Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:46:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 12527.90 | 1104.24 | 1104.24 |
Net Site Energy | 12527.90 | 1104.24 | 1104.24 |
Total Source Energy | 23924.84 | 2108.79 | 2108.79 |
Net Source Energy | 23924.84 | 2108.79 | 2108.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2407.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 763.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 515.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 77.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 183.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3365.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4966.20 | 7561.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2407.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 763.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 515.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 77.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 183.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3365.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2407.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 763.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 640.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 515.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 77.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 183.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3365.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.54 | 508.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.23 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 437.73 | 666.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.54 | 508.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.23 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 437.73 | 666.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4966.204 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4966.204 | 100.00 |
Total On-Site and Utility Electric Sources | 4966.204 | 100.00 |
Total Electricity End Uses | 4966.204 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 222.23 | 4.70 |
Air to Air Heat Recovery for Heating | 4505.60 | 95.30 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4727.83 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 296.50 |
Time Setpoint Not Met During Occupied Cooling | 37.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8048.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:40 | 02-FEB-21:49 | - | - | - | - | - | - | - | - | - | - | 05-JAN-21:19 |
Heating | 0.00 | 748675.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 175533.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31553.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27239.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3901.11 | 305241.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2400.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 418492.64 | 1129040.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 748675.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 175533.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27239.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3901.11 | 305241.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1062.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1097.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2609.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2416.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2475.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2029.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1631.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 247.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 3648.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15727.97 | 8196.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 230.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 321.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1386.30 | 722.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 230.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 321.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1386.30 | 722.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.57 | 0.586220 | 0.505000 | 1.30 | 1.00 | 0.500000 | 0.000650 | 0.000071 | 1.30 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.401421 | 0.127318 | 0.505000 | 0.202718 | 0.505000 | 0.500000 | 0.002992 | 0.000044 | 0.202718 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.235261 | 0.251567 | 0.505000 | 0.118807 | 0.670844 | 0.500000 | 0.001515 | 0.000016 | 0.118807 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.188033 | 0.665593 | 0.505000 | 0.094957 | 1.00 | 0.500000 | 0.000572 | 0.000025 | 0.105464 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110997 | 0.650525 | 0.505000 | 0.056054 | 1.00 | 0.500000 | 0.000586 | 0.000017 | 0.070857 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017440 | 0.505000 | 1.72 | 0.505000 | 0.500000 | 0.021847 | 0.000103 | 1.72 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.66 | 0.086723 | 0.505000 | 0.838023 | 0.505000 | 0.500000 | 0.004393 | 0.000125 | 0.838023 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.14 | 0.193881 | 0.505000 | 2.60 | 0.517017 | 0.500000 | 0.001965 | 0.000316 | 2.60 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.63 | 0.727239 | 0.505000 | 0.824195 | 1.00 | 0.500000 | 0.000524 | 0.000155 | 0.824195 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113158 | 0.505000 | 1.13 | 0.505000 | 0.500000 | 0.003367 | 0.000126 | 1.13 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.34 | 0.107952 | 0.505000 | 1.18 | 0.505000 | 0.500000 | 0.003529 | 0.000130 | 1.18 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.37 | 0.059749 | 0.505000 | 1.20 | 0.505000 | 0.500000 | 0.011469 | 0.000086 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.801633 | 0.391749 | 0.505000 | 0.404825 | 1.00 | 0.500000 | 0.000973 | 0.000097 | 0.408127 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8129.99 | 0.000071 | 171.70 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4997.51 | 0.000044 | 131.43 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1858.31 | 0.000016 | 43.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2877.34 | 0.000025 | 78.52 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1933.23 | 0.000017 | 52.76 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11752.69 | 0.000103 | 249.69 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14268.47 | 0.000125 | 340.13 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 36137.92 | 0.000316 | 830.24 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 8856.24 | 0.000077 | 253.08 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 8876.52 | 0.000078 | 253.66 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 50004.40 | 0.000437 | 1428.94 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 50388.69 | 0.000441 | 1439.92 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 8815.11 | 0.000077 | 251.91 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 8835.40 | 0.000077 | 252.48 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17737.89 | 0.000155 | 447.39 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2675.66 | 0.000023 | 76.46 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2683.22 | 0.000023 | 76.67 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12729.02 | 0.000111 | 363.73 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14428.13 | 0.000126 | 327.21 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14871.95 | 0.000130 | 336.46 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9818.29 | 0.000086 | 211.67 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11136.39 | 0.000097 | 303.93 |
VAV WITH REHEAT HEATING COIL | 341180.79 | 0.002985 | 4966.10 |
FLR_3_DOAS HEATING COIL | 30469.72 | 0.000267 | 443.51 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.25 | 0.000077 | 0.000392 |
ROOM_2_FLR_3 FAN COIL | 1.21 | 0.000078 | 0.000381 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.53 | 0.000437 | 0.002314 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.36 | 0.000441 | 0.002085 |
ROOM_5_FLR_3 FAN COIL | 1.14 | 0.000077 | 0.000358 |
ROOM_6_FLR_3 FAN COIL | 1.10 | 0.000077 | 0.000348 |
ROOM_1_FLR_6 FAN COIL | 0.325383 | 0.000023 | 0.000102 |
ROOM_2_FLR_6 FAN COIL | 0.314852 | 0.000023 | 0.000099 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.50 | 0.000111 | 0.000476 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.25 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.21 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.53 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.36 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.14 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.325383 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.314852 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.50 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008676 | 12.80 | 0.008500 | 0.000392 | 1.25 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008681 | 12.80 | 0.008500 | 0.000381 | 1.21 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.002314 | 7.53 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008849 | 12.80 | 0.008500 | 0.002085 | 6.36 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008696 | 12.80 | 0.008500 | 0.000358 | 1.14 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008702 | 12.80 | 0.008500 | 0.000348 | 1.10 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008670 | 12.80 | 0.008500 | 0.000102 | 0.325383 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008675 | 12.80 | 0.008500 | 0.000099 | 0.314852 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008726 | 12.80 | 0.008500 | 0.000476 | 1.50 | |
VAV WITH REHEAT COOLING COIL | 27.65 | 6.70 | 0.012571 | 10.90 | 0.008500 | 0.020737 | 22.97 | 725076.75 |
FLR_3_DOAS COOLING COIL | 31.20 | 6.70 | 0.015365 | 11.90 | 0.008500 | 0.002511 | 2.05 | 87803.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 23.10 | 11.66 | 22.97 | 22.97 | 0.300000 | 0.507793 | 22.97 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.97 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.97 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020737 | 0.000023 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002985 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002511 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000267 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.029803 | 4865.96 | |
HEATSYS1 PUMP | 0.005909 | 1779.60 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005909 | 0.709109 |
COOLSYS1 | 0.029803 | 3.58 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 675462.85 | 675462.85 | 0.005909 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.029803 | 3368.87 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.029803 | 1042076.10 | 1042703.28 | 118.87 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6524 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.365 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.20756307E-14 | -0.33770914E-15 | -0.16263325E-09 | 0.36952592E-16 |
29 | 8 | 0.23685375E-07 | 0.88714462E-13 | 0.39655920E-03 | -0.26931086E-09 |
30 | 7 | -0.12800682E-01 | 0.45320291E-08 | -0.23890593E-01 | 0.14554843E-03 |
31 | 6 | 0.42054172 | 0.15673111E-05 | 0.48500809 | -0.49268323E-02 |
32 | 5 | -5.3387987 | 0.58223180E-04 | -4.5403777 | 0.65021910E-01 |
33 | 4 | 33.658449 | 0.47408857E-03 | 21.827556 | -0.43082749 |
34 | 3 | -112.62083 | 0.10289916E-02 | -56.389455 | 1.5353436 |
35 | 2 | 198.51314 | 0.57668395E-03 | 78.577213 | -2.9226634 |
36 | 1 | -171.67490 | 0.61354169E-04 | -55.459608 | 2.7545325 |
37 | 0 | 57.057407 | 0.34787598E-06 | 15.525360 | |
38 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
39 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
40 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
41 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
42 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
43 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
44 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
45 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
46 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
47 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
48 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
49 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
50 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
51 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
52 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
53 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
54 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
55 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
56 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
57 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.361_SHGC_0.4 | 37 | 1 | VerySmooth | 2.051 | 2.051 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.361_SHGC_0.4 | 38 | 1 | VerySmooth | 2.051 | 2.051 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.64640E-002 | 0.31435 | 0.48144 | 0.48144 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11581 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.64640E-002 | 0.31435 | 0.48144 | 0.48144 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11581 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1649 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.6465E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1866 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.8510E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1147 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5344E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.6285E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5376E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1873 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1039 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2126 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1179 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1269 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6629E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1970E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.1022E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.0136E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.3165E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0856E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7487E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9611E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1840E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5560E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6155E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.0136E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.3165E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0856E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7487E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9611E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1840E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5560E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6155E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33766.62565 | 33766.62565 | 2.57219 | 2.57219 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.48300 | 1.53564E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1588.52735 | 1588.52735 | 7.13858E-002 | 0.85446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5268.84019 | 5268.84019 | 0.40142 | 0.40142 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3977.85611 | 3977.85611 | 0.17874 | 0.17874 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3087.97149 | 3087.97149 | 0.23526 | 0.23526 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53645E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1260.67604 | 1260.67604 | 5.66505E-002 | 9.17347E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2468.59619 | 2468.59619 | 0.18803 | 0.18803 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53645E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2346.96544 | 2346.96544 | 0.10546 | 0.10546 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1457.22342 | 1457.22342 | 0.11100 | 0.11100 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1576.83317 | 1576.83317 | 7.08572E-002 | 7.08572E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44760.16202 | 44760.16202 | 3.40980 | 3.40980 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3095.61799 | 3095.61799 | 0.13910 | 0.13910 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21763.40633 | 21763.40633 | 1.65945 | 1.65945 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10052.55445 | 10052.55445 | 0.45171 | 0.67639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 67467.14171 | 67467.14171 | 5.14148 | 5.14148 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23075.77761 | 23075.77761 | 1.03695 | 1.89399 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12187.02641 | 12187.02641 | 1.25105 | 1.25105 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 8856.37107 | 8856.37107 | 0.40028 | 0.40028 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11824.31579 | 11824.31579 | 1.21382 | 1.21382 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 8876.65272 | 8876.65272 | 0.40120 | 0.40120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 73374.00120 | 73374.00120 | 7.53149 | 7.53149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 50004.78230 | 50004.78230 | 2.26021 | 2.26021 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 61956.94831 | 61956.94831 | 6.36010 | 6.36010 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.06600 | 1.53574E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 50389.07931 | 50389.07931 | 2.27758 | 2.27758 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11071.93147 | 11071.93147 | 1.13658 | 1.13658 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.87167 | 1.53571E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 8815.23592 | 8815.23592 | 0.39842 | 0.39842 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10749.23793 | 10749.23793 | 1.10346 | 1.10346 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 8835.52582 | 8835.52582 | 0.39934 | 0.39934 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21425.43209 | 21425.43209 | 1.63207 | 1.63207 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 31.20000 | 1.53651E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 13590.33341 | 13590.33341 | 0.61072 | 0.61072 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3169.70130 | 3169.70130 | 0.32538 | 0.32538 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2675.70060 | 2675.70060 | 0.12093 | 0.12093 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3067.10709 | 3067.10709 | 0.31485 | 0.31485 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2683.25307 | 2683.25307 | 0.12128 | 0.12128 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14599.37495 | 14599.37495 | 1.49870 | 1.49870 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 12729.16267 | 12729.16267 | 0.57534 | 0.57534 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29281.79503 | 29281.79503 | 2.23336 | 2.23336 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8752.15695 | 8752.15695 | 0.39329 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30694.26555 | 30694.26555 | 2.34106 | 2.34106 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8922.21941 | 8922.21941 | 0.40093 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31024.91095 | 31024.91095 | 2.36964 | 2.36964 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3805.82764 | 3805.82764 | 0.17100 | 0.36735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10523.65250 | 10523.65250 | 0.80163 | 0.80163 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9082.19175 | 9082.19175 | 0.40813 | 0.40813 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 393580.82 | 22.96936 | 22.96936 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 384836.42 | 7.77252 | 7.77252 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43560.46 | 19.28626 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101562.16 | 6.95459 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57219 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58622 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29896 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.49927E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.11247E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29896 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8129.99010 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.11247E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.69989 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.40142 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12732 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20272 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99250E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.37204E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20272 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4997.51329 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.37204E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.42975 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23526 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25157 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11881 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67084 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51451E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62573E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11881 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1858.30674 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62573E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.56657 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18803 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66559 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.49565E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.72422E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51722E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10546 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2877.33586 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51722E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.52316 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11100 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65053 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.60537E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.85681E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69127E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.08572E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1933.22820 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69127E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.75888 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40980 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74397E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72195 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18467E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02818E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72195 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11752.68633 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02818E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.68771 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65945 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.67231E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83802 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.39329E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24827E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83802 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14268.47415 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24827E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 340.13262 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.14148 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19388 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59645 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51702 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96512E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16150E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.59645 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36137.92165 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16150E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 830.24330 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25105 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25105 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.74783E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.92131E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70999 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67640E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.92131E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25105 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8856.24013 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.74783E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 253.08024 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21382 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21382 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.76557E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.80972E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70998 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68145E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.80972E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21382 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8876.52154 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.76557E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 253.65965 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.53149 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.53149 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.37460E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.31403E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71080 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60187E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.31403E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.53149 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 50004.39769 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.37460E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1428.94269 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.36010 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.36010 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.40822E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.08521E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70987 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84916E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.08521E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.36010 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 50388.69226 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.40822E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1439.92175 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13658 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13658 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.71184E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.58069E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70995 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69557E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.58069E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13658 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8815.10545 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.71184E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 251.90506 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10346 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10346 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.72959E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.48185E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70994 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70156E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.48185E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10346 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8835.39512 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.72959E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.48471 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.63207 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72724 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82420 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.23899E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55179E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82420 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17737.88869 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55179E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 447.39042 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32538 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32538 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.34079E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.01809E-004 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71000 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66980E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01809E-004 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32538 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2675.66359 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34079E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 76.45755 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31485 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31485 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.34739E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.86531E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70999 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67509E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.86531E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31485 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2683.21599 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34739E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 76.67331 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.49870 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.49870 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.11359E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.75909E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70986 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72564E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.75909E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.49870 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 12729.01937 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11359E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 363.73275 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23336 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11316 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.12785 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36697E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26224E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12785 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14428.12529 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26224E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.21043 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34106 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10795 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18223 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.52933E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30106E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18223 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14871.94814 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30106E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 336.45775 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36964 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.97492E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19667 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50500 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14692E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.58947E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19667 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9818.28768 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.58947E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.67101 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80163 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39175 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50500 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40482 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.72561E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.74260E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40813 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11136.38678 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.74260E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.93183 |
318 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66369 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66369 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.09641 |
321 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66369 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.96936 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.96936 |
324 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50779 |
326 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.96936 |
335 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
336 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.96936 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.65086 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90269 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.25709E-002 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 725076.74864 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.07371E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.96936 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 341180.78868 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.98480E-003 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4966.10040 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.96936 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07371E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.29632E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.98480E-003 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.20000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89847 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.53651E-002 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 87803.63747 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51117E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 30469.71807 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66562E-004 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 443.50586 |
367 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51117E-003 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89629E-004 |
370 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.66562E-004 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.98032E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4865.95916 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.90924E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.70911 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.90924E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1779.60469 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 675462.85078 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 675462.85000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.90924E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.98032E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.57639 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.98032E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3368.86764 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.98032E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1042076.10264 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1042703.28000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 118.86817 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8171.67 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5017.57 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1866.86 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2888.49 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1940.72 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11812.64 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 14333.27 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 36307.33 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 9539.57 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 9561.42 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 53863.05 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 54276.94 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 9495.27 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 9517.12 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17813.09 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2882.04 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2890.17 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13710.83 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14496.57 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14942.66 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9867.76 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11179.55 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 207420.48 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 18524.03 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 20830.50 | 17464.31 | 3366.20 | 0.84 | 4905.73 | 49.76 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20228.97 | 16950.55 | 3278.42 | 0.84 | 4754.20 | 48.22 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 123693.73 | 104579.71 | 19114.03 | 0.85 | 30054.01 | 304.82 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 109181.95 | 89881.73 | 19300.22 | 0.82 | 24187.47 | 245.32 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 18992.16 | 15889.11 | 3103.05 | 0.84 | 4442.47 | 45.06 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18458.41 | 15432.50 | 3025.91 | 0.84 | 4307.23 | 43.69 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5411.30 | 4540.15 | 871.15 | 0.84 | 1277.89 | 12.96 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5241.17 | 4394.84 | 846.33 | 0.84 | 1235.00 | 12.53 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 25177.52 | 20995.47 | 4182.05 | 0.83 | 5819.69 | 59.03 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 677481.58 | 437184.10 | 240297.48 | 0.65 | 104859.91 | 1063.55 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64803.99 | 40877.16 | 23926.83 | 0.63 | 9107.44 | 92.37 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8258407857E-002 | 2.2403088970E-002 | Pass | Pass | 4.1359985818E-003 | 1.0974721355E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8759777963E-003 | 1.2474506502E-003 | Pass | Pass | 0.1251206775 | 0.4671998436 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4878674240E-002 | 2.2353137912E-002 | Pass | Pass | 2.0194736853E-002 | 5.5176866053E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7496493494E-004 | 2.9841970876E-004 | Pass | Pass | 0.2686075640 | 2.0663596424 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5947113094E-004 | 3.4989382726E-004 | Pass | Pass | 7.2214523965E-002 | 0.1536338155 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7212735729E-002 | 0.2045782071 | Pass | Pass | 1.9531606564E-002 | 5.3427793030E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.2084789828E-003 | 2.4540266290E-002 | Pass | Pass | 6.8718250314E-002 | 0.1681667744 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6772094936E-002 | 4.4776648005E-002 | Pass | Pass | 1.5853431722E-002 | 4.2462588282E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2626656589E-002 | 0.3118898191 | Pass | Pass | 8.3076331473E-002 | 0.2153791066 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2629737121E-002 | 0.3161946473 | Pass | Pass | 7.8107972813E-002 | 0.2026596865 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.3174956511E-002 | 2.6721680465E-002 | Pass | Pass | 0.1073061188 | 0.3075607394 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2818381914E-002 | 0.1151690194 | Pass | Pass | 0.5092180822 | 3.4176394342 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2664731514E-002 | 0.3086343042 | Pass | Pass | 8.6932764669E-002 | 0.2120463425 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2620739043E-002 | 0.3122662189 | Pass | Pass | 8.3966954351E-002 | 0.2086744782 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0070877056E-004 | 3.2901751895E-004 | Pass | Pass | 0.2745484293 | 1.5150969098 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2633528831E-002 | 0.3320007654 | Pass | Pass | 0.1309579746 | 0.5193060701 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2623012648E-002 | 0.3350809502 | Pass | Pass | 0.1321735511 | 0.5675238973 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.8714563811E-002 | 0.2871386547 | Pass | Pass | 8.1202692154E-002 | 0.2186362623 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3713718030E-002 | 7.7640533673E-002 | Pass | Pass | 1.0754169314E-002 | 3.0076408623E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3207442023E-002 | 6.6307557048E-002 | Pass | Pass | 1.1622460269E-002 | 3.5768677021E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7663192995E-002 | 8.4810061446E-002 | Pass | Pass | 2.1980307106E-002 | 4.2488873115E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9871439634E-004 | 5.9532933290E-004 | Pass | Pass | 0.2920087473 | 1.2046576073 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4416.54 | 167.62 | 2160.57 | 8857.03 | 3999.43 | 19601.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.051 | 0.401 | 0.442 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.051 | 0.401 | 0.442 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.051 | 0.401 | 0.442 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.051 | 0.401 | 0.442 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.051 | 0.401 | 0.442 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.051 | 0.401 | 0.442 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.051 | 0.401 | 0.442 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.051 | 0.401 | 0.442 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.051 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 432.95 | 2.051 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.051 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.39 | 0.0000 | Y | 13.98 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.53 | 0.0000 | Y | 109.79 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.20 | 0.0000 | Y | 30.67 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.20 | 0.0000 | Y | 30.67 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 455.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.63 | 83.63 | 193.69 | |
Exterior Lighting Total | 12338.45 | 193.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 675462.85 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1042703.28 | 2.96 | 1042886.56 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13711.19 | 20830.50 | 17464.31 | 3366.20 | 0.84 | - | 4905.73 | 49.76 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13321.00 | 20228.97 | 16950.55 | 3278.42 | 0.84 | - | 4754.20 | 48.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 80911.99 | 123693.73 | 104579.71 | 19114.03 | 0.85 | - | 30054.01 | 304.82 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 72911.15 | 109181.95 | 89881.73 | 19300.22 | 0.82 | - | 24187.47 | 245.32 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12520.19 | 18992.16 | 15889.11 | 3103.05 | 0.84 | - | 4442.47 | 45.06 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12174.58 | 18458.41 | 15432.50 | 3025.91 | 0.84 | - | 4307.23 | 43.69 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3559.85 | 5411.30 | 4540.15 | 871.15 | 0.84 | - | 1277.89 | 12.96 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3449.49 | 5241.17 | 4394.84 | 846.33 | 0.84 | - | 1235.00 | 12.53 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16640.57 | 25177.52 | 20995.47 | 4182.05 | 0.83 | - | 5819.69 | 59.03 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 725076.75 | 677481.58 | 437184.10 | 240297.48 | 0.65 | - | 104859.91 | 1063.55 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 87803.64 | 64803.99 | 40877.16 | 23926.83 | 0.63 | - | 9107.44 | 92.37 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8129.99 | 8171.67 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4997.51 | 5017.57 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1858.31 | 1866.86 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2877.34 | 2888.49 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1933.23 | 1940.72 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11752.69 | 11812.64 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14268.47 | 14333.27 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36137.92 | 36307.33 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8856.24 | 9539.57 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8876.52 | 9561.42 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 50004.40 | 53863.05 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 50388.69 | 54276.94 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8815.11 | 9495.27 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8835.40 | 9517.12 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17737.89 | 17813.09 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2675.66 | 2882.04 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2683.22 | 2890.17 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 12729.02 | 13710.83 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14428.13 | 14496.57 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14871.95 | 14942.66 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9818.29 | 9867.76 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11136.39 | 11179.55 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 341180.79 | 207420.48 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 30469.72 | 18524.03 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.25 | 880.28 | 703.64 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 854.09 | 703.64 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.53 | 5299.43 | 703.64 | 1.00 | 0.95 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.36 | 4475.19 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.14 | 799.74 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 776.43 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 228.95 | 703.64 | 1.00 | 1.66 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 221.54 | 703.64 | 1.00 | 1.68 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.50 | 1054.54 | 703.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.97 | 51466.04 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.029803 | 4865.96 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005909 | 1779.60 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029803 | 3368.87 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33766.63 | 33766.63 | 17.06 | 2.572 | 2.572 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00921 | 26.48 | 0.01536 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5268.84 | 5268.84 | 78.56 | 0.401 | 0.401 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00911 | 30.85 | 0.01536 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3087.97 | 3087.97 | 39.76 | 0.235 | 0.235 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00951 | 30.88 | 0.01536 | 0.092 | 0.00 |
MECH_FLR_1 | 2468.60 | 2468.60 | 15.03 | 0.188 | 0.188 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00903 | 30.88 | 0.01536 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1457.22 | 1457.22 | 15.38 | 0.111 | 0.111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00909 | 31.20 | 0.01537 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44760.16 | 44760.16 | 573.56 | 3.410 | 3.410 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01537 | 0.000 | 0.00 |
CAFE_FLR_1 | 21763.41 | 21763.41 | 115.23 | 1.659 | 1.659 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01004 | 30.85 | 0.01536 | 0.676 | 0.00 |
LOBBY_FLR_1 | 67467.14 | 67467.14 | 51.57 | 5.141 | 5.141 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00998 | 31.02 | 0.01536 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12187.03 | 12187.03 | 312.31 | 1.251 | 1.251 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00868 | 29.72 | 0.01536 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11824.32 | 11824.32 | 303.05 | 1.214 | 1.214 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00868 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 73374.00 | 73374.00 | 2991.95 | 7.531 | 7.531 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00860 | 30.93 | 0.01536 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 61956.95 | 61956.95 | 2525.71 | 6.360 | 6.360 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 21.11 | 21.11 | 0.00885 | 27.07 | 0.01536 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11071.93 | 11071.93 | 283.74 | 1.137 | 1.137 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00870 | 26.87 | 0.01536 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10749.24 | 10749.24 | 275.50 | 1.103 | 1.103 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00870 | 25.67 | 0.01535 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21425.43 | 21425.43 | 55.02 | 1.632 | 1.632 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00948 | 31.20 | 0.01537 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3169.70 | 3169.70 | 81.23 | 0.325 | 0.325 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00867 | 29.72 | 0.01536 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3067.11 | 3067.11 | 78.61 | 0.315 | 0.315 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00868 | 29.54 | 0.01536 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14599.37 | 14599.37 | 595.15 | 1.499 | 1.499 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00873 | 31.02 | 0.01536 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29281.80 | 29281.80 | 88.29 | 2.233 | 2.233 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01046 | 31.20 | 0.01537 | 1.188 | 0.00 |
DINING_FLR_6 | 30694.27 | 30694.27 | 92.55 | 2.341 | 2.341 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01037 | 31.20 | 0.01537 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31024.91 | 31024.91 | 300.32 | 2.370 | 2.370 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01010 | 30.25 | 0.01536 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10523.65 | 10523.65 | 25.54 | 0.802 | 0.802 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00907 | 31.20 | 0.01537 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1588.53 | 1588.53 | 0.80 | 0.071 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3977.86 | 3977.86 | 59.31 | 0.179 | 0.179 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1260.68 | 1260.68 | 16.23 | 0.057 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00744 | -26.20 | 0.00036 | 0.092 | 0.00 |
MECH_FLR_1 | 2346.97 | 2346.97 | 14.29 | 0.105 | 0.105 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00730 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1576.83 | 1576.83 | 16.64 | 0.071 | 0.071 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00739 | -26.20 | 0.00036 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3095.62 | 3095.62 | 39.67 | 0.139 | 0.139 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00728 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 10052.55 | 10052.55 | 53.23 | 0.452 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00759 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23075.78 | 23075.78 | 17.64 | 1.037 | 1.894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00749 | -26.20 | 0.00036 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8856.37 | 8856.37 | 226.96 | 0.400 | 0.400 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8876.65 | 8876.65 | 227.50 | 0.401 | 0.401 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 50004.78 | 50004.78 | 2039.03 | 2.260 | 2.260 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 50389.08 | 50389.08 | 2054.14 | 2.278 | 2.278 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8815.24 | 8815.24 | 225.90 | 0.398 | 0.398 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8835.53 | 8835.53 | 226.45 | 0.399 | 0.399 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -26.20 | 0.00036 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 13590.33 | 13590.33 | 34.90 | 0.611 | 0.611 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00761 | -26.20 | 0.00036 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2675.70 | 2675.70 | 68.57 | 0.121 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00760 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2683.25 | 2683.25 | 68.77 | 0.121 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00760 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12729.16 | 12729.16 | 518.91 | 0.575 | 0.575 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00761 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8752.16 | 8752.16 | 26.39 | 0.393 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00769 | -26.20 | 0.00036 | 1.188 | 0.00 |
DINING_FLR_6 | 8922.22 | 8922.22 | 26.90 | 0.401 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00770 | -26.20 | 0.00036 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3805.83 | 3805.83 | 36.84 | 0.171 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00711 | -26.20 | 0.00036 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9082.19 | 9082.19 | 22.04 | 0.408 | 0.408 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.97 | 22.97 | 7.77 | 7.77 | 22.9694 | 11.6637 | 22.9694 | 0.5078 | 0.3000 |
FLR_3_DOAS | 19.29 | 2.05 | 6.95 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8129.990 | 8129.990 | 1.298956 | 0.00007112 | 171.700 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8129.99 | 8129.99 | 1.298956 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797818 | 49.1961 | 1588.53 | 0.00 | 8175.48 | 8175.48 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4997.513 | 4997.513 | 0.202718 | 0.00004372 | 131.430 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4997.51 | 4997.51 | 0.202718 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753335 | 46.4907 | 3977.86 | 0.00 | 5022.56 | 5022.56 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1858.307 | 1858.307 | 0.118807 | 0.00001626 | 43.567 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1858.31 | 1858.31 | 0.118807 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00743913 | 45.9132 | 1260.68 | 0.00 | 1868.21 | 1868.21 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2877.336 | 2877.336 | 0.105464 | 0.00002517 | 78.523 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2877.34 | 2877.34 | 0.105464 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00730178 | 45.0755 | 2346.97 | 0.00 | 2891.61 | 2891.61 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1933.228 | 1933.228 | 0.070857 | 0.00001691 | 52.759 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1933.23 | 1933.23 | 0.070857 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00739258 | 45.6294 | 1576.83 | 0.00 | 1942.82 | 1942.82 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11752.686 | 11752.686 | 1.721950 | 0.00010282 | 249.688 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11752.69 | 11752.69 | 1.721950 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00727947 | 44.9423 | 3095.62 | 0.00 | 11818.31 | 11818.31 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14268.474 | 14268.474 | 0.838023 | 0.00012483 | 340.133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14268.47 | 14268.47 | 0.838023 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00758867 | 46.8271 | 10052.55 | 0.00 | 14344.22 | 14344.22 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 36137.922 | 36137.922 | 2.596449 | 0.00031615 | 830.243 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36137.92 | 36137.92 | 2.596449 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00749469 | 46.2520 | 23075.78 | 0.00 | 36331.82 | 36331.82 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13711.187 | -999.000 | 1.251051 | 0.00039213 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 13711.19 | 13176.51 | 1.251051 | 21.71 | 15.25 | 0.00867640 | 12.80 | 11.68 | 0.00850000 | 29.72 | 0.01536233 | 22.73 | 0.0000 | 21.11 | 0.00867640 | 53.0825 | 12187.03 | 0.00 | 14369.74 | 14369.74 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8856.240 | 8856.240 | 0.400283 | 0.00007748 | 253.080 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8856.24 | 8856.24 | 0.400283 | 21.11 | 13.99 | 0.00751729 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751729 | 46.0782 | 8856.37 | 0.00 | 9547.04 | 9547.04 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13320.997 | -999.000 | 1.213818 | 0.00038097 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 13321.00 | 12787.27 | 1.213818 | 21.71 | 15.25 | 0.00868145 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00868145 | 53.1130 | 11824.32 | 0.00 | 13960.22 | 13960.22 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8876.522 | 8876.522 | 0.401200 | 0.00007766 | 253.660 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8876.52 | 8876.52 | 0.401200 | 21.11 | 13.99 | 0.00751836 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751836 | 46.0846 | 8876.65 | 0.00 | 9568.91 | 9568.91 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 80911.988 | -999.000 | 7.531494 | 0.00231403 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 80911.99 | 79059.44 | 7.531494 | 21.71 | 15.18 | 0.00860187 | 12.80 | 11.68 | 0.00850000 | 30.93 | 0.01536459 | 23.06 | 0.0000 | 21.11 | 0.00860187 | 52.6305 | 73374.00 | 0.00 | 84841.05 | 84841.05 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 50004.398 | 50004.398 | 2.260212 | 0.00043746 | 1428.943 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 50004.40 | 50004.40 | 2.260212 | 21.11 | 14.02 | 0.00754505 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00754505 | 46.2434 | 50004.78 | 0.00 | 53905.74 | 53905.74 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 72911.147 | -999.000 | 6.360096 | 0.00208521 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | 7/21 19:00:00 | 72911.15 | 67490.45 | 6.360096 | 21.71 | 15.40 | 0.00884916 | 12.80 | 11.68 | 0.00850000 | 27.07 | 0.01535744 | 22.00 | 0.0000 | 21.11 | 0.00884916 | 54.1244 | 61956.95 | 0.00 | 76338.69 | 72473.58 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 50388.692 | 50388.692 | 2.277582 | 0.00044082 | 1439.922 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 50388.69 | 50388.69 | 2.277582 | 21.11 | 14.02 | 0.00754820 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00754820 | 46.2625 | 50389.08 | 0.00 | 54320.02 | 54320.02 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12520.190 | -999.000 | 1.136584 | 0.00035807 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 12520.19 | 11981.20 | 1.136584 | 21.71 | 15.26 | 0.00869557 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | 0.0000 | 21.11 | 0.00869557 | 53.1982 | 11071.93 | 0.00 | 13121.22 | 13121.22 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8815.105 | 8815.105 | 0.398424 | 0.00007712 | 251.905 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8815.11 | 8815.11 | 0.398424 | 21.11 | 13.99 | 0.00751518 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751518 | 46.0654 | 8815.24 | 0.00 | 9502.70 | 9502.70 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12174.578 | -999.000 | 1.103459 | 0.00034818 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 12174.58 | 11635.12 | 1.103459 | 21.71 | 15.27 | 0.00870156 | 12.80 | 11.68 | 0.00850000 | 25.67 | 0.01535487 | 21.60 | 0.0000 | 21.11 | 0.00870156 | 53.2344 | 10749.24 | 0.00 | 12758.37 | 12758.37 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8835.395 | 8835.395 | 0.399341 | 0.00007730 | 252.485 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8835.40 | 8835.40 | 0.399341 | 21.11 | 13.99 | 0.00751626 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00751626 | 46.0719 | 8835.53 | 0.00 | 9524.57 | 9524.57 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 17737.889 | 17737.889 | 0.824195 | 0.00015518 | 447.390 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 17737.89 | 17737.89 | 0.824195 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00761234 | 46.9683 | 13590.33 | 0.00 | 17829.09 | 17829.09 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3559.847 | -999.000 | 0.325383 | 0.00010181 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3559.85 | 3426.03 | 0.325383 | 21.71 | 15.24 | 0.00866980 | 12.80 | 11.68 | 0.00850000 | 29.72 | 0.01536233 | 22.73 | 0.0000 | 21.11 | 0.00866980 | 53.0427 | 3169.70 | 0.00 | 3731.03 | 3731.03 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2675.664 | 2675.664 | 0.120934 | 0.00002341 | 76.458 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2675.66 | 2675.66 | 0.120934 | 21.11 | 14.06 | 0.00759607 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00759607 | 46.5551 | 2675.70 | 0.00 | 2884.37 | 2884.37 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3449.489 | -999.000 | 0.314852 | 0.00009865 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3449.49 | 3315.94 | 0.314852 | 21.71 | 15.25 | 0.00867509 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00867509 | 53.0746 | 3067.11 | 0.00 | 3615.21 | 3615.21 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2683.216 | 2683.216 | 0.121276 | 0.00002347 | 76.673 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2683.22 | 2683.22 | 0.121276 | 21.11 | 14.07 | 0.00759718 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00759718 | 46.5618 | 2683.25 | 0.00 | 2892.51 | 2892.51 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16640.574 | -999.000 | 1.498703 | 0.00047591 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 16640.57 | 15819.45 | 1.498703 | 21.71 | 15.29 | 0.00872564 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00872564 | 53.3799 | 14599.37 | 0.00 | 17435.05 | 17077.88 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12729.019 | 12729.019 | 0.575336 | 0.00011136 | 363.733 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12729.02 | 12729.02 | 0.575336 | 21.11 | 14.08 | 0.00760837 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00760837 | 46.6286 | 12729.16 | 0.00 | 13722.00 | 13722.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14428.125 | 14428.125 | 1.127849 | 0.00012622 | 327.210 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14428.13 | 14428.13 | 1.127849 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00769267 | 47.4590 | 8752.16 | 0.00 | 14505.89 | 14505.89 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14871.948 | 14871.948 | 1.182234 | 0.00013011 | 336.458 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14871.95 | 14871.95 | 1.182234 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00769830 | 47.4933 | 8922.22 | 0.00 | 14952.18 | 14952.18 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9818.288 | 9818.288 | 1.196669 | 0.00008589 | 211.671 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9818.29 | 9818.29 | 1.196669 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00711493 | 43.9417 | 3805.83 | 0.00 | 9872.86 | 9872.86 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11136.387 | 11136.387 | 0.408127 | 0.00009743 | 303.932 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11136.39 | 11136.39 | 0.408127 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773887 | 47.7399 | 9082.19 | 0.00 | 11191.61 | 11191.61 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 725076.749 | -999.000 | 22.969364 | 0.02073710 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 725076.75 | 451136.03 | 22.969364 | 27.65 | 20.25 | 0.01257090 | 10.90 | 10.89 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 50.7696 | 23.99 | 0.00965226 | 49.4920 | 301241.01 | 0.00 | 744635.56 | 450524.96 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 341180.789 | 341180.789 | 6.890809 | 0.00298480 | 4966.100 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 341180.79 | 341180.79 | 6.890809 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 169.2321 | 21.00 | 0.00757713 | 46.7440 | 89794.73 | 0.00 | 250596.44 | 250596.44 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 87803.64 | 47531.07 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 11.90 | 11.31 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 99.9965 | 21.11 | 0.00871867 | 53.3362 | 187882.29 | 0.00 | 89691.54 | 48118.14 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 30469.72 | 30469.72 | 0.615395 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3216 | 21.11 | 0.00754702 | 46.2554 | 153865.76 | 0.00 | 22379.93 | 22379.93 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8129.990 | 8129.990 | 1.298956 | 0.00007112 | 171.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.1799 | 1.203618 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8129.99 | 8129.99 | 1.0000 | 1.49192365 | 1.298956 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07111744 | 60.00 | 32.22 | 27.78 | 0.000 | 8129.99 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797818 | 21.00 | 0.00797818 | 49.1961 | 1588.53 | 0.00 | 8175.48 | 8175.48 | 1.49192365 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.97 | 15.21 | 0.00800000 | 42414.6 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4997.513 | 4997.513 | 0.202718 | 0.00004372 | 131.430 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.7253 | 0.739865 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4997.51 | 4997.51 | 1.0000 | 0.23283276 | 0.202718 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04371597 | 60.00 | 32.22 | 27.78 | 0.000 | 4997.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00753335 | 21.00 | 0.00753335 | 46.4907 | 3977.86 | 0.00 | 5022.56 | 5022.56 | 0.23283276 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.75 | 20.51 | 0.00800000 | 58506.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1858.307 | 1858.307 | 0.118807 | 0.00001626 | 43.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.2697 | 0.275116 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1858.31 | 1858.31 | 1.0000 | 0.13645603 | 0.118807 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01625562 | 60.00 | 32.22 | 27.78 | 0.000 | 1858.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00743913 | 21.00 | 0.00743913 | 45.9132 | 1260.68 | 0.00 | 1868.21 | 1868.21 | 0.13645603 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.03 | 18.05 | 0.00800000 | 50625.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2877.336 | 2877.336 | 0.105464 | 0.00002517 | 78.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.4176 | 0.425980 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2877.34 | 2877.34 | 1.0000 | 0.12113139 | 0.105464 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02516962 | 60.00 | 32.22 | 27.78 | 0.000 | 2877.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00730178 | 21.00 | 0.00730178 | 45.0755 | 2346.97 | 0.00 | 2891.61 | 2891.61 | 0.12113139 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1933.228 | 1933.228 | 0.070857 | 0.00001691 | 52.759 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.2806 | 0.286208 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1933.23 | 1933.23 | 1.0000 | 0.08138345 | 0.070857 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01691100 | 60.00 | 32.22 | 27.78 | 0.000 | 1933.23 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00739258 | 21.00 | 0.00739258 | 45.6294 | 1576.83 | 0.00 | 1942.82 | 1942.82 | 0.08138345 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.1 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11752.686 | 11752.686 | 1.721950 | 0.00010282 | 249.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.7056 | 1.739946 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11752.69 | 11752.69 | 1.0000 | 1.97775622 | 1.721950 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10280714 | 60.00 | 32.22 | 27.78 | 0.000 | 11752.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00727947 | 21.00 | 0.00727947 | 44.9423 | 3095.62 | 0.00 | 11818.31 | 11818.31 | 1.97775622 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.46 | 15.39 | 0.00800000 | 42910.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14268.474 | 14268.474 | 0.838023 | 0.00012483 | 340.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 2.0707 | 2.112400 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 14268.47 | 14268.47 | 1.0000 | 0.96251595 | 0.838023 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12481410 | 60.00 | 32.22 | 27.78 | 0.000 | 14268.47 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00758867 | 21.00 | 0.00758867 | 46.8271 | 10052.55 | 0.00 | 14344.22 | 14344.22 | 0.96251595 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.21 | 18.44 | 0.00800000 | 51837.6 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36137.922 | 36137.922 | 2.596449 | 0.00031615 | 830.243 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 5.2445 | 5.350098 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 36137.92 | 36137.92 | 1.0000 | 2.98216715 | 2.596449 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.31611805 | 60.00 | 32.22 | 27.78 | 0.000 | 36137.92 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749469 | 21.00 | 0.00749469 | 46.2520 | 23075.78 | 0.00 | 36331.82 | 36331.82 | 2.98216715 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.55 | 17.55 | 0.00800000 | 49117.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13711.187 | -999.000 | 1.251051 | 0.00039213 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9690 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.251051 | 1.43690139 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 1.3158 | 1.315732 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 13711.19 | 13176.51 | 1.0000 | 1.43690139 | 1.251051 | 21.71 | 15.25 | 0.00867640 | 43864.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.39209089 | 6.70 | 15.03 | 8.33 | 0.000 | 13711.19 | 29.72 | 0.01536233 | 22.73 | 0.00000000 | 0.0000 | 21.11 | 0.00867640 | 21.11 | 0.00867640 | 53.0825 | 12187.03 | 0.00 | 14369.74 | 14369.74 | 1.43690139 | 21.71 | 15.72 | 0.00867640 | 43864.4 | 11.91 | 11.91 | 0.00867640 | 33863.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8856.240 | 8856.240 | 0.400283 | 0.00007748 | 253.080 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.251051 | 1.43690139 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.2853 | 1.311137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8856.24 | 8856.24 | 1.0000 | 0.45974719 | 0.400283 | 21.11 | 13.99 | 0.00751729 | 40306.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07747035 | 60.00 | 32.22 | 27.78 | 0.000 | 8856.24 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751729 | 21.11 | 0.00751729 | 46.0782 | 8856.37 | 0.00 | 9547.04 | 9547.04 | 0.45974719 | 16.60 | 12.68 | 0.00751729 | 35712.6 | 36.98 | 19.91 | 0.00751729 | 56478.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13320.997 | -999.000 | 1.213818 | 0.00038097 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9784 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.213818 | 1.39413781 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 1.2783 | 1.278289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 13321.00 | 12787.27 | 1.0000 | 1.39413781 | 1.213818 | 21.71 | 15.25 | 0.00868145 | 43877.2 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.38093284 | 6.70 | 15.03 | 8.33 | 0.000 | 13321.00 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00868145 | 21.11 | 0.00868145 | 53.1130 | 11824.32 | 0.00 | 13960.22 | 13960.22 | 1.39413781 | 21.71 | 15.72 | 0.00868145 | 43877.2 | 11.90 | 11.90 | 0.00868145 | 33863.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8876.522 | 8876.522 | 0.401200 | 0.00007766 | 253.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.213818 | 1.39413781 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.2882 | 1.314139 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8876.52 | 8876.52 | 1.0000 | 0.46080005 | 0.401200 | 21.11 | 13.99 | 0.00751836 | 40309.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07764776 | 60.00 | 32.22 | 27.78 | 0.000 | 8876.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751836 | 21.11 | 0.00751836 | 46.0846 | 8876.65 | 0.00 | 9568.91 | 9568.91 | 0.46080005 | 16.60 | 12.68 | 0.00751836 | 35715.3 | 36.98 | 19.91 | 0.00751836 | 56481.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80911.988 | -999.000 | 7.531494 | 0.00231403 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8305 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.531494 | 8.65034127 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 7.7645 | 7.764354 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 80911.99 | 79059.44 | 1.0000 | 8.65034127 | 7.531494 | 21.71 | 15.18 | 0.00860187 | 43675.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 2.31379335 | 6.70 | 15.03 | 8.33 | 0.000 | 80911.99 | 30.93 | 0.01536459 | 23.06 | 0.00000000 | 0.0000 | 21.11 | 0.00860187 | 21.11 | 0.00860187 | 52.6305 | 73374.00 | 0.00 | 84841.05 | 84841.05 | 8.65034127 | 21.71 | 15.65 | 0.00860187 | 43675.8 | 12.10 | 11.91 | 0.00860187 | 33868.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 50004.398 | 50004.398 | 2.260212 | 0.00043746 | 1428.943 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.531494 | 8.65034127 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 7.2569 | 7.402983 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 50004.40 | 50004.40 | 1.0000 | 2.59597950 | 2.260212 | 21.11 | 14.02 | 0.00754505 | 40378.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.43741566 | 60.00 | 32.22 | 27.78 | 0.000 | 50004.40 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00754505 | 21.11 | 0.00754505 | 46.2434 | 50004.78 | 0.00 | 53905.74 | 53905.74 | 2.59597950 | 16.60 | 12.71 | 0.00754505 | 35782.9 | 36.98 | 19.93 | 0.00754505 | 56548.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72911.147 | -999.000 | 6.360096 | 0.00208521 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2901 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.360096 | 7.30492506 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 6.9967 | 6.996589 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | unknown | unknown | 7/21 19:00:00 | Sensible | 72911.15 | 67490.45 | 1.0000 | 7.30492506 | 6.360096 | 21.71 | 15.40 | 0.00884916 | 44303.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 2.08499793 | 6.70 | 15.03 | 8.33 | 0.000 | 72911.15 | 27.07 | 0.01535744 | 22.00 | 0.00000000 | 0.0000 | 21.11 | 0.00884916 | 21.11 | 0.00884916 | 54.1244 | 61956.95 | 0.00 | 76338.69 | 72473.58 | 7.30492506 | 21.71 | 15.87 | 0.00884916 | 44303.3 | 12.00 | 11.91 | 0.00863946 | 33853.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 50388.692 | 50388.692 | 2.277582 | 0.00044082 | 1439.922 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.360096 | 7.30492506 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 7.3127 | 7.459876 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 50388.69 | 50388.69 | 1.0000 | 2.61593019 | 2.277582 | 21.11 | 14.02 | 0.00754820 | 40386.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.44077729 | 60.00 | 32.22 | 27.78 | 0.000 | 50388.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00754820 | 21.11 | 0.00754820 | 46.2625 | 50389.08 | 0.00 | 54320.02 | 54320.02 | 2.61593019 | 16.60 | 12.71 | 0.00754820 | 35790.9 | 36.98 | 19.93 | 0.00754820 | 56555.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12520.190 | -999.000 | 1.136584 | 0.00035807 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0046 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.136584 | 1.30542995 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 1.2015 | 1.201444 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 12520.19 | 11981.20 | 1.0000 | 1.30542995 | 1.136584 | 21.71 | 15.26 | 0.00869557 | 43913.1 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.35803265 | 6.70 | 15.03 | 8.33 | 0.000 | 12520.19 | 26.87 | 0.01535708 | 21.94 | 0.00000000 | 0.0000 | 21.11 | 0.00869557 | 21.11 | 0.00869557 | 53.1982 | 11071.93 | 0.00 | 13121.22 | 13121.22 | 1.30542995 | 21.71 | 15.74 | 0.00869557 | 43913.1 | 11.87 | 11.87 | 0.00869557 | 33861.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8815.105 | 8815.105 | 0.398424 | 0.00007712 | 251.905 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.136584 | 1.30542995 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.2793 | 1.305047 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8815.11 | 8815.11 | 1.0000 | 0.45761179 | 0.398424 | 21.11 | 13.99 | 0.00751518 | 40301.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07711052 | 60.00 | 32.22 | 27.78 | 0.000 | 8815.11 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751518 | 21.11 | 0.00751518 | 46.0654 | 8815.24 | 0.00 | 9502.70 | 9502.70 | 0.45761179 | 16.60 | 12.68 | 0.00751518 | 35707.3 | 36.98 | 19.91 | 0.00751518 | 56473.1 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12174.578 | -999.000 | 1.103459 | 0.00034818 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0158 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.103459 | 1.26738441 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 1.1683 | 1.168278 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 12174.58 | 11635.12 | 1.0000 | 1.26738441 | 1.103459 | 21.71 | 15.27 | 0.00870156 | 43928.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.34814937 | 6.70 | 15.03 | 8.33 | 0.000 | 12174.58 | 25.67 | 0.01535487 | 21.60 | 0.00000000 | 0.0000 | 21.11 | 0.00870156 | 21.11 | 0.00870156 | 53.2344 | 10749.24 | 0.00 | 12758.37 | 12758.37 | 1.26738441 | 21.71 | 15.74 | 0.00870156 | 43928.3 | 11.85 | 11.85 | 0.00870156 | 33861.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8835.395 | 8835.395 | 0.399341 | 0.00007730 | 252.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.103459 | 1.26738441 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.2822 | 1.308050 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8835.40 | 8835.40 | 1.0000 | 0.45866507 | 0.399341 | 21.11 | 13.99 | 0.00751626 | 40303.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07728801 | 60.00 | 32.22 | 27.78 | 0.000 | 8835.40 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00751626 | 21.11 | 0.00751626 | 46.0719 | 8835.53 | 0.00 | 9524.57 | 9524.57 | 0.45866507 | 16.60 | 12.68 | 0.00751626 | 35710.0 | 36.98 | 19.91 | 0.00751626 | 56475.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17737.889 | 17737.889 | 0.824195 | 0.00015518 | 447.390 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 2.5742 | 2.626035 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 17737.89 | 17737.89 | 1.0000 | 0.94663453 | 0.824195 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15516296 | 60.00 | 32.22 | 27.78 | 0.000 | 17737.89 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00761234 | 21.00 | 0.00761234 | 46.9683 | 13590.33 | 0.00 | 17829.09 | 17829.09 | 0.94663453 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.07 | 19.68 | 0.00800000 | 55768.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3559.847 | -999.000 | 0.325383 | 0.00010181 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9567 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.325383 | 0.37372071 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 0.3416 | 0.341605 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3559.85 | 3426.03 | 1.0000 | 0.37372071 | 0.325383 | 21.71 | 15.24 | 0.00866980 | 43847.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.10179888 | 6.70 | 15.03 | 8.33 | 0.000 | 3559.85 | 29.72 | 0.01536233 | 22.73 | 0.00000000 | 0.0000 | 21.11 | 0.00866980 | 21.11 | 0.00866980 | 53.0427 | 3169.70 | 0.00 | 3731.03 | 3731.03 | 0.37372071 | 21.71 | 15.71 | 0.00866980 | 43847.6 | 11.93 | 11.91 | 0.00866980 | 33864.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2675.664 | 2675.664 | 0.120934 | 0.00002341 | 76.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.325383 | 0.37372071 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.3883 | 0.396123 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2675.66 | 2675.66 | 1.0000 | 0.13889994 | 0.120934 | 21.11 | 14.06 | 0.00759607 | 40506.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02340548 | 60.00 | 32.22 | 27.78 | 0.000 | 2675.66 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759607 | 21.11 | 0.00759607 | 46.5551 | 2675.70 | 0.00 | 2884.37 | 2884.37 | 0.13889994 | 16.60 | 12.76 | 0.00759607 | 35912.1 | 36.98 | 19.97 | 0.00759607 | 56677.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3449.489 | -999.000 | 0.314852 | 0.00009865 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9666 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.314852 | 0.36162485 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 0.3310 | 0.331015 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3449.49 | 3315.94 | 1.0000 | 0.36162485 | 0.314852 | 21.71 | 15.25 | 0.00867509 | 43861.1 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.09864303 | 6.70 | 15.03 | 8.33 | 0.000 | 3449.49 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00867509 | 21.11 | 0.00867509 | 53.0746 | 3067.11 | 0.00 | 3615.21 | 3615.21 | 0.36162485 | 21.71 | 15.72 | 0.00867509 | 43861.1 | 11.92 | 11.91 | 0.00867509 | 33863.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2683.216 | 2683.216 | 0.121276 | 0.00002347 | 76.673 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.314852 | 0.36162485 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 0.3894 | 0.397241 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2683.22 | 2683.22 | 1.0000 | 0.13929201 | 0.121276 | 21.11 | 14.07 | 0.00759718 | 40509.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02347155 | 60.00 | 32.22 | 27.78 | 0.000 | 2683.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759718 | 21.11 | 0.00759718 | 46.5618 | 2683.25 | 0.00 | 2892.51 | 2892.51 | 0.13929201 | 16.60 | 12.76 | 0.00759718 | 35914.9 | 36.98 | 19.97 | 0.00759718 | 56680.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16640.574 | -999.000 | 1.498703 | 0.00047591 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0605 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.498703 | 1.72134450 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 1.5969 | 1.596838 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 16640.57 | 15819.45 | 1.0000 | 1.72134450 | 1.498703 | 21.71 | 15.29 | 0.00872564 | 43989.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.47586086 | 6.70 | 15.03 | 8.33 | 0.000 | 16640.57 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00872564 | 21.11 | 0.00872564 | 53.3799 | 14599.37 | 0.00 | 17435.05 | 17077.88 | 1.72134450 | 21.71 | 15.76 | 0.00872564 | 43989.4 | 11.99 | 11.91 | 0.00864341 | 33860.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12729.019 | 12729.019 | 0.575336 | 0.00011136 | 363.733 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.498703 | 1.72134450 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.8473 | 1.884488 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 12729.02 | 12729.02 | 1.0000 | 0.66080587 | 0.575336 | 21.11 | 14.08 | 0.00760837 | 40538.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.11134765 | 60.00 | 32.22 | 27.78 | 0.000 | 12729.02 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00760837 | 21.11 | 0.00760837 | 46.6286 | 12729.16 | 0.00 | 13722.00 | 13722.00 | 0.66080587 | 16.60 | 12.77 | 0.00760837 | 35943.2 | 36.98 | 19.98 | 0.00760837 | 56708.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14428.125 | 14428.125 | 1.127849 | 0.00012622 | 327.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 2.0939 | 2.136035 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 14428.13 | 14428.13 | 1.0000 | 1.29539761 | 1.127849 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12621066 | 60.00 | 32.22 | 27.78 | 0.000 | 14428.13 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769267 | 21.00 | 0.00769267 | 47.4590 | 8752.16 | 0.00 | 14505.89 | 14505.89 | 1.29539761 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.58 | 17.22 | 0.00800000 | 48132.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14871.948 | 14871.948 | 1.182234 | 0.00013011 | 336.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 2.1583 | 2.201742 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 14871.95 | 14871.95 | 1.0000 | 1.35786225 | 1.182234 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.13009302 | 60.00 | 32.22 | 27.78 | 0.000 | 14871.95 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769830 | 21.00 | 0.00769830 | 47.4933 | 8922.22 | 0.00 | 14952.18 | 14952.18 | 1.35786225 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.40 | 17.15 | 0.00800000 | 47946.3 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9818.288 | 9818.288 | 1.196669 | 0.00008589 | 211.671 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.4249 | 1.453564 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9818.29 | 9818.29 | 1.0000 | 1.37444159 | 1.196669 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.08588590 | 60.00 | 32.22 | 27.78 | 0.000 | 9818.29 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.73 | 0.00711493 | 21.00 | 0.00711493 | 43.9417 | 3805.83 | 0.00 | 9872.86 | 9872.86 | 1.37444159 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.64 | 15.83 | 0.00800000 | 44117.9 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11136.387 | 11136.387 | 0.408127 | 0.00009743 | 303.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 1.6162 | 1.648705 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11136.39 | 11136.39 | 1.0000 | 0.46875698 | 0.408127 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09741603 | 60.00 | 32.22 | 27.78 | 0.000 | 11136.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773887 | 21.00 | 0.00773887 | 47.7399 | 9082.19 | 0.00 | 11191.61 | 11191.61 | 0.46875698 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 725076.749 | -999.000 | 22.969364 | 0.02073710 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.2087 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.969364 | 26.38159644 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 69.5800 | 69.580019 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 725076.75 | 451136.03 | 1.0000 | 26.38159644 | 22.969364 | 27.65 | 20.25 | 0.01257090 | 59869.9 | 10.90 | 10.89 | 0.00850000 | 32385.7 | 20.73498783 | 6.70 | 15.03 | 8.33 | 51466.043 | 673610.71 | 31.20 | 0.01536508 | 23.13 | 11.66146000 | 50.7696 | 23.99 | 0.00968768 | 23.99 | 0.00965226 | 49.4920 | 301241.01 | 0.00 | 744635.56 | 450524.96 | 26.38159644 | 27.65 | 20.79 | 0.01257090 | 59869.9 | 11.04 | 11.00 | 0.00814953 | 31644.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 341180.789 | 341180.789 | 6.890809 | 0.00298480 | 4966.100 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.969364 | 26.38159644 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 49.5142 | 50.510667 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 341180.79 | 341180.79 | 1.0000 | 7.91447893 | 6.890809 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 2.98449390 | 60.00 | 32.22 | 27.78 | 0.000 | 341180.79 | -26.20 | 0.00036134 | -26.20 | 11.66146000 | 169.2321 | 20.99 | 0.00759425 | 21.00 | 0.00757713 | 46.7440 | 89794.73 | 0.00 | 250596.44 | 250596.44 | 7.91447893 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.4029 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 29.80020438 | 15.03 | 6.70 | 8.33 | 1042076.10 | 8.4258 | 8.425837 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 87803.64 | 47531.07 | 1.0000 | 2.35605237 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 70669.3 | 11.90 | 11.31 | 0.00850000 | 33402.1 | 2.51091675 | 6.70 | 15.03 | 8.33 | 2195.006 | 85608.63 | 31.20 | 0.01536508 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00872299 | 21.11 | 0.00871867 | 53.3362 | 187882.29 | 0.00 | 89691.54 | 48118.14 | 2.35605237 | 31.20 | 23.70 | 0.01536508 | 70669.3 | 11.44 | 11.40 | 0.00836907 | 32600.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 5.90864088 | 54.44 | 82.22 | 27.78 | 689056.81 | 4.4219 | 4.510939 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 30469.72 | 30469.72 | 1.0000 | 0.70681571 | 0.615395 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 0.26653519 | 60.00 | 32.22 | 27.78 | 0.000 | 30469.72 | -26.20 | 0.00036134 | -26.20 | 2.05124512 | 333.3216 | 21.11 | 0.00754661 | 21.11 | 0.00754702 | 46.2554 | 153865.76 | 0.00 | 22379.93 | 22379.93 | 0.70681571 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.97 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 865.50 | 7107.33 | 466.83 |
RETAIL_1_FLR_1 | 3451.17 | 7276.33 | 2429.17 |
RETAIL_2_FLR_1 | 2133.17 | 7028.33 | 1200.50 |
MECH_FLR_1 | 2374.17 | 7626.67 | 2013.50 |
STORAGE_FLR_1 | 2400.33 | 8136.17 | 2301.00 |
LAUNDRY_FLR_1 | 6788.67 | 3531.50 | 2646.00 |
CAFE_FLR_1 | 3636.33 | 6427.17 | 1939.67 |
LOBBY_FLR_1 | 2657.17 | 6431.67 | 1236.33 |
ROOM_1_FLR_3 | 3188.67 | 8232.83 | 3062.83 |
ROOM_2_FLR_3 | 4102.83 | 8022.17 | 3787.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2789.17 | 8688.33 | 2766.50 |
ROOM_5_FLR_3 | 3092.17 | 8173.83 | 3047.00 |
ROOM_6_FLR_3 | 3895.50 | 7953.33 | 3657.50 |
CORRIDOR_FLR_3 | 2309.33 | 8290.17 | 2240.17 |
ROOM_1_FLR_6 | 3736.83 | 8169.00 | 3532.33 |
ROOM_2_FLR_6 | 4611.67 | 7993.50 | 4262.67 |
ROOM_3_MULT9_FLR_6 | 2609.83 | 8163.67 | 2533.83 |
BANQUET_FLR_6 | 3967.83 | 4334.17 | 1096.67 |
DINING_FLR_6 | 4420.67 | 3237.33 | 955.33 |
KITCHEN_FLR_6 | 8013.67 | 6347.50 | 5943.00 |
CORRIDOR_FLR_6 | 2929.83 | 7260.00 | 2087.00 |
Facility | 8756.33 | 8760.00 | 8048.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 171.17 | 0.00 | 171.17 | 0.00 |
RETAIL_1_FLR_1 | 176.67 | 0.00 | 176.67 | 0.00 |
RETAIL_2_FLR_1 | 186.17 | 0.00 | 186.17 | 0.00 |
MECH_FLR_1 | 247.67 | 0.00 | 247.67 | 0.00 |
STORAGE_FLR_1 | 275.83 | 0.00 | 275.83 | 0.00 |
LAUNDRY_FLR_1 | 141.67 | 0.00 | 141.67 | 0.00 |
CAFE_FLR_1 | 170.33 | 0.00 | 170.33 | 0.00 |
LOBBY_FLR_1 | 178.00 | 0.00 | 178.00 | 0.00 |
ROOM_1_FLR_3 | 49.00 | 1.50 | 49.00 | 1.50 |
ROOM_2_FLR_3 | 79.50 | 3.33 | 79.50 | 3.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 131.83 | 14.83 | 131.83 | 14.83 |
ROOM_5_FLR_3 | 59.83 | 0.00 | 59.83 | 0.00 |
ROOM_6_FLR_3 | 91.17 | 17.17 | 91.17 | 17.17 |
CORRIDOR_FLR_3 | 217.50 | 0.00 | 217.50 | 0.00 |
ROOM_1_FLR_6 | 60.33 | 4.33 | 60.33 | 4.33 |
ROOM_2_FLR_6 | 101.33 | 7.67 | 101.33 | 7.67 |
ROOM_3_MULT9_FLR_6 | 19.17 | 4.17 | 19.17 | 4.17 |
BANQUET_FLR_6 | 124.00 | 0.00 | 124.00 | 0.00 |
DINING_FLR_6 | 120.50 | 0.00 | 120.50 | 0.00 |
KITCHEN_FLR_6 | 96.50 | 0.00 | 96.50 | 0.00 |
CORRIDOR_FLR_6 | 221.50 | 0.00 | 221.50 | 0.00 |
Facility | 296.50 | 37.33 | 296.50 | 37.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 1.014 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.827 | 0.140 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.434 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.534 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.545 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.881 | 0.151 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 4.174 | 0.111 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.876 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.047 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.081 | 0.000 | 0.085 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.055 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.053 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.634 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.067 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.148 | 0.000 | 0.106 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.815 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 5.207 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 22.380 | 0.152 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.182 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.896 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.543 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.327 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.504 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.514 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.563 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.830 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.722 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.597 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.835 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.019 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 12.839 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.110 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.74 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.49 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.88 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.55 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42066669.95 | 0.00 | 42066669.95 | 0.00 | 42066669.95 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6493033.53 | 0.00 | 6493033.53 | 322448.37 | 6815481.91 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3801049.11 | 0.00 | 3801049.11 | 124465.48 | 3925514.59 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3001828.54 | 0.00 | 3001828.54 | 294162.45 | 3295990.99 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1767720.90 | 0.00 | 1767720.90 | 169715.53 | 1937436.43 | 1821682.01 | 8752.00 | 3.67 | 4.33 | 0.00 |
LAUNDRY_FLR_1 | 63562864.23 | 0.00 | 63562864.23 | 401663.80 | 63964528.04 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26886066.94 | 0.00 | 26886066.94 | 712790.38 | 27598857.32 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83613986.10 | 0.00 | 83613986.10 | 2036604.93 | 85650591.03 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 56724.38 | 1516881.09 | 187159.47 | 1704040.56 | 1946875.62 | 2190.00 | 6004.00 | 566.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 47336.47 | 1507322.11 | 187145.19 | 1694467.29 | 1946647.51 | 2190.00 | 6102.90 | 467.10 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 586.27 | 1100498.24 | 52219.59 | 1152717.83 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 369.17 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 54485.64 | 19858314.94 | 52233.87 | 19910548.81 | 26405105.73 | 2190.00 | 6014.20 | 555.80 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 56820.39 | 1516977.10 | 187159.47 | 1704136.57 | 1946875.62 | 2190.00 | 6004.00 | 566.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 53638.20 | 1513623.83 | 187145.19 | 1700769.02 | 1946647.51 | 2190.00 | 6008.43 | 561.57 | 0.00 |
CORRIDOR_FLR_3 | 25991316.04 | 0.00 | 25991316.04 | 226313.45 | 26217629.49 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 68523.48 | 433562.66 | 187199.47 | 620762.13 | 486718.90 | 2043.99 | 6004.35 | 711.66 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 53006.39 | 418002.80 | 187185.19 | 605187.98 | 486661.88 | 2071.58 | 6134.27 | 554.16 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 68461.81 | 2413652.13 | 95777.80 | 2509429.93 | 3126920.42 | 2190.00 | 6003.00 | 567.00 | 0.00 |
BANQUET_FLR_6 | 41687759.33 | 0.00 | 41687759.33 | 457094.06 | 42144853.39 | 37458366.31 | 4286.28 | 216.45 | 4257.27 | 0.00 |
DINING_FLR_6 | 45069971.46 | 0.00 | 45069971.46 | 457094.06 | 45527065.52 | 37458366.31 | 0.00 | 3150.08 | 5609.92 | 0.00 |
KITCHEN_FLR_6 | 60360817.88 | 0.00 | 60360817.88 | 409205.16 | 60770023.03 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12824864.34 | 0.00 | 12824864.34 | 400507.17 | 13225371.51 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 5781229.54 | 0.21E+10 | 18860290.15 | 0.22E+10 | 0.43E+10 | 8760.00 | 7691.64 | 8760.00 | 369.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3339 | 0.0000 | 1.3339 | 0.0000 | 1.3339 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2059 | 0.0000 | 0.2059 | 0.0102 | 0.2161 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1205 | 0.0000 | 0.1205 | 0.0039 | 0.1245 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0952 | 0.0000 | 0.0952 | 0.0093 | 0.1045 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0561 | 0.0000 | 0.0561 | 0.0054 | 0.0614 | 0.0578 | 8752.00 | 3.67 | 4.33 |
LAUNDRY_FLR_1 | 2.0156 | 0.0000 | 2.0156 | 0.0127 | 2.0283 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8526 | 0.0000 | 0.8526 | 0.0226 | 0.8752 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6514 | 0.0000 | 2.6514 | 0.0646 | 2.7160 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0059 | 0.0540 | 0.0617 | 2190.00 | 6004.00 | 566.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0059 | 0.0537 | 0.0617 | 2190.00 | 6102.90 | 467.10 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0017 | 0.6297 | 0.0017 | 0.6314 | 0.8373 | 2190.00 | 6014.20 | 555.80 |
ROOM_5_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0059 | 0.0540 | 0.0617 | 2190.00 | 6004.00 | 566.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0059 | 0.0539 | 0.0617 | 2190.00 | 6008.43 | 561.57 |
CORRIDOR_FLR_3 | 0.8242 | 0.0000 | 0.8242 | 0.0072 | 0.8314 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0022 | 0.0137 | 0.0059 | 0.0197 | 0.0154 | 2043.99 | 6004.35 | 711.66 |
ROOM_2_FLR_6 | 0.0116 | 0.0017 | 0.0133 | 0.0059 | 0.0192 | 0.0154 | 2071.58 | 6134.27 | 554.16 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0022 | 0.0765 | 0.0030 | 0.0796 | 0.0992 | 2190.00 | 6003.00 | 567.00 |
BANQUET_FLR_6 | 1.3219 | 0.0000 | 1.3219 | 0.0145 | 1.3364 | 1.1878 | 4286.28 | 216.45 | 4257.27 |
DINING_FLR_6 | 1.4292 | 0.0000 | 1.4292 | 0.0145 | 1.4437 | 1.1878 | 0.00 | 3150.08 | 5609.92 |
KITCHEN_FLR_6 | 1.9140 | 0.0000 | 1.9140 | 0.0130 | 1.9270 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4067 | 0.0000 | 0.4067 | 0.0127 | 0.4194 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.8589 | 0.1819 | 65.0408 | 0.4722 | 65.5130 | 73.9670 | 8760.00 | 7691.64 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 39336975.27 | 459583.04 | 39796558.32 | 64690340.46 | 8755.50 | 1.17 | 3.33 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.4489 | 0.0000 | 17.4489 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2474 | 0.0146 | 1.2619 | 2.0513 | 8755.50 | 1.17 | 3.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3474.15 | 0.00 | 0.00 | 0.00 | 5285.85 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.0183 | 0.0000 | 0.0000 | 0.0000 | 17.0778 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5756 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4001 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
Electricity:Building | 2446.80 | 31063.18 | 17-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.71 | 30922.03 | 17-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.32 | 293.96 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.98 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.98 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.79 | 3093.58 | 03-JUN-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.79 | 982.16 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.79 | 982.16 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.52 | 2448.50 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.52 | 2448.50 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.40 | 778.33 | 02-FEB-23:30 | 3263.93 | 12-SEP-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 986.09 | 2652.74 | 27-APR-00:20 | 226681.71 | 04-AUG-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.30 | 0.00 | 01-JAN-11:10 | 1894.00 | 02-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.01 | 511.95 | 02-FEB-06:00 | 1202.50 | 11-MAY-13:10 |
Fans:Electricity | 515.20 | 10719.45 | 05-JAN-08:10 | 35587.11 | 07-SEP-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 720.59 | 12378.47 | 14-NOV-15:00 | 44617.75 | 03-AUG-21:10 |
ExteriorEquipment:Electricity | 640.80 | 9445.83 | 02-JAN-02:20 | 39169.97 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 17-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
ElectricityPurchased:Plant | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
Cogeneration:ElectricityPurchased | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
General:Cogeneration:ElectricityPurchased | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
ElectricityNet:Plant | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
Cogeneration:ElectricityNet | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
General:Cogeneration:ElectricityNet | 4966.20 | 70900.43 | 29-MAR-03:00 | 418492.64 | 26-JUL-19:40 |
General:Fans:Electricity | 515.20 | 10719.45 | 05-JAN-08:10 | 35587.11 | 07-SEP-22:00 |
ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 183.63 | 0.00 | 24-FEB-11:40 | 9938.94 | 06-JAN-10:40 |
General:HeatRecovery:Electricity | 183.63 | 0.00 | 24-FEB-11:40 | 9938.94 | 06-JAN-10:40 |
WaterSystems:Electricity | 90.75 | 1086.56 | 05-MAY-00:30 | 4745.15 | 03-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 05-MAY-00:30 | 4745.15 | 03-FEB-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 763.03 | 0.00 | 01-JAN-00:10 | 218436.64 | 04-AUG-15:20 |
General:Cooling:Electricity | 763.03 | 0.00 | 01-JAN-00:10 | 218436.64 | 04-AUG-15:20 |
Pumps:Electricity | 77.99 | 48.92 | 25-OCT-14:40 | 5071.46 | 30-JAN-16:30 |
General:Pumps:Electricity | 77.99 | 48.92 | 25-OCT-14:40 | 5071.46 | 30-JAN-16:30 |
WIRED_LTG_ELECTRICITY | 27.51 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 7561.69 | 29270.80 | 05-MAY-01:10 | 1129040.87 | 02-FEB-21:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 5772.85 | 15908.90 | 17-APR-15:10 | 1053917.11 | 02-FEB-21:50 |
WaterSystems:NaturalGas | 3365.37 | 15908.90 | 04-JAN-16:10 | 305638.84 | 16-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3365.37 | 15908.90 | 04-JAN-16:10 | 305638.84 | 16-FEB-21:40 |
Heating:NaturalGas | 2407.48 | 0.00 | 19-MAR-12:30 | 804620.23 | 02-FEB-06:00 |
Boiler:Heating:NaturalGas | 2407.48 | 0.00 | 19-MAR-12:30 | 804620.23 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2334.93 | 0.00 | 01-JAN-00:10 | 702874.44 | 26-JUL-18:30 |
PlantLoopCoolingDemand:HVAC | 2334.93 | 0.00 | 01-JAN-00:10 | 702874.44 | 26-JUL-18:30 |
CoolingCoils:PlantLoopCoolingDemand | 2334.93 | 0.00 | 01-JAN-00:10 | 702874.44 | 26-JUL-18:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 19-JAN-02:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 19-JAN-02:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 21957.14 | 140806.14 | 06-JUN-11:30 | 2987472.23 | 26-JUL-18:30 |
EnergyTransfer:Building | 4886.84 | 64951.96 | 06-FEB-11:10 | 344926.44 | 26-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 702.38 | 8261.15 | 05-FEB-04:00 | 36625.53 | 02-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.94 | 1376.33 | 02-FEB-04:00 | 10373.36 | 12-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.47 | 688.16 | 02-FEB-04:00 | 5186.68 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 90.47 | 688.16 | 02-FEB-04:00 | 5186.68 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.47 | 688.16 | 02-FEB-04:00 | 5186.68 | 12-SEP-06:20 |
EnergyTransfer:Plant | 8239.51 | 19020.37 | 20-OCT-01:10 | 1644421.75 | 26-JUL-18:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.55 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.92 | 485.85 | 02-FEB-06:00 | 2557.51 | 11-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 389.57 | 81.22 | 05-FEB-18:10 | 36175.77 | 26-NOV-06:40 |
Heating:EnergyTransfer | 388.65 | 0.00 | 12-JAN-18:30 | 126386.57 | 12-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.17 | 0.00 | 01-JAN-00:10 | 5515.56 | 04-FEB-11:30 |
General:Heating:EnergyTransfer | 388.65 | 0.00 | 12-JAN-18:30 | 126386.57 | 12-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.17 | 0.00 | 01-JAN-00:10 | 5515.56 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 4407.72 | 13923.97 | 04-FEB-11:20 | 341304.15 | 26-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 389.39 | 0.00 | 04-FEB-11:20 | 36175.77 | 26-NOV-06:40 |
General:Cooling:EnergyTransfer | 4407.72 | 13923.97 | 04-FEB-11:20 | 341304.15 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 389.39 | 0.00 | 04-FEB-11:20 | 36175.77 | 26-NOV-06:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.50 | 0.00 | 06-DEC-19:00 | 4630.86 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 5.16 | 0.00 | 01-JAN-10:30 | 2737.65 | 20-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 5.16 | 0.00 | 01-JAN-10:30 | 2737.65 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.33 | 0.00 | 01-JAN-00:10 | 4630.86 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.33 | 0.00 | 01-JAN-00:10 | 4630.86 | 07-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.78 | 0.09 | 09-DEC-12:00 | 2023.34 | 30-JUN-20:50 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 1200.48 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 1200.48 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.67 | 0.00 | 06-JAN-10:40 | 2023.34 | 30-JUN-20:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.67 | 0.00 | 06-JAN-10:40 | 2023.34 | 30-JUN-20:50 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.22 | 0.00 | 27-FEB-23:20 | 1901.83 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.63 | 0.00 | 01-JAN-00:10 | 1901.83 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.63 | 0.00 | 01-JAN-00:10 | 1901.83 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.59 | 0.00 | 01-JAN-02:10 | 1557.42 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.59 | 0.00 | 01-JAN-02:10 | 1557.42 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.10 | 0.00 | 22-NOV-23:40 | 1213.95 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.80 | 0.00 | 11-JAN-21:30 | 1213.95 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.80 | 0.00 | 11-JAN-21:30 | 1213.95 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.29 | 0.00 | 01-JAN-00:10 | 706.84 | 30-JUN-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.29 | 0.00 | 01-JAN-00:10 | 706.84 | 30-JUN-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.83 | 3797.48 | 04-FEB-11:20 | 38841.68 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 433.74 | 04-FEB-11:20 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 433.74 | 04-FEB-11:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.83 | 3363.75 | 04-FEB-11:20 | 38841.68 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.83 | 3363.75 | 04-FEB-11:20 | 38841.68 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 211.14 | 1.09 | 23-DEC-14:30 | 15128.43 | 07-SEP-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.50 | 0.00 | 01-JAN-00:10 | 5517.31 | 20-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.50 | 0.00 | 01-JAN-00:10 | 5517.31 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.64 | 0.00 | 07-JAN-16:10 | 15128.43 | 07-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.64 | 0.00 | 07-JAN-16:10 | 15128.43 | 07-SEP-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 721.91 | 7.28 | 26-NOV-14:00 | 40712.38 | 07-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.49 | 0.00 | 01-JAN-00:10 | 18526.89 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.49 | 0.00 | 01-JAN-00:10 | 18526.89 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 721.42 | 0.00 | 06-JAN-10:50 | 40712.38 | 07-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 721.42 | 0.00 | 06-JAN-10:50 | 40712.38 | 07-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 75.50 | 0.00 | 01-JAN-08:10 | 12352.12 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 34.07 | 0.00 | 01-JAN-08:10 | 8313.02 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 34.07 | 0.00 | 01-JAN-08:10 | 8313.02 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.42 | 0.00 | 01-JAN-00:10 | 12352.12 | 06-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.42 | 0.00 | 01-JAN-00:10 | 12352.12 | 06-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 70.49 | 0.00 | 01-JAN-08:10 | 13531.83 | 16-JUN-17:00 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.34 | 0.00 | 01-JAN-08:10 | 8330.20 | 04-FEB-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.34 | 0.00 | 01-JAN-08:10 | 8330.20 | 04-FEB-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.15 | 0.00 | 01-JAN-00:10 | 13531.83 | 16-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.15 | 0.00 | 01-JAN-00:10 | 13531.83 | 16-JUN-17:00 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 246.51 | 0.00 | 01-JAN-08:10 | 55217.75 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 24.20 | 0.00 | 01-JAN-08:10 | 30039.43 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 24.20 | 0.00 | 01-JAN-08:10 | 30039.43 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 222.31 | 0.00 | 01-JAN-00:10 | 55217.75 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 222.31 | 0.00 | 01-JAN-00:10 | 55217.75 | 07-SEP-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 394.16 | 0.00 | 01-JAN-08:10 | 68938.74 | 26-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 123.76 | 0.00 | 01-JAN-08:10 | 47803.65 | 03-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 123.76 | 0.00 | 01-JAN-08:10 | 47803.65 | 03-FEB-11:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 270.40 | 0.00 | 01-JAN-00:10 | 68938.74 | 26-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 270.40 | 0.00 | 01-JAN-00:10 | 68938.74 | 26-JUN-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 74.59 | 0.00 | 01-JAN-08:10 | 11296.15 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.05 | 0.00 | 01-JAN-08:10 | 8122.58 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.05 | 0.00 | 01-JAN-08:10 | 8122.58 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 40.55 | 0.00 | 01-JAN-00:10 | 11296.15 | 02-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 40.55 | 0.00 | 01-JAN-00:10 | 11296.15 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 70.16 | 0.00 | 01-JAN-08:10 | 12777.76 | 09-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.35 | 0.00 | 01-JAN-08:10 | 8642.13 | 03-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.35 | 0.00 | 01-JAN-08:10 | 8642.13 | 03-FEB-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.81 | 0.00 | 01-JAN-00:10 | 12777.76 | 09-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.81 | 0.00 | 01-JAN-00:10 | 12777.76 | 09-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.67 | 0.09 | 24-JAN-23:10 | 10433.18 | 02-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 9.17 | 0.00 | 01-JAN-00:10 | 9820.64 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 9.17 | 0.00 | 01-JAN-00:10 | 9820.64 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 154.50 | 0.00 | 01-JAN-08:10 | 10433.18 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 154.50 | 0.00 | 01-JAN-08:10 | 10433.18 | 02-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.24 | 0.00 | 01-JAN-08:10 | 3339.45 | 04-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.95 | 0.00 | 01-JAN-08:10 | 2454.11 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.95 | 0.00 | 01-JAN-08:10 | 2454.11 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.29 | 0.00 | 01-JAN-00:10 | 3339.45 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.29 | 0.00 | 01-JAN-00:10 | 3339.45 | 04-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.51 | 0.00 | 01-JAN-08:10 | 3724.53 | 16-JUN-17:00 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.87 | 0.00 | 01-JAN-08:10 | 2646.47 | 02-FEB-08:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.87 | 0.00 | 01-JAN-08:10 | 2646.47 | 02-FEB-08:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.64 | 0.00 | 01-JAN-00:10 | 3724.53 | 16-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.64 | 0.00 | 01-JAN-00:10 | 3724.53 | 16-JUN-17:00 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 97.72 | 0.00 | 01-JAN-08:10 | 17005.23 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 35.50 | 0.00 | 01-JAN-08:10 | 11445.36 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 35.50 | 0.00 | 01-JAN-08:10 | 11445.36 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.23 | 0.00 | 01-JAN-00:10 | 17005.23 | 06-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.23 | 0.00 | 01-JAN-00:10 | 17005.23 | 06-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 408.48 | 2.75 | 04-FEB-14:10 | 23011.00 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4564.94 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4564.94 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 408.45 | 0.00 | 31-JAN-11:40 | 23011.00 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 408.45 | 0.00 | 31-JAN-11:40 | 23011.00 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 448.21 | 166.71 | 04-FEB-12:30 | 24232.55 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4119.67 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4119.67 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 448.19 | 0.00 | 31-JAN-11:40 | 24232.55 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 448.19 | 0.00 | 31-JAN-11:40 | 24232.55 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.91 | 6278.40 | 05-FEB-04:00 | 31557.56 | 02-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 611.91 | 6278.40 | 05-FEB-04:00 | 31557.56 | 02-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.18 | 0.49 | 10-JAN-20:40 | 7116.17 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 9.48 | 0.00 | 01-JAN-00:10 | 7116.17 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 9.48 | 0.00 | 01-JAN-00:10 | 7116.17 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.70 | 0.00 | 01-JAN-00:30 | 6767.32 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.70 | 0.00 | 01-JAN-00:30 | 6767.32 | 04-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 2615.55 | 9886.54 | 24-AUG-01:20 | 701402.10 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.53 | 9886.54 | 24-AUG-01:20 | 63729.98 | 17-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 847.53 | 9886.54 | 24-AUG-01:20 | 63729.98 | 17-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 847.53 | 9886.54 | 24-AUG-01:20 | 63729.98 | 17-FEB-07:10 |
EnergyTransfer:HVAC | 8830.79 | 467.94 | 06-JUN-11:40 | 1033366.61 | 26-JUL-18:30 |
HeatingCoils:EnergyTransfer | 1768.03 | 0.00 | 19-MAR-12:30 | 647743.59 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1768.03 | 0.00 | 19-MAR-12:30 | 647743.59 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1768.03 | 0.00 | 19-MAR-12:30 | 647743.59 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2334.93 | 0.00 | 01-JAN-00:10 | 702874.44 | 26-JUL-18:30 |
HeatRecoveryForHeating:EnergyTransfer | 4505.60 | 0.00 | 05-JAN-08:00 | 558138.05 | 08-DEC-21:20 |
HeatRecoveryForCooling:EnergyTransfer | 222.23 | 0.00 | 01-JAN-00:10 | 336530.33 | 26-JUL-19:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 847.53 | 9886.54 | 24-AUG-01:20 | 63729.98 | 17-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 847.53 | 9886.54 | 24-AUG-01:20 | 63729.98 | 17-FEB-07:10 |
Boilers:EnergyTransfer | 1755.42 | 0.00 | 19-MAR-12:30 | 645301.33 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2391.53 | 0.00 | 01-JAN-00:10 | 704679.13 | 26-JUL-18:30 |
HeatRejection:EnergyTransfer | 3154.56 | 0.00 | 01-JAN-00:10 | 903827.64 | 26-JUL-18:30 |
General:HeatRejection:EnergyTransfer | 3154.56 | 0.00 | 01-JAN-00:10 | 903827.64 | 26-JUL-18:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.173 | -389.396 | 0.000 | 0.000 | 141.944 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.120 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 5.163 | -33.334 | 0.000 | 0.000 | 15.753 | 7.307 | 10.186 | 25.372 | 0.000 | 0.089 | 0.000 | 0.000 | -14.081 | 0.000 | -6.019 | -10.435 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.116 | -30.666 | 0.000 | 0.000 | 17.264 | 8.462 | 11.795 | 0.000 | 0.000 | 0.035 | 0.000 | 0.000 | 0.000 | 0.000 | -2.431 | -4.576 |
MECH_FLR_1 | 0.000 | 0.000 | 2.631 | -17.586 | 0.000 | 0.000 | 3.768 | 8.366 | 12.471 | 0.000 | 0.000 | 0.086 | 0.000 | 0.000 | 0.000 | 0.000 | -5.587 | -4.150 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.804 | -9.292 | 0.000 | 0.000 | 2.927 | 3.079 | 3.598 | 0.000 | 0.000 | 0.052 | 0.025 | 0.000 | 0.000 | 0.000 | -3.193 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.001 | -585.832 | 0.000 | 0.000 | 11.361 | 3.975 | 658.131 | 0.000 | 0.000 | 0.133 | 0.000 | 0.000 | 0.000 | 0.000 | -8.081 | -79.688 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.503 | -210.641 | 0.000 | 0.000 | 196.576 | 13.979 | 14.341 | 70.556 | 0.000 | 0.188 | 0.000 | 0.000 | -41.245 | 0.000 | -13.887 | -30.369 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.486 | -721.427 | 0.000 | 0.000 | 569.726 | 109.788 | 148.998 | 93.187 | 0.000 | 0.571 | 0.000 | 0.000 | -55.924 | 0.000 | -40.482 | -104.922 |
ROOM_1_FLR_3 | 39.601 | -35.725 | 0.000 | -11.227 | 0.000 | 0.000 | 9.756 | 9.244 | 10.478 | 47.684 | 0.000 | 0.399 | 0.000 | 0.000 | -32.899 | 0.000 | -14.485 | -22.827 |
ROOM_2_FLR_3 | 46.106 | -24.205 | 0.000 | -11.716 | 0.000 | 0.000 | 9.628 | 9.243 | 10.477 | 33.569 | 0.000 | 0.302 | 0.000 | 0.000 | -34.913 | 0.000 | -14.862 | -23.628 |
ROOM_3_MULT19_FLR_3 | 24.191 | -210.322 | 0.011 | -11.991 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 288.931 | 0.000 | 0.286 | 0.000 | 0.000 | -193.600 | 0.000 | -82.131 | -120.756 |
ROOM_4_MULT19_FLR_3 | 184.390 | -175.247 | 0.000 | -155.764 | 0.000 | 0.000 | 183.946 | 110.415 | 195.050 | 84.829 | 0.000 | 1.941 | 0.000 | 0.000 | -197.927 | 0.000 | -90.204 | -141.429 |
ROOM_5_FLR_3 | 39.529 | -34.799 | 0.000 | -11.224 | 0.000 | 0.000 | 9.754 | 9.244 | 10.478 | 46.451 | 0.000 | 0.399 | 0.000 | 0.000 | -32.333 | 0.000 | -14.511 | -22.988 |
ROOM_6_FLR_3 | 46.118 | -23.930 | 0.000 | -11.644 | 0.000 | 0.000 | 9.660 | 9.243 | 10.477 | 32.151 | 0.000 | 0.302 | 0.000 | 0.000 | -34.087 | 0.000 | -14.933 | -23.357 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 9.166 | -154.501 | 0.000 | 0.000 | 119.852 | 91.336 | 0.000 | 42.363 | 0.000 | 0.267 | 0.000 | 0.000 | -42.175 | 0.000 | -17.157 | -49.150 |
ROOM_1_FLR_6 | 13.428 | -8.963 | 0.000 | -2.802 | 0.000 | 0.000 | 2.442 | 2.311 | 2.620 | 11.855 | 0.000 | 0.102 | 0.000 | 0.000 | -8.208 | 0.000 | -3.654 | -9.131 |
ROOM_2_FLR_6 | 15.382 | -6.216 | 0.000 | -2.933 | 0.000 | 0.000 | 2.406 | 2.311 | 2.619 | 8.341 | 0.000 | 0.075 | 0.000 | 0.000 | -8.731 | 0.000 | -3.741 | -9.513 |
ROOM_3_MULT9_FLR_6 | 43.298 | -51.861 | 0.000 | -18.165 | 0.000 | 0.000 | 21.875 | 13.076 | 23.098 | 65.427 | 0.000 | 0.582 | 0.000 | 0.000 | -38.127 | 0.000 | -17.885 | -41.318 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.030 | -408.458 | 0.000 | 0.000 | 321.164 | 30.666 | 175.857 | 8.707 | 0.000 | 0.104 | 0.000 | 0.000 | -25.695 | 0.000 | -9.558 | -92.817 |
DINING_FLR_6 | 0.000 | 0.000 | 0.018 | -448.196 | 0.000 | 0.000 | 319.446 | 30.666 | 175.857 | 8.516 | 0.000 | 0.103 | 0.000 | 0.000 | -26.302 | 0.000 | -9.630 | -50.478 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -611.895 | 0.000 | 0.000 | 28.718 | 12.972 | 550.372 | 21.715 | 0.000 | 0.092 | 23.643 | 0.000 | -16.977 | 0.000 | -8.641 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 9.477 | -71.702 | 0.000 | 0.000 | 31.752 | 24.166 | 0.000 | 20.869 | 0.000 | 0.098 | 11.769 | 0.000 | -18.831 | 0.000 | -7.599 | -0.000 |
Total Facility | 452.043 | -571.268 | 30.578 | -3930.393 | 0.000 | 0.000 | 2029.717 | 781.531 | 2365.005 | 910.522 | 0.000 | 6.207 | 35.438 | 0.000 | -822.056 | 0.000 | -388.670 | -898.657 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-NOV-07:07 | 0.00 | 0.00 | 0.00 | -36750.98 | 0.00 | 0.00 | 6163.61 | 5862.42 | 5069.75 | 0.00 | 0.00 | 0.00 | 19655.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | -4629.45 | 0.00 | 0.00 | 150.61 | 166.00 | 252.59 | 5800.13 | 0.00 | 84.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1824.27 |
RETAIL_2_FLR_1 | 30-JUN-20:50 | 0.00 | 0.00 | 0.00 | -2023.39 | 0.00 | 0.00 | 697.59 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.06 | -34.41 |
MECH_FLR_1 | 30-JUN-19:53 | 0.00 | 0.00 | 0.00 | -1558.57 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.22 | -86.92 |
STORAGE_FLR_1 | 30-JUN-10:33 | 0.00 | 0.00 | 0.00 | -708.91 | 0.00 | 0.00 | 29.20 | 69.95 | 89.22 | 0.00 | 0.00 | 25.64 | 494.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-JAN-21:42 | 0.00 | 0.00 | 0.00 | -39488.67 | 0.00 | 0.00 | 505.17 | 288.96 | 41967.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -776.21 | -2497.08 |
CAFE_FLR_1 | 07-SEP-12:50 | 0.00 | 0.00 | 0.00 | -15124.02 | 0.00 | 0.00 | 1979.18 | 103.98 | 355.63 | 16529.32 | 0.00 | 182.22 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4026.30 |
LOBBY_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -47656.42 | 0.00 | 0.00 | 31418.43 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 22759.54 | 0.00 | -6987.76 | 0.00 | -3757.19 | 0.00 |
ROOM_1_FLR_3 | 21-MAY-18:01 | 0.00 | -16158.47 | 0.00 | -544.99 | 0.00 | 0.00 | 283.22 | 711.53 | 484.65 | 6640.13 | 0.00 | 0.00 | 9263.20 | 0.00 | -0.00 | 0.00 | -679.27 | 0.00 |
ROOM_2_FLR_3 | 20-MAY-18:41 | 0.00 | -17883.11 | 0.00 | -644.99 | 0.00 | 0.00 | 243.77 | 711.45 | 484.60 | 2815.66 | 0.00 | 0.00 | 14564.86 | 0.00 | -0.00 | 0.00 | -292.23 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-SEP-13:00 | 0.00 | -55218.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 69375.79 | 0.00 | 672.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19561.54 |
ROOM_4_MULT19_FLR_3 | 06-MAY-19:31 | 0.00 | -86850.06 | 0.00 | -7199.16 | 0.00 | 0.00 | 5396.73 | 8498.53 | 12159.85 | 0.00 | 0.00 | 0.00 | 75263.69 | 0.00 | -5878.49 | 0.00 | -1391.09 | 0.00 |
ROOM_5_FLR_3 | 26-APR-08:61 | 0.00 | -14632.37 | 0.00 | -490.73 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 10220.01 | 0.00 | 0.00 | 4613.25 | 0.00 | -0.00 | 0.00 | -563.42 | 0.00 |
ROOM_6_FLR_3 | 09-JUN-08:32 | 0.00 | -15413.58 | 0.00 | -1002.55 | 0.00 | 0.00 | 58.86 | 313.04 | 452.99 | 10032.30 | 0.00 | 0.00 | 5660.18 | 0.00 | -0.00 | 0.00 | -101.24 | 0.00 |
CORRIDOR_FLR_3 | 02-JUL-10:33 | 0.00 | 0.00 | 0.00 | -10458.28 | 0.00 | 0.00 | 1796.33 | 2489.76 | 0.00 | 5905.88 | 0.00 | 128.93 | 137.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 21-MAY-18:01 | 0.00 | -4206.68 | 0.00 | -136.50 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 1647.14 | 0.00 | 0.00 | 2510.94 | 0.00 | -0.00 | 0.00 | -184.76 | 0.00 |
ROOM_2_FLR_6 | 20-MAY-18:41 | 0.00 | -4686.48 | 0.00 | -164.43 | 0.00 | 0.00 | 60.13 | 177.86 | 121.15 | 683.29 | 0.00 | 0.00 | 3883.14 | 0.00 | -0.00 | 0.00 | -74.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:02 | 0.00 | -18315.21 | 0.00 | -2737.24 | 0.00 | 0.00 | 540.92 | 281.79 | 441.28 | 3369.27 | 0.00 | 0.00 | 18090.86 | 0.00 | -0.00 | 0.00 | -1671.68 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -29241.46 | 0.00 | 0.00 | 17470.20 | 498.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 12844.64 | 0.00 | -2953.76 | 0.00 | -866.93 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -30984.42 | 0.00 | 0.00 | 17210.38 | 498.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 14890.61 | 0.00 | -2992.35 | 0.00 | -871.52 | 0.00 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31561.92 | 0.00 | 0.00 | 464.23 | 353.60 | 24259.91 | 3843.94 | 0.00 | 49.78 | 2590.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-AUG-15:03 | 0.00 | 0.00 | 0.00 | -6770.47 | 0.00 | 0.00 | 771.15 | 548.96 | 0.00 | 2621.40 | 0.00 | 130.81 | 2698.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -176153.63 | 0.00 | -201227.79 | 0.00 | 0.00 | 74831.59 | 52987.32 | 120482.43 | 63270.51 | 0.00 | 3708.44 | 62101.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:22 | 0.00 | 0.00 | 6108.98 | 0.00 | 0.00 | 0.00 | 3255.91 | 3664.03 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16577.75 |
RETAIL_1_FLR_1 | 20-JAN-07:52 | 0.00 | 0.00 | 2894.06 | 0.00 | 0.00 | 0.00 | 414.22 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1483.22 | 0.00 | -542.14 | -2047.93 |
RETAIL_2_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1268.66 | 0.00 | 0.00 | 0.00 | 380.16 | 192.23 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -199.26 | -1934.29 |
MECH_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1921.89 | 0.00 | 0.00 | 0.00 | 83.14 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -460.03 | -2044.33 |
STORAGE_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1225.56 | 0.00 | 0.00 | 0.00 | 64.50 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -263.04 | -1186.19 |
LAUNDRY_FLR_1 | 04-FEB-11:11 | 0.00 | 0.00 | 3610.20 | 0.00 | 0.00 | 0.00 | 253.97 | 90.30 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -662.75 | -19612.54 |
CAFE_FLR_1 | 20-JAN-07:52 | 0.00 | 0.00 | 6474.90 | 0.00 | 0.00 | 0.00 | 5154.02 | 822.41 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4319.90 | 0.00 | -1237.93 | -7503.15 |
LOBBY_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 20653.76 | 0.00 | 0.00 | 0.00 | 12178.86 | 2270.59 | 3694.97 | 23947.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3378.32 | -59367.78 |
ROOM_1_FLR_3 | 09-DEC-16:13 | 8563.06 | 344.14 | 0.00 | -344.14 | 0.00 | 0.00 | 149.63 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3409.75 | 0.00 | -1205.78 | -4553.21 |
ROOM_2_FLR_3 | 03-FEB-08:62 | 9102.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.69 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4161.87 | 0.00 | -1721.63 | -4221.30 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 30038.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22411.53 | 0.00 | -7094.19 | -4800.80 |
ROOM_4_MULT19_FLR_3 | 03-FEB-11:13 | 51251.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2068.77 | 2379.59 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13187.47 | 0.00 | -8147.98 | -36718.20 |
ROOM_5_FLR_3 | 09-DEC-16:13 | 8333.25 | 332.65 | 0.00 | -332.65 | 0.00 | 0.00 | 151.42 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3613.84 | 0.00 | -1200.88 | -4126.01 |
ROOM_6_FLR_3 | 01-FEB-18:04 | 9015.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.41 | 476.67 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4383.20 | 0.00 | -1469.70 | -4425.28 |
CORRIDOR_FLR_3 | 04-FEB-11:22 | 0.00 | 0.00 | 10040.59 | 0.00 | 0.00 | 0.00 | 2402.69 | 2074.80 | 0.00 | 7338.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1528.19 | -20328.56 |
ROOM_1_FLR_6 | 04-FEB-08:03 | 2713.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.10 | 99.61 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -954.15 | 0.00 | -398.03 | -1768.30 |
ROOM_2_FLR_6 | 01-FEB-08:03 | 2702.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1101.30 | 0.00 | -411.28 | -1438.29 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 11709.35 | 530.50 | 0.00 | -530.50 | 0.00 | 0.00 | 340.89 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4018.14 | 0.00 | -1383.54 | -7468.40 |
BANQUET_FLR_6 | 04-FEB-11:11 | 0.00 | 0.00 | 5943.89 | 0.00 | 0.00 | 0.00 | 7214.97 | 498.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1314.39 | 0.00 | -770.58 | -18319.79 |
DINING_FLR_6 | 04-FEB-11:11 | 0.00 | 0.00 | 5745.77 | 0.00 | 0.00 | 0.00 | 7168.05 | 498.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.52 | 0.00 | -774.98 | -18046.23 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 7254.43 | 0.00 | 0.00 | 0.00 | 669.23 | 548.96 | 0.00 | 4259.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -649.89 | -12082.30 |
Total Facility | 20-JAN-09:02 | 57595.95 | 55575.42 | 24091.99 | -55575.42 | 0.00 | 0.00 | 24735.38 | 26564.80 | 88178.92 | 1788.80 | 0.00 | 0.00 | 0.00 | 0.00 | -30817.51 | 0.00 | -31727.09 | -160411.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.0964 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.9694 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6637 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6637 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5722 | 2.5722 | 1.2990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4014 | 0.4014 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2353 | 0.2353 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1880 | 0.1880 | 0.0950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1110 | 0.1110 | 0.0561 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4098 | 3.4098 | 1.7220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6595 | 1.6595 | 0.8380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1415 | 5.1415 | 2.5964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6321 | 1.6321 | 0.8242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2334 | 2.2334 | 1.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3411 | 2.3411 | 1.1822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3696 | 2.3696 | 1.1967 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8016 | 0.8016 | 0.4048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.0964 | 22.9694 | 23.0964 | 11.6637 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2990 | 1.2990 | 1.2990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2027 | 0.2027 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1188 | 0.1188 | 0.1188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0950 | 0.0950 | 0.0950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0561 | 0.0561 | 0.0561 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7220 | 1.7220 | 1.7220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8380 | 0.8380 | 0.8380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5964 | 2.5964 | 2.5964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8242 | 0.8242 | 0.8242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1278 | 1.1278 | 1.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1822 | 1.1822 | 1.1822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1967 | 1.1967 | 1.1967 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4048 | 0.4048 | 0.4048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6637 | 11.6637 | 11.6637 | 11.6637 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 296.50 |
Number of hours cooling loads not met | 37.33 |
Number of hours not met | 333.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2407.48 | 804620.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 763.03 | 218436.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.53 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.69 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 515.20 | 35587.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 77.99 | 5071.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 183.63 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4745.15 | 3365.37 | 305638.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.30 | 1894.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.01 | 1202.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.58 | 4966.20 |
Natural Gas | 1788.84 | 7561.69 |
Additional | 0.00 | 0.00 |
Total | 3508.42 | 12527.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.89 |
Space Heating | 0.00 |
Space Cooling | 67.26 |
Fans (All) | 45.41 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 437.73 |
Subtotal | 437.73 |
Natural Gas [MJ/m2] | |
Space Heating | 212.20 |
Service Water Heating | 296.63 |
Miscellaneous (All) | 666.51 |
Subtotal | 666.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.24 |
Space Heating | 19.22 |
Space Cooling | 6.09 |
Fans (All) | 4.11 |
Service Water Heating | 27.59 |
Receptacle Equipment | 27.51 |
Miscellaneous | 9.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8690.33 | 69.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8167.50 | 592.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8654.83 | 105.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8167.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 592.50 | 0.00 | 0.00 | 0.00 |
Average | 8723.32 | 36.68 | 0.00 | 0.00 | 0.00 |
Sum | 191913.00 | 807.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4131.50 | 22.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4111.83 | 42.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 42.17 | 0.00 | 0.00 | 0.00 |
Average | 288884.11 | 2.94 | 0.00 | 0.00 | 0.00 |
Sum | 6355450.33 | 64.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8614.17 | 145.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8212.50 | 547.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8208.33 | 551.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8528.17 | 231.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7816.50 | 943.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8584.33 | 175.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8463.83 | 296.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8163.50 | 596.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8217.33 | 542.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8711.67 | 48.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7816.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 943.50 | 0.00 | 0.00 | 0.00 |
Average | 8571.89 | 188.11 | 0.00 | 0.00 | 0.00 |
Sum | 188581.50 | 4138.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 57596.33 | 1559.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 643715.33 | 66701.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1922248.00 | 193181.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4050.83 | 103.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4136.17 | 17.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4118.17 | 35.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4007.67 | 146.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1124024.00 | 121691.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1133574.33 | 112140.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107899.67 | 369.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1922248.00 | 193181.00 | 0.00 | 0.00 | 0.00 |
Average | 266344.02 | 22543.02 | 0.00 | 0.00 | 0.00 |
Sum | 5859568.50 | 495946.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:46:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341166E+11 | 34937.96 | 19-JAN-04:40 | -26.8 | -27.1 | 0.727277E+10 | 4836.90 | 04-JAN-22:10 | -26.8 | -27.1 |
February | 0.274381E+11 | 31071.01 | 02-FEB-06:02 | -36.7 | -36.8 | 0.590044E+10 | 4628.59 | 28-FEB-22:10 | -14.5 | -15.2 |
March | 0.278146E+11 | 12739.47 | 19-MAR-10:33 | 13.87 | 10.01 | 0.712207E+10 | 4567.97 | 01-MAR-22:10 | 13.87 | 10.01 |
April | 0.259211E+11 | 13143.78 | 16-APR-10:33 | 23.33 | 18.86 | 0.660412E+10 | 4275.75 | 21-APR-21:10 | -0.1 | -0.4 |
May | 0.285426E+11 | 13743.38 | 29-MAY-10:33 | 24.63 | 18.66 | 0.700795E+10 | 4378.90 | 19-MAY-22:10 | 24.63 | 18.66 |
June | 0.304029E+11 | 14783.36 | 25-JUN-10:33 | 28.87 | 21.94 | 0.716289E+10 | 4628.13 | 15-JUN-22:10 | 28.87 | 21.94 |
July | 0.336527E+11 | 15551.07 | 30-JUL-10:33 | 24.63 | 19.89 | 0.773209E+10 | 4837.07 | 21-JUL-22:10 | 24.63 | 19.89 |
August | 0.362216E+11 | 18602.45 | 25-AUG-21:00 | 19.40 | 17.91 | 0.808544E+10 | 4837.09 | 07-AUG-22:10 | 19.40 | 17.91 |
September | 0.367795E+11 | 20634.92 | 13-SEP-20:55 | 13.90 | 11.61 | 0.791142E+10 | 4837.35 | 12-SEP-22:10 | 13.90 | 11.61 |
October | 0.380160E+11 | 21050.56 | 31-OCT-21:00 | -1.1 | -2.8 | 0.819563E+10 | 4837.05 | 13-OCT-23:19 | -1.1 | -2.8 |
November | 0.360438E+11 | 36751.03 | 26-NOV-07:07 | -28.3 | -28.5 | 0.783671E+10 | 4837.07 | 22-NOV-00:20 | -28.3 | -28.5 |
December | 0.344453E+11 | 18760.79 | 07-DEC-22:00 | -7.8 | -9.7 | 0.808568E+10 | 4837.07 | 08-DEC-00:20 | -6.8 | -8.6 |
Annual Sum or Average | 0.389395E+12 | 0.889172E+11 | ||||||||
Minimum of Months | 0.259211E+11 | 12739.47 | -36.7 | -36.8 | 0.590044E+10 | 4275.75 | -28.3 | -28.5 | ||
Maximum of Months | 0.380160E+11 | 36751.03 | 28.87 | 21.94 | 0.819563E+10 | 4837.35 | 28.87 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471245E+09 | 2063.87 | 12-JAN-12:40 | 2.03 | 0.42 | 0.589754E+09 | 364.18 | 18-JAN-23:30 | -20.0 | -20.2 |
February | 0.818214E+09 | 2897.09 | 08-FEB-13:30 | 2.50 | 1.29 | 0.518178E+09 | 365.97 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.163891E+10 | 2572.75 | 24-MAR-13:10 | 12.38 | 6.48 | 0.633129E+09 | 393.78 | 23-MAR-21:30 | 12.38 | 6.48 |
April | 0.257077E+10 | 3754.00 | 15-APR-13:30 | 28.85 | 20.45 | 0.629936E+09 | 452.87 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.388386E+10 | 2751.91 | 31-MAY-13:30 | 29.70 | 19.57 | 0.660082E+09 | 468.01 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.443317E+10 | 3162.11 | 30-JUN-13:00 | 29.40 | 21.96 | 0.685797E+09 | 487.68 | 26-JUN-21:19 | 29.40 | 21.96 |
July | 0.500957E+10 | 3301.67 | 30-JUL-12:00 | 26.70 | 21.51 | 0.728996E+09 | 479.18 | 03-JUL-21:30 | 26.70 | 21.51 |
August | 0.504961E+10 | 3615.80 | 29-AUG-13:30 | 23.60 | 16.39 | 0.730223E+09 | 482.24 | 02-AUG-21:30 | 23.60 | 16.39 |
September | 0.436053E+10 | 4630.86 | 07-SEP-13:00 | 31.70 | 18.06 | 0.673607E+09 | 491.75 | 07-SEP-21:30 | 21.70 | 16.25 |
October | 0.307582E+10 | 4206.61 | 20-OCT-12:50 | 21.68 | 12.55 | 0.646121E+09 | 442.44 | 20-OCT-21:30 | 13.90 | 9.49 |
November | 0.136975E+10 | 3950.44 | 04-NOV-12:50 | 13.72 | 6.77 | 0.602099E+09 | 393.48 | 03-NOV-21:30 | 13.72 | 6.77 |
December | 0.652226E+09 | 3036.53 | 03-DEC-13:00 | 5.60 | 2.41 | 0.623605E+09 | 364.17 | 11-DEC-04:30 | -21.9 | -22.4 |
Annual Sum or Average | 0.333337E+11 | 0.772153E+10 | ||||||||
Minimum of Months | 0.471245E+09 | 2063.87 | 2.03 | 0.42 | 0.518178E+09 | 364.17 | -21.9 | -22.4 | ||
Maximum of Months | 0.504961E+10 | 4630.86 | 31.70 | 21.96 | 0.730223E+09 | 491.75 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166351E+10 | 1430.96 | 05-JAN-21:13 | -23.5 | -23.8 | 0.711592E+09 | 509.09 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.181533E+10 | 1482.97 | 02-FEB-06:00 | -36.7 | -36.8 | 0.637424E+09 | 525.01 | 24-FEB-22:30 | 1.40 | 0.88 |
March | 0.228433E+10 | 1222.82 | 24-MAR-20:00 | 3.90 | 2.01 | 0.800148E+09 | 549.88 | 24-MAR-21:30 | 1.70 | 0.37 |
April | 0.253014E+10 | 1680.51 | 18-APR-21:00 | 16.70 | 13.63 | 0.819181E+09 | 569.55 | 14-APR-21:30 | 16.70 | 13.63 |
May | 0.290683E+10 | 1819.56 | 31-MAY-20:55 | 22.20 | 17.24 | 0.894184E+09 | 569.55 | 30-MAY-22:10 | 22.20 | 17.24 |
June | 0.312395E+10 | 2023.34 | 30-JUN-20:50 | 22.38 | 17.30 | 0.899070E+09 | 569.55 | 20-JUN-22:10 | 22.38 | 17.30 |
July | 0.337647E+10 | 1995.34 | 03-JUL-21:00 | 24.40 | 22.86 | 0.944015E+09 | 569.55 | 07-JUL-22:10 | 17.70 | 15.89 |
August | 0.334856E+10 | 1942.99 | 02-AUG-21:00 | 24.40 | 21.64 | 0.948106E+09 | 569.55 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.300624E+10 | 2021.12 | 07-SEP-20:04 | 23.72 | 16.94 | 0.887306E+09 | 569.57 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.266071E+10 | 1435.15 | 20-OCT-21:00 | 13.90 | 9.43 | 0.859471E+09 | 569.51 | 11-OCT-22:10 | 13.90 | 9.43 |
November | 0.215346E+10 | 1510.24 | 25-NOV-21:12 | -23.7 | -24.1 | 0.768135E+09 | 560.11 | 03-NOV-21:30 | -23.7 | -24.1 |
December | 0.179611E+10 | 1051.05 | 03-DEC-11:35 | 4.80 | 2.32 | 0.750546E+09 | 501.47 | 05-DEC-22:19 | -7.0 | -9.4 |
Annual Sum or Average | 0.306656E+11 | 0.991918E+10 | ||||||||
Minimum of Months | 0.166351E+10 | 1051.05 | -36.7 | -36.8 | 0.637424E+09 | 501.47 | -23.7 | -24.1 | ||
Maximum of Months | 0.337647E+10 | 2023.34 | 24.40 | 22.86 | 0.948106E+09 | 569.57 | 22.38 | 17.30 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96014462.10 | 705.37 | 13-JAN-21:00 | -0.6 | -1.3 | 0.147476E+09 | 91.99 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.309037E+09 | 738.84 | 24-FEB-21:00 | 2.20 | 1.50 | 0.125150E+09 | 93.88 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.904297E+09 | 836.28 | 20-MAR-10:33 | 9.43 | 6.43 | 0.154781E+09 | 99.22 | 24-MAR-21:10 | 2.43 | 0.93 |
April | 0.151379E+10 | 1088.25 | 16-APR-10:33 | 23.33 | 18.86 | 0.156579E+09 | 115.82 | 18-APR-21:10 | 16.32 | 13.39 |
May | 0.212994E+10 | 1137.45 | 31-MAY-10:33 | 27.93 | 19.39 | 0.176401E+09 | 120.05 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.235842E+10 | 1558.57 | 30-JUN-19:53 | 23.30 | 18.22 | 0.184245E+09 | 120.45 | 28-JUN-21:30 | 23.30 | 18.22 |
July | 0.255596E+10 | 1497.72 | 03-JUL-20:00 | 26.70 | 23.80 | 0.195990E+09 | 120.45 | 27-JUL-21:19 | 20.73 | 17.79 |
August | 0.251403E+10 | 1509.67 | 04-AUG-20:00 | 18.90 | 18.12 | 0.196016E+09 | 120.45 | 11-AUG-21:19 | 18.33 | 16.08 |
September | 0.221052E+10 | 1289.26 | 11-SEP-21:00 | 19.40 | 17.91 | 0.178811E+09 | 120.45 | 11-SEP-21:19 | 19.40 | 17.91 |
October | 0.182751E+10 | 894.71 | 11-OCT-20:00 | 12.60 | 7.23 | 0.162699E+09 | 106.13 | 11-OCT-21:10 | 10.80 | 5.64 |
November | 0.953979E+09 | 880.80 | 04-NOV-10:33 | 10.20 | 5.24 | 0.150956E+09 | 104.13 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 0.212148E+09 | 684.34 | 04-DEC-21:00 | 1.70 | 0.04 | 0.151734E+09 | 90.76 | 04-DEC-22:10 | 1.78 | 0.09 |
Annual Sum or Average | 0.175856E+11 | 0.198084E+10 | ||||||||
Minimum of Months | 96014462.10 | 684.34 | -0.6 | -1.3 | 0.125150E+09 | 90.76 | 1.78 | 0.09 | ||
Maximum of Months | 0.255596E+10 | 1558.57 | 27.93 | 23.80 | 0.196016E+09 | 120.45 | 23.30 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11191265.82 | 319.75 | 13-JAN-22:00 | 2.20 | 0.77 | 0.112586E+09 | 68.57 | 18-JAN-04:49 | -4.6 | -4.8 |
February | 63258512.83 | 406.12 | 24-FEB-21:00 | 2.20 | 1.50 | 95464696.36 | 69.06 | 24-FEB-22:30 | 1.40 | 0.88 |
March | 0.369009E+09 | 481.49 | 20-MAR-10:33 | 9.43 | 6.43 | 0.117981E+09 | 73.01 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.745800E+09 | 634.75 | 16-APR-10:33 | 23.33 | 18.86 | 0.118347E+09 | 85.59 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.121066E+10 | 663.14 | 31-MAY-10:33 | 27.93 | 19.39 | 0.131991E+09 | 88.96 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.133827E+10 | 708.94 | 30-JUN-10:33 | 27.93 | 22.99 | 0.138459E+09 | 92.66 | 28-JUN-21:30 | 27.93 | 22.99 |
July | 0.145320E+10 | 703.43 | 02-JUL-10:33 | 27.77 | 21.90 | 0.147316E+09 | 92.65 | 03-JUL-21:19 | 24.03 | 22.77 |
August | 0.143035E+10 | 698.48 | 04-AUG-10:45 | 29.63 | 25.62 | 0.147024E+09 | 92.66 | 04-AUG-21:40 | 18.30 | 17.68 |
September | 0.125093E+10 | 685.94 | 09-SEP-10:33 | 25.53 | 16.73 | 0.133586E+09 | 91.02 | 11-SEP-21:40 | 19.40 | 17.91 |
October | 0.988565E+09 | 510.59 | 20-OCT-10:33 | 17.13 | 11.05 | 0.121515E+09 | 78.19 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.407978E+09 | 503.56 | 04-NOV-10:33 | 10.20 | 5.24 | 0.114564E+09 | 76.70 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 22410743.95 | 242.47 | 03-DEC-21:00 | -1.1 | -2.3 | 0.116676E+09 | 68.57 | 30-DEC-00:10 | -5.7 | -6.0 |
Annual Sum or Average | 0.929162E+10 | 0.149551E+10 | ||||||||
Minimum of Months | 11191265.82 | 242.47 | -1.1 | -2.3 | 95464696.36 | 68.57 | -5.7 | -6.0 | ||
Maximum of Months | 0.145320E+10 | 708.94 | 29.63 | 25.62 | 0.147316E+09 | 92.66 | 27.93 | 22.99 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462928E+11 | 39484.57 | 05-JAN-21:42 | -23.8 | -24.1 | 0.529323E+09 | 381.59 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.426527E+11 | 36797.77 | 24-FEB-21:00 | 2.20 | 1.50 | 0.469544E+09 | 381.59 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.483388E+11 | 37313.30 | 28-MAR-20:00 | 11.70 | 8.27 | 0.588871E+09 | 381.61 | 15-MAR-21:10 | 11.70 | 8.27 |
April | 0.480209E+11 | 38291.73 | 18-APR-20:00 | 18.30 | 15.20 | 0.572413E+09 | 381.67 | 19-APR-21:10 | 7.62 | 3.96 |
May | 0.514513E+11 | 38641.87 | 31-MAY-20:00 | 24.40 | 17.91 | 0.596329E+09 | 381.69 | 30-MAY-21:19 | 24.40 | 17.91 |
June | 0.508486E+11 | 38841.68 | 26-JUN-20:00 | 26.70 | 21.52 | 0.579374E+09 | 381.68 | 27-JUN-21:10 | 23.62 | 18.90 |
July | 0.527880E+11 | 38685.00 | 03-JUL-20:00 | 26.70 | 23.80 | 0.598694E+09 | 381.70 | 28-JUL-21:19 | 19.40 | 17.20 |
August | 0.528235E+11 | 38720.80 | 03-AUG-20:00 | 25.00 | 23.44 | 0.600101E+09 | 381.73 | 09-AUG-21:10 | 17.62 | 14.83 |
September | 0.499697E+11 | 38673.07 | 07-SEP-20:00 | 23.90 | 17.04 | 0.577542E+09 | 381.71 | 11-SEP-21:19 | 19.40 | 17.91 |
October | 0.497961E+11 | 37783.50 | 20-OCT-20:00 | 15.00 | 9.90 | 0.593355E+09 | 381.71 | 24-OCT-21:10 | 9.90 | 5.74 |
November | 0.465848E+11 | 38279.48 | 25-NOV-21:23 | -23.9 | -24.3 | 0.560837E+09 | 381.67 | 03-NOV-21:10 | -23.9 | -24.3 |
December | 0.462628E+11 | 36117.21 | 01-DEC-21:00 | -5.0 | -5.8 | 0.581167E+09 | 381.62 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.585830E+12 | 0.684755E+10 | ||||||||
Minimum of Months | 0.426527E+11 | 36117.21 | -23.9 | -24.3 | 0.469544E+09 | 381.59 | -23.9 | -24.3 | ||
Maximum of Months | 0.528235E+11 | 39484.57 | 26.70 | 23.80 | 0.600101E+09 | 381.73 | 24.40 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109162E+11 | 8981.47 | 12-JAN-12:30 | 1.95 | 0.38 | 0.800938E+10 | 5867.65 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.125130E+11 | 11434.92 | 08-FEB-13:30 | 2.50 | 1.29 | 0.729393E+10 | 6077.55 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.156328E+11 | 10417.92 | 25-MAR-13:40 | 15.03 | 8.62 | 0.908974E+10 | 6356.14 | 23-MAR-21:40 | 15.03 | 8.62 |
April | 0.173502E+11 | 13921.10 | 15-APR-13:20 | 28.67 | 20.40 | 0.926198E+10 | 6462.64 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.202547E+11 | 11055.31 | 06-MAY-13:00 | 22.20 | 11.68 | 0.100623E+11 | 6462.72 | 30-MAY-22:10 | 18.90 | 16.33 |
June | 0.213136E+11 | 11490.83 | 26-JUN-21:10 | 25.40 | 21.26 | 0.101048E+11 | 6462.77 | 16-JUN-22:10 | 25.40 | 21.26 |
July | 0.229952E+11 | 12102.70 | 30-JUL-12:00 | 26.70 | 21.51 | 0.105987E+11 | 6462.76 | 18-JUL-22:10 | 26.70 | 21.51 |
August | 0.232266E+11 | 12617.71 | 22-AUG-15:03 | 30.00 | 22.36 | 0.106800E+11 | 6462.77 | 07-AUG-22:10 | 30.00 | 22.36 |
September | 0.216030E+11 | 15128.43 | 07-SEP-12:50 | 31.52 | 18.17 | 0.996377E+10 | 6462.82 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.192163E+11 | 14873.30 | 20-OCT-12:50 | 21.68 | 12.55 | 0.971637E+10 | 6461.96 | 21-OCT-01:19 | 12.67 | 9.26 |
November | 0.142512E+11 | 14964.51 | 04-NOV-12:50 | 13.72 | 6.77 | 0.860196E+10 | 6339.58 | 03-NOV-21:40 | 13.72 | 6.77 |
December | 0.113665E+11 | 12419.53 | 03-DEC-13:00 | 5.60 | 2.41 | 0.850986E+10 | 5689.89 | 01-DEC-22:40 | 5.60 | 2.41 |
Annual Sum or Average | 0.210639E+12 | 0.111893E+12 | ||||||||
Minimum of Months | 0.109162E+11 | 8981.47 | 1.95 | 0.38 | 0.729393E+10 | 5689.89 | 1.13 | 0.51 | ||
Maximum of Months | 0.232266E+11 | 15128.43 | 31.52 | 22.36 | 0.106800E+11 | 6462.82 | 30.00 | 22.36 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460014E+11 | 47658.64 | 19-JAN-01:51 | -23.9 | -24.0 | 0.250397E+11 | 18296.11 | 13-JAN-22:49 | -23.9 | -24.0 |
February | 0.459390E+11 | 37550.81 | 02-FEB-06:00 | -36.7 | -36.8 | 0.226801E+11 | 18704.59 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.547218E+11 | 27361.99 | 24-MAR-20:00 | 3.90 | 2.01 | 0.284942E+11 | 19183.40 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.584930E+11 | 36043.20 | 18-APR-21:10 | 16.32 | 13.39 | 0.287391E+11 | 19185.99 | 14-APR-21:30 | 16.32 | 13.39 |
May | 0.664237E+11 | 37510.94 | 31-MAY-21:10 | 21.80 | 16.82 | 0.311398E+11 | 19186.16 | 30-MAY-22:10 | 21.80 | 16.82 |
June | 0.701949E+11 | 40158.58 | 26-JUN-21:10 | 25.40 | 21.26 | 0.307725E+11 | 19186.24 | 20-JUN-22:10 | 25.40 | 21.26 |
July | 0.752330E+11 | 39177.70 | 03-JUL-21:10 | 24.22 | 22.81 | 0.320100E+11 | 19186.21 | 07-JUL-22:10 | 17.70 | 15.89 |
August | 0.752642E+11 | 39344.71 | 02-AUG-21:10 | 24.32 | 21.63 | 0.322191E+11 | 19186.23 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.684981E+11 | 40712.38 | 07-SEP-21:10 | 22.43 | 16.38 | 0.306039E+11 | 19186.35 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.619214E+11 | 33925.43 | 20-OCT-21:10 | 13.90 | 9.45 | 0.303388E+11 | 19185.15 | 21-OCT-01:19 | 12.67 | 9.26 |
November | 0.522420E+11 | 44650.74 | 25-NOV-21:12 | -23.7 | -24.1 | 0.272613E+11 | 19183.35 | 03-NOV-21:10 | -23.7 | -24.1 |
December | 0.464899E+11 | 25790.31 | 03-DEC-11:35 | 4.80 | 2.32 | 0.267014E+11 | 17994.78 | 05-DEC-22:49 | -6.8 | -9.2 |
Annual Sum or Average | 0.721422E+12 | 0.346000E+12 | ||||||||
Minimum of Months | 0.459390E+11 | 25790.31 | -36.7 | -36.8 | 0.226801E+11 | 17994.78 | -23.9 | -24.1 | ||
Maximum of Months | 0.752642E+11 | 47658.64 | 25.40 | 22.81 | 0.322191E+11 | 19186.35 | 25.40 | 21.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4623570.36 | 3927.17 | 12-JAN-16:01 | 2.62 | 1.03 | 92546855.30 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 41573178.32 | 4089.03 | 08-FEB-16:01 | 2.02 | 0.67 | 83535747.55 | 56.69 | 10-FEB-04:19 | 3.30 | 1.87 |
March | 0.142880E+09 | 4113.83 | 25-MAR-15:01 | 18.72 | 10.45 | 95288578.10 | 56.69 | 26-MAR-01:19 | 12.03 | 10.54 |
April | 0.677592E+09 | 4145.18 | 26-APR-15:01 | 10.10 | 3.34 | 93535956.03 | 56.69 | 16-APR-04:00 | 10.10 | 3.34 |
May | 0.117989E+10 | 4175.91 | 21-MAY-18:01 | 16.93 | 9.12 | 98501914.60 | 56.70 | 31-MAY-22:30 | 18.65 | 13.49 |
June | 0.193377E+10 | 3674.08 | 17-JUN-18:02 | 23.72 | 19.22 | 95614428.21 | 56.70 | 20-JUN-21:30 | 18.85 | 15.10 |
July | 0.238664E+10 | 3646.80 | 21-JUL-18:01 | 20.00 | 15.79 | 98978241.41 | 56.70 | 04-JUL-00:20 | 20.00 | 15.79 |
August | 0.213884E+10 | 3656.74 | 30-AUG-18:01 | 20.13 | 17.18 | 99010508.36 | 56.70 | 28-AUG-21:00 | 20.13 | 17.18 |
September | 0.141346E+10 | 4113.06 | 30-SEP-15:01 | 10.92 | 3.93 | 95047618.87 | 56.70 | 11-SEP-21:19 | 10.92 | 3.93 |
October | 0.354051E+09 | 4146.73 | 19-OCT-15:01 | 18.53 | 10.65 | 96757537.62 | 56.69 | 20-OCT-23:49 | 13.90 | 9.75 |
November | 74942451.09 | 4163.01 | 04-NOV-15:01 | 14.13 | 6.72 | 91262967.45 | 56.69 | 28-NOV-04:19 | -20.2 | -20.5 |
December | 7523261.66 | 3849.89 | 01-DEC-16:01 | -2.1 | -4.3 | 93033696.47 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.103558E+11 | 0.113311E+10 | ||||||||
Minimum of Months | 4623570.36 | 3646.80 | -2.1 | -4.3 | 83535747.55 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.238664E+10 | 4175.91 | 23.72 | 19.22 | 99010508.36 | 56.70 | 20.13 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 426948.29 | 560.30 | 12-JAN-16:03 | 2.62 | 1.03 | 91961586.63 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 11819501.37 | 3837.36 | 24-FEB-16:02 | 8.12 | 5.76 | 82241868.70 | 56.69 | 05-FEB-02:20 | 8.12 | 5.76 |
March | 57877046.96 | 3966.93 | 25-MAR-15:01 | 18.72 | 10.45 | 94373659.46 | 56.69 | 01-MAR-04:19 | 18.72 | 10.45 |
April | 0.440457E+09 | 4057.33 | 29-APR-18:41 | 12.77 | 8.28 | 94576783.17 | 79.99 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.850135E+09 | 4632.02 | 20-MAY-18:41 | 13.68 | 7.74 | 0.103175E+09 | 76.68 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.158262E+10 | 4176.52 | 16-JUN-16:32 | 24.23 | 16.73 | 0.103506E+09 | 93.00 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.188686E+10 | 4042.01 | 23-JUL-21:51 | 13.90 | 11.92 | 0.109231E+09 | 91.73 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.158908E+10 | 4155.41 | 11-AUG-18:11 | 23.70 | 17.82 | 0.108289E+09 | 88.94 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.951187E+09 | 4515.58 | 24-SEP-16:11 | 14.63 | 7.59 | 98984638.48 | 81.71 | 12-SEP-18:10 | 14.63 | 7.59 |
October | 0.140177E+09 | 3952.90 | 29-OCT-15:01 | 14.82 | 8.16 | 96107390.30 | 58.29 | 20-OCT-20:10 | 14.82 | 8.16 |
November | 26892773.52 | 3972.56 | 04-NOV-15:01 | 14.13 | 6.72 | 90542751.39 | 56.69 | 29-NOV-00:20 | -7.0 | -8.0 |
December | 924266.12 | 669.63 | 01-DEC-16:03 | -2.1 | -4.3 | 92349486.94 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.753846E+10 | 0.116534E+10 | ||||||||
Minimum of Months | 426948.29 | 560.30 | -2.1 | -4.3 | 82241868.70 | 56.69 | -17.9 | -18.6 | ||
Maximum of Months | 0.188686E+10 | 4632.02 | 24.23 | 17.82 | 0.109231E+09 | 93.00 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3238698.39 | 205.19 | 30-JAN-15:05 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -24.0 | -24.3 |
February | 8074067.88 | 240.74 | 02-FEB-15:05 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -28.9 | -29.2 |
March | 43813053.85 | 421.32 | 24-MAR-13:10 | 12.38 | 6.48 | 0.00 | 0.00 | 01-MAR-00:10 | 12.38 | 6.48 |
April | 0.164186E+09 | 623.93 | 15-APR-13:30 | 28.85 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | 28.85 | 20.45 |
May | 0.316245E+09 | 459.99 | 06-MAY-13:00 | 22.20 | 11.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 11.68 |
June | 0.453305E+09 | 477.41 | 26-JUN-12:50 | 31.02 | 21.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 21.46 |
July | 0.563208E+09 | 516.51 | 30-JUL-13:30 | 26.95 | 19.99 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 19.99 |
August | 0.579160E+09 | 583.21 | 29-AUG-13:30 | 23.60 | 16.39 | 0.00 | 0.00 | 01-AUG-00:10 | 23.60 | 16.39 |
September | 0.482624E+09 | 726.55 | 07-SEP-13:00 | 31.70 | 18.06 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.06 |
October | 0.237439E+09 | 703.70 | 20-OCT-12:40 | 21.57 | 12.49 | 0.00 | 0.00 | 01-OCT-00:10 | 21.57 | 12.49 |
November | 69909645.07 | 668.49 | 04-NOV-12:30 | 13.35 | 6.69 | 0.00 | 0.00 | 01-NOV-00:10 | 13.35 | 6.69 |
December | 3963176.73 | 124.96 | 07-DEC-15:15 | -3.9 | -7.6 | 0.00 | 0.00 | 01-DEC-00:10 | -3.9 | -7.6 |
Annual Sum or Average | 0.292517E+10 | 0.00 | ||||||||
Minimum of Months | 3238698.39 | 124.96 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.579160E+09 | 726.55 | 31.70 | 21.46 | 0.00 | 0.00 | 31.70 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3123829.19 | 280.07 | 13-JAN-19:03 | 0.40 | -0.6 | 92222688.18 | 56.69 | 21-JAN-00:20 | -11.3 | -11.7 |
February | 9694921.70 | 733.49 | 25-FEB-09:02 | 0.78 | -0.3 | 82444510.35 | 56.69 | 05-FEB-00:20 | 0.78 | -0.3 |
March | 77900924.13 | 1131.28 | 24-MAR-18:01 | 8.35 | 4.47 | 95295077.33 | 56.69 | 19-MAR-23:19 | 8.35 | 4.47 |
April | 0.224437E+09 | 1197.29 | 30-APR-18:01 | 15.22 | 9.05 | 94009185.16 | 72.03 | 14-APR-21:10 | 15.22 | 9.05 |
May | 0.482151E+09 | 1237.49 | 06-MAY-19:31 | 13.13 | 8.89 | 0.100450E+09 | 73.32 | 12-MAY-21:00 | 16.70 | 15.64 |
June | 0.674561E+09 | 1168.13 | 23-JUN-21:51 | 18.90 | 13.98 | 99835963.15 | 77.14 | 08-JUN-21:40 | 18.90 | 13.98 |
July | 0.719985E+09 | 1137.74 | 18-JUL-21:51 | 18.30 | 14.23 | 0.104761E+09 | 76.10 | 07-JUL-21:49 | 18.30 | 14.23 |
August | 0.643973E+09 | 1183.22 | 11-AUG-18:11 | 23.70 | 17.82 | 0.104267E+09 | 75.01 | 23-AUG-21:49 | 17.88 | 17.07 |
September | 0.455431E+09 | 1191.29 | 19-SEP-18:01 | 12.65 | 8.22 | 97076490.05 | 75.84 | 12-SEP-21:10 | 12.65 | 8.22 |
October | 0.185174E+09 | 1123.15 | 19-OCT-18:01 | 11.92 | 7.44 | 96393984.00 | 57.50 | 20-OCT-20:19 | 14.63 | 9.75 |
November | 76710617.83 | 1094.10 | 04-NOV-18:02 | 5.50 | 2.14 | 91727489.10 | 56.69 | 08-NOV-23:30 | 14.40 | 12.79 |
December | 4729238.83 | 260.66 | 18-DEC-19:05 | -3.9 | -4.1 | 93414181.66 | 56.69 | 12-DEC-04:19 | -3.9 | -4.1 |
Annual Sum or Average | 0.355787E+10 | 0.115190E+10 | ||||||||
Minimum of Months | 3123829.19 | 260.66 | -3.9 | -4.1 | 82444510.35 | 56.69 | -11.3 | -11.7 | ||
Maximum of Months | 0.719985E+09 | 1237.49 | 23.70 | 17.82 | 0.104761E+09 | 77.14 | 18.90 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4150502.32 | 622.87 | 13-JAN-16:03 | 3.62 | 1.75 | 92359320.51 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 29970737.48 | 3647.55 | 24-FEB-09:01 | 3.07 | 0.61 | 83147906.43 | 56.69 | 14-FEB-04:19 | 3.07 | 0.61 |
March | 0.139004E+09 | 3738.11 | 24-MAR-15:01 | 12.43 | 6.33 | 95463136.45 | 56.69 | 07-MAR-04:19 | 12.43 | 6.33 |
April | 0.577824E+09 | 3780.86 | 26-APR-08:61 | 2.48 | -1.4 | 93623614.61 | 56.69 | 18-APR-21:19 | 2.48 | -1.4 |
May | 0.124687E+10 | 3743.17 | 06-MAY-18:01 | 16.83 | 10.29 | 98807914.63 | 56.70 | 30-MAY-21:19 | 19.63 | 16.89 |
June | 0.196056E+10 | 3434.35 | 11-JUN-08:61 | 24.37 | 20.62 | 95734793.63 | 56.70 | 26-JUN-00:10 | 23.80 | 21.15 |
July | 0.232276E+10 | 3512.72 | 02-JUL-08:61 | 24.18 | 20.57 | 99068369.43 | 56.70 | 24-JUL-21:40 | 19.40 | 15.97 |
August | 0.205430E+10 | 3469.95 | 02-AUG-08:61 | 22.48 | 19.67 | 99160906.04 | 56.70 | 03-AUG-23:19 | 23.90 | 23.15 |
September | 0.141660E+10 | 3734.69 | 20-SEP-18:01 | 17.23 | 10.71 | 95292375.98 | 56.70 | 11-SEP-21:30 | 17.23 | 10.71 |
October | 0.305580E+09 | 3746.97 | 29-OCT-15:01 | 14.82 | 8.16 | 96980527.61 | 56.69 | 20-OCT-23:19 | 14.82 | 8.16 |
November | 66910499.65 | 3762.32 | 04-NOV-15:01 | 14.13 | 6.72 | 91212389.23 | 56.69 | 25-NOV-04:19 | -14.6 | -14.9 |
December | 11784855.35 | 2100.84 | 03-DEC-09:02 | -1.5 | -1.7 | 92894351.63 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.101363E+11 | 0.113375E+10 | ||||||||
Minimum of Months | 4150502.32 | 622.87 | -1.5 | -1.7 | 83147906.43 | 56.69 | -17.9 | -18.6 | ||
Maximum of Months | 0.232276E+10 | 3780.86 | 24.37 | 20.62 | 99160906.04 | 56.70 | 23.90 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 443112.91 | 595.46 | 12-JAN-09:04 | -4.1 | -4.6 | 91716700.84 | 56.69 | 10-JAN-04:19 | -4.1 | -4.6 |
February | 7382514.60 | 3125.81 | 24-FEB-09:01 | 3.07 | 0.61 | 81703669.29 | 56.69 | 24-FEB-04:19 | 3.07 | 0.61 |
March | 55828086.76 | 3345.06 | 24-MAR-15:01 | 12.43 | 6.33 | 94427450.55 | 56.69 | 10-MAR-04:19 | 12.43 | 6.33 |
April | 0.367321E+09 | 3752.09 | 18-APR-08:51 | 22.80 | 18.62 | 94061488.05 | 73.04 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.954597E+09 | 3846.70 | 31-MAY-08:32 | 25.17 | 19.42 | 0.101994E+09 | 75.39 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.161942E+10 | 4104.21 | 09-JUN-08:32 | 22.77 | 17.31 | 0.102042E+09 | 77.36 | 20-JUN-21:30 | 18.85 | 15.10 |
July | 0.182361E+10 | 3998.19 | 13-JUL-08:32 | 22.23 | 18.50 | 0.107849E+09 | 78.10 | 05-JUL-21:19 | 22.23 | 18.50 |
August | 0.153673E+10 | 3906.79 | 11-AUG-08:51 | 23.30 | 17.93 | 0.106526E+09 | 76.61 | 04-AUG-21:40 | 23.30 | 17.93 |
September | 0.962127E+09 | 3972.10 | 08-SEP-08:51 | 25.00 | 17.45 | 98372459.91 | 75.30 | 07-SEP-21:10 | 25.00 | 17.45 |
October | 0.108624E+09 | 3099.92 | 21-OCT-15:01 | 20.67 | 14.27 | 95852710.56 | 56.69 | 20-OCT-21:10 | 20.67 | 14.27 |
November | 15370864.73 | 2018.64 | 04-NOV-08:62 | 2.77 | 0.71 | 90449479.54 | 56.69 | 29-NOV-04:19 | -5.0 | -6.0 |
December | 700477.77 | 491.13 | 03-DEC-09:03 | -1.5 | -1.7 | 92327279.58 | 56.69 | 12-DEC-04:19 | -20.0 | -20.3 |
Annual Sum or Average | 0.745216E+10 | 0.115732E+10 | ||||||||
Minimum of Months | 443112.91 | 491.13 | -4.1 | -4.6 | 81703669.29 | 56.69 | -20.0 | -20.3 | ||
Maximum of Months | 0.182361E+10 | 4104.21 | 25.17 | 19.42 | 0.107849E+09 | 78.10 | 25.00 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662586E+09 | 1590.84 | 31-JAN-04:00 | -31.1 | -31.3 | 0.117392E+10 | 709.10 | 13-JAN-22:40 | -31.1 | -31.3 |
February | 0.131381E+10 | 2073.68 | 02-FEB-06:00 | -36.7 | -36.8 | 0.102274E+10 | 725.37 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.228718E+10 | 1805.54 | 20-MAR-10:33 | 9.43 | 6.43 | 0.121704E+10 | 758.05 | 24-MAR-21:40 | 1.33 | 0.09 |
April | 0.338330E+10 | 2361.22 | 18-APR-10:33 | 26.33 | 20.75 | 0.123024E+10 | 886.32 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.452489E+10 | 2421.24 | 31-MAY-10:33 | 27.93 | 19.39 | 0.136820E+10 | 900.01 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.495258E+10 | 2607.49 | 30-JUN-10:33 | 27.93 | 22.99 | 0.142838E+10 | 951.85 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.539477E+10 | 2614.68 | 02-JUL-10:33 | 27.77 | 21.90 | 0.152312E+10 | 951.73 | 03-JUL-21:40 | 23.67 | 22.67 |
August | 0.527663E+10 | 2542.82 | 02-AUG-10:33 | 26.33 | 21.24 | 0.151306E+10 | 942.10 | 04-AUG-21:40 | 18.30 | 17.68 |
September | 0.464783E+10 | 2567.59 | 09-SEP-10:33 | 25.53 | 16.73 | 0.138017E+10 | 936.41 | 08-SEP-21:40 | 25.53 | 16.73 |
October | 0.363051E+10 | 1911.27 | 20-OCT-10:33 | 17.13 | 11.05 | 0.124124E+10 | 793.97 | 20-OCT-21:49 | 13.90 | 9.53 |
November | 0.188074E+10 | 1865.93 | 04-NOV-10:33 | 10.20 | 5.24 | 0.116924E+10 | 759.28 | 03-NOV-21:40 | 10.20 | 5.24 |
December | 0.670308E+09 | 1614.52 | 03-DEC-11:35 | 4.80 | 2.32 | 0.119885E+10 | 704.45 | 09-DEC-05:00 | -22.8 | -23.0 |
Annual Sum or Average | 0.386251E+11 | 0.154662E+11 | ||||||||
Minimum of Months | 0.662586E+09 | 1590.84 | -36.7 | -36.8 | 0.102274E+10 | 704.45 | -31.1 | -31.3 | ||
Maximum of Months | 0.539477E+10 | 2614.68 | 27.93 | 22.99 | 0.152312E+10 | 951.85 | 25.53 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2999930.53 | 4021.25 | 12-JAN-16:01 | 2.62 | 1.03 | 92192034.95 | 56.69 | 10-JAN-04:19 | 2.62 | 1.03 |
February | 38886111.55 | 4234.82 | 08-FEB-16:01 | 2.02 | 0.67 | 83125736.40 | 56.69 | 24-FEB-04:19 | 0.20 | -1.4 |
March | 0.124947E+09 | 4250.95 | 23-MAR-18:01 | 13.53 | 8.78 | 94814980.57 | 56.69 | 20-MAR-00:30 | 13.53 | 8.78 |
April | 0.685658E+09 | 4311.02 | 26-APR-15:01 | 10.10 | 3.34 | 93245048.00 | 56.70 | 24-APR-00:00 | 10.10 | 3.34 |
May | 0.116486E+10 | 4343.23 | 21-MAY-18:01 | 16.93 | 9.12 | 98384939.88 | 56.70 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.196921E+10 | 3827.12 | 17-JUN-18:02 | 23.72 | 19.22 | 95523277.29 | 56.70 | 20-JUN-21:10 | 19.22 | 15.00 |
July | 0.242040E+10 | 3797.86 | 26-JUL-18:02 | 29.13 | 26.06 | 98916924.99 | 56.70 | 07-JUL-21:00 | 29.13 | 26.06 |
August | 0.212295E+10 | 3796.70 | 30-AUG-18:01 | 20.13 | 17.18 | 98923349.11 | 56.70 | 03-AUG-21:49 | 20.13 | 17.18 |
September | 0.136240E+10 | 4260.05 | 20-SEP-18:01 | 17.23 | 10.71 | 94829023.61 | 56.70 | 06-SEP-21:49 | 17.23 | 10.71 |
October | 0.327587E+09 | 4296.10 | 19-OCT-15:01 | 18.53 | 10.65 | 96366099.69 | 56.69 | 21-OCT-01:19 | 12.67 | 9.26 |
November | 63697661.49 | 4318.51 | 04-NOV-15:01 | 14.13 | 6.72 | 90839371.24 | 56.69 | 21-NOV-04:19 | -8.9 | -9.7 |
December | 5589156.77 | 3974.14 | 01-DEC-16:01 | -2.1 | -4.3 | 92714587.11 | 56.69 | 12-DEC-04:19 | -20.0 | -20.3 |
Annual Sum or Average | 0.102892E+11 | 0.112988E+10 | ||||||||
Minimum of Months | 2999930.53 | 3796.70 | -2.1 | -4.3 | 83125736.40 | 56.69 | -20.0 | -20.3 | ||
Maximum of Months | 0.242040E+10 | 4343.23 | 29.13 | 26.06 | 98923349.11 | 56.70 | 29.13 | 26.06 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 108580.73 | 739.98 | 13-JAN-16:04 | 3.62 | 1.75 | 91584898.01 | 56.69 | 03-JAN-04:19 | 3.62 | 1.75 |
February | 8722260.24 | 3866.48 | 24-FEB-16:02 | 8.12 | 5.76 | 81840462.34 | 56.69 | 17-FEB-04:19 | 8.12 | 5.76 |
March | 44761670.49 | 4184.65 | 23-MAR-18:01 | 13.53 | 8.78 | 93964351.32 | 56.69 | 17-MAR-03:20 | 13.53 | 8.78 |
April | 0.441958E+09 | 4280.25 | 29-APR-18:41 | 12.77 | 8.28 | 94444746.58 | 86.84 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.841321E+09 | 4850.90 | 20-MAY-18:41 | 13.68 | 7.74 | 0.103708E+09 | 80.39 | 03-MAY-18:10 | 13.68 | 7.74 |
June | 0.165437E+10 | 4334.54 | 16-JUN-16:32 | 24.23 | 16.73 | 0.104365E+09 | 101.76 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.197578E+10 | 4299.01 | 23-JUL-21:51 | 13.90 | 11.92 | 0.109970E+09 | 98.00 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.161792E+10 | 4294.56 | 11-AUG-18:11 | 23.70 | 17.82 | 0.109049E+09 | 96.27 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.916061E+09 | 4670.36 | 24-SEP-16:11 | 14.63 | 7.59 | 99012612.64 | 88.00 | 12-SEP-18:10 | 14.63 | 7.59 |
October | 0.114995E+09 | 4008.01 | 24-OCT-15:01 | 15.42 | 8.80 | 95642164.47 | 58.53 | 11-OCT-18:10 | 15.42 | 8.80 |
November | 20677360.07 | 4093.02 | 04-NOV-15:01 | 14.13 | 6.72 | 90172291.65 | 56.69 | 17-NOV-04:19 | 0.20 | -1.0 |
December | 329225.97 | 762.96 | 02-DEC-16:03 | 4.95 | 2.78 | 92225138.81 | 56.69 | 26-DEC-04:19 | -3.9 | -4.4 |
Annual Sum or Average | 0.763700E+10 | 0.116598E+10 | ||||||||
Minimum of Months | 108580.73 | 739.98 | 3.62 | 1.75 | 81840462.34 | 56.69 | -3.9 | -4.4 | ||
Maximum of Months | 0.197578E+10 | 4850.90 | 24.23 | 17.82 | 0.109970E+09 | 101.76 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58297934.52 | 2339.23 | 30-JAN-16:02 | -24.5 | -24.9 | 94178127.40 | 56.69 | 03-JAN-04:19 | -24.5 | -24.9 |
February | 0.117940E+09 | 2231.29 | 17-FEB-16:01 | -6.8 | -8.8 | 85683518.15 | 56.69 | 17-FEB-04:19 | -6.8 | -8.8 |
March | 0.215241E+09 | 2272.27 | 22-MAR-15:01 | 6.70 | 3.37 | 96389580.88 | 56.69 | 20-MAR-00:10 | 6.70 | 3.37 |
April | 0.467433E+09 | 2263.48 | 05-APR-15:01 | 4.40 | 0.63 | 93711525.02 | 56.69 | 18-APR-21:49 | 14.78 | 12.42 |
May | 0.717784E+09 | 2205.58 | 21-MAY-18:01 | 16.93 | 9.12 | 98497762.30 | 56.69 | 30-MAY-21:00 | 18.90 | 16.37 |
June | 0.103412E+10 | 1977.15 | 11-JUN-18:02 | 30.18 | 23.02 | 95579008.24 | 56.69 | 23-JUN-21:49 | 19.08 | 14.05 |
July | 0.125063E+10 | 2016.81 | 14-JUL-15:02 | 24.50 | 20.55 | 98863941.63 | 56.69 | 13-JUL-21:49 | 24.50 | 20.55 |
August | 0.123715E+10 | 2020.97 | 03-AUG-18:02 | 29.03 | 24.34 | 98912775.46 | 56.69 | 02-AUG-23:40 | 29.03 | 24.34 |
September | 0.100519E+10 | 2269.54 | 30-SEP-15:01 | 10.92 | 3.93 | 95204253.07 | 56.69 | 06-SEP-22:00 | 10.92 | 3.93 |
October | 0.525754E+09 | 2290.01 | 27-OCT-15:01 | 10.23 | 4.53 | 97648705.90 | 56.69 | 02-OCT-21:49 | 10.23 | 4.53 |
November | 0.177985E+09 | 2253.17 | 12-NOV-16:01 | 0.55 | -2.4 | 92533263.47 | 56.69 | 08-NOV-22:10 | 0.55 | -2.4 |
December | 0.106641E+09 | 2233.49 | 01-DEC-16:01 | -2.1 | -4.3 | 94481288.47 | 56.69 | 26-DEC-04:19 | -3.9 | -4.4 |
Annual Sum or Average | 0.691416E+10 | 0.114168E+10 | ||||||||
Minimum of Months | 58297934.52 | 1977.15 | -24.5 | -24.9 | 85683518.15 | 56.69 | -24.5 | -24.9 | ||
Maximum of Months | 0.125063E+10 | 2339.23 | 30.18 | 24.34 | 98912775.46 | 56.69 | 29.03 | 24.34 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270436E+11 | 29244.81 | 19-JAN-01:51 | -23.9 | -24.0 | 0.171330E+11 | 11347.91 | 17-JAN-00:20 | -23.9 | -24.0 |
February | 0.260834E+11 | 18763.90 | 02-FEB-06:00 | -36.7 | -36.8 | 0.153533E+11 | 11347.91 | 21-FEB-00:20 | -4.1 | -5.9 |
March | 0.307976E+11 | 18364.88 | 28-MAR-21:10 | 9.82 | 7.62 | 0.189444E+11 | 11347.91 | 07-MAR-00:20 | 9.82 | 7.62 |
April | 0.332139E+11 | 21045.65 | 18-APR-21:10 | 16.32 | 13.39 | 0.184892E+11 | 11348.90 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.385393E+11 | 22245.38 | 31-MAY-21:10 | 21.80 | 16.82 | 0.192927E+11 | 11349.32 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.406429E+11 | 23011.00 | 26-JUN-21:20 | 25.20 | 21.20 | 0.187340E+11 | 11365.02 | 30-JUN-21:19 | 21.87 | 16.96 |
July | 0.429168E+11 | 22726.17 | 03-JUL-21:20 | 24.03 | 22.77 | 0.192976E+11 | 11361.90 | 28-JUL-21:19 | 19.40 | 17.20 |
August | 0.419695E+11 | 22572.78 | 03-AUG-21:20 | 24.23 | 23.04 | 0.193730E+11 | 11370.72 | 04-AUG-21:19 | 18.30 | 17.83 |
September | 0.373007E+11 | 21995.18 | 07-SEP-21:10 | 22.43 | 16.38 | 0.186355E+11 | 11349.25 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.335483E+11 | 19166.90 | 20-OCT-22:00 | 13.90 | 9.54 | 0.190890E+11 | 11347.89 | 17-OCT-03:20 | 13.90 | 9.54 |
November | 0.294192E+11 | 22505.31 | 25-NOV-21:23 | -23.9 | -24.3 | 0.179521E+11 | 11347.91 | 13-NOV-00:20 | -23.9 | -24.3 |
December | 0.269795E+11 | 15800.20 | 04-DEC-23:00 | 2.20 | 0.30 | 0.182503E+11 | 11347.92 | 18-DEC-00:20 | -4.1 | -4.8 |
Annual Sum or Average | 0.408455E+12 | 0.220544E+12 | ||||||||
Minimum of Months | 0.260834E+11 | 15800.20 | -36.7 | -36.8 | 0.153533E+11 | 11347.89 | -23.9 | -24.3 | ||
Maximum of Months | 0.429168E+11 | 29244.81 | 25.20 | 23.04 | 0.193730E+11 | 11370.72 | 21.87 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300200E+11 | 30988.10 | 19-JAN-01:51 | -23.9 | -24.0 | 0.174854E+11 | 11347.98 | 17-JAN-00:20 | -23.9 | -24.0 |
February | 0.290406E+11 | 19706.23 | 02-FEB-06:00 | -36.7 | -36.8 | 0.155824E+11 | 11347.98 | 13-FEB-00:20 | -6.7 | -7.2 |
March | 0.344806E+11 | 20309.76 | 28-MAR-21:10 | 9.82 | 7.62 | 0.191451E+11 | 11347.99 | 06-MAR-00:20 | 9.82 | 7.62 |
April | 0.368107E+11 | 22427.39 | 18-APR-21:10 | 16.32 | 13.39 | 0.186080E+11 | 11348.90 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.421717E+11 | 23550.91 | 31-MAY-21:20 | 21.40 | 16.40 | 0.193305E+11 | 11372.75 | 30-MAY-21:19 | 21.40 | 16.40 |
June | 0.437630E+11 | 24232.55 | 26-JUN-21:20 | 25.20 | 21.20 | 0.187519E+11 | 11375.83 | 30-JUN-21:19 | 21.87 | 16.96 |
July | 0.459508E+11 | 23931.75 | 03-JUL-21:20 | 24.03 | 22.77 | 0.193071E+11 | 11377.80 | 14-JUL-21:19 | 22.60 | 20.30 |
August | 0.450491E+11 | 23805.63 | 03-AUG-21:20 | 24.23 | 23.04 | 0.193864E+11 | 11384.49 | 04-AUG-21:19 | 18.30 | 17.83 |
September | 0.405412E+11 | 23249.50 | 07-SEP-21:20 | 22.07 | 16.32 | 0.186792E+11 | 11364.01 | 07-SEP-21:19 | 22.07 | 16.32 |
October | 0.373574E+11 | 20896.12 | 20-OCT-22:00 | 13.90 | 9.54 | 0.192136E+11 | 11347.93 | 17-OCT-03:20 | 13.90 | 9.54 |
November | 0.328226E+11 | 27827.75 | 25-NOV-21:23 | -23.9 | -24.3 | 0.181781E+11 | 11347.98 | 13-NOV-00:20 | -23.9 | -24.3 |
December | 0.301853E+11 | 17789.91 | 04-DEC-23:00 | 2.20 | 0.30 | 0.185944E+11 | 11348.00 | 26-DEC-00:20 | -6.5 | -7.2 |
Annual Sum or Average | 0.448193E+12 | 0.222262E+12 | ||||||||
Minimum of Months | 0.290406E+11 | 17789.91 | -36.7 | -36.8 | 0.155824E+11 | 11347.93 | -23.9 | -24.3 | ||
Maximum of Months | 0.459508E+11 | 30988.10 | 25.20 | 23.04 | 0.193864E+11 | 11384.49 | 22.60 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447601E+11 | 27143.02 | 29-JAN-19:42 | -23.8 | -24.0 | 0.186660E+11 | 11319.71 | 07-JAN-18:19 | -23.8 | -24.0 |
February | 0.422721E+11 | 27307.09 | 24-FEB-11:33 | 5.93 | 2.90 | 0.168359E+11 | 11319.71 | 04-FEB-18:19 | 5.93 | 2.90 |
March | 0.493913E+11 | 28770.81 | 19-MAR-10:50 | 14.13 | 10.21 | 0.188161E+11 | 11319.60 | 04-MAR-18:19 | 14.13 | 10.21 |
April | 0.505135E+11 | 30768.83 | 18-APR-10:33 | 26.33 | 20.75 | 0.182236E+11 | 11319.68 | 15-APR-17:19 | 26.33 | 20.75 |
May | 0.555621E+11 | 31303.63 | 31-MAY-10:37 | 27.93 | 19.39 | 0.188515E+11 | 11319.67 | 06-MAY-17:19 | 27.93 | 19.39 |
June | 0.558659E+11 | 31534.56 | 11-JUN-10:40 | 29.67 | 22.05 | 0.182558E+11 | 11319.67 | 24-JUN-17:19 | 26.50 | 20.26 |
July | 0.584208E+11 | 31571.91 | 02-JUL-10:40 | 27.77 | 21.90 | 0.188618E+11 | 11319.68 | 08-JUL-17:19 | 22.80 | 18.35 |
August | 0.576771E+11 | 31269.97 | 01-AUG-10:33 | 26.83 | 21.26 | 0.188670E+11 | 11319.68 | 05-AUG-17:19 | 25.03 | 17.79 |
September | 0.536719E+11 | 31346.43 | 08-SEP-10:37 | 28.33 | 18.78 | 0.182427E+11 | 11319.68 | 09-SEP-17:19 | 26.27 | 16.30 |
October | 0.516255E+11 | 28955.99 | 01-OCT-10:33 | 16.07 | 11.42 | 0.188299E+11 | 11319.59 | 07-OCT-17:19 | 4.90 | 2.60 |
November | 0.467438E+11 | 28615.31 | 25-NOV-21:23 | -23.9 | -24.3 | 0.181838E+11 | 11319.71 | 25-NOV-18:19 | -23.9 | -24.3 |
December | 0.454067E+11 | 26629.29 | 03-DEC-11:40 | 4.80 | 2.32 | 0.187834E+11 | 11319.71 | 09-DEC-18:19 | -19.6 | -20.0 |
Annual Sum or Average | 0.611911E+12 | 0.221418E+12 | ||||||||
Minimum of Months | 0.422721E+11 | 26629.29 | -23.9 | -24.3 | 0.168359E+11 | 11319.59 | -23.9 | -24.3 | ||
Maximum of Months | 0.584208E+11 | 31571.91 | 29.67 | 22.05 | 0.188670E+11 | 11319.71 | 27.93 | 20.75 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331861E+09 | 2626.67 | 13-JAN-11:50 | 3.62 | 1.34 | 0.122603E+10 | 745.69 | 18-JAN-05:00 | -9.4 | -9.8 |
February | 0.128149E+10 | 3375.44 | 24-FEB-11:33 | 5.93 | 2.90 | 0.105332E+10 | 751.40 | 24-FEB-22:30 | 1.40 | 0.88 |
March | 0.368658E+10 | 3668.48 | 20-MAR-10:33 | 9.43 | 6.43 | 0.128648E+10 | 806.36 | 19-MAR-23:19 | 9.43 | 6.43 |
April | 0.621755E+10 | 4834.99 | 18-APR-10:33 | 26.33 | 20.75 | 0.130506E+10 | 951.49 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.900949E+10 | 5125.34 | 31-MAY-10:33 | 27.93 | 19.39 | 0.145309E+10 | 999.11 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.101404E+11 | 6559.30 | 30-JUN-14:10 | 29.40 | 21.90 | 0.152637E+10 | 1007.40 | 28-JUN-21:19 | 29.40 | 21.90 |
July | 0.109931E+11 | 6290.38 | 05-JUL-14:10 | 27.30 | 19.85 | 0.162080E+10 | 1007.40 | 05-JUL-22:10 | 20.60 | 19.73 |
August | 0.105720E+11 | 6770.60 | 04-AUG-15:03 | 33.90 | 25.49 | 0.160486E+10 | 1007.38 | 03-AUG-21:19 | 33.90 | 25.49 |
September | 0.901648E+10 | 6631.48 | 07-SEP-13:30 | 31.95 | 18.23 | 0.144050E+10 | 1006.38 | 07-SEP-21:40 | 21.33 | 16.17 |
October | 0.668123E+10 | 3895.85 | 20-OCT-10:50 | 17.62 | 11.24 | 0.130962E+10 | 850.93 | 20-OCT-21:40 | 13.90 | 9.51 |
November | 0.312791E+10 | 3755.93 | 04-NOV-10:33 | 10.20 | 5.24 | 0.123356E+10 | 804.19 | 03-NOV-21:30 | 10.20 | 5.24 |
December | 0.643611E+09 | 3230.18 | 03-DEC-11:35 | 4.80 | 2.32 | 0.126890E+10 | 745.64 | 22-DEC-05:40 | -14.2 | -14.5 |
Annual Sum or Average | 0.717017E+11 | 0.163286E+11 | ||||||||
Minimum of Months | 0.331861E+09 | 2626.67 | 3.62 | 1.34 | 0.105332E+10 | 745.64 | -14.2 | -14.5 | ||
Maximum of Months | 0.109931E+11 | 6770.60 | 33.90 | 25.49 | 0.162080E+10 | 1007.40 | 33.90 | 25.49 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 |
February | 0.172717E+09 | 6108.93 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.172717E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.172717E+09 | 6108.93 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176572E+10 | 2894.01 | 20-JAN-07:52 | -23.3 |
February | 0.740717E+09 | 2398.93 | 04-FEB-11:22 | -23.0 |
March | 0.379294E+09 | 1137.65 | 06-MAR-04:50 | -15.7 |
April | 0.101191E+09 | 836.47 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 1199912.96 | 205.98 | 30-SEP-06:30 | 0.60 |
October | 5907791.00 | 249.78 | 23-OCT-06:10 | -3.0 |
November | 0.576340E+09 | 2759.53 | 26-NOV-08:51 | -23.3 |
December | 0.159217E+10 | 2135.14 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.516254E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.176572E+10 | 2894.01 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43385233.86 | 931.02 | 31-JAN-11:42 | -23.1 |
February | 63789791.59 | 1268.65 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 6600222.26 | 774.50 | 26-NOV-08:51 | -23.3 |
December | 1887682.74 | 94.47 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.115663E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 63789791.59 | 1268.65 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107467E+10 | 1560.78 | 31-JAN-11:42 | -23.1 |
February | 0.599561E+09 | 1921.88 | 04-FEB-11:22 | -23.0 |
March | 0.114439E+09 | 519.90 | 06-MAR-05:00 | -15.6 |
April | 9643361.85 | 209.22 | 03-APR-11:50 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.237589E+09 | 1355.81 | 26-NOV-08:51 | -23.3 |
December | 0.594890E+09 | 1042.48 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.263079E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.107467E+10 | 1921.88 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104908E+10 | 1015.38 | 31-JAN-11:42 | -23.1 |
February | 0.564551E+09 | 1225.55 | 04-FEB-11:22 | -23.0 |
March | 0.191782E+09 | 463.43 | 06-MAR-05:00 | -15.6 |
April | 27171853.13 | 243.03 | 03-APR-11:40 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.272168E+09 | 896.16 | 26-NOV-08:51 | -23.3 |
December | 0.698864E+09 | 777.69 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.280361E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.104908E+10 | 1225.55 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 207175.32 | 1739.33 | 06-JAN-10:41 | -23.2 |
February | 260241.28 | 3610.08 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 53420.89 | 890.35 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 520837.49 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 260241.28 | 3610.08 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198833E+09 | 6474.66 | 20-JAN-07:52 | -23.3 |
February | 9965925.37 | 5121.37 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 46690125.37 | 6377.67 | 26-NOV-08:51 | -23.3 |
December | 0.247407E+09 | 2993.58 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.502896E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.247407E+09 | 6474.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134939E+09 | 14516.57 | 06-JAN-10:41 | -23.2 |
February | 0.337078E+09 | 20653.36 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 14119507.81 | 13270.24 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.486136E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.337078E+09 | 20653.36 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238077E+10 | 2121.04 | 19-JAN-19:13 | -23.3 |
February | 0.153384E+10 | 2139.86 | 04-FEB-08:03 | -30.3 |
March | 0.849149E+09 | 2044.19 | 01-MAR-16:02 | -3.9 |
April | 0.332231E+09 | 2029.63 | 03-APR-08:62 | -5.9 |
May | 18570983.14 | 1733.33 | 02-MAY-08:61 | 4.08 |
June | 5548774.38 | 1092.15 | 07-JUN-08:03 | 13.58 |
July | 1452127.08 | 940.82 | 20-JUL-08:04 | 20.68 |
August | 1688490.73 | 902.38 | 22-AUG-08:04 | 22.07 |
September | 54810962.45 | 1916.50 | 29-SEP-08:62 | 5.05 |
October | 0.250462E+09 | 1997.61 | 26-OCT-08:61 | 1.28 |
November | 0.108126E+10 | 2100.50 | 26-NOV-16:13 | -13.9 |
December | 0.200822E+10 | 2140.79 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.851801E+10 | |||
Minimum of Months | 1452127.08 | 902.38 | -30.3 | |
Maximum of Months | 0.238077E+10 | 2140.79 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277411E+10 | 2127.50 | 19-JAN-16:13 | -23.0 |
February | 0.185434E+10 | 2275.47 | 03-FEB-08:62 | -33.7 |
March | 0.101542E+10 | 2040.98 | 06-MAR-09:02 | -9.5 |
April | 0.381096E+09 | 2021.55 | 03-APR-08:62 | -5.9 |
May | 21706991.82 | 1933.99 | 02-MAY-08:61 | 4.08 |
June | 5427085.40 | 1077.76 | 03-JUN-08:03 | 8.68 |
July | 686196.68 | 1133.22 | 12-JUL-08:53 | 20.00 |
August | 1056204.04 | 1197.23 | 18-AUG-08:53 | 21.10 |
September | 68605521.80 | 1936.68 | 29-SEP-08:62 | 5.05 |
October | 0.368469E+09 | 2000.80 | 26-OCT-08:61 | 1.28 |
November | 0.128315E+10 | 2101.92 | 26-NOV-16:13 | -13.9 |
December | 0.231017E+10 | 2132.75 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.100842E+11 | |||
Minimum of Months | 686196.68 | 1077.76 | -33.7 | |
Maximum of Months | 0.277411E+10 | 2275.47 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155597E+09 | 395.26 | 19-JAN-05:00 | -27.2 |
February | 37511689.50 | 329.22 | 04-FEB-06:00 | -30.6 |
March | 5593109.40 | 145.66 | 05-MAR-06:00 | -8.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 14232151.45 | 276.65 | 28-NOV-05:00 | -21.7 |
December | 0.105473E+09 | 312.07 | 12-DEC-05:00 | -20.0 |
Annual Sum or Average | 0.318407E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.155597E+09 | 395.26 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544115E+09 | 614.43 | 31-JAN-16:01 | -20.1 |
February | 0.338893E+09 | 674.36 | 03-FEB-11:13 | -29.0 |
March | 0.122178E+09 | 591.54 | 05-MAR-16:01 | -9.6 |
April | 22776099.78 | 564.49 | 29-APR-15:04 | 17.02 |
May | 761092.54 | 465.70 | 03-MAY-15:04 | 17.30 |
June | 245408.61 | 375.40 | 06-JUN-15:05 | 16.28 |
July | 135863.55 | 370.09 | 11-JUL-15:06 | 17.77 |
August | 303091.13 | 366.03 | 06-AUG-15:06 | 19.22 |
September | 1150927.49 | 537.27 | 30-SEP-15:03 | 10.92 |
October | 6824383.94 | 555.02 | 10-OCT-15:04 | 16.95 |
November | 0.177661E+09 | 601.62 | 25-NOV-16:02 | -18.1 |
December | 0.413373E+09 | 600.75 | 25-DEC-16:01 | -8.6 |
Annual Sum or Average | 0.162842E+10 | |||
Minimum of Months | 135863.55 | 366.03 | -29.0 | |
Maximum of Months | 0.544115E+09 | 674.36 | 19.22 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235561E+10 | 2067.34 | 19-JAN-16:02 | -22.9 |
February | 0.154443E+10 | 2073.32 | 04-FEB-19:02 | -20.0 |
March | 0.829925E+09 | 1995.03 | 01-MAR-16:02 | -3.9 |
April | 0.365045E+09 | 1974.73 | 03-APR-08:62 | -5.9 |
May | 15588228.80 | 1099.45 | 11-MAY-15:04 | 16.70 |
June | 3857067.35 | 1169.16 | 03-JUN-08:03 | 8.68 |
July | 682419.76 | 979.47 | 06-JUL-08:04 | 19.90 |
August | 1092649.77 | 925.02 | 06-AUG-08:04 | 12.80 |
September | 48252399.28 | 1269.23 | 25-SEP-18:03 | 11.42 |
October | 0.251452E+09 | 1935.93 | 26-OCT-08:61 | 1.28 |
November | 0.108642E+10 | 2044.24 | 26-NOV-16:13 | -13.9 |
December | 0.201008E+10 | 2083.34 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.851243E+10 | |||
Minimum of Months | 682419.76 | 925.02 | -22.9 | |
Maximum of Months | 0.235561E+10 | 2083.34 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274968E+10 | 2086.27 | 31-JAN-16:01 | -20.1 |
February | 0.187320E+10 | 2253.82 | 01-FEB-18:04 | -27.5 |
March | 0.989758E+09 | 2005.79 | 05-MAR-16:01 | -9.6 |
April | 0.421040E+09 | 1966.22 | 03-APR-08:62 | -5.9 |
May | 18892964.92 | 1557.56 | 20-MAY-18:43 | 13.68 |
June | 4320037.08 | 1059.59 | 03-JUN-08:03 | 8.68 |
July | 663117.81 | 934.90 | 10-JUL-21:53 | 15.00 |
August | 819307.36 | 912.50 | 06-AUG-08:04 | 12.80 |
September | 58389448.09 | 1383.25 | 24-SEP-18:03 | 11.52 |
October | 0.363275E+09 | 1938.18 | 26-OCT-08:61 | 1.28 |
November | 0.128643E+10 | 2043.91 | 26-NOV-16:13 | -13.9 |
December | 0.232110E+10 | 2076.25 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.100876E+11 | |||
Minimum of Months | 663117.81 | 912.50 | -27.5 | |
Maximum of Months | 0.274968E+10 | 2253.82 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.913852E+09 | 2018.80 | 31-JAN-11:42 | -23.1 |
February | 0.468440E+09 | 2510.13 | 04-FEB-11:22 | -23.0 |
March | 51121700.20 | 593.67 | 01-MAR-15:00 | -3.9 |
April | 6451849.39 | 327.16 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.215725E+09 | 1930.05 | 26-NOV-08:51 | -23.3 |
December | 0.635992E+09 | 1622.84 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.229158E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.913852E+09 | 2510.13 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318591E+10 | 2493.58 | 19-JAN-19:13 | -23.3 |
February | 0.206527E+10 | 2713.60 | 04-FEB-08:03 | -30.3 |
March | 0.124556E+10 | 2386.79 | 01-MAR-16:02 | -3.9 |
April | 0.533862E+09 | 2356.69 | 03-APR-08:62 | -5.9 |
May | 48938074.58 | 2267.69 | 02-MAY-08:61 | 4.08 |
June | 21005646.19 | 1207.92 | 04-JUN-08:03 | 11.38 |
July | 1720396.06 | 958.28 | 06-JUL-08:04 | 19.90 |
August | 1751901.15 | 1066.57 | 07-AUG-08:03 | 15.47 |
September | 0.118493E+09 | 2254.78 | 29-SEP-08:62 | 5.05 |
October | 0.457672E+09 | 2349.39 | 26-OCT-08:61 | 1.28 |
November | 0.154651E+10 | 2469.14 | 26-NOV-16:13 | -13.9 |
December | 0.272574E+10 | 2509.40 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.119524E+11 | |||
Minimum of Months | 1720396.06 | 958.28 | -30.3 | |
Maximum of Months | 0.318591E+10 | 2713.60 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363226E+10 | 2694.98 | 31-JAN-08:03 | -29.7 |
February | 0.244667E+10 | 2702.66 | 01-FEB-08:03 | -32.2 |
March | 0.146441E+10 | 2379.52 | 06-MAR-09:02 | -9.5 |
April | 0.598440E+09 | 2350.45 | 04-APR-08:61 | -3.7 |
May | 50759401.18 | 2266.42 | 02-MAY-08:61 | 4.08 |
June | 21241022.02 | 1191.84 | 04-JUN-08:03 | 11.38 |
July | 730626.17 | 1071.28 | 12-JUL-08:53 | 20.00 |
August | 1187261.55 | 1244.01 | 08-AUG-08:53 | 20.00 |
September | 0.141247E+09 | 2274.20 | 29-SEP-08:62 | 5.05 |
October | 0.623904E+09 | 2344.47 | 26-OCT-08:61 | 1.28 |
November | 0.179941E+10 | 2464.62 | 26-NOV-16:13 | -13.9 |
December | 0.308923E+10 | 2497.67 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.138695E+11 | |||
Minimum of Months | 730626.17 | 1071.28 | -32.2 | |
Maximum of Months | 0.363226E+10 | 2702.66 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113276E+10 | 1284.63 | 26-JAN-16:13 | -11.5 |
February | 0.656493E+09 | 1244.98 | 28-FEB-19:02 | -15.7 |
March | 0.391950E+09 | 1244.43 | 01-MAR-16:02 | -3.9 |
April | 0.181488E+09 | 1230.84 | 03-APR-08:62 | -5.9 |
May | 8327063.41 | 685.06 | 09-MAY-15:04 | 17.62 |
June | 2508616.42 | 649.13 | 03-JUN-08:03 | 8.68 |
July | 877269.62 | 571.08 | 10-JUL-15:04 | 18.30 |
August | 906325.30 | 485.76 | 06-AUG-08:04 | 12.80 |
September | 20565254.15 | 545.07 | 13-SEP-18:04 | 17.12 |
October | 76141137.81 | 1194.69 | 26-OCT-08:61 | 1.28 |
November | 0.487975E+09 | 1272.13 | 26-NOV-16:13 | -13.9 |
December | 0.984167E+09 | 1301.05 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.394415E+10 | |||
Minimum of Months | 877269.62 | 485.76 | -19.1 | |
Maximum of Months | 0.113276E+10 | 1301.05 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9597030.35 | 4950.13 | 06-JAN-10:41 | -23.2 |
February | 20013089.23 | 5943.78 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 339308.02 | 3165.80 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 29949427.60 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 20013089.23 | 5943.78 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6935520.54 | 4719.51 | 06-JAN-10:41 | -23.2 |
February | 10862929.19 | 5745.66 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 174711.35 | 2911.86 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 17973161.08 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 10862929.19 | 5745.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381822E+10 | 5918.54 | 31-JAN-11:42 | -23.1 |
February | 0.182524E+10 | 7254.36 | 04-FEB-11:22 | -23.0 |
March | 0.344791E+09 | 2076.19 | 06-MAR-07:10 | -12.7 |
April | 20092762.41 | 823.51 | 03-APR-06:05 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.922486E+09 | 5798.58 | 26-NOV-08:51 | -23.3 |
December | 0.254650E+10 | 4539.39 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.947734E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.381822E+10 | 7254.36 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137273E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118668E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122017E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108820E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.100426E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.943052E+09 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.976412E+09 | 1701.53 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.105647E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.114096E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128357E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.130868E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.139780E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.139790E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.943052E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.139780E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.949127E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.851521E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.937522E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.895688E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.917716E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.885384E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.910218E+10 | 9504.80 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923280E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.899930E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.940012E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.918179E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.950216E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109788E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.851521E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.950216E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280253E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248130E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264408E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245212E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.240571E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228996E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236708E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246339E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250707E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271012E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.269615E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284647E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306660E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228996E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284647E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280253E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248130E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264408E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245212E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.240571E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228996E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236708E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246339E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250707E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271012E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.269615E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284647E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306660E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228996E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284647E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114514E+10 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859916E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686101E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3617669.98 | 0.459057E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3981320.91 | 0.239944E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26220490.66 | 0.123241E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21243547.33 | 76095730.85 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20636155.91 | 0.102559E+09 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12805069.98 | 0.222647E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452796E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677976E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973202E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88504254.79 | 0.601867E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76095730.85 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26220490.66 | 0.114514E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445041E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335184E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271734E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1586826.23 | 0.187141E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701255.67 | 0.107900E+09 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10075129.64 | 59142606.66 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8318299.74 | 40233283.25 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8266472.73 | 50751485.41 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5474535.42 | 98263204.76 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.24 | 0.187235E+09 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269921E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377992E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35422928.69 | 0.243054E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40233283.25 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10075129.64 | 0.445041E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104840E+10 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777847E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621424E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4415353.85 | 0.418828E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4573526.09 | 0.238698E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23952921.80 | 0.133458E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19572078.06 | 91720882.81 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19914613.07 | 0.115777E+09 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13828628.45 | 0.221518E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74804.10 | 0.414047E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621548E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883470E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86331925.43 | 0.558673E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91720882.81 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23952921.80 | 0.104840E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603470E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447281E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357348E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2617856.43 | 0.239397E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2761619.73 | 0.133705E+09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14387623.08 | 74047716.16 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12016156.92 | 50015836.52 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12147636.73 | 63519371.23 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8287053.15 | 0.123733E+09 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47168.65 | 0.234565E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356735E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509660E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52265114.69 | 0.319348E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50015836.52 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14387623.08 | 0.603470E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147189E+10 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110442E+10 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923975E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 5702332.87 | 0.630234E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 5874164.04 | 0.355053E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 36198304.40 | 0.186278E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 32461406.07 | 0.119095E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 31783691.21 | 0.152422E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 21171533.74 | 0.316147E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 1528.68 | 0.625175E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911776E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128479E+10 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.133193E+09 | 0.808126E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119095E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 36198304.40 | 0.147189E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.137273E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254901E+10 |
February | 0.236489E+11 | 0.118668E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193228E+10 |
March | 0.262800E+11 | 0.122017E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156243E+10 |
April | 0.253579E+11 | 0.108820E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7749734.14 | 0.107002E+10 |
May | 0.262123E+11 | 0.100426E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8142985.97 | 0.609248E+09 |
June | 0.254132E+11 | 0.943052E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55664044.87 | 0.328015E+09 |
July | 0.261570E+11 | 0.976412E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45390847.48 | 0.219371E+09 |
August | 0.262677E+11 | 0.105647E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43313387.86 | 0.280726E+09 |
September | 0.253456E+11 | 0.114096E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28059592.33 | 0.553070E+09 |
October | 0.261693E+11 | 0.128357E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107187E+10 |
November | 0.253025E+11 | 0.130868E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153900E+10 |
December | 0.261570E+11 | 0.139780E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217196E+10 |
Annual Sum or Average | 0.308468E+12 | 0.139790E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188321E+09 | 0.138870E+11 |
Minimum of Months | 0.236489E+11 | 0.943052E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219371E+09 |
Maximum of Months | 0.262800E+11 | 0.139780E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55664044.87 | 0.254901E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.949127E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734871E+10 |
February | 0.702046E+11 | 0.851521E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556467E+10 |
March | 0.780153E+11 | 0.937522E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454243E+10 |
April | 0.752779E+11 | 0.895688E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24553519.77 | 0.312936E+10 |
May | 0.778146E+11 | 0.917716E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26504280.46 | 0.182111E+10 |
June | 0.754422E+11 | 0.885384E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165044E+09 | 0.992202E+09 |
July | 0.776503E+11 | 0.910218E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137031E+09 | 0.667718E+09 |
August | 0.779788E+11 | 0.923280E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132483E+09 | 0.842134E+09 |
September | 0.752414E+11 | 0.899930E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85208204.71 | 0.164670E+10 |
October | 0.776868E+11 | 0.940012E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315044E+10 |
November | 0.751137E+11 | 0.918179E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450134E+10 |
December | 0.776503E+11 | 0.950216E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627534E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109788E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570824E+09 | 0.404822E+11 |
Minimum of Months | 0.702046E+11 | 0.851521E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667718E+09 |
Maximum of Months | 0.780153E+11 | 0.950216E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165044E+09 | 0.734871E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664947E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507726E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394419E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3123478.97 | 0.263380E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3423762.57 | 0.140101E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21497048.84 | 67313436.93 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20143495.84 | 36161501.30 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18715008.75 | 50307903.02 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11487352.41 | 0.122836E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20845.44 | 0.259723E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389822E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556259E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78410992.81 | 0.345300E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36161501.30 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21497048.84 | 0.664947E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662756E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503573E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390459E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2949914.47 | 0.263420E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3086783.41 | 0.146762E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19911977.57 | 77016920.83 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18077328.82 | 49363922.72 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17055347.46 | 61951094.79 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10760410.21 | 0.127431E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6317.53 | 0.256136E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386830E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553140E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71848079.46 | 0.347884E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49363922.72 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19911977.57 | 0.662756E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163456E+09 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135048E+09 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113357E+09 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171607.22 | 91847632.19 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 132061.33 | 63077822.91 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446274.55 | 37910652.77 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543919.78 | 29339009.70 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769249.34 | 34028996.33 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705096.29 | 55655473.85 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97495199.30 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116914E+09 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138293E+09 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768208.51 | 0.107642E+10 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29339009.70 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446274.55 | 0.163456E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185443E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141024E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109994E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 847867.75 | 73562584.81 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 892224.87 | 39653307.00 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5646306.36 | 20155090.80 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5162990.65 | 12059211.40 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4917755.39 | 15773946.88 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3115368.49 | 34858359.58 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13660.14 | 71920924.03 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109096E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155327E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20596173.65 | 0.968869E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12059211.40 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5646306.36 | 0.185443E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664562E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507280E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395729E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3127543.93 | 0.264035E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3425790.85 | 0.141144E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21492027.94 | 67730469.06 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20163420.47 | 36450188.06 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18717163.13 | 50691567.48 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11505261.89 | 0.123671E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21619.51 | 0.260799E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389577E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555652E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78452827.73 | 0.345732E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36450188.06 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21492027.94 | 0.664562E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662490E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502804E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391584E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2947055.58 | 0.263482E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3066552.43 | 0.146103E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19800720.83 | 76501617.17 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17991474.07 | 49249638.86 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17006090.64 | 60941938.70 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10725014.53 | 0.127734E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9091.61 | 0.256451E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386572E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553012E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71545999.69 | 0.347693E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49249638.86 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19800720.83 | 0.662490E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809771E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608248E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478318E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3397203.32 | 0.322420E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3576806.98 | 0.181200E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18684440.18 | 0.100137E+09 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15029099.28 | 68198697.33 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15508618.89 | 85386686.52 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10421837.29 | 0.166628E+09 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43967.10 | 0.312753E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475481E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680693E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66661973.03 | 0.428923E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68198697.33 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18684440.18 | 0.809771E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665055E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507492E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393740E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3068777.93 | 0.263368E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3350911.59 | 0.140811E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21160334.78 | 67757999.41 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19714534.07 | 36651345.63 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18351322.76 | 50804130.53 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11290611.73 | 0.123020E+09 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19266.35 | 0.259460E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389389E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556147E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76955759.20 | 0.345370E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36651345.63 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21160334.78 | 0.665055E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663248E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503622E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390152E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2903957.17 | 0.263575E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3026301.85 | 0.148405E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19619299.34 | 78493883.01 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17723578.97 | 50703181.13 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16753800.16 | 63325264.95 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10596868.07 | 0.127813E+09 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6047.46 | 0.255492E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386688E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553899E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70629853.03 | 0.348541E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50703181.13 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19619299.34 | 0.663248E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344653E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264068E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204664E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1571068.64 | 0.135809E+09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1718355.44 | 72288261.91 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10848658.06 | 34786064.96 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10117614.21 | 18690355.33 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9397285.61 | 25979132.04 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5773473.81 | 63606543.49 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6717.36 | 0.134986E+09 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202514E+09 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288209E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39433173.15 | 0.179025E+10 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18690355.33 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10848658.06 | 0.344653E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280253E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171151E+10 |
February | 0.415303E+11 | 0.248130E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130366E+10 |
March | 0.461508E+11 | 0.264408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107924E+10 |
April | 0.445315E+11 | 0.245212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4691658.69 | 0.748895E+09 |
May | 0.460320E+11 | 0.240571E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4405921.00 | 0.441258E+09 |
June | 0.446286E+11 | 0.228996E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30645327.12 | 0.240808E+09 |
July | 0.459349E+11 | 0.236708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23066396.04 | 0.161942E+09 |
August | 0.461292E+11 | 0.246339E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23575600.82 | 0.200771E+09 |
September | 0.445099E+11 | 0.250707E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17173766.85 | 0.389416E+09 |
October | 0.459565E+11 | 0.271012E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743443E+09 |
November | 0.444343E+11 | 0.269615E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106295E+10 |
December | 0.459349E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147419E+10 |
Annual Sum or Average | 0.541708E+12 | 0.306660E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103559E+09 | 0.955809E+10 |
Minimum of Months | 0.415303E+11 | 0.228996E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161942E+09 |
Maximum of Months | 0.461508E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30645327.12 | 0.171151E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280253E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172394E+10 |
February | 0.415303E+11 | 0.248130E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131255E+10 |
March | 0.461508E+11 | 0.264408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108826E+10 |
April | 0.445315E+11 | 0.245212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4639519.49 | 0.754663E+09 |
May | 0.460320E+11 | 0.240571E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4369971.26 | 0.443643E+09 |
June | 0.446286E+11 | 0.228996E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30588124.15 | 0.241888E+09 |
July | 0.459349E+11 | 0.236708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22965108.27 | 0.162451E+09 |
August | 0.461292E+11 | 0.246339E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23361607.11 | 0.201440E+09 |
September | 0.445099E+11 | 0.250707E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17009055.22 | 0.391780E+09 |
October | 0.459565E+11 | 0.271012E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749719E+09 |
November | 0.444343E+11 | 0.269615E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107223E+10 |
December | 0.459349E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148697E+10 |
Annual Sum or Average | 0.541708E+12 | 0.306660E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102933E+09 | 0.962953E+10 |
Minimum of Months | 0.415303E+11 | 0.228996E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162451E+09 |
Maximum of Months | 0.461508E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30588124.15 | 0.172394E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155294E+10 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117523E+10 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976386E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4132263.38 | 0.674645E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3920239.67 | 0.394810E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27414494.62 | 0.215303E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 20587116.84 | 0.144465E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 20898559.45 | 0.179126E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15176976.19 | 0.349212E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670080E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963856E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134510E+10 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 92129650.14 | 0.864116E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144465E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27414494.62 | 0.155294E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143002E+10 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106635E+10 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849264E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4924654.07 | 0.574310E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4660989.64 | 0.325195E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28279268.18 | 0.180560E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21485529.87 | 0.122258E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22716093.94 | 0.151892E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16008051.01 | 0.291629E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11083.17 | 0.556663E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843262E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120718E+10 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98085669.89 | 0.759858E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122258E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28279268.18 | 0.143002E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 630.32 | 30-JAN-11:40 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 680.70 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 499.56 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 15-APR-17:00 | 356.10 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 31-MAY-13:00 | 251.15 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 11-JUN-15:00 | 193.49 | 01-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 | 26-JUL-18:00 | 134.30 | 24-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.43 | 04-AUG-15:00 | 150.97 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.71 | 07-SEP-14:00 | 272.37 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 304.02 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 602.04 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 583.20 | 09-DEC-01:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.30 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 106.43 | 680.70 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 252.56 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 278.89 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 194.54 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 15-APR-16:00 | 139.15 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 31-MAY-13:00 | 104.28 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 11-JUN-15:00 | 85.45 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 | 26-JUL-15:00 | 61.85 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.04 | 04-AUG-15:00 | 69.72 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.36 | 06-SEP-14:00 | 111.95 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 20-OCT-15:00 | 123.82 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 246.53 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.88 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.85 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 42.04 | 278.89 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 607.76 | 31-JAN-04:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 672.33 | 02-FEB-06:10 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 455.70 | 06-MAR-01:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.25 | 15-APR-16:00 | 324.85 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.10 | 31-MAY-13:00 | 231.61 | 03-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 | 11-JUN-15:00 | 196.37 | 01-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.99 | 26-JUL-16:00 | 140.80 | 23-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 | 04-AUG-16:00 | 161.37 | 07-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.90 | 06-SEP-14:00 | 252.87 | 30-SEP-01:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 20-OCT-15:00 | 283.19 | 23-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 596.46 | 26-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 535.80 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.80 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 | 672.33 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 348.00 | 31-JAN-04:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 384.39 | 02-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 262.92 | 06-MAR-01:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.51 | 15-APR-17:00 | 187.42 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | 31-MAY-13:00 | 132.19 | 03-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 | 11-JUN-15:00 | 111.58 | 01-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 26-JUL-16:00 | 79.22 | 23-JUL-04:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 04-AUG-16:00 | 91.03 | 07-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.16 | 06-SEP-14:00 | 143.46 | 30-SEP-01:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 20-OCT-15:00 | 160.52 | 23-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 341.40 | 26-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 308.41 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.22 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 384.39 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 803.73 | 05-JAN-21:23 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 839.92 | 02-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 650.40 | 05-MAR-23:10 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 106.28 | 15-APR-17:00 | 490.43 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 98.07 | 31-MAY-13:00 | 345.14 | 03-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 151.62 | 11-JUN-15:20 | 269.77 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 105.49 | 02-JUL-16:00 | 200.55 | 24-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 155.21 | 04-AUG-16:00 | 232.38 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 129.24 | 07-SEP-13:50 | 366.92 | 29-SEP-23:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 1.92 | 20-OCT-15:00 | 425.30 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 792.02 | 25-NOV-21:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 776.12 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 200.55 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 155.21 | 839.92 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1431.12 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1568.60 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1110.67 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.00 | 15-APR-17:00 | 793.47 | 03-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.92 | 31-MAY-13:00 | 599.50 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.88 | 11-JUN-15:00 | 485.97 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.62 | 26-JUL-18:00 | 354.00 | 24-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.30 | 04-AUG-15:00 | 394.95 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.36 | 07-SEP-14:00 | 637.95 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 684.85 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1360.02 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1298.46 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.00 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 235.30 | 1568.60 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4157.78 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4585.01 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3245.18 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.07 | 15-APR-16:00 | 2341.64 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.44 | 31-MAY-13:00 | 1757.49 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.06 | 11-JUN-15:00 | 1424.95 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.72 | 26-JUL-15:00 | 1044.74 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.56 | 04-AUG-15:00 | 1170.59 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.96 | 06-SEP-14:00 | 1888.23 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2064.15 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4027.38 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3759.47 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.74 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 684.56 | 4585.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 413.90 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 463.14 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.11 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:10 | 207.81 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 31-MAY-15:10 | 146.87 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 | 11-JUN-15:10 | 111.92 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 26-JUL-15:10 | 76.59 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:10 | 88.68 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.59 | 06-SEP-15:10 | 159.16 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 20-OCT-15:10 | 177.57 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.55 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.10 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 463.14 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 409.14 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 459.39 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.08 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:10 | 207.79 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 31-MAY-15:10 | 146.86 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 11-JUN-15:10 | 111.91 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:10 | 76.58 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:10 | 88.67 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 06-SEP-15:10 | 159.14 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 20-OCT-15:09 | 177.55 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 393.54 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.06 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 459.39 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 104.67 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 120.98 | 02-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 71.05 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 15-APR-15:10 | 61.80 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 31-MAY-13:00 | 49.60 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 11-JUN-15:00 | 41.55 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 26-JUL-15:00 | 31.94 | 24-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 04-AUG-15:00 | 35.43 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 06-SEP-14:00 | 51.63 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 57.33 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 98.40 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 90.45 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 120.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 112.57 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 128.22 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 81.25 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 15-APR-15:10 | 58.00 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 31-MAY-15:10 | 40.99 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 11-JUN-15:10 | 31.24 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 26-JUL-15:10 | 21.37 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 04-AUG-15:10 | 24.75 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 06-SEP-15:10 | 44.42 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 | 20-OCT-15:07 | 49.56 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 108.77 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.47 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 128.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 411.10 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 461.80 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.10 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 | 15-APR-15:10 | 207.81 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 31-MAY-15:10 | 146.87 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 | 11-JUN-15:10 | 111.92 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 26-JUL-15:08 | 76.59 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.53 | 04-AUG-15:10 | 88.68 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 | 06-SEP-15:10 | 159.16 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 20-OCT-15:10 | 177.56 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 394.36 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.09 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.53 | 461.80 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.81 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 459.38 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.09 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 | 15-APR-15:07 | 207.79 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 31-MAY-15:10 | 146.86 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 11-JUN-15:10 | 111.91 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 26-JUL-15:08 | 76.58 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:10 | 88.67 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 06-SEP-15:08 | 159.15 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 20-OCT-15:10 | 177.55 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 391.58 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.07 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 459.38 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 479.70 | 31-JAN-04:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 537.07 | 02-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 351.00 | 06-MAR-01:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.60 | 15-APR-17:00 | 250.31 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.44 | 31-MAY-13:00 | 179.71 | 03-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.07 | 11-JUN-15:00 | 149.13 | 01-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.43 | 26-JUL-16:00 | 107.99 | 24-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.40 | 04-AUG-16:00 | 122.54 | 07-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 06-SEP-14:00 | 192.06 | 30-SEP-01:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 20-OCT-15:00 | 213.75 | 23-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 460.57 | 26-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 412.63 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.99 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.40 | 537.07 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 411.99 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.04 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.63 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 15-APR-17:00 | 208.29 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 31-MAY-15:10 | 147.33 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 | 11-JUN-15:10 | 112.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 26-JUL-15:10 | 77.01 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 | 04-AUG-15:10 | 89.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.06 | 06-SEP-15:10 | 159.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 20-OCT-15:10 | 178.04 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 394.32 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.64 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 | 460.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 406.30 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 458.08 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.61 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 15-APR-15:10 | 208.28 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 31-MAY-15:10 | 147.31 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 | 11-JUN-15:10 | 112.35 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 26-JUL-15:10 | 77.01 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 04-AUG-15:10 | 89.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 06-SEP-15:10 | 159.61 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 20-OCT-15:09 | 178.03 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 391.27 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.62 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 458.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 214.77 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 241.61 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 149.21 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 | 15-APR-15:10 | 106.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 | 31-MAY-15:10 | 75.38 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 11-JUN-15:10 | 57.49 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 26-JUL-15:10 | 39.40 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 04-AUG-15:10 | 45.59 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 06-SEP-15:10 | 81.67 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 20-OCT-15:10 | 91.09 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 202.69 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.30 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 241.61 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 953.31 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1049.67 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 759.81 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 | 15-APR-16:50 | 560.17 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 | 31-MAY-13:00 | 410.05 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.58 | 11-JUN-15:00 | 323.14 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 | 26-JUL-15:40 | 236.40 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 04-AUG-15:00 | 266.17 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 07-SEP-14:00 | 440.11 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 485.87 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 921.44 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 885.07 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.40 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 1049.67 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 951.96 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1046.61 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 765.03 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 | 15-APR-16:50 | 560.22 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 | 31-MAY-13:00 | 410.06 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.58 | 11-JUN-15:00 | 323.14 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 | 26-JUL-15:40 | 236.40 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 04-AUG-15:00 | 266.17 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 07-SEP-14:00 | 440.11 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 485.88 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 922.19 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 885.08 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.40 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 1046.61 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 818.29 | 05-JAN-21:17 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 855.39 | 02-FEB-21:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 664.20 | 05-MAR-24:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 81.45 | 15-APR-15:50 | 501.44 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 81.92 | 31-MAY-13:00 | 353.84 | 03-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 125.98 | 11-JUN-15:00 | 287.79 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 82.60 | 26-JUL-15:40 | 211.39 | 24-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 133.84 | 04-AUG-15:40 | 238.22 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 112.58 | 07-SEP-14:00 | 377.37 | 30-SEP-01:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 434.89 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 808.54 | 25-NOV-21:07 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 792.41 | 09-DEC-08:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 211.39 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 133.84 | 855.39 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 814.75 | 31-JAN-04:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 899.72 | 02-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 622.13 | 06-MAR-01:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.49 | 15-APR-17:00 | 443.89 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 31-MAY-13:00 | 313.50 | 03-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.16 | 11-JUN-15:00 | 263.07 | 01-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 26-JUL-15:00 | 187.23 | 24-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 | 04-AUG-15:00 | 209.67 | 07-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.06 | 07-SEP-14:00 | 339.83 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 20-OCT-15:00 | 379.22 | 23-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 793.84 | 26-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 731.24 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.23 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 | 899.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34937.96 | 19-JAN-04:40 | 11501.89 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31071.01 | 02-FEB-06:02 | 44729.58 | 29312.09 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12739.47 | 19-MAR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13143.78 | 16-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13743.38 | 29-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14783.36 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15551.07 | 30-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18602.45 | 25-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20634.92 | 13-SEP-20:55 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21050.56 | 31-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36751.03 | 26-NOV-07:07 | 26837.75 | 17587.25 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18760.79 | 07-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12739.47 | 10223.90 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36751.03 | 44729.58 | 29312.09 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2063.87 | 12-JAN-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.77 |
February | 2897.09 | 08-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.98 |
March | 2572.75 | 24-MAR-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.90 |
April | 3754.00 | 15-APR-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 | 0.00 |
May | 2751.91 | 31-MAY-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 0.00 |
June | 3162.11 | 30-JUN-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 0.00 |
July | 3301.67 | 30-JUL-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
August | 3615.80 | 29-AUG-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
September | 4630.86 | 07-SEP-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.39 | 0.00 |
October | 4206.61 | 20-OCT-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
November | 3950.44 | 04-NOV-12:50 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 |
December | 3036.53 | 03-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2063.87 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4630.86 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 84.39 | 263.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1430.96 | 05-JAN-21:13 | 3611.52 | 1845.37 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.30 |
February | 1482.97 | 02-FEB-06:00 | 1354.32 | 153.78 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.89 |
March | 1222.82 | 24-MAR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 |
April | 1680.51 | 18-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 |
May | 1819.56 | 31-MAY-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 |
June | 2023.34 | 30-JUN-20:50 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
July | 1995.34 | 03-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
August | 1942.99 | 02-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
September | 2021.12 | 07-SEP-20:04 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
October | 1435.15 | 20-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.82 |
November | 1510.24 | 25-NOV-21:12 | 5266.80 | 2691.17 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
December | 1051.05 | 03-DEC-11:35 | 902.88 | 461.34 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1051.05 | 902.88 | 153.78 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2023.34 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 278.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 705.37 | 13-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.68 |
February | 738.84 | 24-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.06 |
March | 836.28 | 20-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 |
April | 1088.25 | 16-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 0.00 |
May | 1137.45 | 31-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 0.00 |
June | 1558.57 | 30-JUN-19:53 | 1336.61 | 4105.06 | 5036.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
July | 1497.72 | 03-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
August | 1509.67 | 04-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 |
September | 1289.26 | 11-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 |
October | 894.71 | 11-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.17 |
November | 880.80 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.60 |
December | 684.34 | 04-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 684.34 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1558.57 | 1336.61 | 4105.06 | 5036.68 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 239.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 319.75 | 13-JAN-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 |
February | 406.12 | 24-FEB-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.16 |
March | 481.49 | 20-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 |
April | 634.75 | 16-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
May | 663.14 | 31-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
June | 708.94 | 30-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 0.00 |
July | 703.43 | 02-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 0.00 |
August | 698.48 | 04-AUG-10:45 | 97.92 | 139.91 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 | 0.00 |
September | 685.94 | 09-SEP-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
October | 510.59 | 20-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
November | 503.56 | 04-NOV-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.31 |
December | 242.47 | 03-DEC-21:00 | 146.88 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 242.47 | 97.92 | 139.91 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 708.94 | 220.32 | 251.84 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 | 143.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39484.57 | 05-JAN-21:42 | 4032.00 | 1444.82 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 776.21 |
February | 36797.77 | 24-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 |
March | 37313.30 | 28-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 177.49 |
April | 38291.73 | 18-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.68 |
May | 38641.87 | 31-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
June | 38841.68 | 26-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.66 | 0.00 |
July | 38685.00 | 03-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.19 | 0.00 |
August | 38720.80 | 03-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.76 | 0.00 |
September | 38673.07 | 07-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
October | 37783.50 | 20-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 128.41 |
November | 38279.48 | 25-NOV-21:23 | 2822.40 | 1011.37 | 15403.12 | 133815.84 | 0.00 | 0.00 | 0.00 | 0.00 | 755.44 |
December | 36117.21 | 01-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 447.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36117.21 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39484.57 | 4032.00 | 1444.82 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 37.66 | 776.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8981.47 | 12-JAN-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.39 |
February | 11434.92 | 08-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.06 |
March | 10417.92 | 25-MAR-13:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.14 |
April | 13921.10 | 15-APR-13:20 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 112.54 | 0.00 |
May | 11055.31 | 06-MAY-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
June | 11490.83 | 26-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 | 0.00 |
July | 12102.70 | 30-JUL-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 66.26 | 0.00 |
August | 12617.71 | 22-AUG-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 145.07 | 0.00 |
September | 15128.43 | 07-SEP-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 182.22 | 0.00 |
October | 14873.30 | 20-OCT-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.60 |
November | 14964.51 | 04-NOV-12:50 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.37 |
December | 12419.53 | 03-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8981.47 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15128.43 | 51228.00 | 1134.35 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 182.22 | 585.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 47658.64 | 19-JAN-01:51 | 456229.80 | 15841.33 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.19 |
February | 37550.81 | 02-FEB-06:00 | 45622.98 | 2112.18 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4585.01 |
March | 27361.99 | 24-MAR-20:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.75 |
April | 36043.20 | 18-APR-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.45 |
May | 37510.94 | 31-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 |
June | 40158.58 | 26-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 | 0.00 |
July | 39177.70 | 03-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 | 0.00 |
August | 39344.71 | 02-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 | 0.00 |
September | 40712.38 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.87 |
October | 33925.43 | 20-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.31 |
November | 44650.74 | 25-NOV-21:12 | 177422.70 | 36963.11 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3790.50 |
December | 25790.31 | 03-DEC-11:35 | 30415.32 | 5449.42 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1364.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25790.31 | 30415.32 | 2112.18 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47658.64 | 456229.80 | 36963.11 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 | 4585.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3927.17 | 12-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.42 |
February | 4089.03 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.51 |
March | 4113.83 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
April | 4145.18 | 26-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.48 |
May | 4175.91 | 21-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
June | 3674.08 | 17-JUN-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 0.00 |
July | 3646.80 | 21-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 |
August | 3656.74 | 30-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
September | 4113.06 | 30-SEP-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.85 |
October | 4146.73 | 19-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 |
November | 4163.01 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 |
December | 3849.89 | 01-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3646.80 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4175.91 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 167.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 560.30 | 12-JAN-16:03 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.67 |
February | 3837.36 | 24-FEB-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 |
March | 3966.93 | 25-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
April | 4057.33 | 29-APR-18:41 | 936.00 | 1422.89 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.54 |
May | 4632.02 | 20-MAY-18:41 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.06 |
June | 4176.52 | 16-JUN-16:32 | 583.20 | 298.81 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
July | 4042.01 | 23-JUL-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.44 |
August | 4155.41 | 11-AUG-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
September | 4515.58 | 24-SEP-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 |
October | 3952.90 | 29-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 |
November | 3972.56 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.04 |
December | 669.63 | 01-DEC-16:03 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 560.30 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | |
Maximum of Months | 4632.02 | 1386.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 205.19 | 30-JAN-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.99 |
February | 240.74 | 02-FEB-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 |
March | 421.32 | 24-MAR-13:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 |
April | 623.93 | 15-APR-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
May | 459.99 | 06-MAY-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
June | 477.41 | 26-JUN-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 0.00 |
July | 516.51 | 30-JUL-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
August | 583.21 | 29-AUG-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
September | 726.55 | 07-SEP-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
October | 703.70 | 20-OCT-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.37 |
November | 668.49 | 04-NOV-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
December | 124.96 | 07-DEC-15:15 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 124.96 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 726.55 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 105.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 280.07 | 13-JAN-19:03 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 |
February | 733.49 | 25-FEB-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 |
March | 1131.28 | 24-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
April | 1197.29 | 30-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 |
May | 1237.49 | 06-MAY-19:31 | 1170.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 |
June | 1168.13 | 23-JUN-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 |
July | 1137.74 | 18-JUL-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
August | 1183.22 | 11-AUG-18:11 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 0.00 |
September | 1191.29 | 19-SEP-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 |
October | 1123.15 | 19-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
November | 1094.10 | 04-NOV-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
December | 260.66 | 18-DEC-19:05 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 260.66 | 270.00 | 313.10 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1237.49 | 1800.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 50.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 622.87 | 13-JAN-16:03 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 |
February | 3647.55 | 24-FEB-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 |
March | 3738.11 | 24-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.56 |
April | 3780.86 | 26-APR-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.85 |
May | 3743.17 | 06-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 |
June | 3434.35 | 11-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
July | 3512.72 | 02-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
August | 3469.95 | 02-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
September | 3734.69 | 20-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 |
October | 3746.97 | 29-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 |
November | 3762.32 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 |
December | 2100.84 | 03-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 622.87 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3780.86 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 160.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 595.46 | 12-JAN-09:04 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.43 |
February | 3125.81 | 24-FEB-09:01 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.42 |
March | 3345.06 | 24-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
April | 3752.09 | 18-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 |
May | 3846.70 | 31-MAY-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 |
June | 4104.21 | 09-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 |
July | 3998.19 | 13-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 |
August | 3906.79 | 11-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
September | 3972.10 | 08-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
October | 3099.92 | 21-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
November | 2018.64 | 04-NOV-08:62 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.18 |
December | 491.13 | 03-DEC-09:03 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 491.13 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | |
Maximum of Months | 4104.21 | 680.40 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1590.84 | 31-JAN-04:00 | 2263.36 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.70 |
February | 2073.68 | 02-FEB-06:00 | 2263.36 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.07 |
March | 1805.54 | 20-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.43 |
April | 2361.22 | 18-APR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.84 | 0.00 |
May | 2421.24 | 31-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 0.00 |
June | 2607.49 | 30-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 0.00 |
July | 2614.68 | 02-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 0.00 |
August | 2542.82 | 02-AUG-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 0.00 |
September | 2567.59 | 09-SEP-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 0.00 |
October | 1911.27 | 20-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
November | 1865.93 | 04-NOV-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.60 |
December | 1614.52 | 03-DEC-11:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1590.84 | 1508.90 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2614.68 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 537.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4021.25 | 12-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 |
February | 4234.82 | 08-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.73 |
March | 4250.95 | 23-MAR-18:01 | 1108.80 | 1266.52 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 |
April | 4311.02 | 26-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.99 |
May | 4343.23 | 21-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 |
June | 3827.12 | 17-JUN-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
July | 3797.86 | 26-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 | 0.00 |
August | 3796.70 | 30-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 |
September | 4260.05 | 20-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 |
October | 4296.10 | 19-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 |
November | 4318.51 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
December | 3974.14 | 01-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3796.70 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4343.23 | 1108.80 | 1266.52 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 | 166.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 739.98 | 13-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 |
February | 3866.48 | 24-FEB-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.37 |
March | 4184.65 | 23-MAR-18:01 | 1108.80 | 1266.37 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.90 |
April | 4280.25 | 29-APR-18:41 | 936.00 | 1422.89 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.87 |
May | 4850.90 | 20-MAY-18:41 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 |
June | 4334.54 | 16-JUN-16:32 | 583.20 | 298.81 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
July | 4299.01 | 23-JUL-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 |
August | 4294.56 | 11-AUG-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 |
September | 4670.36 | 24-SEP-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.55 |
October | 4008.01 | 24-OCT-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 |
November | 4093.02 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.05 |
December | 762.96 | 02-DEC-16:03 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 739.98 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | |
Maximum of Months | 4850.90 | 1386.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2339.23 | 30-JAN-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.74 |
February | 2231.29 | 17-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.18 |
March | 2272.27 | 22-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 |
April | 2263.48 | 05-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 |
May | 2205.58 | 21-MAY-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
June | 1977.15 | 11-JUN-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 0.00 |
July | 2016.81 | 14-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 | 0.00 |
August | 2020.97 | 03-AUG-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 0.00 |
September | 2269.54 | 30-SEP-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 |
October | 2290.01 | 27-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
November | 2253.17 | 12-NOV-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.36 |
December | 2233.49 | 01-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1977.15 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2339.23 | 831.60 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 185.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29244.81 | 19-JAN-01:51 | 269887.68 | 4980.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.93 |
February | 18763.90 | 02-FEB-06:00 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.67 |
March | 18364.88 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.32 |
April | 21045.65 | 18-APR-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.28 |
May | 22245.38 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 |
June | 23011.00 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 | 0.00 |
July | 22726.17 | 03-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
August | 22572.78 | 03-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
September | 21995.18 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 |
October | 19166.90 | 20-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.19 |
November | 22505.31 | 25-NOV-21:23 | 83965.06 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.94 |
December | 15800.20 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15800.20 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29244.81 | 269887.68 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 | 1049.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30988.10 | 19-JAN-01:51 | 269887.68 | 4980.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.52 |
February | 19706.23 | 02-FEB-06:00 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.61 |
March | 20309.76 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.33 |
April | 22427.39 | 18-APR-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.28 |
May | 23550.91 | 31-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 |
June | 24232.55 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 0.00 |
July | 23931.75 | 03-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
August | 23805.63 | 03-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
September | 23249.50 | 07-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 |
October | 20896.12 | 20-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.19 |
November | 27827.75 | 25-NOV-21:23 | 83965.06 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.81 |
December | 17789.91 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17789.91 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30988.10 | 269887.68 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 1046.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27143.02 | 29-JAN-19:42 | 6404.54 | 3300.29 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 776.69 |
February | 27307.09 | 24-FEB-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 273.45 |
March | 28770.81 | 19-MAR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 143.54 |
April | 30768.83 | 18-APR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 31.37 | 0.00 |
May | 31303.63 | 31-MAY-10:37 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 53.37 | 0.00 |
June | 31534.56 | 11-JUN-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 75.78 | 0.00 |
July | 31571.91 | 02-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 49.78 | 0.00 |
August | 31269.97 | 01-AUG-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
September | 31346.43 | 08-SEP-10:37 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 59.12 | 0.00 |
October | 28955.99 | 01-OCT-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 |
November | 28615.31 | 25-NOV-21:23 | 7471.97 | 3300.29 | 59651.42 | 44985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 771.40 |
December | 26629.29 | 03-DEC-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 292.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26629.29 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31571.91 | 7471.97 | 3300.29 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 75.78 | 776.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2626.67 | 13-JAN-11:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.59 |
February | 3375.44 | 24-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.46 |
March | 3668.48 | 20-MAR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 |
April | 4834.99 | 18-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.80 | 0.00 |
May | 5125.34 | 31-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.40 | 0.00 |
June | 6559.30 | 30-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.53 | 0.00 |
July | 6290.38 | 05-JUL-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
August | 6770.60 | 04-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 0.00 |
September | 6631.48 | 07-SEP-13:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.74 | 0.00 |
October | 3895.85 | 20-OCT-10:50 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.60 |
November | 3755.93 | 04-NOV-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 |
December | 3230.18 | 03-DEC-11:35 | 1596.96 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2626.67 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6770.60 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 258.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.368829E+12 | 235743.13 | 19-JAN-20:19 | 0.109763E+13 | 1091809.93 | 30-JAN-21:19 |
February | 0.330103E+12 | 235684.47 | 08-FEB-20:10 | 0.865820E+12 | 1129040.87 | 02-FEB-21:49 |
March | 0.361891E+12 | 242525.65 | 24-MAR-19:10 | 0.666408E+12 | 595024.74 | 05-MAR-19:10 |
April | 0.371551E+12 | 345691.13 | 16-APR-19:40 | 0.552570E+12 | 585338.75 | 24-APR-17:49 |
May | 0.413479E+12 | 355210.85 | 31-MAY-19:40 | 0.509888E+12 | 540889.94 | 01-MAY-17:00 |
June | 0.496117E+12 | 391469.81 | 26-JUN-19:00 | 0.455434E+12 | 479868.08 | 01-JUN-17:00 |
July | 0.559867E+12 | 418492.64 | 26-JUL-19:40 | 0.424404E+12 | 351923.91 | 03-JUL-17:10 |
August | 0.538681E+12 | 404593.80 | 03-AUG-19:30 | 0.428794E+12 | 385720.30 | 06-AUG-21:00 |
September | 0.432724E+12 | 362098.54 | 07-SEP-19:10 | 0.470242E+12 | 536066.91 | 29-SEP-17:00 |
October | 0.371463E+12 | 253737.35 | 20-OCT-19:10 | 0.567393E+12 | 548881.61 | 28-OCT-18:19 |
November | 0.353487E+12 | 239091.11 | 03-NOV-19:10 | 0.681319E+12 | 1002382.11 | 25-NOV-21:00 |
December | 0.368012E+12 | 236740.56 | 11-DEC-20:10 | 0.841791E+12 | 713802.37 | 11-DEC-17:19 |
Annual Sum or Average | 0.496620E+13 | 0.756169E+13 | ||||
Minimum of Months | 0.330103E+12 | 235684.47 | 0.424404E+12 | 351923.91 | ||
Maximum of Months | 0.559867E+12 | 418492.64 | 0.109763E+13 | 1129040.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671532E+11 | 0.204621E+11 | 0.140828E+12 | 0.544239E+11 | 0.437109E+11 | 0.342338E+10 | 0.00 | 0.320156E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.770751E+10 | 0.00 |
February | 0.604321E+11 | 0.170493E+11 | 0.127191E+12 | 0.491571E+11 | 0.378654E+11 | 0.305937E+10 | 0.00 | 0.716975E+09 | 0.00 | 0.00 | 0.231561E+11 | 0.696588E+10 | 0.00 |
March | 0.664655E+11 | 0.168938E+11 | 0.140882E+12 | 0.544261E+11 | 0.398915E+11 | 0.442534E+10 | 0.00 | 0.454828E+10 | 0.00 | 0.00 | 0.214728E+11 | 0.770369E+10 | 0.00 |
April | 0.639806E+11 | 0.143175E+11 | 0.136245E+12 | 0.526675E+11 | 0.398069E+11 | 0.592771E+10 | 0.00 | 0.296860E+11 | 0.00 | 0.00 | 0.164080E+11 | 0.746525E+10 | 0.00 |
May | 0.656312E+11 | 0.130220E+11 | 0.140860E+12 | 0.544243E+11 | 0.434084E+11 | 0.940534E+10 | 0.00 | 0.677902E+11 | 0.00 | 0.00 | 0.593802E+10 | 0.770466E+10 | 0.00 |
June | 0.633487E+11 | 0.117117E+11 | 0.136336E+12 | 0.526695E+11 | 0.458355E+11 | 0.930591E+10 | 0.00 | 0.156625E+12 | 0.00 | 0.00 | 0.765723E+10 | 0.745684E+10 | 0.00 |
July | 0.655135E+11 | 0.124816E+11 | 0.140770E+12 | 0.544217E+11 | 0.484877E+11 | 0.974722E+10 | 0.00 | 0.207589E+12 | 0.00 | 0.00 | 0.780624E+10 | 0.771256E+10 | 0.00 |
August | 0.658085E+11 | 0.140140E+11 | 0.140892E+12 | 0.544257E+11 | 0.482350E+11 | 0.970632E+10 | 0.00 | 0.184967E+12 | 0.00 | 0.00 | 0.757306E+10 | 0.770438E+10 | 0.00 |
September | 0.642023E+11 | 0.154428E+11 | 0.136256E+12 | 0.526677E+11 | 0.443293E+11 | 0.870953E+10 | 0.00 | 0.902592E+11 | 0.00 | 0.00 | 0.827145E+10 | 0.746645E+10 | 0.00 |
October | 0.667746E+11 | 0.180561E+11 | 0.140818E+12 | 0.544237E+11 | 0.414686E+11 | 0.697555E+10 | 0.00 | 0.159619E+11 | 0.00 | 0.00 | 0.140644E+11 | 0.770334E+10 | 0.00 |
November | 0.649238E+11 | 0.192850E+11 | 0.136330E+12 | 0.526690E+11 | 0.399993E+11 | 0.409102E+10 | 0.00 | 0.398748E+10 | 0.00 | 0.00 | 0.197524E+11 | 0.744978E+10 | 0.00 |
December | 0.672967E+11 | 0.209581E+11 | 0.140770E+12 | 0.544229E+11 | 0.421578E+11 | 0.321685E+10 | 0.00 | 0.577828E+09 | 0.00 | 0.00 | 0.257561E+11 | 0.771344E+10 | 0.00 |
Annual Sum or Average | 0.781531E+12 | 0.193694E+12 | 0.165818E+13 | 0.640799E+12 | 0.515196E+12 | 0.779936E+11 | 0.00 | 0.763029E+12 | 0.00 | 0.00 | 0.183627E+12 | 0.907538E+11 | 0.00 |
Minimum of Months | 0.604321E+11 | 0.117117E+11 | 0.127191E+12 | 0.491571E+11 | 0.378654E+11 | 0.305937E+10 | 0.00 | 0.320156E+09 | 0.00 | 0.00 | 0.593802E+10 | 0.696588E+10 | 0.00 |
Maximum of Months | 0.672967E+11 | 0.209581E+11 | 0.140892E+12 | 0.544261E+11 | 0.484877E+11 | 0.974722E+10 | 0.00 | 0.207589E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.771344E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.641269E+12 | 0.00 | 0.304441E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.451492E+12 | 0.00 | 0.277124E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.208684E+12 | 0.00 | 0.305700E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.114009E+12 | 0.00 | 0.291605E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.679621E+11 | 0.00 | 0.289947E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.406689E+11 | 0.00 | 0.267651E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.644929E+10 | 0.00 | 0.266134E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.152879E+11 | 0.00 | 0.261467E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.680438E+11 | 0.00 | 0.255228E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.143214E+12 | 0.00 | 0.272276E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.258489E+12 | 0.00 | 0.275739E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.391912E+12 | 0.00 | 0.298059E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.240748E+13 | 0.00 | 0.336537E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.644929E+10 | 0.00 | 0.255228E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.641269E+12 | 0.00 | 0.305700E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 39169.97 | 02-JAN-07:19 | 26057.92 | 18-JAN-19:10 | 5071.46 | 30-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 39169.97 | 01-FEB-07:19 | 23435.14 | 28-FEB-19:10 | 4789.76 | 04-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 39169.97 | 13-MAR-06:19 | 23038.88 | 19-MAR-20:10 | 4379.75 | 05-MAR-17:30 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 39169.86 | 14-APR-06:19 | 29951.68 | 18-APR-21:00 | 4289.71 | 08-APR-08:09 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 39168.39 | 10-MAY-06:19 | 31451.02 | 31-MAY-21:00 | 4182.97 | 01-MAY-08:20 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 39168.78 | 13-JUN-06:19 | 33516.53 | 26-JUN-21:10 | 4371.37 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 39168.39 | 20-JUL-06:19 | 33076.29 | 03-JUL-21:10 | 4757.86 | 26-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:30 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 39168.59 | 23-AUG-06:19 | 34517.51 | 04-AUG-21:00 | 4586.58 | 03-AUG-21:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 39169.97 | 21-SEP-06:19 | 35587.11 | 07-SEP-21:00 | 4278.57 | 27-SEP-08:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 39169.97 | 02-OCT-06:19 | 29904.08 | 20-OCT-21:10 | 4309.27 | 05-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 39169.97 | 01-NOV-06:19 | 25242.18 | 03-NOV-21:10 | 4557.44 | 25-NOV-10:50 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 39169.97 | 01-DEC-07:19 | 27002.86 | 11-DEC-19:19 | 4423.77 | 25-DEC-16:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 39168.39 | 23038.88 | 4182.97 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 39169.97 | 35587.11 | 5071.46 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4345.01 | 12-JAN-16:30 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4744.27 | 31-JAN-07:19 | 0.00 |
February | 9016.39 | 24-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4745.15 | 03-FEB-07:30 | 0.00 |
March | 48279.24 | 25-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.56 | 13-MAR-18:10 | 0.00 |
April | 133564.08 | 18-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.57 | 10-APR-18:10 | 0.00 |
May | 131889.48 | 31-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:00 | 4738.32 | 15-MAY-06:10 | 0.00 |
June | 187632.04 | 11-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUN-03:09 | 4738.73 | 29-JUN-18:10 | 0.00 |
July | 199412.55 | 26-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:50 | 4738.33 | 17-JUL-06:40 | 0.00 |
August | 218436.64 | 04-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 01-AUG-08:30 | 4738.49 | 11-AUG-18:30 | 0.00 |
September | 157760.04 | 06-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-12:09 | 4738.33 | 01-SEP-18:00 | 0.00 |
October | 90868.18 | 20-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.66 | 16-OCT-18:10 | 0.00 |
November | 37271.91 | 03-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.60 | 22-NOV-19:10 | 0.00 |
December | 4126.35 | 01-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.71 | 22-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4126.35 | 0.00 | 0.00 | 9938.94 | 4738.32 | 0.00 | |||
Maximum of Months | 218436.64 | 0.00 | 0.00 | 9938.94 | 4745.15 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 235743.13 | 19-JAN-20:19 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 23120.04 | 1396.09 | 0.00 | 0.00 | 0.00 |
February | 235684.47 | 08-FEB-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 19412.83 | 3745.98 | 0.00 | 1499.42 | 0.00 |
March | 242525.65 | 24-MAR-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 20292.68 | 3438.39 | 0.00 | 8201.20 | 0.00 |
April | 345691.13 | 16-APR-19:40 | 59807.00 | 84978.71 | 12338.45 | 31515.42 | 25737.46 | 3875.84 | 0.00 | 112119.42 | 0.00 |
May | 355210.85 | 31-MAY-19:40 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 26782.50 | 3891.38 | 0.00 | 113704.46 | 0.00 |
June | 391469.81 | 26-JUN-19:00 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 28553.53 | 4233.95 | 0.00 | 147698.34 | 0.00 |
July | 418492.64 | 26-JUL-19:40 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 27239.14 | 4514.80 | 0.00 | 175533.99 | 0.00 |
August | 404593.80 | 03-AUG-19:30 | 64632.59 | 86439.81 | 12338.45 | 31552.61 | 27303.13 | 4405.32 | 0.00 | 161691.15 | 0.00 |
September | 362098.54 | 07-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 28408.24 | 3911.92 | 0.00 | 118843.67 | 0.00 |
October | 253737.35 | 20-OCT-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 23309.16 | 3445.22 | 0.00 | 26319.68 | 0.00 |
November | 239091.11 | 03-NOV-19:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 22308.99 | 4018.83 | 0.00 | 10540.97 | 0.00 |
December | 236740.56 | 11-DEC-20:10 | 64632.59 | 86439.81 | 12338.45 | 31547.24 | 24338.73 | 1343.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 235684.47 | 59807.00 | 84978.71 | 12338.45 | 31515.42 | 19412.83 | 1343.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 418492.64 | 64632.59 | 86439.81 | 12338.45 | 31553.12 | 28553.53 | 4514.80 | 0.00 | 175533.99 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 761468.57 | 31-JAN-04:10 | 0.00 | 304872.77 | 30-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 804620.23 | 02-FEB-05:00 | 0.00 | 305638.84 | 16-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 247611.88 | 05-MAR-19:10 | 0.00 | 305365.90 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 199376.60 | 06-APR-18:19 | 0.00 | 301571.31 | 03-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 189572.78 | 06-MAY-22:19 | 0.00 | 293851.11 | 04-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 186642.34 | 03-JUN-06:30 | 0.00 | 283021.38 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 89165.19 | 24-JUL-04:00 | 0.00 | 252983.85 | 01-JUL-21:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 162871.90 | 07-AUG-05:00 | 0.00 | 247162.34 | 01-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 198868.14 | 30-SEP-17:00 | 0.00 | 247865.51 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 207787.14 | 05-OCT-08:09 | 0.00 | 278704.11 | 25-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 721925.51 | 26-NOV-06:00 | 0.00 | 291193.28 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 368373.84 | 11-DEC-16:19 | 0.00 | 299376.82 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 89165.19 | 0.00 | 247162.34 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 804620.23 | 0.00 | 305638.84 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.00 | 19.38 | 37.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 134.17 | 16.93 | 134.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.17 | 17.46 | 171.17 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.17 | 19.38 | 134.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.67 | 16.58 | 77.67 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
February | 87.00 | 14.42 | 87.00 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 17.14 | 12.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.67 | 15.56 | 176.67 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.00 | 17.14 | 87.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.83 | 18.11 | 82.83 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
February | 93.00 | 14.99 | 93.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 18.94 | 10.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.17 | 16.60 | 186.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.00 | 18.94 | 93.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.83 | 18.97 | 98.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 138.50 | 16.33 | 138.50 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 19.67 | 10.33 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.67 | 17.52 | 247.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.50 | 19.67 | 138.50 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 123.67 | 18.93 | 123.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 139.50 | 15.99 | 139.50 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.67 | 19.49 | 12.67 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.83 | 17.47 | 275.83 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.50 | 19.49 | 139.50 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.17 | 11.84 | 63.17 | 11.84 | 0.00 | 11.84 | 0.00 | 11.84 |
February | 70.50 | 8.63 | 70.50 | 8.63 | 0.00 | 8.63 | 0.00 | 8.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.00 | 13.34 | 8.00 | 13.34 | 0.00 | 13.34 | 0.00 | 13.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.67 | 10.33 | 141.67 | 10.33 | 0.00 | 10.33 | 0.00 | 10.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.50 | 13.34 | 70.50 | 13.34 | 0.00 | 13.34 | 0.00 | 13.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.50 | 17.31 | 75.50 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
February | 83.33 | 14.83 | 83.33 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.50 | 17.90 | 11.50 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 170.33 | 16.14 | 170.33 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.33 | 17.90 | 83.33 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.50 | 18.07 | 77.50 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
February | 90.17 | 15.13 | 90.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 18.95 | 10.33 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 178.00 | 16.63 | 178.00 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.17 | 18.95 | 90.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 20.38 | 9.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 37.67 | 19.73 | 37.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 2.00 | 20.37 | 2.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 49.00 | 19.88 | 49.00 | 19.88 | 1.50 | 19.91 | 1.50 | 19.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.67 | 20.47 | 37.67 | 20.47 | 0.83 | 21.81 | 0.83 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 20.18 | 22.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 54.00 | 19.31 | 54.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.86 | 1.17 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.95 | 0.17 | 21.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.46 | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 2.67 | 20.34 | 2.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 79.50 | 19.59 | 79.50 | 19.59 | 3.33 | 19.64 | 3.33 | 19.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.00 | 20.46 | 54.00 | 20.46 | 1.33 | 21.95 | 1.33 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.67 | 20.00 | 53.67 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
February | 66.33 | 18.80 | 66.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
March | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.82 | 3.67 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.78 | 5.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 20.41 | 4.83 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 6.67 | 20.27 | 6.67 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 131.83 | 19.43 | 131.83 | 19.43 | 14.83 | 19.55 | 14.83 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.33 | 20.49 | 66.33 | 20.49 | 5.67 | 21.82 | 5.67 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 20.26 | 12.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
February | 44.67 | 19.46 | 44.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 2.33 | 20.36 | 2.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 59.83 | 19.67 | 59.83 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.67 | 20.49 | 44.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 20.12 | 30.17 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
February | 57.00 | 18.99 | 57.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.09 | 0.33 | 22.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.08 | 1.33 | 22.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.34 | 4.33 | 22.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.35 | 6.17 | 22.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.15 | 3.50 | 22.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.20 | 1.50 | 22.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 3.17 | 20.34 | 3.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 91.17 | 19.42 | 91.17 | 19.42 | 17.17 | 19.67 | 17.17 | 19.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.00 | 20.44 | 57.00 | 20.44 | 6.17 | 22.35 | 6.17 | 22.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.50 | 19.34 | 83.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 122.67 | 17.89 | 122.67 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.33 | 19.76 | 11.33 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.50 | 18.54 | 217.50 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.67 | 19.76 | 122.67 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.00 | 20.28 | 16.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
February | 41.33 | 19.67 | 41.33 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 2.67 | 20.32 | 2.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 60.33 | 19.86 | 60.33 | 19.86 | 4.33 | 19.93 | 4.33 | 19.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.33 | 20.46 | 41.33 | 20.46 | 1.33 | 21.82 | 1.33 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 20.12 | 41.17 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
February | 54.83 | 19.11 | 54.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.93 | 1.00 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.82 | 2.17 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.78 | 0.83 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.45 | 1.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 3.83 | 20.29 | 3.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 101.33 | 19.59 | 101.33 | 19.59 | 7.67 | 19.67 | 7.67 | 19.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.83 | 20.45 | 54.83 | 20.45 | 3.17 | 21.93 | 3.17 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.43 | 2.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 14.33 | 20.24 | 14.33 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.83 | 0.83 | 21.83 |
November | 0.17 | 20.48 | 0.17 | 20.48 | 0.50 | 21.34 | 0.50 | 21.56 |
December | 2.33 | 20.39 | 2.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Annual Sum or Average | 19.17 | 20.29 | 19.17 | 20.29 | 4.17 | 20.43 | 4.17 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.33 | 20.48 | 14.33 | 20.48 | 1.83 | 21.83 | 1.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 17.48 | 42.17 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
February | 79.50 | 15.28 | 79.50 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 19.31 | 2.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.00 | 16.10 | 124.00 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.50 | 19.31 | 79.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.50 | 17.50 | 40.50 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
February | 78.17 | 15.24 | 78.17 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 19.22 | 1.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.50 | 16.06 | 120.50 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.17 | 19.22 | 78.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.67 | 14.20 | 38.67 | 14.20 | 0.00 | 14.20 | 0.00 | 14.20 |
February | 51.00 | 11.69 | 51.00 | 11.69 | 0.00 | 11.69 | 0.00 | 11.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.83 | 14.79 | 6.83 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.50 | 12.91 | 96.50 | 12.91 | 0.00 | 12.91 | 0.00 | 12.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 14.79 | 51.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.33 | 18.47 | 92.33 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
February | 117.17 | 16.01 | 117.17 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 18.94 | 12.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.50 | 17.19 | 221.50 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.17 | 18.94 | 117.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.59 | 63.83 | 22.38 | 63.83 | 22.20 |
February | 672.00 | 21.40 | 140.83 | 20.66 | 140.83 | 20.13 |
March | 744.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
April | 720.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
May | 744.00 | 22.20 | 8.83 | 22.21 | 8.83 | 22.21 |
June | 719.67 | 22.73 | 47.33 | 22.74 | 47.33 | 22.75 |
July | 560.00 | 23.09 | 120.83 | 23.16 | 92.67 | 23.18 |
August | 252.50 | 23.48 | 324.00 | 23.70 | 98.17 | 23.71 |
September | 215.33 | 23.75 | 148.17 | 23.84 | 15.17 | 23.84 |
October | 454.00 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
November | 537.83 | 23.71 | 11.67 | 23.72 | 0.00 | 23.72 |
December | 744.00 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 7107.33 | 22.75 | 865.50 | 22.71 | 466.83 | 22.62 |
Minimum of Months | 215.33 | 21.40 | 0.00 | 20.66 | 0.00 | 20.13 |
Maximum of Months | 744.00 | 23.86 | 324.00 | 23.86 | 140.83 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.67 | 20.60 | 624.33 | 20.53 | 624.33 | 20.51 |
February | 655.50 | 20.21 | 445.50 | 20.03 | 437.33 | 19.93 |
March | 715.50 | 21.17 | 295.17 | 21.15 | 285.33 | 21.12 |
April | 632.00 | 21.29 | 169.83 | 21.41 | 115.17 | 21.36 |
May | 658.00 | 21.47 | 50.00 | 21.62 | 0.00 | 21.62 |
June | 469.50 | 21.77 | 177.67 | 22.28 | 0.00 | 22.28 |
July | 398.00 | 22.05 | 245.00 | 22.63 | 0.00 | 22.63 |
August | 422.50 | 22.05 | 253.33 | 22.64 | 9.00 | 22.64 |
September | 497.33 | 21.61 | 168.67 | 22.15 | 5.00 | 22.14 |
October | 660.33 | 21.27 | 71.00 | 21.46 | 17.83 | 21.45 |
November | 696.00 | 21.03 | 349.67 | 21.01 | 337.00 | 20.98 |
December | 731.00 | 21.10 | 601.00 | 21.06 | 598.17 | 21.04 |
Annual Sum or Average | 7276.33 | 21.22 | 3451.17 | 21.32 | 2429.17 | 21.19 |
Minimum of Months | 398.00 | 20.21 | 50.00 | 20.03 | 0.00 | 19.93 |
Maximum of Months | 740.67 | 22.05 | 624.33 | 22.64 | 624.33 | 22.64 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 335.67 | 20.66 | 335.67 | 20.57 |
February | 672.00 | 20.57 | 165.00 | 19.99 | 165.00 | 19.59 |
March | 744.00 | 21.83 | 7.17 | 21.82 | 7.17 | 21.81 |
April | 651.33 | 22.25 | 32.50 | 22.32 | 5.00 | 22.33 |
May | 626.83 | 22.81 | 65.83 | 22.90 | 33.00 | 22.93 |
June | 390.17 | 23.08 | 284.17 | 23.40 | 107.00 | 23.46 |
July | 299.50 | 23.47 | 446.00 | 23.69 | 169.00 | 23.73 |
August | 270.00 | 23.45 | 405.83 | 23.68 | 141.67 | 23.70 |
September | 431.83 | 22.91 | 181.00 | 23.20 | 27.00 | 23.23 |
October | 734.67 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
November | 720.00 | 21.81 | 71.33 | 21.71 | 71.33 | 21.63 |
December | 744.00 | 21.33 | 138.67 | 21.28 | 138.67 | 21.24 |
Annual Sum or Average | 7028.33 | 22.02 | 2133.17 | 22.13 | 1200.50 | 22.05 |
Minimum of Months | 270.00 | 20.57 | 0.00 | 19.99 | 0.00 | 19.59 |
Maximum of Months | 744.00 | 23.47 | 446.00 | 23.69 | 335.67 | 23.73 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.72 | 599.83 | 20.69 | 599.83 | 20.68 |
February | 672.00 | 20.05 | 382.17 | 19.78 | 382.17 | 19.65 |
March | 744.00 | 21.12 | 235.83 | 21.09 | 235.83 | 21.07 |
April | 717.83 | 21.52 | 36.17 | 21.50 | 36.17 | 21.47 |
May | 735.17 | 22.34 | 0.67 | 22.34 | 0.00 | 22.34 |
June | 489.67 | 22.83 | 91.50 | 22.99 | 0.00 | 22.99 |
July | 309.83 | 23.15 | 156.00 | 23.39 | 0.00 | 23.39 |
August | 412.67 | 23.22 | 94.67 | 23.34 | 2.50 | 23.34 |
September | 593.50 | 22.65 | 20.33 | 22.69 | 0.00 | 22.69 |
October | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
November | 720.00 | 21.24 | 213.17 | 21.17 | 213.17 | 21.12 |
December | 744.00 | 21.00 | 543.83 | 21.00 | 543.83 | 21.00 |
Annual Sum or Average | 7626.67 | 21.61 | 2374.17 | 21.48 | 2013.50 | 21.33 |
Minimum of Months | 309.83 | 20.05 | 0.00 | 19.78 | 0.00 | 19.65 |
Maximum of Months | 744.00 | 23.22 | 599.83 | 23.39 | 599.83 | 23.39 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 637.50 | 20.62 | 637.50 | 20.61 |
February | 672.00 | 19.96 | 416.67 | 19.71 | 416.67 | 19.60 |
March | 744.00 | 21.05 | 308.50 | 21.03 | 308.50 | 21.03 |
April | 720.00 | 21.38 | 67.67 | 21.35 | 67.67 | 21.32 |
May | 742.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
June | 573.00 | 22.69 | 41.83 | 22.77 | 0.00 | 22.77 |
July | 462.17 | 23.04 | 30.83 | 23.09 | 0.00 | 23.09 |
August | 607.83 | 23.08 | 32.17 | 23.12 | 5.83 | 23.12 |
September | 663.17 | 22.47 | 0.33 | 22.47 | 0.00 | 22.47 |
October | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
November | 720.00 | 21.12 | 260.50 | 21.07 | 260.50 | 21.03 |
December | 744.00 | 21.00 | 604.33 | 21.00 | 604.33 | 21.00 |
Annual Sum or Average | 8136.17 | 21.57 | 2400.33 | 21.38 | 2301.00 | 21.23 |
Minimum of Months | 462.17 | 19.96 | 0.00 | 19.71 | 0.00 | 19.60 |
Maximum of Months | 744.00 | 23.08 | 637.50 | 23.12 | 637.50 | 23.12 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 387.17 | 20.41 | 389.33 | 21.01 | 175.00 | 20.67 |
February | 295.50 | 18.94 | 415.17 | 20.07 | 182.00 | 19.55 |
March | 251.50 | 22.86 | 486.00 | 23.31 | 148.83 | 23.43 |
April | 255.50 | 23.26 | 560.67 | 23.37 | 188.83 | 23.49 |
May | 295.33 | 23.73 | 670.67 | 23.43 | 268.50 | 23.55 |
June | 305.83 | 23.90 | 685.83 | 23.42 | 298.67 | 23.55 |
July | 331.00 | 23.96 | 734.33 | 23.41 | 330.83 | 23.54 |
August | 323.83 | 23.95 | 724.67 | 23.43 | 322.17 | 23.55 |
September | 295.00 | 23.71 | 651.50 | 23.43 | 266.67 | 23.55 |
October | 245.33 | 23.25 | 620.67 | 23.37 | 180.83 | 23.48 |
November | 267.67 | 22.58 | 480.33 | 23.07 | 164.83 | 23.13 |
December | 277.83 | 22.51 | 369.50 | 23.23 | 118.83 | 23.35 |
Annual Sum or Average | 3531.50 | 22.71 | 6788.67 | 22.96 | 2646.00 | 23.00 |
Minimum of Months | 245.33 | 18.94 | 369.50 | 20.07 | 118.83 | 19.55 |
Maximum of Months | 387.17 | 23.96 | 734.33 | 23.43 | 330.83 | 23.55 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 728.33 | 20.79 | 407.83 | 20.62 | 405.83 | 20.54 |
February | 641.00 | 20.62 | 221.83 | 20.18 | 204.83 | 19.86 |
March | 677.17 | 21.75 | 87.67 | 21.77 | 59.50 | 21.71 |
April | 556.00 | 22.01 | 133.50 | 22.33 | 25.50 | 22.35 |
May | 484.67 | 22.56 | 210.67 | 22.86 | 73.00 | 22.93 |
June | 358.67 | 22.99 | 475.17 | 23.35 | 172.50 | 23.42 |
July | 357.50 | 23.51 | 625.67 | 23.58 | 302.00 | 23.62 |
August | 297.17 | 23.49 | 618.33 | 23.61 | 242.50 | 23.64 |
September | 367.00 | 22.63 | 335.00 | 23.21 | 68.17 | 23.27 |
October | 573.67 | 22.22 | 99.83 | 22.48 | 0.00 | 22.48 |
November | 673.67 | 21.57 | 137.17 | 21.53 | 111.83 | 21.42 |
December | 712.33 | 21.33 | 283.67 | 21.26 | 274.00 | 21.21 |
Annual Sum or Average | 6427.17 | 21.89 | 3636.33 | 22.17 | 1939.67 | 22.11 |
Minimum of Months | 297.17 | 20.62 | 87.67 | 20.18 | 0.00 | 19.86 |
Maximum of Months | 728.33 | 23.51 | 625.67 | 23.61 | 405.83 | 23.64 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.15 | 205.33 | 20.88 | 205.33 | 20.70 |
February | 672.00 | 21.00 | 139.33 | 20.34 | 139.33 | 19.88 |
March | 728.83 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
April | 601.83 | 22.54 | 72.17 | 22.68 | 16.33 | 22.71 |
May | 463.83 | 22.99 | 199.83 | 23.23 | 71.00 | 23.29 |
June | 310.00 | 23.34 | 432.50 | 23.61 | 156.83 | 23.67 |
July | 310.00 | 23.81 | 589.33 | 23.79 | 276.83 | 23.83 |
August | 234.83 | 23.82 | 588.83 | 23.80 | 211.00 | 23.82 |
September | 317.67 | 23.10 | 317.00 | 23.48 | 58.50 | 23.52 |
October | 645.50 | 22.88 | 6.83 | 22.89 | 0.00 | 22.89 |
November | 659.17 | 22.10 | 38.17 | 22.03 | 33.33 | 21.95 |
December | 744.00 | 21.75 | 67.83 | 21.69 | 67.83 | 21.64 |
Annual Sum or Average | 6431.67 | 22.29 | 2657.17 | 22.51 | 1236.33 | 22.48 |
Minimum of Months | 234.83 | 21.00 | 0.00 | 20.34 | 0.00 | 19.88 |
Maximum of Months | 744.00 | 23.82 | 589.33 | 23.80 | 276.83 | 23.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 715.83 | 20.54 | 715.83 | 20.53 |
February | 672.00 | 20.66 | 551.00 | 20.58 | 551.00 | 20.56 |
March | 742.17 | 21.02 | 400.50 | 20.91 | 400.50 | 20.86 |
April | 693.17 | 21.21 | 166.67 | 21.12 | 158.83 | 21.04 |
May | 696.67 | 21.52 | 6.00 | 21.53 | 0.33 | 21.53 |
June | 616.67 | 21.40 | 30.17 | 21.49 | 2.33 | 21.49 |
July | 607.83 | 21.37 | 43.00 | 21.50 | 2.17 | 21.50 |
August | 613.00 | 21.38 | 32.33 | 21.47 | 5.33 | 21.48 |
September | 648.00 | 21.40 | 31.17 | 21.44 | 14.50 | 21.43 |
October | 738.17 | 21.34 | 84.17 | 21.29 | 84.17 | 21.25 |
November | 717.17 | 20.87 | 435.83 | 20.78 | 435.83 | 20.74 |
December | 744.00 | 20.66 | 692.00 | 20.63 | 692.00 | 20.62 |
Annual Sum or Average | 8232.83 | 21.10 | 3188.67 | 20.99 | 3062.83 | 20.91 |
Minimum of Months | 607.83 | 20.55 | 6.00 | 20.54 | 0.33 | 20.53 |
Maximum of Months | 744.00 | 21.52 | 715.83 | 21.53 | 715.83 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 742.17 | 20.45 | 742.17 | 20.45 |
February | 672.00 | 20.42 | 634.50 | 20.40 | 634.50 | 20.39 |
March | 744.00 | 20.82 | 486.00 | 20.73 | 486.00 | 20.69 |
April | 686.83 | 21.18 | 218.67 | 21.12 | 203.33 | 21.03 |
May | 660.33 | 21.73 | 66.50 | 22.02 | 19.67 | 22.09 |
June | 571.33 | 21.93 | 131.00 | 22.49 | 63.50 | 22.72 |
July | 554.33 | 22.17 | 180.17 | 22.80 | 97.83 | 23.05 |
August | 563.67 | 22.02 | 167.67 | 22.56 | 91.83 | 22.75 |
September | 622.83 | 21.58 | 54.00 | 21.73 | 26.50 | 21.74 |
October | 738.83 | 21.14 | 191.33 | 21.06 | 190.83 | 21.01 |
November | 720.00 | 20.72 | 489.33 | 20.64 | 489.33 | 20.61 |
December | 744.00 | 20.50 | 741.50 | 20.50 | 741.50 | 20.50 |
Annual Sum or Average | 8022.17 | 21.16 | 4102.83 | 21.15 | 3787.00 | 21.07 |
Minimum of Months | 554.33 | 20.42 | 54.00 | 20.40 | 19.67 | 20.39 |
Maximum of Months | 744.00 | 22.17 | 742.17 | 22.80 | 742.17 | 23.05 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 678.50 | 20.51 | 678.50 | 20.50 |
February | 672.00 | 20.53 | 471.67 | 20.43 | 471.67 | 20.39 |
March | 744.00 | 21.01 | 351.33 | 20.94 | 351.33 | 20.91 |
April | 720.00 | 21.31 | 69.50 | 21.26 | 69.50 | 21.22 |
May | 735.83 | 21.73 | 10.17 | 21.76 | 7.83 | 21.77 |
June | 699.67 | 21.98 | 44.17 | 22.08 | 36.50 | 22.14 |
July | 707.50 | 22.13 | 69.67 | 22.26 | 57.50 | 22.34 |
August | 737.33 | 22.11 | 71.17 | 22.21 | 70.67 | 22.29 |
September | 720.00 | 21.73 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 744.00 | 21.24 | 2.67 | 21.24 | 2.67 | 21.23 |
November | 720.00 | 20.94 | 340.50 | 20.85 | 340.50 | 20.81 |
December | 744.00 | 20.67 | 679.33 | 20.66 | 679.33 | 20.65 |
Annual Sum or Average | 8688.33 | 21.33 | 2789.17 | 21.19 | 2766.50 | 21.10 |
Minimum of Months | 672.00 | 20.53 | 0.50 | 20.43 | 0.50 | 20.39 |
Maximum of Months | 744.00 | 22.13 | 679.33 | 22.26 | 679.33 | 22.34 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 717.00 | 20.52 | 717.00 | 20.52 |
February | 672.00 | 20.63 | 553.50 | 20.56 | 553.50 | 20.54 |
March | 744.00 | 21.10 | 376.33 | 20.99 | 376.33 | 20.93 |
April | 696.17 | 21.26 | 179.83 | 21.14 | 178.33 | 21.07 |
May | 691.67 | 21.57 | 1.17 | 21.57 | 0.00 | 21.57 |
June | 590.67 | 21.34 | 13.83 | 21.39 | 2.17 | 21.39 |
July | 585.00 | 21.31 | 16.50 | 21.37 | 1.67 | 21.37 |
August | 603.50 | 21.37 | 14.33 | 21.41 | 4.50 | 21.42 |
September | 638.83 | 21.42 | 13.67 | 21.44 | 7.50 | 21.43 |
October | 744.00 | 21.41 | 70.17 | 21.37 | 70.17 | 21.34 |
November | 720.00 | 20.87 | 441.83 | 20.77 | 441.83 | 20.73 |
December | 744.00 | 20.63 | 694.00 | 20.61 | 694.00 | 20.60 |
Annual Sum or Average | 8173.83 | 21.11 | 3092.17 | 20.98 | 3047.00 | 20.90 |
Minimum of Months | 585.00 | 20.54 | 1.17 | 20.52 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.57 | 717.00 | 21.57 | 717.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 740.33 | 20.43 | 740.33 | 20.43 |
February | 672.00 | 20.38 | 635.00 | 20.36 | 635.00 | 20.36 |
March | 744.00 | 20.88 | 464.83 | 20.79 | 464.83 | 20.76 |
April | 697.00 | 21.24 | 215.50 | 21.13 | 211.17 | 21.04 |
May | 686.83 | 21.85 | 32.50 | 21.96 | 13.17 | 22.00 |
June | 532.50 | 21.81 | 109.50 | 22.31 | 48.83 | 22.52 |
July | 490.50 | 21.99 | 172.00 | 22.68 | 77.67 | 22.92 |
August | 541.00 | 21.94 | 122.67 | 22.35 | 79.00 | 22.52 |
September | 637.50 | 21.68 | 29.50 | 21.77 | 13.83 | 21.78 |
October | 744.00 | 21.17 | 142.17 | 21.14 | 142.17 | 21.11 |
November | 720.00 | 20.70 | 495.17 | 20.63 | 495.17 | 20.60 |
December | 744.00 | 20.49 | 736.33 | 20.49 | 736.33 | 20.49 |
Annual Sum or Average | 7953.33 | 21.15 | 3895.50 | 21.10 | 3657.50 | 21.02 |
Minimum of Months | 490.50 | 20.38 | 29.50 | 20.36 | 13.17 | 20.36 |
Maximum of Months | 744.00 | 21.99 | 740.33 | 22.68 | 740.33 | 22.92 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.80 | 583.67 | 20.78 | 583.67 | 20.77 |
February | 672.00 | 20.43 | 324.67 | 20.23 | 324.67 | 20.12 |
March | 744.00 | 21.09 | 170.67 | 21.07 | 170.67 | 21.06 |
April | 720.00 | 21.49 | 25.33 | 21.48 | 25.33 | 21.46 |
May | 744.00 | 22.20 | 21.50 | 22.21 | 21.50 | 22.22 |
June | 624.50 | 22.82 | 126.83 | 22.91 | 100.33 | 22.95 |
July | 529.17 | 23.19 | 193.17 | 23.26 | 161.00 | 23.28 |
August | 649.33 | 23.14 | 143.17 | 23.16 | 132.67 | 23.17 |
September | 655.17 | 22.53 | 18.83 | 22.55 | 18.83 | 22.57 |
October | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
November | 720.00 | 21.06 | 198.67 | 21.03 | 198.67 | 21.02 |
December | 744.00 | 21.00 | 502.83 | 21.00 | 502.83 | 21.00 |
Annual Sum or Average | 8290.17 | 21.69 | 2309.33 | 21.60 | 2240.17 | 21.53 |
Minimum of Months | 529.17 | 20.43 | 0.00 | 20.23 | 0.00 | 20.12 |
Maximum of Months | 744.00 | 23.19 | 583.67 | 23.26 | 583.67 | 23.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 730.00 | 20.49 | 730.00 | 20.48 |
February | 672.00 | 20.58 | 596.33 | 20.53 | 596.33 | 20.51 |
March | 741.83 | 20.92 | 484.17 | 20.82 | 484.17 | 20.77 |
April | 688.33 | 21.14 | 247.50 | 21.04 | 237.00 | 20.96 |
May | 680.83 | 21.46 | 23.33 | 21.48 | 12.00 | 21.48 |
June | 603.33 | 21.35 | 52.00 | 21.49 | 7.83 | 21.50 |
July | 596.00 | 21.33 | 71.17 | 21.54 | 8.50 | 21.55 |
August | 603.83 | 21.34 | 63.00 | 21.50 | 16.83 | 21.51 |
September | 642.67 | 21.35 | 57.17 | 21.41 | 28.17 | 21.39 |
October | 735.33 | 21.25 | 197.83 | 21.17 | 197.17 | 21.12 |
November | 716.83 | 20.78 | 495.33 | 20.71 | 495.33 | 20.67 |
December | 744.00 | 20.59 | 719.00 | 20.57 | 719.00 | 20.57 |
Annual Sum or Average | 8169.00 | 21.03 | 3736.83 | 20.94 | 3532.33 | 20.86 |
Minimum of Months | 596.00 | 20.49 | 23.33 | 20.49 | 7.83 | 20.48 |
Maximum of Months | 744.00 | 21.46 | 730.00 | 21.54 | 730.00 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.40 | 744.00 | 20.40 | 744.00 | 20.40 |
February | 672.00 | 20.36 | 649.67 | 20.35 | 649.67 | 20.34 |
March | 744.00 | 20.74 | 546.17 | 20.66 | 546.17 | 20.63 |
April | 685.33 | 21.12 | 299.33 | 21.06 | 280.67 | 20.98 |
May | 649.67 | 21.75 | 88.33 | 22.10 | 41.50 | 22.21 |
June | 567.83 | 22.01 | 151.67 | 22.64 | 78.83 | 22.93 |
July | 552.33 | 22.25 | 209.67 | 22.93 | 118.67 | 23.22 |
August | 560.17 | 22.06 | 193.83 | 22.66 | 112.67 | 22.88 |
September | 616.50 | 21.52 | 101.17 | 21.70 | 64.17 | 21.70 |
October | 737.67 | 21.04 | 337.83 | 20.95 | 336.33 | 20.90 |
November | 720.00 | 20.64 | 546.33 | 20.59 | 546.33 | 20.56 |
December | 744.00 | 20.47 | 743.67 | 20.47 | 743.67 | 20.47 |
Annual Sum or Average | 7993.50 | 21.13 | 4611.67 | 21.14 | 4262.67 | 21.07 |
Minimum of Months | 552.33 | 20.36 | 88.33 | 20.35 | 41.50 | 20.34 |
Maximum of Months | 744.00 | 22.25 | 744.00 | 22.93 | 744.00 | 23.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 20.92 | 615.33 | 20.82 | 615.33 | 20.78 |
February | 660.83 | 21.02 | 427.67 | 20.90 | 427.67 | 20.85 |
March | 729.50 | 21.22 | 307.67 | 21.10 | 307.67 | 21.03 |
April | 676.83 | 21.22 | 168.50 | 21.14 | 160.83 | 21.07 |
May | 693.67 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 629.17 | 21.43 | 11.67 | 21.45 | 9.00 | 21.47 |
July | 632.67 | 21.42 | 18.33 | 21.47 | 9.33 | 21.49 |
August | 631.00 | 21.41 | 33.50 | 21.47 | 17.83 | 21.49 |
September | 633.33 | 21.40 | 40.17 | 21.49 | 6.00 | 21.49 |
October | 689.67 | 21.37 | 35.67 | 21.37 | 30.83 | 21.35 |
November | 705.67 | 21.10 | 358.33 | 20.98 | 356.33 | 20.92 |
December | 738.00 | 20.94 | 593.00 | 20.83 | 593.00 | 20.79 |
Annual Sum or Average | 8163.67 | 21.24 | 2609.83 | 21.14 | 2533.83 | 21.06 |
Minimum of Months | 629.17 | 20.92 | 0.00 | 20.82 | 0.00 | 20.78 |
Maximum of Months | 743.33 | 21.52 | 615.33 | 21.52 | 615.33 | 21.52 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 712.17 | 22.26 | 112.67 | 21.87 | 112.67 | 21.57 |
February | 560.50 | 21.82 | 118.83 | 21.00 | 118.83 | 20.42 |
March | 486.83 | 23.24 | 52.00 | 23.31 | 0.00 | 23.31 |
April | 256.33 | 23.31 | 193.67 | 23.59 | 18.00 | 23.61 |
May | 106.33 | 23.84 | 563.17 | 23.94 | 85.00 | 23.94 |
June | 163.50 | 23.98 | 698.00 | 23.97 | 161.00 | 23.98 |
July | 278.50 | 24.00 | 744.00 | 23.98 | 278.50 | 23.98 |
August | 222.67 | 24.00 | 740.50 | 23.98 | 222.67 | 23.98 |
September | 120.83 | 23.65 | 506.50 | 23.91 | 67.00 | 23.92 |
October | 233.83 | 23.21 | 115.50 | 23.46 | 0.00 | 23.46 |
November | 474.33 | 22.98 | 105.67 | 23.06 | 15.67 | 22.98 |
December | 718.33 | 22.99 | 17.33 | 22.95 | 17.33 | 22.90 |
Annual Sum or Average | 4334.17 | 22.97 | 3967.83 | 23.27 | 1096.67 | 23.20 |
Minimum of Months | 106.33 | 21.82 | 17.33 | 21.00 | 0.00 | 20.42 |
Maximum of Months | 718.33 | 24.00 | 744.00 | 23.98 | 278.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 645.00 | 22.38 | 97.00 | 21.98 | 94.50 | 21.66 |
February | 450.67 | 21.61 | 108.67 | 20.69 | 106.50 | 20.05 |
March | 284.33 | 23.24 | 94.67 | 23.43 | 0.00 | 23.43 |
April | 120.17 | 23.32 | 286.67 | 23.78 | 14.00 | 23.79 |
May | 62.50 | 23.97 | 659.83 | 23.98 | 59.67 | 23.98 |
June | 144.50 | 24.00 | 712.50 | 23.99 | 144.50 | 23.99 |
July | 257.00 | 24.00 | 744.00 | 23.99 | 257.00 | 23.99 |
August | 204.83 | 24.00 | 743.33 | 23.99 | 204.83 | 23.99 |
September | 76.17 | 23.88 | 584.50 | 23.97 | 62.17 | 23.97 |
October | 94.00 | 23.28 | 231.50 | 23.77 | 0.00 | 23.77 |
November | 321.67 | 23.00 | 157.67 | 23.21 | 11.83 | 23.13 |
December | 576.50 | 23.10 | 0.33 | 23.09 | 0.33 | 23.09 |
Annual Sum or Average | 3237.33 | 22.97 | 4420.67 | 23.39 | 955.33 | 23.30 |
Minimum of Months | 62.50 | 21.61 | 0.33 | 20.69 | 0.00 | 20.05 |
Maximum of Months | 645.00 | 24.00 | 744.00 | 23.99 | 257.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 22.39 | 575.50 | 22.80 | 367.50 | 22.78 |
February | 479.17 | 21.97 | 551.50 | 22.27 | 412.17 | 22.22 |
March | 524.67 | 23.83 | 643.50 | 23.88 | 476.17 | 23.91 |
April | 503.83 | 23.97 | 669.17 | 23.93 | 497.67 | 23.95 |
May | 552.00 | 23.99 | 741.33 | 23.94 | 552.00 | 23.96 |
June | 568.67 | 23.99 | 720.00 | 23.97 | 568.67 | 23.97 |
July | 599.50 | 23.99 | 744.00 | 23.98 | 599.50 | 23.98 |
August | 591.00 | 23.99 | 744.00 | 23.97 | 591.00 | 23.98 |
September | 531.33 | 23.99 | 715.00 | 23.95 | 531.33 | 23.96 |
October | 508.17 | 23.99 | 702.83 | 23.93 | 508.17 | 23.95 |
November | 499.50 | 23.65 | 625.33 | 23.73 | 450.50 | 23.76 |
December | 496.00 | 23.58 | 581.50 | 23.79 | 388.33 | 23.84 |
Annual Sum or Average | 6347.50 | 23.64 | 8013.67 | 23.71 | 5943.00 | 23.73 |
Minimum of Months | 479.17 | 21.97 | 551.50 | 22.27 | 367.50 | 22.22 |
Maximum of Months | 599.50 | 23.99 | 744.00 | 23.98 | 599.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 623.50 | 20.65 | 623.50 | 20.64 |
February | 672.00 | 20.14 | 371.83 | 19.88 | 371.83 | 19.76 |
March | 744.00 | 21.10 | 232.83 | 21.07 | 232.83 | 21.06 |
April | 691.67 | 21.49 | 36.67 | 21.49 | 29.83 | 21.47 |
May | 703.83 | 22.23 | 22.67 | 22.28 | 0.00 | 22.28 |
June | 365.33 | 22.55 | 208.00 | 23.01 | 0.00 | 23.01 |
July | 220.67 | 22.88 | 329.00 | 23.44 | 0.00 | 23.44 |
August | 361.33 | 22.93 | 197.17 | 23.24 | 5.00 | 23.25 |
September | 549.17 | 22.20 | 84.17 | 22.42 | 0.00 | 22.42 |
October | 744.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
November | 720.00 | 21.05 | 246.83 | 21.01 | 246.83 | 20.99 |
December | 744.00 | 21.00 | 577.17 | 21.00 | 577.17 | 21.00 |
Annual Sum or Average | 7260.00 | 21.42 | 2929.83 | 21.45 | 2087.00 | 21.31 |
Minimum of Months | 220.67 | 20.14 | 0.00 | 19.88 | 0.00 | 19.76 |
Maximum of Months | 744.00 | 22.93 | 623.50 | 23.44 | 623.50 | 23.44 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59320 | 17.62359 | -0.1543 | 6.83757 |
February | 672.00000 | 21.40080 | 21.78830 | -0.4184 | 15.11683 |
March | 744.00000 | 22.34392 | 27.75902 | -0.1686 | 5.75603 |
April | 720.00000 | 21.95025 | 35.90416 | -0.2176 | 6.20622 |
May | 744.00000 | 22.20458 | 48.73097 | -1.1628 | 33.70131 |
June | 720.00000 | 22.73066 | 55.99596 | -0.9229 | 23.29165 |
July | 744.00000 | 23.22296 | 59.02171 | -0.7211 | 16.19371 |
August | 744.00000 | 23.67105 | 55.93065 | -0.5732 | 12.06998 |
September | 720.00000 | 23.84852 | 42.90097 | -0.5914 | 12.54697 |
October | 744.00000 | 23.90026 | 30.75198 | 0.26028 | 6.47735 |
November | 720.00000 | 23.77246 | 26.86967 | 0.20048 | 6.22320 |
December | 744.00000 | 23.73502 | 20.14979 | 0.13686 | 5.49100 |
Annual Sum or Average | 8760.00000 | 22.95912 | 37.03889 | -0.3604 | 12.47575 |
Minimum of Months | 672.00000 | 21.40080 | 17.62359 | -1.1628 | 5.49100 |
Maximum of Months | 744.00000 | 23.90026 | 59.02171 | 0.26028 | 33.70131 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.61558 | 17.14508 | -0.7504 | 19.19278 |
February | 672.00000 | 20.29567 | 21.19052 | -0.7379 | 20.45257 |
March | 744.00000 | 21.27376 | 27.43370 | -0.4300 | 10.24627 |
April | 720.00000 | 21.57115 | 34.63231 | -0.2579 | 8.95147 |
May | 744.00000 | 21.69671 | 48.57907 | -1.1736 | 36.06802 |
June | 720.00000 | 22.33839 | 55.85323 | -0.8680 | 24.21182 |
July | 744.00000 | 22.66864 | 59.82102 | -0.7029 | 17.64054 |
August | 744.00000 | 22.66524 | 58.08582 | -0.7134 | 18.21767 |
September | 720.00000 | 22.24913 | 45.03699 | -0.9713 | 29.89984 |
October | 744.00000 | 21.56678 | 33.33201 | -0.2418 | 8.12081 |
November | 720.00000 | 21.12788 | 29.10924 | -0.4770 | 11.49138 |
December | 744.00000 | 21.14738 | 20.82052 | -0.5996 | 13.69672 |
Annual Sum or Average | 8760.00000 | 21.60968 | 37.68225 | -0.6599 | 18.15883 |
Minimum of Months | 672.00000 | 20.29567 | 17.14508 | -1.1736 | 8.12081 |
Maximum of Months | 744.00000 | 22.66864 | 59.82102 | -0.2418 | 36.06802 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83686 | 19.50067 | -0.5774 | 13.44890 |
February | 672.00000 | 20.57349 | 23.23629 | -0.5996 | 17.48615 |
March | 744.00000 | 21.82680 | 29.04973 | -0.2582 | 7.12075 |
April | 720.00000 | 22.38652 | 35.66345 | -0.0683 | 6.31629 |
May | 744.00000 | 22.94796 | 47.78549 | -0.8429 | 20.83431 |
June | 720.00000 | 23.34391 | 55.13192 | -0.6391 | 14.61258 |
July | 744.00000 | 23.57473 | 58.97837 | -0.5236 | 11.14492 |
August | 744.00000 | 23.57681 | 57.35373 | -0.5353 | 11.34949 |
September | 720.00000 | 23.25387 | 45.11762 | -0.7400 | 18.05417 |
October | 744.00000 | 22.57424 | 34.07820 | -0.0308 | 5.42725 |
November | 720.00000 | 21.81155 | 30.35074 | -0.2562 | 7.64653 |
December | 744.00000 | 21.32685 | 23.13056 | -0.4346 | 9.25268 |
Annual Sum or Average | 8760.00000 | 22.34664 | 38.36906 | -0.4581 | 11.84775 |
Minimum of Months | 672.00000 | 20.57349 | 19.50067 | -0.8429 | 5.42725 |
Maximum of Months | 744.00000 | 23.57681 | 58.97837 | -0.0308 | 20.83431 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.72215 | 13.99588 | 0.19144 | 17.57182 |
February | 672.00000 | 21.25956 | 17.68434 | 0.13016 | 22.30738 |
March | 744.00000 | 22.98519 | 23.13693 | 0.58531 | 14.98458 |
April | 720.00000 | 23.04445 | 30.15571 | 0.67282 | 17.22404 |
May | 744.00000 | 23.11449 | 42.70734 | 0.09710 | 10.25038 |
June | 720.00000 | 23.11699 | 51.13297 | 0.18354 | 10.62232 |
July | 744.00000 | 23.14331 | 55.56272 | 0.23215 | 10.70138 |
August | 744.00000 | 23.14451 | 53.94658 | 0.21982 | 10.76152 |
September | 720.00000 | 23.12804 | 41.01046 | 0.09829 | 10.19314 |
October | 744.00000 | 23.10187 | 28.58521 | 0.68086 | 17.17109 |
November | 720.00000 | 22.84526 | 24.48894 | 0.55688 | 15.67736 |
December | 744.00000 | 22.87390 | 17.22352 | 0.47840 | 12.59422 |
Annual Sum or Average | 8760.00000 | 22.79988 | 33.39372 | 0.34528 | 14.11287 |
Minimum of Months | 672.00000 | 21.25956 | 13.99588 | 0.09710 | 10.19314 |
Maximum of Months | 744.00000 | 23.14451 | 55.56272 | 0.68086 | 22.30738 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84759 | 22.23091 | -0.5867 | 14.78909 |
February | 672.00000 | 20.76549 | 25.84490 | -0.5258 | 16.71065 |
March | 744.00000 | 21.91738 | 31.93374 | -0.1851 | 7.46958 |
April | 720.00000 | 22.38750 | 38.64841 | 0.01344 | 7.65632 |
May | 744.00000 | 22.84838 | 51.11792 | -0.7216 | 17.69536 |
June | 720.00000 | 23.21453 | 58.52256 | -0.5034 | 12.36774 |
July | 744.00000 | 23.44573 | 62.40936 | -0.3723 | 8.88847 |
August | 744.00000 | 23.49192 | 60.64858 | -0.3640 | 8.80805 |
September | 720.00000 | 23.16267 | 48.26659 | -0.5856 | 15.89298 |
October | 744.00000 | 22.57318 | 37.10080 | 0.07091 | 6.69776 |
November | 720.00000 | 21.71356 | 33.45231 | -0.2437 | 8.66297 |
December | 744.00000 | 21.42732 | 25.96259 | -0.4248 | 10.22324 |
Annual Sum or Average | 8760.00000 | 22.32569 | 41.43527 | -0.3682 | 11.27950 |
Minimum of Months | 672.00000 | 20.76549 | 22.23091 | -0.7216 | 6.69776 |
Maximum of Months | 744.00000 | 23.49192 | 62.40936 | 0.07091 | 17.69536 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14899 | 21.85668 | -0.4733 | 11.53510 |
February | 672.00000 | 20.99700 | 25.38017 | -0.4710 | 15.67021 |
March | 744.00000 | 22.29464 | 31.22684 | -0.1149 | 6.15096 |
April | 720.00000 | 22.73700 | 37.84920 | 0.05300 | 6.30848 |
May | 744.00000 | 23.23618 | 49.82925 | -0.6875 | 15.81564 |
June | 720.00000 | 23.47129 | 57.28061 | -0.5304 | 11.73759 |
July | 744.00000 | 23.61769 | 61.21393 | -0.4400 | 9.40180 |
August | 744.00000 | 23.65125 | 59.48822 | -0.4398 | 9.34644 |
September | 720.00000 | 23.47980 | 47.24598 | -0.5987 | 13.81078 |
October | 744.00000 | 23.00519 | 36.19322 | 0.11401 | 5.74055 |
November | 720.00000 | 22.23668 | 32.50045 | -0.1222 | 6.92234 |
December | 744.00000 | 21.75367 | 25.44156 | -0.3073 | 7.59658 |
Annual Sum or Average | 8760.00000 | 22.64547 | 40.54705 | -0.3341 | 9.95984 |
Minimum of Months | 672.00000 | 20.99700 | 21.85668 | -0.6875 | 5.74055 |
Maximum of Months | 744.00000 | 23.65125 | 61.21393 | 0.11401 | 15.81564 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55424 | 25.28087 | -0.8045 | 19.28574 |
February | 672.00000 | 20.65700 | 29.17751 | -0.7091 | 16.92855 |
March | 744.00000 | 21.02927 | 35.18503 | -0.5235 | 11.83791 |
April | 720.00000 | 21.29142 | 41.03988 | -0.3437 | 9.08173 |
May | 744.00000 | 21.63316 | 50.81543 | -1.2537 | 39.25956 |
June | 720.00000 | 21.67486 | 53.39127 | -1.1427 | 34.20111 |
July | 744.00000 | 21.72529 | 54.28686 | -1.0772 | 31.23228 |
August | 744.00000 | 21.71642 | 54.54373 | -1.1017 | 32.31897 |
September | 720.00000 | 21.59252 | 48.20921 | -1.2636 | 40.12295 |
October | 744.00000 | 21.35224 | 41.59649 | -0.3481 | 8.39241 |
November | 720.00000 | 20.88067 | 37.22685 | -0.5772 | 13.17079 |
December | 744.00000 | 20.66134 | 28.72382 | -0.7442 | 17.38415 |
Annual Sum or Average | 8760.00000 | 21.23400 | 41.68873 | -0.8250 | 22.80093 |
Minimum of Months | 672.00000 | 20.55424 | 25.28087 | -1.2636 | 8.39241 |
Maximum of Months | 744.00000 | 21.72529 | 54.54373 | -0.3437 | 40.12295 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.44592 | 25.47940 | -0.8612 | 21.31169 |
February | 672.00000 | 20.42405 | 29.53594 | -0.7959 | 19.64089 |
March | 744.00000 | 20.81914 | 35.61200 | -0.5958 | 13.35463 |
April | 720.00000 | 21.31104 | 41.31143 | -0.3620 | 9.73226 |
May | 744.00000 | 22.02933 | 50.69425 | -1.1546 | 36.32972 |
June | 720.00000 | 22.33544 | 53.12554 | -0.9560 | 29.39685 |
July | 744.00000 | 22.59030 | 54.46101 | -0.8308 | 24.40809 |
August | 744.00000 | 22.46909 | 54.93561 | -0.8970 | 25.99861 |
September | 720.00000 | 21.90525 | 48.47963 | -1.2089 | 38.58554 |
October | 744.00000 | 21.15974 | 42.15090 | -0.4248 | 9.47025 |
November | 720.00000 | 20.71749 | 37.60771 | -0.6385 | 14.59629 |
December | 744.00000 | 20.50059 | 29.01545 | -0.8071 | 19.29750 |
Annual Sum or Average | 8760.00000 | 21.39832 | 41.93299 | -0.7944 | 21.84811 |
Minimum of Months | 672.00000 | 20.42405 | 25.47940 | -1.2089 | 9.47025 |
Maximum of Months | 744.00000 | 22.59030 | 54.93561 | -0.3620 | 38.58554 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53546 | 24.47157 | -0.7408 | 17.27381 |
February | 672.00000 | 20.53272 | 28.27602 | -0.7022 | 16.73027 |
March | 744.00000 | 21.00975 | 34.44659 | -0.5154 | 10.92382 |
April | 720.00000 | 21.30720 | 40.38107 | -0.3734 | 8.57532 |
May | 744.00000 | 21.75803 | 49.37190 | -1.2983 | 41.08324 |
June | 720.00000 | 22.03558 | 53.75666 | -1.1406 | 33.98264 |
July | 744.00000 | 22.21717 | 56.53077 | -1.0555 | 30.15022 |
August | 744.00000 | 22.12907 | 56.15632 | -1.1004 | 31.93351 |
September | 720.00000 | 21.73146 | 47.99377 | -1.3223 | 42.24714 |
October | 744.00000 | 21.23787 | 40.63164 | -0.3941 | 8.41162 |
November | 720.00000 | 20.94014 | 36.01607 | -0.5312 | 11.56426 |
December | 744.00000 | 20.67491 | 28.15468 | -0.6774 | 15.10083 |
Annual Sum or Average | 8760.00000 | 21.34734 | 41.42143 | -0.8217 | 22.35813 |
Minimum of Months | 672.00000 | 20.53272 | 24.47157 | -1.3223 | 8.41162 |
Maximum of Months | 744.00000 | 22.21717 | 56.53077 | -0.3734 | 42.24714 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53518 | 25.26117 | -0.8061 | 19.35799 |
February | 672.00000 | 20.63477 | 29.14143 | -0.7162 | 17.22357 |
March | 744.00000 | 21.09853 | 35.04616 | -0.5055 | 11.45967 |
April | 720.00000 | 21.32744 | 40.92087 | -0.3463 | 9.17267 |
May | 744.00000 | 21.69025 | 50.04649 | -1.2275 | 38.05006 |
June | 720.00000 | 21.69912 | 52.80482 | -1.1324 | 33.78693 |
July | 744.00000 | 21.74034 | 53.83676 | -1.0787 | 31.34551 |
August | 744.00000 | 21.73774 | 54.10716 | -1.1032 | 32.41019 |
September | 720.00000 | 21.63864 | 47.82975 | -1.2463 | 39.29741 |
October | 744.00000 | 21.40999 | 41.51430 | -0.3377 | 8.25363 |
November | 720.00000 | 20.86728 | 37.25455 | -0.5809 | 13.26414 |
December | 744.00000 | 20.62950 | 28.74723 | -0.7508 | 17.54105 |
Annual Sum or Average | 8760.00000 | 21.25434 | 41.43999 | -0.8201 | 22.62700 |
Minimum of Months | 672.00000 | 20.53518 | 25.26117 | -1.2463 | 8.25363 |
Maximum of Months | 744.00000 | 21.74034 | 54.10716 | -0.3377 | 39.29741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43322 | 25.44292 | -0.8627 | 21.41750 |
February | 672.00000 | 20.38345 | 29.51166 | -0.8073 | 20.12499 |
March | 744.00000 | 20.87842 | 35.45312 | -0.5801 | 12.87159 |
April | 720.00000 | 21.31267 | 41.25226 | -0.3725 | 9.66423 |
May | 744.00000 | 21.99160 | 50.08883 | -1.1564 | 35.39739 |
June | 720.00000 | 22.31188 | 52.83466 | -0.9582 | 28.90199 |
July | 744.00000 | 22.58834 | 54.28109 | -0.8354 | 24.49453 |
August | 744.00000 | 22.41439 | 54.81271 | -0.9199 | 26.10504 |
September | 720.00000 | 21.92311 | 48.02181 | -1.2006 | 37.78195 |
October | 744.00000 | 21.17452 | 42.10266 | -0.4243 | 9.16345 |
November | 720.00000 | 20.70301 | 37.62282 | -0.6435 | 14.72479 |
December | 744.00000 | 20.49359 | 29.01545 | -0.8099 | 19.43688 |
Annual Sum or Average | 8760.00000 | 21.39028 | 41.76815 | -0.7975 | 21.67443 |
Minimum of Months | 672.00000 | 20.38345 | 25.44292 | -1.2006 | 9.16345 |
Maximum of Months | 744.00000 | 22.58834 | 54.81271 | -0.3725 | 37.78195 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49271 | 25.62526 | -0.8739 | 21.78008 |
February | 672.00000 | 20.57704 | 29.66392 | -0.7710 | 18.93679 |
March | 744.00000 | 20.92898 | 35.87092 | -0.5798 | 13.32351 |
April | 720.00000 | 21.23185 | 41.76356 | -0.3749 | 9.90858 |
May | 744.00000 | 21.61580 | 51.77295 | -1.2651 | 40.03106 |
June | 720.00000 | 21.66069 | 54.31358 | -1.1440 | 34.54120 |
July | 744.00000 | 21.71785 | 55.34201 | -1.0721 | 31.24739 |
August | 744.00000 | 21.70537 | 55.90825 | -1.1018 | 32.53833 |
September | 720.00000 | 21.55410 | 49.23368 | -1.2917 | 41.74447 |
October | 744.00000 | 21.27556 | 42.42405 | -0.3882 | 9.17318 |
November | 720.00000 | 20.79223 | 38.00592 | -0.6353 | 14.80437 |
December | 744.00000 | 20.58874 | 29.16953 | -0.8115 | 19.58818 |
Annual Sum or Average | 8760.00000 | 21.18191 | 42.49204 | -0.8598 | 23.99540 |
Minimum of Months | 672.00000 | 20.49271 | 25.62526 | -1.2917 | 9.17318 |
Maximum of Months | 744.00000 | 21.71785 | 55.90825 | -0.3749 | 41.74447 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.40480 | 25.80289 | -0.9274 | 23.86970 |
February | 672.00000 | 20.36142 | 30.00433 | -0.8566 | 21.81606 |
March | 744.00000 | 20.73774 | 36.30135 | -0.6507 | 14.89703 |
April | 720.00000 | 21.26080 | 41.98059 | -0.3923 | 10.70458 |
May | 744.00000 | 22.06374 | 51.30130 | -1.1478 | 36.97637 |
June | 720.00000 | 22.37874 | 53.56272 | -0.9353 | 30.04726 |
July | 744.00000 | 22.62649 | 54.85576 | -0.8071 | 24.77500 |
August | 744.00000 | 22.50382 | 55.62165 | -0.8792 | 26.32321 |
September | 720.00000 | 21.87646 | 49.33942 | -1.2330 | 40.33943 |
October | 744.00000 | 21.06213 | 43.05369 | -0.4719 | 10.53282 |
November | 720.00000 | 20.64429 | 38.38600 | -0.6953 | 16.30857 |
December | 744.00000 | 20.47303 | 29.42511 | -0.8666 | 21.43136 |
Annual Sum or Average | 8760.00000 | 21.37247 | 42.53534 | -0.8217 | 23.16662 |
Minimum of Months | 672.00000 | 20.36142 | 25.80289 | -1.2330 | 10.53282 |
Maximum of Months | 744.00000 | 22.62649 | 55.62165 | -0.3923 | 40.33943 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92161 | 27.28620 | -0.6676 | 15.77365 |
February | 672.00000 | 21.05979 | 30.86227 | -0.5636 | 13.28212 |
March | 744.00000 | 21.26232 | 36.38921 | -0.4417 | 10.62606 |
April | 720.00000 | 21.34624 | 41.93074 | -0.3363 | 9.07905 |
May | 744.00000 | 21.64130 | 51.20090 | -1.2810 | 40.68142 |
June | 720.00000 | 21.67120 | 54.45224 | -1.1973 | 36.70529 |
July | 744.00000 | 21.70754 | 56.01588 | -1.1426 | 34.16973 |
August | 744.00000 | 21.70288 | 55.64544 | -1.1476 | 34.48492 |
September | 720.00000 | 21.62818 | 48.67202 | -1.2580 | 40.10700 |
October | 744.00000 | 21.51297 | 42.17913 | -0.2752 | 7.86828 |
November | 720.00000 | 21.14268 | 38.23599 | -0.4802 | 11.46454 |
December | 744.00000 | 20.95923 | 30.50298 | -0.6271 | 15.01208 |
Annual Sum or Average | 8760.00000 | 21.38155 | 42.84571 | -0.7863 | 22.49226 |
Minimum of Months | 672.00000 | 20.92161 | 27.28620 | -1.2810 | 7.86828 |
Maximum of Months | 744.00000 | 21.70754 | 56.01588 | -0.2752 | 40.68142 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.33670 | 23.80845 | -0.2002 | 9.20141 |
February | 672.00000 | 22.17718 | 26.78806 | -0.1929 | 14.12111 |
March | 744.00000 | 23.48646 | 31.97010 | 0.18494 | 6.42595 |
April | 720.00000 | 23.71038 | 37.88537 | 0.32296 | 7.80685 |
May | 744.00000 | 23.90948 | 48.89122 | -0.3718 | 8.25084 |
June | 720.00000 | 23.95432 | 56.27297 | -0.2526 | 6.58263 |
July | 744.00000 | 23.97662 | 60.36115 | -0.2008 | 5.90630 |
August | 744.00000 | 23.96682 | 58.96775 | -0.2299 | 6.19931 |
September | 720.00000 | 23.88814 | 47.34509 | -0.3907 | 8.79548 |
October | 744.00000 | 23.70803 | 36.60812 | 0.30528 | 7.25709 |
November | 720.00000 | 23.30692 | 33.29844 | 0.14421 | 6.95153 |
December | 744.00000 | 23.02815 | 27.13418 | -0.0091 | 6.12523 |
Annual Sum or Average | 8760.00000 | 23.46174 | 40.86053 | -0.0736 | 7.75298 |
Minimum of Months | 672.00000 | 22.17718 | 23.80845 | -0.3907 | 5.90630 |
Maximum of Months | 744.00000 | 23.97662 | 60.36115 | 0.32296 | 14.12111 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59419 | 23.00911 | -0.0996 | 8.68724 |
February | 672.00000 | 22.38710 | 25.85895 | -0.1031 | 14.09047 |
March | 744.00000 | 23.68245 | 30.88248 | 0.27263 | 7.04353 |
April | 720.00000 | 23.84246 | 36.89544 | 0.39284 | 8.67100 |
May | 744.00000 | 23.96453 | 48.08213 | -0.3020 | 7.17681 |
June | 720.00000 | 23.98123 | 55.66013 | -0.1997 | 6.02008 |
July | 744.00000 | 23.99081 | 59.82526 | -0.1556 | 5.55795 |
August | 744.00000 | 23.98736 | 58.39531 | -0.1814 | 5.76738 |
September | 720.00000 | 23.94753 | 46.59604 | -0.3231 | 7.59022 |
October | 744.00000 | 23.84788 | 35.55482 | 0.37800 | 8.17351 |
November | 720.00000 | 23.51322 | 32.27660 | 0.23374 | 7.43234 |
December | 744.00000 | 23.29557 | 26.15977 | 0.09599 | 6.09406 |
Annual Sum or Average | 8760.00000 | 23.59347 | 40.01664 | 0.00131 | 7.64235 |
Minimum of Months | 672.00000 | 22.38710 | 23.00911 | -0.3231 | 5.55795 |
Maximum of Months | 744.00000 | 23.99081 | 59.82526 | 0.39284 | 14.09047 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.83008 | 22.40805 | 0.56959 | 21.71167 |
February | 672.00000 | 22.41891 | 26.02559 | 0.53732 | 26.61786 |
March | 744.00000 | 23.73630 | 29.35607 | 0.92455 | 25.76307 |
April | 720.00000 | 23.81982 | 35.65385 | 1.04192 | 30.31502 |
May | 744.00000 | 23.90605 | 47.10310 | 0.64154 | 18.39138 |
June | 720.00000 | 23.94806 | 54.77012 | 0.76511 | 21.53756 |
July | 744.00000 | 23.96549 | 58.90596 | 0.81920 | 22.93775 |
August | 744.00000 | 23.95716 | 57.44450 | 0.78348 | 21.85300 |
September | 720.00000 | 23.91052 | 45.56573 | 0.62904 | 17.96329 |
October | 744.00000 | 23.82374 | 34.23550 | 1.02214 | 29.18966 |
November | 720.00000 | 23.61517 | 30.87248 | 0.88338 | 25.54348 |
December | 744.00000 | 23.62035 | 24.45299 | 0.78227 | 20.96808 |
Annual Sum or Average | 8760.00000 | 23.63713 | 38.97445 | 0.78481 | 23.53790 |
Minimum of Months | 672.00000 | 22.41891 | 22.40805 | 0.53732 | 17.96329 |
Maximum of Months | 744.00000 | 23.96549 | 58.90596 | 1.04192 | 30.31502 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64469 | 16.29509 | -0.7053 | 16.45993 |
February | 672.00000 | 19.95834 | 20.55372 | -0.8157 | 22.72775 |
March | 744.00000 | 21.04776 | 26.68988 | -0.5040 | 10.47309 |
April | 720.00000 | 21.38369 | 34.03840 | -0.3573 | 8.59813 |
May | 744.00000 | 22.10336 | 46.45015 | -1.1837 | 35.06442 |
June | 720.00000 | 22.88242 | 53.59041 | -0.8644 | 21.86029 |
July | 744.00000 | 23.23188 | 57.49512 | -0.7152 | 16.04393 |
August | 744.00000 | 23.17053 | 55.90557 | -0.7479 | 17.01663 |
September | 720.00000 | 22.55660 | 43.44092 | -1.0409 | 29.38541 |
October | 744.00000 | 21.33432 | 32.71588 | -0.3656 | 8.01117 |
November | 720.00000 | 21.12090 | 28.03737 | -0.4786 | 10.35187 |
December | 744.00000 | 20.99879 | 19.89525 | -0.5910 | 12.38424 |
Annual Sum or Average | 8760.00000 | 21.71401 | 36.34951 | -0.6966 | 17.31864 |
Minimum of Months | 672.00000 | 19.95834 | 16.29509 | -1.1837 | 8.01117 |
Maximum of Months | 744.00000 | 23.23188 | 57.49512 | -0.3573 | 35.06442 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80364 | 19.57645 | -0.6326 | 13.85353 |
February | 672.00000 | 20.42979 | 23.68610 | -0.6778 | 16.86871 |
March | 744.00000 | 21.08518 | 29.93985 | -0.4758 | 9.87788 |
April | 720.00000 | 21.49263 | 37.09401 | -0.3211 | 8.00840 |
May | 744.00000 | 22.19807 | 49.36584 | -1.1546 | 33.50189 |
June | 720.00000 | 22.93050 | 56.32998 | -0.8493 | 21.18265 |
July | 744.00000 | 23.30663 | 59.90429 | -0.6911 | 15.25884 |
August | 744.00000 | 23.19226 | 58.58984 | -0.7417 | 16.75460 |
September | 720.00000 | 22.62250 | 46.44713 | -1.0196 | 28.56310 |
October | 744.00000 | 21.29021 | 36.01527 | -0.3743 | 8.06984 |
November | 720.00000 | 21.06437 | 31.48077 | -0.4790 | 10.11074 |
December | 744.00000 | 21.00112 | 23.30142 | -0.5641 | 11.71292 |
Annual Sum or Average | 8760.00000 | 21.79322 | 39.40068 | -0.6650 | 16.13201 |
Minimum of Months | 672.00000 | 20.42979 | 19.57645 | -1.1546 | 8.00840 |
Maximum of Months | 744.00000 | 23.30663 | 59.90429 | -0.3211 | 33.50189 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68054 | 17.49828 | -0.6979 | 16.30355 |
February | 672.00000 | 20.13594 | 21.66997 | -0.7674 | 20.91734 |
March | 744.00000 | 21.09609 | 27.86628 | -0.4744 | 9.95014 |
April | 720.00000 | 21.56454 | 34.78617 | -0.2894 | 8.04355 |
May | 744.00000 | 22.30476 | 46.89968 | -1.0717 | 30.26300 |
June | 720.00000 | 23.09759 | 53.51258 | -0.7371 | 18.08681 |
July | 744.00000 | 23.42736 | 57.20965 | -0.5919 | 12.92872 |
August | 744.00000 | 23.28280 | 56.02721 | -0.6560 | 14.61704 |
September | 720.00000 | 22.54680 | 44.33817 | -0.9989 | 28.59046 |
October | 744.00000 | 21.31562 | 33.86777 | -0.3528 | 7.88453 |
November | 720.00000 | 21.05285 | 29.41769 | -0.4867 | 10.48973 |
December | 744.00000 | 21.00257 | 21.22717 | -0.5901 | 12.38357 |
Annual Sum or Average | 8760.00000 | 21.80291 | 37.11472 | -0.6420 | 15.82534 |
Minimum of Months | 672.00000 | 20.13594 | 17.49828 | -1.0717 | 7.88453 |
Maximum of Months | 744.00000 | 23.42736 | 57.20965 | -0.2894 | 30.26300 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.71862 | 15.91723 | -0.6759 | 15.41245 |
February | 672.00000 | 20.04528 | 20.18113 | -0.7865 | 21.71601 |
March | 744.00000 | 21.11847 | 26.19229 | -0.4805 | 10.04267 |
April | 720.00000 | 21.52749 | 33.37862 | -0.3224 | 8.20217 |
May | 744.00000 | 22.35558 | 45.42379 | -1.1062 | 31.51964 |
June | 720.00000 | 23.10748 | 52.53696 | -0.7944 | 19.35549 |
July | 744.00000 | 23.45799 | 56.37481 | -0.6444 | 14.00649 |
August | 744.00000 | 23.41506 | 54.75175 | -0.6713 | 14.72634 |
September | 720.00000 | 22.83301 | 42.40838 | -0.9547 | 25.83039 |
October | 744.00000 | 21.59185 | 31.88416 | -0.3087 | 7.24143 |
November | 720.00000 | 21.23525 | 27.44874 | -0.4455 | 9.81103 |
December | 744.00000 | 21.00181 | 19.52321 | -0.5759 | 12.00684 |
Annual Sum or Average | 8760.00000 | 21.87892 | 35.58996 | -0.6462 | 15.77439 |
Minimum of Months | 672.00000 | 20.04528 | 15.91723 | -1.1062 | 7.24143 |
Maximum of Months | 744.00000 | 23.45799 | 56.37481 | -0.3087 | 31.51964 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.320156E+09 | 6962.84 | 12-JAN-16:01 | 50.56 | 0.997583E+09 | 0.00 | 0.131774E+10 | 0.21 | 3.12 | 02-JAN-10:15 | 0.00 | 0.00 |
February | 0.716975E+09 | 13099.72 | 25-FEB-16:03 | 90.83 | 0.223405E+10 | 0.00 | 0.295102E+10 | 0.42 | 3.12 | 07-FEB-19:10 | 0.00 | 0.00 |
March | 0.454828E+10 | 74130.81 | 25-MAR-15:01 | 252.82 | 0.138144E+11 | 0.00 | 0.183627E+11 | 1.05 | 3.19 | 25-MAR-15:01 | 0.00 | 0.00 |
April | 0.296860E+11 | 142951.41 | 18-APR-15:03 | 418.01 | 0.895464E+11 | 0.00 | 0.119232E+12 | 1.78 | 3.67 | 16-APR-21:52 | 0.00 | 0.00 |
May | 0.677902E+11 | 140272.10 | 31-MAY-18:03 | 728.00 | 0.201768E+12 | 0.00 | 0.269558E+12 | 2.96 | 3.80 | 29-MAY-15:03 | 0.00 | 0.00 |
June | 0.156625E+12 | 194654.27 | 11-JUN-15:03 | 708.35 | 0.489014E+12 | 0.00 | 0.645639E+12 | 3.02 | 4.04 | 11-JUN-21:52 | 0.00 | 0.00 |
July | 0.207589E+12 | 212664.97 | 26-JUL-18:02 | 744.00 | 0.674982E+12 | 0.00 | 0.882571E+12 | 3.16 | 4.15 | 05-JUL-21:52 | 0.00 | 0.00 |
August | 0.184967E+12 | 222130.62 | 04-AUG-15:03 | 744.00 | 0.592468E+12 | 0.00 | 0.777435E+12 | 3.11 | 4.17 | 28-AUG-21:52 | 0.00 | 0.00 |
September | 0.902592E+11 | 167492.69 | 06-SEP-15:03 | 663.89 | 0.264658E+12 | 0.00 | 0.354917E+12 | 2.76 | 3.94 | 11-SEP-21:52 | 0.00 | 0.00 |
October | 0.159619E+11 | 104702.35 | 20-OCT-15:01 | 498.35 | 0.479566E+11 | 0.00 | 0.639186E+11 | 2.07 | 3.53 | 20-OCT-15:01 | 0.00 | 0.00 |
November | 0.398748E+10 | 58351.59 | 03-NOV-15:01 | 214.96 | 0.122952E+11 | 0.00 | 0.162827E+11 | 0.93 | 3.12 | 01-NOV-15:07 | 0.00 | 0.00 |
December | 0.577828E+09 | 7965.87 | 03-DEC-09:02 | 80.59 | 0.180047E+10 | 0.00 | 0.237830E+10 | 0.34 | 3.12 | 01-DEC-11:45 | 0.00 | 0.00 |
Annual Sum or Average | 0.763029E+12 | 5194.35 | 0.239153E+13 | 0.00 | 0.315456E+13 | 1.82 | 0.00 | 0.00 | ||||
Minimum of Months | 0.320156E+09 | 6962.84 | 50.56 | 0.997583E+09 | 0.00 | 0.131774E+10 | 0.21 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.207589E+12 | 222130.62 | 744.00 | 0.674982E+12 | 0.00 | 0.882571E+12 | 3.16 | 4.17 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.497307E+12 | 0.00 | 744.00 | 611675.43 | 31-JAN-04:03 | 0.00 | 37.35 | 60.00 | 1.90 | 0.00 | 0.27 | 0.91 | 31-JAN-04:03 |
February | 0.343228E+12 | 0.00 | 672.00 | 645301.33 | 02-FEB-06:00 | 0.00 | 39.03 | 60.00 | 1.45 | 0.00 | 0.21 | 0.96 | 02-FEB-06:00 |
March | 0.140845E+12 | 0.00 | 722.41 | 222647.56 | 05-MAR-19:02 | 0.00 | 38.02 | 59.13 | 0.57 | 0.00 | 0.08 | 0.33 | 05-MAR-19:02 |
April | 0.742567E+11 | 0.00 | 605.36 | 177425.35 | 03-APR-08:62 | 0.00 | 36.79 | 54.93 | 0.30 | 0.00 | 0.04 | 0.26 | 03-APR-08:62 |
May | 0.473525E+11 | 0.00 | 392.92 | 150108.75 | 01-MAY-08:04 | 0.00 | 29.40 | 44.69 | 0.14 | 0.00 | 0.03 | 0.22 | 01-MAY-08:04 |
June | 0.282177E+11 | 0.00 | 189.02 | 135613.32 | 03-JUN-08:03 | 0.00 | 30.25 | 38.44 | 0.09 | 0.00 | 0.02 | 0.20 | 03-JUN-08:03 |
July | 0.508364E+10 | 0.00 | 57.85 | 71332.15 | 24-JUL-05:00 | 0.00 | 32.19 | 34.75 | 0.01 | 0.00 | 0.00 | 0.11 | 24-JUL-05:00 |
August | 0.117478E+11 | 0.00 | 104.80 | 101395.95 | 07-AUG-06:00 | 0.00 | 30.99 | 35.61 | 0.03 | 0.00 | 0.01 | 0.15 | 07-AUG-06:00 |
September | 0.453678E+11 | 0.00 | 340.11 | 138257.37 | 27-SEP-08:05 | 0.00 | 31.94 | 44.30 | 0.15 | 0.00 | 0.03 | 0.20 | 27-SEP-08:05 |
October | 0.907363E+11 | 0.00 | 670.93 | 171556.54 | 17-OCT-18:03 | 0.00 | 38.16 | 57.27 | 0.35 | 0.00 | 0.05 | 0.25 | 17-OCT-18:03 |
November | 0.181806E+12 | 0.00 | 712.58 | 581464.02 | 26-NOV-07:00 | 0.00 | 37.59 | 59.67 | 0.74 | 0.00 | 0.10 | 0.86 | 26-NOV-07:00 |
December | 0.289470E+12 | 0.00 | 744.00 | 302935.94 | 09-DEC-09:08 | 0.00 | 37.78 | 60.00 | 1.15 | 0.00 | 0.16 | 0.45 | 09-DEC-09:08 |
Annual Sum or Average | 0.175542E+13 | 0.00 | 5955.98 | 0.00 | 34.93 | 50.67 | 0.57 | 0.00 | 0.08 | ||||
Minimum of Months | 0.508364E+10 | 0.00 | 57.85 | 71332.15 | 0.00 | 29.40 | 34.75 | 0.01 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.497307E+12 | 0.00 | 744.00 | 645301.33 | 0.00 | 39.03 | 60.00 | 1.90 | 0.00 | 0.27 | 0.96 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1491782.44 | 0.00 | 4.44 | 1491782.44 | 0.00 | 0.00 | 0.00 | 0.00 | 796.74 | 17-JAN-23:10 | 796.74 | 17-JAN-23:10 | 0.00 | 0.00 | 0.00 |
February | 569732.18 | 0.00 | 4.53 | 569732.18 | 0.00 | 0.00 | 0.00 | 0.00 | 509.45 | 07-FEB-19:40 | 509.45 | 07-FEB-19:40 | 0.00 | 0.00 | 0.00 |
March | 0.290482E+10 | 0.00 | 26.50 | 0.290482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72493.38 | 19-MAR-16:20 | 72493.38 | 19-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.458794E+11 | 0.00 | 120.50 | 0.384366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 302332.89 | 18-APR-10:33 | 211272.41 | 15-APR-17:15 | 0.00 | 0.00 | 0.00 |
May | 0.106678E+12 | 0.00 | 358.28 | 0.868902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 305551.10 | 30-MAY-19:20 | 218182.26 | 31-MAY-18:40 | 0.00 | 0.00 | 0.00 |
June | 0.328153E+12 | 0.00 | 539.56 | 0.224361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 394026.76 | 26-JUN-18:20 | 250001.98 | 26-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.476320E+12 | 0.00 | 691.33 | 0.285209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 576578.70 | 03-JUL-21:30 | 243222.30 | 03-JUL-18:40 | 0.00 | 0.00 | 0.00 |
August | 0.412070E+12 | 0.00 | 644.83 | 0.250589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 582238.39 | 03-AUG-22:00 | 241297.04 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.151035E+12 | 0.00 | 380.33 | 0.138570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 313632.28 | 11-SEP-19:20 | 241102.03 | 07-SEP-18:05 | 0.00 | 0.00 | 0.00 |
October | 0.103039E+11 | 0.00 | 69.00 | 0.103039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141733.73 | 20-OCT-15:04 | 141733.73 | 20-OCT-15:04 | 0.00 | 0.00 | 0.00 |
November | 0.452982E+09 | 0.00 | 13.50 | 0.452982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22164.34 | 03-NOV-15:20 | 22164.34 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153380E+13 | 0.00 | 2852.81 | 0.103772E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.476320E+12 | 0.00 | 691.33 | 0.285209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 582238.39 | 250001.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.213301E+09 | 0.00 | 17.33 | 0.213301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8515.76 | 19-MAR-16:00 | 8515.76 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.323797E+10 | 0.00 | 81.50 | 0.259061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26462.51 | 18-APR-08:50 | 18720.93 | 15-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.744936E+10 | 0.00 | 247.83 | 0.563759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29501.61 | 29-MAY-15:02 | 18680.58 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.240232E+11 | 0.00 | 410.83 | 0.157030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40758.49 | 26-JUN-06:55 | 20103.84 | 11-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.362691E+11 | 0.00 | 538.67 | 0.207034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40259.71 | 17-JUL-18:50 | 18985.68 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.297117E+11 | 0.00 | 494.67 | 0.173764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 31-AUG-18:03 | 20399.90 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.108269E+11 | 0.00 | 280.33 | 0.934616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29549.17 | 11-SEP-08:15 | 19479.77 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.651762E+09 | 0.00 | 41.00 | 0.651762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.74 | 20-OCT-15:01 | 15286.74 | 20-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 24319556.63 | 0.00 | 7.00 | 24319556.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.01 | 03-NOV-15:01 | 2178.01 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112408E+12 | 0.00 | 2119.17 | 0.722466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.362691E+11 | 0.00 | 538.67 | 0.207034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 20399.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5974004.25 | 0.00 | 1.38 | 5974004.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18004.48 | 12-JAN-16:01 | 18004.48 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.132881E+09 | 0.00 | 19.72 | 0.132385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18458.23 | 25-FEB-16:01 | 18458.23 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.444526E+09 | 0.00 | 78.38 | 0.347835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18460.39 | 25-MAR-15:01 | 18460.39 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.261192E+10 | 0.00 | 269.41 | 0.172110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18674.66 | 16-APR-08:61 | 18457.12 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.469854E+10 | 0.00 | 546.01 | 0.240727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18836.21 | 11-MAY-15:01 | 18456.62 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.840382E+10 | 0.00 | 608.83 | 0.446994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20062.46 | 25-JUN-08:61 | 16399.50 | 20-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.107376E+11 | 0.00 | 700.90 | 0.567848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20583.59 | 20-JUL-08:61 | 16311.68 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.955593E+10 | 0.00 | 696.78 | 0.477171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21652.11 | 31-AUG-08:61 | 16226.30 | 12-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.572202E+10 | 0.00 | 504.80 | 0.322858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18691.25 | 11-SEP-08:61 | 18458.18 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.119508E+10 | 0.00 | 191.07 | 0.808049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18458.86 | 19-OCT-15:01 | 18458.86 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.218244E+09 | 0.00 | 35.64 | 0.155096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18451.98 | 04-NOV-15:01 | 18451.98 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 9097600.28 | 0.00 | 1.77 | 9097600.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17668.58 | 01-DEC-16:01 | 17668.58 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437357E+11 | 0.00 | 3654.70 | 0.237355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5974004.25 | 0.00 | 1.38 | 5974004.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17668.58 | 16226.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107376E+11 | 0.00 | 700.90 | 0.567848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21652.11 | 18460.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 249788.37 | 0.00 | 0.05 | 249788.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.32 | 12-JAN-16:03 | 1932.32 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 31211676.38 | 0.00 | 6.99 | 30980846.34 | 0.00 | 0.00 | 0.00 | 0.00 | 17727.89 | 24-FEB-16:02 | 17727.89 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.143539E+09 | 0.00 | 35.51 | 0.109981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17915.43 | 25-MAR-15:01 | 17915.43 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.158213E+10 | 0.00 | 186.40 | 0.988317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18703.51 | 16-APR-21:51 | 18179.40 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.308901E+10 | 0.00 | 422.57 | 0.140796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20135.13 | 20-MAY-18:41 | 20135.13 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.660616E+10 | 0.00 | 467.38 | 0.357283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23064.97 | 26-JUN-08:11 | 18598.75 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.811467E+10 | 0.00 | 505.26 | 0.438912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21336.87 | 02-JUL-08:51 | 17638.51 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.671152E+10 | 0.00 | 505.13 | 0.323507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23364.35 | 03-AUG-07:51 | 17866.46 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.361296E+10 | 0.00 | 370.16 | 0.181300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20462.88 | 19-SEP-17:41 | 20462.88 | 19-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 0.363186E+09 | 0.00 | 84.25 | 0.230873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17913.22 | 24-OCT-15:01 | 17913.22 | 24-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 62534319.70 | 0.00 | 12.00 | 44070853.85 | 0.00 | 0.00 | 0.00 | 0.00 | 17906.45 | 04-NOV-15:01 | 17906.45 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 487922.92 | 0.00 | 0.10 | 487922.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.91 | 01-DEC-16:03 | 2378.91 | 01-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303177E+11 | 0.00 | 2595.80 | 0.158229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 249788.37 | 0.00 | 0.05 | 249788.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.32 | 1932.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.811467E+10 | 0.00 | 505.26 | 0.438912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23364.35 | 20462.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.268919E+10 | 0.00 | 78.73 | 0.260121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33092.46 | 24-MAR-13:10 | 33092.46 | 24-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.122195E+11 | 0.00 | 235.72 | 0.689671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51511.54 | 15-APR-13:30 | 44126.88 | 15-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.246030E+11 | 0.00 | 562.38 | 0.109301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37477.78 | 05-MAY-13:30 | 29481.57 | 06-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.371158E+11 | 0.00 | 629.19 | 0.140709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41019.66 | 26-JUN-12:30 | 26490.84 | 26-JUN-12:50 | 0.00 | 0.00 | 0.00 |
July | 0.471639E+11 | 0.00 | 726.47 | 0.181141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43538.91 | 30-JUL-13:20 | 30745.50 | 30-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.479440E+11 | 0.00 | 730.94 | 0.198686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47641.05 | 22-AUG-13:30 | 38676.61 | 29-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.378297E+11 | 0.00 | 552.33 | 0.218998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58517.50 | 08-SEP-14:00 | 54743.20 | 06-SEP-13:05 | 0.00 | 0.00 | 0.00 |
October | 0.175188E+11 | 0.00 | 345.77 | 0.150093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55179.66 | 20-OCT-12:40 | 55179.66 | 20-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.475371E+10 | 0.00 | 111.33 | 0.398955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52426.28 | 04-NOV-12:30 | 52426.28 | 04-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231838E+12 | 0.00 | 3972.87 | 0.113380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.479440E+11 | 0.00 | 730.94 | 0.218998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58517.50 | 55179.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12292091.80 | 0.00 | 0.43 | 12292091.80 | 0.00 | 0.00 | 0.00 | 0.00 | 16549.05 | 13-JAN-19:03 | 16549.05 | 13-JAN-19:03 | 0.00 | 0.00 | 0.00 |
February | 56278230.21 | 0.00 | 3.59 | 47736190.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58610.21 | 25-FEB-09:02 | 58610.21 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.237177E+10 | 0.00 | 105.16 | 0.129893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88589.78 | 24-MAR-18:01 | 88589.78 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.108946E+11 | 0.00 | 247.04 | 0.653081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97083.12 | 16-APR-21:51 | 93053.19 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.304110E+11 | 0.00 | 443.92 | 0.167390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102389.44 | 29-MAY-21:51 | 94452.32 | 06-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.477871E+11 | 0.00 | 469.94 | 0.284369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118637.16 | 26-JUN-08:11 | 87265.49 | 21-JUN-21:01 | 0.00 | 0.00 | 0.00 |
July | 0.525021E+11 | 0.00 | 453.21 | 0.304653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108831.85 | 02-JUL-08:51 | 85527.24 | 22-JUL-21:31 | 0.00 | 0.00 | 0.00 |
August | 0.461590E+11 | 0.00 | 442.94 | 0.254968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124100.33 | 03-AUG-07:51 | 86622.38 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.275624E+11 | 0.00 | 418.90 | 0.153094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100418.52 | 11-SEP-21:51 | 92612.49 | 19-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.667103E+10 | 0.00 | 269.89 | 0.379448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88473.53 | 12-OCT-18:03 | 88473.53 | 12-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.283382E+10 | 0.00 | 114.41 | 0.104937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86579.69 | 04-NOV-18:02 | 86579.69 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 23607981.93 | 0.00 | 0.80 | 23607981.93 | 0.00 | 0.00 | 0.00 | 0.00 | 14987.58 | 18-DEC-19:05 | 14987.58 | 18-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227285E+12 | 0.00 | 2970.22 | 0.129205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12292091.80 | 0.00 | 0.43 | 12292091.80 | 0.00 | 0.00 | 0.00 | 0.00 | 14987.58 | 14987.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.525021E+11 | 0.00 | 469.94 | 0.304653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124100.33 | 94452.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4078868.28 | 0.00 | 2.20 | 4078868.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2188.06 | 13-JAN-16:03 | 2188.06 | 13-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 82383749.79 | 0.00 | 13.76 | 66878466.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16472.70 | 24-FEB-16:02 | 16472.70 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.415652E+09 | 0.00 | 95.48 | 0.283684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16788.79 | 24-MAR-15:01 | 16788.79 | 24-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.221118E+10 | 0.00 | 275.17 | 0.132178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16788.56 | 09-APR-15:01 | 16788.56 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.501598E+10 | 0.00 | 592.48 | 0.252576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17113.16 | 11-MAY-15:01 | 16786.60 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.856926E+10 | 0.00 | 634.37 | 0.464510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18074.95 | 14-JUN-08:62 | 14933.17 | 04-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.105195E+11 | 0.00 | 716.20 | 0.555523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18752.32 | 20-JUL-08:61 | 14918.07 | 02-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.924388E+10 | 0.00 | 710.88 | 0.458199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19745.08 | 31-AUG-08:61 | 14961.49 | 29-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.576303E+10 | 0.00 | 526.07 | 0.323716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16774.01 | 30-SEP-15:01 | 16774.01 | 30-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.982694E+09 | 0.00 | 205.90 | 0.611768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16789.57 | 29-OCT-15:01 | 16789.57 | 29-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.175610E+09 | 0.00 | 42.36 | 0.113026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16783.71 | 04-NOV-15:01 | 16783.71 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 20409799.58 | 0.00 | 6.26 | 19898146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8940.21 | 03-DEC-09:02 | 8940.21 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430037E+11 | 0.00 | 3821.13 | 0.229664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4078868.28 | 0.00 | 2.20 | 4078868.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2188.06 | 2188.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105195E+11 | 0.00 | 716.20 | 0.555523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19745.08 | 16789.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 215277.45 | 0.00 | 0.05 | 215277.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.61 | 12-JAN-09:04 | 2065.61 | 12-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 12994246.52 | 0.00 | 5.01 | 10480366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 13986.65 | 24-FEB-09:01 | 13986.65 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.121039E+09 | 0.00 | 33.93 | 77571361.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15098.86 | 24-MAR-15:01 | 15098.86 | 24-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.129704E+10 | 0.00 | 175.10 | 0.744291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17846.99 | 16-APR-08:51 | 16298.13 | 25-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.359409E+10 | 0.00 | 472.85 | 0.177823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20185.67 | 31-MAY-08:32 | 16835.44 | 31-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.680332E+10 | 0.00 | 496.09 | 0.375366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21778.36 | 26-JUN-07:52 | 18017.27 | 09-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.789784E+10 | 0.00 | 518.46 | 0.420127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21024.18 | 30-JUL-08:32 | 17547.91 | 13-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.653616E+10 | 0.00 | 518.84 | 0.316903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21108.38 | 03-AUG-07:51 | 16528.71 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.369982E+10 | 0.00 | 397.75 | 0.189709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18598.47 | 11-SEP-08:51 | 16738.17 | 08-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.238304E+09 | 0.00 | 67.87 | 0.126294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15405.70 | 02-OCT-15:01 | 13845.87 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 20625418.50 | 0.00 | 6.15 | 11350961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8855.88 | 04-NOV-08:62 | 8502.18 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 352062.04 | 0.00 | 0.11 | 352062.04 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.09 | 03-DEC-09:03 | 1642.09 | 03-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302218E+11 | 0.00 | 2692.20 | 0.157698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 215277.45 | 0.00 | 0.05 | 215277.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.09 | 1642.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.789784E+10 | 0.00 | 518.84 | 0.420127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21778.36 | 18017.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1199152.75 | 0.00 | 0.79 | 1199152.75 | 0.00 | 0.00 | 0.00 | 0.00 | 4630.33 | 12-JAN-16:01 | 4630.33 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 32965548.58 | 0.00 | 16.51 | 32836614.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4799.44 | 25-FEB-16:01 | 4799.44 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.101164E+09 | 0.00 | 63.83 | 80637091.07 | 0.00 | 0.00 | 0.00 | 0.00 | 4799.50 | 23-MAR-18:01 | 4799.50 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.673413E+09 | 0.00 | 242.20 | 0.462473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4931.94 | 16-APR-08:61 | 4799.13 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.117677E+10 | 0.00 | 490.54 | 0.640505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5021.37 | 29-MAY-08:61 | 4799.32 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.214687E+10 | 0.00 | 588.41 | 0.119364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5385.25 | 25-JUN-08:61 | 4257.38 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.271645E+10 | 0.00 | 696.07 | 0.149122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5537.46 | 20-JUL-08:61 | 4243.72 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.236740E+10 | 0.00 | 688.68 | 0.122397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5797.99 | 31-AUG-08:61 | 4190.32 | 03-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.138745E+10 | 0.00 | 456.81 | 0.818989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5026.96 | 11-SEP-08:61 | 4799.41 | 23-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.289538E+09 | 0.00 | 148.68 | 0.205725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4799.52 | 19-OCT-15:01 | 4799.52 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 53604267.99 | 0.00 | 26.14 | 39828563.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4797.70 | 04-NOV-15:01 | 4797.70 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1828631.83 | 0.00 | 0.92 | 1800610.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4581.21 | 01-DEC-16:01 | 4581.21 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109487E+11 | 0.00 | 3419.59 | 0.619283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1199152.75 | 0.00 | 0.79 | 1199152.75 | 0.00 | 0.00 | 0.00 | 0.00 | 4581.21 | 4190.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.271645E+10 | 0.00 | 696.07 | 0.149122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5797.99 | 4799.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 60233.35 | 0.00 | 0.05 | 60233.35 | 0.00 | 0.00 | 0.00 | 0.00 | 664.53 | 13-JAN-16:04 | 664.53 | 13-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 5766639.47 | 0.00 | 5.40 | 5699125.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4495.57 | 24-FEB-16:02 | 4495.57 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 27225366.72 | 0.00 | 26.25 | 21262888.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4720.23 | 23-MAR-18:01 | 4720.23 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.406756E+09 | 0.00 | 166.07 | 0.264789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.53 | 16-APR-21:51 | 4810.59 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.780390E+09 | 0.00 | 383.01 | 0.382052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5266.74 | 20-MAY-18:41 | 5266.74 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.173893E+10 | 0.00 | 455.06 | 0.977838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6083.82 | 26-JUN-08:11 | 4841.69 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.212546E+10 | 0.00 | 506.28 | 0.118555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5594.55 | 02-JUL-08:51 | 4690.35 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.170903E+10 | 0.00 | 504.62 | 0.850000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6262.10 | 03-AUG-07:51 | 4620.88 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.877599E+09 | 0.00 | 329.59 | 0.464649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.59 | 19-SEP-17:41 | 5374.59 | 19-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 79172341.53 | 0.00 | 61.95 | 51100530.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4583.25 | 24-OCT-15:01 | 4583.25 | 24-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 14998524.70 | 0.00 | 7.45 | 10328097.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.42 | 04-NOV-15:01 | 4643.42 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 124742.63 | 0.00 | 0.08 | 124742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 689.41 | 02-DEC-16:03 | 689.41 | 02-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776551E+10 | 0.00 | 2445.80 | 0.421345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 60233.35 | 0.00 | 0.05 | 60233.35 | 0.00 | 0.00 | 0.00 | 0.00 | 664.53 | 664.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212546E+10 | 0.00 | 506.28 | 0.118555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6262.10 | 5374.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.422568E+09 | 0.00 | 45.45 | 0.421742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22172.84 | 13-JAN-16:01 | 22172.84 | 13-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.885005E+09 | 0.00 | 83.98 | 0.728017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22170.63 | 19-FEB-16:01 | 22170.63 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.161756E+10 | 0.00 | 190.10 | 0.119451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22171.44 | 31-MAR-15:01 | 22171.44 | 31-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.396368E+10 | 0.00 | 309.34 | 0.258440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22617.55 | 16-APR-08:61 | 22167.40 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.631541E+10 | 0.00 | 562.14 | 0.304782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22920.73 | 31-MAY-08:61 | 21976.19 | 21-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.996952E+10 | 0.00 | 610.87 | 0.503302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25109.00 | 25-JUN-08:61 | 19602.44 | 04-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.125724E+11 | 0.00 | 690.19 | 0.632623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25989.94 | 20-JUL-08:61 | 19661.21 | 14-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.123925E+11 | 0.00 | 687.19 | 0.634426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27146.54 | 31-AUG-08:61 | 19744.64 | 03-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.905503E+10 | 0.00 | 540.13 | 0.562405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23365.53 | 11-SEP-08:61 | 22166.29 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.421591E+10 | 0.00 | 352.83 | 0.314535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22170.98 | 27-OCT-15:01 | 22170.98 | 27-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.133726E+10 | 0.00 | 144.20 | 0.101645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22160.77 | 11-NOV-16:01 | 22160.77 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.866227E+09 | 0.00 | 79.83 | 0.829854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22157.16 | 01-DEC-16:01 | 22157.16 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.636130E+11 | 0.00 | 4296.26 | 0.362957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.422568E+09 | 0.00 | 45.45 | 0.421742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22157.16 | 19602.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.125724E+11 | 0.00 | 690.19 | 0.634426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27146.54 | 22172.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 867.18 | 594.15 | 273.04 | 756.32 | 940.32 | 0.00 | 0.00 | 0.00 |
February | 934.82 | 634.23 | 300.59 | 855.58 | 741.86 | 0.00 | 0.00 | 0.00 |
March | 800.77 | 419.18 | 381.59 | 760.69 | 544.27 | 0.00 | 0.00 | 0.00 |
April | 713.90 | 327.18 | 386.72 | 763.08 | 392.57 | 0.00 | 0.00 | 0.00 |
May | 608.86 | 170.32 | 438.54 | 715.30 | 213.99 | 0.00 | 0.00 | 0.00 |
June | 581.22 | 116.07 | 465.15 | 754.61 | 136.53 | 0.00 | 0.00 | 0.00 |
July | 616.80 | 154.26 | 462.54 | 834.14 | 114.56 | 0.00 | 0.00 | 0.00 |
August | 683.50 | 236.70 | 446.81 | 928.82 | 141.40 | 0.00 | 0.00 | 0.00 |
September | 825.25 | 425.84 | 399.41 | 1040.25 | 253.05 | 0.00 | 0.00 | 0.00 |
October | 889.33 | 560.68 | 328.64 | 975.29 | 402.92 | 0.00 | 0.00 | 0.00 |
November | 665.62 | 416.74 | 248.88 | 616.12 | 607.34 | 0.00 | 0.00 | 0.00 |
December | 708.75 | 536.76 | 171.99 | 657.66 | 885.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 740.24 | 381.28 | 358.96 | 804.53 | 446.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.22 | 116.07 | 171.99 | 616.12 | 114.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 934.82 | 634.23 | 465.15 | 1040.25 | 940.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2441.93 | 1673.08 | 768.85 | 2112.49 | 2672.72 | 0.00 | 0.00 | 0.00 |
February | 2632.40 | 1785.95 | 846.45 | 2388.17 | 2134.50 | 0.00 | 0.00 | 0.00 |
March | 2254.92 | 1180.40 | 1074.52 | 2113.92 | 1586.05 | 0.00 | 0.00 | 0.00 |
April | 2010.29 | 921.31 | 1088.99 | 2122.35 | 1169.82 | 0.00 | 0.00 | 0.00 |
May | 1714.50 | 479.61 | 1234.89 | 1969.78 | 671.14 | 0.00 | 0.00 | 0.00 |
June | 1636.69 | 326.85 | 1309.83 | 2089.01 | 432.24 | 0.00 | 0.00 | 0.00 |
July | 1736.88 | 434.39 | 1302.49 | 2316.84 | 360.18 | 0.00 | 0.00 | 0.00 |
August | 1924.70 | 666.53 | 1258.17 | 2585.07 | 444.14 | 0.00 | 0.00 | 0.00 |
September | 2323.84 | 1199.13 | 1124.71 | 2898.78 | 773.33 | 0.00 | 0.00 | 0.00 |
October | 2504.29 | 1578.85 | 925.44 | 2713.98 | 1211.27 | 0.00 | 0.00 | 0.00 |
November | 1874.36 | 1173.52 | 700.84 | 1712.55 | 1761.74 | 0.00 | 0.00 | 0.00 |
December | 1995.80 | 1511.48 | 484.32 | 1835.20 | 2521.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2084.46 | 1073.66 | 1010.80 | 2237.30 | 1307.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1636.69 | 326.85 | 484.32 | 1712.55 | 360.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2632.40 | 1785.95 | 1309.83 | 2898.78 | 2672.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3172.21 | 2173.42 | 998.78 | 2781.49 | 3610.97 | 0.00 | 0.00 | 0.00 |
February | 3419.64 | 2320.05 | 1099.59 | 3157.06 | 2874.79 | 0.00 | 0.00 | 0.00 |
March | 2929.27 | 1533.40 | 1395.87 | 2793.08 | 2157.78 | 0.00 | 0.00 | 0.00 |
April | 2611.48 | 1196.83 | 1414.65 | 2809.98 | 1596.72 | 0.00 | 0.00 | 0.00 |
May | 2227.23 | 623.04 | 1604.19 | 2600.53 | 917.75 | 0.00 | 0.00 | 0.00 |
June | 2126.15 | 424.60 | 1701.55 | 2765.35 | 587.63 | 0.00 | 0.00 | 0.00 |
July | 2256.31 | 564.29 | 1692.01 | 3069.96 | 482.29 | 0.00 | 0.00 | 0.00 |
August | 2500.30 | 865.86 | 1634.44 | 3422.99 | 591.88 | 0.00 | 0.00 | 0.00 |
September | 3018.80 | 1557.74 | 1461.06 | 3827.13 | 1046.97 | 0.00 | 0.00 | 0.00 |
October | 3253.21 | 2051.01 | 1202.20 | 3577.38 | 1646.22 | 0.00 | 0.00 | 0.00 |
November | 2434.89 | 1524.47 | 910.43 | 2248.56 | 2407.90 | 0.00 | 0.00 | 0.00 |
December | 2592.66 | 1963.50 | 629.16 | 2419.75 | 3418.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2707.83 | 1394.74 | 1313.08 | 2954.93 | 1773.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2126.15 | 424.60 | 629.16 | 2248.56 | 482.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3419.64 | 2320.05 | 1701.55 | 3827.13 | 3610.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 149.06 | 194.68 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 167.48 | 155.59 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 150.11 | 111.06 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 150.84 | 79.36 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 140.27 | 42.51 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 150.95 | 24.68 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 167.50 | 19.20 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 186.05 | 24.29 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 207.89 | 47.62 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 193.76 | 80.16 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 122.28 | 123.46 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.92 | 179.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 159.71 | 89.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 122.28 | 19.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 207.89 | 194.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 46.26 | 412.54 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 98.07 | 327.71 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 138.32 | 214.38 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 282.02 | 144.37 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 317.43 | 77.05 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 417.50 | 45.43 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 462.44 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 402.82 | 45.03 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 296.92 | 88.47 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 159.31 | 156.20 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 61.50 | 252.22 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 40.81 | 371.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 227.60 | 180.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 40.81 | 35.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 462.44 | 412.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.09 | 236.26 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.60 | 188.99 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 15.94 | 120.77 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.66 | 79.23 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 71.13 | 40.17 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 108.63 | 24.69 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 106.34 | 20.64 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 88.30 | 25.55 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 54.12 | 49.47 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 19.77 | 85.57 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 4.86 | 140.75 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.02 | 207.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 42.28 | 101.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.02 | 20.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 108.63 | 236.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 48.15 | 409.62 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 101.41 | 323.65 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 142.41 | 212.03 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 284.35 | 143.98 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 315.77 | 78.66 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 413.39 | 48.37 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 457.87 | 40.04 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 400.10 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 298.18 | 90.10 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 164.00 | 154.05 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 64.24 | 249.81 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 43.10 | 368.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 228.38 | 180.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 43.10 | 40.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 457.87 | 409.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.14 | 93.96 | 43.18 | 122.48 | 137.96 | 0.00 | 0.00 | 0.00 |
February | 147.84 | 100.30 | 47.54 | 134.53 | 121.57 | 0.00 | 0.00 | 0.00 |
March | 126.64 | 66.29 | 60.35 | 116.52 | 93.15 | 0.00 | 0.00 | 0.00 |
April | 112.90 | 51.74 | 61.16 | 113.14 | 82.32 | 0.00 | 0.00 | 0.00 |
May | 96.29 | 26.93 | 69.35 | 99.68 | 52.07 | 0.00 | 0.00 | 0.00 |
June | 91.92 | 18.36 | 73.56 | 107.42 | 35.25 | 0.00 | 0.00 | 0.00 |
July | 97.54 | 24.40 | 73.15 | 120.78 | 29.56 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 37.43 | 70.66 | 136.28 | 35.53 | 0.00 | 0.00 | 0.00 |
September | 130.51 | 67.34 | 63.16 | 154.97 | 57.90 | 0.00 | 0.00 | 0.00 |
October | 140.64 | 88.67 | 51.97 | 143.20 | 87.20 | 0.00 | 0.00 | 0.00 |
November | 105.26 | 65.90 | 39.36 | 92.43 | 109.44 | 0.00 | 0.00 | 0.00 |
December | 112.08 | 84.88 | 27.20 | 106.07 | 130.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.06 | 60.30 | 56.77 | 120.55 | 80.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.92 | 18.36 | 27.20 | 92.43 | 29.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 147.84 | 100.30 | 73.56 | 154.97 | 137.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.99 | 0.00 | 21.99 | 0.04 | 194.88 | 0.00 | 0.00 | 0.00 |
February | 27.88 | 0.00 | 27.88 | 1.04 | 155.55 | 0.00 | 0.00 | 0.00 |
March | 41.79 | 0.00 | 41.79 | 12.33 | 99.36 | 0.00 | 0.00 | 0.00 |
April | 48.43 | 0.39 | 48.04 | 28.28 | 64.08 | 0.00 | 0.00 | 0.00 |
May | 62.97 | 2.39 | 60.58 | 60.00 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 73.69 | 6.83 | 66.86 | 91.10 | 18.61 | 0.00 | 0.00 | 0.00 |
July | 69.12 | 4.77 | 64.35 | 89.85 | 14.67 | 0.00 | 0.00 | 0.00 |
August | 57.91 | 1.17 | 56.74 | 74.87 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 44.32 | 0.04 | 44.28 | 45.56 | 38.58 | 0.00 | 0.00 | 0.00 |
October | 32.91 | 0.00 | 32.91 | 15.65 | 69.89 | 0.00 | 0.00 | 0.00 |
November | 23.02 | 0.00 | 23.02 | 3.55 | 117.01 | 0.00 | 0.00 | 0.00 |
December | 14.93 | 0.00 | 14.93 | 0.00 | 172.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 1.30 | 42.02 | 35.39 | 82.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.93 | 0.00 | 14.93 | 0.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.69 | 6.83 | 66.86 | 91.10 | 194.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.65 | 44.94 | 64.72 | 42.74 | 405.24 | 0.00 | 0.00 | 0.00 |
February | 146.01 | 64.26 | 81.74 | 77.17 | 320.47 | 0.00 | 0.00 | 0.00 |
March | 198.30 | 78.68 | 119.63 | 144.23 | 208.78 | 0.00 | 0.00 | 0.00 |
April | 242.03 | 105.49 | 136.55 | 229.46 | 141.03 | 0.00 | 0.00 | 0.00 |
May | 305.81 | 133.75 | 172.06 | 347.01 | 72.81 | 0.00 | 0.00 | 0.00 |
June | 336.08 | 146.41 | 189.67 | 427.79 | 43.03 | 0.00 | 0.00 | 0.00 |
July | 339.77 | 156.84 | 182.93 | 443.50 | 33.31 | 0.00 | 0.00 | 0.00 |
August | 286.45 | 123.45 | 163.00 | 372.67 | 42.11 | 0.00 | 0.00 | 0.00 |
September | 256.63 | 121.72 | 134.92 | 305.46 | 86.20 | 0.00 | 0.00 | 0.00 |
October | 162.51 | 67.64 | 94.87 | 139.35 | 151.16 | 0.00 | 0.00 | 0.00 |
November | 96.13 | 31.20 | 64.93 | 47.52 | 246.95 | 0.00 | 0.00 | 0.00 |
December | 74.19 | 31.76 | 42.42 | 29.44 | 365.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.13 | 92.31 | 120.82 | 217.96 | 175.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.19 | 31.20 | 42.42 | 29.44 | 33.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 339.77 | 156.84 | 189.67 | 443.50 | 405.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 148.82 | 194.46 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 167.17 | 154.95 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 149.01 | 110.74 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 150.32 | 78.44 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 139.10 | 42.30 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 150.12 | 24.30 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 166.96 | 18.62 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 185.72 | 23.81 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 207.01 | 47.25 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 193.10 | 79.79 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 122.17 | 123.19 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.91 | 179.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 159.16 | 89.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 122.17 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 207.01 | 194.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.07 | 236.20 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.41 | 188.46 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 15.34 | 120.88 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.31 | 78.20 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 70.25 | 39.68 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 107.79 | 24.00 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 105.43 | 19.58 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 87.87 | 24.46 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 53.04 | 48.76 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 19.18 | 84.97 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 4.74 | 140.50 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.01 | 207.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 41.78 | 100.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.01 | 19.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 107.79 | 236.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.65 | 44.94 | 64.72 | 43.80 | 401.41 | 0.00 | 0.00 | 0.00 |
February | 146.01 | 64.26 | 81.74 | 79.36 | 315.11 | 0.00 | 0.00 | 0.00 |
March | 198.30 | 78.68 | 119.63 | 147.79 | 205.77 | 0.00 | 0.00 | 0.00 |
April | 242.03 | 105.49 | 136.55 | 231.91 | 140.12 | 0.00 | 0.00 | 0.00 |
May | 305.81 | 133.75 | 172.06 | 346.40 | 74.07 | 0.00 | 0.00 | 0.00 |
June | 336.08 | 146.41 | 189.67 | 423.81 | 45.48 | 0.00 | 0.00 | 0.00 |
July | 339.77 | 156.84 | 182.93 | 438.21 | 36.92 | 0.00 | 0.00 | 0.00 |
August | 286.45 | 123.45 | 163.00 | 370.09 | 45.55 | 0.00 | 0.00 | 0.00 |
September | 256.63 | 121.72 | 134.92 | 306.48 | 87.20 | 0.00 | 0.00 | 0.00 |
October | 162.51 | 67.64 | 94.87 | 143.99 | 148.31 | 0.00 | 0.00 | 0.00 |
November | 96.13 | 31.20 | 64.93 | 49.36 | 243.59 | 0.00 | 0.00 | 0.00 |
December | 74.19 | 31.76 | 42.42 | 30.22 | 361.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.13 | 92.31 | 120.82 | 218.37 | 174.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.19 | 31.20 | 42.42 | 30.22 | 36.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 339.77 | 156.84 | 189.67 | 438.21 | 401.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.81 | 0.00 | 34.81 | 0.03 | 316.36 | 0.00 | 0.00 | 0.00 |
February | 44.13 | 0.00 | 44.13 | 1.31 | 249.81 | 0.00 | 0.00 | 0.00 |
March | 66.14 | 0.00 | 66.14 | 18.81 | 161.00 | 0.00 | 0.00 | 0.00 |
April | 76.66 | 0.62 | 76.04 | 43.95 | 104.84 | 0.00 | 0.00 | 0.00 |
May | 99.67 | 3.78 | 95.89 | 93.94 | 53.62 | 0.00 | 0.00 | 0.00 |
June | 116.63 | 10.81 | 105.82 | 140.62 | 34.22 | 0.00 | 0.00 | 0.00 |
July | 109.40 | 7.55 | 101.85 | 137.35 | 28.64 | 0.00 | 0.00 | 0.00 |
August | 91.66 | 1.86 | 89.81 | 113.81 | 35.58 | 0.00 | 0.00 | 0.00 |
September | 70.14 | 0.06 | 70.08 | 68.72 | 68.03 | 0.00 | 0.00 | 0.00 |
October | 52.09 | 0.00 | 52.09 | 24.20 | 113.49 | 0.00 | 0.00 | 0.00 |
November | 36.43 | 0.00 | 36.43 | 5.42 | 190.04 | 0.00 | 0.00 | 0.00 |
December | 23.63 | 0.00 | 23.63 | 0.00 | 280.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.58 | 2.06 | 66.51 | 54.33 | 135.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.63 | 0.00 | 23.63 | 0.00 | 28.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.63 | 10.81 | 105.82 | 140.62 | 316.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.83 | 0.00 | 12.83 | 0.01 | 116.62 | 0.00 | 0.00 | 0.00 |
February | 16.27 | 0.00 | 16.27 | 0.48 | 92.09 | 0.00 | 0.00 | 0.00 |
March | 24.38 | 0.00 | 24.38 | 6.93 | 59.35 | 0.00 | 0.00 | 0.00 |
April | 28.26 | 0.23 | 28.03 | 16.20 | 38.65 | 0.00 | 0.00 | 0.00 |
May | 36.74 | 1.39 | 35.35 | 34.63 | 19.77 | 0.00 | 0.00 | 0.00 |
June | 43.00 | 3.98 | 39.01 | 51.84 | 12.61 | 0.00 | 0.00 | 0.00 |
July | 40.33 | 2.78 | 37.55 | 50.63 | 10.56 | 0.00 | 0.00 | 0.00 |
August | 33.79 | 0.68 | 33.11 | 41.95 | 13.12 | 0.00 | 0.00 | 0.00 |
September | 25.86 | 0.02 | 25.83 | 25.33 | 25.08 | 0.00 | 0.00 | 0.00 |
October | 19.20 | 0.00 | 19.20 | 8.92 | 41.84 | 0.00 | 0.00 | 0.00 |
November | 13.43 | 0.00 | 13.43 | 2.00 | 70.06 | 0.00 | 0.00 | 0.00 |
December | 8.71 | 0.00 | 8.71 | 0.00 | 103.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.28 | 0.76 | 24.52 | 20.03 | 50.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.71 | 0.00 | 8.71 | 0.00 | 10.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.00 | 3.98 | 39.01 | 51.84 | 116.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.00 | 54.81 | 25.19 | 68.70 | 94.59 | 0.00 | 0.00 | 0.00 |
February | 86.24 | 58.51 | 27.73 | 78.21 | 74.50 | 0.00 | 0.00 | 0.00 |
March | 73.87 | 38.67 | 35.20 | 70.17 | 53.76 | 0.00 | 0.00 | 0.00 |
April | 65.86 | 30.18 | 35.68 | 71.38 | 38.54 | 0.00 | 0.00 | 0.00 |
May | 56.17 | 15.71 | 40.46 | 66.51 | 21.35 | 0.00 | 0.00 | 0.00 |
June | 53.62 | 10.71 | 42.91 | 70.61 | 13.54 | 0.00 | 0.00 | 0.00 |
July | 56.90 | 14.23 | 42.67 | 78.09 | 11.17 | 0.00 | 0.00 | 0.00 |
August | 63.06 | 21.84 | 41.22 | 86.97 | 13.78 | 0.00 | 0.00 | 0.00 |
September | 76.13 | 39.29 | 36.85 | 97.36 | 24.64 | 0.00 | 0.00 | 0.00 |
October | 82.04 | 51.73 | 30.32 | 91.36 | 38.59 | 0.00 | 0.00 | 0.00 |
November | 61.41 | 38.45 | 22.96 | 56.78 | 60.35 | 0.00 | 0.00 | 0.00 |
December | 65.39 | 49.52 | 15.87 | 60.64 | 88.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.29 | 35.17 | 33.12 | 74.71 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.62 | 10.71 | 15.87 | 56.78 | 11.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.24 | 58.51 | 42.91 | 97.36 | 94.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 217.14 | 148.77 | 68.37 | 186.46 | 256.74 | 0.00 | 0.00 | 0.00 |
February | 234.08 | 158.81 | 75.27 | 212.27 | 202.22 | 0.00 | 0.00 | 0.00 |
March | 200.51 | 104.96 | 95.55 | 190.47 | 145.91 | 0.00 | 0.00 | 0.00 |
April | 178.76 | 81.92 | 96.83 | 193.74 | 104.60 | 0.00 | 0.00 | 0.00 |
May | 152.46 | 42.65 | 109.81 | 180.53 | 57.94 | 0.00 | 0.00 | 0.00 |
June | 145.54 | 29.06 | 116.47 | 191.64 | 36.74 | 0.00 | 0.00 | 0.00 |
July | 154.45 | 38.63 | 115.82 | 211.94 | 30.31 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 59.27 | 111.88 | 236.04 | 37.39 | 0.00 | 0.00 | 0.00 |
September | 206.64 | 106.63 | 100.01 | 264.25 | 66.87 | 0.00 | 0.00 | 0.00 |
October | 222.68 | 140.39 | 82.29 | 247.98 | 104.73 | 0.00 | 0.00 | 0.00 |
November | 166.67 | 104.35 | 62.32 | 154.12 | 163.81 | 0.00 | 0.00 | 0.00 |
December | 177.47 | 134.40 | 43.07 | 164.59 | 239.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.35 | 95.47 | 89.88 | 202.78 | 120.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.54 | 29.06 | 43.07 | 154.12 | 30.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.08 | 158.81 | 116.47 | 264.25 | 256.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 148.34 | 194.92 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 166.62 | 155.72 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 149.52 | 110.94 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 149.91 | 79.10 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 139.06 | 42.32 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 149.94 | 24.30 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 166.44 | 18.79 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 184.89 | 23.93 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 207.04 | 46.98 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 193.03 | 79.77 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 121.95 | 123.22 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.63 | 179.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 158.90 | 89.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 121.95 | 18.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 207.04 | 194.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 45.86 | 413.73 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 97.18 | 328.81 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 137.59 | 214.18 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 280.11 | 143.80 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 315.08 | 76.59 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 415.18 | 44.71 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 459.97 | 34.79 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 400.57 | 44.32 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 295.72 | 87.26 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 158.49 | 155.33 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 61.52 | 251.62 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 40.78 | 372.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 226.32 | 179.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 40.78 | 34.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 459.97 | 413.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.10 | 236.94 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.62 | 189.44 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 16.05 | 120.64 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.40 | 79.15 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 70.06 | 40.35 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 107.54 | 24.80 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 105.39 | 20.82 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 87.60 | 25.81 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 54.08 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 20.07 | 84.95 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 5.02 | 140.27 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.02 | 208.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 41.99 | 101.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.02 | 20.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 107.54 | 236.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 47.68 | 410.75 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 100.62 | 324.67 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 141.82 | 211.86 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 282.57 | 143.54 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 312.90 | 78.79 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 410.48 | 48.48 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 454.96 | 40.27 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 397.52 | 49.69 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 297.07 | 89.29 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 163.73 | 152.99 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 64.37 | 249.24 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 42.99 | 369.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 227.02 | 180.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 42.99 | 40.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 454.96 | 410.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.46 | 172.29 | 79.17 | 210.09 | 293.56 | 0.00 | 0.00 | 0.00 |
February | 271.07 | 183.91 | 87.16 | 237.01 | 235.92 | 0.00 | 0.00 | 0.00 |
March | 232.20 | 121.55 | 110.65 | 213.68 | 167.10 | 0.00 | 0.00 | 0.00 |
April | 207.01 | 94.87 | 112.14 | 218.52 | 117.15 | 0.00 | 0.00 | 0.00 |
May | 176.55 | 49.39 | 127.16 | 204.57 | 61.62 | 0.00 | 0.00 | 0.00 |
June | 168.54 | 33.66 | 134.88 | 222.45 | 34.64 | 0.00 | 0.00 | 0.00 |
July | 178.86 | 44.73 | 134.13 | 247.32 | 25.91 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 68.64 | 129.56 | 273.16 | 33.89 | 0.00 | 0.00 | 0.00 |
September | 239.30 | 123.48 | 115.82 | 302.52 | 69.29 | 0.00 | 0.00 | 0.00 |
October | 257.88 | 162.58 | 95.30 | 278.29 | 120.59 | 0.00 | 0.00 | 0.00 |
November | 193.01 | 120.84 | 72.17 | 173.55 | 186.83 | 0.00 | 0.00 | 0.00 |
December | 205.52 | 155.65 | 49.87 | 185.56 | 271.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.65 | 110.56 | 104.09 | 230.52 | 134.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.54 | 33.66 | 49.87 | 173.55 | 25.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 271.07 | 183.91 | 134.88 | 302.52 | 293.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.37 | 0.00 | 192.37 | 0.01 | 1821.43 | 0.00 | 0.00 | 0.00 |
February | 243.89 | 0.00 | 243.89 | 3.80 | 1459.84 | 0.00 | 0.00 | 0.00 |
March | 365.57 | 0.00 | 365.56 | 79.99 | 994.57 | 0.00 | 0.00 | 0.00 |
April | 423.69 | 3.43 | 420.26 | 208.13 | 664.61 | 0.00 | 0.00 | 0.00 |
May | 550.88 | 20.87 | 530.01 | 462.74 | 337.39 | 0.00 | 0.00 | 0.00 |
June | 644.65 | 59.75 | 584.90 | 736.12 | 211.76 | 0.00 | 0.00 | 0.00 |
July | 604.66 | 41.71 | 562.95 | 728.37 | 169.95 | 0.00 | 0.00 | 0.00 |
August | 506.63 | 10.26 | 496.37 | 598.75 | 212.57 | 0.00 | 0.00 | 0.00 |
September | 387.70 | 0.36 | 387.34 | 353.17 | 413.68 | 0.00 | 0.00 | 0.00 |
October | 287.89 | 0.00 | 287.89 | 102.62 | 719.66 | 0.00 | 0.00 | 0.00 |
November | 201.38 | 0.00 | 201.38 | 20.13 | 1154.65 | 0.00 | 0.00 | 0.00 |
December | 130.63 | 0.00 | 130.63 | 0.00 | 1653.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.04 | 11.41 | 367.63 | 276.11 | 814.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.63 | 0.00 | 130.63 | 0.00 | 169.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 644.65 | 59.75 | 584.90 | 736.12 | 1821.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.37 | 0.00 | 192.37 | 0.00 | 1856.55 | 0.00 | 0.00 | 0.00 |
February | 243.89 | 0.00 | 243.89 | 2.86 | 1491.18 | 0.00 | 0.00 | 0.00 |
March | 365.57 | 0.00 | 365.56 | 73.15 | 1020.11 | 0.00 | 0.00 | 0.00 |
April | 423.69 | 3.43 | 420.26 | 199.78 | 682.85 | 0.00 | 0.00 | 0.00 |
May | 550.88 | 20.87 | 530.01 | 451.31 | 345.68 | 0.00 | 0.00 | 0.00 |
June | 644.65 | 59.75 | 584.90 | 726.97 | 217.84 | 0.00 | 0.00 | 0.00 |
July | 604.66 | 41.71 | 562.95 | 720.17 | 175.01 | 0.00 | 0.00 | 0.00 |
August | 506.63 | 10.26 | 496.37 | 590.60 | 218.60 | 0.00 | 0.00 | 0.00 |
September | 387.70 | 0.36 | 387.34 | 344.98 | 424.19 | 0.00 | 0.00 | 0.00 |
October | 287.89 | 0.00 | 287.89 | 94.23 | 738.74 | 0.00 | 0.00 | 0.00 |
November | 201.38 | 0.00 | 201.38 | 17.46 | 1184.28 | 0.00 | 0.00 | 0.00 |
December | 130.63 | 0.00 | 130.63 | 0.00 | 1690.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.04 | 11.41 | 367.63 | 270.05 | 834.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.63 | 0.00 | 130.63 | 0.00 | 175.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 644.65 | 59.75 | 584.90 | 726.97 | 1856.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.11 | 235.36 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.74 | 184.93 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 18.38 | 125.87 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 42.79 | 82.70 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 90.50 | 44.35 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 133.08 | 28.41 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 133.20 | 22.71 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 112.82 | 27.67 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 70.48 | 51.10 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 25.39 | 87.99 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 6.83 | 143.96 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.03 | 212.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 53.25 | 103.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.03 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 133.20 | 235.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.29 | 89.86 | 129.42 | 94.15 | 804.37 | 0.00 | 0.00 | 0.00 |
February | 291.99 | 128.52 | 163.48 | 168.70 | 621.34 | 0.00 | 0.00 | 0.00 |
March | 396.58 | 157.34 | 239.23 | 312.82 | 432.70 | 0.00 | 0.00 | 0.00 |
April | 484.03 | 210.96 | 273.07 | 502.99 | 299.85 | 0.00 | 0.00 | 0.00 |
May | 611.58 | 267.49 | 344.09 | 767.80 | 164.73 | 0.00 | 0.00 | 0.00 |
June | 672.10 | 292.79 | 379.31 | 940.88 | 106.51 | 0.00 | 0.00 | 0.00 |
July | 679.49 | 313.66 | 365.83 | 979.94 | 85.03 | 0.00 | 0.00 | 0.00 |
August | 572.86 | 246.88 | 325.98 | 833.42 | 103.34 | 0.00 | 0.00 | 0.00 |
September | 513.23 | 243.41 | 269.81 | 682.81 | 185.67 | 0.00 | 0.00 | 0.00 |
October | 325.01 | 135.28 | 189.73 | 318.32 | 310.71 | 0.00 | 0.00 | 0.00 |
November | 192.24 | 62.39 | 129.85 | 109.52 | 503.59 | 0.00 | 0.00 | 0.00 |
December | 148.36 | 63.52 | 84.84 | 63.21 | 741.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 426.22 | 184.60 | 241.62 | 482.93 | 362.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.36 | 62.39 | 84.84 | 63.21 | 85.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 679.49 | 313.66 | 379.31 | 979.94 | 804.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 152.55 | 193.51 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 174.33 | 152.59 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 156.58 | 115.28 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 162.22 | 82.56 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 158.66 | 46.86 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 172.84 | 29.87 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 191.72 | 23.49 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 208.80 | 28.57 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 226.04 | 50.53 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 205.36 | 83.19 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 127.41 | 126.54 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 133.86 | 182.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 172.52 | 92.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 127.41 | 23.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 226.04 | 193.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.81 | 0.00 | 34.81 | 0.01 | 319.05 | 0.00 | 0.00 | 0.00 |
February | 44.13 | 0.00 | 44.13 | 1.01 | 250.40 | 0.00 | 0.00 | 0.00 |
March | 66.14 | 0.00 | 66.14 | 17.29 | 164.17 | 0.00 | 0.00 | 0.00 |
April | 76.66 | 0.62 | 76.04 | 41.11 | 107.37 | 0.00 | 0.00 | 0.00 |
May | 99.67 | 3.78 | 95.89 | 89.59 | 55.32 | 0.00 | 0.00 | 0.00 |
June | 116.63 | 10.81 | 105.82 | 135.65 | 35.89 | 0.00 | 0.00 | 0.00 |
July | 109.40 | 7.55 | 101.85 | 132.79 | 30.00 | 0.00 | 0.00 | 0.00 |
August | 91.66 | 1.86 | 89.81 | 109.69 | 37.09 | 0.00 | 0.00 | 0.00 |
September | 70.14 | 0.06 | 70.08 | 66.07 | 68.83 | 0.00 | 0.00 | 0.00 |
October | 52.09 | 0.00 | 52.09 | 22.03 | 115.95 | 0.00 | 0.00 | 0.00 |
November | 36.43 | 0.00 | 36.43 | 4.81 | 193.26 | 0.00 | 0.00 | 0.00 |
December | 23.63 | 0.00 | 23.63 | 0.00 | 284.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.58 | 2.06 | 66.51 | 51.98 | 137.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.63 | 0.00 | 23.63 | 0.00 | 30.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.63 | 10.81 | 105.82 | 135.65 | 319.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.14 | 0.00 | 31.14 | 0.01 | 285.44 | 0.00 | 0.00 | 0.00 |
February | 39.48 | 0.00 | 39.48 | 0.90 | 224.03 | 0.00 | 0.00 | 0.00 |
March | 59.18 | 0.00 | 59.18 | 15.47 | 146.89 | 0.00 | 0.00 | 0.00 |
April | 68.58 | 0.55 | 68.03 | 36.78 | 96.07 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 3.38 | 85.80 | 80.16 | 49.50 | 0.00 | 0.00 | 0.00 |
June | 104.35 | 9.67 | 94.68 | 121.37 | 32.11 | 0.00 | 0.00 | 0.00 |
July | 97.88 | 6.75 | 91.13 | 118.81 | 26.85 | 0.00 | 0.00 | 0.00 |
August | 82.01 | 1.66 | 80.35 | 98.14 | 33.18 | 0.00 | 0.00 | 0.00 |
September | 62.76 | 0.06 | 62.70 | 59.11 | 61.58 | 0.00 | 0.00 | 0.00 |
October | 46.60 | 0.00 | 46.60 | 19.71 | 103.74 | 0.00 | 0.00 | 0.00 |
November | 32.60 | 0.00 | 32.60 | 4.31 | 172.91 | 0.00 | 0.00 | 0.00 |
December | 21.15 | 0.00 | 21.15 | 0.00 | 254.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.36 | 1.85 | 59.51 | 46.50 | 123.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.15 | 0.00 | 21.15 | 0.00 | 26.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.35 | 9.67 | 94.68 | 121.37 | 285.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.10 | 438.56 | 201.54 | 543.81 | 761.35 | 0.00 | 0.00 | 0.00 |
February | 690.03 | 468.15 | 221.88 | 620.43 | 596.44 | 0.00 | 0.00 | 0.00 |
March | 591.08 | 309.42 | 281.67 | 551.69 | 437.59 | 0.00 | 0.00 | 0.00 |
April | 526.96 | 241.50 | 285.46 | 559.93 | 315.69 | 0.00 | 0.00 | 0.00 |
May | 449.42 | 125.72 | 323.70 | 518.17 | 176.56 | 0.00 | 0.00 | 0.00 |
June | 429.03 | 85.68 | 343.35 | 549.67 | 113.86 | 0.00 | 0.00 | 0.00 |
July | 455.29 | 113.87 | 341.42 | 610.26 | 93.86 | 0.00 | 0.00 | 0.00 |
August | 504.52 | 174.72 | 329.81 | 681.66 | 115.20 | 0.00 | 0.00 | 0.00 |
September | 609.15 | 314.33 | 294.82 | 768.23 | 199.72 | 0.00 | 0.00 | 0.00 |
October | 656.45 | 413.86 | 242.59 | 719.59 | 314.98 | 0.00 | 0.00 | 0.00 |
November | 491.32 | 307.61 | 183.71 | 447.15 | 490.73 | 0.00 | 0.00 | 0.00 |
December | 523.16 | 396.20 | 126.96 | 479.67 | 713.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.40 | 281.44 | 264.96 | 587.32 | 359.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.03 | 85.68 | 126.96 | 447.15 | 93.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.03 | 468.15 | 343.35 | 768.23 | 761.35 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232266E+10 | 0.159136E+10 | 0.731301E+09 | 0.202572E+10 | 0.251854E+10 |
February | 0.226152E+10 | 0.153433E+10 | 0.727194E+09 | 0.206982E+10 | 0.179470E+10 |
March | 0.214479E+10 | 0.112274E+10 | 0.102204E+10 | 0.203742E+10 | 0.145776E+10 |
April | 0.185043E+10 | 0.848040E+09 | 0.100239E+10 | 0.197790E+10 | 0.101753E+10 |
May | 0.163076E+10 | 0.456187E+09 | 0.117457E+10 | 0.191585E+10 | 0.573156E+09 |
June | 0.150653E+10 | 0.300860E+09 | 0.120567E+10 | 0.195594E+10 | 0.353884E+09 |
July | 0.165205E+10 | 0.413171E+09 | 0.123888E+10 | 0.223417E+10 | 0.306843E+09 |
August | 0.183070E+10 | 0.633976E+09 | 0.119672E+10 | 0.248775E+10 | 0.378724E+09 |
September | 0.213904E+10 | 0.110377E+10 | 0.103527E+10 | 0.269632E+10 | 0.655911E+09 |
October | 0.238198E+10 | 0.150174E+10 | 0.880239E+09 | 0.261223E+10 | 0.107919E+10 |
November | 0.172530E+10 | 0.108019E+10 | 0.645105E+09 | 0.159699E+10 | 0.157423E+10 |
December | 0.189833E+10 | 0.143766E+10 | 0.460667E+09 | 0.176149E+10 | 0.237041E+10 |
Annual Sum or Average | 0.233441E+11 | 0.120240E+11 | 0.113200E+11 | 0.253716E+11 | 0.140809E+11 |
Minimum of Months | 0.150653E+10 | 0.300860E+09 | 0.460667E+09 | 0.159699E+10 | 0.306843E+09 |
Maximum of Months | 0.238198E+10 | 0.159136E+10 | 0.123888E+10 | 0.269632E+10 | 0.251854E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.654047E+10 | 0.448117E+10 | 0.205930E+10 | 0.565810E+10 | 0.715863E+10 |
February | 0.636831E+10 | 0.432057E+10 | 0.204773E+10 | 0.577747E+10 | 0.516378E+10 |
March | 0.603958E+10 | 0.316157E+10 | 0.287800E+10 | 0.566191E+10 | 0.424808E+10 |
April | 0.521068E+10 | 0.238803E+10 | 0.282265E+10 | 0.550114E+10 | 0.303216E+10 |
May | 0.459212E+10 | 0.128459E+10 | 0.330752E+10 | 0.527587E+10 | 0.179758E+10 |
June | 0.424230E+10 | 0.847203E+09 | 0.339509E+10 | 0.541470E+10 | 0.112038E+10 |
July | 0.465206E+10 | 0.116346E+10 | 0.348860E+10 | 0.620544E+10 | 0.964712E+09 |
August | 0.515513E+10 | 0.178524E+10 | 0.336989E+10 | 0.692385E+10 | 0.118957E+10 |
September | 0.602340E+10 | 0.310816E+10 | 0.291524E+10 | 0.751364E+10 | 0.200447E+10 |
October | 0.670748E+10 | 0.422879E+10 | 0.247870E+10 | 0.726913E+10 | 0.324425E+10 |
November | 0.485833E+10 | 0.304176E+10 | 0.181657E+10 | 0.443893E+10 | 0.456644E+10 |
December | 0.534556E+10 | 0.404835E+10 | 0.129721E+10 | 0.491541E+10 | 0.675484E+10 |
Annual Sum or Average | 0.657354E+11 | 0.338589E+11 | 0.318765E+11 | 0.705556E+11 | 0.412449E+11 |
Minimum of Months | 0.424230E+10 | 0.847203E+09 | 0.129721E+10 | 0.443893E+10 | 0.964712E+09 |
Maximum of Months | 0.670748E+10 | 0.448117E+10 | 0.348860E+10 | 0.751364E+10 | 0.715863E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.849644E+10 | 0.582130E+10 | 0.267514E+10 | 0.744995E+10 | 0.967161E+10 |
February | 0.827279E+10 | 0.561267E+10 | 0.266012E+10 | 0.763756E+10 | 0.695470E+10 |
March | 0.784575E+10 | 0.410706E+10 | 0.373869E+10 | 0.748099E+10 | 0.577940E+10 |
April | 0.676897E+10 | 0.310218E+10 | 0.366678E+10 | 0.728347E+10 | 0.413871E+10 |
May | 0.596542E+10 | 0.166876E+10 | 0.429666E+10 | 0.696525E+10 | 0.245811E+10 |
June | 0.551098E+10 | 0.110057E+10 | 0.441042E+10 | 0.716778E+10 | 0.152313E+10 |
July | 0.604329E+10 | 0.151140E+10 | 0.453188E+10 | 0.822258E+10 | 0.129177E+10 |
August | 0.669681E+10 | 0.231912E+10 | 0.437768E+10 | 0.916814E+10 | 0.158528E+10 |
September | 0.782473E+10 | 0.403767E+10 | 0.378706E+10 | 0.991992E+10 | 0.271374E+10 |
October | 0.871340E+10 | 0.549344E+10 | 0.321997E+10 | 0.958167E+10 | 0.440925E+10 |
November | 0.631125E+10 | 0.395142E+10 | 0.235983E+10 | 0.582828E+10 | 0.624129E+10 |
December | 0.694419E+10 | 0.525904E+10 | 0.168515E+10 | 0.648106E+10 | 0.915716E+10 |
Annual Sum or Average | 0.853940E+11 | 0.439846E+11 | 0.414094E+11 | 0.931866E+11 | 0.559241E+11 |
Minimum of Months | 0.551098E+10 | 0.110057E+10 | 0.168515E+10 | 0.582828E+10 | 0.129177E+10 |
Maximum of Months | 0.871340E+10 | 0.582130E+10 | 0.453188E+10 | 0.991992E+10 | 0.967161E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.399236E+09 | 0.521419E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.405170E+09 | 0.376406E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.402055E+09 | 0.297473E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.390977E+09 | 0.205702E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.375687E+09 | 0.113857E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.391267E+09 | 63971859.21 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.448634E+09 | 51437051.36 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.498305E+09 | 65053595.67 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.538861E+09 | 0.123426E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.518980E+09 | 0.214707E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.316948E+09 | 0.320004E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.350645E+09 | 0.481451E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.503676E+10 | 0.283491E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.316948E+09 | 51437051.36 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.538861E+09 | 0.521419E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.123902E+09 | 0.110494E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.237242E+09 | 0.792796E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.370489E+09 | 0.574208E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.730988E+09 | 0.374195E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.850203E+09 | 0.206365E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.108216E+10 | 0.117759E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123861E+10 | 95286815.38 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107890E+10 | 0.120614E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.769621E+09 | 0.229304E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.426700E+09 | 0.418369E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.159402E+09 | 0.653761E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.109312E+09 | 0.995707E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.717753E+10 | 0.568331E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.109312E+09 | 95286815.38 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123861E+10 | 0.110494E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 238596.22 | 0.632806E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3859700.03 | 0.457200E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 42689638.20 | 0.323459E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 87242348.70 | 0.205356E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.190524E+09 | 0.107593E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.281578E+09 | 63991089.53 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.284809E+09 | 55284489.02 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.236501E+09 | 68424893.42 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.140276E+09 | 0.128227E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 52944805.81 | 0.229180E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 12584815.96 | 0.364826E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 48104.64 | 0.556543E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.133330E+10 | 0.319289E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 48104.64 | 55284489.02 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.284809E+09 | 0.632806E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.128956E+09 | 0.109712E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.245324E+09 | 0.782975E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.381429E+09 | 0.567904E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.737025E+09 | 0.373199E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.845756E+09 | 0.210690E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.107151E+10 | 0.125375E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.122636E+10 | 0.107232E+09 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107163E+10 | 0.132212E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.772886E+09 | 0.233529E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.439256E+09 | 0.412597E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.166504E+09 | 0.647517E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.115446E+09 | 0.988142E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.720208E+10 | 0.567849E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.115446E+09 | 0.107232E+09 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.122636E+10 | 0.109712E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367312E+09 | 0.251662E+09 | 0.115650E+09 | 0.328058E+09 | 0.369513E+09 |
February | 0.357643E+09 | 0.242643E+09 | 0.115001E+09 | 0.325463E+09 | 0.294091E+09 |
March | 0.339182E+09 | 0.177553E+09 | 0.161629E+09 | 0.312087E+09 | 0.249484E+09 |
April | 0.292632E+09 | 0.134111E+09 | 0.158521E+09 | 0.293263E+09 | 0.213378E+09 |
May | 0.257894E+09 | 72142461.01 | 0.185752E+09 | 0.266975E+09 | 0.139469E+09 |
June | 0.238248E+09 | 47578762.80 | 0.190670E+09 | 0.278437E+09 | 91362570.52 |
July | 0.261261E+09 | 65339777.42 | 0.195921E+09 | 0.323505E+09 | 79166902.63 |
August | 0.289513E+09 | 0.100258E+09 | 0.189254E+09 | 0.365023E+09 | 95163975.06 |
September | 0.338274E+09 | 0.174553E+09 | 0.163721E+09 | 0.401680E+09 | 0.150074E+09 |
October | 0.376692E+09 | 0.237488E+09 | 0.139204E+09 | 0.383555E+09 | 0.233556E+09 |
November | 0.272843E+09 | 0.170824E+09 | 0.102019E+09 | 0.239571E+09 | 0.283666E+09 |
December | 0.300206E+09 | 0.227355E+09 | 72851358.19 | 0.284103E+09 | 0.348449E+09 |
Annual Sum or Average | 0.369170E+10 | 0.190151E+10 | 0.179019E+10 | 0.380172E+10 | 0.254737E+10 |
Minimum of Months | 0.238248E+09 | 47578762.80 | 72851358.19 | 0.239571E+09 | 79166902.63 |
Maximum of Months | 0.376692E+09 | 0.251662E+09 | 0.195921E+09 | 0.401680E+09 | 0.369513E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58895473.06 | 0.00 | 58895473.06 | 109685.49 | 0.521956E+09 |
February | 67442057.94 | 0.00 | 67442057.94 | 2511952.67 | 0.376317E+09 |
March | 0.111920E+09 | 993.85 | 0.111919E+09 | 33025625.95 | 0.266135E+09 |
April | 0.125530E+09 | 1015262.00 | 0.124515E+09 | 73307678.70 | 0.166090E+09 |
May | 0.168655E+09 | 6389204.19 | 0.162265E+09 | 0.160700E+09 | 84348028.83 |
June | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.236120E+09 | 48246758.58 |
July | 0.185118E+09 | 12769280.31 | 0.172349E+09 | 0.240646E+09 | 39301422.15 |
August | 0.155107E+09 | 3140916.24 | 0.151966E+09 | 0.200530E+09 | 50129359.99 |
September | 0.114867E+09 | 105193.30 | 0.114761E+09 | 0.118099E+09 | 99997644.38 |
October | 88137585.25 | 0.00 | 88137585.25 | 41913134.68 | 0.187201E+09 |
November | 59664261.98 | 0.00 | 59664261.98 | 9200587.79 | 0.303295E+09 |
December | 39991922.20 | 0.00 | 39991922.20 | 10007.58 | 0.461280E+09 |
Annual Sum or Average | 0.136632E+10 | 41122816.28 | 0.132520E+10 | 0.111617E+10 | 0.260430E+10 |
Minimum of Months | 39991922.20 | 0.00 | 39991922.20 | 10007.58 | 39301422.15 |
Maximum of Months | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.240646E+09 | 0.521956E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293690E+09 | 0.120355E+09 | 0.173335E+09 | 0.114478E+09 | 0.108540E+10 |
February | 0.353221E+09 | 0.155464E+09 | 0.197757E+09 | 0.186697E+09 | 0.775278E+09 |
March | 0.531135E+09 | 0.210730E+09 | 0.320405E+09 | 0.386306E+09 | 0.559203E+09 |
April | 0.627343E+09 | 0.273418E+09 | 0.353925E+09 | 0.594754E+09 | 0.365549E+09 |
May | 0.819085E+09 | 0.358244E+09 | 0.460841E+09 | 0.929423E+09 | 0.195003E+09 |
June | 0.871108E+09 | 0.379482E+09 | 0.491626E+09 | 0.110883E+10 | 0.111523E+09 |
July | 0.910034E+09 | 0.420082E+09 | 0.489951E+09 | 0.118787E+10 | 89223107.80 |
August | 0.767225E+09 | 0.330645E+09 | 0.436581E+09 | 0.998149E+09 | 0.112797E+09 |
September | 0.665190E+09 | 0.315486E+09 | 0.349704E+09 | 0.791753E+09 | 0.223435E+09 |
October | 0.435280E+09 | 0.181178E+09 | 0.254102E+09 | 0.373222E+09 | 0.404860E+09 |
November | 0.249166E+09 | 80867192.16 | 0.168299E+09 | 0.123163E+09 | 0.640086E+09 |
December | 0.198698E+09 | 85074026.75 | 0.113624E+09 | 78857723.75 | 0.978968E+09 |
Annual Sum or Average | 0.672118E+10 | 0.291103E+10 | 0.381015E+10 | 0.687351E+10 | 0.554132E+10 |
Minimum of Months | 0.198698E+09 | 80867192.16 | 0.113624E+09 | 78857723.75 | 89223107.80 |
Maximum of Months | 0.910034E+09 | 0.420082E+09 | 0.491626E+09 | 0.118787E+10 | 0.108540E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.398603E+09 | 0.520843E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.404427E+09 | 0.374865E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.399119E+09 | 0.296619E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.389639E+09 | 0.203316E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.372569E+09 | 0.113287E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.389107E+09 | 62973210.89 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.447190E+09 | 49867696.34 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.497434E+09 | 63774356.82 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.536565E+09 | 0.122460E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.517198E+09 | 0.213700E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.316671E+09 | 0.319303E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.350620E+09 | 0.480858E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.501914E+10 | 0.282187E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.316671E+09 | 49867696.34 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.536565E+09 | 0.520843E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 192824.21 | 0.632644E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3414341.32 | 0.455927E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 41097847.18 | 0.323770E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 86346784.08 | 0.202706E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.188156E+09 | 0.106271E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.279380E+09 | 62204721.87 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.282385E+09 | 52433344.29 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.235361E+09 | 65511755.72 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.137473E+09 | 0.126393E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 51374227.21 | 0.227594E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 12280826.92 | 0.364167E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 29942.85 | 0.556593E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.131749E+10 | 0.317621E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 29942.85 | 52433344.29 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.282385E+09 | 0.632644E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293690E+09 | 0.120355E+09 | 0.173335E+09 | 0.117326E+09 | 0.107513E+10 |
February | 0.353221E+09 | 0.155464E+09 | 0.197757E+09 | 0.191977E+09 | 0.762313E+09 |
March | 0.531135E+09 | 0.210730E+09 | 0.320405E+09 | 0.395837E+09 | 0.551147E+09 |
April | 0.627343E+09 | 0.273418E+09 | 0.353925E+09 | 0.601099E+09 | 0.363191E+09 |
May | 0.819085E+09 | 0.358244E+09 | 0.460841E+09 | 0.927804E+09 | 0.198393E+09 |
June | 0.871108E+09 | 0.379482E+09 | 0.491626E+09 | 0.109852E+10 | 0.117886E+09 |
July | 0.910034E+09 | 0.420082E+09 | 0.489951E+09 | 0.117370E+10 | 98887276.26 |
August | 0.767225E+09 | 0.330645E+09 | 0.436581E+09 | 0.991249E+09 | 0.121991E+09 |
September | 0.665190E+09 | 0.315486E+09 | 0.349704E+09 | 0.794386E+09 | 0.226024E+09 |
October | 0.435280E+09 | 0.181178E+09 | 0.254102E+09 | 0.385675E+09 | 0.397229E+09 |
November | 0.249166E+09 | 80867192.16 | 0.168299E+09 | 0.127948E+09 | 0.631378E+09 |
December | 0.198698E+09 | 85074026.75 | 0.113624E+09 | 80947564.93 | 0.968236E+09 |
Annual Sum or Average | 0.672118E+10 | 0.291103E+10 | 0.381015E+10 | 0.688647E+10 | 0.551180E+10 |
Minimum of Months | 0.198698E+09 | 80867192.16 | 0.113624E+09 | 80947564.93 | 98887276.26 |
Maximum of Months | 0.910034E+09 | 0.420082E+09 | 0.491626E+09 | 0.117370E+10 | 0.107513E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93221893.58 | 0.00 | 93221893.58 | 77873.61 | 0.847334E+09 |
February | 0.106750E+09 | 0.00 | 0.106750E+09 | 3173192.57 | 0.604338E+09 |
March | 0.177150E+09 | 1573.11 | 0.177149E+09 | 50386099.60 | 0.431211E+09 |
April | 0.198693E+09 | 1606993.56 | 0.197086E+09 | 0.113928E+09 | 0.271742E+09 |
May | 0.266953E+09 | 10113064.41 | 0.256839E+09 | 0.251598E+09 | 0.143606E+09 |
June | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.364478E+09 | 88697068.62 |
July | 0.293012E+09 | 20211680.59 | 0.272800E+09 | 0.367868E+09 | 76717836.32 |
August | 0.245510E+09 | 4971556.29 | 0.240538E+09 | 0.304825E+09 | 95300371.62 |
September | 0.181815E+09 | 166503.77 | 0.181648E+09 | 0.178130E+09 | 0.176345E+09 |
October | 0.139507E+09 | 0.00 | 0.139507E+09 | 64806661.70 | 0.303967E+09 |
November | 94438760.59 | 0.00 | 94438760.59 | 14048664.43 | 0.492592E+09 |
December | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 0.751952E+09 |
Annual Sum or Average | 0.216267E+10 | 65090687.00 | 0.209758E+10 | 0.171332E+10 | 0.428380E+10 |
Minimum of Months | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 76717836.32 |
Maximum of Months | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.367868E+09 | 0.847334E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34365449.99 | 0.00 | 34365449.99 | 28707.44 | 0.312362E+09 |
February | 39352373.77 | 0.00 | 39352373.77 | 1169770.17 | 0.222784E+09 |
March | 65304963.22 | 579.91 | 65304383.30 | 18574402.64 | 0.158962E+09 |
April | 73246539.20 | 592404.37 | 72654134.83 | 41998683.21 | 0.100175E+09 |
May | 98409767.03 | 3728094.29 | 94681672.73 | 92749316.84 | 52939214.85 |
June | 0.111446E+09 | 10329079.80 | 0.101117E+09 | 0.134362E+09 | 32697412.15 |
July | 0.108016E+09 | 7450862.37 | 0.100566E+09 | 0.135611E+09 | 28281371.10 |
August | 90504969.44 | 1832721.51 | 88672247.94 | 0.112371E+09 | 35131663.06 |
September | 67024524.33 | 61380.18 | 66963144.15 | 65665988.89 | 65008074.73 |
October | 51428193.38 | 0.00 | 51428193.38 | 23890418.94 | 0.112055E+09 |
November | 34814037.56 | 0.00 | 34814037.56 | 5178919.42 | 0.181590E+09 |
December | 23335246.85 | 0.00 | 23335246.85 | 0.00 | 0.277201E+09 |
Annual Sum or Average | 0.797248E+09 | 23995122.42 | 0.773253E+09 | 0.631600E+09 | 0.157919E+10 |
Minimum of Months | 23335246.85 | 0.00 | 23335246.85 | 0.00 | 28281371.10 |
Maximum of Months | 0.111446E+09 | 10329079.80 | 0.101117E+09 | 0.135611E+09 | 0.312362E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214275E+09 | 0.146810E+09 | 67465805.62 | 0.183998E+09 | 0.253355E+09 |
February | 0.208635E+09 | 0.141548E+09 | 67086999.07 | 0.189199E+09 | 0.180241E+09 |
March | 0.197866E+09 | 0.103578E+09 | 94288199.77 | 0.187955E+09 | 0.143986E+09 |
April | 0.170710E+09 | 78235132.85 | 92474964.41 | 0.185018E+09 | 99892834.10 |
May | 0.150445E+09 | 42085094.92 | 0.108360E+09 | 0.178152E+09 | 57177641.23 |
June | 0.138985E+09 | 27755592.49 | 0.111229E+09 | 0.183013E+09 | 35086086.95 |
July | 0.152409E+09 | 38116674.93 | 0.114293E+09 | 0.209144E+09 | 29913461.47 |
August | 0.168890E+09 | 58486891.36 | 0.110404E+09 | 0.232927E+09 | 36897750.69 |
September | 0.197336E+09 | 0.101828E+09 | 95508225.40 | 0.252352E+09 | 63859037.73 |
October | 0.219747E+09 | 0.138541E+09 | 81206153.04 | 0.244709E+09 | 0.103347E+09 |
November | 0.159166E+09 | 99652319.79 | 59513840.21 | 0.147181E+09 | 0.156430E+09 |
December | 0.175129E+09 | 0.132630E+09 | 42498637.86 | 0.162422E+09 | 0.236043E+09 |
Annual Sum or Average | 0.215359E+10 | 0.110927E+10 | 0.104433E+10 | 0.235607E+10 | 0.139623E+10 |
Minimum of Months | 0.138985E+09 | 27755592.49 | 42498637.86 | 0.147181E+09 | 29913461.47 |
Maximum of Months | 0.219747E+09 | 0.146810E+09 | 0.114293E+09 | 0.252352E+09 | 0.253355E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581588E+09 | 0.398472E+09 | 0.183116E+09 | 0.499409E+09 | 0.687657E+09 |
February | 0.566279E+09 | 0.384191E+09 | 0.182088E+09 | 0.513525E+09 | 0.489210E+09 |
March | 0.537048E+09 | 0.281131E+09 | 0.255917E+09 | 0.510149E+09 | 0.390807E+09 |
April | 0.463342E+09 | 0.212346E+09 | 0.250996E+09 | 0.502176E+09 | 0.271130E+09 |
May | 0.408340E+09 | 0.114228E+09 | 0.294112E+09 | 0.483540E+09 | 0.155192E+09 |
June | 0.377233E+09 | 75334355.29 | 0.301899E+09 | 0.496735E+09 | 95230816.69 |
July | 0.413670E+09 | 0.103456E+09 | 0.310214E+09 | 0.567659E+09 | 81191253.09 |
August | 0.458403E+09 | 0.158745E+09 | 0.299658E+09 | 0.632212E+09 | 0.100148E+09 |
September | 0.535610E+09 | 0.276381E+09 | 0.259229E+09 | 0.684936E+09 | 0.173326E+09 |
October | 0.596439E+09 | 0.376029E+09 | 0.220410E+09 | 0.664191E+09 | 0.280505E+09 |
November | 0.432010E+09 | 0.270477E+09 | 0.161533E+09 | 0.399478E+09 | 0.424584E+09 |
December | 0.475335E+09 | 0.359985E+09 | 0.115350E+09 | 0.440846E+09 | 0.640670E+09 |
Annual Sum or Average | 0.584530E+10 | 0.301077E+10 | 0.283452E+10 | 0.639486E+10 | 0.378965E+10 |
Minimum of Months | 0.377233E+09 | 75334355.29 | 0.115350E+09 | 0.399478E+09 | 81191253.09 |
Maximum of Months | 0.596439E+09 | 0.398472E+09 | 0.310214E+09 | 0.684936E+09 | 0.687657E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.397309E+09 | 0.522075E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.403075E+09 | 0.376709E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.400467E+09 | 0.297151E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.388566E+09 | 0.205023E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.372449E+09 | 0.113337E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.388657E+09 | 62993865.69 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.445788E+09 | 50338674.94 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.495218E+09 | 64086602.32 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.536641E+09 | 0.121762E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.517021E+09 | 0.213643E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.316086E+09 | 0.319389E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.349877E+09 | 0.481409E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.501116E+10 | 0.282792E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.316086E+09 | 50338674.94 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.536641E+09 | 0.522075E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.122836E+09 | 0.110813E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.235100E+09 | 0.795457E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.368522E+09 | 0.573663E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.726050E+09 | 0.372725E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.843912E+09 | 0.205139E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.107615E+10 | 0.115876E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123199E+10 | 93171227.53 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107288E+10 | 0.118696E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.766516E+09 | 0.226189E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.424502E+09 | 0.416037E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.159451E+09 | 0.652205E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.109229E+09 | 0.996556E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.713714E+10 | 0.567385E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.109229E+09 | 93171227.53 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123199E+10 | 0.110813E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 257232.03 | 0.634616E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3915415.75 | 0.458302E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 42985454.79 | 0.323117E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 86582268.51 | 0.205151E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.187656E+09 | 0.108072E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.278744E+09 | 64293544.31 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.282273E+09 | 55753072.83 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.234641E+09 | 69129569.75 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.140186E+09 | 0.127227E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 53747452.04 | 0.227538E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 13002221.00 | 0.363571E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 58759.46 | 0.557152E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.132405E+10 | 0.319392E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 58759.46 | 55753072.83 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.282273E+09 | 0.634616E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.127704E+09 | 0.110014E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.243418E+09 | 0.785444E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.379860E+09 | 0.567440E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.732420E+09 | 0.372062E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.838077E+09 | 0.211035E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.106396E+10 | 0.125663E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.121855E+10 | 0.107847E+09 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.106473E+10 | 0.133095E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.770017E+09 | 0.231443E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.438533E+09 | 0.409781E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.166844E+09 | 0.646033E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.115158E+09 | 0.989595E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.715927E+10 | 0.567958E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.115158E+09 | 0.107847E+09 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.121855E+10 | 0.110014E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673507E+09 | 0.461450E+09 | 0.212057E+09 | 0.562704E+09 | 0.786279E+09 |
February | 0.655778E+09 | 0.444912E+09 | 0.210867E+09 | 0.573385E+09 | 0.570728E+09 |
March | 0.621928E+09 | 0.325563E+09 | 0.296365E+09 | 0.572308E+09 | 0.447566E+09 |
April | 0.536573E+09 | 0.245907E+09 | 0.290666E+09 | 0.566397E+09 | 0.303664E+09 |
May | 0.472877E+09 | 0.132281E+09 | 0.340596E+09 | 0.547929E+09 | 0.165052E+09 |
June | 0.436855E+09 | 87240873.66 | 0.349614E+09 | 0.576579E+09 | 89795733.93 |
July | 0.479050E+09 | 0.119808E+09 | 0.359242E+09 | 0.662433E+09 | 69402422.19 |
August | 0.530853E+09 | 0.183835E+09 | 0.347018E+09 | 0.731627E+09 | 90770448.53 |
September | 0.620262E+09 | 0.320063E+09 | 0.300200E+09 | 0.784130E+09 | 0.179597E+09 |
October | 0.690706E+09 | 0.435460E+09 | 0.255246E+09 | 0.745359E+09 | 0.322982E+09 |
November | 0.500288E+09 | 0.313225E+09 | 0.187063E+09 | 0.449851E+09 | 0.484264E+09 |
December | 0.550461E+09 | 0.416880E+09 | 0.133581E+09 | 0.497006E+09 | 0.726222E+09 |
Annual Sum or Average | 0.676914E+10 | 0.348662E+10 | 0.328251E+10 | 0.726971E+10 | 0.423632E+10 |
Minimum of Months | 0.436855E+09 | 87240873.66 | 0.133581E+09 | 0.449851E+09 | 69402422.19 |
Maximum of Months | 0.690706E+09 | 0.461450E+09 | 0.359242E+09 | 0.784130E+09 | 0.786279E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515248E+09 | 0.00 | 0.515248E+09 | 15439.82 | 0.487852E+10 |
February | 0.590017E+09 | 0.00 | 0.590017E+09 | 9181205.19 | 0.353166E+10 |
March | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.214248E+09 | 0.266387E+10 |
April | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.539476E+09 | 0.172268E+10 |
May | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.123939E+10 | 0.903674E+09 |
June | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.190803E+10 | 0.548895E+09 |
July | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.195087E+10 | 0.455181E+09 |
August | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.160368E+10 | 0.569343E+09 |
September | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.915426E+09 | 0.107227E+10 |
October | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.274848E+09 | 0.192754E+10 |
November | 0.521973E+09 | 0.00 | 0.521973E+09 | 52173341.19 | 0.299285E+10 |
December | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.442877E+10 |
Annual Sum or Average | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.870734E+10 | 0.256952E+11 |
Minimum of Months | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.455181E+09 |
Maximum of Months | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.195087E+10 | 0.487852E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.497259E+10 |
February | 0.590017E+09 | 0.00 | 0.590017E+09 | 6929363.87 | 0.360747E+10 |
March | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.195928E+09 | 0.273227E+10 |
April | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.517829E+09 | 0.176995E+10 |
May | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.120878E+10 | 0.925857E+09 |
June | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.188430E+10 | 0.564637E+09 |
July | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.192889E+10 | 0.468736E+09 |
August | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.158186E+10 | 0.585491E+09 |
September | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.894182E+09 | 0.109949E+10 |
October | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.252397E+09 | 0.197863E+10 |
November | 0.521973E+09 | 0.00 | 0.521973E+09 | 45259768.92 | 0.306964E+10 |
December | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.452735E+10 |
Annual Sum or Average | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.851636E+10 | 0.263021E+11 |
Minimum of Months | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.468736E+09 |
Maximum of Months | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.192889E+10 | 0.497259E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 292951.76 | 0.630395E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 4197709.02 | 0.447384E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 49227250.86 | 0.337130E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 0.110900E+09 | 0.214370E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.242396E+09 | 0.118786E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.344954E+09 | 73626713.05 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.356763E+09 | 60836005.00 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.302180E+09 | 74114723.91 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.182693E+09 | 0.132461E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 68002630.00 | 0.235685E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 17692654.07 | 0.373156E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 86349.52 | 0.569928E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.167938E+10 | 0.326787E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 86349.52 | 60836005.00 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.356763E+09 | 0.630395E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.587339E+09 | 0.240693E+09 | 0.346645E+09 | 0.252165E+09 | 0.215442E+10 |
February | 0.706392E+09 | 0.310906E+09 | 0.395485E+09 | 0.408110E+09 | 0.150314E+10 |
March | 0.106219E+10 | 0.421431E+09 | 0.640764E+09 | 0.837854E+09 | 0.115894E+10 |
April | 0.125460E+10 | 0.546798E+09 | 0.707799E+09 | 0.130375E+10 | 0.777221E+09 |
May | 0.163805E+10 | 0.716437E+09 | 0.921616E+09 | 0.205648E+10 | 0.441220E+09 |
June | 0.174209E+10 | 0.758910E+09 | 0.983183E+09 | 0.243877E+10 | 0.276061E+09 |
July | 0.181994E+10 | 0.840105E+09 | 0.979833E+09 | 0.262468E+10 | 0.227740E+09 |
August | 0.153434E+10 | 0.661242E+09 | 0.873100E+09 | 0.223223E+10 | 0.276795E+09 |
September | 0.133028E+10 | 0.630927E+09 | 0.699358E+09 | 0.176984E+10 | 0.481248E+09 |
October | 0.870498E+09 | 0.362331E+09 | 0.508168E+09 | 0.852601E+09 | 0.832216E+09 |
November | 0.498298E+09 | 0.161723E+09 | 0.336575E+09 | 0.283882E+09 | 0.130531E+10 |
December | 0.397368E+09 | 0.170136E+09 | 0.227232E+09 | 0.169292E+09 | 0.198547E+10 |
Annual Sum or Average | 0.134414E+11 | 0.582164E+10 | 0.761976E+10 | 0.152296E+11 | 0.114198E+11 |
Minimum of Months | 0.397368E+09 | 0.161723E+09 | 0.227232E+09 | 0.169292E+09 | 0.227740E+09 |
Maximum of Months | 0.181994E+10 | 0.840105E+09 | 0.983183E+09 | 0.262468E+10 | 0.215442E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.408579E+09 | 0.518291E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.421751E+09 | 0.369151E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.419388E+09 | 0.308755E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.420468E+09 | 0.214006E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.424968E+09 | 0.125497E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.448007E+09 | 77410335.58 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.513501E+09 | 62916370.41 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.559249E+09 | 76521778.99 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.585904E+09 | 0.130984E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.550049E+09 | 0.222804E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.330246E+09 | 0.327982E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.358540E+09 | 0.489691E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.544065E+10 | 0.292401E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.330246E+09 | 62916370.41 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.585904E+09 | 0.518291E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93221893.58 | 0.00 | 93221893.58 | 31633.10 | 0.854537E+09 |
February | 0.106750E+09 | 0.00 | 0.106750E+09 | 2444507.34 | 0.605757E+09 |
March | 0.177150E+09 | 1573.11 | 0.177149E+09 | 46317517.95 | 0.439725E+09 |
April | 0.198693E+09 | 1606993.56 | 0.197086E+09 | 0.106561E+09 | 0.278311E+09 |
May | 0.266953E+09 | 10113064.41 | 0.256839E+09 | 0.239970E+09 | 0.148180E+09 |
June | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.351609E+09 | 93015092.23 |
July | 0.293012E+09 | 20211680.59 | 0.272800E+09 | 0.355675E+09 | 80364985.00 |
August | 0.245510E+09 | 4971556.29 | 0.240538E+09 | 0.293799E+09 | 99331042.23 |
September | 0.181815E+09 | 166503.77 | 0.181648E+09 | 0.171255E+09 | 0.178396E+09 |
October | 0.139507E+09 | 0.00 | 0.139507E+09 | 59001160.52 | 0.310561E+09 |
November | 94438760.59 | 0.00 | 94438760.59 | 12473806.09 | 0.500931E+09 |
December | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 0.762542E+09 |
Annual Sum or Average | 0.216267E+10 | 65090687.00 | 0.209758E+10 | 0.163914E+10 | 0.435165E+10 |
Minimum of Months | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 80364985.00 |
Maximum of Months | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.355675E+09 | 0.854537E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83405981.40 | 0.00 | 83405981.40 | 28302.25 | 0.764519E+09 |
February | 95509395.51 | 0.00 | 95509395.51 | 2187109.98 | 0.541973E+09 |
March | 0.158497E+09 | 1407.47 | 0.158496E+09 | 41440458.81 | 0.393423E+09 |
April | 0.177772E+09 | 1437783.23 | 0.176334E+09 | 95340146.35 | 0.249005E+09 |
May | 0.238843E+09 | 9048197.05 | 0.229795E+09 | 0.214702E+09 | 0.132577E+09 |
June | 0.270483E+09 | 25068987.53 | 0.245414E+09 | 0.314586E+09 | 83220955.45 |
July | 0.262159E+09 | 18083467.21 | 0.244076E+09 | 0.318224E+09 | 71902856.58 |
August | 0.219658E+09 | 4448070.25 | 0.215210E+09 | 0.262863E+09 | 88871859.85 |
September | 0.162671E+09 | 148971.55 | 0.162522E+09 | 0.153222E+09 | 0.159612E+09 |
October | 0.124818E+09 | 0.00 | 0.124818E+09 | 52788561.87 | 0.277860E+09 |
November | 84494716.93 | 0.00 | 84494716.93 | 11160361.57 | 0.448174E+09 |
December | 56635346.41 | 0.00 | 56635346.41 | 0.00 | 0.682209E+09 |
Annual Sum or Average | 0.193495E+10 | 58236884.29 | 0.187671E+10 | 0.146654E+10 | 0.389335E+10 |
Minimum of Months | 56635346.41 | 0.00 | 56635346.41 | 0.00 | 71902856.58 |
Maximum of Months | 0.270483E+09 | 25068987.53 | 0.245414E+09 | 0.318224E+09 | 0.764519E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171445E+10 | 0.117464E+10 | 0.539803E+09 | 0.145654E+10 | 0.203919E+10 |
February | 0.166932E+10 | 0.113255E+10 | 0.536772E+09 | 0.150094E+10 | 0.144290E+10 |
March | 0.158315E+10 | 0.828739E+09 | 0.754413E+09 | 0.147764E+10 | 0.117204E+10 |
April | 0.136587E+10 | 0.625970E+09 | 0.739905E+09 | 0.145133E+10 | 0.818273E+09 |
May | 0.120373E+10 | 0.336729E+09 | 0.867005E+09 | 0.138786E+10 | 0.472906E+09 |
June | 0.111204E+10 | 0.222076E+09 | 0.889960E+09 | 0.142474E+10 | 0.295135E+09 |
July | 0.121945E+10 | 0.304977E+09 | 0.914471E+09 | 0.163451E+10 | 0.251401E+09 |
August | 0.135132E+10 | 0.467962E+09 | 0.883354E+09 | 0.182575E+10 | 0.308562E+09 |
September | 0.157891E+10 | 0.814737E+09 | 0.764174E+09 | 0.199124E+10 | 0.517665E+09 |
October | 0.175823E+10 | 0.110849E+10 | 0.649742E+09 | 0.192735E+10 | 0.843642E+09 |
November | 0.127351E+10 | 0.797332E+09 | 0.476178E+09 | 0.115901E+10 | 0.127197E+10 |
December | 0.140123E+10 | 0.106119E+10 | 0.340037E+09 | 0.128475E+10 | 0.191008E+10 |
Annual Sum or Average | 0.172312E+11 | 0.887539E+10 | 0.835581E+10 | 0.185217E+11 | 0.113438E+11 |
Minimum of Months | 0.111204E+10 | 0.222076E+09 | 0.340037E+09 | 0.115901E+10 | 0.251401E+09 |
Maximum of Months | 0.175823E+10 | 0.117464E+10 | 0.914471E+09 | 0.199124E+10 | 0.203919E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 756.32 | 940.32 | 867.18 | 594.15 | 273.04 | 0.00 | 0.00 |
February | 855.58 | 741.86 | 934.82 | 634.23 | 300.59 | 0.00 | 0.00 |
March | 760.69 | 544.27 | 800.77 | 419.18 | 381.59 | 0.00 | 0.00 |
April | 763.08 | 392.57 | 713.90 | 327.18 | 386.72 | 0.00 | 0.00 |
May | 715.30 | 213.99 | 608.86 | 170.32 | 438.54 | 0.00 | 0.00 |
June | 754.61 | 136.53 | 581.22 | 116.07 | 465.15 | 0.00 | 0.00 |
July | 834.14 | 114.56 | 616.80 | 154.26 | 462.54 | 0.00 | 0.00 |
August | 928.82 | 141.40 | 683.50 | 236.70 | 446.81 | 0.00 | 0.00 |
September | 1040.25 | 253.05 | 825.25 | 425.84 | 399.41 | 0.00 | 0.00 |
October | 975.29 | 402.92 | 889.33 | 560.68 | 328.64 | 0.00 | 0.00 |
November | 616.12 | 607.34 | 665.62 | 416.74 | 248.88 | 0.00 | 0.00 |
December | 657.66 | 885.01 | 708.75 | 536.76 | 171.99 | 0.00 | 0.00 |
Annual Sum or Average | 804.53 | 446.50 | 740.24 | 381.28 | 358.96 | 0.00 | 0.00 |
Minimum of Months | 616.12 | 114.56 | 581.22 | 116.07 | 171.99 | 0.00 | 0.00 |
Maximum of Months | 1040.25 | 940.32 | 934.82 | 634.23 | 465.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2112.49 | 2672.72 | 2441.93 | 1673.08 | 768.85 | 0.00 | 0.00 |
February | 2388.17 | 2134.50 | 2632.40 | 1785.95 | 846.45 | 0.00 | 0.00 |
March | 2113.92 | 1586.05 | 2254.92 | 1180.40 | 1074.52 | 0.00 | 0.00 |
April | 2122.35 | 1169.82 | 2010.29 | 921.31 | 1088.99 | 0.00 | 0.00 |
May | 1969.78 | 671.14 | 1714.50 | 479.61 | 1234.89 | 0.00 | 0.00 |
June | 2089.01 | 432.24 | 1636.69 | 326.85 | 1309.83 | 0.00 | 0.00 |
July | 2316.84 | 360.18 | 1736.88 | 434.39 | 1302.49 | 0.00 | 0.00 |
August | 2585.07 | 444.14 | 1924.70 | 666.53 | 1258.17 | 0.00 | 0.00 |
September | 2898.78 | 773.33 | 2323.84 | 1199.13 | 1124.71 | 0.00 | 0.00 |
October | 2713.98 | 1211.27 | 2504.29 | 1578.85 | 925.44 | 0.00 | 0.00 |
November | 1712.55 | 1761.74 | 1874.36 | 1173.52 | 700.84 | 0.00 | 0.00 |
December | 1835.20 | 2521.97 | 1995.80 | 1511.48 | 484.32 | 0.00 | 0.00 |
Annual Sum or Average | 2237.30 | 1307.87 | 2084.46 | 1073.66 | 1010.80 | 0.00 | 0.00 |
Minimum of Months | 1712.55 | 360.18 | 1636.69 | 326.85 | 484.32 | 0.00 | 0.00 |
Maximum of Months | 2898.78 | 2672.72 | 2632.40 | 1785.95 | 1309.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2781.49 | 3610.97 | 3172.21 | 2173.42 | 998.78 | 0.00 | 0.00 |
February | 3157.06 | 2874.79 | 3419.64 | 2320.05 | 1099.59 | 0.00 | 0.00 |
March | 2793.08 | 2157.78 | 2929.27 | 1533.40 | 1395.87 | 0.00 | 0.00 |
April | 2809.98 | 1596.72 | 2611.48 | 1196.83 | 1414.65 | 0.00 | 0.00 |
May | 2600.53 | 917.75 | 2227.23 | 623.04 | 1604.19 | 0.00 | 0.00 |
June | 2765.35 | 587.63 | 2126.15 | 424.60 | 1701.55 | 0.00 | 0.00 |
July | 3069.96 | 482.29 | 2256.31 | 564.29 | 1692.01 | 0.00 | 0.00 |
August | 3422.99 | 591.88 | 2500.30 | 865.86 | 1634.44 | 0.00 | 0.00 |
September | 3827.13 | 1046.97 | 3018.80 | 1557.74 | 1461.06 | 0.00 | 0.00 |
October | 3577.38 | 1646.22 | 3253.21 | 2051.01 | 1202.20 | 0.00 | 0.00 |
November | 2248.56 | 2407.90 | 2434.89 | 1524.47 | 910.43 | 0.00 | 0.00 |
December | 2419.75 | 3418.89 | 2592.66 | 1963.50 | 629.16 | 0.00 | 0.00 |
Annual Sum or Average | 2954.93 | 1773.34 | 2707.83 | 1394.74 | 1313.08 | 0.00 | 0.00 |
Minimum of Months | 2248.56 | 482.29 | 2126.15 | 424.60 | 629.16 | 0.00 | 0.00 |
Maximum of Months | 3827.13 | 3610.97 | 3419.64 | 2320.05 | 1701.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.49 | 573.38 | 281.02 | 162.03 | 118.99 | 0.00 | 0.00 |
February | 239.58 | 457.34 | 344.74 | 204.13 | 140.61 | 0.00 | 0.00 |
March | 280.50 | 317.51 | 349.16 | 153.86 | 195.30 | 0.00 | 0.00 |
April | 429.76 | 220.63 | 420.22 | 202.79 | 217.43 | 0.00 | 0.00 |
May | 456.73 | 118.59 | 400.02 | 145.64 | 254.38 | 0.00 | 0.00 |
June | 568.17 | 69.83 | 442.05 | 164.40 | 277.65 | 0.00 | 0.00 |
July | 629.82 | 54.66 | 473.32 | 197.20 | 276.12 | 0.00 | 0.00 |
August | 588.64 | 69.10 | 441.92 | 187.18 | 254.74 | 0.00 | 0.00 |
September | 503.58 | 134.85 | 412.10 | 202.15 | 209.95 | 0.00 | 0.00 |
October | 348.84 | 232.12 | 350.34 | 188.81 | 161.52 | 0.00 | 0.00 |
November | 171.37 | 363.27 | 235.72 | 121.05 | 114.66 | 0.00 | 0.00 |
December | 149.44 | 529.22 | 220.27 | 144.05 | 76.22 | 0.00 | 0.00 |
Annual Sum or Average | 378.01 | 260.81 | 364.25 | 172.52 | 191.74 | 0.00 | 0.00 |
Minimum of Months | 149.44 | 54.66 | 220.27 | 121.05 | 76.22 | 0.00 | 0.00 |
Maximum of Months | 629.82 | 573.38 | 473.32 | 204.13 | 277.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.26 | 633.91 | 137.05 | 44.55 | 92.49 | 0.00 | 0.00 |
February | 89.62 | 499.26 | 194.75 | 78.73 | 116.02 | 0.00 | 0.00 |
March | 152.40 | 326.85 | 243.06 | 70.98 | 172.08 | 0.00 | 0.00 |
April | 315.50 | 220.70 | 339.60 | 138.59 | 201.01 | 0.00 | 0.00 |
May | 385.64 | 117.57 | 358.34 | 114.94 | 243.39 | 0.00 | 0.00 |
June | 520.69 | 71.73 | 419.23 | 149.99 | 269.24 | 0.00 | 0.00 |
July | 563.46 | 59.93 | 437.75 | 172.65 | 265.09 | 0.00 | 0.00 |
August | 487.85 | 74.36 | 379.16 | 141.85 | 237.31 | 0.00 | 0.00 |
September | 351.14 | 138.40 | 304.32 | 118.01 | 186.31 | 0.00 | 0.00 |
October | 181.05 | 236.89 | 215.63 | 77.96 | 137.67 | 0.00 | 0.00 |
November | 63.95 | 385.42 | 132.88 | 38.66 | 94.23 | 0.00 | 0.00 |
December | 34.79 | 568.39 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Annual Sum or Average | 266.12 | 276.77 | 272.05 | 98.76 | 173.29 | 0.00 | 0.00 |
Minimum of Months | 34.79 | 59.93 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Maximum of Months | 563.46 | 633.91 | 437.75 | 172.65 | 269.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.48 | 137.96 | 137.14 | 93.96 | 43.18 | 0.00 | 0.00 |
February | 134.53 | 121.57 | 147.84 | 100.30 | 47.54 | 0.00 | 0.00 |
March | 116.52 | 93.15 | 126.64 | 66.29 | 60.35 | 0.00 | 0.00 |
April | 113.14 | 82.32 | 112.90 | 51.74 | 61.16 | 0.00 | 0.00 |
May | 99.68 | 52.07 | 96.29 | 26.93 | 69.35 | 0.00 | 0.00 |
June | 107.42 | 35.25 | 91.92 | 18.36 | 73.56 | 0.00 | 0.00 |
July | 120.78 | 29.56 | 97.54 | 24.40 | 73.15 | 0.00 | 0.00 |
August | 136.28 | 35.53 | 108.09 | 37.43 | 70.66 | 0.00 | 0.00 |
September | 154.97 | 57.90 | 130.51 | 67.34 | 63.16 | 0.00 | 0.00 |
October | 143.20 | 87.20 | 140.64 | 88.67 | 51.97 | 0.00 | 0.00 |
November | 92.43 | 109.44 | 105.26 | 65.90 | 39.36 | 0.00 | 0.00 |
December | 106.07 | 130.10 | 112.08 | 84.88 | 27.20 | 0.00 | 0.00 |
Annual Sum or Average | 120.55 | 80.78 | 117.06 | 60.30 | 56.77 | 0.00 | 0.00 |
Minimum of Months | 92.43 | 29.56 | 91.92 | 18.36 | 27.20 | 0.00 | 0.00 |
Maximum of Months | 154.97 | 137.96 | 147.84 | 100.30 | 73.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.04 | 194.88 | 21.99 | 0.00 | 21.99 | 0.00 | 0.00 |
February | 1.04 | 155.55 | 27.88 | 0.00 | 27.88 | 0.00 | 0.00 |
March | 12.33 | 99.36 | 41.79 | 0.00 | 41.79 | 0.00 | 0.00 |
April | 28.28 | 64.08 | 48.43 | 0.39 | 48.04 | 0.00 | 0.00 |
May | 60.00 | 31.49 | 62.97 | 2.39 | 60.58 | 0.00 | 0.00 |
June | 91.10 | 18.61 | 73.69 | 6.83 | 66.86 | 0.00 | 0.00 |
July | 89.85 | 14.67 | 69.12 | 4.77 | 64.35 | 0.00 | 0.00 |
August | 74.87 | 18.72 | 57.91 | 1.17 | 56.74 | 0.00 | 0.00 |
September | 45.56 | 38.58 | 44.32 | 0.04 | 44.28 | 0.00 | 0.00 |
October | 15.65 | 69.89 | 32.91 | 0.00 | 32.91 | 0.00 | 0.00 |
November | 3.55 | 117.01 | 23.02 | 0.00 | 23.02 | 0.00 | 0.00 |
December | 0.00 | 172.22 | 14.93 | 0.00 | 14.93 | 0.00 | 0.00 |
Annual Sum or Average | 35.39 | 82.58 | 43.33 | 1.30 | 42.02 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.67 | 14.93 | 0.00 | 14.93 | 0.00 | 0.00 |
Maximum of Months | 91.10 | 194.88 | 73.69 | 6.83 | 66.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.13 | 570.27 | 281.11 | 162.41 | 118.70 | 0.00 | 0.00 |
February | 219.20 | 450.28 | 330.84 | 189.66 | 141.18 | 0.00 | 0.00 |
March | 286.58 | 312.86 | 356.63 | 161.56 | 195.07 | 0.00 | 0.00 |
April | 376.46 | 216.15 | 383.18 | 170.17 | 213.01 | 0.00 | 0.00 |
May | 483.35 | 112.35 | 426.19 | 167.43 | 258.77 | 0.00 | 0.00 |
June | 576.70 | 66.11 | 450.99 | 169.35 | 281.64 | 0.00 | 0.00 |
July | 609.69 | 51.15 | 461.72 | 187.34 | 274.38 | 0.00 | 0.00 |
August | 557.22 | 64.75 | 421.59 | 170.25 | 251.34 | 0.00 | 0.00 |
September | 510.96 | 131.94 | 419.80 | 205.91 | 213.89 | 0.00 | 0.00 |
October | 329.40 | 227.90 | 338.35 | 178.50 | 159.85 | 0.00 | 0.00 |
November | 158.61 | 359.06 | 227.73 | 113.60 | 114.14 | 0.00 | 0.00 |
December | 138.93 | 523.62 | 214.32 | 137.89 | 76.43 | 0.00 | 0.00 |
Annual Sum or Average | 368.24 | 256.32 | 359.49 | 167.69 | 191.79 | 0.00 | 0.00 |
Minimum of Months | 138.93 | 51.15 | 214.32 | 113.60 | 76.43 | 0.00 | 0.00 |
Maximum of Months | 609.69 | 570.27 | 461.72 | 205.91 | 281.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.15 | 622.89 | 137.13 | 44.94 | 92.20 | 0.00 | 0.00 |
February | 66.50 | 489.31 | 180.85 | 64.26 | 116.59 | 0.00 | 0.00 |
March | 155.50 | 319.03 | 250.53 | 78.68 | 171.85 | 0.00 | 0.00 |
April | 262.20 | 215.30 | 302.56 | 105.97 | 196.58 | 0.00 | 0.00 |
May | 415.44 | 112.53 | 384.51 | 136.73 | 247.78 | 0.00 | 0.00 |
June | 531.04 | 68.92 | 428.17 | 154.94 | 273.23 | 0.00 | 0.00 |
July | 543.33 | 56.19 | 426.15 | 162.80 | 263.35 | 0.00 | 0.00 |
August | 457.49 | 69.53 | 358.83 | 124.91 | 233.91 | 0.00 | 0.00 |
September | 357.58 | 134.03 | 312.02 | 121.77 | 190.25 | 0.00 | 0.00 |
October | 158.78 | 228.89 | 203.64 | 67.64 | 136.00 | 0.00 | 0.00 |
November | 47.51 | 377.49 | 124.90 | 31.20 | 93.70 | 0.00 | 0.00 |
December | 21.51 | 560.58 | 92.85 | 31.76 | 61.08 | 0.00 | 0.00 |
Annual Sum or Average | 254.87 | 270.22 | 267.28 | 93.94 | 173.34 | 0.00 | 0.00 |
Minimum of Months | 21.51 | 56.19 | 92.85 | 31.20 | 61.08 | 0.00 | 0.00 |
Maximum of Months | 543.33 | 622.89 | 428.17 | 162.80 | 273.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.42 | 725.54 | 344.78 | 203.58 | 141.19 | 0.00 | 0.00 |
February | 246.52 | 572.87 | 380.71 | 217.32 | 163.39 | 0.00 | 0.00 |
March | 275.64 | 409.26 | 364.91 | 143.63 | 221.27 | 0.00 | 0.00 |
April | 324.13 | 285.48 | 349.53 | 112.96 | 236.58 | 0.00 | 0.00 |
May | 373.51 | 150.57 | 345.04 | 63.53 | 281.51 | 0.00 | 0.00 |
June | 452.43 | 94.84 | 358.79 | 54.57 | 304.22 | 0.00 | 0.00 |
July | 476.64 | 79.32 | 361.08 | 63.19 | 297.89 | 0.00 | 0.00 |
August | 477.95 | 99.05 | 359.66 | 83.65 | 276.01 | 0.00 | 0.00 |
September | 454.93 | 183.89 | 378.78 | 146.00 | 232.77 | 0.00 | 0.00 |
October | 365.87 | 292.05 | 376.02 | 192.12 | 183.90 | 0.00 | 0.00 |
November | 195.48 | 461.42 | 277.94 | 142.80 | 135.15 | 0.00 | 0.00 |
December | 184.54 | 670.87 | 275.20 | 183.92 | 91.28 | 0.00 | 0.00 |
Annual Sum or Average | 335.83 | 334.34 | 347.50 | 133.47 | 214.03 | 0.00 | 0.00 |
Minimum of Months | 184.54 | 79.32 | 275.20 | 54.57 | 91.28 | 0.00 | 0.00 |
Maximum of Months | 477.95 | 725.54 | 380.71 | 217.32 | 304.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.22 | 574.67 | 281.02 | 162.03 | 118.99 | 0.00 | 0.00 |
February | 237.62 | 458.35 | 344.74 | 204.13 | 140.61 | 0.00 | 0.00 |
March | 279.19 | 317.20 | 349.16 | 153.86 | 195.30 | 0.00 | 0.00 |
April | 426.85 | 219.73 | 420.22 | 202.79 | 217.43 | 0.00 | 0.00 |
May | 453.13 | 117.89 | 400.02 | 145.64 | 254.38 | 0.00 | 0.00 |
June | 564.83 | 68.71 | 442.05 | 164.40 | 277.65 | 0.00 | 0.00 |
July | 626.28 | 53.45 | 473.32 | 197.20 | 276.12 | 0.00 | 0.00 |
August | 585.22 | 68.01 | 441.92 | 187.18 | 254.74 | 0.00 | 0.00 |
September | 501.54 | 133.02 | 412.10 | 202.15 | 209.95 | 0.00 | 0.00 |
October | 347.40 | 230.97 | 350.34 | 188.81 | 161.52 | 0.00 | 0.00 |
November | 171.13 | 362.51 | 235.72 | 121.05 | 114.66 | 0.00 | 0.00 |
December | 149.28 | 529.68 | 220.27 | 144.05 | 76.22 | 0.00 | 0.00 |
Annual Sum or Average | 375.91 | 260.28 | 364.25 | 172.52 | 191.74 | 0.00 | 0.00 |
Minimum of Months | 149.28 | 53.45 | 220.27 | 121.05 | 76.22 | 0.00 | 0.00 |
Maximum of Months | 626.28 | 574.67 | 473.32 | 204.13 | 277.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.89 | 635.80 | 137.05 | 44.55 | 92.49 | 0.00 | 0.00 |
February | 88.91 | 500.79 | 194.75 | 78.73 | 116.02 | 0.00 | 0.00 |
March | 151.93 | 326.56 | 243.06 | 70.98 | 172.08 | 0.00 | 0.00 |
April | 313.37 | 220.09 | 339.60 | 138.59 | 201.01 | 0.00 | 0.00 |
May | 381.68 | 117.86 | 358.34 | 114.94 | 243.39 | 0.00 | 0.00 |
June | 516.71 | 71.97 | 419.23 | 149.99 | 269.24 | 0.00 | 0.00 |
July | 559.63 | 60.36 | 437.75 | 172.65 | 265.09 | 0.00 | 0.00 |
August | 484.55 | 74.92 | 379.16 | 141.85 | 237.31 | 0.00 | 0.00 |
September | 349.94 | 137.16 | 304.32 | 118.01 | 186.31 | 0.00 | 0.00 |
October | 181.06 | 235.21 | 215.63 | 77.96 | 137.67 | 0.00 | 0.00 |
November | 64.33 | 384.46 | 132.88 | 38.66 | 94.23 | 0.00 | 0.00 |
December | 34.81 | 569.28 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Annual Sum or Average | 264.48 | 276.86 | 272.05 | 98.76 | 173.29 | 0.00 | 0.00 |
Minimum of Months | 34.81 | 60.36 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Maximum of Months | 559.63 | 635.80 | 437.75 | 172.65 | 269.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.09 | 293.56 | 251.46 | 172.29 | 79.17 | 0.00 | 0.00 |
February | 237.01 | 235.92 | 271.07 | 183.91 | 87.16 | 0.00 | 0.00 |
March | 213.68 | 167.10 | 232.20 | 121.55 | 110.65 | 0.00 | 0.00 |
April | 218.52 | 117.15 | 207.01 | 94.87 | 112.14 | 0.00 | 0.00 |
May | 204.57 | 61.62 | 176.55 | 49.39 | 127.16 | 0.00 | 0.00 |
June | 222.45 | 34.64 | 168.54 | 33.66 | 134.88 | 0.00 | 0.00 |
July | 247.32 | 25.91 | 178.86 | 44.73 | 134.13 | 0.00 | 0.00 |
August | 273.16 | 33.89 | 198.20 | 68.64 | 129.56 | 0.00 | 0.00 |
September | 302.52 | 69.29 | 239.30 | 123.48 | 115.82 | 0.00 | 0.00 |
October | 278.29 | 120.59 | 257.88 | 162.58 | 95.30 | 0.00 | 0.00 |
November | 173.55 | 186.83 | 193.01 | 120.84 | 72.17 | 0.00 | 0.00 |
December | 185.56 | 271.14 | 205.52 | 155.65 | 49.87 | 0.00 | 0.00 |
Annual Sum or Average | 230.52 | 134.33 | 214.65 | 110.56 | 104.09 | 0.00 | 0.00 |
Minimum of Months | 173.55 | 25.91 | 168.54 | 33.66 | 49.87 | 0.00 | 0.00 |
Maximum of Months | 302.52 | 293.56 | 271.07 | 183.91 | 134.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.01 | 1821.43 | 192.37 | 0.00 | 192.37 | 0.00 | 0.00 |
February | 3.80 | 1459.84 | 243.89 | 0.00 | 243.89 | 0.00 | 0.00 |
March | 79.99 | 994.57 | 365.57 | 0.00 | 365.56 | 0.00 | 0.00 |
April | 208.13 | 664.61 | 423.69 | 3.43 | 420.26 | 0.00 | 0.00 |
May | 462.74 | 337.39 | 550.88 | 20.87 | 530.01 | 0.00 | 0.00 |
June | 736.12 | 211.76 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
July | 728.37 | 169.95 | 604.66 | 41.71 | 562.95 | 0.00 | 0.00 |
August | 598.75 | 212.57 | 506.63 | 10.26 | 496.37 | 0.00 | 0.00 |
September | 353.17 | 413.68 | 387.70 | 0.36 | 387.34 | 0.00 | 0.00 |
October | 102.62 | 719.66 | 287.89 | 0.00 | 287.89 | 0.00 | 0.00 |
November | 20.13 | 1154.65 | 201.38 | 0.00 | 201.38 | 0.00 | 0.00 |
December | 0.00 | 1653.51 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Annual Sum or Average | 276.11 | 814.79 | 379.04 | 11.41 | 367.63 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 169.95 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Maximum of Months | 736.12 | 1821.43 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1856.55 | 192.37 | 0.00 | 192.37 | 0.00 | 0.00 |
February | 2.86 | 1491.18 | 243.89 | 0.00 | 243.89 | 0.00 | 0.00 |
March | 73.15 | 1020.11 | 365.57 | 0.00 | 365.56 | 0.00 | 0.00 |
April | 199.78 | 682.85 | 423.69 | 3.43 | 420.26 | 0.00 | 0.00 |
May | 451.31 | 345.68 | 550.88 | 20.87 | 530.01 | 0.00 | 0.00 |
June | 726.97 | 217.84 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
July | 720.17 | 175.01 | 604.66 | 41.71 | 562.95 | 0.00 | 0.00 |
August | 590.60 | 218.60 | 506.63 | 10.26 | 496.37 | 0.00 | 0.00 |
September | 344.98 | 424.19 | 387.70 | 0.36 | 387.34 | 0.00 | 0.00 |
October | 94.23 | 738.74 | 287.89 | 0.00 | 287.89 | 0.00 | 0.00 |
November | 17.46 | 1184.28 | 201.38 | 0.00 | 201.38 | 0.00 | 0.00 |
December | 0.00 | 1690.32 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Annual Sum or Average | 270.05 | 834.03 | 379.04 | 11.41 | 367.63 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 175.01 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Maximum of Months | 726.97 | 1856.55 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.84 | 1162.28 | 418.23 | 207.34 | 210.89 | 0.00 | 0.00 |
February | 287.76 | 901.85 | 511.67 | 253.91 | 257.75 | 0.00 | 0.00 |
March | 471.78 | 657.84 | 607.13 | 240.22 | 366.91 | 0.00 | 0.00 |
April | 702.63 | 459.76 | 685.71 | 276.13 | 409.57 | 0.00 | 0.00 |
May | 1013.70 | 252.67 | 810.66 | 304.14 | 506.52 | 0.00 | 0.00 |
June | 1245.25 | 163.21 | 879.12 | 324.27 | 554.84 | 0.00 | 0.00 |
July | 1304.02 | 130.39 | 887.82 | 350.12 | 537.71 | 0.00 | 0.00 |
August | 1153.94 | 158.48 | 780.38 | 295.14 | 485.23 | 0.00 | 0.00 |
September | 976.92 | 284.89 | 731.78 | 327.66 | 404.12 | 0.00 | 0.00 |
October | 542.81 | 475.62 | 541.97 | 246.14 | 295.84 | 0.00 | 0.00 |
November | 216.62 | 746.96 | 352.62 | 144.79 | 207.83 | 0.00 | 0.00 |
December | 145.30 | 1085.10 | 307.15 | 169.65 | 137.51 | 0.00 | 0.00 |
Annual Sum or Average | 688.57 | 538.33 | 626.73 | 261.62 | 365.11 | 0.00 | 0.00 |
Minimum of Months | 145.30 | 130.39 | 307.15 | 144.79 | 137.51 | 0.00 | 0.00 |
Maximum of Months | 1304.02 | 1162.28 | 887.82 | 350.12 | 554.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 457.47 | 1279.47 | 706.05 | 438.56 | 267.48 | 0.00 | 0.00 |
February | 555.59 | 1004.11 | 773.64 | 468.15 | 305.49 | 0.00 | 0.00 |
March | 567.61 | 731.81 | 716.40 | 309.42 | 406.98 | 0.00 | 0.00 |
April | 635.84 | 517.15 | 672.20 | 242.68 | 429.52 | 0.00 | 0.00 |
May | 684.24 | 277.70 | 638.27 | 132.87 | 505.39 | 0.00 | 0.00 |
June | 802.08 | 177.25 | 650.01 | 106.16 | 543.85 | 0.00 | 0.00 |
July | 859.07 | 147.93 | 662.57 | 128.16 | 534.40 | 0.00 | 0.00 |
August | 888.02 | 183.99 | 678.20 | 178.23 | 499.96 | 0.00 | 0.00 |
September | 892.25 | 328.96 | 742.05 | 314.45 | 427.60 | 0.00 | 0.00 |
October | 750.85 | 524.19 | 755.14 | 413.86 | 341.27 | 0.00 | 0.00 |
November | 421.73 | 822.36 | 560.36 | 307.61 | 252.74 | 0.00 | 0.00 |
December | 419.56 | 1192.44 | 567.94 | 396.20 | 171.73 | 0.00 | 0.00 |
Annual Sum or Average | 661.77 | 597.12 | 676.33 | 285.35 | 390.98 | 0.00 | 0.00 |
Minimum of Months | 419.56 | 147.93 | 560.36 | 106.16 | 171.73 | 0.00 | 0.00 |
Maximum of Months | 892.25 | 1279.47 | 773.64 | 468.15 | 543.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202572E+10 | 0.251854E+10 | 0.232266E+10 | 0.159136E+10 | 0.731301E+09 | 0.00 | 0.00 |
February | 0.206982E+10 | 0.179470E+10 | 0.226152E+10 | 0.153433E+10 | 0.727194E+09 | 0.00 | 0.00 |
March | 0.203742E+10 | 0.145776E+10 | 0.214479E+10 | 0.112274E+10 | 0.102204E+10 | 0.00 | 0.00 |
April | 0.197790E+10 | 0.101753E+10 | 0.185043E+10 | 0.848040E+09 | 0.100239E+10 | 0.00 | 0.00 |
May | 0.191585E+10 | 0.573156E+09 | 0.163076E+10 | 0.456187E+09 | 0.117457E+10 | 0.00 | 0.00 |
June | 0.195594E+10 | 0.353884E+09 | 0.150653E+10 | 0.300860E+09 | 0.120567E+10 | 0.00 | 0.00 |
July | 0.223417E+10 | 0.306843E+09 | 0.165205E+10 | 0.413171E+09 | 0.123888E+10 | 0.00 | 0.00 |
August | 0.248775E+10 | 0.378724E+09 | 0.183070E+10 | 0.633976E+09 | 0.119672E+10 | 0.00 | 0.00 |
September | 0.269632E+10 | 0.655911E+09 | 0.213904E+10 | 0.110377E+10 | 0.103527E+10 | 0.00 | 0.00 |
October | 0.261223E+10 | 0.107919E+10 | 0.238198E+10 | 0.150174E+10 | 0.880239E+09 | 0.00 | 0.00 |
November | 0.159699E+10 | 0.157423E+10 | 0.172530E+10 | 0.108019E+10 | 0.645105E+09 | 0.00 | 0.00 |
December | 0.176149E+10 | 0.237041E+10 | 0.189833E+10 | 0.143766E+10 | 0.460667E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.253716E+11 | 0.140809E+11 | 0.233441E+11 | 0.120240E+11 | 0.113200E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159699E+10 | 0.306843E+09 | 0.150653E+10 | 0.300860E+09 | 0.460667E+09 | 0.00 | 0.00 |
Maximum of Months | 0.269632E+10 | 0.251854E+10 | 0.238198E+10 | 0.159136E+10 | 0.123888E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565810E+10 | 0.715863E+10 | 0.654047E+10 | 0.448117E+10 | 0.205930E+10 | 0.00 | 0.00 |
February | 0.577747E+10 | 0.516378E+10 | 0.636831E+10 | 0.432057E+10 | 0.204773E+10 | 0.00 | 0.00 |
March | 0.566191E+10 | 0.424808E+10 | 0.603958E+10 | 0.316157E+10 | 0.287800E+10 | 0.00 | 0.00 |
April | 0.550114E+10 | 0.303216E+10 | 0.521068E+10 | 0.238803E+10 | 0.282265E+10 | 0.00 | 0.00 |
May | 0.527587E+10 | 0.179758E+10 | 0.459212E+10 | 0.128459E+10 | 0.330752E+10 | 0.00 | 0.00 |
June | 0.541470E+10 | 0.112038E+10 | 0.424230E+10 | 0.847203E+09 | 0.339509E+10 | 0.00 | 0.00 |
July | 0.620544E+10 | 0.964712E+09 | 0.465206E+10 | 0.116346E+10 | 0.348860E+10 | 0.00 | 0.00 |
August | 0.692385E+10 | 0.118957E+10 | 0.515513E+10 | 0.178524E+10 | 0.336989E+10 | 0.00 | 0.00 |
September | 0.751364E+10 | 0.200447E+10 | 0.602340E+10 | 0.310816E+10 | 0.291524E+10 | 0.00 | 0.00 |
October | 0.726913E+10 | 0.324425E+10 | 0.670748E+10 | 0.422879E+10 | 0.247870E+10 | 0.00 | 0.00 |
November | 0.443893E+10 | 0.456644E+10 | 0.485833E+10 | 0.304176E+10 | 0.181657E+10 | 0.00 | 0.00 |
December | 0.491541E+10 | 0.675484E+10 | 0.534556E+10 | 0.404835E+10 | 0.129721E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.705556E+11 | 0.412449E+11 | 0.657354E+11 | 0.338589E+11 | 0.318765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443893E+10 | 0.964712E+09 | 0.424230E+10 | 0.847203E+09 | 0.129721E+10 | 0.00 | 0.00 |
Maximum of Months | 0.751364E+10 | 0.715863E+10 | 0.670748E+10 | 0.448117E+10 | 0.348860E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.744995E+10 | 0.967161E+10 | 0.849644E+10 | 0.582130E+10 | 0.267514E+10 | 0.00 | 0.00 |
February | 0.763756E+10 | 0.695470E+10 | 0.827279E+10 | 0.561267E+10 | 0.266012E+10 | 0.00 | 0.00 |
March | 0.748099E+10 | 0.577940E+10 | 0.784575E+10 | 0.410706E+10 | 0.373869E+10 | 0.00 | 0.00 |
April | 0.728347E+10 | 0.413871E+10 | 0.676897E+10 | 0.310218E+10 | 0.366678E+10 | 0.00 | 0.00 |
May | 0.696525E+10 | 0.245811E+10 | 0.596542E+10 | 0.166876E+10 | 0.429666E+10 | 0.00 | 0.00 |
June | 0.716778E+10 | 0.152313E+10 | 0.551098E+10 | 0.110057E+10 | 0.441042E+10 | 0.00 | 0.00 |
July | 0.822258E+10 | 0.129177E+10 | 0.604329E+10 | 0.151140E+10 | 0.453188E+10 | 0.00 | 0.00 |
August | 0.916814E+10 | 0.158528E+10 | 0.669681E+10 | 0.231912E+10 | 0.437768E+10 | 0.00 | 0.00 |
September | 0.991992E+10 | 0.271374E+10 | 0.782473E+10 | 0.403767E+10 | 0.378706E+10 | 0.00 | 0.00 |
October | 0.958167E+10 | 0.440925E+10 | 0.871340E+10 | 0.549344E+10 | 0.321997E+10 | 0.00 | 0.00 |
November | 0.582828E+10 | 0.624129E+10 | 0.631125E+10 | 0.395142E+10 | 0.235983E+10 | 0.00 | 0.00 |
December | 0.648106E+10 | 0.915716E+10 | 0.694419E+10 | 0.525904E+10 | 0.168515E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.931866E+11 | 0.559241E+11 | 0.853940E+11 | 0.439846E+11 | 0.414094E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582828E+10 | 0.129177E+10 | 0.551098E+10 | 0.110057E+10 | 0.168515E+10 | 0.00 | 0.00 |
Maximum of Months | 0.991992E+10 | 0.967161E+10 | 0.871340E+10 | 0.582130E+10 | 0.453188E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432526E+09 | 0.153575E+10 | 0.752685E+09 | 0.433971E+09 | 0.318714E+09 | 0.00 | 0.00 |
February | 0.579602E+09 | 0.110639E+10 | 0.833992E+09 | 0.493819E+09 | 0.340173E+09 | 0.00 | 0.00 |
March | 0.751295E+09 | 0.850431E+09 | 0.935195E+09 | 0.412091E+09 | 0.523104E+09 | 0.00 | 0.00 |
April | 0.111393E+10 | 0.571865E+09 | 0.108922E+10 | 0.525632E+09 | 0.563590E+09 | 0.00 | 0.00 |
May | 0.122330E+10 | 0.317632E+09 | 0.107141E+10 | 0.390073E+09 | 0.681337E+09 | 0.00 | 0.00 |
June | 0.147270E+10 | 0.181009E+09 | 0.114579E+10 | 0.426126E+09 | 0.719668E+09 | 0.00 | 0.00 |
July | 0.168692E+10 | 0.146402E+09 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
August | 0.157663E+10 | 0.185086E+09 | 0.118365E+10 | 0.501344E+09 | 0.682304E+09 | 0.00 | 0.00 |
September | 0.130527E+10 | 0.349519E+09 | 0.106816E+10 | 0.523980E+09 | 0.544180E+09 | 0.00 | 0.00 |
October | 0.934327E+09 | 0.621724E+09 | 0.938338E+09 | 0.505720E+09 | 0.432618E+09 | 0.00 | 0.00 |
November | 0.444193E+09 | 0.941607E+09 | 0.610984E+09 | 0.313774E+09 | 0.297210E+09 | 0.00 | 0.00 |
December | 0.400259E+09 | 0.141746E+10 | 0.589980E+09 | 0.385823E+09 | 0.204157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119210E+11 | 0.822487E+10 | 0.114871E+11 | 0.544052E+10 | 0.604662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.400259E+09 | 0.146402E+09 | 0.589980E+09 | 0.313774E+09 | 0.204157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168692E+10 | 0.153575E+10 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 97127023.35 | 0.169785E+10 | 0.367064E+09 | 0.119331E+09 | 0.247732E+09 | 0.00 | 0.00 |
February | 0.216819E+09 | 0.120781E+10 | 0.471140E+09 | 0.190456E+09 | 0.280685E+09 | 0.00 | 0.00 |
March | 0.408193E+09 | 0.875437E+09 | 0.651014E+09 | 0.190107E+09 | 0.460907E+09 | 0.00 | 0.00 |
April | 0.817771E+09 | 0.572059E+09 | 0.880251E+09 | 0.359229E+09 | 0.521022E+09 | 0.00 | 0.00 |
May | 0.103290E+10 | 0.314905E+09 | 0.959768E+09 | 0.307862E+09 | 0.651906E+09 | 0.00 | 0.00 |
June | 0.134963E+10 | 0.185913E+09 | 0.108664E+10 | 0.388765E+09 | 0.697872E+09 | 0.00 | 0.00 |
July | 0.150918E+10 | 0.160529E+09 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
August | 0.130666E+10 | 0.199166E+09 | 0.101554E+10 | 0.379922E+09 | 0.635622E+09 | 0.00 | 0.00 |
September | 0.910145E+09 | 0.358740E+09 | 0.788798E+09 | 0.305877E+09 | 0.482922E+09 | 0.00 | 0.00 |
October | 0.484912E+09 | 0.634488E+09 | 0.577537E+09 | 0.208801E+09 | 0.368736E+09 | 0.00 | 0.00 |
November | 0.165752E+09 | 0.999006E+09 | 0.344432E+09 | 0.100201E+09 | 0.244232E+09 | 0.00 | 0.00 |
December | 93183571.65 | 0.152237E+10 | 0.264631E+09 | 0.101573E+09 | 0.163058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.839227E+10 | 0.872828E+10 | 0.857928E+10 | 0.311456E+10 | 0.546472E+10 | 0.00 | 0.00 |
Minimum of Months | 93183571.65 | 0.160529E+09 | 0.264631E+09 | 0.100201E+09 | 0.163058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150918E+10 | 0.169785E+10 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328058E+09 | 0.369513E+09 | 0.367312E+09 | 0.251662E+09 | 0.115650E+09 | 0.00 | 0.00 |
February | 0.325463E+09 | 0.294091E+09 | 0.357643E+09 | 0.242643E+09 | 0.115001E+09 | 0.00 | 0.00 |
March | 0.312087E+09 | 0.249484E+09 | 0.339182E+09 | 0.177553E+09 | 0.161629E+09 | 0.00 | 0.00 |
April | 0.293263E+09 | 0.213378E+09 | 0.292632E+09 | 0.134111E+09 | 0.158521E+09 | 0.00 | 0.00 |
May | 0.266975E+09 | 0.139469E+09 | 0.257894E+09 | 72142461.01 | 0.185752E+09 | 0.00 | 0.00 |
June | 0.278437E+09 | 91362570.52 | 0.238248E+09 | 47578762.80 | 0.190670E+09 | 0.00 | 0.00 |
July | 0.323505E+09 | 79166902.63 | 0.261261E+09 | 65339777.42 | 0.195921E+09 | 0.00 | 0.00 |
August | 0.365023E+09 | 95163975.06 | 0.289513E+09 | 0.100258E+09 | 0.189254E+09 | 0.00 | 0.00 |
September | 0.401680E+09 | 0.150074E+09 | 0.338274E+09 | 0.174553E+09 | 0.163721E+09 | 0.00 | 0.00 |
October | 0.383555E+09 | 0.233556E+09 | 0.376692E+09 | 0.237488E+09 | 0.139204E+09 | 0.00 | 0.00 |
November | 0.239571E+09 | 0.283666E+09 | 0.272843E+09 | 0.170824E+09 | 0.102019E+09 | 0.00 | 0.00 |
December | 0.284103E+09 | 0.348449E+09 | 0.300206E+09 | 0.227355E+09 | 72851358.19 | 0.00 | 0.00 |
Annual Sum or Average | 0.380172E+10 | 0.254737E+10 | 0.369170E+10 | 0.190151E+10 | 0.179019E+10 | 0.00 | 0.00 |
Minimum of Months | 0.239571E+09 | 79166902.63 | 0.238248E+09 | 47578762.80 | 72851358.19 | 0.00 | 0.00 |
Maximum of Months | 0.401680E+09 | 0.369513E+09 | 0.376692E+09 | 0.251662E+09 | 0.195921E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 109685.49 | 0.521956E+09 | 58895473.06 | 0.00 | 58895473.06 | 0.00 | 0.00 |
February | 2511952.67 | 0.376317E+09 | 67442057.94 | 0.00 | 67442057.94 | 0.00 | 0.00 |
March | 33025625.95 | 0.266135E+09 | 0.111920E+09 | 993.85 | 0.111919E+09 | 0.00 | 0.00 |
April | 73307678.70 | 0.166090E+09 | 0.125530E+09 | 1015262.00 | 0.124515E+09 | 0.00 | 0.00 |
May | 0.160700E+09 | 84348028.83 | 0.168655E+09 | 6389204.19 | 0.162265E+09 | 0.00 | 0.00 |
June | 0.236120E+09 | 48246758.58 | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.00 | 0.00 |
July | 0.240646E+09 | 39301422.15 | 0.185118E+09 | 12769280.31 | 0.172349E+09 | 0.00 | 0.00 |
August | 0.200530E+09 | 50129359.99 | 0.155107E+09 | 3140916.24 | 0.151966E+09 | 0.00 | 0.00 |
September | 0.118099E+09 | 99997644.38 | 0.114867E+09 | 105193.30 | 0.114761E+09 | 0.00 | 0.00 |
October | 41913134.68 | 0.187201E+09 | 88137585.25 | 0.00 | 88137585.25 | 0.00 | 0.00 |
November | 9200587.79 | 0.303295E+09 | 59664261.98 | 0.00 | 59664261.98 | 0.00 | 0.00 |
December | 10007.58 | 0.461280E+09 | 39991922.20 | 0.00 | 39991922.20 | 0.00 | 0.00 |
Annual Sum or Average | 0.111617E+10 | 0.260430E+10 | 0.136632E+10 | 41122816.28 | 0.132520E+10 | 0.00 | 0.00 |
Minimum of Months | 10007.58 | 39301422.15 | 39991922.20 | 0.00 | 39991922.20 | 0.00 | 0.00 |
Maximum of Months | 0.240646E+09 | 0.521956E+09 | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434260E+09 | 0.152742E+10 | 0.752922E+09 | 0.434995E+09 | 0.317926E+09 | 0.00 | 0.00 |
February | 0.530294E+09 | 0.108931E+10 | 0.800364E+09 | 0.458828E+09 | 0.341536E+09 | 0.00 | 0.00 |
March | 0.767566E+09 | 0.837963E+09 | 0.955197E+09 | 0.432716E+09 | 0.522482E+09 | 0.00 | 0.00 |
April | 0.975788E+09 | 0.560260E+09 | 0.993206E+09 | 0.441090E+09 | 0.552115E+09 | 0.00 | 0.00 |
May | 0.129461E+10 | 0.300909E+09 | 0.114152E+10 | 0.448440E+09 | 0.693077E+09 | 0.00 | 0.00 |
June | 0.149479E+10 | 0.171350E+09 | 0.116898E+10 | 0.438967E+09 | 0.730011E+09 | 0.00 | 0.00 |
July | 0.163298E+10 | 0.137009E+09 | 0.123667E+10 | 0.501773E+09 | 0.734901E+09 | 0.00 | 0.00 |
August | 0.149245E+10 | 0.173439E+09 | 0.112919E+10 | 0.455993E+09 | 0.673196E+09 | 0.00 | 0.00 |
September | 0.132442E+10 | 0.341998E+09 | 0.108812E+10 | 0.533721E+09 | 0.554395E+09 | 0.00 | 0.00 |
October | 0.882262E+09 | 0.610402E+09 | 0.906239E+09 | 0.478097E+09 | 0.428141E+09 | 0.00 | 0.00 |
November | 0.411116E+09 | 0.930672E+09 | 0.590289E+09 | 0.294440E+09 | 0.295848E+09 | 0.00 | 0.00 |
December | 0.372116E+09 | 0.140246E+10 | 0.574030E+09 | 0.369324E+09 | 0.204706E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116127E+11 | 0.808320E+10 | 0.113367E+11 | 0.528838E+10 | 0.604834E+10 | 0.00 | 0.00 |
Minimum of Months | 0.372116E+09 | 0.137009E+09 | 0.574030E+09 | 0.294440E+09 | 0.204706E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163298E+10 | 0.152742E+10 | 0.123667E+10 | 0.533721E+09 | 0.734901E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 78088272.99 | 0.166834E+10 | 0.367300E+09 | 0.120355E+09 | 0.246945E+09 | 0.00 | 0.00 |
February | 0.160887E+09 | 0.118374E+10 | 0.437512E+09 | 0.155464E+09 | 0.282048E+09 | 0.00 | 0.00 |
March | 0.416500E+09 | 0.854482E+09 | 0.671016E+09 | 0.210732E+09 | 0.460285E+09 | 0.00 | 0.00 |
April | 0.679618E+09 | 0.558068E+09 | 0.784234E+09 | 0.274687E+09 | 0.509547E+09 | 0.00 | 0.00 |
May | 0.111271E+10 | 0.301408E+09 | 0.102988E+10 | 0.366229E+09 | 0.663646E+09 | 0.00 | 0.00 |
June | 0.137644E+10 | 0.178636E+09 | 0.110982E+10 | 0.401606E+09 | 0.708215E+09 | 0.00 | 0.00 |
July | 0.145526E+10 | 0.150493E+09 | 0.114140E+10 | 0.436042E+09 | 0.705359E+09 | 0.00 | 0.00 |
August | 0.122535E+10 | 0.186241E+09 | 0.961084E+09 | 0.334570E+09 | 0.626514E+09 | 0.00 | 0.00 |
September | 0.926846E+09 | 0.347404E+09 | 0.808754E+09 | 0.315617E+09 | 0.493136E+09 | 0.00 | 0.00 |
October | 0.425278E+09 | 0.613052E+09 | 0.545437E+09 | 0.181178E+09 | 0.364259E+09 | 0.00 | 0.00 |
November | 0.123133E+09 | 0.978449E+09 | 0.323737E+09 | 80867192.16 | 0.242870E+09 | 0.00 | 0.00 |
December | 57606201.10 | 0.150146E+10 | 0.248681E+09 | 85074026.75 | 0.163607E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803772E+10 | 0.852177E+10 | 0.842885E+10 | 0.296242E+10 | 0.546643E+10 | 0.00 | 0.00 |
Minimum of Months | 57606201.10 | 0.150493E+09 | 0.248681E+09 | 80867192.16 | 0.163607E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145526E+10 | 0.166834E+10 | 0.114140E+10 | 0.436042E+09 | 0.708215E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526086E+09 | 0.194328E+10 | 0.923450E+09 | 0.545281E+09 | 0.378169E+09 | 0.00 | 0.00 |
February | 0.596374E+09 | 0.138588E+10 | 0.921016E+09 | 0.525739E+09 | 0.395277E+09 | 0.00 | 0.00 |
March | 0.738263E+09 | 0.109616E+10 | 0.977369E+09 | 0.384711E+09 | 0.592659E+09 | 0.00 | 0.00 |
April | 0.840133E+09 | 0.739951E+09 | 0.905992E+09 | 0.292781E+09 | 0.613211E+09 | 0.00 | 0.00 |
May | 0.100042E+10 | 0.403293E+09 | 0.924147E+09 | 0.170154E+09 | 0.753993E+09 | 0.00 | 0.00 |
June | 0.117271E+10 | 0.245830E+09 | 0.929979E+09 | 0.141438E+09 | 0.788541E+09 | 0.00 | 0.00 |
July | 0.127663E+10 | 0.212453E+09 | 0.967108E+09 | 0.169236E+09 | 0.797872E+09 | 0.00 | 0.00 |
August | 0.128015E+10 | 0.265291E+09 | 0.963308E+09 | 0.224037E+09 | 0.739271E+09 | 0.00 | 0.00 |
September | 0.117919E+10 | 0.476644E+09 | 0.981785E+09 | 0.378437E+09 | 0.603349E+09 | 0.00 | 0.00 |
October | 0.979945E+09 | 0.782221E+09 | 0.100712E+10 | 0.514570E+09 | 0.492552E+09 | 0.00 | 0.00 |
November | 0.506679E+09 | 0.119599E+10 | 0.720428E+09 | 0.370129E+09 | 0.350299E+09 | 0.00 | 0.00 |
December | 0.494263E+09 | 0.179686E+10 | 0.737099E+09 | 0.492615E+09 | 0.244485E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105908E+11 | 0.105439E+11 | 0.109588E+11 | 0.420913E+10 | 0.674968E+10 | 0.00 | 0.00 |
Minimum of Months | 0.494263E+09 | 0.212453E+09 | 0.720428E+09 | 0.141438E+09 | 0.244485E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128015E+10 | 0.194328E+10 | 0.100712E+10 | 0.545281E+09 | 0.797872E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429129E+09 | 0.153919E+10 | 0.752685E+09 | 0.433971E+09 | 0.318714E+09 | 0.00 | 0.00 |
February | 0.574859E+09 | 0.110885E+10 | 0.833992E+09 | 0.493819E+09 | 0.340173E+09 | 0.00 | 0.00 |
March | 0.747775E+09 | 0.849599E+09 | 0.935195E+09 | 0.412091E+09 | 0.523104E+09 | 0.00 | 0.00 |
April | 0.110641E+10 | 0.569537E+09 | 0.108922E+10 | 0.525632E+09 | 0.563590E+09 | 0.00 | 0.00 |
May | 0.121365E+10 | 0.315767E+09 | 0.107141E+10 | 0.390073E+09 | 0.681337E+09 | 0.00 | 0.00 |
June | 0.146404E+10 | 0.178096E+09 | 0.114579E+10 | 0.426126E+09 | 0.719668E+09 | 0.00 | 0.00 |
July | 0.167742E+10 | 0.143159E+09 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
August | 0.156746E+10 | 0.182148E+09 | 0.118365E+10 | 0.501344E+09 | 0.682304E+09 | 0.00 | 0.00 |
September | 0.129998E+10 | 0.344775E+09 | 0.106816E+10 | 0.523980E+09 | 0.544180E+09 | 0.00 | 0.00 |
October | 0.930481E+09 | 0.618639E+09 | 0.938338E+09 | 0.505720E+09 | 0.432618E+09 | 0.00 | 0.00 |
November | 0.443559E+09 | 0.939616E+09 | 0.610984E+09 | 0.313774E+09 | 0.297210E+09 | 0.00 | 0.00 |
December | 0.399833E+09 | 0.141869E+10 | 0.589980E+09 | 0.385823E+09 | 0.204157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118546E+11 | 0.820807E+10 | 0.114871E+11 | 0.544052E+10 | 0.604662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.399833E+09 | 0.143159E+09 | 0.589980E+09 | 0.313774E+09 | 0.204157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167742E+10 | 0.153919E+10 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96138312.73 | 0.170293E+10 | 0.367064E+09 | 0.119331E+09 | 0.247732E+09 | 0.00 | 0.00 |
February | 0.215094E+09 | 0.121151E+10 | 0.471140E+09 | 0.190456E+09 | 0.280685E+09 | 0.00 | 0.00 |
March | 0.406942E+09 | 0.874652E+09 | 0.651014E+09 | 0.190107E+09 | 0.460907E+09 | 0.00 | 0.00 |
April | 0.812265E+09 | 0.570475E+09 | 0.880251E+09 | 0.359229E+09 | 0.521022E+09 | 0.00 | 0.00 |
May | 0.102229E+10 | 0.315664E+09 | 0.959768E+09 | 0.307862E+09 | 0.651906E+09 | 0.00 | 0.00 |
June | 0.133930E+10 | 0.186553E+09 | 0.108664E+10 | 0.388765E+09 | 0.697872E+09 | 0.00 | 0.00 |
July | 0.149890E+10 | 0.161675E+09 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
August | 0.129782E+10 | 0.200675E+09 | 0.101554E+10 | 0.379922E+09 | 0.635622E+09 | 0.00 | 0.00 |
September | 0.907039E+09 | 0.355506E+09 | 0.788798E+09 | 0.305877E+09 | 0.482922E+09 | 0.00 | 0.00 |
October | 0.484957E+09 | 0.629994E+09 | 0.577537E+09 | 0.208801E+09 | 0.368736E+09 | 0.00 | 0.00 |
November | 0.166756E+09 | 0.996513E+09 | 0.344432E+09 | 0.100201E+09 | 0.244232E+09 | 0.00 | 0.00 |
December | 93226154.40 | 0.152476E+10 | 0.264631E+09 | 0.101573E+09 | 0.163058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.834073E+10 | 0.873091E+10 | 0.857928E+10 | 0.311456E+10 | 0.546472E+10 | 0.00 | 0.00 |
Minimum of Months | 93226154.40 | 0.161675E+09 | 0.264631E+09 | 0.100201E+09 | 0.163058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149890E+10 | 0.170293E+10 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562704E+09 | 0.786279E+09 | 0.673507E+09 | 0.461450E+09 | 0.212057E+09 | 0.00 | 0.00 |
February | 0.573385E+09 | 0.570728E+09 | 0.655778E+09 | 0.444912E+09 | 0.210867E+09 | 0.00 | 0.00 |
March | 0.572308E+09 | 0.447566E+09 | 0.621928E+09 | 0.325563E+09 | 0.296365E+09 | 0.00 | 0.00 |
April | 0.566397E+09 | 0.303664E+09 | 0.536573E+09 | 0.245907E+09 | 0.290666E+09 | 0.00 | 0.00 |
May | 0.547929E+09 | 0.165052E+09 | 0.472877E+09 | 0.132281E+09 | 0.340596E+09 | 0.00 | 0.00 |
June | 0.576579E+09 | 89795733.93 | 0.436855E+09 | 87240873.66 | 0.349614E+09 | 0.00 | 0.00 |
July | 0.662433E+09 | 69402422.19 | 0.479050E+09 | 0.119808E+09 | 0.359242E+09 | 0.00 | 0.00 |
August | 0.731627E+09 | 90770448.53 | 0.530853E+09 | 0.183835E+09 | 0.347018E+09 | 0.00 | 0.00 |
September | 0.784130E+09 | 0.179597E+09 | 0.620262E+09 | 0.320063E+09 | 0.300200E+09 | 0.00 | 0.00 |
October | 0.745359E+09 | 0.322982E+09 | 0.690706E+09 | 0.435460E+09 | 0.255246E+09 | 0.00 | 0.00 |
November | 0.449851E+09 | 0.484264E+09 | 0.500288E+09 | 0.313225E+09 | 0.187063E+09 | 0.00 | 0.00 |
December | 0.497006E+09 | 0.726222E+09 | 0.550461E+09 | 0.416880E+09 | 0.133581E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.726971E+10 | 0.423632E+10 | 0.676914E+10 | 0.348662E+10 | 0.328251E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449851E+09 | 69402422.19 | 0.436855E+09 | 87240873.66 | 0.133581E+09 | 0.00 | 0.00 |
Maximum of Months | 0.784130E+09 | 0.786279E+09 | 0.690706E+09 | 0.461450E+09 | 0.359242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15439.82 | 0.487852E+10 | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.00 |
February | 9181205.19 | 0.353166E+10 | 0.590017E+09 | 0.00 | 0.590017E+09 | 0.00 | 0.00 |
March | 0.214248E+09 | 0.266387E+10 | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.00 | 0.00 |
April | 0.539476E+09 | 0.172268E+10 | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.00 | 0.00 |
May | 0.123939E+10 | 0.903674E+09 | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.00 | 0.00 |
June | 0.190803E+10 | 0.548895E+09 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
July | 0.195087E+10 | 0.455181E+09 | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.00 | 0.00 |
August | 0.160368E+10 | 0.569343E+09 | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.00 | 0.00 |
September | 0.915426E+09 | 0.107227E+10 | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.00 | 0.00 |
October | 0.274848E+09 | 0.192754E+10 | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.00 | 0.00 |
November | 52173341.19 | 0.299285E+10 | 0.521973E+09 | 0.00 | 0.521973E+09 | 0.00 | 0.00 |
December | 0.00 | 0.442877E+10 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870734E+10 | 0.256952E+11 | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.455181E+09 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195087E+10 | 0.487852E+10 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.497259E+10 | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.00 |
February | 6929363.87 | 0.360747E+10 | 0.590017E+09 | 0.00 | 0.590017E+09 | 0.00 | 0.00 |
March | 0.195928E+09 | 0.273227E+10 | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.00 | 0.00 |
April | 0.517829E+09 | 0.176995E+10 | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.00 | 0.00 |
May | 0.120878E+10 | 0.925857E+09 | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.00 | 0.00 |
June | 0.188430E+10 | 0.564637E+09 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
July | 0.192889E+10 | 0.468736E+09 | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.00 | 0.00 |
August | 0.158186E+10 | 0.585491E+09 | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.00 | 0.00 |
September | 0.894182E+09 | 0.109949E+10 | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.00 | 0.00 |
October | 0.252397E+09 | 0.197863E+10 | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.00 | 0.00 |
November | 45259768.92 | 0.306964E+10 | 0.521973E+09 | 0.00 | 0.521973E+09 | 0.00 | 0.00 |
December | 0.00 | 0.452735E+10 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851636E+10 | 0.263021E+11 | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.468736E+09 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192889E+10 | 0.497259E+10 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470977E+09 | 0.311305E+10 | 0.112018E+10 | 0.555333E+09 | 0.564846E+09 | 0.00 | 0.00 |
February | 0.696149E+09 | 0.218176E+10 | 0.123783E+10 | 0.614270E+09 | 0.623556E+09 | 0.00 | 0.00 |
March | 0.126360E+10 | 0.176196E+10 | 0.162614E+10 | 0.643418E+09 | 0.982721E+09 | 0.00 | 0.00 |
April | 0.182122E+10 | 0.119170E+10 | 0.177735E+10 | 0.715739E+09 | 0.106161E+10 | 0.00 | 0.00 |
May | 0.271509E+10 | 0.676745E+09 | 0.217128E+10 | 0.814618E+09 | 0.135666E+10 | 0.00 | 0.00 |
June | 0.322768E+10 | 0.423045E+09 | 0.227868E+10 | 0.840520E+09 | 0.143816E+10 | 0.00 | 0.00 |
July | 0.349269E+10 | 0.349236E+09 | 0.237795E+10 | 0.937755E+09 | 0.144019E+10 | 0.00 | 0.00 |
August | 0.309071E+10 | 0.424483E+09 | 0.209016E+10 | 0.790516E+09 | 0.129965E+10 | 0.00 | 0.00 |
September | 0.253218E+10 | 0.738433E+09 | 0.189678E+10 | 0.849293E+09 | 0.104748E+10 | 0.00 | 0.00 |
October | 0.145386E+10 | 0.127391E+10 | 0.145161E+10 | 0.659250E+09 | 0.792365E+09 | 0.00 | 0.00 |
November | 0.561485E+09 | 0.193611E+10 | 0.913990E+09 | 0.375296E+09 | 0.538694E+09 | 0.00 | 0.00 |
December | 0.389171E+09 | 0.290634E+10 | 0.822683E+09 | 0.454386E+09 | 0.368297E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.217148E+11 | 0.169768E+11 | 0.197646E+11 | 0.825039E+10 | 0.115142E+11 | 0.00 | 0.00 |
Minimum of Months | 0.389171E+09 | 0.349236E+09 | 0.822683E+09 | 0.375296E+09 | 0.368297E+09 | 0.00 | 0.00 |
Maximum of Months | 0.349269E+10 | 0.311305E+10 | 0.237795E+10 | 0.937755E+09 | 0.144019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122528E+10 | 0.342693E+10 | 0.189108E+10 | 0.117464E+10 | 0.716431E+09 | 0.00 | 0.00 |
February | 0.134409E+10 | 0.242914E+10 | 0.187158E+10 | 0.113255E+10 | 0.739031E+09 | 0.00 | 0.00 |
March | 0.152028E+10 | 0.196007E+10 | 0.191880E+10 | 0.828742E+09 | 0.109006E+10 | 0.00 | 0.00 |
April | 0.164811E+10 | 0.134046E+10 | 0.174234E+10 | 0.629015E+09 | 0.111332E+10 | 0.00 | 0.00 |
May | 0.183266E+10 | 0.743795E+09 | 0.170953E+10 | 0.355890E+09 | 0.135364E+10 | 0.00 | 0.00 |
June | 0.207899E+10 | 0.459428E+09 | 0.168483E+10 | 0.275165E+09 | 0.140967E+10 | 0.00 | 0.00 |
July | 0.230095E+10 | 0.396207E+09 | 0.177462E+10 | 0.343272E+09 | 0.143135E+10 | 0.00 | 0.00 |
August | 0.237846E+10 | 0.492811E+09 | 0.181648E+10 | 0.477381E+09 | 0.133910E+10 | 0.00 | 0.00 |
September | 0.231271E+10 | 0.852668E+09 | 0.192340E+10 | 0.815052E+09 | 0.110834E+10 | 0.00 | 0.00 |
October | 0.201107E+10 | 0.140400E+10 | 0.202255E+10 | 0.110849E+10 | 0.914067E+09 | 0.00 | 0.00 |
November | 0.109313E+10 | 0.213157E+10 | 0.145244E+10 | 0.797332E+09 | 0.655112E+09 | 0.00 | 0.00 |
December | 0.112375E+10 | 0.319383E+10 | 0.152116E+10 | 0.106119E+10 | 0.459973E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208695E+11 | 0.188309E+11 | 0.213288E+11 | 0.899872E+10 | 0.123301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109313E+10 | 0.396207E+09 | 0.145244E+10 | 0.275165E+09 | 0.459973E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237846E+10 | 0.342693E+10 | 0.202255E+10 | 0.117464E+10 | 0.143135E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770746E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164672330.8 | 81.21 | 0.00 | 0.00 |
February | 0.696575E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149786090.0 | 81.21 | 0.00 | 0.00 |
March | 0.770360E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162119429.8 | 81.21 | 0.00 | 0.00 |
April | 0.746526E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156664569.2 | 81.21 | 0.00 | 0.00 |
May | 0.770443E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161647424.6 | 81.21 | 0.00 | 0.00 |
June | 0.745684E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156321531.3 | 81.21 | 0.00 | 0.00 |
July | 0.771233E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161484345.7 | 81.21 | 0.00 | 0.00 |
August | 0.770431E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161507038.4 | 81.21 | 0.00 | 0.00 |
September | 0.746634E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156421281.2 | 81.21 | 0.00 | 0.00 |
October | 0.770332E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161874772.3 | 81.21 | 0.00 | 0.00 |
November | 0.744964E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157219311.2 | 81.21 | 0.00 | 0.00 |
December | 0.771331E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162446009.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907526E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191216E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696575E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164672330.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771331E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149786090.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.128963E+12 | -0.127211E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175253E+10 | 80.73 | 0.00 | 0.00 |
February | 0.116649E+12 | -0.115042E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160738E+10 | 80.44 | 0.00 | 0.00 |
March | 0.129046E+12 | -0.127291E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175573E+10 | 80.59 | 0.00 | 0.00 |
April | 0.124567E+12 | -0.122841E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172683E+10 | 81.15 | 0.00 | 0.00 |
May | 0.124188E+12 | -0.122407E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178098E+10 | 81.29 | 0.00 | 0.00 |
June | 0.114539E+12 | -0.112831E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170745E+10 | 81.26 | 0.00 | 0.00 |
July | 0.113881E+12 | -0.112132E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174924E+10 | 81.25 | 0.00 | 0.00 |
August | 0.111836E+12 | -0.110100E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173570E+10 | 81.25 | 0.00 | 0.00 |
September | 0.109188E+12 | -0.107514E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167441E+10 | 81.25 | 0.00 | 0.00 |
October | 0.116549E+12 | -0.114820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172888E+10 | 81.26 | 0.00 | 0.00 |
November | 0.118084E+12 | -0.116407E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167716E+10 | 81.27 | 0.00 | 0.00 |
December | 0.127703E+12 | -0.125968E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173443E+10 | 81.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.143519E+13 | -0.141456E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206307E+11 | 81.09 | 0.00 | 0.00 |
Minimum of Months | 0.109188E+12 | -0.127291E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178098E+10 | 80.44 | 0.00 | 0.00 |
Maximum of Months | 0.129046E+12 | -0.107514E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160738E+10 | 81.29 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.814390E+11 | -0.799184E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152063E+10 | 58.99 | 0.00 | 0.00 |
February | 0.750829E+11 | -0.736643E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.141852E+10 | 58.99 | 0.00 | 0.00 |
March | 0.823238E+11 | -0.807927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153106E+10 | 58.99 | 0.00 | 0.00 |
April | 0.766140E+11 | -0.751164E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149757E+10 | 58.99 | 0.00 | 0.00 |
May | 0.745269E+11 | -0.729901E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153684E+10 | 58.98 | 0.00 | 0.00 |
June | 0.673876E+11 | -0.659216E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146597E+10 | 58.98 | 0.00 | 0.00 |
July | 0.657197E+11 | -0.642254E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149423E+10 | 58.98 | 0.00 | 0.00 |
August | 0.640181E+11 | -0.625426E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147545E+10 | 58.98 | 0.00 | 0.00 |
September | 0.627423E+11 | -0.613216E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142066E+10 | 58.98 | 0.00 | 0.00 |
October | 0.680007E+11 | -0.665348E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146591E+10 | 58.98 | 0.00 | 0.00 |
November | 0.703248E+11 | -0.689010E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142383E+10 | 58.98 | 0.00 | 0.00 |
December | 0.775489E+11 | -0.760760E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147290E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.865729E+12 | -0.848005E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177236E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.627423E+11 | -0.807927E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.153684E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.823238E+11 | -0.613216E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.141852E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.87 | 0.86 | 01-JAN-09:39 | 6560.51 | 38.07 | 207.17 | 251.67 | 4405.62 | 37.54 | 209.33 | 220.00 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:00 | 7949.11 | 37.88 | 221.67 | 259.00 | 1683.07 | 29.13 | 211.17 | 234.83 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-08:09 | 4433.43 | 26.24 | 208.67 | 332.00 | 763.38 | 22.41 | 241.33 | 286.17 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:30 | 1638.54 | 20.98 | 132.67 | 352.50 | 668.04 | 22.69 | 227.00 | 286.33 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:49 | 1347.95 | 20.09 | 100.83 | 402.17 | 527.62 | 21.79 | 286.50 | 336.17 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-06:10 | 1372.97 | 20.47 | 156.50 | 403.67 | 549.99 | 22.18 | 290.00 | 338.50 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-06:10 | 1411.89 | 20.81 | 180.67 | 413.67 | 569.66 | 22.51 | 315.50 | 350.00 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:40 | 1583.16 | 20.54 | 156.83 | 384.17 | 620.94 | 22.24 | 311.00 | 333.00 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:40 | 2683.09 | 23.20 | 196.00 | 337.50 | 737.60 | 22.83 | 252.50 | 294.83 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-07:10 | 6894.32 | 33.84 | 296.83 | 310.67 | 935.80 | 23.82 | 248.67 | 280.50 |
November | 254.83 | 0.87 | 0.86 | 01-NOV-07:49 | 4689.54 | 33.36 | 239.67 | 253.83 | 2253.42 | 30.81 | 229.83 | 223.83 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-08:09 | 5688.36 | 38.18 | 180.50 | 227.50 | 5052.28 | 39.16 | 180.83 | 176.33 |
Annual Sum or Average | 3807.33 | 0.87 | 3386.20 | 26.15 | 2278.00 | 3928.33 | 1252.44 | 25.12 | 3003.67 | 3360.50 | ||
Minimum of Months | 186.17 | 0.87 | 0.86 | 1347.95 | 20.09 | 100.83 | 227.50 | 527.62 | 21.79 | 180.83 | 176.33 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 7949.11 | 38.18 | 296.83 | 413.67 | 5052.28 | 39.16 | 315.50 | 350.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.24 | 0.22 | 01-JAN-09:39 | 7089.00 | 38.16 | 207.17 | 259.67 | 4933.36 | 37.53 | 204.67 | 238.50 |
February | 226.83 | 0.25 | 0.22 | 01-FEB-07:49 | 8469.40 | 37.94 | 222.00 | 266.17 | 2199.12 | 28.86 | 206.67 | 249.83 |
March | 334.33 | 0.25 | 0.22 | 01-MAR-07:40 | 4812.25 | 26.46 | 211.00 | 341.67 | 1138.84 | 22.54 | 245.83 | 314.00 |
April | 285.17 | 0.26 | 0.22 | 01-APR-06:00 | 2003.95 | 21.18 | 131.17 | 362.67 | 1032.39 | 22.75 | 238.83 | 332.33 |
May | 428.67 | 0.26 | 0.22 | 01-MAY-06:40 | 1589.32 | 20.64 | 161.00 | 416.67 | 768.17 | 22.16 | 312.33 | 379.33 |
June | 400.67 | 0.26 | 0.22 | 01-JUN-05:30 | 1613.23 | 21.00 | 198.33 | 416.17 | 789.43 | 22.53 | 316.00 | 383.00 |
July | 414.00 | 0.25 | 0.22 | 01-JUL-05:49 | 1668.88 | 21.28 | 222.67 | 426.00 | 825.79 | 22.81 | 336.17 | 392.50 |
August | 410.83 | 0.26 | 0.22 | 01-AUG-05:00 | 1866.75 | 20.97 | 203.17 | 396.00 | 903.52 | 22.50 | 327.00 | 368.00 |
September | 326.50 | 0.25 | 0.22 | 01-SEP-06:19 | 3066.31 | 23.36 | 186.67 | 346.33 | 1119.45 | 22.90 | 271.33 | 320.33 |
October | 325.17 | 0.25 | 0.22 | 01-OCT-06:49 | 7307.74 | 34.00 | 298.50 | 317.00 | 1349.44 | 23.84 | 243.17 | 299.83 |
November | 254.83 | 0.25 | 0.22 | 01-NOV-07:40 | 5046.66 | 33.47 | 241.33 | 262.00 | 2610.83 | 30.86 | 229.67 | 241.67 |
December | 186.17 | 0.25 | 0.22 | 01-DEC-07:00 | 6180.94 | 38.27 | 180.50 | 238.67 | 5540.93 | 39.23 | 180.83 | 210.67 |
Annual Sum or Average | 3807.33 | 0.25 | 3734.73 | 26.45 | 2463.50 | 4049.00 | 1599.64 | 25.27 | 3112.50 | 3730.00 | ||
Minimum of Months | 186.17 | 0.24 | 0.22 | 1589.32 | 20.64 | 131.17 | 238.67 | 768.17 | 22.16 | 180.83 | 210.67 | |
Maximum of Months | 428.67 | 0.26 | 0.22 | 8469.40 | 38.27 | 298.50 | 426.00 | 5540.93 | 39.23 | 336.17 | 392.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 471.36 | 15.70 | 0.00 | 234.00 | 229.93 | 19.17 | 0.50 | 138.50 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 483.84 | 15.93 | 0.00 | 245.67 | 238.13 | 19.35 | 0.50 | 164.00 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 679.86 | 17.19 | 0.00 | 332.17 | 304.73 | 20.39 | 33.83 | 270.33 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 772.63 | 18.34 | 0.00 | 362.33 | 367.82 | 21.54 | 143.00 | 305.17 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 912.49 | 18.41 | 4.17 | 423.00 | 398.77 | 22.41 | 236.50 | 387.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1107.44 | 21.39 | 67.17 | 424.50 | 513.48 | 24.46 | 307.17 | 398.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1035.02 | 20.95 | 54.17 | 432.33 | 479.48 | 23.61 | 308.33 | 406.17 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 851.20 | 18.49 | 4.50 | 398.33 | 386.76 | 21.86 | 234.17 | 370.17 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 683.00 | 17.87 | 0.00 | 340.50 | 328.29 | 21.06 | 102.83 | 293.83 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 553.68 | 16.40 | 0.00 | 299.50 | 255.68 | 19.70 | 0.17 | 227.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 485.11 | 15.48 | 0.00 | 240.50 | 214.82 | 18.78 | 0.00 | 144.67 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 |
Annual Sum or Average | 3807.33 | 0.63 | 751.26 | 17.98 | 130.00 | 3936.67 | 346.89 | 21.28 | 1367.00 | 3156.50 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1107.44 | 21.39 | 67.17 | 432.33 | 513.48 | 24.46 | 308.33 | 406.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 471.36 | 15.70 | 0.00 | 234.00 | 229.93 | 19.17 | 0.50 | 138.50 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 483.84 | 15.93 | 0.00 | 245.67 | 238.13 | 19.35 | 0.50 | 164.00 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 679.86 | 17.19 | 0.00 | 332.17 | 304.73 | 20.39 | 33.83 | 270.33 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 772.63 | 18.34 | 0.00 | 362.33 | 367.82 | 21.54 | 143.00 | 305.17 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 912.49 | 18.41 | 4.17 | 423.00 | 398.77 | 22.41 | 236.50 | 387.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1107.44 | 21.39 | 67.17 | 424.50 | 513.48 | 24.46 | 307.17 | 398.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1035.02 | 20.95 | 54.17 | 432.33 | 479.48 | 23.61 | 308.33 | 406.17 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 851.20 | 18.49 | 4.50 | 398.33 | 386.76 | 21.86 | 234.17 | 370.17 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 683.00 | 17.87 | 0.00 | 340.50 | 328.29 | 21.06 | 102.83 | 293.83 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 553.68 | 16.40 | 0.00 | 299.50 | 255.68 | 19.70 | 0.17 | 227.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 485.11 | 15.48 | 0.00 | 240.50 | 214.82 | 18.78 | 0.00 | 144.67 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 |
Annual Sum or Average | 3807.33 | 0.63 | 751.26 | 17.98 | 130.00 | 3936.67 | 346.89 | 21.28 | 1367.00 | 3156.50 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1107.44 | 21.39 | 67.17 | 432.33 | 513.48 | 24.46 | 308.33 | 406.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279075E+12 | 332395.80 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186142E+12 | 348283.42 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.852004E+11 | 124834.41 | 31-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530760E+11 | 123152.02 | 25-APR-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.463308E+11 | 116188.18 | 20-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.278310E+11 | 118352.49 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.507348E+10 | 71817.73 | 24-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117490E+11 | 101856.78 | 07-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426453E+11 | 123398.76 | 30-SEP-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767437E+11 | 126085.48 | 23-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104756E+12 | 325973.21 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148179E+12 | 166660.03 | 08-DEC-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106680E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.507348E+10 | 71817.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279075E+12 | 348283.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185953E+10 | 7445.54 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343989E+10 | 7853.39 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40030063.16 | 7248.41 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343989E+10 | 7853.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565588E+10 | 4634.97 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409789E+10 | 4897.91 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240916E+10 | 2407.96 | 06-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141357E+10 | 2106.26 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267180E+09 | 1144.80 | 02-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138432E+09 | 975.33 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4205730.06 | 282.33 | 10-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380511.54 | 121.88 | 07-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.331163E+09 | 1479.77 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.969622E+09 | 1522.39 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284963E+10 | 4530.73 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446412E+10 | 3275.63 | 09-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 380511.54 | 121.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565588E+10 | 4897.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102045E+10 | 1712.40 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.780310E+09 | 1807.83 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68793976.68 | 517.24 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13921811.75 | 421.33 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209128E+09 | 1674.48 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335586E+09 | 836.88 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102045E+10 | 1807.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305211E+10 | 2524.47 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217122E+10 | 2667.66 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878579E+09 | 1115.06 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.268053E+09 | 857.23 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113066.85 | 234.98 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3857537.96 | 197.05 | 16-OCT-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.998953E+09 | 2467.71 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198683E+10 | 1637.05 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305211E+10 | 2667.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224884E+10 | 1586.31 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159776E+10 | 1675.73 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.795255E+09 | 814.62 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303176E+09 | 614.75 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2515594.21 | 201.68 | 02-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3300004.25 | 142.86 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47528422.11 | 221.89 | 26-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857357E+09 | 1550.83 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162268E+10 | 1122.75 | 09-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.747841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224884E+10 | 1675.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323729E+10 | 10767.13 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340745E+10 | 11357.52 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132439E+09 | 1827.37 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41087102.05 | 1300.99 | 03-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 532747.61 | 210.03 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 256568.94 | 141.76 | 03-JUN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3058303.99 | 598.76 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17231204.04 | 598.77 | 14-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.550208E+09 | 10532.02 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274158E+09 | 2536.36 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340745E+10 | 11357.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.794611E+10 | 13161.05 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.589610E+10 | 13896.42 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127499E+10 | 5195.37 | 01-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770967E+09 | 4754.80 | 03-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4449382.08 | 1461.06 | 25-MAY-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30355447.68 | 2184.39 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 134826.54 | 224.71 | 10-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49162339.85 | 2280.44 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134608E+09 | 2693.76 | 26-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237651E+10 | 12868.92 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422637E+10 | 8228.72 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.794611E+10 | 13896.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144175E+11 | 33260.79 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128715E+11 | 35108.28 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561214E+09 | 8394.80 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129609E+09 | 6214.49 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267786E+10 | 32526.30 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356020E+10 | 15554.86 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144175E+11 | 35108.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.192194E+11 | 16413.33 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138321E+11 | 17338.55 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546098E+10 | 7537.37 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180183E+10 | 6467.67 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34364198.44 | 2650.24 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.612154E+09 | 3550.77 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780908E+10 | 16046.21 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137846E+11 | 11602.19 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.192194E+11 | 17338.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122765E+11 | 10304.76 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.866411E+10 | 10892.30 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374404E+10 | 4608.73 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140595E+10 | 3361.82 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16033728.99 | 843.98 | 02-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113426E+09 | 2029.33 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.779588E+09 | 2237.30 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488467E+10 | 10071.98 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874131E+10 | 7068.39 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122765E+11 | 10892.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385819E+10 | 13269.26 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418580E+10 | 14004.76 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533815E+09 | 12976.77 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37667162.77 | 1451.66 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.861547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418580E+10 | 14004.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.386060E+10 | 13675.47 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422986E+10 | 14433.18 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.526444E+09 | 13374.13 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82888.44 | 91.80 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.861699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422986E+10 | 14433.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242291E+10 | 9002.96 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268287E+10 | 9497.83 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344602E+09 | 8805.95 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 124633.92 | 147.43 | 10-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268287E+10 | 9497.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163770E+11 | 31980.12 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111491E+11 | 33531.07 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235863E+10 | 7144.88 | 05-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439575E+09 | 4040.53 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10306.48 | 0.27 | 12-MAY-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14991.45 | 0.27 | 18-JUN-22:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13312.96 | 0.27 | 09-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13777.61 | 0.27 | 12-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 296263.34 | 189.22 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21341119.14 | 1120.92 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.387191E+10 | 31354.11 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695629E+10 | 11604.85 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10306.48 | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163770E+11 | 33531.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.989562E+10 | 8457.06 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666585E+10 | 8457.01 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.379120E+10 | 8456.40 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162031E+10 | 8456.14 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148249E+09 | 7242.53 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 61861265.05 | 4434.24 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7041739.41 | 4071.38 | 20-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8054540.40 | 3928.23 | 22-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337332E+09 | 8188.27 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138540E+10 | 8341.06 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.472618E+10 | 8456.49 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.826790E+10 | 8457.28 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7041739.41 | 3928.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.989562E+10 | 8457.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113659E+11 | 8412.39 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788119E+10 | 8513.70 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447365E+10 | 8412.63 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183412E+10 | 8411.44 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158017E+09 | 8117.04 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 62535340.04 | 4439.14 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3620856.63 | 4807.21 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5330672.54 | 5085.04 | 18-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407028E+09 | 8229.02 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190608E+10 | 8342.26 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552447E+10 | 8412.28 | 10-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943615E+10 | 8412.64 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3620856.63 | 4439.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113659E+11 | 8513.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110219E+11 | 28543.83 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266543E+10 | 23697.36 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386592E+09 | 10291.80 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.994573E+09 | 19845.89 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.744031E+10 | 22440.01 | 12-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110219E+11 | 28543.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.523200E+11 | 46813.21 | 22-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365428E+11 | 48031.91 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154088E+11 | 46577.01 | 01-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470842E+10 | 45585.09 | 03-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171028E+09 | 38724.86 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35455928.14 | 31328.90 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20364689.72 | 32027.37 | 11-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43250050.93 | 32320.57 | 06-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.428476E+09 | 41803.25 | 30-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322599E+10 | 43675.70 | 10-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198495E+11 | 46810.26 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393220E+11 | 46815.82 | 29-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20364689.72 | 31328.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.523200E+11 | 48031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.982682E+10 | 8236.43 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672795E+10 | 8308.51 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372459E+10 | 8235.73 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176402E+10 | 8235.45 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124846E+09 | 4575.27 | 11-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49330655.16 | 4770.25 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3572669.48 | 4209.35 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5853483.06 | 3865.28 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309561E+09 | 5159.69 | 25-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139546E+10 | 8080.33 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475168E+10 | 8235.85 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.829628E+10 | 8236.65 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3572669.48 | 3865.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.982682E+10 | 8308.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113124E+11 | 8189.95 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797101E+10 | 8392.08 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438087E+10 | 8189.22 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201167E+10 | 8188.94 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140985E+09 | 6093.29 | 20-MAY-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51301595.51 | 4388.77 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3244730.10 | 3892.83 | 10-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4496003.39 | 3819.67 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367325E+09 | 5432.58 | 24-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190479E+10 | 8075.81 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556245E+10 | 8190.83 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.949619E+10 | 8190.18 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3244730.10 | 3819.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113124E+11 | 8392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323971E+10 | 2463.43 | 13-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217783E+10 | 2480.06 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133629E+10 | 2463.57 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607990E+09 | 2463.44 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83172923.55 | 2398.52 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37111118.26 | 1234.16 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2096466.51 | 1033.67 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2786166.98 | 1095.10 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159112E+09 | 2423.60 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.559858E+09 | 2463.36 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163399E+10 | 2464.20 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.275375E+10 | 2463.53 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2096466.51 | 1033.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323971E+10 | 2480.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365691E+10 | 2447.47 | 13-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253824E+10 | 2505.36 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155370E+10 | 2447.60 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.674879E+09 | 2447.48 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82369834.60 | 2391.91 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37314187.03 | 1220.66 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 940285.59 | 1144.84 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1493593.91 | 1310.06 | 08-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183703E+09 | 2431.30 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.734202E+09 | 2447.73 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187983E+10 | 2448.26 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309725E+10 | 2447.57 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 940285.59 | 1144.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365691E+10 | 2505.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111597E+11 | 11620.51 | 16-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697703E+10 | 11619.82 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416132E+10 | 11619.76 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209563E+10 | 11619.57 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185862E+09 | 6577.03 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75823589.39 | 6124.13 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10545612.49 | 5608.73 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13512238.83 | 4925.49 | 12-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329041E+09 | 5285.07 | 13-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111165E+10 | 11310.74 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504937E+10 | 11619.94 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944180E+10 | 11620.15 | 30-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10545612.49 | 4925.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111597E+11 | 11620.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1491782.44 | 1491782.44 | 796.74 | 17-JAN-23:10 | 796.74 | 0.00 |
February | 0.00 | 0.00 | 569732.18 | 569732.18 | 509.45 | 07-FEB-19:40 | 509.45 | 0.00 |
March | 0.00 | 0.00 | 0.290482E+10 | 0.290482E+10 | 72493.38 | 19-MAR-16:20 | 72493.38 | 0.02 |
April | 0.00 | 0.00 | 0.458794E+11 | 0.384366E+11 | 302332.89 | 18-APR-10:33 | 184060.41 | 0.14 |
May | 0.00 | 0.00 | 0.106678E+12 | 0.868902E+11 | 305551.10 | 30-MAY-19:20 | 195590.51 | 0.40 |
June | 0.00 | 0.00 | 0.328153E+12 | 0.224361E+12 | 394026.76 | 26-JUN-18:20 | 250001.98 | 0.75 |
July | 0.00 | 0.00 | 0.476320E+12 | 0.285209E+12 | 576578.70 | 03-JUL-21:30 | 206963.66 | 0.93 |
August | 0.00 | 0.00 | 0.412070E+12 | 0.250589E+12 | 582238.39 | 03-AUG-22:00 | 208598.90 | 0.85 |
September | 0.00 | 0.00 | 0.151035E+12 | 0.138570E+12 | 313632.28 | 11-SEP-19:20 | 195529.06 | 0.46 |
October | 0.00 | 0.00 | 0.103039E+11 | 0.103039E+11 | 141733.73 | 20-OCT-15:04 | 141733.73 | 0.05 |
November | 0.00 | 0.00 | 0.452982E+09 | 0.452982E+09 | 22164.34 | 03-NOV-15:20 | 22164.34 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153380E+13 | 0.103772E+13 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.476320E+12 | 0.285209E+12 | 582238.39 | 250001.98 | 0.93 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213301E+09 | 0.213301E+09 | 8515.76 | 19-MAR-16:00 | 8515.76 | 0.01 |
April | 0.00 | 0.00 | 0.323797E+10 | 0.259061E+10 | 26462.51 | 18-APR-08:50 | 14831.26 | 0.10 |
May | 0.00 | 0.00 | 0.744936E+10 | 0.563759E+10 | 29501.61 | 29-MAY-15:02 | 14685.64 | 0.29 |
June | 0.00 | 0.00 | 0.240232E+11 | 0.157030E+11 | 40758.49 | 26-JUN-06:55 | 16463.34 | 0.57 |
July | 0.00 | 0.00 | 0.362691E+11 | 0.207034E+11 | 40259.71 | 17-JUL-18:50 | 16006.70 | 0.72 |
August | 0.00 | 0.00 | 0.297117E+11 | 0.173764E+11 | 42516.66 | 31-AUG-18:03 | 16363.09 | 0.66 |
September | 0.00 | 0.00 | 0.108269E+11 | 0.934616E+10 | 29549.17 | 11-SEP-08:15 | 15611.99 | 0.35 |
October | 0.00 | 0.00 | 0.651762E+09 | 0.651762E+09 | 15286.74 | 20-OCT-15:01 | 15286.74 | 0.03 |
November | 0.00 | 0.00 | 24319556.63 | 24319556.63 | 2178.01 | 03-NOV-15:01 | 2178.01 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.112408E+12 | 0.722466E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.362691E+11 | 0.207034E+11 | 42516.66 | 16463.34 | 0.72 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5974004.25 | 5974004.25 | 18004.48 | 12-JAN-16:01 | 18004.48 | 0.00 |
February | 0.00 | 0.00 | 0.132881E+09 | 0.132385E+09 | 18458.23 | 25-FEB-16:01 | 18458.23 | 0.00 |
March | 0.00 | 0.00 | 0.444526E+09 | 0.347835E+09 | 18460.39 | 25-MAR-15:01 | 18460.39 | 0.05 |
April | 0.00 | 0.00 | 0.261192E+10 | 0.172110E+10 | 18674.66 | 16-APR-08:61 | 14559.60 | 0.28 |
May | 0.00 | 0.00 | 0.469854E+10 | 0.240727E+10 | 18836.21 | 11-MAY-15:01 | 14448.22 | 0.68 |
June | 0.00 | 0.00 | 0.840382E+10 | 0.446994E+10 | 20062.46 | 25-JUN-08:61 | 13510.45 | 0.85 |
July | 0.00 | 0.00 | 0.107376E+11 | 0.567848E+10 | 20583.59 | 20-JUL-08:61 | 13081.15 | 0.94 |
August | 0.00 | 0.00 | 0.955593E+10 | 0.477171E+10 | 21652.11 | 31-AUG-08:61 | 12130.19 | 0.94 |
September | 0.00 | 0.00 | 0.572202E+10 | 0.322858E+10 | 18691.25 | 11-SEP-08:61 | 14572.77 | 0.66 |
October | 0.00 | 0.00 | 0.119508E+10 | 0.808049E+09 | 18458.86 | 19-OCT-15:01 | 18458.86 | 0.19 |
November | 0.00 | 0.00 | 0.218244E+09 | 0.155096E+09 | 18451.98 | 04-NOV-15:01 | 18451.98 | 0.03 |
December | 0.00 | 0.00 | 9097600.28 | 9097600.28 | 17668.58 | 01-DEC-16:01 | 17668.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.437357E+11 | 0.237355E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 5974004.25 | 5974004.25 | 17668.58 | 12130.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107376E+11 | 0.567848E+10 | 21652.11 | 18460.39 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 249788.37 | 249788.37 | 1932.32 | 12-JAN-16:03 | 1932.32 | 0.00 |
February | 0.00 | 0.00 | 31211676.38 | 30980846.34 | 17727.89 | 24-FEB-16:02 | 17727.89 | 0.00 |
March | 0.00 | 0.00 | 0.143539E+09 | 0.109981E+09 | 17915.43 | 25-MAR-15:01 | 17915.43 | 0.03 |
April | 0.00 | 0.00 | 0.158213E+10 | 0.988317E+09 | 18703.51 | 16-APR-21:51 | 14707.30 | 0.20 |
May | 0.00 | 0.00 | 0.308901E+10 | 0.140796E+10 | 20135.13 | 20-MAY-18:41 | 20135.13 | 0.54 |
June | 0.00 | 0.00 | 0.660616E+10 | 0.357283E+10 | 23064.97 | 26-JUN-08:11 | 13128.13 | 0.65 |
July | 0.00 | 0.00 | 0.811467E+10 | 0.438912E+10 | 21336.87 | 02-JUL-08:51 | 13874.68 | 0.68 |
August | 0.00 | 0.00 | 0.671152E+10 | 0.323507E+10 | 23364.35 | 03-AUG-07:51 | 12574.25 | 0.68 |
September | 0.00 | 0.00 | 0.361296E+10 | 0.181300E+10 | 20462.88 | 19-SEP-17:41 | 20462.88 | 0.50 |
October | 0.00 | 0.00 | 0.363186E+09 | 0.230873E+09 | 17913.22 | 24-OCT-15:01 | 17913.22 | 0.08 |
November | 0.00 | 0.00 | 62534319.70 | 44070853.85 | 17906.45 | 04-NOV-15:01 | 17906.45 | 0.01 |
December | 0.00 | 0.00 | 487922.92 | 487922.92 | 2378.91 | 01-DEC-16:03 | 2378.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303177E+11 | 0.158229E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 249788.37 | 249788.37 | 1932.32 | 1932.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.811467E+10 | 0.438912E+10 | 23364.35 | 20462.88 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.268919E+10 | 0.260121E+10 | 33092.46 | 24-MAR-13:10 | 33092.46 | 0.01 |
April | 0.00 | 0.00 | 0.122195E+11 | 0.689671E+10 | 51511.54 | 15-APR-13:30 | 44126.88 | 0.23 |
May | 0.00 | 0.00 | 0.246030E+11 | 0.109301E+11 | 37477.78 | 05-MAY-13:30 | 23471.18 | 0.62 |
June | 0.00 | 0.00 | 0.371158E+11 | 0.140709E+11 | 41019.66 | 26-JUN-12:30 | 26239.76 | 0.87 |
July | 0.00 | 0.00 | 0.471639E+11 | 0.181141E+11 | 43538.91 | 30-JUL-13:20 | 30572.47 | 0.98 |
August | 0.00 | 0.00 | 0.479440E+11 | 0.198686E+11 | 47641.05 | 22-AUG-13:30 | 35069.10 | 0.98 |
September | 0.00 | 0.00 | 0.378297E+11 | 0.218998E+11 | 58517.50 | 08-SEP-14:00 | 54148.48 | 0.67 |
October | 0.00 | 0.00 | 0.175188E+11 | 0.150093E+11 | 55179.66 | 20-OCT-12:40 | 55179.66 | 0.15 |
November | 0.00 | 0.00 | 0.475371E+10 | 0.398955E+10 | 52426.28 | 04-NOV-12:30 | 52426.28 | 0.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.231838E+12 | 0.113380E+12 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.479440E+11 | 0.218998E+11 | 58517.50 | 55179.66 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12292091.80 | 12292091.80 | 16549.05 | 13-JAN-19:03 | 16549.05 | 0.00 |
February | 0.00 | 0.00 | 56278230.21 | 47736190.32 | 58610.21 | 25-FEB-09:02 | 58610.21 | 0.00 |
March | 0.00 | 0.00 | 0.237177E+10 | 0.129893E+10 | 88589.78 | 24-MAR-18:01 | 88589.78 | 0.10 |
April | 0.00 | 0.00 | 0.108946E+11 | 0.653081E+10 | 97083.12 | 16-APR-21:51 | 75398.88 | 0.23 |
May | 0.00 | 0.00 | 0.304110E+11 | 0.167390E+11 | 102389.44 | 29-MAY-21:51 | 77608.55 | 0.56 |
June | 0.00 | 0.00 | 0.477871E+11 | 0.284369E+11 | 118637.16 | 26-JUN-08:11 | 66801.72 | 0.65 |
July | 0.00 | 0.00 | 0.525021E+11 | 0.304653E+11 | 108831.85 | 02-JUL-08:51 | 72188.69 | 0.61 |
August | 0.00 | 0.00 | 0.461590E+11 | 0.254968E+11 | 124100.33 | 03-AUG-07:51 | 61504.42 | 0.60 |
September | 0.00 | 0.00 | 0.275624E+11 | 0.153094E+11 | 100418.52 | 11-SEP-21:51 | 74604.57 | 0.53 |
October | 0.00 | 0.00 | 0.667103E+10 | 0.379448E+10 | 88473.53 | 12-OCT-18:03 | 88473.53 | 0.23 |
November | 0.00 | 0.00 | 0.283382E+10 | 0.104937E+10 | 86579.69 | 04-NOV-18:02 | 86579.69 | 0.14 |
December | 0.00 | 0.00 | 23607981.93 | 23607981.93 | 14987.58 | 18-DEC-19:05 | 14987.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.227285E+12 | 0.129205E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 12292091.80 | 12292091.80 | 14987.58 | 14987.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.525021E+11 | 0.304653E+11 | 124100.33 | 88589.78 | 0.65 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4078868.28 | 4078868.28 | 2188.06 | 13-JAN-16:03 | 2188.06 | 0.00 |
February | 0.00 | 0.00 | 82383749.79 | 66878466.61 | 16472.70 | 24-FEB-16:02 | 16472.70 | 0.01 |
March | 0.00 | 0.00 | 0.415652E+09 | 0.283684E+09 | 16788.79 | 24-MAR-15:01 | 16788.79 | 0.07 |
April | 0.00 | 0.00 | 0.221118E+10 | 0.132178E+10 | 16788.56 | 09-APR-15:01 | 16788.56 | 0.29 |
May | 0.00 | 0.00 | 0.501598E+10 | 0.252576E+10 | 17113.16 | 11-MAY-15:01 | 13194.23 | 0.74 |
June | 0.00 | 0.00 | 0.856926E+10 | 0.464510E+10 | 18074.95 | 14-JUN-08:62 | 12052.90 | 0.88 |
July | 0.00 | 0.00 | 0.105195E+11 | 0.555523E+10 | 18752.32 | 20-JUL-08:61 | 11877.60 | 0.96 |
August | 0.00 | 0.00 | 0.924388E+10 | 0.458199E+10 | 19745.08 | 31-AUG-08:61 | 10815.16 | 0.96 |
September | 0.00 | 0.00 | 0.576303E+10 | 0.323716E+10 | 16774.01 | 30-SEP-15:01 | 16774.01 | 0.69 |
October | 0.00 | 0.00 | 0.982694E+09 | 0.611768E+09 | 16789.57 | 29-OCT-15:01 | 16789.57 | 0.19 |
November | 0.00 | 0.00 | 0.175610E+09 | 0.113026E+09 | 16783.71 | 04-NOV-15:01 | 16783.71 | 0.04 |
December | 0.00 | 0.00 | 20409799.58 | 19898146.46 | 8940.21 | 03-DEC-09:02 | 8940.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.430037E+11 | 0.229664E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 4078868.28 | 4078868.28 | 2188.06 | 2188.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105195E+11 | 0.555523E+10 | 19745.08 | 16789.57 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 215277.45 | 215277.45 | 2065.61 | 12-JAN-09:04 | 2065.61 | 0.00 |
February | 0.00 | 0.00 | 12994246.52 | 10480366.68 | 13986.65 | 24-FEB-09:01 | 13986.65 | 0.00 |
March | 0.00 | 0.00 | 0.121039E+09 | 77571361.99 | 15098.86 | 24-MAR-15:01 | 15098.86 | 0.03 |
April | 0.00 | 0.00 | 0.129704E+10 | 0.744291E+09 | 17846.99 | 16-APR-08:51 | 14703.68 | 0.20 |
May | 0.00 | 0.00 | 0.359409E+10 | 0.177823E+10 | 20185.67 | 31-MAY-08:32 | 16835.44 | 0.60 |
June | 0.00 | 0.00 | 0.680332E+10 | 0.375366E+10 | 21778.36 | 26-JUN-07:52 | 15545.67 | 0.69 |
July | 0.00 | 0.00 | 0.789784E+10 | 0.420127E+10 | 21024.18 | 30-JUL-08:32 | 16092.54 | 0.70 |
August | 0.00 | 0.00 | 0.653616E+10 | 0.316903E+10 | 21108.38 | 03-AUG-07:51 | 13108.79 | 0.70 |
September | 0.00 | 0.00 | 0.369982E+10 | 0.189709E+10 | 18598.47 | 11-SEP-08:51 | 15170.95 | 0.54 |
October | 0.00 | 0.00 | 0.238304E+09 | 0.126294E+09 | 15405.70 | 02-OCT-15:01 | 13006.73 | 0.07 |
November | 0.00 | 0.00 | 20625418.50 | 11350961.71 | 8855.88 | 04-NOV-08:62 | 8502.18 | 0.01 |
December | 0.00 | 0.00 | 352062.04 | 352062.04 | 1642.09 | 03-DEC-09:03 | 1642.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.302218E+11 | 0.157698E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 215277.45 | 215277.45 | 1642.09 | 1642.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.789784E+10 | 0.420127E+10 | 21778.36 | 16835.44 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1199152.75 | 1199152.75 | 4630.33 | 12-JAN-16:01 | 4630.33 | 0.00 |
February | 0.00 | 0.00 | 32965548.58 | 32836614.27 | 4799.44 | 25-FEB-16:01 | 4799.44 | 0.00 |
March | 0.00 | 0.00 | 0.101164E+09 | 80637091.07 | 4799.50 | 23-MAR-18:01 | 4799.50 | 0.04 |
April | 0.00 | 0.00 | 0.673413E+09 | 0.462473E+09 | 4931.94 | 16-APR-08:61 | 3722.31 | 0.25 |
May | 0.00 | 0.00 | 0.117677E+10 | 0.640505E+09 | 5021.37 | 29-MAY-08:61 | 3661.57 | 0.61 |
June | 0.00 | 0.00 | 0.214687E+10 | 0.119364E+10 | 5385.25 | 25-JUN-08:61 | 3372.15 | 0.82 |
July | 0.00 | 0.00 | 0.271645E+10 | 0.149122E+10 | 5537.46 | 20-JUL-08:61 | 3127.60 | 0.94 |
August | 0.00 | 0.00 | 0.236740E+10 | 0.122397E+10 | 5797.99 | 31-AUG-08:61 | 2890.56 | 0.93 |
September | 0.00 | 0.00 | 0.138745E+10 | 0.818989E+09 | 5026.96 | 11-SEP-08:61 | 3628.15 | 0.60 |
October | 0.00 | 0.00 | 0.289538E+09 | 0.205725E+09 | 4799.52 | 19-OCT-15:01 | 4799.52 | 0.14 |
November | 0.00 | 0.00 | 53604267.99 | 39828563.55 | 4797.70 | 04-NOV-15:01 | 4797.70 | 0.02 |
December | 0.00 | 0.00 | 1828631.83 | 1800610.47 | 4581.21 | 01-DEC-16:01 | 4581.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109487E+11 | 0.619283E+10 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 1199152.75 | 1199152.75 | 4581.21 | 2890.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271645E+10 | 0.149122E+10 | 5797.99 | 4799.52 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 60233.35 | 60233.35 | 664.53 | 13-JAN-16:04 | 664.53 | 0.00 |
February | 0.00 | 0.00 | 5766639.47 | 5699125.85 | 4495.57 | 24-FEB-16:02 | 4495.57 | 0.00 |
March | 0.00 | 0.00 | 27225366.72 | 21262888.58 | 4720.23 | 23-MAR-18:01 | 4720.23 | 0.02 |
April | 0.00 | 0.00 | 0.406756E+09 | 0.264789E+09 | 4943.53 | 16-APR-21:51 | 3773.63 | 0.17 |
May | 0.00 | 0.00 | 0.780390E+09 | 0.382052E+09 | 5266.74 | 20-MAY-18:41 | 5266.74 | 0.49 |
June | 0.00 | 0.00 | 0.173893E+10 | 0.977838E+09 | 6083.82 | 26-JUN-08:11 | 3318.53 | 0.63 |
July | 0.00 | 0.00 | 0.212546E+10 | 0.118555E+10 | 5594.55 | 02-JUL-08:51 | 3559.06 | 0.68 |
August | 0.00 | 0.00 | 0.170903E+10 | 0.850000E+09 | 6262.10 | 03-AUG-07:51 | 3035.88 | 0.68 |
September | 0.00 | 0.00 | 0.877599E+09 | 0.464649E+09 | 5374.59 | 19-SEP-17:41 | 5374.59 | 0.44 |
October | 0.00 | 0.00 | 79172341.53 | 51100530.41 | 4583.25 | 24-OCT-15:01 | 4583.25 | 0.06 |
November | 0.00 | 0.00 | 14998524.70 | 10328097.13 | 4643.42 | 04-NOV-15:01 | 4643.42 | 0.01 |
December | 0.00 | 0.00 | 124742.63 | 124742.63 | 689.41 | 02-DEC-16:03 | 689.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.776551E+10 | 0.421345E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 60233.35 | 60233.35 | 664.53 | 664.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212546E+10 | 0.118555E+10 | 6262.10 | 5374.59 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.422568E+09 | 0.421742E+09 | 22172.84 | 13-JAN-16:01 | 22172.84 | 0.00 |
February | 0.00 | 0.00 | 0.885005E+09 | 0.728017E+09 | 22170.63 | 19-FEB-16:01 | 22170.63 | 0.05 |
March | 0.00 | 0.00 | 0.161756E+10 | 0.119451E+10 | 22171.44 | 31-MAR-15:01 | 22171.44 | 0.14 |
April | 0.00 | 0.00 | 0.396368E+10 | 0.258440E+10 | 22617.55 | 16-APR-08:61 | 17417.63 | 0.32 |
May | 0.00 | 0.00 | 0.631541E+10 | 0.304782E+10 | 22920.73 | 31-MAY-08:61 | 17264.78 | 0.71 |
June | 0.00 | 0.00 | 0.996952E+10 | 0.503302E+10 | 25109.00 | 25-JUN-08:61 | 15584.03 | 0.85 |
July | 0.00 | 0.00 | 0.125724E+11 | 0.632623E+10 | 25989.94 | 20-JUL-08:61 | 14134.21 | 0.93 |
August | 0.00 | 0.00 | 0.123925E+11 | 0.634426E+10 | 27146.54 | 31-AUG-08:61 | 13046.46 | 0.92 |
September | 0.00 | 0.00 | 0.905503E+10 | 0.562405E+10 | 23365.53 | 11-SEP-08:61 | 16936.32 | 0.71 |
October | 0.00 | 0.00 | 0.421591E+10 | 0.314535E+10 | 22170.98 | 27-OCT-15:01 | 22170.98 | 0.34 |
November | 0.00 | 0.00 | 0.133726E+10 | 0.101645E+10 | 22160.77 | 11-NOV-16:01 | 22160.77 | 0.13 |
December | 0.00 | 0.00 | 0.866227E+09 | 0.829854E+09 | 22157.16 | 01-DEC-16:01 | 22157.16 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.636130E+11 | 0.362957E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.422568E+09 | 0.421742E+09 | 22157.16 | 13046.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125724E+11 | 0.634426E+10 | 27146.54 | 22172.84 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 185673.30 | 611675.43 | 31-JAN-04:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 141876.52 | 645301.33 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52585.61 | 222647.56 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28648.41 | 177425.35 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 17679.41 | 150108.75 | 01-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10886.45 | 135613.32 | 03-JUN-08:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1898.02 | 71332.15 | 24-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 4386.14 | 101395.95 | 07-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 17503.02 | 138257.37 | 27-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33877.06 | 171556.54 | 17-OCT-18:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 70141.37 | 581464.02 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 108075.81 | 302935.94 | 09-DEC-09:08 |
Annual Sum or Average | 0.00 | 55663.99 | ||||
Minimum of Months | 0.00 | 0.00 | 1898.02 | 71332.15 | ||
Maximum of Months | 0.00 | 0.00 | 185673.30 | 645301.33 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372.45 | 21695.72 | 12-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 923.46 | 40817.81 | 25-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 5157.70 | 236684.08 | 25-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 34547.23 | 487286.14 | 18-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75331.38 | 493886.50 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 188662.66 | 607262.89 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 252009.29 | 745305.44 | 26-JUL-18:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221202.22 | 705473.09 | 21-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 102105.79 | 517118.93 | 06-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17904.96 | 369903.73 | 20-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4743.51 | 172971.54 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 672.22 | 24821.09 | 03-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 75835.04 | 0.00 | ||||
Minimum of Months | 372.45 | 21695.72 | 0.00 | 0.00 | ||
Maximum of Months | 252009.29 | 745305.44 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 31396.84 | 64793.86 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 32007.31 | 65238.63 | 21-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31722.50 | 65141.60 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30540.14 | 63282.09 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28814.61 | 60291.79 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26999.88 | 56312.65 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25549.31 | 52640.87 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 24922.80 | 50605.86 | 01-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 25230.32 | 51750.50 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26409.82 | 55097.21 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28147.18 | 58905.64 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29964.86 | 62344.12 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 28454.61 | ||||
Minimum of Months | 0.00 | 0.00 | 24922.80 | 50605.86 | ||
Maximum of Months | 0.00 | 0.00 | 32007.31 | 65238.63 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.73 | 1299.30 | 19-JAN-01:50 | 0.92 |
February | 0.244774E+10 | 0.73 | 1299.30 | 20-FEB-19:02 | 0.92 |
March | 0.271000E+10 | 0.73 | 1299.30 | 06-MAR-09:05 | 0.92 |
April | 0.262258E+10 | 0.73 | 1299.30 | 01-APR-08:03 | 0.92 |
May | 0.271000E+10 | 0.72 | 1299.30 | 06-MAY-19:34 | 0.92 |
June | 0.262258E+10 | 0.72 | 1299.30 | 01-JUN-08:15 | 0.92 |
July | 0.271000E+10 | 0.72 | 1299.30 | 01-JUL-09:13 | 0.91 |
August | 0.271000E+10 | 0.72 | 1299.30 | 01-AUG-08:56 | 0.91 |
September | 0.262258E+10 | 0.72 | 1299.30 | 01-SEP-08:54 | 0.91 |
October | 0.271000E+10 | 0.73 | 1299.30 | 19-OCT-15:03 | 0.92 |
November | 0.262258E+10 | 0.73 | 1299.30 | 02-NOV-08:62 | 0.92 |
December | 0.271000E+10 | 0.73 | 1299.30 | 09-DEC-09:40 | 0.92 |
Annual Sum or Average | 0.319080E+11 | 0.73 | |||
Minimum of Months | 0.244774E+10 | 0.72 | 1299.30 | 0.91 | |
Maximum of Months | 0.271000E+10 | 0.73 | 1299.30 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303227E+11 | 0.78 | 17097.28 | 13-JAN-19:20 | 0.98 |
February | 0.280349E+11 | 0.79 | 17378.85 | 24-FEB-19:40 | 0.98 |
March | 0.327419E+11 | 0.81 | 18798.46 | 28-MAR-21:10 | 1.03 |
April | 0.331219E+11 | 0.83 | 25174.80 | 18-APR-21:10 | 1.22 |
May | 0.359214E+11 | 0.84 | 26671.86 | 31-MAY-21:10 | 1.26 |
June | 0.367786E+11 | 0.87 | 28243.40 | 30-JUN-21:10 | 1.31 |
July | 0.385588E+11 | 0.87 | 27637.72 | 27-JUL-21:10 | 1.29 |
August | 0.388051E+11 | 0.88 | 29430.93 | 22-AUG-21:10 | 1.34 |
September | 0.363137E+11 | 0.86 | 31366.29 | 08-SEP-21:10 | 1.39 |
October | 0.349419E+11 | 0.84 | 26030.37 | 20-OCT-21:10 | 1.25 |
November | 0.320747E+11 | 0.81 | 22138.05 | 03-NOV-21:10 | 1.14 |
December | 0.314886E+11 | 0.79 | 18320.09 | 04-DEC-21:10 | 1.02 |
Annual Sum or Average | 0.409104E+12 | 0.83 | |||
Minimum of Months | 0.280349E+11 | 0.78 | 17097.28 | 0.98 | |
Maximum of Months | 0.388051E+11 | 0.88 | 31366.29 | 1.39 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:10 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:05 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.770409E+09 | 0.54 | 880.28 | 01-JAN-09:02 | 0.60 |
February | 0.534805E+09 | 0.51 | 880.28 | 01-FEB-02:50 | 0.61 |
March | 0.293908E+09 | 0.46 | 880.28 | 01-MAR-09:02 | 0.60 |
April | 0.253394E+09 | 0.49 | 880.28 | 01-APR-08:62 | 0.60 |
May | 0.229218E+09 | 0.51 | 880.28 | 01-MAY-15:01 | 0.60 |
June | 0.361120E+09 | 0.54 | 880.28 | 01-JUN-08:61 | 0.60 |
July | 0.438755E+09 | 0.57 | 880.28 | 01-JUL-08:61 | 0.60 |
August | 0.392368E+09 | 0.56 | 880.28 | 01-AUG-08:61 | 0.60 |
September | 0.290233E+09 | 0.52 | 880.28 | 01-SEP-08:62 | 0.60 |
October | 0.189082E+09 | 0.46 | 880.28 | 01-OCT-15:01 | 0.60 |
November | 0.357627E+09 | 0.48 | 880.28 | 03-NOV-15:01 | 0.60 |
December | 0.570738E+09 | 0.52 | 880.28 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.468166E+10 | 0.51 | |||
Minimum of Months | 0.189082E+09 | 0.46 | 880.28 | 0.60 | |
Maximum of Months | 0.770409E+09 | 0.57 | 880.28 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.881256E+09 | 0.58 | 854.09 | 01-JAN-09:02 | 0.60 |
February | 0.602861E+09 | 0.53 | 854.09 | 01-FEB-00:12 | 0.61 |
March | 0.313770E+09 | 0.47 | 854.09 | 01-MAR-09:02 | 0.60 |
April | 0.217562E+09 | 0.44 | 854.09 | 01-APR-08:62 | 0.60 |
May | 0.158109E+09 | 0.41 | 854.09 | 01-MAY-15:01 | 0.60 |
June | 0.283623E+09 | 0.43 | 854.09 | 01-JUN-08:61 | 0.60 |
July | 0.330234E+09 | 0.41 | 854.09 | 01-JUL-08:51 | 0.60 |
August | 0.273195E+09 | 0.41 | 854.09 | 01-AUG-08:51 | 0.60 |
September | 0.199671E+09 | 0.42 | 854.09 | 01-SEP-08:51 | 0.60 |
October | 0.182761E+09 | 0.42 | 854.09 | 01-OCT-15:01 | 0.60 |
November | 0.404129E+09 | 0.49 | 854.09 | 01-NOV-08:62 | 0.60 |
December | 0.627290E+09 | 0.56 | 854.09 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.447446E+10 | 0.46 | |||
Minimum of Months | 0.158109E+09 | 0.41 | 854.09 | 0.60 | |
Maximum of Months | 0.881256E+09 | 0.58 | 854.09 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.800264E+09 | 0.25 | 1495.63 | 19-JAN-05:00 | 0.61 |
February | 0.185433E+09 | 0.06 | 1323.69 | 04-FEB-06:00 | 0.61 |
March | 0.145618E+09 | 0.08 | 1071.89 | 24-MAR-13:10 | 0.60 |
April | 0.442340E+09 | 0.20 | 1575.10 | 15-APR-13:30 | 0.60 |
May | 0.904126E+09 | 0.45 | 1217.83 | 06-MAY-13:00 | 0.60 |
June | 0.124586E+10 | 0.52 | 1234.82 | 26-JUN-12:50 | 0.60 |
July | 0.153824E+10 | 0.59 | 1325.00 | 30-JUL-13:30 | 0.60 |
August | 0.157708E+10 | 0.59 | 1476.80 | 29-AUG-13:30 | 0.60 |
September | 0.130719E+10 | 0.46 | 2525.71 | 07-SEP-12:50 | 0.60 |
October | 0.640541E+09 | 0.28 | 1698.12 | 20-OCT-12:40 | 0.60 |
November | 0.264609E+09 | 0.13 | 1621.24 | 04-NOV-12:30 | 0.60 |
December | 0.571820E+09 | 0.20 | 1277.40 | 12-DEC-05:00 | 0.61 |
Annual Sum or Average | 0.962312E+10 | 0.32 | |||
Minimum of Months | 0.145618E+09 | 0.06 | 1071.89 | 0.60 | |
Maximum of Months | 0.157708E+10 | 0.59 | 2525.71 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.400156E+10 | 0.50 | 4475.19 | 01-JAN-16:02 | 0.60 |
February | 0.286795E+10 | 0.47 | 4475.19 | 01-FEB-00:01 | 0.61 |
March | 0.121947E+10 | 0.42 | 4475.19 | 01-MAR-09:02 | 0.60 |
April | 0.918333E+09 | 0.40 | 4475.19 | 01-APR-15:02 | 0.60 |
May | 0.131185E+10 | 0.37 | 4475.19 | 01-MAY-08:61 | 0.60 |
June | 0.199397E+10 | 0.39 | 4475.19 | 01-JUN-08:61 | 0.60 |
July | 0.212078E+10 | 0.37 | 4475.19 | 01-JUL-08:51 | 0.60 |
August | 0.182526E+10 | 0.36 | 4475.19 | 01-AUG-08:51 | 0.60 |
September | 0.123545E+10 | 0.38 | 4475.19 | 01-SEP-08:51 | 0.60 |
October | 0.681798E+09 | 0.41 | 4475.19 | 01-OCT-08:61 | 0.60 |
November | 0.158445E+10 | 0.44 | 4475.19 | 01-NOV-15:01 | 0.60 |
December | 0.264847E+10 | 0.46 | 4475.19 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.224093E+11 | 0.41 | |||
Minimum of Months | 0.681798E+09 | 0.36 | 4475.19 | 0.60 | |
Maximum of Months | 0.400156E+10 | 0.50 | 4475.19 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.735325E+09 | 0.54 | 799.74 | 01-JAN-09:02 | 0.60 |
February | 0.504545E+09 | 0.50 | 799.74 | 01-FEB-01:15 | 0.61 |
March | 0.271242E+09 | 0.46 | 799.74 | 01-MAR-09:02 | 0.60 |
April | 0.232807E+09 | 0.50 | 799.74 | 01-APR-08:62 | 0.60 |
May | 0.235022E+09 | 0.54 | 799.74 | 01-MAY-08:61 | 0.60 |
June | 0.357912E+09 | 0.56 | 799.74 | 01-JUN-08:61 | 0.60 |
July | 0.417594E+09 | 0.58 | 799.74 | 01-JUL-08:61 | 0.60 |
August | 0.367064E+09 | 0.57 | 799.74 | 01-AUG-08:61 | 0.60 |
September | 0.281130E+09 | 0.54 | 799.74 | 01-SEP-08:62 | 0.60 |
October | 0.171856E+09 | 0.47 | 799.74 | 01-OCT-08:61 | 0.60 |
November | 0.342560E+09 | 0.48 | 799.74 | 03-NOV-15:01 | 0.60 |
December | 0.541935E+09 | 0.52 | 799.74 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.445899E+10 | 0.52 | |||
Minimum of Months | 0.171856E+09 | 0.46 | 799.74 | 0.60 | |
Maximum of Months | 0.735325E+09 | 0.58 | 799.74 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.833848E+09 | 0.58 | 776.43 | 01-JAN-09:02 | 0.60 |
February | 0.583777E+09 | 0.53 | 776.43 | 01-FEB-00:01 | 0.61 |
March | 0.290906E+09 | 0.45 | 776.43 | 01-MAR-09:02 | 0.60 |
April | 0.205178E+09 | 0.44 | 776.43 | 01-APR-08:62 | 0.60 |
May | 0.175930E+09 | 0.44 | 776.43 | 01-MAY-08:61 | 0.60 |
June | 0.290342E+09 | 0.45 | 776.43 | 01-JUN-08:61 | 0.60 |
July | 0.317945E+09 | 0.42 | 776.43 | 01-JUL-08:32 | 0.60 |
August | 0.262588E+09 | 0.42 | 776.43 | 01-AUG-08:32 | 0.60 |
September | 0.195020E+09 | 0.44 | 776.43 | 01-SEP-08:51 | 0.60 |
October | 0.166789E+09 | 0.41 | 776.43 | 01-OCT-08:61 | 0.60 |
November | 0.382778E+09 | 0.50 | 776.43 | 09-NOV-16:02 | 0.60 |
December | 0.609733E+09 | 0.57 | 776.43 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.431483E+10 | 0.47 | |||
Minimum of Months | 0.166789E+09 | 0.41 | 776.43 | 0.60 | |
Maximum of Months | 0.833848E+09 | 0.58 | 776.43 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.233478E+09 | 0.57 | 228.95 | 01-JAN-09:02 | 0.60 |
February | 0.155976E+09 | 0.53 | 228.95 | 01-FEB-01:50 | 0.61 |
March | 89414743.25 | 0.47 | 228.95 | 01-MAR-09:02 | 0.60 |
April | 74509076.94 | 0.49 | 228.95 | 01-APR-08:62 | 0.60 |
May | 61619976.67 | 0.51 | 228.95 | 01-MAY-15:01 | 0.60 |
June | 95200096.67 | 0.54 | 228.95 | 01-JUN-08:61 | 0.60 |
July | 0.112953E+09 | 0.56 | 228.95 | 01-JUL-08:61 | 0.60 |
August | 98737443.55 | 0.56 | 228.95 | 01-AUG-08:61 | 0.59 |
September | 76851433.66 | 0.52 | 228.95 | 01-SEP-15:01 | 0.60 |
October | 58288808.17 | 0.46 | 228.95 | 01-OCT-15:01 | 0.60 |
November | 0.112811E+09 | 0.49 | 228.95 | 01-NOV-08:62 | 0.60 |
December | 0.175427E+09 | 0.54 | 228.95 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.134527E+10 | 0.52 | |||
Minimum of Months | 58288808.17 | 0.46 | 228.95 | 0.59 | |
Maximum of Months | 0.233478E+09 | 0.57 | 228.95 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.262946E+09 | 0.59 | 221.54 | 01-JAN-09:02 | 0.60 |
February | 0.175882E+09 | 0.56 | 221.54 | 01-FEB-00:01 | 0.61 |
March | 97012291.00 | 0.49 | 221.54 | 01-MAR-09:02 | 0.60 |
April | 64673188.93 | 0.45 | 221.54 | 01-APR-08:62 | 0.60 |
May | 43355623.74 | 0.41 | 221.54 | 01-MAY-15:01 | 0.60 |
June | 77740007.55 | 0.43 | 221.54 | 01-JUN-08:61 | 0.60 |
July | 88385053.55 | 0.41 | 221.54 | 01-JUL-08:51 | 0.60 |
August | 70239455.78 | 0.41 | 221.54 | 01-AUG-08:51 | 0.59 |
September | 54121592.28 | 0.42 | 221.54 | 01-SEP-08:51 | 0.60 |
October | 57337119.60 | 0.42 | 221.54 | 01-OCT-15:01 | 0.60 |
November | 0.124344E+09 | 0.52 | 221.54 | 01-NOV-08:62 | 0.60 |
December | 0.199320E+09 | 0.58 | 221.54 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.131536E+10 | 0.47 | |||
Minimum of Months | 43355623.74 | 0.41 | 221.54 | 0.59 | |
Maximum of Months | 0.262946E+09 | 0.59 | 221.54 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.791163E+09 | 0.51 | 1054.54 | 01-JAN-09:02 | 0.60 |
February | 0.535943E+09 | 0.48 | 1054.54 | 01-FEB-05:50 | 0.61 |
March | 0.350305E+09 | 0.49 | 1054.54 | 01-MAR-09:02 | 0.60 |
April | 0.329708E+09 | 0.50 | 1054.54 | 01-APR-08:62 | 0.60 |
May | 0.289751E+09 | 0.52 | 1054.54 | 01-MAY-15:01 | 0.60 |
June | 0.404691E+09 | 0.54 | 1054.54 | 01-JUN-08:61 | 0.60 |
July | 0.486036E+09 | 0.56 | 1054.54 | 01-JUL-08:61 | 0.60 |
August | 0.485278E+09 | 0.56 | 1054.54 | 01-AUG-08:61 | 0.59 |
September | 0.429480E+09 | 0.53 | 1054.54 | 01-SEP-08:62 | 0.60 |
October | 0.300164E+09 | 0.50 | 1054.54 | 01-OCT-08:61 | 0.60 |
November | 0.404811E+09 | 0.48 | 1054.54 | 01-NOV-15:01 | 0.60 |
December | 0.646389E+09 | 0.53 | 1054.54 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.545372E+10 | 0.52 | |||
Minimum of Months | 0.289751E+09 | 0.48 | 1054.54 | 0.59 | |
Maximum of Months | 0.791163E+09 | 0.56 | 1054.54 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.268175E+10 | 0.241358E+10 | 1819.07 | 19-JAN-04:50 | 1637.17 | 1637.17 | 35.27 | 5.82 |
February | 0.184157E+10 | 0.165742E+10 | 1802.74 | 04-FEB-06:00 | 1622.47 | 1622.47 | 34.43 | 5.78 |
March | 0.122684E+10 | 0.110415E+10 | 1151.17 | 05-MAR-19:02 | 1036.06 | 1036.06 | 32.60 | 1.94 |
April | 0.674566E+09 | 0.607110E+09 | 1007.01 | 03-APR-08:62 | 906.31 | 906.31 | 32.03 | 1.52 |
May | 0.331533E+09 | 0.298379E+09 | 926.58 | 01-MAY-08:04 | 833.93 | 833.93 | 32.94 | 1.33 |
June | 0.191994E+09 | 0.172794E+09 | 831.87 | 03-JUN-08:03 | 748.69 | 748.69 | 31.33 | 1.13 |
July | 33588224.85 | 30229402.37 | 469.95 | 24-JUL-05:00 | 422.96 | 422.96 | 28.95 | 0.55 |
August | 77339004.38 | 69605103.94 | 659.12 | 07-AUG-06:00 | 593.21 | 593.21 | 30.71 | 0.83 |
September | 0.339712E+09 | 0.305741E+09 | 948.55 | 28-SEP-08:04 | 853.70 | 853.70 | 41.03 | 1.37 |
October | 0.784274E+09 | 0.705847E+09 | 979.16 | 03-OCT-08:07 | 881.25 | 881.25 | 33.81 | 1.45 |
November | 0.135584E+10 | 0.122025E+10 | 1691.73 | 26-NOV-06:50 | 1522.56 | 1522.56 | 34.58 | 5.45 |
December | 0.211091E+10 | 0.189982E+10 | 1347.00 | 11-DEC-09:03 | 1212.30 | 1212.30 | 35.80 | 2.97 |
Annual Sum or Average | 0.116499E+11 | 0.104849E+11 | ||||||
Minimum of Months | 33588224.85 | 30229402.37 | 469.95 | 422.96 | 422.96 | 28.95 | 0.55 | |
Maximum of Months | 0.268175E+10 | 0.241358E+10 | 1819.07 | 1637.17 | 1637.17 | 41.03 | 5.82 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 104470.14 | 94023.12 | 7.34 | 12-JAN-09:04 | 6.60 | 6.60 | 6.72 | 1.19 |
February | 342954.40 | 308658.96 | 29.18 | 25-FEB-09:02 | 26.27 | 26.27 | 6.72 | 2.79 |
March | 4012505.17 | 3611254.65 | 154.09 | 25-MAR-15:01 | 138.68 | 138.68 | 6.72 | 6.68 |
April | 59404740.55 | 53464266.50 | 609.91 | 16-APR-18:03 | 548.92 | 548.92 | 6.72 | 12.59 |
May | 0.116421E+09 | 0.104779E+09 | 650.66 | 31-MAY-18:03 | 585.59 | 585.59 | 6.72 | 12.96 |
June | 0.398961E+09 | 0.359065E+09 | 1012.00 | 26-JUN-18:03 | 910.80 | 910.80 | 6.72 | 15.67 |
July | 0.562147E+09 | 0.505932E+09 | 1431.25 | 26-JUL-18:02 | 1288.13 | 1288.13 | 6.72 | 18.14 |
August | 0.477495E+09 | 0.429745E+09 | 1203.46 | 03-AUG-18:02 | 1083.11 | 1083.11 | 6.72 | 16.87 |
September | 0.194049E+09 | 0.174644E+09 | 699.58 | 06-SEP-18:02 | 629.62 | 629.62 | 6.72 | 13.37 |
October | 19040007.28 | 17136006.55 | 319.17 | 20-OCT-15:01 | 287.25 | 287.25 | 6.72 | 9.42 |
November | 3965502.34 | 3568952.10 | 145.18 | 03-NOV-15:01 | 130.66 | 130.66 | 6.72 | 6.49 |
December | 219490.84 | 197541.76 | 9.89 | 03-DEC-09:02 | 8.90 | 8.90 | 6.72 | 1.45 |
Annual Sum or Average | 0.183616E+10 | 0.165255E+10 | ||||||
Minimum of Months | 104470.14 | 94023.12 | 7.34 | 6.60 | 6.60 | 6.72 | 1.19 | |
Maximum of Months | 0.562147E+09 | 0.505932E+09 | 1431.25 | 1288.13 | 1288.13 | 6.72 | 18.14 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.613206E+09 | 0.551885E+09 | 3368.87 | 01-JAN-09:02 | 3031.98 | 3031.98 | 6.74 | 29.80 |
February | 0.110156E+10 | 0.991406E+09 | 3368.87 | 01-FEB-16:02 | 3031.98 | 3031.98 | 6.77 | 29.80 |
March | 0.306617E+10 | 0.275956E+10 | 3368.87 | 01-MAR-19:05 | 3031.98 | 3031.98 | 6.77 | 29.80 |
April | 0.506957E+10 | 0.456261E+10 | 3368.87 | 01-APR-08:62 | 3031.98 | 3031.98 | 6.91 | 29.80 |
May | 0.882908E+10 | 0.794617E+10 | 3368.87 | 01-MAY-00:05 | 3031.98 | 3031.98 | 6.77 | 29.80 |
June | 0.859078E+10 | 0.773170E+10 | 3368.87 | 01-JUN-00:05 | 3031.98 | 3031.98 | 7.12 | 29.80 |
July | 0.902318E+10 | 0.812086E+10 | 3368.87 | 01-JUL-00:10 | 3031.98 | 3031.98 | 7.90 | 29.80 |
August | 0.902318E+10 | 0.812086E+10 | 3368.87 | 01-AUG-00:05 | 3031.98 | 3031.98 | 8.51 | 29.80 |
September | 0.805159E+10 | 0.724643E+10 | 3368.87 | 01-SEP-00:05 | 3031.98 | 3031.98 | 7.53 | 29.80 |
October | 0.604392E+10 | 0.543953E+10 | 3368.87 | 01-OCT-06:30 | 3031.98 | 3031.98 | 6.73 | 29.80 |
November | 0.260705E+10 | 0.234634E+10 | 3368.87 | 01-NOV-05:15 | 3031.98 | 3031.98 | 6.74 | 29.80 |
December | 0.977405E+09 | 0.879664E+09 | 3368.87 | 01-DEC-09:04 | 3031.98 | 3031.98 | 6.82 | 29.80 |
Annual Sum or Average | 0.629967E+11 | 0.566970E+11 | ||||||
Minimum of Months | 0.613206E+09 | 0.551885E+09 | 3368.87 | 3031.98 | 3031.98 | 6.73 | 29.80 | |
Maximum of Months | 0.902318E+10 | 0.812086E+10 | 3368.87 | 3031.98 | 3031.98 | 8.51 | 29.80 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 47.05 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 46.48 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.17 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.90 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.36 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 51.60 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.11 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.28 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 51.87 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.54 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.48 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.35 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.48 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.28 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 43.19 | 60.00 | 185673.30 | 611675.43 | 31-JAN-04:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 35.56 | 60.00 | 141876.52 | 645301.33 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 37.31 | 60.00 | 52585.61 | 222647.56 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.12 | 60.00 | 28648.41 | 177425.35 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31.33 | 60.00 | 17679.41 | 150108.75 | 01-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.11 | 60.00 | 10886.45 | 135613.32 | 03-JUN-08:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 38.76 | 38.76 | 1898.02 | 71332.15 | 24-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.01 | 33.01 | 4386.14 | 101395.95 | 07-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 32.26 | 32.26 | 17503.02 | 138257.37 | 27-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.72 | 60.00 | 33877.06 | 171556.54 | 17-OCT-18:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 50.74 | 60.00 | 70141.37 | 581464.02 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 43.30 | 60.00 | 108075.81 | 302935.94 | 09-DEC-09:08 |
Annual Sum or Average | 0.00 | 55663.99 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.11 | 32.26 | 1898.02 | 71332.15 | ||
Maximum of Months | 0.00 | 0.00 | 51.72 | 60.00 | 185673.30 | 645301.33 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372.45 | 21695.72 | 12-JAN-16:01 | 6.87 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 923.46 | 40817.81 | 25-FEB-16:03 | 7.03 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 5157.70 | 236684.08 | 25-MAR-15:01 | 8.59 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 34547.23 | 487286.14 | 18-APR-15:03 | 10.60 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75331.38 | 493886.50 | 30-MAY-18:03 | 10.66 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 188662.66 | 607262.89 | 26-JUN-18:03 | 11.56 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 252009.29 | 745305.44 | 26-JUL-18:02 | 12.67 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221202.22 | 705473.09 | 21-AUG-21:51 | 12.35 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 102105.79 | 517118.93 | 06-SEP-15:03 | 10.84 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17904.96 | 369903.73 | 20-OCT-15:01 | 9.66 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4743.51 | 172971.54 | 03-NOV-15:01 | 8.08 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 672.22 | 24821.09 | 03-DEC-09:02 | 6.90 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 75835.04 | 0.00 | ||||||
Minimum of Months | 372.45 | 21695.72 | 6.87 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 252009.29 | 745305.44 | 12.67 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.05 | 59.35 | 31396.84 | 64793.86 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.48 | 58.82 | 32007.31 | 65238.63 | 21-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.17 | 59.46 | 31722.50 | 65141.60 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.90 | 59.56 | 30540.14 | 63282.09 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.36 | 58.39 | 28814.61 | 60291.79 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 51.60 | 59.78 | 26999.88 | 56312.65 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.11 | 59.11 | 25549.31 | 52640.87 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.28 | 59.06 | 24922.80 | 50605.86 | 01-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.87 | 58.43 | 25230.32 | 51750.50 | 29-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.54 | 59.39 | 26409.82 | 55097.21 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.48 | 59.24 | 28147.18 | 58905.64 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.35 | 59.65 | 29964.86 | 62344.12 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 28454.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.48 | 58.39 | 24922.80 | 50605.86 | ||
Maximum of Months | 0.00 | 0.00 | 52.28 | 59.78 | 32007.31 | 65238.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.360150E+12 | 0.00 | 1491782.44 | 0.303227E+11 | 0.00 | 0.00 |
February | 0.253999E+12 | 0.00 | 569732.18 | 0.280349E+11 | 0.00 | 0.00 |
March | 0.100526E+12 | 0.00 | 0.290482E+10 | 0.327419E+11 | 0.00 | 0.00 |
April | 0.592241E+11 | 0.00 | 0.458794E+11 | 0.331219E+11 | 0.00 | 0.00 |
May | 0.466216E+11 | 0.00 | 0.106678E+12 | 0.359214E+11 | 0.00 | 0.00 |
June | 0.280000E+11 | 0.00 | 0.328153E+12 | 0.367786E+11 | 0.00 | 0.00 |
July | 0.507782E+10 | 0.00 | 0.476320E+12 | 0.385588E+11 | 0.00 | 0.00 |
August | 0.117493E+11 | 0.00 | 0.412070E+12 | 0.388051E+11 | 0.00 | 0.00 |
September | 0.431797E+11 | 0.00 | 0.151035E+12 | 0.363137E+11 | 0.00 | 0.00 |
October | 0.793083E+11 | 0.00 | 0.103039E+11 | 0.349419E+11 | 0.00 | 0.00 |
November | 0.129414E+12 | 0.00 | 0.452982E+09 | 0.320747E+11 | 0.00 | 0.00 |
December | 0.187213E+12 | 0.00 | 0.00 | 0.314886E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.130446E+13 | 0.00 | 0.153380E+13 | 0.409104E+12 | 0.00 | 0.00 |
Minimum of Months | 0.507782E+10 | 0.00 | 0.00 | 0.280349E+11 | 0.00 | 0.00 |
Maximum of Months | 0.360150E+12 | 0.00 | 0.476320E+12 | 0.388051E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.163770E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.111491E+11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.235863E+10 | 0.00 | 0.213301E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.439575E+09 | 0.00 | 0.323797E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 10306.48 | 0.00 | 0.744936E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 14991.45 | 0.00 | 0.240232E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 13312.96 | 0.00 | 0.362691E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 13777.61 | 0.00 | 0.297117E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 296263.34 | 0.00 | 0.108269E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 21341119.14 | 0.00 | 0.651762E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.387191E+10 | 0.00 | 24319556.63 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.695629E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.411742E+11 | 0.00 | 0.112408E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 10306.48 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.163770E+11 | 0.00 | 0.362691E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303227E+11 | 1491782.44 | 0.360150E+12 | 0.801361E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280349E+11 | 569732.18 | 0.253999E+12 | 0.598869E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327419E+11 | 0.290482E+10 | 0.100526E+12 | 0.583627E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331219E+11 | 0.458794E+11 | 0.592241E+11 | 0.340436E+12 | 0.621984E+10 | 0.00 | 0.00 | 0.00 |
May | 0.359214E+11 | 0.106678E+12 | 0.466216E+11 | 0.608473E+11 | 0.467738E+10 | 0.00 | 0.00 | 0.00 |
June | 0.367786E+11 | 0.328153E+12 | 0.280000E+11 | 0.866449E+10 | 0.555946E+11 | 0.00 | 0.00 | 0.00 |
July | 0.385588E+11 | 0.476320E+12 | 0.507782E+10 | 0.720376E+09 | 0.651081E+11 | 0.00 | 0.00 | 0.00 |
August | 0.388051E+11 | 0.412070E+12 | 0.117493E+11 | 0.125975E+10 | 0.566580E+11 | 0.00 | 0.00 | 0.00 |
September | 0.363137E+11 | 0.151035E+12 | 0.431797E+11 | 0.751979E+11 | 0.949000E+10 | 0.00 | 0.00 | 0.00 |
October | 0.349419E+11 | 0.103039E+11 | 0.793083E+11 | 0.282531E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320747E+11 | 0.452982E+09 | 0.129414E+12 | 0.533669E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314886E+11 | 0.00 | 0.187213E+12 | 0.844348E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409104E+12 | 0.153380E+13 | 0.130446E+13 | 0.413153E+13 | 0.197748E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280349E+11 | 0.00 | 0.507782E+10 | 0.720376E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388051E+11 | 0.476320E+12 | 0.360150E+12 | 0.844348E+12 | 0.651081E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.163770E+11 | 0.672399E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.111491E+11 | 0.499803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.213301E+09 | 0.235863E+10 | 0.511586E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.323797E+10 | 0.439575E+09 | 0.316668E+11 | 0.733433E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.744936E+10 | 10306.48 | 0.102271E+11 | 0.665303E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.240232E+11 | 14991.45 | 0.338664E+10 | 0.657053E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.362691E+11 | 13312.96 | 0.464556E+09 | 0.790040E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.297117E+11 | 13777.61 | 0.114760E+10 | 0.693841E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.108269E+11 | 296263.34 | 0.108150E+11 | 0.167068E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.651762E+09 | 21341119.14 | 0.307600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 24319556.63 | 0.387191E+10 | 0.466679E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.695629E+10 | 0.705546E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.112408E+12 | 0.411742E+11 | 0.374069E+12 | 0.244788E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 10306.48 | 0.464556E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.362691E+11 | 0.163770E+11 | 0.705546E+11 | 0.790040E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.303227E+11 | 0.360150E+12 | 1491782.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280349E+11 | 0.253999E+12 | 569732.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327419E+11 | 0.100526E+12 | 0.290482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331219E+11 | 0.592241E+11 | 0.458794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359214E+11 | 0.466216E+11 | 0.106678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.367786E+11 | 0.280000E+11 | 0.328153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.385588E+11 | 0.507782E+10 | 0.476320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.388051E+11 | 0.117493E+11 | 0.412070E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363137E+11 | 0.431797E+11 | 0.151035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349419E+11 | 0.793083E+11 | 0.103039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320747E+11 | 0.129414E+12 | 0.452982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314886E+11 | 0.187213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409104E+12 | 0.130446E+13 | 0.153380E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280349E+11 | 0.507782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388051E+11 | 0.360150E+12 | 0.476320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.163770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.111491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.235863E+10 | 0.213301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.439575E+09 | 0.323797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 10306.48 | 0.744936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 14991.45 | 0.240232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 13312.96 | 0.362691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 13777.61 | 0.297117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 296263.34 | 0.108269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 21341119.14 | 0.651762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.387191E+10 | 24319556.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.695629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.411742E+11 | 0.112408E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 10306.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.163770E+11 | 0.362691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600108E+11 | 0.00 | 0.00 | 2262873.28 | 0.00 | 0.973383E+10 | 0.580560E+10 | 0.00 | 0.98 |
February | 0.364025E+11 | 0.00 | 0.00 | 3624.43 | 0.00 | 0.257749E+11 | 0.159820E+09 | 0.00 | 0.98 |
March | 0.510462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
April | 0.441953E+11 | 0.00 | 0.00 | 0.00 | 0.474923E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.413910E+11 | 0.00 | 0.00 | 0.00 | 0.570852E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
June | 0.243968E+11 | 0.00 | 0.00 | 8424.18 | 0.535648E+10 | 0.00 | 0.168823E+09 | 0.00 | 0.99 |
July | 0.120199E+11 | 0.154879E+10 | 0.00 | 3320583.52 | 0.712169E+10 | 0.00 | 0.266317E+10 | 0.00 | 0.99 |
August | 0.258367E+10 | 0.312998E+10 | 0.00 | 28054192.39 | 0.477646E+10 | 0.00 | 0.181542E+11 | 0.00 | 1.02 |
September | 0.191395E+10 | 0.299948E+09 | 0.00 | 56076040.73 | 0.220685E+09 | 0.00 | 0.383899E+11 | 0.00 | 1.07 |
October | 0.218431E+10 | 0.00 | 0.00 | 62462164.19 | 0.00 | 0.00 | 0.549570E+11 | 0.00 | 1.09 |
November | 0.104524E+11 | 0.00 | 0.00 | 50466225.30 | 0.00 | 0.00 | 0.467451E+11 | 0.00 | 1.07 |
December | 0.184119E+11 | 0.00 | 0.00 | 32687260.53 | 0.00 | 0.00 | 0.409924E+11 | 0.00 | 1.02 |
Annual Sum or Average | 0.305009E+12 | 0.497871E+10 | 0.00 | 0.235341E+09 | 0.185211E+11 | 0.355087E+11 | 0.208036E+12 | 0.00 | 1.01 |
Minimum of Months | 0.191395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
Maximum of Months | 0.600108E+11 | 0.312998E+10 | 0.00 | 62462164.19 | 0.712169E+10 | 0.257749E+11 | 0.549570E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177475E+10 | 0.00 | 0.00 | 57838.51 | 0.00 | 0.987593E+10 | 0.140096E+09 | 0.00 | 2.76 |
February | 0.259671E+10 | 0.00 | 0.00 | 258705.46 | 0.00 | 0.692037E+10 | 0.235002E+09 | 0.00 | 2.78 |
March | 0.497375E+10 | 0.00 | 0.00 | 358251.18 | 0.00 | 0.263357E+10 | 0.369323E+09 | 0.00 | 2.79 |
April | 0.524324E+10 | 87511861.30 | 0.00 | 644306.32 | 5709652.82 | 0.113158E+10 | 0.541243E+09 | 0.00 | 2.82 |
May | 0.621717E+10 | 55899188.73 | 0.00 | 415405.20 | 35565531.91 | 0.00 | 0.244395E+09 | 0.00 | 2.80 |
June | 0.365657E+10 | 0.616052E+09 | 0.00 | 366122.62 | 0.262438E+09 | 0.00 | 0.177060E+09 | 0.00 | 2.84 |
July | 0.213161E+10 | 0.922149E+09 | 0.00 | 510266.36 | 0.484693E+09 | 0.00 | 0.161716E+09 | 0.00 | 2.87 |
August | 0.276084E+10 | 0.811076E+09 | 0.00 | 1261324.11 | 0.472420E+09 | 0.00 | 0.387409E+09 | 0.00 | 2.91 |
September | 0.511378E+10 | 0.105784E+09 | 0.00 | 2381537.44 | 3931084.56 | 44838526.04 | 0.661711E+09 | 0.00 | 2.96 |
October | 0.703141E+10 | 0.00 | 0.00 | 1609766.29 | 0.00 | 0.183152E+09 | 0.104042E+10 | 0.00 | 2.85 |
November | 0.441386E+10 | 0.00 | 0.00 | 500003.11 | 0.00 | 0.360589E+10 | 0.342760E+09 | 0.00 | 2.80 |
December | 0.201218E+10 | 0.00 | 0.00 | 218439.61 | 0.00 | 0.661218E+10 | 0.277322E+09 | 0.00 | 2.76 |
Annual Sum or Average | 0.479259E+11 | 0.259847E+10 | 0.00 | 8581966.23 | 0.126476E+10 | 0.310075E+11 | 0.457845E+10 | 0.00 | 2.83 |
Minimum of Months | 0.177475E+10 | 0.00 | 0.00 | 57838.51 | 0.00 | 0.00 | 0.140096E+09 | 0.00 | 2.76 |
Maximum of Months | 0.703141E+10 | 0.922149E+09 | 0.00 | 2381537.44 | 0.484693E+09 | 0.987593E+10 | 0.104042E+10 | 0.00 | 2.96 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.476123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214897E+10 | 0.00 | 0.00 | 1.40 |
February | 0.348869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221287E+10 | 0.00 | 0.00 | 1.40 |
March | 0.459033E+10 | 0.00 | 0.00 | 18575.46 | 0.00 | 0.00 | 78490376.47 | 0.00 | 1.41 |
April | 0.358862E+10 | 16162172.79 | 0.00 | 456056.08 | 27505496.09 | 0.00 | 0.466546E+09 | 0.00 | 1.42 |
May | 0.279901E+10 | 8824082.54 | 0.00 | 760677.38 | 43752202.79 | 0.00 | 0.998062E+09 | 0.00 | 1.43 |
June | 0.122521E+10 | 0.308630E+09 | 0.00 | 1651670.22 | 0.202545E+09 | 0.00 | 0.105808E+10 | 0.00 | 1.48 |
July | 0.350622E+09 | 0.588547E+09 | 0.00 | 2020618.84 | 0.265995E+09 | 0.00 | 0.102981E+10 | 0.00 | 1.50 |
August | 0.336320E+09 | 0.479830E+09 | 0.00 | 2599821.96 | 0.273654E+09 | 0.00 | 0.158714E+10 | 0.00 | 1.50 |
September | 0.197638E+10 | 36933537.86 | 0.00 | 2124770.59 | 11051605.46 | 0.00 | 0.147756E+10 | 0.00 | 1.46 |
October | 0.422511E+10 | 0.00 | 0.00 | 225333.90 | 0.00 | 0.00 | 0.523555E+09 | 0.00 | 1.41 |
November | 0.440389E+10 | 0.00 | 0.00 | 43744.81 | 0.00 | 0.308699E+09 | 0.152809E+09 | 0.00 | 1.41 |
December | 0.506081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149814E+09 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.368062E+11 | 0.143893E+10 | 0.00 | 9901269.24 | 0.824503E+09 | 0.482035E+10 | 0.737205E+10 | 0.00 | 1.43 |
Minimum of Months | 0.336320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Maximum of Months | 0.506081E+10 | 0.588547E+09 | 0.00 | 2599821.96 | 0.273654E+09 | 0.221287E+10 | 0.158714E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.609014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491398E+10 | 0.00 | 0.00 | 0.53 |
February | 0.146726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308973E+10 | 0.00 | 0.00 | 0.53 |
March | 0.272641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100518E+10 | 0.00 | 0.00 | 0.53 |
April | 0.309623E+10 | 0.00 | 0.00 | 0.00 | 34717918.60 | 0.134544E+09 | 0.00 | 0.00 | 0.53 |
May | 0.302060E+10 | 303991.55 | 0.00 | 10536.53 | 41426501.51 | 0.00 | 5159196.91 | 0.00 | 0.54 |
June | 0.172764E+10 | 0.101757E+09 | 0.00 | 164034.02 | 0.295907E+09 | 0.00 | 70855931.10 | 0.00 | 0.54 |
July | 0.952436E+09 | 0.195667E+09 | 0.00 | 308500.75 | 0.452150E+09 | 0.00 | 0.123304E+09 | 0.00 | 0.54 |
August | 0.128643E+10 | 0.189461E+09 | 0.00 | 280871.26 | 0.386185E+09 | 0.00 | 0.185421E+09 | 0.00 | 0.54 |
September | 0.261054E+10 | 2102372.23 | 0.00 | 233992.42 | 35589251.16 | 0.00 | 0.101454E+09 | 0.00 | 0.54 |
October | 0.379388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.270669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118203E+10 | 0.00 | 0.00 | 0.53 |
December | 0.129099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287362E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.252881E+11 | 0.489291E+09 | 0.00 | 997934.97 | 0.124598E+10 | 0.131991E+11 | 0.486194E+09 | 0.00 | 0.53 |
Minimum of Months | 0.609014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.379388E+10 | 0.195667E+09 | 0.00 | 308500.75 | 0.452150E+09 | 0.491398E+10 | 0.185421E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84450713.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317582E+10 | 0.00 | 0.00 | 0.54 |
February | 0.431849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225818E+10 | 0.00 | 0.00 | 0.54 |
March | 0.120170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100109E+10 | 0.00 | 0.00 | 0.54 |
April | 0.168573E+10 | 0.00 | 0.00 | 0.00 | 20494294.64 | 0.221427E+09 | 0.00 | 0.00 | 0.54 |
May | 0.178614E+10 | 0.00 | 0.00 | 0.00 | 24633879.42 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.104867E+10 | 19075550.83 | 0.00 | 47020.56 | 0.212221E+09 | 0.00 | 11500810.60 | 0.00 | 0.55 |
July | 0.627119E+09 | 43345703.82 | 0.00 | 9051.40 | 0.330937E+09 | 0.00 | 6624670.67 | 0.00 | 0.55 |
August | 0.862160E+09 | 34783413.43 | 0.00 | 12179.81 | 0.299781E+09 | 0.00 | 5396834.48 | 0.00 | 0.55 |
September | 0.159320E+10 | 120237.56 | 0.00 | 3611.09 | 22066012.98 | 0.00 | 6138141.05 | 0.00 | 0.55 |
October | 0.223956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.127295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102260E+10 | 0.00 | 0.00 | 0.54 |
December | 0.198452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225995E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.130320E+11 | 97324905.64 | 0.00 | 71862.86 | 0.910133E+09 | 0.993906E+10 | 29660456.81 | 0.00 | 0.54 |
Minimum of Months | 84450713.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.223956E+10 | 43345703.82 | 0.00 | 47020.56 | 0.330937E+09 | 0.317582E+10 | 11500810.60 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.352348E+10 | 0.00 | 0.00 | 82150334.57 | 0.00 | 0.208529E+11 | 0.881560E+11 | 0.00 | 23.13 |
February | 0.147909E+10 | 0.00 | 0.00 | 73963246.93 | 0.00 | 0.231715E+11 | 0.673689E+11 | 0.00 | 23.23 |
March | 0.243472E+09 | 0.00 | 0.00 | 94831331.89 | 0.00 | 0.00 | 0.795941E+11 | 0.00 | 24.04 |
April | 0.132766E+09 | 0.663939E+09 | 0.00 | 93454325.87 | 583822.83 | 0.00 | 0.689495E+11 | 0.00 | 23.94 |
May | 73955907.41 | 0.830759E+09 | 0.00 | 0.107497E+09 | 0.00 | 0.00 | 0.650832E+11 | 0.00 | 24.15 |
June | 23634917.56 | 0.815257E+10 | 0.00 | 81441438.05 | 1173958.72 | 0.00 | 0.379020E+11 | 0.00 | 24.16 |
July | 19072455.23 | 0.141584E+11 | 0.00 | 68636912.86 | 4315676.39 | 0.00 | 0.219240E+11 | 0.00 | 24.08 |
August | 11873177.10 | 0.122666E+11 | 0.00 | 84018882.34 | 673926.39 | 0.00 | 0.310349E+11 | 0.00 | 24.27 |
September | 80729602.17 | 0.741028E+09 | 0.00 | 0.105797E+09 | 0.00 | 0.00 | 0.583794E+11 | 0.00 | 24.14 |
October | 0.185182E+09 | 0.00 | 0.00 | 95993385.35 | 0.00 | 0.00 | 0.809206E+11 | 0.00 | 24.02 |
November | 0.985129E+09 | 0.00 | 0.00 | 89357661.95 | 0.00 | 0.259060E+10 | 0.788019E+11 | 0.00 | 23.84 |
December | 0.610753E+09 | 0.00 | 0.00 | 92475298.48 | 0.00 | 0.00 | 0.876315E+11 | 0.00 | 23.52 |
Annual Sum or Average | 0.736914E+10 | 0.368133E+11 | 0.00 | 0.106962E+10 | 6747384.33 | 0.466149E+11 | 0.765746E+12 | 0.00 | 23.88 |
Minimum of Months | 11873177.10 | 0.00 | 0.00 | 68636912.86 | 0.00 | 0.00 | 0.219240E+11 | 0.00 | 23.13 |
Maximum of Months | 0.352348E+10 | 0.141584E+11 | 0.00 | 0.107497E+09 | 4315676.39 | 0.231715E+11 | 0.881560E+11 | 0.00 | 24.27 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319114E+11 | 0.00 | 0.00 | 711458.27 | 0.00 | 0.153637E+11 | 0.146812E+10 | 0.00 | 4.06 |
February | 0.230633E+11 | 0.00 | 0.00 | 2247179.89 | 0.00 | 0.136832E+11 | 0.357059E+10 | 0.00 | 4.09 |
March | 0.241575E+11 | 0.00 | 0.00 | 5025014.89 | 0.00 | 0.00 | 0.883829E+10 | 0.00 | 4.11 |
April | 0.155688E+11 | 0.349140E+09 | 0.00 | 10877983.46 | 10194996.07 | 0.00 | 0.130430E+11 | 0.00 | 4.15 |
May | 0.909100E+10 | 0.317182E+09 | 0.00 | 14167791.07 | 54948056.82 | 0.00 | 0.176630E+11 | 0.00 | 4.14 |
June | 0.483725E+10 | 0.315430E+10 | 0.00 | 15838523.02 | 0.430303E+09 | 0.00 | 0.111064E+11 | 0.00 | 4.22 |
July | 0.131995E+10 | 0.507263E+10 | 0.00 | 16437462.02 | 0.750363E+09 | 0.00 | 0.826027E+10 | 0.00 | 4.26 |
August | 0.154404E+10 | 0.461674E+10 | 0.00 | 23364248.49 | 0.718328E+09 | 0.00 | 0.116628E+11 | 0.00 | 4.31 |
September | 0.719857E+10 | 0.400703E+09 | 0.00 | 25907542.76 | 4643189.68 | 0.00 | 0.171107E+11 | 0.00 | 4.36 |
October | 0.142692E+11 | 0.00 | 0.00 | 14930965.96 | 0.00 | 0.00 | 0.198667E+11 | 0.00 | 4.20 |
November | 0.240325E+11 | 0.00 | 0.00 | 5004131.68 | 0.00 | 0.258866E+10 | 0.795411E+10 | 0.00 | 4.12 |
December | 0.304799E+11 | 0.00 | 0.00 | 1796142.42 | 0.00 | 0.369788E+10 | 0.264372E+10 | 0.00 | 4.06 |
Annual Sum or Average | 0.187473E+12 | 0.139107E+11 | 0.00 | 0.136308E+09 | 0.196878E+10 | 0.353335E+11 | 0.123188E+12 | 0.00 | 4.17 |
Minimum of Months | 0.131995E+10 | 0.00 | 0.00 | 711458.27 | 0.00 | 0.00 | 0.146812E+10 | 0.00 | 4.06 |
Maximum of Months | 0.319114E+11 | 0.507263E+10 | 0.00 | 25907542.76 | 0.750363E+09 | 0.153637E+11 | 0.198667E+11 | 0.00 | 4.36 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110254E+12 | 0.00 | 0.00 | 193797.95 | 0.00 | 0.400569E+11 | 0.707437E+09 | 0.00 | 1.82 |
February | 0.779397E+11 | 0.00 | 0.00 | 701462.46 | 0.00 | 0.439845E+11 | 0.267930E+10 | 0.00 | 1.82 |
March | 0.851257E+11 | 0.00 | 0.00 | 6287971.41 | 0.00 | 0.00 | 0.169171E+11 | 0.00 | 1.84 |
April | 0.591330E+11 | 0.735292E+09 | 0.00 | 23909394.26 | 0.217289E+09 | 0.00 | 0.298199E+11 | 0.00 | 1.85 |
May | 0.316758E+11 | 0.440713E+09 | 0.00 | 48559540.60 | 0.706059E+09 | 0.00 | 0.519611E+11 | 0.00 | 1.87 |
June | 0.155098E+11 | 0.838284E+10 | 0.00 | 57806939.50 | 0.277239E+10 | 0.00 | 0.352945E+11 | 0.00 | 1.94 |
July | 0.373460E+10 | 0.144219E+11 | 0.00 | 61739865.06 | 0.411995E+10 | 0.00 | 0.274210E+11 | 0.00 | 1.97 |
August | 0.395113E+10 | 0.124665E+11 | 0.00 | 78578882.27 | 0.413126E+10 | 0.00 | 0.395967E+11 | 0.00 | 1.98 |
September | 0.245617E+11 | 0.934464E+09 | 0.00 | 74586699.35 | 0.112215E+09 | 0.00 | 0.522354E+11 | 0.00 | 1.93 |
October | 0.581886E+11 | 0.00 | 0.00 | 26477887.28 | 0.00 | 0.00 | 0.458987E+11 | 0.00 | 1.84 |
November | 0.822076E+11 | 0.00 | 0.00 | 10110064.14 | 0.00 | 0.539904E+10 | 0.187519E+11 | 0.00 | 1.83 |
December | 0.112491E+12 | 0.00 | 0.00 | 156416.23 | 0.00 | 0.00 | 0.138373E+10 | 0.00 | 1.82 |
Annual Sum or Average | 0.664773E+12 | 0.373818E+11 | 0.00 | 0.389109E+09 | 0.120592E+11 | 0.894405E+11 | 0.322667E+12 | 0.00 | 1.88 |
Minimum of Months | 0.373460E+10 | 0.00 | 0.00 | 156416.23 | 0.00 | 0.00 | 0.707437E+09 | 0.00 | 1.82 |
Maximum of Months | 0.112491E+12 | 0.144219E+11 | 0.00 | 78578882.27 | 0.413126E+10 | 0.439845E+11 | 0.522354E+11 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29169560.07 | 0.00 | 0.00 | 60424.68 | 0.00 | 0.242883E+10 | 3482083.16 | 0.00 | 0.35 |
February | 32912336.69 | 0.00 | 0.00 | 521948.03 | 0.00 | 0.201635E+10 | 44592596.93 | 0.00 | 0.35 |
March | 64525035.26 | 0.00 | 0.00 | 1786693.47 | 0.00 | 0.116567E+10 | 0.223924E+09 | 0.00 | 0.36 |
April | 42676505.37 | 23954716.99 | 0.00 | 5549324.04 | 0.00 | 0.683227E+09 | 0.492351E+09 | 0.00 | 0.35 |
May | 22252948.38 | 29547633.22 | 953.59 | 10949904.78 | 0.00 | 0.104992E+09 | 0.849468E+09 | 2841.93 | 0.36 |
June | 13126239.91 | 0.307396E+09 | 90286.72 | 8097211.84 | 0.00 | 54420766.44 | 0.406589E+09 | 11359.35 | 0.36 |
July | 1732824.31 | 0.506579E+09 | 189837.50 | 6308592.79 | 0.00 | 473291.61 | 0.201859E+09 | 29543.26 | 0.36 |
August | 0.00 | 0.357240E+09 | 321029.93 | 8212069.86 | 0.00 | 566734.94 | 0.337080E+09 | 25639.97 | 0.36 |
September | 19545514.51 | 60617473.39 | 27040.97 | 8661070.43 | 0.00 | 0.208051E+09 | 0.625994E+09 | 5903.96 | 0.36 |
October | 55396421.30 | 0.00 | 0.00 | 4054345.15 | 0.00 | 0.785741E+09 | 0.511585E+09 | 0.00 | 0.35 |
November | 50428473.12 | 0.00 | 0.00 | 810394.36 | 0.00 | 0.131432E+10 | 0.172532E+09 | 0.00 | 0.35 |
December | 37573779.48 | 0.00 | 0.00 | 99799.91 | 0.00 | 0.161002E+10 | 5795734.15 | 0.00 | 0.35 |
Annual Sum or Average | 0.369340E+09 | 0.128534E+10 | 629148.70 | 55111779.31 | 0.00 | 0.103727E+11 | 0.387525E+10 | 75288.47 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 60424.68 | 0.00 | 473291.61 | 3482083.16 | 0.00 | 0.35 |
Maximum of Months | 64525035.26 | 0.506579E+09 | 321029.93 | 10949904.78 | 0.00 | 0.242883E+10 | 0.849468E+09 | 29543.26 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3214485.70 | 0.00 | 0.00 | 3897.05 | 0.00 | 0.245777E+10 | 261013.85 | 0.00 | 0.35 |
February | 17153537.79 | 0.00 | 0.00 | 187280.31 | 0.00 | 0.205778E+10 | 19008844.17 | 0.00 | 0.35 |
March | 59392072.31 | 0.00 | 0.00 | 900497.25 | 0.00 | 0.127404E+10 | 0.121404E+09 | 0.00 | 0.36 |
April | 96918627.24 | 22082405.96 | 9271.33 | 3644434.56 | 1854674.98 | 0.744421E+09 | 0.378676E+09 | 5558.09 | 0.35 |
May | 0.153633E+09 | 22665675.03 | 24431.25 | 8036252.71 | 6852017.23 | 0.106853E+09 | 0.719025E+09 | 5842.84 | 0.36 |
June | 89940770.78 | 0.272550E+09 | 176556.80 | 5527785.54 | 34722084.33 | 56845013.21 | 0.329863E+09 | 13374.96 | 0.36 |
July | 81375433.22 | 0.421782E+09 | 252085.49 | 4345834.17 | 84682935.50 | 212366.86 | 0.124415E+09 | 22035.22 | 0.36 |
August | 0.110898E+09 | 0.300359E+09 | 427382.38 | 5387933.49 | 56730214.76 | 436152.40 | 0.229097E+09 | 28467.91 | 0.36 |
September | 0.128560E+09 | 54961021.98 | 35808.69 | 5300335.56 | 5636720.64 | 0.247099E+09 | 0.481192E+09 | 9760.93 | 0.36 |
October | 97721367.96 | 0.00 | 0.00 | 1999097.40 | 0.00 | 0.939495E+09 | 0.317402E+09 | 0.00 | 0.35 |
November | 44195748.46 | 0.00 | 0.00 | 387330.94 | 0.00 | 0.141508E+10 | 78243200.39 | 0.00 | 0.35 |
December | 8074015.18 | 0.00 | 0.00 | 6920.04 | 0.00 | 0.164499E+10 | 223135.14 | 0.00 | 0.35 |
Annual Sum or Average | 0.891077E+09 | 0.109440E+10 | 925535.93 | 35727599.03 | 0.190479E+09 | 0.109450E+11 | 0.279881E+10 | 85039.95 | 0.36 |
Minimum of Months | 3214485.70 | 0.00 | 0.00 | 3897.05 | 0.00 | 212366.86 | 223135.14 | 0.00 | 0.35 |
Maximum of Months | 0.153633E+09 | 0.421782E+09 | 427382.38 | 8036252.71 | 84682935.50 | 0.245777E+10 | 0.719025E+09 | 28467.91 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.847902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234860E+09 | 0.00 | 0.00 | 0.02 |
February | 0.121908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.665904E+09 | 0.00 | 0.00 | 784134.21 | 0.00 | 0.00 | 0.299327E+09 | 0.00 | 0.02 |
April | 0.542168E+09 | 52919608.40 | 0.00 | 1196028.84 | 0.00 | 0.00 | 0.464435E+09 | 0.00 | 0.02 |
May | 0.168135E+09 | 0.107786E+09 | 0.00 | 1803237.61 | 0.00 | 0.00 | 0.616348E+09 | 0.00 | 0.02 |
June | 0.146026E+09 | 0.391158E+09 | 0.00 | 1124385.56 | 0.00 | 0.00 | 0.221681E+09 | 0.00 | 0.02 |
July | 0.00 | 0.640969E+09 | 0.00 | 579787.97 | 0.00 | 0.00 | 82212086.85 | 0.00 | 0.02 |
August | 0.00 | 0.537515E+09 | 0.00 | 910980.34 | 0.00 | 0.00 | 81275960.15 | 0.00 | 0.02 |
September | 0.199130E+09 | 86242515.08 | 0.00 | 2290848.21 | 0.00 | 0.00 | 0.527874E+09 | 0.00 | 0.02 |
October | 0.412313E+09 | 0.00 | 0.00 | 3334830.97 | 0.00 | 0.00 | 0.850448E+09 | 0.00 | 0.02 |
November | 0.831592E+09 | 0.00 | 0.00 | 840341.61 | 0.00 | 42457480.50 | 0.218989E+09 | 0.00 | 0.02 |
December | 0.634987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233478E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.566723E+10 | 0.181659E+10 | 0.00 | 12864575.32 | 0.00 | 0.510796E+09 | 0.336259E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.121908E+10 | 0.640969E+09 | 0.00 | 3334830.97 | 0.00 | 0.234860E+09 | 0.850448E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495188E+09 | 0.00 | 0.00 | 278217.26 | 0.00 | 0.326786E+11 | 0.211312E+09 | 0.00 | 0.40 |
February | 0.678032E+09 | 0.00 | 0.00 | 1365714.71 | 0.00 | 0.263151E+11 | 0.141103E+10 | 0.00 | 0.40 |
March | 0.115080E+10 | 0.00 | 0.00 | 14225859.90 | 0.00 | 0.116197E+11 | 0.696150E+10 | 0.00 | 0.40 |
April | 0.142290E+10 | 0.273207E+09 | 419618.20 | 39578047.35 | 51223699.35 | 0.395769E+10 | 0.111780E+11 | 42681.19 | 0.40 |
May | 0.221860E+10 | 0.248399E+09 | 681123.45 | 0.105759E+09 | 0.151691E+09 | 36000969.34 | 0.110351E+11 | 29051.02 | 0.40 |
June | 0.127174E+10 | 0.367484E+10 | 778477.95 | 73122158.64 | 0.494892E+09 | 8825192.81 | 0.518675E+10 | 27844.03 | 0.40 |
July | 0.112768E+10 | 0.564862E+10 | 1697483.15 | 52661928.90 | 0.122328E+10 | 2141340.35 | 0.167077E+10 | 21809.49 | 0.41 |
August | 0.156657E+10 | 0.393297E+10 | 5756541.24 | 63679778.47 | 0.911003E+09 | 3222169.22 | 0.305735E+10 | 152364.61 | 0.41 |
September | 0.183283E+10 | 0.703607E+09 | 2505382.70 | 71932098.68 | 0.116382E+09 | 0.203732E+09 | 0.958606E+10 | 95352.63 | 0.40 |
October | 0.132553E+10 | 0.00 | 0.00 | 35994925.09 | 0.00 | 0.227405E+10 | 0.147661E+11 | 0.00 | 0.40 |
November | 0.893527E+09 | 0.00 | 0.00 | 13321649.88 | 0.00 | 0.134585E+11 | 0.649551E+10 | 0.00 | 0.40 |
December | 0.798264E+09 | 0.00 | 0.00 | 459584.07 | 0.00 | 0.214503E+11 | 0.176963E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.147817E+11 | 0.144816E+11 | 11838626.70 | 0.472379E+09 | 0.294847E+10 | 0.112008E+12 | 0.717365E+11 | 369102.98 | 0.40 |
Minimum of Months | 0.495188E+09 | 0.00 | 0.00 | 278217.26 | 0.00 | 2141340.35 | 0.176963E+09 | 0.00 | 0.40 |
Maximum of Months | 0.221860E+10 | 0.564862E+10 | 5756541.24 | 0.105759E+09 | 0.122328E+10 | 0.326786E+11 | 0.147661E+11 | 152364.61 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22814770.15 | 0.00 | 0.00 | 28830.84 | 0.00 | 0.243085E+10 | 7840626.95 | 0.00 | 0.35 |
February | 33308864.26 | 0.00 | 0.00 | 375406.65 | 0.00 | 0.201304E+10 | 47652200.28 | 0.00 | 0.35 |
March | 59814304.88 | 0.00 | 0.00 | 1582787.68 | 0.00 | 0.115231E+10 | 0.242203E+09 | 0.00 | 0.36 |
April | 32162616.92 | 23954716.99 | 0.00 | 4701541.19 | 0.00 | 0.705781E+09 | 0.481159E+09 | 0.00 | 0.35 |
May | 11950760.49 | 29545007.85 | 4755.64 | 11278871.90 | 0.00 | 87417794.46 | 0.877015E+09 | 1665.25 | 0.36 |
June | 7834228.90 | 0.307492E+09 | 3819.01 | 8522736.15 | 0.00 | 37777348.74 | 0.428099E+09 | 2548.62 | 0.36 |
July | 1732824.31 | 0.506594E+09 | 192826.06 | 6733549.78 | 0.00 | 262517.82 | 0.201644E+09 | 11815.73 | 0.36 |
August | 0.00 | 0.357308E+09 | 266133.00 | 7930132.28 | 0.00 | 511971.47 | 0.337417E+09 | 13440.61 | 0.36 |
September | 15314608.23 | 60640960.92 | 8120.82 | 8820632.71 | 0.00 | 0.204729E+09 | 0.633388E+09 | 1336.58 | 0.36 |
October | 44917298.59 | 0.00 | 0.00 | 3532023.37 | 0.00 | 0.793654E+09 | 0.514673E+09 | 0.00 | 0.35 |
November | 49079875.79 | 0.00 | 0.00 | 701294.82 | 0.00 | 0.129992E+10 | 0.188392E+09 | 0.00 | 0.35 |
December | 34568651.87 | 0.00 | 0.00 | 90958.10 | 0.00 | 0.159447E+10 | 24357917.76 | 0.00 | 0.35 |
Annual Sum or Average | 0.313499E+09 | 0.128553E+10 | 475654.52 | 54298765.46 | 0.00 | 0.103207E+11 | 0.398384E+10 | 30806.79 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28830.84 | 0.00 | 262517.82 | 7840626.95 | 0.00 | 0.35 |
Maximum of Months | 59814304.88 | 0.506594E+09 | 266133.00 | 11278871.90 | 0.00 | 0.243085E+10 | 0.877015E+09 | 13440.61 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3550195.44 | 0.00 | 0.00 | 4280.06 | 0.00 | 0.245734E+10 | 354756.82 | 0.00 | 0.35 |
February | 16571144.65 | 0.00 | 0.00 | 79318.68 | 0.00 | 0.205911E+10 | 18368693.36 | 0.00 | 0.35 |
March | 68317729.29 | 0.00 | 0.00 | 629557.84 | 0.00 | 0.125100E+10 | 0.135792E+09 | 0.00 | 0.36 |
April | 92080713.39 | 22340088.47 | 25188.18 | 2870965.01 | 1582467.50 | 0.773679E+09 | 0.355030E+09 | 4166.20 | 0.35 |
May | 0.135937E+09 | 23119923.30 | 34213.09 | 8615553.53 | 6391725.56 | 95725673.66 | 0.747268E+09 | 2104.41 | 0.36 |
June | 83890548.94 | 0.274279E+09 | 211245.31 | 5734444.85 | 32956456.40 | 41719132.59 | 0.350833E+09 | 14977.51 | 0.36 |
July | 80073965.66 | 0.425664E+09 | 183849.75 | 4319243.31 | 80881893.22 | 301095.76 | 0.125654E+09 | 9795.69 | 0.36 |
August | 0.110221E+09 | 0.302422E+09 | 455475.89 | 4923529.90 | 54653041.95 | 617194.16 | 0.230057E+09 | 15076.22 | 0.36 |
September | 0.121100E+09 | 55425669.76 | 31064.38 | 5460927.55 | 5180984.28 | 0.233378E+09 | 0.502212E+09 | 5593.81 | 0.36 |
October | 97721367.96 | 0.00 | 0.00 | 1232260.69 | 0.00 | 0.937144E+09 | 0.320520E+09 | 0.00 | 0.35 |
November | 41171051.16 | 0.00 | 0.00 | 142926.82 | 0.00 | 0.142070E+10 | 75892160.21 | 0.00 | 0.35 |
December | 4342759.19 | 0.00 | 0.00 | 5930.32 | 0.00 | 0.164684E+10 | 2110717.64 | 0.00 | 0.35 |
Annual Sum or Average | 0.854977E+09 | 0.110325E+10 | 941036.60 | 34018938.56 | 0.181647E+09 | 0.109175E+11 | 0.286409E+10 | 51713.83 | 0.36 |
Minimum of Months | 3550195.44 | 0.00 | 0.00 | 4280.06 | 0.00 | 301095.76 | 354756.82 | 0.00 | 0.35 |
Maximum of Months | 0.135937E+09 | 0.425664E+09 | 455475.89 | 8615553.53 | 80881893.22 | 0.245734E+10 | 0.747268E+09 | 15076.22 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369911E+11 | 0.00 | 0.00 | 0.63 |
February | 0.181091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214442E+11 | 0.00 | 0.00 | 0.63 |
March | 0.295372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285187E+10 | 0.00 | 0.00 | 0.63 |
April | 0.275955E+11 | 0.00 | 0.00 | 0.00 | 0.301342E+09 | 0.446700E+09 | 0.00 | 0.00 | 0.63 |
May | 0.262629E+11 | 0.00 | 0.00 | 0.00 | 0.362209E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 0.154126E+11 | 0.433370E+09 | 0.00 | 513600.86 | 0.296612E+10 | 0.00 | 0.175907E+09 | 0.00 | 0.64 |
July | 0.906270E+10 | 0.856647E+09 | 0.00 | 205330.85 | 0.464482E+10 | 0.00 | 0.255591E+09 | 0.00 | 0.64 |
August | 0.126632E+11 | 0.504677E+09 | 0.00 | 79401.94 | 0.441466E+10 | 0.00 | 93173878.87 | 0.00 | 0.64 |
September | 0.233923E+11 | 5152509.40 | 0.00 | 74571.91 | 0.321067E+09 | 0.00 | 0.123926E+09 | 0.00 | 0.64 |
October | 0.329298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.253551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839784E+10 | 0.00 | 0.00 | 0.63 |
December | 0.187705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173771E+11 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.250038E+12 | 0.179985E+10 | 0.00 | 872905.56 | 0.130102E+11 | 0.875088E+11 | 0.648598E+09 | 0.00 | 0.63 |
Minimum of Months | 0.906270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.329298E+11 | 0.856647E+09 | 0.00 | 513600.86 | 0.464482E+10 | 0.369911E+11 | 0.255591E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3632024.72 | 0.00 | 0.00 | 11909.91 | 0.00 | 0.610951E+09 | 789567.89 | 0.00 | 0.35 |
February | 6190056.32 | 0.00 | 0.00 | 122795.75 | 0.00 | 0.509475E+09 | 7805282.03 | 0.00 | 0.35 |
March | 15677739.92 | 0.00 | 0.00 | 409477.03 | 0.00 | 0.310098E+09 | 37791643.46 | 0.00 | 0.36 |
April | 9978892.73 | 5988679.25 | 0.00 | 1373872.41 | 0.00 | 0.191296E+09 | 0.103302E+09 | 0.00 | 0.35 |
May | 5217320.97 | 7386908.31 | 214.43 | 2629517.05 | 0.00 | 57496637.50 | 0.181572E+09 | 734.45 | 0.36 |
June | 3226086.51 | 76849084.58 | 22285.27 | 1937227.70 | 0.00 | 26994179.45 | 88400891.86 | 3126.24 | 0.36 |
July | 433206.08 | 0.126656E+09 | 35849.95 | 1462061.98 | 0.00 | 108282.13 | 50589771.65 | 7968.91 | 0.36 |
August | 0.00 | 89310461.28 | 80462.85 | 1891339.27 | 0.00 | 123915.68 | 84449561.14 | 5845.00 | 0.36 |
September | 5336734.07 | 15154368.35 | 6606.61 | 1981324.07 | 0.00 | 81867931.75 | 0.126377E+09 | 1629.63 | 0.36 |
October | 15107782.49 | 0.00 | 0.00 | 961055.12 | 0.00 | 0.233174E+09 | 89951606.89 | 0.00 | 0.35 |
November | 10799838.64 | 0.00 | 0.00 | 185867.95 | 0.00 | 0.354263E+09 | 19274092.75 | 0.00 | 0.35 |
December | 7672409.90 | 0.00 | 0.00 | 20623.47 | 0.00 | 0.404840E+09 | 838746.65 | 0.00 | 0.35 |
Annual Sum or Average | 83272092.36 | 0.321345E+09 | 145419.11 | 12987071.71 | 0.00 | 0.278069E+10 | 0.791143E+09 | 19304.22 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 11909.91 | 0.00 | 108282.13 | 789567.89 | 0.00 | 0.35 |
Maximum of Months | 15677739.92 | 0.126656E+09 | 80462.85 | 2629517.05 | 0.00 | 0.610951E+09 | 0.181572E+09 | 7968.91 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 163170.73 | 0.00 | 0.00 | 915.57 | 0.00 | 0.615113E+09 | 35746.79 | 0.00 | 0.35 |
February | 2524776.42 | 0.00 | 0.00 | 34177.95 | 0.00 | 0.516652E+09 | 4320935.48 | 0.00 | 0.35 |
March | 12502871.24 | 0.00 | 0.00 | 185660.03 | 0.00 | 0.331715E+09 | 19530268.82 | 0.00 | 0.36 |
April | 23426157.21 | 5518831.76 | 4119.15 | 894417.61 | 463668.74 | 0.201454E+09 | 80140734.75 | 1357.93 | 0.35 |
May | 36853631.06 | 5710487.48 | 6367.36 | 1971780.50 | 1668935.58 | 53442687.84 | 0.154619E+09 | 1201.16 | 0.36 |
June | 21967126.99 | 68142926.94 | 39464.83 | 1385044.52 | 8680521.08 | 27946690.62 | 69245398.22 | 2576.27 | 0.36 |
July | 19867592.15 | 0.105458E+09 | 50519.80 | 1089408.80 | 21170733.87 | 42894.40 | 31587264.41 | 5730.04 | 0.36 |
August | 27724486.60 | 75109667.41 | 85136.67 | 1314891.78 | 14182553.69 | 98897.86 | 57316409.24 | 8937.22 | 0.36 |
September | 32079700.28 | 13741138.88 | 5841.40 | 1188210.92 | 1409180.16 | 86459077.00 | 95810686.41 | 4667.62 | 0.36 |
October | 24170539.60 | 0.00 | 0.00 | 440217.16 | 0.00 | 0.263312E+09 | 51231171.52 | 0.00 | 0.35 |
November | 9452476.70 | 0.00 | 0.00 | 84758.26 | 0.00 | 0.368013E+09 | 6926675.56 | 0.00 | 0.35 |
December | 579026.47 | 0.00 | 0.00 | 1515.33 | 0.00 | 0.412699E+09 | 44396.98 | 0.00 | 0.35 |
Annual Sum or Average | 0.211312E+09 | 0.273681E+09 | 191449.22 | 8590998.42 | 47575593.14 | 0.287695E+10 | 0.570808E+09 | 24470.24 | 0.36 |
Minimum of Months | 163170.73 | 0.00 | 0.00 | 915.57 | 0.00 | 42894.40 | 35746.79 | 0.00 | 0.35 |
Maximum of Months | 36853631.06 | 0.105458E+09 | 85136.67 | 1971780.50 | 21170733.87 | 0.615113E+09 | 0.154619E+09 | 8937.22 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 95278819.86 | 0.00 | 0.00 | 1100648.58 | 0.00 | 0.367922E+10 | 0.177932E+09 | 0.00 | 0.40 |
February | 0.119924E+09 | 0.00 | 0.00 | 2334266.65 | 0.00 | 0.294596E+10 | 0.295604E+09 | 0.00 | 0.40 |
March | 55031085.53 | 0.00 | 0.00 | 4545809.61 | 0.00 | 0.160994E+10 | 0.668845E+09 | 0.00 | 0.40 |
April | 35768661.20 | 38474206.00 | 0.00 | 7734722.79 | 0.00 | 0.968016E+09 | 0.954059E+09 | 0.00 | 0.40 |
May | 24091991.33 | 47453330.17 | 5673.41 | 14219688.33 | 0.00 | 0.139918E+09 | 0.140808E+10 | 4206.18 | 0.40 |
June | 11447198.72 | 0.493130E+09 | 137973.81 | 9475771.31 | 595624.45 | 43702455.73 | 0.709901E+09 | 15604.95 | 0.40 |
July | 2783127.82 | 0.813587E+09 | 364833.84 | 7032786.63 | 0.00 | 855654.18 | 0.327214E+09 | 28770.44 | 0.40 |
August | 0.00 | 0.574010E+09 | 306899.33 | 9955336.23 | 0.00 | 3114216.19 | 0.542423E+09 | 12126.59 | 0.40 |
September | 21317532.77 | 97374267.66 | 32666.16 | 13293956.18 | 0.00 | 0.219895E+09 | 0.113038E+10 | 5057.70 | 0.40 |
October | 42251615.15 | 0.00 | 0.00 | 10687611.32 | 0.00 | 0.720111E+09 | 0.140610E+10 | 0.00 | 0.40 |
November | 54396624.54 | 0.00 | 0.00 | 3560302.06 | 0.00 | 0.177950E+10 | 0.632908E+09 | 0.00 | 0.40 |
December | 30440287.66 | 0.00 | 0.00 | 1885107.60 | 0.00 | 0.241075E+10 | 0.212629E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.492731E+09 | 0.206403E+10 | 848046.54 | 85826007.29 | 595624.45 | 0.145210E+11 | 0.846607E+10 | 65765.84 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1100648.58 | 0.00 | 855654.18 | 0.177932E+09 | 0.00 | 0.40 |
Maximum of Months | 0.119924E+09 | 0.813587E+09 | 364833.84 | 14219688.33 | 595624.45 | 0.367922E+10 | 0.140808E+10 | 28770.44 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291620E+11 | 0.00 | 0.00 | 20290908.93 | 0.00 | 0.902372E+10 | 0.282076E+11 | 0.00 | 4.14 |
February | 0.121400E+11 | 0.00 | 0.00 | 26138526.59 | 0.00 | 0.173306E+11 | 0.262326E+11 | 0.00 | 4.24 |
March | 0.648612E+10 | 0.00 | 0.00 | 46006599.94 | 0.00 | 0.00 | 0.417725E+11 | 0.00 | 4.47 |
April | 0.169819E+10 | 0.447868E+09 | 0.00 | 59630452.00 | 2385219.55 | 0.00 | 0.428995E+11 | 0.00 | 4.75 |
May | 0.163653E+09 | 0.561289E+09 | 0.00 | 83563484.72 | 0.00 | 0.00 | 0.459049E+11 | 0.00 | 5.15 |
June | 7404333.92 | 0.584167E+10 | 0.00 | 70024050.59 | 0.00 | 0.00 | 0.286841E+11 | 0.00 | 5.49 |
July | 0.00 | 0.992374E+10 | 0.00 | 61486654.68 | 0.00 | 0.00 | 0.180568E+11 | 0.00 | 5.58 |
August | 6994877.83 | 0.866520E+10 | 0.00 | 70613021.41 | 324705.26 | 0.00 | 0.247841E+11 | 0.00 | 5.50 |
September | 0.297058E+09 | 0.502948E+09 | 0.00 | 79885582.22 | 169165.68 | 0.00 | 0.405056E+11 | 0.00 | 5.14 |
October | 0.138280E+10 | 0.00 | 0.00 | 59323104.17 | 0.00 | 0.00 | 0.502988E+11 | 0.00 | 4.68 |
November | 0.105033E+11 | 0.00 | 0.00 | 40380207.07 | 0.00 | 0.477094E+09 | 0.389988E+11 | 0.00 | 4.44 |
December | 0.177083E+11 | 0.00 | 0.00 | 28372180.15 | 0.00 | 0.00 | 0.329940E+11 | 0.00 | 4.17 |
Annual Sum or Average | 0.795559E+11 | 0.259427E+11 | 0.00 | 0.645715E+09 | 2879090.50 | 0.268314E+11 | 0.419339E+12 | 0.00 | 4.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20290908.93 | 0.00 | 0.00 | 0.180568E+11 | 0.00 | 4.14 |
Maximum of Months | 0.291620E+11 | 0.992374E+10 | 0.00 | 83563484.72 | 2385219.55 | 0.173306E+11 | 0.502988E+11 | 0.00 | 5.58 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260844E+11 | 0.00 | 0.00 | 28673926.45 | 0.00 | 0.908142E+10 | 0.353418E+11 | 0.00 | 4.41 |
February | 0.841440E+10 | 0.00 | 0.00 | 36207007.72 | 0.00 | 0.177122E+11 | 0.335295E+11 | 0.00 | 4.58 |
March | 0.251407E+10 | 0.00 | 0.00 | 60736956.62 | 0.00 | 0.00 | 0.502912E+11 | 0.00 | 4.89 |
April | 0.438907E+09 | 0.490738E+09 | 0.00 | 73482868.39 | 0.00 | 0.00 | 0.483247E+11 | 0.00 | 5.19 |
May | 14433166.19 | 0.611423E+09 | 0.00 | 95570467.50 | 0.00 | 0.00 | 0.500917E+11 | 0.00 | 5.60 |
June | 0.00 | 0.627903E+10 | 0.00 | 77686302.03 | 0.00 | 0.00 | 0.308857E+11 | 0.00 | 5.90 |
July | 0.00 | 0.106333E+11 | 0.00 | 66997485.24 | 0.00 | 0.00 | 0.192384E+11 | 0.00 | 5.96 |
August | 0.00 | 0.930298E+10 | 0.00 | 77657918.50 | 0.00 | 0.00 | 0.264208E+11 | 0.00 | 5.89 |
September | 12351592.46 | 0.542567E+09 | 0.00 | 91010118.69 | 0.00 | 0.00 | 0.441629E+11 | 0.00 | 5.56 |
October | 0.370279E+09 | 0.00 | 0.00 | 74090161.27 | 0.00 | 0.00 | 0.563364E+11 | 0.00 | 5.13 |
November | 0.760665E+10 | 0.00 | 0.00 | 53363845.04 | 0.00 | 0.441568E+09 | 0.461966E+11 | 0.00 | 4.83 |
December | 0.124606E+11 | 0.00 | 0.00 | 39438865.21 | 0.00 | 0.00 | 0.420959E+11 | 0.00 | 4.50 |
Annual Sum or Average | 0.579161E+11 | 0.278601E+11 | 0.00 | 0.774916E+09 | 0.00 | 0.272352E+11 | 0.482915E+12 | 0.00 | 5.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28673926.45 | 0.00 | 0.00 | 0.192384E+11 | 0.00 | 4.41 |
Maximum of Months | 0.260844E+11 | 0.106333E+11 | 0.00 | 95570467.50 | 0.00 | 0.177122E+11 | 0.563364E+11 | 0.00 | 5.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.473566E+10 | 0.00 | 0.00 | 97473794.98 | 0.00 | 0.903093E+10 | 0.796423E+11 | 0.00 | 19.68 |
February | 0.457327E+10 | 0.00 | 0.00 | 87720692.68 | 0.00 | 0.119554E+11 | 0.606483E+11 | 0.00 | 20.36 |
March | 0.00 | 0.00 | 0.00 | 0.113834E+09 | 0.00 | 0.00 | 0.736636E+11 | 0.00 | 22.12 |
April | 0.00 | 0.865302E+09 | 0.00 | 0.113384E+09 | 0.00 | 0.00 | 0.648155E+11 | 0.00 | 22.69 |
May | 0.00 | 0.103970E+10 | 0.00 | 0.132253E+09 | 0.00 | 0.00 | 0.602479E+11 | 0.00 | 23.55 |
June | 0.00 | 0.947424E+10 | 0.00 | 99693553.10 | 0.00 | 0.00 | 0.345025E+11 | 0.00 | 23.88 |
July | 0.00 | 0.150322E+11 | 0.00 | 83102880.99 | 0.00 | 0.00 | 0.192634E+11 | 0.00 | 24.00 |
August | 0.00 | 0.134421E+11 | 0.00 | 97939490.09 | 0.00 | 0.00 | 0.267921E+11 | 0.00 | 23.91 |
September | 0.00 | 0.931842E+09 | 0.00 | 0.127493E+09 | 0.00 | 0.00 | 0.535870E+11 | 0.00 | 23.41 |
October | 0.00 | 0.00 | 0.00 | 0.116193E+09 | 0.00 | 0.00 | 0.767094E+11 | 0.00 | 22.62 |
November | 0.673787E+09 | 0.00 | 0.00 | 0.105519E+09 | 0.00 | 0.152982E+10 | 0.720520E+11 | 0.00 | 21.56 |
December | 77766232.20 | 0.00 | 0.00 | 0.107804E+09 | 0.00 | 0.00 | 0.778377E+11 | 0.00 | 20.64 |
Annual Sum or Average | 0.100605E+11 | 0.407853E+11 | 0.00 | 0.128241E+10 | 0.00 | 0.225161E+11 | 0.699762E+12 | 0.00 | 22.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 83102880.99 | 0.00 | 0.00 | 0.192634E+11 | 0.00 | 19.68 |
Maximum of Months | 0.473566E+10 | 0.150322E+11 | 0.00 | 0.132253E+09 | 0.00 | 0.119554E+11 | 0.796423E+11 | 0.00 | 24.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211776E+11 | 0.00 | 0.00 | 1.17 |
February | 0.676135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126663E+11 | 0.00 | 0.00 | 1.17 |
March | 0.123452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356350E+10 | 0.00 | 0.00 | 1.18 |
April | 0.132778E+11 | 59713514.45 | 0.00 | 22923.07 | 88298155.16 | 0.456336E+09 | 39483534.83 | 0.00 | 1.17 |
May | 0.128325E+11 | 72882781.24 | 0.00 | 79207.61 | 0.106214E+09 | 0.00 | 67115229.41 | 0.00 | 1.18 |
June | 0.718359E+10 | 0.139560E+10 | 0.00 | 958801.29 | 0.384394E+09 | 0.00 | 0.473508E+09 | 0.00 | 1.21 |
July | 0.400045E+10 | 0.214919E+10 | 0.00 | 1265065.00 | 0.676701E+09 | 0.00 | 0.576520E+09 | 0.00 | 1.21 |
August | 0.570198E+10 | 0.163618E+10 | 0.00 | 1382426.76 | 0.858762E+09 | 0.00 | 0.562869E+09 | 0.00 | 1.20 |
September | 0.111694E+11 | 0.147953E+09 | 0.00 | 1287511.56 | 24606943.94 | 0.00 | 0.381008E+09 | 0.00 | 1.19 |
October | 0.161743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
November | 0.108528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572583E+10 | 0.00 | 0.00 | 1.17 |
December | 0.474044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130144E+11 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 0.107408E+12 | 0.546151E+10 | 0.00 | 4995935.29 | 0.213898E+10 | 0.566039E+11 | 0.210051E+10 | 0.00 | 1.18 |
Minimum of Months | 0.236836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Maximum of Months | 0.161743E+11 | 0.214919E+10 | 0.00 | 1382426.76 | 0.858762E+09 | 0.211776E+11 | 0.576520E+09 | 0.00 | 1.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:46:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.218786E+12 | 0.305856E+11 | 0.386703E+12 | 0.149764E+13 | 0.161128E+12 |
February | 0.244989E+12 | 0.235888E+11 | 0.301561E+12 | 0.117980E+13 | 0.124681E+12 |
March | 0.410514E+12 | 0.202322E+11 | 0.264725E+12 | 0.108013E+13 | 0.101094E+12 |
April | 0.481817E+12 | 0.141313E+11 | 0.184832E+12 | 0.769063E+12 | 0.173868E+12 |
May | 0.550133E+12 | 0.832114E+10 | 0.107065E+12 | 0.470656E+12 | 0.307100E+12 |
June | 0.573737E+12 | 0.221209E+10 | 0.278234E+11 | 0.140891E+12 | 0.675942E+12 |
July | 0.556927E+12 | -656248166.0 | -0.103559E+11 | -0.181754E+11 | 0.903454E+12 |
August | 0.502869E+12 | 0.717432E+09 | 0.597047E+10 | 0.620417E+11 | 0.799634E+12 |
September | 0.346567E+12 | 0.749923E+10 | 0.970344E+11 | 0.438243E+12 | 0.394030E+12 |
October | 0.257184E+12 | 0.143144E+11 | 0.188324E+12 | 0.806723E+12 | 0.131020E+12 |
November | 0.158976E+12 | 0.196778E+11 | 0.260160E+12 | 0.104912E+13 | 0.107344E+12 |
December | 0.114044E+12 | 0.269920E+11 | 0.346729E+12 | 0.138060E+13 | 0.120114E+12 |
Annual Sum or Average | 0.441654E+13 | 0.167616E+12 | 0.216057E+13 | 0.885674E+13 | 0.399941E+13 |
Minimum of Months | 0.114044E+12 | -656248166.0 | -0.103559E+11 | -0.181754E+11 | 0.101094E+12 |