-DEC-09:41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246607E+11 | 0.00 | 3723.25 | 0.119018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.463394E+09 | 0.00 | 146.43 | 0.288243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12082.71 | 11581.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.458800E+10 | 0.00 | 433.39 | 0.219690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14576.97 | 14032.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.410664E+09 | 0.00 | 316.30 | 0.229603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3840.74 | 21-JAN-09:02 | 3685.20 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.373467E+09 | 0.00 | 238.92 | 0.215122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3779.79 | 13-FEB-16:02 | 3684.09 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.443135E+09 | 0.00 | 260.15 | 0.221848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3697.44 | 24-MAR-08:61 | 3343.82 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.941031E+09 | 0.00 | 471.75 | 0.486424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.12 | 12-APR-08:62 | 3595.64 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.860524E+09 | 0.00 | 477.22 | 0.420163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3881.14 | 06-MAY-08:62 | 3471.87 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.129313E+10 | 0.00 | 586.62 | 0.616889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.23 | 28-JUN-08:62 | 3355.60 | 05-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.190395E+10 | 0.00 | 688.15 | 0.933156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.40 | 30-JUL-08:61 | 3354.53 | 27-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.195071E+10 | 0.00 | 688.22 | 0.956387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4138.31 | 06-AUG-08:61 | 3326.02 | 01-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.143606E+10 | 0.00 | 634.36 | 0.692422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.53 | 22-SEP-08:62 | 3331.45 | 17-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.126800E+10 | 0.00 | 572.76 | 0.762886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4104.90 | 01-OCT-08:61 | 3685.06 | 13-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.551249E+09 | 0.00 | 373.25 | 0.299447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3721.05 | 11-NOV-16:01 | 3684.92 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.459409E+09 | 0.00 | 336.90 | 0.339355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3685.90 | 05-DEC-16:02 | 3685.90 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118913E+11 | 0.00 | 5644.62 | 0.617370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.373467E+09 | 0.00 | 238.92 | 0.215122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3685.90 | 3326.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195071E+10 | 0.00 | 688.22 | 0.956387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4138.31 | 3685.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 68657856.61 | 0.00 | 77.94 | 36929445.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.58 | 14-JAN-16:01 | 3541.58 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.100500E+09 | 0.00 | 106.54 | 48548239.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.30 | 06-FEB-16:01 | 3541.30 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.174698E+09 | 0.00 | 147.79 | 72526573.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3632.99 | 22-MAR-18:51 | 3245.68 | 19-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.511356E+09 | 0.00 | 336.15 | 0.211393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3917.86 | 26-APR-21:51 | 3541.76 | 23-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.569708E+09 | 0.00 | 377.34 | 0.242038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3776.67 | 03-MAY-21:51 | 3399.40 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.863079E+09 | 0.00 | 395.59 | 0.383161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4063.79 | 28-JUN-21:51 | 3324.87 | 04-JUN-19:31 | 0.00 | 0.00 | 0.00 |
July | 0.131327E+10 | 0.00 | 422.83 | 0.651353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4117.27 | 27-JUL-21:51 | 3197.69 | 08-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.121345E+10 | 0.00 | 419.12 | 0.571484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4081.63 | 16-AUG-21:51 | 3101.47 | 21-AUG-20:11 | 0.00 | 0.00 | 0.00 |
September | 0.768472E+09 | 0.00 | 404.29 | 0.317929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3935.76 | 30-SEP-21:51 | 3184.98 | 19-SEP-19:01 | 0.00 | 0.00 | 0.00 |
October | 0.561017E+09 | 0.00 | 329.65 | 0.317850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4072.36 | 01-OCT-08:52 | 3606.20 | 14-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.116378E+09 | 0.00 | 147.04 | 53962318.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3550.66 | 11-NOV-16:01 | 3541.91 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 64803156.34 | 0.00 | 78.06 | 49331065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.66 | 30-DEC-16:01 | 3541.66 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632539E+10 | 0.00 | 3242.36 | 0.295651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 64803156.34 | 0.00 | 77.94 | 36929445.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.30 | 3101.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131327E+10 | 0.00 | 422.83 | 0.651353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4117.27 | 3606.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.725121E+10 | 0.00 | 554.49 | 0.515667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17392.91 | 15-JAN-16:01 | 17392.91 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.477842E+10 | 0.00 | 433.36 | 0.317392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17941.41 | 11-FEB-16:02 | 17390.21 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.415033E+10 | 0.00 | 423.34 | 0.218387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17249.14 | 20-MAR-15:01 | 15777.69 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.507629E+10 | 0.00 | 554.60 | 0.231917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17130.58 | 08-APR-08:62 | 17047.64 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.321881E+10 | 0.00 | 483.61 | 0.120638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17570.87 | 06-MAY-08:62 | 16191.27 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.441828E+10 | 0.00 | 567.67 | 0.159503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17922.54 | 16-JUN-15:01 | 15478.26 | 21-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.715796E+10 | 0.00 | 656.59 | 0.285181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18923.73 | 30-JUL-08:61 | 15828.72 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.901568E+10 | 0.00 | 677.94 | 0.390682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19089.20 | 20-AUG-08:61 | 15840.76 | 02-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.868136E+10 | 0.00 | 641.44 | 0.428469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18654.41 | 22-SEP-08:62 | 15599.35 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.999215E+10 | 0.00 | 655.04 | 0.675005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19109.85 | 05-OCT-18:01 | 17391.39 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.746247E+10 | 0.00 | 588.26 | 0.511122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17819.07 | 11-NOV-16:01 | 17388.33 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.780442E+10 | 0.00 | 564.29 | 0.628712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17392.48 | 29-DEC-19:01 | 17392.48 | 29-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790074E+11 | 0.00 | 6800.66 | 0.448267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.321881E+10 | 0.00 | 423.34 | 0.120638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17130.58 | 15478.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.999215E+10 | 0.00 | 677.94 | 0.675005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19109.85 | 17392.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.88 | 507.95 | 183.94 | 1017.04 | 358.39 | 0.00 | 0.00 | 0.00 |
February | 546.53 | 338.18 | 208.36 | 767.72 | 323.60 | 0.00 | 0.00 | 0.00 |
March | 435.89 | 212.33 | 223.56 | 609.74 | 333.49 | 0.00 | 0.00 | 0.00 |
April | 364.49 | 140.88 | 223.62 | 545.02 | 268.62 | 0.00 | 0.00 | 0.00 |
May | 256.82 | 31.10 | 225.72 | 331.30 | 235.63 | 0.00 | 0.00 | 0.00 |
June | 225.30 | 13.21 | 212.09 | 296.03 | 176.16 | 0.00 | 0.00 | 0.00 |
July | 237.61 | 25.41 | 212.20 | 351.79 | 155.50 | 0.00 | 0.00 | 0.00 |
August | 305.17 | 94.83 | 210.34 | 500.15 | 168.31 | 0.00 | 0.00 | 0.00 |
September | 419.06 | 208.19 | 210.87 | 676.55 | 201.19 | 0.00 | 0.00 | 0.00 |
October | 548.73 | 368.52 | 180.22 | 885.13 | 223.80 | 0.00 | 0.00 | 0.00 |
November | 666.54 | 472.26 | 194.28 | 982.41 | 323.57 | 0.00 | 0.00 | 0.00 |
December | 740.41 | 564.21 | 176.20 | 1093.85 | 360.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.81 | 247.78 | 205.03 | 671.11 | 260.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.30 | 13.21 | 176.20 | 296.03 | 155.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 740.41 | 564.21 | 225.72 | 1093.85 | 360.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1948.30 | 1430.34 | 517.96 | 2824.28 | 1096.53 | 0.00 | 0.00 | 0.00 |
February | 1539.00 | 952.28 | 586.71 | 2120.78 | 1008.65 | 0.00 | 0.00 | 0.00 |
March | 1227.43 | 597.91 | 629.52 | 1678.46 | 1028.04 | 0.00 | 0.00 | 0.00 |
April | 1026.39 | 396.71 | 629.69 | 1497.43 | 844.38 | 0.00 | 0.00 | 0.00 |
May | 723.18 | 87.58 | 635.60 | 891.18 | 746.92 | 0.00 | 0.00 | 0.00 |
June | 634.43 | 37.21 | 597.22 | 793.99 | 569.17 | 0.00 | 0.00 | 0.00 |
July | 669.08 | 71.55 | 597.53 | 960.20 | 495.06 | 0.00 | 0.00 | 0.00 |
August | 859.34 | 267.03 | 592.31 | 1384.41 | 530.26 | 0.00 | 0.00 | 0.00 |
September | 1180.05 | 586.24 | 593.81 | 1877.92 | 632.88 | 0.00 | 0.00 | 0.00 |
October | 1545.20 | 1037.72 | 507.48 | 2460.45 | 696.96 | 0.00 | 0.00 | 0.00 |
November | 1876.94 | 1329.86 | 547.08 | 2723.94 | 1002.49 | 0.00 | 0.00 | 0.00 |
December | 2084.94 | 1588.78 | 496.16 | 3039.17 | 1101.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1275.09 | 697.73 | 577.36 | 1853.60 | 811.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 634.43 | 37.21 | 496.16 | 793.99 | 495.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2084.94 | 1588.78 | 635.60 | 3039.17 | 1101.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2530.95 | 1858.09 | 672.86 | 3761.37 | 1445.85 | 0.00 | 0.00 | 0.00 |
February | 1999.24 | 1237.07 | 762.17 | 2820.43 | 1349.65 | 0.00 | 0.00 | 0.00 |
March | 1594.50 | 776.72 | 817.79 | 2231.23 | 1385.54 | 0.00 | 0.00 | 0.00 |
April | 1333.34 | 515.34 | 818.00 | 1993.87 | 1135.89 | 0.00 | 0.00 | 0.00 |
May | 939.45 | 113.77 | 825.68 | 1167.82 | 1027.73 | 0.00 | 0.00 | 0.00 |
June | 824.17 | 48.34 | 775.83 | 1036.99 | 785.31 | 0.00 | 0.00 | 0.00 |
July | 869.17 | 92.94 | 776.23 | 1267.65 | 677.15 | 0.00 | 0.00 | 0.00 |
August | 1116.33 | 346.89 | 769.44 | 1845.30 | 708.96 | 0.00 | 0.00 | 0.00 |
September | 1532.95 | 761.56 | 771.39 | 2504.04 | 839.38 | 0.00 | 0.00 | 0.00 |
October | 2007.30 | 1348.05 | 659.24 | 3270.16 | 918.03 | 0.00 | 0.00 | 0.00 |
November | 2438.25 | 1727.56 | 710.69 | 3622.67 | 1325.35 | 0.00 | 0.00 | 0.00 |
December | 2708.45 | 2063.92 | 644.54 | 4041.64 | 1454.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1656.41 | 906.39 | 750.02 | 2462.57 | 1086.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 824.17 | 48.34 | 644.54 | 1036.99 | 677.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2708.45 | 2063.92 | 825.68 | 4041.64 | 1454.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 203.72 | 73.20 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 151.52 | 67.17 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 119.25 | 71.15 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 106.19 | 56.54 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 61.79 | 51.00 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 55.76 | 36.76 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.97 | 30.45 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 100.29 | 31.60 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 135.73 | 38.13 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.67 | 41.68 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 196.36 | 65.07 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 219.23 | 72.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 133.08 | 52.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 55.76 | 30.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 219.23 | 73.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 123.85 | 148.26 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 141.90 | 131.85 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 167.13 | 134.38 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 263.33 | 102.00 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 253.08 | 90.45 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 286.34 | 64.41 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 321.89 | 53.50 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 304.40 | 56.59 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 250.62 | 69.19 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 197.91 | 81.11 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 148.02 | 129.77 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 127.95 | 148.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 215.90 | 100.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 123.85 | 53.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 321.89 | 148.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 14.45 | 79.47 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.30 | 71.66 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 23.69 | 73.89 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 32.53 | 56.18 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 41.19 | 48.24 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 52.22 | 36.40 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 55.18 | 32.35 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 44.87 | 34.39 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 35.52 | 41.12 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 32.29 | 46.32 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 16.55 | 70.69 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.11 | 79.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 31.59 | 55.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.11 | 32.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 55.18 | 79.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 129.93 | 144.60 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 146.29 | 129.37 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 170.00 | 133.02 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 262.45 | 103.15 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 249.47 | 92.86 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 278.65 | 70.01 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 313.11 | 61.12 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 298.29 | 63.93 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 248.95 | 73.17 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 199.13 | 83.94 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 153.08 | 127.34 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 134.10 | 144.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 215.63 | 102.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 129.93 | 61.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 313.11 | 144.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.42 | 80.33 | 29.09 | 148.46 | 86.71 | 0.00 | 0.00 | 0.00 |
February | 86.43 | 53.48 | 32.95 | 107.19 | 82.46 | 0.00 | 0.00 | 0.00 |
March | 68.93 | 33.58 | 35.35 | 82.07 | 84.36 | 0.00 | 0.00 | 0.00 |
April | 57.64 | 22.28 | 35.36 | 72.04 | 70.30 | 0.00 | 0.00 | 0.00 |
May | 40.61 | 4.92 | 35.70 | 36.29 | 64.55 | 0.00 | 0.00 | 0.00 |
June | 35.63 | 2.09 | 33.54 | 30.91 | 51.13 | 0.00 | 0.00 | 0.00 |
July | 37.58 | 4.02 | 33.56 | 41.29 | 44.74 | 0.00 | 0.00 | 0.00 |
August | 48.26 | 15.00 | 33.26 | 66.54 | 47.01 | 0.00 | 0.00 | 0.00 |
September | 66.27 | 32.92 | 33.35 | 95.28 | 54.25 | 0.00 | 0.00 | 0.00 |
October | 86.78 | 58.28 | 28.50 | 128.74 | 57.97 | 0.00 | 0.00 | 0.00 |
November | 105.41 | 74.68 | 30.72 | 142.50 | 79.48 | 0.00 | 0.00 | 0.00 |
December | 117.09 | 89.23 | 27.86 | 160.50 | 86.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.61 | 39.18 | 32.42 | 92.61 | 67.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.63 | 2.09 | 27.86 | 30.91 | 44.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.09 | 89.23 | 35.70 | 160.50 | 86.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.54 | 0.00 | 16.54 | 11.87 | 64.31 | 0.00 | 0.00 | 0.00 |
February | 20.77 | 0.00 | 20.77 | 13.56 | 57.73 | 0.00 | 0.00 | 0.00 |
March | 25.45 | 0.00 | 25.45 | 19.76 | 59.37 | 0.00 | 0.00 | 0.00 |
April | 29.48 | 0.24 | 29.24 | 29.09 | 43.12 | 0.00 | 0.00 | 0.00 |
May | 35.46 | 1.85 | 33.61 | 36.41 | 37.41 | 0.00 | 0.00 | 0.00 |
June | 37.59 | 3.71 | 33.88 | 46.19 | 27.41 | 0.00 | 0.00 | 0.00 |
July | 35.61 | 3.02 | 32.58 | 49.15 | 23.48 | 0.00 | 0.00 | 0.00 |
August | 29.60 | 0.66 | 28.95 | 40.33 | 24.64 | 0.00 | 0.00 | 0.00 |
September | 24.99 | 0.00 | 24.98 | 31.48 | 30.20 | 0.00 | 0.00 | 0.00 |
October | 19.82 | 0.00 | 19.82 | 27.85 | 35.23 | 0.00 | 0.00 | 0.00 |
November | 17.95 | 0.00 | 17.95 | 14.16 | 55.94 | 0.00 | 0.00 | 0.00 |
December | 15.40 | 0.00 | 15.40 | 10.96 | 64.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.74 | 0.79 | 24.95 | 27.65 | 43.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.40 | 0.00 | 15.40 | 10.96 | 23.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.59 | 3.71 | 33.88 | 49.15 | 64.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 125.88 | 140.60 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 123.47 | 126.15 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 160.42 | 128.31 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 235.89 | 97.80 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 216.52 | 87.61 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 233.12 | 63.82 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 284.35 | 53.51 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 283.44 | 55.31 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 194.94 | 67.69 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 175.90 | 77.17 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 128.06 | 124.51 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 121.44 | 140.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 190.75 | 96.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 121.44 | 53.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 284.35 | 140.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 202.84 | 72.98 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 151.05 | 66.55 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 118.39 | 70.60 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 105.30 | 55.56 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 61.20 | 49.99 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 55.43 | 35.64 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.33 | 29.41 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 99.56 | 30.69 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 135.67 | 36.95 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.29 | 41.08 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 195.91 | 64.46 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 218.56 | 72.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 132.50 | 52.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 55.43 | 29.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 218.56 | 72.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 13.65 | 79.02 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 15.72 | 70.61 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 22.85 | 73.09 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 31.90 | 54.50 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 41.21 | 46.83 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 53.07 | 34.44 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 55.34 | 30.24 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 44.22 | 32.28 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 35.46 | 38.69 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 31.57 | 45.03 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 15.99 | 69.39 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 12.30 | 78.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 31.20 | 54.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 12.30 | 30.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 55.34 | 79.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 131.36 | 135.87 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 127.78 | 122.91 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 163.54 | 126.57 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 236.61 | 98.30 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 214.54 | 89.48 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 228.19 | 68.23 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 277.55 | 59.68 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 278.03 | 60.98 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 194.38 | 70.25 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 177.09 | 79.22 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 132.82 | 120.62 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 126.85 | 135.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 191.17 | 97.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 126.85 | 59.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 278.03 | 135.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 18.27 | 100.43 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 21.47 | 90.53 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 32.35 | 91.10 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 46.66 | 68.45 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 59.34 | 59.27 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 75.22 | 43.71 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 78.48 | 38.40 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 62.95 | 41.38 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 48.53 | 50.82 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 41.43 | 59.90 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 20.97 | 90.85 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 16.09 | 101.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 43.61 | 69.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 16.09 | 38.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 78.48 | 101.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.65 | 0.00 | 9.65 | 6.73 | 37.02 | 0.00 | 0.00 | 0.00 |
February | 12.12 | 0.00 | 12.12 | 7.92 | 33.37 | 0.00 | 0.00 | 0.00 |
March | 14.85 | 0.00 | 14.85 | 11.92 | 33.58 | 0.00 | 0.00 | 0.00 |
April | 17.20 | 0.14 | 17.06 | 17.20 | 25.23 | 0.00 | 0.00 | 0.00 |
May | 20.69 | 1.08 | 19.61 | 21.88 | 21.85 | 0.00 | 0.00 | 0.00 |
June | 21.93 | 2.17 | 19.77 | 27.73 | 16.11 | 0.00 | 0.00 | 0.00 |
July | 20.78 | 1.76 | 19.01 | 28.93 | 14.16 | 0.00 | 0.00 | 0.00 |
August | 17.27 | 0.38 | 16.89 | 23.20 | 15.26 | 0.00 | 0.00 | 0.00 |
September | 14.58 | 0.00 | 14.58 | 17.89 | 18.73 | 0.00 | 0.00 | 0.00 |
October | 11.57 | 0.00 | 11.57 | 15.27 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 10.47 | 0.00 | 10.47 | 7.73 | 33.49 | 0.00 | 0.00 | 0.00 |
December | 8.99 | 0.00 | 8.99 | 5.93 | 37.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.02 | 0.46 | 14.56 | 16.08 | 25.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.99 | 0.00 | 8.99 | 5.93 | 14.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.93 | 2.17 | 19.77 | 28.93 | 37.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.83 | 46.86 | 16.97 | 96.52 | 33.43 | 0.00 | 0.00 | 0.00 |
February | 50.42 | 31.20 | 19.22 | 72.17 | 30.93 | 0.00 | 0.00 | 0.00 |
March | 40.21 | 19.59 | 20.62 | 57.26 | 32.22 | 0.00 | 0.00 | 0.00 |
April | 33.63 | 13.00 | 20.63 | 51.41 | 25.83 | 0.00 | 0.00 | 0.00 |
May | 23.69 | 2.87 | 20.82 | 30.50 | 23.59 | 0.00 | 0.00 | 0.00 |
June | 20.79 | 1.22 | 19.57 | 27.40 | 17.54 | 0.00 | 0.00 | 0.00 |
July | 21.92 | 2.34 | 19.58 | 33.18 | 15.13 | 0.00 | 0.00 | 0.00 |
August | 28.15 | 8.75 | 19.41 | 47.55 | 15.89 | 0.00 | 0.00 | 0.00 |
September | 38.66 | 19.21 | 19.45 | 64.24 | 18.63 | 0.00 | 0.00 | 0.00 |
October | 50.62 | 34.00 | 16.63 | 83.62 | 20.79 | 0.00 | 0.00 | 0.00 |
November | 61.49 | 43.57 | 17.92 | 92.79 | 30.43 | 0.00 | 0.00 | 0.00 |
December | 68.31 | 52.05 | 16.25 | 103.55 | 33.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 22.86 | 18.92 | 63.33 | 24.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.79 | 1.22 | 16.25 | 27.40 | 15.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.31 | 52.05 | 20.82 | 103.55 | 33.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.25 | 127.19 | 46.06 | 261.97 | 90.73 | 0.00 | 0.00 | 0.00 |
February | 136.85 | 84.68 | 52.17 | 195.88 | 83.95 | 0.00 | 0.00 | 0.00 |
March | 109.15 | 53.17 | 55.98 | 155.43 | 87.44 | 0.00 | 0.00 | 0.00 |
April | 91.27 | 35.28 | 55.99 | 139.52 | 70.11 | 0.00 | 0.00 | 0.00 |
May | 64.31 | 7.79 | 56.52 | 82.78 | 64.02 | 0.00 | 0.00 | 0.00 |
June | 56.42 | 3.31 | 53.11 | 74.38 | 47.62 | 0.00 | 0.00 | 0.00 |
July | 59.50 | 6.36 | 53.13 | 90.06 | 41.05 | 0.00 | 0.00 | 0.00 |
August | 76.41 | 23.74 | 52.67 | 129.07 | 43.13 | 0.00 | 0.00 | 0.00 |
September | 104.93 | 52.13 | 52.80 | 174.37 | 50.56 | 0.00 | 0.00 | 0.00 |
October | 137.40 | 92.28 | 45.13 | 226.96 | 56.42 | 0.00 | 0.00 | 0.00 |
November | 166.90 | 118.25 | 48.65 | 251.86 | 82.60 | 0.00 | 0.00 | 0.00 |
December | 185.40 | 141.28 | 44.12 | 281.04 | 91.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.38 | 62.04 | 51.34 | 171.88 | 67.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.42 | 3.31 | 44.12 | 74.38 | 41.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 185.40 | 141.28 | 56.52 | 281.04 | 91.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 202.59 | 72.37 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 150.09 | 66.34 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 117.92 | 70.71 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 104.54 | 56.19 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 60.40 | 50.75 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 54.51 | 36.55 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 67.72 | 30.20 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 98.86 | 31.28 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 134.19 | 37.62 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 177.31 | 40.91 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 194.98 | 64.18 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 218.00 | 71.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 131.72 | 52.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 54.51 | 30.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 218.00 | 72.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 122.26 | 146.07 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 139.94 | 129.79 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 164.36 | 133.10 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 258.96 | 101.11 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 248.60 | 89.71 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 281.50 | 63.83 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 317.36 | 52.85 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 300.17 | 55.86 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 247.06 | 68.13 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 195.83 | 79.41 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 146.25 | 127.52 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 126.68 | 145.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 212.78 | 99.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 122.26 | 52.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 317.36 | 146.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 14.72 | 78.02 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.44 | 70.44 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 23.32 | 73.33 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 31.45 | 56.36 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 39.76 | 48.39 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 50.22 | 37.14 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 53.33 | 33.27 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 43.62 | 35.25 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 34.83 | 41.14 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 32.32 | 45.46 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 16.87 | 69.24 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.60 | 77.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 30.97 | 55.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.60 | 33.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 53.33 | 78.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 129.22 | 141.81 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 144.97 | 126.99 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 167.40 | 131.78 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 257.54 | 103.00 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 244.27 | 92.92 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 272.47 | 71.13 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 307.16 | 62.55 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 293.07 | 65.07 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 245.13 | 72.82 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 197.44 | 82.25 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 152.17 | 124.54 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 133.88 | 140.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 212.40 | 101.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 129.22 | 62.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 307.16 | 141.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.63 | 147.29 | 53.34 | 292.05 | 110.71 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 98.06 | 60.42 | 216.44 | 100.70 | 0.00 | 0.00 | 0.00 |
March | 126.40 | 61.57 | 64.83 | 170.54 | 105.81 | 0.00 | 0.00 | 0.00 |
April | 105.69 | 40.85 | 64.84 | 153.72 | 81.36 | 0.00 | 0.00 | 0.00 |
May | 74.47 | 9.02 | 65.45 | 90.79 | 72.36 | 0.00 | 0.00 | 0.00 |
June | 65.33 | 3.83 | 61.50 | 83.47 | 50.79 | 0.00 | 0.00 | 0.00 |
July | 68.90 | 7.37 | 61.53 | 103.27 | 41.18 | 0.00 | 0.00 | 0.00 |
August | 88.49 | 27.50 | 60.99 | 147.53 | 43.42 | 0.00 | 0.00 | 0.00 |
September | 121.52 | 60.37 | 61.15 | 197.22 | 54.00 | 0.00 | 0.00 | 0.00 |
October | 159.12 | 106.86 | 52.26 | 258.59 | 60.70 | 0.00 | 0.00 | 0.00 |
November | 193.28 | 136.94 | 56.34 | 281.96 | 97.51 | 0.00 | 0.00 | 0.00 |
December | 214.70 | 163.60 | 51.09 | 314.55 | 109.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.30 | 71.85 | 59.45 | 192.46 | 77.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 3.83 | 51.09 | 83.47 | 41.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.70 | 163.60 | 65.45 | 314.55 | 110.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 73.01 | 641.76 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 83.71 | 596.93 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 132.11 | 600.38 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 200.04 | 449.84 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 255.70 | 387.95 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 343.68 | 288.85 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 372.52 | 248.28 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 297.40 | 267.66 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 225.31 | 330.44 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 197.98 | 380.64 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 87.43 | 576.89 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 64.41 | 644.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 195.14 | 450.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 64.41 | 248.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 372.52 | 644.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 65.38 | 663.69 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 74.94 | 618.33 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 121.27 | 620.52 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 187.91 | 463.41 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 241.53 | 398.98 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 330.60 | 297.91 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 360.92 | 256.20 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 286.81 | 276.61 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 215.47 | 341.90 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 189.23 | 393.26 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 79.20 | 595.61 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 57.31 | 666.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 184.90 | 465.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 57.31 | 256.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 360.92 | 666.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 16.87 | 81.12 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 18.59 | 77.42 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 27.12 | 78.65 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 40.61 | 59.92 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 51.60 | 53.36 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 66.27 | 40.11 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 71.27 | 34.57 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 58.85 | 36.52 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 45.35 | 42.14 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 39.84 | 48.07 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 19.85 | 72.89 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 15.58 | 81.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 39.45 | 58.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 15.58 | 34.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 71.27 | 81.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.05 | 111.16 | 96.89 | 280.06 | 284.16 | 0.00 | 0.00 | 0.00 |
February | 219.54 | 100.46 | 119.08 | 268.45 | 274.45 | 0.00 | 0.00 | 0.00 |
March | 267.94 | 119.67 | 148.26 | 345.93 | 277.38 | 0.00 | 0.00 | 0.00 |
April | 341.54 | 171.37 | 170.17 | 507.71 | 218.26 | 0.00 | 0.00 | 0.00 |
May | 321.70 | 134.06 | 187.64 | 466.18 | 201.76 | 0.00 | 0.00 | 0.00 |
June | 320.07 | 138.95 | 181.12 | 503.66 | 155.19 | 0.00 | 0.00 | 0.00 |
July | 362.45 | 180.07 | 182.38 | 612.82 | 133.53 | 0.00 | 0.00 | 0.00 |
August | 358.23 | 190.39 | 167.84 | 610.67 | 137.66 | 0.00 | 0.00 | 0.00 |
September | 261.54 | 120.30 | 141.24 | 428.32 | 155.79 | 0.00 | 0.00 | 0.00 |
October | 230.50 | 118.31 | 112.19 | 388.04 | 172.69 | 0.00 | 0.00 | 0.00 |
November | 209.64 | 106.13 | 103.51 | 283.25 | 257.72 | 0.00 | 0.00 | 0.00 |
December | 201.53 | 112.32 | 89.21 | 270.09 | 284.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.60 | 133.87 | 141.73 | 414.77 | 212.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.53 | 100.46 | 89.21 | 268.45 | 133.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.45 | 190.39 | 187.64 | 612.82 | 284.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 212.17 | 74.80 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 157.95 | 73.26 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 125.51 | 76.34 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 114.80 | 61.19 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 69.70 | 56.84 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 65.56 | 42.84 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 80.48 | 36.26 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 111.54 | 37.54 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 146.09 | 42.14 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 188.35 | 46.30 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 204.82 | 67.90 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 227.63 | 74.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 142.02 | 57.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 65.56 | 36.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 227.63 | 76.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 16.12 | 102.03 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 19.28 | 91.71 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 29.23 | 93.17 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 42.34 | 70.45 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 54.89 | 60.76 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 69.87 | 45.52 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 73.12 | 40.15 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 58.10 | 43.43 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 44.72 | 52.64 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 38.59 | 61.24 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 19.07 | 91.23 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 14.34 | 102.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 40.10 | 71.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 14.34 | 40.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 73.12 | 102.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 14.42 | 91.27 | 0.00 | 0.00 | 0.00 |
February | 29.41 | 0.00 | 29.41 | 17.25 | 82.05 | 0.00 | 0.00 | 0.00 |
March | 36.04 | 0.00 | 36.04 | 26.15 | 83.36 | 0.00 | 0.00 | 0.00 |
April | 41.74 | 0.34 | 41.41 | 37.88 | 63.03 | 0.00 | 0.00 | 0.00 |
May | 50.22 | 2.62 | 47.60 | 49.11 | 54.37 | 0.00 | 0.00 | 0.00 |
June | 53.23 | 5.26 | 47.97 | 62.51 | 40.73 | 0.00 | 0.00 | 0.00 |
July | 50.42 | 4.28 | 46.15 | 65.42 | 35.93 | 0.00 | 0.00 | 0.00 |
August | 41.92 | 0.93 | 40.99 | 51.98 | 38.86 | 0.00 | 0.00 | 0.00 |
September | 35.39 | 0.01 | 35.38 | 40.01 | 47.10 | 0.00 | 0.00 | 0.00 |
October | 28.07 | 0.00 | 28.07 | 34.53 | 54.79 | 0.00 | 0.00 | 0.00 |
November | 25.41 | 0.00 | 25.41 | 17.06 | 81.63 | 0.00 | 0.00 | 0.00 |
December | 21.81 | 0.00 | 21.81 | 12.83 | 91.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.46 | 1.13 | 35.33 | 35.88 | 63.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.81 | 0.00 | 21.81 | 12.83 | 35.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.23 | 5.26 | 47.97 | 65.42 | 91.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.71 | 374.93 | 135.77 | 760.51 | 271.55 | 0.00 | 0.00 | 0.00 |
February | 403.42 | 249.62 | 153.80 | 565.42 | 251.07 | 0.00 | 0.00 | 0.00 |
March | 321.75 | 156.73 | 165.02 | 445.14 | 264.34 | 0.00 | 0.00 | 0.00 |
April | 269.05 | 103.99 | 165.06 | 396.28 | 213.47 | 0.00 | 0.00 | 0.00 |
May | 189.57 | 22.96 | 166.61 | 230.41 | 194.66 | 0.00 | 0.00 | 0.00 |
June | 166.31 | 9.75 | 156.55 | 204.55 | 147.26 | 0.00 | 0.00 | 0.00 |
July | 175.39 | 18.75 | 156.63 | 250.25 | 127.63 | 0.00 | 0.00 | 0.00 |
August | 225.26 | 70.00 | 155.26 | 364.91 | 134.14 | 0.00 | 0.00 | 0.00 |
September | 309.33 | 153.67 | 155.66 | 499.80 | 154.72 | 0.00 | 0.00 | 0.00 |
October | 405.04 | 272.02 | 133.03 | 656.26 | 170.48 | 0.00 | 0.00 | 0.00 |
November | 492.00 | 348.59 | 143.41 | 731.41 | 244.77 | 0.00 | 0.00 | 0.00 |
December | 546.52 | 416.47 | 130.06 | 817.53 | 269.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 334.24 | 182.90 | 151.34 | 493.34 | 203.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.31 | 9.75 | 130.06 | 204.55 | 127.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 546.52 | 416.47 | 166.61 | 817.53 | 271.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.272405E+10 | 0.959899E+09 |
February | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.185728E+10 | 0.782842E+09 |
March | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.163312E+10 | 0.893212E+09 |
April | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.141270E+10 | 0.696271E+09 |
May | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.887349E+09 | 0.631117E+09 |
June | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.767310E+09 | 0.456618E+09 |
July | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.942223E+09 | 0.416489E+09 |
August | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.133961E+10 | 0.450794E+09 |
September | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.175361E+10 | 0.521482E+09 |
October | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.237074E+10 | 0.599428E+09 |
November | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.254641E+10 | 0.838700E+09 |
December | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.292977E+10 | 0.964382E+09 |
Annual Sum or Average | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.211642E+11 | 0.821123E+10 |
Minimum of Months | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.767310E+09 | 0.416489E+09 |
Maximum of Months | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.292977E+10 | 0.964382E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.756455E+10 | 0.293694E+10 |
February | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.513059E+10 | 0.244011E+10 |
March | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.449558E+10 | 0.275350E+10 |
April | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.388135E+10 | 0.218862E+10 |
May | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.238693E+10 | 0.200054E+10 |
June | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.205803E+10 | 0.147530E+10 |
July | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.257181E+10 | 0.132596E+10 |
August | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.370800E+10 | 0.142026E+10 |
September | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.486757E+10 | 0.164043E+10 |
October | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.659007E+10 | 0.186673E+10 |
November | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.706046E+10 | 0.259846E+10 |
December | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.814011E+10 | 0.295102E+10 |
Annual Sum or Average | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.584550E+11 | 0.255979E+11 |
Minimum of Months | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.205803E+10 | 0.132596E+10 |
Maximum of Months | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.814011E+10 | 0.295102E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.100745E+11 | 0.387257E+10 |
February | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.682319E+10 | 0.326507E+10 |
March | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.597613E+10 | 0.371104E+10 |
April | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.516811E+10 | 0.294424E+10 |
May | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.312788E+10 | 0.275266E+10 |
June | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.268787E+10 | 0.203552E+10 |
July | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.339526E+10 | 0.181369E+10 |
August | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.494245E+10 | 0.189887E+10 |
September | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.649046E+10 | 0.217568E+10 |
October | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.875879E+10 | 0.245885E+10 |
November | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.938995E+10 | 0.343531E+10 |
December | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.108251E+11 | 0.389512E+10 |
Annual Sum or Average | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.776597E+11 | 0.342586E+11 |
Minimum of Months | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.268787E+10 | 0.181369E+10 |
Maximum of Months | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.108251E+11 | 0.389512E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.545643E+09 | 0.196050E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.366558E+09 | 0.162507E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.319399E+09 | 0.190568E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.275254E+09 | 0.146540E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.165510E+09 | 0.136608E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.144521E+09 | 95283107.28 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.184717E+09 | 81549598.74 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.268604E+09 | 84640067.61 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.351822E+09 | 98822291.60 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.478556E+09 | 0.111625E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.508961E+09 | 0.168667E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.587199E+09 | 0.195110E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.419674E+10 | 0.166797E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.144521E+09 | 81549598.74 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.587199E+09 | 0.196050E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.331720E+09 | 0.397107E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.343277E+09 | 0.318968E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.447632E+09 | 0.359928E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.682551E+09 | 0.264373E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.677840E+09 | 0.242259E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.742193E+09 | 0.166963E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.862156E+09 | 0.143302E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.815302E+09 | 0.151567E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.649600E+09 | 0.179340E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.530084E+09 | 0.217250E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.383666E+09 | 0.336360E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.342706E+09 | 0.396461E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.680873E+10 | 0.317388E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.331720E+09 | 0.143302E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.862156E+09 | 0.397107E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 38707147.66 | 0.212859E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 39441680.64 | 0.173357E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 63462228.62 | 0.197919E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 84307385.60 | 0.145611E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.110333E+09 | 0.129201E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.135342E+09 | 94350067.86 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.147804E+09 | 86640426.29 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.120168E+09 | 92119679.94 |
September | 80955510.48 | 16100.43 | 80939410.05 | 92074347.73 | 0.106588E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 86480695.34 | 0.124073E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 42904778.19 | 0.183236E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 35111675.21 | 0.213380E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.996137E+09 | 0.175933E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 35111675.21 | 86640426.29 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.147804E+09 | 0.213380E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.347999E+09 | 0.387305E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.353914E+09 | 0.312973E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.455341E+09 | 0.356273E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.680281E+09 | 0.267364E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.668185E+09 | 0.248727E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.722272E+09 | 0.181458E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.838631E+09 | 0.163704E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.798936E+09 | 0.171225E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.645271E+09 | 0.189669E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.533347E+09 | 0.224838E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.396787E+09 | 0.330073E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.359170E+09 | 0.386511E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.680013E+10 | 0.322012E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.347999E+09 | 0.163704E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.838631E+09 | 0.387305E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.397642E+09 | 0.232235E+09 |
February | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.259319E+09 | 0.199498E+09 |
March | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.219823E+09 | 0.225949E+09 |
April | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.186727E+09 | 0.182224E+09 |
May | 0.108781E+09 | 13173513.96 | 95607483.13 | 97189303.42 | 0.172892E+09 |
June | 92353413.13 | 5416561.15 | 86936851.98 | 80112802.65 | 0.132533E+09 |
July | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.110590E+09 | 0.119825E+09 |
August | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.178227E+09 | 0.125921E+09 |
September | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.246968E+09 | 0.140615E+09 |
October | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.344819E+09 | 0.155272E+09 |
November | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.369358E+09 | 0.206023E+09 |
December | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.429886E+09 | 0.231689E+09 |
Annual Sum or Average | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.292066E+10 | 0.212468E+10 |
Minimum of Months | 92353413.13 | 5416561.15 | 74631825.39 | 80112802.65 | 0.119825E+09 |
Maximum of Months | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.429886E+09 | 0.232235E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44312955.30 | 0.00 | 44312955.30 | 31800182.22 | 0.172255E+09 |
February | 50241522.13 | 0.00 | 50241522.13 | 32797345.69 | 0.139653E+09 |
March | 68169765.21 | 624.22 | 68169140.99 | 52932975.87 | 0.159010E+09 |
April | 76404816.42 | 614812.68 | 75790003.74 | 75406483.45 | 0.111771E+09 |
May | 94978755.02 | 4953021.70 | 90025733.32 | 97522265.38 | 0.100195E+09 |
June | 97431324.50 | 9625266.49 | 87806058.00 | 0.119722E+09 | 71034872.60 |
July | 95367114.15 | 8092321.46 | 87274792.68 | 0.131638E+09 | 62895927.13 |
August | 79292341.88 | 1761686.91 | 77530654.97 | 0.108012E+09 | 65984320.41 |
September | 64772993.27 | 12882.05 | 64760111.22 | 81604114.78 | 78276088.06 |
October | 53086943.81 | 0.00 | 53086943.81 | 74601343.79 | 94360668.46 |
November | 46515858.69 | 0.00 | 46515858.69 | 36710420.81 | 0.144986E+09 |
December | 41251595.16 | 0.00 | 41251595.16 | 29360313.90 | 0.171516E+09 |
Annual Sum or Average | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.872107E+09 | 0.137194E+10 |
Minimum of Months | 41251595.16 | 0.00 | 41251595.16 | 29360313.90 | 62895927.13 |
Maximum of Months | 97431324.50 | 9625266.49 | 90025733.32 | 0.131638E+09 | 0.172255E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.337153E+09 | 0.376572E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.298704E+09 | 0.305190E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.429657E+09 | 0.343676E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.611426E+09 | 0.253493E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.579937E+09 | 0.234658E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.604245E+09 | 0.165417E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.761602E+09 | 0.143329E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.759162E+09 | 0.148135E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.505273E+09 | 0.175457E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.471122E+09 | 0.206703E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.331934E+09 | 0.322724E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.325263E+09 | 0.376108E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.601548E+10 | 0.305146E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.298704E+09 | 0.143329E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.761602E+09 | 0.376572E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.543276E+09 | 0.195476E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.365423E+09 | 0.161005E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.317093E+09 | 0.189089E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.272938E+09 | 0.144023E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.163918E+09 | 0.133897E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.143667E+09 | 92374609.88 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.183010E+09 | 78777560.76 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.266658E+09 | 82211128.61 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.351664E+09 | 95776071.96 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.477544E+09 | 0.110025E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.507799E+09 | 0.167090E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.585385E+09 | 0.194017E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.417838E+10 | 0.164376E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.143667E+09 | 78777560.76 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.585385E+09 | 0.195476E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 36553774.46 | 0.211642E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 38034954.25 | 0.170828E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 61211756.90 | 0.195777E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 82684718.12 | 0.141265E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.110386E+09 | 0.125433E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.137563E+09 | 89263666.07 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.148216E+09 | 81001836.75 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.118442E+09 | 86452696.38 |
September | 80955510.48 | 16100.43 | 80939410.05 | 91922784.35 | 0.100282E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 84565904.91 | 0.120619E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 41454911.44 | 0.179848E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 32935410.58 | 0.211291E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.983970E+09 | 0.171370E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 32935410.58 | 81001836.75 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.148216E+09 | 0.211642E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.351821E+09 | 0.363902E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.309117E+09 | 0.297355E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.438023E+09 | 0.338993E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.613289E+09 | 0.254795E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.574619E+09 | 0.239676E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.591466E+09 | 0.176843E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.743382E+09 | 0.159835E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.744670E+09 | 0.163323E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.503844E+09 | 0.182095E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.474330E+09 | 0.212178E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.344272E+09 | 0.312648E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.339756E+09 | 0.363063E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.602859E+10 | 0.306471E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.309117E+09 | 0.159835E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.744670E+09 | 0.363902E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 48926629.59 | 0.268993E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 51951284.32 | 0.219009E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 86638684.95 | 0.243997E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.120930E+09 | 0.177425E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.158938E+09 | 0.158755E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.194980E+09 | 0.113290E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.210212E+09 | 0.102849E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.168593E+09 | 0.110841E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.125786E+09 | 0.131719E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.110959E+09 | 0.160433E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 54354977.03 | 0.235474E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 43084632.07 | 0.273029E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.137535E+10 | 0.219581E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 43084632.07 | 0.102849E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.210212E+09 | 0.273029E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25856565.37 | 0.00 | 25856565.37 | 18036381.56 | 99161892.68 |
February | 29315878.22 | 0.00 | 29315878.22 | 19151394.54 | 80735773.04 |
March | 39776990.23 | 364.23 | 39776626.00 | 31938606.70 | 89947317.40 |
April | 44582134.43 | 358742.59 | 44223391.84 | 44579863.53 | 65406308.87 |
May | 55420009.14 | 2890083.24 | 52529925.90 | 58591187.25 | 58523504.44 |
June | 56851080.99 | 5616333.43 | 51234747.56 | 71877846.63 | 41763299.20 |
July | 55646616.31 | 4721861.53 | 50924754.78 | 77492684.76 | 37914232.43 |
August | 46267002.67 | 1027942.56 | 45239060.11 | 62150332.35 | 40860673.68 |
September | 37794977.19 | 7516.66 | 37787460.52 | 46370011.34 | 48556919.44 |
October | 30976178.94 | 0.00 | 30976178.94 | 40903972.37 | 59142315.67 |
November | 27141957.31 | 0.00 | 27141957.31 | 20037495.20 | 86805617.76 |
December | 24070264.77 | 0.00 | 24070264.77 | 15882779.38 | 0.100650E+09 |
Annual Sum or Average | 0.473700E+09 | 14622844.25 | 0.459077E+09 | 0.507013E+09 | 0.809468E+09 |
Minimum of Months | 24070264.77 | 0.00 | 24070264.77 | 15882779.38 | 37914232.43 |
Maximum of Months | 56851080.99 | 5616333.43 | 52529925.90 | 77492684.76 | 0.100650E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170960E+09 | 0.125510E+09 | 45450508.02 | 0.258519E+09 | 89531615.14 |
February | 0.121976E+09 | 75474510.52 | 46501214.20 | 0.174586E+09 | 74821200.79 |
March | 0.107705E+09 | 52465342.08 | 55239968.79 | 0.153375E+09 | 86287538.79 |
April | 87159368.36 | 33687257.57 | 53472110.79 | 0.133242E+09 | 66951533.84 |
May | 63458586.31 | 7684913.68 | 55773672.63 | 81686718.18 | 63178278.75 |
June | 53875375.24 | 3159810.28 | 50715564.96 | 71028654.38 | 45472613.89 |
July | 58711357.72 | 6278198.12 | 52433159.60 | 88867879.81 | 40511611.86 |
August | 75406282.36 | 23431540.72 | 51974741.64 | 0.127370E+09 | 42557637.73 |
September | 0.100207E+09 | 49782017.80 | 50425334.32 | 0.166519E+09 | 48282800.40 |
October | 0.135589E+09 | 91057819.93 | 44530737.20 | 0.223971E+09 | 55675086.76 |
November | 0.159386E+09 | 0.112929E+09 | 46457190.11 | 0.240517E+09 | 78879866.24 |
December | 0.182950E+09 | 0.139413E+09 | 43537292.90 | 0.277335E+09 | 90006155.96 |
Annual Sum or Average | 0.131738E+10 | 0.720873E+09 | 0.596511E+09 | 0.199702E+10 | 0.782156E+09 |
Minimum of Months | 53875375.24 | 3159810.28 | 43537292.90 | 71028654.38 | 40511611.86 |
Maximum of Months | 0.182950E+09 | 0.139413E+09 | 55773672.63 | 0.277335E+09 | 90006155.96 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.464021E+09 | 0.340659E+09 | 0.123362E+09 | 0.701673E+09 | 0.243007E+09 |
February | 0.331067E+09 | 0.204853E+09 | 0.126214E+09 | 0.473863E+09 | 0.203080E+09 |
March | 0.292334E+09 | 0.142402E+09 | 0.149933E+09 | 0.416292E+09 | 0.234202E+09 |
April | 0.236568E+09 | 91434107.63 | 0.145134E+09 | 0.361645E+09 | 0.181721E+09 |
May | 0.172240E+09 | 20858427.64 | 0.151381E+09 | 0.221714E+09 | 0.171479E+09 |
June | 0.146229E+09 | 8576371.43 | 0.137652E+09 | 0.192786E+09 | 0.123422E+09 |
July | 0.159355E+09 | 17040313.89 | 0.142314E+09 | 0.241206E+09 | 0.109957E+09 |
August | 0.204668E+09 | 63597994.32 | 0.141070E+09 | 0.345708E+09 | 0.115510E+09 |
September | 0.271983E+09 | 0.135119E+09 | 0.136865E+09 | 0.451966E+09 | 0.131049E+09 |
October | 0.368015E+09 | 0.247150E+09 | 0.120866E+09 | 0.607902E+09 | 0.151114E+09 |
November | 0.432606E+09 | 0.306511E+09 | 0.126094E+09 | 0.652813E+09 | 0.214096E+09 |
December | 0.496564E+09 | 0.378395E+09 | 0.118169E+09 | 0.752744E+09 | 0.244295E+09 |
Annual Sum or Average | 0.357565E+10 | 0.195660E+10 | 0.161905E+10 | 0.542031E+10 | 0.212293E+10 |
Minimum of Months | 0.146229E+09 | 8576371.43 | 0.118169E+09 | 0.192786E+09 | 0.109957E+09 |
Maximum of Months | 0.496564E+09 | 0.378395E+09 | 0.151381E+09 | 0.752744E+09 | 0.244295E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.542620E+09 | 0.193841E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.363104E+09 | 0.160500E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.315844E+09 | 0.189391E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.270965E+09 | 0.145654E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.161780E+09 | 0.135935E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.141284E+09 | 94735284.39 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.181381E+09 | 80891110.45 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.264791E+09 | 83791178.31 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.347816E+09 | 97516151.52 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.474917E+09 | 0.109574E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.505384E+09 | 0.166356E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.583897E+09 | 0.192343E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.415378E+10 | 0.165053E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.141284E+09 | 80891110.45 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.583897E+09 | 0.193841E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.327449E+09 | 0.391230E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.338549E+09 | 0.313990E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.440233E+09 | 0.356489E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.671217E+09 | 0.262080E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.665857E+09 | 0.240274E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.729638E+09 | 0.165436E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.850009E+09 | 0.141558E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.803980E+09 | 0.149610E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.640370E+09 | 0.176596E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.524522E+09 | 0.212691E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.379071E+09 | 0.330535E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.339297E+09 | 0.389403E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.671019E+10 | 0.312989E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.327449E+09 | 0.141558E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.850009E+09 | 0.391230E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 39434603.37 | 0.208967E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 39782483.64 | 0.170404E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 62454210.10 | 0.196406E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 81517654.52 | 0.146081E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.106504E+09 | 0.129595E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.130170E+09 | 96260645.26 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.142845E+09 | 89100465.47 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.116819E+09 | 94422662.86 |
September | 80955510.48 | 16100.43 | 80939410.05 | 90274942.87 | 0.106627E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 86565148.04 | 0.121753E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 43718719.64 | 0.179481E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 36432351.35 | 0.208597E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.976518E+09 | 0.174770E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 36432351.35 | 89100465.47 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.142845E+09 | 0.208967E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.346095E+09 | 0.379830E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.350700E+09 | 0.307219E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.448367E+09 | 0.352948E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.667546E+09 | 0.266976E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.654263E+09 | 0.248864E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.706250E+09 | 0.184359E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.822702E+09 | 0.167526E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.784970E+09 | 0.174286E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.635373E+09 | 0.188759E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.528833E+09 | 0.220285E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.394416E+09 | 0.322814E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.358581E+09 | 0.377522E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.669810E+10 | 0.319139E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.346095E+09 | 0.167526E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.822702E+09 | 0.379830E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.782231E+09 | 0.296523E+09 |
February | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.523608E+09 | 0.243618E+09 |
March | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.456770E+09 | 0.283403E+09 |
April | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.398451E+09 | 0.210891E+09 |
May | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.243185E+09 | 0.193801E+09 |
June | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.216363E+09 | 0.131645E+09 |
July | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.276595E+09 | 0.110300E+09 |
August | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.395156E+09 | 0.116300E+09 |
September | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.511182E+09 | 0.139968E+09 |
October | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.692595E+09 | 0.162584E+09 |
November | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.730834E+09 | 0.252750E+09 |
December | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.842486E+09 | 0.294317E+09 |
Annual Sum or Average | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.606946E+10 | 0.243610E+10 |
Minimum of Months | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.216363E+09 | 0.110300E+09 |
Maximum of Months | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.842486E+09 | 0.296523E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.195552E+09 | 0.171888E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.202517E+09 | 0.144410E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.353846E+09 | 0.160806E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.518496E+09 | 0.116599E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.684858E+09 | 0.103907E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.890823E+09 | 0.748693E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.997761E+09 | 0.665000E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.796554E+09 | 0.716902E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.584005E+09 | 0.856496E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.530260E+09 | 0.101949E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.226625E+09 | 0.149531E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.172524E+09 | 0.172573E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.615382E+10 | 0.142037E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.172524E+09 | 0.665000E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.997761E+09 | 0.172573E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.175114E+09 | 0.177762E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.181303E+09 | 0.149587E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.324816E+09 | 0.166200E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.487068E+09 | 0.120115E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.646927E+09 | 0.106862E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.856917E+09 | 0.772194E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.966695E+09 | 0.686199E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.768203E+09 | 0.740873E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.558502E+09 | 0.886206E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.506829E+09 | 0.105330E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.205287E+09 | 0.154383E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.153498E+09 | 0.178381E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.583116E+10 | 0.146717E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.153498E+09 | 0.686199E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.966695E+09 | 0.178381E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 45193253.49 | 0.217273E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 44962076.33 | 0.187305E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 72643034.56 | 0.210660E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 0.105268E+09 | 0.155304E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.138197E+09 | 0.142906E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.171766E+09 | 0.103961E+09 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.190887E+09 | 92598875.86 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.157619E+09 | 97825990.93 |
September | 80955510.48 | 16100.43 | 80939410.05 | 0.117536E+09 | 0.109225E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 0.106699E+09 | 0.128757E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 51440791.55 | 0.188922E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 41739689.69 | 0.217852E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.124395E+10 | 0.185259E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 41739689.69 | 92598875.86 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.190887E+09 | 0.217852E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.557245E+09 | 0.297743E+09 | 0.259502E+09 | 0.750114E+09 | 0.761093E+09 |
February | 0.531115E+09 | 0.243035E+09 | 0.288080E+09 | 0.649445E+09 | 0.663940E+09 |
March | 0.717645E+09 | 0.320532E+09 | 0.397113E+09 | 0.926533E+09 | 0.742946E+09 |
April | 0.885266E+09 | 0.444188E+09 | 0.441078E+09 | 0.131599E+10 | 0.565718E+09 |
May | 0.861631E+09 | 0.359068E+09 | 0.502562E+09 | 0.124862E+10 | 0.540393E+09 |
June | 0.829612E+09 | 0.360156E+09 | 0.469456E+09 | 0.130549E+10 | 0.402249E+09 |
July | 0.970781E+09 | 0.482287E+09 | 0.488494E+09 | 0.164138E+10 | 0.357639E+09 |
August | 0.959482E+09 | 0.509932E+09 | 0.449550E+09 | 0.163561E+10 | 0.368705E+09 |
September | 0.677922E+09 | 0.311816E+09 | 0.366105E+09 | 0.111021E+10 | 0.403820E+09 |
October | 0.617378E+09 | 0.316876E+09 | 0.300501E+09 | 0.103934E+10 | 0.462533E+09 |
November | 0.543378E+09 | 0.275091E+09 | 0.268287E+09 | 0.734191E+09 | 0.668018E+09 |
December | 0.539779E+09 | 0.300845E+09 | 0.238934E+09 | 0.723408E+09 | 0.761536E+09 |
Annual Sum or Average | 0.869123E+10 | 0.422157E+10 | 0.446966E+10 | 0.130803E+11 | 0.669859E+10 |
Minimum of Months | 0.531115E+09 | 0.243035E+09 | 0.238934E+09 | 0.649445E+09 | 0.357639E+09 |
Maximum of Months | 0.970781E+09 | 0.509932E+09 | 0.502562E+09 | 0.164138E+10 | 0.761536E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.568278E+09 | 0.200349E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.382107E+09 | 0.177227E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.336154E+09 | 0.204478E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.297574E+09 | 0.158609E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.186673E+09 | 0.152229E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.169926E+09 | 0.111042E+09 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.215546E+09 | 97116297.53 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.298736E+09 | 0.100560E+09 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.378677E+09 | 0.109239E+09 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.504484E+09 | 0.124008E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.530890E+09 | 0.175996E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.609694E+09 | 0.199635E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.447874E+10 | 0.181049E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.169926E+09 | 97116297.53 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.609694E+09 | 0.204478E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 43172381.46 | 0.273268E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 46635472.94 | 0.221853E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 78280712.86 | 0.249556E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.109751E+09 | 0.182606E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.147026E+09 | 0.162752E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.181101E+09 | 0.117998E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.195856E+09 | 0.107550E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.155618E+09 | 0.116336E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.115922E+09 | 0.136446E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.103364E+09 | 0.164022E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 49424646.17 | 0.236476E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 38415023.57 | 0.274110E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.126457E+10 | 0.224297E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 38415023.57 | 0.107550E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.195856E+09 | 0.274110E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62754662.34 | 0.00 | 62754662.34 | 38626493.28 | 0.244470E+09 |
February | 71150518.74 | 0.00 | 71150518.74 | 41724934.34 | 0.198493E+09 |
March | 96539952.45 | 884.00 | 96539068.45 | 70038050.40 | 0.223278E+09 |
April | 0.108202E+09 | 870679.06 | 0.107332E+09 | 98194730.63 | 0.163379E+09 |
May | 0.134506E+09 | 7014319.00 | 0.127492E+09 | 0.131544E+09 | 0.145615E+09 |
June | 0.137979E+09 | 13631010.27 | 0.124348E+09 | 0.162032E+09 | 0.105574E+09 |
July | 0.135056E+09 | 11460100.04 | 0.123596E+09 | 0.175233E+09 | 96225356.39 |
August | 0.112291E+09 | 2494847.54 | 0.109797E+09 | 0.139232E+09 | 0.104086E+09 |
September | 91729547.13 | 18243.17 | 91711303.96 | 0.103716E+09 | 0.122078E+09 |
October | 75180118.57 | 0.00 | 75180118.57 | 92479716.74 | 0.146751E+09 |
November | 65874347.26 | 0.00 | 65874347.26 | 44220418.20 | 0.211574E+09 |
December | 58419257.03 | 0.00 | 58419257.03 | 34370067.14 | 0.245213E+09 |
Annual Sum or Average | 0.114968E+10 | 35490083.08 | 0.111419E+10 | 0.113141E+10 | 0.200674E+10 |
Minimum of Months | 58419257.03 | 0.00 | 58419257.03 | 34370067.14 | 96225356.39 |
Maximum of Months | 0.137979E+09 | 13631010.27 | 0.127492E+09 | 0.175233E+09 | 0.245213E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136788E+10 | 0.100422E+10 | 0.363656E+09 | 0.203695E+10 | 0.727326E+09 |
February | 0.975944E+09 | 0.603882E+09 | 0.372063E+09 | 0.136787E+10 | 0.607377E+09 |
March | 0.861765E+09 | 0.419782E+09 | 0.441983E+09 | 0.119226E+10 | 0.708016E+09 |
April | 0.697374E+09 | 0.269536E+09 | 0.427838E+09 | 0.102716E+10 | 0.553317E+09 |
May | 0.507741E+09 | 61488042.30 | 0.446253E+09 | 0.617120E+09 | 0.521390E+09 |
June | 0.431064E+09 | 25282072.96 | 0.405782E+09 | 0.530194E+09 | 0.381687E+09 |
July | 0.469758E+09 | 50232719.31 | 0.419525E+09 | 0.670266E+09 | 0.341839E+09 |
August | 0.603336E+09 | 0.187479E+09 | 0.415857E+09 | 0.977387E+09 | 0.359271E+09 |
September | 0.801773E+09 | 0.398313E+09 | 0.403460E+09 | 0.129547E+10 | 0.401033E+09 |
October | 0.108486E+10 | 0.728566E+09 | 0.356297E+09 | 0.175773E+10 | 0.456602E+09 |
November | 0.127527E+10 | 0.903557E+09 | 0.371710E+09 | 0.189582E+10 | 0.634456E+09 |
December | 0.146381E+10 | 0.111546E+10 | 0.348348E+09 | 0.218966E+10 | 0.723116E+09 |
Annual Sum or Average | 0.105406E+11 | 0.576780E+10 | 0.477277E+10 | 0.155579E+11 | 0.641543E+10 |
Minimum of Months | 0.431064E+09 | 25282072.96 | 0.348348E+09 | 0.530194E+09 | 0.341839E+09 |
Maximum of Months | 0.146381E+10 | 0.111546E+10 | 0.446253E+09 | 0.218966E+10 | 0.727326E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1017.04 | 358.39 | 691.88 | 507.95 | 183.94 | 0.00 | 0.00 |
February | 767.72 | 323.60 | 546.53 | 338.18 | 208.36 | 0.00 | 0.00 |
March | 609.74 | 333.49 | 435.89 | 212.33 | 223.56 | 0.00 | 0.00 |
April | 545.02 | 268.62 | 364.49 | 140.88 | 223.62 | 0.00 | 0.00 |
May | 331.30 | 235.63 | 256.82 | 31.10 | 225.72 | 0.00 | 0.00 |
June | 296.03 | 176.16 | 225.30 | 13.21 | 212.09 | 0.00 | 0.00 |
July | 351.79 | 155.50 | 237.61 | 25.41 | 212.20 | 0.00 | 0.00 |
August | 500.15 | 168.31 | 305.17 | 94.83 | 210.34 | 0.00 | 0.00 |
September | 676.55 | 201.19 | 419.06 | 208.19 | 210.87 | 0.00 | 0.00 |
October | 885.13 | 223.80 | 548.73 | 368.52 | 180.22 | 0.00 | 0.00 |
November | 982.41 | 323.57 | 666.54 | 472.26 | 194.28 | 0.00 | 0.00 |
December | 1093.85 | 360.06 | 740.41 | 564.21 | 176.20 | 0.00 | 0.00 |
Annual Sum or Average | 671.11 | 260.38 | 452.81 | 247.78 | 205.03 | 0.00 | 0.00 |
Minimum of Months | 296.03 | 155.50 | 225.30 | 13.21 | 176.20 | 0.00 | 0.00 |
Maximum of Months | 1093.85 | 360.06 | 740.41 | 564.21 | 225.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2824.28 | 1096.53 | 1948.30 | 1430.34 | 517.96 | 0.00 | 0.00 |
February | 2120.78 | 1008.65 | 1539.00 | 952.28 | 586.71 | 0.00 | 0.00 |
March | 1678.46 | 1028.04 | 1227.43 | 597.91 | 629.52 | 0.00 | 0.00 |
April | 1497.43 | 844.38 | 1026.39 | 396.71 | 629.69 | 0.00 | 0.00 |
May | 891.18 | 746.92 | 723.18 | 87.58 | 635.60 | 0.00 | 0.00 |
June | 793.99 | 569.17 | 634.43 | 37.21 | 597.22 | 0.00 | 0.00 |
July | 960.20 | 495.06 | 669.08 | 71.55 | 597.53 | 0.00 | 0.00 |
August | 1384.41 | 530.26 | 859.34 | 267.03 | 592.31 | 0.00 | 0.00 |
September | 1877.92 | 632.88 | 1180.05 | 586.24 | 593.81 | 0.00 | 0.00 |
October | 2460.45 | 696.96 | 1545.20 | 1037.72 | 507.48 | 0.00 | 0.00 |
November | 2723.94 | 1002.49 | 1876.94 | 1329.86 | 547.08 | 0.00 | 0.00 |
December | 3039.17 | 1101.78 | 2084.94 | 1588.78 | 496.16 | 0.00 | 0.00 |
Annual Sum or Average | 1853.60 | 811.70 | 1275.09 | 697.73 | 577.36 | 0.00 | 0.00 |
Minimum of Months | 793.99 | 495.06 | 634.43 | 37.21 | 496.16 | 0.00 | 0.00 |
Maximum of Months | 3039.17 | 1101.78 | 2084.94 | 1588.78 | 635.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3761.37 | 1445.85 | 2530.95 | 1858.09 | 672.86 | 0.00 | 0.00 |
February | 2820.43 | 1349.65 | 1999.24 | 1237.07 | 762.17 | 0.00 | 0.00 |
March | 2231.23 | 1385.54 | 1594.50 | 776.72 | 817.79 | 0.00 | 0.00 |
April | 1993.87 | 1135.89 | 1333.34 | 515.34 | 818.00 | 0.00 | 0.00 |
May | 1167.82 | 1027.73 | 939.45 | 113.77 | 825.68 | 0.00 | 0.00 |
June | 1036.99 | 785.31 | 824.17 | 48.34 | 775.83 | 0.00 | 0.00 |
July | 1267.65 | 677.15 | 869.17 | 92.94 | 776.23 | 0.00 | 0.00 |
August | 1845.30 | 708.96 | 1116.33 | 346.89 | 769.44 | 0.00 | 0.00 |
September | 2504.04 | 839.38 | 1532.95 | 761.56 | 771.39 | 0.00 | 0.00 |
October | 3270.16 | 918.03 | 2007.30 | 1348.05 | 659.24 | 0.00 | 0.00 |
November | 3622.67 | 1325.35 | 2438.25 | 1727.56 | 710.69 | 0.00 | 0.00 |
December | 4041.64 | 1454.27 | 2708.45 | 2063.92 | 644.54 | 0.00 | 0.00 |
Annual Sum or Average | 2462.57 | 1086.33 | 1656.41 | 906.39 | 750.02 | 0.00 | 0.00 |
Minimum of Months | 1036.99 | 677.15 | 824.17 | 48.34 | 644.54 | 0.00 | 0.00 |
Maximum of Months | 4041.64 | 1454.27 | 2708.45 | 2063.92 | 825.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.74 | 214.63 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 289.70 | 195.31 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 283.79 | 202.95 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 367.47 | 156.48 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 312.72 | 139.30 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 339.94 | 99.02 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 389.21 | 82.30 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 403.49 | 87.00 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 385.09 | 106.05 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 374.91 | 121.12 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 339.57 | 190.03 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 339.52 | 213.20 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 345.83 | 150.39 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 283.79 | 82.30 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 403.49 | 214.63 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.19 | 221.89 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 160.25 | 198.68 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 191.17 | 204.39 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 293.36 | 157.71 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 289.39 | 139.83 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 329.64 | 105.18 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 367.37 | 92.54 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 342.25 | 97.42 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 282.58 | 112.40 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 230.11 | 128.97 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 167.09 | 195.49 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 144.77 | 221.54 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 245.46 | 156.14 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 142.19 | 92.54 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 367.37 | 221.89 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.46 | 86.71 | 109.42 | 80.33 | 29.09 | 0.00 | 0.00 |
February | 107.19 | 82.46 | 86.43 | 53.48 | 32.95 | 0.00 | 0.00 |
March | 82.07 | 84.36 | 68.93 | 33.58 | 35.35 | 0.00 | 0.00 |
April | 72.04 | 70.30 | 57.64 | 22.28 | 35.36 | 0.00 | 0.00 |
May | 36.29 | 64.55 | 40.61 | 4.92 | 35.70 | 0.00 | 0.00 |
June | 30.91 | 51.13 | 35.63 | 2.09 | 33.54 | 0.00 | 0.00 |
July | 41.29 | 44.74 | 37.58 | 4.02 | 33.56 | 0.00 | 0.00 |
August | 66.54 | 47.01 | 48.26 | 15.00 | 33.26 | 0.00 | 0.00 |
September | 95.28 | 54.25 | 66.27 | 32.92 | 33.35 | 0.00 | 0.00 |
October | 128.74 | 57.97 | 86.78 | 58.28 | 28.50 | 0.00 | 0.00 |
November | 142.50 | 79.48 | 105.41 | 74.68 | 30.72 | 0.00 | 0.00 |
December | 160.50 | 86.50 | 117.09 | 89.23 | 27.86 | 0.00 | 0.00 |
Annual Sum or Average | 92.61 | 67.37 | 71.61 | 39.18 | 32.42 | 0.00 | 0.00 |
Minimum of Months | 30.91 | 44.74 | 35.63 | 2.09 | 27.86 | 0.00 | 0.00 |
Maximum of Months | 160.50 | 86.71 | 117.09 | 89.23 | 35.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.87 | 64.31 | 16.54 | 0.00 | 16.54 | 0.00 | 0.00 |
February | 13.56 | 57.73 | 20.77 | 0.00 | 20.77 | 0.00 | 0.00 |
March | 19.76 | 59.37 | 25.45 | 0.00 | 25.45 | 0.00 | 0.00 |
April | 29.09 | 43.12 | 29.48 | 0.24 | 29.24 | 0.00 | 0.00 |
May | 36.41 | 37.41 | 35.46 | 1.85 | 33.61 | 0.00 | 0.00 |
June | 46.19 | 27.41 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
July | 49.15 | 23.48 | 35.61 | 3.02 | 32.58 | 0.00 | 0.00 |
August | 40.33 | 24.64 | 29.60 | 0.66 | 28.95 | 0.00 | 0.00 |
September | 31.48 | 30.20 | 24.99 | 0.00 | 24.98 | 0.00 | 0.00 |
October | 27.85 | 35.23 | 19.82 | 0.00 | 19.82 | 0.00 | 0.00 |
November | 14.16 | 55.94 | 17.95 | 0.00 | 17.95 | 0.00 | 0.00 |
December | 10.96 | 64.04 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Annual Sum or Average | 27.65 | 43.50 | 25.74 | 0.79 | 24.95 | 0.00 | 0.00 |
Minimum of Months | 10.96 | 23.48 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Maximum of Months | 49.15 | 64.31 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 325.18 | 210.05 | 240.83 | 156.02 | 84.82 | 0.00 | 0.00 |
February | 271.91 | 190.09 | 217.84 | 117.10 | 100.74 | 0.00 | 0.00 |
March | 275.69 | 195.80 | 220.16 | 101.82 | 118.34 | 0.00 | 0.00 |
April | 338.63 | 150.80 | 242.85 | 113.54 | 129.30 | 0.00 | 0.00 |
May | 275.06 | 134.94 | 211.64 | 73.18 | 138.45 | 0.00 | 0.00 |
June | 287.24 | 98.15 | 204.59 | 72.09 | 132.50 | 0.00 | 0.00 |
July | 352.08 | 82.33 | 228.22 | 95.06 | 133.15 | 0.00 | 0.00 |
August | 382.08 | 85.08 | 239.47 | 113.95 | 125.52 | 0.00 | 0.00 |
September | 329.86 | 103.90 | 213.64 | 101.32 | 112.32 | 0.00 | 0.00 |
October | 352.99 | 117.05 | 223.75 | 132.02 | 91.73 | 0.00 | 0.00 |
November | 320.88 | 185.88 | 236.61 | 146.44 | 90.17 | 0.00 | 0.00 |
December | 336.41 | 209.28 | 247.16 | 167.72 | 79.44 | 0.00 | 0.00 |
Annual Sum or Average | 321.09 | 146.73 | 227.34 | 115.93 | 111.41 | 0.00 | 0.00 |
Minimum of Months | 271.91 | 82.33 | 204.59 | 72.09 | 79.44 | 0.00 | 0.00 |
Maximum of Months | 382.08 | 210.05 | 247.16 | 167.72 | 138.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.28 | 209.16 | 124.71 | 55.59 | 69.12 | 0.00 | 0.00 |
February | 139.32 | 189.35 | 135.73 | 50.23 | 85.50 | 0.00 | 0.00 |
March | 181.58 | 194.84 | 165.79 | 59.84 | 105.95 | 0.00 | 0.00 |
April | 266.23 | 150.53 | 207.62 | 85.99 | 121.64 | 0.00 | 0.00 |
May | 254.42 | 134.99 | 205.18 | 69.35 | 135.83 | 0.00 | 0.00 |
June | 279.50 | 100.90 | 207.02 | 74.12 | 132.90 | 0.00 | 0.00 |
July | 331.49 | 88.53 | 225.74 | 93.82 | 131.92 | 0.00 | 0.00 |
August | 321.57 | 92.58 | 216.13 | 96.02 | 120.11 | 0.00 | 0.00 |
September | 228.92 | 108.01 | 162.01 | 60.16 | 101.85 | 0.00 | 0.00 |
October | 206.17 | 121.75 | 140.03 | 59.16 | 80.87 | 0.00 | 0.00 |
November | 144.34 | 185.53 | 127.26 | 53.07 | 74.19 | 0.00 | 0.00 |
December | 133.28 | 208.57 | 120.02 | 56.17 | 63.86 | 0.00 | 0.00 |
Annual Sum or Average | 219.38 | 148.53 | 169.98 | 67.93 | 102.05 | 0.00 | 0.00 |
Minimum of Months | 133.28 | 88.53 | 120.02 | 50.23 | 63.86 | 0.00 | 0.00 |
Maximum of Months | 331.49 | 209.16 | 225.74 | 96.02 | 135.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 374.18 | 252.29 | 272.92 | 174.05 | 98.87 | 0.00 | 0.00 |
February | 292.40 | 233.74 | 232.26 | 115.88 | 116.38 | 0.00 | 0.00 |
March | 255.12 | 242.50 | 204.49 | 72.76 | 131.74 | 0.00 | 0.00 |
April | 254.47 | 189.31 | 188.75 | 48.79 | 139.97 | 0.00 | 0.00 |
May | 192.48 | 166.72 | 164.82 | 14.66 | 150.16 | 0.00 | 0.00 |
June | 201.81 | 122.05 | 158.63 | 12.57 | 146.06 | 0.00 | 0.00 |
July | 228.53 | 106.61 | 158.55 | 15.25 | 143.30 | 0.00 | 0.00 |
August | 262.10 | 114.98 | 168.70 | 33.92 | 134.78 | 0.00 | 0.00 |
September | 304.91 | 138.61 | 197.73 | 71.35 | 126.38 | 0.00 | 0.00 |
October | 364.81 | 156.72 | 230.96 | 126.27 | 104.69 | 0.00 | 0.00 |
November | 366.22 | 230.24 | 267.27 | 161.82 | 105.45 | 0.00 | 0.00 |
December | 395.97 | 253.70 | 287.07 | 193.33 | 93.74 | 0.00 | 0.00 |
Annual Sum or Average | 291.17 | 183.70 | 210.92 | 86.62 | 124.30 | 0.00 | 0.00 |
Minimum of Months | 192.48 | 106.61 | 158.55 | 12.57 | 93.74 | 0.00 | 0.00 |
Maximum of Months | 395.97 | 253.70 | 287.07 | 193.33 | 150.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.36 | 211.96 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 286.51 | 192.61 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 279.72 | 201.24 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 361.36 | 155.17 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 306.77 | 138.23 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 333.73 | 98.10 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 383.33 | 81.31 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 397.78 | 85.89 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 379.94 | 104.45 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 371.59 | 118.76 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 336.67 | 187.15 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 337.43 | 209.95 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 341.42 | 148.51 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 279.72 | 81.31 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 397.78 | 211.96 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.74 | 217.63 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 159.01 | 195.03 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 188.07 | 202.45 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 287.13 | 157.49 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 282.71 | 139.97 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 321.36 | 106.93 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 359.48 | 94.80 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 335.60 | 99.24 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 277.88 | 111.88 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 228.41 | 126.35 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 166.44 | 191.19 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 145.06 | 216.41 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 241.51 | 154.76 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 141.74 | 94.80 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 359.48 | 217.63 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 292.05 | 110.71 | 200.63 | 147.29 | 53.34 | 0.00 | 0.00 |
February | 216.44 | 100.70 | 158.48 | 98.06 | 60.42 | 0.00 | 0.00 |
March | 170.54 | 105.81 | 126.40 | 61.57 | 64.83 | 0.00 | 0.00 |
April | 153.72 | 81.36 | 105.69 | 40.85 | 64.84 | 0.00 | 0.00 |
May | 90.79 | 72.36 | 74.47 | 9.02 | 65.45 | 0.00 | 0.00 |
June | 83.47 | 50.79 | 65.33 | 3.83 | 61.50 | 0.00 | 0.00 |
July | 103.27 | 41.18 | 68.90 | 7.37 | 61.53 | 0.00 | 0.00 |
August | 147.53 | 43.42 | 88.49 | 27.50 | 60.99 | 0.00 | 0.00 |
September | 197.22 | 54.00 | 121.52 | 60.37 | 61.15 | 0.00 | 0.00 |
October | 258.59 | 60.70 | 159.12 | 106.86 | 52.26 | 0.00 | 0.00 |
November | 281.96 | 97.51 | 193.28 | 136.94 | 56.34 | 0.00 | 0.00 |
December | 314.55 | 109.89 | 214.70 | 163.60 | 51.09 | 0.00 | 0.00 |
Annual Sum or Average | 192.46 | 77.25 | 131.30 | 71.85 | 59.45 | 0.00 | 0.00 |
Minimum of Months | 83.47 | 41.18 | 65.33 | 3.83 | 51.09 | 0.00 | 0.00 |
Maximum of Months | 314.55 | 110.71 | 214.70 | 163.60 | 65.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.01 | 641.76 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 83.71 | 596.93 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 132.11 | 600.38 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 200.04 | 449.84 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 255.70 | 387.95 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 343.68 | 288.85 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 372.52 | 248.28 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 297.40 | 267.66 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 225.31 | 330.44 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 197.98 | 380.64 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 87.43 | 576.89 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 64.41 | 644.31 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 195.14 | 450.40 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 64.41 | 248.28 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 372.52 | 644.31 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 65.38 | 663.69 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 74.94 | 618.33 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 121.27 | 620.52 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 187.91 | 463.41 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 241.53 | 398.98 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 330.60 | 297.91 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 360.92 | 256.20 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 286.81 | 276.61 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 215.47 | 341.90 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 189.23 | 393.26 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 79.20 | 595.61 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 57.31 | 666.00 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 184.90 | 465.24 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 57.31 | 256.20 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 360.92 | 666.00 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 500.12 | 431.10 | 365.53 | 211.59 | 153.93 | 0.00 | 0.00 |
February | 438.88 | 419.02 | 353.56 | 167.32 | 186.23 | 0.00 | 0.00 |
March | 491.68 | 425.50 | 385.93 | 161.65 | 224.28 | 0.00 | 0.00 |
April | 658.96 | 335.19 | 450.45 | 199.52 | 250.93 | 0.00 | 0.00 |
May | 583.96 | 308.44 | 416.79 | 142.52 | 274.27 | 0.00 | 0.00 |
June | 632.72 | 235.37 | 411.59 | 146.20 | 265.39 | 0.00 | 0.00 |
July | 762.69 | 202.49 | 453.93 | 188.87 | 265.06 | 0.00 | 0.00 |
August | 779.81 | 210.48 | 455.57 | 209.96 | 245.61 | 0.00 | 0.00 |
September | 618.58 | 238.89 | 375.63 | 161.47 | 214.16 | 0.00 | 0.00 |
October | 613.28 | 264.11 | 363.77 | 191.17 | 172.60 | 0.00 | 0.00 |
November | 500.52 | 391.11 | 363.85 | 199.51 | 164.35 | 0.00 | 0.00 |
December | 503.91 | 430.80 | 367.17 | 223.88 | 143.29 | 0.00 | 0.00 |
Annual Sum or Average | 591.54 | 323.86 | 397.30 | 183.85 | 213.45 | 0.00 | 0.00 |
Minimum of Months | 438.88 | 202.49 | 353.56 | 142.52 | 143.29 | 0.00 | 0.00 |
Maximum of Months | 779.81 | 431.10 | 455.57 | 223.88 | 274.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 776.72 | 450.53 | 560.32 | 374.93 | 185.39 | 0.00 | 0.00 |
February | 594.12 | 417.00 | 465.70 | 249.62 | 216.08 | 0.00 | 0.00 |
March | 497.54 | 437.90 | 398.08 | 156.73 | 241.35 | 0.00 | 0.00 |
April | 476.00 | 346.45 | 357.45 | 104.70 | 252.75 | 0.00 | 0.00 |
May | 330.82 | 306.21 | 295.92 | 28.50 | 267.41 | 0.00 | 0.00 |
June | 331.43 | 228.00 | 279.04 | 20.89 | 258.15 | 0.00 | 0.00 |
July | 384.63 | 199.54 | 282.17 | 27.82 | 254.35 | 0.00 | 0.00 |
August | 473.81 | 215.24 | 314.04 | 71.97 | 242.07 | 0.00 | 0.00 |
September | 584.31 | 254.23 | 384.27 | 153.68 | 230.58 | 0.00 | 0.00 |
October | 725.54 | 282.67 | 464.48 | 272.02 | 192.47 | 0.00 | 0.00 |
November | 756.68 | 406.77 | 545.82 | 348.59 | 197.23 | 0.00 | 0.00 |
December | 828.78 | 447.95 | 592.71 | 416.47 | 176.25 | 0.00 | 0.00 |
Annual Sum or Average | 563.40 | 332.28 | 411.44 | 185.28 | 226.16 | 0.00 | 0.00 |
Minimum of Months | 330.82 | 199.54 | 279.04 | 20.89 | 176.25 | 0.00 | 0.00 |
Maximum of Months | 828.78 | 450.53 | 592.71 | 416.47 | 267.41 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272405E+10 | 0.959899E+09 | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.00 | 0.00 |
February | 0.185728E+10 | 0.782842E+09 | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.00 | 0.00 |
March | 0.163312E+10 | 0.893212E+09 | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.00 | 0.00 |
April | 0.141270E+10 | 0.696271E+09 | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.00 | 0.00 |
May | 0.887349E+09 | 0.631117E+09 | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.00 | 0.00 |
June | 0.767310E+09 | 0.456618E+09 | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.00 | 0.00 |
July | 0.942223E+09 | 0.416489E+09 | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.00 | 0.00 |
August | 0.133961E+10 | 0.450794E+09 | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.00 | 0.00 |
September | 0.175361E+10 | 0.521482E+09 | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.00 | 0.00 |
October | 0.237074E+10 | 0.599428E+09 | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.00 | 0.00 |
November | 0.254641E+10 | 0.838700E+09 | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.00 | 0.00 |
December | 0.292977E+10 | 0.964382E+09 | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.211642E+11 | 0.821123E+10 | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.767310E+09 | 0.416489E+09 | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292977E+10 | 0.964382E+09 | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756455E+10 | 0.293694E+10 | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.00 | 0.00 |
February | 0.513059E+10 | 0.244011E+10 | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.00 | 0.00 |
March | 0.449558E+10 | 0.275350E+10 | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.00 | 0.00 |
April | 0.388135E+10 | 0.218862E+10 | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.00 | 0.00 |
May | 0.238693E+10 | 0.200054E+10 | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.00 | 0.00 |
June | 0.205803E+10 | 0.147530E+10 | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.00 | 0.00 |
July | 0.257181E+10 | 0.132596E+10 | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.00 | 0.00 |
August | 0.370800E+10 | 0.142026E+10 | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.00 | 0.00 |
September | 0.486757E+10 | 0.164043E+10 | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.00 | 0.00 |
October | 0.659007E+10 | 0.186673E+10 | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.00 | 0.00 |
November | 0.706046E+10 | 0.259846E+10 | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.00 | 0.00 |
December | 0.814011E+10 | 0.295102E+10 | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.584550E+11 | 0.255979E+11 | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205803E+10 | 0.132596E+10 | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.00 | 0.00 |
Maximum of Months | 0.814011E+10 | 0.295102E+10 | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100745E+11 | 0.387257E+10 | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.00 | 0.00 |
February | 0.682319E+10 | 0.326507E+10 | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.00 | 0.00 |
March | 0.597613E+10 | 0.371104E+10 | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.00 | 0.00 |
April | 0.516811E+10 | 0.294424E+10 | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.00 | 0.00 |
May | 0.312788E+10 | 0.275266E+10 | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.00 | 0.00 |
June | 0.268787E+10 | 0.203552E+10 | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.00 | 0.00 |
July | 0.339526E+10 | 0.181369E+10 | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.00 | 0.00 |
August | 0.494245E+10 | 0.189887E+10 | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.00 | 0.00 |
September | 0.649046E+10 | 0.217568E+10 | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.00 | 0.00 |
October | 0.875879E+10 | 0.245885E+10 | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.00 | 0.00 |
November | 0.938995E+10 | 0.343531E+10 | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.00 | 0.00 |
December | 0.108251E+11 | 0.389512E+10 | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.776597E+11 | 0.342586E+11 | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268787E+10 | 0.181369E+10 | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108251E+11 | 0.389512E+10 | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.859069E+09 | 0.574863E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.700852E+09 | 0.472493E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.760104E+09 | 0.543569E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.952492E+09 | 0.405600E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.837580E+09 | 0.373097E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.881122E+09 | 0.256654E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.104246E+10 | 0.220440E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.108071E+10 | 0.233011E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.998152E+09 | 0.274893E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.100416E+10 | 0.324396E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.880169E+09 | 0.492568E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.909364E+09 | 0.571029E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109062E+11 | 0.474261E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.700852E+09 | 0.220440E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108071E+10 | 0.574863E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380841E+09 | 0.594299E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.387679E+09 | 0.480653E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.512041E+09 | 0.547430E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.760394E+09 | 0.408781E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.775112E+09 | 0.374520E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.854432E+09 | 0.272627E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.983950E+09 | 0.247860E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.916684E+09 | 0.260925E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.732441E+09 | 0.291352E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.616339E+09 | 0.345422E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.433085E+09 | 0.506703E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.387756E+09 | 0.593365E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.774075E+10 | 0.492394E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.380841E+09 | 0.247860E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.983950E+09 | 0.594299E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397642E+09 | 0.232235E+09 | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.00 | 0.00 |
February | 0.259319E+09 | 0.199498E+09 | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.00 | 0.00 |
March | 0.219823E+09 | 0.225949E+09 | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.00 | 0.00 |
April | 0.186727E+09 | 0.182224E+09 | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.00 | 0.00 |
May | 97189303.42 | 0.172892E+09 | 0.108781E+09 | 13173513.96 | 95607483.13 | 0.00 | 0.00 |
June | 80112802.65 | 0.132533E+09 | 92353413.13 | 5416561.15 | 86936851.98 | 0.00 | 0.00 |
July | 0.110590E+09 | 0.119825E+09 | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.00 | 0.00 |
August | 0.178227E+09 | 0.125921E+09 | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.00 | 0.00 |
September | 0.246968E+09 | 0.140615E+09 | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.00 | 0.00 |
October | 0.344819E+09 | 0.155272E+09 | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.00 | 0.00 |
November | 0.369358E+09 | 0.206023E+09 | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.00 | 0.00 |
December | 0.429886E+09 | 0.231689E+09 | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.292066E+10 | 0.212468E+10 | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.00 | 0.00 |
Minimum of Months | 80112802.65 | 0.119825E+09 | 92353413.13 | 5416561.15 | 74631825.39 | 0.00 | 0.00 |
Maximum of Months | 0.429886E+09 | 0.232235E+09 | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 31800182.22 | 0.172255E+09 | 44312955.30 | 0.00 | 44312955.30 | 0.00 | 0.00 |
February | 32797345.69 | 0.139653E+09 | 50241522.13 | 0.00 | 50241522.13 | 0.00 | 0.00 |
March | 52932975.87 | 0.159010E+09 | 68169765.21 | 624.22 | 68169140.99 | 0.00 | 0.00 |
April | 75406483.45 | 0.111771E+09 | 76404816.42 | 614812.68 | 75790003.74 | 0.00 | 0.00 |
May | 97522265.38 | 0.100195E+09 | 94978755.02 | 4953021.70 | 90025733.32 | 0.00 | 0.00 |
June | 0.119722E+09 | 71034872.60 | 97431324.50 | 9625266.49 | 87806058.00 | 0.00 | 0.00 |
July | 0.131638E+09 | 62895927.13 | 95367114.15 | 8092321.46 | 87274792.68 | 0.00 | 0.00 |
August | 0.108012E+09 | 65984320.41 | 79292341.88 | 1761686.91 | 77530654.97 | 0.00 | 0.00 |
September | 81604114.78 | 78276088.06 | 64772993.27 | 12882.05 | 64760111.22 | 0.00 | 0.00 |
October | 74601343.79 | 94360668.46 | 53086943.81 | 0.00 | 53086943.81 | 0.00 | 0.00 |
November | 36710420.81 | 0.144986E+09 | 46515858.69 | 0.00 | 46515858.69 | 0.00 | 0.00 |
December | 29360313.90 | 0.171516E+09 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.872107E+09 | 0.137194E+10 | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.00 | 0.00 |
Minimum of Months | 29360313.90 | 62895927.13 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Maximum of Months | 0.131638E+09 | 0.172255E+09 | 97431324.50 | 9625266.49 | 90025733.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.870973E+09 | 0.562591E+09 | 0.645041E+09 | 0.417872E+09 | 0.227169E+09 | 0.00 | 0.00 |
February | 0.657798E+09 | 0.459866E+09 | 0.526993E+09 | 0.283282E+09 | 0.243711E+09 | 0.00 | 0.00 |
March | 0.738415E+09 | 0.524430E+09 | 0.589680E+09 | 0.272720E+09 | 0.316960E+09 | 0.00 | 0.00 |
April | 0.877728E+09 | 0.390880E+09 | 0.629463E+09 | 0.294307E+09 | 0.335155E+09 | 0.00 | 0.00 |
May | 0.736734E+09 | 0.361434E+09 | 0.566849E+09 | 0.196017E+09 | 0.370832E+09 | 0.00 | 0.00 |
June | 0.744523E+09 | 0.254402E+09 | 0.530300E+09 | 0.186863E+09 | 0.343438E+09 | 0.00 | 0.00 |
July | 0.943007E+09 | 0.220502E+09 | 0.611254E+09 | 0.254616E+09 | 0.356638E+09 | 0.00 | 0.00 |
August | 0.102336E+10 | 0.227885E+09 | 0.641384E+09 | 0.305202E+09 | 0.336182E+09 | 0.00 | 0.00 |
September | 0.855008E+09 | 0.269304E+09 | 0.553748E+09 | 0.262611E+09 | 0.291136E+09 | 0.00 | 0.00 |
October | 0.945451E+09 | 0.313513E+09 | 0.599302E+09 | 0.353603E+09 | 0.245699E+09 | 0.00 | 0.00 |
November | 0.831732E+09 | 0.481813E+09 | 0.613301E+09 | 0.379582E+09 | 0.233719E+09 | 0.00 | 0.00 |
December | 0.901050E+09 | 0.560527E+09 | 0.662004E+09 | 0.449220E+09 | 0.212784E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101258E+11 | 0.462715E+10 | 0.716932E+10 | 0.365590E+10 | 0.351342E+10 | 0.00 | 0.00 |
Minimum of Months | 0.657798E+09 | 0.220502E+09 | 0.526993E+09 | 0.186863E+09 | 0.212784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102336E+10 | 0.562591E+09 | 0.662004E+09 | 0.449220E+09 | 0.370832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.373050E+09 | 0.560219E+09 | 0.334026E+09 | 0.148882E+09 | 0.185144E+09 | 0.00 | 0.00 |
February | 0.337046E+09 | 0.458077E+09 | 0.328370E+09 | 0.121526E+09 | 0.206844E+09 | 0.00 | 0.00 |
March | 0.486336E+09 | 0.521871E+09 | 0.444049E+09 | 0.160278E+09 | 0.283771E+09 | 0.00 | 0.00 |
April | 0.690078E+09 | 0.390164E+09 | 0.538158E+09 | 0.222878E+09 | 0.315280E+09 | 0.00 | 0.00 |
May | 0.681444E+09 | 0.361548E+09 | 0.549554E+09 | 0.185737E+09 | 0.363816E+09 | 0.00 | 0.00 |
June | 0.724461E+09 | 0.261540E+09 | 0.536608E+09 | 0.192121E+09 | 0.344488E+09 | 0.00 | 0.00 |
July | 0.887867E+09 | 0.237106E+09 | 0.604618E+09 | 0.251275E+09 | 0.353343E+09 | 0.00 | 0.00 |
August | 0.861293E+09 | 0.247957E+09 | 0.578877E+09 | 0.257186E+09 | 0.321691E+09 | 0.00 | 0.00 |
September | 0.593350E+09 | 0.279960E+09 | 0.419941E+09 | 0.155935E+09 | 0.264005E+09 | 0.00 | 0.00 |
October | 0.552195E+09 | 0.326096E+09 | 0.375061E+09 | 0.158449E+09 | 0.216611E+09 | 0.00 | 0.00 |
November | 0.374119E+09 | 0.480889E+09 | 0.329845E+09 | 0.137555E+09 | 0.192290E+09 | 0.00 | 0.00 |
December | 0.356972E+09 | 0.558634E+09 | 0.321466E+09 | 0.150433E+09 | 0.171033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.691821E+10 | 0.468406E+10 | 0.536057E+10 | 0.214226E+10 | 0.321832E+10 | 0.00 | 0.00 |
Minimum of Months | 0.337046E+09 | 0.237106E+09 | 0.321466E+09 | 0.121526E+09 | 0.171033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.887867E+09 | 0.560219E+09 | 0.604618E+09 | 0.257186E+09 | 0.363816E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100220E+10 | 0.675741E+09 | 0.730978E+09 | 0.466169E+09 | 0.264809E+09 | 0.00 | 0.00 |
February | 0.707370E+09 | 0.565463E+09 | 0.561883E+09 | 0.280328E+09 | 0.281555E+09 | 0.00 | 0.00 |
March | 0.683313E+09 | 0.649502E+09 | 0.547718E+09 | 0.194868E+09 | 0.352850E+09 | 0.00 | 0.00 |
April | 0.659592E+09 | 0.490698E+09 | 0.489246E+09 | 0.126453E+09 | 0.362793E+09 | 0.00 | 0.00 |
May | 0.515530E+09 | 0.446535E+09 | 0.441454E+09 | 39273247.18 | 0.402181E+09 | 0.00 | 0.00 |
June | 0.523087E+09 | 0.316362E+09 | 0.411173E+09 | 32587736.49 | 0.378585E+09 | 0.00 | 0.00 |
July | 0.612087E+09 | 0.285541E+09 | 0.424663E+09 | 40849193.83 | 0.383814E+09 | 0.00 | 0.00 |
August | 0.702018E+09 | 0.307966E+09 | 0.451848E+09 | 90845939.63 | 0.361002E+09 | 0.00 | 0.00 |
September | 0.790320E+09 | 0.359286E+09 | 0.512511E+09 | 0.184929E+09 | 0.327582E+09 | 0.00 | 0.00 |
October | 0.977120E+09 | 0.419749E+09 | 0.618608E+09 | 0.338207E+09 | 0.280400E+09 | 0.00 | 0.00 |
November | 0.949254E+09 | 0.596787E+09 | 0.692760E+09 | 0.419440E+09 | 0.273320E+09 | 0.00 | 0.00 |
December | 0.106057E+10 | 0.679508E+09 | 0.768878E+09 | 0.517807E+09 | 0.251071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.918247E+10 | 0.579314E+10 | 0.665172E+10 | 0.273176E+10 | 0.391996E+10 | 0.00 | 0.00 |
Minimum of Months | 0.515530E+09 | 0.285541E+09 | 0.411173E+09 | 32587736.49 | 0.251071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106057E+10 | 0.679508E+09 | 0.768878E+09 | 0.517807E+09 | 0.402181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.852701E+09 | 0.567702E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.693124E+09 | 0.465962E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.749206E+09 | 0.539010E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.936646E+09 | 0.402198E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.821664E+09 | 0.370237E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.865035E+09 | 0.254283E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.102671E+10 | 0.217770E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.106542E+10 | 0.230048E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.984802E+09 | 0.270728E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.995271E+09 | 0.318098E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.872656E+09 | 0.485091E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.903766E+09 | 0.562317E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107670E+11 | 0.468344E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.693124E+09 | 0.217770E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106542E+10 | 0.567702E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379630E+09 | 0.582897E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.384666E+09 | 0.471805E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.503717E+09 | 0.542250E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.744232E+09 | 0.408226E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.757207E+09 | 0.374899E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.832974E+09 | 0.277174E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.962831E+09 | 0.253911E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.898876E+09 | 0.265796E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.720262E+09 | 0.290000E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.611772E+09 | 0.338413E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.431413E+09 | 0.495573E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.388535E+09 | 0.579640E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.761612E+10 | 0.488058E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.379630E+09 | 0.253911E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.962831E+09 | 0.582897E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.782231E+09 | 0.296523E+09 | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.00 | 0.00 |
February | 0.523608E+09 | 0.243618E+09 | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.00 | 0.00 |
March | 0.456770E+09 | 0.283403E+09 | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.00 | 0.00 |
April | 0.398451E+09 | 0.210891E+09 | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.00 | 0.00 |
May | 0.243185E+09 | 0.193801E+09 | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.00 | 0.00 |
June | 0.216363E+09 | 0.131645E+09 | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.00 | 0.00 |
July | 0.276595E+09 | 0.110300E+09 | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.00 | 0.00 |
August | 0.395156E+09 | 0.116300E+09 | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.00 | 0.00 |
September | 0.511182E+09 | 0.139968E+09 | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.00 | 0.00 |
October | 0.692595E+09 | 0.162584E+09 | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.00 | 0.00 |
November | 0.730834E+09 | 0.252750E+09 | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.00 | 0.00 |
December | 0.842486E+09 | 0.294317E+09 | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606946E+10 | 0.243610E+10 | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.00 | 0.00 |
Minimum of Months | 0.216363E+09 | 0.110300E+09 | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.00 | 0.00 |
Maximum of Months | 0.842486E+09 | 0.296523E+09 | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195552E+09 | 0.171888E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.202517E+09 | 0.144410E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.353846E+09 | 0.160806E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.518496E+09 | 0.116599E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.684858E+09 | 0.103907E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.890823E+09 | 0.748693E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.997761E+09 | 0.665000E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.796554E+09 | 0.716902E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.584005E+09 | 0.856496E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.530260E+09 | 0.101949E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.226625E+09 | 0.149531E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.172524E+09 | 0.172573E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.615382E+10 | 0.142037E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.172524E+09 | 0.665000E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.997761E+09 | 0.172573E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175114E+09 | 0.177762E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.181303E+09 | 0.149587E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.324816E+09 | 0.166200E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.487068E+09 | 0.120115E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.646927E+09 | 0.106862E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.856917E+09 | 0.772194E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.966695E+09 | 0.686199E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.768203E+09 | 0.740873E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.558502E+09 | 0.886206E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.506829E+09 | 0.105330E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.205287E+09 | 0.154383E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.153498E+09 | 0.178381E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.583116E+10 | 0.146717E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153498E+09 | 0.686199E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.966695E+09 | 0.178381E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133953E+10 | 0.115466E+10 | 0.979027E+09 | 0.566733E+09 | 0.412294E+09 | 0.00 | 0.00 |
February | 0.106174E+10 | 0.101370E+10 | 0.855325E+09 | 0.404791E+09 | 0.450534E+09 | 0.00 | 0.00 |
March | 0.131691E+10 | 0.113967E+10 | 0.103368E+10 | 0.432976E+09 | 0.600702E+09 | 0.00 | 0.00 |
April | 0.170802E+10 | 0.868813E+09 | 0.116756E+10 | 0.517154E+09 | 0.650404E+09 | 0.00 | 0.00 |
May | 0.156409E+10 | 0.826125E+09 | 0.111634E+10 | 0.381729E+09 | 0.734613E+09 | 0.00 | 0.00 |
June | 0.164001E+10 | 0.610083E+09 | 0.106685E+10 | 0.378958E+09 | 0.687892E+09 | 0.00 | 0.00 |
July | 0.204280E+10 | 0.542338E+09 | 0.121580E+10 | 0.505857E+09 | 0.709947E+09 | 0.00 | 0.00 |
August | 0.208864E+10 | 0.563761E+09 | 0.122019E+10 | 0.562352E+09 | 0.657842E+09 | 0.00 | 0.00 |
September | 0.160335E+10 | 0.619208E+09 | 0.973640E+09 | 0.418524E+09 | 0.555116E+09 | 0.00 | 0.00 |
October | 0.164262E+10 | 0.707394E+09 | 0.974319E+09 | 0.512030E+09 | 0.462289E+09 | 0.00 | 0.00 |
November | 0.129735E+10 | 0.101376E+10 | 0.943108E+09 | 0.517117E+09 | 0.425991E+09 | 0.00 | 0.00 |
December | 0.134968E+10 | 0.115386E+10 | 0.983432E+09 | 0.599632E+09 | 0.383800E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186547E+11 | 0.102134E+11 | 0.125293E+11 | 0.579785E+10 | 0.673142E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106174E+10 | 0.542338E+09 | 0.855325E+09 | 0.378958E+09 | 0.383800E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208864E+10 | 0.115466E+10 | 0.122019E+10 | 0.599632E+09 | 0.734613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208038E+10 | 0.120669E+10 | 0.150077E+10 | 0.100422E+10 | 0.496551E+09 | 0.00 | 0.00 |
February | 0.143731E+10 | 0.100880E+10 | 0.112662E+10 | 0.603882E+09 | 0.522737E+09 | 0.00 | 0.00 |
March | 0.133261E+10 | 0.117287E+10 | 0.106621E+10 | 0.419784E+09 | 0.646422E+09 | 0.00 | 0.00 |
April | 0.123379E+10 | 0.897991E+09 | 0.926512E+09 | 0.271380E+09 | 0.655132E+09 | 0.00 | 0.00 |
May | 0.886074E+09 | 0.820141E+09 | 0.792583E+09 | 76342183.92 | 0.716240E+09 | 0.00 | 0.00 |
June | 0.859054E+09 | 0.590986E+09 | 0.723261E+09 | 54148304.57 | 0.669113E+09 | 0.00 | 0.00 |
July | 0.103018E+10 | 0.534442E+09 | 0.755764E+09 | 74501639.64 | 0.681262E+09 | 0.00 | 0.00 |
August | 0.126905E+10 | 0.576504E+09 | 0.841134E+09 | 0.192762E+09 | 0.648372E+09 | 0.00 | 0.00 |
September | 0.151452E+10 | 0.658973E+09 | 0.996027E+09 | 0.398351E+09 | 0.597676E+09 | 0.00 | 0.00 |
October | 0.194330E+10 | 0.757097E+09 | 0.124407E+10 | 0.728566E+09 | 0.515505E+09 | 0.00 | 0.00 |
November | 0.196132E+10 | 0.105435E+10 | 0.141477E+10 | 0.903557E+09 | 0.511212E+09 | 0.00 | 0.00 |
December | 0.221979E+10 | 0.119978E+10 | 0.158752E+10 | 0.111546E+10 | 0.472062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177674E+11 | 0.104786E+11 | 0.129752E+11 | 0.584296E+10 | 0.713228E+10 | 0.00 | 0.00 |
Minimum of Months | 0.859054E+09 | 0.534442E+09 | 0.723261E+09 | 54148304.57 | 0.472062E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221979E+10 | 0.120669E+10 | 0.158752E+10 | 0.111546E+10 | 0.716240E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770518E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162399503.5 | 81.21 | 0.00 | 0.00 |
February | 0.696231E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146344949.9 | 81.21 | 0.00 | 0.00 |
March | 0.770372E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162252522.7 | 81.21 | 0.00 | 0.00 |
April | 0.746519E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156604194.7 | 81.21 | 0.00 | 0.00 |
May | 0.770460E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161814346.1 | 81.21 | 0.00 | 0.00 |
June | 0.745701E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156483688.9 | 81.21 | 0.00 | 0.00 |
July | 0.771248E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161633977.3 | 81.21 | 0.00 | 0.00 |
August | 0.770443E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161627349.9 | 81.21 | 0.00 | 0.00 |
September | 0.746639E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156469224.9 | 81.21 | 0.00 | 0.00 |
October | 0.770315E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161717671.5 | 81.21 | 0.00 | 0.00 |
November | 0.744918E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156759614.4 | 81.21 | 0.00 | 0.00 |
December | 0.771315E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162287281.1 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907468E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190639E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696231E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162399503.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771315E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146344949.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109800E+12 | -0.108049E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175095E+10 | 81.24 | 0.00 | 0.00 |
February | 0.992560E+11 | -0.976639E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159213E+10 | 81.25 | 0.00 | 0.00 |
March | 0.109129E+12 | -0.107357E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177195E+10 | 81.25 | 0.00 | 0.00 |
April | 0.104196E+12 | -0.102483E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171378E+10 | 81.25 | 0.00 | 0.00 |
May | 0.105918E+12 | -0.104147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177011E+10 | 81.25 | 0.00 | 0.00 |
June | 0.100982E+12 | -0.992663E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171568E+10 | 81.25 | 0.00 | 0.00 |
July | 0.103371E+12 | -0.101609E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176244E+10 | 81.25 | 0.00 | 0.00 |
August | 0.103268E+12 | -0.101509E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175921E+10 | 81.25 | 0.00 | 0.00 |
September | 0.100698E+12 | -0.990055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169293E+10 | 81.25 | 0.00 | 0.00 |
October | 0.105523E+12 | -0.103781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174129E+10 | 81.25 | 0.00 | 0.00 |
November | 0.103813E+12 | -0.102129E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168375E+10 | 81.25 | 0.00 | 0.00 |
December | 0.108839E+12 | -0.107092E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174730E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.125479E+13 | -0.123409E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207015E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.992560E+11 | -0.108049E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.177195E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.109800E+12 | -0.976639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159213E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.622097E+11 | -0.607128E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149697E+10 | 58.98 | 0.00 | 0.00 |
February | 0.562763E+11 | -0.549097E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.136654E+10 | 58.98 | 0.00 | 0.00 |
March | 0.616971E+11 | -0.601715E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152567E+10 | 58.98 | 0.00 | 0.00 |
April | 0.584565E+11 | -0.569815E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147503E+10 | 58.98 | 0.00 | 0.00 |
May | 0.589029E+11 | -0.573797E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152320E+10 | 58.98 | 0.00 | 0.00 |
June | 0.557156E+11 | -0.542379E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147766E+10 | 58.98 | 0.00 | 0.00 |
July | 0.566713E+11 | -0.551586E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151265E+10 | 58.98 | 0.00 | 0.00 |
August | 0.566377E+11 | -0.551295E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150814E+10 | 58.98 | 0.00 | 0.00 |
September | 0.554333E+11 | -0.539869E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144638E+10 | 58.98 | 0.00 | 0.00 |
October | 0.585153E+11 | -0.570318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148350E+10 | 58.98 | 0.00 | 0.00 |
November | 0.580881E+11 | -0.566544E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143370E+10 | 58.98 | 0.00 | 0.00 |
December | 0.613769E+11 | -0.598852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149166E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.699981E+12 | -0.682240E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177411E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.554333E+11 | -0.607128E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.152567E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.622097E+11 | -0.539869E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.136654E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.87 | 0.86 | 01-JAN-07:30 | 7052.51 | 37.52 | 285.00 | 281.50 | 1015.00 | 27.16 | 209.67 | 265.00 |
February | 279.67 | 0.87 | 0.86 | 01-FEB-07:30 | 4904.28 | 32.25 | 218.50 | 277.00 | 670.04 | 23.86 | 187.83 | 247.67 |
March | 338.17 | 0.87 | 0.86 | 01-MAR-07:40 | 1285.36 | 20.03 | 18.83 | 322.67 | 479.18 | 21.29 | 186.67 | 268.33 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:19 | 884.18 | 19.54 | 0.00 | 335.17 | 373.14 | 21.29 | 213.17 | 274.67 |
May | 393.83 | 0.88 | 0.86 | 01-MAY-06:00 | 803.15 | 19.04 | 0.00 | 367.83 | 327.24 | 20.77 | 162.33 | 280.33 |
June | 381.00 | 0.88 | 0.86 | 01-JUN-07:10 | 694.69 | 18.85 | 0.00 | 360.33 | 292.55 | 20.60 | 125.00 | 260.50 |
July | 408.67 | 0.88 | 0.86 | 01-JUL-07:00 | 684.44 | 18.97 | 0.00 | 369.83 | 298.69 | 20.73 | 173.83 | 280.00 |
August | 390.67 | 0.88 | 0.86 | 01-AUG-07:40 | 744.35 | 19.22 | 0.00 | 356.00 | 324.31 | 20.97 | 187.33 | 283.00 |
September | 328.83 | 0.87 | 0.86 | 01-SEP-07:10 | 999.70 | 19.53 | 0.33 | 311.00 | 416.32 | 21.30 | 182.17 | 261.17 |
October | 296.17 | 0.87 | 0.86 | 01-OCT-09:39 | 3383.21 | 27.32 | 136.83 | 307.33 | 492.85 | 21.81 | 127.33 | 256.83 |
November | 300.00 | 0.87 | 0.86 | 01-NOV-06:49 | 6865.72 | 37.35 | 295.17 | 281.67 | 889.85 | 26.74 | 225.17 | 269.50 |
December | 297.00 | 0.87 | 0.86 | 01-DEC-07:19 | 6902.00 | 37.93 | 289.17 | 282.17 | 1244.45 | 28.71 | 200.50 | 267.83 |
Annual Sum or Average | 4065.67 | 0.87 | 2652.36 | 24.77 | 1243.83 | 3852.50 | 538.51 | 22.67 | 2181.00 | 3214.83 | ||
Minimum of Months | 279.67 | 0.87 | 0.86 | 684.44 | 18.85 | 0.00 | 277.00 | 292.55 | 20.60 | 125.00 | 247.67 | |
Maximum of Months | 408.67 | 0.88 | 0.86 | 7052.51 | 37.93 | 295.17 | 369.83 | 1244.45 | 28.71 | 225.17 | 283.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.25 | 0.22 | 01-JAN-07:19 | 7460.67 | 37.60 | 285.00 | 288.33 | 1425.15 | 26.86 | 184.67 | 276.00 |
February | 279.67 | 0.25 | 0.22 | 01-FEB-07:19 | 5228.42 | 32.34 | 219.00 | 283.17 | 993.76 | 23.90 | 182.17 | 266.00 |
March | 338.17 | 0.28 | 0.22 | 01-MAR-07:10 | 1535.43 | 20.47 | 44.50 | 331.67 | 728.33 | 21.58 | 206.00 | 303.83 |
April | 358.33 | 0.26 | 0.22 | 01-APR-06:40 | 1086.01 | 20.10 | 41.67 | 348.00 | 574.49 | 21.65 | 229.33 | 317.83 |
May | 393.83 | 0.27 | 0.22 | 01-MAY-06:30 | 945.90 | 19.84 | 7.17 | 381.33 | 469.50 | 21.36 | 251.33 | 346.17 |
June | 381.00 | 0.28 | 0.22 | 01-JUN-06:40 | 823.20 | 19.70 | 0.17 | 372.50 | 420.64 | 21.22 | 248.50 | 336.50 |
July | 408.67 | 0.28 | 0.22 | 01-JUL-06:10 | 820.23 | 19.76 | 0.67 | 380.33 | 434.09 | 21.30 | 305.33 | 350.50 |
August | 390.67 | 0.28 | 0.22 | 01-AUG-07:10 | 913.02 | 19.87 | 14.50 | 368.50 | 492.57 | 21.42 | 254.50 | 339.67 |
September | 328.83 | 0.27 | 0.22 | 01-SEP-06:49 | 1240.89 | 19.96 | 38.67 | 324.17 | 656.95 | 21.56 | 193.33 | 295.50 |
October | 296.17 | 0.26 | 0.22 | 01-OCT-09:39 | 3714.16 | 27.35 | 138.50 | 318.17 | 821.62 | 21.74 | 123.67 | 286.50 |
November | 300.00 | 0.26 | 0.22 | 01-NOV-06:40 | 7249.89 | 37.41 | 295.17 | 286.17 | 1271.19 | 26.49 | 203.33 | 277.67 |
December | 297.00 | 0.26 | 0.22 | 01-DEC-07:10 | 7326.86 | 38.01 | 289.33 | 287.83 | 1668.60 | 28.35 | 178.67 | 277.67 |
Annual Sum or Average | 4065.67 | 0.27 | 2901.42 | 25.22 | 1374.33 | 3970.17 | 786.93 | 22.90 | 2560.83 | 3673.83 | ||
Minimum of Months | 279.67 | 0.25 | 0.22 | 820.23 | 19.70 | 0.17 | 283.17 | 420.64 | 21.22 | 123.67 | 266.00 | |
Maximum of Months | 408.67 | 0.28 | 0.22 | 7460.67 | 38.01 | 295.17 | 381.33 | 1668.60 | 28.35 | 305.33 | 350.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 331.49 | 14.72 | 0.00 | 246.50 | 171.60 | 18.27 | 0.00 | 65.83 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 414.60 | 15.58 | 0.00 | 259.17 | 198.91 | 18.90 | 0.00 | 130.50 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 496.51 | 16.13 | 0.00 | 317.67 | 228.10 | 19.33 | 0.00 | 229.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 523.15 | 17.06 | 0.00 | 346.17 | 256.09 | 20.31 | 33.67 | 297.67 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 703.49 | 18.00 | 12.50 | 389.50 | 316.66 | 21.20 | 95.33 | 355.00 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 745.03 | 20.01 | 58.83 | 383.67 | 344.66 | 22.41 | 133.83 | 348.17 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 677.39 | 19.27 | 44.83 | 391.83 | 298.57 | 20.88 | 117.33 | 362.17 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 536.69 | 17.14 | 0.00 | 372.67 | 257.97 | 20.42 | 59.50 | 331.17 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 460.90 | 16.42 | 0.00 | 314.83 | 228.79 | 19.69 | 1.67 | 235.33 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 343.47 | 15.07 | 0.00 | 273.00 | 174.39 | 18.51 | 0.00 | 96.83 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 340.01 | 14.51 | 0.00 | 252.50 | 173.32 | 17.96 | 0.00 | 81.00 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 |
Annual Sum or Average | 4065.67 | 0.65 | 506.69 | 16.71 | 116.17 | 3787.17 | 241.01 | 19.80 | 441.33 | 2579.50 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 745.03 | 20.01 | 58.83 | 391.83 | 344.66 | 22.41 | 133.83 | 362.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 331.49 | 14.72 | 0.00 | 246.50 | 171.60 | 18.27 | 0.00 | 65.83 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 414.60 | 15.58 | 0.00 | 259.17 | 198.91 | 18.90 | 0.00 | 130.50 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 496.51 | 16.13 | 0.00 | 317.67 | 228.10 | 19.33 | 0.00 | 229.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 523.15 | 17.06 | 0.00 | 346.17 | 256.09 | 20.31 | 33.67 | 297.67 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 703.49 | 18.00 | 12.50 | 389.50 | 316.66 | 21.20 | 95.33 | 355.00 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 745.03 | 20.01 | 58.83 | 383.67 | 344.66 | 22.41 | 133.83 | 348.17 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 677.39 | 19.27 | 44.83 | 391.83 | 298.57 | 20.88 | 117.33 | 362.17 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 536.69 | 17.14 | 0.00 | 372.67 | 257.97 | 20.42 | 59.67 | 331.17 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 460.90 | 16.42 | 0.00 | 314.83 | 228.79 | 19.69 | 1.67 | 235.33 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 343.47 | 15.07 | 0.00 | 273.00 | 174.39 | 18.51 | 0.00 | 96.83 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 340.01 | 14.51 | 0.00 | 252.50 | 173.32 | 17.96 | 0.00 | 81.00 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 |
Annual Sum or Average | 4065.67 | 0.65 | 506.69 | 16.71 | 116.17 | 3787.17 | 241.01 | 19.80 | 441.50 | 2579.50 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 745.03 | 20.01 | 58.83 | 391.83 | 344.66 | 22.41 | 133.83 | 362.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.881387E+11 | 90253.45 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698606E+11 | 85881.20 | 03-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.945348E+11 | 86119.74 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.424804E+11 | 83366.03 | 15-APR-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369405E+11 | 81192.23 | 19-MAY-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669053E+10 | 57073.96 | 13-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.393054E+09 | 24584.59 | 06-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159162E+09 | 9134.38 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297738E+10 | 54349.65 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152450E+11 | 81096.67 | 29-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593274E+11 | 85584.79 | 29-NOV-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874460E+11 | 86094.38 | 28-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.159162E+09 | 9134.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.945348E+11 | 90253.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.410313E+09 | 2015.68 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325879E+09 | 1272.83 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625041E+09 | 1922.78 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119314E+09 | 1325.51 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159719E+09 | 999.65 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23268561.17 | 323.14 | 08-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 275714.09 | 295.04 | 18-SEP-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11191242.18 | 381.11 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84995652.25 | 894.47 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272723E+09 | 1474.67 | 13-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625041E+09 | 2015.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4649115.87 | 463.60 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6782444.29 | 337.78 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11431560.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6782444.29 | 463.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 74054837.22 | 931.16 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6186.09 | 10.31 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78332292.78 | 893.46 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2641479.19 | 245.04 | 01-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3877494.63 | 195.23 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78332292.78 | 931.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 79247200.29 | 701.92 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2238382.56 | 131.92 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79455960.19 | 601.29 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3226962.81 | 244.14 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12776625.63 | 243.01 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79455960.19 | 701.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120244E+10 | 8042.42 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321330E+09 | 7542.48 | 04-FEB-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936416E+09 | 7673.95 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102392E+09 | 3805.22 | 01-APR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101120E+09 | 2850.15 | 27-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35586961.97 | 823.96 | 12-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15180649.67 | 431.90 | 17-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11694191.25 | 431.90 | 28-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28787240.56 | 659.62 | 18-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35064172.05 | 1345.53 | 30-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245106E+09 | 5132.87 | 08-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.757969E+09 | 7548.03 | 23-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11694191.25 | 431.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120244E+10 | 8042.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 98478919.79 | 4586.83 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54443410.84 | 1764.25 | 28-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178303E+09 | 4291.17 | 30-MAR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 631974.70 | 1102.00 | 22-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5255147.71 | 1524.46 | 09-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 425459.45 | 940.45 | 08-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 685422.89 | 1061.12 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1827974.78 | 1462.52 | 13-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178303E+09 | 4586.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25229023.24 | 6896.92 | 03-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32317731.65 | 6216.22 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57546754.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32317731.65 | 6896.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.368084E+09 | 6644.51 | 03-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19417240.65 | 2268.70 | 28-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.476183E+09 | 5721.96 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16242956.98 | 2775.52 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10378824.58 | 1419.65 | 15-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.476183E+09 | 6644.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610953E+09 | 4739.61 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100479E+09 | 1687.87 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524739E+09 | 3801.88 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21523814.97 | 1838.30 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3373253.24 | 721.04 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13260806.49 | 1026.78 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263816E+09 | 2490.16 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610953E+09 | 4739.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152985E+09 | 4794.98 | 09-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 606854.99 | 468.64 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107059E+09 | 4511.46 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22971141.11 | 2693.99 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152985E+09 | 4794.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.796681E+10 | 8943.46 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641444E+10 | 8391.78 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857742E+10 | 8532.16 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405566E+10 | 8113.59 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360689E+10 | 7975.38 | 19-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639403E+09 | 5275.70 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37027780.10 | 2369.00 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17469178.06 | 904.59 | 24-AUG-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319034E+09 | 5276.32 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143387E+10 | 7833.53 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.564075E+10 | 8114.43 | 05-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800628E+10 | 8394.05 | 03-DEC-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17469178.06 | 904.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.857742E+10 | 8943.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551001E+09 | 4009.55 | 14-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375528E+09 | 4084.01 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605352E+09 | 4117.69 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93637755.69 | 4004.83 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74545984.35 | 4006.87 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11694687.91 | 4006.57 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6712406.77 | 4003.37 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6694470.75 | 3369.30 | 03-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10762875.83 | 4006.38 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26449475.31 | 4008.65 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179896E+09 | 4006.34 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420753E+09 | 4011.00 | 17-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6694470.75 | 3369.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.605352E+09 | 4117.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101198E+10 | 4098.33 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579087E+09 | 4076.11 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779243E+09 | 4112.39 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105379E+09 | 3989.65 | 30-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60731848.88 | 3985.50 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6178590.39 | 3983.20 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1761904.72 | 2752.66 | 08-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1970522.50 | 2957.14 | 22-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8398138.75 | 3663.85 | 03-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31374062.90 | 3988.05 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373392E+09 | 3988.47 | 24-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820720E+09 | 4092.50 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1761904.72 | 2752.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101198E+10 | 4112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226237E+10 | 23340.15 | 26-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547331E+09 | 23341.99 | 22-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131554E+10 | 23337.24 | 09-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142259E+09 | 23335.60 | 30-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79242185.21 | 23336.63 | 09-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35500959.74 | 23328.94 | 08-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11709625.54 | 15712.67 | 10-JUL-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19514447.45 | 15818.93 | 22-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53342100.41 | 23337.98 | 03-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65550758.98 | 23298.70 | 25-OCT-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433647E+09 | 23345.89 | 14-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148778E+10 | 23334.53 | 30-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11709625.54 | 15712.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226237E+10 | 23345.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544023E+09 | 3937.15 | 16-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439387E+09 | 4007.45 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657954E+09 | 4028.96 | 29-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114350E+09 | 3934.69 | 07-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109813E+09 | 3938.33 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15583688.38 | 3935.74 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1566812.06 | 2818.13 | 09-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1678920.45 | 3219.46 | 21-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10357569.68 | 3933.15 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29834115.70 | 3934.62 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219053E+09 | 3936.65 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451887E+09 | 3935.16 | 17-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1566812.06 | 2818.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657954E+09 | 4028.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.974402E+09 | 3989.38 | 02-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.662585E+09 | 3997.04 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842884E+09 | 4019.00 | 29-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142162E+09 | 3913.37 | 18-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96881103.86 | 3914.74 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8566823.18 | 3909.63 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1253482.54 | 1949.76 | 08-JUL-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1210215.29 | 2224.83 | 22-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9827838.90 | 3408.58 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43780251.92 | 3913.48 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440675E+09 | 3910.75 | 28-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.846817E+09 | 3998.21 | 12-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1210215.29 | 1949.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.974402E+09 | 4019.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262843E+09 | 1224.54 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206330E+09 | 1240.23 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277151E+09 | 1247.37 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61440795.38 | 1166.28 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55843952.09 | 1199.56 | 11-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9440326.87 | 1198.73 | 16-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1584885.58 | 1053.11 | 26-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1567989.76 | 945.85 | 03-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4779021.91 | 1035.95 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29612044.74 | 1200.03 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129048E+09 | 1069.99 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228108E+09 | 1158.82 | 17-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1567989.76 | 945.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277151E+09 | 1247.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447377E+09 | 1241.95 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290394E+09 | 1236.91 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341269E+09 | 1243.62 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65281345.41 | 1175.12 | 14-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41224881.93 | 1191.12 | 11-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4312534.28 | 1190.46 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 394681.29 | 698.35 | 08-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 494527.30 | 976.93 | 22-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3488371.81 | 928.04 | 11-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35259463.79 | 1192.15 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225276E+09 | 1208.57 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398351E+09 | 1239.23 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 394681.29 | 698.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447377E+09 | 1243.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307733E+09 | 4284.21 | 31-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280811E+09 | 4365.46 | 25-FEB-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.648400E+09 | 5860.38 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133105E+09 | 5764.41 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199841E+09 | 5771.59 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36546418.92 | 5767.77 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12249262.90 | 5587.09 | 08-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6165480.70 | 4227.09 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13020837.83 | 4555.53 | 22-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25906150.41 | 5752.81 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83618677.40 | 5765.32 | 24-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217824E+09 | 5279.74 | 06-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6165480.70 | 4227.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648400E+09 | 5860.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.574553E+11 | 0.573052E+11 | 209208.80 | 14-JAN-11:45 | 209208.80 | 0.25 |
February | 0.00 | 0.00 | 0.319855E+11 | 0.312701E+11 | 197295.73 | 01-FEB-11:45 | 197295.73 | 0.24 |
March | 0.00 | 0.00 | 0.354940E+11 | 0.348869E+11 | 180825.23 | 23-MAR-10:45 | 146777.63 | 0.24 |
April | 0.00 | 0.00 | 0.846909E+11 | 0.833200E+11 | 247984.44 | 26-APR-10:45 | 205151.70 | 0.47 |
May | 0.00 | 0.00 | 0.906633E+11 | 0.897867E+11 | 158994.96 | 18-MAY-10:45 | 143010.91 | 0.56 |
June | 0.00 | 0.00 | 0.167383E+12 | 0.146626E+12 | 310015.27 | 29-JUN-10:45 | 191716.12 | 0.85 |
July | 0.00 | 0.00 | 0.342462E+12 | 0.224523E+12 | 379363.38 | 31-JUL-10:45 | 224750.99 | 0.99 |
August | 0.00 | 0.00 | 0.385564E+12 | 0.234349E+12 | 406692.91 | 14-AUG-10:45 | 241588.81 | 0.99 |
September | 0.00 | 0.00 | 0.227607E+12 | 0.176344E+12 | 372683.64 | 22-SEP-12:00 | 185456.71 | 0.90 |
October | 0.00 | 0.00 | 0.258823E+12 | 0.208948E+12 | 384235.76 | 16-OCT-10:45 | 384235.76 | 0.61 |
November | 0.00 | 0.00 | 0.597894E+11 | 0.591585E+11 | 213902.40 | 19-NOV-11:45 | 213902.40 | 0.32 |
December | 0.00 | 0.00 | 0.662692E+11 | 0.662692E+11 | 193106.60 | 19-DEC-11:45 | 193106.60 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.180819E+13 | 0.141279E+13 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.319855E+11 | 0.312701E+11 | 158994.96 | 143010.91 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.385564E+12 | 0.234349E+12 | 406692.91 | 384235.76 | 0.99 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.352394E+10 | 0.349905E+10 | 20570.98 | 13-JAN-14:00 | 20570.98 | 0.16 |
February | 0.00 | 0.00 | 0.189694E+10 | 0.184114E+10 | 17583.23 | 01-FEB-09:51 | 17583.23 | 0.14 |
March | 0.00 | 0.00 | 0.213914E+10 | 0.197595E+10 | 22012.17 | 22-MAR-13:00 | 14832.69 | 0.12 |
April | 0.00 | 0.00 | 0.536186E+10 | 0.504844E+10 | 22090.96 | 26-APR-13:00 | 22090.96 | 0.27 |
May | 0.00 | 0.00 | 0.568659E+10 | 0.557961E+10 | 18829.64 | 04-MAY-13:00 | 16265.15 | 0.35 |
June | 0.00 | 0.00 | 0.127689E+11 | 0.101524E+11 | 30817.80 | 29-JUN-12:30 | 17826.82 | 0.64 |
July | 0.00 | 0.00 | 0.285718E+11 | 0.167816E+11 | 40153.36 | 31-JUL-12:30 | 23766.73 | 0.78 |
August | 0.00 | 0.00 | 0.326065E+11 | 0.176854E+11 | 38729.91 | 14-AUG-10:00 | 22142.75 | 0.78 |
September | 0.00 | 0.00 | 0.185738E+11 | 0.130116E+11 | 39619.58 | 22-SEP-12:15 | 19372.88 | 0.69 |
October | 0.00 | 0.00 | 0.206208E+11 | 0.151880E+11 | 38860.24 | 01-OCT-12:10 | 20585.66 | 0.46 |
November | 0.00 | 0.00 | 0.354751E+10 | 0.347968E+10 | 21516.80 | 19-NOV-13:05 | 21516.80 | 0.19 |
December | 0.00 | 0.00 | 0.428641E+10 | 0.428428E+10 | 20480.92 | 05-DEC-09:55 | 20480.92 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.139584E+12 | 0.985272E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.189694E+10 | 0.184114E+10 | 17583.23 | 14832.69 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.326065E+11 | 0.176854E+11 | 40153.36 | 23766.73 | 0.78 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.191871E+10 | 0.100795E+10 | 14239.27 | 03-JAN-16:01 | 14239.27 | 0.42 |
February | 0.00 | 0.00 | 0.170032E+10 | 0.933308E+09 | 14578.27 | 13-FEB-16:02 | 10763.79 | 0.39 |
March | 0.00 | 0.00 | 0.185571E+10 | 0.855041E+09 | 13923.36 | 18-MAR-15:01 | 12057.01 | 0.45 |
April | 0.00 | 0.00 | 0.386004E+10 | 0.185618E+10 | 14007.03 | 08-APR-08:62 | 11509.56 | 0.74 |
May | 0.00 | 0.00 | 0.360462E+10 | 0.165849E+10 | 14271.68 | 06-MAY-08:62 | 10702.30 | 0.73 |
June | 0.00 | 0.00 | 0.526085E+10 | 0.237790E+10 | 14541.67 | 16-JUN-15:01 | 11501.16 | 0.85 |
July | 0.00 | 0.00 | 0.757089E+10 | 0.359344E+10 | 15059.65 | 30-JUL-08:61 | 11156.94 | 0.91 |
August | 0.00 | 0.00 | 0.786349E+10 | 0.374912E+10 | 15286.58 | 18-AUG-08:62 | 10876.57 | 0.93 |
September | 0.00 | 0.00 | 0.609180E+10 | 0.283976E+10 | 15073.32 | 22-SEP-08:62 | 10793.79 | 0.90 |
October | 0.00 | 0.00 | 0.555890E+10 | 0.327707E+10 | 15208.21 | 01-OCT-08:61 | 11039.12 | 0.71 |
November | 0.00 | 0.00 | 0.263101E+10 | 0.137677E+10 | 14561.31 | 12-NOV-09:02 | 9927.20 | 0.53 |
December | 0.00 | 0.00 | 0.218230E+10 | 0.154968E+10 | 14241.72 | 05-DEC-16:02 | 14241.72 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.500986E+11 | 0.250747E+11 | 0.66 | |||
Minimum of Months | 0.00 | 0.00 | 0.170032E+10 | 0.855041E+09 | 13923.36 | 9927.20 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.786349E+10 | 0.374912E+10 | 15286.58 | 14241.72 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.400726E+09 | 0.189930E+09 | 13714.97 | 14-JAN-16:01 | 13714.97 | 0.17 |
February | 0.00 | 0.00 | 0.551930E+09 | 0.246052E+09 | 13875.69 | 13-FEB-16:02 | 10093.51 | 0.22 |
March | 0.00 | 0.00 | 0.790828E+09 | 0.299648E+09 | 13816.83 | 22-MAR-18:51 | 10995.22 | 0.27 |
April | 0.00 | 0.00 | 0.216010E+10 | 0.820813E+09 | 14773.55 | 26-APR-21:51 | 11098.42 | 0.56 |
May | 0.00 | 0.00 | 0.240894E+10 | 0.950428E+09 | 14292.55 | 02-MAY-21:51 | 11088.27 | 0.57 |
June | 0.00 | 0.00 | 0.333356E+10 | 0.141358E+10 | 15305.42 | 28-JUN-21:51 | 11234.47 | 0.55 |
July | 0.00 | 0.00 | 0.488563E+10 | 0.234808E+10 | 15544.72 | 19-JUL-21:51 | 10934.43 | 0.56 |
August | 0.00 | 0.00 | 0.463556E+10 | 0.213766E+10 | 15525.07 | 19-AUG-08:51 | 10481.00 | 0.56 |
September | 0.00 | 0.00 | 0.328257E+10 | 0.134100E+10 | 15020.53 | 30-SEP-21:51 | 10981.27 | 0.55 |
October | 0.00 | 0.00 | 0.258425E+10 | 0.141163E+10 | 15449.47 | 01-OCT-08:52 | 10007.76 | 0.41 |
November | 0.00 | 0.00 | 0.752993E+09 | 0.314451E+09 | 13996.38 | 12-NOV-09:02 | 9473.49 | 0.30 |
December | 0.00 | 0.00 | 0.424619E+09 | 0.286869E+09 | 13719.51 | 31-DEC-16:01 | 13719.51 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.262117E+11 | 0.117601E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.400726E+09 | 0.189930E+09 | 13714.97 | 9473.49 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.488563E+10 | 0.234808E+10 | 15544.72 | 13719.51 | 0.57 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.314637E+11 | 0.215651E+11 | 44774.73 | 14-JAN-12:40 | 44774.73 | 0.51 |
February | 0.00 | 0.00 | 0.197937E+11 | 0.126937E+11 | 39959.64 | 02-FEB-12:30 | 34148.47 | 0.43 |
March | 0.00 | 0.00 | 0.142695E+11 | 0.571585E+10 | 33022.58 | 11-MAR-13:10 | 26644.32 | 0.50 |
April | 0.00 | 0.00 | 0.164759E+11 | 0.522226E+10 | 25114.32 | 08-APR-12:40 | 12703.18 | 0.66 |
May | 0.00 | 0.00 | 0.923484E+10 | 0.199727E+10 | 23781.09 | 04-MAY-15:03 | 10876.41 | 0.59 |
June | 0.00 | 0.00 | 0.133570E+11 | 0.293034E+10 | 18311.57 | 30-JUN-07:00 | 5692.27 | 0.71 |
July | 0.00 | 0.00 | 0.223705E+11 | 0.596089E+10 | 25725.06 | 23-JUL-15:03 | 11341.46 | 0.86 |
August | 0.00 | 0.00 | 0.304191E+11 | 0.979213E+10 | 24633.28 | 27-AUG-12:10 | 11422.41 | 0.97 |
September | 0.00 | 0.00 | 0.329171E+11 | 0.134121E+11 | 42230.61 | 30-SEP-13:05 | 39382.80 | 0.96 |
October | 0.00 | 0.00 | 0.414860E+11 | 0.264774E+11 | 51380.22 | 16-OCT-12:20 | 51380.22 | 0.71 |
November | 0.00 | 0.00 | 0.328573E+11 | 0.208223E+11 | 48376.09 | 19-NOV-12:30 | 37576.77 | 0.62 |
December | 0.00 | 0.00 | 0.358677E+11 | 0.281757E+11 | 46025.56 | 19-DEC-13:00 | 46025.56 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.300512E+12 | 0.154765E+12 | 0.66 | |||
Minimum of Months | 0.00 | 0.00 | 0.923484E+10 | 0.199727E+10 | 18311.57 | 5692.27 | 0.41 | |
Maximum of Months | 0.00 | 0.00 | 0.414860E+11 | 0.281757E+11 | 51380.22 | 51380.22 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.978209E+10 | 0.472958E+10 | 84898.66 | 20-JAN-19:01 | 66786.11 | 0.33 |
February | 0.00 | 0.00 | 0.111114E+11 | 0.493709E+10 | 83490.59 | 13-FEB-21:12 | 65543.67 | 0.47 |
March | 0.00 | 0.00 | 0.139423E+11 | 0.585970E+10 | 82361.33 | 22-MAR-18:51 | 66472.91 | 0.51 |
April | 0.00 | 0.00 | 0.215816E+11 | 0.101262E+11 | 89739.03 | 26-APR-21:51 | 66977.97 | 0.55 |
May | 0.00 | 0.00 | 0.258125E+11 | 0.133562E+11 | 87568.42 | 04-MAY-21:51 | 69497.79 | 0.55 |
June | 0.00 | 0.00 | 0.299231E+11 | 0.162785E+11 | 92943.37 | 28-JUN-21:51 | 67819.78 | 0.48 |
July | 0.00 | 0.00 | 0.365632E+11 | 0.206085E+11 | 94996.09 | 19-JUL-21:51 | 66355.23 | 0.49 |
August | 0.00 | 0.00 | 0.338858E+11 | 0.181904E+11 | 93875.40 | 16-AUG-21:51 | 66979.36 | 0.47 |
September | 0.00 | 0.00 | 0.263197E+11 | 0.132247E+11 | 93243.26 | 22-SEP-21:52 | 64940.31 | 0.45 |
October | 0.00 | 0.00 | 0.235691E+11 | 0.145993E+11 | 93073.43 | 01-OCT-08:52 | 62987.05 | 0.36 |
November | 0.00 | 0.00 | 0.129231E+11 | 0.628219E+10 | 85374.22 | 09-NOV-22:53 | 63763.92 | 0.43 |
December | 0.00 | 0.00 | 0.903571E+10 | 0.546505E+10 | 81865.66 | 05-DEC-16:02 | 81865.66 | 0.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.254450E+12 | 0.133657E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.903571E+10 | 0.472958E+10 | 81865.66 | 62987.05 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.365632E+11 | 0.206085E+11 | 94996.09 | 81865.66 | 0.55 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.204059E+10 | 0.118754E+10 | 12597.74 | 03-JAN-16:01 | 12597.74 | 0.43 |
February | 0.00 | 0.00 | 0.159971E+10 | 0.927738E+09 | 12597.84 | 01-FEB-09:01 | 12597.84 | 0.38 |
March | 0.00 | 0.00 | 0.183639E+10 | 0.867316E+09 | 12306.10 | 15-MAR-15:01 | 10687.66 | 0.45 |
April | 0.00 | 0.00 | 0.351168E+10 | 0.169643E+10 | 12592.62 | 02-APR-08:62 | 12592.62 | 0.74 |
May | 0.00 | 0.00 | 0.309002E+10 | 0.140316E+10 | 12751.14 | 06-MAY-08:62 | 9788.56 | 0.72 |
June | 0.00 | 0.00 | 0.446306E+10 | 0.197884E+10 | 12979.13 | 28-JUN-08:62 | 9440.35 | 0.86 |
July | 0.00 | 0.00 | 0.692840E+10 | 0.326331E+10 | 12760.44 | 13-JUL-18:01 | 10335.87 | 0.95 |
August | 0.00 | 0.00 | 0.750859E+10 | 0.359781E+10 | 12994.27 | 08-AUG-08:62 | 9784.45 | 0.95 |
September | 0.00 | 0.00 | 0.525808E+10 | 0.241236E+10 | 13212.99 | 23-SEP-08:62 | 9217.52 | 0.90 |
October | 0.00 | 0.00 | 0.527047E+10 | 0.317353E+10 | 13489.85 | 01-OCT-08:61 | 9749.92 | 0.71 |
November | 0.00 | 0.00 | 0.243818E+10 | 0.140161E+10 | 12893.94 | 12-NOV-09:02 | 8760.69 | 0.52 |
December | 0.00 | 0.00 | 0.218862E+10 | 0.165657E+10 | 12598.68 | 23-DEC-09:01 | 12598.68 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.461338E+11 | 0.235662E+11 | 0.66 | |||
Minimum of Months | 0.00 | 0.00 | 0.159971E+10 | 0.867316E+09 | 12306.10 | 8760.69 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.750859E+10 | 0.359781E+10 | 13489.85 | 12598.68 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.535782E+09 | 0.288243E+09 | 12176.85 | 20-JAN-19:01 | 9091.42 | 0.17 |
February | 0.00 | 0.00 | 0.556899E+09 | 0.296744E+09 | 12247.36 | 01-FEB-09:51 | 12247.36 | 0.20 |
March | 0.00 | 0.00 | 0.857113E+09 | 0.381529E+09 | 12082.71 | 24-MAR-15:01 | 10097.62 | 0.28 |
April | 0.00 | 0.00 | 0.210116E+10 | 0.989115E+09 | 12939.02 | 02-APR-08:51 | 12939.02 | 0.53 |
May | 0.00 | 0.00 | 0.216571E+10 | 0.972426E+09 | 13274.28 | 24-MAY-08:51 | 13274.28 | 0.55 |
June | 0.00 | 0.00 | 0.297547E+10 | 0.132169E+10 | 13835.82 | 30-JUN-08:51 | 11483.88 | 0.57 |
July | 0.00 | 0.00 | 0.458800E+10 | 0.219690E+10 | 14344.28 | 30-JUL-08:51 | 11069.98 | 0.58 |
August | 0.00 | 0.00 | 0.452885E+10 | 0.212270E+10 | 14576.97 | 18-AUG-08:51 | 11002.33 | 0.58 |
September | 0.00 | 0.00 | 0.273979E+10 | 0.121024E+10 | 14010.14 | 10-SEP-08:51 | 11366.11 | 0.56 |
October | 0.00 | 0.00 | 0.241698E+10 | 0.143134E+10 | 14032.94 | 17-OCT-08:21 | 14032.94 | 0.42 |
November | 0.00 | 0.00 | 0.731584E+09 | 0.364404E+09 | 12361.73 | 12-NOV-09:02 | 8332.30 | 0.24 |
December | 0.00 | 0.00 | 0.463394E+09 | 0.326505E+09 | 12770.69 | 05-DEC-09:41 | 12770.69 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.246607E+11 | 0.119018E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.463394E+09 | 0.288243E+09 | 12082.71 | 8332.30 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.458800E+10 | 0.219690E+10 | 14576.97 | 14032.94 | 0.58 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.410664E+09 | 0.229603E+09 | 3840.74 | 21-JAN-09:02 | 2719.85 | 0.32 |
February | 0.00 | 0.00 | 0.373467E+09 | 0.215122E+09 | 3779.79 | 13-FEB-16:02 | 2722.81 | 0.29 |
March | 0.00 | 0.00 | 0.443135E+09 | 0.221848E+09 | 3697.44 | 24-MAR-08:61 | 2644.37 | 0.35 |
April | 0.00 | 0.00 | 0.941031E+09 | 0.486424E+09 | 3716.12 | 12-APR-08:62 | 2664.56 | 0.64 |
May | 0.00 | 0.00 | 0.860524E+09 | 0.420163E+09 | 3881.14 | 06-MAY-08:62 | 2483.69 | 0.64 |
June | 0.00 | 0.00 | 0.129313E+10 | 0.616889E+09 | 3890.23 | 28-JUN-08:62 | 2575.25 | 0.81 |
July | 0.00 | 0.00 | 0.190395E+10 | 0.933156E+09 | 4028.40 | 30-JUL-08:61 | 2780.34 | 0.92 |
August | 0.00 | 0.00 | 0.195071E+10 | 0.956387E+09 | 4138.31 | 06-AUG-08:61 | 2668.17 | 0.93 |
September | 0.00 | 0.00 | 0.143606E+10 | 0.692422E+09 | 4055.53 | 22-SEP-08:62 | 2602.02 | 0.88 |
October | 0.00 | 0.00 | 0.126800E+10 | 0.762886E+09 | 4104.90 | 01-OCT-08:61 | 2717.50 | 0.64 |
November | 0.00 | 0.00 | 0.551249E+09 | 0.299447E+09 | 3721.05 | 11-NOV-16:01 | 2740.06 | 0.41 |
December | 0.00 | 0.00 | 0.459409E+09 | 0.339355E+09 | 3685.90 | 05-DEC-16:02 | 3685.90 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.118913E+11 | 0.617370E+10 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.373467E+09 | 0.215122E+09 | 3685.90 | 2483.69 | 0.24 | |
Maximum of Months | 0.00 | 0.00 | 0.195071E+10 | 0.956387E+09 | 4138.31 | 3685.90 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 68657856.61 | 36929445.63 | 3541.58 | 14-JAN-16:01 | 3541.58 | 0.09 |
February | 0.00 | 0.00 | 0.100500E+09 | 48548239.43 | 3541.30 | 06-FEB-16:01 | 3541.30 | 0.14 |
March | 0.00 | 0.00 | 0.174698E+09 | 72526573.82 | 3632.99 | 22-MAR-18:51 | 2916.84 | 0.20 |
April | 0.00 | 0.00 | 0.511356E+09 | 0.211393E+09 | 3917.86 | 26-APR-21:51 | 2873.56 | 0.46 |
May | 0.00 | 0.00 | 0.569708E+09 | 0.242038E+09 | 3776.67 | 03-MAY-21:51 | 2973.53 | 0.50 |
June | 0.00 | 0.00 | 0.863079E+09 | 0.383161E+09 | 4063.79 | 28-JUN-21:51 | 2916.30 | 0.55 |
July | 0.00 | 0.00 | 0.131327E+10 | 0.651353E+09 | 4117.27 | 27-JUL-21:51 | 2880.16 | 0.57 |
August | 0.00 | 0.00 | 0.121345E+10 | 0.571484E+09 | 4081.63 | 16-AUG-21:51 | 2846.79 | 0.56 |
September | 0.00 | 0.00 | 0.768472E+09 | 0.317929E+09 | 3935.76 | 30-SEP-21:51 | 2762.89 | 0.56 |
October | 0.00 | 0.00 | 0.561017E+09 | 0.317850E+09 | 4072.36 | 01-OCT-08:52 | 2456.32 | 0.36 |
November | 0.00 | 0.00 | 0.116378E+09 | 53962318.95 | 3550.66 | 11-NOV-16:01 | 2517.51 | 0.17 |
December | 0.00 | 0.00 | 64803156.34 | 49331065.50 | 3541.66 | 30-DEC-16:01 | 3541.66 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.632539E+10 | 0.295651E+10 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 64803156.34 | 36929445.63 | 3541.30 | 2456.32 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.131327E+10 | 0.651353E+09 | 4117.27 | 3541.66 | 0.57 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.725121E+10 | 0.515667E+10 | 17392.91 | 15-JAN-16:01 | 17392.91 | 0.60 |
February | 0.00 | 0.00 | 0.477842E+10 | 0.317392E+10 | 17941.41 | 11-FEB-16:02 | 12794.82 | 0.54 |
March | 0.00 | 0.00 | 0.415033E+10 | 0.218387E+10 | 17249.14 | 20-MAR-15:01 | 14434.77 | 0.57 |
April | 0.00 | 0.00 | 0.507629E+10 | 0.231917E+10 | 17130.58 | 08-APR-08:62 | 14589.22 | 0.75 |
May | 0.00 | 0.00 | 0.321881E+10 | 0.120638E+10 | 17570.87 | 06-MAY-08:62 | 13232.30 | 0.65 |
June | 0.00 | 0.00 | 0.441828E+10 | 0.159503E+10 | 17922.54 | 16-JUN-15:01 | 13609.89 | 0.79 |
July | 0.00 | 0.00 | 0.715796E+10 | 0.285181E+10 | 18923.73 | 30-JUL-08:61 | 13320.62 | 0.88 |
August | 0.00 | 0.00 | 0.901568E+10 | 0.390682E+10 | 19089.20 | 20-AUG-08:61 | 13195.56 | 0.91 |
September | 0.00 | 0.00 | 0.868136E+10 | 0.428469E+10 | 18654.41 | 22-SEP-08:62 | 13096.00 | 0.89 |
October | 0.00 | 0.00 | 0.999215E+10 | 0.675005E+10 | 19109.85 | 05-OCT-18:01 | 13167.90 | 0.73 |
November | 0.00 | 0.00 | 0.746247E+10 | 0.511122E+10 | 17819.07 | 11-NOV-16:01 | 14079.69 | 0.66 |
December | 0.00 | 0.00 | 0.780442E+10 | 0.628712E+10 | 17392.48 | 29-DEC-19:01 | 17392.48 | 0.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.790074E+11 | 0.448267E+11 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.321881E+10 | 0.120638E+10 | 17130.58 | 12794.82 | 0.45 | |
Maximum of Months | 0.00 | 0.00 | 0.999215E+10 | 0.675005E+10 | 19109.85 | 17392.91 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 39137.43 | 157985.91 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 33047.55 | 114777.01 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 41409.11 | 145961.47 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18259.29 | 108312.68 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15401.03 | 96727.15 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2879.78 | 64253.74 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 180.90 | 26771.94 | 06-JUL-03:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 82.76 | 24722.60 | 28-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1320.32 | 60473.10 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6305.83 | 90885.20 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25829.52 | 104821.87 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 37716.56 | 120212.37 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 18414.36 | ||||
Minimum of Months | 0.00 | 0.00 | 82.76 | 24722.60 | ||
Maximum of Months | 0.00 | 0.00 | 41409.11 | 157985.91 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 44644.30 | 330190.06 | 14-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 32589.52 | 308453.58 | 01-FEB-09:51 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 30059.40 | 341227.97 | 23-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 58453.78 | 321489.97 | 11-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57040.52 | 315028.86 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 96966.35 | 379428.63 | 28-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 175384.17 | 532078.27 | 18-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 195872.53 | 542005.34 | 18-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 130777.59 | 501577.04 | 29-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 140981.08 | 506514.25 | 14-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 49705.91 | 384220.39 | 19-NOV-09:41 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 49978.81 | 364313.33 | 05-DEC-09:41 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 89047.67 | 0.00 | ||||
Minimum of Months | 30059.40 | 308453.58 | 0.00 | 0.00 | ||
Maximum of Months | 195872.53 | 542005.34 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 24241.13 | 49013.46 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 24271.28 | 49031.78 | 03-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 24039.37 | 48773.85 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23559.05 | 47893.67 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22999.11 | 46865.62 | 02-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22503.51 | 45719.50 | 02-JUN-06:53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22173.11 | 44744.80 | 05-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22161.44 | 44645.88 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22406.76 | 45442.47 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22869.90 | 46573.85 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23433.43 | 47736.08 | 28-NOV-07:45 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23932.79 | 48581.50 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 23209.86 | ||||
Minimum of Months | 0.00 | 0.00 | 22161.44 | 44645.88 | ||
Maximum of Months | 0.00 | 0.00 | 24271.28 | 49031.78 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 25-JAN-16:04 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-00:50 | 0.89 |
March | 0.271000E+10 | 0.70 | 1299.30 | 01-MAR-03:40 | 0.89 |
April | 0.262258E+10 | 0.70 | 1299.30 | 03-APR-15:04 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 01-MAY-00:30 | 0.88 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-04:00 | 0.89 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-01:40 | 0.88 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-02:00 | 0.89 |
September | 0.262258E+10 | 0.70 | 1299.30 | 29-SEP-16:20 | 0.89 |
October | 0.271000E+10 | 0.70 | 1299.30 | 14-OCT-15:40 | 0.89 |
November | 0.262258E+10 | 0.70 | 1299.30 | 01-NOV-00:05 | 0.89 |
December | 0.271000E+10 | 0.71 | 1299.30 | 29-DEC-16:03 | 0.90 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.353135E+11 | 0.85 | 23417.92 | 18-JAN-22:10 | 1.19 |
February | 0.323363E+11 | 0.86 | 22485.97 | 01-FEB-22:10 | 1.16 |
March | 0.354661E+11 | 0.85 | 22350.83 | 24-MAR-21:10 | 1.16 |
April | 0.354494E+11 | 0.87 | 23107.86 | 26-APR-21:10 | 1.18 |
May | 0.368926E+11 | 0.87 | 24163.07 | 04-MAY-21:10 | 1.21 |
June | 0.364179E+11 | 0.88 | 23880.37 | 27-JUN-21:10 | 1.20 |
July | 0.380372E+11 | 0.88 | 24815.53 | 31-JUL-21:10 | 1.23 |
August | 0.382506E+11 | 0.88 | 25255.99 | 18-AUG-21:10 | 1.24 |
September | 0.365331E+11 | 0.88 | 27415.00 | 29-SEP-21:10 | 1.32 |
October | 0.382605E+11 | 0.89 | 28432.85 | 16-OCT-21:10 | 1.35 |
November | 0.352946E+11 | 0.87 | 23879.26 | 28-NOV-22:10 | 1.22 |
December | 0.357230E+11 | 0.86 | 25210.88 | 05-DEC-22:10 | 1.26 |
Annual Sum or Average | 0.433975E+12 | 0.87 | |||
Minimum of Months | 0.323363E+11 | 0.85 | 22350.83 | 1.16 | |
Maximum of Months | 0.382605E+11 | 0.89 | 28432.85 | 1.35 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160063E+09 | 0.49 | 697.92 | 02-JAN-16:02 | 0.59 |
February | 0.133742E+09 | 0.47 | 697.92 | 01-FEB-09:01 | 0.59 |
March | 0.159732E+09 | 0.46 | 697.92 | 01-MAR-16:01 | 0.58 |
April | 0.189402E+09 | 0.50 | 697.92 | 01-APR-15:01 | 0.59 |
May | 0.175640E+09 | 0.48 | 697.92 | 01-MAY-08:62 | 0.58 |
June | 0.227159E+09 | 0.50 | 697.92 | 01-JUN-15:01 | 0.58 |
July | 0.310911E+09 | 0.53 | 697.92 | 01-JUL-08:61 | 0.58 |
August | 0.318748E+09 | 0.54 | 697.92 | 01-AUG-08:62 | 0.58 |
September | 0.258674E+09 | 0.53 | 697.92 | 01-SEP-08:62 | 0.58 |
October | 0.256331E+09 | 0.52 | 697.92 | 01-OCT-08:61 | 0.58 |
November | 0.151067E+09 | 0.50 | 697.92 | 01-NOV-08:62 | 0.58 |
December | 0.163163E+09 | 0.50 | 697.92 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.250463E+10 | 0.50 | |||
Minimum of Months | 0.133742E+09 | 0.46 | 697.92 | 0.58 | |
Maximum of Months | 0.318748E+09 | 0.54 | 697.92 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132084E+09 | 0.39 | 672.20 | 01-JAN-19:03 | 0.58 |
February | 0.103134E+09 | 0.40 | 672.20 | 01-FEB-16:01 | 0.58 |
March | 0.127921E+09 | 0.41 | 672.20 | 01-MAR-16:01 | 0.58 |
April | 0.110808E+09 | 0.39 | 672.20 | 01-APR-15:01 | 0.59 |
May | 0.116806E+09 | 0.37 | 672.20 | 01-MAY-08:51 | 0.58 |
June | 0.135258E+09 | 0.32 | 672.20 | 01-JUN-08:51 | 0.58 |
July | 0.190150E+09 | 0.33 | 672.20 | 01-JUL-08:51 | 0.58 |
August | 0.178610E+09 | 0.32 | 672.20 | 01-AUG-08:51 | 0.58 |
September | 0.135582E+09 | 0.32 | 672.20 | 01-SEP-08:51 | 0.58 |
October | 0.125495E+09 | 0.33 | 672.20 | 01-OCT-08:52 | 0.58 |
November | 90971064.44 | 0.39 | 672.20 | 01-NOV-15:01 | 0.58 |
December | 0.119573E+09 | 0.39 | 672.20 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.156639E+10 | 0.36 | |||
Minimum of Months | 90971064.44 | 0.32 | 672.20 | 0.58 | |
Maximum of Months | 0.190150E+09 | 0.41 | 672.20 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111296E+10 | 0.42 | 1378.43 | 14-JAN-12:40 | 0.59 |
February | 0.715212E+09 | 0.34 | 1253.81 | 02-FEB-12:30 | 0.58 |
March | 0.545187E+09 | 0.30 | 1158.12 | 11-MAR-13:00 | 0.59 |
April | 0.624582E+09 | 0.40 | 788.63 | 08-APR-12:40 | 0.58 |
May | 0.393872E+09 | 0.34 | 735.74 | 04-MAY-15:03 | 0.58 |
June | 0.519015E+09 | 0.41 | 551.95 | 30-JUN-07:00 | 0.58 |
July | 0.790959E+09 | 0.50 | 754.82 | 23-JUL-15:03 | 0.58 |
August | 0.103816E+10 | 0.56 | 765.05 | 30-AUG-13:00 | 0.58 |
September | 0.113315E+10 | 0.56 | 1338.51 | 30-SEP-13:05 | 0.58 |
October | 0.143312E+10 | 0.53 | 2142.17 | 31-OCT-12:15 | 0.58 |
November | 0.116681E+10 | 0.46 | 2253.19 | 19-NOV-09:53 | 0.59 |
December | 0.126508E+10 | 0.45 | 2103.55 | 25-DEC-13:30 | 0.59 |
Annual Sum or Average | 0.107381E+11 | 0.44 | |||
Minimum of Months | 0.393872E+09 | 0.30 | 551.95 | 0.58 | |
Maximum of Months | 0.143312E+10 | 0.56 | 2253.19 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.765574E+09 | 0.37 | 4090.49 | 01-JAN-09:01 | 0.58 |
February | 0.666810E+09 | 0.38 | 4090.49 | 01-FEB-09:51 | 0.59 |
March | 0.857518E+09 | 0.39 | 4090.49 | 01-MAR-09:01 | 0.59 |
April | 0.931206E+09 | 0.34 | 4090.49 | 01-APR-08:62 | 0.59 |
May | 0.110327E+10 | 0.32 | 4090.49 | 01-MAY-08:51 | 0.58 |
June | 0.118651E+10 | 0.28 | 4090.49 | 01-JUN-08:51 | 0.58 |
July | 0.143029E+10 | 0.28 | 4090.49 | 01-JUL-08:51 | 0.58 |
August | 0.129158E+10 | 0.27 | 4090.49 | 01-AUG-08:51 | 0.58 |
September | 0.103081E+10 | 0.27 | 4090.49 | 01-SEP-08:51 | 0.58 |
October | 0.102705E+10 | 0.28 | 4090.49 | 01-OCT-08:52 | 0.58 |
November | 0.701959E+09 | 0.35 | 4090.49 | 01-NOV-08:62 | 0.58 |
December | 0.683843E+09 | 0.36 | 4090.49 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.116764E+11 | 0.33 | |||
Minimum of Months | 0.666810E+09 | 0.27 | 4090.49 | 0.58 | |
Maximum of Months | 0.143029E+10 | 0.39 | 4090.49 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157274E+09 | 0.50 | 617.05 | 01-JAN-09:01 | 0.58 |
February | 0.130882E+09 | 0.48 | 617.05 | 01-FEB-09:01 | 0.59 |
March | 0.155160E+09 | 0.47 | 617.05 | 01-MAR-09:01 | 0.58 |
April | 0.170746E+09 | 0.52 | 617.05 | 01-APR-08:62 | 0.58 |
May | 0.152802E+09 | 0.49 | 617.05 | 01-MAY-08:62 | 0.58 |
June | 0.187902E+09 | 0.51 | 617.05 | 01-JUN-08:62 | 0.58 |
July | 0.276450E+09 | 0.55 | 617.05 | 01-JUL-08:61 | 0.58 |
August | 0.297319E+09 | 0.55 | 617.05 | 01-AUG-08:62 | 0.58 |
September | 0.220426E+09 | 0.53 | 617.05 | 01-SEP-08:62 | 0.58 |
October | 0.239916E+09 | 0.53 | 617.05 | 01-OCT-08:61 | 0.58 |
November | 0.146108E+09 | 0.51 | 617.05 | 01-NOV-08:62 | 0.58 |
December | 0.160562E+09 | 0.50 | 617.05 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.229555E+10 | 0.51 | |||
Minimum of Months | 0.130882E+09 | 0.47 | 617.05 | 0.58 | |
Maximum of Months | 0.297319E+09 | 0.55 | 617.05 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122138E+09 | 0.37 | 593.75 | 01-JAN-09:01 | 0.58 |
February | 0.101716E+09 | 0.39 | 593.75 | 01-FEB-09:51 | 0.59 |
March | 0.125894E+09 | 0.41 | 593.75 | 01-MAR-09:01 | 0.58 |
April | 0.112757E+09 | 0.41 | 593.75 | 01-APR-08:62 | 0.58 |
May | 0.110934E+09 | 0.39 | 593.75 | 01-MAY-08:51 | 0.58 |
June | 0.127239E+09 | 0.34 | 593.75 | 01-JUN-08:51 | 0.58 |
July | 0.187071E+09 | 0.34 | 593.75 | 01-JUL-08:51 | 0.58 |
August | 0.183822E+09 | 0.34 | 593.75 | 01-AUG-08:51 | 0.58 |
September | 0.118670E+09 | 0.34 | 593.75 | 01-SEP-08:51 | 0.58 |
October | 0.118392E+09 | 0.34 | 593.75 | 01-OCT-08:52 | 0.58 |
November | 89153310.93 | 0.36 | 593.75 | 01-NOV-08:62 | 0.58 |
December | 0.112377E+09 | 0.37 | 593.75 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.151016E+10 | 0.36 | |||
Minimum of Months | 89153310.93 | 0.34 | 593.75 | 0.58 | |
Maximum of Months | 0.187071E+09 | 0.41 | 593.75 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 45970700.45 | 0.49 | 180.65 | 01-JAN-19:03 | 0.58 |
February | 40316959.79 | 0.47 | 180.65 | 01-FEB-09:01 | 0.59 |
March | 48325004.41 | 0.46 | 180.65 | 01-MAR-16:01 | 0.58 |
April | 50563116.06 | 0.50 | 180.65 | 01-APR-15:01 | 0.59 |
May | 46688894.28 | 0.49 | 180.65 | 01-MAY-08:62 | 0.58 |
June | 57346397.67 | 0.51 | 180.65 | 01-JUN-15:01 | 0.58 |
July | 79221154.93 | 0.54 | 180.65 | 01-JUL-08:61 | 0.58 |
August | 80133455.63 | 0.54 | 180.65 | 01-AUG-08:62 | 0.58 |
September | 62366659.62 | 0.53 | 180.65 | 01-SEP-08:62 | 0.58 |
October | 62498952.78 | 0.52 | 180.65 | 01-OCT-08:61 | 0.58 |
November | 40891022.05 | 0.50 | 180.65 | 01-NOV-15:01 | 0.58 |
December | 46247300.17 | 0.49 | 180.65 | 01-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.660570E+09 | 0.50 | |||
Minimum of Months | 40316959.79 | 0.46 | 180.65 | 0.58 | |
Maximum of Months | 80133455.63 | 0.54 | 180.65 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 43870244.76 | 0.39 | 173.61 | 01-JAN-09:01 | 0.58 |
February | 34369662.38 | 0.40 | 173.61 | 01-FEB-16:01 | 0.58 |
March | 40678162.01 | 0.41 | 173.61 | 01-MAR-09:01 | 0.58 |
April | 30186845.86 | 0.39 | 173.61 | 01-APR-15:01 | 0.59 |
May | 30415666.44 | 0.38 | 173.61 | 01-MAY-08:51 | 0.58 |
June | 35491702.30 | 0.33 | 173.61 | 01-JUN-08:51 | 0.58 |
July | 51465696.90 | 0.33 | 173.61 | 01-JUL-08:51 | 0.58 |
August | 47068943.96 | 0.33 | 173.61 | 01-AUG-08:51 | 0.58 |
September | 32364858.95 | 0.33 | 173.61 | 01-SEP-08:51 | 0.58 |
October | 30972916.75 | 0.33 | 173.61 | 01-OCT-08:52 | 0.58 |
November | 30065423.20 | 0.39 | 173.61 | 01-NOV-15:01 | 0.58 |
December | 40816558.71 | 0.39 | 173.61 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.447767E+09 | 0.37 | |||
Minimum of Months | 30065423.20 | 0.33 | 173.61 | 0.58 | |
Maximum of Months | 51465696.90 | 0.41 | 173.61 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369579E+09 | 0.53 | 848.13 | 01-JAN-09:01 | 0.58 |
February | 0.253865E+09 | 0.50 | 848.13 | 01-FEB-09:01 | 0.59 |
March | 0.251889E+09 | 0.48 | 848.13 | 01-MAR-09:01 | 0.58 |
April | 0.233817E+09 | 0.51 | 848.13 | 01-APR-08:62 | 0.59 |
May | 0.170695E+09 | 0.47 | 848.13 | 01-MAY-08:62 | 0.58 |
June | 0.187509E+09 | 0.48 | 848.13 | 01-JUN-15:01 | 0.58 |
July | 0.276526E+09 | 0.52 | 848.13 | 01-JUL-08:61 | 0.58 |
August | 0.343634E+09 | 0.53 | 848.13 | 01-AUG-08:62 | 0.58 |
September | 0.349561E+09 | 0.52 | 848.13 | 01-SEP-08:62 | 0.58 |
October | 0.450944E+09 | 0.53 | 848.13 | 01-OCT-08:61 | 0.58 |
November | 0.350548E+09 | 0.53 | 848.13 | 01-NOV-08:62 | 0.58 |
December | 0.392019E+09 | 0.54 | 848.13 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.363059E+10 | 0.51 | |||
Minimum of Months | 0.170695E+09 | 0.47 | 848.13 | 0.58 | |
Maximum of Months | 0.450944E+09 | 0.54 | 848.13 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.595006E+09 | 0.535506E+09 | 587.77 | 08-JAN-06:50 | 528.99 | 528.99 | 36.17 | 1.58 |
February | 0.489270E+09 | 0.440343E+09 | 556.29 | 04-FEB-06:00 | 500.66 | 500.66 | 38.06 | 1.24 |
March | 0.643712E+09 | 0.579340E+09 | 584.01 | 30-MAR-03:00 | 525.61 | 525.61 | 37.29 | 1.54 |
April | 0.297498E+09 | 0.267748E+09 | 550.83 | 01-APR-05:00 | 495.75 | 495.75 | 38.34 | 1.20 |
May | 0.257683E+09 | 0.231914E+09 | 533.69 | 14-MAY-04:50 | 480.32 | 480.32 | 38.47 | 1.07 |
June | 47920120.81 | 43128108.73 | 403.37 | 13-JUN-04:00 | 363.03 | 363.03 | 34.25 | 0.60 |
July | 3264903.40 | 2938413.06 | 168.91 | 06-JUL-03:00 | 152.02 | 152.02 | 26.93 | 0.19 |
August | 1657585.27 | 1491826.75 | 159.40 | 22-AUG-08:54 | 143.46 | 143.46 | 40.42 | 0.18 |
September | 22211955.86 | 19990760.27 | 383.38 | 20-SEP-04:00 | 345.04 | 345.04 | 33.73 | 0.55 |
October | 0.106731E+09 | 96057548.21 | 521.84 | 12-OCT-05:00 | 469.66 | 469.66 | 38.39 | 1.01 |
November | 0.408139E+09 | 0.367325E+09 | 546.04 | 24-NOV-04:00 | 491.44 | 491.44 | 38.37 | 1.16 |
December | 0.588741E+09 | 0.529867E+09 | 562.32 | 23-DEC-06:00 | 506.09 | 506.09 | 37.85 | 1.30 |
Annual Sum or Average | 0.346183E+10 | 0.311565E+10 | ||||||
Minimum of Months | 1657585.27 | 1491826.75 | 159.40 | 143.46 | 143.46 | 26.93 | 0.18 | |
Maximum of Months | 0.643712E+09 | 0.579340E+09 | 587.77 | 528.99 | 528.99 | 40.42 | 1.58 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 77187670.47 | 69468903.42 | 541.09 | 24-JAN-09:51 | 486.98 | 486.98 | 6.72 | 9.56 |
February | 42664666.10 | 38398199.49 | 299.89 | 01-FEB-09:51 | 269.90 | 269.90 | 6.72 | 7.38 |
March | 44798782.42 | 40318904.18 | 445.42 | 23-MAR-15:03 | 400.88 | 400.88 | 6.72 | 8.79 |
April | 95744921.46 | 86170429.31 | 435.43 | 13-APR-08:51 | 391.89 | 391.89 | 6.72 | 8.70 |
May | 90220721.24 | 81198649.12 | 439.95 | 18-MAY-15:03 | 395.95 | 395.95 | 6.72 | 8.74 |
June | 0.161858E+09 | 0.145672E+09 | 544.73 | 29-JUN-18:03 | 490.26 | 490.26 | 6.72 | 9.59 |
July | 0.419737E+09 | 0.377763E+09 | 1150.82 | 18-JUL-18:03 | 1035.73 | 1035.73 | 6.72 | 13.15 |
August | 0.491566E+09 | 0.442410E+09 | 1028.35 | 17-AUG-15:13 | 925.52 | 925.52 | 6.72 | 12.55 |
September | 0.290558E+09 | 0.261503E+09 | 2001.65 | 29-SEP-15:13 | 1801.49 | 1801.49 | 6.72 | 16.47 |
October | 0.332984E+09 | 0.299686E+09 | 1482.91 | 17-OCT-10:50 | 1334.62 | 1334.62 | 6.72 | 14.59 |
November | 83855998.28 | 75470398.45 | 806.99 | 19-NOV-11:00 | 726.29 | 726.29 | 6.72 | 11.34 |
December | 75949920.83 | 68354928.75 | 441.76 | 16-DEC-16:01 | 397.58 | 397.58 | 6.72 | 8.76 |
Annual Sum or Average | 0.220713E+10 | 0.198641E+10 | ||||||
Minimum of Months | 42664666.10 | 38398199.49 | 299.89 | 269.90 | 269.90 | 6.72 | 7.38 | |
Maximum of Months | 0.491566E+09 | 0.442410E+09 | 2001.65 | 1801.49 | 1801.49 | 6.72 | 16.47 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.522620E+10 | 0.470358E+10 | 2268.88 | 01-JAN-00:10 | 2041.99 | 2041.99 | 6.72 | 20.07 |
February | 0.486236E+10 | 0.437613E+10 | 2268.88 | 01-FEB-00:03 | 2041.99 | 2041.99 | 6.81 | 20.07 |
March | 0.504891E+10 | 0.454402E+10 | 2268.88 | 01-MAR-07:00 | 2041.99 | 2041.99 | 6.72 | 20.07 |
April | 0.580390E+10 | 0.522351E+10 | 2268.88 | 01-APR-00:20 | 2041.99 | 2041.99 | 6.72 | 20.07 |
May | 0.603510E+10 | 0.543159E+10 | 2268.88 | 01-MAY-00:05 | 2041.99 | 2041.99 | 7.23 | 20.07 |
June | 0.588093E+10 | 0.529284E+10 | 2268.88 | 01-JUN-00:05 | 2041.99 | 2041.99 | 6.93 | 20.07 |
July | 0.607696E+10 | 0.546927E+10 | 2268.88 | 01-JUL-00:10 | 2041.99 | 2041.99 | 7.98 | 20.07 |
August | 0.607696E+10 | 0.546927E+10 | 2268.88 | 01-AUG-00:05 | 2041.99 | 2041.99 | 8.82 | 20.07 |
September | 0.588093E+10 | 0.529284E+10 | 2268.88 | 01-SEP-00:05 | 2041.99 | 2041.99 | 7.49 | 20.07 |
October | 0.607696E+10 | 0.546927E+10 | 2268.88 | 01-OCT-00:10 | 2041.99 | 2041.99 | 8.98 | 20.07 |
November | 0.556597E+10 | 0.500937E+10 | 2268.88 | 01-NOV-00:05 | 2041.99 | 2041.99 | 7.11 | 20.07 |
December | 0.534309E+10 | 0.480878E+10 | 2268.88 | 01-DEC-00:03 | 2041.99 | 2041.99 | 6.85 | 20.07 |
Annual Sum or Average | 0.678783E+11 | 0.610905E+11 | ||||||
Minimum of Months | 0.486236E+10 | 0.437613E+10 | 2268.88 | 2041.99 | 2041.99 | 6.72 | 20.07 | |
Maximum of Months | 0.607696E+10 | 0.546927E+10 | 2268.88 | 2041.99 | 2041.99 | 8.98 | 20.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.01 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 50.20 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.81 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.54 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.73 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.66 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.28 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.86 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.54 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.33 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.93 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.44 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.81 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.28 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 38.47 | 60.00 | 39137.43 | 157985.91 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 29.37 | 60.00 | 33047.55 | 114777.01 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 38.27 | 60.00 | 41409.11 | 145961.47 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.84 | 60.00 | 18259.29 | 108312.68 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 29.70 | 29.70 | 15401.03 | 96727.15 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.79 | 60.00 | 2879.78 | 64253.74 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.03 | 27.03 | 180.90 | 26771.94 | 06-JUL-03:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 36.16 | 36.16 | 82.76 | 24722.60 | 28-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 29.24 | 29.24 | 1320.32 | 60473.10 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39.91 | 39.91 | 6305.83 | 90885.20 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 29.33 | 29.33 | 25829.52 | 104821.87 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 34.48 | 60.00 | 37716.56 | 120212.37 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 18414.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.79 | 27.03 | 82.76 | 24722.60 | ||
Maximum of Months | 0.00 | 0.00 | 39.91 | 60.00 | 41409.11 | 157985.91 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 44644.30 | 330190.06 | 14-JAN-16:01 | 10.63 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 32589.52 | 308453.58 | 01-FEB-09:51 | 10.37 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 30059.40 | 341227.97 | 23-MAR-15:03 | 10.76 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 58453.78 | 321489.97 | 11-APR-15:03 | 10.52 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57040.52 | 315028.86 | 04-MAY-15:03 | 10.45 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 96966.35 | 379428.63 | 28-JUN-15:03 | 11.21 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 175384.17 | 532078.27 | 18-JUL-18:03 | 13.03 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 195872.53 | 542005.34 | 18-AUG-15:03 | 13.15 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 130777.59 | 501577.04 | 29-SEP-15:03 | 12.67 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 140981.08 | 506514.25 | 14-OCT-15:01 | 12.73 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 49705.91 | 384220.39 | 19-NOV-09:41 | 11.27 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 49978.81 | 364313.33 | 05-DEC-09:41 | 11.03 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 89047.67 | 0.00 | ||||||
Minimum of Months | 30059.40 | 308453.58 | 10.37 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 195872.53 | 542005.34 | 13.15 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.01 | 59.50 | 24241.13 | 49013.46 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.20 | 59.77 | 24271.28 | 49031.78 | 03-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.81 | 58.55 | 24039.37 | 48773.85 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.54 | 58.69 | 23559.05 | 47893.67 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.73 | 59.44 | 22999.11 | 46865.62 | 02-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.66 | 58.62 | 22503.51 | 45719.50 | 02-JUN-06:53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.28 | 59.20 | 22173.11 | 44744.80 | 05-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.86 | 59.03 | 22161.44 | 44645.88 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.54 | 58.30 | 22406.76 | 45442.47 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.33 | 59.11 | 22869.90 | 46573.85 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.93 | 59.53 | 23433.43 | 47736.08 | 28-NOV-07:45 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.44 | 58.97 | 23932.79 | 48581.50 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 23209.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.81 | 58.30 | 22161.44 | 44645.88 | ||
Maximum of Months | 0.00 | 0.00 | 53.28 | 59.77 | 24271.28 | 49031.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.911651E+11 | 0.00 | 0.574553E+11 | 0.353135E+11 | 0.00 | 0.00 |
February | 0.706850E+11 | 0.00 | 0.319855E+11 | 0.323363E+11 | 0.00 | 0.00 |
March | 0.975794E+11 | 0.00 | 0.354940E+11 | 0.354661E+11 | 0.00 | 0.00 |
April | 0.427463E+11 | 0.00 | 0.846909E+11 | 0.354494E+11 | 0.00 | 0.00 |
May | 0.372100E+11 | 0.00 | 0.906633E+11 | 0.368926E+11 | 0.00 | 0.00 |
June | 0.674981E+10 | 0.00 | 0.167383E+12 | 0.364179E+11 | 0.00 | 0.00 |
July | 0.408235E+09 | 0.00 | 0.342462E+12 | 0.380372E+11 | 0.00 | 0.00 |
August | 0.170856E+09 | 0.00 | 0.385564E+12 | 0.382506E+11 | 0.00 | 0.00 |
September | 0.300713E+10 | 0.00 | 0.227607E+12 | 0.365331E+11 | 0.00 | 0.00 |
October | 0.152913E+11 | 0.00 | 0.258823E+12 | 0.382605E+11 | 0.00 | 0.00 |
November | 0.596707E+11 | 0.00 | 0.597894E+11 | 0.352946E+11 | 0.00 | 0.00 |
December | 0.887923E+11 | 0.00 | 0.662692E+11 | 0.357230E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.513476E+12 | 0.00 | 0.180819E+13 | 0.433975E+12 | 0.00 | 0.00 |
Minimum of Months | 0.170856E+09 | 0.00 | 0.319855E+11 | 0.323363E+11 | 0.00 | 0.00 |
Maximum of Months | 0.975794E+11 | 0.00 | 0.385564E+12 | 0.382605E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.796681E+10 | 0.00 | 0.352394E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.641444E+10 | 0.00 | 0.189694E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.857742E+10 | 0.00 | 0.213914E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.405566E+10 | 0.00 | 0.536186E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 0.360689E+10 | 0.00 | 0.568659E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 0.639403E+09 | 0.00 | 0.127689E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 37027780.10 | 0.00 | 0.285718E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 17469178.06 | 0.00 | 0.326065E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.319034E+09 | 0.00 | 0.185738E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.143387E+10 | 0.00 | 0.206208E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.564075E+10 | 0.00 | 0.354751E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.800628E+10 | 0.00 | 0.428641E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.467151E+11 | 0.00 | 0.139584E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 17469178.06 | 0.00 | 0.189694E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.857742E+10 | 0.00 | 0.326065E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.353135E+11 | 0.574553E+11 | 0.911651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323363E+11 | 0.319855E+11 | 0.706850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354661E+11 | 0.354940E+11 | 0.975794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354494E+11 | 0.846909E+11 | 0.427463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368926E+11 | 0.906633E+11 | 0.372100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.364179E+11 | 0.167383E+12 | 0.674981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.380372E+11 | 0.342462E+12 | 0.408235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.382506E+11 | 0.385564E+12 | 0.170856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365331E+11 | 0.227607E+12 | 0.300713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.382605E+11 | 0.258823E+12 | 0.152913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352946E+11 | 0.597894E+11 | 0.596707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357230E+11 | 0.662692E+11 | 0.887923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433975E+12 | 0.180819E+13 | 0.513476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323363E+11 | 0.319855E+11 | 0.170856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382605E+11 | 0.385564E+12 | 0.975794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.352394E+10 | 0.796681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.189694E+10 | 0.641444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.213914E+10 | 0.857742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.536186E+10 | 0.405566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.568659E+10 | 0.360689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.127689E+11 | 0.639403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.285718E+11 | 37027780.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.326065E+11 | 17469178.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.185738E+11 | 0.319034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.206208E+11 | 0.143387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.354751E+10 | 0.564075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.428641E+10 | 0.800628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.139584E+12 | 0.467151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.189694E+10 | 17469178.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.326065E+11 | 0.857742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.353135E+11 | 0.911651E+11 | 0.574553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323363E+11 | 0.706850E+11 | 0.319855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354661E+11 | 0.975794E+11 | 0.354940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354494E+11 | 0.427463E+11 | 0.846909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368926E+11 | 0.372100E+11 | 0.906633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.364179E+11 | 0.674981E+10 | 0.167383E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.380372E+11 | 0.408235E+09 | 0.342462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.382506E+11 | 0.170856E+09 | 0.385564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365331E+11 | 0.300713E+10 | 0.227607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.382605E+11 | 0.152913E+11 | 0.258823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352946E+11 | 0.596707E+11 | 0.597894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357230E+11 | 0.887923E+11 | 0.662692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433975E+12 | 0.513476E+12 | 0.180819E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323363E+11 | 0.170856E+09 | 0.319855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382605E+11 | 0.975794E+11 | 0.385564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.796681E+10 | 0.352394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.641444E+10 | 0.189694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.857742E+10 | 0.213914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.405566E+10 | 0.536186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.360689E+10 | 0.568659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.639403E+09 | 0.127689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 37027780.10 | 0.285718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 17469178.06 | 0.326065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.319034E+09 | 0.185738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.143387E+10 | 0.206208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.564075E+10 | 0.354751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.800628E+10 | 0.428641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.467151E+11 | 0.139584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 17469178.06 | 0.189694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.857742E+10 | 0.326065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421153E+11 | 0.00 | 0.00 | 5246928.79 | 78380407.52 | 0.00 | 0.110644E+11 | 0.00 | 1.01 |
February | 0.464412E+11 | 0.00 | 0.00 | 404992.00 | 14436957.05 | 0.00 | 0.117164E+10 | 0.00 | 1.01 |
March | 0.545738E+11 | 0.00 | 0.00 | 0.00 | 113069.93 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 0.427937E+11 | 0.00 | 0.00 | 0.00 | 79827503.14 | 0.00 | 0.00 | 0.00 | 1.01 |
May | 0.430138E+11 | 0.00 | 0.00 | 0.00 | 11391769.71 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 0.318827E+11 | 0.00 | 0.00 | 0.00 | 0.541873E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.203068E+11 | 0.00 | 0.00 | 27102.06 | 0.452752E+10 | 0.00 | 0.270936E+09 | 0.00 | 1.02 |
August | 0.161630E+11 | 0.00 | 0.00 | 308684.09 | 0.543985E+10 | 0.00 | 0.134630E+10 | 0.00 | 1.02 |
September | 0.223103E+11 | 66200130.33 | 0.00 | 4076580.82 | 0.165838E+10 | 0.00 | 0.554901E+10 | 0.00 | 1.02 |
October | 0.963986E+10 | 0.104635E+09 | 0.00 | 14961517.11 | 0.296413E+10 | 0.00 | 0.200127E+11 | 0.00 | 1.02 |
November | 0.192118E+11 | 462891.70 | 0.00 | 15521029.65 | 51999578.60 | 0.00 | 0.293036E+11 | 0.00 | 1.02 |
December | 0.371937E+11 | 0.00 | 0.00 | 7298175.47 | 29203138.68 | 0.00 | 0.149289E+11 | 0.00 | 1.01 |
Annual Sum or Average | 0.385646E+12 | 0.171298E+09 | 0.00 | 47845009.99 | 0.153971E+11 | 0.00 | 0.836474E+11 | 0.00 | 1.01 |
Minimum of Months | 0.963986E+10 | 0.00 | 0.00 | 0.00 | 113069.93 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.545738E+11 | 0.104635E+09 | 0.00 | 15521029.65 | 0.543985E+10 | 0.00 | 0.293036E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.615738E+10 | 14589162.24 | 0.00 | 2122904.15 | 464512.03 | 14223258.90 | 0.803549E+09 | 0.00 | 2.44 |
February | 0.569215E+10 | 2491599.90 | 0.00 | 1368471.04 | 0.00 | 0.00 | 0.510630E+09 | 0.00 | 2.41 |
March | 0.678358E+10 | 0.00 | 0.00 | 571853.68 | 14640.57 | 72687105.54 | 0.211730E+09 | 0.00 | 2.37 |
April | 0.542614E+10 | 4898280.87 | 0.00 | 164898.72 | 5437978.51 | 0.00 | 0.114721E+09 | 0.00 | 2.36 |
May | 0.556708E+10 | 537994.52 | 0.00 | 4766.33 | 937039.55 | 0.00 | 2448874.44 | 0.00 | 2.36 |
June | 0.412825E+10 | 0.00 | 0.00 | 0.00 | 70163018.27 | 0.00 | 0.00 | 0.00 | 2.37 |
July | 0.266230E+10 | 95751226.39 | 0.00 | 919.38 | 0.490483E+09 | 0.00 | 2157609.63 | 0.00 | 2.38 |
August | 0.223187E+10 | 0.342098E+09 | 0.00 | 67776.72 | 0.362267E+09 | 0.00 | 35247135.38 | 0.00 | 2.39 |
September | 0.326808E+10 | 0.184807E+09 | 0.00 | 874068.15 | 82648451.02 | 0.00 | 0.342387E+09 | 0.00 | 2.42 |
October | 0.324929E+10 | 0.444793E+09 | 0.00 | 1892376.94 | 94772587.72 | 0.00 | 0.585839E+09 | 0.00 | 2.54 |
November | 0.558087E+10 | 10985053.87 | 0.00 | 2283538.07 | 0.00 | 0.00 | 0.721190E+09 | 0.00 | 2.47 |
December | 0.601868E+10 | 5974592.86 | 0.00 | 3057632.03 | 0.00 | 0.00 | 0.826501E+09 | 0.00 | 2.50 |
Annual Sum or Average | 0.567657E+11 | 0.110693E+10 | 0.00 | 12409205.20 | 0.110719E+10 | 86910364.44 | 0.415640E+10 | 0.00 | 2.42 |
Minimum of Months | 0.223187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
Maximum of Months | 0.678358E+10 | 0.444793E+09 | 0.00 | 3057632.03 | 0.490483E+09 | 72687105.54 | 0.826501E+09 | 0.00 | 2.54 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.434778E+10 | 0.00 | 0.00 | 236506.81 | 7299884.36 | 0.00 | 0.603022E+09 | 0.00 | 1.47 |
February | 0.378822E+10 | 0.00 | 0.00 | 254875.47 | 1344572.20 | 0.00 | 0.647207E+09 | 0.00 | 1.47 |
March | 0.464258E+10 | 0.00 | 0.00 | 162404.23 | 10530.66 | 0.00 | 0.440671E+09 | 0.00 | 1.47 |
April | 0.304734E+10 | 0.00 | 0.00 | 503448.81 | 7434658.22 | 0.00 | 0.941689E+09 | 0.00 | 1.48 |
May | 0.322113E+10 | 0.00 | 0.00 | 422307.75 | 1060961.59 | 0.00 | 0.786819E+09 | 0.00 | 1.48 |
June | 0.195146E+10 | 38311.04 | 0.00 | 892383.72 | 50428501.13 | 0.00 | 0.102545E+10 | 0.00 | 1.48 |
July | 0.717827E+09 | 11396570.76 | 0.00 | 1705337.27 | 0.410332E+09 | 0.00 | 0.121392E+10 | 0.00 | 1.50 |
August | 0.385479E+09 | 9108881.39 | 0.00 | 2135919.31 | 0.497531E+09 | 0.00 | 0.127344E+10 | 0.00 | 1.51 |
September | 0.114221E+10 | 39800724.12 | 0.00 | 1564584.46 | 0.121011E+09 | 0.00 | 0.148103E+10 | 0.00 | 1.50 |
October | 0.133274E+10 | 94801528.25 | 0.00 | 1791991.20 | 0.191214E+09 | 0.00 | 0.145044E+10 | 0.00 | 1.50 |
November | 0.337181E+10 | 0.00 | 0.00 | 550883.35 | 4886042.04 | 0.00 | 0.109936E+10 | 0.00 | 1.47 |
December | 0.401886E+10 | 0.00 | 0.00 | 373913.40 | 2719806.42 | 0.00 | 0.832345E+09 | 0.00 | 1.47 |
Annual Sum or Average | 0.319674E+11 | 0.155146E+09 | 0.00 | 10594555.78 | 0.129527E+10 | 0.00 | 0.117954E+11 | 0.00 | 1.48 |
Minimum of Months | 0.385479E+09 | 0.00 | 0.00 | 162404.23 | 10530.66 | 0.00 | 0.440671E+09 | 0.00 | 1.47 |
Maximum of Months | 0.464258E+10 | 94801528.25 | 0.00 | 2135919.31 | 0.497531E+09 | 0.00 | 0.148103E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400030E+10 | 0.00 | 0.00 | 0.00 | 5898310.18 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.358301E+10 | 0.00 | 0.00 | 0.00 | 1086415.00 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.410680E+10 | 0.00 | 0.00 | 0.00 | 8508.78 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.322033E+10 | 0.00 | 0.00 | 0.00 | 6007207.53 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.323689E+10 | 0.00 | 0.00 | 0.00 | 857257.49 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.239925E+10 | 0.00 | 0.00 | 0.00 | 40777209.24 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.154848E+10 | 0.00 | 0.00 | 17.14 | 0.340707E+09 | 0.00 | 41142.21 | 0.00 | 0.57 |
August | 0.131726E+10 | 0.00 | 0.00 | 144.54 | 0.409362E+09 | 0.00 | 380074.25 | 0.00 | 0.57 |
September | 0.209216E+10 | 38285.43 | 0.00 | 12122.19 | 0.129741E+09 | 0.00 | 4610142.85 | 0.00 | 0.57 |
October | 0.218282E+10 | 1649592.88 | 0.00 | 40229.76 | 0.229144E+09 | 0.00 | 30515680.55 | 0.00 | 0.56 |
November | 0.361144E+10 | 0.00 | 0.00 | 0.00 | 3947924.39 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.391862E+10 | 0.00 | 0.00 | 0.00 | 2197604.93 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.352174E+11 | 1687878.31 | 0.00 | 52513.63 | 0.116973E+10 | 0.00 | 35547039.85 | 0.00 | 0.56 |
Minimum of Months | 0.131726E+10 | 0.00 | 0.00 | 0.00 | 8508.78 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.410680E+10 | 1649592.88 | 0.00 | 40229.76 | 0.409362E+09 | 0.00 | 30515680.55 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232949E+10 | 0.00 | 0.00 | 0.00 | 3434758.09 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.208649E+10 | 0.00 | 0.00 | 0.00 | 632651.15 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.239151E+10 | 0.00 | 0.00 | 0.00 | 4954.91 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.187529E+10 | 0.00 | 0.00 | 0.00 | 3498172.20 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.188494E+10 | 0.00 | 0.00 | 0.00 | 499206.04 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.139715E+10 | 0.00 | 0.00 | 0.00 | 23745758.57 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.901751E+09 | 0.00 | 0.00 | 0.00 | 0.198403E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.767300E+09 | 0.00 | 0.00 | 0.00 | 0.238383E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.122102E+10 | 0.00 | 0.00 | 0.00 | 75574034.35 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.128891E+10 | 0.00 | 0.00 | 0.00 | 0.134398E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.210305E+10 | 0.00 | 0.00 | 0.00 | 2298991.55 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.228193E+10 | 0.00 | 0.00 | 0.00 | 1279729.46 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.205288E+11 | 0.00 | 0.00 | 0.00 | 0.682153E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 0.767300E+09 | 0.00 | 0.00 | 0.00 | 4954.91 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.239151E+10 | 0.00 | 0.00 | 0.00 | 0.238383E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.450916E+09 | 0.106207E+09 | 0.00 | 96346414.43 | 0.00 | 0.00 | 0.813184E+11 | 0.00 | 23.81 |
February | 0.315408E+09 | 19562445.39 | 0.00 | 86295987.07 | 0.00 | 0.00 | 0.734374E+11 | 0.00 | 24.07 |
March | 0.323530E+09 | 153212.64 | 0.00 | 94260556.88 | 0.00 | 0.00 | 0.839335E+11 | 0.00 | 24.00 |
April | 0.203815E+09 | 0.108168E+09 | 0.00 | 0.103238E+09 | 0.00 | 0.00 | 0.665410E+11 | 0.00 | 24.10 |
May | 0.227106E+09 | 15436138.80 | 0.00 | 0.111654E+09 | 0.00 | 0.00 | 0.669133E+11 | 0.00 | 24.15 |
June | 93972404.19 | 0.741656E+09 | 0.00 | 0.112454E+09 | 170823.70 | 0.00 | 0.499215E+11 | 0.00 | 24.25 |
July | 56851767.79 | 0.627544E+10 | 0.00 | 96619896.53 | 47284843.09 | 0.00 | 0.315939E+11 | 0.00 | 24.20 |
August | 7926133.35 | 0.738018E+10 | 0.00 | 89375912.89 | 0.116692E+09 | 0.00 | 0.273065E+11 | 0.00 | 24.35 |
September | 62074037.75 | 0.239296E+10 | 0.00 | 98213015.53 | 0.00 | 0.00 | 0.433009E+11 | 0.00 | 24.31 |
October | 0.105082E+09 | 0.425679E+10 | 0.00 | 92021473.13 | 39042785.74 | 0.00 | 0.458401E+11 | 0.00 | 24.25 |
November | 0.236046E+09 | 71087986.68 | 0.00 | 96327972.03 | 0.00 | 0.00 | 0.744800E+11 | 0.00 | 24.11 |
December | 0.303457E+09 | 39914025.71 | 0.00 | 97314049.04 | 0.00 | 0.00 | 0.803130E+11 | 0.00 | 23.90 |
Annual Sum or Average | 0.238618E+10 | 0.214076E+11 | 0.00 | 0.117412E+10 | 0.203190E+09 | 0.00 | 0.724899E+12 | 0.00 | 24.13 |
Minimum of Months | 7926133.35 | 153212.64 | 0.00 | 86295987.07 | 0.00 | 0.00 | 0.273065E+11 | 0.00 | 23.81 |
Maximum of Months | 0.450916E+09 | 0.738018E+10 | 0.00 | 0.112454E+09 | 0.116692E+09 | 0.00 | 0.839335E+11 | 0.00 | 24.35 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.892136E+10 | 58006564.56 | 0.00 | 21269877.90 | 1227834.85 | 0.00 | 0.217423E+11 | 0.00 | 3.80 |
February | 0.825925E+10 | 9708483.15 | 0.00 | 16396865.57 | 0.00 | 0.00 | 0.190520E+11 | 0.00 | 3.77 |
March | 0.144723E+11 | 64441.83 | 0.00 | 11049314.63 | 0.00 | 0.00 | 0.166415E+11 | 0.00 | 3.72 |
April | 0.713990E+10 | 33504919.05 | 0.00 | 11981789.20 | 11991088.97 | 0.00 | 0.172558E+11 | 0.00 | 3.72 |
May | 0.932974E+10 | 2368032.95 | 0.00 | 8793053.03 | 4124466.82 | 0.00 | 0.151916E+11 | 0.00 | 3.71 |
June | 0.559751E+10 | 21326624.56 | 0.00 | 11941402.41 | 0.287502E+09 | 0.00 | 0.125726E+11 | 0.00 | 3.73 |
July | 0.233102E+10 | 0.138979E+10 | 0.00 | 15656559.69 | 0.119058E+10 | 0.00 | 0.941663E+10 | 0.00 | 3.75 |
August | 0.118464E+10 | 0.210221E+10 | 0.00 | 19059072.65 | 0.998115E+09 | 0.00 | 0.890215E+10 | 0.00 | 3.78 |
September | 0.232745E+10 | 0.828871E+09 | 0.00 | 21854024.64 | 0.244255E+09 | 0.00 | 0.137414E+11 | 0.00 | 3.82 |
October | 0.217645E+10 | 0.186628E+10 | 0.00 | 27080529.26 | 0.196170E+09 | 0.00 | 0.151164E+11 | 0.00 | 3.96 |
November | 0.428080E+10 | 42321662.95 | 0.00 | 25060577.70 | 0.00 | 0.00 | 0.234851E+11 | 0.00 | 3.84 |
December | 0.727817E+10 | 22551157.44 | 0.00 | 26524103.98 | 0.00 | 0.00 | 0.228762E+11 | 0.00 | 3.88 |
Annual Sum or Average | 0.732985E+11 | 0.637700E+10 | 0.00 | 0.216667E+09 | 0.293396E+10 | 0.00 | 0.195994E+12 | 0.00 | 3.79 |
Minimum of Months | 0.118464E+10 | 64441.83 | 0.00 | 8793053.03 | 0.00 | 0.00 | 0.890215E+10 | 0.00 | 3.71 |
Maximum of Months | 0.144723E+11 | 0.210221E+10 | 0.00 | 27080529.26 | 0.119058E+10 | 0.00 | 0.234851E+11 | 0.00 | 3.96 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565957E+11 | 55470310.21 | 0.00 | 26181682.83 | 95199424.51 | 0.00 | 0.458834E+11 | 0.00 | 1.81 |
February | 0.438267E+11 | 0.00 | 0.00 | 24574065.30 | 27751992.59 | 0.00 | 0.480090E+11 | 0.00 | 1.81 |
March | 0.648553E+11 | 0.00 | 0.00 | 18448160.79 | 217352.99 | 0.00 | 0.401725E+11 | 0.00 | 1.81 |
April | 0.341337E+11 | 0.00 | 0.00 | 32021792.25 | 0.153451E+09 | 0.00 | 0.484360E+11 | 0.00 | 1.82 |
May | 0.344683E+11 | 0.00 | 0.00 | 32292937.05 | 21898264.82 | 0.00 | 0.484609E+11 | 0.00 | 1.81 |
June | 0.186337E+11 | 1694671.67 | 0.00 | 48659109.87 | 0.103994E+10 | 0.00 | 0.431300E+11 | 0.00 | 1.83 |
July | 0.695060E+10 | 0.388685E+09 | 0.00 | 65496101.97 | 0.831501E+10 | 0.00 | 0.332340E+11 | 0.00 | 1.85 |
August | 0.410714E+10 | 0.638989E+09 | 0.00 | 71623479.82 | 0.981797E+10 | 0.00 | 0.305636E+11 | 0.00 | 1.86 |
September | 0.123498E+11 | 0.138828E+10 | 0.00 | 61858630.00 | 0.194774E+10 | 0.00 | 0.423512E+11 | 0.00 | 1.86 |
October | 0.101366E+11 | 0.363099E+10 | 0.00 | 69443970.68 | 0.228187E+10 | 0.00 | 0.485293E+11 | 0.00 | 1.88 |
November | 0.303230E+11 | 92969312.99 | 0.00 | 42019915.35 | 7895109.53 | 0.00 | 0.627445E+11 | 0.00 | 1.82 |
December | 0.461079E+11 | 34359896.16 | 0.00 | 33314300.06 | 21776953.55 | 0.00 | 0.545710E+11 | 0.00 | 1.81 |
Annual Sum or Average | 0.362489E+12 | 0.623144E+10 | 0.00 | 0.525934E+09 | 0.237307E+11 | 0.00 | 0.546085E+12 | 0.00 | 1.83 |
Minimum of Months | 0.410714E+10 | 0.00 | 0.00 | 18448160.79 | 217352.99 | 0.00 | 0.305636E+11 | 0.00 | 1.81 |
Maximum of Months | 0.648553E+11 | 0.363099E+10 | 0.00 | 71623479.82 | 0.981797E+10 | 0.00 | 0.627445E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10458409.05 | 3020648.21 | 7253.74 | 6153811.05 | 820164.47 | 0.680468E+09 | 0.111108E+10 | 4781.52 | 0.35 |
February | 26930338.61 | 1800872.63 | 0.00 | 5722867.71 | 0.00 | 0.463671E+09 | 0.106816E+10 | 0.00 | 0.36 |
March | 40149905.69 | 2719197.46 | 0.00 | 6023820.68 | 0.00 | 0.699394E+09 | 0.106357E+10 | 0.00 | 0.36 |
April | 14434851.13 | 6892438.62 | 0.00 | 11475873.92 | 0.00 | 79019439.54 | 0.114792E+10 | 0.00 | 0.36 |
May | 25465827.65 | 2504668.22 | 0.00 | 12120122.59 | 146263.67 | 76662085.55 | 0.114938E+10 | 0.00 | 0.36 |
June | 9494231.73 | 39879721.64 | 0.00 | 12740641.43 | 325521.35 | 1978217.20 | 0.712046E+09 | 0.00 | 0.36 |
July | 0.00 | 0.242907E+09 | 9450.39 | 11036301.05 | 0.00 | 705985.05 | 0.325241E+09 | 3833.48 | 0.36 |
August | 0.00 | 0.315013E+09 | 32250.77 | 8578878.60 | 0.00 | 673544.40 | 0.246544E+09 | 8756.74 | 0.36 |
September | 1558622.04 | 96439759.81 | 13827.58 | 11148368.51 | 3211454.92 | 1946838.39 | 0.547578E+09 | 2492.93 | 0.36 |
October | 4296604.86 | 0.185471E+09 | 64824.19 | 9107615.62 | 0.00 | 6200567.79 | 0.832063E+09 | 9345.02 | 0.36 |
November | 10514027.73 | 2905379.99 | 0.00 | 7815444.15 | 208811.05 | 0.259523E+09 | 0.125160E+10 | 0.00 | 0.35 |
December | 12247264.87 | 4849800.31 | 12124.62 | 6803086.87 | 0.00 | 0.573111E+09 | 0.117680E+10 | 1889.24 | 0.35 |
Annual Sum or Average | 0.155550E+09 | 0.904403E+09 | 139731.29 | 0.108727E+09 | 4712215.46 | 0.284335E+10 | 0.106320E+11 | 31098.94 | 0.36 |
Minimum of Months | 0.00 | 1800872.63 | 0.00 | 5722867.71 | 0.00 | 673544.40 | 0.246544E+09 | 0.00 | 0.35 |
Maximum of Months | 40149905.69 | 0.315013E+09 | 64824.19 | 12740641.43 | 3211454.92 | 0.699394E+09 | 0.125160E+10 | 9345.02 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119086E+09 | 1499441.95 | 18747.85 | 2387936.57 | 2324848.25 | 0.105772E+10 | 0.628750E+09 | 9358.48 | 0.35 |
February | 0.104722E+09 | 733363.93 | 502.19 | 2849482.66 | 1063177.57 | 0.696739E+09 | 0.759996E+09 | 3617.94 | 0.36 |
March | 0.102064E+09 | 624422.56 | 0.00 | 3485629.57 | 2094456.31 | 0.838498E+09 | 0.864876E+09 | 0.00 | 0.36 |
April | 0.155633E+09 | 4442281.63 | 6708.78 | 7571465.01 | 2442568.16 | 91707199.52 | 0.997790E+09 | 72.50 | 0.36 |
May | 0.222094E+09 | 2322560.36 | 0.00 | 9247347.68 | 328060.93 | 60645677.22 | 0.971496E+09 | 0.00 | 0.36 |
June | 0.296454E+09 | 32402531.40 | 41926.66 | 8563793.49 | 7745671.47 | 1210685.03 | 0.429945E+09 | 10402.83 | 0.36 |
July | 0.216132E+09 | 0.204553E+09 | 94475.77 | 6581758.19 | 38237709.02 | 115050.01 | 0.114116E+09 | 6796.99 | 0.36 |
August | 0.173227E+09 | 0.261448E+09 | 115646.41 | 4356416.27 | 53445513.79 | 158207.86 | 78024116.21 | 7718.49 | 0.36 |
September | 0.231075E+09 | 82990522.65 | 159034.76 | 6262511.41 | 16497633.36 | 1347947.71 | 0.323480E+09 | 8666.96 | 0.36 |
October | 0.230077E+09 | 0.152799E+09 | 169308.92 | 4479032.72 | 32532222.48 | 18605072.27 | 0.598407E+09 | 22382.91 | 0.36 |
November | 0.156985E+09 | 2497736.80 | 15232.77 | 3468424.39 | 596938.85 | 0.501880E+09 | 0.866939E+09 | 3917.74 | 0.35 |
December | 0.130703E+09 | 3528164.63 | 46143.95 | 2475633.28 | 1276405.56 | 0.979702E+09 | 0.655878E+09 | 12530.16 | 0.35 |
Annual Sum or Average | 0.213825E+10 | 0.749841E+09 | 667728.05 | 61729431.22 | 0.158585E+09 | 0.424833E+10 | 0.728970E+10 | 85465.01 | 0.36 |
Minimum of Months | 0.102064E+09 | 624422.56 | 0.00 | 2387936.57 | 328060.93 | 115050.01 | 78024116.21 | 0.00 | 0.35 |
Maximum of Months | 0.296454E+09 | 0.261448E+09 | 169308.92 | 9247347.68 | 53445513.79 | 0.105772E+10 | 0.997790E+09 | 22382.91 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92976593.22 | 3390967.17 | 0.00 | 4122878.92 | 0.00 | 0.00 | 0.917780E+09 | 0.00 | 0.02 |
February | 0.380047E+09 | 0.00 | 0.00 | 2448110.37 | 0.00 | 0.00 | 0.683736E+09 | 0.00 | 0.02 |
March | 0.541475E+09 | 6138837.43 | 0.00 | 1718109.60 | 0.00 | 0.00 | 0.590055E+09 | 0.00 | 0.02 |
April | 0.172278E+09 | 908187.16 | 0.00 | 1848996.07 | 0.00 | 0.00 | 0.606610E+09 | 0.00 | 0.02 |
May | 0.661773E+09 | 0.00 | 0.00 | 374616.15 | 0.00 | 0.00 | 0.215663E+09 | 0.00 | 0.02 |
June | 0.412962E+09 | 9190813.15 | 0.00 | 209213.33 | 1255053.89 | 0.00 | 0.136762E+09 | 0.00 | 0.02 |
July | 66272453.97 | 0.299933E+09 | 0.00 | 181120.51 | 931979.74 | 0.00 | 82032037.77 | 0.00 | 0.02 |
August | 0.00 | 0.462868E+09 | 0.00 | 235353.43 | 0.00 | 0.00 | 27123847.28 | 0.00 | 0.02 |
September | 0.00 | 0.156896E+09 | 0.00 | 1669659.79 | 0.00 | 0.00 | 0.168918E+09 | 0.00 | 0.02 |
October | 46454037.84 | 0.210034E+09 | 0.00 | 2423197.28 | 0.00 | 0.00 | 0.290968E+09 | 0.00 | 0.02 |
November | 40637701.65 | 178793.01 | 0.00 | 3790513.72 | 0.00 | 0.00 | 0.893527E+09 | 0.00 | 0.02 |
December | 0.101886E+09 | 133776.38 | 0.00 | 4379937.97 | 0.00 | 0.00 | 0.927711E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.251676E+10 | 0.114967E+10 | 0.00 | 23401707.16 | 2187033.63 | 0.00 | 0.554089E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 181120.51 | 0.00 | 0.00 | 27123847.28 | 0.00 | 0.02 |
Maximum of Months | 0.661773E+09 | 0.462868E+09 | 0.00 | 4379937.97 | 1255053.89 | 0.00 | 0.927711E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161622E+10 | 15718529.17 | 342731.73 | 50596248.34 | 36175160.83 | 0.605191E+09 | 0.222517E+11 | 19026.13 | 0.40 |
February | 0.141233E+10 | 8684381.98 | 41388.37 | 53557652.86 | 15684625.80 | 0.119205E+09 | 0.196338E+11 | 14498.72 | 0.40 |
March | 0.139541E+10 | 8160749.10 | 302650.89 | 62925872.97 | 28410043.36 | 0.367467E+09 | 0.227111E+11 | 6517.40 | 0.40 |
April | 0.213155E+10 | 40905603.55 | 394140.40 | 89263734.28 | 52148680.24 | 35398571.15 | 0.147359E+11 | 32417.02 | 0.40 |
May | 0.307488E+10 | 13317356.73 | 0.00 | 0.112796E+09 | 22636731.02 | 24325047.02 | 0.139264E+11 | 0.00 | 0.40 |
June | 0.408591E+10 | 0.309775E+09 | 56636.33 | 0.108608E+09 | 0.235463E+09 | 8925136.53 | 0.578230E+10 | 1636.60 | 0.41 |
July | 0.294061E+10 | 0.229265E+10 | 908885.32 | 80434888.44 | 0.100112E+10 | 2097031.50 | 0.154730E+10 | 9181.24 | 0.41 |
August | 0.234972E+10 | 0.289289E+10 | 3407804.24 | 53117628.15 | 0.137670E+10 | 2682389.88 | 0.106379E+10 | 17920.73 | 0.41 |
September | 0.316714E+10 | 0.910939E+09 | 690822.81 | 71845908.68 | 0.440104E+09 | 12371336.03 | 0.437409E+10 | 37937.34 | 0.41 |
October | 0.313454E+10 | 0.177080E+10 | 3489801.69 | 61717683.23 | 0.742119E+09 | 13186113.85 | 0.834157E+10 | 99958.92 | 0.40 |
November | 0.214239E+10 | 21761079.60 | 293624.85 | 59506802.63 | 20164600.19 | 83810165.49 | 0.184580E+11 | 17879.29 | 0.40 |
December | 0.177865E+10 | 45214469.85 | 603344.90 | 50054640.31 | 20065343.45 | 0.126622E+09 | 0.220368E+11 | 83833.28 | 0.40 |
Annual Sum or Average | 0.292294E+11 | 0.833081E+10 | 10531831.51 | 0.854425E+09 | 0.399079E+10 | 0.140128E+10 | 0.154863E+12 | 340806.67 | 0.40 |
Minimum of Months | 0.139541E+10 | 8160749.10 | 0.00 | 50054640.31 | 15684625.80 | 2097031.50 | 0.106379E+10 | 0.00 | 0.40 |
Maximum of Months | 0.408591E+10 | 0.289289E+10 | 3489801.69 | 0.112796E+09 | 0.137670E+10 | 0.605191E+09 | 0.227111E+11 | 99958.92 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12947603.48 | 3017205.38 | 10091.71 | 7348609.68 | 820164.47 | 0.666287E+09 | 0.112158E+10 | 5386.38 | 0.35 |
February | 29041146.78 | 1800032.98 | 748.49 | 5761183.58 | 0.00 | 0.518346E+09 | 0.101134E+10 | 91.16 | 0.36 |
March | 40732040.48 | 2719197.46 | 0.00 | 6233031.86 | 0.00 | 0.705167E+09 | 0.105700E+10 | 0.00 | 0.36 |
April | 10521568.21 | 6892438.62 | 0.00 | 10585064.79 | 0.00 | 0.120949E+09 | 0.111079E+10 | 0.00 | 0.36 |
May | 21272242.37 | 2650931.89 | 0.00 | 10973054.66 | 0.00 | 0.112968E+09 | 0.111842E+10 | 0.00 | 0.36 |
June | 8919292.78 | 40205242.99 | 0.00 | 11423038.96 | 0.00 | 5859546.34 | 0.710057E+09 | 0.00 | 0.36 |
July | 0.00 | 0.242921E+09 | 0.00 | 10437146.93 | 0.00 | 421608.53 | 0.326125E+09 | 0.00 | 0.36 |
August | 0.00 | 0.315054E+09 | 0.00 | 8573274.35 | 0.00 | 370805.39 | 0.246852E+09 | 0.00 | 0.36 |
September | 1558622.04 | 96238689.56 | 14644.71 | 9934236.94 | 3412525.16 | 1779143.38 | 0.548960E+09 | 1675.80 | 0.36 |
October | 4856059.48 | 0.184377E+09 | 0.00 | 9353783.99 | 1167735.58 | 15261485.81 | 0.822196E+09 | 0.00 | 0.36 |
November | 13661439.67 | 2819173.74 | 0.00 | 8176345.22 | 295017.30 | 0.312589E+09 | 0.119503E+10 | 0.00 | 0.35 |
December | 14870589.28 | 4849800.31 | 10080.92 | 7583583.10 | 0.00 | 0.600758E+09 | 0.114575E+10 | 3932.94 | 0.35 |
Annual Sum or Average | 0.158381E+09 | 0.903544E+09 | 35565.83 | 0.106382E+09 | 5695442.51 | 0.306076E+10 | 0.104141E+11 | 11086.29 | 0.36 |
Minimum of Months | 0.00 | 1800032.98 | 0.00 | 5761183.58 | 0.00 | 370805.39 | 0.246852E+09 | 0.00 | 0.35 |
Maximum of Months | 40732040.48 | 0.315054E+09 | 14644.71 | 11423038.96 | 3412525.16 | 0.705167E+09 | 0.119503E+10 | 5386.38 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119100E+09 | 1170426.45 | 22682.97 | 2866599.51 | 2653863.74 | 0.102390E+10 | 0.662081E+09 | 5423.36 | 0.35 |
February | 0.104120E+09 | 719276.51 | 12734.69 | 2801712.75 | 1063177.57 | 0.806774E+09 | 0.650610E+09 | 5472.86 | 0.36 |
March | 0.102050E+09 | 960940.21 | 0.00 | 3713585.13 | 1757938.66 | 0.873740E+09 | 0.829420E+09 | 0.00 | 0.36 |
April | 0.153376E+09 | 6178633.44 | 22134.40 | 7383002.43 | 690734.42 | 0.149112E+09 | 0.942830E+09 | 128.82 | 0.36 |
May | 0.219397E+09 | 2618602.73 | 0.00 | 8874162.05 | 32018.57 | 0.106674E+09 | 0.928538E+09 | 0.00 | 0.36 |
June | 0.295590E+09 | 32659239.73 | 0.00 | 7387858.85 | 7541292.63 | 1555475.81 | 0.431639E+09 | 0.00 | 0.36 |
July | 0.214715E+09 | 0.206625E+09 | 0.00 | 5611946.67 | 36267374.16 | 470477.82 | 0.116147E+09 | 0.00 | 0.36 |
August | 0.172999E+09 | 0.265084E+09 | 0.00 | 3773767.87 | 49932769.52 | 330755.39 | 78662693.39 | 0.00 | 0.36 |
September | 0.231307E+09 | 82363637.61 | 123080.81 | 5380847.72 | 17166198.49 | 1478439.69 | 0.324000E+09 | 2940.81 | 0.36 |
October | 0.230061E+09 | 0.154507E+09 | 162417.19 | 4772814.43 | 30847815.38 | 48017148.16 | 0.568717E+09 | 5630.33 | 0.36 |
November | 0.158507E+09 | 2199160.51 | 14210.12 | 3635148.76 | 894039.68 | 0.560628E+09 | 0.806504E+09 | 6415.85 | 0.35 |
December | 0.131025E+09 | 3390666.88 | 55466.89 | 2679871.22 | 1410867.66 | 0.960057E+09 | 0.674997E+09 | 6242.87 | 0.35 |
Annual Sum or Average | 0.213225E+10 | 0.758477E+09 | 412727.08 | 58881317.39 | 0.150258E+09 | 0.453274E+10 | 0.701414E+10 | 32254.89 | 0.36 |
Minimum of Months | 0.102050E+09 | 719276.51 | 0.00 | 2679871.22 | 32018.57 | 330755.39 | 78662693.39 | 0.00 | 0.35 |
Maximum of Months | 0.295590E+09 | 0.265084E+09 | 162417.19 | 8874162.05 | 49932769.52 | 0.102390E+10 | 0.942830E+09 | 6415.85 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312817E+11 | 0.00 | 0.00 | 0.00 | 46123798.11 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.280185E+11 | 0.00 | 0.00 | 0.00 | 8495583.44 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.321145E+11 | 0.00 | 0.00 | 0.00 | 66537.22 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.251824E+11 | 0.00 | 0.00 | 0.00 | 46975357.17 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.253120E+11 | 0.00 | 0.00 | 0.00 | 6703610.03 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.187617E+11 | 0.00 | 0.00 | 0.00 | 0.318871E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.121092E+11 | 0.00 | 0.00 | 0.00 | 0.266427E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.103037E+11 | 0.00 | 0.00 | 0.00 | 0.320114E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.163965E+11 | 0.00 | 0.00 | 0.00 | 0.101485E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.173082E+11 | 0.00 | 0.00 | 0.00 | 0.180477E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.282409E+11 | 0.00 | 0.00 | 0.00 | 30872107.78 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.306429E+11 | 0.00 | 0.00 | 0.00 | 17184902.65 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.275672E+12 | 0.00 | 0.00 | 0.00 | 0.916032E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 0.103037E+11 | 0.00 | 0.00 | 0.00 | 66537.22 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.321145E+11 | 0.00 | 0.00 | 0.00 | 0.320114E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2815422.62 | 756868.30 | 22.10 | 1263684.94 | 205041.12 | 0.254683E+09 | 0.193278E+09 | 1280.46 | 0.35 |
February | 6697042.87 | 450218.16 | 0.00 | 1202142.62 | 0.00 | 0.212381E+09 | 0.170842E+09 | 0.00 | 0.36 |
March | 9670474.41 | 679799.36 | 0.00 | 1362639.96 | 0.00 | 0.252537E+09 | 0.188714E+09 | 0.00 | 0.36 |
April | 3186585.27 | 1723109.66 | 0.00 | 2749796.45 | 0.00 | 65056996.60 | 0.242219E+09 | 0.00 | 0.36 |
May | 5181270.93 | 662732.97 | 0.00 | 2902841.69 | 0.00 | 58693947.81 | 0.249130E+09 | 0.00 | 0.36 |
June | 2044024.41 | 10048742.18 | 0.00 | 3058245.62 | 2568.57 | 6089367.26 | 0.172873E+09 | 0.00 | 0.36 |
July | 0.00 | 60726834.72 | 2637.21 | 2672780.26 | 0.00 | 194341.80 | 81378770.06 | 683.76 | 0.36 |
August | 0.00 | 78754339.36 | 7152.65 | 2018323.35 | 0.00 | 175093.11 | 61755580.53 | 1946.77 | 0.36 |
September | 389655.51 | 24448210.39 | 4972.18 | 2550386.91 | 462787.37 | 1159788.83 | 0.136458E+09 | 913.88 | 0.36 |
October | 1436623.25 | 46347247.00 | 36272.27 | 1933472.76 | 0.00 | 34051078.77 | 0.175496E+09 | 2658.63 | 0.36 |
November | 2752756.41 | 704793.43 | 0.00 | 1590746.11 | 73754.33 | 0.156403E+09 | 0.221617E+09 | 0.00 | 0.35 |
December | 3239020.50 | 1212450.08 | 3142.44 | 1386386.57 | 0.00 | 0.240027E+09 | 0.197589E+09 | 361.02 | 0.35 |
Annual Sum or Average | 37412876.18 | 0.226515E+09 | 54198.86 | 24691447.22 | 744151.38 | 0.128145E+10 | 0.209135E+10 | 7844.52 | 0.36 |
Minimum of Months | 0.00 | 450218.16 | 0.00 | 1202142.62 | 0.00 | 175093.11 | 61755580.53 | 0.00 | 0.35 |
Maximum of Months | 9670474.41 | 78754339.36 | 36272.27 | 3058245.62 | 462787.37 | 0.254683E+09 | 0.249130E+09 | 2658.63 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29878438.70 | 374860.49 | 5056.33 | 429743.06 | 581212.06 | 0.356088E+09 | 65591215.65 | 1970.25 | 0.35 |
February | 26082087.41 | 183340.98 | 606.05 | 548393.34 | 265794.39 | 0.269070E+09 | 95376157.00 | 423.98 | 0.36 |
March | 25438269.87 | 156105.64 | 0.00 | 751721.92 | 523614.08 | 0.299264E+09 | 0.126777E+09 | 0.00 | 0.36 |
April | 38330209.82 | 1438376.53 | 0.00 | 1805295.74 | 284531.24 | 65833715.59 | 0.207206E+09 | 0.00 | 0.36 |
May | 54048125.22 | 654650.68 | 0.00 | 2271587.96 | 8004.64 | 42764251.45 | 0.216787E+09 | 0.00 | 0.36 |
June | 73802470.36 | 8145863.42 | 6886.27 | 2168831.96 | 1896684.74 | 3177620.77 | 0.104894E+09 | 698.65 | 0.36 |
July | 54032898.14 | 51146576.06 | 15617.64 | 1705246.63 | 9559427.25 | 38173.95 | 28459702.76 | 1419.31 | 0.36 |
August | 43306819.34 | 65388661.79 | 23902.07 | 1086050.15 | 13340405.96 | 28230.40 | 19520404.53 | 1240.68 | 0.36 |
September | 57510138.95 | 21067723.84 | 29296.85 | 1419256.14 | 3814486.71 | 1115775.50 | 80496295.54 | 2457.03 | 0.36 |
October | 57600315.28 | 38259935.04 | 28130.62 | 863849.75 | 8088203.37 | 44419381.30 | 0.110008E+09 | 4474.05 | 0.36 |
November | 39318654.09 | 624434.20 | 4016.02 | 599162.61 | 149234.71 | 0.224706E+09 | 0.117695E+09 | 771.60 | 0.35 |
December | 32686164.74 | 874443.18 | 6692.84 | 428216.54 | 332446.01 | 0.332716E+09 | 76358810.24 | 2229.05 | 0.35 |
Annual Sum or Average | 0.532035E+09 | 0.188315E+09 | 120204.70 | 14077355.81 | 38844045.17 | 0.163922E+10 | 0.124917E+10 | 15684.60 | 0.36 |
Minimum of Months | 25438269.87 | 156105.64 | 0.00 | 428216.54 | 8004.64 | 28230.40 | 19520404.53 | 0.00 | 0.35 |
Maximum of Months | 73802470.36 | 65388661.79 | 29296.85 | 2271587.96 | 13340405.96 | 0.356088E+09 | 0.216787E+09 | 4474.05 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7696078.33 | 6179776.82 | 6411.73 | 18252941.76 | 0.00 | 0.384141E+09 | 0.249404E+10 | 1956.59 | 0.40 |
February | 33027960.20 | 2892421.76 | 0.00 | 13178600.57 | 0.00 | 0.301281E+09 | 0.216527E+10 | 0.00 | 0.40 |
March | 47214523.62 | 4367363.77 | 0.00 | 11743348.87 | 0.00 | 0.719083E+09 | 0.212765E+10 | 0.00 | 0.40 |
April | 13242020.89 | 11070099.62 | 0.00 | 14802360.25 | 0.00 | 0.105930E+09 | 0.187825E+10 | 0.00 | 0.40 |
May | 32239565.61 | 4257720.92 | 0.00 | 12275464.02 | 0.00 | 0.195585E+09 | 0.178945E+10 | 0.00 | 0.40 |
June | 13795877.13 | 64290023.58 | 0.00 | 12452444.25 | 284515.20 | 4332843.24 | 0.115194E+10 | 0.00 | 0.40 |
July | 0.00 | 0.390160E+09 | 0.00 | 11305665.91 | 0.00 | 1862136.88 | 0.528069E+09 | 0.00 | 0.40 |
August | 0.00 | 0.506015E+09 | 0.00 | 10147585.88 | 0.00 | 1106308.90 | 0.399586E+09 | 0.00 | 0.41 |
September | 2503337.67 | 0.155976E+09 | 24046.17 | 14841741.69 | 4075639.96 | 2914979.51 | 0.882753E+09 | 2166.58 | 0.41 |
October | 2833566.73 | 0.297756E+09 | 21399.54 | 15471691.11 | 227949.46 | 5423341.49 | 0.134415E+10 | 2192.06 | 0.40 |
November | 3192930.66 | 5001771.78 | 0.00 | 18627077.48 | 0.00 | 30175272.48 | 0.240449E+10 | 0.00 | 0.40 |
December | 9070793.89 | 7811880.57 | 0.00 | 19213753.83 | 0.00 | 0.202518E+09 | 0.261037E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.164817E+09 | 0.145578E+10 | 51857.43 | 0.172313E+09 | 4588104.61 | 0.195435E+10 | 0.197760E+11 | 6315.23 | 0.40 |
Minimum of Months | 0.00 | 2892421.76 | 0.00 | 10147585.88 | 0.00 | 1106308.90 | 0.399586E+09 | 0.00 | 0.40 |
Maximum of Months | 47214523.62 | 0.506015E+09 | 24046.17 | 19213753.83 | 4075639.96 | 0.719083E+09 | 0.261037E+10 | 2192.06 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227588E+10 | 67394372.63 | 0.00 | 56804710.25 | 957047.68 | 0.00 | 0.486873E+11 | 0.00 | 4.57 |
February | 0.104197E+10 | 11750241.31 | 0.00 | 55361776.73 | 839260.61 | 0.00 | 0.460208E+11 | 0.00 | 4.69 |
March | 0.163995E+10 | 0.00 | 0.00 | 61347983.11 | 98600.70 | 0.00 | 0.516372E+11 | 0.00 | 4.65 |
April | 0.310629E+09 | 68292650.19 | 0.00 | 76474993.45 | 1347075.48 | 0.00 | 0.444025E+11 | 0.00 | 4.87 |
May | 0.188897E+09 | 9711519.44 | 0.00 | 83919359.88 | 222478.85 | 0.00 | 0.453882E+11 | 0.00 | 4.93 |
June | 49780886.71 | 0.480643E+09 | 0.00 | 90024737.77 | 189492.01 | 0.00 | 0.354000E+11 | 0.00 | 5.11 |
July | 4307652.74 | 0.411686E+10 | 0.00 | 82247054.61 | 6728907.87 | 0.00 | 0.237539E+11 | 0.00 | 5.20 |
August | 29169008.91 | 0.484470E+10 | 0.00 | 71914634.76 | 26876190.23 | 0.00 | 0.204571E+11 | 0.00 | 5.20 |
September | 0.110620E+09 | 0.157235E+10 | 0.00 | 77274134.23 | 12247706.24 | 0.00 | 0.303746E+11 | 0.00 | 5.08 |
October | 0.110355E+09 | 0.276365E+10 | 0.00 | 70606314.75 | 16560031.71 | 0.00 | 0.318633E+11 | 0.00 | 5.04 |
November | 0.666442E+09 | 46440091.20 | 0.00 | 62760752.78 | 55648.02 | 0.00 | 0.476382E+11 | 0.00 | 4.73 |
December | 0.120890E+10 | 23100080.90 | 0.00 | 59185362.14 | 2366017.61 | 0.00 | 0.492771E+11 | 0.00 | 4.60 |
Annual Sum or Average | 0.763691E+10 | 0.140049E+11 | 0.00 | 0.847922E+09 | 68488457.02 | 0.00 | 0.474900E+12 | 0.00 | 4.89 |
Minimum of Months | 4307652.74 | 0.00 | 0.00 | 55361776.73 | 55648.02 | 0.00 | 0.204571E+11 | 0.00 | 4.57 |
Maximum of Months | 0.227588E+10 | 0.484470E+10 | 0.00 | 90024737.77 | 26876190.23 | 0.00 | 0.516372E+11 | 0.00 | 5.20 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111030E+10 | 71959137.64 | 0.00 | 72454689.44 | 0.00 | 0.00 | 0.540288E+11 | 0.00 | 4.93 |
February | 0.178635E+09 | 13181827.19 | 0.00 | 69985606.59 | 19052.90 | 0.00 | 0.510162E+11 | 0.00 | 5.08 |
March | 0.482468E+09 | 103389.00 | 0.00 | 77555244.35 | 0.00 | 0.00 | 0.573301E+11 | 0.00 | 5.03 |
April | 4354161.85 | 73530715.98 | 0.00 | 91996335.17 | 0.00 | 0.00 | 0.486500E+11 | 0.00 | 5.28 |
May | 2342761.74 | 10500500.16 | 0.00 | 0.100041E+09 | 0.00 | 0.00 | 0.495997E+11 | 0.00 | 5.35 |
June | 0.00 | 0.509907E+09 | 0.00 | 0.103795E+09 | 0.00 | 0.00 | 0.383607E+11 | 0.00 | 5.53 |
July | 0.00 | 0.443657E+10 | 0.00 | 91968394.51 | 0.00 | 0.00 | 0.255277E+11 | 0.00 | 5.60 |
August | 0.00 | 0.521131E+10 | 0.00 | 79669872.43 | 0.00 | 0.00 | 0.219584E+11 | 0.00 | 5.58 |
September | 7734953.39 | 0.169251E+10 | 0.00 | 88782860.17 | 0.00 | 0.00 | 0.328889E+11 | 0.00 | 5.47 |
October | 21997417.45 | 0.296635E+10 | 0.00 | 80760989.79 | 1141040.76 | 0.00 | 0.344766E+11 | 0.00 | 5.42 |
November | 0.101071E+09 | 49279814.50 | 0.00 | 78056367.65 | 0.00 | 0.00 | 0.523711E+11 | 0.00 | 5.12 |
December | 0.359101E+09 | 26358842.19 | 0.00 | 75205688.36 | 344164.32 | 0.00 | 0.543594E+11 | 0.00 | 4.97 |
Annual Sum or Average | 0.226801E+10 | 0.150616E+11 | 0.00 | 0.101027E+10 | 1504257.99 | 0.00 | 0.520568E+12 | 0.00 | 5.28 |
Minimum of Months | 0.00 | 103389.00 | 0.00 | 69985606.59 | 0.00 | 0.00 | 0.219584E+11 | 0.00 | 4.93 |
Maximum of Months | 0.111030E+10 | 0.521131E+10 | 0.00 | 0.103795E+09 | 1141040.76 | 0.00 | 0.573301E+11 | 0.00 | 5.60 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.130649E+09 | 0.00 | 0.123252E+09 | 0.00 | 0.00 | 0.692093E+11 | 0.00 | 21.64 |
February | 0.00 | 24149364.41 | 0.00 | 0.111535E+09 | 0.00 | 0.00 | 0.638887E+11 | 0.00 | 21.94 |
March | 17900950.42 | 189269.94 | 0.00 | 0.122375E+09 | 0.00 | 0.00 | 0.722392E+11 | 0.00 | 21.82 |
April | 0.00 | 0.133563E+09 | 0.00 | 0.136428E+09 | 0.00 | 0.00 | 0.573296E+11 | 0.00 | 22.35 |
May | 0.00 | 19015326.86 | 0.00 | 0.144179E+09 | 0.00 | 0.00 | 0.576476E+11 | 0.00 | 22.38 |
June | 0.00 | 0.906085E+09 | 0.00 | 0.141437E+09 | 0.00 | 0.00 | 0.424114E+11 | 0.00 | 22.61 |
July | 0.00 | 0.757310E+10 | 0.00 | 0.114639E+09 | 0.00 | 0.00 | 0.262630E+11 | 0.00 | 22.74 |
August | 0.00 | 0.909995E+10 | 0.00 | 95919381.50 | 0.00 | 0.00 | 0.220258E+11 | 0.00 | 22.79 |
September | 0.00 | 0.285332E+10 | 0.00 | 0.123292E+09 | 0.00 | 0.00 | 0.369075E+11 | 0.00 | 22.65 |
October | 0.00 | 0.506596E+10 | 0.00 | 0.110664E+09 | 0.00 | 0.00 | 0.383761E+11 | 0.00 | 22.50 |
November | 4355587.02 | 87531417.32 | 0.00 | 0.123062E+09 | 0.00 | 0.00 | 0.641993E+11 | 0.00 | 22.09 |
December | 8863266.20 | 48766783.69 | 0.00 | 0.124700E+09 | 0.00 | 0.00 | 0.683173E+11 | 0.00 | 21.77 |
Annual Sum or Average | 31119803.64 | 0.259423E+11 | 0.00 | 0.147148E+10 | 0.00 | 0.00 | 0.618815E+12 | 0.00 | 22.27 |
Minimum of Months | 0.00 | 189269.94 | 0.00 | 95919381.50 | 0.00 | 0.00 | 0.220258E+11 | 0.00 | 21.64 |
Maximum of Months | 17900950.42 | 0.909995E+10 | 0.00 | 0.144179E+09 | 0.00 | 0.00 | 0.722392E+11 | 0.00 | 22.79 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154634E+11 | 0.00 | 0.00 | 0.00 | 22800295.76 | 0.00 | 0.00 | 0.00 | 1.12 |
February | 0.138504E+11 | 0.00 | 0.00 | 0.00 | 4199606.78 | 0.00 | 0.00 | 0.00 | 1.12 |
March | 0.158751E+11 | 0.00 | 0.00 | 0.00 | 32891.23 | 0.00 | 0.00 | 0.00 | 1.12 |
April | 0.124484E+11 | 0.00 | 0.00 | 0.00 | 23221245.45 | 0.00 | 0.00 | 0.00 | 1.12 |
May | 0.125124E+11 | 0.00 | 0.00 | 0.00 | 3313783.72 | 0.00 | 0.00 | 0.00 | 1.12 |
June | 0.927444E+10 | 0.00 | 0.00 | 0.00 | 0.157627E+09 | 0.00 | 0.00 | 0.00 | 1.13 |
July | 0.598592E+10 | 14229089.23 | 0.00 | 0.00 | 0.130279E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
August | 0.509330E+10 | 0.132006E+09 | 0.00 | 168.98 | 0.145041E+10 | 0.00 | 122389.06 | 0.00 | 1.14 |
September | 0.808474E+10 | 0.173446E+09 | 0.00 | 30027.49 | 0.334560E+09 | 0.00 | 20478599.27 | 0.00 | 1.14 |
October | 0.845091E+10 | 0.368871E+09 | 0.00 | 50263.70 | 0.528023E+09 | 0.00 | 0.104974E+09 | 0.00 | 1.13 |
November | 0.139603E+11 | 0.00 | 0.00 | 0.00 | 15260954.58 | 0.00 | 0.00 | 0.00 | 1.12 |
December | 0.151477E+11 | 0.00 | 0.00 | 0.00 | 8494982.61 | 0.00 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.136147E+12 | 0.688552E+09 | 0.00 | 80460.17 | 0.385073E+10 | 0.00 | 0.125575E+09 | 0.00 | 1.13 |
Minimum of Months | 0.509330E+10 | 0.00 | 0.00 | 0.00 | 32891.23 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 0.158751E+11 | 0.368871E+09 | 0.00 | 50263.70 | 0.145041E+10 | 0.00 | 0.104974E+09 | 0.00 | 1.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:08
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.159879E+12 | 0.926958E+10 | 0.124587E+12 | 0.501297E+12 | 0.227234E+12 |
February | 0.208952E+12 | 0.825444E+10 | 0.115754E+12 | 0.453431E+12 | 0.166386E+12 |
March | 0.298001E+12 | 0.941881E+10 | 0.131931E+12 | 0.517344E+12 | 0.181949E+12 |
April | 0.387319E+12 | 0.745615E+10 | 0.101958E+12 | 0.409467E+12 | 0.249655E+12 |
May | 0.415715E+12 | 0.771822E+10 | 0.103179E+12 | 0.414044E+12 | 0.249392E+12 |
June | 0.410209E+12 | 0.565479E+10 | 0.757929E+11 | 0.299481E+12 | 0.356620E+12 |
July | 0.434624E+12 | 0.254398E+10 | 0.361532E+11 | 0.148681E+12 | 0.628252E+12 |
August | 0.394796E+12 | 0.176798E+10 | 0.260111E+11 | 0.110251E+12 | 0.695472E+12 |
September | 0.310420E+12 | 0.452170E+10 | 0.615616E+11 | 0.245510E+12 | 0.464178E+12 |
October | 0.211379E+12 | 0.473147E+10 | 0.587890E+11 | 0.254598E+12 | 0.521148E+12 |
November | 0.176379E+12 | 0.837512E+10 | 0.111840E+12 | 0.459273E+12 | 0.227846E+12 |
December | 0.140089E+12 | 0.917089E+10 | 0.121498E+12 | 0.494497E+12 | 0.247134E+12 |
Annual Sum or Average | 0.354776E+13 | 0.788831E+11 | 0.106905E+13 | 0.430788E+13 | 0.421527E+13 |
Minimum of Months | 0.140089E+12 | 0.176798E+10 | 0.260111E+11 | 0.110251E+12 | 0.166386E+12 |
Maximum of Months | 0.434624E+12 | 0.941881E+10 | 0.131931E+12 | 0.517344E+12 | 0.695472E+12 |