Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:45:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13419.54 | 1182.83 | 1182.83 |
Net Site Energy | 13419.54 | 1182.83 | 1182.83 |
Total Source Energy | 33727.01 | 2972.78 | 2972.78 |
Net Source Energy | 33727.01 | 2972.78 | 2972.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 25.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4830.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 499.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 145.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 302.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2397.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 9207.98 | 4211.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 25.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4830.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 499.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 145.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 302.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2397.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 25.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4830.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 499.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 145.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 302.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 2397.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 490.69 | 213.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.82 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 811.61 | 371.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 490.69 | 213.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.82 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 811.61 | 371.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 9207.983 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 9207.983 | 100.00 |
Total On-Site and Utility Electric Sources | 9207.983 | 100.00 |
Total Electricity End Uses | 9207.983 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 6868.51 | 100.00 |
Air to Air Heat Recovery for Heating | 0.02 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6868.52 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 50.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7220.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-19:10 | 04-JAN-18:10 | - | - | - | - | - | - | - | - | - | - | 31-MAY-20:30 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 227334.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31547.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28957.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5615.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3709.36 | 208832.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 472906.68 | 313080.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 227334.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1243.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28957.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5615.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3709.36 | 208832.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1060.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1090.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 27.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2478.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1581.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 461.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 958.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2598.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 29161.68 | 4565.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1348.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 229.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2570.38 | 402.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1348.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 229.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2570.38 | 402.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.96 | 0.510100 | 0.524000 | 1.55 | 1.00 | 0.500000 | 0.000747 | 0.000072 | 1.55 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.307757 | 0.166067 | 0.524000 | 0.161265 | 0.524000 | 0.500000 | 0.002294 | 0.000010 | 0.161265 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.276401 | 0.214123 | 0.524000 | 0.144834 | 0.570994 | 0.500000 | 0.001779 | 0.000007 | 0.144834 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.284742 | 0.439532 | 0.524000 | 0.149205 | 1.00 | 0.500000 | 0.000867 | 0.000008 | 0.149205 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.155771 | 0.463542 | 0.524000 | 0.081624 | 1.00 | 0.500000 | 0.000822 | 0.000004 | 0.081624 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.20 | 0.018605 | 0.524000 | 1.67 | 0.524000 | 0.500000 | 0.020478 | 0.000081 | 1.67 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.29 | 0.111963 | 0.524000 | 0.673528 | 0.524000 | 0.500000 | 0.003403 | 0.000038 | 0.673528 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.75 | 0.209861 | 0.524000 | 2.49 | 0.559629 | 0.500000 | 0.001815 | 0.000127 | 2.49 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.54 | 0.771153 | 0.524000 | 0.806505 | 1.00 | 0.500000 | 0.000494 | 0.000050 | 0.806505 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114348 | 0.524000 | 1.16 | 0.524000 | 0.500000 | 0.003332 | 0.000062 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.31 | 0.109319 | 0.524000 | 1.21 | 0.524000 | 0.500000 | 0.003485 | 0.000064 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.20 | 0.064228 | 0.524000 | 1.16 | 0.524000 | 0.500000 | 0.010669 | 0.000053 | 1.16 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.766544 | 0.409682 | 0.524000 | 0.401669 | 1.00 | 0.500000 | 0.000930 | 0.000028 | 0.401669 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8174.58 | 0.000072 | 170.47 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1180.25 | 0.000010 | 25.12 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 851.79 | 0.000007 | 17.87 |
MECH_FLR_1 VAV BOX REHEAT COIL | 952.58 | 0.000008 | 20.08 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 513.47 | 0.000004 | 10.82 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9236.29 | 0.000081 | 193.06 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 4312.02 | 0.000038 | 90.92 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 14480.85 | 0.000127 | 303.58 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 1431.10 | 0.000013 | 40.81 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 1430.93 | 0.000013 | 40.81 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19405.06 | 0.000170 | 553.46 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19410.36 | 0.000170 | 553.63 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 1431.10 | 0.000013 | 40.81 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 1430.93 | 0.000013 | 40.81 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 5750.75 | 0.000050 | 122.15 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 357.77 | 0.000003 | 10.21 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 357.73 | 0.000003 | 10.20 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 2298.53 | 0.000020 | 65.57 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 7134.79 | 0.000062 | 150.09 |
DINING_FLR_6 VAV BOX REHEAT COIL | 7302.83 | 0.000064 | 153.42 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6096.05 | 0.000053 | 127.12 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 3147.47 | 0.000028 | 67.33 |
VAV WITH REHEAT HEATING COIL | 133777.87 | 0.001170 | 2343.43 |
FLR_3_DOAS HEATING COIL | 12429.56 | 0.000109 | 217.73 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.947750 | 0.000013 | 0.000318 |
ROOM_2_FLR_3 FAN COIL | 0.959474 | 0.000013 | 0.000321 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.37 | 0.000170 | 0.001759 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.44 | 0.000170 | 0.002215 |
ROOM_5_FLR_3 FAN COIL | 0.838638 | 0.000013 | 0.000284 |
ROOM_6_FLR_3 FAN COIL | 0.846375 | 0.000013 | 0.000286 |
ROOM_1_FLR_6 FAN COIL | 0.259215 | 0.000003 | 0.000086 |
ROOM_2_FLR_6 FAN COIL | 0.262184 | 0.000003 | 0.000087 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.05 | 0.000020 | 0.000360 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.947750 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.959474 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.37 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.44 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.838638 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.846375 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.259215 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.262184 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.05 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008764 | 12.80 | 0.008500 | 0.000318 | 0.947750 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008761 | 12.80 | 0.008500 | 0.000321 | 0.959474 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008676 | 12.80 | 0.008500 | 0.001759 | 5.37 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008863 | 12.80 | 0.008500 | 0.002215 | 6.44 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008800 | 12.80 | 0.008500 | 0.000284 | 0.838638 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008798 | 12.80 | 0.008500 | 0.000286 | 0.846375 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008742 | 12.80 | 0.008500 | 0.000086 | 0.259215 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008739 | 12.80 | 0.008500 | 0.000087 | 0.262184 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008850 | 12.80 | 0.008500 | 0.000360 | 1.05 | |
VAV WITH REHEAT COOLING COIL | 29.92 | 6.70 | 0.013643 | 11.09 | 0.008500 | 0.024599 | 22.08 | 860093.80 |
FLR_3_DOAS COOLING COIL | 35.20 | 6.70 | 0.017158 | 11.94 | 0.008500 | 0.003245 | 2.05 | 113467.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.24 | 11.66 | 22.08 | 22.08 | 0.300000 | 0.527943 | 22.08 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.08 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.08 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024599 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001170 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003245 | 0.000147 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000109 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.033561 | 5479.43 | |
HEATSYS1 PUMP | 0.002300 | 692.63 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002300 | 0.275990 |
COOLSYS1 | 0.033561 | 4.03 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 262894.65 | 262894.65 | 0.002300 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.033561 | 3793.60 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.033561 | 1173455.60 | 1176699.03 | 134.14 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
29 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
30 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
31 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
32 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
33 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
34 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
35 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
36 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
37 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
38 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
39 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
40 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
41 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
42 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
43 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
44 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
45 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
46 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
47 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
48 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
49 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
50 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
51 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
52 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
53 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
54 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
55 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
56 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
57 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
58 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
59 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
60 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
61 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
62 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
63 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
64 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
65 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
66 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
67 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
68 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
69 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
70 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
71 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
72 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
73 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
74 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
75 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
76 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
77 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
78 | 7 | -0.54138470E-12 | 0.12463713E-14 | -0.64276224E-14 | 0.11113167E-15 |
79 | 6 | 0.12246794E-07 | 0.15689727E-09 | 0.20336639E-09 | -0.66085082E-11 |
80 | 5 | -0.43638646E-04 | 0.91064443E-06 | -0.10338442E-05 | 0.73798452E-07 |
81 | 4 | 0.19644206E-01 | 0.40532412E-03 | 0.96204216E-03 | -0.14823791E-03 |
82 | 3 | -1.4347347 | 0.16410182E-01 | -0.13915079 | 0.27725787E-01 |
83 | 2 | 17.082538 | 0.80550987E-01 | 2.2432332 | -0.47694951 |
84 | 1 | -41.597683 | 0.53207822E-01 | -6.4041654 | 1.4049886 |
85 | 0 | 26.083068 | 0.22662127E-02 | 4.4519555 | |
86 | 7 | -0.64276224E-14 | 0.12463713E-14 | -0.54138470E-12 | 0.11113167E-15 |
87 | 6 | 0.20336639E-09 | 0.15689727E-09 | 0.12246794E-07 | -0.66085082E-11 |
88 | 5 | -0.10338442E-05 | 0.91064443E-06 | -0.43638646E-04 | 0.73798452E-07 |
89 | 4 | 0.96204216E-03 | 0.40532412E-03 | 0.19644206E-01 | -0.14823791E-03 |
90 | 3 | -0.13915079 | 0.16410182E-01 | -1.4347347 | 0.27725787E-01 |
91 | 2 | 2.2432332 | 0.80550987E-01 | 17.082538 | -0.47694951 |
92 | 1 | -6.4041654 | 0.53207822E-01 | -41.597683 | 1.4049886 |
93 | 0 | 4.4519555 | 0.22662127E-02 | 26.083068 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.496_SHGC_0.22 | 37 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.221 | ||
2 | RESWINDOW_U_0.496_SHGC_0.22 | 38 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.13126 | 0.64145 | 0.64145 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.13126 | 0.64145 | 0.64145 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2957E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.0672E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.4172E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.0001E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.5901E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5388E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.5663E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.5002E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.9149E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.6492E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.0526E-002 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.5894E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1055E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.0344E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.8836E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.1652E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.8428E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9890E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4624E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.7537E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.2609E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 4.9811E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5273E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.9357E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.8428E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9890E-003 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4624E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.7537E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.2609E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 4.9811E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5273E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.9357E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 40665.31243 | 40665.31243 | 2.95602 | 2.95602 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 22:00:00 | 29.42000 | 1.71471E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 20.10000 | 1.47983E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4232.94196 | 4232.94196 | 0.30776 | 0.30776 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 324.65527 | 324.65527 | 1.39232E-002 | 7.92179E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3801.83785 | 3801.83785 | 0.27640 | 0.27640 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 31.57333 | 1.71512E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 82.51099 | 82.51099 | 3.53841E-003 | 9.17347E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3917.36287 | 3917.36287 | 0.28474 | 0.28474 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:00:00 | 31.88500 | 1.71518E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 159.59012 | 159.59012 | 6.84389E-003 | 6.84389E-003 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2143.02305 | 2143.02305 | 0.15577 | 0.15577 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | 33.58500 | 1.71551E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 79.46652 | 79.46652 | 3.40785E-003 | 5.77652E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 43965.67783 | 43965.67783 | 3.19617 | 3.19617 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 346.42120 | 346.42120 | 1.48566E-002 | 1.48566E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17664.61246 | 17664.61246 | 1.28536 | 1.28536 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 739.05556 | 739.05556 | 3.16948E-002 | 0.67639 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65317.16522 | 65317.16522 | 4.74999 | 4.74999 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:50:00 | 34.12333 | 1.71561E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 1257.68717 | 1257.68717 | 5.39348E-002 | 1.89399 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9674.59534 | 9674.59534 | 0.94775 | 0.94775 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 645.89486 | 645.89486 | 2.78628E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9794.28460 | 9794.28460 | 0.95947 | 0.95947 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 651.55053 | 651.55053 | 2.81068E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 54826.76658 | 54826.76658 | 5.37043 | 5.37043 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 3785.88426 | 3785.88426 | 0.16331 | 0.83707 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 65780.54539 | 65780.54539 | 6.44386 | 6.44386 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 34.69000 | 1.71572E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 3897.39418 | 3897.39418 | 0.16812 | 0.83730 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8560.76195 | 8560.76195 | 0.83864 | 0.83864 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 645.89486 | 645.89486 | 2.78628E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8639.74007 | 8639.74007 | 0.84637 | 0.84637 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 651.55053 | 651.55053 | 2.81068E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21173.58795 | 21173.58795 | 1.53913 | 1.53913 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 33.86833 | 1.71556E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 1478.51568 | 1478.51568 | 6.34045E-002 | 0.47476 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2646.06269 | 2646.06269 | 0.25922 | 0.25922 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 205.86728 | 205.86728 | 8.88081E-003 | 1.54338E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2676.36507 | 2676.36507 | 0.26218 | 0.26218 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 206.87441 | 206.87441 | 8.92425E-003 | 1.54319E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10735.55580 | 10735.55580 | 1.05169 | 1.05169 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 1007.45176 | 1007.45176 | 4.34594E-002 | 9.91540E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30366.67268 | 30366.67268 | 2.21012 | 2.21012 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 1004.00371 | 1004.00371 | 4.30563E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31764.15153 | 31764.15153 | 2.31179 | 2.31179 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 888.19374 | 888.19374 | 3.80898E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30244.79292 | 30244.79292 | 2.20440 | 2.20440 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 34.43500 | 1.71567E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 20.10000 | 1.47983E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 10545.20364 | 10545.20364 | 0.76654 | 0.76654 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 1021.87002 | 1021.87002 | 4.38221E-002 | 0.12562 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 20.10000 | 1.47983E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 456457.42 | 22.07808 | 22.07808 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | FLR_3_DOAS | Cooling | Sensible | 55571.34 | 16.76814 | 2.05125 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.95602 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51010 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.54896 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.46912E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.15148E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.54896 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8174.57967 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15148E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 170.46677 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30776 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16607 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16126 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29425E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03254E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16126 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1180.25421 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03254E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 25.11670 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27640 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21412 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14483 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57099 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77935E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.45187E-006 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14483 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 851.79418 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.45187E-006 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 17.86867 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28474 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.43953 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14920 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.66831E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.33357E-006 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14920 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 952.57788 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33357E-006 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 20.08287 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15577 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46354 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.16242E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.21932E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.49207E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.16242E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 513.47146 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.49207E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10.81526 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.19617 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.86054E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.67480 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04779E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.08031E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.67480 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9236.29274 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.08031E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 193.05699 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28536 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11196 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.67353 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40291E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.77234E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67353 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4312.01596 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.77234E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 90.92483 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.74999 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20986 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.48900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55963 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81549E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26685E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.48900 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14480.84626 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26685E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.58478 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94775 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94775 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25199E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.17628E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68223 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76389E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.17628E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94775 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1431.09611 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25199E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81353 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95947 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95947 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25184E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.21319E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68224 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76105E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.21319E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95947 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1430.92813 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25184E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.80909 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.37043 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.37043 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69764E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.75886E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68317 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67628E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.75886E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.37043 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19405.05742 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69764E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 553.46392 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.44386 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.44386 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69810E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.21520E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68235 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86250E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.21520E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.44386 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19410.35754 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69810E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 553.63040 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83864 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.83864 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25199E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.83737E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68217 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80040E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.83737E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83864 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1431.09611 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25199E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.81353 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84637 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84637 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25184E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.86160E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68218 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79777E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86160E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84637 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1430.92813 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25184E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.80909 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53913 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.77115 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80650 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.94065E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.03101E-005 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80650 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5750.75263 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.03101E-005 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 122.14889 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25922 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.25922 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.12995E-006 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.63711E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68227 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74174E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.63711E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25922 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 357.77215 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12995E-006 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10.20571 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26218 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.26218 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.12958E-006 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.72963E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68228 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73895E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.72963E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26218 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 357.73019 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12958E-006 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10.20456 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05169 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05169 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.01086E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.60383E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68209 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85004E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.60383E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05169 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2298.53271 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01086E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 65.57085 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21012 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11435 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15810 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33192E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.24183E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15810 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7134.78947 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.24183E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.08647 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31179 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10932 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21138 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48521E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.38884E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21138 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7302.83364 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.38884E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.42013 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20440 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.42280E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15511 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06694E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.33309E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15511 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6096.04563 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.33309E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 127.12252 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76654 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40968 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40167 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.29990E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.75354E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40167 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3147.46924 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75354E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 67.33140 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65596 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65596 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.24420 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65596 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.07808 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.07808 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52794 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.07808 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.07808 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.91905 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09011 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.36435E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 860093.80104 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.45986E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.07808 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 133777.86667 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17035E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2343.43206 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.07808 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.45986E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.93585E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.17035E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.20000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94246 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71581E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 113467.38685 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.24515E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 12429.56338 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08739E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 217.73286 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.24515E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46739E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.08739E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.35607E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5479.43382 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.29992E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.27599 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.29992E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 692.63403 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 262894.65150 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 262894.65000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.29992E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.35607E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.02728 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.35607E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3793.59684 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.35607E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1173455.60337 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1176699.03000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 134.14369 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8216.80 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1186.23 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 856.17 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 957.45 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 516.10 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9283.89 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 4334.05 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 14555.25 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 1539.60 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 1539.43 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20877.31 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20883.35 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 1539.60 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 1539.43 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 5779.94 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 384.95 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 384.91 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 2473.22 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 7171.33 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 7340.28 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6127.53 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 3163.34 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 107180.50 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 9958.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 16007.91 | 13606.81 | 2401.10 | 0.85 | 2851.57 | 28.92 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16197.96 | 13772.19 | 2425.77 | 0.85 | 2886.95 | 29.28 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 89303.90 | 76580.24 | 12723.65 | 0.86 | 16165.91 | 163.96 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 110710.73 | 93218.34 | 17492.39 | 0.84 | 19393.26 | 196.70 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14254.60 | 12073.52 | 2181.08 | 0.85 | 2522.26 | 25.58 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14379.59 | 12182.48 | 2197.11 | 0.85 | 2545.59 | 25.82 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4361.36 | 3715.31 | 646.05 | 0.85 | 780.17 | 7.91 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4409.15 | 3757.06 | 652.09 | 0.85 | 789.14 | 8.00 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18030.80 | 15199.76 | 2831.04 | 0.84 | 3165.37 | 32.10 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 683959.32 | 448933.61 | 235025.71 | 0.66 | 96410.77 | 977.85 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 68584.33 | 43991.18 | 24593.14 | 0.64 | 9329.01 | 94.62 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1916999104E-002 | 1.6729446921E-002 | Pass | Pass | 1.2848602322E-003 | 2.3098480040E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3783689531E-002 | 1.8567081002E-002 | Pass | Pass | 2.5306847534E-003 | 2.5736682673E-003 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7288963518E-002 | 2.2608408561E-002 | Pass | Pass | 1.8858561477E-003 | 3.1848795514E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4525106531E-003 | 9.2446605616E-003 | Pass | Pass | 1.0503636116E-003 | 1.2977971569E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1801063483E-003 | 5.5156596380E-003 | Pass | Pass | 7.5328285194E-004 | 8.5824829863E-004 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4019393540E-002 | 0.2039434612 | Pass | Pass | 1.4633871837E-002 | 4.2792003824E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5864057583E-002 | 6.0595527103E-002 | Pass | Pass | 3.6795638785E-003 | 7.8977795268E-003 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4515426389E-002 | 3.6461960966E-002 | Pass | Pass | 2.5315871767E-003 | 4.7549087163E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2645231972E-002 | 0.3420548473 | Pass | Pass | 0.1408503107 | 0.4784154251 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1011588290 | 0.3331997090 | Pass | Pass | 0.1389593559 | 0.4411595318 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0481480860E-005 | 9.5910980772E-005 | Pass | Pass | 2.4678521899E-002 | 5.0569972282E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1056308158 | 0.2984793320 | Pass | Pass | 0.1291453823 | 0.3340771756 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2658115037E-002 | 0.3391769725 | Pass | Pass | 0.1542297969 | 0.6160403847 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1037755058 | 0.3323453485 | Pass | Pass | 0.1433676163 | 0.5404911529 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4263814746E-003 | 7.5165815622E-003 | Pass | Pass | 8.1542278697E-004 | 1.0876122871E-003 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2644787207E-002 | 0.3452022460 | Pass | Pass | 1.2746309149 | 13.4030580158 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1025065394 | 0.3370434079 | Pass | Pass | 0.1600511133 | 0.7009405525 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2659902355E-002 | 0.3370859050 | Pass | Pass | 0.1894703825 | 0.7825948750 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6386754348E-002 | 5.9925083180E-002 | Pass | Pass | 7.4359906170E-003 | 2.6132359525E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1355930866E-002 | 4.9334134813E-002 | Pass | Pass | 8.3391273618E-003 | 2.7149204192E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4567899269E-002 | 9.8935728939E-002 | Pass | Pass | 1.7658074741E-002 | 3.3373383143E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1216621388E-002 | 6.7663868777E-003 | Pass | Pass | 1.2344811869E-003 | 9.0273253557E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3144.90 | -210.9 | -3014.0 | -11873.3 | 21101.38 | 9148.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.820 | 0.221 | 0.243 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.820 | 0.221 | 0.243 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.820 | 0.221 | 0.243 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.820 | 0.221 | 0.243 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.820 | 0.221 | 0.243 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.820 | 0.221 | 0.243 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.221 | 0.243 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.221 | 0.243 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.820 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 432.95 | 2.820 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.820 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.44 | 0.0000 | Y | 14.35 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.55 | 0.0000 | Y | 30.88 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.55 | 0.0000 | Y | 30.88 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.83 | 83.83 | 194.17 | |
Exterior Lighting Total | 12338.45 | 194.17 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 262894.65 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1176699.03 | 2.96 | 1176905.86 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11106.12 | 16007.91 | 13606.81 | 2401.10 | 0.85 | - | 2851.57 | 28.92 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11235.20 | 16197.96 | 13772.19 | 2425.77 | 0.85 | - | 2886.95 | 29.28 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 61499.97 | 89303.90 | 76580.24 | 12723.65 | 0.86 | - | 16165.91 | 163.96 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 77456.42 | 110710.73 | 93218.34 | 17492.39 | 0.84 | - | 19393.26 | 196.70 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9921.11 | 14254.60 | 12073.52 | 2181.08 | 0.85 | - | 2522.26 | 25.58 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10005.81 | 14379.59 | 12182.48 | 2197.11 | 0.85 | - | 2545.59 | 25.82 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3020.04 | 4361.36 | 3715.31 | 646.05 | 0.85 | - | 780.17 | 7.91 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3052.39 | 4409.15 | 3757.06 | 652.09 | 0.85 | - | 789.14 | 8.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12601.09 | 18030.80 | 15199.76 | 2831.04 | 0.84 | - | 3165.37 | 32.10 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 860093.80 | 683959.32 | 448933.61 | 235025.71 | 0.66 | - | 96410.77 | 977.85 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 113467.39 | 68584.33 | 43991.18 | 24593.14 | 0.64 | - | 9329.01 | 94.62 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8174.58 | 8216.80 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1180.25 | 1186.23 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 851.79 | 856.17 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 952.58 | 957.45 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 513.47 | 516.10 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9236.29 | 9283.89 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4312.02 | 4334.05 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14480.85 | 14555.25 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1431.10 | 1539.60 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1430.93 | 1539.43 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19405.06 | 20877.31 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19410.36 | 20883.35 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1431.10 | 1539.60 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 1430.93 | 1539.43 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5750.75 | 5779.94 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 357.77 | 384.95 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 357.73 | 384.91 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2298.53 | 2473.22 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7134.79 | 7171.33 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7302.83 | 7340.28 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6096.05 | 6127.53 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 3147.47 | 3163.34 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 133777.87 | 107180.50 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 12429.56 | 9958.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 666.87 | 703.64 | 1.00 | 1.21 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 675.12 | 703.64 | 1.00 | 1.21 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.37 | 3778.83 | 703.64 | 1.00 | 0.97 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.44 | 4534.13 | 703.64 | 1.00 | 0.95 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 590.10 | 703.64 | 1.00 | 1.24 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 595.54 | 703.64 | 1.00 | 1.24 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 182.39 | 703.64 | 1.00 | 1.82 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 184.48 | 703.64 | 1.00 | 1.81 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 740.01 | 703.64 | 1.00 | 1.18 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1314.72 | 22.08 | 46809.37 | 2120.17 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.033561 | 5479.43 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002300 | 692.63 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033561 | 3793.60 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 40665.31 | 40665.31 | 20.55 | 2.956 | 2.956 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 22:00:00 | 24.00 | 24.00 | 0.00909 | 29.42 | 0.01715 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4232.94 | 4232.94 | 63.11 | 0.308 | 0.308 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00931 | 34.35 | 0.01716 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3801.84 | 3801.84 | 48.95 | 0.276 | 0.276 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 24.00 | 24.00 | 0.00935 | 31.57 | 0.01715 | 0.092 | 0.00 |
MECH_FLR_1 | 3917.36 | 3917.36 | 23.85 | 0.285 | 0.285 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:00:00 | 24.00 | 24.00 | 0.00890 | 31.89 | 0.01715 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2143.02 | 2143.02 | 22.62 | 0.156 | 0.156 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | 24.00 | 24.00 | 0.00897 | 33.59 | 0.01716 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 43965.68 | 43965.68 | 563.38 | 3.196 | 3.196 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 24.00 | 24.00 | 0.00857 | 34.46 | 0.01716 | 0.000 | 0.00 |
CAFE_FLR_1 | 17664.61 | 17664.61 | 93.53 | 1.285 | 1.285 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 23.99 | 0.01043 | 35.20 | 0.01716 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65317.17 | 65317.17 | 49.93 | 4.750 | 4.750 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:50:00 | 24.00 | 23.99 | 0.01005 | 34.12 | 0.01716 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9674.60 | 9674.60 | 247.93 | 0.948 | 0.948 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00876 | 34.58 | 0.01716 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9794.28 | 9794.28 | 251.02 | 0.959 | 0.959 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 21.11 | 21.11 | 0.00876 | 34.46 | 0.01716 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 54826.77 | 54826.77 | 2235.65 | 5.370 | 5.370 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 21.11 | 21.11 | 0.00868 | 35.03 | 0.01716 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 65780.55 | 65780.55 | 2681.58 | 6.444 | 6.444 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 21.11 | 21.11 | 0.00886 | 34.69 | 0.01716 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8560.76 | 8560.76 | 219.38 | 0.839 | 0.839 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 21.11 | 21.11 | 0.00880 | 31.73 | 0.01715 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8639.74 | 8639.74 | 221.43 | 0.846 | 0.846 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 21.11 | 21.11 | 0.00880 | 31.73 | 0.01715 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21173.59 | 21173.59 | 54.37 | 1.539 | 1.539 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 24.00 | 24.00 | 0.00953 | 33.87 | 0.01716 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2646.06 | 2646.06 | 67.81 | 0.259 | 0.259 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00874 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2676.37 | 2676.37 | 68.59 | 0.262 | 0.262 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00874 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10735.56 | 10735.56 | 437.64 | 1.052 | 1.052 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 21.11 | 21.11 | 0.00885 | 35.20 | 0.01716 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30366.67 | 30366.67 | 91.56 | 2.210 | 2.210 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 23.98 | 0.01040 | 35.12 | 0.01716 | 1.188 | 0.00 |
DINING_FLR_6 | 31764.15 | 31764.15 | 95.77 | 2.312 | 2.312 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 23.98 | 0.01032 | 35.12 | 0.01716 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30244.79 | 30244.79 | 292.77 | 2.204 | 2.204 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 24.00 | 23.97 | 0.01014 | 34.44 | 0.01716 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10545.20 | 10545.20 | 25.59 | 0.767 | 0.767 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 24.00 | 0.00910 | 35.20 | 0.01716 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.11 | 0.01480 | 20.10 | 0.01480 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 324.66 | 324.66 | 4.84 | 0.014 | 0.079 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01077 | 20.10 | 0.01480 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 82.51 | 82.51 | 1.06 | 0.004 | 0.092 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01149 | 20.10 | 0.01480 | 0.092 | 0.00 |
MECH_FLR_1 | 159.59 | 159.59 | 0.97 | 0.007 | 0.007 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01183 | 20.10 | 0.01480 | 0.000 | 0.00 |
STORAGE_FLR_1 | 79.47 | 79.47 | 0.84 | 0.003 | 0.058 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01208 | 20.10 | 0.01480 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 346.42 | 346.42 | 4.44 | 0.015 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01103 | 20.10 | 0.01480 | 0.000 | 0.00 |
CAFE_FLR_1 | 739.06 | 739.06 | 3.91 | 0.032 | 0.676 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01072 | 20.10 | 0.01480 | 0.676 | 0.00 |
LOBBY_FLR_1 | 1257.69 | 1257.69 | 0.96 | 0.054 | 1.894 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01161 | 20.10 | 0.01480 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 645.89 | 645.89 | 16.55 | 0.028 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01102 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 651.55 | 651.55 | 16.70 | 0.028 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01100 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3785.88 | 3785.88 | 154.38 | 0.163 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01085 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3897.39 | 3897.39 | 158.88 | 0.168 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01080 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 645.89 | 645.89 | 16.55 | 0.028 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01102 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 651.55 | 651.55 | 16.70 | 0.028 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01100 | 20.10 | 0.01480 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 1478.52 | 1478.52 | 3.80 | 0.063 | 0.475 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01002 | 20.10 | 0.01480 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 205.87 | 205.87 | 5.28 | 0.009 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | 21.11 | 21.11 | 0.01062 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 206.87 | 206.87 | 5.30 | 0.009 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.01061 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 1007.45 | 1007.45 | 41.07 | 0.043 | 0.099 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 21.11 | 21.11 | 0.01052 | 20.10 | 0.01480 | 0.099 | 0.00 |
BANQUET_FLR_6 | 1004.00 | 1004.00 | 3.03 | 0.043 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00963 | 20.10 | 0.01480 | 1.188 | 0.00 |
DINING_FLR_6 | 888.19 | 888.19 | 2.68 | 0.038 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 21.00 | 21.00 | 0.00979 | 20.10 | 0.01480 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 24.00 | 0.00885 | 20.10 | 0.01480 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 1021.87 | 1021.87 | 2.48 | 0.044 | 0.126 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 21.00 | 21.00 | 0.00945 | 20.10 | 0.01480 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.08 | 22.08 | 0.00 | 0.00 | 22.0781 | 11.6560 | 22.0781 | 0.5279 | 0.3000 |
FLR_3_DOAS | 16.77 | 2.05 | 0.00 | 0.00 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8174.580 | 8174.580 | 1.548957 | 0.00007151 | 170.467 | 12/21 00:10:00 | 12/21 00:10:00 | 8174.58 | 8174.58 | 1.548957 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 8220.52 | 8220.52 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 1180.254 | 1180.254 | 0.161265 | 0.00001033 | 25.117 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1180.25 | 1180.25 | 0.161265 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01077023 | 69.2833 | 324.66 | 0.00 | 1186.84 | 1186.84 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 851.794 | 851.794 | 0.144834 | 0.00000745 | 17.869 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 851.79 | 851.79 | 0.144834 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01148960 | 73.8307 | 82.51 | 0.00 | 856.57 | 856.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 952.578 | 952.578 | 0.149205 | 0.00000833 | 20.083 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 952.58 | 952.58 | 0.149205 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01182895 | 75.9705 | 159.59 | 0.00 | 957.91 | 957.91 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 513.471 | 513.471 | 0.081624 | 0.00000449 | 10.815 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 513.47 | 513.47 | 0.081624 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01207742 | 77.5360 | 79.47 | 0.00 | 516.35 | 516.35 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9236.293 | 9236.293 | 1.674795 | 0.00008080 | 193.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9236.29 | 9236.29 | 1.674795 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01102759 | 70.9100 | 346.42 | 0.00 | 9288.16 | 9288.16 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 4312.016 | 4312.016 | 0.673528 | 0.00003772 | 90.925 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4312.02 | 4312.02 | 0.673528 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01072256 | 68.9827 | 739.06 | 0.00 | 4336.16 | 4336.16 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14480.846 | 14480.846 | 2.488996 | 0.00012668 | 303.585 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14480.85 | 14480.85 | 2.488996 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01161195 | 74.6025 | 1257.69 | 0.00 | 14562.08 | 14562.08 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11106.117 | -999.000 | 0.947750 | 0.00031763 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 11106.12 | 10427.19 | 0.947750 | 21.68 | 15.78 | 0.00876389 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00876389 | 56.1801 | 9674.60 | 0.00 | 11121.87 | 10893.43 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 1431.096 | 1431.096 | 0.061735 | 0.00001252 | 40.814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.10 | 1431.10 | 0.061735 | 21.11 | 17.49 | 0.01101632 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01101632 | 70.3568 | 645.89 | 0.00 | 1542.81 | 1542.81 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11235.203 | -999.000 | 0.959474 | 0.00032132 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | 4/21 16:20:00 | 11235.20 | 10555.32 | 0.959474 | 21.68 | 15.78 | 0.00876105 | 12.80 | 12.09 | 0.00850000 | 34.46 | 0.01715674 | 25.64 | 0.0000 | 21.11 | 0.00876105 | 56.1622 | 9794.28 | 0.00 | 11251.19 | 11028.06 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 1430.928 | 1430.928 | 0.061728 | 0.00001252 | 40.809 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.93 | 1430.93 | 0.061728 | 21.11 | 17.48 | 0.01100157 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01100157 | 70.2642 | 651.55 | 0.00 | 1542.63 | 1542.63 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 61499.967 | -999.000 | 5.370425 | 0.00175886 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | 4/21 15:20:00 | 61499.97 | 58936.74 | 5.370425 | 21.68 | 15.70 | 0.00867628 | 12.80 | 12.09 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 0.0000 | 21.11 | 0.00867628 | 55.6234 | 54826.77 | 0.00 | 61584.43 | 61584.43 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19405.057 | 19405.057 | 0.837072 | 0.00016976 | 553.464 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19405.06 | 19405.06 | 0.837072 | 21.11 | 17.35 | 0.01084889 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01084889 | 69.3086 | 3785.88 | 0.00 | 20919.62 | 20919.62 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 77456.420 | -999.000 | 6.443860 | 0.00221520 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | 4/21 16:00:00 | 77456.42 | 71097.25 | 6.443860 | 21.68 | 15.87 | 0.00886250 | 12.80 | 12.09 | 0.00850000 | 34.69 | 0.01715717 | 25.70 | 0.0000 | 21.11 | 0.00886250 | 56.8027 | 65780.55 | 0.00 | 77570.04 | 74115.97 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19410.358 | 19410.358 | 0.837300 | 0.00016981 | 553.630 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19410.36 | 19410.36 | 0.837300 | 21.11 | 17.31 | 0.01080141 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01080141 | 69.0104 | 3897.39 | 0.00 | 20925.33 | 20925.33 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9921.110 | -999.000 | 0.838638 | 0.00028374 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | 4/21 09:50:00 | 9921.11 | 9236.48 | 0.838638 | 21.68 | 15.81 | 0.00880040 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01715153 | 24.95 | 0.0000 | 21.11 | 0.00880040 | 56.4110 | 8560.76 | 0.00 | 9934.63 | 9640.93 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 1431.096 | 1431.096 | 0.061735 | 0.00001252 | 40.814 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.10 | 1431.10 | 0.061735 | 21.11 | 17.49 | 0.01101632 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01101632 | 70.3568 | 645.89 | 0.00 | 1542.81 | 1542.81 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10005.812 | -999.000 | 0.846375 | 0.00028616 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | 4/21 09:50:00 | 10005.81 | 9320.99 | 0.846375 | 21.68 | 15.81 | 0.00879777 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01715153 | 24.95 | 0.0000 | 21.11 | 0.00879777 | 56.3944 | 8639.74 | 0.00 | 10019.48 | 9729.75 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 1430.928 | 1430.928 | 0.061728 | 0.00001252 | 40.809 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.93 | 1430.93 | 0.061728 | 21.11 | 17.48 | 0.01100157 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01100157 | 70.2642 | 651.55 | 0.00 | 1542.63 | 1542.63 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 5750.753 | 5750.753 | 0.806505 | 0.00005031 | 122.149 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5750.75 | 5750.75 | 0.806505 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01002379 | 64.5614 | 1478.52 | 0.00 | 5782.87 | 5782.87 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3020.038 | -999.000 | 0.259215 | 0.00008637 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 3020.04 | 2850.05 | 0.259215 | 21.68 | 15.76 | 0.00874174 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00874174 | 56.0401 | 2646.06 | 0.00 | 3024.43 | 3024.43 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 357.772 | 357.772 | 0.015434 | 0.00000313 | 10.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | 357.77 | 357.77 | 0.015434 | 21.11 | 17.16 | 0.01061650 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01061650 | 67.8458 | 205.87 | 0.00 | 385.70 | 385.70 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3052.389 | -999.000 | 0.262184 | 0.00008730 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 3052.39 | 2882.45 | 0.262184 | 21.68 | 15.76 | 0.00873895 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00873895 | 56.0224 | 2676.37 | 0.00 | 3056.84 | 3056.84 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 357.730 | 357.730 | 0.015432 | 0.00000313 | 10.205 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 357.73 | 357.73 | 0.015432 | 21.11 | 17.16 | 0.01060853 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01060853 | 67.7957 | 206.87 | 0.00 | 385.66 | 385.66 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12601.091 | -999.000 | 1.051690 | 0.00036038 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | 4/21 14:50:00 | 12601.09 | 11599.25 | 1.051690 | 21.68 | 15.86 | 0.00885004 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 0.0000 | 21.11 | 0.00885004 | 56.7249 | 10735.56 | 0.00 | 12619.83 | 12095.21 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 2298.533 | 2298.533 | 0.099154 | 0.00002011 | 65.571 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 2298.53 | 2298.53 | 0.099154 | 21.11 | 17.08 | 0.01051927 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.01051927 | 67.2357 | 1007.45 | 0.00 | 2477.95 | 2477.95 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7134.789 | 7134.789 | 1.158100 | 0.00006242 | 150.086 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 7134.79 | 7134.79 | 1.158100 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00962896 | 62.0559 | 1004.00 | 0.00 | 7174.76 | 7174.76 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7302.834 | 7302.834 | 1.211379 | 0.00006389 | 153.420 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 7302.83 | 7302.83 | 1.211379 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00978557 | 63.0497 | 888.19 | 0.00 | 7343.77 | 7343.77 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6096.046 | 6096.046 | 1.155106 | 0.00005333 | 127.123 | 12/21 00:10:00 | 12/21 00:10:00 | 6096.05 | 6096.05 | 1.155106 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6130.31 | 6130.31 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 3147.469 | 3147.469 | 0.401669 | 0.00002754 | 67.331 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 3147.47 | 3147.47 | 0.401669 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00945071 | 60.9249 | 1021.87 | 0.00 | 3165.01 | 3165.01 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 860093.801 | -999.000 | 22.078076 | 0.02459857 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 860093.80 | 505059.46 | 22.078076 | 29.92 | 22.20 | 0.01364346 | 11.09 | 11.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 52.8192 | 23.99 | 0.00967084 | 51.9615 | 303083.35 | 0.00 | 861064.57 | 506055.69 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 133777.867 | 133777.867 | 6.623423 | 0.00117035 | 2343.432 | unknown | unknown | unknown | 133777.87 | 133777.87 | 6.623423 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 176.0640 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 129577.48 | 129577.48 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 113467.387 | -999.000 | 2.051317 | 0.00324515 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 113467.39 | 59031.63 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 11.94 | 11.74 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 99.9965 | 21.11 | 0.00877956 | 56.2775 | 170658.50 | 0.00 | 113576.05 | 59963.95 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 12429.563 | 12429.563 | 0.615395 | 0.00010874 | 217.733 | unknown | unknown | unknown | 12429.56 | 12429.56 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 333.3216 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 12039.30 | 12039.30 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8174.580 | 8174.580 | 1.548957 | 0.00007151 | 170.467 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 3.0481 | 3.109451 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 8174.58 | 8174.58 | 1.0000 | 1.86431638 | 1.548957 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07150749 | 60.00 | 32.22 | 27.78 | 0.000 | 8174.58 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 8220.52 | 8220.52 | 1.86431638 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1180.254 | 1180.254 | 0.161265 | 0.00001033 | 25.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.4401 | 0.448946 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1180.25 | 1180.25 | 1.0000 | 0.19409757 | 0.161265 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01032433 | 60.00 | 32.22 | 27.78 | 0.000 | 1180.25 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01077023 | 21.00 | 0.01077023 | 69.2833 | 324.66 | 0.00 | 1186.84 | 1186.84 | 0.19409757 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.60 | 15.44 | 0.00800000 | 43049.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 851.794 | 851.794 | 0.144834 | 0.00000745 | 17.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.3176 | 0.324006 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 851.79 | 851.79 | 1.0000 | 0.17432150 | 0.144834 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00745111 | 60.00 | 32.22 | 27.78 | 0.000 | 851.79 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01148960 | 21.00 | 0.01148960 | 73.8307 | 82.51 | 0.00 | 856.57 | 856.57 | 0.17432150 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.42 | 15.01 | 0.00800000 | 41848.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 952.578 | 952.578 | 0.149205 | 0.00000833 | 20.083 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.3552 | 0.362342 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 952.58 | 952.58 | 1.0000 | 0.17958217 | 0.149205 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00833272 | 60.00 | 32.22 | 27.78 | 0.000 | 952.58 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01182895 | 21.00 | 0.01182895 | 75.9705 | 159.59 | 0.00 | 957.91 | 957.91 | 0.17958217 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.83 | 15.16 | 0.00800000 | 42268.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 513.471 | 513.471 | 0.081624 | 0.00000449 | 10.815 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.1915 | 0.195315 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 513.47 | 513.47 | 1.0000 | 0.09824246 | 0.081624 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00449161 | 60.00 | 32.22 | 27.78 | 0.000 | 513.47 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01207742 | 21.00 | 0.01207742 | 77.5360 | 79.47 | 0.00 | 516.35 | 516.35 | 0.09824246 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.75 | 15.13 | 0.00800000 | 42190.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9236.293 | 9236.293 | 1.674795 | 0.00008080 | 193.057 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 3.4440 | 3.513306 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9236.29 | 9236.29 | 1.0000 | 2.01577528 | 1.674795 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.08079488 | 60.00 | 32.22 | 27.78 | 0.000 | 9236.29 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01102759 | 21.00 | 0.01102759 | 70.9100 | 346.42 | 0.00 | 9288.16 | 9288.16 | 2.01577528 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.12 | 14.90 | 0.00800000 | 41542.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4312.016 | 4312.016 | 0.673528 | 0.00003772 | 90.925 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 1.6078 | 1.640207 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4312.02 | 4312.02 | 1.0000 | 0.81065523 | 0.673528 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03771955 | 60.00 | 32.22 | 27.78 | 0.000 | 4312.02 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01072256 | 21.00 | 0.01072256 | 68.9827 | 739.06 | 0.00 | 4336.16 | 4336.16 | 0.81065523 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.85 | 15.17 | 0.00800000 | 42283.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14480.846 | 14480.846 | 2.488996 | 0.00012668 | 303.585 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 5.3996 | 5.508232 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14480.85 | 14480.85 | 1.0000 | 2.99574258 | 2.488996 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.12667184 | 60.00 | 32.22 | 27.78 | 0.000 | 14480.85 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01161195 | 21.00 | 0.01161195 | 74.6025 | 1257.69 | 0.00 | 14562.08 | 14562.08 | 2.99574258 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.37 | 14.99 | 0.00800000 | 41795.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11106.117 | -999.000 | 0.947750 | 0.00031763 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1316 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.947750 | 1.14070717 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.9464 | 0.946428 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 11106.12 | 10427.19 | 1.0000 | 1.14070717 | 0.947750 | 21.68 | 15.78 | 0.00876389 | 44058.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.31759522 | 6.70 | 15.03 | 8.33 | 0.000 | 11106.12 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00876389 | 21.11 | 0.00876389 | 56.1801 | 9674.60 | 0.00 | 11121.87 | 10893.43 | 1.14070717 | 21.68 | 15.79 | 0.00876389 | 44058.4 | 12.33 | 12.09 | 0.00868454 | 34308.4 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1431.096 | 1431.096 | 0.061735 | 0.00001252 | 40.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.947750 | 1.14070717 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.5336 | 0.544361 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.10 | 1431.10 | 1.0000 | 0.07430396 | 0.061735 | 21.11 | 17.49 | 0.01101632 | 49198.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251858 | 60.00 | 32.22 | 27.78 | 0.000 | 1431.10 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01101632 | 21.11 | 0.01101632 | 70.3568 | 645.89 | 0.00 | 1542.81 | 1542.81 | 0.07430396 | 16.60 | 15.91 | 0.01101632 | 44571.4 | 36.85 | 22.39 | 0.01101632 | 65334.9 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11235.203 | -999.000 | 0.959474 | 0.00032132 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1264 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.959474 | 1.15481850 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.9574 | 0.957428 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | unknown | unknown | 4/21 16:20:00 | Sensible | 11235.20 | 10555.32 | 1.0000 | 1.15481850 | 0.959474 | 21.68 | 15.78 | 0.00876105 | 44051.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.32128661 | 6.70 | 15.03 | 8.33 | 0.000 | 11235.20 | 34.46 | 0.01715674 | 25.64 | 0.00000000 | 0.0000 | 21.11 | 0.00876105 | 21.11 | 0.00876105 | 56.1622 | 9794.28 | 0.00 | 11251.19 | 11028.06 | 1.15481850 | 21.68 | 15.78 | 0.00876105 | 44051.2 | 12.33 | 12.09 | 0.00868449 | 34308.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1430.928 | 1430.928 | 0.061728 | 0.00001252 | 40.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.959474 | 1.15481850 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.5336 | 0.544297 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.93 | 1430.93 | 1.0000 | 0.07429526 | 0.061728 | 21.11 | 17.48 | 0.01100157 | 49160.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251711 | 60.00 | 32.22 | 27.78 | 0.000 | 1430.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01100157 | 21.11 | 0.01100157 | 70.2642 | 651.55 | 0.00 | 1542.63 | 1542.63 | 0.07429526 | 16.60 | 15.90 | 0.01100157 | 44534.1 | 36.85 | 22.38 | 0.01100157 | 65297.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 61499.967 | -999.000 | 5.370425 | 0.00175886 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9688 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.370425 | 6.46381700 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 5.2409 | 5.240830 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | unknown | unknown | 4/21 15:20:00 | Sensible | 61499.97 | 58936.74 | 1.0000 | 6.46381700 | 5.370425 | 21.68 | 15.70 | 0.00867628 | 43836.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.75867901 | 6.70 | 15.03 | 8.33 | 0.000 | 61499.97 | 35.03 | 0.01715783 | 25.79 | 0.00000000 | 0.0000 | 21.11 | 0.00867628 | 21.11 | 0.00867628 | 55.6234 | 54826.77 | 0.00 | 61584.43 | 61584.43 | 6.46381700 | 21.68 | 15.71 | 0.00867628 | 43836.7 | 12.35 | 12.09 | 0.00867628 | 34309.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19405.057 | 19405.057 | 0.837072 | 0.00016976 | 553.464 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.370425 | 6.46381700 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 7.2357 | 7.381306 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19405.06 | 19405.06 | 1.0000 | 1.00749507 | 0.837072 | 21.11 | 17.35 | 0.01084889 | 48772.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16974659 | 60.00 | 32.22 | 27.78 | 0.000 | 19405.06 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01084889 | 21.11 | 0.01084889 | 69.3086 | 3785.88 | 0.00 | 20919.62 | 20919.62 | 1.00749507 | 16.60 | 15.77 | 0.01084889 | 44147.5 | 36.86 | 22.27 | 0.01084889 | 64911.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 77456.420 | -999.000 | 6.443860 | 0.00221520 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3150 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.443860 | 7.75579801 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 6.6007 | 6.600588 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | unknown | unknown | 4/21 16:00:00 | Sensible | 77456.42 | 71097.25 | 1.0000 | 7.75579801 | 6.443860 | 21.68 | 15.87 | 0.00886250 | 44309.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.21497647 | 6.70 | 15.03 | 8.33 | 0.000 | 77456.42 | 34.69 | 0.01715717 | 25.70 | 0.00000000 | 0.0000 | 21.11 | 0.00886250 | 21.11 | 0.00886250 | 56.8027 | 65780.55 | 0.00 | 77570.04 | 74115.97 | 7.75579801 | 21.68 | 15.87 | 0.00886250 | 44309.1 | 12.33 | 12.09 | 0.00868605 | 34307.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19410.358 | 19410.358 | 0.837300 | 0.00016981 | 553.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.443860 | 7.75579801 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 7.2377 | 7.383322 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19410.36 | 19410.36 | 1.0000 | 1.00777057 | 0.837300 | 21.11 | 17.31 | 0.01080141 | 48651.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16979295 | 60.00 | 32.22 | 27.78 | 0.000 | 19410.36 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01080141 | 21.11 | 0.01080141 | 69.0104 | 3897.39 | 0.00 | 20925.33 | 20925.33 | 1.00777057 | 16.60 | 15.73 | 0.01080141 | 44027.3 | 36.86 | 22.24 | 0.01080141 | 64791.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9921.110 | -999.000 | 0.838638 | 0.00028374 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1995 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.838638 | 1.00938045 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.8455 | 0.845445 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | unknown | unknown | 4/21 09:50:00 | Sensible | 9921.11 | 9236.48 | 1.0000 | 1.00938045 | 0.838638 | 21.68 | 15.81 | 0.00880040 | 44151.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.28370825 | 6.70 | 15.03 | 8.33 | 0.000 | 9921.11 | 31.73 | 0.01715153 | 24.95 | 0.00000000 | 0.0000 | 21.11 | 0.00880040 | 21.11 | 0.00880040 | 56.4110 | 8560.76 | 0.00 | 9934.63 | 9640.93 | 1.00938045 | 21.68 | 15.82 | 0.00880040 | 44151.1 | 12.33 | 12.09 | 0.00868512 | 34308.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1431.096 | 1431.096 | 0.061735 | 0.00001252 | 40.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.838638 | 1.00938045 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.5336 | 0.544361 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.10 | 1431.10 | 1.0000 | 0.07430396 | 0.061735 | 21.11 | 17.49 | 0.01101632 | 49198.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251858 | 60.00 | 32.22 | 27.78 | 0.000 | 1431.10 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01101632 | 21.11 | 0.01101632 | 70.3568 | 645.89 | 0.00 | 1542.81 | 1542.81 | 0.07430396 | 16.60 | 15.91 | 0.01101632 | 44571.4 | 36.85 | 22.39 | 0.01101632 | 65334.9 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10005.812 | -999.000 | 0.846375 | 0.00028616 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1946 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.846375 | 1.01869228 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.8527 | 0.852663 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | unknown | unknown | 4/21 09:50:00 | Sensible | 10005.81 | 9320.99 | 1.0000 | 1.01869228 | 0.846375 | 21.68 | 15.81 | 0.00879777 | 44144.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.28613043 | 6.70 | 15.03 | 8.33 | 0.000 | 10005.81 | 31.73 | 0.01715153 | 24.95 | 0.00000000 | 0.0000 | 21.11 | 0.00879777 | 21.11 | 0.00879777 | 56.3944 | 8639.74 | 0.00 | 10019.48 | 9729.75 | 1.01869228 | 21.68 | 15.82 | 0.00879777 | 44144.4 | 12.33 | 12.09 | 0.00868508 | 34308.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1430.928 | 1430.928 | 0.061728 | 0.00001252 | 40.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.846375 | 1.01869228 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.5336 | 0.544297 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.93 | 1430.93 | 1.0000 | 0.07429526 | 0.061728 | 21.11 | 17.48 | 0.01100157 | 49160.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01251711 | 60.00 | 32.22 | 27.78 | 0.000 | 1430.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01100157 | 21.11 | 0.01100157 | 70.2642 | 651.55 | 0.00 | 1542.63 | 1542.63 | 0.07429526 | 16.60 | 15.90 | 0.01100157 | 44534.1 | 36.85 | 22.38 | 0.01100157 | 65297.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5750.753 | 5750.753 | 0.806505 | 0.00005031 | 122.149 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 2.1443 | 2.187474 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5750.75 | 5750.75 | 1.0000 | 0.97070484 | 0.806505 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05030496 | 60.00 | 32.22 | 27.78 | 0.000 | 5750.75 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01002379 | 21.00 | 0.01002379 | 64.5614 | 1478.52 | 0.00 | 5782.87 | 5782.87 | 0.97070484 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.44 | 15.39 | 0.00800000 | 42892.1 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3020.038 | -999.000 | 0.259215 | 0.00008637 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0904 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.259215 | 0.31198990 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.2574 | 0.257358 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 3020.04 | 2850.05 | 1.0000 | 0.31198990 | 0.259215 | 21.68 | 15.76 | 0.00874174 | 44002.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08636229 | 6.70 | 15.03 | 8.33 | 0.000 | 3020.04 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00874174 | 21.11 | 0.00874174 | 56.0401 | 2646.06 | 0.00 | 3024.43 | 3024.43 | 0.31198990 | 21.68 | 15.77 | 0.00874174 | 44002.1 | 12.19 | 12.09 | 0.00874174 | 34308.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 357.772 | 357.772 | 0.015434 | 0.00000313 | 10.206 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.259215 | 0.31198990 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.1334 | 0.136090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 17:10:00 | Sensible | 357.77 | 357.77 | 1.0000 | 0.01857599 | 0.015434 | 21.11 | 17.16 | 0.01061650 | 48182.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00312963 | 60.00 | 32.22 | 27.78 | 0.000 | 357.77 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01061650 | 21.11 | 0.01061650 | 67.8458 | 205.87 | 0.00 | 385.70 | 385.70 | 0.01857599 | 16.60 | 15.56 | 0.01061650 | 43559.2 | 36.87 | 22.12 | 0.01061650 | 64322.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3052.389 | -999.000 | 0.262184 | 0.00008730 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0853 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.262184 | 0.31556275 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 0.2601 | 0.260115 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 3052.39 | 2882.45 | 1.0000 | 0.31556275 | 0.262184 | 21.68 | 15.76 | 0.00873895 | 43995.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08728740 | 6.70 | 15.03 | 8.33 | 0.000 | 3052.39 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00873895 | 21.11 | 0.00873895 | 56.0224 | 2676.37 | 0.00 | 3056.84 | 3056.84 | 0.31556275 | 21.68 | 15.76 | 0.00873895 | 43995.0 | 12.20 | 12.09 | 0.00873895 | 34308.1 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 357.730 | 357.730 | 0.015432 | 0.00000313 | 10.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.262184 | 0.31556275 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.1334 | 0.136074 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 357.73 | 357.73 | 1.0000 | 0.01857381 | 0.015432 | 21.11 | 17.16 | 0.01060853 | 48162.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00312926 | 60.00 | 32.22 | 27.78 | 0.000 | 357.73 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01060853 | 21.11 | 0.01060853 | 67.7957 | 206.87 | 0.00 | 385.66 | 385.66 | 0.01857381 | 16.60 | 15.56 | 0.01060853 | 43539.0 | 36.87 | 22.11 | 0.01060853 | 64302.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12601.091 | -999.000 | 1.051690 | 0.00036038 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2918 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.051690 | 1.26580907 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 1.0738 | 1.073825 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | unknown | unknown | 4/21 14:50:00 | Sensible | 12601.09 | 11599.25 | 1.0000 | 1.26580907 | 1.051690 | 21.68 | 15.86 | 0.00885004 | 44277.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.36034611 | 6.70 | 15.03 | 8.33 | 0.000 | 12601.09 | 35.20 | 0.01715815 | 25.83 | 0.00000000 | 0.0000 | 21.11 | 0.00885004 | 21.11 | 0.00885004 | 56.7249 | 10735.56 | 0.00 | 12619.83 | 12095.21 | 1.26580907 | 21.68 | 15.86 | 0.00885004 | 44277.2 | 12.33 | 12.09 | 0.00868583 | 34307.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2298.533 | 2298.533 | 0.099154 | 0.00002011 | 65.571 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.051690 | 1.26580907 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 0.8571 | 0.874317 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | Sensible | 2298.53 | 2298.53 | 1.0000 | 0.11934125 | 0.099154 | 21.11 | 17.08 | 0.01051927 | 47935.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02010652 | 60.00 | 32.22 | 27.78 | 0.000 | 2298.53 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.01051927 | 21.11 | 0.01051927 | 67.2357 | 1007.45 | 0.00 | 2477.95 | 2477.95 | 0.11934125 | 16.60 | 15.48 | 0.01051927 | 43313.0 | 36.87 | 22.05 | 0.01051927 | 64076.6 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7134.789 | 7134.789 | 1.158100 | 0.00006242 | 150.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 2.6604 | 2.713935 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 7134.79 | 7134.79 | 1.0000 | 1.39388373 | 1.158100 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06241188 | 60.00 | 32.22 | 27.78 | 0.000 | 7134.79 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00962896 | 21.00 | 0.00962896 | 62.0559 | 1004.00 | 0.00 | 7174.76 | 7174.76 | 1.39388373 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.65 | 15.09 | 0.00800000 | 42082.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7302.834 | 7302.834 | 1.211379 | 0.00006389 | 153.420 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 2.7231 | 2.777856 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | Sensible | 7302.83 | 7302.83 | 1.0000 | 1.45800944 | 1.211379 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06388186 | 60.00 | 32.22 | 27.78 | 0.000 | 7302.83 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00978557 | 21.00 | 0.00978557 | 63.0497 | 888.19 | 0.00 | 7343.77 | 7343.77 | 1.45800944 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.54 | 15.05 | 0.00800000 | 41971.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6096.046 | 6096.046 | 1.155106 | 0.00005333 | 127.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 2.2731 | 2.318817 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6096.05 | 6096.05 | 1.0000 | 1.39028038 | 1.155106 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05332543 | 60.00 | 32.22 | 27.78 | 0.000 | 6096.05 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6130.31 | 6130.31 | 1.39028038 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3147.469 | 3147.469 | 0.401669 | 0.00002754 | 67.331 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 1.1736 | 1.197236 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | Sensible | 3147.47 | 3147.47 | 1.0000 | 0.48344662 | 0.401669 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02753263 | 60.00 | 32.22 | 27.78 | 0.000 | 3147.47 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00945071 | 21.00 | 0.00945071 | 60.9249 | 1021.87 | 0.00 | 3165.01 | 3165.01 | 0.48344662 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.02 | 15.60 | 0.00800000 | 43481.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 860093.801 | -999.000 | 22.078076 | 0.02459857 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1030.2025 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.078076 | 26.57306140 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 73.2958 | 73.295811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 860093.80 | 505059.46 | 1.0000 | 26.57306140 | 22.078076 | 29.92 | 22.20 | 0.01364346 | 64944.1 | 11.09 | 11.09 | 0.00850000 | 32577.0 | 24.59606452 | 6.70 | 15.03 | 8.33 | 46809.366 | 813284.43 | 35.20 | 0.01715815 | 25.83 | 11.66146000 | 52.8192 | 23.99 | 0.00969669 | 23.99 | 0.00967084 | 51.9615 | 303083.35 | 0.00 | 861064.57 | 506055.69 | 26.57306140 | 29.92 | 22.21 | 0.01364346 | 64944.1 | 11.43 | 11.37 | 0.00834659 | 32540.5 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 133777.867 | 133777.867 | 6.623423 | 0.00117035 | 2343.432 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.078076 | 26.57306140 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 49.8826 | 50.886492 | unknown | unknown | unknown | unknown | unknown | Sensible | 133777.87 | 133777.87 | 1.0000 | 7.97191842 | 6.623423 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 1.17022775 | 60.00 | 32.22 | 27.78 | 0.000 | 133777.87 | 0.00 | 0.00000000 | -6.26 | 11.66146000 | 176.0640 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 129577.48 | 129577.48 | 7.97191842 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 18.98 | 5.31 | 0.00000000 | 19092.9 | ||
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113467.387 | -999.000 | 2.051317 | 0.00324515 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7361 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 33.55725818 | 15.03 | 6.70 | 8.33 | 1173455.60 | 9.6695 | 9.669508 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 113467.39 | 59031.63 | 1.0000 | 2.46895513 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 79404.6 | 11.94 | 11.74 | 0.00850000 | 33447.0 | 3.24482186 | 6.70 | 15.03 | 8.33 | 2195.006 | 111272.38 | 35.20 | 0.01715815 | 25.83 | 2.05124512 | 99.9965 | 21.11 | 0.00878656 | 21.11 | 0.00877956 | 56.2775 | 170658.50 | 0.00 | 113576.05 | 59963.95 | 2.46895513 | 35.20 | 25.84 | 0.01715815 | 79404.6 | 11.77 | 11.72 | 0.00855094 | 33402.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12429.563 | 12429.563 | 0.615395 | 0.00010874 | 217.733 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 2.29968248 | 54.44 | 82.22 | 27.78 | 268185.51 | 4.6347 | 4.727964 | unknown | unknown | unknown | unknown | unknown | Sensible | 12429.56 | 12429.56 | 1.0000 | 0.74068654 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.10872815 | 60.00 | 32.22 | 27.78 | 0.000 | 12429.56 | 0.00 | 0.00000000 | -6.26 | 2.05124512 | 333.3216 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 12039.30 | 12039.30 | 0.74068654 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 18.98 | 5.31 | 0.00000000 | 19092.9 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 30.50 | 5883.83 | 0.00 |
RETAIL_1_FLR_1 | 5807.67 | 1522.50 | 0.00 |
RETAIL_2_FLR_1 | 2550.17 | 3721.67 | 0.00 |
MECH_FLR_1 | 1698.33 | 4342.83 | 0.00 |
STORAGE_FLR_1 | 1139.50 | 5227.00 | 0.00 |
LAUNDRY_FLR_1 | 8222.83 | 1921.33 | 1914.33 |
CAFE_FLR_1 | 7527.17 | 1076.17 | 642.33 |
LOBBY_FLR_1 | 5070.50 | 1259.50 | 0.00 |
ROOM_1_FLR_3 | 9.17 | 7312.67 | 7.50 |
ROOM_2_FLR_3 | 121.83 | 7343.67 | 102.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56.67 | 8757.50 | 56.67 |
ROOM_5_FLR_3 | 6.83 | 7057.33 | 6.83 |
ROOM_6_FLR_3 | 154.83 | 7056.00 | 101.83 |
CORRIDOR_FLR_3 | 64.67 | 8074.33 | 0.00 |
ROOM_1_FLR_6 | 569.17 | 6937.00 | 14.50 |
ROOM_2_FLR_6 | 607.83 | 6967.17 | 167.33 |
ROOM_3_MULT9_FLR_6 | 179.67 | 7275.33 | 6.17 |
BANQUET_FLR_6 | 8507.00 | 24.33 | 3.83 |
DINING_FLR_6 | 8707.67 | 3.67 | 0.00 |
KITCHEN_FLR_6 | 8745.83 | 6596.50 | 6596.50 |
CORRIDOR_FLR_6 | 2788.00 | 3226.50 | 0.00 |
Facility | 8760.00 | 8760.00 | 7220.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 2.33 | 0.00 | 2.33 |
ROOM_2_FLR_3 | 0.00 | 3.33 | 0.00 | 3.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 7.83 | 0.00 | 7.83 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 8.83 | 0.00 | 8.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 18.00 | 0.00 | 18.00 |
ROOM_2_FLR_6 | 0.00 | 15.17 | 0.00 | 15.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 34.50 | 0.00 | 34.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 50.50 | 0.00 | 50.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.134 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.284 | 0.129 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.674 | 0.043 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.826 | 0.048 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.776 | 0.048 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.134 | 0.137 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.314 | 0.102 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.723 | 0.042 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.166 | 0.000 | 0.007 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.166 | 0.000 | 0.007 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.406 | 0.074 | 0.000 | 0.011 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.166 | 0.000 | 0.007 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.166 | 0.000 | 0.007 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.600 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.358 | 0.166 | 0.000 | 0.008 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.358 | 0.166 | 0.000 | 0.008 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.406 | 0.135 | 0.000 | 0.013 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.475 | 0.048 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.717 | 0.048 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.213 | 0.138 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.142 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.758 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.672 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.163 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.541 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.513 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 13.754 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.864 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.275 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.402 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.826 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.981 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 10.189 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.789 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 46591636.97 | 0.00 | 46591636.97 | 0.00 | 46591636.97 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5162883.40 | 0.00 | 5162883.40 | 291644.21 | 5454527.61 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4386774.97 | 0.00 | 4386774.97 | 112575.04 | 4499350.00 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 4574257.45 | 0.00 | 4574257.45 | 266060.50 | 4840317.95 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2479487.30 | 0.00 | 2479487.30 | 153502.25 | 2632989.56 | 1821682.01 | 83.89 | 63.78 | 8612.33 | 0.00 |
LAUNDRY_FLR_1 | 53237426.42 | 0.00 | 53237426.42 | 363292.03 | 53600718.45 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 21049738.69 | 0.00 | 21049738.69 | 644696.04 | 21694434.73 | 21330615.53 | 2382.02 | 5898.87 | 479.11 | 0.00 |
LOBBY_FLR_1 | 75898567.19 | 0.00 | 75898567.19 | 1842043.85 | 77740611.03 | 59728886.00 | 6.78 | 17.57 | 8735.65 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 7580.70 | 1467737.41 | 169277.80 | 1637015.21 | 1946875.62 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 6991.18 | 1466976.81 | 169264.88 | 1636241.69 | 1946647.51 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 47230.40 | 1147142.37 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 6947.18 | 19810776.47 | 47243.32 | 19858019.79 | 26405105.73 | 2190.00 | 6470.94 | 99.06 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 7580.62 | 1467737.34 | 169277.80 | 1637015.13 | 1946875.62 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 7184.16 | 1467169.79 | 169264.88 | 1636434.68 | 1946647.51 | 2190.00 | 6378.39 | 191.61 | 0.00 |
CORRIDOR_FLR_3 | 24263371.48 | 0.00 | 24263371.48 | 204690.91 | 24468062.39 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 8487.60 | 373526.77 | 169311.27 | 542838.04 | 486718.90 | 2187.89 | 6374.07 | 198.04 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 8291.77 | 373288.17 | 169298.35 | 542586.53 | 486661.88 | 2186.00 | 6374.17 | 199.83 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 8486.24 | 2353676.55 | 86625.57 | 2440302.12 | 3126920.42 | 2190.00 | 6374.00 | 196.00 | 0.00 |
BANQUET_FLR_6 | 38374021.45 | 0.00 | 38374021.45 | 413415.57 | 38787437.02 | 37458366.31 | 4430.38 | 534.61 | 3795.00 | 0.00 |
DINING_FLR_6 | 40450168.56 | 0.00 | 40450168.56 | 413415.57 | 40863584.13 | 37458366.31 | 159.28 | 136.51 | 8464.22 | 0.00 |
KITCHEN_FLR_6 | 48672987.14 | 0.00 | 48672987.14 | 370102.78 | 49043089.93 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12207731.71 | 0.00 | 12207731.71 | 362235.95 | 12569967.66 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 738487.60 | 0.21E+10 | 17058331.55 | 0.21E+10 | 0.43E+10 | 8760.00 | 8548.14 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4774 | 0.0000 | 1.4774 | 0.0000 | 1.4774 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1637 | 0.0000 | 0.1637 | 0.0092 | 0.1730 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1391 | 0.0000 | 0.1391 | 0.0036 | 0.1427 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1450 | 0.0000 | 0.1450 | 0.0084 | 0.1535 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0786 | 0.0000 | 0.0786 | 0.0049 | 0.0835 | 0.0578 | 83.89 | 63.78 | 8612.33 |
LAUNDRY_FLR_1 | 1.6881 | 0.0000 | 1.6881 | 0.0115 | 1.6997 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6675 | 0.0000 | 0.6675 | 0.0204 | 0.6879 | 0.6764 | 2382.02 | 5898.87 | 479.11 |
LOBBY_FLR_1 | 2.4067 | 0.0000 | 2.4067 | 0.0584 | 2.4651 | 1.8940 | 6.78 | 17.57 | 8735.65 |
ROOM_1_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0054 | 0.0519 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0054 | 0.0519 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0002 | 0.6282 | 0.0015 | 0.6297 | 0.8373 | 2190.00 | 6470.94 | 99.06 |
ROOM_5_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0054 | 0.0519 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0054 | 0.0519 | 0.0617 | 2190.00 | 6378.39 | 191.61 |
CORRIDOR_FLR_3 | 0.7694 | 0.0000 | 0.7694 | 0.0065 | 0.7759 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0003 | 0.0118 | 0.0054 | 0.0172 | 0.0154 | 2187.89 | 6374.07 | 198.04 |
ROOM_2_FLR_6 | 0.0116 | 0.0003 | 0.0118 | 0.0054 | 0.0172 | 0.0154 | 2186.00 | 6374.17 | 199.83 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0003 | 0.0746 | 0.0027 | 0.0774 | 0.0992 | 2190.00 | 6374.00 | 196.00 |
BANQUET_FLR_6 | 1.2168 | 0.0000 | 1.2168 | 0.0131 | 1.2299 | 1.1878 | 4430.38 | 534.61 | 3795.00 |
DINING_FLR_6 | 1.2827 | 0.0000 | 1.2827 | 0.0131 | 1.2958 | 1.1878 | 159.28 | 136.51 | 8464.22 |
KITCHEN_FLR_6 | 1.5434 | 0.0000 | 1.5434 | 0.0117 | 1.5551 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3871 | 0.0000 | 0.3871 | 0.0115 | 0.3986 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.4332 | 0.0234 | 63.4566 | 0.4271 | 63.8837 | 73.9670 | 8760.00 | 8548.14 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 43197387.25 | 61549.44 | 43258936.68 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.3339 | 0.0000 | 17.3339 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3698 | 0.0020 | 1.3717 | 2.0513 | 8759.83 | 0.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 17.3339 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7302 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 3997 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
Electricity:Building | 2447.99 | 31358.38 | 25-NOV-06:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.90 | 31217.23 | 25-NOV-06:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.69 | 318.54 | 25-NOV-06:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.35 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.35 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.18 | 3142.86 | 25-NOV-06:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1031.45 | 25-NOV-06:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1031.45 | 25-NOV-06:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.74 | 2559.17 | 25-NOV-06:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.74 | 2559.17 | 25-NOV-06:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.45 | 1174.22 | 15-JUN-22:30 | 3257.38 | 17-NOV-07:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 5122.86 | 88285.90 | 23-JAN-06:20 | 272575.19 | 13-JUN-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.40 | 0.00 | 01-JAN-11:10 | 1892.37 | 07-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.96 | 1006.76 | 23-OCT-03:10 | 1192.37 | 17-MAY-13:10 |
Fans:Electricity | 499.49 | 11247.59 | 23-OCT-07:10 | 29183.16 | 12-JUN-18:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 823.93 | 20352.07 | 17-MAY-10:10 | 40172.84 | 12-JUN-18:30 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 13-MAR-06:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
ElectricityPurchased:Plant | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
Cogeneration:ElectricityPurchased | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
ElectricityNet:Plant | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
Cogeneration:ElectricityNet | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
General:Cogeneration:ElectricityNet | 9207.98 | 164372.82 | 21-DEC-05:00 | 472906.68 | 12-JUN-19:10 |
General:Fans:Electricity | 499.49 | 11247.59 | 23-OCT-07:10 | 29183.16 | 12-JUN-18:30 |
ExteriorLights:Electricity | 194.17 | 0.00 | 01-JAN-06:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.17 | 0.00 | 01-JAN-06:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 302.68 | 8417.13 | 01-JAN-08:40 | 9938.94 | 07-JAN-09:20 |
General:HeatRecovery:Electricity | 302.68 | 8417.13 | 01-JAN-08:40 | 9938.94 | 07-JAN-09:20 |
WaterSystems:Electricity | 90.75 | 1086.73 | 31-MAY-00:30 | 4738.75 | 23-AUG-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.73 | 31-MAY-00:30 | 4738.75 | 23-AUG-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 4830.95 | 78288.66 | 23-JAN-06:20 | 263115.23 | 13-JUN-15:20 |
General:Cooling:Electricity | 4830.95 | 78288.66 | 23-JAN-06:20 | 263115.23 | 13-JUN-15:20 |
Pumps:Electricity | 145.80 | 4001.44 | 23-JAN-06:20 | 5789.67 | 31-MAY-20:20 |
General:Pumps:Electricity | 145.80 | 4001.44 | 23-JAN-06:20 | 5789.67 | 31-MAY-20:20 |
WIRED_LTG_ELECTRICITY | 27.55 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4211.56 | 30961.74 | 13-JUN-01:10 | 313080.40 | 04-JAN-18:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2422.72 | 15908.90 | 03-JAN-11:10 | 213237.55 | 01-JAN-19:10 |
WaterSystems:NaturalGas | 2397.33 | 15908.90 | 01-JAN-09:10 | 209146.51 | 09-JAN-21:40 |
Water Heater:WaterSystems:NaturalGas | 2397.33 | 15908.90 | 01-JAN-09:10 | 209146.51 | 09-JAN-21:40 |
Heating:NaturalGas | 25.38 | 0.00 | 01-JAN-00:10 | 10022.41 | 23-OCT-01:20 |
Boiler:Heating:NaturalGas | 25.38 | 0.00 | 01-JAN-00:10 | 10022.41 | 23-OCT-01:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 15957.85 | 232098.67 | 23-JAN-06:20 | 779565.55 | 13-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 15957.85 | 232098.67 | 23-JAN-06:20 | 779565.55 | 13-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 15957.85 | 232098.67 | 23-JAN-06:20 | 779565.55 | 13-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 67819.69 | 985761.80 | 23-JAN-06:20 | 3295389.18 | 13-JUN-18:10 |
EnergyTransfer:Building | 7418.23 | 150265.04 | 20-AUG-13:10 | 364846.87 | 12-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 781.55 | 14284.97 | 23-OCT-03:00 | 35715.51 | 07-MAY-10:50 |
Refrigeration:EnergyTransfer | 186.94 | 4364.27 | 15-JUN-22:20 | 10336.67 | 08-DEC-08:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.47 | 2182.13 | 15-JUN-22:20 | 5168.33 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer | 93.47 | 2182.13 | 15-JUN-22:20 | 5168.33 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.47 | 2182.13 | 15-JUN-22:20 | 5168.33 | 08-DEC-08:20 |
EnergyTransfer:Plant | 37559.07 | 570005.90 | 23-JAN-06:20 | 1831544.67 | 13-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.71 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.76 | 1970.27 | 23-OCT-03:10 | 2527.12 | 17-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 626.09 | 17999.15 | 01-JAN-16:00 | 22310.94 | 15-JUN-21:00 |
Heating:EnergyTransfer | 0.09 | 0.00 | 01-JAN-00:10 | 2216.22 | 24-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.09 | 0.00 | 01-JAN-00:10 | 2216.22 | 24-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 7324.67 | 147303.86 | 20-AUG-13:10 | 361230.45 | 12-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 626.09 | 17999.15 | 01-JAN-16:00 | 22310.94 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer | 7324.67 | 147303.86 | 20-AUG-13:10 | 361230.45 | 12-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 626.09 | 17999.15 | 01-JAN-16:00 | 22310.94 | 15-JUN-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 71.22 | 1660.42 | 20-AUG-17:00 | 3836.53 | 05-JAN-15:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 71.22 | 1660.42 | 20-AUG-17:00 | 3836.53 | 05-JAN-15:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 71.22 | 1660.42 | 20-AUG-17:00 | 3836.53 | 05-JAN-15:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.63 | 1510.23 | 20-AUG-15:00 | 2754.02 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.63 | 1510.23 | 20-AUG-15:00 | 2754.02 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.63 | 1510.23 | 20-AUG-15:00 | 2754.02 | 13-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 62.11 | 1670.28 | 21-AUG-04:00 | 3765.89 | 13-JUN-19:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 62.11 | 1670.28 | 21-AUG-04:00 | 3765.89 | 13-JUN-19:30 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 62.11 | 1670.28 | 21-AUG-04:00 | 3765.89 | 13-JUN-19:30 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 33.38 | 914.60 | 20-AUG-16:00 | 1814.70 | 13-JUN-19:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 33.38 | 914.60 | 20-AUG-16:00 | 1814.70 | 13-JUN-19:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 33.38 | 914.60 | 20-AUG-16:00 | 1814.70 | 13-JUN-19:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 636.89 | 11076.93 | 23-OCT-04:00 | 36984.73 | 05-MAY-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 636.89 | 11076.93 | 23-OCT-04:00 | 36984.73 | 05-MAY-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 636.89 | 11076.93 | 23-OCT-04:00 | 36984.73 | 05-MAY-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 294.50 | 6540.28 | 20-AUG-15:00 | 12983.29 | 08-DEC-22:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 294.50 | 6540.28 | 20-AUG-15:00 | 12983.29 | 08-DEC-22:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 294.50 | 6540.28 | 20-AUG-15:00 | 12983.29 | 08-DEC-22:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 1042.75 | 26696.74 | 20-AUG-15:00 | 47857.02 | 13-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1042.75 | 26696.74 | 20-AUG-15:00 | 47857.02 | 13-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1042.75 | 26696.74 | 20-AUG-15:00 | 47857.02 | 13-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 120.74 | 0.00 | 01-JAN-08:10 | 10166.85 | 06-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 307.89 | 14-JUL-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 307.89 | 14-JUL-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 120.73 | 0.00 | 01-JAN-08:10 | 10166.85 | 06-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 120.73 | 0.00 | 01-JAN-08:10 | 10166.85 | 06-MAY-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 115.73 | 0.00 | 01-JAN-08:10 | 10410.21 | 06-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 311.29 | 28-NOV-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.01 | 0.00 | 01-JAN-00:10 | 311.29 | 28-NOV-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 115.72 | 0.00 | 01-JAN-08:10 | 10410.21 | 06-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 115.72 | 0.00 | 01-JAN-08:10 | 10410.21 | 06-MAY-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 586.21 | 4627.66 | 20-AUG-05:00 | 38811.90 | 07-DEC-13:50 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 586.21 | 4627.66 | 20-AUG-05:00 | 38811.90 | 07-DEC-13:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 586.21 | 4627.66 | 20-AUG-05:00 | 38811.90 | 07-DEC-13:50 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 902.01 | 0.00 | 01-JAN-08:10 | 76502.29 | 13-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 2216.22 | 24-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 2216.22 | 24-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 901.96 | 0.00 | 01-JAN-08:10 | 76502.29 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 901.96 | 0.00 | 01-JAN-08:10 | 76502.29 | 13-JUN-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 121.04 | 0.00 | 01-JAN-08:10 | 8758.94 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 200.14 | 23-OCT-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 200.14 | 23-OCT-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 121.04 | 0.00 | 01-JAN-08:10 | 8758.94 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 121.04 | 0.00 | 01-JAN-08:10 | 8758.94 | 06-MAY-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 115.75 | 0.00 | 01-JAN-08:10 | 9046.59 | 13-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 176.51 | 22-OCT-19:50 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 176.51 | 22-OCT-19:50 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 115.75 | 0.00 | 01-JAN-08:10 | 9046.59 | 13-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 115.75 | 0.00 | 01-JAN-08:10 | 9046.59 | 13-JUN-15:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 323.08 | 9182.15 | 21-AUG-10:40 | 12768.43 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 323.08 | 9182.15 | 21-AUG-10:40 | 12768.43 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 323.08 | 9182.15 | 21-AUG-10:40 | 12768.43 | 13-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 31.04 | 0.00 | 01-JAN-08:10 | 3020.17 | 22-FEB-16:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 79.99 | 20-JUN-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 79.99 | 20-JUN-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 31.04 | 0.00 | 01-JAN-08:10 | 3020.17 | 22-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 31.04 | 0.00 | 01-JAN-08:10 | 3020.17 | 22-FEB-16:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.82 | 0.00 | 01-JAN-08:10 | 3044.88 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 80.14 | 05-AUG-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 80.14 | 05-AUG-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.82 | 0.00 | 01-JAN-08:10 | 3044.88 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.82 | 0.00 | 01-JAN-08:10 | 3044.88 | 06-MAY-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 166.75 | 0.00 | 01-JAN-08:10 | 13308.37 | 07-DEC-16:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 220.23 | 17-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 220.23 | 17-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 166.75 | 0.00 | 01-JAN-08:10 | 13308.37 | 07-DEC-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 166.75 | 0.00 | 01-JAN-08:10 | 13308.37 | 07-DEC-16:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 549.96 | 13228.35 | 20-AUG-15:00 | 25466.60 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 549.96 | 13228.35 | 20-AUG-15:00 | 25466.60 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 549.96 | 13228.35 | 20-AUG-15:00 | 25466.60 | 12-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 582.06 | 14190.84 | 03-MAR-14:50 | 26699.10 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 582.06 | 14190.84 | 03-MAR-14:50 | 26699.10 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 582.06 | 14190.84 | 03-MAR-14:50 | 26699.10 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 688.08 | 12064.86 | 23-OCT-03:00 | 30646.26 | 07-MAY-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 688.08 | 12064.86 | 23-OCT-03:00 | 30646.26 | 07-MAY-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 166.88 | 4376.23 | 21-AUG-06:30 | 7505.27 | 13-JUN-15:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 166.88 | 4376.23 | 21-AUG-06:30 | 7505.27 | 13-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 166.88 | 4376.23 | 21-AUG-06:30 | 7505.27 | 13-JUN-15:40 |
PlantLoopHeatingDemand:Facility | 498.34 | 6146.60 | 24-JUN-00:20 | 34859.38 | 15-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 482.33 | 6128.97 | 15-JUL-01:10 | 33488.30 | 09-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 482.33 | 6128.97 | 15-JUL-01:10 | 33488.30 | 09-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 482.33 | 6128.97 | 15-JUL-01:10 | 33488.30 | 09-JAN-07:10 |
EnergyTransfer:HVAC | 22842.38 | 232098.67 | 23-JAN-06:20 | 1187807.43 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 16.01 | 0.00 | 01-JAN-00:10 | 5813.63 | 23-OCT-04:00 |
PlantLoopHeatingDemand:HVAC | 16.01 | 0.00 | 01-JAN-00:10 | 5813.63 | 23-OCT-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 16.01 | 0.00 | 01-JAN-00:10 | 5813.63 | 23-OCT-04:00 |
CoolingCoils:EnergyTransfer | 15957.85 | 232098.67 | 23-JAN-06:20 | 779565.55 | 13-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 0.02 | 0.00 | 01-JAN-00:10 | 20309.59 | 10-FEB-01:00 |
HeatRecoveryForCooling:EnergyTransfer | 6868.51 | 0.00 | 08-JAN-06:50 | 450299.34 | 15-JUN-10:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 482.33 | 6128.97 | 15-JUL-01:10 | 33488.30 | 09-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 482.33 | 6128.97 | 15-JUL-01:10 | 33488.30 | 09-JAN-07:10 |
Boilers:EnergyTransfer | 15.88 | 0.00 | 01-JAN-00:10 | 6031.08 | 20-AUG-15:10 |
Chillers:EnergyTransfer | 16068.22 | 231377.68 | 23-JAN-06:20 | 783450.65 | 13-JUN-18:10 |
HeatRejection:EnergyTransfer | 20899.17 | 309666.34 | 23-JAN-06:20 | 1025556.52 | 13-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 20899.17 | 309666.34 | 23-JAN-06:20 | 1025556.52 | 13-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -626.096 | 0.000 | 0.000 | 140.061 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 181.635 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -71.219 | 0.000 | 0.000 | 14.160 | 7.307 | 10.186 | 17.907 | 0.000 | 1.529 | 20.850 | 0.000 | -0.704 | 0.000 | -0.015 | 0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -58.631 | 0.000 | 0.000 | 16.499 | 8.462 | 11.795 | 0.000 | 0.000 | 0.631 | 21.252 | 0.000 | 0.000 | 0.000 | -0.007 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -62.111 | 0.000 | 0.000 | 3.478 | 8.366 | 12.471 | 0.000 | 0.000 | 1.437 | 36.373 | 0.000 | 0.000 | 0.000 | -0.014 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -33.384 | 0.000 | 0.000 | 2.689 | 3.079 | 3.598 | 0.000 | 0.000 | 0.842 | 23.183 | 0.000 | 0.000 | 0.000 | -0.008 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -636.890 | 0.000 | 0.000 | 11.761 | 3.975 | 658.131 | 0.000 | 0.000 | 2.474 | 0.001 | 0.000 | 0.000 | 0.000 | -0.009 | -39.443 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -294.505 | 0.000 | 0.000 | 182.224 | 14.351 | 14.341 | 50.733 | 0.000 | 3.315 | 31.742 | 0.000 | -2.130 | 0.000 | -0.071 | 0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -1042.758 | 0.000 | 0.000 | 545.269 | 110.179 | 148.998 | 68.560 | 0.000 | 9.793 | 162.542 | 0.000 | -2.403 | 0.000 | -0.179 | 0.000 |
ROOM_1_FLR_3 | 0.022 | -105.594 | 0.000 | -15.140 | 0.000 | 0.000 | 9.619 | 9.244 | 10.478 | 50.856 | 0.000 | 4.963 | 35.913 | 0.000 | -0.348 | 0.000 | -0.013 | 0.000 |
ROOM_2_FLR_3 | 0.025 | -100.445 | 0.000 | -15.276 | 0.000 | 0.000 | 9.588 | 9.243 | 10.477 | 47.786 | 0.000 | 4.874 | 34.139 | 0.000 | -0.370 | 0.000 | -0.041 | 0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -567.649 | 0.000 | -18.559 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 188.473 | 0.000 | 7.560 | 116.421 | 0.000 | -27.876 | 0.000 | -3.752 | 0.000 |
ROOM_4_MULT19_FLR_3 | 0.248 | -695.418 | 0.000 | -206.680 | 0.000 | 0.000 | 182.445 | 110.415 | 195.050 | 213.341 | 0.000 | 26.316 | 175.974 | 0.000 | -1.315 | 0.000 | -0.376 | -0.002 |
ROOM_5_FLR_3 | 0.001 | -105.893 | 0.000 | -15.144 | 0.000 | 0.000 | 9.618 | 9.244 | 10.478 | 51.015 | 0.000 | 4.958 | 36.073 | 0.000 | -0.336 | 0.000 | -0.014 | 0.000 |
ROOM_6_FLR_3 | 0.002 | -100.442 | 0.000 | -15.302 | 0.000 | 0.000 | 9.582 | 9.243 | 10.477 | 47.888 | 0.000 | 4.861 | 34.093 | 0.000 | -0.348 | 0.000 | -0.056 | 0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -323.082 | 0.000 | 0.000 | 111.190 | 91.336 | 0.000 | 49.181 | 0.000 | 4.565 | 67.809 | 0.000 | -0.946 | 0.000 | -0.054 | 0.000 |
ROOM_1_FLR_6 | 0.010 | -27.254 | 0.000 | -3.786 | 0.000 | 0.000 | 2.405 | 2.311 | 2.620 | 12.641 | 0.000 | 1.230 | 9.897 | 0.000 | -0.069 | 0.000 | -0.004 | 0.000 |
ROOM_2_FLR_6 | 0.010 | -26.003 | 0.000 | -3.817 | 0.000 | 0.000 | 2.398 | 2.311 | 2.619 | 11.877 | 0.000 | 1.209 | 9.483 | 0.000 | -0.076 | 0.000 | -0.010 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.014 | -142.412 | 0.000 | -24.342 | 0.000 | 0.000 | 21.641 | 13.076 | 23.098 | 54.616 | 0.000 | 5.733 | 48.889 | 0.000 | -0.288 | 0.000 | -0.024 | 0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -549.967 | 0.000 | 0.000 | 316.258 | 30.881 | 175.857 | 20.205 | 0.000 | 1.969 | 5.901 | 0.000 | -1.044 | 0.000 | -0.060 | -0.001 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -582.068 | 0.000 | 0.000 | 315.746 | 30.881 | 175.857 | 19.789 | 0.000 | 1.944 | 39.086 | 0.000 | -1.174 | 0.000 | -0.061 | 0.000 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -688.065 | 0.000 | 0.000 | 28.906 | 12.972 | 550.372 | 25.431 | 0.000 | 1.800 | 69.449 | 0.000 | -0.836 | 0.000 | -0.030 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -166.879 | 0.000 | 0.000 | 29.013 | 24.166 | 0.000 | 20.926 | 0.000 | 1.869 | 91.531 | 0.000 | -0.605 | 0.000 | -0.022 | 0.000 |
Total Facility | 0.331 | -1871.110 | 0.000 | -5453.702 | 0.000 | 0.000 | 1964.550 | 782.723 | 2365.005 | 951.225 | 0.000 | 93.874 | 1252.237 | 0.000 | -40.868 | 0.000 | -4.821 | -39.446 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -22311.13 | 0.00 | 0.00 | 5924.48 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4463.56 |
RETAIL_1_FLR_1 | 05-JAN-15:10 | 0.00 | 0.00 | 0.00 | -3836.65 | 0.00 | 0.00 | 225.90 | 166.00 | 252.59 | 2466.82 | 0.00 | 110.05 | 615.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2754.08 | 0.00 | 0.00 | 697.63 | 615.12 | 752.15 | 0.00 | 0.00 | 29.45 | 659.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 13-JUN-19:30 | 0.00 | 0.00 | 0.00 | -3765.82 | 0.00 | 0.00 | 129.09 | 684.18 | 839.45 | 0.00 | 0.00 | 71.92 | 2041.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 13-JUN-19:30 | 0.00 | 0.00 | 0.00 | -1814.67 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 41.49 | 1179.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-MAY-20:00 | 0.00 | 0.00 | 0.00 | -36984.81 | 0.00 | 0.00 | 408.89 | 325.08 | 44299.38 | 0.00 | 0.00 | 85.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8134.04 |
CAFE_FLR_1 | 08-DEC-22:10 | 0.00 | 0.00 | 0.00 | -12984.60 | 0.00 | 0.00 | 8908.43 | 1134.35 | 711.25 | 140.50 | 0.00 | 100.23 | 1989.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 13-JUN-21:10 | 0.00 | 0.00 | 0.00 | -47860.87 | 0.00 | 0.00 | 26440.98 | 6336.53 | 7389.94 | 422.70 | 0.00 | 361.43 | 6909.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 13-JUN-18:02 | 0.00 | -11280.16 | 0.00 | -750.18 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 2253.64 | 0.00 | 239.89 | 8083.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 26-MAY-15:02 | 0.00 | -11388.74 | 0.00 | -746.22 | 0.00 | 0.00 | 235.27 | 199.20 | 200.16 | 5418.13 | 0.00 | 271.28 | 5810.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-DEC-13:50 | 0.00 | -38816.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 34920.88 | 0.00 | 850.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1686.29 |
ROOM_4_MULT19_FLR_3 | 19-JUN-18:02 | 0.00 | -79010.64 | 0.00 | -10306.70 | 0.00 | 0.00 | 6374.46 | 7563.69 | 9021.83 | 4512.93 | 0.00 | 715.31 | 61129.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 27-DEC-09:01 | 0.00 | -10235.82 | 0.00 | -767.26 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 6013.02 | 0.00 | 93.31 | 4043.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 24-FEB-09:11 | 0.00 | -10568.60 | 0.00 | -938.61 | 0.00 | 0.00 | 74.67 | 313.04 | 452.99 | 5117.23 | 0.00 | 24.61 | 5524.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 | -12768.65 | 0.00 | 0.00 | 4663.30 | 6639.35 | 0.00 | 719.03 | 0.00 | 212.78 | 534.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 08-AUG-18:02 | 0.00 | -3060.30 | 0.00 | -185.95 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 516.06 | 0.00 | 47.26 | 2319.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 13-JUN-15:02 | 0.00 | -3128.83 | 0.00 | -190.27 | 0.00 | 0.00 | 58.82 | 49.80 | 50.04 | 1617.70 | 0.00 | 84.65 | 1458.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-DEC-16:02 | 0.00 | -12972.68 | 0.00 | -1233.64 | 0.00 | 0.00 | 294.10 | 332.11 | 487.74 | 3670.06 | 0.00 | 217.06 | 9205.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -25469.20 | 0.00 | 0.00 | 15645.42 | 1992.02 | 6747.90 | 256.59 | 0.00 | 91.78 | 735.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -26701.87 | 0.00 | 0.00 | 15645.33 | 1992.02 | 6747.90 | 241.40 | 0.00 | 91.78 | 1983.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 07-MAY-10:50 | 0.00 | 0.00 | 0.00 | -30643.69 | 0.00 | 0.00 | 461.54 | 353.60 | 24259.91 | 2137.82 | 0.00 | 127.46 | 3303.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 13-JUN-15:40 | 0.00 | 0.00 | 0.00 | -7505.46 | 0.00 | 0.00 | 771.15 | 548.96 | 0.00 | 1677.92 | 0.00 | 161.38 | 4346.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUN-18:02 | 0.00 | -160772.99 | 0.00 | -231150.73 | 0.00 | 0.00 | 73806.60 | 56569.79 | 120482.43 | 28314.95 | 0.00 | 5137.18 | 107612.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 24-JAN-09:04 | 2000.80 | 562.01 | 0.00 | -562.01 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 1762.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -58.52 | -4558.15 |
ROOM_2_FLR_3 | 17-MAY-08:04 | 1970.36 | 630.19 | 0.00 | -630.19 | 0.00 | 0.00 | 87.14 | 313.04 | 452.99 | 1003.44 | 0.00 | 78.10 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3905.07 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21-DEC-22:56 | 14152.10 | 8570.83 | 0.00 | -8570.83 | 0.00 | 0.00 | 8458.22 | 5694.01 | 6668.31 | 0.00 | 0.00 | 267.31 | 0.00 | 0.00 | -377.55 | 0.00 | 0.00 | -34862.40 |
ROOM_5_FLR_3 | 23-OCT-08:05 | 1600.86 | 633.24 | 0.00 | -633.24 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 1694.51 | 0.00 | 97.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4246.31 |
ROOM_6_FLR_3 | 22-OCT-19:46 | 1235.31 | 634.19 | 0.00 | -634.19 | 0.00 | 0.00 | 278.97 | 711.45 | 653.15 | 0.00 | 0.00 | 99.84 | 0.00 | 0.00 | -8.71 | 0.00 | 0.00 | -2970.01 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 24-JAN-09:04 | 523.01 | 139.09 | 0.00 | -139.09 | 0.00 | 0.00 | 21.85 | 78.27 | 113.26 | 438.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.48 | -1160.04 |
ROOM_2_FLR_6 | 17-MAY-08:04 | 512.69 | 157.46 | 0.00 | -157.46 | 0.00 | 0.00 | 21.79 | 78.26 | 113.25 | 252.19 | 0.00 | 19.22 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -997.39 |
ROOM_3_MULT9_FLR_6 | 17-DEC-09:06 | 1541.39 | 1017.47 | 0.00 | -1017.47 | 0.00 | 0.00 | 294.10 | 563.59 | 1439.98 | 2633.03 | 0.00 | 99.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6571.73 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-22:56 | -207652.78 | 195469.92 | 0.00 | -195469.92 | 0.00 | 0.00 | 95961.83 | 43159.07 | 95722.11 | 0.00 | 0.00 | 551.56 | 0.00 | 0.00 | -5738.02 | 0.00 | -728.95 | -21274.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.2442 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.0781 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6560 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6560 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9560 | 2.9560 | 1.5490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3078 | 0.3078 | 0.1613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2764 | 0.2764 | 0.1448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2847 | 0.2847 | 0.1492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1558 | 0.1558 | 0.0816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1962 | 3.1962 | 1.6748 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2854 | 1.2854 | 0.6735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7500 | 4.7500 | 2.4890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5391 | 1.5391 | 0.8065 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2101 | 2.2101 | 1.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3118 | 2.3118 | 1.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2044 | 2.2044 | 1.1551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7665 | 0.7665 | 0.4017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.2442 | 22.0781 | 22.2442 | 11.6560 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5490 | 1.5490 | 1.5490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1613 | 0.1613 | 0.1613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1448 | 0.1448 | 0.1448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1492 | 0.1492 | 0.1492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0816 | 0.0816 | 0.0816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6748 | 1.6748 | 1.6748 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6735 | 0.6735 | 0.6735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4890 | 2.4890 | 2.4890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8065 | 0.8065 | 0.8065 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1581 | 1.1581 | 1.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2114 | 1.2114 | 1.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1551 | 1.1551 | 1.1551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4017 | 0.4017 | 0.4017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6560 | 11.6560 | 11.6560 | 11.6560 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 50.50 |
Number of hours not met | 50.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 25.38 | 10022.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4830.95 | 263115.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.72 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.17 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 499.49 | 29183.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 145.80 | 5789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 302.68 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.75 | 2397.33 | 209146.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.40 | 1892.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.96 | 1192.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.62 | 9207.98 |
Natural Gas | 1788.84 | 4211.56 |
Additional | 0.00 | 0.00 |
Total | 3509.46 | 13419.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.99 |
Space Heating | 0.00 |
Space Cooling | 425.81 |
Fans (All) | 44.03 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 811.61 |
Subtotal | 811.61 |
Natural Gas [MJ/m2] | |
Space Heating | 2.24 |
Service Water Heating | 211.31 |
Miscellaneous (All) | 371.22 |
Subtotal | 371.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.83 |
Space Heating | 0.19 |
Space Cooling | 36.00 |
Fans (All) | 3.72 |
Service Water Heating | 18.54 |
Receptacle Equipment | 25.69 |
Miscellaneous | 10.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3150.00 | 5610.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 3150.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 5610.00 | 0.00 | 0.00 | 0.00 |
Average | 8505.00 | 255.00 | 0.00 | 0.00 | 0.00 |
Sum | 187110.00 | 5610.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7742.67 | 1017.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8680.67 | 79.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 2082.17 | 6677.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8650.33 | 109.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8653.33 | 106.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8675.00 | 85.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 2082.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 6677.83 | 0.00 | 0.00 | 0.00 |
Average | 8390.95 | 369.05 | 0.00 | 0.00 | 0.00 |
Sum | 184600.83 | 8119.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 580210.83 | 130206.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4132.67 | 21.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4140.00 | 14.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4132.50 | 21.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4131.33 | 22.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1226675.00 | 19040.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245491.00 | 224.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 130206.17 | 0.00 | 0.00 | 0.00 |
Average | 282089.33 | 6797.71 | 0.00 | 0.00 | 0.00 |
Sum | 6205965.33 | 149549.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:45:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527024E+11 | 20936.39 | 06-JAN-22:00 | 24.60 | 22.00 | 0.763215E+10 | 4739.59 | 06-JAN-22:10 | 24.50 | 21.98 |
February | 0.480960E+11 | 20941.02 | 24-FEB-22:00 | 26.80 | 22.90 | 0.697146E+10 | 4740.90 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.528366E+11 | 20794.32 | 01-MAR-22:00 | 26.00 | 23.18 | 0.768826E+10 | 4707.10 | 01-MAR-22:10 | 25.83 | 23.12 |
April | 0.512334E+11 | 20899.13 | 28-APR-21:00 | 28.50 | 25.82 | 0.743077E+10 | 4731.33 | 28-APR-21:10 | 28.43 | 25.81 |
May | 0.534799E+11 | 21210.32 | 08-MAY-21:00 | 28.00 | 26.50 | 0.775979E+10 | 4803.48 | 08-MAY-21:10 | 27.23 | 25.96 |
June | 0.525103E+11 | 22310.94 | 15-JUN-21:00 | 29.00 | 26.74 | 0.763268E+10 | 4836.85 | 13-JUN-21:10 | 29.00 | 26.74 |
July | 0.537185E+11 | 21182.81 | 28-JUL-21:00 | 25.00 | 23.59 | 0.777697E+10 | 4797.58 | 28-JUL-21:10 | 24.87 | 23.50 |
August | 0.532766E+11 | 21206.94 | 15-AUG-21:00 | 27.00 | 24.83 | 0.774736E+10 | 4803.68 | 15-AUG-21:10 | 26.87 | 24.82 |
September | 0.515651E+11 | 21143.93 | 08-SEP-21:00 | 28.00 | 25.20 | 0.747506E+10 | 4788.58 | 08-SEP-21:10 | 27.68 | 24.93 |
October | 0.524808E+11 | 20862.72 | 05-OCT-21:00 | 26.50 | 25.32 | 0.760229E+10 | 4722.63 | 05-OCT-21:10 | 26.65 | 25.42 |
November | 0.512116E+11 | 21042.06 | 22-NOV-22:00 | 25.60 | 23.63 | 0.741206E+10 | 4764.78 | 22-NOV-22:10 | 25.42 | 23.59 |
December | 0.529837E+11 | 21078.39 | 08-DEC-22:00 | 28.10 | 23.77 | 0.767138E+10 | 4773.30 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.626095E+12 | 0.908002E+11 | ||||||||
Minimum of Months | 0.480960E+11 | 20794.32 | 24.60 | 22.00 | 0.697146E+10 | 4707.10 | 24.50 | 21.98 | ||
Maximum of Months | 0.537185E+11 | 22310.94 | 29.00 | 26.74 | 0.777697E+10 | 4836.85 | 29.00 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644336E+10 | 3836.53 | 05-JAN-15:10 | 33.73 | 23.23 | 0.793014E+09 | 491.82 | 17-JAN-23:19 | 24.30 | 21.68 |
February | 0.595158E+10 | 3504.56 | 03-FEB-16:03 | 33.17 | 23.89 | 0.727728E+09 | 491.82 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.628915E+10 | 3190.14 | 20-MAR-19:10 | 29.00 | 23.66 | 0.807647E+09 | 491.82 | 13-MAR-22:19 | 29.00 | 23.66 |
April | 0.587142E+10 | 3054.23 | 01-APR-18:03 | 30.82 | 26.81 | 0.775873E+09 | 491.81 | 26-APR-22:19 | 28.13 | 23.80 |
May | 0.596185E+10 | 3330.52 | 05-MAY-19:10 | 30.92 | 26.05 | 0.795158E+09 | 491.83 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.588996E+10 | 3353.11 | 12-JUN-19:10 | 31.17 | 27.49 | 0.778053E+09 | 491.81 | 11-JUN-23:19 | 31.17 | 27.49 |
July | 0.565057E+10 | 2965.46 | 14-JUL-19:30 | 29.85 | 24.95 | 0.781977E+09 | 491.83 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.561437E+10 | 2951.34 | 14-AUG-19:20 | 29.40 | 27.71 | 0.774439E+09 | 491.83 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.560359E+10 | 3195.71 | 13-SEP-19:20 | 30.33 | 26.40 | 0.758823E+09 | 491.81 | 08-SEP-22:19 | 30.33 | 26.40 |
October | 0.572387E+10 | 3064.60 | 04-OCT-19:10 | 28.42 | 25.07 | 0.774317E+09 | 491.81 | 04-OCT-22:19 | 27.00 | 25.53 |
November | 0.590093E+10 | 3434.29 | 19-NOV-13:00 | 32.40 | 24.76 | 0.760056E+09 | 491.81 | 22-NOV-23:19 | 24.33 | 23.33 |
December | 0.631824E+10 | 3803.75 | 08-DEC-14:00 | 33.00 | 23.23 | 0.787590E+09 | 491.83 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.712189E+11 | 0.931467E+10 | ||||||||
Minimum of Months | 0.560359E+10 | 2951.34 | 28.42 | 23.23 | 0.727728E+09 | 491.81 | 22.00 | 19.41 | ||
Maximum of Months | 0.644336E+10 | 3836.53 | 33.73 | 27.71 | 0.807647E+09 | 491.83 | 31.17 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490775E+10 | 2328.32 | 31-JAN-21:10 | 26.73 | 22.00 | 0.898926E+09 | 569.49 | 31-JAN-22:19 | 26.27 | 22.11 |
February | 0.455703E+10 | 2444.77 | 22-FEB-21:10 | 27.43 | 22.28 | 0.829777E+09 | 569.53 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.508543E+10 | 2477.53 | 29-MAR-20:10 | 28.00 | 23.68 | 0.925325E+09 | 569.53 | 13-MAR-22:19 | 28.00 | 23.68 |
April | 0.494824E+10 | 2522.38 | 27-APR-20:10 | 29.37 | 24.32 | 0.892870E+09 | 569.53 | 26-APR-22:19 | 29.37 | 24.32 |
May | 0.505188E+10 | 2651.05 | 05-MAY-20:10 | 29.83 | 26.38 | 0.916533E+09 | 569.55 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.501141E+10 | 2754.02 | 13-JUN-20:10 | 30.67 | 27.30 | 0.899012E+09 | 569.53 | 11-JUN-23:19 | 30.67 | 27.30 |
July | 0.494166E+10 | 2456.14 | 14-JUL-20:50 | 28.58 | 24.55 | 0.904695E+09 | 569.55 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.490772E+10 | 2423.91 | 14-AUG-20:10 | 29.00 | 28.18 | 0.899439E+09 | 569.55 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.478339E+10 | 2580.00 | 13-SEP-20:10 | 29.92 | 26.86 | 0.873428E+09 | 569.53 | 12-SEP-22:19 | 29.92 | 26.86 |
October | 0.483203E+10 | 2320.05 | 04-OCT-20:10 | 27.92 | 25.10 | 0.886436E+09 | 569.53 | 04-OCT-22:19 | 27.00 | 25.53 |
November | 0.472419E+10 | 2296.53 | 03-NOV-20:10 | 25.50 | 24.73 | 0.864313E+09 | 569.49 | 22-NOV-22:19 | 25.23 | 23.55 |
December | 0.488029E+10 | 2264.08 | 07-DEC-21:10 | 26.88 | 23.89 | 0.894109E+09 | 569.52 | 26-DEC-22:10 | 23.08 | 19.87 |
Annual Sum or Average | 0.586310E+11 | 0.106849E+11 | ||||||||
Minimum of Months | 0.455703E+10 | 2264.08 | 25.50 | 22.00 | 0.829777E+09 | 569.49 | 23.08 | 19.87 | ||
Maximum of Months | 0.508543E+10 | 2754.02 | 30.67 | 28.18 | 0.925325E+09 | 569.55 | 30.67 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498063E+10 | 2014.99 | 05-JAN-21:00 | 27.00 | 23.38 | 0.186252E+09 | 117.87 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.462380E+10 | 2033.37 | 22-FEB-21:00 | 27.50 | 22.29 | 0.173031E+09 | 119.01 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.515989E+10 | 2237.07 | 29-MAR-20:00 | 28.00 | 23.68 | 0.193751E+09 | 120.45 | 29-MAR-21:30 | 28.10 | 23.70 |
April | 0.516719E+10 | 2808.22 | 30-APR-19:20 | 32.33 | 26.74 | 0.190546E+09 | 120.45 | 26-APR-22:19 | 32.33 | 26.74 |
May | 0.566459E+10 | 3271.96 | 05-MAY-19:30 | 30.55 | 26.16 | 0.199619E+09 | 120.45 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.599938E+10 | 3765.89 | 13-JUN-19:30 | 30.90 | 27.22 | 0.196460E+09 | 120.45 | 26-JUN-22:19 | 24.27 | 24.10 |
July | 0.547599E+10 | 3154.38 | 14-JUL-20:00 | 29.50 | 24.72 | 0.198624E+09 | 120.45 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.523797E+10 | 2814.50 | 01-AUG-20:00 | 29.00 | 27.47 | 0.193546E+09 | 120.45 | 15-AUG-22:19 | 26.13 | 25.18 |
September | 0.498133E+10 | 2403.87 | 08-SEP-20:00 | 29.00 | 25.99 | 0.185961E+09 | 120.45 | 08-SEP-22:10 | 26.02 | 23.59 |
October | 0.499836E+10 | 2041.27 | 04-OCT-20:00 | 28.00 | 25.05 | 0.186765E+09 | 119.47 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.485967E+10 | 2025.56 | 21-NOV-21:00 | 28.00 | 25.20 | 0.181352E+09 | 118.53 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.496225E+10 | 2008.03 | 08-DEC-22:00 | 28.10 | 23.77 | 0.185382E+09 | 117.54 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.621110E+11 | 0.227129E+10 | ||||||||
Minimum of Months | 0.462380E+10 | 2008.03 | 27.00 | 22.29 | 0.173031E+09 | 117.54 | 23.42 | 22.22 | ||
Maximum of Months | 0.599938E+10 | 3765.89 | 32.33 | 27.47 | 0.199619E+09 | 120.45 | 32.33 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270879E+10 | 1078.80 | 05-JAN-22:10 | 26.38 | 23.18 | 0.142136E+09 | 88.63 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.251138E+10 | 1087.53 | 22-FEB-22:10 | 27.00 | 22.22 | 0.131860E+09 | 89.38 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.279688E+10 | 1109.87 | 29-MAR-21:10 | 28.03 | 23.69 | 0.147502E+09 | 91.25 | 29-MAR-21:10 | 28.03 | 23.69 |
April | 0.277109E+10 | 1326.60 | 30-APR-19:20 | 32.33 | 26.74 | 0.145225E+09 | 92.65 | 28-APR-22:19 | 32.33 | 26.74 |
May | 0.299153E+10 | 1580.69 | 06-MAY-19:00 | 32.30 | 26.17 | 0.152626E+09 | 92.65 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.313789E+10 | 1814.70 | 13-JUN-19:30 | 30.90 | 27.22 | 0.150503E+09 | 92.65 | 13-JUN-03:20 | 30.90 | 27.22 |
July | 0.290599E+10 | 1467.13 | 14-JUL-20:00 | 29.50 | 24.72 | 0.151478E+09 | 92.65 | 14-JUL-23:19 | 27.00 | 24.11 |
August | 0.281019E+10 | 1303.65 | 01-AUG-20:00 | 29.00 | 27.47 | 0.147580E+09 | 92.65 | 01-AUG-22:19 | 28.07 | 26.61 |
September | 0.269569E+10 | 1122.43 | 07-SEP-21:10 | 28.97 | 26.76 | 0.141580E+09 | 92.27 | 07-SEP-21:10 | 28.97 | 26.76 |
October | 0.271478E+10 | 1091.00 | 04-OCT-21:10 | 27.42 | 25.35 | 0.142396E+09 | 89.64 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.264064E+10 | 1084.21 | 21-NOV-22:10 | 27.33 | 25.20 | 0.138304E+09 | 89.11 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.269947E+10 | 1078.03 | 08-DEC-22:10 | 27.92 | 23.84 | 0.141516E+09 | 88.60 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.333843E+11 | 0.173271E+10 | ||||||||
Minimum of Months | 0.251138E+10 | 1078.03 | 26.38 | 22.22 | 0.131860E+09 | 88.60 | 24.07 | 22.22 | ||
Maximum of Months | 0.313789E+10 | 1814.70 | 32.33 | 27.47 | 0.152626E+09 | 92.65 | 32.33 | 27.22 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535293E+11 | 35723.84 | 04-JAN-21:00 | 26.80 | 23.34 | 0.544771E+09 | 381.52 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.491154E+11 | 35953.58 | 22-FEB-21:00 | 27.50 | 22.29 | 0.495068E+09 | 381.49 | 22-FEB-22:30 | 26.80 | 22.14 |
March | 0.547297E+11 | 36314.04 | 29-MAR-20:00 | 28.00 | 23.68 | 0.551084E+09 | 381.50 | 03-MAR-22:30 | 28.00 | 23.68 |
April | 0.531893E+11 | 36591.18 | 28-APR-20:00 | 29.00 | 25.99 | 0.532880E+09 | 381.49 | 26-APR-21:30 | 29.00 | 25.99 |
May | 0.546958E+11 | 36984.73 | 05-MAY-20:00 | 30.00 | 26.30 | 0.550378E+09 | 381.51 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.535050E+11 | 36936.63 | 13-JUN-20:00 | 31.00 | 27.23 | 0.535043E+09 | 381.49 | 07-JUN-21:30 | 31.00 | 27.23 |
July | 0.540627E+11 | 36435.79 | 14-JUL-20:00 | 29.50 | 24.72 | 0.546554E+09 | 381.52 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.537683E+11 | 36307.77 | 01-AUG-20:00 | 29.00 | 27.47 | 0.547780E+09 | 381.51 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.522127E+11 | 36238.56 | 06-SEP-20:00 | 28.50 | 26.55 | 0.529161E+09 | 381.51 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.530875E+11 | 35887.29 | 04-OCT-20:00 | 28.00 | 25.05 | 0.543950E+09 | 381.51 | 30-OCT-21:10 | 23.98 | 23.94 |
November | 0.517591E+11 | 35616.85 | 22-NOV-21:00 | 25.00 | 23.59 | 0.527223E+09 | 381.51 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.532347E+11 | 35620.09 | 08-DEC-21:00 | 28.00 | 24.30 | 0.543661E+09 | 381.52 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.636889E+12 | 0.644755E+10 | ||||||||
Minimum of Months | 0.491154E+11 | 35616.85 | 25.00 | 22.29 | 0.495068E+09 | 381.49 | 22.00 | 18.26 | ||
Maximum of Months | 0.547297E+11 | 36984.73 | 31.00 | 27.47 | 0.551084E+09 | 381.52 | 31.00 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261505E+11 | 12898.11 | 05-JAN-22:10 | 26.38 | 23.18 | 0.108017E+11 | 6462.43 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.237755E+11 | 12569.15 | 22-FEB-22:10 | 27.00 | 22.22 | 0.982206E+10 | 6461.92 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.254688E+11 | 12409.09 | 13-MAR-21:10 | 28.03 | 22.97 | 0.108440E+11 | 6461.89 | 03-MAR-04:19 | 28.03 | 22.97 |
April | 0.241050E+11 | 12106.83 | 19-APR-21:10 | 28.97 | 26.21 | 0.103789E+11 | 6461.87 | 20-APR-22:19 | 27.13 | 24.77 |
May | 0.247743E+11 | 12602.51 | 05-MAY-21:10 | 29.02 | 26.76 | 0.107145E+11 | 6462.54 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.242353E+11 | 12532.65 | 13-JUN-21:10 | 28.97 | 27.36 | 0.104184E+11 | 6461.83 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.239871E+11 | 11689.76 | 26-JUL-21:10 | 26.87 | 24.52 | 0.106057E+11 | 6462.61 | 19-JUL-22:10 | 26.87 | 24.52 |
August | 0.238361E+11 | 11984.51 | 14-AUG-21:10 | 28.95 | 27.94 | 0.105780E+11 | 6462.54 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.235825E+11 | 12228.35 | 13-SEP-21:10 | 29.32 | 26.39 | 0.102957E+11 | 6462.47 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.242799E+11 | 12268.46 | 16-OCT-21:10 | 27.02 | 25.86 | 0.106152E+11 | 6461.88 | 31-OCT-22:19 | 25.00 | 24.11 |
November | 0.244535E+11 | 12475.96 | 21-NOV-22:10 | 27.33 | 25.20 | 0.103916E+11 | 6462.49 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.258540E+11 | 12983.29 | 08-DEC-22:10 | 27.92 | 23.84 | 0.107781E+11 | 6462.50 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.294503E+12 | 0.126244E+12 | ||||||||
Minimum of Months | 0.235825E+11 | 11689.76 | 26.38 | 22.22 | 0.982206E+10 | 6461.83 | 22.00 | 18.26 | ||
Maximum of Months | 0.261505E+11 | 12983.29 | 29.32 | 27.94 | 0.108440E+11 | 6462.61 | 28.07 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.877578E+11 | 42050.14 | 05-JAN-22:10 | 26.38 | 23.18 | 0.312870E+11 | 19185.78 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.807157E+11 | 41792.64 | 22-FEB-22:10 | 27.00 | 22.22 | 0.286042E+11 | 19184.74 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.888578E+11 | 41688.78 | 29-MAR-21:10 | 28.03 | 23.69 | 0.317108E+11 | 19184.75 | 02-MAR-23:19 | 28.03 | 23.69 |
April | 0.863529E+11 | 42981.75 | 28-APR-21:10 | 28.43 | 25.81 | 0.306161E+11 | 19184.70 | 26-APR-22:19 | 28.43 | 25.81 |
May | 0.904642E+11 | 45903.99 | 05-MAY-21:10 | 29.02 | 26.76 | 0.317614E+11 | 19185.92 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.901687E+11 | 47857.02 | 13-JUN-21:10 | 28.97 | 27.36 | 0.310277E+11 | 19185.05 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.887316E+11 | 43872.55 | 14-JUL-21:10 | 28.23 | 24.46 | 0.315321E+11 | 19186.01 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.872189E+11 | 42862.46 | 01-AUG-21:10 | 28.85 | 27.27 | 0.312878E+11 | 19185.93 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.845733E+11 | 41749.12 | 13-SEP-21:10 | 29.32 | 26.39 | 0.302649E+11 | 19184.68 | 08-SEP-22:19 | 29.32 | 26.39 |
October | 0.860360E+11 | 40657.71 | 04-OCT-21:10 | 27.42 | 25.35 | 0.309561E+11 | 19184.66 | 10-OCT-22:19 | 24.57 | 23.94 |
November | 0.844947E+11 | 41139.44 | 21-NOV-22:10 | 27.33 | 25.20 | 0.302001E+11 | 19185.86 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.873823E+11 | 41986.06 | 08-DEC-22:10 | 27.92 | 23.84 | 0.312093E+11 | 19185.88 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.104275E+13 | 0.370458E+12 | ||||||||
Minimum of Months | 0.807157E+11 | 40657.71 | 26.38 | 22.22 | 0.286042E+11 | 19184.66 | 22.00 | 18.26 | ||
Maximum of Months | 0.904642E+11 | 47857.02 | 29.32 | 27.36 | 0.317614E+11 | 19186.01 | 29.32 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256875E+10 | 2965.83 | 30-JAN-19:02 | 27.17 | 23.15 | 99149797.91 | 56.70 | 30-JAN-03:00 | 27.17 | 23.15 |
February | 0.249461E+10 | 2965.49 | 04-FEB-19:02 | 28.00 | 23.74 | 89568701.18 | 56.70 | 24-FEB-22:00 | 26.00 | 22.46 |
March | 0.278059E+10 | 2980.61 | 24-MAR-18:02 | 27.97 | 24.37 | 99231065.32 | 56.70 | 22-MAR-21:40 | 27.97 | 24.37 |
April | 0.269136E+10 | 2973.30 | 21-APR-18:02 | 29.95 | 25.43 | 95949924.72 | 56.70 | 26-APR-22:10 | 28.22 | 23.80 |
May | 0.266565E+10 | 2999.96 | 08-MAY-15:02 | 29.40 | 27.49 | 99193140.57 | 56.69 | 17-MAY-01:49 | 24.05 | 24.03 |
June | 0.267772E+10 | 3007.30 | 13-JUN-18:02 | 31.80 | 28.00 | 96022358.46 | 56.70 | 13-JUN-23:10 | 28.00 | 26.50 |
July | 0.239435E+10 | 2974.14 | 20-JUL-15:02 | 32.78 | 26.38 | 99100814.24 | 56.69 | 09-JUL-02:49 | 32.78 | 26.38 |
August | 0.237643E+10 | 3000.06 | 10-AUG-15:02 | 30.83 | 27.07 | 99200823.63 | 56.69 | 24-AUG-01:49 | 23.17 | 23.05 |
September | 0.235844E+10 | 2991.47 | 04-SEP-15:02 | 32.17 | 27.38 | 95935285.48 | 56.70 | 12-SEP-21:30 | 26.30 | 24.85 |
October | 0.233495E+10 | 2981.68 | 20-OCT-15:02 | 30.43 | 25.02 | 99132092.17 | 56.70 | 02-OCT-21:30 | 30.43 | 25.02 |
November | 0.236724E+10 | 2973.69 | 13-NOV-16:02 | 27.83 | 24.85 | 95978864.44 | 56.70 | 24-NOV-03:09 | 25.05 | 21.96 |
December | 0.247178E+10 | 2927.90 | 04-DEC-16:02 | 29.08 | 22.75 | 99116835.39 | 56.70 | 07-DEC-22:30 | 26.15 | 22.96 |
Annual Sum or Average | 0.301819E+11 | 0.116758E+10 | ||||||||
Minimum of Months | 0.233495E+10 | 2927.90 | 27.17 | 22.75 | 89568701.18 | 56.69 | 23.17 | 21.96 | ||
Maximum of Months | 0.278059E+10 | 3007.30 | 32.78 | 28.00 | 99231065.32 | 56.70 | 32.78 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218857E+10 | 2988.56 | 29-JAN-19:02 | 28.67 | 23.86 | 0.100459E+09 | 71.96 | 23-JAN-22:00 | 28.67 | 23.86 |
February | 0.221432E+10 | 2983.29 | 07-FEB-16:02 | 30.08 | 24.34 | 90618253.21 | 56.70 | 13-FEB-01:00 | 24.80 | 22.46 |
March | 0.265461E+10 | 2992.65 | 31-MAR-18:02 | 28.00 | 23.68 | 99384868.31 | 56.70 | 21-MAR-21:40 | 28.00 | 23.68 |
April | 0.270498E+10 | 2999.56 | 08-APR-18:02 | 28.55 | 25.74 | 95996564.69 | 56.70 | 04-APR-21:40 | 28.55 | 25.74 |
May | 0.274634E+10 | 3033.52 | 26-MAY-15:02 | 32.95 | 27.86 | 99440635.80 | 79.38 | 10-MAY-21:00 | 32.95 | 27.86 |
June | 0.282964E+10 | 3032.94 | 16-JUN-18:02 | 30.75 | 25.90 | 96345122.50 | 60.77 | 25-JUN-20:00 | 23.00 | 23.00 |
July | 0.247981E+10 | 3011.12 | 26-JUL-18:02 | 30.42 | 25.63 | 99562284.19 | 81.34 | 19-JUL-21:10 | 30.42 | 25.63 |
August | 0.241304E+10 | 3024.74 | 11-AUG-18:02 | 28.67 | 25.80 | 99482092.37 | 78.13 | 23-AUG-21:00 | 24.30 | 22.91 |
September | 0.231477E+10 | 3027.47 | 04-SEP-15:02 | 32.17 | 27.38 | 96321077.78 | 75.48 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.219906E+10 | 3008.26 | 16-OCT-15:02 | 31.33 | 27.27 | 99620599.74 | 67.15 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.210402E+10 | 2984.15 | 15-NOV-16:02 | 28.08 | 25.50 | 97157926.48 | 75.33 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.207960E+10 | 2985.00 | 12-DEC-16:02 | 30.50 | 25.51 | 0.100771E+09 | 75.44 | 26-DEC-22:10 | 23.08 | 19.87 |
Annual Sum or Average | 0.289288E+11 | 0.117516E+10 | ||||||||
Minimum of Months | 0.207960E+10 | 2983.29 | 28.00 | 23.68 | 90618253.21 | 56.70 | 22.87 | 19.87 | ||
Maximum of Months | 0.282964E+10 | 3033.52 | 32.95 | 27.86 | 0.100771E+09 | 81.34 | 32.95 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791167E+09 | 510.40 | 05-JAN-14:30 | 33.80 | 23.21 | 0.00 | 0.00 | 01-JAN-00:10 | 33.80 | 23.21 |
February | 0.707484E+09 | 455.19 | 04-FEB-14:30 | 32.50 | 24.95 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 24.95 |
March | 0.678784E+09 | 370.82 | 11-MAR-09:00 | 28.00 | 23.68 | 0.00 | 0.00 | 01-MAR-00:10 | 28.00 | 23.68 |
April | 0.593779E+09 | 353.99 | 01-APR-20:20 | 29.33 | 26.00 | 0.00 | 0.00 | 01-APR-00:10 | 29.33 | 26.00 |
May | 0.606801E+09 | 369.08 | 06-MAY-08:00 | 32.00 | 26.09 | 0.00 | 0.00 | 01-MAY-00:10 | 32.00 | 26.09 |
June | 0.588360E+09 | 355.90 | 13-JUN-20:20 | 30.33 | 27.35 | 0.00 | 0.00 | 01-JUN-00:10 | 30.33 | 27.35 |
July | 0.552661E+09 | 334.25 | 15-JUL-20:10 | 28.92 | 25.01 | 0.00 | 0.00 | 01-JUL-00:10 | 28.92 | 25.01 |
August | 0.535116E+09 | 330.99 | 14-AUG-20:50 | 29.00 | 28.18 | 0.00 | 0.00 | 01-AUG-00:10 | 29.00 | 28.18 |
September | 0.568600E+09 | 345.12 | 27-SEP-20:30 | 28.00 | 25.79 | 0.00 | 0.00 | 01-SEP-00:10 | 28.00 | 25.79 |
October | 0.618378E+09 | 392.00 | 29-OCT-08:00 | 28.00 | 25.64 | 0.00 | 0.00 | 01-OCT-00:10 | 28.00 | 25.64 |
November | 0.695728E+09 | 465.75 | 23-NOV-09:00 | 28.50 | 23.82 | 0.00 | 0.00 | 01-NOV-00:10 | 28.50 | 23.82 |
December | 0.776472E+09 | 510.68 | 07-DEC-13:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-DEC-00:10 | 32.80 | 23.14 |
Annual Sum or Average | 0.771333E+10 | 0.00 | ||||||||
Minimum of Months | 0.535116E+09 | 330.99 | 28.00 | 23.14 | 0.00 | 0.00 | 28.00 | 23.14 | ||
Maximum of Months | 0.791167E+09 | 510.68 | 33.80 | 28.18 | 0.00 | 0.00 | 33.80 | 28.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897921E+09 | 1166.75 | 04-JAN-09:01 | 28.32 | 23.71 | 99974860.21 | 68.75 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.862499E+09 | 1159.96 | 22-FEB-19:02 | 29.17 | 22.94 | 90214772.04 | 56.69 | 24-FEB-04:10 | 23.08 | 19.39 |
March | 0.100082E+10 | 1169.46 | 31-MAR-08:61 | 28.17 | 24.35 | 99151326.74 | 56.69 | 07-MAR-22:30 | 28.17 | 24.35 |
April | 0.103235E+10 | 1171.76 | 24-APR-18:02 | 31.17 | 26.11 | 95814041.14 | 56.69 | 27-APR-22:40 | 28.07 | 24.31 |
May | 0.113224E+10 | 1171.38 | 14-MAY-18:02 | 31.87 | 26.79 | 99268297.47 | 73.86 | 10-MAY-21:10 | 31.87 | 26.79 |
June | 0.117180E+10 | 1175.20 | 19-JUN-18:02 | 27.90 | 25.23 | 96217150.28 | 57.63 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.108534E+10 | 1169.62 | 12-JUL-08:61 | 25.23 | 23.66 | 99350825.10 | 76.08 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.102015E+10 | 1157.83 | 01-AUG-08:62 | 29.17 | 27.39 | 99258276.33 | 72.93 | 23-AUG-21:10 | 23.22 | 23.00 |
September | 0.958375E+09 | 1169.34 | 12-SEP-08:61 | 29.00 | 26.74 | 96060749.04 | 73.49 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.938437E+09 | 1164.05 | 17-OCT-08:61 | 28.17 | 25.51 | 99329053.00 | 67.18 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.891436E+09 | 1169.57 | 15-NOV-09:01 | 28.52 | 25.19 | 96762179.69 | 72.28 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.876504E+09 | 1164.40 | 19-DEC-19:02 | 26.00 | 20.73 | 0.100248E+09 | 71.61 | 20-DEC-22:10 | 21.83 | 18.17 |
Annual Sum or Average | 0.118679E+11 | 0.117165E+10 | ||||||||
Minimum of Months | 0.862499E+09 | 1157.83 | 25.23 | 20.73 | 90214772.04 | 56.69 | 21.83 | 18.17 | ||
Maximum of Months | 0.117180E+10 | 1175.20 | 31.87 | 27.39 | 0.100248E+09 | 76.08 | 31.87 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256953E+10 | 2689.16 | 31-JAN-09:02 | 26.33 | 21.99 | 99169750.18 | 56.69 | 25-JAN-01:00 | 26.33 | 21.99 |
February | 0.251467E+10 | 2715.46 | 27-FEB-09:01 | 27.35 | 22.81 | 89578635.12 | 56.70 | 07-FEB-22:49 | 27.35 | 22.81 |
March | 0.277179E+10 | 2713.69 | 21-MAR-08:61 | 28.50 | 23.03 | 99245427.60 | 56.70 | 13-MAR-22:40 | 28.50 | 23.03 |
April | 0.270364E+10 | 2694.49 | 22-APR-15:02 | 31.48 | 25.99 | 95962804.86 | 56.69 | 22-APR-02:09 | 31.48 | 25.99 |
May | 0.268427E+10 | 2705.76 | 05-MAY-18:02 | 31.85 | 26.66 | 99202198.51 | 56.69 | 04-MAY-23:30 | 31.85 | 26.66 |
June | 0.268490E+10 | 2709.42 | 19-JUN-15:02 | 31.40 | 27.35 | 96033319.87 | 56.70 | 21-JUN-21:19 | 26.13 | 26.01 |
July | 0.239253E+10 | 2694.49 | 09-JUL-15:02 | 31.80 | 25.12 | 99126579.80 | 56.69 | 03-JUL-03:39 | 31.80 | 25.12 |
August | 0.238030E+10 | 2709.34 | 28-AUG-15:02 | 31.87 | 27.90 | 99228048.69 | 56.69 | 14-AUG-22:40 | 31.87 | 27.90 |
September | 0.237601E+10 | 2671.09 | 02-SEP-15:02 | 32.83 | 26.89 | 95949942.10 | 56.69 | 29-SEP-02:49 | 24.08 | 23.28 |
October | 0.233602E+10 | 2705.76 | 16-OCT-15:02 | 31.33 | 27.27 | 99153816.50 | 56.69 | 02-OCT-01:00 | 31.33 | 27.27 |
November | 0.237343E+10 | 2700.32 | 22-NOV-09:02 | 28.22 | 23.51 | 95990358.18 | 56.70 | 21-NOV-23:10 | 28.22 | 23.51 |
December | 0.247298E+10 | 2750.69 | 27-DEC-09:01 | 26.40 | 20.69 | 99131361.13 | 56.70 | 06-DEC-22:30 | 26.40 | 20.69 |
Annual Sum or Average | 0.302601E+11 | 0.116777E+10 | ||||||||
Minimum of Months | 0.233602E+10 | 2671.09 | 26.33 | 20.69 | 89578635.12 | 56.69 | 24.08 | 20.69 | ||
Maximum of Months | 0.277179E+10 | 2750.69 | 32.83 | 27.90 | 99245427.60 | 56.70 | 31.87 | 27.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216603E+10 | 2682.68 | 30-JAN-16:02 | 29.92 | 24.51 | 0.100903E+09 | 72.43 | 23-JAN-22:00 | 29.92 | 24.51 |
February | 0.221818E+10 | 2877.10 | 24-FEB-09:11 | 26.07 | 19.98 | 90958575.04 | 56.69 | 25-FEB-05:19 | 24.00 | 21.17 |
March | 0.264389E+10 | 2728.61 | 09-MAR-09:01 | 30.22 | 23.02 | 99430109.46 | 56.69 | 05-MAR-02:00 | 30.22 | 23.02 |
April | 0.271754E+10 | 2716.33 | 10-APR-15:02 | 32.85 | 27.14 | 96001111.76 | 56.69 | 28-APR-23:10 | 28.00 | 25.79 |
May | 0.276557E+10 | 2733.81 | 05-MAY-08:62 | 32.17 | 26.12 | 99430390.68 | 77.86 | 31-MAY-21:00 | 24.10 | 23.85 |
June | 0.283701E+10 | 2732.54 | 18-JUN-18:02 | 31.07 | 27.26 | 96353367.52 | 59.75 | 25-JUN-20:00 | 23.00 | 23.00 |
July | 0.247891E+10 | 2710.32 | 08-JUL-15:02 | 31.40 | 24.32 | 99573485.26 | 78.80 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.241747E+10 | 2726.97 | 28-AUG-15:02 | 31.87 | 27.90 | 99497522.40 | 76.60 | 23-AUG-21:00 | 31.87 | 27.90 |
September | 0.233226E+10 | 2699.44 | 13-SEP-15:02 | 32.92 | 26.53 | 96331484.07 | 75.03 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.219805E+10 | 2705.40 | 08-OCT-15:02 | 31.22 | 25.87 | 99662810.53 | 67.35 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.210311E+10 | 2693.57 | 24-NOV-16:02 | 28.40 | 22.75 | 97295516.65 | 75.14 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.205885E+10 | 2693.76 | 27-DEC-09:01 | 26.40 | 20.69 | 0.101189E+09 | 74.41 | 26-DEC-22:10 | 26.40 | 20.69 |
Annual Sum or Average | 0.289369E+11 | 0.117663E+10 | ||||||||
Minimum of Months | 0.205885E+10 | 2682.68 | 26.07 | 19.98 | 90958575.04 | 56.69 | 22.87 | 20.57 | ||
Maximum of Months | 0.283701E+10 | 2877.10 | 32.92 | 27.90 | 0.101189E+09 | 78.80 | 31.87 | 27.90 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684340E+10 | 2685.06 | 31-JAN-22:10 | 26.33 | 22.10 | 0.149103E+10 | 916.01 | 31-JAN-22:30 | 26.20 | 22.13 |
February | 0.630741E+10 | 2709.19 | 24-FEB-22:10 | 26.67 | 22.83 | 0.137571E+10 | 924.46 | 24-FEB-22:30 | 26.40 | 22.68 |
March | 0.691630E+10 | 2690.52 | 29-MAR-21:10 | 28.03 | 23.69 | 0.151557E+10 | 917.47 | 21-MAR-21:30 | 28.03 | 23.69 |
April | 0.668471E+10 | 2694.06 | 28-APR-21:10 | 28.43 | 25.81 | 0.146043E+10 | 918.78 | 28-APR-21:30 | 28.30 | 25.78 |
May | 0.697596E+10 | 2775.19 | 06-MAY-21:10 | 29.85 | 26.27 | 0.152414E+10 | 944.13 | 05-MAY-21:30 | 29.85 | 26.27 |
June | 0.689802E+10 | 3192.11 | 13-JUN-20:10 | 30.67 | 27.30 | 0.150517E+10 | 951.82 | 12-JUN-22:19 | 30.67 | 27.30 |
July | 0.681342E+10 | 2657.53 | 27-JUL-21:10 | 26.97 | 24.11 | 0.148614E+10 | 905.64 | 27-JUL-21:30 | 26.90 | 24.09 |
August | 0.672022E+10 | 2677.40 | 14-AUG-21:10 | 28.95 | 27.94 | 0.147232E+10 | 912.30 | 14-AUG-21:40 | 28.80 | 27.23 |
September | 0.650675E+10 | 2657.29 | 08-SEP-21:10 | 27.68 | 24.93 | 0.142107E+10 | 905.99 | 08-SEP-21:30 | 27.05 | 24.38 |
October | 0.670325E+10 | 2641.25 | 04-OCT-21:10 | 27.42 | 25.35 | 0.146205E+10 | 900.26 | 05-OCT-21:40 | 27.10 | 25.72 |
November | 0.658581E+10 | 2690.80 | 22-NOV-22:10 | 25.42 | 23.59 | 0.143384E+10 | 917.22 | 22-NOV-22:30 | 25.05 | 23.51 |
December | 0.681523E+10 | 2711.17 | 08-DEC-22:10 | 27.92 | 23.84 | 0.148407E+10 | 924.94 | 08-DEC-22:30 | 27.55 | 23.96 |
Annual Sum or Average | 0.807705E+11 | 0.176316E+11 | ||||||||
Minimum of Months | 0.630741E+10 | 2641.25 | 25.42 | 22.10 | 0.137571E+10 | 900.26 | 25.05 | 22.13 | ||
Maximum of Months | 0.697596E+10 | 3192.11 | 30.67 | 27.94 | 0.152414E+10 | 951.82 | 30.67 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262874E+10 | 3241.57 | 04-JAN-16:02 | 31.48 | 24.73 | 99132755.32 | 56.70 | 29-JAN-00:20 | 24.33 | 21.71 |
February | 0.253967E+10 | 3233.49 | 04-FEB-16:02 | 32.50 | 24.69 | 89553421.63 | 56.70 | 25-FEB-01:19 | 25.00 | 22.79 |
March | 0.287440E+10 | 3242.83 | 09-MAR-16:02 | 33.17 | 24.95 | 99213492.83 | 56.70 | 03-MAR-22:40 | 33.17 | 24.95 |
April | 0.281249E+10 | 3231.77 | 02-APR-15:02 | 34.75 | 27.18 | 95938519.86 | 56.70 | 05-APR-21:10 | 28.00 | 25.05 |
May | 0.274398E+10 | 3242.15 | 06-MAY-15:02 | 36.65 | 27.35 | 99180826.57 | 56.70 | 09-MAY-21:10 | 29.00 | 27.47 |
June | 0.273173E+10 | 3218.32 | 22-JUN-18:02 | 26.07 | 25.16 | 96010523.46 | 56.70 | 13-JUN-21:40 | 26.07 | 25.16 |
July | 0.245882E+10 | 3218.25 | 03-JUL-15:02 | 25.88 | 23.72 | 99081435.00 | 56.70 | 26-JUL-00:10 | 26.77 | 23.75 |
August | 0.245343E+10 | 3245.98 | 08-AUG-18:02 | 29.80 | 28.15 | 99187630.03 | 56.70 | 28-AUG-00:00 | 26.40 | 24.54 |
September | 0.245485E+10 | 3228.33 | 20-SEP-15:02 | 28.72 | 26.54 | 95924076.62 | 56.70 | 14-SEP-01:00 | 28.72 | 26.54 |
October | 0.240274E+10 | 3219.60 | 12-OCT-18:02 | 28.42 | 25.27 | 99115857.78 | 56.70 | 17-OCT-00:30 | 25.85 | 24.48 |
November | 0.242028E+10 | 3200.99 | 03-NOV-18:02 | 28.82 | 25.57 | 95970509.25 | 56.70 | 21-NOV-01:10 | 25.33 | 22.88 |
December | 0.251614E+10 | 3208.14 | 13-DEC-19:02 | 28.17 | 23.09 | 99104867.53 | 56.70 | 14-DEC-22:49 | 23.22 | 21.09 |
Annual Sum or Average | 0.310373E+11 | 0.116741E+10 | ||||||||
Minimum of Months | 0.240274E+10 | 3200.99 | 25.88 | 23.09 | 89553421.63 | 56.70 | 23.22 | 21.09 | ||
Maximum of Months | 0.287440E+10 | 3245.98 | 36.65 | 28.15 | 99213492.83 | 56.70 | 33.17 | 27.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225158E+10 | 3218.77 | 17-JAN-19:02 | 26.42 | 21.74 | 0.100225E+09 | 71.18 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.226544E+10 | 3232.23 | 17-FEB-19:02 | 28.08 | 22.77 | 90439281.36 | 56.70 | 21-FEB-00:49 | 26.58 | 22.22 |
March | 0.274824E+10 | 3252.79 | 23-MAR-18:02 | 28.83 | 24.57 | 99343220.81 | 56.70 | 17-MAR-00:30 | 28.83 | 24.57 |
April | 0.282752E+10 | 3229.08 | 18-APR-18:02 | 29.40 | 26.09 | 95990924.49 | 56.70 | 05-APR-00:40 | 29.40 | 26.09 |
May | 0.283003E+10 | 3285.11 | 31-MAY-15:02 | 34.33 | 27.03 | 99432975.93 | 80.47 | 10-MAY-21:00 | 34.33 | 27.03 |
June | 0.289201E+10 | 3318.92 | 13-JUN-15:02 | 35.92 | 28.46 | 96337928.20 | 62.67 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.255098E+10 | 3233.73 | 27-JUL-18:02 | 29.78 | 24.89 | 99554367.29 | 84.44 | 19-JUL-21:00 | 29.78 | 24.89 |
August | 0.249307E+10 | 3260.71 | 08-AUG-18:02 | 29.80 | 28.15 | 99480126.22 | 80.07 | 23-AUG-21:00 | 24.30 | 22.91 |
September | 0.241152E+10 | 3239.35 | 24-SEP-18:02 | 28.87 | 26.02 | 96343429.76 | 77.21 | 15-SEP-21:10 | 28.87 | 26.02 |
October | 0.226478E+10 | 3260.12 | 18-OCT-15:02 | 29.90 | 26.58 | 99624222.38 | 69.34 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.215531E+10 | 3249.45 | 03-NOV-18:02 | 28.82 | 25.57 | 97111679.14 | 75.16 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.212717E+10 | 3224.02 | 11-DEC-16:02 | 29.17 | 25.51 | 0.100556E+09 | 75.16 | 26-DEC-22:10 | 23.08 | 19.87 |
Annual Sum or Average | 0.298177E+11 | 0.117444E+10 | ||||||||
Minimum of Months | 0.212717E+10 | 3218.77 | 26.42 | 21.74 | 90439281.36 | 56.70 | 22.50 | 18.29 | ||
Maximum of Months | 0.289201E+10 | 3318.92 | 35.92 | 28.46 | 0.100556E+09 | 84.44 | 34.33 | 27.03 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179434E+10 | 1573.38 | 12-JAN-16:02 | 29.73 | 24.51 | 99209731.86 | 56.69 | 24-JAN-01:10 | 20.52 | 18.04 |
February | 0.161609E+10 | 1575.20 | 13-FEB-16:02 | 33.25 | 25.80 | 89599679.57 | 56.69 | 24-FEB-03:39 | 23.30 | 19.66 |
March | 0.163043E+10 | 1557.11 | 09-MAR-16:02 | 33.17 | 24.95 | 99226749.94 | 56.69 | 03-MAR-02:00 | 33.17 | 24.95 |
April | 0.148581E+10 | 1549.98 | 26-APR-18:02 | 29.95 | 24.10 | 95932450.19 | 56.69 | 22-APR-23:49 | 29.95 | 24.10 |
May | 0.151458E+10 | 1555.27 | 06-MAY-18:02 | 32.05 | 25.49 | 99179063.94 | 56.69 | 05-MAY-23:10 | 32.05 | 25.49 |
June | 0.147011E+10 | 1553.05 | 21-JUN-15:02 | 26.93 | 25.46 | 96006527.29 | 56.69 | 29-JUN-22:10 | 25.67 | 25.67 |
July | 0.138666E+10 | 1550.75 | 15-JUL-18:02 | 31.95 | 25.35 | 99080295.63 | 56.69 | 27-JUL-21:00 | 26.80 | 24.07 |
August | 0.136052E+10 | 1553.63 | 08-AUG-15:02 | 32.82 | 27.71 | 99183897.16 | 56.69 | 11-AUG-22:10 | 27.00 | 25.53 |
September | 0.140748E+10 | 1551.61 | 01-SEP-15:02 | 27.63 | 25.82 | 95925833.89 | 56.69 | 12-SEP-21:49 | 26.50 | 25.05 |
October | 0.149243E+10 | 1537.01 | 18-OCT-15:02 | 29.90 | 26.58 | 99136198.70 | 56.69 | 25-OCT-21:19 | 25.70 | 25.10 |
November | 0.160986E+10 | 1577.74 | 19-NOV-16:02 | 30.00 | 25.69 | 96001590.12 | 56.69 | 25-NOV-02:39 | 24.67 | 20.37 |
December | 0.175953E+10 | 1578.42 | 30-DEC-16:02 | 30.08 | 25.69 | 99170063.96 | 56.69 | 21-DEC-01:10 | 30.08 | 25.69 |
Annual Sum or Average | 0.185278E+11 | 0.116765E+10 | ||||||||
Minimum of Months | 0.136052E+10 | 1537.01 | 26.93 | 24.10 | 89599679.57 | 56.69 | 20.52 | 18.04 | ||
Maximum of Months | 0.179434E+10 | 1578.42 | 33.25 | 27.71 | 99226749.94 | 56.69 | 33.17 | 25.69 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454090E+11 | 23103.08 | 03-JAN-22:10 | 26.88 | 23.35 | 0.190502E+11 | 11348.41 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.418220E+11 | 23180.01 | 15-FEB-23:00 | 27.00 | 24.40 | 0.172856E+11 | 11347.31 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.470063E+11 | 23803.66 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192282E+11 | 11347.33 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.463209E+11 | 24242.94 | 28-APR-21:10 | 28.43 | 25.81 | 0.185959E+11 | 11347.29 | 20-APR-22:19 | 28.43 | 25.81 |
May | 0.483706E+11 | 24905.24 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192282E+11 | 11348.73 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.478467E+11 | 25466.60 | 12-JUN-21:10 | 29.73 | 26.89 | 0.186801E+11 | 11347.27 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.473141E+11 | 24800.53 | 14-JUL-21:10 | 28.23 | 24.46 | 0.191572E+11 | 11348.87 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.464952E+11 | 24335.99 | 01-AUG-21:10 | 28.85 | 27.27 | 0.191707E+11 | 11348.73 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.449290E+11 | 23915.16 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185121E+11 | 11348.57 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.454505E+11 | 23341.69 | 16-OCT-21:30 | 27.05 | 25.72 | 0.190649E+11 | 11347.76 | 30-OCT-22:19 | 23.93 | 23.52 |
November | 0.440138E+11 | 23093.69 | 14-NOV-22:10 | 27.15 | 26.04 | 0.184403E+11 | 11348.59 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.449856E+11 | 23180.51 | 08-DEC-22:10 | 27.92 | 23.84 | 0.190368E+11 | 11348.60 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.549964E+12 | 0.225450E+12 | ||||||||
Minimum of Months | 0.418220E+11 | 23093.69 | 26.88 | 23.35 | 0.172856E+11 | 11347.27 | 22.00 | 18.26 | ||
Maximum of Months | 0.483706E+11 | 25466.60 | 29.73 | 27.27 | 0.192282E+11 | 11348.87 | 28.43 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480315E+11 | 24319.85 | 03-JAN-22:10 | 26.88 | 23.35 | 0.190994E+11 | 11348.42 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.441655E+11 | 24346.82 | 15-FEB-22:10 | 27.00 | 24.52 | 0.173185E+11 | 11347.32 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.496586E+11 | 25011.19 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192648E+11 | 11347.35 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.489374E+11 | 25468.23 | 28-APR-21:10 | 28.43 | 25.81 | 0.186284E+11 | 11347.31 | 20-APR-22:19 | 28.43 | 25.81 |
May | 0.511271E+11 | 26125.85 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192573E+11 | 11348.73 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.505094E+11 | 26699.10 | 12-JUN-21:10 | 29.73 | 26.89 | 0.187040E+11 | 11347.28 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.501556E+11 | 26079.96 | 14-JUL-21:10 | 28.23 | 24.46 | 0.191985E+11 | 11348.87 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.493490E+11 | 25612.72 | 01-AUG-21:10 | 28.85 | 27.27 | 0.192252E+11 | 11348.74 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.476337E+11 | 25160.21 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185620E+11 | 11348.57 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.482349E+11 | 24566.99 | 16-OCT-21:10 | 27.02 | 25.86 | 0.191209E+11 | 11347.77 | 30-OCT-22:19 | 23.93 | 23.52 |
November | 0.466217E+11 | 24345.88 | 14-NOV-22:10 | 27.15 | 26.04 | 0.184906E+11 | 11348.59 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.476400E+11 | 24339.79 | 08-DEC-22:10 | 27.92 | 23.84 | 0.190924E+11 | 11348.60 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.582065E+12 | 0.225962E+12 | ||||||||
Minimum of Months | 0.441655E+11 | 24319.85 | 26.88 | 23.35 | 0.173185E+11 | 11347.28 | 22.00 | 18.26 | ||
Maximum of Months | 0.511271E+11 | 26699.10 | 29.73 | 27.27 | 0.192648E+11 | 11348.87 | 28.43 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.580129E+11 | 29659.61 | 04-JAN-11:50 | 33.00 | 23.69 | 0.187804E+11 | 11319.62 | 28-JAN-18:19 | 26.73 | 22.58 |
February | 0.531311E+11 | 29846.00 | 20-FEB-11:50 | 31.33 | 23.96 | 0.169695E+11 | 11319.62 | 04-FEB-18:19 | 31.33 | 23.96 |
March | 0.589698E+11 | 30171.85 | 19-MAR-10:40 | 33.40 | 23.19 | 0.187967E+11 | 11319.65 | 18-MAR-17:19 | 33.40 | 23.19 |
April | 0.575123E+11 | 30466.99 | 09-APR-10:40 | 33.23 | 26.18 | 0.181908E+11 | 11319.65 | 15-APR-17:19 | 30.50 | 25.05 |
May | 0.590754E+11 | 30646.65 | 07-MAY-10:40 | 33.07 | 26.79 | 0.187966E+11 | 11319.65 | 27-MAY-17:19 | 32.33 | 26.08 |
June | 0.576824E+11 | 30491.46 | 24-JUN-10:50 | 32.20 | 27.56 | 0.181962E+11 | 11319.65 | 17-JUN-17:19 | 32.20 | 27.56 |
July | 0.582948E+11 | 29892.83 | 15-JUL-18:03 | 31.95 | 25.35 | 0.187880E+11 | 11319.65 | 08-JUL-17:19 | 31.95 | 25.35 |
August | 0.579060E+11 | 30142.44 | 27-AUG-10:50 | 32.72 | 27.53 | 0.187918E+11 | 11319.65 | 26-AUG-17:19 | 32.72 | 27.53 |
September | 0.564359E+11 | 30246.84 | 03-SEP-10:50 | 31.78 | 28.02 | 0.181844E+11 | 11319.65 | 02-SEP-17:19 | 31.78 | 28.02 |
October | 0.574355E+11 | 30039.88 | 07-OCT-10:50 | 31.43 | 26.03 | 0.187825E+11 | 11319.65 | 28-OCT-17:19 | 29.50 | 26.26 |
November | 0.559230E+11 | 29786.84 | 23-NOV-11:50 | 30.88 | 24.99 | 0.181749E+11 | 11319.65 | 04-NOV-17:19 | 30.88 | 24.99 |
December | 0.577056E+11 | 29723.71 | 03-DEC-11:50 | 31.00 | 22.63 | 0.187775E+11 | 11319.58 | 02-DEC-18:19 | 31.00 | 22.63 |
Annual Sum or Average | 0.688085E+12 | 0.221229E+12 | ||||||||
Minimum of Months | 0.531311E+11 | 29659.61 | 30.88 | 22.63 | 0.169695E+11 | 11319.58 | 26.73 | 22.58 | ||
Maximum of Months | 0.590754E+11 | 30646.65 | 33.40 | 28.02 | 0.187967E+11 | 11319.65 | 33.40 | 28.02 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141013E+11 | 6911.23 | 05-JAN-16:03 | 32.17 | 22.74 | 0.161331E+10 | 1007.35 | 31-JAN-22:10 | 26.33 | 22.10 |
February | 0.129867E+11 | 6754.14 | 22-FEB-16:03 | 34.42 | 21.55 | 0.148320E+10 | 1007.35 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.143544E+11 | 6733.08 | 28-MAR-15:13 | 34.40 | 25.56 | 0.164784E+10 | 1007.38 | 13-MAR-22:19 | 34.40 | 25.56 |
April | 0.140475E+11 | 6608.12 | 01-APR-14:40 | 35.17 | 26.82 | 0.159678E+10 | 1007.38 | 26-APR-22:19 | 28.13 | 23.80 |
May | 0.146218E+11 | 7307.07 | 06-MAY-14:30 | 37.00 | 27.34 | 0.164342E+10 | 1007.37 | 05-MAY-23:19 | 37.00 | 27.34 |
June | 0.145361E+11 | 7505.27 | 13-JUN-15:40 | 35.67 | 28.55 | 0.160914E+10 | 1007.38 | 11-JUN-23:19 | 35.67 | 28.55 |
July | 0.139531E+11 | 6447.16 | 15-JUL-17:13 | 32.67 | 25.56 | 0.160972E+10 | 1007.37 | 14-JUL-22:19 | 32.67 | 25.56 |
August | 0.137249E+11 | 6262.54 | 14-AUG-15:03 | 31.30 | 27.86 | 0.159107E+10 | 1007.37 | 14-AUG-22:19 | 28.47 | 26.67 |
September | 0.134405E+11 | 6026.48 | 06-SEP-15:03 | 32.60 | 26.92 | 0.155086E+10 | 1007.34 | 08-SEP-21:30 | 27.05 | 24.38 |
October | 0.136813E+11 | 5705.44 | 07-OCT-14:30 | 31.30 | 26.08 | 0.157984E+10 | 1007.34 | 16-OCT-21:10 | 27.02 | 25.86 |
November | 0.134821E+11 | 6313.45 | 22-NOV-14:00 | 31.50 | 24.56 | 0.154611E+10 | 1007.34 | 03-NOV-21:10 | 31.50 | 24.56 |
December | 0.139487E+11 | 6809.20 | 08-DEC-14:30 | 33.00 | 23.44 | 0.159624E+10 | 1007.38 | 08-DEC-23:19 | 26.67 | 24.28 |
Annual Sum or Average | 0.166878E+12 | 0.190675E+11 | ||||||||
Minimum of Months | 0.129867E+11 | 5705.44 | 31.30 | 21.55 | 0.148320E+10 | 1007.34 | 26.33 | 22.10 | ||
Maximum of Months | 0.146218E+11 | 7505.27 | 37.00 | 28.55 | 0.164784E+10 | 1007.38 | 37.00 | 28.55 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 157948.07 | 500.25 | 24-JAN-09:04 | 19.07 |
February | 222556.66 | 381.04 | 08-FEB-09:05 | 25.52 |
March | 168677.32 | 445.42 | 03-MAR-09:05 | 27.33 |
April | 54036.97 | 211.22 | 15-APR-08:05 | 31.00 |
May | 103452.49 | 483.91 | 17-MAY-08:04 | 24.00 |
June | 198464.05 | 317.70 | 26-JUN-08:05 | 28.33 |
July | 748715.82 | 461.84 | 14-JUL-08:05 | 25.83 |
August | 188333.51 | 414.55 | 01-AUG-08:05 | 29.17 |
September | 191608.16 | 383.52 | 16-SEP-18:05 | 23.88 |
October | 207776.84 | 455.66 | 26-OCT-18:05 | 24.98 |
November | 205263.24 | 456.27 | 02-NOV-08:05 | 25.58 |
December | 270977.34 | 452.32 | 20-DEC-09:05 | 24.40 |
Annual Sum or Average | 2717810.47 | |||
Minimum of Months | 54036.97 | 211.22 | 19.07 | |
Maximum of Months | 748715.82 | 500.25 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 336522.33 | 472.78 | 05-JAN-07:14 | 24.67 |
February | 174184.23 | 468.35 | 15-FEB-07:14 | 25.40 |
March | 321689.75 | 455.03 | 04-MAR-09:05 | 29.40 |
April | 78898.78 | 244.24 | 15-APR-08:05 | 31.00 |
May | 83893.82 | 492.63 | 17-MAY-08:04 | 24.00 |
June | 45453.83 | 224.06 | 04-JUN-08:05 | 27.50 |
July | 605887.78 | 485.10 | 07-JUL-08:04 | 25.25 |
August | 213859.25 | 439.72 | 05-AUG-08:05 | 27.33 |
September | 348097.68 | 398.88 | 23-SEP-08:05 | 27.17 |
October | 333417.98 | 462.79 | 26-OCT-18:05 | 24.98 |
November | 439363.19 | 466.93 | 28-NOV-09:05 | 26.55 |
December | 288220.68 | 445.38 | 17-DEC-19:05 | 24.50 |
Annual Sum or Average | 3269489.29 | |||
Minimum of Months | 45453.83 | 224.06 | 24.00 | |
Maximum of Months | 605887.78 | 492.63 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 119932.18 | 174.96 | 24-JAN-16:07 | 29.50 |
February | 74282.39 | 137.75 | 12-FEB-19:07 | 27.92 |
March | 136304.52 | 161.82 | 03-MAR-16:07 | 32.33 |
April | 82227.94 | 138.30 | 15-APR-18:07 | 29.40 |
May | 4658.25 | 25.34 | 11-MAY-08:07 | 28.17 |
June | 13327.19 | 69.99 | 30-JUN-18:07 | 26.90 |
July | 52399.67 | 107.67 | 17-JUL-18:07 | 24.77 |
August | 43799.91 | 101.54 | 06-AUG-18:07 | 26.83 |
September | 54782.32 | 120.72 | 03-SEP-18:07 | 24.97 |
October | 8069.00 | 80.69 | 09-OCT-18:07 | 24.35 |
November | 6249.96 | 42.80 | 28-NOV-16:07 | 28.57 |
December | 110028.13 | 186.21 | 21-DEC-22:56 | 23.00 |
Annual Sum or Average | 706061.47 | |||
Minimum of Months | 4658.25 | 25.34 | 23.00 | |
Maximum of Months | 136304.52 | 186.21 | 32.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 3768.05 | 43.96 | 20-AUG-08:06 | 26.33 |
September | 12282.99 | 143.30 | 18-SEP-08:06 | 24.00 |
October | 30021.05 | 400.28 | 23-OCT-08:05 | 24.75 |
November | 9571.50 | 90.90 | 26-NOV-09:06 | 23.55 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 55643.59 | |||
Minimum of Months | 0.00 | 0.00 | 23.55 | |
Maximum of Months | 30021.05 | 400.28 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45241.02 | 243.81 | 09-JAN-07:56 | 25.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 20633.91 | 240.73 | 29-JUL-06:46 | 26.08 |
August | 13006.71 | 151.74 | 20-AUG-08:06 | 26.33 |
September | 24331.87 | 279.52 | 18-SEP-08:36 | 24.00 |
October | 28011.12 | 308.89 | 22-OCT-19:46 | 24.85 |
November | 4666.14 | 62.22 | 27-NOV-09:26 | 25.05 |
December | 39677.97 | 186.30 | 17-DEC-09:46 | 26.00 |
Annual Sum or Average | 175568.75 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 45241.02 | 308.89 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 484498.78 | 523.09 | 24-JAN-09:04 | 19.07 |
February | 433387.69 | 472.52 | 08-FEB-09:05 | 25.52 |
March | 359050.38 | 462.61 | 12-MAR-08:05 | 26.33 |
April | 251958.34 | 502.66 | 21-APR-08:04 | 26.17 |
May | 332524.29 | 508.42 | 17-MAY-08:04 | 24.00 |
June | 463084.77 | 479.96 | 20-JUN-08:05 | 26.33 |
July | 1171415.41 | 506.75 | 17-JUL-08:04 | 25.75 |
August | 512365.72 | 498.15 | 20-AUG-18:04 | 25.00 |
September | 395511.52 | 383.07 | 21-SEP-08:04 | 24.83 |
October | 424162.49 | 463.62 | 22-OCT-18:05 | 23.18 |
November | 337229.41 | 478.80 | 02-NOV-08:05 | 25.58 |
December | 398554.21 | 471.66 | 20-DEC-09:05 | 24.40 |
Annual Sum or Average | 5563743.01 | |||
Minimum of Months | 251958.34 | 383.07 | 19.07 | |
Maximum of Months | 1171415.41 | 523.09 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 387936.10 | 507.26 | 13-JAN-09:04 | 27.87 |
February | 236062.79 | 459.13 | 15-FEB-07:14 | 25.40 |
March | 508236.99 | 498.96 | 16-MAR-08:04 | 27.17 |
April | 247911.43 | 504.59 | 21-APR-08:04 | 26.17 |
May | 293179.42 | 512.76 | 17-MAY-08:04 | 24.00 |
June | 177361.17 | 472.01 | 20-JUN-08:05 | 26.33 |
July | 955825.39 | 510.41 | 18-JUL-08:04 | 24.93 |
August | 501575.50 | 496.53 | 20-AUG-18:04 | 25.00 |
September | 589642.95 | 489.49 | 20-SEP-08:04 | 26.17 |
October | 712021.83 | 486.20 | 09-OCT-06:34 | 24.80 |
November | 667078.03 | 486.17 | 28-NOV-07:34 | 25.03 |
December | 377858.64 | 505.92 | 21-DEC-22:54 | 23.00 |
Annual Sum or Average | 5654690.24 | |||
Minimum of Months | 177361.17 | 459.13 | 23.00 | |
Maximum of Months | 955825.39 | 512.76 | 27.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25834.16 | 122.86 | 01-JAN-09:06 | 24.28 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 30628.71 | 94.10 | 15-MAR-08:06 | 24.50 |
April | 35767.43 | 49.50 | 11-APR-08:06 | 29.75 |
May | 30330.09 | 73.39 | 26-MAY-08:06 | 27.17 |
June | 14068.80 | 74.36 | 01-JUN-08:06 | 26.00 |
July | 22735.68 | 63.14 | 19-JUL-08:06 | 26.70 |
August | 73084.68 | 109.10 | 20-AUG-18:06 | 25.00 |
September | 57837.52 | 70.11 | 25-SEP-08:06 | 28.25 |
October | 71992.12 | 80.85 | 18-OCT-08:06 | 26.17 |
November | 15143.23 | 140.33 | 27-NOV-09:06 | 24.68 |
December | 30883.88 | 171.29 | 17-DEC-09:06 | 24.40 |
Annual Sum or Average | 408306.30 | |||
Minimum of Months | 0.00 | 0.00 | 24.28 | |
Maximum of Months | 73084.68 | 171.29 | 29.75 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123718E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.111771E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122372E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.115398E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.120690E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.115355E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.119926E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.120405E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.119373E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.123683E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.119052E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.123366E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.143511E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.111771E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.123718E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.934832E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.844610E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.937823E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.902001E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.937693E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.906877E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.934270E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.938388E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.905757E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.936575E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.906574E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.932461E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110179E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.844610E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.938388E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267303E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.239872E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.263668E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249988E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.258463E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.247556E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.256073E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259557E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254900E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.265767E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.258012E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.266925E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308808E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.239872E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.267303E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267303E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.239872E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.263668E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249988E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.258463E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.247556E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.256073E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259557E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254900E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.265767E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.258012E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.266925E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308808E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.239872E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.267303E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95912498.89 | 6555209.85 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107482E+09 | 596162.13 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145258E+09 | 55790.03 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166993E+09 | 0.00 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170892E+09 | 122699.25 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158104E+09 | 107112.08 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123350E+09 | 130227.16 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136551E+09 | 63215.12 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127699E+09 | 946.07 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113741E+09 | 12244.93 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97996281.77 | 436180.56 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84630759.48 | 7192316.61 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152861E+10 | 15272103.81 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84630759.48 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170892E+09 | 7192316.61 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42979435.63 | 3014130.61 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45702956.44 | 334836.01 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59708765.35 | 45425.35 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67021017.94 | 0.00 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68298729.21 | 48664.59 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62969666.50 | 61732.09 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49348876.86 | 53753.14 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54025430.17 | 25798.06 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51914094.38 | 6643.76 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47596192.56 | 0.00 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42759049.56 | 285911.52 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38666456.07 | 3382489.17 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630991E+09 | 7259384.29 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38666456.07 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68298729.21 | 3382489.17 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103712E+09 | 5958135.83 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109261E+09 | 619125.79 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141229E+09 | 88045.15 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153018E+09 | 1478.02 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149468E+09 | 121581.25 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136128E+09 | 361861.20 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102511E+09 | 154747.35 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119472E+09 | 45416.40 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118087E+09 | 4686.68 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110705E+09 | 0.00 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100608E+09 | 583161.65 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92781202.82 | 6218211.64 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143698E+10 | 14156450.97 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92781202.82 | 0.00 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153018E+09 | 6218211.64 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60712295.53 | 3316547.47 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64126228.22 | 319294.06 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82902870.95 | 33188.65 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89605610.27 | 449.82 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87134201.18 | 68541.64 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79096693.68 | 159965.00 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60400442.52 | 69625.03 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70206566.39 | 15140.82 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69552550.66 | 28.45 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65091776.79 | 0.00 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59119240.32 | 294248.12 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54323815.65 | 3425859.77 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842272E+09 | 7702888.83 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54323815.65 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89605610.27 | 3425859.77 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.169716E+09 | 3444099.97 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.185792E+09 | 607509.90 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.235228E+09 | 13509.79 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.256741E+09 | 0.00 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.260338E+09 | 149970.76 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.244936E+09 | 181052.78 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.197315E+09 | 165252.10 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.208765E+09 | 150821.50 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.203474E+09 | 229971.06 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.186446E+09 | 106576.20 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.171840E+09 | 701118.91 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.153441E+09 | 3012949.59 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.247403E+10 | 8762832.55 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.153441E+09 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.260338E+09 | 3444099.97 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.123718E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207191E+09 | 25636644.07 |
February | 0.236489E+11 | 0.111771E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230507E+09 | 3944302.42 |
March | 0.262800E+11 | 0.122372E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318605E+09 | 1205284.37 |
April | 0.253579E+11 | 0.115398E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370179E+09 | 0.00 |
May | 0.262123E+11 | 0.120690E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374619E+09 | 291989.73 |
June | 0.254132E+11 | 0.115355E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350969E+09 | 1013964.50 |
July | 0.261570E+11 | 0.119926E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266531E+09 | 565866.00 |
August | 0.262677E+11 | 0.120405E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291552E+09 | 223847.06 |
September | 0.253456E+11 | 0.119373E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275805E+09 | 435642.48 |
October | 0.261693E+11 | 0.123683E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237721E+09 | 349125.65 |
November | 0.253025E+11 | 0.119052E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205736E+09 | 4947517.01 |
December | 0.261570E+11 | 0.123366E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185298E+09 | 32096675.84 |
Annual Sum or Average | 0.308468E+12 | 0.143511E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331471E+10 | 70710859.12 |
Minimum of Months | 0.236489E+11 | 0.111771E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185298E+09 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.123718E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374619E+09 | 32096675.84 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.934832E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659475E+09 | 66645746.61 |
February | 0.702046E+11 | 0.844610E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714426E+09 | 9871983.38 |
March | 0.780153E+11 | 0.937823E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952153E+09 | 2715226.38 |
April | 0.752779E+11 | 0.902001E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107084E+10 | 0.00 |
May | 0.778146E+11 | 0.937693E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106819E+10 | 838664.13 |
June | 0.754422E+11 | 0.906877E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989259E+09 | 3006716.89 |
July | 0.776503E+11 | 0.934270E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748048E+09 | 1463246.16 |
August | 0.779788E+11 | 0.938388E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830650E+09 | 536001.55 |
September | 0.752414E+11 | 0.905757E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805541E+09 | 851713.30 |
October | 0.776868E+11 | 0.936575E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718144E+09 | 432631.43 |
November | 0.751137E+11 | 0.906574E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643568E+09 | 11531406.10 |
December | 0.776503E+11 | 0.932461E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592798E+09 | 81589163.44 |
Annual Sum or Average | 0.915726E+12 | 0.110179E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979309E+10 | 0.179482E+09 |
Minimum of Months | 0.702046E+11 | 0.844610E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592798E+09 | 0.00 |
Maximum of Months | 0.780153E+11 | 0.938388E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107084E+10 | 81589163.44 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84165547.86 | 1161278.00 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92402697.31 | 6634.29 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116761E+09 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127013E+09 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128476E+09 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121794E+09 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97942461.75 | 726.85 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103133E+09 | 34332.54 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100586E+09 | 394.58 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91804373.06 | 2083.97 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85202340.05 | 50062.26 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76058041.70 | 807244.05 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122534E+10 | 2062756.54 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76058041.70 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128476E+09 | 1161278.00 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82374288.80 | 2080500.55 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90618640.34 | 340828.01 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116496E+09 | 168.27 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126917E+09 | 717.19 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128252E+09 | 74194.42 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121318E+09 | 90462.65 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97356496.17 | 101075.25 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102780E+09 | 92122.26 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100107E+09 | 72505.99 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91086027.60 | 58990.34 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83696140.72 | 454303.85 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73612547.11 | 1379013.16 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121461E+10 | 4744881.93 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73612547.11 | 168.27 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128252E+09 | 2080500.55 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6278265.30 | 7976822.80 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7706290.90 | 4294228.42 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10492393.62 | 2570120.79 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12395618.64 | 742730.77 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13134087.69 | 1863475.76 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12171402.51 | 1983178.04 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6683752.68 | 4103092.37 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7382557.44 | 3333998.37 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7363250.07 | 3269546.63 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5414537.94 | 4596264.28 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5193740.82 | 5450620.82 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5256023.89 | 9178398.09 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99471921.50 | 49362477.13 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5193740.82 | 742730.77 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13134087.69 | 9178398.09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23253131.66 | 505669.42 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25531632.58 | 53477.42 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32724336.71 | 0.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35590883.73 | 0.00 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35909684.41 | 6591.65 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33944477.50 | 12796.99 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27294697.86 | 11487.52 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28854916.86 | 13818.42 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28133495.00 | 9246.40 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25642605.75 | 5882.26 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23579022.28 | 86988.46 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20819320.51 | 329561.08 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341278E+09 | 1035519.62 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20819320.51 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35909684.41 | 505669.42 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84073575.56 | 1189663.38 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92299463.12 | 9143.10 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116637E+09 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126889E+09 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128381E+09 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121693E+09 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97817279.17 | 727.21 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102992E+09 | 34331.81 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100477E+09 | 304.36 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91690737.33 | 2098.90 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85110781.77 | 52845.70 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75961020.13 | 814801.74 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122402E+10 | 2103916.21 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75961020.13 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128381E+09 | 1189663.38 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81931833.83 | 2717565.68 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90199802.98 | 738400.39 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116301E+09 | 2498.97 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126807E+09 | 159.58 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128168E+09 | 58968.75 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121211E+09 | 80572.09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97216564.64 | 82459.82 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102646E+09 | 83443.89 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99987046.48 | 65133.51 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90929569.94 | 62356.57 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83409268.80 | 532375.36 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73063678.66 | 1786487.24 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121187E+10 | 6210421.85 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73063678.66 | 159.58 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128168E+09 | 2717565.68 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76630396.85 | 5830350.96 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81710594.87 | 678462.23 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109613E+09 | 84807.07 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123362E+09 | 763.02 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121996E+09 | 60597.17 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111007E+09 | 111171.35 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89977159.16 | 9385.68 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99305406.76 | 2733.95 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96967693.94 | 1257.79 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86112163.32 | 1026.53 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76325965.90 | 686530.53 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68310583.77 | 6023535.35 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114132E+10 | 13490621.62 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68310583.77 | 763.02 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123362E+09 | 6023535.35 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83171512.78 | 1217311.19 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91467146.35 | 7364.57 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115717E+09 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125991E+09 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127442E+09 | 152.69 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120793E+09 | 151.26 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96900423.24 | 1128.23 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102085E+09 | 38000.76 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99561033.66 | 807.10 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90756824.33 | 2772.16 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84180378.03 | 54368.45 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75052453.62 | 865531.00 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121312E+10 | 2187587.42 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75052453.62 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127442E+09 | 1217311.19 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81523017.85 | 1920174.29 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89845270.24 | 248240.67 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115480E+09 | 0.00 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125888E+09 | 1251.33 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127224E+09 | 81819.87 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120344E+09 | 112204.11 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96349476.23 | 135971.38 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101741E+09 | 114995.59 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99076258.50 | 111158.23 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90066188.63 | 108201.86 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82769455.27 | 490402.53 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72811247.55 | 1302777.06 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120312E+10 | 4627196.91 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72811247.55 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127224E+09 | 1920174.29 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42418962.57 | 636548.31 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46704172.73 | 4528.06 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59175295.42 | 0.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64486689.81 | 0.00 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65211452.56 | 77.28 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61819489.93 | 76.86 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49585392.34 | 576.85 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52243940.60 | 19238.53 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50932791.02 | 304.66 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46383584.70 | 1552.64 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42977994.64 | 29795.27 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38258223.94 | 447121.83 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620198E+09 | 1139820.27 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38258223.94 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65211452.56 | 636548.31 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133275E+09 | 19802276.87 |
February | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146748E+09 | 3910078.01 |
March | 0.461508E+11 | 0.263668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194574E+09 | 1243199.41 |
April | 0.445315E+11 | 0.249988E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219277E+09 | 22216.28 |
May | 0.460320E+11 | 0.258463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220078E+09 | 361279.50 |
June | 0.446286E+11 | 0.247556E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205289E+09 | 1066809.50 |
July | 0.459349E+11 | 0.256073E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146751E+09 | 858761.66 |
August | 0.461292E+11 | 0.259557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162472E+09 | 800585.03 |
September | 0.445099E+11 | 0.254900E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158300E+09 | 823254.73 |
October | 0.459565E+11 | 0.265767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136558E+09 | 1122044.97 |
November | 0.444343E+11 | 0.258012E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126620E+09 | 5297346.63 |
December | 0.459349E+11 | 0.266925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119494E+09 | 24720733.70 |
Annual Sum or Average | 0.541708E+12 | 0.308808E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196944E+10 | 60028586.29 |
Minimum of Months | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119494E+09 | 22216.28 |
Maximum of Months | 0.461508E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220078E+09 | 24720733.70 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131137E+09 | 19996174.94 |
February | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145090E+09 | 3969842.45 |
March | 0.461508E+11 | 0.263668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192628E+09 | 1246595.42 |
April | 0.445315E+11 | 0.249988E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217556E+09 | 25677.00 |
May | 0.460320E+11 | 0.258463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218468E+09 | 361456.19 |
June | 0.446286E+11 | 0.247556E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203933E+09 | 1070814.91 |
July | 0.459349E+11 | 0.256073E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144560E+09 | 864962.77 |
August | 0.461292E+11 | 0.259557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159866E+09 | 865763.10 |
September | 0.445099E+11 | 0.254900E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155893E+09 | 841483.88 |
October | 0.459565E+11 | 0.265767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133902E+09 | 1159986.49 |
November | 0.444343E+11 | 0.258012E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124322E+09 | 5385639.06 |
December | 0.459349E+11 | 0.266925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117127E+09 | 24884673.71 |
Annual Sum or Average | 0.541708E+12 | 0.308808E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194448E+10 | 60673069.92 |
Minimum of Months | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117127E+09 | 25677.00 |
Maximum of Months | 0.461508E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218468E+09 | 24884673.71 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.116363E+09 | 10871133.70 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.135248E+09 | 2513894.31 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.178577E+09 | 334497.26 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.202606E+09 | 16811.34 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.203669E+09 | 246178.83 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.191288E+09 | 501375.42 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.137369E+09 | 401395.68 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.149228E+09 | 479684.80 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.145566E+09 | 437055.66 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.124981E+09 | 500810.96 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.114904E+09 | 2392233.87 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.100400E+09 | 11551131.10 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.180020E+10 | 30246202.94 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.100400E+09 | 16811.34 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.203669E+09 | 11551131.10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121461E+09 | 9403636.84 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133490E+09 | 910145.76 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179157E+09 | 135562.69 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201780E+09 | 3030.91 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204766E+09 | 182483.48 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188633E+09 | 221816.11 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146674E+09 | 119131.99 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164236E+09 | 54625.38 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156176E+09 | 14056.51 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140359E+09 | 951.48 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123019E+09 | 780932.57 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109480E+09 | 10431314.39 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186923E+10 | 22257688.12 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109480E+09 | 951.48 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204766E+09 | 10431314.39 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 | 04-JAN-13:00 | 41.61 | 24-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.39 | 26-FEB-14:00 | 40.68 | 21-FEB-10:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 21-MAR-13:00 | 7.16 | 03-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 | 06-MAY-13:00 | 23.54 | 10-MAY-20:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.81 | 13-JUN-14:00 | 8.90 | 25-JUN-20:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.90 | 01-JUL-13:00 | 11.76 | 19-JUL-18:53 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 | 22-AUG-15:00 | 11.78 | 23-AUG-20:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.11 | 12-SEP-14:00 | 0.72 | 15-SEP-17:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 | 04-OCT-14:00 | 4.60 | 09-OCT-18:53 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.45 | 18-NOV-13:00 | 27.98 | 25-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 08-DEC-14:00 | 46.39 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 0.00 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 | 46.39 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.87 | 04-JAN-13:00 | 19.07 | 23-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | 26-FEB-14:00 | 11.57 | 21-FEB-10:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 | 21-MAR-13:00 | 5.13 | 03-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 06-MAY-13:00 | 9.09 | 10-MAY-20:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 18-JUN-14:00 | 3.26 | 25-JUN-20:20 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 01-JUL-13:00 | 4.54 | 19-JUL-18:57 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 | 22-AUG-15:00 | 4.55 | 23-AUG-20:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 | 10-SEP-14:00 | 1.64 | 15-SEP-21:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.20 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 | 18-NOV-13:00 | 13.26 | 25-NOV-05:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 07-DEC-14:00 | 21.22 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 21.22 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 | 04-JAN-13:00 | 41.54 | 23-JAN-06:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.64 | 21-FEB-14:00 | 29.29 | 21-FEB-10:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.90 | 21-MAR-13:00 | 10.50 | 03-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.71 | 01-APR-14:00 | 2.59 | 14-APR-15:52 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 | 06-MAY-13:00 | 21.48 | 10-MAY-20:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.97 | 13-JUN-14:00 | 10.75 | 25-JUN-21:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 | 01-JUL-13:00 | 10.73 | 19-JUL-19:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.88 | 22-AUG-15:00 | 8.91 | 23-AUG-20:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.35 | 12-SEP-14:00 | 2.10 | 15-SEP-21:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.89 | 18-NOV-13:00 | 30.28 | 25-NOV-05:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | 07-DEC-14:00 | 47.10 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 | 0.00 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 | 47.10 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 04-JAN-13:00 | 23.81 | 23-JAN-06:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.66 | 21-FEB-14:00 | 16.47 | 21-FEB-10:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.31 | 21-MAR-13:00 | 5.73 | 03-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.41 | 01-APR-14:00 | 0.82 | 14-APR-15:52 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 06-MAY-13:00 | 12.39 | 10-MAY-20:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 13-JUN-14:00 | 5.74 | 20-JUN-24:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 01-JUL-13:00 | 5.75 | 19-JUL-19:10 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 | 22-AUG-15:00 | 3.16 | 23-AUG-19:52 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.77 | 12-SEP-14:00 | 0.05 | 15-SEP-21:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.56 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 18-NOV-13:00 | 17.34 | 25-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.66 | 07-DEC-14:00 | 27.05 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 0.00 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 27.05 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 176.99 | 04-JAN-13:00 | 55.25 | 24-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 197.16 | 26-FEB-14:30 | 38.26 | 21-FEB-10:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 207.46 | 19-MAR-14:00 | 5.90 | 14-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 194.59 | 02-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 218.97 | 06-MAY-13:00 | 29.33 | 10-MAY-20:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 205.99 | 18-JUN-14:00 | 14.67 | 25-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 164.02 | 15-JUL-16:00 | 14.65 | 19-JUL-18:57 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 182.34 | 27-AUG-14:00 | 14.68 | 23-AUG-19:56 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 182.36 | 10-SEP-14:00 | 14.69 | 16-SEP-20:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 163.06 | 28-OCT-13:00 | 11.95 | 22-OCT-18:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 182.11 | 18-NOV-13:00 | 19.11 | 25-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 162.43 | 08-DEC-14:00 | 64.21 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 162.43 | 0.00 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 218.97 | 64.21 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.68 | 04-JAN-13:00 | 128.75 | 23-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.99 | 26-FEB-14:00 | 71.85 | 21-FEB-10:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.96 | 21-MAR-13:00 | 49.69 | 03-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.04 | 09-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.90 | 05-MAY-12:00 | 52.02 | 10-MAY-19:56 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.46 | 16-JUN-13:00 | 25.89 | 25-JUN-21:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.07 | 28-JUL-13:00 | 25.76 | 19-JUL-18:55 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.80 | 22-AUG-15:00 | 26.02 | 23-AUG-19:56 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.50 | 06-SEP-14:00 | 24.29 | 15-SEP-21:10 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.16 | 04-OCT-14:00 | 23.36 | 23-OCT-24:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.44 | 18-NOV-13:00 | 99.04 | 25-NOV-05:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.51 | 08-DEC-14:00 | 145.15 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 225.51 | 0.00 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 337.90 | 145.15 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 787.11 | 04-JAN-13:00 | 357.47 | 23-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 859.32 | 26-FEB-14:00 | 199.50 | 02-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 954.90 | 21-MAR-13:00 | 126.45 | 03-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 876.81 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 996.12 | 06-MAY-13:00 | 148.68 | 10-MAY-20:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 901.43 | 16-JUN-13:00 | 74.28 | 25-JUN-21:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 729.39 | 28-JUL-13:00 | 74.27 | 19-JUL-18:55 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 821.95 | 22-AUG-15:00 | 74.40 | 23-AUG-19:56 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.86 | 12-SEP-14:00 | 62.05 | 15-SEP-21:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 730.05 | 04-OCT-14:00 | 46.14 | 23-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.09 | 18-NOV-13:00 | 267.02 | 25-NOV-05:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 703.75 | 07-DEC-14:00 | 402.04 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 703.75 | 0.00 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 996.12 | 402.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 03-JAN-16:10 | 30.33 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 | 22-FEB-16:10 | 5.92 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 06-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-JUL-16:00 | 1.21 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 9.42 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 04-SEP-16:00 | 1.43 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 2.58 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 18-NOV-13:00 | 7.96 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 13-DEC-16:10 | 21.97 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 30.33 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 03-JAN-16:10 | 30.26 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 22-FEB-16:10 | 13.51 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 0.69 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 3.73 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 | 06-MAY-15:10 | 11.57 | 10-MAY-20:30 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.18 | 13-JUN-15:10 | 10.23 | 25-JUN-20:50 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 15-JUL-16:00 | 10.67 | 19-JUL-20:30 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 9.43 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.03 | 04-SEP-16:00 | 6.92 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:08 | 7.20 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 18-NOV-13:00 | 11.61 | 25-NOV-06:30 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 13-DEC-16:10 | 27.29 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 0.69 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 | 30.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 04-JAN-13:00 | 15.50 | 23-JAN-06:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 26-FEB-14:00 | 12.37 | 21-FEB-10:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 21-MAR-13:00 | 9.00 | 03-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 | 01-APR-14:00 | 7.25 | 14-APR-15:52 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 06-MAY-13:00 | 8.97 | 10-MAY-19:52 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 13-JUN-14:00 | 7.07 | 25-JUN-23:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 15-JUL-16:00 | 7.05 | 13-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 22-AUG-15:00 | 8.99 | 20-AUG-11:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 10-SEP-14:00 | 7.26 | 19-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 04-OCT-14:00 | 8.02 | 23-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 18-NOV-13:00 | 12.89 | 25-NOV-05:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 07-DEC-14:00 | 16.91 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 7.05 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 16.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 03-JAN-16:10 | 7.91 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 22-FEB-16:08 | 3.09 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 | 06-MAY-15:10 | 1.90 | 10-MAY-20:40 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 | 13-JUN-15:10 | 1.76 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 15-JUL-16:00 | 1.54 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 13-AUG-15:10 | 2.37 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 04-SEP-16:00 | 1.39 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 04-OCT-15:10 | 1.33 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 18-NOV-13:00 | 2.78 | 25-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 13-DEC-16:10 | 7.39 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 | 7.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 03-JAN-16:10 | 30.33 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 22-FEB-16:10 | 5.92 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 06-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-JUL-16:00 | 1.21 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 9.43 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 04-SEP-16:00 | 1.06 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 2.58 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 | 18-NOV-13:00 | 7.96 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 13-DEC-16:10 | 21.96 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | 30.33 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 03-JAN-16:08 | 37.35 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 22-FEB-16:10 | 17.85 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 | 19-MAR-15:10 | 2.65 | 15-MAR-07:30 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.40 | 01-APR-15:10 | 1.31 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 06-MAY-15:10 | 10.06 | 10-MAY-20:30 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.18 | 13-JUN-15:10 | 8.96 | 25-JUN-20:50 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-JUL-16:00 | 8.26 | 19-JUL-20:30 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 13-AUG-15:10 | 9.42 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.03 | 04-SEP-16:00 | 6.49 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 04-OCT-15:10 | 7.20 | 30-OCT-17:50 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 18-NOV-13:00 | 16.74 | 25-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 13-DEC-16:08 | 30.30 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 1.31 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 37.35 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.92 | 04-JAN-13:00 | 36.11 | 23-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 | 26-FEB-14:00 | 23.49 | 21-FEB-10:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.13 | 21-MAR-13:00 | 9.67 | 03-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.93 | 01-APR-14:00 | 1.34 | 14-APR-15:52 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 | 06-MAY-13:00 | 14.14 | 10-MAY-19:52 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.97 | 24-JUN-14:00 | 5.90 | 20-JUN-24:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.96 | 15-JUL-16:00 | 1.91 | 19-JUL-18:52 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.32 | 22-AUG-15:00 | 2.91 | 20-AUG-11:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 | 12-SEP-14:00 | 0.79 | 15-SEP-21:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.31 | 28-OCT-13:00 | 0.57 | 23-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 18-NOV-13:00 | 26.10 | 25-NOV-05:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 07-DEC-14:00 | 39.08 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 0.57 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 | 39.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 | 03-JAN-16:10 | 30.40 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 | 22-FEB-16:10 | 6.34 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.03 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 06-MAY-15:10 | 0.25 | 21-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.82 | 13-JUN-15:10 | 0.25 | 30-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.66 | 15-JUL-16:00 | 1.62 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.90 | 13-AUG-15:10 | 9.83 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 | 04-SEP-16:00 | 1.84 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 04-OCT-15:10 | 2.98 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 | 18-NOV-13:00 | 8.37 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 | 13-DEC-16:10 | 22.38 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 30.40 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 | 03-JAN-16:10 | 29.27 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 | 22-FEB-16:10 | 11.13 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.60 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 | 01-APR-15:10 | 5.32 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 | 06-MAY-15:10 | 12.05 | 10-MAY-20:40 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.76 | 13-JUN-15:10 | 12.44 | 25-JUN-21:30 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 15-JUL-16:00 | 13.58 | 19-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 13-AUG-15:10 | 10.64 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 | 04-SEP-16:00 | 9.00 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.41 | 04-OCT-15:10 | 9.52 | 30-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.29 | 18-NOV-13:00 | 11.58 | 16-NOV-19:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 13-DEC-16:10 | 24.58 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 0.00 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 | 29.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.35 | 03-JAN-16:10 | 15.73 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.31 | 22-FEB-16:10 | 3.24 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 06-MAY-15:10 | 0.13 | 21-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.02 | 13-JUN-15:10 | 0.13 | 30-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 15-JUL-16:00 | 0.83 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.88 | 13-AUG-15:10 | 5.03 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 04-SEP-16:00 | 0.75 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.53 | 04-OCT-15:10 | 1.52 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 18-NOV-13:00 | 4.28 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 13-DEC-16:10 | 11.45 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 15.73 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.23 | 04-JAN-13:00 | 91.39 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.50 | 28-FEB-14:00 | 53.72 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.55 | 21-MAR-13:00 | 35.07 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.36 | 01-APR-14:00 | 15.88 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 06-MAY-13:00 | 35.05 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.62 | 16-JUN-13:00 | 18.34 | 27-JUN-05:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.69 | 28-JUL-13:00 | 18.35 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.91 | 10-AUG-14:00 | 18.38 | 23-AUG-19:56 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.23 | 12-SEP-14:00 | 19.96 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.23 | 04-OCT-14:00 | 26.60 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.77 | 18-NOV-13:00 | 68.89 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.79 | 07-DEC-15:00 | 103.61 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 153.69 | 15.88 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 103.61 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.44 | 04-JAN-13:00 | 91.39 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.47 | 28-FEB-14:00 | 53.72 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.55 | 21-MAR-13:00 | 35.07 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.36 | 01-APR-14:00 | 18.11 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 06-MAY-13:00 | 35.05 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 13-JUN-14:00 | 18.34 | 27-JUN-05:23 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 | 28-JUL-13:00 | 18.35 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.81 | 10-AUG-14:00 | 19.46 | 20-AUG-11:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.05 | 12-SEP-14:00 | 19.96 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.11 | 04-OCT-14:00 | 26.61 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.77 | 18-NOV-13:00 | 68.90 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.32 | 07-DEC-15:00 | 103.61 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 | 18.11 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 103.61 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 143.79 | 04-JAN-13:00 | 77.11 | 24-JAN-09:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 156.57 | 26-FEB-14:00 | 57.32 | 21-FEB-10:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 174.72 | 21-MAR-13:00 | 27.92 | 03-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 162.49 | 01-APR-14:00 | 17.86 | 14-APR-15:58 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 191.43 | 06-MAY-13:00 | 31.32 | 10-MAY-20:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 169.77 | 13-JUN-14:00 | 16.38 | 27-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 130.74 | 15-JUL-16:00 | 16.38 | 19-JUL-18:58 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 142.24 | 22-AUG-15:00 | 31.23 | 20-AUG-11:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 142.23 | 12-SEP-14:00 | 16.34 | 15-SEP-23:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 128.41 | 04-OCT-14:00 | 16.59 | 23-OCT-05:50 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 146.52 | 18-NOV-13:00 | 50.23 | 25-NOV-06:30 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 128.16 | 08-DEC-14:00 | 88.27 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 128.16 | 16.34 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 191.43 | 88.27 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.52 | 04-JAN-13:00 | 56.86 | 23-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.14 | 28-FEB-14:00 | 46.07 | 21-FEB-10:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.22 | 21-MAR-13:00 | 14.70 | 03-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 | 01-APR-14:00 | 5.25 | 14-APR-15:52 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 | 06-MAY-13:00 | 30.73 | 10-MAY-19:58 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | 13-JUN-14:00 | 11.58 | 20-JUN-24:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.78 | 28-JUL-13:00 | 12.64 | 19-JUL-18:52 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.41 | 22-AUG-15:00 | 11.24 | 23-AUG-19:52 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.77 | 12-SEP-14:00 | 3.34 | 15-SEP-21:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.32 | 04-OCT-14:00 | 1.30 | 09-OCT-18:53 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.19 | 18-NOV-13:00 | 41.45 | 25-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | 08-DEC-14:00 | 64.78 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | 1.30 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 | 64.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20936.39 | 06-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20941.02 | 24-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20794.32 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20899.13 | 28-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21210.32 | 08-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22310.94 | 15-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21182.81 | 28-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21206.94 | 15-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21143.93 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20862.72 | 05-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21042.06 | 22-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21078.39 | 08-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20794.32 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22310.94 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3836.53 | 05-JAN-15:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 | 0.00 |
February | 3504.56 | 03-FEB-16:03 | 3898.44 | 995.99 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 | 0.00 |
March | 3190.14 | 20-MAR-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 0.00 |
April | 3054.23 | 01-APR-18:03 | 4678.13 | 2788.77 | 3464.10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
May | 3330.52 | 05-MAY-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | 0.00 |
June | 3353.11 | 12-JUN-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 81.80 | 0.00 |
July | 2965.46 | 14-JUL-19:30 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 | 0.00 |
August | 2951.34 | 14-AUG-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.00 |
September | 3195.71 | 13-SEP-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 | 0.00 |
October | 3064.60 | 04-OCT-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 0.00 |
November | 3434.29 | 19-NOV-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 95.36 | 0.00 |
December | 3803.75 | 08-DEC-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2951.34 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 0.00 | |
Maximum of Months | 3836.53 | 4678.13 | 2788.77 | 3464.10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2328.32 | 31-JAN-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
February | 2444.77 | 22-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 | 0.00 |
March | 2477.53 | 29-MAR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 0.00 |
April | 2522.38 | 27-APR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
May | 2651.05 | 05-MAY-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 0.00 |
June | 2754.02 | 13-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
July | 2456.14 | 14-JUL-20:50 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 |
August | 2423.91 | 14-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
September | 2580.00 | 13-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 0.00 |
October | 2320.05 | 04-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 0.00 |
November | 2296.53 | 03-NOV-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 |
December | 2264.08 | 07-DEC-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2264.08 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 2754.02 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2014.99 | 05-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 | 0.00 |
February | 2033.37 | 22-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 0.00 |
March | 2237.07 | 29-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 0.00 |
April | 2808.22 | 30-APR-19:20 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 0.00 |
May | 3271.96 | 05-MAY-19:30 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 0.00 |
June | 3765.89 | 13-JUN-19:30 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 | 0.00 |
July | 3154.38 | 14-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 | 0.00 |
August | 2814.50 | 01-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 0.00 |
September | 2403.87 | 08-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 0.00 |
October | 2041.27 | 04-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.01 | 0.00 |
November | 2025.56 | 21-NOV-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 | 0.00 |
December | 2008.03 | 08-DEC-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2008.03 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 | 0.00 | |
Maximum of Months | 3765.89 | 254.59 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1078.80 | 05-JAN-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 0.00 |
February | 1087.53 | 22-FEB-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 0.00 |
March | 1109.87 | 29-MAR-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
April | 1326.60 | 30-APR-19:20 | 146.88 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 0.00 |
May | 1580.69 | 06-MAY-19:00 | 146.88 | 195.87 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 0.00 |
June | 1814.70 | 13-JUN-19:30 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
July | 1467.13 | 14-JUL-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 0.00 |
August | 1303.65 | 01-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
September | 1122.43 | 07-SEP-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 30.52 | 0.00 |
October | 1091.00 | 04-OCT-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
November | 1084.21 | 21-NOV-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 0.00 |
December | 1078.03 | 08-DEC-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1078.03 | 146.88 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 0.00 | |
Maximum of Months | 1814.70 | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35723.84 | 04-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 40.43 | 0.00 |
February | 35953.58 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 50.61 | 0.00 |
March | 36314.04 | 29-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.55 | 0.00 |
April | 36591.18 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.55 | 0.00 |
May | 36984.73 | 05-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 85.50 | 0.00 |
June | 36936.63 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 99.65 | 0.00 |
July | 36435.79 | 14-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 78.61 | 0.00 |
August | 36307.77 | 01-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.52 | 0.00 |
September | 36238.56 | 06-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 64.71 | 0.00 |
October | 35887.29 | 04-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.58 | 0.00 |
November | 35616.85 | 22-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
December | 35620.09 | 08-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35616.85 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 | |
Maximum of Months | 36984.73 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 99.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12898.11 | 05-JAN-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.28 | 0.00 |
February | 12569.15 | 22-FEB-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.29 | 0.00 |
March | 12409.09 | 13-MAR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 103.05 | 0.00 |
April | 12106.83 | 19-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.41 | 0.00 |
May | 12602.51 | 05-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 127.56 | 0.00 |
June | 12532.65 | 13-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.58 | 0.00 |
July | 11689.76 | 26-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 | 0.00 |
August | 11984.51 | 14-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 125.86 | 0.00 |
September | 12228.35 | 13-SEP-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 | 0.00 |
October | 12268.46 | 16-OCT-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 | 0.00 |
November | 12475.96 | 21-NOV-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 | 0.00 |
December | 12983.29 | 08-DEC-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 100.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11689.76 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.28 | 0.00 | |
Maximum of Months | 12983.29 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42050.14 | 05-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 0.00 |
February | 41792.64 | 22-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 220.64 | 0.00 |
March | 41688.78 | 29-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 294.60 | 0.00 |
April | 42981.75 | 28-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 322.68 | 0.00 |
May | 45903.99 | 05-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 364.25 | 0.00 |
June | 47857.02 | 13-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 361.43 | 0.00 |
July | 43872.55 | 14-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 308.22 | 0.00 |
August | 42862.46 | 01-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 352.14 | 0.00 |
September | 41749.12 | 13-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 386.67 | 0.00 |
October | 40657.71 | 04-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 | 0.00 |
November | 41139.44 | 21-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 243.95 | 0.00 |
December | 41986.06 | 08-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 286.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40657.71 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 0.00 | |
Maximum of Months | 47857.02 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 386.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2965.83 | 30-JAN-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 | 0.00 |
February | 2965.49 | 04-FEB-19:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 0.00 |
March | 2980.61 | 24-MAR-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 | 0.00 |
April | 2973.30 | 21-APR-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | 0.00 |
May | 2999.96 | 08-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 | 0.00 |
June | 3007.30 | 13-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 59.97 | 0.00 |
July | 2974.14 | 20-JUL-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 66.63 | 0.00 |
August | 3000.06 | 10-AUG-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 0.00 |
September | 2991.47 | 04-SEP-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 0.00 |
October | 2981.68 | 20-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 | 0.00 |
November | 2973.69 | 13-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 | 0.00 |
December | 2927.90 | 04-DEC-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2927.90 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 | 0.00 | |
Maximum of Months | 3007.30 | 831.60 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 66.63 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2988.56 | 29-JAN-19:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 0.00 |
February | 2983.29 | 07-FEB-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 0.00 |
March | 2992.65 | 31-MAR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 0.00 |
April | 2999.56 | 08-APR-18:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
May | 3033.52 | 26-MAY-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 67.82 | 0.00 |
June | 3032.94 | 16-JUN-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 53.36 | 0.00 |
July | 3011.12 | 26-JUL-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 0.00 |
August | 3024.74 | 11-AUG-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.20 | 0.00 |
September | 3027.47 | 04-SEP-15:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 62.72 | 0.00 |
October | 3008.26 | 16-OCT-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 0.00 |
November | 2984.15 | 15-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 0.00 |
December | 2985.00 | 12-DEC-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2983.29 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 0.00 | |
Maximum of Months | 3033.52 | 831.60 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.82 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 510.40 | 05-JAN-14:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
February | 455.19 | 04-FEB-14:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 | 0.00 |
March | 370.82 | 11-MAR-09:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
April | 353.99 | 01-APR-20:20 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
May | 369.08 | 06-MAY-08:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 | 0.00 |
June | 355.90 | 13-JUN-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
July | 334.25 | 15-JUL-20:10 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
August | 330.99 | 14-AUG-20:50 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
September | 345.12 | 27-SEP-20:30 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 |
October | 392.00 | 29-OCT-08:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 |
November | 465.75 | 23-NOV-09:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 | 0.00 |
December | 510.68 | 07-DEC-13:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 330.99 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 | |
Maximum of Months | 510.68 | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1166.75 | 04-JAN-09:01 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 0.00 |
February | 1159.96 | 22-FEB-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 0.00 |
March | 1169.46 | 31-MAR-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 0.00 |
April | 1171.76 | 24-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 |
May | 1171.38 | 14-MAY-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 1175.20 | 19-JUN-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 0.00 |
July | 1169.62 | 12-JUL-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
August | 1157.83 | 01-AUG-08:62 | 216.00 | 295.21 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 11.91 | 0.00 |
September | 1169.34 | 12-SEP-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 | 0.00 |
October | 1164.05 | 17-OCT-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 0.00 |
November | 1169.57 | 15-NOV-09:01 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
December | 1164.40 | 19-DEC-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1157.83 | 216.00 | 295.21 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 | |
Maximum of Months | 1175.20 | 831.60 | 670.94 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2689.16 | 31-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | 0.00 |
February | 2715.46 | 27-FEB-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
March | 2713.69 | 21-MAR-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 | 0.00 |
April | 2694.49 | 22-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 | 0.00 |
May | 2705.76 | 05-MAY-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 | 0.00 |
June | 2709.42 | 19-JUN-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 0.00 |
July | 2694.49 | 09-JUL-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 60.12 | 0.00 |
August | 2709.34 | 28-AUG-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 60.26 | 0.00 |
September | 2671.09 | 02-SEP-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 | 0.00 |
October | 2705.76 | 16-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 0.00 |
November | 2700.32 | 22-NOV-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.75 | 0.00 |
December | 2750.69 | 27-DEC-09:01 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2671.09 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 | |
Maximum of Months | 2750.69 | 831.60 | 949.89 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2682.68 | 30-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 | 0.00 |
February | 2877.10 | 24-FEB-09:11 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
March | 2728.61 | 09-MAR-09:01 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 49.51 | 0.00 |
April | 2716.33 | 10-APR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 66.59 | 0.00 |
May | 2733.81 | 05-MAY-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 61.91 | 0.00 |
June | 2732.54 | 18-JUN-18:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 0.00 |
July | 2710.32 | 08-JUL-15:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 | 0.00 |
August | 2726.97 | 28-AUG-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 60.28 | 0.00 |
September | 2699.44 | 13-SEP-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 0.00 |
October | 2705.40 | 08-OCT-15:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 56.43 | 0.00 |
November | 2693.57 | 24-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | 0.00 |
December | 2693.76 | 27-DEC-09:01 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2682.68 | 216.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 | |
Maximum of Months | 2877.10 | 702.00 | 1067.17 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2685.06 | 31-JAN-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 0.00 |
February | 2709.19 | 24-FEB-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
March | 2690.52 | 29-MAR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 | 0.00 |
April | 2694.06 | 28-APR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 | 0.00 |
May | 2775.19 | 06-MAY-21:10 | 1760.39 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 | 0.00 |
June | 3192.11 | 13-JUN-20:10 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 | 0.00 |
July | 2657.53 | 27-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 0.00 |
August | 2677.40 | 14-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 | 0.00 |
September | 2657.29 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 0.00 |
October | 2641.25 | 04-OCT-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 0.00 |
November | 2690.80 | 22-NOV-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 |
December | 2711.17 | 08-DEC-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2641.25 | 1760.39 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 | |
Maximum of Months | 3192.11 | 2263.36 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3241.57 | 04-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 0.00 |
February | 3233.49 | 04-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 0.00 |
March | 3242.83 | 09-MAR-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 0.00 |
April | 3231.77 | 02-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 77.18 | 0.00 |
May | 3242.15 | 06-MAY-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 0.00 |
June | 3218.32 | 22-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
July | 3218.25 | 03-JUL-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 | 0.00 |
August | 3245.98 | 08-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 | 0.00 |
September | 3228.33 | 20-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 40.58 | 0.00 |
October | 3219.60 | 12-OCT-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 | 0.00 |
November | 3200.99 | 03-NOV-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 | 0.00 |
December | 3208.14 | 13-DEC-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3200.99 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 | 0.00 | |
Maximum of Months | 3245.98 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3218.77 | 17-JAN-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 0.00 |
February | 3232.23 | 17-FEB-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.81 | 0.00 |
March | 3252.79 | 23-MAR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 0.00 |
April | 3229.08 | 18-APR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 | 0.00 |
May | 3285.11 | 31-MAY-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 | 0.00 |
June | 3318.92 | 13-JUN-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 | 0.00 |
July | 3233.73 | 27-JUL-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 | 0.00 |
August | 3260.71 | 08-AUG-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 | 0.00 |
September | 3239.35 | 24-SEP-18:02 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 | 0.00 |
October | 3260.12 | 18-OCT-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 | 0.00 |
November | 3249.45 | 03-NOV-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 0.00 |
December | 3224.02 | 11-DEC-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3218.77 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 0.00 | |
Maximum of Months | 3318.92 | 831.60 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1573.38 | 12-JAN-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 |
February | 1575.20 | 13-FEB-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 | 0.00 |
March | 1557.11 | 09-MAR-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 0.00 |
April | 1549.98 | 26-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 0.00 |
May | 1555.27 | 06-MAY-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 | 0.00 |
June | 1553.05 | 21-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 |
July | 1550.75 | 15-JUL-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 | 0.00 |
August | 1553.63 | 08-AUG-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | 0.00 |
September | 1551.61 | 01-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 | 0.00 |
October | 1537.01 | 18-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 | 0.00 |
November | 1577.74 | 19-NOV-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 0.00 |
December | 1578.42 | 30-DEC-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1537.01 | 324.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 | |
Maximum of Months | 1578.42 | 831.60 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23103.08 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 |
February | 23180.01 | 15-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 | 0.00 |
March | 23803.66 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
April | 24242.94 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 | 0.00 |
May | 24905.24 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 | 0.00 |
June | 25466.60 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
July | 24800.53 | 14-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 | 0.00 |
August | 24335.99 | 01-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.44 | 0.00 |
September | 23915.16 | 05-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
October | 23341.69 | 16-OCT-21:30 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 0.00 |
November | 23093.69 | 14-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 0.00 |
December | 23180.51 | 08-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23093.69 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 | |
Maximum of Months | 25466.60 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24319.85 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 |
February | 24346.82 | 15-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 | 0.00 |
March | 25011.19 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
April | 25468.23 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 | 0.00 |
May | 26125.85 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 | 0.00 |
June | 26699.10 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
July | 26079.96 | 14-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 | 0.00 |
August | 25612.72 | 01-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.43 | 0.00 |
September | 25160.21 | 05-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
October | 24566.99 | 16-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 0.00 |
November | 24345.88 | 14-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 0.00 |
December | 24339.79 | 08-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24319.85 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 0.00 | |
Maximum of Months | 26699.10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29659.61 | 04-JAN-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 128.60 | 0.00 |
February | 29846.00 | 20-FEB-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 105.25 | 0.00 |
March | 30171.85 | 19-MAR-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 133.85 | 0.00 |
April | 30466.99 | 09-APR-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 131.43 | 0.00 |
May | 30646.65 | 07-MAY-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 128.04 | 0.00 |
June | 30491.46 | 24-JUN-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 116.82 | 0.00 |
July | 29892.83 | 15-JUL-18:03 | 9606.82 | 4950.44 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 113.24 | 0.00 |
August | 30142.44 | 27-AUG-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 124.69 | 0.00 |
September | 30246.84 | 03-SEP-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 111.56 | 0.00 |
October | 30039.88 | 07-OCT-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 106.64 | 0.00 |
November | 29786.84 | 23-NOV-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.80 | 0.00 |
December | 29723.71 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 100.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29659.61 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.80 | 0.00 | |
Maximum of Months | 30646.65 | 9606.82 | 4950.44 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 133.85 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6911.23 | 05-JAN-16:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.83 | 0.00 |
February | 6754.14 | 22-FEB-16:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 0.00 |
March | 6733.08 | 28-MAR-15:13 | 3992.40 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.98 | 0.00 |
April | 6608.12 | 01-APR-14:40 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.29 | 0.00 |
May | 7307.07 | 06-MAY-14:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 0.00 |
June | 7505.27 | 13-JUN-15:40 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.38 | 0.00 |
July | 6447.16 | 15-JUL-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | 0.00 |
August | 6262.54 | 14-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 | 0.00 |
September | 6026.48 | 06-SEP-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.93 | 0.00 |
October | 5705.44 | 07-OCT-14:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.11 | 0.00 |
November | 6313.45 | 22-NOV-14:00 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.92 | 0.00 |
December | 6809.20 | 08-DEC-14:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5705.44 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 | 0.00 | |
Maximum of Months | 7505.27 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.733264E+12 | 406634.80 | 09-JAN-20:10 | 0.362676E+12 | 313080.40 | 04-JAN-18:10 |
February | 0.676396E+12 | 415890.05 | 14-FEB-20:10 | 0.326624E+12 | 312794.62 | 07-FEB-18:40 |
March | 0.765366E+12 | 422974.44 | 28-MAR-19:10 | 0.359996E+12 | 312429.47 | 02-MAR-18:30 |
April | 0.783184E+12 | 456515.59 | 30-APR-19:10 | 0.345618E+12 | 311650.40 | 03-APR-17:30 |
May | 0.839910E+12 | 462394.42 | 16-MAY-19:10 | 0.355023E+12 | 310813.99 | 02-MAY-17:19 |
June | 0.818831E+12 | 472906.68 | 12-JUN-19:10 | 0.341744E+12 | 309985.90 | 07-JUN-17:10 |
July | 0.767258E+12 | 435350.14 | 14-JUL-19:10 | 0.352631E+12 | 309639.70 | 11-JUL-17:10 |
August | 0.801266E+12 | 455984.41 | 14-AUG-19:00 | 0.354000E+12 | 310082.11 | 25-AUG-17:10 |
September | 0.769515E+12 | 443116.85 | 13-SEP-19:00 | 0.343936E+12 | 310943.60 | 29-SEP-17:19 |
October | 0.774502E+12 | 428137.33 | 16-OCT-19:10 | 0.358245E+12 | 311690.89 | 26-OCT-17:30 |
November | 0.736720E+12 | 428578.08 | 17-NOV-19:10 | 0.348904E+12 | 312538.05 | 30-NOV-18:30 |
December | 0.741771E+12 | 419012.61 | 29-DEC-19:10 | 0.362160E+12 | 312928.96 | 28-DEC-18:40 |
Annual Sum or Average | 0.920798E+13 | 0.421156E+13 | ||||
Minimum of Months | 0.676396E+12 | 406634.80 | 0.326624E+12 | 309639.70 | ||
Maximum of Months | 0.839910E+12 | 472906.68 | 0.362676E+12 | 313080.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.666157E+11 | 0.172936E+11 | 0.140828E+12 | 0.544236E+11 | 0.418526E+11 | 0.119128E+11 | 0.00 | 0.361817E+12 | 0.00 | 0.00 | 0.255123E+11 | 0.770531E+10 | 0.00 |
February | 0.601289E+11 | 0.153762E+11 | 0.127191E+12 | 0.491569E+11 | 0.385914E+11 | 0.108085E+11 | 0.00 | 0.340158E+12 | 0.00 | 0.00 | 0.232326E+11 | 0.696275E+10 | 0.00 |
March | 0.664572E+11 | 0.165014E+11 | 0.140882E+12 | 0.544261E+11 | 0.428182E+11 | 0.120921E+11 | 0.00 | 0.393406E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.770394E+10 | 0.00 |
April | 0.642051E+11 | 0.155909E+11 | 0.136245E+12 | 0.526676E+11 | 0.418779E+11 | 0.121150E+11 | 0.00 | 0.422947E+12 | 0.00 | 0.00 | 0.249400E+11 | 0.746569E+10 | 0.00 |
May | 0.663914E+11 | 0.158352E+11 | 0.140860E+12 | 0.544248E+11 | 0.438139E+11 | 0.129336E+11 | 0.00 | 0.466877E+12 | 0.00 | 0.00 | 0.257581E+11 | 0.770531E+10 | 0.00 |
June | 0.641454E+11 | 0.151467E+11 | 0.136336E+12 | 0.526700E+11 | 0.438497E+11 | 0.126077E+11 | 0.00 | 0.456547E+12 | 0.00 | 0.00 | 0.249275E+11 | 0.745752E+10 | 0.00 |
July | 0.663642E+11 | 0.157759E+11 | 0.140770E+12 | 0.544223E+11 | 0.422807E+11 | 0.122583E+11 | 0.00 | 0.396650E+12 | 0.00 | 0.00 | 0.257415E+11 | 0.771345E+10 | 0.00 |
August | 0.663715E+11 | 0.159758E+11 | 0.140892E+12 | 0.544261E+11 | 0.416759E+11 | 0.126451E+11 | 0.00 | 0.430521E+12 | 0.00 | 0.00 | 0.257457E+11 | 0.770525E+10 | 0.00 |
September | 0.643972E+11 | 0.158574E+11 | 0.136256E+12 | 0.526678E+11 | 0.403790E+11 | 0.121347E+11 | 0.00 | 0.410291E+12 | 0.00 | 0.00 | 0.249244E+11 | 0.746720E+10 | 0.00 |
October | 0.665886E+11 | 0.168124E+11 | 0.140818E+12 | 0.544235E+11 | 0.409286E+11 | 0.123789E+11 | 0.00 | 0.403793E+12 | 0.00 | 0.00 | 0.257504E+11 | 0.770400E+10 | 0.00 |
November | 0.644575E+11 | 0.165977E+11 | 0.136330E+12 | 0.526687E+11 | 0.400736E+11 | 0.118442E+11 | 0.00 | 0.377315E+12 | 0.00 | 0.00 | 0.248591E+11 | 0.744988E+10 | 0.00 |
December | 0.666006E+11 | 0.174046E+11 | 0.140770E+12 | 0.544224E+11 | 0.413457E+11 | 0.120714E+11 | 0.00 | 0.370627E+12 | 0.00 | 0.00 | 0.255133E+11 | 0.771344E+10 | 0.00 |
Annual Sum or Average | 0.782723E+12 | 0.194168E+12 | 0.165818E+13 | 0.640800E+12 | 0.499487E+12 | 0.145802E+12 | 0.00 | 0.483095E+13 | 0.00 | 0.00 | 0.302676E+12 | 0.907537E+11 | 0.00 |
Minimum of Months | 0.601289E+11 | 0.151467E+11 | 0.127191E+12 | 0.491569E+11 | 0.385914E+11 | 0.108085E+11 | 0.00 | 0.340158E+12 | 0.00 | 0.00 | 0.232326E+11 | 0.696275E+10 | 0.00 |
Maximum of Months | 0.666157E+11 | 0.174046E+11 | 0.140892E+12 | 0.544261E+11 | 0.438497E+11 | 0.129336E+11 | 0.00 | 0.466877E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.771345E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.236744E+10 | 0.00 | 0.208390E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.183710E+10 | 0.00 | 0.187583E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.203879E+10 | 0.00 | 0.205934E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.177480E+10 | 0.00 | 0.196888E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.197577E+10 | 0.00 | 0.201069E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.169362E+10 | 0.00 | 0.192937E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.205117E+10 | 0.00 | 0.198759E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.239299E+10 | 0.00 | 0.199568E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.206657E+10 | 0.00 | 0.194898E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.250019E+10 | 0.00 | 0.203842E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.225273E+10 | 0.00 | 0.199560E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.243349E+10 | 0.00 | 0.207906E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.253847E+11 | 0.00 | 0.239733E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.169362E+10 | 0.00 | 0.187583E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.250019E+10 | 0.00 | 0.208390E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39168.47 | 02-JAN-07:19 | 24026.12 | 05-JAN-19:19 | 4971.00 | 10-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39168.28 | 06-FEB-07:19 | 24029.34 | 22-FEB-21:10 | 5027.74 | 14-FEB-19:19 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 24354.26 | 29-MAR-20:10 | 5245.24 | 14-MAR-21:30 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.68 | 21-APR-06:19 | 25114.01 | 27-APR-20:10 | 5520.39 | 10-APR-18:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.28 | 09-MAY-06:19 | 27422.97 | 05-MAY-18:30 | 5789.67 | 31-MAY-20:19 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39169.68 | 20-JUN-06:19 | 29183.16 | 12-JUN-18:30 | 5758.51 | 13-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:10 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39169.68 | 11-JUL-06:19 | 25654.85 | 14-JUL-20:10 | 5622.16 | 17-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.68 | 21-AUG-06:19 | 25014.50 | 14-AUG-20:10 | 5635.04 | 14-AUG-19:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.68 | 21-SEP-06:19 | 24461.96 | 13-SEP-20:10 | 5385.64 | 08-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 23-OCT-06:19 | 23563.80 | 04-OCT-20:10 | 5183.95 | 17-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.57 | 03-NOV-06:19 | 23242.33 | 21-NOV-21:10 | 5339.25 | 30-NOV-22:00 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39168.07 | 11-DEC-07:19 | 23840.37 | 08-DEC-21:10 | 5191.89 | 21-DEC-21:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.07 | 23242.33 | 4971.00 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 29183.16 | 5789.67 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 190631.54 | 04-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.66 | 11-JAN-19:10 | 0.00 |
February | 208938.53 | 13-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.65 | 01-FEB-19:10 | 0.00 |
March | 210542.95 | 28-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.72 | 10-MAR-19:10 | 0.00 |
April | 229444.75 | 02-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.58 | 20-APR-18:10 | 0.00 |
May | 249434.12 | 06-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.63 | 24-MAY-18:10 | 0.00 |
June | 263115.23 | 13-JUN-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.67 | 23-JUN-18:10 | 0.00 |
July | 212089.28 | 20-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.74 | 21-JUL-18:10 | 0.00 |
August | 235284.73 | 13-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.75 | 23-AUG-18:10 | 0.00 |
September | 218963.70 | 12-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.70 | 15-SEP-18:10 | 0.00 |
October | 213774.33 | 16-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.63 | 18-OCT-18:10 | 0.00 |
November | 206124.95 | 17-NOV-19:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.71 | 01-NOV-18:10 | 0.00 |
December | 196630.19 | 29-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.72 | 13-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 190631.54 | 0.00 | 0.00 | 9938.94 | 4738.58 | 0.00 | |||
Maximum of Months | 263115.23 | 0.00 | 0.00 | 9938.94 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 406634.80 | 09-JAN-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21140.23 | 4950.65 | 0.00 | 169404.46 | 0.00 |
February | 415890.05 | 14-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22508.54 | 4976.39 | 0.00 | 178088.29 | 0.00 |
March | 422974.44 | 28-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23561.65 | 5096.64 | 0.00 | 184019.92 | 0.00 |
April | 456515.59 | 30-APR-19:10 | 59807.00 | 84978.71 | 12338.45 | 31511.55 | 23504.43 | 5289.70 | 0.00 | 223775.70 | 0.00 |
May | 462394.42 | 16-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22568.44 | 5620.62 | 0.00 | 223611.73 | 0.00 |
June | 472906.68 | 12-JUN-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 28957.51 | 5615.72 | 0.00 | 227334.04 | 0.00 |
July | 435350.14 | 14-JUL-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 25110.83 | 5139.57 | 0.00 | 194442.26 | 0.00 |
August | 455984.41 | 14-AUG-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 24351.83 | 5635.04 | 0.00 | 215007.76 | 0.00 |
September | 443116.85 | 13-SEP-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 23815.01 | 5277.89 | 0.00 | 203196.43 | 0.00 |
October | 428137.33 | 16-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22835.42 | 5161.39 | 0.00 | 188997.54 | 0.00 |
November | 428578.08 | 17-NOV-19:10 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 22111.84 | 5102.36 | 0.00 | 206124.95 | 0.00 |
December | 419012.61 | 29-DEC-19:10 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 22298.68 | 5023.22 | 0.00 | 196630.19 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 406634.80 | 57474.69 | 77573.37 | 12338.45 | 31344.35 | 21140.23 | 4950.65 | 0.00 | 169404.46 | 0.00 | |
Maximum of Months | 472906.68 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 28957.51 | 5635.04 | 0.00 | 227334.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 8726.86 | 02-JAN-04:49 | 0.00 | 209146.51 | 09-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 7900.75 | 11-FEB-05:00 | 0.00 | 209025.17 | 03-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 9125.22 | 04-MAR-05:00 | 0.00 | 208592.68 | 03-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 8923.35 | 10-APR-03:00 | 0.00 | 207648.45 | 05-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 8680.13 | 26-MAY-03:00 | 0.00 | 206921.28 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 8101.95 | 05-JUN-03:49 | 0.00 | 206106.32 | 02-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 8795.96 | 01-JUL-04:00 | 0.00 | 205678.82 | 05-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 9981.85 | 21-AUG-01:19 | 0.00 | 206195.04 | 29-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 9681.34 | 16-SEP-04:00 | 0.00 | 206910.67 | 26-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 10022.41 | 23-OCT-01:19 | 0.00 | 207720.54 | 30-OCT-20:10 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 9239.96 | 27-NOV-04:49 | 0.00 | 208687.01 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 8747.42 | 21-DEC-04:00 | 0.00 | 209107.49 | 26-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 7900.75 | 0.00 | 205678.82 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 10022.41 | 0.00 | 209146.51 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 21.74 | 2.33 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 21.72 | 3.33 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.70 | 3.83 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.00 | 0.50 | 22.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 21.75 | 7.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.00 | 3.83 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.00 | 2.17 | 22.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.10 | 1.33 | 22.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.88 | 0.67 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.94 | 1.67 | 21.94 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 21.91 | 8.83 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.10 | 2.17 | 22.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.72 | 2.50 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.74 | 1.67 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.73 | 3.67 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.72 | 3.33 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.71 | 1.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.69 | 1.83 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
Annual Sum or Average | 0.00 | 0.00 | 18.00 | 21.72 | 18.00 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.74 | 3.67 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.73 | 3.50 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.72 | 3.17 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.71 | 1.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 21.73 | 15.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.82 | 3.50 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.88 | 7.50 | 21.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.86 | 5.67 | 21.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.81 | 5.00 | 21.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.71 | 1.50 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.81 | 3.67 | 21.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.89 | 6.33 | 21.89 |
Annual Sum or Average | 0.00 | 0.00 | 34.50 | 21.83 | 34.50 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.89 | 7.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 598.00 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
February | 453.83 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
March | 605.50 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
April | 557.83 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
May | 438.33 | 23.11 | 1.00 | 23.12 | 0.00 | 23.12 |
June | 235.00 | 23.16 | 28.50 | 23.25 | 0.00 | 23.25 |
July | 350.33 | 23.13 | 0.33 | 23.13 | 0.00 | 23.13 |
August | 460.33 | 23.07 | 0.67 | 23.07 | 0.00 | 23.07 |
September | 444.00 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
October | 640.83 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
November | 544.33 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
December | 555.50 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 5883.83 | 23.08 | 30.50 | 23.08 | 0.00 | 23.08 |
Minimum of Months | 235.00 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
Maximum of Months | 640.83 | 23.16 | 28.50 | 23.25 | 0.00 | 23.25 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 135.17 | 22.47 | 516.67 | 23.58 | 0.00 | 23.58 |
February | 51.17 | 22.65 | 520.67 | 23.77 | 0.00 | 23.77 |
March | 53.17 | 22.55 | 558.17 | 23.72 | 0.00 | 23.72 |
April | 61.83 | 22.34 | 552.33 | 23.61 | 0.00 | 23.61 |
May | 122.50 | 22.38 | 524.33 | 23.50 | 0.00 | 23.50 |
June | 77.33 | 22.55 | 551.67 | 23.61 | 0.00 | 23.61 |
July | 158.50 | 22.48 | 411.33 | 23.34 | 0.00 | 23.34 |
August | 221.83 | 22.24 | 370.00 | 23.15 | 0.00 | 23.15 |
September | 153.67 | 22.33 | 430.17 | 23.37 | 0.00 | 23.37 |
October | 211.00 | 22.29 | 408.17 | 23.26 | 0.00 | 23.26 |
November | 131.17 | 22.38 | 473.67 | 23.50 | 0.00 | 23.50 |
December | 145.17 | 22.42 | 490.50 | 23.54 | 0.00 | 23.54 |
Annual Sum or Average | 1522.50 | 22.39 | 5807.67 | 23.50 | 0.00 | 23.50 |
Minimum of Months | 51.17 | 22.24 | 370.00 | 23.15 | 0.00 | 23.15 |
Maximum of Months | 221.83 | 22.65 | 558.17 | 23.77 | 0.00 | 23.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 379.67 | 22.64 | 165.67 | 22.99 | 0.00 | 22.99 |
February | 213.17 | 22.79 | 224.33 | 23.30 | 0.00 | 23.30 |
March | 230.17 | 22.74 | 288.00 | 23.32 | 0.00 | 23.32 |
April | 205.33 | 22.71 | 303.00 | 23.34 | 0.00 | 23.34 |
May | 244.83 | 22.64 | 280.00 | 23.24 | 0.00 | 23.24 |
June | 170.83 | 22.70 | 327.33 | 23.42 | 0.00 | 23.42 |
July | 338.83 | 22.66 | 185.00 | 23.05 | 0.00 | 23.05 |
August | 371.33 | 22.50 | 188.83 | 22.93 | 0.00 | 22.93 |
September | 330.33 | 22.59 | 196.50 | 23.02 | 0.00 | 23.02 |
October | 439.67 | 22.54 | 118.17 | 22.79 | 0.00 | 22.79 |
November | 383.50 | 22.63 | 133.83 | 22.92 | 0.00 | 22.92 |
December | 414.00 | 22.65 | 139.50 | 22.93 | 0.00 | 22.93 |
Annual Sum or Average | 3721.67 | 22.63 | 2550.17 | 23.10 | 0.00 | 23.10 |
Minimum of Months | 170.83 | 22.50 | 118.17 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 439.67 | 22.79 | 327.33 | 23.42 | 0.00 | 23.42 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 645.33 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 445.33 | 23.05 | 0.33 | 23.05 | 0.00 | 23.05 |
March | 382.33 | 23.03 | 59.00 | 23.15 | 0.00 | 23.15 |
April | 152.00 | 23.03 | 174.00 | 23.51 | 0.00 | 23.51 |
May | 109.83 | 22.98 | 418.00 | 23.73 | 0.00 | 23.73 |
June | 20.83 | 23.16 | 534.83 | 23.93 | 0.00 | 23.93 |
July | 94.67 | 23.08 | 261.33 | 23.70 | 0.00 | 23.70 |
August | 328.50 | 22.83 | 154.83 | 23.18 | 0.00 | 23.18 |
September | 328.67 | 22.88 | 85.50 | 23.09 | 0.00 | 23.09 |
October | 583.33 | 22.82 | 10.17 | 22.84 | 0.00 | 22.84 |
November | 587.67 | 22.90 | 0.33 | 22.91 | 0.00 | 22.91 |
December | 664.33 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 4342.83 | 22.90 | 1698.33 | 23.19 | 0.00 | 23.19 |
Minimum of Months | 20.83 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 664.33 | 23.16 | 534.83 | 23.93 | 0.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 718.67 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 544.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
March | 500.67 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
April | 234.67 | 23.08 | 80.33 | 23.29 | 0.00 | 23.29 |
May | 153.17 | 23.03 | 329.00 | 23.63 | 0.00 | 23.63 |
June | 41.33 | 23.18 | 467.50 | 23.90 | 0.00 | 23.90 |
July | 153.83 | 23.12 | 151.00 | 23.52 | 0.00 | 23.52 |
August | 400.00 | 22.86 | 95.67 | 23.06 | 0.00 | 23.06 |
September | 430.83 | 22.92 | 16.00 | 22.95 | 0.00 | 22.95 |
October | 663.83 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
November | 662.67 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
December | 723.17 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 5227.00 | 22.92 | 1139.50 | 23.10 | 0.00 | 23.10 |
Minimum of Months | 41.33 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 723.17 | 23.18 | 467.50 | 23.90 | 0.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.67 | 23.96 | 683.33 | 22.51 | 152.67 | 22.73 |
February | 145.17 | 23.94 | 645.17 | 22.52 | 145.17 | 22.74 |
March | 168.00 | 23.92 | 717.67 | 22.54 | 168.00 | 22.76 |
April | 171.33 | 23.90 | 703.17 | 22.56 | 171.33 | 22.78 |
May | 172.17 | 23.91 | 704.00 | 22.58 | 172.17 | 22.80 |
June | 176.50 | 23.88 | 704.83 | 22.58 | 176.50 | 22.80 |
July | 161.50 | 23.93 | 713.17 | 22.49 | 161.50 | 22.71 |
August | 165.17 | 23.86 | 683.17 | 22.53 | 161.00 | 22.75 |
September | 158.50 | 23.91 | 676.83 | 22.51 | 157.33 | 22.74 |
October | 153.17 | 23.93 | 656.00 | 22.52 | 151.50 | 22.75 |
November | 146.50 | 23.97 | 659.00 | 22.51 | 146.50 | 22.74 |
December | 150.67 | 23.97 | 676.50 | 22.50 | 150.67 | 22.72 |
Annual Sum or Average | 1921.33 | 23.92 | 8222.83 | 22.53 | 1914.33 | 22.75 |
Minimum of Months | 145.17 | 23.86 | 645.17 | 22.49 | 145.17 | 22.71 |
Maximum of Months | 176.50 | 23.97 | 717.67 | 22.58 | 176.50 | 22.80 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.67 | 23.45 | 703.33 | 23.78 | 26.83 | 23.79 |
February | 14.67 | 23.96 | 667.17 | 23.82 | 14.67 | 23.82 |
March | 30.00 | 23.41 | 679.83 | 23.73 | 20.83 | 23.74 |
April | 36.83 | 23.31 | 615.00 | 23.64 | 24.00 | 23.65 |
May | 117.00 | 23.18 | 629.17 | 23.59 | 70.67 | 23.62 |
June | 71.33 | 23.49 | 627.17 | 23.64 | 52.67 | 23.66 |
July | 156.50 | 23.16 | 552.83 | 23.54 | 88.33 | 23.58 |
August | 215.83 | 22.99 | 505.83 | 23.46 | 105.33 | 23.51 |
September | 135.00 | 23.16 | 575.50 | 23.54 | 75.50 | 23.58 |
October | 147.33 | 23.11 | 604.50 | 23.54 | 81.50 | 23.57 |
November | 65.00 | 23.41 | 663.83 | 23.70 | 47.33 | 23.72 |
December | 49.00 | 23.44 | 703.00 | 23.76 | 34.67 | 23.77 |
Annual Sum or Average | 1076.17 | 23.21 | 7527.17 | 23.64 | 642.33 | 23.66 |
Minimum of Months | 14.67 | 22.99 | 505.83 | 23.46 | 14.67 | 23.51 |
Maximum of Months | 215.83 | 23.96 | 703.33 | 23.82 | 105.33 | 23.82 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.17 | 22.58 | 388.67 | 23.52 | 0.00 | 23.52 |
February | 13.00 | 22.71 | 426.33 | 23.73 | 0.00 | 23.73 |
March | 82.17 | 22.66 | 434.33 | 23.61 | 0.00 | 23.61 |
April | 82.33 | 22.64 | 439.33 | 23.60 | 0.00 | 23.60 |
May | 79.00 | 22.53 | 501.50 | 23.61 | 0.00 | 23.61 |
June | 39.00 | 22.66 | 547.83 | 23.71 | 0.00 | 23.71 |
July | 117.33 | 22.62 | 446.33 | 23.54 | 0.00 | 23.54 |
August | 196.00 | 22.51 | 381.50 | 23.34 | 0.00 | 23.34 |
September | 151.00 | 22.55 | 384.67 | 23.41 | 0.00 | 23.41 |
October | 203.33 | 22.51 | 341.83 | 23.26 | 0.00 | 23.26 |
November | 111.17 | 22.57 | 381.17 | 23.46 | 0.00 | 23.46 |
December | 93.00 | 22.58 | 397.00 | 23.49 | 0.00 | 23.49 |
Annual Sum or Average | 1259.50 | 22.57 | 5070.50 | 23.52 | 0.00 | 23.52 |
Minimum of Months | 13.00 | 22.51 | 341.83 | 23.26 | 0.00 | 23.26 |
Maximum of Months | 203.33 | 22.71 | 547.83 | 23.73 | 0.00 | 23.73 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 628.50 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
February | 554.83 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
March | 621.67 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 595.83 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 610.50 | 21.40 | 2.33 | 21.41 | 2.17 | 21.41 |
June | 584.83 | 21.38 | 1.50 | 21.39 | 0.00 | 21.39 |
July | 634.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
August | 624.50 | 21.43 | 3.67 | 21.44 | 3.67 | 21.45 |
September | 600.83 | 21.43 | 0.50 | 21.43 | 0.50 | 21.43 |
October | 627.17 | 21.44 | 1.00 | 21.45 | 1.00 | 21.45 |
November | 604.00 | 21.44 | 0.17 | 21.44 | 0.17 | 21.44 |
December | 626.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
Annual Sum or Average | 7312.67 | 21.43 | 9.17 | 21.43 | 7.50 | 21.43 |
Minimum of Months | 554.83 | 21.38 | 0.00 | 21.39 | 0.00 | 21.39 |
Maximum of Months | 634.00 | 21.46 | 3.67 | 21.46 | 3.67 | 21.46 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 648.17 | 21.67 | 20.33 | 21.74 | 19.83 | 21.80 |
February | 564.33 | 21.59 | 7.67 | 21.62 | 4.67 | 21.64 |
March | 633.00 | 21.48 | 1.67 | 21.49 | 1.67 | 21.49 |
April | 593.00 | 21.41 | 0.83 | 21.41 | 0.00 | 21.41 |
May | 601.67 | 21.39 | 5.33 | 21.41 | 3.17 | 21.42 |
June | 568.83 | 21.36 | 13.00 | 21.41 | 4.00 | 21.43 |
July | 621.83 | 21.47 | 4.50 | 21.49 | 3.67 | 21.51 |
August | 621.00 | 21.45 | 8.33 | 21.48 | 8.17 | 21.50 |
September | 602.00 | 21.47 | 8.50 | 21.50 | 8.00 | 21.52 |
October | 637.33 | 21.52 | 11.50 | 21.56 | 11.00 | 21.59 |
November | 610.67 | 21.58 | 15.50 | 21.63 | 13.50 | 21.68 |
December | 641.83 | 21.68 | 24.67 | 21.75 | 24.33 | 21.82 |
Annual Sum or Average | 7343.67 | 21.51 | 121.83 | 21.54 | 102.00 | 21.57 |
Minimum of Months | 564.33 | 21.36 | 0.83 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 648.17 | 21.68 | 24.67 | 21.75 | 24.33 | 21.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.83 | 7.50 | 21.84 | 7.50 | 21.86 |
February | 672.00 | 21.81 | 0.33 | 21.81 | 0.33 | 21.82 |
March | 744.00 | 21.72 | 1.33 | 21.72 | 1.33 | 21.72 |
April | 720.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
May | 743.67 | 21.73 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 720.00 | 21.76 | 2.33 | 21.76 | 2.33 | 21.77 |
July | 743.33 | 21.75 | 2.83 | 21.76 | 2.83 | 21.76 |
August | 744.00 | 21.73 | 6.00 | 21.74 | 6.00 | 21.75 |
September | 720.00 | 21.73 | 8.17 | 21.75 | 8.17 | 21.77 |
October | 743.50 | 21.73 | 8.33 | 21.75 | 8.33 | 21.77 |
November | 719.00 | 21.79 | 8.17 | 21.82 | 8.17 | 21.84 |
December | 744.00 | 21.84 | 11.50 | 21.87 | 11.50 | 21.89 |
Annual Sum or Average | 8757.50 | 21.76 | 56.67 | 21.77 | 56.67 | 21.78 |
Minimum of Months | 672.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
Maximum of Months | 744.00 | 21.84 | 11.50 | 21.87 | 11.50 | 21.89 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 606.67 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
February | 528.33 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
March | 587.83 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
April | 558.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
May | 587.83 | 21.33 | 3.00 | 21.34 | 3.00 | 21.35 |
June | 556.67 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
July | 625.17 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
August | 608.33 | 21.39 | 2.50 | 21.40 | 2.50 | 21.41 |
September | 584.00 | 21.38 | 0.33 | 21.38 | 0.33 | 21.38 |
October | 614.33 | 21.41 | 1.00 | 21.41 | 1.00 | 21.42 |
November | 591.17 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
December | 609.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
Annual Sum or Average | 7057.33 | 21.37 | 6.83 | 21.37 | 6.83 | 21.37 |
Minimum of Months | 528.33 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
Maximum of Months | 625.17 | 21.45 | 3.00 | 21.45 | 3.00 | 21.45 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 619.33 | 21.65 | 33.50 | 21.79 | 20.33 | 21.88 |
February | 521.67 | 21.48 | 21.50 | 21.60 | 6.00 | 21.64 |
March | 599.50 | 21.39 | 2.33 | 21.40 | 1.50 | 21.41 |
April | 554.67 | 21.29 | 0.33 | 21.29 | 0.00 | 21.29 |
May | 579.50 | 21.32 | 5.17 | 21.34 | 4.00 | 21.36 |
June | 543.00 | 21.28 | 5.50 | 21.30 | 2.67 | 21.32 |
July | 604.50 | 21.42 | 5.17 | 21.45 | 4.17 | 21.47 |
August | 603.67 | 21.40 | 7.50 | 21.43 | 7.50 | 21.46 |
September | 584.33 | 21.42 | 8.17 | 21.45 | 8.00 | 21.48 |
October | 627.33 | 21.50 | 11.17 | 21.54 | 10.67 | 21.58 |
November | 597.67 | 21.56 | 18.67 | 21.63 | 13.50 | 21.69 |
December | 620.83 | 21.67 | 35.83 | 21.81 | 23.50 | 21.89 |
Annual Sum or Average | 7056.00 | 21.45 | 154.83 | 21.51 | 101.83 | 21.55 |
Minimum of Months | 521.67 | 21.28 | 0.33 | 21.29 | 0.00 | 21.29 |
Maximum of Months | 627.33 | 21.67 | 35.83 | 21.81 | 23.50 | 21.89 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.17 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
February | 609.33 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
March | 716.67 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
April | 686.50 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
May | 571.33 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
June | 368.33 | 23.23 | 64.67 | 23.34 | 0.00 | 23.34 |
July | 744.00 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
August | 740.00 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
September | 720.00 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
October | 744.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
November | 710.50 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
December | 731.50 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 8074.33 | 23.06 | 64.67 | 23.07 | 0.00 | 23.07 |
Minimum of Months | 368.33 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
Maximum of Months | 744.00 | 23.27 | 64.67 | 23.34 | 0.00 | 23.34 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 589.67 | 21.33 | 53.83 | 21.50 | 0.50 | 21.50 |
February | 526.17 | 21.31 | 62.67 | 21.53 | 0.00 | 21.53 |
March | 583.67 | 21.32 | 59.33 | 21.51 | 0.00 | 21.51 |
April | 562.17 | 21.31 | 58.67 | 21.50 | 0.00 | 21.50 |
May | 583.00 | 21.31 | 55.17 | 21.49 | 1.17 | 21.49 |
June | 560.67 | 21.30 | 60.50 | 21.50 | 0.00 | 21.50 |
July | 597.83 | 21.35 | 7.67 | 21.38 | 0.17 | 21.38 |
August | 598.83 | 21.35 | 41.00 | 21.48 | 5.17 | 21.49 |
September | 572.67 | 21.34 | 38.67 | 21.46 | 1.33 | 21.46 |
October | 595.00 | 21.34 | 38.67 | 21.46 | 3.50 | 21.47 |
November | 574.00 | 21.34 | 39.00 | 21.47 | 1.33 | 21.47 |
December | 593.33 | 21.34 | 54.00 | 21.51 | 1.33 | 21.51 |
Annual Sum or Average | 6937.00 | 21.33 | 569.17 | 21.48 | 14.50 | 21.48 |
Minimum of Months | 526.17 | 21.30 | 7.67 | 21.38 | 0.00 | 21.38 |
Maximum of Months | 598.83 | 21.35 | 62.67 | 21.53 | 5.17 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 21.55 | 47.50 | 21.69 | 37.33 | 21.79 |
February | 532.67 | 21.47 | 55.17 | 21.66 | 15.00 | 21.71 |
March | 592.67 | 21.36 | 50.00 | 21.51 | 2.33 | 21.52 |
April | 559.00 | 21.31 | 61.00 | 21.51 | 0.00 | 21.51 |
May | 576.00 | 21.31 | 65.67 | 21.52 | 2.00 | 21.53 |
June | 550.17 | 21.31 | 83.67 | 21.58 | 5.83 | 21.60 |
July | 590.83 | 21.37 | 25.33 | 21.46 | 7.00 | 21.49 |
August | 592.67 | 21.36 | 47.83 | 21.51 | 8.00 | 21.53 |
September | 571.50 | 21.37 | 45.00 | 21.52 | 9.00 | 21.55 |
October | 600.67 | 21.41 | 37.33 | 21.53 | 14.83 | 21.57 |
November | 581.17 | 21.49 | 38.83 | 21.62 | 19.83 | 21.68 |
December | 609.83 | 21.57 | 50.50 | 21.71 | 46.17 | 21.81 |
Annual Sum or Average | 6967.17 | 21.41 | 607.83 | 21.57 | 167.33 | 21.61 |
Minimum of Months | 532.67 | 21.31 | 25.33 | 21.46 | 0.00 | 21.49 |
Maximum of Months | 610.00 | 21.57 | 83.67 | 21.71 | 46.17 | 21.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 593.17 | 21.36 | 55.17 | 21.53 | 0.00 | 21.53 |
February | 538.50 | 21.37 | 31.17 | 21.48 | 0.00 | 21.48 |
March | 619.50 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
April | 608.33 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
May | 624.83 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
June | 603.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
July | 645.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
August | 641.50 | 21.48 | 1.33 | 21.48 | 1.33 | 21.49 |
September | 606.83 | 21.45 | 2.00 | 21.45 | 2.00 | 21.46 |
October | 620.50 | 21.43 | 4.17 | 21.44 | 2.33 | 21.45 |
November | 583.50 | 21.38 | 26.33 | 21.47 | 0.50 | 21.47 |
December | 590.67 | 21.35 | 59.50 | 21.54 | 0.00 | 21.54 |
Annual Sum or Average | 7275.33 | 21.43 | 179.67 | 21.47 | 6.17 | 21.47 |
Minimum of Months | 538.50 | 21.35 | 0.00 | 21.43 | 0.00 | 21.43 |
Maximum of Months | 645.00 | 21.49 | 59.50 | 21.54 | 2.33 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 717.83 | 23.73 | 0.00 | 23.73 |
February | 0.00 | 0.00 | 672.00 | 23.76 | 0.00 | 23.76 |
March | 4.50 | 22.35 | 735.67 | 23.78 | 0.00 | 23.78 |
April | 0.00 | 0.00 | 718.83 | 23.83 | 0.00 | 23.83 |
May | 4.17 | 22.44 | 730.17 | 23.85 | 0.00 | 23.85 |
June | 0.00 | 0.00 | 718.33 | 23.89 | 0.00 | 23.89 |
July | 0.00 | 0.00 | 737.67 | 23.81 | 0.00 | 23.81 |
August | 9.83 | 23.00 | 710.67 | 23.77 | 3.83 | 23.77 |
September | 0.00 | 0.00 | 691.67 | 23.79 | 0.00 | 23.79 |
October | 5.67 | 22.47 | 685.67 | 23.76 | 0.00 | 23.76 |
November | 0.17 | 22.52 | 692.17 | 23.74 | 0.00 | 23.74 |
December | 0.00 | 0.00 | 696.33 | 23.75 | 0.00 | 23.75 |
Annual Sum or Average | 24.33 | 22.66 | 8507.00 | 23.79 | 3.83 | 23.79 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.73 | 0.00 | 23.73 |
Maximum of Months | 9.83 | 23.00 | 737.67 | 23.89 | 3.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 741.33 | 23.75 | 0.00 | 23.75 |
February | 0.00 | 0.00 | 672.00 | 23.81 | 0.00 | 23.81 |
March | 1.83 | 22.39 | 737.83 | 23.83 | 0.00 | 23.83 |
April | 0.00 | 0.00 | 720.00 | 23.87 | 0.00 | 23.87 |
May | 0.00 | 0.00 | 737.67 | 23.88 | 0.00 | 23.88 |
June | 0.00 | 0.00 | 720.00 | 23.92 | 0.00 | 23.92 |
July | 0.00 | 0.00 | 744.00 | 23.85 | 0.00 | 23.85 |
August | 1.83 | 22.40 | 734.67 | 23.80 | 0.00 | 23.80 |
September | 0.00 | 0.00 | 720.00 | 23.81 | 0.00 | 23.81 |
October | 0.00 | 0.00 | 725.17 | 23.78 | 0.00 | 23.78 |
November | 0.00 | 0.00 | 713.50 | 23.77 | 0.00 | 23.77 |
December | 0.00 | 0.00 | 741.50 | 23.75 | 0.00 | 23.75 |
Annual Sum or Average | 3.67 | 22.39 | 8707.67 | 23.82 | 0.00 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.75 | 0.00 | 23.75 |
Maximum of Months | 1.83 | 22.40 | 744.00 | 23.92 | 0.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 556.00 | 23.98 | 743.67 | 23.77 | 556.00 | 23.83 |
February | 505.67 | 23.98 | 672.00 | 23.78 | 505.67 | 23.84 |
March | 561.83 | 23.98 | 743.83 | 23.79 | 561.83 | 23.85 |
April | 547.50 | 23.98 | 719.83 | 23.80 | 547.50 | 23.86 |
May | 564.50 | 23.98 | 743.67 | 23.80 | 564.50 | 23.86 |
June | 548.67 | 23.98 | 719.50 | 23.81 | 548.67 | 23.86 |
July | 560.67 | 23.98 | 744.00 | 23.79 | 560.67 | 23.85 |
August | 558.50 | 23.98 | 741.00 | 23.79 | 558.50 | 23.84 |
September | 542.67 | 23.98 | 716.83 | 23.79 | 542.67 | 23.85 |
October | 554.83 | 23.98 | 739.67 | 23.78 | 554.83 | 23.84 |
November | 540.17 | 23.98 | 719.50 | 23.77 | 540.17 | 23.83 |
December | 555.50 | 23.98 | 742.33 | 23.76 | 555.50 | 23.83 |
Annual Sum or Average | 6596.50 | 23.98 | 8745.83 | 23.79 | 6596.50 | 23.85 |
Minimum of Months | 505.67 | 23.98 | 672.00 | 23.76 | 505.67 | 23.83 |
Maximum of Months | 564.50 | 23.98 | 744.00 | 23.81 | 564.50 | 23.86 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.17 | 22.86 | 233.17 | 23.33 | 0.00 | 23.33 |
February | 182.83 | 23.00 | 316.17 | 23.58 | 0.00 | 23.58 |
March | 197.17 | 22.98 | 311.67 | 23.56 | 0.00 | 23.56 |
April | 125.00 | 22.97 | 323.17 | 23.66 | 0.00 | 23.66 |
May | 183.67 | 22.89 | 327.50 | 23.55 | 0.00 | 23.55 |
June | 115.17 | 23.01 | 366.50 | 23.71 | 0.00 | 23.71 |
July | 312.67 | 22.94 | 128.83 | 23.21 | 0.00 | 23.21 |
August | 405.00 | 22.75 | 146.00 | 23.05 | 0.00 | 23.05 |
September | 337.00 | 22.84 | 175.83 | 23.19 | 0.00 | 23.19 |
October | 418.00 | 22.79 | 98.83 | 22.99 | 0.00 | 22.99 |
November | 325.00 | 22.85 | 176.50 | 23.21 | 0.00 | 23.21 |
December | 336.83 | 22.81 | 183.83 | 23.20 | 0.00 | 23.20 |
Annual Sum or Average | 3226.50 | 22.86 | 2788.00 | 23.35 | 0.00 | 23.35 |
Minimum of Months | 115.17 | 22.75 | 98.83 | 22.99 | 0.00 | 22.99 |
Maximum of Months | 418.00 | 23.01 | 366.50 | 23.71 | 0.00 | 23.71 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.12497 | 52.85130 | 0.25773 | 6.46003 |
February | 672.00000 | 23.23202 | 52.52867 | 0.28409 | 6.72712 |
March | 744.00000 | 23.15131 | 52.66357 | 0.26357 | 6.49727 |
April | 720.00000 | 23.17170 | 52.58701 | 0.26721 | 6.56178 |
May | 744.00000 | 23.27698 | 52.25832 | -0.6673 | 14.47315 |
June | 720.00000 | 23.42794 | 51.80886 | -0.6152 | 13.05821 |
July | 744.00000 | 23.32379 | 52.15226 | -0.6515 | 14.00983 |
August | 744.00000 | 23.23705 | 52.43727 | -0.6818 | 14.93304 |
September | 720.00000 | 23.23859 | 52.55490 | -0.6788 | 14.85579 |
October | 744.00000 | 23.08143 | 52.93540 | 0.24642 | 6.32717 |
November | 720.00000 | 23.16721 | 52.70225 | 0.26768 | 6.55220 |
December | 744.00000 | 23.17987 | 52.76638 | 0.27150 | 6.59351 |
Annual Sum or Average | 8760.00000 | 23.21725 | 52.52162 | -0.1222 | 9.77346 |
Minimum of Months | 672.00000 | 23.08143 | 51.80886 | -0.6818 | 6.32717 |
Maximum of Months | 744.00000 | 23.42794 | 52.93540 | 0.28409 | 14.93304 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50797 | 53.14552 | 0.49892 | 10.86522 |
February | 672.00000 | 23.65224 | 52.71451 | 0.53781 | 11.47164 |
March | 744.00000 | 23.59648 | 53.09808 | 0.51440 | 10.93085 |
April | 720.00000 | 23.52440 | 54.06126 | 0.49262 | 10.50232 |
May | 744.00000 | 23.42812 | 54.97021 | -0.4249 | 9.84195 |
June | 720.00000 | 23.52448 | 54.57941 | -0.3865 | 8.91057 |
July | 744.00000 | 23.24937 | 54.83975 | -0.5033 | 11.11023 |
August | 744.00000 | 23.10923 | 56.00716 | -0.5479 | 12.71245 |
September | 720.00000 | 23.30189 | 55.33082 | -0.4733 | 10.93202 |
October | 744.00000 | 23.21230 | 55.40753 | 0.41152 | 9.27169 |
November | 720.00000 | 23.41762 | 54.22565 | 0.47033 | 10.26601 |
December | 744.00000 | 23.45718 | 53.66952 | 0.48490 | 10.61513 |
Annual Sum or Average | 8760.00000 | 23.41286 | 54.34847 | 0.08658 | 10.61728 |
Minimum of Months | 672.00000 | 23.10923 | 52.71451 | -0.5479 | 8.91057 |
Maximum of Months | 744.00000 | 23.65224 | 56.00716 | 0.53781 | 12.71245 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.04608 | 54.76718 | 0.30741 | 7.25281 |
February | 672.00000 | 23.26704 | 54.11378 | 0.36356 | 7.96106 |
March | 744.00000 | 23.28818 | 54.02830 | 0.36889 | 8.08954 |
April | 720.00000 | 23.29768 | 54.27262 | 0.37224 | 8.18328 |
May | 744.00000 | 23.22748 | 54.75218 | -0.5840 | 12.78353 |
June | 720.00000 | 23.35374 | 54.29435 | -0.5361 | 11.56871 |
July | 744.00000 | 23.10083 | 54.80630 | -0.6321 | 13.90229 |
August | 744.00000 | 22.99544 | 55.47575 | -0.6671 | 15.21661 |
September | 720.00000 | 23.07229 | 55.30626 | -0.6381 | 14.29499 |
October | 744.00000 | 22.89940 | 55.70137 | 0.27333 | 6.88152 |
November | 720.00000 | 22.99823 | 55.22286 | 0.29732 | 7.11204 |
December | 744.00000 | 23.00284 | 55.09163 | 0.29798 | 7.10173 |
Annual Sum or Average | 8760.00000 | 23.12740 | 54.82568 | -0.0676 | 10.04315 |
Minimum of Months | 672.00000 | 22.89940 | 54.02830 | -0.6671 | 6.88152 |
Maximum of Months | 744.00000 | 23.35374 | 55.70137 | 0.37224 | 15.21661 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08461 | 53.34141 | 0.65897 | 16.20609 |
February | 672.00000 | 22.15656 | 53.09867 | 0.69497 | 17.17595 |
March | 744.00000 | 22.17944 | 52.94950 | 0.70567 | 17.53706 |
April | 720.00000 | 22.20874 | 52.93389 | 0.71892 | 17.90709 |
May | 744.00000 | 22.18659 | 53.06095 | -0.0684 | 9.42610 |
June | 720.00000 | 22.23022 | 52.88664 | -0.0346 | 9.26253 |
July | 744.00000 | 22.11493 | 53.21539 | -0.1082 | 9.56254 |
August | 744.00000 | 22.10377 | 53.37499 | -0.1260 | 9.74192 |
September | 720.00000 | 22.11617 | 53.44553 | -0.1105 | 9.58681 |
October | 744.00000 | 22.05250 | 53.57317 | 0.64158 | 15.76354 |
November | 720.00000 | 22.08845 | 53.40808 | 0.65820 | 16.16404 |
December | 744.00000 | 22.06239 | 53.52581 | 0.64926 | 15.92906 |
Annual Sum or Average | 8760.00000 | 22.13151 | 53.23634 | 0.35441 | 13.66492 |
Minimum of Months | 672.00000 | 22.05250 | 52.88664 | -0.1260 | 9.26253 |
Maximum of Months | 744.00000 | 22.23022 | 53.57317 | 0.71892 | 17.90709 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73601 | 58.19005 | 0.61362 | 13.19204 |
February | 672.00000 | 23.80615 | 57.96933 | 0.63292 | 13.56502 |
March | 744.00000 | 23.64505 | 58.59652 | 0.58279 | 12.37917 |
April | 720.00000 | 23.50477 | 59.42520 | 0.54295 | 11.49398 |
May | 744.00000 | 23.46989 | 59.85316 | -0.3476 | 8.26800 |
June | 720.00000 | 23.50940 | 59.63720 | -0.3289 | 7.84883 |
July | 744.00000 | 23.33881 | 60.04238 | -0.4082 | 9.20240 |
August | 744.00000 | 23.25623 | 60.70429 | -0.4389 | 10.01432 |
September | 720.00000 | 23.40177 | 60.21840 | -0.3764 | 8.71591 |
October | 744.00000 | 23.41271 | 60.07772 | 0.51535 | 10.98705 |
November | 720.00000 | 23.63757 | 59.01995 | 0.58143 | 12.38552 |
December | 744.00000 | 23.71323 | 58.57857 | 0.60581 | 12.98781 |
Annual Sum or Average | 8760.00000 | 23.53399 | 59.36846 | 0.17836 | 10.90713 |
Minimum of Months | 672.00000 | 23.25623 | 57.96933 | -0.4389 | 7.84883 |
Maximum of Months | 744.00000 | 23.80615 | 60.70429 | 0.63292 | 13.56502 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.35592 | 57.72003 | 0.41625 | 8.85575 |
February | 672.00000 | 23.47962 | 57.34333 | 0.44987 | 9.40613 |
March | 744.00000 | 23.42453 | 57.51042 | 0.43482 | 9.19695 |
April | 720.00000 | 23.43367 | 57.72327 | 0.43827 | 9.29314 |
May | 744.00000 | 23.48028 | 57.72018 | -0.4568 | 9.88305 |
June | 720.00000 | 23.58147 | 57.21934 | -0.4137 | 8.99201 |
July | 744.00000 | 23.40665 | 57.71204 | -0.4881 | 10.49339 |
August | 744.00000 | 23.26767 | 58.50323 | -0.5392 | 11.80883 |
September | 720.00000 | 23.30648 | 58.46932 | -0.5232 | 11.36123 |
October | 744.00000 | 23.20995 | 58.64710 | 0.37992 | 8.31977 |
November | 720.00000 | 23.32843 | 58.10667 | 0.41061 | 8.76794 |
December | 744.00000 | 23.33730 | 57.98144 | 0.41237 | 8.76996 |
Annual Sum or Average | 8760.00000 | 23.38324 | 57.89260 | 0.04080 | 9.59715 |
Minimum of Months | 672.00000 | 23.20995 | 57.21934 | -0.5392 | 8.31977 |
Maximum of Months | 744.00000 | 23.58147 | 58.64710 | 0.44987 | 11.80883 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74417 | 54.29947 | 0.00887 | 5.77406 |
February | 672.00000 | 21.74712 | 53.71707 | 0.01867 | 5.77980 |
March | 744.00000 | 21.74604 | 53.96701 | 0.01994 | 5.75436 |
April | 720.00000 | 21.74597 | 55.25547 | 0.02538 | 5.80339 |
May | 744.00000 | 21.74545 | 56.56174 | -1.0428 | 29.29470 |
June | 720.00000 | 21.74683 | 56.37884 | -1.0331 | 28.89641 |
July | 744.00000 | 21.73963 | 56.03622 | -1.0719 | 30.52226 |
August | 744.00000 | 21.73900 | 57.56102 | -1.0659 | 30.30933 |
September | 720.00000 | 21.74199 | 57.07782 | -1.0600 | 30.07965 |
October | 744.00000 | 21.73990 | 57.04678 | 0.00790 | 5.78627 |
November | 720.00000 | 21.74289 | 55.58837 | 0.00833 | 5.77996 |
December | 744.00000 | 21.74369 | 55.05287 | 0.00710 | 5.78261 |
Annual Sum or Average | 8760.00000 | 21.74352 | 55.72430 | -0.4342 | 15.85904 |
Minimum of Months | 672.00000 | 21.73900 | 53.71707 | -1.0719 | 5.75436 |
Maximum of Months | 744.00000 | 21.74712 | 57.56102 | 0.02538 | 30.52226 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89182 | 55.78146 | 0.02638 | 5.86749 |
February | 672.00000 | 21.87495 | 54.79135 | 0.03424 | 5.86353 |
March | 744.00000 | 21.76004 | 54.32827 | 0.01683 | 5.74951 |
April | 720.00000 | 21.75097 | 55.19011 | 0.02723 | 5.81312 |
May | 744.00000 | 21.76130 | 56.32354 | -1.0309 | 28.83642 |
June | 720.00000 | 21.77855 | 56.03326 | -1.0091 | 27.96873 |
July | 744.00000 | 21.77698 | 55.73063 | -1.0524 | 29.75635 |
August | 744.00000 | 21.76113 | 57.39819 | -1.0555 | 29.90204 |
September | 720.00000 | 21.77282 | 57.28102 | -1.0527 | 29.81225 |
October | 744.00000 | 21.78208 | 57.72160 | 0.01258 | 5.83875 |
November | 720.00000 | 21.85064 | 56.67924 | 0.02186 | 5.87382 |
December | 744.00000 | 21.90827 | 56.61198 | 0.02835 | 5.88833 |
Annual Sum or Average | 8760.00000 | 21.80542 | 56.16557 | -0.4222 | 15.65814 |
Minimum of Months | 672.00000 | 21.75097 | 54.32827 | -1.0555 | 5.74951 |
Maximum of Months | 744.00000 | 21.90827 | 57.72160 | 0.03424 | 29.90204 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.82504 | 56.82227 | -0.0639 | 5.72535 |
February | 672.00000 | 21.81322 | 56.13188 | -0.0644 | 5.71501 |
March | 744.00000 | 21.71796 | 55.30707 | -0.0871 | 5.72304 |
April | 720.00000 | 21.71609 | 55.63297 | -0.0793 | 5.77124 |
May | 744.00000 | 21.73572 | 56.06361 | -1.1682 | 34.68851 |
June | 720.00000 | 21.75868 | 56.02307 | -1.1470 | 33.76069 |
July | 744.00000 | 21.74939 | 55.40606 | -1.1740 | 34.95995 |
August | 744.00000 | 21.72512 | 56.86170 | -1.1851 | 35.45976 |
September | 720.00000 | 21.73076 | 57.06633 | -1.1857 | 35.50955 |
October | 744.00000 | 21.73605 | 57.32600 | -0.0772 | 5.77317 |
November | 720.00000 | 21.79742 | 56.98655 | -0.0663 | 5.76105 |
December | 744.00000 | 21.84309 | 57.44034 | -0.0583 | 5.73043 |
Annual Sum or Average | 8760.00000 | 21.76209 | 56.42465 | -0.5325 | 17.95606 |
Minimum of Months | 672.00000 | 21.71609 | 55.30707 | -1.1857 | 5.71501 |
Maximum of Months | 744.00000 | 21.84309 | 57.44034 | -0.0583 | 35.50955 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.75079 | 54.68236 | 0.01363 | 5.77326 |
February | 672.00000 | 21.75357 | 54.14769 | 0.02504 | 5.78203 |
March | 744.00000 | 21.75293 | 54.20516 | 0.02345 | 5.76349 |
April | 720.00000 | 21.75309 | 55.28476 | 0.02923 | 5.81708 |
May | 744.00000 | 21.75074 | 56.70066 | -1.0373 | 29.07892 |
June | 720.00000 | 21.75267 | 56.50258 | -1.0281 | 28.69506 |
July | 744.00000 | 21.74658 | 56.15249 | -1.0679 | 30.35648 |
August | 744.00000 | 21.74684 | 57.57931 | -1.0613 | 30.12895 |
September | 720.00000 | 21.74826 | 57.10527 | -1.0548 | 29.86901 |
October | 744.00000 | 21.74621 | 57.18609 | 0.01097 | 5.78939 |
November | 720.00000 | 21.74829 | 56.07579 | 0.01350 | 5.77807 |
December | 744.00000 | 21.74946 | 55.47333 | 0.01168 | 5.77914 |
Annual Sum or Average | 8760.00000 | 21.74992 | 55.93575 | -0.4296 | 15.77927 |
Minimum of Months | 672.00000 | 21.74621 | 54.14769 | -1.0679 | 5.76349 |
Maximum of Months | 744.00000 | 21.75357 | 57.57931 | 0.02923 | 30.35648 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.95092 | 56.04178 | 0.04194 | 6.07928 |
February | 672.00000 | 21.92453 | 55.10803 | 0.04945 | 6.04850 |
March | 744.00000 | 21.77098 | 54.58821 | 0.02140 | 5.76956 |
April | 720.00000 | 21.75724 | 55.26394 | 0.03113 | 5.82315 |
May | 744.00000 | 21.76516 | 56.50345 | -1.0257 | 28.62429 |
June | 720.00000 | 21.78415 | 56.10971 | -1.0047 | 27.79124 |
July | 744.00000 | 21.78371 | 55.92699 | -1.0480 | 29.57996 |
August | 744.00000 | 21.76814 | 57.45866 | -1.0510 | 29.72152 |
September | 720.00000 | 21.77927 | 57.29863 | -1.0476 | 29.60166 |
October | 744.00000 | 21.79095 | 57.74707 | 0.01554 | 5.84459 |
November | 720.00000 | 21.87142 | 57.00826 | 0.02949 | 5.92107 |
December | 744.00000 | 21.96069 | 56.85775 | 0.04218 | 6.06589 |
Annual Sum or Average | 8760.00000 | 21.82509 | 56.33502 | -0.4150 | 15.63208 |
Minimum of Months | 672.00000 | 21.75724 | 54.58821 | -1.0510 | 5.76956 |
Maximum of Months | 744.00000 | 21.96069 | 57.74707 | 0.04945 | 29.72152 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74378 | 55.02190 | 0.01801 | 6.02238 |
February | 672.00000 | 21.74637 | 54.43561 | 0.02705 | 6.05383 |
March | 744.00000 | 21.74616 | 54.44774 | 0.03057 | 6.00617 |
April | 720.00000 | 21.74705 | 55.44459 | 0.03717 | 6.03535 |
May | 744.00000 | 21.74529 | 56.83422 | -1.0310 | 29.17658 |
June | 720.00000 | 21.74665 | 56.69050 | -1.0234 | 28.87681 |
July | 744.00000 | 21.73926 | 56.43692 | -1.0610 | 30.39032 |
August | 744.00000 | 21.73922 | 57.89959 | -1.0539 | 30.12346 |
September | 720.00000 | 21.74258 | 57.26701 | -1.0461 | 29.84846 |
October | 744.00000 | 21.73965 | 57.49228 | 0.01635 | 5.95901 |
November | 720.00000 | 21.74321 | 56.11572 | 0.01644 | 5.98160 |
December | 744.00000 | 21.74384 | 55.82057 | 0.01536 | 6.01596 |
Annual Sum or Average | 8760.00000 | 21.74355 | 56.17063 | -0.4240 | 15.93502 |
Minimum of Months | 672.00000 | 21.73922 | 54.43561 | -1.0610 | 5.95901 |
Maximum of Months | 744.00000 | 21.74705 | 57.89959 | 0.03717 | 30.39032 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.87186 | 56.48966 | 0.03117 | 6.05058 |
February | 672.00000 | 21.85876 | 55.34622 | 0.03846 | 6.07042 |
March | 744.00000 | 21.75862 | 54.68600 | 0.02649 | 5.97105 |
April | 720.00000 | 21.75248 | 55.37480 | 0.03922 | 6.04903 |
May | 744.00000 | 21.76121 | 56.61630 | -1.0187 | 28.72236 |
June | 720.00000 | 21.77799 | 56.29168 | -0.9993 | 27.99826 |
July | 744.00000 | 21.77657 | 56.10248 | -1.0411 | 29.65256 |
August | 744.00000 | 21.76198 | 57.73652 | -1.0430 | 29.71667 |
September | 720.00000 | 21.77585 | 57.45537 | -1.0379 | 29.55198 |
October | 744.00000 | 21.78298 | 58.14537 | 0.02138 | 6.01061 |
November | 720.00000 | 21.84736 | 57.19817 | 0.02928 | 6.05730 |
December | 744.00000 | 21.88993 | 57.45547 | 0.03307 | 6.06962 |
Annual Sum or Average | 8760.00000 | 21.80097 | 56.58488 | -0.4129 | 15.71963 |
Minimum of Months | 672.00000 | 21.75248 | 54.68600 | -1.0430 | 5.97105 |
Maximum of Months | 744.00000 | 21.88993 | 58.14537 | 0.03922 | 29.71667 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.75990 | 55.09237 | 0.01400 | 6.04489 |
February | 672.00000 | 21.75777 | 54.62793 | 0.00974 | 5.99827 |
March | 744.00000 | 21.74939 | 54.62564 | -0.0092 | 5.87161 |
April | 720.00000 | 21.74417 | 55.82885 | -0.0148 | 5.88015 |
May | 744.00000 | 21.74443 | 56.96439 | -1.0948 | 31.71824 |
June | 720.00000 | 21.74463 | 57.06597 | -1.0931 | 31.64394 |
July | 744.00000 | 21.73839 | 56.49364 | -1.1179 | 32.71550 |
August | 744.00000 | 21.73771 | 57.85621 | -1.1146 | 32.59005 |
September | 720.00000 | 21.74324 | 57.11762 | -1.1005 | 32.02574 |
October | 744.00000 | 21.74518 | 56.72843 | -0.0114 | 5.89267 |
November | 720.00000 | 21.75372 | 55.76387 | 0.00339 | 5.95738 |
December | 744.00000 | 21.75963 | 55.72504 | 0.01414 | 6.05198 |
Annual Sum or Average | 8760.00000 | 21.74812 | 56.16693 | -0.4624 | 16.93315 |
Minimum of Months | 672.00000 | 21.73771 | 54.62564 | -1.1179 | 5.87161 |
Maximum of Months | 744.00000 | 21.75990 | 57.85621 | 0.01414 | 32.71550 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.69753 | 57.72559 | 0.57703 | 12.16684 |
February | 672.00000 | 23.76311 | 57.40514 | 0.60072 | 12.70576 |
March | 744.00000 | 23.77504 | 57.17199 | 0.60866 | 12.93035 |
April | 720.00000 | 23.83207 | 56.97559 | 0.62989 | 13.45557 |
May | 744.00000 | 23.83405 | 56.95416 | -0.2018 | 6.12648 |
June | 720.00000 | 23.88612 | 56.61669 | -0.1713 | 5.77002 |
July | 744.00000 | 23.79926 | 57.11353 | -0.2267 | 6.30812 |
August | 744.00000 | 23.72794 | 57.61259 | -0.2618 | 6.82375 |
September | 720.00000 | 23.74846 | 57.67953 | -0.2525 | 6.66466 |
October | 744.00000 | 23.69111 | 57.91226 | 0.57676 | 12.20933 |
November | 720.00000 | 23.70797 | 57.79306 | 0.58092 | 12.26234 |
December | 744.00000 | 23.68639 | 57.98022 | 0.57145 | 12.04040 |
Annual Sum or Average | 8760.00000 | 23.76207 | 57.41334 | 0.25037 | 9.93727 |
Minimum of Months | 672.00000 | 23.68639 | 56.61669 | -0.2618 | 5.77002 |
Maximum of Months | 744.00000 | 23.88612 | 57.98022 | 0.62989 | 13.45557 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.75078 | 57.08229 | 0.61281 | 13.02561 |
February | 672.00000 | 23.80671 | 56.80522 | 0.63365 | 13.53520 |
March | 744.00000 | 23.81992 | 56.57113 | 0.64244 | 13.78953 |
April | 720.00000 | 23.87313 | 56.38504 | 0.66305 | 14.33610 |
May | 744.00000 | 23.87112 | 56.36732 | -0.1545 | 5.71413 |
June | 720.00000 | 23.91850 | 56.06224 | -0.1259 | 5.45509 |
July | 744.00000 | 23.84958 | 56.46776 | -0.1736 | 5.80280 |
August | 744.00000 | 23.78913 | 56.91274 | -0.2045 | 6.16045 |
September | 720.00000 | 23.80571 | 57.00002 | -0.1974 | 6.06334 |
October | 744.00000 | 23.75267 | 57.20541 | 0.61604 | 13.14443 |
November | 720.00000 | 23.76425 | 57.12089 | 0.61811 | 13.15952 |
December | 744.00000 | 23.74407 | 57.30724 | 0.60868 | 12.92587 |
Annual Sum or Average | 8760.00000 | 23.81187 | 56.77513 | 0.29273 | 10.23796 |
Minimum of Months | 672.00000 | 23.74407 | 56.06224 | -0.2045 | 5.45509 |
Maximum of Months | 744.00000 | 23.91850 | 57.30724 | 0.66305 | 14.33610 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60529 | 56.39863 | 1.23420 | 39.37986 |
February | 672.00000 | 23.63174 | 56.19946 | 1.25551 | 40.27833 |
March | 744.00000 | 23.64828 | 56.04042 | 1.26121 | 40.45283 |
April | 720.00000 | 23.66903 | 55.98875 | 1.27479 | 41.02264 |
May | 744.00000 | 23.66540 | 56.09256 | 0.70697 | 21.58886 |
June | 720.00000 | 23.67925 | 55.95780 | 0.72612 | 22.08013 |
July | 744.00000 | 23.64092 | 56.18173 | 0.67993 | 20.92181 |
August | 744.00000 | 23.62954 | 56.38389 | 0.66336 | 20.56941 |
September | 720.00000 | 23.64305 | 56.40641 | 0.68100 | 20.96455 |
October | 744.00000 | 23.61332 | 56.52718 | 1.22540 | 38.83890 |
November | 720.00000 | 23.61071 | 56.45977 | 1.23223 | 39.20251 |
December | 744.00000 | 23.59260 | 56.57997 | 1.22598 | 39.04912 |
Annual Sum or Average | 8760.00000 | 23.63563 | 56.26932 | 1.01229 | 31.97455 |
Minimum of Months | 672.00000 | 23.59260 | 55.95780 | 0.66336 | 20.56941 |
Maximum of Months | 744.00000 | 23.67925 | 56.57997 | 1.27479 | 41.02264 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.87100 | 53.56994 | 0.19980 | 5.90623 |
February | 672.00000 | 23.13712 | 52.81802 | 0.26355 | 6.48263 |
March | 744.00000 | 23.19736 | 52.76836 | 0.27816 | 6.69503 |
April | 720.00000 | 23.41312 | 52.82278 | 0.33286 | 7.42177 |
May | 744.00000 | 23.59951 | 52.76040 | -0.5434 | 11.50123 |
June | 720.00000 | 23.79152 | 51.90886 | -0.4705 | 9.81031 |
July | 744.00000 | 23.52485 | 52.19388 | -0.5756 | 12.12256 |
August | 744.00000 | 23.20857 | 53.97078 | -0.6775 | 15.17775 |
September | 720.00000 | 23.15135 | 54.14223 | -0.6959 | 15.54445 |
October | 744.00000 | 22.88900 | 54.73552 | 0.21178 | 6.05656 |
November | 720.00000 | 22.94209 | 54.13300 | 0.22187 | 6.10550 |
December | 744.00000 | 22.83528 | 54.03859 | 0.19394 | 5.85516 |
Annual Sum or Average | 8760.00000 | 23.21281 | 53.32677 | -0.1076 | 9.07048 |
Minimum of Months | 672.00000 | 22.83528 | 51.90886 | -0.6959 | 5.85516 |
Maximum of Months | 744.00000 | 23.79152 | 54.73552 | 0.33286 | 15.54445 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.09057 | 55.70863 | 0.22266 | 6.11206 |
February | 672.00000 | 23.30032 | 55.13950 | 0.27314 | 6.57402 |
March | 744.00000 | 23.19939 | 55.46160 | 0.24913 | 6.32522 |
April | 720.00000 | 23.18476 | 55.89391 | 0.24682 | 6.32899 |
May | 744.00000 | 23.28611 | 55.92575 | -0.7054 | 15.63338 |
June | 720.00000 | 23.47947 | 55.32763 | -0.6398 | 13.80039 |
July | 744.00000 | 23.04400 | 56.14196 | -0.7900 | 18.22023 |
August | 744.00000 | 22.90240 | 57.03242 | -0.8346 | 19.88691 |
September | 720.00000 | 22.90794 | 57.06394 | -0.8312 | 19.76698 |
October | 744.00000 | 22.87768 | 56.97256 | 0.17631 | 5.70459 |
November | 720.00000 | 23.03183 | 56.28938 | 0.21156 | 5.98810 |
December | 744.00000 | 23.04758 | 56.06100 | 0.21407 | 6.02124 |
Annual Sum or Average | 8760.00000 | 23.11071 | 56.09198 | -0.1869 | 10.89211 |
Minimum of Months | 672.00000 | 22.87768 | 55.13950 | -0.8346 | 5.70459 |
Maximum of Months | 744.00000 | 23.47947 | 57.06394 | 0.27314 | 19.88691 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.37687 | 52.42621 | 0.33794 | 7.64344 |
February | 672.00000 | 23.55478 | 51.92885 | 0.38167 | 8.22787 |
March | 744.00000 | 23.52836 | 52.01768 | 0.37591 | 8.14298 |
April | 720.00000 | 23.57400 | 52.19846 | 0.38906 | 8.35184 |
May | 744.00000 | 23.52161 | 52.60210 | -0.5480 | 11.78833 |
June | 720.00000 | 23.63312 | 52.18429 | -0.5073 | 10.72591 |
July | 744.00000 | 23.31528 | 52.86823 | -0.6253 | 13.55088 |
August | 744.00000 | 23.14554 | 53.79222 | -0.6810 | 15.47235 |
September | 720.00000 | 23.26445 | 53.48161 | -0.6383 | 14.15758 |
October | 744.00000 | 23.13206 | 53.73194 | 0.28196 | 6.92238 |
November | 720.00000 | 23.28593 | 53.06217 | 0.31809 | 7.38477 |
December | 744.00000 | 23.27966 | 52.92487 | 0.31543 | 7.36256 |
Annual Sum or Average | 8760.00000 | 23.38230 | 52.77552 | -0.0529 | 9.99001 |
Minimum of Months | 672.00000 | 23.13206 | 51.92885 | -0.6810 | 6.92238 |
Maximum of Months | 744.00000 | 23.63312 | 53.79222 | 0.38906 | 15.47235 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.93157 | 52.95049 | 0.21904 | 6.10400 |
February | 672.00000 | 23.21317 | 52.14797 | 0.28667 | 6.77784 |
March | 744.00000 | 23.28555 | 52.04718 | 0.30419 | 7.04814 |
April | 720.00000 | 23.49724 | 52.04170 | 0.35894 | 7.82009 |
May | 744.00000 | 23.65480 | 51.98891 | -0.5114 | 10.80941 |
June | 720.00000 | 23.82991 | 51.18150 | -0.4406 | 9.23835 |
July | 744.00000 | 23.60289 | 51.42268 | -0.5370 | 11.24726 |
August | 744.00000 | 23.28749 | 53.17568 | -0.6413 | 14.22195 |
September | 720.00000 | 23.24136 | 53.34971 | -0.6574 | 14.51996 |
October | 744.00000 | 22.96353 | 54.00826 | 0.23396 | 6.30036 |
November | 720.00000 | 23.01237 | 53.44186 | 0.24321 | 6.34098 |
December | 744.00000 | 22.89315 | 53.41200 | 0.21246 | 6.04038 |
Annual Sum or Average | 8760.00000 | 23.28379 | 52.60205 | -0.0799 | 8.88295 |
Minimum of Months | 672.00000 | 22.89315 | 51.18150 | -0.6574 | 6.04038 |
Maximum of Months | 744.00000 | 23.82991 | 54.00826 | 0.35894 | 14.51996 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.361817E+12 | 200342.50 | 04-JAN-16:03 | 744.00 | 0.119617E+13 | 0.00 | 0.155799E+13 | 3.31 | 4.05 | 08-JAN-09:54 | 0.00 | 0.00 |
February | 0.340158E+12 | 217804.10 | 13-FEB-16:03 | 672.00 | 0.110165E+13 | 0.00 | 0.144180E+13 | 3.25 | 3.78 | 10-FEB-07:20 | 0.00 | 0.00 |
March | 0.393406E+12 | 223394.89 | 28-MAR-15:03 | 744.00 | 0.126340E+13 | 0.00 | 0.165681E+13 | 3.22 | 3.90 | 14-MAR-22:50 | 0.00 | 0.00 |
April | 0.422947E+12 | 240088.16 | 10-APR-18:03 | 720.00 | 0.136988E+13 | 0.00 | 0.179283E+13 | 3.25 | 3.70 | 14-APR-15:50 | 0.00 | 0.00 |
May | 0.466877E+12 | 255784.12 | 06-MAY-15:03 | 744.00 | 0.154238E+13 | 0.00 | 0.200926E+13 | 3.32 | 4.01 | 10-MAY-19:50 | 0.00 | 0.00 |
June | 0.456547E+12 | 272516.82 | 13-JUN-15:03 | 720.00 | 0.151645E+13 | 0.00 | 0.197300E+13 | 3.34 | 4.04 | 25-JUN-21:53 | 0.00 | 0.00 |
July | 0.396650E+12 | 219477.10 | 20-JUL-15:03 | 744.00 | 0.132639E+13 | 0.00 | 0.172304E+13 | 3.35 | 3.99 | 19-JUL-21:53 | 0.00 | 0.00 |
August | 0.430521E+12 | 243587.09 | 13-AUG-15:03 | 744.00 | 0.145852E+13 | 0.00 | 0.188904E+13 | 3.40 | 3.97 | 23-AUG-21:00 | 0.00 | 0.00 |
September | 0.410291E+12 | 232609.12 | 08-SEP-18:02 | 720.00 | 0.138401E+13 | 0.00 | 0.179430E+13 | 3.38 | 4.05 | 15-SEP-21:52 | 0.00 | 0.00 |
October | 0.403793E+12 | 223939.28 | 16-OCT-15:03 | 744.00 | 0.137438E+13 | 0.00 | 0.177818E+13 | 3.41 | 3.90 | 09-OCT-19:05 | 0.00 | 0.00 |
November | 0.377315E+12 | 218179.06 | 17-NOV-19:03 | 720.00 | 0.127643E+13 | 0.00 | 0.165375E+13 | 3.39 | 4.00 | 25-NOV-22:52 | 0.00 | 0.00 |
December | 0.370627E+12 | 208017.31 | 29-DEC-19:03 | 744.00 | 0.125855E+13 | 0.00 | 0.162917E+13 | 3.40 | 3.92 | 04-DEC-23:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483095E+13 | 8760.00 | 0.160682E+14 | 0.00 | 0.208992E+14 | 3.34 | 0.00 | 0.00 | ||||
Minimum of Months | 0.340158E+12 | 200342.50 | 672.00 | 0.110165E+13 | 0.00 | 0.144180E+13 | 3.22 | 3.70 | 0.00 | 0.00 | ||
Maximum of Months | 0.466877E+12 | 272516.82 | 744.00 | 0.154238E+13 | 0.00 | 0.200926E+13 | 3.41 | 4.05 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.150080E+10 | 0.00 | 180.06 | 20385.22 | 22-JAN-19:07 | 0.00 | 30.69 | 37.95 | 0.00 | 0.00 | 0.00 | 0.08 | 22-JAN-19:07 |
February | 0.114428E+10 | 0.00 | 149.87 | 20512.97 | 12-FEB-19:07 | 0.00 | 30.40 | 37.08 | 0.00 | 0.00 | 0.00 | 0.08 | 12-FEB-19:07 |
March | 0.126267E+10 | 0.00 | 159.49 | 22186.71 | 03-MAR-16:07 | 0.00 | 30.46 | 36.86 | 0.00 | 0.00 | 0.00 | 0.08 | 03-MAR-16:07 |
April | 0.109340E+10 | 0.00 | 141.24 | 21877.62 | 23-APR-18:07 | 0.00 | 30.20 | 36.15 | 0.00 | 0.00 | 0.00 | 0.08 | 23-APR-18:07 |
May | 0.123381E+10 | 0.00 | 155.77 | 14581.43 | 21-MAY-18:07 | 0.00 | 29.79 | 36.17 | 0.00 | 0.00 | 0.00 | 0.06 | 21-MAY-18:07 |
June | 0.105611E+10 | 0.00 | 143.80 | 17800.45 | 30-JUN-18:07 | 0.00 | 29.14 | 35.38 | 0.00 | 0.00 | 0.00 | 0.07 | 30-JUN-18:07 |
July | 0.127835E+10 | 0.00 | 175.39 | 20933.44 | 16-JUL-18:07 | 0.00 | 30.48 | 37.57 | 0.00 | 0.00 | 0.00 | 0.08 | 16-JUL-18:07 |
August | 0.149102E+10 | 0.00 | 181.54 | 21669.50 | 06-AUG-18:07 | 0.00 | 30.68 | 37.90 | 0.00 | 0.00 | 0.00 | 0.08 | 06-AUG-18:07 |
September | 0.129264E+10 | 0.00 | 166.75 | 19234.88 | 03-SEP-18:07 | 0.00 | 30.37 | 37.29 | 0.00 | 0.00 | 0.00 | 0.07 | 03-SEP-18:07 |
October | 0.156674E+10 | 0.00 | 212.07 | 19193.89 | 09-OCT-18:07 | 0.00 | 30.72 | 39.15 | 0.00 | 0.00 | 0.00 | 0.07 | 09-OCT-18:07 |
November | 0.142346E+10 | 0.00 | 177.45 | 14008.85 | 11-NOV-19:07 | 0.00 | 30.61 | 37.96 | 0.00 | 0.00 | 0.00 | 0.05 | 11-NOV-19:07 |
December | 0.153609E+10 | 0.00 | 181.42 | 19745.24 | 28-DEC-16:07 | 0.00 | 31.18 | 38.35 | 0.00 | 0.00 | 0.00 | 0.08 | 28-DEC-16:07 |
Annual Sum or Average | 0.158794E+11 | 0.00 | 2024.86 | 0.00 | 30.40 | 37.33 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105611E+10 | 0.00 | 141.24 | 14008.85 | 0.00 | 29.14 | 35.38 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.156674E+10 | 0.00 | 212.07 | 22186.71 | 0.00 | 31.18 | 39.15 | 0.00 | 0.00 | 0.00 | 0.08 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.927660E+12 | 0.00 | 744.00 | 0.507221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471446.77 | 08-JAN-08:23 | 239862.56 | 04-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.850215E+12 | 0.00 | 672.00 | 0.482361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465919.81 | 17-FEB-06:50 | 246253.09 | 22-FEB-19:20 | 0.00 | 0.00 | 0.00 |
March | 0.984885E+12 | 0.00 | 744.00 | 0.546801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 511839.21 | 14-MAR-21:20 | 251046.10 | 28-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.108567E+13 | 0.00 | 720.00 | 0.544446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 575100.56 | 10-APR-18:07 | 271131.75 | 30-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 0.123382E+13 | 0.00 | 744.00 | 0.565357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 606446.11 | 31-MAY-20:20 | 274000.67 | 05-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.120933E+13 | 0.00 | 720.00 | 0.553989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588108.33 | 15-JUN-10:00 | 284799.18 | 12-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.105131E+13 | 0.00 | 744.00 | 0.530040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 600058.82 | 17-JUL-18:50 | 267979.71 | 14-JUL-18:05 | 0.00 | 0.00 | 0.00 |
August | 0.117731E+13 | 0.00 | 744.00 | 0.531546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 592107.94 | 08-AUG-18:07 | 264018.41 | 14-AUG-18:07 | 0.00 | 0.00 | 0.00 |
September | 0.111134E+13 | 0.00 | 720.00 | 0.514809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 601562.73 | 15-SEP-19:25 | 258742.77 | 13-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.110059E+13 | 0.00 | 744.00 | 0.515766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 567548.06 | 09-OCT-19:20 | 242711.69 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.100939E+13 | 0.00 | 720.00 | 0.498378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 553938.97 | 30-NOV-23:00 | 244612.21 | 17-NOV-19:10 | 0.00 | 0.00 | 0.00 |
December | 0.989946E+12 | 0.00 | 744.00 | 0.498939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 521915.33 | 18-DEC-24:00 | 243890.38 | 08-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127315E+14 | 0.00 | 8760.00 | 0.628965E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.850215E+12 | 0.00 | 672.00 | 0.482361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465919.81 | 239862.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.123382E+13 | 0.00 | 744.00 | 0.565357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 606446.11 | 284799.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.577821E+11 | 0.00 | 589.00 | 0.331550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44040.44 | 08-JAN-09:03 | 21122.61 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.527113E+11 | 0.00 | 532.00 | 0.310032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41854.11 | 13-FEB-06:50 | 21531.97 | 26-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.609979E+11 | 0.00 | 589.00 | 0.348596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38636.66 | 27-MAR-13:00 | 21920.69 | 19-MAR-12:03 | 0.00 | 0.00 | 0.00 |
April | 0.677701E+11 | 0.00 | 570.00 | 0.345865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44437.98 | 10-APR-18:02 | 21728.14 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.775428E+11 | 0.00 | 589.00 | 0.357355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51677.37 | 10-MAY-21:10 | 22724.66 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.745676E+11 | 0.00 | 570.00 | 0.344855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50593.91 | 25-JUN-19:40 | 22299.71 | 16-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.654993E+11 | 0.00 | 589.00 | 0.342664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47849.78 | 10-JUL-15:00 | 20959.04 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.744237E+11 | 0.00 | 589.00 | 0.345488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50776.45 | 19-AUG-18:03 | 21497.27 | 13-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.703157E+11 | 0.00 | 570.00 | 0.334783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50918.60 | 15-SEP-20:40 | 20998.80 | 09-SEP-12:20 | 0.00 | 0.00 | 0.00 |
October | 0.705625E+11 | 0.00 | 589.00 | 0.340114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53022.45 | 30-OCT-18:03 | 20721.72 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.640725E+11 | 0.00 | 570.00 | 0.327425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46554.98 | 26-NOV-09:03 | 20940.34 | 18-NOV-13:20 | 0.00 | 0.00 | 0.00 |
December | 0.611706E+11 | 0.00 | 589.00 | 0.329165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44549.58 | 24-DEC-09:02 | 20519.01 | 31-DEC-13:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.797416E+12 | 0.00 | 6935.00 | 0.405789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.527113E+11 | 0.00 | 532.00 | 0.310032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38636.66 | 20519.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.775428E+11 | 0.00 | 589.00 | 0.357355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53022.45 | 22724.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.116144E+11 | 0.00 | 716.74 | 0.690711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14992.71 | 08-JAN-09:02 | 12715.08 | 22-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.112709E+11 | 0.00 | 649.13 | 0.696700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14199.85 | 12-FEB-09:02 | 12721.34 | 19-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.126018E+11 | 0.00 | 717.06 | 0.781686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14445.13 | 15-MAR-08:61 | 12755.55 | 24-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.124994E+11 | 0.00 | 694.41 | 0.758995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14349.08 | 10-APR-08:61 | 12713.69 | 21-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.126855E+11 | 0.00 | 717.73 | 0.738938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15074.87 | 17-MAY-15:02 | 12755.46 | 08-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.127269E+11 | 0.00 | 696.29 | 0.757551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14457.25 | 27-JUN-08:62 | 12758.61 | 16-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.111132E+11 | 0.00 | 711.98 | 0.619580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14705.41 | 22-JUL-08:61 | 12707.48 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.113455E+11 | 0.00 | 711.05 | 0.621215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15996.34 | 20-AUG-15:02 | 12763.52 | 10-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.111855E+11 | 0.00 | 691.07 | 0.619364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15838.45 | 18-SEP-08:61 | 12705.98 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.110499E+11 | 0.00 | 712.91 | 0.599426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16027.33 | 30-OCT-18:02 | 12742.28 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.110345E+11 | 0.00 | 692.33 | 0.624267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15416.12 | 26-NOV-09:01 | 12711.47 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.113227E+11 | 0.00 | 716.71 | 0.650790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15288.14 | 24-DEC-09:02 | 12550.16 | 04-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140450E+12 | 0.00 | 8427.41 | 0.815922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.110345E+11 | 0.00 | 649.13 | 0.599426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14199.85 | 12550.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127269E+11 | 0.00 | 717.73 | 0.781686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16027.33 | 12763.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.981755E+10 | 0.00 | 648.43 | 0.554383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17162.90 | 07-JAN-09:11 | 12856.84 | 07-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.995620E+10 | 0.00 | 603.08 | 0.588945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16736.05 | 12-FEB-09:41 | 12774.30 | 07-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.120381E+11 | 0.00 | 708.91 | 0.728838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16086.58 | 15-MAR-08:61 | 12899.87 | 01-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.125628E+11 | 0.00 | 693.91 | 0.762199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15279.41 | 14-APR-17:02 | 12871.14 | 09-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.130374E+11 | 0.00 | 716.51 | 0.769344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16675.00 | 10-MAY-21:51 | 12907.39 | 30-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.133680E+11 | 0.00 | 692.42 | 0.817606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371.48 | 25-JUN-21:51 | 12913.19 | 05-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.114780E+11 | 0.00 | 704.47 | 0.654737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17416.62 | 19-JUL-21:51 | 12865.99 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.114962E+11 | 0.00 | 705.17 | 0.635849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17048.15 | 19-AUG-20:11 | 12903.07 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.109664E+11 | 0.00 | 680.86 | 0.601057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17028.76 | 15-SEP-21:51 | 12915.48 | 15-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.103907E+11 | 0.00 | 695.11 | 0.546769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17892.56 | 23-OCT-08:61 | 12832.00 | 05-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.977156E+10 | 0.00 | 649.91 | 0.525010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16986.63 | 26-NOV-09:51 | 12768.62 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.944758E+10 | 0.00 | 641.93 | 0.513473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17631.50 | 24-DEC-09:41 | 12875.59 | 15-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134330E+12 | 0.00 | 8140.71 | 0.769821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.944758E+10 | 0.00 | 603.08 | 0.513473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15279.41 | 12768.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133680E+11 | 0.00 | 716.51 | 0.817606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17892.56 | 12915.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.682655E+11 | 0.00 | 744.00 | 0.409889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45765.79 | 04-JAN-14:50 | 39030.16 | 04-JAN-12:30 | 0.00 | 0.00 | 0.00 |
February | 0.612694E+11 | 0.00 | 672.00 | 0.356108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40154.29 | 04-FEB-09:00 | 32828.42 | 04-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.598392E+11 | 0.00 | 744.00 | 0.299571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35857.33 | 11-MAR-09:00 | 22693.40 | 11-MAR-09:00 | 0.00 | 0.00 | 0.00 |
April | 0.544740E+11 | 0.00 | 719.67 | 0.241838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34137.42 | 30-APR-08:00 | 20679.57 | 01-APR-20:20 | 0.00 | 0.00 | 0.00 |
May | 0.572796E+11 | 0.00 | 741.47 | 0.248498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36781.72 | 07-MAY-08:00 | 22604.77 | 06-MAY-08:00 | 0.00 | 0.00 | 0.00 |
June | 0.555225E+11 | 0.00 | 719.00 | 0.240215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35417.50 | 10-JUN-08:00 | 20923.39 | 13-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.505257E+11 | 0.00 | 742.67 | 0.207553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31611.20 | 15-JUL-08:00 | 18502.11 | 15-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.508613E+11 | 0.00 | 738.06 | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34035.04 | 13-AUG-08:00 | 18361.63 | 14-AUG-20:50 | 0.00 | 0.00 | 0.00 |
September | 0.531499E+11 | 0.00 | 717.97 | 0.226251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33871.41 | 03-SEP-08:00 | 19670.25 | 27-SEP-20:30 | 0.00 | 0.00 | 0.00 |
October | 0.570858E+11 | 0.00 | 740.94 | 0.258722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38927.38 | 29-OCT-08:00 | 25355.99 | 29-OCT-08:00 | 0.00 | 0.00 | 0.00 |
November | 0.622930E+11 | 0.00 | 718.83 | 0.333394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43930.14 | 23-NOV-09:00 | 34743.41 | 23-NOV-09:00 | 0.00 | 0.00 | 0.00 |
December | 0.678043E+11 | 0.00 | 743.67 | 0.401037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45581.59 | 31-DEC-08:55 | 38859.77 | 07-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698370E+12 | 0.00 | 8742.28 | 0.342216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.505257E+11 | 0.00 | 672.00 | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31611.20 | 18361.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.682655E+11 | 0.00 | 744.00 | 0.409889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45765.79 | 39030.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.671628E+11 | 0.00 | 595.29 | 0.391155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108654.06 | 07-JAN-09:11 | 87537.64 | 25-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.651043E+11 | 0.00 | 557.31 | 0.387476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104187.43 | 12-FEB-09:41 | 86874.10 | 22-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.766548E+11 | 0.00 | 650.79 | 0.468218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107494.51 | 15-MAR-08:61 | 87596.07 | 19-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.810637E+11 | 0.00 | 642.01 | 0.509365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101550.71 | 14-APR-15:02 | 87673.73 | 24-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.904386E+11 | 0.00 | 676.24 | 0.576823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106041.92 | 17-MAY-15:02 | 87568.04 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.937312E+11 | 0.00 | 665.79 | 0.612664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113893.95 | 25-JUN-21:51 | 87715.19 | 19-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.847787E+11 | 0.00 | 656.88 | 0.540811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114256.37 | 19-JUL-21:51 | 87515.55 | 12-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.808439E+11 | 0.00 | 650.29 | 0.490429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114296.10 | 19-AUG-20:11 | 87008.24 | 01-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.754475E+11 | 0.00 | 624.08 | 0.449206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113355.75 | 15-SEP-18:41 | 87408.44 | 12-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.731223E+11 | 0.00 | 633.03 | 0.423997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115470.44 | 23-OCT-08:61 | 87002.84 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.684286E+11 | 0.00 | 596.70 | 0.398431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110917.39 | 26-NOV-09:51 | 87355.39 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.659954E+11 | 0.00 | 591.16 | 0.377338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114276.28 | 20-DEC-09:02 | 87321.38 | 19-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922772E+12 | 0.00 | 7539.58 | 0.562591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.651043E+11 | 0.00 | 557.31 | 0.377338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101550.71 | 86874.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.937312E+11 | 0.00 | 676.24 | 0.612664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115470.44 | 87715.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.116032E+11 | 0.00 | 724.99 | 0.697734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12859.99 | 08-JAN-09:02 | 11309.31 | 29-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.113430E+11 | 0.00 | 657.83 | 0.714682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12057.17 | 08-FEB-09:02 | 11310.14 | 02-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.125511E+11 | 0.00 | 727.93 | 0.792083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12354.74 | 15-MAR-08:61 | 11297.19 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.125535E+11 | 0.00 | 704.61 | 0.782572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12426.16 | 14-APR-18:02 | 11330.82 | 22-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.127567E+11 | 0.00 | 724.29 | 0.768468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13702.93 | 17-MAY-15:02 | 11327.30 | 05-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.127544E+11 | 0.00 | 703.95 | 0.775723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12737.31 | 01-JUN-08:61 | 11333.08 | 19-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.110940E+11 | 0.00 | 720.06 | 0.631011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12802.27 | 22-JUL-08:61 | 11333.19 | 09-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.113640E+11 | 0.00 | 719.26 | 0.635457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14205.99 | 20-AUG-15:02 | 11343.47 | 28-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.112652E+11 | 0.00 | 699.21 | 0.644191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13869.59 | 18-SEP-08:61 | 11182.30 | 02-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.110449E+11 | 0.00 | 719.42 | 0.614402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14220.75 | 30-OCT-18:02 | 11336.55 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.110397E+11 | 0.00 | 699.13 | 0.636290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13617.69 | 26-NOV-09:01 | 11327.52 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.113176E+11 | 0.00 | 723.69 | 0.661648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13069.85 | 14-DEC-09:02 | 11267.41 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140687E+12 | 0.00 | 8524.38 | 0.835426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.110397E+11 | 0.00 | 657.83 | 0.614402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12057.17 | 11182.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127567E+11 | 0.00 | 727.93 | 0.792083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14220.75 | 11343.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.971816E+10 | 0.00 | 655.25 | 0.547681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15870.57 | 07-JAN-09:11 | 11368.83 | 15-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.996458E+10 | 0.00 | 610.62 | 0.593444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15485.15 | 12-FEB-09:41 | 11763.32 | 24-FEB-09:11 | 0.00 | 0.00 | 0.00 |
March | 0.119807E+11 | 0.00 | 720.20 | 0.732953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.44 | 15-MAR-07:33 | 11385.71 | 18-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.126110E+11 | 0.00 | 704.05 | 0.784699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13448.96 | 14-APR-17:02 | 11427.63 | 27-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.131083E+11 | 0.00 | 721.80 | 0.801822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14647.79 | 10-MAY-21:51 | 11439.01 | 07-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.133958E+11 | 0.00 | 697.61 | 0.844939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15307.29 | 25-JUN-21:51 | 11448.92 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.114619E+11 | 0.00 | 711.73 | 0.667398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15248.06 | 19-JUL-21:51 | 11424.80 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.115134E+11 | 0.00 | 713.35 | 0.650534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15150.59 | 19-AUG-20:11 | 11428.95 | 28-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.110440E+11 | 0.00 | 688.84 | 0.625805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15085.52 | 15-SEP-21:51 | 11319.47 | 13-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.103877E+11 | 0.00 | 701.10 | 0.562645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15924.24 | 23-OCT-08:61 | 11367.84 | 08-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.975924E+10 | 0.00 | 656.13 | 0.535364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15338.25 | 02-NOV-07:42 | 11395.82 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.936123E+10 | 0.00 | 646.31 | 0.515319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16080.96 | 24-DEC-09:41 | 11313.06 | 20-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134306E+12 | 0.00 | 8226.99 | 0.786260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.936123E+10 | 0.00 | 610.62 | 0.515319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13448.96 | 11313.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133958E+11 | 0.00 | 721.80 | 0.844939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16080.96 | 11763.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.296649E+10 | 0.00 | 718.19 | 0.174635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4278.08 | 08-JAN-09:02 | 3464.46 | 14-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.286600E+10 | 0.00 | 650.91 | 0.173551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4006.58 | 12-FEB-09:02 | 3456.56 | 11-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.325419E+10 | 0.00 | 718.30 | 0.198568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4168.23 | 15-MAR-08:61 | 3465.75 | 23-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.326082E+10 | 0.00 | 696.05 | 0.194857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4089.04 | 10-APR-08:61 | 3459.44 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.326223E+10 | 0.00 | 717.77 | 0.185835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4210.09 | 26-MAY-08:61 | 3453.48 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.324716E+10 | 0.00 | 696.56 | 0.187551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4141.83 | 27-JUN-08:62 | 3474.06 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.285100E+10 | 0.00 | 712.43 | 0.153937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.75 | 22-JUL-08:61 | 3474.56 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.292590E+10 | 0.00 | 712.21 | 0.155962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4480.37 | 19-AUG-18:02 | 3486.42 | 05-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.290796E+10 | 0.00 | 692.14 | 0.158185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.65 | 18-SEP-08:61 | 3480.49 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.283941E+10 | 0.00 | 713.70 | 0.150177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.85 | 30-OCT-18:02 | 3479.43 | 12-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.281715E+10 | 0.00 | 694.15 | 0.155921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4439.30 | 26-NOV-09:01 | 3443.65 | 03-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.287484E+10 | 0.00 | 717.99 | 0.163972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.14 | 24-DEC-09:02 | 3470.22 | 13-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360731E+11 | 0.00 | 8440.41 | 0.205315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.281715E+10 | 0.00 | 650.91 | 0.150177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4006.58 | 3443.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.326223E+10 | 0.00 | 718.30 | 0.198568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.65 | 3486.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.252071E+10 | 0.00 | 650.63 | 0.139768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4859.23 | 07-JAN-09:11 | 3509.70 | 14-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.254554E+10 | 0.00 | 604.72 | 0.149009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4672.50 | 12-FEB-09:41 | 3508.52 | 19-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.311341E+10 | 0.00 | 709.00 | 0.186553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4592.38 | 15-MAR-08:61 | 3524.68 | 23-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.327764E+10 | 0.00 | 695.60 | 0.195710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213.09 | 14-APR-17:02 | 3537.75 | 14-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.335691E+10 | 0.00 | 716.50 | 0.193991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4595.54 | 10-MAY-21:51 | 3509.99 | 23-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.342100E+10 | 0.00 | 692.65 | 0.204162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4913.50 | 25-JUN-21:51 | 3502.92 | 03-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.295019E+10 | 0.00 | 704.33 | 0.163918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.48 | 19-JUL-21:51 | 3509.43 | 16-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.296615E+10 | 0.00 | 707.17 | 0.159745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.57 | 19-AUG-20:11 | 3513.87 | 25-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.285417E+10 | 0.00 | 682.06 | 0.153419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4824.28 | 15-SEP-21:51 | 3509.78 | 24-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.267341E+10 | 0.00 | 695.39 | 0.136013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.18 | 23-OCT-08:61 | 3511.24 | 18-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.250026E+10 | 0.00 | 651.25 | 0.129827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4800.97 | 26-NOV-09:51 | 3514.64 | 03-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.241016E+10 | 0.00 | 644.14 | 0.128058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5004.18 | 24-DEC-09:41 | 3501.16 | 02-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345895E+11 | 0.00 | 8153.45 | 0.194017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.241016E+10 | 0.00 | 604.72 | 0.128058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213.09 | 3501.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.342100E+10 | 0.00 | 716.50 | 0.204162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.18 | 3537.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.177393E+11 | 0.00 | 723.95 | 0.119425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16941.89 | 08-JAN-09:02 | 14255.79 | 14-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.159786E+11 | 0.00 | 653.89 | 0.107852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15712.89 | 08-FEB-09:02 | 14248.45 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.161371E+11 | 0.00 | 716.59 | 0.104693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16376.31 | 15-MAR-08:61 | 14277.75 | 22-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.150556E+11 | 0.00 | 690.89 | 0.925836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15827.34 | 10-APR-08:61 | 14290.23 | 26-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.156434E+11 | 0.00 | 713.64 | 0.938315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16591.84 | 17-MAY-15:02 | 14284.46 | 06-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.152178E+11 | 0.00 | 691.21 | 0.908837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16350.95 | 27-JUN-08:62 | 14285.10 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.139699E+11 | 0.00 | 710.05 | 0.806553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16768.45 | 22-JUL-08:61 | 14274.24 | 15-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.140766E+11 | 0.00 | 708.07 | 0.791307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19716.86 | 19-AUG-18:02 | 14226.80 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.144637E+11 | 0.00 | 689.77 | 0.845506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18787.85 | 18-SEP-08:61 | 14265.01 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.152766E+11 | 0.00 | 714.82 | 0.914280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19276.31 | 30-OCT-18:02 | 14137.81 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.162708E+11 | 0.00 | 698.18 | 0.103860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17960.97 | 26-NOV-09:01 | 14291.17 | 19-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.175630E+11 | 0.00 | 724.77 | 0.115690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17231.06 | 14-DEC-09:02 | 14253.50 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187392E+12 | 0.00 | 8435.84 | 0.116458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.139699E+11 | 0.00 | 653.89 | 0.791307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15712.89 | 14137.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.177393E+11 | 0.00 | 724.77 | 0.119425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19716.86 | 14291.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.91 | 157.79 | 221.13 | 815.82 | 53.54 | 0.00 | 0.00 | 0.00 |
February | 320.52 | 103.37 | 217.15 | 736.71 | 40.43 | 0.00 | 0.00 | 0.00 |
March | 223.51 | 33.17 | 190.34 | 566.63 | 20.86 | 0.00 | 0.00 | 0.00 |
April | 165.70 | 0.95 | 164.74 | 454.67 | 2.71 | 0.00 | 0.00 | 0.00 |
May | 164.05 | 0.00 | 164.05 | 471.16 | 6.08 | 0.00 | 0.00 | 0.00 |
June | 163.46 | 0.00 | 163.46 | 457.61 | 7.16 | 0.00 | 0.00 | 0.00 |
July | 168.39 | 0.00 | 168.39 | 419.20 | 16.46 | 0.00 | 0.00 | 0.00 |
August | 163.72 | 0.01 | 163.71 | 413.02 | 7.84 | 0.00 | 0.00 | 0.00 |
September | 180.67 | 4.95 | 175.72 | 455.29 | 9.14 | 0.00 | 0.00 | 0.00 |
October | 235.29 | 35.70 | 199.59 | 546.64 | 14.20 | 0.00 | 0.00 | 0.00 |
November | 310.57 | 95.95 | 214.61 | 681.25 | 28.10 | 0.00 | 0.00 | 0.00 |
December | 380.24 | 162.30 | 217.94 | 805.08 | 61.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.60 | 49.34 | 188.26 | 567.83 | 22.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.46 | 0.00 | 163.46 | 413.02 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 380.24 | 162.30 | 221.13 | 815.82 | 61.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1066.99 | 444.32 | 622.68 | 2288.14 | 153.98 | 0.00 | 0.00 | 0.00 |
February | 902.57 | 291.08 | 611.49 | 2072.87 | 111.14 | 0.00 | 0.00 | 0.00 |
March | 629.40 | 93.41 | 535.99 | 1611.44 | 57.29 | 0.00 | 0.00 | 0.00 |
April | 466.60 | 2.69 | 463.91 | 1310.41 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 461.95 | 0.00 | 461.95 | 1346.84 | 21.85 | 0.00 | 0.00 | 0.00 |
June | 460.29 | 0.00 | 460.29 | 1316.67 | 22.79 | 0.00 | 0.00 | 0.00 |
July | 474.16 | 0.00 | 474.16 | 1197.48 | 53.07 | 0.00 | 0.00 | 0.00 |
August | 461.03 | 0.04 | 460.99 | 1174.23 | 29.52 | 0.00 | 0.00 | 0.00 |
September | 508.76 | 13.94 | 494.81 | 1298.09 | 33.45 | 0.00 | 0.00 | 0.00 |
October | 662.57 | 100.54 | 562.03 | 1541.28 | 50.95 | 0.00 | 0.00 | 0.00 |
November | 874.53 | 270.20 | 604.34 | 1915.96 | 87.80 | 0.00 | 0.00 | 0.00 |
December | 1070.73 | 457.02 | 613.71 | 2257.01 | 179.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 669.07 | 138.93 | 530.13 | 1608.72 | 67.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.29 | 0.00 | 460.29 | 1174.23 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1070.73 | 457.02 | 622.68 | 2288.14 | 179.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1386.08 | 577.19 | 808.89 | 3106.15 | 173.68 | 0.00 | 0.00 | 0.00 |
February | 1172.49 | 378.13 | 794.36 | 2820.28 | 123.85 | 0.00 | 0.00 | 0.00 |
March | 817.62 | 121.34 | 696.28 | 2197.10 | 60.30 | 0.00 | 0.00 | 0.00 |
April | 606.13 | 3.49 | 602.65 | 1779.55 | 11.75 | 0.00 | 0.00 | 0.00 |
May | 600.10 | 0.00 | 600.10 | 1803.84 | 26.58 | 0.00 | 0.00 | 0.00 |
June | 597.94 | 0.00 | 597.94 | 1749.98 | 30.21 | 0.00 | 0.00 | 0.00 |
July | 615.96 | 0.00 | 615.96 | 1589.45 | 67.21 | 0.00 | 0.00 | 0.00 |
August | 598.91 | 0.05 | 598.85 | 1570.56 | 34.67 | 0.00 | 0.00 | 0.00 |
September | 660.90 | 18.11 | 642.79 | 1756.34 | 35.67 | 0.00 | 0.00 | 0.00 |
October | 860.71 | 130.60 | 730.11 | 2088.84 | 50.01 | 0.00 | 0.00 | 0.00 |
November | 1136.07 | 351.00 | 785.07 | 2603.13 | 94.69 | 0.00 | 0.00 | 0.00 |
December | 1390.94 | 593.70 | 797.25 | 3059.45 | 206.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 869.15 | 180.48 | 688.67 | 2174.01 | 76.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.94 | 0.00 | 597.94 | 1570.56 | 11.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1390.94 | 593.70 | 808.89 | 3106.15 | 206.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 175.05 | 3.82 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 161.19 | 1.33 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 131.13 | 0.25 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.52 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.24 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 111.14 | 0.06 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.50 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.53 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 106.62 | 0.03 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 122.65 | 0.09 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 148.98 | 0.76 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 171.51 | 4.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.84 | 0.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.50 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 175.05 | 4.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 246.91 | 7.37 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 276.15 | 2.54 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 319.07 | 0.43 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 335.81 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 303.94 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 318.26 | 0.09 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 257.08 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 275.64 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 265.29 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 238.81 | 0.20 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 229.41 | 1.53 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 227.76 | 9.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 274.36 | 1.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 227.76 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 335.81 | 9.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.80 | 3.87 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.82 | 1.32 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.36 | 0.23 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.43 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.68 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.66 | 0.14 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.91 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.39 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.93 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.93 | 0.16 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.77 | 1.06 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 74.48 | 5.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 104.47 | 1.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 74.48 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.66 | 5.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 247.80 | 7.11 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 276.78 | 2.40 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 320.00 | 0.40 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 335.56 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 303.02 | 0.17 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 316.39 | 0.25 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 255.84 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 274.93 | 0.17 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 265.23 | 0.18 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 239.47 | 0.27 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 230.53 | 1.92 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 228.50 | 9.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 274.35 | 1.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 228.50 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 335.56 | 9.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.92 | 24.95 | 34.97 | 119.02 | 17.76 | 0.00 | 0.00 | 0.00 |
February | 50.69 | 16.35 | 34.34 | 107.50 | 14.49 | 0.00 | 0.00 | 0.00 |
March | 35.35 | 5.25 | 30.10 | 80.29 | 10.91 | 0.00 | 0.00 | 0.00 |
April | 26.20 | 0.15 | 26.05 | 60.39 | 5.78 | 0.00 | 0.00 | 0.00 |
May | 25.94 | 0.00 | 25.94 | 61.32 | 6.44 | 0.00 | 0.00 | 0.00 |
June | 25.85 | 0.00 | 25.85 | 60.77 | 6.77 | 0.00 | 0.00 | 0.00 |
July | 26.63 | 0.00 | 26.63 | 54.40 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 25.89 | 0.00 | 25.89 | 52.18 | 9.99 | 0.00 | 0.00 | 0.00 |
September | 28.57 | 0.78 | 27.79 | 60.38 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 37.21 | 5.65 | 31.56 | 74.14 | 12.37 | 0.00 | 0.00 | 0.00 |
November | 49.11 | 15.17 | 33.94 | 97.25 | 14.11 | 0.00 | 0.00 | 0.00 |
December | 60.13 | 25.67 | 34.47 | 117.65 | 19.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.57 | 7.80 | 29.77 | 78.64 | 11.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 52.18 | 5.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.13 | 25.67 | 34.97 | 119.02 | 19.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.67 | 0.00 | 22.67 | 67.72 | 2.30 | 0.00 | 0.00 | 0.00 |
February | 24.18 | 0.00 | 24.18 | 75.86 | 0.47 | 0.00 | 0.00 | 0.00 |
March | 24.84 | 0.00 | 24.84 | 86.06 | 0.07 | 0.00 | 0.00 | 0.00 |
April | 27.53 | 0.66 | 26.86 | 98.96 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34.53 | 3.60 | 30.94 | 116.02 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 42.43 | 8.68 | 33.75 | 132.02 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 3.87 | 32.57 | 104.88 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 30.13 | 1.41 | 28.71 | 92.96 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 25.56 | 0.04 | 25.51 | 83.83 | 0.02 | 0.00 | 0.00 | 0.00 |
October | 24.57 | 0.00 | 24.57 | 75.51 | 0.01 | 0.00 | 0.00 | 0.00 |
November | 23.24 | 0.00 | 23.24 | 70.24 | 0.46 | 0.00 | 0.00 | 0.00 |
December | 22.03 | 0.00 | 22.03 | 63.76 | 3.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.19 | 1.53 | 26.67 | 89.01 | 0.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.03 | 0.00 | 22.03 | 63.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.43 | 8.68 | 33.75 | 132.02 | 3.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.99 | 34.38 | 67.60 | 244.36 | 6.99 | 0.00 | 0.00 | 0.00 |
February | 115.59 | 42.34 | 73.25 | 281.58 | 2.43 | 0.00 | 0.00 | 0.00 |
March | 126.21 | 49.40 | 76.81 | 318.63 | 0.42 | 0.00 | 0.00 | 0.00 |
April | 127.32 | 48.57 | 78.75 | 338.33 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 109.60 | 33.22 | 76.38 | 307.84 | 0.05 | 0.00 | 0.00 | 0.00 |
June | 116.66 | 38.41 | 78.25 | 318.40 | 0.07 | 0.00 | 0.00 | 0.00 |
July | 99.77 | 22.40 | 77.37 | 257.05 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 109.67 | 32.24 | 77.43 | 277.59 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 28.10 | 74.93 | 269.07 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 96.67 | 24.80 | 71.86 | 241.42 | 0.16 | 0.00 | 0.00 | 0.00 |
November | 93.58 | 25.89 | 67.69 | 230.05 | 1.43 | 0.00 | 0.00 | 0.00 |
December | 95.66 | 30.72 | 64.93 | 226.65 | 8.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.89 | 34.13 | 73.76 | 275.73 | 1.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.58 | 22.40 | 64.93 | 226.65 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.32 | 49.40 | 78.75 | 338.33 | 8.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 174.87 | 3.72 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 160.97 | 1.27 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 131.06 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.36 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.08 | 0.03 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 110.99 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.37 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.34 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 106.45 | 0.02 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 122.54 | 0.08 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 148.88 | 0.75 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 171.33 | 4.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.69 | 0.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.34 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 174.87 | 4.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.23 | 3.79 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.27 | 1.27 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.23 | 0.21 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.27 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.54 | 0.08 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.52 | 0.12 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.79 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.22 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.74 | 0.09 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.80 | 0.15 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.56 | 1.05 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 73.93 | 4.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 104.22 | 1.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 73.93 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.52 | 4.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.99 | 34.38 | 67.60 | 244.18 | 6.71 | 0.00 | 0.00 | 0.00 |
February | 115.59 | 42.34 | 73.25 | 281.32 | 2.27 | 0.00 | 0.00 | 0.00 |
March | 126.21 | 49.40 | 76.81 | 319.49 | 0.39 | 0.00 | 0.00 | 0.00 |
April | 127.32 | 48.57 | 78.75 | 338.11 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 109.60 | 33.22 | 76.38 | 306.92 | 0.14 | 0.00 | 0.00 | 0.00 |
June | 116.66 | 38.41 | 78.25 | 316.53 | 0.22 | 0.00 | 0.00 | 0.00 |
July | 99.77 | 22.40 | 77.37 | 255.80 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 109.67 | 32.24 | 77.43 | 276.90 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 28.10 | 74.93 | 269.01 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 96.67 | 24.80 | 71.86 | 242.05 | 0.25 | 0.00 | 0.00 | 0.00 |
November | 93.58 | 25.89 | 67.69 | 230.88 | 1.82 | 0.00 | 0.00 | 0.00 |
December | 95.66 | 30.72 | 64.93 | 226.45 | 8.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.89 | 34.13 | 73.76 | 275.45 | 1.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.58 | 22.40 | 64.93 | 226.45 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.32 | 49.40 | 78.75 | 338.11 | 8.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.89 | 0.00 | 35.89 | 96.66 | 8.53 | 0.00 | 0.00 | 0.00 |
February | 38.28 | 0.00 | 38.28 | 106.46 | 5.08 | 0.00 | 0.00 | 0.00 |
March | 39.31 | 0.00 | 39.31 | 119.67 | 1.55 | 0.00 | 0.00 | 0.00 |
April | 43.57 | 1.05 | 42.52 | 139.70 | 0.20 | 0.00 | 0.00 | 0.00 |
May | 54.66 | 5.69 | 48.97 | 166.34 | 0.62 | 0.00 | 0.00 | 0.00 |
June | 67.17 | 13.75 | 53.42 | 190.27 | 0.76 | 0.00 | 0.00 | 0.00 |
July | 57.67 | 6.12 | 51.55 | 153.34 | 1.37 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 2.24 | 45.45 | 134.30 | 0.51 | 0.00 | 0.00 | 0.00 |
September | 40.45 | 0.07 | 40.38 | 119.91 | 0.61 | 0.00 | 0.00 | 0.00 |
October | 38.88 | 0.00 | 38.88 | 106.99 | 1.01 | 0.00 | 0.00 | 0.00 |
November | 36.79 | 0.00 | 36.79 | 99.20 | 3.38 | 0.00 | 0.00 | 0.00 |
December | 34.86 | 0.00 | 34.86 | 91.90 | 10.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.63 | 2.42 | 42.21 | 127.12 | 2.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.86 | 0.00 | 34.86 | 91.90 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.17 | 13.75 | 53.42 | 190.27 | 10.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.23 | 0.00 | 13.23 | 35.63 | 3.15 | 0.00 | 0.00 | 0.00 |
February | 14.11 | 0.00 | 14.11 | 39.25 | 1.87 | 0.00 | 0.00 | 0.00 |
March | 14.49 | 0.00 | 14.49 | 44.12 | 0.57 | 0.00 | 0.00 | 0.00 |
April | 16.06 | 0.39 | 15.67 | 51.50 | 0.07 | 0.00 | 0.00 | 0.00 |
May | 20.15 | 2.10 | 18.05 | 61.32 | 0.23 | 0.00 | 0.00 | 0.00 |
June | 24.76 | 5.07 | 19.69 | 70.14 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 21.26 | 2.26 | 19.00 | 56.53 | 0.50 | 0.00 | 0.00 | 0.00 |
August | 17.58 | 0.83 | 16.75 | 49.51 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 14.91 | 0.03 | 14.89 | 44.20 | 0.22 | 0.00 | 0.00 | 0.00 |
October | 14.33 | 0.00 | 14.33 | 39.44 | 0.37 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 36.57 | 1.25 | 0.00 | 0.00 | 0.00 |
December | 12.85 | 0.00 | 12.85 | 33.88 | 3.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.45 | 0.89 | 15.56 | 46.86 | 1.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.85 | 0.00 | 12.85 | 33.88 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.76 | 5.07 | 19.69 | 70.14 | 3.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.96 | 14.56 | 20.40 | 80.58 | 2.99 | 0.00 | 0.00 | 0.00 |
February | 29.57 | 9.54 | 20.03 | 73.45 | 1.79 | 0.00 | 0.00 | 0.00 |
March | 20.62 | 3.06 | 17.56 | 59.08 | 0.57 | 0.00 | 0.00 | 0.00 |
April | 15.29 | 0.09 | 15.20 | 49.60 | 0.07 | 0.00 | 0.00 | 0.00 |
May | 15.13 | 0.00 | 15.13 | 49.68 | 0.23 | 0.00 | 0.00 | 0.00 |
June | 15.08 | 0.00 | 15.08 | 47.98 | 0.29 | 0.00 | 0.00 | 0.00 |
July | 15.53 | 0.00 | 15.53 | 43.44 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 15.10 | 0.00 | 15.10 | 43.80 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 16.67 | 0.46 | 16.21 | 48.21 | 0.21 | 0.00 | 0.00 | 0.00 |
October | 21.71 | 3.29 | 18.41 | 55.71 | 0.35 | 0.00 | 0.00 | 0.00 |
November | 28.65 | 8.85 | 19.80 | 68.06 | 1.17 | 0.00 | 0.00 | 0.00 |
December | 35.08 | 14.97 | 20.11 | 79.15 | 3.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.92 | 4.55 | 17.37 | 58.16 | 1.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 0.00 | 15.08 | 43.44 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.08 | 14.97 | 20.40 | 80.58 | 3.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.88 | 39.51 | 55.37 | 218.71 | 8.12 | 0.00 | 0.00 | 0.00 |
February | 80.26 | 25.88 | 54.38 | 199.35 | 4.87 | 0.00 | 0.00 | 0.00 |
March | 55.97 | 8.31 | 47.66 | 160.36 | 1.54 | 0.00 | 0.00 | 0.00 |
April | 41.49 | 0.24 | 41.25 | 134.63 | 0.19 | 0.00 | 0.00 | 0.00 |
May | 41.08 | 0.00 | 41.08 | 134.85 | 0.64 | 0.00 | 0.00 | 0.00 |
June | 40.93 | 0.00 | 40.93 | 130.24 | 0.78 | 0.00 | 0.00 | 0.00 |
July | 42.16 | 0.00 | 42.16 | 117.91 | 1.39 | 0.00 | 0.00 | 0.00 |
August | 41.00 | 0.00 | 40.99 | 118.87 | 0.52 | 0.00 | 0.00 | 0.00 |
September | 45.24 | 1.24 | 44.00 | 130.84 | 0.58 | 0.00 | 0.00 | 0.00 |
October | 58.92 | 8.94 | 49.98 | 151.21 | 0.94 | 0.00 | 0.00 | 0.00 |
November | 77.76 | 24.03 | 53.74 | 184.72 | 3.18 | 0.00 | 0.00 | 0.00 |
December | 95.21 | 40.64 | 54.57 | 214.84 | 9.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.49 | 12.35 | 47.14 | 157.85 | 2.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.93 | 0.00 | 40.93 | 117.91 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.21 | 40.64 | 55.37 | 218.71 | 9.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 173.67 | 3.21 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 160.28 | 0.88 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 131.00 | 0.12 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.53 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.22 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 111.30 | 0.03 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.00 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.23 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 105.90 | 0.01 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 121.73 | 0.04 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 147.85 | 0.52 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 169.96 | 4.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.23 | 0.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 173.67 | 4.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 244.68 | 6.17 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 274.37 | 1.68 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 317.68 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 334.21 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 302.83 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 317.33 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 255.33 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 274.06 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 263.28 | 0.01 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 237.01 | 0.09 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 227.61 | 1.03 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 225.33 | 8.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 272.66 | 1.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 225.33 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 334.21 | 8.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.16 | 3.23 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.48 | 0.87 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.25 | 0.12 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.05 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.18 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.05 | 0.13 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.02 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 108.78 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.22 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.34 | 0.14 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.24 | 0.85 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 73.74 | 4.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 103.91 | 0.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 73.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.05 | 4.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 245.85 | 5.92 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 275.23 | 1.55 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 318.65 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 333.93 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 301.86 | 0.16 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 315.40 | 0.24 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 254.05 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 273.32 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 263.21 | 0.21 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 237.69 | 0.24 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 228.90 | 1.54 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 226.40 | 7.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 272.72 | 1.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 226.40 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 333.93 | 7.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.87 | 45.75 | 64.12 | 256.22 | 4.43 | 0.00 | 0.00 | 0.00 |
February | 92.94 | 29.97 | 62.97 | 238.09 | 1.03 | 0.00 | 0.00 | 0.00 |
March | 64.81 | 9.62 | 55.19 | 197.76 | 0.13 | 0.00 | 0.00 | 0.00 |
April | 48.05 | 0.28 | 47.77 | 170.58 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47.57 | 0.00 | 47.57 | 172.12 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 47.40 | 0.00 | 47.40 | 169.76 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 48.83 | 0.00 | 48.83 | 147.42 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 47.48 | 0.00 | 47.47 | 148.26 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 52.39 | 1.44 | 50.95 | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68.23 | 10.35 | 57.88 | 182.05 | 0.03 | 0.00 | 0.00 | 0.00 |
November | 90.06 | 27.82 | 62.23 | 219.04 | 0.61 | 0.00 | 0.00 | 0.00 |
December | 110.26 | 47.06 | 63.20 | 250.31 | 5.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.90 | 14.31 | 54.59 | 192.43 | 1.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.40 | 0.00 | 47.40 | 147.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.26 | 47.06 | 64.12 | 256.22 | 5.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.34 | 0.00 | 198.34 | 491.35 | 72.38 | 0.00 | 0.00 | 0.00 |
February | 211.58 | 0.00 | 211.58 | 549.41 | 48.68 | 0.00 | 0.00 | 0.00 |
March | 217.29 | 0.01 | 217.28 | 600.79 | 23.48 | 0.00 | 0.00 | 0.00 |
April | 240.82 | 5.80 | 235.01 | 693.24 | 5.61 | 0.00 | 0.00 | 0.00 |
May | 302.12 | 31.47 | 270.65 | 845.98 | 12.31 | 0.00 | 0.00 | 0.00 |
June | 371.24 | 75.98 | 295.26 | 985.93 | 13.14 | 0.00 | 0.00 | 0.00 |
July | 318.75 | 33.82 | 284.93 | 777.87 | 28.50 | 0.00 | 0.00 | 0.00 |
August | 263.57 | 12.38 | 251.20 | 660.91 | 17.29 | 0.00 | 0.00 | 0.00 |
September | 223.59 | 0.39 | 223.20 | 586.80 | 18.79 | 0.00 | 0.00 | 0.00 |
October | 214.91 | 0.00 | 214.91 | 524.71 | 28.06 | 0.00 | 0.00 | 0.00 |
November | 203.35 | 0.00 | 203.35 | 499.06 | 42.05 | 0.00 | 0.00 | 0.00 |
December | 192.69 | 0.00 | 192.69 | 469.91 | 86.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 13.35 | 233.31 | 640.69 | 33.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 192.69 | 0.00 | 192.69 | 469.91 | 5.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.24 | 75.98 | 295.26 | 985.93 | 86.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.34 | 0.00 | 198.34 | 479.93 | 78.01 | 0.00 | 0.00 | 0.00 |
February | 211.58 | 0.00 | 211.58 | 538.12 | 53.31 | 0.00 | 0.00 | 0.00 |
March | 217.29 | 0.01 | 217.28 | 587.84 | 27.27 | 0.00 | 0.00 | 0.00 |
April | 240.82 | 5.80 | 235.01 | 678.07 | 6.81 | 0.00 | 0.00 | 0.00 |
May | 302.12 | 31.47 | 270.65 | 831.68 | 14.50 | 0.00 | 0.00 | 0.00 |
June | 371.24 | 75.98 | 295.26 | 972.31 | 15.20 | 0.00 | 0.00 | 0.00 |
July | 318.75 | 33.82 | 284.93 | 764.71 | 32.91 | 0.00 | 0.00 | 0.00 |
August | 263.57 | 12.38 | 251.20 | 645.42 | 21.29 | 0.00 | 0.00 | 0.00 |
September | 223.59 | 0.39 | 223.20 | 572.72 | 22.84 | 0.00 | 0.00 | 0.00 |
October | 214.91 | 0.00 | 214.91 | 511.20 | 33.65 | 0.00 | 0.00 | 0.00 |
November | 203.35 | 0.00 | 203.35 | 487.10 | 47.62 | 0.00 | 0.00 | 0.00 |
December | 192.69 | 0.00 | 192.69 | 458.72 | 93.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 13.35 | 233.31 | 627.50 | 37.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 192.69 | 0.00 | 192.69 | 458.72 | 6.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.24 | 75.98 | 295.26 | 972.31 | 93.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 87.41 | 9.80 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 95.92 | 6.72 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 101.97 | 3.72 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 116.07 | 1.04 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.49 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 159.14 | 2.02 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 130.09 | 3.73 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.49 | 2.60 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 101.71 | 2.83 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 90.33 | 3.88 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 89.16 | 5.52 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 84.60 | 11.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 108.63 | 4.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 84.60 | 1.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 159.14 | 11.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.96 | 68.76 | 135.19 | 521.21 | 36.44 | 0.00 | 0.00 | 0.00 |
February | 231.16 | 84.67 | 146.49 | 592.90 | 25.25 | 0.00 | 0.00 | 0.00 |
March | 252.39 | 98.79 | 153.60 | 643.76 | 13.91 | 0.00 | 0.00 | 0.00 |
April | 254.63 | 97.13 | 157.50 | 675.55 | 3.95 | 0.00 | 0.00 | 0.00 |
May | 219.18 | 66.43 | 152.76 | 610.62 | 7.16 | 0.00 | 0.00 | 0.00 |
June | 233.31 | 76.82 | 156.49 | 637.00 | 7.69 | 0.00 | 0.00 | 0.00 |
July | 199.52 | 44.79 | 154.73 | 530.85 | 14.07 | 0.00 | 0.00 | 0.00 |
August | 219.33 | 64.47 | 154.86 | 553.34 | 9.87 | 0.00 | 0.00 | 0.00 |
September | 206.05 | 56.20 | 149.85 | 550.99 | 10.66 | 0.00 | 0.00 | 0.00 |
October | 193.32 | 49.60 | 143.71 | 490.90 | 14.77 | 0.00 | 0.00 | 0.00 |
November | 187.15 | 51.78 | 135.36 | 487.99 | 20.76 | 0.00 | 0.00 | 0.00 |
December | 191.30 | 61.44 | 129.86 | 491.77 | 43.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.77 | 68.25 | 147.52 | 565.11 | 17.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.15 | 44.79 | 129.86 | 487.99 | 3.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.63 | 98.79 | 157.50 | 675.55 | 43.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 184.00 | 9.67 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 169.30 | 6.70 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 133.44 | 3.70 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.71 | 1.05 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 112.11 | 1.89 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 110.87 | 2.05 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 102.12 | 3.77 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 96.75 | 2.62 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 110.23 | 2.82 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 125.15 | 3.88 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 156.84 | 5.49 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 182.08 | 11.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 132.70 | 4.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 96.75 | 1.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 184.00 | 11.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.89 | 0.00 | 35.89 | 89.05 | 10.83 | 0.00 | 0.00 | 0.00 |
February | 38.28 | 0.00 | 38.28 | 99.02 | 7.10 | 0.00 | 0.00 | 0.00 |
March | 39.31 | 0.00 | 39.31 | 110.20 | 2.55 | 0.00 | 0.00 | 0.00 |
April | 43.57 | 1.05 | 42.52 | 128.46 | 0.40 | 0.00 | 0.00 | 0.00 |
May | 54.66 | 5.69 | 48.97 | 157.01 | 1.16 | 0.00 | 0.00 | 0.00 |
June | 67.17 | 13.75 | 53.42 | 181.79 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 57.67 | 6.12 | 51.55 | 144.62 | 2.82 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 2.24 | 45.45 | 125.40 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 40.45 | 0.07 | 40.38 | 109.79 | 1.41 | 0.00 | 0.00 | 0.00 |
October | 38.88 | 0.00 | 38.88 | 98.50 | 2.09 | 0.00 | 0.00 | 0.00 |
November | 36.79 | 0.00 | 36.79 | 91.49 | 5.09 | 0.00 | 0.00 | 0.00 |
December | 34.86 | 0.00 | 34.86 | 85.36 | 12.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.63 | 2.42 | 42.21 | 118.45 | 4.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.86 | 0.00 | 34.86 | 85.36 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.17 | 13.75 | 53.42 | 181.79 | 12.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.11 | 0.00 | 32.11 | 79.67 | 9.69 | 0.00 | 0.00 | 0.00 |
February | 34.25 | 0.00 | 34.25 | 88.59 | 6.36 | 0.00 | 0.00 | 0.00 |
March | 35.17 | 0.00 | 35.17 | 98.60 | 2.28 | 0.00 | 0.00 | 0.00 |
April | 38.98 | 0.94 | 38.04 | 114.93 | 0.36 | 0.00 | 0.00 | 0.00 |
May | 48.91 | 5.09 | 43.81 | 140.48 | 1.03 | 0.00 | 0.00 | 0.00 |
June | 60.09 | 12.30 | 47.80 | 162.65 | 1.24 | 0.00 | 0.00 | 0.00 |
July | 51.60 | 5.47 | 46.12 | 129.39 | 2.52 | 0.00 | 0.00 | 0.00 |
August | 42.67 | 2.00 | 40.66 | 112.19 | 0.93 | 0.00 | 0.00 | 0.00 |
September | 36.19 | 0.06 | 36.13 | 98.23 | 1.26 | 0.00 | 0.00 | 0.00 |
October | 34.79 | 0.00 | 34.79 | 88.13 | 1.87 | 0.00 | 0.00 | 0.00 |
November | 32.92 | 0.00 | 32.92 | 81.86 | 4.55 | 0.00 | 0.00 | 0.00 |
December | 31.19 | 0.00 | 31.19 | 76.37 | 11.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.93 | 2.16 | 37.77 | 105.97 | 3.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.19 | 0.00 | 31.19 | 76.37 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.09 | 12.30 | 47.80 | 162.65 | 11.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.69 | 116.47 | 163.22 | 619.85 | 30.58 | 0.00 | 0.00 | 0.00 |
February | 236.59 | 76.30 | 160.29 | 563.85 | 20.21 | 0.00 | 0.00 | 0.00 |
March | 164.98 | 24.49 | 140.50 | 444.18 | 7.33 | 0.00 | 0.00 | 0.00 |
April | 122.31 | 0.70 | 121.61 | 364.59 | 1.15 | 0.00 | 0.00 | 0.00 |
May | 121.09 | 0.00 | 121.09 | 371.22 | 3.48 | 0.00 | 0.00 | 0.00 |
June | 120.66 | 0.00 | 120.66 | 361.07 | 4.20 | 0.00 | 0.00 | 0.00 |
July | 124.29 | 0.00 | 124.29 | 322.99 | 8.55 | 0.00 | 0.00 | 0.00 |
August | 120.85 | 0.01 | 120.84 | 324.73 | 3.12 | 0.00 | 0.00 | 0.00 |
September | 133.36 | 3.65 | 129.71 | 355.59 | 4.17 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 26.35 | 147.33 | 419.27 | 6.03 | 0.00 | 0.00 | 0.00 |
November | 229.24 | 70.83 | 158.41 | 519.83 | 14.50 | 0.00 | 0.00 | 0.00 |
December | 280.67 | 119.80 | 160.87 | 611.62 | 36.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.38 | 36.42 | 138.96 | 439.32 | 11.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.66 | 0.00 | 120.66 | 322.99 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.67 | 119.80 | 163.22 | 619.85 | 36.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101488E+10 | 0.422614E+09 | 0.592265E+09 | 0.218510E+10 | 0.143412E+09 |
February | 0.775409E+09 | 0.250070E+09 | 0.525339E+09 | 0.178225E+10 | 97798543.14 |
March | 0.598658E+09 | 88846440.13 | 0.509811E+09 | 0.151767E+10 | 55870528.65 |
April | 0.429490E+09 | 2472579.53 | 0.427018E+09 | 0.117851E+10 | 7034356.13 |
May | 0.439386E+09 | 0.00 | 0.439386E+09 | 0.126196E+10 | 16280430.43 |
June | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.118612E+10 | 18548425.30 |
July | 0.451004E+09 | 0.00 | 0.451004E+09 | 0.112279E+10 | 44086884.25 |
August | 0.438513E+09 | 36987.92 | 0.438476E+09 | 0.110622E+10 | 20996803.70 |
September | 0.468298E+09 | 12832635.36 | 0.455465E+09 | 0.118011E+10 | 23694904.35 |
October | 0.630206E+09 | 95626572.27 | 0.534580E+09 | 0.146412E+10 | 38023538.50 |
November | 0.804987E+09 | 0.248710E+09 | 0.556277E+09 | 0.176579E+10 | 72838912.26 |
December | 0.101844E+10 | 0.434702E+09 | 0.583736E+09 | 0.215632E+10 | 0.165144E+09 |
Annual Sum or Average | 0.749295E+10 | 0.155591E+10 | 0.593704E+10 | 0.179070E+11 | 0.703729E+09 |
Minimum of Months | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.110622E+10 | 7034356.13 |
Maximum of Months | 0.101844E+10 | 0.434702E+09 | 0.592265E+09 | 0.218510E+10 | 0.165144E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285783E+10 | 0.119005E+10 | 0.166778E+10 | 0.612856E+10 | 0.412422E+09 |
February | 0.218350E+10 | 0.704181E+09 | 0.147932E+10 | 0.501468E+10 | 0.268873E+09 |
March | 0.168578E+10 | 0.250186E+09 | 0.143560E+10 | 0.431609E+10 | 0.153439E+09 |
April | 0.120942E+10 | 6962620.92 | 0.120245E+10 | 0.339659E+10 | 25730198.80 |
May | 0.123728E+10 | 0.00 | 0.123728E+10 | 0.360737E+10 | 58531674.79 |
June | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.341281E+10 | 59059289.12 |
July | 0.127000E+10 | 0.00 | 0.127000E+10 | 0.320733E+10 | 0.142132E+09 |
August | 0.123482E+10 | 104155.55 | 0.123472E+10 | 0.314505E+10 | 79053723.54 |
September | 0.131870E+10 | 36135855.08 | 0.128256E+10 | 0.336464E+10 | 86711321.25 |
October | 0.177462E+10 | 0.269278E+09 | 0.150534E+10 | 0.412816E+10 | 0.136462E+09 |
November | 0.226679E+10 | 0.700352E+09 | 0.156644E+10 | 0.496616E+10 | 0.227584E+09 |
December | 0.286785E+10 | 0.122409E+10 | 0.164376E+10 | 0.604518E+10 | 0.480388E+09 |
Annual Sum or Average | 0.210997E+11 | 0.438134E+10 | 0.167183E+11 | 0.507326E+11 | 0.213039E+10 |
Minimum of Months | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.314505E+10 | 25730198.80 |
Maximum of Months | 0.286785E+10 | 0.122409E+10 | 0.166778E+10 | 0.612856E+10 | 0.480388E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371249E+10 | 0.154595E+10 | 0.216654E+10 | 0.831951E+10 | 0.465191E+09 |
February | 0.283649E+10 | 0.914771E+09 | 0.192172E+10 | 0.682281E+10 | 0.299618E+09 |
March | 0.218993E+10 | 0.325005E+09 | 0.186492E+10 | 0.588472E+10 | 0.161508E+09 |
April | 0.157110E+10 | 9044840.82 | 0.156206E+10 | 0.461258E+10 | 30464608.26 |
May | 0.160730E+10 | 0.00 | 0.160730E+10 | 0.483139E+10 | 71205086.00 |
June | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.453594E+10 | 78296710.78 |
July | 0.164980E+10 | 0.00 | 0.164980E+10 | 0.425718E+10 | 0.180021E+09 |
August | 0.160411E+10 | 135303.99 | 0.160397E+10 | 0.420658E+10 | 92850062.18 |
September | 0.171306E+10 | 46942532.26 | 0.166612E+10 | 0.455244E+10 | 92465098.22 |
October | 0.230533E+10 | 0.349808E+09 | 0.195552E+10 | 0.559474E+10 | 0.133955E+09 |
November | 0.294469E+10 | 0.909796E+09 | 0.203489E+10 | 0.674731E+10 | 0.245442E+09 |
December | 0.372551E+10 | 0.159016E+10 | 0.213534E+10 | 0.819442E+10 | 0.551942E+09 |
Annual Sum or Average | 0.274097E+11 | 0.569162E+10 | 0.217180E+11 | 0.685596E+11 | 0.240296E+10 |
Minimum of Months | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.420658E+10 | 30464608.26 |
Maximum of Months | 0.372551E+10 | 0.159016E+10 | 0.216654E+10 | 0.831951E+10 | 0.551942E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.468866E+09 | 10219551.41 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.389962E+09 | 3223052.22 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.351225E+09 | 662319.81 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289067E+09 | 35189.78 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.303293E+09 | 97378.43 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.288069E+09 | 143915.98 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.261143E+09 | 314293.23 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.261214E+09 | 133206.05 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.276370E+09 | 70460.47 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.328496E+09 | 245839.53 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.386157E+09 | 1978642.23 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.459370E+09 | 13070381.08 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.406323E+10 | 30194230.22 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.261143E+09 | 35189.78 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.468866E+09 | 13070381.08 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.661325E+09 | 19734146.90 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.668056E+09 | 6149989.64 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.854599E+09 | 1159578.94 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.870413E+09 | 61905.40 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.814084E+09 | 170261.37 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.824932E+09 | 244569.54 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.688565E+09 | 556947.91 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.738275E+09 | 224408.94 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.687640E+09 | 140293.87 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.639622E+09 | 523674.08 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.594620E+09 | 3965991.21 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.610042E+09 | 25356122.31 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.865217E+10 | 58287890.09 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.594620E+09 | 61905.40 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.870413E+09 | 25356122.31 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.211048E+09 | 10366008.65 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.212455E+09 | 3190244.17 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.266119E+09 | 619808.75 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.299186E+09 | 33911.95 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368775E+09 | 244454.88 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408644E+09 | 356981.81 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.334567E+09 | 640865.41 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.292999E+09 | 250099.54 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.253828E+09 | 274303.22 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.235510E+09 | 417938.19 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.211959E+09 | 2754205.98 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.199493E+09 | 13562829.98 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.329458E+10 | 32711652.53 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.199493E+09 | 33911.95 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408644E+09 | 13562829.98 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.663704E+09 | 19035221.60 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.669597E+09 | 5798257.22 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.857097E+09 | 1079492.16 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.869765E+09 | 64381.38 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.811599E+09 | 452359.84 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.820078E+09 | 660106.82 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.685236E+09 | 1171528.95 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.736375E+09 | 452781.54 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.687486E+09 | 459221.15 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.641402E+09 | 722145.39 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.597544E+09 | 4963976.22 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.612009E+09 | 24915510.08 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.865189E+10 | 59774982.36 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.597544E+09 | 64381.38 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.869765E+09 | 24915510.08 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160496E+09 | 66833161.06 | 93662786.16 | 0.318789E+09 | 47572561.07 |
February | 0.122626E+09 | 39546664.89 | 83078992.27 | 0.260070E+09 | 35047278.80 |
March | 94673987.22 | 14050379.47 | 80623607.75 | 0.215053E+09 | 29228249.14 |
April | 67921429.52 | 391019.39 | 67530410.13 | 0.156518E+09 | 14978958.81 |
May | 69486232.11 | 0.00 | 69486232.11 | 0.164229E+09 | 17244893.05 |
June | 67002720.86 | 0.00 | 67002720.86 | 0.157511E+09 | 17539989.37 |
July | 71323528.04 | 0.00 | 71323528.04 | 0.145710E+09 | 29472410.79 |
August | 69348227.89 | 5849.35 | 69342378.53 | 0.139771E+09 | 26754038.21 |
September | 74058349.55 | 2029382.34 | 72028967.21 | 0.156495E+09 | 25796625.17 |
October | 99662864.04 | 15122605.09 | 84540258.96 | 0.198563E+09 | 33135928.83 |
November | 0.127303E+09 | 39331600.67 | 87971427.44 | 0.252081E+09 | 36577928.67 |
December | 0.161059E+09 | 68744751.16 | 92314006.95 | 0.315118E+09 | 53444831.01 |
Annual Sum or Average | 0.118496E+10 | 0.246055E+09 | 0.938905E+09 | 0.247991E+10 | 0.366794E+09 |
Minimum of Months | 67002720.86 | 0.00 | 67002720.86 | 0.139771E+09 | 14978958.81 |
Maximum of Months | 0.161059E+09 | 68744751.16 | 93662786.16 | 0.318789E+09 | 53444831.01 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60724100.24 | 0.00 | 60724100.24 | 0.181387E+09 | 6164547.20 |
February | 58507357.38 | 0.00 | 58507357.38 | 0.183519E+09 | 1142117.51 |
March | 66523193.68 | 3317.10 | 66519876.59 | 0.230504E+09 | 196023.85 |
April | 71349170.49 | 1719341.05 | 69629829.44 | 0.256513E+09 | 0.00 |
May | 92494836.56 | 9633454.15 | 82861382.42 | 0.310753E+09 | 55847.13 |
June | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.342191E+09 | 105984.11 |
July | 97586225.79 | 10353414.93 | 87232810.86 | 0.280907E+09 | 153627.16 |
August | 80694351.16 | 3789203.30 | 76905147.87 | 0.248986E+09 | 26378.92 |
September | 66245541.57 | 116605.50 | 66128936.07 | 0.217276E+09 | 44785.23 |
October | 65795960.95 | 0.00 | 65795960.95 | 0.202250E+09 | 30198.16 |
November | 60249166.34 | 0.00 | 60249166.34 | 0.182057E+09 | 1183881.83 |
December | 58992615.48 | 0.00 | 58992615.48 | 0.170770E+09 | 8195399.17 |
Annual Sum or Average | 0.889153E+09 | 48126855.52 | 0.841027E+09 | 0.280711E+10 | 17298790.28 |
Minimum of Months | 58507357.38 | 0.00 | 58507357.38 | 0.170770E+09 | 0.00 |
Maximum of Months | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.342191E+09 | 8195399.17 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273157E+09 | 92096303.80 | 0.181060E+09 | 0.654486E+09 | 18725045.09 |
February | 0.279632E+09 | 0.102419E+09 | 0.177212E+09 | 0.681187E+09 | 5873333.66 |
March | 0.338031E+09 | 0.132310E+09 | 0.205721E+09 | 0.853411E+09 | 1123525.05 |
April | 0.330020E+09 | 0.125890E+09 | 0.204130E+09 | 0.876955E+09 | 17366.56 |
May | 0.293553E+09 | 88968658.34 | 0.204584E+09 | 0.824520E+09 | 139975.47 |
June | 0.302391E+09 | 99564373.77 | 0.202827E+09 | 0.825300E+09 | 192254.93 |
July | 0.267221E+09 | 59987150.76 | 0.207234E+09 | 0.688494E+09 | 434000.27 |
August | 0.293747E+09 | 86350089.41 | 0.207397E+09 | 0.743506E+09 | 162780.84 |
September | 0.267059E+09 | 72837236.32 | 0.194222E+09 | 0.697441E+09 | 125114.13 |
October | 0.258910E+09 | 66433527.72 | 0.192476E+09 | 0.646626E+09 | 440042.08 |
November | 0.242558E+09 | 67113721.24 | 0.175444E+09 | 0.596285E+09 | 3696306.97 |
December | 0.256204E+09 | 82286475.08 | 0.173918E+09 | 0.607067E+09 | 24032905.06 |
Annual Sum or Average | 0.340248E+10 | 0.107626E+10 | 0.232623E+10 | 0.869528E+10 | 54962650.12 |
Minimum of Months | 0.242558E+09 | 59987150.76 | 0.173918E+09 | 0.596285E+09 | 17366.56 |
Maximum of Months | 0.338031E+09 | 0.132310E+09 | 0.207397E+09 | 0.876955E+09 | 24032905.06 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.468382E+09 | 9953682.43 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.389408E+09 | 3067012.25 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.351032E+09 | 601174.50 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.288639E+09 | 18079.26 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.302866E+09 | 82079.27 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.287681E+09 | 114297.50 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.260802E+09 | 260983.02 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.260719E+09 | 99153.69 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.275915E+09 | 58230.65 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.328220E+09 | 224015.59 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.385903E+09 | 1941399.43 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.458881E+09 | 12746954.92 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.405845E+10 | 29167062.51 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.260719E+09 | 18079.26 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.468382E+09 | 12746954.92 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.209522E+09 | 10141924.78 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.211135E+09 | 3066788.75 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.265790E+09 | 567437.73 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.298770E+09 | 14587.78 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368377E+09 | 210937.85 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408301E+09 | 310561.71 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.334246E+09 | 571215.50 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.292537E+09 | 209047.56 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.253353E+09 | 242345.67 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.235163E+09 | 396760.81 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.211393E+09 | 2720980.78 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.198017E+09 | 13236937.63 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.328660E+10 | 31689526.54 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.198017E+09 | 14587.78 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408301E+09 | 13236937.63 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273157E+09 | 92096303.80 | 0.181060E+09 | 0.654019E+09 | 17963616.57 |
February | 0.279632E+09 | 0.102419E+09 | 0.177212E+09 | 0.680581E+09 | 5502455.12 |
March | 0.338031E+09 | 0.132310E+09 | 0.205721E+09 | 0.855709E+09 | 1048566.89 |
April | 0.330020E+09 | 0.125890E+09 | 0.204130E+09 | 0.876370E+09 | 19119.13 |
May | 0.293553E+09 | 88968658.34 | 0.204584E+09 | 0.822063E+09 | 387399.14 |
June | 0.302391E+09 | 99564373.77 | 0.202827E+09 | 0.820446E+09 | 573678.50 |
July | 0.267221E+09 | 59987150.76 | 0.207234E+09 | 0.685141E+09 | 1006183.89 |
August | 0.293747E+09 | 86350089.41 | 0.207397E+09 | 0.741651E+09 | 378192.54 |
September | 0.267059E+09 | 72837236.32 | 0.194222E+09 | 0.697262E+09 | 411080.04 |
October | 0.258910E+09 | 66433527.72 | 0.192476E+09 | 0.648301E+09 | 657348.12 |
November | 0.242558E+09 | 67113721.24 | 0.175444E+09 | 0.598442E+09 | 4716247.76 |
December | 0.256204E+09 | 82286475.08 | 0.173918E+09 | 0.606525E+09 | 23567980.02 |
Annual Sum or Average | 0.340248E+10 | 0.107626E+10 | 0.232623E+10 | 0.868651E+10 | 56231867.71 |
Minimum of Months | 0.242558E+09 | 59987150.76 | 0.173918E+09 | 0.598442E+09 | 19119.13 |
Maximum of Months | 0.338031E+09 | 0.132310E+09 | 0.207397E+09 | 0.876370E+09 | 23567980.02 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96116311.08 | 0.00 | 96116311.08 | 0.258902E+09 | 22857147.48 |
February | 92607569.98 | 0.00 | 92607569.98 | 0.257560E+09 | 12300646.47 |
March | 0.105295E+09 | 5250.42 | 0.105290E+09 | 0.320528E+09 | 4152985.96 |
April | 0.112934E+09 | 2721435.46 | 0.110213E+09 | 0.362109E+09 | 524647.51 |
May | 0.146404E+09 | 15248181.07 | 0.131156E+09 | 0.445524E+09 | 1667355.06 |
June | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.493180E+09 | 1968016.86 |
July | 0.154463E+09 | 16387761.13 | 0.138075E+09 | 0.410715E+09 | 3662138.63 |
August | 0.127726E+09 | 5997688.58 | 0.121728E+09 | 0.359717E+09 | 1364515.51 |
September | 0.104856E+09 | 184567.42 | 0.104671E+09 | 0.310801E+09 | 1579626.02 |
October | 0.104144E+09 | 0.00 | 0.104144E+09 | 0.286570E+09 | 2712282.64 |
November | 95364568.46 | 0.00 | 95364568.46 | 0.257122E+09 | 8763658.95 |
December | 93375654.12 | 0.00 | 93375654.12 | 0.246137E+09 | 27835097.73 |
Annual Sum or Average | 0.140738E+10 | 76176934.66 | 0.133121E+10 | 0.400886E+10 | 89388118.81 |
Minimum of Months | 92607569.98 | 0.00 | 92607569.98 | 0.246137E+09 | 524647.51 |
Maximum of Months | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.493180E+09 | 27835097.73 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35432452.13 | 0.00 | 35432452.13 | 95441921.48 | 8426091.00 |
February | 34138984.87 | 0.00 | 34138984.87 | 94947198.28 | 4534783.22 |
March | 38816217.39 | 1935.52 | 38814281.86 | 0.118160E+09 | 1530962.59 |
April | 41632170.06 | 1003233.80 | 40628936.26 | 0.133488E+09 | 193406.80 |
May | 53970645.19 | 5621110.92 | 48349534.27 | 0.164238E+09 | 614656.12 |
June | 64179613.14 | 13135449.25 | 51044163.89 | 0.181806E+09 | 725492.50 |
July | 56941465.74 | 6041207.32 | 50900258.43 | 0.151406E+09 | 1350015.94 |
August | 47085073.69 | 2210996.36 | 44874077.33 | 0.132606E+09 | 503016.92 |
September | 38654207.65 | 68039.19 | 38586168.46 | 0.114574E+09 | 582315.56 |
October | 38391877.81 | 0.00 | 38391877.81 | 0.105642E+09 | 999859.69 |
November | 35155328.67 | 0.00 | 35155328.67 | 94785733.08 | 3230647.56 |
December | 34422132.49 | 0.00 | 34422132.49 | 90736408.58 | 10261169.58 |
Annual Sum or Average | 0.518820E+09 | 28081972.36 | 0.490738E+09 | 0.147783E+10 | 32952417.47 |
Minimum of Months | 34138984.87 | 0.00 | 34138984.87 | 90736408.58 | 193406.80 |
Maximum of Months | 64179613.14 | 13135449.25 | 51044163.89 | 0.181806E+09 | 10261169.58 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93627068.97 | 38987856.63 | 54639212.34 | 0.215824E+09 | 8010261.19 |
February | 71535020.42 | 23069980.18 | 48465040.24 | 0.177679E+09 | 4340668.90 |
March | 55229107.56 | 8196442.78 | 47032664.78 | 0.158241E+09 | 1522171.18 |
April | 39622709.96 | 228105.44 | 39394604.52 | 0.128566E+09 | 183752.26 |
May | 40535554.69 | 0.00 | 40535554.69 | 0.133068E+09 | 627616.54 |
June | 39086771.20 | 0.00 | 39086771.20 | 0.124372E+09 | 742087.81 |
July | 41607361.40 | 0.00 | 41607361.40 | 0.116353E+09 | 1372530.02 |
August | 40455048.42 | 3412.29 | 40451636.13 | 0.117306E+09 | 512998.55 |
September | 43202749.49 | 1183862.42 | 42018887.07 | 0.124950E+09 | 551075.40 |
October | 58139423.51 | 8821937.34 | 49317486.17 | 0.149218E+09 | 926928.90 |
November | 74263616.00 | 22944520.11 | 51319095.89 | 0.176407E+09 | 3034458.65 |
December | 93955390.88 | 40103003.66 | 53852387.21 | 0.212004E+09 | 9750799.72 |
Annual Sum or Average | 0.691260E+09 | 0.143539E+09 | 0.547721E+09 | 0.183399E+10 | 31575349.14 |
Minimum of Months | 39086771.20 | 0.00 | 39086771.20 | 0.116353E+09 | 183752.26 |
Maximum of Months | 93955390.88 | 40103003.66 | 54639212.34 | 0.215824E+09 | 9750799.72 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254123E+09 | 0.105821E+09 | 0.148302E+09 | 0.585790E+09 | 21741487.33 |
February | 0.194161E+09 | 62616645.07 | 0.131544E+09 | 0.482256E+09 | 11781463.27 |
March | 0.149903E+09 | 22246822.25 | 0.127656E+09 | 0.429499E+09 | 4131483.95 |
April | 0.107544E+09 | 619124.83 | 0.106925E+09 | 0.348955E+09 | 498741.23 |
May | 0.110022E+09 | 0.00 | 0.110022E+09 | 0.361175E+09 | 1703479.68 |
June | 0.106089E+09 | 0.00 | 0.106089E+09 | 0.337572E+09 | 2014178.10 |
July | 0.112931E+09 | 0.00 | 0.112931E+09 | 0.315806E+09 | 3725327.22 |
August | 0.109803E+09 | 9261.64 | 0.109794E+09 | 0.318393E+09 | 1392382.99 |
September | 0.117261E+09 | 3213244.76 | 0.114048E+09 | 0.339141E+09 | 1495731.35 |
October | 0.157802E+09 | 23944542.43 | 0.133858E+09 | 0.405008E+09 | 2515874.64 |
November | 0.201567E+09 | 62276120.79 | 0.139291E+09 | 0.478805E+09 | 8236141.47 |
December | 0.255014E+09 | 0.108848E+09 | 0.146166E+09 | 0.575422E+09 | 26465664.93 |
Annual Sum or Average | 0.187622E+10 | 0.389595E+09 | 0.148663E+10 | 0.497782E+10 | 85701956.16 |
Minimum of Months | 0.106089E+09 | 0.00 | 0.106089E+09 | 0.315806E+09 | 498741.23 |
Maximum of Months | 0.255014E+09 | 0.108848E+09 | 0.148302E+09 | 0.585790E+09 | 26465664.93 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.465152E+09 | 8589888.46 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.387755E+09 | 2138490.45 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.350861E+09 | 314221.41 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289074E+09 | 9344.66 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.303257E+09 | 64649.67 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.288489E+09 | 78294.17 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.259818E+09 | 178493.17 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.260433E+09 | 70411.23 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.274492E+09 | 18914.39 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.326036E+09 | 113596.59 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.383227E+09 | 1339179.66 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.455228E+09 | 11146286.26 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.404382E+10 | 24061770.12 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.259818E+09 | 9344.66 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.465152E+09 | 11146286.26 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.655353E+09 | 16532439.64 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.663759E+09 | 4052744.05 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.850875E+09 | 588179.43 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.866276E+09 | 13183.96 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.811100E+09 | 115153.37 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.822529E+09 | 129694.40 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.683869E+09 | 302455.50 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.734044E+09 | 105383.07 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.682422E+09 | 34403.66 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.634815E+09 | 245760.31 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.589974E+09 | 2659987.32 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.603528E+09 | 21475787.85 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.859854E+10 | 46255172.55 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.589974E+09 | 13183.96 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.866276E+09 | 21475787.85 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.209343E+09 | 8656015.51 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.211633E+09 | 2095147.85 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.265823E+09 | 323123.71 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.298220E+09 | 6885.32 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.367427E+09 | 228192.83 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.407062E+09 | 341797.05 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.332186E+09 | 564598.04 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.291345E+09 | 228824.63 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.251991E+09 | 300048.95 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.233939E+09 | 367792.61 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.210583E+09 | 2211472.22 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.197502E+09 | 11561877.24 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.327705E+10 | 26885775.96 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.197502E+09 | 6885.32 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.407062E+09 | 11561877.24 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.658488E+09 | 15857432.32 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.665844E+09 | 3750634.23 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.853477E+09 | 577640.88 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.865539E+09 | 14137.08 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.808501E+09 | 418744.20 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.817528E+09 | 623546.24 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.680446E+09 | 1028064.50 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.732065E+09 | 402259.24 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.682235E+09 | 536936.90 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.636625E+09 | 637765.94 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.593301E+09 | 3983489.73 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.606378E+09 | 21224523.97 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.860043E+10 | 49055175.23 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.593301E+09 | 14137.08 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.865539E+09 | 21224523.97 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294287E+09 | 0.122546E+09 | 0.171741E+09 | 0.686256E+09 | 11853165.54 |
February | 0.224848E+09 | 72513142.25 | 0.152334E+09 | 0.575984E+09 | 2485237.97 |
March | 0.173595E+09 | 25762909.92 | 0.147832E+09 | 0.529670E+09 | 339890.71 |
April | 0.124541E+09 | 716976.88 | 0.123824E+09 | 0.442151E+09 | 0.00 |
May | 0.127411E+09 | 0.00 | 0.127411E+09 | 0.461015E+09 | 54565.87 |
June | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.440031E+09 | 22748.60 |
July | 0.130780E+09 | 0.00 | 0.130780E+09 | 0.394858E+09 | 88936.97 |
August | 0.127158E+09 | 10725.43 | 0.127147E+09 | 0.397112E+09 | 13769.83 |
September | 0.135794E+09 | 3721094.83 | 0.132073E+09 | 0.415617E+09 | 3438.37 |
October | 0.182743E+09 | 27728953.05 | 0.155014E+09 | 0.487597E+09 | 70187.94 |
November | 0.233424E+09 | 72118798.45 | 0.161305E+09 | 0.567752E+09 | 1582518.00 |
December | 0.295319E+09 | 0.126051E+09 | 0.169268E+09 | 0.670434E+09 | 15508651.27 |
Annual Sum or Average | 0.217276E+10 | 0.451170E+09 | 0.172159E+10 | 0.606848E+10 | 32023111.07 |
Minimum of Months | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.394858E+09 | 0.00 |
Maximum of Months | 0.295319E+09 | 0.126051E+09 | 0.171741E+09 | 0.686256E+09 | 15508651.27 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.131604E+10 | 0.193866E+09 |
February | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.132914E+10 | 0.117770E+09 |
March | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.160916E+10 | 62894486.20 |
April | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.179687E+10 | 14545982.45 |
May | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.226587E+10 | 32966251.12 |
June | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.255552E+10 | 34054644.22 |
July | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.208343E+10 | 76323141.59 |
August | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.177019E+10 | 46298989.88 |
September | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.152099E+10 | 48698488.10 |
October | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.140537E+10 | 75160772.73 |
November | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.129356E+10 | 0.108992E+09 |
December | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.125861E+10 | 0.232444E+09 |
Annual Sum or Average | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.202048E+11 | 0.104401E+10 |
Minimum of Months | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.125861E+10 | 14545982.45 |
Maximum of Months | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.255552E+10 | 0.232444E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.128545E+10 | 0.208939E+09 |
February | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.130183E+10 | 0.128972E+09 |
March | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.157448E+10 | 73036689.93 |
April | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.175755E+10 | 17651548.97 |
May | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.222757E+10 | 38846525.19 |
June | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.252022E+10 | 39411040.23 |
July | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.204821E+10 | 88146071.71 |
August | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.172870E+10 | 57029960.70 |
September | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.148450E+10 | 59210012.92 |
October | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.136919E+10 | 90130192.15 |
November | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.126255E+10 | 0.123431E+09 |
December | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.122864E+10 | 0.249539E+09 |
Annual Sum or Average | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.197889E+11 | 0.117434E+10 |
Minimum of Months | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.122864E+10 | 17651548.97 |
Maximum of Months | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.252022E+10 | 0.249539E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.234128E+09 | 26235937.13 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.232051E+09 | 16258912.11 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.273120E+09 | 9962134.49 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.300840E+09 | 2696694.29 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368254E+09 | 5047047.55 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.412484E+09 | 5244667.63 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.348437E+09 | 9996102.48 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.293250E+09 | 6976534.57 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.263643E+09 | 7326554.58 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.241937E+09 | 10399936.56 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.231097E+09 | 14298775.59 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.226589E+09 | 30988734.01 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.342583E+10 | 0.145432E+09 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.226589E+09 | 2696694.29 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.412484E+09 | 30988734.01 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.546275E+09 | 0.184180E+09 | 0.362095E+09 | 0.139602E+10 | 97613444.60 |
February | 0.559224E+09 | 0.204824E+09 | 0.354400E+09 | 0.143434E+10 | 61075185.32 |
March | 0.676014E+09 | 0.264601E+09 | 0.411414E+09 | 0.172425E+10 | 37261639.97 |
April | 0.659994E+09 | 0.251763E+09 | 0.408231E+09 | 0.175102E+10 | 10233629.84 |
May | 0.587064E+09 | 0.177925E+09 | 0.409139E+09 | 0.163548E+10 | 19185106.64 |
June | 0.604740E+09 | 0.199115E+09 | 0.405625E+09 | 0.165111E+10 | 19940377.89 |
July | 0.534404E+09 | 0.119966E+09 | 0.414438E+09 | 0.142183E+10 | 37682545.94 |
August | 0.587453E+09 | 0.172688E+09 | 0.414765E+09 | 0.148207E+10 | 26440819.16 |
September | 0.534080E+09 | 0.145664E+09 | 0.388416E+09 | 0.142817E+10 | 27632743.14 |
October | 0.517782E+09 | 0.132858E+09 | 0.384925E+09 | 0.131484E+10 | 39572098.91 |
November | 0.485082E+09 | 0.134218E+09 | 0.350864E+09 | 0.126488E+10 | 53797000.01 |
December | 0.512372E+09 | 0.164561E+09 | 0.347811E+09 | 0.131716E+10 | 0.115777E+09 |
Annual Sum or Average | 0.680448E+10 | 0.215236E+10 | 0.465212E+10 | 0.178212E+11 | 0.546212E+09 |
Minimum of Months | 0.485082E+09 | 0.119966E+09 | 0.347811E+09 | 0.126488E+10 | 10233629.84 |
Maximum of Months | 0.676014E+09 | 0.264601E+09 | 0.414765E+09 | 0.175102E+10 | 0.115777E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.492835E+09 | 25902112.03 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.409569E+09 | 16219952.46 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.357397E+09 | 9904288.14 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289541E+09 | 2709751.55 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.300272E+09 | 5049203.81 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.287374E+09 | 5305170.97 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.273528E+09 | 10108224.72 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.259122E+09 | 7012353.01 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.285721E+09 | 7315578.42 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.335211E+09 | 10382576.39 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.406525E+09 | 14239707.23 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.487693E+09 | 30710395.37 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.418479E+10 | 0.144859E+09 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.259122E+09 | 2709751.55 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.492835E+09 | 30710395.37 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96116311.08 | 0.00 | 96116311.08 | 0.238512E+09 | 29000285.09 |
February | 92607569.98 | 0.00 | 92607569.98 | 0.239538E+09 | 17187554.25 |
March | 0.105295E+09 | 5250.42 | 0.105290E+09 | 0.295169E+09 | 6831578.67 |
April | 0.112934E+09 | 2721435.46 | 0.110213E+09 | 0.332968E+09 | 1029323.11 |
May | 0.146404E+09 | 15248181.07 | 0.131156E+09 | 0.420547E+09 | 3095206.56 |
June | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.471200E+09 | 3580710.39 |
July | 0.154463E+09 | 16387761.13 | 0.138075E+09 | 0.387349E+09 | 7555938.21 |
August | 0.127726E+09 | 5997688.58 | 0.121728E+09 | 0.335860E+09 | 2789091.94 |
September | 0.104856E+09 | 184567.42 | 0.104671E+09 | 0.284586E+09 | 3647662.35 |
October | 0.104144E+09 | 0.00 | 0.104144E+09 | 0.263824E+09 | 5610522.46 |
November | 95364568.46 | 0.00 | 95364568.46 | 0.237142E+09 | 13192747.39 |
December | 93375654.12 | 0.00 | 93375654.12 | 0.228634E+09 | 34549266.55 |
Annual Sum or Average | 0.140738E+10 | 76176934.66 | 0.133121E+10 | 0.373533E+10 | 0.128070E+09 |
Minimum of Months | 92607569.98 | 0.00 | 92607569.98 | 0.228634E+09 | 1029323.11 |
Maximum of Months | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.471200E+09 | 34549266.55 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85995627.71 | 0.00 | 85995627.71 | 0.213398E+09 | 25946664.95 |
February | 82856343.75 | 0.00 | 82856343.75 | 0.214316E+09 | 15379648.79 |
March | 94208127.83 | 4697.57 | 94203430.26 | 0.264089E+09 | 6112239.32 |
April | 0.101043E+09 | 2434878.62 | 98607651.10 | 0.297908E+09 | 920939.29 |
May | 0.130988E+09 | 13642605.38 | 0.117346E+09 | 0.376265E+09 | 2769293.04 |
June | 0.155766E+09 | 31880130.66 | 0.123886E+09 | 0.421584E+09 | 3203675.15 |
July | 0.138199E+09 | 14662191.98 | 0.123536E+09 | 0.346562E+09 | 6760326.54 |
August | 0.114277E+09 | 5366154.70 | 0.108911E+09 | 0.300495E+09 | 2495411.12 |
September | 93814925.33 | 165133.17 | 93649792.16 | 0.254621E+09 | 3263577.33 |
October | 93178242.92 | 0.00 | 93178242.92 | 0.236044E+09 | 5019755.71 |
November | 85323040.73 | 0.00 | 85323040.73 | 0.212171E+09 | 11804176.19 |
December | 83543551.54 | 0.00 | 83543551.54 | 0.204559E+09 | 30911359.69 |
Annual Sum or Average | 0.125919E+10 | 68155792.08 | 0.119104E+10 | 0.334201E+10 | 0.114587E+09 |
Minimum of Months | 82856343.75 | 0.00 | 82856343.75 | 0.204559E+09 | 920939.29 |
Maximum of Months | 0.155766E+09 | 31880130.66 | 0.123886E+09 | 0.421584E+09 | 30911359.69 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.749123E+09 | 0.311947E+09 | 0.437176E+09 | 0.166021E+10 | 81917284.09 |
February | 0.572361E+09 | 0.184586E+09 | 0.387775E+09 | 0.136407E+10 | 48898242.96 |
March | 0.441896E+09 | 65580856.37 | 0.376315E+09 | 0.118970E+10 | 19632971.81 |
April | 0.317027E+09 | 1825102.76 | 0.315202E+09 | 0.945015E+09 | 2991400.60 |
May | 0.324331E+09 | 0.00 | 0.324331E+09 | 0.994277E+09 | 9322995.36 |
June | 0.312739E+09 | 0.00 | 0.312739E+09 | 0.935886E+09 | 10898104.00 |
July | 0.332906E+09 | 0.00 | 0.332906E+09 | 0.865101E+09 | 22895464.09 |
August | 0.323686E+09 | 27302.16 | 0.323659E+09 | 0.869752E+09 | 8366740.04 |
September | 0.345671E+09 | 9472244.64 | 0.336199E+09 | 0.921696E+09 | 10809461.75 |
October | 0.465181E+09 | 70585523.65 | 0.394596E+09 | 0.112298E+10 | 16143158.94 |
November | 0.594193E+09 | 0.183582E+09 | 0.410611E+09 | 0.134741E+10 | 37585222.08 |
December | 0.751750E+09 | 0.320870E+09 | 0.430880E+09 | 0.163816E+10 | 98050738.06 |
Annual Sum or Average | 0.553086E+10 | 0.114848E+10 | 0.438239E+10 | 0.138543E+11 | 0.367512E+09 |
Minimum of Months | 0.312739E+09 | 0.00 | 0.312739E+09 | 0.865101E+09 | 2991400.60 |
Maximum of Months | 0.751750E+09 | 0.320870E+09 | 0.437176E+09 | 0.166021E+10 | 98050738.06 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 815.82 | 53.54 | 378.91 | 157.79 | 221.13 | 0.00 | 0.00 |
February | 736.71 | 40.43 | 320.52 | 103.37 | 217.15 | 0.00 | 0.00 |
March | 566.63 | 20.86 | 223.51 | 33.17 | 190.34 | 0.00 | 0.00 |
April | 454.67 | 2.71 | 165.70 | 0.95 | 164.74 | 0.00 | 0.00 |
May | 471.16 | 6.08 | 164.05 | 0.00 | 164.05 | 0.00 | 0.00 |
June | 457.61 | 7.16 | 163.46 | 0.00 | 163.46 | 0.00 | 0.00 |
July | 419.20 | 16.46 | 168.39 | 0.00 | 168.39 | 0.00 | 0.00 |
August | 413.02 | 7.84 | 163.72 | 0.01 | 163.71 | 0.00 | 0.00 |
September | 455.29 | 9.14 | 180.67 | 4.95 | 175.72 | 0.00 | 0.00 |
October | 546.64 | 14.20 | 235.29 | 35.70 | 199.59 | 0.00 | 0.00 |
November | 681.25 | 28.10 | 310.57 | 95.95 | 214.61 | 0.00 | 0.00 |
December | 805.08 | 61.66 | 380.24 | 162.30 | 217.94 | 0.00 | 0.00 |
Annual Sum or Average | 567.83 | 22.32 | 237.60 | 49.34 | 188.26 | 0.00 | 0.00 |
Minimum of Months | 413.02 | 2.71 | 163.46 | 0.00 | 163.46 | 0.00 | 0.00 |
Maximum of Months | 815.82 | 61.66 | 380.24 | 162.30 | 221.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2288.14 | 153.98 | 1066.99 | 444.32 | 622.68 | 0.00 | 0.00 |
February | 2072.87 | 111.14 | 902.57 | 291.08 | 611.49 | 0.00 | 0.00 |
March | 1611.44 | 57.29 | 629.40 | 93.41 | 535.99 | 0.00 | 0.00 |
April | 1310.41 | 9.93 | 466.60 | 2.69 | 463.91 | 0.00 | 0.00 |
May | 1346.84 | 21.85 | 461.95 | 0.00 | 461.95 | 0.00 | 0.00 |
June | 1316.67 | 22.79 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
July | 1197.48 | 53.07 | 474.16 | 0.00 | 474.16 | 0.00 | 0.00 |
August | 1174.23 | 29.52 | 461.03 | 0.04 | 460.99 | 0.00 | 0.00 |
September | 1298.09 | 33.45 | 508.76 | 13.94 | 494.81 | 0.00 | 0.00 |
October | 1541.28 | 50.95 | 662.57 | 100.54 | 562.03 | 0.00 | 0.00 |
November | 1915.96 | 87.80 | 874.53 | 270.20 | 604.34 | 0.00 | 0.00 |
December | 2257.01 | 179.36 | 1070.73 | 457.02 | 613.71 | 0.00 | 0.00 |
Annual Sum or Average | 1608.72 | 67.55 | 669.07 | 138.93 | 530.13 | 0.00 | 0.00 |
Minimum of Months | 1174.23 | 9.93 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
Maximum of Months | 2288.14 | 179.36 | 1070.73 | 457.02 | 622.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3106.15 | 173.68 | 1386.08 | 577.19 | 808.89 | 0.00 | 0.00 |
February | 2820.28 | 123.85 | 1172.49 | 378.13 | 794.36 | 0.00 | 0.00 |
March | 2197.10 | 60.30 | 817.62 | 121.34 | 696.28 | 0.00 | 0.00 |
April | 1779.55 | 11.75 | 606.13 | 3.49 | 602.65 | 0.00 | 0.00 |
May | 1803.84 | 26.58 | 600.10 | 0.00 | 600.10 | 0.00 | 0.00 |
June | 1749.98 | 30.21 | 597.94 | 0.00 | 597.94 | 0.00 | 0.00 |
July | 1589.45 | 67.21 | 615.96 | 0.00 | 615.96 | 0.00 | 0.00 |
August | 1570.56 | 34.67 | 598.91 | 0.05 | 598.85 | 0.00 | 0.00 |
September | 1756.34 | 35.67 | 660.90 | 18.11 | 642.79 | 0.00 | 0.00 |
October | 2088.84 | 50.01 | 860.71 | 130.60 | 730.11 | 0.00 | 0.00 |
November | 2603.13 | 94.69 | 1136.07 | 351.00 | 785.07 | 0.00 | 0.00 |
December | 3059.45 | 206.07 | 1390.94 | 593.70 | 797.25 | 0.00 | 0.00 |
Annual Sum or Average | 2174.01 | 76.20 | 869.15 | 180.48 | 688.67 | 0.00 | 0.00 |
Minimum of Months | 1570.56 | 11.75 | 597.94 | 0.00 | 597.94 | 0.00 | 0.00 |
Maximum of Months | 3106.15 | 206.07 | 1390.94 | 593.70 | 808.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 421.75 | 10.97 | 178.38 | 67.64 | 110.74 | 0.00 | 0.00 |
February | 437.28 | 3.81 | 176.93 | 60.66 | 116.27 | 0.00 | 0.00 |
March | 450.20 | 0.68 | 171.27 | 56.69 | 114.58 | 0.00 | 0.00 |
April | 447.33 | 0.04 | 160.49 | 49.03 | 111.46 | 0.00 | 0.00 |
May | 417.18 | 0.10 | 141.30 | 32.31 | 108.99 | 0.00 | 0.00 |
June | 429.40 | 0.15 | 150.18 | 40.60 | 109.57 | 0.00 | 0.00 |
July | 354.58 | 0.32 | 133.76 | 23.65 | 110.11 | 0.00 | 0.00 |
August | 373.17 | 0.13 | 141.95 | 32.57 | 109.38 | 0.00 | 0.00 |
September | 371.92 | 0.08 | 138.01 | 29.32 | 108.69 | 0.00 | 0.00 |
October | 361.45 | 0.29 | 142.70 | 31.89 | 110.81 | 0.00 | 0.00 |
November | 378.36 | 2.27 | 155.18 | 44.58 | 110.61 | 0.00 | 0.00 |
December | 399.05 | 14.13 | 171.24 | 63.57 | 107.67 | 0.00 | 0.00 |
Annual Sum or Average | 403.16 | 2.76 | 154.98 | 44.28 | 110.70 | 0.00 | 0.00 |
Minimum of Months | 354.58 | 0.04 | 133.76 | 23.65 | 107.67 | 0.00 | 0.00 |
Maximum of Months | 450.20 | 14.13 | 178.38 | 67.64 | 116.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.59 | 10.98 | 131.80 | 36.45 | 95.35 | 0.00 | 0.00 |
February | 364.60 | 3.72 | 143.78 | 40.22 | 103.56 | 0.00 | 0.00 |
March | 419.36 | 0.63 | 158.12 | 50.13 | 107.99 | 0.00 | 0.00 |
April | 450.98 | 0.04 | 162.13 | 49.67 | 112.46 | 0.00 | 0.00 |
May | 440.70 | 0.26 | 152.03 | 36.80 | 115.22 | 0.00 | 0.00 |
June | 474.04 | 0.39 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
July | 380.75 | 0.68 | 146.01 | 28.49 | 117.52 | 0.00 | 0.00 |
August | 384.32 | 0.26 | 147.23 | 34.33 | 112.90 | 0.00 | 0.00 |
September | 363.16 | 0.28 | 134.24 | 28.40 | 105.83 | 0.00 | 0.00 |
October | 327.40 | 0.42 | 126.88 | 24.83 | 102.05 | 0.00 | 0.00 |
November | 312.31 | 2.98 | 122.83 | 25.61 | 97.22 | 0.00 | 0.00 |
December | 302.98 | 14.36 | 123.59 | 31.48 | 92.11 | 0.00 | 0.00 |
Annual Sum or Average | 378.82 | 2.93 | 143.24 | 36.43 | 106.81 | 0.00 | 0.00 |
Minimum of Months | 302.98 | 0.04 | 122.83 | 24.83 | 92.11 | 0.00 | 0.00 |
Maximum of Months | 474.04 | 14.36 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.02 | 17.76 | 59.92 | 24.95 | 34.97 | 0.00 | 0.00 |
February | 107.50 | 14.49 | 50.69 | 16.35 | 34.34 | 0.00 | 0.00 |
March | 80.29 | 10.91 | 35.35 | 5.25 | 30.10 | 0.00 | 0.00 |
April | 60.39 | 5.78 | 26.20 | 0.15 | 26.05 | 0.00 | 0.00 |
May | 61.32 | 6.44 | 25.94 | 0.00 | 25.94 | 0.00 | 0.00 |
June | 60.77 | 6.77 | 25.85 | 0.00 | 25.85 | 0.00 | 0.00 |
July | 54.40 | 11.00 | 26.63 | 0.00 | 26.63 | 0.00 | 0.00 |
August | 52.18 | 9.99 | 25.89 | 0.00 | 25.89 | 0.00 | 0.00 |
September | 60.38 | 9.95 | 28.57 | 0.78 | 27.79 | 0.00 | 0.00 |
October | 74.14 | 12.37 | 37.21 | 5.65 | 31.56 | 0.00 | 0.00 |
November | 97.25 | 14.11 | 49.11 | 15.17 | 33.94 | 0.00 | 0.00 |
December | 117.65 | 19.95 | 60.13 | 25.67 | 34.47 | 0.00 | 0.00 |
Annual Sum or Average | 78.64 | 11.63 | 37.57 | 7.80 | 29.77 | 0.00 | 0.00 |
Minimum of Months | 52.18 | 5.78 | 25.85 | 0.00 | 25.85 | 0.00 | 0.00 |
Maximum of Months | 119.02 | 19.95 | 60.13 | 25.67 | 34.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.72 | 2.30 | 22.67 | 0.00 | 22.67 | 0.00 | 0.00 |
February | 75.86 | 0.47 | 24.18 | 0.00 | 24.18 | 0.00 | 0.00 |
March | 86.06 | 0.07 | 24.84 | 0.00 | 24.84 | 0.00 | 0.00 |
April | 98.96 | 0.00 | 27.53 | 0.66 | 26.86 | 0.00 | 0.00 |
May | 116.02 | 0.02 | 34.53 | 3.60 | 30.94 | 0.00 | 0.00 |
June | 132.02 | 0.04 | 42.43 | 8.68 | 33.75 | 0.00 | 0.00 |
July | 104.88 | 0.06 | 36.43 | 3.87 | 32.57 | 0.00 | 0.00 |
August | 92.96 | 0.01 | 30.13 | 1.41 | 28.71 | 0.00 | 0.00 |
September | 83.83 | 0.02 | 25.56 | 0.04 | 25.51 | 0.00 | 0.00 |
October | 75.51 | 0.01 | 24.57 | 0.00 | 24.57 | 0.00 | 0.00 |
November | 70.24 | 0.46 | 23.24 | 0.00 | 23.24 | 0.00 | 0.00 |
December | 63.76 | 3.06 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
Annual Sum or Average | 89.01 | 0.55 | 28.19 | 1.53 | 26.67 | 0.00 | 0.00 |
Minimum of Months | 63.76 | 0.00 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 3.06 | 42.43 | 8.68 | 33.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.23 | 10.71 | 176.90 | 65.58 | 111.32 | 0.00 | 0.00 |
February | 442.54 | 3.70 | 178.96 | 62.77 | 116.19 | 0.00 | 0.00 |
March | 449.69 | 0.64 | 170.40 | 55.96 | 114.44 | 0.00 | 0.00 |
April | 449.69 | 0.01 | 160.08 | 48.76 | 111.33 | 0.00 | 0.00 |
May | 420.92 | 0.08 | 142.04 | 33.22 | 108.82 | 0.00 | 0.00 |
June | 429.39 | 0.12 | 148.98 | 38.41 | 110.57 | 0.00 | 0.00 |
July | 354.43 | 0.26 | 133.06 | 22.40 | 110.67 | 0.00 | 0.00 |
August | 374.93 | 0.10 | 142.04 | 32.24 | 109.80 | 0.00 | 0.00 |
September | 375.52 | 0.07 | 138.75 | 29.08 | 109.67 | 0.00 | 0.00 |
October | 363.97 | 0.25 | 143.19 | 31.86 | 111.32 | 0.00 | 0.00 |
November | 378.93 | 2.17 | 154.98 | 44.86 | 110.12 | 0.00 | 0.00 |
December | 397.98 | 13.73 | 170.84 | 62.81 | 108.02 | 0.00 | 0.00 |
Annual Sum or Average | 404.42 | 2.67 | 154.87 | 43.88 | 110.99 | 0.00 | 0.00 |
Minimum of Months | 354.43 | 0.01 | 133.06 | 22.40 | 108.02 | 0.00 | 0.00 |
Maximum of Months | 449.69 | 13.73 | 178.96 | 65.58 | 116.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.25 | 10.33 | 130.32 | 34.38 | 95.94 | 0.00 | 0.00 |
February | 368.54 | 3.48 | 145.82 | 42.34 | 103.48 | 0.00 | 0.00 |
March | 418.72 | 0.60 | 157.25 | 49.40 | 107.85 | 0.00 | 0.00 |
April | 453.37 | 0.01 | 161.73 | 49.40 | 112.33 | 0.00 | 0.00 |
May | 444.46 | 0.22 | 152.76 | 37.71 | 115.05 | 0.00 | 0.00 |
June | 474.05 | 0.34 | 169.70 | 49.27 | 120.43 | 0.00 | 0.00 |
July | 380.59 | 0.59 | 145.31 | 27.23 | 118.08 | 0.00 | 0.00 |
August | 386.12 | 0.22 | 147.33 | 34.01 | 113.32 | 0.00 | 0.00 |
September | 366.75 | 0.25 | 134.97 | 28.16 | 106.82 | 0.00 | 0.00 |
October | 329.85 | 0.39 | 127.37 | 24.80 | 102.56 | 0.00 | 0.00 |
November | 312.42 | 2.85 | 122.63 | 25.89 | 96.74 | 0.00 | 0.00 |
December | 300.23 | 13.59 | 123.18 | 30.72 | 92.46 | 0.00 | 0.00 |
Annual Sum or Average | 379.63 | 2.76 | 143.13 | 36.04 | 107.10 | 0.00 | 0.00 |
Minimum of Months | 300.23 | 0.01 | 122.63 | 24.80 | 92.46 | 0.00 | 0.00 |
Maximum of Months | 474.05 | 13.59 | 169.70 | 49.40 | 120.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.14 | 22.35 | 178.95 | 54.07 | 124.88 | 0.00 | 0.00 |
February | 418.26 | 13.38 | 162.22 | 35.42 | 126.80 | 0.00 | 0.00 |
March | 383.22 | 4.23 | 130.39 | 11.37 | 119.02 | 0.00 | 0.00 |
April | 375.43 | 0.54 | 116.41 | 1.76 | 114.65 | 0.00 | 0.00 |
May | 412.19 | 1.72 | 131.02 | 7.79 | 123.23 | 0.00 | 0.00 |
June | 438.62 | 2.09 | 147.94 | 18.81 | 129.12 | 0.00 | 0.00 |
July | 371.22 | 3.77 | 136.63 | 8.37 | 128.25 | 0.00 | 0.00 |
August | 346.48 | 1.41 | 121.37 | 3.07 | 118.30 | 0.00 | 0.00 |
September | 343.16 | 1.62 | 117.27 | 1.79 | 115.48 | 0.00 | 0.00 |
October | 353.36 | 2.67 | 133.84 | 12.23 | 121.61 | 0.00 | 0.00 |
November | 388.48 | 8.90 | 156.77 | 32.88 | 123.89 | 0.00 | 0.00 |
December | 419.32 | 27.30 | 178.00 | 55.61 | 122.39 | 0.00 | 0.00 |
Annual Sum or Average | 389.88 | 7.50 | 142.49 | 20.21 | 122.28 | 0.00 | 0.00 |
Minimum of Months | 343.16 | 0.54 | 116.41 | 1.76 | 114.65 | 0.00 | 0.00 |
Maximum of Months | 438.62 | 27.30 | 178.95 | 55.61 | 129.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.18 | 9.22 | 178.38 | 67.64 | 110.74 | 0.00 | 0.00 |
February | 434.61 | 2.52 | 176.93 | 60.66 | 116.27 | 0.00 | 0.00 |
March | 448.68 | 0.34 | 171.27 | 56.69 | 114.58 | 0.00 | 0.00 |
April | 445.74 | 0.01 | 160.49 | 49.03 | 111.46 | 0.00 | 0.00 |
May | 416.05 | 0.07 | 141.30 | 32.31 | 108.99 | 0.00 | 0.00 |
June | 428.63 | 0.08 | 150.18 | 40.60 | 109.57 | 0.00 | 0.00 |
July | 352.33 | 0.18 | 133.76 | 23.65 | 110.11 | 0.00 | 0.00 |
August | 371.29 | 0.06 | 141.95 | 32.57 | 109.38 | 0.00 | 0.00 |
September | 369.18 | 0.02 | 138.01 | 29.32 | 108.69 | 0.00 | 0.00 |
October | 358.74 | 0.13 | 142.70 | 31.89 | 110.81 | 0.00 | 0.00 |
November | 375.45 | 1.53 | 155.18 | 44.58 | 110.61 | 0.00 | 0.00 |
December | 395.12 | 12.01 | 171.24 | 63.57 | 107.67 | 0.00 | 0.00 |
Annual Sum or Average | 400.85 | 2.20 | 154.98 | 44.28 | 110.70 | 0.00 | 0.00 |
Minimum of Months | 352.33 | 0.01 | 133.76 | 23.65 | 107.67 | 0.00 | 0.00 |
Maximum of Months | 448.68 | 12.01 | 178.38 | 67.64 | 116.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.01 | 9.15 | 131.80 | 36.45 | 95.35 | 0.00 | 0.00 |
February | 362.71 | 2.42 | 143.78 | 40.22 | 103.56 | 0.00 | 0.00 |
March | 417.90 | 0.34 | 158.12 | 50.13 | 107.99 | 0.00 | 0.00 |
April | 448.98 | 0.01 | 162.13 | 49.67 | 112.46 | 0.00 | 0.00 |
May | 439.04 | 0.24 | 152.03 | 36.80 | 115.22 | 0.00 | 0.00 |
June | 472.45 | 0.37 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
July | 378.07 | 0.59 | 146.01 | 28.49 | 117.52 | 0.00 | 0.00 |
August | 382.10 | 0.24 | 147.23 | 34.33 | 112.90 | 0.00 | 0.00 |
September | 360.42 | 0.32 | 134.24 | 28.40 | 105.83 | 0.00 | 0.00 |
October | 325.03 | 0.37 | 126.88 | 24.83 | 102.05 | 0.00 | 0.00 |
November | 310.14 | 2.39 | 122.83 | 25.61 | 97.22 | 0.00 | 0.00 |
December | 300.13 | 12.24 | 123.59 | 31.48 | 92.11 | 0.00 | 0.00 |
Annual Sum or Average | 376.63 | 2.41 | 143.24 | 36.43 | 106.81 | 0.00 | 0.00 |
Minimum of Months | 300.13 | 0.01 | 122.83 | 24.83 | 92.11 | 0.00 | 0.00 |
Maximum of Months | 472.45 | 12.24 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.22 | 4.43 | 109.87 | 45.75 | 64.12 | 0.00 | 0.00 |
February | 238.09 | 1.03 | 92.94 | 29.97 | 62.97 | 0.00 | 0.00 |
March | 197.76 | 0.13 | 64.81 | 9.62 | 55.19 | 0.00 | 0.00 |
April | 170.58 | 0.00 | 48.05 | 0.28 | 47.77 | 0.00 | 0.00 |
May | 172.12 | 0.02 | 47.57 | 0.00 | 47.57 | 0.00 | 0.00 |
June | 169.76 | 0.01 | 47.40 | 0.00 | 47.40 | 0.00 | 0.00 |
July | 147.42 | 0.03 | 48.83 | 0.00 | 48.83 | 0.00 | 0.00 |
August | 148.26 | 0.01 | 47.48 | 0.00 | 47.47 | 0.00 | 0.00 |
September | 160.35 | 0.00 | 52.39 | 1.44 | 50.95 | 0.00 | 0.00 |
October | 182.05 | 0.03 | 68.23 | 10.35 | 57.88 | 0.00 | 0.00 |
November | 219.04 | 0.61 | 90.06 | 27.82 | 62.23 | 0.00 | 0.00 |
December | 250.31 | 5.79 | 110.26 | 47.06 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 192.43 | 1.02 | 68.90 | 14.31 | 54.59 | 0.00 | 0.00 |
Minimum of Months | 147.42 | 0.00 | 47.40 | 0.00 | 47.40 | 0.00 | 0.00 |
Maximum of Months | 256.22 | 5.79 | 110.26 | 47.06 | 64.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 491.35 | 72.38 | 198.34 | 0.00 | 198.34 | 0.00 | 0.00 |
February | 549.41 | 48.68 | 211.58 | 0.00 | 211.58 | 0.00 | 0.00 |
March | 600.79 | 23.48 | 217.29 | 0.01 | 217.28 | 0.00 | 0.00 |
April | 693.24 | 5.61 | 240.82 | 5.80 | 235.01 | 0.00 | 0.00 |
May | 845.98 | 12.31 | 302.12 | 31.47 | 270.65 | 0.00 | 0.00 |
June | 985.93 | 13.14 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
July | 777.87 | 28.50 | 318.75 | 33.82 | 284.93 | 0.00 | 0.00 |
August | 660.91 | 17.29 | 263.57 | 12.38 | 251.20 | 0.00 | 0.00 |
September | 586.80 | 18.79 | 223.59 | 0.39 | 223.20 | 0.00 | 0.00 |
October | 524.71 | 28.06 | 214.91 | 0.00 | 214.91 | 0.00 | 0.00 |
November | 499.06 | 42.05 | 203.35 | 0.00 | 203.35 | 0.00 | 0.00 |
December | 469.91 | 86.78 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Annual Sum or Average | 640.69 | 33.11 | 246.66 | 13.35 | 233.31 | 0.00 | 0.00 |
Minimum of Months | 469.91 | 5.61 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Maximum of Months | 985.93 | 86.78 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 479.93 | 78.01 | 198.34 | 0.00 | 198.34 | 0.00 | 0.00 |
February | 538.12 | 53.31 | 211.58 | 0.00 | 211.58 | 0.00 | 0.00 |
March | 587.84 | 27.27 | 217.29 | 0.01 | 217.28 | 0.00 | 0.00 |
April | 678.07 | 6.81 | 240.82 | 5.80 | 235.01 | 0.00 | 0.00 |
May | 831.68 | 14.50 | 302.12 | 31.47 | 270.65 | 0.00 | 0.00 |
June | 972.31 | 15.20 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
July | 764.71 | 32.91 | 318.75 | 33.82 | 284.93 | 0.00 | 0.00 |
August | 645.42 | 21.29 | 263.57 | 12.38 | 251.20 | 0.00 | 0.00 |
September | 572.72 | 22.84 | 223.59 | 0.39 | 223.20 | 0.00 | 0.00 |
October | 511.20 | 33.65 | 214.91 | 0.00 | 214.91 | 0.00 | 0.00 |
November | 487.10 | 47.62 | 203.35 | 0.00 | 203.35 | 0.00 | 0.00 |
December | 458.72 | 93.17 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Annual Sum or Average | 627.50 | 37.24 | 246.66 | 13.35 | 233.31 | 0.00 | 0.00 |
Minimum of Months | 458.72 | 6.81 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Maximum of Months | 972.31 | 93.17 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.51 | 55.79 | 307.21 | 99.96 | 207.25 | 0.00 | 0.00 |
February | 858.10 | 38.66 | 324.76 | 105.10 | 219.66 | 0.00 | 0.00 |
March | 879.17 | 21.33 | 327.63 | 105.35 | 222.28 | 0.00 | 0.00 |
April | 903.32 | 6.03 | 321.79 | 98.15 | 223.64 | 0.00 | 0.00 |
May | 860.21 | 10.93 | 294.78 | 70.92 | 223.86 | 0.00 | 0.00 |
June | 907.00 | 11.75 | 318.67 | 87.67 | 230.99 | 0.00 | 0.00 |
July | 763.05 | 21.56 | 278.35 | 49.62 | 228.73 | 0.00 | 0.00 |
August | 759.57 | 15.09 | 289.36 | 66.25 | 223.11 | 0.00 | 0.00 |
September | 762.94 | 16.31 | 273.71 | 57.23 | 216.48 | 0.00 | 0.00 |
October | 706.38 | 22.53 | 270.54 | 56.66 | 213.88 | 0.00 | 0.00 |
November | 733.94 | 31.72 | 277.60 | 70.75 | 206.85 | 0.00 | 0.00 |
December | 758.35 | 66.16 | 294.01 | 93.53 | 200.48 | 0.00 | 0.00 |
Annual Sum or Average | 806.41 | 26.50 | 297.99 | 79.91 | 218.07 | 0.00 | 0.00 |
Minimum of Months | 706.38 | 6.03 | 270.54 | 49.62 | 200.48 | 0.00 | 0.00 |
Maximum of Months | 907.00 | 66.16 | 327.63 | 105.35 | 230.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 787.86 | 50.39 | 347.68 | 116.47 | 231.22 | 0.00 | 0.00 |
February | 751.05 | 33.27 | 309.12 | 76.30 | 232.82 | 0.00 | 0.00 |
March | 652.97 | 12.15 | 239.47 | 24.49 | 214.98 | 0.00 | 0.00 |
April | 607.98 | 1.90 | 204.86 | 2.69 | 202.17 | 0.00 | 0.00 |
May | 668.71 | 5.67 | 224.66 | 10.79 | 213.87 | 0.00 | 0.00 |
June | 705.45 | 6.77 | 247.92 | 26.05 | 221.87 | 0.00 | 0.00 |
July | 596.99 | 13.88 | 233.56 | 11.59 | 221.97 | 0.00 | 0.00 |
August | 562.31 | 5.09 | 211.20 | 4.25 | 206.95 | 0.00 | 0.00 |
September | 563.61 | 6.83 | 210.01 | 3.79 | 206.22 | 0.00 | 0.00 |
October | 605.90 | 9.99 | 247.35 | 26.35 | 221.00 | 0.00 | 0.00 |
November | 693.05 | 24.01 | 298.95 | 70.83 | 228.12 | 0.00 | 0.00 |
December | 772.65 | 60.34 | 346.73 | 119.80 | 226.93 | 0.00 | 0.00 |
Annual Sum or Average | 663.56 | 19.18 | 259.94 | 40.99 | 218.94 | 0.00 | 0.00 |
Minimum of Months | 562.31 | 1.90 | 204.86 | 2.69 | 202.17 | 0.00 | 0.00 |
Maximum of Months | 787.86 | 60.34 | 347.68 | 119.80 | 232.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218510E+10 | 0.143412E+09 | 0.101488E+10 | 0.422614E+09 | 0.592265E+09 | 0.00 | 0.00 |
February | 0.178225E+10 | 97798543.14 | 0.775409E+09 | 0.250070E+09 | 0.525339E+09 | 0.00 | 0.00 |
March | 0.151767E+10 | 55870528.65 | 0.598658E+09 | 88846440.13 | 0.509811E+09 | 0.00 | 0.00 |
April | 0.117851E+10 | 7034356.13 | 0.429490E+09 | 2472579.53 | 0.427018E+09 | 0.00 | 0.00 |
May | 0.126196E+10 | 16280430.43 | 0.439386E+09 | 0.00 | 0.439386E+09 | 0.00 | 0.00 |
June | 0.118612E+10 | 18548425.30 | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.00 | 0.00 |
July | 0.112279E+10 | 44086884.25 | 0.451004E+09 | 0.00 | 0.451004E+09 | 0.00 | 0.00 |
August | 0.110622E+10 | 20996803.70 | 0.438513E+09 | 36987.92 | 0.438476E+09 | 0.00 | 0.00 |
September | 0.118011E+10 | 23694904.35 | 0.468298E+09 | 12832635.36 | 0.455465E+09 | 0.00 | 0.00 |
October | 0.146412E+10 | 38023538.50 | 0.630206E+09 | 95626572.27 | 0.534580E+09 | 0.00 | 0.00 |
November | 0.176579E+10 | 72838912.26 | 0.804987E+09 | 0.248710E+09 | 0.556277E+09 | 0.00 | 0.00 |
December | 0.215632E+10 | 0.165144E+09 | 0.101844E+10 | 0.434702E+09 | 0.583736E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179070E+11 | 0.703729E+09 | 0.749295E+10 | 0.155591E+10 | 0.593704E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110622E+10 | 7034356.13 | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218510E+10 | 0.165144E+09 | 0.101844E+10 | 0.434702E+09 | 0.592265E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612856E+10 | 0.412422E+09 | 0.285783E+10 | 0.119005E+10 | 0.166778E+10 | 0.00 | 0.00 |
February | 0.501468E+10 | 0.268873E+09 | 0.218350E+10 | 0.704181E+09 | 0.147932E+10 | 0.00 | 0.00 |
March | 0.431609E+10 | 0.153439E+09 | 0.168578E+10 | 0.250186E+09 | 0.143560E+10 | 0.00 | 0.00 |
April | 0.339659E+10 | 25730198.80 | 0.120942E+10 | 6962620.92 | 0.120245E+10 | 0.00 | 0.00 |
May | 0.360737E+10 | 58531674.79 | 0.123728E+10 | 0.00 | 0.123728E+10 | 0.00 | 0.00 |
June | 0.341281E+10 | 59059289.12 | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.00 | 0.00 |
July | 0.320733E+10 | 0.142132E+09 | 0.127000E+10 | 0.00 | 0.127000E+10 | 0.00 | 0.00 |
August | 0.314505E+10 | 79053723.54 | 0.123482E+10 | 104155.55 | 0.123472E+10 | 0.00 | 0.00 |
September | 0.336464E+10 | 86711321.25 | 0.131870E+10 | 36135855.08 | 0.128256E+10 | 0.00 | 0.00 |
October | 0.412816E+10 | 0.136462E+09 | 0.177462E+10 | 0.269278E+09 | 0.150534E+10 | 0.00 | 0.00 |
November | 0.496616E+10 | 0.227584E+09 | 0.226679E+10 | 0.700352E+09 | 0.156644E+10 | 0.00 | 0.00 |
December | 0.604518E+10 | 0.480388E+09 | 0.286785E+10 | 0.122409E+10 | 0.164376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.507326E+11 | 0.213039E+10 | 0.210997E+11 | 0.438134E+10 | 0.167183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314505E+10 | 25730198.80 | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.612856E+10 | 0.480388E+09 | 0.286785E+10 | 0.122409E+10 | 0.166778E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.831951E+10 | 0.465191E+09 | 0.371249E+10 | 0.154595E+10 | 0.216654E+10 | 0.00 | 0.00 |
February | 0.682281E+10 | 0.299618E+09 | 0.283649E+10 | 0.914771E+09 | 0.192172E+10 | 0.00 | 0.00 |
March | 0.588472E+10 | 0.161508E+09 | 0.218993E+10 | 0.325005E+09 | 0.186492E+10 | 0.00 | 0.00 |
April | 0.461258E+10 | 30464608.26 | 0.157110E+10 | 9044840.82 | 0.156206E+10 | 0.00 | 0.00 |
May | 0.483139E+10 | 71205086.00 | 0.160730E+10 | 0.00 | 0.160730E+10 | 0.00 | 0.00 |
June | 0.453594E+10 | 78296710.78 | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.00 | 0.00 |
July | 0.425718E+10 | 0.180021E+09 | 0.164980E+10 | 0.00 | 0.164980E+10 | 0.00 | 0.00 |
August | 0.420658E+10 | 92850062.18 | 0.160411E+10 | 135303.99 | 0.160397E+10 | 0.00 | 0.00 |
September | 0.455244E+10 | 92465098.22 | 0.171306E+10 | 46942532.26 | 0.166612E+10 | 0.00 | 0.00 |
October | 0.559474E+10 | 0.133955E+09 | 0.230533E+10 | 0.349808E+09 | 0.195552E+10 | 0.00 | 0.00 |
November | 0.674731E+10 | 0.245442E+09 | 0.294469E+10 | 0.909796E+09 | 0.203489E+10 | 0.00 | 0.00 |
December | 0.819442E+10 | 0.551942E+09 | 0.372551E+10 | 0.159016E+10 | 0.213534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.685596E+11 | 0.240296E+10 | 0.274097E+11 | 0.569162E+10 | 0.217180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.420658E+10 | 30464608.26 | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.831951E+10 | 0.551942E+09 | 0.372551E+10 | 0.159016E+10 | 0.216654E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112963E+10 | 29389213.98 | 0.477776E+09 | 0.181179E+09 | 0.296597E+09 | 0.00 | 0.00 |
February | 0.105786E+10 | 9211923.75 | 0.428026E+09 | 0.146750E+09 | 0.281277E+09 | 0.00 | 0.00 |
March | 0.120582E+10 | 1819313.98 | 0.458725E+09 | 0.151829E+09 | 0.306896E+09 | 0.00 | 0.00 |
April | 0.115948E+10 | 97095.18 | 0.415983E+09 | 0.127091E+09 | 0.288892E+09 | 0.00 | 0.00 |
May | 0.111738E+10 | 267148.59 | 0.378460E+09 | 86531119.76 | 0.291929E+09 | 0.00 | 0.00 |
June | 0.111300E+10 | 387187.93 | 0.389256E+09 | 0.105248E+09 | 0.284008E+09 | 0.00 | 0.00 |
July | 0.949707E+09 | 870396.58 | 0.358273E+09 | 63355417.25 | 0.294918E+09 | 0.00 | 0.00 |
August | 0.999487E+09 | 355832.83 | 0.380194E+09 | 87233773.61 | 0.292960E+09 | 0.00 | 0.00 |
September | 0.964008E+09 | 209691.96 | 0.357734E+09 | 76007007.34 | 0.281727E+09 | 0.00 | 0.00 |
October | 0.968116E+09 | 768177.48 | 0.382207E+09 | 85417110.97 | 0.296790E+09 | 0.00 | 0.00 |
November | 0.980721E+09 | 5888265.94 | 0.402232E+09 | 0.115544E+09 | 0.286689E+09 | 0.00 | 0.00 |
December | 0.106883E+10 | 37840666.89 | 0.458652E+09 | 0.170264E+09 | 0.288388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127140E+11 | 87104915.09 | 0.488752E+10 | 0.139645E+10 | 0.349107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.949707E+09 | 97095.18 | 0.357734E+09 | 63355417.25 | 0.281277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120582E+10 | 37840666.89 | 0.477776E+09 | 0.181179E+09 | 0.306896E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.874750E+09 | 29399386.72 | 0.353011E+09 | 97620505.06 | 0.255391E+09 | 0.00 | 0.00 |
February | 0.882051E+09 | 8988000.10 | 0.347838E+09 | 97306347.91 | 0.250532E+09 | 0.00 | 0.00 |
March | 0.112321E+10 | 1697939.84 | 0.423502E+09 | 0.134267E+09 | 0.289236E+09 | 0.00 | 0.00 |
April | 0.116895E+10 | 98110.90 | 0.420239E+09 | 0.128751E+09 | 0.291488E+09 | 0.00 | 0.00 |
May | 0.118037E+10 | 696017.06 | 0.407188E+09 | 98571341.44 | 0.308617E+09 | 0.00 | 0.00 |
June | 0.122872E+10 | 1011044.78 | 0.442956E+09 | 0.133384E+09 | 0.309573E+09 | 0.00 | 0.00 |
July | 0.101980E+10 | 1811298.55 | 0.391068E+09 | 76295470.63 | 0.314772E+09 | 0.00 | 0.00 |
August | 0.102937E+10 | 699348.35 | 0.394346E+09 | 91962336.82 | 0.302383E+09 | 0.00 | 0.00 |
September | 0.941311E+09 | 730437.47 | 0.347939E+09 | 73615512.48 | 0.274324E+09 | 0.00 | 0.00 |
October | 0.876909E+09 | 1136968.03 | 0.339838E+09 | 66510095.26 | 0.273328E+09 | 0.00 | 0.00 |
November | 0.809499E+09 | 7714140.88 | 0.318373E+09 | 66369645.99 | 0.252004E+09 | 0.00 | 0.00 |
December | 0.811498E+09 | 38474935.48 | 0.331020E+09 | 84315877.95 | 0.246704E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119464E+11 | 92457628.14 | 0.451732E+10 | 0.114897E+10 | 0.336835E+10 | 0.00 | 0.00 |
Minimum of Months | 0.809499E+09 | 98110.90 | 0.318373E+09 | 66369645.99 | 0.246704E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122872E+10 | 38474935.48 | 0.442956E+09 | 0.134267E+09 | 0.314772E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.318789E+09 | 47572561.07 | 0.160496E+09 | 66833161.06 | 93662786.16 | 0.00 | 0.00 |
February | 0.260070E+09 | 35047278.80 | 0.122626E+09 | 39546664.89 | 83078992.27 | 0.00 | 0.00 |
March | 0.215053E+09 | 29228249.14 | 94673987.22 | 14050379.47 | 80623607.75 | 0.00 | 0.00 |
April | 0.156518E+09 | 14978958.81 | 67921429.52 | 391019.39 | 67530410.13 | 0.00 | 0.00 |
May | 0.164229E+09 | 17244893.05 | 69486232.11 | 0.00 | 69486232.11 | 0.00 | 0.00 |
June | 0.157511E+09 | 17539989.37 | 67002720.86 | 0.00 | 67002720.86 | 0.00 | 0.00 |
July | 0.145710E+09 | 29472410.79 | 71323528.04 | 0.00 | 71323528.04 | 0.00 | 0.00 |
August | 0.139771E+09 | 26754038.21 | 69348227.89 | 5849.35 | 69342378.53 | 0.00 | 0.00 |
September | 0.156495E+09 | 25796625.17 | 74058349.55 | 2029382.34 | 72028967.21 | 0.00 | 0.00 |
October | 0.198563E+09 | 33135928.83 | 99662864.04 | 15122605.09 | 84540258.96 | 0.00 | 0.00 |
November | 0.252081E+09 | 36577928.67 | 0.127303E+09 | 39331600.67 | 87971427.44 | 0.00 | 0.00 |
December | 0.315118E+09 | 53444831.01 | 0.161059E+09 | 68744751.16 | 92314006.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.247991E+10 | 0.366794E+09 | 0.118496E+10 | 0.246055E+09 | 0.938905E+09 | 0.00 | 0.00 |
Minimum of Months | 0.139771E+09 | 14978958.81 | 67002720.86 | 0.00 | 67002720.86 | 0.00 | 0.00 |
Maximum of Months | 0.318789E+09 | 53444831.01 | 0.161059E+09 | 68744751.16 | 93662786.16 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181387E+09 | 6164547.20 | 60724100.24 | 0.00 | 60724100.24 | 0.00 | 0.00 |
February | 0.183519E+09 | 1142117.51 | 58507357.38 | 0.00 | 58507357.38 | 0.00 | 0.00 |
March | 0.230504E+09 | 196023.85 | 66523193.68 | 3317.10 | 66519876.59 | 0.00 | 0.00 |
April | 0.256513E+09 | 0.00 | 71349170.49 | 1719341.05 | 69629829.44 | 0.00 | 0.00 |
May | 0.310753E+09 | 55847.13 | 92494836.56 | 9633454.15 | 82861382.42 | 0.00 | 0.00 |
June | 0.342191E+09 | 105984.11 | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.00 | 0.00 |
July | 0.280907E+09 | 153627.16 | 97586225.79 | 10353414.93 | 87232810.86 | 0.00 | 0.00 |
August | 0.248986E+09 | 26378.92 | 80694351.16 | 3789203.30 | 76905147.87 | 0.00 | 0.00 |
September | 0.217276E+09 | 44785.23 | 66245541.57 | 116605.50 | 66128936.07 | 0.00 | 0.00 |
October | 0.202250E+09 | 30198.16 | 65795960.95 | 0.00 | 65795960.95 | 0.00 | 0.00 |
November | 0.182057E+09 | 1183881.83 | 60249166.34 | 0.00 | 60249166.34 | 0.00 | 0.00 |
December | 0.170770E+09 | 8195399.17 | 58992615.48 | 0.00 | 58992615.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.280711E+10 | 17298790.28 | 0.889153E+09 | 48126855.52 | 0.841027E+09 | 0.00 | 0.00 |
Minimum of Months | 0.170770E+09 | 0.00 | 58507357.38 | 0.00 | 58507357.38 | 0.00 | 0.00 |
Maximum of Months | 0.342191E+09 | 8195399.17 | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112287E+10 | 28677634.56 | 0.473817E+09 | 0.175654E+09 | 0.298162E+09 | 0.00 | 0.00 |
February | 0.107059E+10 | 8939635.90 | 0.432945E+09 | 0.151863E+09 | 0.281082E+09 | 0.00 | 0.00 |
March | 0.120444E+10 | 1724541.87 | 0.456397E+09 | 0.149876E+09 | 0.306521E+09 | 0.00 | 0.00 |
April | 0.116559E+10 | 35018.72 | 0.414939E+09 | 0.126379E+09 | 0.288560E+09 | 0.00 | 0.00 |
May | 0.112738E+10 | 220229.78 | 0.380428E+09 | 88968658.34 | 0.291459E+09 | 0.00 | 0.00 |
June | 0.111298E+10 | 305727.71 | 0.386161E+09 | 99564373.77 | 0.286597E+09 | 0.00 | 0.00 |
July | 0.949293E+09 | 692830.55 | 0.356393E+09 | 59987150.76 | 0.296406E+09 | 0.00 | 0.00 |
August | 0.100422E+10 | 260621.42 | 0.380450E+09 | 86357402.56 | 0.294092E+09 | 0.00 | 0.00 |
September | 0.973355E+09 | 182274.90 | 0.359650E+09 | 75374468.73 | 0.284276E+09 | 0.00 | 0.00 |
October | 0.974846E+09 | 663383.21 | 0.383513E+09 | 85340543.43 | 0.298172E+09 | 0.00 | 0.00 |
November | 0.982185E+09 | 5635444.19 | 0.401718E+09 | 0.116288E+09 | 0.285430E+09 | 0.00 | 0.00 |
December | 0.106595E+10 | 36778799.33 | 0.457568E+09 | 0.168235E+09 | 0.289333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127537E+11 | 84116142.14 | 0.488398E+10 | 0.138389E+10 | 0.350009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.949293E+09 | 35018.72 | 0.356393E+09 | 59987150.76 | 0.281082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120444E+10 | 36778799.33 | 0.473817E+09 | 0.175654E+09 | 0.306521E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863105E+09 | 27670208.35 | 0.349052E+09 | 92096303.80 | 0.256955E+09 | 0.00 | 0.00 |
February | 0.891577E+09 | 8430656.33 | 0.352756E+09 | 0.102419E+09 | 0.250337E+09 | 0.00 | 0.00 |
March | 0.112149E+10 | 1609953.33 | 0.421174E+09 | 0.132314E+09 | 0.288860E+09 | 0.00 | 0.00 |
April | 0.117514E+10 | 33188.10 | 0.419195E+09 | 0.128039E+09 | 0.291156E+09 | 0.00 | 0.00 |
May | 0.119044E+10 | 596973.01 | 0.409156E+09 | 0.101009E+09 | 0.308147E+09 | 0.00 | 0.00 |
June | 0.122875E+10 | 883702.62 | 0.439862E+09 | 0.127700E+09 | 0.312162E+09 | 0.00 | 0.00 |
July | 0.101939E+10 | 1575686.67 | 0.389188E+09 | 72927204.14 | 0.316260E+09 | 0.00 | 0.00 |
August | 0.103419E+10 | 586217.95 | 0.394602E+09 | 91085965.77 | 0.303516E+09 | 0.00 | 0.00 |
September | 0.950614E+09 | 652596.05 | 0.349855E+09 | 72982973.88 | 0.276872E+09 | 0.00 | 0.00 |
October | 0.883462E+09 | 1051908.75 | 0.341144E+09 | 66433527.72 | 0.274710E+09 | 0.00 | 0.00 |
November | 0.809793E+09 | 7395610.26 | 0.317860E+09 | 67113721.24 | 0.250746E+09 | 0.00 | 0.00 |
December | 0.804148E+09 | 36411329.49 | 0.329935E+09 | 82286475.08 | 0.247649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119721E+11 | 86898030.90 | 0.451378E+10 | 0.113641E+10 | 0.337737E+10 | 0.00 | 0.00 |
Minimum of Months | 0.804148E+09 | 33188.10 | 0.317860E+09 | 66433527.72 | 0.247649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122875E+10 | 36411329.49 | 0.439862E+09 | 0.132314E+09 | 0.316260E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115477E+10 | 59850080.64 | 0.479299E+09 | 0.144809E+09 | 0.334490E+09 | 0.00 | 0.00 |
February | 0.101184E+10 | 32359823.34 | 0.392442E+09 | 85686625.25 | 0.306756E+09 | 0.00 | 0.00 |
March | 0.102642E+10 | 11334207.56 | 0.349244E+09 | 30450450.97 | 0.318793E+09 | 0.00 | 0.00 |
April | 0.973117E+09 | 1399682.49 | 0.301733E+09 | 4571899.53 | 0.297161E+09 | 0.00 | 0.00 |
May | 0.110400E+10 | 4607853.99 | 0.350932E+09 | 20869291.99 | 0.330063E+09 | 0.00 | 0.00 |
June | 0.113689E+10 | 5411110.32 | 0.383454E+09 | 48767499.82 | 0.334686E+09 | 0.00 | 0.00 |
July | 0.994275E+09 | 10105805.60 | 0.365943E+09 | 22428968.45 | 0.343514E+09 | 0.00 | 0.00 |
August | 0.928019E+09 | 3770010.46 | 0.325069E+09 | 8221358.87 | 0.316848E+09 | 0.00 | 0.00 |
September | 0.889462E+09 | 4204567.90 | 0.303974E+09 | 4649713.78 | 0.299324E+09 | 0.00 | 0.00 |
October | 0.946431E+09 | 7148312.15 | 0.358478E+09 | 32766479.77 | 0.325711E+09 | 0.00 | 0.00 |
November | 0.100693E+10 | 23074290.27 | 0.406350E+09 | 85220640.90 | 0.321130E+09 | 0.00 | 0.00 |
December | 0.112310E+10 | 73110884.54 | 0.476767E+09 | 0.148951E+09 | 0.327817E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.122953E+11 | 0.236377E+09 | 0.449368E+10 | 0.637393E+09 | 0.385629E+10 | 0.00 | 0.00 |
Minimum of Months | 0.889462E+09 | 1399682.49 | 0.301733E+09 | 4571899.53 | 0.297161E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115477E+10 | 73110884.54 | 0.479299E+09 | 0.148951E+09 | 0.343514E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112006E+10 | 24681672.31 | 0.477776E+09 | 0.181179E+09 | 0.296597E+09 | 0.00 | 0.00 |
February | 0.105142E+10 | 6097211.92 | 0.428026E+09 | 0.146750E+09 | 0.281277E+09 | 0.00 | 0.00 |
March | 0.120173E+10 | 899557.43 | 0.458725E+09 | 0.151829E+09 | 0.306896E+09 | 0.00 | 0.00 |
April | 0.115535E+10 | 22528.62 | 0.415983E+09 | 0.127091E+09 | 0.288892E+09 | 0.00 | 0.00 |
May | 0.111436E+10 | 179699.47 | 0.378460E+09 | 86531119.76 | 0.291929E+09 | 0.00 | 0.00 |
June | 0.111102E+10 | 207339.33 | 0.389256E+09 | 0.105248E+09 | 0.284008E+09 | 0.00 | 0.00 |
July | 0.943687E+09 | 480785.49 | 0.358273E+09 | 63355417.25 | 0.294918E+09 | 0.00 | 0.00 |
August | 0.994473E+09 | 172595.08 | 0.380194E+09 | 87233773.61 | 0.292960E+09 | 0.00 | 0.00 |
September | 0.956911E+09 | 50934.67 | 0.357734E+09 | 76007007.34 | 0.281727E+09 | 0.00 | 0.00 |
October | 0.960850E+09 | 357597.27 | 0.382207E+09 | 85417110.97 | 0.296790E+09 | 0.00 | 0.00 |
November | 0.973160E+09 | 3958388.38 | 0.402232E+09 | 0.115544E+09 | 0.286689E+09 | 0.00 | 0.00 |
December | 0.105829E+10 | 32157836.42 | 0.458652E+09 | 0.170264E+09 | 0.288388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126413E+11 | 69266146.38 | 0.488752E+10 | 0.139645E+10 | 0.349107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.943687E+09 | 22528.62 | 0.357734E+09 | 63355417.25 | 0.281277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120173E+10 | 32157836.42 | 0.477776E+09 | 0.181179E+09 | 0.306896E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.867829E+09 | 24512308.90 | 0.353011E+09 | 97620505.06 | 0.255391E+09 | 0.00 | 0.00 |
February | 0.877475E+09 | 5844149.37 | 0.347838E+09 | 97306347.91 | 0.250532E+09 | 0.00 | 0.00 |
March | 0.111930E+10 | 900212.25 | 0.423502E+09 | 0.134267E+09 | 0.289236E+09 | 0.00 | 0.00 |
April | 0.116376E+10 | 20995.25 | 0.420239E+09 | 0.128751E+09 | 0.291488E+09 | 0.00 | 0.00 |
May | 0.117593E+10 | 646558.76 | 0.407188E+09 | 98571341.44 | 0.308617E+09 | 0.00 | 0.00 |
June | 0.122459E+10 | 963827.72 | 0.442956E+09 | 0.133384E+09 | 0.309573E+09 | 0.00 | 0.00 |
July | 0.101263E+10 | 1592114.53 | 0.391068E+09 | 76295470.63 | 0.314772E+09 | 0.00 | 0.00 |
August | 0.102341E+10 | 629937.35 | 0.394346E+09 | 91962336.82 | 0.302383E+09 | 0.00 | 0.00 |
September | 0.934219E+09 | 830150.97 | 0.347939E+09 | 73615512.48 | 0.274324E+09 | 0.00 | 0.00 |
October | 0.870555E+09 | 997009.31 | 0.339838E+09 | 66510095.26 | 0.273328E+09 | 0.00 | 0.00 |
November | 0.803880E+09 | 6191262.97 | 0.318373E+09 | 66369645.99 | 0.252004E+09 | 0.00 | 0.00 |
December | 0.803877E+09 | 32783982.49 | 0.331020E+09 | 84315877.95 | 0.246704E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118775E+11 | 75912509.87 | 0.451732E+10 | 0.114897E+10 | 0.336835E+10 | 0.00 | 0.00 |
Minimum of Months | 0.803877E+09 | 20995.25 | 0.318373E+09 | 66369645.99 | 0.246704E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122459E+10 | 32783982.49 | 0.442956E+09 | 0.134267E+09 | 0.314772E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.686256E+09 | 11853165.54 | 0.294287E+09 | 0.122546E+09 | 0.171741E+09 | 0.00 | 0.00 |
February | 0.575984E+09 | 2485237.97 | 0.224848E+09 | 72513142.25 | 0.152334E+09 | 0.00 | 0.00 |
March | 0.529670E+09 | 339890.71 | 0.173595E+09 | 25762909.92 | 0.147832E+09 | 0.00 | 0.00 |
April | 0.442151E+09 | 0.00 | 0.124541E+09 | 716976.88 | 0.123824E+09 | 0.00 | 0.00 |
May | 0.461015E+09 | 54565.87 | 0.127411E+09 | 0.00 | 0.127411E+09 | 0.00 | 0.00 |
June | 0.440031E+09 | 22748.60 | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.00 |
July | 0.394858E+09 | 88936.97 | 0.130780E+09 | 0.00 | 0.130780E+09 | 0.00 | 0.00 |
August | 0.397112E+09 | 13769.83 | 0.127158E+09 | 10725.43 | 0.127147E+09 | 0.00 | 0.00 |
September | 0.415617E+09 | 3438.37 | 0.135794E+09 | 3721094.83 | 0.132073E+09 | 0.00 | 0.00 |
October | 0.487597E+09 | 70187.94 | 0.182743E+09 | 27728953.05 | 0.155014E+09 | 0.00 | 0.00 |
November | 0.567752E+09 | 1582518.00 | 0.233424E+09 | 72118798.45 | 0.161305E+09 | 0.00 | 0.00 |
December | 0.670434E+09 | 15508651.27 | 0.295319E+09 | 0.126051E+09 | 0.169268E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606848E+10 | 32023111.07 | 0.217276E+10 | 0.451170E+09 | 0.172159E+10 | 0.00 | 0.00 |
Minimum of Months | 0.394858E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.00 |
Maximum of Months | 0.686256E+09 | 15508651.27 | 0.295319E+09 | 0.126051E+09 | 0.171741E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131604E+10 | 0.193866E+09 | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.00 | 0.00 |
February | 0.132914E+10 | 0.117770E+09 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
March | 0.160916E+10 | 62894486.20 | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.00 | 0.00 |
April | 0.179687E+10 | 14545982.45 | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.00 | 0.00 |
May | 0.226587E+10 | 32966251.12 | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.00 | 0.00 |
June | 0.255552E+10 | 34054644.22 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
July | 0.208343E+10 | 76323141.59 | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.00 | 0.00 |
August | 0.177019E+10 | 46298989.88 | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.00 | 0.00 |
September | 0.152099E+10 | 48698488.10 | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.00 | 0.00 |
October | 0.140537E+10 | 75160772.73 | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.00 | 0.00 |
November | 0.129356E+10 | 0.108992E+09 | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.00 | 0.00 |
December | 0.125861E+10 | 0.232444E+09 | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202048E+11 | 0.104401E+10 | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125861E+10 | 14545982.45 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
Maximum of Months | 0.255552E+10 | 0.232444E+09 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128545E+10 | 0.208939E+09 | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.00 | 0.00 |
February | 0.130183E+10 | 0.128972E+09 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
March | 0.157448E+10 | 73036689.93 | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.00 | 0.00 |
April | 0.175755E+10 | 17651548.97 | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.00 | 0.00 |
May | 0.222757E+10 | 38846525.19 | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.00 | 0.00 |
June | 0.252022E+10 | 39411040.23 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
July | 0.204821E+10 | 88146071.71 | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.00 | 0.00 |
August | 0.172870E+10 | 57029960.70 | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.00 | 0.00 |
September | 0.148450E+10 | 59210012.92 | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.00 | 0.00 |
October | 0.136919E+10 | 90130192.15 | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.00 | 0.00 |
November | 0.126255E+10 | 0.123431E+09 | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.00 | 0.00 |
December | 0.122864E+10 | 0.249539E+09 | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197889E+11 | 0.117434E+10 | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.00 | 0.00 |
Minimum of Months | 0.122864E+10 | 17651548.97 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252022E+10 | 0.249539E+09 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212266E+10 | 0.149429E+09 | 0.822829E+09 | 0.267738E+09 | 0.555092E+09 | 0.00 | 0.00 |
February | 0.207592E+10 | 93515080.10 | 0.785661E+09 | 0.254268E+09 | 0.531394E+09 | 0.00 | 0.00 |
March | 0.235476E+10 | 57122008.08 | 0.877523E+09 | 0.282171E+09 | 0.595352E+09 | 0.00 | 0.00 |
April | 0.234140E+10 | 15637557.77 | 0.834087E+09 | 0.254401E+09 | 0.579686E+09 | 0.00 | 0.00 |
May | 0.230400E+10 | 29274756.63 | 0.789542E+09 | 0.189965E+09 | 0.599577E+09 | 0.00 | 0.00 |
June | 0.235094E+10 | 30461797.70 | 0.825980E+09 | 0.227250E+09 | 0.598730E+09 | 0.00 | 0.00 |
July | 0.204375E+10 | 57740957.97 | 0.745543E+09 | 0.132906E+09 | 0.612637E+09 | 0.00 | 0.00 |
August | 0.203444E+10 | 40425015.16 | 0.775010E+09 | 0.177431E+09 | 0.597579E+09 | 0.00 | 0.00 |
September | 0.197753E+10 | 42271569.67 | 0.709467E+09 | 0.148347E+09 | 0.561120E+09 | 0.00 | 0.00 |
October | 0.189197E+10 | 60342157.54 | 0.724620E+09 | 0.151765E+09 | 0.572855E+09 | 0.00 | 0.00 |
November | 0.190238E+10 | 82214573.10 | 0.719544E+09 | 0.183392E+09 | 0.536151E+09 | 0.00 | 0.00 |
December | 0.203117E+10 | 0.177202E+09 | 0.787467E+09 | 0.250509E+09 | 0.536957E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.254309E+11 | 0.835636E+09 | 0.939727E+10 | 0.252014E+10 | 0.687713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.189197E+10 | 15637557.77 | 0.709467E+09 | 0.132906E+09 | 0.531394E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235476E+10 | 0.177202E+09 | 0.877523E+09 | 0.282171E+09 | 0.612637E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211021E+10 | 0.134956E+09 | 0.931235E+09 | 0.311947E+09 | 0.619288E+09 | 0.00 | 0.00 |
February | 0.181693E+10 | 80477945.02 | 0.747825E+09 | 0.184586E+09 | 0.563239E+09 | 0.00 | 0.00 |
March | 0.174892E+10 | 32532874.04 | 0.641399E+09 | 65590804.37 | 0.575808E+09 | 0.00 | 0.00 |
April | 0.157588E+10 | 4934876.31 | 0.531003E+09 | 6981416.84 | 0.524022E+09 | 0.00 | 0.00 |
May | 0.179108E+10 | 15178212.77 | 0.601723E+09 | 28890786.45 | 0.572832E+09 | 0.00 | 0.00 |
June | 0.182854E+10 | 17550137.99 | 0.642602E+09 | 67512181.24 | 0.575090E+09 | 0.00 | 0.00 |
July | 0.159897E+10 | 37170839.17 | 0.625568E+09 | 31049953.11 | 0.594518E+09 | 0.00 | 0.00 |
August | 0.150608E+10 | 13624931.77 | 0.565689E+09 | 11391145.45 | 0.554298E+09 | 0.00 | 0.00 |
September | 0.146089E+10 | 17703182.38 | 0.544342E+09 | 9821945.23 | 0.534520E+09 | 0.00 | 0.00 |
October | 0.162284E+10 | 26758212.18 | 0.662504E+09 | 70585523.65 | 0.591918E+09 | 0.00 | 0.00 |
November | 0.179638E+10 | 62237606.60 | 0.774881E+09 | 0.183582E+09 | 0.591299E+09 | 0.00 | 0.00 |
December | 0.206946E+10 | 0.161619E+09 | 0.928669E+09 | 0.320870E+09 | 0.607799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209262E+11 | 0.604743E+09 | 0.819744E+10 | 0.129281E+10 | 0.690463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.146089E+10 | 4934876.31 | 0.531003E+09 | 6981416.84 | 0.524022E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211021E+10 | 0.161619E+09 | 0.931235E+09 | 0.320870E+09 | 0.619288E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770527E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162480524.6 | 81.21 | 0.00 | 0.00 |
February | 0.696267E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146690025.3 | 81.21 | 0.00 | 0.00 |
March | 0.770383E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162361298.6 | 81.21 | 0.00 | 0.00 |
April | 0.746567E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157067798.0 | 81.21 | 0.00 | 0.00 |
May | 0.770511E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162314397.9 | 81.21 | 0.00 | 0.00 |
June | 0.745757E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157041002.3 | 81.21 | 0.00 | 0.00 |
July | 0.771323E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162383205.8 | 81.21 | 0.00 | 0.00 |
August | 0.770524E+10 | -0.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162415686.5 | 81.21 | 0.00 | 0.00 |
September | 0.746709E+10 | -0.730995E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157139783.3 | 81.21 | 0.00 | 0.00 |
October | 0.770391E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162461835.6 | 81.21 | 0.00 | 0.00 |
November | 0.744967E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157227896.4 | 81.21 | 0.00 | 0.00 |
December | 0.771338E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162516083.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907526E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191210E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696267E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162516083.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771338E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146690025.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.889794E+11 | -0.872272E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175214E+10 | 81.25 | 0.00 | 0.00 |
February | 0.800755E+11 | -0.784960E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157943E+10 | 81.24 | 0.00 | 0.00 |
March | 0.878861E+11 | -0.861351E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175100E+10 | 81.24 | 0.00 | 0.00 |
April | 0.840329E+11 | -0.823389E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169398E+10 | 81.24 | 0.00 | 0.00 |
May | 0.857981E+11 | -0.840508E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174727E+10 | 81.24 | 0.00 | 0.00 |
June | 0.823124E+11 | -0.806262E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168623E+10 | 81.23 | 0.00 | 0.00 |
July | 0.848180E+11 | -0.830719E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174610E+10 | 81.25 | 0.00 | 0.00 |
August | 0.851489E+11 | -0.834007E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174817E+10 | 81.23 | 0.00 | 0.00 |
September | 0.831738E+11 | -0.814819E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169197E+10 | 81.24 | 0.00 | 0.00 |
October | 0.870070E+11 | -0.852538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175318E+10 | 81.24 | 0.00 | 0.00 |
November | 0.851933E+11 | -0.834992E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169403E+10 | 81.24 | 0.00 | 0.00 |
December | 0.887546E+11 | -0.870044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175020E+10 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 0.102318E+13 | -0.100259E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205937E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.800755E+11 | -0.872272E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175318E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.889794E+11 | -0.784960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157943E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.442500E+11 | -0.427520E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149806E+10 | 58.98 | 0.00 | 0.00 |
February | 0.397202E+11 | -0.383712E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134899E+10 | 58.97 | 0.00 | 0.00 |
March | 0.433423E+11 | -0.418454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149690E+10 | 58.97 | 0.00 | 0.00 |
April | 0.410418E+11 | -0.395940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144780E+10 | 58.98 | 0.00 | 0.00 |
May | 0.415193E+11 | -0.400276E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149162E+10 | 58.97 | 0.00 | 0.00 |
June | 0.395720E+11 | -0.381346E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143736E+10 | 58.97 | 0.00 | 0.00 |
July | 0.406507E+11 | -0.391610E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148964E+10 | 58.97 | 0.00 | 0.00 |
August | 0.409777E+11 | -0.394845E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149327E+10 | 58.97 | 0.00 | 0.00 |
September | 0.403015E+11 | -0.388564E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144504E+10 | 58.97 | 0.00 | 0.00 |
October | 0.425436E+11 | -0.410438E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149980E+10 | 58.97 | 0.00 | 0.00 |
November | 0.420276E+11 | -0.405797E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144797E+10 | 58.97 | 0.00 | 0.00 |
December | 0.440523E+11 | -0.425566E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149572E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.499999E+12 | -0.482407E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.175922E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.395720E+11 | -0.427520E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.149980E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.442500E+11 | -0.381346E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134899E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.87 | 0.86 | 01-JAN-08:09 | 1647.95 | 25.47 | 140.67 | 325.50 | 583.86 | 24.45 | 304.17 | 306.83 |
February | 321.17 | 0.87 | 0.86 | 01-FEB-06:49 | 1282.84 | 20.74 | 21.83 | 294.83 | 487.53 | 21.83 | 249.33 | 265.17 |
March | 361.17 | 0.87 | 0.86 | 01-MAR-08:09 | 969.28 | 19.79 | 0.00 | 330.33 | 389.62 | 21.52 | 257.17 | 287.67 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:19 | 794.33 | 19.48 | 0.00 | 327.67 | 326.80 | 21.20 | 200.00 | 267.33 |
May | 376.33 | 0.88 | 0.86 | 01-MAY-07:30 | 678.43 | 18.30 | 0.00 | 334.33 | 270.27 | 20.02 | 76.33 | 230.83 |
June | 370.50 | 0.88 | 0.86 | 01-JUN-08:30 | 655.00 | 18.57 | 0.00 | 327.00 | 272.11 | 20.32 | 59.67 | 242.67 |
July | 383.17 | 0.88 | 0.86 | 01-JUL-07:00 | 641.74 | 17.79 | 0.00 | 331.33 | 247.37 | 19.51 | 0.83 | 210.00 |
August | 369.33 | 0.88 | 0.86 | 01-AUG-07:40 | 761.87 | 18.76 | 0.00 | 333.67 | 299.90 | 20.46 | 113.50 | 258.50 |
September | 357.83 | 0.88 | 0.86 | 01-SEP-07:19 | 874.12 | 18.43 | 0.00 | 316.83 | 330.91 | 20.11 | 129.67 | 257.67 |
October | 356.83 | 0.87 | 0.86 | 01-OCT-07:49 | 1142.53 | 19.35 | 5.00 | 328.83 | 420.77 | 20.92 | 170.00 | 270.50 |
November | 337.67 | 0.87 | 0.86 | 01-NOV-07:30 | 1475.84 | 23.60 | 105.33 | 317.17 | 519.44 | 22.24 | 225.67 | 276.50 |
December | 349.33 | 0.87 | 0.86 | 01-DEC-06:00 | 1728.36 | 25.79 | 149.50 | 323.00 | 590.36 | 24.28 | 282.33 | 298.83 |
Annual Sum or Average | 4292.33 | 0.88 | 1041.97 | 20.44 | 422.33 | 3890.50 | 390.79 | 21.36 | 2068.67 | 3172.50 | ||
Minimum of Months | 321.17 | 0.87 | 0.86 | 641.74 | 17.79 | 0.00 | 294.83 | 247.37 | 19.51 | 0.83 | 210.00 | |
Maximum of Months | 383.17 | 0.88 | 0.86 | 1728.36 | 25.79 | 149.50 | 334.33 | 590.36 | 24.45 | 304.17 | 306.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.26 | 0.22 | 01-JAN-07:19 | 1879.71 | 25.69 | 144.50 | 331.00 | 814.79 | 24.70 | 321.50 | 319.67 |
February | 321.17 | 0.27 | 0.22 | 01-FEB-06:49 | 1485.46 | 21.33 | 48.83 | 300.00 | 689.44 | 22.27 | 265.50 | 284.33 |
March | 361.17 | 0.26 | 0.22 | 01-MAR-07:40 | 1124.39 | 20.56 | 22.33 | 342.17 | 544.21 | 22.06 | 288.83 | 316.67 |
April | 358.33 | 0.26 | 0.22 | 01-APR-06:49 | 919.53 | 20.34 | 1.00 | 341.00 | 451.54 | 21.83 | 261.50 | 308.17 |
May | 376.33 | 0.28 | 0.22 | 01-MAY-06:40 | 784.10 | 19.27 | 0.00 | 351.33 | 375.52 | 20.74 | 156.50 | 308.00 |
June | 370.50 | 0.28 | 0.22 | 01-JUN-07:30 | 760.79 | 19.50 | 0.00 | 344.33 | 377.51 | 21.01 | 198.33 | 302.17 |
July | 383.17 | 0.29 | 0.22 | 01-JUL-06:00 | 739.71 | 18.81 | 0.00 | 348.67 | 344.96 | 20.27 | 91.33 | 303.50 |
August | 369.33 | 0.27 | 0.22 | 01-AUG-06:49 | 876.77 | 19.70 | 0.00 | 351.33 | 414.34 | 21.16 | 192.50 | 309.67 |
September | 357.83 | 0.29 | 0.22 | 01-SEP-06:49 | 998.38 | 19.36 | 1.67 | 327.33 | 454.63 | 20.81 | 174.33 | 295.83 |
October | 356.83 | 0.26 | 0.22 | 01-OCT-06:30 | 1299.51 | 20.18 | 21.17 | 340.00 | 576.94 | 21.54 | 231.17 | 306.50 |
November | 337.67 | 0.25 | 0.22 | 01-NOV-06:00 | 1674.96 | 24.01 | 111.33 | 326.00 | 717.67 | 22.71 | 265.67 | 302.50 |
December | 349.33 | 0.26 | 0.22 | 01-DEC-06:40 | 1959.84 | 26.01 | 149.50 | 329.33 | 821.16 | 24.55 | 313.33 | 315.50 |
Annual Sum or Average | 4292.33 | 0.27 | 1194.50 | 21.17 | 500.33 | 4032.50 | 542.74 | 21.93 | 2760.50 | 3672.50 | ||
Minimum of Months | 321.17 | 0.25 | 0.22 | 739.71 | 18.81 | 0.00 | 300.00 | 344.96 | 20.27 | 91.33 | 284.33 | |
Maximum of Months | 383.17 | 0.29 | 0.22 | 1959.84 | 26.01 | 149.50 | 351.33 | 821.16 | 24.70 | 321.50 | 319.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.66 | 0.60 | 01-JAN-09:09 | 501.47 | 15.96 | 0.00 | 311.00 | 229.27 | 19.17 | 0.00 | 239.83 |
February | 321.17 | 0.65 | 0.60 | 01-FEB-08:09 | 550.90 | 16.45 | 0.00 | 287.00 | 252.35 | 19.63 | 0.00 | 242.33 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-08:09 | 632.98 | 17.31 | 0.00 | 333.17 | 290.54 | 20.48 | 14.17 | 293.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 799.57 | 18.10 | 0.00 | 343.17 | 350.28 | 21.28 | 122.50 | 304.83 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:19 | 950.69 | 18.70 | 27.67 | 357.17 | 387.47 | 21.32 | 156.83 | 323.17 |
June | 370.50 | 0.62 | 0.60 | 01-JUN-07:19 | 1155.80 | 22.10 | 102.50 | 356.00 | 455.56 | 23.22 | 253.00 | 332.67 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:40 | 1000.84 | 19.92 | 71.50 | 358.83 | 389.15 | 22.83 | 158.67 | 327.00 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 887.58 | 17.81 | 0.00 | 354.17 | 368.14 | 20.97 | 128.00 | 314.33 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:49 | 712.23 | 16.72 | 0.00 | 324.33 | 294.94 | 19.80 | 40.33 | 278.00 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:40 | 622.12 | 16.54 | 0.00 | 324.83 | 260.69 | 19.63 | 0.00 | 264.17 |
November | 337.67 | 0.65 | 0.60 | 01-NOV-07:49 | 548.86 | 16.25 | 0.00 | 302.83 | 237.05 | 19.39 | 0.00 | 235.67 |
December | 349.33 | 0.66 | 0.60 | 01-DEC-07:40 | 492.48 | 15.74 | 0.00 | 304.67 | 222.09 | 18.94 | 0.00 | 230.50 |
Annual Sum or Average | 4292.33 | 0.64 | 745.38 | 17.69 | 201.67 | 3957.17 | 313.99 | 20.60 | 873.50 | 3385.50 | ||
Minimum of Months | 321.17 | 0.62 | 0.60 | 492.48 | 15.74 | 0.00 | 287.00 | 222.09 | 18.94 | 0.00 | 230.50 | |
Maximum of Months | 383.17 | 0.66 | 0.60 | 1155.80 | 22.10 | 102.50 | 358.83 | 455.56 | 23.22 | 253.00 | 332.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.66 | 0.60 | 01-JAN-09:09 | 501.47 | 15.96 | 0.00 | 311.00 | 229.27 | 19.17 | 0.00 | 239.83 |
February | 321.17 | 0.65 | 0.60 | 01-FEB-08:09 | 550.90 | 16.45 | 0.00 | 287.00 | 252.35 | 19.63 | 0.00 | 242.33 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-08:09 | 632.98 | 17.31 | 0.00 | 333.17 | 290.54 | 20.48 | 14.17 | 293.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 799.57 | 18.10 | 0.00 | 343.17 | 350.28 | 21.28 | 122.50 | 304.83 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:19 | 950.69 | 18.70 | 27.67 | 357.17 | 387.47 | 21.32 | 156.83 | 323.17 |
June | 370.50 | 0.62 | 0.60 | 01-JUN-07:19 | 1155.80 | 22.10 | 102.50 | 356.00 | 455.56 | 23.22 | 253.00 | 332.67 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:40 | 1000.84 | 19.92 | 71.50 | 358.83 | 389.15 | 22.83 | 158.67 | 327.00 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 887.58 | 17.81 | 0.00 | 354.17 | 368.14 | 20.97 | 128.00 | 314.33 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:49 | 712.23 | 16.72 | 0.00 | 324.33 | 294.94 | 19.80 | 40.33 | 278.00 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:40 | 622.12 | 16.54 | 0.00 | 324.83 | 260.69 | 19.63 | 0.00 | 264.17 |
November | 337.67 | 0.65 | 0.60 | 01-NOV-07:49 | 548.86 | 16.25 | 0.00 | 302.83 | 237.05 | 19.39 | 0.00 | 235.67 |
December | 349.33 | 0.66 | 0.60 | 01-DEC-07:40 | 492.48 | 15.74 | 0.00 | 304.67 | 222.09 | 18.94 | 0.00 | 230.50 |
Annual Sum or Average | 4292.33 | 0.64 | 745.38 | 17.69 | 201.67 | 3957.17 | 313.99 | 20.60 | 873.50 | 3385.50 | ||
Minimum of Months | 321.17 | 0.62 | 0.60 | 492.48 | 15.74 | 0.00 | 287.00 | 222.09 | 18.94 | 0.00 | 230.50 | |
Maximum of Months | 383.17 | 0.66 | 0.60 | 1155.80 | 22.10 | 102.50 | 358.83 | 455.56 | 23.22 | 253.00 | 332.67 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147778E+10 | 5005.60 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112947E+10 | 4552.41 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123607E+10 | 5341.33 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107436E+10 | 5211.18 | 10-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123631E+10 | 5040.76 | 26-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105464E+10 | 4632.19 | 05-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126030E+10 | 5144.06 | 01-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148025E+10 | 5758.43 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127891E+10 | 5702.24 | 16-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156494E+10 | 5813.63 | 23-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142101E+10 | 5341.35 | 27-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151431E+10 | 5005.62 | 21-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.105464E+10 | 4552.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156494E+10 | 5813.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 599376.43 | 257.14 | 20-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 599376.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 599376.43 | 257.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7117.04 | 0.22 | 06-JAN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6286.35 | 0.22 | 16-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7441.29 | 0.22 | 31-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9355.43 | 0.22 | 27-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7714.94 | 0.22 | 13-MAY-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8120.85 | 0.22 | 07-JUN-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10214.23 | 0.22 | 04-JUL-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7118.94 | 0.22 | 13-AUG-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9829.99 | 0.22 | 06-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10366.95 | 0.22 | 18-OCT-22:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7968.48 | 0.22 | 02-NOV-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6250.01 | 0.22 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97784.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6250.01 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10366.95 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1222829.72 | 1584.16 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1455046.02 | 1450.80 | 24-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 996610.52 | 1584.58 | 03-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 616569.54 | 1207.06 | 15-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 690705.71 | 1577.55 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1196272.76 | 1358.94 | 26-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3453108.09 | 1587.58 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1249056.61 | 1473.86 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1408151.12 | 1396.35 | 16-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1284134.20 | 1587.53 | 10-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1194949.77 | 1582.45 | 02-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1539154.78 | 1582.10 | 20-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16306588.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 616569.54 | 1207.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3453108.09 | 1587.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1736743.00 | 1585.30 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 980167.43 | 1588.97 | 24-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1636716.22 | 1585.32 | 04-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 739037.03 | 1323.69 | 15-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 600719.14 | 1579.84 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 454236.33 | 1250.06 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2877327.80 | 1579.11 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1323237.48 | 1514.82 | 05-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2277788.40 | 1424.31 | 16-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2016133.42 | 1585.03 | 26-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2343635.74 | 1582.68 | 28-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1628635.57 | 1587.48 | 15-DEC-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18614377.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 454236.33 | 1250.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2877327.80 | 1588.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27762206.92 | 18688.73 | 24-JAN-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21595806.38 | 16163.79 | 12-FEB-19:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31572936.37 | 17741.33 | 03-MAR-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24887801.22 | 16189.68 | 15-APR-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5380507.88 | 9376.42 | 11-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6574308.55 | 12483.58 | 30-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17820756.91 | 15171.02 | 17-JUL-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16225176.35 | 14741.58 | 06-AUG-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17357589.66 | 16128.88 | 03-SEP-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6870825.71 | 13264.63 | 09-OCT-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10522770.05 | 10496.76 | 28-NOV-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30820295.54 | 18500.96 | 20-DEC-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5380507.88 | 9376.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31572936.37 | 18688.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48531.50 | 221.15 | 02-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53946.13 | 417.96 | 18-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1727.11 | 20.15 | 01-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2017.66 | 23.54 | 11-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 126042.03 | 685.79 | 20-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 132890.95 | 1040.36 | 18-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 228336.34 | 1574.83 | 23-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 124753.93 | 851.86 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56366.42 | 357.42 | 22-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 774612.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 228336.34 | 1574.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 422114.86 | 1388.23 | 09-JAN-07:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66069.85 | 511.08 | 15-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27873.82 | 295.26 | 18-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 118272.59 | 1379.85 | 29-JUL-06:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 166869.05 | 1062.88 | 20-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 194826.10 | 1334.82 | 18-SEP-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 321927.23 | 1447.07 | 22-OCT-19:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81705.69 | 750.29 | 27-NOV-09:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 378428.01 | 1188.72 | 17-DEC-09:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1778087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 422114.86 | 1447.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 664471.24 | 397.49 | 24-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 557556.44 | 398.13 | 08-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 438050.76 | 398.08 | 12-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 388452.69 | 396.79 | 21-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417342.06 | 397.97 | 22-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 468441.52 | 398.06 | 26-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1108431.79 | 398.35 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 618920.18 | 398.10 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 574068.16 | 377.49 | 23-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 573042.65 | 399.18 | 10-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 462783.81 | 398.12 | 02-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 553307.22 | 398.08 | 20-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6824868.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 388452.69 | 377.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1108431.79 | 399.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 495078.41 | 399.09 | 23-JAN-09:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 311758.51 | 399.20 | 01-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 644741.62 | 398.83 | 05-MAR-07:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 424278.82 | 397.11 | 21-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 386709.69 | 397.40 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 215657.18 | 398.16 | 20-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 942836.17 | 398.37 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 633875.62 | 398.23 | 25-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 729978.45 | 398.09 | 24-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 835655.50 | 398.47 | 26-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 755705.42 | 399.34 | 22-NOV-07:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 566262.42 | 399.09 | 08-DEC-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6942537.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 215657.18 | 397.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 942836.17 | 399.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 518547.24 | 1883.38 | 01-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33993.42 | 396.59 | 16-FEB-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1420532.55 | 1647.07 | 15-MAR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1192360.47 | 1279.63 | 11-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 848406.64 | 1476.29 | 26-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 340060.39 | 1484.51 | 01-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1081517.66 | 1391.67 | 19-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1797509.97 | 1776.12 | 20-AUG-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1672459.75 | 1449.23 | 25-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2225811.18 | 1539.40 | 18-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 437337.38 | 2023.15 | 27-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 465322.23 | 2071.69 | 17-DEC-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12033858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 33993.42 | 396.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2225811.18 | 2071.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.927660E+12 | 0.507221E+12 | 471446.77 | 08-JAN-08:23 | 164610.12 | 1.00 |
February | 0.00 | 0.00 | 0.850215E+12 | 0.482361E+12 | 465919.81 | 17-FEB-06:50 | 172705.49 | 1.00 |
March | 0.00 | 0.00 | 0.984885E+12 | 0.546801E+12 | 511839.21 | 14-MAR-21:20 | 208002.91 | 1.00 |
April | 0.00 | 0.00 | 0.108567E+13 | 0.544446E+12 | 575100.56 | 10-APR-18:07 | 247883.90 | 1.00 |
May | 0.00 | 0.00 | 0.123382E+13 | 0.565357E+12 | 606446.11 | 31-MAY-20:20 | 229035.33 | 1.00 |
June | 0.00 | 0.00 | 0.120933E+13 | 0.553989E+12 | 588108.33 | 15-JUN-10:00 | 233461.19 | 1.00 |
July | 0.00 | 0.00 | 0.105131E+13 | 0.530040E+12 | 600058.82 | 17-JUL-18:50 | 206934.80 | 1.00 |
August | 0.00 | 0.00 | 0.117731E+13 | 0.531546E+12 | 592107.94 | 08-AUG-18:07 | 245145.52 | 1.00 |
September | 0.00 | 0.00 | 0.111134E+13 | 0.514809E+12 | 601562.73 | 15-SEP-19:25 | 198701.54 | 1.00 |
October | 0.00 | 0.00 | 0.110059E+13 | 0.515766E+12 | 567548.06 | 09-OCT-19:20 | 198127.39 | 1.00 |
November | 0.00 | 0.00 | 0.100939E+13 | 0.498378E+12 | 553938.97 | 30-NOV-23:00 | 198639.12 | 1.00 |
December | 0.00 | 0.00 | 0.989946E+12 | 0.498939E+12 | 521915.33 | 18-DEC-24:00 | 177753.65 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127315E+14 | 0.628965E+13 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.850215E+12 | 0.482361E+12 | 465919.81 | 164610.12 | 1.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123382E+13 | 0.565357E+12 | 606446.11 | 247883.90 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.577821E+11 | 0.331550E+11 | 44040.44 | 08-JAN-09:03 | 15315.95 | 0.79 |
February | 0.00 | 0.00 | 0.527113E+11 | 0.310032E+11 | 41854.11 | 13-FEB-06:50 | 15474.74 | 0.79 |
March | 0.00 | 0.00 | 0.609979E+11 | 0.348596E+11 | 38636.66 | 27-MAR-13:00 | 21220.02 | 0.79 |
April | 0.00 | 0.00 | 0.677701E+11 | 0.345865E+11 | 44437.98 | 10-APR-18:02 | 20071.90 | 0.79 |
May | 0.00 | 0.00 | 0.775428E+11 | 0.357355E+11 | 51677.37 | 10-MAY-21:10 | 17105.00 | 0.79 |
June | 0.00 | 0.00 | 0.745676E+11 | 0.344855E+11 | 50593.91 | 25-JUN-19:40 | 16895.52 | 0.79 |
July | 0.00 | 0.00 | 0.654993E+11 | 0.342664E+11 | 47849.78 | 10-JUL-15:00 | 15337.53 | 0.79 |
August | 0.00 | 0.00 | 0.744237E+11 | 0.345488E+11 | 50776.45 | 19-AUG-18:03 | 17022.32 | 0.79 |
September | 0.00 | 0.00 | 0.703157E+11 | 0.334783E+11 | 50918.60 | 15-SEP-20:40 | 16948.22 | 0.79 |
October | 0.00 | 0.00 | 0.705625E+11 | 0.340114E+11 | 53022.45 | 30-OCT-18:03 | 17592.92 | 0.79 |
November | 0.00 | 0.00 | 0.640725E+11 | 0.327425E+11 | 46554.98 | 26-NOV-09:03 | 17587.83 | 0.79 |
December | 0.00 | 0.00 | 0.611706E+11 | 0.329165E+11 | 44549.58 | 24-DEC-09:02 | 18464.91 | 0.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.797416E+12 | 0.405789E+12 | 0.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.527113E+11 | 0.310032E+11 | 38636.66 | 15315.95 | 0.79 | |
Maximum of Months | 0.00 | 0.00 | 0.775428E+11 | 0.357355E+11 | 53022.45 | 21220.02 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116144E+11 | 0.690711E+10 | 14992.71 | 08-JAN-09:02 | 10850.00 | 0.96 |
February | 0.00 | 0.00 | 0.112709E+11 | 0.696700E+10 | 14199.85 | 12-FEB-09:02 | 11450.90 | 0.97 |
March | 0.00 | 0.00 | 0.126018E+11 | 0.781686E+10 | 14445.13 | 15-MAR-08:61 | 11272.23 | 0.96 |
April | 0.00 | 0.00 | 0.124994E+11 | 0.758995E+10 | 14349.08 | 10-APR-08:61 | 11271.67 | 0.96 |
May | 0.00 | 0.00 | 0.126855E+11 | 0.738938E+10 | 15074.87 | 17-MAY-15:02 | 10712.99 | 0.96 |
June | 0.00 | 0.00 | 0.127269E+11 | 0.757551E+10 | 14457.25 | 27-JUN-08:62 | 11225.68 | 0.97 |
July | 0.00 | 0.00 | 0.111132E+11 | 0.619580E+10 | 14705.41 | 22-JUL-08:61 | 11041.13 | 0.96 |
August | 0.00 | 0.00 | 0.113455E+11 | 0.621215E+10 | 15996.34 | 20-AUG-15:02 | 9998.69 | 0.96 |
September | 0.00 | 0.00 | 0.111855E+11 | 0.619364E+10 | 15838.45 | 18-SEP-08:61 | 10205.81 | 0.96 |
October | 0.00 | 0.00 | 0.110499E+11 | 0.599426E+10 | 16027.33 | 30-OCT-18:02 | 9999.64 | 0.96 |
November | 0.00 | 0.00 | 0.110345E+11 | 0.624267E+10 | 15416.12 | 26-NOV-09:01 | 10517.41 | 0.96 |
December | 0.00 | 0.00 | 0.113227E+11 | 0.650790E+10 | 15288.14 | 24-DEC-09:02 | 10650.90 | 0.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.140450E+12 | 0.815922E+11 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.110345E+11 | 0.599426E+10 | 14199.85 | 9998.69 | 0.96 | |
Maximum of Months | 0.00 | 0.00 | 0.127269E+11 | 0.781686E+10 | 16027.33 | 11450.90 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.981755E+10 | 0.554383E+10 | 17162.90 | 07-JAN-09:11 | 10736.38 | 0.87 |
February | 0.00 | 0.00 | 0.995620E+10 | 0.588945E+10 | 16736.05 | 12-FEB-09:41 | 10626.33 | 0.90 |
March | 0.00 | 0.00 | 0.120381E+11 | 0.728838E+10 | 16086.58 | 15-MAR-08:61 | 10295.30 | 0.95 |
April | 0.00 | 0.00 | 0.125628E+11 | 0.762199E+10 | 15279.41 | 14-APR-17:02 | 12545.37 | 0.96 |
May | 0.00 | 0.00 | 0.130374E+11 | 0.769344E+10 | 16675.00 | 10-MAY-21:51 | 11297.55 | 0.96 |
June | 0.00 | 0.00 | 0.133680E+11 | 0.817606E+10 | 17371.48 | 25-JUN-21:51 | 10661.43 | 0.96 |
July | 0.00 | 0.00 | 0.114780E+11 | 0.654737E+10 | 17416.62 | 19-JUL-21:51 | 10968.97 | 0.95 |
August | 0.00 | 0.00 | 0.114962E+11 | 0.635849E+10 | 17048.15 | 19-AUG-20:11 | 9976.13 | 0.95 |
September | 0.00 | 0.00 | 0.109664E+11 | 0.601057E+10 | 17028.76 | 15-SEP-21:51 | 10111.66 | 0.95 |
October | 0.00 | 0.00 | 0.103907E+11 | 0.546769E+10 | 17892.56 | 23-OCT-08:61 | 9504.88 | 0.93 |
November | 0.00 | 0.00 | 0.977156E+10 | 0.525010E+10 | 16986.63 | 26-NOV-09:51 | 10078.26 | 0.90 |
December | 0.00 | 0.00 | 0.944758E+10 | 0.513473E+10 | 17631.50 | 24-DEC-09:41 | 9808.88 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.134330E+12 | 0.769821E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.944758E+10 | 0.513473E+10 | 15279.41 | 9504.88 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.133680E+11 | 0.817606E+10 | 17892.56 | 12545.37 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.682655E+11 | 0.409889E+11 | 45765.79 | 04-JAN-14:50 | 38766.61 | 1.00 |
February | 0.00 | 0.00 | 0.612694E+11 | 0.356108E+11 | 40154.29 | 04-FEB-09:00 | 30052.77 | 1.00 |
March | 0.00 | 0.00 | 0.598392E+11 | 0.299571E+11 | 35857.33 | 11-MAR-09:00 | 22693.40 | 1.00 |
April | 0.00 | 0.00 | 0.544740E+11 | 0.241838E+11 | 34137.42 | 30-APR-08:00 | 19011.83 | 1.00 |
May | 0.00 | 0.00 | 0.572796E+11 | 0.248498E+11 | 36781.72 | 07-MAY-08:00 | 22539.66 | 1.00 |
June | 0.00 | 0.00 | 0.555225E+11 | 0.240215E+11 | 35417.50 | 10-JUN-08:00 | 19664.04 | 1.00 |
July | 0.00 | 0.00 | 0.505257E+11 | 0.207553E+11 | 31611.20 | 15-JUL-08:00 | 16609.54 | 1.00 |
August | 0.00 | 0.00 | 0.508613E+11 | 0.199083E+11 | 34035.04 | 13-AUG-08:00 | 18315.73 | 0.99 |
September | 0.00 | 0.00 | 0.531499E+11 | 0.226251E+11 | 33871.41 | 03-SEP-08:00 | 18345.76 | 1.00 |
October | 0.00 | 0.00 | 0.570858E+11 | 0.258722E+11 | 38927.38 | 29-OCT-08:00 | 25355.99 | 1.00 |
November | 0.00 | 0.00 | 0.622930E+11 | 0.333394E+11 | 43930.14 | 23-NOV-09:00 | 34743.41 | 1.00 |
December | 0.00 | 0.00 | 0.678043E+11 | 0.401037E+11 | 45581.59 | 31-DEC-08:55 | 36159.27 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.698370E+12 | 0.342216E+12 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.505257E+11 | 0.199083E+11 | 31611.20 | 16609.54 | 0.99 | |
Maximum of Months | 0.00 | 0.00 | 0.682655E+11 | 0.409889E+11 | 45765.79 | 38766.61 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.671628E+11 | 0.391155E+11 | 108654.06 | 07-JAN-09:11 | 74138.79 | 0.80 |
February | 0.00 | 0.00 | 0.651043E+11 | 0.387476E+11 | 104187.43 | 12-FEB-09:41 | 74166.26 | 0.83 |
March | 0.00 | 0.00 | 0.766548E+11 | 0.468218E+11 | 107494.51 | 15-MAR-08:61 | 71750.71 | 0.87 |
April | 0.00 | 0.00 | 0.810637E+11 | 0.509365E+11 | 101550.71 | 14-APR-15:02 | 75753.66 | 0.89 |
May | 0.00 | 0.00 | 0.904386E+11 | 0.576823E+11 | 106041.92 | 17-MAY-15:02 | 72218.52 | 0.91 |
June | 0.00 | 0.00 | 0.937312E+11 | 0.612664E+11 | 113893.95 | 25-JUN-21:51 | 70620.12 | 0.92 |
July | 0.00 | 0.00 | 0.847787E+11 | 0.540811E+11 | 114256.37 | 19-JUL-21:51 | 71235.07 | 0.88 |
August | 0.00 | 0.00 | 0.808439E+11 | 0.490429E+11 | 114296.10 | 19-AUG-20:11 | 68475.58 | 0.87 |
September | 0.00 | 0.00 | 0.754475E+11 | 0.449206E+11 | 113355.75 | 15-SEP-18:41 | 67386.20 | 0.87 |
October | 0.00 | 0.00 | 0.731223E+11 | 0.423997E+11 | 115470.44 | 23-OCT-08:61 | 68191.23 | 0.85 |
November | 0.00 | 0.00 | 0.684286E+11 | 0.398431E+11 | 110917.39 | 26-NOV-09:51 | 69678.54 | 0.83 |
December | 0.00 | 0.00 | 0.659954E+11 | 0.377338E+11 | 114276.28 | 20-DEC-09:02 | 66872.73 | 0.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.922772E+12 | 0.562591E+12 | 0.86 | |||
Minimum of Months | 0.00 | 0.00 | 0.651043E+11 | 0.377338E+11 | 101550.71 | 66872.73 | 0.79 | |
Maximum of Months | 0.00 | 0.00 | 0.937312E+11 | 0.612664E+11 | 115470.44 | 75753.66 | 0.92 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116032E+11 | 0.697734E+10 | 12859.99 | 08-JAN-09:02 | 9995.49 | 0.97 |
February | 0.00 | 0.00 | 0.113430E+11 | 0.714682E+10 | 12057.17 | 08-FEB-09:02 | 10586.42 | 0.98 |
March | 0.00 | 0.00 | 0.125511E+11 | 0.792083E+10 | 12354.74 | 15-MAR-08:61 | 10373.95 | 0.98 |
April | 0.00 | 0.00 | 0.125535E+11 | 0.782572E+10 | 12426.16 | 14-APR-18:02 | 10280.96 | 0.98 |
May | 0.00 | 0.00 | 0.127567E+11 | 0.768468E+10 | 13702.93 | 17-MAY-15:02 | 9302.93 | 0.97 |
June | 0.00 | 0.00 | 0.127544E+11 | 0.775723E+10 | 12737.31 | 01-JUN-08:61 | 10042.76 | 0.98 |
July | 0.00 | 0.00 | 0.110940E+11 | 0.631011E+10 | 12802.27 | 22-JUL-08:61 | 10016.73 | 0.97 |
August | 0.00 | 0.00 | 0.113640E+11 | 0.635457E+10 | 14205.99 | 20-AUG-15:02 | 8912.90 | 0.97 |
September | 0.00 | 0.00 | 0.112652E+11 | 0.644191E+10 | 13869.59 | 18-SEP-08:61 | 9243.82 | 0.97 |
October | 0.00 | 0.00 | 0.110449E+11 | 0.614402E+10 | 14220.75 | 30-OCT-18:02 | 8923.88 | 0.97 |
November | 0.00 | 0.00 | 0.110397E+11 | 0.636290E+10 | 13617.69 | 26-NOV-09:01 | 9423.03 | 0.97 |
December | 0.00 | 0.00 | 0.113176E+11 | 0.661648E+10 | 13069.85 | 14-DEC-09:02 | 9860.46 | 0.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.140687E+12 | 0.835426E+11 | 0.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.110397E+11 | 0.614402E+10 | 12057.17 | 8912.90 | 0.97 | |
Maximum of Months | 0.00 | 0.00 | 0.127567E+11 | 0.792083E+10 | 14220.75 | 10586.42 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.971816E+10 | 0.547681E+10 | 15870.57 | 07-JAN-09:11 | 10065.34 | 0.88 |
February | 0.00 | 0.00 | 0.996458E+10 | 0.593444E+10 | 15485.15 | 12-FEB-09:41 | 9984.59 | 0.91 |
March | 0.00 | 0.00 | 0.119807E+11 | 0.732953E+10 | 14988.44 | 15-MAR-07:33 | 9874.97 | 0.97 |
April | 0.00 | 0.00 | 0.126110E+11 | 0.784699E+10 | 13448.96 | 14-APR-17:02 | 10675.14 | 0.98 |
May | 0.00 | 0.00 | 0.131083E+11 | 0.801822E+10 | 14647.79 | 10-MAY-21:51 | 9830.93 | 0.97 |
June | 0.00 | 0.00 | 0.133958E+11 | 0.844939E+10 | 15307.29 | 25-JUN-21:51 | 9301.84 | 0.97 |
July | 0.00 | 0.00 | 0.114619E+11 | 0.667398E+10 | 15248.06 | 19-JUL-21:51 | 9448.30 | 0.96 |
August | 0.00 | 0.00 | 0.115134E+11 | 0.650534E+10 | 15150.59 | 19-AUG-20:11 | 8844.03 | 0.96 |
September | 0.00 | 0.00 | 0.110440E+11 | 0.625805E+10 | 15085.52 | 15-SEP-21:51 | 8910.67 | 0.96 |
October | 0.00 | 0.00 | 0.103877E+11 | 0.562645E+10 | 15924.24 | 23-OCT-08:61 | 8495.79 | 0.94 |
November | 0.00 | 0.00 | 0.975924E+10 | 0.535364E+10 | 15338.25 | 02-NOV-07:42 | 10144.18 | 0.91 |
December | 0.00 | 0.00 | 0.936123E+10 | 0.515319E+10 | 16080.96 | 24-DEC-09:41 | 9107.12 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.134306E+12 | 0.786260E+11 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.936123E+10 | 0.515319E+10 | 13448.96 | 8495.79 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.133958E+11 | 0.844939E+10 | 16080.96 | 10675.14 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.296649E+10 | 0.174635E+10 | 4278.08 | 08-JAN-09:02 | 2813.55 | 0.97 |
February | 0.00 | 0.00 | 0.286600E+10 | 0.173551E+10 | 4006.58 | 12-FEB-09:02 | 3023.63 | 0.97 |
March | 0.00 | 0.00 | 0.325419E+10 | 0.198568E+10 | 4168.23 | 15-MAR-08:61 | 2901.79 | 0.97 |
April | 0.00 | 0.00 | 0.326082E+10 | 0.194857E+10 | 4089.04 | 10-APR-08:61 | 2942.12 | 0.97 |
May | 0.00 | 0.00 | 0.326223E+10 | 0.185835E+10 | 4210.09 | 26-MAY-08:61 | 2865.81 | 0.96 |
June | 0.00 | 0.00 | 0.324716E+10 | 0.187551E+10 | 4141.83 | 27-JUN-08:62 | 2911.46 | 0.97 |
July | 0.00 | 0.00 | 0.285100E+10 | 0.153937E+10 | 4208.75 | 22-JUL-08:61 | 2860.23 | 0.96 |
August | 0.00 | 0.00 | 0.292590E+10 | 0.155962E+10 | 4480.37 | 19-AUG-18:02 | 2635.32 | 0.96 |
September | 0.00 | 0.00 | 0.290796E+10 | 0.158185E+10 | 4531.65 | 18-SEP-08:61 | 2614.84 | 0.96 |
October | 0.00 | 0.00 | 0.283941E+10 | 0.150177E+10 | 4508.85 | 30-OCT-18:02 | 2616.23 | 0.96 |
November | 0.00 | 0.00 | 0.281715E+10 | 0.155921E+10 | 4439.30 | 26-NOV-09:01 | 2684.32 | 0.96 |
December | 0.00 | 0.00 | 0.287484E+10 | 0.163972E+10 | 4323.14 | 24-DEC-09:02 | 2785.27 | 0.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.360731E+11 | 0.205315E+11 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.281715E+10 | 0.150177E+10 | 4006.58 | 2614.84 | 0.96 | |
Maximum of Months | 0.00 | 0.00 | 0.326223E+10 | 0.198568E+10 | 4531.65 | 3023.63 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.252071E+10 | 0.139768E+10 | 4859.23 | 07-JAN-09:11 | 2829.53 | 0.87 |
February | 0.00 | 0.00 | 0.254554E+10 | 0.149009E+10 | 4672.50 | 12-FEB-09:41 | 2901.86 | 0.90 |
March | 0.00 | 0.00 | 0.311341E+10 | 0.186553E+10 | 4592.38 | 15-MAR-08:61 | 2639.09 | 0.95 |
April | 0.00 | 0.00 | 0.327764E+10 | 0.195710E+10 | 4213.09 | 14-APR-17:02 | 3537.75 | 0.97 |
May | 0.00 | 0.00 | 0.335691E+10 | 0.193991E+10 | 4595.54 | 10-MAY-21:51 | 3088.91 | 0.96 |
June | 0.00 | 0.00 | 0.342100E+10 | 0.204162E+10 | 4913.50 | 25-JUN-21:51 | 2886.54 | 0.96 |
July | 0.00 | 0.00 | 0.295019E+10 | 0.163918E+10 | 4943.48 | 19-JUL-21:51 | 3005.67 | 0.95 |
August | 0.00 | 0.00 | 0.296615E+10 | 0.159745E+10 | 4966.57 | 19-AUG-20:11 | 2557.44 | 0.95 |
September | 0.00 | 0.00 | 0.285417E+10 | 0.153419E+10 | 4824.28 | 15-SEP-21:51 | 2707.82 | 0.95 |
October | 0.00 | 0.00 | 0.267341E+10 | 0.136013E+10 | 5078.18 | 23-OCT-08:61 | 2444.71 | 0.93 |
November | 0.00 | 0.00 | 0.250026E+10 | 0.129827E+10 | 4800.97 | 26-NOV-09:51 | 2667.10 | 0.90 |
December | 0.00 | 0.00 | 0.241016E+10 | 0.128058E+10 | 5004.18 | 24-DEC-09:41 | 2620.03 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.345895E+11 | 0.194017E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.241016E+10 | 0.128058E+10 | 4213.09 | 2444.71 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.342100E+10 | 0.204162E+10 | 5078.18 | 3537.75 | 0.97 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177393E+11 | 0.119425E+11 | 16941.89 | 08-JAN-09:02 | 12098.01 | 0.97 |
February | 0.00 | 0.00 | 0.159786E+11 | 0.107852E+11 | 15712.89 | 08-FEB-09:02 | 13000.14 | 0.97 |
March | 0.00 | 0.00 | 0.161371E+11 | 0.104693E+11 | 16376.31 | 15-MAR-08:61 | 12525.38 | 0.96 |
April | 0.00 | 0.00 | 0.150556E+11 | 0.925836E+10 | 15827.34 | 10-APR-08:61 | 12840.66 | 0.96 |
May | 0.00 | 0.00 | 0.156434E+11 | 0.938315E+10 | 16591.84 | 17-MAY-15:02 | 12271.80 | 0.96 |
June | 0.00 | 0.00 | 0.152178E+11 | 0.908837E+10 | 16350.95 | 27-JUN-08:62 | 12501.81 | 0.96 |
July | 0.00 | 0.00 | 0.139699E+11 | 0.806553E+10 | 16768.45 | 22-JUL-08:61 | 12198.11 | 0.95 |
August | 0.00 | 0.00 | 0.140766E+11 | 0.791307E+10 | 19716.86 | 19-AUG-18:02 | 9905.41 | 0.95 |
September | 0.00 | 0.00 | 0.144637E+11 | 0.845506E+10 | 18787.85 | 18-SEP-08:61 | 10710.16 | 0.96 |
October | 0.00 | 0.00 | 0.152766E+11 | 0.914280E+10 | 19276.31 | 30-OCT-18:02 | 10264.51 | 0.96 |
November | 0.00 | 0.00 | 0.162708E+11 | 0.103860E+11 | 17960.97 | 26-NOV-09:01 | 11325.97 | 0.97 |
December | 0.00 | 0.00 | 0.175630E+11 | 0.115690E+11 | 17231.06 | 14-DEC-09:02 | 11909.18 | 0.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.187392E+12 | 0.116458E+12 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.139699E+11 | 0.791307E+10 | 15712.89 | 9905.41 | 0.95 | |
Maximum of Months | 0.00 | 0.00 | 0.177393E+11 | 0.119425E+11 | 19716.86 | 13000.14 | 0.97 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 560.34 | 20385.22 | 22-JAN-19:07 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 473.00 | 20512.97 | 12-FEB-19:07 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 471.43 | 22186.71 | 03-MAR-16:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 421.84 | 21877.62 | 23-APR-18:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 460.65 | 14581.43 | 21-MAY-18:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 407.45 | 17800.45 | 30-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 477.28 | 20933.44 | 16-JUL-18:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 556.69 | 21669.50 | 06-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 498.71 | 19234.88 | 03-SEP-18:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 584.95 | 19193.89 | 09-OCT-18:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 549.18 | 14008.85 | 11-NOV-19:07 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 573.51 | 19745.24 | 28-DEC-16:07 |
Annual Sum or Average | 0.00 | 503.53 | ||||
Minimum of Months | 0.00 | 0.00 | 407.45 | 14008.85 | ||
Maximum of Months | 0.00 | 0.00 | 584.95 | 22186.71 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 446600.48 | 686100.12 | 10-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 455376.64 | 673717.73 | 14-FEB-19:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 471699.44 | 675763.64 | 28-MAR-18:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 528504.85 | 810171.56 | 10-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 575859.77 | 829656.70 | 22-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 585049.63 | 811766.40 | 11-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 495219.03 | 746989.10 | 17-JUL-18:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 544549.00 | 826817.61 | 08-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 533954.01 | 784465.06 | 08-SEP-18:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 513136.19 | 746851.73 | 17-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 492450.46 | 742183.89 | 14-NOV-19:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 469887.60 | 714232.10 | 10-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 509520.03 | 0.00 | ||||
Minimum of Months | 446600.48 | 673717.73 | 0.00 | 0.00 | ||
Maximum of Months | 585049.63 | 829656.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17552.23 | 35124.88 | 10-JAN-07:36 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17453.82 | 35000.77 | 06-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17216.30 | 34667.59 | 02-MAR-07:45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16868.59 | 33804.97 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16540.03 | 33209.11 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16309.38 | 32550.84 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16217.41 | 32314.47 | 13-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16337.96 | 32642.56 | 29-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16586.62 | 33258.23 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16918.27 | 33995.77 | 30-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17248.69 | 34670.91 | 29-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 17480.59 | 34951.61 | 28-DEC-07:15 |
Annual Sum or Average | 0.00 | 16891.10 | ||||
Minimum of Months | 0.00 | 0.00 | 16217.41 | 32314.47 | ||
Maximum of Months | 0.00 | 0.00 | 17552.23 | 35124.88 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 05-JAN-16:07 | 0.87 |
February | 0.244774E+10 | 0.69 | 1299.30 | 01-FEB-09:15 | 0.87 |
March | 0.271000E+10 | 0.69 | 1299.30 | 04-MAR-16:17 | 0.87 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-15:17 | 0.87 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-08:50 | 0.87 |
June | 0.262258E+10 | 0.69 | 1299.30 | 02-JUN-18:40 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-19:20 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-08:05 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 01-SEP-19:20 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 10-OCT-15:07 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 02-NOV-15:20 | 0.87 |
December | 0.271000E+10 | 0.69 | 1299.30 | 07-DEC-16:17 | 0.87 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.69 | 1299.30 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.302789E+11 | 0.73 | 17113.90 | 05-JAN-21:10 | 0.93 |
February | 0.277613E+11 | 0.74 | 17071.57 | 22-FEB-21:10 | 0.92 |
March | 0.308711E+11 | 0.74 | 17350.92 | 29-MAR-20:10 | 0.93 |
April | 0.301356E+11 | 0.74 | 17964.41 | 27-APR-20:10 | 0.95 |
May | 0.314535E+11 | 0.75 | 19565.89 | 05-MAY-20:10 | 1.00 |
June | 0.313606E+11 | 0.76 | 21051.39 | 13-JUN-20:10 | 1.05 |
July | 0.306359E+11 | 0.74 | 18367.50 | 14-JUL-20:10 | 0.97 |
August | 0.303400E+11 | 0.73 | 17844.45 | 14-AUG-20:10 | 0.95 |
September | 0.293600E+11 | 0.73 | 17367.32 | 13-SEP-20:10 | 0.93 |
October | 0.298243E+11 | 0.73 | 16661.85 | 04-OCT-20:10 | 0.91 |
November | 0.290771E+11 | 0.73 | 16451.47 | 21-NOV-21:10 | 0.90 |
December | 0.300055E+11 | 0.73 | 16897.58 | 08-DEC-21:10 | 0.92 |
Annual Sum or Average | 0.361104E+12 | 0.74 | |||
Minimum of Months | 0.277613E+11 | 0.73 | 16451.47 | 0.90 | |
Maximum of Months | 0.314535E+11 | 0.76 | 21051.39 | 1.05 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:05 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:03 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:03 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:10 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:10 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:03 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.459578E+09 | 0.55 | 666.87 | 01-JAN-09:01 | 0.57 |
February | 0.451535E+09 | 0.55 | 666.87 | 01-FEB-09:02 | 0.57 |
March | 0.510143E+09 | 0.55 | 666.87 | 01-MAR-09:01 | 0.57 |
April | 0.498539E+09 | 0.55 | 666.87 | 01-APR-08:62 | 0.57 |
May | 0.490976E+09 | 0.55 | 666.87 | 01-MAY-08:62 | 0.57 |
June | 0.499055E+09 | 0.55 | 666.87 | 01-JUN-08:61 | 0.57 |
July | 0.430668E+09 | 0.55 | 666.87 | 01-JUL-08:61 | 0.57 |
August | 0.429667E+09 | 0.55 | 666.87 | 01-AUG-08:62 | 0.57 |
September | 0.426841E+09 | 0.55 | 666.87 | 01-SEP-08:62 | 0.57 |
October | 0.417011E+09 | 0.55 | 666.87 | 01-OCT-08:62 | 0.57 |
November | 0.419453E+09 | 0.55 | 666.87 | 01-NOV-08:61 | 0.57 |
December | 0.438638E+09 | 0.55 | 666.87 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.547211E+10 | 0.55 | |||
Minimum of Months | 0.417011E+09 | 0.55 | 666.87 | 0.57 | |
Maximum of Months | 0.510143E+09 | 0.55 | 666.87 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.380582E+09 | 0.50 | 675.12 | 01-JAN-09:01 | 0.57 |
February | 0.392844E+09 | 0.51 | 675.12 | 01-FEB-09:11 | 0.57 |
March | 0.481366E+09 | 0.55 | 675.12 | 01-MAR-09:01 | 0.57 |
April | 0.500321E+09 | 0.55 | 675.12 | 01-APR-08:62 | 0.57 |
May | 0.508819E+09 | 0.55 | 675.12 | 01-MAY-08:62 | 0.57 |
June | 0.534085E+09 | 0.55 | 675.12 | 01-JUN-08:61 | 0.57 |
July | 0.447950E+09 | 0.54 | 675.12 | 01-JUL-08:61 | 0.57 |
August | 0.436194E+09 | 0.54 | 675.12 | 01-AUG-08:62 | 0.57 |
September | 0.417399E+09 | 0.54 | 675.12 | 01-SEP-08:62 | 0.57 |
October | 0.389391E+09 | 0.53 | 675.12 | 01-OCT-08:62 | 0.57 |
November | 0.366201E+09 | 0.52 | 675.12 | 01-NOV-08:61 | 0.57 |
December | 0.357500E+09 | 0.49 | 675.12 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.521265E+10 | 0.53 | |||
Minimum of Months | 0.357500E+09 | 0.49 | 675.12 | 0.57 | |
Maximum of Months | 0.534085E+09 | 0.55 | 675.12 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205142E+10 | 0.57 | 1723.84 | 05-JAN-13:40 | 0.57 |
February | 0.183296E+10 | 0.57 | 1145.43 | 04-FEB-14:30 | 0.57 |
March | 0.179484E+10 | 0.57 | 970.71 | 11-MAR-09:00 | 0.57 |
April | 0.160232E+10 | 0.57 | 926.62 | 01-APR-20:20 | 0.57 |
May | 0.164899E+10 | 0.57 | 971.29 | 06-MAY-08:00 | 0.57 |
June | 0.159862E+10 | 0.57 | 932.48 | 13-JUN-20:20 | 0.57 |
July | 0.150980E+10 | 0.57 | 877.90 | 15-JUL-20:10 | 0.57 |
August | 0.147866E+10 | 0.57 | 884.35 | 13-AUG-08:00 | 0.57 |
September | 0.154649E+10 | 0.57 | 904.02 | 27-SEP-20:30 | 0.57 |
October | 0.166710E+10 | 0.57 | 1025.99 | 29-OCT-08:00 | 0.57 |
November | 0.183039E+10 | 0.57 | 1184.36 | 23-NOV-09:00 | 0.57 |
December | 0.201996E+10 | 0.57 | 1734.57 | 07-DEC-13:30 | 0.57 |
Annual Sum or Average | 0.205816E+11 | 0.57 | |||
Minimum of Months | 0.147866E+10 | 0.57 | 877.90 | 0.57 | |
Maximum of Months | 0.205142E+10 | 0.57 | 1734.57 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.276430E+10 | 0.46 | 4534.13 | 01-JAN-09:01 | 0.57 |
February | 0.270154E+10 | 0.48 | 4534.13 | 01-FEB-09:11 | 0.57 |
March | 0.315230E+10 | 0.50 | 4534.13 | 01-MAR-09:01 | 0.57 |
April | 0.331164E+10 | 0.51 | 4534.13 | 01-APR-08:62 | 0.57 |
May | 0.372965E+10 | 0.52 | 4534.13 | 01-MAY-08:62 | 0.57 |
June | 0.399232E+10 | 0.53 | 4534.13 | 01-JUN-08:61 | 0.57 |
July | 0.350350E+10 | 0.51 | 4534.13 | 01-JUL-08:61 | 0.57 |
August | 0.325790E+10 | 0.50 | 4534.13 | 01-AUG-08:62 | 0.57 |
September | 0.302654E+10 | 0.50 | 4534.13 | 01-SEP-08:62 | 0.57 |
October | 0.291633E+10 | 0.49 | 4534.13 | 01-OCT-08:62 | 0.57 |
November | 0.275243E+10 | 0.47 | 4534.13 | 01-NOV-08:61 | 0.57 |
December | 0.267819E+10 | 0.46 | 4534.13 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.377866E+11 | 0.49 | |||
Minimum of Months | 0.267819E+10 | 0.46 | 4534.13 | 0.57 | |
Maximum of Months | 0.399232E+10 | 0.53 | 4534.13 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.471833E+09 | 0.56 | 590.10 | 01-JAN-09:01 | 0.57 |
February | 0.466411E+09 | 0.56 | 590.10 | 01-FEB-09:02 | 0.57 |
March | 0.514353E+09 | 0.56 | 590.10 | 01-MAR-09:01 | 0.57 |
April | 0.506334E+09 | 0.56 | 590.10 | 01-APR-08:62 | 0.57 |
May | 0.504002E+09 | 0.56 | 590.10 | 01-MAY-08:62 | 0.57 |
June | 0.508396E+09 | 0.56 | 590.10 | 01-JUN-08:61 | 0.57 |
July | 0.437991E+09 | 0.55 | 590.10 | 01-JUL-08:61 | 0.57 |
August | 0.438605E+09 | 0.55 | 590.10 | 01-AUG-08:62 | 0.57 |
September | 0.437080E+09 | 0.56 | 590.10 | 01-SEP-08:62 | 0.57 |
October | 0.425638E+09 | 0.55 | 590.10 | 01-OCT-08:62 | 0.57 |
November | 0.433874E+09 | 0.56 | 590.10 | 01-NOV-08:61 | 0.57 |
December | 0.451472E+09 | 0.56 | 590.10 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.559599E+10 | 0.56 | |||
Minimum of Months | 0.425638E+09 | 0.55 | 590.10 | 0.57 | |
Maximum of Months | 0.514353E+09 | 0.56 | 590.10 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.390042E+09 | 0.50 | 595.54 | 01-JAN-09:01 | 0.57 |
February | 0.407498E+09 | 0.52 | 595.54 | 01-FEB-09:11 | 0.57 |
March | 0.488320E+09 | 0.55 | 595.54 | 01-MAR-09:01 | 0.57 |
April | 0.509490E+09 | 0.56 | 595.54 | 01-APR-08:62 | 0.57 |
May | 0.522637E+09 | 0.56 | 595.54 | 01-MAY-08:62 | 0.57 |
June | 0.542718E+09 | 0.55 | 595.54 | 01-JUN-08:61 | 0.57 |
July | 0.456164E+09 | 0.55 | 595.54 | 01-JUL-08:61 | 0.57 |
August | 0.446013E+09 | 0.55 | 595.54 | 01-AUG-08:62 | 0.57 |
September | 0.427666E+09 | 0.55 | 595.54 | 01-SEP-08:62 | 0.57 |
October | 0.395952E+09 | 0.54 | 595.54 | 01-OCT-08:62 | 0.57 |
November | 0.377105E+09 | 0.52 | 595.54 | 01-NOV-08:61 | 0.57 |
December | 0.365570E+09 | 0.50 | 595.54 | 01-DEC-08:42 | 0.57 |
Annual Sum or Average | 0.532918E+10 | 0.54 | |||
Minimum of Months | 0.365570E+09 | 0.50 | 595.54 | 0.57 | |
Maximum of Months | 0.542718E+09 | 0.56 | 595.54 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118353E+09 | 0.55 | 182.39 | 01-JAN-09:01 | 0.57 |
February | 0.115456E+09 | 0.55 | 182.39 | 01-FEB-09:02 | 0.57 |
March | 0.133080E+09 | 0.55 | 182.39 | 01-MAR-09:01 | 0.57 |
April | 0.131661E+09 | 0.55 | 182.39 | 01-APR-08:62 | 0.57 |
May | 0.126715E+09 | 0.55 | 182.39 | 01-MAY-08:62 | 0.57 |
June | 0.127462E+09 | 0.55 | 182.39 | 01-JUN-08:61 | 0.57 |
July | 0.111517E+09 | 0.55 | 182.39 | 01-JUL-08:61 | 0.57 |
August | 0.111866E+09 | 0.55 | 182.39 | 01-AUG-08:62 | 0.57 |
September | 0.111702E+09 | 0.55 | 182.39 | 01-SEP-08:62 | 0.57 |
October | 0.108077E+09 | 0.55 | 182.39 | 01-OCT-08:62 | 0.57 |
November | 0.107581E+09 | 0.55 | 182.39 | 01-NOV-08:61 | 0.57 |
December | 0.112081E+09 | 0.55 | 182.39 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.141555E+10 | 0.55 | |||
Minimum of Months | 0.107581E+09 | 0.55 | 182.39 | 0.57 | |
Maximum of Months | 0.133080E+09 | 0.55 | 182.39 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 98629154.15 | 0.50 | 184.48 | 01-JAN-09:01 | 0.57 |
February | 0.100545E+09 | 0.52 | 184.48 | 01-FEB-09:11 | 0.57 |
March | 0.125785E+09 | 0.55 | 184.48 | 01-MAR-09:01 | 0.57 |
April | 0.132272E+09 | 0.55 | 184.48 | 01-APR-08:62 | 0.57 |
May | 0.131466E+09 | 0.55 | 184.48 | 01-MAY-08:62 | 0.57 |
June | 0.136140E+09 | 0.55 | 184.48 | 01-JUN-08:61 | 0.57 |
July | 0.115981E+09 | 0.54 | 184.48 | 01-JUL-08:61 | 0.57 |
August | 0.113800E+09 | 0.54 | 184.48 | 01-AUG-08:62 | 0.57 |
September | 0.109483E+09 | 0.54 | 184.48 | 01-SEP-08:62 | 0.57 |
October | 0.101369E+09 | 0.54 | 184.48 | 01-OCT-08:62 | 0.57 |
November | 94520291.78 | 0.52 | 184.48 | 01-NOV-08:61 | 0.57 |
December | 92192783.62 | 0.50 | 184.48 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.135218E+10 | 0.53 | |||
Minimum of Months | 92192783.62 | 0.50 | 184.48 | 0.57 | |
Maximum of Months | 0.136140E+09 | 0.55 | 184.48 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.760946E+09 | 0.56 | 740.01 | 01-JAN-09:01 | 0.57 |
February | 0.677920E+09 | 0.56 | 740.01 | 01-FEB-09:02 | 0.57 |
March | 0.668917E+09 | 0.55 | 740.01 | 01-MAR-09:01 | 0.57 |
April | 0.603321E+09 | 0.55 | 740.01 | 01-APR-08:62 | 0.57 |
May | 0.619132E+09 | 0.55 | 740.01 | 01-MAY-08:62 | 0.57 |
June | 0.603862E+09 | 0.55 | 740.01 | 01-JUN-08:61 | 0.57 |
July | 0.553246E+09 | 0.55 | 740.01 | 01-JUL-08:61 | 0.57 |
August | 0.545244E+09 | 0.54 | 740.01 | 01-AUG-08:62 | 0.57 |
September | 0.569342E+09 | 0.55 | 740.01 | 01-SEP-08:62 | 0.57 |
October | 0.605438E+09 | 0.55 | 740.01 | 01-OCT-08:62 | 0.57 |
November | 0.668452E+09 | 0.55 | 740.01 | 01-NOV-08:61 | 0.57 |
December | 0.746546E+09 | 0.56 | 740.01 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.762237E+10 | 0.55 | |||
Minimum of Months | 0.545244E+09 | 0.54 | 740.01 | 0.57 | |
Maximum of Months | 0.760946E+09 | 0.56 | 740.01 | 0.57 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11809624.11 | 10628661.70 | 144.64 | 24-JAN-16:07 | 130.17 | 130.17 | 32.12 | 0.16 |
February | 8861889.94 | 7975700.95 | 143.51 | 25-FEB-19:07 | 129.15 | 129.15 | 32.58 | 0.16 |
March | 9762273.95 | 8786046.56 | 144.25 | 03-MAR-16:07 | 129.83 | 129.83 | 27.48 | 0.16 |
April | 8397684.30 | 7557915.87 | 135.72 | 23-APR-18:07 | 122.15 | 122.15 | 25.69 | 0.15 |
May | 9510079.31 | 8559071.38 | 103.34 | 11-MAY-08:07 | 93.01 | 93.01 | 29.83 | 0.11 |
June | 7873583.33 | 7086224.99 | 123.22 | 30-JUN-18:07 | 110.90 | 110.90 | 28.92 | 0.14 |
July | 9880638.70 | 8892574.83 | 139.06 | 17-JUL-18:07 | 125.16 | 125.16 | 31.11 | 0.16 |
August | 11799855.80 | 10619870.22 | 136.43 | 06-AUG-18:07 | 122.79 | 122.79 | 26.21 | 0.15 |
September | 10089655.20 | 9080689.68 | 144.44 | 03-SEP-18:07 | 129.99 | 129.99 | 31.82 | 0.16 |
October | 12581613.91 | 11323452.52 | 127.86 | 09-OCT-18:07 | 115.08 | 115.08 | 27.83 | 0.14 |
November | 11273307.66 | 10145976.89 | 110.95 | 28-NOV-16:07 | 99.85 | 99.85 | 32.69 | 0.12 |
December | 12331652.99 | 11098487.69 | 145.90 | 28-DEC-16:07 | 131.31 | 131.31 | 31.40 | 0.17 |
Annual Sum or Average | 0.124172E+09 | 0.111755E+09 | ||||||
Minimum of Months | 7873583.33 | 7086224.99 | 103.34 | 93.01 | 93.01 | 25.69 | 0.11 | |
Maximum of Months | 12581613.91 | 11323452.52 | 145.90 | 131.31 | 131.31 | 32.69 | 0.17 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.161190E+10 | 0.145071E+10 | 1266.65 | 10-JAN-19:02 | 1139.99 | 1139.99 | 6.72 | 18.46 |
February | 0.150629E+10 | 0.135566E+10 | 1263.76 | 14-FEB-19:02 | 1137.38 | 1137.38 | 6.72 | 18.44 |
March | 0.179327E+10 | 0.161394E+10 | 1403.74 | 14-MAR-21:30 | 1263.37 | 1263.37 | 6.72 | 19.28 |
April | 0.214938E+10 | 0.193444E+10 | 1821.89 | 10-APR-18:02 | 1639.70 | 1639.70 | 6.72 | 21.49 |
May | 0.263499E+10 | 0.237149E+10 | 1948.17 | 31-MAY-20:20 | 1753.35 | 1753.35 | 6.72 | 22.09 |
June | 0.264261E+10 | 0.237834E+10 | 1966.33 | 13-JUN-18:02 | 1769.70 | 1769.70 | 6.72 | 22.18 |
July | 0.195930E+10 | 0.176337E+10 | 1780.66 | 17-JUL-18:50 | 1602.59 | 1602.59 | 6.72 | 21.29 |
August | 0.234420E+10 | 0.210978E+10 | 1941.83 | 14-AUG-18:02 | 1747.65 | 1747.65 | 6.72 | 22.06 |
September | 0.216746E+10 | 0.195072E+10 | 1754.34 | 08-SEP-18:02 | 1578.91 | 1578.91 | 6.72 | 21.16 |
October | 0.207724E+10 | 0.186951E+10 | 1530.92 | 17-OCT-18:02 | 1377.83 | 1377.83 | 6.72 | 19.99 |
November | 0.187572E+10 | 0.168815E+10 | 1503.17 | 14-NOV-19:02 | 1352.86 | 1352.86 | 6.72 | 19.84 |
December | 0.176994E+10 | 0.159294E+10 | 1366.68 | 10-DEC-19:03 | 1230.01 | 1230.01 | 6.72 | 19.06 |
Annual Sum or Average | 0.245323E+11 | 0.220791E+11 | ||||||
Minimum of Months | 0.150629E+10 | 0.135566E+10 | 1263.76 | 1137.38 | 1137.38 | 6.72 | 18.44 | |
Maximum of Months | 0.264261E+10 | 0.237834E+10 | 1966.33 | 1769.70 | 1769.70 | 6.72 | 22.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-JAN-00:05 | 3414.24 | 3414.24 | 9.77 | 33.56 |
February | 0.917747E+10 | 0.825972E+10 | 3793.60 | 01-FEB-00:03 | 3414.24 | 3414.24 | 9.72 | 33.56 |
March | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-MAR-00:03 | 3414.24 | 3414.24 | 9.79 | 33.56 |
April | 0.983300E+10 | 0.884970E+10 | 3793.60 | 01-APR-00:10 | 3414.24 | 3414.24 | 10.14 | 33.56 |
May | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-MAY-00:10 | 3414.24 | 3414.24 | 10.46 | 33.56 |
June | 0.983300E+10 | 0.884970E+10 | 3793.60 | 01-JUN-00:10 | 3414.24 | 3414.24 | 10.08 | 33.56 |
July | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-JUL-00:10 | 3414.24 | 3414.24 | 9.98 | 33.56 |
August | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-AUG-00:10 | 3414.24 | 3414.24 | 10.13 | 33.56 |
September | 0.983300E+10 | 0.884970E+10 | 3793.60 | 01-SEP-00:10 | 3414.24 | 3414.24 | 10.27 | 33.56 |
October | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-OCT-00:10 | 3414.24 | 3414.24 | 10.21 | 33.56 |
November | 0.983300E+10 | 0.884970E+10 | 3793.60 | 01-NOV-00:10 | 3414.24 | 3414.24 | 10.01 | 33.56 |
December | 0.101608E+11 | 0.914469E+10 | 3793.60 | 01-DEC-00:03 | 3414.24 | 3414.24 | 9.91 | 33.56 |
Annual Sum or Average | 0.119635E+12 | 0.107671E+12 | ||||||
Minimum of Months | 0.917747E+10 | 0.825972E+10 | 3793.60 | 3414.24 | 3414.24 | 9.72 | 33.56 | |
Maximum of Months | 0.101608E+11 | 0.914469E+10 | 3793.60 | 3414.24 | 3414.24 | 10.46 | 33.56 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 52.51 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 52.27 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 52.83 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.27 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 54.79 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.55 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.22 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.19 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.56 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.08 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 52.52 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 52.27 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.22 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26.53 | 26.53 | 560.34 | 20385.22 | 22-JAN-19:07 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 31.07 | 31.07 | 473.00 | 20512.97 | 12-FEB-19:07 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 29.64 | 29.64 | 471.43 | 22186.71 | 03-MAR-16:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30.03 | 30.03 | 421.84 | 21877.62 | 23-APR-18:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29.45 | 60.00 | 460.65 | 14581.43 | 21-MAY-18:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.03 | 60.00 | 407.45 | 17800.45 | 30-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.14 | 60.00 | 477.28 | 20933.44 | 16-JUL-18:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.00 | 60.00 | 556.69 | 21669.50 | 06-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.82 | 60.00 | 498.71 | 19234.88 | 03-SEP-18:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32.03 | 32.03 | 584.95 | 19193.89 | 09-OCT-18:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 33.04 | 60.00 | 549.18 | 14008.85 | 11-NOV-19:07 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30.49 | 30.49 | 573.51 | 19745.24 | 28-DEC-16:07 |
Annual Sum or Average | 0.00 | 503.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.53 | 26.53 | 407.45 | 14008.85 | ||
Maximum of Months | 0.00 | 0.00 | 33.04 | 60.00 | 584.95 | 22186.71 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 446600.48 | 686100.12 | 10-JAN-19:03 | 11.58 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 455376.64 | 673717.73 | 14-FEB-19:03 | 11.49 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 471699.44 | 675763.64 | 28-MAR-18:02 | 11.51 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 528504.85 | 810171.56 | 10-APR-18:03 | 12.46 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 575859.77 | 829656.70 | 22-MAY-18:03 | 12.60 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 585049.63 | 811766.40 | 11-JUN-18:03 | 12.48 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 495219.03 | 746989.10 | 17-JUL-18:50 | 12.01 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 544549.00 | 826817.61 | 08-AUG-18:03 | 12.58 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 533954.01 | 784465.06 | 08-SEP-18:02 | 12.28 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 513136.19 | 746851.73 | 17-OCT-18:03 | 12.01 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 492450.46 | 742183.89 | 14-NOV-19:03 | 11.98 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 469887.60 | 714232.10 | 10-DEC-19:03 | 11.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 509520.03 | 0.00 | ||||||
Minimum of Months | 446600.48 | 673717.73 | 11.49 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 585049.63 | 829656.70 | 12.60 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52.51 | 59.81 | 17552.23 | 35124.88 | 10-JAN-07:36 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 52.27 | 58.26 | 17453.82 | 35000.77 | 06-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.83 | 58.80 | 17216.30 | 34667.59 | 02-MAR-07:45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.27 | 58.49 | 16868.59 | 33804.97 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 54.79 | 59.24 | 16540.03 | 33209.11 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.55 | 58.60 | 16309.38 | 32550.84 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.22 | 59.62 | 16217.41 | 32314.47 | 13-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.19 | 59.55 | 16337.96 | 32642.56 | 29-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.56 | 58.63 | 16586.62 | 33258.23 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.87 | 58.61 | 16918.27 | 33995.77 | 30-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.08 | 58.32 | 17248.69 | 34670.91 | 29-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.52 | 58.83 | 17480.59 | 34951.61 | 28-DEC-07:15 |
Annual Sum or Average | 0.00 | 16891.10 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.27 | 58.26 | 16217.41 | 32314.47 | ||
Maximum of Months | 0.00 | 0.00 | 55.22 | 59.81 | 17552.23 | 35124.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.147778E+10 | 0.00 | 0.927660E+12 | 0.302789E+11 | 0.00 | 0.00 |
February | 0.112947E+10 | 0.00 | 0.850215E+12 | 0.277613E+11 | 0.00 | 0.00 |
March | 0.123607E+10 | 0.00 | 0.984885E+12 | 0.308711E+11 | 0.00 | 0.00 |
April | 0.107436E+10 | 0.00 | 0.108567E+13 | 0.301356E+11 | 0.00 | 0.00 |
May | 0.123631E+10 | 0.00 | 0.123382E+13 | 0.314535E+11 | 0.00 | 0.00 |
June | 0.105464E+10 | 0.00 | 0.120933E+13 | 0.313606E+11 | 0.00 | 0.00 |
July | 0.126030E+10 | 0.00 | 0.105131E+13 | 0.306359E+11 | 0.00 | 0.00 |
August | 0.148085E+10 | 0.00 | 0.117731E+13 | 0.303400E+11 | 0.00 | 0.00 |
September | 0.127891E+10 | 0.00 | 0.111134E+13 | 0.293600E+11 | 0.00 | 0.00 |
October | 0.156494E+10 | 0.00 | 0.110059E+13 | 0.298243E+11 | 0.00 | 0.00 |
November | 0.142101E+10 | 0.00 | 0.100939E+13 | 0.290771E+11 | 0.00 | 0.00 |
December | 0.151431E+10 | 0.00 | 0.989946E+12 | 0.300055E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.157289E+11 | 0.00 | 0.127315E+14 | 0.361104E+12 | 0.00 | 0.00 |
Minimum of Months | 0.105464E+10 | 0.00 | 0.850215E+12 | 0.277613E+11 | 0.00 | 0.00 |
Maximum of Months | 0.156494E+10 | 0.00 | 0.123382E+13 | 0.314535E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 7117.04 | 0.00 | 0.577821E+11 | 0.271000E+10 | 0.00 | 0.00 |
February | 6286.35 | 0.00 | 0.527113E+11 | 0.244774E+10 | 0.00 | 0.00 |
March | 7441.29 | 0.00 | 0.609979E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 9355.43 | 0.00 | 0.677701E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 7714.94 | 0.00 | 0.775428E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 8120.85 | 0.00 | 0.745676E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 10214.23 | 0.00 | 0.654993E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 7118.94 | 0.00 | 0.744237E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 9829.99 | 0.00 | 0.703157E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 10366.95 | 0.00 | 0.705625E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 7968.48 | 0.00 | 0.640725E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 6250.01 | 0.00 | 0.611706E+11 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 97784.51 | 0.00 | 0.797416E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 6250.01 | 0.00 | 0.527113E+11 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 10366.95 | 0.00 | 0.775428E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.302789E+11 | 0.927660E+12 | 0.147778E+10 | 0.00 | 0.321291E+12 | 0.00 | 0.00 | 0.00 |
February | 0.277613E+11 | 0.850215E+12 | 0.112947E+10 | 14998571.86 | 0.345683E+12 | 0.00 | 0.00 | 0.00 |
March | 0.308711E+11 | 0.984885E+12 | 0.123607E+10 | 0.00 | 0.450753E+12 | 0.00 | 0.00 | 0.00 |
April | 0.301356E+11 | 0.108567E+13 | 0.107436E+10 | 0.00 | 0.585973E+12 | 0.00 | 0.00 | 0.00 |
May | 0.314535E+11 | 0.123382E+13 | 0.123631E+10 | 0.00 | 0.705852E+12 | 0.00 | 0.00 | 0.00 |
June | 0.313606E+11 | 0.120933E+13 | 0.105464E+10 | 0.00 | 0.674400E+12 | 0.00 | 0.00 | 0.00 |
July | 0.306359E+11 | 0.105131E+13 | 0.126030E+10 | 0.00 | 0.518394E+12 | 0.00 | 0.00 | 0.00 |
August | 0.303400E+11 | 0.117731E+13 | 0.148085E+10 | 0.00 | 0.651296E+12 | 0.00 | 0.00 | 0.00 |
September | 0.293600E+11 | 0.111134E+13 | 0.127891E+10 | 0.00 | 0.596452E+12 | 0.00 | 0.00 | 0.00 |
October | 0.298243E+11 | 0.110059E+13 | 0.156494E+10 | 0.00 | 0.574546E+12 | 0.00 | 0.00 | 0.00 |
November | 0.290771E+11 | 0.100939E+13 | 0.142101E+10 | 0.00 | 0.458919E+12 | 0.00 | 0.00 | 0.00 |
December | 0.300055E+11 | 0.989946E+12 | 0.151431E+10 | 0.00 | 0.331286E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361104E+12 | 0.127315E+14 | 0.157289E+11 | 14998571.86 | 0.621485E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277613E+11 | 0.850215E+12 | 0.105464E+10 | 0.00 | 0.321291E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314535E+11 | 0.123382E+13 | 0.156494E+10 | 14998571.86 | 0.705852E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.577821E+11 | 7117.04 | 0.00 | 0.383393E+11 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.527113E+11 | 6286.35 | 0.00 | 0.393587E+11 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.609979E+11 | 7441.29 | 0.00 | 0.503486E+11 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.677701E+11 | 9355.43 | 0.00 | 0.610147E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.775428E+11 | 7714.94 | 0.00 | 0.712642E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.745676E+11 | 8120.85 | 0.00 | 0.681326E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.654993E+11 | 10214.23 | 0.00 | 0.536458E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.744237E+11 | 7118.94 | 0.00 | 0.640333E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.703157E+11 | 9829.99 | 0.00 | 0.601422E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.705625E+11 | 10366.95 | 0.00 | 0.579534E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.640725E+11 | 7968.48 | 0.00 | 0.493108E+11 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.611706E+11 | 6250.01 | 240500.16 | 0.401185E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.797416E+12 | 97784.51 | 240500.16 | 0.653662E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.527113E+11 | 6250.01 | 0.00 | 0.383393E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.775428E+11 | 10366.95 | 240500.16 | 0.712642E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.302789E+11 | 0.147778E+10 | 0.927660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277613E+11 | 0.112947E+10 | 0.850215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308711E+11 | 0.123607E+10 | 0.984885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301356E+11 | 0.107436E+10 | 0.108567E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314535E+11 | 0.123631E+10 | 0.123382E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313606E+11 | 0.105464E+10 | 0.120933E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.306359E+11 | 0.126030E+10 | 0.105131E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303400E+11 | 0.148085E+10 | 0.117731E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293600E+11 | 0.127891E+10 | 0.111134E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298243E+11 | 0.156494E+10 | 0.110059E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290771E+11 | 0.142101E+10 | 0.100939E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300055E+11 | 0.151431E+10 | 0.989946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361104E+12 | 0.157289E+11 | 0.127315E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277613E+11 | 0.105464E+10 | 0.850215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314535E+11 | 0.156494E+10 | 0.123382E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 7117.04 | 0.577821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 6286.35 | 0.527113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 7441.29 | 0.609979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 9355.43 | 0.677701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 7714.94 | 0.775428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 8120.85 | 0.745676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 10214.23 | 0.654993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 7118.94 | 0.744237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 9829.99 | 0.703157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 10366.95 | 0.705625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 7968.48 | 0.640725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 6250.01 | 0.611706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 97784.51 | 0.797416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 6250.01 | 0.527113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 10366.95 | 0.775428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49882324.12 | 0.769793E+10 | 0.00 | 0.00 | 0.351481E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
February | 0.00 | 0.921850E+10 | 0.00 | 5547.46 | 0.296713E+11 | 0.00 | 2189754.52 | 0.00 | 1.11 |
March | 0.00 | 0.836184E+10 | 0.00 | 0.00 | 0.398433E+11 | 0.00 | 0.00 | 0.00 | 1.11 |
April | 0.00 | 0.134874E+11 | 0.00 | 0.00 | 0.483933E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
May | 0.00 | 0.253292E+11 | 0.00 | 0.00 | 0.512199E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
June | 0.00 | 0.371865E+11 | 0.00 | 0.00 | 0.367106E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
July | 0.00 | 0.228542E+11 | 0.00 | 0.00 | 0.337213E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
August | 0.00 | 0.221624E+11 | 0.00 | 0.00 | 0.504649E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
September | 0.00 | 0.205344E+11 | 0.00 | 0.00 | 0.462449E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 0.00 | 0.101314E+11 | 0.00 | 0.00 | 0.544981E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.00 | 0.120924E+11 | 0.00 | 0.00 | 0.429336E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
December | 9506515.59 | 0.116110E+11 | 0.00 | 0.00 | 0.393243E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 59388839.71 | 0.200667E+12 | 0.00 | 5547.46 | 0.508174E+12 | 0.00 | 2189754.52 | 0.00 | 1.13 |
Minimum of Months | 0.00 | 0.769793E+10 | 0.00 | 0.00 | 0.296713E+11 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 49882324.12 | 0.371865E+11 | 0.00 | 5547.46 | 0.544981E+11 | 0.00 | 2189754.52 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5193344.99 | 0.409859E+10 | 0.00 | 0.00 | 0.951046E+09 | 0.00 | 0.00 | 0.00 | 2.39 |
February | 0.00 | 0.422599E+10 | 0.00 | 4351.99 | 0.451033E+09 | 0.00 | 224205.13 | 0.00 | 2.38 |
March | 0.00 | 0.486684E+10 | 0.00 | 0.00 | 0.644129E+09 | 0.00 | 0.00 | 0.00 | 2.29 |
April | 0.00 | 0.587940E+10 | 0.00 | 0.00 | 0.958633E+09 | 0.00 | 0.00 | 0.00 | 2.25 |
May | 0.00 | 0.671360E+10 | 0.00 | 0.00 | 0.165730E+10 | 0.00 | 0.00 | 0.00 | 2.24 |
June | 0.00 | 0.697350E+10 | 0.00 | 0.00 | 0.120349E+10 | 0.00 | 0.00 | 0.00 | 2.24 |
July | 0.00 | 0.437252E+10 | 0.00 | 0.00 | 0.160730E+10 | 0.00 | 0.00 | 0.00 | 2.22 |
August | 0.00 | 0.505042E+10 | 0.00 | 0.00 | 0.268174E+10 | 0.00 | 0.00 | 0.00 | 2.23 |
September | 0.00 | 0.531841E+10 | 0.00 | 0.00 | 0.187604E+10 | 0.00 | 0.00 | 0.00 | 2.23 |
October | 0.00 | 0.489259E+10 | 0.00 | 0.00 | 0.206310E+10 | 0.00 | 0.00 | 0.00 | 2.24 |
November | 0.00 | 0.498324E+10 | 0.00 | 0.00 | 0.123261E+10 | 0.00 | 0.00 | 0.00 | 2.31 |
December | 989741.68 | 0.459152E+10 | 0.00 | 0.00 | 0.128677E+10 | 0.00 | 0.00 | 0.00 | 2.38 |
Annual Sum or Average | 6183086.67 | 0.619666E+11 | 0.00 | 4351.99 | 0.166132E+11 | 0.00 | 224205.13 | 0.00 | 2.28 |
Minimum of Months | 0.00 | 0.409859E+10 | 0.00 | 0.00 | 0.451033E+09 | 0.00 | 0.00 | 0.00 | 2.22 |
Maximum of Months | 5193344.99 | 0.697350E+10 | 0.00 | 4351.99 | 0.268174E+10 | 0.00 | 224205.13 | 0.00 | 2.39 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4522108.16 | 0.158554E+10 | 0.00 | 203.58 | 0.242901E+10 | 0.00 | 141897.33 | 0.00 | 1.65 |
February | 0.00 | 0.184986E+10 | 0.00 | 3205.44 | 0.181054E+10 | 0.00 | 202064.62 | 0.00 | 1.64 |
March | 0.00 | 0.252536E+10 | 0.00 | 0.00 | 0.203792E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
April | 0.00 | 0.336582E+10 | 0.00 | 0.00 | 0.251331E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
May | 0.00 | 0.396421E+10 | 0.00 | 0.00 | 0.327441E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
June | 0.00 | 0.459591E+10 | 0.00 | 0.00 | 0.246293E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
July | 0.00 | 0.229190E+10 | 0.00 | 0.00 | 0.301813E+10 | 0.00 | 0.00 | 0.00 | 1.70 |
August | 0.00 | 0.272765E+10 | 0.00 | 0.00 | 0.410653E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
September | 0.00 | 0.258430E+10 | 0.00 | 0.00 | 0.369623E+10 | 0.00 | 0.00 | 0.00 | 1.69 |
October | 0.00 | 0.197966E+10 | 0.00 | 0.00 | 0.407139E+10 | 0.00 | 0.00 | 0.00 | 1.69 |
November | 0.00 | 0.188584E+10 | 0.00 | 0.00 | 0.326860E+10 | 0.00 | 0.00 | 0.00 | 1.67 |
December | 888899.56 | 0.179558E+10 | 0.00 | 0.00 | 0.297203E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
Annual Sum or Average | 5411007.72 | 0.311516E+11 | 0.00 | 3409.02 | 0.356610E+11 | 0.00 | 343961.95 | 0.00 | 1.67 |
Minimum of Months | 0.00 | 0.158554E+10 | 0.00 | 0.00 | 0.181054E+10 | 0.00 | 0.00 | 0.00 | 1.64 |
Maximum of Months | 4522108.16 | 0.459591E+10 | 0.00 | 3205.44 | 0.410653E+10 | 0.00 | 202064.62 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4804965.49 | 0.235218E+09 | 0.00 | 0.00 | 0.389197E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
February | 211464.69 | 0.571181E+09 | 0.00 | 0.00 | 0.317492E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
March | 0.00 | 0.107237E+10 | 0.00 | 0.00 | 0.357462E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
April | 0.00 | 0.289437E+10 | 0.00 | 0.00 | 0.314476E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
May | 0.00 | 0.535088E+10 | 0.00 | 0.00 | 0.242221E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 0.00 | 0.693869E+10 | 0.00 | 0.00 | 0.112380E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.344886E+10 | 0.00 | 0.00 | 0.215429E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.275264E+10 | 0.00 | 0.00 | 0.433924E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 0.00 | 0.161835E+10 | 0.00 | 0.00 | 0.482705E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
October | 0.00 | 0.468271E+09 | 0.00 | 0.00 | 0.575723E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
November | 0.00 | 0.440010E+09 | 0.00 | 0.00 | 0.486042E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
December | 915724.76 | 0.251425E+09 | 0.00 | 0.00 | 0.465497E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
Annual Sum or Average | 5932154.95 | 0.260423E+11 | 0.00 | 0.00 | 0.439255E+11 | 0.00 | 0.00 | 0.00 | 0.83 |
Minimum of Months | 0.00 | 0.235218E+09 | 0.00 | 0.00 | 0.112380E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 4804965.49 | 0.693869E+10 | 0.00 | 0.00 | 0.575723E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2628610.80 | 6249735.40 | 0.00 | 0.00 | 0.225158E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
February | 115684.15 | 0.100889E+09 | 0.00 | 0.00 | 0.194846E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
March | 0.00 | 0.330717E+09 | 0.00 | 0.00 | 0.220951E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
April | 0.00 | 0.109831E+10 | 0.00 | 0.00 | 0.217053E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
May | 0.00 | 0.252599E+10 | 0.00 | 0.00 | 0.161186E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 0.00 | 0.344794E+10 | 0.00 | 0.00 | 0.803355E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.146080E+10 | 0.00 | 0.00 | 0.153974E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.111189E+10 | 0.00 | 0.00 | 0.272609E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.511953E+09 | 0.00 | 0.00 | 0.300706E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
October | 0.00 | 89277677.58 | 0.00 | 0.00 | 0.331645E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
November | 0.00 | 32187036.38 | 0.00 | 0.00 | 0.286747E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
December | 500957.60 | 6145607.44 | 0.00 | 0.00 | 0.267795E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
Annual Sum or Average | 3245252.56 | 0.107223E+11 | 0.00 | 0.00 | 0.271301E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 6145607.44 | 0.00 | 0.00 | 0.803355E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 2628610.80 | 0.344794E+10 | 0.00 | 0.00 | 0.331645E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 448384.30 | 0.478819E+11 | 0.00 | 500872.00 | 0.872128E+09 | 0.00 | 52985556.96 | 0.00 | 19.82 |
February | 0.00 | 0.436260E+11 | 0.00 | 31933.92 | 0.757347E+09 | 0.00 | 2341716.55 | 0.00 | 19.64 |
March | 0.00 | 0.543120E+11 | 0.00 | 0.00 | 0.925242E+09 | 0.00 | 0.00 | 0.00 | 19.83 |
April | 0.00 | 0.701587E+11 | 0.00 | 0.00 | 0.102620E+10 | 0.00 | 0.00 | 0.00 | 20.06 |
May | 0.00 | 0.866342E+11 | 0.00 | 0.00 | 0.130422E+10 | 0.00 | 0.00 | 0.00 | 20.14 |
June | 0.00 | 0.837246E+11 | 0.00 | 0.00 | 0.118999E+10 | 0.00 | 0.00 | 0.00 | 19.99 |
July | 0.00 | 0.638707E+11 | 0.00 | 0.00 | 0.106808E+10 | 0.00 | 0.00 | 0.00 | 20.62 |
August | 0.00 | 0.817455E+11 | 0.00 | 0.00 | 0.145134E+10 | 0.00 | 0.00 | 0.00 | 20.60 |
September | 0.00 | 0.751740E+11 | 0.00 | 0.00 | 0.131327E+10 | 0.00 | 0.00 | 0.00 | 20.33 |
October | 0.00 | 0.723894E+11 | 0.00 | 0.00 | 0.130000E+10 | 0.00 | 0.00 | 0.00 | 20.41 |
November | 0.00 | 0.619168E+11 | 0.00 | 0.00 | 0.104850E+10 | 0.00 | 0.00 | 0.00 | 20.09 |
December | 0.00 | 0.568315E+11 | 0.00 | 191891.95 | 0.944313E+09 | 0.00 | 10086942.33 | 0.00 | 20.03 |
Annual Sum or Average | 448384.30 | 0.798265E+12 | 0.00 | 724697.86 | 0.132006E+11 | 0.00 | 65414215.84 | 0.00 | 20.13 |
Minimum of Months | 0.00 | 0.436260E+11 | 0.00 | 0.00 | 0.757347E+09 | 0.00 | 0.00 | 0.00 | 19.64 |
Maximum of Months | 448384.30 | 0.866342E+11 | 0.00 | 500872.00 | 0.145134E+10 | 0.00 | 52985556.96 | 0.00 | 20.62 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 929557.97 | 0.187870E+11 | 0.00 | 331408.47 | 0.105546E+10 | 0.00 | 20429218.30 | 0.00 | 3.37 |
February | 0.00 | 0.174240E+11 | 0.00 | 31166.53 | 0.569564E+09 | 0.00 | 1034917.20 | 0.00 | 3.32 |
March | 0.00 | 0.202555E+11 | 0.00 | 0.00 | 0.164562E+10 | 0.00 | 0.00 | 0.00 | 3.28 |
April | 0.00 | 0.252481E+11 | 0.00 | 0.00 | 0.262244E+10 | 0.00 | 0.00 | 0.00 | 3.29 |
May | 0.00 | 0.302050E+11 | 0.00 | 0.00 | 0.421954E+10 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 0.00 | 0.299723E+11 | 0.00 | 0.00 | 0.339831E+10 | 0.00 | 0.00 | 0.00 | 3.28 |
July | 0.00 | 0.210293E+11 | 0.00 | 0.00 | 0.400851E+10 | 0.00 | 0.00 | 0.00 | 3.32 |
August | 0.00 | 0.255805E+11 | 0.00 | 0.00 | 0.658948E+10 | 0.00 | 0.00 | 0.00 | 3.32 |
September | 0.00 | 0.255200E+11 | 0.00 | 0.00 | 0.425046E+10 | 0.00 | 0.00 | 0.00 | 3.30 |
October | 0.00 | 0.245976E+11 | 0.00 | 0.00 | 0.413234E+10 | 0.00 | 0.00 | 0.00 | 3.31 |
November | 0.00 | 0.231937E+11 | 0.00 | 0.00 | 0.171411E+10 | 0.00 | 0.00 | 0.00 | 3.32 |
December | 448096.08 | 0.223633E+11 | 0.00 | 81056.89 | 0.101731E+10 | 0.00 | 3604537.33 | 0.00 | 3.37 |
Annual Sum or Average | 1377654.05 | 0.284176E+12 | 0.00 | 443631.88 | 0.352231E+11 | 0.00 | 25068672.83 | 0.00 | 3.31 |
Minimum of Months | 0.00 | 0.174240E+11 | 0.00 | 0.00 | 0.569564E+09 | 0.00 | 0.00 | 0.00 | 3.28 |
Maximum of Months | 929557.97 | 0.302050E+11 | 0.00 | 331408.47 | 0.658948E+10 | 0.00 | 20429218.30 | 0.00 | 3.37 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16868554.52 | 0.459837E+11 | 0.00 | 586883.12 | 0.234471E+11 | 0.00 | 62699735.53 | 0.00 | 1.70 |
February | 0.00 | 0.459416E+11 | 0.00 | 98622.57 | 0.173910E+11 | 0.00 | 3428975.90 | 0.00 | 1.69 |
March | 0.00 | 0.503142E+11 | 0.00 | 0.00 | 0.282325E+11 | 0.00 | 0.00 | 0.00 | 1.69 |
April | 0.00 | 0.658148E+11 | 0.00 | 0.00 | 0.352793E+11 | 0.00 | 0.00 | 0.00 | 1.72 |
May | 0.00 | 0.926925E+11 | 0.00 | 0.00 | 0.333245E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
June | 0.00 | 0.983461E+11 | 0.00 | 0.00 | 0.251583E+11 | 0.00 | 0.00 | 0.00 | 1.75 |
July | 0.00 | 0.580640E+11 | 0.00 | 0.00 | 0.341880E+11 | 0.00 | 0.00 | 0.00 | 1.76 |
August | 0.00 | 0.664204E+11 | 0.00 | 0.00 | 0.515661E+11 | 0.00 | 0.00 | 0.00 | 1.75 |
September | 0.00 | 0.622393E+11 | 0.00 | 0.00 | 0.460762E+11 | 0.00 | 0.00 | 0.00 | 1.73 |
October | 0.00 | 0.557252E+11 | 0.00 | 0.00 | 0.485740E+11 | 0.00 | 0.00 | 0.00 | 1.73 |
November | 0.00 | 0.561409E+11 | 0.00 | 0.00 | 0.329116E+11 | 0.00 | 0.00 | 0.00 | 1.71 |
December | 3515865.35 | 0.561447E+11 | 0.00 | 135969.17 | 0.262215E+11 | 0.00 | 11624045.59 | 0.00 | 1.71 |
Annual Sum or Average | 20384419.86 | 0.753827E+12 | 0.00 | 821474.86 | 0.402370E+12 | 0.00 | 77752757.02 | 0.00 | 1.72 |
Minimum of Months | 0.00 | 0.459416E+11 | 0.00 | 0.00 | 0.173910E+11 | 0.00 | 0.00 | 0.00 | 1.69 |
Maximum of Months | 16868554.52 | 0.983461E+11 | 0.00 | 586883.12 | 0.515661E+11 | 0.00 | 62699735.53 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.122408E+10 | 364620.08 | 66871.95 | 0.00 | 19027.52 | 366897.59 | 4462.96 | 0.36 |
February | 0.00 | 0.115513E+10 | 502394.36 | 0.00 | 0.00 | 0.00 | 0.00 | 7779.37 | 0.36 |
March | 0.00 | 0.146280E+10 | 352299.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6314.64 | 0.36 |
April | 0.00 | 0.181881E+10 | 419616.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1815.55 | 0.36 |
May | 0.00 | 0.219729E+10 | 458339.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3849.79 | 0.36 |
June | 0.00 | 0.209985E+10 | 989572.13 | 0.00 | 0.00 | 0.00 | 0.00 | 6970.91 | 0.36 |
July | 0.00 | 0.163038E+10 | 1850329.62 | 0.00 | 0.00 | 0.00 | 0.00 | 30098.32 | 0.36 |
August | 0.00 | 0.198880E+10 | 911640.64 | 0.00 | 160337.83 | 0.00 | 0.00 | 6553.92 | 0.36 |
September | 0.00 | 0.185294E+10 | 1112766.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6376.43 | 0.36 |
October | 0.00 | 0.179327E+10 | 658053.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9026.89 | 0.36 |
November | 0.00 | 0.153844E+10 | 629045.52 | 0.00 | 0.00 | 0.00 | 0.00 | 7340.91 | 0.36 |
December | 0.00 | 0.134254E+10 | 674173.65 | 13251.26 | 0.00 | 2085.53 | 0.00 | 9517.81 | 0.36 |
Annual Sum or Average | 0.00 | 0.201043E+11 | 8922851.68 | 80123.22 | 160337.83 | 21113.06 | 366897.59 | 100107.51 | 0.36 |
Minimum of Months | 0.00 | 0.115513E+10 | 352299.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1815.55 | 0.36 |
Maximum of Months | 0.00 | 0.219729E+10 | 1850329.62 | 66871.95 | 160337.83 | 19027.52 | 366897.59 | 30098.32 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 448522.17 | 0.113321E+10 | 753568.80 | 4221.85 | 90328574.34 | 0.00 | 0.00 | 14351.12 | 0.36 |
February | 0.00 | 0.108532E+10 | 368804.83 | 0.00 | 69803878.11 | 0.00 | 0.00 | 9528.92 | 0.36 |
March | 0.00 | 0.145121E+10 | 795235.03 | 0.00 | 10969040.02 | 0.00 | 0.00 | 12462.91 | 0.36 |
April | 0.00 | 0.181522E+10 | 492460.88 | 0.00 | 3311858.13 | 0.00 | 0.00 | 2793.17 | 0.36 |
May | 0.00 | 0.218682E+10 | 458350.74 | 0.00 | 10215664.97 | 0.00 | 0.00 | 3784.61 | 0.36 |
June | 0.00 | 0.207942E+10 | 414726.67 | 0.00 | 20769197.02 | 0.00 | 0.00 | 1495.51 | 0.36 |
July | 0.00 | 0.160789E+10 | 1698055.43 | 0.00 | 22452007.12 | 0.00 | 0.00 | 23028.68 | 0.36 |
August | 0.00 | 0.197696E+10 | 1152221.19 | 0.00 | 11525555.48 | 0.00 | 0.00 | 7605.40 | 0.36 |
September | 0.00 | 0.183457E+10 | 1664211.45 | 0.00 | 17586560.61 | 0.00 | 0.00 | 12802.91 | 0.36 |
October | 0.00 | 0.176668E+10 | 1502539.61 | 0.00 | 25537987.82 | 0.00 | 0.00 | 12710.07 | 0.36 |
November | 0.00 | 0.146873E+10 | 1176662.23 | 0.00 | 68967303.47 | 0.00 | 0.00 | 17873.41 | 0.36 |
December | 0.00 | 0.123597E+10 | 738338.81 | 14360.31 | 0.106351E+09 | 0.00 | 974.69 | 12024.01 | 0.36 |
Annual Sum or Average | 448522.17 | 0.196420E+11 | 11215175.67 | 18582.16 | 0.457818E+09 | 0.00 | 974.69 | 130460.72 | 0.36 |
Minimum of Months | 0.00 | 0.108532E+10 | 368804.83 | 0.00 | 3311858.13 | 0.00 | 0.00 | 1495.51 | 0.36 |
Maximum of Months | 448522.17 | 0.218682E+10 | 1698055.43 | 14360.31 | 0.106351E+09 | 0.00 | 974.69 | 23028.68 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.888216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.948166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.106985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.123682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.154216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.148594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.124574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.165075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.146368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.149037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.129201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.101402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.153277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.888216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.165075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6083934.10 | 0.148382E+11 | 12258020.00 | 57266.86 | 0.175642E+10 | 0.00 | 0.00 | 96314.05 | 0.41 |
February | 0.00 | 0.145314E+11 | 9984758.44 | 0.00 | 0.113226E+10 | 0.00 | 0.00 | 57096.30 | 0.41 |
March | 0.00 | 0.192938E+11 | 18382484.82 | 0.00 | 0.532282E+09 | 0.00 | 0.00 | 99574.24 | 0.41 |
April | 0.00 | 0.244079E+11 | 23292035.14 | 0.00 | 0.242735E+09 | 0.00 | 0.00 | 58926.52 | 0.41 |
May | 0.00 | 0.295422E+11 | 4474556.38 | 0.00 | 0.261032E+09 | 0.00 | 0.00 | 3014.40 | 0.41 |
June | 0.00 | 0.281828E+11 | 5634108.06 | 0.00 | 0.305010E+09 | 0.00 | 0.00 | 9344.45 | 0.41 |
July | 0.00 | 0.217402E+11 | 13878986.37 | 0.00 | 0.383886E+09 | 0.00 | 0.00 | 37702.47 | 0.41 |
August | 0.00 | 0.263458E+11 | 15545593.98 | 0.00 | 0.626985E+09 | 0.00 | 0.00 | 31039.50 | 0.41 |
September | 0.00 | 0.242450E+11 | 20080226.57 | 0.00 | 0.881071E+09 | 0.00 | 0.00 | 38564.81 | 0.41 |
October | 0.00 | 0.230791E+11 | 933421.68 | 0.00 | 0.125082E+10 | 0.00 | 0.00 | 5920.84 | 0.41 |
November | 0.00 | 0.191791E+11 | 3340616.55 | 0.00 | 0.169179E+10 | 0.00 | 0.00 | 3787.78 | 0.41 |
December | 0.00 | 0.161583E+11 | 14206907.98 | 208010.06 | 0.204539E+10 | 0.00 | 0.00 | 82865.26 | 0.41 |
Annual Sum or Average | 6083934.10 | 0.261544E+12 | 0.142012E+09 | 265276.92 | 0.111097E+11 | 0.00 | 0.00 | 524150.62 | 0.41 |
Minimum of Months | 0.00 | 0.145314E+11 | 933421.68 | 0.00 | 0.242735E+09 | 0.00 | 0.00 | 3014.40 | 0.41 |
Maximum of Months | 6083934.10 | 0.295422E+11 | 23292035.14 | 208010.06 | 0.204539E+10 | 0.00 | 0.00 | 99574.24 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.122445E+10 | 0.00 | 94262.27 | 0.00 | 0.00 | 358534.80 | 0.00 | 0.36 |
February | 0.00 | 0.115564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.146316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
April | 0.00 | 0.181924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.219775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.210085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.163226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.198966E+10 | 57692.75 | 0.00 | 160337.83 | 0.00 | 0.00 | 173.65 | 0.36 |
September | 0.00 | 0.185401E+10 | 42867.97 | 0.00 | 0.00 | 0.00 | 0.00 | 566.44 | 0.36 |
October | 0.00 | 0.179390E+10 | 43119.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1743.43 | 0.36 |
November | 0.00 | 0.153903E+10 | 48581.99 | 0.00 | 0.00 | 0.00 | 0.00 | 440.20 | 0.36 |
December | 0.00 | 0.134323E+10 | 0.00 | 15336.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.201132E+11 | 192262.58 | 109599.06 | 160337.83 | 0.00 | 358534.80 | 2923.72 | 0.36 |
Minimum of Months | 0.00 | 0.115564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.00 | 0.219775E+10 | 57692.75 | 94262.27 | 160337.83 | 0.00 | 358534.80 | 1743.43 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 448522.17 | 0.113371E+10 | 259834.92 | 4221.85 | 90328574.34 | 0.00 | 0.00 | 2037.02 | 0.36 |
February | 0.00 | 0.108571E+10 | 0.00 | 0.00 | 69790662.51 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.145202E+10 | 0.00 | 0.00 | 10969040.02 | 0.00 | 0.00 | 0.00 | 0.36 |
April | 0.00 | 0.181571E+10 | 0.00 | 0.00 | 3311858.13 | 0.00 | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.218728E+10 | 0.00 | 0.00 | 10215664.97 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.207983E+10 | 0.00 | 0.00 | 20769197.02 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.160955E+10 | 63105.18 | 0.00 | 22452007.12 | 0.00 | 0.00 | 939.93 | 0.36 |
August | 0.00 | 0.197806E+10 | 57269.01 | 0.00 | 11525555.48 | 0.00 | 0.00 | 590.60 | 0.36 |
September | 0.00 | 0.183620E+10 | 51482.01 | 0.00 | 17586560.61 | 0.00 | 0.00 | 1054.10 | 0.36 |
October | 0.00 | 0.176814E+10 | 50015.95 | 0.00 | 25537987.82 | 0.00 | 0.00 | 1189.90 | 0.36 |
November | 0.00 | 0.146989E+10 | 34323.01 | 0.00 | 68967303.47 | 0.00 | 0.00 | 247.06 | 0.36 |
December | 0.00 | 0.123652E+10 | 201437.80 | 15335.00 | 0.106351E+09 | 0.00 | 0.00 | 1881.55 | 0.36 |
Annual Sum or Average | 448522.17 | 0.196526E+11 | 717467.88 | 19556.85 | 0.457805E+09 | 0.00 | 0.00 | 7940.16 | 0.36 |
Minimum of Months | 0.00 | 0.108571E+10 | 0.00 | 0.00 | 3311858.13 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 448522.17 | 0.218728E+10 | 259834.92 | 15335.00 | 0.106351E+09 | 0.00 | 0.00 | 2037.02 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25972530.05 | 0.00 | 0.00 | 0.00 | 0.223089E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 1143041.10 | 0.384279E+09 | 0.00 | 0.00 | 0.198647E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
March | 0.00 | 67785340.48 | 0.00 | 0.00 | 0.250315E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.112697E+09 | 0.00 | 0.00 | 0.321071E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.434913E+10 | 0.00 | 0.00 | 0.355081E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.130847E+11 | 0.00 | 0.00 | 0.254844E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.294575E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.378153E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.347704E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.336510E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.00 | 17696038.35 | 0.00 | 0.00 | 0.286330E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 4949814.71 | 0.160926E+09 | 0.00 | 0.00 | 0.263599E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 32065385.86 | 0.181772E+11 | 0.00 | 0.00 | 0.350992E+12 | 0.00 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.198647E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 25972530.05 | 0.130847E+11 | 0.00 | 0.00 | 0.378153E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.305893E+09 | 214807.82 | 16312.04 | 0.00 | 4756.88 | 92130.34 | 4020.07 | 0.36 |
February | 0.00 | 0.288742E+09 | 163634.37 | 0.00 | 0.00 | 0.00 | 0.00 | 4036.29 | 0.36 |
March | 0.00 | 0.365601E+09 | 185176.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3296.32 | 0.36 |
April | 0.00 | 0.454534E+09 | 272898.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2343.23 | 0.36 |
May | 0.00 | 0.549100E+09 | 334467.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3208.71 | 0.36 |
June | 0.00 | 0.524897E+09 | 311222.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4514.19 | 0.36 |
July | 0.00 | 0.407470E+09 | 581852.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12025.11 | 0.36 |
August | 0.00 | 0.496937E+09 | 528257.35 | 0.00 | 0.00 | 0.00 | 0.00 | 4838.75 | 0.36 |
September | 0.00 | 0.463045E+09 | 465075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3556.70 | 0.36 |
October | 0.00 | 0.448092E+09 | 388535.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4258.20 | 0.36 |
November | 0.00 | 0.384560E+09 | 205901.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3219.43 | 0.36 |
December | 0.00 | 0.335610E+09 | 193355.93 | 3312.82 | 0.00 | 521.38 | 0.00 | 3612.43 | 0.36 |
Annual Sum or Average | 0.00 | 0.502448E+10 | 3845185.16 | 19624.86 | 0.00 | 5278.26 | 92130.34 | 52929.43 | 0.36 |
Minimum of Months | 0.00 | 0.288742E+09 | 163634.37 | 0.00 | 0.00 | 0.00 | 0.00 | 2343.23 | 0.36 |
Maximum of Months | 0.00 | 0.549100E+09 | 581852.39 | 16312.04 | 0.00 | 4756.88 | 92130.34 | 12025.11 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 112130.54 | 0.283285E+09 | 204215.94 | 1055.46 | 22582143.59 | 0.00 | 0.00 | 5097.72 | 0.36 |
February | 0.00 | 0.271293E+09 | 129056.69 | 0.00 | 17450969.53 | 0.00 | 0.00 | 3045.23 | 0.36 |
March | 0.00 | 0.362714E+09 | 285902.65 | 0.00 | 2742260.00 | 0.00 | 0.00 | 5052.79 | 0.36 |
April | 0.00 | 0.453651E+09 | 274654.31 | 0.00 | 827964.53 | 0.00 | 0.00 | 2323.57 | 0.36 |
May | 0.00 | 0.546523E+09 | 293399.51 | 0.00 | 2553916.24 | 0.00 | 0.00 | 3001.89 | 0.36 |
June | 0.00 | 0.519774E+09 | 183586.32 | 0.00 | 5192299.26 | 0.00 | 0.00 | 1590.99 | 0.36 |
July | 0.00 | 0.401884E+09 | 509575.68 | 0.00 | 5613001.78 | 0.00 | 0.00 | 9394.21 | 0.36 |
August | 0.00 | 0.493990E+09 | 535768.80 | 0.00 | 2881388.87 | 0.00 | 0.00 | 4687.48 | 0.36 |
September | 0.00 | 0.458495E+09 | 562292.55 | 0.00 | 4396640.15 | 0.00 | 0.00 | 5494.16 | 0.36 |
October | 0.00 | 0.441536E+09 | 505401.37 | 0.00 | 6384496.96 | 0.00 | 0.00 | 6962.59 | 0.36 |
November | 0.00 | 0.367062E+09 | 412743.38 | 0.00 | 17241825.87 | 0.00 | 0.00 | 7118.18 | 0.36 |
December | 0.00 | 0.308866E+09 | 310099.00 | 3655.52 | 26587664.05 | 0.00 | 178.23 | 4288.17 | 0.36 |
Annual Sum or Average | 112130.54 | 0.490907E+10 | 4206696.19 | 4710.98 | 0.114455E+09 | 0.00 | 178.23 | 58056.98 | 0.36 |
Minimum of Months | 0.00 | 0.271293E+09 | 129056.69 | 0.00 | 827964.53 | 0.00 | 0.00 | 1590.99 | 0.36 |
Maximum of Months | 112130.54 | 0.546523E+09 | 562292.55 | 3655.52 | 26587664.05 | 0.00 | 178.23 | 9394.21 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.196646E+10 | 150320.50 | 125364.86 | 0.00 | 27966.18 | 573916.44 | 1725.96 | 0.41 |
February | 0.00 | 0.185610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.234870E+10 | 1305915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3113.36 | 0.41 |
April | 0.00 | 0.292044E+10 | 1470747.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3653.49 | 0.41 |
May | 0.00 | 0.352872E+10 | 1135093.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3117.22 | 0.41 |
June | 0.00 | 0.337382E+10 | 397093.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.50 | 0.41 |
July | 0.00 | 0.262044E+10 | 1161167.37 | 0.00 | 0.00 | 0.00 | 0.00 | 2298.26 | 0.41 |
August | 0.00 | 0.319344E+10 | 2290324.69 | 0.00 | 257522.17 | 0.00 | 0.00 | 7505.85 | 0.41 |
September | 0.00 | 0.297571E+10 | 2123544.40 | 0.00 | 0.00 | 0.00 | 0.00 | 5918.42 | 0.41 |
October | 0.00 | 0.287928E+10 | 1996200.11 | 0.00 | 0.00 | 0.00 | 0.00 | 7381.26 | 0.41 |
November | 0.00 | 0.247166E+10 | 279089.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1550.80 | 0.41 |
December | 0.00 | 0.215721E+10 | 179056.54 | 24632.77 | 0.00 | 0.00 | 0.00 | 3168.76 | 0.41 |
Annual Sum or Average | 0.00 | 0.322920E+11 | 12488553.38 | 149997.63 | 257522.17 | 27966.18 | 573916.44 | 40879.88 | 0.41 |
Minimum of Months | 0.00 | 0.185610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.00 | 0.352872E+10 | 2290324.69 | 125364.86 | 257522.17 | 27966.18 | 573916.44 | 7505.85 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.336549E+11 | 0.00 | 1020179.59 | 0.696433E+09 | 0.00 | 37151120.62 | 0.00 | 4.32 |
February | 0.00 | 0.309744E+11 | 0.00 | 55652.25 | 0.488666E+09 | 0.00 | 1848993.67 | 0.00 | 4.33 |
March | 0.00 | 0.389641E+11 | 0.00 | 0.00 | 0.680842E+09 | 0.00 | 0.00 | 0.00 | 4.41 |
April | 0.00 | 0.511444E+11 | 0.00 | 0.00 | 0.486871E+09 | 0.00 | 0.00 | 0.00 | 4.52 |
May | 0.00 | 0.638151E+11 | 0.00 | 0.00 | 0.708706E+09 | 0.00 | 0.00 | 0.00 | 4.59 |
June | 0.00 | 0.628426E+11 | 0.00 | 0.00 | 0.289315E+09 | 0.00 | 0.00 | 0.00 | 4.62 |
July | 0.00 | 0.462629E+11 | 0.00 | 0.00 | 0.632864E+09 | 0.00 | 0.00 | 0.00 | 4.63 |
August | 0.00 | 0.582617E+11 | 0.00 | 0.00 | 0.116749E+10 | 0.00 | 0.00 | 0.00 | 4.57 |
September | 0.00 | 0.536181E+11 | 0.00 | 0.00 | 0.867024E+09 | 0.00 | 0.00 | 0.00 | 4.50 |
October | 0.00 | 0.506930E+11 | 0.00 | 0.00 | 0.126094E+10 | 0.00 | 0.00 | 0.00 | 4.47 |
November | 0.00 | 0.433391E+11 | 0.00 | 0.00 | 0.894077E+09 | 0.00 | 0.00 | 0.00 | 4.39 |
December | 0.00 | 0.399449E+11 | 0.00 | 311554.88 | 0.723746E+09 | 0.00 | 6825164.36 | 0.00 | 4.34 |
Annual Sum or Average | 0.00 | 0.573515E+12 | 0.00 | 1387386.71 | 0.889697E+10 | 0.00 | 45825278.65 | 0.00 | 4.47 |
Minimum of Months | 0.00 | 0.309744E+11 | 0.00 | 0.00 | 0.289315E+09 | 0.00 | 0.00 | 0.00 | 4.32 |
Maximum of Months | 0.00 | 0.638151E+11 | 0.00 | 1020179.59 | 0.126094E+10 | 0.00 | 37151120.62 | 0.00 | 4.63 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.356770E+11 | 0.00 | 1076682.10 | 0.492000E+09 | 0.00 | 39039477.28 | 0.00 | 4.55 |
February | 0.00 | 0.327625E+11 | 0.00 | 58421.01 | 0.355743E+09 | 0.00 | 1940703.79 | 0.00 | 4.55 |
March | 0.00 | 0.413114E+11 | 0.00 | 0.00 | 0.424764E+09 | 0.00 | 0.00 | 0.00 | 4.64 |
April | 0.00 | 0.541856E+11 | 0.00 | 0.00 | 0.231236E+09 | 0.00 | 0.00 | 0.00 | 4.76 |
May | 0.00 | 0.677413E+11 | 0.00 | 0.00 | 0.312463E+09 | 0.00 | 0.00 | 0.00 | 4.84 |
June | 0.00 | 0.664462E+11 | 0.00 | 0.00 | 0.101871E+09 | 0.00 | 0.00 | 0.00 | 4.86 |
July | 0.00 | 0.492564E+11 | 0.00 | 0.00 | 0.275213E+09 | 0.00 | 0.00 | 0.00 | 4.89 |
August | 0.00 | 0.621246E+11 | 0.00 | 0.00 | 0.627398E+09 | 0.00 | 0.00 | 0.00 | 4.83 |
September | 0.00 | 0.569812E+11 | 0.00 | 0.00 | 0.518747E+09 | 0.00 | 0.00 | 0.00 | 4.75 |
October | 0.00 | 0.540638E+11 | 0.00 | 0.00 | 0.775082E+09 | 0.00 | 0.00 | 0.00 | 4.72 |
November | 0.00 | 0.461085E+11 | 0.00 | 0.00 | 0.535070E+09 | 0.00 | 0.00 | 0.00 | 4.63 |
December | 0.00 | 0.423575E+11 | 0.00 | 333003.94 | 0.484902E+09 | 0.00 | 7177871.99 | 0.00 | 4.58 |
Annual Sum or Average | 0.00 | 0.609016E+12 | 0.00 | 1468107.05 | 0.513449E+10 | 0.00 | 48158053.06 | 0.00 | 4.72 |
Minimum of Months | 0.00 | 0.327625E+11 | 0.00 | 0.00 | 0.101871E+09 | 0.00 | 0.00 | 0.00 | 4.55 |
Maximum of Months | 0.00 | 0.677413E+11 | 0.00 | 1076682.10 | 0.775082E+09 | 0.00 | 39039477.28 | 0.00 | 4.89 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.451575E+11 | 0.00 | 725139.35 | 0.00 | 0.00 | 36918899.84 | 0.00 | 17.90 |
February | 0.00 | 0.422395E+11 | 0.00 | 35426.98 | 0.00 | 0.00 | 1601679.96 | 0.00 | 17.92 |
March | 0.00 | 0.521837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 |
April | 0.00 | 0.676929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
May | 0.00 | 0.829400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
June | 0.00 | 0.810142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 |
July | 0.00 | 0.607321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
August | 0.00 | 0.778057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 |
September | 0.00 | 0.719075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
October | 0.00 | 0.685651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
November | 0.00 | 0.586605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 |
December | 0.00 | 0.527937E+11 | 0.00 | 217097.43 | 0.00 | 0.00 | 6905098.80 | 0.00 | 18.01 |
Annual Sum or Average | 0.00 | 0.761692E+12 | 0.00 | 977663.75 | 0.00 | 0.00 | 45425678.60 | 0.00 | 18.21 |
Minimum of Months | 0.00 | 0.422395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 |
Maximum of Months | 0.00 | 0.829400E+11 | 0.00 | 725139.35 | 0.00 | 0.00 | 36918899.84 | 0.00 | 18.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12935272.70 | 0.580847E+10 | 0.00 | 0.00 | 0.538304E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
February | 0.00 | 0.684182E+10 | 0.00 | 4780.43 | 0.334776E+10 | 0.00 | 564495.97 | 0.00 | 1.12 |
March | 0.00 | 0.818672E+10 | 0.00 | 0.00 | 0.445710E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
April | 0.00 | 0.113043E+11 | 0.00 | 0.00 | 0.504465E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
May | 0.00 | 0.133849E+11 | 0.00 | 0.00 | 0.704615E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 0.00 | 0.152463E+11 | 0.00 | 0.00 | 0.485329E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
July | 0.00 | 0.689773E+10 | 0.00 | 0.00 | 0.780632E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
August | 0.00 | 0.689284E+10 | 0.00 | 0.00 | 0.119784E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.772289E+10 | 0.00 | 0.00 | 0.963390E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 0.00 | 0.601118E+10 | 0.00 | 0.00 | 0.107498E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.00 | 0.652626E+10 | 0.00 | 0.00 | 0.779762E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
December | 2465189.30 | 0.598001E+10 | 0.00 | 0.00 | 0.729637E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
Annual Sum or Average | 15400462.00 | 0.100803E+12 | 0.00 | 4780.43 | 0.853944E+11 | 0.00 | 564495.97 | 0.00 | 1.14 |
Minimum of Months | 0.00 | 0.580847E+10 | 0.00 | 0.00 | 0.334776E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 12935272.70 | 0.152463E+11 | 0.00 | 4780.43 | 0.119784E+11 | 0.00 | 564495.97 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:45:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.209086E+12 | -0.121885E+11 | -0.169120E+12 | -0.663431E+12 | 0.157562E+13 |
February | 0.210026E+12 | -0.121037E+11 | -0.169585E+12 | -0.659600E+12 | 0.145770E+13 |
March | 0.291790E+12 | -0.151847E+11 | -0.211499E+12 | -0.841521E+12 | 0.167392E+13 |
April | 0.292073E+12 | -0.191410E+11 | -0.274151E+12 | -0.108415E+13 | 0.180915E+13 |
May | 0.305175E+12 | -0.231088E+11 | -0.335275E+12 | -0.132069E+13 | 0.202608E+13 |
June | 0.319770E+12 | -0.223051E+11 | -0.327447E+12 | -0.127273E+13 | 0.198927E+13 |
July | 0.263343E+12 | -0.169420E+11 | -0.238469E+12 | -0.972091E+12 | 0.173980E+13 |
August | 0.328450E+12 | -0.213377E+11 | -0.310164E+12 | -0.122416E+13 | 0.190609E+13 |
September | 0.249307E+12 | -0.198503E+11 | -0.286260E+12 | -0.112423E+13 | 0.181070E+13 |
October | 0.270479E+12 | -0.191569E+11 | -0.273782E+12 | -0.108196E+13 | 0.179533E+13 |
November | 0.210288E+12 | -0.161354E+11 | -0.229700E+12 | -0.894498E+12 | 0.167056E+13 |
December | 0.195110E+12 | -0.134162E+11 | -0.188547E+12 | -0.734111E+12 | 0.164697E+13 |
Annual Sum or Average | 0.314490E+13 | -0.210870E+12 | -0.301400E+13 | -0.118732E+14 | 0.211012E+14 |
Minimum of Months | 0.195110E+12 | -0.231088E+11 | -0.335275E+12 | -0.132069E+13 | 0.145770E+13 |
Maximum of Months | 0.328450E+12 | -0.121037E+11 | -0.169120E+12 | -0.659600E+12 | 0.202608E+13 |