Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:46:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10889.46 | 959.82 | 959.82 |
Net Site Energy | 10889.46 | 959.82 | 959.82 |
Total Source Energy | 21248.40 | 1872.88 | 1872.88 |
Net Source Energy | 21248.40 | 1872.88 | 1872.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 426.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 496.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 120.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4533.95 | 6355.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 426.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 496.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 120.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 426.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 496.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 120.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.83 | 402.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 218.75 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.63 | 560.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.83 | 402.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 218.75 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.63 | 560.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4533.952 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4533.952 | 100.00 |
Total On-Site and Utility Electric Sources | 4533.952 | 100.00 |
Total Electricity End Uses | 4533.952 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 14.43 | 0.68 |
Air to Air Heat Recovery for Heating | 2099.87 | 99.32 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2114.31 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.33 |
Time Setpoint Not Met During Occupied Cooling | 26.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7192.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-19:30 | 22-MAR-17:00 | - | - | - | - | - | - | - | - | - | - | 08-MAY-20:10 |
Heating | 0.00 | 196294.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113008.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31552.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26848.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3211.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3880.17 | 266399.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2398.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 354250.08 | 566943.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 196294.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 113008.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26848.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3211.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3880.17 | 266399.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1095.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1529.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1351.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2479.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1571.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 197.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 382.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.39 | 3420.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14359.03 | 6889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 134.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 119.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 301.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1265.64 | 607.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 134.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 119.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 301.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1265.64 | 607.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.55 | 0.591933 | 0.512000 | 1.30 | 1.00 | 0.500000 | 0.000644 | 0.000059 | 1.30 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.444681 | 0.114933 | 0.512000 | 0.227676 | 0.512000 | 0.500000 | 0.003315 | 0.000030 | 0.227676 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.231204 | 0.255981 | 0.512000 | 0.118376 | 0.682615 | 0.500000 | 0.001488 | 0.000012 | 0.118376 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.176202 | 0.710282 | 0.512000 | 0.090216 | 1.00 | 0.500000 | 0.000536 | 0.000017 | 0.090216 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.103795 | 0.695666 | 0.512000 | 0.053143 | 1.00 | 0.500000 | 0.000548 | 0.000011 | 0.053143 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.29 | 0.018070 | 0.512000 | 1.68 | 0.512000 | 0.500000 | 0.021084 | 0.000093 | 1.68 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.77 | 0.081242 | 0.512000 | 0.906963 | 0.512000 | 0.500000 | 0.004690 | 0.000092 | 0.906963 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.16 | 0.193350 | 0.512000 | 2.64 | 0.515599 | 0.500000 | 0.001971 | 0.000239 | 2.64 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.61 | 0.735320 | 0.512000 | 0.826437 | 1.00 | 0.500000 | 0.000518 | 0.000108 | 0.826437 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.12 | 0.119166 | 0.512000 | 1.09 | 0.512000 | 0.500000 | 0.003197 | 0.000094 | 1.09 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113777 | 0.512000 | 1.14 | 0.512000 | 0.500000 | 0.003349 | 0.000097 | 1.14 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.062271 | 0.512000 | 1.16 | 0.512000 | 0.500000 | 0.011005 | 0.000065 | 1.16 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.807033 | 0.389128 | 0.512000 | 0.413201 | 1.00 | 0.500000 | 0.000979 | 0.000065 | 0.413201 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6788.19 | 0.000059 | 141.56 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3485.01 | 0.000030 | 80.90 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1380.34 | 0.000012 | 30.78 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1895.61 | 0.000017 | 47.08 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1200.98 | 0.000011 | 30.43 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10639.37 | 0.000093 | 224.35 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10492.37 | 0.000092 | 233.70 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 27300.00 | 0.000239 | 600.13 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5067.06 | 0.000044 | 144.81 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5070.31 | 0.000044 | 144.90 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 29097.60 | 0.000255 | 831.53 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 29172.70 | 0.000255 | 833.67 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5074.16 | 0.000044 | 145.01 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5077.41 | 0.000044 | 145.10 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12381.15 | 0.000108 | 286.37 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1531.89 | 0.000013 | 43.78 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1533.54 | 0.000013 | 43.82 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7348.20 | 0.000064 | 209.98 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10697.57 | 0.000094 | 233.97 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11071.83 | 0.000097 | 241.85 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7373.35 | 0.000065 | 155.51 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7433.50 | 0.000065 | 178.01 |
VAV WITH REHEAT HEATING COIL | 169288.45 | 0.001481 | 2890.13 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000134 | 261.90 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.19 | 0.000044 | 0.000373 |
ROOM_2_FLR_3 FAN COIL | 1.08 | 0.000044 | 0.000339 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.37 | 0.000255 | 0.002582 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.63 | 0.000255 | 0.001858 |
ROOM_5_FLR_3 FAN COIL | 1.07 | 0.000044 | 0.000336 |
ROOM_6_FLR_3 FAN COIL | 0.973021 | 0.000044 | 0.000307 |
ROOM_1_FLR_6 FAN COIL | 0.309453 | 0.000013 | 0.000097 |
ROOM_2_FLR_6 FAN COIL | 0.278558 | 0.000013 | 0.000088 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.69 | 0.000064 | 0.000537 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.19 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.08 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.37 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.63 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.07 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.973021 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.309453 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.278558 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.69 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008568 | 12.80 | 0.008500 | 0.000373 | 1.19 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000339 | 1.08 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008504 | 12.80 | 0.008500 | 0.002582 | 8.37 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008755 | 12.80 | 0.008500 | 0.001858 | 5.63 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008575 | 12.80 | 0.008500 | 0.000336 | 1.07 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008582 | 12.80 | 0.008500 | 0.000307 | 0.973021 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000097 | 0.309453 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008572 | 12.80 | 0.008500 | 0.000088 | 0.278558 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008603 | 12.80 | 0.008500 | 0.000537 | 1.69 | |
VAV WITH REHEAT COOLING COIL | 26.78 | 6.70 | 0.009205 | 10.95 | 0.008500 | 0.013794 | 22.64 | 482309.22 |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001300 | 2.05 | 45447.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.65 | 11.65 | 22.76 | 11.65 | 22.64 | 22.64 | 0.300000 | 0.514748 | 22.64 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.64 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.64 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013794 | 0.000035 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001481 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001300 | 0.000366 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000134 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.021608 | 3527.99 | |
HEATSYS1 PUMP | 0.003375 | 1016.29 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003375 | 0.404956 |
COOLSYS1 | 0.021608 | 2.59 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 385741.57 | 385741.57 | 0.003375 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.021608 | 2442.54 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.021608 | 755540.86 | 756166.44 | 86.20 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8203 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.052 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.15703352E-14 | 0.29012323E-16 | -0.15483104E-09 | 0.40370831E-16 |
29 | 8 | 0.22592825E-07 | 0.11106548E-12 | 0.38529762E-03 | -0.25688817E-09 |
30 | 7 | -0.12465369E-01 | 0.57225352E-08 | -0.23408026E-01 | 0.14173579E-03 |
31 | 6 | 0.41143163 | 0.19878644E-05 | 0.47726710 | -0.48194459E-02 |
32 | 5 | -5.2499075 | 0.74130146E-04 | -4.4810026 | 0.63919688E-01 |
33 | 4 | 33.265337 | 0.60571720E-03 | 21.595652 | -0.42560793 |
34 | 3 | -111.78466 | 0.13187857E-02 | -55.931065 | 1.5232626 |
35 | 2 | 197.68466 | 0.74115454E-03 | 78.156489 | -2.9095067 |
36 | 1 | -171.36898 | 0.79055603E-04 | -55.336681 | 2.7491709 |
37 | 0 | 57.057407 | 0.44959794E-06 | 15.545184 | |
38 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
39 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
40 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
41 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
42 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
43 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
44 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
45 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
46 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
47 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
48 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
49 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
50 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
51 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
52 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
53 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
54 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
55 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
56 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
57 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
58 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
59 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
60 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
61 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
62 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
63 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
64 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
65 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
66 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
67 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
68 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
69 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
70 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
71 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
72 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
73 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
74 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
75 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
76 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
77 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.38_SHGC_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1490 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.8401E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1700 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1033 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.9040E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0567E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.1657E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3839E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1708 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1058 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1958 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1233 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1096 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0553E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.6776E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8924E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9132E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.2626E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0128E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7133E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8567E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1374E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1005E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4540E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9132E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.2626E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0128E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7133E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8567E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1374E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1005E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4540E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34559.86620 | 34559.86620 | 2.54736 | 2.54736 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 26.12400 | 8.81626E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6032.43119 | 6032.43119 | 0.44468 | 0.44468 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2301.28341 | 2301.28341 | 0.10006 | 0.10006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3136.37594 | 3136.37594 | 0.23120 | 0.23120 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 764.91278 | 764.91278 | 3.32603E-002 | 9.17347E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2390.76963 | 2390.76963 | 0.17620 | 0.17620 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1426.70734 | 1426.70734 | 6.20366E-002 | 6.20366E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1408.31139 | 1408.31139 | 0.10379 | 0.10379 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 924.73325 | 924.73325 | 4.02096E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44646.33209 | 44646.33209 | 3.29079 | 3.29079 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1883.09688 | 1883.09688 | 8.18789E-002 | 8.18789E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24011.39559 | 24011.39559 | 1.77141 | 1.77141 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5776.33240 | 5776.33240 | 0.25116 | 0.67639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69919.40468 | 69919.40468 | 5.15562 | 5.15562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13575.56490 | 13575.56490 | 0.59030 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11952.94596 | 11952.94596 | 1.18720 | 1.18720 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5067.17323 | 5067.17323 | 0.22162 | 0.22162 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10838.92848 | 10838.92848 | 1.07655 | 1.07655 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5070.41683 | 5070.41683 | 0.22176 | 0.22176 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 84288.20333 | 84288.20333 | 8.37132 | 8.37132 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 29097.90585 | 29097.90585 | 1.27267 | 1.27267 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 56661.97902 | 56661.97902 | 5.62798 | 5.62798 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 29173.01522 | 29173.01522 | 1.27596 | 1.27596 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10745.67559 | 10745.67559 | 1.06729 | 1.06729 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5074.27328 | 5074.27328 | 0.22193 | 0.22193 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9796.58814 | 9796.58814 | 0.97302 | 0.97302 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5077.51592 | 5077.51592 | 0.22207 | 0.22207 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21899.39665 | 21899.39665 | 1.61413 | 1.61413 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8083.17938 | 8083.17938 | 0.35148 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3115.63825 | 3115.63825 | 0.30945 | 0.30945 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1531.92674 | 1531.92674 | 6.70007E-002 | 6.70007E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2804.57988 | 2804.57988 | 0.27856 | 0.27856 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1533.57006 | 1533.57006 | 6.70726E-002 | 6.70726E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17043.20485 | 17043.20485 | 1.69281 | 1.69281 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7348.32024 | 7348.32024 | 0.32139 | 0.32139 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28737.30940 | 28737.30940 | 2.12077 | 2.12077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5049.97613 | 5049.97613 | 0.21958 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30098.97419 | 30098.97419 | 2.22122 | 2.22122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5157.06502 | 5157.06502 | 0.22424 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30767.29106 | 30767.29106 | 2.27366 | 2.27366 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1346.71126 | 1346.71126 | 5.85490E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10949.30794 | 10949.30794 | 0.80703 | 0.80703 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5284.23607 | 5284.23607 | 0.22977 | 0.22977 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 377262.28 | 22.63641 | 22.63641 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 181124.64 | 7.26573 | 7.26573 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 19.35313 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 3.89147 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.54736 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59193 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30425 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.43654E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.93860E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30425 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6788.19026 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.93860E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.55601 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44468 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11493 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22768 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31498E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04884E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22768 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3485.00904 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04884E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 80.90494 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23120 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25598 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11838 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68261 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48839E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20758E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11838 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1380.33928 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20758E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.77516 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17620 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71028 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.02156E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.36407E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65836E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.02156E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1895.61102 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65836E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.08259 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10379 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69567 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.31430E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.47677E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05067E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.31430E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1200.98370 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05067E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.42893 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29079 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.80704E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68489 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10841E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.30779E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68489 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10639.37272 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.30779E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.34770 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77141 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.12418E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.90696 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.68970E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.17918E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90696 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10492.37188 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.17918E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 233.69900 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.15562 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19335 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.63968 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51560 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97052E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38832E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.63968 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27300.00389 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38832E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 600.12532 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18720 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.18720 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.43289E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.72670E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56772E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.72670E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18720 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5067.06294 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.43289E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.80508 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07655 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07655 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.43573E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.38554E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57436E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.38554E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07655 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5070.30647 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.43573E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 144.89775 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.37132 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.37132 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.54558E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.58219E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69178 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50436E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.58219E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.37132 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29097.59631 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54558E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 831.52800 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.62798 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.62798 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.55216E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.85762E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69087 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75524E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.85762E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.62798 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29172.70492 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.55216E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 833.67388 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06729 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.06729 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.43910E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.35727E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57530E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.35727E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06729 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5074.16285 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.43910E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 145.00792 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97302 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.97302 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.44194E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.06671E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69131 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58240E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.06671E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.97302 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5077.40541 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.44194E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 145.10056 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61413 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73532 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82644 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.18142E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08316E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82644 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12381.15469 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08316E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 286.37045 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30945 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30945 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.34017E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.70675E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56502E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.70675E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30945 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1531.89443 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34017E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.77587 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27856 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27856 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.34161E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.75428E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57194E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.75428E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27856 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1533.53772 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34161E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.82281 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.69281 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.69281 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.42852E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.36539E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69111 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60309E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.36539E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.69281 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7348.19559 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.42852E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 209.98246 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12077 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11917 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.08583 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19723E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.35870E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08583 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10697.57352 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.35870E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 233.96619 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22122 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11378 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13727 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34867E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.68612E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13727 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11071.83323 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.68612E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 241.85403 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27366 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.22714E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16412 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51200 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10047E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.45053E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16412 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7373.35227 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.45053E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 155.50883 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80703 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38913 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51200 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41320 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.79112E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.50315E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41320 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7433.49771 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.50315E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.00646 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65204 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65204 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.75789 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65204 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.63641 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.63641 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51475 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.63641 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.63641 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.77767 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95288 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.20523E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 482309.22296 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37940E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.63641 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 169288.44853 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48101E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2890.13070 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.63641 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37940E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.45216E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.48101E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29980E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34209E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.90442 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29980E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.66356E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.34209E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.16084E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3527.98703 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.37464E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.40496 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.37464E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1016.29203 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 385741.57294 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 385741.57000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.37464E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.16084E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.59300 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.16084E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2442.54441 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.16084E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 755540.86120 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 756166.44000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 86.20297 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6823.29 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3501.04 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1386.95 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1903.65 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1205.98 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10693.81 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10542.67 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 27432.65 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5457.85 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5461.35 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 31341.50 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 31422.39 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5465.50 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5468.99 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12438.32 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1649.99 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1651.76 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7914.66 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10750.56 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11126.73 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7411.08 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7466.23 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 128945.79 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11685.10 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19357.23 | 16710.31 | 2646.92 | 0.86 | 3837.25 | 38.92 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17574.97 | 15160.39 | 2414.58 | 0.86 | 3477.63 | 35.27 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 134847.25 | 117261.19 | 17586.06 | 0.87 | 27189.50 | 275.77 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 94956.79 | 80340.98 | 14615.81 | 0.85 | 17998.83 | 182.55 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17426.81 | 15031.00 | 2395.81 | 0.86 | 3447.43 | 34.97 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15908.69 | 13710.65 | 2198.04 | 0.86 | 3141.07 | 31.86 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5043.07 | 4354.81 | 688.26 | 0.86 | 1000.45 | 10.15 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4545.47 | 3922.05 | 623.42 | 0.86 | 900.03 | 9.13 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27783.25 | 23889.62 | 3893.64 | 0.86 | 5455.62 | 55.33 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 560052.88 | 395427.14 | 164625.74 | 0.71 | 88688.01 | 899.52 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49570.73 | 35167.84 | 14402.90 | 0.71 | 6912.11 | 70.11 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8452296449E-002 | 2.2766551341E-002 | Pass | Pass | 4.7502985884E-003 | 1.3962516492E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.9721471055E-003 | 1.3800732394E-003 | Pass | Pass | 0.7203699758 | 5.6840378561 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.9278979035E-002 | 2.9204877490E-002 | Pass | Pass | 1.2192634848E-002 | 3.3579857184E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3201383304E-003 | 6.3234942286E-003 | Pass | Pass | 4.5418076192E-002 | 9.6198748931E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5481409613E-004 | 2.7136811581E-004 | Pass | Pass | 9.2397003976E-002 | 0.2612198598 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.8682859200E-002 | 0.2032611096 | Pass | Pass | 1.9410021182E-002 | 5.2658849438E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1616577688E-002 | 3.6327510428E-002 | Pass | Pass | 2.7804786101E-002 | 8.7901251202E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7453689260E-002 | 4.6811239002E-002 | Pass | Pass | 1.3134247040E-002 | 3.1790858413E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5602300151E-002 | 0.2346208771 | Pass | Pass | 0.1076182313 | 0.3825634972 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5839494634E-002 | 0.2349806950 | Pass | Pass | 0.1292778679 | 0.4613882879 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.7375485729E-002 | 3.7107925234E-002 | Pass | Pass | 7.3797805792E-003 | 6.2846341306E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6213190979E-002 | 8.3508237529E-002 | Pass | Pass | 0.5522346569 | 2.7880968412 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5154812283E-002 | 0.2328648633 | Pass | Pass | 0.1222182969 | 0.4149382925 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5439239537E-002 | 0.2328853392 | Pass | Pass | 0.1888571652 | 1.0627425760 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3321114993E-004 | 3.4713138822E-004 | Pass | Pass | 0.4375655840 | 3.8008614701 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6283997213E-002 | 0.2754613341 | Pass | Pass | 6.9061942444E-002 | 0.2104897376 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6379441465E-002 | 0.2750506040 | Pass | Pass | 6.8869221316E-002 | 0.2136175579 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2530332610E-002 | 0.1969401488 | Pass | Pass | 7.4735551522E-002 | 0.2205258987 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9503487088E-002 | 6.7952405882E-002 | Pass | Pass | 1.3268264918E-002 | 4.1245581226E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.9369321793E-002 | 4.8435838930E-002 | Pass | Pass | 1.3731731219E-002 | 3.9987989080E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2543967066E-002 | 6.5049102002E-002 | Pass | Pass | 2.1133320567E-002 | 4.2659586698E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.1223551734E-004 | 5.1957590003E-004 | Pass | Pass | 3.0970419627E-002 | 4.4521343175E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3529.82 | 131.29 | 1818.08 | 7357.85 | 2410.66 | 15247.70 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.361 | 0.397 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.361 | 0.397 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.361 | 0.397 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.361 | 0.397 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.13 | 0.0000 | Y | 14.24 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.17 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.75 | 0.0000 | Y | 31.01 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.75 | 0.0000 | Y | 31.01 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.55 | 83.55 | 193.50 | |
Exterior Lighting Total | 12338.45 | 193.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 385741.57 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 756166.44 | 2.96 | 756299.35 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13030.72 | 19357.23 | 16710.31 | 2646.92 | 0.86 | - | 3837.25 | 38.92 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11837.82 | 17574.97 | 15160.39 | 2414.58 | 0.86 | - | 3477.63 | 35.27 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 90288.61 | 134847.25 | 117261.19 | 17586.06 | 0.87 | - | 27189.50 | 275.77 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64953.35 | 94956.79 | 80340.98 | 14615.81 | 0.85 | - | 17998.83 | 182.55 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11738.98 | 17426.81 | 15031.00 | 2395.81 | 0.86 | - | 3447.43 | 34.97 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10722.99 | 15908.69 | 13710.65 | 2198.04 | 0.86 | - | 3141.07 | 31.86 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3394.05 | 5043.07 | 4354.81 | 688.26 | 0.86 | - | 1000.45 | 10.15 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3061.01 | 4545.47 | 3922.05 | 623.42 | 0.86 | - | 900.03 | 9.13 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 18760.53 | 27783.25 | 23889.62 | 3893.64 | 0.86 | - | 5455.62 | 55.33 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 482309.22 | 560052.88 | 395427.14 | 164625.74 | 0.71 | - | 88688.01 | 899.52 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49570.73 | 35167.84 | 14402.90 | 0.71 | - | 6912.11 | 70.11 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6788.19 | 6823.29 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3485.01 | 3501.04 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1380.34 | 1386.95 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1895.61 | 1903.65 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1200.98 | 1205.98 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10639.37 | 10693.81 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10492.37 | 10542.67 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27300.00 | 27432.65 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5067.06 | 5457.85 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5070.31 | 5461.35 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29097.60 | 31341.50 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29172.70 | 31422.39 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5074.16 | 5465.50 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5077.41 | 5468.99 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12381.15 | 12438.32 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1531.89 | 1649.99 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1533.54 | 1651.76 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7348.20 | 7914.66 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10697.57 | 10750.56 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11071.83 | 11126.73 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7373.35 | 7411.08 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7433.50 | 7466.23 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 169288.45 | 128945.79 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 11685.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 835.35 | 703.64 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.08 | 757.50 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.37 | 5890.37 | 703.64 | 1.00 | 0.94 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.63 | 3960.05 | 703.64 | 1.00 | 0.96 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 750.98 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 684.65 | 703.64 | 1.00 | 1.20 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 217.74 | 703.64 | 1.00 | 1.69 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 196.00 | 703.64 | 1.00 | 1.77 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.69 | 1191.12 | 703.64 | 1.00 | 1.09 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.64 | 50720.01 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.021608 | 3527.99 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003375 | 1016.29 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.021608 | 2442.54 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34559.87 | 34559.87 | 17.46 | 2.547 | 2.547 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 24.00 | 24.00 | 0.00920 | 26.12 | 0.00882 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6032.43 | 6032.43 | 89.94 | 0.445 | 0.445 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00890 | 29.05 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3136.38 | 3136.38 | 40.38 | 0.231 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00940 | 29.19 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 2390.77 | 2390.77 | 14.56 | 0.176 | 0.176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00876 | 29.09 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1408.31 | 1408.31 | 14.86 | 0.104 | 0.104 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44646.33 | 44646.33 | 572.10 | 3.291 | 3.291 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 24011.40 | 24011.40 | 127.14 | 1.771 | 1.771 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.00983 | 29.05 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69919.40 | 69919.40 | 53.45 | 5.156 | 5.156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00986 | 29.23 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11952.95 | 11952.95 | 306.31 | 1.187 | 1.187 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 28.36 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10838.93 | 10838.93 | 277.80 | 1.077 | 1.077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 84288.20 | 84288.20 | 3436.99 | 8.371 | 8.371 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 29.14 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56661.98 | 56661.98 | 2309.85 | 5.628 | 5.628 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00876 | 29.40 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10745.68 | 10745.68 | 275.37 | 1.067 | 1.067 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00858 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9796.59 | 9796.59 | 251.08 | 0.973 | 0.973 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 23.68 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21899.40 | 21899.40 | 56.24 | 1.614 | 1.614 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00936 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3115.64 | 3115.64 | 79.84 | 0.309 | 0.309 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2804.58 | 2804.58 | 71.88 | 0.279 | 0.279 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17043.20 | 17043.20 | 694.77 | 1.693 | 1.693 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00860 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28737.31 | 28737.31 | 86.65 | 2.121 | 2.121 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01045 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 30098.97 | 30098.97 | 90.75 | 2.221 | 2.221 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01037 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30767.29 | 30767.29 | 297.83 | 2.274 | 2.274 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01008 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10949.31 | 10949.31 | 26.57 | 0.807 | 0.807 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00896 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.90 | 0.00269 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2301.28 | 2301.28 | 34.31 | 0.100 | 0.100 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 764.91 | 764.91 | 9.85 | 0.033 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00742 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1426.71 | 1426.71 | 8.69 | 0.062 | 0.062 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00728 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 924.73 | 924.73 | 9.76 | 0.040 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00735 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1883.10 | 1883.10 | 24.13 | 0.082 | 0.082 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00726 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 5776.33 | 5776.33 | 30.58 | 0.251 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13575.56 | 13575.56 | 10.38 | 0.590 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5067.17 | 5067.17 | 129.85 | 0.222 | 0.222 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5070.42 | 5070.42 | 129.95 | 0.222 | 0.222 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 29097.91 | 29097.91 | 1186.51 | 1.273 | 1.273 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00750 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29173.02 | 29173.02 | 1189.25 | 1.276 | 1.276 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00751 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5074.27 | 5074.27 | 130.04 | 0.222 | 0.222 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5077.52 | 5077.52 | 130.13 | 0.222 | 0.222 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8083.18 | 8083.18 | 20.76 | 0.351 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1531.93 | 1531.93 | 39.26 | 0.067 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1533.57 | 1533.57 | 39.30 | 0.067 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7348.32 | 7348.32 | 299.56 | 0.321 | 0.321 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5049.98 | 5049.98 | 15.23 | 0.220 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 5157.07 | 5157.07 | 15.55 | 0.224 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1346.71 | 1346.71 | 13.04 | 0.059 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00556 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5284.24 | 5284.24 | 12.82 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.64 | 22.64 | 7.27 | 7.27 | 22.6364 | 11.6520 | 22.6364 | 0.5147 | 0.3000 |
FLR_3_DOAS | 19.35 | 2.05 | 3.89 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6788.190 | 6788.190 | 1.304250 | 0.00005939 | 141.556 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6788.19 | 6788.19 | 1.304250 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6826.34 | 6826.34 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3485.009 | 3485.009 | 0.227676 | 0.00003049 | 80.905 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3485.01 | 3485.01 | 0.227676 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00748969 | 47.7681 | 2301.28 | 0.00 | 3503.64 | 3503.64 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1380.339 | 1380.339 | 0.118376 | 0.00001208 | 30.775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1380.34 | 1380.34 | 0.118376 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00741621 | 47.3039 | 764.91 | 0.00 | 1387.83 | 1387.83 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1895.611 | 1895.611 | 0.090216 | 0.00001658 | 47.083 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1895.61 | 1895.61 | 0.090216 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00728128 | 46.4533 | 1426.71 | 0.00 | 1905.40 | 1905.40 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1200.984 | 1200.984 | 0.053143 | 0.00001051 | 30.429 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1200.98 | 1200.98 | 0.053143 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00735066 | 46.8907 | 924.73 | 0.00 | 1207.15 | 1207.15 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10639.373 | 10639.373 | 1.684885 | 0.00009308 | 224.348 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10639.37 | 10639.37 | 1.684885 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00726024 | 46.3216 | 1883.10 | 0.00 | 10698.93 | 10698.93 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10492.372 | 10492.372 | 0.906963 | 0.00009179 | 233.699 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10492.37 | 10492.37 | 0.906963 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754537 | 48.1186 | 5776.33 | 0.00 | 10549.31 | 10549.31 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 27300.004 | 27300.004 | 2.639678 | 0.00023883 | 600.125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 27300.00 | 27300.00 | 2.639678 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00745713 | 47.5618 | 13575.56 | 0.00 | 27448.95 | 27448.95 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13030.717 | -999.000 | 1.187195 | 0.00037267 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 13030.72 | 12821.03 | 1.187195 | 21.69 | 15.47 | 0.00856772 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856772 | 54.1788 | 11952.95 | 0.00 | 13223.27 | 13223.27 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5067.063 | 5067.063 | 0.221619 | 0.00004433 | 144.805 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5067.06 | 5067.06 | 0.221619 | 21.11 | 14.26 | 0.00746754 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746754 | 47.3051 | 5067.17 | 0.00 | 5462.41 | 5462.41 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11837.817 | -999.000 | 1.076549 | 0.00033855 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 11837.82 | 11628.97 | 1.076549 | 21.69 | 15.48 | 0.00857436 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00857436 | 54.2203 | 10838.93 | 0.00 | 12012.44 | 12012.44 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5070.306 | 5070.306 | 0.221761 | 0.00004436 | 144.898 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5070.31 | 5070.31 | 0.221761 | 21.11 | 14.27 | 0.00746788 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746788 | 47.3073 | 5070.42 | 0.00 | 5465.91 | 5465.91 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 90288.607 | -999.000 | 8.371320 | 0.00258219 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 90288.61 | 90193.65 | 8.371320 | 21.69 | 15.42 | 0.00850436 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00882108 | 18.26 | 0.0000 | 21.11 | 0.00850436 | 53.7823 | 84288.20 | 0.00 | 91630.04 | 91630.04 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 29097.596 | 29097.596 | 1.272671 | 0.00025456 | 831.528 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29097.60 | 29097.60 | 1.272671 | 21.11 | 14.30 | 0.00750462 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00750462 | 47.5362 | 29097.91 | 0.00 | 31368.09 | 31368.09 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64953.351 | -999.000 | 5.627980 | 0.00185762 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 64953.35 | 61181.80 | 5.627980 | 21.69 | 15.64 | 0.00875524 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 0.0000 | 21.11 | 0.00875524 | 55.3491 | 56661.98 | 0.00 | 65892.06 | 64547.78 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 29172.705 | 29172.705 | 1.275956 | 0.00025522 | 833.674 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29172.70 | 29172.70 | 1.275956 | 21.11 | 14.30 | 0.00750566 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00750566 | 47.5426 | 29173.02 | 0.00 | 31449.06 | 31449.06 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11738.984 | -999.000 | 1.067286 | 0.00033573 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 11738.98 | 11529.32 | 1.067286 | 21.69 | 15.48 | 0.00857530 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00857530 | 54.2261 | 10745.68 | 0.00 | 11912.11 | 11912.11 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5074.163 | 5074.163 | 0.221930 | 0.00004439 | 145.008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5074.16 | 5074.16 | 0.221930 | 21.11 | 14.27 | 0.00746821 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746821 | 47.3093 | 5074.27 | 0.00 | 5470.07 | 5470.07 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10722.993 | -999.000 | 0.973021 | 0.00030667 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 10722.99 | 10513.77 | 0.973021 | 21.69 | 15.49 | 0.00858240 | 12.80 | 11.97 | 0.00850000 | 23.68 | 0.00881240 | 16.40 | 0.0000 | 21.11 | 0.00858240 | 54.2704 | 9796.59 | 0.00 | 10880.85 | 10880.85 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5077.405 | 5077.405 | 0.222071 | 0.00004442 | 145.101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5077.41 | 5077.41 | 0.222071 | 21.11 | 14.27 | 0.00746855 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00746855 | 47.3115 | 5077.52 | 0.00 | 5473.56 | 5473.56 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12381.155 | 12381.155 | 0.826437 | 0.00010832 | 286.370 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12381.15 | 12381.15 | 0.826437 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758392 | 48.3605 | 8083.18 | 0.00 | 12447.44 | 12447.44 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3394.048 | -999.000 | 0.309453 | 0.00009707 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3394.05 | 3341.58 | 0.309453 | 21.69 | 15.47 | 0.00856502 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856502 | 54.1620 | 3115.64 | 0.00 | 3444.24 | 3444.24 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1531.894 | 1531.894 | 0.067001 | 0.00001340 | 43.776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1531.89 | 1531.89 | 0.067001 | 21.11 | 14.34 | 0.00755184 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00755184 | 47.8327 | 1531.93 | 0.00 | 1651.42 | 1651.42 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3061.007 | -999.000 | 0.278558 | 0.00008754 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 3061.01 | 3008.73 | 0.278558 | 21.69 | 15.48 | 0.00857194 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00857194 | 54.2052 | 2804.58 | 0.00 | 3106.19 | 3106.19 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1533.538 | 1533.538 | 0.067073 | 0.00001342 | 43.823 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1533.54 | 1533.54 | 0.067073 | 21.11 | 14.34 | 0.00755231 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00755231 | 47.8357 | 1533.57 | 0.00 | 1653.19 | 1653.19 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 18760.530 | -999.000 | 1.692810 | 0.00053654 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 18760.53 | 18304.78 | 1.692810 | 21.69 | 15.50 | 0.00860309 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00860309 | 54.4001 | 17043.20 | 0.00 | 19035.30 | 19035.30 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7348.196 | 7348.196 | 0.321391 | 0.00006429 | 209.982 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7348.20 | 7348.20 | 0.321391 | 21.11 | 14.36 | 0.00756832 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00756832 | 47.9355 | 7348.32 | 0.00 | 7921.55 | 7921.55 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10697.574 | 10697.574 | 1.085833 | 0.00009359 | 233.966 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10697.57 | 10697.57 | 1.085833 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765874 | 48.8321 | 5049.98 | 0.00 | 10756.80 | 10756.80 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11071.833 | 11071.833 | 1.137266 | 0.00009686 | 241.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 11071.83 | 11071.83 | 1.137266 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00766537 | 48.8748 | 5157.07 | 0.00 | 11133.15 | 11133.15 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7373.352 | 7373.352 | 1.164115 | 0.00006451 | 155.509 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7373.35 | 7373.35 | 1.164115 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00556339 | 35.5983 | 1346.71 | 0.00 | 7414.63 | 7414.63 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7433.498 | 7433.498 | 0.413201 | 0.00006503 | 178.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 7433.50 | 7433.50 | 0.413201 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771122 | 49.1630 | 5284.24 | 0.00 | 7472.40 | 7472.40 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 482309.223 | -999.000 | 22.636407 | 0.01379398 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 482309.22 | 432768.57 | 22.636407 | 26.78 | 17.78 | 0.00920523 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 51.5164 | 23.99 | 0.00956952 | 50.7147 | 306806.65 | 0.00 | 487688.36 | 422944.65 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 169288.449 | 169288.449 | 6.790922 | 0.00148101 | 2890.131 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 169288.45 | 169288.45 | 6.790922 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 171.7213 | 21.20 | 0.00649290 | 40.9699 | 51075.11 | 0.00 | 155961.81 | 155961.81 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00860625 | 54.4188 | 194853.19 | 0.00 | 45917.97 | 43441.59 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00750543 | 47.5412 | 88974.12 | 0.00 | 14133.30 | 14133.30 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6788.190 | 6788.190 | 1.304250 | 0.00005939 | 141.556 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.7251 | 1.759777 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6788.19 | 6788.19 | 1.0000 | 1.54813272 | 1.304250 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05937999 | 60.00 | 32.22 | 27.78 | 0.000 | 6788.19 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6826.34 | 6826.34 | 1.54813272 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3485.009 | 3485.009 | 0.227676 | 0.00003049 | 80.905 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.8856 | 0.903457 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3485.01 | 3485.01 | 1.0000 | 0.27024988 | 0.227676 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03048527 | 60.00 | 32.22 | 27.78 | 0.000 | 3485.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00748969 | 21.00 | 0.00748969 | 47.7681 | 2301.28 | 0.00 | 3503.64 | 3503.64 | 0.27024988 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.31 | 17.81 | 0.00800000 | 49899.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1380.339 | 1380.339 | 0.118376 | 0.00001208 | 30.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.3508 | 0.357840 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1380.34 | 1380.34 | 1.0000 | 0.14051165 | 0.118376 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01207458 | 60.00 | 32.22 | 27.78 | 0.000 | 1380.34 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741621 | 21.00 | 0.00741621 | 47.3039 | 764.91 | 0.00 | 1387.83 | 1387.83 | 0.14051165 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.29 | 16.77 | 0.00800000 | 46811.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1895.611 | 1895.611 | 0.090216 | 0.00001658 | 47.083 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.4817 | 0.491420 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1895.61 | 1895.61 | 1.0000 | 0.10708504 | 0.090216 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01658194 | 60.00 | 32.22 | 27.78 | 0.000 | 1895.61 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00728128 | 21.00 | 0.00728128 | 46.4533 | 1426.71 | 0.00 | 1905.40 | 1905.40 | 0.10708504 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.05 | 19.36 | 0.00800000 | 54728.1 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1200.984 | 1200.984 | 0.053143 | 0.00001051 | 30.429 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.3052 | 0.311344 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1200.98 | 1200.98 | 1.0000 | 0.06308023 | 0.053143 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01050566 | 60.00 | 32.22 | 27.78 | 0.000 | 1200.98 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00735066 | 21.00 | 0.00735066 | 46.8907 | 924.73 | 0.00 | 1207.15 | 1207.15 | 0.06308023 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.37 | 19.77 | 0.00800000 | 56071.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10639.373 | 10639.373 | 1.684885 | 0.00009308 | 224.348 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 2.7037 | 2.758161 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10639.37 | 10639.37 | 1.0000 | 1.99994330 | 1.684885 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09306838 | 60.00 | 32.22 | 27.78 | 0.000 | 10639.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00726024 | 21.00 | 0.00726024 | 46.3216 | 1883.10 | 0.00 | 10698.93 | 10698.93 | 1.99994330 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.85 | 15.17 | 0.00800000 | 42284.4 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10492.372 | 10492.372 | 0.906963 | 0.00009179 | 233.699 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 2.6664 | 2.720052 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10492.37 | 10492.37 | 1.0000 | 1.07655685 | 0.906963 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09178248 | 60.00 | 32.22 | 27.78 | 0.000 | 10492.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00754537 | 21.00 | 0.00754537 | 48.1186 | 5776.33 | 0.00 | 10549.31 | 10549.31 | 1.07655685 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.21 | 16.74 | 0.00800000 | 46733.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27300.004 | 27300.004 | 2.639678 | 0.00023883 | 600.125 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 6.9377 | 7.077278 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 27300.00 | 27300.00 | 1.0000 | 3.13327397 | 2.639678 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23880798 | 60.00 | 32.22 | 27.78 | 0.000 | 27300.00 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00745713 | 21.00 | 0.00745713 | 47.5618 | 13575.56 | 0.00 | 27448.95 | 27448.95 | 3.13327397 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.19 | 16.38 | 0.00800000 | 45695.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13030.717 | -999.000 | 1.187195 | 0.00037267 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7670 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.187195 | 1.40918958 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 1.7247 | 1.724655 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 13030.72 | 12821.03 | 1.0000 | 1.40918958 | 1.187195 | 21.69 | 15.47 | 0.00856772 | 43569.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.37263187 | 6.70 | 15.03 | 8.33 | 0.000 | 13030.72 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856772 | 21.11 | 0.00856772 | 54.1788 | 11952.95 | 0.00 | 13223.27 | 13223.27 | 1.40918958 | 21.69 | 15.62 | 0.00856772 | 43569.2 | 12.50 | 12.04 | 0.00856772 | 34185.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5067.063 | 5067.063 | 0.221619 | 0.00004433 | 144.805 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.187195 | 1.40918958 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.2877 | 1.313590 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5067.06 | 5067.06 | 1.0000 | 0.26305975 | 0.221619 | 21.11 | 14.26 | 0.00746754 | 40181.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04432436 | 60.00 | 32.22 | 27.78 | 0.000 | 5067.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746754 | 21.11 | 0.00746754 | 47.3051 | 5067.17 | 0.00 | 5462.41 | 5462.41 | 0.26305975 | 16.60 | 12.63 | 0.00746754 | 35586.7 | 36.98 | 19.87 | 0.00746754 | 56351.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11837.817 | -999.000 | 1.076549 | 0.00033855 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7793 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.076549 | 1.27785392 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 1.5668 | 1.566771 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 11837.82 | 11628.97 | 1.0000 | 1.27785392 | 1.076549 | 21.69 | 15.48 | 0.00857436 | 43586.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.33851922 | 6.70 | 15.03 | 8.33 | 0.000 | 11837.82 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00857436 | 21.11 | 0.00857436 | 54.2203 | 10838.93 | 0.00 | 12012.44 | 12012.44 | 1.27785392 | 21.69 | 15.62 | 0.00857436 | 43586.0 | 12.48 | 12.04 | 0.00857436 | 34185.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5070.306 | 5070.306 | 0.221761 | 0.00004436 | 144.898 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.076549 | 1.27785392 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.2885 | 1.314431 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5070.31 | 5070.31 | 1.0000 | 0.26322814 | 0.221761 | 21.11 | 14.27 | 0.00746788 | 40182.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04435273 | 60.00 | 32.22 | 27.78 | 0.000 | 5070.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746788 | 21.11 | 0.00746788 | 47.3073 | 5070.42 | 0.00 | 5465.91 | 5465.91 | 0.26322814 | 16.60 | 12.63 | 0.00746788 | 35587.5 | 36.98 | 19.87 | 0.00746788 | 56352.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 90288.607 | -999.000 | 8.371320 | 0.00258219 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6492 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.371320 | 9.93667970 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 11.9502 | 11.949972 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 90288.61 | 90193.65 | 1.0000 | 9.93667970 | 8.371320 | 21.69 | 15.42 | 0.00850436 | 43408.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 2.58193110 | 6.70 | 15.03 | 8.33 | 0.000 | 90288.61 | 29.14 | 0.00882108 | 18.26 | 0.00000000 | 0.0000 | 21.11 | 0.00850436 | 21.11 | 0.00850436 | 53.7823 | 84288.20 | 0.00 | 91630.04 | 91630.04 | 9.93667970 | 21.69 | 15.56 | 0.00850436 | 43408.6 | 12.66 | 12.05 | 0.00850436 | 34187.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29097.596 | 29097.596 | 1.272671 | 0.00025456 | 831.528 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.371320 | 9.93667970 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 7.3945 | 7.543288 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29097.60 | 29097.60 | 1.0000 | 1.51064918 | 1.272671 | 21.11 | 14.30 | 0.00750462 | 40276.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.25453250 | 60.00 | 32.22 | 27.78 | 0.000 | 29097.60 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00750462 | 21.11 | 0.00750462 | 47.5362 | 29097.91 | 0.00 | 31368.09 | 31368.09 | 1.51064918 | 16.60 | 12.67 | 0.00750462 | 35680.5 | 36.98 | 19.90 | 0.00750462 | 56445.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64953.351 | -999.000 | 5.627980 | 0.00185762 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1156 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.627980 | 6.68036098 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 8.5969 | 8.596774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 64953.35 | 61181.80 | 1.0000 | 6.68036098 | 5.627980 | 21.69 | 15.64 | 0.00875524 | 44045.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 1.85743343 | 6.70 | 15.03 | 8.33 | 0.000 | 64953.35 | 29.40 | 0.00882150 | 18.34 | 0.00000000 | 0.0000 | 21.11 | 0.00875524 | 21.11 | 0.00875524 | 55.3491 | 56661.98 | 0.00 | 65892.06 | 64547.78 | 6.68036098 | 21.69 | 15.78 | 0.00875524 | 44045.2 | 12.23 | 12.04 | 0.00867551 | 34181.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29172.705 | 29172.705 | 1.275956 | 0.00025522 | 833.674 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.627980 | 6.68036098 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 7.4136 | 7.562759 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29172.70 | 29172.70 | 1.0000 | 1.51454856 | 1.275956 | 21.11 | 14.30 | 0.00750566 | 40278.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.25518951 | 60.00 | 32.22 | 27.78 | 0.000 | 29172.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00750566 | 21.11 | 0.00750566 | 47.5426 | 29173.02 | 0.00 | 31449.06 | 31449.06 | 1.51454856 | 16.60 | 12.67 | 0.00750566 | 35683.2 | 36.98 | 19.90 | 0.00750566 | 56447.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11738.984 | -999.000 | 1.067286 | 0.00033573 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7811 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.067286 | 1.26685888 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 1.5537 | 1.553690 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 11738.98 | 11529.32 | 1.0000 | 1.26685888 | 1.067286 | 21.69 | 15.48 | 0.00857530 | 43588.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.33569295 | 6.70 | 15.03 | 8.33 | 0.000 | 11738.98 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00857530 | 21.11 | 0.00857530 | 54.2261 | 10745.68 | 0.00 | 11912.11 | 11912.11 | 1.26685888 | 21.69 | 15.62 | 0.00857530 | 43588.4 | 12.48 | 12.04 | 0.00857530 | 34185.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5074.163 | 5074.163 | 0.221930 | 0.00004439 | 145.008 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.067286 | 1.26685888 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.2895 | 1.315431 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5074.16 | 5074.16 | 1.0000 | 0.26342835 | 0.221930 | 21.11 | 14.27 | 0.00746821 | 40183.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04438646 | 60.00 | 32.22 | 27.78 | 0.000 | 5074.16 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746821 | 21.11 | 0.00746821 | 47.3093 | 5074.27 | 0.00 | 5470.07 | 5470.07 | 0.26342835 | 16.60 | 12.63 | 0.00746821 | 35588.4 | 36.98 | 19.87 | 0.00746821 | 56353.3 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10722.993 | -999.000 | 0.973021 | 0.00030667 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7943 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.973021 | 1.15496753 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 1.4192 | 1.419221 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | Sensible | 10722.99 | 10513.77 | 1.0000 | 1.15496753 | 0.973021 | 21.69 | 15.49 | 0.00858240 | 43606.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.30663922 | 6.70 | 15.03 | 8.33 | 0.000 | 10722.99 | 23.68 | 0.00881240 | 16.40 | 0.00000000 | 0.0000 | 21.11 | 0.00858240 | 21.11 | 0.00858240 | 54.2704 | 9796.59 | 0.00 | 10880.85 | 10880.85 | 1.15496753 | 21.69 | 15.63 | 0.00858240 | 43606.4 | 12.46 | 12.04 | 0.00858240 | 34185.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5077.405 | 5077.405 | 0.222071 | 0.00004442 | 145.101 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.973021 | 1.15496753 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.2903 | 1.316271 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5077.41 | 5077.41 | 1.0000 | 0.26359669 | 0.222071 | 21.11 | 14.27 | 0.00746855 | 40184.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04441483 | 60.00 | 32.22 | 27.78 | 0.000 | 5077.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746855 | 21.11 | 0.00746855 | 47.3115 | 5077.52 | 0.00 | 5473.56 | 5473.56 | 0.26359669 | 16.60 | 12.63 | 0.00746855 | 35589.2 | 36.98 | 19.87 | 0.00746855 | 56354.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12381.155 | 12381.155 | 0.826437 | 0.00010832 | 286.370 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 3.1464 | 3.209702 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12381.15 | 12381.15 | 1.0000 | 0.98097307 | 0.826437 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10830469 | 60.00 | 32.22 | 27.78 | 0.000 | 12381.15 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00758392 | 21.00 | 0.00758392 | 48.3605 | 8083.18 | 0.00 | 12447.44 | 12447.44 | 0.98097307 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.04 | 17.72 | 0.00800000 | 49623.6 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3394.048 | -999.000 | 0.309453 | 0.00009707 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7619 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.309453 | 0.36731727 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 0.4492 | 0.449213 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3394.05 | 3341.58 | 1.0000 | 0.36731727 | 0.309453 | 21.69 | 15.47 | 0.00856502 | 43562.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.09705763 | 6.70 | 15.03 | 8.33 | 0.000 | 3394.05 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856502 | 21.11 | 0.00856502 | 54.1620 | 3115.64 | 0.00 | 3444.24 | 3444.24 | 0.36731727 | 21.69 | 15.61 | 0.00856502 | 43562.3 | 12.51 | 12.04 | 0.00856502 | 34185.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1531.894 | 1531.894 | 0.067001 | 0.00001340 | 43.776 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.309453 | 0.36731727 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.3893 | 0.397130 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1531.89 | 1531.89 | 1.0000 | 0.07952926 | 0.067001 | 21.11 | 14.34 | 0.00755184 | 40395.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01340031 | 60.00 | 32.22 | 27.78 | 0.000 | 1531.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755184 | 21.11 | 0.00755184 | 47.8327 | 1531.93 | 0.00 | 1651.42 | 1651.42 | 0.07952926 | 16.60 | 12.71 | 0.00755184 | 35800.1 | 36.98 | 19.93 | 0.00755184 | 56565.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3061.007 | -999.000 | 0.278558 | 0.00008754 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7748 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.278558 | 0.33064545 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 0.4051 | 0.405134 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 3061.01 | 3008.73 | 1.0000 | 0.33064545 | 0.278558 | 21.69 | 15.48 | 0.00857194 | 43579.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.08753386 | 6.70 | 15.03 | 8.33 | 0.000 | 3061.01 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00857194 | 21.11 | 0.00857194 | 54.2052 | 2804.58 | 0.00 | 3106.19 | 3106.19 | 0.33064545 | 21.69 | 15.62 | 0.00857194 | 43579.9 | 12.49 | 12.04 | 0.00857194 | 34185.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1533.538 | 1533.538 | 0.067073 | 0.00001342 | 43.823 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.278558 | 0.33064545 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 0.3897 | 0.397556 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1533.54 | 1533.54 | 1.0000 | 0.07961457 | 0.067073 | 21.11 | 14.34 | 0.00755231 | 40396.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01341469 | 60.00 | 32.22 | 27.78 | 0.000 | 1533.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755231 | 21.11 | 0.00755231 | 47.8357 | 1533.57 | 0.00 | 1653.19 | 1653.19 | 0.07961457 | 16.60 | 12.71 | 0.00755231 | 35801.3 | 36.98 | 19.94 | 0.00755231 | 56566.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18760.530 | -999.000 | 1.692810 | 0.00053654 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8327 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.692810 | 2.00934987 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 2.4831 | 2.483013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 18760.53 | 18304.78 | 1.0000 | 2.00934987 | 1.692810 | 21.69 | 15.50 | 0.00860309 | 43658.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.53648403 | 6.70 | 15.03 | 8.33 | 0.000 | 18760.53 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00860309 | 21.11 | 0.00860309 | 54.4001 | 17043.20 | 0.00 | 19035.30 | 19035.30 | 2.00934987 | 21.69 | 15.65 | 0.00860309 | 43658.8 | 12.41 | 12.04 | 0.00860309 | 34185.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7348.196 | 7348.196 | 0.321391 | 0.00006429 | 209.982 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.692810 | 2.00934987 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.8674 | 1.904953 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7348.20 | 7348.20 | 1.0000 | 0.38148873 | 0.321391 | 21.11 | 14.36 | 0.00756832 | 40437.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06427866 | 60.00 | 32.22 | 27.78 | 0.000 | 7348.20 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756832 | 21.11 | 0.00756832 | 47.9355 | 7348.32 | 0.00 | 7921.55 | 7921.55 | 0.38148873 | 16.60 | 12.73 | 0.00756832 | 35841.8 | 36.98 | 19.95 | 0.00756832 | 56606.6 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10697.574 | 10697.574 | 1.085833 | 0.00009359 | 233.966 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 2.7185 | 2.773249 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10697.57 | 10697.57 | 1.0000 | 1.28887344 | 1.085833 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09357749 | 60.00 | 32.22 | 27.78 | 0.000 | 10697.57 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00765874 | 21.00 | 0.00765874 | 48.8321 | 5049.98 | 0.00 | 10756.80 | 10756.80 | 1.28887344 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.78 | 16.24 | 0.00800000 | 45280.6 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11071.833 | 11071.833 | 1.137266 | 0.00009686 | 241.854 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 2.8136 | 2.870272 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 11071.83 | 11071.83 | 1.0000 | 1.34992411 | 1.137266 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09685135 | 60.00 | 32.22 | 27.78 | 0.000 | 11071.83 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766537 | 21.00 | 0.00766537 | 48.8748 | 5157.07 | 0.00 | 11133.15 | 11133.15 | 1.34992411 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.69 | 16.20 | 0.00800000 | 45182.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7373.352 | 7373.352 | 1.164115 | 0.00006451 | 155.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.8738 | 1.911475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7373.35 | 7373.35 | 1.0000 | 1.38179425 | 1.164115 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06449872 | 60.00 | 32.22 | 27.78 | 0.000 | 7373.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.22 | 0.00556339 | 21.00 | 0.00556339 | 35.5983 | 1346.71 | 0.00 | 7414.63 | 7414.63 | 1.38179425 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.86 | 15.17 | 0.00800000 | 42300.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7433.498 | 7433.498 | 0.413201 | 0.00006503 | 178.006 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 1.8890 | 1.927067 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 7433.50 | 7433.50 | 1.0000 | 0.49046547 | 0.413201 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06502485 | 60.00 | 32.22 | 27.78 | 0.000 | 7433.50 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771122 | 21.00 | 0.00771122 | 49.1630 | 5284.24 | 0.00 | 7472.40 | 7472.40 | 0.49046547 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.54 | 18.55 | 0.00800000 | 52170.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 482309.223 | -999.000 | 22.636407 | 0.01379398 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9521 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.636407 | 26.86920611 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 63.8363 | 63.836286 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 482309.22 | 432768.57 | 1.0000 | 26.86920611 | 22.636407 | 26.78 | 17.78 | 0.00920523 | 50387.2 | 10.95 | 10.95 | 0.00850000 | 32437.0 | 13.79257559 | 6.70 | 15.03 | 8.33 | 50720.007 | 431589.22 | 29.40 | 0.00882150 | 18.34 | 11.66146000 | 51.5164 | 23.99 | 0.00961325 | 23.99 | 0.00956952 | 50.7147 | 306806.65 | 0.00 | 487688.36 | 422944.65 | 26.86920611 | 26.78 | 17.94 | 0.00920523 | 50387.2 | 11.37 | 11.25 | 0.00824983 | 32236.8 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 169288.449 | 169288.449 | 6.790922 | 0.00148101 | 2890.131 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.636407 | 26.86920611 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 43.0207 | 43.886493 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 169288.45 | 169288.45 | 1.0000 | 8.06076183 | 6.790922 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 1.48085812 | 60.00 | 32.22 | 27.78 | 0.000 | 169288.45 | -4.20 | 0.00269032 | -4.20 | 11.66146000 | 171.7213 | 18.50 | 0.00688787 | 21.20 | 0.00649290 | 40.9699 | 51075.11 | 0.00 | 155961.81 | 155961.81 | 8.06076183 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 21.60616871 | 15.03 | 6.70 | 8.33 | 755540.86 | 6.0153 | 6.015272 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.29966980 | 6.70 | 15.03 | 8.33 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00860364 | 21.11 | 0.00860625 | 54.4188 | 194853.19 | 0.00 | 45917.97 | 43441.59 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 11.93 | 11.66 | 0.00841841 | 33228.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 3.37429131 | 54.44 | 82.22 | 27.78 | 393504.78 | 3.8985 | 3.977006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.13419576 | 60.00 | 32.22 | 27.78 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00750352 | 21.11 | 0.00750543 | 47.5412 | 88974.12 | 0.00 | 14133.30 | 14133.30 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.64 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 57.67 | 7630.33 | 0.00 |
RETAIL_1_FLR_1 | 996.33 | 8063.00 | 578.83 |
RETAIL_2_FLR_1 | 351.17 | 7717.50 | 0.00 |
MECH_FLR_1 | 64.50 | 8646.17 | 62.33 |
STORAGE_FLR_1 | 130.67 | 8739.50 | 130.67 |
LAUNDRY_FLR_1 | 7270.67 | 3247.33 | 2573.50 |
CAFE_FLR_1 | 1093.67 | 6983.33 | 45.17 |
LOBBY_FLR_1 | 972.67 | 6645.50 | 29.00 |
ROOM_1_FLR_3 | 1500.83 | 8447.17 | 1465.50 |
ROOM_2_FLR_3 | 2310.67 | 8193.50 | 2027.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 439.00 | 8748.17 | 438.83 |
ROOM_5_FLR_3 | 1459.50 | 8450.33 | 1456.67 |
ROOM_6_FLR_3 | 2046.17 | 8427.17 | 1970.17 |
CORRIDOR_FLR_3 | 30.33 | 8755.67 | 30.33 |
ROOM_1_FLR_6 | 2256.50 | 8341.00 | 2169.83 |
ROOM_2_FLR_6 | 3057.83 | 8104.33 | 2723.83 |
ROOM_3_MULT9_FLR_6 | 920.50 | 8237.67 | 848.17 |
BANQUET_FLR_6 | 4384.33 | 1795.83 | 40.00 |
DINING_FLR_6 | 5822.83 | 819.83 | 21.83 |
KITCHEN_FLR_6 | 8493.17 | 6238.83 | 6216.00 |
CORRIDOR_FLR_6 | 173.17 | 8365.67 | 57.83 |
Facility | 8759.00 | 8760.00 | 7192.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 7.83 | 3.00 | 7.83 | 3.00 |
ROOM_2_FLR_3 | 14.67 | 5.33 | 14.67 | 5.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.17 | 9.83 | 0.17 | 9.83 |
ROOM_5_FLR_3 | 9.00 | 0.00 | 9.00 | 0.00 |
ROOM_6_FLR_3 | 16.83 | 6.67 | 16.83 | 6.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 6.33 | 6.00 | 6.33 | 6.00 |
ROOM_2_FLR_6 | 13.83 | 12.00 | 13.83 | 12.00 |
ROOM_3_MULT9_FLR_6 | 2.50 | 1.83 | 2.50 | 1.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 20.33 | 26.17 | 20.33 | 26.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.999 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.138 | 0.138 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.416 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.506 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.516 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.306 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.453 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.879 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.179 | 0.000 | 0.042 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.179 | 0.000 | 0.041 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.079 | 0.000 | 0.074 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.179 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.179 | 0.000 | 0.048 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.636 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.179 | 0.000 | 0.049 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.179 | 0.000 | 0.043 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.146 | 0.000 | 0.079 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.730 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.157 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.025 | 0.149 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.201 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.964 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.036 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.364 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.491 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.502 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.368 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.296 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.807 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.617 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.830 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.017 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.212 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.166 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41437960.00 | 0.00 | 41437960.00 | 0.00 | 41437960.00 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 7214948.05 | 0.00 | 7214948.05 | 316459.92 | 7531407.96 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3752300.31 | 0.00 | 3752300.31 | 122153.93 | 3874454.24 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2845407.29 | 0.00 | 2845407.29 | 288699.32 | 3134106.60 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1675917.03 | 0.00 | 1675917.03 | 166563.60 | 1842480.64 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 62000264.03 | 0.00 | 62000264.03 | 394204.17 | 62394468.20 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28717253.83 | 0.00 | 28717253.83 | 699552.56 | 29416806.39 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83764892.71 | 0.00 | 83764892.71 | 1998781.45 | 85763674.16 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 43565.36 | 1503722.08 | 183682.98 | 1687405.06 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 41999.94 | 1501985.57 | 183668.97 | 1685654.54 | 1946647.51 | 2190.00 | 6114.67 | 455.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 64.43 | 1099976.40 | 51249.61 | 1151226.02 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 47963.90 | 19851793.19 | 51263.63 | 19903056.82 | 26405105.73 | 2190.00 | 6028.29 | 541.71 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 43525.59 | 1503682.30 | 183682.98 | 1687365.29 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 48675.12 | 1508660.76 | 183668.97 | 1692329.73 | 1946647.51 | 2190.00 | 6019.08 | 550.92 | 0.00 |
CORRIDOR_FLR_3 | 26062516.34 | 0.00 | 26062516.34 | 222109.68 | 26284626.02 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 50855.51 | 415894.68 | 183721.42 | 599616.11 | 486718.90 | 2074.12 | 6019.41 | 666.47 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 43712.65 | 408709.06 | 183707.41 | 592416.47 | 486661.88 | 2103.72 | 6156.97 | 499.31 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 50780.08 | 2395970.39 | 93998.31 | 2489968.70 | 3126920.42 | 2190.00 | 6017.83 | 552.17 | 0.00 |
BANQUET_FLR_6 | 40933227.72 | 0.00 | 40933227.72 | 448601.54 | 41381829.27 | 37458366.31 | 3811.17 | 181.55 | 4767.28 | 0.00 |
DINING_FLR_6 | 44626789.29 | 0.00 | 44626789.29 | 448601.54 | 45075390.84 | 37458366.31 | 2570.04 | 195.21 | 5994.75 | 0.00 |
KITCHEN_FLR_6 | 59399981.77 | 0.00 | 59399981.77 | 401602.39 | 59801584.15 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13035067.94 | 0.00 | 13035067.94 | 393066.01 | 13428133.95 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4912805.92 | 0.21E+10 | 18509960.64 | 0.22E+10 | 0.43E+10 | 8760.00 | 6667.73 | 8760.00 | 365.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3140 | 0.0000 | 1.3140 | 0.0000 | 1.3140 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2288 | 0.0000 | 0.2288 | 0.0100 | 0.2388 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1190 | 0.0000 | 0.1190 | 0.0039 | 0.1229 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0902 | 0.0000 | 0.0902 | 0.0092 | 0.0994 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0531 | 0.0000 | 0.0531 | 0.0053 | 0.0584 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 1.9660 | 0.0000 | 1.9660 | 0.0125 | 1.9785 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9106 | 0.0000 | 0.9106 | 0.0222 | 0.9328 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6562 | 0.0000 | 2.6562 | 0.0634 | 2.7195 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0058 | 0.0535 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0058 | 0.0535 | 0.0617 | 2190.00 | 6114.67 | 455.33 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0015 | 0.6295 | 0.0016 | 0.6311 | 0.8373 | 2190.00 | 6028.29 | 541.71 |
ROOM_5_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0058 | 0.0535 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0058 | 0.0537 | 0.0617 | 2190.00 | 6019.08 | 550.92 |
CORRIDOR_FLR_3 | 0.8264 | 0.0000 | 0.8264 | 0.0070 | 0.8335 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0016 | 0.0132 | 0.0058 | 0.0190 | 0.0154 | 2074.12 | 6019.41 | 666.47 |
ROOM_2_FLR_6 | 0.0116 | 0.0014 | 0.0130 | 0.0058 | 0.0188 | 0.0154 | 2103.72 | 6156.97 | 499.31 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0016 | 0.0760 | 0.0030 | 0.0790 | 0.0992 | 2190.00 | 6017.83 | 552.17 |
BANQUET_FLR_6 | 1.2980 | 0.0000 | 1.2980 | 0.0142 | 1.3122 | 1.1878 | 3811.17 | 181.55 | 4767.28 |
DINING_FLR_6 | 1.4151 | 0.0000 | 1.4151 | 0.0142 | 1.4293 | 1.1878 | 2570.04 | 195.21 | 5994.75 |
KITCHEN_FLR_6 | 1.8836 | 0.0000 | 1.8836 | 0.0127 | 1.8963 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4133 | 0.0000 | 0.4133 | 0.0125 | 0.4258 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.8130 | 0.1556 | 64.9686 | 0.4634 | 65.4321 | 73.9670 | 8760.00 | 6667.73 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 42013749.02 | 371142.57 | 42384891.60 | 64690340.46 | 8754.17 | 4.95 | 0.88 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.5620 | 0.0000 | 18.5620 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3322 | 0.0118 | 1.3440 | 2.0513 | 8754.17 | 4.95 | 0.88 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 5339.78 | 0.00 | 0.00 | 0.00 | 3420.22 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.7207 | 0.0000 | 0.0000 | 0.0000 | 18.3196 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
Electricity:Building | 2448.13 | 31038.54 | 01-JUL-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.03 | 30897.39 | 01-JUL-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.58 | 293.96 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.24 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.24 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.17 | 3068.93 | 01-JUL-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 957.52 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 957.52 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.86 | 2448.50 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.86 | 2448.50 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.95 | 1115.47 | 11-FEB-23:30 | 3259.14 | 29-AUG-06:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 634.64 | 2598.56 | 26-APR-03:00 | 146520.09 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.46 | 0.00 | 01-JAN-11:10 | 1890.96 | 13-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.40 | 974.29 | 19-FEB-04:10 | 1201.93 | 30-AUG-13:30 |
Fans:Electricity | 496.07 | 11620.86 | 07-JAN-08:10 | 31040.20 | 24-AUG-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 638.66 | 12436.86 | 22-JAN-15:00 | 40655.05 | 10-AUG-20:30 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 17-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
ElectricityPurchased:Plant | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
Cogeneration:ElectricityPurchased | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
General:Cogeneration:ElectricityPurchased | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
ElectricityNet:Plant | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
Cogeneration:ElectricityNet | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
General:Cogeneration:ElectricityNet | 4533.95 | 70925.25 | 13-APR-02:40 | 354250.08 | 10-AUG-19:30 |
General:Fans:Electricity | 496.07 | 11620.86 | 07-JAN-08:10 | 31040.20 | 24-AUG-22:00 |
ExteriorLights:Electricity | 193.50 | 0.00 | 01-JAN-08:10 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.50 | 0.00 | 01-JAN-08:10 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 120.81 | 0.00 | 01-JAN-08:40 | 9938.94 | 22-JUN-16:30 |
General:HeatRecovery:Electricity | 120.81 | 0.00 | 01-JAN-08:40 | 9938.94 | 22-JUN-16:30 |
WaterSystems:Electricity | 90.75 | 1086.58 | 17-JUN-00:20 | 4738.73 | 04-DEC-19:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.58 | 17-JUN-00:20 | 4738.73 | 04-DEC-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 426.72 | 0.00 | 01-JAN-00:10 | 136223.38 | 10-AUG-18:10 |
General:Cooling:Electricity | 426.72 | 0.00 | 01-JAN-00:10 | 136223.38 | 10-AUG-18:10 |
Pumps:Electricity | 62.32 | 50.85 | 05-JUN-14:10 | 3400.93 | 10-AUG-18:10 |
General:Pumps:Electricity | 62.32 | 50.85 | 05-JUN-14:10 | 3400.93 | 10-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 27.56 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6355.51 | 29270.80 | 06-MAY-02:00 | 566943.26 | 22-MAR-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4566.67 | 15908.90 | 29-APR-15:10 | 462694.94 | 22-MAR-18:00 |
WaterSystems:NaturalGas | 3155.82 | 15908.90 | 05-FEB-16:10 | 283730.80 | 10-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3155.82 | 15908.90 | 05-FEB-16:10 | 283730.80 | 10-FEB-21:40 |
Heating:NaturalGas | 1410.85 | 0.00 | 27-FEB-11:20 | 213393.23 | 11-NOV-11:50 |
Boiler:Heating:NaturalGas | 1410.85 | 0.00 | 27-FEB-11:20 | 213393.23 | 11-NOV-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1267.58 | 0.00 | 01-JAN-00:10 | 447484.45 | 10-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 1267.58 | 0.00 | 01-JAN-00:10 | 447484.45 | 10-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1267.58 | 0.00 | 01-JAN-00:10 | 447484.45 | 10-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 28-JUN-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 28-JUN-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13841.23 | 131634.91 | 09-MAR-14:20 | 1927366.55 | 10-AUG-18:10 |
EnergyTransfer:Building | 4682.33 | 79501.61 | 26-DEC-11:10 | 337499.21 | 10-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 712.28 | 11091.78 | 19-FEB-04:00 | 36152.83 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 183.38 | 4021.80 | 11-FEB-23:20 | 10344.88 | 29-AUG-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.69 | 2010.90 | 11-FEB-23:20 | 5172.44 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer | 91.69 | 2010.90 | 11-FEB-23:20 | 5172.44 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.69 | 2010.90 | 11-FEB-23:20 | 5172.44 | 29-AUG-06:50 |
EnergyTransfer:Plant | 4841.95 | 17264.96 | 26-APR-02:50 | 1070633.98 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.08 | 1872.86 | 19-FEB-04:10 | 2555.78 | 30-AUG-13:30 |
EnergyTransfer:Zone:BASEMENT | 397.33 | 10501.68 | 23-APR-15:00 | 18898.63 | 06-OCT-21:00 |
Heating:EnergyTransfer | 96.86 | 0.00 | 01-JAN-09:00 | 54911.41 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 96.86 | 0.00 | 01-JAN-09:00 | 54911.41 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4493.78 | 71096.39 | 26-DEC-15:00 | 333888.60 | 10-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 397.33 | 10501.68 | 23-APR-15:00 | 18898.63 | 06-OCT-21:00 |
General:Cooling:EnergyTransfer | 4493.78 | 71096.39 | 26-DEC-15:00 | 333888.60 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 397.33 | 10501.68 | 23-APR-15:00 | 18898.63 | 06-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.71 | 0.03 | 14-JAN-23:10 | 3966.63 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.45 | 0.00 | 01-JAN-00:10 | 801.01 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.45 | 0.00 | 01-JAN-00:10 | 801.01 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.25 | 0.00 | 01-JAN-00:40 | 3966.63 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.25 | 0.00 | 01-JAN-00:40 | 3966.63 | 04-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.25 | 340.43 | 16-JAN-16:00 | 2006.71 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.25 | 340.43 | 16-JAN-16:00 | 2006.71 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.25 | 340.43 | 16-JAN-16:00 | 2006.71 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.52 | 0.08 | 15-JAN-11:10 | 1281.75 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 200.07 | 16-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 200.07 | 16-JAN-16:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.50 | 0.00 | 07-JAN-04:40 | 1281.75 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.50 | 0.00 | 07-JAN-04:40 | 1281.75 | 10-AUG-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.91 | 0.00 | 15-DEC-17:30 | 663.86 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 218.20 | 16-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 218.20 | 16-JAN-17:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.80 | 0.00 | 01-JAN-13:10 | 663.86 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.80 | 0.00 | 01-JAN-13:10 | 663.86 | 10-AUG-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.57 | 9540.84 | 18-FEB-06:00 | 38688.45 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.57 | 9540.84 | 18-FEB-06:00 | 38688.45 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.57 | 9540.84 | 18-FEB-06:00 | 38688.45 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 227.67 | 248.81 | 26-DEC-12:20 | 14026.07 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 227.67 | 248.81 | 26-DEC-12:20 | 14026.07 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 227.67 | 248.81 | 26-DEC-12:20 | 14026.07 | 04-OCT-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 750.54 | 9362.09 | 26-DEC-15:00 | 39335.80 | 10-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 750.54 | 9362.09 | 26-DEC-15:00 | 39335.80 | 10-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 750.54 | 9362.09 | 26-DEC-15:00 | 39335.80 | 10-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.82 | 0.00 | 01-JAN-08:10 | 11856.92 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.42 | 0.00 | 01-JAN-08:10 | 4720.69 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.42 | 0.00 | 01-JAN-08:10 | 4720.69 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 34.40 | 0.00 | 01-JAN-00:10 | 11856.92 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 34.40 | 0.00 | 01-JAN-00:10 | 11856.92 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 38.60 | 0.00 | 01-JAN-08:10 | 11975.48 | 14-JUL-16:40 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.35 | 0.00 | 01-JAN-08:10 | 4779.07 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.35 | 0.00 | 01-JAN-08:10 | 4779.07 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 22.25 | 0.00 | 01-JAN-00:10 | 11975.48 | 14-JUL-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 22.25 | 0.00 | 01-JAN-00:10 | 11975.48 | 14-JUL-16:40 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 206.85 | 0.00 | 01-JAN-00:10 | 52660.92 | 04-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 206.85 | 0.00 | 01-JAN-00:10 | 52660.92 | 04-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 206.85 | 0.00 | 01-JAN-00:10 | 52660.92 | 04-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 286.41 | 0.00 | 01-JAN-08:10 | 64467.23 | 11-JUL-20:50 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.72 | 0.00 | 01-JAN-00:10 | 25591.28 | 15-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.72 | 0.00 | 01-JAN-00:10 | 25591.28 | 15-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 272.70 | 0.00 | 01-JAN-02:00 | 64467.23 | 11-JUL-20:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 272.70 | 0.00 | 01-JAN-02:00 | 64467.23 | 11-JUL-20:50 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 46.08 | 0.00 | 01-JAN-08:10 | 10566.96 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.46 | 0.00 | 01-JAN-08:10 | 4720.10 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.46 | 0.00 | 01-JAN-08:10 | 4720.10 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 32.62 | 0.00 | 01-JAN-00:10 | 10566.96 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 32.62 | 0.00 | 01-JAN-00:10 | 10566.96 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 38.14 | 0.00 | 01-JAN-08:10 | 11652.30 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.30 | 0.00 | 01-JAN-08:10 | 4763.98 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.30 | 0.00 | 01-JAN-08:10 | 4763.98 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 21.84 | 0.00 | 01-JAN-00:10 | 11652.30 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 21.84 | 0.00 | 01-JAN-00:10 | 11652.30 | 24-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 173.87 | 6.31 | 26-DEC-07:20 | 10287.29 | 13-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.13 | 0.00 | 01-JAN-00:10 | 1718.90 | 26-DEC-14:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.13 | 0.00 | 01-JAN-00:10 | 1718.90 | 26-DEC-14:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 173.74 | 0.00 | 01-JAN-13:20 | 10287.29 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 173.74 | 0.00 | 01-JAN-13:20 | 10287.29 | 13-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.82 | 0.00 | 01-JAN-08:10 | 3284.74 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.28 | 0.00 | 01-JAN-08:10 | 1535.78 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.28 | 0.00 | 01-JAN-08:10 | 1535.78 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.54 | 0.00 | 01-JAN-00:10 | 3284.74 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.54 | 0.00 | 01-JAN-00:10 | 3284.74 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.79 | 0.00 | 01-JAN-08:10 | 3183.31 | 14-JUL-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.25 | 0.00 | 01-JAN-08:10 | 1510.11 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.25 | 0.00 | 01-JAN-08:10 | 1510.11 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.54 | 0.00 | 01-JAN-00:10 | 3183.31 | 14-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.54 | 0.00 | 01-JAN-00:10 | 3183.31 | 14-JUL-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 70.73 | 0.00 | 01-JAN-08:10 | 17210.86 | 14-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.33 | 0.00 | 01-JAN-08:10 | 7306.43 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.33 | 0.00 | 01-JAN-08:10 | 7306.43 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 59.39 | 0.00 | 01-JAN-00:10 | 17210.86 | 14-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 59.39 | 0.00 | 01-JAN-00:10 | 17210.86 | 14-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 420.20 | 8414.22 | 26-DEC-15:00 | 22244.75 | 24-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 420.20 | 8414.22 | 26-DEC-15:00 | 22244.75 | 24-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 420.20 | 8414.22 | 26-DEC-15:00 | 22244.75 | 24-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 463.25 | 9432.68 | 26-DEC-15:00 | 23504.29 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 463.25 | 9432.68 | 26-DEC-15:00 | 23504.29 | 24-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 463.25 | 9432.68 | 26-DEC-15:00 | 23504.29 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.59 | 8966.88 | 19-FEB-04:00 | 31060.90 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.59 | 8966.88 | 19-FEB-04:00 | 31060.90 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 88.00 | 0.95 | 15-JAN-15:50 | 6186.98 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 747.89 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 747.89 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 87.96 | 0.00 | 06-JAN-07:10 | 6186.98 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 87.96 | 0.00 | 06-JAN-07:10 | 6186.98 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1699.30 | 9488.95 | 14-AUG-00:20 | 184341.56 | 03-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 764.24 | 9488.95 | 14-AUG-00:20 | 54601.72 | 10-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 764.24 | 9488.95 | 14-AUG-00:20 | 54601.72 | 10-FEB-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 764.24 | 9488.95 | 14-AUG-00:20 | 54601.72 | 10-FEB-07:30 |
EnergyTransfer:HVAC | 4316.95 | 483.65 | 27-FEB-11:20 | 527174.70 | 10-AUG-18:10 |
HeatingCoils:EnergyTransfer | 935.06 | 0.00 | 27-FEB-11:20 | 156307.64 | 16-DEC-16:10 |
PlantLoopHeatingDemand:HVAC | 935.06 | 0.00 | 27-FEB-11:20 | 156307.64 | 16-DEC-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 935.06 | 0.00 | 27-FEB-11:20 | 156307.64 | 16-DEC-16:10 |
CoolingCoils:EnergyTransfer | 1267.58 | 0.00 | 01-JAN-00:10 | 447484.45 | 10-AUG-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2099.87 | 0.00 | 01-JAN-08:40 | 371498.29 | 19-FEB-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 14.43 | 0.00 | 01-JAN-00:10 | 83485.22 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 764.24 | 9488.95 | 14-AUG-00:20 | 54601.72 | 10-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 764.24 | 9488.95 | 14-AUG-00:20 | 54601.72 | 10-FEB-07:30 |
Boilers:EnergyTransfer | 927.98 | 0.00 | 27-FEB-11:20 | 157377.17 | 16-DEC-16:10 |
Chillers:EnergyTransfer | 1315.66 | 0.00 | 01-JAN-00:10 | 450212.33 | 10-AUG-18:10 |
HeatRejection:EnergyTransfer | 1742.38 | 0.00 | 01-JAN-00:10 | 586435.71 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 1742.38 | 0.00 | 01-JAN-00:10 | 586435.71 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -397.329 | 0.000 | 0.000 | 139.535 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -46.605 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.453 | -36.255 | 0.000 | 0.000 | 15.910 | 7.307 | 10.186 | 20.687 | 0.000 | 0.030 | 0.000 | 0.000 | -9.975 | 0.000 | -3.960 | -4.383 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.251 | 0.000 | 0.000 | 17.148 | 8.462 | 11.795 | 0.000 | 0.000 | 0.012 | 0.000 | 0.000 | 0.000 | 0.000 | -1.682 | -3.483 |
MECH_FLR_1 | 0.000 | 0.000 | 0.020 | -20.497 | 0.000 | 0.000 | 3.765 | 8.366 | 12.471 | 0.000 | 0.000 | 0.030 | 0.000 | 0.000 | 0.000 | 0.000 | -3.785 | -0.371 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.107 | -10.800 | 0.000 | 0.000 | 2.928 | 3.079 | 3.598 | 0.000 | 0.000 | 0.018 | 3.217 | 0.000 | 0.000 | 0.000 | -2.148 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -588.572 | 0.000 | 0.000 | 11.253 | 3.975 | 658.131 | 0.000 | 0.000 | 0.043 | 0.000 | 0.000 | 0.000 | 0.000 | -5.707 | -79.123 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -227.671 | 0.000 | 0.000 | 198.076 | 14.244 | 14.341 | 57.412 | 0.000 | 0.061 | 0.000 | 0.000 | -29.903 | 0.000 | -9.382 | -17.178 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -750.540 | 0.000 | 0.000 | 565.831 | 110.169 | 148.998 | 75.484 | 0.000 | 0.184 | 0.000 | 0.000 | -41.485 | 0.000 | -28.210 | -80.432 |
ROOM_1_FLR_3 | 17.992 | -28.504 | 0.000 | -10.474 | 0.000 | 0.000 | 9.735 | 9.244 | 10.478 | 38.996 | 0.000 | 0.154 | 0.000 | 0.000 | -22.846 | 0.000 | -9.799 | -14.977 |
ROOM_2_FLR_3 | 21.272 | -16.230 | 0.000 | -10.944 | 0.000 | 0.000 | 9.613 | 9.243 | 10.477 | 26.968 | 0.000 | 0.094 | 0.000 | 0.000 | -23.454 | 0.000 | -10.301 | -16.739 |
ROOM_3_MULT19_FLR_3 | 0.000 | -193.125 | 0.000 | -13.724 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 226.874 | 0.000 | 0.066 | 0.010 | 0.000 | -162.539 | 0.000 | -65.956 | -96.977 |
ROOM_4_MULT19_FLR_3 | 43.349 | -156.867 | 0.000 | -145.452 | 0.000 | 0.000 | 183.469 | 110.415 | 195.050 | 64.973 | 0.000 | 0.754 | 0.000 | 0.000 | -130.405 | 0.000 | -65.872 | -99.413 |
ROOM_5_FLR_3 | 18.027 | -26.702 | 0.000 | -10.478 | 0.000 | 0.000 | 9.731 | 9.244 | 10.478 | 37.179 | 0.000 | 0.155 | 0.000 | 0.000 | -22.371 | 0.000 | -9.811 | -15.452 |
ROOM_6_FLR_3 | 21.257 | -16.001 | 0.000 | -10.798 | 0.000 | 0.000 | 9.661 | 9.243 | 10.477 | 25.138 | 0.000 | 0.097 | 0.000 | 0.000 | -22.765 | 0.000 | -10.235 | -16.074 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.130 | -173.737 | 0.000 | 0.000 | 120.612 | 91.336 | 0.000 | 35.126 | 0.000 | 0.095 | 0.000 | 0.000 | -29.406 | 0.000 | -11.462 | -32.694 |
ROOM_1_FLR_6 | 6.566 | -7.206 | 0.000 | -2.615 | 0.000 | 0.000 | 2.437 | 2.311 | 2.620 | 9.676 | 0.000 | 0.040 | 0.000 | 0.000 | -5.667 | 0.000 | -2.475 | -5.686 |
ROOM_2_FLR_6 | 7.591 | -4.134 | 0.000 | -2.750 | 0.000 | 0.000 | 2.400 | 2.311 | 2.619 | 6.673 | 0.000 | 0.023 | 0.000 | 0.000 | -5.831 | 0.000 | -2.598 | -6.304 |
ROOM_3_MULT9_FLR_6 | 17.148 | -48.296 | 0.000 | -16.911 | 0.000 | 0.000 | 21.837 | 13.076 | 23.098 | 53.078 | 0.000 | 0.247 | 0.000 | 0.000 | -26.726 | 0.000 | -12.340 | -24.210 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -420.206 | 0.000 | 0.000 | 316.155 | 31.006 | 175.857 | 6.316 | 0.000 | 0.029 | 0.000 | 0.000 | -18.245 | 0.000 | -6.934 | -83.979 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -463.248 | 0.000 | 0.000 | 314.999 | 31.006 | 175.857 | 6.106 | 0.000 | 0.029 | 0.000 | 0.000 | -18.818 | 0.000 | -6.993 | -38.938 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -620.577 | 0.000 | 0.000 | 28.328 | 12.972 | 550.372 | 17.567 | 0.000 | 0.026 | 29.776 | 0.000 | -12.217 | 0.000 | -6.248 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.041 | -87.962 | 0.000 | 0.000 | 31.865 | 24.166 | 0.000 | 17.108 | 0.000 | 0.030 | 33.238 | 0.000 | -13.366 | 0.000 | -5.121 | 0.000 |
Total Facility | 153.203 | -497.065 | 0.752 | -4053.791 | 0.000 | 0.000 | 2015.288 | 782.856 | 2365.005 | 725.360 | 0.000 | 2.215 | 66.243 | 0.000 | -596.018 | 0.000 | -281.019 | -683.018 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18898.83 | 0.00 | 0.00 | 5924.44 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7875.83 |
RETAIL_1_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -3966.19 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 6353.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -39.65 | -2917.06 |
RETAIL_2_FLR_1 | 10-AUG-20:44 | 0.00 | 0.00 | 0.00 | -2007.49 | 0.00 | 0.00 | 697.60 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.53 | -54.85 |
MECH_FLR_1 | 10-AUG-20:57 | 0.00 | 0.00 | 0.00 | -1281.78 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10.56 | -258.61 |
STORAGE_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -665.66 | 0.00 | 0.00 | 102.89 | 223.85 | 229.41 | 0.00 | 0.00 | 41.69 | 67.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38689.91 | 0.00 | 0.00 | 408.86 | 325.08 | 44299.38 | 0.00 | 0.00 | 22.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6366.15 |
CAFE_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -14024.50 | 0.00 | 0.00 | 1979.10 | 103.98 | 355.63 | 17818.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -87.64 | -6145.44 |
LOBBY_FLR_1 | 10-AUG-21:05 | 0.00 | 0.00 | 0.00 | -39351.94 | 0.00 | 0.00 | 26437.37 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.97 | 0.00 | -79.06 | -58.87 |
ROOM_1_FLR_3 | 14-MAY-18:01 | 0.00 | -15019.38 | 0.00 | -724.66 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 6185.89 | 0.00 | 0.00 | 8145.70 | 0.00 | -0.00 | 0.00 | -66.95 | 0.00 |
ROOM_2_FLR_3 | 21-MAY-17:41 | 0.00 | -15668.44 | 0.00 | 0.00 | 0.00 | 0.00 | 193.47 | 604.73 | 505.67 | 3976.24 | 0.00 | 0.00 | 10646.49 | 0.00 | -0.00 | 0.00 | -258.16 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:30 | 0.00 | -52661.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 77029.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -877.34 | -28222.77 |
ROOM_4_MULT19_FLR_3 | 14-MAY-21:51 | 0.00 | -75339.59 | 0.00 | -8128.97 | 0.00 | 0.00 | 6382.12 | 7223.75 | 6668.31 | 0.00 | 0.00 | 0.00 | 68633.42 | 0.00 | -4519.67 | 0.00 | -919.37 | 0.00 |
ROOM_5_FLR_3 | 14-MAY-18:01 | 0.00 | -13309.82 | 0.00 | -712.92 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 344.54 | 0.00 | 0.00 | 12251.81 | 0.00 | -0.00 | 0.00 | -53.00 | 0.00 |
ROOM_6_FLR_3 | 24-JUL-08:32 | 0.00 | -13644.10 | 0.00 | -1043.40 | 0.00 | 0.00 | 59.48 | 313.04 | 452.99 | 9324.40 | 0.00 | 0.00 | 4633.76 | 0.00 | -0.00 | 0.00 | -96.18 | 0.00 |
CORRIDOR_FLR_3 | 13-AUG-10:33 | 0.00 | 0.00 | 0.00 | -10313.40 | 0.00 | 0.00 | 1852.76 | 2489.76 | 0.00 | 7056.08 | 0.00 | 33.99 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1119.20 |
ROOM_1_FLR_6 | 14-MAY-18:01 | 0.00 | -3920.49 | 0.00 | -181.45 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 1531.52 | 0.00 | 0.00 | 2221.42 | 0.00 | -0.00 | 0.00 | -20.85 | 0.00 |
ROOM_2_FLR_6 | 25-APR-17:41 | 0.00 | -4065.11 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 | 119.17 | 126.42 | 1451.15 | 0.00 | 0.00 | 2392.83 | 0.00 | -0.00 | 0.00 | -72.83 | 0.00 |
ROOM_3_MULT9_FLR_6 | 25-MAR-15:01 | 0.00 | -21339.19 | 0.00 | -832.03 | 0.00 | 0.00 | 294.09 | 332.11 | 487.74 | 7017.21 | 0.00 | 0.00 | 14394.03 | 0.00 | -0.00 | 0.00 | -353.97 | 0.00 |
BANQUET_FLR_6 | 24-JUL-21:10 | 0.00 | 0.00 | 0.00 | -22245.89 | 0.00 | 0.00 | 15644.01 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.44 | 0.00 | -27.46 | -1893.14 |
DINING_FLR_6 | 24-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23505.64 | 0.00 | 0.00 | 15629.36 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -254.34 | 0.00 | -33.61 | -575.68 |
KITCHEN_FLR_6 | 13-AUG-10:40 | 0.00 | 0.00 | 0.00 | -31057.11 | 0.00 | 0.00 | 464.19 | 353.60 | 24259.91 | 3650.60 | 0.00 | 0.35 | 2328.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-15:03 | 0.00 | 0.00 | 0.00 | -6189.23 | 0.00 | 0.00 | 771.14 | 548.96 | 0.00 | 2449.18 | 0.00 | 87.60 | 2332.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -165358.16 | 0.00 | -202218.71 | 0.00 | 0.00 | 75133.89 | 53578.21 | 120482.43 | 47558.59 | 0.00 | 4355.24 | 66468.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 19-FEB-06:00 | 0.00 | 0.00 | 800.99 | 0.00 | 0.00 | 0.00 | 626.59 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1148.77 | 0.00 | -339.00 | -289.12 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-JAN-16:00 | 0.00 | 0.00 | 200.06 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -217.14 | -443.89 |
STORAGE_FLR_1 | 16-JAN-17:00 | 0.00 | 0.00 | 218.19 | 0.00 | 0.00 | 0.00 | 50.59 | 55.96 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -128.84 | -272.37 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 03-DEC-16:03 | 5733.00 | 413.60 | 0.00 | -413.60 | 0.00 | 0.00 | 138.67 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -299.28 | 0.00 | -285.45 | -5743.00 |
ROOM_2_FLR_3 | 26-MAR-15:03 | 5300.16 | 417.64 | 0.00 | -417.64 | 0.00 | 0.00 | 140.03 | 234.78 | 221.23 | 2858.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -295.92 | -8459.24 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:01 | 27580.70 | 4446.76 | 0.00 | -4446.76 | 0.00 | 0.00 | 2997.47 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8328.26 | 0.00 | -2665.83 | -26507.27 |
ROOM_5_FLR_3 | 12-FEB-16:03 | 5425.36 | 417.36 | 0.00 | -417.36 | 0.00 | 0.00 | 140.21 | 234.80 | 221.25 | 599.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -413.40 | -6207.56 |
ROOM_6_FLR_3 | 24-MAY-15:04 | 5299.98 | 425.95 | 0.00 | -425.95 | 0.00 | 0.00 | 235.28 | 199.20 | 200.16 | 1928.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -980.75 | -6882.75 |
CORRIDOR_FLR_3 | 26-DEC-14:40 | 0.00 | 0.00 | 1718.89 | 0.00 | 0.00 | 0.00 | 1385.83 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1719.98 | 0.00 | -677.96 | -2781.57 |
ROOM_1_FLR_6 | 26-DEC-16:13 | 1608.98 | 91.02 | 0.00 | -91.02 | 0.00 | 0.00 | 66.90 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -402.19 | 0.00 | -121.54 | -1252.00 |
ROOM_2_FLR_6 | 26-DEC-16:13 | 1571.42 | 89.95 | 0.00 | -89.95 | 0.00 | 0.00 | 67.15 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -398.94 | 0.00 | -121.12 | -1218.35 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:13 | 7841.92 | 591.43 | 0.00 | -591.43 | 0.00 | 0.00 | 600.52 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1896.87 | 0.00 | -561.50 | -6707.15 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-06:00 | 0.00 | 0.00 | 747.88 | 0.00 | 0.00 | 0.00 | 1283.35 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1510.84 | 0.00 | -422.73 | -536.82 |
Total Facility | 16-JAN-16:13 | -18420.13 | 84601.63 | 1975.63 | -84601.63 | 0.00 | 0.00 | 35540.32 | 16549.49 | 71286.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36361.21 | 0.00 | -13873.39 | -56696.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.7579 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.6364 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6520 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6520 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5474 | 2.5474 | 1.3042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4447 | 0.4447 | 0.2277 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2312 | 0.2312 | 0.1184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1762 | 0.1762 | 0.0902 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1038 | 0.1038 | 0.0531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2908 | 3.2908 | 1.6849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7714 | 1.7714 | 0.9070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1556 | 5.1556 | 2.6397 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6141 | 1.6141 | 0.8264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1208 | 2.1208 | 1.0858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2212 | 2.2212 | 1.1373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2737 | 2.2737 | 1.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8070 | 0.8070 | 0.4132 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.7579 | 22.6364 | 22.7579 | 11.6520 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3042 | 1.3042 | 1.3042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2277 | 0.2277 | 0.2277 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1184 | 0.1184 | 0.1184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0902 | 0.0902 | 0.0902 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0531 | 0.0531 | 0.0531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6849 | 1.6849 | 1.6849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9070 | 0.9070 | 0.9070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6397 | 2.6397 | 2.6397 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8264 | 0.8264 | 0.8264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0858 | 1.0858 | 1.0858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1373 | 1.1373 | 1.1373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1641 | 1.1641 | 1.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4132 | 0.4132 | 0.4132 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6520 | 11.6520 | 11.6520 | 11.6520 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 20.33 |
Number of hours cooling loads not met | 26.17 |
Number of hours not met | 46.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1410.85 | 213393.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 426.72 | 136223.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.86 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.50 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 496.07 | 31040.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 62.32 | 3400.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 120.81 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.73 | 3155.82 | 283730.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.46 | 1890.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.40 | 1201.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.12 | 4533.95 |
Natural Gas | 1788.84 | 6355.51 |
Additional | 0.00 | 0.00 |
Total | 3508.96 | 10889.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.00 |
Space Heating | 0.00 |
Space Cooling | 37.61 |
Fans (All) | 43.72 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 399.63 |
Subtotal | 399.63 |
Natural Gas [MJ/m2] | |
Space Heating | 124.36 |
Service Water Heating | 278.16 |
Miscellaneous (All) | 560.19 |
Subtotal | 560.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.19 |
Space Heating | 12.96 |
Space Cooling | 3.92 |
Fans (All) | 4.56 |
Service Water Heating | 29.81 |
Receptacle Equipment | 31.65 |
Miscellaneous | 9.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8705.83 | 54.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8541.17 | 218.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8659.33 | 100.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8541.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 218.83 | 0.00 | 0.00 | 0.00 |
Average | 8742.58 | 17.42 | 0.00 | 0.00 | 0.00 |
Sum | 192336.83 | 383.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4138.50 | 15.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4119.33 | 34.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 34.67 | 0.00 | 0.00 | 0.00 |
Average | 288884.77 | 2.28 | 0.00 | 0.00 | 0.00 |
Sum | 6355464.83 | 50.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8694.67 | 65.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8267.17 | 492.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8640.67 | 119.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8267.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 492.83 | 0.00 | 0.00 | 0.00 |
Average | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
Sum | 191913.17 | 806.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 708241.00 | 2176.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2106000.67 | 9428.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4126.00 | 28.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4098.00 | 56.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1236884.50 | 8830.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1241185.67 | 4529.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108220.00 | 49.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2106000.67 | 9428.33 | 0.00 | 0.00 | 0.00 |
Average | 287746.27 | 1140.78 | 0.00 | 0.00 | 0.00 |
Sum | 6330417.83 | 25097.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325255E+11 | 14283.64 | 11-JAN-21:00 | 11.10 | 10.22 | 0.773551E+10 | 4836.06 | 13-JAN-22:10 | 0.60 | 0.60 |
February | 0.288392E+11 | 14130.61 | 01-FEB-21:00 | 6.70 | 5.41 | 0.687625E+10 | 4777.97 | 01-FEB-22:10 | 6.60 | 5.31 |
March | 0.314351E+11 | 14162.32 | 25-MAR-10:33 | 8.87 | 1.80 | 0.750340E+10 | 4690.96 | 03-MAR-22:10 | 8.87 | 1.80 |
April | 0.304161E+11 | 14639.33 | 27-APR-18:10 | 25.55 | 15.86 | 0.716357E+10 | 4592.42 | 14-APR-21:10 | 25.55 | 15.86 |
May | 0.321452E+11 | 15088.79 | 14-MAY-10:33 | 20.03 | 12.68 | 0.746922E+10 | 4643.87 | 18-MAY-21:10 | 8.90 | 7.04 |
June | 0.321539E+11 | 15501.86 | 25-JUN-10:33 | 18.87 | 13.09 | 0.736175E+10 | 4725.66 | 23-JUN-22:10 | 18.87 | 13.09 |
July | 0.344029E+11 | 16105.61 | 30-JUL-10:33 | 23.33 | 16.24 | 0.773464E+10 | 4820.37 | 28-JUL-22:10 | 23.33 | 16.24 |
August | 0.353397E+11 | 16339.25 | 13-AUG-10:33 | 24.17 | 17.28 | 0.790188E+10 | 4837.10 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.347978E+11 | 17602.31 | 15-SEP-21:00 | 16.10 | 14.33 | 0.774410E+10 | 4837.09 | 11-SEP-22:10 | 16.10 | 14.33 |
October | 0.362065E+11 | 18898.63 | 06-OCT-21:00 | 12.80 | 10.62 | 0.807041E+10 | 4837.07 | 04-OCT-21:30 | 12.80 | 10.62 |
November | 0.348472E+11 | 18717.74 | 08-NOV-22:00 | 8.90 | 7.25 | 0.781391E+10 | 4837.03 | 16-NOV-22:19 | 5.20 | 4.52 |
December | 0.342186E+11 | 17623.89 | 01-DEC-22:00 | 5.00 | 4.72 | 0.795191E+10 | 4837.04 | 22-DEC-22:19 | 1.90 | 1.47 |
Annual Sum or Average | 0.397328E+12 | 0.913265E+11 | ||||||||
Minimum of Months | 0.288392E+11 | 14130.61 | 5.00 | 1.80 | 0.687625E+10 | 4592.42 | 0.60 | 0.60 | ||
Maximum of Months | 0.362065E+11 | 18898.63 | 25.55 | 17.28 | 0.807041E+10 | 4837.10 | 25.55 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765534E+09 | 2227.21 | 20-JAN-11:50 | 5.60 | 3.57 | 0.620620E+09 | 364.20 | 03-JAN-01:49 | 5.60 | 3.57 |
February | 0.153332E+10 | 2618.11 | 08-FEB-13:30 | 6.40 | 3.77 | 0.564745E+09 | 385.48 | 27-FEB-22:30 | 12.20 | 10.20 |
March | 0.250395E+10 | 3318.54 | 02-MAR-13:20 | 12.57 | 7.60 | 0.631893E+09 | 402.81 | 14-MAR-21:30 | 12.50 | 8.53 |
April | 0.326206E+10 | 3199.93 | 27-APR-13:05 | 26.10 | 16.37 | 0.617180E+09 | 434.66 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.390159E+10 | 3069.82 | 04-MAY-13:20 | 22.77 | 15.31 | 0.643411E+09 | 432.31 | 04-MAY-21:30 | 18.35 | 12.20 |
June | 0.418919E+10 | 2559.02 | 28-JUN-10:33 | 21.50 | 14.65 | 0.628302E+09 | 429.79 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.489318E+10 | 3044.11 | 31-JUL-13:20 | 27.57 | 18.47 | 0.670728E+09 | 452.17 | 24-JUL-21:30 | 27.57 | 18.47 |
August | 0.508921E+10 | 3869.38 | 24-AUG-13:10 | 28.93 | 19.36 | 0.685067E+09 | 465.85 | 10-AUG-21:19 | 28.93 | 19.36 |
September | 0.435999E+10 | 3957.64 | 14-SEP-13:15 | 23.17 | 17.52 | 0.641636E+09 | 449.94 | 12-SEP-21:30 | 23.17 | 17.52 |
October | 0.323226E+10 | 3966.63 | 04-OCT-12:50 | 20.60 | 11.27 | 0.636625E+09 | 430.86 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.152667E+10 | 3228.33 | 04-NOV-13:30 | 20.85 | 16.00 | 0.602262E+09 | 364.21 | 20-NOV-04:00 | 8.30 | 6.44 |
December | 0.997964E+09 | 2496.05 | 05-DEC-11:50 | 9.72 | 5.97 | 0.621999E+09 | 364.19 | 28-DEC-04:30 | 8.60 | 7.35 |
Annual Sum or Average | 0.362549E+11 | 0.756447E+10 | ||||||||
Minimum of Months | 0.765534E+09 | 2227.21 | 5.60 | 3.57 | 0.564745E+09 | 364.19 | 5.60 | 3.57 | ||
Maximum of Months | 0.508921E+10 | 3966.63 | 28.93 | 19.36 | 0.685067E+09 | 465.85 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224340E+10 | 1121.51 | 11-JAN-21:00 | 11.10 | 10.22 | 0.774145E+09 | 512.33 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.216729E+10 | 1234.10 | 27-FEB-21:00 | 12.20 | 10.06 | 0.720337E+09 | 545.43 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.258624E+10 | 1259.85 | 14-MAR-20:00 | 14.40 | 9.49 | 0.831392E+09 | 551.81 | 14-MAR-22:10 | 12.12 | 8.27 |
April | 0.266447E+10 | 1593.08 | 27-APR-21:00 | 17.20 | 11.44 | 0.827696E+09 | 569.55 | 26-APR-21:00 | 17.20 | 11.44 |
May | 0.289938E+10 | 1567.48 | 04-MAY-21:00 | 17.80 | 12.21 | 0.880612E+09 | 569.55 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.290939E+10 | 1647.44 | 28-JUN-21:00 | 16.70 | 13.67 | 0.868392E+09 | 569.55 | 27-JUN-22:10 | 16.70 | 13.67 |
July | 0.318499E+10 | 1853.62 | 24-JUL-21:00 | 22.80 | 16.50 | 0.917973E+09 | 569.55 | 18-JUL-22:10 | 22.80 | 16.50 |
August | 0.324475E+10 | 2007.45 | 10-AUG-20:44 | 23.43 | 17.10 | 0.925931E+09 | 569.55 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.294003E+10 | 1787.81 | 14-SEP-21:00 | 18.30 | 14.89 | 0.871882E+09 | 569.55 | 11-SEP-22:10 | 18.30 | 14.89 |
October | 0.273578E+10 | 1536.20 | 04-OCT-21:00 | 13.90 | 9.05 | 0.855205E+09 | 569.55 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.237849E+10 | 1246.96 | 04-NOV-18:10 | 15.00 | 13.34 | 0.779139E+09 | 532.91 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.229630E+10 | 1163.55 | 05-DEC-21:00 | 5.60 | 1.73 | 0.782896E+09 | 523.91 | 05-DEC-22:30 | 4.70 | 2.12 |
Annual Sum or Average | 0.322505E+11 | 0.100356E+11 | ||||||||
Minimum of Months | 0.216729E+10 | 1121.51 | 5.60 | 1.73 | 0.720337E+09 | 512.33 | 4.70 | 2.12 | ||
Maximum of Months | 0.324475E+10 | 2007.45 | 23.43 | 17.10 | 0.925931E+09 | 569.55 | 22.80 | 16.50 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.833753E+09 | 739.91 | 11-JAN-21:00 | 11.10 | 10.22 | 0.152462E+09 | 95.80 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.103017E+10 | 814.69 | 27-FEB-19:10 | 15.73 | 11.89 | 0.139357E+09 | 101.01 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.164854E+10 | 815.60 | 18-MAR-18:10 | 18.03 | 9.10 | 0.158265E+09 | 100.78 | 10-MAR-22:10 | 18.03 | 9.10 |
April | 0.179588E+10 | 987.66 | 27-APR-18:10 | 25.55 | 15.86 | 0.159415E+09 | 110.24 | 27-APR-21:19 | 16.27 | 11.36 |
May | 0.204014E+10 | 1041.98 | 06-MAY-10:33 | 20.93 | 16.16 | 0.174255E+09 | 113.83 | 05-MAY-21:19 | 20.93 | 16.16 |
June | 0.210660E+10 | 1070.11 | 28-JUN-18:10 | 25.40 | 16.48 | 0.175507E+09 | 116.96 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.231047E+10 | 1142.69 | 24-JUL-21:00 | 22.80 | 16.50 | 0.187746E+09 | 120.45 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.235511E+10 | 1281.76 | 10-AUG-20:57 | 23.00 | 16.96 | 0.190832E+09 | 120.45 | 10-AUG-21:10 | 22.92 | 16.74 |
September | 0.208585E+10 | 1073.56 | 14-SEP-10:33 | 19.43 | 16.41 | 0.174706E+09 | 117.63 | 14-SEP-21:19 | 17.93 | 14.75 |
October | 0.187827E+10 | 962.57 | 04-OCT-10:33 | 18.33 | 11.02 | 0.166759E+09 | 110.44 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.139787E+10 | 873.87 | 04-NOV-10:33 | 17.23 | 14.47 | 0.151481E+09 | 102.80 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 0.101481E+10 | 746.63 | 03-DEC-11:33 | 11.33 | 5.78 | 0.152675E+09 | 94.81 | 29-DEC-22:10 | 8.90 | 7.55 |
Annual Sum or Average | 0.204975E+11 | 0.198346E+10 | ||||||||
Minimum of Months | 0.833753E+09 | 739.91 | 11.10 | 5.78 | 0.139357E+09 | 94.81 | 8.12 | 7.00 | ||
Maximum of Months | 0.235511E+10 | 1281.76 | 25.55 | 16.96 | 0.190832E+09 | 120.45 | 22.92 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255535E+09 | 410.98 | 11-JAN-21:00 | 11.10 | 10.22 | 0.116731E+09 | 70.92 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.436630E+09 | 459.91 | 27-FEB-19:10 | 15.73 | 11.89 | 0.106110E+09 | 74.67 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.847963E+09 | 465.91 | 18-MAR-18:10 | 18.03 | 9.10 | 0.119201E+09 | 74.25 | 10-MAR-23:10 | 18.03 | 9.10 |
April | 0.100255E+10 | 568.20 | 27-APR-18:10 | 25.55 | 15.86 | 0.119450E+09 | 81.76 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.115845E+10 | 606.01 | 06-MAY-10:33 | 20.93 | 16.16 | 0.130349E+09 | 84.34 | 05-MAY-22:10 | 20.93 | 16.16 |
June | 0.119998E+10 | 616.99 | 28-JUN-10:33 | 21.50 | 14.65 | 0.131473E+09 | 86.66 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.131826E+10 | 655.78 | 24-JUL-18:10 | 28.72 | 17.86 | 0.140710E+09 | 89.99 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.134221E+10 | 665.66 | 10-AUG-18:10 | 30.57 | 19.31 | 0.143025E+09 | 91.24 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.118556E+10 | 620.76 | 14-SEP-10:33 | 19.43 | 16.41 | 0.130739E+09 | 86.96 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.105397E+10 | 556.14 | 04-OCT-10:33 | 18.33 | 11.02 | 0.124622E+09 | 81.86 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.646416E+09 | 503.12 | 04-NOV-10:33 | 17.23 | 14.47 | 0.114666E+09 | 75.90 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.352454E+09 | 405.15 | 05-DEC-21:00 | 5.60 | 1.73 | 0.116745E+09 | 70.06 | 29-DEC-23:10 | 8.72 | 7.62 |
Annual Sum or Average | 0.108000E+11 | 0.149382E+10 | ||||||||
Minimum of Months | 0.255535E+09 | 405.15 | 5.60 | 1.73 | 0.106110E+09 | 70.06 | 8.72 | 7.62 | ||
Maximum of Months | 0.134221E+10 | 665.66 | 30.57 | 19.31 | 0.143025E+09 | 91.24 | 21.82 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477542E+11 | 36660.27 | 11-JAN-21:00 | 11.10 | 10.22 | 0.584456E+09 | 381.60 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.436692E+11 | 37140.77 | 27-FEB-21:00 | 12.20 | 10.06 | 0.529739E+09 | 381.61 | 03-FEB-22:10 | 12.20 | 10.06 |
March | 0.493248E+11 | 37288.68 | 14-MAR-20:00 | 14.40 | 9.49 | 0.589980E+09 | 381.68 | 28-MAR-21:10 | 7.70 | 4.73 |
April | 0.484496E+11 | 38150.39 | 27-APR-20:00 | 19.40 | 13.66 | 0.571845E+09 | 381.65 | 03-APR-21:10 | 19.40 | 13.66 |
May | 0.508197E+11 | 38086.13 | 04-MAY-20:00 | 19.40 | 13.12 | 0.592463E+09 | 381.67 | 10-MAY-21:10 | 7.62 | 6.32 |
June | 0.499070E+11 | 38318.12 | 28-JUN-19:55 | 21.70 | 15.30 | 0.575586E+09 | 381.67 | 26-JUN-21:10 | 21.70 | 15.30 |
July | 0.518685E+11 | 38605.67 | 24-JUL-20:00 | 23.90 | 16.63 | 0.594865E+09 | 381.69 | 12-JUL-21:10 | 23.90 | 16.63 |
August | 0.523034E+11 | 38688.45 | 10-AUG-20:00 | 25.60 | 17.66 | 0.596845E+09 | 381.71 | 17-AUG-21:10 | 15.88 | 12.46 |
September | 0.495074E+11 | 38225.77 | 14-SEP-20:00 | 18.90 | 14.81 | 0.574501E+09 | 381.68 | 07-SEP-21:10 | 18.90 | 14.81 |
October | 0.498781E+11 | 37817.88 | 04-OCT-20:00 | 17.20 | 10.66 | 0.591255E+09 | 381.64 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 0.472033E+11 | 37018.29 | 02-NOV-20:00 | 12.80 | 10.42 | 0.568851E+09 | 381.63 | 16-NOV-22:10 | 5.40 | 4.66 |
December | 0.478857E+11 | 36534.87 | 05-DEC-21:00 | 5.60 | 1.73 | 0.585194E+09 | 381.64 | 22-DEC-22:10 | 2.10 | 1.63 |
Annual Sum or Average | 0.588571E+12 | 0.695558E+10 | ||||||||
Minimum of Months | 0.436692E+11 | 36534.87 | 5.60 | 1.73 | 0.529739E+09 | 381.60 | 2.10 | 1.63 | ||
Maximum of Months | 0.523034E+11 | 38688.45 | 25.60 | 17.66 | 0.596845E+09 | 381.71 | 23.90 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144122E+11 | 9183.57 | 08-JAN-11:35 | 1.33 | 0.94 | 0.858989E+10 | 5702.66 | 11-JAN-22:40 | 9.97 | 8.97 |
February | 0.151019E+11 | 10546.63 | 08-FEB-13:30 | 6.40 | 3.77 | 0.801272E+10 | 6168.63 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.184310E+11 | 12450.81 | 02-MAR-13:20 | 12.57 | 7.60 | 0.920490E+10 | 6325.43 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.194201E+11 | 11652.16 | 27-APR-14:10 | 26.28 | 16.91 | 0.911106E+10 | 6462.65 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.208793E+11 | 11331.96 | 04-MAY-14:10 | 23.98 | 15.25 | 0.958868E+10 | 6462.75 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.209270E+11 | 10641.89 | 28-JUN-18:10 | 25.40 | 16.48 | 0.946235E+10 | 6462.72 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.227845E+11 | 11378.16 | 30-JUL-10:33 | 23.33 | 16.24 | 0.100069E+11 | 6462.75 | 20-JUL-22:10 | 23.33 | 16.24 |
August | 0.234868E+11 | 13318.77 | 24-AUG-15:03 | 29.62 | 19.18 | 0.101737E+11 | 6462.74 | 11-AUG-22:10 | 29.62 | 19.18 |
September | 0.216502E+11 | 14009.16 | 23-SEP-13:15 | 22.57 | 17.43 | 0.958368E+10 | 6462.75 | 11-SEP-22:10 | 22.57 | 17.43 |
October | 0.198462E+11 | 14026.07 | 04-OCT-12:50 | 20.60 | 11.27 | 0.943046E+10 | 6462.54 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.158007E+11 | 12622.81 | 04-NOV-13:30 | 20.85 | 16.00 | 0.857109E+10 | 5922.31 | 02-NOV-21:40 | 20.85 | 16.00 |
December | 0.149295E+11 | 10278.73 | 02-DEC-11:33 | 11.83 | 6.03 | 0.865658E+10 | 5817.18 | 05-DEC-22:40 | 4.60 | 2.18 |
Annual Sum or Average | 0.227669E+12 | 0.110392E+12 | ||||||||
Minimum of Months | 0.144122E+11 | 9183.57 | 1.33 | 0.94 | 0.801272E+10 | 5702.66 | 4.60 | 2.18 | ||
Maximum of Months | 0.234868E+11 | 14026.07 | 29.62 | 19.18 | 0.101737E+11 | 6462.75 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540379E+11 | 26030.65 | 11-JAN-22:00 | 11.10 | 10.49 | 0.274549E+11 | 18227.28 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.517646E+11 | 28155.75 | 27-FEB-21:00 | 12.20 | 10.06 | 0.254928E+11 | 19180.50 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.608277E+11 | 28620.94 | 14-MAR-20:00 | 14.40 | 9.49 | 0.292586E+11 | 19183.24 | 02-MAR-22:00 | 14.40 | 9.49 |
April | 0.619622E+11 | 33782.30 | 27-APR-21:10 | 16.73 | 11.41 | 0.288842E+11 | 19186.09 | 26-APR-21:00 | 16.73 | 11.41 |
May | 0.667148E+11 | 33911.68 | 04-MAY-21:52 | 18.90 | 12.17 | 0.304909E+11 | 19186.33 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.667927E+11 | 34789.69 | 28-JUN-21:52 | 18.30 | 14.03 | 0.300087E+11 | 19186.27 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.720832E+11 | 37813.45 | 24-JUL-21:10 | 22.43 | 16.40 | 0.313820E+11 | 19186.25 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.736461E+11 | 39352.68 | 10-AUG-21:05 | 22.92 | 16.74 | 0.316639E+11 | 19186.23 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.674885E+11 | 37442.64 | 14-SEP-21:10 | 18.12 | 14.82 | 0.300760E+11 | 19186.20 | 11-SEP-22:10 | 18.12 | 14.82 |
October | 0.639972E+11 | 34606.62 | 04-OCT-21:10 | 14.27 | 9.23 | 0.299498E+11 | 19185.90 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.561896E+11 | 28843.13 | 04-NOV-10:33 | 17.23 | 14.47 | 0.275134E+11 | 18844.46 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.550314E+11 | 27064.21 | 03-DEC-11:33 | 11.33 | 5.78 | 0.277203E+11 | 18535.25 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.750536E+12 | 0.349896E+12 | ||||||||
Minimum of Months | 0.517646E+11 | 26030.65 | 11.10 | 5.78 | 0.254928E+11 | 18227.28 | 4.50 | 2.23 | ||
Maximum of Months | 0.736461E+11 | 39352.68 | 22.92 | 16.74 | 0.316639E+11 | 19186.33 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9476366.15 | 2580.60 | 08-JAN-16:02 | 4.03 | 1.75 | 93542799.41 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 64684689.87 | 3783.83 | 08-FEB-16:01 | 7.12 | 3.76 | 85701488.59 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.211128E+09 | 3824.16 | 01-MAR-16:01 | 12.20 | 6.79 | 96254814.84 | 56.69 | 18-MAR-23:10 | 10.40 | 8.02 |
April | 0.588137E+09 | 3831.96 | 25-APR-18:01 | 13.95 | 8.77 | 94326215.28 | 56.69 | 27-APR-21:19 | 16.27 | 11.36 |
May | 0.106065E+10 | 3936.04 | 14-MAY-18:01 | 21.83 | 11.88 | 98292432.29 | 56.69 | 04-MAY-21:19 | 21.83 | 11.88 |
June | 0.126057E+10 | 3383.48 | 29-JUN-15:01 | 17.30 | 13.30 | 95482998.39 | 56.70 | 22-JUN-21:00 | 17.30 | 13.30 |
July | 0.188663E+10 | 3398.66 | 11-JUL-15:01 | 21.88 | 17.19 | 98772967.70 | 56.70 | 27-JUL-21:00 | 17.80 | 14.44 |
August | 0.182868E+10 | 3451.94 | 02-AUG-15:01 | 18.37 | 14.02 | 98847672.90 | 56.70 | 24-AUG-22:49 | 20.48 | 16.60 |
September | 0.122463E+10 | 3474.01 | 22-SEP-18:01 | 20.40 | 16.20 | 95042001.42 | 56.70 | 12-SEP-21:19 | 20.40 | 16.20 |
October | 0.398695E+09 | 3796.31 | 04-OCT-18:01 | 17.52 | 10.01 | 96760129.28 | 56.69 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 54409171.40 | 3283.02 | 04-NOV-15:01 | 20.92 | 15.94 | 91641984.27 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 13312654.10 | 3542.50 | 02-DEC-16:02 | 10.40 | 4.47 | 93880732.32 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.860100E+10 | 0.113855E+10 | ||||||||
Minimum of Months | 9476366.15 | 2580.60 | 4.03 | 1.75 | 85701488.59 | 56.69 | -0.9 | -0.9 | ||
Maximum of Months | 0.188663E+10 | 3936.04 | 21.88 | 17.19 | 98847672.90 | 56.70 | 21.83 | 16.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4938948.89 | 386.96 | 20-JAN-16:04 | 5.40 | 3.78 | 92944303.97 | 56.69 | 17-JAN-04:19 | 5.40 | 3.78 |
February | 21190885.44 | 2879.36 | 26-FEB-16:01 | 14.40 | 10.25 | 84856662.19 | 56.69 | 14-FEB-04:19 | 14.40 | 10.25 |
March | 84536957.60 | 3458.37 | 01-MAR-16:01 | 12.20 | 6.79 | 95498938.15 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.350920E+09 | 3915.20 | 25-APR-17:41 | 14.60 | 8.96 | 94932323.94 | 72.67 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.689833E+09 | 3917.11 | 21-MAY-17:41 | 15.60 | 9.45 | 0.103065E+09 | 82.85 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.893552E+09 | 3449.58 | 18-JUN-20:11 | 14.63 | 11.86 | 0.101988E+09 | 85.01 | 19-JUN-18:10 | 19.22 | 12.49 |
July | 0.133407E+10 | 3699.25 | 25-JUL-16:51 | 25.60 | 18.36 | 0.109152E+09 | 89.75 | 21-JUL-18:10 | 25.60 | 18.36 |
August | 0.130591E+10 | 3530.05 | 06-AUG-21:51 | 17.90 | 14.41 | 0.105553E+09 | 79.97 | 08-AUG-21:10 | 24.15 | 15.61 |
September | 0.681984E+09 | 3586.59 | 22-SEP-16:11 | 24.43 | 17.44 | 0.100289E+09 | 78.72 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.168594E+09 | 3108.89 | 08-OCT-15:01 | 19.50 | 13.11 | 96542544.35 | 69.58 | 04-OCT-21:10 | 19.50 | 13.11 |
November | 22200813.54 | 2993.38 | 04-NOV-15:01 | 20.92 | 15.94 | 91077508.15 | 56.69 | 12-NOV-02:20 | 2.80 | 2.46 |
December | 5410780.96 | 419.56 | 28-DEC-19:06 | 10.60 | 9.36 | 93148147.41 | 56.69 | 22-DEC-04:19 | 10.60 | 9.36 |
Annual Sum or Average | 0.556314E+10 | 0.116905E+10 | ||||||||
Minimum of Months | 4938948.89 | 386.96 | 5.40 | 3.78 | 84856662.19 | 56.69 | 2.80 | 2.46 | ||
Maximum of Months | 0.133407E+10 | 3917.11 | 25.60 | 18.36 | 0.109152E+09 | 89.75 | 25.60 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7081441.63 | 111.24 | 08-JAN-15:20 | 5.20 | 2.41 | 0.00 | 0.00 | 01-JAN-00:10 | 5.20 | 2.41 |
February | 37014925.82 | 384.24 | 08-FEB-14:00 | 6.70 | 3.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.83 |
March | 0.124674E+09 | 560.39 | 02-MAR-13:30 | 12.75 | 7.74 | 0.00 | 0.00 | 01-MAR-00:10 | 12.75 | 7.74 |
April | 0.217252E+09 | 547.10 | 27-APR-13:05 | 26.10 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.37 |
May | 0.287146E+09 | 523.70 | 04-MAY-13:20 | 22.77 | 15.31 | 0.00 | 0.00 | 01-MAY-00:10 | 22.77 | 15.31 |
June | 0.328785E+09 | 397.30 | 28-JUN-13:20 | 24.60 | 15.70 | 0.00 | 0.00 | 01-JUN-00:10 | 24.60 | 15.70 |
July | 0.459439E+09 | 499.84 | 31-JUL-13:20 | 27.57 | 18.47 | 0.00 | 0.00 | 01-JUL-00:10 | 27.57 | 18.47 |
August | 0.523858E+09 | 628.06 | 24-AUG-13:05 | 28.93 | 19.36 | 0.00 | 0.00 | 01-AUG-00:10 | 28.93 | 19.36 |
September | 0.435369E+09 | 667.14 | 14-SEP-13:30 | 23.35 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.35 | 17.43 |
October | 0.242206E+09 | 692.91 | 04-OCT-12:30 | 20.60 | 11.38 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.38 |
November | 40815002.89 | 500.54 | 04-NOV-13:40 | 20.93 | 15.98 | 0.00 | 0.00 | 01-NOV-00:10 | 20.93 | 15.98 |
December | 18091696.27 | 312.26 | 05-DEC-12:30 | 10.30 | 6.13 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 6.13 |
Annual Sum or Average | 0.272173E+10 | 0.00 | ||||||||
Minimum of Months | 7081441.63 | 111.24 | 5.20 | 2.41 | 0.00 | 0.00 | 5.20 | 2.41 | ||
Maximum of Months | 0.523858E+09 | 692.91 | 28.93 | 19.36 | 0.00 | 0.00 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52186122.76 | 775.73 | 01-JAN-09:02 | 7.80 | 6.49 | 94944315.28 | 56.69 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 88917093.12 | 890.10 | 26-FEB-09:02 | 9.60 | 8.77 | 86224470.52 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.189781E+09 | 997.39 | 28-MAR-18:01 | 10.92 | 4.32 | 96378569.64 | 56.69 | 18-MAR-23:19 | 10.92 | 4.32 |
April | 0.310200E+09 | 1040.53 | 24-APR-18:01 | 12.93 | 7.27 | 94516384.28 | 69.48 | 27-APR-21:00 | 14.40 | 11.03 |
May | 0.436203E+09 | 1098.27 | 14-MAY-21:51 | 16.70 | 9.76 | 99803981.13 | 75.18 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.504111E+09 | 1015.16 | 22-JUN-21:51 | 15.60 | 12.67 | 98726056.56 | 73.85 | 22-JUN-21:49 | 15.60 | 12.67 |
July | 0.577596E+09 | 1029.74 | 29-JUL-15:01 | 23.30 | 15.38 | 0.103422E+09 | 76.08 | 26-JUL-21:10 | 23.30 | 15.38 |
August | 0.569101E+09 | 1032.54 | 06-AUG-15:01 | 23.72 | 15.80 | 0.102597E+09 | 73.35 | 18-AUG-21:10 | 15.13 | 12.34 |
September | 0.407331E+09 | 1014.41 | 11-SEP-15:01 | 23.30 | 15.89 | 97051711.64 | 71.84 | 13-SEP-21:49 | 18.30 | 14.68 |
October | 0.263596E+09 | 1026.40 | 04-OCT-21:12 | 14.63 | 9.40 | 96787879.67 | 67.75 | 04-OCT-21:10 | 14.63 | 9.40 |
November | 0.135649E+09 | 902.71 | 05-NOV-08:62 | 12.88 | 12.19 | 92714509.19 | 56.69 | 06-NOV-23:19 | 15.20 | 13.99 |
December | 53431358.31 | 955.13 | 03-DEC-09:02 | 7.98 | 3.60 | 95008002.05 | 56.69 | 01-DEC-04:19 | 7.98 | 3.60 |
Annual Sum or Average | 0.358810E+10 | 0.115817E+10 | ||||||||
Minimum of Months | 52186122.76 | 775.73 | 7.80 | 3.60 | 86224470.52 | 56.69 | 7.98 | 3.60 | ||
Maximum of Months | 0.577596E+09 | 1098.27 | 23.72 | 15.89 | 0.103422E+09 | 76.08 | 23.30 | 15.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9242419.35 | 506.82 | 05-JAN-09:04 | -0.0 | -0.1 | 93468749.35 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 60776106.37 | 3233.26 | 08-FEB-16:01 | 7.12 | 3.76 | 85726407.31 | 56.69 | 10-FEB-04:19 | 1.13 | 0.40 |
March | 0.203618E+09 | 3442.07 | 25-MAR-08:61 | 4.78 | 0.26 | 96455688.71 | 56.69 | 18-MAR-23:10 | 4.78 | 0.26 |
April | 0.600629E+09 | 3438.71 | 19-APR-15:01 | 13.22 | 6.85 | 94694689.40 | 56.69 | 28-APR-00:00 | 14.40 | 12.20 |
May | 0.925411E+09 | 3505.71 | 14-MAY-18:01 | 21.83 | 11.88 | 98360007.33 | 56.69 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.132505E+10 | 3107.44 | 11-JUN-08:61 | 14.08 | 12.32 | 95676137.55 | 56.69 | 28-JUN-21:19 | 17.23 | 13.81 |
July | 0.165050E+10 | 3172.22 | 15-JUL-15:01 | 22.30 | 17.28 | 98856691.34 | 56.70 | 20-JUL-21:19 | 17.23 | 13.29 |
August | 0.179749E+10 | 3227.17 | 25-AUG-08:61 | 19.83 | 16.44 | 98983795.20 | 56.70 | 10-AUG-22:49 | 19.83 | 16.44 |
September | 0.111154E+10 | 3148.17 | 22-SEP-18:01 | 20.40 | 16.20 | 95019321.26 | 56.70 | 13-SEP-21:19 | 20.40 | 16.20 |
October | 0.389463E+09 | 3437.13 | 04-OCT-18:01 | 17.52 | 10.01 | 96896142.42 | 56.69 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 58555975.01 | 3148.77 | 04-NOV-15:01 | 20.92 | 15.94 | 91608492.10 | 56.69 | 10-NOV-04:19 | 4.27 | 3.70 |
December | 21695805.04 | 1705.57 | 02-DEC-09:02 | 8.58 | 4.35 | 93797612.07 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.815397E+10 | 0.113954E+10 | ||||||||
Minimum of Months | 9242419.35 | 506.82 | -0.0 | -0.1 | 85726407.31 | 56.69 | -0.9 | -0.9 | ||
Maximum of Months | 0.179749E+10 | 3505.71 | 22.30 | 17.28 | 98983795.20 | 56.70 | 20.40 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4037879.60 | 376.89 | 10-JAN-19:06 | 9.32 | 4.98 | 92901861.87 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 17314305.99 | 2313.59 | 27-FEB-16:01 | 19.32 | 12.38 | 84789410.71 | 56.69 | 14-FEB-04:19 | 19.32 | 12.38 |
March | 73474045.56 | 3104.71 | 25-MAR-08:61 | 4.78 | 0.26 | 95526309.02 | 56.69 | 19-MAR-01:19 | 4.78 | 0.26 |
April | 0.372111E+09 | 3088.62 | 25-APR-18:01 | 13.95 | 8.77 | 94896296.56 | 70.26 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.642165E+09 | 3378.59 | 06-MAY-08:51 | 19.40 | 15.38 | 0.100617E+09 | 74.64 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.100231E+10 | 3222.66 | 10-JUN-08:51 | 18.30 | 14.28 | 0.100269E+09 | 73.78 | 20-JUN-21:30 | 18.60 | 13.40 |
July | 0.120309E+10 | 3672.00 | 24-JUL-08:32 | 23.17 | 16.50 | 0.105192E+09 | 77.36 | 24-JUL-21:19 | 22.07 | 16.28 |
August | 0.129400E+10 | 3588.47 | 10-AUG-08:32 | 22.00 | 17.03 | 0.104559E+09 | 77.37 | 08-AUG-21:10 | 22.00 | 17.03 |
September | 0.652879E+09 | 3340.68 | 13-SEP-08:51 | 18.30 | 15.25 | 97933562.11 | 73.71 | 13-SEP-21:40 | 18.30 | 14.73 |
October | 0.171236E+09 | 2912.87 | 07-OCT-08:61 | 10.18 | 9.20 | 96315173.15 | 66.02 | 04-OCT-21:10 | 10.18 | 9.20 |
November | 22297536.49 | 2491.73 | 04-NOV-15:01 | 20.92 | 15.94 | 90985950.84 | 56.69 | 25-NOV-02:20 | 5.60 | 4.81 |
December | 5505312.86 | 427.73 | 30-DEC-09:04 | 4.18 | 3.83 | 93067532.04 | 56.69 | 12-DEC-04:19 | 4.18 | 3.83 |
Annual Sum or Average | 0.546043E+10 | 0.115705E+10 | ||||||||
Minimum of Months | 4037879.60 | 376.89 | 4.18 | 0.26 | 84789410.71 | 56.69 | 1.70 | -0.1 | ||
Maximum of Months | 0.129400E+10 | 3672.00 | 23.17 | 17.03 | 0.105192E+09 | 77.37 | 22.07 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166736E+10 | 1562.93 | 11-JAN-21:00 | 11.10 | 10.22 | 0.119905E+10 | 719.62 | 11-JAN-22:49 | 9.68 | 8.60 |
February | 0.223158E+10 | 1771.61 | 27-FEB-19:10 | 15.73 | 11.89 | 0.108854E+10 | 753.11 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.341747E+10 | 1872.42 | 25-MAR-10:33 | 8.87 | 1.80 | 0.122673E+10 | 762.05 | 14-MAR-21:49 | 8.87 | 1.80 |
April | 0.392862E+10 | 2227.72 | 27-APR-18:10 | 25.55 | 15.86 | 0.122704E+10 | 835.66 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.452260E+10 | 2319.82 | 06-MAY-10:33 | 20.93 | 16.16 | 0.134151E+10 | 856.14 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.462373E+10 | 2383.93 | 28-JUN-10:33 | 21.50 | 14.65 | 0.134055E+10 | 877.64 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.507004E+10 | 2530.65 | 24-JUL-18:10 | 28.72 | 17.86 | 0.143233E+10 | 906.90 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.516012E+10 | 2578.42 | 13-AUG-10:33 | 24.17 | 17.28 | 0.145465E+10 | 919.03 | 10-AUG-21:40 | 24.17 | 17.28 |
September | 0.458236E+10 | 2464.08 | 14-SEP-10:33 | 19.43 | 16.41 | 0.133613E+10 | 900.37 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.386086E+10 | 2175.80 | 04-OCT-10:33 | 18.33 | 11.02 | 0.126358E+10 | 833.93 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.248284E+10 | 1896.86 | 04-NOV-10:45 | 17.52 | 14.63 | 0.116668E+10 | 741.53 | 05-NOV-23:19 | 11.10 | 9.49 |
December | 0.188658E+10 | 1715.07 | 03-DEC-11:33 | 11.33 | 5.78 | 0.119947E+10 | 720.94 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.434341E+11 | 0.152763E+11 | ||||||||
Minimum of Months | 0.166736E+10 | 1562.93 | 8.87 | 1.80 | 0.108854E+10 | 719.62 | 4.50 | 1.80 | ||
Maximum of Months | 0.516012E+10 | 2578.42 | 28.72 | 17.86 | 0.145465E+10 | 919.03 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6204825.91 | 2448.97 | 20-JAN-16:01 | 5.40 | 3.78 | 93014315.45 | 56.69 | 20-JAN-04:19 | 5.40 | 3.78 |
February | 58745232.50 | 3929.66 | 08-FEB-16:01 | 7.12 | 3.76 | 85257354.41 | 56.69 | 17-FEB-04:19 | 1.50 | -0.2 |
March | 0.204971E+09 | 3981.88 | 01-MAR-16:01 | 12.20 | 6.79 | 95898928.71 | 56.69 | 18-MAR-23:40 | 9.80 | 8.00 |
April | 0.585968E+09 | 3992.59 | 25-APR-18:01 | 13.95 | 8.77 | 94149102.39 | 56.69 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.106296E+10 | 4101.97 | 14-MAY-18:01 | 21.83 | 11.88 | 98179458.71 | 56.70 | 22-MAY-02:30 | 10.00 | 7.38 |
June | 0.126799E+10 | 3529.23 | 29-JUN-15:01 | 17.30 | 13.30 | 95415022.78 | 56.70 | 24-JUN-03:30 | 17.30 | 13.30 |
July | 0.192959E+10 | 3483.19 | 11-JUL-15:01 | 21.88 | 17.19 | 98699606.65 | 56.70 | 27-JUL-21:19 | 18.53 | 15.10 |
August | 0.182715E+10 | 3585.35 | 28-AUG-15:01 | 24.43 | 16.91 | 98758437.64 | 56.70 | 10-AUG-22:49 | 24.43 | 16.91 |
September | 0.118518E+10 | 3599.89 | 22-SEP-18:01 | 20.40 | 16.20 | 94874584.81 | 56.69 | 15-SEP-22:40 | 20.40 | 16.20 |
October | 0.351891E+09 | 3946.68 | 04-OCT-18:01 | 17.52 | 10.01 | 96424649.97 | 56.69 | 05-OCT-02:49 | 10.18 | 6.62 |
November | 47148215.83 | 3336.80 | 04-NOV-15:01 | 20.92 | 15.94 | 91155723.49 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 9332921.55 | 3706.73 | 02-DEC-16:02 | 10.40 | 4.47 | 93414726.32 | 56.69 | 22-DEC-04:19 | 0.20 | -0.9 |
Annual Sum or Average | 0.853713E+10 | 0.113524E+10 | ||||||||
Minimum of Months | 6204825.91 | 2448.97 | 5.40 | 3.76 | 85257354.41 | 56.69 | 0.20 | -0.9 | ||
Maximum of Months | 0.192959E+10 | 4101.97 | 24.43 | 17.19 | 98758437.64 | 56.70 | 24.43 | 16.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1017971.07 | 548.91 | 05-JAN-16:04 | 5.73 | 4.38 | 92569621.56 | 56.69 | 06-JAN-04:19 | -1.5 | -1.5 |
February | 15773779.16 | 2989.11 | 26-FEB-16:01 | 14.40 | 10.25 | 84422462.67 | 56.69 | 10-FEB-04:19 | 14.40 | 10.25 |
March | 74274582.17 | 3566.58 | 01-MAR-16:01 | 12.20 | 6.79 | 95125395.77 | 59.61 | 14-MAR-18:10 | 15.50 | 9.66 |
April | 0.340999E+09 | 4065.11 | 25-APR-17:41 | 14.60 | 8.96 | 94956074.61 | 74.64 | 26-APR-21:19 | 14.67 | 10.66 |
May | 0.688430E+09 | 4061.41 | 21-MAY-17:41 | 15.60 | 9.45 | 0.104061E+09 | 89.41 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.911889E+09 | 3616.43 | 18-JUN-20:11 | 14.63 | 11.86 | 0.103119E+09 | 92.36 | 19-JUN-21:10 | 16.20 | 11.60 |
July | 0.140561E+10 | 3818.48 | 21-JUL-21:51 | 16.70 | 12.86 | 0.110862E+09 | 95.80 | 21-JUL-18:10 | 16.70 | 12.86 |
August | 0.132183E+10 | 3893.32 | 06-AUG-21:51 | 17.90 | 14.41 | 0.106037E+09 | 82.62 | 11-AUG-18:10 | 20.88 | 15.38 |
September | 0.635467E+09 | 3707.41 | 22-SEP-16:11 | 24.43 | 17.44 | 0.101125E+09 | 85.92 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.127601E+09 | 3168.56 | 08-OCT-15:01 | 19.50 | 13.11 | 96198825.41 | 70.22 | 04-OCT-21:10 | 19.50 | 13.11 |
November | 15041273.64 | 3088.58 | 04-NOV-15:01 | 20.92 | 15.94 | 90598039.93 | 56.69 | 24-NOV-04:19 | 3.53 | 2.50 |
December | 3082931.61 | 494.79 | 01-DEC-16:04 | 7.62 | 6.00 | 92708871.18 | 56.69 | 12-DEC-04:19 | 1.33 | 1.33 |
Annual Sum or Average | 0.554102E+10 | 0.117178E+10 | ||||||||
Minimum of Months | 1017971.07 | 494.79 | 5.73 | 4.38 | 84422462.67 | 56.69 | -1.5 | -1.5 | ||
Maximum of Months | 0.140561E+10 | 4065.11 | 24.43 | 17.44 | 0.110862E+09 | 95.80 | 24.43 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55499718.71 | 1917.11 | 09-JAN-16:02 | 5.00 | 2.45 | 94894184.33 | 56.69 | 24-JAN-04:19 | 5.00 | 3.79 |
February | 0.202928E+09 | 2437.32 | 12-FEB-16:01 | 6.52 | 1.59 | 86917761.21 | 56.69 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.356819E+09 | 2463.53 | 25-MAR-15:01 | 11.70 | 3.86 | 97228177.46 | 56.69 | 18-MAR-23:30 | 11.70 | 3.86 |
April | 0.546704E+09 | 2367.57 | 13-APR-18:01 | 16.52 | 9.25 | 94866104.20 | 56.69 | 26-APR-21:19 | 14.67 | 10.66 |
May | 0.691816E+09 | 2454.70 | 14-MAY-18:01 | 21.83 | 11.88 | 98388919.19 | 56.69 | 06-MAY-23:30 | 21.83 | 11.88 |
June | 0.786925E+09 | 2190.68 | 23-JUN-15:01 | 16.88 | 12.55 | 95498557.90 | 56.69 | 11-JUN-23:49 | 16.88 | 12.55 |
July | 0.105264E+10 | 2217.05 | 11-JUL-15:01 | 21.88 | 17.19 | 98690103.92 | 56.70 | 31-JUL-21:30 | 21.00 | 16.47 |
August | 0.115702E+10 | 2222.37 | 17-AUG-15:01 | 20.23 | 13.67 | 98792508.22 | 56.70 | 23-AUG-21:00 | 21.20 | 16.16 |
September | 0.945389E+09 | 2235.72 | 23-SEP-18:01 | 20.40 | 16.56 | 95165309.49 | 56.70 | 13-SEP-21:30 | 20.40 | 16.56 |
October | 0.542507E+09 | 2426.82 | 04-OCT-18:01 | 17.52 | 10.01 | 97587972.88 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.147811E+09 | 2154.30 | 05-NOV-15:01 | 14.50 | 12.81 | 92744444.45 | 56.69 | 04-NOV-23:00 | 14.50 | 12.81 |
December | 0.113361E+09 | 2403.88 | 03-DEC-16:01 | 10.92 | 4.95 | 95114376.40 | 56.69 | 23-DEC-00:20 | 1.87 | 1.62 |
Annual Sum or Average | 0.659941E+10 | 0.114589E+10 | ||||||||
Minimum of Months | 55499718.71 | 1917.11 | 5.00 | 1.59 | 86917761.21 | 56.69 | 1.87 | 1.62 | ||
Maximum of Months | 0.115702E+10 | 2463.53 | 21.88 | 17.19 | 98792508.22 | 56.70 | 21.83 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310422E+11 | 17856.16 | 11-JAN-22:50 | 9.68 | 8.60 | 0.188727E+11 | 11347.95 | 10-JAN-04:19 | 9.68 | 8.60 |
February | 0.288547E+11 | 18919.82 | 27-FEB-23:00 | 12.20 | 10.35 | 0.171381E+11 | 11347.94 | 10-FEB-04:19 | 12.20 | 10.35 |
March | 0.337560E+11 | 18795.69 | 10-MAR-23:00 | 11.10 | 10.84 | 0.191877E+11 | 11347.96 | 30-MAR-23:19 | 7.60 | 4.67 |
April | 0.345468E+11 | 20684.48 | 27-APR-21:10 | 16.73 | 11.41 | 0.185996E+11 | 11348.87 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.377909E+11 | 21031.30 | 05-MAY-21:53 | 17.80 | 12.72 | 0.192871E+11 | 11349.24 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.381988E+11 | 21480.93 | 28-JUN-21:52 | 18.30 | 14.03 | 0.187202E+11 | 11349.22 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.406802E+11 | 22244.75 | 24-JUL-21:10 | 22.43 | 16.40 | 0.192849E+11 | 11349.21 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.407168E+11 | 22237.50 | 10-AUG-21:52 | 22.50 | 15.63 | 0.193583E+11 | 11349.11 | 11-AUG-22:10 | 15.85 | 13.74 |
September | 0.368190E+11 | 20931.61 | 12-SEP-21:52 | 18.30 | 14.27 | 0.186420E+11 | 11349.11 | 11-SEP-22:10 | 18.30 | 14.27 |
October | 0.348544E+11 | 19750.74 | 04-OCT-22:00 | 16.10 | 10.03 | 0.191544E+11 | 11348.61 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.317012E+11 | 18888.48 | 06-NOV-23:00 | 15.60 | 14.58 | 0.183900E+11 | 11348.04 | 14-NOV-04:19 | 5.00 | 2.33 |
December | 0.312429E+11 | 17606.40 | 29-DEC-23:00 | 8.90 | 7.76 | 0.189181E+11 | 11348.10 | 12-DEC-04:19 | 8.90 | 7.76 |
Annual Sum or Average | 0.420204E+12 | 0.225553E+12 | ||||||||
Minimum of Months | 0.288547E+11 | 17606.40 | 8.90 | 7.76 | 0.171381E+11 | 11347.94 | 5.00 | 2.33 | ||
Maximum of Months | 0.407168E+11 | 22244.75 | 22.50 | 16.40 | 0.193583E+11 | 11349.24 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347661E+11 | 19923.81 | 11-JAN-22:10 | 10.82 | 10.11 | 0.190814E+11 | 11348.00 | 10-JAN-04:19 | 10.82 | 10.11 |
February | 0.322707E+11 | 20743.25 | 27-FEB-23:00 | 12.20 | 10.35 | 0.172997E+11 | 11347.98 | 10-FEB-04:19 | 12.20 | 10.35 |
March | 0.376312E+11 | 20733.17 | 08-MAR-23:00 | 13.90 | 9.29 | 0.193058E+11 | 11347.97 | 30-MAR-23:19 | 7.60 | 4.67 |
April | 0.382625E+11 | 22206.65 | 27-APR-21:10 | 16.73 | 11.41 | 0.186747E+11 | 11348.88 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.414610E+11 | 22531.06 | 05-MAY-21:20 | 18.53 | 12.90 | 0.193291E+11 | 11360.87 | 05-MAY-21:19 | 18.53 | 12.90 |
June | 0.415958E+11 | 22828.67 | 28-JUN-21:20 | 17.23 | 13.81 | 0.187486E+11 | 11367.98 | 20-JUN-21:19 | 17.23 | 13.81 |
July | 0.439934E+11 | 23504.29 | 24-JUL-21:20 | 22.07 | 16.28 | 0.193037E+11 | 11368.71 | 25-JUL-21:19 | 17.23 | 14.73 |
August | 0.439661E+11 | 23446.53 | 10-AUG-21:05 | 22.92 | 16.74 | 0.193817E+11 | 11371.70 | 23-AUG-21:19 | 21.47 | 16.20 |
September | 0.401980E+11 | 22276.70 | 12-SEP-21:10 | 19.22 | 14.66 | 0.186840E+11 | 11349.12 | 11-SEP-22:10 | 19.22 | 14.66 |
October | 0.386660E+11 | 21288.87 | 04-OCT-22:00 | 16.10 | 10.03 | 0.192458E+11 | 11348.62 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.354306E+11 | 20765.38 | 06-NOV-23:00 | 15.60 | 14.58 | 0.185421E+11 | 11348.08 | 14-NOV-04:19 | 5.00 | 2.33 |
December | 0.350037E+11 | 19644.76 | 29-DEC-23:00 | 8.90 | 7.76 | 0.191117E+11 | 11348.14 | 12-DEC-04:19 | 8.90 | 7.76 |
Annual Sum or Average | 0.463245E+12 | 0.226708E+12 | ||||||||
Minimum of Months | 0.322707E+11 | 19644.76 | 8.90 | 7.76 | 0.172997E+11 | 11347.97 | 5.00 | 2.33 | ||
Maximum of Months | 0.439934E+11 | 23504.29 | 22.92 | 16.74 | 0.193817E+11 | 11371.70 | 21.47 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486473E+11 | 26421.79 | 30-JAN-11:33 | 8.13 | 6.36 | 0.188149E+11 | 11319.63 | 21-JAN-18:19 | 8.13 | 6.36 |
February | 0.449394E+11 | 27590.05 | 27-FEB-11:45 | 16.23 | 10.66 | 0.169990E+11 | 11319.63 | 18-FEB-18:19 | 16.23 | 10.66 |
March | 0.512961E+11 | 28726.98 | 14-MAR-10:33 | 11.13 | 8.42 | 0.188357E+11 | 11319.58 | 18-MAR-17:19 | 19.03 | 9.50 |
April | 0.514298E+11 | 30139.38 | 27-APR-10:33 | 20.37 | 13.53 | 0.182308E+11 | 11319.66 | 29-APR-17:19 | 20.57 | 14.52 |
May | 0.544002E+11 | 30251.25 | 14-MAY-10:45 | 20.32 | 12.80 | 0.188458E+11 | 11319.65 | 13-MAY-17:19 | 20.32 | 12.80 |
June | 0.539577E+11 | 30520.85 | 10-JUN-10:45 | 20.40 | 14.81 | 0.182484E+11 | 11319.62 | 24-JUN-17:19 | 19.23 | 11.83 |
July | 0.564485E+11 | 31019.33 | 24-JUL-10:37 | 25.93 | 17.48 | 0.188543E+11 | 11319.69 | 29-JUL-17:19 | 23.17 | 15.48 |
August | 0.567411E+11 | 31068.02 | 13-AUG-10:37 | 24.17 | 17.28 | 0.188635E+11 | 11319.69 | 12-AUG-17:19 | 24.17 | 17.28 |
September | 0.530796E+11 | 30403.20 | 10-SEP-10:50 | 18.62 | 13.97 | 0.182431E+11 | 11319.66 | 23-SEP-17:19 | 21.67 | 16.65 |
October | 0.522069E+11 | 29263.19 | 04-OCT-10:33 | 18.33 | 11.02 | 0.188372E+11 | 11319.62 | 28-OCT-17:19 | 10.73 | 7.68 |
November | 0.485095E+11 | 28791.07 | 04-NOV-10:45 | 17.52 | 14.63 | 0.182179E+11 | 11319.63 | 18-NOV-18:19 | 11.87 | 9.60 |
December | 0.489364E+11 | 26935.35 | 03-DEC-11:50 | 11.52 | 5.93 | 0.188166E+11 | 11319.62 | 23-DEC-18:19 | 5.60 | 4.96 |
Annual Sum or Average | 0.620593E+12 | 0.221807E+12 | ||||||||
Minimum of Months | 0.449394E+11 | 26421.79 | 8.13 | 5.93 | 0.169990E+11 | 11319.58 | 5.60 | 4.96 | ||
Maximum of Months | 0.567411E+11 | 31068.02 | 25.93 | 17.48 | 0.188635E+11 | 11319.69 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334586E+10 | 3236.64 | 20-JAN-11:35 | 5.60 | 3.50 | 0.126899E+10 | 762.00 | 11-JAN-22:40 | 5.60 | 3.50 |
February | 0.439102E+10 | 3712.95 | 27-FEB-11:33 | 15.77 | 10.52 | 0.115351E+10 | 815.75 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.684677E+10 | 3922.95 | 18-MAR-17:13 | 19.03 | 9.50 | 0.130134E+10 | 829.51 | 14-MAR-21:40 | 19.03 | 9.50 |
April | 0.792672E+10 | 4771.78 | 27-APR-18:10 | 25.55 | 15.86 | 0.130786E+10 | 916.77 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.916747E+10 | 4912.35 | 06-MAY-10:33 | 20.93 | 16.16 | 0.142211E+10 | 923.11 | 04-MAY-21:40 | 20.93 | 16.16 |
June | 0.949066E+10 | 5078.55 | 28-JUN-18:10 | 25.40 | 16.48 | 0.143503E+10 | 956.82 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.103996E+11 | 5361.51 | 24-JUL-18:10 | 28.72 | 17.86 | 0.153326E+10 | 992.34 | 24-JUL-21:30 | 21.70 | 16.16 |
August | 0.105166E+11 | 6189.32 | 10-AUG-15:03 | 30.37 | 18.88 | 0.154803E+10 | 1005.09 | 10-AUG-21:30 | 22.75 | 16.30 |
September | 0.918967E+10 | 5065.87 | 14-SEP-10:33 | 19.43 | 16.41 | 0.140797E+10 | 955.27 | 14-SEP-21:30 | 17.75 | 14.69 |
October | 0.776766E+10 | 4504.50 | 04-OCT-10:33 | 18.33 | 11.02 | 0.133028E+10 | 883.70 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.519666E+10 | 4016.37 | 04-NOV-10:50 | 17.52 | 14.63 | 0.123725E+10 | 798.42 | 05-NOV-23:19 | 11.10 | 9.49 |
December | 0.372301E+10 | 3563.16 | 03-DEC-11:33 | 11.33 | 5.78 | 0.126953E+10 | 750.08 | 29-DEC-22:40 | 8.90 | 7.67 |
Annual Sum or Average | 0.879616E+11 | 0.162152E+11 | ||||||||
Minimum of Months | 0.334586E+10 | 3236.64 | 5.60 | 3.50 | 0.115351E+10 | 750.08 | 5.60 | 3.50 | ||
Maximum of Months | 0.105166E+11 | 6189.32 | 30.37 | 18.88 | 0.154803E+10 | 1005.09 | 22.75 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178942E+09 | 608.83 | 16-JAN-17:00 | 1.70 |
February | 73594353.98 | 801.01 | 19-FEB-06:00 | -5.6 |
March | 1326087.98 | 169.52 | 05-MAR-18:00 | 5.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 28858501.45 | 393.60 | 30-NOV-16:00 | 4.40 |
December | 0.170691E+09 | 782.31 | 26-DEC-12:00 | 0.20 |
Annual Sum or Average | 0.453411E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.178942E+09 | 801.01 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11219210.12 | 200.07 | 16-JAN-16:00 | 2.20 |
February | 4182314.78 | 140.40 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 5019934.97 | 160.13 | 26-DEC-13:00 | 0.60 |
Annual Sum or Average | 20421459.87 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 11219210.12 | 200.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52788201.90 | 218.20 | 16-JAN-17:00 | 1.70 |
February | 27648918.19 | 204.89 | 19-FEB-06:00 | -5.6 |
March | 1972.13 | 2.63 | 05-MAR-17:00 | 5.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 1419636.27 | 49.78 | 30-NOV-16:00 | 4.40 |
December | 25348617.95 | 201.96 | 26-DEC-12:40 | 0.47 |
Annual Sum or Average | 0.107207E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 52788201.90 | 218.20 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.925175E+09 | 1342.95 | 16-JAN-16:13 | 2.03 |
February | 0.548011E+09 | 1361.86 | 19-FEB-16:03 | 2.62 |
March | 0.272078E+09 | 1417.57 | 24-MAR-18:03 | 7.70 |
April | 97166131.07 | 1251.18 | 19-APR-08:62 | 5.87 |
May | 20109149.05 | 1268.47 | 01-MAY-18:03 | 14.32 |
June | 4025519.52 | 1068.82 | 07-JUN-08:03 | 11.88 |
July | 2086891.00 | 1000.33 | 12-JUL-08:04 | 12.80 |
August | 2688302.46 | 1055.36 | 04-AUG-08:03 | 13.03 |
September | 8962520.41 | 1147.53 | 18-SEP-15:03 | 16.10 |
October | 0.123614E+09 | 1229.68 | 27-OCT-15:02 | 10.82 |
November | 0.505382E+09 | 1331.61 | 30-NOV-16:13 | 4.60 |
December | 0.845228E+09 | 1433.29 | 03-DEC-16:03 | 10.92 |
Annual Sum or Average | 0.335453E+10 | |||
Minimum of Months | 2086891.00 | 1000.33 | 2.03 | |
Maximum of Months | 0.925175E+09 | 1433.29 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106714E+10 | 1323.66 | 16-JAN-16:13 | 2.03 |
February | 0.699770E+09 | 1306.50 | 19-FEB-09:13 | -2.9 |
March | 0.367652E+09 | 1325.07 | 26-MAR-15:03 | 10.60 |
April | 0.128451E+09 | 1246.67 | 19-APR-08:62 | 5.87 |
May | 22281146.07 | 1091.82 | 15-MAY-08:04 | 15.37 |
June | 4114942.14 | 1129.51 | 21-JUN-08:04 | 14.68 |
July | 1849529.66 | 1092.38 | 19-JUL-08:04 | 15.97 |
August | 2326609.61 | 1069.36 | 23-AUG-08:53 | 21.20 |
September | 10398666.15 | 1229.71 | 21-SEP-15:04 | 17.30 |
October | 0.180350E+09 | 1238.70 | 07-OCT-18:04 | 13.80 |
November | 0.611115E+09 | 1305.64 | 30-NOV-16:13 | 4.60 |
December | 0.992047E+09 | 1324.21 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.408749E+10 | |||
Minimum of Months | 1849529.66 | 1069.36 | -2.9 | |
Maximum of Months | 0.106714E+10 | 1325.07 | 21.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68172338.88 | 362.91 | 07-JAN-16:01 | 2.70 |
February | 40757623.07 | 359.21 | 19-FEB-16:01 | 2.62 |
March | 2805337.70 | 356.56 | 08-MAR-16:05 | 16.02 |
April | 1183589.72 | 355.30 | 08-APR-15:04 | 10.10 |
May | 534525.11 | 354.63 | 21-MAY-15:06 | 16.10 |
June | 351565.59 | 348.96 | 04-JUN-15:06 | 17.12 |
July | 201120.44 | 356.24 | 03-JUL-15:06 | 16.42 |
August | 307191.78 | 336.56 | 02-AUG-15:06 | 18.37 |
September | 695450.68 | 356.36 | 18-SEP-15:05 | 16.10 |
October | 1781854.68 | 350.58 | 02-OCT-15:04 | 17.20 |
November | 14591176.68 | 346.35 | 30-NOV-16:02 | 4.50 |
December | 49110698.09 | 353.77 | 06-DEC-16:01 | 2.93 |
Annual Sum or Average | 0.180492E+09 | |||
Minimum of Months | 201120.44 | 336.56 | 2.62 | |
Maximum of Months | 68172338.88 | 362.91 | 18.37 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929558E+09 | 1314.68 | 16-JAN-16:13 | 2.03 |
February | 0.550052E+09 | 1356.36 | 12-FEB-16:03 | 6.52 |
March | 0.263438E+09 | 1251.64 | 05-MAR-16:02 | 6.02 |
April | 91525077.15 | 1214.88 | 18-APR-08:62 | 4.50 |
May | 25164631.47 | 1149.52 | 16-MAY-18:04 | 13.72 |
June | 4084524.93 | 1199.30 | 07-JUN-18:04 | 14.90 |
July | 2287237.32 | 1278.56 | 16-JUL-15:04 | 17.80 |
August | 2321498.45 | 1246.05 | 31-AUG-18:04 | 20.10 |
September | 10815219.07 | 1228.66 | 06-SEP-15:04 | 16.02 |
October | 0.126956E+09 | 1332.70 | 01-OCT-15:04 | 16.70 |
November | 0.508049E+09 | 1302.24 | 30-NOV-16:13 | 4.60 |
December | 0.851464E+09 | 1320.94 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.336572E+10 | |||
Minimum of Months | 2287237.32 | 1149.52 | 2.03 | |
Maximum of Months | 0.929558E+09 | 1356.36 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107521E+10 | 1303.83 | 07-JAN-16:01 | 2.70 |
February | 0.698577E+09 | 1292.16 | 19-FEB-16:01 | 2.62 |
March | 0.347557E+09 | 1240.00 | 05-MAR-16:02 | 6.02 |
April | 0.119702E+09 | 1317.98 | 19-APR-18:03 | 10.82 |
May | 29405152.16 | 1325.08 | 24-MAY-15:04 | 15.68 |
June | 4149939.65 | 1167.14 | 06-JUN-15:04 | 14.53 |
July | 2201643.55 | 1177.15 | 01-JUL-08:04 | 15.10 |
August | 1542196.59 | 1107.20 | 03-AUG-15:04 | 19.30 |
September | 13001253.60 | 1276.67 | 19-SEP-15:04 | 18.12 |
October | 0.182946E+09 | 1271.95 | 07-OCT-15:04 | 18.03 |
November | 0.607145E+09 | 1277.32 | 12-NOV-16:02 | 4.72 |
December | 0.993245E+09 | 1294.49 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.407469E+10 | |||
Minimum of Months | 1542196.59 | 1107.20 | 2.62 | |
Maximum of Months | 0.107521E+10 | 1325.08 | 19.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10266360.97 | 336.06 | 16-JAN-16:00 | 2.20 |
February | 1337602.59 | 135.03 | 17-FEB-10:30 | 1.15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 1738973.59 | 150.59 | 30-NOV-14:50 | 4.90 |
December | 19183141.16 | 429.72 | 26-DEC-14:40 | 1.87 |
Annual Sum or Average | 32526078.31 | |||
Minimum of Months | 0.00 | 0.00 | 1.15 | |
Maximum of Months | 19183141.16 | 429.72 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135379E+10 | 1600.53 | 16-JAN-16:13 | 2.03 |
February | 0.844660E+09 | 1565.23 | 18-FEB-19:13 | -1.0 |
March | 0.477652E+09 | 1509.70 | 05-MAR-16:02 | 6.02 |
April | 0.195111E+09 | 1481.86 | 19-APR-08:62 | 5.87 |
May | 61790497.08 | 1402.40 | 18-MAY-08:62 | 6.28 |
June | 11843865.09 | 1261.52 | 02-JUN-08:03 | 14.08 |
July | 2242850.96 | 1134.64 | 10-JUL-08:03 | 14.08 |
August | 2466045.04 | 1033.95 | 04-AUG-08:03 | 13.03 |
September | 24858892.24 | 1376.76 | 18-SEP-15:03 | 16.10 |
October | 0.255397E+09 | 1459.72 | 27-OCT-15:02 | 10.82 |
November | 0.800281E+09 | 1587.52 | 30-NOV-16:13 | 4.60 |
December | 0.125157E+10 | 1608.99 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.528167E+10 | |||
Minimum of Months | 2242850.96 | 1033.95 | -1.0 | |
Maximum of Months | 0.135379E+10 | 1608.99 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153075E+10 | 1570.78 | 15-JAN-16:13 | 1.50 |
February | 0.103755E+10 | 1555.98 | 19-FEB-09:13 | -2.9 |
March | 0.607751E+09 | 1504.84 | 25-MAR-08:61 | 4.78 |
April | 0.244091E+09 | 1473.69 | 19-APR-08:62 | 5.87 |
May | 63996452.32 | 1380.63 | 18-MAY-08:62 | 6.28 |
June | 11422949.08 | 1056.28 | 27-JUN-08:53 | 17.80 |
July | 1662955.69 | 1003.43 | 15-JUL-08:04 | 15.78 |
August | 2129627.91 | 1096.74 | 04-AUG-08:03 | 13.03 |
September | 28604817.98 | 1424.47 | 28-SEP-08:62 | 10.28 |
October | 0.350278E+09 | 1446.88 | 30-OCT-08:62 | 7.30 |
November | 0.934005E+09 | 1551.84 | 30-NOV-16:13 | 4.60 |
December | 0.143542E+10 | 1571.42 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.624766E+10 | |||
Minimum of Months | 1662955.69 | 1003.43 | -2.9 | |
Maximum of Months | 0.153075E+10 | 1571.42 | 17.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383286E+09 | 848.23 | 13-JAN-16:13 | 2.93 |
February | 0.198789E+09 | 826.22 | 16-FEB-16:13 | 2.80 |
March | 74521374.31 | 794.24 | 05-MAR-16:02 | 6.02 |
April | 28931136.07 | 776.10 | 18-APR-08:62 | 4.50 |
May | 8400445.36 | 732.87 | 11-MAY-18:04 | 12.12 |
June | 2272873.47 | 794.96 | 07-JUN-08:03 | 11.88 |
July | 1392659.33 | 691.17 | 16-JUL-15:04 | 17.80 |
August | 1645174.72 | 624.39 | 18-AUG-18:04 | 19.45 |
September | 4052602.47 | 622.49 | 30-SEP-18:04 | 14.90 |
October | 24956786.50 | 768.32 | 27-OCT-15:02 | 10.82 |
November | 0.174100E+09 | 858.36 | 30-NOV-16:13 | 4.60 |
December | 0.356866E+09 | 871.32 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.125921E+10 | |||
Minimum of Months | 1392659.33 | 622.49 | 2.80 | |
Maximum of Months | 0.383286E+09 | 871.32 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15769329.39 | 350.92 | 15-JAN-05:00 | -2.8 |
February | 13113255.62 | 747.89 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 12140017.59 | 477.01 | 26-DEC-10:30 | 0.05 |
Annual Sum or Average | 41022602.61 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 15769329.39 | 747.89 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141930E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120632E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125166E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108886E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.103943E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.922157E+09 | 1701.53 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.985607E+09 | 1701.53 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106554E+10 | 1701.53 | 01-AUG-19:19 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.117377E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.132050E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.134594E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.142460E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142437E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.922157E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.142460E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954301E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.853979E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.941463E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.896188E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.921214E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.885814E+10 | 9504.80 | 01-JUN-19:30 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.914681E+10 | 9504.80 | 03-JUL-19:40 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.925746E+10 | 9504.80 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.903708E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.944307E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.922463E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.953034E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110169E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.853979E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.954301E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287054E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250957E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268827E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245393E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244131E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.226940E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.235884E+10 | 2988.03 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247234E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254653E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275942E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.275372E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.288189E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.310058E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.226940E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.288189E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287054E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250957E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268827E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245393E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244131E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.226940E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.235884E+10 | 2988.03 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247234E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254653E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275942E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.275372E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.288189E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.310058E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.226940E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.288189E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551502E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457147E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424165E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1547659.53 | 0.334016E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 607357.98 | 0.275680E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2105163.32 | 0.186088E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8843466.49 | 0.144005E+09 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16639269.99 | 0.120227E+09 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 189206.44 | 0.208010E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322871E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415409E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520740E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29932123.74 | 0.395986E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120227E+09 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16639269.99 | 0.551502E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219405E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184080E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175603E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 740568.66 | 0.142825E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235881.92 | 0.123069E+09 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 635089.13 | 89104920.13 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3220381.28 | 72360424.76 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6546306.16 | 62276846.33 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 136784.56 | 95787867.25 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138808E+09 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170520E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208465E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11515011.71 | 0.168231E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62276846.33 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6546306.16 | 0.219405E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502922E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415932E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388472E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434210.76 | 0.315106E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 958738.62 | 0.274928E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1881800.00 | 0.201234E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8024196.31 | 0.164360E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16069330.01 | 0.142824E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769539.30 | 0.214264E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307642E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383672E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473827E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30137815.01 | 0.378518E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142824E+09 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16069330.01 | 0.502922E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289627E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238774E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221217E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1438652.28 | 0.178052E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 611591.15 | 0.154379E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1210234.15 | 0.112207E+09 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4934209.91 | 90990635.52 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9756758.32 | 78717535.37 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501921.83 | 0.119437E+09 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173018E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219232E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272674E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18453367.64 | 0.214832E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78717535.37 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9756758.32 | 0.289627E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765293E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636311E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600108E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2263699.15 | 0.481725E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1146232.63 | 0.407936E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 2313855.68 | 0.291944E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 11940228.39 | 0.228698E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 23665964.51 | 0.195314E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 1358072.53 | 0.311394E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469581E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593069E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725736E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 42688052.90 | 0.570711E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195314E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 23665964.51 | 0.765293E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.141930E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124385E+10 |
February | 0.236489E+11 | 0.120632E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104527E+10 |
March | 0.262800E+11 | 0.125166E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990262E+09 |
April | 0.253579E+11 | 0.108886E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2987304.03 | 0.797200E+09 |
May | 0.262123E+11 | 0.103943E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 967126.23 | 0.675130E+09 |
June | 0.254132E+11 | 0.922157E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3528385.78 | 0.480183E+09 |
July | 0.261570E+11 | 0.985607E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18110218.47 | 0.384768E+09 |
August | 0.262677E+11 | 0.106554E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34794213.76 | 0.328947E+09 |
September | 0.253456E+11 | 0.117377E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309711.56 | 0.525473E+09 |
October | 0.261693E+11 | 0.132050E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775708E+09 |
November | 0.253025E+11 | 0.134594E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955725E+09 |
December | 0.261570E+11 | 0.142460E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117941E+10 |
Annual Sum or Average | 0.308468E+12 | 0.142437E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60696959.84 | 0.938193E+10 |
Minimum of Months | 0.236489E+11 | 0.922157E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328947E+09 |
Maximum of Months | 0.262800E+11 | 0.142460E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34794213.76 | 0.124385E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.954301E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367251E+10 |
February | 0.702046E+11 | 0.853979E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308797E+10 |
March | 0.780153E+11 | 0.941463E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294835E+10 |
April | 0.752779E+11 | 0.896188E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11008282.04 | 0.239541E+10 |
May | 0.778146E+11 | 0.921214E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3534024.96 | 0.205917E+10 |
June | 0.754422E+11 | 0.885814E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10030596.54 | 0.149767E+10 |
July | 0.776503E+11 | 0.914681E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52965699.69 | 0.120698E+10 |
August | 0.779788E+11 | 0.925746E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105004E+09 | 0.104076E+10 |
September | 0.752414E+11 | 0.903708E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1671104.85 | 0.160654E+10 |
October | 0.776868E+11 | 0.944307E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233889E+10 |
November | 0.751137E+11 | 0.922463E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286413E+10 |
December | 0.776503E+11 | 0.953034E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349183E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110169E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184214E+09 | 0.282102E+11 |
Minimum of Months | 0.702046E+11 | 0.853979E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104076E+10 |
Maximum of Months | 0.780153E+11 | 0.954301E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105004E+09 | 0.367251E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314914E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263296E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246614E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1327392.43 | 0.196856E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 784326.47 | 0.164026E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833329.47 | 0.112196E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7284766.76 | 83361402.76 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13804504.94 | 68874815.74 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1065056.63 | 0.119494E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3377.76 | 0.187450E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239161E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297721E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26102754.46 | 0.229396E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68874815.74 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13804504.94 | 0.314914E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312236E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259679E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243147E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285028.36 | 0.196257E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 329209.36 | 0.170424E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1208410.82 | 0.120877E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5932358.88 | 96916227.75 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12448644.26 | 77457671.16 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 421816.00 | 0.126481E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.24 | 0.185232E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236678E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294621E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21626601.92 | 0.232001E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77457671.16 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12448644.26 | 0.312236E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85520034.53 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84734383.32 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92914931.29 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7048.29 | 79597073.83 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71289363.54 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55669063.43 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187342.39 | 46969631.01 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 670479.39 | 41460726.05 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58258974.52 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78315721.36 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84306330.07 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88182250.09 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864870.07 | 0.867218E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41460726.05 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 670479.39 | 92914931.29 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89178276.61 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73797932.71 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68806122.41 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401059.16 | 54768963.75 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 126050.64 | 46066474.34 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 378752.00 | 32303491.93 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1764468.36 | 24710809.45 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3639524.38 | 20358423.44 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187369.82 | 33803801.67 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 354.29 | 52120089.22 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67659984.00 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84074805.57 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6497578.66 | 0.647649E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20358423.44 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3639524.38 | 89178276.61 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314664E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263447E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247700E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342265.04 | 0.198394E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 795078.93 | 0.164416E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852410.75 | 0.112922E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7335897.31 | 83693676.21 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13830558.09 | 69319902.62 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081286.25 | 0.119588E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4177.24 | 0.188075E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239045E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297387E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26241673.63 | 0.229865E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69319902.62 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13830558.09 | 0.314664E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312077E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259559E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244068E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291003.11 | 0.197613E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 353637.82 | 0.167301E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1259400.52 | 0.119431E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6002680.81 | 92489172.14 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12413192.40 | 77328887.74 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501777.39 | 0.123211E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1273.89 | 0.185436E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236414E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294253E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21822965.95 | 0.230918E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77328887.74 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12413192.40 | 0.312077E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387192E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319068E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296461E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1802454.60 | 0.238368E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704131.73 | 0.207206E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1540318.85 | 0.148932E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6445329.35 | 0.120139E+09 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12900804.67 | 0.103709E+09 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479417.83 | 0.158936E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229189E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291537E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364639E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23872457.03 | 0.286538E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103709E+09 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12900804.67 | 0.387192E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314110E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262744E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246480E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1295406.32 | 0.197376E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 740012.72 | 0.164804E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1768166.86 | 0.113049E+09 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7111805.73 | 84130363.71 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13514218.80 | 69449128.48 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1019718.08 | 0.120014E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.13 | 0.187428E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238502E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297239E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25451339.64 | 0.229532E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69449128.48 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13514218.80 | 0.314110E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312079E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259137E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242850E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248748.31 | 0.197057E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 307666.30 | 0.172796E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159934.98 | 0.123424E+09 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5804448.31 | 99958514.58 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12190207.88 | 78779744.96 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401637.86 | 0.128517E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 963.70 | 0.185026E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236008E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294234E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21113607.34 | 0.232987E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78779744.96 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12190207.88 | 0.312079E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164429E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137515E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128605E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 666696.75 | 0.102308E+09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 387022.73 | 84706676.61 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 915571.96 | 58019586.50 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3668283.91 | 43055620.63 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6939415.14 | 35622271.73 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526441.14 | 61941237.49 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489.69 | 97918480.49 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125062E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155303E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13103921.32 | 0.119449E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35622271.73 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6939415.14 | 0.164429E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.287054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902872E+09 |
February | 0.415303E+11 | 0.250957E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754673E+09 |
March | 0.461508E+11 | 0.268827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721114E+09 |
April | 0.445315E+11 | 0.245393E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1453026.35 | 0.587084E+09 |
May | 0.460320E+11 | 0.244131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83828.54 | 0.506977E+09 |
June | 0.446286E+11 | 0.226940E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 766922.90 | 0.372981E+09 |
July | 0.459349E+11 | 0.235884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8154884.69 | 0.298735E+09 |
August | 0.461292E+11 | 0.247234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18349802.24 | 0.256724E+09 |
September | 0.445099E+11 | 0.254653E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115888.12 | 0.393434E+09 |
October | 0.459565E+11 | 0.275942E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572230E+09 |
November | 0.444343E+11 | 0.275372E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708200E+09 |
December | 0.459349E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858711E+09 |
Annual Sum or Average | 0.541708E+12 | 0.310058E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 28924352.85 | 0.693373E+10 |
Minimum of Months | 0.415303E+11 | 0.226940E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256724E+09 |
Maximum of Months | 0.461508E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18349802.24 | 0.902872E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.287054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912384E+09 |
February | 0.415303E+11 | 0.250957E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762255E+09 |
March | 0.461508E+11 | 0.268827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727597E+09 |
April | 0.445315E+11 | 0.245393E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1427327.46 | 0.591507E+09 |
May | 0.460320E+11 | 0.244131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83820.17 | 0.509748E+09 |
June | 0.446286E+11 | 0.226940E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 766887.58 | 0.374943E+09 |
July | 0.459349E+11 | 0.235884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8105811.77 | 0.299973E+09 |
August | 0.461292E+11 | 0.247234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18154382.46 | 0.258123E+09 |
September | 0.445099E+11 | 0.254653E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115876.69 | 0.396133E+09 |
October | 0.459565E+11 | 0.275942E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577453E+09 |
November | 0.444343E+11 | 0.275372E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715631E+09 |
December | 0.459349E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867705E+09 |
Annual Sum or Average | 0.541708E+12 | 0.310058E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 28654106.14 | 0.699345E+10 |
Minimum of Months | 0.415303E+11 | 0.226940E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258123E+09 |
Maximum of Months | 0.461508E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18154382.46 | 0.912384E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818786E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682506E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649760E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1283671.97 | 0.526625E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 76915.48 | 0.453010E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 694163.42 | 0.333262E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7264911.99 | 0.266402E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16222622.80 | 0.229496E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 106299.21 | 0.352968E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515592E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640966E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778129E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 25648584.88 | 0.624750E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229496E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16222622.80 | 0.818786E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687713E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567977E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529719E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2256876.90 | 0.428278E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388624.33 | 0.371899E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237608.36 | 0.271630E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8298774.37 | 0.219363E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17994197.64 | 0.185584E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237671.14 | 0.283814E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407895E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519479E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648049E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30413752.75 | 0.512140E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185584E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17994197.64 | 0.687713E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.30 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 339.00 | 19-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 275.51 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.96 | 01-APR-17:00 | 243.90 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 | 05-MAY-16:00 | 206.21 | 11-MAY-03:30 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.85 | 28-JUN-17:00 | 155.02 | 15-JUN-03:40 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 24-JUL-15:00 | 120.51 | 07-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.20 | 10-AUG-17:00 | 122.77 | 01-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | 14-SEP-17:00 | 169.92 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 190.25 | 13-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 264.97 | 11-NOV-07:30 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 291.35 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 94.20 | 339.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 127.03 | 15-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 131.11 | 19-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 113.06 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 01-APR-16:00 | 99.83 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 05-MAY-16:00 | 87.49 | 11-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 28-JUN-17:00 | 67.70 | 15-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 | 24-JUL-15:00 | 57.57 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 | 29-AUG-16:00 | 58.26 | 01-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 22-SEP-16:00 | 73.00 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.13 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 107.18 | 11-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 114.32 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.57 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 | 131.11 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 294.95 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 309.29 | 19-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 256.46 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 | 01-APR-16:00 | 222.91 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 05-MAY-16:00 | 198.81 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.63 | 28-JUN-17:00 | 153.19 | 15-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.60 | 24-JUL-15:00 | 129.53 | 19-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.99 | 29-AUG-16:00 | 133.38 | 01-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 22-SEP-16:00 | 164.62 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182.56 | 13-OCT-05:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 241.68 | 11-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 265.74 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.53 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 85.99 | 309.29 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.17 | 15-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 178.44 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 145.44 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.86 | 01-APR-16:00 | 128.38 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 05-MAY-16:00 | 112.95 | 11-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | 28-JUN-17:00 | 86.88 | 15-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 | 24-JUL-15:00 | 73.51 | 19-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 29-AUG-16:00 | 75.13 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 22-SEP-16:00 | 93.28 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 103.78 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 139.44 | 11-NOV-07:30 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.32 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.51 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 178.44 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 451.16 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 459.76 | 19-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 390.66 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 71.01 | 01-APR-16:00 | 346.93 | 19-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 38.68 | 05-MAY-16:00 | 290.74 | 11-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 66.88 | 28-JUN-17:00 | 227.20 | 15-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 109.30 | 24-JUL-15:00 | 188.46 | 07-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 136.42 | 10-AUG-17:00 | 192.56 | 21-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 41.35 | 14-SEP-17:00 | 253.62 | 27-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 279.23 | 13-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 377.07 | 11-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 410.36 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 188.46 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 136.42 | 459.76 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 714.88 | 15-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 749.51 | 19-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 621.44 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 01-APR-16:00 | 567.59 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 05-MAY-16:00 | 493.29 | 11-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 | 28-JUN-17:00 | 381.80 | 15-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 | 24-JUL-15:00 | 324.14 | 19-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:19 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.55 | 10-AUG-17:00 | 324.14 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 14-SEP-17:00 | 410.76 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 467.50 | 13-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 594.90 | 11-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 644.03 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.14 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 205.55 | 749.51 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2121.97 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2189.23 | 19-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1882.63 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.22 | 01-APR-16:00 | 1690.93 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.10 | 05-MAY-16:00 | 1477.99 | 11-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:30 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.23 | 28-JUN-17:00 | 1155.05 | 15-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:40 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.42 | 24-JUL-15:00 | 976.25 | 19-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.93 | 10-AUG-17:00 | 969.83 | 01-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.64 | 22-SEP-16:00 | 1244.48 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1392.30 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1793.21 | 11-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1916.80 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.83 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 593.93 | 2189.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 188.81 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.92 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.02 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.77 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.05 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 80.12 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 154.89 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.05 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 188.79 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.03 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 79.40 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 80.39 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:09 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 154.88 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 51.35 | 15-JAN-08:10 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 55.82 | 09-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 52.79 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 27-APR-15:00 | 47.32 | 19-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 42.84 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 34.98 | 01-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 | 24-JUL-15:00 | 30.61 | 19-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 10-AUG-17:00 | 30.62 | 06-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 36.24 | 27-SEP-05:10 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 41.19 | 13-OCT-05:10 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 51.48 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 53.15 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 55.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 52.69 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 55.24 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 44.94 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27-APR-15:10 | 39.83 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 05-MAY-16:00 | 33.70 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 28-JUN-17:00 | 25.41 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 24-JUL-15:10 | 21.05 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 10-AUG-17:00 | 22.14 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 14-SEP-17:00 | 27.83 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 04-OCT-15:09 | 31.21 | 29-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 43.61 | 11-NOV-08:20 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 47.50 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 55.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 188.81 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.92 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.03 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.77 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 82.11 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 154.89 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 188.79 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.03 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.28 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 82.60 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:09 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 154.88 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.28 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.90 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 227.31 | 15-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 238.34 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 193.73 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.38 | 01-APR-16:00 | 171.57 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 | 05-MAY-16:00 | 152.39 | 11-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.81 | 28-JUN-17:00 | 116.40 | 15-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 24-JUL-15:00 | 97.57 | 19-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 29-AUG-16:00 | 99.45 | 01-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 22-SEP-16:00 | 123.90 | 27-SEP-04:40 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.04 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 186.32 | 11-NOV-07:30 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 204.83 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 238.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.30 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.39 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.50 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:50 | 143.17 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.22 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 28-JUN-17:00 | 91.48 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 24-JUL-15:10 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 78.40 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 14-SEP-17:00 | 100.15 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:10 | 111.97 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 155.36 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.69 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.39 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.29 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.49 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:10 | 143.15 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.21 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 28-JUN-17:00 | 91.47 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 | 24-JUL-15:10 | 88.11 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 78.89 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 14-SEP-17:00 | 100.14 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:09 | 111.96 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 155.35 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.68 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.89 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 96.85 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 101.51 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 82.63 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 27-APR-15:10 | 73.25 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 05-MAY-16:00 | 62.02 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 28-JUN-17:00 | 46.80 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 24-JUL-15:10 | 37.01 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 10-AUG-17:00 | 40.68 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 14-SEP-17:00 | 51.24 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 04-OCT-15:10 | 57.29 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 79.49 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 87.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 101.51 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 515.30 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 529.51 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 446.49 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.82 | 01-APR-16:00 | 401.22 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 05-MAY-16:00 | 346.78 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 | 28-JUN-17:00 | 273.27 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 | 24-JUL-15:00 | 224.20 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 10-AUG-17:00 | 226.05 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 14-SEP-17:00 | 294.85 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 323.89 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 430.94 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 469.25 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.20 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 529.51 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 515.31 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 533.73 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 446.49 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 27-APR-16:00 | 401.23 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 05-MAY-16:00 | 346.78 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 | 28-JUN-17:00 | 273.27 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 | 24-JUL-15:00 | 224.21 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 10-AUG-17:00 | 226.05 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 14-SEP-17:00 | 294.85 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 323.89 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 430.94 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 469.25 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.21 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 533.73 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 461.22 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 477.29 | 19-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 399.63 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 45.06 | 27-APR-15:40 | 357.80 | 19-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 13.32 | 05-MAY-16:00 | 299.92 | 11-MAY-03:30 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 38.05 | 28-JUN-17:00 | 236.60 | 15-JUN-03:30 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 93.28 | 24-JUL-15:00 | 200.72 | 07-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 109.57 | 10-AUG-17:00 | 201.77 | 06-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 13.35 | 14-SEP-17:00 | 260.96 | 27-SEP-05:10 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 289.96 | 13-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 385.73 | 11-NOV-07:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 420.01 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 200.72 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 109.57 | 477.29 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 403.25 | 15-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 422.73 | 19-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 343.78 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.03 | 01-APR-16:00 | 304.58 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | 05-MAY-16:00 | 262.70 | 11-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 | 28-JUN-17:00 | 201.22 | 15-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 24-JUL-15:00 | 171.26 | 19-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 10-AUG-17:00 | 174.36 | 01-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 22-SEP-16:00 | 213.14 | 27-SEP-04:03 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 239.99 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 330.68 | 11-NOV-07:50 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 363.47 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.26 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 422.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14283.64 | 11-JAN-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14130.61 | 01-FEB-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14162.32 | 25-MAR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14639.33 | 27-APR-18:10 | 53675.50 | 70347.97 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15088.79 | 14-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15501.86 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16105.61 | 30-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16339.25 | 13-AUG-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17602.31 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18898.63 | 06-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18717.74 | 08-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17623.89 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14130.61 | 8945.92 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18898.63 | 53675.50 | 70347.97 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2227.21 | 20-JAN-11:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.26 |
February | 2618.11 | 08-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.50 |
March | 3318.54 | 02-MAR-13:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.89 |
April | 3199.93 | 27-APR-13:05 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
May | 3069.82 | 04-MAY-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 |
June | 2559.02 | 28-JUN-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 |
July | 3044.11 | 31-JUL-13:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 40.93 | 0.00 |
August | 3869.38 | 24-AUG-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 0.00 |
September | 3957.64 | 14-SEP-13:15 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
October | 3966.63 | 04-OCT-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 |
November | 3228.33 | 04-NOV-13:30 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
December | 2496.05 | 05-DEC-11:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2227.21 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3966.63 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 217.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1121.51 | 11-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 |
February | 1234.10 | 27-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
March | 1259.85 | 14-MAR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.68 |
April | 1593.08 | 27-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 |
May | 1567.48 | 04-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 |
June | 1647.44 | 28-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
July | 1853.62 | 24-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
August | 2007.45 | 10-AUG-20:44 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 |
September | 1787.81 | 14-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 |
October | 1536.20 | 04-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 |
November | 1246.96 | 04-NOV-18:10 | 6320.16 | 3767.64 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 |
December | 1163.55 | 05-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1121.51 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | |
Maximum of Months | 2007.45 | 6320.16 | 3767.64 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 739.91 | 11-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.40 |
February | 814.69 | 27-FEB-19:10 | 891.07 | 2432.63 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 |
March | 815.60 | 18-MAR-18:10 | 1336.61 | 3724.96 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 |
April | 987.66 | 27-APR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 0.00 |
May | 1041.98 | 06-MAY-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 |
June | 1070.11 | 28-JUN-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 0.00 |
July | 1142.69 | 24-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
August | 1281.76 | 10-AUG-20:57 | 1018.37 | 2432.63 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
September | 1073.56 | 14-SEP-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.75 |
October | 962.57 | 04-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 |
November | 873.87 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 |
December | 746.63 | 03-DEC-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 739.91 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1281.76 | 1336.61 | 3724.96 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 115.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 410.98 | 11-JAN-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.11 |
February | 459.91 | 27-FEB-19:10 | 685.44 | 895.41 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 |
March | 465.91 | 18-MAR-18:10 | 1028.16 | 1371.08 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 |
April | 568.20 | 27-APR-18:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
May | 606.01 | 06-MAY-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
June | 616.99 | 28-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
July | 655.78 | 24-JUL-18:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | 0.00 |
August | 665.66 | 10-AUG-18:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 | 0.00 |
September | 620.76 | 14-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 |
October | 556.14 | 04-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 |
November | 503.12 | 04-NOV-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 |
December | 405.15 | 05-DEC-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 405.15 | 146.88 | 209.86 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 665.66 | 1028.16 | 1371.08 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 | 99.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36660.27 | 11-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 194.04 |
February | 37140.77 | 27-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 177.66 |
March | 37288.68 | 14-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 143.26 |
April | 38150.39 | 27-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 |
May | 38086.13 | 04-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
June | 38318.12 | 28-JUN-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
July | 38605.67 | 24-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
August | 38688.45 | 10-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
September | 38225.77 | 14-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.92 |
October | 37817.88 | 04-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 |
November | 37018.29 | 02-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 168.78 |
December | 36534.87 | 05-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 280.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36534.87 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38688.45 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 22.74 | 280.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9183.57 | 08-JAN-11:35 | 10245.60 | 249.56 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.44 |
February | 10546.63 | 08-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.77 |
March | 12450.81 | 02-MAR-13:20 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.79 |
April | 11652.16 | 27-APR-14:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 0.00 |
May | 11331.96 | 04-MAY-14:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 10641.89 | 28-JUN-18:10 | 71719.20 | 1996.46 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 | 0.00 |
July | 11378.16 | 30-JUL-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
August | 13318.77 | 24-AUG-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 140.58 | 0.00 |
September | 14009.16 | 23-SEP-13:15 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 |
October | 14026.07 | 04-OCT-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 |
November | 12622.81 | 04-NOV-13:30 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.77 |
December | 10278.73 | 02-DEC-11:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9183.57 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14026.07 | 71719.20 | 1996.46 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 140.58 | 602.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26030.65 | 11-JAN-22:00 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.28 |
February | 28155.75 | 27-FEB-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.46 |
March | 28620.94 | 14-MAR-20:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.70 |
April | 33782.30 | 27-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.61 |
May | 33911.68 | 04-MAY-21:52 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.68 |
June | 34789.69 | 28-JUN-21:52 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.84 |
July | 37813.45 | 24-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 |
August | 39352.68 | 10-AUG-21:05 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.06 |
September | 37442.64 | 14-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.20 |
October | 34606.62 | 04-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.94 |
November | 28843.13 | 04-NOV-10:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.03 |
December | 27064.21 | 03-DEC-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26030.65 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.06 | |
Maximum of Months | 39352.68 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2580.60 | 08-JAN-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.74 |
February | 3783.83 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.61 |
March | 3824.16 | 01-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 |
April | 3831.96 | 25-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
May | 3936.04 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
June | 3383.48 | 29-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 |
July | 3398.66 | 11-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
August | 3451.94 | 02-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
September | 3474.01 | 22-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
October | 3796.31 | 04-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
November | 3283.02 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
December | 3542.50 | 02-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2580.60 | 324.00 | 348.65 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | |
Maximum of Months | 3936.04 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 386.96 | 20-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.01 |
February | 2879.36 | 26-FEB-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 |
March | 3458.37 | 01-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.63 |
April | 3915.20 | 25-APR-17:41 | 777.60 | 953.34 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.05 |
May | 3917.11 | 21-MAY-17:41 | 777.60 | 1209.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.54 |
June | 3449.58 | 18-JUN-20:11 | 1386.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.83 |
July | 3699.25 | 25-JUL-16:51 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
August | 3530.05 | 06-AUG-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
September | 3586.59 | 22-SEP-16:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 |
October | 3108.89 | 08-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
November | 2993.38 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 |
December | 419.56 | 28-DEC-19:06 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 386.96 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3917.11 | 1386.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 114.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 111.24 | 08-JAN-15:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.80 |
February | 384.24 | 08-FEB-14:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 |
March | 560.39 | 02-MAR-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 |
April | 547.10 | 27-APR-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
May | 523.70 | 04-MAY-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
June | 397.30 | 28-JUN-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
July | 499.84 | 31-JUL-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
August | 628.06 | 24-AUG-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
September | 667.14 | 14-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
October | 692.91 | 04-OCT-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
November | 500.54 | 04-NOV-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 |
December | 312.26 | 05-DEC-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 111.24 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 692.91 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 39.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 775.73 | 01-JAN-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
February | 890.10 | 26-FEB-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 |
March | 997.39 | 28-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
April | 1040.53 | 24-APR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 |
May | 1098.27 | 14-MAY-21:51 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
June | 1015.16 | 22-JUN-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
July | 1029.74 | 29-JUL-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
August | 1032.54 | 06-AUG-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
September | 1014.41 | 11-SEP-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
October | 1026.40 | 04-OCT-21:12 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
November | 902.71 | 05-NOV-08:62 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 |
December | 955.13 | 03-DEC-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 775.73 | 270.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1098.27 | 1800.00 | 950.49 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 26.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 506.82 | 05-JAN-09:04 | 180.00 | 391.34 | 566.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 |
February | 3233.26 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
March | 3442.07 | 25-MAR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.03 |
April | 3438.71 | 19-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 |
May | 3505.71 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
June | 3107.44 | 11-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.04 |
July | 3172.22 | 15-JUL-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
August | 3227.17 | 25-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
September | 3148.17 | 22-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
October | 3437.13 | 04-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 |
November | 3148.77 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 |
December | 1705.57 | 02-DEC-09:02 | 270.00 | 498.07 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 506.82 | 180.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | |
Maximum of Months | 3505.71 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 376.89 | 10-JAN-19:06 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.97 |
February | 2313.59 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 |
March | 3104.71 | 25-MAR-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.35 |
April | 3088.62 | 25-APR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
May | 3378.59 | 06-MAY-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 |
June | 3222.66 | 10-JUN-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 |
July | 3672.00 | 24-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 |
August | 3588.47 | 10-AUG-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 |
September | 3340.68 | 13-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 |
October | 2912.87 | 07-OCT-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
November | 2491.73 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 |
December | 427.73 | 30-DEC-09:04 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.89 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | |
Maximum of Months | 3672.00 | 970.20 | 1108.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1562.93 | 11-JAN-21:00 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.62 |
February | 1771.61 | 27-FEB-19:10 | 7041.55 | 6639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 |
March | 1872.42 | 25-MAR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.96 |
April | 2227.72 | 27-APR-18:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 0.00 |
May | 2319.82 | 06-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 |
June | 2383.93 | 28-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
July | 2530.65 | 24-JUL-18:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 0.00 |
August | 2578.42 | 13-AUG-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 0.00 |
September | 2464.08 | 14-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 |
October | 2175.80 | 04-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 |
November | 1896.86 | 04-NOV-10:45 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 |
December | 1715.07 | 03-DEC-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1562.93 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2578.42 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 105.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2448.97 | 20-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.79 |
February | 3929.66 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.89 |
March | 3981.88 | 01-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.57 |
April | 3992.59 | 25-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.81 |
May | 4101.97 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
June | 3529.23 | 29-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 |
July | 3483.19 | 11-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
August | 3585.35 | 28-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 0.00 |
September | 3599.89 | 22-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 |
October | 3946.68 | 04-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
November | 3336.80 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
December | 3706.73 | 02-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2448.97 | 324.00 | 348.65 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4101.97 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 115.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 548.91 | 05-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
February | 2989.11 | 26-FEB-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 |
March | 3566.58 | 01-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.91 |
April | 4065.11 | 25-APR-17:41 | 777.60 | 953.34 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.83 |
May | 4061.41 | 21-MAY-17:41 | 777.60 | 1209.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.14 |
June | 3616.43 | 18-JUN-20:11 | 1386.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 |
July | 3818.48 | 21-JUL-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 |
August | 3893.32 | 06-AUG-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 |
September | 3707.41 | 22-SEP-16:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 |
October | 3168.56 | 08-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 |
November | 3088.58 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 |
December | 494.79 | 01-DEC-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 494.79 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | |
Maximum of Months | 4065.11 | 1800.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1917.11 | 09-JAN-16:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 |
February | 2437.32 | 12-FEB-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 |
March | 2463.53 | 25-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 |
April | 2367.57 | 13-APR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 |
May | 2454.70 | 14-MAY-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
June | 2190.68 | 23-JUN-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 |
July | 2217.05 | 11-JUL-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
August | 2222.37 | 17-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
September | 2235.72 | 23-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 |
October | 2426.82 | 04-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
November | 2154.30 | 05-NOV-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 |
December | 2403.88 | 03-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1917.11 | 378.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | |
Maximum of Months | 2463.53 | 970.20 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17856.16 | 11-JAN-22:50 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.35 |
February | 18919.82 | 27-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.84 |
March | 18795.69 | 10-MAR-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.70 |
April | 20684.48 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.21 |
May | 21031.30 | 05-MAY-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 |
June | 21480.93 | 28-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 |
July | 22244.75 | 24-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.46 |
August | 22237.50 | 10-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 |
September | 20931.61 | 12-SEP-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.79 |
October | 19750.74 | 04-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.77 |
November | 18888.48 | 06-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.97 |
December | 17606.40 | 29-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17606.40 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | |
Maximum of Months | 22244.75 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19923.81 | 11-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.06 |
February | 20743.25 | 27-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.84 |
March | 20733.17 | 08-MAR-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.27 |
April | 22206.65 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.21 |
May | 22531.06 | 05-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.17 |
June | 22828.67 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.59 |
July | 23504.29 | 24-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 |
August | 23446.53 | 10-AUG-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
September | 22276.70 | 12-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.31 |
October | 21288.87 | 04-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.78 |
November | 20765.38 | 06-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.97 |
December | 19644.76 | 29-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19644.76 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | |
Maximum of Months | 23504.29 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26421.79 | 30-JAN-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 246.98 |
February | 27590.05 | 27-FEB-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 118.71 |
March | 28726.98 | 14-MAR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 200.26 |
April | 30139.38 | 27-APR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 |
May | 30251.25 | 14-MAY-10:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 |
June | 30520.85 | 10-JUN-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 55.13 |
July | 31019.33 | 24-JUL-10:37 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.50 | 0.00 |
August | 31068.02 | 13-AUG-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
September | 30403.20 | 10-SEP-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 81.95 |
October | 29263.19 | 04-OCT-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 |
November | 28791.07 | 04-NOV-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 99.19 |
December | 26935.35 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 192.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26421.79 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31068.02 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.50 | 246.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3236.64 | 20-JAN-11:35 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.27 |
February | 3712.95 | 27-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 |
March | 3922.95 | 18-MAR-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 |
April | 4771.78 | 27-APR-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 0.00 |
May | 4912.35 | 06-MAY-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 |
June | 5078.55 | 28-JUN-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 0.00 |
July | 5361.51 | 24-JUL-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 0.00 |
August | 6189.32 | 10-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 | 0.00 |
September | 5065.87 | 14-SEP-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.81 |
October | 4504.50 | 04-OCT-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
November | 4016.37 | 04-NOV-10:50 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.59 |
December | 3563.16 | 03-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3236.64 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6189.32 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 | 240.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.361833E+12 | 235675.23 | 02-JAN-20:10 | 0.580066E+12 | 559558.93 | 25-JAN-18:30 |
February | 0.325008E+12 | 238898.81 | 27-FEB-20:10 | 0.532904E+12 | 533108.53 | 04-FEB-18:49 |
March | 0.359625E+12 | 245170.14 | 14-MAR-19:10 | 0.592286E+12 | 566943.26 | 22-MAR-17:00 |
April | 0.359320E+12 | 303612.69 | 27-APR-18:10 | 0.560724E+12 | 536059.66 | 18-APR-17:30 |
May | 0.383323E+12 | 287671.06 | 04-MAY-19:19 | 0.546068E+12 | 497855.28 | 23-MAY-20:10 |
June | 0.390709E+12 | 311240.32 | 28-JUN-19:10 | 0.463676E+12 | 434932.50 | 13-JUN-21:30 |
July | 0.435844E+12 | 335322.38 | 24-JUL-19:49 | 0.430119E+12 | 363731.31 | 04-JUL-20:00 |
August | 0.456728E+12 | 354250.08 | 10-AUG-19:30 | 0.424772E+12 | 349551.82 | 31-AUG-17:10 |
September | 0.388145E+12 | 286712.45 | 15-SEP-19:10 | 0.464123E+12 | 443597.91 | 27-SEP-20:00 |
October | 0.364520E+12 | 265246.73 | 04-OCT-19:00 | 0.605896E+12 | 500173.19 | 31-OCT-18:10 |
November | 0.347302E+12 | 238568.66 | 03-NOV-19:00 | 0.573508E+12 | 546381.99 | 21-NOV-18:30 |
December | 0.361594E+12 | 235359.67 | 14-DEC-20:19 | 0.581367E+12 | 555988.59 | 16-DEC-18:00 |
Annual Sum or Average | 0.453395E+13 | 0.635551E+13 | ||||
Minimum of Months | 0.325008E+12 | 235359.67 | 0.424772E+12 | 349551.82 | ||
Maximum of Months | 0.456728E+12 | 354250.08 | 0.605896E+12 | 566943.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.673876E+11 | 0.210395E+11 | 0.140828E+12 | 0.544240E+11 | 0.401904E+11 | 0.196961E+10 | 0.00 | 0.635071E+09 | 0.00 | 0.00 | 0.224379E+11 | 0.770490E+10 | 0.00 |
February | 0.605329E+11 | 0.173454E+11 | 0.127191E+12 | 0.491571E+11 | 0.362196E+11 | 0.302768E+10 | 0.00 | 0.340153E+10 | 0.00 | 0.00 | 0.164568E+11 | 0.696242E+10 | 0.00 |
March | 0.666248E+11 | 0.169308E+11 | 0.140882E+12 | 0.544262E+11 | 0.403193E+11 | 0.478487E+10 | 0.00 | 0.879090E+10 | 0.00 | 0.00 | 0.139343E+11 | 0.770344E+10 | 0.00 |
April | 0.639899E+11 | 0.141028E+11 | 0.136245E+12 | 0.526675E+11 | 0.400415E+11 | 0.614263E+10 | 0.00 | 0.249021E+11 | 0.00 | 0.00 | 0.869419E+10 | 0.746516E+10 | 0.00 |
May | 0.657725E+11 | 0.125260E+11 | 0.140860E+12 | 0.544244E+11 | 0.427005E+11 | 0.709716E+10 | 0.00 | 0.419612E+11 | 0.00 | 0.00 | 0.500488E+10 | 0.770468E+10 | 0.00 |
June | 0.632910E+11 | 0.110232E+11 | 0.136336E+12 | 0.526694E+11 | 0.425460E+11 | 0.687437E+10 | 0.00 | 0.627288E+11 | 0.00 | 0.00 | 0.266181E+10 | 0.745695E+10 | 0.00 |
July | 0.655509E+11 | 0.118967E+11 | 0.140770E+12 | 0.544217E+11 | 0.453991E+11 | 0.704916E+10 | 0.00 | 0.940422E+11 | 0.00 | 0.00 | 0.371422E+10 | 0.771264E+10 | 0.00 |
August | 0.658601E+11 | 0.136587E+11 | 0.140892E+12 | 0.544257E+11 | 0.459825E+11 | 0.709941E+10 | 0.00 | 0.110415E+12 | 0.00 | 0.00 | 0.535548E+10 | 0.770442E+10 | 0.00 |
September | 0.643518E+11 | 0.153910E+11 | 0.136256E+12 | 0.526678E+11 | 0.422126E+11 | 0.675181E+10 | 0.00 | 0.555259E+11 | 0.00 | 0.00 | 0.237692E+10 | 0.746646E+10 | 0.00 |
October | 0.669530E+11 | 0.182634E+11 | 0.140818E+12 | 0.544238E+11 | 0.412281E+11 | 0.601830E+10 | 0.00 | 0.187159E+11 | 0.00 | 0.00 | 0.513420E+10 | 0.770324E+10 | 0.00 |
November | 0.651190E+11 | 0.197440E+11 | 0.136330E+12 | 0.526691E+11 | 0.390274E+11 | 0.332901E+10 | 0.00 | 0.453715E+10 | 0.00 | 0.00 | 0.140246E+11 | 0.744929E+10 | 0.00 |
December | 0.674225E+11 | 0.215799E+11 | 0.140770E+12 | 0.544229E+11 | 0.402046E+11 | 0.217779E+10 | 0.00 | 0.106097E+10 | 0.00 | 0.00 | 0.210185E+11 | 0.771301E+10 | 0.00 |
Annual Sum or Average | 0.782856E+12 | 0.193501E+12 | 0.165818E+13 | 0.640800E+12 | 0.496071E+12 | 0.623218E+11 | 0.00 | 0.426717E+12 | 0.00 | 0.00 | 0.120814E+12 | 0.907466E+11 | 0.00 |
Minimum of Months | 0.605329E+11 | 0.110232E+11 | 0.127191E+12 | 0.491571E+11 | 0.362196E+11 | 0.196961E+10 | 0.00 | 0.635071E+09 | 0.00 | 0.00 | 0.237692E+10 | 0.696242E+10 | 0.00 |
Maximum of Months | 0.674225E+11 | 0.215799E+11 | 0.140892E+12 | 0.544262E+11 | 0.459825E+11 | 0.709941E+10 | 0.00 | 0.110415E+12 | 0.00 | 0.00 | 0.224379E+11 | 0.771301E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.148052E+12 | 0.00 | 0.280096E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.141464E+12 | 0.00 | 0.254236E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.160864E+12 | 0.00 | 0.279399E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.148406E+12 | 0.00 | 0.265362E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.126678E+12 | 0.00 | 0.267411E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.641722E+11 | 0.00 | 0.252390E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.222369E+11 | 0.00 | 0.256062E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.180502E+11 | 0.00 | 0.254683E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.686095E+11 | 0.00 | 0.248542E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.191957E+12 | 0.00 | 0.262036E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.166255E+12 | 0.00 | 0.260162E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.154104E+12 | 0.00 | 0.275442E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.141085E+13 | 0.00 | 0.315582E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.180502E+11 | 0.00 | 0.248542E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.191957E+12 | 0.00 | 0.280096E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 21857.97 | 13-JAN-19:10 | 3198.59 | 03-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 21999.50 | 27-FEB-21:19 | 3203.15 | 07-FEB-17:19 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 23101.05 | 18-MAR-20:49 | 3199.23 | 02-MAR-10:20 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.68 | 04-APR-06:19 | 27703.64 | 27-APR-21:00 | 3188.04 | 06-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39169.57 | 01-MAY-06:19 | 28926.01 | 15-MAY-21:30 | 3177.57 | 18-MAY-09:09 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.59 | 22-JUN-06:19 | 28874.89 | 28-JUN-21:00 | 3130.95 | 20-JUN-18:30 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 10-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.59 | 10-JUL-06:19 | 30216.90 | 31-JUL-21:00 | 3272.73 | 31-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:19 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39169.28 | 16-AUG-06:19 | 31040.20 | 24-AUG-21:00 | 3400.93 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 06-SEP-06:19 | 30762.29 | 13-SEP-21:00 | 3144.22 | 08-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 28716.75 | 04-OCT-21:19 | 3201.95 | 13-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 22917.81 | 06-NOV-21:00 | 3222.28 | 11-NOV-11:50 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 22132.87 | 26-DEC-19:10 | 3210.80 | 13-DEC-09:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.59 | 21857.97 | 3130.95 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 31040.20 | 3400.93 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6292.73 | 11-JAN-19:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.69 | 02-JAN-19:10 | 0.00 |
February | 49579.81 | 27-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.32 | 23-FEB-07:10 | 0.00 |
March | 58784.05 | 18-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.21 | 20-MAR-18:10 | 0.00 |
April | 99235.83 | 27-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.26 | 21-APR-06:10 | 0.00 |
May | 87701.15 | 04-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 03-MAY-03:49 | 4738.42 | 24-MAY-18:10 | 0.00 |
June | 96915.34 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 09-JUN-15:00 | 4738.31 | 30-JUN-18:30 | 0.00 |
July | 120072.53 | 24-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 07-JUL-12:09 | 4738.31 | 24-JUL-06:40 | 0.00 |
August | 136223.38 | 10-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 06-AUG-15:00 | 4738.52 | 02-AUG-18:19 | 0.00 |
September | 95697.60 | 14-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 08-SEP-16:00 | 4738.33 | 22-SEP-06:19 | 0.00 |
October | 73723.43 | 04-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 03-OCT-04:00 | 4738.30 | 20-OCT-06:10 | 0.00 |
November | 66425.41 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 08-NOV-22:10 | 4738.31 | 29-NOV-19:10 | 0.00 |
December | 10969.37 | 05-DEC-12:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.73 | 04-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6292.73 | 0.00 | 0.00 | 9938.94 | 4738.21 | 0.00 | |||
Maximum of Months | 136223.38 | 0.00 | 0.00 | 9938.94 | 4738.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 235675.23 | 02-JAN-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20354.00 | 2692.96 | 0.00 | 1571.08 | 0.00 |
February | 238898.81 | 27-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21801.64 | 2526.17 | 0.00 | 11798.43 | 0.00 |
March | 245170.14 | 14-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 21672.71 | 2542.33 | 0.00 | 20550.39 | 0.00 |
April | 303612.69 | 27-APR-18:10 | 53578.21 | 77573.37 | 0.00 | 31342.09 | 24261.68 | 3103.96 | 0.00 | 96901.74 | 0.00 |
May | 287671.06 | 04-MAY-19:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21877.06 | 2792.52 | 0.00 | 61768.61 | 0.00 |
June | 311240.32 | 28-JUN-19:10 | 60692.03 | 86439.81 | 0.00 | 31544.04 | 24712.56 | 3036.56 | 0.00 | 88515.32 | 0.00 |
July | 335322.38 | 24-JUL-19:49 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 26030.48 | 3091.68 | 0.00 | 94877.69 | 0.00 |
August | 354250.08 | 10-AUG-19:30 | 64632.59 | 86439.81 | 12338.45 | 31552.79 | 26848.94 | 3211.26 | 0.00 | 113008.53 | 0.00 |
September | 286712.45 | 15-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23755.53 | 2678.30 | 0.00 | 59854.73 | 0.00 |
October | 265246.73 | 04-OCT-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 22814.58 | 2554.33 | 0.00 | 38856.54 | 0.00 |
November | 238568.66 | 03-NOV-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 21058.36 | 2537.79 | 0.00 | 14480.07 | 0.00 |
December | 235359.67 | 14-DEC-20:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 20139.36 | 2648.83 | 0.00 | 1297.10 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 235359.67 | 53578.21 | 77573.37 | 0.00 | 31342.09 | 20139.36 | 2526.17 | 0.00 | 1297.10 | 0.00 | |
Maximum of Months | 354250.08 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 26848.94 | 3211.26 | 0.00 | 113008.53 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 197600.97 | 20-JAN-11:50 | 0.00 | 283537.62 | 31-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 197042.70 | 07-FEB-11:50 | 0.00 | 283730.80 | 10-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 196300.01 | 22-MAR-17:40 | 0.00 | 282605.27 | 09-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 187681.05 | 24-APR-22:40 | 0.00 | 274516.28 | 13-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 182055.57 | 18-MAY-09:20 | 0.00 | 256602.68 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 163447.33 | 15-JUN-02:00 | 0.00 | 247486.77 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 91393.98 | 03-JUL-03:00 | 0.00 | 246389.96 | 05-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 95108.43 | 21-AUG-04:00 | 0.00 | 245882.22 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 171610.42 | 27-SEP-03:09 | 0.00 | 246625.99 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 198674.64 | 30-OCT-08:09 | 0.00 | 247636.03 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 213393.23 | 11-NOV-11:50 | 0.00 | 270710.41 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 203681.62 | 09-DEC-11:50 | 0.00 | 280373.80 | 27-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 91393.98 | 0.00 | 245882.22 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 213393.23 | 0.00 | 283730.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.47 | 2.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.17 | 20.52 | 1.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
November | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 3.17 | 20.47 | 3.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 7.83 | 20.48 | 7.83 | 20.48 | 3.00 | 20.68 | 3.00 | 20.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.52 | 3.17 | 20.52 | 1.33 | 21.77 | 1.33 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.47 | 6.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 2.17 | 20.47 | 2.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.04 | 1.17 | 22.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.88 | 2.17 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.99 | 0.17 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.49 | 1.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 4.67 | 20.46 | 4.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 14.67 | 20.47 | 14.67 | 20.47 | 5.33 | 20.69 | 5.33 | 20.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.49 | 6.50 | 20.49 | 2.17 | 22.04 | 2.17 | 22.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.77 | 3.00 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.81 | 4.17 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.72 | 1.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 0.17 | 20.51 | 0.17 | 20.51 | 9.83 | 21.74 | 9.83 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.51 | 0.17 | 20.51 | 4.17 | 21.81 | 4.17 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.48 | 3.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.33 | 20.52 | 1.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.49 | 1.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 3.50 | 20.47 | 3.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 9.00 | 20.48 | 9.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.52 | 3.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 20.45 | 7.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 2.17 | 20.47 | 2.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.26 | 0.17 | 22.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.93 | 0.33 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.42 | 0.67 | 22.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.38 | 2.17 | 22.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.34 | 3.00 | 22.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.19 | 0.33 | 22.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 5.83 | 20.46 | 5.83 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 16.83 | 20.46 | 16.83 | 20.46 | 6.67 | 20.77 | 6.67 | 20.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 20.48 | 7.17 | 20.48 | 3.00 | 22.42 | 3.00 | 22.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.51 | 2.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
November | 0.67 | 20.52 | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 2.67 | 20.48 | 2.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 6.33 | 20.50 | 6.33 | 20.50 | 6.00 | 20.91 | 6.00 | 21.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.54 | 2.67 | 20.54 | 2.67 | 21.86 | 2.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 20.49 | 5.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 2.50 | 20.52 | 2.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.01 | 2.50 | 22.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.91 | 2.17 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.91 | 4.33 | 21.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.78 | 2.83 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.16 | 0.17 | 22.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 4.83 | 20.49 | 4.83 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 13.83 | 20.49 | 13.83 | 20.49 | 12.00 | 20.92 | 12.00 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 20.52 | 5.67 | 20.52 | 4.33 | 22.16 | 4.33 | 22.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.68 | 0.67 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.86 | 0.17 | 21.86 |
November | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 1.50 | 20.49 | 1.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 2.50 | 20.49 | 2.50 | 20.49 | 1.83 | 20.82 | 1.83 | 21.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.50 | 1.50 | 20.50 | 1.00 | 21.86 | 1.00 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.33 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
February | 672.00 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
March | 744.00 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
April | 720.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
May | 744.00 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
June | 719.50 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
July | 684.67 | 23.19 | 0.83 | 23.19 | 0.00 | 23.19 |
August | 506.83 | 23.26 | 14.17 | 23.28 | 0.00 | 23.28 |
September | 387.17 | 23.40 | 31.17 | 23.45 | 0.00 | 23.45 |
October | 477.67 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
November | 513.00 | 23.64 | 11.50 | 23.65 | 0.00 | 23.65 |
December | 719.17 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 7630.33 | 23.17 | 57.67 | 23.17 | 0.00 | 23.17 |
Minimum of Months | 387.17 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 744.00 | 23.64 | 31.17 | 23.65 | 0.00 | 23.65 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.50 | 21.03 | 220.00 | 21.02 | 220.00 | 21.02 |
February | 654.33 | 21.09 | 134.83 | 21.10 | 127.33 | 21.09 |
March | 715.67 | 21.14 | 25.00 | 21.20 | 10.50 | 21.19 |
April | 680.00 | 21.24 | 21.50 | 21.32 | 0.00 | 21.32 |
May | 692.50 | 21.31 | 28.67 | 21.40 | 0.00 | 21.40 |
June | 679.00 | 21.39 | 14.50 | 21.44 | 0.00 | 21.44 |
July | 617.83 | 21.58 | 74.83 | 21.79 | 0.00 | 21.79 |
August | 562.33 | 21.56 | 123.00 | 21.94 | 0.00 | 21.94 |
September | 589.33 | 21.36 | 92.33 | 21.69 | 0.00 | 21.69 |
October | 685.00 | 21.19 | 34.83 | 21.32 | 0.00 | 21.32 |
November | 708.17 | 21.05 | 38.33 | 21.06 | 33.00 | 21.06 |
December | 737.33 | 21.06 | 188.50 | 21.05 | 188.00 | 21.04 |
Annual Sum or Average | 8063.00 | 21.24 | 996.33 | 21.34 | 578.83 | 21.32 |
Minimum of Months | 562.33 | 21.03 | 14.50 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 741.50 | 21.58 | 220.00 | 21.94 | 220.00 | 21.94 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
February | 672.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
March | 744.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
April | 698.00 | 22.45 | 1.50 | 22.46 | 0.00 | 22.46 |
May | 692.83 | 22.71 | 5.67 | 22.72 | 0.00 | 22.72 |
June | 614.83 | 22.81 | 13.50 | 22.84 | 0.00 | 22.84 |
July | 468.67 | 22.95 | 101.67 | 23.13 | 0.00 | 23.13 |
August | 370.50 | 22.87 | 166.50 | 23.19 | 0.00 | 23.19 |
September | 522.50 | 22.78 | 62.33 | 22.91 | 0.00 | 22.91 |
October | 727.33 | 22.48 | 0.00 | 22.48 | 0.00 | 22.48 |
November | 718.83 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
December | 744.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
Annual Sum or Average | 7717.50 | 22.29 | 351.17 | 22.36 | 0.00 | 22.36 |
Minimum of Months | 370.50 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
Maximum of Months | 744.00 | 22.95 | 166.50 | 23.19 | 0.00 | 23.19 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 23.33 | 21.03 | 23.33 | 21.03 |
February | 672.00 | 21.12 | 27.67 | 21.12 | 27.67 | 21.11 |
March | 744.00 | 21.29 | 11.33 | 21.29 | 11.33 | 21.28 |
April | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 744.00 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
June | 720.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
July | 717.00 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
August | 664.50 | 23.04 | 2.17 | 23.05 | 0.00 | 23.05 |
September | 712.67 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
October | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
November | 720.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
December | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Annual Sum or Average | 8646.17 | 21.88 | 64.50 | 21.88 | 62.33 | 21.87 |
Minimum of Months | 664.50 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 23.04 | 27.67 | 23.05 | 27.67 | 23.05 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 54.67 | 21.00 | 54.67 | 21.00 |
February | 672.00 | 21.04 | 56.00 | 21.04 | 56.00 | 21.04 |
March | 744.00 | 21.12 | 15.33 | 21.12 | 15.33 | 21.12 |
April | 720.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
May | 744.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
June | 720.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
July | 739.33 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
August | 728.17 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
September | 720.00 | 22.33 | 0.00 | 22.33 | 0.00 | 22.33 |
October | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
November | 720.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
December | 744.00 | 21.00 | 4.67 | 21.00 | 4.67 | 21.00 |
Annual Sum or Average | 8739.50 | 21.72 | 130.67 | 21.71 | 130.67 | 21.70 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.86 | 56.00 | 22.86 | 56.00 | 22.86 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.67 | 22.85 | 519.17 | 23.25 | 146.17 | 23.37 |
February | 228.17 | 22.97 | 488.33 | 23.29 | 145.17 | 23.41 |
March | 251.50 | 23.09 | 584.67 | 23.30 | 172.67 | 23.42 |
April | 258.50 | 23.31 | 602.67 | 23.33 | 196.67 | 23.45 |
May | 292.17 | 23.52 | 643.50 | 23.37 | 243.50 | 23.50 |
June | 293.83 | 23.72 | 638.17 | 23.42 | 265.17 | 23.55 |
July | 299.00 | 23.86 | 678.83 | 23.44 | 285.00 | 23.56 |
August | 307.67 | 23.91 | 696.33 | 23.42 | 299.50 | 23.55 |
September | 298.17 | 23.76 | 649.67 | 23.42 | 273.50 | 23.55 |
October | 278.50 | 23.38 | 634.50 | 23.35 | 219.33 | 23.48 |
November | 252.50 | 23.17 | 581.67 | 23.30 | 180.33 | 23.43 |
December | 238.67 | 22.90 | 553.17 | 23.25 | 146.50 | 23.37 |
Annual Sum or Average | 3247.33 | 23.40 | 7270.67 | 23.35 | 2573.50 | 23.48 |
Minimum of Months | 228.17 | 22.85 | 488.33 | 23.25 | 145.17 | 23.37 |
Maximum of Months | 307.67 | 23.91 | 696.33 | 23.44 | 299.50 | 23.56 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.17 | 21.36 | 10.00 | 21.36 | 7.67 | 21.36 |
February | 638.17 | 21.59 | 16.67 | 21.64 | 1.33 | 21.64 |
March | 694.00 | 21.85 | 24.50 | 21.92 | 0.00 | 21.92 |
April | 621.17 | 22.03 | 47.50 | 22.15 | 0.00 | 22.15 |
May | 599.83 | 22.16 | 65.67 | 22.29 | 0.00 | 22.29 |
June | 528.67 | 22.26 | 69.00 | 22.40 | 0.00 | 22.40 |
July | 353.67 | 22.32 | 233.17 | 22.77 | 2.00 | 22.78 |
August | 346.17 | 22.33 | 321.33 | 22.96 | 25.67 | 22.99 |
September | 419.83 | 22.13 | 214.33 | 22.66 | 0.17 | 22.66 |
October | 621.00 | 22.00 | 63.67 | 22.17 | 0.00 | 22.17 |
November | 699.67 | 21.57 | 14.67 | 21.61 | 1.33 | 21.62 |
December | 725.00 | 21.42 | 13.17 | 21.44 | 7.00 | 21.43 |
Annual Sum or Average | 6983.33 | 21.85 | 1093.67 | 22.09 | 45.17 | 22.09 |
Minimum of Months | 346.17 | 21.36 | 10.00 | 21.36 | 0.00 | 21.36 |
Maximum of Months | 736.17 | 22.33 | 321.33 | 22.96 | 25.67 | 22.99 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
February | 666.83 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
March | 732.33 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
April | 635.67 | 22.68 | 13.33 | 22.70 | 0.00 | 22.70 |
May | 561.67 | 22.78 | 38.33 | 22.85 | 0.00 | 22.85 |
June | 438.17 | 22.77 | 97.17 | 22.98 | 0.00 | 22.98 |
July | 273.00 | 22.82 | 236.33 | 23.31 | 0.67 | 23.31 |
August | 215.33 | 22.84 | 364.67 | 23.46 | 24.67 | 23.48 |
September | 309.83 | 22.70 | 208.83 | 23.15 | 2.00 | 23.16 |
October | 624.67 | 22.68 | 10.00 | 22.70 | 0.00 | 22.70 |
November | 700.00 | 22.26 | 4.00 | 22.26 | 1.67 | 22.27 |
December | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
Annual Sum or Average | 6645.50 | 22.44 | 972.67 | 22.62 | 29.00 | 22.63 |
Minimum of Months | 215.33 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
Maximum of Months | 744.00 | 22.84 | 364.67 | 23.46 | 24.67 | 23.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.73 | 506.17 | 20.65 | 506.17 | 20.62 |
February | 670.83 | 21.00 | 256.33 | 20.89 | 256.33 | 20.82 |
March | 742.00 | 21.21 | 59.17 | 21.16 | 59.17 | 21.10 |
April | 706.50 | 21.43 | 2.67 | 21.42 | 2.33 | 21.42 |
May | 708.83 | 21.51 | 1.17 | 21.52 | 0.00 | 21.52 |
June | 685.83 | 21.57 | 0.83 | 21.57 | 0.00 | 21.57 |
July | 664.17 | 21.50 | 11.33 | 21.53 | 0.00 | 21.53 |
August | 664.33 | 21.50 | 15.50 | 21.54 | 0.00 | 21.54 |
September | 663.67 | 21.44 | 6.17 | 21.46 | 0.00 | 21.46 |
October | 735.00 | 21.32 | 3.17 | 21.31 | 3.17 | 21.31 |
November | 718.00 | 20.93 | 205.00 | 20.82 | 205.00 | 20.75 |
December | 744.00 | 20.81 | 433.33 | 20.70 | 433.33 | 20.65 |
Annual Sum or Average | 8447.17 | 21.24 | 1500.83 | 21.14 | 1465.50 | 21.06 |
Minimum of Months | 663.67 | 20.73 | 0.83 | 20.65 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.57 | 506.17 | 21.57 | 506.17 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 590.33 | 20.53 | 590.33 | 20.51 |
February | 672.00 | 20.79 | 382.33 | 20.70 | 382.33 | 20.65 |
March | 744.00 | 21.04 | 124.67 | 20.95 | 124.67 | 20.89 |
April | 704.50 | 21.37 | 8.33 | 21.40 | 3.17 | 21.39 |
May | 667.33 | 21.65 | 51.33 | 21.96 | 7.83 | 22.02 |
June | 627.17 | 21.81 | 51.50 | 22.10 | 3.00 | 22.12 |
July | 586.67 | 22.00 | 108.33 | 22.57 | 21.33 | 22.72 |
August | 624.33 | 21.88 | 53.83 | 22.14 | 5.17 | 22.18 |
September | 619.00 | 21.64 | 52.67 | 21.92 | 3.50 | 21.95 |
October | 740.50 | 21.21 | 13.50 | 21.20 | 11.83 | 21.18 |
November | 720.00 | 20.81 | 296.33 | 20.70 | 296.33 | 20.64 |
December | 744.00 | 20.64 | 577.50 | 20.59 | 577.50 | 20.57 |
Annual Sum or Average | 8193.50 | 21.25 | 2310.67 | 21.24 | 2027.00 | 21.14 |
Minimum of Months | 586.67 | 20.59 | 8.33 | 20.53 | 3.00 | 20.51 |
Maximum of Months | 744.00 | 22.00 | 590.33 | 22.57 | 590.33 | 22.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 176.00 | 20.90 | 176.00 | 20.85 |
February | 672.00 | 21.07 | 121.83 | 21.01 | 121.83 | 20.97 |
March | 744.00 | 21.22 | 6.00 | 21.21 | 6.00 | 21.21 |
April | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 744.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
June | 719.50 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
July | 733.33 | 22.00 | 0.17 | 22.00 | 0.00 | 22.00 |
August | 743.33 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
September | 720.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
October | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
November | 720.00 | 21.12 | 33.83 | 21.09 | 33.83 | 21.06 |
December | 744.00 | 20.99 | 101.17 | 20.91 | 101.17 | 20.85 |
Annual Sum or Average | 8748.17 | 21.44 | 439.00 | 21.40 | 438.83 | 21.36 |
Minimum of Months | 672.00 | 20.97 | 0.00 | 20.90 | 0.00 | 20.85 |
Maximum of Months | 744.00 | 22.00 | 176.00 | 22.00 | 176.00 | 22.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.71 | 506.00 | 20.64 | 506.00 | 20.61 |
February | 672.00 | 21.01 | 253.33 | 20.90 | 253.33 | 20.85 |
March | 744.00 | 21.28 | 44.83 | 21.23 | 44.83 | 21.18 |
April | 711.83 | 21.53 | 1.67 | 21.52 | 1.67 | 21.52 |
May | 712.67 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 677.50 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
July | 668.00 | 21.53 | 1.00 | 21.53 | 0.00 | 21.53 |
August | 652.33 | 21.49 | 1.83 | 21.49 | 0.00 | 21.49 |
September | 663.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
October | 741.00 | 21.37 | 2.83 | 21.36 | 2.83 | 21.36 |
November | 720.00 | 20.93 | 212.50 | 20.82 | 212.50 | 20.76 |
December | 744.00 | 20.79 | 435.50 | 20.70 | 435.50 | 20.65 |
Annual Sum or Average | 8450.33 | 21.26 | 1459.50 | 21.15 | 1456.67 | 21.07 |
Minimum of Months | 652.33 | 20.71 | 0.00 | 20.64 | 0.00 | 20.61 |
Maximum of Months | 744.00 | 21.59 | 506.00 | 21.59 | 506.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.58 | 589.33 | 20.52 | 589.33 | 20.50 |
February | 672.00 | 20.78 | 394.00 | 20.70 | 394.00 | 20.66 |
March | 744.00 | 21.09 | 84.00 | 21.03 | 84.00 | 20.98 |
April | 718.67 | 21.50 | 3.50 | 21.50 | 2.83 | 21.50 |
May | 724.83 | 21.74 | 1.33 | 21.75 | 0.00 | 21.75 |
June | 666.00 | 21.93 | 11.00 | 21.98 | 0.00 | 21.98 |
July | 632.17 | 21.97 | 32.00 | 22.12 | 4.00 | 22.15 |
August | 626.50 | 21.92 | 32.83 | 22.09 | 4.50 | 22.12 |
September | 691.00 | 21.74 | 6.67 | 21.77 | 0.00 | 21.77 |
October | 744.00 | 21.23 | 9.00 | 21.22 | 9.00 | 21.20 |
November | 720.00 | 20.79 | 305.67 | 20.68 | 305.67 | 20.63 |
December | 744.00 | 20.63 | 576.83 | 20.57 | 576.83 | 20.54 |
Annual Sum or Average | 8427.17 | 21.31 | 2046.17 | 21.18 | 1970.17 | 21.08 |
Minimum of Months | 626.50 | 20.58 | 1.33 | 20.52 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.97 | 589.33 | 22.12 | 589.33 | 22.15 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 15.83 | 21.00 | 15.83 | 21.00 |
February | 672.00 | 21.03 | 13.83 | 21.03 | 13.83 | 21.03 |
March | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
April | 720.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
May | 744.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
June | 720.00 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
July | 744.00 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
August | 739.67 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
September | 720.00 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
October | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
November | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
December | 744.00 | 21.00 | 0.67 | 21.00 | 0.67 | 21.00 |
Annual Sum or Average | 8755.67 | 21.68 | 30.33 | 21.68 | 30.33 | 21.68 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.77 | 15.83 | 22.77 | 15.83 | 22.77 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.62 | 672.67 | 20.60 | 672.67 | 20.59 |
February | 670.33 | 20.90 | 369.17 | 20.80 | 369.17 | 20.75 |
March | 740.33 | 21.14 | 159.83 | 21.04 | 159.83 | 20.97 |
April | 699.33 | 21.38 | 21.33 | 21.37 | 18.33 | 21.35 |
May | 693.67 | 21.46 | 9.17 | 21.48 | 0.83 | 21.48 |
June | 666.00 | 21.51 | 5.00 | 21.52 | 0.00 | 21.52 |
July | 636.50 | 21.41 | 23.83 | 21.48 | 0.00 | 21.48 |
August | 645.67 | 21.44 | 30.00 | 21.52 | 0.17 | 21.52 |
September | 653.33 | 21.38 | 16.83 | 21.43 | 0.50 | 21.43 |
October | 730.17 | 21.24 | 22.33 | 21.20 | 22.00 | 21.16 |
November | 717.67 | 20.84 | 341.17 | 20.74 | 341.17 | 20.68 |
December | 744.00 | 20.72 | 585.17 | 20.65 | 585.17 | 20.63 |
Annual Sum or Average | 8341.00 | 21.16 | 2256.50 | 21.05 | 2169.83 | 20.97 |
Minimum of Months | 636.50 | 20.62 | 5.00 | 20.60 | 0.00 | 20.59 |
Maximum of Months | 744.00 | 21.51 | 672.67 | 21.52 | 672.67 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 707.33 | 20.50 | 707.33 | 20.50 |
February | 672.00 | 20.70 | 469.00 | 20.62 | 469.00 | 20.59 |
March | 742.50 | 20.95 | 261.67 | 20.85 | 261.67 | 20.80 |
April | 692.33 | 21.31 | 42.67 | 21.32 | 36.17 | 21.29 |
May | 663.67 | 21.72 | 65.83 | 22.13 | 20.50 | 22.28 |
June | 608.83 | 21.85 | 72.67 | 22.27 | 12.83 | 22.37 |
July | 567.67 | 22.11 | 128.00 | 22.82 | 37.83 | 23.10 |
August | 608.67 | 21.87 | 73.00 | 22.22 | 12.00 | 22.30 |
September | 602.00 | 21.60 | 78.00 | 22.04 | 9.17 | 22.11 |
October | 738.67 | 21.12 | 55.83 | 21.06 | 53.50 | 20.98 |
November | 720.00 | 20.71 | 417.83 | 20.62 | 417.83 | 20.57 |
December | 744.00 | 20.56 | 686.00 | 20.54 | 686.00 | 20.53 |
Annual Sum or Average | 8104.33 | 21.21 | 3057.83 | 21.21 | 2723.83 | 21.12 |
Minimum of Months | 567.67 | 20.52 | 42.67 | 20.50 | 9.17 | 20.50 |
Maximum of Months | 744.00 | 22.11 | 707.33 | 22.82 | 707.33 | 23.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.83 | 20.98 | 313.17 | 20.87 | 313.17 | 20.81 |
February | 652.50 | 21.19 | 154.83 | 21.11 | 154.83 | 21.06 |
March | 721.67 | 21.35 | 16.83 | 21.33 | 16.33 | 21.32 |
April | 684.33 | 21.48 | 3.17 | 21.49 | 0.83 | 21.48 |
May | 690.00 | 21.49 | 1.33 | 21.49 | 0.00 | 21.49 |
June | 665.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
July | 650.50 | 21.45 | 1.17 | 21.45 | 0.00 | 21.45 |
August | 655.00 | 21.46 | 25.67 | 21.53 | 0.00 | 21.53 |
September | 645.17 | 21.42 | 33.00 | 21.51 | 0.00 | 21.51 |
October | 692.50 | 21.35 | 5.67 | 21.37 | 0.00 | 21.37 |
November | 707.33 | 21.13 | 88.50 | 21.06 | 85.83 | 20.99 |
December | 733.83 | 21.02 | 277.17 | 20.89 | 277.17 | 20.82 |
Annual Sum or Average | 8237.67 | 21.31 | 920.50 | 21.26 | 848.17 | 21.21 |
Minimum of Months | 645.17 | 20.98 | 0.00 | 20.87 | 0.00 | 20.81 |
Maximum of Months | 739.83 | 21.52 | 313.17 | 21.53 | 313.17 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 393.00 | 23.10 | 25.50 | 23.15 | 0.00 | 23.15 |
February | 292.67 | 23.14 | 95.50 | 23.35 | 0.00 | 23.35 |
March | 223.00 | 23.19 | 126.50 | 23.48 | 0.00 | 23.48 |
April | 92.17 | 23.19 | 265.50 | 23.77 | 0.00 | 23.77 |
May | 9.33 | 23.17 | 554.67 | 23.96 | 0.00 | 23.96 |
June | 0.67 | 23.04 | 648.67 | 23.97 | 0.00 | 23.97 |
July | 2.33 | 23.99 | 728.33 | 23.96 | 2.33 | 23.96 |
August | 27.00 | 23.99 | 740.33 | 23.95 | 27.00 | 23.95 |
September | 15.17 | 23.62 | 642.33 | 23.94 | 8.67 | 23.94 |
October | 135.33 | 23.11 | 347.67 | 23.74 | 0.00 | 23.74 |
November | 258.17 | 23.08 | 179.00 | 23.45 | 2.00 | 23.45 |
December | 347.00 | 23.05 | 30.33 | 23.13 | 0.00 | 23.13 |
Annual Sum or Average | 1795.83 | 23.13 | 4384.33 | 23.72 | 40.00 | 23.72 |
Minimum of Months | 0.67 | 23.04 | 25.50 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 393.00 | 23.99 | 740.33 | 23.97 | 27.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 235.33 | 23.17 | 146.17 | 23.49 | 0.00 | 23.49 |
February | 165.83 | 23.25 | 205.00 | 23.65 | 0.00 | 23.65 |
March | 80.00 | 23.30 | 337.33 | 23.85 | 0.00 | 23.85 |
April | 7.33 | 23.28 | 494.67 | 23.97 | 0.00 | 23.97 |
May | 0.00 | 0.00 | 699.33 | 23.98 | 0.00 | 23.98 |
June | 0.00 | 0.00 | 711.00 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 742.50 | 23.99 | 0.00 | 23.99 |
August | 18.50 | 23.99 | 744.00 | 23.98 | 18.50 | 23.98 |
September | 2.17 | 24.00 | 705.50 | 23.96 | 2.17 | 23.96 |
October | 6.50 | 23.23 | 540.00 | 23.98 | 0.00 | 23.98 |
November | 111.33 | 23.17 | 332.00 | 23.78 | 1.17 | 23.78 |
December | 192.83 | 23.13 | 165.33 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 819.83 | 23.21 | 5822.83 | 23.89 | 21.83 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 146.17 | 23.49 | 0.00 | 23.49 |
Maximum of Months | 235.33 | 24.00 | 744.00 | 23.99 | 18.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.33 | 23.95 | 666.83 | 23.92 | 490.83 | 23.94 |
February | 461.83 | 23.95 | 614.50 | 23.91 | 451.50 | 23.94 |
March | 518.67 | 23.99 | 719.17 | 23.91 | 518.50 | 23.93 |
April | 512.17 | 23.99 | 714.33 | 23.92 | 512.17 | 23.94 |
May | 537.00 | 23.99 | 743.83 | 23.93 | 537.00 | 23.95 |
June | 531.67 | 23.99 | 720.00 | 23.95 | 531.67 | 23.96 |
July | 556.83 | 23.99 | 744.00 | 23.96 | 556.83 | 23.97 |
August | 565.17 | 23.99 | 744.00 | 23.96 | 565.17 | 23.97 |
September | 530.00 | 23.99 | 720.00 | 23.94 | 530.00 | 23.96 |
October | 527.50 | 23.99 | 744.00 | 23.91 | 527.50 | 23.93 |
November | 498.67 | 23.99 | 687.67 | 23.91 | 498.67 | 23.94 |
December | 497.00 | 23.99 | 674.83 | 23.92 | 496.17 | 23.94 |
Annual Sum or Average | 6238.83 | 23.98 | 8493.17 | 23.93 | 6216.00 | 23.95 |
Minimum of Months | 461.83 | 23.95 | 614.50 | 23.91 | 451.50 | 23.93 |
Maximum of Months | 565.17 | 23.99 | 744.00 | 23.96 | 565.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 30.00 | 21.00 | 30.00 | 21.00 |
February | 672.00 | 21.06 | 27.83 | 21.06 | 27.83 | 21.06 |
March | 744.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
April | 718.17 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
May | 736.67 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
June | 698.67 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
July | 609.33 | 22.70 | 31.33 | 22.76 | 0.00 | 22.76 |
August | 568.50 | 22.66 | 68.33 | 22.79 | 0.00 | 22.79 |
September | 666.33 | 22.21 | 15.67 | 22.25 | 0.00 | 22.25 |
October | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
November | 720.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
December | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Annual Sum or Average | 8365.67 | 21.67 | 173.17 | 21.70 | 57.83 | 21.69 |
Minimum of Months | 568.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.70 | 68.33 | 22.79 | 30.00 | 22.79 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.24108 | 32.88698 | 0.09646 | 5.31647 |
February | 672.00000 | 23.06448 | 34.06152 | 0.05904 | 5.22594 |
March | 744.00000 | 22.87466 | 34.79714 | 0.01596 | 5.16902 |
April | 720.00000 | 22.76590 | 38.34336 | 0.01097 | 5.16691 |
May | 744.00000 | 22.85054 | 42.38436 | -0.9663 | 24.91451 |
June | 720.00000 | 23.01713 | 44.91921 | -0.8875 | 21.85969 |
July | 744.00000 | 23.23251 | 48.95805 | -0.7809 | 18.08831 |
August | 744.00000 | 23.41157 | 52.66475 | -0.6901 | 15.20666 |
September | 720.00000 | 23.59219 | 48.62531 | -0.6498 | 14.07515 |
October | 744.00000 | 23.70469 | 39.48500 | 0.26675 | 6.56984 |
November | 720.00000 | 23.72307 | 37.77606 | 0.25890 | 6.49176 |
December | 744.00000 | 23.54134 | 33.78077 | 0.18146 | 5.79049 |
Annual Sum or Average | 8760.00000 | 23.25288 | 40.75975 | -0.2590 | 11.19684 |
Minimum of Months | 672.00000 | 22.76590 | 32.88698 | -0.9663 | 5.16691 |
Maximum of Months | 744.00000 | 23.72307 | 52.66475 | 0.26675 | 24.91451 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.03905 | 34.76732 | -0.4905 | 10.28482 |
February | 672.00000 | 21.16158 | 35.63482 | -0.4007 | 9.18768 |
March | 744.00000 | 21.24144 | 36.04235 | -0.3346 | 8.22329 |
April | 720.00000 | 21.36772 | 39.46401 | -0.2417 | 7.39119 |
May | 744.00000 | 21.45211 | 43.89086 | -1.2857 | 41.05816 |
June | 720.00000 | 21.49670 | 47.02446 | -1.2263 | 37.71678 |
July | 744.00000 | 21.87069 | 50.86976 | -1.0408 | 30.18832 |
August | 744.00000 | 22.01515 | 55.03249 | -0.9577 | 27.53158 |
September | 720.00000 | 21.75649 | 51.98031 | -1.0988 | 33.94142 |
October | 744.00000 | 21.38204 | 43.02779 | -0.2265 | 7.35239 |
November | 720.00000 | 21.08931 | 41.57363 | -0.3898 | 8.76123 |
December | 744.00000 | 21.08544 | 36.38678 | -0.4594 | 9.86329 |
Annual Sum or Average | 8760.00000 | 21.41505 | 43.01256 | -0.6810 | 19.34557 |
Minimum of Months | 672.00000 | 21.03905 | 34.76732 | -1.2857 | 7.35239 |
Maximum of Months | 744.00000 | 22.01515 | 55.03249 | -0.2265 | 41.05816 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54871 | 36.53369 | -0.2864 | 6.98385 |
February | 672.00000 | 21.82554 | 37.00215 | -0.2083 | 6.37273 |
March | 744.00000 | 22.17750 | 36.95948 | -0.1148 | 5.65051 |
April | 720.00000 | 22.49520 | 39.79472 | -0.0120 | 5.50830 |
May | 744.00000 | 22.78313 | 43.51930 | -0.9276 | 23.86530 |
June | 720.00000 | 22.95237 | 46.07275 | -0.8472 | 20.81076 |
July | 744.00000 | 23.24410 | 49.85244 | -0.7104 | 16.26639 |
August | 744.00000 | 23.29408 | 53.89999 | -0.6639 | 14.93835 |
September | 720.00000 | 23.03800 | 51.09070 | -0.7810 | 18.73989 |
October | 744.00000 | 22.51439 | 43.10827 | 0.01293 | 5.41402 |
November | 720.00000 | 21.92052 | 42.39159 | -0.1506 | 5.93885 |
December | 744.00000 | 21.66731 | 37.99699 | -0.2469 | 6.54103 |
Annual Sum or Average | 8760.00000 | 22.45864 | 43.21789 | -0.4126 | 11.44606 |
Minimum of Months | 672.00000 | 21.54871 | 36.53369 | -0.9276 | 5.41402 |
Maximum of Months | 744.00000 | 23.29408 | 53.89999 | 0.01293 | 23.86530 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.93211 | 29.61629 | 0.59733 | 15.14374 |
February | 672.00000 | 22.96846 | 30.45800 | 0.62571 | 15.89658 |
March | 744.00000 | 22.99866 | 30.84556 | 0.65589 | 16.62966 |
April | 720.00000 | 23.02988 | 34.11543 | 0.70258 | 17.90664 |
May | 744.00000 | 23.04246 | 38.23744 | 0.02253 | 10.13404 |
June | 720.00000 | 23.06141 | 41.10042 | 0.06976 | 10.18851 |
July | 744.00000 | 23.08439 | 45.61885 | 0.11891 | 10.16012 |
August | 744.00000 | 23.08572 | 49.85330 | 0.15605 | 10.40321 |
September | 720.00000 | 23.07188 | 46.32694 | 0.09784 | 10.22299 |
October | 744.00000 | 23.05093 | 37.20666 | 0.72320 | 18.46776 |
November | 720.00000 | 22.99875 | 35.55961 | 0.67394 | 17.17373 |
December | 744.00000 | 22.95004 | 31.07541 | 0.61502 | 15.55348 |
Annual Sum or Average | 8760.00000 | 23.02315 | 37.53960 | 0.42027 | 13.97565 |
Minimum of Months | 672.00000 | 22.93211 | 29.61629 | 0.02253 | 10.13404 |
Maximum of Months | 744.00000 | 23.08572 | 49.85330 | 0.72320 | 18.46776 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37655 | 39.16401 | -0.3052 | 7.40507 |
February | 672.00000 | 21.68998 | 39.63119 | -0.1812 | 6.76816 |
March | 744.00000 | 21.96673 | 39.78425 | -0.0803 | 6.14655 |
April | 720.00000 | 22.21837 | 42.81040 | 0.03063 | 6.07820 |
May | 744.00000 | 22.37528 | 46.88492 | -0.9041 | 23.88741 |
June | 720.00000 | 22.51523 | 49.60701 | -0.8206 | 20.32516 |
July | 744.00000 | 22.83012 | 53.46660 | -0.6577 | 15.56229 |
August | 744.00000 | 22.94055 | 57.44903 | -0.5805 | 14.18150 |
September | 720.00000 | 22.71200 | 54.41970 | -0.7058 | 18.51567 |
October | 744.00000 | 22.24739 | 46.10328 | 0.05246 | 6.32875 |
November | 720.00000 | 21.62402 | 45.37388 | -0.1708 | 6.50827 |
December | 744.00000 | 21.47163 | 40.71231 | -0.2649 | 7.10015 |
Annual Sum or Average | 8760.00000 | 22.16675 | 46.31918 | -0.3836 | 11.59258 |
Minimum of Months | 672.00000 | 21.37655 | 39.16401 | -0.9041 | 6.07820 |
Maximum of Months | 744.00000 | 22.94055 | 57.44903 | 0.05246 | 23.88741 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94077 | 38.45719 | -0.1641 | 6.05035 |
February | 672.00000 | 22.22937 | 38.90063 | -0.0782 | 5.76071 |
March | 744.00000 | 22.53935 | 38.96633 | 0.01030 | 5.52353 |
April | 720.00000 | 22.79351 | 41.87396 | 0.10231 | 5.73932 |
May | 744.00000 | 23.00617 | 45.68443 | -0.7941 | 19.05156 |
June | 720.00000 | 23.15607 | 48.23523 | -0.7156 | 16.49718 |
July | 744.00000 | 23.35590 | 52.18889 | -0.6058 | 13.29352 |
August | 744.00000 | 23.41232 | 56.10985 | -0.5546 | 12.05287 |
September | 720.00000 | 23.24030 | 53.15999 | -0.6491 | 14.78231 |
October | 744.00000 | 22.84459 | 45.01961 | 0.13536 | 5.90523 |
November | 720.00000 | 22.28827 | 44.25133 | -0.0287 | 5.69670 |
December | 744.00000 | 22.05231 | 39.90848 | -0.1250 | 5.81899 |
Annual Sum or Average | 8760.00000 | 22.74099 | 45.26359 | -0.2903 | 9.70231 |
Minimum of Months | 672.00000 | 21.94077 | 38.45719 | -0.7941 | 5.52353 |
Maximum of Months | 744.00000 | 23.41232 | 56.10985 | 0.13536 | 19.05156 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.72590 | 43.44809 | -0.5871 | 12.56790 |
February | 672.00000 | 20.99989 | 44.05781 | -0.4814 | 10.53447 |
March | 744.00000 | 21.22035 | 44.60009 | -0.3825 | 8.62706 |
April | 720.00000 | 21.46261 | 47.12150 | -0.2563 | 7.21296 |
May | 744.00000 | 21.59902 | 49.80189 | -1.2869 | 40.84124 |
June | 720.00000 | 21.65226 | 51.06051 | -1.2316 | 38.05428 |
July | 744.00000 | 21.69535 | 51.35010 | -1.1542 | 34.62482 |
August | 744.00000 | 21.69029 | 53.86296 | -1.1499 | 34.40852 |
September | 720.00000 | 21.58619 | 54.77095 | -1.2390 | 38.51751 |
October | 744.00000 | 21.34049 | 51.65937 | -0.2831 | 7.35716 |
November | 720.00000 | 20.94125 | 50.20841 | -0.4613 | 9.99638 |
December | 744.00000 | 20.80636 | 45.09830 | -0.5521 | 11.88216 |
Annual Sum or Average | 8760.00000 | 21.31144 | 48.93946 | -0.7573 | 21.28212 |
Minimum of Months | 672.00000 | 20.72590 | 43.44809 | -1.2869 | 7.21296 |
Maximum of Months | 744.00000 | 21.69535 | 54.77095 | -0.2563 | 40.84124 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58848 | 43.78533 | -0.6313 | 13.76717 |
February | 672.00000 | 20.79089 | 44.56323 | -0.5513 | 11.91278 |
March | 744.00000 | 21.03811 | 45.01545 | -0.4482 | 9.53636 |
April | 720.00000 | 21.43534 | 47.34941 | -0.2868 | 7.61207 |
May | 744.00000 | 21.97409 | 49.29527 | -1.2031 | 38.98418 |
June | 720.00000 | 22.17750 | 49.97350 | -1.0994 | 33.75900 |
July | 744.00000 | 22.51025 | 50.07156 | -0.9397 | 28.93267 |
August | 744.00000 | 22.23478 | 53.78649 | -1.0187 | 29.83809 |
September | 720.00000 | 22.01798 | 55.02767 | -1.1500 | 35.93344 |
October | 744.00000 | 21.22355 | 52.21007 | -0.3374 | 7.88599 |
November | 720.00000 | 20.80775 | 50.70717 | -0.5061 | 10.83971 |
December | 744.00000 | 20.64485 | 45.50938 | -0.6043 | 13.02382 |
Annual Sum or Average | 8760.00000 | 21.45737 | 48.95722 | -0.7325 | 20.21617 |
Minimum of Months | 672.00000 | 20.58848 | 43.78533 | -1.2031 | 7.61207 |
Maximum of Months | 744.00000 | 22.51025 | 55.02767 | -0.2868 | 38.98418 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96724 | 41.94719 | -0.4876 | 10.10483 |
February | 672.00000 | 21.06580 | 42.76954 | -0.4471 | 9.41241 |
March | 744.00000 | 21.21522 | 43.21736 | -0.3838 | 8.16576 |
April | 720.00000 | 21.42213 | 45.73442 | -0.2991 | 7.13986 |
May | 744.00000 | 21.67361 | 47.98133 | -1.3474 | 43.26171 |
June | 720.00000 | 21.87894 | 48.35697 | -1.2577 | 38.88260 |
July | 744.00000 | 22.03027 | 50.26688 | -1.1835 | 35.52280 |
August | 744.00000 | 21.95431 | 53.37998 | -1.1951 | 35.85782 |
September | 720.00000 | 21.69995 | 53.58220 | -1.3080 | 41.21093 |
October | 744.00000 | 21.30193 | 50.04257 | -0.3116 | 7.11673 |
November | 720.00000 | 21.11868 | 48.28059 | -0.3916 | 8.38037 |
December | 744.00000 | 20.98878 | 43.65122 | -0.4709 | 9.73735 |
Annual Sum or Average | 8760.00000 | 21.44522 | 47.45549 | -0.7589 | 21.30065 |
Minimum of Months | 672.00000 | 20.96724 | 41.94719 | -1.3474 | 7.11673 |
Maximum of Months | 744.00000 | 22.03027 | 53.58220 | -0.2991 | 43.26171 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.71287 | 43.46102 | -0.5901 | 12.61943 |
February | 672.00000 | 21.00819 | 44.03190 | -0.4800 | 10.42564 |
March | 744.00000 | 21.27720 | 44.44806 | -0.3686 | 8.44046 |
April | 720.00000 | 21.54554 | 46.74965 | -0.2343 | 7.08427 |
May | 744.00000 | 21.61906 | 49.54143 | -1.2954 | 41.25383 |
June | 720.00000 | 21.69145 | 50.19968 | -1.2134 | 37.27353 |
July | 744.00000 | 21.71043 | 51.28390 | -1.1713 | 35.41483 |
August | 744.00000 | 21.71284 | 53.25801 | -1.1463 | 34.29147 |
September | 720.00000 | 21.59027 | 54.84528 | -1.2502 | 39.06947 |
October | 744.00000 | 21.37368 | 51.41482 | -0.2771 | 7.33957 |
November | 720.00000 | 20.93492 | 50.18903 | -0.4624 | 9.99138 |
December | 744.00000 | 20.78873 | 45.13141 | -0.5558 | 11.90588 |
Annual Sum or Average | 8760.00000 | 21.33187 | 48.73178 | -0.7556 | 21.32522 |
Minimum of Months | 672.00000 | 20.71287 | 43.46102 | -1.2954 | 7.08427 |
Maximum of Months | 744.00000 | 21.71284 | 54.84528 | -0.2343 | 41.25383 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58012 | 43.79577 | -0.6339 | 13.86785 |
February | 672.00000 | 20.78316 | 44.55448 | -0.5533 | 11.88561 |
March | 744.00000 | 21.08569 | 44.86490 | -0.4364 | 9.20199 |
April | 720.00000 | 21.50792 | 47.01638 | -0.2668 | 7.25780 |
May | 744.00000 | 21.80164 | 49.41856 | -1.2673 | 39.97635 |
June | 720.00000 | 22.09226 | 49.49269 | -1.1170 | 33.25607 |
July | 744.00000 | 22.26364 | 50.88777 | -1.0316 | 30.14530 |
August | 744.00000 | 22.22903 | 53.26490 | -1.0226 | 29.80062 |
September | 720.00000 | 21.82857 | 55.59704 | -1.2185 | 37.65608 |
October | 744.00000 | 21.23368 | 51.99647 | -0.3367 | 7.76712 |
November | 720.00000 | 20.79318 | 50.72167 | -0.5087 | 10.88513 |
December | 744.00000 | 20.62537 | 45.54382 | -0.6086 | 13.15118 |
Annual Sum or Average | 8760.00000 | 21.40543 | 48.94602 | -0.7514 | 20.45390 |
Minimum of Months | 672.00000 | 20.58012 | 43.79577 | -1.2673 | 7.25780 |
Maximum of Months | 744.00000 | 22.26364 | 55.59704 | -0.2668 | 39.97635 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.62079 | 44.49097 | -0.6430 | 14.10691 |
February | 672.00000 | 20.90486 | 45.10664 | -0.5294 | 11.70807 |
March | 744.00000 | 21.15106 | 45.60748 | -0.4167 | 9.35633 |
April | 720.00000 | 21.43132 | 48.01420 | -0.2727 | 7.58435 |
May | 744.00000 | 21.58185 | 50.60816 | -1.2995 | 41.72733 |
June | 720.00000 | 21.64283 | 51.79835 | -1.2344 | 38.43269 |
July | 744.00000 | 21.68627 | 52.15541 | -1.1509 | 34.74213 |
August | 744.00000 | 21.67758 | 55.01896 | -1.1511 | 34.71306 |
September | 720.00000 | 21.55701 | 56.18817 | -1.2545 | 39.51186 |
October | 744.00000 | 21.27787 | 52.91222 | -0.3129 | 7.86291 |
November | 720.00000 | 20.84329 | 51.52761 | -0.5071 | 11.07959 |
December | 744.00000 | 20.71820 | 46.15517 | -0.6034 | 13.20977 |
Annual Sum or Average | 8760.00000 | 21.25943 | 49.98421 | -0.7830 | 22.06398 |
Minimum of Months | 672.00000 | 20.62079 | 44.49097 | -1.2995 | 7.58435 |
Maximum of Months | 744.00000 | 21.68627 | 56.18817 | -0.2727 | 41.72733 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51682 | 44.77188 | -0.6820 | 15.25683 |
February | 672.00000 | 20.69644 | 45.65185 | -0.6011 | 13.25143 |
March | 744.00000 | 20.96018 | 46.06298 | -0.4864 | 10.41041 |
April | 720.00000 | 21.42023 | 48.19757 | -0.3012 | 8.06172 |
May | 744.00000 | 22.04232 | 49.92418 | -1.1867 | 39.68962 |
June | 720.00000 | 22.26239 | 50.37070 | -1.0688 | 33.66444 |
July | 744.00000 | 22.62260 | 50.28024 | -0.8928 | 29.05054 |
August | 744.00000 | 22.26119 | 54.57505 | -1.0049 | 30.05774 |
September | 720.00000 | 22.07271 | 56.08162 | -1.1385 | 36.59557 |
October | 744.00000 | 21.15110 | 53.53571 | -0.3715 | 8.53309 |
November | 720.00000 | 20.70920 | 52.06390 | -0.5530 | 12.03552 |
December | 744.00000 | 20.56145 | 46.58180 | -0.6559 | 14.47286 |
Annual Sum or Average | 8760.00000 | 21.44390 | 49.85576 | -0.7462 | 20.96811 |
Minimum of Months | 672.00000 | 20.51682 | 44.77188 | -1.1867 | 8.06172 |
Maximum of Months | 744.00000 | 22.62260 | 56.08162 | -0.3012 | 39.68962 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99791 | 44.12509 | -0.4981 | 10.85953 |
February | 672.00000 | 21.25541 | 44.62387 | -0.3851 | 9.20830 |
March | 744.00000 | 21.40893 | 45.08174 | -0.3081 | 7.96772 |
April | 720.00000 | 21.57249 | 47.42224 | -0.2191 | 7.12027 |
May | 744.00000 | 21.62109 | 50.14374 | -1.3021 | 41.79663 |
June | 720.00000 | 21.66107 | 51.29878 | -1.2564 | 39.42980 |
July | 744.00000 | 21.68419 | 52.00976 | -1.2047 | 37.12596 |
August | 744.00000 | 21.68422 | 54.05055 | -1.1795 | 35.97617 |
September | 720.00000 | 21.61455 | 54.27163 | -1.2349 | 38.67254 |
October | 744.00000 | 21.48882 | 51.13838 | -0.2229 | 7.04689 |
November | 720.00000 | 21.16466 | 50.10791 | -0.3851 | 8.88987 |
December | 744.00000 | 21.04688 | 45.69156 | -0.4660 | 10.49911 |
Annual Sum or Average | 8760.00000 | 21.43405 | 49.18343 | -0.7240 | 21.28942 |
Minimum of Months | 672.00000 | 20.99791 | 44.12509 | -1.3021 | 7.04689 |
Maximum of Months | 744.00000 | 21.68422 | 54.27163 | -0.2191 | 41.79663 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50896 | 38.35189 | 0.23512 | 6.63075 |
February | 672.00000 | 23.59213 | 38.87807 | 0.27112 | 7.01920 |
March | 744.00000 | 23.71756 | 38.82485 | 0.32440 | 7.48929 |
April | 720.00000 | 23.82483 | 41.50459 | 0.39302 | 8.43263 |
May | 744.00000 | 23.90148 | 44.91658 | -0.4135 | 8.75330 |
June | 720.00000 | 23.93109 | 47.32373 | -0.3600 | 7.83442 |
July | 744.00000 | 23.95724 | 51.38309 | -0.3031 | 7.04129 |
August | 744.00000 | 23.94445 | 55.41883 | -0.2816 | 6.75771 |
September | 720.00000 | 23.89147 | 52.60731 | -0.3601 | 7.91991 |
October | 744.00000 | 23.77385 | 44.67835 | 0.39187 | 8.41394 |
November | 720.00000 | 23.63632 | 43.63695 | 0.32421 | 7.61463 |
December | 744.00000 | 23.54465 | 39.73914 | 0.25554 | 6.79284 |
Annual Sum or Average | 8760.00000 | 23.76955 | 44.80399 | 0.03829 | 7.55846 |
Minimum of Months | 672.00000 | 23.50896 | 38.35189 | -0.4135 | 6.63075 |
Maximum of Months | 744.00000 | 23.95724 | 55.41883 | 0.39302 | 8.75330 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.71111 | 37.15352 | 0.32448 | 7.48979 |
February | 672.00000 | 23.77261 | 37.71589 | 0.35487 | 7.94177 |
March | 744.00000 | 23.85766 | 37.71940 | 0.39752 | 8.46820 |
April | 720.00000 | 23.92494 | 40.49433 | 0.45484 | 9.44824 |
May | 744.00000 | 23.96225 | 44.05132 | -0.3409 | 7.53629 |
June | 720.00000 | 23.97596 | 46.56549 | -0.2962 | 6.90925 |
July | 744.00000 | 23.98587 | 50.71370 | -0.2482 | 6.38781 |
August | 744.00000 | 23.98010 | 54.73513 | -0.2251 | 6.12868 |
September | 720.00000 | 23.95293 | 51.75727 | -0.2900 | 6.88228 |
October | 744.00000 | 23.88817 | 43.60289 | 0.45737 | 9.48311 |
November | 720.00000 | 23.80117 | 42.44234 | 0.40426 | 8.67440 |
December | 744.00000 | 23.73639 | 38.51599 | 0.34246 | 7.70697 |
Annual Sum or Average | 8760.00000 | 23.87959 | 43.82213 | 0.10975 | 7.75074 |
Minimum of Months | 672.00000 | 23.71111 | 37.15352 | -0.3409 | 6.12868 |
Maximum of Months | 744.00000 | 23.98587 | 54.73513 | 0.45737 | 9.48311 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.75999 | 35.55374 | 0.95364 | 26.40650 |
February | 672.00000 | 23.77746 | 36.18921 | 0.98493 | 27.73447 |
March | 744.00000 | 23.82079 | 36.41059 | 1.02827 | 29.27329 |
April | 720.00000 | 23.85357 | 39.35815 | 1.09268 | 32.12708 |
May | 744.00000 | 23.88218 | 43.14872 | 0.57463 | 16.56413 |
June | 720.00000 | 23.91546 | 45.73715 | 0.64087 | 17.91052 |
July | 744.00000 | 23.93325 | 49.94033 | 0.69528 | 19.48366 |
August | 744.00000 | 23.94204 | 53.78329 | 0.72797 | 20.25520 |
September | 720.00000 | 23.91135 | 50.61938 | 0.64447 | 17.98317 |
October | 744.00000 | 23.85628 | 42.29114 | 1.09309 | 31.97629 |
November | 720.00000 | 23.80971 | 40.93479 | 1.03149 | 29.46965 |
December | 744.00000 | 23.76972 | 36.89424 | 0.97013 | 27.00833 |
Annual Sum or Average | 8760.00000 | 23.85305 | 42.60675 | 0.86903 | 24.66101 |
Minimum of Months | 672.00000 | 23.75999 | 35.55374 | 0.57463 | 16.56413 |
Maximum of Months | 744.00000 | 23.94204 | 53.78329 | 1.09309 | 32.12708 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00225 | 34.11534 | -0.4730 | 9.70966 |
February | 672.00000 | 21.04383 | 35.13407 | -0.4458 | 9.27388 |
March | 744.00000 | 21.12113 | 35.57614 | -0.4077 | 8.56272 |
April | 720.00000 | 21.46121 | 38.57678 | -0.3016 | 7.21443 |
May | 744.00000 | 21.97623 | 42.01405 | -1.2576 | 38.37209 |
June | 720.00000 | 22.36193 | 44.19579 | -1.1098 | 31.20659 |
July | 744.00000 | 22.75419 | 47.85554 | -0.9487 | 24.31763 |
August | 744.00000 | 22.87294 | 51.87904 | -0.8820 | 21.76962 |
September | 720.00000 | 22.33429 | 49.76994 | -1.0840 | 30.18302 |
October | 744.00000 | 21.56057 | 42.04546 | -0.2557 | 6.59119 |
November | 720.00000 | 21.12613 | 40.84711 | -0.3837 | 8.27088 |
December | 744.00000 | 21.00313 | 35.81524 | -0.4575 | 9.39378 |
Annual Sum or Average | 8760.00000 | 21.72257 | 41.51717 | -0.6685 | 17.11270 |
Minimum of Months | 672.00000 | 21.00225 | 34.11534 | -1.2576 | 6.59119 |
Maximum of Months | 744.00000 | 22.87294 | 51.87904 | -0.2557 | 38.37209 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00161 | 37.30096 | -0.4633 | 9.50851 |
February | 672.00000 | 21.03290 | 38.28445 | -0.4386 | 9.09826 |
March | 744.00000 | 21.14257 | 38.63352 | -0.3981 | 8.37421 |
April | 720.00000 | 21.46670 | 41.60794 | -0.2954 | 7.10587 |
May | 744.00000 | 21.99832 | 45.00319 | -1.2500 | 37.94216 |
June | 720.00000 | 22.29118 | 47.40855 | -1.1319 | 32.19981 |
July | 744.00000 | 22.66473 | 51.16298 | -0.9754 | 25.41817 |
August | 744.00000 | 22.77894 | 55.24428 | -0.9091 | 22.77826 |
September | 720.00000 | 22.28634 | 52.90802 | -1.0982 | 30.97711 |
October | 744.00000 | 21.45091 | 45.25606 | -0.2794 | 6.87445 |
November | 720.00000 | 21.04580 | 44.10326 | -0.4013 | 8.45893 |
December | 744.00000 | 21.00490 | 38.97309 | -0.4505 | 9.25877 |
Annual Sum or Average | 8760.00000 | 21.68472 | 44.68930 | -0.6756 | 17.37478 |
Minimum of Months | 672.00000 | 21.00161 | 37.30096 | -1.2500 | 6.87445 |
Maximum of Months | 744.00000 | 22.77894 | 55.24428 | -0.2794 | 37.94216 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00275 | 35.21581 | -0.4564 | 9.38468 |
February | 672.00000 | 21.06418 | 36.13109 | -0.4197 | 8.82596 |
March | 744.00000 | 21.20927 | 36.41442 | -0.3625 | 7.87789 |
April | 720.00000 | 21.59982 | 39.21305 | -0.2381 | 6.66914 |
May | 744.00000 | 22.09452 | 42.60127 | -1.1687 | 34.38163 |
June | 720.00000 | 22.48402 | 44.74239 | -1.0138 | 27.28145 |
July | 744.00000 | 22.85917 | 48.40128 | -0.8533 | 21.15946 |
August | 744.00000 | 22.89979 | 52.62750 | -0.8118 | 19.77918 |
September | 720.00000 | 22.31215 | 50.64354 | -1.0394 | 28.83767 |
October | 744.00000 | 21.45003 | 43.12439 | -0.2556 | 6.67187 |
November | 720.00000 | 21.07695 | 41.92137 | -0.3782 | 8.16762 |
December | 744.00000 | 21.01239 | 36.87843 | -0.4410 | 9.08990 |
Annual Sum or Average | 8760.00000 | 21.75987 | 42.35736 | -0.6210 | 15.71092 |
Minimum of Months | 672.00000 | 21.00275 | 35.21581 | -1.1687 | 6.66914 |
Maximum of Months | 744.00000 | 22.89979 | 52.62750 | -0.2381 | 34.38163 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.03303 | 33.67017 | -0.4593 | 9.45539 |
February | 672.00000 | 21.12076 | 34.58045 | -0.4247 | 8.94151 |
March | 744.00000 | 21.28982 | 34.85249 | -0.3698 | 7.99815 |
April | 720.00000 | 21.68936 | 37.69423 | -0.2529 | 6.68247 |
May | 744.00000 | 22.22895 | 41.02772 | -1.1804 | 34.63343 |
June | 720.00000 | 22.60858 | 43.18359 | -1.0343 | 27.89927 |
July | 744.00000 | 23.00139 | 46.78719 | -0.8724 | 21.43146 |
August | 744.00000 | 23.12305 | 50.73977 | -0.8046 | 19.04402 |
September | 720.00000 | 22.59372 | 48.64404 | -1.0043 | 26.75622 |
October | 744.00000 | 21.82316 | 41.03975 | -0.1993 | 6.07399 |
November | 720.00000 | 21.25435 | 40.14758 | -0.3523 | 7.86535 |
December | 744.00000 | 21.04329 | 35.35690 | -0.4424 | 9.11878 |
Annual Sum or Average | 8760.00000 | 21.90571 | 40.67405 | -0.6175 | 15.52568 |
Minimum of Months | 672.00000 | 21.03303 | 33.67017 | -1.1804 | 6.07399 |
Maximum of Months | 744.00000 | 23.12305 | 50.73977 | -0.1993 | 34.63343 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.635071E+09 | 12552.45 | 11-JAN-19:03 | 115.35 | 0.197875E+10 | 0.00 | 0.261382E+10 | 0.48 | 3.12 | 01-JAN-20:10 | 0.00 | 0.00 |
February | 0.340153E+10 | 58642.10 | 27-FEB-16:03 | 249.28 | 0.103656E+11 | 0.00 | 0.137671E+11 | 1.15 | 3.38 | 27-FEB-16:03 | 0.00 | 0.00 |
March | 0.879090E+10 | 70285.30 | 18-MAR-15:01 | 445.27 | 0.269432E+11 | 0.00 | 0.357341E+11 | 1.86 | 3.71 | 18-MAR-15:01 | 0.00 | 0.00 |
April | 0.249021E+11 | 107385.20 | 27-APR-15:03 | 604.84 | 0.763551E+11 | 0.00 | 0.101257E+12 | 2.59 | 3.80 | 29-APR-15:03 | 0.00 | 0.00 |
May | 0.419612E+11 | 95484.90 | 04-MAY-15:03 | 719.29 | 0.127940E+12 | 0.00 | 0.169902E+12 | 2.97 | 3.81 | 07-MAY-15:03 | 0.00 | 0.00 |
June | 0.627288E+11 | 106296.20 | 28-JUN-18:03 | 716.83 | 0.189516E+12 | 0.00 | 0.252244E+12 | 3.02 | 3.93 | 17-JUN-15:01 | 0.00 | 0.00 |
July | 0.940422E+11 | 128324.32 | 24-JUL-18:03 | 744.00 | 0.291084E+12 | 0.00 | 0.385126E+12 | 3.04 | 3.88 | 11-JUL-15:03 | 0.00 | 0.00 |
August | 0.110415E+12 | 146486.06 | 10-AUG-18:03 | 744.00 | 0.346086E+12 | 0.00 | 0.456501E+12 | 3.06 | 3.90 | 26-AUG-15:03 | 0.00 | 0.00 |
September | 0.555259E+11 | 102389.44 | 14-SEP-15:03 | 703.75 | 0.171680E+12 | 0.00 | 0.227206E+12 | 2.99 | 3.85 | 13-SEP-15:03 | 0.00 | 0.00 |
October | 0.187159E+11 | 81056.32 | 04-OCT-15:03 | 575.82 | 0.566163E+11 | 0.00 | 0.753322E+11 | 2.38 | 3.80 | 04-OCT-15:03 | 0.00 | 0.00 |
November | 0.453715E+10 | 78019.24 | 04-NOV-15:03 | 275.37 | 0.137924E+11 | 0.00 | 0.183296E+11 | 1.19 | 3.81 | 04-NOV-15:03 | 0.00 | 0.00 |
December | 0.106097E+10 | 12770.73 | 02-DEC-09:02 | 139.76 | 0.330591E+10 | 0.00 | 0.436688E+10 | 0.59 | 3.12 | 01-DEC-13:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.426717E+12 | 6033.56 | 0.131566E+13 | 0.00 | 0.174238E+13 | 2.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.635071E+09 | 12552.45 | 115.35 | 0.197875E+10 | 0.00 | 0.261382E+10 | 0.48 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.110415E+12 | 146486.06 | 744.00 | 0.346086E+12 | 0.00 | 0.456501E+12 | 3.06 | 3.93 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.997424E+11 | 0.00 | 744.00 | 168443.16 | 02-JAN-16:04 | 0.00 | 39.06 | 60.00 | 0.40 | 0.00 | 0.10 | 0.44 | 02-JAN-16:04 |
February | 0.920447E+11 | 0.00 | 663.45 | 166408.03 | 22-FEB-09:03 | 0.00 | 37.94 | 59.59 | 0.39 | 0.00 | 0.10 | 0.43 | 22-FEB-09:03 |
March | 0.102305E+12 | 0.00 | 724.52 | 148581.37 | 03-MAR-19:04 | 0.00 | 37.01 | 59.11 | 0.36 | 0.00 | 0.10 | 0.39 | 03-MAR-19:04 |
April | 0.974413E+11 | 0.00 | 609.77 | 128631.30 | 11-APR-18:04 | 0.00 | 32.90 | 54.87 | 0.33 | 0.00 | 0.10 | 0.33 | 11-APR-18:04 |
May | 0.865882E+11 | 0.00 | 521.22 | 118668.24 | 28-MAY-08:04 | 0.00 | 29.42 | 49.81 | 0.27 | 0.00 | 0.08 | 0.31 | 28-MAY-08:04 |
June | 0.437710E+11 | 0.00 | 367.15 | 102035.27 | 15-JUN-04:00 | 0.00 | 26.02 | 42.98 | 0.13 | 0.00 | 0.04 | 0.26 | 15-JUN-04:00 |
July | 0.163216E+11 | 0.00 | 241.90 | 64238.68 | 12-JUL-08:04 | 0.00 | 25.55 | 36.89 | 0.04 | 0.00 | 0.02 | 0.17 | 12-JUL-08:04 |
August | 0.125734E+11 | 0.00 | 196.11 | 69955.82 | 03-AUG-08:06 | 0.00 | 27.32 | 36.30 | 0.03 | 0.00 | 0.01 | 0.18 | 03-AUG-08:06 |
September | 0.463060E+11 | 0.00 | 416.26 | 116829.47 | 27-SEP-08:07 | 0.00 | 27.03 | 45.98 | 0.14 | 0.00 | 0.05 | 0.30 | 27-SEP-08:07 |
October | 0.123267E+12 | 0.00 | 651.65 | 164500.23 | 30-OCT-08:04 | 0.00 | 31.83 | 56.02 | 0.41 | 0.00 | 0.12 | 0.43 | 30-OCT-08:04 |
November | 0.106014E+12 | 0.00 | 706.32 | 173420.83 | 17-NOV-09:04 | 0.00 | 36.56 | 59.48 | 0.40 | 0.00 | 0.11 | 0.45 | 17-NOV-09:04 |
December | 0.101604E+12 | 0.00 | 744.00 | 172528.96 | 16-DEC-16:04 | 0.00 | 38.80 | 60.00 | 0.41 | 0.00 | 0.10 | 0.45 | 16-DEC-16:04 |
Annual Sum or Average | 0.927978E+12 | 0.00 | 6586.35 | 0.00 | 32.43 | 51.70 | 0.28 | 0.00 | 0.08 | ||||
Minimum of Months | 0.125734E+11 | 0.00 | 196.11 | 64238.68 | 0.00 | 25.55 | 36.30 | 0.03 | 0.00 | 0.01 | 0.17 | ||
Maximum of Months | 0.123267E+12 | 0.00 | 744.00 | 173420.83 | 0.00 | 39.06 | 60.00 | 0.41 | 0.00 | 0.12 | 0.45 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.175155E+10 | 0.00 | 10.67 | 0.175155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78777.98 | 27-FEB-15:00 | 78777.98 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.387079E+10 | 0.00 | 33.33 | 0.387079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103583.92 | 18-MAR-16:10 | 103583.92 | 18-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.281901E+11 | 0.00 | 119.17 | 0.281901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204511.87 | 27-APR-18:10 | 204511.87 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.545502E+11 | 0.00 | 239.82 | 0.542280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205686.61 | 05-MAY-18:00 | 176380.12 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.977781E+11 | 0.00 | 388.33 | 0.976865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208837.45 | 28-JUN-18:10 | 208837.45 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.165331E+12 | 0.00 | 536.33 | 0.160590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263984.87 | 27-JUL-18:03 | 235161.11 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.208657E+12 | 0.00 | 589.58 | 0.201105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286713.46 | 10-AUG-18:10 | 249777.18 | 10-AUG-18:50 | 0.00 | 0.00 | 0.00 |
September | 0.794603E+11 | 0.00 | 341.50 | 0.776976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197734.67 | 14-SEP-17:15 | 180295.12 | 14-SEP-17:04 | 0.00 | 0.00 | 0.00 |
October | 0.147084E+11 | 0.00 | 118.31 | 0.146930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123818.23 | 04-OCT-15:15 | 123818.23 | 04-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 0.335422E+10 | 0.00 | 25.67 | 0.335422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102360.86 | 04-NOV-14:30 | 102360.86 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657652E+12 | 0.00 | 2402.70 | 0.643167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.208657E+12 | 0.00 | 589.58 | 0.201105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286713.46 | 249777.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.108438E+09 | 0.00 | 5.00 | 0.108438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9635.08 | 27-FEB-16:03 | 9635.08 | 27-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 0.233614E+09 | 0.00 | 18.33 | 0.233614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12388.66 | 18-MAR-16:00 | 12388.66 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.179828E+10 | 0.00 | 73.00 | 0.179828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18211.92 | 27-APR-15:02 | 18211.92 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.355652E+10 | 0.00 | 145.50 | 0.343549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20677.56 | 05-MAY-18:03 | 17246.38 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.630854E+10 | 0.00 | 267.83 | 0.630854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17789.39 | 28-JUN-15:02 | 17789.39 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.116662E+11 | 0.00 | 399.17 | 0.109072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23708.15 | 15-JUL-18:03 | 19376.14 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.152467E+11 | 0.00 | 453.17 | 0.141061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24768.28 | 30-AUG-12:40 | 19656.81 | 29-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.544442E+10 | 0.00 | 235.50 | 0.511307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22992.79 | 14-SEP-12:50 | 17200.83 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.903569E+09 | 0.00 | 70.50 | 0.903569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14148.91 | 04-OCT-15:01 | 14148.91 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.218215E+09 | 0.00 | 15.50 | 0.196313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15659.16 | 04-NOV-15:01 | 13199.77 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454846E+11 | 0.00 | 1683.50 | 0.431106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.152467E+11 | 0.00 | 453.17 | 0.141061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24768.28 | 19656.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6748521.40 | 0.00 | 1.63 | 4977643.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11280.64 | 05-JAN-16:01 | 11280.64 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.169901E+09 | 0.00 | 40.14 | 0.101981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16995.06 | 08-FEB-16:01 | 16995.06 | 08-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.649117E+09 | 0.00 | 118.89 | 0.456742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16992.82 | 01-MAR-16:01 | 16992.82 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.202341E+10 | 0.00 | 303.28 | 0.121207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16998.20 | 25-APR-18:01 | 16998.20 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.389502E+10 | 0.00 | 490.15 | 0.219604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16996.77 | 20-MAY-18:01 | 16996.77 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.470185E+10 | 0.00 | 586.82 | 0.241218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17128.20 | 12-JUN-15:01 | 15382.44 | 21-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.760143E+10 | 0.00 | 677.09 | 0.424302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16910.18 | 16-JUL-15:01 | 15136.21 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.747709E+10 | 0.00 | 666.14 | 0.410248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17425.39 | 30-AUG-08:62 | 15365.60 | 02-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.479628E+10 | 0.00 | 542.88 | 0.246790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16628.63 | 23-SEP-08:61 | 15436.55 | 22-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.129170E+10 | 0.00 | 241.30 | 0.644015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16997.50 | 04-OCT-18:01 | 16997.50 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.141719E+09 | 0.00 | 36.57 | 58489309.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16718.97 | 05-NOV-15:01 | 14572.14 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 15025359.13 | 0.00 | 6.34 | 11389047.71 | 0.00 | 0.00 | 0.00 | 0.00 | 16425.79 | 02-DEC-16:02 | 16425.79 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327693E+11 | 0.00 | 3711.23 | 0.179113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6748521.40 | 0.00 | 1.63 | 4977643.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11280.64 | 11280.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.760143E+10 | 0.00 | 677.09 | 0.424302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17425.39 | 16998.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 964576.07 | 0.00 | 0.44 | 246009.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.99 | 20-JAN-16:04 | 702.01 | 08-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 32461181.57 | 0.00 | 11.40 | 15326552.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12957.58 | 26-FEB-16:01 | 12957.58 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.196520E+09 | 0.00 | 47.87 | 0.126220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15417.08 | 01-MAR-16:01 | 15417.08 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.106411E+10 | 0.00 | 193.12 | 0.591386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.45 | 25-APR-17:41 | 17823.45 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.221659E+10 | 0.00 | 372.86 | 0.104275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17850.20 | 21-MAY-17:41 | 17850.20 | 21-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.303101E+10 | 0.00 | 433.26 | 0.142715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15757.68 | 12-JUN-18:01 | 14841.19 | 18-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.502341E+10 | 0.00 | 492.83 | 0.267978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17435.45 | 15-JUL-21:51 | 15641.84 | 25-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.498674E+10 | 0.00 | 486.70 | 0.269284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16044.15 | 30-AUG-08:51 | 15123.79 | 02-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.227016E+10 | 0.00 | 376.72 | 0.905451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15960.61 | 24-SEP-18:11 | 15158.53 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.387851E+09 | 0.00 | 120.25 | 0.149394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15715.81 | 01-OCT-15:01 | 13796.42 | 08-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 26057814.65 | 0.00 | 9.80 | 8815396.73 | 0.00 | 0.00 | 0.00 | 0.00 | 15134.55 | 04-NOV-15:01 | 13111.50 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1213439.30 | 0.00 | 0.61 | 333125.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.18 | 28-DEC-19:06 | 450.46 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192371E+11 | 0.00 | 2545.86 | 0.963969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 964576.07 | 0.00 | 0.44 | 246009.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.99 | 450.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.502341E+10 | 0.00 | 492.83 | 0.269284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17850.20 | 17850.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.208797E+10 | 0.00 | 63.36 | 0.196471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30234.93 | 08-FEB-14:00 | 30234.93 | 08-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.868295E+10 | 0.00 | 209.81 | 0.810133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44001.97 | 02-MAR-13:30 | 44001.97 | 02-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.159708E+11 | 0.00 | 408.22 | 0.106238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42983.08 | 27-APR-13:05 | 37637.90 | 02-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.215685E+11 | 0.00 | 513.18 | 0.901378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42332.34 | 04-MAY-13:15 | 29891.55 | 14-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.247211E+11 | 0.00 | 590.50 | 0.790258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32176.41 | 28-JUN-13:00 | 17013.49 | 28-JUN-13:15 | 0.00 | 0.00 | 0.00 |
July | 0.356028E+11 | 0.00 | 691.93 | 0.128276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41314.87 | 31-JUL-13:00 | 26382.72 | 31-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.411049E+11 | 0.00 | 686.32 | 0.168780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51738.68 | 24-AUG-13:00 | 40516.96 | 24-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.337947E+11 | 0.00 | 593.39 | 0.153718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54376.18 | 14-SEP-13:15 | 45405.16 | 14-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.179519E+11 | 0.00 | 367.39 | 0.987473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54529.17 | 04-OCT-12:30 | 52410.75 | 04-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.231869E+10 | 0.00 | 61.62 | 0.113310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41742.43 | 04-NOV-13:25 | 26381.88 | 04-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.710587E+09 | 0.00 | 22.53 | 0.710587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24605.97 | 05-DEC-12:30 | 24605.97 | 05-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204515E+12 | 0.00 | 4208.25 | 0.944022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.411049E+11 | 0.00 | 691.93 | 0.168780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54529.17 | 52410.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.690167E+09 | 0.00 | 66.66 | 0.264891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60726.02 | 01-JAN-09:02 | 60726.02 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.248834E+10 | 0.00 | 130.47 | 0.942536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75865.12 | 25-FEB-09:02 | 69206.25 | 26-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.611912E+10 | 0.00 | 274.91 | 0.315801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77182.13 | 18-MAR-20:42 | 77182.13 | 18-MAR-20:42 | 0.00 | 0.00 | 0.00 |
April | 0.142038E+11 | 0.00 | 399.12 | 0.792161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79455.31 | 24-APR-18:01 | 79455.31 | 24-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.238213E+11 | 0.00 | 457.46 | 0.138280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82047.86 | 06-MAY-21:51 | 81780.93 | 21-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.302138E+11 | 0.00 | 418.04 | 0.185371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81663.25 | 12-JUN-18:01 | 75481.84 | 11-JUN-21:31 | 0.00 | 0.00 | 0.00 |
July | 0.362482E+11 | 0.00 | 429.34 | 0.228038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85982.90 | 26-JUL-21:51 | 75774.30 | 28-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.366127E+11 | 0.00 | 426.65 | 0.214308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86418.41 | 26-AUG-21:51 | 75506.01 | 06-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.237079E+11 | 0.00 | 396.74 | 0.118475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83167.80 | 15-SEP-21:51 | 74712.91 | 02-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.104494E+11 | 0.00 | 385.82 | 0.440008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80907.32 | 01-OCT-15:01 | 78846.92 | 04-OCT-21:12 | 0.00 | 0.00 | 0.00 |
November | 0.427181E+10 | 0.00 | 205.21 | 0.149235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76817.05 | 04-NOV-15:01 | 70673.06 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.587070E+09 | 0.00 | 59.84 | 0.277996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75115.67 | 03-DEC-09:02 | 75115.67 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189414E+12 | 0.00 | 3650.26 | 0.106905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.587070E+09 | 0.00 | 59.84 | 0.264891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60726.02 | 60726.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.366127E+11 | 0.00 | 457.46 | 0.228038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86418.41 | 81780.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3455668.15 | 0.00 | 2.05 | 835414.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.25 | 05-JAN-09:04 | 943.48 | 07-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 0.147637E+09 | 0.00 | 39.01 | 81254902.36 | 0.00 | 0.00 | 0.00 | 0.00 | 14510.78 | 08-FEB-16:01 | 14510.78 | 08-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.596708E+09 | 0.00 | 137.95 | 0.409277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15285.96 | 01-MAR-16:01 | 15285.96 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.207569E+10 | 0.00 | 340.12 | 0.113828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15288.64 | 19-APR-15:01 | 15288.64 | 19-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.335985E+10 | 0.00 | 482.83 | 0.173008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15290.82 | 21-MAY-18:01 | 15290.82 | 21-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.503269E+10 | 0.00 | 614.33 | 0.261662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.89 | 12-JUN-15:01 | 13885.08 | 11-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.660027E+10 | 0.00 | 688.40 | 0.348419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15706.32 | 16-JUL-15:01 | 14054.03 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.739686E+10 | 0.00 | 681.07 | 0.403336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15756.54 | 30-AUG-08:62 | 14028.25 | 18-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.431335E+10 | 0.00 | 529.40 | 0.218169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15515.68 | 24-SEP-15:01 | 13881.00 | 22-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.126419E+10 | 0.00 | 249.20 | 0.613379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15816.60 | 01-OCT-15:01 | 15288.72 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.145864E+09 | 0.00 | 40.48 | 45795876.04 | 0.00 | 0.00 | 0.00 | 0.00 | 14742.82 | 05-NOV-15:01 | 13771.21 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 39092897.76 | 0.00 | 13.21 | 20117557.80 | 0.00 | 0.00 | 0.00 | 0.00 | 7353.65 | 02-DEC-09:02 | 6404.50 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309757E+11 | 0.00 | 3818.04 | 0.163549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3455668.15 | 0.00 | 2.05 | 835414.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.25 | 943.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.739686E+10 | 0.00 | 688.40 | 0.403336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15816.60 | 15290.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1080998.00 | 0.00 | 0.49 | 225352.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.01 | 10-JAN-19:06 | 365.59 | 10-JAN-19:06 | 0.00 | 0.00 | 0.00 |
February | 13563619.66 | 0.00 | 8.21 | 6704772.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10215.09 | 27-FEB-16:01 | 10215.09 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.145562E+09 | 0.00 | 39.60 | 0.100462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13704.10 | 25-MAR-08:61 | 13704.10 | 25-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.113017E+10 | 0.00 | 233.90 | 0.591576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13680.10 | 25-APR-18:01 | 13680.10 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.208196E+10 | 0.00 | 362.81 | 0.103046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14479.53 | 06-MAY-08:51 | 14172.74 | 06-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.355457E+10 | 0.00 | 474.27 | 0.185624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14143.99 | 12-JUN-18:01 | 13480.55 | 10-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.445924E+10 | 0.00 | 515.57 | 0.232637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16547.05 | 31-JUL-08:32 | 15761.24 | 24-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.499500E+10 | 0.00 | 512.16 | 0.266218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16752.67 | 10-AUG-08:32 | 15390.40 | 10-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.217991E+10 | 0.00 | 363.32 | 0.100730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14201.21 | 15-SEP-21:51 | 14028.74 | 13-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.420269E+09 | 0.00 | 112.52 | 0.197661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14098.54 | 01-OCT-15:01 | 12759.19 | 07-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 22700594.43 | 0.00 | 8.74 | 6875209.22 | 0.00 | 0.00 | 0.00 | 0.00 | 13388.55 | 04-NOV-15:01 | 10906.87 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1424161.76 | 0.00 | 0.64 | 477427.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.93 | 28-DEC-19:06 | 987.19 | 03-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190055E+11 | 0.00 | 2632.23 | 0.978653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1080998.00 | 0.00 | 0.49 | 225352.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.01 | 365.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.499500E+10 | 0.00 | 515.57 | 0.266218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16752.67 | 15761.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1169933.87 | 0.00 | 0.76 | 905113.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.73 | 20-JAN-16:01 | 2842.73 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 43996989.88 | 0.00 | 31.62 | 26795563.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4429.18 | 08-FEB-16:01 | 4429.18 | 08-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.168730E+09 | 0.00 | 97.73 | 0.122154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.47 | 01-MAR-16:01 | 4428.47 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.525340E+09 | 0.00 | 258.71 | 0.334644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.95 | 30-APR-08:62 | 4429.68 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.100423E+10 | 0.00 | 436.51 | 0.611878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4429.19 | 20-MAY-18:01 | 4429.19 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.119817E+10 | 0.00 | 540.02 | 0.657602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4463.43 | 12-JUN-15:01 | 4011.39 | 29-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.194557E+10 | 0.00 | 660.55 | 0.114954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4454.72 | 15-JUL-08:61 | 3939.03 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.186339E+10 | 0.00 | 639.41 | 0.107478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4561.29 | 20-AUG-08:61 | 4008.70 | 17-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.117061E+10 | 0.00 | 484.37 | 0.649500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4556.52 | 23-SEP-08:61 | 4022.77 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.299977E+09 | 0.00 | 187.72 | 0.162214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4487.74 | 01-OCT-08:62 | 4429.49 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 35226680.35 | 0.00 | 26.57 | 16247630.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4412.42 | 05-NOV-15:01 | 3824.05 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 3380158.64 | 0.00 | 3.67 | 2538165.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4314.47 | 02-DEC-16:02 | 4314.47 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825978E+10 | 0.00 | 3367.66 | 0.480880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1169933.87 | 0.00 | 0.76 | 905113.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.73 | 2842.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.194557E+10 | 0.00 | 660.55 | 0.114954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4561.29 | 4429.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 91590.07 | 0.00 | 0.14 | 29270.76 | 0.00 | 0.00 | 0.00 | 0.00 | 466.76 | 05-JAN-16:04 | 182.85 | 05-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 6302887.95 | 0.00 | 8.94 | 2662616.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3377.92 | 26-FEB-16:01 | 3377.92 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 47033105.21 | 0.00 | 37.64 | 29879128.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.55 | 01-MAR-16:01 | 3988.55 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.273644E+09 | 0.00 | 163.32 | 0.164474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4617.69 | 25-APR-17:41 | 4617.69 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.576464E+09 | 0.00 | 331.71 | 0.295931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.00 | 21-MAY-17:41 | 4619.00 | 21-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.789051E+09 | 0.00 | 414.48 | 0.395966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4273.71 | 22-JUN-21:51 | 3892.44 | 18-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.133294E+10 | 0.00 | 501.59 | 0.738129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.46 | 26-JUL-21:51 | 4094.06 | 21-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.125933E+10 | 0.00 | 478.96 | 0.716890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4222.35 | 26-AUG-21:51 | 4167.08 | 06-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.531334E+09 | 0.00 | 332.07 | 0.228358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4212.41 | 13-SEP-21:51 | 3921.50 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 75482725.51 | 0.00 | 82.61 | 31840960.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4066.38 | 01-OCT-15:01 | 3535.27 | 08-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 5510879.13 | 0.00 | 5.06 | 1907869.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3915.83 | 04-NOV-15:01 | 3390.78 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 236836.20 | 0.00 | 0.28 | 116471.75 | 0.00 | 0.00 | 0.00 | 0.00 | 430.71 | 10-DEC-16:03 | 323.38 | 03-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489742E+10 | 0.00 | 2356.81 | 0.260618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 91590.07 | 0.00 | 0.14 | 29270.76 | 0.00 | 0.00 | 0.00 | 0.00 | 430.71 | 182.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133294E+10 | 0.00 | 501.59 | 0.738129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.00 | 4619.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.361188E+09 | 0.00 | 52.42 | 0.199338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19870.58 | 09-JAN-16:02 | 19870.58 | 09-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.154166E+10 | 0.00 | 160.33 | 0.951776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24295.69 | 19-FEB-16:01 | 24295.69 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.270176E+10 | 0.00 | 270.35 | 0.188959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24299.52 | 26-MAR-15:01 | 24299.52 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.429362E+10 | 0.00 | 415.20 | 0.233585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24112.11 | 30-APR-15:02 | 23959.25 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.558377E+10 | 0.00 | 523.32 | 0.281507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24294.31 | 14-MAY-18:01 | 24294.31 | 14-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.644855E+10 | 0.00 | 606.35 | 0.297152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24552.66 | 12-JUN-15:01 | 22280.37 | 23-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.931972E+10 | 0.00 | 673.35 | 0.460060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24920.32 | 16-JUL-15:01 | 21954.62 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.105335E+11 | 0.00 | 668.32 | 0.558711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24064.78 | 29-AUG-08:62 | 22221.37 | 17-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.839097E+10 | 0.00 | 576.58 | 0.468930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23413.11 | 23-SEP-08:61 | 22384.80 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.428769E+10 | 0.00 | 407.28 | 0.236762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24299.05 | 04-OCT-18:01 | 24299.05 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.106871E+10 | 0.00 | 125.55 | 0.498819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23048.98 | 05-NOV-08:62 | 21722.34 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.842779E+09 | 0.00 | 93.79 | 0.554735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24305.08 | 03-DEC-16:01 | 24305.08 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553739E+11 | 0.00 | 4572.86 | 0.294613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.361188E+09 | 0.00 | 52.42 | 0.199338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19870.58 | 19870.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105335E+11 | 0.00 | 673.35 | 0.558711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24920.32 | 24305.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.12 | 226.72 | 154.40 | 338.10 | 509.65 | 0.00 | 0.00 | 0.00 |
February | 586.49 | 363.88 | 222.60 | 597.01 | 447.39 | 0.00 | 0.00 | 0.00 |
March | 622.14 | 328.93 | 293.21 | 670.85 | 372.14 | 0.00 | 0.00 | 0.00 |
April | 657.40 | 282.14 | 375.26 | 758.55 | 299.29 | 0.00 | 0.00 | 0.00 |
May | 612.50 | 186.73 | 425.76 | 725.80 | 238.11 | 0.00 | 0.00 | 0.00 |
June | 554.17 | 148.32 | 405.85 | 679.49 | 176.19 | 0.00 | 0.00 | 0.00 |
July | 602.08 | 218.62 | 383.46 | 803.59 | 156.13 | 0.00 | 0.00 | 0.00 |
August | 641.87 | 294.94 | 346.93 | 876.64 | 151.03 | 0.00 | 0.00 | 0.00 |
September | 711.91 | 389.37 | 322.54 | 904.46 | 223.86 | 0.00 | 0.00 | 0.00 |
October | 643.99 | 394.27 | 249.72 | 744.82 | 314.45 | 0.00 | 0.00 | 0.00 |
November | 385.41 | 220.61 | 164.80 | 373.76 | 403.43 | 0.00 | 0.00 | 0.00 |
December | 403.36 | 260.85 | 142.51 | 395.99 | 511.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 566.59 | 275.74 | 290.86 | 655.98 | 316.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 381.12 | 148.32 | 142.51 | 338.10 | 151.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.91 | 394.27 | 425.76 | 904.46 | 511.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1073.21 | 638.43 | 434.78 | 937.61 | 1477.34 | 0.00 | 0.00 | 0.00 |
February | 1651.51 | 1024.67 | 626.84 | 1658.84 | 1309.41 | 0.00 | 0.00 | 0.00 |
March | 1751.91 | 926.24 | 825.67 | 1864.47 | 1110.63 | 0.00 | 0.00 | 0.00 |
April | 1851.19 | 794.48 | 1056.71 | 2105.27 | 905.69 | 0.00 | 0.00 | 0.00 |
May | 1724.75 | 525.83 | 1198.93 | 2010.45 | 731.25 | 0.00 | 0.00 | 0.00 |
June | 1560.51 | 417.65 | 1142.85 | 1873.56 | 558.22 | 0.00 | 0.00 | 0.00 |
July | 1695.42 | 615.61 | 1079.81 | 2227.95 | 495.35 | 0.00 | 0.00 | 0.00 |
August | 1807.46 | 830.52 | 976.94 | 2436.38 | 482.81 | 0.00 | 0.00 | 0.00 |
September | 2004.70 | 1096.43 | 908.26 | 2517.76 | 694.90 | 0.00 | 0.00 | 0.00 |
October | 1813.42 | 1110.24 | 703.18 | 2070.66 | 956.98 | 0.00 | 0.00 | 0.00 |
November | 1085.28 | 621.22 | 464.06 | 1035.32 | 1189.67 | 0.00 | 0.00 | 0.00 |
December | 1135.85 | 734.54 | 401.31 | 1100.55 | 1487.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1595.49 | 776.46 | 819.03 | 1820.53 | 948.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1073.21 | 417.65 | 401.31 | 937.61 | 482.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2004.70 | 1110.24 | 1198.93 | 2517.76 | 1487.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1394.16 | 829.35 | 564.80 | 1227.38 | 2046.28 | 0.00 | 0.00 | 0.00 |
February | 2145.41 | 1331.11 | 814.30 | 2180.90 | 1804.00 | 0.00 | 0.00 | 0.00 |
March | 2275.84 | 1203.24 | 1072.60 | 2455.41 | 1536.38 | 0.00 | 0.00 | 0.00 |
April | 2404.80 | 1032.08 | 1372.72 | 2773.02 | 1252.38 | 0.00 | 0.00 | 0.00 |
May | 2240.55 | 683.08 | 1557.47 | 2643.16 | 1020.93 | 0.00 | 0.00 | 0.00 |
June | 2027.19 | 542.56 | 1484.63 | 2457.00 | 783.13 | 0.00 | 0.00 | 0.00 |
July | 2202.45 | 799.71 | 1402.74 | 2933.32 | 690.00 | 0.00 | 0.00 | 0.00 |
August | 2348.00 | 1078.89 | 1269.10 | 3209.31 | 666.88 | 0.00 | 0.00 | 0.00 |
September | 2604.21 | 1424.33 | 1179.88 | 3314.75 | 960.64 | 0.00 | 0.00 | 0.00 |
October | 2355.74 | 1442.27 | 913.47 | 2723.48 | 1328.85 | 0.00 | 0.00 | 0.00 |
November | 1409.84 | 807.00 | 602.84 | 1352.25 | 1662.73 | 0.00 | 0.00 | 0.00 |
December | 1475.53 | 954.20 | 521.33 | 1442.74 | 2061.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2072.64 | 1008.67 | 1063.97 | 2393.57 | 1315.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1394.16 | 542.56 | 521.33 | 1227.38 | 666.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2604.21 | 1442.27 | 1557.47 | 3314.75 | 2061.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.73 | 102.21 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.85 | 89.71 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 133.07 | 74.84 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 149.12 | 60.72 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 141.52 | 48.33 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 132.24 | 35.13 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 157.99 | 30.04 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 173.77 | 27.93 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 179.92 | 43.50 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.92 | 62.19 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.73 | 80.30 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.28 | 101.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.72 | 62.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.73 | 27.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 179.92 | 102.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 22.45 | 206.67 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 65.90 | 179.09 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 114.13 | 142.58 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 211.48 | 110.67 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 301.08 | 87.38 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 298.15 | 63.53 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 402.51 | 54.46 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 338.21 | 51.34 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 253.68 | 81.17 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 114.25 | 119.95 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 33.98 | 159.04 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 26.97 | 204.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 182.66 | 121.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 22.45 | 51.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 402.51 | 206.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.57 | 114.26 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.26 | 98.92 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 17.45 | 77.55 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 37.67 | 59.51 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 59.22 | 46.43 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 70.27 | 33.75 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 74.76 | 29.90 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 63.67 | 27.84 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.70 | 45.51 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.47 | 64.95 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.20 | 86.71 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.29 | 111.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.21 | 66.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.29 | 27.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 74.76 | 114.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 23.94 | 204.75 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 68.95 | 176.41 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 117.90 | 140.61 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 214.36 | 110.07 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 299.78 | 88.91 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 295.50 | 66.13 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 398.04 | 58.63 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 337.10 | 54.38 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 253.77 | 83.28 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 117.67 | 118.25 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 35.77 | 157.19 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 28.72 | 202.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 183.37 | 121.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 23.94 | 54.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 398.04 | 204.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.27 | 35.85 | 24.42 | 53.22 | 81.85 | 0.00 | 0.00 | 0.00 |
February | 92.75 | 57.55 | 35.20 | 89.31 | 85.29 | 0.00 | 0.00 | 0.00 |
March | 98.39 | 52.02 | 46.37 | 96.83 | 84.01 | 0.00 | 0.00 | 0.00 |
April | 103.96 | 44.62 | 59.34 | 107.37 | 71.04 | 0.00 | 0.00 | 0.00 |
May | 96.86 | 29.53 | 67.33 | 101.26 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 87.64 | 23.46 | 64.18 | 92.53 | 46.52 | 0.00 | 0.00 | 0.00 |
July | 95.22 | 34.57 | 60.64 | 114.00 | 41.64 | 0.00 | 0.00 | 0.00 |
August | 101.51 | 46.64 | 54.87 | 126.48 | 40.50 | 0.00 | 0.00 | 0.00 |
September | 112.58 | 61.58 | 51.01 | 132.84 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 101.84 | 62.35 | 39.49 | 107.94 | 75.50 | 0.00 | 0.00 | 0.00 |
November | 60.95 | 34.89 | 26.06 | 53.34 | 84.84 | 0.00 | 0.00 | 0.00 |
December | 63.79 | 41.25 | 22.54 | 60.52 | 89.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.60 | 43.61 | 46.00 | 94.66 | 67.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.27 | 23.46 | 22.54 | 53.22 | 40.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.58 | 62.35 | 67.33 | 132.84 | 89.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.60 | 0.00 | 13.60 | 0.27 | 97.05 | 0.00 | 0.00 | 0.00 |
February | 21.15 | 0.00 | 21.15 | 3.62 | 82.96 | 0.00 | 0.00 | 0.00 |
March | 31.17 | 0.00 | 31.17 | 13.46 | 64.24 | 0.00 | 0.00 | 0.00 |
April | 44.26 | 0.27 | 43.99 | 31.00 | 48.11 | 0.00 | 0.00 | 0.00 |
May | 56.79 | 1.71 | 55.08 | 50.37 | 36.50 | 0.00 | 0.00 | 0.00 |
June | 59.76 | 4.00 | 55.77 | 59.50 | 26.18 | 0.00 | 0.00 | 0.00 |
July | 56.88 | 4.58 | 52.30 | 64.64 | 22.16 | 0.00 | 0.00 | 0.00 |
August | 46.11 | 1.38 | 44.72 | 54.54 | 20.79 | 0.00 | 0.00 | 0.00 |
September | 35.69 | 0.03 | 35.66 | 31.64 | 34.92 | 0.00 | 0.00 | 0.00 |
October | 24.44 | 0.00 | 24.44 | 12.28 | 53.38 | 0.00 | 0.00 | 0.00 |
November | 15.39 | 0.00 | 15.39 | 2.12 | 73.72 | 0.00 | 0.00 | 0.00 |
December | 11.55 | 0.00 | 11.55 | 0.11 | 94.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.80 | 1.00 | 33.80 | 27.11 | 54.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.55 | 0.00 | 11.55 | 0.11 | 20.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.76 | 4.58 | 55.77 | 64.64 | 97.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 16.48 | 204.61 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 58.54 | 175.49 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 115.98 | 137.84 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 221.64 | 106.28 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 252.06 | 84.73 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 326.61 | 60.92 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 320.96 | 50.01 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 324.78 | 47.85 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 213.99 | 77.58 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 112.78 | 116.77 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 31.70 | 156.70 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 21.54 | 200.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 168.65 | 118.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 16.48 | 47.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 326.61 | 204.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.70 | 102.08 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.59 | 89.50 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 132.31 | 74.64 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 147.96 | 60.51 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 141.37 | 47.71 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 131.17 | 34.83 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 158.03 | 29.24 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 173.25 | 27.52 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 179.77 | 42.78 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.41 | 61.91 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.61 | 80.17 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.25 | 101.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.33 | 62.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.70 | 27.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 179.77 | 102.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.55 | 114.20 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.16 | 98.75 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 16.82 | 77.39 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 36.65 | 59.40 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 59.94 | 45.38 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 69.70 | 33.10 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 75.88 | 28.26 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 62.88 | 27.02 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 37.01 | 43.96 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 14.98 | 64.49 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.08 | 86.51 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.26 | 111.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.08 | 65.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.26 | 27.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 75.88 | 114.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 17.09 | 201.87 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 60.57 | 171.54 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 119.57 | 135.49 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 224.50 | 105.43 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 252.85 | 85.51 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 325.63 | 63.21 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 319.17 | 52.96 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 323.50 | 50.36 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 215.67 | 78.44 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 116.25 | 114.62 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 32.88 | 154.10 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 22.33 | 197.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 169.72 | 117.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 17.09 | 50.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 325.63 | 201.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.39 | 157.27 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 5.61 | 134.25 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 21.19 | 103.31 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 49.13 | 78.37 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 79.18 | 61.55 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 93.14 | 44.96 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 99.97 | 39.46 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 82.80 | 38.56 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 48.11 | 60.80 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 18.72 | 87.64 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 3.38 | 118.60 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.15 | 153.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 42.04 | 89.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.15 | 38.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 99.97 | 157.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.93 | 0.00 | 7.93 | 0.14 | 57.98 | 0.00 | 0.00 | 0.00 |
February | 12.34 | 0.00 | 12.34 | 2.07 | 49.49 | 0.00 | 0.00 | 0.00 |
March | 18.19 | 0.00 | 18.19 | 7.81 | 38.09 | 0.00 | 0.00 | 0.00 |
April | 25.83 | 0.16 | 25.67 | 18.11 | 28.89 | 0.00 | 0.00 | 0.00 |
May | 33.14 | 0.99 | 32.14 | 29.19 | 22.69 | 0.00 | 0.00 | 0.00 |
June | 34.87 | 2.33 | 32.54 | 34.33 | 16.57 | 0.00 | 0.00 | 0.00 |
July | 33.19 | 2.67 | 30.52 | 36.85 | 14.55 | 0.00 | 0.00 | 0.00 |
August | 26.90 | 0.81 | 26.10 | 30.52 | 14.21 | 0.00 | 0.00 | 0.00 |
September | 20.82 | 0.02 | 20.81 | 17.74 | 22.41 | 0.00 | 0.00 | 0.00 |
October | 14.26 | 0.00 | 14.26 | 6.90 | 32.31 | 0.00 | 0.00 | 0.00 |
November | 8.98 | 0.00 | 8.98 | 1.25 | 43.72 | 0.00 | 0.00 | 0.00 |
December | 6.74 | 0.00 | 6.74 | 0.05 | 56.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.31 | 0.59 | 19.72 | 15.50 | 33.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.74 | 0.00 | 6.74 | 0.05 | 14.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.87 | 2.67 | 32.54 | 36.85 | 57.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.16 | 20.92 | 14.24 | 30.98 | 50.74 | 0.00 | 0.00 | 0.00 |
February | 54.11 | 33.57 | 20.54 | 55.40 | 43.84 | 0.00 | 0.00 | 0.00 |
March | 57.40 | 30.35 | 27.05 | 62.64 | 36.19 | 0.00 | 0.00 | 0.00 |
April | 60.65 | 26.03 | 34.62 | 70.76 | 29.26 | 0.00 | 0.00 | 0.00 |
May | 56.51 | 17.23 | 39.28 | 67.29 | 24.00 | 0.00 | 0.00 | 0.00 |
June | 51.12 | 13.68 | 37.44 | 62.68 | 18.04 | 0.00 | 0.00 | 0.00 |
July | 55.54 | 20.17 | 35.38 | 74.69 | 15.87 | 0.00 | 0.00 | 0.00 |
August | 59.22 | 27.21 | 32.01 | 81.69 | 15.18 | 0.00 | 0.00 | 0.00 |
September | 65.68 | 35.92 | 29.76 | 84.69 | 22.09 | 0.00 | 0.00 | 0.00 |
October | 59.41 | 36.37 | 23.04 | 69.60 | 30.48 | 0.00 | 0.00 | 0.00 |
November | 35.56 | 20.35 | 15.20 | 34.69 | 39.70 | 0.00 | 0.00 | 0.00 |
December | 37.21 | 24.06 | 13.15 | 36.75 | 50.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.27 | 25.44 | 26.83 | 61.01 | 31.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.16 | 13.68 | 13.15 | 30.98 | 15.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.68 | 36.37 | 39.28 | 84.69 | 50.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.43 | 56.77 | 38.66 | 84.09 | 137.73 | 0.00 | 0.00 | 0.00 |
February | 146.85 | 91.12 | 55.74 | 150.38 | 118.98 | 0.00 | 0.00 | 0.00 |
March | 155.78 | 82.36 | 73.42 | 170.01 | 98.24 | 0.00 | 0.00 | 0.00 |
April | 164.61 | 70.65 | 93.96 | 192.06 | 79.43 | 0.00 | 0.00 | 0.00 |
May | 153.37 | 46.76 | 106.61 | 182.63 | 65.14 | 0.00 | 0.00 | 0.00 |
June | 138.76 | 37.14 | 101.62 | 170.14 | 48.96 | 0.00 | 0.00 | 0.00 |
July | 150.76 | 54.74 | 96.02 | 202.72 | 43.07 | 0.00 | 0.00 | 0.00 |
August | 160.72 | 73.85 | 86.87 | 221.71 | 41.21 | 0.00 | 0.00 | 0.00 |
September | 178.26 | 97.50 | 80.76 | 229.85 | 59.95 | 0.00 | 0.00 | 0.00 |
October | 161.25 | 98.72 | 62.53 | 188.91 | 82.72 | 0.00 | 0.00 | 0.00 |
November | 96.50 | 55.24 | 41.26 | 94.15 | 107.76 | 0.00 | 0.00 | 0.00 |
December | 101.00 | 65.32 | 35.69 | 99.74 | 137.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.87 | 69.04 | 72.83 | 165.59 | 84.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.43 | 37.14 | 35.69 | 84.09 | 41.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 178.26 | 98.72 | 106.61 | 229.85 | 137.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.78 | 101.59 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.54 | 89.20 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 132.38 | 74.46 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 147.80 | 60.67 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 139.97 | 48.24 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 130.67 | 34.99 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 156.37 | 29.89 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 172.46 | 27.58 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 178.99 | 43.06 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.22 | 61.61 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.68 | 79.59 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.29 | 100.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 128.88 | 62.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.78 | 27.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 178.99 | 101.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 22.69 | 205.00 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 65.68 | 177.68 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 113.25 | 141.54 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 209.08 | 110.40 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 297.80 | 87.05 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 294.81 | 63.13 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 398.84 | 54.04 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 335.60 | 50.59 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 251.93 | 80.17 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 113.47 | 118.53 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 34.11 | 157.20 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 27.08 | 202.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 181.12 | 120.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 22.69 | 50.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 398.84 | 205.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.63 | 113.20 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.39 | 98.08 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 17.50 | 76.95 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 37.17 | 59.39 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 57.91 | 46.70 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 68.73 | 34.09 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 73.13 | 30.48 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 62.93 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.16 | 45.65 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.65 | 64.09 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.33 | 85.55 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.35 | 109.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 31.74 | 65.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.35 | 27.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 73.13 | 113.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 24.16 | 203.27 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 69.04 | 175.02 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 117.37 | 139.45 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 212.06 | 109.92 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 295.77 | 89.41 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 291.20 | 66.74 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 393.16 | 59.67 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 334.13 | 54.37 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 251.57 | 83.25 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 117.27 | 116.70 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 36.06 | 155.33 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 29.01 | 200.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 181.63 | 120.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 24.16 | 54.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 393.16 | 203.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.51 | 65.74 | 44.77 | 95.20 | 155.20 | 0.00 | 0.00 | 0.00 |
February | 170.06 | 105.52 | 64.55 | 168.72 | 136.32 | 0.00 | 0.00 | 0.00 |
March | 180.40 | 95.38 | 85.02 | 190.07 | 113.30 | 0.00 | 0.00 | 0.00 |
April | 190.63 | 81.81 | 108.82 | 214.27 | 90.59 | 0.00 | 0.00 | 0.00 |
May | 177.61 | 54.15 | 123.46 | 205.36 | 70.56 | 0.00 | 0.00 | 0.00 |
June | 160.69 | 43.01 | 117.69 | 192.42 | 50.72 | 0.00 | 0.00 | 0.00 |
July | 174.59 | 63.39 | 111.20 | 231.35 | 42.37 | 0.00 | 0.00 | 0.00 |
August | 186.12 | 85.52 | 100.60 | 253.86 | 39.53 | 0.00 | 0.00 | 0.00 |
September | 206.43 | 112.91 | 93.53 | 261.47 | 63.32 | 0.00 | 0.00 | 0.00 |
October | 186.74 | 114.33 | 72.41 | 212.08 | 93.95 | 0.00 | 0.00 | 0.00 |
November | 111.76 | 63.97 | 47.79 | 105.91 | 122.29 | 0.00 | 0.00 | 0.00 |
December | 116.96 | 75.64 | 41.33 | 112.47 | 154.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.30 | 79.96 | 84.34 | 187.01 | 94.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.51 | 43.01 | 41.33 | 95.20 | 39.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 206.43 | 114.33 | 123.46 | 261.47 | 155.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.52 | 1000.64 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 18.79 | 866.77 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 83.94 | 678.50 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 220.02 | 515.37 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 378.54 | 392.81 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 452.83 | 287.69 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 502.47 | 248.52 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 417.03 | 242.67 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 230.89 | 382.79 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 74.98 | 581.57 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 9.43 | 784.11 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.14 | 977.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 200.29 | 578.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.14 | 242.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 502.47 | 1000.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.27 | 1033.20 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 16.44 | 895.83 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 76.05 | 698.98 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 209.16 | 529.49 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 367.41 | 402.51 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 441.50 | 295.16 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 492.84 | 255.32 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 407.72 | 250.11 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 222.48 | 393.94 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 68.04 | 600.84 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 7.86 | 812.71 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.07 | 1009.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 193.63 | 596.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.07 | 250.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 492.84 | 1033.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.94 | 119.59 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 7.09 | 104.23 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 21.97 | 82.40 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 47.64 | 64.59 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 75.95 | 50.87 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 89.48 | 38.84 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 97.64 | 33.27 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 84.07 | 31.83 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 52.23 | 45.63 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 21.11 | 69.03 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 5.26 | 90.93 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.73 | 116.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 42.22 | 70.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.73 | 31.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 97.64 | 119.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.53 | 25.44 | 76.09 | 38.49 | 428.93 | 0.00 | 0.00 | 0.00 |
February | 187.04 | 66.25 | 120.79 | 132.40 | 368.17 | 0.00 | 0.00 | 0.00 |
March | 280.32 | 101.65 | 178.67 | 262.41 | 293.69 | 0.00 | 0.00 | 0.00 |
April | 432.94 | 179.66 | 253.29 | 494.99 | 233.58 | 0.00 | 0.00 | 0.00 |
May | 460.98 | 160.51 | 300.48 | 566.06 | 191.06 | 0.00 | 0.00 | 0.00 |
June | 551.74 | 240.14 | 311.60 | 724.37 | 146.40 | 0.00 | 0.00 | 0.00 |
July | 514.55 | 231.34 | 283.21 | 718.75 | 123.39 | 0.00 | 0.00 | 0.00 |
August | 505.11 | 252.66 | 252.44 | 727.46 | 118.82 | 0.00 | 0.00 | 0.00 |
September | 374.06 | 172.82 | 201.24 | 492.34 | 166.80 | 0.00 | 0.00 | 0.00 |
October | 244.59 | 104.51 | 140.08 | 260.24 | 250.37 | 0.00 | 0.00 | 0.00 |
November | 119.70 | 33.90 | 85.80 | 76.80 | 330.38 | 0.00 | 0.00 | 0.00 |
December | 97.92 | 31.47 | 66.44 | 50.53 | 419.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.14 | 133.66 | 189.48 | 380.01 | 255.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.92 | 25.44 | 66.44 | 38.49 | 118.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.74 | 252.66 | 311.60 | 727.46 | 428.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 70.33 | 108.15 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 124.63 | 94.99 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 141.49 | 79.63 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 161.32 | 65.95 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 157.38 | 53.16 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 149.71 | 41.36 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 178.05 | 35.11 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 193.56 | 33.19 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 197.19 | 45.34 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 157.83 | 67.00 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 79.35 | 85.40 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 83.02 | 107.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 141.23 | 67.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 70.33 | 33.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 197.19 | 108.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.30 | 161.01 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 4.84 | 138.10 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 18.96 | 106.40 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 45.43 | 81.07 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 74.72 | 63.34 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 87.80 | 46.95 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 94.65 | 41.37 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 78.47 | 40.30 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 44.94 | 62.32 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 16.77 | 90.00 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 2.81 | 122.36 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.10 | 156.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 39.36 | 92.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.10 | 40.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 94.65 | 161.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.25 | 0.00 | 19.25 | 0.27 | 144.04 | 0.00 | 0.00 | 0.00 |
February | 29.96 | 0.00 | 29.96 | 4.33 | 123.56 | 0.00 | 0.00 | 0.00 |
March | 44.14 | 0.00 | 44.14 | 16.96 | 95.19 | 0.00 | 0.00 | 0.00 |
April | 62.68 | 0.39 | 62.30 | 40.64 | 72.53 | 0.00 | 0.00 | 0.00 |
May | 80.42 | 2.41 | 78.01 | 66.85 | 56.67 | 0.00 | 0.00 | 0.00 |
June | 84.63 | 5.66 | 78.97 | 78.56 | 42.01 | 0.00 | 0.00 | 0.00 |
July | 80.56 | 6.48 | 74.07 | 84.69 | 37.01 | 0.00 | 0.00 | 0.00 |
August | 65.30 | 1.96 | 63.34 | 70.21 | 36.05 | 0.00 | 0.00 | 0.00 |
September | 50.54 | 0.04 | 50.50 | 40.21 | 55.76 | 0.00 | 0.00 | 0.00 |
October | 34.60 | 0.00 | 34.60 | 15.00 | 80.52 | 0.00 | 0.00 | 0.00 |
November | 21.80 | 0.00 | 21.80 | 2.51 | 109.47 | 0.00 | 0.00 | 0.00 |
December | 16.36 | 0.00 | 16.36 | 0.09 | 140.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.28 | 1.42 | 47.86 | 35.22 | 82.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.36 | 0.00 | 16.36 | 0.09 | 36.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.63 | 6.48 | 78.97 | 84.69 | 144.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 281.32 | 167.35 | 113.97 | 243.36 | 416.23 | 0.00 | 0.00 | 0.00 |
February | 432.91 | 268.60 | 164.31 | 435.21 | 359.62 | 0.00 | 0.00 | 0.00 |
March | 459.23 | 242.79 | 216.43 | 491.02 | 298.73 | 0.00 | 0.00 | 0.00 |
April | 485.25 | 208.26 | 277.00 | 551.98 | 243.05 | 0.00 | 0.00 | 0.00 |
May | 452.11 | 137.83 | 314.28 | 523.25 | 198.60 | 0.00 | 0.00 | 0.00 |
June | 409.06 | 109.48 | 299.58 | 484.48 | 151.70 | 0.00 | 0.00 | 0.00 |
July | 444.42 | 161.37 | 283.05 | 580.24 | 133.90 | 0.00 | 0.00 | 0.00 |
August | 473.79 | 217.70 | 256.09 | 638.56 | 127.52 | 0.00 | 0.00 | 0.00 |
September | 525.49 | 287.41 | 238.08 | 666.04 | 181.63 | 0.00 | 0.00 | 0.00 |
October | 475.35 | 291.03 | 184.33 | 547.05 | 250.91 | 0.00 | 0.00 | 0.00 |
November | 284.48 | 162.84 | 121.64 | 271.76 | 327.86 | 0.00 | 0.00 | 0.00 |
December | 297.74 | 192.54 | 105.20 | 289.65 | 413.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 418.23 | 203.53 | 214.69 | 477.04 | 258.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.32 | 109.48 | 105.20 | 243.36 | 127.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.49 | 291.03 | 314.28 | 666.04 | 416.23 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.905574E+09 | 0.136504E+10 |
February | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.144429E+10 | 0.108231E+10 |
March | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.179681E+10 | 0.996730E+09 |
April | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.196615E+10 | 0.775757E+09 |
May | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.194398E+10 | 0.637749E+09 |
June | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.176125E+10 | 0.456697E+09 |
July | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.215233E+10 | 0.418185E+09 |
August | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.234799E+10 | 0.404525E+09 |
September | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.234435E+10 | 0.580234E+09 |
October | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.199492E+10 | 0.842213E+09 |
November | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.968782E+09 | 0.104569E+10 |
December | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.106063E+10 | 0.137022E+10 |
Annual Sum or Average | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.206871E+11 | 0.997536E+10 |
Minimum of Months | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.905574E+09 | 0.404525E+09 |
Maximum of Months | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.234799E+10 | 0.137022E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.251131E+10 | 0.395690E+10 |
February | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.401307E+10 | 0.316771E+10 |
March | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.499379E+10 | 0.297471E+10 |
April | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.545685E+10 | 0.234755E+10 |
May | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.538478E+10 | 0.195859E+10 |
June | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.485627E+10 | 0.144690E+10 |
July | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.596733E+10 | 0.132676E+10 |
August | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.652559E+10 | 0.129317E+10 |
September | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.652603E+10 | 0.180117E+10 |
October | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.554606E+10 | 0.256317E+10 |
November | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.268356E+10 | 0.308361E+10 |
December | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.294771E+10 | 0.398303E+10 |
Annual Sum or Average | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.574123E+11 | 0.299033E+11 |
Minimum of Months | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.251131E+10 | 0.129317E+10 |
Maximum of Months | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.652603E+10 | 0.398303E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.328740E+10 | 0.548075E+10 |
February | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.527604E+10 | 0.436423E+10 |
March | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.657657E+10 | 0.411503E+10 |
April | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.718768E+10 | 0.324618E+10 |
May | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.707944E+10 | 0.273445E+10 |
June | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.636854E+10 | 0.202988E+10 |
July | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.785662E+10 | 0.184810E+10 |
August | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.859582E+10 | 0.178618E+10 |
September | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.859184E+10 | 0.248998E+10 |
October | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.729457E+10 | 0.355919E+10 |
November | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.350503E+10 | 0.430981E+10 |
December | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.386422E+10 | 0.552077E+10 |
Annual Sum or Average | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.754838E+11 | 0.414845E+11 |
Minimum of Months | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.328740E+10 | 0.178618E+10 |
Maximum of Months | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.859582E+10 | 0.552077E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.181419E+09 | 0.273768E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.287513E+09 | 0.217038E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.356425E+09 | 0.200443E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.386522E+09 | 0.157381E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.379040E+09 | 0.129455E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.342778E+09 | 91059377.91 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.423169E+09 | 80461162.65 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.465420E+09 | 74809015.94 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.466361E+09 | 0.112764E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.396180E+09 | 0.166582E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.193695E+09 | 0.208142E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.212352E+09 | 0.272522E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.409087E+10 | 0.198442E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.181419E+09 | 74809015.94 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.466361E+09 | 0.273768E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 60132993.14 | 0.553539E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.159421E+09 | 0.433264E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.305690E+09 | 0.381878E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.548156E+09 | 0.286853E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.806425E+09 | 0.234051E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.772797E+09 | 0.164658E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.107810E+10 | 0.145870E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.905872E+09 | 0.137506E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.657534E+09 | 0.210396E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.306007E+09 | 0.321285E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 88088620.75 | 0.412227E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 72224020.38 | 0.547815E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.576044E+10 | 0.382934E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 60132993.14 | 0.137506E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.107810E+10 | 0.553539E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1527956.93 | 0.306041E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 12728032.96 | 0.239303E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 46742547.09 | 0.207708E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 97653157.71 | 0.154262E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.158618E+09 | 0.124371E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.182134E+09 | 87472824.65 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.200249E+09 | 80075775.22 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.170541E+09 | 74571530.12 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 95121242.22 | 0.117972E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 41421999.05 | 0.173963E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8293398.74 | 0.224740E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 789787.41 | 0.298297E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.101582E+10 | 0.208878E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 789787.41 | 74571530.12 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.200249E+09 | 0.306041E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 64129099.77 | 0.548394E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.166814E+09 | 0.426783E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.315794E+09 | 0.376599E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.555622E+09 | 0.285306E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.802923E+09 | 0.238133E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.765926E+09 | 0.171397E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.106611E+10 | 0.157047E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.902899E+09 | 0.145664E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.657772E+09 | 0.215854E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.315164E+09 | 0.316708E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 92710028.14 | 0.407430E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 76914649.58 | 0.541921E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.578278E+10 | 0.383124E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 64129099.77 | 0.145664E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.106611E+10 | 0.548394E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.142538E+09 | 0.219216E+09 |
February | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.216052E+09 | 0.206327E+09 |
March | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.259359E+09 | 0.225000E+09 |
April | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.278315E+09 | 0.184127E+09 |
May | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.271210E+09 | 0.157549E+09 |
June | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.239828E+09 | 0.120579E+09 |
July | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.305327E+09 | 0.111523E+09 |
August | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.338756E+09 | 0.108468E+09 |
September | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.344325E+09 | 0.144355E+09 |
October | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.289117E+09 | 0.202222E+09 |
November | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.138263E+09 | 0.219913E+09 |
December | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.162097E+09 | 0.239398E+09 |
Annual Sum or Average | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.298519E+10 | 0.213868E+10 |
Minimum of Months | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.138263E+09 | 0.108468E+09 |
Maximum of Months | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.344325E+09 | 0.239398E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36413225.08 | 0.00 | 36413225.08 | 726333.45 | 0.259945E+09 |
February | 51176770.43 | 0.00 | 51176770.43 | 8757240.63 | 0.200705E+09 |
March | 83487367.90 | 272.21 | 83487095.69 | 36047308.75 | 0.172068E+09 |
April | 0.114728E+09 | 705856.95 | 0.114022E+09 | 80344405.17 | 0.124705E+09 |
May | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.134920E+09 | 97761102.10 |
June | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.154221E+09 | 67864347.01 |
July | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.173122E+09 | 59345057.49 |
August | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.146081E+09 | 55692977.46 |
September | 92504439.09 | 69295.25 | 92435143.84 | 82007286.71 | 90516829.20 |
October | 65447658.79 | 0.00 | 65447658.79 | 32888265.30 | 0.142976E+09 |
November | 39895669.45 | 0.00 | 39895669.45 | 5484789.06 | 0.191075E+09 |
December | 30941853.50 | 0.00 | 30941853.50 | 303307.28 | 0.253200E+09 |
Annual Sum or Average | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.854902E+09 | 0.171585E+10 |
Minimum of Months | 30941853.50 | 0.00 | 30941853.50 | 303307.28 | 55692977.46 |
Maximum of Months | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.173122E+09 | 0.259945E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 44133839.45 | 0.548034E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.141616E+09 | 0.424554E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.310641E+09 | 0.369192E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.574485E+09 | 0.275484E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.675109E+09 | 0.226951E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.846581E+09 | 0.157903E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.859650E+09 | 0.133940E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.869891E+09 | 0.128173E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.554661E+09 | 0.201100E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.302077E+09 | 0.312749E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 82155033.80 | 0.406179E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 57701682.54 | 0.537799E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.531870E+10 | 0.372206E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 44133839.45 | 0.128173E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.869891E+09 | 0.548034E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.181335E+09 | 0.273404E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.286898E+09 | 0.216507E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.354391E+09 | 0.199904E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.383513E+09 | 0.156846E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.378641E+09 | 0.127776E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.339985E+09 | 90284246.05 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.423265E+09 | 78310417.44 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.464031E+09 | 73715813.04 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.465967E+09 | 0.110878E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.394820E+09 | 0.165817E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.193380E+09 | 0.207798E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.212257E+09 | 0.272087E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.407848E+10 | 0.197333E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.181335E+09 | 73715813.04 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.465967E+09 | 0.273404E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1467974.85 | 0.305878E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 12472701.71 | 0.238899E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 45059580.09 | 0.207288E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 94992760.03 | 0.153964E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.160532E+09 | 0.121535E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.180659E+09 | 85806446.70 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.203236E+09 | 75682445.55 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.168420E+09 | 72381275.92 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 95922690.72 | 0.113949E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 40131423.86 | 0.172727E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 7979436.19 | 0.224231E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 702050.00 | 0.297924E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.101158E+10 | 0.207026E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 702050.00 | 72381275.92 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.203236E+09 | 0.305878E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 45768014.08 | 0.540685E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.146523E+09 | 0.414995E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.320246E+09 | 0.362903E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.581903E+09 | 0.273287E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.677230E+09 | 0.229036E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.844034E+09 | 0.163847E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.854865E+09 | 0.141858E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.866454E+09 | 0.134872E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.559009E+09 | 0.203309E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.311357E+09 | 0.306997E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 85236888.10 | 0.399439E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 59808761.89 | 0.529163E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.535243E+10 | 0.370039E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 45768014.08 | 0.134872E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.866454E+09 | 0.540685E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 1033385.08 | 0.421235E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 13582315.73 | 0.324784E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 56749144.26 | 0.276713E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.127349E+09 | 0.203139E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.212084E+09 | 0.164861E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.241406E+09 | 0.116525E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.267773E+09 | 0.105697E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.221759E+09 | 0.103277E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.124703E+09 | 0.157582E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 50151725.41 | 0.234741E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 8771454.25 | 0.307412E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 392467.55 | 0.410361E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.132575E+10 | 0.282633E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 392467.55 | 0.103277E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.267773E+09 | 0.421235E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21247080.64 | 0.00 | 21247080.64 | 380948.53 | 0.155285E+09 |
February | 29861594.68 | 0.00 | 29861594.68 | 5007003.98 | 0.119729E+09 |
March | 48714796.18 | 158.83 | 48714637.34 | 20920084.37 | 0.102008E+09 |
April | 66943790.08 | 411866.83 | 66531923.25 | 46946072.39 | 74885626.59 |
May | 88748888.58 | 2664758.02 | 86084130.55 | 78182964.53 | 60774646.86 |
June | 90387603.67 | 6046854.08 | 84340749.59 | 88992277.88 | 42956057.07 |
July | 88899508.73 | 7156640.74 | 81742867.99 | 98712163.35 | 38964280.88 |
August | 72062069.48 | 2164206.09 | 69897863.39 | 81749410.16 | 38072101.86 |
September | 53976248.26 | 40433.71 | 53935814.54 | 45970820.96 | 58091126.28 |
October | 38188643.85 | 0.00 | 38188643.85 | 18488002.61 | 86535336.93 |
November | 23279083.47 | 0.00 | 23279083.47 | 3233521.23 | 0.113325E+09 |
December | 18054540.76 | 0.00 | 18054540.76 | 144679.79 | 0.151276E+09 |
Annual Sum or Average | 0.640364E+09 | 18484918.30 | 0.621879E+09 | 0.488728E+09 | 0.104190E+10 |
Minimum of Months | 18054540.76 | 0.00 | 18054540.76 | 144679.79 | 38072101.86 |
Maximum of Months | 90387603.67 | 7156640.74 | 86084130.55 | 98712163.35 | 0.155285E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94172104.10 | 56020951.86 | 38151152.24 | 82978975.29 | 0.135913E+09 |
February | 0.130893E+09 | 81212052.17 | 49681081.31 | 0.134033E+09 | 0.106046E+09 |
March | 0.153728E+09 | 81276128.21 | 72451757.76 | 0.167772E+09 | 96942417.47 |
April | 0.157199E+09 | 67465641.93 | 89733781.59 | 0.183415E+09 | 75850886.33 |
May | 0.151345E+09 | 46140406.03 | 0.105205E+09 | 0.180219E+09 | 64276830.22 |
June | 0.132516E+09 | 35466261.44 | 97049331.00 | 0.162476E+09 | 46754315.26 |
July | 0.148771E+09 | 54018417.70 | 94752617.30 | 0.200046E+09 | 42504159.61 |
August | 0.158603E+09 | 72876646.06 | 85725869.59 | 0.218788E+09 | 40662304.34 |
September | 0.170235E+09 | 93106622.21 | 77128015.79 | 0.219506E+09 | 57249911.53 |
October | 0.159125E+09 | 97421719.72 | 61703299.94 | 0.186418E+09 | 81633034.98 |
November | 92159449.27 | 52752675.23 | 39406774.04 | 89912530.35 | 0.102911E+09 |
December | 99668866.61 | 64454268.94 | 35214597.67 | 98428384.13 | 0.135299E+09 |
Annual Sum or Average | 0.164841E+10 | 0.802212E+09 | 0.846203E+09 | 0.192399E+10 | 0.986042E+09 |
Minimum of Months | 92159449.27 | 35466261.44 | 35214597.67 | 82978975.29 | 40662304.34 |
Maximum of Months | 0.170235E+09 | 97421719.72 | 0.105205E+09 | 0.219506E+09 | 0.135913E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255602E+09 | 0.152052E+09 | 0.103550E+09 | 0.225222E+09 | 0.368895E+09 |
February | 0.355271E+09 | 0.220426E+09 | 0.134845E+09 | 0.363792E+09 | 0.287830E+09 |
March | 0.417249E+09 | 0.220600E+09 | 0.196649E+09 | 0.455368E+09 | 0.263122E+09 |
April | 0.426671E+09 | 0.183116E+09 | 0.243556E+09 | 0.497825E+09 | 0.205875E+09 |
May | 0.410781E+09 | 0.125234E+09 | 0.285547E+09 | 0.489152E+09 | 0.174460E+09 |
June | 0.359674E+09 | 96262688.00 | 0.263412E+09 | 0.440994E+09 | 0.126901E+09 |
July | 0.403795E+09 | 0.146617E+09 | 0.257178E+09 | 0.542965E+09 | 0.115365E+09 |
August | 0.430480E+09 | 0.197802E+09 | 0.232678E+09 | 0.593836E+09 | 0.110366E+09 |
September | 0.462052E+09 | 0.252710E+09 | 0.209341E+09 | 0.595783E+09 | 0.155388E+09 |
October | 0.431898E+09 | 0.264422E+09 | 0.167475E+09 | 0.505975E+09 | 0.221569E+09 |
November | 0.250140E+09 | 0.143182E+09 | 0.106958E+09 | 0.244041E+09 | 0.279322E+09 |
December | 0.270522E+09 | 0.174942E+09 | 95579621.07 | 0.267155E+09 | 0.367229E+09 |
Annual Sum or Average | 0.447413E+10 | 0.217737E+10 | 0.229677E+10 | 0.522211E+10 | 0.267632E+10 |
Minimum of Months | 0.250140E+09 | 96262688.00 | 95579621.07 | 0.225222E+09 | 0.110366E+09 |
Maximum of Months | 0.462052E+09 | 0.264422E+09 | 0.285547E+09 | 0.595783E+09 | 0.368895E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.181545E+09 | 0.272103E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.286770E+09 | 0.215789E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.354578E+09 | 0.199445E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.383100E+09 | 0.157255E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.374896E+09 | 0.129194E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.338698E+09 | 90692201.36 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.418809E+09 | 80066185.81 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.461916E+09 | 73879771.94 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.463948E+09 | 0.111619E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.394321E+09 | 0.165013E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.193559E+09 | 0.206292E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.212366E+09 | 0.270304E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.406451E+10 | 0.197165E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.181545E+09 | 73879771.94 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.463948E+09 | 0.272103E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 60783898.81 | 0.549078E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.158892E+09 | 0.429853E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.303337E+09 | 0.379106E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.541939E+09 | 0.286165E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.797623E+09 | 0.233157E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.764146E+09 | 0.163625E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.106826E+10 | 0.144739E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.898860E+09 | 0.135497E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.653010E+09 | 0.207801E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.303921E+09 | 0.317477E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 88403695.80 | 0.407456E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 72543509.32 | 0.541665E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.571172E+10 | 0.379562E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 60783898.81 | 0.135497E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.106826E+10 | 0.549078E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1680788.94 | 0.303198E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 13049534.57 | 0.237279E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 46872504.73 | 0.206112E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 96349228.01 | 0.153948E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.155094E+09 | 0.125095E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.178141E+09 | 88361624.55 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.195880E+09 | 81633650.75 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.168558E+09 | 74663863.11 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 93715908.24 | 0.118337E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 41916476.38 | 0.171667E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8618720.04 | 0.221752E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 943642.28 | 0.294424E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.100082E+10 | 0.207647E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 943642.28 | 74663863.11 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.195880E+09 | 0.303198E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 64708681.11 | 0.544438E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.167022E+09 | 0.423405E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.314360E+09 | 0.373504E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.549655E+09 | 0.284909E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.792182E+09 | 0.239471E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.754779E+09 | 0.172998E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.105304E+10 | 0.159830E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.894935E+09 | 0.145620E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.652080E+09 | 0.215783E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.314102E+09 | 0.312572E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 93464129.26 | 0.402614E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 77710308.23 | 0.535878E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.572803E+10 | 0.381102E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 64708681.11 | 0.145620E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.105304E+10 | 0.544438E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.254980E+09 | 0.415676E+09 |
February | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.408164E+09 | 0.329775E+09 |
March | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.509078E+09 | 0.303461E+09 |
April | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.555394E+09 | 0.234808E+09 |
May | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.550035E+09 | 0.188975E+09 |
June | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.498764E+09 | 0.131476E+09 |
July | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.619637E+09 | 0.113472E+09 |
August | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.679951E+09 | 0.105887E+09 |
September | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.677721E+09 | 0.164131E+09 |
October | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.568042E+09 | 0.251641E+09 |
November | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.274519E+09 | 0.316980E+09 |
December | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.301239E+09 | 0.413246E+09 |
Annual Sum or Average | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.589752E+10 | 0.296953E+10 |
Minimum of Months | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.254980E+09 | 0.105887E+09 |
Maximum of Months | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.679951E+09 | 0.415676E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 1405299.89 | 0.268010E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 45464454.24 | 0.209688E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.224815E+09 | 0.181730E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.570288E+09 | 0.133583E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.101389E+10 | 0.105211E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.117373E+10 | 0.745684E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.134581E+10 | 0.665647E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.111697E+10 | 0.649966E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.598459E+09 | 0.992189E+09 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.200831E+09 | 0.155768E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 24436759.33 | 0.203241E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 370517.32 | 0.261902E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.631646E+10 | 0.182448E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 370517.32 | 0.649966E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.134581E+10 | 0.268010E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 712484.73 | 0.276733E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 39766386.67 | 0.216719E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.203696E+09 | 0.187215E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.542135E+09 | 0.137244E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.984058E+09 | 0.107808E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.114437E+10 | 0.765060E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.132002E+10 | 0.683842E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.109203E+10 | 0.669893E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.576681E+09 | 0.102109E+10 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.182229E+09 | 0.160930E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 20362356.07 | 0.210654E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 197938.66 | 0.270506E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.610625E+10 | 0.188180E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 197938.66 | 0.669893E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.132002E+10 | 0.276733E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 2511947.30 | 0.320301E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 17146480.92 | 0.252165E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 58833987.01 | 0.220693E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 0.123485E+09 | 0.167412E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.203438E+09 | 0.136245E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.231936E+09 | 0.100661E+09 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.261516E+09 | 89117975.62 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.225172E+09 | 85247886.30 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 0.135376E+09 | 0.118282E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 56534885.05 | 0.184885E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 13625520.41 | 0.235679E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 1948037.45 | 0.310891E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.133152E+10 | 0.222158E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 1948037.45 | 85247886.30 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.261516E+09 | 0.320301E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271947E+09 | 68150481.81 | 0.203796E+09 | 0.103082E+09 | 0.114885E+10 |
February | 0.452484E+09 | 0.160271E+09 | 0.292213E+09 | 0.320292E+09 | 0.890681E+09 |
March | 0.750798E+09 | 0.272253E+09 | 0.478545E+09 | 0.702826E+09 | 0.786622E+09 |
April | 0.112219E+10 | 0.465673E+09 | 0.656516E+09 | 0.128302E+10 | 0.605439E+09 |
May | 0.123469E+10 | 0.429897E+09 | 0.804794E+09 | 0.151613E+10 | 0.511724E+09 |
June | 0.143010E+10 | 0.622438E+09 | 0.807660E+09 | 0.187756E+10 | 0.379470E+09 |
July | 0.137818E+10 | 0.619625E+09 | 0.758553E+09 | 0.192510E+10 | 0.330478E+09 |
August | 0.135288E+10 | 0.676736E+09 | 0.676140E+09 | 0.194843E+10 | 0.318239E+09 |
September | 0.969561E+09 | 0.447953E+09 | 0.521608E+09 | 0.127615E+10 | 0.432336E+09 |
October | 0.655116E+09 | 0.279920E+09 | 0.375195E+09 | 0.697037E+09 | 0.670582E+09 |
November | 0.310255E+09 | 87857553.18 | 0.222397E+09 | 0.199072E+09 | 0.856355E+09 |
December | 0.262259E+09 | 84294097.83 | 0.177965E+09 | 0.135334E+09 | 0.112408E+10 |
Annual Sum or Average | 0.101905E+11 | 0.421507E+10 | 0.597538E+10 | 0.119840E+11 | 0.805485E+10 |
Minimum of Months | 0.262259E+09 | 68150481.81 | 0.177965E+09 | 0.103082E+09 | 0.318239E+09 |
Maximum of Months | 0.143010E+10 | 0.676736E+09 | 0.807660E+09 | 0.194843E+10 | 0.114885E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.188375E+09 | 0.289657E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.301516E+09 | 0.229797E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.378966E+09 | 0.213269E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.418150E+09 | 0.170954E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.421525E+09 | 0.142396E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.388037E+09 | 0.107202E+09 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.476883E+09 | 94050869.02 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.518440E+09 | 88889306.49 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.511108E+09 | 0.117520E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.422720E+09 | 0.179454E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.205687E+09 | 0.221360E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.222353E+09 | 0.288047E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.445376E+10 | 0.214260E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.188375E+09 | 88889306.49 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.518440E+09 | 0.289657E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 797487.78 | 0.431238E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 11712651.43 | 0.334102E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 50777956.41 | 0.284971E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.117745E+09 | 0.210123E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.200132E+09 | 0.169661E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.227589E+09 | 0.121700E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.253522E+09 | 0.110807E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.210172E+09 | 0.107933E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.116496E+09 | 0.161539E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 44914495.97 | 0.241046E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 7275240.66 | 0.317147E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 271847.03 | 0.419581E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.124141E+10 | 0.290985E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 271847.03 | 0.107933E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.253522E+09 | 0.431238E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51567304.17 | 0.00 | 51567304.17 | 713515.34 | 0.385809E+09 |
February | 72474989.01 | 0.00 | 72474989.01 | 10479353.61 | 0.298921E+09 |
March | 0.118232E+09 | 385.50 | 0.118232E+09 | 45431230.00 | 0.254965E+09 |
April | 0.162475E+09 | 999613.19 | 0.161475E+09 | 0.105347E+09 | 0.187998E+09 |
May | 0.215396E+09 | 6467447.92 | 0.208929E+09 | 0.179059E+09 | 0.151797E+09 |
June | 0.219373E+09 | 14675896.84 | 0.204698E+09 | 0.203625E+09 | 0.108886E+09 |
July | 0.215762E+09 | 17369382.46 | 0.198392E+09 | 0.226827E+09 | 99139300.44 |
August | 0.174897E+09 | 5252593.31 | 0.169644E+09 | 0.188042E+09 | 96568124.71 |
September | 0.131002E+09 | 98133.84 | 0.130904E+09 | 0.104229E+09 | 0.144530E+09 |
October | 92684987.96 | 0.00 | 92684987.96 | 40185169.72 | 0.215665E+09 |
November | 56499036.19 | 0.00 | 56499036.19 | 6509185.39 | 0.283744E+09 |
December | 43818913.81 | 0.00 | 43818913.81 | 243222.57 | 0.375357E+09 |
Annual Sum or Average | 0.155418E+10 | 44863453.06 | 0.150932E+10 | 0.111069E+10 | 0.260338E+10 |
Minimum of Months | 43818913.81 | 0.00 | 43818913.81 | 243222.57 | 96568124.71 |
Maximum of Months | 0.219373E+09 | 17369382.46 | 0.208929E+09 | 0.226827E+09 | 0.385809E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.753484E+09 | 0.448231E+09 | 0.305253E+09 | 0.651802E+09 | 0.111482E+10 |
February | 0.104729E+10 | 0.649789E+09 | 0.397505E+09 | 0.105285E+10 | 0.870000E+09 |
March | 0.123000E+10 | 0.650301E+09 | 0.579696E+09 | 0.131515E+10 | 0.800121E+09 |
April | 0.125777E+10 | 0.539802E+09 | 0.717972E+09 | 0.143074E+10 | 0.629976E+09 |
May | 0.121093E+10 | 0.369176E+09 | 0.841756E+09 | 0.140146E+10 | 0.531931E+09 |
June | 0.106028E+10 | 0.283770E+09 | 0.776505E+09 | 0.125577E+10 | 0.393218E+09 |
July | 0.119034E+10 | 0.432209E+09 | 0.758129E+09 | 0.155413E+10 | 0.358651E+09 |
August | 0.126900E+10 | 0.583096E+09 | 0.685904E+09 | 0.171032E+10 | 0.341548E+09 |
September | 0.136207E+10 | 0.744959E+09 | 0.617112E+09 | 0.172639E+10 | 0.470779E+09 |
October | 0.127318E+10 | 0.779484E+09 | 0.493697E+09 | 0.146523E+10 | 0.672034E+09 |
November | 0.737380E+09 | 0.422081E+09 | 0.315299E+09 | 0.704407E+09 | 0.849809E+09 |
December | 0.797464E+09 | 0.515707E+09 | 0.281757E+09 | 0.775811E+09 | 0.110775E+10 |
Annual Sum or Average | 0.131892E+11 | 0.641861E+10 | 0.677058E+10 | 0.150441E+11 | 0.814064E+10 |
Minimum of Months | 0.737380E+09 | 0.283770E+09 | 0.281757E+09 | 0.651802E+09 | 0.341548E+09 |
Maximum of Months | 0.136207E+10 | 0.779484E+09 | 0.841756E+09 | 0.172639E+10 | 0.111482E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 338.10 | 509.65 | 381.12 | 226.72 | 154.40 | 0.00 | 0.00 |
February | 597.01 | 447.39 | 586.49 | 363.88 | 222.60 | 0.00 | 0.00 |
March | 670.85 | 372.14 | 622.14 | 328.93 | 293.21 | 0.00 | 0.00 |
April | 758.55 | 299.29 | 657.40 | 282.14 | 375.26 | 0.00 | 0.00 |
May | 725.80 | 238.11 | 612.50 | 186.73 | 425.76 | 0.00 | 0.00 |
June | 679.49 | 176.19 | 554.17 | 148.32 | 405.85 | 0.00 | 0.00 |
July | 803.59 | 156.13 | 602.08 | 218.62 | 383.46 | 0.00 | 0.00 |
August | 876.64 | 151.03 | 641.87 | 294.94 | 346.93 | 0.00 | 0.00 |
September | 904.46 | 223.86 | 711.91 | 389.37 | 322.54 | 0.00 | 0.00 |
October | 744.82 | 314.45 | 643.99 | 394.27 | 249.72 | 0.00 | 0.00 |
November | 373.76 | 403.43 | 385.41 | 220.61 | 164.80 | 0.00 | 0.00 |
December | 395.99 | 511.58 | 403.36 | 260.85 | 142.51 | 0.00 | 0.00 |
Annual Sum or Average | 655.98 | 316.32 | 566.59 | 275.74 | 290.86 | 0.00 | 0.00 |
Minimum of Months | 338.10 | 151.03 | 381.12 | 148.32 | 142.51 | 0.00 | 0.00 |
Maximum of Months | 904.46 | 511.58 | 711.91 | 394.27 | 425.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 937.61 | 1477.34 | 1073.21 | 638.43 | 434.78 | 0.00 | 0.00 |
February | 1658.84 | 1309.41 | 1651.51 | 1024.67 | 626.84 | 0.00 | 0.00 |
March | 1864.47 | 1110.63 | 1751.91 | 926.24 | 825.67 | 0.00 | 0.00 |
April | 2105.27 | 905.69 | 1851.19 | 794.48 | 1056.71 | 0.00 | 0.00 |
May | 2010.45 | 731.25 | 1724.75 | 525.83 | 1198.93 | 0.00 | 0.00 |
June | 1873.56 | 558.22 | 1560.51 | 417.65 | 1142.85 | 0.00 | 0.00 |
July | 2227.95 | 495.35 | 1695.42 | 615.61 | 1079.81 | 0.00 | 0.00 |
August | 2436.38 | 482.81 | 1807.46 | 830.52 | 976.94 | 0.00 | 0.00 |
September | 2517.76 | 694.90 | 2004.70 | 1096.43 | 908.26 | 0.00 | 0.00 |
October | 2070.66 | 956.98 | 1813.42 | 1110.24 | 703.18 | 0.00 | 0.00 |
November | 1035.32 | 1189.67 | 1085.28 | 621.22 | 464.06 | 0.00 | 0.00 |
December | 1100.55 | 1487.09 | 1135.85 | 734.54 | 401.31 | 0.00 | 0.00 |
Annual Sum or Average | 1820.53 | 948.23 | 1595.49 | 776.46 | 819.03 | 0.00 | 0.00 |
Minimum of Months | 937.61 | 482.81 | 1073.21 | 417.65 | 401.31 | 0.00 | 0.00 |
Maximum of Months | 2517.76 | 1487.09 | 2004.70 | 1110.24 | 1198.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1227.38 | 2046.28 | 1394.16 | 829.35 | 564.80 | 0.00 | 0.00 |
February | 2180.90 | 1804.00 | 2145.41 | 1331.11 | 814.30 | 0.00 | 0.00 |
March | 2455.41 | 1536.38 | 2275.84 | 1203.24 | 1072.60 | 0.00 | 0.00 |
April | 2773.02 | 1252.38 | 2404.80 | 1032.08 | 1372.72 | 0.00 | 0.00 |
May | 2643.16 | 1020.93 | 2240.55 | 683.08 | 1557.47 | 0.00 | 0.00 |
June | 2457.00 | 783.13 | 2027.19 | 542.56 | 1484.63 | 0.00 | 0.00 |
July | 2933.32 | 690.00 | 2202.45 | 799.71 | 1402.74 | 0.00 | 0.00 |
August | 3209.31 | 666.88 | 2348.00 | 1078.89 | 1269.10 | 0.00 | 0.00 |
September | 3314.75 | 960.64 | 2604.21 | 1424.33 | 1179.88 | 0.00 | 0.00 |
October | 2723.48 | 1328.85 | 2355.74 | 1442.27 | 913.47 | 0.00 | 0.00 |
November | 1352.25 | 1662.73 | 1409.84 | 807.00 | 602.84 | 0.00 | 0.00 |
December | 1442.74 | 2061.22 | 1475.53 | 954.20 | 521.33 | 0.00 | 0.00 |
Annual Sum or Average | 2393.57 | 1315.47 | 2072.64 | 1008.67 | 1063.97 | 0.00 | 0.00 |
Minimum of Months | 1227.38 | 666.88 | 1394.16 | 542.56 | 521.33 | 0.00 | 0.00 |
Maximum of Months | 3314.75 | 2061.22 | 2604.21 | 1442.27 | 1557.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.63 | 300.33 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 177.09 | 261.15 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 244.41 | 214.62 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 358.96 | 169.74 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 441.47 | 134.59 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 429.64 | 97.90 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 559.84 | 83.84 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 511.59 | 78.88 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 432.63 | 123.71 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 259.73 | 179.71 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 104.25 | 234.88 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 98.48 | 298.51 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 309.14 | 181.11 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 81.63 | 78.88 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 559.84 | 300.33 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.23 | 315.72 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 70.87 | 271.99 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 133.50 | 216.30 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 251.01 | 168.56 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 357.92 | 134.27 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 364.07 | 98.18 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 471.37 | 87.10 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 399.92 | 81.37 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 289.53 | 127.85 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 131.67 | 181.73 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 37.05 | 241.97 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 26.28 | 310.97 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 213.79 | 185.93 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 21.23 | 81.37 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 471.37 | 315.72 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 53.22 | 81.85 | 60.27 | 35.85 | 24.42 | 0.00 | 0.00 |
February | 89.31 | 85.29 | 92.75 | 57.55 | 35.20 | 0.00 | 0.00 |
March | 96.83 | 84.01 | 98.39 | 52.02 | 46.37 | 0.00 | 0.00 |
April | 107.37 | 71.04 | 103.96 | 44.62 | 59.34 | 0.00 | 0.00 |
May | 101.26 | 58.82 | 96.86 | 29.53 | 67.33 | 0.00 | 0.00 |
June | 92.53 | 46.52 | 87.64 | 23.46 | 64.18 | 0.00 | 0.00 |
July | 114.00 | 41.64 | 95.22 | 34.57 | 60.64 | 0.00 | 0.00 |
August | 126.48 | 40.50 | 101.51 | 46.64 | 54.87 | 0.00 | 0.00 |
September | 132.84 | 55.69 | 112.58 | 61.58 | 51.01 | 0.00 | 0.00 |
October | 107.94 | 75.50 | 101.84 | 62.35 | 39.49 | 0.00 | 0.00 |
November | 53.34 | 84.84 | 60.95 | 34.89 | 26.06 | 0.00 | 0.00 |
December | 60.52 | 89.38 | 63.79 | 41.25 | 22.54 | 0.00 | 0.00 |
Annual Sum or Average | 94.66 | 67.82 | 89.60 | 43.61 | 46.00 | 0.00 | 0.00 |
Minimum of Months | 53.22 | 40.50 | 60.27 | 23.46 | 22.54 | 0.00 | 0.00 |
Maximum of Months | 132.84 | 89.38 | 112.58 | 62.35 | 67.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.27 | 97.05 | 13.60 | 0.00 | 13.60 | 0.00 | 0.00 |
February | 3.62 | 82.96 | 21.15 | 0.00 | 21.15 | 0.00 | 0.00 |
March | 13.46 | 64.24 | 31.17 | 0.00 | 31.17 | 0.00 | 0.00 |
April | 31.00 | 48.11 | 44.26 | 0.27 | 43.99 | 0.00 | 0.00 |
May | 50.37 | 36.50 | 56.79 | 1.71 | 55.08 | 0.00 | 0.00 |
June | 59.50 | 26.18 | 59.76 | 4.00 | 55.77 | 0.00 | 0.00 |
July | 64.64 | 22.16 | 56.88 | 4.58 | 52.30 | 0.00 | 0.00 |
August | 54.54 | 20.79 | 46.11 | 1.38 | 44.72 | 0.00 | 0.00 |
September | 31.64 | 34.92 | 35.69 | 0.03 | 35.66 | 0.00 | 0.00 |
October | 12.28 | 53.38 | 24.44 | 0.00 | 24.44 | 0.00 | 0.00 |
November | 2.12 | 73.72 | 15.39 | 0.00 | 15.39 | 0.00 | 0.00 |
December | 0.11 | 94.53 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 27.11 | 54.41 | 34.80 | 1.00 | 33.80 | 0.00 | 0.00 |
Minimum of Months | 0.11 | 20.79 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 64.64 | 97.05 | 59.76 | 4.58 | 55.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 76.32 | 298.83 | 126.12 | 57.55 | 68.57 | 0.00 | 0.00 |
February | 171.07 | 258.93 | 209.48 | 105.07 | 104.41 | 0.00 | 0.00 |
March | 246.10 | 210.28 | 263.18 | 115.86 | 147.31 | 0.00 | 0.00 |
April | 366.69 | 163.89 | 346.47 | 145.62 | 200.85 | 0.00 | 0.00 |
May | 391.71 | 130.72 | 351.61 | 117.18 | 234.43 | 0.00 | 0.00 |
June | 456.18 | 94.15 | 385.46 | 149.40 | 236.05 | 0.00 | 0.00 |
July | 477.49 | 77.75 | 376.34 | 158.90 | 217.43 | 0.00 | 0.00 |
August | 496.31 | 73.66 | 379.48 | 184.65 | 194.83 | 0.00 | 0.00 |
September | 392.28 | 118.88 | 327.80 | 163.40 | 164.40 | 0.00 | 0.00 |
October | 258.61 | 177.09 | 249.63 | 130.21 | 119.42 | 0.00 | 0.00 |
November | 102.52 | 233.09 | 136.05 | 60.57 | 75.49 | 0.00 | 0.00 |
December | 94.02 | 295.60 | 128.71 | 67.31 | 61.40 | 0.00 | 0.00 |
Annual Sum or Average | 294.73 | 177.35 | 273.61 | 121.35 | 152.25 | 0.00 | 0.00 |
Minimum of Months | 76.32 | 73.66 | 126.12 | 57.55 | 61.40 | 0.00 | 0.00 |
Maximum of Months | 496.31 | 298.83 | 385.46 | 184.65 | 236.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.84 | 312.27 | 67.76 | 12.72 | 55.04 | 0.00 | 0.00 |
February | 60.64 | 265.21 | 119.97 | 33.13 | 86.84 | 0.00 | 0.00 |
March | 132.56 | 209.05 | 179.13 | 50.83 | 128.30 | 0.00 | 0.00 |
April | 258.31 | 161.99 | 271.81 | 90.18 | 181.63 | 0.00 | 0.00 |
May | 311.80 | 129.91 | 301.48 | 82.39 | 219.09 | 0.00 | 0.00 |
June | 394.49 | 95.48 | 350.58 | 125.07 | 225.51 | 0.00 | 0.00 |
July | 393.83 | 80.00 | 328.39 | 121.40 | 206.99 | 0.00 | 0.00 |
August | 385.80 | 76.81 | 310.20 | 128.07 | 182.13 | 0.00 | 0.00 |
September | 250.69 | 120.42 | 231.65 | 86.45 | 145.20 | 0.00 | 0.00 |
October | 128.44 | 176.32 | 152.84 | 52.26 | 100.59 | 0.00 | 0.00 |
November | 33.30 | 237.95 | 79.09 | 16.95 | 62.14 | 0.00 | 0.00 |
December | 18.76 | 304.97 | 63.40 | 15.74 | 47.66 | 0.00 | 0.00 |
Annual Sum or Average | 199.28 | 180.47 | 205.07 | 68.09 | 136.98 | 0.00 | 0.00 |
Minimum of Months | 13.84 | 76.81 | 63.40 | 12.72 | 47.66 | 0.00 | 0.00 |
Maximum of Months | 394.49 | 312.27 | 350.58 | 128.07 | 225.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 99.23 | 387.35 | 160.04 | 77.69 | 82.36 | 0.00 | 0.00 |
February | 200.31 | 333.40 | 246.79 | 124.69 | 122.10 | 0.00 | 0.00 |
March | 258.75 | 272.93 | 280.70 | 112.71 | 168.00 | 0.00 | 0.00 |
April | 329.60 | 215.49 | 321.15 | 97.26 | 223.88 | 0.00 | 0.00 |
May | 356.51 | 171.59 | 332.89 | 67.68 | 265.22 | 0.00 | 0.00 |
June | 357.66 | 125.89 | 319.36 | 59.48 | 259.87 | 0.00 | 0.00 |
July | 411.58 | 110.29 | 329.53 | 84.83 | 244.70 | 0.00 | 0.00 |
August | 415.53 | 107.97 | 319.83 | 104.06 | 215.77 | 0.00 | 0.00 |
September | 379.87 | 164.73 | 321.25 | 133.47 | 187.78 | 0.00 | 0.00 |
October | 280.63 | 229.64 | 273.60 | 135.10 | 138.50 | 0.00 | 0.00 |
November | 124.87 | 301.19 | 165.40 | 75.59 | 89.81 | 0.00 | 0.00 |
December | 121.93 | 382.55 | 163.24 | 89.38 | 73.86 | 0.00 | 0.00 |
Annual Sum or Average | 278.46 | 233.11 | 269.53 | 96.66 | 172.88 | 0.00 | 0.00 |
Minimum of Months | 99.23 | 107.97 | 160.04 | 59.48 | 73.86 | 0.00 | 0.00 |
Maximum of Months | 415.53 | 387.35 | 332.89 | 135.10 | 265.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 82.09 | 298.21 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 176.75 | 259.41 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 242.89 | 213.26 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 355.22 | 169.41 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 436.59 | 134.10 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 424.69 | 97.32 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 554.50 | 83.22 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 507.64 | 77.76 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 429.95 | 122.26 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 258.34 | 177.79 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 104.46 | 232.46 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 98.85 | 295.63 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 306.81 | 179.69 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 82.09 | 77.76 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 554.50 | 298.21 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.60 | 313.28 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 71.22 | 269.88 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 132.98 | 214.52 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 248.15 | 168.23 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 352.56 | 135.00 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 358.23 | 99.14 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 464.88 | 88.74 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 396.17 | 81.36 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 286.65 | 127.82 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 131.43 | 179.30 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 37.55 | 239.05 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 26.78 | 307.42 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 211.59 | 184.91 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 21.60 | 81.36 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 464.88 | 313.28 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.20 | 155.20 | 110.51 | 65.74 | 44.77 | 0.00 | 0.00 |
February | 168.72 | 136.32 | 170.06 | 105.52 | 64.55 | 0.00 | 0.00 |
March | 190.07 | 113.30 | 180.40 | 95.38 | 85.02 | 0.00 | 0.00 |
April | 214.27 | 90.59 | 190.63 | 81.81 | 108.82 | 0.00 | 0.00 |
May | 205.36 | 70.56 | 177.61 | 54.15 | 123.46 | 0.00 | 0.00 |
June | 192.42 | 50.72 | 160.69 | 43.01 | 117.69 | 0.00 | 0.00 |
July | 231.35 | 42.37 | 174.59 | 63.39 | 111.20 | 0.00 | 0.00 |
August | 253.86 | 39.53 | 186.12 | 85.52 | 100.60 | 0.00 | 0.00 |
September | 261.47 | 63.32 | 206.43 | 112.91 | 93.53 | 0.00 | 0.00 |
October | 212.08 | 93.95 | 186.74 | 114.33 | 72.41 | 0.00 | 0.00 |
November | 105.91 | 122.29 | 111.76 | 63.97 | 47.79 | 0.00 | 0.00 |
December | 112.47 | 154.29 | 116.96 | 75.64 | 41.33 | 0.00 | 0.00 |
Annual Sum or Average | 187.01 | 94.16 | 164.30 | 79.96 | 84.34 | 0.00 | 0.00 |
Minimum of Months | 95.20 | 39.53 | 110.51 | 43.01 | 41.33 | 0.00 | 0.00 |
Maximum of Months | 261.47 | 155.20 | 206.43 | 114.33 | 123.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.52 | 1000.64 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 18.79 | 866.77 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 83.94 | 678.50 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 220.02 | 515.37 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 378.54 | 392.81 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 452.83 | 287.69 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 502.47 | 248.52 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 417.03 | 242.67 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 230.89 | 382.79 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 74.98 | 581.57 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 9.43 | 784.11 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.14 | 977.83 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 200.29 | 578.54 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.14 | 242.67 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 502.47 | 1000.64 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.27 | 1033.20 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 16.44 | 895.83 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 76.05 | 698.98 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 209.16 | 529.49 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 367.41 | 402.51 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 441.50 | 295.16 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 492.84 | 255.32 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 407.72 | 250.11 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 222.48 | 393.94 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 68.04 | 600.84 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 7.86 | 812.71 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.07 | 1009.95 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 193.63 | 596.71 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 250.11 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 492.84 | 1033.20 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.72 | 638.63 | 193.88 | 70.27 | 123.61 | 0.00 | 0.00 |
February | 249.58 | 552.86 | 329.44 | 138.20 | 191.24 | 0.00 | 0.00 |
March | 420.84 | 450.69 | 442.28 | 166.68 | 275.60 | 0.00 | 0.00 |
April | 699.34 | 359.51 | 618.24 | 235.78 | 382.46 | 0.00 | 0.00 |
May | 797.09 | 292.78 | 653.06 | 199.56 | 453.50 | 0.00 | 0.00 |
June | 961.41 | 224.45 | 736.00 | 274.46 | 461.54 | 0.00 | 0.00 |
July | 992.44 | 189.78 | 704.69 | 280.29 | 424.40 | 0.00 | 0.00 |
August | 1003.38 | 182.12 | 689.64 | 312.71 | 376.94 | 0.00 | 0.00 |
September | 739.50 | 255.51 | 559.42 | 249.84 | 309.58 | 0.00 | 0.00 |
October | 435.93 | 383.15 | 402.46 | 182.46 | 220.00 | 0.00 | 0.00 |
November | 153.96 | 499.26 | 215.14 | 77.51 | 137.62 | 0.00 | 0.00 |
December | 120.14 | 629.17 | 192.11 | 83.05 | 109.06 | 0.00 | 0.00 |
Annual Sum or Average | 557.05 | 387.39 | 478.66 | 189.43 | 289.22 | 0.00 | 0.00 |
Minimum of Months | 91.72 | 182.12 | 192.11 | 70.27 | 109.06 | 0.00 | 0.00 |
Maximum of Months | 1003.38 | 638.63 | 736.00 | 312.71 | 461.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.16 | 696.51 | 322.09 | 167.35 | 154.74 | 0.00 | 0.00 |
February | 423.67 | 600.58 | 496.35 | 268.60 | 227.75 | 0.00 | 0.00 |
March | 522.29 | 495.67 | 552.71 | 242.80 | 309.91 | 0.00 | 0.00 |
April | 637.28 | 395.87 | 618.00 | 209.07 | 408.92 | 0.00 | 0.00 |
May | 661.61 | 315.41 | 622.41 | 142.95 | 479.47 | 0.00 | 0.00 |
June | 645.42 | 235.25 | 588.29 | 121.47 | 466.82 | 0.00 | 0.00 |
July | 753.98 | 206.69 | 615.01 | 175.10 | 439.91 | 0.00 | 0.00 |
August | 785.15 | 201.79 | 612.07 | 221.86 | 390.22 | 0.00 | 0.00 |
September | 750.38 | 298.89 | 632.52 | 287.49 | 345.03 | 0.00 | 0.00 |
October | 573.22 | 415.82 | 548.63 | 291.03 | 257.61 | 0.00 | 0.00 |
November | 263.36 | 545.97 | 330.64 | 162.84 | 167.80 | 0.00 | 0.00 |
December | 267.03 | 687.57 | 332.38 | 192.54 | 139.84 | 0.00 | 0.00 |
Annual Sum or Average | 542.50 | 423.83 | 522.59 | 206.55 | 316.05 | 0.00 | 0.00 |
Minimum of Months | 219.16 | 201.79 | 322.09 | 121.47 | 139.84 | 0.00 | 0.00 |
Maximum of Months | 785.15 | 696.51 | 632.52 | 291.03 | 479.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.905574E+09 | 0.136504E+10 | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.00 | 0.00 |
February | 0.144429E+10 | 0.108231E+10 | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.00 | 0.00 |
March | 0.179681E+10 | 0.996730E+09 | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.00 | 0.00 |
April | 0.196615E+10 | 0.775757E+09 | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.00 | 0.00 |
May | 0.194398E+10 | 0.637749E+09 | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.00 | 0.00 |
June | 0.176125E+10 | 0.456697E+09 | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.00 | 0.00 |
July | 0.215233E+10 | 0.418185E+09 | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.00 | 0.00 |
August | 0.234799E+10 | 0.404525E+09 | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.00 | 0.00 |
September | 0.234435E+10 | 0.580234E+09 | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.00 | 0.00 |
October | 0.199492E+10 | 0.842213E+09 | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.00 | 0.00 |
November | 0.968782E+09 | 0.104569E+10 | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.00 | 0.00 |
December | 0.106063E+10 | 0.137022E+10 | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206871E+11 | 0.997536E+10 | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.00 | 0.00 |
Minimum of Months | 0.905574E+09 | 0.404525E+09 | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234799E+10 | 0.137022E+10 | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251131E+10 | 0.395690E+10 | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.00 | 0.00 |
February | 0.401307E+10 | 0.316771E+10 | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.00 | 0.00 |
March | 0.499379E+10 | 0.297471E+10 | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.00 | 0.00 |
April | 0.545685E+10 | 0.234755E+10 | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.00 | 0.00 |
May | 0.538478E+10 | 0.195859E+10 | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.00 | 0.00 |
June | 0.485627E+10 | 0.144690E+10 | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.00 | 0.00 |
July | 0.596733E+10 | 0.132676E+10 | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.00 | 0.00 |
August | 0.652559E+10 | 0.129317E+10 | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.00 | 0.00 |
September | 0.652603E+10 | 0.180117E+10 | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.00 | 0.00 |
October | 0.554606E+10 | 0.256317E+10 | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.00 | 0.00 |
November | 0.268356E+10 | 0.308361E+10 | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.00 | 0.00 |
December | 0.294771E+10 | 0.398303E+10 | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574123E+11 | 0.299033E+11 | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251131E+10 | 0.129317E+10 | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652603E+10 | 0.398303E+10 | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328740E+10 | 0.548075E+10 | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.00 | 0.00 |
February | 0.527604E+10 | 0.436423E+10 | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.00 | 0.00 |
March | 0.657657E+10 | 0.411503E+10 | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.00 | 0.00 |
April | 0.718768E+10 | 0.324618E+10 | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.00 | 0.00 |
May | 0.707944E+10 | 0.273445E+10 | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.00 | 0.00 |
June | 0.636854E+10 | 0.202988E+10 | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.00 | 0.00 |
July | 0.785662E+10 | 0.184810E+10 | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.00 | 0.00 |
August | 0.859582E+10 | 0.178618E+10 | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.00 | 0.00 |
September | 0.859184E+10 | 0.248998E+10 | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.00 | 0.00 |
October | 0.729457E+10 | 0.355919E+10 | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.00 | 0.00 |
November | 0.350503E+10 | 0.430981E+10 | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.00 | 0.00 |
December | 0.386422E+10 | 0.552077E+10 | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.754838E+11 | 0.414845E+11 | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328740E+10 | 0.178618E+10 | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859582E+10 | 0.552077E+10 | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218648E+09 | 0.804403E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.428417E+09 | 0.631786E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.654621E+09 | 0.574826E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.930411E+09 | 0.439967E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.118244E+10 | 0.360477E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.111362E+10 | 0.253759E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.149949E+10 | 0.224553E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.137025E+10 | 0.211272E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.112139E+10 | 0.320653E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.695665E+09 | 0.481344E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.270228E+09 | 0.608814E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.263780E+09 | 0.799542E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.974895E+10 | 0.571140E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218648E+09 | 0.211272E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149949E+10 | 0.804403E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 56856492.14 | 0.845635E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.171443E+09 | 0.657987E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.357571E+09 | 0.579341E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.650610E+09 | 0.436903E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.958662E+09 | 0.359627E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.943674E+09 | 0.254484E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.126252E+10 | 0.233285E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.107114E+10 | 0.217933E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.750451E+09 | 0.331385E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.352655E+09 | 0.486741E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 96023537.32 | 0.627190E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 70379893.18 | 0.832893E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.674199E+10 | 0.586340E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 56856492.14 | 0.217933E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126252E+10 | 0.845635E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142538E+09 | 0.219216E+09 | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.00 | 0.00 |
February | 0.216052E+09 | 0.206327E+09 | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.00 | 0.00 |
March | 0.259359E+09 | 0.225000E+09 | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.00 | 0.00 |
April | 0.278315E+09 | 0.184127E+09 | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.00 | 0.00 |
May | 0.271210E+09 | 0.157549E+09 | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.00 | 0.00 |
June | 0.239828E+09 | 0.120579E+09 | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.00 | 0.00 |
July | 0.305327E+09 | 0.111523E+09 | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.00 | 0.00 |
August | 0.338756E+09 | 0.108468E+09 | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.00 | 0.00 |
September | 0.344325E+09 | 0.144355E+09 | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.00 | 0.00 |
October | 0.289117E+09 | 0.202222E+09 | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.00 | 0.00 |
November | 0.138263E+09 | 0.219913E+09 | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.00 | 0.00 |
December | 0.162097E+09 | 0.239398E+09 | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.00 | 0.00 |
Annual Sum or Average | 0.298519E+10 | 0.213868E+10 | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.00 | 0.00 |
Minimum of Months | 0.138263E+09 | 0.108468E+09 | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.00 | 0.00 |
Maximum of Months | 0.344325E+09 | 0.239398E+09 | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 726333.45 | 0.259945E+09 | 36413225.08 | 0.00 | 36413225.08 | 0.00 | 0.00 |
February | 8757240.63 | 0.200705E+09 | 51176770.43 | 0.00 | 51176770.43 | 0.00 | 0.00 |
March | 36047308.75 | 0.172068E+09 | 83487367.90 | 272.21 | 83487095.69 | 0.00 | 0.00 |
April | 80344405.17 | 0.124705E+09 | 0.114728E+09 | 705856.95 | 0.114022E+09 | 0.00 | 0.00 |
May | 0.134920E+09 | 97761102.10 | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.00 | 0.00 |
June | 0.154221E+09 | 67864347.01 | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.00 | 0.00 |
July | 0.173122E+09 | 59345057.49 | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.00 | 0.00 |
August | 0.146081E+09 | 55692977.46 | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.00 | 0.00 |
September | 82007286.71 | 90516829.20 | 92504439.09 | 69295.25 | 92435143.84 | 0.00 | 0.00 |
October | 32888265.30 | 0.142976E+09 | 65447658.79 | 0.00 | 65447658.79 | 0.00 | 0.00 |
November | 5484789.06 | 0.191075E+09 | 39895669.45 | 0.00 | 39895669.45 | 0.00 | 0.00 |
December | 303307.28 | 0.253200E+09 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.854902E+09 | 0.171585E+10 | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.00 | 0.00 |
Minimum of Months | 303307.28 | 55692977.46 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Maximum of Months | 0.173122E+09 | 0.259945E+09 | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204415E+09 | 0.800383E+09 | 0.337811E+09 | 0.154141E+09 | 0.183670E+09 | 0.00 | 0.00 |
February | 0.413850E+09 | 0.626397E+09 | 0.506786E+09 | 0.254193E+09 | 0.252592E+09 | 0.00 | 0.00 |
March | 0.659158E+09 | 0.563222E+09 | 0.704892E+09 | 0.310326E+09 | 0.394567E+09 | 0.00 | 0.00 |
April | 0.950465E+09 | 0.424797E+09 | 0.898041E+09 | 0.377444E+09 | 0.520597E+09 | 0.00 | 0.00 |
May | 0.104915E+10 | 0.350124E+09 | 0.941749E+09 | 0.313851E+09 | 0.627898E+09 | 0.00 | 0.00 |
June | 0.118241E+10 | 0.244037E+09 | 0.999105E+09 | 0.387252E+09 | 0.611853E+09 | 0.00 | 0.00 |
July | 0.127890E+10 | 0.208238E+09 | 0.100798E+10 | 0.425606E+09 | 0.582376E+09 | 0.00 | 0.00 |
August | 0.132932E+10 | 0.197291E+09 | 0.101640E+10 | 0.494580E+09 | 0.521820E+09 | 0.00 | 0.00 |
September | 0.101678E+10 | 0.308134E+09 | 0.849659E+09 | 0.423537E+09 | 0.426122E+09 | 0.00 | 0.00 |
October | 0.692655E+09 | 0.474324E+09 | 0.668615E+09 | 0.348763E+09 | 0.319852E+09 | 0.00 | 0.00 |
November | 0.265726E+09 | 0.604168E+09 | 0.352653E+09 | 0.156990E+09 | 0.195662E+09 | 0.00 | 0.00 |
December | 0.251818E+09 | 0.791745E+09 | 0.344747E+09 | 0.180287E+09 | 0.164460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.929466E+10 | 0.559286E+10 | 0.862844E+10 | 0.382697E+10 | 0.480147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.204415E+09 | 0.197291E+09 | 0.337811E+09 | 0.154141E+09 | 0.164460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132932E+10 | 0.800383E+09 | 0.101640E+10 | 0.494580E+09 | 0.627898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37063749.11 | 0.836390E+09 | 0.181494E+09 | 34077660.85 | 0.147416E+09 | 0.00 | 0.00 |
February | 0.146707E+09 | 0.641606E+09 | 0.290220E+09 | 80141237.88 | 0.210079E+09 | 0.00 | 0.00 |
March | 0.355045E+09 | 0.559930E+09 | 0.479771E+09 | 0.136136E+09 | 0.343635E+09 | 0.00 | 0.00 |
April | 0.669529E+09 | 0.419885E+09 | 0.704526E+09 | 0.233735E+09 | 0.470791E+09 | 0.00 | 0.00 |
May | 0.835137E+09 | 0.347945E+09 | 0.807486E+09 | 0.220672E+09 | 0.586815E+09 | 0.00 | 0.00 |
June | 0.102252E+10 | 0.247485E+09 | 0.908707E+09 | 0.324193E+09 | 0.584513E+09 | 0.00 | 0.00 |
July | 0.105483E+10 | 0.214271E+09 | 0.879557E+09 | 0.325164E+09 | 0.554394E+09 | 0.00 | 0.00 |
August | 0.103334E+10 | 0.205717E+09 | 0.830840E+09 | 0.343027E+09 | 0.487813E+09 | 0.00 | 0.00 |
September | 0.649793E+09 | 0.312119E+09 | 0.600430E+09 | 0.224079E+09 | 0.376351E+09 | 0.00 | 0.00 |
October | 0.344017E+09 | 0.472253E+09 | 0.409380E+09 | 0.139970E+09 | 0.269410E+09 | 0.00 | 0.00 |
November | 86322376.17 | 0.616777E+09 | 0.205001E+09 | 43931896.31 | 0.161070E+09 | 0.00 | 0.00 |
December | 50245511.56 | 0.816821E+09 | 0.169811E+09 | 42150042.10 | 0.127661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.628455E+10 | 0.569120E+10 | 0.646722E+10 | 0.214728E+10 | 0.431995E+10 | 0.00 | 0.00 |
Minimum of Months | 37063749.11 | 0.205717E+09 | 0.169811E+09 | 34077660.85 | 0.127661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105483E+10 | 0.836390E+09 | 0.908707E+09 | 0.343027E+09 | 0.586815E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265779E+09 | 0.103749E+10 | 0.428658E+09 | 0.208073E+09 | 0.220584E+09 | 0.00 | 0.00 |
February | 0.484596E+09 | 0.806570E+09 | 0.597030E+09 | 0.301638E+09 | 0.295392E+09 | 0.00 | 0.00 |
March | 0.693029E+09 | 0.731005E+09 | 0.751838E+09 | 0.301877E+09 | 0.449962E+09 | 0.00 | 0.00 |
April | 0.854335E+09 | 0.558552E+09 | 0.832411E+09 | 0.252110E+09 | 0.580300E+09 | 0.00 | 0.00 |
May | 0.954865E+09 | 0.459600E+09 | 0.891621E+09 | 0.181268E+09 | 0.710352E+09 | 0.00 | 0.00 |
June | 0.927042E+09 | 0.326309E+09 | 0.827769E+09 | 0.154179E+09 | 0.673590E+09 | 0.00 | 0.00 |
July | 0.110237E+10 | 0.295401E+09 | 0.882620E+09 | 0.227206E+09 | 0.655414E+09 | 0.00 | 0.00 |
August | 0.111295E+10 | 0.289197E+09 | 0.856624E+09 | 0.278714E+09 | 0.577911E+09 | 0.00 | 0.00 |
September | 0.984621E+09 | 0.426969E+09 | 0.832682E+09 | 0.345967E+09 | 0.486715E+09 | 0.00 | 0.00 |
October | 0.751634E+09 | 0.615079E+09 | 0.732804E+09 | 0.361844E+09 | 0.370960E+09 | 0.00 | 0.00 |
November | 0.323673E+09 | 0.780684E+09 | 0.428726E+09 | 0.195934E+09 | 0.232792E+09 | 0.00 | 0.00 |
December | 0.326586E+09 | 0.102463E+10 | 0.437221E+09 | 0.239396E+09 | 0.197825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.878148E+10 | 0.735149E+10 | 0.850000E+10 | 0.304821E+10 | 0.545180E+10 | 0.00 | 0.00 |
Minimum of Months | 0.265779E+09 | 0.289197E+09 | 0.428658E+09 | 0.154179E+09 | 0.197825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111295E+10 | 0.103749E+10 | 0.891621E+09 | 0.361844E+09 | 0.710352E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219878E+09 | 0.798731E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.427584E+09 | 0.627563E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.650558E+09 | 0.571193E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.920718E+09 | 0.439100E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.116935E+10 | 0.359185E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.110078E+10 | 0.252257E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.148517E+10 | 0.222907E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.135966E+10 | 0.208264E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.111443E+10 | 0.316895E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.691949E+09 | 0.476197E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.270761E+09 | 0.602545E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.264766E+09 | 0.791826E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967561E+10 | 0.566666E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.219878E+09 | 0.208264E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148517E+10 | 0.798731E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 57848987.95 | 0.839096E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.172291E+09 | 0.652903E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.356183E+09 | 0.574567E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.643199E+09 | 0.436052E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.944305E+09 | 0.361595E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.928529E+09 | 0.256969E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.124513E+10 | 0.237672E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.106111E+10 | 0.217905E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.742996E+09 | 0.331320E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.352029E+09 | 0.480250E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 97341387.69 | 0.619624E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 71737859.15 | 0.823386E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.667270E+10 | 0.583134E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 57848987.95 | 0.217905E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124513E+10 | 0.839096E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254980E+09 | 0.415676E+09 | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.00 | 0.00 |
February | 0.408164E+09 | 0.329775E+09 | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.00 | 0.00 |
March | 0.509078E+09 | 0.303461E+09 | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.00 | 0.00 |
April | 0.555394E+09 | 0.234808E+09 | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.00 | 0.00 |
May | 0.550035E+09 | 0.188975E+09 | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.00 | 0.00 |
June | 0.498764E+09 | 0.131476E+09 | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.00 | 0.00 |
July | 0.619637E+09 | 0.113472E+09 | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.00 | 0.00 |
August | 0.679951E+09 | 0.105887E+09 | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.00 | 0.00 |
September | 0.677721E+09 | 0.164131E+09 | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.00 | 0.00 |
October | 0.568042E+09 | 0.251641E+09 | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.00 | 0.00 |
November | 0.274519E+09 | 0.316980E+09 | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.00 | 0.00 |
December | 0.301239E+09 | 0.413246E+09 | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.589752E+10 | 0.296953E+10 | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.00 | 0.00 |
Minimum of Months | 0.254980E+09 | 0.105887E+09 | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679951E+09 | 0.415676E+09 | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1405299.89 | 0.268010E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 45464454.24 | 0.209688E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.224815E+09 | 0.181730E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.570288E+09 | 0.133583E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.101389E+10 | 0.105211E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.117373E+10 | 0.745684E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.134581E+10 | 0.665647E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.111697E+10 | 0.649966E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.598459E+09 | 0.992189E+09 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.200831E+09 | 0.155768E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 24436759.33 | 0.203241E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 370517.32 | 0.261902E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.631646E+10 | 0.182448E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 370517.32 | 0.649966E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134581E+10 | 0.268010E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 712484.73 | 0.276733E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 39766386.67 | 0.216719E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.203696E+09 | 0.187215E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.542135E+09 | 0.137244E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.984058E+09 | 0.107808E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.114437E+10 | 0.765060E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.132002E+10 | 0.683842E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.109203E+10 | 0.669893E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.576681E+09 | 0.102109E+10 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.182229E+09 | 0.160930E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 20362356.07 | 0.210654E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 197938.66 | 0.270506E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610625E+10 | 0.188180E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 197938.66 | 0.669893E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132002E+10 | 0.276733E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245657E+09 | 0.171050E+10 | 0.519285E+09 | 0.188214E+09 | 0.331072E+09 | 0.00 | 0.00 |
February | 0.603786E+09 | 0.133747E+10 | 0.796974E+09 | 0.334323E+09 | 0.462651E+09 | 0.00 | 0.00 |
March | 0.112716E+10 | 0.120712E+10 | 0.118461E+10 | 0.446443E+09 | 0.738167E+09 | 0.00 | 0.00 |
April | 0.181269E+10 | 0.931840E+09 | 0.160249E+10 | 0.611146E+09 | 0.991341E+09 | 0.00 | 0.00 |
May | 0.213492E+10 | 0.784195E+09 | 0.174915E+10 | 0.534492E+09 | 0.121466E+10 | 0.00 | 0.00 |
June | 0.249196E+10 | 0.581765E+09 | 0.190771E+10 | 0.711401E+09 | 0.119631E+10 | 0.00 | 0.00 |
July | 0.265815E+10 | 0.508294E+09 | 0.188744E+10 | 0.750725E+09 | 0.113672E+10 | 0.00 | 0.00 |
August | 0.268744E+10 | 0.487777E+09 | 0.184714E+10 | 0.837559E+09 | 0.100959E+10 | 0.00 | 0.00 |
September | 0.191679E+10 | 0.662289E+09 | 0.145002E+10 | 0.647584E+09 | 0.802436E+09 | 0.00 | 0.00 |
October | 0.116761E+10 | 0.102624E+10 | 0.107795E+10 | 0.488713E+09 | 0.589235E+09 | 0.00 | 0.00 |
November | 0.399071E+09 | 0.129408E+10 | 0.557632E+09 | 0.200916E+09 | 0.356716E+09 | 0.00 | 0.00 |
December | 0.321783E+09 | 0.168517E+10 | 0.514539E+09 | 0.222431E+09 | 0.292108E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175670E+11 | 0.122167E+11 | 0.150949E+11 | 0.597395E+10 | 0.912099E+10 | 0.00 | 0.00 |
Minimum of Months | 0.245657E+09 | 0.487777E+09 | 0.514539E+09 | 0.188214E+09 | 0.292108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268744E+10 | 0.171050E+10 | 0.190771E+10 | 0.837559E+09 | 0.121466E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586987E+09 | 0.186554E+10 | 0.862687E+09 | 0.448231E+09 | 0.414456E+09 | 0.00 | 0.00 |
February | 0.102495E+10 | 0.145293E+10 | 0.120077E+10 | 0.649789E+09 | 0.550985E+09 | 0.00 | 0.00 |
March | 0.139890E+10 | 0.132760E+10 | 0.148038E+10 | 0.650302E+09 | 0.830075E+09 | 0.00 | 0.00 |
April | 0.165184E+10 | 0.102611E+10 | 0.160184E+10 | 0.541919E+09 | 0.105993E+10 | 0.00 | 0.00 |
May | 0.177207E+10 | 0.844805E+09 | 0.166707E+10 | 0.382872E+09 | 0.128420E+10 | 0.00 | 0.00 |
June | 0.167294E+10 | 0.609756E+09 | 0.152484E+10 | 0.314849E+09 | 0.120999E+10 | 0.00 | 0.00 |
July | 0.201947E+10 | 0.553593E+09 | 0.164725E+10 | 0.468992E+09 | 0.117826E+10 | 0.00 | 0.00 |
August | 0.210295E+10 | 0.540467E+09 | 0.163938E+10 | 0.594219E+09 | 0.104516E+10 | 0.00 | 0.00 |
September | 0.194499E+10 | 0.774728E+09 | 0.163949E+10 | 0.745167E+09 | 0.894325E+09 | 0.00 | 0.00 |
October | 0.153532E+10 | 0.111373E+10 | 0.146946E+10 | 0.779484E+09 | 0.689974E+09 | 0.00 | 0.00 |
November | 0.682638E+09 | 0.141515E+10 | 0.857028E+09 | 0.422081E+09 | 0.434946E+09 | 0.00 | 0.00 |
December | 0.715223E+09 | 0.184158E+10 | 0.890259E+09 | 0.515707E+09 | 0.374552E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171083E+11 | 0.133660E+11 | 0.164805E+11 | 0.651361E+10 | 0.996685E+10 | 0.00 | 0.00 |
Minimum of Months | 0.586987E+09 | 0.540467E+09 | 0.857028E+09 | 0.314849E+09 | 0.374552E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210295E+10 | 0.186554E+10 | 0.166707E+10 | 0.779484E+09 | 0.128420E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770485E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162052936.1 | 81.21 | 0.00 | 0.00 |
February | 0.696231E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146326412.9 | 81.21 | 0.00 | 0.00 |
March | 0.770334E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161882447.8 | 81.21 | 0.00 | 0.00 |
April | 0.746517E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156573312.9 | 81.21 | 0.00 | 0.00 |
May | 0.770449E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161713832.3 | 81.21 | 0.00 | 0.00 |
June | 0.745693E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156407977.4 | 81.21 | 0.00 | 0.00 |
July | 0.771242E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161572433.2 | 81.21 | 0.00 | 0.00 |
August | 0.770435E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161548739.3 | 81.21 | 0.00 | 0.00 |
September | 0.746634E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156418945.6 | 81.21 | 0.00 | 0.00 |
October | 0.770323E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161784464.8 | 81.21 | 0.00 | 0.00 |
November | 0.744912E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156691554.9 | 81.21 | 0.00 | 0.00 |
December | 0.771290E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162025803.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907454E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190500E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696231E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162052936.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771290E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146326412.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.119928E+12 | -0.118179E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174895E+10 | 81.26 | 0.00 | 0.00 |
February | 0.108842E+12 | -0.107257E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158455E+10 | 81.27 | 0.00 | 0.00 |
March | 0.119580E+12 | -0.117820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176000E+10 | 81.26 | 0.00 | 0.00 |
April | 0.113566E+12 | -0.111860E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170633E+10 | 81.26 | 0.00 | 0.00 |
May | 0.114406E+12 | -0.112646E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176057E+10 | 81.26 | 0.00 | 0.00 |
June | 0.107944E+12 | -0.106245E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169884E+10 | 81.26 | 0.00 | 0.00 |
July | 0.109530E+12 | -0.107781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174878E+10 | 81.25 | 0.00 | 0.00 |
August | 0.108905E+12 | -0.107162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174349E+10 | 81.25 | 0.00 | 0.00 |
September | 0.106312E+12 | -0.104630E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168197E+10 | 81.25 | 0.00 | 0.00 |
October | 0.112109E+12 | -0.110374E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173468E+10 | 81.25 | 0.00 | 0.00 |
November | 0.111343E+12 | -0.109665E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167821E+10 | 81.25 | 0.00 | 0.00 |
December | 0.117908E+12 | -0.116168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173984E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.135037E+13 | -0.132979E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205862E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.106312E+12 | -0.118179E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176057E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.119928E+12 | -0.104630E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158455E+10 | 81.27 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.709102E+11 | -0.694167E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149348E+10 | 58.98 | 0.00 | 0.00 |
February | 0.645036E+11 | -0.631480E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.135564E+10 | 58.98 | 0.00 | 0.00 |
March | 0.706799E+11 | -0.691711E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150880E+10 | 58.98 | 0.00 | 0.00 |
April | 0.665176E+11 | -0.650531E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146450E+10 | 58.98 | 0.00 | 0.00 |
May | 0.662133E+11 | -0.647036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150975E+10 | 58.98 | 0.00 | 0.00 |
June | 0.617120E+11 | -0.602577E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145430E+10 | 58.98 | 0.00 | 0.00 |
July | 0.619736E+11 | -0.604798E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149379E+10 | 58.98 | 0.00 | 0.00 |
August | 0.614955E+11 | -0.600092E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148627E+10 | 58.98 | 0.00 | 0.00 |
September | 0.602679E+11 | -0.588369E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143102E+10 | 58.98 | 0.00 | 0.00 |
October | 0.641865E+11 | -0.627125E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147405E+10 | 58.98 | 0.00 | 0.00 |
November | 0.645684E+11 | -0.631427E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142579E+10 | 58.98 | 0.00 | 0.00 |
December | 0.691724E+11 | -0.676914E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148093E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.782201E+12 | -0.764623E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.175783E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.602679E+11 | -0.694167E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.150975E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.709102E+11 | -0.588369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135564E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.88 | 0.86 | 01-JAN-10:09 | 2313.90 | 32.52 | 223.50 | 221.83 | 1753.65 | 33.48 | 226.67 | 177.67 |
February | 259.50 | 0.87 | 0.86 | 01-FEB-08:39 | 4072.80 | 33.17 | 241.00 | 245.50 | 1755.64 | 29.18 | 209.67 | 212.83 |
March | 247.00 | 0.87 | 0.86 | 01-MAR-07:30 | 5992.21 | 30.52 | 183.83 | 315.50 | 753.73 | 22.30 | 170.50 | 254.00 |
April | 379.50 | 0.87 | 0.86 | 01-APR-07:19 | 1564.44 | 19.76 | 106.17 | 349.67 | 605.54 | 21.50 | 244.67 | 288.17 |
May | 427.83 | 0.88 | 0.86 | 01-MAY-07:30 | 1442.36 | 19.59 | 108.50 | 389.00 | 552.25 | 21.29 | 259.83 | 317.00 |
June | 375.17 | 0.88 | 0.86 | 01-JUN-06:00 | 1222.26 | 19.58 | 57.67 | 399.50 | 490.02 | 21.32 | 256.17 | 318.00 |
July | 471.00 | 0.89 | 0.86 | 01-JUL-09:00 | 1053.37 | 18.55 | 68.33 | 397.83 | 422.07 | 20.31 | 212.17 | 289.67 |
August | 366.67 | 0.88 | 0.86 | 01-AUG-06:30 | 1218.12 | 19.63 | 53.33 | 377.83 | 495.75 | 21.37 | 240.50 | 301.50 |
September | 301.17 | 0.87 | 0.86 | 01-SEP-07:00 | 3413.00 | 24.83 | 149.17 | 322.33 | 683.10 | 22.35 | 226.00 | 269.17 |
October | 245.33 | 0.87 | 0.86 | 01-OCT-08:09 | 6361.65 | 34.77 | 221.33 | 287.33 | 913.20 | 24.24 | 188.67 | 244.33 |
November | 242.67 | 0.87 | 0.86 | 01-NOV-08:30 | 2612.59 | 32.24 | 226.33 | 228.50 | 1732.70 | 32.54 | 224.67 | 185.67 |
December | 160.33 | 0.87 | 0.86 | 01-DEC-09:39 | 3101.92 | 35.76 | 150.33 | 211.17 | 2530.32 | 36.82 | 150.33 | 154.17 |
Annual Sum or Average | 3714.00 | 0.88 | 2536.17 | 24.93 | 1789.50 | 3746.00 | 900.71 | 24.28 | 2609.83 | 3012.17 | ||
Minimum of Months | 160.33 | 0.87 | 0.86 | 1053.37 | 18.55 | 53.33 | 211.17 | 422.07 | 20.31 | 150.33 | 154.17 | |
Maximum of Months | 471.00 | 0.89 | 0.86 | 6361.65 | 35.76 | 241.00 | 399.50 | 2530.32 | 36.82 | 259.83 | 318.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.27 | 0.22 | 01-JAN-09:39 | 2537.74 | 32.63 | 224.33 | 233.83 | 1975.68 | 33.57 | 227.50 | 206.33 |
February | 259.50 | 0.26 | 0.22 | 01-FEB-08:30 | 4378.38 | 33.29 | 242.33 | 254.33 | 2058.85 | 29.30 | 217.33 | 232.50 |
March | 247.00 | 0.26 | 0.22 | 01-MAR-07:19 | 6368.42 | 30.77 | 184.33 | 328.67 | 1127.58 | 22.39 | 175.33 | 290.50 |
April | 379.50 | 0.27 | 0.22 | 01-APR-06:00 | 1850.55 | 20.23 | 114.17 | 362.00 | 890.56 | 21.80 | 256.17 | 327.50 |
May | 427.83 | 0.27 | 0.22 | 01-MAY-07:10 | 1692.12 | 20.16 | 134.67 | 404.33 | 801.02 | 21.68 | 288.83 | 366.17 |
June | 375.17 | 0.28 | 0.22 | 01-JUN-05:49 | 1453.91 | 20.13 | 114.00 | 418.17 | 720.93 | 21.70 | 291.83 | 371.00 |
July | 471.00 | 0.31 | 0.22 | 01-JUL-05:30 | 1274.56 | 19.13 | 103.00 | 418.67 | 642.62 | 20.71 | 233.50 | 366.67 |
August | 366.67 | 0.28 | 0.22 | 01-AUG-05:00 | 1497.50 | 19.98 | 84.83 | 394.00 | 774.37 | 21.56 | 246.00 | 352.17 |
September | 301.17 | 0.26 | 0.22 | 01-SEP-07:40 | 3775.30 | 25.02 | 157.50 | 332.00 | 1044.42 | 22.44 | 225.00 | 304.17 |
October | 245.33 | 0.27 | 0.22 | 01-OCT-07:49 | 6743.61 | 34.93 | 221.33 | 299.67 | 1295.45 | 24.23 | 186.00 | 269.83 |
November | 242.67 | 0.26 | 0.22 | 01-NOV-07:00 | 2836.08 | 32.35 | 227.67 | 239.83 | 1955.13 | 32.63 | 224.83 | 213.67 |
December | 160.33 | 0.26 | 0.22 | 01-DEC-09:39 | 3407.81 | 35.90 | 150.33 | 223.67 | 2834.37 | 36.92 | 150.33 | 192.33 |
Annual Sum or Average | 3714.00 | 0.27 | 2816.34 | 25.28 | 1958.50 | 3909.17 | 1179.77 | 24.50 | 2722.67 | 3492.83 | ||
Minimum of Months | 160.33 | 0.26 | 0.22 | 1274.56 | 19.13 | 84.83 | 223.67 | 642.62 | 20.71 | 150.33 | 192.33 | |
Maximum of Months | 471.00 | 0.31 | 0.22 | 6743.61 | 35.90 | 242.33 | 418.67 | 2834.37 | 36.92 | 291.83 | 371.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.71 | 0.60 | 03-JAN-10:30 | 350.19 | 13.75 | 0.00 | 199.67 | 149.72 | 16.99 | 0.00 | 36.17 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:09 | 434.41 | 15.01 | 0.00 | 231.83 | 192.00 | 18.30 | 0.00 | 111.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:09 | 563.11 | 16.39 | 0.00 | 315.00 | 259.94 | 19.64 | 2.33 | 206.67 |
April | 379.50 | 0.63 | 0.60 | 01-APR-07:19 | 674.58 | 17.16 | 0.00 | 360.67 | 301.35 | 20.33 | 50.50 | 304.83 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 843.04 | 18.34 | 17.67 | 409.00 | 373.09 | 21.95 | 192.33 | 366.83 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:30 | 876.37 | 19.62 | 40.17 | 427.00 | 408.72 | 23.56 | 225.17 | 391.33 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-04:00 | 735.34 | 18.60 | 48.00 | 435.17 | 344.16 | 22.67 | 207.67 | 340.17 |
August | 366.67 | 0.63 | 0.60 | 01-AUG-05:40 | 627.16 | 17.86 | 13.17 | 400.00 | 293.70 | 21.05 | 83.33 | 332.33 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:49 | 600.90 | 17.20 | 0.00 | 325.00 | 285.74 | 20.41 | 25.33 | 254.17 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-08:50 | 451.85 | 15.60 | 0.00 | 276.00 | 215.84 | 18.93 | 0.17 | 145.83 |
November | 242.67 | 0.70 | 0.60 | 01-NOV-11:39 | 378.80 | 14.21 | 0.00 | 212.00 | 160.91 | 17.43 | 0.00 | 51.33 |
December | 160.33 | 0.72 | 0.60 | 01-DEC-10:20 | 316.81 | 13.88 | 0.00 | 179.33 | 149.55 | 17.36 | 0.00 | 27.00 |
Annual Sum or Average | 3714.00 | 0.65 | 616.97 | 16.94 | 119.00 | 3770.67 | 282.39 | 20.41 | 786.83 | 2568.33 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 316.81 | 13.75 | 0.00 | 179.33 | 149.55 | 16.99 | 0.00 | 27.00 | |
Maximum of Months | 471.00 | 0.72 | 0.60 | 876.37 | 19.62 | 48.00 | 435.17 | 408.72 | 23.56 | 225.17 | 391.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.71 | 0.60 | 03-JAN-10:30 | 350.19 | 13.75 | 0.00 | 199.67 | 149.72 | 16.99 | 0.00 | 36.17 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:09 | 434.41 | 15.01 | 0.00 | 231.83 | 192.00 | 18.30 | 0.00 | 111.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:09 | 563.11 | 16.39 | 0.00 | 315.00 | 259.94 | 19.64 | 2.33 | 206.67 |
April | 379.50 | 0.63 | 0.60 | 01-APR-07:19 | 674.58 | 17.16 | 0.00 | 360.67 | 301.35 | 20.33 | 50.50 | 304.83 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 843.04 | 18.34 | 17.67 | 409.00 | 373.09 | 21.95 | 192.33 | 366.83 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:30 | 876.37 | 19.62 | 40.17 | 427.00 | 408.72 | 23.56 | 225.17 | 391.33 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-04:00 | 735.34 | 18.60 | 48.00 | 435.17 | 344.16 | 22.67 | 207.67 | 340.17 |
August | 366.67 | 0.63 | 0.60 | 01-AUG-05:40 | 627.16 | 17.86 | 13.17 | 400.00 | 293.70 | 21.05 | 83.33 | 332.33 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:49 | 600.90 | 17.20 | 0.00 | 325.00 | 285.74 | 20.41 | 25.33 | 254.17 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-08:50 | 451.85 | 15.60 | 0.00 | 276.00 | 215.84 | 18.93 | 0.17 | 145.83 |
November | 242.67 | 0.70 | 0.60 | 01-NOV-11:39 | 378.80 | 14.21 | 0.00 | 212.00 | 160.91 | 17.43 | 0.00 | 51.33 |
December | 160.33 | 0.72 | 0.60 | 01-DEC-10:20 | 316.81 | 13.88 | 0.00 | 179.33 | 149.55 | 17.36 | 0.00 | 27.00 |
Annual Sum or Average | 3714.00 | 0.65 | 616.97 | 16.94 | 119.00 | 3770.67 | 282.39 | 20.41 | 786.83 | 2568.33 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 316.81 | 13.75 | 0.00 | 179.33 | 149.55 | 16.99 | 0.00 | 27.00 | |
Maximum of Months | 471.00 | 0.72 | 0.60 | 876.37 | 19.62 | 48.00 | 435.17 | 408.72 | 23.56 | 225.17 | 391.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.425994E+11 | 122910.12 | 20-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.567933E+11 | 124246.33 | 07-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857947E+11 | 118733.10 | 22-MAR-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918032E+11 | 116393.14 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.849114E+11 | 116077.52 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.433714E+11 | 97999.51 | 15-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162113E+11 | 58096.27 | 07-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123930E+11 | 58169.19 | 21-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452869E+11 | 101762.47 | 28-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115144E+12 | 119064.82 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753894E+11 | 138803.02 | 11-NOV-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496512E+11 | 127477.52 | 12-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.123930E+11 | 58096.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115144E+12 | 138803.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346679E+10 | 2083.24 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230973E+10 | 2276.58 | 19-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180092E+10 | 1688.90 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105996E+10 | 1429.18 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.683403E+09 | 1184.86 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334313E+09 | 953.67 | 14-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115237E+09 | 739.19 | 12-JUL-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139481E+09 | 652.08 | 04-AUG-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.451799E+09 | 1286.08 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123421E+10 | 1432.07 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250533E+10 | 1978.34 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326586E+10 | 2296.24 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.115237E+09 | 652.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346679E+10 | 2296.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61852732.03 | 426.54 | 16-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22686105.07 | 338.09 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 830946.69 | 120.83 | 13-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10362667.49 | 223.69 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57214000.30 | 451.83 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61852732.03 | 451.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.781961E+09 | 784.33 | 16-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.455513E+09 | 725.52 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 62144204.93 | 425.49 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2452414.23 | 242.75 | 19-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 320738.73 | 44.22 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232467E+09 | 500.77 | 14-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599917E+09 | 781.91 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.781961E+09 | 784.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737083E+09 | 562.33 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451791E+09 | 549.51 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130861E+09 | 353.31 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18968768.84 | 241.26 | 18-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7615160.05 | 163.91 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294069E+09 | 406.43 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614210E+09 | 570.00 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737083E+09 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137907E+09 | 1418.23 | 17-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91329058.93 | 1418.24 | 18-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50514977.90 | 972.35 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22491104.09 | 761.29 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4592540.83 | 369.02 | 18-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 387131.09 | 128.19 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39096.73 | 65.16 | 03-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1318187.42 | 310.19 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20461981.13 | 652.39 | 28-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64144919.30 | 1125.23 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131031E+09 | 1418.24 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137907E+09 | 1418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275430E+10 | 5071.85 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135010E+10 | 5056.92 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.879087E+09 | 4022.08 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242070E+09 | 3108.57 | 18-APR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125086E+09 | 2678.48 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28245273.97 | 2322.97 | 14-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11798580.53 | 1960.00 | 12-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6237810.43 | 1270.31 | 01-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151933E+09 | 3355.60 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501883E+09 | 3632.67 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170025E+10 | 5180.69 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254220E+10 | 6030.79 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6237810.43 | 1270.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275430E+10 | 6030.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.761792E+09 | 7517.56 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230062E+09 | 5716.85 | 17-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11653372.70 | 2388.46 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173472E+09 | 4466.06 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786753E+09 | 8305.91 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.786753E+09 | 8305.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.799297E+10 | 6695.99 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444744E+10 | 6302.48 | 17-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162136E+10 | 4789.79 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199224E+09 | 3116.88 | 11-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785368E+09 | 4026.12 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448015E+10 | 6154.98 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718171E+10 | 7183.21 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.799297E+10 | 7183.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397952E+10 | 3032.59 | 16-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234077E+10 | 3427.53 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.882874E+09 | 1817.18 | 25-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196774E+09 | 1512.91 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 171141.14 | 168.10 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2548993.51 | 388.94 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340112E+09 | 1322.13 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204245E+10 | 2536.44 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362181E+10 | 3343.16 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397952E+10 | 3427.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114071E+09 | 1642.81 | 07-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95243714.89 | 2206.46 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13922.70 | 20.23 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4780.58 | 0.53 | 29-APR-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8064.32 | 0.53 | 05-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23608.77 | 0.53 | 21-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24867.71 | 0.54 | 30-JUL-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28574.24 | 0.54 | 15-AUG-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20807.92 | 0.54 | 23-SEP-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4456.95 | 0.53 | 05-OCT-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 218670.90 | 361.97 | 30-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21704288.62 | 2717.24 | 26-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4456.95 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114071E+09 | 2717.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415029E+10 | 5358.73 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261065E+10 | 5357.89 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152818E+10 | 5321.50 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646160E+09 | 5218.73 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197714E+09 | 4539.07 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42901757.50 | 4148.48 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9233888.51 | 3998.14 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13000780.73 | 4004.87 | 04-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87494596.70 | 4386.67 | 06-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.827737E+09 | 5214.54 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249344E+10 | 5358.49 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384182E+10 | 5359.43 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9233888.51 | 3998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415029E+10 | 5359.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.471660E+10 | 5280.00 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323252E+10 | 5279.25 | 14-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196495E+10 | 5265.56 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.827917E+09 | 5147.19 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214424E+09 | 4314.05 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44348908.18 | 4454.61 | 27-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8191404.24 | 4273.39 | 19-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11308474.17 | 4371.58 | 23-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102669E+09 | 4613.66 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113150E+10 | 5157.84 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293467E+10 | 5279.75 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443113E+10 | 5280.76 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8191404.24 | 4273.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.471660E+10 | 5280.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120669E+11 | 29283.47 | 07-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.802180E+10 | 29161.61 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244727E+10 | 28535.57 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.574599E+09 | 28275.24 | 08-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84486104.93 | 28279.00 | 16-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49010813.39 | 28277.53 | 04-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36443413.07 | 28234.48 | 16-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46736187.46 | 28249.84 | 02-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106552E+09 | 28257.44 | 18-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.758305E+09 | 28266.67 | 03-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486364E+10 | 29007.31 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105247E+11 | 29373.07 | 26-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 36443413.07 | 28234.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120669E+11 | 29373.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419041E+10 | 5275.89 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263125E+10 | 5275.00 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149212E+10 | 5230.49 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619084E+09 | 5128.84 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245200E+09 | 4474.20 | 16-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45643456.86 | 4441.74 | 07-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10306723.33 | 4772.61 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12255115.69 | 4750.48 | 31-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107372E+09 | 4563.51 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.850761E+09 | 5139.58 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250944E+10 | 5275.64 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387955E+10 | 5276.65 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10306723.33 | 4441.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419041E+10 | 5276.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.477168E+10 | 5196.01 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324345E+10 | 5195.07 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190001E+10 | 5173.01 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771381E+09 | 5056.31 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275046E+09 | 4905.22 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48297145.08 | 4465.79 | 23-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9949774.06 | 4470.25 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8374945.75 | 4464.26 | 03-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138588E+09 | 4822.77 | 19-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115462E+10 | 5083.33 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293281E+10 | 5195.75 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.445734E+10 | 5196.82 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8374945.75 | 4464.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477168E+10 | 5196.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144984E+10 | 1582.09 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.941455E+09 | 1582.07 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.588228E+09 | 1581.82 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272410E+09 | 1560.60 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110129E+09 | 1542.05 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30044723.52 | 1201.52 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3961471.89 | 1108.49 | 04-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6712187.39 | 1061.45 | 04-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52396071.96 | 1314.24 | 18-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353711E+09 | 1560.67 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.911137E+09 | 1582.10 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135196E+10 | 1582.31 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3961471.89 | 1061.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144984E+10 | 1582.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162282E+10 | 1554.25 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113402E+10 | 1554.22 | 15-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728410E+09 | 1553.98 | 05-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332673E+09 | 1534.50 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112110E+09 | 1513.14 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26990065.53 | 1062.43 | 27-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2116200.53 | 1036.03 | 15-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4176699.44 | 1076.79 | 04-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58201921.97 | 1499.22 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463244E+09 | 1539.43 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104860E+10 | 1554.27 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153467E+10 | 1554.47 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2116200.53 | 1036.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162282E+10 | 1554.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.424912E+10 | 7751.11 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239582E+10 | 7724.95 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121015E+10 | 7594.92 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553132E+09 | 7476.84 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230022E+09 | 6395.87 | 11-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51789749.31 | 6552.30 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15337594.43 | 6216.68 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19208854.95 | 5729.70 | 18-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86774747.75 | 5519.85 | 30-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.549004E+09 | 7468.62 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225045E+10 | 7750.50 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396820E+10 | 7750.93 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15337594.43 | 5519.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.424912E+10 | 7751.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.175155E+10 | 0.175155E+10 | 78777.98 | 27-FEB-15:00 | 78777.98 | 0.01 |
March | 0.00 | 0.00 | 0.387079E+10 | 0.387079E+10 | 103583.92 | 18-MAR-16:10 | 103583.92 | 0.02 |
April | 0.00 | 0.00 | 0.281901E+11 | 0.281901E+11 | 204511.87 | 27-APR-18:10 | 204511.87 | 0.07 |
May | 0.00 | 0.00 | 0.545502E+11 | 0.542280E+11 | 205686.61 | 05-MAY-18:00 | 170899.94 | 0.21 |
June | 0.00 | 0.00 | 0.977781E+11 | 0.976865E+11 | 208837.45 | 28-JUN-18:10 | 208837.45 | 0.46 |
July | 0.00 | 0.00 | 0.165331E+12 | 0.160590E+12 | 263984.87 | 27-JUL-18:03 | 202188.36 | 0.68 |
August | 0.00 | 0.00 | 0.208657E+12 | 0.201105E+12 | 286713.46 | 10-AUG-18:10 | 248470.45 | 0.79 |
September | 0.00 | 0.00 | 0.794603E+11 | 0.776976E+11 | 197734.67 | 14-SEP-17:15 | 179404.70 | 0.47 |
October | 0.00 | 0.00 | 0.147084E+11 | 0.146930E+11 | 123818.23 | 04-OCT-15:15 | 123818.23 | 0.10 |
November | 0.00 | 0.00 | 0.335422E+10 | 0.335422E+10 | 102360.86 | 04-NOV-14:30 | 102360.86 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.657652E+12 | 0.643167E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208657E+12 | 0.201105E+12 | 286713.46 | 248470.45 | 0.79 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108438E+09 | 0.108438E+09 | 9635.08 | 27-FEB-16:03 | 9635.08 | 0.00 |
March | 0.00 | 0.00 | 0.233614E+09 | 0.233614E+09 | 12388.66 | 18-MAR-16:00 | 12388.66 | 0.01 |
April | 0.00 | 0.00 | 0.179828E+10 | 0.179828E+10 | 18211.92 | 27-APR-15:02 | 18211.92 | 0.04 |
May | 0.00 | 0.00 | 0.355652E+10 | 0.343549E+10 | 20677.56 | 05-MAY-18:03 | 16125.17 | 0.14 |
June | 0.00 | 0.00 | 0.630854E+10 | 0.630854E+10 | 17789.39 | 28-JUN-15:02 | 17789.39 | 0.32 |
July | 0.00 | 0.00 | 0.116662E+11 | 0.109072E+11 | 23708.15 | 15-JUL-18:03 | 15807.51 | 0.51 |
August | 0.00 | 0.00 | 0.152467E+11 | 0.141061E+11 | 24768.28 | 30-AUG-12:40 | 15889.63 | 0.61 |
September | 0.00 | 0.00 | 0.544442E+10 | 0.511307E+10 | 22992.79 | 14-SEP-12:50 | 15654.78 | 0.32 |
October | 0.00 | 0.00 | 0.903569E+09 | 0.903569E+09 | 14148.91 | 04-OCT-15:01 | 14148.91 | 0.06 |
November | 0.00 | 0.00 | 0.218215E+09 | 0.196313E+09 | 15659.16 | 04-NOV-15:01 | 13199.77 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454846E+11 | 0.431106E+11 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152467E+11 | 0.141061E+11 | 24768.28 | 18211.92 | 0.61 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6748521.40 | 4977643.70 | 11280.64 | 05-JAN-16:01 | 11280.64 | 0.00 |
February | 0.00 | 0.00 | 0.169901E+09 | 0.101981E+09 | 16995.06 | 08-FEB-16:01 | 16995.06 | 0.04 |
March | 0.00 | 0.00 | 0.649117E+09 | 0.456742E+09 | 16992.82 | 01-MAR-16:01 | 16992.82 | 0.10 |
April | 0.00 | 0.00 | 0.202341E+10 | 0.121207E+10 | 16998.20 | 25-APR-18:01 | 16998.20 | 0.37 |
May | 0.00 | 0.00 | 0.389502E+10 | 0.219604E+10 | 16996.77 | 20-MAY-18:01 | 16996.77 | 0.64 |
June | 0.00 | 0.00 | 0.470185E+10 | 0.241218E+10 | 17128.20 | 12-JUN-15:01 | 14071.92 | 0.82 |
July | 0.00 | 0.00 | 0.760143E+10 | 0.424302E+10 | 16910.18 | 16-JUL-15:01 | 14264.60 | 0.91 |
August | 0.00 | 0.00 | 0.747709E+10 | 0.410248E+10 | 17425.39 | 30-AUG-08:62 | 12521.15 | 0.90 |
September | 0.00 | 0.00 | 0.479628E+10 | 0.246790E+10 | 16628.63 | 23-SEP-08:61 | 14192.01 | 0.75 |
October | 0.00 | 0.00 | 0.129170E+10 | 0.644015E+09 | 16997.50 | 04-OCT-18:01 | 16997.50 | 0.31 |
November | 0.00 | 0.00 | 0.141719E+09 | 58489309.88 | 16718.97 | 05-NOV-15:01 | 14303.60 | 0.05 |
December | 0.00 | 0.00 | 15025359.13 | 11389047.71 | 16425.79 | 02-DEC-16:02 | 16425.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.327693E+11 | 0.179113E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 6748521.40 | 4977643.70 | 11280.64 | 11280.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.760143E+10 | 0.424302E+10 | 17425.39 | 16998.20 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 964576.07 | 246009.91 | 1203.99 | 20-JAN-16:04 | 366.28 | 0.00 |
February | 0.00 | 0.00 | 32461181.57 | 15326552.55 | 12957.58 | 26-FEB-16:01 | 12957.58 | 0.01 |
March | 0.00 | 0.00 | 0.196520E+09 | 0.126220E+09 | 15417.08 | 01-MAR-16:01 | 15417.08 | 0.04 |
April | 0.00 | 0.00 | 0.106411E+10 | 0.591386E+09 | 17823.45 | 25-APR-17:41 | 17823.45 | 0.24 |
May | 0.00 | 0.00 | 0.221659E+10 | 0.104275E+10 | 17850.20 | 21-MAY-17:41 | 17850.20 | 0.50 |
June | 0.00 | 0.00 | 0.303101E+10 | 0.142715E+10 | 15757.68 | 12-JUN-18:01 | 12599.96 | 0.60 |
July | 0.00 | 0.00 | 0.502341E+10 | 0.267978E+10 | 17435.45 | 15-JUL-21:51 | 14200.66 | 0.66 |
August | 0.00 | 0.00 | 0.498674E+10 | 0.269284E+10 | 16044.15 | 30-AUG-08:51 | 11757.07 | 0.65 |
September | 0.00 | 0.00 | 0.227016E+10 | 0.905451E+09 | 15960.61 | 24-SEP-18:11 | 12983.88 | 0.52 |
October | 0.00 | 0.00 | 0.387851E+09 | 0.149394E+09 | 15715.81 | 01-OCT-15:01 | 12653.60 | 0.16 |
November | 0.00 | 0.00 | 26057814.65 | 8815396.73 | 15134.55 | 04-NOV-15:01 | 13111.50 | 0.01 |
December | 0.00 | 0.00 | 1213439.30 | 333125.13 | 1565.18 | 28-DEC-19:06 | 381.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192371E+11 | 0.963969E+10 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 964576.07 | 246009.91 | 1203.99 | 366.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.502341E+10 | 0.269284E+10 | 17850.20 | 17850.20 | 0.66 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.208797E+10 | 0.196471E+10 | 30234.93 | 08-FEB-14:00 | 30234.93 | 0.02 |
March | 0.00 | 0.00 | 0.868295E+10 | 0.810133E+10 | 44001.97 | 02-MAR-13:30 | 44001.97 | 0.03 |
April | 0.00 | 0.00 | 0.159708E+11 | 0.106238E+11 | 42983.08 | 27-APR-13:05 | 31038.30 | 0.31 |
May | 0.00 | 0.00 | 0.215685E+11 | 0.901378E+10 | 42332.34 | 04-MAY-13:15 | 28731.38 | 0.62 |
June | 0.00 | 0.00 | 0.247211E+11 | 0.790258E+10 | 32176.41 | 28-JUN-13:00 | 16948.80 | 0.82 |
July | 0.00 | 0.00 | 0.356028E+11 | 0.128276E+11 | 41314.87 | 31-JUL-13:00 | 26237.17 | 0.93 |
August | 0.00 | 0.00 | 0.411049E+11 | 0.168780E+11 | 51738.68 | 24-AUG-13:00 | 40516.96 | 0.92 |
September | 0.00 | 0.00 | 0.337947E+11 | 0.153718E+11 | 54376.18 | 14-SEP-13:15 | 45305.66 | 0.82 |
October | 0.00 | 0.00 | 0.179519E+11 | 0.987473E+10 | 54529.17 | 04-OCT-12:30 | 52409.31 | 0.41 |
November | 0.00 | 0.00 | 0.231869E+10 | 0.113310E+10 | 41742.43 | 04-NOV-13:25 | 26380.82 | 0.06 |
December | 0.00 | 0.00 | 0.710587E+09 | 0.710587E+09 | 24605.97 | 05-DEC-12:30 | 24605.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204515E+12 | 0.944022E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.411049E+11 | 0.168780E+11 | 54529.17 | 52409.31 | 0.93 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.690167E+09 | 0.264891E+09 | 60726.02 | 01-JAN-09:02 | 60726.02 | 0.08 |
February | 0.00 | 0.00 | 0.248834E+10 | 0.942536E+09 | 75865.12 | 25-FEB-09:02 | 68649.23 | 0.18 |
March | 0.00 | 0.00 | 0.611912E+10 | 0.315801E+10 | 77182.13 | 18-MAR-20:42 | 77182.13 | 0.30 |
April | 0.00 | 0.00 | 0.142038E+11 | 0.792161E+10 | 79455.31 | 24-APR-18:01 | 79455.31 | 0.50 |
May | 0.00 | 0.00 | 0.238213E+11 | 0.138280E+11 | 82047.86 | 06-MAY-21:51 | 69433.81 | 0.60 |
June | 0.00 | 0.00 | 0.302138E+11 | 0.185371E+11 | 81663.25 | 12-JUN-18:01 | 69437.59 | 0.58 |
July | 0.00 | 0.00 | 0.362482E+11 | 0.228038E+11 | 85982.90 | 26-JUL-21:51 | 70295.04 | 0.58 |
August | 0.00 | 0.00 | 0.366127E+11 | 0.214308E+11 | 86418.41 | 26-AUG-21:51 | 67757.49 | 0.57 |
September | 0.00 | 0.00 | 0.237079E+11 | 0.118475E+11 | 83167.80 | 15-SEP-21:51 | 68616.70 | 0.55 |
October | 0.00 | 0.00 | 0.104494E+11 | 0.440008E+10 | 80907.32 | 01-OCT-15:01 | 65848.49 | 0.51 |
November | 0.00 | 0.00 | 0.427181E+10 | 0.149235E+10 | 76817.05 | 04-NOV-15:01 | 65577.46 | 0.28 |
December | 0.00 | 0.00 | 0.587070E+09 | 0.277996E+09 | 75115.67 | 03-DEC-09:02 | 75115.67 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.189414E+12 | 0.106905E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.587070E+09 | 0.264891E+09 | 60726.02 | 60726.02 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.366127E+11 | 0.228038E+11 | 86418.41 | 79455.31 | 0.60 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3455668.15 | 835414.24 | 1690.25 | 05-JAN-09:04 | 621.44 | 0.00 |
February | 0.00 | 0.00 | 0.147637E+09 | 81254902.36 | 14510.78 | 08-FEB-16:01 | 14510.78 | 0.04 |
March | 0.00 | 0.00 | 0.596708E+09 | 0.409277E+09 | 15285.96 | 01-MAR-16:01 | 15285.96 | 0.11 |
April | 0.00 | 0.00 | 0.207569E+10 | 0.113828E+10 | 15288.64 | 19-APR-15:01 | 15288.64 | 0.43 |
May | 0.00 | 0.00 | 0.335985E+10 | 0.173008E+10 | 15290.82 | 21-MAY-18:01 | 15290.82 | 0.63 |
June | 0.00 | 0.00 | 0.503269E+10 | 0.261662E+10 | 14988.89 | 12-JUN-15:01 | 12993.58 | 0.85 |
July | 0.00 | 0.00 | 0.660027E+10 | 0.348419E+10 | 15706.32 | 16-JUL-15:01 | 12453.59 | 0.93 |
August | 0.00 | 0.00 | 0.739686E+10 | 0.403336E+10 | 15756.54 | 30-AUG-08:62 | 11469.43 | 0.92 |
September | 0.00 | 0.00 | 0.431335E+10 | 0.218169E+10 | 15515.68 | 24-SEP-15:01 | 12597.93 | 0.74 |
October | 0.00 | 0.00 | 0.126419E+10 | 0.613379E+09 | 15816.60 | 01-OCT-15:01 | 12361.75 | 0.33 |
November | 0.00 | 0.00 | 0.145864E+09 | 45795876.04 | 14742.82 | 05-NOV-15:01 | 12416.51 | 0.06 |
December | 0.00 | 0.00 | 39092897.76 | 20117557.80 | 7353.65 | 02-DEC-09:02 | 6404.50 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.309757E+11 | 0.163549E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 3455668.15 | 835414.24 | 1690.25 | 621.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.739686E+10 | 0.403336E+10 | 15816.60 | 15290.82 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1080998.00 | 225352.44 | 1150.01 | 10-JAN-19:06 | 365.59 | 0.00 |
February | 0.00 | 0.00 | 13563619.66 | 6704772.12 | 10215.09 | 27-FEB-16:01 | 10215.09 | 0.01 |
March | 0.00 | 0.00 | 0.145562E+09 | 0.100462E+09 | 13704.10 | 25-MAR-08:61 | 13704.10 | 0.03 |
April | 0.00 | 0.00 | 0.113017E+10 | 0.591576E+09 | 13680.10 | 25-APR-18:01 | 13680.10 | 0.30 |
May | 0.00 | 0.00 | 0.208196E+10 | 0.103046E+10 | 14479.53 | 06-MAY-08:51 | 14172.74 | 0.49 |
June | 0.00 | 0.00 | 0.355457E+10 | 0.185624E+10 | 14143.99 | 12-JUN-18:01 | 11489.84 | 0.66 |
July | 0.00 | 0.00 | 0.445924E+10 | 0.232637E+10 | 16547.05 | 31-JUL-08:32 | 15300.52 | 0.69 |
August | 0.00 | 0.00 | 0.499500E+10 | 0.266218E+10 | 16752.67 | 10-AUG-08:32 | 15390.40 | 0.69 |
September | 0.00 | 0.00 | 0.217991E+10 | 0.100730E+10 | 14201.21 | 15-SEP-21:51 | 11584.68 | 0.50 |
October | 0.00 | 0.00 | 0.420269E+09 | 0.197661E+09 | 14098.54 | 01-OCT-15:01 | 10486.48 | 0.15 |
November | 0.00 | 0.00 | 22700594.43 | 6875209.22 | 13388.55 | 04-NOV-15:01 | 10906.87 | 0.01 |
December | 0.00 | 0.00 | 1424161.76 | 477427.67 | 1447.93 | 28-DEC-19:06 | 358.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190055E+11 | 0.978653E+10 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 1080998.00 | 225352.44 | 1150.01 | 358.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.499500E+10 | 0.266218E+10 | 16752.67 | 15390.40 | 0.69 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1169933.87 | 905113.68 | 2842.73 | 20-JAN-16:01 | 2842.73 | 0.00 |
February | 0.00 | 0.00 | 43996989.88 | 26795563.47 | 4429.18 | 08-FEB-16:01 | 4429.18 | 0.03 |
March | 0.00 | 0.00 | 0.168730E+09 | 0.122154E+09 | 4428.47 | 01-MAR-16:01 | 4428.47 | 0.08 |
April | 0.00 | 0.00 | 0.525340E+09 | 0.334644E+09 | 4458.95 | 30-APR-08:62 | 3378.75 | 0.31 |
May | 0.00 | 0.00 | 0.100423E+10 | 0.611878E+09 | 4429.19 | 20-MAY-18:01 | 4429.19 | 0.57 |
June | 0.00 | 0.00 | 0.119817E+10 | 0.657602E+09 | 4463.43 | 12-JUN-15:01 | 3666.32 | 0.75 |
July | 0.00 | 0.00 | 0.194557E+10 | 0.114954E+10 | 4454.72 | 15-JUL-08:61 | 3648.83 | 0.89 |
August | 0.00 | 0.00 | 0.186339E+10 | 0.107478E+10 | 4561.29 | 20-AUG-08:61 | 3256.48 | 0.86 |
September | 0.00 | 0.00 | 0.117061E+10 | 0.649500E+09 | 4556.52 | 23-SEP-08:61 | 3397.82 | 0.67 |
October | 0.00 | 0.00 | 0.299977E+09 | 0.162214E+09 | 4487.74 | 01-OCT-08:62 | 3240.34 | 0.24 |
November | 0.00 | 0.00 | 35226680.35 | 16247630.04 | 4412.42 | 05-NOV-15:01 | 3708.37 | 0.04 |
December | 0.00 | 0.00 | 3380158.64 | 2538165.61 | 4314.47 | 02-DEC-16:02 | 4314.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.825978E+10 | 0.480880E+10 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 1169933.87 | 905113.68 | 2842.73 | 2842.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194557E+10 | 0.114954E+10 | 4561.29 | 4429.19 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 91590.07 | 29270.76 | 466.76 | 05-JAN-16:04 | 182.85 | 0.00 |
February | 0.00 | 0.00 | 6302887.95 | 2662616.15 | 3377.92 | 26-FEB-16:01 | 3377.92 | 0.01 |
March | 0.00 | 0.00 | 47033105.21 | 29879128.38 | 3988.55 | 01-MAR-16:01 | 3988.55 | 0.04 |
April | 0.00 | 0.00 | 0.273644E+09 | 0.164474E+09 | 4617.69 | 25-APR-17:41 | 4617.69 | 0.20 |
May | 0.00 | 0.00 | 0.576464E+09 | 0.295931E+09 | 4619.00 | 21-MAY-17:41 | 4619.00 | 0.44 |
June | 0.00 | 0.00 | 0.789051E+09 | 0.395966E+09 | 4273.71 | 22-JUN-21:51 | 3869.73 | 0.58 |
July | 0.00 | 0.00 | 0.133294E+10 | 0.738129E+09 | 4608.46 | 26-JUL-21:51 | 3710.63 | 0.67 |
August | 0.00 | 0.00 | 0.125933E+10 | 0.716890E+09 | 4222.35 | 26-AUG-21:51 | 3109.12 | 0.64 |
September | 0.00 | 0.00 | 0.531334E+09 | 0.228358E+09 | 4212.41 | 13-SEP-21:51 | 3526.57 | 0.46 |
October | 0.00 | 0.00 | 75482725.51 | 31840960.27 | 4066.38 | 01-OCT-15:01 | 3272.09 | 0.11 |
November | 0.00 | 0.00 | 5510879.13 | 1907869.03 | 3915.83 | 04-NOV-15:01 | 3390.78 | 0.01 |
December | 0.00 | 0.00 | 236836.20 | 116471.75 | 430.71 | 10-DEC-16:03 | 118.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.489742E+10 | 0.260618E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 91590.07 | 29270.76 | 430.71 | 118.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.133294E+10 | 0.738129E+09 | 4619.00 | 4619.00 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361188E+09 | 0.199338E+09 | 19870.58 | 09-JAN-16:02 | 19870.58 | 0.05 |
February | 0.00 | 0.00 | 0.154166E+10 | 0.951776E+09 | 24295.69 | 19-FEB-16:01 | 24295.69 | 0.20 |
March | 0.00 | 0.00 | 0.270176E+10 | 0.188959E+10 | 24299.52 | 26-MAR-15:01 | 24299.52 | 0.27 |
April | 0.00 | 0.00 | 0.429362E+10 | 0.233585E+10 | 24112.11 | 30-APR-15:02 | 20014.50 | 0.54 |
May | 0.00 | 0.00 | 0.558377E+10 | 0.281507E+10 | 24294.31 | 14-MAY-18:01 | 24294.31 | 0.69 |
June | 0.00 | 0.00 | 0.644855E+10 | 0.297152E+10 | 24552.66 | 12-JUN-15:01 | 20146.35 | 0.84 |
July | 0.00 | 0.00 | 0.931972E+10 | 0.460060E+10 | 24920.32 | 16-JUL-15:01 | 19892.20 | 0.91 |
August | 0.00 | 0.00 | 0.105335E+11 | 0.558711E+10 | 24064.78 | 29-AUG-08:62 | 20154.21 | 0.90 |
September | 0.00 | 0.00 | 0.839097E+10 | 0.468930E+10 | 23413.11 | 23-SEP-08:61 | 21040.01 | 0.80 |
October | 0.00 | 0.00 | 0.428769E+10 | 0.236762E+10 | 24299.05 | 04-OCT-18:01 | 24299.05 | 0.54 |
November | 0.00 | 0.00 | 0.106871E+10 | 0.498819E+09 | 23048.98 | 05-NOV-08:62 | 20220.99 | 0.17 |
December | 0.00 | 0.00 | 0.842779E+09 | 0.554735E+09 | 24305.08 | 03-DEC-16:01 | 24305.08 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.553739E+11 | 0.294613E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.361188E+09 | 0.199338E+09 | 19870.58 | 19870.58 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.105335E+11 | 0.558711E+10 | 24920.32 | 24305.08 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 37239.53 | 168443.16 | 02-JAN-16:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38047.58 | 166408.03 | 22-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 38196.34 | 148581.37 | 03-MAR-19:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37593.08 | 128631.30 | 11-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32328.33 | 118668.24 | 28-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16886.95 | 102035.27 | 15-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 6093.80 | 64238.68 | 12-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 4694.38 | 69955.82 | 03-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 17864.97 | 116829.47 | 27-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 46022.63 | 164500.23 | 30-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 40900.47 | 173420.83 | 17-NOV-09:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 37934.49 | 172528.96 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 29426.00 | ||||
Minimum of Months | 0.00 | 0.00 | 4694.38 | 64238.68 | ||
Maximum of Months | 0.00 | 0.00 | 46022.63 | 173420.83 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 738.78 | 39112.57 | 11-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 4284.70 | 198002.96 | 27-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 10059.45 | 260919.92 | 18-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 29458.00 | 389997.99 | 27-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47767.45 | 354141.62 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 73115.55 | 392875.24 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 108678.26 | 456805.70 | 31-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 129213.78 | 489160.77 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 66234.64 | 391215.10 | 14-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 21138.11 | 307831.24 | 04-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5321.16 | 297484.40 | 04-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1234.29 | 39792.72 | 02-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 41719.41 | 0.00 | ||||
Minimum of Months | 738.78 | 39112.57 | 0.00 | 0.00 | ||
Maximum of Months | 129213.78 | 489160.77 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 27483.34 | 55997.15 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27668.03 | 56066.80 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27391.68 | 55857.43 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26665.72 | 54630.66 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25727.97 | 52983.22 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24820.31 | 50924.13 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24154.12 | 49170.43 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23979.27 | 48466.50 | 29-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24273.55 | 49464.44 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24986.25 | 51380.26 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25930.12 | 53359.54 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26840.02 | 54991.58 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 25815.99 | ||||
Minimum of Months | 0.00 | 0.00 | 23979.27 | 48466.50 | ||
Maximum of Months | 0.00 | 0.00 | 27668.03 | 56066.80 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.70 | 1299.30 | 14-JAN-16:07 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 13-FEB-19:04 | 0.89 |
March | 0.271000E+10 | 0.70 | 1299.30 | 04-MAR-09:03 | 0.89 |
April | 0.262258E+10 | 0.70 | 1299.30 | 02-APR-20:40 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 04-MAY-08:15 | 0.89 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-20:40 | 0.89 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-21:10 | 0.89 |
August | 0.271000E+10 | 0.70 | 1299.30 | 02-AUG-18:40 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 02-SEP-18:03 | 0.88 |
October | 0.271000E+10 | 0.70 | 1299.30 | 01-OCT-08:08 | 0.88 |
November | 0.262258E+10 | 0.70 | 1299.30 | 30-NOV-09:04 | 0.89 |
December | 0.271000E+10 | 0.70 | 1299.30 | 01-DEC-00:03 | 0.89 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.328667E+11 | 0.79 | 18290.21 | 11-JAN-21:10 | 0.99 |
February | 0.300603E+11 | 0.79 | 18913.48 | 27-FEB-22:10 | 1.01 |
March | 0.340393E+11 | 0.80 | 19024.75 | 14-MAR-21:10 | 1.01 |
April | 0.335971E+11 | 0.81 | 23507.49 | 27-APR-21:10 | 1.15 |
May | 0.355078E+11 | 0.82 | 23447.41 | 04-MAY-21:10 | 1.15 |
June | 0.350361E+11 | 0.83 | 23670.96 | 28-JUN-21:10 | 1.15 |
July | 0.367629E+11 | 0.83 | 24774.31 | 31-JUL-21:10 | 1.18 |
August | 0.371931E+11 | 0.84 | 25886.35 | 24-AUG-21:10 | 1.21 |
September | 0.348714E+11 | 0.82 | 26490.56 | 14-SEP-21:10 | 1.23 |
October | 0.347889E+11 | 0.81 | 24347.91 | 04-OCT-21:10 | 1.17 |
November | 0.328095E+11 | 0.80 | 19820.11 | 06-NOV-21:10 | 1.03 |
December | 0.330328E+11 | 0.79 | 18428.08 | 28-DEC-21:10 | 0.99 |
Annual Sum or Average | 0.410566E+12 | 0.81 | |||
Minimum of Months | 0.300603E+11 | 0.79 | 18290.21 | 0.99 | |
Maximum of Months | 0.371931E+11 | 0.84 | 26490.56 | 1.23 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371967E+09 | 0.43 | 835.35 | 01-JAN-09:02 | 0.58 |
February | 0.257446E+09 | 0.43 | 835.35 | 01-FEB-09:02 | 0.58 |
March | 0.206216E+09 | 0.43 | 835.35 | 01-MAR-16:01 | 0.58 |
April | 0.185054E+09 | 0.46 | 835.35 | 01-APR-15:01 | 0.58 |
May | 0.224717E+09 | 0.49 | 835.35 | 01-MAY-15:01 | 0.58 |
June | 0.234602E+09 | 0.50 | 835.35 | 01-JUN-08:62 | 0.58 |
July | 0.350982E+09 | 0.53 | 835.35 | 01-JUL-08:61 | 0.58 |
August | 0.337442E+09 | 0.52 | 835.35 | 01-AUG-08:62 | 0.58 |
September | 0.233884E+09 | 0.49 | 835.35 | 01-SEP-15:01 | 0.58 |
October | 0.171640E+09 | 0.45 | 835.35 | 01-OCT-08:62 | 0.58 |
November | 0.255674E+09 | 0.43 | 835.35 | 02-NOV-15:01 | 0.58 |
December | 0.352910E+09 | 0.44 | 835.35 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.318253E+10 | 0.47 | |||
Minimum of Months | 0.171640E+09 | 0.43 | 835.35 | 0.58 | |
Maximum of Months | 0.371967E+09 | 0.53 | 835.35 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.384187E+09 | 0.46 | 757.50 | 01-JAN-09:02 | 0.58 |
February | 0.278914E+09 | 0.43 | 757.50 | 01-FEB-09:02 | 0.58 |
March | 0.205385E+09 | 0.41 | 757.50 | 01-MAR-09:02 | 0.58 |
April | 0.148888E+09 | 0.41 | 757.50 | 01-APR-15:01 | 0.58 |
May | 0.139663E+09 | 0.40 | 757.50 | 01-MAY-15:01 | 0.58 |
June | 0.150283E+09 | 0.38 | 757.50 | 01-JUN-08:62 | 0.58 |
July | 0.226767E+09 | 0.39 | 757.50 | 01-JUL-08:61 | 0.58 |
August | 0.225142E+09 | 0.38 | 757.50 | 01-AUG-08:62 | 0.58 |
September | 0.118419E+09 | 0.36 | 757.50 | 01-SEP-08:52 | 0.58 |
October | 0.148090E+09 | 0.40 | 757.50 | 01-OCT-08:62 | 0.58 |
November | 0.264462E+09 | 0.42 | 757.50 | 01-NOV-08:62 | 0.58 |
December | 0.367353E+09 | 0.45 | 757.50 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.265755E+10 | 0.41 | |||
Minimum of Months | 0.118419E+09 | 0.36 | 757.50 | 0.58 | |
Maximum of Months | 0.384187E+09 | 0.46 | 757.50 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 89857435.42 | 0.06 | 1032.38 | 08-FEB-14:00 | 0.58 |
March | 0.361032E+09 | 0.16 | 1412.07 | 02-MAR-13:30 | 0.58 |
April | 0.672968E+09 | 0.33 | 1404.41 | 27-APR-13:00 | 0.58 |
May | 0.898894E+09 | 0.40 | 1356.92 | 04-MAY-13:15 | 0.58 |
June | 0.101187E+10 | 0.48 | 1058.20 | 28-JUN-13:15 | 0.58 |
July | 0.134484E+10 | 0.54 | 1305.15 | 31-JUL-13:20 | 0.58 |
August | 0.147937E+10 | 0.54 | 1596.96 | 24-AUG-13:00 | 0.58 |
September | 0.123790E+10 | 0.48 | 1684.75 | 14-SEP-13:30 | 0.58 |
October | 0.720928E+09 | 0.29 | 1868.40 | 04-OCT-12:40 | 0.58 |
November | 92250818.36 | 0.05 | 1303.99 | 04-NOV-13:25 | 0.58 |
December | 30457488.36 | 0.02 | 874.31 | 05-DEC-12:30 | 0.58 |
Annual Sum or Average | 0.794037E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147937E+10 | 0.54 | 1868.40 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112565E+10 | 0.41 | 3960.05 | 01-JAN-09:02 | 0.58 |
February | 0.869620E+09 | 0.41 | 3960.05 | 02-FEB-19:02 | 0.58 |
March | 0.649666E+09 | 0.41 | 3960.05 | 01-MAR-09:02 | 0.58 |
April | 0.790698E+09 | 0.39 | 3960.05 | 01-APR-08:62 | 0.58 |
May | 0.111673E+10 | 0.36 | 3960.05 | 01-MAY-08:62 | 0.58 |
June | 0.134191E+10 | 0.34 | 3960.05 | 01-JUN-08:62 | 0.58 |
July | 0.157729E+10 | 0.34 | 3960.05 | 01-JUL-08:61 | 0.58 |
August | 0.152945E+10 | 0.33 | 3960.05 | 01-AUG-08:62 | 0.58 |
September | 0.999887E+09 | 0.32 | 3960.05 | 01-SEP-08:52 | 0.58 |
October | 0.638163E+09 | 0.39 | 3960.05 | 01-OCT-08:62 | 0.58 |
November | 0.722846E+09 | 0.41 | 3960.05 | 01-NOV-18:03 | 0.58 |
December | 0.102879E+10 | 0.41 | 3960.05 | 01-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.123907E+11 | 0.38 | |||
Minimum of Months | 0.638163E+09 | 0.32 | 3960.05 | 0.58 | |
Maximum of Months | 0.157729E+10 | 0.41 | 3960.05 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344696E+09 | 0.43 | 750.98 | 01-JAN-09:02 | 0.58 |
February | 0.237599E+09 | 0.42 | 750.98 | 01-FEB-09:02 | 0.58 |
March | 0.185433E+09 | 0.43 | 750.98 | 01-MAR-09:02 | 0.58 |
April | 0.176096E+09 | 0.48 | 750.98 | 01-APR-08:62 | 0.58 |
May | 0.194506E+09 | 0.50 | 750.98 | 01-MAY-15:01 | 0.58 |
June | 0.240694E+09 | 0.53 | 750.98 | 01-JUN-08:62 | 0.58 |
July | 0.293894E+09 | 0.54 | 750.98 | 01-JUL-08:61 | 0.58 |
August | 0.322367E+09 | 0.54 | 750.98 | 01-AUG-08:62 | 0.58 |
September | 0.209321E+09 | 0.50 | 750.98 | 01-SEP-15:01 | 0.58 |
October | 0.162149E+09 | 0.46 | 750.98 | 01-OCT-08:62 | 0.58 |
November | 0.236474E+09 | 0.42 | 750.98 | 02-NOV-15:01 | 0.58 |
December | 0.328267E+09 | 0.44 | 750.98 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.293150E+10 | 0.47 | |||
Minimum of Months | 0.162149E+09 | 0.42 | 750.98 | 0.58 | |
Maximum of Months | 0.344696E+09 | 0.54 | 750.98 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.363318E+09 | 0.47 | 684.65 | 01-JAN-09:02 | 0.58 |
February | 0.257761E+09 | 0.42 | 684.65 | 01-FEB-09:02 | 0.58 |
March | 0.183227E+09 | 0.41 | 684.65 | 01-MAR-09:02 | 0.58 |
April | 0.137827E+09 | 0.41 | 684.65 | 01-APR-08:62 | 0.58 |
May | 0.136977E+09 | 0.41 | 684.65 | 01-MAY-15:01 | 0.58 |
June | 0.173151E+09 | 0.41 | 684.65 | 01-JUN-08:62 | 0.58 |
July | 0.201460E+09 | 0.40 | 684.65 | 01-JUL-08:61 | 0.58 |
August | 0.218714E+09 | 0.40 | 684.65 | 01-AUG-08:62 | 0.58 |
September | 0.119144E+09 | 0.38 | 684.65 | 01-SEP-08:52 | 0.58 |
October | 0.140316E+09 | 0.40 | 684.65 | 01-OCT-08:62 | 0.58 |
November | 0.244963E+09 | 0.42 | 684.65 | 04-NOV-15:01 | 0.58 |
December | 0.343034E+09 | 0.46 | 684.65 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.251989E+10 | 0.42 | |||
Minimum of Months | 0.119144E+09 | 0.38 | 684.65 | 0.58 | |
Maximum of Months | 0.363318E+09 | 0.47 | 684.65 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113875E+09 | 0.47 | 217.74 | 01-JAN-09:02 | 0.58 |
February | 80664392.04 | 0.44 | 217.74 | 01-FEB-09:02 | 0.58 |
March | 64124083.64 | 0.43 | 217.74 | 01-MAR-09:02 | 0.58 |
April | 55569814.00 | 0.46 | 217.74 | 01-APR-15:01 | 0.58 |
May | 63544852.34 | 0.49 | 217.74 | 01-MAY-15:01 | 0.58 |
June | 62419296.43 | 0.51 | 217.74 | 01-JUN-08:62 | 0.58 |
July | 91364958.11 | 0.53 | 217.74 | 01-JUL-08:61 | 0.58 |
August | 86771655.59 | 0.52 | 217.74 | 01-AUG-08:62 | 0.58 |
September | 61400954.91 | 0.49 | 217.74 | 01-SEP-15:01 | 0.58 |
October | 52487694.10 | 0.45 | 217.74 | 01-OCT-08:62 | 0.58 |
November | 79708948.68 | 0.44 | 217.74 | 01-NOV-08:62 | 0.58 |
December | 0.108363E+09 | 0.47 | 217.74 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.920295E+09 | 0.48 | |||
Minimum of Months | 52487694.10 | 0.43 | 217.74 | 0.58 | |
Maximum of Months | 0.113875E+09 | 0.53 | 217.74 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121336E+09 | 0.51 | 196.00 | 01-JAN-09:02 | 0.58 |
February | 86207523.20 | 0.46 | 196.00 | 01-FEB-09:02 | 0.58 |
March | 63192368.76 | 0.41 | 196.00 | 01-MAR-09:02 | 0.58 |
April | 45337354.37 | 0.41 | 196.00 | 01-APR-08:62 | 0.58 |
May | 40646989.64 | 0.41 | 196.00 | 01-MAY-15:01 | 0.58 |
June | 40846780.63 | 0.39 | 196.00 | 01-JUN-08:62 | 0.58 |
July | 61791534.44 | 0.40 | 196.00 | 01-JUL-08:61 | 0.58 |
August | 58932235.58 | 0.39 | 196.00 | 01-AUG-08:62 | 0.58 |
September | 31096076.90 | 0.37 | 196.00 | 01-SEP-08:52 | 0.58 |
October | 47016201.86 | 0.40 | 196.00 | 01-OCT-08:62 | 0.58 |
November | 81620715.03 | 0.45 | 196.00 | 01-NOV-08:62 | 0.58 |
December | 0.112134E+09 | 0.49 | 196.00 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.790158E+09 | 0.42 | |||
Minimum of Months | 31096076.90 | 0.37 | 196.00 | 0.58 | |
Maximum of Months | 0.121336E+09 | 0.51 | 196.00 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.420662E+09 | 0.44 | 1191.12 | 01-JAN-09:02 | 0.58 |
February | 0.317831E+09 | 0.46 | 1191.12 | 01-FEB-16:01 | 0.58 |
March | 0.283706E+09 | 0.47 | 1191.12 | 01-MAR-09:02 | 0.58 |
April | 0.285491E+09 | 0.49 | 1191.12 | 01-APR-15:01 | 0.58 |
May | 0.298938E+09 | 0.50 | 1191.12 | 01-MAY-15:01 | 0.58 |
June | 0.307546E+09 | 0.51 | 1191.12 | 01-JUN-08:62 | 0.58 |
July | 0.409856E+09 | 0.53 | 1191.12 | 01-JUL-08:61 | 0.58 |
August | 0.453211E+09 | 0.53 | 1191.12 | 01-AUG-08:62 | 0.58 |
September | 0.383706E+09 | 0.50 | 1191.12 | 01-SEP-15:01 | 0.58 |
October | 0.280372E+09 | 0.48 | 1191.12 | 01-OCT-08:62 | 0.58 |
November | 0.293357E+09 | 0.44 | 1191.12 | 02-NOV-15:01 | 0.58 |
December | 0.422481E+09 | 0.45 | 1191.12 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.415716E+10 | 0.48 | |||
Minimum of Months | 0.280372E+09 | 0.44 | 1191.12 | 0.58 | |
Maximum of Months | 0.453211E+09 | 0.53 | 1191.12 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.826572E+09 | 0.743915E+09 | 752.24 | 02-JAN-16:02 | 677.02 | 677.02 | 34.59 | 1.57 |
February | 0.716086E+09 | 0.644477E+09 | 762.88 | 22-FEB-09:03 | 686.59 | 686.59 | 35.82 | 1.65 |
March | 0.729343E+09 | 0.656409E+09 | 730.10 | 15-MAR-08:07 | 657.09 | 657.09 | 36.26 | 1.43 |
April | 0.641794E+09 | 0.577615E+09 | 695.45 | 06-APR-06:05 | 625.90 | 625.90 | 41.42 | 1.25 |
May | 0.547531E+09 | 0.492778E+09 | 686.96 | 18-MAY-09:05 | 618.26 | 618.26 | 40.04 | 1.22 |
June | 0.275098E+09 | 0.247588E+09 | 622.12 | 15-JUN-04:00 | 559.90 | 559.90 | 35.46 | 0.99 |
July | 0.102256E+09 | 92030591.97 | 370.22 | 12-JUL-08:04 | 333.20 | 333.20 | 26.84 | 0.46 |
August | 79224413.97 | 71301972.57 | 421.20 | 03-AUG-08:06 | 379.08 | 379.08 | 29.45 | 0.55 |
September | 0.294797E+09 | 0.265317E+09 | 646.23 | 27-SEP-08:07 | 581.60 | 581.60 | 33.91 | 1.07 |
October | 0.793417E+09 | 0.714075E+09 | 754.10 | 30-OCT-08:04 | 678.69 | 678.69 | 35.11 | 1.58 |
November | 0.777460E+09 | 0.699714E+09 | 760.95 | 17-NOV-09:04 | 684.86 | 684.86 | 34.58 | 1.63 |
December | 0.819726E+09 | 0.737753E+09 | 760.09 | 16-DEC-16:13 | 684.08 | 684.08 | 35.53 | 1.62 |
Annual Sum or Average | 0.660331E+10 | 0.594297E+10 | ||||||
Minimum of Months | 79224413.97 | 71301972.57 | 370.22 | 333.20 | 333.20 | 26.84 | 0.46 | |
Maximum of Months | 0.826572E+09 | 0.743915E+09 | 762.88 | 686.59 | 686.59 | 41.42 | 1.65 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 410345.41 | 369310.87 | 25.34 | 11-JAN-19:03 | 22.81 | 22.81 | 6.72 | 2.24 |
February | 3775802.30 | 3398222.07 | 286.32 | 27-FEB-16:01 | 257.69 | 257.69 | 6.72 | 7.52 |
March | 11914772.51 | 10723295.26 | 271.63 | 18-MAR-15:01 | 244.47 | 244.47 | 6.72 | 7.35 |
April | 58201391.69 | 52381252.52 | 732.80 | 26-APR-15:02 | 659.52 | 659.52 | 6.72 | 11.36 |
May | 96471438.38 | 86824294.54 | 653.75 | 04-MAY-15:02 | 588.38 | 588.38 | 6.72 | 10.82 |
June | 0.171867E+09 | 0.154680E+09 | 712.46 | 20-JUN-18:02 | 641.22 | 641.22 | 6.72 | 11.22 |
July | 0.276474E+09 | 0.248827E+09 | 866.60 | 31-JUL-18:03 | 779.94 | 779.94 | 6.72 | 12.19 |
August | 0.349757E+09 | 0.314782E+09 | 1006.47 | 10-AUG-18:03 | 905.83 | 905.83 | 6.72 | 12.98 |
September | 0.144655E+09 | 0.130190E+09 | 745.01 | 08-SEP-15:01 | 670.51 | 670.51 | 6.72 | 11.44 |
October | 33295618.37 | 29966056.53 | 384.25 | 04-OCT-15:03 | 345.82 | 345.82 | 6.72 | 8.58 |
November | 5977406.02 | 5379665.42 | 383.82 | 04-NOV-15:01 | 345.43 | 345.43 | 6.72 | 8.58 |
December | 830827.17 | 747744.45 | 34.92 | 02-DEC-09:02 | 31.43 | 31.43 | 6.72 | 2.67 |
Annual Sum or Average | 0.115363E+10 | 0.103827E+10 | ||||||
Minimum of Months | 410345.41 | 369310.87 | 25.34 | 22.81 | 22.81 | 6.72 | 2.24 | |
Maximum of Months | 0.349757E+09 | 0.314782E+09 | 1006.47 | 905.83 | 905.83 | 6.72 | 12.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101432E+10 | 0.912884E+09 | 2442.54 | 01-JAN-09:02 | 2198.29 | 2198.29 | 7.00 | 21.61 |
February | 0.219193E+10 | 0.197273E+10 | 2442.54 | 01-FEB-06:05 | 2198.29 | 2198.29 | 6.73 | 21.61 |
March | 0.391530E+10 | 0.352377E+10 | 2442.54 | 01-MAR-00:03 | 2198.29 | 2198.29 | 6.75 | 21.61 |
April | 0.531846E+10 | 0.478661E+10 | 2442.54 | 01-APR-06:05 | 2198.29 | 2198.29 | 6.73 | 21.61 |
May | 0.632485E+10 | 0.569236E+10 | 2442.54 | 01-MAY-00:05 | 2198.29 | 2198.29 | 6.81 | 21.61 |
June | 0.630323E+10 | 0.567291E+10 | 2442.54 | 01-JUN-00:05 | 2198.29 | 2198.29 | 7.11 | 21.61 |
July | 0.654211E+10 | 0.588790E+10 | 2442.54 | 01-JUL-00:10 | 2198.29 | 2198.29 | 7.30 | 21.61 |
August | 0.654211E+10 | 0.588790E+10 | 2442.54 | 01-AUG-00:05 | 2198.29 | 2198.29 | 7.81 | 21.61 |
September | 0.618819E+10 | 0.556937E+10 | 2442.54 | 01-SEP-00:05 | 2198.29 | 2198.29 | 7.44 | 21.61 |
October | 0.506327E+10 | 0.455695E+10 | 2442.54 | 01-OCT-00:10 | 2198.29 | 2198.29 | 6.88 | 21.61 |
November | 0.242140E+10 | 0.217926E+10 | 2442.54 | 01-NOV-05:03 | 2198.29 | 2198.29 | 6.76 | 21.61 |
December | 0.122892E+10 | 0.110603E+10 | 2442.54 | 01-DEC-12:50 | 2198.29 | 2198.29 | 6.73 | 21.61 |
Annual Sum or Average | 0.530541E+11 | 0.477487E+11 | ||||||
Minimum of Months | 0.101432E+10 | 0.912884E+09 | 2442.54 | 2198.29 | 2198.29 | 6.73 | 21.61 | |
Maximum of Months | 0.654211E+10 | 0.588790E+10 | 2442.54 | 2198.29 | 2198.29 | 7.81 | 21.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.67 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.58 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.75 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.54 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.34 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.17 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.67 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.69 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.67 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.72 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.20 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.30 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.58 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.69 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 42.74 | 60.00 | 37239.53 | 168443.16 | 02-JAN-16:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 44.34 | 60.00 | 38047.58 | 166408.03 | 22-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 46.51 | 60.00 | 38196.34 | 148581.37 | 03-MAR-19:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 38.53 | 60.00 | 37593.08 | 128631.30 | 11-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32.00 | 60.00 | 32328.33 | 118668.24 | 28-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.21 | 60.00 | 16886.95 | 102035.27 | 15-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.42 | 26.42 | 6093.80 | 64238.68 | 12-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.41 | 28.41 | 4694.38 | 69955.82 | 03-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 29.51 | 29.51 | 17864.97 | 116829.47 | 27-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.06 | 60.00 | 46022.63 | 164500.23 | 30-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 35.38 | 60.00 | 40900.47 | 173420.83 | 17-NOV-09:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 42.33 | 60.00 | 37934.49 | 172528.96 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 29426.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.06 | 26.42 | 4694.38 | 64238.68 | ||
Maximum of Months | 0.00 | 0.00 | 46.51 | 60.00 | 46022.63 | 173420.83 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 738.78 | 39112.57 | 11-JAN-19:03 | 7.13 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 4284.70 | 198002.96 | 27-FEB-16:03 | 8.89 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 10059.45 | 260919.92 | 18-MAR-15:01 | 9.58 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 29458.00 | 389997.99 | 27-APR-18:03 | 11.01 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47767.45 | 354141.62 | 04-MAY-15:03 | 10.61 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 73115.55 | 392875.24 | 28-JUN-18:03 | 11.04 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 108678.26 | 456805.70 | 31-JUL-18:03 | 11.75 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 129213.78 | 489160.77 | 10-AUG-18:03 | 12.11 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 66234.64 | 391215.10 | 14-SEP-15:03 | 11.02 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 21138.11 | 307831.24 | 04-OCT-15:03 | 10.10 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5321.16 | 297484.40 | 04-NOV-15:03 | 9.99 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1234.29 | 39792.72 | 02-DEC-09:02 | 7.14 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 41719.41 | 0.00 | ||||||
Minimum of Months | 738.78 | 39112.57 | 7.13 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 129213.78 | 489160.77 | 12.11 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.67 | 59.43 | 27483.34 | 55997.15 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.58 | 58.42 | 27668.03 | 56066.80 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.75 | 58.62 | 27391.68 | 55857.43 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.54 | 58.69 | 26665.72 | 54630.66 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.34 | 58.24 | 25727.97 | 52983.22 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.17 | 58.92 | 24820.31 | 50924.13 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.67 | 59.21 | 24154.12 | 49170.43 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.69 | 59.55 | 23979.27 | 48466.50 | 29-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.67 | 59.56 | 24273.55 | 49464.44 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.72 | 59.12 | 24986.25 | 51380.26 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.20 | 59.32 | 25930.12 | 53359.54 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.30 | 58.78 | 26840.02 | 54991.58 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 25815.99 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.58 | 58.24 | 23979.27 | 48466.50 | ||
Maximum of Months | 0.00 | 0.00 | 52.69 | 59.56 | 27668.03 | 56066.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.632735E+11 | 0.00 | 0.00 | 0.328667E+11 | 0.00 | 0.00 |
February | 0.684927E+11 | 0.00 | 0.175155E+10 | 0.300603E+11 | 0.00 | 0.00 |
March | 0.912350E+11 | 0.00 | 0.387079E+10 | 0.340393E+11 | 0.00 | 0.00 |
April | 0.935451E+11 | 0.00 | 0.281901E+11 | 0.335971E+11 | 0.00 | 0.00 |
May | 0.857247E+11 | 0.00 | 0.545502E+11 | 0.355078E+11 | 0.00 | 0.00 |
June | 0.437344E+11 | 0.00 | 0.977781E+11 | 0.350361E+11 | 0.00 | 0.00 |
July | 0.163384E+11 | 0.00 | 0.165331E+12 | 0.367629E+11 | 0.00 | 0.00 |
August | 0.125387E+11 | 0.00 | 0.208657E+12 | 0.371931E+11 | 0.00 | 0.00 |
September | 0.458945E+11 | 0.00 | 0.794603E+11 | 0.348714E+11 | 0.00 | 0.00 |
October | 0.118034E+12 | 0.00 | 0.147084E+11 | 0.347889E+11 | 0.00 | 0.00 |
November | 0.868921E+11 | 0.00 | 0.335422E+10 | 0.328095E+11 | 0.00 | 0.00 |
December | 0.684519E+11 | 0.00 | 0.00 | 0.330328E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.794155E+12 | 0.00 | 0.657652E+12 | 0.410566E+12 | 0.00 | 0.00 |
Minimum of Months | 0.125387E+11 | 0.00 | 0.00 | 0.300603E+11 | 0.00 | 0.00 |
Maximum of Months | 0.118034E+12 | 0.00 | 0.208657E+12 | 0.371931E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.114071E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 95243714.89 | 0.00 | 0.108438E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 13922.70 | 0.00 | 0.233614E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 4780.58 | 0.00 | 0.179828E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 8064.32 | 0.00 | 0.355652E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 23608.77 | 0.00 | 0.630854E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 24867.71 | 0.00 | 0.116662E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 28574.24 | 0.00 | 0.152467E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 20807.92 | 0.00 | 0.544442E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 4456.95 | 0.00 | 0.903569E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 218670.90 | 0.00 | 0.218215E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 21704288.62 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.231367E+09 | 0.00 | 0.454846E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 4456.95 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114071E+09 | 0.00 | 0.152467E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.328667E+11 | 0.00 | 0.632735E+11 | 0.462750E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300603E+11 | 0.175155E+10 | 0.684927E+11 | 0.338180E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340393E+11 | 0.387079E+10 | 0.912350E+11 | 0.227513E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335971E+11 | 0.281901E+11 | 0.935451E+11 | 0.109877E+12 | 0.282641E+09 | 0.00 | 0.00 | 0.00 |
May | 0.355078E+11 | 0.545502E+11 | 0.857247E+11 | 0.382221E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350361E+11 | 0.977781E+11 | 0.437344E+11 | 0.194990E+10 | 27266158.84 | 0.00 | 0.00 | 0.00 |
July | 0.367629E+11 | 0.165331E+12 | 0.163384E+11 | 0.174947E+10 | 0.302889E+10 | 0.00 | 0.00 | 0.00 |
August | 0.371931E+11 | 0.208657E+12 | 0.125387E+11 | 0.288804E+10 | 0.823142E+10 | 0.00 | 0.00 | 0.00 |
September | 0.348714E+11 | 0.794603E+11 | 0.458945E+11 | 0.211973E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347889E+11 | 0.147084E+11 | 0.118034E+12 | 0.404983E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328095E+11 | 0.335422E+10 | 0.868921E+11 | 0.238990E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330328E+11 | 0.00 | 0.684519E+11 | 0.412107E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410566E+12 | 0.657652E+12 | 0.794155E+12 | 0.187685E+13 | 0.115702E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300603E+11 | 0.00 | 0.125387E+11 | 0.174947E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371931E+11 | 0.208657E+12 | 0.118034E+12 | 0.462750E+12 | 0.823142E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.114071E+09 | 0.405388E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.108438E+09 | 95243714.89 | 0.325145E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.233614E+09 | 13922.70 | 0.272233E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.179828E+10 | 4780.58 | 0.188437E+11 | 72024625.29 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.355652E+10 | 8064.32 | 0.123700E+11 | 47215929.38 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.630854E+10 | 23608.77 | 0.456520E+10 | 74084838.04 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.116662E+11 | 24867.71 | 0.165107E+10 | 0.801135E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.152467E+11 | 28574.24 | 0.113228E+10 | 0.175156E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.544442E+10 | 20807.92 | 0.465003E+10 | 0.118521E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.903569E+09 | 4456.95 | 0.155138E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.218215E+09 | 218670.90 | 0.264051E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 21704288.62 | 0.376180E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.454846E+11 | 0.231367E+09 | 0.223026E+12 | 0.286454E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 4456.95 | 0.113228E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.152467E+11 | 0.114071E+09 | 0.405388E+11 | 0.175156E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.328667E+11 | 0.632735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300603E+11 | 0.684927E+11 | 0.175155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340393E+11 | 0.912350E+11 | 0.387079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335971E+11 | 0.935451E+11 | 0.281901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.355078E+11 | 0.857247E+11 | 0.545502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350361E+11 | 0.437344E+11 | 0.977781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.367629E+11 | 0.163384E+11 | 0.165331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.371931E+11 | 0.125387E+11 | 0.208657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348714E+11 | 0.458945E+11 | 0.794603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347889E+11 | 0.118034E+12 | 0.147084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328095E+11 | 0.868921E+11 | 0.335422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330328E+11 | 0.684519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410566E+12 | 0.794155E+12 | 0.657652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300603E+11 | 0.125387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371931E+11 | 0.118034E+12 | 0.208657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.114071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 95243714.89 | 0.108438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 13922.70 | 0.233614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 4780.58 | 0.179828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 8064.32 | 0.355652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 23608.77 | 0.630854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 24867.71 | 0.116662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 28574.24 | 0.152467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 20807.92 | 0.544442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 4456.95 | 0.903569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 218670.90 | 0.218215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 21704288.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.231367E+09 | 0.454846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 4456.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.114071E+09 | 0.152467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.390637E+11 | 0.00 | 0.00 | 5020155.69 | 0.00 | 0.00 | 0.867328E+10 | 0.00 | 0.99 |
February | 0.403578E+11 | 0.00 | 0.00 | 1761698.83 | 0.00 | 0.00 | 0.502113E+10 | 0.00 | 0.99 |
March | 0.517484E+11 | 0.00 | 0.00 | 219926.41 | 0.00 | 0.00 | 0.144864E+10 | 0.00 | 0.99 |
April | 0.509933E+11 | 0.00 | 0.00 | 0.00 | 8631853.69 | 0.00 | 0.00 | 0.00 | 0.99 |
May | 0.486101E+11 | 0.00 | 0.00 | 122359.24 | 0.00 | 0.00 | 0.176149E+10 | 0.00 | 0.99 |
June | 0.378820E+11 | 0.00 | 0.00 | 1284412.30 | 0.00 | 0.00 | 0.369361E+10 | 0.00 | 0.99 |
July | 0.289420E+11 | 297253.12 | 0.00 | 4555542.11 | 0.100083E+09 | 0.00 | 0.618212E+10 | 0.00 | 0.99 |
August | 0.179000E+11 | 7967631.35 | 0.00 | 13036397.33 | 0.332927E+09 | 0.00 | 0.134640E+11 | 0.00 | 1.00 |
September | 0.139041E+11 | 0.00 | 0.00 | 22345678.09 | 0.00 | 0.00 | 0.304484E+11 | 0.00 | 1.01 |
October | 0.161492E+11 | 0.00 | 0.00 | 30438546.62 | 0.00 | 0.00 | 0.419817E+11 | 0.00 | 1.02 |
November | 0.155628E+11 | 0.00 | 0.00 | 30527901.03 | 0.00 | 0.00 | 0.365464E+11 | 0.00 | 1.02 |
December | 0.251798E+11 | 0.00 | 0.00 | 15296481.72 | 0.00 | 0.00 | 0.242478E+11 | 0.00 | 1.00 |
Annual Sum or Average | 0.386293E+12 | 8264884.47 | 0.00 | 0.124609E+09 | 0.441642E+09 | 0.00 | 0.173469E+12 | 0.00 | 1.00 |
Minimum of Months | 0.139041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.517484E+11 | 7967631.35 | 0.00 | 30527901.03 | 0.332927E+09 | 0.00 | 0.419817E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556906E+10 | 0.00 | 0.00 | 20932.05 | 0.00 | 0.272552E+10 | 39488392.95 | 0.00 | 3.11 |
February | 0.661426E+10 | 0.00 | 0.00 | 233360.75 | 0.00 | 0.105979E+10 | 0.251922E+09 | 0.00 | 3.13 |
March | 0.881922E+10 | 0.00 | 0.00 | 467328.86 | 0.00 | 50949438.32 | 0.442675E+09 | 0.00 | 3.13 |
April | 0.864768E+10 | 1898431.67 | 0.00 | 423281.11 | 0.00 | 0.00 | 0.255087E+09 | 0.00 | 3.13 |
May | 0.856605E+10 | 0.00 | 0.00 | 473598.97 | 0.00 | 0.00 | 0.228456E+09 | 0.00 | 3.13 |
June | 0.713889E+10 | 0.00 | 0.00 | 212924.86 | 0.00 | 0.00 | 0.118763E+09 | 0.00 | 3.13 |
July | 0.591299E+10 | 14068201.17 | 0.00 | 671228.77 | 4111790.87 | 0.00 | 0.218736E+09 | 0.00 | 3.14 |
August | 0.517915E+10 | 62971360.67 | 0.00 | 1016308.78 | 5335534.90 | 0.00 | 0.283834E+09 | 0.00 | 3.19 |
September | 0.706036E+10 | 0.00 | 0.00 | 2255973.38 | 0.00 | 0.00 | 0.613487E+09 | 0.00 | 3.20 |
October | 0.931710E+10 | 0.00 | 0.00 | 882061.16 | 0.00 | 0.00 | 0.570721E+09 | 0.00 | 3.15 |
November | 0.811092E+10 | 0.00 | 0.00 | 159797.61 | 0.00 | 0.580949E+09 | 0.121358E+09 | 0.00 | 3.12 |
December | 0.592849E+10 | 0.00 | 0.00 | 76220.46 | 0.00 | 0.244974E+10 | 0.160846E+09 | 0.00 | 3.11 |
Annual Sum or Average | 0.868642E+11 | 78937993.51 | 0.00 | 6893016.75 | 9447325.77 | 0.686695E+10 | 0.330537E+10 | 0.00 | 3.14 |
Minimum of Months | 0.517915E+10 | 0.00 | 0.00 | 20932.05 | 0.00 | 0.00 | 39488392.95 | 0.00 | 3.11 |
Maximum of Months | 0.931710E+10 | 62971360.67 | 0.00 | 2255973.38 | 5335534.90 | 0.272552E+10 | 0.613487E+09 | 0.00 | 3.20 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.433316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
February | 0.409109E+10 | 0.00 | 0.00 | 4420.27 | 0.00 | 0.00 | 27750292.78 | 0.00 | 1.41 |
March | 0.471306E+10 | 0.00 | 0.00 | 26074.04 | 0.00 | 0.00 | 0.115204E+09 | 0.00 | 1.40 |
April | 0.420880E+10 | 0.00 | 0.00 | 228209.98 | 783444.48 | 0.00 | 0.423215E+09 | 0.00 | 1.41 |
May | 0.372036E+10 | 0.00 | 0.00 | 577208.55 | 0.00 | 0.00 | 0.858366E+09 | 0.00 | 1.41 |
June | 0.276784E+10 | 0.00 | 0.00 | 893809.70 | 0.00 | 0.00 | 0.101863E+10 | 0.00 | 1.42 |
July | 0.166720E+10 | 3430442.47 | 0.00 | 1958085.83 | 5689977.24 | 0.00 | 0.156686E+10 | 0.00 | 1.44 |
August | 0.145330E+10 | 11942571.39 | 0.00 | 2303747.41 | 19190361.10 | 0.00 | 0.143595E+10 | 0.00 | 1.45 |
September | 0.276863E+10 | 0.00 | 0.00 | 1141936.11 | 0.00 | 0.00 | 0.123093E+10 | 0.00 | 1.43 |
October | 0.466462E+10 | 0.00 | 0.00 | 229876.00 | 0.00 | 0.00 | 0.460875E+09 | 0.00 | 1.41 |
November | 0.456880E+10 | 0.00 | 0.00 | 2409.63 | 0.00 | 0.00 | 11877977.85 | 0.00 | 1.40 |
December | 0.443968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.433965E+11 | 15373013.86 | 0.00 | 7365777.52 | 25663782.82 | 0.00 | 0.714966E+10 | 0.00 | 1.42 |
Minimum of Months | 0.145330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Maximum of Months | 0.471306E+10 | 11942571.39 | 0.00 | 2303747.41 | 19190361.10 | 0.00 | 0.156686E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197782E+09 | 0.00 | 0.00 | 0.50 |
February | 0.301704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121958E+09 | 0.00 | 0.00 | 0.51 |
March | 0.367968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.352723E+10 | 0.00 | 0.00 | 0.00 | 597069.24 | 0.00 | 0.00 | 0.00 | 0.51 |
May | 0.348423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.287589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.237652E+10 | 5341.88 | 0.00 | 77654.52 | 6937981.52 | 0.00 | 53512917.98 | 0.00 | 0.51 |
August | 0.206575E+10 | 410971.80 | 0.00 | 238347.98 | 23173216.68 | 0.00 | 99049335.67 | 0.00 | 0.51 |
September | 0.301789E+10 | 0.00 | 0.00 | 621.43 | 0.00 | 0.00 | 5019338.42 | 0.00 | 0.51 |
October | 0.390362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.349097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.331948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64041864.21 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.378629E+11 | 416313.69 | 0.00 | 316623.92 | 30708267.44 | 0.383782E+09 | 0.157582E+09 | 0.00 | 0.51 |
Minimum of Months | 0.206575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.390362E+10 | 410971.80 | 0.00 | 238347.98 | 23173216.68 | 0.197782E+09 | 99049335.67 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559719E+09 | 0.00 | 0.00 | 0.51 |
February | 0.157436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274722E+09 | 0.00 | 0.00 | 0.52 |
March | 0.216695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 629253.60 | 0.00 | 0.00 | 0.51 |
April | 0.207777E+10 | 0.00 | 0.00 | 0.00 | 351713.58 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.205245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.169409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.143135E+10 | 0.00 | 0.00 | 0.00 | 4090080.25 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.127274E+10 | 53025.53 | 0.00 | 1848.88 | 13837084.19 | 0.00 | 1821524.87 | 0.00 | 0.52 |
September | 0.178069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.229949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.201787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38543719.87 | 0.00 | 0.00 | 0.51 |
December | 0.172301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270105E+09 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.214764E+11 | 53025.53 | 0.00 | 1848.88 | 18278878.01 | 0.114372E+10 | 1821524.87 | 0.00 | 0.52 |
Minimum of Months | 0.127274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.229949E+10 | 53025.53 | 0.00 | 1848.88 | 13837084.19 | 0.559719E+09 | 1821524.87 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254601E+09 | 0.00 | 0.00 | 90536943.25 | 0.00 | 0.00 | 0.716339E+11 | 0.00 | 23.13 |
February | 0.187372E+09 | 0.00 | 0.00 | 81336122.91 | 0.00 | 0.00 | 0.682797E+11 | 0.00 | 23.32 |
March | 0.203052E+09 | 0.00 | 0.00 | 91658286.41 | 0.00 | 0.00 | 0.805957E+11 | 0.00 | 23.32 |
April | 0.141852E+09 | 11150993.53 | 0.00 | 96286467.87 | 0.00 | 0.00 | 0.771652E+11 | 0.00 | 23.28 |
May | 0.125570E+09 | 0.00 | 0.00 | 0.108570E+09 | 0.00 | 0.00 | 0.762794E+11 | 0.00 | 23.34 |
June | 42748899.27 | 0.00 | 0.00 | 0.112390E+09 | 0.00 | 0.00 | 0.625458E+11 | 0.00 | 23.40 |
July | 55823279.94 | 0.138783E+09 | 0.00 | 0.121024E+09 | 1350488.80 | 0.00 | 0.524309E+11 | 0.00 | 23.30 |
August | 30076657.40 | 0.463439E+09 | 0.00 | 0.116862E+09 | 1164355.61 | 0.00 | 0.469140E+11 | 0.00 | 23.49 |
September | 81243207.28 | 0.00 | 0.00 | 0.107135E+09 | 0.00 | 0.00 | 0.658145E+11 | 0.00 | 23.38 |
October | 0.176241E+09 | 0.00 | 0.00 | 94570462.42 | 0.00 | 0.00 | 0.853704E+11 | 0.00 | 23.39 |
November | 0.192780E+09 | 0.00 | 0.00 | 87418388.83 | 0.00 | 0.00 | 0.758124E+11 | 0.00 | 23.24 |
December | 0.248195E+09 | 0.00 | 0.00 | 90421300.23 | 0.00 | 0.00 | 0.730697E+11 | 0.00 | 23.09 |
Annual Sum or Average | 0.173955E+10 | 0.613373E+09 | 0.00 | 0.119821E+10 | 2514844.41 | 0.00 | 0.835912E+12 | 0.00 | 23.31 |
Minimum of Months | 30076657.40 | 0.00 | 0.00 | 81336122.91 | 0.00 | 0.00 | 0.469140E+11 | 0.00 | 23.09 |
Maximum of Months | 0.254601E+09 | 0.463439E+09 | 0.00 | 0.121024E+09 | 1350488.80 | 0.00 | 0.853704E+11 | 0.00 | 23.49 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311799E+11 | 0.00 | 0.00 | 389794.49 | 0.00 | 0.00 | 0.201912E+10 | 0.00 | 4.41 |
February | 0.245704E+11 | 0.00 | 0.00 | 2494985.53 | 0.00 | 0.00 | 0.701202E+10 | 0.00 | 4.45 |
March | 0.236847E+11 | 0.00 | 0.00 | 5297451.39 | 0.00 | 0.00 | 0.134184E+11 | 0.00 | 4.44 |
April | 0.196536E+11 | 6973651.45 | 0.00 | 7265130.87 | 0.00 | 0.00 | 0.158080E+11 | 0.00 | 4.44 |
May | 0.166524E+11 | 0.00 | 0.00 | 9557161.19 | 0.00 | 0.00 | 0.183747E+11 | 0.00 | 4.44 |
June | 0.110061E+11 | 0.00 | 0.00 | 10566049.81 | 0.00 | 0.00 | 0.178959E+11 | 0.00 | 4.44 |
July | 0.759334E+10 | 62625358.05 | 0.00 | 16517640.32 | 8124954.50 | 0.00 | 0.168292E+11 | 0.00 | 4.45 |
August | 0.649507E+10 | 0.245890E+09 | 0.00 | 19579907.84 | 11238419.76 | 0.00 | 0.153036E+11 | 0.00 | 4.52 |
September | 0.113552E+11 | 0.00 | 0.00 | 20858846.59 | 0.00 | 0.00 | 0.191887E+11 | 0.00 | 4.53 |
October | 0.203103E+11 | 0.00 | 0.00 | 9866233.97 | 0.00 | 0.00 | 0.190615E+11 | 0.00 | 4.48 |
November | 0.275786E+11 | 0.00 | 0.00 | 2073348.80 | 0.00 | 0.00 | 0.753091E+10 | 0.00 | 4.42 |
December | 0.309390E+11 | 0.00 | 0.00 | 958032.52 | 0.00 | 0.00 | 0.308230E+10 | 0.00 | 4.41 |
Annual Sum or Average | 0.231019E+12 | 0.315489E+09 | 0.00 | 0.105425E+09 | 19363374.26 | 0.00 | 0.155524E+12 | 0.00 | 4.45 |
Minimum of Months | 0.649507E+10 | 0.00 | 0.00 | 389794.49 | 0.00 | 0.00 | 0.201912E+10 | 0.00 | 4.41 |
Maximum of Months | 0.311799E+11 | 0.245890E+09 | 0.00 | 20858846.59 | 11238419.76 | 0.00 | 0.191887E+11 | 0.00 | 4.53 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.937935E+11 | 0.00 | 0.00 | 363903.87 | 0.00 | 0.00 | 0.283145E+10 | 0.00 | 1.86 |
February | 0.824396E+11 | 0.00 | 0.00 | 2978957.58 | 0.00 | 0.00 | 0.940365E+10 | 0.00 | 1.87 |
March | 0.822841E+11 | 0.00 | 0.00 | 8412447.85 | 0.00 | 0.00 | 0.253808E+11 | 0.00 | 1.86 |
April | 0.638965E+11 | 11460137.27 | 0.00 | 18299518.49 | 6009916.86 | 0.00 | 0.394269E+11 | 0.00 | 1.87 |
May | 0.495445E+11 | 0.00 | 0.00 | 33060651.80 | 0.00 | 0.00 | 0.526818E+11 | 0.00 | 1.87 |
June | 0.321987E+11 | 0.00 | 0.00 | 47153454.78 | 0.00 | 0.00 | 0.524697E+11 | 0.00 | 1.88 |
July | 0.203850E+11 | 0.125292E+09 | 0.00 | 67200488.88 | 77875154.28 | 0.00 | 0.519984E+11 | 0.00 | 1.91 |
August | 0.172163E+11 | 0.527930E+09 | 0.00 | 74713869.85 | 0.163291E+09 | 0.00 | 0.478519E+11 | 0.00 | 1.93 |
September | 0.325194E+11 | 0.00 | 0.00 | 52488200.18 | 0.00 | 0.00 | 0.569945E+11 | 0.00 | 1.90 |
October | 0.666804E+11 | 0.00 | 0.00 | 22270381.24 | 0.00 | 0.00 | 0.477697E+11 | 0.00 | 1.88 |
November | 0.858660E+11 | 0.00 | 0.00 | 4099904.26 | 0.00 | 0.00 | 0.162747E+11 | 0.00 | 1.86 |
December | 0.947095E+11 | 0.00 | 0.00 | 869658.33 | 0.00 | 0.00 | 0.429028E+10 | 0.00 | 1.86 |
Annual Sum or Average | 0.721533E+12 | 0.664682E+09 | 0.00 | 0.331911E+09 | 0.247176E+09 | 0.00 | 0.407374E+12 | 0.00 | 1.88 |
Minimum of Months | 0.172163E+11 | 0.00 | 0.00 | 363903.87 | 0.00 | 0.00 | 0.283145E+10 | 0.00 | 1.86 |
Maximum of Months | 0.947095E+11 | 0.527930E+09 | 0.00 | 74713869.85 | 0.163291E+09 | 0.00 | 0.569945E+11 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56053088.46 | 0.00 | 0.00 | 86083.17 | 0.00 | 0.132832E+10 | 5834679.26 | 0.00 | 0.35 |
February | 58214807.02 | 0.00 | 0.00 | 810991.83 | 0.00 | 0.105048E+10 | 0.151431E+09 | 0.00 | 0.36 |
March | 70890323.04 | 0.00 | 0.00 | 2679612.04 | 0.00 | 0.947113E+09 | 0.383011E+09 | 0.00 | 0.35 |
April | 57624231.83 | 898255.74 | 0.00 | 6283835.48 | 0.00 | 0.483743E+09 | 0.748421E+09 | 0.00 | 0.35 |
May | 35630748.53 | 1514837.51 | 0.00 | 12426465.62 | 0.00 | 0.164138E+09 | 0.104014E+10 | 0.00 | 0.36 |
June | 18585384.16 | 815311.90 | 0.00 | 13546468.64 | 0.00 | 26511233.44 | 0.993530E+09 | 0.00 | 0.36 |
July | 2953279.93 | 16302227.17 | 0.00 | 15684009.92 | 0.00 | 1921212.51 | 0.831912E+09 | 0.00 | 0.35 |
August | 6345261.10 | 39103062.67 | 9832.34 | 11819040.41 | 0.00 | 1946512.84 | 0.628233E+09 | 2809.18 | 0.36 |
September | 31251974.83 | 4140019.79 | 0.00 | 11832972.91 | 0.00 | 57390812.79 | 0.923245E+09 | 0.00 | 0.36 |
October | 55065819.88 | 0.00 | 0.00 | 4428758.13 | 0.00 | 0.625720E+09 | 0.687442E+09 | 0.00 | 0.36 |
November | 59667060.47 | 0.00 | 0.00 | 620198.49 | 0.00 | 0.115693E+10 | 0.123737E+09 | 0.00 | 0.35 |
December | 51079576.82 | 0.00 | 0.00 | 165353.72 | 0.00 | 0.130883E+10 | 30224270.75 | 0.00 | 0.35 |
Annual Sum or Average | 0.503362E+09 | 62773714.79 | 9832.34 | 80383790.34 | 0.00 | 0.715305E+10 | 0.654716E+10 | 2809.18 | 0.35 |
Minimum of Months | 2953279.93 | 0.00 | 0.00 | 86083.17 | 0.00 | 1921212.51 | 5834679.26 | 0.00 | 0.35 |
Maximum of Months | 70890323.04 | 39103062.67 | 9832.34 | 15684009.92 | 0.00 | 0.132832E+10 | 0.104014E+10 | 2809.18 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46902938.75 | 0.00 | 0.00 | 15000.26 | 0.00 | 0.134127E+10 | 1945968.21 | 0.00 | 0.35 |
February | 59511770.95 | 0.00 | 0.00 | 267273.44 | 0.00 | 0.113298E+10 | 68030375.10 | 0.00 | 0.36 |
March | 91594345.23 | 0.00 | 0.00 | 1220998.60 | 0.00 | 0.108534E+10 | 0.225378E+09 | 0.00 | 0.35 |
April | 0.121156E+09 | 893553.63 | 0.00 | 3960169.07 | 4596.87 | 0.589682E+09 | 0.581123E+09 | 0.00 | 0.36 |
May | 0.180247E+09 | 1220266.37 | 5365.33 | 8805986.12 | 288805.27 | 0.179268E+09 | 0.883865E+09 | 223.05 | 0.36 |
June | 0.215772E+09 | 720562.72 | 0.00 | 9958183.94 | 94653.65 | 29589464.15 | 0.796730E+09 | 0.00 | 0.36 |
July | 0.201455E+09 | 13890285.52 | 1700.19 | 11756766.70 | 2407161.52 | 1956948.06 | 0.637202E+09 | 1169.89 | 0.36 |
August | 0.176536E+09 | 36471871.40 | 11105.89 | 7712628.13 | 2620690.07 | 1878852.95 | 0.462140E+09 | 7453.87 | 0.36 |
September | 0.201547E+09 | 3078594.70 | 0.00 | 7007093.14 | 1060940.03 | 67020358.69 | 0.748027E+09 | 0.00 | 0.36 |
October | 0.118735E+09 | 0.00 | 0.00 | 2047880.33 | 0.00 | 0.789606E+09 | 0.462106E+09 | 0.00 | 0.36 |
November | 65744251.02 | 0.00 | 0.00 | 200211.56 | 0.00 | 0.120703E+10 | 67826044.28 | 0.00 | 0.35 |
December | 43995633.09 | 0.00 | 0.00 | 19304.17 | 0.00 | 0.134414E+10 | 1981847.42 | 0.00 | 0.35 |
Annual Sum or Average | 0.152320E+10 | 56275134.34 | 18171.41 | 52971495.47 | 6476847.41 | 0.776976E+10 | 0.493635E+10 | 8846.81 | 0.36 |
Minimum of Months | 43995633.09 | 0.00 | 0.00 | 15000.26 | 0.00 | 1878852.95 | 1945968.21 | 0.00 | 0.35 |
Maximum of Months | 0.215772E+09 | 36471871.40 | 11105.89 | 11756766.70 | 2620690.07 | 0.134414E+10 | 0.883865E+09 | 7453.87 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.702029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.721572E+09 | 0.00 | 0.00 | 531955.64 | 0.00 | 0.00 | 0.261686E+09 | 0.00 | 0.02 |
March | 0.633714E+09 | 0.00 | 0.00 | 1758136.64 | 0.00 | 0.00 | 0.769988E+09 | 0.00 | 0.02 |
April | 0.353249E+09 | 5135618.99 | 0.00 | 2234171.40 | 0.00 | 0.00 | 0.913844E+09 | 0.00 | 0.02 |
May | 0.236439E+09 | 839107.24 | 0.00 | 2812378.62 | 0.00 | 0.00 | 0.939227E+09 | 0.00 | 0.02 |
June | 61709655.47 | 0.00 | 0.00 | 2845945.66 | 0.00 | 0.00 | 0.953322E+09 | 0.00 | 0.02 |
July | 0.00 | 33053267.63 | 0.00 | 3030858.66 | 0.00 | 0.00 | 0.493464E+09 | 0.00 | 0.02 |
August | 0.00 | 95206243.41 | 0.00 | 2037442.35 | 0.00 | 0.00 | 0.387596E+09 | 0.00 | 0.02 |
September | 0.223120E+09 | 34709520.45 | 0.00 | 2945718.45 | 0.00 | 0.00 | 0.616084E+09 | 0.00 | 0.02 |
October | 0.610874E+09 | 0.00 | 0.00 | 2622568.17 | 0.00 | 0.00 | 0.767665E+09 | 0.00 | 0.02 |
November | 0.946175E+09 | 0.00 | 0.00 | 397166.13 | 0.00 | 0.00 | 0.135524E+09 | 0.00 | 0.02 |
December | 0.793896E+09 | 0.00 | 0.00 | 133315.13 | 0.00 | 0.00 | 94734559.97 | 0.00 | 0.02 |
Annual Sum or Average | 0.528278E+10 | 0.168944E+09 | 0.00 | 21349656.87 | 0.00 | 0.00 | 0.633313E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.946175E+09 | 95206243.41 | 0.00 | 3030858.66 | 0.00 | 0.00 | 0.953322E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.857061E+09 | 0.00 | 0.00 | 7915696.48 | 0.00 | 0.993496E+10 | 0.805633E+10 | 0.00 | 0.40 |
February | 0.901405E+09 | 0.00 | 0.00 | 14955874.21 | 0.00 | 0.683634E+10 | 0.934922E+10 | 0.00 | 0.40 |
March | 0.124242E+10 | 0.00 | 0.00 | 35895449.19 | 0.00 | 0.858832E+09 | 0.169009E+11 | 0.00 | 0.40 |
April | 0.164441E+10 | 11000468.93 | 0.00 | 69526612.29 | 1182403.82 | 98835983.80 | 0.157656E+11 | 0.00 | 0.40 |
May | 0.258448E+10 | 12111968.18 | 80227.07 | 0.114855E+09 | 8342498.26 | 43340351.29 | 0.142425E+11 | 10761.02 | 0.40 |
June | 0.311149E+10 | 9774001.08 | 0.00 | 0.136638E+09 | 1283919.94 | 23227159.07 | 0.109991E+11 | 0.00 | 0.40 |
July | 0.300534E+10 | 0.166408E+09 | 113299.89 | 0.143078E+09 | 54574223.26 | 8947635.16 | 0.840452E+10 | 8613.39 | 0.40 |
August | 0.245419E+10 | 0.425817E+09 | 785095.37 | 99034452.92 | 0.103869E+09 | 9948356.77 | 0.623019E+10 | 47505.33 | 0.40 |
September | 0.277717E+10 | 23473930.27 | 0.00 | 94214265.21 | 32676375.04 | 46778112.83 | 0.109664E+11 | 0.00 | 0.40 |
October | 0.161057E+10 | 0.00 | 0.00 | 51720937.50 | 0.00 | 0.223595E+09 | 0.167312E+11 | 0.00 | 0.40 |
November | 0.959461E+09 | 0.00 | 0.00 | 23365043.83 | 0.00 | 0.426948E+10 | 0.129349E+11 | 0.00 | 0.40 |
December | 0.879357E+09 | 0.00 | 0.00 | 8158490.89 | 0.00 | 0.951086E+10 | 0.845804E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.220274E+11 | 0.648585E+09 | 978622.33 | 0.799358E+09 | 0.201929E+09 | 0.318652E+11 | 0.139039E+12 | 66879.74 | 0.40 |
Minimum of Months | 0.857061E+09 | 0.00 | 0.00 | 7915696.48 | 0.00 | 8947635.16 | 0.623019E+10 | 0.00 | 0.40 |
Maximum of Months | 0.311149E+10 | 0.425817E+09 | 785095.37 | 0.143078E+09 | 0.103869E+09 | 0.993496E+10 | 0.169009E+11 | 47505.33 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56712650.99 | 0.00 | 0.00 | 38486.30 | 0.00 | 0.132078E+10 | 12766094.28 | 0.00 | 0.35 |
February | 58876561.19 | 0.00 | 0.00 | 655477.79 | 0.00 | 0.104951E+10 | 0.151897E+09 | 0.00 | 0.36 |
March | 63582614.35 | 0.00 | 0.00 | 2431533.26 | 0.00 | 0.918524E+09 | 0.419156E+09 | 0.00 | 0.35 |
April | 39050667.91 | 898255.74 | 0.00 | 6627098.52 | 0.00 | 0.459022E+09 | 0.791372E+09 | 0.00 | 0.35 |
May | 28164387.43 | 1509248.47 | 5031.10 | 10456413.49 | 0.00 | 0.204144E+09 | 0.100957E+10 | 557.94 | 0.36 |
June | 15162723.64 | 814927.68 | 0.00 | 14300970.83 | 0.00 | 34504055.22 | 0.988206E+09 | 384.21 | 0.36 |
July | 2839061.80 | 16283234.52 | 18781.51 | 14922086.49 | 0.00 | 2154516.10 | 0.832555E+09 | 211.14 | 0.35 |
August | 5711744.69 | 39103062.67 | 10523.71 | 12876290.64 | 0.00 | 1598440.17 | 0.628157E+09 | 2117.81 | 0.36 |
September | 27608665.35 | 4140019.79 | 0.00 | 10791662.19 | 0.00 | 61476289.29 | 0.923844E+09 | 0.00 | 0.36 |
October | 45932065.82 | 0.00 | 0.00 | 4279980.59 | 0.00 | 0.633563E+09 | 0.688881E+09 | 0.00 | 0.36 |
November | 59708414.80 | 0.00 | 0.00 | 581279.52 | 0.00 | 0.113566E+10 | 0.145004E+09 | 0.00 | 0.35 |
December | 50759006.22 | 0.00 | 0.00 | 166967.12 | 0.00 | 0.129902E+10 | 40354431.88 | 0.00 | 0.35 |
Annual Sum or Average | 0.454109E+09 | 62748748.88 | 34336.32 | 78128246.74 | 0.00 | 0.711996E+10 | 0.663176E+10 | 3271.11 | 0.35 |
Minimum of Months | 2839061.80 | 0.00 | 0.00 | 38486.30 | 0.00 | 1598440.17 | 12766094.28 | 0.00 | 0.35 |
Maximum of Months | 63582614.35 | 39103062.67 | 18781.51 | 14922086.49 | 0.00 | 0.132078E+10 | 0.100957E+10 | 2117.81 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37195767.26 | 0.00 | 0.00 | 16123.84 | 0.00 | 0.135026E+10 | 2660993.19 | 0.00 | 0.35 |
February | 61262627.94 | 0.00 | 0.00 | 127214.54 | 0.00 | 0.113256E+10 | 66842582.60 | 0.00 | 0.36 |
March | 91662079.22 | 0.00 | 0.00 | 822750.79 | 0.00 | 0.105738E+10 | 0.253669E+09 | 0.00 | 0.35 |
April | 0.119063E+09 | 893553.63 | 0.00 | 4440912.99 | 4596.87 | 0.548494E+09 | 0.623921E+09 | 0.00 | 0.36 |
May | 0.170836E+09 | 1220266.37 | 4381.63 | 7532886.02 | 288805.27 | 0.234517E+09 | 0.839300E+09 | 1206.75 | 0.36 |
June | 0.197959E+09 | 720562.72 | 0.00 | 11205445.86 | 94653.65 | 36948450.02 | 0.805937E+09 | 0.00 | 0.36 |
July | 0.198588E+09 | 13751749.83 | 8137.67 | 11241375.24 | 2539390.66 | 2159377.87 | 0.640382E+09 | 1038.98 | 0.36 |
August | 0.169132E+09 | 36631101.77 | 0.00 | 8371416.34 | 2480019.45 | 1473171.44 | 0.469292E+09 | 0.00 | 0.36 |
September | 0.196393E+09 | 3120143.33 | 5302.46 | 6641604.91 | 1011353.25 | 86343565.61 | 0.734223E+09 | 2735.69 | 0.36 |
October | 0.118493E+09 | 0.00 | 0.00 | 1973938.52 | 0.00 | 0.787477E+09 | 0.464551E+09 | 0.00 | 0.36 |
November | 66406088.91 | 0.00 | 0.00 | 176103.80 | 0.00 | 0.119374E+10 | 80483549.40 | 0.00 | 0.35 |
December | 43571495.07 | 0.00 | 0.00 | 22843.70 | 0.00 | 0.133834E+10 | 8201312.49 | 0.00 | 0.35 |
Annual Sum or Average | 0.147056E+10 | 56337377.66 | 17821.76 | 52572616.55 | 6418819.13 | 0.776969E+10 | 0.498946E+10 | 4981.42 | 0.36 |
Minimum of Months | 37195767.26 | 0.00 | 0.00 | 16123.84 | 0.00 | 1473171.44 | 2660993.19 | 0.00 | 0.35 |
Maximum of Months | 0.198588E+09 | 36631101.77 | 8137.67 | 11241375.24 | 2539390.66 | 0.135026E+10 | 0.839300E+09 | 2735.69 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952233E+09 | 0.00 | 0.00 | 0.63 |
February | 0.285532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202256E+09 | 0.00 | 0.00 | 0.64 |
March | 0.337084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.323119E+11 | 0.00 | 0.00 | 0.00 | 5469567.22 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.319180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 0.263451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.222592E+11 | 0.00 | 0.00 | 0.00 | 63605644.62 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.198209E+11 | 0.00 | 0.00 | 0.00 | 0.216008E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.276919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.357599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
November | 0.317622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217527E+09 | 0.00 | 0.00 | 0.63 |
December | 0.294427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155271E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.348873E+12 | 0.00 | 0.00 | 0.00 | 0.285083E+09 | 0.292473E+10 | 0.00 | 0.00 | 0.64 |
Minimum of Months | 0.198209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.357599E+11 | 0.00 | 0.00 | 0.00 | 0.216008E+09 | 0.155271E+10 | 0.00 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9507170.66 | 0.00 | 0.00 | 15004.93 | 0.00 | 0.337176E+09 | 874575.59 | 0.00 | 0.35 |
February | 12371522.84 | 0.00 | 0.00 | 189146.64 | 0.00 | 0.280843E+09 | 21831839.88 | 0.00 | 0.36 |
March | 17353896.83 | 0.00 | 0.00 | 656963.07 | 0.00 | 0.262466E+09 | 70447014.62 | 0.00 | 0.35 |
April | 14044474.26 | 224563.94 | 0.00 | 1538021.20 | 0.00 | 0.158138E+09 | 0.150297E+09 | 0.00 | 0.35 |
May | 7034980.68 | 378709.38 | 0.00 | 3106774.36 | 0.00 | 83951779.32 | 0.218990E+09 | 0.00 | 0.36 |
June | 4694492.52 | 203827.97 | 0.00 | 3336472.46 | 0.00 | 22747896.45 | 0.232264E+09 | 0.00 | 0.36 |
July | 909425.34 | 4075556.79 | 0.00 | 3831847.49 | 0.00 | 511999.33 | 0.207864E+09 | 0.00 | 0.35 |
August | 1709424.61 | 9775765.67 | 2540.21 | 2740345.23 | 0.00 | 1190368.54 | 0.156446E+09 | 620.17 | 0.36 |
September | 7410403.75 | 1035004.95 | 0.00 | 2803868.45 | 0.00 | 38435323.73 | 0.207281E+09 | 0.00 | 0.36 |
October | 14043391.44 | 0.00 | 0.00 | 998925.50 | 0.00 | 0.205715E+09 | 0.122406E+09 | 0.00 | 0.36 |
November | 13204240.61 | 0.00 | 0.00 | 139531.32 | 0.00 | 0.302464E+09 | 19431609.21 | 0.00 | 0.35 |
December | 9133175.14 | 0.00 | 0.00 | 38547.88 | 0.00 | 0.334878E+09 | 3526319.53 | 0.00 | 0.35 |
Annual Sum or Average | 0.111417E+09 | 15693428.70 | 2540.21 | 19395448.52 | 0.00 | 0.202852E+10 | 0.141166E+10 | 620.17 | 0.36 |
Minimum of Months | 909425.34 | 0.00 | 0.00 | 15004.93 | 0.00 | 511999.33 | 874575.59 | 0.00 | 0.35 |
Maximum of Months | 17353896.83 | 9775765.67 | 2540.21 | 3831847.49 | 0.00 | 0.337176E+09 | 0.232264E+09 | 620.17 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2498820.54 | 0.00 | 0.00 | 1520.51 | 0.00 | 0.344865E+09 | 166568.85 | 0.00 | 0.35 |
February | 11928373.00 | 0.00 | 0.00 | 49865.61 | 0.00 | 0.294607E+09 | 8613837.06 | 0.00 | 0.36 |
March | 22298234.24 | 0.00 | 0.00 | 274685.65 | 0.00 | 0.292010E+09 | 36299512.92 | 0.00 | 0.35 |
April | 30039154.49 | 223388.41 | 0.00 | 960127.18 | 1149.22 | 0.181453E+09 | 0.111528E+09 | 0.00 | 0.36 |
May | 43873079.84 | 306463.69 | 0.00 | 2256534.94 | 72201.32 | 83456445.01 | 0.183460E+09 | 0.00 | 0.36 |
June | 51339399.88 | 180140.68 | 0.00 | 2529439.75 | 23663.41 | 20295841.59 | 0.188848E+09 | 0.00 | 0.36 |
July | 49267412.51 | 3472571.38 | 414.19 | 3040329.89 | 601790.38 | 473497.22 | 0.160311E+09 | 303.33 | 0.36 |
August | 43754746.65 | 9119090.83 | 2778.93 | 1797460.41 | 654049.53 | 493456.12 | 0.116021E+09 | 1861.01 | 0.36 |
September | 49944486.19 | 793304.43 | 0.00 | 1633959.09 | 241579.25 | 42692627.87 | 0.161629E+09 | 0.00 | 0.36 |
October | 29990669.16 | 0.00 | 0.00 | 413222.62 | 0.00 | 0.241111E+09 | 71609341.58 | 0.00 | 0.36 |
November | 13547787.75 | 0.00 | 0.00 | 34567.11 | 0.00 | 0.315198E+09 | 6420107.22 | 0.00 | 0.35 |
December | 6683428.21 | 0.00 | 0.00 | 3532.48 | 0.00 | 0.340595E+09 | 253174.08 | 0.00 | 0.35 |
Annual Sum or Average | 0.355166E+09 | 14094959.42 | 3193.13 | 12995245.25 | 1594433.11 | 0.215725E+10 | 0.104516E+10 | 2164.33 | 0.36 |
Minimum of Months | 2498820.54 | 0.00 | 0.00 | 1520.51 | 0.00 | 473497.22 | 166568.85 | 0.00 | 0.35 |
Maximum of Months | 51339399.88 | 9119090.83 | 2778.93 | 3040329.89 | 654049.53 | 0.344865E+09 | 0.188848E+09 | 1861.01 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84956625.34 | 0.00 | 0.00 | 1141319.43 | 0.00 | 0.193789E+10 | 0.208992E+09 | 0.00 | 0.40 |
February | 60776507.05 | 0.00 | 0.00 | 3871902.27 | 0.00 | 0.132491E+10 | 0.635667E+09 | 0.00 | 0.40 |
March | 58574841.91 | 0.00 | 0.00 | 7443444.73 | 0.00 | 0.955847E+09 | 0.123264E+10 | 0.00 | 0.40 |
April | 36213476.66 | 1442708.61 | 0.00 | 11601738.77 | 0.00 | 0.455477E+09 | 0.157836E+10 | 0.00 | 0.40 |
May | 24150312.43 | 2433014.35 | 0.00 | 16512030.68 | 0.00 | 0.164982E+09 | 0.180576E+10 | 0.00 | 0.40 |
June | 24400818.35 | 1309490.65 | 0.00 | 18371323.63 | 0.00 | 18483822.52 | 0.162866E+10 | 0.00 | 0.40 |
July | 5791776.78 | 26183371.18 | 0.00 | 19470606.59 | 0.00 | 4002101.98 | 0.133991E+10 | 0.00 | 0.40 |
August | 10861724.36 | 62820690.93 | 0.00 | 16183315.68 | 0.00 | 3375650.18 | 0.101090E+10 | 3915.25 | 0.40 |
September | 40962976.36 | 6649378.26 | 0.00 | 18648974.46 | 0.00 | 52329806.34 | 0.153228E+10 | 0.00 | 0.40 |
October | 49486822.25 | 0.00 | 0.00 | 11051284.67 | 0.00 | 0.501458E+09 | 0.164266E+10 | 0.00 | 0.40 |
November | 73958269.84 | 0.00 | 0.00 | 2814650.86 | 0.00 | 0.139108E+10 | 0.685889E+09 | 0.00 | 0.40 |
December | 67553419.97 | 0.00 | 0.00 | 2024596.96 | 0.00 | 0.179793E+10 | 0.365492E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.537688E+09 | 0.100839E+09 | 0.00 | 0.129135E+09 | 0.00 | 0.860776E+10 | 0.136672E+11 | 3915.25 | 0.40 |
Minimum of Months | 5791776.78 | 0.00 | 0.00 | 1141319.43 | 0.00 | 3375650.18 | 0.208992E+09 | 0.00 | 0.40 |
Maximum of Months | 84956625.34 | 62820690.93 | 0.00 | 19470606.59 | 0.00 | 0.193789E+10 | 0.180576E+10 | 3915.25 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.403133E+10 | 0.00 | 0.00 | 45778727.95 | 0.00 | 0.00 | 0.398779E+11 | 0.00 | 4.34 |
February | 0.253578E+10 | 0.00 | 0.00 | 45168138.48 | 0.00 | 0.00 | 0.398273E+11 | 0.00 | 4.43 |
March | 0.165671E+10 | 0.00 | 0.00 | 59131159.05 | 0.00 | 0.00 | 0.494203E+11 | 0.00 | 4.55 |
April | 0.620723E+09 | 7679509.56 | 0.00 | 69054744.28 | 0.00 | 0.00 | 0.504751E+11 | 0.00 | 4.71 |
May | 0.111132E+09 | 0.00 | 0.00 | 87710676.07 | 0.00 | 0.00 | 0.528880E+11 | 0.00 | 4.90 |
June | 20211483.29 | 0.00 | 0.00 | 93045531.26 | 0.00 | 0.00 | 0.455723E+11 | 0.00 | 5.06 |
July | 3742984.69 | 98886718.69 | 0.00 | 0.103380E+09 | 0.00 | 0.00 | 0.397326E+11 | 0.00 | 5.17 |
August | 8759256.18 | 0.322413E+09 | 0.00 | 94150532.39 | 116097.31 | 0.00 | 0.354847E+11 | 0.00 | 5.18 |
September | 0.139042E+09 | 0.00 | 0.00 | 84957031.00 | 0.00 | 0.00 | 0.462512E+11 | 0.00 | 4.93 |
October | 0.843895E+09 | 0.00 | 0.00 | 64851628.04 | 0.00 | 0.00 | 0.551866E+11 | 0.00 | 4.66 |
November | 0.198130E+10 | 0.00 | 0.00 | 51736425.73 | 0.00 | 0.00 | 0.460831E+11 | 0.00 | 4.48 |
December | 0.372758E+10 | 0.00 | 0.00 | 47256781.36 | 0.00 | 0.00 | 0.412191E+11 | 0.00 | 4.34 |
Annual Sum or Average | 0.156802E+11 | 0.428979E+09 | 0.00 | 0.846222E+09 | 116097.31 | 0.00 | 0.542018E+12 | 0.00 | 4.73 |
Minimum of Months | 3742984.69 | 0.00 | 0.00 | 45168138.48 | 0.00 | 0.00 | 0.354847E+11 | 0.00 | 4.34 |
Maximum of Months | 0.403133E+10 | 0.322413E+09 | 0.00 | 0.103380E+09 | 116097.31 | 0.00 | 0.551866E+11 | 0.00 | 5.18 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128372E+10 | 0.00 | 0.00 | 61589353.98 | 0.00 | 0.00 | 0.468073E+11 | 0.00 | 4.74 |
February | 0.636279E+09 | 0.00 | 0.00 | 59274895.50 | 0.00 | 0.00 | 0.458352E+11 | 0.00 | 4.85 |
March | 0.168093E+09 | 0.00 | 0.00 | 73885850.09 | 0.00 | 0.00 | 0.559505E+11 | 0.00 | 5.00 |
April | 17334398.85 | 8588004.97 | 0.00 | 82805070.59 | 0.00 | 0.00 | 0.560131E+11 | 0.00 | 5.16 |
May | 0.00 | 0.00 | 0.00 | 0.100660E+09 | 0.00 | 0.00 | 0.577792E+11 | 0.00 | 5.34 |
June | 0.00 | 0.00 | 0.00 | 0.105254E+09 | 0.00 | 0.00 | 0.493451E+11 | 0.00 | 5.49 |
July | 0.00 | 0.106651E+09 | 0.00 | 0.115092E+09 | 0.00 | 0.00 | 0.427411E+11 | 0.00 | 5.58 |
August | 0.00 | 0.348956E+09 | 0.00 | 0.105511E+09 | 0.00 | 0.00 | 0.381226E+11 | 0.00 | 5.58 |
September | 0.00 | 0.00 | 0.00 | 97350871.78 | 0.00 | 0.00 | 0.503398E+11 | 0.00 | 5.35 |
October | 69385072.88 | 0.00 | 0.00 | 78833698.69 | 0.00 | 0.00 | 0.614417E+11 | 0.00 | 5.11 |
November | 0.404485E+09 | 0.00 | 0.00 | 66581985.21 | 0.00 | 0.00 | 0.524043E+11 | 0.00 | 4.92 |
December | 0.995507E+09 | 0.00 | 0.00 | 63117306.66 | 0.00 | 0.00 | 0.483048E+11 | 0.00 | 4.75 |
Annual Sum or Average | 0.357480E+10 | 0.464195E+09 | 0.00 | 0.100996E+10 | 0.00 | 0.00 | 0.605085E+12 | 0.00 | 5.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 59274895.50 | 0.00 | 0.00 | 0.381226E+11 | 0.00 | 4.74 |
Maximum of Months | 0.128372E+10 | 0.348956E+09 | 0.00 | 0.115092E+09 | 0.00 | 0.00 | 0.614417E+11 | 0.00 | 5.58 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.109344E+09 | 0.00 | 0.00 | 0.657004E+11 | 0.00 | 21.04 |
February | 0.00 | 0.00 | 0.00 | 98928337.48 | 0.00 | 0.00 | 0.633461E+11 | 0.00 | 21.50 |
March | 0.00 | 0.00 | 0.00 | 0.112315E+09 | 0.00 | 0.00 | 0.761731E+11 | 0.00 | 21.76 |
April | 0.00 | 15029930.59 | 0.00 | 0.120091E+09 | 0.00 | 0.00 | 0.726116E+11 | 0.00 | 22.18 |
May | 0.00 | 0.00 | 0.00 | 0.140310E+09 | 0.00 | 0.00 | 0.705800E+11 | 0.00 | 22.42 |
June | 0.00 | 0.00 | 0.00 | 0.144540E+09 | 0.00 | 0.00 | 0.575274E+11 | 0.00 | 22.69 |
July | 0.00 | 0.174744E+09 | 0.00 | 0.154979E+09 | 0.00 | 0.00 | 0.476187E+11 | 0.00 | 22.75 |
August | 0.00 | 0.593521E+09 | 0.00 | 0.141852E+09 | 0.00 | 0.00 | 0.421815E+11 | 0.00 | 22.87 |
September | 0.00 | 0.00 | 0.00 | 0.138067E+09 | 0.00 | 0.00 | 0.607075E+11 | 0.00 | 22.51 |
October | 0.00 | 0.00 | 0.00 | 0.116504E+09 | 0.00 | 0.00 | 0.792457E+11 | 0.00 | 22.04 |
November | 0.00 | 0.00 | 0.00 | 0.105376E+09 | 0.00 | 0.00 | 0.701497E+11 | 0.00 | 21.44 |
December | 0.00 | 0.00 | 0.00 | 0.109603E+09 | 0.00 | 0.00 | 0.674950E+11 | 0.00 | 21.09 |
Annual Sum or Average | 0.00 | 0.783295E+09 | 0.00 | 0.149191E+10 | 0.00 | 0.00 | 0.773337E+12 | 0.00 | 22.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 98928337.48 | 0.00 | 0.00 | 0.421815E+11 | 0.00 | 21.04 |
Maximum of Months | 0.00 | 0.593521E+09 | 0.00 | 0.154979E+09 | 0.00 | 0.00 | 0.792457E+11 | 0.00 | 22.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576972E+09 | 0.00 | 0.00 | 1.19 |
February | 0.141083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268755E+09 | 0.00 | 0.00 | 1.20 |
March | 0.168535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
April | 0.161552E+11 | 1417444.56 | 0.00 | 0.00 | 1317221.61 | 0.00 | 0.00 | 0.00 | 1.20 |
May | 0.159463E+11 | 0.00 | 0.00 | 18558.37 | 0.00 | 0.00 | 11995581.80 | 0.00 | 1.20 |
June | 0.131170E+11 | 0.00 | 0.00 | 100100.43 | 0.00 | 0.00 | 54888992.77 | 0.00 | 1.20 |
July | 0.108008E+11 | 25405403.62 | 0.00 | 588019.62 | 6932218.68 | 0.00 | 0.327757E+09 | 0.00 | 1.21 |
August | 0.945466E+10 | 92462664.35 | 0.00 | 1009916.82 | 19190502.11 | 0.00 | 0.454641E+09 | 0.00 | 1.21 |
September | 0.137100E+11 | 0.00 | 0.00 | 498624.64 | 0.00 | 0.00 | 0.134920E+09 | 0.00 | 1.20 |
October | 0.178792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
November | 0.159892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
December | 0.153104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186657E+09 | 0.00 | 0.00 | 1.19 |
Annual Sum or Average | 0.173873E+12 | 0.119286E+09 | 0.00 | 2215219.88 | 27439942.39 | 0.103238E+10 | 0.984202E+09 | 0.00 | 1.20 |
Minimum of Months | 0.945466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
Maximum of Months | 0.178792E+11 | 92462664.35 | 0.00 | 1009916.82 | 19190502.11 | 0.576972E+09 | 0.454641E+09 | 0.00 | 1.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.601573E+11 | 0.168016E+11 | 0.234890E+12 | 0.921229E+12 | 0.656229E+11 |
February | 0.132073E+12 | 0.140692E+11 | 0.195807E+12 | 0.780092E+12 | 0.762467E+11 |
March | 0.251349E+12 | 0.135126E+11 | 0.184818E+12 | 0.756237E+12 | 0.108613E+12 |
April | 0.404830E+12 | 0.110578E+11 | 0.149514E+12 | 0.621836E+12 | 0.166891E+12 |
May | 0.531312E+12 | 0.970653E+10 | 0.130451E+12 | 0.547088E+12 | 0.226408E+12 |
June | 0.547101E+12 | 0.752659E+10 | 0.101264E+12 | 0.421942E+12 | 0.289154E+12 |
July | 0.569348E+12 | 0.609791E+10 | 0.820571E+11 | 0.349091E+12 | 0.409216E+12 |
August | 0.448904E+12 | 0.517532E+10 | 0.704949E+11 | 0.300367E+12 | 0.480102E+12 |
September | 0.285456E+12 | 0.765306E+10 | 0.107247E+12 | 0.437531E+12 | 0.265721E+12 |
October | 0.190160E+12 | 0.106556E+11 | 0.149980E+12 | 0.605519E+12 | 0.158666E+12 |
November | 0.706152E+11 | 0.130447E+11 | 0.187621E+12 | 0.733095E+12 | 0.924554E+11 |
December | 0.385158E+11 | 0.159871E+11 | 0.223934E+12 | 0.883616E+12 | 0.715494E+11 |
Annual Sum or Average | 0.352982E+13 | 0.131288E+12 | 0.181808E+13 | 0.735764E+13 | 0.241065E+13 |
Minimum of Months | 0.385158E+11 | 0.517532E+10 | 0.704949E+11 | 0.300367E+12 | 0.656229E+11 |