Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:46:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11906.91 | 1049.50 | 1049.50 |
Net Site Energy | 11906.91 | 1049.50 | 1049.50 |
Total Source Energy | 28659.49 | 2526.11 | 2526.11 |
Net Source Energy | 28659.49 | 2526.11 | 2526.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 584.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 114.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 295.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2524.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7562.36 | 4344.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 584.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 114.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 295.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2524.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 35.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 31.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 584.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 114.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 295.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2524.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 346.23 | 225.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.18 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 666.56 | 382.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 346.23 | 225.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.18 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 666.56 | 382.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7562.359 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7562.359 | 100.00 |
Total On-Site and Utility Electric Sources | 7562.359 | 100.00 |
Total Electricity End Uses | 7562.359 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2555.85 | 88.90 |
Air to Air Heat Recovery for Heating | 319.26 | 11.10 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2875.11 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 63.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7914.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JUN-19:19 | 10-FEB-18:10 | - | - | - | - | - | - | - | - | - | - | 06-FEB-21:40 |
Heating | 0.00 | 1185.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 268074.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31553.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40110.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5057.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3976.35 | 242354.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 523992.11 | 347787.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1185.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 268074.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 40110.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5057.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3976.35 | 242354.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 34.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9937.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2481.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1852.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 363.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 934.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.39 | 2736.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 199.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 23949.99 | 4709.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 875.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2111.01 | 415.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 875.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2111.01 | 415.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.99 | 0.503626 | 0.464000 | 1.39 | 1.00 | 0.500000 | 0.000757 | 0.000067 | 1.39 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.420337 | 0.121589 | 0.464000 | 0.195036 | 0.464000 | 0.500000 | 0.003134 | 0.000030 | 0.195036 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.308062 | 0.192116 | 0.464000 | 0.142941 | 0.512310 | 0.500000 | 0.001983 | 0.000015 | 0.142941 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.363670 | 0.344140 | 0.464000 | 0.168743 | 0.917707 | 0.500000 | 0.001107 | 0.000026 | 0.168743 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.198298 | 0.364132 | 0.464000 | 0.092010 | 0.971019 | 0.500000 | 0.001046 | 0.000014 | 0.092010 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.36 | 0.017694 | 0.464000 | 1.56 | 0.464000 | 0.500000 | 0.021532 | 0.000094 | 1.56 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.58 | 0.091112 | 0.464000 | 0.732893 | 0.464000 | 0.500000 | 0.004182 | 0.000083 | 0.732893 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.49 | 0.181489 | 0.464000 | 2.55 | 0.483972 | 0.500000 | 0.002099 | 0.000255 | 2.55 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.92 | 0.617671 | 0.464000 | 0.891614 | 1.00 | 0.500000 | 0.000617 | 0.000115 | 0.891614 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.48 | 0.101855 | 0.464000 | 1.15 | 0.464000 | 0.500000 | 0.003741 | 0.000101 | 1.15 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.59 | 0.097688 | 0.464000 | 1.20 | 0.464000 | 0.500000 | 0.003900 | 0.000104 | 1.20 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.38 | 0.059371 | 0.464000 | 1.11 | 0.464000 | 0.500000 | 0.011542 | 0.000064 | 1.11 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 1.02 | 0.309071 | 0.464000 | 0.471459 | 0.824188 | 0.500000 | 0.001233 | 0.000073 | 0.471459 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7679.63 | 0.000067 | 160.76 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3459.25 | 0.000030 | 82.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1724.96 | 0.000015 | 38.69 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2953.82 | 0.000026 | 70.49 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1609.80 | 0.000014 | 38.42 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10710.75 | 0.000094 | 227.30 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9523.15 | 0.000083 | 215.78 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29104.85 | 0.000255 | 648.12 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3949.12 | 0.000035 | 112.84 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3948.87 | 0.000035 | 112.83 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 22882.42 | 0.000200 | 653.81 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 22888.98 | 0.000200 | 654.00 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3953.22 | 0.000035 | 112.95 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3952.98 | 0.000035 | 112.95 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13133.22 | 0.000115 | 303.47 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1218.11 | 0.000011 | 34.80 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1218.02 | 0.000011 | 34.80 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5902.08 | 0.000052 | 168.63 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11496.76 | 0.000101 | 252.10 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11872.14 | 0.000104 | 260.07 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7337.24 | 0.000064 | 155.33 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8327.07 | 0.000073 | 199.10 |
VAV WITH REHEAT HEATING COIL | 91840.25 | 0.000803 | 1674.52 |
FLR_3_DOAS HEATING COIL | 7548.86 | 0.000066 | 137.64 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.12 | 0.000035 | 0.000348 |
ROOM_2_FLR_3 FAN COIL | 1.12 | 0.000035 | 0.000349 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.93 | 0.000200 | 0.002119 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.88 | 0.000200 | 0.002530 |
ROOM_5_FLR_3 FAN COIL | 1.01 | 0.000035 | 0.000316 |
ROOM_6_FLR_3 FAN COIL | 1.01 | 0.000035 | 0.000317 |
ROOM_1_FLR_6 FAN COIL | 0.312147 | 0.000011 | 0.000097 |
ROOM_2_FLR_6 FAN COIL | 0.313085 | 0.000011 | 0.000097 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.45 | 0.000052 | 0.000456 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.12 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.12 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.93 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.88 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.01 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.01 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.312147 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.313085 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.45 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008579 | 12.80 | 0.008500 | 0.000348 | 1.12 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008578 | 12.80 | 0.008500 | 0.000349 | 1.12 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008510 | 12.80 | 0.008500 | 0.002119 | 6.93 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008690 | 12.80 | 0.008500 | 0.002530 | 7.88 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008587 | 12.80 | 0.008500 | 0.000316 | 1.01 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008587 | 12.80 | 0.008500 | 0.000317 | 1.01 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000097 | 0.312147 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008570 | 12.80 | 0.008500 | 0.000097 | 0.313085 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008627 | 12.80 | 0.008500 | 0.000456 | 1.45 | |
VAV WITH REHEAT COOLING COIL | 32.43 | 6.70 | 0.009354 | 11.03 | 0.008500 | 0.020130 | 24.96 | 703847.63 |
FLR_3_DOAS COOLING COIL | 42.00 | 6.70 | 0.009158 | 11.91 | 0.008500 | 0.002232 | 2.05 | 78036.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.55 | 11.65 | 25.11 | 11.65 | 24.96 | 24.96 | 0.300000 | 0.466812 | 24.96 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.96 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.96 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020130 | 0.000024 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000803 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002232 | 0.000213 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000066 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.028992 | 4733.53 | |
HEATSYS1 PUMP | 0.002522 | 759.40 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002522 | 0.302593 |
COOLSYS1 | 0.028992 | 3.48 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 288235.55 | 288235.55 | 0.002522 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.028992 | 3277.18 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.028992 | 1013714.80 | 1017387.08 | 115.98 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
29 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
30 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
31 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
32 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
33 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
34 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
35 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
36 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
37 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
38 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
39 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
40 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
41 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
42 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
43 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
44 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
45 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
46 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
47 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
48 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
49 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
50 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
51 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
52 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
53 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
54 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
55 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
56 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
57 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
58 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
59 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
60 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
61 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
62 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
63 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
64 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
65 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
66 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
67 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
68 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
69 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
70 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
71 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
72 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
73 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
74 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
75 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
76 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
77 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
78 | 7 | -0.54138470E-12 | 0.12463713E-14 | -0.64276224E-14 | 0.11113167E-15 |
79 | 6 | 0.12246794E-07 | 0.15689727E-09 | 0.20336639E-09 | -0.66085082E-11 |
80 | 5 | -0.43638646E-04 | 0.91064443E-06 | -0.10338442E-05 | 0.73798452E-07 |
81 | 4 | 0.19644206E-01 | 0.40532412E-03 | 0.96204216E-03 | -0.14823791E-03 |
82 | 3 | -1.4347347 | 0.16410182E-01 | -0.13915079 | 0.27725787E-01 |
83 | 2 | 17.082538 | 0.80550987E-01 | 2.2432332 | -0.47694951 |
84 | 1 | -41.597683 | 0.53207822E-01 | -6.4041654 | 1.4049886 |
85 | 0 | 26.083068 | 0.22662127E-02 | 4.4519555 | |
86 | 7 | -0.64276224E-14 | 0.12463713E-14 | -0.54138470E-12 | 0.11113167E-15 |
87 | 6 | 0.20336639E-09 | 0.15689727E-09 | 0.12246794E-07 | -0.66085082E-11 |
88 | 5 | -0.10338442E-05 | 0.91064443E-06 | -0.43638646E-04 | 0.73798452E-07 |
89 | 4 | 0.96204216E-03 | 0.40532412E-03 | 0.19644206E-01 | -0.14823791E-03 |
90 | 3 | -0.13915079 | 0.16410182E-01 | -1.4347347 | 0.27725787E-01 |
91 | 2 | 2.2432332 | 0.80550987E-01 | 17.082538 | -0.47694951 |
92 | 1 | -6.4041654 | 0.53207822E-01 | -41.597683 | 1.4049886 |
93 | 0 | 4.4519555 | 0.22662127E-02 | 26.083068 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.57_SHGC_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.7224E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.4735E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.5423E-002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6448E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.8921E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4212E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.7401E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.3237E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1066 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5468E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.6186E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0937E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.2141E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2489E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7197E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.5026E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6243E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.4835E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.2141E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2489E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7197E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.5026E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6243E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.4835E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 40167.85384 | 40167.85384 | 2.99402 | 2.99402 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 21:30:00 | 35.84050 | 9.14765E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 548.84616 | 548.84616 | 2.41340E-002 | 0.85446 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5638.71931 | 5638.71931 | 0.42034 | 0.42034 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.15671E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2455.78860 | 2455.78860 | 0.10799 | 0.10799 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 4132.51452 | 4132.51452 | 0.30806 | 0.30806 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:20:00 | 37.86133 | 9.15100E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 989.50739 | 989.50739 | 4.35107E-002 | 9.17347E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4879.48985 | 4879.48985 | 0.36367 | 0.36367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:30:00 | 37.68350 | 9.15069E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2085.63222 | 2085.63222 | 9.17096E-002 | 9.17096E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2660.61393 | 2660.61393 | 0.19830 | 0.19830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 39.67200 | 9.15401E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1136.41836 | 1136.41836 | 4.99707E-002 | 5.77652E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45087.63832 | 45087.63832 | 3.36072 | 3.36072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 39.67200 | 9.15401E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2688.13513 | 2688.13513 | 0.11820 | 0.11820 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21171.35408 | 21171.35408 | 1.57951 | 1.57951 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5752.33936 | 5752.33936 | 0.25294 | 0.67639 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 73659.74533 | 73659.74533 | 5.49254 | 5.49254 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 40.77133 | 9.15585E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15992.19108 | 15992.19108 | 0.70321 | 1.89399 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11121.65141 | 11121.65141 | 1.11706 | 1.11706 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3949.13280 | 3949.13280 | 0.17467 | 0.17467 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11163.92716 | 11163.92716 | 1.12131 | 1.12131 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3948.88945 | 3948.88945 | 0.17466 | 0.17466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 69014.57007 | 69014.57007 | 6.93150 | 6.93150 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 22882.47258 | 22882.47258 | 1.01210 | 1.01210 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 78466.73755 | 78466.73755 | 7.88142 | 7.88142 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 22889.02434 | 22889.02434 | 1.01239 | 1.01239 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10075.83870 | 10075.83870 | 1.01202 | 1.01202 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | 39.76900 | 9.15417E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3953.23848 | 3953.23848 | 0.17485 | 0.17485 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10091.70417 | 10091.70417 | 1.01361 | 1.01361 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3952.99568 | 3952.99568 | 0.17484 | 0.17484 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 25780.61186 | 25780.61186 | 1.92158 | 1.92158 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 40.77133 | 9.15585E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8545.46026 | 8545.46026 | 0.37576 | 0.47476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3107.79333 | 3107.79333 | 0.31215 | 0.31215 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1218.11505 | 1218.11505 | 5.38773E-002 | 5.38773E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3117.13317 | 3117.13317 | 0.31309 | 0.31309 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1218.02952 | 1218.02952 | 5.38735E-002 | 5.38735E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14391.40366 | 14391.40366 | 1.44551 | 1.44551 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5902.10183 | 5902.10183 | 0.26105 | 0.26105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 33248.23749 | 33248.23749 | 2.48119 | 2.48119 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5572.68086 | 5572.68086 | 0.24504 | 1.18780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6.30000 | 6.07234E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 34667.13900 | 34667.13900 | 2.58705 | 2.58705 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5695.30554 | 5695.30554 | 0.25043 | 1.18780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 6.30000 | 6.07234E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31910.90630 | 31910.90630 | 2.38474 | 2.38474 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1658.17238 | 1658.17238 | 7.29055E-002 | 0.36735 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6.30000 | 6.07234E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 13632.12122 | 13632.12122 | 1.01608 | 1.01608 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5901.00733 | 5901.00733 | 0.25948 | 0.25948 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 6.30000 | 6.07234E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 576089.36 | 24.95656 | 24.95656 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 90397.44 | 7.36935 | 7.36935 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 70647.06 | 21.05051 | 2.05125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 25161.97 | 3.09232 | 2.05125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.99402 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50363 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.38923 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.56513E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.71847E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38923 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7679.62723 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.71847E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.76255 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.42034 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12159 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19504 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13351E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02630E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19504 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3459.24635 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02630E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 82.78404 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30806 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19212 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14294 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51231 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98317E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50907E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14294 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1724.96411 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50907E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.68588 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36367 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34414 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16874 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91771 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10711E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.58413E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16874 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2953.81520 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58413E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.49362 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19830 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36413 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.20102E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97102 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04632E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40833E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.20102E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1609.80356 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40833E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.41826 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.36072 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.76944E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.55937 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15322E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.37023E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.55937 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10710.75361 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.37023E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.30228 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57951 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.11122E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73289 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18166E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.33127E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73289 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9523.14991 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33127E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 215.78017 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.49254 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18149 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.54854 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48397 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09930E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.54622E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.54854 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29104.84904 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54622E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 648.11907 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11706 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11706 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.45486E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.48060E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69782 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57883E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.48060E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11706 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3949.11567 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45486E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 112.83714 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.12131 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.12131 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.45465E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.49350E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69782 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57848E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.49350E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.12131 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3948.87231 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45465E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 112.83018 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.93150 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.93150 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.00185E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.11936E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69829 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51033E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.11936E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.93150 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 22882.42387 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00185E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 653.80823 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.88142 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.88142 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.00243E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.53029E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69748 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68985E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.53029E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.88142 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 22888.97561 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00243E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 653.99542 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01202 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01202 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.45845E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.16024E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69780 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58687E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.16024E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01202 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3953.22133 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45845E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 112.95443 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01361 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01361 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.45824E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.16506E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69780 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58668E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.16506E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01361 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3952.97853 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45824E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 112.94750 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92158 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61767 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.89161 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.16834E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14895E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89161 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13133.21770 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14895E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.47006 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31215 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31215 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06566E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.70425E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69783 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57064E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.70425E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31215 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1218.10992 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06566E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 34.80396 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31309 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31309 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.06558E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.73272E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69783 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57037E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.73272E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31309 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1218.02440 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06558E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 34.80152 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.44551 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.44551 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.16340E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.56348E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69757 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62717E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.56348E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.44551 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5902.08190 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16340E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.63411 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48119 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10186 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15127 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.74060E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00579E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15127 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11496.75929 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00579E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.10201 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58705 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.76878E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20039 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.90018E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03863E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20039 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11872.13891 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03863E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.06608 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.38474 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.93711E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.10652 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46400 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15423E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.41894E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10652 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7337.24257 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.41894E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 155.33032 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01608 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30907 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46400 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47146 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82419 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23273E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.28488E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47146 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8327.06988 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.28488E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 199.10101 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.55390 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65002 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.10779 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65002 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.95656 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.95656 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46681 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.95656 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.95656 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 32.43128 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03301 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.35403E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 703847.63139 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.01300E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.95656 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 91840.24949 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.03459E-004 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1674.52353 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.95656 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.01300E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.36558E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.03459E-004 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 42.00000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90788 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.15790E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 78036.98448 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.23185E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 7548.85526 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.60407E-005 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 137.63830 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.23185E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.13362E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.60407E-005 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.89921E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4733.52647 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.52161E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.30259 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.52161E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 759.39828 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 288235.54566 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 288235.55000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.52161E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.89921E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.47905 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.89921E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3277.18003 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.89921E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1013714.79983 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1017387.08000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 115.98213 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7719.23 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3474.55 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1733.19 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2966.92 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1617.05 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10765.31 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9568.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29244.71 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 4253.37 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 4253.11 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 24645.30 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 24652.35 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 4257.80 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 4257.53 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13194.10 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1311.94 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1311.85 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6356.71 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11553.69 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11930.98 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7374.70 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8363.94 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 79611.27 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 6543.69 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18257.40 | 15657.55 | 2599.84 | 0.86 | 3843.95 | 38.99 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18325.61 | 15716.68 | 2608.93 | 0.86 | 3858.74 | 39.14 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 111817.84 | 96666.28 | 15151.56 | 0.86 | 24063.97 | 244.07 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 131472.67 | 111372.99 | 20099.68 | 0.85 | 26794.18 | 271.76 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16565.40 | 14193.48 | 2371.93 | 0.86 | 3478.74 | 35.28 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16590.92 | 14215.64 | 2375.28 | 0.86 | 3484.31 | 35.34 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5093.97 | 4372.69 | 721.28 | 0.86 | 1075.34 | 10.91 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5109.03 | 4385.75 | 723.28 | 0.86 | 1078.61 | 10.94 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23840.94 | 20334.64 | 3506.30 | 0.85 | 4949.17 | 50.20 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 681751.96 | 458430.85 | 223321.10 | 0.67 | 96154.04 | 975.25 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 59608.02 | 39109.31 | 20498.71 | 0.66 | 7316.35 | 74.21 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3544207153E-002 | 1.8231935257E-002 | Pass | Pass | 2.2852310432E-003 | 4.6310685766E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4358568920E-003 | 1.3471110711E-002 | Pass | Pass | 0.2084629667 | 0.6039165451 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7406852682E-002 | 2.3795069474E-002 | Pass | Pass | 6.0244401271E-003 | 1.5789710231E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9100803439E-004 | 4.4585256429E-004 | Pass | Pass | 5.3379439125E-002 | 8.8817938602E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0889277010E-004 | 3.9614928439E-004 | Pass | Pass | 3.8485007724E-002 | 4.5363120404E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1603986275E-002 | 0.1943718094 | Pass | Pass | 1.8063646538E-002 | 5.2745623298E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0850059191E-002 | 6.0509541317E-002 | Pass | Pass | 8.6763581525E-003 | 1.2982576532E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8771808433E-002 | 3.6800949401E-002 | Pass | Pass | 5.0278814454E-003 | 8.2882703334E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5667777987E-002 | 8.6602399597E-002 | Pass | Pass | 0.6268797553 | 2.6789123082 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.5141874554E-002 | 9.9688242531E-002 | Pass | Pass | 0.1625449021 | 0.7960561430 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3612889629E-002 | 5.0614120524E-002 | Pass | Pass | 0.2016029216 | 0.9025010231 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2832493771E-002 | 0.1017459004 | Pass | Pass | 0.2056683479 | 0.6417924784 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0015532711E-002 | 5.8517774620E-002 | Pass | Pass | 0.1865842814 | 0.4223078427 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6676230649E-002 | 7.5283739128E-002 | Pass | Pass | 0.5565046294 | 4.6341082368 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.1863052807E-004 | 1.3835798759E-003 | Pass | Pass | 2.8278860343E-002 | 5.2358949366E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4568202431E-002 | 0.1505069424 | Pass | Pass | 0.1514759844 | 0.5293225595 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3331222661E-002 | 0.1527801615 | Pass | Pass | 0.1873887987 | 1.0105468366 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9433568882E-002 | 0.2271795060 | Pass | Pass | 0.3789962514 | 2.0602485349 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2542529062E-002 | 7.7312478541E-002 | Pass | Pass | 8.6648641155E-003 | 2.4390913173E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5461905456E-002 | 6.6238457858E-002 | Pass | Pass | 1.0004787467E-002 | 3.0631042729E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9152090386E-002 | 8.8167947095E-002 | Pass | Pass | 2.2417794219E-002 | 4.4393863496E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2460511527E-004 | 6.6910165614E-004 | Pass | Pass | 0.3869364487 | 2.6218981938 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2330.83 | -53.1 | -795.2 | -2393.0 | 12811.23 | 11900.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.241 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.241 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.241 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 3.241 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.241 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.241 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.72 | 0.0000 | Y | 14.45 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.72 | 0.0000 | Y | 110.27 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.98 | 0.0000 | Y | 31.15 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.98 | 0.0000 | Y | 31.15 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.75 | 83.75 | 193.98 | |
Exterior Lighting Total | 12338.45 | 193.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 288235.55 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1017387.08 | 2.96 | 1017565.91 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12170.20 | 18257.40 | 15657.55 | 2599.84 | 0.86 | - | 3843.95 | 38.99 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12215.30 | 18325.61 | 15716.68 | 2608.93 | 0.86 | - | 3858.74 | 39.14 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 74105.29 | 111817.84 | 96666.28 | 15151.56 | 0.86 | - | 24063.97 | 244.07 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 88473.86 | 131472.67 | 111372.99 | 20099.68 | 0.85 | - | 26794.18 | 271.76 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11050.05 | 16565.40 | 14193.48 | 2371.93 | 0.86 | - | 3478.74 | 35.28 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11066.90 | 16590.92 | 14215.64 | 2375.28 | 0.86 | - | 3484.31 | 35.34 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3393.17 | 5093.97 | 4372.69 | 721.28 | 0.86 | - | 1075.34 | 10.91 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3403.13 | 5109.03 | 4385.75 | 723.28 | 0.86 | - | 1078.61 | 10.94 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15956.61 | 23840.94 | 20334.64 | 3506.30 | 0.85 | - | 4949.17 | 50.20 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 703847.63 | 681751.96 | 458430.85 | 223321.10 | 0.67 | - | 96154.04 | 975.25 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 78036.98 | 59608.02 | 39109.31 | 20498.71 | 0.66 | - | 7316.35 | 74.21 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7679.63 | 7719.23 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3459.25 | 3474.55 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1724.96 | 1733.19 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2953.82 | 2966.92 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1609.80 | 1617.05 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10710.75 | 10765.31 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9523.15 | 9568.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29104.85 | 29244.71 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3949.12 | 4253.37 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3948.87 | 4253.11 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 22882.42 | 24645.30 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 22888.98 | 24652.35 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3953.22 | 4257.80 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3952.98 | 4257.53 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13133.22 | 13194.10 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1218.11 | 1311.94 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1218.02 | 1311.85 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 5902.08 | 6356.71 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11496.76 | 11553.69 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11872.14 | 11930.98 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7337.24 | 7374.70 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8327.07 | 8363.94 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 91840.25 | 79611.27 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 7548.86 | 6543.69 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 786.01 | 703.64 | 1.00 | 1.17 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.12 | 788.99 | 703.64 | 1.00 | 1.17 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.93 | 4877.26 | 703.64 | 1.00 | 0.95 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.88 | 5545.66 | 703.64 | 1.00 | 0.94 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 712.09 | 703.64 | 1.00 | 1.19 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 713.22 | 703.64 | 1.00 | 1.19 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 219.64 | 703.64 | 1.00 | 1.69 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 220.30 | 703.64 | 1.00 | 1.68 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.45 | 1017.11 | 703.64 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1314.72 | 24.96 | 52912.26 | 2120.17 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.028992 | 4733.53 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002522 | 759.40 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028992 | 3277.18 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 40167.85 | 40167.85 | 20.30 | 2.994 | 2.994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 21:30:00 | 24.00 | 24.00 | 0.00910 | 35.84 | 0.00915 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5638.72 | 5638.72 | 84.07 | 0.420 | 0.420 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 24.00 | 24.00 | 0.00894 | 41.29 | 0.00916 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 4132.51 | 4132.51 | 53.21 | 0.308 | 0.308 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:20:00 | 24.00 | 24.00 | 0.00919 | 37.86 | 0.00915 | 0.092 | 0.00 |
MECH_FLR_1 | 4879.49 | 4879.49 | 29.71 | 0.364 | 0.364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:30:00 | 24.00 | 24.00 | 0.00864 | 37.68 | 0.00915 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2660.61 | 2660.61 | 28.08 | 0.198 | 0.198 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 24.00 | 24.00 | 0.00869 | 39.67 | 0.00915 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45087.64 | 45087.64 | 577.75 | 3.361 | 3.361 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 24.00 | 24.00 | 0.00854 | 39.67 | 0.00915 | 0.000 | 0.00 |
CAFE_FLR_1 | 21171.35 | 21171.35 | 112.10 | 1.580 | 1.580 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 24.00 | 23.99 | 0.01001 | 42.00 | 0.00916 | 0.676 | 0.00 |
LOBBY_FLR_1 | 73659.75 | 73659.75 | 56.31 | 5.493 | 5.493 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 24.00 | 23.99 | 0.00979 | 40.77 | 0.00916 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11121.65 | 11121.65 | 285.01 | 1.117 | 1.117 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 21.11 | 21.11 | 0.00858 | 41.03 | 0.00916 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11163.93 | 11163.93 | 286.13 | 1.121 | 1.121 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 21.11 | 21.11 | 0.00858 | 41.03 | 0.00916 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 69014.57 | 69014.57 | 2814.18 | 6.932 | 6.932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 21.11 | 21.11 | 0.00851 | 41.71 | 0.00916 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 78466.74 | 78466.74 | 3198.74 | 7.881 | 7.881 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 21.11 | 21.11 | 0.00869 | 41.03 | 0.00916 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10075.84 | 10075.84 | 258.21 | 1.012 | 1.012 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | 21.11 | 21.11 | 0.00859 | 39.77 | 0.00915 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10091.70 | 10091.70 | 258.65 | 1.014 | 1.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 21.11 | 21.11 | 0.00859 | 39.53 | 0.00915 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 25780.61 | 25780.61 | 66.21 | 1.922 | 1.922 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 24.00 | 24.00 | 0.00924 | 40.77 | 0.00916 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3107.79 | 3107.79 | 79.64 | 0.312 | 0.312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 41.16 | 0.00916 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3117.13 | 3117.13 | 79.89 | 0.313 | 0.313 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 41.16 | 0.00916 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14391.40 | 14391.40 | 586.67 | 1.446 | 1.446 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 21.11 | 21.11 | 0.00863 | 42.00 | 0.00916 | 0.099 | 0.00 |
BANQUET_FLR_6 | 33248.24 | 33248.24 | 100.25 | 2.481 | 2.481 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 23.99 | 0.01019 | 41.71 | 0.00916 | 1.188 | 0.00 |
DINING_FLR_6 | 34667.14 | 34667.14 | 104.53 | 2.587 | 2.587 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 23.99 | 0.01012 | 41.61 | 0.00916 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31910.91 | 31910.91 | 308.90 | 2.385 | 2.385 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 24.00 | 23.97 | 0.01002 | 41.13 | 0.00916 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 13632.12 | 13632.12 | 33.08 | 1.016 | 1.016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00887 | 41.81 | 0.00916 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 548.85 | 548.85 | 0.28 | 0.024 | 0.854 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00653 | 6.30 | 0.00607 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2455.79 | 2455.79 | 36.61 | 0.108 | 0.108 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | 6.30 | 0.00607 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 989.51 | 989.51 | 12.74 | 0.044 | 0.092 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 0.092 | 0.00 |
MECH_FLR_1 | 2085.63 | 2085.63 | 12.70 | 0.092 | 0.092 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00782 | 6.30 | 0.00607 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1136.42 | 1136.42 | 11.99 | 0.050 | 0.058 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00781 | 6.30 | 0.00607 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2688.14 | 2688.14 | 34.45 | 0.118 | 0.118 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00781 | 6.30 | 0.00607 | 0.000 | 0.00 |
CAFE_FLR_1 | 5752.34 | 5752.34 | 30.46 | 0.253 | 0.676 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15992.19 | 15992.19 | 12.22 | 0.703 | 1.894 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3949.13 | 3949.13 | 101.20 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3948.89 | 3948.89 | 101.21 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22882.47 | 22882.47 | 933.07 | 1.012 | 1.012 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00779 | 6.30 | 0.00607 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 22889.02 | 22889.02 | 933.08 | 1.012 | 1.012 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00779 | 6.30 | 0.00607 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3953.24 | 3953.24 | 101.31 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3953.00 | 3953.00 | 101.31 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | 6.30 | 0.00607 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8545.46 | 8545.46 | 21.94 | 0.376 | 0.475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | 6.30 | 0.00607 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1218.12 | 1218.12 | 31.22 | 0.054 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00781 | 6.30 | 0.00607 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1218.03 | 1218.03 | 31.22 | 0.054 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00781 | 6.30 | 0.00607 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5902.10 | 5902.10 | 240.60 | 0.261 | 0.261 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00782 | 6.30 | 0.00607 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5572.68 | 5572.68 | 16.80 | 0.245 | 1.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00789 | 6.30 | 0.00607 | 1.188 | 0.00 |
DINING_FLR_6 | 5695.31 | 5695.31 | 17.17 | 0.250 | 1.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00789 | 6.30 | 0.00607 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1658.17 | 1658.17 | 16.05 | 0.073 | 0.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00676 | 6.30 | 0.00607 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5901.01 | 5901.01 | 14.32 | 0.259 | 0.259 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.96 | 24.96 | 7.37 | 7.37 | 24.9566 | 11.6500 | 24.9566 | 0.4668 | 0.3000 |
FLR_3_DOAS | 21.05 | 2.05 | 3.09 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7679.627 | 7679.627 | 1.389226 | 0.00006718 | 160.763 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7679.63 | 7679.63 | 1.389226 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00652661 | 41.2243 | 548.85 | 0.00 | 7722.73 | 7722.73 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3459.246 | 3459.246 | 0.195036 | 0.00003026 | 82.784 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3459.25 | 3459.25 | 0.195036 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00783387 | 49.3793 | 2455.79 | 0.00 | 3477.35 | 3477.35 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1724.964 | 1724.964 | 0.142941 | 0.00001509 | 38.686 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1724.96 | 1724.96 | 0.142941 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00784021 | 49.4183 | 989.51 | 0.00 | 1734.30 | 1734.30 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2953.815 | 2953.815 | 0.168743 | 0.00002584 | 70.494 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2953.82 | 2953.82 | 0.168743 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00782261 | 49.3088 | 2085.63 | 0.00 | 2969.29 | 2969.29 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1609.804 | 1609.804 | 0.092010 | 0.00001408 | 38.418 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1609.80 | 1609.80 | 0.092010 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00781317 | 49.2500 | 1136.42 | 0.00 | 1618.35 | 1618.35 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10710.754 | 10710.754 | 1.559374 | 0.00009370 | 227.302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10710.75 | 10710.75 | 1.559374 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00781316 | 49.2504 | 2688.14 | 0.00 | 10770.58 | 10770.58 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9523.150 | 9523.150 | 0.732893 | 0.00008331 | 215.780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9523.15 | 9523.15 | 0.732893 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00784245 | 49.4326 | 5752.34 | 0.00 | 9574.50 | 9574.50 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29104.849 | 29104.849 | 2.548538 | 0.00025462 | 648.119 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 29104.85 | 29104.85 | 2.548538 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00783838 | 49.4070 | 15992.19 | 0.00 | 29262.82 | 29262.82 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12170.201 | -999.000 | 1.117061 | 0.00034806 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | 6/21 16:30:00 | 12170.20 | 11946.58 | 1.117061 | 21.70 | 15.37 | 0.00857883 | 12.80 | 11.87 | 0.00850000 | 41.03 | 0.00915628 | 21.99 | 0.0000 | 21.11 | 0.00857883 | 53.6447 | 11121.65 | 0.00 | 12485.48 | 12485.48 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3949.116 | 3949.116 | 0.174670 | 0.00003455 | 112.837 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3949.12 | 3949.12 | 0.174670 | 21.11 | 14.43 | 0.00777017 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00777017 | 48.6499 | 3949.13 | 0.00 | 4257.27 | 4257.27 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12215.302 | -999.000 | 1.121308 | 0.00034935 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | 6/21 16:30:00 | 12215.30 | 11991.82 | 1.121308 | 21.70 | 15.37 | 0.00857848 | 12.80 | 11.87 | 0.00850000 | 41.03 | 0.00915628 | 21.99 | 0.0000 | 21.11 | 0.00857848 | 53.6426 | 11163.93 | 0.00 | 12531.77 | 12531.77 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3948.872 | 3948.872 | 0.174660 | 0.00003455 | 112.830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3948.87 | 3948.87 | 0.174660 | 21.11 | 14.43 | 0.00777017 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00777017 | 48.6499 | 3948.89 | 0.00 | 4257.01 | 4257.01 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 74105.294 | -999.000 | 6.931502 | 0.00211936 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | unknown | 6/21 15:30:00 | 74105.29 | 73923.99 | 6.931502 | 21.70 | 15.31 | 0.00851033 | 12.80 | 11.87 | 0.00850000 | 41.71 | 0.00915741 | 22.18 | 0.0000 | 21.11 | 0.00851033 | 53.2209 | 69014.57 | 0.00 | 76041.89 | 76041.89 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 22882.424 | 22882.424 | 1.012103 | 0.00020019 | 653.808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 22882.42 | 22882.42 | 1.012103 | 21.11 | 14.45 | 0.00778757 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00778757 | 48.7571 | 22882.47 | 0.00 | 24668.04 | 24668.04 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 88473.856 | -999.000 | 7.881424 | 0.00253029 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | 6/21 16:30:00 | 88473.86 | 84657.03 | 7.881424 | 21.70 | 15.47 | 0.00868985 | 12.80 | 11.87 | 0.00850000 | 41.03 | 0.00915628 | 21.99 | 0.0000 | 21.11 | 0.00868985 | 54.3302 | 78466.74 | 0.00 | 90727.94 | 90727.94 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 22888.976 | 22888.976 | 1.012392 | 0.00020024 | 653.995 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 22888.98 | 22888.98 | 1.012392 | 21.11 | 14.45 | 0.00778757 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00778757 | 48.7571 | 22889.02 | 0.00 | 24675.10 | 24675.10 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11050.054 | -999.000 | 1.012020 | 0.00031602 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | unknown | 6/21 11:00:00 | 11050.05 | 10826.72 | 1.012020 | 21.70 | 15.38 | 0.00858687 | 12.80 | 11.87 | 0.00850000 | 39.77 | 0.00915417 | 21.63 | 0.0000 | 21.11 | 0.00858687 | 53.6944 | 10075.84 | 0.00 | 11335.83 | 11335.83 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3953.221 | 3953.221 | 0.174852 | 0.00003458 | 112.954 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3953.22 | 3953.22 | 0.174852 | 21.11 | 14.43 | 0.00777038 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00777038 | 48.6512 | 3953.24 | 0.00 | 4261.70 | 4261.70 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11066.898 | -999.000 | 1.013614 | 0.00031651 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | 6/21 10:50:00 | 11066.90 | 10843.69 | 1.013614 | 21.70 | 15.38 | 0.00858668 | 12.80 | 11.87 | 0.00850000 | 39.53 | 0.00915377 | 21.56 | 0.0000 | 21.11 | 0.00858668 | 53.6932 | 10091.70 | 0.00 | 11353.12 | 11353.12 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3952.979 | 3952.979 | 0.174841 | 0.00003458 | 112.947 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3952.98 | 3952.98 | 0.174841 | 21.11 | 14.43 | 0.00777038 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00777038 | 48.6512 | 3953.00 | 0.00 | 4261.44 | 4261.44 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13133.218 | 13133.218 | 0.891614 | 0.00011490 | 303.470 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13133.22 | 13133.22 | 0.891614 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00786370 | 49.5644 | 8545.46 | 0.00 | 13203.55 | 13203.55 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3393.174 | -999.000 | 0.312147 | 0.00009704 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | 6/21 16:20:00 | 3393.17 | 3337.20 | 0.312147 | 21.70 | 15.37 | 0.00857064 | 12.80 | 11.87 | 0.00850000 | 41.16 | 0.00915650 | 22.03 | 0.0000 | 21.11 | 0.00857064 | 53.5942 | 3107.79 | 0.00 | 3481.23 | 3481.23 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1218.110 | 1218.110 | 0.053877 | 0.00001066 | 34.804 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1218.11 | 1218.11 | 0.053877 | 21.11 | 14.47 | 0.00780938 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00780938 | 48.8924 | 1218.12 | 0.00 | 1313.16 | 1313.16 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3403.127 | -999.000 | 0.313085 | 0.00009733 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | 6/21 16:20:00 | 3403.13 | 3347.19 | 0.313085 | 21.70 | 15.37 | 0.00857037 | 12.80 | 11.87 | 0.00850000 | 41.16 | 0.00915650 | 22.03 | 0.0000 | 21.11 | 0.00857037 | 53.5926 | 3117.13 | 0.00 | 3491.45 | 3491.45 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1218.024 | 1218.024 | 0.053874 | 0.00001066 | 34.802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1218.02 | 1218.02 | 0.053874 | 21.11 | 14.47 | 0.00780939 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00780939 | 48.8924 | 1218.03 | 0.00 | 1313.07 | 1313.07 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15956.607 | -999.000 | 1.445510 | 0.00045635 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | unknown | 6/21 14:50:00 | 15956.61 | 15488.86 | 1.445510 | 21.70 | 15.42 | 0.00862717 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 0.0000 | 21.11 | 0.00862717 | 53.9435 | 14391.40 | 0.00 | 16368.40 | 16368.40 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5902.082 | 5902.082 | 0.261051 | 0.00005163 | 168.634 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 5902.08 | 5902.08 | 0.261051 | 21.11 | 14.48 | 0.00781795 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00781795 | 48.9452 | 5902.10 | 0.00 | 6362.64 | 6362.64 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11496.759 | 11496.759 | 1.151274 | 0.00010058 | 252.102 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11496.76 | 11496.76 | 1.151274 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00789275 | 49.7454 | 5572.68 | 0.00 | 11560.37 | 11560.37 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11872.139 | 11872.139 | 1.200390 | 0.00010386 | 260.066 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 11872.14 | 11872.14 | 1.200390 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00789494 | 49.7590 | 5695.31 | 0.00 | 11937.84 | 11937.84 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7337.243 | 7337.243 | 1.106517 | 0.00006419 | 155.330 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7337.24 | 7337.24 | 1.106517 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00675572 | 42.6618 | 1658.17 | 0.00 | 7378.26 | 7378.26 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8327.070 | 8327.070 | 0.471459 | 0.00007285 | 199.101 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8327.07 | 8327.07 | 0.471459 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791040 | 49.8552 | 5901.01 | 0.00 | 8370.67 | 8370.67 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 703847.631 | -999.000 | 24.956564 | 0.02012995 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 703847.63 | 639278.99 | 24.956564 | 32.43 | 19.59 | 0.00935403 | 11.03 | 11.03 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 46.7270 | 23.99 | 0.00947585 | 49.6665 | 333581.86 | 0.00 | 715070.71 | 630280.56 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 91840.249 | 91840.249 | 7.486969 | 0.00080346 | 1674.524 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 91840.25 | 91840.25 | 7.486969 | 6.30 | 6.30 | 0.00607234 | 16.70 | 12.95 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 155.7568 | 21.02 | 0.00783621 | 49.3423 | 58555.83 | 0.00 | 96384.05 | 96384.05 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 78036.984 | -999.000 | 2.051317 | 0.00223185 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 78036.98 | 74039.07 | 2.051317 | 42.00 | 22.26 | 0.00915790 | 11.91 | 11.50 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 99.9965 | 21.11 | 0.00860619 | 53.8133 | 208231.56 | 0.00 | 79029.81 | 74008.48 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 7548.855 | 7548.855 | 0.615395 | 0.00006604 | 137.638 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 7548.86 | 7548.86 | 0.615395 | 6.30 | 6.30 | 0.00607234 | 16.70 | 12.95 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 333.3216 | 21.11 | 0.00778773 | 48.7581 | 69914.00 | 0.00 | 7922.34 | 7922.34 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7679.627 | 7679.627 | 1.389226 | 0.00006718 | 160.763 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 2.6118 | 2.664358 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7679.63 | 7679.63 | 1.0000 | 1.63065377 | 1.389226 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06717788 | 60.00 | 32.22 | 27.78 | 0.000 | 7679.63 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00652661 | 21.00 | 0.00652661 | 41.2243 | 548.85 | 0.00 | 7722.73 | 7722.73 | 1.63065377 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.24 | 14.94 | 0.00800000 | 41670.7 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3459.246 | 3459.246 | 0.195036 | 0.00003026 | 82.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.1765 | 1.200146 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3459.25 | 3459.25 | 1.0000 | 0.22893088 | 0.195036 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03025991 | 60.00 | 32.22 | 27.78 | 0.000 | 3459.25 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783387 | 21.00 | 0.00783387 | 49.3793 | 2455.79 | 0.00 | 3477.35 | 3477.35 | 0.22893088 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.50 | 18.53 | 0.00800000 | 52124.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1724.964 | 1724.964 | 0.142941 | 0.00001509 | 38.686 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 0.5866 | 0.598456 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1724.96 | 1724.96 | 1.0000 | 0.16778176 | 0.142941 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01508920 | 60.00 | 32.22 | 27.78 | 0.000 | 1724.96 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00784021 | 21.00 | 0.00784021 | 49.4183 | 989.51 | 0.00 | 1734.30 | 1734.30 | 0.16778176 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.74 | 16.92 | 0.00800000 | 47271.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2953.815 | 2953.815 | 0.168743 | 0.00002584 | 70.494 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.0046 | 1.024792 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2953.82 | 2953.82 | 1.0000 | 0.19806771 | 0.168743 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02583863 | 60.00 | 32.22 | 27.78 | 0.000 | 2953.82 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00782261 | 21.00 | 0.00782261 | 49.3088 | 2085.63 | 0.00 | 2969.29 | 2969.29 | 0.19806771 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.30 | 18.47 | 0.00800000 | 51926.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1609.804 | 1609.804 | 0.092010 | 0.00001408 | 38.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 0.5475 | 0.558503 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1609.80 | 1609.80 | 1.0000 | 0.10800018 | 0.092010 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01408183 | 60.00 | 32.22 | 27.78 | 0.000 | 1609.80 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00781317 | 21.00 | 0.00781317 | 49.2500 | 1136.42 | 0.00 | 1618.35 | 1618.35 | 0.10800018 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.30 | 18.47 | 0.00800000 | 51919.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10710.754 | 10710.754 | 1.559374 | 0.00009370 | 227.302 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 3.6427 | 3.715972 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10710.75 | 10710.75 | 1.0000 | 1.83037022 | 1.559374 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09369279 | 60.00 | 32.22 | 27.78 | 0.000 | 10710.75 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00781316 | 21.00 | 0.00781316 | 49.2504 | 2688.14 | 0.00 | 10770.58 | 10770.58 | 1.83037022 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.37 | 15.36 | 0.00800000 | 42819.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9523.150 | 9523.150 | 0.732893 | 0.00008331 | 215.780 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 3.2388 | 3.303947 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9523.15 | 9523.15 | 1.0000 | 0.86025934 | 0.732893 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08330417 | 60.00 | 32.22 | 27.78 | 0.000 | 9523.15 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00784245 | 21.00 | 0.00784245 | 49.4326 | 5752.34 | 0.00 | 9574.50 | 9574.50 | 0.86025934 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.51 | 17.19 | 0.00800000 | 48064.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29104.849 | 29104.849 | 2.548538 | 0.00025462 | 648.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 9.8984 | 10.097592 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 29104.85 | 29104.85 | 1.0000 | 2.99143645 | 2.548538 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.25459594 | 60.00 | 32.22 | 27.78 | 0.000 | 29104.85 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783838 | 21.00 | 0.00783838 | 49.4070 | 15992.19 | 0.00 | 29262.82 | 29262.82 | 2.99143645 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.19 | 16.73 | 0.00800000 | 46716.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12170.201 | -999.000 | 1.117061 | 0.00034806 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7876 | 1004.8586 | 1.1738 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.117061 | 1.31119045 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 1.2006 | 1.200532 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | unknown | unknown | 6/21 16:30:00 | Sensible | 12170.20 | 11946.58 | 1.0000 | 1.31119045 | 1.117061 | 21.70 | 15.37 | 0.00857883 | 43604.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.34802420 | 6.70 | 15.03 | 8.33 | 0.000 | 12170.20 | 41.03 | 0.00915628 | 21.99 | 0.00000000 | 0.0000 | 21.11 | 0.00857883 | 21.11 | 0.00857883 | 53.6447 | 11121.65 | 0.00 | 12485.48 | 12485.48 | 1.31119045 | 21.70 | 15.63 | 0.00857883 | 43604.0 | 12.37 | 12.00 | 0.00857883 | 34081.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3949.116 | 3949.116 | 0.174670 | 0.00003455 | 112.837 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.117061 | 1.31119045 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.3431 | 1.370100 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3949.12 | 3949.12 | 1.0000 | 0.20502566 | 0.174670 | 21.11 | 14.43 | 0.00777017 | 40950.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03454506 | 60.00 | 32.22 | 27.78 | 0.000 | 3949.12 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777017 | 21.11 | 0.00777017 | 48.6499 | 3949.13 | 0.00 | 4257.27 | 4257.27 | 0.20502566 | 16.60 | 12.93 | 0.00777017 | 36352.9 | 36.97 | 20.10 | 0.00777017 | 57117.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12215.302 | -999.000 | 1.121308 | 0.00034935 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7870 | 1004.8586 | 1.1738 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.121308 | 1.31617464 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 1.2050 | 1.204981 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | unknown | unknown | 6/21 16:30:00 | Sensible | 12215.30 | 11991.82 | 1.0000 | 1.31617464 | 1.121308 | 21.70 | 15.37 | 0.00857848 | 43603.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.34931392 | 6.70 | 15.03 | 8.33 | 0.000 | 12215.30 | 41.03 | 0.00915628 | 21.99 | 0.00000000 | 0.0000 | 21.11 | 0.00857848 | 21.11 | 0.00857848 | 53.6426 | 11163.93 | 0.00 | 12531.77 | 12531.77 | 1.31617464 | 21.70 | 15.63 | 0.00857848 | 43603.1 | 12.37 | 12.00 | 0.00857848 | 34081.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3948.872 | 3948.872 | 0.174660 | 0.00003455 | 112.830 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.121308 | 1.31617464 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.3430 | 1.370016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3948.87 | 3948.87 | 1.0000 | 0.20501302 | 0.174660 | 21.11 | 14.43 | 0.00777017 | 40950.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03454293 | 60.00 | 32.22 | 27.78 | 0.000 | 3948.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777017 | 21.11 | 0.00777017 | 48.6499 | 3948.89 | 0.00 | 4257.01 | 4257.01 | 0.20501302 | 16.60 | 12.93 | 0.00777017 | 36352.9 | 36.97 | 20.10 | 0.00777017 | 57117.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74105.294 | -999.000 | 6.931502 | 0.00211936 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6603 | 1004.8586 | 1.1738 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.931502 | 8.13609683 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 7.3103 | 7.310134 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | unknown | unknown | unknown | 6/21 15:30:00 | Sensible | 74105.29 | 73923.99 | 1.0000 | 8.13609683 | 6.931502 | 21.70 | 15.31 | 0.00851033 | 43430.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.11914624 | 6.70 | 15.03 | 8.33 | 0.000 | 74105.29 | 41.71 | 0.00915741 | 22.18 | 0.00000000 | 0.0000 | 21.11 | 0.00851033 | 21.11 | 0.00851033 | 53.2209 | 69014.57 | 0.00 | 76041.89 | 76041.89 | 8.13609683 | 21.70 | 15.57 | 0.00851033 | 43430.4 | 12.54 | 12.00 | 0.00851033 | 34084.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22882.424 | 22882.424 | 1.012103 | 0.00020019 | 653.808 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.931502 | 8.13609683 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 7.7822 | 7.938793 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 22882.42 | 22882.42 | 1.0000 | 1.18799127 | 1.012103 | 21.11 | 14.45 | 0.00778757 | 40994.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20016501 | 60.00 | 32.22 | 27.78 | 0.000 | 22882.42 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00778757 | 21.11 | 0.00778757 | 48.7571 | 22882.47 | 0.00 | 24668.04 | 24668.04 | 1.18799127 | 16.60 | 12.94 | 0.00778757 | 36396.9 | 36.97 | 20.11 | 0.00778757 | 57161.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 88473.856 | -999.000 | 7.881424 | 0.00253029 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9940 | 1004.8586 | 1.1738 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.881424 | 9.25110088 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 8.7277 | 8.727524 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | unknown | unknown | 6/21 16:30:00 | Sensible | 88473.86 | 84657.03 | 1.0000 | 9.25110088 | 7.881424 | 21.70 | 15.47 | 0.00868985 | 43885.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.53003571 | 6.70 | 15.03 | 8.33 | 0.000 | 88473.86 | 41.03 | 0.00915628 | 21.99 | 0.00000000 | 0.0000 | 21.11 | 0.00868985 | 21.11 | 0.00868985 | 54.3302 | 78466.74 | 0.00 | 90727.94 | 90727.94 | 9.25110088 | 21.70 | 15.73 | 0.00868985 | 43885.8 | 12.09 | 12.00 | 0.00868985 | 34078.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22888.976 | 22888.976 | 1.012392 | 0.00020024 | 653.995 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.881424 | 9.25110088 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 7.7844 | 7.941066 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 22888.98 | 22888.98 | 1.0000 | 1.18833141 | 1.012392 | 21.11 | 14.45 | 0.00778757 | 40994.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20022232 | 60.00 | 32.22 | 27.78 | 0.000 | 22888.98 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00778757 | 21.11 | 0.00778757 | 48.7571 | 22889.02 | 0.00 | 24675.10 | 24675.10 | 1.18833141 | 16.60 | 12.94 | 0.00778757 | 36396.9 | 36.97 | 20.11 | 0.00778757 | 57161.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11050.054 | -999.000 | 1.012020 | 0.00031602 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8026 | 1004.8586 | 1.1738 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.012020 | 1.18789484 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 1.0901 | 1.090035 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | unknown | unknown | unknown | 6/21 11:00:00 | Sensible | 11050.05 | 10826.72 | 1.0000 | 1.18789484 | 1.012020 | 21.70 | 15.38 | 0.00858687 | 43624.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.31599202 | 6.70 | 15.03 | 8.33 | 0.000 | 11050.05 | 39.77 | 0.00915417 | 21.63 | 0.00000000 | 0.0000 | 21.11 | 0.00858687 | 21.11 | 0.00858687 | 53.6944 | 10075.84 | 0.00 | 11335.83 | 11335.83 | 1.18789484 | 21.70 | 15.64 | 0.00858687 | 43624.4 | 12.35 | 12.00 | 0.00858687 | 34081.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3953.221 | 3953.221 | 0.174852 | 0.00003458 | 112.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.012020 | 1.18789484 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.3445 | 1.371525 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3953.22 | 3953.22 | 1.0000 | 0.20523881 | 0.174852 | 21.11 | 14.43 | 0.00777038 | 40951.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03458098 | 60.00 | 32.22 | 27.78 | 0.000 | 3953.22 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777038 | 21.11 | 0.00777038 | 48.6512 | 3953.24 | 0.00 | 4261.70 | 4261.70 | 0.20523881 | 16.60 | 12.93 | 0.00777038 | 36353.4 | 36.97 | 20.10 | 0.00777038 | 57118.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11066.898 | -999.000 | 1.013614 | 0.00031651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8022 | 1004.8586 | 1.1738 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.013614 | 1.18976537 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 1.0917 | 1.091697 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | unknown | unknown | 6/21 10:50:00 | Sensible | 11066.90 | 10843.69 | 1.0000 | 1.18976537 | 1.013614 | 21.70 | 15.38 | 0.00858668 | 43623.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.31647370 | 6.70 | 15.03 | 8.33 | 0.000 | 11066.90 | 39.53 | 0.00915377 | 21.56 | 0.00000000 | 0.0000 | 21.11 | 0.00858668 | 21.11 | 0.00858668 | 53.6932 | 10091.70 | 0.00 | 11353.12 | 11353.12 | 1.18976537 | 21.70 | 15.64 | 0.00858668 | 43623.9 | 12.35 | 12.00 | 0.00858668 | 34081.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3952.979 | 3952.979 | 0.174841 | 0.00003458 | 112.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.013614 | 1.18976537 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 1.3444 | 1.371440 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3952.98 | 3952.98 | 1.0000 | 0.20522620 | 0.174841 | 21.11 | 14.43 | 0.00777038 | 40951.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03457885 | 60.00 | 32.22 | 27.78 | 0.000 | 3952.98 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777038 | 21.11 | 0.00777038 | 48.6512 | 3953.00 | 0.00 | 4261.44 | 4261.44 | 0.20522620 | 16.60 | 12.93 | 0.00777038 | 36353.4 | 36.97 | 20.10 | 0.00777038 | 57118.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13133.218 | 13133.218 | 0.891614 | 0.00011490 | 303.470 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 4.4665 | 4.556418 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13133.22 | 13133.22 | 1.0000 | 1.04656413 | 0.891614 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11488340 | 60.00 | 32.22 | 27.78 | 0.000 | 13133.22 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00786370 | 21.00 | 0.00786370 | 49.5644 | 8545.46 | 0.00 | 13203.55 | 13203.55 | 1.04656413 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.97 | 17.69 | 0.00800000 | 49550.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3393.174 | -999.000 | 0.312147 | 0.00009704 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7724 | 1004.8586 | 1.1738 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.312147 | 0.36639392 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 0.3347 | 0.334720 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | unknown | unknown | 6/21 16:20:00 | Sensible | 3393.17 | 3337.20 | 1.0000 | 0.36639392 | 0.312147 | 21.70 | 15.37 | 0.00857064 | 43583.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.09703263 | 6.70 | 15.03 | 8.33 | 0.000 | 3393.17 | 41.16 | 0.00915650 | 22.03 | 0.00000000 | 0.0000 | 21.11 | 0.00857064 | 21.11 | 0.00857064 | 53.5942 | 3107.79 | 0.00 | 3481.23 | 3481.23 | 0.36639392 | 21.70 | 15.62 | 0.00857064 | 43583.2 | 12.39 | 12.00 | 0.00857064 | 34081.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1218.110 | 1218.110 | 0.053877 | 0.00001066 | 34.804 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.312147 | 0.36639392 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 0.4143 | 0.422609 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1218.11 | 1218.11 | 1.0000 | 0.06324043 | 0.053877 | 21.11 | 14.47 | 0.00780938 | 41050.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01065547 | 60.00 | 32.22 | 27.78 | 0.000 | 1218.11 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00780938 | 21.11 | 0.00780938 | 48.8924 | 1218.12 | 0.00 | 1313.16 | 1313.16 | 0.06324043 | 16.60 | 12.97 | 0.00780938 | 36452.1 | 36.97 | 20.13 | 0.00780938 | 57216.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3403.127 | -999.000 | 0.313085 | 0.00009733 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7719 | 1004.8586 | 1.1738 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.313085 | 0.36749507 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 0.3357 | 0.335702 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | unknown | unknown | 6/21 16:20:00 | Sensible | 3403.13 | 3347.19 | 1.0000 | 0.36749507 | 0.313085 | 21.70 | 15.37 | 0.00857037 | 43582.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.09731727 | 6.70 | 15.03 | 8.33 | 0.000 | 3403.13 | 41.16 | 0.00915650 | 22.03 | 0.00000000 | 0.0000 | 21.11 | 0.00857037 | 21.11 | 0.00857037 | 53.5926 | 3117.13 | 0.00 | 3491.45 | 3491.45 | 0.36749507 | 21.70 | 15.62 | 0.00857037 | 43582.5 | 12.39 | 12.00 | 0.00857037 | 34081.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1218.024 | 1218.024 | 0.053874 | 0.00001066 | 34.802 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.313085 | 0.36749507 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 0.4142 | 0.422580 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1218.02 | 1218.02 | 1.0000 | 0.06323599 | 0.053874 | 21.11 | 14.47 | 0.00780939 | 41050.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01065472 | 60.00 | 32.22 | 27.78 | 0.000 | 1218.02 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00780939 | 21.11 | 0.00780939 | 48.8924 | 1218.03 | 0.00 | 1313.07 | 1313.07 | 0.06323599 | 16.60 | 12.97 | 0.00780939 | 36452.1 | 36.97 | 20.13 | 0.00780939 | 57216.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15956.607 | -999.000 | 1.445510 | 0.00045635 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8775 | 1004.8586 | 1.1738 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.445510 | 1.69671864 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 1.5741 | 1.574043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | unknown | unknown | unknown | 6/21 14:50:00 | Sensible | 15956.61 | 15488.86 | 1.0000 | 1.69671864 | 1.445510 | 21.70 | 15.42 | 0.00862717 | 43726.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.45630186 | 6.70 | 15.03 | 8.33 | 0.000 | 15956.61 | 42.00 | 0.00915790 | 22.26 | 0.00000000 | 0.0000 | 21.11 | 0.00862717 | 21.11 | 0.00862717 | 53.9435 | 14391.40 | 0.00 | 16368.40 | 16368.40 | 1.69671864 | 21.70 | 15.67 | 0.00862717 | 43726.6 | 12.25 | 12.00 | 0.00862717 | 34079.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5902.082 | 5902.082 | 0.261051 | 0.00005163 | 168.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.445510 | 1.69671864 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 2.0073 | 2.047659 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 5902.08 | 5902.08 | 1.0000 | 0.30641819 | 0.261051 | 21.11 | 14.48 | 0.00781795 | 41072.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05162872 | 60.00 | 32.22 | 27.78 | 0.000 | 5902.08 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00781795 | 21.11 | 0.00781795 | 48.9452 | 5902.10 | 0.00 | 6362.64 | 6362.64 | 0.30641819 | 16.60 | 12.97 | 0.00781795 | 36473.8 | 36.97 | 20.13 | 0.00781795 | 57238.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11496.759 | 11496.759 | 1.151274 | 0.00010058 | 252.102 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 3.9100 | 3.988668 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11496.76 | 11496.76 | 1.0000 | 1.35134903 | 1.151274 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10056841 | 60.00 | 32.22 | 27.78 | 0.000 | 11496.76 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00789275 | 21.00 | 0.00789275 | 49.7454 | 5572.68 | 0.00 | 11560.37 | 11560.37 | 1.35134903 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.99 | 16.31 | 0.00800000 | 45489.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11872.139 | 11872.139 | 1.200390 | 0.00010386 | 260.066 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 4.0376 | 4.118902 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 11872.14 | 11872.14 | 1.0000 | 1.40900057 | 1.200390 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10385206 | 60.00 | 32.22 | 27.78 | 0.000 | 11872.14 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00789494 | 21.00 | 0.00789494 | 49.7590 | 5695.31 | 0.00 | 11937.84 | 11937.84 | 1.40900057 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.91 | 16.28 | 0.00800000 | 45407.3 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7337.243 | 7337.243 | 1.106517 | 0.00006419 | 155.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 2.4954 | 2.545572 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7337.24 | 7337.24 | 1.0000 | 1.29881365 | 1.106517 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06418285 | 60.00 | 32.22 | 27.78 | 0.000 | 7337.24 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.38 | 0.00675572 | 21.00 | 0.00675572 | 42.6618 | 1658.17 | 0.00 | 7378.26 | 7378.26 | 1.29881365 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.17 | 15.29 | 0.00800000 | 42615.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8327.070 | 8327.070 | 0.471459 | 0.00007285 | 199.101 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 2.8320 | 2.888981 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8327.07 | 8327.07 | 1.0000 | 0.55339170 | 0.471459 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07284141 | 60.00 | 32.22 | 27.78 | 0.000 | 8327.07 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00791040 | 21.00 | 0.00791040 | 49.8552 | 5901.01 | 0.00 | 8370.67 | 8370.67 | 0.55339170 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.43 | 18.51 | 0.00800000 | 52060.9 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 703847.631 | -999.000 | 24.956564 | 0.02012995 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2287 | 1004.8586 | 1.1738 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.956564 | 29.29365157 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 69.4325 | 69.432510 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | Sensible | 703847.63 | 639278.99 | 1.0000 | 29.29365157 | 24.956564 | 32.43 | 19.59 | 0.00935403 | 56546.0 | 11.03 | 11.03 | 0.00850000 | 32518.7 | 20.12789970 | 6.70 | 15.03 | 8.33 | 52912.262 | 650935.37 | 42.00 | 0.00915790 | 22.26 | 11.66146000 | 46.7270 | 23.99 | 0.00952705 | 23.99 | 0.00947585 | 49.6665 | 333581.86 | 0.00 | 715070.71 | 630280.56 | 29.29365157 | 32.43 | 19.88 | 0.00935403 | 56546.0 | 11.38 | 11.21 | 0.00820638 | 32135.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 91840.249 | 91840.249 | 7.486969 | 0.00080346 | 1674.524 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.956564 | 29.29365157 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 31.2343 | 31.862916 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 91840.25 | 91840.25 | 1.0000 | 8.78809547 | 7.486969 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.80337661 | 60.00 | 32.22 | 27.78 | 0.000 | 91840.25 | 6.30 | 0.00607234 | 6.30 | 11.66146000 | 155.7568 | 20.97 | 0.00765506 | 21.02 | 0.00783621 | 49.3423 | 58555.83 | 0.00 | 96384.05 | 96384.05 | 8.78809547 | 2.80 | 2.80 | 0.00607234 | 18031.7 | 13.59 | 9.91 | 0.00607234 | 28999.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 78036.984 | -999.000 | 2.051317 | 0.00223185 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8641 | 1004.8586 | 1.1738 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40772169 | 4197.9300 | 999.8980 | 28.98915746 | 15.03 | 6.70 | 8.33 | 1013714.80 | 7.6981 | 7.698120 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | Sensible | 78036.98 | 74039.07 | 1.0000 | 2.40780635 | 2.051317 | 42.00 | 22.26 | 0.00915790 | 65821.7 | 11.91 | 11.50 | 0.00850000 | 33411.7 | 2.23162021 | 6.70 | 15.03 | 8.33 | 2195.006 | 75841.98 | 42.00 | 0.00915790 | 22.26 | 2.05124512 | 99.9965 | 21.11 | 0.00860259 | 21.11 | 0.00860619 | 53.8133 | 208231.56 | 0.00 | 79029.81 | 74008.48 | 2.40780635 | 42.00 | 22.57 | 0.00915790 | 65821.7 | 11.92 | 11.56 | 0.00833137 | 32999.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 7548.855 | 7548.855 | 0.615395 | 0.00006604 | 137.638 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40772169 | 4197.9300 | 999.8980 | 2.52135306 | 54.44 | 82.22 | 27.78 | 294036.40 | 2.5673 | 2.618988 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 7548.86 | 7548.86 | 1.0000 | 0.72234190 | 0.615395 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.06603394 | 60.00 | 32.22 | 27.78 | 0.000 | 7548.86 | 6.30 | 0.00607234 | 6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00778699 | 21.11 | 0.00778773 | 48.7581 | 69914.00 | 0.00 | 7922.34 | 7922.34 | 0.72234190 | 2.80 | 2.80 | 0.00607234 | 18031.7 | 13.59 | 9.91 | 0.00607234 | 28999.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5312.67 | 1508.17 | 26.33 |
RETAIL_1_FLR_1 | 5674.67 | 2795.33 | 236.50 |
RETAIL_2_FLR_1 | 5498.17 | 3088.33 | 482.17 |
MECH_FLR_1 | 4196.33 | 3936.50 | 0.00 |
STORAGE_FLR_1 | 4061.83 | 4018.50 | 0.00 |
LAUNDRY_FLR_1 | 8464.67 | 4774.00 | 4672.50 |
CAFE_FLR_1 | 7109.83 | 3938.50 | 2780.33 |
LOBBY_FLR_1 | 6280.33 | 4009.83 | 2225.50 |
ROOM_1_FLR_3 | 112.50 | 7649.50 | 8.33 |
ROOM_2_FLR_3 | 121.67 | 7771.67 | 35.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 14.17 | 8760.00 | 14.17 |
ROOM_5_FLR_3 | 24.67 | 7520.67 | 7.17 |
ROOM_6_FLR_3 | 86.50 | 7560.33 | 28.50 |
CORRIDOR_FLR_3 | 4231.67 | 4701.17 | 1033.17 |
ROOM_1_FLR_6 | 675.00 | 7245.17 | 36.50 |
ROOM_2_FLR_6 | 649.00 | 7409.67 | 138.83 |
ROOM_3_MULT9_FLR_6 | 222.50 | 7220.67 | 4.00 |
BANQUET_FLR_6 | 7384.83 | 3139.83 | 2478.67 |
DINING_FLR_6 | 7886.50 | 2532.83 | 2259.50 |
KITCHEN_FLR_6 | 8641.50 | 7094.67 | 7074.00 |
CORRIDOR_FLR_6 | 4533.33 | 3585.17 | 0.00 |
Facility | 8734.67 | 8760.00 | 7914.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 21.00 | 0.00 | 21.00 |
ROOM_2_FLR_3 | 0.00 | 14.00 | 0.00 | 14.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_5_FLR_3 | 0.00 | 10.50 | 0.00 | 10.50 |
ROOM_6_FLR_3 | 0.00 | 15.00 | 0.00 | 15.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 45.17 | 0.00 | 45.17 |
ROOM_2_FLR_6 | 0.00 | 35.00 | 0.00 | 35.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 28.50 | 0.00 | 28.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 63.17 | 0.00 | 63.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.946 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.406 | 0.132 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.457 | 0.044 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.795 | 0.049 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.741 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 16.868 | 0.141 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 3.263 | 0.104 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.573 | 0.043 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.169 | 0.000 | 0.033 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.359 | 0.169 | 0.000 | 0.036 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.407 | 0.075 | 0.000 | 0.055 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.169 | 0.000 | 0.033 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.359 | 0.169 | 0.000 | 0.036 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.555 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.359 | 0.169 | 0.000 | 0.035 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.359 | 0.170 | 0.000 | 0.038 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.407 | 0.138 | 0.000 | 0.056 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.125 | 0.049 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.398 | 0.049 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.005 | 0.141 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.155 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.513 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.340 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.941 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.458 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.431 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 8.488 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 2.556 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.142 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.297 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.344 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.502 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 7.470 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.652 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38736486.36 | 0.00 | 38736486.36 | 0.00 | 38736486.36 | 26946214.98 | 759.03 | 120.10 | 7880.87 | 0.00 |
RETAIL_1_FLR_1 | 5433237.78 | 0.00 | 5433237.78 | 296896.43 | 5730134.21 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3805368.40 | 0.00 | 3805368.40 | 114602.40 | 3919970.80 | 2892943.94 | 114.90 | 106.90 | 8538.20 | 0.00 |
MECH_FLR_1 | 4405316.50 | 0.00 | 4405316.50 | 270851.99 | 4676168.49 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2367507.52 | 0.00 | 2367507.52 | 156266.68 | 2523774.19 | 1821682.01 | 1129.74 | 170.56 | 7459.70 | 0.00 |
LAUNDRY_FLR_1 | 44332815.83 | 0.00 | 44332815.83 | 369834.55 | 44702650.38 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 20691018.28 | 0.00 | 20691018.28 | 656306.37 | 21347324.65 | 21330615.53 | 5932.78 | 136.11 | 2691.11 | 0.00 |
LOBBY_FLR_1 | 69093310.86 | 0.00 | 69093310.86 | 1875217.21 | 70968528.08 | 59728886.00 | 653.01 | 479.41 | 7627.58 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 33497.89 | 1493654.60 | 172326.58 | 1665981.18 | 1946875.62 | 2190.00 | 5952.50 | 617.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 36544.01 | 1496529.65 | 172313.44 | 1668843.08 | 1946647.51 | 2190.00 | 5951.82 | 618.18 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 761.01 | 1100672.98 | 48081.05 | 1148754.03 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 375.33 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 35397.65 | 19839226.95 | 48094.20 | 19887321.15 | 26405105.73 | 2190.00 | 6085.51 | 484.49 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 33639.17 | 1493795.88 | 172326.58 | 1666122.47 | 1946875.62 | 2190.00 | 5952.50 | 617.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 36256.55 | 1496242.18 | 172313.44 | 1668555.62 | 1946647.51 | 2190.00 | 5951.58 | 618.42 | 0.00 |
CORRIDOR_FLR_3 | 22385148.38 | 0.00 | 22385148.38 | 208377.51 | 22593525.89 | 14972100.18 | 163.81 | 56.78 | 8539.41 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 35470.49 | 400509.67 | 172361.03 | 572870.69 | 486718.90 | 2127.33 | 5958.10 | 674.57 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 38534.40 | 403530.81 | 172347.88 | 575878.68 | 486661.88 | 2126.83 | 5958.36 | 674.81 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 35852.94 | 2381043.25 | 88185.93 | 2469229.19 | 3126920.42 | 2190.00 | 5953.71 | 616.29 | 0.00 |
BANQUET_FLR_6 | 35289413.13 | 0.00 | 35289413.13 | 420862.31 | 35710275.43 | 37458366.31 | 6982.43 | 496.78 | 1280.79 | 0.00 |
DINING_FLR_6 | 37626219.91 | 0.00 | 37626219.91 | 420862.31 | 38047082.22 | 37458366.31 | 3559.78 | 371.02 | 4829.20 | 0.00 |
KITCHEN_FLR_6 | 48024594.12 | 0.00 | 48024594.12 | 376769.34 | 48401363.46 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12343804.71 | 0.00 | 12343804.71 | 368760.81 | 12712565.51 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.20E+10 | 3704490.06 | 0.20E+10 | 17365561.60 | 0.21E+10 | 0.43E+10 | 8760.00 | 6840.32 | 8760.00 | 375.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2283 | 0.0000 | 1.2283 | 0.0000 | 1.2283 | 0.8545 | 759.03 | 120.10 | 7880.87 |
RETAIL_1_FLR_1 | 0.1723 | 0.0000 | 0.1723 | 0.0094 | 0.1817 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1207 | 0.0000 | 0.1207 | 0.0036 | 0.1243 | 0.0917 | 114.90 | 106.90 | 8538.20 |
MECH_FLR_1 | 0.1397 | 0.0000 | 0.1397 | 0.0086 | 0.1483 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0751 | 0.0000 | 0.0751 | 0.0050 | 0.0800 | 0.0578 | 1129.74 | 170.56 | 7459.70 |
LAUNDRY_FLR_1 | 1.4058 | 0.0000 | 1.4058 | 0.0117 | 1.4175 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6561 | 0.0000 | 0.6561 | 0.0208 | 0.6769 | 0.6764 | 5932.78 | 136.11 | 2691.11 |
LOBBY_FLR_1 | 2.1909 | 0.0000 | 2.1909 | 0.0595 | 2.2504 | 1.8940 | 653.01 | 479.41 | 7627.58 |
ROOM_1_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0055 | 0.0528 | 0.0617 | 2190.00 | 5952.50 | 617.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0012 | 0.0475 | 0.0055 | 0.0529 | 0.0617 | 2190.00 | 5951.82 | 618.18 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0011 | 0.6291 | 0.0015 | 0.6306 | 0.8373 | 2190.00 | 6085.51 | 484.49 |
ROOM_5_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0055 | 0.0528 | 0.0617 | 2190.00 | 5952.50 | 617.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0055 | 0.0529 | 0.0617 | 2190.00 | 5951.58 | 618.42 |
CORRIDOR_FLR_3 | 0.7098 | 0.0000 | 0.7098 | 0.0066 | 0.7164 | 0.4748 | 163.81 | 56.78 | 8539.41 |
ROOM_1_FLR_6 | 0.0116 | 0.0011 | 0.0127 | 0.0055 | 0.0182 | 0.0154 | 2127.33 | 5958.10 | 674.57 |
ROOM_2_FLR_6 | 0.0116 | 0.0012 | 0.0128 | 0.0055 | 0.0183 | 0.0154 | 2126.83 | 5958.36 | 674.81 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0011 | 0.0755 | 0.0028 | 0.0783 | 0.0992 | 2190.00 | 5953.71 | 616.29 |
BANQUET_FLR_6 | 1.1190 | 0.0000 | 1.1190 | 0.0133 | 1.1324 | 1.1878 | 6982.43 | 496.78 | 1280.79 |
DINING_FLR_6 | 1.1931 | 0.0000 | 1.1931 | 0.0133 | 1.2065 | 1.1878 | 3559.78 | 371.02 | 4829.20 |
KITCHEN_FLR_6 | 1.5228 | 0.0000 | 1.5228 | 0.0119 | 1.5348 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3914 | 0.0000 | 0.3914 | 0.0117 | 0.4031 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 62.2139 | 0.1156 | 62.3296 | 0.4348 | 62.7644 | 73.9670 | 8760.00 | 6840.32 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.47E+09 | 0.00 | 0.47E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 41084139.42 | 285954.10 | 41370093.52 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.0523 | 0.0000 | 15.0523 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3028 | 0.0091 | 1.3118 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 15.0523 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6456 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
Electricity:Building | 2448.73 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.64 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.46 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.46 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.46 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.46 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.79 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.45 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.45 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.27 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.28 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.28 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.84 | 1146.97 | 20-DEC-23:30 | 3265.65 | 29-SEP-06:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 3398.96 | 2614.41 | 01-FEB-02:20 | 296898.18 | 10-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.57 | 0.00 | 01-JAN-11:10 | 1895.94 | 04-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 35.18 | 998.55 | 30-DEC-04:10 | 1204.32 | 09-SEP-13:10 |
Fans:Electricity | 584.85 | 10020.68 | 01-JAN-08:10 | 49575.79 | 07-JUL-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 901.66 | 19216.56 | 16-JAN-15:00 | 60348.25 | 07-JUL-21:20 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
ElectricityPurchased:Plant | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
Cogeneration:ElectricityPurchased | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
General:Cogeneration:ElectricityPurchased | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
ElectricityNet:Plant | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
Cogeneration:ElectricityNet | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
General:Cogeneration:ElectricityNet | 7562.36 | 76724.16 | 01-FEB-02:20 | 523992.11 | 09-JUN-19:20 |
General:Fans:Electricity | 584.85 | 10020.68 | 01-JAN-08:10 | 49575.79 | 07-JUL-21:20 |
ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 295.04 | 8417.13 | 01-JAN-08:10 | 9938.94 | 07-MAR-10:00 |
General:HeatRecovery:Electricity | 295.04 | 8417.13 | 01-JAN-08:10 | 9938.94 | 07-MAR-10:00 |
WaterSystems:Electricity | 90.74 | 1086.56 | 04-APR-00:50 | 4738.76 | 01-JUN-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 04-APR-00:50 | 4738.76 | 01-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3137.73 | 0.00 | 01-JAN-00:10 | 285144.78 | 10-JUN-18:10 |
General:Cooling:Electricity | 3137.73 | 0.00 | 01-JAN-00:10 | 285144.78 | 10-JUN-18:10 |
Pumps:Electricity | 114.73 | 57.09 | 15-JAN-18:30 | 5554.72 | 05-JUL-18:30 |
General:Pumps:Electricity | 114.73 | 57.09 | 15-JAN-18:30 | 5554.72 | 05-JUL-18:30 |
WIRED_LTG_ELECTRICITY | 27.58 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4344.56 | 29270.80 | 09-FEB-02:30 | 347787.78 | 10-FEB-18:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2555.72 | 15908.90 | 10-MAR-11:10 | 261862.47 | 01-JAN-19:10 |
WaterSystems:NaturalGas | 2524.21 | 15908.90 | 01-JAN-16:10 | 243742.46 | 24-JAN-21:30 |
Water Heater:WaterSystems:NaturalGas | 2524.21 | 15908.90 | 01-JAN-16:10 | 243742.46 | 24-JAN-21:30 |
Heating:NaturalGas | 31.50 | 0.00 | 05-JAN-18:10 | 43284.75 | 02-JAN-09:10 |
Boiler:Heating:NaturalGas | 31.50 | 0.00 | 05-JAN-18:10 | 43284.75 | 02-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 9382.08 | 0.00 | 01-JAN-00:10 | 783669.74 | 01-JUL-18:30 |
PlantLoopCoolingDemand:HVAC | 9382.08 | 0.00 | 01-JAN-00:10 | 783669.74 | 01-JUL-18:30 |
CoolingCoils:PlantLoopCoolingDemand | 9382.08 | 0.00 | 01-JAN-00:10 | 783669.74 | 01-JUL-18:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 06-FEB-21:40 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 41798.67 | 124610.55 | 15-JAN-15:00 | 3344602.51 | 01-JUL-18:10 |
EnergyTransfer:Building | 6795.57 | 92854.26 | 02-JAN-11:10 | 440642.20 | 12-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 756.81 | 10850.73 | 31-DEC-04:00 | 37722.40 | 04-MAY-10:50 |
Refrigeration:EnergyTransfer | 188.33 | 4207.67 | 20-DEC-23:20 | 10383.53 | 29-SEP-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.17 | 2103.84 | 20-DEC-23:20 | 5191.76 | 29-SEP-06:50 |
General:Refrigeration:EnergyTransfer | 94.17 | 2103.84 | 20-DEC-23:20 | 5191.76 | 29-SEP-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.17 | 2103.84 | 20-DEC-23:20 | 5191.76 | 29-SEP-06:50 |
EnergyTransfer:Plant | 22726.56 | 15547.88 | 01-FEB-02:20 | 1872126.15 | 01-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.73 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 72.44 | 1945.65 | 30-DEC-04:10 | 2562.95 | 09-SEP-13:10 |
EnergyTransfer:Zone:BASEMENT | 538.64 | 11873.26 | 01-JAN-16:00 | 28756.72 | 08-AUG-21:00 |
Heating:EnergyTransfer | 6.12 | 0.00 | 01-JAN-08:40 | 14694.47 | 16-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 6.12 | 0.00 | 01-JAN-08:40 | 14694.47 | 16-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6695.28 | 83501.22 | 01-JAN-06:00 | 437034.44 | 12-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 538.64 | 11873.26 | 01-JAN-16:00 | 28756.72 | 08-AUG-21:00 |
General:Cooling:EnergyTransfer | 6695.28 | 83501.22 | 01-JAN-06:00 | 437034.44 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 538.64 | 11873.26 | 01-JAN-16:00 | 28756.72 | 08-AUG-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.40 | 1.52 | 23-DEC-07:30 | 4938.50 | 04-MAY-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 351.76 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 351.76 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.39 | 0.00 | 01-JAN-03:00 | 4938.50 | 04-MAY-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.39 | 0.00 | 01-JAN-03:00 | 4938.50 | 04-MAY-18:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 51.79 | 696.63 | 02-JAN-10:30 | 3495.87 | 12-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 51.79 | 696.63 | 02-JAN-10:30 | 3495.87 | 12-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 51.79 | 696.63 | 02-JAN-10:30 | 3495.87 | 12-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 55.56 | 1.35 | 02-JAN-10:30 | 4188.33 | 12-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 6.20 | 02-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 6.20 | 02-JAN-10:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 55.56 | 0.00 | 02-JAN-10:40 | 4188.33 | 12-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 55.56 | 0.00 | 02-JAN-10:40 | 4188.33 | 12-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 29.71 | 35.65 | 02-JAN-10:10 | 2084.46 | 12-JUN-19:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 29.71 | 35.65 | 02-JAN-10:10 | 2084.46 | 12-JUN-19:50 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 29.71 | 35.65 | 02-JAN-10:10 | 2084.46 | 12-JUN-19:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 599.39 | 9246.62 | 02-JAN-05:00 | 39192.29 | 12-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 599.39 | 9246.62 | 02-JAN-05:00 | 39192.29 | 12-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 599.39 | 9246.62 | 02-JAN-05:00 | 39192.29 | 12-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 288.42 | 2984.31 | 10-FEB-10:20 | 15713.88 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 288.42 | 2984.31 | 10-FEB-10:20 | 15713.88 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 288.42 | 2984.31 | 10-FEB-10:20 | 15713.88 | 12-JUN-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 963.41 | 17116.87 | 02-JAN-10:30 | 55868.64 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 963.41 | 17116.87 | 02-JAN-10:30 | 55868.64 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 963.41 | 17116.87 | 02-JAN-10:30 | 55868.64 | 12-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 110.12 | 0.00 | 01-JAN-08:10 | 11829.14 | 04-MAY-16:40 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.57 | 0.00 | 01-JAN-08:10 | 1569.72 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.57 | 0.00 | 01-JAN-08:10 | 1569.72 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 109.55 | 0.00 | 01-JAN-00:10 | 11829.14 | 04-MAY-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 109.55 | 0.00 | 01-JAN-00:10 | 11829.14 | 04-MAY-16:40 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 96.81 | 0.00 | 01-JAN-08:10 | 11847.73 | 10-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.21 | 0.00 | 01-JAN-08:10 | 2391.86 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.21 | 0.00 | 01-JAN-08:10 | 2391.86 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 95.60 | 0.00 | 01-JAN-00:10 | 11847.73 | 10-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 95.60 | 0.00 | 01-JAN-00:10 | 11847.73 | 10-JUN-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.36 | 0.00 | 01-JAN-00:10 | 44743.04 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.36 | 0.00 | 01-JAN-00:10 | 44743.04 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.36 | 0.00 | 01-JAN-00:10 | 44743.04 | 02-OCT-13:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 727.39 | 0.00 | 01-JAN-08:10 | 81718.24 | 12-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.75 | 0.00 | 01-JAN-00:10 | 8136.67 | 16-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.75 | 0.00 | 01-JAN-00:10 | 8136.67 | 16-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 726.65 | 0.00 | 01-JAN-08:10 | 81718.24 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 726.65 | 0.00 | 01-JAN-08:10 | 81718.24 | 12-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 109.86 | 0.00 | 01-JAN-08:10 | 10885.94 | 04-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.56 | 0.00 | 01-JAN-08:10 | 1396.36 | 01-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.56 | 0.00 | 01-JAN-08:10 | 1396.36 | 01-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 109.30 | 0.00 | 01-JAN-00:10 | 10885.94 | 04-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 109.30 | 0.00 | 01-JAN-00:10 | 10885.94 | 04-MAY-15:20 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 96.45 | 0.00 | 01-JAN-08:10 | 10650.33 | 04-MAY-08:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.18 | 0.00 | 01-JAN-08:10 | 1814.82 | 03-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.18 | 0.00 | 01-JAN-08:10 | 1814.82 | 03-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 95.27 | 0.00 | 01-JAN-00:10 | 10650.33 | 04-MAY-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 95.27 | 0.00 | 01-JAN-00:10 | 10650.33 | 04-MAY-08:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 285.49 | 1149.75 | 02-JAN-09:10 | 17725.60 | 07-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 285.49 | 1149.75 | 02-JAN-09:10 | 17725.60 | 07-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 285.49 | 1149.75 | 02-JAN-09:10 | 17725.60 | 07-JUN-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 28.23 | 0.00 | 01-JAN-08:10 | 3494.37 | 09-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.54 | 0.00 | 01-JAN-08:10 | 674.91 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.54 | 0.00 | 01-JAN-08:10 | 674.91 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 27.70 | 0.00 | 01-JAN-00:10 | 3494.37 | 09-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 27.70 | 0.00 | 01-JAN-00:10 | 3494.37 | 09-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 25.03 | 0.00 | 01-JAN-08:10 | 3497.89 | 10-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.82 | 0.00 | 01-JAN-08:10 | 891.18 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.82 | 0.00 | 01-JAN-08:10 | 891.18 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.21 | 0.00 | 01-JAN-00:10 | 3497.89 | 10-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.21 | 0.00 | 01-JAN-00:10 | 3497.89 | 10-JUN-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 165.52 | 0.00 | 01-JAN-08:10 | 16687.65 | 03-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.46 | 0.00 | 01-JAN-00:10 | 1943.41 | 11-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.46 | 0.00 | 01-JAN-00:10 | 1943.41 | 11-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 165.06 | 0.00 | 01-JAN-00:20 | 16687.65 | 03-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 165.06 | 0.00 | 01-JAN-00:20 | 16687.65 | 03-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 506.90 | 8936.75 | 02-JAN-10:10 | 27251.54 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 506.90 | 8936.75 | 02-JAN-10:10 | 27251.54 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 506.90 | 8936.75 | 02-JAN-10:10 | 27251.54 | 12-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 541.09 | 9883.04 | 02-JAN-10:10 | 28446.90 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 541.09 | 9883.04 | 02-JAN-10:10 | 28446.90 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 541.09 | 9883.04 | 02-JAN-10:10 | 28446.90 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 662.64 | 8627.66 | 01-JAN-04:00 | 32656.27 | 04-MAY-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 662.64 | 8627.66 | 01-JAN-04:00 | 32656.27 | 04-MAY-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 154.18 | 0.56 | 02-JAN-04:40 | 11113.29 | 04-MAY-15:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 633.39 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 633.39 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 154.16 | 0.00 | 01-JAN-03:20 | 11113.29 | 04-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 154.16 | 0.00 | 01-JAN-03:20 | 11113.29 | 04-MAY-15:20 |
PlantLoopHeatingDemand:Facility | 549.11 | 5342.44 | 22-JUL-01:00 | 63519.63 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 529.75 | 5342.44 | 22-JUL-01:00 | 43452.83 | 18-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 529.75 | 5342.44 | 22-JUL-01:00 | 43452.83 | 18-JAN-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 529.75 | 5342.44 | 22-JUL-01:00 | 43452.83 | 18-JAN-08:00 |
EnergyTransfer:HVAC | 12276.54 | 2586.83 | 15-JAN-14:50 | 1087255.64 | 01-JUL-18:10 |
HeatingCoils:EnergyTransfer | 19.36 | 0.00 | 05-JAN-18:10 | 26085.12 | 01-JAN-00:10 |
PlantLoopHeatingDemand:HVAC | 19.36 | 0.00 | 05-JAN-18:10 | 26085.12 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 19.36 | 0.00 | 05-JAN-18:10 | 26085.12 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 9382.08 | 0.00 | 01-JAN-00:10 | 783669.74 | 01-JUL-18:30 |
HeatRecoveryForHeating:EnergyTransfer | 319.26 | 0.00 | 01-JAN-13:00 | 216664.87 | 05-JAN-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 2555.85 | 0.00 | 01-JAN-00:10 | 347570.81 | 25-AUG-10:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 529.75 | 5342.44 | 22-JUL-01:00 | 43452.83 | 18-JAN-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 529.75 | 5342.44 | 22-JUL-01:00 | 43452.83 | 18-JAN-08:00 |
Boilers:EnergyTransfer | 19.12 | 0.00 | 05-JAN-18:10 | 29745.22 | 02-JAN-09:10 |
Chillers:EnergyTransfer | 9472.89 | 0.00 | 01-JAN-00:10 | 787144.39 | 01-JUL-18:10 |
HeatRejection:EnergyTransfer | 12610.63 | 0.00 | 01-JAN-00:10 | 1064114.12 | 01-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 12610.63 | 0.00 | 01-JAN-00:10 | 1064114.12 | 01-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -538.645 | 0.000 | 0.000 | 134.812 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 99.434 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.008 | -70.394 | 0.000 | 0.000 | 14.323 | 7.307 | 10.186 | 24.978 | 0.000 | 1.391 | 17.999 | 0.000 | -4.903 | 0.000 | -0.894 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -51.794 | 0.000 | 0.000 | 16.208 | 8.462 | 11.795 | 0.000 | 0.000 | 0.541 | 15.170 | 0.000 | 0.000 | 0.000 | -0.383 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -55.557 | 0.000 | 0.000 | 3.537 | 8.366 | 12.471 | 0.000 | 0.000 | 1.309 | 30.648 | 0.000 | 0.000 | 0.000 | -0.775 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -29.712 | 0.000 | 0.000 | 2.722 | 3.079 | 3.598 | 0.000 | 0.000 | 0.755 | 20.005 | 0.000 | 0.000 | 0.000 | -0.447 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -599.397 | 0.000 | 0.000 | 10.932 | 3.975 | 658.131 | 0.000 | 0.000 | 1.787 | 0.000 | 0.000 | 0.000 | 0.000 | -1.300 | -74.129 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -288.420 | 0.000 | 0.000 | 181.586 | 14.451 | 14.341 | 69.785 | 0.000 | 3.052 | 22.462 | 0.000 | -14.923 | 0.000 | -2.334 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -963.417 | 0.000 | 0.000 | 538.869 | 110.275 | 148.998 | 93.797 | 0.000 | 8.770 | 88.763 | 0.000 | -19.404 | 0.000 | -6.653 | -0.001 |
ROOM_1_FLR_3 | 1.260 | -96.817 | 0.000 | -13.417 | 0.000 | 0.000 | 9.636 | 9.244 | 10.478 | 56.392 | 0.000 | 4.279 | 31.002 | 0.000 | -9.771 | 0.000 | -2.286 | -0.001 |
ROOM_2_FLR_3 | 2.301 | -82.988 | 0.000 | -13.695 | 0.000 | 0.000 | 9.576 | 9.243 | 10.477 | 46.274 | 0.000 | 4.221 | 27.174 | 0.000 | -10.092 | 0.000 | -2.491 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -576.501 | 0.000 | -17.853 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 273.643 | 0.000 | 10.509 | 114.603 | 0.000 | -89.535 | 0.000 | -20.247 | -0.001 |
ROOM_4_MULT19_FLR_3 | 3.299 | -544.581 | 0.000 | -184.586 | 0.000 | 0.000 | 182.325 | 110.415 | 195.050 | 183.788 | 0.000 | 22.875 | 104.884 | 0.000 | -52.947 | 0.000 | -20.522 | -0.000 |
ROOM_5_FLR_3 | 1.239 | -96.553 | 0.000 | -13.417 | 0.000 | 0.000 | 9.632 | 9.244 | 10.478 | 56.119 | 0.000 | 4.278 | 30.679 | 0.000 | -9.392 | 0.000 | -2.308 | -0.002 |
ROOM_6_FLR_3 | 2.209 | -82.603 | 0.000 | -13.699 | 0.000 | 0.000 | 9.575 | 9.243 | 10.477 | 45.700 | 0.000 | 4.219 | 26.804 | 0.000 | -9.431 | 0.000 | -2.494 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -285.495 | 0.000 | 0.000 | 110.763 | 91.336 | 0.000 | 54.800 | 0.000 | 3.950 | 40.211 | 0.000 | -13.046 | 0.000 | -2.519 | -0.001 |
ROOM_1_FLR_6 | 0.849 | -24.652 | 0.000 | -3.358 | 0.000 | 0.000 | 2.410 | 2.311 | 2.620 | 14.003 | 0.000 | 1.063 | 7.687 | 0.000 | -2.354 | 0.000 | -0.577 | -0.000 |
ROOM_2_FLR_6 | 1.201 | -21.162 | 0.000 | -3.422 | 0.000 | 0.000 | 2.395 | 2.311 | 2.619 | 11.507 | 0.000 | 1.048 | 6.575 | 0.000 | -2.442 | 0.000 | -0.630 | -0.000 |
ROOM_3_MULT9_FLR_6 | 1.234 | -144.248 | 0.000 | -21.574 | 0.000 | 0.000 | 21.663 | 13.076 | 23.098 | 72.126 | 0.000 | 4.946 | 43.787 | 0.000 | -10.851 | 0.000 | -3.257 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -506.902 | 0.000 | 0.000 | 315.101 | 31.150 | 175.857 | 17.026 | 0.000 | 1.913 | 0.000 | 0.000 | -8.132 | 0.000 | -1.601 | -24.412 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -541.101 | 0.000 | 0.000 | 314.600 | 31.150 | 175.857 | 16.672 | 0.000 | 1.909 | 10.956 | 0.000 | -8.423 | 0.000 | -1.621 | -0.001 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -662.632 | 0.000 | 0.000 | 28.099 | 12.972 | 550.372 | 24.627 | 0.000 | 1.709 | 52.637 | 0.000 | -6.332 | 0.000 | -1.452 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.015 | -154.163 | 0.000 | 0.000 | 29.570 | 24.166 | 0.000 | 25.251 | 0.000 | 1.725 | 80.260 | 0.000 | -5.757 | 0.000 | -1.069 | -0.001 |
Total Facility | 13.591 | -1670.107 | 0.023 | -5032.651 | 0.000 | 0.000 | 1948.336 | 783.458 | 2365.005 | 1086.488 | 0.000 | 86.251 | 871.741 | 0.000 | -277.736 | 0.000 | -75.858 | -98.556 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-AUG-21:00 | 0.00 | 0.00 | 0.00 | -28758.12 | 0.00 | 0.00 | 5924.40 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 1983.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 | -4939.97 | 0.00 | 0.00 | 527.11 | 531.19 | 649.52 | 785.27 | 0.00 | 173.92 | 2272.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 12-JUN-20:10 | 0.00 | 0.00 | 0.00 | -3496.38 | 0.00 | 0.00 | 697.61 | 615.12 | 752.15 | 0.00 | 0.00 | 59.56 | 1371.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-JUN-20:00 | 0.00 | 0.00 | 0.00 | -4188.50 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 143.21 | 2392.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 12-JUN-19:50 | 0.00 | 0.00 | 0.00 | -2084.55 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 84.50 | 1406.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 12-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39193.33 | 0.00 | 0.00 | 408.87 | 325.08 | 44299.38 | 0.00 | 0.00 | 195.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6035.55 |
CAFE_FLR_1 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -15718.79 | 0.00 | 0.00 | 8907.85 | 1134.35 | 711.25 | 1397.59 | 0.00 | 307.89 | 3259.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -55881.41 | 0.00 | 0.00 | 26439.92 | 6336.53 | 7389.94 | 1919.88 | 0.00 | 879.56 | 12915.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 20-DEC-16:01 | 0.00 | -13935.89 | 0.00 | -632.98 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 3933.10 | 0.00 | 0.00 | 10303.09 | 0.00 | -0.00 | 0.00 | -302.01 | 0.00 |
ROOM_2_FLR_3 | 20-DEC-16:01 | 0.00 | -13435.89 | 0.00 | -591.56 | 0.00 | 0.00 | 242.83 | 199.20 | 200.16 | 2935.72 | 0.00 | 0.00 | 10686.70 | 0.00 | -0.00 | 0.00 | -237.16 | 0.00 |
ROOM_3_MULT19_FLR_3 | 02-OCT-13:40 | 0.00 | -44741.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 44039.37 | 0.00 | 1297.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5326.94 |
ROOM_4_MULT19_FLR_3 | 03-SEP-08:61 | 0.00 | -92870.18 | 0.00 | -9964.99 | 0.00 | 0.00 | 2483.52 | 4759.18 | 12159.85 | 6931.69 | 0.00 | 598.35 | 75902.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 20-DEC-16:01 | 0.00 | -12645.04 | 0.00 | -633.71 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 947.72 | 0.00 | 0.00 | 11999.24 | 0.00 | -0.00 | 0.00 | -302.90 | 0.00 |
ROOM_6_FLR_3 | 07-APR-08:51 | 0.00 | -13259.29 | 0.00 | -885.12 | 0.00 | 0.00 | 74.90 | 313.04 | 452.99 | 6960.38 | 0.00 | 18.92 | 6324.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 07-JUN-18:13 | 0.00 | 0.00 | 0.00 | -17727.25 | 0.00 | 0.00 | 4080.26 | 6639.35 | 0.00 | 3075.91 | 0.00 | 530.90 | 3400.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-DEC-16:01 | 0.00 | -3881.03 | 0.00 | -157.73 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 955.58 | 0.00 | 0.00 | 3003.22 | 0.00 | -0.00 | 0.00 | -78.71 | 0.00 |
ROOM_2_FLR_6 | 20-DEC-16:01 | 0.00 | -3828.52 | 0.00 | -154.55 | 0.00 | 0.00 | 58.82 | 49.80 | 50.04 | 708.42 | 0.00 | 0.00 | 3190.42 | 0.00 | -0.00 | 0.00 | -74.43 | 0.00 |
ROOM_3_MULT9_FLR_6 | 31-DEC-16:01 | 0.00 | -18470.81 | 0.00 | -827.00 | 0.00 | 0.00 | 294.11 | 332.11 | 487.74 | 2501.84 | 0.00 | 0.00 | 15946.76 | 0.00 | -0.00 | 0.00 | -264.75 | 0.00 |
BANQUET_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -27260.81 | 0.00 | 0.00 | 15644.41 | 1992.02 | 6747.90 | 741.22 | 0.00 | 195.89 | 1939.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -28456.87 | 0.00 | 0.00 | 15644.34 | 1992.02 | 6747.90 | 727.03 | 0.00 | 195.89 | 3149.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 04-MAY-10:50 | 0.00 | 0.00 | 0.00 | -32659.01 | 0.00 | 0.00 | 305.73 | 294.67 | 24259.91 | 3343.34 | 0.00 | 219.03 | 4236.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-MAY-15:13 | 0.00 | 0.00 | 0.00 | -11114.87 | 0.00 | 0.00 | 771.14 | 548.96 | 0.00 | 2117.45 | 0.00 | 240.24 | 7437.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-18:02 | 0.00 | -188141.27 | 0.00 | -266023.18 | 0.00 | 0.00 | 73661.73 | 53578.21 | 120482.43 | 63766.03 | 0.00 | 11184.35 | 131491.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-JAN-07:10 | 0.00 | 0.00 | 351.87 | 0.00 | 0.00 | 0.00 | 358.01 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -854.60 | 0.00 | -174.12 | -446.17 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-10:08 | 0.00 | 0.00 | 6.37 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -119.34 | -430.19 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 20-DEC-19:03 | 4633.83 | 412.00 | 0.00 | -412.00 | 0.00 | 0.00 | 352.08 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1332.57 | 0.00 | -173.79 | -4597.46 |
ROOM_2_FLR_3 | 30-DEC-16:03 | 4645.52 | 408.48 | 0.00 | -408.48 | 0.00 | 0.00 | 139.64 | 234.78 | 221.23 | 1835.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -168.83 | -6907.97 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 31-DEC-19:03 | 25349.63 | 5505.61 | 0.00 | -5505.61 | 0.00 | 0.00 | 5863.06 | 8498.53 | 9021.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8955.28 | 0.00 | -1530.65 | -38247.11 |
ROOM_5_FLR_3 | 20-DEC-19:03 | 4443.42 | 413.28 | 0.00 | -413.28 | 0.00 | 0.00 | 354.75 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1318.91 | 0.00 | -174.27 | -4422.90 |
ROOM_6_FLR_3 | 27-JAN-16:03 | 4440.44 | 446.14 | 0.00 | -446.14 | 0.00 | 0.00 | 252.97 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.29 | 0.00 | -500.89 | -4515.60 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-DEC-19:03 | 1322.96 | 103.69 | 0.00 | -103.69 | 0.00 | 0.00 | 87.76 | 158.32 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -335.12 | 0.00 | -44.12 | -1310.96 |
ROOM_2_FLR_6 | 30-DEC-16:03 | 1417.64 | 102.45 | 0.00 | -102.45 | 0.00 | 0.00 | 34.49 | 58.69 | 55.31 | 442.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.74 | -1965.94 |
ROOM_3_MULT9_FLR_6 | 17-JAN-16:04 | 6348.23 | 817.14 | 0.00 | -817.14 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 464.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -523.25 | -7542.23 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-07:10 | 0.00 | 0.00 | 652.46 | 0.00 | 0.00 | 0.00 | 733.26 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1087.41 | 0.00 | -217.80 | -1178.43 |
Total Facility | 09-FEB-16:05 | -65869.33 | 119508.04 | 0.00 | -119508.04 | 0.00 | 0.00 | 57234.05 | 17004.36 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6744.18 | 0.00 | -15403.36 | -60134.14 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.1078 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.9566 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.5539 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6500 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9940 | 2.9940 | 1.3892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4203 | 0.4203 | 0.1950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3081 | 0.3081 | 0.1429 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3637 | 0.3637 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1983 | 0.1983 | 0.0920 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3607 | 3.3607 | 1.5594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5795 | 1.5795 | 0.7329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4925 | 5.4925 | 2.5485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9216 | 1.9216 | 0.8916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4812 | 2.4812 | 1.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5870 | 2.5870 | 1.2004 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3847 | 2.3847 | 1.1065 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0161 | 1.0161 | 0.4715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.1078 | 24.9566 | 25.1078 | 11.6500 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4970 | 1.4970 | 1.3892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2102 | 0.2102 | 0.1950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1540 | 0.1540 | 0.1429 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1818 | 0.1818 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0991 | 0.0991 | 0.0920 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6804 | 1.6804 | 1.5594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7898 | 0.7898 | 0.7329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7463 | 2.7463 | 2.5485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9608 | 0.9608 | 0.8916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2406 | 1.2406 | 1.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2935 | 1.2935 | 1.2004 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1924 | 1.1924 | 1.1065 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5080 | 0.5080 | 0.4715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.5539 | 11.6500 | 11.6500 | 11.6500 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 63.17 |
Number of hours not met | 63.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 31.50 | 43284.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3137.73 | 285144.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.46 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.98 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 584.85 | 49575.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 114.73 | 5554.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 295.04 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2524.21 | 243742.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.57 | 1895.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 35.18 | 1204.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1721.02 | 7562.36 |
Natural Gas | 1788.84 | 4344.56 |
Additional | 0.00 | 0.00 |
Total | 3509.86 | 11906.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.06 |
Space Heating | 0.00 |
Space Cooling | 276.57 |
Fans (All) | 51.55 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 666.56 |
Subtotal | 666.56 |
Natural Gas [MJ/m2] | |
Space Heating | 2.78 |
Service Water Heating | 222.49 |
Miscellaneous (All) | 382.94 |
Subtotal | 382.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.58 |
Space Heating | 0.26 |
Space Cooling | 26.35 |
Fans (All) | 4.91 |
Service Water Heating | 21.96 |
Receptacle Equipment | 28.95 |
Miscellaneous | 10.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7111.17 | 1648.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7111.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1648.83 | 0.00 | 0.00 | 0.00 |
Average | 8685.05 | 74.95 | 0.00 | 0.00 | 0.00 |
Sum | 191071.17 | 1648.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8678.50 | 81.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 6617.83 | 2142.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7162.67 | 1597.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6423.00 | 2337.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8574.83 | 185.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 6798.50 | 1961.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 6971.83 | 1788.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8394.33 | 365.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6423.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2337.00 | 0.00 | 0.00 | 0.00 |
Average | 8281.88 | 478.12 | 0.00 | 0.00 | 0.00 |
Sum | 182201.33 | 10518.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58271.50 | 884.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 462455.33 | 247961.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1558580.17 | 556848.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4150.33 | 3.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4148.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 97125.00 | 3233.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4148.67 | 5.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 842905.67 | 402809.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 874274.00 | 371441.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 105507.67 | 2761.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1558580.17 | 556848.83 | 0.00 | 0.00 | 0.00 |
Average | 216798.03 | 72089.02 | 0.00 | 0.00 | 0.00 |
Sum | 4769556.67 | 1585958.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362938E+11 | 18741.27 | 13-JAN-22:00 | 17.60 | 13.76 | 0.799340E+10 | 4837.05 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.327462E+11 | 18652.20 | 23-FEB-22:00 | 19.30 | 13.82 | 0.719735E+10 | 4837.08 | 22-FEB-23:10 | 19.30 | 13.82 |
March | 0.369977E+11 | 17684.68 | 14-MAR-21:00 | 25.00 | 17.31 | 0.800136E+10 | 4837.11 | 17-MAR-22:10 | 19.20 | 14.51 |
April | 0.379560E+11 | 19128.39 | 20-APR-21:00 | 31.80 | 19.79 | 0.781445E+10 | 4837.15 | 19-APR-21:19 | 31.80 | 19.79 |
May | 0.430181E+11 | 21916.76 | 05-MAY-21:00 | 36.90 | 18.95 | 0.819300E+10 | 4837.07 | 11-MAY-21:30 | 30.75 | 23.21 |
June | 0.458023E+11 | 24784.45 | 08-JUN-21:00 | 36.10 | 25.84 | 0.797925E+10 | 4837.08 | 15-JUN-21:30 | 30.95 | 24.85 |
July | 0.531735E+11 | 27582.18 | 07-JUL-21:00 | 34.70 | 26.01 | 0.823200E+10 | 4837.10 | 10-JUL-21:30 | 27.40 | 23.56 |
August | 0.568287E+11 | 28756.72 | 08-AUG-21:00 | 32.50 | 27.21 | 0.826731E+10 | 4837.10 | 24-AUG-21:30 | 31.15 | 27.59 |
September | 0.546523E+11 | 28738.76 | 26-SEP-21:00 | 27.30 | 22.85 | 0.797709E+10 | 4837.10 | 14-SEP-21:30 | 27.30 | 22.85 |
October | 0.538757E+11 | 27864.42 | 03-OCT-21:00 | 28.00 | 22.52 | 0.823631E+10 | 4837.10 | 24-OCT-21:10 | 21.52 | 16.41 |
November | 0.466880E+11 | 25778.13 | 01-NOV-21:00 | 19.30 | 15.01 | 0.796265E+10 | 4837.08 | 02-NOV-22:10 | 18.65 | 14.52 |
December | 0.406095E+11 | 23319.90 | 01-DEC-22:00 | 11.40 | 11.31 | 0.819501E+10 | 4837.07 | 14-DEC-22:40 | 14.40 | 12.54 |
Annual Sum or Average | 0.538642E+12 | 0.960492E+11 | ||||||||
Minimum of Months | 0.327462E+11 | 17684.68 | 11.40 | 11.31 | 0.719735E+10 | 4837.05 | 14.40 | 12.54 | ||
Maximum of Months | 0.568287E+11 | 28756.72 | 36.90 | 27.21 | 0.826731E+10 | 4837.15 | 31.80 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313083E+10 | 2098.95 | 12-JAN-14:30 | 23.45 | 14.09 | 0.658230E+09 | 440.93 | 12-JAN-22:10 | 13.33 | 10.96 |
February | 0.364833E+10 | 2794.67 | 22-FEB-14:05 | 27.02 | 16.30 | 0.630717E+09 | 491.82 | 22-FEB-22:10 | 19.68 | 14.28 |
March | 0.535946E+10 | 3719.43 | 28-MAR-15:03 | 35.58 | 18.54 | 0.769876E+09 | 491.84 | 07-MAR-23:10 | 35.58 | 18.54 |
April | 0.685864E+10 | 4426.43 | 28-APR-18:03 | 38.13 | 19.51 | 0.794235E+09 | 491.85 | 19-APR-21:30 | 38.13 | 19.51 |
May | 0.787800E+10 | 4939.95 | 04-MAY-18:03 | 40.25 | 22.32 | 0.834099E+09 | 491.85 | 08-MAY-21:30 | 33.55 | 19.72 |
June | 0.757227E+10 | 4930.33 | 12-JUN-18:03 | 42.22 | 22.60 | 0.804735E+09 | 491.84 | 12-JUN-21:30 | 36.65 | 22.52 |
July | 0.718963E+10 | 4427.29 | 07-JUL-18:03 | 38.10 | 25.41 | 0.830729E+09 | 491.83 | 06-JUL-21:30 | 38.10 | 25.41 |
August | 0.674836E+10 | 4140.41 | 07-AUG-18:03 | 35.77 | 27.05 | 0.832488E+09 | 491.82 | 03-AUG-04:19 | 35.77 | 27.05 |
September | 0.644632E+10 | 4263.17 | 26-SEP-14:10 | 35.77 | 22.87 | 0.790518E+09 | 491.82 | 25-SEP-21:19 | 35.77 | 22.87 |
October | 0.666653E+10 | 4576.51 | 02-OCT-14:20 | 36.40 | 21.05 | 0.804276E+09 | 491.84 | 20-OCT-22:10 | 21.75 | 16.56 |
November | 0.522342E+10 | 3785.38 | 09-NOV-13:30 | 29.35 | 18.04 | 0.729042E+09 | 491.84 | 01-NOV-22:10 | 29.35 | 18.04 |
December | 0.367202E+10 | 2741.98 | 02-DEC-13:50 | 23.97 | 13.12 | 0.671973E+09 | 466.97 | 28-DEC-22:10 | 17.95 | 13.92 |
Annual Sum or Average | 0.703938E+11 | 0.915092E+10 | ||||||||
Minimum of Months | 0.313083E+10 | 2098.95 | 23.45 | 13.12 | 0.630717E+09 | 440.93 | 13.33 | 10.96 | ||
Maximum of Months | 0.787800E+10 | 4939.95 | 42.22 | 27.05 | 0.834099E+09 | 491.85 | 38.13 | 27.05 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302367E+10 | 1423.76 | 12-JAN-19:10 | 18.12 | 13.15 | 0.826462E+09 | 552.76 | 12-JAN-22:10 | 13.33 | 10.96 |
February | 0.299755E+10 | 1785.64 | 22-FEB-21:10 | 20.90 | 14.58 | 0.788619E+09 | 569.55 | 22-FEB-23:10 | 18.43 | 13.97 |
March | 0.391988E+10 | 2592.77 | 28-MAR-20:10 | 28.48 | 18.89 | 0.937591E+09 | 569.55 | 17-MAR-22:10 | 28.48 | 18.89 |
April | 0.482974E+10 | 3215.26 | 28-APR-20:10 | 34.95 | 19.09 | 0.933495E+09 | 569.55 | 19-APR-21:30 | 34.95 | 19.09 |
May | 0.558941E+10 | 3423.72 | 04-MAY-20:10 | 34.88 | 23.02 | 0.969906E+09 | 569.61 | 04-MAY-21:30 | 32.80 | 22.55 |
June | 0.540771E+10 | 3495.87 | 12-JUN-20:10 | 38.43 | 22.54 | 0.939222E+09 | 569.70 | 08-JUN-21:30 | 38.43 | 22.54 |
July | 0.521473E+10 | 3261.70 | 03-JUL-20:10 | 36.42 | 27.19 | 0.967491E+09 | 569.54 | 10-JUL-21:30 | 27.40 | 23.56 |
August | 0.498562E+10 | 3047.28 | 07-AUG-20:10 | 34.07 | 27.23 | 0.971399E+09 | 569.53 | 05-AUG-01:19 | 34.07 | 27.23 |
September | 0.460708E+10 | 2822.00 | 22-SEP-20:10 | 30.25 | 25.16 | 0.932233E+09 | 569.54 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.441692E+10 | 2775.28 | 02-OCT-20:10 | 27.12 | 20.31 | 0.959424E+09 | 569.55 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.361312E+10 | 2061.62 | 09-NOV-21:10 | 20.38 | 16.92 | 0.895760E+09 | 569.55 | 02-NOV-22:10 | 20.38 | 16.92 |
December | 0.318829E+10 | 1476.49 | 28-DEC-19:10 | 20.73 | 14.41 | 0.853318E+09 | 566.55 | 01-DEC-22:10 | 20.73 | 14.41 |
Annual Sum or Average | 0.517937E+11 | 0.109749E+11 | ||||||||
Minimum of Months | 0.299755E+10 | 1423.76 | 18.12 | 13.15 | 0.788619E+09 | 552.76 | 13.33 | 10.96 | ||
Maximum of Months | 0.558941E+10 | 3495.87 | 38.43 | 27.23 | 0.971399E+09 | 569.70 | 38.43 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249910E+10 | 1393.03 | 14-JAN-19:10 | 18.95 | 14.25 | 0.154957E+09 | 99.88 | 26-JAN-22:10 | 14.45 | 11.64 |
February | 0.292653E+10 | 1651.89 | 23-FEB-19:10 | 21.65 | 14.67 | 0.147607E+09 | 109.10 | 24-FEB-22:10 | 19.35 | 16.58 |
March | 0.395322E+10 | 2010.66 | 29-MAR-18:10 | 30.77 | 18.53 | 0.181925E+09 | 119.90 | 29-MAR-21:19 | 26.20 | 18.28 |
April | 0.486729E+10 | 3273.20 | 28-APR-20:00 | 35.20 | 19.07 | 0.193456E+09 | 120.46 | 19-APR-21:30 | 35.20 | 19.07 |
May | 0.638118E+10 | 3813.76 | 04-MAY-19:50 | 35.67 | 22.96 | 0.204954E+09 | 120.46 | 08-MAY-21:30 | 33.55 | 19.72 |
June | 0.644840E+10 | 4188.33 | 12-JUN-20:00 | 38.70 | 22.52 | 0.198391E+09 | 120.47 | 12-JUN-21:30 | 36.65 | 22.52 |
July | 0.643712E+10 | 3925.35 | 07-JUL-20:00 | 35.70 | 25.97 | 0.204729E+09 | 120.45 | 06-JUL-21:30 | 35.70 | 25.97 |
August | 0.592803E+10 | 3497.45 | 08-AUG-20:00 | 33.20 | 27.10 | 0.205588E+09 | 120.45 | 02-AUG-21:30 | 33.20 | 27.10 |
September | 0.498583E+10 | 3021.28 | 01-SEP-20:00 | 31.50 | 26.31 | 0.196142E+09 | 120.45 | 25-SEP-21:30 | 28.85 | 23.26 |
October | 0.446825E+10 | 2441.44 | 02-OCT-20:00 | 27.40 | 20.32 | 0.194825E+09 | 120.45 | 02-OCT-21:19 | 25.47 | 20.14 |
November | 0.363348E+10 | 1783.60 | 09-NOV-19:10 | 23.47 | 17.31 | 0.170361E+09 | 112.80 | 10-NOV-22:10 | 18.88 | 15.74 |
December | 0.302823E+10 | 1452.39 | 28-DEC-19:10 | 20.73 | 14.41 | 0.158651E+09 | 102.43 | 01-DEC-22:10 | 20.73 | 14.41 |
Annual Sum or Average | 0.555567E+11 | 0.221159E+10 | ||||||||
Minimum of Months | 0.249910E+10 | 1393.03 | 18.95 | 14.25 | 0.147607E+09 | 99.88 | 14.45 | 11.64 | ||
Maximum of Months | 0.644840E+10 | 4188.33 | 38.70 | 27.10 | 0.205588E+09 | 120.47 | 36.65 | 27.10 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142658E+10 | 756.58 | 14-JAN-19:09 | 18.95 | 14.25 | 0.119238E+09 | 75.92 | 26-JAN-22:10 | 14.45 | 11.64 |
February | 0.162160E+10 | 891.68 | 23-FEB-19:10 | 21.65 | 14.67 | 0.113735E+09 | 82.68 | 24-FEB-22:10 | 19.35 | 16.58 |
March | 0.215385E+10 | 1082.51 | 29-MAR-18:10 | 30.77 | 18.53 | 0.139565E+09 | 90.60 | 29-MAR-21:40 | 25.80 | 18.13 |
April | 0.258091E+10 | 1602.79 | 28-APR-20:00 | 35.20 | 19.07 | 0.148242E+09 | 92.66 | 19-APR-21:30 | 35.20 | 19.07 |
May | 0.333740E+10 | 1885.69 | 04-MAY-19:30 | 36.60 | 22.78 | 0.157574E+09 | 92.66 | 05-MAY-23:40 | 34.23 | 18.55 |
June | 0.338983E+10 | 2084.46 | 12-JUN-19:50 | 39.05 | 22.50 | 0.152553E+09 | 92.66 | 12-JUN-21:30 | 36.65 | 22.52 |
July | 0.337301E+10 | 1944.77 | 07-JUL-19:50 | 35.93 | 25.93 | 0.157421E+09 | 92.66 | 06-JUL-21:30 | 35.93 | 25.93 |
August | 0.310065E+10 | 1724.50 | 08-AUG-19:40 | 33.60 | 27.14 | 0.158053E+09 | 92.66 | 02-AUG-21:30 | 33.60 | 27.14 |
September | 0.263288E+10 | 1478.54 | 01-SEP-20:00 | 31.50 | 26.31 | 0.150591E+09 | 92.66 | 25-SEP-21:30 | 28.85 | 23.26 |
October | 0.241526E+10 | 1167.49 | 03-OCT-20:00 | 28.90 | 22.46 | 0.149259E+09 | 92.66 | 02-OCT-21:19 | 28.90 | 22.46 |
November | 0.199155E+10 | 963.03 | 09-NOV-19:10 | 23.47 | 17.31 | 0.131234E+09 | 85.49 | 09-NOV-22:10 | 19.68 | 16.56 |
December | 0.168846E+10 | 788.75 | 28-DEC-19:10 | 20.73 | 14.41 | 0.122536E+09 | 77.89 | 01-DEC-22:10 | 20.73 | 14.41 |
Annual Sum or Average | 0.297120E+11 | 0.170000E+10 | ||||||||
Minimum of Months | 0.142658E+10 | 756.58 | 18.95 | 14.25 | 0.113735E+09 | 75.92 | 14.45 | 11.64 | ||
Maximum of Months | 0.338983E+10 | 2084.46 | 39.05 | 27.14 | 0.158053E+09 | 92.66 | 36.65 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447394E+11 | 33728.41 | 26-JAN-21:00 | 14.80 | 11.71 | 0.593607E+09 | 381.55 | 24-JAN-22:19 | 14.80 | 11.71 |
February | 0.421875E+11 | 34982.54 | 22-FEB-21:00 | 21.10 | 14.62 | 0.544409E+09 | 381.55 | 13-FEB-22:30 | 21.10 | 14.62 |
March | 0.498965E+11 | 36780.19 | 28-MAR-20:00 | 28.80 | 18.84 | 0.616480E+09 | 381.69 | 24-MAR-21:10 | 28.80 | 18.84 |
April | 0.517906E+11 | 38248.87 | 28-APR-20:00 | 35.20 | 19.07 | 0.606890E+09 | 381.62 | 04-APR-21:10 | 35.20 | 19.07 |
May | 0.554572E+11 | 39141.44 | 04-MAY-20:00 | 35.20 | 23.02 | 0.632452E+09 | 381.59 | 08-MAY-21:30 | 33.55 | 19.72 |
June | 0.533276E+11 | 39192.29 | 12-JUN-20:00 | 38.70 | 22.52 | 0.612097E+09 | 381.58 | 05-JUN-21:30 | 38.70 | 22.52 |
July | 0.541763E+11 | 38865.18 | 07-JUL-20:00 | 35.70 | 25.97 | 0.629482E+09 | 381.58 | 10-JUL-21:30 | 27.40 | 23.56 |
August | 0.536371E+11 | 37954.55 | 07-AUG-20:00 | 34.20 | 27.22 | 0.629936E+09 | 381.58 | 15-AUG-21:10 | 28.05 | 24.82 |
September | 0.506912E+11 | 37178.78 | 22-SEP-20:00 | 30.40 | 25.15 | 0.604538E+09 | 381.57 | 25-SEP-21:19 | 29.03 | 23.31 |
October | 0.512807E+11 | 36984.60 | 02-OCT-20:00 | 27.40 | 20.32 | 0.620267E+09 | 381.61 | 24-OCT-21:10 | 21.52 | 16.41 |
November | 0.468488E+11 | 35263.71 | 09-NOV-21:00 | 20.50 | 16.99 | 0.589887E+09 | 381.61 | 03-NOV-21:10 | 20.50 | 16.99 |
December | 0.453568E+11 | 33842.08 | 28-DEC-21:00 | 19.00 | 14.10 | 0.597030E+09 | 381.54 | 20-DEC-22:19 | 19.00 | 14.10 |
Annual Sum or Average | 0.599390E+12 | 0.727707E+10 | ||||||||
Minimum of Months | 0.421875E+11 | 33728.41 | 14.80 | 11.71 | 0.544409E+09 | 381.54 | 14.80 | 11.71 | ||
Maximum of Months | 0.554572E+11 | 39192.29 | 38.70 | 27.22 | 0.632452E+09 | 381.69 | 38.70 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174387E+11 | 9232.98 | 12-JAN-16:03 | 23.13 | 14.50 | 0.100482E+11 | 6462.26 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.175831E+11 | 11093.82 | 20-FEB-13:00 | 25.90 | 13.36 | 0.944057E+10 | 6462.63 | 22-FEB-23:10 | 18.43 | 13.97 |
March | 0.228226E+11 | 13537.25 | 28-MAR-15:03 | 35.58 | 18.54 | 0.108591E+11 | 6462.71 | 22-MAR-22:10 | 35.58 | 18.54 |
April | 0.261755E+11 | 14751.85 | 27-APR-21:10 | 34.92 | 17.25 | 0.106022E+11 | 6462.11 | 08-APR-01:19 | 34.92 | 17.25 |
May | 0.288159E+11 | 15520.68 | 05-MAY-21:10 | 36.73 | 18.90 | 0.110011E+11 | 6461.98 | 05-MAY-04:19 | 36.73 | 18.90 |
June | 0.276621E+11 | 15713.88 | 12-JUN-21:10 | 36.95 | 22.55 | 0.106570E+11 | 6461.96 | 05-JUN-04:19 | 36.95 | 22.55 |
July | 0.275997E+11 | 15081.35 | 07-JUL-21:10 | 34.58 | 25.98 | 0.109701E+11 | 6461.90 | 22-JUL-01:19 | 31.23 | 25.95 |
August | 0.267109E+11 | 14483.45 | 07-AUG-21:10 | 33.28 | 27.30 | 0.110129E+11 | 6461.90 | 03-AUG-04:19 | 33.28 | 27.30 |
September | 0.255883E+11 | 14542.17 | 26-SEP-15:03 | 36.05 | 22.65 | 0.105919E+11 | 6461.93 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.268367E+11 | 15407.86 | 02-OCT-15:03 | 36.32 | 21.08 | 0.109335E+11 | 6462.68 | 20-OCT-22:10 | 21.75 | 16.56 |
November | 0.226427E+11 | 13546.18 | 04-NOV-13:30 | 30.20 | 17.21 | 0.104681E+11 | 6462.63 | 02-NOV-22:10 | 30.20 | 17.21 |
December | 0.185395E+11 | 11377.23 | 02-DEC-13:30 | 23.70 | 13.05 | 0.102973E+11 | 6462.43 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.288416E+12 | 0.126882E+12 | ||||||||
Minimum of Months | 0.174387E+11 | 9232.98 | 23.13 | 13.05 | 0.944057E+10 | 6461.90 | 16.43 | 13.26 | ||
Maximum of Months | 0.288159E+11 | 15713.88 | 36.95 | 27.30 | 0.110129E+11 | 6462.71 | 36.95 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.592014E+11 | 28625.52 | 13-JAN-22:10 | 17.58 | 13.72 | 0.297507E+11 | 19185.56 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.578948E+11 | 35079.83 | 22-FEB-22:10 | 19.68 | 14.28 | 0.279455E+11 | 19186.06 | 22-FEB-23:10 | 18.43 | 13.97 |
March | 0.738015E+11 | 43059.48 | 29-MAR-21:10 | 26.40 | 18.36 | 0.322105E+11 | 19186.18 | 22-MAR-22:10 | 26.40 | 18.36 |
April | 0.856083E+11 | 50697.38 | 27-APR-21:10 | 34.92 | 17.25 | 0.315058E+11 | 19185.43 | 08-APR-01:19 | 34.92 | 17.25 |
May | 0.978529E+11 | 54061.76 | 04-MAY-20:10 | 34.88 | 23.02 | 0.326741E+11 | 19185.15 | 13-MAY-01:19 | 23.47 | 19.67 |
June | 0.956806E+11 | 55868.64 | 12-JUN-21:10 | 36.95 | 22.55 | 0.316698E+11 | 19185.10 | 05-JUN-04:19 | 36.95 | 22.55 |
July | 0.965889E+11 | 53830.04 | 07-JUL-21:10 | 34.58 | 25.98 | 0.326090E+11 | 19185.07 | 22-JUL-01:19 | 31.23 | 25.95 |
August | 0.936065E+11 | 51348.60 | 07-AUG-21:10 | 33.28 | 27.30 | 0.327421E+11 | 19185.05 | 05-AUG-01:19 | 33.28 | 27.30 |
September | 0.865653E+11 | 48187.82 | 22-SEP-21:10 | 29.42 | 25.15 | 0.315328E+11 | 19185.11 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.844815E+11 | 47024.00 | 02-OCT-20:10 | 27.12 | 20.31 | 0.325438E+11 | 19186.10 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.700897E+11 | 39107.84 | 09-NOV-22:10 | 19.68 | 16.56 | 0.310959E+11 | 19186.06 | 02-NOV-22:10 | 19.68 | 16.56 |
December | 0.620345E+11 | 31534.62 | 28-DEC-22:10 | 17.95 | 13.92 | 0.305771E+11 | 19185.80 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.963406E+12 | 0.376857E+12 | ||||||||
Minimum of Months | 0.578948E+11 | 28625.52 | 17.58 | 13.72 | 0.279455E+11 | 19185.05 | 16.43 | 13.26 | ||
Maximum of Months | 0.978529E+11 | 55868.64 | 36.95 | 27.30 | 0.327421E+11 | 19186.18 | 36.95 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405498E+09 | 3375.27 | 21-JAN-19:02 | 13.52 | 8.41 | 97262907.53 | 56.69 | 25-JAN-22:00 | 16.50 | 13.24 |
February | 0.885465E+09 | 3271.81 | 15-FEB-16:01 | 22.83 | 16.88 | 88725739.53 | 56.70 | 22-FEB-22:40 | 19.03 | 14.13 |
March | 0.202236E+10 | 3270.06 | 12-MAR-08:61 | 21.93 | 16.02 | 98979074.18 | 56.70 | 28-MAR-21:10 | 26.67 | 19.04 |
April | 0.311861E+10 | 3319.93 | 26-APR-08:61 | 28.62 | 21.71 | 95973954.87 | 56.70 | 14-APR-22:30 | 28.62 | 21.71 |
May | 0.368944E+10 | 3332.89 | 12-MAY-15:01 | 27.68 | 21.99 | 99294418.93 | 56.70 | 02-MAY-00:30 | 27.68 | 21.99 |
June | 0.352576E+10 | 3350.72 | 17-JUN-08:61 | 31.33 | 25.84 | 96078437.51 | 56.70 | 23-JUN-23:30 | 33.55 | 25.87 |
July | 0.324869E+10 | 3333.54 | 10-JUL-08:61 | 31.78 | 26.26 | 99135412.79 | 56.70 | 07-JUL-00:10 | 31.78 | 26.26 |
August | 0.297744E+10 | 3341.22 | 09-AUG-08:61 | 30.93 | 25.71 | 99238730.95 | 56.70 | 07-AUG-23:30 | 30.93 | 25.71 |
September | 0.273664E+10 | 3332.21 | 13-SEP-15:02 | 33.33 | 26.95 | 95942773.59 | 56.70 | 25-SEP-21:30 | 28.85 | 23.26 |
October | 0.258110E+10 | 3315.70 | 12-OCT-18:01 | 25.38 | 21.81 | 99083464.00 | 56.70 | 19-OCT-01:39 | 21.53 | 18.89 |
November | 0.161503E+10 | 3257.71 | 17-NOV-19:01 | 21.33 | 17.12 | 95680365.52 | 56.70 | 07-NOV-22:00 | 21.33 | 17.12 |
December | 0.580915E+09 | 3642.31 | 20-DEC-16:01 | 19.20 | 10.37 | 97845751.96 | 56.69 | 27-DEC-22:19 | 14.07 | 12.80 |
Annual Sum or Average | 0.273870E+11 | 0.116324E+10 | ||||||||
Minimum of Months | 0.405498E+09 | 3257.71 | 13.52 | 8.41 | 88725739.53 | 56.69 | 14.07 | 12.80 | ||
Maximum of Months | 0.368944E+10 | 3642.31 | 33.33 | 26.95 | 99294418.93 | 56.70 | 33.55 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129174E+09 | 3126.43 | 14-JAN-16:01 | 21.20 | 15.01 | 96635269.05 | 62.36 | 13-JAN-22:40 | 21.20 | 15.01 |
February | 0.437578E+09 | 3300.24 | 24-FEB-16:01 | 26.18 | 17.45 | 91308009.27 | 71.01 | 22-FEB-22:19 | 26.18 | 17.45 |
March | 0.152330E+10 | 3326.51 | 15-MAR-21:51 | 19.60 | 13.80 | 0.103478E+09 | 75.66 | 13-MAR-21:00 | 19.60 | 13.80 |
April | 0.286098E+10 | 3433.72 | 06-APR-08:51 | 25.60 | 16.75 | 97188432.53 | 58.81 | 09-APR-20:40 | 22.10 | 14.30 |
May | 0.363941E+10 | 3358.71 | 12-MAY-15:01 | 27.68 | 21.99 | 99346463.50 | 56.70 | 09-MAY-00:20 | 27.68 | 21.99 |
June | 0.353034E+10 | 3355.86 | 17-JUN-08:61 | 31.33 | 25.84 | 96125676.19 | 56.70 | 04-JUN-23:30 | 31.33 | 25.84 |
July | 0.324610E+10 | 3340.93 | 19-JUL-15:02 | 33.52 | 27.38 | 99135469.89 | 56.70 | 01-JUL-23:00 | 33.52 | 27.38 |
August | 0.293024E+10 | 3327.41 | 06-AUG-08:61 | 30.08 | 23.94 | 99238345.34 | 56.70 | 01-AUG-21:19 | 30.08 | 23.94 |
September | 0.255169E+10 | 3317.04 | 02-SEP-18:02 | 31.38 | 26.46 | 96023698.82 | 56.70 | 28-SEP-03:49 | 24.73 | 22.36 |
October | 0.197286E+10 | 3449.10 | 17-OCT-21:51 | 23.00 | 18.98 | 0.102511E+09 | 76.41 | 11-OCT-21:10 | 23.00 | 18.98 |
November | 0.886794E+09 | 3252.79 | 28-NOV-16:01 | 22.55 | 15.25 | 99811716.67 | 72.83 | 09-NOV-22:19 | 22.55 | 15.25 |
December | 0.191211E+09 | 3506.95 | 20-DEC-16:01 | 19.20 | 10.37 | 97547106.20 | 64.66 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.238997E+11 | 0.117835E+10 | ||||||||
Minimum of Months | 0.129174E+09 | 3126.43 | 19.20 | 10.37 | 91308009.27 | 56.70 | 17.65 | 13.80 | ||
Maximum of Months | 0.363941E+10 | 3506.95 | 33.52 | 27.38 | 0.103478E+09 | 76.41 | 33.52 | 27.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271481E+09 | 394.58 | 08-JAN-14:30 | 22.60 | 13.48 | 0.00 | 0.00 | 01-JAN-00:10 | 22.60 | 13.48 |
February | 0.375198E+09 | 453.96 | 20-FEB-14:30 | 26.35 | 13.75 | 0.00 | 0.00 | 01-FEB-00:10 | 26.35 | 13.75 |
March | 0.599526E+09 | 483.17 | 13-MAR-13:50 | 32.32 | 18.86 | 0.00 | 0.00 | 01-MAR-00:10 | 32.32 | 18.86 |
April | 0.765539E+09 | 502.12 | 15-APR-14:00 | 40.20 | 20.61 | 0.00 | 0.00 | 01-APR-00:10 | 40.20 | 20.61 |
May | 0.848900E+09 | 525.12 | 04-MAY-17:20 | 41.63 | 22.16 | 0.00 | 0.00 | 01-MAY-00:10 | 41.63 | 22.16 |
June | 0.796975E+09 | 509.94 | 12-JUN-17:20 | 43.43 | 22.47 | 0.00 | 0.00 | 01-JUN-00:10 | 43.43 | 22.47 |
July | 0.786386E+09 | 489.88 | 04-JUL-20:10 | 39.85 | 24.37 | 0.00 | 0.00 | 01-JUL-00:10 | 39.85 | 24.37 |
August | 0.742466E+09 | 448.04 | 07-AUG-20:20 | 33.93 | 27.24 | 0.00 | 0.00 | 01-AUG-00:10 | 33.93 | 27.24 |
September | 0.729054E+09 | 525.03 | 26-SEP-14:00 | 35.70 | 22.91 | 0.00 | 0.00 | 01-SEP-00:10 | 35.70 | 22.91 |
October | 0.842206E+09 | 588.72 | 02-OCT-13:40 | 36.33 | 21.10 | 0.00 | 0.00 | 01-OCT-00:10 | 36.33 | 21.10 |
November | 0.685761E+09 | 560.38 | 08-NOV-13:40 | 29.60 | 17.22 | 0.00 | 0.00 | 01-NOV-00:10 | 29.60 | 17.22 |
December | 0.377013E+09 | 471.37 | 02-DEC-13:40 | 23.83 | 13.08 | 0.00 | 0.00 | 01-DEC-00:10 | 23.83 | 13.08 |
Annual Sum or Average | 0.782050E+10 | 0.00 | ||||||||
Minimum of Months | 0.271481E+09 | 394.58 | 22.60 | 13.08 | 0.00 | 0.00 | 22.60 | 13.08 | ||
Maximum of Months | 0.848900E+09 | 588.72 | 43.43 | 27.24 | 0.00 | 0.00 | 43.43 | 27.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227821E+09 | 1311.79 | 21-JAN-19:02 | 13.52 | 8.41 | 96954735.30 | 64.74 | 13-JAN-22:49 | 13.52 | 8.41 |
February | 0.338421E+09 | 1324.47 | 24-FEB-16:01 | 26.18 | 17.45 | 90707285.42 | 70.00 | 23-FEB-22:49 | 26.18 | 17.45 |
March | 0.658896E+09 | 1348.55 | 29-MAR-15:01 | 33.07 | 18.99 | 0.102312E+09 | 72.24 | 30-MAR-21:10 | 21.58 | 17.06 |
April | 0.986899E+09 | 1345.83 | 18-APR-15:02 | 37.58 | 23.23 | 96712107.35 | 56.69 | 26-APR-21:00 | 30.20 | 22.27 |
May | 0.124912E+10 | 1344.76 | 25-MAY-15:02 | 38.85 | 24.95 | 99168427.06 | 56.69 | 17-MAY-22:30 | 38.85 | 24.95 |
June | 0.123685E+10 | 1349.08 | 16-JUN-15:02 | 37.97 | 25.32 | 95980974.49 | 56.69 | 16-JUN-22:49 | 33.42 | 25.89 |
July | 0.123007E+10 | 1353.05 | 29-JUL-08:61 | 29.37 | 25.90 | 99033690.63 | 56.69 | 05-JUL-00:30 | 29.37 | 25.90 |
August | 0.113892E+10 | 1349.77 | 28-AUG-08:61 | 29.95 | 27.22 | 99105121.19 | 56.69 | 22-AUG-21:10 | 29.95 | 27.22 |
September | 0.984799E+09 | 1353.10 | 03-SEP-08:61 | 27.08 | 24.99 | 95800229.24 | 56.69 | 29-SEP-02:20 | 24.97 | 20.75 |
October | 0.780774E+09 | 1342.37 | 25-OCT-15:01 | 28.80 | 18.59 | 0.101518E+09 | 75.40 | 11-OCT-21:10 | 28.80 | 18.59 |
November | 0.457791E+09 | 1344.01 | 08-NOV-16:01 | 28.98 | 18.63 | 98420603.10 | 70.39 | 09-NOV-22:40 | 19.33 | 16.42 |
December | 0.270790E+09 | 1321.82 | 30-DEC-19:02 | 11.73 | 7.40 | 97504497.82 | 66.30 | 28-DEC-22:49 | 11.73 | 7.40 |
Annual Sum or Average | 0.956115E+10 | 0.117322E+10 | ||||||||
Minimum of Months | 0.227821E+09 | 1311.79 | 11.73 | 7.40 | 90707285.42 | 56.69 | 11.73 | 7.40 | ||
Maximum of Months | 0.124912E+10 | 1353.10 | 38.85 | 27.22 | 0.102312E+09 | 75.40 | 38.85 | 27.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399095E+09 | 3071.75 | 21-JAN-19:02 | 13.52 | 8.41 | 97523562.45 | 56.69 | 25-JAN-22:10 | 16.75 | 13.27 |
February | 0.917057E+09 | 3012.67 | 08-FEB-19:01 | 21.05 | 16.28 | 88959001.80 | 56.69 | 24-FEB-22:19 | 19.30 | 16.56 |
March | 0.203922E+10 | 3029.52 | 05-MAR-09:02 | 20.38 | 15.16 | 99109710.77 | 56.69 | 13-MAR-01:39 | 21.30 | 18.15 |
April | 0.312377E+10 | 3103.76 | 03-APR-08:61 | 25.37 | 19.02 | 95962254.49 | 56.70 | 16-APR-23:19 | 27.27 | 19.97 |
May | 0.371279E+10 | 3042.82 | 12-MAY-18:02 | 30.30 | 23.62 | 99229211.71 | 56.70 | 27-MAY-23:40 | 28.67 | 19.24 |
June | 0.343147E+10 | 3072.83 | 23-JUN-08:61 | 31.55 | 26.30 | 96045624.56 | 56.70 | 07-JUN-04:30 | 31.55 | 26.30 |
July | 0.325406E+10 | 3057.34 | 13-JUL-18:02 | 34.02 | 27.50 | 99136171.69 | 56.70 | 05-JUL-03:49 | 34.02 | 27.50 |
August | 0.297270E+10 | 3067.86 | 01-AUG-08:61 | 29.25 | 24.37 | 99239920.05 | 56.70 | 01-AUG-22:30 | 30.15 | 24.23 |
September | 0.270595E+10 | 3080.15 | 21-SEP-08:61 | 27.67 | 23.19 | 95947603.77 | 56.69 | 01-SEP-22:10 | 27.67 | 23.19 |
October | 0.258893E+10 | 3135.58 | 05-OCT-08:61 | 25.27 | 19.02 | 99113074.81 | 56.70 | 03-OCT-21:49 | 25.27 | 19.02 |
November | 0.160102E+10 | 3019.23 | 09-NOV-09:01 | 22.33 | 17.31 | 95816782.16 | 56.69 | 06-NOV-22:40 | 22.33 | 17.31 |
December | 0.577874E+09 | 3319.78 | 20-DEC-16:01 | 19.20 | 10.37 | 98037904.49 | 56.69 | 27-DEC-22:40 | 13.83 | 12.67 |
Annual Sum or Average | 0.273239E+11 | 0.116412E+10 | ||||||||
Minimum of Months | 0.399095E+09 | 3012.67 | 13.52 | 8.41 | 88959001.80 | 56.69 | 13.83 | 12.67 | ||
Maximum of Months | 0.371279E+10 | 3319.78 | 34.02 | 27.50 | 99239920.05 | 56.70 | 34.02 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140667E+09 | 2806.02 | 14-JAN-16:01 | 21.20 | 15.01 | 96364539.66 | 61.45 | 13-JAN-22:40 | 21.20 | 15.01 |
February | 0.469923E+09 | 3082.96 | 23-FEB-09:51 | 21.00 | 14.25 | 91379536.39 | 71.12 | 23-FEB-22:30 | 18.85 | 13.71 |
March | 0.151984E+10 | 3286.34 | 28-MAR-08:51 | 25.40 | 17.31 | 0.103702E+09 | 75.87 | 13-MAR-21:00 | 25.40 | 17.31 |
April | 0.285606E+10 | 3536.10 | 07-APR-08:51 | 25.50 | 16.31 | 97341660.12 | 58.08 | 09-APR-20:40 | 22.10 | 14.30 |
May | 0.366211E+10 | 3044.42 | 12-MAY-18:02 | 30.30 | 23.62 | 99289755.51 | 56.70 | 29-MAY-00:10 | 29.68 | 18.90 |
June | 0.343629E+10 | 3076.47 | 23-JUN-08:61 | 31.55 | 26.30 | 96090034.24 | 56.70 | 01-JUN-21:30 | 31.55 | 26.30 |
July | 0.325126E+10 | 3086.94 | 08-JUL-08:62 | 33.90 | 28.37 | 99136175.97 | 56.70 | 19-JUL-21:19 | 30.67 | 26.84 |
August | 0.292534E+10 | 3075.36 | 26-AUG-15:02 | 34.15 | 28.54 | 99239670.37 | 56.70 | 15-AUG-21:19 | 34.15 | 28.54 |
September | 0.252092E+10 | 3066.15 | 22-SEP-08:61 | 29.38 | 23.60 | 96029309.48 | 56.70 | 28-SEP-21:10 | 27.75 | 22.94 |
October | 0.196684E+10 | 3398.51 | 15-OCT-08:51 | 26.10 | 16.03 | 0.102636E+09 | 76.78 | 11-OCT-21:10 | 26.10 | 16.03 |
November | 0.860314E+09 | 3046.85 | 14-NOV-09:51 | 22.30 | 15.47 | 99888694.22 | 72.15 | 09-NOV-22:19 | 22.30 | 15.47 |
December | 0.209097E+09 | 2897.83 | 27-DEC-16:01 | 22.02 | 15.09 | 97359446.89 | 63.29 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.238187E+11 | 0.117846E+10 | ||||||||
Minimum of Months | 0.140667E+09 | 2806.02 | 21.00 | 14.25 | 91379536.39 | 56.70 | 17.65 | 13.71 | ||
Maximum of Months | 0.366211E+10 | 3536.10 | 34.15 | 28.54 | 0.103702E+09 | 76.78 | 34.15 | 28.54 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389512E+10 | 1838.06 | 12-JAN-19:10 | 18.12 | 13.15 | 0.124074E+10 | 783.18 | 13-JAN-22:49 | 17.52 | 13.58 |
February | 0.416671E+10 | 2258.11 | 22-FEB-19:10 | 23.30 | 15.09 | 0.120547E+10 | 867.26 | 23-FEB-22:40 | 18.70 | 13.67 |
March | 0.550867E+10 | 2692.53 | 13-MAR-18:10 | 27.88 | 18.21 | 0.149063E+10 | 949.78 | 13-MAR-21:40 | 21.37 | 17.15 |
April | 0.652153E+10 | 3939.63 | 28-APR-18:17 | 37.87 | 19.51 | 0.154888E+10 | 951.87 | 19-APR-21:19 | 37.87 | 19.51 |
May | 0.767123E+10 | 4358.27 | 04-MAY-18:15 | 39.80 | 22.35 | 0.161968E+10 | 951.85 | 05-MAY-23:40 | 34.23 | 18.55 |
June | 0.739842E+10 | 4431.80 | 07-JUN-18:13 | 41.90 | 22.54 | 0.156751E+10 | 951.84 | 05-JUN-21:30 | 41.90 | 22.54 |
July | 0.726833E+10 | 4098.29 | 07-JUL-20:10 | 35.53 | 25.98 | 0.161388E+10 | 951.84 | 06-JUL-21:30 | 35.53 | 25.98 |
August | 0.682909E+10 | 3788.56 | 07-AUG-20:10 | 34.07 | 27.23 | 0.161604E+10 | 951.84 | 05-AUG-01:19 | 34.07 | 27.23 |
September | 0.633239E+10 | 3457.10 | 17-SEP-20:10 | 37.37 | 27.68 | 0.153727E+10 | 951.84 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.621592E+10 | 3388.69 | 02-OCT-18:15 | 31.73 | 20.95 | 0.158327E+10 | 951.85 | 24-OCT-21:10 | 21.52 | 16.41 |
November | 0.521270E+10 | 2473.60 | 01-NOV-18:10 | 24.40 | 15.69 | 0.142328E+10 | 921.27 | 01-NOV-21:40 | 18.90 | 14.83 |
December | 0.435333E+10 | 2033.05 | 03-DEC-11:35 | 22.07 | 14.16 | 0.129182E+10 | 834.90 | 01-DEC-22:19 | 22.07 | 14.16 |
Annual Sum or Average | 0.713734E+11 | 0.177385E+11 | ||||||||
Minimum of Months | 0.389512E+10 | 1838.06 | 18.12 | 13.15 | 0.120547E+10 | 783.18 | 17.52 | 13.58 | ||
Maximum of Months | 0.767123E+10 | 4431.80 | 41.90 | 27.68 | 0.161968E+10 | 951.87 | 41.90 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422455E+09 | 3732.29 | 21-JAN-19:02 | 13.52 | 8.41 | 97166384.35 | 56.69 | 18-JAN-22:19 | 13.52 | 8.41 |
February | 0.856900E+09 | 3624.75 | 25-FEB-16:01 | 21.12 | 17.96 | 88607339.95 | 56.69 | 22-FEB-04:00 | 21.12 | 17.96 |
March | 0.198958E+10 | 3548.46 | 30-MAR-18:01 | 24.02 | 19.33 | 98853845.00 | 56.70 | 28-MAR-23:00 | 24.02 | 19.33 |
April | 0.318932E+10 | 3621.29 | 16-APR-08:61 | 30.70 | 20.53 | 95990606.87 | 56.70 | 28-APR-22:10 | 32.18 | 19.32 |
May | 0.385332E+10 | 3678.21 | 19-MAY-08:61 | 31.52 | 24.14 | 99354086.27 | 56.70 | 01-MAY-22:19 | 31.52 | 24.14 |
June | 0.371020E+10 | 3727.77 | 09-JUN-18:02 | 40.07 | 26.50 | 96113938.25 | 56.70 | 05-JUN-23:10 | 40.07 | 26.50 |
July | 0.335315E+10 | 3691.97 | 02-JUL-18:02 | 39.48 | 26.63 | 99130283.68 | 56.70 | 30-JUL-01:49 | 28.47 | 25.87 |
August | 0.303363E+10 | 3664.43 | 18-AUG-18:02 | 30.85 | 27.57 | 99228478.89 | 56.70 | 03-AUG-03:49 | 30.85 | 27.57 |
September | 0.275204E+10 | 3660.51 | 13-SEP-18:02 | 29.63 | 25.48 | 95915813.06 | 56.70 | 15-SEP-00:00 | 28.00 | 25.03 |
October | 0.251095E+10 | 3667.22 | 11-OCT-15:01 | 23.05 | 19.80 | 98975255.79 | 56.70 | 03-OCT-23:00 | 23.05 | 19.80 |
November | 0.148094E+10 | 3580.32 | 17-NOV-19:01 | 21.33 | 17.12 | 95514921.12 | 56.69 | 13-NOV-05:49 | 21.33 | 17.12 |
December | 0.545368E+09 | 4038.87 | 20-DEC-16:01 | 19.20 | 10.37 | 97718036.71 | 56.69 | 26-DEC-23:10 | 12.82 | 11.34 |
Annual Sum or Average | 0.276978E+11 | 0.116257E+10 | ||||||||
Minimum of Months | 0.422455E+09 | 3548.46 | 13.52 | 8.41 | 88607339.95 | 56.69 | 12.82 | 8.41 | ||
Maximum of Months | 0.385332E+10 | 4038.87 | 40.07 | 27.57 | 99354086.27 | 56.70 | 40.07 | 27.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114147E+09 | 3494.08 | 26-JAN-16:01 | 19.93 | 13.09 | 96896543.84 | 62.82 | 25-JAN-22:40 | 19.93 | 13.09 |
February | 0.389861E+09 | 3659.73 | 15-FEB-16:01 | 22.83 | 16.88 | 91763298.37 | 72.62 | 22-FEB-22:19 | 19.47 | 14.23 |
March | 0.151007E+10 | 3686.18 | 15-MAR-21:51 | 19.60 | 13.80 | 0.103219E+09 | 75.96 | 13-MAR-21:00 | 19.60 | 13.80 |
April | 0.294439E+10 | 3837.31 | 30-APR-07:51 | 25.70 | 14.00 | 96910173.11 | 58.19 | 09-APR-20:40 | 25.70 | 14.00 |
May | 0.380257E+10 | 3694.08 | 18-MAY-08:61 | 31.87 | 24.38 | 99395445.11 | 56.70 | 14-MAY-00:10 | 31.87 | 24.38 |
June | 0.371594E+10 | 3734.94 | 09-JUN-18:02 | 40.07 | 26.50 | 96151078.67 | 56.70 | 05-JUN-23:10 | 40.07 | 26.50 |
July | 0.335033E+10 | 3698.68 | 02-JUL-18:02 | 39.48 | 26.63 | 99130672.74 | 56.70 | 12-JUL-03:09 | 30.15 | 26.55 |
August | 0.298398E+10 | 3679.89 | 18-AUG-18:02 | 30.85 | 27.57 | 99228009.91 | 56.70 | 07-AUG-21:30 | 30.85 | 27.57 |
September | 0.255979E+10 | 3688.22 | 06-SEP-18:01 | 29.58 | 25.52 | 95975993.84 | 56.70 | 16-SEP-00:20 | 27.23 | 24.65 |
October | 0.192541E+10 | 3691.27 | 09-OCT-21:51 | 22.80 | 18.80 | 0.101764E+09 | 77.75 | 11-OCT-21:10 | 22.40 | 20.30 |
November | 0.755954E+09 | 3550.31 | 28-NOV-16:01 | 22.55 | 15.25 | 99393778.61 | 72.71 | 09-NOV-22:10 | 22.55 | 15.25 |
December | 0.154496E+09 | 3983.19 | 20-DEC-16:01 | 19.20 | 10.37 | 97624404.56 | 66.14 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.242070E+11 | 0.117745E+10 | ||||||||
Minimum of Months | 0.114147E+09 | 3494.08 | 19.20 | 10.37 | 91763298.37 | 56.70 | 17.65 | 13.09 | ||
Maximum of Months | 0.380257E+10 | 3983.19 | 40.07 | 27.57 | 0.103219E+09 | 77.75 | 40.07 | 27.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.682536E+09 | 2086.73 | 31-JAN-19:02 | 15.65 | 10.08 | 98344608.88 | 56.69 | 12-JAN-22:10 | 15.65 | 10.08 |
February | 0.879040E+09 | 1961.39 | 26-FEB-16:01 | 20.93 | 15.46 | 89018408.72 | 56.69 | 24-FEB-22:19 | 20.93 | 15.46 |
March | 0.140417E+10 | 1923.61 | 12-MAR-15:01 | 31.47 | 19.65 | 98963285.59 | 56.69 | 12-MAR-23:00 | 21.80 | 18.17 |
April | 0.180465E+10 | 1947.45 | 14-APR-08:61 | 28.30 | 18.66 | 95929534.82 | 56.70 | 26-APR-21:00 | 30.20 | 22.27 |
May | 0.204128E+10 | 1960.94 | 17-MAY-08:61 | 30.97 | 23.55 | 99215799.54 | 56.70 | 19-MAY-22:49 | 32.27 | 22.84 |
June | 0.195097E+10 | 1971.38 | 17-JUN-08:61 | 31.33 | 25.84 | 96038172.72 | 56.70 | 12-JUN-23:00 | 31.33 | 25.84 |
July | 0.190337E+10 | 1964.72 | 10-JUL-08:61 | 31.78 | 26.26 | 99127660.98 | 56.70 | 06-JUL-22:49 | 31.78 | 26.26 |
August | 0.178977E+10 | 1961.25 | 26-AUG-18:02 | 32.08 | 28.10 | 99228604.04 | 56.70 | 24-AUG-21:30 | 32.08 | 28.10 |
September | 0.171785E+10 | 1979.91 | 17-SEP-15:02 | 34.18 | 26.03 | 95927331.32 | 56.70 | 25-SEP-21:40 | 28.67 | 23.21 |
October | 0.186074E+10 | 1944.48 | 11-OCT-15:01 | 23.05 | 19.80 | 99070539.32 | 56.70 | 16-OCT-21:10 | 23.85 | 18.69 |
November | 0.145633E+10 | 1959.19 | 17-NOV-19:01 | 21.33 | 17.12 | 95771858.28 | 56.69 | 08-NOV-23:00 | 21.33 | 17.12 |
December | 0.848985E+09 | 2144.27 | 31-DEC-16:01 | 14.22 | 6.78 | 98586725.16 | 56.69 | 01-DEC-22:10 | 14.22 | 6.78 |
Annual Sum or Average | 0.183397E+11 | 0.116522E+10 | ||||||||
Minimum of Months | 0.682536E+09 | 1923.61 | 14.22 | 6.78 | 89018408.72 | 56.69 | 14.22 | 6.78 | ||
Maximum of Months | 0.204128E+10 | 2144.27 | 34.18 | 28.10 | 99228604.04 | 56.70 | 32.27 | 28.10 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320474E+11 | 18644.15 | 13-JAN-22:55 | 17.50 | 13.55 | 0.188834E+11 | 11347.98 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.317856E+11 | 20593.19 | 22-FEB-22:10 | 19.68 | 14.28 | 0.172749E+11 | 11348.85 | 22-FEB-23:10 | 18.43 | 13.97 |
March | 0.407135E+11 | 23323.10 | 29-MAR-21:10 | 26.40 | 18.36 | 0.193531E+11 | 11349.02 | 22-MAR-22:10 | 26.40 | 18.36 |
April | 0.455306E+11 | 25893.25 | 27-APR-21:10 | 34.92 | 17.25 | 0.187170E+11 | 11347.59 | 08-APR-01:19 | 34.92 | 17.25 |
May | 0.510118E+11 | 26641.19 | 05-MAY-21:10 | 36.73 | 18.90 | 0.193511E+11 | 11357.85 | 05-MAY-21:30 | 36.40 | 18.80 |
June | 0.499191E+11 | 27251.54 | 12-JUN-21:10 | 36.95 | 22.55 | 0.187610E+11 | 11373.28 | 09-JUN-22:00 | 36.95 | 22.55 |
July | 0.502427E+11 | 26547.91 | 07-JUL-21:10 | 34.58 | 25.98 | 0.193099E+11 | 11370.21 | 03-JUL-22:00 | 34.58 | 25.98 |
August | 0.488281E+11 | 25642.20 | 07-AUG-21:10 | 33.28 | 27.30 | 0.193913E+11 | 11353.38 | 08-AUG-21:30 | 32.40 | 27.12 |
September | 0.448824E+11 | 24573.88 | 01-SEP-21:10 | 30.68 | 26.00 | 0.187095E+11 | 11347.37 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.429764E+11 | 23424.93 | 03-OCT-21:10 | 27.92 | 22.53 | 0.193030E+11 | 11348.97 | 20-OCT-22:10 | 21.75 | 16.56 |
November | 0.361509E+11 | 20824.18 | 08-NOV-22:53 | 19.60 | 17.40 | 0.185866E+11 | 11348.84 | 02-NOV-22:10 | 19.60 | 17.40 |
December | 0.328072E+11 | 19080.56 | 28-DEC-22:54 | 17.20 | 13.76 | 0.189661E+11 | 11348.38 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.506896E+12 | 0.226607E+12 | ||||||||
Minimum of Months | 0.317856E+11 | 18644.15 | 17.20 | 13.55 | 0.172749E+11 | 11347.37 | 16.43 | 13.26 | ||
Maximum of Months | 0.510118E+11 | 27251.54 | 36.95 | 27.30 | 0.193913E+11 | 11373.28 | 36.95 | 27.12 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353416E+11 | 20278.82 | 13-JAN-22:55 | 17.50 | 13.55 | 0.190522E+11 | 11348.00 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.347590E+11 | 21988.91 | 22-FEB-22:10 | 19.68 | 14.28 | 0.173628E+11 | 11348.85 | 22-FEB-23:10 | 18.43 | 13.97 |
March | 0.437330E+11 | 24472.24 | 29-MAR-21:10 | 26.40 | 18.36 | 0.193809E+11 | 11349.02 | 22-MAR-22:10 | 26.40 | 18.36 |
April | 0.481895E+11 | 27056.16 | 27-APR-21:10 | 34.92 | 17.25 | 0.187197E+11 | 11352.53 | 27-APR-21:30 | 34.55 | 17.23 |
May | 0.537088E+11 | 27817.76 | 05-MAY-21:10 | 36.73 | 18.90 | 0.193514E+11 | 11363.35 | 30-MAY-21:30 | 34.45 | 21.96 |
June | 0.525455E+11 | 28446.90 | 12-JUN-21:10 | 36.95 | 22.55 | 0.187615E+11 | 11371.18 | 09-JUN-22:00 | 36.95 | 22.55 |
July | 0.529216E+11 | 27731.64 | 07-JUL-21:10 | 34.58 | 25.98 | 0.193104E+11 | 11369.38 | 03-JUL-22:00 | 34.58 | 25.98 |
August | 0.515068E+11 | 26803.66 | 07-AUG-21:10 | 33.28 | 27.30 | 0.193919E+11 | 11360.78 | 08-AUG-21:30 | 32.40 | 27.12 |
September | 0.475319E+11 | 25726.50 | 01-SEP-21:10 | 30.68 | 26.00 | 0.187107E+11 | 11347.39 | 30-SEP-01:19 | 25.03 | 22.80 |
October | 0.457149E+11 | 24555.96 | 03-OCT-21:10 | 27.92 | 22.53 | 0.193129E+11 | 11348.97 | 20-OCT-22:10 | 21.75 | 16.56 |
November | 0.390586E+11 | 22062.52 | 08-NOV-22:10 | 19.85 | 17.54 | 0.186389E+11 | 11348.85 | 02-NOV-22:10 | 19.85 | 17.54 |
December | 0.360835E+11 | 20641.12 | 28-DEC-22:10 | 17.95 | 13.92 | 0.191144E+11 | 11348.39 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.541095E+12 | 0.227108E+12 | ||||||||
Minimum of Months | 0.347590E+11 | 20278.82 | 17.50 | 13.55 | 0.173628E+11 | 11347.39 | 16.43 | 13.26 | ||
Maximum of Months | 0.537088E+11 | 28446.90 | 36.95 | 27.30 | 0.193919E+11 | 11371.18 | 36.95 | 27.12 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484017E+11 | 26584.93 | 26-JAN-11:50 | 21.12 | 13.59 | 0.188196E+11 | 11319.58 | 07-JAN-18:19 | 21.12 | 13.59 |
February | 0.460209E+11 | 28083.91 | 22-FEB-11:45 | 25.10 | 15.22 | 0.170149E+11 | 11319.61 | 04-FEB-18:19 | 25.10 | 15.22 |
March | 0.550015E+11 | 30002.00 | 11-MAR-11:45 | 29.73 | 18.81 | 0.188663E+11 | 11319.66 | 11-MAR-18:19 | 28.90 | 19.64 |
April | 0.577935E+11 | 32162.72 | 16-APR-10:50 | 36.58 | 21.89 | 0.182617E+11 | 11319.68 | 01-APR-17:19 | 36.58 | 21.89 |
May | 0.619896E+11 | 32656.27 | 04-MAY-10:50 | 40.37 | 22.14 | 0.188720E+11 | 11319.68 | 13-MAY-17:19 | 33.17 | 22.98 |
June | 0.597129E+11 | 32476.01 | 12-JUN-18:08 | 42.22 | 22.60 | 0.182661E+11 | 11319.67 | 03-JUN-17:19 | 42.22 | 22.60 |
July | 0.604192E+11 | 32068.25 | 07-JUL-10:33 | 37.63 | 24.76 | 0.188683E+11 | 11319.67 | 29-JUL-17:19 | 33.57 | 26.66 |
August | 0.595172E+11 | 31191.30 | 07-AUG-18:03 | 35.77 | 27.05 | 0.188756E+11 | 11319.67 | 12-AUG-17:19 | 32.77 | 27.21 |
September | 0.563847E+11 | 30599.82 | 24-SEP-10:50 | 32.35 | 25.28 | 0.182614E+11 | 11319.68 | 30-SEP-17:19 | 33.67 | 23.54 |
October | 0.569044E+11 | 30787.05 | 01-OCT-10:50 | 31.62 | 19.69 | 0.188664E+11 | 11319.69 | 07-OCT-17:19 | 30.47 | 18.85 |
November | 0.513468E+11 | 28770.21 | 09-NOV-11:50 | 28.17 | 18.34 | 0.182402E+11 | 11319.68 | 04-NOV-17:19 | 28.17 | 18.34 |
December | 0.491508E+11 | 27051.86 | 03-DEC-11:50 | 22.38 | 14.19 | 0.188237E+11 | 11319.66 | 16-DEC-18:19 | 18.63 | 14.47 |
Annual Sum or Average | 0.662643E+12 | 0.222036E+12 | ||||||||
Minimum of Months | 0.460209E+11 | 26584.93 | 21.12 | 13.59 | 0.170149E+11 | 11319.58 | 18.63 | 13.59 | ||
Maximum of Months | 0.619896E+11 | 32656.27 | 42.22 | 27.05 | 0.188756E+11 | 11319.69 | 42.22 | 27.21 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.671924E+10 | 4016.93 | 12-JAN-19:10 | 18.12 | 13.15 | 0.130304E+10 | 829.24 | 25-JAN-22:19 | 16.70 | 13.27 |
February | 0.815213E+10 | 4970.87 | 22-FEB-19:08 | 23.30 | 15.09 | 0.124880E+10 | 933.17 | 22-FEB-22:10 | 19.68 | 14.28 |
March | 0.116864E+11 | 7580.96 | 28-MAR-15:40 | 35.53 | 18.66 | 0.155439E+10 | 1007.40 | 29-MAR-21:19 | 26.20 | 18.28 |
April | 0.148096E+11 | 9797.39 | 16-APR-15:03 | 39.63 | 22.37 | 0.162109E+10 | 1007.42 | 19-APR-21:30 | 31.40 | 18.58 |
May | 0.177659E+11 | 11115.23 | 04-MAY-15:13 | 42.27 | 22.20 | 0.170854E+10 | 1007.41 | 08-MAY-21:30 | 33.55 | 19.72 |
June | 0.174352E+11 | 11083.13 | 08-JUN-15:30 | 44.55 | 22.34 | 0.165343E+10 | 1007.41 | 05-JUN-21:30 | 44.55 | 22.34 |
July | 0.166525E+11 | 9982.43 | 07-JUL-15:40 | 40.20 | 24.67 | 0.170547E+10 | 1007.40 | 06-JUL-21:30 | 40.20 | 24.67 |
August | 0.154562E+11 | 9003.25 | 08-AUG-15:30 | 36.85 | 26.57 | 0.170716E+10 | 1007.39 | 02-AUG-21:30 | 36.85 | 26.57 |
September | 0.139792E+11 | 8639.83 | 26-SEP-15:03 | 36.05 | 22.65 | 0.161825E+10 | 1007.39 | 25-SEP-21:19 | 36.05 | 22.65 |
October | 0.133034E+11 | 8779.89 | 02-OCT-15:03 | 36.32 | 21.08 | 0.163368E+10 | 1007.40 | 02-OCT-21:19 | 25.47 | 20.14 |
November | 0.104245E+11 | 5499.36 | 09-NOV-15:10 | 29.07 | 17.68 | 0.143548E+10 | 967.19 | 09-NOV-22:10 | 19.68 | 16.56 |
December | 0.777785E+10 | 4253.10 | 28-DEC-19:10 | 20.73 | 14.41 | 0.132063E+10 | 861.77 | 28-DEC-22:10 | 17.95 | 13.92 |
Annual Sum or Average | 0.154162E+12 | 0.185100E+11 | ||||||||
Minimum of Months | 0.671924E+10 | 4016.93 | 18.12 | 13.15 | 0.124880E+10 | 829.24 | 16.70 | 13.27 | ||
Maximum of Months | 0.177659E+11 | 11115.23 | 44.55 | 26.57 | 0.170854E+10 | 1007.42 | 44.55 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6635701.22 | 351.91 | 02-JAN-07:10 | 6.78 |
February | 894648.23 | 176.58 | 11-FEB-07:05 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 323561.18 | 180.18 | 23-DEC-07:05 | 6.25 |
Annual Sum or Average | 7853910.62 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 6635701.22 | 351.91 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6547.57 | 6.37 | 02-JAN-10:08 | 10.20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 6547.57 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 6547.57 | 6.37 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81535409.08 | 1131.55 | 01-JAN-16:03 | 15.52 |
February | 18179145.48 | 1123.09 | 11-FEB-19:03 | 17.67 |
March | 2413532.58 | 1008.50 | 01-MAR-09:03 | 16.07 |
April | 1160309.16 | 1046.86 | 11-APR-08:04 | 22.90 |
May | 410497.68 | 713.34 | 13-MAY-08:04 | 24.87 |
June | 470675.74 | 815.77 | 25-JUN-08:04 | 27.88 |
July | 496108.21 | 777.28 | 28-JUL-08:04 | 27.58 |
August | 798126.49 | 812.14 | 11-AUG-08:04 | 27.25 |
September | 1630234.79 | 943.14 | 04-SEP-08:04 | 25.58 |
October | 1981815.63 | 1047.45 | 23-OCT-08:04 | 21.77 |
November | 2499621.95 | 1044.70 | 25-NOV-19:04 | 17.82 |
December | 31124654.16 | 1158.42 | 20-DEC-19:03 | 14.82 |
Annual Sum or Average | 0.142700E+09 | |||
Minimum of Months | 410497.68 | 713.34 | 14.82 | |
Maximum of Months | 81535409.08 | 1158.42 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179231E+09 | 1128.37 | 27-JAN-16:03 | 16.42 |
February | 31211872.46 | 1146.45 | 18-FEB-09:03 | 14.02 |
March | 2172370.30 | 1050.70 | 08-MAR-09:53 | 23.10 |
April | 716973.16 | 918.01 | 02-APR-06:44 | 24.75 |
May | 353569.30 | 606.56 | 24-MAY-08:04 | 25.67 |
June | 460797.36 | 827.86 | 25-JUN-08:04 | 27.88 |
July | 503662.75 | 773.58 | 28-JUL-08:04 | 27.58 |
August | 858151.51 | 813.21 | 23-AUG-08:04 | 27.25 |
September | 1880203.59 | 967.15 | 04-SEP-08:04 | 25.58 |
October | 1344240.14 | 876.46 | 23-OCT-08:54 | 23.60 |
November | 3116990.15 | 1102.19 | 24-NOV-09:03 | 16.07 |
December | 81432270.91 | 1161.40 | 30-DEC-16:03 | 14.92 |
Annual Sum or Average | 0.303282E+09 | |||
Minimum of Months | 353569.30 | 606.56 | 14.02 | |
Maximum of Months | 0.179231E+09 | 1161.40 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2533386.09 | 329.67 | 15-JAN-16:05 | 14.23 |
February | 1369875.15 | 330.96 | 09-FEB-16:05 | 17.52 |
March | 941944.30 | 297.04 | 19-MAR-08:54 | 18.60 |
April | 370396.13 | 284.66 | 07-APR-08:54 | 25.50 |
May | 168101.51 | 133.42 | 30-MAY-08:06 | 32.52 |
June | 119751.47 | 161.78 | 24-JUN-15:06 | 25.62 |
July | 51313.54 | 81.94 | 03-JUL-08:06 | 30.90 |
August | 96275.74 | 86.41 | 20-AUG-18:06 | 26.28 |
September | 143308.73 | 143.97 | 27-SEP-08:06 | 26.72 |
October | 789201.61 | 293.29 | 29-OCT-08:54 | 21.30 |
November | 975449.06 | 318.06 | 27-NOV-09:04 | 14.70 |
December | 2247178.17 | 333.54 | 31-DEC-19:03 | 10.68 |
Annual Sum or Average | 9806181.49 | |||
Minimum of Months | 51313.54 | 81.94 | 10.68 | |
Maximum of Months | 2533386.09 | 333.54 | 32.52 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84124080.55 | 1088.02 | 02-JAN-16:03 | 17.95 |
February | 18042738.17 | 1057.02 | 26-FEB-16:04 | 20.93 |
March | 816700.77 | 1051.42 | 14-MAR-08:04 | 21.43 |
April | 10599.28 | 123.66 | 22-APR-18:04 | 22.77 |
May | 3256.86 | 38.00 | 24-MAY-08:04 | 25.67 |
June | 10247.87 | 116.92 | 25-JUN-08:04 | 27.88 |
July | 85844.12 | 419.61 | 27-JUL-08:04 | 27.32 |
August | 125019.48 | 581.69 | 16-AUG-08:04 | 24.65 |
September | 350148.60 | 836.15 | 07-SEP-08:04 | 24.37 |
October | 608325.38 | 635.54 | 30-OCT-08:05 | 18.63 |
November | 2002879.29 | 1060.62 | 28-NOV-19:04 | 19.52 |
December | 34243304.21 | 1110.82 | 20-DEC-19:03 | 14.82 |
Annual Sum or Average | 0.140423E+09 | |||
Minimum of Months | 3256.86 | 38.00 | 14.82 | |
Maximum of Months | 84124080.55 | 1110.82 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171857E+09 | 1110.14 | 27-JAN-16:03 | 16.42 |
February | 30414218.48 | 1064.39 | 26-FEB-16:04 | 20.93 |
March | 1161834.29 | 853.52 | 21-MAR-21:54 | 20.20 |
April | 108209.17 | 797.93 | 02-APR-06:44 | 24.75 |
May | 4059.49 | 47.36 | 24-MAY-08:04 | 25.67 |
June | 20699.88 | 150.77 | 18-JUN-06:54 | 24.80 |
July | 89022.85 | 434.89 | 27-JUL-08:04 | 27.32 |
August | 136575.31 | 634.73 | 16-AUG-08:04 | 24.65 |
September | 370902.16 | 835.21 | 07-SEP-08:04 | 24.37 |
October | 313359.10 | 385.18 | 22-OCT-08:55 | 23.00 |
November | 2953554.23 | 1061.69 | 26-NOV-16:04 | 22.62 |
December | 87282571.27 | 1092.13 | 19-DEC-16:03 | 16.52 |
Annual Sum or Average | 0.294712E+09 | |||
Minimum of Months | 4059.49 | 47.36 | 16.42 | |
Maximum of Months | 0.171857E+09 | 1110.14 | 27.32 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264887E+09 | 1225.20 | 02-JAN-09:02 | 8.57 |
February | 81201006.18 | 1216.79 | 24-FEB-09:03 | 18.72 |
March | 2280804.14 | 1107.38 | 24-MAR-08:03 | 19.40 |
April | 1307059.69 | 829.62 | 24-APR-08:04 | 26.45 |
May | 459667.22 | 862.81 | 13-MAY-08:04 | 24.87 |
June | 533647.88 | 792.94 | 18-JUN-08:04 | 26.23 |
July | 760661.32 | 887.89 | 28-JUL-08:04 | 27.58 |
August | 1212348.44 | 920.32 | 16-AUG-08:04 | 24.65 |
September | 1786658.17 | 914.01 | 07-SEP-08:04 | 24.37 |
October | 1777870.34 | 912.51 | 11-OCT-08:04 | 24.20 |
November | 11185249.24 | 1148.96 | 01-NOV-08:03 | 19.27 |
December | 0.168677E+09 | 1322.92 | 20-DEC-19:03 | 14.82 |
Annual Sum or Average | 0.536069E+09 | |||
Minimum of Months | 459667.22 | 792.94 | 8.57 | |
Maximum of Months | 0.264887E+09 | 1322.92 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404269E+09 | 1251.60 | 27-JAN-16:03 | 16.42 |
February | 0.106642E+09 | 1204.88 | 03-FEB-09:02 | 11.77 |
March | 2416698.33 | 1127.84 | 12-MAR-08:53 | 23.60 |
April | 1056616.60 | 1272.92 | 11-APR-08:53 | 24.90 |
May | 357846.84 | 696.56 | 24-MAY-08:04 | 25.67 |
June | 513645.29 | 740.51 | 25-JUN-08:04 | 27.88 |
July | 743486.22 | 883.74 | 28-JUL-08:04 | 27.58 |
August | 1215205.72 | 908.18 | 16-AUG-08:04 | 24.65 |
September | 1994630.90 | 912.62 | 07-SEP-08:04 | 24.37 |
October | 2399510.97 | 1126.66 | 16-OCT-08:43 | 25.87 |
November | 18020157.28 | 977.03 | 13-NOV-09:53 | 22.20 |
December | 0.282942E+09 | 1417.68 | 30-DEC-16:03 | 14.92 |
Annual Sum or Average | 0.822569E+09 | |||
Minimum of Months | 357846.84 | 696.56 | 11.77 | |
Maximum of Months | 0.404269E+09 | 1417.68 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26031244.46 | 705.49 | 17-JAN-16:04 | 18.03 |
February | 8941367.70 | 587.28 | 09-FEB-16:05 | 17.52 |
March | 864570.87 | 532.29 | 08-MAR-09:04 | 20.93 |
April | 929925.72 | 541.61 | 18-APR-08:04 | 27.33 |
May | 347898.25 | 559.20 | 24-MAY-08:04 | 25.67 |
June | 312831.45 | 520.60 | 24-JUN-08:04 | 25.47 |
July | 345291.58 | 537.06 | 26-JUL-08:04 | 26.73 |
August | 463792.97 | 554.33 | 16-AUG-08:04 | 24.65 |
September | 798797.81 | 553.58 | 07-SEP-08:04 | 24.37 |
October | 854334.19 | 542.29 | 16-OCT-08:04 | 24.53 |
November | 567511.66 | 460.61 | 24-NOV-09:04 | 16.07 |
December | 11194974.92 | 697.81 | 29-DEC-16:04 | 18.80 |
Annual Sum or Average | 51652541.59 | |||
Minimum of Months | 312831.45 | 460.61 | 16.07 | |
Maximum of Months | 26031244.46 | 705.49 | 27.33 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11618970.07 | 652.51 | 02-JAN-07:10 | 6.78 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 3786679.01 | 480.90 | 23-DEC-07:05 | 6.25 |
Annual Sum or Average | 15405649.07 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 11618970.07 | 652.51 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130686E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.115659E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122401E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.112923E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.113962E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.110160E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.116226E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.120801E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.119632E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128199E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.124447E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.130028E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.144512E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.110160E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.130686E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.942056E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.848830E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.938246E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899586E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.930799E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.902391E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.930156E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.938921E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.906518E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.939883E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.911363E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.938795E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110275E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.848830E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.942056E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.276089E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.245113E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264878E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248402E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.252769E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.245060E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.255172E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.261552E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256188E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.270324E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.264360E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.275074E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311498E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.245060E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.276089E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.276089E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.245113E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264878E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248402E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.252769E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.245060E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.255172E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.261552E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256188E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.270324E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.264360E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.275074E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311498E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.245060E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.276089E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267392E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027959.48 | 0.155321E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41278662.88 | 66218042.57 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158367E+09 | 5721335.18 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263192E+09 | 15522.04 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273401E+09 | 0.00 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227373E+09 | 0.00 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181771E+09 | 27216.37 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145109E+09 | 27232.42 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77843502.00 | 34822666.96 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19739008.80 | 0.125616E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139406.87 | 0.239216E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139124E+10 | 0.894378E+09 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273401E+09 | 0.267392E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115822.77 | 0.109158E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2703164.68 | 66556367.88 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18129137.71 | 31811696.54 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61310743.19 | 3569635.94 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101385E+09 | 89506.08 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104830E+09 | 17859.56 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87293892.96 | 13937.82 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69497720.85 | 10768.28 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54247562.11 | 29243.02 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31139995.97 | 16964600.29 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10141659.71 | 54759046.42 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 576749.10 | 99653871.99 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541372E+09 | 0.382635E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 115822.77 | 10768.28 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104830E+09 | 0.109158E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 917073.15 | 0.229027E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10762112.67 | 0.133271E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50540173.07 | 60078195.83 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148753E+09 | 6592448.91 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239482E+09 | 126381.15 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247743E+09 | 23895.97 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205649E+09 | 18820.33 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163491E+09 | 25516.85 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129094E+09 | 58078.43 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78607340.02 | 33570451.66 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30909650.63 | 0.108651E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3225688.19 | 0.203960E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130917E+10 | 0.775403E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 917073.15 | 18820.33 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247743E+09 | 0.229027E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483102.88 | 0.132235E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868726.23 | 77004739.27 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28993254.03 | 34387757.44 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86144053.87 | 3656719.71 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138245E+09 | 69977.44 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142971E+09 | 11647.40 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118722E+09 | 10530.22 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94428084.24 | 14720.42 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74743846.06 | 28122.93 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45327334.64 | 18962126.37 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17301894.96 | 62707354.24 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1656569.04 | 0.118340E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754885E+09 | 0.447429E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483102.88 | 10530.22 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142971E+09 | 0.132235E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 39514.57 | 0.388759E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 5741226.47 | 0.231260E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 54775132.51 | 0.100401E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.203164E+09 | 9290518.77 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.335398E+09 | 84002.56 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.346530E+09 | 17757.82 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.290604E+09 | 0.00 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.233955E+09 | 15993.43 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.183665E+09 | 47834.65 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.102180E+09 | 47613696.73 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 30155204.29 | 0.175421E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 760254.24 | 0.346619E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.178697E+10 | 0.129953E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 39514.57 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.346530E+09 | 0.388759E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.130686E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676839E+09 |
February | 0.236489E+11 | 0.115659E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6266501.08 | 0.410517E+09 |
March | 0.262800E+11 | 0.122401E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88893457.03 | 0.185377E+09 |
April | 0.253579E+11 | 0.112923E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348629E+09 | 19608099.47 |
May | 0.262123E+11 | 0.113962E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581141E+09 | 503459.36 |
June | 0.254132E+11 | 0.110160E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600711E+09 | 103152.79 |
July | 0.261570E+11 | 0.116226E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501307E+09 | 104704.34 |
August | 0.262677E+11 | 0.120801E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399361E+09 | 60987.52 |
September | 0.253456E+11 | 0.119632E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310513E+09 | 161588.94 |
October | 0.261693E+11 | 0.128199E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171084E+09 | 95693485.46 |
November | 0.253025E+11 | 0.124447E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43573478.91 | 0.326595E+09 |
December | 0.261570E+11 | 0.130028E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211085.20 | 0.618000E+09 |
Annual Sum or Average | 0.308468E+12 | 0.144512E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305169E+10 | 0.233356E+10 |
Minimum of Months | 0.236489E+11 | 0.110160E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60987.52 |
Maximum of Months | 0.262800E+11 | 0.130686E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600711E+09 | 0.676839E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.942056E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 561301.51 | 0.190976E+10 |
February | 0.702046E+11 | 0.848830E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32854452.51 | 0.116649E+10 |
March | 0.780153E+11 | 0.938246E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280598E+09 | 0.545919E+09 |
April | 0.752779E+11 | 0.899586E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100138E+10 | 60330791.18 |
May | 0.778146E+11 | 0.930799E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165978E+10 | 1539886.91 |
June | 0.754422E+11 | 0.902391E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171361E+10 | 330106.85 |
July | 0.776503E+11 | 0.930156E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142711E+10 | 300533.18 |
August | 0.779788E+11 | 0.938921E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113532E+10 | 175575.40 |
September | 0.752414E+11 | 0.906518E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878249E+09 | 477407.32 |
October | 0.776868E+11 | 0.939883E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493941E+09 | 0.283373E+09 |
November | 0.751137E+11 | 0.911363E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142487E+09 | 0.938641E+09 |
December | 0.776503E+11 | 0.938795E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4302012.63 | 0.174552E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110275E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877018E+10 | 0.665286E+10 |
Minimum of Months | 0.702046E+11 | 0.848830E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 561301.51 | 175575.40 |
Maximum of Months | 0.780153E+11 | 0.942056E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171361E+10 | 0.190976E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61358.31 | 0.151135E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4328747.24 | 82432314.33 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36710117.32 | 27076769.78 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123000E+09 | 1255386.16 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189215E+09 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192951E+09 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168287E+09 | 0.00 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141793E+09 | 0.00 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116570E+09 | 0.00 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66248808.97 | 9099407.63 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18508402.19 | 56873544.26 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 353150.74 | 0.132325E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105803E+10 | 0.460197E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61358.31 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192951E+09 | 0.151135E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113147.53 | 0.147747E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3988745.02 | 85006567.44 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35274535.50 | 32279539.63 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121547E+09 | 2147123.94 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189112E+09 | 5216.24 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192857E+09 | 0.00 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168274E+09 | 0.00 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141792E+09 | 0.00 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116457E+09 | 0.00 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63909023.62 | 12314396.03 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18240792.52 | 62252406.12 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 682706.88 | 0.130032E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105225E+10 | 0.471785E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113147.53 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192857E+09 | 0.147747E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67923520.41 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3733.32 | 44748510.25 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2800047.22 | 24822061.88 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15836882.77 | 4918214.43 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29928823.72 | 493252.39 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31606358.42 | 328007.08 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23600283.30 | 125640.68 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16321935.64 | 463977.09 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10911376.64 | 1494090.14 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6471493.95 | 14881331.60 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 793501.33 | 35752832.85 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62819205.02 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138274E+09 | 0.258771E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125640.68 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31606358.42 | 67923520.41 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80923.29 | 41554872.33 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1415697.37 | 23649012.63 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10159826.19 | 8678304.41 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34199337.26 | 520088.46 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52962671.38 | 0.00 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53981886.99 | 0.00 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47094539.26 | 0.00 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39723089.50 | 0.00 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32716948.55 | 0.00 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18171355.85 | 3198645.65 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593220.88 | 17020138.21 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 327685.57 | 36331070.17 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296427E+09 | 0.130952E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80923.29 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53981886.99 | 41554872.33 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61431.34 | 0.152134E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4309957.88 | 83149758.16 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36661358.90 | 27424087.39 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122974E+09 | 1281185.91 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189277E+09 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192982E+09 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168252E+09 | 0.00 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141755E+09 | 0.00 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116524E+09 | 0.00 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66187598.31 | 9159002.12 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18453186.40 | 57210681.18 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 349863.21 | 0.132967E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105779E+10 | 0.463325E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61431.34 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192982E+09 | 0.152134E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166218.64 | 0.147705E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3887022.37 | 85781563.52 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35045538.51 | 33325410.13 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121366E+09 | 2470821.89 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189159E+09 | 7666.07 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192891E+09 | 0.00 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168238E+09 | 0.00 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141751E+09 | 0.00 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116396E+09 | 0.00 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63606394.37 | 12649116.70 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17998403.59 | 62951941.50 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702710.15 | 0.130040E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105121E+10 | 0.474932E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166218.64 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192891E+09 | 0.147705E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480931.82 | 0.179569E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6193136.05 | 0.107855E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34542368.84 | 51219743.24 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111285E+09 | 6024496.22 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183538E+09 | 143178.74 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189944E+09 | 27873.59 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158200E+09 | 23271.60 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126483E+09 | 22465.05 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100362E+09 | 54249.82 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56031952.01 | 29250190.10 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18876206.68 | 91956231.77 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1621721.25 | 0.163581E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987558E+09 | 0.629726E+09 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480931.82 | 22465.05 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189944E+09 | 0.179569E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55207.77 | 0.152085E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4174197.98 | 82959350.11 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36136843.32 | 27284307.63 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122007E+09 | 1271514.97 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188131E+09 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191940E+09 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167315E+09 | 0.00 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140817E+09 | 0.00 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115640E+09 | 0.00 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65498636.33 | 9167789.43 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18157413.80 | 57181519.14 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 317701.34 | 0.133172E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105019E+10 | 0.463122E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55207.77 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191940E+09 | 0.152085E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60298.62 | 0.149224E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3686525.24 | 86253851.45 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34768538.35 | 31958011.57 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120791E+09 | 1855683.50 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188039E+09 | 2384.86 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191859E+09 | 0.00 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167300E+09 | 0.00 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140815E+09 | 0.00 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115559E+09 | 0.00 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63474811.51 | 11401618.00 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17901743.31 | 61926011.81 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 509496.54 | 0.131027E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104476E+10 | 0.473648E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60298.62 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191859E+09 | 0.149224E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26766.80 | 79612094.32 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110833.01 | 43063784.52 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18450489.28 | 14096031.48 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62493078.47 | 654249.43 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96412674.25 | 0.00 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98298491.80 | 0.00 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85616295.93 | 0.00 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72050707.15 | 0.00 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59147595.24 | 0.00 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33435444.65 | 4766073.03 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9202607.32 | 29575726.51 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 158069.57 | 69379702.75 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537403E+09 | 0.241148E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26766.80 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98298491.80 | 79612094.32 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.276089E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21429.31 | 0.466131E+09 |
February | 0.415303E+11 | 0.245113E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4703474.14 | 0.284532E+09 |
March | 0.461508E+11 | 0.264878E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55150737.25 | 0.131081E+09 |
April | 0.445315E+11 | 0.248402E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217547E+09 | 14668016.07 |
May | 0.460320E+11 | 0.252769E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366857E+09 | 398083.84 |
June | 0.446286E+11 | 0.245060E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378890E+09 | 96469.64 |
July | 0.459349E+11 | 0.255172E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314681E+09 | 79611.08 |
August | 0.461292E+11 | 0.261552E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248967E+09 | 53406.71 |
September | 0.445099E+11 | 0.256188E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189905E+09 | 140095.77 |
October | 0.459565E+11 | 0.270324E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106722E+09 | 66511486.82 |
November | 0.444343E+11 | 0.264360E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28961098.14 | 0.218260E+09 |
December | 0.459349E+11 | 0.275074E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 487095.77 | 0.418659E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311498E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191289E+10 | 0.160061E+10 |
Minimum of Months | 0.415303E+11 | 0.245060E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21429.31 | 53406.71 |
Maximum of Months | 0.461508E+11 | 0.276089E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378890E+09 | 0.466131E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.276089E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.25 | 0.473524E+09 |
February | 0.415303E+11 | 0.245113E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4048998.06 | 0.288288E+09 |
March | 0.461508E+11 | 0.264878E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54506678.77 | 0.132155E+09 |
April | 0.445315E+11 | 0.248402E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217404E+09 | 14689270.21 |
May | 0.460320E+11 | 0.252769E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366843E+09 | 398113.72 |
June | 0.446286E+11 | 0.245060E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378869E+09 | 98712.63 |
July | 0.459349E+11 | 0.255172E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314657E+09 | 79622.25 |
August | 0.461292E+11 | 0.261552E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248940E+09 | 53416.02 |
September | 0.445099E+11 | 0.256188E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189831E+09 | 140115.48 |
October | 0.459565E+11 | 0.270324E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106250E+09 | 66678403.06 |
November | 0.444343E+11 | 0.264360E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27665983.70 | 0.219783E+09 |
December | 0.459349E+11 | 0.275074E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 273138.51 | 0.425087E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311498E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190929E+10 | 0.162098E+10 |
Minimum of Months | 0.415303E+11 | 0.245060E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.25 | 53416.02 |
Maximum of Months | 0.461508E+11 | 0.276089E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378869E+09 | 0.473524E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427185E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 3336388.86 | 0.257612E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48659915.02 | 0.117573E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.194711E+09 | 12992771.30 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.328522E+09 | 349870.09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.339324E+09 | 85143.04 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.281814E+09 | 59621.66 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.222988E+09 | 47973.87 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.170113E+09 | 125070.17 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95015190.79 | 59393418.10 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24142524.39 | 0.194995E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 83890.19 | 0.381481E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.170871E+10 | 0.145190E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47973.87 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.339324E+09 | 0.427185E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390764.15 | 0.319127E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8300705.88 | 0.185260E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55745255.98 | 83127649.03 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195477E+09 | 8022214.37 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323284E+09 | 128154.96 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334714E+09 | 5476.52 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277815E+09 | 6510.58 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221621E+09 | 45330.54 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176783E+09 | 24446.64 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97986932.83 | 44034184.06 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31293849.70 | 0.147686E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1928752.60 | 0.281109E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172534E+10 | 0.106858E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390764.15 | 5476.52 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334714E+09 | 0.319127E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 199.33 | 05-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 | 22-FEB-15:00 | 171.39 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 | 28-MAR-15:00 | 96.48 | 01-MAR-03:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.83 | 15-APR-15:00 | 59.84 | 11-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.23 | 03-MAY-15:00 | 1.69 | 13-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.84 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.95 | 07-AUG-15:00 | 6.84 | 15-AUG-24:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.09 | 17-SEP-20:00 | 7.33 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.83 | 02-OCT-14:00 | 78.87 | 31-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.34 | 04-NOV-14:00 | 138.37 | 27-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 28-DEC-14:00 | 197.33 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 | 199.33 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 12-JAN-15:00 | 81.56 | 05-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 | 22-FEB-14:05 | 71.55 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 | 28-MAR-15:00 | 44.43 | 01-MAR-04:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 15-APR-15:00 | 29.38 | 11-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 | 03-MAY-15:00 | 5.42 | 13-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.55 | 08-JUN-16:00 | 2.61 | 18-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 07-JUL-15:00 | 2.77 | 19-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 | 07-AUG-15:00 | 2.64 | 15-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.39 | 17-SEP-20:00 | 4.40 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 | 02-OCT-14:00 | 37.15 | 31-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 04-NOV-14:00 | 62.08 | 27-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 24-DEC-15:00 | 81.81 | 21-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 2.61 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 83.55 | 81.81 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 12-JAN-15:00 | 181.83 | 05-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 22-FEB-15:00 | 156.32 | 02-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.21 | 28-MAR-15:00 | 92.64 | 05-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.49 | 15-APR-15:00 | 60.37 | 11-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.26 | 03-MAY-15:00 | 8.36 | 13-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 | 08-JUN-16:00 | 4.34 | 18-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.50 | 07-JUL-15:00 | 4.27 | 19-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.32 | 07-AUG-15:00 | 6.25 | 15-AUG-24:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 17-SEP-20:00 | 9.51 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.48 | 02-OCT-14:00 | 77.14 | 31-OCT-05:10 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.27 | 04-NOV-14:00 | 132.94 | 27-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 | 24-DEC-15:00 | 180.01 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 4.27 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 | 181.83 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 12-JAN-15:00 | 104.92 | 05-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 | 22-FEB-15:00 | 90.19 | 02-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 28-MAR-15:00 | 53.41 | 05-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 | 15-APR-15:00 | 34.54 | 11-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.81 | 03-MAY-15:00 | 4.84 | 13-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.93 | 08-JUN-16:00 | 2.38 | 18-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 | 07-JUL-15:00 | 2.42 | 19-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 07-AUG-15:00 | 3.60 | 15-AUG-24:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.89 | 17-SEP-20:00 | 5.17 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 | 02-OCT-14:00 | 44.61 | 31-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.87 | 04-NOV-14:00 | 77.18 | 27-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | 24-DEC-15:00 | 103.85 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 2.38 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 113.93 | 104.92 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 6.03 | 08-JAN-15:00 | 294.09 | 05-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 47.89 | 22-FEB-15:00 | 258.06 | 02-FEB-06:10 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 166.60 | 28-MAR-16:00 | 151.46 | 01-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 221.40 | 15-APR-15:20 | 91.61 | 11-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 273.10 | 03-MAY-15:40 | 15.08 | 13-MAY-05:30 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 276.37 | 08-JUN-16:00 | 7.27 | 18-JUN-05:20 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 232.35 | 02-JUL-16:40 | 0.00 | 01-JUL-00:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 184.17 | 07-AUG-15:40 | 8.52 | 15-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 181.98 | 17-SEP-20:00 | 11.82 | 27-SEP-05:20 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 175.19 | 01-OCT-15:20 | 123.74 | 31-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 93.17 | 04-NOV-15:10 | 215.30 | 27-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 26.70 | 24-DEC-15:00 | 284.50 | 21-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 276.37 | 294.09 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 479.84 | 05-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.24 | 22-FEB-15:00 | 423.51 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.59 | 28-MAR-15:00 | 270.56 | 01-MAR-03:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.51 | 15-APR-15:00 | 170.58 | 11-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.02 | 03-MAY-15:00 | 32.77 | 13-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.55 | 08-JUN-16:00 | 15.35 | 18-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.53 | 07-JUL-15:00 | 19.97 | 19-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.24 | 07-AUG-15:00 | 15.02 | 15-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.00 | 17-SEP-20:00 | 25.10 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.29 | 02-OCT-14:00 | 221.41 | 31-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.53 | 04-NOV-14:00 | 369.23 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 28-DEC-14:00 | 481.81 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 478.55 | 481.81 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 12-JAN-15:00 | 1389.72 | 05-JAN-06:03 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.54 | 22-FEB-15:00 | 1241.01 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 813.11 | 28-MAR-15:00 | 777.37 | 01-MAR-04:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.29 | 15-APR-15:00 | 487.55 | 11-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1365.75 | 03-MAY-15:00 | 93.83 | 13-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.23 | 08-JUN-16:00 | 50.05 | 18-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.35 | 07-JUL-15:00 | 57.25 | 19-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 909.21 | 07-AUG-15:00 | 43.10 | 15-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 922.76 | 17-SEP-20:00 | 71.91 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 857.96 | 02-OCT-14:00 | 632.81 | 31-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.20 | 04-NOV-14:00 | 1075.65 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.35 | 24-DEC-15:00 | 1401.80 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 43.10 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.23 | 1401.80 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 12-JAN-16:07 | 116.79 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 22-FEB-16:10 | 100.54 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 28-MAR-15:10 | 54.01 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.77 | 15-APR-15:10 | 25.50 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.63 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.94 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.76 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.57 | 02-OCT-15:10 | 38.70 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 04-NOV-15:09 | 81.38 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 28-DEC-16:07 | 115.62 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 140.94 | 116.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 12-JAN-16:07 | 116.78 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 22-FEB-16:07 | 100.53 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 | 28-MAR-15:10 | 54.01 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.49 | 15-APR-15:10 | 30.27 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.30 | 03-MAY-15:10 | 3.13 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.72 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.76 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 | 02-OCT-15:10 | 41.27 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 04-NOV-15:10 | 81.37 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 24-DEC-14:00 | 115.61 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 0.00 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 140.72 | 116.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 43.16 | 05-JAN-07:10 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 22-FEB-15:00 | 38.34 | 02-FEB-07:20 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 28-MAR-15:00 | 25.72 | 01-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 | 15-APR-15:00 | 17.64 | 11-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 | 03-MAY-15:00 | 7.42 | 13-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 08-JUN-16:00 | 6.24 | 18-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 07-JUL-15:00 | 6.44 | 19-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 07-AUG-15:00 | 6.09 | 15-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17-SEP-20:00 | 6.84 | 27-SEP-05:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.19 | 02-OCT-14:00 | 21.40 | 31-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 04-NOV-14:00 | 33.44 | 27-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.89 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 43.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 12-JAN-16:10 | 32.59 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 22-FEB-16:09 | 28.06 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 28-MAR-15:09 | 15.08 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 15-APR-15:10 | 7.89 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 07-AUG-15:08 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 02-OCT-15:09 | 11.33 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 04-NOV-15:09 | 22.71 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 24-DEC-14:00 | 32.27 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 32.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 12-JAN-16:09 | 116.79 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 22-FEB-16:09 | 100.54 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 28-MAR-15:10 | 54.01 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.51 | 15-APR-15:10 | 25.50 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.14 | 03-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.98 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.71 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 | 02-OCT-15:10 | 38.70 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 04-NOV-15:10 | 81.38 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 28-DEC-16:07 | 115.62 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 142.98 | 116.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 12-JAN-16:07 | 116.78 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 22-FEB-16:07 | 100.53 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 | 28-MAR-15:09 | 54.01 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.70 | 15-APR-15:10 | 29.62 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.63 | 03-MAY-16:00 | 3.48 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.97 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.71 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 | 02-OCT-15:10 | 40.92 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 04-NOV-15:07 | 81.37 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 24-DEC-14:00 | 115.61 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 0.00 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 142.97 | 116.78 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 12-JAN-15:00 | 140.27 | 05-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 | 22-FEB-15:00 | 122.24 | 02-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.76 | 28-MAR-15:00 | 74.56 | 01-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.38 | 15-APR-15:00 | 50.56 | 11-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.44 | 03-MAY-15:00 | 8.93 | 13-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.61 | 08-JUN-16:00 | 4.56 | 18-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 | 07-JUL-15:00 | 4.79 | 19-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.70 | 07-AUG-15:00 | 5.14 | 15-AUG-24:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.20 | 17-SEP-20:00 | 8.27 | 27-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 02-OCT-14:00 | 64.69 | 31-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 04-NOV-14:00 | 108.16 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 | 24-DEC-15:00 | 141.42 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 4.56 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.61 | 141.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 12-JAN-16:09 | 117.24 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 | 22-FEB-16:09 | 100.98 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 | 28-MAR-16:00 | 54.43 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.57 | 15-APR-16:00 | 25.91 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.40 | 01-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.34 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.35 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.87 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.31 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 | 02-OCT-15:10 | 39.11 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.39 | 04-NOV-15:10 | 81.81 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 28-DEC-16:10 | 116.07 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 138.34 | 117.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 12-JAN-16:07 | 117.22 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 22-FEB-16:10 | 100.97 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.26 | 28-MAR-15:10 | 54.43 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 15-APR-15:10 | 26.27 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.68 | 01-MAY-16:00 | 1.70 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.34 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.85 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.30 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.96 | 02-OCT-15:10 | 39.11 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 04-NOV-15:10 | 81.80 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 28-DEC-16:10 | 116.06 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 0.00 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 117.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 12-JAN-16:10 | 59.98 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 22-FEB-16:10 | 51.66 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 28-MAR-15:50 | 27.85 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.81 | 15-APR-15:10 | 13.25 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 03-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.96 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.98 | 02-OCT-15:50 | 20.01 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 04-NOV-15:10 | 41.86 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 28-DEC-16:10 | 59.38 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 72.96 | 59.98 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 12-JAN-15:00 | 334.45 | 05-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.81 | 22-FEB-15:00 | 296.23 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.36 | 28-MAR-15:00 | 181.32 | 01-MAR-04:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.30 | 15-APR-15:00 | 111.06 | 11-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.01 | 03-MAY-15:00 | 22.65 | 13-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.36 | 08-JUN-16:00 | 12.82 | 18-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.33 | 07-JUL-15:00 | 14.43 | 19-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.51 | 07-AUG-15:00 | 11.26 | 15-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.57 | 17-SEP-20:00 | 17.73 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.98 | 02-OCT-14:00 | 143.67 | 31-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 04-NOV-14:00 | 248.93 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 24-DEC-15:00 | 332.50 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 11.26 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 305.36 | 334.45 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 12-JAN-15:00 | 336.56 | 05-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 22-FEB-15:00 | 296.23 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.35 | 28-MAR-15:00 | 181.33 | 01-MAR-04:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.30 | 15-APR-15:00 | 111.06 | 11-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.01 | 03-MAY-15:00 | 22.65 | 13-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.36 | 08-JUN-16:00 | 12.82 | 18-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.33 | 07-JUL-15:00 | 14.43 | 19-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.51 | 07-AUG-15:00 | 11.26 | 15-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.57 | 17-SEP-20:00 | 17.73 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.98 | 02-OCT-14:00 | 143.67 | 31-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 04-NOV-14:00 | 248.93 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 28-DEC-14:00 | 333.80 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 11.26 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 305.36 | 336.56 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 301.22 | 05-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 43.00 | 22-FEB-15:00 | 264.93 | 02-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 159.79 | 28-MAR-15:00 | 156.70 | 01-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 220.62 | 15-APR-15:00 | 99.43 | 11-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 273.18 | 03-MAY-15:00 | 20.29 | 13-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 273.54 | 08-JUN-16:00 | 11.47 | 18-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 220.64 | 07-JUL-15:00 | 10.58 | 19-JUL-02:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 181.41 | 07-AUG-15:00 | 10.11 | 15-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 184.13 | 17-SEP-20:00 | 15.88 | 27-SEP-05:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 171.08 | 02-OCT-14:00 | 128.63 | 31-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 87.95 | 04-NOV-14:00 | 221.95 | 27-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 7.31 | 28-DEC-14:00 | 292.16 | 21-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 273.54 | 301.22 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 12-JAN-15:00 | 249.15 | 05-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.35 | 22-FEB-14:05 | 214.39 | 02-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.25 | 28-MAR-15:00 | 121.33 | 01-MAR-03:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.79 | 15-APR-15:00 | 76.47 | 11-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.22 | 03-MAY-15:00 | 9.18 | 13-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.51 | 08-JUN-16:00 | 2.39 | 18-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.81 | 07-JUL-15:00 | 1.59 | 19-JUL-02:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.41 | 07-AUG-15:00 | 9.94 | 15-AUG-24:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.07 | 17-SEP-20:00 | 8.04 | 27-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 | 02-OCT-14:00 | 101.68 | 31-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 04-NOV-13:05 | 173.80 | 27-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 24-DEC-14:05 | 246.66 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 1.59 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.51 | 249.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18741.27 | 13-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18652.20 | 23-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17684.68 | 14-MAR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19128.39 | 20-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21916.76 | 05-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24784.45 | 08-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27582.18 | 07-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28756.72 | 08-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28738.76 | 26-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27864.42 | 03-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25778.13 | 01-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23319.90 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17684.68 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28756.72 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2098.95 | 12-JAN-14:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
February | 2794.67 | 22-FEB-14:05 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 0.00 |
March | 3719.43 | 28-MAR-15:03 | 4548.18 | 1161.99 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 126.72 | 0.00 |
April | 4426.43 | 28-APR-18:03 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 151.71 | 0.00 |
May | 4939.95 | 04-MAY-18:03 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 173.92 | 0.00 |
June | 4930.33 | 12-JUN-18:03 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 192.32 | 0.00 |
July | 4427.29 | 07-JUL-18:03 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 | 0.00 |
August | 4140.41 | 07-AUG-18:03 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 127.89 | 0.00 |
September | 4263.17 | 26-SEP-14:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 128.21 | 0.00 |
October | 4576.51 | 02-OCT-14:20 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 135.77 | 0.00 |
November | 3785.38 | 09-NOV-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 59.91 | 0.00 |
December | 2741.98 | 02-DEC-13:50 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2098.95 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4939.95 | 5457.82 | 3187.16 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 192.32 | 6.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1423.76 | 12-JAN-19:10 | 7373.52 | 4305.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 |
February | 1785.64 | 22-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
March | 2592.77 | 28-MAR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 0.00 |
April | 3215.26 | 28-APR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | 0.00 |
May | 3423.72 | 04-MAY-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 45.82 | 0.00 |
June | 3495.87 | 12-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 0.00 |
July | 3261.70 | 03-JUL-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 0.00 |
August | 3047.28 | 07-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 42.49 | 0.00 |
September | 2822.00 | 22-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 0.00 |
October | 2775.28 | 02-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
November | 2061.62 | 09-NOV-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
December | 1476.49 | 28-DEC-19:10 | 7373.52 | 4305.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1423.76 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3495.87 | 7373.52 | 4305.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 22.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1393.03 | 14-JAN-19:10 | 1336.61 | 3724.96 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
February | 1651.89 | 23-FEB-19:10 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
March | 2010.66 | 29-MAR-18:10 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 73.06 | 0.00 |
April | 3273.20 | 28-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 110.82 | 0.00 |
May | 3813.76 | 04-MAY-19:50 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 115.77 | 0.00 |
June | 4188.33 | 12-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 | 0.00 |
July | 3925.35 | 07-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 115.63 | 0.00 |
August | 3497.45 | 08-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 92.10 | 0.00 |
September | 3021.28 | 01-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 75.64 | 0.00 |
October | 2441.44 | 02-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | 0.00 |
November | 1783.60 | 09-NOV-19:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
December | 1452.39 | 28-DEC-19:10 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1393.03 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4188.33 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 | 30.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 756.58 | 14-JAN-19:09 | 1028.16 | 1371.08 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 |
February | 891.68 | 23-FEB-19:10 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
March | 1082.51 | 29-MAR-18:10 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 42.89 | 0.00 |
April | 1602.79 | 28-APR-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 | 0.00 |
May | 1885.69 | 04-MAY-19:30 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 71.91 | 0.00 |
June | 2084.46 | 12-JUN-19:50 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 0.00 |
July | 1944.77 | 07-JUL-19:50 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 0.00 |
August | 1724.50 | 08-AUG-19:40 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 | 0.00 |
September | 1478.54 | 01-SEP-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 | 0.00 |
October | 1167.49 | 03-OCT-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 | 0.00 |
November | 963.03 | 09-NOV-19:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
December | 788.75 | 28-DEC-19:10 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 756.58 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2084.46 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 17.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33728.41 | 26-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 135.10 |
February | 34982.54 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 |
March | 36780.19 | 28-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 66.85 | 0.00 |
April | 38248.87 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 151.33 | 0.00 |
May | 39141.44 | 04-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 151.99 | 0.00 |
June | 39192.29 | 12-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 195.55 | 0.00 |
July | 38865.18 | 07-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 157.89 | 0.00 |
August | 37954.55 | 07-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 138.84 | 0.00 |
September | 37178.78 | 22-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 88.69 | 0.00 |
October | 36984.60 | 02-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 47.74 | 0.00 |
November | 35263.71 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 |
December | 33842.08 | 28-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 33728.41 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39192.29 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 195.55 | 135.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9232.98 | 12-JAN-16:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
February | 11093.82 | 20-FEB-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 0.00 |
March | 13537.25 | 28-MAR-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 280.14 | 0.00 |
April | 14751.85 | 27-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 | 0.00 |
May | 15520.68 | 05-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 304.77 | 0.00 |
June | 15713.88 | 12-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 307.89 | 0.00 |
July | 15081.35 | 07-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 254.52 | 0.00 |
August | 14483.45 | 07-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 225.23 | 0.00 |
September | 14542.17 | 26-SEP-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 289.89 | 0.00 |
October | 15407.86 | 02-OCT-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 298.05 | 0.00 |
November | 13546.18 | 04-NOV-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 153.11 | 0.00 |
December | 11377.23 | 02-DEC-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9232.98 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15713.88 | 59766.00 | 1134.35 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 307.89 | 22.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28625.52 | 13-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.23 |
February | 35079.83 | 22-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.10 |
March | 43059.48 | 29-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 170.84 | 0.00 |
April | 50697.38 | 27-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 749.82 | 0.00 |
May | 54061.76 | 04-MAY-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 749.77 | 0.00 |
June | 55868.64 | 12-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 879.56 | 0.00 |
July | 53830.04 | 07-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 727.07 | 0.00 |
August | 51348.60 | 07-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 643.39 | 0.00 |
September | 48187.82 | 22-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 381.98 | 0.00 |
October | 47024.00 | 02-OCT-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 222.17 | 0.00 |
November | 39107.84 | 09-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.97 |
December | 31534.62 | 28-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28625.52 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55868.64 | 45622.98 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 879.56 | 473.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3375.27 | 21-JAN-19:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 |
February | 3271.81 | 15-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
March | 3270.06 | 12-MAR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
April | 3319.93 | 26-APR-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 0.00 |
May | 3332.89 | 12-MAY-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 0.00 |
June | 3350.72 | 17-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 | 0.00 |
July | 3333.54 | 10-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 58.96 | 0.00 |
August | 3341.22 | 09-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 |
September | 3332.21 | 13-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 69.06 | 0.00 |
October | 3315.70 | 12-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 0.00 |
November | 3257.71 | 17-NOV-19:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 |
December | 3642.31 | 20-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3257.71 | 252.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3642.31 | 970.20 | 1108.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 69.06 | 54.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3126.43 | 14-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
February | 3300.24 | 24-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 0.00 |
March | 3326.51 | 15-MAR-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
April | 3433.72 | 06-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 0.00 |
May | 3358.71 | 12-MAY-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 0.00 |
June | 3355.86 | 17-JUN-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 56.27 | 0.00 |
July | 3340.93 | 19-JUL-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 0.00 |
August | 3327.41 | 06-AUG-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | 0.00 |
September | 3317.04 | 02-SEP-18:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 | 0.00 |
October | 3449.10 | 17-OCT-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
November | 3252.79 | 28-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
December | 3506.95 | 20-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3126.43 | 360.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3506.95 | 1440.00 | 1067.17 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 22.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 394.58 | 08-JAN-14:30 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
February | 453.96 | 20-FEB-14:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
March | 483.17 | 13-MAR-13:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 0.00 |
April | 502.12 | 15-APR-14:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 0.00 |
May | 525.12 | 04-MAY-17:20 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 | 0.00 |
June | 509.94 | 12-JUN-17:20 | 0.00 | 149.80 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 0.00 |
July | 489.88 | 04-JUL-20:10 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 0.00 |
August | 448.04 | 07-AUG-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
September | 525.03 | 26-SEP-14:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
October | 588.72 | 02-OCT-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 0.00 |
November | 560.38 | 08-NOV-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
December | 471.37 | 02-DEC-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 394.58 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 588.72 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 7.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1311.79 | 21-JAN-19:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 |
February | 1324.47 | 24-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 0.00 |
March | 1348.55 | 29-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 |
April | 1345.83 | 18-APR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
May | 1344.76 | 25-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
June | 1349.08 | 16-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 0.00 |
July | 1353.05 | 29-JUL-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 0.00 |
August | 1349.77 | 28-AUG-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
September | 1353.10 | 03-SEP-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 0.00 |
October | 1342.37 | 25-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 0.00 |
November | 1344.01 | 08-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
December | 1321.82 | 30-DEC-19:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1311.79 | 252.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1353.10 | 702.00 | 670.94 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 18.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3071.75 | 21-JAN-19:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 |
February | 3012.67 | 08-FEB-19:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
March | 3029.52 | 05-MAR-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 |
April | 3103.76 | 03-APR-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 | 0.00 |
May | 3042.82 | 12-MAY-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 | 0.00 |
June | 3072.83 | 23-JUN-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 | 0.00 |
July | 3057.34 | 13-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 | 0.00 |
August | 3067.86 | 01-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 | 0.00 |
September | 3080.15 | 21-SEP-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 0.00 |
October | 3135.58 | 05-OCT-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 0.00 |
November | 3019.23 | 09-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
December | 3319.78 | 20-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3012.67 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3319.78 | 970.20 | 1108.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 | 54.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2806.02 | 14-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 |
February | 3082.96 | 23-FEB-09:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
March | 3286.34 | 28-MAR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
April | 3536.10 | 07-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 0.00 |
May | 3044.42 | 12-MAY-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 0.00 |
June | 3076.47 | 23-JUN-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 | 0.00 |
July | 3086.94 | 08-JUL-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 71.37 | 0.00 |
August | 3075.36 | 26-AUG-15:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 0.00 |
September | 3066.15 | 22-SEP-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 | 0.00 |
October | 3398.51 | 15-OCT-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 0.00 |
November | 3046.85 | 14-NOV-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
December | 2897.83 | 27-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2806.02 | 252.00 | 348.61 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3536.10 | 831.60 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 13.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1838.06 | 12-JAN-19:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 |
February | 2258.11 | 22-FEB-19:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
March | 2692.53 | 13-MAR-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 | 0.00 |
April | 3939.63 | 28-APR-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.26 | 0.00 |
May | 4358.27 | 04-MAY-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.56 | 0.00 |
June | 4431.80 | 07-JUN-18:13 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 | 0.00 |
July | 4098.29 | 07-JUL-20:10 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 0.00 |
August | 3788.56 | 07-AUG-20:10 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 0.00 |
September | 3457.10 | 17-SEP-20:10 | 2011.87 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.24 | 0.00 |
October | 3388.69 | 02-OCT-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.93 | 0.00 |
November | 2473.60 | 01-NOV-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 0.00 |
December | 2033.05 | 03-DEC-11:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1838.06 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4431.80 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 | 30.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3732.29 | 21-JAN-19:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.91 |
February | 3624.75 | 25-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 |
March | 3548.46 | 30-MAR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
April | 3621.29 | 16-APR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 52.82 | 0.00 |
May | 3678.21 | 19-MAY-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 | 0.00 |
June | 3727.77 | 09-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 107.15 | 0.00 |
July | 3691.97 | 02-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 | 0.00 |
August | 3664.43 | 18-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 53.56 | 0.00 |
September | 3660.51 | 13-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 | 0.00 |
October | 3667.22 | 11-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 0.00 |
November | 3580.32 | 17-NOV-19:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 |
December | 4038.87 | 20-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3548.46 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4038.87 | 970.20 | 1108.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 107.15 | 54.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3494.08 | 26-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
February | 3659.73 | 15-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
March | 3686.18 | 15-MAR-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 |
April | 3837.31 | 30-APR-07:51 | 763.20 | 796.82 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 0.00 |
May | 3694.08 | 18-MAY-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 0.00 |
June | 3734.94 | 09-JUN-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | 0.00 |
July | 3698.68 | 02-JUL-18:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 102.96 | 0.00 |
August | 3679.89 | 18-AUG-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 0.00 |
September | 3688.22 | 06-SEP-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 | 0.00 |
October | 3691.27 | 09-OCT-21:51 | 1108.80 | 1209.46 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
November | 3550.31 | 28-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 0.00 |
December | 3983.19 | 20-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3494.08 | 252.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3983.19 | 1440.00 | 1209.46 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | 22.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2086.73 | 31-JAN-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
February | 1961.39 | 26-FEB-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
March | 1923.61 | 12-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 | 0.00 |
April | 1947.45 | 14-APR-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 0.00 |
May | 1960.94 | 17-MAY-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 | 0.00 |
June | 1971.38 | 17-JUN-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 0.00 |
July | 1964.72 | 10-JUL-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 0.00 |
August | 1961.25 | 26-AUG-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 0.00 |
September | 1979.91 | 17-SEP-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 0.00 |
October | 1944.48 | 11-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
November | 1959.19 | 17-NOV-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
December | 2144.27 | 31-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1923.61 | 252.00 | 219.17 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2144.27 | 970.20 | 696.66 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 29.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18644.15 | 13-JAN-22:55 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.30 |
February | 20593.19 | 22-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.57 |
March | 23323.10 | 29-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.76 | 0.00 |
April | 25893.25 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.76 | 0.00 |
May | 26641.19 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 0.00 |
June | 27251.54 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 195.89 | 0.00 |
July | 26547.91 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 161.65 | 0.00 |
August | 25642.20 | 07-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 | 0.00 |
September | 24573.88 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.58 | 0.00 |
October | 23424.93 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 | 0.00 |
November | 20824.18 | 08-NOV-22:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 |
December | 19080.56 | 28-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18644.15 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27251.54 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 195.89 | 114.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20278.82 | 13-JAN-22:55 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.30 |
February | 21988.91 | 22-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.57 |
March | 24472.24 | 29-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.76 | 0.00 |
April | 27056.16 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.76 | 0.00 |
May | 27817.76 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 0.00 |
June | 28446.90 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 195.89 | 0.00 |
July | 27731.64 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 161.65 | 0.00 |
August | 26803.66 | 07-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 142.85 | 0.00 |
September | 25726.50 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.57 | 0.00 |
October | 24555.96 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 | 0.00 |
November | 22062.52 | 08-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 |
December | 20641.12 | 28-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20278.82 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28446.90 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 195.89 | 109.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26584.93 | 26-JAN-11:50 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
February | 28083.91 | 22-FEB-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 14.50 | 0.00 |
March | 30002.00 | 11-MAR-11:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 80.16 | 0.00 |
April | 32162.72 | 16-APR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 172.12 | 0.00 |
May | 32656.27 | 04-MAY-10:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 219.03 | 0.00 |
June | 32476.01 | 12-JUN-18:08 | 11207.95 | 5657.64 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 240.91 | 0.00 |
July | 32068.25 | 07-JUL-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 185.31 | 0.00 |
August | 31191.30 | 07-AUG-18:03 | 11207.95 | 5657.64 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 160.98 | 0.00 |
September | 30599.82 | 24-SEP-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 116.23 | 0.00 |
October | 30787.05 | 01-OCT-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 106.28 | 0.00 |
November | 28770.21 | 09-NOV-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 58.24 | 0.00 |
December | 27051.86 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26584.93 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32656.27 | 11207.95 | 5657.64 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 240.91 | 43.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4016.93 | 12-JAN-19:10 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.39 |
February | 4970.87 | 22-FEB-19:08 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
March | 7580.96 | 28-MAR-15:40 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.28 | 0.00 |
April | 9797.39 | 16-APR-15:03 | 4790.88 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.48 | 0.00 |
May | 11115.23 | 04-MAY-15:13 | 3992.40 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.24 | 0.00 |
June | 11083.13 | 08-JUN-15:30 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.04 | 0.00 |
July | 9982.43 | 07-JUL-15:40 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.16 | 0.00 |
August | 9003.25 | 08-AUG-15:30 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.71 | 0.00 |
September | 8639.83 | 26-SEP-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.50 | 0.00 |
October | 8779.89 | 02-OCT-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.07 | 0.00 |
November | 5499.36 | 09-NOV-15:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 0.00 |
December | 4253.10 | 28-DEC-19:10 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4016.93 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11115.23 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.04 | 57.39 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.398521E+12 | 276972.55 | 13-JAN-20:10 | 0.411871E+12 | 347718.13 | 17-JAN-18:30 |
February | 0.407578E+12 | 311691.52 | 22-FEB-20:10 | 0.357721E+12 | 347787.78 | 10-FEB-18:10 |
March | 0.547311E+12 | 377430.63 | 10-MAR-20:10 | 0.382332E+12 | 341673.93 | 02-MAR-18:49 |
April | 0.652780E+12 | 435285.05 | 26-APR-19:10 | 0.356028E+12 | 317459.50 | 03-APR-17:19 |
May | 0.781988E+12 | 483687.86 | 17-MAY-19:10 | 0.353470E+12 | 312586.37 | 03-MAY-17:40 |
June | 0.810477E+12 | 523992.11 | 09-JUN-19:19 | 0.331483E+12 | 306677.56 | 09-JUN-17:19 |
July | 0.848260E+12 | 513279.21 | 03-JUL-19:30 | 0.337754E+12 | 293686.93 | 01-JUL-17:19 |
August | 0.824685E+12 | 497079.91 | 07-AUG-19:10 | 0.341292E+12 | 307255.51 | 29-AUG-17:19 |
September | 0.746219E+12 | 497354.50 | 17-SEP-19:00 | 0.339848E+12 | 311798.09 | 29-SEP-17:30 |
October | 0.636974E+12 | 415276.00 | 03-OCT-19:10 | 0.365480E+12 | 317083.23 | 31-OCT-17:10 |
November | 0.492438E+12 | 331040.02 | 08-NOV-20:10 | 0.368043E+12 | 333540.43 | 28-NOV-18:19 |
December | 0.415127E+12 | 299134.70 | 28-DEC-20:10 | 0.399233E+12 | 347090.86 | 28-DEC-18:40 |
Annual Sum or Average | 0.756236E+13 | 0.434456E+13 | ||||
Minimum of Months | 0.398521E+12 | 276972.55 | 0.331483E+12 | 293686.93 | ||
Maximum of Months | 0.848260E+12 | 523992.11 | 0.411871E+12 | 347787.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.669334E+11 | 0.186409E+11 | 0.140828E+12 | 0.544238E+11 | 0.348303E+11 | 0.764041E+10 | 0.00 | 0.375103E+11 | 0.00 | 0.00 | 0.247352E+11 | 0.770484E+10 | 0.00 |
February | 0.603148E+11 | 0.161313E+11 | 0.127191E+12 | 0.491570E+11 | 0.333902E+11 | 0.798532E+10 | 0.00 | 0.797948E+11 | 0.00 | 0.00 | 0.218647E+11 | 0.696219E+10 | 0.00 |
March | 0.664860E+11 | 0.167161E+11 | 0.140882E+12 | 0.544261E+11 | 0.426974E+11 | 0.934734E+10 | 0.00 | 0.179734E+12 | 0.00 | 0.00 | 0.239844E+11 | 0.770299E+10 | 0.00 |
April | 0.641244E+11 | 0.150578E+11 | 0.136245E+12 | 0.526676E+11 | 0.508183E+11 | 0.954102E+10 | 0.00 | 0.286980E+12 | 0.00 | 0.00 | 0.247127E+11 | 0.746491E+10 | 0.00 |
May | 0.661413E+11 | 0.145766E+11 | 0.140860E+12 | 0.544246E+11 | 0.602392E+11 | 0.103704E+11 | 0.00 | 0.396535E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.770425E+10 | 0.00 |
June | 0.639986E+11 | 0.135772E+11 | 0.136336E+12 | 0.526699E+11 | 0.602294E+11 | 0.104100E+11 | 0.00 | 0.435665E+12 | 0.00 | 0.00 | 0.249345E+11 | 0.745687E+10 | 0.00 |
July | 0.662680E+11 | 0.143175E+11 | 0.140770E+12 | 0.544223E+11 | 0.612425E+11 | 0.110493E+11 | 0.00 | 0.461365E+12 | 0.00 | 0.00 | 0.257658E+11 | 0.771238E+10 | 0.00 |
August | 0.664207E+11 | 0.151097E+11 | 0.140892E+12 | 0.544261E+11 | 0.592332E+11 | 0.109830E+11 | 0.00 | 0.438772E+12 | 0.00 | 0.00 | 0.257686E+11 | 0.770436E+10 | 0.00 |
September | 0.644332E+11 | 0.156945E+11 | 0.136256E+12 | 0.526679E+11 | 0.540708E+11 | 0.101999E+11 | 0.00 | 0.375285E+12 | 0.00 | 0.00 | 0.249400E+11 | 0.746622E+10 | 0.00 |
October | 0.667579E+11 | 0.173824E+11 | 0.140818E+12 | 0.544237E+11 | 0.509487E+11 | 0.969109E+10 | 0.00 | 0.259176E+12 | 0.00 | 0.00 | 0.247051E+11 | 0.770295E+10 | 0.00 |
November | 0.646863E+11 | 0.177896E+11 | 0.136330E+12 | 0.526688E+11 | 0.411901E+11 | 0.890497E+10 | 0.00 | 0.135150E+12 | 0.00 | 0.00 | 0.231234E+11 | 0.744903E+10 | 0.00 |
December | 0.668935E+11 | 0.189889E+11 | 0.140770E+12 | 0.544226E+11 | 0.359582E+11 | 0.860986E+10 | 0.00 | 0.517649E+11 | 0.00 | 0.00 | 0.247334E+11 | 0.771289E+10 | 0.00 |
Annual Sum or Average | 0.783458E+12 | 0.193983E+12 | 0.165818E+13 | 0.640800E+12 | 0.584848E+12 | 0.114733E+12 | 0.00 | 0.313773E+13 | 0.00 | 0.00 | 0.295039E+12 | 0.907439E+11 | 0.00 |
Minimum of Months | 0.603148E+11 | 0.135772E+11 | 0.127191E+12 | 0.491570E+11 | 0.333902E+11 | 0.764041E+10 | 0.00 | 0.375103E+11 | 0.00 | 0.00 | 0.218647E+11 | 0.696219E+10 | 0.00 |
Maximum of Months | 0.669334E+11 | 0.189889E+11 | 0.140892E+12 | 0.544261E+11 | 0.612425E+11 | 0.110493E+11 | 0.00 | 0.461365E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.771289E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.170583E+11 | 0.00 | 0.242894E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.401073E+10 | 0.00 | 0.216506E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.276467E+09 | 0.00 | 0.230032E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.126639E+09 | 0.00 | 0.208945E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 64928384.91 | 0.00 | 0.201426E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 61400463.71 | 0.00 | 0.184308E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 55066273.39 | 0.00 | 0.185879E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 83170876.80 | 0.00 | 0.189170E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.126740E+09 | 0.00 | 0.192750E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.233795E+09 | 0.00 | 0.213343E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.557270E+09 | 0.00 | 0.220394E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.884954E+10 | 0.00 | 0.238563E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.315040E+11 | 0.00 | 0.252421E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 55066273.39 | 0.00 | 0.184308E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.170583E+11 | 0.00 | 0.242894E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 22917.97 | 12-JAN-21:19 | 3626.22 | 12-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 25548.46 | 22-FEB-22:00 | 3768.01 | 20-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 33400.71 | 29-MAR-21:10 | 4053.24 | 10-MAR-20:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.97 | 03-APR-06:19 | 43974.18 | 28-APR-21:40 | 4592.91 | 08-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.86 | 24-MAY-06:19 | 47660.08 | 05-MAY-21:19 | 4952.82 | 17-MAY-18:19 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39169.97 | 27-JUN-06:19 | 49040.25 | 06-JUN-21:19 | 5429.23 | 22-JUN-18:30 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:19 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39169.97 | 11-JUL-06:19 | 49575.79 | 07-JUL-21:19 | 5554.72 | 05-JUL-18:30 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.97 | 10-AUG-06:19 | 48684.75 | 08-AUG-21:19 | 5403.46 | 28-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 01-SEP-06:19 | 44924.79 | 01-SEP-21:19 | 5171.12 | 14-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 41479.61 | 02-OCT-21:10 | 4298.60 | 02-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 30295.68 | 09-NOV-22:00 | 3877.19 | 01-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 04-DEC-07:19 | 24247.85 | 01-DEC-20:19 | 3662.10 | 02-DEC-16:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.86 | 22917.97 | 3626.22 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 49575.79 | 5554.72 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 80590.34 | 12-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.71 | 09-JAN-19:10 | 0.00 |
February | 100636.66 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.56 | 22-FEB-19:10 | 0.00 |
March | 153007.71 | 28-MAR-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAR-01:19 | 4738.60 | 15-MAR-18:10 | 0.00 |
April | 205207.20 | 26-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.73 | 13-APR-18:10 | 0.00 |
May | 253069.65 | 17-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.60 | 25-MAY-18:10 | 0.00 |
June | 285144.78 | 10-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.76 | 01-JUN-18:10 | 0.00 |
July | 276969.73 | 01-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.72 | 13-JUL-18:10 | 0.00 |
August | 255643.71 | 07-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.56 | 03-AUG-18:10 | 0.00 |
September | 255598.33 | 17-SEP-19:00 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.65 | 21-SEP-18:10 | 0.00 |
October | 185640.64 | 03-OCT-15:20 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.45 | 30-OCT-18:10 | 0.00 |
November | 121557.85 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-09:09 | 4738.68 | 08-NOV-19:10 | 0.00 |
December | 85234.01 | 28-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.40 | 08-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 80590.34 | 0.00 | 0.00 | 9938.94 | 4738.40 | 0.00 | |||
Maximum of Months | 285144.78 | 0.00 | 0.00 | 9938.94 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 276972.55 | 13-JAN-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 19600.29 | 3388.44 | 0.00 | 44860.26 | 0.00 |
February | 311691.52 | 22-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20823.33 | 3539.00 | 0.00 | 77744.35 | 0.00 |
March | 377430.63 | 10-MAR-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 26482.31 | 4053.24 | 0.00 | 136588.90 | 0.00 |
April | 435285.05 | 26-APR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 30047.40 | 4328.91 | 0.00 | 189866.67 | 0.00 |
May | 483687.86 | 17-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 32617.29 | 4804.98 | 0.00 | 235258.27 | 0.00 |
June | 523992.11 | 09-JUN-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 40110.23 | 5057.84 | 0.00 | 268074.16 | 0.00 |
July | 513279.21 | 03-JUL-19:30 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 37102.00 | 5247.34 | 0.00 | 259582.95 | 0.00 |
August | 497079.91 | 07-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 31546.78 | 35138.74 | 5251.61 | 0.00 | 245342.92 | 0.00 |
September | 497354.50 | 17-SEP-19:00 | 59807.00 | 84978.71 | 12338.45 | 31515.42 | 32925.64 | 4875.18 | 0.00 | 255598.33 | 0.00 |
October | 415276.00 | 03-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 34723.71 | 4234.47 | 0.00 | 165860.51 | 0.00 |
November | 331040.02 | 08-NOV-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23829.42 | 3628.04 | 0.00 | 93995.84 | 0.00 |
December | 299134.70 | 28-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20346.96 | 3454.32 | 0.00 | 65629.12 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 276972.55 | 59807.00 | 84978.71 | 12338.45 | 31515.42 | 19600.29 | 3388.44 | 0.00 | 44860.26 | 0.00 | |
Maximum of Months | 523992.11 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 40110.23 | 5251.61 | 0.00 | 268074.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 43284.75 | 02-JAN-09:09 | 0.00 | 243742.46 | 24-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 27133.99 | 10-FEB-16:10 | 0.00 | 243608.95 | 01-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 6805.86 | 25-MAR-06:10 | 0.00 | 237425.61 | 02-MAR-18:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 6006.18 | 24-APR-08:09 | 0.00 | 213652.30 | 03-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 5318.39 | 15-MAY-08:09 | 0.00 | 209077.29 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 5546.15 | 01-JUN-08:09 | 0.00 | 204012.39 | 02-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 5185.73 | 27-JUL-08:09 | 0.00 | 200606.42 | 28-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 5069.65 | 16-AUG-08:09 | 0.00 | 203249.63 | 29-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 5863.66 | 09-SEP-18:10 | 0.00 | 207947.02 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 5656.56 | 12-OCT-18:10 | 0.00 | 213222.81 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 20717.80 | 26-NOV-00:10 | 0.00 | 231582.48 | 28-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 30369.22 | 23-DEC-06:10 | 0.00 | 243488.13 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 5069.65 | 0.00 | 200606.42 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 43284.75 | 0.00 | 243742.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.81 | 5.17 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21.85 | 8.83 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.85 | 4.50 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.00 | 21.83 | 21.00 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21.85 | 8.83 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.86 | 6.67 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.86 | 4.17 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 21.84 | 14.00 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.86 | 6.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.81 | 5.17 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.82 | 2.83 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.50 | 21.80 | 10.50 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.82 | 5.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.83 | 2.50 | 21.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.79 | 4.67 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.80 | 3.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.00 | 21.79 | 15.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.83 | 4.67 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.88 | 11.00 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 21.96 | 15.50 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 21.90 | 10.33 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.74 | 2.00 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.80 | 3.33 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.17 | 21.89 | 45.17 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 21.96 | 15.50 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.84 | 6.50 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 21.93 | 15.33 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 21.89 | 10.83 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.00 | 21.88 | 35.00 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 21.93 | 15.33 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.79 | 2.50 | 21.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.85 | 5.33 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.82 | 4.17 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.83 | 3.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.73 | 2.17 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.84 | 5.50 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.76 | 3.17 | 21.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.50 | 21.81 | 28.50 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.85 | 5.50 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.33 | 23.47 | 14.33 | 23.48 | 0.00 | 23.48 |
February | 398.33 | 23.39 | 66.67 | 23.46 | 0.17 | 23.46 |
March | 336.67 | 23.37 | 161.67 | 23.52 | 2.33 | 23.53 |
April | 148.50 | 23.40 | 316.83 | 23.72 | 3.00 | 23.72 |
May | 24.67 | 23.90 | 548.67 | 23.95 | 19.67 | 23.95 |
June | 1.17 | 24.00 | 715.83 | 23.95 | 1.17 | 23.95 |
July | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 0.00 | 0.00 | 720.00 | 24.00 | 0.00 | 24.00 |
October | 0.00 | 0.00 | 741.50 | 24.00 | 0.00 | 24.00 |
November | 0.00 | 0.00 | 461.33 | 24.00 | 0.00 | 24.00 |
December | 132.50 | 23.75 | 77.83 | 23.84 | 0.00 | 23.84 |
Annual Sum or Average | 1508.17 | 23.45 | 5312.67 | 23.86 | 26.33 | 23.86 |
Minimum of Months | 0.00 | 0.00 | 14.33 | 23.46 | 0.00 | 23.46 |
Maximum of Months | 466.33 | 24.00 | 744.00 | 24.00 | 19.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 684.83 | 21.56 | 5.67 | 21.58 | 0.00 | 21.58 |
February | 477.17 | 21.73 | 109.17 | 22.12 | 0.00 | 22.12 |
March | 286.00 | 22.11 | 361.50 | 23.09 | 0.00 | 23.09 |
April | 47.17 | 22.37 | 630.17 | 23.81 | 0.00 | 23.81 |
May | 15.00 | 23.42 | 737.17 | 23.94 | 14.00 | 23.93 |
June | 32.67 | 23.41 | 694.50 | 23.90 | 22.83 | 23.90 |
July | 67.50 | 23.68 | 742.00 | 23.90 | 67.50 | 23.88 |
August | 88.17 | 23.66 | 744.00 | 23.87 | 88.17 | 23.85 |
September | 76.67 | 23.00 | 655.00 | 23.73 | 44.00 | 23.71 |
October | 95.17 | 22.45 | 592.67 | 23.65 | 0.00 | 23.65 |
November | 293.50 | 22.03 | 355.67 | 23.05 | 0.00 | 23.05 |
December | 631.50 | 21.68 | 47.17 | 21.84 | 0.00 | 21.84 |
Annual Sum or Average | 2795.33 | 21.96 | 5674.67 | 23.25 | 236.50 | 23.26 |
Minimum of Months | 15.00 | 21.56 | 5.67 | 21.58 | 0.00 | 21.58 |
Maximum of Months | 684.83 | 23.68 | 744.00 | 23.94 | 88.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
February | 563.17 | 22.55 | 44.50 | 22.64 | 4.33 | 22.64 |
March | 301.17 | 23.02 | 312.67 | 23.44 | 33.67 | 23.46 |
April | 31.83 | 23.36 | 615.00 | 23.91 | 11.00 | 23.91 |
May | 23.50 | 23.97 | 743.83 | 23.97 | 23.50 | 23.97 |
June | 51.00 | 23.94 | 720.00 | 23.95 | 51.00 | 23.95 |
July | 83.17 | 23.99 | 743.83 | 23.96 | 83.17 | 23.96 |
August | 97.83 | 24.00 | 744.00 | 23.95 | 97.83 | 23.96 |
September | 93.83 | 23.87 | 696.00 | 23.89 | 93.83 | 23.89 |
October | 72.67 | 23.87 | 645.00 | 23.87 | 70.50 | 23.87 |
November | 314.83 | 23.01 | 229.17 | 23.36 | 13.33 | 23.37 |
December | 718.33 | 22.48 | 4.17 | 22.49 | 0.00 | 22.49 |
Annual Sum or Average | 3088.33 | 22.73 | 5498.17 | 23.49 | 482.17 | 23.52 |
Minimum of Months | 23.50 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
Maximum of Months | 737.00 | 24.00 | 744.00 | 23.97 | 97.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
February | 672.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
March | 657.83 | 22.52 | 10.50 | 22.54 | 0.00 | 22.54 |
April | 152.83 | 23.12 | 358.50 | 23.68 | 0.00 | 23.68 |
May | 0.00 | 0.00 | 732.67 | 23.97 | 0.00 | 23.97 |
June | 0.00 | 0.00 | 714.50 | 23.95 | 0.00 | 23.95 |
July | 0.00 | 0.00 | 744.00 | 23.98 | 0.00 | 23.98 |
August | 0.00 | 0.00 | 744.00 | 23.98 | 0.00 | 23.98 |
September | 1.17 | 23.07 | 648.17 | 23.89 | 0.00 | 23.89 |
October | 244.67 | 22.98 | 244.00 | 23.39 | 0.00 | 23.39 |
November | 720.00 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
December | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
Annual Sum or Average | 3936.50 | 21.92 | 4196.33 | 22.96 | 0.00 | 22.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.16 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 23.12 | 744.00 | 23.98 | 0.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
February | 672.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
March | 677.17 | 22.54 | 1.67 | 22.55 | 0.00 | 22.55 |
April | 188.00 | 23.17 | 309.17 | 23.64 | 0.00 | 23.64 |
May | 0.00 | 0.00 | 728.33 | 23.97 | 0.00 | 23.97 |
June | 0.00 | 0.00 | 712.33 | 23.95 | 0.00 | 23.95 |
July | 0.00 | 0.00 | 744.00 | 23.98 | 0.00 | 23.98 |
August | 0.00 | 0.00 | 744.00 | 23.97 | 0.00 | 23.97 |
September | 7.67 | 23.10 | 632.00 | 23.88 | 0.00 | 23.88 |
October | 265.67 | 23.02 | 190.33 | 23.33 | 0.00 | 23.33 |
November | 720.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
December | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Annual Sum or Average | 4018.50 | 21.97 | 4061.83 | 22.96 | 0.00 | 22.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 | 21.17 |
Maximum of Months | 744.00 | 23.17 | 744.00 | 23.98 | 0.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.00 | 23.19 | 628.17 | 23.35 | 122.67 | 23.43 |
February | 162.67 | 23.72 | 625.67 | 23.47 | 146.83 | 23.56 |
March | 278.83 | 23.97 | 733.50 | 23.63 | 278.83 | 23.71 |
April | 492.17 | 23.92 | 720.00 | 23.77 | 492.17 | 23.81 |
May | 632.83 | 23.88 | 744.00 | 23.80 | 632.83 | 23.83 |
June | 580.33 | 23.88 | 720.00 | 23.79 | 580.33 | 23.82 |
July | 598.50 | 23.90 | 744.00 | 23.79 | 598.50 | 23.83 |
August | 579.17 | 23.90 | 744.00 | 23.78 | 579.17 | 23.81 |
September | 502.50 | 23.90 | 720.00 | 23.74 | 502.50 | 23.79 |
October | 409.50 | 23.94 | 744.00 | 23.70 | 409.50 | 23.76 |
November | 198.83 | 23.98 | 707.00 | 23.57 | 198.00 | 23.64 |
December | 165.67 | 23.43 | 634.33 | 23.43 | 131.17 | 23.51 |
Annual Sum or Average | 4774.00 | 23.86 | 8464.67 | 23.68 | 4672.50 | 23.74 |
Minimum of Months | 162.67 | 23.19 | 625.67 | 23.35 | 122.67 | 23.43 |
Maximum of Months | 632.83 | 23.98 | 744.00 | 23.80 | 632.83 | 23.83 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.33 | 22.44 | 169.17 | 22.81 | 14.67 | 22.82 |
February | 280.17 | 22.76 | 366.50 | 23.38 | 65.83 | 23.41 |
March | 263.83 | 23.49 | 608.50 | 23.77 | 182.67 | 23.80 |
April | 234.83 | 23.88 | 701.67 | 23.91 | 228.83 | 23.91 |
May | 313.17 | 23.97 | 744.00 | 23.96 | 313.17 | 23.96 |
June | 324.17 | 23.95 | 717.33 | 23.95 | 324.17 | 23.95 |
July | 376.33 | 23.97 | 743.33 | 23.95 | 376.33 | 23.95 |
August | 397.50 | 23.96 | 743.83 | 23.94 | 397.50 | 23.94 |
September | 394.67 | 23.90 | 715.17 | 23.89 | 394.50 | 23.89 |
October | 335.17 | 23.90 | 725.33 | 23.91 | 331.33 | 23.91 |
November | 208.17 | 23.60 | 605.83 | 23.85 | 145.50 | 23.87 |
December | 356.17 | 22.69 | 269.17 | 23.19 | 5.83 | 23.20 |
Annual Sum or Average | 3938.50 | 23.52 | 7109.83 | 23.77 | 2780.33 | 23.80 |
Minimum of Months | 208.17 | 22.44 | 169.17 | 22.81 | 5.83 | 22.82 |
Maximum of Months | 454.33 | 23.97 | 744.00 | 23.96 | 397.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 657.83 | 22.68 | 20.67 | 22.72 | 0.00 | 22.72 |
February | 425.50 | 22.94 | 153.33 | 23.18 | 39.17 | 23.22 |
March | 257.83 | 23.54 | 474.50 | 23.76 | 146.50 | 23.79 |
April | 194.33 | 23.96 | 675.67 | 23.93 | 190.17 | 23.93 |
May | 253.83 | 23.99 | 744.00 | 23.97 | 253.83 | 23.97 |
June | 260.17 | 23.99 | 720.00 | 23.97 | 260.17 | 23.97 |
July | 306.83 | 23.99 | 744.00 | 23.97 | 306.83 | 23.98 |
August | 310.00 | 23.99 | 744.00 | 23.97 | 310.00 | 23.98 |
September | 327.00 | 23.98 | 720.00 | 23.94 | 327.00 | 23.95 |
October | 284.17 | 23.98 | 741.33 | 23.93 | 284.17 | 23.94 |
November | 181.17 | 23.64 | 479.33 | 23.82 | 102.83 | 23.84 |
December | 551.17 | 22.89 | 63.50 | 23.00 | 4.83 | 23.00 |
Annual Sum or Average | 4009.83 | 23.47 | 6280.33 | 23.75 | 2225.50 | 23.79 |
Minimum of Months | 181.17 | 22.68 | 20.67 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 657.83 | 23.99 | 744.00 | 23.97 | 327.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
February | 667.33 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
March | 688.17 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
April | 598.67 | 21.44 | 8.83 | 21.47 | 0.00 | 21.47 |
May | 582.17 | 21.34 | 29.33 | 21.44 | 0.00 | 21.44 |
June | 558.17 | 21.32 | 30.83 | 21.42 | 0.33 | 21.42 |
July | 582.67 | 21.31 | 18.67 | 21.38 | 0.00 | 21.38 |
August | 595.50 | 21.35 | 7.17 | 21.38 | 0.00 | 21.38 |
September | 592.83 | 21.41 | 15.83 | 21.46 | 8.00 | 21.48 |
October | 633.17 | 21.46 | 1.83 | 21.46 | 0.00 | 21.46 |
November | 662.83 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
December | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
Annual Sum or Average | 7649.50 | 21.45 | 112.50 | 21.48 | 8.33 | 21.48 |
Minimum of Months | 558.17 | 21.31 | 0.00 | 21.38 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 21.59 | 30.83 | 21.59 | 8.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.26 | 4.17 | 21.25 | 4.17 | 21.25 |
February | 672.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
March | 694.83 | 21.98 | 0.67 | 21.98 | 0.00 | 21.98 |
April | 606.50 | 21.61 | 5.17 | 21.63 | 0.00 | 21.63 |
May | 587.33 | 21.36 | 26.50 | 21.45 | 1.00 | 21.46 |
June | 557.00 | 21.32 | 32.17 | 21.43 | 1.67 | 21.43 |
July | 583.33 | 21.32 | 18.50 | 21.38 | 0.00 | 21.38 |
August | 599.33 | 21.37 | 4.17 | 21.38 | 0.00 | 21.38 |
September | 605.67 | 21.45 | 8.17 | 21.48 | 8.17 | 21.50 |
October | 664.50 | 21.88 | 19.50 | 21.93 | 17.83 | 21.98 |
November | 713.17 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
December | 744.00 | 21.42 | 2.67 | 21.41 | 2.67 | 21.41 |
Annual Sum or Average | 7771.67 | 21.57 | 121.67 | 21.60 | 35.50 | 21.60 |
Minimum of Months | 557.00 | 21.26 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 22.01 | 32.17 | 22.01 | 17.83 | 22.01 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
February | 672.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
March | 744.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
April | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 744.00 | 21.73 | 0.50 | 21.74 | 0.50 | 21.74 |
June | 720.00 | 21.73 | 0.50 | 21.73 | 0.50 | 21.73 |
July | 744.00 | 21.72 | 0.17 | 21.72 | 0.17 | 21.73 |
August | 744.00 | 21.72 | 0.83 | 21.72 | 0.83 | 21.72 |
September | 720.00 | 21.71 | 2.33 | 21.71 | 2.33 | 21.72 |
October | 744.00 | 21.93 | 9.83 | 21.95 | 9.83 | 21.97 |
November | 720.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
December | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
Annual Sum or Average | 8760.00 | 21.71 | 14.17 | 21.72 | 14.17 | 21.72 |
Minimum of Months | 672.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
Maximum of Months | 744.00 | 21.95 | 9.83 | 21.95 | 9.83 | 21.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
February | 672.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
March | 679.67 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
April | 557.67 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
May | 549.83 | 21.21 | 7.33 | 21.24 | 0.00 | 21.24 |
June | 544.00 | 21.25 | 4.00 | 21.27 | 0.00 | 21.27 |
July | 570.50 | 21.27 | 6.17 | 21.30 | 0.00 | 21.30 |
August | 582.67 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
September | 577.50 | 21.36 | 7.17 | 21.38 | 7.17 | 21.41 |
October | 606.33 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
November | 692.50 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
December | 744.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
Annual Sum or Average | 7520.67 | 21.44 | 24.67 | 21.44 | 7.17 | 21.45 |
Minimum of Months | 544.00 | 21.21 | 0.00 | 21.24 | 0.00 | 21.24 |
Maximum of Months | 744.00 | 21.66 | 7.33 | 21.66 | 7.17 | 21.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
February | 671.17 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
March | 679.67 | 22.00 | 14.67 | 22.05 | 0.00 | 22.05 |
April | 539.17 | 21.39 | 14.67 | 21.48 | 0.00 | 21.48 |
May | 549.83 | 21.22 | 2.00 | 21.23 | 1.00 | 21.24 |
June | 542.83 | 21.25 | 5.50 | 21.27 | 1.33 | 21.28 |
July | 570.50 | 21.27 | 7.00 | 21.30 | 0.00 | 21.30 |
August | 583.83 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
September | 581.33 | 21.38 | 7.67 | 21.40 | 7.33 | 21.43 |
October | 640.67 | 21.85 | 32.17 | 21.96 | 18.33 | 22.01 |
November | 713.33 | 22.06 | 2.33 | 22.07 | 0.00 | 22.07 |
December | 744.00 | 21.42 | 0.50 | 21.42 | 0.50 | 21.42 |
Annual Sum or Average | 7560.33 | 21.54 | 86.50 | 21.57 | 28.50 | 21.57 |
Minimum of Months | 539.17 | 21.22 | 0.00 | 21.23 | 0.00 | 21.24 |
Maximum of Months | 744.00 | 22.06 | 32.17 | 22.07 | 18.33 | 22.07 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
February | 672.00 | 21.96 | 3.00 | 21.96 | 3.00 | 21.96 |
March | 618.00 | 22.90 | 63.67 | 22.96 | 40.33 | 22.98 |
April | 128.67 | 23.60 | 354.17 | 23.85 | 55.33 | 23.84 |
May | 79.50 | 23.94 | 692.83 | 23.96 | 79.50 | 23.96 |
June | 122.00 | 23.90 | 698.33 | 23.94 | 122.00 | 23.94 |
July | 175.83 | 23.93 | 733.50 | 23.94 | 175.83 | 23.94 |
August | 219.00 | 23.91 | 699.67 | 23.92 | 219.00 | 23.92 |
September | 294.00 | 23.56 | 567.50 | 23.76 | 213.17 | 23.75 |
October | 213.17 | 23.54 | 409.67 | 23.74 | 115.67 | 23.74 |
November | 691.00 | 22.93 | 9.33 | 22.94 | 9.33 | 22.94 |
December | 744.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
Annual Sum or Average | 4701.17 | 22.54 | 4231.67 | 23.19 | 1033.17 | 23.25 |
Minimum of Months | 79.50 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 23.94 | 733.50 | 23.96 | 219.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.83 | 21.43 | 13.50 | 21.40 | 13.50 | 21.38 |
February | 621.67 | 21.44 | 1.33 | 21.44 | 1.33 | 21.44 |
March | 633.33 | 21.41 | 23.83 | 21.48 | 0.50 | 21.48 |
April | 550.33 | 21.32 | 71.33 | 21.54 | 0.00 | 21.54 |
May | 538.83 | 21.27 | 107.33 | 21.60 | 0.00 | 21.60 |
June | 525.00 | 21.26 | 115.67 | 21.62 | 3.17 | 21.63 |
July | 564.83 | 21.26 | 94.17 | 21.56 | 0.00 | 21.56 |
August | 575.00 | 21.29 | 90.67 | 21.57 | 0.50 | 21.57 |
September | 569.83 | 21.34 | 76.00 | 21.57 | 7.00 | 21.59 |
October | 592.17 | 21.32 | 60.00 | 21.51 | 1.33 | 21.51 |
November | 615.83 | 21.40 | 12.00 | 21.44 | 0.00 | 21.44 |
December | 719.50 | 21.49 | 9.17 | 21.48 | 9.17 | 21.47 |
Annual Sum or Average | 7245.17 | 21.36 | 675.00 | 21.51 | 36.50 | 21.51 |
Minimum of Months | 525.00 | 21.26 | 1.33 | 21.40 | 0.00 | 21.38 |
Maximum of Months | 738.83 | 21.49 | 115.67 | 21.62 | 13.50 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 43.33 | 21.23 | 43.33 | 21.18 |
February | 650.17 | 21.75 | 4.67 | 21.75 | 4.67 | 21.74 |
March | 634.33 | 21.77 | 7.83 | 21.80 | 2.50 | 21.80 |
April | 559.83 | 21.46 | 53.33 | 21.63 | 0.67 | 21.63 |
May | 541.00 | 21.28 | 100.00 | 21.59 | 1.83 | 21.60 |
June | 524.50 | 21.27 | 117.67 | 21.63 | 5.50 | 21.64 |
July | 564.50 | 21.26 | 91.67 | 21.55 | 0.00 | 21.55 |
August | 576.50 | 21.29 | 85.17 | 21.55 | 0.50 | 21.56 |
September | 578.83 | 21.37 | 56.83 | 21.54 | 8.17 | 21.57 |
October | 624.00 | 21.70 | 46.50 | 21.81 | 29.67 | 21.88 |
November | 668.00 | 21.86 | 1.17 | 21.86 | 1.17 | 21.86 |
December | 744.00 | 21.42 | 40.83 | 21.39 | 40.83 | 21.35 |
Annual Sum or Average | 7409.67 | 21.48 | 649.00 | 21.60 | 138.83 | 21.60 |
Minimum of Months | 524.50 | 21.26 | 1.17 | 21.23 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 21.86 | 117.67 | 21.86 | 43.33 | 21.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 667.17 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
February | 580.83 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
March | 626.33 | 21.41 | 10.00 | 21.44 | 0.00 | 21.44 |
April | 581.50 | 21.37 | 6.67 | 21.40 | 0.00 | 21.40 |
May | 593.50 | 21.36 | 11.00 | 21.39 | 0.00 | 21.39 |
June | 577.83 | 21.37 | 1.50 | 21.37 | 0.67 | 21.37 |
July | 596.83 | 21.36 | 3.00 | 21.37 | 0.00 | 21.37 |
August | 599.83 | 21.37 | 4.33 | 21.38 | 0.00 | 21.38 |
September | 582.33 | 21.37 | 45.67 | 21.52 | 3.17 | 21.53 |
October | 581.83 | 21.31 | 83.00 | 21.56 | 0.17 | 21.56 |
November | 579.17 | 21.33 | 57.33 | 21.51 | 0.00 | 21.51 |
December | 653.50 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
Annual Sum or Average | 7220.67 | 21.38 | 222.50 | 21.44 | 4.00 | 21.44 |
Minimum of Months | 577.83 | 21.31 | 0.00 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 667.17 | 21.45 | 83.00 | 21.56 | 3.17 | 21.56 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.33 | 23.00 | 229.67 | 23.41 | 22.83 | 23.43 |
February | 146.83 | 23.32 | 425.50 | 23.80 | 48.83 | 23.81 |
March | 173.17 | 23.96 | 688.67 | 23.96 | 167.33 | 23.97 |
April | 213.83 | 24.00 | 719.67 | 23.99 | 213.83 | 23.99 |
May | 277.00 | 24.00 | 744.00 | 24.00 | 277.00 | 24.00 |
June | 283.00 | 24.00 | 720.00 | 24.00 | 283.00 | 24.00 |
July | 316.00 | 24.00 | 744.00 | 24.00 | 316.00 | 24.00 |
August | 322.00 | 24.00 | 744.00 | 24.00 | 322.00 | 24.00 |
September | 353.00 | 24.00 | 720.00 | 23.99 | 353.00 | 23.99 |
October | 327.17 | 24.00 | 744.00 | 23.98 | 327.17 | 23.98 |
November | 157.33 | 23.91 | 601.33 | 23.94 | 142.50 | 23.95 |
December | 254.17 | 23.08 | 304.00 | 23.57 | 5.17 | 23.57 |
Annual Sum or Average | 3139.83 | 23.78 | 7384.83 | 23.92 | 2478.67 | 23.94 |
Minimum of Months | 146.83 | 23.00 | 229.67 | 23.41 | 5.17 | 23.43 |
Maximum of Months | 353.00 | 24.00 | 744.00 | 24.00 | 353.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 171.17 | 23.13 | 387.00 | 23.71 | 12.33 | 23.72 |
February | 59.33 | 23.63 | 547.33 | 23.93 | 37.67 | 23.93 |
March | 149.83 | 24.00 | 726.50 | 23.98 | 149.83 | 23.98 |
April | 198.67 | 24.00 | 720.00 | 24.00 | 198.67 | 24.00 |
May | 261.67 | 24.00 | 744.00 | 24.00 | 261.67 | 24.00 |
June | 260.33 | 24.00 | 720.00 | 24.00 | 260.33 | 24.00 |
July | 297.00 | 24.00 | 744.00 | 24.00 | 297.00 | 24.00 |
August | 297.50 | 24.00 | 744.00 | 24.00 | 297.50 | 24.00 |
September | 320.00 | 24.00 | 720.00 | 24.00 | 320.00 | 24.00 |
October | 303.50 | 24.00 | 744.00 | 23.99 | 303.50 | 23.99 |
November | 116.50 | 24.00 | 672.17 | 23.97 | 116.50 | 23.97 |
December | 97.33 | 23.17 | 417.50 | 23.82 | 4.50 | 23.82 |
Annual Sum or Average | 2532.83 | 23.90 | 7886.50 | 23.96 | 2259.50 | 23.97 |
Minimum of Months | 59.33 | 23.13 | 387.00 | 23.71 | 4.50 | 23.72 |
Maximum of Months | 320.00 | 24.00 | 744.00 | 24.00 | 320.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 503.83 | 23.96 | 681.17 | 23.92 | 494.83 | 23.94 |
February | 469.00 | 23.99 | 657.83 | 23.93 | 469.00 | 23.94 |
March | 558.67 | 23.99 | 744.00 | 23.97 | 558.67 | 23.97 |
April | 606.33 | 23.99 | 720.00 | 23.99 | 606.33 | 23.99 |
May | 690.83 | 23.99 | 744.00 | 23.99 | 690.83 | 23.99 |
June | 674.33 | 23.99 | 720.00 | 23.99 | 674.33 | 23.99 |
July | 694.33 | 23.99 | 744.00 | 23.99 | 694.33 | 23.99 |
August | 667.83 | 23.99 | 744.00 | 23.99 | 667.83 | 23.99 |
September | 612.00 | 23.99 | 720.00 | 23.99 | 612.00 | 23.99 |
October | 595.33 | 23.99 | 744.00 | 23.99 | 595.33 | 23.99 |
November | 515.50 | 23.99 | 719.83 | 23.94 | 515.50 | 23.96 |
December | 506.67 | 23.96 | 702.67 | 23.90 | 495.00 | 23.93 |
Annual Sum or Average | 7094.67 | 23.99 | 8641.50 | 23.97 | 7074.00 | 23.98 |
Minimum of Months | 469.00 | 23.96 | 657.83 | 23.90 | 469.00 | 23.93 |
Maximum of Months | 694.33 | 23.99 | 744.00 | 23.99 | 694.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
February | 672.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
March | 488.17 | 22.49 | 155.83 | 22.83 | 0.00 | 22.83 |
April | 92.67 | 22.90 | 502.33 | 23.76 | 0.00 | 23.76 |
May | 0.50 | 23.09 | 729.83 | 23.95 | 0.00 | 23.95 |
June | 7.33 | 22.90 | 687.17 | 23.94 | 0.00 | 23.94 |
July | 0.00 | 0.00 | 736.33 | 23.95 | 0.00 | 23.95 |
August | 0.00 | 0.00 | 731.33 | 23.91 | 0.00 | 23.91 |
September | 46.83 | 22.87 | 560.50 | 23.78 | 0.00 | 23.78 |
October | 198.17 | 22.76 | 412.67 | 23.51 | 0.00 | 23.51 |
November | 591.50 | 22.34 | 17.33 | 22.39 | 0.00 | 22.39 |
December | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Annual Sum or Average | 3585.17 | 21.90 | 4533.33 | 23.03 | 0.00 | 23.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.27 | 0.00 | 21.27 |
Maximum of Months | 744.00 | 23.09 | 736.33 | 23.95 | 0.00 | 23.95 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60855 | 43.05987 | 0.26581 | 6.62172 |
February | 672.00000 | 23.56113 | 47.41061 | 0.28453 | 6.85721 |
March | 744.00000 | 23.56313 | 52.17949 | 0.31966 | 7.29259 |
April | 720.00000 | 23.69440 | 54.28794 | 0.37294 | 8.04464 |
May | 744.00000 | 23.86802 | 56.67953 | -0.4703 | 9.71437 |
June | 720.00000 | 23.95176 | 56.69403 | -0.4240 | 8.77774 |
July | 744.00000 | 23.99847 | 56.74482 | -0.3868 | 8.12270 |
August | 744.00000 | 23.99966 | 56.89548 | -0.3738 | 7.91454 |
September | 720.00000 | 23.99965 | 57.18683 | -0.3721 | 7.91274 |
October | 744.00000 | 23.99950 | 56.18519 | 0.50321 | 10.30905 |
November | 720.00000 | 23.99667 | 49.33102 | 0.43990 | 9.10105 |
December | 744.00000 | 23.91116 | 41.81527 | 0.34469 | 7.56323 |
Annual Sum or Average | 8760.00000 | 23.84764 | 52.39135 | 0.04040 | 8.19389 |
Minimum of Months | 672.00000 | 23.56113 | 41.81527 | -0.4703 | 6.62172 |
Maximum of Months | 744.00000 | 23.99966 | 57.18683 | 0.50321 | 10.30905 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.71672 | 46.62010 | -0.1326 | 6.56537 |
February | 672.00000 | 22.27457 | 49.82685 | 0.06756 | 6.84779 |
March | 744.00000 | 23.10788 | 52.17859 | 0.34886 | 9.04942 |
April | 720.00000 | 23.76934 | 52.50132 | 0.58068 | 12.64233 |
May | 744.00000 | 23.94101 | 55.43322 | -0.1433 | 5.74932 |
June | 720.00000 | 23.88270 | 56.81198 | -0.1574 | 6.09291 |
July | 744.00000 | 23.91469 | 58.16149 | -0.1663 | 5.89535 |
August | 744.00000 | 23.89214 | 58.91843 | -0.1914 | 6.08193 |
September | 720.00000 | 23.71123 | 59.51454 | -0.2565 | 7.36175 |
October | 744.00000 | 23.59871 | 57.38678 | 0.55618 | 12.23870 |
November | 720.00000 | 23.06869 | 51.45494 | 0.33355 | 9.00427 |
December | 744.00000 | 21.97643 | 45.53614 | -0.0489 | 6.61973 |
Annual Sum or Average | 8760.00000 | 23.24170 | 53.71209 | 0.06521 | 7.84376 |
Minimum of Months | 672.00000 | 21.71672 | 45.53614 | -0.2565 | 5.74932 |
Maximum of Months | 744.00000 | 23.94101 | 59.51454 | 0.58068 | 12.64233 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.17989 | 46.83995 | -0.0352 | 5.44969 |
February | 672.00000 | 22.72316 | 49.97512 | 0.13331 | 5.93916 |
March | 744.00000 | 23.43817 | 52.72753 | 0.35568 | 8.09101 |
April | 720.00000 | 23.86983 | 53.45599 | 0.50604 | 10.54464 |
May | 744.00000 | 23.96551 | 56.24034 | -0.2919 | 6.84617 |
June | 720.00000 | 23.94653 | 57.23157 | -0.2924 | 6.88415 |
July | 744.00000 | 23.95639 | 58.34455 | -0.2973 | 6.90127 |
August | 744.00000 | 23.94904 | 58.94314 | -0.3066 | 7.01197 |
September | 720.00000 | 23.86851 | 59.45222 | -0.3417 | 7.63813 |
October | 744.00000 | 23.79840 | 58.03724 | 0.50233 | 10.40374 |
November | 720.00000 | 23.37600 | 52.09498 | 0.32971 | 7.65137 |
December | 744.00000 | 22.51656 | 45.65785 | 0.04907 | 5.47818 |
Annual Sum or Average | 8760.00000 | 23.46849 | 54.10097 | 0.02476 | 7.40682 |
Minimum of Months | 672.00000 | 22.17989 | 45.65785 | -0.3417 | 5.44969 |
Maximum of Months | 744.00000 | 23.96551 | 59.45222 | 0.50604 | 10.54464 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.10994 | 40.77346 | 0.62821 | 14.84426 |
February | 672.00000 | 23.27601 | 44.69370 | 0.74546 | 18.16224 |
March | 744.00000 | 23.47903 | 48.92109 | 0.89992 | 23.24076 |
April | 720.00000 | 23.66235 | 50.86442 | 1.04301 | 28.69576 |
May | 744.00000 | 23.73652 | 53.86191 | 0.50659 | 11.85119 |
June | 720.00000 | 23.71334 | 54.65677 | 0.48993 | 11.64531 |
July | 744.00000 | 23.71346 | 55.38927 | 0.47086 | 11.12783 |
August | 744.00000 | 23.68781 | 55.85327 | 0.44477 | 10.65359 |
September | 720.00000 | 23.62962 | 56.29876 | 0.38929 | 9.88399 |
October | 744.00000 | 23.56803 | 55.16080 | 0.99821 | 26.83813 |
November | 720.00000 | 23.41380 | 48.22976 | 0.84437 | 21.26369 |
December | 744.00000 | 23.17967 | 40.30498 | 0.66002 | 15.67193 |
Annual Sum or Average | 8760.00000 | 23.51509 | 50.44143 | 0.67599 | 16.97058 |
Minimum of Months | 672.00000 | 23.10994 | 40.30498 | 0.38929 | 9.88399 |
Maximum of Months | 744.00000 | 23.73652 | 56.29876 | 1.04301 | 28.69576 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.92987 | 50.13959 | 0.20832 | 6.94330 |
February | 672.00000 | 23.34394 | 53.18894 | 0.37060 | 8.86593 |
March | 744.00000 | 23.70772 | 56.19931 | 0.54072 | 11.77116 |
April | 720.00000 | 23.89696 | 57.11070 | 0.65775 | 14.35492 |
May | 744.00000 | 23.95765 | 59.90362 | -0.0917 | 5.36085 |
June | 720.00000 | 23.94116 | 60.93107 | -0.0955 | 5.44393 |
July | 744.00000 | 23.93585 | 62.02344 | -0.1060 | 5.43119 |
August | 744.00000 | 23.92869 | 62.70100 | -0.1223 | 5.48949 |
September | 720.00000 | 23.87120 | 63.13122 | -0.1466 | 5.94477 |
October | 744.00000 | 23.88627 | 61.34122 | 0.68064 | 15.05492 |
November | 720.00000 | 23.79367 | 55.14882 | 0.56154 | 12.16529 |
December | 744.00000 | 23.23975 | 48.95638 | 0.30000 | 7.78895 |
Annual Sum or Average | 8760.00000 | 23.70378 | 57.58396 | 0.22847 | 8.70835 |
Minimum of Months | 672.00000 | 22.92987 | 48.95638 | -0.1466 | 5.36085 |
Maximum of Months | 744.00000 | 23.95765 | 63.13122 | 0.68064 | 15.05492 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.80009 | 49.05772 | 0.13056 | 5.78441 |
February | 672.00000 | 23.21764 | 52.33122 | 0.27419 | 7.03330 |
March | 744.00000 | 23.65077 | 55.46431 | 0.43644 | 9.30900 |
April | 720.00000 | 23.89020 | 56.35245 | 0.54312 | 11.32228 |
May | 744.00000 | 23.96140 | 58.95244 | -0.2511 | 6.36253 |
June | 720.00000 | 23.95607 | 59.80646 | -0.2440 | 6.30624 |
July | 744.00000 | 23.96355 | 60.73200 | -0.2411 | 6.25536 |
August | 744.00000 | 23.95891 | 61.33369 | -0.2495 | 6.33451 |
September | 720.00000 | 23.91968 | 61.85351 | -0.2743 | 6.68982 |
October | 744.00000 | 23.91011 | 60.49309 | 0.56854 | 11.83232 |
November | 720.00000 | 23.72380 | 54.49066 | 0.44458 | 9.35700 |
December | 744.00000 | 23.11367 | 48.00173 | 0.21316 | 6.34447 |
Annual Sum or Average | 8760.00000 | 23.67370 | 56.59028 | 0.11116 | 7.74272 |
Minimum of Months | 672.00000 | 22.80009 | 48.00173 | -0.2743 | 5.78441 |
Maximum of Months | 744.00000 | 23.96355 | 61.85351 | 0.56854 | 11.83232 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.44713 | 52.85823 | -0.2441 | 6.74469 |
February | 672.00000 | 21.59975 | 53.75033 | -0.1467 | 6.13503 |
March | 744.00000 | 21.70945 | 51.12306 | -0.0560 | 5.82008 |
April | 720.00000 | 21.75457 | 48.79382 | 0.01635 | 5.81256 |
May | 744.00000 | 21.76725 | 50.12921 | -0.9839 | 26.84972 |
June | 720.00000 | 21.76098 | 52.23462 | -0.9789 | 26.62955 |
July | 744.00000 | 21.75104 | 53.86461 | -1.0037 | 27.62513 |
August | 744.00000 | 21.74836 | 54.52786 | -1.0237 | 28.48409 |
September | 720.00000 | 21.74614 | 54.53132 | -1.0378 | 29.15348 |
October | 744.00000 | 21.73782 | 51.88778 | -0.0064 | 5.78489 |
November | 720.00000 | 21.70081 | 51.99148 | -0.0747 | 5.89471 |
December | 744.00000 | 21.56106 | 51.42029 | -0.2015 | 6.47750 |
Annual Sum or Average | 8760.00000 | 21.69056 | 52.25120 | -0.4807 | 15.17222 |
Minimum of Months | 672.00000 | 21.44713 | 48.79382 | -1.0378 | 5.78489 |
Maximum of Months | 744.00000 | 21.76725 | 54.53132 | 0.01635 | 29.15348 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25917 | 53.78370 | -0.3250 | 7.49440 |
February | 672.00000 | 21.77889 | 54.89279 | -0.1409 | 6.15276 |
March | 744.00000 | 22.07964 | 51.84932 | 0.00025 | 5.80627 |
April | 720.00000 | 21.89025 | 49.16343 | 0.03250 | 5.82724 |
May | 744.00000 | 21.77245 | 50.14505 | -0.9867 | 26.93789 |
June | 720.00000 | 21.76571 | 52.25384 | -0.9767 | 26.53747 |
July | 744.00000 | 21.75103 | 53.89035 | -1.0038 | 27.62458 |
August | 744.00000 | 21.74782 | 54.67114 | -1.0275 | 28.62868 |
September | 720.00000 | 21.75218 | 55.03054 | -1.0509 | 29.65057 |
October | 744.00000 | 22.04821 | 53.69593 | 0.03604 | 5.85966 |
November | 720.00000 | 22.02365 | 54.24380 | -0.0428 | 5.80471 |
December | 744.00000 | 21.41754 | 52.78428 | -0.2733 | 6.96983 |
Annual Sum or Average | 8760.00000 | 21.77292 | 53.02235 | -0.4824 | 15.33106 |
Minimum of Months | 672.00000 | 21.25917 | 49.16343 | -1.0509 | 5.80471 |
Maximum of Months | 744.00000 | 22.07964 | 55.03054 | 0.03604 | 29.65057 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30948 | 51.46008 | -0.3080 | 7.10161 |
February | 672.00000 | 21.69300 | 52.71870 | -0.1836 | 6.05912 |
March | 744.00000 | 21.94930 | 51.48031 | -0.0933 | 5.70617 |
April | 720.00000 | 21.81521 | 50.51058 | -0.0931 | 5.77474 |
May | 744.00000 | 21.73408 | 51.42498 | -1.1809 | 35.18553 |
June | 720.00000 | 21.73210 | 52.88047 | -1.1686 | 34.62569 |
July | 744.00000 | 21.72436 | 54.24963 | -1.1682 | 34.63717 |
August | 744.00000 | 21.71713 | 54.92112 | -1.1803 | 35.21017 |
September | 720.00000 | 21.70671 | 55.07926 | -1.2016 | 36.18498 |
October | 744.00000 | 21.93228 | 54.32882 | -0.0666 | 5.69238 |
November | 720.00000 | 21.84526 | 53.42450 | -0.1290 | 5.75598 |
December | 744.00000 | 21.39600 | 50.78006 | -0.2831 | 6.81798 |
Annual Sum or Average | 8760.00000 | 21.71240 | 52.76976 | -0.5907 | 18.30350 |
Minimum of Months | 672.00000 | 21.30948 | 50.51058 | -1.2016 | 5.69238 |
Maximum of Months | 744.00000 | 21.94930 | 55.07926 | -0.0666 | 36.18498 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50129 | 52.52144 | -0.2329 | 6.65134 |
February | 672.00000 | 21.64433 | 52.98101 | -0.1357 | 6.09429 |
March | 744.00000 | 21.73141 | 50.63211 | -0.0501 | 5.84386 |
April | 720.00000 | 21.75743 | 48.95330 | 0.02049 | 5.86081 |
May | 744.00000 | 21.76333 | 50.44432 | -0.9792 | 26.72453 |
June | 720.00000 | 21.75896 | 52.46566 | -0.9854 | 26.91410 |
July | 744.00000 | 21.75312 | 54.18713 | -0.9998 | 27.49299 |
August | 744.00000 | 21.75058 | 54.70021 | -1.0215 | 28.40840 |
September | 720.00000 | 21.74885 | 54.65031 | -1.0378 | 29.17732 |
October | 744.00000 | 21.74456 | 51.86960 | -0.0030 | 5.80259 |
November | 720.00000 | 21.72312 | 51.57827 | -0.0717 | 5.87398 |
December | 744.00000 | 21.59604 | 51.11461 | -0.1948 | 6.40949 |
Annual Sum or Average | 8760.00000 | 21.70614 | 52.17109 | -0.4766 | 15.15823 |
Minimum of Months | 672.00000 | 21.50129 | 48.95330 | -1.0378 | 5.80259 |
Maximum of Months | 744.00000 | 21.76333 | 54.70021 | 0.02049 | 29.17732 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25291 | 53.67703 | -0.3251 | 7.41480 |
February | 672.00000 | 21.83218 | 54.14442 | -0.1278 | 6.05949 |
March | 744.00000 | 22.15054 | 51.21622 | 0.01599 | 5.94335 |
April | 720.00000 | 21.91959 | 49.25579 | 0.04193 | 5.99172 |
May | 744.00000 | 21.76954 | 50.46269 | -0.9816 | 26.80176 |
June | 720.00000 | 21.76348 | 52.51160 | -0.9831 | 26.81693 |
July | 744.00000 | 21.75315 | 54.20906 | -0.9999 | 27.49392 |
August | 744.00000 | 21.75016 | 54.81796 | -1.0254 | 28.55785 |
September | 720.00000 | 21.75578 | 55.14264 | -1.0507 | 29.66550 |
October | 744.00000 | 22.08403 | 53.32829 | 0.04383 | 5.98443 |
November | 720.00000 | 22.07759 | 53.69888 | -0.0337 | 5.79359 |
December | 744.00000 | 21.41612 | 52.70422 | -0.2731 | 6.87625 |
Annual Sum or Average | 8760.00000 | 21.79251 | 52.92381 | -0.4774 | 15.33957 |
Minimum of Months | 672.00000 | 21.25291 | 49.25579 | -1.0507 | 5.79359 |
Maximum of Months | 744.00000 | 22.15054 | 55.14264 | 0.04383 | 29.66550 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43849 | 54.02725 | -0.2615 | 7.34198 |
February | 672.00000 | 21.58121 | 55.25197 | -0.1573 | 6.59450 |
March | 744.00000 | 21.69418 | 52.72054 | -0.0559 | 6.14257 |
April | 720.00000 | 21.75697 | 49.52295 | 0.02613 | 6.18499 |
May | 744.00000 | 21.77378 | 50.42223 | -0.9619 | 26.64612 |
June | 720.00000 | 21.76544 | 52.29673 | -0.9561 | 26.34742 |
July | 744.00000 | 21.75039 | 54.00645 | -0.9902 | 27.50924 |
August | 744.00000 | 21.74709 | 54.88581 | -1.0141 | 28.49702 |
September | 720.00000 | 21.74338 | 55.26396 | -1.0319 | 29.35051 |
October | 744.00000 | 21.72559 | 53.73558 | -0.0061 | 6.09549 |
November | 720.00000 | 21.67888 | 54.32848 | -0.0837 | 6.27432 |
December | 744.00000 | 21.54844 | 52.56787 | -0.2218 | 7.06953 |
Annual Sum or Average | 8760.00000 | 21.68392 | 53.24043 | -0.4784 | 15.39102 |
Minimum of Months | 672.00000 | 21.43849 | 49.52295 | -1.0319 | 6.09549 |
Maximum of Months | 744.00000 | 21.77378 | 55.26396 | 0.02613 | 29.35051 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28230 | 54.93122 | -0.3381 | 7.99863 |
February | 672.00000 | 21.81399 | 56.13337 | -0.1410 | 6.64210 |
March | 744.00000 | 22.03143 | 53.28368 | -0.0059 | 6.12249 |
April | 720.00000 | 21.86092 | 49.84187 | 0.03553 | 6.10780 |
May | 744.00000 | 21.77824 | 50.42628 | -0.9649 | 26.71169 |
June | 720.00000 | 21.76935 | 52.31356 | -0.9541 | 26.25697 |
July | 744.00000 | 21.75048 | 54.01182 | -0.9904 | 27.50673 |
August | 744.00000 | 21.74660 | 55.01631 | -1.0181 | 28.63191 |
September | 720.00000 | 21.74755 | 55.78555 | -1.0459 | 29.82078 |
October | 744.00000 | 21.96360 | 55.57503 | 0.02105 | 6.03193 |
November | 720.00000 | 21.96500 | 56.53897 | -0.0614 | 6.15600 |
December | 744.00000 | 21.42101 | 53.90051 | -0.2947 | 7.58809 |
Annual Sum or Average | 8760.00000 | 21.75962 | 53.96609 | -0.4823 | 15.51935 |
Minimum of Months | 672.00000 | 21.28230 | 49.84187 | -1.0459 | 6.03193 |
Maximum of Months | 744.00000 | 22.03143 | 56.53897 | 0.03553 | 29.82078 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62976 | 51.51993 | -0.1667 | 6.74046 |
February | 672.00000 | 21.65740 | 52.62686 | -0.1167 | 6.41359 |
March | 744.00000 | 21.71319 | 51.44786 | -0.0613 | 6.16236 |
April | 720.00000 | 21.74893 | 49.64792 | -0.0195 | 6.05557 |
May | 744.00000 | 21.75511 | 50.66378 | -1.0557 | 30.16192 |
June | 720.00000 | 21.75380 | 52.20741 | -1.0510 | 29.89461 |
July | 744.00000 | 21.74897 | 53.76351 | -1.0563 | 30.08354 |
August | 744.00000 | 21.74668 | 54.33013 | -1.0689 | 30.67726 |
September | 720.00000 | 21.74545 | 54.41009 | -1.0715 | 31.00369 |
October | 744.00000 | 21.74223 | 52.75976 | -0.0009 | 6.21938 |
November | 720.00000 | 21.72430 | 51.69269 | -0.0453 | 6.34820 |
December | 744.00000 | 21.68108 | 49.91769 | -0.1395 | 6.61378 |
Annual Sum or Average | 8760.00000 | 21.72085 | 52.07884 | -0.4902 | 16.42483 |
Minimum of Months | 672.00000 | 21.62976 | 49.64792 | -1.0715 | 6.05557 |
Maximum of Months | 744.00000 | 21.75511 | 54.41009 | -0.0009 | 31.00369 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.52932 | 49.09163 | 0.32010 | 7.59761 |
February | 672.00000 | 23.74682 | 52.20845 | 0.43635 | 9.30289 |
March | 744.00000 | 23.92552 | 55.44463 | 0.56838 | 11.97311 |
April | 720.00000 | 23.99100 | 56.82836 | 0.66076 | 14.27154 |
May | 744.00000 | 23.99621 | 59.50719 | -0.0901 | 5.21038 |
June | 720.00000 | 23.99597 | 60.15666 | -0.0787 | 5.18581 |
July | 744.00000 | 23.99579 | 60.94577 | -0.0897 | 5.20481 |
August | 744.00000 | 23.99564 | 61.49792 | -0.1060 | 5.26208 |
September | 720.00000 | 23.99373 | 62.05043 | -0.1359 | 5.43763 |
October | 744.00000 | 23.97134 | 61.31853 | 0.64607 | 13.82146 |
November | 720.00000 | 23.87076 | 55.29697 | 0.51543 | 10.77361 |
December | 744.00000 | 23.61850 | 48.47935 | 0.34856 | 7.93954 |
Annual Sum or Average | 8760.00000 | 23.88618 | 56.92231 | 0.24817 | 8.48717 |
Minimum of Months | 672.00000 | 23.52932 | 48.47935 | -0.1359 | 5.18581 |
Maximum of Months | 744.00000 | 23.99621 | 62.05043 | 0.66076 | 14.27154 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.69463 | 47.98142 | 0.39532 | 8.57767 |
February | 672.00000 | 23.85722 | 51.26254 | 0.49593 | 10.36157 |
March | 744.00000 | 23.96494 | 54.82252 | 0.60632 | 12.86381 |
April | 720.00000 | 23.99497 | 56.43847 | 0.68628 | 14.99467 |
May | 744.00000 | 23.99654 | 59.18083 | -0.0557 | 5.11046 |
June | 720.00000 | 23.99653 | 59.82669 | -0.0441 | 5.10113 |
July | 744.00000 | 23.99635 | 60.60343 | -0.0554 | 5.10401 |
August | 744.00000 | 23.99627 | 61.13645 | -0.0715 | 5.13729 |
September | 720.00000 | 23.99555 | 61.64535 | -0.0997 | 5.25895 |
October | 744.00000 | 23.98615 | 60.83330 | 0.67474 | 14.61220 |
November | 720.00000 | 23.93741 | 54.54865 | 0.56059 | 11.73291 |
December | 744.00000 | 23.76719 | 47.43600 | 0.41883 | 8.94054 |
Annual Sum or Average | 8760.00000 | 23.93206 | 56.33134 | 0.29115 | 8.96843 |
Minimum of Months | 672.00000 | 23.69463 | 47.43600 | -0.0997 | 5.10113 |
Maximum of Months | 744.00000 | 23.99654 | 61.64535 | 0.68628 | 14.99467 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78070 | 46.20490 | 1.01018 | 28.88473 |
February | 672.00000 | 23.85497 | 49.89696 | 1.10713 | 32.77852 |
March | 744.00000 | 23.95025 | 53.89716 | 1.24214 | 38.65363 |
April | 720.00000 | 23.98849 | 55.80509 | 1.35888 | 44.15189 |
May | 744.00000 | 23.99331 | 58.71652 | 0.91930 | 25.98776 |
June | 720.00000 | 23.99234 | 59.40689 | 0.91481 | 25.82007 |
July | 744.00000 | 23.99274 | 60.11155 | 0.88752 | 24.53652 |
August | 744.00000 | 23.99285 | 60.52552 | 0.86315 | 23.63747 |
September | 720.00000 | 23.99091 | 60.87358 | 0.82808 | 22.53751 |
October | 744.00000 | 23.98124 | 59.84131 | 1.32764 | 42.60765 |
November | 720.00000 | 23.90954 | 53.30913 | 1.18771 | 36.22214 |
December | 744.00000 | 23.79893 | 45.85331 | 1.02829 | 29.63537 |
Annual Sum or Average | 8760.00000 | 23.93580 | 55.39346 | 1.05564 | 31.26571 |
Minimum of Months | 672.00000 | 23.78070 | 45.85331 | 0.82808 | 22.53751 |
Maximum of Months | 744.00000 | 23.99331 | 60.87358 | 1.35888 | 44.15189 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.17136 | 46.35220 | -0.3114 | 7.18489 |
February | 672.00000 | 21.65780 | 49.82558 | -0.1573 | 5.90321 |
March | 744.00000 | 22.62121 | 52.10062 | 0.10931 | 5.64046 |
April | 720.00000 | 23.62588 | 51.74339 | 0.37220 | 8.13064 |
May | 744.00000 | 23.96250 | 54.37503 | -0.3915 | 8.23516 |
June | 720.00000 | 23.94408 | 55.65880 | -0.3820 | 8.10185 |
July | 744.00000 | 23.97574 | 56.93148 | -0.3660 | 7.81229 |
August | 744.00000 | 23.97066 | 57.62241 | -0.3746 | 7.93881 |
September | 720.00000 | 23.81755 | 58.23139 | -0.4405 | 9.21857 |
October | 744.00000 | 23.36202 | 56.90804 | 0.33553 | 7.49893 |
November | 720.00000 | 22.40465 | 51.88104 | 0.05045 | 5.31990 |
December | 744.00000 | 21.41800 | 45.36856 | -0.2466 | 6.46486 |
Annual Sum or Average | 8760.00000 | 23.00030 | 53.09579 | -0.1507 | 7.29440 |
Minimum of Months | 672.00000 | 21.17136 | 45.36856 | -0.4405 | 5.31990 |
Maximum of Months | 744.00000 | 23.97574 | 58.23139 | 0.37220 | 9.21857 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28076 | 49.36330 | -0.2968 | 6.94812 |
February | 672.00000 | 21.95772 | 52.29748 | -0.1040 | 5.62253 |
March | 744.00000 | 23.01836 | 54.37709 | 0.18320 | 6.08150 |
April | 720.00000 | 23.81491 | 54.52044 | 0.39425 | 8.35549 |
May | 744.00000 | 23.96133 | 57.16037 | -0.4526 | 9.29800 |
June | 720.00000 | 23.93726 | 58.24631 | -0.4543 | 9.33883 |
July | 744.00000 | 23.93925 | 59.42603 | -0.4496 | 9.24319 |
August | 744.00000 | 23.90132 | 60.23886 | -0.4630 | 9.51524 |
September | 720.00000 | 23.74189 | 60.89121 | -0.5172 | 10.85966 |
October | 744.00000 | 23.71054 | 59.04571 | 0.39548 | 8.33102 |
November | 720.00000 | 22.95600 | 53.70449 | 0.16226 | 5.81304 |
December | 744.00000 | 21.66061 | 48.06172 | -0.2053 | 6.10330 |
Annual Sum or Average | 8760.00000 | 23.16152 | 55.62484 | -0.1515 | 7.97143 |
Minimum of Months | 672.00000 | 21.28076 | 48.06172 | -0.5172 | 5.62253 |
Maximum of Months | 744.00000 | 23.96133 | 60.89121 | 0.39548 | 10.85966 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26948 | 47.35946 | -0.2881 | 6.93082 |
February | 672.00000 | 21.81919 | 50.65719 | -0.1094 | 5.84243 |
March | 744.00000 | 22.90965 | 52.47493 | 0.20019 | 6.72863 |
April | 720.00000 | 23.72664 | 52.53211 | 0.43438 | 9.23689 |
May | 744.00000 | 23.94083 | 55.10339 | -0.3502 | 7.65432 |
June | 720.00000 | 23.91798 | 56.06034 | -0.3485 | 7.69814 |
July | 744.00000 | 23.93785 | 57.06996 | -0.3493 | 7.63251 |
August | 744.00000 | 23.90246 | 57.77291 | -0.3706 | 7.97052 |
September | 720.00000 | 23.70453 | 58.63602 | -0.4457 | 9.53726 |
October | 744.00000 | 23.48276 | 57.53612 | 0.39022 | 8.52593 |
November | 720.00000 | 22.55802 | 52.67941 | 0.10295 | 5.96051 |
December | 744.00000 | 21.41649 | 46.60457 | -0.2458 | 6.62041 |
Annual Sum or Average | 8760.00000 | 23.05424 | 53.71835 | -0.1156 | 7.53570 |
Minimum of Months | 672.00000 | 21.26948 | 46.60457 | -0.4457 | 5.84243 |
Maximum of Months | 744.00000 | 23.94083 | 58.63602 | 0.43438 | 9.53726 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16239 | 46.11081 | -0.3162 | 7.25515 |
February | 672.00000 | 21.62681 | 49.63561 | -0.1636 | 5.98189 |
March | 744.00000 | 22.62766 | 51.78971 | 0.11475 | 5.72505 |
April | 720.00000 | 23.65616 | 51.36405 | 0.38786 | 8.39678 |
May | 744.00000 | 23.96760 | 54.04756 | -0.3700 | 7.89865 |
June | 720.00000 | 23.94655 | 55.29968 | -0.3615 | 7.79869 |
July | 744.00000 | 23.98041 | 56.48731 | -0.3455 | 7.51142 |
August | 744.00000 | 23.97714 | 57.12948 | -0.3552 | 7.64376 |
September | 720.00000 | 23.83500 | 57.72662 | -0.4215 | 8.87851 |
October | 744.00000 | 23.38530 | 56.51260 | 0.34655 | 7.68916 |
November | 720.00000 | 22.36911 | 51.69457 | 0.04507 | 5.35845 |
December | 744.00000 | 21.36540 | 45.23595 | -0.2590 | 6.61314 |
Annual Sum or Average | 8760.00000 | 22.99780 | 52.76455 | -0.1419 | 7.23532 |
Minimum of Months | 672.00000 | 21.16239 | 45.23595 | -0.4215 | 5.35845 |
Maximum of Months | 744.00000 | 23.98041 | 57.72662 | 0.38786 | 8.87851 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.375103E+11 | 93575.91 | 12-JAN-16:01 | 622.23 | 0.106372E+12 | 0.00 | 0.143882E+12 | 2.49 | 3.46 | 11-JAN-16:01 | 0.00 | 0.00 |
February | 0.797948E+11 | 113381.30 | 22-FEB-16:03 | 653.42 | 0.221444E+12 | 0.00 | 0.301239E+12 | 2.82 | 3.76 | 24-FEB-22:53 | 0.00 | 0.00 |
March | 0.179734E+12 | 164984.80 | 28-MAR-15:03 | 744.00 | 0.515016E+12 | 0.00 | 0.694749E+12 | 2.86 | 3.84 | 06-MAR-22:52 | 0.00 | 0.00 |
April | 0.286980E+12 | 218849.26 | 26-APR-18:03 | 720.00 | 0.813918E+12 | 0.00 | 0.110090E+13 | 2.84 | 3.67 | 22-APR-21:53 | 0.00 | 0.00 |
May | 0.396535E+12 | 267994.15 | 17-MAY-18:03 | 744.00 | 0.112456E+13 | 0.00 | 0.152109E+13 | 2.87 | 3.69 | 24-MAY-08:61 | 0.00 | 0.00 |
June | 0.435665E+12 | 297832.83 | 10-JUN-18:03 | 720.00 | 0.125689E+13 | 0.00 | 0.169255E+13 | 2.92 | 3.77 | 24-JUN-08:03 | 0.00 | 0.00 |
July | 0.461365E+12 | 292527.81 | 01-JUL-18:03 | 744.00 | 0.143573E+13 | 0.00 | 0.189709E+13 | 3.14 | 3.80 | 19-JUL-02:00 | 0.00 | 0.00 |
August | 0.438772E+12 | 271373.37 | 28-AUG-18:03 | 744.00 | 0.142783E+13 | 0.00 | 0.186660E+13 | 3.27 | 3.84 | 16-AUG-08:61 | 0.00 | 0.00 |
September | 0.375285E+12 | 259573.64 | 17-SEP-18:03 | 720.00 | 0.123373E+13 | 0.00 | 0.160901E+13 | 3.30 | 3.87 | 07-SEP-08:61 | 0.00 | 0.00 |
October | 0.259176E+12 | 197266.32 | 03-OCT-15:03 | 744.00 | 0.805972E+12 | 0.00 | 0.106515E+13 | 3.09 | 4.15 | 25-OCT-21:52 | 0.00 | 0.00 |
November | 0.135150E+12 | 135499.92 | 04-NOV-15:03 | 720.00 | 0.386460E+12 | 0.00 | 0.521610E+12 | 2.90 | 4.00 | 08-NOV-22:53 | 0.00 | 0.00 |
December | 0.517649E+11 | 109035.08 | 02-DEC-16:01 | 706.75 | 0.144990E+12 | 0.00 | 0.196755E+12 | 2.82 | 3.69 | 02-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.313773E+13 | 8582.39 | 0.947289E+13 | 0.00 | 0.126106E+14 | 2.94 | 0.00 | 0.00 | ||||
Minimum of Months | 0.375103E+11 | 93575.91 | 622.23 | 0.106372E+12 | 0.00 | 0.143882E+12 | 2.49 | 3.46 | 0.00 | 0.00 | ||
Maximum of Months | 0.461365E+12 | 297832.83 | 744.00 | 0.143573E+13 | 0.00 | 0.189709E+13 | 3.30 | 4.15 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.103768E+11 | 0.00 | 611.58 | 47147.41 | 02-JAN-09:04 | 0.00 | 40.96 | 56.68 | 0.05 | 0.00 | 0.01 | 0.16 | 02-JAN-09:04 |
February | 0.242335E+10 | 0.00 | 284.84 | 35276.97 | 09-FEB-16:05 | 0.00 | 41.88 | 49.48 | 0.01 | 0.00 | 0.00 | 0.12 | 09-FEB-16:05 |
March | 0.168125E+09 | 0.00 | 32.77 | 20029.32 | 15-MAR-08:54 | 0.00 | 39.89 | 40.70 | 0.00 | 0.00 | 0.00 | 0.07 | 15-MAR-08:54 |
April | 76836224.41 | 0.00 | 2.37 | 20960.01 | 07-APR-08:54 | 0.00 | 39.02 | 39.09 | 0.00 | 0.00 | 0.00 | 0.07 | 07-APR-08:54 |
May | 39005946.13 | 0.00 | 1.36 | 14335.34 | 12-MAY-15:06 | 0.00 | 39.88 | 39.91 | 0.00 | 0.00 | 0.00 | 0.05 | 12-MAY-15:06 |
June | 36919022.96 | 0.00 | 1.36 | 15346.71 | 24-JUN-15:06 | 0.00 | 40.68 | 40.72 | 0.00 | 0.00 | 0.00 | 0.05 | 24-JUN-15:06 |
July | 33081249.39 | 0.00 | 1.54 | 14372.48 | 27-JUL-08:04 | 0.00 | 41.52 | 41.56 | 0.00 | 0.00 | 0.00 | 0.05 | 27-JUL-08:04 |
August | 49966863.05 | 0.00 | 1.99 | 14480.36 | 16-AUG-08:04 | 0.00 | 41.77 | 41.82 | 0.00 | 0.00 | 0.00 | 0.05 | 16-AUG-08:04 |
September | 76230679.35 | 0.00 | 2.70 | 16016.18 | 07-SEP-08:04 | 0.00 | 41.13 | 41.21 | 0.00 | 0.00 | 0.00 | 0.06 | 07-SEP-08:04 |
October | 0.142399E+09 | 0.00 | 6.13 | 20071.52 | 24-OCT-08:54 | 0.00 | 38.92 | 39.10 | 0.00 | 0.00 | 0.00 | 0.07 | 24-OCT-08:54 |
November | 0.340087E+09 | 0.00 | 126.91 | 24305.08 | 28-NOV-16:04 | 0.00 | 41.81 | 44.96 | 0.00 | 0.00 | 0.00 | 0.08 | 28-NOV-16:04 |
December | 0.535567E+10 | 0.00 | 464.30 | 39325.97 | 23-DEC-09:05 | 0.00 | 42.66 | 53.37 | 0.03 | 0.00 | 0.01 | 0.14 | 23-DEC-09:05 |
Annual Sum or Average | 0.191185E+11 | 0.00 | 1537.85 | 0.00 | 40.84 | 44.03 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 33081249.39 | 0.00 | 1.36 | 14335.34 | 0.00 | 38.92 | 39.09 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.103768E+11 | 0.00 | 611.58 | 47147.41 | 0.00 | 42.66 | 56.68 | 0.05 | 0.00 | 0.01 | 0.16 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.585799E+11 | 0.00 | 424.36 | 0.585799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130887.64 | 12-JAN-16:10 | 130887.64 | 12-JAN-16:10 | 0.00 | 0.00 | 0.00 |
February | 0.140729E+12 | 0.00 | 531.07 | 0.138655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 180647.37 | 22-FEB-19:10 | 180647.37 | 22-FEB-19:10 | 0.00 | 0.00 | 0.00 |
March | 0.347040E+12 | 0.00 | 738.92 | 0.329234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 320382.24 | 10-MAR-20:10 | 259365.51 | 28-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.566157E+12 | 0.00 | 720.00 | 0.510719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 382441.05 | 26-APR-21:00 | 317264.07 | 27-APR-20:10 | 0.00 | 0.00 | 0.00 |
May | 0.811077E+12 | 0.00 | 744.00 | 0.621735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 489660.93 | 22-MAY-20:00 | 347429.18 | 05-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.935341E+12 | 0.00 | 720.00 | 0.616860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 545982.40 | 29-JUN-21:00 | 363208.71 | 12-JUN-18:13 | 0.00 | 0.00 | 0.00 |
July | 0.109794E+13 | 0.00 | 744.00 | 0.609467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 568079.77 | 01-JUL-17:17 | 344428.58 | 04-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.110559E+13 | 0.00 | 744.00 | 0.581636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 567277.87 | 28-AUG-18:02 | 326293.89 | 07-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.948320E+12 | 0.00 | 720.00 | 0.531195E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 539680.39 | 14-SEP-18:02 | 317528.99 | 17-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.572352E+12 | 0.00 | 744.00 | 0.447907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 411809.11 | 12-OCT-20:00 | 284546.52 | 02-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.246967E+12 | 0.00 | 673.38 | 0.240298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281546.00 | 08-NOV-19:03 | 211718.52 | 03-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 0.808798E+11 | 0.00 | 454.46 | 0.808097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140753.38 | 03-DEC-13:00 | 140753.38 | 03-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691097E+13 | 0.00 | 7958.18 | 0.476709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.585799E+11 | 0.00 | 424.36 | 0.585799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130887.64 | 130887.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110559E+13 | 0.00 | 744.00 | 0.621735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 568079.77 | 363208.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.414961E+10 | 0.00 | 195.67 | 0.413550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.06 | 12-JAN-16:01 | 15714.06 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.984670E+10 | 0.00 | 316.33 | 0.927230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25424.56 | 25-FEB-17:00 | 17683.77 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.256342E+11 | 0.00 | 572.00 | 0.231689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26146.32 | 18-MAR-16:10 | 21052.89 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.365398E+11 | 0.00 | 570.00 | 0.329944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29289.91 | 25-APR-08:61 | 22742.17 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.492159E+11 | 0.00 | 589.00 | 0.374126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38342.03 | 22-MAY-23:00 | 24249.15 | 03-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.593928E+11 | 0.00 | 570.00 | 0.371271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47260.28 | 28-JUN-13:00 | 24330.21 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.731211E+11 | 0.00 | 589.00 | 0.372468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45566.21 | 18-JUL-15:00 | 23127.93 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.740364E+11 | 0.00 | 589.00 | 0.359033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47804.25 | 12-AUG-08:61 | 22120.25 | 07-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.639558E+11 | 0.00 | 570.00 | 0.335574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45733.00 | 12-SEP-15:02 | 21596.57 | 17-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.404807E+11 | 0.00 | 589.00 | 0.293477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40480.49 | 13-OCT-08:15 | 21397.36 | 02-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.154323E+11 | 0.00 | 461.17 | 0.141476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25763.49 | 08-NOV-19:40 | 19074.84 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.544276E+10 | 0.00 | 207.33 | 0.542117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16094.49 | 28-DEC-16:01 | 16094.49 | 28-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457248E+12 | 0.00 | 5818.50 | 0.299735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.414961E+10 | 0.00 | 195.67 | 0.413550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.06 | 15714.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.740364E+11 | 0.00 | 589.00 | 0.374126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47804.25 | 24330.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122744E+10 | 0.00 | 287.46 | 0.492845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15822.32 | 18-JAN-16:01 | 15483.76 | 21-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.328430E+10 | 0.00 | 477.19 | 0.143570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15851.17 | 25-FEB-19:01 | 14421.68 | 11-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.823068E+10 | 0.00 | 689.61 | 0.451623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16106.35 | 18-MAR-08:62 | 14491.88 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.130013E+11 | 0.00 | 697.03 | 0.900493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15494.59 | 23-APR-08:61 | 14566.23 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.159553E+11 | 0.00 | 729.45 | 0.113543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15574.30 | 13-MAY-08:61 | 14561.06 | 21-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.156985E+11 | 0.00 | 705.52 | 0.106626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16534.18 | 25-JUN-08:61 | 14582.81 | 17-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.150955E+11 | 0.00 | 725.47 | 0.937486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16657.94 | 18-JUL-15:02 | 14538.67 | 10-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.140342E+11 | 0.00 | 722.58 | 0.822545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16541.27 | 20-AUG-08:61 | 14587.57 | 09-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.126212E+11 | 0.00 | 694.62 | 0.734479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18176.89 | 09-SEP-15:01 | 14547.72 | 13-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.111413E+11 | 0.00 | 710.20 | 0.653659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16961.31 | 12-OCT-08:61 | 14579.91 | 12-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.659426E+10 | 0.00 | 662.24 | 0.314691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16206.42 | 18-NOV-09:01 | 14379.61 | 14-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.187867E+10 | 0.00 | 395.78 | 0.714613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16122.01 | 20-DEC-16:01 | 16122.01 | 20-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118763E+12 | 0.00 | 7497.15 | 0.728098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.122744E+10 | 0.00 | 287.46 | 0.492845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15494.59 | 14379.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159553E+11 | 0.00 | 729.45 | 0.113543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18176.89 | 16122.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.152232E+09 | 0.00 | 72.01 | 64199720.66 | 0.00 | 0.00 | 0.00 | 0.00 | 15683.12 | 15-JAN-09:02 | 13910.11 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.121113E+10 | 0.00 | 251.79 | 0.442657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16381.57 | 24-FEB-22:52 | 14510.10 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.588472E+10 | 0.00 | 511.72 | 0.312035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16563.41 | 13-MAR-21:51 | 14561.55 | 15-MAR-21:51 | 0.00 | 0.00 | 0.00 |
April | 0.118335E+11 | 0.00 | 645.41 | 0.808735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17226.17 | 03-APR-08:61 | 15796.96 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.157404E+11 | 0.00 | 726.88 | 0.111474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18330.64 | 13-MAY-08:11 | 14624.74 | 21-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.157148E+11 | 0.00 | 704.20 | 0.106750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17072.51 | 18-JUN-06:51 | 14626.41 | 19-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.150837E+11 | 0.00 | 725.47 | 0.934413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16725.29 | 18-JUL-15:02 | 14627.88 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.138273E+11 | 0.00 | 722.23 | 0.800426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16612.13 | 20-AUG-08:61 | 14532.84 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.118087E+11 | 0.00 | 688.62 | 0.654598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18291.95 | 09-SEP-15:01 | 14580.38 | 26-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.827357E+10 | 0.00 | 575.58 | 0.452585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18319.81 | 06-OCT-08:61 | 15062.96 | 17-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.313616E+10 | 0.00 | 434.80 | 0.125138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16976.50 | 08-NOV-22:51 | 14378.97 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.304539E+09 | 0.00 | 115.03 | 0.108246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15688.67 | 20-DEC-16:01 | 15688.67 | 20-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102971E+12 | 0.00 | 6173.76 | 0.633168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.152232E+09 | 0.00 | 72.01 | 64199720.66 | 0.00 | 0.00 | 0.00 | 0.00 | 15683.12 | 13910.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.157404E+11 | 0.00 | 726.88 | 0.111474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18330.64 | 15796.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200527E+11 | 0.00 | 466.84 | 0.948964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31038.16 | 08-JAN-14:30 | 24950.69 | 21-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 0.287159E+11 | 0.00 | 558.44 | 0.123779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35674.12 | 20-FEB-14:30 | 29912.04 | 05-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 0.471863E+11 | 0.00 | 740.83 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40249.41 | 12-MAR-15:01 | 29109.97 | 13-MAR-13:50 | 0.00 | 0.00 | 0.00 |
April | 0.608108E+11 | 0.00 | 720.00 | 0.317466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41347.30 | 16-APR-15:02 | 31232.26 | 15-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.699754E+11 | 0.00 | 744.00 | 0.364256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42689.52 | 04-MAY-17:20 | 34139.04 | 04-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.683713E+11 | 0.00 | 719.17 | 0.337071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41714.11 | 09-JUN-20:20 | 32262.19 | 12-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.707162E+11 | 0.00 | 743.00 | 0.318674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42120.10 | 08-JUL-08:00 | 30013.77 | 04-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.677445E+11 | 0.00 | 744.00 | 0.285964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39723.97 | 07-AUG-20:20 | 25551.15 | 07-AUG-20:20 | 0.00 | 0.00 | 0.00 |
September | 0.647402E+11 | 0.00 | 717.09 | 0.299421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45051.19 | 24-SEP-15:02 | 34230.24 | 26-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.687104E+11 | 0.00 | 744.00 | 0.384064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48020.60 | 02-OCT-15:01 | 42487.37 | 02-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.540127E+11 | 0.00 | 715.93 | 0.295124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.04 | 09-NOV-13:00 | 38607.35 | 08-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.284762E+11 | 0.00 | 584.48 | 0.132195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37305.84 | 02-DEC-13:40 | 29154.18 | 20-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649513E+12 | 0.00 | 8197.78 | 0.317043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.200527E+11 | 0.00 | 466.84 | 0.948964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31038.16 | 24950.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.707162E+11 | 0.00 | 744.00 | 0.384064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48020.60 | 42487.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.812306E+10 | 0.00 | 277.61 | 0.270296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110722.99 | 16-JAN-09:02 | 106249.23 | 21-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.170637E+11 | 0.00 | 315.48 | 0.680658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117548.74 | 15-FEB-22:52 | 102273.20 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.426858E+11 | 0.00 | 441.73 | 0.239170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114984.85 | 18-MAR-21:52 | 103627.50 | 29-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.700171E+11 | 0.00 | 592.56 | 0.438664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114263.39 | 22-APR-21:51 | 104000.19 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.949551E+11 | 0.00 | 688.45 | 0.626232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124982.13 | 13-MAY-08:11 | 103863.37 | 16-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.966437E+11 | 0.00 | 664.35 | 0.631253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121449.48 | 24-JUN-15:01 | 104017.85 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.985974E+11 | 0.00 | 683.70 | 0.614988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121987.19 | 18-JUL-15:02 | 104179.75 | 29-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.915601E+11 | 0.00 | 667.57 | 0.544993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122931.78 | 11-AUG-15:02 | 104234.50 | 11-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.772259E+11 | 0.00 | 622.21 | 0.435234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127840.01 | 09-SEP-15:01 | 104260.69 | 03-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.552277E+11 | 0.00 | 506.56 | 0.314849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127736.14 | 11-OCT-21:51 | 103563.65 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.273797E+11 | 0.00 | 360.17 | 0.119220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117985.24 | 17-NOV-22:52 | 103856.89 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.104186E+11 | 0.00 | 366.04 | 0.362228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113669.55 | 29-DEC-22:53 | 107051.35 | 30-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689898E+12 | 0.00 | 6186.43 | 0.409592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.812306E+10 | 0.00 | 277.61 | 0.270296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110722.99 | 102273.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.985974E+11 | 0.00 | 688.45 | 0.631253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127840.01 | 107051.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.120117E+10 | 0.00 | 294.21 | 0.467976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14141.74 | 15-JAN-09:02 | 13914.29 | 21-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.346357E+10 | 0.00 | 494.63 | 0.158517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14438.77 | 25-FEB-19:01 | 13161.58 | 08-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.833831E+10 | 0.00 | 707.87 | 0.466574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14632.70 | 18-MAR-08:62 | 13203.75 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.130068E+11 | 0.00 | 706.52 | 0.905262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13265.68 | 23-APR-08:61 | 13059.97 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.160447E+11 | 0.00 | 733.58 | 0.117000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13984.66 | 13-MAY-08:61 | 13197.57 | 12-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.152972E+11 | 0.00 | 707.36 | 0.105340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14955.19 | 24-JUN-15:01 | 13199.72 | 23-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.151060E+11 | 0.00 | 727.51 | 0.964516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15119.44 | 18-JUL-15:02 | 13198.03 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.140042E+11 | 0.00 | 725.71 | 0.843547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14952.21 | 20-AUG-08:61 | 13167.90 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.124891E+11 | 0.00 | 698.23 | 0.738151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16464.42 | 09-SEP-15:01 | 13230.82 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.111834E+11 | 0.00 | 719.08 | 0.666680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15311.07 | 12-OCT-08:61 | 13215.99 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.657151E+10 | 0.00 | 671.24 | 0.333379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14508.80 | 18-NOV-09:01 | 13055.52 | 22-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.189162E+10 | 0.00 | 400.23 | 0.748279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14614.20 | 20-DEC-16:01 | 14614.20 | 20-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118598E+12 | 0.00 | 7586.16 | 0.742165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120117E+10 | 0.00 | 294.21 | 0.467976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13265.68 | 13055.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.160447E+11 | 0.00 | 733.58 | 0.117000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16464.42 | 14614.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185767E+09 | 0.00 | 81.76 | 62684381.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14194.01 | 15-JAN-09:02 | 12334.62 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.137704E+10 | 0.00 | 269.78 | 0.539270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14962.67 | 24-FEB-22:52 | 13379.96 | 24-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.590655E+10 | 0.00 | 535.86 | 0.317669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15784.88 | 10-MAR-09:51 | 13860.03 | 05-MAR-09:51 | 0.00 | 0.00 | 0.00 |
April | 0.118068E+11 | 0.00 | 652.94 | 0.803023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16137.65 | 22-APR-08:11 | 14866.77 | 07-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.158260E+11 | 0.00 | 730.77 | 0.114666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16752.34 | 13-MAY-08:11 | 13205.45 | 12-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.153139E+11 | 0.00 | 705.94 | 0.105468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15435.08 | 18-JUN-06:51 | 13246.43 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.150937E+11 | 0.00 | 727.67 | 0.962750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15145.74 | 18-JUL-15:02 | 13216.54 | 08-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.137986E+11 | 0.00 | 725.47 | 0.822068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14982.19 | 20-AUG-08:61 | 13242.17 | 26-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.116753E+11 | 0.00 | 694.04 | 0.652305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16531.57 | 09-SEP-15:01 | 13224.64 | 19-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.829055E+10 | 0.00 | 584.51 | 0.461818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16690.70 | 06-OCT-08:61 | 14338.99 | 15-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.305626E+10 | 0.00 | 441.45 | 0.127509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15294.54 | 09-NOV-09:51 | 13239.67 | 14-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.369237E+09 | 0.00 | 128.51 | 0.128259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13476.07 | 16-DEC-16:01 | 12743.08 | 18-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102700E+12 | 0.00 | 6278.70 | 0.642151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.185767E+09 | 0.00 | 81.76 | 62684381.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13476.07 | 12334.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.158260E+11 | 0.00 | 730.77 | 0.114666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16752.34 | 14866.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.355992E+09 | 0.00 | 232.38 | 0.166109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4555.54 | 18-JAN-16:01 | 4342.67 | 21-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.813055E+09 | 0.00 | 395.08 | 0.390819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4628.80 | 25-FEB-09:01 | 4066.48 | 15-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.200081E+10 | 0.00 | 665.45 | 0.112864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4705.50 | 18-MAR-08:62 | 3952.04 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.332533E+10 | 0.00 | 695.10 | 0.226625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4732.12 | 23-APR-08:61 | 4044.22 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.417630E+10 | 0.00 | 727.87 | 0.288500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4620.74 | 13-MAY-08:61 | 4069.18 | 19-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.413793E+10 | 0.00 | 704.42 | 0.277957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4934.58 | 25-JUN-08:61 | 4069.53 | 11-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.389950E+10 | 0.00 | 724.75 | 0.233784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.76 | 28-JUL-08:61 | 4070.94 | 22-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.357756E+10 | 0.00 | 721.95 | 0.200445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4882.18 | 20-AUG-08:61 | 4065.31 | 22-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.317401E+10 | 0.00 | 693.62 | 0.177210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4906.32 | 09-SEP-08:61 | 4074.50 | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.268056E+10 | 0.00 | 702.71 | 0.155061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4989.41 | 12-OCT-08:61 | 4074.14 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.148338E+10 | 0.00 | 583.55 | 0.754294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.74 | 18-NOV-09:01 | 4003.06 | 17-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.482059E+09 | 0.00 | 313.34 | 0.208167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4503.14 | 30-DEC-16:01 | 4503.14 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301065E+11 | 0.00 | 7160.22 | 0.182438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.355992E+09 | 0.00 | 232.38 | 0.166109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4503.14 | 3952.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.417630E+10 | 0.00 | 727.87 | 0.288500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4989.41 | 4503.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 40043453.90 | 0.00 | 50.44 | 18970649.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4463.05 | 18-JAN-16:01 | 3954.35 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.272481E+09 | 0.00 | 187.53 | 0.115032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4700.57 | 15-FEB-22:52 | 4089.44 | 11-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.144073E+10 | 0.00 | 503.65 | 0.777356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4707.42 | 29-MAR-08:51 | 4094.94 | 15-MAR-21:51 | 0.00 | 0.00 | 0.00 |
April | 0.304825E+10 | 0.00 | 645.48 | 0.204492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4923.85 | 03-APR-08:61 | 4456.01 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.412185E+10 | 0.00 | 725.49 | 0.283125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5308.85 | 13-MAY-08:11 | 4084.73 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.414362E+10 | 0.00 | 703.09 | 0.278201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4997.68 | 18-JUN-08:61 | 4069.96 | 11-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.389660E+10 | 0.00 | 725.04 | 0.233223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4695.10 | 28-JUL-08:61 | 4081.75 | 28-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.352341E+10 | 0.00 | 721.31 | 0.194689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4899.14 | 20-AUG-08:61 | 4073.70 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.296185E+10 | 0.00 | 687.44 | 0.156202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.99 | 09-SEP-08:61 | 4078.08 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.199117E+10 | 0.00 | 575.33 | 0.105644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5318.91 | 06-OCT-08:61 | 4093.86 | 09-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.638375E+09 | 0.00 | 342.59 | 0.282875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.70 | 08-NOV-22:51 | 3971.59 | 12-NOV-22:52 | 0.00 | 0.00 | 0.00 |
December | 66635806.38 | 0.00 | 82.39 | 26189683.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4516.25 | 20-DEC-16:01 | 4516.25 | 20-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261450E+11 | 0.00 | 5949.78 | 0.157762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 40043453.90 | 0.00 | 50.44 | 18970649.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4463.05 | 3954.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.414362E+10 | 0.00 | 725.49 | 0.283125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5318.91 | 4516.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.568166E+10 | 0.00 | 458.43 | 0.322585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21829.20 | 17-JAN-16:01 | 20858.58 | 31-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.771258E+10 | 0.00 | 525.18 | 0.455013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21432.91 | 25-FEB-19:01 | 19000.54 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.127121E+11 | 0.00 | 696.69 | 0.784600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20978.49 | 18-MAR-18:01 | 18751.72 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.166426E+11 | 0.00 | 694.47 | 0.113271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20711.24 | 23-APR-08:61 | 18957.47 | 14-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.195712E+11 | 0.00 | 724.59 | 0.133336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20899.70 | 13-MAY-08:61 | 18985.36 | 12-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.192479E+11 | 0.00 | 699.51 | 0.127893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21330.11 | 24-JUN-15:01 | 18983.64 | 20-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.194126E+11 | 0.00 | 722.07 | 0.120006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21576.96 | 18-JUL-15:02 | 18968.77 | 25-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.184110E+11 | 0.00 | 719.25 | 0.108875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21100.95 | 20-AUG-08:61 | 18940.84 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.172887E+11 | 0.00 | 692.75 | 0.104107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22494.05 | 09-SEP-15:01 | 18915.86 | 26-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.177552E+11 | 0.00 | 712.26 | 0.116016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22722.63 | 12-OCT-08:61 | 18862.90 | 02-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.134842E+11 | 0.00 | 676.27 | 0.884520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20909.19 | 18-NOV-09:01 | 18857.12 | 17-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.724895E+10 | 0.00 | 535.26 | 0.432148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20940.47 | 31-DEC-16:01 | 20940.47 | 31-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175169E+12 | 0.00 | 7856.72 | 0.111139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.568166E+10 | 0.00 | 458.43 | 0.322585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20711.24 | 18751.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195712E+11 | 0.00 | 724.59 | 0.133336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22722.63 | 20940.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.20 | 338.55 | 217.64 | 793.08 | 404.97 | 0.00 | 0.00 | 0.00 |
February | 527.68 | 293.11 | 234.58 | 816.17 | 318.03 | 0.00 | 0.00 | 0.00 |
March | 448.38 | 196.62 | 251.76 | 802.39 | 195.14 | 0.00 | 0.00 | 0.00 |
April | 319.67 | 92.19 | 227.48 | 754.00 | 66.43 | 0.00 | 0.00 | 0.00 |
May | 230.45 | 19.41 | 211.03 | 704.21 | 8.39 | 0.00 | 0.00 | 0.00 |
June | 208.43 | 3.62 | 204.81 | 692.64 | 5.19 | 0.00 | 0.00 | 0.00 |
July | 216.49 | 2.12 | 214.37 | 650.31 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 228.27 | 10.00 | 218.27 | 604.34 | 3.19 | 0.00 | 0.00 | 0.00 |
September | 315.87 | 86.97 | 228.90 | 696.66 | 18.64 | 0.00 | 0.00 | 0.00 |
October | 534.76 | 299.93 | 234.83 | 1009.46 | 155.19 | 0.00 | 0.00 | 0.00 |
November | 667.22 | 442.03 | 225.19 | 1106.91 | 300.04 | 0.00 | 0.00 | 0.00 |
December | 593.54 | 372.23 | 221.31 | 879.26 | 398.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 403.18 | 179.06 | 224.12 | 792.04 | 155.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 208.43 | 2.12 | 204.81 | 604.34 | 0.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 667.22 | 442.03 | 251.76 | 1106.91 | 404.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1566.22 | 953.35 | 612.87 | 2171.67 | 1256.49 | 0.00 | 0.00 | 0.00 |
February | 1485.92 | 825.37 | 660.55 | 2243.83 | 990.34 | 0.00 | 0.00 | 0.00 |
March | 1262.60 | 553.67 | 708.93 | 2227.10 | 587.73 | 0.00 | 0.00 | 0.00 |
April | 900.16 | 259.60 | 640.56 | 2125.13 | 183.29 | 0.00 | 0.00 | 0.00 |
May | 648.92 | 54.66 | 594.26 | 2004.76 | 20.06 | 0.00 | 0.00 | 0.00 |
June | 586.93 | 10.21 | 576.72 | 1971.93 | 16.88 | 0.00 | 0.00 | 0.00 |
July | 609.63 | 5.97 | 603.66 | 1847.13 | 2.32 | 0.00 | 0.00 | 0.00 |
August | 642.79 | 28.17 | 614.62 | 1712.72 | 9.29 | 0.00 | 0.00 | 0.00 |
September | 889.46 | 244.90 | 644.56 | 1950.70 | 52.79 | 0.00 | 0.00 | 0.00 |
October | 1505.85 | 844.58 | 661.27 | 2823.21 | 447.12 | 0.00 | 0.00 | 0.00 |
November | 1878.85 | 1244.71 | 634.13 | 3076.59 | 901.21 | 0.00 | 0.00 | 0.00 |
December | 1671.36 | 1048.17 | 623.19 | 2411.45 | 1237.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1135.33 | 504.21 | 631.12 | 2212.87 | 473.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.93 | 5.97 | 576.72 | 1712.72 | 2.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1878.85 | 1244.71 | 708.93 | 3076.59 | 1256.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2034.60 | 1238.45 | 796.16 | 2912.14 | 1654.37 | 0.00 | 0.00 | 0.00 |
February | 1930.29 | 1072.20 | 858.09 | 3013.78 | 1292.97 | 0.00 | 0.00 | 0.00 |
March | 1640.18 | 719.24 | 920.94 | 2993.43 | 755.95 | 0.00 | 0.00 | 0.00 |
April | 1169.36 | 337.23 | 832.13 | 2873.25 | 232.32 | 0.00 | 0.00 | 0.00 |
May | 842.99 | 71.01 | 771.98 | 2718.62 | 24.83 | 0.00 | 0.00 | 0.00 |
June | 762.45 | 13.26 | 749.20 | 2666.45 | 21.34 | 0.00 | 0.00 | 0.00 |
July | 791.95 | 7.76 | 784.19 | 2492.49 | 3.05 | 0.00 | 0.00 | 0.00 |
August | 835.02 | 36.60 | 798.43 | 2308.93 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 1155.46 | 318.14 | 837.32 | 2619.19 | 62.56 | 0.00 | 0.00 | 0.00 |
October | 1956.19 | 1097.16 | 859.03 | 3771.06 | 568.51 | 0.00 | 0.00 | 0.00 |
November | 2440.73 | 1616.95 | 823.77 | 4108.44 | 1164.39 | 0.00 | 0.00 | 0.00 |
December | 2171.19 | 1361.63 | 809.56 | 3229.38 | 1625.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1474.86 | 655.00 | 819.86 | 2974.28 | 615.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 762.45 | 7.76 | 749.20 | 2308.93 | 3.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2440.73 | 1616.95 | 920.94 | 4108.44 | 1654.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.97 | 66.94 | 43.03 | 159.82 | 77.97 | 0.00 | 0.00 | 0.00 |
February | 104.33 | 57.95 | 46.38 | 165.48 | 58.15 | 0.00 | 0.00 | 0.00 |
March | 88.65 | 38.87 | 49.78 | 166.59 | 29.43 | 0.00 | 0.00 | 0.00 |
April | 63.20 | 18.23 | 44.98 | 167.45 | 5.99 | 0.00 | 0.00 | 0.00 |
May | 45.56 | 3.84 | 41.73 | 168.52 | 0.08 | 0.00 | 0.00 | 0.00 |
June | 41.21 | 0.72 | 40.49 | 166.14 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 42.80 | 0.42 | 42.39 | 158.64 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 45.13 | 1.98 | 43.16 | 146.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62.45 | 17.20 | 45.26 | 160.06 | 0.44 | 0.00 | 0.00 | 0.00 |
October | 105.73 | 59.30 | 46.43 | 211.71 | 19.67 | 0.00 | 0.00 | 0.00 |
November | 131.92 | 87.40 | 44.53 | 227.26 | 50.28 | 0.00 | 0.00 | 0.00 |
December | 117.35 | 73.60 | 43.76 | 178.33 | 75.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.72 | 35.40 | 44.31 | 173.05 | 26.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.21 | 0.42 | 40.49 | 146.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.92 | 87.40 | 49.78 | 227.26 | 77.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.36 | 36.71 | 57.64 | 115.91 | 158.96 | 0.00 | 0.00 | 0.00 |
February | 108.17 | 39.96 | 68.20 | 157.48 | 115.46 | 0.00 | 0.00 | 0.00 |
March | 140.19 | 56.19 | 84.00 | 251.05 | 56.18 | 0.00 | 0.00 | 0.00 |
April | 169.83 | 79.53 | 90.30 | 387.35 | 11.19 | 0.00 | 0.00 | 0.00 |
May | 161.01 | 68.30 | 92.70 | 447.99 | 0.14 | 0.00 | 0.00 | 0.00 |
June | 151.47 | 58.99 | 92.48 | 448.34 | 0.50 | 0.00 | 0.00 | 0.00 |
July | 112.11 | 21.72 | 90.39 | 356.29 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 102.92 | 18.14 | 84.78 | 306.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113.65 | 33.61 | 80.04 | 285.44 | 0.82 | 0.00 | 0.00 | 0.00 |
October | 118.19 | 47.19 | 71.00 | 244.53 | 37.64 | 0.00 | 0.00 | 0.00 |
November | 106.79 | 45.58 | 61.21 | 179.59 | 98.93 | 0.00 | 0.00 | 0.00 |
December | 91.12 | 34.65 | 56.47 | 117.24 | 150.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.46 | 44.99 | 77.47 | 275.21 | 52.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.12 | 18.14 | 56.47 | 115.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 169.83 | 79.53 | 92.70 | 448.34 | 158.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.11 | 0.00 | 24.11 | 18.45 | 84.25 | 0.00 | 0.00 | 0.00 |
February | 28.59 | 0.00 | 28.59 | 33.28 | 62.38 | 0.00 | 0.00 | 0.00 |
March | 34.46 | 0.00 | 34.46 | 61.36 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 37.56 | 0.25 | 37.32 | 110.04 | 6.19 | 0.00 | 0.00 | 0.00 |
May | 41.50 | 1.22 | 40.28 | 158.22 | 0.08 | 0.00 | 0.00 | 0.00 |
June | 42.86 | 1.57 | 41.29 | 169.19 | 0.29 | 0.00 | 0.00 | 0.00 |
July | 42.40 | 0.77 | 41.63 | 158.07 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 38.91 | 0.18 | 38.74 | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34.60 | 0.00 | 34.59 | 105.08 | 0.43 | 0.00 | 0.00 | 0.00 |
October | 29.97 | 0.00 | 29.97 | 68.60 | 20.81 | 0.00 | 0.00 | 0.00 |
November | 25.38 | 0.00 | 25.38 | 37.86 | 53.76 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 0.00 | 23.52 | 20.61 | 80.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.68 | 0.33 | 33.35 | 89.85 | 28.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 18.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.86 | 1.57 | 41.63 | 169.19 | 84.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.36 | 36.71 | 57.64 | 121.73 | 154.90 | 0.00 | 0.00 | 0.00 |
February | 108.17 | 39.96 | 68.20 | 160.92 | 115.67 | 0.00 | 0.00 | 0.00 |
March | 140.19 | 56.19 | 84.00 | 252.24 | 58.71 | 0.00 | 0.00 | 0.00 |
April | 169.83 | 79.53 | 90.30 | 388.06 | 11.59 | 0.00 | 0.00 | 0.00 |
May | 161.01 | 68.30 | 92.70 | 448.40 | 0.14 | 0.00 | 0.00 | 0.00 |
June | 151.47 | 58.99 | 92.48 | 448.22 | 0.53 | 0.00 | 0.00 | 0.00 |
July | 112.11 | 21.72 | 90.39 | 356.32 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 102.92 | 18.14 | 84.78 | 306.81 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113.65 | 33.61 | 80.04 | 287.20 | 0.77 | 0.00 | 0.00 | 0.00 |
October | 118.19 | 47.19 | 71.00 | 246.33 | 38.70 | 0.00 | 0.00 | 0.00 |
November | 106.79 | 45.58 | 61.21 | 183.30 | 99.96 | 0.00 | 0.00 | 0.00 |
December | 91.12 | 34.65 | 56.47 | 123.17 | 147.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.46 | 44.99 | 77.47 | 277.30 | 52.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.12 | 18.14 | 56.47 | 121.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 169.83 | 79.53 | 92.70 | 448.40 | 154.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.96 | 53.54 | 34.42 | 110.97 | 93.38 | 0.00 | 0.00 | 0.00 |
February | 83.45 | 46.35 | 37.10 | 115.68 | 75.43 | 0.00 | 0.00 | 0.00 |
March | 70.91 | 31.09 | 39.81 | 116.05 | 47.00 | 0.00 | 0.00 | 0.00 |
April | 50.55 | 14.58 | 35.97 | 110.84 | 18.20 | 0.00 | 0.00 | 0.00 |
May | 36.44 | 3.07 | 33.37 | 102.42 | 4.25 | 0.00 | 0.00 | 0.00 |
June | 32.96 | 0.57 | 32.39 | 98.82 | 3.11 | 0.00 | 0.00 | 0.00 |
July | 34.24 | 0.34 | 33.90 | 90.15 | 1.31 | 0.00 | 0.00 | 0.00 |
August | 36.10 | 1.58 | 34.52 | 83.44 | 3.51 | 0.00 | 0.00 | 0.00 |
September | 49.95 | 13.75 | 36.20 | 99.57 | 10.58 | 0.00 | 0.00 | 0.00 |
October | 84.57 | 47.43 | 37.14 | 151.98 | 36.67 | 0.00 | 0.00 | 0.00 |
November | 105.52 | 69.90 | 35.61 | 165.66 | 66.27 | 0.00 | 0.00 | 0.00 |
December | 93.86 | 58.86 | 35.00 | 125.23 | 90.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.76 | 28.32 | 35.44 | 114.17 | 37.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.96 | 0.34 | 32.39 | 83.44 | 1.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 105.52 | 69.90 | 39.81 | 165.66 | 93.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.29 | 0.00 | 19.29 | 14.61 | 68.94 | 0.00 | 0.00 | 0.00 |
February | 22.88 | 0.00 | 22.88 | 27.75 | 49.58 | 0.00 | 0.00 | 0.00 |
March | 27.57 | 0.00 | 27.57 | 52.42 | 23.27 | 0.00 | 0.00 | 0.00 |
April | 30.05 | 0.20 | 29.86 | 95.29 | 3.74 | 0.00 | 0.00 | 0.00 |
May | 33.20 | 0.98 | 32.23 | 135.84 | 0.01 | 0.00 | 0.00 | 0.00 |
June | 34.29 | 1.26 | 33.04 | 144.20 | 0.08 | 0.00 | 0.00 | 0.00 |
July | 33.93 | 0.62 | 33.31 | 134.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31.14 | 0.14 | 30.99 | 114.25 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27.68 | 0.00 | 27.68 | 90.83 | 0.14 | 0.00 | 0.00 | 0.00 |
October | 23.98 | 0.00 | 23.98 | 58.89 | 14.46 | 0.00 | 0.00 | 0.00 |
November | 20.31 | 0.00 | 20.31 | 32.35 | 41.15 | 0.00 | 0.00 | 0.00 |
December | 18.82 | 0.00 | 18.82 | 16.66 | 64.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.95 | 0.27 | 26.68 | 76.68 | 22.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.82 | 0.00 | 18.82 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.29 | 1.26 | 33.31 | 144.20 | 68.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.32 | 38.60 | 57.72 | 106.20 | 146.75 | 0.00 | 0.00 | 0.00 |
February | 117.34 | 48.45 | 68.89 | 163.76 | 106.80 | 0.00 | 0.00 | 0.00 |
March | 143.20 | 59.20 | 84.00 | 253.78 | 52.36 | 0.00 | 0.00 | 0.00 |
April | 170.45 | 79.47 | 90.98 | 389.78 | 10.54 | 0.00 | 0.00 | 0.00 |
May | 167.48 | 74.33 | 93.16 | 459.39 | 0.11 | 0.00 | 0.00 | 0.00 |
June | 136.01 | 45.01 | 91.00 | 421.23 | 0.48 | 0.00 | 0.00 | 0.00 |
July | 114.15 | 23.86 | 90.29 | 359.18 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 103.17 | 17.95 | 85.22 | 306.11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110.04 | 30.57 | 79.47 | 279.21 | 0.75 | 0.00 | 0.00 | 0.00 |
October | 120.38 | 48.50 | 71.88 | 246.71 | 35.81 | 0.00 | 0.00 | 0.00 |
November | 106.61 | 45.58 | 61.03 | 171.72 | 92.39 | 0.00 | 0.00 | 0.00 |
December | 93.32 | 37.05 | 56.27 | 112.32 | 143.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.17 | 45.64 | 77.53 | 272.87 | 48.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.32 | 17.95 | 56.27 | 106.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.45 | 79.47 | 93.16 | 459.39 | 146.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.97 | 66.94 | 43.03 | 158.91 | 77.70 | 0.00 | 0.00 | 0.00 |
February | 104.33 | 57.95 | 46.38 | 164.42 | 57.98 | 0.00 | 0.00 | 0.00 |
March | 88.65 | 38.87 | 49.78 | 165.80 | 29.13 | 0.00 | 0.00 | 0.00 |
April | 63.20 | 18.23 | 44.98 | 167.13 | 5.84 | 0.00 | 0.00 | 0.00 |
May | 45.56 | 3.84 | 41.73 | 168.34 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 41.21 | 0.72 | 40.49 | 166.56 | 0.26 | 0.00 | 0.00 | 0.00 |
July | 42.80 | 0.42 | 42.39 | 158.55 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 45.13 | 1.98 | 43.16 | 146.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62.45 | 17.20 | 45.26 | 160.10 | 0.41 | 0.00 | 0.00 | 0.00 |
October | 105.73 | 59.30 | 46.43 | 211.29 | 19.43 | 0.00 | 0.00 | 0.00 |
November | 131.92 | 87.40 | 44.53 | 226.68 | 49.95 | 0.00 | 0.00 | 0.00 |
December | 117.35 | 73.60 | 43.76 | 177.61 | 75.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.72 | 35.40 | 44.31 | 172.66 | 26.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.21 | 0.42 | 40.49 | 146.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.92 | 87.40 | 49.78 | 226.68 | 77.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.11 | 0.00 | 24.11 | 17.81 | 83.69 | 0.00 | 0.00 | 0.00 |
February | 28.59 | 0.00 | 28.59 | 32.13 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 34.46 | 0.00 | 34.46 | 60.17 | 31.31 | 0.00 | 0.00 | 0.00 |
April | 37.56 | 0.25 | 37.32 | 109.47 | 6.05 | 0.00 | 0.00 | 0.00 |
May | 41.50 | 1.22 | 40.28 | 158.01 | 0.07 | 0.00 | 0.00 | 0.00 |
June | 42.86 | 1.57 | 41.29 | 169.61 | 0.27 | 0.00 | 0.00 | 0.00 |
July | 42.40 | 0.77 | 41.63 | 157.97 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 38.91 | 0.18 | 38.74 | 133.94 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34.60 | 0.00 | 34.59 | 105.10 | 0.40 | 0.00 | 0.00 | 0.00 |
October | 29.97 | 0.00 | 29.97 | 67.92 | 20.57 | 0.00 | 0.00 | 0.00 |
November | 25.38 | 0.00 | 25.38 | 36.89 | 53.29 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 0.00 | 23.52 | 19.89 | 79.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.68 | 0.33 | 33.35 | 89.37 | 28.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 17.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.86 | 1.57 | 41.63 | 169.61 | 83.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.32 | 38.60 | 57.72 | 112.39 | 142.16 | 0.00 | 0.00 | 0.00 |
February | 117.34 | 48.45 | 68.89 | 167.16 | 106.99 | 0.00 | 0.00 | 0.00 |
March | 143.20 | 59.20 | 84.00 | 253.58 | 54.56 | 0.00 | 0.00 | 0.00 |
April | 170.45 | 79.47 | 90.98 | 389.72 | 10.80 | 0.00 | 0.00 | 0.00 |
May | 167.48 | 74.33 | 93.16 | 459.78 | 0.11 | 0.00 | 0.00 | 0.00 |
June | 136.01 | 45.01 | 91.00 | 421.12 | 0.50 | 0.00 | 0.00 | 0.00 |
July | 114.15 | 23.86 | 90.29 | 359.22 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 103.17 | 17.95 | 85.22 | 306.58 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110.04 | 30.57 | 79.47 | 280.94 | 0.70 | 0.00 | 0.00 | 0.00 |
October | 120.38 | 48.50 | 71.88 | 247.58 | 36.60 | 0.00 | 0.00 | 0.00 |
November | 106.61 | 45.58 | 61.03 | 174.58 | 93.14 | 0.00 | 0.00 | 0.00 |
December | 93.32 | 37.05 | 56.27 | 118.04 | 139.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.17 | 45.64 | 77.53 | 274.64 | 48.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.32 | 17.95 | 56.27 | 112.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.45 | 79.47 | 93.16 | 459.78 | 142.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.54 | 0.00 | 30.54 | 22.81 | 111.65 | 0.00 | 0.00 | 0.00 |
February | 36.21 | 0.00 | 36.21 | 42.59 | 82.98 | 0.00 | 0.00 | 0.00 |
March | 43.64 | 0.00 | 43.64 | 76.96 | 45.87 | 0.00 | 0.00 | 0.00 |
April | 47.57 | 0.31 | 47.26 | 131.71 | 13.04 | 0.00 | 0.00 | 0.00 |
May | 52.55 | 1.54 | 51.01 | 186.57 | 0.93 | 0.00 | 0.00 | 0.00 |
June | 54.28 | 1.99 | 52.29 | 200.14 | 0.96 | 0.00 | 0.00 | 0.00 |
July | 53.70 | 0.97 | 52.73 | 183.58 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 49.28 | 0.22 | 49.06 | 153.02 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 43.81 | 0.01 | 43.81 | 119.00 | 2.30 | 0.00 | 0.00 | 0.00 |
October | 37.95 | 0.00 | 37.95 | 82.07 | 35.78 | 0.00 | 0.00 | 0.00 |
November | 32.15 | 0.00 | 32.15 | 45.79 | 76.71 | 0.00 | 0.00 | 0.00 |
December | 29.79 | 0.00 | 29.79 | 25.07 | 108.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.66 | 0.42 | 42.23 | 106.09 | 39.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.79 | 0.00 | 29.79 | 22.81 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.28 | 1.99 | 52.73 | 200.14 | 111.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.26 | 0.00 | 11.26 | 8.41 | 41.16 | 0.00 | 0.00 | 0.00 |
February | 13.35 | 0.00 | 13.35 | 15.70 | 30.59 | 0.00 | 0.00 | 0.00 |
March | 16.09 | 0.00 | 16.09 | 28.37 | 16.91 | 0.00 | 0.00 | 0.00 |
April | 17.54 | 0.12 | 17.42 | 48.56 | 4.81 | 0.00 | 0.00 | 0.00 |
May | 19.37 | 0.57 | 18.80 | 68.78 | 0.34 | 0.00 | 0.00 | 0.00 |
June | 20.01 | 0.73 | 19.28 | 73.78 | 0.35 | 0.00 | 0.00 | 0.00 |
July | 19.80 | 0.36 | 19.44 | 67.67 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 18.17 | 0.08 | 18.09 | 56.41 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 16.15 | 0.00 | 16.15 | 43.87 | 0.85 | 0.00 | 0.00 | 0.00 |
October | 13.99 | 0.00 | 13.99 | 30.25 | 13.19 | 0.00 | 0.00 | 0.00 |
November | 11.85 | 0.00 | 11.85 | 16.88 | 28.28 | 0.00 | 0.00 | 0.00 |
December | 10.98 | 0.00 | 10.98 | 9.24 | 39.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.72 | 0.16 | 15.57 | 39.11 | 14.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.98 | 0.00 | 10.98 | 8.41 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.01 | 0.73 | 19.44 | 73.78 | 41.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.31 | 31.23 | 20.08 | 75.86 | 37.08 | 0.00 | 0.00 | 0.00 |
February | 48.68 | 27.04 | 21.64 | 78.22 | 28.64 | 0.00 | 0.00 | 0.00 |
March | 41.36 | 18.14 | 23.23 | 77.55 | 16.50 | 0.00 | 0.00 | 0.00 |
April | 29.49 | 8.50 | 20.99 | 75.39 | 4.84 | 0.00 | 0.00 | 0.00 |
May | 21.26 | 1.79 | 19.47 | 73.64 | 0.35 | 0.00 | 0.00 | 0.00 |
June | 19.23 | 0.33 | 18.89 | 72.30 | 0.36 | 0.00 | 0.00 | 0.00 |
July | 19.97 | 0.20 | 19.78 | 67.92 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 21.06 | 0.92 | 20.14 | 62.44 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 29.14 | 8.02 | 21.12 | 69.82 | 0.83 | 0.00 | 0.00 | 0.00 |
October | 49.33 | 27.67 | 21.66 | 97.16 | 12.84 | 0.00 | 0.00 | 0.00 |
November | 61.55 | 40.78 | 20.78 | 105.87 | 26.70 | 0.00 | 0.00 | 0.00 |
December | 54.76 | 34.34 | 20.42 | 84.28 | 36.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.20 | 16.52 | 20.68 | 78.34 | 13.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.23 | 0.20 | 18.89 | 62.44 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.55 | 40.78 | 23.23 | 105.87 | 37.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.27 | 84.77 | 54.50 | 205.89 | 100.64 | 0.00 | 0.00 | 0.00 |
February | 132.13 | 73.39 | 58.74 | 212.29 | 77.73 | 0.00 | 0.00 | 0.00 |
March | 112.27 | 49.23 | 63.04 | 210.49 | 44.80 | 0.00 | 0.00 | 0.00 |
April | 80.04 | 23.08 | 56.96 | 204.64 | 13.15 | 0.00 | 0.00 | 0.00 |
May | 57.70 | 4.86 | 52.84 | 199.86 | 0.95 | 0.00 | 0.00 | 0.00 |
June | 52.19 | 0.91 | 51.28 | 196.24 | 0.97 | 0.00 | 0.00 | 0.00 |
July | 54.21 | 0.53 | 53.68 | 184.34 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 57.16 | 2.50 | 54.65 | 169.48 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 79.09 | 21.78 | 57.32 | 189.50 | 2.25 | 0.00 | 0.00 | 0.00 |
October | 133.90 | 75.10 | 58.80 | 263.72 | 34.84 | 0.00 | 0.00 | 0.00 |
November | 167.07 | 110.68 | 56.39 | 287.35 | 72.47 | 0.00 | 0.00 | 0.00 |
December | 148.62 | 93.20 | 55.42 | 228.76 | 99.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.96 | 44.84 | 56.12 | 212.64 | 37.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.19 | 0.53 | 51.28 | 169.48 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.07 | 110.68 | 63.04 | 287.35 | 100.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.97 | 66.94 | 43.03 | 158.20 | 76.36 | 0.00 | 0.00 | 0.00 |
February | 104.33 | 57.95 | 46.38 | 163.49 | 56.63 | 0.00 | 0.00 | 0.00 |
March | 88.65 | 38.87 | 49.78 | 164.67 | 27.91 | 0.00 | 0.00 | 0.00 |
April | 63.20 | 18.23 | 44.98 | 166.11 | 5.12 | 0.00 | 0.00 | 0.00 |
May | 45.56 | 3.84 | 41.73 | 168.50 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 41.21 | 0.72 | 40.49 | 165.67 | 0.23 | 0.00 | 0.00 | 0.00 |
July | 42.80 | 0.42 | 42.39 | 158.74 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 45.13 | 1.98 | 43.16 | 146.57 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62.45 | 17.20 | 45.26 | 159.42 | 0.29 | 0.00 | 0.00 | 0.00 |
October | 105.73 | 59.30 | 46.43 | 210.12 | 18.12 | 0.00 | 0.00 | 0.00 |
November | 131.92 | 87.40 | 44.53 | 225.69 | 48.42 | 0.00 | 0.00 | 0.00 |
December | 117.35 | 73.60 | 43.76 | 177.01 | 73.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.72 | 35.40 | 44.31 | 172.01 | 25.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.21 | 0.42 | 40.49 | 146.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.92 | 87.40 | 49.78 | 225.69 | 76.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.36 | 36.71 | 57.64 | 112.74 | 154.97 | 0.00 | 0.00 | 0.00 |
February | 108.17 | 39.96 | 68.20 | 154.07 | 112.00 | 0.00 | 0.00 | 0.00 |
March | 140.19 | 56.19 | 84.00 | 247.44 | 53.08 | 0.00 | 0.00 | 0.00 |
April | 169.83 | 79.53 | 90.30 | 384.55 | 9.53 | 0.00 | 0.00 | 0.00 |
May | 161.01 | 68.30 | 92.70 | 447.19 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 151.47 | 58.99 | 92.48 | 446.64 | 0.40 | 0.00 | 0.00 | 0.00 |
July | 112.11 | 21.72 | 90.39 | 355.69 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 102.92 | 18.14 | 84.78 | 305.75 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113.65 | 33.61 | 80.04 | 284.45 | 0.52 | 0.00 | 0.00 | 0.00 |
October | 118.19 | 47.19 | 71.00 | 242.09 | 34.56 | 0.00 | 0.00 | 0.00 |
November | 106.79 | 45.58 | 61.21 | 177.09 | 94.93 | 0.00 | 0.00 | 0.00 |
December | 91.12 | 34.65 | 56.47 | 114.76 | 146.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.46 | 44.99 | 77.47 | 273.13 | 50.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.12 | 18.14 | 56.47 | 112.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 169.83 | 79.53 | 92.70 | 447.19 | 154.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.11 | 0.00 | 24.11 | 17.95 | 82.91 | 0.00 | 0.00 | 0.00 |
February | 28.59 | 0.00 | 28.59 | 32.49 | 61.51 | 0.00 | 0.00 | 0.00 |
March | 34.46 | 0.00 | 34.46 | 60.59 | 30.28 | 0.00 | 0.00 | 0.00 |
April | 37.56 | 0.25 | 37.32 | 109.59 | 5.28 | 0.00 | 0.00 | 0.00 |
May | 41.50 | 1.22 | 40.28 | 158.33 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 42.86 | 1.57 | 41.29 | 168.67 | 0.23 | 0.00 | 0.00 | 0.00 |
July | 42.40 | 0.77 | 41.63 | 158.07 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 38.91 | 0.18 | 38.74 | 133.94 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34.60 | 0.00 | 34.59 | 105.03 | 0.27 | 0.00 | 0.00 | 0.00 |
October | 29.97 | 0.00 | 29.97 | 68.14 | 19.09 | 0.00 | 0.00 | 0.00 |
November | 25.38 | 0.00 | 25.38 | 37.62 | 51.97 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 0.00 | 23.52 | 20.45 | 78.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.68 | 0.33 | 33.35 | 89.53 | 27.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 17.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.86 | 1.57 | 41.63 | 168.67 | 82.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.36 | 36.71 | 57.64 | 119.43 | 151.87 | 0.00 | 0.00 | 0.00 |
February | 108.17 | 39.96 | 68.20 | 158.04 | 113.66 | 0.00 | 0.00 | 0.00 |
March | 140.19 | 56.19 | 84.00 | 249.40 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 169.83 | 79.53 | 90.30 | 385.60 | 9.81 | 0.00 | 0.00 | 0.00 |
May | 161.01 | 68.30 | 92.70 | 447.60 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 151.47 | 58.99 | 92.48 | 446.51 | 0.41 | 0.00 | 0.00 | 0.00 |
July | 112.11 | 21.72 | 90.39 | 355.72 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 102.92 | 18.14 | 84.78 | 306.24 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113.65 | 33.61 | 80.04 | 286.32 | 0.49 | 0.00 | 0.00 | 0.00 |
October | 118.19 | 47.19 | 71.00 | 244.74 | 35.44 | 0.00 | 0.00 | 0.00 |
November | 106.79 | 45.58 | 61.21 | 182.06 | 96.45 | 0.00 | 0.00 | 0.00 |
December | 91.12 | 34.65 | 56.47 | 121.87 | 143.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.46 | 44.99 | 77.47 | 275.71 | 50.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.12 | 18.14 | 56.47 | 119.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 169.83 | 79.53 | 92.70 | 447.60 | 151.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.28 | 98.17 | 63.11 | 226.01 | 116.61 | 0.00 | 0.00 | 0.00 |
February | 153.01 | 84.99 | 68.02 | 236.39 | 85.16 | 0.00 | 0.00 | 0.00 |
March | 130.02 | 57.01 | 73.00 | 241.78 | 40.48 | 0.00 | 0.00 | 0.00 |
April | 92.69 | 26.73 | 65.96 | 249.50 | 6.80 | 0.00 | 0.00 | 0.00 |
May | 66.82 | 5.63 | 61.19 | 256.27 | 0.01 | 0.00 | 0.00 | 0.00 |
June | 60.44 | 1.05 | 59.39 | 251.93 | 0.22 | 0.00 | 0.00 | 0.00 |
July | 62.78 | 0.61 | 62.16 | 239.49 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 66.19 | 2.90 | 63.29 | 220.37 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91.59 | 25.22 | 66.37 | 237.77 | 0.33 | 0.00 | 0.00 | 0.00 |
October | 155.07 | 86.97 | 68.09 | 308.00 | 26.37 | 0.00 | 0.00 | 0.00 |
November | 193.47 | 128.17 | 65.30 | 327.83 | 72.71 | 0.00 | 0.00 | 0.00 |
December | 172.11 | 107.94 | 64.17 | 254.02 | 112.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.91 | 51.92 | 64.99 | 254.12 | 38.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.44 | 0.61 | 59.39 | 220.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 193.47 | 128.17 | 73.00 | 327.83 | 116.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.78 | 0.00 | 168.78 | 87.15 | 739.70 | 0.00 | 0.00 | 0.00 |
February | 200.15 | 0.00 | 200.15 | 185.89 | 553.61 | 0.00 | 0.00 | 0.00 |
March | 241.22 | 0.01 | 241.22 | 376.55 | 301.16 | 0.00 | 0.00 | 0.00 |
April | 262.92 | 1.73 | 261.20 | 685.21 | 86.79 | 0.00 | 0.00 | 0.00 |
May | 290.46 | 8.53 | 281.93 | 977.55 | 8.70 | 0.00 | 0.00 | 0.00 |
June | 300.03 | 10.99 | 289.04 | 1046.21 | 9.12 | 0.00 | 0.00 | 0.00 |
July | 296.81 | 5.39 | 291.43 | 954.21 | 1.09 | 0.00 | 0.00 | 0.00 |
August | 272.39 | 1.23 | 271.16 | 789.98 | 4.10 | 0.00 | 0.00 | 0.00 |
September | 242.17 | 0.03 | 242.14 | 600.57 | 23.89 | 0.00 | 0.00 | 0.00 |
October | 209.76 | 0.00 | 209.76 | 427.09 | 216.25 | 0.00 | 0.00 | 0.00 |
November | 177.67 | 0.00 | 177.67 | 224.68 | 464.83 | 0.00 | 0.00 | 0.00 |
December | 164.65 | 0.00 | 164.65 | 102.34 | 699.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.77 | 2.34 | 233.43 | 539.91 | 257.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.65 | 0.00 | 164.65 | 87.15 | 1.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.03 | 10.99 | 291.43 | 1046.21 | 739.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.78 | 0.00 | 168.78 | 76.48 | 765.57 | 0.00 | 0.00 | 0.00 |
February | 200.15 | 0.00 | 200.15 | 173.73 | 572.36 | 0.00 | 0.00 | 0.00 |
March | 241.22 | 0.01 | 241.22 | 366.02 | 311.68 | 0.00 | 0.00 | 0.00 |
April | 262.92 | 1.73 | 261.20 | 674.90 | 91.27 | 0.00 | 0.00 | 0.00 |
May | 290.46 | 8.53 | 281.93 | 964.83 | 9.70 | 0.00 | 0.00 | 0.00 |
June | 300.03 | 10.99 | 289.04 | 1033.37 | 9.99 | 0.00 | 0.00 | 0.00 |
July | 296.81 | 5.39 | 291.43 | 940.66 | 1.24 | 0.00 | 0.00 | 0.00 |
August | 272.39 | 1.23 | 271.16 | 777.36 | 5.06 | 0.00 | 0.00 | 0.00 |
September | 242.17 | 0.03 | 242.14 | 589.50 | 27.67 | 0.00 | 0.00 | 0.00 |
October | 209.76 | 0.00 | 209.76 | 419.04 | 224.05 | 0.00 | 0.00 | 0.00 |
November | 177.67 | 0.00 | 177.67 | 215.01 | 478.24 | 0.00 | 0.00 | 0.00 |
December | 164.65 | 0.00 | 164.65 | 91.62 | 722.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.77 | 2.34 | 233.43 | 528.67 | 267.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.65 | 0.00 | 164.65 | 76.48 | 1.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.03 | 10.99 | 291.43 | 1033.37 | 765.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.11 | 0.00 | 24.11 | 13.51 | 103.03 | 0.00 | 0.00 | 0.00 |
February | 28.59 | 0.00 | 28.59 | 29.78 | 78.54 | 0.00 | 0.00 | 0.00 |
March | 34.46 | 0.00 | 34.46 | 61.36 | 44.51 | 0.00 | 0.00 | 0.00 |
April | 37.56 | 0.25 | 37.32 | 108.03 | 14.96 | 0.00 | 0.00 | 0.00 |
May | 41.50 | 1.22 | 40.28 | 147.49 | 2.81 | 0.00 | 0.00 | 0.00 |
June | 42.86 | 1.57 | 41.29 | 158.69 | 2.69 | 0.00 | 0.00 | 0.00 |
July | 42.40 | 0.77 | 41.63 | 144.62 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 38.91 | 0.18 | 38.74 | 124.00 | 1.58 | 0.00 | 0.00 | 0.00 |
September | 34.60 | 0.00 | 34.59 | 96.93 | 6.70 | 0.00 | 0.00 | 0.00 |
October | 29.97 | 0.00 | 29.97 | 72.52 | 31.48 | 0.00 | 0.00 | 0.00 |
November | 25.38 | 0.00 | 25.38 | 39.06 | 64.21 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 0.00 | 23.52 | 17.31 | 97.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.68 | 0.33 | 33.35 | 84.71 | 37.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 13.51 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.86 | 1.57 | 41.63 | 158.69 | 103.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.63 | 77.20 | 115.43 | 204.48 | 353.82 | 0.00 | 0.00 | 0.00 |
February | 234.67 | 96.89 | 137.78 | 323.88 | 274.60 | 0.00 | 0.00 | 0.00 |
March | 286.39 | 118.40 | 167.99 | 512.14 | 159.78 | 0.00 | 0.00 | 0.00 |
April | 340.88 | 158.93 | 181.95 | 772.20 | 55.40 | 0.00 | 0.00 | 0.00 |
May | 334.94 | 148.64 | 186.30 | 878.34 | 10.43 | 0.00 | 0.00 | 0.00 |
June | 272.00 | 90.01 | 181.99 | 798.86 | 10.31 | 0.00 | 0.00 | 0.00 |
July | 228.29 | 47.72 | 180.57 | 665.82 | 2.21 | 0.00 | 0.00 | 0.00 |
August | 206.34 | 35.90 | 170.43 | 574.30 | 5.94 | 0.00 | 0.00 | 0.00 |
September | 220.06 | 61.13 | 158.93 | 528.89 | 25.11 | 0.00 | 0.00 | 0.00 |
October | 240.75 | 97.00 | 143.75 | 510.60 | 115.53 | 0.00 | 0.00 | 0.00 |
November | 213.21 | 91.16 | 122.06 | 356.85 | 228.53 | 0.00 | 0.00 | 0.00 |
December | 186.62 | 74.10 | 112.52 | 223.58 | 342.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.33 | 91.28 | 155.05 | 529.92 | 131.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.62 | 35.90 | 112.52 | 204.48 | 2.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.88 | 158.93 | 186.30 | 878.34 | 353.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.97 | 66.94 | 43.03 | 158.12 | 93.31 | 0.00 | 0.00 | 0.00 |
February | 104.33 | 57.95 | 46.38 | 164.21 | 73.91 | 0.00 | 0.00 | 0.00 |
March | 88.65 | 38.87 | 49.78 | 167.51 | 43.79 | 0.00 | 0.00 | 0.00 |
April | 63.20 | 18.23 | 44.98 | 165.80 | 15.02 | 0.00 | 0.00 | 0.00 |
May | 45.56 | 3.84 | 41.73 | 158.22 | 2.84 | 0.00 | 0.00 | 0.00 |
June | 41.21 | 0.72 | 40.49 | 155.43 | 2.76 | 0.00 | 0.00 | 0.00 |
July | 42.80 | 0.42 | 42.39 | 144.99 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 45.13 | 1.98 | 43.16 | 137.16 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 62.45 | 17.20 | 45.26 | 152.61 | 6.69 | 0.00 | 0.00 | 0.00 |
October | 105.73 | 59.30 | 46.43 | 216.15 | 31.01 | 0.00 | 0.00 | 0.00 |
November | 131.92 | 87.40 | 44.53 | 230.87 | 61.38 | 0.00 | 0.00 | 0.00 |
December | 117.35 | 73.60 | 43.76 | 178.72 | 89.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.72 | 35.40 | 44.31 | 169.11 | 35.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.21 | 0.42 | 40.49 | 137.16 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.92 | 87.40 | 49.78 | 230.87 | 93.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.54 | 0.00 | 30.54 | 20.46 | 112.55 | 0.00 | 0.00 | 0.00 |
February | 36.21 | 0.00 | 36.21 | 39.96 | 83.24 | 0.00 | 0.00 | 0.00 |
March | 43.64 | 0.00 | 43.64 | 73.18 | 46.69 | 0.00 | 0.00 | 0.00 |
April | 47.57 | 0.31 | 47.26 | 126.45 | 13.65 | 0.00 | 0.00 | 0.00 |
May | 52.55 | 1.54 | 51.01 | 179.61 | 1.16 | 0.00 | 0.00 | 0.00 |
June | 54.28 | 1.99 | 52.29 | 192.31 | 1.09 | 0.00 | 0.00 | 0.00 |
July | 53.70 | 0.97 | 52.73 | 175.90 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 49.28 | 0.22 | 49.06 | 145.72 | 0.45 | 0.00 | 0.00 | 0.00 |
September | 43.81 | 0.01 | 43.81 | 112.82 | 2.82 | 0.00 | 0.00 | 0.00 |
October | 37.95 | 0.00 | 37.95 | 79.06 | 36.08 | 0.00 | 0.00 | 0.00 |
November | 32.15 | 0.00 | 32.15 | 44.24 | 74.70 | 0.00 | 0.00 | 0.00 |
December | 29.79 | 0.00 | 29.79 | 23.57 | 107.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.66 | 0.42 | 42.23 | 101.41 | 39.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.79 | 0.00 | 29.79 | 20.46 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.28 | 1.99 | 52.73 | 192.31 | 112.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.32 | 0.00 | 27.32 | 18.31 | 100.69 | 0.00 | 0.00 | 0.00 |
February | 32.40 | 0.00 | 32.40 | 35.75 | 74.47 | 0.00 | 0.00 | 0.00 |
March | 39.05 | 0.00 | 39.05 | 65.47 | 41.77 | 0.00 | 0.00 | 0.00 |
April | 42.56 | 0.28 | 42.28 | 113.14 | 12.21 | 0.00 | 0.00 | 0.00 |
May | 47.02 | 1.38 | 45.64 | 160.69 | 1.03 | 0.00 | 0.00 | 0.00 |
June | 48.57 | 1.78 | 46.79 | 172.06 | 0.97 | 0.00 | 0.00 | 0.00 |
July | 48.05 | 0.87 | 47.18 | 157.38 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 44.09 | 0.20 | 43.89 | 130.37 | 0.40 | 0.00 | 0.00 | 0.00 |
September | 39.20 | 0.00 | 39.20 | 100.94 | 2.52 | 0.00 | 0.00 | 0.00 |
October | 33.96 | 0.00 | 33.96 | 70.73 | 32.28 | 0.00 | 0.00 | 0.00 |
November | 28.76 | 0.00 | 28.76 | 39.58 | 66.84 | 0.00 | 0.00 | 0.00 |
December | 26.65 | 0.00 | 26.65 | 21.09 | 95.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.16 | 0.38 | 37.79 | 90.73 | 35.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.65 | 0.00 | 26.65 | 18.31 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.57 | 1.78 | 47.18 | 172.06 | 100.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 410.55 | 249.90 | 160.65 | 595.83 | 299.06 | 0.00 | 0.00 | 0.00 |
February | 389.50 | 216.35 | 173.15 | 614.36 | 230.53 | 0.00 | 0.00 | 0.00 |
March | 330.96 | 145.13 | 185.83 | 606.70 | 135.11 | 0.00 | 0.00 | 0.00 |
April | 235.96 | 68.05 | 167.91 | 585.40 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 170.10 | 14.33 | 155.77 | 568.21 | 3.46 | 0.00 | 0.00 | 0.00 |
June | 153.85 | 2.68 | 151.18 | 555.50 | 3.29 | 0.00 | 0.00 | 0.00 |
July | 159.80 | 1.56 | 158.24 | 520.99 | 0.35 | 0.00 | 0.00 | 0.00 |
August | 168.50 | 7.38 | 161.11 | 477.58 | 1.32 | 0.00 | 0.00 | 0.00 |
September | 233.15 | 64.20 | 168.96 | 538.44 | 8.17 | 0.00 | 0.00 | 0.00 |
October | 394.73 | 221.39 | 173.34 | 766.46 | 103.98 | 0.00 | 0.00 | 0.00 |
November | 492.50 | 326.28 | 166.23 | 840.87 | 209.02 | 0.00 | 0.00 | 0.00 |
December | 438.11 | 274.76 | 163.36 | 667.42 | 289.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 297.60 | 132.17 | 165.44 | 611.25 | 109.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.85 | 1.56 | 151.18 | 477.58 | 0.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 492.50 | 326.28 | 185.83 | 840.87 | 299.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148972E+10 | 0.906782E+09 | 0.582938E+09 | 0.212418E+10 | 0.108468E+10 |
February | 0.127657E+10 | 0.709082E+09 | 0.567484E+09 | 0.197448E+10 | 0.769388E+09 |
March | 0.120093E+10 | 0.526624E+09 | 0.674306E+09 | 0.214911E+10 | 0.522660E+09 |
April | 0.828574E+09 | 0.238951E+09 | 0.589623E+09 | 0.195436E+10 | 0.172181E+09 |
May | 0.617227E+09 | 51992611.18 | 0.565234E+09 | 0.188615E+10 | 22463770.85 |
June | 0.540254E+09 | 9394508.28 | 0.530860E+09 | 0.179531E+10 | 13447299.23 |
July | 0.579858E+09 | 5678298.02 | 0.574179E+09 | 0.174180E+10 | 1884024.05 |
August | 0.611396E+09 | 26794816.56 | 0.584601E+09 | 0.161867E+10 | 8548579.37 |
September | 0.818726E+09 | 0.225424E+09 | 0.593302E+09 | 0.180575E+10 | 48311117.09 |
October | 0.143230E+10 | 0.803332E+09 | 0.628973E+09 | 0.270374E+10 | 0.415654E+09 |
November | 0.172943E+10 | 0.114573E+10 | 0.583703E+09 | 0.286911E+10 | 0.777713E+09 |
December | 0.158973E+10 | 0.996975E+09 | 0.592752E+09 | 0.235500E+10 | 0.106635E+10 |
Annual Sum or Average | 0.127147E+11 | 0.564676E+10 | 0.706796E+10 | 0.249777E+11 | 0.490328E+10 |
Minimum of Months | 0.540254E+09 | 5678298.02 | 0.530860E+09 | 0.161867E+10 | 1884024.05 |
Maximum of Months | 0.172943E+10 | 0.114573E+10 | 0.674306E+09 | 0.286911E+10 | 0.108468E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419496E+10 | 0.255344E+10 | 0.164152E+10 | 0.581659E+10 | 0.336539E+10 |
February | 0.359473E+10 | 0.199673E+10 | 0.159800E+10 | 0.542827E+10 | 0.239582E+10 |
March | 0.338174E+10 | 0.148294E+10 | 0.189880E+10 | 0.596507E+10 | 0.157416E+10 |
April | 0.233321E+10 | 0.672871E+09 | 0.166034E+10 | 0.550833E+10 | 0.475082E+09 |
May | 0.173807E+10 | 0.146408E+09 | 0.159166E+10 | 0.536954E+10 | 53732172.55 |
June | 0.152132E+10 | 26454315.90 | 0.149487E+10 | 0.511123E+10 | 43749081.18 |
July | 0.163284E+10 | 15989712.82 | 0.161685E+10 | 0.494735E+10 | 6225053.25 |
August | 0.172165E+10 | 75452436.75 | 0.164620E+10 | 0.458735E+10 | 24870132.11 |
September | 0.230548E+10 | 0.634779E+09 | 0.167070E+10 | 0.505622E+10 | 0.136831E+09 |
October | 0.403328E+10 | 0.226213E+10 | 0.177115E+10 | 0.756169E+10 | 0.119757E+10 |
November | 0.486997E+10 | 0.322630E+10 | 0.164367E+10 | 0.797453E+10 | 0.233594E+10 |
December | 0.447657E+10 | 0.280742E+10 | 0.166915E+10 | 0.645884E+10 | 0.331409E+10 |
Annual Sum or Average | 0.358038E+11 | 0.159009E+11 | 0.199029E+11 | 0.697850E+11 | 0.149235E+11 |
Minimum of Months | 0.152132E+10 | 15989712.82 | 0.149487E+10 | 0.458735E+10 | 6225053.25 |
Maximum of Months | 0.486997E+10 | 0.322630E+10 | 0.189880E+10 | 0.797453E+10 | 0.336539E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544949E+10 | 0.331706E+10 | 0.213242E+10 | 0.779987E+10 | 0.443106E+10 |
February | 0.466975E+10 | 0.259386E+10 | 0.207589E+10 | 0.729093E+10 | 0.312795E+10 |
March | 0.439307E+10 | 0.192642E+10 | 0.246665E+10 | 0.801759E+10 | 0.202474E+10 |
April | 0.303097E+10 | 0.874097E+09 | 0.215688E+10 | 0.744745E+10 | 0.602175E+09 |
May | 0.225785E+10 | 0.190192E+09 | 0.206766E+10 | 0.728156E+10 | 66505312.74 |
June | 0.197628E+10 | 34365661.88 | 0.194192E+10 | 0.691145E+10 | 55304816.84 |
July | 0.212115E+10 | 20771546.94 | 0.210038E+10 | 0.667589E+10 | 8174171.48 |
August | 0.223652E+10 | 98017009.38 | 0.213850E+10 | 0.618425E+10 | 30228318.28 |
September | 0.299495E+10 | 0.824615E+09 | 0.217033E+10 | 0.678894E+10 | 0.162168E+09 |
October | 0.523946E+10 | 0.293864E+10 | 0.230082E+10 | 0.101004E+11 | 0.152269E+10 |
November | 0.632636E+10 | 0.419114E+10 | 0.213522E+10 | 0.106491E+11 | 0.301810E+10 |
December | 0.581531E+10 | 0.364699E+10 | 0.216832E+10 | 0.864958E+10 | 0.435441E+10 |
Annual Sum or Average | 0.465112E+11 | 0.206562E+11 | 0.258550E+11 | 0.937970E+11 | 0.194035E+11 |
Minimum of Months | 0.197628E+10 | 20771546.94 | 0.194192E+10 | 0.618425E+10 | 8174171.48 |
Maximum of Months | 0.632636E+10 | 0.419114E+10 | 0.246665E+10 | 0.106491E+11 | 0.443106E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294544E+09 | 0.179286E+09 | 0.115258E+09 | 0.428064E+09 | 0.208841E+09 |
February | 0.252400E+09 | 0.140198E+09 | 0.112202E+09 | 0.400332E+09 | 0.140668E+09 |
March | 0.237446E+09 | 0.104123E+09 | 0.133323E+09 | 0.446191E+09 | 78835966.70 |
April | 0.163825E+09 | 47244750.35 | 0.116580E+09 | 0.434028E+09 | 15531663.75 |
May | 0.122038E+09 | 10279832.20 | 0.111758E+09 | 0.451366E+09 | 204464.48 |
June | 0.106819E+09 | 1857455.64 | 0.104962E+09 | 0.430636E+09 | 731972.12 |
July | 0.114649E+09 | 1122697.04 | 0.113526E+09 | 0.424896E+09 | 40956.23 |
August | 0.120884E+09 | 5297795.43 | 0.115587E+09 | 0.393133E+09 | 0.00 |
September | 0.161877E+09 | 44570222.41 | 0.117307E+09 | 0.414872E+09 | 1137457.95 |
October | 0.283192E+09 | 0.158833E+09 | 0.124360E+09 | 0.567057E+09 | 52684450.66 |
November | 0.341939E+09 | 0.226530E+09 | 0.115409E+09 | 0.589053E+09 | 0.130332E+09 |
December | 0.314317E+09 | 0.197119E+09 | 0.117198E+09 | 0.477631E+09 | 0.202372E+09 |
Annual Sum or Average | 0.251393E+10 | 0.111646E+10 | 0.139747E+10 | 0.545726E+10 | 0.831380E+09 |
Minimum of Months | 0.106819E+09 | 1122697.04 | 0.104962E+09 | 0.393133E+09 | 0.00 |
Maximum of Months | 0.341939E+09 | 0.226530E+09 | 0.133323E+09 | 0.589053E+09 | 0.208841E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252722E+09 | 98336017.03 | 0.154386E+09 | 0.310458E+09 | 0.425771E+09 |
February | 0.261680E+09 | 96678795.88 | 0.165002E+09 | 0.380969E+09 | 0.279309E+09 |
March | 0.375492E+09 | 0.150496E+09 | 0.224996E+09 | 0.672424E+09 | 0.150471E+09 |
April | 0.440209E+09 | 0.206149E+09 | 0.234060E+09 | 0.100401E+10 | 29003434.90 |
May | 0.431236E+09 | 0.182936E+09 | 0.248301E+09 | 0.119991E+10 | 375308.24 |
June | 0.392623E+09 | 0.152910E+09 | 0.239713E+09 | 0.116209E+10 | 1301408.93 |
July | 0.300278E+09 | 58187984.70 | 0.242090E+09 | 0.954287E+09 | 69785.15 |
August | 0.275648E+09 | 48573712.67 | 0.227074E+09 | 0.820477E+09 | 0.00 |
September | 0.294576E+09 | 87110970.87 | 0.207465E+09 | 0.739869E+09 | 2123417.31 |
October | 0.316556E+09 | 0.126392E+09 | 0.190164E+09 | 0.654959E+09 | 0.100826E+09 |
November | 0.276801E+09 | 0.118147E+09 | 0.158654E+09 | 0.465507E+09 | 0.256415E+09 |
December | 0.244062E+09 | 92808591.25 | 0.151254E+09 | 0.314021E+09 | 0.404069E+09 |
Annual Sum or Average | 0.386189E+10 | 0.141873E+10 | 0.244316E+10 | 0.867898E+10 | 0.164973E+10 |
Minimum of Months | 0.244062E+09 | 48573712.67 | 0.151254E+09 | 0.310458E+09 | 0.00 |
Maximum of Months | 0.440209E+09 | 0.206149E+09 | 0.248301E+09 | 0.119991E+10 | 0.425771E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64583759.30 | 0.00 | 64583759.30 | 49407134.08 | 0.225655E+09 |
February | 69173908.08 | 0.00 | 69173908.08 | 80513427.21 | 0.150908E+09 |
March | 92302947.57 | 3154.00 | 92299793.57 | 0.164359E+09 | 84626831.54 |
April | 97360928.36 | 639960.68 | 96720967.68 | 0.285223E+09 | 16039265.05 |
May | 0.111143E+09 | 3264604.17 | 0.107878E+09 | 0.423774E+09 | 218690.56 |
June | 0.111100E+09 | 4069212.55 | 0.107031E+09 | 0.438533E+09 | 746231.34 |
July | 0.113574E+09 | 2060818.43 | 0.111513E+09 | 0.423368E+09 | 40942.66 |
August | 0.104228E+09 | 472450.58 | 0.103756E+09 | 0.358911E+09 | 0.00 |
September | 89674035.71 | 10474.88 | 89663560.83 | 0.272365E+09 | 1113589.56 |
October | 80264144.39 | 0.00 | 80264144.39 | 0.183742E+09 | 55745763.13 |
November | 65791475.18 | 0.00 | 65791475.18 | 98130640.36 | 0.139356E+09 |
December | 63002611.84 | 0.00 | 63002611.84 | 55200592.27 | 0.215473E+09 |
Annual Sum or Average | 0.106220E+10 | 10520675.29 | 0.105168E+10 | 0.283353E+10 | 0.889922E+09 |
Minimum of Months | 63002611.84 | 0.00 | 63002611.84 | 49407134.08 | 0.00 |
Maximum of Months | 0.113574E+09 | 4069212.55 | 0.111513E+09 | 0.438533E+09 | 0.225655E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252722E+09 | 98336017.03 | 0.154386E+09 | 0.326048E+09 | 0.414886E+09 |
February | 0.261680E+09 | 96678795.88 | 0.165002E+09 | 0.389286E+09 | 0.279828E+09 |
March | 0.375492E+09 | 0.150496E+09 | 0.224996E+09 | 0.675603E+09 | 0.157255E+09 |
April | 0.440209E+09 | 0.206149E+09 | 0.234060E+09 | 0.100586E+10 | 30033809.66 |
May | 0.431236E+09 | 0.182936E+09 | 0.248301E+09 | 0.120100E+10 | 381900.69 |
June | 0.392623E+09 | 0.152910E+09 | 0.239713E+09 | 0.116179E+10 | 1368428.43 |
July | 0.300278E+09 | 58187984.70 | 0.242090E+09 | 0.954379E+09 | 69760.73 |
August | 0.275648E+09 | 48573712.67 | 0.227074E+09 | 0.821749E+09 | 0.00 |
September | 0.294576E+09 | 87110970.87 | 0.207465E+09 | 0.744422E+09 | 2008785.94 |
October | 0.316556E+09 | 0.126392E+09 | 0.190164E+09 | 0.659761E+09 | 0.103641E+09 |
November | 0.276801E+09 | 0.118147E+09 | 0.158654E+09 | 0.475104E+09 | 0.259096E+09 |
December | 0.244062E+09 | 92808591.25 | 0.151254E+09 | 0.329890E+09 | 0.394390E+09 |
Annual Sum or Average | 0.386189E+10 | 0.141873E+10 | 0.244316E+10 | 0.874489E+10 | 0.164296E+10 |
Minimum of Months | 0.244062E+09 | 48573712.67 | 0.151254E+09 | 0.326048E+09 | 0.00 |
Maximum of Months | 0.440209E+09 | 0.206149E+09 | 0.248301E+09 | 0.120100E+10 | 0.414886E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235588E+09 | 0.143401E+09 | 92187752.51 | 0.297225E+09 | 0.250097E+09 |
February | 0.201880E+09 | 0.112136E+09 | 89743903.77 | 0.279855E+09 | 0.182470E+09 |
March | 0.189919E+09 | 83281513.00 | 0.106637E+09 | 0.310829E+09 | 0.125879E+09 |
April | 0.131034E+09 | 37788285.21 | 93245487.88 | 0.287299E+09 | 47177735.33 |
May | 97610893.83 | 8222230.58 | 89388663.25 | 0.274331E+09 | 11372141.85 |
June | 85438186.34 | 1485669.05 | 83952517.29 | 0.256139E+09 | 8067285.56 |
July | 91700827.48 | 897979.05 | 90802848.43 | 0.241455E+09 | 3504138.15 |
August | 96688257.17 | 4237393.64 | 92450863.53 | 0.223477E+09 | 9404617.35 |
September | 0.129476E+09 | 35649088.28 | 93826807.71 | 0.258088E+09 | 27412980.44 |
October | 0.226509E+09 | 0.127041E+09 | 99468018.09 | 0.407062E+09 | 98220038.66 |
November | 0.273497E+09 | 0.181188E+09 | 92308884.53 | 0.429386E+09 | 0.171764E+09 |
December | 0.251404E+09 | 0.157664E+09 | 93739704.82 | 0.335423E+09 | 0.242727E+09 |
Annual Sum or Average | 0.201074E+10 | 0.892992E+09 | 0.111775E+10 | 0.360057E+10 | 0.117810E+10 |
Minimum of Months | 85438186.34 | 897979.05 | 83952517.29 | 0.223477E+09 | 3504138.15 |
Maximum of Months | 0.273497E+09 | 0.181188E+09 | 0.106637E+09 | 0.429386E+09 | 0.250097E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51673856.20 | 0.00 | 51673856.20 | 39125764.28 | 0.184652E+09 |
February | 55346461.98 | 0.00 | 55346461.98 | 67129299.72 | 0.119946E+09 |
March | 73852146.28 | 2523.53 | 73849622.74 | 0.140392E+09 | 62318490.13 |
April | 77899067.29 | 512036.41 | 77387030.88 | 0.246994E+09 | 9700296.26 |
May | 88925968.83 | 2612029.53 | 86313939.30 | 0.363829E+09 | 13753.34 |
June | 88891777.18 | 3255801.56 | 85635975.62 | 0.373770E+09 | 219934.21 |
July | 90871340.81 | 1648873.28 | 89222467.53 | 0.359374E+09 | 10391.78 |
August | 83393733.81 | 378010.56 | 83015723.25 | 0.306004E+09 | 0.00 |
September | 71748738.01 | 8381.02 | 71740357.00 | 0.235440E+09 | 356687.78 |
October | 64219827.08 | 0.00 | 64219827.08 | 0.157735E+09 | 38726058.31 |
November | 52640156.97 | 0.00 | 52640156.97 | 83853508.10 | 0.106657E+09 |
December | 50408770.56 | 0.00 | 50408770.56 | 44620116.43 | 0.174075E+09 |
Annual Sum or Average | 0.849872E+09 | 8417655.89 | 0.841454E+09 | 0.241827E+10 | 0.696676E+09 |
Minimum of Months | 50408770.56 | 0.00 | 50408770.56 | 39125764.28 | 0.00 |
Maximum of Months | 90871340.81 | 3255801.56 | 89222467.53 | 0.373770E+09 | 0.184652E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257989E+09 | 0.103397E+09 | 0.154592E+09 | 0.284436E+09 | 0.393048E+09 |
February | 0.283875E+09 | 0.117206E+09 | 0.166670E+09 | 0.396158E+09 | 0.258362E+09 |
March | 0.383559E+09 | 0.158573E+09 | 0.224986E+09 | 0.679737E+09 | 0.140248E+09 |
April | 0.441812E+09 | 0.205992E+09 | 0.235819E+09 | 0.101030E+10 | 27315100.44 |
May | 0.448586E+09 | 0.199072E+09 | 0.249514E+09 | 0.123044E+10 | 288733.55 |
June | 0.352537E+09 | 0.116661E+09 | 0.235876E+09 | 0.109183E+10 | 1234925.69 |
July | 0.305751E+09 | 63914231.92 | 0.241837E+09 | 0.962029E+09 | 75221.55 |
August | 0.276344E+09 | 48081891.75 | 0.228262E+09 | 0.819879E+09 | 0.00 |
September | 0.285218E+09 | 79234770.85 | 0.205983E+09 | 0.723703E+09 | 1955289.10 |
October | 0.322437E+09 | 0.129912E+09 | 0.192525E+09 | 0.660797E+09 | 95909298.03 |
November | 0.276343E+09 | 0.118148E+09 | 0.158195E+09 | 0.445106E+09 | 0.239479E+09 |
December | 0.249944E+09 | 99241778.46 | 0.150703E+09 | 0.300839E+09 | 0.384162E+09 |
Annual Sum or Average | 0.388440E+10 | 0.143943E+10 | 0.244496E+10 | 0.860526E+10 | 0.154208E+10 |
Minimum of Months | 0.249944E+09 | 48081891.75 | 0.150703E+09 | 0.284436E+09 | 0.00 |
Maximum of Months | 0.448586E+09 | 0.205992E+09 | 0.249514E+09 | 0.123044E+10 | 0.393048E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294544E+09 | 0.179286E+09 | 0.115258E+09 | 0.425629E+09 | 0.208104E+09 |
February | 0.252400E+09 | 0.140198E+09 | 0.112202E+09 | 0.397772E+09 | 0.140264E+09 |
March | 0.237446E+09 | 0.104123E+09 | 0.133323E+09 | 0.444087E+09 | 78034745.31 |
April | 0.163825E+09 | 47244750.35 | 0.116580E+09 | 0.433205E+09 | 15132657.63 |
May | 0.122038E+09 | 10279832.20 | 0.111758E+09 | 0.450879E+09 | 168876.48 |
June | 0.106819E+09 | 1857455.64 | 0.104962E+09 | 0.431734E+09 | 670658.49 |
July | 0.114649E+09 | 1122697.04 | 0.113526E+09 | 0.424656E+09 | 40405.05 |
August | 0.120884E+09 | 5297795.43 | 0.115587E+09 | 0.392995E+09 | 0.00 |
September | 0.161877E+09 | 44570222.41 | 0.117307E+09 | 0.414988E+09 | 1063139.29 |
October | 0.283192E+09 | 0.158833E+09 | 0.124360E+09 | 0.565929E+09 | 52048869.36 |
November | 0.341939E+09 | 0.226530E+09 | 0.115409E+09 | 0.587563E+09 | 0.129481E+09 |
December | 0.314317E+09 | 0.197119E+09 | 0.117198E+09 | 0.475703E+09 | 0.201542E+09 |
Annual Sum or Average | 0.251393E+10 | 0.111646E+10 | 0.139747E+10 | 0.544514E+10 | 0.826550E+09 |
Minimum of Months | 0.106819E+09 | 1122697.04 | 0.104962E+09 | 0.392995E+09 | 0.00 |
Maximum of Months | 0.341939E+09 | 0.226530E+09 | 0.133323E+09 | 0.587563E+09 | 0.208104E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64583759.30 | 0.00 | 64583759.30 | 47695598.50 | 0.224151E+09 |
February | 69173908.08 | 0.00 | 69173908.08 | 77723693.43 | 0.150401E+09 |
March | 92302947.57 | 3154.00 | 92299793.57 | 0.161159E+09 | 83857382.52 |
April | 97360928.36 | 639960.68 | 96720967.68 | 0.283747E+09 | 15669334.54 |
May | 0.111143E+09 | 3264604.17 | 0.107878E+09 | 0.423201E+09 | 184072.50 |
June | 0.111100E+09 | 4069212.55 | 0.107031E+09 | 0.439632E+09 | 688435.74 |
July | 0.113574E+09 | 2060818.43 | 0.111513E+09 | 0.423115E+09 | 40392.42 |
August | 0.104228E+09 | 472450.58 | 0.103756E+09 | 0.358753E+09 | 0.00 |
September | 89674035.71 | 10474.88 | 89663560.83 | 0.272422E+09 | 1038396.81 |
October | 80264144.39 | 0.00 | 80264144.39 | 0.181917E+09 | 55104212.51 |
November | 65791475.18 | 0.00 | 65791475.18 | 95610368.04 | 0.138127E+09 |
December | 63002611.84 | 0.00 | 63002611.84 | 53277037.01 | 0.213791E+09 |
Annual Sum or Average | 0.106220E+10 | 10520675.29 | 0.105168E+10 | 0.281825E+10 | 0.883052E+09 |
Minimum of Months | 63002611.84 | 0.00 | 63002611.84 | 47695598.50 | 0.00 |
Maximum of Months | 0.113574E+09 | 4069212.55 | 0.111513E+09 | 0.439632E+09 | 0.224151E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257989E+09 | 0.103397E+09 | 0.154592E+09 | 0.301017E+09 | 0.380767E+09 |
February | 0.283875E+09 | 0.117206E+09 | 0.166670E+09 | 0.404387E+09 | 0.258819E+09 |
March | 0.383559E+09 | 0.158573E+09 | 0.224986E+09 | 0.679195E+09 | 0.146141E+09 |
April | 0.441812E+09 | 0.205992E+09 | 0.235819E+09 | 0.101014E+10 | 27982640.54 |
May | 0.448586E+09 | 0.199072E+09 | 0.249514E+09 | 0.123147E+10 | 292257.41 |
June | 0.352537E+09 | 0.116661E+09 | 0.235876E+09 | 0.109155E+10 | 1292450.70 |
July | 0.305751E+09 | 63914231.92 | 0.241837E+09 | 0.962124E+09 | 75199.10 |
August | 0.276344E+09 | 48081891.75 | 0.228262E+09 | 0.821150E+09 | 0.00 |
September | 0.285218E+09 | 79234770.85 | 0.205983E+09 | 0.728197E+09 | 1805316.68 |
October | 0.322437E+09 | 0.129912E+09 | 0.192525E+09 | 0.663108E+09 | 98018509.08 |
November | 0.276343E+09 | 0.118148E+09 | 0.158195E+09 | 0.452518E+09 | 0.241425E+09 |
December | 0.249944E+09 | 99241778.46 | 0.150703E+09 | 0.316147E+09 | 0.372525E+09 |
Annual Sum or Average | 0.388440E+10 | 0.143943E+10 | 0.244496E+10 | 0.866101E+10 | 0.152914E+10 |
Minimum of Months | 0.249944E+09 | 48081891.75 | 0.150703E+09 | 0.301017E+09 | 0.00 |
Maximum of Months | 0.448586E+09 | 0.205992E+09 | 0.249514E+09 | 0.123147E+10 | 0.380767E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81791256.15 | 0.00 | 81791256.15 | 61087045.87 | 0.299049E+09 |
February | 87604389.95 | 0.00 | 87604389.95 | 0.103024E+09 | 0.200750E+09 |
March | 0.116896E+09 | 3994.34 | 0.116892E+09 | 0.206127E+09 | 0.122859E+09 |
April | 0.123301E+09 | 810469.82 | 0.122491E+09 | 0.341402E+09 | 33799652.20 |
May | 0.140755E+09 | 4134415.20 | 0.136621E+09 | 0.499713E+09 | 2486473.45 |
June | 0.140701E+09 | 5153400.94 | 0.135548E+09 | 0.518761E+09 | 2491821.47 |
July | 0.143834E+09 | 2609896.51 | 0.141225E+09 | 0.491689E+09 | 334444.85 |
August | 0.131999E+09 | 598328.84 | 0.131400E+09 | 0.409855E+09 | 606467.67 |
September | 0.113567E+09 | 13265.78 | 0.113553E+09 | 0.308454E+09 | 5965175.29 |
October | 0.101649E+09 | 0.00 | 0.101649E+09 | 0.219818E+09 | 95821712.78 |
November | 83320752.10 | 0.00 | 83320752.10 | 0.118695E+09 | 0.198822E+09 |
December | 79788832.65 | 0.00 | 79788832.65 | 67139056.04 | 0.290341E+09 |
Annual Sum or Average | 0.134521E+10 | 13323771.43 | 0.133188E+10 | 0.334576E+10 | 0.125333E+10 |
Minimum of Months | 79788832.65 | 0.00 | 79788832.65 | 61087045.87 | 334444.85 |
Maximum of Months | 0.143834E+09 | 5153400.94 | 0.141225E+09 | 0.518761E+09 | 0.299049E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30151643.73 | 0.00 | 30151643.73 | 22519214.52 | 0.110242E+09 |
February | 32294605.55 | 0.00 | 32294605.55 | 37978899.32 | 74004626.86 |
March | 43092653.94 | 1472.48 | 43091181.46 | 75986902.07 | 45290774.65 |
April | 45454028.33 | 298772.74 | 45155255.59 | 0.125855E+09 | 12459951.33 |
May | 51888214.42 | 1524116.63 | 50364097.78 | 0.184215E+09 | 916617.07 |
June | 51868263.62 | 1899756.97 | 49968506.65 | 0.191237E+09 | 918588.57 |
July | 53023337.04 | 962115.92 | 52061221.12 | 0.181257E+09 | 123290.22 |
August | 48660160.78 | 220568.79 | 48439591.99 | 0.151090E+09 | 223569.10 |
September | 41865317.31 | 4890.31 | 41860427.00 | 0.113709E+09 | 2199010.61 |
October | 37472205.27 | 0.00 | 37472205.27 | 81034072.21 | 35323851.00 |
November | 30715479.27 | 0.00 | 30715479.27 | 43755968.87 | 73293884.48 |
December | 29413467.51 | 0.00 | 29413467.51 | 24750236.07 | 0.107032E+09 |
Annual Sum or Average | 0.495899E+09 | 4911693.84 | 0.490988E+09 | 0.123339E+10 | 0.462028E+09 |
Minimum of Months | 29413467.51 | 0.00 | 29413467.51 | 22519214.52 | 123290.22 |
Maximum of Months | 53023337.04 | 1899756.97 | 52061221.12 | 0.191237E+09 | 0.110242E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137433E+09 | 83654345.52 | 53778735.30 | 0.203174E+09 | 99308404.20 |
February | 0.117769E+09 | 65415652.44 | 52353089.37 | 0.189219E+09 | 69280394.17 |
March | 0.110791E+09 | 48583182.93 | 62207951.33 | 0.207716E+09 | 44205711.35 |
April | 76439986.95 | 22044210.13 | 54395776.82 | 0.195422E+09 | 12554012.22 |
May | 56942384.20 | 4796528.28 | 52145855.93 | 0.197228E+09 | 935258.38 |
June | 49841301.94 | 866681.31 | 48974620.63 | 0.187400E+09 | 930385.40 |
July | 53494682.26 | 523845.92 | 52970836.34 | 0.181904E+09 | 122712.60 |
August | 56404154.00 | 2471930.00 | 53932224.00 | 0.167247E+09 | 220591.59 |
September | 75531182.28 | 20796286.17 | 54734896.11 | 0.180967E+09 | 2149080.74 |
October | 0.132136E+09 | 74110624.66 | 58025757.98 | 0.260243E+09 | 34384018.03 |
November | 0.159548E+09 | 0.105698E+09 | 53849399.00 | 0.274412E+09 | 69211578.15 |
December | 0.146659E+09 | 91974985.62 | 54684083.69 | 0.225738E+09 | 97970911.95 |
Annual Sum or Average | 0.117299E+10 | 0.520936E+09 | 0.652053E+09 | 0.247067E+10 | 0.431273E+09 |
Minimum of Months | 49841301.94 | 523845.92 | 48974620.63 | 0.167247E+09 | 122712.60 |
Maximum of Months | 0.159548E+09 | 0.105698E+09 | 62207951.33 | 0.274412E+09 | 99308404.20 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373021E+09 | 0.227055E+09 | 0.145966E+09 | 0.551454E+09 | 0.269543E+09 |
February | 0.319648E+09 | 0.177551E+09 | 0.142097E+09 | 0.513580E+09 | 0.188041E+09 |
March | 0.300710E+09 | 0.131865E+09 | 0.168845E+09 | 0.563782E+09 | 0.119983E+09 |
April | 0.207474E+09 | 59832495.34 | 0.147641E+09 | 0.530414E+09 | 34074157.02 |
May | 0.154553E+09 | 13018758.85 | 0.141535E+09 | 0.535318E+09 | 2538482.55 |
June | 0.135279E+09 | 2352350.36 | 0.132927E+09 | 0.508642E+09 | 2525256.27 |
July | 0.145196E+09 | 1421824.97 | 0.143774E+09 | 0.493725E+09 | 333067.10 |
August | 0.153092E+09 | 6709323.64 | 0.146383E+09 | 0.453943E+09 | 598730.70 |
September | 0.205007E+09 | 56445374.46 | 0.148562E+09 | 0.491182E+09 | 5833044.71 |
October | 0.358645E+09 | 0.201151E+09 | 0.157494E+09 | 0.706354E+09 | 93325258.04 |
November | 0.433045E+09 | 0.286886E+09 | 0.146158E+09 | 0.744811E+09 | 0.187854E+09 |
December | 0.398063E+09 | 0.249639E+09 | 0.148424E+09 | 0.612698E+09 | 0.265913E+09 |
Annual Sum or Average | 0.318373E+10 | 0.141393E+10 | 0.176981E+10 | 0.670590E+10 | 0.117056E+10 |
Minimum of Months | 0.135279E+09 | 1421824.97 | 0.132927E+09 | 0.453943E+09 | 333067.10 |
Maximum of Months | 0.433045E+09 | 0.286886E+09 | 0.168845E+09 | 0.744811E+09 | 0.269543E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294544E+09 | 0.179286E+09 | 0.115258E+09 | 0.423713E+09 | 0.204517E+09 |
February | 0.252400E+09 | 0.140198E+09 | 0.112202E+09 | 0.395506E+09 | 0.136989E+09 |
March | 0.237446E+09 | 0.104123E+09 | 0.133323E+09 | 0.441046E+09 | 74746229.68 |
April | 0.163825E+09 | 47244750.35 | 0.116580E+09 | 0.430566E+09 | 13270612.79 |
May | 0.122038E+09 | 10279832.20 | 0.111758E+09 | 0.451319E+09 | 51259.25 |
June | 0.106819E+09 | 1857455.64 | 0.104962E+09 | 0.429428E+09 | 601011.90 |
July | 0.114649E+09 | 1122697.04 | 0.113526E+09 | 0.425166E+09 | 14718.65 |
August | 0.120884E+09 | 5297795.43 | 0.115587E+09 | 0.392586E+09 | 0.00 |
September | 0.161877E+09 | 44570222.41 | 0.117307E+09 | 0.413221E+09 | 738880.62 |
October | 0.283192E+09 | 0.158833E+09 | 0.124360E+09 | 0.562772E+09 | 48537464.08 |
November | 0.341939E+09 | 0.226530E+09 | 0.115409E+09 | 0.584986E+09 | 0.125502E+09 |
December | 0.314317E+09 | 0.197119E+09 | 0.117198E+09 | 0.474103E+09 | 0.197432E+09 |
Annual Sum or Average | 0.251393E+10 | 0.111646E+10 | 0.139747E+10 | 0.542441E+10 | 0.802401E+09 |
Minimum of Months | 0.106819E+09 | 1122697.04 | 0.104962E+09 | 0.392586E+09 | 0.00 |
Maximum of Months | 0.341939E+09 | 0.226530E+09 | 0.133323E+09 | 0.584986E+09 | 0.204517E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252722E+09 | 98336017.03 | 0.154386E+09 | 0.301959E+09 | 0.415084E+09 |
February | 0.261680E+09 | 96678795.88 | 0.165002E+09 | 0.372716E+09 | 0.270961E+09 |
March | 0.375492E+09 | 0.150496E+09 | 0.224996E+09 | 0.662749E+09 | 0.142166E+09 |
April | 0.440209E+09 | 0.206149E+09 | 0.234060E+09 | 0.996759E+09 | 24690838.11 |
May | 0.431236E+09 | 0.182936E+09 | 0.248301E+09 | 0.119776E+10 | 106115.92 |
June | 0.392623E+09 | 0.152910E+09 | 0.239713E+09 | 0.115769E+10 | 1029255.13 |
July | 0.300278E+09 | 58187984.70 | 0.242090E+09 | 0.952668E+09 | 24612.37 |
August | 0.275648E+09 | 48573712.67 | 0.227074E+09 | 0.818909E+09 | 0.00 |
September | 0.294576E+09 | 87110970.87 | 0.207465E+09 | 0.737293E+09 | 1345907.89 |
October | 0.316556E+09 | 0.126392E+09 | 0.190164E+09 | 0.648416E+09 | 92575047.65 |
November | 0.276801E+09 | 0.118147E+09 | 0.158654E+09 | 0.459014E+09 | 0.246061E+09 |
December | 0.244062E+09 | 92808591.25 | 0.151254E+09 | 0.307384E+09 | 0.392509E+09 |
Annual Sum or Average | 0.386189E+10 | 0.141873E+10 | 0.244316E+10 | 0.861332E+10 | 0.158655E+10 |
Minimum of Months | 0.244062E+09 | 48573712.67 | 0.151254E+09 | 0.301959E+09 | 0.00 |
Maximum of Months | 0.440209E+09 | 0.206149E+09 | 0.248301E+09 | 0.119776E+10 | 0.415084E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64583759.30 | 0.00 | 64583759.30 | 48078987.63 | 0.222066E+09 |
February | 69173908.08 | 0.00 | 69173908.08 | 78599636.57 | 0.148798E+09 |
March | 92302947.57 | 3154.00 | 92299793.57 | 0.162292E+09 | 81114189.65 |
April | 97360928.36 | 639960.68 | 96720967.68 | 0.284060E+09 | 13673011.26 |
May | 0.111143E+09 | 3264604.17 | 0.107878E+09 | 0.424061E+09 | 64498.03 |
June | 0.111100E+09 | 4069212.55 | 0.107031E+09 | 0.437196E+09 | 588622.39 |
July | 0.113574E+09 | 2060818.43 | 0.111513E+09 | 0.423374E+09 | 14714.53 |
August | 0.104228E+09 | 472450.58 | 0.103756E+09 | 0.358733E+09 | 0.00 |
September | 89674035.71 | 10474.88 | 89663560.83 | 0.272239E+09 | 706587.79 |
October | 80264144.39 | 0.00 | 80264144.39 | 0.182502E+09 | 51142977.59 |
November | 65791475.18 | 0.00 | 65791475.18 | 97508410.13 | 0.134699E+09 |
December | 63002611.84 | 0.00 | 63002611.84 | 54765865.43 | 0.210901E+09 |
Annual Sum or Average | 0.106220E+10 | 10520675.29 | 0.105168E+10 | 0.282341E+10 | 0.863768E+09 |
Minimum of Months | 63002611.84 | 0.00 | 63002611.84 | 48078987.63 | 0.00 |
Maximum of Months | 0.113574E+09 | 4069212.55 | 0.111513E+09 | 0.437196E+09 | 0.222066E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252722E+09 | 98336017.03 | 0.154386E+09 | 0.319885E+09 | 0.406761E+09 |
February | 0.261680E+09 | 96678795.88 | 0.165002E+09 | 0.382330E+09 | 0.274977E+09 |
March | 0.375492E+09 | 0.150496E+09 | 0.224996E+09 | 0.667981E+09 | 0.150559E+09 |
April | 0.440209E+09 | 0.206149E+09 | 0.234060E+09 | 0.999467E+09 | 25439885.56 |
May | 0.431236E+09 | 0.182936E+09 | 0.248301E+09 | 0.119886E+10 | 104471.46 |
June | 0.392623E+09 | 0.152910E+09 | 0.239713E+09 | 0.115736E+10 | 1060902.08 |
July | 0.300278E+09 | 58187984.70 | 0.242090E+09 | 0.952752E+09 | 24607.73 |
August | 0.275648E+09 | 48573712.67 | 0.227074E+09 | 0.820224E+09 | 0.00 |
September | 0.294576E+09 | 87110970.87 | 0.207465E+09 | 0.742150E+09 | 1269680.60 |
October | 0.316556E+09 | 0.126392E+09 | 0.190164E+09 | 0.655515E+09 | 94924182.22 |
November | 0.276801E+09 | 0.118147E+09 | 0.158654E+09 | 0.471908E+09 | 0.249985E+09 |
December | 0.244062E+09 | 92808591.25 | 0.151254E+09 | 0.326426E+09 | 0.384579E+09 |
Annual Sum or Average | 0.386189E+10 | 0.141873E+10 | 0.244316E+10 | 0.869486E+10 | 0.158968E+10 |
Minimum of Months | 0.244062E+09 | 48573712.67 | 0.151254E+09 | 0.319885E+09 | 0.00 |
Maximum of Months | 0.440209E+09 | 0.206149E+09 | 0.248301E+09 | 0.119886E+10 | 0.406761E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431977E+09 | 0.262941E+09 | 0.169036E+09 | 0.605354E+09 | 0.312324E+09 |
February | 0.370169E+09 | 0.205613E+09 | 0.164555E+09 | 0.571870E+09 | 0.206011E+09 |
March | 0.348237E+09 | 0.152706E+09 | 0.195531E+09 | 0.647595E+09 | 0.108424E+09 |
April | 0.240265E+09 | 69288960.48 | 0.170976E+09 | 0.646716E+09 | 17614650.17 |
May | 0.178980E+09 | 15076360.47 | 0.163904E+09 | 0.686405E+09 | 17647.94 |
June | 0.156660E+09 | 2724136.95 | 0.153936E+09 | 0.652997E+09 | 570002.46 |
July | 0.168144E+09 | 1646542.96 | 0.166497E+09 | 0.641449E+09 | 14293.49 |
August | 0.177289E+09 | 7769725.43 | 0.169519E+09 | 0.590244E+09 | 0.00 |
September | 0.237408E+09 | 65366508.58 | 0.172042E+09 | 0.616312E+09 | 848971.26 |
October | 0.415329E+09 | 0.232943E+09 | 0.182386E+09 | 0.824959E+09 | 70619372.10 |
November | 0.501487E+09 | 0.332228E+09 | 0.169258E+09 | 0.849728E+09 | 0.188475E+09 |
December | 0.460976E+09 | 0.289094E+09 | 0.171882E+09 | 0.680380E+09 | 0.300758E+09 |
Annual Sum or Average | 0.368692E+10 | 0.163740E+10 | 0.204952E+10 | 0.801401E+10 | 0.120568E+10 |
Minimum of Months | 0.156660E+09 | 1646542.96 | 0.153936E+09 | 0.571870E+09 | 0.00 |
Maximum of Months | 0.501487E+09 | 0.332228E+09 | 0.195531E+09 | 0.849728E+09 | 0.312324E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452069E+09 | 0.00 | 0.452069E+09 | 0.233416E+09 | 0.198120E+10 |
February | 0.484199E+09 | 0.00 | 0.484199E+09 | 0.449704E+09 | 0.133929E+10 |
March | 0.646096E+09 | 22077.16 | 0.646074E+09 | 0.100854E+10 | 0.806622E+09 |
April | 0.681501E+09 | 4479555.11 | 0.677021E+09 | 0.177606E+10 | 0.224966E+09 |
May | 0.777970E+09 | 22851363.71 | 0.755118E+09 | 0.261826E+10 | 23299898.28 |
June | 0.777671E+09 | 28483409.07 | 0.749187E+09 | 0.271177E+10 | 23639417.79 |
July | 0.794989E+09 | 14425182.63 | 0.780564E+09 | 0.255574E+10 | 2911973.87 |
August | 0.729571E+09 | 3307028.78 | 0.726264E+09 | 0.211589E+10 | 10982104.15 |
September | 0.627694E+09 | 73321.39 | 0.627621E+09 | 0.155668E+10 | 61923490.57 |
October | 0.561828E+09 | 0.00 | 0.561828E+09 | 0.114393E+10 | 0.579206E+09 |
November | 0.460523E+09 | 0.00 | 0.460523E+09 | 0.582373E+09 | 0.120484E+10 |
December | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.274109E+09 | 0.187339E+10 |
Annual Sum or Average | 0.743511E+10 | 73641937.85 | 0.736147E+10 | 0.170265E+11 | 0.813227E+10 |
Minimum of Months | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.233416E+09 | 2911973.87 |
Maximum of Months | 0.794989E+09 | 28483409.07 | 0.780564E+09 | 0.271177E+10 | 0.198120E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452069E+09 | 0.00 | 0.452069E+09 | 0.204856E+09 | 0.205050E+10 |
February | 0.484199E+09 | 0.00 | 0.484199E+09 | 0.420283E+09 | 0.138466E+10 |
March | 0.646096E+09 | 22077.16 | 0.646074E+09 | 0.980345E+09 | 0.834793E+09 |
April | 0.681501E+09 | 4479555.11 | 0.677021E+09 | 0.174934E+10 | 0.236561E+09 |
May | 0.777970E+09 | 22851363.71 | 0.755118E+09 | 0.258420E+10 | 25979545.28 |
June | 0.777671E+09 | 28483409.07 | 0.749187E+09 | 0.267849E+10 | 25896336.45 |
July | 0.794989E+09 | 14425182.63 | 0.780564E+09 | 0.251947E+10 | 3324037.09 |
August | 0.729571E+09 | 3307028.78 | 0.726264E+09 | 0.208209E+10 | 13544828.99 |
September | 0.627694E+09 | 73321.39 | 0.627621E+09 | 0.152800E+10 | 71722315.21 |
October | 0.561828E+09 | 0.00 | 0.561828E+09 | 0.112236E+10 | 0.600104E+09 |
November | 0.460523E+09 | 0.00 | 0.460523E+09 | 0.557306E+09 | 0.123960E+10 |
December | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.245383E+09 | 0.193594E+10 |
Annual Sum or Average | 0.743511E+10 | 73641937.85 | 0.736147E+10 | 0.166721E+11 | 0.842263E+10 |
Minimum of Months | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.204856E+09 | 3324037.09 |
Maximum of Months | 0.794989E+09 | 28483409.07 | 0.780564E+09 | 0.267849E+10 | 0.205050E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64583759.30 | 0.00 | 64583759.30 | 36188887.40 | 0.275960E+09 |
February | 69173908.08 | 0.00 | 69173908.08 | 72048513.71 | 0.190010E+09 |
March | 92302947.57 | 3154.00 | 92299793.57 | 0.164341E+09 | 0.119204E+09 |
April | 97360928.36 | 639960.68 | 96720967.68 | 0.280007E+09 | 38783159.82 |
May | 0.111143E+09 | 3264604.17 | 0.107878E+09 | 0.395046E+09 | 7533528.63 |
June | 0.111100E+09 | 4069212.55 | 0.107031E+09 | 0.411321E+09 | 6963018.12 |
July | 0.113574E+09 | 2060818.43 | 0.111513E+09 | 0.387358E+09 | 1566960.39 |
August | 0.104228E+09 | 472450.58 | 0.103756E+09 | 0.332125E+09 | 4241078.84 |
September | 89674035.71 | 10474.88 | 89663560.83 | 0.251252E+09 | 17363227.46 |
October | 80264144.39 | 0.00 | 80264144.39 | 0.194243E+09 | 84310017.76 |
November | 65791475.18 | 0.00 | 65791475.18 | 0.101250E+09 | 0.166436E+09 |
December | 63002611.84 | 0.00 | 63002611.84 | 46367360.09 | 0.260366E+09 |
Annual Sum or Average | 0.106220E+10 | 10520675.29 | 0.105168E+10 | 0.267155E+10 | 0.117274E+10 |
Minimum of Months | 63002611.84 | 0.00 | 63002611.84 | 36188887.40 | 1566960.39 |
Maximum of Months | 0.113574E+09 | 4069212.55 | 0.111513E+09 | 0.411321E+09 | 0.275960E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515941E+09 | 0.206779E+09 | 0.309162E+09 | 0.547679E+09 | 0.947660E+09 |
February | 0.567710E+09 | 0.234395E+09 | 0.333316E+09 | 0.783535E+09 | 0.664313E+09 |
March | 0.767063E+09 | 0.317123E+09 | 0.449940E+09 | 0.137172E+10 | 0.427942E+09 |
April | 0.883560E+09 | 0.411956E+09 | 0.471605E+09 | 0.200155E+10 | 0.143609E+09 |
May | 0.897109E+09 | 0.398117E+09 | 0.498992E+09 | 0.235255E+10 | 27927982.24 |
June | 0.705025E+09 | 0.233306E+09 | 0.471719E+09 | 0.207064E+10 | 26725180.99 |
July | 0.611459E+09 | 0.127819E+09 | 0.483640E+09 | 0.178334E+10 | 5923895.93 |
August | 0.552648E+09 | 96156954.65 | 0.456491E+09 | 0.153821E+10 | 15902010.48 |
September | 0.570395E+09 | 0.158458E+09 | 0.411936E+09 | 0.137087E+10 | 65093838.66 |
October | 0.644829E+09 | 0.259805E+09 | 0.385023E+09 | 0.136758E+10 | 0.309446E+09 |
November | 0.552646E+09 | 0.236279E+09 | 0.316367E+09 | 0.924942E+09 | 0.592344E+09 |
December | 0.499853E+09 | 0.198469E+09 | 0.301384E+09 | 0.598845E+09 | 0.916566E+09 |
Annual Sum or Average | 0.776824E+10 | 0.287866E+10 | 0.488958E+10 | 0.167115E+11 | 0.414345E+10 |
Minimum of Months | 0.499853E+09 | 96156954.65 | 0.301384E+09 | 0.547679E+09 | 5923895.93 |
Maximum of Months | 0.897109E+09 | 0.411956E+09 | 0.498992E+09 | 0.235255E+10 | 0.947660E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294544E+09 | 0.179286E+09 | 0.115258E+09 | 0.423508E+09 | 0.249933E+09 |
February | 0.252400E+09 | 0.140198E+09 | 0.112202E+09 | 0.397262E+09 | 0.178796E+09 |
March | 0.237446E+09 | 0.104123E+09 | 0.133323E+09 | 0.448647E+09 | 0.117277E+09 |
April | 0.163825E+09 | 47244750.35 | 0.116580E+09 | 0.429753E+09 | 38924619.44 |
May | 0.122038E+09 | 10279832.20 | 0.111758E+09 | 0.423785E+09 | 7603779.04 |
June | 0.106819E+09 | 1857455.64 | 0.104962E+09 | 0.402883E+09 | 7154341.25 |
July | 0.114649E+09 | 1122697.04 | 0.113526E+09 | 0.388347E+09 | 1570210.78 |
August | 0.120884E+09 | 5297795.43 | 0.115587E+09 | 0.367381E+09 | 4246663.97 |
September | 0.161877E+09 | 44570222.41 | 0.117307E+09 | 0.395553E+09 | 17330880.04 |
October | 0.283192E+09 | 0.158833E+09 | 0.124360E+09 | 0.578929E+09 | 83065709.05 |
November | 0.341939E+09 | 0.226530E+09 | 0.115409E+09 | 0.598424E+09 | 0.159087E+09 |
December | 0.314317E+09 | 0.197119E+09 | 0.117198E+09 | 0.478689E+09 | 0.239874E+09 |
Annual Sum or Average | 0.251393E+10 | 0.111646E+10 | 0.139747E+10 | 0.533316E+10 | 0.110486E+10 |
Minimum of Months | 0.106819E+09 | 1122697.04 | 0.104962E+09 | 0.367381E+09 | 1570210.78 |
Maximum of Months | 0.341939E+09 | 0.226530E+09 | 0.133323E+09 | 0.598424E+09 | 0.249933E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81791256.15 | 0.00 | 81791256.15 | 54801988.27 | 0.301448E+09 |
February | 87604389.95 | 0.00 | 87604389.95 | 96665757.66 | 0.201368E+09 |
March | 0.116896E+09 | 3994.34 | 0.116892E+09 | 0.196000E+09 | 0.125057E+09 |
April | 0.123301E+09 | 810469.82 | 0.122491E+09 | 0.327770E+09 | 35377707.26 |
May | 0.140755E+09 | 4134415.20 | 0.136621E+09 | 0.481054E+09 | 3094361.88 |
June | 0.140701E+09 | 5153400.94 | 0.135548E+09 | 0.498458E+09 | 2813015.68 |
July | 0.143834E+09 | 2609896.51 | 0.141225E+09 | 0.471133E+09 | 312485.74 |
August | 0.131999E+09 | 598328.84 | 0.131400E+09 | 0.390291E+09 | 1202352.80 |
September | 0.113567E+09 | 13265.78 | 0.113553E+09 | 0.292428E+09 | 7298834.93 |
October | 0.101649E+09 | 0.00 | 0.101649E+09 | 0.211753E+09 | 96635813.49 |
November | 83320752.10 | 0.00 | 83320752.10 | 0.114679E+09 | 0.193631E+09 |
December | 79788832.65 | 0.00 | 79788832.65 | 63122920.65 | 0.286703E+09 |
Annual Sum or Average | 0.134521E+10 | 13323771.43 | 0.133188E+10 | 0.319816E+10 | 0.125494E+10 |
Minimum of Months | 79788832.65 | 0.00 | 79788832.65 | 54801988.27 | 312485.74 |
Maximum of Months | 0.143834E+09 | 5153400.94 | 0.141225E+09 | 0.498458E+09 | 0.301448E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73178946.78 | 0.00 | 73178946.78 | 49031546.55 | 0.269690E+09 |
February | 78379979.62 | 0.00 | 78379979.62 | 86487219.65 | 0.180165E+09 |
March | 0.104587E+09 | 3573.75 | 0.104584E+09 | 0.175362E+09 | 0.111889E+09 |
April | 0.110318E+09 | 725130.42 | 0.109593E+09 | 0.293257E+09 | 31652568.74 |
May | 0.125934E+09 | 3699076.94 | 0.122235E+09 | 0.430401E+09 | 2768537.29 |
June | 0.125886E+09 | 4610767.35 | 0.121275E+09 | 0.445972E+09 | 2516815.79 |
July | 0.128689E+09 | 2335084.29 | 0.126354E+09 | 0.421524E+09 | 279582.17 |
August | 0.118100E+09 | 535327.08 | 0.117564E+09 | 0.349194E+09 | 1075749.60 |
September | 0.101608E+09 | 11868.94 | 0.101597E+09 | 0.261637E+09 | 6530295.26 |
October | 90946169.97 | 0.00 | 90946169.97 | 0.189456E+09 | 86460450.60 |
November | 74547392.61 | 0.00 | 74547392.61 | 0.102603E+09 | 0.173243E+09 |
December | 71387370.89 | 0.00 | 71387370.89 | 56476316.27 | 0.256493E+09 |
Annual Sum or Average | 0.120356E+10 | 11920828.78 | 0.119164E+10 | 0.286140E+10 | 0.112276E+10 |
Minimum of Months | 71387370.89 | 0.00 | 71387370.89 | 49031546.55 | 279582.17 |
Maximum of Months | 0.128689E+09 | 4610767.35 | 0.126354E+09 | 0.445972E+09 | 0.269690E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109962E+10 | 0.669330E+09 | 0.430291E+09 | 0.159588E+10 | 0.801014E+09 |
February | 0.942284E+09 | 0.523400E+09 | 0.418884E+09 | 0.148626E+10 | 0.557701E+09 |
March | 0.886455E+09 | 0.388721E+09 | 0.497734E+09 | 0.162498E+10 | 0.361870E+09 |
April | 0.611607E+09 | 0.176379E+09 | 0.435228E+09 | 0.151735E+10 | 0.105279E+09 |
May | 0.455604E+09 | 38377676.82 | 0.417226E+09 | 0.152190E+10 | 9278994.12 |
June | 0.398787E+09 | 6934435.38 | 0.391853E+09 | 0.143986E+10 | 8517617.18 |
July | 0.428018E+09 | 4191362.60 | 0.423827E+09 | 0.139541E+10 | 927544.47 |
August | 0.451297E+09 | 19778249.01 | 0.431519E+09 | 0.127914E+10 | 3540739.24 |
September | 0.604335E+09 | 0.166394E+09 | 0.437941E+09 | 0.139564E+10 | 21165283.28 |
October | 0.105724E+10 | 0.592969E+09 | 0.464272E+09 | 0.205288E+10 | 0.278498E+09 |
November | 0.127656E+10 | 0.845705E+09 | 0.430856E+09 | 0.217955E+10 | 0.541778E+09 |
December | 0.117344E+10 | 0.735904E+09 | 0.437535E+09 | 0.178763E+10 | 0.774719E+09 |
Annual Sum or Average | 0.938525E+10 | 0.416808E+10 | 0.521717E+10 | 0.192765E+11 | 0.346429E+10 |
Minimum of Months | 0.398787E+09 | 4191362.60 | 0.391853E+09 | 0.127914E+10 | 927544.47 |
Maximum of Months | 0.127656E+10 | 0.845705E+09 | 0.497734E+09 | 0.217955E+10 | 0.801014E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 793.08 | 404.97 | 556.20 | 338.55 | 217.64 | 0.00 | 0.00 |
February | 816.17 | 318.03 | 527.68 | 293.11 | 234.58 | 0.00 | 0.00 |
March | 802.39 | 195.14 | 448.38 | 196.62 | 251.76 | 0.00 | 0.00 |
April | 754.00 | 66.43 | 319.67 | 92.19 | 227.48 | 0.00 | 0.00 |
May | 704.21 | 8.39 | 230.45 | 19.41 | 211.03 | 0.00 | 0.00 |
June | 692.64 | 5.19 | 208.43 | 3.62 | 204.81 | 0.00 | 0.00 |
July | 650.31 | 0.70 | 216.49 | 2.12 | 214.37 | 0.00 | 0.00 |
August | 604.34 | 3.19 | 228.27 | 10.00 | 218.27 | 0.00 | 0.00 |
September | 696.66 | 18.64 | 315.87 | 86.97 | 228.90 | 0.00 | 0.00 |
October | 1009.46 | 155.19 | 534.76 | 299.93 | 234.83 | 0.00 | 0.00 |
November | 1106.91 | 300.04 | 667.22 | 442.03 | 225.19 | 0.00 | 0.00 |
December | 879.26 | 398.13 | 593.54 | 372.23 | 221.31 | 0.00 | 0.00 |
Annual Sum or Average | 792.04 | 155.48 | 403.18 | 179.06 | 224.12 | 0.00 | 0.00 |
Minimum of Months | 604.34 | 0.70 | 208.43 | 2.12 | 204.81 | 0.00 | 0.00 |
Maximum of Months | 1106.91 | 404.97 | 667.22 | 442.03 | 251.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2171.67 | 1256.49 | 1566.22 | 953.35 | 612.87 | 0.00 | 0.00 |
February | 2243.83 | 990.34 | 1485.92 | 825.37 | 660.55 | 0.00 | 0.00 |
March | 2227.10 | 587.73 | 1262.60 | 553.67 | 708.93 | 0.00 | 0.00 |
April | 2125.13 | 183.29 | 900.16 | 259.60 | 640.56 | 0.00 | 0.00 |
May | 2004.76 | 20.06 | 648.92 | 54.66 | 594.26 | 0.00 | 0.00 |
June | 1971.93 | 16.88 | 586.93 | 10.21 | 576.72 | 0.00 | 0.00 |
July | 1847.13 | 2.32 | 609.63 | 5.97 | 603.66 | 0.00 | 0.00 |
August | 1712.72 | 9.29 | 642.79 | 28.17 | 614.62 | 0.00 | 0.00 |
September | 1950.70 | 52.79 | 889.46 | 244.90 | 644.56 | 0.00 | 0.00 |
October | 2823.21 | 447.12 | 1505.85 | 844.58 | 661.27 | 0.00 | 0.00 |
November | 3076.59 | 901.21 | 1878.85 | 1244.71 | 634.13 | 0.00 | 0.00 |
December | 2411.45 | 1237.34 | 1671.36 | 1048.17 | 623.19 | 0.00 | 0.00 |
Annual Sum or Average | 2212.87 | 473.22 | 1135.33 | 504.21 | 631.12 | 0.00 | 0.00 |
Minimum of Months | 1712.72 | 2.32 | 586.93 | 5.97 | 576.72 | 0.00 | 0.00 |
Maximum of Months | 3076.59 | 1256.49 | 1878.85 | 1244.71 | 708.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2912.14 | 1654.37 | 2034.60 | 1238.45 | 796.16 | 0.00 | 0.00 |
February | 3013.78 | 1292.97 | 1930.29 | 1072.20 | 858.09 | 0.00 | 0.00 |
March | 2993.43 | 755.95 | 1640.18 | 719.24 | 920.94 | 0.00 | 0.00 |
April | 2873.25 | 232.32 | 1169.36 | 337.23 | 832.13 | 0.00 | 0.00 |
May | 2718.62 | 24.83 | 842.99 | 71.01 | 771.98 | 0.00 | 0.00 |
June | 2666.45 | 21.34 | 762.45 | 13.26 | 749.20 | 0.00 | 0.00 |
July | 2492.49 | 3.05 | 791.95 | 7.76 | 784.19 | 0.00 | 0.00 |
August | 2308.93 | 11.29 | 835.02 | 36.60 | 798.43 | 0.00 | 0.00 |
September | 2619.19 | 62.56 | 1155.46 | 318.14 | 837.32 | 0.00 | 0.00 |
October | 3771.06 | 568.51 | 1956.19 | 1097.16 | 859.03 | 0.00 | 0.00 |
November | 4108.44 | 1164.39 | 2440.73 | 1616.95 | 823.77 | 0.00 | 0.00 |
December | 3229.38 | 1625.75 | 2171.19 | 1361.63 | 809.56 | 0.00 | 0.00 |
Annual Sum or Average | 2974.28 | 615.28 | 1474.86 | 655.00 | 819.86 | 0.00 | 0.00 |
Minimum of Months | 2308.93 | 3.05 | 762.45 | 7.76 | 749.20 | 0.00 | 0.00 |
Maximum of Months | 4108.44 | 1654.37 | 2440.73 | 1616.95 | 920.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 270.29 | 231.50 | 204.33 | 103.65 | 100.67 | 0.00 | 0.00 |
February | 320.55 | 171.19 | 212.50 | 97.92 | 114.58 | 0.00 | 0.00 |
March | 417.36 | 85.33 | 228.84 | 95.06 | 133.78 | 0.00 | 0.00 |
April | 554.80 | 17.18 | 233.04 | 97.76 | 135.28 | 0.00 | 0.00 |
May | 616.52 | 0.22 | 206.57 | 72.14 | 134.43 | 0.00 | 0.00 |
June | 614.47 | 0.78 | 192.69 | 59.71 | 132.98 | 0.00 | 0.00 |
July | 514.93 | 0.04 | 154.92 | 22.14 | 132.77 | 0.00 | 0.00 |
August | 453.11 | 0.00 | 148.05 | 20.11 | 127.93 | 0.00 | 0.00 |
September | 445.50 | 1.26 | 176.10 | 50.80 | 125.30 | 0.00 | 0.00 |
October | 456.04 | 57.11 | 223.92 | 106.49 | 117.43 | 0.00 | 0.00 |
November | 405.24 | 147.59 | 238.71 | 132.98 | 105.73 | 0.00 | 0.00 |
December | 290.94 | 221.79 | 208.48 | 108.25 | 100.23 | 0.00 | 0.00 |
Annual Sum or Average | 447.04 | 77.46 | 202.18 | 80.39 | 121.79 | 0.00 | 0.00 |
Minimum of Months | 270.29 | 0.00 | 148.05 | 20.11 | 100.23 | 0.00 | 0.00 |
Maximum of Months | 616.52 | 231.50 | 238.71 | 132.98 | 135.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 138.84 | 237.81 | 118.47 | 36.71 | 81.75 | 0.00 | 0.00 |
February | 193.70 | 177.56 | 136.76 | 39.96 | 96.80 | 0.00 | 0.00 |
March | 313.53 | 90.24 | 174.65 | 56.19 | 118.46 | 0.00 | 0.00 |
April | 498.06 | 17.73 | 207.40 | 79.78 | 127.62 | 0.00 | 0.00 |
May | 606.62 | 0.22 | 202.50 | 69.52 | 132.98 | 0.00 | 0.00 |
June | 617.41 | 0.81 | 194.34 | 60.56 | 133.77 | 0.00 | 0.00 |
July | 514.39 | 0.04 | 154.51 | 22.49 | 132.02 | 0.00 | 0.00 |
August | 440.81 | 0.00 | 141.83 | 18.31 | 123.52 | 0.00 | 0.00 |
September | 392.28 | 1.20 | 148.24 | 33.61 | 114.63 | 0.00 | 0.00 |
October | 314.93 | 59.51 | 148.16 | 47.19 | 100.97 | 0.00 | 0.00 |
November | 220.95 | 153.52 | 132.17 | 45.58 | 86.59 | 0.00 | 0.00 |
December | 142.18 | 226.10 | 114.64 | 34.65 | 79.99 | 0.00 | 0.00 |
Annual Sum or Average | 366.83 | 80.00 | 156.14 | 45.32 | 110.82 | 0.00 | 0.00 |
Minimum of Months | 138.84 | 0.00 | 114.64 | 18.31 | 79.99 | 0.00 | 0.00 |
Maximum of Months | 617.41 | 237.81 | 207.40 | 79.78 | 133.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 110.97 | 93.38 | 87.96 | 53.54 | 34.42 | 0.00 | 0.00 |
February | 115.68 | 75.43 | 83.45 | 46.35 | 37.10 | 0.00 | 0.00 |
March | 116.05 | 47.00 | 70.91 | 31.09 | 39.81 | 0.00 | 0.00 |
April | 110.84 | 18.20 | 50.55 | 14.58 | 35.97 | 0.00 | 0.00 |
May | 102.42 | 4.25 | 36.44 | 3.07 | 33.37 | 0.00 | 0.00 |
June | 98.82 | 3.11 | 32.96 | 0.57 | 32.39 | 0.00 | 0.00 |
July | 90.15 | 1.31 | 34.24 | 0.34 | 33.90 | 0.00 | 0.00 |
August | 83.44 | 3.51 | 36.10 | 1.58 | 34.52 | 0.00 | 0.00 |
September | 99.57 | 10.58 | 49.95 | 13.75 | 36.20 | 0.00 | 0.00 |
October | 151.98 | 36.67 | 84.57 | 47.43 | 37.14 | 0.00 | 0.00 |
November | 165.66 | 66.27 | 105.52 | 69.90 | 35.61 | 0.00 | 0.00 |
December | 125.23 | 90.62 | 93.86 | 58.86 | 35.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.17 | 37.36 | 63.76 | 28.32 | 35.44 | 0.00 | 0.00 |
Minimum of Months | 83.44 | 1.31 | 32.96 | 0.34 | 32.39 | 0.00 | 0.00 |
Maximum of Months | 165.66 | 93.38 | 105.52 | 69.90 | 39.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.61 | 68.94 | 19.29 | 0.00 | 19.29 | 0.00 | 0.00 |
February | 27.75 | 49.58 | 22.88 | 0.00 | 22.88 | 0.00 | 0.00 |
March | 52.42 | 23.27 | 27.57 | 0.00 | 27.57 | 0.00 | 0.00 |
April | 95.29 | 3.74 | 30.05 | 0.20 | 29.86 | 0.00 | 0.00 |
May | 135.84 | 0.01 | 33.20 | 0.98 | 32.23 | 0.00 | 0.00 |
June | 144.20 | 0.08 | 34.29 | 1.26 | 33.04 | 0.00 | 0.00 |
July | 134.17 | 0.00 | 33.93 | 0.62 | 33.31 | 0.00 | 0.00 |
August | 114.25 | 0.00 | 31.14 | 0.14 | 30.99 | 0.00 | 0.00 |
September | 90.83 | 0.14 | 27.68 | 0.00 | 27.68 | 0.00 | 0.00 |
October | 58.89 | 14.46 | 23.98 | 0.00 | 23.98 | 0.00 | 0.00 |
November | 32.35 | 41.15 | 20.31 | 0.00 | 20.31 | 0.00 | 0.00 |
December | 16.66 | 64.99 | 18.82 | 0.00 | 18.82 | 0.00 | 0.00 |
Annual Sum or Average | 76.68 | 22.09 | 26.95 | 0.27 | 26.68 | 0.00 | 0.00 |
Minimum of Months | 14.61 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 0.00 |
Maximum of Months | 144.20 | 68.94 | 34.29 | 1.26 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 262.92 | 222.26 | 206.29 | 105.54 | 100.75 | 0.00 | 0.00 |
February | 326.90 | 163.50 | 221.67 | 106.40 | 115.27 | 0.00 | 0.00 |
March | 418.45 | 80.36 | 231.86 | 98.08 | 133.78 | 0.00 | 0.00 |
April | 556.72 | 16.19 | 233.66 | 97.70 | 135.96 | 0.00 | 0.00 |
May | 627.73 | 0.17 | 213.05 | 78.16 | 134.88 | 0.00 | 0.00 |
June | 587.80 | 0.74 | 177.22 | 45.72 | 131.50 | 0.00 | 0.00 |
July | 517.73 | 0.04 | 156.96 | 24.28 | 132.68 | 0.00 | 0.00 |
August | 452.84 | 0.00 | 148.31 | 19.93 | 128.38 | 0.00 | 0.00 |
September | 439.31 | 1.16 | 172.49 | 47.76 | 124.73 | 0.00 | 0.00 |
October | 457.83 | 55.06 | 226.12 | 107.80 | 118.31 | 0.00 | 0.00 |
November | 397.82 | 141.75 | 238.53 | 132.98 | 105.56 | 0.00 | 0.00 |
December | 287.67 | 216.42 | 210.67 | 110.65 | 100.02 | 0.00 | 0.00 |
Annual Sum or Average | 444.88 | 74.46 | 202.89 | 81.05 | 121.84 | 0.00 | 0.00 |
Minimum of Months | 262.92 | 0.00 | 148.31 | 19.93 | 100.02 | 0.00 | 0.00 |
Maximum of Months | 627.73 | 222.26 | 238.53 | 132.98 | 135.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 123.25 | 218.91 | 120.43 | 38.60 | 81.83 | 0.00 | 0.00 |
February | 194.99 | 164.86 | 145.94 | 48.45 | 97.49 | 0.00 | 0.00 |
March | 311.85 | 83.97 | 177.67 | 59.21 | 118.46 | 0.00 | 0.00 |
April | 499.02 | 16.67 | 208.01 | 79.72 | 128.29 | 0.00 | 0.00 |
May | 617.78 | 0.18 | 208.98 | 75.54 | 133.43 | 0.00 | 0.00 |
June | 590.73 | 0.76 | 178.87 | 46.58 | 132.29 | 0.00 | 0.00 |
July | 517.19 | 0.04 | 156.56 | 24.63 | 131.93 | 0.00 | 0.00 |
August | 440.53 | 0.00 | 142.09 | 18.13 | 123.96 | 0.00 | 0.00 |
September | 386.03 | 1.08 | 144.63 | 30.57 | 114.06 | 0.00 | 0.00 |
October | 314.82 | 56.49 | 150.35 | 48.50 | 101.85 | 0.00 | 0.00 |
November | 209.09 | 144.05 | 132.00 | 45.58 | 86.41 | 0.00 | 0.00 |
December | 133.51 | 214.49 | 116.84 | 37.05 | 79.79 | 0.00 | 0.00 |
Annual Sum or Average | 362.28 | 74.77 | 156.86 | 45.98 | 110.88 | 0.00 | 0.00 |
Minimum of Months | 123.25 | 0.00 | 116.84 | 18.13 | 79.79 | 0.00 | 0.00 |
Maximum of Months | 617.78 | 218.91 | 208.98 | 79.72 | 133.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.21 | 282.77 | 232.38 | 116.01 | 116.37 | 0.00 | 0.00 |
February | 345.79 | 216.93 | 230.37 | 100.43 | 129.94 | 0.00 | 0.00 |
March | 393.01 | 123.72 | 213.37 | 67.37 | 146.00 | 0.00 | 0.00 |
April | 460.23 | 35.77 | 174.64 | 32.02 | 142.62 | 0.00 | 0.00 |
May | 528.84 | 2.56 | 150.89 | 8.76 | 142.12 | 0.00 | 0.00 |
June | 542.45 | 2.64 | 145.71 | 3.96 | 141.75 | 0.00 | 0.00 |
July | 503.50 | 0.34 | 147.68 | 2.06 | 145.62 | 0.00 | 0.00 |
August | 441.36 | 0.62 | 145.67 | 3.73 | 141.93 | 0.00 | 0.00 |
September | 422.19 | 6.23 | 168.20 | 29.81 | 138.39 | 0.00 | 0.00 |
October | 472.88 | 96.32 | 235.18 | 102.77 | 132.41 | 0.00 | 0.00 |
November | 453.49 | 201.76 | 272.62 | 151.46 | 121.16 | 0.00 | 0.00 |
December | 340.08 | 276.96 | 244.15 | 127.54 | 116.60 | 0.00 | 0.00 |
Annual Sum or Average | 434.42 | 103.42 | 196.53 | 61.93 | 134.60 | 0.00 | 0.00 |
Minimum of Months | 305.21 | 0.34 | 145.67 | 2.06 | 116.37 | 0.00 | 0.00 |
Maximum of Months | 542.45 | 282.77 | 272.62 | 151.46 | 146.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.83 | 226.23 | 204.33 | 103.65 | 100.67 | 0.00 | 0.00 |
February | 315.38 | 166.45 | 212.50 | 97.92 | 114.58 | 0.00 | 0.00 |
March | 411.84 | 80.72 | 228.84 | 95.06 | 133.78 | 0.00 | 0.00 |
April | 550.66 | 14.64 | 233.04 | 97.76 | 135.28 | 0.00 | 0.00 |
May | 615.70 | 0.06 | 206.57 | 72.14 | 134.43 | 0.00 | 0.00 |
June | 612.30 | 0.62 | 192.69 | 59.71 | 132.98 | 0.00 | 0.00 |
July | 514.42 | 0.01 | 154.92 | 22.14 | 132.77 | 0.00 | 0.00 |
August | 452.32 | 0.00 | 148.05 | 20.11 | 127.93 | 0.00 | 0.00 |
September | 443.87 | 0.80 | 176.10 | 50.80 | 125.30 | 0.00 | 0.00 |
October | 452.03 | 52.51 | 223.92 | 106.49 | 117.43 | 0.00 | 0.00 |
November | 401.36 | 141.93 | 238.71 | 132.98 | 105.73 | 0.00 | 0.00 |
December | 287.56 | 216.04 | 208.48 | 108.25 | 100.23 | 0.00 | 0.00 |
Annual Sum or Average | 444.02 | 74.64 | 202.18 | 80.39 | 121.79 | 0.00 | 0.00 |
Minimum of Months | 265.83 | 0.00 | 148.05 | 20.11 | 100.23 | 0.00 | 0.00 |
Maximum of Months | 615.70 | 226.23 | 238.71 | 132.98 | 135.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 135.79 | 233.19 | 118.47 | 36.71 | 81.75 | 0.00 | 0.00 |
February | 189.86 | 174.51 | 136.76 | 39.96 | 96.80 | 0.00 | 0.00 |
March | 309.90 | 86.41 | 174.65 | 56.19 | 118.46 | 0.00 | 0.00 |
April | 495.15 | 15.05 | 207.40 | 79.78 | 127.62 | 0.00 | 0.00 |
May | 605.93 | 0.06 | 202.50 | 69.52 | 132.98 | 0.00 | 0.00 |
June | 615.18 | 0.63 | 194.34 | 60.56 | 133.77 | 0.00 | 0.00 |
July | 513.79 | 0.01 | 154.51 | 22.49 | 132.02 | 0.00 | 0.00 |
August | 440.17 | 0.00 | 141.83 | 18.31 | 123.52 | 0.00 | 0.00 |
September | 391.35 | 0.76 | 148.24 | 33.61 | 114.63 | 0.00 | 0.00 |
October | 312.88 | 54.53 | 148.16 | 47.19 | 100.97 | 0.00 | 0.00 |
November | 219.43 | 148.16 | 132.17 | 45.58 | 86.59 | 0.00 | 0.00 |
December | 140.52 | 220.53 | 114.64 | 34.65 | 79.99 | 0.00 | 0.00 |
Annual Sum or Average | 364.87 | 77.43 | 156.14 | 45.32 | 110.82 | 0.00 | 0.00 |
Minimum of Months | 135.79 | 0.00 | 114.64 | 18.31 | 79.99 | 0.00 | 0.00 |
Maximum of Months | 615.18 | 233.19 | 207.40 | 79.78 | 133.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 226.01 | 116.61 | 161.28 | 98.17 | 63.11 | 0.00 | 0.00 |
February | 236.39 | 85.16 | 153.01 | 84.99 | 68.02 | 0.00 | 0.00 |
March | 241.78 | 40.48 | 130.02 | 57.01 | 73.00 | 0.00 | 0.00 |
April | 249.50 | 6.80 | 92.69 | 26.73 | 65.96 | 0.00 | 0.00 |
May | 256.27 | 0.01 | 66.82 | 5.63 | 61.19 | 0.00 | 0.00 |
June | 251.93 | 0.22 | 60.44 | 1.05 | 59.39 | 0.00 | 0.00 |
July | 239.49 | 0.01 | 62.78 | 0.61 | 62.16 | 0.00 | 0.00 |
August | 220.37 | 0.00 | 66.19 | 2.90 | 63.29 | 0.00 | 0.00 |
September | 237.77 | 0.33 | 91.59 | 25.22 | 66.37 | 0.00 | 0.00 |
October | 308.00 | 26.37 | 155.07 | 86.97 | 68.09 | 0.00 | 0.00 |
November | 327.83 | 72.71 | 193.47 | 128.17 | 65.30 | 0.00 | 0.00 |
December | 254.02 | 112.29 | 172.11 | 107.94 | 64.17 | 0.00 | 0.00 |
Annual Sum or Average | 254.12 | 38.23 | 116.91 | 51.92 | 64.99 | 0.00 | 0.00 |
Minimum of Months | 220.37 | 0.00 | 60.44 | 0.61 | 59.39 | 0.00 | 0.00 |
Maximum of Months | 327.83 | 116.61 | 193.47 | 128.17 | 73.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.15 | 739.70 | 168.78 | 0.00 | 168.78 | 0.00 | 0.00 |
February | 185.89 | 553.61 | 200.15 | 0.00 | 200.15 | 0.00 | 0.00 |
March | 376.55 | 301.16 | 241.22 | 0.01 | 241.22 | 0.00 | 0.00 |
April | 685.21 | 86.79 | 262.92 | 1.73 | 261.20 | 0.00 | 0.00 |
May | 977.55 | 8.70 | 290.46 | 8.53 | 281.93 | 0.00 | 0.00 |
June | 1046.21 | 9.12 | 300.03 | 10.99 | 289.04 | 0.00 | 0.00 |
July | 954.21 | 1.09 | 296.81 | 5.39 | 291.43 | 0.00 | 0.00 |
August | 789.98 | 4.10 | 272.39 | 1.23 | 271.16 | 0.00 | 0.00 |
September | 600.57 | 23.89 | 242.17 | 0.03 | 242.14 | 0.00 | 0.00 |
October | 427.09 | 216.25 | 209.76 | 0.00 | 209.76 | 0.00 | 0.00 |
November | 224.68 | 464.83 | 177.67 | 0.00 | 177.67 | 0.00 | 0.00 |
December | 102.34 | 699.44 | 164.65 | 0.00 | 164.65 | 0.00 | 0.00 |
Annual Sum or Average | 539.91 | 257.87 | 235.77 | 2.34 | 233.43 | 0.00 | 0.00 |
Minimum of Months | 87.15 | 1.09 | 164.65 | 0.00 | 164.65 | 0.00 | 0.00 |
Maximum of Months | 1046.21 | 739.70 | 300.03 | 10.99 | 291.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 76.48 | 765.57 | 168.78 | 0.00 | 168.78 | 0.00 | 0.00 |
February | 173.73 | 572.36 | 200.15 | 0.00 | 200.15 | 0.00 | 0.00 |
March | 366.02 | 311.68 | 241.22 | 0.01 | 241.22 | 0.00 | 0.00 |
April | 674.90 | 91.27 | 262.92 | 1.73 | 261.20 | 0.00 | 0.00 |
May | 964.83 | 9.70 | 290.46 | 8.53 | 281.93 | 0.00 | 0.00 |
June | 1033.37 | 9.99 | 300.03 | 10.99 | 289.04 | 0.00 | 0.00 |
July | 940.66 | 1.24 | 296.81 | 5.39 | 291.43 | 0.00 | 0.00 |
August | 777.36 | 5.06 | 272.39 | 1.23 | 271.16 | 0.00 | 0.00 |
September | 589.50 | 27.67 | 242.17 | 0.03 | 242.14 | 0.00 | 0.00 |
October | 419.04 | 224.05 | 209.76 | 0.00 | 209.76 | 0.00 | 0.00 |
November | 215.01 | 478.24 | 177.67 | 0.00 | 177.67 | 0.00 | 0.00 |
December | 91.62 | 722.80 | 164.65 | 0.00 | 164.65 | 0.00 | 0.00 |
Annual Sum or Average | 528.67 | 267.08 | 235.77 | 2.34 | 233.43 | 0.00 | 0.00 |
Minimum of Months | 76.48 | 1.24 | 164.65 | 0.00 | 164.65 | 0.00 | 0.00 |
Maximum of Months | 1033.37 | 765.57 | 300.03 | 10.99 | 291.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.48 | 538.53 | 326.71 | 144.14 | 182.57 | 0.00 | 0.00 |
February | 511.47 | 420.65 | 367.59 | 154.84 | 212.75 | 0.00 | 0.00 |
March | 737.90 | 244.96 | 409.50 | 157.28 | 252.23 | 0.00 | 0.00 |
April | 1045.68 | 85.03 | 441.65 | 177.41 | 264.24 | 0.00 | 0.00 |
May | 1184.05 | 16.07 | 422.00 | 153.70 | 268.31 | 0.00 | 0.00 |
June | 1112.95 | 15.73 | 356.07 | 92.30 | 263.78 | 0.00 | 0.00 |
July | 955.44 | 3.38 | 313.50 | 48.91 | 264.59 | 0.00 | 0.00 |
August | 835.47 | 9.11 | 290.38 | 38.06 | 252.33 | 0.00 | 0.00 |
September | 778.42 | 38.49 | 317.11 | 78.33 | 238.78 | 0.00 | 0.00 |
October | 798.58 | 177.34 | 376.45 | 156.30 | 220.15 | 0.00 | 0.00 |
November | 623.94 | 351.27 | 370.52 | 178.55 | 191.96 | 0.00 | 0.00 |
December | 410.68 | 520.04 | 327.50 | 147.70 | 179.80 | 0.00 | 0.00 |
Annual Sum or Average | 780.92 | 200.78 | 359.73 | 127.02 | 232.71 | 0.00 | 0.00 |
Minimum of Months | 364.48 | 3.38 | 290.38 | 38.06 | 179.80 | 0.00 | 0.00 |
Maximum of Months | 1184.05 | 538.53 | 441.65 | 178.55 | 268.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 622.26 | 499.96 | 468.41 | 249.90 | 218.51 | 0.00 | 0.00 |
February | 685.48 | 383.65 | 458.11 | 216.35 | 241.76 | 0.00 | 0.00 |
March | 744.83 | 223.05 | 413.66 | 145.13 | 268.52 | 0.00 | 0.00 |
April | 824.87 | 66.36 | 326.09 | 68.64 | 257.45 | 0.00 | 0.00 |
May | 908.50 | 5.64 | 269.67 | 17.25 | 252.42 | 0.00 | 0.00 |
June | 919.85 | 5.33 | 256.70 | 6.44 | 250.26 | 0.00 | 0.00 |
July | 854.27 | 0.57 | 261.55 | 3.41 | 258.14 | 0.00 | 0.00 |
August | 753.67 | 2.17 | 261.87 | 7.81 | 254.06 | 0.00 | 0.00 |
September | 752.19 | 13.50 | 316.17 | 64.20 | 251.96 | 0.00 | 0.00 |
October | 915.81 | 171.90 | 466.64 | 221.39 | 245.25 | 0.00 | 0.00 |
November | 921.50 | 347.36 | 553.41 | 326.28 | 227.13 | 0.00 | 0.00 |
December | 701.07 | 481.05 | 494.55 | 274.76 | 219.80 | 0.00 | 0.00 |
Annual Sum or Average | 800.71 | 182.56 | 378.43 | 132.97 | 245.46 | 0.00 | 0.00 |
Minimum of Months | 622.26 | 0.57 | 256.70 | 3.41 | 218.51 | 0.00 | 0.00 |
Maximum of Months | 921.50 | 499.96 | 553.41 | 326.28 | 268.52 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212418E+10 | 0.108468E+10 | 0.148972E+10 | 0.906782E+09 | 0.582938E+09 | 0.00 | 0.00 |
February | 0.197448E+10 | 0.769388E+09 | 0.127657E+10 | 0.709082E+09 | 0.567484E+09 | 0.00 | 0.00 |
March | 0.214911E+10 | 0.522660E+09 | 0.120093E+10 | 0.526624E+09 | 0.674306E+09 | 0.00 | 0.00 |
April | 0.195436E+10 | 0.172181E+09 | 0.828574E+09 | 0.238951E+09 | 0.589623E+09 | 0.00 | 0.00 |
May | 0.188615E+10 | 22463770.85 | 0.617227E+09 | 51992611.18 | 0.565234E+09 | 0.00 | 0.00 |
June | 0.179531E+10 | 13447299.23 | 0.540254E+09 | 9394508.28 | 0.530860E+09 | 0.00 | 0.00 |
July | 0.174180E+10 | 1884024.05 | 0.579858E+09 | 5678298.02 | 0.574179E+09 | 0.00 | 0.00 |
August | 0.161867E+10 | 8548579.37 | 0.611396E+09 | 26794816.56 | 0.584601E+09 | 0.00 | 0.00 |
September | 0.180575E+10 | 48311117.09 | 0.818726E+09 | 0.225424E+09 | 0.593302E+09 | 0.00 | 0.00 |
October | 0.270374E+10 | 0.415654E+09 | 0.143230E+10 | 0.803332E+09 | 0.628973E+09 | 0.00 | 0.00 |
November | 0.286911E+10 | 0.777713E+09 | 0.172943E+10 | 0.114573E+10 | 0.583703E+09 | 0.00 | 0.00 |
December | 0.235500E+10 | 0.106635E+10 | 0.158973E+10 | 0.996975E+09 | 0.592752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.249777E+11 | 0.490328E+10 | 0.127147E+11 | 0.564676E+10 | 0.706796E+10 | 0.00 | 0.00 |
Minimum of Months | 0.161867E+10 | 1884024.05 | 0.540254E+09 | 5678298.02 | 0.530860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286911E+10 | 0.108468E+10 | 0.172943E+10 | 0.114573E+10 | 0.674306E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.581659E+10 | 0.336539E+10 | 0.419496E+10 | 0.255344E+10 | 0.164152E+10 | 0.00 | 0.00 |
February | 0.542827E+10 | 0.239582E+10 | 0.359473E+10 | 0.199673E+10 | 0.159800E+10 | 0.00 | 0.00 |
March | 0.596507E+10 | 0.157416E+10 | 0.338174E+10 | 0.148294E+10 | 0.189880E+10 | 0.00 | 0.00 |
April | 0.550833E+10 | 0.475082E+09 | 0.233321E+10 | 0.672871E+09 | 0.166034E+10 | 0.00 | 0.00 |
May | 0.536954E+10 | 53732172.55 | 0.173807E+10 | 0.146408E+09 | 0.159166E+10 | 0.00 | 0.00 |
June | 0.511123E+10 | 43749081.18 | 0.152132E+10 | 26454315.90 | 0.149487E+10 | 0.00 | 0.00 |
July | 0.494735E+10 | 6225053.25 | 0.163284E+10 | 15989712.82 | 0.161685E+10 | 0.00 | 0.00 |
August | 0.458735E+10 | 24870132.11 | 0.172165E+10 | 75452436.75 | 0.164620E+10 | 0.00 | 0.00 |
September | 0.505622E+10 | 0.136831E+09 | 0.230548E+10 | 0.634779E+09 | 0.167070E+10 | 0.00 | 0.00 |
October | 0.756169E+10 | 0.119757E+10 | 0.403328E+10 | 0.226213E+10 | 0.177115E+10 | 0.00 | 0.00 |
November | 0.797453E+10 | 0.233594E+10 | 0.486997E+10 | 0.322630E+10 | 0.164367E+10 | 0.00 | 0.00 |
December | 0.645884E+10 | 0.331409E+10 | 0.447657E+10 | 0.280742E+10 | 0.166915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.697850E+11 | 0.149235E+11 | 0.358038E+11 | 0.159009E+11 | 0.199029E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458735E+10 | 6225053.25 | 0.152132E+10 | 15989712.82 | 0.149487E+10 | 0.00 | 0.00 |
Maximum of Months | 0.797453E+10 | 0.336539E+10 | 0.486997E+10 | 0.322630E+10 | 0.189880E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.779987E+10 | 0.443106E+10 | 0.544949E+10 | 0.331706E+10 | 0.213242E+10 | 0.00 | 0.00 |
February | 0.729093E+10 | 0.312795E+10 | 0.466975E+10 | 0.259386E+10 | 0.207589E+10 | 0.00 | 0.00 |
March | 0.801759E+10 | 0.202474E+10 | 0.439307E+10 | 0.192642E+10 | 0.246665E+10 | 0.00 | 0.00 |
April | 0.744745E+10 | 0.602175E+09 | 0.303097E+10 | 0.874097E+09 | 0.215688E+10 | 0.00 | 0.00 |
May | 0.728156E+10 | 66505312.74 | 0.225785E+10 | 0.190192E+09 | 0.206766E+10 | 0.00 | 0.00 |
June | 0.691145E+10 | 55304816.84 | 0.197628E+10 | 34365661.88 | 0.194192E+10 | 0.00 | 0.00 |
July | 0.667589E+10 | 8174171.48 | 0.212115E+10 | 20771546.94 | 0.210038E+10 | 0.00 | 0.00 |
August | 0.618425E+10 | 30228318.28 | 0.223652E+10 | 98017009.38 | 0.213850E+10 | 0.00 | 0.00 |
September | 0.678894E+10 | 0.162168E+09 | 0.299495E+10 | 0.824615E+09 | 0.217033E+10 | 0.00 | 0.00 |
October | 0.101004E+11 | 0.152269E+10 | 0.523946E+10 | 0.293864E+10 | 0.230082E+10 | 0.00 | 0.00 |
November | 0.106491E+11 | 0.301810E+10 | 0.632636E+10 | 0.419114E+10 | 0.213522E+10 | 0.00 | 0.00 |
December | 0.864958E+10 | 0.435441E+10 | 0.581531E+10 | 0.364699E+10 | 0.216832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.937970E+11 | 0.194035E+11 | 0.465112E+11 | 0.206562E+11 | 0.258550E+11 | 0.00 | 0.00 |
Minimum of Months | 0.618425E+10 | 8174171.48 | 0.197628E+10 | 20771546.94 | 0.194192E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106491E+11 | 0.443106E+10 | 0.632636E+10 | 0.419114E+10 | 0.246665E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.723951E+09 | 0.620042E+09 | 0.547266E+09 | 0.277622E+09 | 0.269644E+09 | 0.00 | 0.00 |
February | 0.775476E+09 | 0.414152E+09 | 0.514080E+09 | 0.236876E+09 | 0.277204E+09 | 0.00 | 0.00 |
March | 0.111785E+10 | 0.228543E+09 | 0.612938E+09 | 0.254619E+09 | 0.358319E+09 | 0.00 | 0.00 |
April | 0.143803E+10 | 44528546.16 | 0.604034E+09 | 0.253394E+09 | 0.350640E+09 | 0.00 | 0.00 |
May | 0.165127E+10 | 579772.72 | 0.553274E+09 | 0.193215E+09 | 0.360059E+09 | 0.00 | 0.00 |
June | 0.159270E+10 | 2010540.56 | 0.499442E+09 | 0.154767E+09 | 0.344674E+09 | 0.00 | 0.00 |
July | 0.137918E+10 | 110741.38 | 0.414927E+09 | 59310681.75 | 0.355616E+09 | 0.00 | 0.00 |
August | 0.121361E+10 | 0.00 | 0.396532E+09 | 53871508.10 | 0.342661E+09 | 0.00 | 0.00 |
September | 0.115474E+10 | 3260395.80 | 0.456453E+09 | 0.131681E+09 | 0.324772E+09 | 0.00 | 0.00 |
October | 0.122146E+10 | 0.152955E+09 | 0.599748E+09 | 0.285224E+09 | 0.314524E+09 | 0.00 | 0.00 |
November | 0.105038E+10 | 0.382563E+09 | 0.618741E+09 | 0.344678E+09 | 0.274063E+09 | 0.00 | 0.00 |
December | 0.779252E+09 | 0.594040E+09 | 0.558379E+09 | 0.289928E+09 | 0.268452E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140979E+11 | 0.244278E+10 | 0.637582E+10 | 0.253519E+10 | 0.384063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.723951E+09 | 0.00 | 0.396532E+09 | 53871508.10 | 0.268452E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165127E+10 | 0.620042E+09 | 0.618741E+09 | 0.344678E+09 | 0.360059E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371859E+09 | 0.636945E+09 | 0.317306E+09 | 98336017.03 | 0.218970E+09 | 0.00 | 0.00 |
February | 0.468605E+09 | 0.429541E+09 | 0.330854E+09 | 96678795.88 | 0.234175E+09 | 0.00 | 0.00 |
March | 0.839772E+09 | 0.241691E+09 | 0.467795E+09 | 0.150499E+09 | 0.317296E+09 | 0.00 | 0.00 |
April | 0.129097E+10 | 45961093.28 | 0.537570E+09 | 0.206789E+09 | 0.330781E+09 | 0.00 | 0.00 |
May | 0.162477E+10 | 597956.97 | 0.542379E+09 | 0.186200E+09 | 0.356179E+09 | 0.00 | 0.00 |
June | 0.160032E+10 | 2110426.90 | 0.503723E+09 | 0.156979E+09 | 0.346744E+09 | 0.00 | 0.00 |
July | 0.137775E+10 | 110703.38 | 0.413852E+09 | 60248803.13 | 0.353604E+09 | 0.00 | 0.00 |
August | 0.118066E+10 | 0.00 | 0.379876E+09 | 49046163.24 | 0.330830E+09 | 0.00 | 0.00 |
September | 0.101679E+10 | 3122091.26 | 0.384250E+09 | 87121445.75 | 0.297129E+09 | 0.00 | 0.00 |
October | 0.843499E+09 | 0.159383E+09 | 0.396820E+09 | 0.126392E+09 | 0.270428E+09 | 0.00 | 0.00 |
November | 0.572699E+09 | 0.397917E+09 | 0.342593E+09 | 0.118147E+09 | 0.224445E+09 | 0.00 | 0.00 |
December | 0.380819E+09 | 0.605590E+09 | 0.307065E+09 | 92808591.25 | 0.214256E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115685E+11 | 0.252297E+10 | 0.492408E+10 | 0.142925E+10 | 0.349484E+10 | 0.00 | 0.00 |
Minimum of Months | 0.371859E+09 | 0.00 | 0.307065E+09 | 49046163.24 | 0.214256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162477E+10 | 0.636945E+09 | 0.542379E+09 | 0.206789E+09 | 0.356179E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297225E+09 | 0.250097E+09 | 0.235588E+09 | 0.143401E+09 | 92187752.51 | 0.00 | 0.00 |
February | 0.279855E+09 | 0.182470E+09 | 0.201880E+09 | 0.112136E+09 | 89743903.77 | 0.00 | 0.00 |
March | 0.310829E+09 | 0.125879E+09 | 0.189919E+09 | 83281513.00 | 0.106637E+09 | 0.00 | 0.00 |
April | 0.287299E+09 | 47177735.33 | 0.131034E+09 | 37788285.21 | 93245487.88 | 0.00 | 0.00 |
May | 0.274331E+09 | 11372141.85 | 97610893.83 | 8222230.58 | 89388663.25 | 0.00 | 0.00 |
June | 0.256139E+09 | 8067285.56 | 85438186.34 | 1485669.05 | 83952517.29 | 0.00 | 0.00 |
July | 0.241455E+09 | 3504138.15 | 91700827.48 | 897979.05 | 90802848.43 | 0.00 | 0.00 |
August | 0.223477E+09 | 9404617.35 | 96688257.17 | 4237393.64 | 92450863.53 | 0.00 | 0.00 |
September | 0.258088E+09 | 27412980.44 | 0.129476E+09 | 35649088.28 | 93826807.71 | 0.00 | 0.00 |
October | 0.407062E+09 | 98220038.66 | 0.226509E+09 | 0.127041E+09 | 99468018.09 | 0.00 | 0.00 |
November | 0.429386E+09 | 0.171764E+09 | 0.273497E+09 | 0.181188E+09 | 92308884.53 | 0.00 | 0.00 |
December | 0.335423E+09 | 0.242727E+09 | 0.251404E+09 | 0.157664E+09 | 93739704.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.360057E+10 | 0.117810E+10 | 0.201074E+10 | 0.892992E+09 | 0.111775E+10 | 0.00 | 0.00 |
Minimum of Months | 0.223477E+09 | 3504138.15 | 85438186.34 | 897979.05 | 83952517.29 | 0.00 | 0.00 |
Maximum of Months | 0.429386E+09 | 0.250097E+09 | 0.273497E+09 | 0.181188E+09 | 0.106637E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39125764.28 | 0.184652E+09 | 51673856.20 | 0.00 | 51673856.20 | 0.00 | 0.00 |
February | 67129299.72 | 0.119946E+09 | 55346461.98 | 0.00 | 55346461.98 | 0.00 | 0.00 |
March | 0.140392E+09 | 62318490.13 | 73852146.28 | 2523.53 | 73849622.74 | 0.00 | 0.00 |
April | 0.246994E+09 | 9700296.26 | 77899067.29 | 512036.41 | 77387030.88 | 0.00 | 0.00 |
May | 0.363829E+09 | 13753.34 | 88925968.83 | 2612029.53 | 86313939.30 | 0.00 | 0.00 |
June | 0.373770E+09 | 219934.21 | 88891777.18 | 3255801.56 | 85635975.62 | 0.00 | 0.00 |
July | 0.359374E+09 | 10391.78 | 90871340.81 | 1648873.28 | 89222467.53 | 0.00 | 0.00 |
August | 0.306004E+09 | 0.00 | 83393733.81 | 378010.56 | 83015723.25 | 0.00 | 0.00 |
September | 0.235440E+09 | 356687.78 | 71748738.01 | 8381.02 | 71740357.00 | 0.00 | 0.00 |
October | 0.157735E+09 | 38726058.31 | 64219827.08 | 0.00 | 64219827.08 | 0.00 | 0.00 |
November | 83853508.10 | 0.106657E+09 | 52640156.97 | 0.00 | 52640156.97 | 0.00 | 0.00 |
December | 44620116.43 | 0.174075E+09 | 50408770.56 | 0.00 | 50408770.56 | 0.00 | 0.00 |
Annual Sum or Average | 0.241827E+10 | 0.696676E+09 | 0.849872E+09 | 8417655.89 | 0.841454E+09 | 0.00 | 0.00 |
Minimum of Months | 39125764.28 | 0.00 | 50408770.56 | 0.00 | 50408770.56 | 0.00 | 0.00 |
Maximum of Months | 0.373770E+09 | 0.184652E+09 | 90871340.81 | 3255801.56 | 89222467.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704204E+09 | 0.595291E+09 | 0.552533E+09 | 0.282683E+09 | 0.269850E+09 | 0.00 | 0.00 |
February | 0.790833E+09 | 0.395529E+09 | 0.536275E+09 | 0.257403E+09 | 0.278872E+09 | 0.00 | 0.00 |
March | 0.112077E+10 | 0.215229E+09 | 0.621004E+09 | 0.262695E+09 | 0.358309E+09 | 0.00 | 0.00 |
April | 0.144301E+10 | 41955978.55 | 0.605636E+09 | 0.253237E+09 | 0.352399E+09 | 0.00 | 0.00 |
May | 0.168132E+10 | 456757.84 | 0.570624E+09 | 0.209352E+09 | 0.361272E+09 | 0.00 | 0.00 |
June | 0.152357E+10 | 1905584.18 | 0.459356E+09 | 0.118519E+09 | 0.340838E+09 | 0.00 | 0.00 |
July | 0.138669E+10 | 115626.61 | 0.420400E+09 | 65036928.96 | 0.355363E+09 | 0.00 | 0.00 |
August | 0.121287E+10 | 0.00 | 0.397228E+09 | 53379687.18 | 0.343848E+09 | 0.00 | 0.00 |
September | 0.113868E+10 | 3011855.97 | 0.447095E+09 | 0.123805E+09 | 0.323290E+09 | 0.00 | 0.00 |
October | 0.122625E+10 | 0.147479E+09 | 0.605629E+09 | 0.288744E+09 | 0.316885E+09 | 0.00 | 0.00 |
November | 0.103114E+10 | 0.367427E+09 | 0.618282E+09 | 0.344678E+09 | 0.273604E+09 | 0.00 | 0.00 |
December | 0.770485E+09 | 0.579648E+09 | 0.564262E+09 | 0.296361E+09 | 0.267901E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140298E+11 | 0.234805E+10 | 0.639833E+10 | 0.255590E+10 | 0.384243E+10 | 0.00 | 0.00 |
Minimum of Months | 0.704204E+09 | 0.00 | 0.397228E+09 | 53379687.18 | 0.267901E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168132E+10 | 0.595291E+09 | 0.621004E+09 | 0.344678E+09 | 0.361272E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.330125E+09 | 0.586330E+09 | 0.322573E+09 | 0.103397E+09 | 0.219176E+09 | 0.00 | 0.00 |
February | 0.471722E+09 | 0.398831E+09 | 0.353049E+09 | 0.117206E+09 | 0.235844E+09 | 0.00 | 0.00 |
March | 0.835260E+09 | 0.224905E+09 | 0.475862E+09 | 0.158576E+09 | 0.317286E+09 | 0.00 | 0.00 |
April | 0.129345E+10 | 43213711.04 | 0.539173E+09 | 0.206632E+09 | 0.332540E+09 | 0.00 | 0.00 |
May | 0.165467E+10 | 475162.39 | 0.559729E+09 | 0.202337E+09 | 0.357392E+09 | 0.00 | 0.00 |
June | 0.153118E+10 | 1973236.13 | 0.463637E+09 | 0.120731E+09 | 0.342907E+09 | 0.00 | 0.00 |
July | 0.138524E+10 | 115591.53 | 0.419326E+09 | 65975050.34 | 0.353351E+09 | 0.00 | 0.00 |
August | 0.117990E+10 | 0.00 | 0.380572E+09 | 48554342.32 | 0.332018E+09 | 0.00 | 0.00 |
September | 0.100059E+10 | 2811295.98 | 0.374892E+09 | 79245245.73 | 0.295646E+09 | 0.00 | 0.00 |
October | 0.843211E+09 | 0.151309E+09 | 0.402701E+09 | 0.129912E+09 | 0.272789E+09 | 0.00 | 0.00 |
November | 0.541950E+09 | 0.373374E+09 | 0.342134E+09 | 0.118148E+09 | 0.223986E+09 | 0.00 | 0.00 |
December | 0.357603E+09 | 0.574496E+09 | 0.312947E+09 | 99241778.46 | 0.213705E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114249E+11 | 0.235783E+10 | 0.494659E+10 | 0.144995E+10 | 0.349664E+10 | 0.00 | 0.00 |
Minimum of Months | 0.330125E+09 | 0.00 | 0.312947E+09 | 48554342.32 | 0.213705E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165467E+10 | 0.586330E+09 | 0.559729E+09 | 0.206632E+09 | 0.357392E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.817472E+09 | 0.757381E+09 | 0.622397E+09 | 0.310709E+09 | 0.311688E+09 | 0.00 | 0.00 |
February | 0.836525E+09 | 0.524800E+09 | 0.557316E+09 | 0.242967E+09 | 0.314349E+09 | 0.00 | 0.00 |
March | 0.105263E+10 | 0.331361E+09 | 0.571489E+09 | 0.180453E+09 | 0.391036E+09 | 0.00 | 0.00 |
April | 0.119293E+10 | 92722343.07 | 0.452669E+09 | 82985948.03 | 0.369683E+09 | 0.00 | 0.00 |
May | 0.141646E+10 | 6859119.61 | 0.404139E+09 | 23473818.96 | 0.380665E+09 | 0.00 | 0.00 |
June | 0.140603E+10 | 6851706.17 | 0.377690E+09 | 10272189.60 | 0.367418E+09 | 0.00 | 0.00 |
July | 0.134857E+10 | 913244.34 | 0.395548E+09 | 5517683.30 | 0.390030E+09 | 0.00 | 0.00 |
August | 0.118213E+10 | 1647693.21 | 0.390155E+09 | 10000151.27 | 0.380155E+09 | 0.00 | 0.00 |
September | 0.109431E+10 | 16142087.02 | 0.435970E+09 | 77259816.72 | 0.358710E+09 | 0.00 | 0.00 |
October | 0.126657E+10 | 0.257972E+09 | 0.629903E+09 | 0.275262E+09 | 0.354641E+09 | 0.00 | 0.00 |
November | 0.117544E+10 | 0.522950E+09 | 0.706628E+09 | 0.392584E+09 | 0.314044E+09 | 0.00 | 0.00 |
December | 0.910867E+09 | 0.741798E+09 | 0.653924E+09 | 0.341614E+09 | 0.312310E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136999E+11 | 0.326140E+10 | 0.619783E+10 | 0.195310E+10 | 0.424473E+10 | 0.00 | 0.00 |
Minimum of Months | 0.817472E+09 | 913244.34 | 0.377690E+09 | 5517683.30 | 0.311688E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141646E+10 | 0.757381E+09 | 0.706628E+09 | 0.392584E+09 | 0.391036E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711999E+09 | 0.605927E+09 | 0.547266E+09 | 0.277622E+09 | 0.269644E+09 | 0.00 | 0.00 |
February | 0.762959E+09 | 0.402688E+09 | 0.514080E+09 | 0.236876E+09 | 0.277204E+09 | 0.00 | 0.00 |
March | 0.110308E+10 | 0.216201E+09 | 0.612938E+09 | 0.254619E+09 | 0.358319E+09 | 0.00 | 0.00 |
April | 0.142732E+10 | 37955177.96 | 0.604034E+09 | 0.253394E+09 | 0.350640E+09 | 0.00 | 0.00 |
May | 0.164908E+10 | 155649.27 | 0.553274E+09 | 0.193215E+09 | 0.360059E+09 | 0.00 | 0.00 |
June | 0.158708E+10 | 1595996.93 | 0.499442E+09 | 0.154767E+09 | 0.344674E+09 | 0.00 | 0.00 |
July | 0.137783E+10 | 39331.02 | 0.414927E+09 | 59310681.75 | 0.355616E+09 | 0.00 | 0.00 |
August | 0.121150E+10 | 0.00 | 0.396532E+09 | 53871508.10 | 0.342661E+09 | 0.00 | 0.00 |
September | 0.115051E+10 | 2083419.77 | 0.456453E+09 | 0.131681E+09 | 0.324772E+09 | 0.00 | 0.00 |
October | 0.121072E+10 | 0.140644E+09 | 0.599748E+09 | 0.285224E+09 | 0.314524E+09 | 0.00 | 0.00 |
November | 0.104033E+10 | 0.367887E+09 | 0.618741E+09 | 0.344678E+09 | 0.274063E+09 | 0.00 | 0.00 |
December | 0.770198E+09 | 0.578654E+09 | 0.558379E+09 | 0.289928E+09 | 0.268452E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140026E+11 | 0.235383E+10 | 0.637582E+10 | 0.253519E+10 | 0.384063E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711999E+09 | 0.00 | 0.396532E+09 | 53871508.10 | 0.268452E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164908E+10 | 0.605927E+09 | 0.618741E+09 | 0.344678E+09 | 0.360059E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.363708E+09 | 0.624569E+09 | 0.317306E+09 | 98336017.03 | 0.218970E+09 | 0.00 | 0.00 |
February | 0.459318E+09 | 0.422163E+09 | 0.330854E+09 | 96678795.88 | 0.234175E+09 | 0.00 | 0.00 |
March | 0.830035E+09 | 0.231435E+09 | 0.467795E+09 | 0.150499E+09 | 0.317296E+09 | 0.00 | 0.00 |
April | 0.128343E+10 | 39012105.79 | 0.537570E+09 | 0.206789E+09 | 0.330781E+09 | 0.00 | 0.00 |
May | 0.162292E+10 | 167067.69 | 0.542379E+09 | 0.186200E+09 | 0.356179E+09 | 0.00 | 0.00 |
June | 0.159455E+10 | 1642146.88 | 0.503723E+09 | 0.156979E+09 | 0.346744E+09 | 0.00 | 0.00 |
July | 0.137613E+10 | 39322.26 | 0.413852E+09 | 60248803.13 | 0.353604E+09 | 0.00 | 0.00 |
August | 0.117896E+10 | 0.00 | 0.379876E+09 | 49046163.24 | 0.330830E+09 | 0.00 | 0.00 |
September | 0.101439E+10 | 1975425.17 | 0.384250E+09 | 87121445.75 | 0.297129E+09 | 0.00 | 0.00 |
October | 0.838013E+09 | 0.146063E+09 | 0.396820E+09 | 0.126392E+09 | 0.270428E+09 | 0.00 | 0.00 |
November | 0.568770E+09 | 0.384038E+09 | 0.342593E+09 | 0.118147E+09 | 0.224445E+09 | 0.00 | 0.00 |
December | 0.376379E+09 | 0.590668E+09 | 0.307065E+09 | 92808591.25 | 0.214256E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115066E+11 | 0.244177E+10 | 0.492408E+10 | 0.142925E+10 | 0.349484E+10 | 0.00 | 0.00 |
Minimum of Months | 0.363708E+09 | 0.00 | 0.307065E+09 | 49046163.24 | 0.214256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162292E+10 | 0.624569E+09 | 0.542379E+09 | 0.206789E+09 | 0.356179E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.605354E+09 | 0.312324E+09 | 0.431977E+09 | 0.262941E+09 | 0.169036E+09 | 0.00 | 0.00 |
February | 0.571870E+09 | 0.206011E+09 | 0.370169E+09 | 0.205613E+09 | 0.164555E+09 | 0.00 | 0.00 |
March | 0.647595E+09 | 0.108424E+09 | 0.348237E+09 | 0.152706E+09 | 0.195531E+09 | 0.00 | 0.00 |
April | 0.646716E+09 | 17614650.17 | 0.240265E+09 | 69288960.48 | 0.170976E+09 | 0.00 | 0.00 |
May | 0.686405E+09 | 17647.94 | 0.178980E+09 | 15076360.47 | 0.163904E+09 | 0.00 | 0.00 |
June | 0.652997E+09 | 570002.46 | 0.156660E+09 | 2724136.95 | 0.153936E+09 | 0.00 | 0.00 |
July | 0.641449E+09 | 14293.49 | 0.168144E+09 | 1646542.96 | 0.166497E+09 | 0.00 | 0.00 |
August | 0.590244E+09 | 0.00 | 0.177289E+09 | 7769725.43 | 0.169519E+09 | 0.00 | 0.00 |
September | 0.616312E+09 | 848971.26 | 0.237408E+09 | 65366508.58 | 0.172042E+09 | 0.00 | 0.00 |
October | 0.824959E+09 | 70619372.10 | 0.415329E+09 | 0.232943E+09 | 0.182386E+09 | 0.00 | 0.00 |
November | 0.849728E+09 | 0.188475E+09 | 0.501487E+09 | 0.332228E+09 | 0.169258E+09 | 0.00 | 0.00 |
December | 0.680380E+09 | 0.300758E+09 | 0.460976E+09 | 0.289094E+09 | 0.171882E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.801401E+10 | 0.120568E+10 | 0.368692E+10 | 0.163740E+10 | 0.204952E+10 | 0.00 | 0.00 |
Minimum of Months | 0.571870E+09 | 0.00 | 0.156660E+09 | 1646542.96 | 0.153936E+09 | 0.00 | 0.00 |
Maximum of Months | 0.849728E+09 | 0.312324E+09 | 0.501487E+09 | 0.332228E+09 | 0.195531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233416E+09 | 0.198120E+10 | 0.452069E+09 | 0.00 | 0.452069E+09 | 0.00 | 0.00 |
February | 0.449704E+09 | 0.133929E+10 | 0.484199E+09 | 0.00 | 0.484199E+09 | 0.00 | 0.00 |
March | 0.100854E+10 | 0.806622E+09 | 0.646096E+09 | 22077.16 | 0.646074E+09 | 0.00 | 0.00 |
April | 0.177606E+10 | 0.224966E+09 | 0.681501E+09 | 4479555.11 | 0.677021E+09 | 0.00 | 0.00 |
May | 0.261826E+10 | 23299898.28 | 0.777970E+09 | 22851363.71 | 0.755118E+09 | 0.00 | 0.00 |
June | 0.271177E+10 | 23639417.79 | 0.777671E+09 | 28483409.07 | 0.749187E+09 | 0.00 | 0.00 |
July | 0.255574E+10 | 2911973.87 | 0.794989E+09 | 14425182.63 | 0.780564E+09 | 0.00 | 0.00 |
August | 0.211589E+10 | 10982104.15 | 0.729571E+09 | 3307028.78 | 0.726264E+09 | 0.00 | 0.00 |
September | 0.155668E+10 | 61923490.57 | 0.627694E+09 | 73321.39 | 0.627621E+09 | 0.00 | 0.00 |
October | 0.114393E+10 | 0.579206E+09 | 0.561828E+09 | 0.00 | 0.561828E+09 | 0.00 | 0.00 |
November | 0.582373E+09 | 0.120484E+10 | 0.460523E+09 | 0.00 | 0.460523E+09 | 0.00 | 0.00 |
December | 0.274109E+09 | 0.187339E+10 | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170265E+11 | 0.813227E+10 | 0.743511E+10 | 73641937.85 | 0.736147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.233416E+09 | 2911973.87 | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.00 | 0.00 |
Maximum of Months | 0.271177E+10 | 0.198120E+10 | 0.794989E+09 | 28483409.07 | 0.780564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204856E+09 | 0.205050E+10 | 0.452069E+09 | 0.00 | 0.452069E+09 | 0.00 | 0.00 |
February | 0.420283E+09 | 0.138466E+10 | 0.484199E+09 | 0.00 | 0.484199E+09 | 0.00 | 0.00 |
March | 0.980345E+09 | 0.834793E+09 | 0.646096E+09 | 22077.16 | 0.646074E+09 | 0.00 | 0.00 |
April | 0.174934E+10 | 0.236561E+09 | 0.681501E+09 | 4479555.11 | 0.677021E+09 | 0.00 | 0.00 |
May | 0.258420E+10 | 25979545.28 | 0.777970E+09 | 22851363.71 | 0.755118E+09 | 0.00 | 0.00 |
June | 0.267849E+10 | 25896336.45 | 0.777671E+09 | 28483409.07 | 0.749187E+09 | 0.00 | 0.00 |
July | 0.251947E+10 | 3324037.09 | 0.794989E+09 | 14425182.63 | 0.780564E+09 | 0.00 | 0.00 |
August | 0.208209E+10 | 13544828.99 | 0.729571E+09 | 3307028.78 | 0.726264E+09 | 0.00 | 0.00 |
September | 0.152800E+10 | 71722315.21 | 0.627694E+09 | 73321.39 | 0.627621E+09 | 0.00 | 0.00 |
October | 0.112236E+10 | 0.600104E+09 | 0.561828E+09 | 0.00 | 0.561828E+09 | 0.00 | 0.00 |
November | 0.557306E+09 | 0.123960E+10 | 0.460523E+09 | 0.00 | 0.460523E+09 | 0.00 | 0.00 |
December | 0.245383E+09 | 0.193594E+10 | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166721E+11 | 0.842263E+10 | 0.743511E+10 | 73641937.85 | 0.736147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.204856E+09 | 3324037.09 | 0.441002E+09 | 0.00 | 0.441002E+09 | 0.00 | 0.00 |
Maximum of Months | 0.267849E+10 | 0.205050E+10 | 0.794989E+09 | 28483409.07 | 0.780564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.976217E+09 | 0.144239E+10 | 0.875069E+09 | 0.386065E+09 | 0.489004E+09 | 0.00 | 0.00 |
February | 0.123736E+10 | 0.101763E+10 | 0.889284E+09 | 0.374592E+09 | 0.514692E+09 | 0.00 | 0.00 |
March | 0.197638E+10 | 0.656098E+09 | 0.109681E+10 | 0.421249E+09 | 0.675563E+09 | 0.00 | 0.00 |
April | 0.271040E+10 | 0.220408E+09 | 0.114475E+10 | 0.459840E+09 | 0.684906E+09 | 0.00 | 0.00 |
May | 0.317136E+10 | 43041750.04 | 0.113029E+10 | 0.411661E+09 | 0.718628E+09 | 0.00 | 0.00 |
June | 0.288477E+10 | 40769084.81 | 0.922944E+09 | 0.239233E+09 | 0.683711E+09 | 0.00 | 0.00 |
July | 0.255905E+10 | 9060398.65 | 0.839682E+09 | 0.131003E+09 | 0.708680E+09 | 0.00 | 0.00 |
August | 0.223772E+10 | 24388995.01 | 0.777761E+09 | 0.101927E+09 | 0.675834E+09 | 0.00 | 0.00 |
September | 0.201767E+10 | 99773444.51 | 0.821946E+09 | 0.203039E+09 | 0.618907E+09 | 0.00 | 0.00 |
October | 0.213891E+10 | 0.474976E+09 | 0.100829E+10 | 0.418638E+09 | 0.589647E+09 | 0.00 | 0.00 |
November | 0.161725E+10 | 0.910503E+09 | 0.960377E+09 | 0.462809E+09 | 0.497568E+09 | 0.00 | 0.00 |
December | 0.109998E+10 | 0.139288E+10 | 0.877173E+09 | 0.395589E+09 | 0.481584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246271E+11 | 0.633192E+10 | 0.113444E+11 | 0.400565E+10 | 0.733872E+10 | 0.00 | 0.00 |
Minimum of Months | 0.976217E+09 | 9060398.65 | 0.777761E+09 | 0.101927E+09 | 0.481584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.317136E+10 | 0.144239E+10 | 0.114475E+10 | 0.462809E+09 | 0.718628E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166666E+10 | 0.133909E+10 | 0.125459E+10 | 0.669330E+09 | 0.585261E+09 | 0.00 | 0.00 |
February | 0.165831E+10 | 0.928133E+09 | 0.110827E+10 | 0.523400E+09 | 0.584869E+09 | 0.00 | 0.00 |
March | 0.199496E+10 | 0.597430E+09 | 0.110794E+10 | 0.388728E+09 | 0.719210E+09 | 0.00 | 0.00 |
April | 0.213807E+10 | 0.171997E+09 | 0.845227E+09 | 0.177914E+09 | 0.667312E+09 | 0.00 | 0.00 |
May | 0.243332E+10 | 15105274.16 | 0.722293E+09 | 46211168.96 | 0.676082E+09 | 0.00 | 0.00 |
June | 0.238426E+10 | 13812817.66 | 0.665374E+09 | 16698603.68 | 0.648675E+09 | 0.00 | 0.00 |
July | 0.228807E+10 | 1519612.39 | 0.700542E+09 | 9136343.40 | 0.691406E+09 | 0.00 | 0.00 |
August | 0.201862E+10 | 5816294.56 | 0.701396E+09 | 20911904.94 | 0.680484E+09 | 0.00 | 0.00 |
September | 0.194969E+10 | 34981042.95 | 0.819510E+09 | 0.166419E+09 | 0.653091E+09 | 0.00 | 0.00 |
October | 0.245291E+10 | 0.460415E+09 | 0.124984E+10 | 0.592969E+09 | 0.656868E+09 | 0.00 | 0.00 |
November | 0.238854E+10 | 0.900361E+09 | 0.143443E+10 | 0.845705E+09 | 0.588725E+09 | 0.00 | 0.00 |
December | 0.187776E+10 | 0.128845E+10 | 0.132462E+10 | 0.735904E+09 | 0.588711E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.252512E+11 | 0.575711E+10 | 0.119340E+11 | 0.419333E+10 | 0.774069E+10 | 0.00 | 0.00 |
Minimum of Months | 0.165831E+10 | 1519612.39 | 0.665374E+09 | 9136343.40 | 0.584869E+09 | 0.00 | 0.00 |
Maximum of Months | 0.245291E+10 | 0.133909E+10 | 0.143443E+10 | 0.845705E+09 | 0.719210E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770478E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161992046.5 | 81.21 | 0.00 | 0.00 |
February | 0.696209E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146129406.2 | 81.21 | 0.00 | 0.00 |
March | 0.770298E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161525006.7 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156213710.3 | 81.21 | 0.00 | 0.00 |
May | 0.770420E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161407358.9 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203447.0 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161409065.9 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408827.9 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156207315.0 | 81.21 | 0.00 | 0.00 |
October | 0.770287E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161440915.7 | 81.21 | 0.00 | 0.00 |
November | 0.744885E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156421684.4 | 81.21 | 0.00 | 0.00 |
December | 0.771280E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161941574.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907427E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190230E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696209E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161992046.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771280E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146129406.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.103860E+12 | -0.102123E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173741E+10 | 81.25 | 0.00 | 0.00 |
February | 0.925506E+11 | -0.909801E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157049E+10 | 81.25 | 0.00 | 0.00 |
March | 0.982798E+11 | -0.965412E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173861E+10 | 81.24 | 0.00 | 0.00 |
April | 0.892337E+11 | -0.875551E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167855E+10 | 81.24 | 0.00 | 0.00 |
May | 0.859620E+11 | -0.842326E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172938E+10 | 81.24 | 0.00 | 0.00 |
June | 0.785976E+11 | -0.769265E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167104E+10 | 81.24 | 0.00 | 0.00 |
July | 0.792690E+11 | -0.775435E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172553E+10 | 81.24 | 0.00 | 0.00 |
August | 0.806709E+11 | -0.789456E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172524E+10 | 81.23 | 0.00 | 0.00 |
September | 0.822589E+11 | -0.805893E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166954E+10 | 81.23 | 0.00 | 0.00 |
October | 0.911025E+11 | -0.893771E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172542E+10 | 81.24 | 0.00 | 0.00 |
November | 0.941875E+11 | -0.925175E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166999E+10 | 81.25 | 0.00 | 0.00 |
December | 0.101992E+12 | -0.100264E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172829E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.107796E+13 | -0.105760E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203695E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.785976E+11 | -0.102123E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.173861E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.103860E+12 | -0.769265E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157049E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.570840E+11 | -0.556060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147799E+10 | 58.98 | 0.00 | 0.00 |
February | 0.504844E+11 | -0.491476E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.133674E+10 | 58.98 | 0.00 | 0.00 |
March | 0.523148E+11 | -0.508350E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147982E+10 | 58.98 | 0.00 | 0.00 |
April | 0.455257E+11 | -0.440990E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142670E+10 | 58.98 | 0.00 | 0.00 |
May | 0.416528E+11 | -0.401859E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146689E+10 | 58.97 | 0.00 | 0.00 |
June | 0.363537E+11 | -0.349376E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141612E+10 | 58.97 | 0.00 | 0.00 |
July | 0.358477E+11 | -0.343864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146134E+10 | 58.97 | 0.00 | 0.00 |
August | 0.370947E+11 | -0.356333E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146133E+10 | 58.97 | 0.00 | 0.00 |
September | 0.395001E+11 | -0.380859E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141425E+10 | 58.97 | 0.00 | 0.00 |
October | 0.460660E+11 | -0.446044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146152E+10 | 58.98 | 0.00 | 0.00 |
November | 0.497780E+11 | -0.483634E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141460E+10 | 58.98 | 0.00 | 0.00 |
December | 0.554623E+11 | -0.539970E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146533E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.547164E+12 | -0.529882E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.172826E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.358477E+11 | -0.556060E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.147982E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.570840E+11 | -0.343864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.133674E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.87 | 0.86 | 01-JAN-07:00 | 5571.27 | 35.79 | 302.00 | 291.83 | 755.49 | 25.84 | 286.83 | 269.17 |
February | 303.83 | 0.87 | 0.86 | 01-FEB-07:00 | 2767.98 | 27.63 | 160.33 | 278.00 | 614.51 | 22.63 | 228.67 | 242.67 |
March | 364.50 | 0.87 | 0.86 | 01-MAR-07:00 | 1285.65 | 20.17 | 7.17 | 331.33 | 503.96 | 21.69 | 269.00 | 285.67 |
April | 379.83 | 0.88 | 0.86 | 01-APR-07:40 | 869.55 | 19.18 | 0.00 | 336.33 | 364.12 | 20.90 | 237.33 | 285.50 |
May | 406.00 | 0.88 | 0.86 | 01-MAY-07:30 | 735.79 | 18.60 | 0.00 | 355.67 | 308.45 | 20.35 | 184.67 | 284.17 |
June | 386.67 | 0.88 | 0.86 | 01-JUN-08:09 | 741.03 | 18.15 | 0.00 | 341.83 | 303.27 | 19.89 | 169.67 | 257.50 |
July | 379.83 | 0.88 | 0.86 | 01-JUL-07:40 | 871.00 | 18.17 | 0.00 | 340.67 | 324.46 | 19.87 | 118.33 | 260.17 |
August | 372.50 | 0.88 | 0.86 | 01-AUG-07:40 | 997.51 | 18.08 | 0.00 | 330.00 | 361.77 | 19.74 | 128.17 | 254.33 |
September | 344.33 | 0.88 | 0.86 | 01-SEP-07:49 | 1219.96 | 18.98 | 0.00 | 308.67 | 457.97 | 20.69 | 183.17 | 250.50 |
October | 347.33 | 0.88 | 0.86 | 01-OCT-07:30 | 1692.36 | 22.28 | 77.00 | 311.83 | 557.22 | 21.34 | 256.33 | 281.50 |
November | 317.83 | 0.87 | 0.86 | 01-NOV-07:30 | 6472.54 | 35.45 | 288.67 | 291.50 | 715.52 | 24.97 | 298.67 | 272.50 |
December | 315.50 | 0.87 | 0.86 | 01-DEC-07:30 | 5732.64 | 36.94 | 309.33 | 292.33 | 887.76 | 27.36 | 301.67 | 280.83 |
Annual Sum or Average | 4237.50 | 0.88 | 2260.86 | 23.57 | 1144.50 | 3810.00 | 497.74 | 21.93 | 2662.50 | 3224.50 | ||
Minimum of Months | 303.83 | 0.87 | 0.86 | 735.79 | 18.08 | 0.00 | 278.00 | 303.27 | 19.74 | 118.33 | 242.67 | |
Maximum of Months | 406.00 | 0.88 | 0.86 | 6472.54 | 36.94 | 309.33 | 355.67 | 887.76 | 27.36 | 301.67 | 285.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.27 | 0.22 | 01-JAN-07:49 | 5895.55 | 35.87 | 302.33 | 298.33 | 1076.22 | 25.83 | 284.17 | 285.67 |
February | 303.83 | 0.27 | 0.22 | 01-FEB-07:49 | 3066.38 | 27.70 | 161.00 | 285.17 | 912.96 | 22.80 | 228.50 | 264.50 |
March | 364.50 | 0.27 | 0.22 | 01-MAR-07:40 | 1531.10 | 20.62 | 63.33 | 341.00 | 748.69 | 21.98 | 281.33 | 312.67 |
April | 379.83 | 0.29 | 0.22 | 01-APR-07:10 | 1044.46 | 19.84 | 49.33 | 344.50 | 538.57 | 21.35 | 272.00 | 320.33 |
May | 406.00 | 0.29 | 0.22 | 01-MAY-06:00 | 869.86 | 19.46 | 4.50 | 369.50 | 442.11 | 20.99 | 263.50 | 335.67 |
June | 386.67 | 0.30 | 0.22 | 01-JUN-07:19 | 866.85 | 19.08 | 1.50 | 353.83 | 428.67 | 20.59 | 231.00 | 317.83 |
July | 379.83 | 0.28 | 0.22 | 01-JUL-06:49 | 996.76 | 19.16 | 0.33 | 356.33 | 449.67 | 20.62 | 187.00 | 312.67 |
August | 372.50 | 0.29 | 0.22 | 01-AUG-06:00 | 1132.63 | 19.02 | 8.67 | 344.00 | 496.23 | 20.46 | 187.67 | 301.50 |
September | 344.33 | 0.28 | 0.22 | 01-SEP-07:19 | 1406.49 | 19.73 | 55.50 | 322.17 | 643.74 | 21.23 | 214.67 | 287.83 |
October | 347.33 | 0.28 | 0.22 | 01-OCT-07:10 | 1989.98 | 22.48 | 96.33 | 318.83 | 853.44 | 21.52 | 242.67 | 300.00 |
November | 317.83 | 0.26 | 0.22 | 01-NOV-07:19 | 6847.51 | 35.48 | 288.83 | 297.67 | 1090.50 | 24.82 | 257.00 | 283.83 |
December | 315.50 | 0.26 | 0.22 | 01-DEC-07:19 | 6078.61 | 37.00 | 309.33 | 296.67 | 1231.82 | 27.25 | 298.50 | 287.83 |
Annual Sum or Average | 4237.50 | 0.28 | 2484.40 | 24.10 | 1341.00 | 3928.00 | 720.41 | 22.30 | 2948.00 | 3610.33 | ||
Minimum of Months | 303.83 | 0.26 | 0.22 | 866.85 | 19.02 | 0.33 | 285.17 | 428.67 | 20.46 | 187.00 | 264.50 | |
Maximum of Months | 406.00 | 0.30 | 0.22 | 6847.51 | 37.00 | 309.33 | 369.50 | 1231.82 | 27.25 | 298.50 | 335.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.68 | 0.60 | 01-JAN-09:00 | 380.54 | 14.81 | 0.00 | 269.67 | 186.42 | 18.18 | 0.00 | 165.33 |
February | 303.83 | 0.66 | 0.60 | 01-FEB-09:20 | 439.96 | 15.71 | 0.00 | 264.67 | 212.62 | 19.00 | 0.00 | 188.67 |
March | 364.50 | 0.64 | 0.60 | 01-MAR-08:30 | 518.94 | 16.69 | 0.00 | 330.83 | 248.95 | 19.92 | 0.00 | 272.67 |
April | 379.83 | 0.64 | 0.60 | 01-APR-07:30 | 554.95 | 16.97 | 0.00 | 345.50 | 268.79 | 20.17 | 36.67 | 310.50 |
May | 406.00 | 0.63 | 0.60 | 01-MAY-06:40 | 680.78 | 17.87 | 19.17 | 376.00 | 308.24 | 21.04 | 137.50 | 341.17 |
June | 386.67 | 0.64 | 0.60 | 01-JUN-07:30 | 778.96 | 18.09 | 26.50 | 357.33 | 334.83 | 21.53 | 157.67 | 318.50 |
July | 379.83 | 0.63 | 0.60 | 01-JUL-06:30 | 831.37 | 17.49 | 12.00 | 359.17 | 334.41 | 21.32 | 106.17 | 309.50 |
August | 372.50 | 0.64 | 0.60 | 01-AUG-06:00 | 747.14 | 16.49 | 0.00 | 343.17 | 299.18 | 19.55 | 37.00 | 286.00 |
September | 344.33 | 0.64 | 0.60 | 01-SEP-07:30 | 622.73 | 16.48 | 0.00 | 313.50 | 268.44 | 19.59 | 0.83 | 258.00 |
October | 347.33 | 0.66 | 0.60 | 01-OCT-07:49 | 450.55 | 15.61 | 0.00 | 305.33 | 222.94 | 18.88 | 0.00 | 243.00 |
November | 317.83 | 0.67 | 0.60 | 01-NOV-08:30 | 373.46 | 15.21 | 0.00 | 270.00 | 195.87 | 18.68 | 0.00 | 190.17 |
December | 315.50 | 0.68 | 0.60 | 01-DEC-09:39 | 373.70 | 14.92 | 0.00 | 264.67 | 185.99 | 18.34 | 0.00 | 159.00 |
Annual Sum or Average | 4237.50 | 0.65 | 574.48 | 16.45 | 57.67 | 3799.83 | 259.79 | 19.77 | 475.83 | 3042.50 | ||
Minimum of Months | 303.83 | 0.63 | 0.60 | 373.46 | 14.81 | 0.00 | 264.67 | 185.99 | 18.18 | 0.00 | 159.00 | |
Maximum of Months | 406.00 | 0.68 | 0.60 | 831.37 | 18.09 | 26.50 | 376.00 | 334.83 | 21.53 | 157.67 | 341.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.68 | 0.60 | 01-JAN-09:00 | 380.54 | 14.81 | 0.00 | 269.67 | 186.42 | 18.18 | 0.00 | 165.33 |
February | 303.83 | 0.66 | 0.60 | 01-FEB-09:20 | 439.96 | 15.71 | 0.00 | 264.67 | 212.62 | 19.00 | 0.00 | 188.67 |
March | 364.50 | 0.64 | 0.60 | 01-MAR-08:30 | 518.94 | 16.69 | 0.00 | 330.83 | 248.95 | 19.92 | 0.00 | 272.67 |
April | 379.83 | 0.64 | 0.60 | 01-APR-07:30 | 554.95 | 16.97 | 0.00 | 345.50 | 268.79 | 20.17 | 36.67 | 310.50 |
May | 406.00 | 0.63 | 0.60 | 01-MAY-06:40 | 680.78 | 17.87 | 19.17 | 376.00 | 308.24 | 21.04 | 137.50 | 341.17 |
June | 386.67 | 0.64 | 0.60 | 01-JUN-07:30 | 778.96 | 18.09 | 26.50 | 357.33 | 334.83 | 21.53 | 157.67 | 318.50 |
July | 379.83 | 0.63 | 0.60 | 01-JUL-06:30 | 831.37 | 17.49 | 12.00 | 359.17 | 334.41 | 21.32 | 106.17 | 309.50 |
August | 372.50 | 0.64 | 0.60 | 01-AUG-06:00 | 747.14 | 16.49 | 0.00 | 343.17 | 299.18 | 19.55 | 37.00 | 286.00 |
September | 344.33 | 0.64 | 0.60 | 01-SEP-07:30 | 622.73 | 16.48 | 0.00 | 313.50 | 268.44 | 19.59 | 0.83 | 258.00 |
October | 347.33 | 0.66 | 0.60 | 01-OCT-07:49 | 450.55 | 15.61 | 0.00 | 305.33 | 222.94 | 18.88 | 0.00 | 243.00 |
November | 317.83 | 0.67 | 0.60 | 01-NOV-08:30 | 373.46 | 15.21 | 0.00 | 270.00 | 195.87 | 18.68 | 0.00 | 190.17 |
December | 315.50 | 0.68 | 0.60 | 01-DEC-09:39 | 373.70 | 14.92 | 0.00 | 264.67 | 185.99 | 18.34 | 0.00 | 159.00 |
Annual Sum or Average | 4237.50 | 0.65 | 574.48 | 16.45 | 57.67 | 3799.83 | 259.79 | 19.77 | 475.83 | 3042.50 | ||
Minimum of Months | 303.83 | 0.63 | 0.60 | 373.46 | 14.81 | 0.00 | 264.67 | 185.99 | 18.18 | 0.00 | 159.00 | |
Maximum of Months | 406.00 | 0.68 | 0.60 | 831.37 | 18.09 | 26.50 | 376.00 | 334.83 | 21.53 | 157.67 | 341.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265306E+09 | 15947.43 | 02-JAN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136380E+09 | 17402.47 | 10-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1774407.64 | 1082.64 | 05-MAR-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3191.86 | 5.32 | 21-SEP-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 273.03 | 1.82 | 08-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66349649.03 | 18116.44 | 26-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357160E+09 | 19750.47 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357160E+09 | 19750.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715689E+09 | 1610.34 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243157E+09 | 1437.33 | 11-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69567.30 | 93.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7749248.84 | 361.52 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365488E+09 | 1437.07 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715689E+09 | 1610.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4880763.52 | 226.21 | 02-JAN-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4880763.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4880763.52 | 226.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.522211E+09 | 1096.07 | 02-JAN-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64674647.22 | 566.52 | 11-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109071E+09 | 654.30 | 23-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.695957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.522211E+09 | 1096.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223618E+09 | 560.81 | 02-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17793199.06 | 240.75 | 11-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37855490.40 | 297.24 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.223618E+09 | 560.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5844378.00 | 821.76 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2021380.77 | 545.54 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1789140.13 | 372.02 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9654898.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5844378.00 | 821.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48168839.03 | 1672.96 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34091472.85 | 2021.33 | 10-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 82260311.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48168839.03 | 2021.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.738347E+09 | 4650.43 | 02-JAN-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11362484.26 | 1360.32 | 11-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25620789.69 | 1976.20 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.738347E+09 | 4650.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189739E+10 | 3693.62 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.470750E+09 | 2998.26 | 11-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14267443.89 | 870.01 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107113E+10 | 3519.12 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189739E+10 | 3693.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4715.37 | 0.31 | 12-JAN-01:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8788.34 | 0.31 | 06-FEB-19:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10374.51 | 0.31 | 22-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5331.82 | 0.31 | 08-APR-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13983.61 | 0.31 | 09-MAY-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15485.33 | 0.31 | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24981.23 | 0.31 | 04-JUL-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28548.53 | 0.31 | 04-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22228.37 | 0.31 | 26-SEP-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11096.88 | 0.31 | 07-OCT-01:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14415.29 | 0.31 | 19-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6000.53 | 0.31 | 07-DEC-16:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 165949.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4715.37 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28548.53 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.599313E+09 | 4136.23 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156789E+09 | 4038.43 | 11-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10184995.81 | 3789.27 | 12-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5105936.26 | 3935.34 | 10-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2091119.73 | 3160.92 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2262128.33 | 3301.59 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2519545.51 | 3174.37 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4019455.70 | 3301.56 | 11-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7639346.30 | 3766.36 | 04-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8361212.41 | 3936.47 | 23-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11312303.52 | 3792.08 | 10-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289092E+09 | 4039.16 | 26-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2091119.73 | 3160.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.599313E+09 | 4136.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108253E+10 | 4190.56 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246372E+09 | 4121.15 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10052402.85 | 3940.88 | 08-MAR-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3573693.78 | 3684.62 | 02-APR-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1886070.53 | 2761.02 | 24-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2206379.40 | 3346.18 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2564391.75 | 3160.00 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4352983.95 | 3305.12 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8613219.31 | 3710.84 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6769675.58 | 3551.04 | 23-OCT-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19923291.42 | 3979.39 | 24-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641246E+09 | 4151.30 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1886070.53 | 2761.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108253E+10 | 4190.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136850E+10 | 24029.02 | 01-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202010E+09 | 24022.27 | 12-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115485E+09 | 24015.71 | 12-MAR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56505869.63 | 24021.27 | 05-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29521685.75 | 16703.69 | 30-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26952651.42 | 18672.59 | 24-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21229045.07 | 13096.62 | 03-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32334100.67 | 13442.67 | 20-AUG-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45234388.34 | 17485.27 | 27-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110124E+09 | 24010.24 | 19-OCT-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116583E+09 | 24021.69 | 27-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.656018E+09 | 24024.71 | 17-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 21229045.07 | 13096.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136850E+10 | 24029.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604107E+09 | 3991.05 | 02-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156308E+09 | 3989.31 | 26-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3905419.11 | 3990.55 | 14-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82267.59 | 959.79 | 22-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55291.60 | 645.07 | 24-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 153470.42 | 922.29 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 447289.69 | 2051.10 | 27-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 633380.63 | 2663.48 | 16-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1678035.43 | 3399.97 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3030673.83 | 2824.67 | 30-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9777178.89 | 3966.96 | 28-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311357E+09 | 3994.10 | 19-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 55291.60 | 645.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.604107E+09 | 3994.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104315E+10 | 4074.92 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236505E+09 | 3990.67 | 26-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6143370.87 | 3460.78 | 21-MAR-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 546626.15 | 3272.77 | 02-APR-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58178.39 | 678.75 | 24-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 236073.41 | 1050.07 | 18-JUN-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 463796.86 | 2108.45 | 27-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 676519.36 | 2864.40 | 16-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1818137.28 | 3396.11 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2039909.67 | 1960.90 | 22-OCT-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21331011.04 | 3994.13 | 30-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655529E+09 | 3995.62 | 20-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 58178.39 | 678.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104315E+10 | 4074.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346020E+09 | 1281.73 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126014E+09 | 1264.56 | 10-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6441034.82 | 1075.30 | 24-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1557280.82 | 905.01 | 24-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 686838.92 | 934.96 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 705427.68 | 866.20 | 18-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 972589.11 | 958.47 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1505627.38 | 958.48 | 11-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2074403.54 | 953.83 | 05-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2103094.74 | 924.05 | 11-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26778442.81 | 1121.36 | 01-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244159E+09 | 1271.59 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 686838.92 | 866.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346020E+09 | 1281.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.496930E+09 | 1297.84 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155683E+09 | 1279.00 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5385447.83 | 1111.62 | 12-MAR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1295593.65 | 1184.11 | 11-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 575347.78 | 778.57 | 24-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 691990.81 | 814.80 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 946832.25 | 954.41 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1513071.18 | 961.30 | 21-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2282543.70 | 950.51 | 05-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2830750.91 | 1116.24 | 16-OCT-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40256464.11 | 985.41 | 13-NOV-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373569E+09 | 1292.72 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 575347.78 | 778.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496930E+09 | 1297.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542307E+09 | 5918.86 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194069E+09 | 5318.39 | 09-FEB-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11382300.01 | 5029.65 | 08-MAR-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9228641.99 | 5108.07 | 18-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3837109.58 | 5246.46 | 24-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3557188.18 | 4926.10 | 01-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3700671.94 | 5062.19 | 26-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5579460.03 | 5204.81 | 16-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8700941.47 | 5196.74 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9152267.97 | 5107.52 | 16-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10083445.58 | 4519.49 | 15-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284465E+09 | 5926.41 | 29-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3557188.18 | 4519.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542307E+09 | 5926.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.585799E+11 | 0.585799E+11 | 130887.64 | 12-JAN-16:10 | 130887.64 | 0.42 |
February | 0.00 | 0.00 | 0.140729E+12 | 0.138655E+12 | 180647.37 | 22-FEB-19:10 | 180647.37 | 0.69 |
March | 0.00 | 0.00 | 0.347040E+12 | 0.329234E+12 | 320382.24 | 10-MAR-20:10 | 230246.26 | 0.97 |
April | 0.00 | 0.00 | 0.566157E+12 | 0.510719E+12 | 382441.05 | 26-APR-21:00 | 285799.42 | 0.98 |
May | 0.00 | 0.00 | 0.811077E+12 | 0.621735E+12 | 489660.93 | 22-MAY-20:00 | 242039.45 | 1.00 |
June | 0.00 | 0.00 | 0.935341E+12 | 0.616860E+12 | 545982.40 | 29-JUN-21:00 | 312403.41 | 1.00 |
July | 0.00 | 0.00 | 0.109794E+13 | 0.609467E+12 | 568079.77 | 01-JUL-17:17 | 303042.07 | 1.00 |
August | 0.00 | 0.00 | 0.110559E+13 | 0.581636E+12 | 567277.87 | 28-AUG-18:02 | 298689.85 | 1.00 |
September | 0.00 | 0.00 | 0.948320E+12 | 0.531195E+12 | 539680.39 | 14-SEP-18:02 | 286292.91 | 1.00 |
October | 0.00 | 0.00 | 0.572352E+12 | 0.447907E+12 | 411809.11 | 12-OCT-20:00 | 215265.24 | 1.00 |
November | 0.00 | 0.00 | 0.246967E+12 | 0.240298E+12 | 281546.00 | 08-NOV-19:03 | 201737.02 | 0.90 |
December | 0.00 | 0.00 | 0.808798E+11 | 0.808097E+11 | 140753.38 | 03-DEC-13:00 | 140753.38 | 0.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.691097E+13 | 0.476709E+13 | 0.87 | |||
Minimum of Months | 0.00 | 0.00 | 0.585799E+11 | 0.585799E+11 | 130887.64 | 130887.64 | 0.42 | |
Maximum of Months | 0.00 | 0.00 | 0.110559E+13 | 0.621735E+12 | 568079.77 | 312403.41 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.414961E+10 | 0.413550E+10 | 15714.06 | 12-JAN-16:01 | 15714.06 | 0.19 |
February | 0.00 | 0.00 | 0.984670E+10 | 0.927230E+10 | 25424.56 | 25-FEB-17:00 | 13608.34 | 0.43 |
March | 0.00 | 0.00 | 0.256342E+11 | 0.231689E+11 | 26146.32 | 18-MAR-16:10 | 15018.74 | 0.75 |
April | 0.00 | 0.00 | 0.365398E+11 | 0.329944E+11 | 29289.91 | 25-APR-08:61 | 18739.61 | 0.78 |
May | 0.00 | 0.00 | 0.492159E+11 | 0.374126E+11 | 38342.03 | 22-MAY-23:00 | 16829.83 | 0.79 |
June | 0.00 | 0.00 | 0.593928E+11 | 0.371271E+11 | 47260.28 | 28-JUN-13:00 | 21035.04 | 0.79 |
July | 0.00 | 0.00 | 0.731211E+11 | 0.372468E+11 | 45566.21 | 18-JUL-15:00 | 14775.31 | 0.79 |
August | 0.00 | 0.00 | 0.740364E+11 | 0.359033E+11 | 47804.25 | 12-AUG-08:61 | 19241.94 | 0.79 |
September | 0.00 | 0.00 | 0.639558E+11 | 0.335574E+11 | 45733.00 | 12-SEP-15:02 | 19614.74 | 0.79 |
October | 0.00 | 0.00 | 0.404807E+11 | 0.293477E+11 | 40480.49 | 13-OCT-08:15 | 15566.83 | 0.79 |
November | 0.00 | 0.00 | 0.154323E+11 | 0.141476E+11 | 25763.49 | 08-NOV-19:40 | 15305.05 | 0.62 |
December | 0.00 | 0.00 | 0.544276E+10 | 0.542117E+10 | 16094.49 | 28-DEC-16:01 | 16094.49 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.457248E+12 | 0.299735E+12 | 0.65 | |||
Minimum of Months | 0.00 | 0.00 | 0.414961E+10 | 0.413550E+10 | 15714.06 | 13608.34 | 0.19 | |
Maximum of Months | 0.00 | 0.00 | 0.740364E+11 | 0.374126E+11 | 47804.25 | 21035.04 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122744E+10 | 0.492845E+09 | 15822.32 | 18-JAN-16:01 | 12557.65 | 0.38 |
February | 0.00 | 0.00 | 0.328430E+10 | 0.143570E+10 | 15851.17 | 25-FEB-19:01 | 13408.94 | 0.71 |
March | 0.00 | 0.00 | 0.823068E+10 | 0.451623E+10 | 16106.35 | 18-MAR-08:62 | 12585.50 | 0.93 |
April | 0.00 | 0.00 | 0.130013E+11 | 0.900493E+10 | 15494.59 | 23-APR-08:61 | 13721.99 | 0.97 |
May | 0.00 | 0.00 | 0.159553E+11 | 0.113543E+11 | 15574.30 | 13-MAY-08:61 | 13648.81 | 0.98 |
June | 0.00 | 0.00 | 0.156985E+11 | 0.106626E+11 | 16534.18 | 25-JUN-08:61 | 12883.59 | 0.98 |
July | 0.00 | 0.00 | 0.150955E+11 | 0.937486E+10 | 16657.94 | 18-JUL-15:02 | 12780.81 | 0.98 |
August | 0.00 | 0.00 | 0.140342E+11 | 0.822545E+10 | 16541.27 | 20-AUG-08:61 | 12886.26 | 0.97 |
September | 0.00 | 0.00 | 0.126212E+11 | 0.734479E+10 | 18176.89 | 09-SEP-15:01 | 11557.71 | 0.96 |
October | 0.00 | 0.00 | 0.111413E+11 | 0.653659E+10 | 16961.31 | 12-OCT-08:61 | 12555.11 | 0.95 |
November | 0.00 | 0.00 | 0.659426E+10 | 0.314691E+10 | 16206.42 | 18-NOV-09:01 | 13122.09 | 0.92 |
December | 0.00 | 0.00 | 0.187867E+10 | 0.714613E+09 | 16122.01 | 20-DEC-16:01 | 16122.01 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.118763E+12 | 0.728098E+11 | 0.85 | |||
Minimum of Months | 0.00 | 0.00 | 0.122744E+10 | 0.492845E+09 | 15494.59 | 11557.71 | 0.38 | |
Maximum of Months | 0.00 | 0.00 | 0.159553E+11 | 0.113543E+11 | 18176.89 | 16122.01 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152232E+09 | 64199720.66 | 15683.12 | 15-JAN-09:02 | 12019.00 | 0.10 |
February | 0.00 | 0.00 | 0.121113E+10 | 0.442657E+09 | 16381.57 | 24-FEB-22:52 | 12668.12 | 0.37 |
March | 0.00 | 0.00 | 0.588472E+10 | 0.312035E+10 | 16563.41 | 13-MAR-21:51 | 13964.50 | 0.69 |
April | 0.00 | 0.00 | 0.118335E+11 | 0.808735E+10 | 17226.17 | 03-APR-08:61 | 14281.63 | 0.90 |
May | 0.00 | 0.00 | 0.157404E+11 | 0.111474E+11 | 18330.64 | 13-MAY-08:11 | 13102.37 | 0.98 |
June | 0.00 | 0.00 | 0.157148E+11 | 0.106750E+11 | 17072.51 | 18-JUN-06:51 | 12484.90 | 0.98 |
July | 0.00 | 0.00 | 0.150837E+11 | 0.934413E+10 | 16725.29 | 18-JUL-15:02 | 12824.93 | 0.98 |
August | 0.00 | 0.00 | 0.138273E+11 | 0.800426E+10 | 16612.13 | 20-AUG-08:61 | 12927.69 | 0.97 |
September | 0.00 | 0.00 | 0.118087E+11 | 0.654598E+10 | 18291.95 | 09-SEP-15:01 | 11562.04 | 0.96 |
October | 0.00 | 0.00 | 0.827357E+10 | 0.452585E+10 | 18319.81 | 06-OCT-08:61 | 13077.29 | 0.77 |
November | 0.00 | 0.00 | 0.313616E+10 | 0.125138E+10 | 16976.50 | 08-NOV-22:51 | 12849.79 | 0.60 |
December | 0.00 | 0.00 | 0.304539E+09 | 0.108246E+09 | 15688.67 | 20-DEC-16:01 | 15688.67 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.102971E+12 | 0.633168E+11 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.152232E+09 | 64199720.66 | 15683.12 | 11562.04 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.157404E+11 | 0.111474E+11 | 18330.64 | 15688.67 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200527E+11 | 0.948964E+10 | 31038.16 | 08-JAN-14:30 | 20247.78 | 0.55 |
February | 0.00 | 0.00 | 0.287159E+11 | 0.123779E+11 | 35674.12 | 20-FEB-14:30 | 25998.50 | 0.83 |
March | 0.00 | 0.00 | 0.471863E+11 | 0.217523E+11 | 40249.41 | 12-MAR-15:01 | 27938.17 | 0.99 |
April | 0.00 | 0.00 | 0.608108E+11 | 0.317466E+11 | 41347.30 | 16-APR-15:02 | 29194.03 | 1.00 |
May | 0.00 | 0.00 | 0.699754E+11 | 0.364256E+11 | 42689.52 | 04-MAY-17:20 | 34139.04 | 1.00 |
June | 0.00 | 0.00 | 0.683713E+11 | 0.337071E+11 | 41714.11 | 09-JUN-20:20 | 29550.40 | 1.00 |
July | 0.00 | 0.00 | 0.707162E+11 | 0.318674E+11 | 42120.10 | 08-JUL-08:00 | 25723.27 | 1.00 |
August | 0.00 | 0.00 | 0.677445E+11 | 0.285964E+11 | 39723.97 | 07-AUG-20:20 | 25551.15 | 1.00 |
September | 0.00 | 0.00 | 0.647402E+11 | 0.299421E+11 | 45051.19 | 24-SEP-15:02 | 31759.96 | 1.00 |
October | 0.00 | 0.00 | 0.687104E+11 | 0.384064E+11 | 48020.60 | 02-OCT-15:01 | 39825.44 | 1.00 |
November | 0.00 | 0.00 | 0.540127E+11 | 0.295124E+11 | 45326.04 | 09-NOV-13:00 | 37563.08 | 0.99 |
December | 0.00 | 0.00 | 0.284762E+11 | 0.132195E+11 | 37305.84 | 02-DEC-13:40 | 27667.24 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.649513E+12 | 0.317043E+12 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.200527E+11 | 0.948964E+10 | 31038.16 | 20247.78 | 0.55 | |
Maximum of Months | 0.00 | 0.00 | 0.707162E+11 | 0.384064E+11 | 48020.60 | 39825.44 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.812306E+10 | 0.270296E+10 | 110722.99 | 16-JAN-09:02 | 90632.06 | 0.37 |
February | 0.00 | 0.00 | 0.170637E+11 | 0.680658E+10 | 117548.74 | 15-FEB-22:52 | 88803.78 | 0.47 |
March | 0.00 | 0.00 | 0.426858E+11 | 0.239170E+11 | 114984.85 | 18-MAR-21:52 | 94424.37 | 0.59 |
April | 0.00 | 0.00 | 0.700171E+11 | 0.438664E+11 | 114263.39 | 22-APR-21:51 | 95337.83 | 0.82 |
May | 0.00 | 0.00 | 0.949551E+11 | 0.626232E+11 | 124982.13 | 13-MAY-08:11 | 91353.31 | 0.93 |
June | 0.00 | 0.00 | 0.966437E+11 | 0.631253E+11 | 121449.48 | 24-JUN-15:01 | 89925.49 | 0.92 |
July | 0.00 | 0.00 | 0.985974E+11 | 0.614988E+11 | 121987.19 | 18-JUL-15:02 | 89480.98 | 0.92 |
August | 0.00 | 0.00 | 0.915601E+11 | 0.544993E+11 | 122931.78 | 11-AUG-15:02 | 88793.05 | 0.90 |
September | 0.00 | 0.00 | 0.772259E+11 | 0.435234E+11 | 127840.01 | 09-SEP-15:01 | 84986.24 | 0.86 |
October | 0.00 | 0.00 | 0.552277E+11 | 0.314849E+11 | 127736.14 | 11-OCT-21:51 | 90002.46 | 0.68 |
November | 0.00 | 0.00 | 0.273797E+11 | 0.119220E+11 | 117985.24 | 17-NOV-22:52 | 88268.38 | 0.50 |
December | 0.00 | 0.00 | 0.104186E+11 | 0.362228E+10 | 113669.55 | 29-DEC-22:53 | 84399.48 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.689898E+12 | 0.409592E+12 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.812306E+10 | 0.270296E+10 | 110722.99 | 84399.48 | 0.37 | |
Maximum of Months | 0.00 | 0.00 | 0.985974E+11 | 0.631253E+11 | 127840.01 | 95337.83 | 0.93 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.120117E+10 | 0.467976E+09 | 14141.74 | 15-JAN-09:02 | 11013.15 | 0.39 |
February | 0.00 | 0.00 | 0.346357E+10 | 0.158517E+10 | 14438.77 | 25-FEB-19:01 | 11949.67 | 0.74 |
March | 0.00 | 0.00 | 0.833831E+10 | 0.466574E+10 | 14632.70 | 18-MAR-08:62 | 11480.03 | 0.95 |
April | 0.00 | 0.00 | 0.130068E+11 | 0.905262E+10 | 13265.68 | 23-APR-08:61 | 13038.33 | 0.98 |
May | 0.00 | 0.00 | 0.160447E+11 | 0.117000E+11 | 13984.66 | 13-MAY-08:61 | 12485.05 | 0.99 |
June | 0.00 | 0.00 | 0.152972E+11 | 0.105340E+11 | 14955.19 | 24-JUN-15:01 | 11717.35 | 0.98 |
July | 0.00 | 0.00 | 0.151060E+11 | 0.964516E+10 | 15119.44 | 18-JUL-15:02 | 11582.83 | 0.98 |
August | 0.00 | 0.00 | 0.140042E+11 | 0.843547E+10 | 14952.21 | 20-AUG-08:61 | 11726.74 | 0.98 |
September | 0.00 | 0.00 | 0.124891E+11 | 0.738151E+10 | 16464.42 | 09-SEP-15:01 | 10503.74 | 0.97 |
October | 0.00 | 0.00 | 0.111834E+11 | 0.666680E+10 | 15311.07 | 12-OCT-08:61 | 11446.81 | 0.97 |
November | 0.00 | 0.00 | 0.657151E+10 | 0.333379E+10 | 14508.80 | 18-NOV-09:01 | 12096.59 | 0.93 |
December | 0.00 | 0.00 | 0.189162E+10 | 0.748279E+09 | 14614.20 | 20-DEC-16:01 | 14614.20 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.118598E+12 | 0.742165E+11 | 0.86 | |||
Minimum of Months | 0.00 | 0.00 | 0.120117E+10 | 0.467976E+09 | 13265.68 | 10503.74 | 0.39 | |
Maximum of Months | 0.00 | 0.00 | 0.160447E+11 | 0.117000E+11 | 16464.42 | 14614.20 | 0.99 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185767E+09 | 62684381.90 | 14194.01 | 15-JAN-09:02 | 10842.82 | 0.11 |
February | 0.00 | 0.00 | 0.137704E+10 | 0.539270E+09 | 14962.67 | 24-FEB-22:52 | 11627.89 | 0.40 |
March | 0.00 | 0.00 | 0.590655E+10 | 0.317669E+10 | 15784.88 | 10-MAR-09:51 | 13242.30 | 0.72 |
April | 0.00 | 0.00 | 0.118068E+11 | 0.803023E+10 | 16137.65 | 22-APR-08:11 | 13949.12 | 0.91 |
May | 0.00 | 0.00 | 0.158260E+11 | 0.114666E+11 | 16752.34 | 13-MAY-08:11 | 12124.82 | 0.98 |
June | 0.00 | 0.00 | 0.153139E+11 | 0.105468E+11 | 15435.08 | 18-JUN-06:51 | 11237.42 | 0.98 |
July | 0.00 | 0.00 | 0.150937E+11 | 0.962750E+10 | 15145.74 | 18-JUL-15:02 | 11598.49 | 0.98 |
August | 0.00 | 0.00 | 0.137986E+11 | 0.822068E+10 | 14982.19 | 20-AUG-08:61 | 11739.54 | 0.98 |
September | 0.00 | 0.00 | 0.116753E+11 | 0.652305E+10 | 16531.57 | 09-SEP-15:01 | 10485.51 | 0.96 |
October | 0.00 | 0.00 | 0.829055E+10 | 0.461818E+10 | 16690.70 | 06-OCT-08:61 | 11971.31 | 0.79 |
November | 0.00 | 0.00 | 0.305626E+10 | 0.127509E+10 | 15294.54 | 09-NOV-09:51 | 12839.57 | 0.61 |
December | 0.00 | 0.00 | 0.369237E+09 | 0.128259E+09 | 13476.07 | 16-DEC-16:01 | 12290.06 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.102700E+12 | 0.642151E+11 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.185767E+09 | 62684381.90 | 13476.07 | 10485.51 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.158260E+11 | 0.114666E+11 | 16752.34 | 13949.12 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.355992E+09 | 0.166109E+09 | 4555.54 | 18-JAN-16:01 | 3650.15 | 0.30 |
February | 0.00 | 0.00 | 0.813055E+09 | 0.390819E+09 | 4628.80 | 25-FEB-09:01 | 3370.23 | 0.59 |
March | 0.00 | 0.00 | 0.200081E+10 | 0.112864E+10 | 4705.50 | 18-MAR-08:62 | 3136.93 | 0.89 |
April | 0.00 | 0.00 | 0.332533E+10 | 0.226625E+10 | 4732.12 | 23-APR-08:61 | 3465.61 | 0.97 |
May | 0.00 | 0.00 | 0.417630E+10 | 0.288500E+10 | 4620.74 | 13-MAY-08:61 | 3595.79 | 0.98 |
June | 0.00 | 0.00 | 0.413793E+10 | 0.277957E+10 | 4934.58 | 25-JUN-08:61 | 3337.68 | 0.98 |
July | 0.00 | 0.00 | 0.389950E+10 | 0.233784E+10 | 4680.76 | 28-JUL-08:61 | 3546.09 | 0.97 |
August | 0.00 | 0.00 | 0.357756E+10 | 0.200445E+10 | 4882.18 | 20-AUG-08:61 | 3383.05 | 0.97 |
September | 0.00 | 0.00 | 0.317401E+10 | 0.177210E+10 | 4906.32 | 09-SEP-08:61 | 3363.84 | 0.96 |
October | 0.00 | 0.00 | 0.268056E+10 | 0.155061E+10 | 4989.41 | 12-OCT-08:61 | 3183.97 | 0.94 |
November | 0.00 | 0.00 | 0.148338E+10 | 0.754294E+09 | 4680.74 | 18-NOV-09:01 | 3322.30 | 0.81 |
December | 0.00 | 0.00 | 0.482059E+09 | 0.208167E+09 | 4503.14 | 30-DEC-16:01 | 4503.14 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.301065E+11 | 0.182438E+11 | 0.82 | |||
Minimum of Months | 0.00 | 0.00 | 0.355992E+09 | 0.166109E+09 | 4503.14 | 3136.93 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.417630E+10 | 0.288500E+10 | 4989.41 | 4503.14 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 40043453.90 | 18970649.24 | 4463.05 | 18-JAN-16:01 | 3481.68 | 0.07 |
February | 0.00 | 0.00 | 0.272481E+09 | 0.115032E+09 | 4700.57 | 15-FEB-22:52 | 3317.73 | 0.28 |
March | 0.00 | 0.00 | 0.144073E+10 | 0.777356E+09 | 4707.42 | 29-MAR-08:51 | 3660.26 | 0.68 |
April | 0.00 | 0.00 | 0.304825E+10 | 0.204492E+10 | 4923.85 | 03-APR-08:61 | 3813.64 | 0.90 |
May | 0.00 | 0.00 | 0.412185E+10 | 0.283125E+10 | 5308.85 | 13-MAY-08:11 | 3486.55 | 0.98 |
June | 0.00 | 0.00 | 0.414362E+10 | 0.278201E+10 | 4997.68 | 18-JUN-08:61 | 3307.62 | 0.98 |
July | 0.00 | 0.00 | 0.389660E+10 | 0.233223E+10 | 4695.10 | 28-JUL-08:61 | 3556.26 | 0.97 |
August | 0.00 | 0.00 | 0.352341E+10 | 0.194689E+10 | 4899.14 | 20-AUG-08:61 | 3391.07 | 0.97 |
September | 0.00 | 0.00 | 0.296185E+10 | 0.156202E+10 | 4922.99 | 09-SEP-08:61 | 3372.08 | 0.95 |
October | 0.00 | 0.00 | 0.199117E+10 | 0.105644E+10 | 5318.91 | 06-OCT-08:61 | 3363.93 | 0.77 |
November | 0.00 | 0.00 | 0.638375E+09 | 0.282875E+09 | 4833.70 | 08-NOV-22:51 | 3515.82 | 0.48 |
December | 0.00 | 0.00 | 66635806.38 | 26189683.04 | 4516.25 | 20-DEC-16:01 | 4516.25 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.261450E+11 | 0.157762E+11 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 40043453.90 | 18970649.24 | 4463.05 | 3307.62 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.414362E+10 | 0.283125E+10 | 5318.91 | 4516.25 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.568166E+10 | 0.322585E+10 | 21829.20 | 17-JAN-16:01 | 16586.33 | 0.61 |
February | 0.00 | 0.00 | 0.771258E+10 | 0.455013E+10 | 21432.91 | 25-FEB-19:01 | 16655.15 | 0.78 |
March | 0.00 | 0.00 | 0.127121E+11 | 0.784600E+10 | 20978.49 | 18-MAR-18:01 | 17234.60 | 0.94 |
April | 0.00 | 0.00 | 0.166426E+11 | 0.113271E+11 | 20711.24 | 23-APR-08:61 | 17454.92 | 0.96 |
May | 0.00 | 0.00 | 0.195712E+11 | 0.133336E+11 | 20899.70 | 13-MAY-08:61 | 17295.12 | 0.97 |
June | 0.00 | 0.00 | 0.192479E+11 | 0.127893E+11 | 21330.11 | 24-JUN-15:01 | 16945.02 | 0.97 |
July | 0.00 | 0.00 | 0.194126E+11 | 0.120006E+11 | 21576.96 | 18-JUL-15:02 | 16746.85 | 0.97 |
August | 0.00 | 0.00 | 0.184110E+11 | 0.108875E+11 | 21100.95 | 20-AUG-08:61 | 17132.19 | 0.97 |
September | 0.00 | 0.00 | 0.172887E+11 | 0.104107E+11 | 22494.05 | 09-SEP-15:01 | 16039.50 | 0.96 |
October | 0.00 | 0.00 | 0.177552E+11 | 0.116016E+11 | 22722.63 | 12-OCT-08:61 | 15691.87 | 0.96 |
November | 0.00 | 0.00 | 0.134842E+11 | 0.884520E+10 | 20909.19 | 18-NOV-09:01 | 17311.18 | 0.94 |
December | 0.00 | 0.00 | 0.724895E+10 | 0.432148E+10 | 20940.47 | 31-DEC-16:01 | 20940.47 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.175169E+12 | 0.111139E+12 | 0.89 | |||
Minimum of Months | 0.00 | 0.00 | 0.568166E+10 | 0.322585E+10 | 20711.24 | 15691.87 | 0.61 | |
Maximum of Months | 0.00 | 0.00 | 0.195712E+11 | 0.133336E+11 | 22722.63 | 20940.47 | 0.97 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3874.27 | 47147.41 | 02-JAN-09:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 1001.72 | 35276.97 | 09-FEB-16:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 62.77 | 20029.32 | 15-MAR-08:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.64 | 20960.01 | 07-APR-08:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.56 | 14335.34 | 12-MAY-15:06 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.24 | 15346.71 | 24-JUN-15:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12.35 | 14372.48 | 27-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.66 | 14480.36 | 16-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.41 | 16016.18 | 07-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.17 | 20071.52 | 24-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 131.21 | 24305.08 | 28-NOV-16:04 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 1999.58 | 39325.97 | 23-DEC-09:05 |
Annual Sum or Average | 0.00 | 606.24 | ||||
Minimum of Months | 0.00 | 0.00 | 12.35 | 14335.34 | ||
Maximum of Months | 0.00 | 0.00 | 3874.27 | 47147.41 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 39714.64 | 313170.39 | 12-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 91536.20 | 377655.60 | 20-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 192284.86 | 543670.45 | 10-MAR-19:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 314011.61 | 606629.25 | 26-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 419861.91 | 722215.61 | 22-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 484909.60 | 802059.59 | 22-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 536038.59 | 832109.25 | 01-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 533089.36 | 835771.79 | 27-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 475974.63 | 805977.07 | 14-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 300915.30 | 612610.92 | 03-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 149097.06 | 438335.26 | 05-NOV-18:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 54133.22 | 402884.24 | 02-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 300383.49 | 0.00 | ||||
Minimum of Months | 39714.64 | 313170.39 | 0.00 | 0.00 | ||
Maximum of Months | 536038.59 | 835771.79 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22339.34 | 45036.94 | 19-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 21895.14 | 44726.42 | 02-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 20562.83 | 42852.39 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18602.37 | 38867.76 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16599.19 | 34886.87 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15079.48 | 31013.51 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14441.69 | 28629.89 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14905.16 | 30538.33 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16290.62 | 34092.49 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18243.08 | 38499.86 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 20241.64 | 42256.02 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21740.36 | 44569.11 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 18392.52 | ||||
Minimum of Months | 0.00 | 0.00 | 14441.69 | 28629.89 | ||
Maximum of Months | 0.00 | 0.00 | 22339.34 | 45036.94 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 01-JAN-19:02 | 0.89 |
February | 0.244774E+10 | 0.71 | 1299.30 | 08-FEB-09:52 | 0.89 |
March | 0.271000E+10 | 0.71 | 1299.30 | 10-MAR-16:04 | 0.89 |
April | 0.262258E+10 | 0.71 | 1299.30 | 27-APR-15:25 | 0.90 |
May | 0.271000E+10 | 0.71 | 1299.30 | 16-MAY-18:05 | 0.89 |
June | 0.262258E+10 | 0.71 | 1299.30 | 05-JUN-18:17 | 0.89 |
July | 0.271000E+10 | 0.71 | 1299.30 | 03-JUL-18:30 | 0.89 |
August | 0.271000E+10 | 0.71 | 1299.30 | 06-AUG-18:05 | 0.89 |
September | 0.262258E+10 | 0.71 | 1299.30 | 17-SEP-15:05 | 0.89 |
October | 0.271000E+10 | 0.71 | 1299.30 | 05-OCT-15:04 | 0.89 |
November | 0.262258E+10 | 0.71 | 1299.30 | 07-NOV-16:13 | 0.89 |
December | 0.271000E+10 | 0.71 | 1299.30 | 15-DEC-20:03 | 0.89 |
Annual Sum or Average | 0.319080E+11 | 0.71 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.89 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.282740E+11 | 0.68 | 17785.31 | 12-JAN-21:10 | 0.90 |
February | 0.268765E+11 | 0.70 | 21899.06 | 22-FEB-22:00 | 1.02 |
March | 0.332737E+11 | 0.74 | 27574.32 | 29-MAR-21:10 | 1.17 |
April | 0.384750E+11 | 0.81 | 36537.59 | 28-APR-22:00 | 1.39 |
May | 0.457405E+11 | 0.87 | 39518.02 | 05-MAY-21:20 | 1.47 |
June | 0.461266E+11 | 0.89 | 40779.98 | 06-JUN-21:20 | 1.50 |
July | 0.474136E+11 | 0.89 | 41527.31 | 07-JUL-21:20 | 1.51 |
August | 0.462664E+11 | 0.88 | 41162.69 | 08-AUG-21:20 | 1.50 |
September | 0.421999E+11 | 0.85 | 38214.92 | 01-SEP-21:20 | 1.43 |
October | 0.398704E+11 | 0.81 | 35325.62 | 02-OCT-21:10 | 1.37 |
November | 0.327542E+11 | 0.74 | 26057.24 | 10-NOV-21:10 | 1.13 |
December | 0.291998E+11 | 0.69 | 20809.69 | 28-DEC-21:10 | 0.99 |
Annual Sum or Average | 0.456471E+12 | 0.80 | |||
Minimum of Months | 0.268765E+11 | 0.68 | 17785.31 | 0.90 | |
Maximum of Months | 0.474136E+11 | 0.89 | 41527.31 | 1.51 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:05 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:05 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:10 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:10 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:10 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:10 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148069E+09 | 0.44 | 786.01 | 01-JAN-16:03 | 0.59 |
February | 0.172905E+09 | 0.50 | 786.01 | 01-FEB-16:01 | 0.59 |
March | 0.359671E+09 | 0.55 | 786.01 | 01-MAR-16:01 | 0.59 |
April | 0.597162E+09 | 0.57 | 786.01 | 01-APR-08:61 | 0.59 |
May | 0.719387E+09 | 0.58 | 786.01 | 01-MAY-08:61 | 0.59 |
June | 0.693939E+09 | 0.58 | 786.01 | 01-JUN-08:61 | 0.59 |
July | 0.611775E+09 | 0.57 | 786.01 | 01-JUL-08:62 | 0.59 |
August | 0.546981E+09 | 0.57 | 786.01 | 01-AUG-08:61 | 0.59 |
September | 0.502823E+09 | 0.57 | 786.01 | 01-SEP-08:61 | 0.59 |
October | 0.464077E+09 | 0.56 | 786.01 | 01-OCT-08:61 | 0.59 |
November | 0.281732E+09 | 0.54 | 786.01 | 01-NOV-08:61 | 0.59 |
December | 0.138351E+09 | 0.47 | 786.01 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.523687E+10 | 0.54 | |||
Minimum of Months | 0.138351E+09 | 0.44 | 786.01 | 0.59 | |
Maximum of Months | 0.719387E+09 | 0.58 | 786.01 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145758E+09 | 0.35 | 788.99 | 01-JAN-09:02 | 0.59 |
February | 93324204.35 | 0.33 | 788.99 | 01-FEB-16:01 | 0.59 |
March | 0.255694E+09 | 0.40 | 788.99 | 01-MAR-16:01 | 0.59 |
April | 0.536003E+09 | 0.53 | 788.99 | 01-APR-08:61 | 0.58 |
May | 0.707220E+09 | 0.57 | 788.99 | 01-MAY-08:61 | 0.59 |
June | 0.694994E+09 | 0.57 | 788.99 | 01-JUN-08:61 | 0.59 |
July | 0.611513E+09 | 0.57 | 788.99 | 01-JUL-08:62 | 0.59 |
August | 0.537496E+09 | 0.57 | 788.99 | 01-AUG-08:61 | 0.59 |
September | 0.463974E+09 | 0.56 | 788.99 | 01-SEP-08:61 | 0.59 |
October | 0.340918E+09 | 0.45 | 788.99 | 01-OCT-08:21 | 0.58 |
November | 0.139447E+09 | 0.37 | 788.99 | 01-NOV-08:51 | 0.59 |
December | 0.109222E+09 | 0.34 | 788.99 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.463556E+10 | 0.47 | |||
Minimum of Months | 93324204.35 | 0.33 | 788.99 | 0.58 | |
Maximum of Months | 0.707220E+09 | 0.57 | 788.99 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.793494E+09 | 0.37 | 1050.27 | 08-JAN-14:25 | 0.59 |
February | 0.105997E+10 | 0.49 | 1172.96 | 20-FEB-14:30 | 0.59 |
March | 0.164041E+10 | 0.59 | 1234.40 | 13-MAR-13:50 | 0.59 |
April | 0.203519E+10 | 0.59 | 1274.68 | 15-APR-14:00 | 0.59 |
May | 0.223243E+10 | 0.59 | 1332.32 | 04-MAY-17:20 | 0.59 |
June | 0.211480E+10 | 0.59 | 1296.47 | 12-JUN-17:20 | 0.59 |
July | 0.211557E+10 | 0.59 | 1255.19 | 04-JUL-20:10 | 0.59 |
August | 0.201664E+10 | 0.59 | 1167.69 | 07-AUG-20:20 | 0.59 |
September | 0.196376E+10 | 0.58 | 1335.98 | 26-SEP-14:00 | 0.59 |
October | 0.220624E+10 | 0.59 | 1479.45 | 02-OCT-13:30 | 0.59 |
November | 0.183389E+10 | 0.58 | 1412.19 | 08-NOV-13:40 | 0.59 |
December | 0.107041E+10 | 0.46 | 1202.65 | 02-DEC-13:40 | 0.59 |
Annual Sum or Average | 0.210828E+11 | 0.55 | |||
Minimum of Months | 0.793494E+09 | 0.37 | 1050.27 | 0.59 | |
Maximum of Months | 0.223243E+10 | 0.59 | 1479.45 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.681226E+09 | 0.35 | 5545.66 | 01-JAN-09:05 | 0.59 |
February | 0.786232E+09 | 0.30 | 5545.66 | 01-FEB-16:01 | 0.59 |
March | 0.176659E+10 | 0.35 | 5545.66 | 01-MAR-09:52 | 0.59 |
April | 0.307553E+10 | 0.48 | 5545.66 | 01-APR-08:61 | 0.59 |
May | 0.409614E+10 | 0.54 | 5545.66 | 01-MAY-08:61 | 0.59 |
June | 0.412865E+10 | 0.54 | 5545.66 | 01-JUN-08:61 | 0.59 |
July | 0.407260E+10 | 0.54 | 5545.66 | 01-JUL-08:62 | 0.59 |
August | 0.369188E+10 | 0.53 | 5545.66 | 01-AUG-08:61 | 0.59 |
September | 0.308772E+10 | 0.51 | 5545.66 | 01-SEP-08:61 | 0.59 |
October | 0.220774E+10 | 0.40 | 5545.66 | 01-OCT-08:21 | 0.59 |
November | 0.113053E+10 | 0.30 | 5545.66 | 01-NOV-08:51 | 0.59 |
December | 0.663061E+09 | 0.34 | 5545.66 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.293879E+11 | 0.43 | |||
Minimum of Months | 0.663061E+09 | 0.30 | 5545.66 | 0.59 | |
Maximum of Months | 0.412865E+10 | 0.54 | 5545.66 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138954E+09 | 0.44 | 712.09 | 02-JAN-16:01 | 0.59 |
February | 0.175470E+09 | 0.51 | 712.09 | 01-FEB-16:01 | 0.59 |
March | 0.357915E+09 | 0.56 | 712.09 | 01-MAR-09:02 | 0.59 |
April | 0.584792E+09 | 0.58 | 712.09 | 01-APR-08:61 | 0.59 |
May | 0.726254E+09 | 0.58 | 712.09 | 01-MAY-08:61 | 0.59 |
June | 0.670614E+09 | 0.58 | 712.09 | 01-JUN-08:61 | 0.59 |
July | 0.621083E+09 | 0.57 | 712.09 | 01-JUL-08:62 | 0.59 |
August | 0.552022E+09 | 0.57 | 712.09 | 01-AUG-08:61 | 0.59 |
September | 0.497760E+09 | 0.57 | 712.09 | 01-SEP-08:61 | 0.59 |
October | 0.465104E+09 | 0.57 | 712.09 | 01-OCT-08:61 | 0.59 |
November | 0.276063E+09 | 0.55 | 712.09 | 01-NOV-08:61 | 0.59 |
December | 0.136568E+09 | 0.47 | 712.09 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.520260E+10 | 0.55 | |||
Minimum of Months | 0.136568E+09 | 0.44 | 712.09 | 0.59 | |
Maximum of Months | 0.726254E+09 | 0.58 | 712.09 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131108E+09 | 0.35 | 713.22 | 01-JAN-16:01 | 0.59 |
February | 94538952.55 | 0.34 | 713.22 | 01-FEB-16:01 | 0.59 |
March | 0.252100E+09 | 0.42 | 713.22 | 01-MAR-09:52 | 0.59 |
April | 0.528457E+09 | 0.53 | 713.22 | 01-APR-07:52 | 0.58 |
May | 0.713593E+09 | 0.58 | 713.22 | 01-MAY-08:61 | 0.59 |
June | 0.673072E+09 | 0.58 | 713.22 | 01-JUN-08:61 | 0.59 |
July | 0.620709E+09 | 0.57 | 713.22 | 01-JUL-08:62 | 0.59 |
August | 0.542073E+09 | 0.57 | 713.22 | 01-AUG-08:61 | 0.59 |
September | 0.461136E+09 | 0.57 | 713.22 | 01-SEP-08:61 | 0.59 |
October | 0.339099E+09 | 0.46 | 713.22 | 01-OCT-08:21 | 0.58 |
November | 0.134317E+09 | 0.37 | 713.22 | 01-NOV-08:51 | 0.59 |
December | 0.104278E+09 | 0.34 | 713.22 | 01-DEC-09:52 | 0.59 |
Annual Sum or Average | 0.459448E+10 | 0.47 | |||
Minimum of Months | 94538952.55 | 0.34 | 713.22 | 0.58 | |
Maximum of Months | 0.713593E+09 | 0.58 | 713.22 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 56292548.22 | 0.46 | 219.64 | 01-JAN-09:02 | 0.59 |
February | 52942875.94 | 0.51 | 219.64 | 01-FEB-16:01 | 0.59 |
March | 90646389.00 | 0.55 | 219.64 | 01-MAR-16:01 | 0.59 |
April | 0.155654E+09 | 0.57 | 219.64 | 01-APR-08:61 | 0.59 |
May | 0.188842E+09 | 0.58 | 219.64 | 01-MAY-08:61 | 0.59 |
June | 0.181628E+09 | 0.57 | 219.64 | 01-JUN-08:61 | 0.59 |
July | 0.157171E+09 | 0.57 | 219.64 | 01-JUL-08:62 | 0.59 |
August | 0.139115E+09 | 0.57 | 219.64 | 01-AUG-08:61 | 0.59 |
September | 0.126850E+09 | 0.57 | 219.64 | 01-SEP-08:61 | 0.58 |
October | 0.114710E+09 | 0.56 | 219.64 | 01-OCT-08:61 | 0.59 |
November | 68418152.63 | 0.54 | 219.64 | 01-NOV-15:01 | 0.59 |
December | 52430038.55 | 0.49 | 219.64 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.138470E+10 | 0.54 | |||
Minimum of Months | 52430038.55 | 0.46 | 219.64 | 0.58 | |
Maximum of Months | 0.188842E+09 | 0.58 | 219.64 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 54455557.40 | 0.36 | 220.30 | 01-JAN-09:02 | 0.59 |
February | 31640681.02 | 0.34 | 220.30 | 01-FEB-09:02 | 0.59 |
March | 64921778.17 | 0.41 | 220.30 | 01-MAR-16:01 | 0.59 |
April | 0.140880E+09 | 0.53 | 220.30 | 01-APR-08:61 | 0.58 |
May | 0.186045E+09 | 0.57 | 220.30 | 01-MAY-08:61 | 0.59 |
June | 0.182115E+09 | 0.57 | 220.30 | 01-JUN-08:61 | 0.59 |
July | 0.157003E+09 | 0.57 | 220.30 | 01-JUL-08:62 | 0.59 |
August | 0.136511E+09 | 0.57 | 220.30 | 01-AUG-08:61 | 0.59 |
September | 0.116488E+09 | 0.56 | 220.30 | 01-SEP-08:61 | 0.58 |
October | 84361670.55 | 0.46 | 220.30 | 01-OCT-08:21 | 0.58 |
November | 34351226.05 | 0.37 | 220.30 | 01-NOV-15:01 | 0.59 |
December | 45617733.88 | 0.36 | 220.30 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.123439E+10 | 0.47 | |||
Minimum of Months | 31640681.02 | 0.34 | 220.30 | 0.58 | |
Maximum of Months | 0.186045E+09 | 0.57 | 220.30 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.328942E+09 | 0.51 | 1017.11 | 01-JAN-16:01 | 0.59 |
February | 0.363254E+09 | 0.53 | 1017.11 | 01-FEB-16:01 | 0.59 |
March | 0.557738E+09 | 0.55 | 1017.11 | 01-MAR-09:02 | 0.59 |
April | 0.743202E+09 | 0.57 | 1017.11 | 01-APR-08:61 | 0.59 |
May | 0.850761E+09 | 0.57 | 1017.11 | 01-MAY-08:61 | 0.59 |
June | 0.816511E+09 | 0.57 | 1017.11 | 01-JUN-08:61 | 0.59 |
July | 0.783390E+09 | 0.57 | 1017.11 | 01-JUL-08:62 | 0.59 |
August | 0.726000E+09 | 0.57 | 1017.11 | 01-AUG-08:61 | 0.59 |
September | 0.703886E+09 | 0.57 | 1017.11 | 01-SEP-08:61 | 0.59 |
October | 0.778031E+09 | 0.56 | 1017.11 | 01-OCT-08:61 | 0.59 |
November | 0.590726E+09 | 0.56 | 1017.11 | 01-NOV-08:61 | 0.59 |
December | 0.360468E+09 | 0.54 | 1017.11 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.760291E+10 | 0.56 | |||
Minimum of Months | 0.328942E+09 | 0.51 | 1017.11 | 0.59 | |
Maximum of Months | 0.850761E+09 | 0.57 | 1017.11 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.125662E+09 | 0.113096E+09 | 311.15 | 02-JAN-09:04 | 280.04 | 280.04 | 32.00 | 0.40 |
February | 31675118.01 | 28507606.21 | 302.35 | 09-FEB-16:05 | 272.11 | 272.11 | 38.19 | 0.39 |
March | 1875056.63 | 1687550.96 | 192.76 | 24-MAR-08:54 | 173.48 | 173.48 | 38.65 | 0.22 |
April | 795536.14 | 715982.53 | 196.63 | 07-APR-08:54 | 176.97 | 176.97 | 38.06 | 0.23 |
May | 424207.28 | 381786.55 | 156.09 | 30-MAY-08:06 | 140.48 | 140.48 | 40.52 | 0.18 |
June | 420153.69 | 378138.32 | 167.17 | 24-JUN-15:06 | 150.45 | 150.45 | 40.64 | 0.19 |
July | 397027.45 | 357324.71 | 163.66 | 27-JUL-08:04 | 147.29 | 147.29 | 41.43 | 0.19 |
August | 603745.57 | 543371.02 | 167.39 | 16-AUG-08:04 | 150.65 | 150.65 | 41.75 | 0.19 |
September | 880784.76 | 792706.28 | 173.36 | 07-SEP-08:04 | 156.02 | 156.02 | 40.61 | 0.20 |
October | 1462401.86 | 1316161.67 | 193.38 | 19-OCT-21:55 | 174.04 | 174.04 | 38.70 | 0.22 |
November | 4359414.49 | 3923473.04 | 266.02 | 24-NOV-09:04 | 239.42 | 239.42 | 42.95 | 0.33 |
December | 71730442.81 | 64557398.53 | 277.41 | 23-DEC-09:05 | 249.67 | 249.67 | 32.89 | 0.35 |
Annual Sum or Average | 0.240286E+09 | 0.216257E+09 | ||||||
Minimum of Months | 397027.45 | 357324.71 | 156.09 | 140.48 | 140.48 | 32.00 | 0.18 | |
Maximum of Months | 0.125662E+09 | 0.113096E+09 | 311.15 | 280.04 | 280.04 | 42.95 | 0.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 45487686.73 | 40938918.06 | 414.87 | 12-JAN-16:01 | 373.38 | 373.38 | 6.72 | 10.45 |
February | 0.128834E+09 | 0.115951E+09 | 545.40 | 06-FEB-16:03 | 490.86 | 490.86 | 6.72 | 11.80 |
March | 0.439554E+09 | 0.395599E+09 | 793.14 | 10-MAR-19:03 | 713.83 | 713.83 | 6.72 | 13.90 |
April | 0.921598E+09 | 0.829439E+09 | 1418.97 | 08-APR-18:03 | 1277.08 | 1277.08 | 6.72 | 17.78 |
May | 0.146407E+10 | 0.131766E+10 | 1745.96 | 17-MAY-18:03 | 1571.36 | 1571.36 | 6.72 | 19.38 |
June | 0.179092E+10 | 0.161183E+10 | 2270.75 | 22-JUN-18:03 | 2043.68 | 2043.68 | 6.72 | 21.58 |
July | 0.214298E+10 | 0.192868E+10 | 2385.96 | 01-JUL-18:03 | 2147.36 | 2147.36 | 6.72 | 22.01 |
August | 0.207646E+10 | 0.186881E+10 | 2288.93 | 28-AUG-18:02 | 2060.04 | 2060.04 | 6.72 | 21.65 |
September | 0.158039E+10 | 0.142235E+10 | 2094.42 | 14-SEP-18:02 | 1884.98 | 1884.98 | 6.72 | 20.88 |
October | 0.783711E+09 | 0.705340E+09 | 1113.53 | 02-OCT-18:02 | 1002.18 | 1002.18 | 6.72 | 16.06 |
November | 0.281983E+09 | 0.253785E+09 | 632.68 | 01-NOV-15:01 | 569.41 | 569.41 | 6.72 | 12.60 |
December | 71687428.47 | 64518685.63 | 474.17 | 02-DEC-16:01 | 426.75 | 426.75 | 6.72 | 11.09 |
Annual Sum or Average | 0.117277E+11 | 0.105549E+11 | ||||||
Minimum of Months | 45487686.73 | 40938918.06 | 414.87 | 373.38 | 373.38 | 6.72 | 10.45 | |
Maximum of Months | 0.214298E+10 | 0.192868E+10 | 2385.96 | 2147.36 | 2147.36 | 6.72 | 22.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.734095E+10 | 0.660685E+10 | 3277.18 | 01-JAN-09:02 | 2949.46 | 2949.46 | 7.07 | 28.99 |
February | 0.770891E+10 | 0.693802E+10 | 3277.18 | 01-FEB-00:03 | 2949.46 | 2949.46 | 6.77 | 28.99 |
March | 0.877760E+10 | 0.789984E+10 | 3277.18 | 01-MAR-00:05 | 2949.46 | 2949.46 | 7.36 | 28.99 |
April | 0.849445E+10 | 0.764501E+10 | 3277.18 | 01-APR-00:10 | 2949.46 | 2949.46 | 8.51 | 28.99 |
May | 0.877760E+10 | 0.789984E+10 | 3277.18 | 01-MAY-00:10 | 2949.46 | 2949.46 | 9.31 | 28.99 |
June | 0.849445E+10 | 0.764501E+10 | 3277.18 | 01-JUN-00:05 | 2949.46 | 2949.46 | 9.78 | 28.99 |
July | 0.877760E+10 | 0.789984E+10 | 3277.18 | 01-JUL-00:10 | 2949.46 | 2949.46 | 10.67 | 28.99 |
August | 0.877760E+10 | 0.789984E+10 | 3277.18 | 01-AUG-00:10 | 2949.46 | 2949.46 | 10.81 | 28.99 |
September | 0.849445E+10 | 0.764501E+10 | 3277.18 | 01-SEP-00:10 | 2949.46 | 2949.46 | 10.73 | 28.99 |
October | 0.877760E+10 | 0.789984E+10 | 3277.18 | 01-OCT-00:10 | 2949.46 | 2949.46 | 9.79 | 28.99 |
November | 0.849445E+10 | 0.764501E+10 | 3277.18 | 01-NOV-00:05 | 2949.46 | 2949.46 | 7.94 | 28.99 |
December | 0.833813E+10 | 0.750432E+10 | 3277.18 | 01-DEC-00:05 | 2949.46 | 2949.46 | 6.93 | 28.99 |
Annual Sum or Average | 0.101254E+12 | 0.911284E+11 | ||||||
Minimum of Months | 0.734095E+10 | 0.660685E+10 | 3277.18 | 2949.46 | 2949.46 | 6.77 | 28.99 | |
Maximum of Months | 0.877760E+10 | 0.789984E+10 | 3277.18 | 2949.46 | 2949.46 | 10.81 | 28.99 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.73 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 51.02 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 51.19 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.61 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.96 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.36 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.53 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.71 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 55.39 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.03 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 54.10 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 51.25 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.73 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.71 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 40.04 | 60.00 | 3874.27 | 47147.41 | 02-JAN-09:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 39.71 | 60.00 | 1001.72 | 35276.97 | 09-FEB-16:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 40.78 | 40.78 | 62.77 | 20029.32 | 15-MAR-08:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 39.49 | 39.49 | 29.64 | 20960.01 | 07-APR-08:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 39.08 | 39.08 | 14.56 | 14335.34 | 12-MAY-15:06 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 40.20 | 40.20 | 14.24 | 15346.71 | 24-JUN-15:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.09 | 41.09 | 12.35 | 14372.48 | 27-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 42.05 | 42.05 | 18.66 | 14480.36 | 16-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 41.94 | 41.94 | 29.41 | 16016.18 | 07-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 40.43 | 40.43 | 53.17 | 20071.52 | 24-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 39.59 | 39.59 | 131.21 | 24305.08 | 28-NOV-16:04 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 39.59 | 60.00 | 1999.58 | 39325.97 | 23-DEC-09:05 |
Annual Sum or Average | 0.00 | 606.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.08 | 39.08 | 12.35 | 14335.34 | ||
Maximum of Months | 0.00 | 0.00 | 42.05 | 60.00 | 3874.27 | 47147.41 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 39714.64 | 313170.39 | 12-JAN-16:01 | 9.28 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 91536.20 | 377655.60 | 20-FEB-16:01 | 9.81 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 192284.86 | 543670.45 | 10-MAR-19:03 | 11.18 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 314011.61 | 606629.25 | 26-APR-18:03 | 11.70 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 419861.91 | 722215.61 | 22-MAY-18:03 | 12.65 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 484909.60 | 802059.59 | 22-JUN-18:03 | 13.31 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 536038.59 | 832109.25 | 01-JUL-18:03 | 13.56 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 533089.36 | 835771.79 | 27-AUG-18:03 | 13.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 475974.63 | 805977.07 | 14-SEP-18:03 | 13.34 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 300915.30 | 612610.92 | 03-OCT-18:03 | 11.74 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 149097.06 | 438335.26 | 05-NOV-18:03 | 10.31 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 54133.22 | 402884.24 | 02-DEC-16:01 | 10.02 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 300383.49 | 0.00 | ||||||
Minimum of Months | 39714.64 | 313170.39 | 9.28 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 536038.59 | 835771.79 | 13.59 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.73 | 59.53 | 22339.34 | 45036.94 | 19-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.02 | 58.93 | 21895.14 | 44726.42 | 02-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.19 | 58.52 | 20562.83 | 42852.39 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.61 | 58.56 | 18602.37 | 38867.76 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.96 | 58.32 | 16599.19 | 34886.87 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.36 | 58.25 | 15079.48 | 31013.51 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.53 | 59.17 | 14441.69 | 28629.89 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.71 | 59.57 | 14905.16 | 30538.33 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.39 | 59.46 | 16290.62 | 34092.49 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.03 | 59.12 | 18243.08 | 38499.86 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.10 | 59.81 | 20241.64 | 42256.02 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.25 | 58.48 | 21740.36 | 44569.11 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 18392.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.73 | 58.25 | 14441.69 | 28629.89 | ||
Maximum of Months | 0.00 | 0.00 | 55.71 | 59.81 | 22339.34 | 45036.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.442146E+10 | 0.00 | 0.585799E+11 | 0.282740E+11 | 0.00 | 0.00 |
February | 0.980230E+09 | 0.00 | 0.140729E+12 | 0.268765E+11 | 0.00 | 0.00 |
March | 1843974.95 | 0.00 | 0.347040E+12 | 0.332737E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.566157E+12 | 0.384750E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.811077E+12 | 0.457405E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.935341E+12 | 0.461266E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109794E+13 | 0.474136E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.110559E+13 | 0.462664E+11 | 0.00 | 0.00 |
September | 3191.86 | 0.00 | 0.948320E+12 | 0.421999E+11 | 0.00 | 0.00 |
October | 273.03 | 0.00 | 0.572352E+12 | 0.398704E+11 | 0.00 | 0.00 |
November | 88366341.76 | 0.00 | 0.246967E+12 | 0.327542E+11 | 0.00 | 0.00 |
December | 0.196811E+10 | 0.00 | 0.808798E+11 | 0.291998E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.746001E+10 | 0.00 | 0.691097E+13 | 0.456471E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.585799E+11 | 0.268765E+11 | 0.00 | 0.00 |
Maximum of Months | 0.442146E+10 | 0.00 | 0.110559E+13 | 0.474136E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 4715.37 | 0.00 | 0.414961E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 8788.34 | 0.00 | 0.984670E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 10374.51 | 0.00 | 0.256342E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 5331.82 | 0.00 | 0.365398E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 13983.61 | 0.00 | 0.492159E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 15485.33 | 0.00 | 0.593928E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 24981.23 | 0.00 | 0.731211E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 28548.53 | 0.00 | 0.740364E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 22228.37 | 0.00 | 0.639558E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 11096.88 | 0.00 | 0.404807E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 14415.29 | 0.00 | 0.154323E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 6000.53 | 0.00 | 0.544276E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 165949.81 | 0.00 | 0.457248E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 4715.37 | 0.00 | 0.414961E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 28548.53 | 0.00 | 0.740364E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.282740E+11 | 0.585799E+11 | 0.442146E+10 | 0.126687E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268765E+11 | 0.140729E+12 | 0.980230E+09 | 0.417713E+11 | 0.473427E+09 | 0.00 | 0.00 | 0.00 |
March | 0.332737E+11 | 0.347040E+12 | 1843974.95 | 0.690378E+10 | 0.163899E+11 | 0.00 | 0.00 | 0.00 |
April | 0.384750E+11 | 0.566157E+12 | 0.00 | 0.100665E+11 | 0.806970E+11 | 0.00 | 0.00 | 0.00 |
May | 0.457405E+11 | 0.811077E+12 | 0.00 | 0.138724E+10 | 0.243865E+12 | 0.00 | 0.00 | 0.00 |
June | 0.461266E+11 | 0.935341E+12 | 0.00 | 0.00 | 0.376171E+12 | 0.00 | 0.00 | 0.00 |
July | 0.474136E+11 | 0.109794E+13 | 0.00 | 0.00 | 0.506299E+12 | 0.00 | 0.00 | 0.00 |
August | 0.462664E+11 | 0.110559E+13 | 0.00 | 0.00 | 0.512351E+12 | 0.00 | 0.00 | 0.00 |
September | 0.421999E+11 | 0.948320E+12 | 3191.86 | 0.00 | 0.398475E+12 | 0.00 | 0.00 | 0.00 |
October | 0.398704E+11 | 0.572352E+12 | 273.03 | 0.967167E+09 | 0.675301E+11 | 0.00 | 0.00 | 0.00 |
November | 0.327542E+11 | 0.246967E+12 | 88366341.76 | 0.121709E+11 | 0.592008E+10 | 0.00 | 0.00 | 0.00 |
December | 0.291998E+11 | 0.808798E+11 | 0.196811E+10 | 0.901249E+11 | 4331023.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456471E+12 | 0.691097E+13 | 0.746001E+10 | 0.290079E+12 | 0.220818E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.268765E+11 | 0.585799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.474136E+11 | 0.110559E+13 | 0.442146E+10 | 0.126687E+12 | 0.512351E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.414961E+10 | 4715.37 | 0.128291E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.984670E+10 | 8788.34 | 0.466768E+10 | 0.148350E+09 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.256342E+11 | 10374.51 | 0.247077E+09 | 0.507109E+10 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.365398E+11 | 5331.82 | 53747751.84 | 0.196477E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.492159E+11 | 13983.61 | 0.00 | 0.440138E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.593928E+11 | 15485.33 | 0.00 | 0.588437E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.731211E+11 | 24981.23 | 0.00 | 0.733146E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.740364E+11 | 28548.53 | 0.00 | 0.717610E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.639558E+11 | 22228.37 | 0.00 | 0.572659E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.404807E+11 | 11096.88 | 9711548.79 | 0.160911E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.154323E+11 | 14415.29 | 0.135223E+10 | 0.151093E+10 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.544276E+10 | 6000.53 | 0.100234E+11 | 2681502.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.457248E+12 | 165949.81 | 0.291830E+11 | 0.347671E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.414961E+10 | 4715.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.740364E+11 | 28548.53 | 0.128291E+11 | 0.733146E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.282740E+11 | 0.442146E+10 | 0.585799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268765E+11 | 0.980230E+09 | 0.140729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332737E+11 | 1843974.95 | 0.347040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384750E+11 | 0.00 | 0.566157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457405E+11 | 0.00 | 0.811077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.461266E+11 | 0.00 | 0.935341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.474136E+11 | 0.00 | 0.109794E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.462664E+11 | 0.00 | 0.110559E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.421999E+11 | 3191.86 | 0.948320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398704E+11 | 273.03 | 0.572352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327542E+11 | 88366341.76 | 0.246967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291998E+11 | 0.196811E+10 | 0.808798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456471E+12 | 0.746001E+10 | 0.691097E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.268765E+11 | 0.00 | 0.585799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.474136E+11 | 0.442146E+10 | 0.110559E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 4715.37 | 0.414961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 8788.34 | 0.984670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 10374.51 | 0.256342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 5331.82 | 0.365398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 13983.61 | 0.492159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 15485.33 | 0.593928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 24981.23 | 0.731211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 28548.53 | 0.740364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 22228.37 | 0.639558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 11096.88 | 0.404807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 14415.29 | 0.154323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 6000.53 | 0.544276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 165949.81 | 0.457248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 4715.37 | 0.414961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 28548.53 | 0.740364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137917E+11 | 0.00 | 0.00 | 23528618.66 | 0.00 | 0.00 | 0.282091E+11 | 0.00 | 1.02 |
February | 0.109895E+11 | 1018489.68 | 0.00 | 18498326.33 | 2999841.01 | 0.00 | 0.193684E+11 | 0.00 | 0.97 |
March | 0.588012E+10 | 0.160425E+09 | 0.00 | 17444139.40 | 0.557525E+09 | 0.00 | 0.125888E+11 | 0.00 | 0.88 |
April | 0.262057E+09 | 0.207682E+10 | 0.00 | 17944743.85 | 0.227009E+10 | 0.00 | 0.389453E+10 | 0.00 | 0.76 |
May | 0.00 | 0.162265E+11 | 0.00 | 6536623.19 | 0.135453E+10 | 0.00 | 0.287033E+09 | 0.00 | 0.72 |
June | 0.00 | 0.314845E+11 | 0.00 | 334175.74 | 0.262711E+09 | 0.00 | 5703052.15 | 0.00 | 0.78 |
July | 0.00 | 0.520713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.00 | 0.585181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 0.00 | 0.453891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 0.00 | 0.783126E+10 | 0.00 | 56340374.74 | 0.00 | 0.00 | 0.910446E+10 | 0.00 | 1.07 |
November | 0.00 | 0.138792E+09 | 0.00 | 0.109187E+09 | 0.00 | 0.00 | 0.337319E+11 | 0.00 | 1.13 |
December | 0.708099E+09 | 0.00 | 0.00 | 70504259.49 | 0.00 | 0.00 | 0.437067E+11 | 0.00 | 1.08 |
Annual Sum or Average | 0.316314E+11 | 0.213898E+12 | 0.00 | 0.320318E+09 | 0.444786E+10 | 0.00 | 0.150897E+12 | 0.00 | 0.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.137917E+11 | 0.585181E+11 | 0.00 | 0.109187E+09 | 0.227009E+10 | 0.00 | 0.437067E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.542295E+10 | 0.00 | 0.00 | 443096.33 | 0.00 | 0.127881E+09 | 0.267656E+09 | 0.00 | 2.57 |
February | 0.366975E+10 | 730676.68 | 0.00 | 1956087.41 | 0.00 | 30216492.45 | 0.539066E+09 | 0.00 | 2.50 |
March | 0.190471E+10 | 0.133293E+09 | 0.00 | 4199182.81 | 3559078.40 | 0.00 | 0.695872E+09 | 0.00 | 2.40 |
April | 0.192944E+09 | 0.851394E+09 | 0.00 | 3462079.00 | 11705295.41 | 0.00 | 0.410484E+09 | 0.00 | 2.39 |
May | 0.00 | 0.314263E+10 | 0.00 | 1056294.04 | 29893470.67 | 0.00 | 44511820.99 | 0.00 | 2.34 |
June | 0.00 | 0.504150E+10 | 0.00 | 50325.36 | 0.182069E+09 | 0.00 | 875569.47 | 0.00 | 2.31 |
July | 0.00 | 0.706416E+10 | 0.00 | 0.00 | 0.123015E+09 | 0.00 | 0.00 | 0.00 | 2.19 |
August | 0.00 | 0.712020E+10 | 0.00 | 0.00 | 0.105905E+09 | 0.00 | 0.00 | 0.00 | 2.16 |
September | 0.00 | 0.493779E+10 | 0.00 | 0.00 | 0.648767E+09 | 0.00 | 0.00 | 0.00 | 2.31 |
October | 0.529161E+09 | 0.970832E+09 | 0.00 | 2987371.79 | 0.126174E+09 | 0.00 | 0.382099E+09 | 0.00 | 2.55 |
November | 0.259376E+10 | 27679183.57 | 0.00 | 6219385.71 | 0.00 | 0.00 | 0.104494E+10 | 0.00 | 2.62 |
December | 0.523673E+10 | 0.00 | 0.00 | 1050636.40 | 0.00 | 22153096.42 | 0.381227E+09 | 0.00 | 2.55 |
Annual Sum or Average | 0.195500E+11 | 0.292902E+11 | 0.00 | 21424458.85 | 0.123109E+10 | 0.180251E+09 | 0.376673E+10 | 0.00 | 2.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
Maximum of Months | 0.542295E+10 | 0.712020E+10 | 0.00 | 6219385.71 | 0.648767E+09 | 0.127881E+09 | 0.104494E+10 | 0.00 | 2.62 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.408863E+10 | 0.00 | 0.00 | 59137.74 | 0.00 | 0.00 | 0.175905E+09 | 0.00 | 1.63 |
February | 0.245307E+10 | 0.00 | 0.00 | 623409.00 | 413455.39 | 0.00 | 0.653773E+09 | 0.00 | 1.56 |
March | 0.734794E+09 | 59050401.71 | 0.00 | 3059548.32 | 18397164.29 | 0.00 | 0.119926E+10 | 0.00 | 1.46 |
April | 23995082.23 | 0.493586E+09 | 0.00 | 3841194.82 | 23130911.14 | 0.00 | 0.467050E+09 | 0.00 | 1.43 |
May | 0.00 | 0.210407E+10 | 0.00 | 934304.63 | 20494187.83 | 0.00 | 39817966.66 | 0.00 | 1.42 |
June | 0.00 | 0.357012E+10 | 0.00 | 41912.51 | 57546865.94 | 0.00 | 719329.53 | 0.00 | 1.41 |
July | 0.00 | 0.501232E+10 | 0.00 | 0.00 | 50033195.53 | 0.00 | 0.00 | 0.00 | 1.35 |
August | 0.00 | 0.505898E+10 | 0.00 | 0.00 | 64340636.78 | 0.00 | 0.00 | 0.00 | 1.35 |
September | 0.00 | 0.355703E+10 | 0.00 | 0.00 | 0.290665E+09 | 0.00 | 0.00 | 0.00 | 1.39 |
October | 52511233.14 | 0.591839E+09 | 0.00 | 3047181.44 | 80244495.90 | 0.00 | 0.637378E+09 | 0.00 | 1.40 |
November | 0.105230E+10 | 8679848.43 | 0.00 | 2576062.60 | 4559263.66 | 0.00 | 0.162591E+10 | 0.00 | 1.49 |
December | 0.363826E+10 | 0.00 | 0.00 | 199297.10 | 0.00 | 0.00 | 0.492464E+09 | 0.00 | 1.61 |
Annual Sum or Average | 0.120436E+11 | 0.204557E+11 | 0.00 | 14382048.15 | 0.609825E+09 | 0.00 | 0.529228E+10 | 0.00 | 1.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
Maximum of Months | 0.408863E+10 | 0.505898E+10 | 0.00 | 3841194.82 | 0.290665E+09 | 0.00 | 0.162591E+10 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.503090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3485061.84 | 0.00 | 0.00 | 0.90 |
February | 0.366432E+10 | 0.00 | 0.00 | 0.00 | 488087.39 | 0.00 | 0.00 | 0.00 | 0.87 |
March | 0.222643E+10 | 7593513.91 | 0.00 | 49864.97 | 79098004.24 | 0.00 | 11681635.92 | 0.00 | 0.78 |
April | 0.284395E+09 | 0.409661E+09 | 0.00 | 1791714.36 | 0.151520E+09 | 0.00 | 0.226419E+09 | 0.00 | 0.71 |
May | 0.00 | 0.242772E+10 | 0.00 | 1018075.71 | 53002479.98 | 0.00 | 43949394.92 | 0.00 | 0.77 |
June | 0.00 | 0.420351E+10 | 0.00 | 49672.25 | 0.170955E+09 | 0.00 | 857804.16 | 0.00 | 0.80 |
July | 0.00 | 0.625738E+10 | 0.00 | 0.00 | 40406221.88 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.609734E+10 | 0.00 | 0.00 | 59097490.35 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.334148E+10 | 0.00 | 0.00 | 0.945533E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.716184E+09 | 0.322396E+09 | 0.00 | 261416.75 | 0.407723E+09 | 0.00 | 61803315.88 | 0.00 | 0.72 |
November | 0.311755E+10 | 0.00 | 0.00 | 0.00 | 15586961.23 | 0.00 | 0.00 | 0.00 | 0.82 |
December | 0.487659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Annual Sum or Average | 0.199164E+11 | 0.230671E+11 | 0.00 | 3170744.04 | 0.192341E+10 | 3485061.84 | 0.344712E+09 | 0.00 | 0.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.503090E+10 | 0.625738E+10 | 0.00 | 1791714.36 | 0.945533E+09 | 3485061.84 | 0.226419E+09 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
February | 0.199804E+10 | 0.00 | 0.00 | 0.00 | 266138.92 | 0.00 | 0.00 | 0.00 | 0.82 |
March | 0.121900E+10 | 549794.32 | 0.00 | 4267.01 | 46720402.06 | 0.00 | 1391984.75 | 0.00 | 0.74 |
April | 0.183773E+09 | 0.212128E+09 | 0.00 | 721495.21 | 87340478.96 | 0.00 | 92463654.63 | 0.00 | 0.66 |
May | 0.00 | 0.127165E+10 | 0.00 | 522949.19 | 36503343.44 | 0.00 | 22588212.53 | 0.00 | 0.70 |
June | 0.00 | 0.220091E+10 | 0.00 | 25681.12 | 0.107847E+09 | 0.00 | 443554.34 | 0.00 | 0.73 |
July | 0.00 | 0.328023E+10 | 0.00 | 0.00 | 33711130.48 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.319086E+10 | 0.00 | 0.00 | 48803843.54 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.167535E+10 | 0.00 | 0.00 | 0.606963E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.405354E+09 | 0.147066E+09 | 0.00 | 65627.22 | 0.247769E+09 | 0.00 | 18926285.06 | 0.00 | 0.68 |
November | 0.169990E+10 | 0.00 | 0.00 | 0.00 | 8499086.58 | 0.00 | 0.00 | 0.00 | 0.77 |
December | 0.265906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.109102E+11 | 0.119787E+11 | 0.00 | 1340019.74 | 0.122442E+10 | 0.00 | 0.135814E+09 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.274510E+10 | 0.328023E+10 | 0.00 | 721495.21 | 0.606963E+09 | 0.00 | 92463654.63 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210333E+09 | 0.00 | 0.00 | 86164686.81 | 0.00 | 0.00 | 0.547401E+11 | 0.00 | 20.45 |
February | 84070938.32 | 4510481.00 | 0.00 | 90426261.76 | 0.00 | 0.00 | 0.397159E+11 | 0.00 | 19.64 |
March | 0.00 | 0.939335E+09 | 0.00 | 0.100625E+09 | 0.00 | 0.00 | 0.238682E+11 | 0.00 | 17.91 |
April | 0.00 | 0.576445E+10 | 0.00 | 49503490.85 | 0.00 | 0.00 | 0.533876E+10 | 0.00 | 15.65 |
May | 0.00 | 0.230985E+11 | 0.00 | 7309305.17 | 0.00 | 0.00 | 0.330431E+09 | 0.00 | 14.49 |
June | 0.00 | 0.382830E+11 | 0.00 | 346626.28 | 0.00 | 0.00 | 6126726.24 | 0.00 | 14.36 |
July | 0.00 | 0.553115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
August | 0.00 | 0.577132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 |
September | 0.00 | 0.443728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
October | 0.00 | 0.810174E+10 | 0.00 | 49253457.93 | 0.00 | 0.00 | 0.805643E+10 | 0.00 | 16.40 |
November | 19328100.73 | 0.149055E+09 | 0.00 | 0.104118E+09 | 0.00 | 0.00 | 0.339074E+11 | 0.00 | 18.47 |
December | 0.153861E+09 | 0.00 | 0.00 | 90393299.35 | 0.00 | 0.00 | 0.534525E+11 | 0.00 | 20.23 |
Annual Sum or Average | 0.467593E+09 | 0.233738E+12 | 0.00 | 0.578140E+09 | 0.00 | 0.00 | 0.219416E+12 | 0.00 | 16.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
Maximum of Months | 0.210333E+09 | 0.577132E+11 | 0.00 | 0.104118E+09 | 0.00 | 0.00 | 0.547401E+11 | 0.00 | 20.45 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.803657E+10 | 0.00 | 0.00 | 15735272.22 | 0.00 | 0.00 | 0.139198E+11 | 0.00 | 3.47 |
February | 0.397307E+10 | 2733234.48 | 0.00 | 25762058.39 | 0.00 | 0.00 | 0.123251E+11 | 0.00 | 3.45 |
March | 0.144668E+10 | 0.489179E+09 | 0.00 | 33780860.93 | 2081581.45 | 0.00 | 0.895235E+10 | 0.00 | 3.35 |
April | 98194772.25 | 0.292937E+10 | 0.00 | 19096104.51 | 23670841.78 | 0.00 | 0.247683E+10 | 0.00 | 3.19 |
May | 0.00 | 0.110844E+11 | 0.00 | 4527211.95 | 42047803.16 | 0.00 | 0.190825E+09 | 0.00 | 3.02 |
June | 0.00 | 0.183953E+11 | 0.00 | 206976.76 | 0.161534E+09 | 0.00 | 3530540.68 | 0.00 | 2.97 |
July | 0.00 | 0.264687E+11 | 0.00 | 0.00 | 0.218021E+09 | 0.00 | 0.00 | 0.00 | 2.95 |
August | 0.00 | 0.271567E+11 | 0.00 | 0.00 | 0.175579E+09 | 0.00 | 0.00 | 0.00 | 2.98 |
September | 0.00 | 0.206073E+11 | 0.00 | 0.00 | 0.615937E+09 | 0.00 | 0.00 | 0.00 | 3.16 |
October | 0.210029E+09 | 0.393533E+10 | 0.00 | 20617539.01 | 0.143260E+09 | 0.00 | 0.358813E+10 | 0.00 | 3.49 |
November | 0.120146E+10 | 99019435.98 | 0.00 | 43693962.79 | 0.00 | 0.00 | 0.133660E+11 | 0.00 | 3.66 |
December | 0.507880E+10 | 0.00 | 0.00 | 21651491.25 | 0.00 | 0.00 | 0.163033E+11 | 0.00 | 3.48 |
Annual Sum or Average | 0.200448E+11 | 0.111168E+12 | 0.00 | 0.185071E+09 | 0.138213E+10 | 0.00 | 0.711258E+11 | 0.00 | 3.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 |
Maximum of Months | 0.803657E+10 | 0.271567E+11 | 0.00 | 43693962.79 | 0.615937E+09 | 0.00 | 0.163033E+11 | 0.00 | 3.66 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495045E+11 | 0.00 | 0.00 | 15550284.81 | 0.00 | 0.00 | 0.265724E+11 | 0.00 | 1.73 |
February | 0.223733E+11 | 5064639.33 | 0.00 | 38015918.59 | 2306993.55 | 0.00 | 0.335369E+11 | 0.00 | 1.67 |
March | 0.542931E+10 | 0.128238E+10 | 0.00 | 83733196.63 | 0.102872E+09 | 0.00 | 0.303153E+11 | 0.00 | 1.58 |
April | 0.159692E+09 | 0.870653E+10 | 0.00 | 70075408.85 | 0.312491E+09 | 0.00 | 0.901174E+10 | 0.00 | 1.51 |
May | 0.00 | 0.368639E+11 | 0.00 | 16575530.50 | 0.368772E+09 | 0.00 | 0.705799E+09 | 0.00 | 1.48 |
June | 0.00 | 0.633226E+11 | 0.00 | 752288.04 | 0.644131E+09 | 0.00 | 12813511.88 | 0.00 | 1.48 |
July | 0.00 | 0.921274E+11 | 0.00 | 0.00 | 0.659481E+09 | 0.00 | 0.00 | 0.00 | 1.49 |
August | 0.00 | 0.940750E+11 | 0.00 | 0.00 | 0.674797E+09 | 0.00 | 0.00 | 0.00 | 1.50 |
September | 0.00 | 0.693635E+11 | 0.00 | 0.00 | 0.187786E+10 | 0.00 | 0.00 | 0.00 | 1.53 |
October | 0.361954E+09 | 0.119882E+11 | 0.00 | 68536794.38 | 0.491763E+09 | 0.00 | 0.131048E+11 | 0.00 | 1.56 |
November | 0.539523E+10 | 0.231950E+09 | 0.00 | 94065888.72 | 4736038.94 | 0.00 | 0.446172E+11 | 0.00 | 1.63 |
December | 0.343431E+11 | 0.00 | 0.00 | 28191489.90 | 0.00 | 0.00 | 0.395275E+11 | 0.00 | 1.71 |
Annual Sum or Average | 0.117567E+12 | 0.377966E+12 | 0.00 | 0.415497E+09 | 0.513921E+10 | 0.00 | 0.197404E+12 | 0.00 | 1.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
Maximum of Months | 0.495045E+11 | 0.940750E+11 | 0.00 | 94065888.72 | 0.187786E+10 | 0.00 | 0.446172E+11 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63419733.74 | 0.00 | 0.00 | 4717941.05 | 0.00 | 0.507011E+09 | 0.671485E+09 | 0.00 | 0.36 |
February | 9926252.77 | 4695713.25 | 30540.32 | 8078825.35 | 0.00 | 0.126177E+09 | 0.694151E+09 | 5185.51 | 0.36 |
March | 47821.46 | 0.137926E+09 | 54671.98 | 8395789.89 | 0.00 | 993972.93 | 0.332323E+09 | 13776.99 | 0.36 |
April | 0.00 | 0.420102E+09 | 241374.33 | 2035339.27 | 0.00 | 50099.38 | 23470547.18 | 29396.45 | 0.36 |
May | 0.00 | 0.106998E+10 | 570452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18566.65 | 0.36 |
June | 0.00 | 0.157402E+10 | 796971.98 | 0.00 | 0.00 | 0.00 | 0.00 | 21256.51 | 0.36 |
July | 0.00 | 0.214597E+10 | 1081748.24 | 0.00 | 0.00 | 0.00 | 0.00 | 22331.85 | 0.36 |
August | 0.00 | 0.215758E+10 | 1803157.78 | 0.00 | 0.00 | 0.00 | 0.00 | 35655.68 | 0.36 |
September | 0.00 | 0.170395E+10 | 2622833.59 | 0.00 | 0.00 | 0.00 | 0.00 | 73386.09 | 0.36 |
October | 0.00 | 0.584247E+09 | 339959.07 | 1735015.90 | 0.00 | 264738.60 | 45134838.75 | 52846.39 | 0.36 |
November | 0.00 | 33617256.24 | 84356.96 | 9604594.04 | 0.00 | 1496578.32 | 0.610954E+09 | 9214.38 | 0.36 |
December | 27020864.83 | 14980.55 | 0.00 | 6337436.94 | 0.00 | 0.222516E+09 | 0.951816E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.100415E+09 | 0.983209E+10 | 7626066.52 | 40904942.43 | 0.00 | 0.858509E+09 | 0.332933E+10 | 281616.50 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 63419733.74 | 0.215758E+10 | 2622833.59 | 9604594.04 | 0.00 | 0.507011E+09 | 0.951816E+09 | 73386.09 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174638E+09 | 0.00 | 0.00 | 1418756.06 | 0.00 | 0.763896E+09 | 0.306534E+09 | 0.00 | 0.36 |
February | 0.175959E+09 | 2593468.20 | 22138.42 | 3479122.90 | 2108700.45 | 0.204275E+09 | 0.454521E+09 | 6577.65 | 0.36 |
March | 0.112895E+09 | 0.124023E+09 | 117643.67 | 5225415.12 | 13820115.15 | 818255.85 | 0.222782E+09 | 17055.55 | 0.36 |
April | 12179687.65 | 0.409965E+09 | 268292.61 | 1263324.77 | 10060984.75 | 21947.92 | 12088031.23 | 29626.15 | 0.36 |
May | 0.00 | 0.106801E+10 | 575355.72 | 0.00 | 1845138.57 | 0.00 | 0.00 | 16117.26 | 0.36 |
June | 0.00 | 0.157131E+10 | 726390.69 | 0.00 | 2588812.55 | 0.00 | 0.00 | 20792.28 | 0.36 |
July | 0.00 | 0.214572E+10 | 1081255.94 | 0.00 | 0.00 | 0.00 | 0.00 | 22694.80 | 0.36 |
August | 0.00 | 0.215714E+10 | 1986218.80 | 0.00 | 0.00 | 0.00 | 0.00 | 38392.27 | 0.36 |
September | 0.00 | 0.169951E+10 | 2727498.23 | 0.00 | 4126082.65 | 0.00 | 0.00 | 84739.33 | 0.36 |
October | 28962401.76 | 0.502588E+09 | 585467.51 | 670316.62 | 81353935.11 | 23647.01 | 17472705.35 | 43767.27 | 0.36 |
November | 0.166864E+09 | 27101132.73 | 53989.59 | 4798942.52 | 6528690.10 | 2349198.67 | 0.447970E+09 | 23065.43 | 0.36 |
December | 0.167716E+09 | 14978.80 | 0.00 | 1941567.19 | 0.00 | 0.550567E+09 | 0.487324E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.839214E+09 | 0.970797E+10 | 8144251.17 | 18797445.19 | 0.122432E+09 | 0.152195E+10 | 0.194869E+10 | 302828.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.175959E+09 | 0.215714E+10 | 2727498.23 | 5225415.12 | 81353935.11 | 0.763896E+09 | 0.487324E+09 | 84739.33 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200385E+09 | 0.00 | 0.00 | 2955633.84 | 0.00 | 0.00 | 0.785718E+09 | 0.00 | 0.02 |
February | 67956988.33 | 11510482.14 | 0.00 | 3194808.58 | 0.00 | 0.00 | 0.414996E+09 | 0.00 | 0.02 |
March | 0.00 | 0.123016E+09 | 0.00 | 1835800.94 | 0.00 | 0.00 | 0.168184E+09 | 0.00 | 0.02 |
April | 0.00 | 0.253532E+09 | 0.00 | 1083300.27 | 0.00 | 0.00 | 17091792.58 | 0.00 | 0.02 |
May | 0.00 | 0.698570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.103968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.148105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.155811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.115673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.413957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 0.00 | 80142434.06 | 0.00 | 2770438.12 | 0.00 | 0.00 | 0.168378E+09 | 0.00 | 0.02 |
December | 15232300.21 | 0.00 | 0.00 | 3746875.71 | 0.00 | 0.00 | 0.828069E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.283575E+09 | 0.681629E+10 | 0.00 | 15586857.44 | 0.00 | 0.00 | 0.238244E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.200385E+09 | 0.155811E+10 | 0.00 | 3746875.71 | 0.00 | 0.00 | 0.828069E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236402E+10 | 0.00 | 0.00 | 38298987.19 | 0.00 | 0.283897E+09 | 0.142216E+11 | 0.00 | 0.40 |
February | 0.239980E+10 | 33284412.99 | 401710.15 | 57553452.41 | 30471492.80 | 70551013.07 | 0.884225E+10 | 13997.21 | 0.40 |
March | 0.156383E+10 | 0.160508E+10 | 6401239.75 | 57913957.64 | 0.259705E+09 | 11035743.27 | 0.300245E+10 | 399366.60 | 0.41 |
April | 0.169429E+09 | 0.551780E+10 | 8735840.30 | 11580191.05 | 0.174647E+09 | 305959.29 | 0.165296E+09 | 250828.87 | 0.41 |
May | 0.00 | 0.144434E+11 | 17940613.40 | 0.00 | 58470677.45 | 0.00 | 0.00 | 145185.82 | 0.41 |
June | 0.00 | 0.212287E+11 | 22054639.84 | 0.00 | 0.108349E+09 | 0.00 | 0.00 | 102952.95 | 0.41 |
July | 0.00 | 0.289518E+11 | 25973168.39 | 0.00 | 0.142521E+09 | 0.00 | 0.00 | 43116.51 | 0.41 |
August | 0.00 | 0.290772E+11 | 38092928.95 | 0.00 | 0.172369E+09 | 0.00 | 0.00 | 81582.11 | 0.41 |
September | 0.00 | 0.226327E+11 | 40104505.58 | 0.00 | 0.473986E+09 | 0.00 | 0.00 | 119970.34 | 0.41 |
October | 0.392858E+09 | 0.657654E+10 | 22174990.86 | 7354740.77 | 0.132995E+10 | 164923.47 | 0.238900E+09 | 691862.57 | 0.41 |
November | 0.228792E+10 | 0.342313E+09 | 1800618.41 | 60693880.13 | 0.112974E+09 | 20017194.74 | 0.606818E+10 | 125339.86 | 0.41 |
December | 0.227496E+10 | 203178.39 | 0.00 | 46075231.53 | 0.00 | 0.211560E+09 | 0.138471E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.114528E+11 | 0.130409E+12 | 0.183680E+09 | 0.279470E+09 | 0.286345E+10 | 0.597532E+09 | 0.463858E+11 | 1974202.83 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.239980E+10 | 0.290772E+11 | 40104505.58 | 60693880.13 | 0.132995E+10 | 0.283897E+09 | 0.142216E+11 | 691862.57 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58311388.72 | 0.00 | 0.00 | 4739365.79 | 0.00 | 0.487866E+09 | 0.695717E+09 | 0.00 | 0.36 |
February | 9118905.81 | 4695713.25 | 32715.23 | 8779474.21 | 0.00 | 0.124502E+09 | 0.695932E+09 | 3010.60 | 0.36 |
March | 0.00 | 0.137987E+09 | 5406.10 | 8902505.00 | 0.00 | 553443.01 | 0.332304E+09 | 1485.57 | 0.36 |
April | 0.00 | 0.420360E+09 | 12487.33 | 2207846.97 | 0.00 | 0.00 | 23348138.86 | 436.85 | 0.36 |
May | 0.00 | 0.107051E+10 | 58087.59 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 | 0.36 |
June | 0.00 | 0.157476E+10 | 76672.46 | 0.00 | 0.00 | 0.00 | 0.00 | 389.95 | 0.36 |
July | 0.00 | 0.214684E+10 | 231930.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3766.89 | 0.36 |
August | 0.00 | 0.215911E+10 | 303859.01 | 0.00 | 0.00 | 0.00 | 0.00 | 5513.58 | 0.36 |
September | 0.00 | 0.170599E+10 | 635775.18 | 0.00 | 0.00 | 0.00 | 0.00 | 15514.97 | 0.36 |
October | 0.00 | 0.584467E+09 | 163483.06 | 1884801.13 | 0.00 | 239810.86 | 45009981.25 | 9636.72 | 0.36 |
November | 0.00 | 33629323.08 | 74999.53 | 10253372.79 | 0.00 | 1334298.48 | 0.610467E+09 | 6504.97 | 0.36 |
December | 26682901.74 | 14980.55 | 0.00 | 6537850.77 | 0.00 | 0.244345E+09 | 0.930124E+09 | 0.00 | 0.35 |
Annual Sum or Average | 94113196.28 | 0.983836E+10 | 1595415.68 | 43305216.65 | 0.00 | 0.858840E+09 | 0.333290E+10 | 46355.25 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 58311388.72 | 0.215911E+10 | 635775.18 | 10253372.79 | 0.00 | 0.487866E+09 | 0.930124E+09 | 15514.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174281E+09 | 0.00 | 0.00 | 1245858.30 | 0.00 | 0.694082E+09 | 0.376878E+09 | 0.00 | 0.36 |
February | 0.175023E+09 | 2613388.59 | 17879.90 | 4158287.21 | 2095030.13 | 0.194867E+09 | 0.464186E+09 | 4586.10 | 0.36 |
March | 0.111662E+09 | 0.124098E+09 | 59325.57 | 5428321.50 | 13816835.07 | 740947.18 | 0.223889E+09 | 4142.49 | 0.36 |
April | 12179687.65 | 0.410211E+09 | 46669.09 | 1338233.95 | 10060984.75 | 12610.64 | 12022459.33 | 4599.14 | 0.36 |
May | 0.00 | 0.106854E+10 | 58044.08 | 0.00 | 1845138.57 | 0.00 | 0.00 | 131.84 | 0.36 |
June | 0.00 | 0.157195E+10 | 115379.64 | 0.00 | 2588812.55 | 0.00 | 0.00 | 811.92 | 0.36 |
July | 0.00 | 0.214659E+10 | 231754.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3914.56 | 0.36 |
August | 0.00 | 0.215885E+10 | 303286.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6050.12 | 0.36 |
September | 0.00 | 0.170163E+10 | 673512.70 | 0.00 | 4126082.65 | 0.00 | 0.00 | 16393.01 | 0.36 |
October | 28962401.76 | 0.502957E+09 | 248513.66 | 647543.39 | 81353935.11 | 16880.30 | 17502245.30 | 12223.64 | 0.36 |
November | 0.167454E+09 | 27088745.08 | 69974.95 | 5127873.83 | 6526489.79 | 4133557.24 | 0.445267E+09 | 21668.04 | 0.36 |
December | 0.168612E+09 | 14978.80 | 0.00 | 2010153.34 | 0.00 | 0.564232E+09 | 0.472695E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.838174E+09 | 0.971453E+10 | 1824340.71 | 19956271.52 | 0.122413E+09 | 0.145809E+10 | 0.201244E+10 | 74520.86 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.175023E+09 | 0.215885E+10 | 673512.70 | 5428321.50 | 81353935.11 | 0.694082E+09 | 0.472695E+09 | 21668.04 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
February | 0.193618E+11 | 0.00 | 0.00 | 0.00 | 2578990.63 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 0.115406E+11 | 60854894.23 | 0.00 | 710511.85 | 0.397212E+09 | 0.00 | 0.284845E+09 | 0.00 | 0.57 |
April | 0.103237E+10 | 0.228789E+10 | 0.00 | 10831384.48 | 0.674823E+09 | 0.00 | 0.166686E+10 | 0.00 | 0.52 |
May | 0.00 | 0.114996E+11 | 0.00 | 4754145.29 | 0.517882E+09 | 0.00 | 0.203940E+09 | 0.00 | 0.51 |
June | 0.00 | 0.180573E+11 | 0.00 | 217393.48 | 0.217232E+10 | 0.00 | 3724722.87 | 0.00 | 0.51 |
July | 0.00 | 0.267188E+11 | 0.00 | 0.00 | 0.198985E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.245079E+11 | 0.00 | 0.00 | 0.429049E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.127734E+11 | 0.00 | 0.00 | 0.920688E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.290006E+10 | 0.228250E+10 | 0.00 | 4564084.45 | 0.163787E+10 | 0.00 | 0.121377E+10 | 0.00 | 0.53 |
November | 0.164727E+11 | 0.00 | 0.00 | 0.00 | 82359486.78 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.257673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.103676E+12 | 0.981883E+11 | 0.00 | 21077519.55 | 0.209723E+11 | 0.00 | 0.337313E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.266011E+11 | 0.267188E+11 | 0.00 | 10831384.48 | 0.920688E+10 | 0.00 | 0.166686E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11757474.82 | 0.00 | 0.00 | 1207502.34 | 0.00 | 0.182637E+09 | 0.116057E+09 | 0.00 | 0.36 |
February | 1444591.06 | 1179545.47 | 2796.26 | 1824924.20 | 0.00 | 80962557.71 | 0.125351E+09 | 518.04 | 0.36 |
March | 0.00 | 34481291.60 | 14264.85 | 1752167.88 | 0.00 | 2021153.65 | 81666746.19 | 2979.71 | 0.36 |
April | 0.00 | 0.104994E+09 | 90501.82 | 421504.29 | 0.00 | 17735.76 | 5949756.40 | 8881.17 | 0.36 |
May | 0.00 | 0.267405E+09 | 232017.14 | 0.00 | 0.00 | 0.00 | 0.00 | 5177.62 | 0.36 |
June | 0.00 | 0.393395E+09 | 308063.78 | 0.00 | 0.00 | 0.00 | 0.00 | 6038.17 | 0.36 |
July | 0.00 | 0.536281E+09 | 478204.66 | 0.00 | 0.00 | 0.00 | 0.00 | 8629.92 | 0.36 |
August | 0.00 | 0.539110E+09 | 730873.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13731.04 | 0.36 |
September | 0.00 | 0.425991E+09 | 649543.92 | 0.00 | 0.00 | 0.00 | 0.00 | 20364.40 | 0.36 |
October | 0.00 | 0.146044E+09 | 102266.81 | 287138.39 | 0.00 | 60774.94 | 11435734.98 | 13319.22 | 0.36 |
November | 0.00 | 8408848.50 | 16909.54 | 1810466.50 | 0.00 | 19651099.49 | 0.134052E+09 | 1948.86 | 0.36 |
December | 4810940.72 | 3745.14 | 0.00 | 1428599.39 | 0.00 | 0.164230E+09 | 0.131453E+09 | 0.00 | 0.35 |
Annual Sum or Average | 18013006.61 | 0.245729E+10 | 2625442.04 | 8732303.00 | 0.00 | 0.449580E+09 | 0.605965E+09 | 81588.16 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 11757474.82 | 0.539110E+09 | 730873.27 | 1824924.20 | 0.00 | 0.182637E+09 | 0.134052E+09 | 20364.40 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43671722.37 | 0.00 | 0.00 | 375396.70 | 0.00 | 0.223708E+09 | 43866719.05 | 0.00 | 0.36 |
February | 43866852.30 | 660597.58 | 6782.05 | 698909.25 | 514944.59 | 94894233.09 | 70098601.69 | 396.97 | 0.36 |
March | 28027647.64 | 31005113.63 | 29466.03 | 1103002.08 | 3454208.77 | 1368373.37 | 54931034.08 | 5705.72 | 0.36 |
April | 3044921.91 | 0.102451E+09 | 105384.70 | 275642.57 | 2515246.19 | 7343.78 | 3060339.63 | 9538.11 | 0.36 |
May | 0.00 | 0.266914E+09 | 231191.30 | 0.00 | 461284.64 | 0.00 | 0.00 | 4005.26 | 0.36 |
June | 0.00 | 0.392691E+09 | 318046.17 | 0.00 | 647203.14 | 0.00 | 0.00 | 5803.52 | 0.36 |
July | 0.00 | 0.536218E+09 | 478344.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8432.68 | 0.36 |
August | 0.00 | 0.539046E+09 | 730743.34 | 0.00 | 0.00 | 0.00 | 0.00 | 13773.72 | 0.36 |
September | 0.00 | 0.424900E+09 | 656720.94 | 0.00 | 1031520.66 | 0.00 | 0.00 | 22781.85 | 0.36 |
October | 7240600.44 | 0.125597E+09 | 183238.97 | 107789.84 | 20338483.78 | 7621.02 | 4426256.38 | 23644.63 | 0.36 |
November | 41462203.28 | 6779584.59 | 9220.59 | 765929.42 | 1631622.45 | 28036683.10 | 85230685.58 | 6291.84 | 0.36 |
December | 41908626.06 | 3744.70 | 0.00 | 410744.25 | 0.00 | 0.207959E+09 | 51608556.88 | 0.00 | 0.35 |
Annual Sum or Average | 0.209223E+09 | 0.242627E+10 | 2749138.96 | 3737414.12 | 30594514.20 | 0.555981E+09 | 0.313222E+09 | 100374.29 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 43866852.30 | 0.539046E+09 | 730743.34 | 1103002.08 | 20338483.78 | 0.223708E+09 | 85230685.58 | 23644.63 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37368413.09 | 0.00 | 0.00 | 14410799.97 | 0.00 | 0.509460E+09 | 0.144101E+10 | 0.00 | 0.40 |
February | 5282011.57 | 7599269.98 | 0.00 | 16264681.86 | 0.00 | 0.137409E+09 | 0.118751E+10 | 0.00 | 0.40 |
March | 0.00 | 0.221606E+09 | 20845.37 | 12194985.15 | 0.00 | 1269664.23 | 0.535444E+09 | 9060.64 | 0.41 |
April | 0.00 | 0.674710E+09 | 399778.82 | 2546123.61 | 0.00 | 113943.22 | 38385972.81 | 60514.26 | 0.41 |
May | 0.00 | 0.171852E+10 | 906449.95 | 0.00 | 0.00 | 0.00 | 0.00 | 35062.95 | 0.41 |
June | 0.00 | 0.252801E+10 | 1339505.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31410.81 | 0.41 |
July | 0.00 | 0.344684E+10 | 1589851.06 | 0.00 | 0.00 | 0.00 | 0.00 | 34830.73 | 0.41 |
August | 0.00 | 0.346546E+10 | 2782221.41 | 0.00 | 0.00 | 0.00 | 0.00 | 46372.63 | 0.41 |
September | 0.00 | 0.273791E+10 | 3088576.21 | 0.00 | 0.00 | 0.00 | 0.00 | 80224.77 | 0.41 |
October | 0.00 | 0.938465E+09 | 490803.88 | 2343563.57 | 0.00 | 425202.57 | 72935156.86 | 47418.87 | 0.41 |
November | 0.00 | 54143713.12 | 0.00 | 16872396.77 | 0.00 | 1667535.59 | 0.980556E+09 | 0.00 | 0.40 |
December | 1044620.40 | 24060.60 | 0.00 | 17172525.56 | 0.00 | 0.216417E+09 | 0.170506E+10 | 0.00 | 0.40 |
Annual Sum or Average | 43695045.06 | 0.157933E+11 | 10618032.68 | 81805076.49 | 0.00 | 0.866761E+09 | 0.596090E+10 | 344895.66 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 37368413.09 | 0.346546E+10 | 3088576.21 | 17172525.56 | 0.00 | 0.509460E+09 | 0.170506E+10 | 80224.77 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248736E+10 | 0.00 | 0.00 | 49588335.36 | 0.00 | 0.00 | 0.351523E+11 | 0.00 | 4.32 |
February | 0.556362E+09 | 3339899.18 | 0.00 | 61850387.27 | 0.00 | 0.00 | 0.286574E+11 | 0.00 | 4.34 |
March | 0.136750E+09 | 0.726950E+09 | 0.00 | 77169659.66 | 0.00 | 0.00 | 0.194668E+11 | 0.00 | 4.28 |
April | 1988592.02 | 0.475984E+10 | 0.00 | 43679465.64 | 0.00 | 0.00 | 0.490034E+10 | 0.00 | 4.07 |
May | 0.00 | 0.197007E+11 | 0.00 | 8245183.18 | 0.00 | 0.00 | 0.346506E+09 | 0.00 | 3.97 |
June | 0.00 | 0.336551E+11 | 0.00 | 369341.59 | 0.00 | 0.00 | 6305108.02 | 0.00 | 3.98 |
July | 0.00 | 0.485074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
August | 0.00 | 0.495727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
September | 0.00 | 0.368651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
October | 21314845.39 | 0.631212E+10 | 0.00 | 40344675.32 | 0.00 | 0.00 | 0.687504E+10 | 0.00 | 4.04 |
November | 0.210360E+09 | 0.114268E+09 | 0.00 | 73740961.42 | 0.00 | 0.00 | 0.258182E+11 | 0.00 | 4.19 |
December | 0.136209E+10 | 0.00 | 0.00 | 54601174.80 | 0.00 | 0.00 | 0.357703E+11 | 0.00 | 4.30 |
Annual Sum or Average | 0.477622E+10 | 0.200218E+12 | 0.00 | 0.409589E+09 | 0.00 | 0.00 | 0.156993E+12 | 0.00 | 4.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
Maximum of Months | 0.248736E+10 | 0.495727E+11 | 0.00 | 77169659.66 | 0.00 | 0.00 | 0.357703E+11 | 0.00 | 4.34 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.923578E+09 | 0.00 | 0.00 | 63139464.36 | 0.00 | 0.00 | 0.399213E+11 | 0.00 | 4.66 |
February | 0.268745E+09 | 3616457.84 | 0.00 | 73976426.53 | 0.00 | 0.00 | 0.313337E+11 | 0.00 | 4.68 |
March | 44639110.16 | 0.782212E+09 | 0.00 | 86710562.09 | 0.00 | 0.00 | 0.208882E+11 | 0.00 | 4.58 |
April | 0.00 | 0.506234E+10 | 0.00 | 46743781.14 | 0.00 | 0.00 | 0.516099E+10 | 0.00 | 4.31 |
May | 0.00 | 0.208390E+11 | 0.00 | 8604421.81 | 0.00 | 0.00 | 0.361056E+09 | 0.00 | 4.18 |
June | 0.00 | 0.355513E+11 | 0.00 | 383303.19 | 0.00 | 0.00 | 6543125.73 | 0.00 | 4.20 |
July | 0.00 | 0.512484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
August | 0.00 | 0.524793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
September | 0.00 | 0.392066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
October | 6682364.51 | 0.673324E+10 | 0.00 | 44052114.94 | 0.00 | 0.00 | 0.729204E+10 | 0.00 | 4.30 |
November | 90421362.38 | 0.124520E+09 | 0.00 | 84615511.15 | 0.00 | 0.00 | 0.278128E+11 | 0.00 | 4.50 |
December | 0.562397E+09 | 0.00 | 0.00 | 68638627.72 | 0.00 | 0.00 | 0.397367E+11 | 0.00 | 4.65 |
Annual Sum or Average | 0.189646E+10 | 0.212031E+12 | 0.00 | 0.476864E+09 | 0.00 | 0.00 | 0.172513E+12 | 0.00 | 4.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
Maximum of Months | 0.923578E+09 | 0.524793E+11 | 0.00 | 86710562.09 | 0.00 | 0.00 | 0.399213E+11 | 0.00 | 4.68 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.108876E+09 | 0.00 | 0.00 | 0.515091E+11 | 0.00 | 20.36 |
February | 0.00 | 6623962.98 | 0.00 | 0.112227E+09 | 0.00 | 0.00 | 0.364025E+11 | 0.00 | 20.18 |
March | 0.00 | 0.121535E+10 | 0.00 | 0.115403E+09 | 0.00 | 0.00 | 0.214607E+11 | 0.00 | 19.07 |
April | 0.00 | 0.713691E+10 | 0.00 | 52750724.65 | 0.00 | 0.00 | 0.482096E+10 | 0.00 | 17.21 |
May | 0.00 | 0.268814E+11 | 0.00 | 7603062.49 | 0.00 | 0.00 | 0.308045E+09 | 0.00 | 16.07 |
June | 0.00 | 0.437134E+11 | 0.00 | 330763.36 | 0.00 | 0.00 | 5710420.48 | 0.00 | 15.92 |
July | 0.00 | 0.629857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
August | 0.00 | 0.659295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
September | 0.00 | 0.502861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
October | 0.00 | 0.935646E+10 | 0.00 | 53560472.79 | 0.00 | 0.00 | 0.719380E+10 | 0.00 | 17.88 |
November | 0.00 | 0.216134E+09 | 0.00 | 0.122877E+09 | 0.00 | 0.00 | 0.299384E+11 | 0.00 | 19.52 |
December | 0.00 | 0.00 | 0.00 | 0.113449E+09 | 0.00 | 0.00 | 0.496133E+11 | 0.00 | 20.38 |
Annual Sum or Average | 0.00 | 0.267728E+12 | 0.00 | 0.687077E+09 | 0.00 | 0.00 | 0.201252E+12 | 0.00 | 18.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
Maximum of Months | 0.00 | 0.659295E+11 | 0.00 | 0.122877E+09 | 0.00 | 0.00 | 0.515091E+11 | 0.00 | 20.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271154E+09 | 0.00 | 0.00 | 1.31 |
February | 0.102370E+11 | 20388.89 | 0.00 | 1454.88 | 1343303.94 | 0.00 | 987824.69 | 0.00 | 1.26 |
March | 0.587802E+10 | 0.233674E+09 | 0.00 | 1748659.88 | 32230565.33 | 0.00 | 0.374455E+09 | 0.00 | 1.15 |
April | 0.822800E+09 | 0.175176E+10 | 0.00 | 4938918.16 | 0.110298E+09 | 0.00 | 0.596783E+09 | 0.00 | 1.11 |
May | 461764.60 | 0.713878E+10 | 0.00 | 2023631.64 | 0.188460E+09 | 0.00 | 95142460.98 | 0.00 | 1.13 |
June | 0.00 | 0.115451E+11 | 0.00 | 102274.23 | 0.658542E+09 | 0.00 | 1800214.51 | 0.00 | 1.14 |
July | 0.00 | 0.162780E+11 | 0.00 | 0.00 | 0.455082E+09 | 0.00 | 0.00 | 0.00 | 1.08 |
August | 0.00 | 0.158572E+11 | 0.00 | 0.00 | 0.755392E+09 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 0.00 | 0.898043E+10 | 0.00 | 0.00 | 0.332491E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
October | 0.189199E+10 | 0.155569E+10 | 0.00 | 2246125.66 | 0.650087E+09 | 0.00 | 0.280563E+09 | 0.00 | 1.10 |
November | 0.859025E+10 | 37764997.74 | 0.00 | 458827.80 | 5913775.54 | 0.00 | 0.119587E+09 | 0.00 | 1.19 |
December | 0.135054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119551E+09 | 0.00 | 0.00 | 1.29 |
Annual Sum or Average | 0.547206E+11 | 0.633785E+11 | 0.00 | 11519892.24 | 0.618226E+10 | 0.390705E+09 | 0.146932E+10 | 0.00 | 1.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
Maximum of Months | 0.137947E+11 | 0.162780E+11 | 0.00 | 4938918.16 | 0.332491E+10 | 0.271154E+09 | 0.596783E+09 | 0.00 | 1.31 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.153937E+12 | 0.975287E+10 | 0.126130E+12 | 0.506685E+12 | 0.165449E+12 |
February | 0.175121E+12 | 0.635589E+10 | 0.812849E+11 | 0.318141E+12 | 0.317222E+12 |
March | 0.227049E+12 | 0.290106E+10 | 0.403158E+11 | 0.143601E+12 | 0.712030E+12 |
April | 0.250461E+12 | -0.223599E+10 | -0.275452E+11 | -0.960308E+11 | 0.111695E+13 |
May | 0.266994E+12 | -0.973385E+10 | -0.139340E+12 | -0.444028E+12 | 0.153679E+13 |
June | 0.244674E+12 | -0.151620E+11 | -0.216416E+12 | -0.703529E+12 | 0.170765E+13 |
July | 0.204424E+12 | -0.206387E+11 | -0.296773E+12 | -0.972783E+12 | 0.191244E+13 |
August | 0.171137E+12 | -0.206763E+11 | -0.299631E+12 | -0.993579E+12 | 0.188212E+13 |
September | 0.184942E+12 | -0.156265E+11 | -0.218488E+12 | -0.770978E+12 | 0.162432E+13 |
October | 0.167737E+12 | -0.199754E+10 | -0.219116E+11 | -0.891632E+11 | 0.108276E+13 |
November | 0.148232E+12 | 0.497270E+10 | 0.631795E+11 | 0.244726E+12 | 0.538102E+12 |
December | 0.136122E+12 | 0.894296E+10 | 0.113968E+12 | 0.463703E+12 | 0.215388E+12 |
Annual Sum or Average | 0.233083E+13 | -0.531454E+11 | -0.795227E+12 | -0.239323E+13 | 0.128112E+14 |
Minimum of Months | 0.136122E+12 | -0.206763E+11 | -0.299631E+12 | -0.993579E+12 | 0.165449E+12 |
Maximum of Months | 0.266994E+12 | 0.975287E+10 | 0.126130E+12 | 0.506685E+12 | 0.191244E+13 |